Skip to main content

Full text of "Minnesota Residential Code"

See other formats


The 2007 Minnesota State Building Code 



Minnesota Rules, Chapter 1309 
Adoption of the 2006 International Residential Code 



1309.0010 adoption OF 

international residential 

code (IRC) BY reference. 

Subpart 1. Generally. The 2006 edition 
of the International Residential Code (IRC) as 
promulgated by the International Code 
Council (ICC), Falls Church, Virginia, is 
incorporated by reference and made part of 
the Minnesota State Building Code except as 
qualified by the applicable provisions in 
Minnesota Rules, chapter 1300, and as 
amended in this chapter. The IRC is not 
subject to frequent change and a copy of the 
IRC, with amendments for use in Minnesota, 
is available in the office of the commissioner 
of labor and industry. Portions of this chapter 
reproduce text and tables from the IRC. The 
IRC is copyright 2006 by the ICC. All rights 
reserved. 

Subp. 2. Mandatory chapters. The 
2006 IRC Chapters 2 through 10 and 43 must 
be administered by any municipality that has 
adopted the code, except as qualified by the 
applicable provisions in Minnesota Rules, 
chapter 1300, and as amended by this chapter. 

Subp. 3. Replacement chapters. The 
following 2006 IRC chapters are being 
deleted and replaced with the provisions listed 
below: 

A. Chapter 1 of the 2006 IRC and any 
references to code administration in this code 
are deleted and replaced with Minnesota 
Rules, chapter 1300, Minnesota 
Administration Code. 

B. Chapter 11 of the 2006 IRC and any 
references to energy in this code are deleted 
and replaced with Minnesota Statutes, section 
16B.617. 



C. Chapters 12 through 24 of the 2006 
IRC and any references to mechanical matters 
in this code are deleted and replaced with 
Minnesota Rules, chapter 1346, Minnesota 
Mechanical Code. 

D. Chapters 25 through 32 of the 2006 
IRC and any references to plumbing in this 
code are deleted and replaced with Minnesota 
Rules, chapter 4715, Minnesota Plumbing 
Code. 

E. Chapters 33 through 42 of the 2006 
IRC and references to electrical matters in this 
code, other than Section R3 13 Smoke Alarms, 
are deleted and replaced with Minnesota 
Rules, chapter 1315, Minnesota Electrical 
Code. 

Subp. 4. Seismic or earthquake 

provisions. Any seismic or earthquake 
provisions and any references to them are 
deleted and are not included in this code. 

Subp. 5. Flood hazard or floodproofing 
provisions. Any flood hazard or 

floodproofing provisions in the IRC, and any 
reference to those provisions, are deleted in 
their entirety. Requirements for 

floodproofing are located in chapter 1335, 
floodproofing regulations. 

Subp. 6. Elevator and platform lift 
provisions. Any elevator and platform lift 
provisions in the IRC and any reference to 
those provisions are deleted in their entirety. 
Requirements for elevators or platform lifts 
are located in chapter 1307, elevators and 
related devices. 

1309.0020 REFERENCES TO OTHER 
ICC CODES. 



236 



The 2007 Minnesota State Building Code 



Subpart 1. Generally. References to 
other codes and standards promulgated by the 
ICC in the 2006 IRC are modified in subparts 
2to II. 

Subp. 2. Building code. References to 
the International Building Code in this code 
mean the Minnesota Building Code, adopted 
pursuant to Minnesota Rules, chapter 1305, 
and Minnesota Statutes, section I6B.6I, 
subdivision I. 

Subp. 3. Residential code. References to 
the IRC in this code mean the Minnesota 
Residential Code, adopted under Minnesota 
Rules, chapter 1309, and Minnesota Statutes, 
section I6B.6I, subdivision I. 

Subp. 4. Electrical code. References to 
the ICC Electrical Code in this code mean the 
Minnesota Electrical Code, Minnesota Rules, 
chapter 1315, adopted under Minnesota 
Statutes, section 326.243. 

Subp. 5. Fuel gas code. References to 
the International Fuel Gas Code in this code 
mean the Minnesota Mechanical Code, 
Minnesota Rules, chapter 1346, adopted 
under Minnesota Statutes, section I6B.6I, 
subdivision I. 

Subp. 6. Mechanical code. References 
to the International Mechanical Code in this 
code mean the Minnesota Mechanical Code, 
Minnesota Rules, chapter 1346, adopted 
under Minnesota Statutes, section I6B.6I, 
subdivision I. 



Minnesota Pollution Control Agency's 
minimum standards and criteria for individual 
sewage treatment systems in Minnesota 
Rules, chapter 7080, adopted under 
Minnesota Statutes, chapters I03F, I03G, 
115, and 116. 

Subp. 9. Energy conservation code. 

References to the International Energy 
Conservation Code in this code mean the 
Minnesota Energy Code, adopted under 
Minnesota Statutes, section I6B.6I7. 

Subp. 10. Property maintenance code. 

References to the International Property 
Maintenance Code in this code do not apply. 

Subp. II. Accessibility code. References 

to accessibility in this code mean the 

Minnesota Accessibility Code, Minnesota 
Rules, chapter 1 34 1. 

1309.0030 ADMINISTRATIVE 

PROCEDURE CRITERIA. 

Procedures relating to the administration 
and enforcement of this code under 
Minnesota Statutes, section I6B.57, are 
contained in Minnesota Rules, chapter 1300, 
Minnesota Administration Code. Minnesota 
Rules, chapter 1300, governs the application 
of this code. 

1309.0040 VIOLATION. 

A violation of this code is a misdemeanor 
under Minnesota Statutes, section I6B.69. 



Subp. 7. Plumbing code. References to 
the International Plumbing code in this code 
mean the Minnesota Plumbing Code, 
Minnesota Rules, chapter 4715, adopted 
under Minnesota Statutes, section I6B.6I, 
subdivisions I and 2. 

Subp. 8. Private sewage disposal code. 

References to the International Private 
Sewage Disposal Code in this code mean the 



1309.0100 CHAPTER 

ADMINISTRATION. 



1, 



Subpart I. IRC chapter 1. IRC chapter I 
is deleted and replaced with the following: 

CHAPTER I 

ADMINISTRATION 



237 



The 2007 Minnesota State Building Code 



This code shall be administered according to 
Minnesota Rules, chapter 1300. 

Subp. 2. Existing buildings and 

structures. Additions, alterations, or repairs 
to existing buildings and structures meeting 
the scope of the International Residential 
Code shall be exempt from Minnesota Rules, 
chapter 1311, Minnesota Conservation Code 
for Existing Buildings. 

Additions, alterations, or repairs to 
existing one and two family dwellings 
including townhouses may be made without 
requiring the existing building or structure to 
comply with all the requirements of this code 
provided that any addition or alteration 
conforms to this code. Repairs to existing 
buildings or structures may be made that are 
nonstructural and do not adversely affect any 
structural member or required fire resistive 
element with the same methods and materials 
of which the building or structure is 
constructed. 

Exception: The installation or 

replacement of glass shall be as required 
for new installations in accordance with 
IRC Section R308. 

1309.0201 SECTION R201, GENERAL. 

IRC Section R201.4 is amended to read as 
follows: 

R201.4 Terms not defined. Where terms are 
not defined through the methods authorized 
by this chapter, the Merriam-Webster 
Collegiate Dictionary, available at www.m- 
w.com, shall be considered as providing 
ordinarily accepted meanings. The dictionary 
is incorporated by reference, is subject to 
frequent change, and is available through the 
Minitex interlibrary loan system. 



1309.0202 
DEFINITIONS. 



SECTION 



R202, 



Subpart 1. Modifications. IRC Section 
R202 is amended by modifying the following 
definitions: 

DWELLING. 

SINGLE FAMILY. Any building that 
contains one dwelling unit used, intended, 
or designed to be built, used, rented, 
leased, let or hired out to be occupied, or 
occupied for living purposes. 

TWO FAMILY. Any building that 
contains two separate dwelling units with 
separation either horizontal or vertical on 
one lot that is used, intended, or designed 
to be built, used, rented, leased, let or 
hired out to be occupied, or occupied for 
living purposes. 

TOWNHOUSE. A single family 

dwelling unit constructed in a group of 
two or more attached units in which each 
unit extends from the foundation to the 
roof and having open space on at least two 
sides of each unit. Each single family 
dwelling unit shall be considered to be a 
separate building. Separate building 
service utilities shall be provided to each 
single family dwelling unit when required 
by other chapters of the State Building 
Code. 

Subp. 2. Additional definitions. IRC 
Section R202 is amended by adding the 
following definitions: 

CONNECTOR. A device for fastening 

together two or more pieces, members, or 

parts, including anchors, fasteners, and wall 

ties. 

CRAWL SPACE. Areas or rooms with less 

than 7 feet (2134 mm) ceiling height 

measured to the finished floor or grade below. 

DAMPPROOFING. Treatment of a surface 
or structure located below grade to resist the 



238 



The 2007 Minnesota State Building Code 



passage of water in liquid form, in the 
absence of hydrostatic pressure. 

FASTENER. A device for holding together 
two or more pieces, parts, or members. 

FLASHING. Approved corrosion resistive 
material provided in such a manner as to 
deflect and resist entry of water into the 
construction assembly. 

KICK OUT FLASHING. Flashing used to 
divert water where the lower portion of a 
sloped roof stops within the plane of an 
intersecting wall cladding. 

OCCUPANCY CLASSIFICATIONS 

IRC 1 Single family dwelling 
IRC 2 Two family dwellings 
IRC 3 Townhouses 
IRC 4 Accessory structures: 

a. Garages; 

b. Storage sheds; and 

c. Similar structures. 

PAN FLASHING. A type of corrosion 
resistive flashing that is integrated into the 
building envelope at the base of a window or 
door rough opening that diverts incidental 
water to the exterior surface of a weather 
resistive barrier. 

STAIR. A change in elevation, consisting of 
one or more risers. 

STORY ABOVE GRADE PLANE. Any 

story having its finished floor surface entirely 
above grade plane, except a basement, shall 
be considered as a story above grade where 
the finished surface of the floor above the 
basement is: 

1. more than 6 feet (1829 mm) above 
grade plane; 



2. more than 6 feet (1829 mm) above the 
finished ground level for more than 50 
percent of the total building perimeter; or 

3. more than 12 feet (3658 mm) above 
the finished ground level at any point. 

WATERPROOFING. Treatment of a 
surface or structure located below grade to 
resist the passage of water in liquid form, 
under hydrostatic pressure and bridges 
nonstructural cracks. 



1309.0300 SECTION 

CLASSIFICATION. 



R300, 



IRC Chapter 3 is amended by adding a 
new section to read as follows: 

R300.1 Occupancy classification. Structures 
or portions of structures shall be classified 
with respect to occupancy in one or more of 
the groups in accordance with Table R300.1. 

Table R300.1 

Occupancy Classifications 



IRC-1 
IRC-2 
IRC-3 
IRC-4 



Dwelling, single family 
Dwelling, two family 
Townhouse 
Accessory structures 



1309.0301 SECTION R301, DESIGN 
CRITERIA. 

Subpart 1. IRC Section R301.1.4. IRC 

Section R301.1 is amended by adding a 
section to read as follows: 

R301.1.4 Automatic sprinkler systems 
(general). All IRC 2 and IRC 3 buildings 
shall be provided with an automatic sprinkler 
system. 

Exception: 



239 



The 2007 Minnesota State Building Code 



IRC 2 and IRC 3 buildings less than or 
equal to 9,250 square feet of floor area. 
Floor area shall include all floors, 
basements, and garages. 

R301.1.4.1 State licensed facilities. IRC 1, 

IRC 2, and IRC 3 buildings containing 
facilities licensed by the state of Minnesota 
shall be provided with a fire suppression 
system as required by the applicable licensing 
provisions or this section, whichever is more 
restrictive. 

R301. 1.4.2 Installation requirements. 

Where an automatic sprinkler system is 
required in an IRC 2 and IRC 3 building, it 
shall be installed in accordance with NFPA 
13D 2002 edition and the following: 

Attached garages are required to have 
automatic sprinklers with a minimum of one 
dry head, located within five lineal feet of 
each door installed in the common wall 



separating the dwelling unit and the attached 
garage. 

Attached covered patios, covered decks, 
covered porches, and similar structures are 
required to have automatic sprinklers with a 
minimum of one dry head for every 20 lineal 
feet of common wall between the dwelling 
unit and the covered patios, covered decks, 
covered porches, and similar structures. 

Exception: 

Attached roofs of covered patios, covered 
decks, covered porches, and similar 
structures that do not exceed 40 square 
feet of floor area. 

For the purposes of this section, fire 
resistance rated floor, wall, or ceiling 
assemblies separating dwelling units of IRC 2 
and IRC 3 buildings shall not constitute 
separate buildings. 



Subp. 2. Table R301.2(l). IRC Table R301.2(l) is amended to read as follows: 

Table R301.2(l) 
Climatic and Geographic Design Criteria 



Roof Snow Wind Speed'^ (mph) Weathering^ 
Load'^ 
p^O.7 X pg 90 Severe 



Subject to Damage From 
Frost Line Depth^ Flood Hazards 

See M.R. chapter See M.R. chapter 
1303 1335 



For SI: I pound per square foot = 0.0479 kPa ,1 mile per hour = 1.609 km/h 

a. Weathering may require a higher strength concrete or grade of masonry than necessary to 
satisfy the structural requirement of this code. The grade of masonry units shall be determined 
from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216, or C 652. 

b. The frost line depth may require deeper footings than indicated in Figure R403. 1(1) 

c. Wind exposure category shall be determined on a site specific basis in accordance with 
Section R301.2. 1.4. 

d. The ground snow loads to be used in determining the design snow loads for buildings and 
other structures are given in Minnesota Rules, chapter 1303. 



240 



The 2007 Minnesota State Building Code 



Subp. 3. Figure R301.2(5). IRC Figure 
R30 1.2(5), Ground Snow Loads, Pg, for the 
United States (Ib/ft^), is deleted in its entirety. 

Subp. 4. Table R301.5. IRC Table 
R301.5 is amended to read as follows: 

Table R30 1.5 

Minimum Uniformly Distributed Live Loads 
(in pounds per square foot) 



Use 
Attics with limited storage^'^'^ 
Attics without storage^ 
Decks' 

Exterior balconies 
Fire escapes 

Guardrails and handrails'^ 
Guardrails in fill components^ 
Passenger vehicle garages^ 
Rooms other than sleeping rooms 
Sleeping rooms 
Stairs 



Live 
Load 

20 

10 

40 

60 

40 
200^ 

50^ 

50' 

40 

30 

40'^ 



For SI: 1 pound per square foot = 0.0479 
kPa, 1 square inch = 645 mm^ , 1 pound = 

4.45 N. 

a. Elevated garage floors shall be capable of 
supporting a 2,000 pound load applied over a 
20 square inch area. 

b. Attics without storage are those where the 
maximum clear height between joist and 
rafter is less than 42 inches, or where there 
are not two or more adjacent trusses with the 
same web configuration capable of containing 
a rectangle 42 inches high by 2 feet wide, or 
greater, located within the plane of the truss. 
For attics without storage, this live load need 
not be assumed to act concurrently with any 
other live load requirements. 

c. Individual stair treads shall be designed 
for the uniformly distributed live load or a 
300 pound concentrated load acting over an 
area of four square inches, whichever 
produces the greater stresses. 



d. A single concentrated load applied in any 
direction at any point along the top. 

e. See Section R502.2.1 for decks attached 
to exterior walls. 

f Guard in fill components (all those except 
the handrail), balusters and panel fillers shall 
be designed to withstand a horizontally 
applied normal load of 50 pounds on an area 
equal to one square foot. This load need not 
be assumed to act concurrently with any other 
live load requirement. 

g. For attics with limited storage and 
constructed with trusses, this live load need 
be applied only to those portions of the 
bottom chord where there are two or more 
adjacent trusses with the same web 
configuration capable of containing a 
rectangle 42 inches high or greater by 2 feet 
wide or greater, located within the plane of 
the truss. The rectangle shall fit between the 
top of the bottom chord and the bottom of any 
other truss member, provided that each of the 
following criteria is met: 

1. The attic area is accessible by a pull 
down stairway or framed opening in 
accordance with Section R807.1; 

2. The truss has a bottom chord pitch less 
than 2: 12; and 

3. Required insulation depth is less than 
the bottom chord member depth. 

The bottom chords of trusses meeting the 
above criteria for limited storage shall be 
designed for the greater of the actual imposed 
dead load or ten pounds per square foot, 
uniformly distributed over the entire span, 
h. Attic spaces served by a fixed stair shall 
be designed to support the minimum live load 
specified for sleeping rooms, 
i. Glazing used in handrail assemblies and 
guards shall be designed with a safety factor 
of 4. The safety factor shall be applied to 
each of the concentrated loads applied to the 
top of the rail, and to the load on the in fill 
components. These loads shall be determined 
independent of one another, and loads are 
assumed not to occur with any other live load. 



241 



The 2007 Minnesota State Building Code 



1309.0302 SECTION R302, EXTERIOR 
WALL LOCATION. 

IRC Section R302.1 is amended to read as 
follows: 

R302.1 Exterior walls. Construction, 
projections, openings, and penetrations of 
exterior walls of dwellings and accessory 
buildings shall comply with Table 302.1. 
These provisions shall not apply to walls, 
projections, openings, or penetrations in walls 
that are perpendicular to the line used to 
determine the fire separation distance. 



Projections beyond the exterior shall not 
extend more than 12 inches (305 mm) into 
areas where openings are prohibited. 

Exceptions: 

1. Detached garages accessory to a 
dwelling located within 2 feet (610 mm) 
of a lot line are permitted to have eave 
projections not exceeding 4 inches (103 
mm). 

2. Foundation vents installed in 
compliance with this code are permitted. 



Table R302.1 
Exterior Walls 



Walls 



Exterior Wall Element 

(Fire-resistance rated) 

(Not fire-resistance 
rated) 



Minimum Fire- 
Resistance Rating 
1 hour with exposure 
from both sides 



hours 



Minimum Fire 
Separation Distance 

Ofeet 



5 feet 



Projections 



Openings 



Penetrations 



(Fire-resistance rated) 

(Not fire-resistance 
rated) 

Not allowed 
25% Maximum of 
Wall Area 
Unlimited 



All 



1 hour on the 




underside^ 


2 feet ** 


hours 


5 feet 


N/A 


less than 3 feet 


hours 


3 feet 


hours 


5 feet 


Comply with Section 




R317.3 


less than 5 feet 


None required 


5 feet 



N/A= Not Applicable 

^ 1 hour on the underside equates to one layer of 5/8" type X gypsum sheathing. Openings are 

not allowed. 

** ICC Errata, 9-12-2006 



242 



The 2007 Minnesota State Building Code 



1309.0305 SECTION R305, CEILING 
HEIGHT. 

IRC Section R305.1 is amended to read as 
follows: 



and shall comply with the provisions of this 
section for garages. 

Subp. 3. IRC Section R309.6. IRC 

Section R309.6 is amended to read as follows: 



R305.1 Minimum height. Habitable rooms, 
hallways, corridors, bathrooms, toilet rooms, 
and basements shall have a ceiling height of 
not less than 7 feet (2134 mm). The required 
height shall be measured from the finish floor 
to the lowest projection from the ceiling. 
Areas or rooms with ceiling heights less than 
7 feet (2134 mm) are considered crawl 
spaces. 

Exceptions: 

1. Beams and girders spaced not less 
than 4 feet (1219 mm) on center may 
project not more than 6 inches (152 mm) 
below the required ceiling height. 

2. Not more than 50 percent of the 
required floor area of a room or space is 
permitted to have a sloped ceiling less 
than 7 feet (2134 mm) in height with no 
portion of the required floor area less than 
5 feet (1524 mm) in height. 

1309.0309 SECTION R309, GARAGES 
AND CARPORTS. 

Subpart 1. IRC Section R309.3. IRC 

Section R309.3 is amended to read as follows: 

R309.3 Floor surface. Garage floor surfaces 
may be concrete, asphalt, sand, gravel, 
crushed rock, or natural earth. 

Subp. 2. IRC Section R309.4. IRC 

Section R309.4 is amended to read as follows: 

R309.4 Carports. Carports shall be open on 
at least two sides. Carport floor surfaces may 
be concrete, asphalt, sand, gravel, crushed 
rock, or natural earth. Carports not open on at 
least two sides shall be considered a garage 



R309.6 Automatic garage door opening 
systems. All automatic garage door opening 
systems that are installed, serviced, or 
repaired for garages serving residential 
buildings must comply with the provisions of 
Minnesota Statutes, sections 325F.82 and 
325F.83. 

1309.0310 SECTION R310, EMERGENCY 
ESCAPE AND RESCUE OPENINGS. 

IRC Section R3I0.1 is amended to read as 
follows: 

R310.1.5 Replacement windows. 

Replacement windows installed in buildings 
meeting the scope of the International 
Residential Code shall be exempt from the 
requirements of Sections R310.1, R310.1.1, 
R3I0.1.2, and R310.1.3 if the replacement 
window meets the following conditions: 

1. The replacement window is the 
manufacturer's largest standard size window 
that will fit within the existing frame or 
existing rough opening. The replacement 
window shall be permitted to be of the same 
operating style as the existing window or a 
style that provides for a greater window 
opening area than the existing window; 

2. The rooms or areas are not used for 
any Minnesota state licensed purpose 
requiring an egress window; and 

3. The window is not required to be 
replaced pursuant to a locally adopted rental 
housing or rental licensing code. 

1309.0311 SECTION R311, MEANS OF 
EGRESS. 



243 



The 2007 Minnesota State Building Code 



R31 1.4.3 Landings at doors. Except as 
provided in this section, there shall be a floor 
or landing on each side of each exterior door. 
The width of the landing shall not be less than 
the door served. The landing shall have a 
minimum dimension of 36 inches (9114 mm) 
measured in the direction of travel. 

R31 1.4.3.1 Landings at the exterior exit 
door required by Section R31 1.4.1. 

1. The floor or landing at the exit door 
required by Section R31 1.4.1 shall not be 
more than 1.5 inches (38 mm) below the top 
of the threshold, regardless of door swing. 

2. The exterior landing shall be up to 7 
3/4 inches (196 mm) below the top of the 
threshold, provided the door, other than an 
exterior storm or screen door, does not swing 
over the exterior landing. 

R31 1.4.3.2 Landings or floors at exterior 
doors other than those required by Section 
R311.4.1. 

1 . The exterior landing shall be permitted 
to be no greater than 7 3/4 inches (196 mm) 
below the top of the threshold, provided the 
door, other than an exterior storm or screen 
door, does not swing over the exterior 
landing. 

2. Landings in this subsection are not 
required for the exterior side of a door when a 
stairway that is less than 30 inches (762 mm) 
in height is located on the exterior side of the 
door. The stairway height shall be measured 
vertically from the interior floor surface to the 
finished grade. 

3 . An exterior landing is not required at a 
doorway when only a storm or screen door is 
installed which does not swing over the 
exterior landing. 

1309.0312 Repealed 



1309.0313 SMOKE ALARMS. 

IRC Section R3 13.2.1 is amended as 
follows: 

R313.2.1 Alterations, repairs, or additions. 

When alterations, repairs, or additions 
requiring a permit occur, or when one or more 
sleeping rooms are added or created in 
existing dwellings, the individual dwelling 
unit shall be equipped with smoke alarms 
located as required for new dwellings, and the 
smoke alarms shall be interconnected and 
hardwired. 

Exceptions: 

1. Interconnection and hardwiring of 
smoke alarms in existing areas shall not 
be required to be hardwired where the 
alterations or repairs do not result in the 
removal of interior wall or ceiling finishes 
exposing the structure. 

2. Work on the exterior surfaces of 
dwellings, such as the replacement of 
roofing or siding are exempt from the 
requirements of this section. 

3. Permits involving alterations or 
repairs to plumbing, electrical, and 
mechanical are exempt from the 
requirements of this section. 



1309.0314 
PLASTIC. 



SECTION R314, FOAM 



IRC Section R3 14.5. 11 
read as follows: 



is amended to 



R314.5.11 Sill plate and headers. Foam 
plastic shall be permitted to be spray applied 
to a sill plate and header (rim joist) without 
thermal barrier subject to all of the following: 

1 . The maximum thickness of the foam 
plastic shall not exceed 5 1/2 inches (139.5 
mm). 



244 



The 2007 Minnesota State Building Code 



2. The foam plastic shall have a flame 
spread index of 25 or less and an 
accompanying smoke developed index of 450 
or less when tested in accordance with ASTM 
E84. 

1309.0315 Repealed 

1309.0316 Repealed 

1309.0317 SECTION R317, DWELLING 
UNIT SEPARATION. 

Subpart 1. IRC Section R317.1. IRC 

Section R317.1 is amended to read as follows: 



R317.1.1 Supporting construction. When 
floor assemblies are required to be fire 
resistance rated by Section R317.1, the 
supporting construction of such assemblies 
shall have an equal or greater fire resistive 
rating. 

Subp. 2. IRC Section 317.2. IRC 

Section 317.2 is amended to read as follows: 

R317.2 Townhouses. Each townhouse shall 
be considered a separate building and shall be 
separated by fire resistance rated wall 
assemblies meeting the requirements of 
Section R302 for exterior walls. 



R317.1 Two family dwellings. Dwelling 
units in two family dwellings shall be 
separated from each other by wall and/or floor 
assemblies having not less than 1 hour fire 
resistance rating when tested in accordance 
with ASTM E 1 19. Fire resistance rated floor 
ceiling and wall assemblies shall extend to 
and be tight against the exterior wall, and wall 
assemblies shall extend to and be tight against 
the exterior wall, and wall assemblies shall 
extend to the underside of the roof sheathing. 

Exceptions: 

1. A fire resistance rating of 1/2 hour 
shall be permitted in buildings equipped 
throughout with an automatic sprinkler 
system installed in accordance with NFPA 
13. 

2. Wall assemblies need not extend 
through attic spaces when the ceiling is 
protected by not less than 5/8 inch (15.9 
mm) type X gypsum board and an attic 
draftstop constructed as specified in 
Section R502.12.I is provided above and 
along the wall assembly separating the 
dwellings. The structural framing 
supporting the ceiling shall also be 
protected by not less than 1/2 inch (12.7 
mm) gypsum board or equivalent. 



Exception: A common 2 hour fire 
resistance rated wall is permitted for 
townhouses if such walls do not contain 
plumbing or mechanical equipment, ducts 
or vents in the cavity of the common wall. 
Electrical installations shall be installed in 
accordance with chapters 33 through 42. 
Penetrations of electrical outlet boxes 
shall be in accordance with Section 
R317.3. 

R3 17.2.1 Continuity. The fire resistance 
rated wall or assembly separating townhouses 
shall be continuous from the foundation to the 
underside of the roof sheathing, roof deck, or 
roof slab and shall extend the full length of 
the wall including wall extensions through 
and separating attached accessory structures. 
Separation shall extend through enclosed 
soffits, overhangs, and similar projections. 

Subp. 3. IRC Section R317.4. IRC 

Section R317 is amended by adding a new 
section to read as follows: 

R317.4 Sound transmission. Wall and floor 
ceiling assemblies separating dwelling units, 
including those separating adjacent 
townhouse units, shall provide airborne sound 
insulation for walls, and both airborne and 
impact sound insulation for floor ceiling 
assemblies. 



245 



The 2007 Minnesota State Building Code 



R317.4.1 Airborne sound. Airborne sound 
insulation for wall and floor ceiling 
assemblies shall meet a Sound Transmission 
Class (STC) rating of 45 when tested in 
accordance with ASTM E 90. Penetrations or 
openings in construction assemblies for 
piping; electrical devices; recessed cabinets; 
bathtubs; soffits; or heating, ventilating, or 
exhaust ducts shall be sealed, lined, insulated, 
or otherwise treated to maintain the required 
ratings. Dwelling unit entrance doors, which 
share a common space, shall be tight fitting to 
the frame and sill. 

R317.4.2 Structural borne sound. 

Floor/ceiling assemblies between dwelling 
units or between a dwelling unit and a public 
or service area within a structure shall have an 
Impact Insulation Class (IIC) rating of not 
less than 45 when tested in accordance with 
ASTM E 492. 

R317.4.3 Referenced standards. 

R317.4.3.1 ASTM E 90 04 Test Method for 
Laboratory Measurement of Airborne Sound 
Transmission Loss of Building Partitions and 
Elements R317.4.1. 

R317.4.3.2 ASTM E 492 04 (1996)e 
Specification for Laboratory Measurement of 
Impact Sound Transmission through Floor 
Ceiling Assemblies Using the Tapping 
Machine R3 17.4.2. 

1309.0318 SECTION R318, MOISTURE 
VAPOR RETARDERS. 

IRC Section R318.1 is amended to read as 
follows: 



Exception: In construction where 

moisture or freezing will not damage the 
materials. 

1309.0322 Repealed 

1309.0403 SECTION R403, FOOTINGS. 

Subpart 1. IRC Section R403.1.4.1. IRC 

Section R403. 1.4.1 is amended to read as 
follows: 

R403.1.4.1 Frost protection. Except where 
otherwise protected from frost, foundation 
walls, piers, and other permanent supports of 
buildings and structures shall be protected 
from frost by one or more of the following 
methods: 

1. Extended below the frost line 
specified in Table R301.2(l); 

2. Constructing in accordance with 
Section R403. 3; 

3. Constructing in accordance with 
ASCE 32; 

4. Erected on solid rock; or 

5. Constructing in accordance with 
chapter 1303. 

Exception: Decks not supported by a 
dwelling need not be provided with 
footings that extend below the frost line. 

Subp. 2. IRC Section R403.1.6. IRC 

Section R403.1.6 is amended to read as 
follows: 



R318.1 Vapor retarders. In all above grade 
framed walls, floors, and roof/ceilings 
comprising elements of the building thermal 
envelope, a vapor retarder shall be installed 
on the warm side of the insulation. Vapor 
retarders installed under a concrete floor slab 
shall comply with section R506.2.3. 



R403.1.6 Foundation anchorage. When 
braced wall panels are supported directly on 
continuous foundations, the wall wood sill 
plate or cold formed steel bottom track shall 
be anchored to the foundation in accordance 
with this section. 



246 



The 2007 Minnesota State Building Code 



The wood sole plate at exterior walls on 
monolithic slabs and wood sill plate shall be 
anchored to the foundation with anchor bolts 
spaced a maximum of 6 feet (1829 mm) on 
center. There shall be a minimum of two 
bolts per plate section with one bolt located 
not more than 12 inches (305 mm) or less 
than seven bolt diameters from each end of 
the plate section. Bolts shall be at least 1/2 
inch (12.7 mm) in diameter and shall extend a 
minimum of 7 inches (178 mm) into masonry 
or concrete. Interior bearing wall sole plates 
on monolithic slab foundations shall be 
positively anchored with approved fasteners. 
A nut and washer shall be tightened on each 
bolt to the plate. Sills and sole plates shall be 
protected against decay and termites where 
required by Sections R322 and R323. Cold 
formed steel framing systems shall be 
fastened to the wood sill plates or anchored 
directly to the foundation as required in 
Section R505.3.1 or R603.1.1. When vertical 
reinforcing is required by other sections of 
this code, the foundation anchor bolts shall 
align with the reinforcing. All anchor bolts 
installed in masonry shall be grouted in place 
with at least 1 inch (25 mm) of grout between 
the bolt and the masonry. 

Exceptions: 



3. Walls 12 inches (304.8 mm) total 
length or shorter connecting offset braced 
wall panels shall be permitted to be 
connected to the foundation without 
anchor bolts. The wall shall be attached 
to adjacent braced wall panels according 
to Figure R602.10.5 at corners. 



1309.0404 

FOUNDATION 

WALLS. 



SECTION R404, 

AND RETAINING 



Subpart 1. Section R404.L IRC Section 
R404.1, Items 4 and 5, are amended to read as 
follows: 

4. Floor shall be blocked perpendicular 
to the floor joists. Blocking shall be full 
depth within three joist spaces of the 
foundation wall. 

5. Where foundation walls support 
unbalanced load on opposite sides of the 
building, such as a daylight basement, the rim 
board shall be attached to the sill with a 20 
gage metal angle clip at 24 inches on center, 
with five 8d nails per leg, or an approved 
connector supplying 230 pounds per linear 
foot capacity. 



1. Foundation anchor straps spaced as 
required to provide equivalent anchorage 
to 1/2 inch diameter (12.7 mm) anchor 
bolts. When vertical reinforcing is 
required by other sections of this code, the 
foundation anchor straps shall align with 
the reinforcing. 

2. Walls 24 inches (609.6 mm) total 
length or shorter connecting offset braced 
wall panels shall be anchored to the 
foundation with a minimum of one anchor 
bolt located in the center third of the plate 
section and shall be attached to adjacent 
braced wall panels according to Figure 
R602.10.5 at corners. 



247 



The 2007 Minnesota State Building Code 



Subp. 2. Table R404.1(2). IRC Table R404.1(2) is amended to read as follows: 

Table R404. 1(2) 
Maximum Anchor Bolt Spacing for Supported Foundation Wall 



Max. 
Unbalanced 



1/2" diameter 
Anchor Bolt 



Max. Wall 


Backfill 




Soil Load Top of Wall 


Spacing 


Height 


Height 


Soil Classes 


(pcf/ft) Reaction (plf)^ 


(inches)^ 






GW, GP, SW, & SP 


30 250 


72 


8' - 0" 


T - 4" 


GM, GC, SM-SC, & ML 


45 370 


72 






SC, MH, ML-CL & I-CL 


60 490 


48 



GW, GP, SW, & SP 30 

9'_0" 8' -4" GM, GC, SM-SC, & ML 45 

SC, MR ML-CL, & I-CL 60 



320 


72 


480 


48 


640 


40 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm 
^ Sill plate shall be 2 x 6 minimum. Anchor bolt shall be minimum 0.5" diameter cast in place 
with 7" embed. Anchor bolt shall have a 2" diameter by 0.125" thick washer tightened and 
countersunk 0.25" into the top of the sill plate. 
^ Minimum load to be used for sizing of accepted anchors or fasteners if bolts are not used. 



Subp. 3. Table R404.1(3). IRC Table 
R404.1(3) is deleted in its entirety. 

Subp. 4. Section R404.1.1. IRC Section 
R404.I.1 is amended to read as follows: 

R404.1.1 Masonry foundation walls. 

Concrete masonry and clay masonry 
foundation walls shall be constructed as set 
forth in Table R404.1.1(l), R404.1.1(2), 
R404.1.1(3), or R404. 1.1(4) and shall also 
comply with the provisions of Section R404 
and the applicable provisions of Sections 
R606, R607, and R608. Rubble stone 
masonry foundation walls shall be constructed 
in accordance with Sections R404.1.8 and 
R607.2.2. Cantilevered masonry foundation 
walls shall be constructed as set forth in Table 
R404. 1.1(6), R404. 1.1(7), or R404. 1.1(8). 
Cantilevered means: foundation walls that do 
not have permanent lateral support at the top. 



Subp. 5. Section R404.1.2. IRC Section 
R404.I.2 is amended to read as follows: 

R404.1.2 Concrete foundation walls. 

Concrete foundation walls shall be 
constructed as set forth in Table R404.1.1(5) 
and shall also comply with the provisions of 
Section R404 and the applicable provisions of 
Section R404.2. Cantilevered concrete 
foundation walls shall be constructed as set 
forth in Table R404.1.1(6), R404. 1.1(7), or 
R404. 1.1(8). Cantilevered means: 

foundation walls that do not have permanent 
lateral support at the top. 

Subp. 6. Table R404.1.1(6). IRC Section 
R404 is amended by adding a new table as 
follows: 



248 



The 2007 Minnesota State Building Code 

Table R404. 1.1(6) 
Cantilevered Concrete and Masonry Foundation Walls 





Maximum 


Maximui 


n Unbalanced 


Wall 


Backfill 


Height' 


Height' 


(feet) 


(feet) 



Minimum 

Vertical Reinforcement Size and Spacing for 

8_-JnclLl^minalJWan Thickneis^^'^"'^^^^^ _ 

Soil Classes^ 
GW, GP, SW, & SP GM, GC, SM, SM-CS, 
&ML 



SC, MH, ML-CL, and 
inorganic CL 



3 None required 

_4 None required 



None required 
None required 



None required 
No. 4 @ 72 in. o.c. 



3 None required 

4 No. 4 @ 72 in. o.c. 

5 No. 4 @ 72 in. o.c. 



None required 
No. 4 @ 56 in. o.c. 
No. 4 @ 56 in. o.c. 



None required 
No. 4 @ 40 in. o.c.^ 
No. 4 @ 40 in. o.c.^ 



a. Mortar shall be Type M or S and masonry 
shall be laid in running bond. Minimum unit 
compressive strength is 1,900 psi. 

b. Alternative reinforcing bar sizes and 
spacings having an equivalent cross sectional 
area of reinforcement per lineal foot of wall 
shall be permitted provided the spacing of the 
reinforcement does not exceed 72 inches. 

c. Vertical reinforcement shall be Grade 60 
minimum. The distance from the face of the 
soil side of the wall to the center of vertical 
reinforcement shall be no greater than 2.5 
inches. 

d. Soil classes are in accordance with the 
Unified Soil Classification System. Refer to 
Table R405.1. 

e. Interior concrete floor slab on grade shall 
be placed tight to the wall. The exterior grade 
level shall be 6 inches minimum below the 
top of wall. Maximum height from top of 
slab on grade to bottom of floor joists is 10 
feet inches. Unbalanced backfill height is 
the difference in height of the exterior finish 
ground levels and the top of the interior 
concrete slab on grade. 

f Minimum footing size of 20 inches by 8 
inches shall be placed on soil with a bearing 
capacity of 2,000 psf Minimum concrete 



compressive strength of footing shall be 3,000 

psi. 

g. Provide propped cantilever wall: top of 

footing shall be 16 inches below the bottom 

of the concrete floor slab minimum. 

h. Provide #5 Grade 60 dowels, 1 foot 6 

inches long, to connect footing to wall. 

Embed dowel 5 inches into footing. Place 

dowels in center of wall thickness spaced at 

32 inches o.c. maximum. No dowels are 

required where length of the foundation wall 

between perpendicular walls is two times the 

foundation wall height or less. 

i. This table is applicable where the length 

of the foundation wall between perpendicular 

walls is 35 feet or less, or where the length of 

the foundation laterally supported on only one 

end by a perpendicular wall is 17 feet or less. 

j. Maximum wall height is measured from 

top of the foundation wall to the bottom of the 

interior concrete slab on grade. 

k. Install foundation anchorage per Section 

R403.1.6. 



249 



The 2007 Minnesota State Building Code 



Subp. 7. Table R404.1.1(7). IRC Section 
R404 is amended by adding a new table as 



follows: 



Table R404. 1.1(7) 
Cantilevered Concrete and Masonry Foundation Walls 





Maximum 




Maximui 


n Unbalanced 




Wall 


Backfill 


Minimum 


Height' 


Height' 


Vertical Reinforcement Size and Spacing for 


(feet) 


(feet) 


10 - Inch Nominal Wall Thickness"'^'^'''^''''' 

Soil Classes 
GW, GP, SW, & SP GM, GC, SM, SM-SC. 
&ML 



SC, MH, ML-CL, and 
inorganic CL 



None 
None 



required 
required 



None required 
None required 



None required 
None required 



None 
None 
No. 4 



required 
required 
@ 72 in. o.c. 



None required 
No. 4 @ 72 in. o.c. 
No. 4 @ 72 in. o.c. 



None required 
No. 4 @ 64 in. o.c.^ 
No. 4 @ 56 in. o.c.^ 



3 None required 

4 No. 4 @ 72 in. o.c. 

5 No. 4 @ 64 in. o.c. 

6 No. 4 (d), 64 in. o.c. 



No. 4 @ 72 in. o.c. 
No. 4 @ 72 in. o.c. 
No. 4 @ 40 in. o.c.^'^ 
No. 4 @ 40 in. o.c.^'^ 



No. 4 @ 72 in. o.c. 
No. 4 @ 64 in. o.c.^ 
No. 5 @ 48 in. o.c.^'^ 
No. 5 (a), 48 in. o.c.^'^ 



a. Mortar shall be Type M or S and masonry 
shall be laid in running bond. Minimum unit 
compressive strength is 1,900 psi. 

b. Alternative reinforcing bar sizes and 
spacings having an equivalent cross sectional 
area of reinforcement per lineal foot of wall 
shall be permitted provided the spacing of the 
reinforcement does not exceed 72 inches. 

c. Vertical reinforcement shall be Grade 60 
minimum. The distance from the face of the 
soil side of the wall to the center of vertical 
reinforcement shall be no greater than 2.5 
inches. 

d. Soil classes are in accordance with the 
Unified Soil Classification System. Refer to 
Table R405.1. 

e. Interior concrete slab on grade shall be 
placed tight to the wall. The exterior grade 
level shall be 6 inches minimum below the 
top of wall. Maximum height from top of 
slab on grade to bottom of floor joists is 10 



feet inches. Unbalanced backfill height is 

the difference in height of the exterior finish 

ground levels and the top of the interior 

concrete slab on grade. 

f Minimum footing size of 20 inches by 8 

inches shall be placed on soil with a bearing 

capacity of 2,000 psf Minimum concrete 

compressive strength of footing shall be 3,000 

psi. 

g. Provide propped cantilever wall: top of 

footing shall be 16 inches below the bottom 

of the concrete floor slab minimum. 

h. Provide #5 Grade 60 dowels, 1 foot, 6 

inches long, to connect footing to wall. 

Embed dowel 5 inches into footing. Place 

dowels in center of wall thickness spaced at 

32 inches o.c. maximum. No dowels are 

required where length of the foundation wall 

between perpendicular walls is two times the 

foundation wall height or less. 

i. This table is applicable where the length 

of the foundation wall between perpendicular 



250 



The 2007 Minnesota State Building Code 



walls is 35 feet or less, or where the length of 
the foundation laterally supported on only one 
end by a perpendicular wall is 17 feet or less, 
j. Maximum wall height is measured from 
top of the foundation wall to the bottom of the 
interior concrete slab on grade. 



k. Install foundation anchorage per Section 
R403.1.6. 

Subp. 8. Table R404.1.1(8). IRC Section 
R404 is amended by adding a new table as 
follows: 



Table R404. 1.1(8) 
Cantilevered Concrete and Masonry Foundation Walls 





Maximum 


Maximui 


n Unbalanced 


Wall 


Backfill 


Height' 


Height' 


(feet) 


(feet) 



Minimum 

Vertical Reinforcement Size and Spacing for 

12 - Inch Nominal Wall Thickn^ss"'^"'^^':^ _ 

Soil Classes^ 
GW, GP, SW, & SP GM, GC, SM, SM-SC, 
&ML 



SC, MH, ML-CL, and 
inorganic CL 



None 
None 



required 
required 



None 
None 



required 
required 



None required 
None required 



None 
None 
No. 4 



required 
required 
(a), 72 in. o.c. 



None 
None 
No. 4 



required 
required 
(a), 72 in. o.c. 



None required 
No. 4 @ 72 in. o.c. 
No. 4 (a), 72 in. o.c. 



None 
None 
No. 4 
No. 4 



required 
required 
@ 72 in. o.c. 
@ 72 in. o.c. 



None 
None 
No. 4 
No. 4 



required 
required 
@ 56 in. o.c. 
@ 56 in. o.c. 



None required 
No. 4 @ 72 in. o.c. 
No. 4 @ 40 in. o.c.^ 

No. 4 (a), 32 in. o.c.^^' 



3 None required 

4 None required 

5 No. 4 @ 72 in. o.c. 

6 No. 4 @ 48 in. o.c. 

7 No. 4 (a), 48 in. o.c. 



None required 
No. 4 
No. 4 

No. 5 
No. 5 



@ 72 in. o.c. 
@ 56 in. o.c.*^ 
@ 48 in. o.c.^'^ 
@ 40 in. o.c.^'^ 



None required 
No. 4 @ 72 in. o.c. 
No. 4 @ 40 in. o.c.^ 
No. 6 @ 48 in. o.c.^'^ 
No. 6 @ 48 in. o.c.^'^ 



a. Mortar shall be Type M or S and masonry 
shall be laid in running bond. Minimum unit 
compressive strength is 1,900 psi. 

b. Alternative reinforcing bar sizes and 
spacings having an equivalent cross sectional 
area of reinforcement per lineal foot of wall 
shall be permitted provided the spacing of the 
reinforcement does not exceed 72 inches. 

c. Vertical reinforcement shall be Grade 60 
minimum. The distance from the face of the 
soil side of the wall to the center of vertical 



reinforcement shall be no greater than 3 
inches. 

d. Soil classes are in accordance with the 
Unified Soil Classification System. Refer to 
Table R405.1. 

e. Interior concrete slab on grade shall be 
placed tight to the wall. The exterior grade 
level shall be 6 inches minimum below the 
top of wall. Maximum height from top of 
slab on grade to bottom of floor joists is 10 
feet, inches. Unbalanced backfill height is 
the difference in height of the exterior finish 



251 



The 2007 Minnesota State Building Code 



ground levels and the top of the interior 
concrete slab on grade. 

f. Minimum footing size of 20 inches by 8 
inches shall be placed on soil with a bearing 
capacity of 2,000 psf Minimum concrete 
compressive strength of footing shall be 3,000 
psi. 

g. Provide propped cantilever wall: top of 
footing shall be 16 inches below the bottom 
of the concrete floor slab minimum. 

h. Provide #5 Grade 60 dowels, 1 foot, 6 
inches long, to connect footing to wall. 
Embed dowel 5 inches into footing. Place 
dowels in center of wall thickness spaced at 
32 inches o.c. maximum. No dowels are 
required where length of the foundation wall 
between perpendicular walls is two times the 
foundation wall height or less, 
i. This table is applicable where the length 
of the foundation wall between perpendicular 
walls is 35 feet or less, or where the length of 
the foundation laterally supported on only one 
end by a perpendicular wall is 17 feet or less, 
j. Maximum wall height is measured from 
top of the foundation wall to the bottom of the 
interior concrete slab on grade, 
k. Install foundation anchorage per Section 
R403.1.6. 



foundation walls that retain earth and enclose 
interior spaces and floors below grade shall be 
dampproofed at a minimum from the top of 
the footing to the finished grade. Masonry 
walls shall be parged with not less than 3/8 
inch (9.5 mm) portland cement parging 
applied to the exterior of the wall. The 
parging shall be dampproofed in accordance 
with one of the following: 

1. Bituminous coating. 

2. 3 pounds per square yard (1.63 kg/m^) 
of acrylic modified cement. 

3. 1/8 inch (3.2 mm) coat of surface 
bonding cement complying with ASTM C 
887. 



4. Any material permitted 
waterproofing in Section R406.2. 



for 



5. Other approved methods or materials. 

Exception: Parging of unit masonry 
walls is not required where a material is 
approved for direct application to the 
masonry. 



Subp. 9. IRC Section R404.1.3. IRC 

Section R404.1.3 is amended by adding the 
following exception to condition 2: 

Exception: Cantilevered concrete and 
masonry foundation walls constructed in 
accordance with Table R404. 1.1(6), 
R404.1. 1(7), or R404. 1.1(8). 



Concrete walls shall be dampproofed by 
applying any one of the above listed 
dampproofing materials or any one of the 
waterproofing materials listed in Section 
R406.2 to the exterior of the wall. 

Subp. 2. IRC Section R406.2. IRC 

Section R406.2 is amended to read as follows: 



1309.0406 SECTION R406, 

FOUNDATION WATERPROOFING 

AND DAMPPROOFING. 

Subpart 1. IRC Section R406.1. IRC 

Section R406.1 is amended to read as follows: 

R406.1 Concrete and masonry foundation 
dampproofing. Except where required by 
Section R406.2 to be waterproofed. 



R406.2 Concrete and masonry foundation 
waterproofing. In all soils groups other than 
Group 1 soils in accordance with Table 
R405.1, exterior foundation walls that retain 
earth and enclose interior spaces and floors 
below grade shall be waterproofed at a 
minimum from the top of the footing to the 
finished grade. Walls shall be waterproofed 
in accordance with one of the following: 



252 



The 2007 Minnesota State Building Code 



1 . 2 ply hot mopped felts. 

2. 55 pound (25 kg) roll roofing. 

3. 6 mil (0.15 mm) polyvinyl chloride. 

4. 6 mil (0.15 mm) polyethylene. 

5. 40 mil (1 mm) polymer modified 
asphalt. 

6. 60 mil (1.5 mm) flexible polymer 
cement. 



7. 1/8 inch cement based, 
reinforced, waterproof coating. 



fiber 



8. 60 mil (1.5 mm) solvent free liquid 
applied synthetic rubber. 

Exception: Organic solvent based 
products such as hydrocarbons, 
chlorinated hydrocarbons, ketones, and 
esters shall not be used for ICF walls with 
expanded polystyrene form material. 
Plastic roofing cements, acrylic coatings, 
latex coatings, mortars, and pargings are 
permitted to be used to seal ICF walls. 
Cold setting asphalt or hot asphalt shall 
conform to Type C of ASTMD 449. Hot 
asphalt shall be applied at a temperature 
of less than 200 degrees. 

All joints in membrane waterproofing shall be 
lapped and sealed with an adhesive 
compatible with the membrane. 

1309.0506 Repealed 

1309.0602 SECTION R602, WOOD WALL 
FRAMING. 

Subpart 1. Table R602.3.1. IRC Table 
R602.3.1 is amended to read as follows: 



Table R602.3.1 

Maximum Allowable Length of Wood Wall 

Studs Exposed to 

Wind Speeds of 90 mph or less^"'^'''^'^'*''^ 

Where conditions are not within the 

parameters 

of footnotes b, c, d, e, f, g, h, and i, 

design is required. 

Roof spans up to 22' supporting a roof only 



Maximum 




On-Center Spacing 


Wall 


Exposure 




(inches) 




Height 
(feet) 


Category*"' 
B 


24 


16 


12 


8 


10 


"2x6 


2x4" 


"2x4" 


"2x4" 




C 


2x6 


2x6 


2x4 


2x4 


12 


B 


2x6 


2x6 


2x4 


2x4 




C 


2x6 


2x6 


2x6 


2x4 


14 


B 


2x6 


2x6 


2x6 


2x4 




C 


2x6 


2x6 


2x6 


2x6 


16 


B 


2x8 


2x6 


2x6 


2x6 




C 


2x8 


2x6 


2x6 


2x6 


18 


B 


2x8 


2x8 


2x6 


2x6 




C 


2x8 


2x8 


2x6 


2x6 


20 


B 


2x8 


2x8 


2x8 


2x6 




C 


NA^ 


2x8 


2x8 


2x6 


24 


B 


NA' 


2x8 


2x8 


2x8 




C 


NA' 


NA' 


2x8 


2x8 


Roof spans greater than 22 


' and 


up tc 


) 26' 


supporting 


a roof only 










Maximum 




On-Center Spacing 


Wall 


Exposure 




(inches) 




Height 
(feet) 


Category*"' 
B 


24 


16 


12 


8 


10 


"2x6 


"2x6" 


""2x4" 


"2"x"4"" 




C 


2x6 


2x6 


2x6 


2x4 


12 


B 


2x6 


2x6 


2x6 


2x4 




C 


2x8 


2x6 


2x6 


2x6 


14 


B 


2x6 


2x6 


2x6 


2x6 




C 


2x8 


2x8 


2x6 


2x6 


16 


B 


2x8 


2x6 


2x6 


2x6 




C 


2x8 


2x8 


2x6 


2x6 


18 


B 


2x8 


2x8 


2x6 


2x6 




C 


NA' 


2x8 


2x8 


2x6 


20 


B 


NA^ 


2x8 


2x8 


2x6 




C 


NA' 


NA' 


2x8 


2x8 



253 



The 2007 Minnesota State Building Code 



Maximum 

Wall Exposure 

Height Category 

(feet) 

24 B 

C 



hj 



On-Center Spacing 
(inches) 

24 16 12 8 

NA'"nA'""2x8""2xY 
NA' NA' NA' 2x8 



Roof spans greater than 26' and up to 30' 
supporting a roof only 

Maximum On-Center Spacing 

Wall Exposure (inches) 

Height Category"' ^4 16 12 8 

(feet) 

10 B 2x6""2x6""2x4"'2x4' 

C 2x6 2x6 2x6 2x4 

12 B 2x6 2x6 2x6 2x4 

C 2x8 2x6 2x6 2x6 

14 B 2x8 2x6 2x6 2x6 

C 2x8 2x8 2x6 2x6 

16 B 2x8 2x6 2x6 2x6 

C 2x8 2x8 2x8 2x6 

18 B 2x8 2x8 2x6 2x6 

C NA' 2x8 2x8 2x8 

20 B NA' 2x8 2x8 2x6 

C NA' NA' 2x8 2x8 

24 B NA' NA' 2x8 2x8 

C NA' NA' NA' 2x8 



(inches) 
24 16 12 



Roof spans greater than 30' and up to 34' 

supporting a roof only 

Maximum On-Center Spacing 

Wall Exposure 

Height Category *^'^ 

(feet) 

10 B 2x6 "2x6" 2x4 2x4' 

C 2x6 2x6 2x6 2x4 

12 B 2x6 2x6 2x6 2x4 

C 2x8 2x6 2x6 2x6 

14 B 2x8 2x6 2x6 2x6 

C 2x8 2x8 2x6 2x6 

16 B 2x8 2x8 2x6 2x6 

C NA' 2x8 2x8 2x6 

18 B 2x8 2x8 2x6 2x6 

C NA' NA' 2x8 2x8 

20 B NA' 2x8 2x8 2x6 

C NA' NA' 2x8 2x8 

24 B NA' NA' 2x8 2x8 

C NA' NA' NA' 2x8 



a. Design required. 

b. Applicability of these tables assumes the 
following: SPF#2 or better, Ground snow = 
60 psf, Roof snow = 42 psf, Component and 
Cladding Zone 4 50 square feet (Exposure B 
= 14.3 psf, Exposure C = 18.4 psf), eaves not 
greater than 2.0 feet in dimension. 

c. The exterior of the wall shall be 
continuously sheathed in accordance with one 
of the methods (2-8) listed in Section 
R602.10.3. 

d. Studs shall be continuous full height. 

e. Full depth blocking is required at 10 foot 
spacing maximum. 

f Utility, standard, stud, and No. 3 grade 
lumber of any species are not permitted, 
g. This table is based on a maximum 
allowable deflection limit of L/120. 
h. Exposure B - Urban and suburban areas, 
wooded areas, or other terrain with numerous 
closely spaced obstructions having the size of 
single family dwellings or larger. Exposure B 
shall be assumed unless the site meets the 
definition of another type exposure, 
i. Exposure C - Open terrain with scattered 
obstructions, including surface undulations or 
other irregularities, having heights generally 
less than 30 feet extending more than 1,500 
feet from the building site in any quadrant. 
This category includes flat open country, 
grasslands, and shorelines in hurricane prone 
regions. Exposure C shall also apply to any 
building located within Exposure B type 
terrain where the building is directly adjacent 
to open areas of Exposure C type terrain in 
any quadrant for a distance of more than 600 
feet. 

1309.0613 SECTION R613, EXTERIOR 
WINDOWS AND GLASS DOORS. 

Subpart 1. Section R613.1. IRC Section 
R613.1 is amended to read as follows: 

R613.1 General. This section prescribes 
performance and construction requirements 
for exterior window systems installed in wall 
systems. Windows and doors shall be 



254 



The 2007 Minnesota State Building Code 



installed in accordance with the 
manufacturer's installation instructions. 
Installation instructions shall be provided by 
the manufacturer for each exterior window or 
door type. 



Subp. 2. Section R613.2. 
R613.2 is deleted in its entirety. 



IRC Section 



1309.0703 SECTION R703, EXTERIOR 
COVERING. 

Subpart 1. Repealed 

Subp. 2. Repealed 

Subp. 3. Section R703.6. IRC Section 
R703.6 is amended to read as follows: 

R703.6 Exterior plaster. Installation of 
these materials shall be in compliance with 
ASTM C 926 98a and ASTM C 1063 03 and 
provisions of this code. 

R703.6.1 Lath. All lath and lath attachments 
shall be of corrosion resistant materials. 
Expanded metal or woven wire lath shall be 
attached with 1 1 gage nails having a 7/16 inch 
(11.1 mm) head or 16 gage staples, spaced at 
no more than 6 inches (152 mm) or as 
otherwise approved. Nails or staples shall 
penetrate wood framing support members not 
less than 3/4 inch (19 mm). 

R703.6.2.1 Weep screeds. A minimum 
0.019 inch (No. 26 galvanized sheet gage), 
corrosion resistant weep screed or plastic 
weep screed, with a minimum vertical 
attachment flange of 3 1/2 inches (89 mm) 
shall be provided at or below the foundation 
plate line on exterior stud walls in accordance 
with ASTM C 1063 03. The weep screed 
shall be placed a minimum of 4 inches (102 
mm) above the earth or 2 inches (51 mm) 
above paved areas and shall be of a type that 
will allow trapped water to drain to the 
exterior of the building. The weather resistant 
barrier shall lap the attachment flange. The 



exterior lath shall cover and terminate on the 
attachment flange of the weep screed. 

R703.6.1.3 Control joints and expansion 
joints. Provisions for the control of 
expansion shall be determined by the exterior 
plaster application designer. ASTM C 1063 
03 sections 7.11 4-7.11 4.4 do not apply. 

R703.6.3 Water resistive barriers. Water 
resistive barriers shall be installed as required 
in Section R703.2 and, where applied over 
wood based sheathing, shall include two 
layers of a water resistive vapor permeable 
barrier. Each layer shall meet both of the 
following requirements: 

1 . A water resistance not less than that of 60 
minute Grade D paper; or a minimum 
hydrostatic head of 60.9 cm when tested in 
accordance with hydrostatic pressure test 
method AATCC 127 1998; or a minimum 
water transudation time of 60 minutes when 
tested in accordance with ASTM D 779. 

2. A water vapor permeance not less than 
that of no. 15 felt; or a minimum permeance 
rating of 8.5 gr/h.ft.^ in Hg (US perm) (4.9 x 
10^^ kg/Pa.s.m^) when tested in accordance 
with Procedure B of ASTM E96. 

Exception: One layer of water resistive 
barrier complying with R703.2 is 
permitted when a drainage space that 
allows bulk water to flow freely behind 
the cladding is provided. 

Subp. 3a. Section R703.7. IRC Section 
R703.7 is amended by adding the following 
sentence to the end of Section R703.7: For 
structures in 90 mph wind speed region apply 
Seismic Design Category A limitations and 
requirements of Exception 1 and Table 
R703.7(l). 

Subp. 4. Repealed 

Subp. 5. Repealed 



255 



The 2007 Minnesota State Building Code 



Subp. 6. Repealed 
Subp. 7. Repealed 
Subp. 8. Repealed 

Subp. 8a. Section R703.7.4.2. IRC 

Section R703. 7.4.2 is amended to read as 
follows: 

R703.7.4.2 Air space. The veneer shall be 
separated from the sheathing by an air space 
of a minimum of a nominal 1 inch (25 mm) 
but not more than 4 1/2 inches (114 mm). 

Exception: One layer of water resistive 
barrier complying with Section R703.2 is 
permitted when a drainage space that 
allows bulk water to flow freely behind 
the cladding is provided. 

Subp. 8b. Section R703.7.4.3. IRC 

Section R703.7.4.3 is amended to read as 
follows: 

R703.7.4.3 Mortar or grout fill. As an 

alternate to the air space required by Section 
R703.7.4.2, mortar or grout shall be permitted 
to fill the air space. When the 1 inch (25.4 
mm) space is filled with mortar, a weather 
resistant membrane or building paper as 
described in Section R703.2 or R703.6.3 is 
required over studs or sheathing. When 
filling the air space, it is permitted to replace 
the sheathing and weather resistant membrane 
or asphalt saturated felt paper with a wire 
mesh and approved paper or an approved 
paper backed reinforcement attached directly 
to the studs. 

R703.7.4.4 Masonry veneer on sheathed 
substrates. On sheathed substrates, a 
corrosion resistant, self furring expanded 
metal lath shall be installed over the weather 
resistant membrane or building paper with 
appropriate fasteners as described in Section 
R703.6.1. Fasteners shall penetrate wood 
supports a minimum of one inch. 



Subp. 9. Section R703.8. IRC Section 
R703.8 is amended to read as follows: 

R703.8 Flashing. Approved corrosion 
resistant flashing shall be applied shingle 
fashion in such a manner as to prevent entry 
of water into the wall cavity or penetration of 
water to the building structural framing 
components. The flashing shall extend to the 
surface of the exterior wall finish. Approved 
corrosion resistant flashing shall be installed 
at all of the following locations: 

1. Exterior window and door openings. 
Flashing at exterior window and door 
openings shall extend to the surface of the 
exterior wall finish or to the water resistive 
barrier for subsequent drainage. 

2. At the intersection of chimneys or other 
masonry construction with frame or stucco 
walls, with projecting lips on both sides under 
stucco copings. 

3. Under and at the ends of masonry, wood, 
or metal copings and sills. 

4. Continuously above all projecting wood 
trim. 

5. Where exterior porches, decks, or stairs 
attach to a wall or floor assembly of wood 
frame construction. 

6. At wall and roof intersections. 

7. At built in gutters. 

8. Where exterior material meets in other 
than a vertical line. 

9. Where the lower portion of a sloped roof 
stops within the plane of an intersecting wall 
cladding in such a manner as to divert or kick 
out water away from the assembly. 

R703.8.1 Pan flashing of windows and 
doors. A pan flashing shall be provided 



256 



The 2007 Minnesota State Building Code 



under all exterior windows and doors. Pan 
flashing shall be (a) sloped to drain water to 
the exterior surface of a weather resistive 
barrier or flat with sealed back dam and side 
dams to prevent re entry of water into the wall 
cavity or onto interior finishes, and (b) 
maintain the thermal envelope of the building. 
Pan flashing made from metal must be 
thermally isolated from interior surfaces. 

Exceptions: 

1. Windows or doors installed in 
accordance with the manufacturer's 
installation instructions which include an 
alternate flashing method. 

2. Windows or doors in detached 
accessory structures. 

3 . Skylights, bow or bay windows. 

4. Doors required to meet accessibility 
requirements that would prevent the 
installation of pan flashing. 



1309.0903 SECTION R903, WEATHER 
PROTECTION. 

IRC Section R903.2.2 is amended as 
follows: 

R903.2.2 Kick out flashing/diverter. A kick 
out flashing shall be installed where the lower 
portion of a sloped roof stops within the plane 
of an intersecting wall cladding, in such a 
manner as to divert or kick out water away 
from the assembly. 

1309.0905 SECTION R905, 

REQUIREMENTS FOR ROOF 

COVERINGS. 

IRC Section R905.2.1 is amended as 
follows: 

R905.2.1 Sheathing requirements. Asphalt 
shingles shall be fastened to solidly sheathed 
decks or 1 inch thick nominal wood boards. 



5. Repairs or replacement of existing 
windows and doors. 

6. When a method is provided by a 
registered design professional. 

1309.0802 SECTION 802, WOOD ROOF 
FRAMING. 

IRC Section R802.10.5 is amended to 
read as follows: 

R802.10.5 Truss to wall connection. 

Trusses shall be connected to wall plates by 
the use of approved fasteners or connectors 
having a resistance to uplift of not less than 
the value listed on the truss design drawings. 

1309.0806 SECTION R806, ROOF 
VENTILATION. 

IRC Section R806.4 is deleted in its 
entirety. 



257 



A yVlember of the International Code Family® 

International 

Residential 

Code* 



FOR One- and Two-Family Dwellings 




international 

CODE COUNCIL® 



2006 



2006 International Residential Code® for One- and Two-family Dwellings 



First Printing: Febmary 2006 
Second Printing: November 2006 



ISBN-13: 978-1-58001-253-9 (soft-cover) 

ISBN-10: 1-58001-253-1 (soft-cover 
ISBN-13: 978-1-58001-252-2 (loose-leaf) 

ISBN-10: 1-58001-252-3 (loose-leaf) 

ISBN-13: 978-1-58001-303-1 (e-document) 

ISBN-10: 1-58001-303-1 (e-document) 



COPYRIGHT © 2006 

by 

INTERNATIONAL CODE COUNCIL, INC. 



ALL RIGHTS RESERVED. This 2006 International Residential Code® for One- and Two-family Dwellings is a copyrighted work 
owned by the International Code Council, Inc. Without advance written permission from the copyright owner, no part of this book 
may be reproduced, distributed, or transmitted in any form or by any means, including, without limitation, electronic, optical or 
mechanical means (by way of example and not limitation, photocopying, or recording by or in an information storage retrieval sys- 
tem). For information on permission to copy material exceeding fair use, please contact: Publications, 405 1 West Flossmoor Road, 
Country Club Hills, IL 60478-5795. Phone 1-888-lCC-SAFE (422-7233). 

Trademarks: "International Code Council," the "International Code Council" logo and the "International Residential Code" are 
trademarks of the International Code Council, Inc. 



PRINTED IN THE U.S.A. 



PREFACE 



Introduction 

Internationally, code officials recognize the need for a modern, up-to-date residential code addressing the design and construction 
of one- and two-family dwellings and townhouses. The International Residential Code®, in this 2006 edition, is designed to meet 
these needs through model code regulations that safeguard the public health and safety in all communities, large and small. 

This comprehensive, stand-alone residential code establishes minimum regulations for one- and two-family dwellings and town- 
houses using prescriptive provisions. It is founded on broad-based principles that make possible the use of new materials and new 
building designs. This 2006 edition is fully compatible with all the International Codes® (I-Codes®) published by the International 
Code Council® (ICC)®, including the International Building Code®, ICC Electrical Code®, International Energy Conservation 
Code®, International Existing Building Code®, International Fire Code®, International Fuel Gas Code®, International Mechanical 
Code®, ICC Performance Code®, International Plumbing Code®, International Private Sewage Disposal Code®, International 
Property Maintenance Code®, International Wildland-Urban Interface Code™ and International Zoning Code®. 

The International Residential Code provisions provide many benefits, among which is the model code development process that 
offers an international forum for residential construction professionals to discuss prescriptive code requirements. This forum pro- 
vides an excellent arena to debate proposed revisions. This model code also encourages international consistency in the application 
of provisions. 

Development 

The first edition of the International Residential Code (2000) was the culmination of an effort initiated in 1 996 by the ICC and con- 
sisting of representatives from the three statutory members of the International Code Council at the time, including: Building Offi- 
cials and Code Administrators International, Inc. (BOCA), International Conference of Building Officials (ICBO) and Southern 
Building Code Congress International (SBCCI) and representatives from the National Association of Home Builders (NAHB). The 
intent was to draft a stand-alone residential code consistent with and inclusive of the scope of the existing model codes. Technical 
content of the 1998 International One- and Two-Family Dwelling Code and the latest model codes promulgated by BOCA, ICBO, 
SBCCI and ICC was used as the basis for the development, followed by public hearings in 1998 and 1999 to consider proposed 
changes. This 2006 edition represents the code as originally issued, with changes reflected in the 2003 edition, and further changes 
developed through the ICC Code Development Process through 2005. Residential electrical provisions are based on the 2005 
National Electrical Code® (NFPA-70). A new edition such as this is promulgated every three years. 

Fuel gas provisions have been included through an agreement with the American Gas Association (AG A). Electrical provisions 
have been included through an agreement with the National Fire Protection Association (NFPA). 

This code is founded on principles intended to establish provisions consistent with the scope of a residential code that adequately 
protects public health, safety and welfare; provisions that do not unnecessarily increase construction costs; provisions that do not 
restrict the use of new materials, products or methods of construction; and provisions that do not give preferential treatment to par- 
ticular types or classes of materials, products or methods of construction. 

Adoption 

The International Residential Code is available for adoption and use by jurisdictions internationally. Its use within a governmental 
jurisdiction is intended to be accomplished through adoption by reference in accordance with proceedings establishing the jurisdic- 
tion's laws. At the time of adoption, jurisdictions should insert the appropriate information in provisions requiring specific local 
information, such as the name of the adopting jurisdiction. These locations are shown in bracketed words in small capital letters in 
the code and in the sample ordinance. The sample adoption ordinance on page v addresses several key elements of a code adoption 
ordinance, including the information required for insertion into the code text. 

Maintenance 

The International Residential Code is kept up to date through the review of proposed changes submitted by code enforcing officials, 
industry representatives, design professionals and other interested parties. Proposed changes are carefully considered through an 
open code development process in which all interested and affected parties may participate. 

The contents of this work are subject to change both through the Code Development Cycles and the governmental body that enacts 
the code into law. For more information regarding the code development process, contact the Code and Standard Development 
Department of the International Code Council. 

2006 INTERNATIONAL RESIDENTIAL CODE® iii 



PREFACE 



The maintenance process for the fuel gas provisions is based upon the process used to maintain the International Fuel Gas Code, in 
conjunction with the American Gas Association. The maintenance process for the electrical provisions is undertaken by the 
National Fire Protection Association. 

While the development procedure of the International Residential Code assures the highest degree of care, ICC and the founding 
members of ICC and its members and those participating in the development of this code do not accept any liability resulting from 
compliance or noncompliance with the provisions because ICC and its founding members do not have the power or authority to 
police or enforce compliance with the contents of this code. Only the governmental body that enacts the code into law has such 
authority. 

Marginal Markings 

Solid vertical lines in the margins within the body of the code indicate a technical change from the requirements of the 2003 edition. 
Deletion indicators in the form of an arrow (^) are provided in the margin where an entire section, paragraph, exception or table has 
been deleted or an item in a list of items or a table has been deleted. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 

i 



ORDINANCE 



The International Codes are designed and promulgated to be adopted by reference by ordinance. Jurisdictions wishing to adopt the 
2006 International Residential Code as an enforceable regulation governing one- and two-family dwellings and townhouses should 
ensure that certain factual information is included in the adopting ordinance at the time adoption is being considered by the appro- 
priate governmental body. The following sample adoption ordinance addresses several key elements of a code adoption ordinance, 
including the information required for insertion into the code text. 

SAMPLE ORDINANCE FOR ADOPTION OF THE 
INTERNATIONAL RESIDENTIAL CODE 



ORDINANCE NO. 

An ordinance of the [JURISDICTION] adopting the 2006 edition of the International Residential Code, regulating and governing the 
construction, alteration, movement, enlargement, replacement, repair, equipment, location, removal and demolition of detached 
one and two family dwellings and multiple single family dwellings (townhouses) not more than threes stories in height with separate 
means of egress in the [JURISDICTION]; providing for the issuance of permits and collection of fees therefor; repealing Ordinance 
No. of the [JURISDICTION] and all other ordinances and parts of the ordinances in conflict therewith. 

The [GOVERNING BODY] of the [JURISDICTION] does ordain as follows: 

Section 1. That a certain document, three (3) copies of which are on file in the office of the [TITLE OF JURISDICTION'S KEEPER OF 
RECORDS] of [NAME OF JURISDICTION], being marked and designated as the International Residential Code, 2006 edition, includ- 
ing Appendix Chapters [FILL IN THE APPENDIX CHAPTERS BEING ADOPTED] (see International Residential Code Section R102.5, 
2006 edition), as published by the International Code Council, be and is hereby adopted as the Residential Code of the [JURISDIC- 
TION], in the State of [STATE NAME] for regulating and governing the construction, alteration, movement, enlargement, replacement, 
repair, equipment, location, removal and demolition of detached one and two family dwellings and multiple single family dwelhngs 
(townhouses) not more than threes stories in height with separate means of egress as herein provided; providing for the issuance of 
permits and collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions and terms of said Resi- 
dential Code on file in the office of the [JURISDICTION] are hereby referred to, adopted, and made a part hereof, as if fully set out in 
this ordinance, with the additions, insertions, deletions and changes, if any, prescribed in Section 2 of this ordinance. 

Section 2. The following sections are hereby revised: 



Section RlOl.l. Insert: [NAME OF JURISDICTION] 

Table R301.2 (1) Insert: [APPROPRIATE DESIGN CRITERIA] 

Section P2603.6.1 Insert: [NUMBER OF INCHES IN TWO LOCATIONS] 

Section P3 103.1 Insert: [NUMBER OF INCHES IN TWO LOCATIONS] 

Section 3. That Ordinance No. of [JURISDICTION] entitled [FILL IN HERE THE COMPLETE TITLE OF THE ORDINANCE OR 

ORDINANCES IN EFFECT AT THE PRESENT TIME SO THAT THEY WILL BE REPEALED BY DEFINITE MENTION] and all other ordinances 
or parts of ordinances in conflict herewith are hereby repealed. 

Section 4. That if any section, subsection, sentence, clause or phrase of this ordinance is, for any reason, held to be unconstitutional, 
such decision shall not affect the validity of the remaining portions of this ordinance. The [GOVERNING BODY] hereby declares that 
it would have passed this ordinance, and each section, subsection, clause or phrase thereof, irrespective of the fact that any one or 
more sections, subsections, sentences, clauses and phrases be declared unconstitutional. 

Section 5. That nothing in this ordinance or in the Residential Code hereby adopted shall be construed to affect any suit or proceed- 
ing impending in any court, or any rights acquired, or hability incurred, or any cause or causes of action acquired or existing, under 
any act or ordinance hereby repealed as cited in Section 3 of this ordinance; nor shall any just or legal right or remedy of any charac- 
ter be lost, impaired or affected by this ordinance. 

Section 6. That the [JURISDICTION'S KEEPER OF RECORDS] is hereby ordered and directed to cause this ordinance to be published. 
(An additional provision may be required to direct the number of times the ordinance is to be published and to specify that it is to be 
in a newspaper in general circulation. Posting may also be required.) 

Section 7. That this ordinance and the rules, regulations, provisions, requirements, orders and matters established and adopted 
hereby shall take effect and be in full force and effect [TIME PERIOD] from and after the date of its final passage and adoption. 

2006 INTERNATIONAL RESIDENTIAL CODE® v 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



TABLE OF CONTENTS 



Part I — Administrative 1 

CHAPTER 1 ADMINISTRATION 1 

Section 

RlOl Title, Scope and Purpose 1 

R102 Applicability 1 

R103 Department of Building Safety 1 

R104 Duties and Powers of the Building Official 1 

R105 Permits 3 

R106 Construction Documents 4 

R107 Temporary Structures and Uses 5 

R108 Fees 5 

R109 Inspections 6 

RllO Certificate of Occupancy 6 

Rl 1 1 Service Utilities 7 

R112 Board of Appeals 7 

Rl 13 Violations 8 

Rl 14 Stop Work Order 8 

Part II — Definitions 9 

CHAPTER 2 DEFINITIONS 9 

Section 

R201 General 9 

R202 Definitions 9 

Part III — Building Planning and Construction 23 

CHAPTER 3 BUILDING PLANNING 23 

Section 

R301 Design Criteria 23 

R302 Exterior Wall Location 47 

R303 Light, Ventilation and Heating 47 

R304 Minimum Room Areas 48 

R305 Ceiling Height 48 

R306 Sanitation 49 

R307 Toilet, Bath and Shower Spaces 49 

R308 Glazing 50 

R309 Garages and Carports 52 

R310 Emergency Escape and Rescue Openings 52 

R3 1 1 Means of Egress 53 

R312 Guards 55 

R313 Smoke Alarms 55 



R314 Foam Plastic 56 

R315 Flame Spread and Smoke Density 58 

R316 Insulation 58 

R317 Dwelling Unit Separation 58 

R318 Moisture Vapor Retarders 60 

R319 Protection Against Decay 60 

R320 Protection Against Subterranean Termites 61 

R321 Site Address 62 

R322 Accessibility 62 

R323 Elevators and Platform Lifts 62 

R324 Flood-resistant Construction 62 

CHAPTER 4 FOUNDATIONS 67 

Section 

R401 General 67 

R402 Materials 67 

R403 Footings 68 

R404 Foundation and Retaining Walls 78 

R405 Foundation Drainage 88 

R406 Foundation Waterproofing and 

Dampproofing 90 

R407 Columns 93 

R408 Under-floor Space 93 

CHAPTER 5 FLOORS 97 

Section 

R501 General 97 

R502 Wood Floor Framing 97 

R503 Floor Sheathing 106 

R504 Pressure Preservatively Treated-wood 

Floors (On Ground) 108 

R505 Steel Floor Framing 108 

R506 Concrete Floors (On Ground) 121 

CHAPTER 6 WALL CONSTRUCTION 123 

Section 

R601 General 123 

R602 Wood Wall Framing 123 

R603 Steel Wall Framing 143 

R604 Wood Structural Panels 180 

R605 Particleboard 180 

R606 General Masonry Construction 1 80 

R607 Unit Masonry 188 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



TABLE OF CONTENTS 



R608 Multiple Wythe Masonry 188 

R609 Grouted Masonry 190 

R610 Glass Unit Masonry 191 

R611 Insulating Concrete Form Wall Construction. . 193 

R612 Conventionally Formed Concrete 

Wall Construction 224 

R613 Exterior Windows and Glass Doors 224 

CHAPTER 7 WALL COVERING 229 

Section 

R701 General 229 

R702 Interior Covering 229 

R703 Exterior Covering 232 

CHAPTER 8 ROOF-CEILING 

CONSTRUCTION 243 

Section 

R801 General 243 

R802 Wood Roof Framing 243 

R803 Roof Sheathing 268 

R804 Steel Roof Framing 268 

R805 Ceiling Finishes 286 

R806 Roof Ventilation 286 

R807 Attic Access 287 

R808 Insulation Clearance 287 

CHAPTER 9 ROOF ASSEMBLIES 289 

Section 

R901 General 289 

R902 Roof Classification 289 

R903 Weather Protection 289 

R904 Materials 289 

R905 Requirements for Roof Coverings 291 

R906 Roof Insulation 298 

R907 Reroofing 299 

CHAPTER 10 CHIMNEYS AND FIREPLACES . . 301 

Section 

RlOOl Masonry Fireplaces 301 

R1002 Masonry Heaters 305 

R1003 Masonry Chimneys 305 

R1004 Factory-built Fireplaces 309 

R1005 Factory-built Chimneys 309 

R 1006 Exterior Air Supply 310 



Part IV — Energy Conservation 311 

CHAPTER 11 ENERGY EFFICIENCY 311 

Section 

NllOl General 311 

N1102 Building Thermal Envelope 318 

N1103 Systems 321 

Part V — Mechanical 323 

CHAPTER 12 MECHANICAL 

ADMINISTRATION 323 

Section 

M1201 General 323 

M1202 Existing Mechanical Systems 323 

CHAPTER 13 GENERAL MECHANICAL SYSTEM 
REQUIREMENTS 325 

Section 

M1301 General 325 

M1302 Approval 325 

M1303 Labeling of Appliances 325 

M1304 Type of Fuel 325 

M1305 Appliance Access 325 

M1306 Clearances from Combustible Construction. . . 326 

Ml 307 Appliance Installation 329 

Ml 308 Mechanical Systems Installation 329 

CHAPTER 14 HEATING AND COOLING 

EQUIPMENT 331 

Section 

M1401 General 331 

M1402 Central Furnaces 331 

M1403 Heat Pump Equipment 331 

Ml 404 Refrigeration Cooling Equipment 331 

M1405 Baseboard Convectors 331 

M1406 Radiant Heating Systems 331 

M1407 Duct Heaters 332 

M1408 Vented Floor Furnaces 332 

M1409 Vented Wall Furnaces 332 

M1410 Vented Room Heaters 333 

M1411 Heating and Cooling Equipment 333 

M1412 Absorption Cooling Equipment 334 

M1413 Evaporative Cooling Equipment 334 

M1414 Fireplace Stoves 334 

M1415 Masonry Heaters 334 



vin 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



TABLE OF CONTENTS 



CHAPTER 15 EXHAUST SYSTEMS 335 

Section 

M1501 General 335 

M1502 Clothes Dryer Exhaust 335 

M1503 Range Hoods 335 

M1504 Installation of Microwave Ovens 335 

M1505 Overhead Exhaust Hoods 336 

M1506 Exhaust Ducts 336 

M1507 Mechanical Ventilation 336 

CHAPTER 16 DUCT SYSTEMS 337 

Section 

M1601 Duct Construction 337 

M1602 Return Air 339 

CHAPTER 17 COMBUSTION AIR 341 

Section 

M1701 General 341 

Ml 702 All Air from Inside the Building 341 

M1703 All Air from Outdoors 341 

CHAPTER 18 CHIMNEYS AND VENTS 347 

Section 

M1801 General 347 

M1802 Vent Components 347 

Ml 803 Chimney and Vent Connectors 348 

M1804 Vents 349 

Ml 805 Masonry and Factory-built Chimneys 349 

CHAPTER 19 SPECIAL FUEL-BURNING 

EQUIPMENT 351 

Section 

M1901 Ranges and Ovens 351 

M1902 Sauna Heaters 351 

M1903 Stationary Fuel Cell Power Plants 351 

Ml 904 Gaseous Hydrogen Systems 351 

CHAPTER 20 BOILERS AND 

WATER HEATERS 353 

Section 

M2001 Boilers 353 

M2002 Operating and Safety Controls 353 

M2003 Expansion Tanks 353 

M2004 Water Heaters Used for Space Heating 353 

M2005 Water Heaters 353 

M2006 Pool Heaters 354 



CHAPTER 21 HYDRONIC PIPING 355 

Section 

M2101 Hydronic Piping Systems Installation 355 

M2102 Baseboard Convectors 355 

M2103 Floor Heating Systems 355 

M2104 Low Temperature Piping 355 

M2105 Ground Source Heat Pump System 

Loop Piping 357 

CHAPTER 22 SPECIAL PIPING AND STORAGE 

SYSTEMS 359 

Section 

M2201 Oil Tanks 359 

M2202 Oil Piping, Fitting and Connections 359 

M2203 Installation 359 

M2204 Oil Pumps and Valves 360 

CHAPTER 23 SOLAR SYSTEMS 361 

Section 

M2301 Solar Energy Systems 361 

Part VI— Fuel Gas 363 

CHAPTER 24 FUEL GAS 363 

Section 

G2401 General 363 

G2402 General 363 

G2403 General Definitions 363 

G2404 General 369 

G2405 Structural Safety 369 

G2406 Appliance Location 369 

G2407 Combustion, Ventilation and Dilution Air 370 

G2408 Installation 374 

G2409 Clearance Reduction 374 

G2410 Electrical 376 

G241 1 Electrical Bonding 377 

G2412 General 377 

G2413 Pipe Sizing 378 

G2414 Piping Materials 379 

G2415 Piping System Installation 389 

G2416 Piping Bends and Changes in Direction 391 

G2417 Inspection, Testing and Purging 391 

G2418 Piping Support 392 

G2419 Drips and Sloped Piping 392 

G2420 Gas-shutoff Valves 393 

G2421 Flow Controls 393 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



TABLE OF CONTENTS 



G2422 Appliance Connections 394 

G2423 CNG Gas-dispensing Systems 394 

G2424 Piping Support Intervals 394 

G2425 General 395 

G2426 Vents 396 

G2427 Venting of Equipment 396 

G2428 Sizing of Category I Appliance 

Venting Systems 406 

G2429 Direct- vent, Integral Vent, Mechanical Vent 

and Ventilation/Exhaust Hood Venting 417 

G2430 Factory-built Chimneys 417 

G2431 General 418 

G2432 Decorative Appliances for Installation 

in Fireplaces 418 

G2433 Log Lighters 418 

G2434 Vented Gas Fireplaces 

(Decorative Fireplaces) 418 

G2435 Vented Gas Fireplace Heaters 418 

G2436 Vented Wall Furnaces 418 

G2437 Floor Furnaces 418 

G2438 Clothes Dryers 419 

G2439 Clothes Dryer Exhaust 419 

G2440 Sauna Heaters 419 

G2441 Pool and Spa Heaters 420 

G2442 Forced-air Warm-air Furnaces 420 

G2443 Conversion Burners 421 

G2444 Unit Heaters 421 

G2445 Unvented Room Heaters 421 

G2446 Vented Room Heaters 421 

G2447 Cooking Appliances 422 

G2448 Water Heaters 422 

G2449 Air Conditioning Equipment 422 

G2450 Illuminating Appliances 422 

G2451 Infrared Radiant Heaters 422 

G2452 Boilers 422 

G2453 Chimney Damper Opening Area 423 

Part Vn— Plumbing 425 

CHAPTER 25 PLUMBING 

ADMINISTRATION 425 

Section 

P2501 General 425 

P2502 Existing Plumbing Systems 425 

P2503 Inspection and Tests 425 



CHAPTER 26 GENERAL PLUMBING 

REQUIREMENTS 427 

Section 

P2601 General 427 

P2602 Individual Water Supply and 

Sewage Disposal 427 

P2603 Structural and Piping Protection 427 

P2604 Trenching and Backfilling 428 

P2605 Support 428 

P2606 Waterproofing of Openings 428 

P2607 Workmanship 428 

P2608 Materials Evaluation and Listing 428 

CHAPTER 27 PLUMBING FIXTURES 431 

Section 

P2701 Fixtures, Faucets and Fixture Fittings 431 

P2702 Fixture Accessories 431 

P2703 Tail Pieces 431 

P2704 Access to Connections 431 

P2705 Installation 431 

P2706 Waste Receptors 431 

P2707 Directional Fittings 433 

P2708 Showers ■ 433 

P2709 Shower Receptors 433 

P2710 Shower Walls 434 

P271 1 Lavatories , . . 434 

P2712 Water Closets 434 

P2713 Bathtubs 434 

P2714 Sinks 435 

P2715 Laundry Tubs 435 

P2716 Food Waste Grinder 435 

P2717 Dishwashing Machines 435 

P2718 Clothes Washing Machine 435 

P2719 Floor Drains 435 

P2720 Whirlpool Bathtubs 435 

P2721 Bidet Installations 435 

P2722 Fixture Fitting 436 

P2723 Macerating Toilet Systems 436 

P2724 Speciality Temperature Control Devices 

and Valves 436 

CHAPTER 28 WATER HEATERS 437 

Section 

P2801 General 437 

P2802 Water Heaters Used for Space Heating 437 

P2803 Relief Valves 437 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



TABLE OF CONTENTS 



CHAPTER 29 WATER SUPPLY AND 

DISTRIBUTION 439 

Section 

P2901 General 439 

P2902 Protection of Potable Water Supply 439 

P2903 Water-supply System 441 

P2904 Materials, Joints and Connections 447 

P2905 Changes in Direction 451 

P2906 Support 451 

P2907 Drinking Water Treatment Units 451 

CHAPTER 30 SANITARY DRAINAGE 453 

Section 

P3001 General 453 

P3002 Materials 453 

P3003 Joints and Connections 453 

P3004 Determining Drainage Fixture Units 458 

P3005 Drainage System 458 

P3006 Sizing of Drain Pipe Offsets 461 

P3007 Sumps and Ejectors 461 

P3008 Backwater Valves 461 

CHAPTER 31 VENTS 463 

Section 

P3101 Vent Systems 463 

P3102 Vent Stacks and Stack Vents 463 

P3103 Vent Terminals 463 

P3104 Vent Connections and Grades 463 

P3105 Fixture Vents 464 

P3106 Individual Vent 464 

P3107 Common Vent 464 

P3108 Wet Venting 464 

P3109 Waste Stack Vent 465 

P31 10 Circuit Venting 465 

P31 1 1 Combination Waste and Vent System 465 

P3112 Island Fixture Venting 466 

P3113 Vent Pipe Sizing 466 

P31 14 Air Admittance Valves 466 

CHAPTER 32 TRAPS 469 

Section 

P3201 Fixture Traps 469 



Part VIII— Electrical 471 

CHAPTER 33 GENERAL REQUIREMENTS .... 471 

Section 

E3301 General 471 

E3302 Building Structure Protection 471 

E3303 Inspection and Approval 471 

E3304 General Equipment Requirements 471 

E3305 Equipment Location and Clearances 472 

E3306 Electrical Conductors and Connections 474 

E3307 Conductor and Terminal Identification 474 

CHAPTER 34 ELECTRICAL DEFINITIONS .... 477 

Section 

E3401 General 477 

CHAPTER 35 SERVICES 481 

Section 

E3501 General Services 481 

E3502 Service Size and Rating 481 

E3503 Service, Feeder and Grounding Electrode 

Conductor Sizing 482 

E3504 Overhead Service-drop and Service Conductor 

Installation 483 

E3505 Service-entrance Conductors 485 

E3506 Service Equipment — General 485 

E3507 System Grounding 485 

E3508 Grounding Electrode System 486 

E3509 Bonding 487 

E3510 Grounding Electrode Conductors 488 

E35 1 1 Grounding Electrode Conductor Connection to 

the Grounding Electrodes 488 

CHAPTER 36 BRANCH CIRCUIT AND FEEDER 

REQUIREMENTS 491 

Section 

E3601 General 491 

E3602 Branch Circuit Ratings 491 

E3603 Required Branch Circuits 492 

E3604 Feeder Requirements 493 

E3605 Conductor Sizing and Overcurrent 

Protection 494 

E3606 Panelboards 497 



2003 INTERNATIONAL RESIDENTIAL CODE® 



TABLE OF CONTENTS 



CHAPTER 37 WIRING METHODS 499 

Section 

E3701 General Requirements 499 

E3702 Above-ground Installation Requirements 499 

E3703 Underground Installation Requirements 502 

CHAPTER 38 POWER AND LIGHTING 

DISTRIBUTION 505 

Section 

E3801 Receptacle Outlets 505 

E3802 Ground-fault and Arc-fault Circuit-interrupter 

Protection 507 

E3803 Lighting Outlets 508 

E3804 General Installation Requirements 508 

E3805 Boxes, Conduit Bodies and Fittings 519 

E3806 Installation of Boxes, Conduit Bodies 

and Fittings 521 

E3807 Cabinets and Panelboards 523 

E3808 Grounding 524 

E3809 Flexible Cords 526 

CHAPTER 39 DEVICES AND LUMINAIRES .... 527 
Section 

E3901 Switches 527 

E3902 Receptacles 528 

E3903 Fixtures 528 

E3904 Luminaire Installation 530 

E3905 Track Lighting 530 

CHAPTER 40 APPLIANCE INSTALLATION .... 533 

Section 

E4001 General 533 

CHAPTER 41 SWIMMING POOLS 535 

Section 

E4101 General 535 

E4102 Wiring Methods for Pools, Spas, Hot Tubs and 

Hydromassage Bathtubs 535 

E4103 Equipment Location and Clearances 537 

E4104 Bonding 538 

E4105 Grounding 540 

E4I06 Equipment Installation 541 

E4107 Storable Swimming Pools 543 

E4108 Spas and Hot Tubs 544 

E4109 Hydromassage Bathtubs 544 



CHAPTER 42 CLASS 2 REMOTE-CONTROL, 

SIGNALING AND POWER-LIMITED 
CIRCUITS 545 

Section 

E4201 General 545 

E4202 Power Sources 545 

E4203 Wiring Methods 545 

E4204 Installation Requirements 545 

Part IX — Referenced Standards 547 

CHAPTER 43 REFERENCED STANDARDS 547 

APPENDIX A SIZING AND CAPACITIES OF GAS 

PIPING 567 

APPENDIX B SIZING OF VENTING SYSTEMS 

SERVING APPLIANCES EQUIPPED 
WITH DRAFT HOODS, CATEGORY I 
APPLIANCES, AND APPLIANCES 
LISTED FOR USE WITH TYPE 
B VENTS 579 

APPENDIX C EXIT TERMINALS OF 

MECHANICAL DRAFT AND DIRECT- 
VENT VENTING SYSTEMS 589 

APPENDIX D RECOMMENDED PROCEDURE FOR 
SAFETY INSPECTION OF AN 
EXISTING APPLIANCE 
INSTALLATION 591 

APPENDIX E MANUFACTURED HOUSING 

USED AS DWELLINGS 593 

Section 

AElOl Scope 593 

AE102 Application to Existing Manufactured Homes 

and Building Service Equipment 593 

AE201 Definitions 594 

AE301 Permits 594 

AE302 Application for Permit 594 

AE303 Permits Issuance 595 

AE304 Fees '. 595 

AE305 Inspections 596 

AE306 Special Inspections 597 

AE307 Utility Service 597 

AE401 Occupancy Classification 597 

AE402 Location on Property 597 

AE501 Design 597 



XII 



2006 INTERNATIONAL RESIDENTIAL CODE' 



,® 



TABLE OF CONTENTS 



AE502 Foundation Systems 598 

AE503 Skirting and Perimeter Enclosures 598 

AE504 Structural Additions 598 

AE505 Building Service Equipment 598 

AE506 Exits 599 

AE507 Occupancy, Fire Safety and Energy 

Conservation Standards 599 

AE600 Special Requirements for 

Foundation Systems 599 

AE601 Footings and Foundations 599 

AE602 Pier Construction 599 

AE603 Height of Piers 599 

AE604 Anchorage Installations 599 

AE605 Ties, Materials and Installation 600 

AE606 Referenced Standards 600 

APPENDIX F RADON CONTROL METHODS. . . 601 

Section 

AFlOl Scope 601 

AF102 Definitions 601 

AF103 Requirements 601 

APPENDIX G SWIMMING POOLS, SPAS AND 

HOT TUBS 609 

Section 

AGlOl General 609 

AG102 Definitions 609 

AGIOS Swimming Pools 609 

AG104 Spas and Hot Tubs 609 

AG105 Barrier Requirements 609 

AG 106 Entrapment Protection for Swimming Pool and 

Spa Suction Outlets 610 

AG107 Abbreviations 611 

AGIOS Standards 611 

APPENDIX H PATIO COVERS 613 

Section 

AHlOl General 613 

AH102 Definition 613 

AH103 Permitted Uses 613 

AH104 Design Loads 613 

AH 105 Light and Ventilation/Emergency Egress 613 

AH106 Footings 613 

AH107 Special Provisions for Aluminum Screen 

Enclosures in Hurricane-prone Regions. ... 613 



APPENDIX I PRIVATE SEWAGE DISPOSAL ... 615 

Section 

AIlOl General 615 

APPENDIX J EXISTING BUILDINGS AND 

STRUCTURES 617 

Section 

AJlOl Purpose and Intent 617 

AJ102 Compliance 617 

AJ103 Preliminary Meeting 617 

AJ104 Evaluation of an Existing Building 617 

AJ105 Permit 618 

AJ201 Definitions 618 

AJ301 Repairs 618 

AJ401 Renovations 619 

AJ501 Alterations 619 

AJ601 Reconstruction 620 

APPENDIX K SOUND TRANSMISSION 621 

Section 

AKIOI General 621 

AK102 Air-borne Sound 621 

AK103 Structural-borne Sound 621 

AK104 Referenced Standards 621 

APPENDIX L PERMIT FEES 623 

APPENDIX M HOME DAY CARE— 

R-3 OCCUPANCY 625 

AMIOI General 625 

AM102 Definitions 625 

AM103 Means of Egress 625 

AM104 Smoke Detection 625 

APPENDIX N VENTING METHODS 627 

APPENDIX O GRAY WATER RECYCLING 

SYSTEMS 635 

AOlOl General 635 

AG 102 Systems for Flushing Water Closets 

and Urinals 635 

AG 103 Subsurface Landscape 

Irrigation Systems 637 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



XIII 



TABLE OF CONTENTS 



APPENDIX P SPRINKLING 641 

APPENDIX Q ICC INTERNATIONAL 

RESIDENTIAL CODE ELECTRICAL 
PROVISIONS/NATIONAL 
ELECTRICAL CODE CROSS- 
REFERENCE 643 

INDEX 657 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



Part I — Administrative 



CHAPTER 1 

ADMINISTRATION 



SECTION R1 01 
TITLE, SCOPE AND PURPOSE 

RlOl.l Title. These provisions shall be known as the Residen- 
tial Code for One- and Two-family Dwellings of [NAME OF 
JURISDICTION], and shall be cited as such and will be referred to 
herein as "this code." 

R101.2 Scope. The provisions of the International Residen- 
tial Code for One- and Two-family Dwellings shall apply to 
the construction, alteration, movement, enlargement, replace- 
ment, repair, equipment, use and occupancy, location, 
removal and demolition of detached one- and two-family 
dwellings and townhouses not more than three stories 
above-grade in height with a separate means of egress and 
their accessory structures. 

R101.3 Purpose. The purpose of this code is to provide mini- 
mum requirements to safeguard the public safety, health and 
general welfare through affordability, structural strength, 
means of egress facilities, stability, sanitation, light and venti- 
lation, energy conservation and safety to life and property from 
fire and other hazards attributed to the built environment. 



SECTION R102 
APPLICABILITY 

R102.1 GeneraL Where, in any specific case, different sec- 
tions of this code specify different materials, methods of con- 
struction or other requirements, the most restrictive shall 
govern. Where there is a conflict between a general require- 
ment and a specific requirement, the specific requirement shall 
be applicable. 

R102.2 Other laws. The provisions of this code shall not be 
deemed to nullify any provisions of local, state or federal law. 

R102.3 Application of references. References to chapter or 
section numbers, or to provisions not specifically identified by 
number, shall be construed to refer to such chapter, section or 
provision of this code. 

R102.4 Referenced codes and standards. The codes and 
standards referenced in this code shall be considered part of the 
requirements of this code to the prescribed extent of each such 
reference. Where differences occur between provisions of this 
code and referenced codes and standards, the provisions of this 
code shall apply. 

Exception: Where enforcement of a code provision would 
violate the conditions of the listing of the equipment or 
appliance, the conditions of the listing and manufacturer's 
instructions shall apply. 



R102.5 Appendices. Provisions in the appendices shall not 
apply unless specifically referenced in the adopting ordinance. 

R102.6 Partial invalidity. In the event any part or provision of 
this code is held to be illegal or void, this shall not have the 
effect of making void or illegal any of the other parts or provi- 
sions. 

R102.7 Existing structures. The legal occupancy of any struc- 
ture existing on the date of adoption of this code shall be per- 
mitted to continue without change, except as is specifically 
covered in this code, the International Property Maintenance 
Code or the International Fire Code, or as is deemed necessary 
by the building official for the general safety and welfare of the 
occupants and the public. 

R102.7.1 Additions, alterations or repairs. Additions, 
alterations or repairs to any structure shall conform to the 
requirements for a new structure without requiring the 
existing structure to comply with all of the requirements of 
this code, unless otherwise stated. Additions, alterations or 
repairs shall not cause an existing structure to become 
unsafe or adversely affect the performance of the building. 



SECTION R1 03 
DEPARTMENT OF BUILDING SAFETY 

R103.1 Creation of enforcement agency. The department of 
building safety is hereby created and the official in charge 
thereof shall be known as the building official. 

R103.2 Appointment. The building official shall be appointed 
by the chief appointing authority of the jurisdiction. 

R103.3 Deputies. In accordance with the prescribed proce- 
dures of this jurisdiction and with the concurrence of the 
appointing authority, the building official shall have the author- 
ity to appoint a deputy building official, the related technical 
officers, inspectors, plan examiners and other employees. Such 
employees shall have powers as delegated by the building 
official. 



SECTION R104 

DUTIES AND POWERS OF THE 

BUILDING OFFICIAL 

R104.1 General. The building official is hereby authorized 
and directed to enforce the provisions of this code. The build- 
ing official shall have the authority to render interpretations of 
this code and to adopt policies and procedures in order to clar- 
ify the application of its provisions. Such interpretations, poli- 
cies and procedures shall be in conformance with the intent and 
purpose of this code. Such policies and procedures shall not 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



ADMINISTRATION 



have the effect of waiving requirements specifically provided 
for in this code. 

R104.2 Applications and permits. The building official shall 
receive applications, review construction documents and issue 
permits for the erection and alteration of buildings and struc- 
tures, inspect the premises for which such permits have been 
issued and enforce compliance with the provisions of this code. 

R104.3 Notices and orders. The building official shall issue 
all necessary notices or orders to ensure compliance with this 
code. 

R104.4 Inspections. The building official is authorized to 
make all of the required inspections, or the building official 
shall have the authority to accept reports of inspection by 
approved agencies or individuals. Reports of such inspections 
shall be in writing and be certified by a responsible officer of 
such approved agency or by the responsible individual. The 
building official is authorized to engage such expert opinion as 
deemed necessary to report upon unusual technical issues that 
arise, subject to the approval of the appointing authority. 

R104.5 Identification. The building official shall carry proper 
identification when inspecting structures or premises in the 
performance of duties under this code. 

R104.6 Right of entry. Where it is necessary to make an 
inspection to enforce the provisions of this code, or where the 
building official has reasonable cause to believe that there 
exists in a structure or upon a premises a condition which is 
contrary to or in violation of this code which makes the struc- 
ture or premises unsafe, dangerous or hazardous, the building 
official or designee is authorized to enter the structure or pre- 
mises at reasonable times to inspect or to perform the duties 
imposed by this code, provided that if such structure or pre- 
mises be occupied that credentials be presented to the occupant 
and entry requested. If such structure or premises be unoccu- 
pied, the building official shall first make a reasonable effort to 
locate the owner or other person having charge or control of the 
structure or premises and request entry. If entry is refused, the 
building official shall have recourse to the remedies provided 
by law to secure entry. 

R104.7 Department records. The building official shall keep 
official records of applications received, permits and certifi- 
cates issued, fees collected, reports of inspections, and notices 
and orders issued. Such records shall be retained in the official 
records for the period required for the retention of public 
records. 

R104.8 Liability. The building official, member of the board 
of appeals or employee charged with the enforcement of this 
code, while acting for the jurisdiction in good faith and without 
mahce in the discharge of the duties required by this code or 
other pertinent law or ordinance, shall not thereby be rendered 
liable personally and is hereby relieved from personal liability 
for any damage accruing to persons or property as a result of 
any act or by reason of an act or omission in the discharge of 
official duties. Any suit instituted against an officer or 
employee because of an act performed by that officer or 
employee in the lawful discharge of duties and under the provi- 



sions of this code shall be defended by legal representative of 
the jurisdiction until the final termination of the proceedings. 
The building official or any subordinate shall not be liable for 
cost in any action, suit or proceeding that is instituted in 
pursuance of the provisions of this code. 

R104.9 Approved materials and equipment. Materials, 
equipment and devices approved by the building official shall 
be constructed and installed in accordance with such approval. 

R104.9.1 Used materials and equipment. Used materials, 
equipment and devices shall not be reused unless approved 
by the building official. 

R104.10 Modifications. Wherever there are practical difficul- 
ties involved in carrying out the provisions of this code, the 
building official shall have the authority to grant modifications 
for individual cases, provided the building official shall first 
find that special individual reason makes the strict letter of this 
code impractical and the modification is in compliance with the 
intent and purpose of this code and that such modification does 
not lessen health, life and fire safety requirements or structural. 
The details of action granting modifications shall be recorded 
and entered in the files of the department of building safety. 

R104.10.1 Areas prone to flooding. The building official 
shall not grant modifications to any provision related to 
areas prone to flooding as established by Table R301.2(l) 
without the granting of a variance to such provisions by the 
board of appeals. 

R104.il Alternative materials, design and methods of con- 
struction and equipment. The provisions of this code are not 
intended to prevent the installation of any material or to pro- 
hibit any design or method of construction not specifically pre- 
scribed by this code, provided that any such alternative has 
been approved. An alternative material, design or method of 
construction shall be approved where the building official finds 
that the proposed design is satisfactory and complies with the 
intent of the provisions of this code, and that the material, 
method or work offered is, for the purpose intended, at least the 
equivalent of that prescribed in this code. CompUance with the 
specific performance-based provisions of the International 
Codes in lieu of specific requirements of this code shall also be 
permitted as an alternate. 

R104.11.1 Tests. Whenever there is insufficient evidence of 
compliance with the provisions of this code, or evidence 
that a material or method does not conform to the require- 
ments of this code, or in order to substantiate claims for 
alternative materials or methods, the building official shall 
have the authority to require tests as evidence of pompliance 
to be made at no expense to the jurisdiction. Test methods 
shall be as specified in this code or by other recognized test 
standards. In the absence of recognized and accepted test 
methods, the building official shall approve the .testing pro- 
cedures. Tests shall be performed by an approved agency. 
Reports of such tests shall be retained by the building offi- 
cial for the period required for retention of public records. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



ADMINISTRATION 



SECTION R1 05 
PERMITS 

R105.1 Required. Any owner or authorized agent who intends 
to construct, enlarge, alter, repair, move, demolish or change 
the occupancy of a building or structure, or to erect, install, 
enlarge, alter, repair, remove, convert or replace any electrical, 
gas, mechanical or plumbing system, the installation of which 
is regulated by this code, or to cause any such work to be done, 
shall first make application to the building official and obtain 
the required permit. 

R105.2 Work exempt from permit. Permits shall not be 
required for the following. Exemption from permit require- 
ments of this code shall not be deemed to grant authorization 
for any work to be done in any manner in violation of the provi- 
sions of this code or any other laws or ordinances of this 
jurisdiction. 

Building: 

II . One-story detached accessory structures used as tool and 
storage sheds, playhouses and similar uses, provided the 
floor area does not exceed 120 square feet (11.15 m^). 

2. Fences not over 6 feet (1829 mm) high. 

3. Retaining walls that are not over 4 feet (1219 mm) in 
height measured from the bottom of the footing to the top 
of the wall, unless supporting a surcharge. 

4. Water tanks supported direcdy upon grade if the capacity 
does not exceed 5,000 gallons (18 927 L) and the ratio of 
height to diameter or width does not exceed 2 to 1 . 

I 5. Sidewalks and driveways. 

6. Painting, papering, tiling, carpeting, cabinets, counter 
tops and similar finish work. 

7. Prefabricated swimming pools that are less than 24 
inches (610 mm) deep. 

I 8. Swings and other playground equipment. 

9. Window awnings supported by an exterior wall which 
do not project more than 54 inches (1372 mm) from the 
exterior wall and do not require additional support. 

Electrical: 

Repairs and maintenance: A permit shall not be required for 
minor repair work, including the replacement of lamps or the 
connection of approved portable electrical equipment to 
approved permanently installed receptacles. 

Gas: 

1. Portable heating, cooking or clothes drying appliances. 

2. Replacement of any minor part that does not alter 
approval of equipment or make such equipment unsafe. 

3. Portable-fuel-cell appHances that are not connected to a 
fixed piping system and are not interconnected to a 
power grid. 

Mechanical: 

1. Portable heating appliances. 

2. Portable ventilation appliances. 

3. Portable cooling units. 



4. Steam, hot or chilled water piping within any heating or 
cooling equipment regulated by this code. 

5. Replacement of any minor part that does not alter 
approval of equipment or make such equipment unsafe. 

6. Portable evaporative coolers. 

7. Self-contained refrigeration systems containing 10 
pounds (4.54 kg) or less of refrigerant or that are actuated 
by motors of 1 horsepower (746 W) or less. 

8. Portable-fuel-cell appliances that are not connected to a 
fixed piping system and are not interconnected to a 
power grid. 

The stopping of leaks in drains, water, soil, waste or vent pipe; 
provided, however, that if any concealed trap, drainpipe, water, 
soil, waste or vent pipe becomes defective and it becomes nec- 
essary to remove and replace the same with new material, such 
work shall be considered as new work and a permit shall be 
obtained and inspection made as provided in this code. 

The clearing of stoppages or the repairing of leaks in pipes, 
valves or fixtures, and the removal and reinstallation of water 
closets, provided such repairs do not involve or require the 
replacement or rearrangement of valves, pipes or fixtures. 

R105.2.1 Emergency repairs. Where equipment replace- 
ments and repairs must be performed in an emergency situa- 
tion, the permit application shall be submitted within the 
next working business day to the building official. 

R105.2.2 Repairs. Application or notice to the building 
official is not required for ordinary repairs to structures, 
replacement of lamps or the connection of approved porta- 
ble electrical equipment to approved permanently installed 
receptacles. Such repairs shall not include the cutting away 
of any wall, partition or portion thereof, the removal or cut- 
ting of any structural beam or load-bearing support, or the 
removal or change of any required means of egress, or rear- 
rangement of parts of a structure affecting the egress 
requirements; nor shall ordinary repairs include addition to, 
alteration of, replacement or relocation of any water supply, 
sewer, drainage, drain leader, gas, soil, waste, vent or simi- 
lar piping, electric wiring or mechanical or other work 
affecting public health or general safety. 

R105.2.3 Public service agencies. A permit shall not be 
required for the installation, alteration or repair of genera- 
tion, transmission, distribution, metering or other related 
equipment that is under the ownership and control of pubhc 
service agencies by established right. 

R105.3 Application for permit. To obtain a permit, the appli- 
cant shall first file an application therefor in writing on a form 
furnished by the department of building safety for that purpose. 
Such application shall: 

1 . Identify and describe the work to be covered by the per- 
mit for which application is made. 

2. Describe the land on which the proposed work is to be 
done by legal description, street address or similar 
description that will readily identify and definitely locate 
the proposed building or work. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



ADMINISTRATION 



3. Indicate the use and occupancy for which the proposed 
work is intended. 

4. Be accompanied by construction documents and other 
information as required in Section R106.1. 

5. State the valuation of the proposed work. 

6. Be signed by the applicant or the applicant's authorized 
agent. 

7. Give such other data and information as required by the 
building official. 

R105.3.1 Action on application. The building official 
shall examine or cause to be examined applications for per- 
mits and amendments thereto within a reasonable time 
after filing. If the application or the construction docu- 
ments do not conform to the requirements of pertinent 
laws, the building official shall reject such application in 
writing, stating the reasons therefor. If the building official 
is satisfied that the proposed work conforms to the require- 
ments of this code and laws and ordinances applicable 
thereto, the building official shall issue a permit therefor as 
soon as practicable. 

R105.3.1.1 Determination of substantially improved 
or substantially damaged existing buildings in flood 
hazard areas. For applications for reconstruction, reha- 
bilitation, addition or other improvement of existing 
buildings or structures located in an area prone to flood- 
ing as established by Table R301.2(l), the building offi- 
cial shall examine or cause to be examined the 
construction documents and shall prepare a finding with 
regard to the value of the proposed work. For buildings 
that have sustained damage of any origin, the value of the 
proposed work shall include the cost to repair the build- 
ing or structure to its predamage condition. If the build- 
ing official finds that the value of proposed work equals 
or exceeds 50 percent of the market value of the building 
or structure before the damage has occurred or the 
improvement is started, the finding shall be provided to 
the board of appeals for a determination of substantial 
improvement or substantial damage. Applications deter- 
mined by the board of appeals to constitute substantial 
improvement or substantial damage shall meet the 
requirements of Section R324. 

R105.3.2 Time limitation of application. An application 
for a permit for any proposed work shall be deemed to have 
been abandoned 180 days after the date of filing unless such 
application has been pursued in good faith or a permit has 
been issued; except that the building official is authorized to 
grant one or more extensions of time for additional periods 
not exceeding 180 days each. The extension shall be 
requested in writing and justifiable cause demonstrated. 

R105.4 Validity of permit. The issuance or granting of a per- 
mit shall not be construed to be a permit for, or an approval of, 
any violation of any of the provisions of this code or of any 
other ordinance of the jurisdiction. Permits presuming to give 
authority to violate or cancel the provisions of this code or 
other ordinances of the jurisdiction shall not be valid. The issu- 
ance of a permit based on construction documents and other 
data shall not prevent the building official from requiring the 



correction of errors in the construction documents and other 
data. The building official is also authorized to prevent occu- 
pancy or use of a structure where in violation of this code or of 
any other ordinances of this jurisdiction. 

R105.5 Expiration. Every permit issued shall become 
invalid unless the work authorized by such perrnit is com- 
menced within 180 days after its issuance, or if the work 
authorized by such permit is suspended or abandoned for a 
period of 1 80 days after the time the work is commenced. The 
building official is authorized to grant, in writing, one or more 
extensions of time, for periods not more than 180 days each. 
The extension shall be requested in writing and justifiable 
cause demonstrated. 

R105.6 Suspension or revocation. The building official is 
authorized to suspend or revoke a permit issued under the pro- 
visions of this code wherever the permit is issued in error or on 
the basis of incorrect, inaccurate or incomplete information, or 
in violation of any ordinance or regulation or any of the provi- 
sions of this code. 

R105.7 Placement of permit. The building permit or copy 
thereof shall be kept on the site of the work until the completion 
of the project. 

R105.8 Responsibility. It shall be the duty of every person 
who performs work for the installation or repair of building, 
structure, electrical, gas, mechanical or plumbing systems, for 
which this code is applicable, to comply with this code. 



SECTION R106 
CONSTRUCTION DOCUMENTS 

R106.1 Submittal documents. Construction documents, spe- 
cial inspection and structural observation programs and other 
data shall be submitted in one or more sets with each applica- 
tion for a permit. The construction documents shall be prepared 
by a registered design professional where required by the stat- 
utes of the jurisdiction in which the project is to be constructed. 
Where special conditions exist, the building official is autho- 
rized to require additional construction documents to be pre- 
pared by a registered design professional. 

Exception: The building official is authorized to waive the 
submission of construction documents and other data not 
required to be prepared by a registered design professional 
if it is found that the nature of the work applied for is such 
that reviewing of construction documents is not necessary 
to obtain compliance with this code. 

R106.1.1 Information on construction docuiinents. Con- 
struction documents shall be drawn upon suitable material. 

■ Electronic media documents are permitted to tie submitted 
when approved by the building official. Construction docu- 

i ments shall be of sufficient clarity to indicate the location, 

, nature and extent of the work proposed and show in detail 
that it will conform to the provisions of this cdde and rele- 

; vant laws, ordinances, rules and regulations, asi determined 
by the building official. I 

R106.1.2 Manufacturer's installation instructions. Man- 
ufacturer's installation instructions, as required by this 

2006 INTERNATIONAL RESIDENTIAL CODE® 



ADMINISTRATION 



code, shall be available on the job site at the time of 
inspection. 

R106.1.3 Information for construction in flood hazard 
areas. For buildings and structures located in whole or in 
part in flood hazard areas as established by Table R30 1.2(1), 
construction documents shall include: 

1 . Delineation of flood hazard areas, floodway bound- 
aries and flood zones and the design flood elevation, 
as appropriate; 

2. The elevation of the proposed lowest floor, including 
basement; in areas of shallow flooding (AO zones), 
the height of the proposed lowest floor, including 
basement, above the highest adjacent grade; and 

3. The elevation of the bottom of the lowest horizontal 
structural member in coastal high hazard areas (V 
Zone); and 

4. If design flood elevations are not included on the 
community's Flood Insurance Rate Map (FIRM), the 
building official and the applicant shall obtain and 
reasonably utilize any design flood elevation and 
floodway data available from other sources. 

R106.2 Site plan. The construction documents submitted with 
the application for permit shall be accompanied by a site plan 
showing the size and location of new construction and existing 
structures on the site and distances from lot lines. In the case of 
demolition, the site plan shall show construction to be demol- 
ished and the location and size of existing structures and con- 
struction that are to remain on the site or plot. 

R106.3 Examination of documents. The building official 
shall examine or cause to be examined construction documents 
for code compliance. 

R106.3.1 Approval of construction documents. When the 
building official issues a permit, the construction documents 
shall be approved, in writing or by a stamp which states 
"APPROVED PLANS PER IRC SECTION R106.3 . 1 ." One 
set of construction documents so reviewed shall be retained 
by the building official. The other set shall be returned to the 
applicant, shall be kept at the site of work and shall be open to 
inspection by the building official or his or her authorized 
representative. 

R106.3.2 Previous approvals. This code shall not require 
changes in the construction documents, construction or des- 
ignated occupancy of a structure for which a lawful permit 
has been heretofore issued or otherwise lawfully autho- 
rized, and the construction of which has been pursued in 
good faith within 180 days after the effective date of this 
code and has not been abandoned. 

R106.3.3 Phased approval. The building official is autho- 
rized to issue a permit for the construction of foundations or 
any other part of a building or structure before the construc- 
tion documents for the whole building or structure have been 
submitted, provided that adequate information and detailed 
statements have been filed complying with pertinent require- 
ments of this code. The holder of such permit for the founda- 
tion or other parts of a building or structure shall proceed at 



the holder's own risk with the building operation and without 
assurance that a permit for the entire structure will be granted. 

R106.4 Amended construction documents. Work shall be 
installed in accordance with the approved construction docu- 
ments, and any changes made during construction that are not 
in compHance with the approved construction documents shall 
be resubmitted for approval as an amended set of construction 
documents. 

R106.5 Retention of construction documents. One set of 

approved construction documents shall be retained by the 
building official for a period of not less than 1 80 days from date 
of completion of the permitted work, or as required by state or 
local laws. 



SECTION R107 
TEMPORARY STRUCTURES AND USES 

R107.1 General. The building official is authorized to issue a 
permit for temporary structures and temporary uses. Such per- 
mits shall be limited as to time of service, but shall not be per- 
mitted for more than 180 days. The building official is 
authorized to grant extensions for demonstrated cause. 

R107.2 Conformance. Temporary structures and uses shall 
conform to the structural strength, fire safety, means of egress, 
light, ventilation and sanitary requirements of this code as nec- 
essary to ensure the public health, safety and general welfare. 

R107.3 Temporary power. The building official is authorized 
to give permission to temporarily supply and use power in part 
of an electric installation before such installation has been fully 
completed and the final certificate of completion has been 
issued. The part covered by the temporary certificate shall 
comply with the requirements specified for temporary lighting, 
heat or power in the ICC Electrical Code. 

R107.4 Termination of approval. The building official is 
authorized to terminate such permit for a temporary structure 
or use and to order the temporary structure or use to be 
discontinued. 



SECTION R108 
FEES 

R108.1 Payment of fees. A permit shall not be vahd undl the 
fees prescribed by law have been paid. Nor shall an amendment 
to a permit be released until the additional fee, if any, has been 
paid. 

R108.2 Schedule of permit fees. On buildings, structures, 
electrical, gas, mechanical and plumbing systems or alterations 
requiring a permit, a fee for each permit shall be paid as 
required, in accordance with the schedule as established by the 
applicable governing authority. 

R108.3 Building permit valuations. Building permit valua- 
tion shall include total value of the work for which a permit is 
being issued, such as electrical, gas, mechanical, plumbing 
equipment and other permanent systems, including materials 
and labor. 

R108.4 Related fees. The payment of the fee for the construc- 
tion, alteration, removal or demolition for work done in con- 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ADMINISTRATION 



nection with or concurrently with the work authorized by a 
building permit shall not relieve the applicant or holder of the 
permit from the payment of other fees that are prescribed by 
law. 

R108.5 Refunds. The building official is authorized to estab- 
lish a refund policy. 



SECTION R109 
INSPECTIONS 

R109.1 Types of inspections. For onsite construction, from 
time to time the building official, upon notification from the 
permit holder or his agent, shall make or cause to be made any 
necessary inspections and shall either approve that portion of 
the construction as completed or shall notify the permit holder 
or his or her agent wherein the same fails to comply with this 
code. 

R109.1.1 Foundation inspection. Inspection of the foun- 
dation shall be made after poles or piers are set or trenches or 
basement areas are excavated and any required forms 
erected and any required reinforcing steel is in place and 
supported prior to the placing of concrete. The foundation 
inspection shall include excavations for thickened slabs 
intended for the support of bearing walls, partitions, struc- 
tural supports, or equipment and special requirements for 
wood foundations. 

R109.1.2 Plumbing, mechanical, gas and electrical sys- 
tems inspection. Rough inspection of plumbing, mechani- 
cal, gas and electrical systems shall be made prior to 
covering or concealment, before fixtures or appliances are 
set or installed, and prior to framing inspection. 

Exception: Back-filling of ground-source heat pump 
loop systems tested in accordance with Section M2 105.1 
prior to inspection shall be permitted. 

R109.1.3 Floodplain inspections. For construction in 
areas prone to flooding as established by Table R301.2(l), 
upon placement of the lowest floor, including basement, and 
prior to further vertical construction, the building official 
shall require submission of documentation, prepared and 
sealed by a registered design professional, of the elevation 
of the lowest floor, including basement, required in Section 
R324. 

R109.1.4 Frame and masonry inspection. Inspection of 
framing and masonry construction shall be made after the 
roof, masonry, all framing, firestopping, draftstopping and 
bracing are in place and after the plumbing, mechanical and 
electrical rough inspections are approved. 

R109.1.5 Other inspections. In addition to the called 
inspections above, the building official may make or require 
any other inspections to ascertain compliance with this code 
and other laws enforced by the building official. 

R109. 1.5.1 Fire-resistance-rated construction 
inspection. Where fire-resistance-rated construction is 
required between dwelling units or due to location on 
property, the building official shall require an inspection 
of such construction after all lathing and/or wallboard is 



in place, but before any plaster is applied, or before wall- 
board joints and fasteners are taped and finished. 

R109.1.6 Final inspection. Final inspection shall be made 
after the permitted work is complete and prior to occupancy. 

R109.2 Inspection agencies. The building official is authorized 
to accept reports of approved agencies, provided such agencies 
satisfy the requirements as to qualifications and reliability. 

R109.3 Inspection requests. It shall be the duty of the permit 
holder or their agent to notify the building official that such 
work is ready for inspection. It shall be the duty of the person 
requesting any inspections required by this code to provide 
access to and means for inspection of such work. 

R109.4 Approval required. Work shall not be done beyond 
the point indicated in each successive inspection without first 
obtaining the approval of the building official. The building 
official upon notification, shall make the requested inspections 
and shall either indicate the portion of the construction that is 
satisfactory as completed, or shall notify the permit holder or 
an agent of the permit holder wherein the same fails to comply 
with this code. Any portions that do not comply shall be cor- 
rected and such portion shall not be covered or concealed until 
authorized by the building official. 



SECTION R1 10 
CERTIFICATE OF OCCUPANCY 

RllO.l Use and occupancy. No building or structure shall be 
used or occupied, and no change in the existing occupancy 
classification of a building or structure or portion thereof shall 
be made until the building official has issued a certificate of 
occupancy therefor as provided herein. Issuance of a certificate 
of occupancy shall not be construed as an approval of a viola- 
tion of the provisions of this code or of other ordinances of the 
jurisdiction. Certificates presuming to give authority to violate 
or cancel the provisions of this code or other ordinances of the 
jurisdiction shall not be valid. 

Exceptions: 

1 . Certificates of occupancy are not required for work 
exempt from permits under Section R105.2. 

2. Accessory buildings or structures. 

RllO.l Change in use. Changes in the character or use of an 
existing structure shall not be made except as specified in Sec- 
tions 3406 and 3407 of the International Building Code. 

R110.3 Certificate issued. After the building official inspects 
the building or structure and finds no violations of the provi- 
sions of this code or other laws that are enforced by the depart- 
ment of building safety, the building official shall issue a 
certificate of occupancy which shall contain the following: 

1. The building permit number. I 

2. The address of the structure. \ 

3. The name and address of the owner. 

4. A description of that portion of the structure for which 
the certificate is issued. 

2006 INTERNATIONAL RESIDENTIAL CODE® 



ADMINISTRATION 



5. A statement that the described portion of the structure 
has been inspected for compliance with the requirements 
of this code. 

6. The name of the building official. 

7. The edition of the code under which the permit was 
issued. 

8. If an automatic sprinkler system is provided and whether 
the sprinkler system is required. 

9. Any special stipulations and conditions of the building 
permit. 

R110.4 Temporary occupancy. The building official is autho- 
rized to issue a temporary certificate of occupancy before the 
completion of the entire work covered by the permit, provided 
that such portion or portions shall be occupied safely. The 
building official shall set a time period during which the tempo- 
rary certificate of occupancy is valid. 

R110.5 Revocation. The building official shall, in writing, 
suspend or revoke a certificate of occupancy issued under the 
provisions of this code wherever the certificate is issued in 
error, or on the basis of incorrect information supplied, or 
where it is determined that the building or structure or portion 
thereof is in violation of any ordinance or regulation or any of 
the provisions of this code. 



SECTION R1 11 
SERVICE UTILITIES 

Rlll.l Connection of service utilities. No person shall make 
connections from a utility, source of energy, fuel or power to 
any building or system that is regulated by this code for which a 
permit is required, until approved by the building official. 

R111.2 Temporary connection. The building official shall 
have the authority to authorize and approve the temporary con- 
nection of the building or system to the utility, source of energy, 
fuel or power. 

R111.3 Authority to disconnect service utilities. The build- 
ing official shall have the authority to authorize disconnection 
of utility service to the building, structure or system regulated 
by this code and the referenced codes and standards set forth in 
Section R102.4 in case of emergency where necessary to elimi- 
nate an immediate hazard to life or property or when such util- 
ity connection has been made without the approval required by 
Section Rl 1 1 . 1 or Rl 11 .2. The building official shall notify the 
serving utility and whenever possible the owner and occupant 
of the building, structure or service system of the decision to 
disconnect prior to taking such action if not notified prior to 
disconnection. The owner or occupant of the building, struc- 
ture or service system shall be notified in writing as soon as 
practical thereafter. 



SECTION Rl 12 
BOARD OF APPEALS 

R112.1 General. In order to hear and decide appeals of orders, 
decisions or determinations made by the building official rela- 
tive to the application and interpretation of this code, there shall 
be and is hereby created a board of appeals. The building offi- 



cial shall be an ex officio member of said board but shall have 
no vote on any matter before the board. The board of appeals 
shall be appointed by the governing body and shall hold office 
at its pleasure. The board shall adopt rules of procedure for 
conducting its business, and shall render all decisions and find- 
ings in writing to the appellant with a duplicate copy to the 
building official. 

R112.2 Limitations on authority. An application for appeal 
shall be based on a claim that the true intent of this code or the 
rules legally adopted thereunder have been incorrectly inter- 
preted, the provisions of this code do not fully apply, or an 
equally good or better form of construction is proposed. The 
board shall have no authority to waive requirements of this 
code. 

Rl 12.2.1 Determination of substantial improvement in 
areas prone to flooding. When the building official pro- 
vides a finding required in Section R 105. 3. 1.1, the board of 
appeals shall determine whether the value of the proposed 
work constitutes a substantial improvement. A substantial 
improvement means any repair, reconstruction, rehabilita- 
tion, addition or improvement of a building or structure, the 
cost of which equals or exceeds 50 percent of the market 
value of the building or structure before the improvement or 
repair is started. If the building or structure has sustained 
substantial damage, all repairs are considered substantial 
improvement regardless of the actual repair work 
performed. The term does not include: 

1 . Improvements of a building or structure required to 
correct existing health, sanitary or safety code viola- 
tions identified by the building official and which are 
the minimum necessary to assure safe living 
conditions; or 

2. Any alteration of an historic building or structure, 
provided that the alteration will not preclude the con- 
tinued designation as an historic building or structure. 
For the purpose of this exclusion, an historic building 
is: 

2.1. Listed or preliminarily determined to be eligi- 
ble for listing in the National Register of His- 
toric Places; or 

2.2. Determined by the Secretary of the U.S. De- 
partment of Interior as contributing to the his- 
torical significance of a registered historic 
district or a district preliminarily determined 
to qualify as an historic district; or 

2.3. Designated as historic under a state or local 
historic preservation program that is ap- 
proved by the Department of Interior. 

Rl 12.2.2 Criteria for issuance of a variance for areas 
prone to flooding. A variance shall only be issued upon: 

1. A showing of good and sufficient cause that the 
unique characteristics of the size, configuration or 
topography of the site render the elevation standards I 
in Section R324 inappropriate. I 



2006 INTERNATIONAL RESIDENTIAL CODE' 



o 



ADMINISTRATION 



2. A determination that failure to grant the variance 
would result in exceptional hardship by rendering the 
lot undevelopable. 

3. A determination that the granting of a variance will 
not result in increased flood heights, additional 
threats to public safety, extraordinary public expense, 
nor create nuisances, cause fraud on or victimization 
of the public, or conflict with existing local laws or 
ordinances. 

4. A determination that the variance is the minimum 
necessary to afford relief, considering the flood 
hazard. 

5. Submission to the applicant of written notice specify- 
ing the difference between the design flood elevation 
and the elevation to which the building is to be built, 
stating that the cost of flood insurance will be com- 
mensurate with the increased risk resulting from the 
reduced floor elevation, and stating that construction 
below the design flood elevation increases risks to life 
and property. 

R112.3 Qualifications. The board of appeals shall consist of 
members who are qualified by experience and training to pass 
on matters pertaining to building construction and are not 
employees of the jurisdiction. 

R112.4 Administration. The building official shall take 
immediate action in accordance with the decision of the board. 



issued under the provisions of this code, shall be subject to pen- 
alties as prescribed by law. 



SECTION R1 14 
STOP WORK ORDER 

R114.1 Notice to owner. Upon notice from the building offi- 
cial that work on any building or structure is being prosecuted 
contrary to the provisions of this code or in an unsafe and dan- 
gerous manner, such work shall be immediately stopped. The 
stop work order shall be in writing and shall be given to the 
owner of the property involved, or to the owner's agent or to the 
person doing the work and shall state the conditions under 
which work will be permitted to resume. 

R114.2 Unlawful continuance. Any person who shall con- 
tinue any work in or about the structure after having been 
served with a stop work order, except such work as that person 
is directed to perform to remove a violation or unsafe condi- 
tion, shall be subject to penalties as prescribed by law. 



SECTION R1 13 
VIOLATIONS 

R113.1 Unlawful acts. It shall be unlawful for any person, firm 
or corporation to erect, construct, alter, extend, repair, move, 
remove, demolish or occupy any building, structure or equip- 
ment regulated by this code, or cause same to be done, in con- 
flict with or in violation of any of the provisions of this code. 

R113.2 Notice of violation. The building official is authorized 
to serve a notice of violation or order on the person responsible 
for the erection, construction, alteration, extension, repair, 
moving, removal, demolition or occupancy of a building or 
structure in violation of the provisions of this code, or in viola- 
tion of a detail statement or a plan approved thereunder, or in 
violation of a permit or certificate issued under the provisions 
of this code. Such order shall direct the discontinuance of the 
illegal action or condition and the abatement of the violation. 

R113.3 Prosecution of violation. If the notice of violation is 
not complied with in the time prescribed by such notice, the 
building official is authorized to request the legal counsel of the 
jurisdiction to institute the appropriate proceeding at law or in 
equity to restrain, correct or abate such violation, or to require 
the removal or termination of the unlawful occupancy of the 
building or structure in violation of the provisions of this code 
or of the order or direction made pursuant thereto. 

R113.4 Violation penalties. Any person who violates a provi- 
sion of this code or fails to comply with any of the requirements 
thereof or who erects, constructs, alters or repairs a building or 
structure in violation of the approved construction documents 
or directive of the building official, or of a permit or certificate 



8 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



Part II — Definitions 



CHAPTER 2 

DEFINITIONS 



SECTION R201 
GENERAL 

R201.1 Scope. Unless otherwise expressly stated, the follow- 
ing words and terms shall, for the purposes of this code, have 
the meanings indicated in this chapter. 

R201.2 Interchangeability. Words used in the present tense 
include the future; words in the masculine gender include the 
feminine and neuter; the singular number includes the plural 
and the plural, the singular. 

R201.3 Terms defined in other codes. Where terms are not 
defined in this code such terms shall have meanings ascribed to 
them as in other code publications of the International Code 
Council. 

R201.4 Terms not defined. Where terms are not defined 
through the methods authorized by this section, such terms 
shall have ordinarily accepted meanings such as the context 
implies. 



SECTION R202 
DEFINITIONS 

ACCESSIBLE. Signifies access that requires the removal of 
an access panel or similar removable obstruction. 

ACCESSIBLE, READILY. Signifies access without the 
necessity for removing a panel or similar obstruction. 

ACCESSORY STRUCTURE. A structure not greater than 
3,000 square feet (279 m^) in floor area, and not over two sto- 
ries in height, the use of which is customarily accessory to and 
incidental to that of the dwelling(s) and which is located on the 
same lot. 

ADDITION. An extension or increase in floor area or height 
of a building or structure. 

AIR ADMITTANCE VALVE. A one-way valve designed to 
allow air into the plumbing drainage system when a negative 
pressure develops in the piping. This device shall close by grav- 
ity and seal the terminal under conditions of zero differential 
pressure (no flow conditions) and under positive internal pres- 
sure. 

AIR BREAK (DRAINAGE SYSTEM). An arrangement in 
which a discharge pipe from a fixture, appliance or device 
drains indirectly into a receptor below the flood-level rim of the 
receptor, and above the trap seal. 

AIR CIRCULATION, FORCED. A means of providing 
space conditioning utilizing movement of air through ducts or 
plenums by mechanical means. 



AIR-CONDITIONING SYSTEM. A system that consists of 
heat exchangers, blowers, filters, supply, exhaust and return-air 
systems, and shall include any apparatus installed in connec- 
tion therewith. 

AIR GAP, DRAINAGE SYSTEM. The unobstructed vertical 
distance through free atmosphere between the outlet of a waste 
pipe and the flood-level rim of the fixture or receptor into 
which it is discharging. 

AIR GAP, WATER-DISTRIBUTION SYSTEM. The unob- 
structed vertical distance through free atmosphere between the 
lowest opening from a water supply discharge to the 
flood-level rim of a plumbing fixture. 

ALTERATION. Any construction or renovation to an existing 
structure other than repair or addition that requires a permit. 
Also, a change in a mechanical system that involves an exten- 
sion, addition or change to the arrangement, type or purpose of 
the original installation that requires a permit. 

ANCHORS. See "Supports." 

ANTISIPHON. A term applied to valves or mechanical 
devices that eliminate siphonage. 

APPLIANCE. A device or apparatus that is manufactured and 
designed to utihze energy and for which this code provides spe- 
cific requirements. 

APPROVED. Acceptable to the building official. 

APPROVED AGENCY. An established and recognized 
agency regularly engaged in conducting tests or furnishing 
inspection services, when such agency has been approved by 
the building official. 

ASPECT RATIO. The ratio of the height to width (h/w) of a 
shear wall. The shear wall height is the maximum clear height 
from top of foundation or diaphragm to bottom of diaphragm 
framing above and the shear wall width is the sheathed dimen- 
sion in the direction of applied force on the shear wall. 

ATTIC. The unfinished space between the ceiling joists of the 
top story and the roof rafters. 

BACKFLOW, DRAINAGE. A reversal of flow in the drain- 
age system. 

BACKFLOW PREVENTER. A device or means to prevent 
backflow. 

BACKFLOW PREVENTER, REDUCED-PRESSURE- 
ZONE TYPE. A backflow-prevention device consisting of 
two independentiy acting check valves, internally force loaded 
to a normally closed position and separated by an intermediate 
chamber (or zone) in which there is an automatic relief means 
of venting to atmosphere internally loaded to a normally open 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



DEFINITIONS 



position between two tightly closing shutoff valves and with 
means for testing for tightness of the checks and opening of 
relief means. 

BACKFLOW, WATER DISTRIBUTION. The flow of water 
or other liquids into the potable water-supply piping from any 
sources other than its intended source. Backsiphonage is one 
type of backflow. 

BACKPRESSURE. Pressure created by any means in the 
water distribution system, which by being in excess of the pres- 
sure in the water supply mains causes a potential backflow con- 
dition. 

BACKPRESSURE, LOW HEAD. A pressure less than or 
equal to 4.33 psi (29.88 kPa) or the pressure exerted by a 
10-foot (3048 mm) column of water. 

BACKSIPHONAGE. The flowing back of used or contami- 
nated water from piping into a potable water-supply pipe due to 
a negative pressure in such pipe. 

BACKWATER VALVE. A device installed in a drain or pipe 
to prevent backflow of sewage. 

BALCONY, EXTERIOR. An exterior floor projecting from 
and supported by a structure without additional independent 
supports. 

BALL COCK. A valve that is used inside a gravity-type water 
closet flush tank to control the supply of water into the tank. It 
may also be called a flush-tank fill valve or water control. 

BASEMENT. That portion of a building that is partiy or com- 
pletely below grade (see "Story above grade"). 

BASEMENT WALL. The opaque portion of a wall that 
encloses one side of a basement and has an average below 
grade wall area that is 50 percent or more of the total opaque 
and non-opaque area of that enclosing side. 

BASIC WIND SPEED. Three-second gust speed at 33 feet 
(10 058 mm) above the ground in Exposure C (see Section 
R301.2.1) as given in Figure R301.2(4). 

BATHROOM GROUP. A group of fixtures, including or 
excluding a bidet, consisting of a water closet, lavatory, and 
bathtub or shower. Such fixtures are located together on the 
same floor level. 

BEND. A drainage fitting, designed to provide a change in 
direction of a drain pipe of less than the angle specified by the 
amount necessary to establish the desired slope of the line (see 
"Elbow" and "Sweep"). 

BOILER. A self-contained appliance from which hot water is 
circulated for heating purposes and then returned to the boiler, 
and which operates at water pressures not exceeding 160 
pounds per square inch gage (psig) (1102 kPa gauge) and at 
water temperatures not exceeding 250°F (121 °C). 

BOND BEAM. A horizontal grouted element within masonry 
in which reinforcement is embedded. 

BRACED WALL LINE. A series of braced wall panels in a 
single story constructed in accordance with Section R602.10 
for wood framing or Section R603.7 or R30 1.1.1 for 
cold-formed steel framing to resist racking from seismic and 
wind forces. 



BRACED WALL PANEL. A section of a braced wall hne 
constructed in accordance with Section R602.10 for wood 
framing or Section R603.7 or R30 1.1.1 for cold-formed steel 
framing, which extend the full height of the wall. : 

BRANCH. Any part of the piping system other than a riser, 
main or stack. 

BRANCH, FIXTURE. See "Fixture branch, drainage." 

BRANCH, HORIZONTAL. See "Horizontal branch, drain- 
age." 

BRANCH INTERVAL. A vertical measurement of distance, 
8 feet (2438 mm) or more in developed length, between the 
connections of horizontal branches to a drainage stack. Mea- 
surements are taken down the stack from the highest horizontal 
branch connection. 

BRANCH, MAIN. A water-distribution pipe that extends hor- 
izontally off a main or riser to convey water to branches or fix- 
ture groups. 

BRANCH, VENT. A vent connecting two or more individual 
vents with a vent stack or stack vent. 

BTU/H. The listed maximum capacity of an appliance, absorp- 
tion unit or burner expressed in British thermal units input per 
hour. I 

BUILDING. Building shall mean any one- and I two-family 
dwelling or portion thereof, including townhouses, that is used, 
or designed or intended to be used for human habitation, for 
living, sleeping, cooking or eating purposes, or any combina- 
tion thereof, and shall include accessory structures thereto. 

BUILDING DRAIN. The lowest piping that collects the dis- 
charge from all other drainage piping inside the house and 
extends 30 inches (762 mm) in developed length of pipe, 
beyond the exterior walls and conveys the drainage to the build- 
ing sewer. 

BUILDING, EXISTING. Existing building is a building 
erected prior to the adoption of this code, or one for which a 
legal building permit has been issued. 

BUILDING LINE. The line estabhshed by law, beyond which 
a building shall not extend, except as specifically provided by 
law. 

BUILDING OFFICIAL. The officer or other designated 
authority charged with the administration and enforcement of 
this code. 

BUILDING SEWER. That part of the drainage ;system that 
extends from the end of the building drain and conveys its dis- 
charge to a public sewer, private sewer, individual isewage-dis- 
posal system or other point of disposal. \ 

BUILDING THERMAL ENVELOPE. The basement walls, 
exterior walls, floor, roof and any other building element that 
enclose conditioned spaces. I 

BUILT-UP ROOF COVERING. Two or more layers of felt 
cemented together and surfaced with a cap sheet, mineral 
aggregate, smooth coating or similar surfacing material. 

CEILING HEIGHT. The clear vertical distance from the fin- 
ished floor to the finished ceiling. \ 



10 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



DEFINITIONS 



CHIMNEY. A primary vertical structure containing one or 
more flues, for the purpose of carrying gaseous products of 
combustion and air from a fuel-burning appliance to the out- 
side atmosphere. 

CHIMNEY CONNECTOR. A pipe that connects a 
fuel-burning appliance to a chimney. 

CHIMNEY TYPES 

Residential-type appliance. An approved chimney for 
removing the products of combustion from fuel-burning, 
residential-type appliances producing combustion gases not 
in excess of 1 ,000°F (538°C) under normal operating condi- 
tions, but capable of producing combustion gases of 
1,400°F (760°C) during intermittent forces firing for peri- 
ods up to 1 hour. All temperatures shall be measured at the 
appliance flue outlet. Residential-type appliance chimneys 
include masonry and factory-built types. 

CIRCUIT VENT. A vent that connects to a horizontal drain- 
age branch and vents two traps to a maximum of eight traps or 
trapped fixtures connected into a battery. 

CLADDING. The exterior materials that cover the surface of 
the building envelope that is directly loaded by the wind. 

CLEANOUT. An accessible opening in the drainage system 
used for the removal of possible obstruction. 

CLOSET. A small room or chamber used for storage. 

COMBINATION WASTE AND VENT SYSTEM. A spe- 
cially designed system of waste piping embodying the horizon- 
tal wet venting of one or more sinks or floor drains by means of 
a common waste and vent pipe adequately sized to provide free 
movement of air above the flow line of the drain. 

COMBUSTIBLE MATERIAL. Any material not defined as 
noncombustible. 

COMBUSTION AIR. The air provided to fuel-burning equip- 
ment including air for fuel combustion, draft hood dilution and 
ventilation of the equipment enclosure. 

COMMON VENT. A single pipe venting two trap arms within 
the same branch interval, either back-to-back or one above the 
other. 

CONDENSATE. The liquid that separates from a gas due to a 
reduction in temperature, e.g., water that condenses from flue 
gases and water that condenses from air circulating through the 
cooling coil in air conditioning equipment. 

CONDENSING APPLIANCE. An appliance that condenses 
water generated by the burning of fuels. 

CONDITIONED AIR. Air treated to control its temperature, 
relative humidity or quahty. 

CONDITIONED AREA. That area within a building pro- 
vided with heating and/or cooling systems or appliances capa- 
ble of maintaining, through design or heat loss/gain, 68 °F 
(20°C) during the heating season and/or 80°F (27°C) during 
the coohng season, or has a fixed opening directly adjacent to a 
conditioned area. 

CONDITIONED FLOOR AREA. The horizontal projection 
of the floors associated with the conditioned space. 



CONDITIONED SPACE. For energy purposes, space within 
a building that is provided with heating and/or cooling equip- 
ment or systems capable of maintaining, through design or heat 
loss/gain, 50°F (10°C) during the heating season and 85°F 
(29°C) during the cooling season, or communicates directly 
with a conditioned space. For mechanical purposes, an area, 
room or space being heated or cooled by any equipment or 
appliance. 

CONFINED SPACE. A room or space having a volume less 
than 50 cubic feet per 1 ,000 Btu/h (4.83 LAV) of the aggregate 
input rating of all fuel-burning appliances installed in that 
space. 

CONSTRUCTION DOCUMENTS. Written, graphic and 
pictorial documents prepared or assembled for describing the 
design, location and physical characteristics of the elements of 
a project necessary for obtaining a building permit. Construc- 
tion drawings shall be drawn to an appropriate scale. 

CONTAMINATION. An impairment of the quality of the 
potable water that creates an actual hazard to the public health 
through poisoning or through the spread of disease by sewage, 
industrial fluids or waste. 

CONTINUOUS WASTE. A drain from two or more similar 
adjacent fixtures connected to a single trap. 

CONTROL, LIMIT. An automatic control responsive to 
changes in liquid flow or level, pressure, or temperature for 
limiting the operation of an appliance. 

CONTROL, PRIMARY SAFETY. A safety control respon- 
sive directly to flame properties that senses the presence or 
absence of flame and, in event of ignition failure or uninten- 
tional flame extinguishment, automatically causes shutdown 
of mechanical equipment. 

CONVECTOR. A system-incorporating heating element in 
an enclosure in which air enters an opening below the heating 
element, is heated and leaves the enclosure through an opening 
located above the heating element. 

CORROSION RESISTANCE. The ability of a material to 
withstand deterioration of its surface or its properties when 
exposed to its environment. 

COURT. A space, open and unobstructed to the sky, located at 
or above grade level on a lot and bounded on three or more 
sides by walls or a building. 

CRIPPLE WALL. A framed wall extending from the top of 
the foundation to the underside of the floor framing of the first 
story above grade plane. 

CROSS CONNECTION. Any connection between two oth- 
erwise separate piping systems whereby there may be a flow 
from one system to the other. 

DALLE GLASS. A decorative composite glazing material 
made of individual pieces of glass that are embedded in a cast 
matrix of concrete or epoxy. 

DAMPER, VOLUME. A device that will restrict, retard or 
direct the flow of air in any duct, or the products of combustion 
of heat-producing equipment, vent connector, vent or chimney. 

DEAD END. A branch leading from a DWV system terminat- 
ing at a developed length of 2 feet (610 mm) or more. Dead 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



11 



DEFINITIONS 



ends shall be prohibited except as an approved part of a 
rough-in for future connection. 

DEAD LOADS. The weight of all materials of construction 
incorporated into the building, including but not limited to 
walls, floors, roofs, ceilings, stairways, built-in partitions, fin- 
ishes, cladding, and other similarly incorporated architectural 
and structural items, and fixed service equipment. 

DECK. An exterior floor system supported on at least two 
opposing sides by an adjoining structure and/or posts, piers, or 
other independent supports. 

DECORATIVE GLASS. A carved, leaded or Dalle glass or 
glazing material whose purpose is decorative or artistic, not 
functional; whose coloring, texture or other design qualities or 
components cannot be removed without destroying the glazing 
material; and whose surface, or assembly into which it is 
incor-porated, is divided into segments. 

DESIGN PROFESSIONAL. See definition of "Registered 
design professional." 

DEVELOPED LENGTH. The length of a pipeline measured 
along the center line of the pipe and fittings. 

DIAMETER. Unless specifically stated, the term "diameter" 
is the nominal diameter as designated by the approved material 
standard. 

DIAPHRAGM. A horizontal or nearly horizontal system act- 
ing to transmit lateral forces to the vertical resisting elements. 
When the term "diaphragm" is used, it includes horizontal 
bracing systems. 

DILUTION AIR. Air that enters a draft hood or draft regulator 
and mixes with flue gases. 

DIRECT- VENT APPLIANCE. A fuel-burning appliance 
with a sealed combustion system that draws all air for combus- 
tion from the outside atmosphere and discharges all flue gases 
to the outside atmosphere. 

DRAFT. The pressure difference existing between the appli- 
ance or any component part and the atmosphere, that causes a 
continuous flow of air and products of combustion through the 
gas passages of the appliance to the atmosphere. 

Induced draft. The pressure difference created by the 
action of a fan, blower or ejector, that is located between the 
appliance and the chimney or vent termination. 

Natural draft. The pressure difference created by a vent or 
chimney because of its height, and the temperature differ- 
ence between the flue gases and the atmosphere. 

DRAFT HOOD. A device built into an appliance, or a part of 
the vent connector from an appliance, which is designed to pro- 
vide for the ready escape of the flue gases from the appliance in 
the event of no draft, backdraft or stoppage beyond the draft 
hood; prevent a backdraft from entering the appliance; and 
neutralize the effect of stack action of the chimney or gas vent 
on the operation of the appliance. 

DRAFT REGULATOR. A device that functions to maintain a 
desired draft in the appliance by automatically reducing the 
draft to the desired value. 



DRAFT STOP. A material, device or construction installed to 
restrict the movement of air within open spaces of concealed 
areas of building components such as crawl spaces, floor-ceil- 
ing assemblies, roof-ceiling assemblies and attics. 

DRAIN. Any pipe that carries soil and water-borne wastes in a 
building drainage system. 

DRAINAGE FITTING. A pipe fitting designed to provide 
connections in the drainage system that have provisions for 
establishing the desired slope in the system. These fittings are 
made from a variety of both metals and plastics. The methods 
of coupling provide for required slope in the system (see "Dur- 
ham fitting"). 

DUCT SYSTEM. A continuous passageway for the transmis- 
sion of air which, in addition to ducts, includes duct fittings, 
dampers, plenums, fans and accessory air-handling equipment 
and appliances. 

DURHAM FITTING. A special type of drainage fitting for 
use in the durham systems installations in which the joints are 
made with recessed and tapered threaded fittings, as opposed to 
bell and spigot lead/oakum or solvent/cemented or soldered 
joints. The tapping is at an angle (not 90 degrees) to provide for 
proper slope in otherwise rigid connections. 

DURHAM SYSTEM. A term used to describe soil or waste 
systems where all piping is of threaded pipe, tube or other such 
rigid construction using recessed drainage fittings to corre- 
spond to the types of piping. 

DWELLING. Any building that contains one or two dwelling 
units used, intended, or designed to be built, used, rented, 
leased, let or hired out to be occupied, or that are occupied for 
living purposes. 

DWELLING UNIT. A single unit providing complete inde- 
pendent living facilities for one or more persons, including per- 
manent provisions for living, sleeping, eating, cooking and 
sanitation. 

DWV. Abbreviated term for drain, waste and vent piping as 
used in common plumbing practice. 

EFFECTIVE OPENING. The minimum cross-sectional area 
at the point of water-supply discharge, measured or expressed 
in terms of diameter of a circle and if the opening is not circular, 
the diameter of a circle of equivalent cross-sectional area. (This 
is applicable to air gap.) 

ELBOW. A pressure pipe fitting designed to provide an exact 
change in direction of a pipe run. An elbow provides a sharp 
turn in the flow path (see "Bend" and "Sweep"). 

EMERGENCY ESCAPE AND RESCUE OPENING. An 

operable exterior window, door or similar device that provides | 
for a means of escape and access for rescue in the event of an 
emergency. 

EQUIPMENT. All piping, ducts, vents, control devices and 
other components of systems other than appliances that are 
permanently installed and integrated to provide control of envi- 
ronmental conditions for buildings. This definition shall also 
include other systems specifically regulated in this code. 

EQUIVALENT LENGTH. For determining fiicfion losses in 
a piping system, the effect of a particular fitting equal to the 



12 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



DEFINITIONS 



friction loss through a straight piping length of the same nomi- 
nal diameter. 

ESSENTIALLY NONTOXIC TRANSFER FLUIDS. Fluids 
having a Gosselin rating of 1, including propylene glycol; min- 
eral oil; polydimenthyoil oxane; hydrochlorofluorocarbon, 
chlorofluorocarbon and hydrofluorocarbon refrigerants; and 
FDA-approved boiler water additives for steam boilers. 

ESSENTIALLY TOXIC TRANSFER FLUIDS. Soil, water 
or gray water and fluids having a Gosselin rating of 2 or more 
including ethylene glycol, hydrocarbon oils, ammonia refrig- 
erants and hydrazine. 

EVAPORATIVE COOLER. A device used for reducing air 
temperature by the process of evaporating water into an 
airstream. 

EXCESS AIR. Air that passes through the combustion cham- 
ber and the appliance flue in excess of that which is theoreti- 
cally required for complete combustion. 

EXHAUST HOOD, FULL OPENING. An exhaust hood 
with an opening at least equal to the diameter of the connecting 
vent. 

EXISTING INSTALLATIONS. Any plumbing system regu- 
lated by this code that was legally installed prior to the effective 
date of this code, or for which a permit to install has been 
issued. 

EXTERIOR INSULATION FINISH SYSTEMS (EIFS). 

Synthetic stucco cladding systems typically consisting of five 
layers: adhesive, insulation board, base coat into which fiber- 
glass reinforcing mesh is embedded, and a finish coat in the 
desired color. 

EXTERIOR WALL. An above-grade wall that defines the 
I exterior boundaries of a building. Includes between-floor 
spandrels, peripheral edges of floors, roof and basement knee 
walls, dormer walls, gable end walls, walls enclosing a man- 
sard roof and basement walls with an average below-grade wall 
area that is less than 50 percent of the total opaque and 
nonopaque area of that enclosing side. 

FACTORY-BUILT CHIMNEY. A listed and labeled chim- 
ney composed of factory-made components assembled in the 
field in accordance with the manufacturer's instructions and 
the conditions of the listing. 

FENESTRATION. Skyhghts, roof windows, vertical win- 
dows (whether fixed or moveable); opaque doors; glazed 
doors; glass block; and combination opaque/glazed doors. 

FIBER CEMENT SIDING. A manufactured, fiber-reinforc- 
ing product made with an inorganic hydraulic or calcium sili- 
cate binder formed by chemical reaction and reinforced with 
organic or inorganic non-asbestos fibers, or both. Additives 
which enhance manufacturing or product performance are per- 
mitted. Fiber cement siding products have either smooth or tex- 
tured faces and are intended for exterior wall and related 
applications. 

FIREBLOCKING. Building materials installed to resist the 
free passage of flame to other areas of the building through 
concealed spaces. 



FIREPLACE. An assembly consisting of a hearth and fire 
chamber of noncombustible material and provided with a 
chimney, for use with solid fuels. 

Factory-built fireplace. A listed and labeled fireplace and 
chimney system composed of factory-made components, 
and assembled in the field in accordance with manufacturer's 
instructions and the conditions of the listing. 

Masonry chimney. A field-constructed chimney composed 
of solid masonry units, bricks, stones or concrete. 

Masonry fireplace. A field-constructed fireplace com- 
posed of solid masonry units, bricks, stones or concrete. 

FIREPLACE STOVE. A free-standing, chimney-connected 
solid-fuel-burning heater designed to be operated with the fire 
chamber doors in either the open or closed position. 

FIREPLACE THROAT. The opening between the top of the 

firebox and the smoke chamber. 

FIRE SEPARATION DISTANCE. The distance measured 
from the building face to one of the following: 

1. To the closest interior lot line; or 

2. To the centerline of a street, an alley or public way; or 

3. To an imaginary line between two buildings on the lot. 

The distance shall be measured at a right angle from the face of 
the wall. 

FIXTURE. See "Plumbing fixture." 

FIXTURE BRANCH, DRAINAGE. A drain serving two or 
more fixtures that discharges into another portion of the drain- 
age system. 

FIXTURE BRANCH, WATER-SUPPLY. A water supply 
pipe between the fixture supply and a main water-distribution 
pipe or fixture group main. 

FIXTURE DRAIN. The drain from the trap of a fixture to the 
junction of that drain with any other drain pipe. 

FIXTURE FITTING 

Supply fitting. A fitting that controls the volume and/or 
directional flow of water and is either attached to or accessi- 
ble from a fixture or is used with an open or atmospheric dis- 
charge. 

Waste fitting. A combination of components that conveys 
the sanitary waste from the outlet of a fixture to the connec- 
tion of the sanitary drainage system. 

FIXTURE GROUP, MAIN. The main water-distribution 
pipe (or secondary branch) serving a plumbing fixture group- 
ing such as a bath, kitchen or laundry area to which two or more 
individual fixture branch pipes are connected. 

FIXTURE SUPPLY. The water-supply pipe connecting a fix- 
ture or fixture fitting to a fixture branch. 

FIXTURE UNIT, DRAINAGE (d.f.u.). A measure of proba- 
ble discharge into the drainage system by various types of 
plumbing fixtures, used to size DWV piping systems. The 
drainage fixture-unit value for a particular fixture depends on 
its volume rate of drainage discharge, on the time duration of a 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



13 



DEFINITIONS 



single drainage operation and on the average time between suc- 
cessive operations. 

FIXTURE UNIT, WATER-SUPPLY (w.s.f.u.). A measure of 
the probable hydraulic demand on the water supply by various 
types of plumbing fixtures used to size water-piping systems. 
The water-supply fixture-unit value for a particular fixture 
depends on its volume rate of supply, on the time duration of a 
single supply operation and on the average time between suc- 
cessive operations. 

FLAME SPREAD. The propagation of flame over a surface. 

FLAME SPREAD INDEX. The numeric value assigned to a 
material tested in accordance with ASTM E 84. 

FLOOD-LEVEL RIM. The edge of the receptor or fixture 
from which water overflows. 

FLOOR DRAIN. A plumbing fixture for recess in the floor 
having a floor-level strainer intended for the purpose of the col- 
lection and disposal of waste water used in cleaning the floor 
and for the collection and disposal of accidental spillage to the 
floor. 

FLOOR FURNACE. A self-contained furnace suspended 
from the floor of the space being heated, taking air for combus- 
tion from outside such space, and with means for lighting the 
appliance from such space. 

FLOW PRESSURE. The static pressure reading in the 
water-supply pipe near the faucet or water outlet while the fau- 
cet or water outlet is open and flowing at capacity. 

FLUE. See "Vent." 

FLUE, APPLIANCE. The passages within an appliance 
through which combustion products pass from the combustion 
chamber to the flue collar. 

FLUE COLLAR. The portion of a fuel-burning appliance 
designed for the attachment of a draft hood, vent connector or 
venting system. 

FLUE GASES. Products of combustion plus excess air in 

appliance flues or heat exchangers. 

FLUSH VALVE. A device located at the bottom of a flush tank 
that is operated to flush water closets. 

FLUSHOMETER TANK. A device integrated within an air 
accumulator vessel that is designed to discharge a predeter- 
mined quantity of water to fixtures for flushing purposes. 

FLUSHOMETER VALVE. A flushometer valve is a device 
that discharges a predetermined quantity of water to fixtures 
for flushing purposes and is actuated by direct water pressure. 

FOAM BACKER BOARD. Foam plastic used in siding appli- 
cations where the foam plastic is a component of the siding. 

FOAM PLASTIC INSULATION. A plastic that is intention- 
ally expanded by the use of a foaming agent to produce a 
reduced-density plastic containing voids consisting of open or 
closed cells distributed throughout the plastic for thermal insu- 
lating or acoustic purposes and that has a density less than 20 
pounds per cubic foot (320 kg/m^) unless it is used as interior 
trim. 



FOAM PLASTIC INTERIOR TRIM. Exposed foam plastic 
used as picture molds, chair rails, crown moldings, baseboards, 
handrails, ceiling beams, door trim and window trim and simi- 
lar decorative or protective materials used in fixed applications. 

FUEL-PIPING SYSTEM. All piping, tubing, valves and fit- 
tings used to connect fuel utilization equipment to the point of 
fuel delivery. 

FULLWAY VALVE. A valve that in the full open position has 
an opening cross-sectional area equal to a minimum of 85 per- 
cent of the cross-sectional area of the connecting pipe. 

FURNACE. A vented heating appliance designed or arranged 
to discharge heated air into a conditioned space or through a 
duct or ducts. 

GLAZING AREA. The interior surface area of all glazed fen- 
estration, including the area of sash, curbing or other framing 
elements, that enclose conditioned space. Includes the area of 
glazed fenestration assemblies in walls bounding conditioned 
basements. 

GRADE. The finished ground level adjoining the building at 
all exterior walls. 

GRADE FLOOR OPENING. A window or other opening 
located such that the sill height of the opening is not more than 
44 inches (1118 mm) above or below the finished ground level 
adjacent to the opening. 

GRADE, PIPING. See "Slope." 

GRADE PLANE. A reference plane representing the average 
of the finished ground level adjoining the building at all exte- 
rior walls. Where the finished ground level slopes away from 
the exterior walls, the reference plane shall be established by 
the lowest points within the area between the building and the 
lot line or, where the lot line is more than 6 ft (1829 mm) from 
the building between the structure and a point 6 ft (1829 mm) 
from the building. 

GRIDDED WATER DISTRIBUTION SYSTEM. A water 
distribution system where every water distribution pipe is inter- 
connected so as to provide two or more paths to each fixture 
supply pipe. 

GROSS AREA OF EXTERIOR WALLS. The normal pro 
jection of all exterior walls, including the area of all windows 
and doors installed therein. 

GROUND-SOURCE HEAT PUMP LOOP SYSTEM. Pip 

ing buried in horizontal or vertical excavations or placed in a 
body of water for the purpose of transporting heat transfer liq- 
uid to and from a heat pump. Included in this definition are 
closed loop systems in which the liquid is recirculated and open 
loop systems in which the liquid is drawn from a well or other 
source. 

GUARD. A building component or a system of building com- 
ponents located near the open sides of elevated walking sur- 
faces that minimizes the possibility of a fall from the walking 
surface to the lower level. 

HABITABLE SPACE. A space in a building for living, sleep- 
ing, eating or cooking. Bathrooms, toilet rooms, closets, halls, 
storage or utility spaces and similar areas are not considered 
habitable spaces. 



14 



2006 INTERNATIONAL RESIDENTIAL CODE® 



DEFINITIONS 



HANDRAIL. A horizontal or sloping rail intended for grasp- 
ing by the hand for guidance or support. 

HANGERS. See "Supports." 

HAZARDOUS LOCATION. Any location considered to be a 
fire hazard for flammable vapors, dust, combustible fibers or 
other highly combustible substances. 

HEATING DEGREE DAYS (HDD). The sum, on an annual 
basis, of the difference between 65°F (18°C) and the mean tem- 
perature for each day as determined from "NCAA Annual 
Degree Days to Selected Bases Derived from the 1960-1990 
Normals" or other weather data sources acceptable to the code 
official. 

HEAT PUMP. An appliance having heating or heating/cool- 
ing capability and that uses refrigerants to extract heat from air, 
liquid or other sources. 

HEIGHT, BUILDING. The vertical distance from grade 
plane to the average height of the highest roof surface. 

HEIGHT, STORY. The vertical distance from top to top of 
two successive tiers of beams or finished floor surfaces; and, 
for the topmost story, from the top of the floor finish to the top 
of the ceiling joists or, where there is not a ceiling, to the top of 
the roof rafters. 

HIGH-TEMPERATURE (H.T.) CHIMNEY. A high tem- 
perature chimney complying with the requirements of UL 103. 
A Type H.T. chimney is identifiable by the markings "Type 
H.T." on each chimney pipe section. 

HORIZONTAL BRANCH, DRAINAGE. A drain pipe 
extending laterally from a soil or waste stack or building drain, 
that receives the discharge from one or more fixture drains. 

HORIZONTAL PIPE. Any pipe or fitting that makes an angle 
of less than 45 degrees (0.79 rad) with the horizontal. 

HOT WATER. Water at a temperature greater than or equal to 
110°F(43°C). 

HURRICANE-PRONE REGIONS. Areas vulnerable to 
hurricanes, defined as the U.S. Atlantic Ocean and Gulf of 
Mexico coasts where the basic wind speed is greater than 90 
miles per hour (40 m/s), and Hawaii, Puerto Rico, Guam, Vir- 
gin Islands, and America Samoa. 

HYDROGEN GENERATING APPLIANCE. A self con- 
tained package or factory-matched packages of integrated sys- 
tems for generating gaseous hydrogen. Hydrogen generating 
appliances utilize electrolysis, reformation, chemical, or other 
processes to generate hydrogen. 

IGNITION SOURCE. A flame, spark or hot surface capable 
of igniting flammable vapors or fumes. Such sources include 
appliance burners, burner ignitions and electrical switching 
devices. 

INDIRECT WASTE PIPE. A waste pipe that discharges into 
the drainage system through an air gap into a trap, fixture or 
receptor. 

INDIVIDUAL SEWAGE DISPOSAL SYSTEM. A system 
for disposal of sewage by means of a septic tank or mechanical 
treatment, designed for use apart from a public sewer to serve a 
single establishment or building. 



INDIVIDUAL VENT. A pipe installed to vent a single-fixture 
drain that connects with the vent system above or terminates 
independently outside the building. 

INDIVIDUAL WATER SUPPLY. A supply other than an 
approved public water supply that serves one or more families. 

INSULATING CONCRETE FORM (ICE). A concrete 
forming system using stay-in-place forms of rigid foam plastic 
insulation, a hybrid of cement and foam insulation, a hybrid of 
cement and wood chips, or other insulating material for con- 
structing cast-in-place concrete walls. 

INSULATING SHEATHING. An insulating board having a 
minimum thermal resistance of R-2 of the core material. 

JURISDICTION. The governmental unit that has adopted 
this code under due legislative authority. 

KITCHEN. Kitchen shall mean an area used, or designated to 
be used, for the preparation of food. 

LABEL. An identification applied on a product by the manu- 
facturer which contains the name of the manufacturer, the func- 
tion and performance characteristics of the product or material, 
and the name and identification of an approved agency and that 
indicates that the representative sample of the product or mate- 
rial has been tested and evaluated by an approved agency. (See 
also "Manufacturer's designation" and "Mark.") 

LABELED. Devices, equipment or materials to which have 
been affixed a label, seal, symbol or other identifying mark of a 
testing laboratory, inspection agency or other organization 
concerned with product evaluation that maintains periodic 
inspection of the production of the above labeled items that 
attests to compliance with a specific standard. 

LIGHT-FRAMED CONSTRUCTION. A type of construc- 
tion whose vertical and horizontal structural elements are pri- 
marily formed by a system of repetitive wood or light gage steel 
framing members. 

LISTED AND LISTING. Terms referring to equipment that 
is shown in a list published by an approved testing agency qual- 
ified and equipped for experimental testing and maintaining an 
adequate periodic inspection of current productions and whose 
listing states that the equipment complies with nationally rec- 
ognized standards when installed in accordance with the manu- 
facturer's installation instructions. 

LIVE LOADS. Those loads produced by the use and occu- 
pancy of the building or other structure and do not include con- 
struction or environmental loads such as wind load, snow load, 
rain load, earthquake load, flood load or dead load. 

LIVING SPACE. Space within a dweUing unit utihzed for liv- 
ing, sleeping, eating, cooking, bathing, washing and sanitation 
purposes. 

LOT. A portion or parcel of land considered as a unit. 

LOT LINE. A line dividing one lot from another, or from a 
street or any public place. 

MACERATING TOILET SYSTEMS. A system comprised 
of a sump with macerating pump and with connections for a 
water closet and other plumbing fixtures, that is designed to 
accept, grind and pump wastes to an approved point of dis- 
charge. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



15 



DEFINITIONS 



MAIN. The principal pipe artery to which branches may be 
connected. 

MAIN SEWER. See "Pubhc sewer." 

MANIFOLD WATER DISTRIBUTION SYSTEMS. A fab- 
ricated piping arrangement in which a large supply main is fit- 
ted with multiple branches in close proximity in which water is 
distributed separately to fixtures from each branch. 

MANUFACTURED HOME. Manufactured home means a 
structure, transportable in one or more sections, which in the 
traveling mode is 8 body feet (2438 body mm) or more in width 
or 40 body feet (12 192 body mm) or more in length, or, when 
erected on site, is 320 square feet (30 m^) or more, and which is 
built on a permanent chassis and designed to be used as a dwell- 
ing with or without a permanent foundation when connected to 
the required utilities, and includes the plumbing, heating, 
air-conditioning and electrical systems contained therein; 
except that such term shall include any structure that meets all 
the requirements of this paragraph except the size requirements 
and with respect to which the manufacturer voluntarily files a 
certification required by the secretary (HUD) and complies 
with the standards established under this title. For mobile 
homes built prior to June 15, 1976, a label certifying compli- 
ance to the Standard for Mobile Homes, NFPA 501, in effect at 
the time of manufacture is required. For the purpose of these 
provisions, a mobile home shall be considered a manufactured 
home. 

MANUFACTURER'S DESIGNATION. An identification 
applied on a product by the manufacturer indicating that a 
product or material complies with a specified standard or set of 
rules. (See also "Mark" and "Label.") 

MANUFACTURER'S INSTALLATION INSTRUC- 
TIONS. Printed instructions included with equipment as part 
of the conditions of listing and labeling. 

MARK. An identification applied on a product by the manu- 
facturer indicating the name of the manufacturer and the func- 
tion of a product or material. (See also "Manufacturer's 
designation" and "Label.") 

MASONRY CHIMNEY. A field-constructed chimney com- 
posed of solid masonry units, bricks, stones or concrete. 

MASONRY HEATER. A masonry heater is a solid fuel burn- 
ing heating appliance constructed predominantly of concrete or 
solid masonry having a mass of at least 1,100 pounds (500 kg), 
excluding the chimney and foundation. It is designed to absorb 
and store a substantial portion of heat from a fire built in the fire- 
box by routing exhaust gases through internal heat exchange 
channels in which the flow path downstream of the firebox 
includes at least one 1 80-degree (3. 14-rad) change in flow direc- 
tion before entering the chimney and which deliver heat by radi- 
ation through the masonry surface of the heater. 

MASONRY, SOLID. Masonry consisting of solid masonry 
units laid contiguously with the joints between the units filled 
with mortar. 

MASONRY UNIT. Brick, tile, stone, glass block or concrete 
block conforming to the requirements specified in Section 
2103 of the International Building Code. 



Clay. A building unit larger in size than a brick, composed 
of burned clay, shale, fire clay or mixtures thereof 

Concrete. A building unit or block larger in size than 12 
inches by 4 inches by 4 inches (305 mm by 102 mm by 102 
mm) made of cement and suitable aggregates. 

Glass. Nonload-bearing masonry composed of glass units 
bonded by mortar. 

Hollow. A masonry unit whose net cross-sectional area in 
any plane parallel to the loadbearing surface is less than 75 
percent of its gross cross-sectional area measured in the 
same plane. 

Solid. A masonry unit whose net cross-sectional area in 
every plane parallel to the loadbearing surface is 75 percent 
or more of its cross-sectional area measured in the same 
plane. 

MASS WALL. Masonry or concrete walls having a mass 
greater than or equal to 30 pounds per square foot (146 kg/m^), 
solid wood walls having a mass greater than or equal to 20 
pounds per square foot (98 kg/m^), and any other walls having a 
heat capacity greater than or equal to 6 Btu/ft^ • °F [266 ]/(m^ ■ 
K)]. 

MEAN ROOF HEIGHT. The average of the roof eave height 
and the height to the highest point on the roof surface, except 
that eave height shall be used for roof angle of less than or equal 
to 10 degrees (0.18 rad). 

MECHANICAL DRAFT SYSTEM. A venting system 
designed to remove flue or vent gases by mechanical means, 
that consists of an induced draft portion under nonpositive 
static pressure or a forced draft portion under positive static 
pressure. 

Forced-draft venting system. A portion of a venting sys- 
tem using a fan or other mechanical means to cause the 
removal of flue or vent gases under positive static pressure. 

Induced draft venting system. A portion of a venting sys- 
tem using a fan or other mechanical means to cause the 
removal of flue or vent gases under nonpositive static vent 
pressure. 

Power venting system. A portion of a venting system using 
a fan or other mechanical means to cause the removal of flue 
or vent gases under positive static vent pressure. 

MECHANICAL EXHAUST SYSTEM. A system for 
removing air from a room or space by mechanical means. 

MECHANICAL SYSTEM. A system specifically addressed 
and regulated in this code and composed of components, 
devices, appliances and equipment. 

METAL ROOF PANEL. An interlocking metal sheet having 
a minimum installed weather exposure of at least 3 square feet 
(0.28 m^) per sheet. 

METAL ROOF SHINGLE. An interlocking metal sheet hav- 
ing an installed weather exposure less than 3 square feet (0.28 
m^) per sheet. 

MEZZANINE, LOFT. An intermediate level or levels 
between the floor and ceiling of any story with an aggregate 



16 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



DEFINITIONS 



floor area of not more than one-third of the area of the room or 
space in which the level or levels are located. 

MODIFIED BITUMEN ROOF COVERING. One or more 
layers of polymer modified asphalt sheets. The sheet materials 
shall be fully adhered or mechanically attached to the substrate 
or held in place with an approved ballast layer. 

MULTIPLE STATION SMOKE ALARM. Two or more sin 
gle station alarm devices that are capable of interconnection 
such that actuation of one causes all integral or separate audible 
alarms to operate. 

NATURAL DRAFT SYSTEM. A venting system designed to 
remove flue or vent gases under nonpositive static vent pres- 
sure entirely by natural draft. 

NATURALLY DURABLE WOOD. The heartwood of the 
following species: Decay-resistant redwood, cedars, black 
locust and black walnut. 

Note: Comer sap wood is permitted if 90 percent or more of 
the width of each side on which it occurs is heartwood. 

NONCOMBUSTIBLE MATERIAL. Materials that pass the 
test procedure for defining noncombustibility of elementary 
materials set forth in ASTM E 136. 

NONCONDITIONED SPACE. A space that is not a condi- 
tioned space by insulated walls, floors or ceilings. 

OCCUPIED SPACE. The total area of all buildings or struc- 
tures on any lot or parcel of ground projected on a horizontal 
plane, excluding permitted projections as allowed by this code. 

OFFSET. A combination of fittings that makes two changes in 
direction bringing one section of the pipe out of line but into a 
line parallel with the other section. 

OWNER. Any person, agent, firm or corporation having a 
legal or equitable interest in the property. 

PELLET FUEL-BURNING APPLIANCE. A closed com 
bustion, vented appliance equipped with a fuel feed mecha- 
nism for burning processed pellets of solid fuel of a specified 
size and composition. 

PELLET VENT, A vent Hsted and labeled for use with a listed 
pellet fuel-burning appliance. 

PERMIT. An official document or certificate issued by the 
authority having jurisdiction that authorizes performance of a 
specified activity. 

PERSON. An individual, heirs, executors, administrators or 
assigns, and also includes a firm, partnership or corporation, its 
or their successors or assigns, or the agent of any of the afore- 
said. 

PITCH. See "Slope." 

PLATFORM CONSTRUCTION. A method of construction 
by which floor framing bears on load bearing walls that are not 
continuous through the story levels or floor framing. 

PLENUM. A chamber that forms part of an air-circulation sys- 
tem other than the occupied space being conditioned. 

PLUMBING. For the purpose of this code, plumbing refers to 
those installations, repairs, maintenance and alterations regu- 
lated by Chapters 25 through 32. 



PLUMBING APPLIANCE. An energized household appli- 
ance with plumbing connections, such as a dishwasher, 
food-waste grinder, clothes washer or water heater. 

PLUMBING APPURTENANCE. A device or assembly that 
is an adjunct to the basic plumbing system and demands no 
additional water supply nor adds any discharge load to the sys- 
tem. It is presumed that it performs some useful function in the 
operation, maintenance, servicing, economy or safety of the 
plumbing system. Examples include filters, relief valves and 
aerators. 

PLUMBING FIXTURE. A receptor or device that requires 
both a water-supply connection and a discharge to the drainage 
system, such as water closets, lavatories, bathtubs and sinks. 
Plumbing appliances as a special class of fixture are further 
defined. 

PLUMBING SYSTEM. Includes the water supply and distri- 
bution pipes, plumbing fixtures, supports and appurtenances; 
soil, waste and vent pipes; sanitary drains and building sewers 
to an approved point of disposal. 

POLLUTION. An impairment of the quality of the potable 
water to a degree that does not create a hazard to the public 
health but that does adversely and unreasonably affect the aes- 
thetic qualities of such potable water for domestic use. 

PORTABLE FUEL CELL APPLIANCE. A fuel cell gener- 
ator of electricity, which is not fixed in place. A portable fuel 
cell appliance utilizes a cord and plug connection to a grid-iso- 
lated load and has an integral fuel supply. 

POSITIVE ROOF DRAINAGE. The drainage condition in 
which consideration has been made for all loading deflections 
of the roof deck, and additional slope has been provided to 
ensure drainage of the roof within 48 hours of precipitation. 

POTABLE WATER. Water free from impurities present in 
amounts sufficient to cause disease or harmful physiological 
effects and conforming in bacteriological and chemical quality 
to the requirements of the public health authority having juris- 
diction. 

PRECAST CONCRETE. A structural concrete element cast 
elsewhere than its final position in the structure. 

PRESSURE-RELIEF VALVE. A pressure-actuated valve 
held closed by a spring or other means and designed to auto- 
matically relieve pressure at the pressure at which it is set. 

PUBLIC SEWER. A common sewer directiy controlled by 
public authority. 

PUBLIC WATER MAIN. A water-supply pipe for pubhc use 
controlled by public authority. 

PUBLIC WAY. Any street, alley or other parcel of land open to 
the outside air leading to a public street, which has been 
deeded, dedicated or otherwise permanently appropriated to 
the public for public use and that has a clear width and height of 
not less than 10 feet (3048 mm). 

PURGE. To clear of air, gas or other foreign substances. 

QUICK-CLOSING VALVE. A valve or faucet that closes 
automatically when released manually or controlled by 
mechanical means for fast-action closing. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



17 



DEFINITIONS 



R- VALUE, THERMAL RESISTANCE. The inverse of the 
time rate of heat flow through a building thermal envelope ele- 
ment from one of its bounding surfaces to the other for a unit 
temperature difference between the two surfaces, under steady 
state conditions, per unit area (h ■ ft^ • °F/Btu). 

RAMP. A walking surface that has a running slope steeper than 
1 unit vertical in 20 units horizontal (5 -percent slope). 

RECEPTOR. A fixture or device that receives the discharge 
from indirect waste pipes. 

REFRIGERANT. A substance used to ^produce refrigeration 
by its expansion or evaporation. 

REFRIGERANT COMPRESSOR. A specific machine, 
with or without accessories, for compressing a given refriger- 
ant vapor. 

REFRIGERATING SYSTEM. A combination of intercon- 
nected parts forming a closed circuit in which refrigerant is cir- 
culated for the purpose of extracting, then rejecting, heat. A 
direct refrigerating system is one in which the evaporator or 
condenser of the refrigerating system is in direct contact with 
the air or other substances to be cooled or heated. An indirect 
refrigerating system is one in which a secondary coolant 
cooled or heated by the refrigerating system is circulated to the 
air or other substance to be cooled or heated. 

REGISTERED DESIGN PROFESSIONAL. An individual 
who is registered or licensed to practice their respective design 
profession as defined by the statutory requirements of the pro- 
fessional registration laws of the state or jurisdiction in which 
the project is to be constructed. 

RELIEF VALVE, VACUUM. A device to prevent excessive 
buildup of vacuum in a pressure vessel. 

REPAIR. The reconstruction or renewal of any part of an exist- 
ing building for the purpose of its maintenance. 

REROOFING. The process of recovering or replacing an 
existing roof covering. See "Roof recover." 

RETURN AIR. Air removed from an approved conditioned 
space or location and recirculated or exhausted. 

RISER. A water pipe that extends vertically one full story or 
more to convey water to branches or to a group of fixtures. 

ROOF ASSEMBLY. A system designed to provide weather 
protection and resistance to design loads. The system consists 
of a roof covering and roof deck or a single component serving 
as both the roof covering and the roof deck. A roof assembly 
includes the roof deck, vapor retarder, substrate or thermal bar- 
rier, insulation, vapor retarder, and roof covering. 

ROOF COVERING. The covering applied to the roof deck 
for weather resistance, fire classification or appearance. 

ROOF COVERING SYSTEM. See "Roof assembly." 

ROOF DECK. The flat or sloped surface not including its sup- 
porting members or vertical supports. 

ROOF RECOVER. The process of installing an additional 
roof covering over a prepared existing roof covering without 
removing the existing roof covering. 



ROOF REPAIR. Reconstruction or renewal of any part of an 
existing roof for the purposes of its maintenance. 

ROOFTOP STRUCTURE. An enclosed structure on or 
above the roof of any part of a building. 

ROOM HEATER. A freestanding heating appliance installed 
in the space being heated and not connected to ducts. 

ROUGH-IN. The installation of all parts of the plumbing sys- 
tem that must be completed prior to the installation of fixtures. 
This includes DWV, water supply and built-in fixture supports. 

RUNNING BOND. The placement of masonry units such that 
head joints in successive courses are horizontally offset at least 
one-quarter the unit length. 

SANITARY SEWER. A sewer that carries sewage and 
excludes storm, surface and groundwater. 

SCUPPER. An opening in a wall or parapet that allows water 
to drain from a roof. 

SEISMIC DESIGN CATEGORY. A classification assigned 
to a structure based on its Seismic Group and the severity of the 
design earthquake ground motion at the site. 

SEPTIC TANK. A water-tight receptor that receives the dis- 
charge of a building sanitary drainage system and is con- 
structed so as to separate solids from the liquid, digest organic 
matter through a period of detention, and allovv' the liquids to 
discharge into the soil outside of the tank through a system of 
open joint or perforated piping or a seepage pit. 

SEWAGE. Any liquid waste containing animal matter, vegeta- 
ble matter or other impurity in suspension or solution. 

SEWAGE PUMP. A permanently installed mechanical device 
for removing sewage or liquid waste from a sump. 

SHALL. The term, when used in the code, is construed as man- 
datory. 

SHEAR WALL. A general term for walls that are designed 
and constructed to resist racking from seismic and wind by use 
of masonry, concrete, cold-formed steel or wood framing in 
accordance with Chapter 6 of this code and the associated limi- 
tations in Section R301.2 of this code. 

SIDE VENT. A vent connecting to the drain pipe through a fit- 
ting at an angle less than 45 degrees (0.79 rad) to the horizontal. 

SINGLE PLY MEMBRANE. A roofing membrane that is 
field applied using one layer of membrane material (either 
homogeneous or composite) rather than multiple layers. 

SINGLE STATION SMOKE ALARM. An assembly incor- 
porating the detector, control equipment and alarm sounding 
device in one unit that is operated from a power supply either in 
the unit or obtained at the point of installation. 

SKYLIGHT AND SLOPED GLAZING. See Section 
R308.6.1. 

SKYLIGHT, UNIT. See Section R308.6.1. 

SLIP JOINT. A mechanical-type joint used primarily on fix- 
ture traps. The joint tightness is obtained by compressing a 
friction-type washer such as rubber, nylon, neoprene, lead or 
special packing material against the pipe by the tightening of a 
(slip) nut. 



18 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



DEFINITIONS 



SLOPE. The fall (pitch) of a line of pipe in reference to a 
horizonal plane. In drainage, the slope is expressed as the fall in 
units vertical per units horizontal (percent) for a length of pipe. 

SMOKE-DEVELOPED RATING. A numerical index indi- 
cating the relative density of smoke produced by burning 
assigned to a material tested in accordance with ASTM E 84. 

SOIL STACK OR PIPE. A pipe that conveys sewage contain- 
ing fecal material. 

SOLAR HEAT GAIN COEFFICIENT (SHGC). The solar 
heat gain through a fenestration or glazing assembly relative to 
the incident solar radiation (Btu/h • ft^ ■ °F). 

SOLID MASONRY. Load-bearing or nonload-bearing con- 
struction using masonry units where the net cross-sectional 
area of each unit in any plane parallel to the bearing surface is 
not less than 75 percent of its gross cross-sectional area. Sohd 
masonry units shall conform to ASTM C 55, C 62, C 73, C 145 
or C 216. 

STACK. Any main vertical DWV line, including offsets, that 
extends one or more stories as directly as possible to its vent 
terminal. 

STACK BOND. The placement of masonry units in a bond 
pattern is such that head joints in successive courses are verti- 
cally aligned. For the purpose of this code, requirements for 
stack bond shall apply to all masonry laid in other than running 
bond. 

STACK VENT. The extension of soil or waste stack above the 
highest horizontal drain connected. 

STACK VENTING. A method of venting a fixture or fixtures 
through the soil or waste stack without individual fixture vents. 

STANDARD TRUSS. Any construction that does not permit 
the roof/ceiling insulation to achieve the required /?- value over 
the exterior walls. 

STATIONARY FUEL CELL POWER PLANT. A self con- 
tained package or factory-matched packages which constitute 
an automatically-operated assembly of integrated systems for 
generating useful electrical energy and recoverable thermal 
energy that is permanently connected and fixed in place. 

STORM SEWER, DRAIN. A pipe used for conveying rain- 
water, surface water, subsurface water and similar liquid waste. 

STORY. That portion of a building included between the upper 
surface of a floor and the upper surface of the floor or roof next 
above. 

STORY ABOVE GRADE. Any story having its finished floor 
surface entirely above grade, except that a basement shall be 
considered as a story above grade where the finished surface of 
the floor above the basement is: 

1. More than 6 feet (1829 mm) above grade plane. 

2. More than 6 feet (1829 mm) above the finished ground 
level for more than 50 percent of the total building per- 
imeter. 

3. More than 12 feet (3658 mm) above the finished ground 
level at any point. 



STRUCTURAL INSULATED PANELS (SIPS). Factory 
fabricated panels of solid core insulation with structural skins 
of oriented strand board (OSB) or plywood. 

STRUCTURE. That which is built or constructed. 

SUMP. A tank or pit that receives sewage or waste, located 
below the normal grade of the gravity system and that must be 
emptied by mechanical means. 

SUMP PUMP. A pump installed to empty a sump. These 
pumps are used for removing storm water only. The pump is 
selected for the specific head and volume of the load and is usu- 
ally operated by level controllers. 

SUNROOM. A one-story structure attached to a dwelling with | 
a glazing area in excess of 40 percent of the gross area of the 
structure's exterior walls and roof. 

SUPPLY AIR. Air delivered to a conditioned space through 
ducts or plenums from the heat exchanger of a heating, cooling 
or ventilating system. 

SUPPORTS. Devices for supporting, hanging and securing 
pipes, fixtures and equipment. 

SWEEP. A drainage fitting designed to provide a change in 
direction of a drain pipe of less than the angle specified by the 
amount necessary to establish the desired slope of the line. 
Sweeps provide a longer turning radius than bends and a less 
turbulent flow pattern (see "Bend" and "Elbow"). 

TEMPERATURE- AND PRESSURE-RELIEF (T AND P) 
VALVE. A combination relief valve designed to function as 
both a temperature-relief and pressure-relief valve. 

TEMPERATURE-RELIEF VALVE. A temperature-actu- 
ated valve designed to discharge automatically at the tempera- 
ture at which it is set. 

THERMAL ISOLATION. Physical and space conditioning 
separation from conditioned space(s). The conditioned 
space(s) shall be controlled as separate zones for heating and 
cooling or conditioned by separate equipment. 

THERMAL RESISTANCE, /?- VALUE. The inverse of the 
time rate of heat flow through a body from one of its bounding 
surfaces to the other for a unit temperature difference between 
the two surfaces, under steady state conditions, per unit area (h • 
ft2 • °F/Btu). 

THERMAL TRANSMITTANCE, 1/-FACTOR. The coeffi- 
cient of heat transmission (air to air) through a building enve- 
lope component or assembly, equal to the time rate of heat flow 
per unit area and unit temperature difference between the warm 
side and cold side air films (Btu/h • ft^ • °F). 

TOWNHOUSE. A single-family dwelling unit constructed in 
a group of three or more attached units in which each unit 
extends from foundation to roof and with open space on at least 
two sides. 

TRAP. A fitting, either separate or built into a fixture, that pro- 
vides a hquid seal to prevent the emission of sewer gases with- 
out materially affecting the flow of sewage or waste water 
through it. 

TRAP ARM. That portion of a fixture drain between a trap 
weir and the vent fitting. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



19 



DEFINITIONS 



TRAP PRIMER. A device or system of piping to maintain a 
water seal in a trap, typically installed where infrequent use of 
the trap would result in evaporation of the trap seal, such as 
floor drains. 

TRAP SEAL. The trap seal is the maximum vertical depth of 
liquid that a trap will retain, measured between the crown weir 
and the top of the dip of the trap. 

TRIM. Picture molds, chair rails, baseboards, handrails, door 
and window frames, and similar decorative or protective mate- 
rials used in fixed applications. 

TRUSS DESIGN DRAWING. The graphic depiction of an 
individual truss, which describes the design and physical char- 
acteristics of the truss. 

TYPE L VENT. A listed and labeled vent conforming to UL 
641 for venting oil-burning appliances listed for use with Type 
L vents or with gas appliances listed for use with Type B vents. 

{/-FACTOR, THERMAL TRANSMITTANCE. The coeffi- 
cient of heat transmission (air to air) through a building enve- 
lope component or assembly, equal to the time rate of heat flow 
per unit area and unit temperature difference between the warm 
side and cold side air films (Btu/h • ft^ ■ °F). 

UNCONFINED SPACE. A space having a volume not less 
than 50 cubic feet per 1,000 Btu/h (4.8 m^/kW) of the aggregate 
input rating of all appliances installed in that space. Rooms 
communicating directly with the space in which the appliances 
are installed, through openings not furnished with doors, are 
considered a part of the unconfined space. 

UNDERLAYMENT. One or more layers of felt, sheathing 
paper, nonbituminous saturated felt, or other approved material 
over which a roof covering, with a slope of 2 to 12 (17-percent 
slope) or greater, is applied. 

UNUSUALLY TIGHT CONSTRUCTION. Construction in 
which: 

1. Walls and ceilings comprising the building thermal 
envelope have a continuous water vapor retarder with a 
rating of 1 perm (5.7 • 10"^' kg/Pa • s • m^) or less with 
openings therein gasketed or sealed. 

2. Storm windows or weatherstripping is applied around 
the threshold and jambs of opaque doors and openable 
windows. 

3. Caulking or sealants are applied to areas such as joints 
around window and door frames between sole plates and 
floors, between wall-ceiling joints, between wall panels, 
at penetrations for plumbing, electrical and gas lines, and 
at other openings. 

VACUUM BREAKERS. A device which prevents 
backsiphonage of water by admitting atmospheric pressure 
through ports to the discharge side of the device. 

VAPOR PERMEABLE MEMBRANE. A material or cov- 
ering having a permeance rating of 5 perms (2.9 • 10"^ kg/Pa • 
s • m^) or greater, when tested in accordance with the desiccant 
method using Procedure A of ASTM E 96. A vapor permeable 
material permits the passage of moisture vapor. 



VAPOR RETARDER. A vapor resistant material, membrane 
or covering such as foil, plastic sheeting, or insulation facing 
havingapermeanceratingofl perm (5.7 • 1 0"^^ kg/Pa- sm^)or 
less, when tested in accordance with the dessicant method 
using Procedure A of ASTM E 96. Vapor retarders limit the 
amount of moisture vapor that passes through a material or wall 
assembly. 

VEHICULAR ACCESS DOOR. A door that is used primar- 
ily for vehicular traffic at entrances of buildings such as 
garages and parking lots, and that is not generally used for 
pedestrian traffic. 

VENT. A passageway for conveying flue gases from fuel-fired 
appliances, or their vent connectors, to the outside atmosphere. 

VENT COLLAR. See "Flue collar." 

VENT CONNECTOR. That portion of a venting system 
which connects the flue collar or draft hood of an appliance to a 
vent. 

VENT DAMPER DEVICE, AUTOMATIC. A device 
intended for installation in the venting system, in the outlet of 
an individual, automatically operated fuel burning appliance 
and that is designed to open the venting system automatically 
when the appliance is in operation and to close off the venting 
system automatically when the appliance is in a standby or 
shutdown condition. 

VENT GASES. Products of combustion from fuel-burning 
appliances, plus excess air and dilution air, in the venting sys- 
tem above the draft hood or draft regulator. 

VENT STACK. A vertical vent pipe installed to provide circu- 
lation of air to and from the drainage system and which extends 
through one or more stories. 

VENT SYSTEM. Piping installed to equalize pneumatic pres- 
sure in a drainage system to prevent trap seal loss or blow-back 
due to siphonage or back pressure. 

VENTILATION. The natural or mechanical process of sup- 
plying conditioned or unconditioned air to, or removing such 
air from, any space. 

VENTING. Removal of combustion products to the outdoors. 

VENTING SYSTEM. A continuous open passageway from 
the flue collar of an appliance to the outside atmosphere for the 
purpose of removing flue or vent gases. A venting system is 
usually composed of a vent or a chimney and vent connector, if 
used, assembled to form the open passageway. 

VERTICAL PIPE. Any pipe or fitting that makes an angle of 
45 degrees (0.79 rad) or more with the horizontal. 

VINYL SIDING. A shaped material, made principally from I 
rigid polyvinyl chloride (PVC), that is used to cover exterior I 
walls of buildings. | 

WALL, RETAINING. A wall not laterally supported at the I 
top, that resists lateral soil load and other imposed loads. | 

WALLS. Walls shall be defined as follows: 

Load-bearing wall is a wall supporting any vertical load in 
addition to its own weight. 



20 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



DEFINITIONS 



Nonbearing wall is a wall which does not support vertical 
loads other than its own weight. 

WASTE. Liquid-borne waste that is free of fecal matter. 

WASTE PIPE OR STACK. Piping that conveys only hquid 
sewage not containing fecal material. 

WATER-DISTRIBUTION SYSTEM. Piping which conveys 
water from the service to the plumbing fixtures, appliances, 
appurtenances, equipment, devices or other systems served, 
including fittings and control valves. 

WATER HEATER. Any heating appliance or equipment that 
heats potable water and supplies such water to the potable hot 
water distribution system. 

WATER MAIN. A water-supply pipe for public use. 

WATER OUTLET. A valved discharge opening, including a 
hose bibb, through which water is removed from the potable 
water system supplying water to a plumbing fixture or plumb- 
ing appliance that requires either an air gap or backflow 
pre-vention device for protection of the supply system. 

WATER-RESISTIVE BARRIER. A material behind an 
exterior wall covering that is intended to resist liquid water that 
has penetrated behind the exterior covering from further 
intruding into the exterior wall assembly. 

WATER-SERVICE PIPE. The outside pipe from the water 
main or other source of potable water supply to the water-dis- 
tribution system inside the building, terminating at the service 
valve. 

WATER-SUPPLY SYSTEM. The water-service pipe, the 
water-distributing pipes and the necessary connecting pipes, 
fittings, control valves and all appurtenances in or adjacent to 
the building or premises. 

WET VENT. A vent that also receives the discharge of wastes 
from other fixtures. 

WIND BORNE DEBRIS REGION. Areas within hurri- 
cane-prone regions within one mile of the coastal mean high 
water line where the basic wind speed is 110 miles per hour (49 
m/s) or greater; or where the basic wind speed is equal to or 
greater than 120 miles per hour (54 m/s); or Hawaii. 

WINDER. A tread with non-parallel edges. 

WOOD STRUCTURAL PANEL. A panel manufactured 
from veneers; or wood strands or wafers; bonded together with 
waterproof synthetic resins or other suitable bonding systems. 
Examples of wood structural panels are plywood, OSB or com- 
posite panels. 

YARD. An open space, other than a court, unobstructed from 
the ground to the sky, except where specifically provided by 
this code, on the lot on which a building is situated. 



2006 INTERNATIONAL RESIDENTIAL CODE® 21 



22 2006 INTERNATIONAL RESIDENTIAL CODE® 



Part III — Building Planning and Construction 

CHAPTER 3 

BUILDING PLANNING 



SECTION R301 
DESIGN CRITERIA 

R301.1 Application. Buildings and structures, and all parts 
thereof, shall be constructed to safely support all loads, includ- 
ing dead loads, live loads, roof loads, flood loads, snow loads, 
wind loads and seismic loads as prescribed by this code. The 
construction of buildings and structures in accordance with the 
provisions of this code shall result in a system that provides a 
complete load path that meets all requirements for the transfer of 
all loads from their point of origin through the load-resisting ele- 
ments to the foundation. Buildings and structures constructed as 
prescribed by this code are deemed to comply with the require- 
ments of this section. 

R301.1.1 Alternative provisions. As an alternative to the 
requirements in Section R301 . 1 the following standards are 
permitted subject to the limitations of this code and the limi- 
tations therein. Where engineered design is used in conjunc- 
tion with these standards the design shall comply with the 
International Building Code. 

1. American Forest and Paper Association (AF&PA) 
Wood Frame Construction Manual (WFCM). 

2. American fron and Steel Institute (AISI) Standard for 
Cold-Formed Steel Framing — Prescriptive Method 
for One- and Two-Family Dwellings (COFS/PM) with 
Supplement to Standard for Cold-Formed Steel Fram- 
ing-Prescriptive Method for One- and Two-Family 
Dwellings. 

R301.1.2 Construction systems. The requirements of this 
code are based on platform and balloon-frame construction for 
light-frame buildings. The requirements for concrete and 
masonry buildings are based on a balloon framing system. 
Other framing systems must have equivalent detaihng to 
ensure force transfer, continuity and compatible deformations. 

R301.1.3 Engineered design. When a building of otherwise 
conventional construction contains structural elements 
exceeding the limits of Section R301 or otherwise not con- 
forming to this code, these elements shall be designed in accor- 
dance with accepted engineering practice. The extent of such 
design need only demonstrate compUance of nonconventional 
elements with other applicable provisions and shall be compat- 
ible with the performance of the conventional framed system. 
Engineered design in accordance with the International Build- 
ing Code is permitted for all buildings and structures, and parts 
thereof, included in the scope of this code. 



R301.2 Climatic and geographic design criteria. Buildings 
shall be constructed in accordance with the provisions of this 
code as limited by the provisions of this section. Additional cri- 
teria shall be established by the local jurisdiction and set forth 
in Table R301. 2(1). 

R301.2.1 Wind limitations. Buildings and portions thereof 
shall be limited by wind speed, as defined in Table R301 .2(1) 
and construction methods in accordance with this code. Basic 
wind speeds shall be determined from Figure R301.2(4). 
Where different construction methods and structural materi- 
als are used for various portions of a building, the applicable 
requirements of this section for each portion shall apply. 
Where loads for wall coverings, curtain walls, roof coverings, 
exterior windows, skylights, garage doors and exterior doors 
are not otherwise specified, the loads listed in Table 
R301.2(2) adjusted for height and exposure using Table 
R301.2(3) shall be used to determine design load perfor- 
mance requirements for wall coverings, curtain walls, roof 
coverings, exterior windows, skyhghts, garage doors and 
exterior doors. Asphalt shingles shall be designed for wind 
speeds in accordance with Section R905.2.6. 

R301.2.1.1 Design criteria. Construction in regions 
where the basic wind speeds from Figure R301 .2(4) equal 
or exceed 100 miles per hour (45 m/s) in hurricane-prone 
regions, or 1 10 miles per hour (49 m/s) elsewhere, shall be 
designed in accordance with one of the following: 

1 . American Forest and Paper Association (AF&PA) 
Wood Frame Construction Manual for One- and 
Two-Family Dwellings (WFCM); or 

2. Southern Building Code Congress International 
Standard for Hurricane Resistant Residential 
Construction (SSTD 10); or 

3. Minimum Design Loads for Buildings and Other 
Structures (ASCE-7); or 

4. American Iron and Steel Institute (AISI), Stan- 
dard for Cold-Formed Steel Framing — Prescrip- 
tive Method For One- and Two-Family Dwellings 
(COFS/PM) with Supplement to Standard for 
Cold-Formed Steel Framing — Prescriptive 
Method For One- and Two-Family Dwellings. 

5. Concrete construction shall be designed in accor- 
dance with the provisions of this code. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



23 



BUILDING PLANNING 



TABLE R301. 2(1) 
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA 



GROUND 
SNOW 
LOAD 


WIND 

SPEED" 

(mph) 


SEISMIC 

DESIGN 

CATEGORY* 


SUBJECT TO DAMAGE FROM 


WINTER 
DESIGN 
TEMP^ 


ICE BARRIER 

UNDERLAYMENT 

REQUIRED" 


FLOOD 
HAZARDS^ 


AIR 

FREEZING 

INDEX' 


MEAN 

ANNUAL 

TEMP' 


Weathering^ 


Frost line 
depth" 


Termite'' 

























For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s. 

a. Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column 
shall be filled in with the weathering index (i.e., "negligible," "moderate" or "severe") for concrete as determined from the Weathering Probability Map [Figure 
R301 .2(3)]. The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652. 

b. The frost line depth may require deeper footings than indicated in Figure R403.1(l). The jurisdiction shall fill in the frost line depth column with the minimum 
depth of footing below finish grade. 

c. The j urisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local subterranean termite dam- 
age. 

d. The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [FigureR30 1.2(4)]. Wind exposure category shall be deter- 
mined on a site-specific basis in accordance with Section R301.2.1.4. 

e. The outdoor design dry-bulb temperature shall be selected from the columns of 97 V2-percent values for winter from Appendix D of the International Plumbing 
Code. Deviations from the Appendix D temperatures shall be permitted to reflect local climates or local weather experience as determined by the building official. 

f. The jurisdiction shall fill in this part of the table with the seismic design category determined from Section R301.2.2.1. 

g. The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction's entry into the National Flood Insurance Program (date of adoption of the first 
code or ordinance for management of flood hazard areas), (b) the date(s) of the currently effective FIRM and FBFM, or other flood hazard map adopted by the com- 
munity, as may be amended. 

h. In accordance with Sections R905.2.7.1,R905.4.3.1,R905.5.3.1,R905.6.3.1,R905.7.3.1 and R905.8.3.1, where there has beenahistory of local damage from the 
effects of ice damming, the jurisdiction shall fill in this part of the table with "YES". Otherwise, the jurisdiction shall fill in this part of the table with "NO". 

i. The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (BF-days) from Figure R403.3(2) or from the 100-year (99%) 
value on the National Climatic Data Center data table "Air Freezing Index- USA Method (Base 32°Fahrenheit)" at www.ncdc.noaa.gov/fpsf.html. 

j. The jurisdiction shall fill in this part of the table with the mean annual temperature from the National Climatic Data Center data table "Air Freezing Index-USA 
Method (Base 32°Fahrenheit)" at www.ncdc.noaa.gov/fpsf.html. 



24 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



BUILDING PLANNING 



TABLE R301. 2(2) 

COMPONENT AND CLADDING LOADS FOR A BUILDING WITH A MEAN 

ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE B (psf) 





ZONE 


EFFECTIVE 
WIND 
AREA 
(feet^) 


BASIC WIND SPEED (mph— 3-second gust) 


85 


90 


100 


105 


110 


120 


125 


130 


140 


145 


150 


170 


M 
(U 
0) 

g" 

■o 
o 

o 

o 

A 

O 
O 
CE 


1 


10 


10.0 


-13.0 


10.0 


-14.6 


10.0 


-18.0 


10.0 


-19.8 


10.0 


-21.8 


10.5 


-25.9 


11.4 


-28.1 


12.4 


-30.4 


14.3 


-35.3 


15.4 


-37.8 


16.5 


-40.5 


21.1 


-52.0 


1 


20 


10.0 


-12.7 


10.0 


-14.2 


10.0 


-17.5 


10.0 


-19.3 


10.0 


-21.2 


10.0 


-25.2 


10.7 


-27.4 


11.6 


-29.6 


13.4 


-34.4 


14.4 


-36.9 


15.4 


-39.4 


19.8 


-50.7 


1 


50 


10.0 


-12.2 


10.0 


-13.7 


10.0 


-16.9 


10.0 


-18.7 


10.0 


-20.5 


10.0 


-24.4 


10.0 


-26.4 


10.6 


-28.6 


12.3 


-33.2 


13.1 


-35.6 


14.1 


-38.1 


18.1 


-48.9 


1 


100 


10.0 


-11.9 


10.0 


-13.3 


10.0 


-18.5 


10.0 


-18.2 


10.0 


-19.9 


10.0 


-23.7 


10.0 


-25.7 


10.0 


-27.8 


11.4 


-32.3 


12.2 


-34.6 


13.0 


-37.0 


16.7 


-47.6 


2 


10 


10.0 


-21.8 


10.0 


-24.4 


10.0 


-30.2 


10.0 


-33.3 


10.0 


-36.5 


10.5 


-43.5 


11.4 


-47.2 


12.4 


-51.0 


14.3 


-59.2 


15.4 


-63.5 


16.5 


-67.9 


21.1 


-87.2 


2 


20 


10.0 


-19.5 


10.0 


-21.8 


10.0 


-27.0 


10.0 


-29.7 


10.0 


-32.6 


10.0 


-38.8 


10.7 


-42.1 


11.6 


-45.6 


13.4 


-52.9 


14.4 


-56.7 


15.4 


-60.7 


19.8 


-78.0 


2 


50 


10.0 


-16.4 


10.0 


-18.4 


10.0 


-22.7 


10.0 


-25.1 


10.0 


-27.5 


10.0 


-32.7 


10.0 


-35.5 


10.6 


-38.4 


12.3 


-44.5 


13.1 


-47.8 


14.1 


-51.1 


18.1 


-65.7 


2 


100 


10.0 


-14.1 


10.0 


-15.8 


10.0 


-19.5 


10.0 


-21.5 


10.0 


-23.6 


10.0 


-28.1 


10.0 


-30.5 


10.0 


-33.0 


11.4 


-38.2 


12.2 


-41.0 


13.0 


-43.9 


16.7 


-56.4 


3 


10 


10.0 


-32.8 


10.0 


-36.8 


10.0 


-45.4 


10.0 


-50.1 


10.0 


-55.0 


10.5 


-65.4 


11.4 


-71.0 


12.4 


-76.8 


14.3 


-89.0 


15.4 


-95.5 


16.5 


-102.2 


21.1 


-131.3 


3 


20 


10.0 


-27.2 


10.0 


-30.5 


10.0 


-37.6 


10.0 


-41.5 


10.0 


-45.5 


10.0 


-54.2 


10.7 


-58.8 


11.6 


-63.6 


13.4 


-73.8 


14.4 


-79.1 


15.4 


-84.7 


19.8 


-108.7 


■ 
3 


50 


10.0 


-19.7 


10.0 


-22.1 


10.0 


-27.3 


10.0 


-30.1 


10.0 


-33.1 


10.0 


-39.3 


10.0 


-42.7 


10.6 


-46.2 


12.3 


-53.5 


13.1 


-57.4 


14.1 


-61.5 


18.1 


-78.9 


3 


100 


10.0 


-14.1 


10.0 


-15.8 


10.0 


-19.5 


10.0 


-21.5 


10.0 


-23.6 


10.0 


-28.1 


10.0 


-30.5 


10.0 


-33.0 


11.4 


-38.2 


12.2 


-41.0 


13.0 


-43.9 


16.7 


-56.4 


(0 
0) 
0) 

D) 

0) 

T3 
O 

n 

O 

o 

A 

O 
O 

tc 


1 


10 


10.0 


-11.9 


10.0 


-13.3 


10.4 


-16.5 


11.4 


-18.2 


12.5 


-19.9 


14.9 


-23.7 


16.2 


-25.7 


17.5 


-27.8 


20.3 


-32.3 


21.8 


-34.6 


23.3 


-37.0 


30.0 


-47.6 


I 


20 


10.0 


-11.6 


10.0 


-13.0 


10.0 


-16.0 


10.4 


-17.6 


11.4 


-19.4 


13.6 


-23.0 


14.8 


-25.0 


16.0 


-27.0 


18.5 


-31.4 


19.9 


-33.7 


21.3 


-36.0 


27.3 


-46.3 


1 


50 


10.0 


-11.1 


10.0 


-12.5 


10.0 


-15.4 


10.0 


-17.0 


10.0 


-18.6 


11.9 


-22.2 


12.9 


-24.1 


13.9 


-26.0 


16.1 


-30.2 


17.3 


-32.4 


18.5 


-34.6 


23.8 


-44.5 


1 


100 


10.0 


-10.8 


10.0 


-12.1 


10.0 


-14.9 


10.0 


-16.5 


10.0 


-18.1 


10.5 


-21.5 


11.4 


-23.3 


12.4 


-25.2 


14.3 


-29.3 


15.4 


-31.4 


16.5 


-33.6 


21.1 


-43.2 


2 


10 


10.0 


-25.1 


10.0 


-28.2 


10.4 


-34.8 


11.4 


-38.3 


12.5 


-42.1 


14.9 


-50.1 


16.2 


-54.3 


17.5 


-58.7 


20.3 


-68.1 


21.8 


-73.1 


23.3 


-78.2 


30.0 


-100.5 


2 


20 


10.0 


-22.8 


10.0 


-25.6 


10.0 


-31.5 


10.4 


-34.8 


11.4 


-38.2 


13.6 


-45.4 


14.8 


-49.3 


16.0 


-53.3 


18.5 


-61.8 


19.9 


-66.3 


21.3 


-71.0 


27.3 


-91.2 


2 


50 


10.0 


-19.7 


10.0 


-22.1 


10.0 


-27.3 


10.0 


-30.1 


10.0 


-33.0 


11.9 


-39.3 


12.9 


-42.7 


13.9 


-46.1 


16.1 


-53.5 


17.3 


-57.4 


18.5 


-61.4 


23.8 


-78.9 


2 


100 


10.0 


-17.4 


10.0 


-19.5 


10.0 


-24.1 


10.0 


-26.6 


10.0 


-29.1 


10.5 


-34.7 


11.4 


-37.6 


12.4 


-40.7 


14.3 


-47.2 


15.4 


-50.6 


16.5 


-54.2 


21.1 


-69.6 


3 


10 


10.0 


-25.1 


10.0 


-28.2 


10.4 


-34.8 


11.4 


-38.3 


12.5 


-42.1 


14.9 


-50.1 


16.2 


-54.3 


17.5 


-58.7 


20.3 


-68.1 


21.8 


-73.1 


23.3 


-78.2 


30.0 


-100.5 


3 


20 


10.0 


-22.8 


10.0 


-25.6 


10.0 


-31.5 


10.4 


-34.8 


11.4 


-38.2 


13.6 


-45.4 


14.8 


-49.3 


16.0 


-53.3 


18.5 


-61.8 


19.9 


-66.3 


21.3 


-71.0 


27.3 


-91.2 


3 


50 


10.0 


-19.7 


10.0 


-22.1 


10.0 


-27.3 


10.0 


-30.1 


10.0 


-33.0 


11.9 


-39.3 


12.9 


-42.7 


13.9 


-46.1 


16.1 


-53.5 


17.3 


-57.4 


18.5 


-61.4 


23.8 


-78.9 


3 


100 


10.0 


-17.4 


10.0 


-19.5 


10.0 


-24.1 


10.0 


-26.6 


10.0 


-29.1 


10.5 


-34.7 


11.4 


-37.6 


12.4 


-40.7 


14.3 


-47.2 


15.4 


-50.6 


16.5 


-54.2 


21.1 


-69.6 


0) 

O) 
0) 

■o 

$ 

o 

i 

A 
1 

tc 


1 


10 


11.9 


-13.0 


13.3 


-14.6 


16.5 


-18.0 


18.2 


-19.8 


19.9 


-21.8 


23.7 


-25.9 


25.7 


-28.1 


27.8 


-30.4 


32.3 


-35.3 


34.6 


-37.8 


37.0 


-40.5 


47.6 


-52.0 


1 


20 


11.6 


-12.3 


13.0 


-13.8 


16.0 


-17.1 


17.6 


-18.8 


19.4 


-20.7 


23.0 


-24.6 


25.0 


-26.7 


27.0 


-28.9 


31.4 


-33.5 


33.7 


-35.9 


36.0 


-38.4 


46.3 


-49.3 


1 


50 


11.1 


-11.5 


12.5 


-12.8 


15.4 


-15.9 


17.0 


-17.5 


18.6 


-19.2 


22.2 


-22.8 


24.1 


-24.8 


26.0 


-25.8 


30.2 


-31.1 


32.4 


-33.3 


34.6 


-35.7 


44.5 


-45.8 


1 


100 


10.8 


-10.8 


12.1 


-12.1 


14.9 


-14.9 


16.5 


-16.5 


18.1 


-18.1 


21.5 


-21.5 


23.3 


-23.3 


25.2 


-25.2 


29.3 


-29.3 


31.4 


-31.4 


33.6 


-33.6 


43.2 


-43.2 


2 


10 


11.9 


-15.2 


13.3 


-17.0 


16.5 


-21.0 


18.2 


-23.2 


19.9 


-25.5 


23.7 


-30.3 


25.7 


-32.9 


27.8 


-35.6 


32.3 


-41.2 


34.6 


-44.2 


37.0 


-47.3 


47.6 


-60.8 


2 


20 


11.6 


-14.5 


13.0 


-16.3 


16.0 


-20.1 


17.6 


-22.2 


19.4 


-24.3 


23.0 


-29.0 


25.0 


-31.4 


27.0 


-34.0 


31.4 


-39.4 


33.7 


-42.3 


36.0 


-45.3 


46.3 


-58.1 


2 


50 


11.1 


-13.7 


12.5 


-15.3 


15.4 


-18.9 


17.0 


-20.8 


18.6 


-22.9 


22.2 


-27.2 


24.1 


-29.5 


26.0 


-32.0 


30.2 


-37.1 


32.4 


-39.8 


34.6 


-42.5 


44.5 


-54.6 


2 


100 


10.8 


-13.0 


12.1 


-14.6 


14.9 


-18.0 


16.5 


-19.8 


18.1 


-21.8 


21.5 


-25.9 


23.3 


-28.1 


25.2 


-30.4 


29.3 


-35.3 


31.4 


-37.8 


33.6 


-40.5 


43.2 


-52.0 


3 


10 


11.9 


-15.2 


13.3 


-17.0 


16.5 


-21.0 


18.2 


-23.2 


19.9 


-25.5 


23.7 


-30.3 


25.7 


-32.9 


27.8 


-35.6 


32.3 


-41.2 


34.6 


-44.2 


37.0 


-47.3 


47.6 


-60.8 


3 


20 


11.6 


-14.5 


13.0 


-16.3 


16.0 


-20.1 


17.6 


-22.2 


19.4 


-24.3 


23.0 


-29.0 


25.0 


-31.4 


27.0 


-34.0 


31.4 


-39.4 


33.7 


-42.3 


36.0 


-45.3 


46.3 


-58.1 


3 


50 


11.1 


-13.7 


12.5 


-15.3 


15.4 


-18.9 


17.0 


-20.8 


18.6 


-22.9 


22.2 


-27.2 


24.1 


-29.5 


26.0 


-32.0 


30.2 


-37.1 


32.4 


-39.8 


34.6 


-42.5 


44.5 


-54.5 


3 


100 


10.8 


-13.0 


12.1 


-14.6 


14.9 


-18.0 


16.5 


-19.8 


18.1 


-21.8 


21.5 


-25.9 


23.3 


-28.1 


25.2 


-30.4 


29.3 


-35.3 


31.4 


-37.8 


33.6 


-40.5 


43.2 


-52.0 


i 


4 


10 


13.0 


-14.1 


14.6 


-15.8 


18.0 


-19.5 


19.8 


-21.5 


21.8 


-23.6 


25.9 


-28.1 


28.1 


-30.5 


30.4 


-33.0 


35.3 


-38.2 


37.8 


-41.0 


40.5 


-43.9 


52.0 


-56.4 


4 


20 


12.4 


-13.5 


13.9 


-15.1 


17.2 


-18.7 


18.9 


-20.6 


20.8 


-22.6 


24.7 


-26.9 


26.8 


-29.2 


29.0 


-31.6 


33.7 


-36.7 


36.1 


-39.3 


38.7 


-42.1 


49.6 


-54.1 


4 


50 


11.6 


-12.7 


13.0 


-14.3 


16.1 


-17.6 


17.8 


-19.4 


19.5 


-21.3 


23.2 


-25.4 


25.2 


-27.5 


27.2 


-29.8 


31.6 


-34.6 


33.9 


-37.1 


36.2 


-39.7 


46.6 


-51.0 


4 


100 


11.1 


-12.2 


12.4 


-13.6 


15.3 


-16.8 


16.9 


-18.5 


18.5 


-20.4 


22.0 


-24.2 


23.9 


-26.3 


25.9 


-28.4 


30.0 


-33.0 


32.2 


-35.4 


34.4 


-37.8 


44.2 


-48.6 


5 


10 


13.0 


-17.4 


14.6 


-19.5 


18.0 


-24.1 


19.8 


-26.6 


21.8 


-29.1 


25.9 


-34.7 


28.1 


-37.6 


30.4 


-40.7 


35.3 


-47.2 


37.8 


-50.6 


40.5 


-54.2 


52.0 


-69.6 


5 


20 


12.4 


-16.2 


13.9 


-18.2 


17.2 


-22.5 


18.9 


-24.8 


20.8 


-27.2 


24.7 


-32.4 


26.8 


-35.1 


29.0 


-38.0 


33.7 


-44.0 


36.1 


-47.2 


38.7 


-50.5 


49.6 


-64.9 


5 


50 


11.6 


-14.7 


13.0 


-16.5 


16.1 


-20.3 


17.8 


-22.4 


19.5 


-24.6 


23.2 


-29.3 


25.2 


-31.8 


27.2 


-34.3 


31.6 


-39.8 


33.9 


-42.7 


36.2 


-45.7 


46.6 


-58.7 


5 


100 


11.1 


-13.5 


12.4 


-15.1 


15.3 


-18.7 


16.9 


-20.6 


18.5 


-22.6 


22.0 


-26.9 


23.9 


-29.2 


25.9 


-31.6 


30.0 


-36.7 


32.2 


-39.3 


34.4 


-42.1 


44.2 


-54.1 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m^, 1 mile per hour = 0.447 m/s. 

NOTES: For effective areas between those given above the load may be interpolated, otherwise use the load associated with the lower effective area. 

Table values shall be adjusted for height and exposure by multiplying by the adjustment coefficient in Table R301.2(3). 

See Figure R301.2(7) for location of zones. 

Plus and minus signs signify pressures acting toward and away from the building surfaces. 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



25 



BUILDING PLANNING 



TABLE R301. 2(3) 
HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS FOR TABLE R301.2(2) 



MEAN 
ROOF HEIGHT 


EXPOSURE 


B 


C 


D 


15 


1.00 


1.21 


1.47 


20 


1.00 


1.29 


1.55 


25 


1.00 


1.35 


1.61 


30 


1.00 


1.40 


1.66 


35 


1.05 


1.45 


1.70 


40 


1.09 


1.49 


1.74 


45 


1.12 


1.53 


1.78 


50 


1.16 


1.56 


1.81 


55 


1.19 


1.59 


1.84 


60 


1.22 


1.62 


1.87 



20 10 




DESIGN TEMPERATURES IN THIS AREA MUST BE BASED ON 
ANALYSIS OF LOCAL CLIMATE AND TOPOGRAPHY 



For SI: °C = [(°F)-32] /I.8. 



FIGURE R301. 2(1) 
ISOLINES OF THE 97V2 PERCENT WINTER (DECEMBER, JANUARY AND FEBRUARY) DESIGN TEMPERATURES (°F) 



26 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



o 

z 
> 

r- 

33 

m 

U) 

o 
m 

z 

H 

> 

1- 

O 

o 

D 
"I 



Explanation 


Seismic Design 


°^og Category 


^H E 


117 


M|| 






Da 


83 


. ^ ™ - " 








D, 


67 




Do 


50 




c 


33 




B 


17 




A 


^ ' 



165° 160° 135° 



i i-^- 



aV 






^ 



^■f-^>yT 






5->.-^ i 



f\^ 



C„ 



o 



sf^ 



f^. 



fff/" 



-\^^ 



"RIHERENCES 

Wesson, R., Frankel, A., Mueller, C, and Harrasen, S„ 1 999,' 
ProbabiJ istic Seismic Maxatd Maps of A! aska D.S. 
Geolo^cal Survey Open-File Report 99-36, 20 p. 

Wesson, R, Ftania!, A., Mueller, C, aBd Hamiscn, S., 1 999, 
Seismic Hazard MajB for Alaska: and the Aleutian Islands: 
U.S. Geological Survey Miscellaneous Investi^tions Series 
1-2679, 2 shBem, scale J : 7,5(X\000 

Map Prepared by US. Geologcal Survey 



250 



SCO KILOiVCreSS 



CD 

C 



For SI: 1 mile = 1.61km. 



FIGURE R301. 2(2) 
SEISMIC DESIGN CATEGORIES— SITE CLASS D 

(continued) 



O 

T3 

|- 
3> 



O 



REFERENCES 

KlL'iii, I'-., l-rankil. A., Muuik-r. C. Wcssoa R., ami Okiilxi, P., 

2001, Seismic Ha/anJ in Hawaii: High Raitc oiLirgi,! 

EirthMiukes vmd Probabilistic Ground Moiion Maps. 

Bulletin of the SeismototLical Societv of America v, 91 . 

Pii 479-498. 
Klein, H., Frankt:!, A., Mut'ller, C, Wcison, R., and Ofcubo, P., 

20()(). Seismic Ha/iiai Maps for Hawaii: l.i.S. Geoiogita! 

Survey Mi-sceiianeoiLS Investigatiojis Series 1-2724. 

2 .shuJts, .scale ! ;2,OOO.CX30 




O 



For SI: 1 mile = 1.61 km. 



O 
O 

o 
m 



FIGURE R301. 2(2)— continued 
SEISMIC DESIGN CATEGORIES— SITE CLASS D 

(continued) 




%g 



Explanation 

Seismic Design 
Category 




Scale l:2,0Oa(X» 



100 KILOMETERS 



REFERENCES 

Mueller, C, Frankel, A., Peteisen, M, and Leyendecker, E, 2003, 
Documentation for 2003 USGS Sdsmic Hazaid Maps for Purato Ricx) 
and the U.S. Ytiffa Islands, U.S. Geological Survey Opesa-FHe 
Report 03-379. 

Mueller, C, Fninkel, A., Petersen, M, and Leyendecker, E, 2004^ 
S^mic-Hazaid Maps for Puerto Rico uid &e U.S. Viipn Island, 
She^ 2 - 2% Probability of Exceedance in 50 Years for Peak 
Horizontal Acceleration and Horizontal Spectral Response Acceleration 
for a 2, 0.3, and 1 .0 Second Pbiiods U.S. Geolo^cal Survey 
Geologic Invratigation Series (in progress). 

Map Prepared by U.S. Geological Survey 



For SI: 1 mile = 1.61 km. 



FIGURE R301. 2(2)— continued 
SEISMIC DESIGN CATEGORIES— SITE CLASS D 



00 

c 
i- 
g 
z 
o 

■0 



(continued) 



O 



BUILDING PLANNING 




FIGURE R301. 2(2)— continued 
SEISMIC DESIGN CATEGORIES— SITE CLASS D 

(continued) 



30 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANES!ING 




FJGURE R301. 2(2)— continued 

SEISMIC DESIGN CATEGORIES— SITE CLASS D 



2006 INTERNATIONAL RESIDENTIAL CODE® 



31 




o 
•a 

> 



o 



SEVERE 
MODERATE 

NEGLIGIBLE 



a. Alaska and Hawaii are classified as severe and negligible, respectively. 

b. Lines defining areas are approximate only. Local conditions may be more or less severe than indicated by region classification. A severe classification is where weather conditions result in significant snowfall 
combined with extended periods during which there is little or no natural thawing causing deicing salts to be used extensively. 

FIGURE R301. 2(3) 
WEATHERING PROBABILITY MAP FOR CONCRETE 



BUILDING PLANNING 



Lcx;ation 


Vmph 


(m/s) 


Hawaii 


105 


(47) 


Puerto Rico 


145 


(65) 


Guam 


170 


(76) 


Virgin Islands 


145 


(65) 


American Samoa 


125 


(56) 



Special Wind Region 




-154 



148 -142 



FIGURE R301. 2(4) 
BASIC WIND SPEEDS FOR 50-YEAR MEAN RECURRENCE INTERVAL 

(continued) 

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. 

a. Values are nominal design 3-second gust wind speeds in miles per hour at 33 feet above ground for Exposure C category. 

b. Linear interpolation between wind contours is permitted. 

c. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area. 

d. Mountainous terrain, gorges, ocean promontories and special wind regions shall be examined for unusual wind conditions. 

e. Enlarged view of Eastern and Southern seaboards are on the following pages. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



33 



BUILDING PLANNING 




Location 


Vmph 


Hawaii 


105 


Puerto Rico 


145 


Guam 


170 


Virgin Islands 


145 


American Samoa 


125 



FIGURE R301. 2(4)— continued 
BASIC WIND SPEEDS FOR 50-YEAR MEAN RECURRENCE INTERVAL 

(continued) 

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. 

a. Values are nominal design 3-second gust wind speeds in miles per hour at 33 feet above ground for Exposure C category. 

b. Linear interpolation between wind contours is permitted. 

c. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area. 

d. Mountainous terrain, gorges, ocean promontories and special wind regions shall be examined for unusual wind conditions. 

e. Enlarged view of Eastern and Southern seaboards are on the following pages. 



34 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANNING 




FIGURE R301. 2(4)— continued 
BASIC WIND SPEEDS FOR 50-YEAR MEAN RECURRENCE INTERVAL 

(continued) 

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. 

a. Values are nominal design 3-second gust wind speeds in miles per hour at 33 feet above ground for Exposure C category. 

b. Linear interpolation between wind contours is permitted. 

c. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area. 

d. Mountainous terrain, gorges, ocean promontories and special wind r^ions shall be examined for unusual wind conditions. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



35 



BUILDING PLANNING 




100 



Special Wind Region 



FIGURE R301.2(4)^continued 
BASIC WIND SPEEDS FOR 50-YEAR MEAN RECURRENCE INTERVAL 

(continued) 

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. 

a. Values are nominal design 3-second gust wind speeds in miles per hour at 33 feet above ground for Exposure C category. 

b. Linear interpolation between wind contours is permitted. 

c. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area. 

d. Mountainous terrain, gorges, ocean promontories and special wind regions shall be examined for unusual wind conditions. 



36 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



BUILDING PLANNING 



130 




140 



Special Wind Region 



FIGURE R301. 2(4)— continued 
BASIC WIND SPEEDS FOR 50-YEAR MEAN RECURRENCE INTERVAL 



For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. 

a. Values are nominal design 3-second gust wind speeds in miles per hour at 33 feet above ground for Exposure C category. 

b. Linear interpolation between wind contours is permitted. 

c. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area. 

d. Mountainous terrain, gorges, ocean promontories and special wind regions shall be examined for unusual wind conditions. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



37 



BUILDING PLANNING 



|20 




For SI: 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 mile = 1.61 km. 

a. In CS areas, site-specific Case Studies are required to establish ground snow loads. Extreme local varia- 
tions in ground snow loads in these areas preclude mapping at this scale. 

b. Numbers in parentheses represent the upper elevation limits in feet for the ground snow load values pre- 
sented below. Site-specific case studies are required to establish ground snow loads at elevations not 
covered. 



J L 



100 



200 



300 miles 



FIGURE R301. 2(5) 
GROUND SNOW LOADS, Pg, FOR THE UNITED STATES (Ib/ft^) 

(continued) 



38 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANNING 



(600) 
80 




For SI: 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kRi. 



FfGURE R301. 2(5)— continued 
GROUND SNOW LOADS, Pg, FOR THE UNITED STATES (Ib/ft^) 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



39 



m 

3) 

z 
> 

H 
O 

z 
> 

r- 

m 

0) 

5 
m 

z 



o 
o 
o 
rn 




z 
o 



VERY HEAVY 



^^ MODERATE TO HEAVY 
SLIGHT TO MODERATE 
NONE TO SLIGHT 



NOTE: Lines defining areas are approximate only. Local conditions may be more or less severe than indicated by the region classification. 

FIGURE R301. 2(6) 
TERMITE INFESTATION PROBABILITY MAP 



BUILDING PLANNING 




i^ 





® 1® 

r - 

® !® 


®i @ 


~@~1® 



WALLS 



GABLE ROOFS 
0<10° 




< 10° 




GABLE ROOFS 
10°<0 < 45° 



HIP ROOFS 
10° <0 < 30' 



For SI: 1 foot = 304.8 mm, 1 degree = 0.0175 rad. 
NOTE: a = 4 feet in all cases. 



FIGURE R301. 2(7) 
COMPONENT AND CLADDING PRESSURE ZONES 



R301.2.1.2 Protection of openings. Windows in build- 
ings located in windbome debris regions shall have 
glazed openings protected from windborne debris. 
Glazed opening protection for windbome debris shall 
meet the requirements of the Large Missile Test of an 
approved impact resisting standard or ASTM E 1 996 and 
ASTM E 1886 referenced therein. 

Exception: Wood structural panels with a minimum 
of 7,6 inch (11 mm) and a maximum span of 8 feet 
(2438 mm) shall be permitted for opening protection 
in one- and two-story buildings. Panels shall be precut 



so that they shall be attached to the framing surround- 
ing the opening containing the product with the 
glazed opening. Panels shall be secured with the 
attachment hardware provided. Attachments shall be 
designed to resist the component and cladding loads 
determined in accordance with either Table 
R301.2(2) or Section 1609.6.5 of the International 
Building Code. Attachment in accordance with Table 
R301.2.1.2 is permitted for buildings with a mean 
roof height of 3 3 feet ( 1 05 8 mm) or less where wind 
speeds do not exceed 130 miles per hour (58 m/s). 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



41 



BUILDING PLANNING 



TABLER301.2.1.2 

WINDBORNE DEBRIS PROTECTION FASTENING SCHEDULE 

FOR WOOD STRUCTURAL PANELS^'' •=•" 



FASTENER 
TYPE 


FASTENER SPACING (inches) 


Panel span 
< 4 feet 


4 feet < 

panel span 

< 6 feet 


6 feet < 

panel span 

< 8 feet 


No. 6 Screws 


16" 


12" 


9" 


No. 8 Screws 


16" 


16" 


12" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448N, 
I mile per hour = 0.447 m/s. 

a. This table is based on 130mphwindspeedsanda33-footmeanroofheight. 

b. Fasteners shall be installed at opposing ends of the wood structural panel. 
Fasteners shall be located a minimum of 1 inch from the edge of the panel. 

c. Fasteners shall be long enough to penetrate through the exterior wall cover- 
ing and a minimum of 1 V4 inches into wood wall framing and a minimum of 
1 '/4 inches into concrete block or concrete, and into steel framing a mini- 
mum of 3 exposed threads. Fasteners shall be located a minimum of 2V2 
inches from the edge of concrete block or concrete. 

d. Where screws are attached to masonry or masonry/stucco, they shall be 
attached using vibration-resistant anchors having a minimum ultimate with- 
drawal capacity of 490 pounds. 

R301.2.1.3 Wind speed conversion. When referenced 
documents are based on fastest mile wind speeds, the 
three-second gust basic wind speeds, V^^, of Figure 
R301 .2(4) shall be converted to fastest mile wind speeds, 
Vf^, using Table R301.2.1.3. 

R301.2.1.4 Exposure category. For each wind direction 
considered, an exposure category that adequately 
reflects the characteristics of ground surface irregulari- 
ties shall be determined for the site at which the building 
or structure is to be constructed. For a site located in the 
transition zone between categories, the category result- 
ing in the largest wind forces shall apply. Account shall 
be taken of variations in ground surface roughness that 
arise from natural topography and vegetation as well as 
from constructed features. For any given wind direction, 
the exposure in which a specific building or other struc- 
ture is sited shall be assessed as being one of the follow- 
ing categories: 

1 . Exposure A. Large city centers with at least 50 per- 
cent of the buildings having a height in excess of 
70 feet (21 336 mm). Use of this exposure category 
shall be limited to those areas for which terrain 
representative of Exposure A prevails in the 
upwind direction for a distance of at least 0.5 mile 
(0.8 km) or 10 times the height of the building or 
other structure, whichever is greater. Possible 
channeling effects or increased velocity pressures 
due to the building or structure being located in the 
wake of adjacent buildings shall be taken into 
account. 



2. Exposure B. Urban and suburban areas, wooded 
areas, or other terrain with numerous closely spaced 
obstructions having the size of single-family dwell- 
ings or larger. Exposure B shall be assumed unless 
the site meets the definition of another type expo- 
sure. 

3. Exposure C. Open terrain with scattered obstruc- 
tions, including surface undulations or other irreg- 
ularities, having heights generally less than 30 feet 
(9144 mm) extending more than 1,500 feet (457 
m) from the building site in any quadrant. This 
exposure shall also apply to any building located 
within Exposure B type terrain where the building 
is directly adjacent to open areas of Exposure C 
type terrain in any quadrant for a distance of more 
than 600 feet (183 m). This category includes flat 
open country, grasslands and shorelines in hurri- 
cane prone regions. 

4. Exposure D. Flat, unobstructed areas exposed to 
wind flowing over open water (excluding shore- 
lines in hurricane prone regions) for a distance of 
at least 1 mile (1 .61 km). Shorelines in Exposure D 
include inland waterways, the Great Lakes and 
coastal areas of California, Oregon, Washington 
and Alaska. This exposure shall apply only to 
those buildings and other structures exposed to the 
wind coming from over the water. Exposure D 
extends inland from the shoreline a distance of 
1,500 feet (457 m) or 10 times the height of the 
building or structure, whichever is greater. 

R301.2.2 Seismic provisions. The seismic provisions of this 
code shall apply to buildings constructed in Seismic Design 
Categories C, Do, Di and Dj, as determined in accordance 
with this section. Buildings in Seismic Design Category E 
shall be designed in accordance with the International Build- 
ing Code, except when the seismic design category is reclas- 
sified to a lower seismic design category in accordance with 
Section R301. 2.2.1. 

Exception: Detached one- and two-family dwellings 
located in Seismic Design Category C are exempt from 
the seismic requirements of this code. 

The weight and irregularity limitations of Section 
R301.2.2.2 shall apply to buildings in all seismic design 
categories regulated by the seismic provisions of this code. 
Buildings in Seismic Design Category C shall be con- 
structed in accordance with the additional requirements of 
Section R301.2.2.3. Buildings in Seismic Design Catego- 
ries Dq, Dj and D2 shall be constructed in accordance with 
the additional requirements of Section R301. 2.2.4 



TABLE R301 2 1 3 
EQUIVALENT BASIC WIND SPEEDS^ 



3-second gust, ¥3^ 


85 


90 


100 


105 


110 


120 


125 


130 


140 


145 


150 


160 


170 


Fastest mile, V^^ 


71 


76 


85 


90 


95 


104 


109 


114 


123 


128 


133 


142 


152 



For SI: 1 mile per hour = 0.447 m/s. 
a. Linear interpolation is permitted. 



42 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



BUILDING PLANNING 



R301.2.2.1 Determination of seismic design category. 

Buildings shall be assigned a seismic design category in 
accordance with Figure 301.2(2). 

R301.2.2.1.1 Alternate determination of seismic 
design category. The Seismic Design Categories and 
corresponding Short Period Design Spectral 
Response Accelerations, Sds shown in Figure 
R301 .2(2) are based on soil Site Class D, as defined in 
Section 1615.1.1 of the International Building Code. 
If soil conditions are other than Site Class D, the Short 
Period Design Spectral Response Acceleration, S^s, 
for a site can be determined according to Section 
1615.1 of the International Building Code. The value 
of Sds determined according to Section 1615.1 of the 
International Building Code is permitted to be used to 
set the seismic design category according to Table 
R301.2.2.1.1, and to interpolate between values in 
Tables R602.10.1, R603.7, and other seismic design 
requirements of this code. 

TABLE R301 .2.2.1 .1 
SEISMIC DESIGN CATEGORY DETERMINATION 



CALCULATED S^s 


SEISMIC DESIGN 
CATEGORY 


S OS < 0.11% 


A 


0.17g<5o5<0.33g 


B 


0.33g<5o5<0.50g 


C 


0.50g < Sas < 0.67g 


Do 


0.67g<5o5<0.83g 


Di 


0.83g<So5<1.17g 


D2 


1.17g<5^, 


E 



R301.2.2.1.2 Alternative determination of Seismic 
Design Category E. Buildings located in Seismic 
Design Category E in accordance with Figure 
R301.2(2) are permitted to be reclassified as being in 
Seismic Design Category D2 provided one of the fol- 
lowing is done: 

1. A more detailed evaluation of the seismic 
design category is made in accordance with the 
provisions and maps of the International Build- 
ing Code. Buildings located in Seismic Design 
Category E per Table R301 .2.2. 1 . 1 , but located 
in Seismic Design Category D per the Interna- 
tional Building Code, may be designed using 
the Seismic Design Category D2 requirements 
of this code. 

2. Buildings located in Seismic Design Category 
E that conform to the following additional 
restrictions are permitted to be constructed in 
accordance with the provisions for Seismic 
Design Category Dj of this code: 

2. 1 . All exterior shear wall lines or braced 
wall panels are in one plane vertically 
from the foundation to the uppermost 
story. 



2.2. Floors shall not cantilever past the exte- 
rior walls. 

2.3. The building is within all of the require- 
ments of SectionR301.2.2.2.2 for being 
considered as regular. 

R301.2.2.2 Seismic limitations. The following limita- 
tions apply to buildings in all Seismic Design Categories 
regulated by the seismic provisions of this code. 

R301.2.2.2.1 Weights of materials. Average dead 
loads shall not exceed 15 pounds per square foot (720 
Pa) for the combined roof and ceiling assemblies (on a 
horizontal projection) or 10 pounds per square foot 
(480 Pa) for floor assemblies, except as further lim- 
ited by Section R30 1.2.2. Dead loads for walls above 
grade shall not exceed: 

1. Fifteen pounds per square foot (720 Pa) for 
exterior light-frame wood walls. 

2. Fourteen pounds per square foot (670 Pa) for 
exterior light-frame cold-formed steel walls. 

3 . Ten pounds per square foot (480 Pa) for interior 
light-frame wood walls. 

4. Five pounds per square foot (240 Pa) for inte- 
rior light-frame cold-formed steel walls. 

5. Eighty pounds per square foot (3830 Pa) for 
8-inch-thick (203 mm) masonry walls. 

6. Eighty-five pounds per square foot (4070 Pa) 
for 6-inch-thick (152 mm) concrete walls. 

Exceptions: 

1 . Roof and ceiling dead loads not exceeding 
25 pounds per square foot (11 90 Pa) shall be 
permitted provided the wall bracing 
amounts in Chapter 6 are increased in accor- 
dance with Table R301. 2.2.2.1. 

2. Light-frame walls with stone or masonry 
veneer shall be permitted in accordance with 
the provisions of Sections R702.1 andR703. 

3. Fireplaces and chimneys shall be permitted 
in accordance with Chapter 10. 

TABLE R301. 2.2.2.1 

WALL BRACING ADJUSTMENT FACTORS BY 

ROOF COVERING DEAD LOAD^ 



WALL SUPPORTING 


ROOF/CEILING 
DEAD LOAD 


ROOF/CEILING 
DEAD LOAD 


15 psf orless 


25 psf 


Roof only 


1.0 


1.2 


Roof plus one story 


1.0 


1.1 



For SI: 1 pound per square foot = 0.049 kPa. 
a. Linear interpolation shall be permitted. 

R301.2.2.2.2 Irregular buildings. Prescriptive con- 
struction as regulated by this code shall not be used 
for irregular structures located in Seismic Design Cat- 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



43 



BUILDING PLANNING 



egories C, Dq, Dj and Dj. Irregular portions of struc- 
tures shall be designed in accordance with accepted 
engineering practice to the extent the irregular fea- 
tures affect the performance of the remaining struc- 
tural system. When the forces associated with the 
irregularity are resisted by a structural system 
designed in accordance with accepted engineering 
practice, design of the remainder of the building shall 
be permitted using the provisions of this code. A 
building or portion of a building shall be considered 
to be irregular when one or more of the following con- 
ditions occur: 

1 . When exterior shear wall lines or braced wall 
panels are not in one plane vertically from the 
foundation to the uppermost story in which they 
are required. 

Exception: For wood Hght- frame construc- 
tion, floors with cantilevers or setbacks not 
exceeding four times the nominal depth of 
the wood floor joists are permitted to sup- 
port braced wall panels that are out of plane 
with braced wall panels below provided that: 

1 . Floor joists are nominal 2 inches by 10 
inches (5 1 mm by 254 mm) or larger 
and spaced not more than 16 inches 
(406 mm) on center. 

2. The ratio of the back span to the canti- 
lever is at least 2 to 1 . 

3. Floor joists at ends of braced wall pan- 
els are doubled. 

4. For wood-frame construction, a con- 
tinuous rim joist is connected to ends 
of all cantilever joists. When spliced, 
the rim joists shall be spliced using a 
galvanized metal tie not less than 
0.058 inch (1 .5 mm) (16 gage) and 1 ^1^ 
inches (38 mm) wide fastened with six 
16d nails on each side of the splice or a 
block of the same size as the rim joist 
of sufficient length to fit securely 
between the joist space at which the 
splice occurs fastened with eight 16d 
nails on each side of the splice; and 

5 . Gravity loads carried at the end of can- 
tilevered joists are limited to uniform 
wall and roof loads and the reactions 
from headers having a span of 8 feet 
(2438 mm) or less. 

2. When a section of floor or roof is not laterally 
supported by shear walls or braced wall lines on 
all edges. 

Exception: Portions of floors that do not 
support shear walls or braced wall panels 
above, or roofs, shall be permitted to extend 
no more than 6 feet (1829 mm) beyond a 
shear wall or braced wall line. 



3. When the end of a braced wall panel occurs 
over an opening in the wall below and ends at a 
horizontal distance greater than 1 foot (305 
mm) from the edge of the opening. This provi- 
sion is applicable to shear walls and braced wall 
panels offset in plane and to braced wall panels 
offset out of plane as permitted by the exception 
to Item 1 above. 

Exception: For wood light-frame wall con- 
struction, one end of a braced wall panel 
shall be permitted to extend more than 1 foot 
(305 mm) over an opening not more than 8 
feet (2438 mm) wide in the wall below pro- 
vided that the opening includes a header in 
accordance with the following: 

1. The building width, loading condition 
and framing member species limitations 
of Table R502.5(l) shall apply and 

2. Not less than one 2X 12 or two 2x 10 
for an opening not more than 4 feet 
(1219 mm) wide or 

3. Not less than two 2x12 or three 2x10 
for an opening not more than 6 feet 
(1829 mm) wide or 

4. Not less than three 2 X 1 2 or four 2x10 
for an opening not more than 8 feet 
(2438 mm) wide and 

5. The entire length of the braced wall 
panel does not occur over an opening 
in the wall below. 

4. When an opening in a floor or roof exceeds the 
lesser of 12 feet (3657 mm) or 50 percent of the 
least floor or roof dimension. 

5 . When portions of a floor level are vertically off- 
set. 

Exceptions: 

1 . Framing supported directly by contin- 
uous foundations at the perimeter of 
the building. 

2. For wood light-frame construction, 
floors shall be permitted to be verti- 
cally offset when the floor framing is 
lapped or tied together as required by 
Section R502.6.1. 

6. When shear walls and braced wall lines do not 
occur in two perpendicular directions. 

7. When stories above-grade partially or com- 
pletely braced by wood wall framing in accor- 
dance with Section R602 or steel wall framing 
in accordance with Section R603 include 
masonry or concrete construction. 

Exception: Fireplaces, chimneys and 
masonry veneer as permitted by this code. 



44 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



BUILDING PLANNING 



I 



When this irregularity applies, the entire 
story shall be designed in accordance with 
accepted engineering practice. 

R301.2.2.3 Seismic Design Category C. Structures 
assigned to Seismic Design Category C shall conform to 
the requirements of this section. 

R301.2.2.3.1 Stone and masonry veneer. Stone and 
masonry veneer shall comply with the requirements 
of Sections R702.1 and R703. 

R301.2.2.3.2 Masonry construction. Masonry con- 
struction shall comply with the requirements of Sec- 
tion R606.il. 2. 

R301.2.2.3.3 Concrete construction. Concrete con- 
struction shall comply with the requirements of Sec- 
tion R611 orR612. 

R301.2.2.4 Seismic Design Categories Dq, D^ and Dj. 

Structures assigned to Seismic Design Categories Dq, Di 
and D2 shall conform to the requirements for Seismic 
Design Category C and the additional requirements of 
this section. 

R301. 2.2.4.1 Height limitations. Wood framed 
buildings shall be limited to three stories above grade 
or the limits given in Table R602.10.1. Cold-formed 
steel framed buildings shall be limited to two stories 
above grade in accordance with COFS/PM. Mezza- 
nines as defined in Section 202 shall not be consid- 
ered as stories. 

R301. 2.2.4.2 Stone and masonry veneer. Stone and 
masonry veneer shall comply with the requirements 
of Sections R702.1 and R703. 

R301. 2.2.4.3 Masonry construction. Masonry con- 
struction in Seismic Design Categories Dq and Dj 
shall comply with the requirements of Section 
R606.11.3. Masonry construction in Seismic Design 
Category Dj shall comply with the requirements of 
Section R606. 11.4. 

R301.2.2.4.4 Concrete construction. Buildings with 
above-grade concrete walls shall be in accordance 
with Section R611, R612, or designed in accordance 
with accepted engineering practice. 

R301.2.2.4.5 Cold-formed steel framing in Seismic 
Design Categories Do, Dj and Dj. In Seismic Design 
Categories Dq, D, and D2 in addition to the require- 
ments of this code, cold-formed steel framing shall 
comply with the requirements of COFS/PM. 

R301.2.3 Snow loads. Wood framed construction, cold- 
formed steel framed construction and masonry and concrete 
construction in regions with ground snow loads 70 pounds 
per square foot (3.35 kPa) or less, shall be in accordance 
with Chapters 5, 6 and 8. Buildings in regions with ground 
snow loads greater than 70 pounds per square foot (3.35 
kPa) shall be designed in accordance with accepted engi- 
neering practice. 

R301.2.4 Floodplain construction. Buildings and struc- 
tures constructed in whole or in part in flood hazard areas 



(including A or V Zones) as estabhshed in Table R301 .2(1) 
shall be designed and constructed in accordance with Sec- I 
tion R324. | 

Exception: Buildings and structures located in whole or 
in part in identified floodways as established in Table 
R301.2(l) shall be designed and constructed as stipu- 
lated in the International Building Code. 

R301.3 Story height. Buildings constructed in accordance 
with these provisions shall be limited to story heights of not 
more than the following: 

1 . For wood wall framing, the laterally unsupported bear- 
ing wall stud height permitted by Table R602.3(5) plus a 
height of floor framing not to exceed 16 inches. 

Exception: For wood framed wall buildings with 
bracing in accordance with Table R602.10.1 , the wall 
stud clear height used to determine the maximum per- 
mitted story height may be increased to 12 feet with- 
out requiring an engineered design for the building 
wind and seismic force resisting systems provided 
that the length of bracing required by Table 
R602.10.1 is increased by mulfiplying by a factor of 
1 .20. Wall studs are still subject to the requirements of 
this section. 

2. For steel wall framing, a stud height of 10 feet, plus a 
height of floor framing not to exceed 16 inches. 

3. For masonry walls, a maximum bearing wall clear height 
of 12 feet plus a height of floor framing not to exceed 16 
inches. 

Exception: An additional 8 feet is permitted for gable 
end walls. 

4. For insulating concrete form walls, the maximum bear- 
ing wall height per story as permitted by Section 611 
tables plus a height of floor framing not to exceed 16 
inches. 

Individual walls or walls studs shall be permitted to exceed 
these limits as permitted by Chapter 6 provisions, provided 
story heights are not exceeded. An engineered design shall be 
provided for the wall or wall framing members when they 
exceed the limits of Chapter 6. Where the story height limits are 
exceeded, an engineered design shall be provided in accor- 
dance with the International Building Code for the overall 
wind and seismic force resisting systems. 

R301.4 Dead load. The actual weights of materials and con- 
struction shall be used for determining dead load with consid- 
eration for the dead load of fixed service equipment. 

R301.5 Live load. The minimum uniformly distributed live 
load shall be as provided in Table R301.5. 

R301.6 Roof load. The roof shall be designed for the live load 
indicated in Table R301.6 or the snow load indicated in Table 
R301.2(l), whichever is greater. 

R301.7 Deflection. The allowable deflection of any structural 
member under the live load listed in Sections R301.5 and 
R301.6 shall not exceed the values in Table R301.7. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



45 



BUILDING PLANNING 



TABLER301.5 

MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS 

(in pounds per square foot) 



TABLER301.6 

MINIMUM ROOF LIVE LOADS IN POUNDS-FORCE 

PER SQUARE FOOT OF HORIZONTAL PROJECTION 



USE 


LIVE LOAD 


Attics with limited storage'^' §' ^ 


20 


Attics without storage"^ 


10 


Decks^ 


40 


Exterior balconies 


60 


Fire escapes 


40 


Guardrails and handrails'* 


200' 


Guardrails in-fill components^ 


50' 


Passenger vehicle garages'* 


50^ 


Rooms other than sleeping rooms 


40 


Sleeping rooms 


30 


Stairs 


40^ 



For SI: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm^, 
1 pound = 445 N. 

a. Elevated garage floors shall be capable of supporting a 2,000-pound load 
applied over a 20-square-inch area. 

b. Attics without storage are those where the maximum clear height between 
joist and rafter is less than 42 inches, or where there are not two or more adja- 
cent trusses with the same web configuration capable of containing a rectan- 
gle 42 inches high by 2 feet wide, or greater, located within the plane of the 
truss. For attics without storage, this live load need not be assumed to act 
concurrently with any other live load requirements. 

c. Individual stair treads shall be designed for the uniformly distributed live 
load or a 300-pound concentrated load acting over an area of 4 square inches, 
whichever produces the greater stresses. 

d. A single concentrated load applied in any direction at any point along the top. 

e. See Section R502.2.1 for decks attached to exterior walls. 

f. Guard in-fill components (all those except the handrail), balusters and panel 
fillers shall be designed to withstand a horizontally applied normal load of 50 
pounds on an area equal to 1 square foot. This load need not be assumed to act 
concurrently with any other live load requirement. 

g. For attics with limited storage and constructed with trusses, this live load 
need be applied only to those portions of the bottom chord where there are 
two or more adjacent trusses with the same web configuration capable of 
containing a rectangle 42 inches high or greater by 2 feet wide or greater, 
located within the plane of the truss. The rectangle shall fit between the top of 
the bottom chord and the bottom of any other truss member, provided that 
each of the following criteria is met: 

1 . The attic area is accessible by a pull-down stairway or framed opening 
in accordance with Section R807.1; and 

2. The truss has a bottom chord pitch less than 2: 12. 

h. Attic spaces served by a fixed stair shall be designed to support the minimum 
live load specified for sleeping rooms. 

i. Glazing used in handrail assemblies and guards shall be designed with a 
safety factor of 4. The safety factor shall be applied to each of the concen- 
trated loads apphed to the top of the rail, and to the load on the in-fill compo- 
nents. These loads shall be determined independent of one another, and loads 
are assumed not to occur with any other live load. 



ROOF SLOPE 


TRIBUTARY LOADED AREA IN 
SQUARE FEET FOR ANY 
STRUCTURAL MEMBER 


to 200 


201 to 600 


Over 600 


Flat or rise less than 4 inches per 
foot (1:3) 


20 


16 


12 


Rise 4 inches per foot (1:3) to 
less than 12 inches per foot (1:1) 


16 


14 


12 


Rise 12 inches per foot (1:1) 
and greater 


12 


12 


12 



For SI: 1 square foot = 0.0929 m^, 1 pound per square foot = 0.0479 kPa, 
1 inch per foot = 83.3 mm/m. 



TABLER301.7 
ALLOWABLE DEFLECTION OF STRUCTURAL MEMBERS^ 



STRUCTURAL MEMBER 


ALLOWABLE 
DEFLECTION 


Rafters having slopes greater than 3/12 with no 
finished ceiling attached to rafters 


L/180 


Interior walls and partitions 


H/180 


Floors and plastered ceilings 


L/360 


AH other structural members 


L/240 


Exterior walls with plaster or stucco finish 


H/360 


Exterior walls — wind loads^ with brittle finishes 


L/240 


Exterior walls — wind loads^ with flexible 
finishes 


L/120 



Note: L = span length, H = span height. 

a. The wind load shall be permitted to be taken as 0.7 times the Component and 
Cladding loads for the purpose of the determining deflection limits herein. 

b. For cantilever members, L shall be taken as twice the length of the cantilever. 

c. For aluminum structural members or panels used in roofs or walls of sun- 
room additions or patio covers, not supporting edge of glass or sandwich 
panels, the total load deflection shall not exceed L /60. For sandwich panels 
used in roofs or walls of sunroom additions or patio covers, the total load 
deflection shall not exceed L/120. 

R301.8 Nominal sizes. For the purposes of this code, where 
dimensions of lumber are specified, they shall be deemed to be 
nominal dimensions unless specifically designated as actual 
dimensions. 



46 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



BUILDING PLANNING 



SECTION R302 
EXTERIOR WALL LOCATION 

R302.1 Exterior walls. Construction, projections, openings 
and penetrations of exterior walls of dwellings and accessory 
buildings shall comply with Table R302.1. These provisions 
shall not apply to walls, projections, openings or penetrations 
in walls that are perpendicular to the line used to determine the 
fire separation distance. Projections beyond the exterior wall 
shall not extend more than 12 inches (305 mm) into the areas 
where openings are prohibited. 

Exceptions: 

1. Detached tool sheds and storage sheds, playhouses 
and similar structures exempted from permits are not 
required to provide wall protection based on location 
on the lot. Projections beyond the exterior wall shall 
not extend over the lot line. 

2. Detached garages accessory to a dwelhng located 
within 2 feet (610 mm) of a lot line are permitted to 
have roof eave projections not exceeding 4 inches 
(102 mm). 

3. Foundation vents installed in compliance with this 
code are permitted. 



SECTION R303 
LIGHT, VENTILATION AND HEATING 

R303.1 Habitable rooms. All habitable rooms shall have an 
aggregate glazing area of not less than 8 percent of the floor 
area of such rooms. Natural ventilation shall be through win- 
dows, doors, louvers or other approved openings to the outdoor 
air. Such openings shall be provided with ready access or shall 
otherwise be readily controllable by the building occupants. 
The minimum openable area to the outdoors shall be 4 percent 
of the floor area being ventilated. 

Exceptions: 

1. The glazed areas need not be openable where the 
opening is not required by Section R310 and an 
approved mechanical ventilation system capable of 
producing 0.35 air change per hour in the room is 



installed or a whole-house mechanical ventilation 
system is installed capable of supplying outdoor ven- 
tilation air of 15 cubic feet per minute (cfm) (78 L/s) 
per occupant computed on the basis of two occupants 
for the first bedroom and one occupant for each addi- 
tional bedroom. 

2. The glazed areas need not be installed in rooms where 
Exception 1 above is satisfied and artificial light is pro- 
vided capable of producing an average illumination of 
6 footcandles (65 lux) over the area of the room at a 
height of 30 inches (762 mm) above the floor level. 

3 . Use of sunroom additions and patio covers, as defined in 
Section R202, shall be permitted for natural ventilation 
if in excess of 40 percent of the exterior sunroom walls 
are open, or are enclosed only by insect screening. 

R303.2 Adjoining rooms. For the purpose of determining 
light and ventilation requirements, any room shall be consid- 
ered as a portion of an adjoining room when at least one-half of 
the area of the common wall is open and unobstructed and pro- 
vides an opening of not less than one-tenth of the floor area of 
the interior room but not less than 25 square feet (2.3 m^). 

Exception: Openings required for light and/or ventilation 
shall be permitted to open into a thermally isolated sunroom 
addition or patio cover, provided that there is an openable 
area between the adjoining room and the sunroom addition 
or patio cover of not less than one-tenth of the floor area of 
the interior room but not less than 20 square feet (2 m^). The 
minimum openable area to the outdoors shall be based upon 
the total floor area being ventilated. 

R303.3 Bathrooms. Bathrooms, water closet compartments 
and other similar rooms shall be provided with aggregate glaz- 
ing area in windows of not less than 3 square feet (0.3 m^), 
one-half of which must be openable. 

Exception: The glazed areas shall not be required where arti- 
ficial light and a mechanical ventilation system are provided. 
The minimum ventilation rates shall be 50 cubic feet per min- 
ute (24 L/s) for intermittent ventilation or 20 cubic feet per 
minute (10 L/s) for continuous ventilation. Ventilation air 
from the space shall be exhausted directly to the outside. 



TABLE R302.1 
EXTERIOR WALLS 



EXTERIOR WALL ELEMENT 


MINIMUM 
FIRE-RESISTANCE RATING 


MINIMUM FIRE 
SEPARATION DISTANCE 


Walls 


(Fire-resistance rated) 


1 hour with exposure from both sides 


Ofeet 


(Not fire-resistance rated) 


hours 


5 feet 


Projections 


(Fire-resistance rated) 


1 hour on the underside 


2 feet 


(Not fire-resistance rated) 


hours 


5 feet 


Openings 


Not allowed 


N/A 


< 3 feet 


25% Maximum of Wall Area 


hours 


3 feet 


Unlimited 


hours 


5 feet 


Penetrations 


All 


Comply with Section R317.3 


< 5 feet 


None required 


5 feet 



N/A = Not Applicable. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



47 



BUILDING PLANNING 



R303.4 Opening location. Outdoor intake and exhaust open- 
ings shall be located in accordance with Sections R303.4. 1 and 
R303.4.2. 

R303.4.1 Intake openings. Mechanical and gravity out- 
door air intake openings shall be located a minimum of 10 
feet (3048 mm) from any hazardous or noxious contami- 
nant, such as vents, chimneys, plumbing vents, streets, 
alleys, parking lots and loading docks, except as otherwise 
specified in this code. Where a source of contaminant is 
located within 10 feet (3048 mm) of an intake opening, such 
opening shall be located a minimum of 2 feet (610 mm) 
below the contaminant source. 

For the purpose of this section, the exhaust from dwelling 
unit toilet rooms, bathrooms and kitchens shall not be con- 
sidered as hazardous or noxious. 

R303.4.2 Exhaust openings. Outside exhaust openings 
shall be located so as not to create a nuisance. Exhaust air 
shall not be directed onto walkways. 

R303.5 Outside opening protection. Air exhaust and intake 
openings that terminate outdoors shall be protected with 
corrosion-resistant screens, louvers or grilles having a mini- 
mum opening size of V4 inch (6 mm) and a maximum opening 
size of V2 inch (13 mm), in any dimension. Openings shall be 
protected against local weather conditions. Outdoor air exhaust 
and intake openings shall meet the provisions for exterior wall 
opening protectives in accordance with this code. 

R303.6 Stairway illumination. All interior and exterior stair- 
ways shall be provided with a means to illuminate the stairs, 
including the landings and treads. Interior stairways shall be 
provided with an artificial light source located in the immediate 
vicinity of each landing of the stairway. For interior stairs the 
artificial light sources shall be capable of illuminating treads 
and landings to levels not less than 1 foot-candle (11 lux) mea- 
sured at the center of treads and landings. Exterior stairways 
shall be provided with an artificial light source located in the 
immediate vicinity of the top landing of the stairway. Exterior 
stairways providing access to a basement from the outside 
grade level shall be provided with an artificial light source 
located in the immediate vicinity of the bottom landing of the 
stairway. 

Exception: An artificial light source is not required at the 
top and bottom landing, provided an artificial light source is 
located directly over each stairway section. 

R303.6.1 Light activation. Where lighting outlets are 
installed in interior stairways, there shall be a wall switch at 
each floor level to control the lighting outlet where the stair- 
way has six or more risers. The illumination of exterior 
stairways shall be controlled from inside the dwelling unit. 

Exception: Lights that are continuously illuminated or 
automatically controlled. 

R303.7 Required glazed openings. Required glazed openings 
shall open directly onto a street or public alley, or a yard or 
court located on the same lot as the building. 

R303.7.1 Roofed porches. Required glazed openings may 
face into a roofed porch where the porch abuts a street, yard 
or court and the longer side of the porch is at least 65 percent 



48 



open and unobstructed and the ceiling height is not less than 
7 feet (2134 mm). 

R303.7.2 Sunroom additions. Required glazed openings 
shall be permitted to open into sunroom additions or patio 
covers that abut a street, yard or court if in excess of 40 per- 
cent of the exterior sunroom walls are open, or are enclosed 
only by insect screening, and the ceiling height of the sun- 
room is not less than 7 feet (2134 mm). 

R303.8 Required heating. When the winter design tempera- 
ture in Table R301.2(l) is below 60°F (16°C), every dwelling 
unit shall be provided with heating facilities capable of main- 
taining a minimum room temperature of 68°F (20°C) at a point 
3 feet (914 mm) above the floor and 2 feet (610 mm) from exte- 
rior walls in all habitable rooms at the design temperature. The 
installation of one or more portable space heaters shall not be 
used to achieve compliance with this section. 



SECTION R304 
MINIMUM ROOM AREAS 

R304.1 Minimum area. Every dwelling unit shall have at least 
one habitable room that shall have not less than 120 square feet 
(11 m^) of gross floor area. 

R304.2 Other rooms. Other habitable rooms shall have a floor 
area of not less than 70 square feet (6.5 m^). 

Exception: Kitchens. 

R304.3 Minimum dimensions. Habitable rooms shall not be 
less than 7 feet (2134 mm) in any horizontal dimension. 

Exception: Kitchens. 

R304.4 Height effect on room area. Portions of a room with a 
sloping ceiling measuring less than 5 feet (1524 mm) or a 
furred ceiling measuring less than 7 feet (2134 mm) from the 
finished floor to the finished ceiling shall not be considered as 
contributing to the minimum required habitable area for that 
room. 



SECTION R305 
CEILING HEIGHT 

R305.1 Minimum height. Habitable rooms, hallways, corri- 
dors, bathrooms, toilet rooms, laundry rooms and basements 
shall have a ceiling height of not less than 7 feet (2134 mm). 
The required height shall be measured from the finish floor to 
the lowest projection from the ceiling. 

Exceptions: 

1. Beams and girders spaced not less than 4 feet (1219 
mm) on center may project not more than 6 inches 
(152 mm) below the required ceiling height. 

2. Ceilings in basements without habitable spaces may 
project to within 6 feet, 8 inches (2032 ram) of the fin- 
ished floor; and beams, girders, ducts or other 
obstructions may project to within 6 feet 4 inches 
(1931 mm) of the finished floor. 

3. For rooms with sloped ceilings, at least 50 percent of 
the required floor area of the room must have a ceiling 

2006 INTERNATIONAL RESIDENTIAL CODE® 



BUILDING PLANNING 



height of at least 7 feet (2134 mm) and no portion of 
the required floor area may have a ceiling height of 
less than 5 feet (1524 mm). 

Bathrooms shall have a minimum ceiling height of 6 
feet 8 inches (2036 mm) over the fixture and at the 
front clearance area for fixtures as shown in Figure 
R307. 1 . A shower or tub equipped with a showerhead 
shall have a minimum ceiling height of 6 feet 8 inches 
(2036 mm) above a minimum area 30 inches (762 
mm) by 30 inches (762 mm) at the showerhead. 



R306.2 Kitchen. Each dwelling unit shall be provided with a 
kitchen area and every kitchen area shall be provided with a 
sink. 

R306.3 Sewage disposal. All plumbing fixtures shall be con- 
nected to a sanitary sewer or to an approved private sewage dis- 
posal system. 

R306.4 Water supply to fixtures. All plumbing fixtures shall 
be connected to an approved water supply. Kitchen sinks, lava- 
tories, bathtubs, showers, bidets, laundry tubs and washing 
machine outlets shall be provided with hot and cold water. 



SECTION R306 
SANITATION 

R306.1 Toilet facilities. Every dwelling unit shall be provided 
with a water closet, lavatory, and a bathtub or shower. 



SECTION R307 
TOILET, BATH AND SHOWER SPACES 

R307.1 Space required. Fixtures shall be spaced as per Figure 
R307.1. 

R307.2 Bathtub and shower spaces. Bathtub and shower 
floors and walls above bathtubs with installed shower heads 



/WALL 



/WALL (WALL / 

■4(N. / -^|<-4IN. / 2IN. -^|<- / 




WALL 



WALLi 



LAVATORIES 




24 IN. CLEARANCE IN 
FRONT OF OPENING 



SHOWER 



15 IN. 



-U-^ /WALL 



WATER CLOSET^ 
OR BIDET 



15IN. 



ti 



\ /WALL 



TUB 



21 (N. 
CLEARANCE 



21 IN. 
CLEARANCE 

1 



WALL 



For SI: 1 inch = 25.4 mm. 



WATER CLOSETS 



FIGURE R307.1 
MINIMUM FIXTURE CLEARANCES 




WALL 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



49 



BUILDING PLANNING 



and in shower compartments shall be finished with a 
nonabsorbent surface. Such wall surfaces shall extend to a 
height of not less than 6 feet (1829 mm) above the floor. 



SECTION R308 
GLAZING 

R308.1 Identification. Except as indicated in Section R308. 1 . 1 
each pane of glazing installed in hazardous locations as defined 
in Section R308.4 shall be provided with a manufacturer's desig- 
nation specifying who appUed the designation, designating the 
type of glass and the safety glazing standard with which it com- 
plies, which is visible in the final installation. The designation 
shall be acid etched, sandblasted, ceramic-fired, laser etched, 
embossed, or be of a type which once applied cannot be removed 
without being destroyed. A label shall be permitted in heu of the 
manufacturer's designation. 

Exceptions: 

1. For other than tempered glass, manufacturer's desig- 
nations are not required provided the building official 
approves the use of a certificate, affidavit or other evi- 
dence confirming compliance with this code. 

2. Tempered spandrel glass is permitted to be identified 
by the manufacturer with a removable paper designa- 
tion. 

R308.1.1 Identification of multipane assemblies. Multipane 
assembhes having individual panes not exceeding 1 square 
foot (0.09 m^) in exposed area shall have at least one pane in 
the assembly identified in accordance with Section R308.1. 
All other panes in the assembly shall be labeled "16 CFR 
1201." 

R308.2 Louvered windows or jalousies. Regular, float, wired 
or patterned glass in jalousies and louvered windows shall be 
no thinner than nominal Vis inch (5 mm) and no longer than 48 
inches (1219 mm). Exposed glass edges shall be smooth. 

R308.2.1 Wired glass prohibited. Wired glass with wire 
exposed on longitudinal edges shall not be used in jalousies 
or louvered windows. 

R308.3 Human impact loads. Individual glazed areas, includ- 
ing glass mirrors in hazardous locations such as those indicated 
as defined in Section R308.4, shall pass the test requirements of 
CPSC 16 CFR, Part 1201. Glazing shall comply with CPSC 16 



CFR, Part 1201 criteria for Category I or Category II as indi- 
cated in Table R308.3. 

Exception: Louvered windows and jalousies shall comply 
with Section R308.2. 

R308.4 Hazardous locations. The following shall be consid- 
ered specific hazardous locations for the purposes of glazing: 

1. Glazing in swinging doors except jalousies. 

2. Glazing in fixed and sliding panels of sliding door 
assemblies and panels in sliding and bifold closet door 
assemblies. 

3. Glazing in storm doors. 

4. Glazing in all unframed swinging doors. 

5. Glazing in doors and enclosures for hot tubs, whirl- 
pools, saunas, steam rooms, bathtubs and showers. 
Glazing in any part of a building wall enclosing these 
compartments where the bottom exposed edge of the 
glazing is less than 60 inches (1524 mm) measured ver- 
tically above any standing or walking surface. 

6. Glazing, in an individual fixed or operable panel adja- 
cent to a door where the nearest vertical edge is within a 
24-inch (610 mm) arc of the door in a closed position 
and whose bottom edge is less than 60 inches (1524 
mm) above the floor or walking surface. 

7. Glazing in an individual fixed or operable panel, other 
than those locations described in Items 5 and 6 above, 
that meets all of the following conditions: 

7.1. Exposed area of an individual pane larger than 
9 square feet (0.836 m^). 

7.2. Bottom edge less than 18 inches (457 mm) 
above the floor. 

7.3. Top edge more than 36 inches (914 mm) 
above the floor. 

7.4. One or more walking surfaces within 36 
inches (914 mm) horizontally of the glazing. 

8. All glazing in railings regardless of an area or height 
above a walking surface. Included are structural balus- 
ter panels and nonstructural infill panels. 

9. Glazing in walls and fences enclosing indoor and out- 
door swimming pools, hot tubs and spas where the bot- 
tom edge of the glazing is less than 60 inches (1524 



TABLE R308.3 
MINIMUM CATEGORY CLASSIFICATION OF GLAZING 













GLAZING IN DOORS 










GLAZED PANELS 


GLAZED PANELS 


AND ENCLOSURES 






GLAZING IN STORM 




REGULATED BY 


REGULATED BY 


REGULATED BY 




EXPOSED SURFACE 


OR COMBINATION 


GLAZING IN 


ITEM 7 OF SECTION 


ITEM 6 OF SECTION 


ITEM 5 OF SECTION 


SLIDING GLASS 


AREA OF ONE SIDE 


DOORS 


DOORS 


R308.4 


R308.4 


R308.4 


DOORS PATIO TYPE 


OF ONE LITE 


(Category Class) 


(Category Class) 


(Category Class) 


(Category Class) 


(Category Class) 


(Category Class) 


9 sq ft or less 


I 


I 


NR 


I 


II 


II 


More than 9 sq ft 


II 


II 


II 


II 


II 


II 



For SI: 1 square foot = 0.0929 ml 
NR means "No Requirement." 



50 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANNING 



mm) above a walking surface and within 60 inches 
(1524 mm) horizontally of the water's edge. This shall 
apply to single glazing and all panes in multiple glaz- 
ing. 

10. Glazing adjacent to stairways, landings and ramps 
within 36 inches (914 mm) horizontally of a walking 
surface when the exposed surface of the glass is less 
than 60 inches (1524 mm) above the plane of the adja- 
cent walking surface. 

11. Glazing adjacent to stairways within 60 inches (1524 
mm) horizontally of the bottom tread of a stairway in 
any direction when the exposed surface of the glass is 
less than 60 inches (1524 mm) above the nose of the 
tread. 

Exception: The following products, materials and uses are 
exempt from the above hazardous locations: 

1 . Openings in doors through which a 3-inch (76 mm) 
sphere is unable to pass. 

2. Decorative glass in Items 1, 6 or 7. 

3. Glazing in Section R308.4, Item 6, when there is an 
intervening wall or other permanent barrier between 
the door and the glazing. 

4. Glazing in Section R308.4, Item 6, in walls perpen- 
dicular to the plane of the door in a closed position, 
other than the wall toward which the door swings 
when opened, or where access through the door is to 
a closet or storage area 3 feet (914 mm) or less in 
depth. Glazing in these applications shall comply 
with Section R308.4, Item 7. 

5. Glazing in Section R308.4, Items 7 and 10, when a 
protective bar is installed on the accessible side(s) of 
the glazing 36 inches ± 2 inches (914 mm ±51 mm) 
above the floor. The bar shall be capable of with- 
standing a horizontal load of 50 pounds per linear 
foot (730 N/m) without contacting the glass and be a 
minimum of 1 Vj inches (38 mm) in height. 

6. Outboard panes in insulating glass units and other 
multiple glazed panels in Section R308.4, Item 7, 
when the bottom edge of the glass is 25 feet (7620 
mm) or more above grade, a roof, walking surfaces, 
or other horizontal [within 45 degrees (0.79 rad) of 
horizontal] surface adjacent to the glass exterior. 

7. Louvered windows and jalousies complying with 
the requirements of Section R308.2. 

8. Mirrors and other glass panels mounted or hung on a 
surface that provides a continuous backing support. 

9. Safety glazing in Section R308.4, Items 10 and 1 1, 
is not required where: 

9.1. The side of a stairway, landing or ramp has a 
guardrail or handrail, including balusters or 
in-fill panels, complying with the provisions 
of Sections 1013 and 1607.7 of the Interna- 
tional Building Code; and 

9.2. The plane of the glass is more than 18 inches 
(457 mm) from the railing; or 



9.3. When a solid wall or panel extends from the 
plane of the adjacent walking surface to 34 
inches (863 mm) to 36 inches (914 mm) above 
the floor and the construction at the top of that 
wall or panel is capable of withstanding the 
same horizontal load as the protective bar. 

10. Glass block panels complying with Section R610. 

R308.5 Site built windows. Site built windows shall comply 
with Section 2404 of the International Building Code. 

R308.6 Skylights and sloped glazing. Skylights and sloped 
glazing shall comply with the following sections. 

R308.6.1 Definitions. 

SKYLIGHTS AND SLOPED GLAZING. Glass or other 
transparent or translucent glazing material installed at a 
slope of 15 degrees (0.26 rad) or more from vertical. Glaz- 
ing materials in skylights, including unit skylights, solari- 
ums, sunrooms, roofs and sloped walls are included in this 
definition. 

UNIT SKYLIGHT. A factory assembled, glazed fenestra- 
tion unit, containing one panel of glazing material, that 
allows for natural daylighting through an opening in the 
roof assembly while preserving the weather-resistant bar- 
rier of the roof. 

R308.6.2 Permitted materials. The following types of 
glazing may be used: 

1. Laminated glass with a minimum 0.015-inch (0.38 
mm) polyvinyl butyral interlay er for glass panes 16 
square feet (1.5 m^) or less in area located such that 
the highest point of the glass is not more than 12 feet 
(3658 mm) above a walldng surface or other accessi- 
ble area; for higher or larger sizes, the minimum 
interlayer thickness shall be 0.030 inch (0.76 mm). 

2. Fully tempered glass. 

3. Heat- strengthened glass. 

4. Wired glass. 

5. Approved rigid plastics. 

R308.6.3 Screens, general. For fully tempered or 
heat-strengthened glass, a retaining screen meeting the 
requirements of Section R308.6.7 shall be installed below 
the glass, except for fully tempered glass that meets either 
condition listed in Section R308.6.5. 

R308.6.4 Screens with multiple glazing. When the 
inboard pane is fully tempered, heat-strengthened or wired 
glass, a retaining screen meeting the requirements of Sec- 
tion R308.6.7 shall be installed below the glass, except for 
either condition listed in Section R308.6.5. All other panes 
in the multiple glazing may be of any type listed in Section 
R308.6.2. 

R308.6.5 Screens not required. Screens shall not be 
required when fully tempered glass is used as single glazing 
or the inboard pane in multiple glazing and either of the fol- 
lowing conditions are met: 

1. Glass area 16 square feet (1.49 m^) or less. Highest 
point of glass not more than 12 feet (3658 mm) above 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



51 



BUILDING PLANNING 



a walking surface or other accessible area, nominal 
glass thickness not more than V,^ inch (4.8 mm), and 
(for multiple glazing only) the other pane or panes 
fully tempered, laminated or wired glass. 

2. Glass area greater than 16 square feet (1 .49 m^). Glass 
sloped 30 degrees (0.52 rad) or less from vertical, and 
highest point of glass not more than 10 feet (3048 
mm) above a walking surface or other accessible area. 

R308.6.6 Glass in greenhouses. Any glazing material is 
permitted to be installed without screening in the sloped 
areas of greenhouses, provided the greenhouse height at the 
ridge does not exceed 20 feet (6096 mm) above grade. 

R308.6.7 Screen characteristics. The screen and its fasten- 
ings shall be capable of supporting twice the weight of the 
glazing, be firmly and substantially fastened to the framing 
members, and have a mesh opening of no more than 1 inch 
by 1 inch (25 mm by 25 mm). 

R308.6.8 Curbs for skylights. All unit skyhghts installed 
in a roof with a pitch flatter than three units vertical in 12 
units horizontal (25 -percent slope) shall be mounted on a 
curb extending at least 4 inches ( 1 02 mm) above the plane of 
the roof unless otherwise specified in the manufacturer's 
installation instructions. 

R308.6.9 Testing and labeling. Unit skyhghts shall be tested 
by an approved independent laboratory, and bear a label iden- 
tifying manufacturer, performance grade rating and approved 
inspection agency to indicate compliance with the require- 
ments of AAMAAVDMA/CSA 101/I.S.2/A440. 



SECTION R309 
GARAGES AND CARPORTS 

R309.1 Opening protection. Openings from a private garage 
directly into a room used for sleeping purposes shall not be per- 
mitted. Other openings between the garage and residence shall 
be equipped with solid wood doors not less than 1% inches (35 
mm) in thickness, solid or honeycomb core steel doors not less 
than P/g inches (35 mm) thick, or 20-minute fire-rated doors. 

R309.1.1 Duct penetration. Ducts in the garage and ducts 
penetrating the walls or ceilings separating the dwelling 
from the garage shall be constructed of a minimum No. 26 
gage (0.48 mm) sheet steel or other approved material and 
shall have no openings into the garage. 

R309.1.2 Other penetrations. Penetrations through the 
separation required in Section R309.2 shall be protected by 
filling the opening around the penetrating item with 
approved material to resist the free passage of flame and 
products of combustion. 

R309.2 Separation required. The garage shall be separated 
from the residence and its attic area by not less than '/2-inch (12.7 
mm) gypsum board applied to the garage side. Garages beneath 
habitable rooms shall be separated from all habitable rooms 
above by not less than Vg-inch (15.9 mm) Type X gypsum board 
or equivalent. Where the separation is a floor-ceiling assembly, 
the structure supporting the separation shall also be protected by 
not less than Vj-inch (12.7 mm) gypsum board or equivalent. 
I Garages located less than 3 feet (914 mm) from a dweUing unit 



on the same lot shall be protected with not less than '/2-inch (12.7 
mm) gypsum board applied to the interior side of exterior walls 
that are within this area. Openings in these walls shall be regu- 
lated by Section R309. 1 . This provision does not apply to garage 
walls that are perpendicular to the adjacent dwelling unit wall. 

R309.3 Floor surface. Garage floor surfaces shall be of 
approved noncombustible material. 

The area of floor used for parking of automobiles or other 
vehicles shall be sloped to facilitate the movement of liquids to 
a drain or toward the main vehicle entry doorway. 

R309.4 Carports. Carports shall be open on at least two sides. 
Carport floor surfaces shall be of approved noncombustible 
material. Carports not open on at least two sides shall be con- 
sidered a garage and shall comply with the provisions of this 
section for garages. 

Exception; Asphalt surfaces shall be permitted at ground 
level in carports. 

The area of floor used for parking of automobiles or other 
vehicles shall be sloped to facilitate the movement of liquids to 
a drain or toward the main vehicle entry doorway. 

R309.5 Flood hazard areas. For buildings located in flood 
hazard areas as established by Table R301.2(l), garage floors 
shall be: 

1 . Elevated to or above the design flood elevation as deter- 
mined in Section R324; or 

2. Located below the design flood elevation provided they 
are at or above grade on all sides, are used solely for 
parking, building access, or storage, meet the require- 
ments of Section R324, and are otherwise constructed in 
accordance with this code. 

R309.6 Automatic garage door openers. Automatic garage 
door openers, if provided, shall be listed in accordance with UL 

325. 



SECTION R310 
EMERGENCY ESCAPE AND RESCUE OPENINGS 

R310.1 Emergency escape and rescue required. Basements 
and every sleeping room shall have at least one operable emer- 
gency escape and rescue opening. Such opening shall open 
directly into a public street, public alley, yard or court. Where 
basements contain one or more sleeping rooms, emergency 
egress and rescue openings shall be required in each sleeping 
room, but shall not be required in adjoining areas of the base- 
ment. Where emergency escape and rescue openings are pro- 
vided they shall have a sill height of not more than 44 inches 
(1118 mm) above the floor. Where a door opening having a 
threshold below the adjacent ground elevation serves as an 
emergency escape and rescue opening and is provided with a 
bulkhead enclosure, the bulkhead enclosure shall comply with 
Section R3 10.3. The net clear opening dimensions required by 
this section shall be obtained by the normal operation of the 
emergency escape and rescue opening from the inside. Emer- 
gency escape and rescue openings with a finished sill height 
below the adjacent ground elevation shall be provided with a 
window well in accordance with Section R310.2. Emergency 



52 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



BUILDING PLANNING 



escape and rescue openings shall open directly into a public 
way, or to a yard or court that opens to a public way. 

I Exception: Basements used only to house mechanical 
equipment and not exceeding total floor area of 200 square 
feet (18.58 m2). 

R310.1.1 Minimum opening area. All emergency escape 
and rescue openings shall have a minimum net clear open- 
ing of 5.7 square feet (0.530 m^). 

Exception: Grade floor openings shall have a minimum 
net clear opening of 5 square feet (0.465 m^). 

R310.1.2 Minimum opening height. The minimum net 
clear opening height shall be 24 inches (610 mm). 

R310.1.3 Minimum opening width. The minimum net 
clear opening width shall be 20 inches (508 mm). 

R310.1.4 Operational constraints. Emergency escape and 

I rescue openings shall be operational from the inside of the 
room without the use of keys, tools or special knowledge. 

R310.2 Window wells. The minimum horizontal area of the 
window well shall be 9 square feet (0.9 m^), with a minimum 
horizontal projection and width of 36 inches (914 mm). The 
area of the window well shall allow the emergency escape and 
rescue opening to be fully opened. 

Exception: The ladder or steps required by Section R3 10.2. 1 
shall be permitted to encroach a maximum of 6 inches (152 
mm) into the required dimensions of the window well. 

R310.2.1 Ladder and steps. Window wells with a vertical 
depth greater than 44 inches (1118 mm) shall be equipped 
with a permanently affixed ladder or steps usable with the 
window in the fully open position. Ladders or steps required 
by this section shall not be required to comply with Sections 
R31 1.5 and R31 1.6. Ladders or rungs shall have an inside 
width of at least 12 inches (305 mm), shall project at least 3 
inches (76 mm) from the wall and shall be spaced not more 
than 18 inches (457 mm) on center vertically for the full 
height of the window well. 

R310.3 BuUihead enclosures. Bulkhead enclosures shall pro- 
vide direct access to the basement. The bulkhead enclosure with 
the door panels in the fully open position shall provide the mini- 
mum net clear opening required by Section R3 10. 1 . 1 . Bulkhead 
enclosures shall also comply with Section R3 11.5.8.2. 

R310.4 Bars, grilles, covers and screens. Bars, grilles, cov- 
ers, screens or similar devices are permitted to be placed over 
emergency escape and rescue openings, bulkhead enclosures, 
or window wells that serve such openings, provided the mini- 
mum net clear opening size complies with Sections R310.1.1 
to R3 10. 1 .3, and such devices shall be releasable or removable 

I from the inside without the use of a key, tool, special knowl- 
edge or force greater than that which is required for normal 
operation of the escape and rescue opening. 

R310.5 Emergency escape windows under decks and 
porches. Emergency escape windows are allowed to be 
installed under decks and porches provided the location of the 
deck allows the emergency escape window to be fully opened 
and provides a path not less than 36 inches (914 mm) in height 
to a yard or court. 



SECTION R311 
MEANS OF EGRESS 

R311.1 General. Stairways, ramps, exterior egress balconies, 
hallways and doors shall comply with this section. 

R311.2 Construction. 

R311.2.1 Attachment. Required exterior egress balconies, 
exterior exit stairways and similar means of egress 
components shall be positively anchored to the primary 
structure to resist both vertical and lateral forces. Such 
attachment shall not be accomplished by use of toenails or 
nails subject to withdrawal. 

R311.2.2 Under stair protection. Enclosed accessible space 
under stairs shall have walls, under stair surface and any sof- 
fits protected on the enclosed side with Vj-inch (13 mm) gyp- 
sum board. 

R311.3 Hallways. The minimum width of a hallway shall be 
not less than 3 feet (914 mm). 

R311.4 Doors. 

R311.4.1 Exit door required. Not less than one exit door 
conforming to this section shall be provided for each dwell- 
ing unit. The required exit door shall provide for direct 
access from the habitable portions of the dwelling to the 
exterior without requiring travel through a garage. Access to 
habitable levels not having an exit in accordance with this 
section shall be by a ramp in accordance with Section 
R31 1.6 or a stairway in accordance with Section R31 1.5. 

R311.4.2 Door type and size. The required exit door shall 
be a side-hinged door not less than 3 feet (914 mm) in width 
and 6 feet 8 inches (2032 mm) in height. Other doors shall 
not be required to comply with these minimum dimensions. 

R311.4.3 Landings at doors. There shall be a floor or land- 
ing on each side of each exterior door. The floor or landing 
at the exterior door shall not be more than 1.5 inches (38 
mm) lower than the top of the threshold. The landing shall 
be permitted to have a slope not to exceed 0.25 unit vertical 
in 12 units horizontal (2-percent). 

Exceptions: 

1 . Where a stairway of two or fewer risers is located 
on the exterior side of a door, other than the 
required exit door, a landing is not required for the 
exterior side of the door provided the door, other 
than an exterior storm or screen door does not 
swing over the stairway. 

2. The exterior landing at an exterior doorway shall 
not be more than 7V4 inches (196 mm) below the 
top of the threshold, provided the door, other than 
an exterior storm or screen door does not swing 
over the landing. 

3 . The height of floors at exterior doors other than the 
exit door required by Section R3 11 .4. 1 shall not be 
more than VI ^ inches (186 mm) lower than the top 
of the threshold. 

The width of each landing shall not be less than the door 
served. Every landing shall have a minimum dimension of 
36 inches (914 mm) measured in the direction of travel. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



53 



BUILDING PLANNING 



R311.4.4 Type of lock or latch. All egress doors shall be 
readily openable from the side from which egress is to be 
made without the use of a key or special knowledge or effort. 

R311.5 Stairways. 

R311.5.1 Width. Stairways shall not be less than 36 inches 
(914 mm) in clear width at all points above the permitted 
handrail height and below the required headroom height. 
Handrails shall not project more than 4.5 inches (1 14 mm) 
on either side of the stairway and the minimum clear width 
of the stairway at and below the handrail height, including 
treads and landings, shall not be less than 31.5 inches (787 
mm) where a handrail is installed on one side and 27 inches 
(698 mm) where handrails are provided on both sides. 

Exception: The width of spiral stairways shall be in 
accordance with Section R31 1.5.8. 

R311.5.2 Headroom. The minimum headroom in all parts 
of the stairway shall not be less than 6 feet 8 inches (2036 
mm) measured vertically from the sloped plane adjoining 
the tread nosing or from the floor surface of the landing or 
platform. 

R311.5.3 Stair treads and risers. 

R311.5.3.1 Riser height. The maximum riser height 
shall be VI ^ inches (196 mm). The riser shall be mea- 
sured vertically between leading edges of the adjacent 
treads. The greatest riser height within any flight of stairs 
shall not exceed the smallest by more than ^/g inch (9.5 
mm). 

R31 1.5.3.2 Tread depth. The minimum tread depth 
shall be 10 inches (254 mm). The tread depth shall be 
measured horizontally between the vertical planes of the 
foremost projection of adjacent treads and at a right 
angle to the tread's leading edge. The greatest tread depth 
within any flight of stairs shall not exceed the smallest by 
more than Vg inch (9.5 mm). Winder treads shall have a 
minimum tread depth of 10 inches (254 mm) measured 
as above at a point 12 inches (305 mm) from the side 
where the treads are narrower. Winder treads shall have a 
minimum tread depth of 6 inches (152 mm) at any point. 
Within any flight of stairs, the largest winder tread depth 
at the 12 inch (305 mm) walk line shall not exceed the 
smallest by more than Vg inch (9.5 mm). 

R311.5.3.3 Profile. The radius of curvature at the lead- 
ing edge of the tread shall be no greater than 7i6 inch (14 
mm). A nosing not less than V4 inch (19 mm) but not 
more than 1 74 inch (32 mm) shall be provided on stair- 
ways with solid risers. The greatest nosing projection 
shall not exceed the smallest nosing projection by more 
than Vg inch (9.5 mm) between two stories, including 
the nosing at the level of floors and landings. Beveling 
of nosing shall not exceed V2 inch (12.7 mm). Risers 
shall be vertical or sloped from the underside of the 
leading edge of the tread above at an angle not more 
than 30 degrees (0.5 1 rad) from the vertical. Open risers 
are permitted, provided that the opening between treads 
does not permit the passage of a 4-inch diameter (102 
mm) sphere. 



Exceptions: 

1 . A nosing is not required where the tread depth 
is a minimum of 11 inches (279 mm). 

2. The opening between adjacent treads is not lim- 
ited on stairs with a total rise of 30 inches (762 
mm) or less. 

R311.5.4 Landings for stairways. There shall be a floor or 
landing at the top and bottom of each stairway. 

Exception: A floor or landing is not required at the top of 
an interior flight of stairs, including stairs in an enclosed I 
garage, provided a door does not swing over the stairs. | 

A flight of stairs shall not have a vertical rise larger than 
12 feet (3658 mm) between floor levels or landings. 

The width of each landing shall not be less than the width 
of the stairway served. Every landing shall have a minimum 
dimension of 36 inches (914 mm) measured in the direction 
of travel. 

R311.5.5 Stairway walking surface. The walking surface 
of treads and landings of stairways shall be sloped no 
steeper than one unit vertical in 48 inches horizontal (2-per- 
cent slope). 

R311.5.6 Handrails. Handrails shall be provided on at least 
one side of each continuous run of treads or flight with four 
or more risers. 

R3 11.5.6.1 Height. Handrail height, measured verti- 
cally from the sloped plane adjoining the tread nosing, or 
finish surface of ramp slope, shall be not less than 34 
inches (864 mm) and not more than 38 inches (965 mm). 

R311.5.6.2 Continuity. Handrails for stairways shall be 
continuous for the full length of the flight, from a point 
directly above the top riser of the flight to a point directly 
above the lowest riser of the flight. Handrail ends shall be 
returned or shall terminate in newel posts or safety termi- 
nals. Handrails adjacent to a wall shall have a space of not 
less than VI 2 inch (38 mm) between the wall and the 
handrails. 

Exceptions: 

1 . Handrails shall be permitted to be interrupted 
by a newel post at the turn. 

2. The use of a volute, turnout, starting easing or 
starting newel shall be allowed over the lowest 
tread. 

R31 1.5.6.3 Handrail grip size. All required handrails 
shall be of one of the following types or provide equiva- 
lent graspability. 

1. Type I. Handrails with a circular cross section 
shall have an outside diameter of at least 1 V4 inches 
(32 mm) and not greater than 2 inches (5 1 nmi). If 
the handrail is not circular it shall have a perimeter 
dimension of at least 4 inches (102 mm) and not 
greater than 6V4 inches (160 mm) with a maximum 
cross section of dimension of 2V4 inches(57 mm). 

2. Type 11. Handrails with a perimeter greater than 6 74 
inches (160 mm) shall provide a graspable finger 



54 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



BUILDING PLANNING 



recess area on both sides of the profile. The finger 
recess shall begin within a distance of % inch (19 
mm) measured vertically from the tallest portion of 
the profile and achieve a depth of at least ^/|6 inch (8 
mm) within Vg inch (22 mm) below the widest por- 
tion of the profile. This required depth shall con- 
tinue for at least % inch (10 mm) to a level that is not 
less than IV4 inches (45 mm) below the tallest por- 
tion of the profile. The minimum width of the hand- 
rail above the recess shall be 1 74 inches (32 mm) to 
a maximum of 2V4 inches (70 mm). Edges shall 
have a minimum radius of 0.01 inch (0.25 mm). 

R311.5.7 Illumination. All stairs shall be provided with 
illumination in accordance with Section R303.6. 

R311.5.8 Special stairways. Spiral stairways and bulkhead 
enclosure stairways shall comply with all requirements of 
Section R3 1 1 .5 except as specified below. 

R311.5.8.1 Spiral stairways. Spiral stairways are per- 
mitted, provided the minimum width shall be 26 inches 
(660 mm) with each tread having a TVj-inches (190 mm) 
minimum tread depth at 12 inches from the narrower 
edge. All treads shall be identical, and the rise shall be no 
more than 9V2 inches (241 mm). A minimum headroom 
of 6 feet 6 inches (1982 mm) shall be provided. 

R311.5.8.2 Bulkhead enclosure stairways. Stairways 
serving bulkhead enclosures, not part of the required 
building egress, providing access from the outside grade 
level to the basement shall be exempt from the require- 
ments of Sections R3 1 1 .4.3 and R3 1 1 .5 where the maxi- 
mum height from the basement finished floor level to 
grade adjacent to the stairway does not exceed 8 feet 
(2438 mm), and the grade level opening to the stairway is 
covered by a bulkhead enclosure with hinged doors or 
other approved means. 

R311.6 Ramps. 

R31 1.6.1 Maximum slope. Ramps shall have a maximum 
slope of one unit vertical in twelve units horizontal (8.3-per- 
cent slope). 

Exception: Where it is technically infeasible to comply 
because of site constraints, ramps may have a maximum 
slope of one unit vertical in eight horizontal (12.5 percent 
slope). 

R311.6.2 Landings required. A minimum 3-foot-by-3-foot 
(914 mm by 914 mm) landing shall be provided: 

1. At the top and bottom of ramps. 

2. Where doors open onto ramps. 

3. Where ramps change direction. 

R31 1.6.3 Handrails required. Handrails shall be provided 
on at least one side of all ramps exceeding a slope of one unit 
vertical in 12 units horizontal (8.33-percent slope). 

R311.6.3.1 Height. Handrail height, measured above 
the finished surface of the ramp slope, shall be not less 
than 34 inches (864 mm) and not more than 38 inches 
(965 mm). 



R311.6.3.2 Handrail grip size. Handrails on ramps 
shall comply with Section R31 1.5.6.3. 

R311.6.3.3 Continuity. Handrails where required on 
ramps shall be continuous for the full length of the ramp. 
Handrail ends shall be returned or shall terminate in 
newel posts or safety terminals. Handrails adjacent to a 
wall shall have a space of not less than 1.5 inches (38 
mm) between the wall and the handrails. 



SECTION R312 
GUARDS 

R312.1 Guards. Porches, balconies, ramps or raised floor sur- I 
faces located more than 30 inches (762 mm) above the floor or | 
grade below shall have guards not less than 36 inches (914 mm) 
in height. Open sides of stairs with a total rise of more than 30 
inches (762 mm) above the floor or grade below shall have 
guards not less than 34 inches (864 mm) in height measured 
vertically from the nosing of the treads. 

Porches and decks which are enclosed with insect screening 
shall be equipped with guards where the walking surface is 
located more than 30 inches (762 mm) above the floor or grade 
below. 

R312.2 Guard opening limitations. Required guards on open 
sides of stairways, raised floor areas, balconies and porches 
shall have intermediate rails or ornamental closures which do 
not allow passage of a sphere 4 inches (102mm) or more in 
diameter. 

Exceptions: 

1 . The triangular openings formed by the riser, tread and 
bottom rail of a guard at the open side of a stairway are 
permitted to be of such a size that a sphere 6 inches 
(152 mm) cannot pass through. 

2. Openings for required guards on the sides of stair 
treads shall not allow a sphere 4 Vg inches (107 mm) to 
pass through. 



SECTION R313 
SMOKE ALARMS 

R313.1 Smoke detection and notification. All smoke alarms 
shall be listed in accordance with UL 217 and installed in 
accordance with the provisions of this code and the household 
fire warning equipment provisions of NFPA 72. 

Household fire alarm systems installed in accordance with 
NFPA 72 that include smoke alarms, or a combination of 
smoke detector and audible notification device installed as 
required by this section for smoke alarms, shall be permitted. 
The household fire alarm system shall provide the same level of 
smoke detection and alarm as required by this section for 
smoke alarms in the event the fire alarm panel is removed or the 
system is not connected to a central station. 

R313.2 Location. Smoke alarms shall be installed in the fol- 
lowing locations: 

1 . In each sleeping room. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



55 



BUILDING PLANNING 



2. Outside each separate sleeping area in the immediate 
vicinity of the bedrooms. 

3. On each additional story of the dwelling, including base- 
ments but not including crawl spaces and uninhabitable 
attics. In dwellings or dwelling units with split levels and 
without an intervening door between the adjacent levels, 
a smoke alarm installed on the upper level shall suffice 
for the adjacent lower level provided that the lower level 
is less than one full story below the upper level. 

When more than one smoke alarm is required to be installed 
within an individual dwelling unit the alarm devices shall be 
interconnected in such a manner that the actuation of one alarm 
will activate all of the alarms in the individual unit. 

R313.2.1 Alterations, repairs and additions. When alter- 
ations, repairs or additions requiring a permit occur, or 
when one or more sleeping rooms are added or created in 
existing dwellings, the individual dwelling unit shall be 
equipped with smoke alarms located as required for new 
dwellings; the smoke alarms shall be interconnected and 
hard wired. 

Exceptions: 

1. Interconnection and hard- wiring of smoke alarms 
in existing areas shall not be required where the 
alterations or repairs do not result in the removal of 
interior wall or ceiling finishes exposing the struc- 
ture, unless there is an attic, crawl space or base- 
ment available which could provide access for 
hard wiring and interconnection without the 
removal of interior finishes. 

2. Work involving the exterior surfaces of dwellings, 
such as the replacement of roofing or siding, or the 
addition or replacement of windows or doors, or 
the addition of a porch or deck, are exempt from 
the requirements of this section. 

R313.3 Power source. In new construction, the required 
smoke alarms shall receive their primary power from the build- 
ing wiring when such wiring is served from a commercial 
source, and when primary power is interrupted, shall receive 
power from a battery. Wiring shall be permanent and without a 
disconnecting switch other than those required for overcurrent 
protection. Smoke alarms shall be permitted to be battery oper- 
ated when installed in buildings without commercial power or 
in buildings that undergo alterations, repairs or additions regu- 
lated by Section R313.2.1. 



SECTION R314 
FOAM PLASTIC 

R314.1 General. The provisions of this section shall govern 
the materials, design, application, construction and installation 
of foam plastic materials. 

R314.2 Labeling and identification. Packages and contain- 
ers of foam plastic insulation and foam plastic insulation 
components delivered to the job site shall bear the label of an 
approved agency showing the manufacturer's name, the prod- 
uct listing, product identification and information sufficient 



56 



to determine that the end use will comply with the require- 
ments. 

R314.3 Surface burning characteristics. Unless otherwise 
allowed in Section R314.5 or R314.6, all foam plastic or foam 
plastic cores used as a component in manufactured assemblies 
used in building construction shall have a flame spread index of 
not more than 75 and shall have a smoke-developed index of 
not more than 450 when tested in the maximum thickness 
intended for use in accordance with ASTM E 84. 
Loose-fill-type foam plastic insulation shall be tested as board 
stock for the flame spread index and smoke-developed index. 

Exception: Foam plastic insulation more than 4 inches 
thick shall have a maximum flame spread index of 75 and a 
smoke-developed index of 450 where tested at a minimum 
thickness of 4 inches, provided the end use is approved in 
accordance with Section R314.6 using the thickness and 
density intended for use. 

R314.4 Thermal barrier. Unless otherwise allowed in Section 
R3 14.5 or Section R3 14.6, foam plastic shall be separated from 
the interior of a building by an approved thermal barrier of min- 
imum 0.5 inch (12.7 mm) gypsum wallboard or an approved 
finish material equivalent to a thermal barrier material that will 
limit the average temperature rise of the unexposed surface to 
no more than 250°F (139°C) after 15 minutes of fire exposure 
complying with the ASTM E 119 standard time temperature 
Curve. The thermal barrier shall be installed in such a manner 
that it will remain in place for 15 minutes based on NFPA 286 
with the acceptance criteria of Section R315.4, FM 4880, UL 
1040 or UL 1715. 

R314.5 Specific requirements. The following requirements 
shall apply to these uses of foam plastic unless specifically 
approved in accordance with Section R314.6 or by other sec- 
tions of the code or the requirements of Sections R314.2 
through R314.4 have been met. 

R314.5.1 Masonry or concrete construction. The thermal 
barrier specified in Section R314.4 is not required in a 
masonry or concrete wall, floor or roof when the foam plas- 
tic insulation is separated from the interior of the building 
by a minimum 1-inch (25 mm) thickness of masonry or con- 
crete. 

R314.5.2 Roofing. The thermal barrier specified in Section 
R314.4 is not required when the foam plastic in a roof 
assembly or under a roof covering is installed in accordance 
with the code and the manufacturer's installation instruc- 
tions and is separated from the interior of the building by 
tongue-and-groove wood planks or wood structural panel 
sheathing in accordance with Section R803, not less than 
^^/32 inch (11.9 mm) thick bonded with exterior glue and 
identified as Exposure 1 , with edges supported by blocking 
or tongue-and-groove joints or an equivalent material. The 
smoke-developed index for roof applications shall not be 
hmited. 

; R314.5.3 Attics. The thermal barrier specified in Section 
314.4 is not required where attic access is required by Sec- 
tion R807 . 1 and where the space is entered only for service 
of utilities and when the foam plastic insulation is protected 



2006 INTERNATIONAL RESIDENTIAL CODE® 



BUILDING PLANNING 



against ignition using one of the following ignition barrier 
materials: 

1. 1.5 -inch-thick (38 mm) mineral fiber insulation; 

2. 0.25-inch-thick (6.4 mm) wood structural panels; 

3. 0.375-inch (9.5 mm) particleboard; 

4. 0.25-inch (6.4 nam) hardboard; 

5. 0.375-inch (9.5 mm) gypsum board; or 

6. Corrosion-resistant steel having a base metal thick- 
ness of 0.016 inch (0.406 mm). 

The above ignition barrier is not required where the foam 
plastic insulation has been tested in accordance with Section 
R314.6. 

R314.5.4 Crawl spaces. The thermal barrier specified in 
Section R314.4 is not required where crawlspace access is 
required by Section R408.3 and where entry is made only 
for service of utilities and the foam plastic insulation is pro- 
tected against ignition using one of the following ignition 
barrier materials: 

1. 1.5-inch-thick (38 mm) mineral fiber insulation; 

2. 0.25-inch-thick (6.4 mm) wood structural panels; 

3. 0.375-inch (9.5 mm) particleboard; 

4. 0.25-inch (6.4 mm) hardboard; 

5. 0.375-inch (9.5 mm) gypsum board; or 

6. Corrosion-resistant steel having a base metal thick- 
ness of 0.016 inch (0.41 mm). 

The above ignition barrier is not required where the foam 
plastic insulation has been tested in accordance with Section 
R314.6. 

R314.5.5 Foam-filled exterior doors. Foam-filled exterior 
doors are exempt from the requirements of Sections R3 14.3 
and R3 14.4. 

R314.5.6 Foam-filled garage doors. Foam-filled garage 
doors in attached or detached garages are exempt from the 
requirements of Sections R314.3 and R314.4. 

R3 14.5.7 Foam backer board. The thermal barrier speci- 
fied in Section R314.4 is not required where siding backer 
board foam plastic insulation has a maximum thickness of 
0.5 inch (12.7 mm) and a potential heat of not more than 
2000 Btu per square foot (22 720 kJ/m^) when tested in 
accordance with NFPA 259 provided that: 

1 . The foam plastic insulation is separated from the inte- 
rior of the building by not less than 2 inches (5 1 mm) 
of mineral fiber insulation or 

2. The foam plastic insulation is installed over existing 
exterior wall finish in conjunction with re-siding or 

3. The foam plastic insulation has been tested in accor- 
dance with Section R314.6. 

R314.5.8 Re-siding. The thermal barrier specified in Sec- 
tion R314.4 is not required where the foam plastic insula- 
tion is installed over existing exterior wall finish in 
conjunction with re-siding provided the foam plastic has a 
maximum thickness of 0.5 inch (12.7 mm) and a potential 



heat of not more than 2000 Btu per square foot (22 720 
kJ/m^) when tested in accordance with NFPA 259. 

R314.5.9 Interior trim. The thermal barrier specified in 
Section R314.4 is not required for exposed foam plastic 
interior trim, provided all of the following are met: 

1. The minimum density is 20 pounds per cubic foot 
(320 kg/m3). 

2. The maximum thickness of the trim is 0.5 inch (12.7 
mm) and the maximum width is 8 inches (204 mm). 

3 . The interior trim shall not constitute more than 1 per- 
cent of the aggregate wall and ceiling area of any 
room or space. 

4. The flame spread index does not exceed 75 when 
tested per ASTM E 84. The smoke-developed index is 
not hmited. 

R314.5.10 Interior finish. Foam plastics shall be permitted 
as interior finish where approved in accordance with 
R314.6. Foam plastics that are used as interior finish shall 
also meet the flame spread and smoke-developed require- 
ments of Section R315. 

R314.5.11 Sill plates and headers. Foam plastic shall be 
permitted to be spray applied to a sill plate and header with- 
out the thermal barrier specified in Section R314.4 subject 
to all of the following: 

1 . The maximum thickness of the foam plastic shall be 
3 V4 inches (83 mm). 

2. The density of the foam plastic shall be in the range of 
1.5 to 2.0 pounds per cubic foot (24 to 32 kg/m^). 

3 . The foam plastic shall have a flame spread index of 25 
or less and an accompanying smoke developed index 
of 450 or less when tested in accordance with ASTM 

E84. 

R3 14.5. 12 Sheathing. Foam plastic insulation used as 
sheathing shall comply with Section R314.3 and Section 
R3 14.4. Where the foam plastic sheathing is exposed to the 
attic space at a gable or kneewall, the provisions of Section 
R314.5.3 shall apply. 

R314.6 Specific approval. Foam plastic not meeting the 
requirements of Sections R314.3 through R314.5 shall be spe- 
cifically approved on the basis of one of the following 
approved tests: NFPA 286 with the acceptance criteria of Sec- 
tion R3 15.4, FM4880, UL 1040 or UL 17 15, or fire tests related 
to actual end-use configurations. The specific approval shall be 
based on the actual end use configuration and shall be per- 
formed on the finished foam plastic assembly in the maximum 
thickness intended for use. Assembhes tested shall include 
seams, joints and other typical details used in the installation of 
the assembly and shall be tested in the manner intended for use. 

R314.7 Termite damage. The use of foam plastics in areas of 
"very heavy" termite infestation probability shall be in accor- 
dance with Section R320.4. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



57 



BUILDING PLANNING 



SECTION R31 5 
FLAME SPREAD AND SMOKE DENSITY 

R315.1 Wall and ceiling. Wall and ceiling finishes shall have a 
flame-spread classification of not greater than 200. 

Exception: Hame-spread requirements for finishes shall not 
apply to trim defined as picture molds, chair rails, baseboards 
and handrails; to doors and windows or their frames; or to 
materials that are less than V28 i^^ch (0.91 mm) in thickness 
cemented to the surface of walls or ceilings if these materials 
have a flame-spread characteristic no greater than paper of 
this thickness cemented to a noncombustible backing. 

R315.2 Smoke-developed index. Wall and ceiling finishes 
shall have a smoke-developed index of not greater than 450. 

R315.3 Testing. Tests shall be made in accordance with ASTM 

E84. 

R315.4 Alternate test method. As an alternate to having a 
flame-spread classification of not greater than 200 and a smoke 
developed index of not greater than 450 when tested in accor- 
dance with ASTM E 84, wall and ceiling finishes, other than 
textiles, shall be permitted to be tested in accordance with 
NFPA 286. Materials tested in accordance with NFPA 286 
shall meet the following criteria: 

During the 40 kW exposure, the interior finish shall comply 
with Item 1. During the 160 kW exposure, the interior finish 
shall comply with Item 2. During the entire test, the interior fin- 
ish shall comply with Item 3. ~ 

1 . During the 40 kW exposure, flames shall not spread to 
the ceiling. 

2. During the 160 kW exposure, the interior finish shall 
comply with the following: 

2.1. Flame shall not spread to the outer extremity of 
the sample on any wall or ceiling. 

2.2. Flashover, as defined in NFPA 286, shall not 
occur. 

3. The total smoke released throughout the NFPA 286 test 
shall not exceed 1,000 m^. 



SECTION R31 6 
INSULATION 

R316.1 Insulation. Insulation materials, including facings, 
such as vapor retarders or vapor permeable membranes 
installed within floor-ceiling assemblies, roof-ceiling assem- 
blies, wall assembhes, crawl spaces and attics shall have a 
flame-spread index not to exceed 25 with an accompanying 
smoke-developed index not to exceed 450 when tested in 
accordance with ASTM E 84. 

Exceptions: 

1. When such materials are installed in concealed 
spaces, the flame-spread and smoke-developed limi- 
tations do not apply to the facings, provided that the 
facing is installed in substantial contact with the unex- 
posed surface of the ceiling, floor or wall finish. 

2. Cellulose loose-fill insulation, which is not spray 
applied, complying with the requirements of Section 



R316.3, shall only be required to meet the smoke- 
developed index of not more than 450. 

R316.2 Loose-fill insulation. Loose-fill insulation materials 
that cannot be mounted in the ASTM E 84 apparatus without a 
screen or artificial supports shall comply with the flame spread 
and smoke-developed limits of Sections R316.1 and R316.4 
when tested in accordance with CAN/ULC S 102.2. 

Exception: Cellulose loose-fill insulation shall not be 
required to comply with the flame spread index requirement 
of CAN/ULC S 102.2, provided such insulation complies 
with the requirements of Section R316.3. 

R316.3 Cellulose loose-fill insulation. Cellulose loose-fill 
insulation shall comply with CPSC 16 CFR, Parts 1209 and 
■ 1404. Each package of such insulating material shall be clearly 
labeled in accordance with CPSC 16 CFR, Parts 1209 and 
1404. 

R316.4 Exposed attic insulation. All exposed insulation 
materials installed on attic floors shall have a critical radiant 
flux not less than 0.12 watt per square centimeter. 

R316.5 Testing. Tests for critical radiant flux shall be made in 
accordance with ASTM E 970. 



SECTION R317 
DWELLING UNIT SEPARATION 

R317.1 Two-family dwellings. Dwelling units in two-family 
dwellings shall be separated from each other by wall and/or 
floor assemblies having not less than a 1-hour fire-resistance 
rating when tested in accordance with ASTM E 1 19. Fire-resis- 
tance-rated floor-ceiling and wall assemblies shall extend to 
and be tight against the exterior wall, and wall assemblies shall 
extend to the underside of the roof sheathing. 

Exceptions: 

1 . A fire-resistance rating of Vj hour shall be permitted 
in buildings equipped throughout with an automatic 
sprinkler system installed in accordance with NFPA 
13. 

2. Wall assemblies need not extend through attic spaces 
when the ceiling is protected by not less than Vg-inch 
(15.9 mm) Type X gypsum board and an attic draft 
stop constructed as specified in Section R502.12.1 is 
provided above and along the wall assembly separat- 
ing the dwellings. The structural framing supporting 
the ceiUng shall also be protected by not less than Vj 
-inch (12.7 mm) gypsum board or equivalent. 

R317.1.1 Supporting construction. When floor assem- 
: blies are required to be fire-resistance-rated iby Section 
; R317.1, the supporting construction of such assembhes 

shall have an equal or greater fire-resistive rating. 

R317.2 Townhouses. Each townhouse shall be considered a 
separate building and shall be separated by fire-resis- 
tance-rated wall assemblies meeting the requirements of Sec- 
tion R302 for exterior walls. 

Exception: A common 2-hour fire-resistance-rated wall is 
permitted for townhouses if such walls do not contain 
plumbing or mechanical equipment, ducts or vents in the 



58 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANNING 



cavity of the common wall. Electrical installations shall be 
installed in accordance with Chapters 33 through 42. Pene- 
trations of electrical outlet boxes shall be in accordance with 
Section R3 17.3. 

R317.2.1 Continuity. The fire-resistance-rated wall or 
assembly separating townhouses shall be continuous from 
the foundation to the underside of the roof sheathing, deck 
or slab. The fire-resistance rating shall extend the full length 
of the wall or assembly, including wall extensions through 
and separating attached enclosed accessory structures. 

R317.2.2 Parapets. Parapets constructed in accordance 
with Section R3 17.2.3 shall be constructed for townhouses 
as an extension of exterior walls or common walls in accor- 
dance with the following: 

1 . Where roof surfaces adjacent to the wall or walls are 
at the same elevation, the parapet shall extend not 
less than 30 inches (762 mm) above the roof sur- 
faces. 

2. Where roof surfaces adjacent to the wall or walls are 
at different elevations and the higher roof is not more 
than 30 inches (762 mm) above the lower roof, the 
parapet shall extend not less than 30 inches (762 
mm)above the lower roof surface. 

Exception: A parapet is not required in the two 
cases above when the roof is covered with a mini- 
mum class C roof covering, and the roof decking or 
sheathing is of noncombustible materials or 
approved fire-retardant-treated wood for a dis- 
tance of 4 feet (1219 mm) on each side of the wall 
or walls, or one layer of Vg-inch (15.9 mm) Type X 
gypsum board is installed directly beneath the roof 
decking or sheathing, supported by a minimum of 
nominal 2-inch (51 mm) ledgers attached to the 
sides of the roof framing members, for a minimum 
distance of 4 feet (1220 mm) on each side of the 
wall or walls. 

3. A parapet is not required where roof surfaces adja- 
cent to the wall or walls are at different elevations 
and the higher roof is more than 30 inches (762 mm) 
above the lower roof. The common wall construc- 
tion from the lower roof to the underside of the 
higher roof deck shall have not less than a 1-hour 
fire-resistence rating. The wall shall be rated for 
exposure from both sides. 

R317.2.3 Parapet construction. Parapets shall have the 
same fire-resistance rating as that required for the supporting 
wall or walls. On any side adjacent to a roof surface, the para- 
pet shall have noncombustible faces for the uppermost 18 
inches (457 mm), to include counterflashing and coping 
materials. Where the roof slopes toward a parapet at slopes 
greater than two units vertical in 12 units horizontal 
(16.7-percent slope), the parapet shall extend to the same 
height as any portion of the roof within a distance of 3 feet 
(914 mm), but in no case shall the height be less than 30 
inches (762 mm). 



R317.2.4 Structural independence. Each individual town- 
house shall be structurally independent. 

Exceptions: 

1 . Foundations supporting exterior walls or common 
walls. 

2. Structural roof and wall sheathing from each unit 
may fasten to the common wall framing. 

3. Nonstructural wall coverings. 

4. Flashing at termination of roof covering over com- 
mon wall. 

5. Townhouses separated by a common 2-hour 
fire-resistance-rated wall as provided in Section 
R317.2. 

R317.3 Rated penetrations. Penetrations of wall or floor/ceil- 
ing assemblies required to be fire-resistance rated in accor- 
dance with Section R317.1 or R3 17.2 shall be protected in 
accordance with this section. 

R317.3.1 Through penetrations. Through penetrations of 
fire-resistance-rated wall or floor assemblies shall comply 
with Section R317.3. 1.1 or R317.3.1.2. 

Exception: Where the penetrating items are steel, fer- 
rous or copper pipes, tubes or conduits, the annular space 
shall be protected as follows: 

1. In concrete or masonry wall or floor assemblies 
where the penetrating item is a maximum 6 inches 
(152 mm) nominal diameter and the area of the I 
opening through the wall does not exceed 144 | 
square inches (92 900 mm^), concrete, grout or 
mortar is permitted where installed to the full 
thickness of the wall or floor assembly or the thick- 
ness required to maintain the fire-resistance rating. 

2. The material used to fill the annular space shall 
prevent the passage of flame and hot gases suffi- 
cient to ignite cotton waste where subjected to 
ASTM E 119 time temperature fire conditions 
under a minimum positive pressure differential of 
0.01 inch of water (3 Pa) at the location of the pen- 
etration for the time period equivalent to the fire 
resistance rating of the construction penetrated. 

R317.3.1.1 Fire-resistance-rated assembly. Penetra- 
tions shall be installed as tested in the approved fire- 
resistance-rated assembly. 

R317.3.1.2 Penetration firestop system. Penetrations 
shall be protected by an approved penetration firestop 
system installed as tested in accordance with ASTM E 
814 or UL 1479, with a minimum positive pressure dif- 
ferential of 0.01 inch of water (3 Pa) and shall have an F 
rating of not less than the required fire-resistance rating 
of the wall or floor/ceiling assembly penetrated. 

R317.3.2 Membrane penetrations. Membrane penetra- 
tions shall comply with Section R3 17.3.1. Where walls are 
required to have a fire-resistance rating, recessed fixtures | 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



59 



BUILDING PLANNING 



shall be so installed such that the required fire resistance will 
not be reduced. 

Exceptions: 

1. Membrane penetrations of maximum 2-hour 
fire-resistance-rated walls and partitions by steel 
electrical boxes that do not exceed 16 square inches 
(0.0103 m 2) in area provided the aggregate area of 
the openings through the membrane does not 
exceed 100 square inches (0.0645 m^) in any 100 
square feet (9.29 m^) of wall area. The annular 
space between the wall membrane and the box shall 
not exceed Vg inch (3.1 mm). Such boxes on oppo- 
site sides of the wall shall be separated as follows: 

1 . 1 . By a horizontal distance of not less than 24 
inches (610 mm) except at walls or parti- 
tions constructed using parallel rows of 
studs or staggered studs; 

1 .2. By a horizontal distance of not less than the 
depth of the wall cavity when the wall cav- 
ity is filled with cellulose loose-fill, 
rockwool or slag mineral wool insulation; 

1.3. By solid fire blocking in accordance with 
Section R602. 8.1; 

1.4. By protecting both boxes with listed putty 
pads; or 

1.5. By other listed materials and methods. 

2. Membrane penetrations by listed electrical boxes 
of any materials provided the boxes have been 
tested for use in fire-resistance-rated assemblies 
and are installed in accordance with the instruc- 
tions included in the listing. The annular space 
between the wall membrane and the box shall not 
exceed Vg inch (3.1 mm) unless listed otherwise. 
Such boxes on opposite sides of the wall shall be 
separated as follows: 

2. 1 . By a horizontal distance of not less than 24 
inches (610 mm) except at walls or parti- 
tions constructed using parallel rows of 
studs or staggered studs; 

2.2. By solid fire blocking in accordance with 
Section R602.8; 

2.3. By protecting both boxes with listed putty 
pads; or 

2.4. By other hsted materials and methods. 

3. The annular space created by the penetration of a 
fire sprinkler provided it is covered by a metal 
escutcheon plate. 



SECTION R318 
MOISTURE VAPOR RETARDERS 

R318.1 Moisture control. In all framed walls, floors and 
roof/ceilings comprising elements of the building thermal 
envelope, a vapor retarder shall be installed on the warm- 
in- winter side of the insulation. 



Exceptions: 

1 . In construction where moisture or freezing will not 
damage the materials. 

2. Where the framed cavity or space is ventilated to 
allow moisture to escape. 

3. In counties identified as in climate zones 1 through 4 | 
■ in Table Nl 101.2. 



SECTION R319 
PROTECTION AGAINST DECAY 

R319.1 Location required. Protection from decay shall be 
provided in the following locations by the use of naturally 
durable wood or wood that is preservative treated in accor- 
dance with AWPA Ul for the species, product, preservative 
and end use. Preservatives shall be listed in Section 4 of 
AWPAUl. 

1. Wood joists or the bottom of a wood structural floor 
when closer than 18 inches (457 mm) or wood girders 
when closer than 12 inches (305 mm) to the exposed 
ground in crawl spaces or unexcavated area located 
within the periphery of the building foundation. 

2. All wood framing members that rest on concrete or 
masonry exterior foundation walls and are less than 8 
inches (203 mm) from the exposed ground. 

3. Sills and sleepers on a concrete or masoniy slab that is in 
direct contact with the ground unless separated from 
such slab by an impervious moisture bander. 

4. The ends of wood girders entering exterior masonry or con- 
crete walls having clearances of less than 0.5 inch (12.7 
mm) on tops, sides and ends. 

5. Wood siding, sheathing and wall framing on the exterior 
of a building having a clearance of less than 6 inches (152 
mm) from the ground. 

6. Wood structural members supporting moisture-perme- 
able floors or roofs that are exposed to the weather, such 
as concrete or masonry slabs, unless separated from such 
floors or roofs by an impervious moisture barrier. 

7. Wood furring strips or other wood framing members 
attached directly to the interior of exterior masonry walls 
or concrete walls below grade except where an approved 
vapor retarder is applied between the wall and the furring 
strips or framing members. 

R319.1.1 Field treatment. Field-cut ends, notches and 
drilled holes of preservative-treated wood shall be treated in 
the field in accordance with AWPA M4. 

R319.1.2 Ground contact. All wood in contact with the 
ground, embedded in concrete in direct contact with the 
ground or embedded in concrete exposed to the weather that 
supports permanent structures intended for human occu- 
pancy shall be approved pressure-preservative-treated 
wood suitable for ground contact use, except untreated 
wood may be used where entirely below groundwater level 
or continuously submerged in fresh water. 



60 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANNING 



R319.1.3 Geographical areas. In geographical areas 
where experience has demonstrated a speciiic need, 
approved naturally durable or pressure-preservative-treated 
wood shall be used for those portions of wood members that 
form the structural supports of buildings, balconies, porches 
or similar permanent building appurtenances when those 
members are exposed to the weather without adequate pro- 
tection from a roof, eave, overhang or other covering that 
would prevent moisture or water accumulation on the sur- 
face or at joints between members. Depending on local 
experience, such members may include: 

1 . Horizontal members such as girders, joists and deck- 
ing. 

2. Vertical members such as posts, poles and columns. 

3. Both horizontal and vertical members. 

R319.1.4 Wood columns. Wood columns shall be approved 
wood of natural decay resistance or approved pressure-pre- 
servative-treated wood. 

Exceptions: 

1 . Columns exposed to the weather or in basements 
when supported by concrete piers or metal pedes- 
tals projecting 1 inch (25.4 mm) above a concrete 
floor or 6 inches (152 mm) above exposed earth 
and the earth is covered by an approved impervi- 
ous moisture barrier. 

2. Columns in enclosed crawl spaces or unexcavated 
areas located within the periphery of the building 
when supported by a concrete pier or metal pedes- 
tal at a height more than 8 inches (203mm) from 
exposed earth and the earth is covered by an imper- 
vious moisture barrier. 

R319.1.5 Exposed glued-laminated timbers. The portions 
of glued-laminated timbers that form the structural supports 
of a building or other structure and are exposed to weather 
and not properly protected by a roof, eave or similar covering 
shall be pressure treated with preservative, or be manufac- 
tured from naturally durable or preservative-treated wood. 

R319.2 Quality mark. Lumber and plywood required to be 
pressure-preservative-treated in accordance with Section 
R319.1 shall bear the quality mark of an approved inspection 
agency that maintains continuing supervision, testing and 
inspection over the quality of the product and that has been 
approved by an accreditation body that complies with the 
requirements of the American Lumber Standard Committee 
treated wood program. 

R319.2.1 Required information. The required quality 
mark on each piece of pressure-preservative-treated lumber 
or plywood shall contain the following information: 

1. Identification of the treating plant. 

2. Type of preservative. 

3. The minimum preservative retention. 

4. End use for which the product was treated. 

5. Standard to which the product was treated. 

6. Identity of the approved inspection agency. 



7. The designation "Dry," if applicable. 

Exception: Quahty marks on lumber less than 1 
inch (25.4 mm) nominal thickness, or lumber less 
than nominal 1 inch by 5 inches (25.4 mm by 127 
mm) or 2 inches by 4 inches (51 mm by 102 mm) 
or lumber 36 inches (914 mm) or less in length 
shall be applied by stamping the faces of exterior 
pieces or by end labeling not less than 25 percent 
of the pieces of a bundled unit. 

R319.3 Fasteners. Fasteners for pressure-preservative and 
fire-retardant-treated wood shall be of hot-dipped zinc-coated 
galvanized steel, stainless steel, silicon bronze or copper. The 
coating weights for zinc-coated fasteners shall be in accor- 
dance with ASTM A 153. 

Exceptions: 

1. One-half-inch (12.7 mm) diameter or larger steel 
bolts. 

2. Fasteners other than nails and timber rivets shall be 
permitted to be of mechanically deposited zinc- 
coated steel with coating weights in accordance with 
ASTM B 695, Class 55, minimum. 



SECTION R320 

PROTECTION AGAINST 

SUBTERRANEAN TERMITES 

R320.1 Subterranean termite control methods. In areas sub- 
ject to damage from termites as indicated by Table R301 .2(1), 
methods of protection shall be one of the following methods or 
a combination of these methods: 

1 . Chemical termiticide treatment, as provided in Section 
R320.2. 

2. Termite baiting system installed and maintained accord- 
ing to the label. 

3. Pressure-preservative-treated wood in accordance with 
the AWPA standards hsted in Section R319.1. 

4. Naturally termite-resistant wood as provided in Section 
R320.3. 

5. Physical barriers as provided in Section R320.4. 

R320.1.1 Quality mark. Lumber and plywood required to 
be pressure-preservative-treated in accordance with Section 
R320. 1 shall bear the quality mark of an approved inspec- 
tion agency which maintains continuing supervision, test- 
ing and inspection over the quality of the product and which 
has been approved by an accreditation body which complies 
with the requirements of the American Lumber Standard 
Committee treated wood program. 

R320.1.2 Field treatment. Field-cut ends, notches, and 
drilled holes of pressure-preservative-treated wood shall be 
retreated in the field in accordance with AWPA M4. 

R320.2 Chemical termiticide treatment. Chemical 
termiticide treatment shall include soil treatment and/or field 
applied wood treatment. The concentration, rate of application 
and method of treatment of the chemical termiticide shall be in 
strict accordance with the termiticide label. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



61 



BUILDING PLANNING 



R320.3 Naturally resistant wood. Heartwood of redwood and 
eastern red cedar shall be considered termite resistant. 

R320.4 Barriers. Approved physical barriers, such as metal or 
plastic sheeting or collars specifically designed for termite pre- 
vention, shall be installed in a rnanner to prevent termites from 
entering the structure. Shields placed on top of an exterior 
foundation wall are permitted to be used only if in combination 
with another method of protection. 

R320.5 Foam plastic protection. In areas where the probability 
of termite infestation is "very heavy" as indicated in Figure 
R301.2(6), extruded and expanded polystyrene, polyiso- 
cyanurate and other foam plastics shall not be installed on the 
exterior face or under interior or exterior foundation walls or slab 
foundations located below grade. The clearance between foam 
plastics installed above grade and exposed earth shall be at least 
6 inches (152 mm). 

Exceptions: 

1. Buildings where the structural members of walls, 
floors, ceilings and roofs are entirely of noncom- 
bustible materials or pressure-preservative-treated 
wood. 

2. When in addition to the requirements of Section 
R320.1, an approved method of protecting the foam 
plastic and structure from subterranean termite dam- 
age is used. 

3. On the interior side of basement walls. 



SECTION R321 
SITE ADDRESS 

R321.1 Premises identification. Approved numbers or 
addresses shall be provided for all new buildings in such a posi- 
tion as to be plainly visible and legible from the street or road 
fronting the property. 



SECTION R322 
ACCESSIBILITY 

R322.1 Scope. Where there are four or more dwelling units or 
sleeping units in a single structure, the provisions of Chapter 1 1 
of the International Building Code for Group R-3 shall apply. 



SECTION R323 
ELEVATORS AND PLATFORM LIFTS 

R323.1 Elevators. Where provided, passenger elevators, lim- 
ited-use/limited-application elevators or private residence ele- 
vators shall comply with ASME A17.1. 

R323.2 Platform lifts. Where provided, platform lifts shall 
comply with ASME A18.1. 

R323.3 Accessibility. Elevators or platform lifts that are part of 
an accessible route required by Chapter 1 1 of the International 
Building Code, shall comply with ICC A117.1. 



SECTION R324 
FLOOD-RESISTANT CONSTRUCTION 

R324.1 General. Buildings and structures constructed in 
whole or in part in flood hazard areas (including A or V Zones) 
as established in Table R301.2(l) shall be designed and con- 
structed in accordance with the provisions contained in this 
section. 

Exception: Buildings and structures located in whole or in 
part in identified floodways as established in Table 
R301 .2(1) shall be designed and constructed as stipulated in 
the International Building Code. 

R324.1.1 Structural systems. All structural systems of all 
buildings and structures shall be designed, connected and 
anchored to resist flotation, collapse or permanent lateral 
movement due to structural loads and stresses from flooding 
equal to the design flood elevation. 

R324.1.2 Flood-resistant construction. All buildings and 
structures erected in areas prone to flooding shall be con- 
structed by methods and practices that minimize flood dam- 
age. 

R324.1.3 Establishing the design flood elevation. The 

design flood elevation shall be used to define areas prone to 
flooding, and shall describe, at a minimum, the base flood 
elevation at the depth of peak elevation of flooding (includ- 
ing wave height) which has a 1 percent (100-year flood) or 
greater chance of being equaled or exceeded in any given 
year. 

R324. 1.3.1 Determination of design flood elevations. 

If design flood elevations are not specified, the building 
official is authorized to require the applicant to: 

1. Obtain and reasonably use data available from a fed- 
eral, state or other source; or 

2. Determine the design flood elevation in accordance 
with accepted hydrologic and hydraulic engineering 
practices used to define special flood hazard areas. 
Determinations shall be undertaken by a registered 
design professional who shall document that the tech- 
nical methods used reflect currently accepted engi- 
neering practice. Studies, analyses and computations 
shall be submitted in sufficient detail to allow thor- 
ough review and approval. 

R324.1.3.2 Determination of impacts. In riverine flood 
hazard areas where design flood elevations are specified 
but floodways have not been designated, the applicant 
shall demonstrate that the effect of the proposed build- 
ings and structures on design flood elevations, including 
fill, when combined with all other existing and antici- 
pated flood hazard area encroachments, will not increase 
the design flood elevation more than 1 foot (305 mm) at 
any point within the jurisdiction. 

R324.1.4 Lowest floor. The lowest floor shall be the floor 
of the lowest enclosed area, including basement, but exclud- 
ing any unfinished flood-resistant enclosure that is useable 
solely for vehicle parking, building access or limited storage 
provided that such enclosure is not built so as to render the 
: building or structure in violation of this section. 



62 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BUILDING PLANNING 



R324.1.5 Protection of mechanical and electrical sys- 
tems. Electrical systems, equipment and components, and 
heating, ventilating, air conditioning and plumbing appli- 
ances, plumbing fixtures, duct systems, and other service 
equipment shall be located at or above the design flood ele- 
vation. If replaced as part of a substantial improvement, 
electrical systems, equipment and components, and heating, 
ventilating, air conditioning, and plumbing appliances, 
plumbing fixtures, duct systems, and other service equip- 
ment shall meet the requirements of this section. Systems, 
fixtures, and equipment and components shall not be 
mounted on or penetrate through walls intended to break 
away under flood loads. 

Exception: Electrical systems, equipment and compo- 
nents, and heating, ventilating, air conditioning and 
plumbing appliances, plumbing fixtures, duct systems, 
and other service equipment are permitted to be located 
below the design flood elevation provided that they are 
designed and installed to prevent water from entering or 
accumulating within the components and to resist hydro- 
static and hydrodynamic loads and stresses, including 
the effects of buoyancy, during the occurrence of flood- 
ing to the design flood elevation in compliance with the 
flood-resistant construction requirements of the Interna- 
tional Building Code. Electrical wiring systems are per- 
mitted to be located below the design flood elevation 
provided they conform to the provisions of the electrical 
part of this code for wet locations. 

R324.1.6 Protection of water supply and sanitary sew- 
age systems. New and replacement water supply systems 
shall be designed to minimize or eliminate infiltration of 
flood waters into the systems in accordance with the plumb- 
ing provisions of this code. New and replacement sanitary 
sewage systems shall be designed to minimize or eliminate 
infiltration of floodwaters into systems and discharges from 
systems into floodwaters in accordance with the plumbing 
provisions of this code and Chapter 3 of the International 
Private Sewage Disposal Code. 

R324.1.7 Flood-resistant materials. Building materials 
used below the design flood elevation shall comply with the 
following: 

1. All wood, including floor sheathing, shall be pres- 
sure-preservative-treated in accordance with AWPA 
Ul for the species, product, preservative and end use 
or be the decay-resistant heartwood of redwood, 
black locust or cedars. Preservatives shall be listed in 
Section 4 of AWPA Ul. 

2. Materials and installation methods used for flooring 
and interior and exterior walls and wall coverings 
shall conform to the provisions of FEMA/FIA-TB 

R324.1.8 Manufactured housing. New or replacement 
manufactured housing shall be elevated in accordance with 
Section R324.2 and the anchor and tie-down requirements 
of Sections AE604 and AE605 of Appendix E shall apply. 
The foundation and anchorage of manufactured housing to 
be located in identified flood ways as established in Table 
R301.2(l) shall be designed and constructed in accordance 



with the applicable provisions in the International Building 
Code. 

R324.1.9 As-built elevation documentation. A registered 
design professional shall prepare and seal documentation of 
the elevations specified in Section R324.2 or R324.3. 

R324.2 Flood hazard areas (including A Zones). Areas that 
have been determined to be prone to flooding but not subject to 
high velocity wave action shall be designated as flood hazard 
areas. All buildings and structures constructed in whole or in 
part in flood hazard areas shall be designed and constructed in 
accordance with Sections R324.2.1 and R324.2.3. 

R324.2.1 Elevation requirements. 

1 . Buildings and structures shall have the lowest floors 
elevated to or above the design flood elevation. 

2. In areas of shallow flooding (AO Zones), buildings 
and structures shall have the lowest floor (including 
basement) elevated at least as high above the highest 
adjacent grade as the depth number specified in feet 
(mm) on the FIRM, or at least 2 feet (610 mm) if a 
depth number is not specified. 

3 . Basement floors that are below grade on all sides shall 
be elevated to or above the design flood elevation. 

Exception; Enclosed areas below the design flood eleva- 
tion, including basements whose floors are not below 
grade on all sides, shall meet the requirements of Section 
R324.2.2. 

R324.2.2 Enclosed area below design flood elevation. 

Enclosed areas, including crawl spaces, that are below the 
design flood elevation shall: 

1. Be used solely for parking of vehicles, building 
access or storage. 

2. Be provided with flood openings that meet the fol- 
lowing criteria: 

2.1. There shall be a minimum of two openings on 
different sides of each enclosed area; if a 
building has more than one enclosed area be- 
low the design flood elevation, each area shall 
have openings on exterior walls. 

2.2. The total net area of all openings shall be at 
least 1 square inch (645 mm^) for each square 
foot (0.093 m^) of enclosed area, or the open- 
ings shall be designed and the construction 
documents shall include a statement that the 
design and installation will provide for equal- 
ization of hydrostatic flood forces on exterior 
walls by allowing for the automatic entry and 
exit of floodwaters. 

2.3. The bottom of each opening shall be 1 foot 
(305 mm) or less above the adjacent ground 
level. 

2.4. Openings shall be at least 3 inches (76 mm) in 
diameter. 

2.5. Any louvers, screens or other opening covers 
shall allow the automatic flow of floodwaters 
into and out of the enclosed area. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



63 



BUILDING PLANNING 



2.6. Openings installed in doors and windows, that 
meet requirements 2.1 through 2.5, are ac- 
ceptable; however, doors and windows with- 
out installed openings do not meet the 
requirements of this section. 

R324.2.3 Foundation design and construction. Founda- 
tion walls for all buildings and structures erected in flood 
hazard areas shall meet the requirements of Chapter 4. 

Exception: Unless designed in accordance with Section 
R404: 

1. The unsupported height of 6-inch (152 mm) plain 
masonry walls shall be no more than 3 feet (914 
mm). 

2. The unsupported height of 8-inch (203 mm) plain 
masonry walls shall be no more than 4 feet (1219 
mm). 

3. The unsupported height of 8-inch (203 mm) rein- 
forced masonry walls shall be no more than 8 feet 
(2438 mm). 

For the purpose of this exception, unsupported 
height is the distance from the finished grade of the 
under-floor space and the top of the wall. 

R324.3 Coastal high-hazard areas (including V Zones). 

Areas that have been determined to be subject to wave heights 
in excess of 3 feet (914 mm) or subject to high- velocity wave 
action or wave-induced erosion shall be designated as coastal 
high-hazard areas. Buildings and structures constructed in 
whole or in part in coastal high-hazard areas shall be desig- 
nated and constructed in accordance with Sections R324.3.1 
through R324.3.6. 

R324.3.1 Location and site preparation. 

1 . Buildings and structures shall be located landward of 
the reach of mean high tide. 

2. For any alteration of sand dunes and mangrove stands 
the building official shall require submission of an 
engineering analysis which demonstrates that the pro- 
posed alteration will not increase the potential for 
flood damage. 

R324.3.2 Elevation requirements. 

1. All buildings and structures erected within coastal 
high hazard areas shall be elevated so that the lowest 
portion of all structural members supporting the low- 
est floor, with the exception of mat or raft founda- 
tions, pihng, pile caps, columns, grade beams and 
bracing, is located at or above the design flood eleva- 
tion. 

2. Basement floors that are below grade on all sides are 
prohibited. 

3. The use of fill for structural support is prohibited. 

4. The placement of fill beneath buildings and structures 
is prohibited. 

Exception: Walls and partitions enclosing areas below 
the design flood elevation shall meet the requirements of 
Sections R324.3.4 and R324.3.5. 



R324.3.3 Foundations. Buildings and structures erected in 
coastal high-hazard areas shall be supported on pilings or 
columns and shall be adequately anchored to those pilings 
or columns. Pilings shall have adequate soil penetrations to 
resist the combined wave and wind loads (lateral and uplift). 
Water loading values used shall be those associated with the 
design flood. Wind loading values shall be those required by 
this code. Pile embedment shall include consideration of 
decreased resistance capacity caused by scour of soil strata 
surrounding the pihng. Pile systems design and installation 
shall be certified in accordance with Section B1324.3.6. Mat, 
raft or other foundations that support columns shall not be 
permitted where soil investigations that are required in 
accordance with Section R401.4 indicate that soil material 
under the mat, raft or other foundation is subject to scour or 
erosion from wave-velocity flow conditions. Slabs, pools, 
pool decks and walkways shall be located and constructed 
to be structurally independent of buildings and structures 
and their foundations to prevent transfer of flood loads to 
the buildings and structures during conditions of flooding, 
scour or erosion from wave- velocity flow conditions, unless 
the buildings and structures and their foundation are 
designed to resist the additional flood load. 

R324.3.4 Walls below design flood elevation. Walls and 
partitions are permitted below the elevated floor, provided 
that such walls and partitions are not part of the structural 
support of the building or structure and: 

1 . Electrical, mechanical, and plumbing system compo- 
nents are not to be mounted on or penetrate through 
walls that are designed to break away under flood 
loads; and 

2. Are constructed with insect screening or open lattice; 
or 

3. Are designed to break away or collapse without caus- 
ing collapse, displacement or other structural damage 
to the elevated portion of the building or supporting 
foundation system. Such walls, framing and connec- 
tions shall have a design safe loading resistance of not 
less than 10 (479 Pa) and no more than 20 pounds per 
square foot (958 Pa); or 

4. Where wind loading values of this code exceed 20 
pounds per square foot (958 Pa), the construction 
documents shall include documentation prepared and 
sealed by a registered design professional that: 

4.1. The walls and partitions below the design 
flood elevation have been designed to col- 
lapse from a water load less than that which 
would occur during the design flood. 

4.2. The elevated portion of the building and sup- 
porting foundation system have been designed 
to withstand the effects of wind and flood loads 
acting simultaneously on all building compo- 
nents (structural and nonstructural). Water 
loading values used shall be those associated 
with the design flood. Wind loading values 
shall be those required by this code. 



64 



2006 INTERNATIONAL RESIDENTIAL CODE** 



BUILDING PLANNING 



R324.3.5 Enclosed areas below design flood elevation. 

Enclosed areas below the design flood elevation shall be 
used solely for parking of vehicles, building access or stor- 
age. 

R324.3.6 Construction documents. The construction doc- 
uments shall include documentation that is prepared and 
sealed by a registered design professional that the design 
and methods of construction to be used meet the applicable 
criteria of this section. 



2006 INTERNATIONAL RESIDENTIAL CODE® 65 



66 2006 INTERNATIONAL RESIDENTIAL CODE® 



CHAPTER 4 

FOUNDATIONS 



SECTION R401 
GENERAL 

R401.1 Application. The provisions of this chapter shall control 
the design and construction of the foundation and foundation 
spaces for all buildings. In addition to the provisions of this 
chapter, the design and construction of foundations in areas 
prone to flooding as established by Table R301.2(l) shall meet 
the provisions of Section R324. Wood foundations shall be 
designed and installed in accordance with AF&PA Report No. 7. 

Exception: The provisions of this chapter shall be permit- 
ted to be used for wood foundations only in the following 
situations: 

1 . In buildings that have no more than two floors and a 
roof. 

2. When interior basement and foundation walls are con- 
structed at intervals not exceeding 50 feet (15 240 mm). 

I Wood foundations in Seismic Design Category Dq, Dj or Dj 
shall be designed in accordance with accepted engineering 
practice. 

R401.2 Requirements. Foundation construction shall be 
capable of accommodating all loads according to Section R301 
and of transmitting the resulting loads to the supporting soil. 
Fill soils that support footings and foundations shall be 
designed, installed and tested in accordance with accepted 
engineering practice. Gravel fill used as footings for wood and 
precast concrete foundations shall comply with Section R403. 

R401.3 Drainage. Surface drainage shall be diverted to a 
storm sewer conveyance or other approved point of collection 
so as to not create a hazard. Lots shall be graded to drain surface 
water away from foundation walls. The grade shall fall a mini- 
mum of 6 inches (152 mm) within the first 10 feet (3048 mm). 

Exception: Where lot lines, walls, slopes or other physical 
barriers prohibit 6 inches (152 mm) of fall within 10 feet 
(3048 mm), the final grade shall slope away from the foun- 
dation at a minimum slope of 5 percent and the water shall 
be directed to drains or swales to ensure drainage away from 
the structure. Swales shall be sloped a minimum of 2 percent 
when located within 10 feet (3048 mm) of the building 
foundation. Impervious surfaces within 10 feet (3048 mm) 
of the building foundation shall be sloped a minimum of 2 
percent away from the building. 

R401.4 Soil tests. In areas likely to have expansive, compress- 
ible, shifting or other unknown soil characteristics, the building 
official shall determine whether to require a soil test to deter- 
mine the soil's characteristics at a particular location. This test 
shall be made by an approved agency using an approved 
method. 

R401.4.1 Geotechnical evaluation. In lieu of a complete 
geotechnical evaluation, the load-bearing values in Table 
R401.4.1 shall be assumed. 



TABLE R401. 4.1 

PRESUMPTIVE LOAD-BEARING VALUES OF 

FOUNDATION MATERIALS^ 



CLASS OF MATERIAL 


LOAD-BEARING 

PRESSURE 

(pounds per square foot) 


Crystalline bedrock 


12,000 


Sedimentary and foliated rock 


4,000 


Sandy gravel and/or gravel (GW and GP) 


3,000 


Sand, silty sand, clayey sand, silty gravel 

and clayey gravel 

(SW, SP, SM, SC, GM and GC) 


2,000 


Clay, sandy clay, silty clay, clayey silt, silt 

and sandy silt 

(CL, ML, MH and CH) 


1,500"^ 



For SI; 1 pound per square foot = 0.0479 kPa. 

a. When soil tests are required by Section R401 .4, the allowable bearing capaci- 

ties of the soil shall be part of the recommendations. 

b. Where the building official determines that in-place soils with an allowable 
bearing capacity of less than 1 ,500 psf are likely to be present at the site, the 
allowable bearing capacity shall be determined by a soils investigation. 

R401.4.2 Compressible or shifting soil. Instead of a complete 
geotechnical evaluation, when top or subsoils are compressible 
or shifting, they shall be removed to a depth and width suffi- 
cient to assure stable moisture content in each active zone and 
shall not be used as fill or stabilized within each active zone by 
chemical, dewatering or presaturation. 

SECTION R402 
MATERIALS 

R402.1 Wood foundations. Wood foundation systems shall be 
designed and installed in accordance with the provisions of this 
code. 

R402.1.1 Fasteners. Fasteners used below grade to attach 
plywood to the exterior side of exterior basement or crawl- 
space wall studs, or fasteners used in knee wall construc- 
tion, shall be of Type 304 or 316 stainless steel. Fasteners 
used above grade to attach plywood and all lumber-to-lum- 
ber fasteners except those used in knee wall construction 
shall be of Type 304 or 316 stainless steel, silicon bronze, 
copper, hot-dipped galvanized (zinc coated) steel nails, or 
hot- tumbled galvanized (zinc coated) steel nails. Electro- 
galvanized steel nails and galvanized (zinc coated) steel sta- 
ples shall not be permitted. 

R402.1.2 Wood treatment. All lumber and plywood shall 
be pressure-preservative treated and dried after treatment in 
accordance with AWPA Ul (Commodity Specification A, 
Use Category 4B and Section 5.2), and shall bear the label of 
an accredited agency. Where lumber and/or plywood is cut 
or drilled after treatment, the treated surface shall be field 
treated with copper naphthenate, the concentration of which 
shall contain a minimum of 2 percent copper metal, by 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



67 



FOUNDATIONS 



repeated brushing, dipping or soaking until the wood 
absorbs no more preservative. 

R402.2 Concrete. Concrete shall have a minimum specified 

(compressive strength of //, as shown in Table R402.2. Con- 
crete subject to moderate or severe weathering as indicated in 
Table R301.2(l) shall be air entrained as specified in Table 
R402.2. The maximum weight of fly ash, other pozzolans, sil- 

Iica fume, slag or blended cements that is included in concrete 
mixtures for garage floor slabs and for exterior porches, carport 
slabs and steps that will be exposed to deicing chemicals shall 
not exceed the percentages of the total weight of cementitious 
I materials specified in Section 4.2.3 of ACI 318. Materials used 
to produce concrete and testing thereof shall comply with the 
applicable standards listed in Chapter 3 of ACI 318. 

R402.3 Precast concrete. Approved precast concrete founda- 
tions shall be designed and installed in accordance with the 
provisions of this code and the manufacturer's installation 
instructions. 



SECTION R403 
FOOTINGS 

R403.1 General. All exterior walls shall be supported on con- 
tinuous sohd or fully grouted masonry or concrete footings, 
wood foundations, or other approved structural systems which 
shall be of sufficient design to accommodate all loads accord- 
ing to Section R301 and to transmit the resulting loads to the 
soil within the limitations as determined from the character of 
the soil. Footings shall be supported on undisturbed natural 
soils or engineered fill. 



TABLE R403.1 

MINIMUM WIDTH OF CONCRETE OR 

MASONRY FOOTINGS 

(inches)^ 





LOAD-BEARING VALUE OF SOIL (psf) 




1,500 


2,000 


3,000 


>4,000 


Conventional light-frame construction 


1 -story 


12 


12 


12 


12 


2-story 


15 


12 


12 


12 


3 -story 


23 


17 


12 


12 


4-inch brick veneer over light frame or 8-inch hollow concrete masonry 


1- story 


12 


12 


12 


12 


2-story 


21 


16 


12 


12 


3-story 


32 


24 


16 


12 


8-inch solid or fully grouted masonry 


1 -story 


16 


12 


12 


12 


2-story 


29 


21 


14 


12 


3 -story 


42 


32 


21 


16 



For Sr. 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. 
a. Where minimum footing width is 12 inches, use of a single wythe of solid or 
fully grouted 12-inch nominal concrete masonry units is permitted. 

R403.1.1 Minimum size. Minimum sizes for concrete and 
masonry footings shall be as set forth in Table R403.1 and 
Figure R403.1(l). The footing width, W, shall be based on 
the load-bearing value of the soil in accordance with Table 
R401.4.1. Spread footings shall be at least 6 inches (152 
mm) thick. Footing projections, P, shall be at least 2 inches 



TABLE R402.2 
MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE 



TYPE OR LOCATION OF CONCRETE CONSTRUCTION 


MINIMUM SPECIFIED COMPRESSIVE STRENGTH^ (f ^) 


Weathering Potential" 


Negligible 


Moderate 


Severe 


Basement walls, foundations and other concrete not 
exposed to the weather 


2,500 


2,500 


2,500'^ 


Basement slabs and interior slabs on grade, except 
garage floor slabs 


2,500 


2,500 


2,500^ 


Basement walls, foundation walls, exterior walls and 
other vertical concrete work exposed to the weather 


2,500 


3,000^1 


3,000'* 


Porches, carport slabs and steps exposed to the weather, 
and garage floor slabs 


2,500 


3,000'^'^'f 


3,500*^='^ 



For SI: 1 pound per square inch = 6.895 kPa. 

a. Strength at 28 days psi. 

b. See Table R301 .2(1) for weathering potential. 

c. Concrete in these locations that may be subject to freezing and thawing during construction shall be air-entrained concrete in accordance with Footnote d. 

d. Concrete shall be air-entrained. Total air content (percent by volume of concrete) shall be not less than 5 percent or more than 7 percent. 

e. See Section R402.2 for maximum cementitious materials content. 

f. For garage floors with a steel troweled finish, reduction of the total air content (percent by volume of concrete) to not less than 3 percent is permitted if the specified 
compressive strength of the concrete is increased to not less than 4,000 psi. 



68 



2006 INTERNATIONAL RESIDENTIAL CODE® 



FOUNDATIONS 



3.5 IN. MIN. 



V?y^ 



^ 


i, 


|l ° -* 

o°, 


\\\^ //// 



BEARING WALL 







////\\\ 

v// \\\^ 




1^ — w — H 



MONOLITHIC SLAB WITH 
INTEGRAL FOOTING 



1^ — W — M 



INTERIOR 



3.5 IN. MIN. 



^ 



A 



7//\\\v///\\\\f7? 
4^\\v/// A\v///T\v 

y//A\\ 
\\v 



*;^ 






k 



■w- 



GROUND SUPPORT SLAB 
WITH MASONRY WALL 
AND SPREAD FOOTING 



lC^^^^>>W 



Lf- 



INTERIOR 



■W- 



BASEMENT OR CRAWL SPACE 
WITH MASONRY WALL AND 
SPREAD FOOTING 



V^y'^^^o" 



^ 



INTERIOR 





'\ 

° 1 






„ o" 




p 




P 






;- .-- ..■ 


° ' . o 1 


O 






vv 


n 



BASEMENT OR CRAWL SPACE 
WITH CONCRETE WALL AND 
SPREAD FOOTING 



J^ 



INTERIOR 



W 



BASEMENT OR CRAWL SPACE 
WITH FOUNDATION WALL 
BEARING DIRECTLY ON SOIL 



For SI: 1 inch = 25.4 mm. 



FIGURE R403.1(1) 
CONCRETE AND MASONRY FOUNDATION DETAILS 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



69 



FOUNDATIONS 



□ PRESSURE-PRESERVATIVE TREATED 



FIELD^APPUED 2 x 6 IN. TOP PLATE 
2x6!N.TOPPLATe 



MIN, 3.5 IN. CONCRETE SLAB WITH 
VAPOR BARRIER AND OPTIONAL 
1 IN. SCREED BOARD 



SIN. — I 



4 IN. GRAVEL OR CRUSHED 
STONE FILL UNDER FLOOR 
(SEE SECTION R403.2) 




4 FT (MAX. BACKFILL) 



2x6 !N. STUD WALL INSULATED 
AS APPROPRIATE AND WARM SIDE 
VAPOR BARRIER 



1 IN. THICK PRESSURE-PRESERVATIVE 
TREATED LUMBER OR PLYWOOD STf^lP 
PROTECTING TOP OF POLYETHYLENE FILM 

ESSURE-PRESERVATiVE 
EATED PLYWOOD 
E TABLE R404.2.3) 

6 MIL POLYETHYLENE FILM 



6 MIL POLYETHYLENE FILM 
ON CRUSHED STONE OR 
GRAVEL BACKFILL 

FINISH GRADE SLOPE Vo IN. 
PER FOOT, MIN. 6 FT FROM 
WALL 



PRESSURE-PRES£F?VATIVE 
TREATED 2x6 IN. BOTTOM PLATE 



PRESSURE-PRESEF?VATIVE 
TREATED 2x8 IN. FOOTING PLATE 



For SL- 1 inch 25.4 = mm, 1 foot =304.8, 1 mil =0.0254 mm. 



FIGURE R403.1 (2) 
PERMANENT WOOD FOUNDATION BASEMENT WALL SECTION 



(51 mm) and shall not exceed the thickness of the footing. 
The size of footings supporting piers and columns shall be 
based on the tributary load and allowable soil pressure in 
accordance with Table R40 1.4.1. Footings for wood foun- 
dations shall be in accordance with the details set forth in 
Section R403.2, and Figures R403.1(2) and R403.1(3). 

R403.1.2 Continuous footing in Seismic Design Catego- 
ries Dq, Dj and Dj. The braced wall panels at exterior walls 
of buildings located in Seismic Design Categories Do, Dj 



and D2 shall be supported by continuous footings. All 
required interior braced wall panels in buildings with plan 
dimensions greater than 50 feet (15 240 mm) shall also be 
supported by continuous footings. 

R403.1.3 Seismic reinforcing. Concrete footings located in 
Seismic Design Categories Dq, Dj and D2, as established in 
Table R301.2(l), shall have minimum reinforcement. Bot- 
tom reinforcement shall be located a minimum of 3 inches 
(76 mm) clear from the bottom of the footing. 



70 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FOUNDATIONS 



n PRESSURE-PRESERVATIVE TREATED 



FLOOR JO!S 



6 MIL POLYETHYLENE FILM 




6 IN. 



1'7// \\\N '///%\\\ ■;/// s\\\'/// 
|\\\v/;// v\\v<'7/ xw^ ///f ws" 

^v '''*/ -^ \V\'' ////wv //:// \\\^ 

/// \\\! //// ^^\'■ //// \\\'^=~_H 

(S\\ ''/VyA^\^^ /^\\\//^■^^ 



. FIELD-APPLIED 2x6 IN. TOP PLATE 
FLASHING 
. 2 X 6 IN. TOP PLATE 




'/// A Y// 
'Mi 



6 IN. GRAVEL OR CRUSHED STONE ' 
{SEE SECTION R403.2) 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm. 




FINISH GRADE SLOPE V, IN. 
PER FOOT. MIN. 6 FT FROM 
WALL 



PRESSURE-PRESERVATIVE 
TREATED 2x6 IN. STUD WALL 

PRESSURE-PRESERVATIVE 
TREATED PLYWOOD 
(SEE TABLE R404.2.3) 



PRESSURE-PRESERVATIVE 
TREATED 2 x 6 IN. BOTTOM PLATE 



PRESSURE-PRESERVATIVE 
TREATED 2 x 8 IN. FOOTING PLATE 



BELOW FROST LINE 



FIGURE R403.1(3) 
PERMANENT WOOD FOUNDATION CRAWL SPACE SECTION 



In Seismic Design Categories Dq, Dj and Dj where a con- 
struction joint is created between a concrete footing and a 
stem wall, a minimum of one No. 4 bar shall be installed at 
not more than 4 feet (1219 mm) on center. The vertical bar 
shall extend to 3 inches (76 mm) clear of the bottom of the 
footing, have a standard hook and extend a minimum of 14 
inches (357 mm) into the stem wall. 

In Seismic Design Categories Dq, Dj and Dj where a 
grouted masonry stem wall is supported on a concrete foot- 
ing and stem wall, a minimum of one No. 4 bar shall be 
installed at not more than 4 feet on center. The vertical bar 
shall extend to 3 inches (76 mm) clear of the bottom of the 
footing and have a standard hook. 

In Seismic Design Categories Dq, Dj and D2 masonry 
stem walls without solid grout and vertical reinforcing are 
not permitted. 

Exception: In detached one- and two-family dwellings 
which are three stories or less in height and constructed 
with stud bearing walls, plain concrete footings without 
longitudinal reinforcement supporting walls and isolated 
plain concrete footings supporting columns or pedestals 
are permitted. 

R403.1.3.1 Foundations with stemwalls. Foundations 
with stem walls shall have installed a minimum of one 
No. 4 bar within 12 inches (305 mm) of the top of the wall 



and one No. 4 bar located 3 inches (76 mm) to 4 inches | 
(102 mm) from the bottom of the footing. 

R403.1.3.2 Slabs-on-ground with turned-down foot- 
ings. Slabs-on-ground with turned-down footings shall 
have a minimum of one No. 4 bar at the top and bottom of 
the footing. 

Exception: For slabs-on-ground cast monolithically 
with a footing, one No. 5 bar or two No. 4 bars shall be 
located in the middle third of the footing depth. 

R403.1.4 Minimum depth. All exterior footings shall be 
placed at least 12 inches (305 mm) below the undisturbed 
ground surface. Where applicable, the depth of footings shall 
also conform to Sections R403. 1.4.1 through R403. 1.4.2. 

R403.1.4.1 Frost protection. Except where otherwise 
protected from frost, foundation walls, piers and other 
permanent supports of buildings and structures shall be 
protected from frost by one or more of the following 
methods: 

1 . Extended below the frost line specified in Table 
R301.2.(l); 

2. Constructing in accordance with Section R403.3; 

3. Constructing in accordance with ASCE 32; or | 

4. Erected on solid rock. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



71 



FOUNDATIONS 



Exceptions: 

1. Protection of freestanding accessory 
structures with an area of 600 square feet 
(56 m^) or less, of light-framed construc- 
tion, with an eave height of 10 feet (3048 
mm) or less shall not be required. 

2. Protection of freestanding accessory 
structures with an area of 400 square feet 
(37 m^) or less, of other than light-framed 
construction, with an eave height of 10 
feet (3048 mm) or less shall not be 
required. 

3. Decks not supported by a dwelling need 
not be provided with footings that extend 
below the frost line. 

Footings shall not bear on frozen soil unless the frozen 
condition is permanent. 

R403.1.4.2 Seismic conditions. In Seismic Design Cat- 
egories Dq, Dj and D2, interior footings supporting bear- 
ing or bracing walls and cast monolithically with a slab 
on grade shall extend to a depth of not less than 12 inches 
(305 mm) below the top of the slab. 

R403.1.5 Slope. The top surface of footings shall be level. 
The bottom surface of footings shall not have a slope 
exceeding one unit vertical in 10 units horizontal (10-per- 
cent slope). Footings shall be stepped where it is necessary 
to change the elevation of the top surface of the footings or 
where the slope of the bottom surface of the footings will 
exceed one unit vertical in ten units horizontal (10-percent 
slope). 

R403.1.6 Foundation anchorage. When braced wall pan- 
els are supported directly on continuous foundations, the 
wall wood sill plate or cold-formed steel bottom track shall 
be anchored to the foundation in accordance with this sec- 
tion. 

The wood sole plate at exterior walls on monolithic 
slabs and wood sill plate shall be anchored to the founda- 
tion with anchor bolts spaced a maximum of 6 feet (1829 
mm) on center. There shall be a minimum of two bolts per 
plate section with one bolt located not more than 12 inches 
(305 mm) or less than seven bolt diameters from each end 
of the plate section. In Seismic Design Categories Dq, Dj 
and D2, anchor bolts shall be spaced at 6 feet ( 1 829 mm) on 
center and located within 12 inches (305 mm) of the ends 
of each plate section at interior braced wall lines when 
required by Section R602. 10.9 to be supported on a contin- 
uous foundation. Bolts shall be at least V2 inch (13 mm) in 
diameter and shall extend a minimum of 7 inches (178 
mm) into masonry or concrete. Interior bearing wall sole 
plates on monolithic slab foundation shall be positively 
anchored with approved fasteners. A nut and washer shall 
be tightened on each bolt of the plate. Sills and sole plates 
shall be protected against decay and termites where 
required by Sections R319 and R320. Cold-formed steel 
framing systems shall be fastened to the wood sill plates or 
anchored directly to the foundation as required in Section 
R505.3.1orR603.1.1. 



Exceptions: 

1. Foundation anchorage, spaced as required to pro- 
vide equivalent anchorage to Vj-inch-diameter (13 
mm) anchor bolts. 

2. Walls 24 inches (610 mm) total length or shorter 
connecting offset braced wall panels shall be 
anchored to the foundation with a minimum of one 
anchor bolt located in the center third of the plate 
section and shall be attached to adjacent braced 
wall panels per Figure R602.10.5 at comers. 

3. Walls 12 inches (305 mm) total length or shorter 
connecting offset braced wall panels shall be per- 
mitted to be connected to the foundation without 
anchor bolts. The wall shall be attached to adjacent 
braced wall panels per Figure R602.10.5 at cor- 
ners. 

R403.1.6.1 Foundation anchorage in Seismic Design 
Categories C, Dq, D^ and Dj. In addition to the require- 
ments of Section R403.1.6, the following requirements 
shall apply to wood light-frame structures in Seismic 
Design Categories Dq, D, and D2 and wood light-frame 
townhouses in Seismic Design Category C. 

1. Plate washers conforming to Section R602.11.1 
shall be provided for all anchor bolts over the full 
length of required braced wall lines. Properly sized 
cut washers shall be permitted for anchor bolts in 
wall lines not containing braced wall panels. 

2. Interior braced wall plates shall have anchor bolts 
spaced at not more than 6 feet (1 829 mm) on center 
and located within 12 inches (305 mm) of the ends 
of each plate section when supported on a continu- 
ous foundation. 

3. Interior bearing wall sole plates shall have anchor 
bolts spaced at not more than 6 feet (1829 mm) on 
center and located within 12 inches (305 mm) of 
the ends of each plate section when supported on a 
continuous foundation. 

4. The maximum anchor bolt spacing shall be 4 feet 
(1219 mm) for buildings over two stories in height. 

5. Stepped cripple walls shall conform to Section 
R602.11.3. 

6. Where continuous wood foundations in accor- 
dance with Section R404.2 are used, the force 
transfer shall have a capacity equal to or greater 
than the connections required by Section 
R602. 11.1 or the braced wall panel shall be con- 
nected to the wood foundations in accordance with 
the braced wall panel-to-floor fastening require- 
ments of Table R602.3(l). 

R403.1.7 Footings on or adjacent to slopes. The place- 
ment of buildings and structures on or adjacent to slopes 
steeper than 1 unit vertical in 3 units horizontal (33.3-per- 
cent slope) shall conform to Sections R403. 1.7.1 through 
R403.1.7.4. 

R403. 1.7.1 Building clearances from ascending 
slopes. In general, buildings below slopes shall be set a 



72 



2006 INTERNATIONAL RESIDEENTIAL CODE^^ 



FOUNDATIONS 




For SI: 1 foot = 304.8 mm. 



H/2 BUT NEED NOT EXCEED 15 FT MAX 



FIGURE R403.1 .7.1 
FOUNDATION CLEARANCE FROM SLOPES 



sufficient distance from the slope to provide protection 
from slope drainage, erosion and shallow failures. 
Except as provided in Section R403.1.7.4 and Figure 
R403. 1.7.1, the following criteria will be assumed to 
provide this protection. Where the existing slope is 
steeper than one unit vertical in one unit horizontal 
(100-percent slope), the toe of the slope shall be assumed 
to be at the intersection of a horizontal plane drawn from 
the top of the foundation and a plane drawn tangent to the 
slope at an angle of 45 degrees (0.79 rad) to the horizon- 
tal. Where a retaining wall is constructed at the toe of the 
slope, the height of the slope shall be measured from the 
top of the wall to the top of the slope. 

R403.1.7.2 Footing setback from descending slope 
surfaces. Footings on or adjacent to slope surfaces shall 
be founded in material with an embedment and setback 
from the slope surface sufficient to provide vertical and 
lateral support for the footing without detrimental settle- 
ment. Except as provided for in Section R403. 1.7.4 and 
Figure R403 . 1 .7 . 1 , the following setback is deemed ade- 
quate to meet the criteria. Where the slope is steeper than 
one unit vertical in one unit horizontal (100-percent 
slope), the required setback shall be measured from an 
imaginary plane 45 degrees (0.79 rad) to the horizontal, 
projected upward from the toe of the slope. 

R403.1.7.3 Foundation elevation. On graded sites, the 
top of any exterior foundation shall extend above the ele- 
vation of the street gutter at point of discharge or the inlet 
of an approved drainage device a minimum of 12 inches 
(305 mm) plus 2 percent. Alternate elevations are per- 
mitted subject to the approval of the building official, 
provided it can be demonstrated that required drainage to 
the point of discharge and away from the structure is pro- 
vided at all locations on the site. 

R403.1.7.4 Alternate setback and clearances. Alter- 
nate setbacks and clearances are permitted, subject to the 
approval of the building official. The building official is 
permitted to require an investigation and recommenda- 
tion of a qualified engineer to demonstrate that the intent 
of this section has been satisfied. Such an investigation 
shall include consideration of material, height of slope, 
slope gradient, load intensity and erosion characteristics 
of slope material. 



R403.1.8 Foundations on expansive soils. Foundation and 
floor slabs for buildings located on expansive soils shall be 
designed in accordance with Section 1805.8 of the Interna- 
tional Building Code. 

Exception: Slab-on-ground and other foundation sys- 
tems which have performed adequately in soil conditions 
similar to those encountered at the building site are per- 
mitted subject to the approval of the building official. 

R403.1.8.1 Expansive soils classifications. Soils meet- 
ing all four of the following provisions shall be consid- 
ered expansive, except that tests to show compliance 
with Items 1 , 2 and 3 shall not be required if the test pre- 
scribed in Item 4 is conducted: 

1 . Plasticity Index (PI) of 1 5 or greater, determined in 
accordance with ASTM D 4318. 

2. More than 10 percent of the soil particles pass a 
No. 200 sieve (75 mm), determined in accordance 
with ASTM D 422. 

3. More than 10 percent of the soil particles are less 
than 5 micrometers in size, determined in accor- 
dance with ASTM D 422. 

4. Expansion Index greater than 20, determined in 
accordance with ASTM D 4829. 

R403.2 Footings for wood foundations. Footings for wood 
foundations shall be in accordance with Figures R403 . 1 (2) and 
R403.1(3). Gravel shall be washed and well graded. The maxi- 
mum size stone shall not exceed V4 inch (19.1 mm). Gravel 
shall be free from organic, clayey or silty soils. Sand shall be 
coarse, not smaller than Vig-inch (1.6 mm) grains and shall be 
free from organic, clayey or silty soils. Crushed stone shall 
have a maximum size of V2 inch (12.7 mm). 

R403.3 Frost protected shallow foundations. For buildings 
where the monthly mean temperature of the building is main- 
tained at a minimum of 64°F (18°C), footings are not required 
to extend below the frost line when protected from frost by 
insulation in accordance with Figure R403.3(l) and Table 
R403.3. Foundations protected from frost in accordance with 
Figure R403.3(l) and Table R403.3 shall not be used for 
unheated spaces such as porches, utility rooms, garages and 
carports, and shall not be attached to basements or crawl spaces 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



73 



FOUNDATIONS 



TABLE R403.3 
MINIMUM INSULATION REQUIREMENTS FOR FROST-PROTECTED FOOTINGS IN HEATED BUILDINGS^ 



AIR FREEZING 
INDEX ("F-days)" 


VERTICAL 
INSULATION 
ff-VALUE^'" 


HORIZONTAL INSULATION fl-VALUE^'^ 


HORIZONTAL INSULATION DIMENSIONS 
PER FIGURE R403.3(1) (Inches) 


Along walls 


At corners 


A 


B 


C 


1,500 or less 


4.5 


Not required 


Not required 


Not required 


Not required 


Not required 


2,000 


5.6 


Not required 


Not required 


Not required 


Not required 


Not required 


2,500 


6.7 


1.7 


4.9 


12 


24 


40 


3,000 


7.8 


6.5 


8.6 


12 


24 


40 


3,500 


9.0 


8.0 


11.2 


24 


30 


60 


4,000 


10.1 


10.5 


13.1 


24 


36 


60 



a. Insulation requirements are for protection against frost damage in heated buildings: Greater values may be required to meet energy conservation standards. Inter- 
polation between values is permissible. 

b. See Figure R403.3(2) for Air Freezing Index values. 

c. Insulation materials shall provide the stated minimum /?-values under long-term exposure to moist, below-ground conditions in freezing climates. The following 
/?-values shall be used to determine insulation thicknesses required for this application; Type 11 expanded polystyrene — 2.4R per inch; Type IV extruded polysty- 
rene — 4.5R per inch; Type VI extruded polystyrene — 4.57? per inch; Type IX expanded polystyrene — 3 .2/? per inch; Type X extruded polystyrene — 4.5/? per inch. 

d. Vertical insulation shall be expanded polystyrene insulation or extruded polystyrene insulation. 

e. Horizontal insulation shall be extruded polystyrene insulation. 



INSULATION DETAIL 



FLja^SHING PER SECTION R703.8 

INSULATION PROTECTION PER SECTION R403.3.2 
SLOPE FINAL GRADE PER SECTION R403.3.3. 



12 IN. MIN 



NOMINAL 4 IN. SCREENED AND 
WASHED GRAVEL OR CRUSHED 
STONE, DRAINED PER SECTION 
R403.3.3 




( - - \ J o\, o .^ i\v\ 
'?f» 1__X? i_ ° ?.^/A 

^\\\\ '/// \\\\v//%.y// N% y// s\\\v// \\\^ 



^SLAB-ON-GROUND FOUNDATION FLOOR 
PER SECTIONS R403.1 AND R506 



Aw//// 

////\\v 
WW/// 

y//\\v 

WW/// 
y//\\v 
WW/// 



' VERTICAL WALL INSULATIONS 
HORIZONTAL INSULATION^ 



HORIZONTAL INSULATION PLAN 




For SI: 1 inch = 25.4 mm. 

a. See Table R403.3 for required dimensions and R-values for vertical and horizontal insulation. 

FIGURE R403.3(1) 
INSULATION PLACEMENT FOR FROST-PROTECTED FOOTINGS IN HEATED BUILDINGS 



74 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



o 
o 

D 

m 




For SI: °C = [(°F)-32]/l .8. 

NOTE: The air- freezing index is defined as cumulative degree days below 32°F. It is used as a measure of the combined magnitude and duration of air temperature below freezing. The index was computed over a 

12-month period (July-June) for each of the 3,044 stations used in the above analysis. Data from the 1951-80 period were fitted to a Weibull probabihty distribution to produce an estimate of the 100-year return 

period. 

FIGURE R403.3(2) 

AIR-FREEZING INDEX 

AN ESTIMATE OF THE 100-YEAR RETURN PERIOD 



O 

c 
z 
a 

> 

H 
O 

z 

CO 



FOUNDATIONS 



INSULATION DETAIL 



FLASHING PER SECTION R703.8 

INSULATION PROTECTION PER SECTION SECTION R403.3.2 

FINISH GRADE OR CONCRETE- 
SLAB OF ADJACENT UNHEATED 
SLAB-ON-GROUND STRUCTURE 



BEAM LINTEL OR CANTILEVER 
TO CARRY LOAD OVER 
NON LOAD-BEARING 
INSULATION 



CONCRETE MASONRY OR 
PERMANENT WOOD 
FOUNDATION GRADE BEAM 
OR WALL OF ADJACENT 
UNHEATED STRUCTURE 



FOOTING AS REQUIRED 




FROST PROTECTED SHALLOW 
FOUNDATION SLAB-ON-GRADE 
FLOOR PER SECTION 403.3 



NOMINAL 4 IN. SCREEN AND 

WASHED GRAVEL OR CRUSHED STONE, 

DRAINED PER SECTION R403.3.3 

VERTICAL WALL INSULATION ^ 

HORIZONTAL INSULATION ^ 



HORIZONTAL INSULATION PLAN 



ATTACHED SLAB 
FOUNDATION OF UNHEATED 
SLAB-ON-GROUND 
STRUCTURE PER 
SECTION R403.1 
AND R403.2 



-FOUNDATION PERIMETER 



HEATED BUILDING AREA 



t 



For SI: 1 inch = 25.4 mm. 

a. See Table R403.3 for required dimensions and7?-values for vertical and horizontal insulation. 

FIGURE R403.3(3) 

INSULATION PLACEMENT FOR FROST-PROTECTED FOOTINGS 

ADJACENT TO UNHEATED SLAB-ON-GROUND STRUCTURE 



76 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FOUNDATIONS 



that are not maintained at a minimum monthly mean tempera- 
ture of 64°F (18°C). 

Materials used below grade for the purpose of insulating 
footings against frost shall be labeled as complying with 
ASTM C 578. 

R403.3.1 Foundations adjoining frost protected shallow 
foundations. Foundations that adjoin frost protected shal- 
low foundations shall be protected from frost in accordance 
with Section R403. 1.4. 

R403.3.1.1 Attachment to unheated slab-on-ground 
structure. Vertical wall insulation and horizontal insula- 
tion of frost protected shallow foundations that adjoin a 
slab-on-ground foundation that does not have a monthly 
mean temperature maintained at a minimum of 64°F 
(18°C), shall be in accordance with Figure R403.3(3) 
and Table R403.3. Vertical wall insulation shall extend 
between the frost protected shallow foundation and the 
adjoining slab foundation. Required horizontal insula- 
tion shall be continuous under the adjoining slab founda- 
tion and through any foundation walls adjoining the frost 
protected shallow foundation. Where insulation passes 
through a foundation wall, it shall either be of a type 
complying with this section and having bearing capacity 
equal to or greater than the structural loads imposed by 
the building, or the building shall be designed and con- 
structed using beams, lintels, cantilevers or other means 
of transferring building loads such that the structural 
loads of the building do not bear on the insulation. 

R403.3.1.2 Attachment to heated structure. Where a 
frost protected shallow foundation abuts a structure that 
has a monthly mean temperature maintained at a mini- 



mum of 64°F (18°C), horizontal insulation and vertical 
wall insulation shall not be required between the frost 
protected shallow foundation and the adjoining struc- 
ture. Where the frost protected shallow foundation abuts 
the heated structure, the horizontal insulation and verti- 
cal wall insulation shall extend along the adjoining foun- 
dation in accordance with Figure R403.3(4) a distance of 
not less than Dimension A in Table R403.3. 

Exception: Where the frost protected shallow foun- 
dation abuts the heated structure to form an inside cor- 
ner, vertical insulation extending along the adjoining 
foundation is not required. 

R403.3.2 Protection of horizontal insulation below 
ground. Horizontal insulation placed less than 12 inches 
(305 mm) below the ground surface or that portion of hori- 
zontal insulation extending outward more than 24 inches 
(610 mm) from the foundation edge shall be protected 
against damage by use of a concrete slab or asphalt paving 
on the ground surface directly above the insulation or by 
cementitious board, plywood rated for below-ground use, 
or other approved materials placed below ground, directly 
above the top surface of the insulation. 

R403.3.3 Drainage. Final grade shall be sloped in accor- 
dance with Section R401.3. In other than Group I Soils, as 
detailed in Table R405.1, gravel or crushed stone beneath 
horizontal insulation below ground shall drain to daylight or 
into an approved sewer system. 

R403.3.4 Termite damage. The use of foam plastic in 
areas of "very heavy" termite infestation probability shall 
be in accordance with Section R320.5. 



— — — A 



FOUNDATION OF HEATED 
STRUCTURE PER 
SECTIONS R403.1, 
R403.2,ANDR403,3.2.1 



-FROST-PROTECTION — 
SHALLOW FOUNDATION 



INSIDE CORNER 



FIGURE R403.3(4) 

INSULATION PLACEMENT FOR FROST-PROTECTED 

FOOTINGS ADJACENT TO HEATED STRUCTURE 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



77 



FOUNDATIONS 



SECTION R404 
FOUNDATION AND RETAINING WALLS 

R404,l Concrete and masonry foundation walls. Concrete 
and masonry foundation walls shall be selected and con- 
structed in accordance with the provisions of Section R404 or 
in accordance with ACI 3 1 8, ACI 332, NCMA TR68-A or ACI 
530/ASCE 5/TMS 402 or other approved structural standards. 
When ACI 3 1 8, ACI 332 or ACI 530/ASCE 5/TMS 402 or the 
provisions of Section R404 are used to design concrete or 
masonry foundation walls, project drawings, typical details 
and specifications are not required to bear the seal of the archi- 
tect or engineer responsible for design, unless otherwise 
required by the state law of the jurisdiction having authority. 



Foundation walls that meet all of the following shall be con- 
sidered laterally supported: 

1. Full basement floor shall be 3.5 inches (89 mm) thick 
concrete slab poured tight against the bottom of the foun- 
dation wall. 

2. Floor joists and blocking shall be connected to the sill plate 
at the top of wall by the prescriptive method called out in 
Table R404.1(l), or; shall be connected with an approved 
connector with Msted capacity meeting Table R404.1(l). 

3. Bolt spacing for the sill plate shall be no greater than per 
Table R404. 1(2). 

4. Floor shall be blocked perpendicular to the floor joists. 
Blocking shall be full depth within two joist spaces of the 



TABLE R404.1(1) 
TOP REACTIONS AND PRESCRIPTIVE SUPPORT FOR FOUNDATION WALLS^ 



MAXIMUM WALL HEIGHT 
(feet) 


MAXIMUM UNBALANCED 
BACKFILL HEIGHT (feet) 


HORIZONTAL REACTION TO TOP (pif) 


Soil Classes 
(Letter indicates connection types'') 


GW, GP, SW and 
SP soils 


GM, GC, SM-SC 
and ML soils 


SC, MH, ML-CL 
and inorganic CL soils 


7 


4 


45.7 
A 


68.6 

A 


91.4 

A 


5 


89.3 
A 


133.9 
B 


178.6 
B 


6 


154.3 
B 


231.4 
C 


308.6 
C 


7 


245.0 
C 


367.5 
C 


490.0 
D 


8 


4 


40.0 

A 


60.0 

A 


80.0 
A 


5 


78.1 

A 


117.2 
B 


156.3 
B 


6 


135.0 
B 


202.5 
B 


270.0 
C 


7 


214.0 
B 


321.6 
C 


428.8 
C 


8 


320.0 
C 


480.0 
C 


640.0 
D 


9 


4 


35.6 

A 


53.3 

A 


71.1 

A 


5 


69.4 
A 


104.2 
B 


138.9 
B 


6 


120.0 
B 


180.0 
B 


240.0 
C 


7 


190.6 
B 


285.8 
C 


381.1 
C 


8 


284.4 
C 


426.7 
C 


568.9 
D 


9 


405.0 
C 


607.5 
D 


810.0 
D 



For SI: 1 foot - 304.8 mm, 1 pound = 0.454 kg, 1 plf = pounds per linear foot = 1.488 kg/m. 

a. Loads are pounds per linear foot of wall. Prescriptive options are limited to maximum joist and blocking spacing of 24 inches on center 

b. Prescriptive Support Requirements: 



Type 

A 
B 
C 

D 



78 



Joist/blocking Attachment Requirement 

3-8d per joist per Table R602.3(l). 

1-20 gage angle clip each joist with 5-8d per leg. 

l-V4-inch thick steel angle. Horizontal leg attached to sill bolt adjacent to joist/blocking, vertical leg attached to joist/blocking with V2-inch 

minimum diameter bolt. ' 

2-V4-inch thick steel, angles, one on each side of joist/blocking. Attach each angle to adjacent sill bolt through horizontal leg. Bolt to joist/blocking 

with V2-inch minimum diameter bolt common to both angles. 

2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



FOUNDATIONS 



TABLER404.1(2) 
MAXIMUM PLATE ANCHOR-BOLT SPACING FOR SUPPORTED FOUNDATION WALL^ 



MAXIMUM WALL HEIGHT 
(feet) 


MAXIMUM UNBALANCED 
BACKFILL HEIGHT (feet) 


ANCHOR BOLT SPACING (inches) 


Soil Classes 


GW, GP, SW 
and SP soils 


GM, GC, SM-SC 
and ML soils 


SC, MH, ML-CL 
and inorganic CL soils 


7 


4 

5 
6 
7 


72 
44 
26 
16 


58 
30 
17 
11 


43 
22 
13 
8 


8 


4 
5 
6 

7 
8 


72 
51 
29 
18 
12 


66 

34 
20 
12 
8 


50 
25 
15 
9 
6 


9 


4 
5 
6 
7 
8 
9 


72 
57 
33 
21 
14 
10 


72 
38 
22 
14 
9 
7 


56 
29 
17 
10 

7 
5 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Spacing is based on V2-inch diameter anchor bolts. For Vg-inch diameter anchor bolts, spacing may be multiplied by 1 .27, with a maximum spacing of 72 inches. 



foundation wall, and be flat-blocked with minimum 
2-inch by 4-inch (5 1 mm by 1 02 mm) blocking elsewhere. 

5. Where foundation walls support unbalanced load on 
opposite sides of the building, such as a daylight base- 
ment, the building aspect ratio, LAV, shall not exceed the 
value specified in Table R404.1(3). For such foundation 
walls, the rim board shall be attached to the sill with a 20 
gage metal angle clip at 24 inches (610 mm) on center, 
with five 8d nails per leg, or an approved connector sup- 
plying 230 pounds per linear foot (3.36 kN/m) capacity. 

R404.1.1 Masonry foundation walls. Concrete masonry 
and clay masonry foundation walls shall be constructed as 
set forth in Table R404. 1.1(1), R404. 1 . 1 (2), R404. 1.1(3) or 
R404.1.1(4) and shall also comply with the provisions of 
Section R404 and the applicable provisions of Sections 
R606, R607 and R608. In Seismic Design Categories Dq, Di 
and Dj, concrete masonry and clay masonry foundation 
walls shall also comply with Section R404.1.4. Rubble 
stone masonry foundation walls shall be constructed in 
accordance with Sections R404.1.8 and R607.2.2. Rubble 
stone masonry walls shall not be used in Seismic Design 
Categories Do, D, and D2. 

R404.1.2 Concrete foundation walls. Concrete founda- 
tion walls shall be constructed as set forth in Table 
R404.1.1(5) and shall also comply with the provisions of 
Section R404 and the apphcable provisions of Section 
R402.2. In Seismic Design Categories Dq, Dj and D2, con- 
crete foundation walls shall also comply with Section 
R404.1.4. 

R4()4.1.3 Design required. Concrete or masonry founda- 
tion walls shall be designed in accordance with accepted 
engineering practice when either of the following condi- 
tions exists; 

1. Walls are subject to hydrostatic pressure from 
groundwater. 



2. Walls supporting more than 48 inches (1219 mm) 
of unbalanced backfill that do not have permanent 
lateral support at the top or bottom. 

R404.1.4 Seismic Design Categories Dq, D^ and Dj. In 

addition to the requirements of Tables R404. 1.1(1) and 
R404.1.1(5), plain concrete and plain masonry foundation 
walls located in Seismic Design Categories Dq, D, and D2, as 
established in Table R301.2(l), shall comply with the fol- 
lowing. 

1. Wall height shall not exceed 8 feet (2438 mm). 

2. Unbalanced backfill height shall not exceed 4 feet 
(1219 mm). 

3. Minimum reinforcement for plain concrete founda- 
tion walls shall consist of one No. 4 (No. 13) horizon- 
tal bar located in the upper 12 inches (305 mm) of the 
wall. 

4. Minimum thickness for plain concrete foundation 
walls shall be 7.5 inches (191 mm) except that 6 
inches (152 mm) is permitted when the maximum 
height is 4 feet, 6 inches (1372 mm). 

5. Minimum nominal thickness for plain masonry foun- 
dation walls shall be 8 inches (203 mm). 

6. Masonry stem walls shall have a minimum vertical 
reinforcement of one No. 3 (No. 10) bar located a 
maximum of 4 feet (1220 mm) on center in grouted 
cells. Vertical reinforcement shall be tied to the hori- 
zontal reinforcement in the footings. 

Foundation walls located in Seismic Design Categories 
Dq, Dj and D2, as established in Table R301 .2(1), supporting 
more than 4 feet (1219 mm) of unbalanced backfill or 
exceeding 8 feet (2438 mm) in height shall be constructed in 
accordance with Table R404.1.1(2), R404.1.1(3) or 
R404.1.1(4) for masonry, or Table R404.1.1(5) for con- 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



79 



FOUNDATIONS 



TABLE R404.1(3) 
MAXIMUM ASPECT RATIO, L/W FOR UNBALANCED FOUNDATIONS 



MAXIMUM WALL HEIGHT 
(feet) 



MAXIMUM UNBALANCED 
BACKFILL HEIGHT (feet) 



GW, GP, SW 
and SP soils 



SOIL CLASSES 



GM, GC, SM-SC 
and ML soils 



SC, MH, ML-CL 
and inorganic CL soils 



4.0 
4.0 
3.0 
1.9 



4.0 
3.4 
2.0 
1.2 



4.0 
2.6 
1.5 
0.9 



4.0 
4.0 
3.4 
2.1 
1.4 



4.0 
3.9 
2.3 
1.4 
1.0 



4.0 
2.9 
1.7 
1.1 
0.7 



4.0 
4.0 
3.8 
2.4 
1.6 
1.1 



4.0 
4.0 
2.6 
1.6 
1.1 
0.8 



4.0 
3.3 
1.9 
1.2 
0.8 
0.6 



For SI: 1 foot = 304.8 mm. 




UNBALANCED FILL HEIGHT 



Crete. Where Table R404.1.1(5) permits plain concrete 
walls, not less than No. 4 (No. 13) vertical bars at a spacing 
not exceeding 48 inches (1219 mm) shall be provided. Insu- 
lating concrete form foundation walls shall be reinforced as 
required in Table R404.4(l), R404.4(2), R404.4(3), 
R404.4(4) or R404.4(5). Where no vertical reinforcement is 
required by Table R404.4(2), R404.4(3) or R404.4(4) there 
shall be a minimum of one No. 4 (No. 13) bar at 48 inches 
(1220 mm) on center. All concrete and masonry foundation 
walls shall have two No. 4 (No. 13) horizontal bars located 
in the upper 12 inches (305 mm) of the wall. 

R404.1.5 Foundation wall thickness based on walls sup- 
ported. The thickness of concrete and masonry foundation 
walls shall not be less than the thickness of the wall sup- 
ported, except that foundation walls of at least 8-inch (203 
mm) nominal thickness shall be permitted under brick- 
veneered frame walls and under 10-inch- wide (254 mm) cav- 
ity walls where the total height of the wall supported, includ- 
ing gables, is not more than 20 feet (6096 mm), provided the 
requirements of Sections R404.1.1 and R404.1.2 are met. 



R404.1.5.1 Pier and curtain wall foundations. Use of 

Pier and curtain wall foundations shall be permitted to 
support light-frame construction not more than two stories 
in height, provided the following requirements are met: 

1 . All load-bearing walls shall be placed on continu- 
ous concrete footings placed integrally with the 
exterior wall footings. 

2. The minimum actual thickness of a load-bearing 
masonry wall shall be not less than 4 inches (102 
mm) nominal or 3^/^ inches (92 mm) actual thick- 
ness, and shall be bonded integrally with piers 
spaced in accordance with Section R606.9. 

3. Piers shall be constructed in accordance with Sec- 
tion R606.6 and Section R606.6.1, and shall be 
bonded into the load-bearing masonry wall in 
accordance with Section R608.L1 or Section 
R608.1.1.2. 

4. The maximum height of a 4-inch (102 mm) 
load-bearing masonry foundation wall supporting 



80 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FOUNDATIONS 



TABLE R404.1. 1(1) 
PLAIN MASONRY FOUNDATION WALLS 



MAXIMUM WALL HEIGHT 
(feet) 


MAXIMUM 

UNBALANCED 

BACKFILL HEIGHr (feet) 


PLAIN MASONRY^ MINIMUM NOMINAL WALL THICKNESS (inches) 


Soil classes'' 


GW, GP, SW 
andSP 


GM, GC, SM, 
SM-SC and ML 


SC, MH, ML-CL 
and inorganic CL 


5 


4 
5 


6 solid'' or 8 
6 solid'' or 8 


6 solid'' or 8 
8 


6 solid" or 8 
10 


6 


4 
5 
6 


6 solid'' or 8 

6 solid'' or 8 

8 


6 solid'' or 8 
8 
10 


6 solid" or 8 
10 
12 


7 


4 
5 
6 

7 


6 solid'' or 8 
6 solid'' or 8 

10 

12 


8 

10 

12 

10 solid" 


8 

10 
10 solid" 
12 solid" 


8 


4 
5 
6 
7 
8 


6 solid'' or 8 
6 solid'' or 8 

10 

12 
10 solid'' 


6 solid'' or 8 

10 

12 
12 solid'' 
12 solid" 


8 

12 

12 solid" 

Footnote e 

Footnote e 


9 


4 
5 
6 
7 
8 
9 


6 solid'' or 8 

8 

10 

12 

12 solid'' 

Footnote e 


6 solid" or 8 

10 

12 

12 solid" 

Footnote e 

Footnote e 


8 

12 

12 solid" 

Footnote e 

Footnote e 

Footnote e 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 Fh. 

a. Mortar shall be Type M or S and masonry shall be laid in running bond. Ungrouted hollow masonry units are permitted except where otherwise indicated. 

b. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1. 

c. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foun- 
dation wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, 
measurement of the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is pennitted. 

d. Solid grouted hollow units or solid masonry units. 

e. Wall construction shall be in accordance with Table R404.1.1(2) or a design shall be provided. 



wood-frame walls and floors shall not be more 
than 4 feet (1219 mm). 

5. Anchorage shall be in accordance with Section 
R403.1.6, Figure R404. 1.5(1), or as specified by 
engineered design accepted by the building offi- 
cial. 

6. The unbalanced fill for 4-inch (102 mm) founda- 
tion walls shall not exceed 24 inches (610 nrni) for 
solid masonry or 12 inches (305 mm) for hollow 
masonry. 

7. In Seismic Design Categories Dq, Dj and Dj, pre- 
scriptive reinforcement shall be provided in the hor- 
izontal and vertical direction. Provide minimum 
horizontal joint reinforcement of two No.9 gage 
wires spaced not less than 6 inches (152 mm) or one 
'/4 inch (6.4 mm) diameter wire at 10 inches (254 
mm) on center vertically. Provide minimum verti- 
cal reinforcement of one No. 4 bar at 48 inches 
( 1 220 mm) on center horizontally grouted in place. 



R404.1.6 Height above finished grade. Concrete and 
masonry foundation walls shall extend above the finished 
grade adjacent to the foundation at all points a minimum of 
4 inches (102 mm) where masonry veneer is used and a min- 
imum of 6 inches (152 mm) elsewhere. 

R404.1.7 Backfill placement. Backfill shall not be placed 
against the wall until the wall has sufficient strength and has 
been anchored to the floor above, or has been sufficiently 
braced to prevent damage by the backfill. 

Exception: Bracing is not required for walls supporting 
less than 4 feet (1219 mm) of unbalanced backfill. 

R404.1.8 Rubble stone masonry. Rubble stone masonry 
foundation walls shall have a minimum thickness of 16 
inches (406 mm), shall not support an unbalanced backfill 
exceeding 8 feet (2438 mm) in height, shall not support a 
soil pressure greater than 30 pounds per square foot per foot 
(4.71 kPa/m), and shall not be constructed in Seismic 
Design Categories Dq, Dj, Dj or townhouses in Seismic 
Design Category C, as established in Figure R301.2(2). 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



81 



FOUNDATIONS 



TABLE R404.1. 1(2) 

8-INCH MASONRY FOUNDATION WALLS WITH REINFORCING 

WHERE d > 5 INCHES^ 





HEIGHT OF 
UNBALANCED 


MINIMUM VERTICAL REINFORCEMENT* •= 


Soil classes and lateral soil load^ (psf per foot below grade) 


GW, GP, SW and SP soils 


GM, GC, SM, SM-SC and ML soils 


SC, ML-CL and inorganic CL soils 


WALL HEIGHT 


BACKFILL^ 


30 


45 


60 






4 feet (or less) 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 




6 feet 8 inches 


5 feet 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 






6 feet 8 inches 


#4 at 48" o.c. 


#5 at 48" o.c. 


#6 at 48" o.c. 






4 feet (or less) 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 




7 feet 4 inches 


5 feet 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 




6 feet 


#4 at 48" o.c. 


#5 at 48" o.c. 


#5 at 48" o.c. 






7 feet 4 inches 


#5 at 48" o.c. 


#6 at 48" o.c. 


#6 at 40" o.c. 






4 feet (or less) 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 






5 feet 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 




8 feet 


6 feet 


#4 at 48" o.c. 


#5 at 48" o.c. 


#5 at 48" o.c. 






7 feet 


#5 at 48" o.c. 


#6 at 48" o.c. 


#6 at 40" o.c. 






8 feet 


#5 at 48" o.c. 


#6 at 48" o.c. 


#6 at 32" o.c. 






4 feet (or less) 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 






5 feet 


#4 at 48" o.c. 


#4 at 48" o.c. 


#5 at 48" o.c. 




8 feet 8 inches 


6 feet 


#4 at 48" o.c. 


#5 at 48" o.c. 


#6 at 48" o.c. 






7 feet 


#5 at 48" o.c. 


#6 at 48" o.c. 


#6 at 40" o.c. 






8 feet 8 inches 


#6 at 48" o.c. 


#6 at 32" o.c. 


#6 at 24" o.c. 






4 feet (or less) 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 






5 feet 


#4 at 48" o.c. 


#4 at 48" o.c. 


#5 at 48" o.c. 




9 feet 4 inches 


6 feet 


#4 at 48" o.c. 


#5 at 48" o.c. 


#6 at 48" o.c. 




7 feet 


#5 at 48" o.c. 


#6 at 48" o.c. 


#6 at 40" o.c. 






8 feet 


#6 at 48" o.c. 


#6 at 40" o.c. 


#6 at 24" o.c. 






9 feet 4 inches 


#6 at 40" o.c. 


#6 at 24" o.c. 


#6 at 16" o.c. 






4 feet (or less) 


#4 at 48" o.c. 


#4 at 48" o.c. 


#4 at 48" o.c. 






5 feet 


#4 at 48" o.c. 


#4 at 48" o.c. 


#5 at 48" o.c. 






6 feet 


#4 at 48" o.c. 


#5 at 48" o.c. 


#6 at 48" o.c. 




10 feet 


7 feet 


#5 at 48" o.c. 


#6 at 48" o.c. 


#6 at 32" o.c. 






8 feet 


#6 at 48" o.c. 


#6 at 32" o.c. 


#6 at 24" o.c. 






9 feet 


#6 at 40" o.c. 


#6 at 24" o.c. 


#6 at 16" o.c. 






10 feet 


#6 at 32" o.c. 


#6 at 16" o.c. 


#6 at 16" o.c. 





For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm. 

a. Mortar shall be Type M or S and masonry shall be laid in running bond. 

b. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the 
spacing of the reinforcement does not exceed 72 inches. 

c. Vertical reinforcement shall be Grade 60 minimum. The distance from the face of the soil side of the wall to the center of vertical reinforcement shall be at least 5 
inches. 

d. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer 
to Table R405.1. 

e. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foun- 
dation wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, 
measurement of the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted. 



R404.2 Wood foundation walls. Wood foundation walls shall 
be constructed in accordance with the provisions of Sections 
R404.2.1 through R404.2.6 and with the details shown in Fig- 
ures R403.1(2) and R403.1(3). 

R404.2.1 Identification. All load-bearing lumber shall be 
identified by the grade mark of a lumber grading or inspec- 
tion agency which has been approved by an accreditation 
body that complies with DOC PS 20. In lieu of a grade mark, 
a certificate of inspection issued by a lumber grading or 
inspection agency meeting the requirements of this section 
shall be accepted. Wood structural panels shall conform to 
DOC PS 1 or DOC PS 2 and shall be identified by a grade 



mark or certificate of inspection issued by an approved 
agency. 

R404.2.2 Stud size. The studs used in foundation walls 
shall be 2-inch by 6-inch (51 mm by 152 mm) members. 
When spaced 16 inches (406 mm) on center, a wood species 
with an F^ value of not less than 1,250 pounds per square 
inch (8612 kPa) as hsted in AF&PA/NDS shall be used. 
When spaced 12 inches (305 mm) on center, an F,, of not less 
than 875 psi (6029 kPa) shall be required. 

R404.2.3 Height of backfill. For wood foundations that are 
not designed and installed in accordance with i'^&PA Report 



82 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FOUNDATIONS 



No.7, the height of backfill against a foundation wall shall not 
exceed 4 feet (1219 mm). When the height of fill is more than 
1 2 inches (305 mm) above the interior grade of a crawl space or 
floor of a basement, the thickness of the plywood sheathing 
shall meet the requirements of Table R404.2.3. 

R404.2.4 Backfilling. Wood foundation walls shall not be 
backfilled until the basement floor and first floor have been 
constructed or the walls have been braced. For crawl space 
construction, backfill or bracing shall be installed on the 
interior of the walls prior to placing backfill on the exterior. 



R404.2.5 Drainage and dampproofing. Wood foundation 
basements shall be drained and dampproofed in accordance 
with Sections R405 and R406, respectively. 

R404.2.6 Fastening. Wood structural panel foundation 
wall sheathing shall be attached to framing in accordance 
with Table R602.3(l) and Section R402.1.1. 

R404.3 Wood sill plates. Wood sill plates shall be a minimum 
of 2-inch by 4-inch (51 mm by 102 mm) nominal lumber. Sill 
plate anchorage shall be in accordance with Sections R403.1 .6 
and R602.il. 



TABLE R404.1. 1(3) 

10-INCH MASONRY FOUNDATION WALLS WITH REINFORCING 

WHERE d > 6.75 INCHES^ 





HEIGHT OF 
UNBALANCED 


MINIMUM VERTICAL REINFORCEMENT^ "^ 


Soil classes and later soil load" (psf per foot below grade) 


GW, GP, SW and SP soils 


GM, GC, SM, SM-SC and ML soils 


SC, MH, ML-CL and inorganic CL soils 


WALL HEIGHT 


BACKFILL^ 


30 


45 


60 




4 feet (or less) 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 


6 feet 8 inches 


5 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 




6 feet 8 inches 


#4 at 56" o.c. 


#5 at 56" o.c. 


#5 at 56" o.c. 




4 feet (or less) 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 


7 feet 4 inches 


5 feet 

6 feet 


#4 at 56" o.c. 
#4 at 56" o.c. 


#4 at 56" o.c. 
#4 at 56" o.c. 


#4 at 56" o.c. 
#5 at 56" o.c. 




7 feet 4 inches 


#4 at 56" o.c. 


#5 at 56" o.c. 


#6 at 56" o.c. 




4 feet (or less) 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 




5 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 


8 feet 


6 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#5 at 56" o.c. 




7 feet 


#4 at 56" o.c. 


#5 at 56" o.c. 


#6 at 56" o.c. 




8 feet 


#5 at 56" o.c. 


#6 at 56" o.c. 


#6 at 48" o.c. 




4 feet (or less) 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 




5 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 


8 feet 8 inches 


6 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#5 at 56" o.c. 




7 feet 


#4 at 56" o.c. 


#5 at 56" o.c. 


#6 at 56" o.c. 




8 feet 8 inches 


#5 at 56" o.c. 


#6 at 48" o.c. 


#6 at 32" o.c. 




4 feet (or less) 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 




5 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 


9 feet 4 inches 


6 feet 

7 feet 


#4 at 56" o.c. 
#4 at 56" o.c. 


#5 at 56" o.c. 
#5 at 56" o.c. 


#5 at 56" o.c. 
#6 at 56" o.c. 




8 feet 


#5 at 56" o.c. 


#6 at 56" o.c. 


#6 at 40" o.c. 




9 feet 4 inches 


#6 at 56" o.c. 


#6 at 40" o.c. 


#6 at 24" o.c. 




4 feet (or less) 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 




5 feet 


#4 at 56" o.c. 


#4 at 56" o.c. 


#4 at 56" o.c. 




6 feet 


#4 at 56" o.c. 


#5 at 56" o.c. 


#5 at 56" o.c. 


10 feet 


7 feet 


#5 at 56" o.c. 


#6 at 56" o.c. 


#6 at 48" o.c. 




8 feet 


#5 at 56" o.c. 


#6 at 48" o.c. 


#6 at 40" o.c. 




9 feet 


#6 at 56" o.c. 


#6 at 40" o.c. 


#6 at 24" o.c. 




10 feet 


#6 at 48" o.c. 


#6 at 32" o.c. 


#6 at 24" o.c. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm. 

a. Mortar shall be Type M or S and masonry shall be laid in running bond. 

b. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the 
spacing of the reinforcement does not exceed 72 inches. 

c. Vertical reinforcement shall be Grade 60 minimum. The distance from the face of the soil side of the wall to the center of vertical reinforcement shall be at least 6.75 
inches. 

d. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer 
to Table R405.1. 

e. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foun- 
dation wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, 
measurement of the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



83 



FOUNDATIONS 



TABLE R404.1. 1(4) 

12-INCH MASONRY FOUNDATION WALLS WITH REINFORCING 

WHERE d > 8.75 INCHES^ 





HEIGHT OF 
UNBALANCED 


MINIMUM VERTICAL REINFORCEMENT^' = 


Soil classes and lateral soil load" (psf per foot below grade) 


GW, GP, SW and SP soils 


GM, GC, SM, SM-SC and ML soils 


SC, ML-CL and inorqanic CL soils 


WALL HEIGHT 


BACKFILL^ 


30 


45 


60 




4 feet (or less) 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 


6 feet 8 inches 


5 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 




6 feet 8 inches 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#5 at 72" o.c. 




4 feet (or less) 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 


7 feet 4 inches 


5 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 


6 feet 


#4 at 72 


' o.c. 


#4 at 72" o.c. 


#5 at 72" o.c. 




7 feet 4 inches 


#4 at 72 


'o.c. 


#5 at 72" o.c. 


#6 at 72" o.c. 




4 feet (or less) 


#4 at 72 


' o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 




5 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 


8 feet 


6 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#5 at 72" o.c. 




7 feet 


#4 at 72 


' o.c. 


#5 at 72" o.c. 


#6 at 72" o.c. 




8 feet 


#5 at 72 


' o.c. 


#6 at 72" o.c. 


#6 at 64" o.c. 




4 feet (or less) 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 




5 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 


8 feet 8 inches 


6 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#5 at 72" o.c. 




7 feet 


#4 at 72 


'o.c. 


#5 at 72" o.c. 


#6 at 72" o.c. 




8 feet 8 inches 


#5 at 72 


'o.c. 


#7 at 72" o.c. 


#6 at 48" o.c. 




4 feet (or less) 


#4 at 72 


' o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 




5 feet 


#4 at 72 


' o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 


9 feet 4 inches 


6 feet 


#4 at 72 


' o.c. 


#5 at 72" o.c. 


#5 at 72" o.c. 


7 feet 


#4 at 72 


' o.c. 


#5 at 72" o.c. 


#6 at 72" o.c. 




8 feet 


#5 at 72 


'o.c. 


#6 at 72" o.c. 


#6 at 56" o.c. 




9 feet 4 inches 


#6 at 72 


' o.c. 


#6 at 48" o.c. 


#6 at 40" o.c. 




4 feet (or less) 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 




5 feet 


#4 at 72 


'o.c. 


#4 at 72" o.c. 


#4 at 72" o.c. 




6 feet 


#4 at 72 


' o.c. 


#5 at 72" o.c. 


#5 at 72" o.c. 


10 feet 


7 feet 


#4 at 72 


' o.c. 


#6 at 72" o.c. 


#6 at 72" o.c. 




8 feet 


#5 at 72 


' o.c. 


#6 at 72" o.c. 


#6 at 48" o.c. 




9 feet 


#6 at 72 


'o.c. 


#6 at 56" o.c. 


#6 at 40" o.c. 




10 feet 


#6 at 64" o.c. 


#6 at 40" o.c. 


#6 at 32" o.c. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm. 

a. Mortar shall be Type M or S and masonry shall be laid in running bond. 

b. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the 
spacing of the reinforcement does not exceed 72 inches. 

c. Vertical reinforcement shall be Grade 60 minimum. The distance from the face of the soil side of the wall to the center of vertical reinforcement shall be at least 8.75 
inches. 

d. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer 
to Table R405.1. 

e. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foun- 
dation wall or the interior finish ground levels. Where an interior concrete slab-on-grade is provided and in contact with the interior surface of the foundation wall, 
measurement of the unbalanced backfill height is permitted to be measured from the exterior finish ground level to the top of the interior concrete slab is permitted. 



R404.4 Insulating concrete form foundation walls. Insulat- 
ing concrete form (ICF) foundation walls shall be designed and 
constructed in accordance with the provisions of this section or 
in accordance with the provisions of ACI 318. When ACI 318 
or the provisions of this section are used to design insulating 
concrete form foundation walls, project drawings, typical 
details and specifications are not required to bear the seal of the 
architect or engineer responsible for design unless otherwise 
required by the state law of the jurisdiction having authority. 

R404.4.1 Applicability limits. The provisions of this sec- 
tion shall apply to the construction of insulating concrete 
form foundation walls for buildings not more than 60 feet 



(18 288 mm) in plan dimensions, and floors not more than 
32 feet (9754 mm) or roofs not more than 40 feet (12 192 
mm) in clear span. Buildings shall not exceed two stories in 
height above grade with each story not more than 10 feet 
(3048 mm) high. Foundation walls constructed in accor- 
dance with the provisions of this section shall be limited to 
buildings subjected to a maximum ground snow load of 70 
psf (3.35 kPa) and located in Seismic Design Category A, B 
or C. In Seismic Design Categories Dq, D] and D2, founda- 
tion walls shall comply with Section R404.1.4. Insulating 
concrete form foundation walls supporting above-grade 
concrete walls shall be reinforced as required for the above- 



84 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FOUNDATIONS 



TABLE R404.1. 1(5) 
CONCRETE FOUNDATION WALLS'^' '■' "^ 



MAXIMUM 

WALL 

HEIGHT 

(feet) 


MAXIMUM 

unbalanced 
backfill 
height" 

(feet) 


MINIMUM VERTICAL REINFORCEMENT SIZE AND SPACINC^' "'«•'■ ' 


Soil classes^ and design lateral soil (psf per foot of depth) 


GW, GP, SW and SP 
30 


GM, GC, SM, SM-SC and ML 
45 


SC, ML-CL and inorganic CL 
60 


Minimum wall thickness (inches) 


5.5 


7.5 


9.5 


11.5 


5.5 


7.5 


9.5 


11.5 


5.5 


7.5 


9.5 


11.5 


5 


4 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


5 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


6 


4 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


5 


PC 


PC 


PC 


PC 


PC 


PCS 


PC 


PC 


#4@35" 


peg 


PC 


PC 


6 


PC 


PC 


PC 


PC 


#5@48" 


PC 


PC 


PC 


#5@36" 


PC 


PC 


PC 


7 


4 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


5 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


#5@47" 


PC 


PC 


PC 


6 


PC 


PC 


PC 


PC 


#5@42" 


PC 


PC 


PC 


#6@43" 


#5@48" 


PCS 


PC 


7 


#5@46" 


PC 


PC 


PC 


#6@42" 


#5@46" 


PCS 


PC 


#6@34" 


#6@48" 


PC 


PC 


8 


4 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


5 


PC 


PC 


PC 


PC 


#4@38" 


PCS 


PC 


PC 


#5@43" 


PC 


PC 


PC 


6 


#4@37" 


PCS 


PC 


PC 


#5@37" 


PC 


PC 


PC 


#6@37" 


#5@43" 


PCS 


PC 


7 


#5@40" 


PC 


PC 


PC 


#6@37" 


#5@41" 


PC 


PC 


#6@34" 


#6@43" 


PC 


PC 


8 


#6@43" 


#5@47" 


PCS 


PC 


#6@34" 


#6@43" 


PC 


PC 


#6@27" 


#6@32" 


#6@44" 


PC 


9 


4 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


5 


PC 


PC 


PC 


PC 


#4@35" 


PCS 


PC 


PC 


#5@40" 


PC 


PC^ 


PC 


6 


#4@34" 


PCS 


PC 


PC 


#6@48" 


PC 


PC 


PC 


#6@36" 


#5@39" 


PCS 


PC 


7 


#5@36" 


PC 


PC 


PC 


#6@34" 


#5@37" 


PC 


PC 


#6@33" 


#6@38" 


#5@37" 


peg 


8 


#6@38" 


#5@41" 


PCS 


PC 


#6@33" 


#6@38" 


#5@37" 


PCS 


#6@24" 


#7@39" 


#6@39" 


#4@48"'^ 


9 


#6@34" 


#6@46" 


PC 


PC 


#6@26" 


#7@41" 


#6@41" 


PC 


#6@19" 


#7@31" 


#7@41" 


#6@39" 


10 


4 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


PC 


5 


PC 


PC 


PC 


PC 


#4@33" 


PCS 


PC 


PC 


#5@38" 


PC 


PC 


PC 


6 


#5@48" 


PCS 


PC 


PC 


#6@45" 


PC 


PC 


PC 


#6@34" 


#5@37" 


PC 


PC 


7 


#6@47" 


PC 


PC 


PC 


#6@34" 


#6@48" 


PC 


PC 


#6@30" 


#6@35" 


#6@48" 


PCS 


8 


#6@34" 


#5@38" 


PC 


PC 


#6@30" 


#7@47" 


#6@47" 


PCS 


#6@22" 


#7@35" 


#7@48" 


#6@45"'' 


9 


#6@34" 


#6@41" 


#4@48" 


PC8 


#6@23" 


#7@37" 


#7@48" 


#4@48"h 


DR 


#6@22" 


#7@37" 


#7@47" 


10 


#6@28" 


#7@45" 


#6@45" 


PC 


DR 


#7@31" 


#7@40" 


#6@38" 


DR 


#6@22" 


#7@30" 


#7@38" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa; 1 pound per square foot per foot = 0.157 kPa/mm. 

a. Soil classes are in accordance with the United Soil Classification System. Refer to Table R405.1 

b. Unbalanced backfill height is the difference in height of the exterior and interior finish ground levels. Where there is an interior concrete slab, the unbalanced back- 
fill height shall be measured from the exterior finish ground level to the top of the interior concrete slab. 

c. The size and spacing of verfical reinforcement shown in the table is based on the use of reinforcement with a minimum yield strength of 60,000 psi. Vertical rein- 
forcement with a minimum yield strength of 40,000 psi or 50,000 psi is permitted, provided the same size bar is used and the spacing shown in the table is reduced 
by multiplying the spacing by 0.67 or 0.83, respectively. 

d. Vertical reinforcement, when required, shall be placed nearest the inside face of the wall a distance d from the outside face (soil side) of the wall. The distance d is 
equal to the wall thickness, t, minus 1 .25 inches plus one-half the bar diameter, db (d = t - (1 .25 + db/2). The reinforcement shall be placed within a tolerance of ± % 
inch where d is less than or equal to 8 inches, or ± V2 inch where d is greater than 8 inches. 

e. In lieu of the reinforcement shown, smaller reinforcing bar sizes and closer spacings resulting in an equivalent cross-sectional area of reinforcement per linear foot 
of wall are permitted. 

f . Concrete cover for reinforcement measured from the inside face of the wall shall not be less than ^/^ inch. Concrete cover for reinforcement measured from the out- 
side face of the wall shall not be less than 1 V2 inches for No. 5 bars and smaller, and not less than 2 inches for larger bars. 

g. The minimum thickness is permitted to be reduced 2 inches, provided the minimum specified compressive strength of concrete //, is 4,000 psi. 

(continued) 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



85 



FOUNDATIONS 



TABLE R404.1. 1(5)— continued 
CONCRETE FOUNDATION WALLS'^ ''•'' 

h. A plain concrete wall with a minimum thickness of 1 1.5 inches is permitted, provided minimum specified compressive strength of concrete, //, is 3,500 psi. 
i. Concrete shall have a specified compressive strength of not less than 2,500 psi at 28 days, unless a higher strength is required by note g or h. 
j. "DR" means design is required in accordance with ACI 318 or ACI 332. 
k. "PC" means plain concrete. 

1. Where vertical reinforcement is required, horizontal reinforcement shall be provided in accordance with the requirements of Section R404.4.6.2 for ICF founda- 
tion walls. 



grade wall immediately above or the requirements in Tables 
R404.4(l), R404.4(2), R404.4(3), R404.4(4) orR404.4(5), 
whichever is greater. 

R404.4.2 Flat insulating concrete form wall systems. Flat 
ICF wall systems shall comply with Figure R611.3, shall 
have a minimum concrete thickness of 5.5 inches (140 mm), 
and shall have reinforcement in accordance with Table 
R404.4(l), R404.4(2) or R404.4(3). Alternatively, for 
7.5-inch (191 mm) and 9.5-inch (241 mm) flat ICF wall sys- 
tems, use of Table R404. 1 . 1 (5) shall be permitted, provided 
the vertical reinforcement is of the grade and located within 
the wall as required by that table. 

R404.4.3 Waffle-grid insulating concrete form wall sys- 
tems. Waffle-grid wall systems shall have a minimum nom- 
inal concrete thickness of 6 inches (152 mm) for the 
horizontal and vertical concrete members (cores) and shall 
be reinforced in accordance with Table R404.4(4). The min- 
imum core dimension shall comply with Table R61 1.2 and 
Figure R6 11.4. 

R404.4.4 Screen-grid insulating concrete form wall sys- 
tems. Screen-grid ICF wall systems shall have a minimum 
nominal concrete thickness of 6 inches (152 mm) for the 
horizontal and vertical concrete members (cores). The mini- 
mum core dimensions shall comply with Table R611 .2 and 
Figure R611.5. Walls shall have reinforcement in accor- 
dance with Table R404.4(5). 

R404.4.5 Concrete material. Ready-mixed concrete for 
insulating concrete form walls shall be in accordance with 
Section R402.2. Maximum slump shall not be greater than 6 
inches (152 mm) as determined in accordance with ASTM 
C 143. Maximum aggregate size shall not be larger than V4 
inch (19.1 mm). 

Exception: Concrete mixes conforming to the ICF man- 
ufacturer's recommendations. 

R404.4.6 Reinforcing steel. 

R404.4.6.1 General. Reinforcing steel shall meet the 
requirements of ASTM A 615, A 706 or A 996. The min- 
imum yield strength of reinforcing steel shall be 40,000 
psi (Grade 40) (276 MPa). Vertical and horizontal wall 
reinforcements shall be placed no closer to the outside 
face of the wall than one-half the wall thickness. Steel 
reinforcement for foundation walls shall have concrete 
cover in accordance with ACI 318. 

Exception: Where insulated concrete forms are used 
and the form remains in place as cover for the con- 
crete, the minimum concrete cover for the reinforcing 
steel is permitted to be reduced to V4 inch (19.1 mm) . 



R404.4.6.2 Horizontal reinforcement. When vertical 
reinforcement is required, ICF foundation walls shall 
have horizontal reinforcement in accordance with this 
section. ICF foundation walls up to 8 feet (2438 mm) in 
height shall have a minimum of one continuous No. 4 
horizontal reinforcing bar placed at 48 inches (1219 mm) 
on center with one bar located within 12 inches (305 
mm) of the top of the wall story. ICF Foundation walls 
greater than 8 feet (2438 mm) in height shall have a mini- 
mum of one continuous No. 4 horizontal reinforcing bar 
placed at 36 inches (914 mm) on center with one bar 
located within 12 inches (305 mm) of the top of the wall 
story. 

R404.4.6.3 Wall openings. Vertical wall reinforcement 
required by Section R404.4.2, R404.4.3 or R404.4.4 that 
is interrupted by wall openings shall have additional ver- 
tical reinforcement of the same size placed within 12 
inches (305 mm) of each side of the opening. 

R404.4.7 Foam plastic insulation. Foam plastic insulation 
in insulating concrete foam construction shall comply with 
this section. 

R404.4.7.1 Material. Insulating concrete form material 
shall meet the surface burning characteristics of Section 
R3 14.3 . A thermal barrier shall be provided on the build- 
ing interior in accordance with Section R314.4. 

R404.4.7.2 Termite hazards. In areas where hazard of 
termite damage is very heavy in accordance with Figure 
R301.2(6), foam plastic insulation shall be permitted 
below grade on foundation walls in accordance with one 
of the following conditions: 

1. When in addition to the requirements in Section 
R320.1, an approved method of protecting the 
foam plastic and structure from subterranean ter- 
mite damage is provided. 

2. The structural members of walls, floors, ceilings 
and roofs are entirely of noncombustible materials 
or pressure preservatively treated wood. 

3. On the interior side of basement walls. 

R404.4.8 Foundation wall thickness based on walls sup- 
ported. The thickness of ICF foundation walls shall not be 
less than the thickness of the wall supported above. 

R404.4.9 Height above finished ground. ICF foundation 
walls shall extend above the finished ground adjacent to the 
foundation at all points a minimum of 4 inches (102 mm) 
where masonry veneer is used and a minimum of 6 inches 
(152 mm) elsewhere. 



86 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FOUNDATIONS 



GALVANIZED OR STAINLESS STEEL STRAPS, 
MIN. 27,,," WIDE BY 1 2 GAGE THICK, 
MIN. 2" FROM EDGE OF PIER, TYP. 



IN. NINE 16d NAILS PER STRAP 




MIN. 8" X 16" MASONRY PIER. TYP. 



N. TWO 9 GAGE BOX TIES OR TWO 
MASONRY HEADERS AT 8" O.C. EACH PIER 



STRAPS ANCHORED WITH 90 DEGREE HOOK, MIN. TWO STRAPS PER PIER, 
MIN. 4" EMBEDMENT INTO FOOTING, MIN. 1.75" HORIZ. LEG EXTENSION 



DOUBLE RIM JOISTS 



MIN. 18 GAGE PLATE 
CONNECTORS AT 
MAX. 12 IN. O.C. (TYP.) 




MIN. 4 IN. MASONRY 
CURTAIN WALL 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 d^ree = 0.0157 rad. 



FIGURE R404.1. 5(1) 
FOUNDATION WALL CLAY MASONRY CURTAIN WALL WITH CONCRETE MASONRY PIERS 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



87 



FOUNDATIONS 



TABLE R404.2.3 

PLYWOOD GRADE AND THICKNESS FOR WOOD FOUNDATION CONSTRUCTION 

(30 pcf equivalent-fluid weight soil pressure) 



HEIGHT OF FILL 
(inches) 


STUD SPACING 
(inches) 


FACE GRAIN ACROSS STUDS 


FACE GRAIN PARALLEL TO STUDS 


Grade^ 


Minimum 
thickness 
(inches) 


Span rating 


Grade^ 


Minimum 
thickness 
(inches)'''^ 


Span rating 


24 


12 


B 


'%2 


32/16 


A 


•v., 


32/16 


B 


'^A,^ 


32/16 


16 


B 


'%2 


32/16 


A 


^%,^ 


32/16 


B 


i%2^(4,5ply) 


40/20 


36 


12 


B 


'%2 


32/16 


A 


'%2 


32/16 


B 


^V (4, 5 ply) 


32/16 


B 


1%, (4, 5 ply) 


40/20 


16 


B 


'%2' 


32/16 


A 


'%2 


40/20 


B 


'\2 


48/24 


48 


12 


B 


'%2 


32/16 


A 


'%2' 


32/16 


B 


i%/(4,5ply) 


40/20 


16 


B 


'%2 


40/20 


A 


'%/ 


40/20 


A 


'%2 


48/24 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per cubic foot = 0.1572 kN/n?. 

a. Plywood shall be of the following minimum grades in accordance with DOC PS 1 or DOC PS 2: 

1 . DOC PS 1 Plywood grades marked: 

1.1. Structural I C-D (Exposure 1) 

1.2. C-D (Exposure 1) 

2. DOC PS 2 Plywood grades marked: 

2.1. Structural I Sheathing (Exposure 1) 

2.2. Sheathing (Exposure 1) 

3. Where a major portion of the wall is exposed above ground and abetter appearance is desired, the following plywood grades marked exterior are suitable: 

3.1. Structural I A-C, Structural I B-C or Structural I C-C (Plugged) in accordance with DOC PS 1 

3.2. A-C Group 1, B-C Group 1, C-C (Plugged) Group 1 orMDO Group 1 in accordance with DOC PS 1 

3.3. Single Floor in accordance with DOC PS 1 or DOC PS 2 

b. Minimum thickness ^^l-i2 inch, except crawl space sheathing may be ^/g inch for face grain across studs 16 inches on center and maximum 2-foot depth of unequal 
fill. 

c. For this fill height, thickness and grade combination, panels that are continuous over less than three spans (across less than three stud spacings) require blocking 16 
inches above the bottom plate. Offset adjacent blocks and fasten through studs with two 16d corrosion-resistant nails at each end. 



R404.4.10 Backfill placement. Backfill shall be placed in 
accordance with Section R404.1.7. 

R404.4.11 Drainage and dampproofing/waterproofing. 

ICF foundation basements shall be drained and 
dampproofed/waterproofed in accordance with Sections 
R405 and R406. 

R404.5 Retaining walls. Retaining walls that are not laterally 
supported at the top and that retain in excess of 24 inches (610 
mm) of unbalanced fill shall be designed to ensure stability 
against overturning, sliding, excessive foundation pressure and 
water uplift. Retaining walls shall be designed for a safety fac- 
tor of 1.5 against lateral sliding and overturning. 



SECTION R405 
FOUNDATION DRAINAGE 

R405.1 Concrete or masonry foundations. Drains shall be 
provided around all concrete or masonry foundations that retain 
earth and enclose habitable or usable spaces located below 
grade. Drainage tiles, gravel or crushed stone drains, perforated 
pipe or other approved systems or materials shall be installed at 
or below the area to be protected and shall discharge by gravity 
or mechanical means into an approved drainage system. Gravel 
or crushed stone drains shall extend at least 1 foot (305 mm) 
beyond the outside edge of the footing and 6 inches (152 mm) 
above the top of the footing and be covered with an approved fil- 
ter membrane material. The top of open joints of drain tiles shall 
be protected with strips of building paper, and the drainage tiles 
or perforated pipe shall be placed on a minimum of 2 inches (5 1 
mm) of washed gravel or crushed rock at least one sieve size 



88 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FOUNDATIONS 



TABLE R404.4(1) 
5.5-INCH THICK FLAT ICF FOUNDATION WALLS^ *"=■" 



HEIGHT OF BASEMENT 
WALL 
(feet) 


MAXIMUM UNBALANCED 

BACKFILL HEIGHT 

(feet) 


MINIMUM VERTICAL REINFORCEMENT SIZE AND SPACING 


Soil classes' and design lateral soil load (psf per foot of depth) 


GW, GP, SW and SP 
30 


GM, GC, SM, SM-SC and ML 
45 


SC, ML-CL and inorganic CL 
60 


8 


4 


#4@48" 


#4@48" 


#4@48" 


5 


#4@48" 


#3@12";#4@22"; 
#5@32" 


#3@8";#4@14"; 
#5 @ 20"; #6 @ 26" 


6 


#3@12";#4@22"; 
#5@30" 


#3@8";#4@14"; 
#5@20";#6@24" 


#3@6";#4@10": 
#5@14";#6@20" 


7 


#3@8";#4@14"; 
#5@22";#6@26" 


#3@5";#4@10"; 
#5@14";#6@18" 


#3@4";#4@6"; 
#5@10";#6@14" 


9 


4 


#4@48" 


#4@48" 


#4@48" 


5 


#4@48" 


#3@12";#4@20"; 
#5@28";#6@36" 


#3@8";#4@14"; 
#5@20"; #6@22" 


6 


#3@10";#4@20"; 
#5@28";#6@34" 


#3@6";#4@12"; 
#5@18";#6@20" 


#4@8"; 
#5@14";#6@16" 


7 


#3@8";#4@14"; 
#5@20";#6@22" 


#4@8";#5@12";#6@16" 


#4@6"; 
#5@10";#6@12" 


8 


#3@6";#4@10"; 
#5@14";#6@16" 


#4@6";#5@10";#6@12" 


#4@4"; 
#5@6";#6@8" 


10 


4 


#4@48" 


#4@48" 


#4@48" 


5 


#4@48" 


#3@10";#4@18"; 
#5 @ 26"; #6 @ 30" 


#3@6";#4@14"; 
#5@18";#6@20" 


6 


#3@10";#4@18"; 
#5 @ 24"; #6 @ 30" 


#3@6";#4@12"; 
#5@16";#6@18" 


#3@4";#4@8"; 
#5@12";#6@14" 


7 


#3@6";#4@12"; 
#5@16";#6@18" 


#3@4";#4@8";#5@12" 


#4@6"; 
#5@8";#6@10" 


8 


#4@8";#5@12";#6@14" 


#4@6";#5@8";#6@12" 


#4@4"; 
#5@6";#6@8" 


9 


#4@6";#5@10";#6@12" 


#4@4";#5@6";#6@8" 


#5@4";#6@6" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 pound per square foot = 0.0479 kPa. | 

a. This table is based on concrete with a minimum specified concrete strength of 2500 psi, reinforcing steel with a minimum yield strength of 40,000 psi. When rein- 
forcing steel with a minimum yield strength of 60,000 psi is used, the spacing of the reinforcement shall be increased to 1 .5 times the spacing value in the table but 
in no case greater than 48 inches on center. 

b. This table is not intended to prohibit the use of an ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criteria: L/240. 

d. Interpolation between rebar sizes and spacing is not permitted. 

e. Unbalanced backfill height is the difference in height of the exterior and interior finished ground. Where an interior concrete slab is provided, the unbalanced back- 
fill height shall be measured from the exterior finished ground level to the top of the interior concrete slab. 

f. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1. 



larger than the tile joint opening or perforation and covered with 
not less than 6 inches (152 mm) of the same material. 

Exception: A drainage system is not required when the 
foundation is installed on well-drained ground or 
sand-gravel mixture soils according to the Unified Soil 
Classification System, Group I Soils, as detailed in Table 
R405.1. 

R405.2 Wood foundations. Wood foundations enclosing hab- 
itable or usable spaces located below grade shall be adequately 
drained in accordance with Sections R405.2.1 through 
R405.2.3. 



R405.2.1 Base. A porous layer of gravel, crushed stone or 
coarse sand shall be placed to a minimum thickness of 4 
inches (102 mm) under the basement floor. Provision shall 
be made for automatic draining of this layer and the gravel 
or crushed stone wall footings. 

R405.2.2 Moisture barrier. A 6-mil-thick (0. 15 mm) poly- 
ethylene moisture barrier shall be applied over the porous 
layer with the basement floor constructed over the polyeth- 
ylene. 

R405.2.3 Drainage system, hi other than Group I soils, a 
sump shall be provided to drain the porous layer and footings. 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



89 



FOUNDATIONS 



TABLE R404.4(2) 
7.5-INCH-THICK FLAT ICF FOUNDATION WALLS^ "■ "= "^ 



HEIGHT OF 

BASEMENT WALL 

(feet) 


MAXIMUM 

UNBALANCED 

BACKFILL height' 

(feet) 


MINIMUM VERTICAL REINFORCEMENT SIZE AND SPACING 


Soil classes^ and design lateral soil load (psf per foot of depth) 


GW, GP, SW and SP 
30 


GM, GC, SM, SM-SC and ML 
45 


SC, ML-CL and inorganic CL 
60 


8 


6 


N/R 


N/R 


#3@6";#4@12"; 
#5@18";#6@24" 


7 


N/R 


#3@8";#4@14"; 
#5 @ 20"; #6 @ 28" 


#3@6";#4@10"; 
#5@16";#6@20" 


9 


6 


N/R 


N/R 


#3@8";#4@14"; 
#5@20";#6@28" 


7 


N/R 


#3@6";#4@12"; 
#5@18";#6@26" 


#3@4";#4@8"; 
#5@14";#6@18" 


8 


#3@8";#4@14"; 
#5@22";#6@28" 


#3@4";#4@8"; 
#5@14";#6@18" 


#3@4";#4@6"; 
#5@10";#6@14" 


10 


6 


N/R 


N/R 


#3@6";#4@12"; 
#5@18";#6@26" 


7 


N/R 


#3@6";#4@12"; 
#5@18";#6@24" 


#3@4";#4@8"; 
#5@12";#6@18" 


8 


#3@6";#4@12"; 
#5 @ 20"; #6 @ 26" 


#3@4";#4@8"; 
#5@12";#6@16" 


#3@4";#4@6"; 
#5@8";#6@12" 


9 


#3@6";#4@10"; 
#5@14";#6@20" 


#3@4";#4@6"; 
#5@10";#6@12" 


#4@4";#5@6"; 
#6@10" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch - 6.895 kPa, 1 pound per square foot = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified concrete strength of 2500 psi, reinforcing steel with a minimum yield strength of 40,000 psi. When rein- 
forcing steel with a minimum yield strength of 60,000 psi is used, the spacing of the reinforcement shall be increased to 1 .5 times the spacing value in the table. 

b. This table is not intended to prohibit the use of an ICF manuiacturer's tables based on engineering analysis in accordance with ACI 318. 

c. N/R denotes "not required." 

d. Deflection criteria: L/240. 

e. Interpolation between rebar sizes and spacing is not permitted. 

f . Unbalanced backfill height is the difference in height of the exterior and interior finished ground. Where an interior concrete slab is provided, the unbalanced back- 
fill height shall be measured from the exterior finished ground level to the top of the interior concrete slab. 



The sump shall be at least 24 inches (610 mm) in diameter or 
20 inches square (0.0129 m^), shall extend at least 24 inches 
(610 mm) below the bottom of the basement floor and shall 
be capable of positive gravity or mechanical drainage to 
remove any accumulated water. The drainage system shall 
discharge into an approved sewer system or to dayhght. 



SECTION R406 

FOUNDATION WATERPROOFING 

AND DAMPPROOFING 

R406.1 Concrete and masonry foundation dampprooflng. 

Except where required by Section R406.2 to be waterproofed, 
foundation walls that retain earth and enclose interior spaces 
and floors below grade shall be dampproofed from the top of 
the footing to the finished grade. Masonry walls shall have not 
less than Vg inch (9.5 mm) portland cement parging applied to 
the exterior of the wall. The parging shall be dampproofed in 
accordance with one of the following: 

1 . Bituminous coating. 

2. 3 pounds per square yard (1.63 kg/m^) of acrylic modi- 
fied cement. 

3. 1/8-inch (3.2 mm) coat of surface-bonding cement com- 
plying with ASTM C 887. 



4. Any material permitted for waterproofing in Section 
R406.2. 

5. Other approved methods or materials. 

Exception: Parging of unit masonry walls is not 
required where a material is approved for direct appli- 
cation to the masonry. 

Concrete walls shall be dampproofed by applying any one of 
the above listed dampprooflng materials or any one of the 
waterproofing materials listed in Section R406.2 to the exterior 
of the wall. 

R406.2 Concrete and masonry foundation waterproofing. 

In areas where a high water table or other severe soil-water con- 
ditions are known to exist, exterior foundation walls that retain 
earth and enclose interior spaces and floors below grade shall 
be waterproofed from the top of the footing to the finished 
grade. Walls shall be waterproofed in accordance with one of 
the following: 

1. 2-ply hot-mopped felts. 

2. 55 pound (25 kg) roll roofing. 

3. 6-mil (0.15 mm) polyvinyl chloride. 

4. 6-mil (0.15 mm) polyethylene. 

5. 40-mil (1 mm) polymer-modified asphalt. 



90 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



FOUNDATIONS 



TABLE R404.4(3) 
9.5-INCH-THICK FLAT ICF FOUNDATION WALLS^ "''■''^ 



HEIGHT OF 

BASEMENT WALL 

(feet) 


MAXIMUM 

UNBALANCED 

BACKFILL HEIGHT* 

(feet) 


MINIMUM VERTICAL REINFORCEMENT SIZE AND SPACING 


Soil classes^ and design lateral soil load (psf per foot of depth) 


GW, GP, SW and SP 
30 


GM, GC, SM, SM-SC and ML 
45 


SC, ML-CL and inorganic CL 
60 


8 


7 


N/R 


N/R 


N/R 


9 


6 


N/R 


N/R 


N/R 


7 


N/R 


N/R 


#3@6";#4@12"; 
#5@18";#6@26" 


8 


N/R 


#3@6";#4@12"; 
#5@18";#6@26" 


#3@4";#4@8"; 
#5@14";#6@18" 


10 


5 


N/R 


N/R 


N/R 


6 


N/R 


N/R 


N/R 


7 


N/R 


N/R 


#3@6";#4@10"; 
#5@18";#6@24" 


8 


N/R 


#3@6";#4@12"; 
#5@16";#6@24" 


#3@4"; #4@8"; 
#5@12";#6@16" 


9 


#3@4";#4@10"; 
#5@14";#6@20" 


#3@4";#4@8"; 
#5@12";#6@18" 


#3@4";#4@6"; 
#5@10";#6@12" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 pound per square foot = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified concrete strength of 2500 psi, reinforcing steel with a minimum yield strength of 40,000 psi. When rein- 
forcing steel with a minimum yield strength of 60,000 psi is used, the spacing of the reinforcement shall be increased to 1 .5 times the spacing value in the table. 

b. This table is not intended to prohibit the use of an ICF manuiacturer's tables based on engineering analysis in accordance with ACI 318. 

c. N/R denotes "not required." 

d. Deflection criteria: L/240. 

e. Interpolation between rebar sizes and spacing is not permitted. 

f. Unbalanced backfill height is the difference in height of the exterior and interior finished ground. Where an interior concrete slab is provided, the unbalanced back- 
fill height shall be measured from the exterior finished ground level to the top of the interior concrete slab. 

g. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1. 



6. 60-mil (1.5 mm) flexible polymer cement. 

7. Vg inch (3 mm) cement-based, fiber-reinforced, water- 
proof coating. 

8. 60-mil (0.22 mm) solvent-free liquid-applied synthetic 
rubber. 

Exception: Organic-solvent-based products such as hydro- 
carbons, chlorinated hydrocarbons, ketones and esters shall 
not be used for ICF walls with expanded polystyrene form 
material. Use of plastic roofing cements, acrylic coatings, 
latex coatings, mortars and pargings to seal ICF walls is 
permitted. Cold-setting asphalt or hot asphalt shall conform 
to type C of ASTM D 449. Hot asphalt shall be applied at a 
temperature of less than 200°F (93°C). 

All joints in membrane waterproofing shall be lapped and 
sealed with an adhesive compatible with the membrane. 

R406.3 Dampproofing for wood foundations. Wood founda- 
tions enclosing habitable or usable spaces located below grade 
shall be dampproofed in accordance with Sections R406.3.1 
through R406.3.4. 

R406.3.1 Panel joint sealed. Plywood panel joints in the 
foundation walls shall be sealed full length with a caulking 
compound capable of producing a moisture-proof seal 
under the conditions of temperature and moisture content at 
which it will be applied and used. 



R406.3.2 Below-grade moisture barrier. A 6-mil-thick 
(0.15 mm) polyethylene film shall be applied over the 
below-grade portion of exterior foundation walls prior to 
backfilling. Joints in the polyethylene film shall be lapped 6 
inches (152 mm) and sealed with adhesive. The top edge of 
the polyethylene film shall be bonded to the sheathing to 
form a seal. Film areas at grade level shall be protected from 
mechanical damage and exposure by a pressure 
preservatively treated lumber or plywood strip attached to 
the wall several inches above finish grade level and extend- 
ing approximately 9 inches (229 mm) below grade. The 
joint between the strip and the wall shall be caulked full 
length prior to fastening the strip to the wall. Other cover- 
ings appropriate to the architectural treatment may also be 
used. The polyethylene film shall extend down to the bot- 
tom of the wood footing plate but shall not overlap or extend 
into the gravel or crushed stone footing. 

R406.3.3 Porous fill. The space between the excavation and 
the foundation wall shall be backfilled with the same mate- 
rial used for footings, up to a height of 1 foot (305 mm) 
above the footing for well-drained sites, or one-half the total 
back-fill height for poorly drained sites. The porous fill shall 
be covered with strips of 30-pound (13.6 kg) asphalt paper 
or 6-mil (0.15 mm) polyethylene to permit water seepage 
while avoiding infiltration of fine soils. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



91 



FOUNDATIONS 



TABLE R404.4(4) 
WAFFLE GRID ICF FOUNDATION WALLS^- " =■ "^ 



MINIMUM NOMINAL 

WALL THICKNESS' 

(inches) 


HEIGHT OF 

BASEMENT WALL 

(feet) 


MAXIMUM 

UNBALANCED 

BACKFILL HEIGHTS 

(feet) 


MINIMUM VERTICAL REINFORCEMENT SIZE AND SPACING 


Soil classes^ and design lateral soil load (psf per foot of depth) 


GW, GP, SW and SP 
30 


GM, GC, SM, SM-SC and ML 
45 


SC, ML-CL and inorganic CL 
60 


6 


8 


4 


#4@48" 


#3@12";#4@24" 


#3@12" 


5 


#3@12";#5@24" 


#4@12" 


#7@12" 


6 


#4@12" 


Design required 


Design required 


7 


#7@12" 


Design required 


Design required 


9 


4 


#4@48" 


#3@12";#5@24" 


#3@12" 


5 


#3@12" 


#4@12" 


Design required 


6 


#5@12" 


Design required 


Design required 


7 


Design required 


Design required 


Design required 


10 


4 


#4@48" 


#4@12" 


#;5@12" 


5 


#3@12" 


Design required 


Design required 


6 


Design required 


Design required 


Design required 


7 


Design required 


Design required 


Design required 


8 


8 


4 


N/R 


N/R 


N/R 


5 


N/R 


#3@12";#4@24"; 
#5@36" 


#3@12";#5@24" 


6 


■#3@12";#4@24"; 
#5@36" 


#4@12";#5@24" 


#4@12" 


7 


#3@12";#6@24" 


#4@12" 


#:5@12" 


9 


4 


N/R 


N/R 


N/R 


5 


N/R 


#3@12";#5@24" 


#3@12";#5@24" 


6 


#3@12";#4@24" 


#4@12" 


#4@12" 


7 


#4@12";#5@24" 


#5@12" 


#5@12" 


8 


#4@12" 


#5@12" 


#8@12" 


10 


4 


N/R 


#3@12";#4@24"; 
#6@36" 


#3@12";#5@24" 


5 


N/R 


#3@12";#4@24"; 
#6@36" 


#4@12";#5@24" 


6 


#3@12";#5@24" 


#4@12" 


#5@12" 


7 


#4@12" 


#5@12" 


#6@12" 


8 


#4@12" 


#6@12" 


Design required 


9 


#5@12" 


Design required 


Design required 



I For Sr. 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 pound per square foot = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified concrete strength of 2500 psi, reinforcing steel with a minimum yield strength of 40,000 psi. When rein- 
forcing steel with a minimum yield strength of 60,000 psi is used, the spacing of the reinforcement shall be increased 12 inches but in no case greater than 48 inches 
on center. 

b. This table is not intended to prohibit the use of an ICF manulacturer's tables based on engineering analysis in accordance with ACI 318. 

c. N/R denotes "not required." 

d. Deflection criteria: L/240. 

e. Inteipolation between rebar sizes and spacing is not permitted. 

f. Refer to Table R611 .4(2) for wall dimensions. , 

g. Unbalanced backfill height is the difference in height of the exterior and interior finished ground. Where an interior concrete slab is provided, the unbalanced back- 
fill height shall be measured from the exterior finished ground level to the top of ;the interior concrete slab. 

h. Soil classes are in accordance with the Unified Soil Classification System. Refer; to Table R405.I. 



92 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FOUNDATIONS 



TABLE R404.4(5) 
SCREEN-GRID ICF FOUNDATION WALLS^- "=•"■« 



MINIMUM NOMINAL 

WALL THICKNESS* 

(inches) 


HEIGHT OF 

BASEMENT WALL 

(feet) 


MAXIMUM 

UNBALANCED 

BACKFILL HEIGHT^ 

(feet) 


MINIMUM VERTICAL REINFORCEMENT SIZE AND SPACING 


Soil classes^ and design lateral soil load (psf per foot of depth) 


GW, GP, SW and SP 
30 


GM, GC, SM, SM-SC and ML 
45 


SC, ML-CL and inorganic CL 
60 


6 


8 


4 


#4@48" 


#3@12";#4@24"; 
#5@36" 


#3@12";#5@24" 


5 


#3@12";#4@24" 


#3@12" 


#4@12" 


6 


#4@12" 


#5@12" 


Design required 


7 


#4@12" 


Design required 


Design required 


9 


4 


#4@48" 


#3@12";#4@24" 


#3@12";#6@24" 


5 


#3@12";#5@24" 


#4@12" 


#7@12" 


6 


#4@12" 


Design required 


Design required 


7 


Design required 


Design required 


Design required 


8 


Design required 


Design required 


Design required 


10 


4 


#4@48" 


#3@12";#5@24" 


#3@12" 


5 


#3@12" 


#4@12" 


#7@12" 


6 


#4@12" 


Design required 


Design required 


7 


Design required 


Design required 


Design required 


8 


Design required 


Design required 


Design required 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 pound per square foot = 0.0479 kPa. | 

a. This table is based on concrete with a minimum specified concrete strength of 2500 psi, reinforcing steel with a minimum yield strength of 40,000 psi. When rein- 
forcing steel with a minimum yield strength of 60,000 psi is used, the spacing of the reinforcement in the shaded cells shall be increased 12 inches. 

b. This table is not intended to prohibit the use of an ICF manulacturer's tables based on engineering analysis in accordance with ACI 318. 

c. N/R denotes "not required." 

d. Deflection criteria: L/240. 

e. Interpolation between rebar sizes and spacing is not permitted. 

f. Refer to Table R611.4(2) for wall dimensions. 

g. Unbalanced backfill height is the difference in height of the exterior and interior finished ground. Where an interior concrete slab is provided, the unbalanced bacJi- 
fill height shall be measured from the exterior finished ground level to the top of the interior concrete slab. 

h. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1. 



R406.3.4 Backfill. The remainder of the excavated area 
shall be backfilled with the same type of soil as was removed 
during the excavation. 



or footing are exempt from the bottom end lateral displace- 
ment requirement within underfloor areas enclosed by a 
continuous foundation. 



SECTION R407 
COLUMNS 

R407.1 Wood column protection. Wood columns shall be 
protected against decay as set forth in Section R319. 

R407.2 Steel column protection. All surfaces (inside and out- 
side) of steel columns shall be given a shop coat of 
rust-inhibitive paint, except for corrosion-resistant steel and 
steel treated with coatings to provide corrosion resistance. 

R407.3 Structural requirements. The columns shall be 
restrained to prevent lateral displacement at the bottom end. 
Wood columns shall not be less in nominal size than 4 inches by 
4 inches (102 mm by 102 mm) and steel columns shall not be 
less than 3 -inch-diameter (76 mm) standard pipe or approved 
equivalent. 

Exception: In Seismic Design Categories A, B and C col- 
umns no more than 48 inches (1219 mm) in height on a pier 



SECTION R408 
UNDER-FLOOR SPACE 

R408.1 Ventilation. The under-floor space between the bot- 
tom of the floor joists and the earth under any building (except 
space occupied by a basement) shall have ventilation openings 
through foundation walls or exterior walls. The minimum net 
area of ventilation openings shall not be less than 1 square foot 
(0.0929 m^) for each 150 square feet (14 m^) of under-floor 
space area. One such ventilating opening shall be within 3 feet 
(914 mm) of each corner of the building. 

R408.2 Openings for under-floor ventilation. The minimum 
net area of ventilation openings shall not be less than 1 square 
foot (0.0929 m^) for each 150 square feet (14 m^) of under-floor 
area. One ventilating opening shall be within 3 feet (914 mm) 
of each comer of the building. Ventilation openings shall be 
covered for their height and width with any of the following 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



93 



FOUNDATIONS 



TABLE R405.1 
PROPERTIES OF SOILS CLASSIFIED ACCORDING TO THE UNIFIED SOIL CLASSIFICATION SYSTEM 



SOIL 
GROUP 


UNIFIED SOIL 
CLASSIFICATION 
SYSTEM SYMBOL 


SOIL DESCRIPTION 


DRAINAGE 
CHARACTERISTICS^ 


FROST HEAVE 
POTENTIAL 


volume change 
potential 
expansion" 


Group I 


GW 


Well-graded gravels, gravel sand mixtures, 
little or no fines 


Good 


Low 


Low 


GP 


Poorly graded gravels or gravel sand 
mixtures, little or no fines 


Good 


Low 


Low 


sw 


Well-graded sands, gravelly sands, little or 
no fines 


Good 


Low 


Low 


SP 


Poorly graded sands or gravelly sands, little 
or no fines 


Good 


Low 


Low 


GM 


Silty gravels, gravel-sand-silt mixtures 


Good 


Medium 


Low 


SM 


Silty sand, sand-silt mixtures 


Good 


Medium 


Low 


Group II 


GC 


Clayey gravels, gravel-sand-clay mixtures 


Medium 


Medium 


Low 


SC 


Clayey sands, sand-clay mixture 


Medium 


Medium 


Low 


ML 


Inorganic silts and very fine sands, rock 
flour, silty or clayey fine sands or clayey 
silts with slight plasticity 


Medium 


High 


Low 


CL 


Inorganic clays of low to medium plasticity, 
gravelly clays, sandy clays, silty clays, lean 
clays 


Medium 


Medium 


Medium 
to Low 


Group III 


CH 


Inorganic clays of high plasticity, fat clays 


Poor 


Medium 


High 


MH 


Inorganic silts, micaceous or diatomaceous 
fine sandy or silty soils, elastic silts 


Poor 


High 


High 


Group IV 


OL 


Organic silts and organic silty clays of lo\v 
plasticity 


Poor 


Medium 


Medium 


OH 


Organic clays of medium to high plasticity, 
organic silts 


Unsatisfactory 


Medium 


High 


Pt 


Peat and other highly organic soils 


Unsatisfactory 


Medium 


High 



For SI: 1 inch = 25.4 mm. 

a. The percolation rate for good drainage is over 4 inches per hour, medium drainage is 2 inches to 4 inches per hour, and poor is less than 2 inches per hour. 

b. Soils with a low potential expansion typically have a plasticity index (PI) of to 15, soils with a medium potential expansion have a PI of 10 to 35 and soils with a 
high potential expansion have a PI greater than 20. 



materials provided that the least dimension of the covering 
shall not exceed V4 inch (6.4 rrmi): 

1. Perforated sheet metal plates not less than 0.070 inch 
(1.8 mm) thick. 

2. Expanded sheet metal plates not less than 0.047 inch (1.2 
mm) thick. 

3. Cast-iron grill or grating. 

4. Extruded load-bearing brick vents. 

5. Hardware cloth of 0.035 inch (0.89 mm) wire or heavier. 

6. Corrosion-resistant wire mesh, with the least dimension 
being Vg inch (3.2 mm). 

R408.3 Unvented crawl space. Ventilation openings in 
under-floor spaces specified in Sections R408.1 and R408.2 
shall not be required where: 

1. Exposed earth is covered with a continuous vapor 
retarder. Joints of the vapor retarder shall overlap by 6 



inches (152 mm) and shall be sealed or taped. The edges 
of the vapor retarder shall extend at least 6 inches (152 
mm) up the stem wall and shall be attached and sealed to 
the stem wall; and 

2. One of the following is provided for the under-floor 
space: 

2.1. Continuously operated mechanical exhaust ven- 
tilation at a rate equal to 1 cfm (0.47 L/s) for each 
50 ft^ (4.7 m^) of crawlspace floor area, including 
an air pathway to the common area (such as a 
duct or transfer grille), and perimeter walls insu- 
lated in accordance with Section Nl 102.2.8; 

2.2. Conditioned air supply sized to deliver at a rate 
equal to 1 cfm (0.47 L/s) for each 50 ft^ (4.7 m^) 
of under-floor area, including a return air path- 
way to the common area (such as a duct or trans- 
fer grille), and perimeter walls insulated in 
accordance with Section Nl 102.2.8' 



94 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



FOUNDATIONS 



2.3. Plenum complying with Section M1601.4, if 
under-floor space is used as a plenum. 

R408.4 Access. Access shall be provided to all under-floor 
spaces. Access openings through the floor shall be a minimum 
of 18 inches by 24 inches (457 mm by 610 mm). Openings 
through a perimeter wall shall be not less than 16 inches by 24 
inches (407 mm by 610 mm). When any portion of the 
through- wall access is below grade, an areaway not less than 16 
inches by 24 inches (407 mm by 610 mm) shall be provided. 
The bottom of the areaway shall be below the threshold of the 
access opening. Through wall access openings shall not be 
located under a door to the residence. See Section M1305.1.4 
for access requirements where mechanical equipment is 
located under floors. 

R408.5 Removal of debris. The under-floor grade shall be 
cleaned of all vegetation and organic material. All wood forms 
used for placing concrete shall be removed before a building is 
occupied or used for any purpose. All construction materials 
shall be removed before a building is occupied or used for any 
purpose. 

R408.6 Finished grade. The finished grade of under-floor sur- 
face may be located at the bottom of the footings; however, 
where there is evidence that the groundwater table can rise to 
within 6 inches (152 mm) of the finished floor at the building 
perimeter or where there is evidence that the surface water does 
not readily drain from the building site, the grade in the 
under-floor space shall be as high as the outside finished grade, 
unless an approved drainage system is provided. 

R408.7 Flood resistance. For buildings located in areas prone 
to flooding as established in Table R301.2(l): 

1 . Walls enclosing the under-floor space shall be provided 
with flood openings in accordance with Section 
R324.2.2. 

2. The finished ground level of the under-floor space shall 
be equal to or higher than the outside finished ground 
level. 

Exception: Under-floor spaces that meet the require- 
ments of FEM A/FIA TB 1 1 - 1 . 



2006 INTERNATIONAL RESIDENTIAL CODE® 95 



96 2006 INTERNATIONAL RESIDENTIAL CODE*' 



CHAPTER 5 

FLOORS 



SECTION R501 
GENERAL 

R501.1 Application. The provisions of this chapter shall con- 
trol the design and construction of the floors for all buildings 
including the floors of attic spaces used to house mechanical or 
plumbing fixtures and equipment. 

R501.2 Requirements. Hoor construction shall be capable of 
accommodating all loads according to Section R301 and of trans- 
mitting the resulting loads to the supporting structural elements. 



SECTION R502 
WOOD FLOOR FRAMING 

R502.1 Identification. Load-bearing dimension lumber for 
joists, beams and girders shall be identified by a grade mark of 
a lumber grading or inspection agency that has been approved 
by an accreditation body that complies with DOC PS 20. In lieu 
of a grade mark, a certificate of inspection issued by a lumber 
grading or inspection agency meeting the requirements of this 
section shall be accepted. 

R502.1.1 Preservative-treated lumber. Preservative treated 
dimension lumber shall also be identified as required by Sec- 
tion R3 19.1. 

R502.1.2 Blocking and subflooring. Blocking shall be a 
minimum of utility grade lumber. Subflooring may be a mini- 
mum of utility grade lumber or No. 4 common grade boards. 

R502.1.3 End-jointed lumber. Approved end-jointed lum- 
ber identified by a grade mark conforming to Section 
R502. 1 may be used interchangeably with solid-sawn mem- 
bers of the same species and grade. 

R502.1.4 Prefabricated wood I-joists. Structural capaci- 
ties and design provisions for prefabricated wood I-joists 
shall be established and monitored in accordance with 
ASTM D 5055. 

R502.1.5 Structural glued laminated timbers. Glued 
laminated timbers shall be manufactured and identified as 
required in AITC A190.1 and ASTM D 3737. 

R502.1.6 Structural log members. Stress grading of struc- 
tural log members of nonrectangular shape, as typically 
used in log buildings, shall be in accordance with ASTM D 
3957. Such structural log members shall be identified by the 
grade mark of an approved lumber grading or inspection 
agency. In lieu of a grade mark on the material, a certificate 
of inspection as to species and grade issued by a lum- 
ber-grading or inspection agency meeting the requirements 
of this section shall be permitted to be accepted. 

R502.2 Design and construction. Floors shall be designed 
and constructed in accordance with the provisions of this chap- 
ter. Figure R502.2 and Sections R319 and R320 or in accor- 
dance with AF&PA/NDS. 



R502.2.1 Framing at braced wall lines. A load path for 
lateral forces shall be provided between floor framing and 
braced wall panels located above or below a floor, as speci- 
fied in Section R602.10.8. 

R502.2.2 Decks. Where supported by attachment to an 
exterior wall, decks shall be positively anchored to the pri- 
mary structure and designed for both vertical and lateral 
loads as applicable. Such attachment shall not be accom- 
plished by the use of toenails or nails subject to withdrawal. 
Where positive connection to the primary building structure 
cannot be verified during inspection, decks shall be self- 
supporting. For decks with cantilevered framing members, 
connections to exterior walls or other framing members, 
shall be designed and constructed to resist uplift resulting 
from the full live load specified in Table R301.5 acting on 
the cantilevered portion of the deck. 

R502.3 Allowable joist spans. Spans for floor joists shall be in 
accordance with Tables R502.3.1(l) and R502.3.1(2). For 
other grades and species and for other loading conditions, refer 
to the AF&PA Span Tables for Joists and Rafters. 

R502.3.1 Sleeping areas and attic joists. Table 
R502.3 . 1 ( 1 ) shall be used to determine the maximum allow- 
able span of floor joists that support sleeping areas and attics 
that are accessed by means of a fixed stairway in accordance 
with Section R3 1 1 .5 provided that the design live load does 
not exceed 30 psf (1.44 kPa) and the design dead load does 
not exceed 20 psf (0.96 kPa). The allowable span of ceiling 
joists that support attics used for limited storage or no stor- 
age shall be determined in accordance with Section R802.4. 

R502.3.2 Other floor joists. Table R502.3.1(2) shall be 
used to determine the maximum allowable span of floor 
joists that support all other areas of the building, other than 
sleeping rooms and attics, provided that the design live load 
does not exceed 40 psf (1.92 kPa) and the design dead load 
does not exceed 20 psf (0.96 kPa). 

R502.3.3 Floor cantilevers. Floor cantilever spans shall not 
exceed the nominal depth of the wood floor joist. Hoor canti- 
levers constructed in accordance with Table R502.3.3(l) 
shall be permitted when supporting a light-frame bearing 
wall and roof only. Roor cantilevers supporting an exterior 
balcony are permitted to be constructed in accordance with 
Table R502.3.3(2). 

R502.4 Joists under bearing partitions. Joists under parallel 
bearing partitions shall be of adequate size to support the load. 
Double joists, sized to adequately support the load, that are sep- 
arated to permit the installation of piping or vents shall be full 
depth solid blocked with lumber not less than 2 inches (5 1 mm) 
in nominal thickness spaced not more than 4 feet (1219 mm) on 
center. Bearing partitions perpendicular to joists shall not be 
offset from supporting girders, walls or partitions more than 
the joist depth unless such joists are of sufficient size to carry 
the additional load. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



97 



FLOORS 



BOTTOM WALL 
PLATE 



OPTIONAL FINISH 
FLOOR 



STUDS 



2 IN. CLEARANCE- 
SEE SECTION 
R1 003.1 2 



FIREPLACE 




/SUBFLOOROR 
FLOOR SHEATH! NG- 
SEE SECTION R503 



WOOD STRUCTURAL 
PANEL 



N 




JOISTS— SEE TABLES 
R502.3.1 (1) AND R502.3.1 (2) 



^ 



7\ 



HEADER— DOUBLE IF 
MORE THAN 4 FT SPAN 



USE HANGER IF HEADER 

SPANS MORE THAN 

6 FT ,^ 



SOLID 

BLOCKING— SEE 
SECTION R502.7 



\ 



SILLPU\TE> 



FOUNDATION , 



E 



LAPJ0IST3IN. MIN. OR 
SPLICE— SEE SECTION 
R502.6.1 




GIRDER— SEE TABLES 
R502.5(1) ANDR502.5(2) 



\] 



•PIER 



.\ 



/ 



SILL PLATE 



BAND, RIM OR 
HEADER JOIST 



BRIDGING BETWEEN 
JOISTS— SEE SECTION 
R502.7.1 



PROVISION FOR PIPES 
AND VENTS 



DOUBLE JOISTS UNDER BEARING 
PARTITIONS. IF JOISTS ARE 
SEPARATED FOR PIPES, BLOCK 
4 FT ON CENTER MAXIMUM 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



FIGURE R502.2 
FLOOR CONSTRUCTION 



98 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



FLOORS 



TABLE R502.3.1(1) 
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES 









Residential 


sleeping areas, live loac 


i = 30 psf, U 


A = 360)^ 








JOIST 
SPACING 
(inches) 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x6 


2x8 


2x10 


2x12 


2x6 , 


2x8 


2x10 


2x12 


Maximum floor joist spans 


SPECIES AND GRADE 




(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 




Douglas fir-larch 


SS 


12-6 


16-6 


21-0 


25-7 


12-6 


16-6 


21-0 


25-7 




Douglas fir-larch 


#1 


12-0 


15-10 


20-3 


24-8 


12-0 


15-7 


19-0 


22-0 




Douglas fir-larch 


#2 


11-10 


15-7 


19-10 


23-0 


11-6 


14-7 


17-9 


20-7 




Douglas fir-larch 


#3 


9-8 


12-4 


15-0 


17-5 


8-8 


11-0 


13-5 


15-7 




Hem-fir 


SS 


11-10 


15-7 


19-10 


24-2 


11-10 


15-7 


19-10 


24-2 




Hem-fir 


#1 


11-7 


15-3 


19-5 


23-7 


11-7 


15-2 


18-6 


21-6 




Hem-fir 


#2 


11-0 


14-6 


18-6 


22-6 


11-0 


14-4 


17-6 


20-4 


12 


Hem-fir 


#3 


9-8 


12-4 


15-0 


17-5 


8-8 


11-0 


13-5 


15-7 


Southern pine 


SS 


12-3 


16-2 


20-8 


25-1 


12-3 


16-2 


20-8 


25-1 




Southern pine 


#1 


12-0 


15-10 


20-3 


24-8 


12-0 


15-10 


20-3 


24-8 




Southern pine 


#2 


11-10 


15-7 


19-10 


24-2 


11-10 


15-7 


18-7 


21-9 




Southern pine 


#3 


10-5 


13-3 


15-8 


18-8 


9-4 


11-11 


14-0 


16-8 




Spruce-pine-fir 


SS 


11-7 


15-3 


19-5 


23-7 


11-7 


15-3 


19-5 


23-7 




Spruce-pine-fir 


#1 


11-3 


14-11 


19-0 


23-0 


11-3 


14-7 


17-9 


20-7 




Spruce-pine-fir 


#2 


11-3 


14-11 


19-0 


23-0 


11-3 


14-7 


17-9 


20-7 




Spruce-pine-fir 


#3 


9-8 


12-4 


15-0 


17-5 


8-8 


11-0 


13-5 


15-7 




Douglas fir-larch 


SS 


11-4 


15-0 


19-1 


23-3 


11-4 


15-0 


19-1 


23-0 




Douglas fir-larch 


#1 


10-11 


14-5 


18-5 


21-4 


10-8 


13-6 


16-5 


19- 1 




Douglas fir-larch 


#2 


10-9 


14-1 


17-2 


19-11 


9-11 


12-7 


15-5 


17-10 




Douglas fir-larch 


#3 


8-5 


10-8 


13-0 


15-1 


7-6 


9-6 


11-8 


13-6 




Hem-fir 


SS 


10-9 


14-2 


18-0 


21-11 


10-9 


14-2 


18-0 


21-11 




Hem-fir 


#1 


10-6 


13-10 


17-8 


20-9 


10-4 


13-1 


16-0 


18-7 




Hem-fir 


#2 


10-0 


13-2 


16-10 


19-8 


9-10 


12-5 


15-2 


17-7 


16 


Hem-fir 


#3 


8-5 


10-8 


13-0 


15-1 


7-6 


9-6 


11-8 


13-6 


Southern pine 


SS 


11-2 


14-8 


18-9 


22-10 


11-2 


14-8 


18-9 


22-10 




Southern pine 


#1 


10-11 


14-5 


18-5 


22-5 


10-11 


14-5 


17-11 


21-4 




Southern pine 


#2 


10-9 


14-2 


18-0 


21- 1 


10-5 


13-6 


16-1 


18-10 




Southern pine 


#3 


9-0 


11-6 


13-7 


16-2 


8-1 


10-3 


12-2 


14-6 




Spruce-pine-fir 


SS 


10-6 


13-10 


17-8 


21-6 


10-6 


13-10 


17-8 


21-4 




Spruce-pine-fir 


#1 


10-3 


13-6 


17-2 


19-11 


9-11 


12-7 


15-5 


17-10 




Spruce-pine-fir 


#2 


10-3 


13-6 


17-2 


19-11 


9-11 


12-7 


15-5 


17-10 




Spruce-pine-fir 


#3 


8-5 


10-8 


13-0 


15-1 


7-6 


9-6 


11-8 


13-6 




Douglas fir-larch 


SS 


10-8 


14-1 


18-0 


21-10 


10-8 


14-1 


18-0 


21-0 




Douglas fir-larch 


#1 


10-4 


13-7 


16-9 


19-6 


9-8 


12-4 


15-0 


17-5 




Douglas fir-larch 


#2 


10-1 


12-10 


15-8 


18-3 


9-1 


11-6 


14-1 


16-3 




Douglas fir-larch 


#3 


7-8 


9-9 


11-10 


13-9 


6-10 


8-8 


10-7 


12-4 




Hem-fir 


SS 


10- 1 


13-4 


17-0 


20-8 


10-1 


13-4 


17-0 


20-7 




Hem-fir 


#1 


9-10 


13-0 


16-4 


19-0 


9-6 


12-0 


14-8 


17-0 




Hem-fir 


#2 


9-5 


12-5 


15-6 


17-1 


8-11 


11-4 


13-10 


16- 1 


19.2 


Hem-fir 


#3 


7-8 


9-9 


11-10 


13-9 


6-10 


8-8 


10-7 


12-4 


Southern pine 


SS 


10-6 


13-10 


17-8 


21-6 


10-6 


13-10 


17-8 


21-6 




Southern pine 


#1 


10-4 


13-7 


17-4 


21-1 


10-4 


13-7 


16-4 


19-6 




Southern pine 


#2 


10-1 


13-4 


16-5 


19-3 


9-6 


12-4 


14-8 


17-2 




Southern pine 


#3 


8-3 


10-6 


12-5 


14-9 


7-4 


9-5 


11-1 


13-2 




Spruce-pine-fir 


SS 


9- 10 


13-0 


16-7 


20-2 


9-10 


13-0 


16-7 


19-6 




Spruce-pine-fir 


#1 


9-8 


12-9 


15-8 


18-3 


9-1 


11-6 


14- 1 


16-3 




Spruce-pine-fir 


#2 


9-8 


12-9 


15-8 


18-3 


9-1 


11-6 


14- 1 


16-3 




Spmce-pine-fir 


#3 


7-8 


9-9 


11-10 


13-9 


6-10 


8-8 


10-7 


12-4 




Douglas fir-larch 


SS 


9-11 


13-1 


16-8 


20-3 


9-11 


13-1 


16-2 


18-9 




Douglas fir-larch 


#1 


9-7 


12-4 


15-0 


17-5 


8-8 


11-0 


13-5 


15-7 




Douglas fir-larch 


#2 


9- 1 


11-6 


14-1 


16-3 


8-1 


10-3 


12-7 


14-7 




Douglas fir-larch 


#3 


6-10 


8-8 


10-7 


12-4 


6-2 


7-9 


9-6 


11-0 




Hem-fir 


SS 


9-4 


12-4 


15-9 


19-2 


9-4 


12-4 


15-9 


18-5 




Hem-fir 


#1 


9-2 


12-0 


14-8 


17-0 


8-6 


10-9 


13-1 


15-2 




Hem-fir 


#2 


8-9 


11-4 


13-10 


16-1 


8-0 


10-2 


12-5 


14-4 


24 


Hem-fir 


#3 


6-10 


8-8 


10-7 


12-4 


6-2 


7-9 


9-6 


11-0 


Southern pine 


SS 


9-9 


12-10 


16-5 


19-11 


9-9 


12-10 


16-5 


19-11 




Southern pine 


#1 


9-7 


12-7 


16-1 


19-6 


9-7 


12-4 


14-7 


17-5 




Southern pine 


#2 


9-4 


12-4 


14-8 


17-2 


8-6 


11-0 


13-1 


15-5 




Southern pine 


#3 


7-4 


9-5 


11-1 


13-2 


6-7 


8-5 


9-11 


11-10 




Spruce-pine-fir 


SS 


9-2 


12-1 


15-5 


18-9 


9-2 


12- 1 


15-0 


17-5 




Spruce-pine-fir 


#1 


8-11 


11-6 


14-1 


16-3 


8-1 


10-3 


12-7 


14-7 




Spruce-pine-fir 


#2 


8-11 


11-6 


14- 1 


16-3 


8-1 


10-3 


12-7 


14-7 




Spruce-pine-fir 


#3 


6-10 


8-8 


10-7 


12-4 


6-2 


7-9 


9-6 


11-0 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 

NOTE: Check sources for availability of lumber in lengths greater than 20 feet. 

a. Dead load limits for townhouses in Seismic Design Category C and all structures in Seismic Design Categories Dg, Dj and D2 shall be determined in accordance I 



with Section R301. 2.2.2.1. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



99 



FLOORS 



TABLER502.3.1(2) 

FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES 

(Residential living areas, live load = 40 psf, UA = 360)'' 



JOIST 
SPACING 
(inches) 






DEAD LOAD =10 psf 


DEAD LOAD = 20 psf 


2x6 


2x8 


2x10 


2x12 


2x6 


2x6 


2x10 


2x12 


Maximum floor joist spans 


SPECIES AND GRADE 




(ft- in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 


(ft -in.) 




Douglas fir-larch 


SS 


11-4 


15-0 


19-1 


23-3 


11-4 


15-0 


19-1 


23-3 




Douglas fir-larch 


#1 


10-11 


14-5 


18-5 


22-0 


10-11 


14-2 


17-4 


20- 1 




Douglas fir-larch 


#2 


10-9 


14-2 


17-9 


20-7 


10-6 


13-3 


16-3 


18-10 




Douglas fir-larch 


#3 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 




Hem-fir 


SS 


10-9 


14-2 


18-0 


21-11 


10-9 


14-2 


18-0 


21-11 




Hem-fir 


#1 


10-6 


13-10 


17-8 


21-6 


10-6 


13-10 


16-11 


19-7 




Hem-fir 


#2 


10-0 


13-2 


16-10 


20-4 


10-0 


13-1 


16-0 


18-6 


12 


Hem-fir 


#3 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 


Southern pine 


SS 


11-2 


14-8 


18-9 


22-10 


11-2 


14-8 


18-9 


22-10 




Southern pine 


#1 


10-11 


14-5 


18-5 


22-5 


10-11 


14-5 


18-5 


22-5 




Southern pine 


#2 


10-9 


14-2 


18-0 


21-9 


10-9 


14-2 


16-11 


19-10 




Southern pine 


#3 


9-4 


11-11 


14-0 


16-8 


8-6 


10-10 


12-10 


15-3 




Spruce-pine-fir 


SS 


10-6 


13-10 


17-8 


21-6 


10-6 


13-10 


17-8 


21-6 




Spruce-pine-fir 


#1 


10-3 


13-6 


17-3 


20-7 


10-3 


13-3 


16-3 


18-10 




Spruce-pine-fir 


#2 


10-3 


13-6 


17-3 


20-7 


10-3 


13-3 


16-3 


18-10 




Spruce-pine-fir 


#3 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 




Douglas fir-larch 


SS 


10-4 


13-7 


17-4 


21-1 


10-4 


13-7 


17-4 


21-0 




Douglas fir-larch 


#1 


9-11 


13-1 


16-5 


19-1 


9-8 


12-4 


15-0 


17-5 




Douglas fir-larch 


#2 


9-9 


12-7 


15-5 


17-10 


9-1 


11-6 


14-1 


16-3 




Douglas fir-larch 


#3 


7-6 


9-6 


11-8 


13-6 


6-10 


8-8 


10-7 


12-4 




Hem-fir 


SS 


9-9 


12-10 


16-5 


19-11 


9-9 


12-10 


16-5 


19-11 




Hem-fir 


#1 


9-6 


12-7 


16-0 


18-7 


9-6 


12-0 


14-8 


17-0 




Hem-fir 


#2 


9-1 


12-0 


15-2 


17-7 


8-11 


11-4 


13-10 


16- 1 


16 


Hem-fir 


#3 


7-6 


9-6 


11-8 


13-6 


6-10 


8-8 


10-7 


12-4 


Southern pine 


SS 


10-2 


13-4 


17-0 


20-9 


■ 10-2 


13-4 


17-0 


20-9 




Southern pine 


#1 


9-11 


13-1 


16-9 


20-4 


9-11 


13-1 


16-4 


19-6 




Southern pine 


#2 


9-9 


12-10 


16-1 


18-10 


9-6 


12-4 


14-8 


17-2 




Southern pine 


#3 


8-1 


10-3 


12-2 


14-6 


7-4 


9-5 


11-1 


13-2 




Spruce-pine-fir 


SS 


9-6 


12-7 


16-0 


19-6 


9-6 


12-7 


16-0 


19-6 




Spruce-pine-fir 


#1 


9-4 


12-3 


15-5 


17-10 


9-1 


11-6 


14-1 


16-3 




Spruce-pine-fir 


#2 


9-4 


12-3 


15-5 


17-10 


9-1 


11-6 


14-1 


16-3 




Spruce-pine-fir 


#3 


7-6 


9-6 


11-8 


13-6 


6-10 


8-8 


10-7 


12-4 




Douglas fir-larch 


SS 


9-8 


12-10 


16-4' 


19-10 


9-8 


12-10 


16-4 


19-2 




Douglas fir-larch 


#1 


9-4 


12-4 


15- 0' 


17-5 


8-10 


11-3 


13-8 


15-11 




Douglas fir-larch 


#2 


9-1 


11-6 


14-1 


16-3 


8-3 


10-6 


12-10 


14-10 




Douglas fir-larch 


#3 


6-10 


8-8 


10-7' 


12-4 


6-3 


7-11 


9-8 


11-3 




Hem-fir 


SS 


9-2 


12-1 


15-5 


18-9 


9-2 


12-1 


15-5 


18-9 




Hem-fir 


#1 


9-0 


11-10 


14- 8^ 


17-0 


8-8 


10-11 


13-4 


15-6 




Hem-fir 


#2 


8-7 


11-3 


13-iq 


16-1 


8-2 


10-4 


12-8 


14-8 


19.2 


Hem-fir 


#3 


6-10 


8-8 


10-7 


12-4 


6-3 


7-11 


9-8 


11-3 


Southern pine 


SS 


9-6 


12-7 


16- 


19-6 


9-6 


12-7 


16-0 


19-6 




Southern pine 


#1 


9-4 


12-4 


15-91 


19-2 


9-4 


12-4 


14-11 


17-9 




Southern pine 


#2 


9-2 


12-1 


14-8 


17-2 


8-8 


11-3 


13-5 


15-8 




Southern pine 


#3 


7-4 


9-5 


11- 1. 


13-2 


6-9 


8-7 


10-1 


12- 1 




Spruce-pine-fir 


SS 


9-0 


11-10 


15- 1 


18-4 


9-0 


11-10 


15-1 


17-9 




Spruce-pine-fir 


# 


8-9 


11-6 


14- 1 


16-3 


8-3 


10-6 


12-10 


14-10 




Spruce-pine-fir 


#2 


8-9 


11-6 


14- 1: 


16-3 


8-3 


10-6 


12-10 


14-10 




Spruce-pine-fir 


#3 


6-10 


8-8 


10-7 


12-4 


6-3 


7-11 


9-8 


11-3 




Douglas fir-larch 


SS 


9-0 


11-11 


15-2 


18-5 


9-0 


11-11 


14-9 


17-1 




Douglas fir-larch 


#1 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 




Douglas fir-larch 


#2 


8-1 


10-3 


12-7 


14-7 


7-5 


9-5 


11-6 


13-4 




Douglas fir-larch 


#3 


6-2 


7-9 


9-6 


11-0 


5-7 


7-1 


8-8 


10- 1 




Hem-fir 


SS 


8-6 


11-3 


14-4 


17-5 


8-6 


11-3 


14-4 


16-10' 




Hem-fir 


#1 


8-4 


10-9 


13-1 


15-2 


7-9 


9-9 


11-11 


13-10 




Hem-fir 


#2 


7-11 


10-2 


12-5 


14-4 


7-4 


9-3 


11-4 


13-1 


24 


Hem-fir 


#3 


6-2 


7-9 


9-6, 


11-0 


5-7 


7-1 


8-8 


10-1 


Southern pine 


SS 


8-10 


11-8 


14-11 


18-1 


8-10 


11-8 


14-11 


18-1 




Southern pine 


#1 


8-8 


11-5 


14-7 


17-5 


8-8 


11-3 


13-4 


15-11 




Southern pine 


#2 


8-6 


11-0 


13-1 


15-5 


7-9 


10-0 


12-0 


14-0 




Southern pine 


#3 


6-7 


8-5 


9-11 


11-10 


6-0 


7-8 


9-1 


10-9 




Spruce-pine-fir 


SS 


8-4 


11-0 


14-0 


17-0 


8-4 


11-0 


13-8 


15-11 




Spruce-pine-fir 


#1 


8-1 


10-3 


12-7 


14-7 


7-5 


9-5 


11-6 


13-4 




Spruce-pine-fir 


#2 


8-1 


10-3 


12-7 


14-7 


7-5 


9-5 


11-6 


13-4 




Spruce-pine-fir 


#3 


6-2 


7-9 


9-6 


11-0 


5-7 


7-1 


8-8 


10-1 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 
NOTE: Check sources for availability of lumber in lengths greater than 20 feet. 

a. End bearing length shall be increased to 2 inches. 

b. Dead load limits for townhouses in Seismic Design Category C and all structures in Seismic Design Categories Dq, D j , and D2 shall be determined in accordance 



with Section R301.2.2.2.1. 



100 



2006 INTERNATIONAL RESIDENTIAL CODE® 



FLOORS 



TABLE R502.3.3(1) 
CANTILEVER SPANS FOR FLOOR JOISTS SUPPORTING LIGHT-FRAME EXTERIOR BEARING WALL AND ROOF ONLY'- "'"='* a*' 

(Floor Live Load < 40 psf, Roof Live Load < 20 psf) 



Member & Spacing 


Maximum Cantilever Span (Uplift Force at Backspan Support In Lbs.)**' ® 


Ground Snow Load 


< 20 psf 


30 psf 


50 psf 


70 psf 


Roof Widtli 


Roof Width 


Roof Width 


Roof Width 


24 ft 


32 ft 


40 ft 


24 ft 


32 ft 


40 ft 


24 ft 


32 ft 


40 ft 


24 ft 


32 ft 


40 ft 


2 X 8 @ 12" 


20" 

(177) 


15" 

(227) 


— 


18" 
(209) 


— 


— 


— 


— 


— 


— 


— 


— 


2 X 10 @ 16" 


29" 

(228) 


21" 

(297) 


16" 
(364) 


26" 

(271)' 


18" 
(354) 


— 


20" 
(375) 


— 


— 


— 


— 


— 


2 X 10 @ 12" 


36" 
(166) 


26" 
(219) 


20" 
(270) 


34" 
(198) 


22" 
(263) 


16" 

(324) 


26" 

(277) 


— 


— 


19" 

(356) 


— 


— 


2 X 12 @ 16" 


— 


32" 
(287) 


25" 
(356) 


36" 

(263) 


29" 

(345) 


21" 

(428) 


29" 
(367) 


20" 

(484) 


— 


23" 
(471) 




— 


2 X 12 @ 12" 


— 


42" 
(209) 


31" 

(263) 


— 


37" 
(253) 


27" 
(317) 


36" 

(271) 


27" 
(358) 


17" 

(447) 


31" 

(348) 


19" 

(462) 


— 


2 X 12 @ 8" 


— 


48" 
(136) 


45" 
(169) 


— 


48" 
(164) 


38" 
(206) 


— 


40" 

(233) 


26" 
(294) 


36" 

(230) 


29" 
(304) 


18" 

(379) 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. 

a. Tabulated values are for clear-span roof supported solely by exterior bearing walls. 

b. Spans are based on No. 2 Grade lumber of Douglas fir-larch, hem-fir, southern pine, and spruce-pine-fir for repetitive (3 or more) members. 

c. Ratio of backspan to cantilever span shall be at least 3:1. 

d. Connections capable of resisting the indicated uplift force shall be provided at the backspan support. 

e. Uplift force is for a backspan to cantilever span ratio of 3 : 1 . Tabulated uplift values are permitted to be reduced by multiplying by a factor equal to 3 divided by the 
actual backspan ratio provided (3/backspan ratio). 

f. See Section R301.2.2.2.2, Item 1, for additional limitations on cantilevered floor joists for detached one- and two-family dwellings in Seismic Design Category I 
Dq, D] , or Dj and townhouses in Seismic Design Category C, Dg, D^, or D2. I 

g. A full-depth rim joist shall be provided at the cantilevered end of the joists. Solid blocking shall be provided at the cantilever support, 
h. Linear interpolation shall be permitted for building widths and ground snow loads other than shown. 



TABLE R502.3.3(2) 
CANTILEVER SPANS FOR FLOOR JOISTS SUPPORTING EXTERIOR BALCONY^" ^^ 



Member Size 


Spacing 


Maximum Cantilever Span 
(Uplift l=orce at Bacicspan Support in Ibf ■ '' 


Ground Snow Load 


< 30 psf 


50 psf 


70 psf 


2x8 


12" 


42" (139) 


39" (156) 


34" (165) 


2x8 


16" 


36" (151) 


34" (171) 


29" (180) 


2x10 


12" 


61" (164) 


57" (189) 


49" (201) 


2x10 


16" 


53" (180) 


49" (208) 


42" (220) 


2x10 


24" 


43" (212) 


40" (241) 


34" (255) 


2x12 


16" 


72" (228) 


67" (260) 


57" (268) 


2x12 


24" 


58" (279) 


54" (319) 


47" (330) 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. 

a. Spans are based on No. 2 Grade lumber of Douglas fir-larch, hem-fir, southern pine, and spruce-pine-fir for repetitive (3 or more) members. 

b. Ratio of backspan to cantilever span shall be at least 2: 1. 

c. Connections capable of resisting the indicated uplift force shall be provided at the backspan support. 

d. Uplift force is for a backspan to cantilever span ratio of 2: 1 . Tabulated uplift values are permitted to be reduced by multiplying by a factor equal to 2 divided by the 
actual backspan ratio provided (2/backspan ratio). 

e. A full-depth rim joist shall be provided at the cantilevered end of the joists. Solid blocking shall be provided at the cantilevered support. 

f . Linear interpolation shall be permitted for ground snow loads other than shown. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



101 



FLOORS 



TABLE R502.5(1) 

GIRDER SPANS^ AND HEADER SPANS^FOR EXTERIOR BEARING WALLS 

(Maximum spans for Douglas fir-larch, hem-fir, southern pine and spruce-pine-fir'^ and required number of jack studs) 



GIRDERS AND 

HEADERS 
SUPPORTING 


SIZE 


GROUND SNOW LOAD (psf)^ 


30 50 


70 


Building width<= (feet) 


20 


28 


36 


20 


28 


36 


20 


28 


36 


Span 


NJ" 


Span 


NJ" 


Span 


NJ" 


Span 


NJ" 


Span 


NJ'' 


Span 


NJ" 


Span 


NJ" 


Span 


NJ'' 


Span 


NJ"* 


Roof and ceiling 


2-2x4 


3-6 


1 


3-2 


1 


2-10 


1 


3-2 


1 


2-9 


1 


2-6 


1 


2-10 


1 


2-6 


1 


2-3 


1 


2-2x6 


5-5 


1 


4-8 


1 


4-2 


1 


4-8 


1 


4-1 


1 


3-8 


2 


4-2 


1 


3-8 


2 


3-3 


2 


2-2x8 


6-10 


1 


5-11 


2 


5-4 


2 


5-11 


2 


5-2 


2 


4-7 


2 


5-4 


2 


4-7 


2 


4-1 


2 


2-2x10 


8-5 


2 


7-3 


2 


6-6 


2 


7-3 


2 


6-3 


2 


5-7 


2 


6-6 


2 


5-7 


2 


5-0 


2 


2-2x12 


9-9 


2 


8-5 


2 


7-6 


2 


8-5 


2 


7-3 


2 


6-6 


2 


7-6 


2 


6-6 


2 


5-10 


3 


3-2x8 


8-4 


1 


7-5 


1 


6-8 


1 


7-5 


1 


6-5 


2 


5-9 


2 


6-8 


1 


5-9 


2 


5-2 


2 


3-2x10 


10-6 


1 


9-1 


2 


8-2 


2 


9-1 


2 


7-10 


2 


7-0 


2 


8-2 


2 


7-0 


2 


6-4 


2 


,3-2x12 


12-2 


2 


10-7 


2 


9-5 


2 


10-7 


2 


9-2 


2 


8-2 


2 


9-5 


2 


8-2 


2 


7-4 


2 


4-2x8 


9-2 


1 


8-4 


1 


7-8 


1 


8-4 


1 


7-5 


1 


6-8 


1 


7-8 


1 


6-8 


1 


5-11 


2 


4-2x10 


11-8 


1 


10-6 


1 


9-5 


2 


10-6 


1 


9-1 


2 


8-2 


2 


9-5 


2 


8-2 


2 


7-3 


2 


4-2x12 


14-1 


1 


12-2 


2 


10-11 


2 


12-2 


2 


10-7 


2 


9-5 


2 


10-11 


2 


9-5 


2 


8-5 


2 


Roof, ceiling and one 
center-bearing floor 


2-2x4 


3-1 


1 


2-9 


1 


2-5 


1 


2-9 


1 


2-5 


1 


2-2 


1 


2-7 


1 


2-3 


1 


2-0 


1 


2-2x6 


4-6 


1 


4-0 


1 


3-7 


2 


4-1 


1 


3-7 


2 


3-3 


2 


3-9 


2 


3-3 


2 


2-11 


2 


2-2x8 


5-9 


2 


5-0 


2 


4-6 


2 


5-2 


2 


4-6 


2 


4-1 


2 


4-9 


2 


4-2 


2 


3-9 


2 


2-2x10 


7-0 


2 


6-2 


2 


5-6 


2 


6-4 


■2 


5-6 


2 


5-0 


2 


5-9 


2 


5-1 


2 


4-7 


3 


2-2x12 


8-1 


2 


7-1 


2 


6-5 


2 


7-4 


2 


6-5 


2 


5-9 


3 


6-8 


2 


5-10 


3 


5-3 


3 


3-2x8 


7-2 


1 


6-3 


2 


5-8 


2 


6-5 


2 


5-8 


2 


5-1 


2 


5-11 


2 


5-2 


2 


4-8 


2 


3-2x10 


8-9 


2 


7-8 


2 


6-11 


2 


7-11 


2 


6-11 


2 


6-3 


2 


7-3 


2 


6-4 


2 


5-8 


2 


3-2x12 


10-2 


2 


8-11 


2 


8-0 


2 


9-2 


2 


8-0 


2 


7-3 


2 


8-5 


2 


7-4 


2 


6-7 


2 


4-2x8 


8-1 


1 


7-3 


1 


6-7 


1 


7-5 


1 


6-6 


1 


5-11 


2 


6-10 


1 


6-0 


2 


5-5 


2 


4-2x10 


10-1 


1 


8-10 


2 


8-0 


2 


9-1 


2 


8-0 


2 


7-2 


2 


8-4 


2 


7-4 


2 


6-7 


2 


4-2x12 


11-9 


2 


10-3 


2 


9-3 


2 


10-7 


2 


9-3 


2 


8-4 


2 


9-8 


2 


8-6 


2 


7-7 


2 


Roof, ceiling and one 
clear span floor 


2-2x4 


2-8 


1 


2-4 


1 


2-1 


1 


2-7 


1 


2-3 


1 


2-0 


1 


2-5 


1 


2-1 


1 


1-10 


1 


2-2x6 


3-11 


1 


3-5 


2 


3-0 


2 


3-10 


2 


3-4 


2 


3-0 


2 


3-6 


2 


3-1 


2 


2-9 


2 


2-2x8 


5-0 


2 


4-4 


2 


3-10 


2 


4-10 


2 


4-2 


2 


3-9 


2 


4-6 


2 


3-11 


2 


3-6 


2 


2-2x10 


6-1 


2 


5-3 


2 


4-8 


2 


5-11 


2 


5-1 


2 


4-7 


3 


5-6 


2 


4-9 


2 


4-3 


3 


2-2x12 


7-1 


2 


6-1 


3 


5-5 


3 


6-10 


2 


5-11 


3 


5-4 


3 


6-4 


2 


5-6 


3 


5-0 


3 


3-2x8 


6-3 


2 


5-5 


2 


4-10 


2 


6-1 


2 


5-3 


2 


4-8 


2 


5-7 


2 


4-11 


2 


4-5 


2 


3-2x10 


7-7 


2 


6-7 


2 


5-11 


2 


7-5 


2 


6-5 


2 


5-9 


2 


6-10 


2 


6-0 


2 


5-4 


2 


3-2x12 


8-10 


2 


7-8 


2 


6-10 


2 


8-7 


2 


7-5 


2 


6-8 


2 


7-11 


2 


6-11 


2 


6-3 


2 


4-2x8 


7-2 


1 


6-3 


2 


5-7 


2 


7-0 


1 


6-1 


2 


5-5 


2 


6-6 


1 


5-8 


2 


5-1 


2 


4-2x10 


8-9 


2 


7-7 


2 


6-10 


2 


8-7 


2 


7-5 


2 


6-7 


2 


7-11 


2 


6-11 


2 


6-2 


2 


4-2x12 


10-2 


2 


8-10 


2 


7-11 


2 


9-11 


2 


8-7 


2 


7-8 


2 


9-2 


2 


8-0 


2 


7-2 


2 


Roof, ceiling and 

two center-bearing 

floors 


2-2x4 


2-7 


1 


2-3 


1 


2-0 


1 


2-6 


1 


2-2 


1 


1-11 


1 


2-4 


1 


2-0 


1 


1-9 


1 


2-2x6 


3-9 


2 


3-3 


2 


2-11 


2 


3-8 


2 


3-2 


2 


2-10 


2 


3-5 


2 


3-0 


2 


2-8 


2 


2-2x8 


4-9 


2 


4-2 


2 


3-9 


2 


4-7 


■2 


4-0 


2 


3-8 


2 


4-4 


2 


3-9 


2 


3-5 


2 


2-2x10 


5-9 


2 


5-1 


2 


4-7 


3 


5-8 


2 


4-11 


2 


4-5 


3 


5-3 


2 


4-7 


3 


4-2 


3 


2-2x12 


6-8 


2 


5-10 


3 


5-3 


3 


6-6 


'2 


5-9 


3 


5-2 


3 


6-1 


3 


5-4 


3 


4-10 


3 


3-2x8 


5-11 


2 


5-2 


2 


4-8 


2 


5-9 


2 


5-1 


2 


4-7 


2 


5-5 


2 


4-9 


2 


4-3 


2 


3-2x10 


7-3 


2 


6-4 


2 


5-8 


2 


7-1 


2 


6-2 


2 


5-7 


2 


6-7 


2 


5-9 


2 ' 


5-3 


2 


3-2x12 


8-5 


2 


7-4 


2 


6-7 


2 


8-2 


2 


7-2 


2 


6-5 


3 


7-8 


2 


6-9 


2 


6-1 


3 


4-2x8 


6-10 


1 


6-0 


2 


5-5 


2 


6-8 


1 


5-10 


2 


5-3 


2 


6-3 


2 


5-6 


2 


4-11 


2 


4-2x10 


8-4 


2 


7-4 


2 


6-7 


2 


8-2 


2 


7-2 


2 


6-5 


2 


7-7 


2 


6-8 


2 


6-0 


2 


4-2x12 


9-8 


2 


8-6 


2 


7-8 


2 


9-5 


2 


8-3 


2 


7-5 


2 


8-10 


2 


7-9 


2 


7-0 


2 



(continued) 



102 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FLOORS 



TABLE R502.5(1)— continued 

GIRDER SPANS^ AND HEADER SPANS^FOR EXTERIOR BEARING WALLS 

(Maximum spans for Douglas fir-larch, hem-fir, southern pine and spruce-pine-fir" and required number of jack studs) 



GIRDERS AND 

HEADERS 
SUPPORTING 


SIZE 


GROUND SNOW LOAD (psf)^ 


30 


50 70 


Building width^ (feet) 


20 


28 


36 


20 


28 


36 


20 


28 


36 


Span 


NJ" 


Span 


NJ" 


Span 


NJ" 


Span 


NJ'' 


Span 


NJ-- 


Span 


NJ" 


Span 


NJ'' 


Span 


NJ^ 


Span 


NJ'' 


Roof, ceiling, and 

two clear span 

floors 


2-2x4 


2-1 


1 


1-8 


1 


1-6 


2 


2-0 


1 


1-8 


1 


1-5 


2 


2-0 


1 


1-8 


1 


1-5 


2 


2-2x6 


3-1 


2 


2-8 


2 


2-4 


2 


3-0 


2 


2-7 


2 


2-3 


2 


2-11 


2 


2-7 


2 


2-3 


2 


2-2x8 


3-10 


2 


3-4 


2 


3-0 


3 


3-10 


2 


3-4 


2 


2-11 


3 


3-9 


2 


3-3 


2 


2-11 


3 


2-2x10 


4-9 


2 


4-1 


3 


3-8 


3 


4-8 


2 


4-0 


3 


3-7 


3 


4-7 


3 


4-0 


3 


3-6 


3 


2-2x12 


5-6 


3 


4-9 


3 


4-3 


3 


5-5 


3 


4-8 


3 


4-2 


3 


5-4 


3 


4-7 


3 


4-1 


4 


3-2x8 


4-10 


2 


4-2 


2 


3-9 


2 


4-9 


2 


4-1 


2 


3-8 


2 


4-8 


2 


4-1 


2 


3-8 


2 


3-2x10 


5-11 


2 


5-1 


2 


4-7 


3 


5-10 


2 


5-0 


2 


4-6 


3 


5-9 


2 


4-11 


2 


4-5 


3 


3-2x12 


6-10 


2 


5-11 


3 


5-4 


3 


6-9 


2 


5-10 


3 


5-3 


3 


6-8 


2 


5-9 


3 


5-2 


3 


4-2x8 


5-7 


2 


4-10 


2 


4-4 


2 


'5-6 


2 


4-9 


2 


4-3 


2 


5-5 


2 


4-8 


2 


4-2 


2 


4-2x10 


6-10 


2 


5-11 


2 


5-3 


2 


6-9 


2 


5-10 


2 


5-2 


2 


6-7 


2 


5-9 


2 


5-1 


2 


4-2x12 


7-11 


2 


6-10 


2 


6-2 


3 


7-9 


2 


6-9 


2 


6-0 


3 


7-8 


2 


6-8 


2 


5-11 


3 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. 

a. Spans are given in feet and inches. 

b. Tabulated values assume #2 grade lumber 

c. Building width is measured perpendicular to the ridge. Bar widths between those shown, spans are permitted to be interpolated. 

d. NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the header is permitted to be supported by an approved 
framing anchor attached to the full-height wall stud and to the header 

e. Use 30 psf ground snow load for cases in which ground snow load is less than 30 psf and the roof live load is equal to or less than 20 psf. 



R502.5 Allowable girder spans. The allowable spans of gird- 
ers fabricated of dimension lumber shall not exceed the values 
set forth in Tables R502.5(l) and R502.5(2). 

R502.6 Bearing. The ends of each joist, beam or girder shall 
have not less than 1.5 inches (38 mm) of bearing on wood or 
metal and not less than 3 inches (76 mm) on masonry or con- 
crete except where supported on a l-inch-by-4-inch (25.4 mm 
by 102 mm) ribbon strip and nailed to the adjacent stud or by 
the use of approved joist hangers. 

R502.6.1 Floor systems. Joists framing from opposite 
sides over a bearing support shall lap a minimum of 3 inches 
(76 mm) and shall be nailed together with a minimum three 
lOd face nails. A wood or metal splice with strength equal to 
or greater than that provided by the nailed lap is permitted. 

R502.6.2 Joist framing. Joists framing into the side of a 
wood girder shall be supported by approved framing 
anchors or on ledger strips not less than nominal 2 inches by 
2 inches (51 mm by 51 mm). 

R502.7 Lateral restraint at supports. Joists shall be sup- 
ported laterally at the ends by full-depth solid blocking not less 
than 2 inches (51 mm) nominal in thickness; or by attachment 
to a full-depth header, band or rim joist, or to an adjoining stud 
or shall be otherwise provided with lateral support to prevent 
rotation. 

Exception: In Seismic Design Categories Dq, Di and Dj, 
lateral restraint shall also be provided at each intermediate 
support. 

R502.7.1 Bridging. Joists exceeding a nominal 2 inches by 
12 inches (51 mm by 305 mm) shall be supported laterally 



by solid blocking, diagonal bridging (wood or metal), or a 
continuous l-inch-by-3-inch (25.4 mm by 76 mm) strip 
nailed across the bottom of joists perpendicular to joists at 
intervals not exceeding 8 feet (2438 mm). 

R502.8 Drilling and notching. Structural floor members shall 
not be cut, bored or notched in excess of the limitations speci- 
fied in this section. See Figure R502.8. 

R502.8.1 Sawn lumber. Notches in soHd lumber joists, raf- 
ters and beams shall not exceed one-sixth of the depth of the 
member, shall not be longer than one-third of the depth of 
the member and shall not be located in the middle one-third 
of the span. Notches at the ends of the member shall not 
exceed one-fourth the depth of the member. The tension 
side of members 4 inches (102 mm) or greater in nominal 
thickness shall not be notched except at the ends of the 
members. The diameter of holes bored or cut into members 
shall not exceed one-third the depth of the member. Holes 
shall not be closer than 2 inches (5 1 mm) to the top or bot- 
tom of the member, or to any other hole located in the mem- 
ber. Where the member is also notched, the hole shall not be 
closer than 2 inches (5 1 mm) to the notch. 

R502.8.2 Engineered wood products. Cuts, notches and 
holes bored in trusses, structural composite lumber, struc- 
tural glue-laminated members or I-joists are prohibited 
except where permitted by the manufacturer's recommen- 
dations or where the effects of such alterations are specifi- 
cally considered in the design of the member by a registered 
design professional. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



103 



FLOORS 



TABLE R502.5(2) 

GIRDER SPANS' AND HEADER SPANS' FOR INTERIOR BEARING WALLS 

(Maximum spans for Douglas fir-larch, hem-fir, southern pine and spruce-pine-fir'^ and required number of jack studs) 



HEADERS AND GIRDERS SUPPORTING 


SIZE 


BUILDING WIDTH= (feet) 


20 : 


28 


36 


Span 


NJ" 


Span 


NJ" 


Span 


NJ" 


One floor only 


2-2x4 


3-1 


1 


2-8 


1 


2-5 


1 


2-2x6 


4-6 


1 


3-11 


1 


3-6 


1 


2-2x8 


5-9 


1 


5-0 


2 


4-5 


2 


2-2x10 


7-0 


2 


6-1 


2 


5-5 


2 


2-2x12 


8-1 


2 


7-0 


2 


6-3 


2 


3-2x8 


7-2 


1 


6-3 


1 


5-7 


2 


3-2x10 


8-9 


1 


7-7 


2 


6-9 


2 


3-2x12 


10-2 


2 


8-10 


2 


7-10 


2 


4-2x8 


9-0 


1 


7-8 


1 


6-9 


1 


4-2x10 


10-1 


1 


8-9 


1 


7-10 


2 


4-2x12 


11-9 


1 


10-2 


2 


9-1 


2 


Two floors 


2-2x4 


2-2 


1 


1-10 


1 


1-7 


1 


2-2x6 


3-2 


2 


2-9 


2 


2-5 


2 


2-2x8 


4-1 


2 


3-6 


2 


3-2 


2 


2-2x10 


4-11 


2 


4-3 


2 


3-10 


3 


2-2x12 


5-9 


2 


5-0 


3 


4-5 


3 


3-2x8 


5-1 


2 


4-5 


2 


3-11 


2 


3-2x10 


6-2 


2 


5-4 


2 


4-10 


2 


3-2x12 


7-2 


2 


6-3 


2 


5-7 


3 


4-2x8 


6-1 


1 


5-3 


2 


4-8 


2 


4-2x10 


7-2 


2 


6-2 


2 


5-6 


2 


4-2x12 


8-4 


2 


7-2 


2 


6-5 


2 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Spans are given in feet and inches. 

b. Tabulated values assume #2 grade lumber. 

c. Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated. 

d. NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the header is permitted to be supported by an approved 
framing anchor attached to the full-height wall stud and to the header. 



R502.9 Fastening. Roor framing shall be nailed in accordance 
with Table R602.3(l). Where posts and beam or girder construc- 
tion is used to support floor framing, positive connections shall 
be provided to ensure against uplift and lateral displacement. 

R502.10 Framing of openings. Openings in floor framing 
shall be framed with a header and trimmer joists. When the 
header joist span does not exceed 4 feet (1219 mm), the header 
joist may be a single member the same size as the floor joist. 
Single trimmer joists may be used to carry a single header joist 
that is located within 3 feet (914 mm) of the trimmer joist bear- 
ing. When the header joist span exceeds 4 feet (1219 mm), the 
trimmer joists and the header joist shall be doubled and of suffi- 
cient cross section to support the floor joists framing into the 
header. Approved hangers shall be used for the header joist to 
trimmer joist connections when the header joist span exceeds 6 
feet (1829 mm). Tail joists over 12 feet (3658 mm) long shall be 
supported at the header by framing anchors or on ledger strips 
not less than 2 inches by 2 inches (51 mm by 51 mm). 



R502.il Wood trusses. 

R502.11.1 Design. Wood trusses shall be designed in accor- 
dance with approved engineering practice. The design and 
manufacture of metal plate connected wood trusses shall 
comply with ANSI/TPI 1 . The truss design drawings shall 
be prepared by a registered professional where required by 
the statutes of the jurisdiction in which the project is to be 
constructed in accordance with Section R106. 1 . 

R502.11.2 Bracing. Trusses shall be braced to prevent rota- 
tion and provide lateral stabihty in accordance with the 
requirements specified in the construction documents for the 
building and on the individual truss design drawings. In the 

' absence of specific bracing requirements, trusses shall be 
braced in accordance with the Building Component Safety 

' Information (BCSI 1-03) Guide to Good Practice for Han- 
dhng, Instalhng & Bracing of Metal Plate Connected Wood 
Trusses. 



104 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



FLOORS 



L/3 



i-*i r 



D/3MAX, 



U3 



T 



D/6 MAX. 






D/4MAX. 



MAX. D FROM 
SUPPORT 



D/3IVIAX.' 



D/3MAX. 



NO NOTCHES 
PERMITTED 



H_t^, 






r~L 



D/3 MAX. 



g 



D/6 MAX. 



1 



FLOOR JOIST— CENTER CUTS 



D/4 MAX. 



1 



:^ 



I 



FLOOR JOIST-^ND CUTS 






m 



1 



RAFTER/CBUNG JOISTS (R802.7.1) 



2 IN. MIN. FROM TOP 
AND BOTTOM OF JOIST 




PIPE OR CONDUIT 



D (ACTUAL DEPTH) 



For SI: 1 inch = 25.4 mm. 



FIGURE R502.8 
CUTTING, NOTCHING AND DRILLING 



2006 INTERNATIONAL RESIDENTIAL CODE<^ 



105 



FLOORS 



R502.11.3 Alterations to trusses. Truss members and com- 
ponents shall not be cut, notched, spliced or otherwise altered 
in any way without the approval of a registered design profes- 
sional. Alterations resulting in the addition of load (e.g., 
HVAC equipment, water heater, etc.), that exceed the design 
load for the truss, shall not be permitted without verification 
that the truss is capable of supporting the additional loading. 

R502.11.4 Truss design drawings. Truss design drawings, 
prepared in compliance with Section R502. 11.1, shall be sub- 
mitted to the building official and approved prior to installa- 
tion. Truss design drawings shall be provided with the 
shipment of trasses deUvered to the job site. Trass design draw- 
ings shall include, at a minimum, the information specified 
below: 

1. Slope or depth, span and spacing. 

2. Location of all joints. 

3. Required bearing widths. 

4. Design loads as applicable: 

4.1. Top chord live load; 

4.2. Top chord dead load; 

4.3. Bottom chord live load; 

4.4. Bottom chord dead load; 

4.5. Concentrated loads and their points of applica- 
tion; and 

4.6. Controlling wind and earthquake loads. 

5. Adjustments to lumber and joint connector design 
values for conditions of use. 

6. Each reaction force and direction. 

7. Joint connector type and description, e.g., size, 
thickness or gauge, and the dimensioned location of 
each joint connector except where symmetrically 
located relative to the joint interface. 

8. Lumber size, species and grade for each member. 

9. Connection requirements for: 

9.1. Trass-to-girder-trass; 

9.2. Trass ply-to-ply; and 

9.3. Field splices. 

10. Calculated deflection ratio and/or maximum 
description for live and total load. 

11. Maximum axial compression forces in the trass 
members to enable the building designer to design the 
size, connections and anchorage of the permanent 
continuous lateral bracing. Forces shall be shown on 
the trass drawing or on supplemental documents. 

12. Required permanent trass member bracing location. 

R502.12 Draftstopping required. When there is usable space 
both above and below the concealed space of a floor/ceiling 
assembly, draftstops shall be installed so that the area of the 
concealed space does not exceed 1,000 square feet (92.9 m^). 
Draftstopping shall divide the concealed space into approxi- 
mately equal areas. Where the assembly is enclosed by a floor 
membrane above and a ceiling membrane below draftstopping 



shall be provided in floor/ceiling assemblies under the follow- 
ing circumstances: 

1 . Ceiling is suspended under the floor franning. 

2. Floor framing is constracted of trass-type open-web or 
perforated members. 

R502.12.1 Materials. Draftstopping materials shall not be 
less than Vj-inch (12.7 mm) gypsum board, V^-inch (9.5 mm) 
wood stractural panels, Vg-inch (9.5 mm) Type 2-M-W 
particleboard or other approved materials adequately sup- 
ported. Draftstopping shall be installed parallel to the floor 
framing members unless otherwise approved by the building 
official. The integrity of all draftstops shall be maintained. 

R502.13 Fireblocking required. Fireblocking shall be 
provided in accordance with Section R602.8. 

SECTION R503 
FLOOR SHEATHING 

R503.1 Lumber sheathing. Maximum allowable spans for 
lumber used as floor sheathing shall conform to Tables R503. 1 , 
R503.2.1.1(l) and R503.2.1.1(2). 

R503.1.1 End joints. End joints in lumber used as 
subflooring shall occur over supports unless end-matched 
lumber is used, in which case each piece shall bear on at 
least two joists. Subflooring may be omitted when joist 
spacing does not exceed 16 inches (406 mm) and a 1-inch 
(25.4 mm) nominal tongue-and-groove wood strip flooring 
is applied perpendicular to the joists. 

TABLE R503.1 
MINIMUM THICKNESS OF LUMBER FLOOR SHEATHING 



JOIST OR BEAM 
SPACING (inches) 


MINIMUM NET THICKNESS 


Perpendicular to joist 


Diagonal to joist 


24 


'%6 


% 


16 


% 


\ 


48=' 


IV2T&G 


N/A 


54'' 


60^ 



For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa. 

a. For this support spacing, lumber sheathing shall have a minimum F^ of 675 
and minimum E of 1,100,000 (see AF&PA/NDS). 

b. For this support spacing, lumber sheathing shall have a minimum F^ of 765 
and minimum E of 1,400,000 (see AF&PA/NDS). 

c. For this support spacing, lumber sheathing shall have a minimum F^ of 855 
and minimum E of 1,700,000 (see AF&PA/NDS). 

R503.2 Wood structural panel sheathing. 

R503.2.1 Identification and grade. Wood structural panel 
sheathing used for structural purposes shall conform to DOC 
PS 1 , DOC PS 2 or, when manufactured in Canada, CS A 0437 
or CS A 0325 . All panels shall be identified by a grade mark of 
certificate of inspection issued by an approved agency. 

R503.2.1.1 Subfloor and combimed subfloor 
underlayment. Where used as subflooring or combina- 
tion subfloor underlayment, wood structural panels shall 
be of one of the grades specified in Table R503.2.1.1(l). 



106 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FLOORS 



TABLE R503.2.1. 1(1) 

ALLOWABLE SPANS AND LOADS FOR WOOD STRUCTURAL PANELS FOR ROOF 

AND SUBFLOOR SHEATHING AND COMBINATION SUBFLOOR UNDERLAYMENF'''^ 



SPAN RATING 


MINIMUM 

NOMINAL PANEL 

THICKNESS 

(inch) 


ALLOWABLE LIVE LOAD 
(psf)'-' 


MAXIMUM SPAN 
(inches) 


LOAD (pounds per square foot, 
at maximum span) 


MAXIMUM 

SPAN 
(inches) 


SPAN 
@ 16" o.c. 


SPAN 
@ 24" O.C. 


With edge 
support'' 


Without edge 
support 


Total load 


Live load 


Sheathing^ 






Roof 


Subfloor' 


12/0 


v„ 








12 


12 


40 


30 





16/0 


v„ 


30 





16 


16 


40 


30 





20/0 


v.. 


50 





20 


20 


40 


30 





24/0 


% 


100 


30 


24 


20S 


40 


30 





24/16 


'U 


100 


40 


24 


24 


50 


40 


16 


32/16 


15/ 1/ 
'32. '2 


180 


70 


32 


28 


40 


30 


16" 


40/20 


'32, 'S 


305 


130 


40 


32 


40 


30 


20"'' 


48/24 


^32, ^48 




175 


48 


36 


45 


35 


24 


60/32 


% 





305 


60 


48 


45 


35 


32 


Underlayment, C-C plugged, 
single floor^ 






Roof 


Combination 

subfloor 
underlayment** 


16o.c. 


'32, '8 


100 


40 


24 


24 


50 


40 


16' 


20 o.c. 


^32, ^8 


150 


60 


32 


32 


40 


30 


20'J 


24 o.c. 


'%..'U 


240 


100 


48 


36 


35 


25 


24 


32 o.c. 


■ y. 





185 


48 


40 


50 


40 


32 


48 o.c. 


iV.x 1% 


— 


290 


60 


48 


50 


40 


48 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. 

a. The allowable total loads were determined using a dead load of 10 psf. If the dead load exceeds 10 psf, then the live load shall be reduced accordingly. 

b. Panels continuous over two or more spans with long dimension perpendicular to supports. Spans shall be limited to values shown because of possible effect of con- 
centrated loads. 

c. Applies to panels 24 inches or wider. 

d. Lumber blocking, panel edge clips (one midway between each support, except two equally spaced between supports when span is 48 inches), tongue-and-groove 
panel edges, or other approved type of edge support. 

e. Includes Structural 1 panels in these grades. 

f. Uniform load deflection limitation: Vjgg of span under live load plus dead load, V240 of span under live load only. 

g. Maximum span 24 inches for '^/32-and V2-inch panels. 

h. Maximum span 24 inches where ^/4-inch wood finish flooring is installed at right angles to joists. 

i. Maximum span 24 inches where 1 .5 inches of lightweight concrete or approved cellular concrete is placed over the subfloor. 

j. Unsupported edges shall have tongue-and-groove joints or shall be supported with blocking unless minimum nominal V4-inch thick underlayment with end and 
edge joints offset at least 2 inches or 1 .5 inches of lightweight concrete or approved cellular concrete is placed over the subfloor, or ^/4-inch wood finish flooring is 
installed at right angles to the supports. Allowable uniform live load at maximum span, based on deflection of V360 of span, is 100 psf. 

k. Unsupported edges shall have tongue-and-groove joints or shall be supported by blocking unless nominal V4- inch-thick underlayment with end and edge joints 
offset at least 2 inches or ^/4-inch wood finish flooring is installed at right angles to the supports. Allowable uniform live load at maximum span, based on deflection 
of V360 of span, is 100 psf, except panels with a span rating of 48 on center are limited to 65 psf total uniform load at maximum span. 

1. Allowable live load values at spans of 1 6" o.c. and 24" o.c taken from reference standard APA E30, APA Engineered Wood Construction Guide. Refer to reference 
standard for allowable spans not listed in the table. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



107 



FLOORS 



When sanded plywood is used as combination subfloor 
underlayment, the grade shall be as specified in Table 
R503.2.1.1(2). 

TABLE R503.2.1. 1(2) 
ALLOWABLE SPANS FOR SANDED PLYWOOD 
COMBINATION SUBFLOOR UNDERLAYMENT^ 



IDENTIFICATION 


SPACING OF JOISTS (inches) 


16 


20 


24 


Species group'' 








— 


1 


% 


% 


% 


2,3 


% 


% 


% 


4 


'U 


% 


1 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. 

a. Plywood continuous over two or more spans and face grain perpendicular to 
supports. Unsupported edges shall be tongue-and-groove or blocked except 
where nominal V4-inch- thick underlayment or ■'/4-inch wood finish floor is 
used. Allowable uniform live load at maximum span based on deflection of 
V360 of span is 100 psf. 

b. Applicable to all grades of sanded exterior-type plywood. 



R503.2.2 Allowable spans. The maximum allowable span 
for wood structural panels used as subfloor or combination 
subfloor underlayment shall be as set forth in Table 
R503.2. 1.1(1), or APA E30. The maximum span for sanded 
plywood combination subfloor underlayment shall be as set 
forth in Table R503.2. 1.1(2). 

R503.2.3 Installation. Wood structural panels used as 
subfloor or combination subfloor underlayment shall be 
attached to wood framing in accordance with Table 
R602.3(l) and shall be attached to cold-formed steel fram- 
ing in accordance with Table R505.3.1(2). 

R503.3 Particleboard. 

R503.3.1 Identification and grade. Particleboard shall con- 
form to ANSI A208.1 and shall be so identified by a grade 
mark or certificate of inspection issued by an approved 
agency. 

R503.3.2 Floor underlayment. Particleboard floor 
underlayment shall conform to Type PBU and shall not be 
less than V4 inch (6.4 mm) in thickness. 

R503.3.3 Installation. Particleboard underlayment shall be 
installed in accordance with the reconmiendations of the 
manufacturer and attached to framing in accordance with 
Table R602.3(l). 



SECTION R504 

PRESSURE PRESERVATIVELY TREATED-WOOD 

FLOORS (ON GROUND) 

R504.1 General. Pressure preservatively treated-wood base- 
ment floors and floors on ground shall be designed to withstand 
axial forces and bending moments resulting from lateral soil 
pressures at the base of the exterior walls and floor live and 
dead loads. Floor framing shall be designed to meet joist 
deflection requirements in accordance with Section R301. 

R504.1.1 Unbalanced soil loads. Unless special provision 
is made to resist sliding caused by unbalanced lateral soil 



loads, wood basement floors shall be limited to applications 
where the differential depth of fill on opposite exterior foun- 
dation walls is 2 feet (610 mm) or less. 

R504.1.2 Construction. Joists in wood basement floors 
shall bear tightly against the narrow face of studs in the 
foundation wall or directly against a band joist that bears on 
the studs. Plywood subfloor shall be continuous over lapped 
joists or over butt joints between in-line joists. Sufficient 
blocking shall be provided between joists to transfer lateral 
forces at the base of the end walls into the floor system. 

R504.1.3 Uplift and buckling. Where required, resistance 
to uplift or restraint against buckling shall be provided by 
interior bearing walls or properly designed stub walls 
anchored in the supporting soil below. 

R504.2 Site preparation. The area within the foundation 
walls shall have all vegetation, topsoil and foreign material 
removed, and any fill material that is added shall be free of veg- 
etation and foreign material. The fill shall be compacted to 
assure uniform support of the pressure preservatively treated- 
wood floor sleepers. 

R504.2.1 Base. A minimum 4-inch-thick (102 mm) granu- 
lar base of gravel having a maximum size of % inch (19.1 
mm) or crushed stone having a maximum size of V2 inch 
(12.7 mm) shall be placed over the compacted earth. 

R504.2.2 Moisture barrier. Polyethylene sheeting of minimum 
6-mil (0. 15 mm) thickness shall be placed over the granular base. 
Joints shall be lapped 6 inches (152 mm) and left unsealed. The 
polyethylene membrane shall be placed over the pressure 
preservatively treated-wood sleepers and shall not extend beneath 
the footing plates of the exterior walls. 

R504.3 Materials. All framing materials, including sleepers, 
joists, blocking and plywood subflooring, shall be pressure- 
preservative treated and dried after treatment in accordance 
with AWPA Ul (Commodity Specification A, Use Category 
4B and section 5.2), and shall bear the label of an accredited 
agency. 



SECTION R505 
STEEL FLOOR FRAMING 

R505.1 Cold-formed steel floor framing. Elements shall be 
straight and free of any defects that would significantly affect 
structural performance. Cold-formed steel floor framing mem- 
bers shall comply with the requirements of this section. 

R505.1.1 Applicability limits. The provisions of this sec- 
tion shall control the construction of steel floor framing for 
buildings not greater than 60 feet (18,288 mm) in length 
perpendicular to the joist span, not greater than 40 feet (12 
192 mm) in width parallel to the joist span, and not greater 
than two stories in height. Steel floor framing constructed in 
accordance with the provisions of this section shall be hm- 
ited to sites subjected to a maximum design wind speed of 
110 miles per hour (49 m/s). Exposure A, B, or C, and a 
maximum ground snow load of 70 psf (3.35 kPa). 

R505.1.2 In-line framing. When supported by steel- 
framed walls in accordance with Section R603, steel floor 
framing shall be constructed with floor joists located 



108 



2006 INTERNATIONAL RESIDEENTIAL CODE^ 



FLOORS 



directly in-line with load-bearing studs located below the 
joists with a maximum tolerance of V4 inch (19.1 mm) 
between the center lines of the joist and the stud. 

R505.1.3 Floor trusses. The design, quality assurance, 
installation and testing of cold-formed steel trusses shall be 
in accordance with the AISI Standard for Cold-formed Steel 
Framing-Truss Design (COFS/Truss). Truss members shall 
not be notched, cut or altered in any manner without an 
approved design. 

R505.2 Structural framing. Load-bearing floor framing 
members shall comply with Figure R505.2(l) and with the 
dimensional and minimum thickness requirements specified in 
Tables R505.2(l) and R505.2(2). Tracks shall comply with 
Figure R505.2(2) and shall have a minimum flange width of 
174 inches (32 mm). The maximum inside bend radius for 
members shall be the larger of ^/jj inch (2.4 mm) or twice the 
uncoated steel thickness. Holes in joist webs shall comply with 
all of the following conditions: 

1. Holes shall conform to Figure R505.2(3); 

2. Holes shall be permitted only along the centerline of the 
web of the framing member; 

3. Holes shall have a center-to-center spacing of not less 
than 24 inches (610 mm); 

4. Holes shall have a web hole width not greater than 0.5 
times the member depth, or 2V2 inches (64.5 mm); 

5. Holes shall have a web hole length not exceeding 4V2 
inches (1 14 mm); and 

6. Holes shall have a minimum distance between the edge 
of the bearing surface and the edge of the web hole of not 
less than 10 inches (254 mm). 



Framing members with web holes not conforming to the 
above requirements shall be patched in accordance with Sec- 
tion R505.3.6 or designed in accordance with accepted engi- 
neering practices. 

R505.2.1 Material. Load-bearing members used in steel 
floor construction shall be cold-formed to shape from struc- 
tural quality sheet steel complying with the requirements of 
one of the following: 

1. ASTM A 653: Grades 33, 37, 40 and 50 (Class 1 and 
3). 

2. ASTM A 792: Grades 33, 37, 40 and 50A. 

3. ASTM A 875: Grades 33, 37, 40 and 50 (Class 1 and 
3). 

4. ASTM A 1003: Grades 33, 37, 40 and 50. 

R505.2.2 Identification. Load-bearing steel framing mem- 
bers shall have a legible label, stencil, stamp or embossment 
with the following information as a minimum: 

1. Manufacturer's identification. 

2. Minimum uncoated steel thickness in inches (mm). 

3. Minimum coating designation. 

4. Minimum yield strength, in kips per square inch (ksi) 
(kPa). 

R505.2.3 Corrosion protection. Load-bearing steel fram- 
ing shall have a metallic coating complying with one of the 
following: 

1 . A minimum of G 60 in accordance with ASTM A 
653. 

2. A minimum of AZ 50 in accordance with ASTM A 
792. 



TABLE R505.2(1) 
COLD-FORMED STEEL JOIST SIZES 



MEMBER DESIGNATION^ 


WEB DEPTH 
(inches) 


MINIMUM FLANGE WIDTH 
(inches) 


MAXIMUM FLANGE WIDTH 
(inches) 


MINIMUM LIP SIZE 
(inches) 


550S162-t 


5.5 


1.625 


2 


0.5 


800S162-t 


8 


1.625 


2 


0.5 


1000S162-t 


10 


1.625 


2 


0.5 


1200s 162-t 


12 


1.625 


2 


0.5 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 

a. The member designation is defined by the first number representing the member depth in 0.01 inch, the letter "S" representing a stud or joist member, the second 

number representing the flange width in 0.01 inch, and the letter "t" shall be a number representing the minimum base metal thickness in mils [See Table 

R505.2(2)]. 

TABLE R505.2(2) 
MINIMUM THICKNESS OF COLD-FORMED STEEL MEMBERS 



DESIGNATION 
(mils) 


MINIMUM UNCOATED THICKNESS 
(inches) 


REFERENCE GAGE NUMBER 


33 


0.033 


20 


43 


0.043 


18 


54 


0.054 


16 


68 


0.068 


14 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



109 



FLOORS 



FLANGE 



WEB 



DEPTH OF WEB 
(OUTSIDE TO 
OUTSIDE) 




FLANGE 



WEB 




SIZE OF TRACK 
(INSIDE TO INSIDE) 



FIGURE R505.2(1) 
C-SECTION 



FIGURE R505.2(2) 
TRACK SECTION 



C.L. 



C.L. 



2V;' MAX. 



For SI: 1 inch = 25.4 mm. 



24" MIN. 



/ 



MAX* 



> 



<1 



^ 



"^ 



^ 



Sim 
MAX. 



10"MtN. 



/ 



CENTERLINE OF WEB 






BEARING CONDITION 



FIGURE R505.2(3) 
FLOOR JOIST WEB HOLES 



3. A minimum of GF 60 in accordance with ASTM A 
875. 

R505.2.4 Fastening requirements. Screws for steel-to- 
steel connections shall be installed with a minimum edge 
distance and center-to-center spacing of 0.5 inch (12.7 
mm), shall be self-drilling tapping, and shall conform to 
SAE J78. Floor sheathing shall be attached to steel joists 
with minimum No. 8 self-drilling tapping screws that con- 
form to SAE J78. Screws attaching floor-sheath- 
ing-to-steel joists shall have a minimum head diameter of 
0.292 inch (7.4 mm) with countersunk heads and shall be 
installed with a minimum edge distance of 0.375 inch (9.5 



mm). Gypsum board ceilings shall be attached to steel 
joists with minimum No. 6 screws conforming to ASTM C 
954 and shall be installed in accordance with Section 
R702. For all connections, screws shall extend through the 
steel a minimum of three exposed threads. All self -drilling 
tapping screws conforming to SAE J78 shall have a Type II 
coating in accordance with ASTMB 633. 

Where No. 8 screws are specified in a steel to steel con- 
nection the required number of screws in the connection is 
permitted to be reduced in accordance with the reduction 
factors in Table R505.2.4 when larger screws are used or 
when one of the sheets of steel being connected is thicker 



110 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FLOORS 



than 33 mils (0.84 mm). When applying the reduction factor 
the resulting number of screws shall be rounded up. 

TABLE R505.2.4 
SCREW SUBSTITUTION FACTOR 



SCREW SIZE 


THINNEST CONNECTED STEEL SHEET (mils) 


33 


43 


#8 


1.0 


0.67 


#10 


0.93 


0.62 


#12 


0.86 


0.56 



For SI: 1 mil = 0.0254 mm. 

R505.3 Floor construction. Cold-formed steel floors shall be 
constructed in accordance with this section and Figure R505 .3 . 

R505.3.1 Floor to foundation or bearing wall connections. 

Cold-formed steel floors shall be anchored to foundations, 
wood sills or load-bearing walls in accordance with Table 
R505.3.1(l) and Figure R505.3.1(l), R505.3.1(2), 
R505.3.1(3), R505.3.1(4), R505.3.1(5) orR505.3.1(6). Con- 
tinuous steel joists supported by interior load-bearing walls 
shall be constructed in accordance with Figure R505.3.1(7). 
Lapped steel joists shall be constructed in accordance with 
Figure R505. 3. 1(8). Fastening of steel joists to other framing 
members shall be in accordance with Table R505.3.1(2). 



R505.3.2 Allowable joist spans. The clear span of 
cold-formed steel floor joists shall not exceed the limits set 
forth in Tables R505.3.2(l), R505.3.2(2), and R505.3.2(3). 
Hoor joists shall have a minimum bearing length of 1 .5 inches 
(38 mm). When continuous joists are used, the interior bearing 
supports shall be located within 2 feet (610 nrni) of mid span of 
the steel joists, and the individual spans shall not exceed the 
span in Tables R505.3.2(2) and R505.3.2(3). Bearing stiffen- 
ers shall be installed at each bearing location in accordance 
with Section R505.3.4 and as shown in Figure R505.3. 

Blocking is not required for continuous back-to-back floor 
joists at bearing supports. Blocking shall be installed between 
the joists for single continuous floor joists across bearing sup- 
ports. Blocking shall be spaced at a maximum of 12 feet (3660 
mm) on center. Blocking shall consist of C-shape or track sec- 
tion with a minimum thickness of 33 mils (0.84 mm). Blocking 
shall be fastened to each adjacent joist through a 33-mil (0.84 
mm) clip angle, bent web of blocking or flanges of web stiffen- 
ers with two No. 8 screws on each side. The minimum depth of 
the blocking shall be equal to the depth of the joist minus 2 
inches (51 mm). The minimum length of the angle shall be 
equal to the depth of the joist minus 2 inches (51 mm). 



SUBFLOOR SHEATHING 



8 FT MAX. HEADER SPAN 



MAX. 24 IN. 
CANTILEVER 



40 FT MAX. 
BUILDING WIDTH 



BLOCKING 
12 FT 




BEARING 
STIFFENER 



JOIST SPAN 



HEADER TRIMMER 



USE FLAT STRAP WITH BLOCKING 
OR GYPSUM BOARD TO BRACE 
BOTTOM FLANGE 



GIRDER BEAM OR LOAD-BEARING WALL 



STRAPPING 12 FT 
MAX. (TYP) 



TRACK 



FOUNDATION WALL 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



FIGURE R505.3 
STEEL FLOOR CONSTRUCTION 

(continued) 



2006 INTERNATIONAL RESIDENTIAL CODE' 



o 



111 



FLOORS 



BUILT-UP HEADER AND TRIMMER JOISTS SHALL 
CONSIST OF A C-SECTION INSIDE A TRACK 
SECTION, SCREWED TOGETHER 24 IN. O.C. 
MAXIMUM THROUGH THE TOP AND BOTTOM 
FLANGES 



CLIP ANGLE (BOTH SIDES OF CONNECTION) 
MIN. LENGTH = JOIST WEB DEPTH 




FLOOR JOIST INSIDE TRACK 



8 SCREWS (4 PER LEG OF CLIP ANGLE) 



BUILT-UP HEADER OR TRIMMER JOIST 



JOIST 



CLIP ANGLE (BOTH SIDES OF CONNECTION) 
MINIMUM LENGTH = JOIST WEB DEPTH 
MINUS 1/2 IN. 




BUILT-UP HEADER AND TRIMMER JOISTS 
SHALL CONSIST OF A C-SECTION INSIDE A 
TRACK SECTION, SCREWED TOGETHER 24 IN. 
O.C. MAXIMUM THROUGH THE TOP AND 
BOTTOM FLANGES 



BUILT-UP HEADER JOIST 



8 SCREWS (4 PER LEG OF CLIP ANGLE) 



JOIST TO HEADER JOIST 



1 SCREW THROUGH BRACE 
AT EACH FLANGE 




2 SCREWS THROUGH EACH LEG OF 
33 MIL 2 IN. X 2 IN. x BLOCKING 
DEPTH, CLIP ANGLE 



33 MIL TRACK OR C-SECTION 
MINIMUM HEIGHT OF JOIST 
DEPTH MINUS 2 IN. 



OR 




X-BRACING 



For SI: linch = 25.4 mm, 1 mil = 0.0254 mm. 



SOLID BLOCKING 



BLOCKING OPTIONS 



FIGURE R505.3— continued 
STEEL FLOOR CONSTRUCTION 



112 



2006 INTERNATIONAL RESIDENTIAL CODE® 



FLOORS 



TABLE R505.3.1(1) 
FLOOR TO FOUNDATION OR BEARING WALL CONNECTION REQUIREMENTS^' ^ 



FRAMING CONDITION 


WIND SPEED (mph) AND EXPOSURE 


Up to 110 A/B or 85 C or Seismic 
Design Categories A, B, C 


Up to 110 c 


Floor joist to wall track of exterior steel 
load-bearing wall per Figure R505.3.1(l) 


2-No. 8 screws 


3-No. 8 screws 


Floor joist track to wood sill per Figure 
R505.3.U2) 


Steel plate spaced at 3' o.c, with 4-No, 8 
screws and 4-lOd or 6-8d common nails 


Steel plate, spaced at 2' o.c, with 4-No. 8 
screws and 4-lOd or 6-8d common nails 


Floor joist track to foundation per Figure 
R505.3.1(3) 


V2" minimum diameter anchor bolt and clip 
angle spaced at 6' o.c. with 8-No. 8 screws 


V2" minimum diameter anchor bolt and clip 
angle spaced at 4' o.c. with 8-No. 8 screws 


Joist cantilever to wall track per Figure 
R505.3.1('4) 


2-No. 8 screws per stiffener or bent plate 


3-No. 8 screws per stiffener or bent plate 


Joist cantilever to wood sill per Figure 
R505.3.K5) 


Steel plate spaced at 3' o.c, with 4-No. 8 
screws and 4-lOd or 6-8d common nails 


Steel plate spaced at 2' o.c, with 4-No. 8 
screws and 4-lOd or 6-8d common nails 


Joist cantilever to foundation per Figure 
R505.3.1(6) 


V2" minimum diameter anchor bolt and cUp 
angle spaced at 6' o.c. with 8-No. 8 screws 


V2" minimum diameter anchor bolt and clip 
angle spaced at 4' o.c. with 8-No. 8 screws 



For SI: I inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. 

a. Anchor bolts shall be located not more than 1 2 inches from comers or the termination of bottom tracks (e.g., at door openings). Bolts shall extend a minimum of 15 
inches into masonry or 7 inches into concrete. 

b. All screw sizes shown are minimum. 

TABLER505.3.1(2) 
FLOOR FASTENING SCHEDULE^ 



DESCRIPTION OF BUILDING ELEMENTS 


NUMBER AND SIZE OF FASTENERS 


SPACING OF FASTENERS 


Floor joist to track of an interior load-bearing wall 
per Figures R505.3.1(7) and R505.3.1(8) 


2 No. 8 screws 


Each joist 


Floor joist to track at end of joist 


2 No. 8 screws 


One per flange or two per bearing stiffener 


Subfloor to floor joists 


No. 8 screws 


6" o.c. on edges and 12" o.c. at intermediate 
supports 



For SI: 1 inch = 25.4 mm. 

a. All screw sizes shown are minimum. 



R505.3.3 Joist bracing. The top flanges of steel joists shall 
be laterally braced by the application of floor sheathing fas- 
tened to the joists in accordance with Table R505.3.1(2). 
Floor joists with spans that exceed 12 feet (3658 mm) shall 
have the bottom flanges laterally braced in accordance with 
one of the following: 

1 . Gypsum board installed with minimum No. 6 screws 
in accordance with Section R702. 

2. Continuous steel strapping installed in accordance with 
Figure R505.3. Steel straps shall be at least 1.5 inches 
(38 mm) in width and 33 mils (0.84 mm) in thickness. 
Straps shall be fastened to the bottom flange at each joist 
with at least one No. 8 screw and shall be fastened to 
blocking with at least two No. 8 screws. Blocking or 
bridging (X-bracing) shall be installed between joists 
in-hne with straps at a maximum spacing of 12 feet 
(3658 mm) measured perpendicular to the joist run and 
at the termination of all straps. 

R505.3.4 Bearing stiffeners. Bearing stiffeners shall be 
installed at all bearing locations for steel floor joists. A bear- 
ing stiffener shall be fabricated from a minimum 33 mil (0.84 
mm) C-section or 43 mil (1 .09 mm) track section. Each stiff- 
ener shall be fastened to the web of the joist with a minimum 
of four No. 8 screws equally spaced as shown in Figure 
R505.3.4. Stiffeners shall extend across the full depth of the 
web and shall be installed on either side of the web. 



R5053.5 Cutting and notching. Ranges and lips of load-bear- 
ing steel floor framing members shall not be cut or notched. 

R505.3.6 Hole patcliing. Web holes not conforming to the 
requirements in Section R505.2 shall be designed in accor- 
dance with one of the following: 

1. Framing members shall be replaced or designed in 
accordance with accepted engineering practices when 
web holes exceed the following size limits: 

1.1. The depth of the hole, measured across the 
web, exceeds 70 percent of the flat width of 
the web; or 

1.2. The length of the hole measured along the 
web, exceeds 10 inches (254 mm) or the depth 
of the web, whichever is greater. 

2. Web holes not exceeding the dimensional require- 
ments in Section R505.3.6, Item 1, shall be patched 
with a solid steel plate, stud section, or track section in 
accordance with Figure R505.3.6. The steel patch 
shall, as a minimum, be of the same thickness as the 
receiving member and shall extend at least 1 inch (25 
mm) beyond all edges of the hole. The steel patch shall 
be fastened to the web of the receiving member with 
N0.8 screws spaced no greater than 1 inch (25 mm) 
center- to-center along the edges of the patch with mini- 
mum edge distance of V2 inch (13 mm). 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



113 



FLOORS 



TRACK 



BEARING STIFFENER 



SCREWS THROUGH JOIST 
FLANGE, CLIP ANGLE OR 
BENT STIFFENER 



SCREW FLOOR TRACK 
TO WALL TRACK WITH 
SCREWS AT 24 IN. O.C. 



TRACK 




JOIST 



LOAD-BEARING STUD 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 



FIGURE R505.3.1(1) 
FLOOR TO LOAD-BEARING WALL STUD CONNECTION 



4 SCREWS 



FOUNDATION 




TRACK 



4 - 1 0d COMMON OR 
6 -8d COMMON 

3 IN. X 4 IN. X 33 MIL PLATE 
(MIN.) 



WOOD SILL AND ANCHOR BOLT 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 



FIGURE R505.3.1(2) 
FLOOR TO WOOD SILL CONNECTION 



114 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FLOORS 



BEARING STIFFENER 
TRACK 



8 SCREWS 




JOIST 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 



FIGURE R505.3.1(3) 
FLOOR TO FOUNDATION CONNECTION 



SCREW AT EACH 
FLANGE 



TRACK 




SCREWS THROUGH JOIST 
FLANGE, CLIP ANGLE OR 
BENT STIFFENER 



TRACK 



JOIST 



LOAD-BEARING STUD 



FIGURE R505.3.1(4) 
FLOOR CANTILEVER TO LOAD-BEARING WALL CONNECTION 



2006 INTERNATIONAL RESIDENTIAL CODE® 



115 



FLOORS 



BLOCKING CONNECTED TO JOIST 
WITH SCREWS THROUGH WEB 
STIFFENER OR CLIP ANGLE 



BLOCKING EVERY OTHER JOIST 
(MIN. THICKNESS OF TRACK) 




WOOD SILL AND 
ANCHOR BOLT 



SCREW AT 
EACH FLANGE 



TRACK 



'FOUNDATION 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254. 



FIGURE R505.3.1(5) 
FLOOR CANTILEVER TO WOOD SILL CONNECTION 



TRACK 



BLOCKING EVERY OTHER JOIST 
(MIN. THICKNESS AS TRACK) 



SCREW AT EVERY 
FU\NGE 



SHEATHING 



BEARING STIFFENER 




JOIST 



6IN. x6IN. x6IN. X54MIL 
CLIP ANGLE AND 
ANCHOR BOLT 



FOUNDATION 



For Sr. 1 inch = 25.4 mm, 1 mil = 0.0254. 



CONNECTION OF BLOCKING TO 
JOIST THROUGH WEB STIFFENER 
OR CLIP ANGLE WITH 4 SCREWS 
THROUGH EACH LEG 



FIGURE R505.3.1 (6) 
FLOOR CANTILEVER TO FOUNDATION CONNECTION 



116 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FLOORS 



BEARING STIFFENER 



2 SCREWS THROUGH JOIST 
FLANGE, CLIP ANGLE OR 
BENT STIFFENER 




JOIST 



TRACK 



LOAD-BEARING STUD 



FIGURE R505.3.1(7) 
CONTINUOUS JOIST SPAN SUPPORTED ON STUD 



TRACK 




ONE BEARING STIFFENER 
(4 SCREWS THROUGH 
STIFFENER AND BOTH 
JOISTS) 

TWO SCREWS 



LOAD-BEARING' 
STUD 



FIGURE R505.3.1(8) 
LAPPED JOISTS SUPPORTED ON STUD 



2006 INTERNATIONAL RESIDENTIAL CODE® 



117 



FLOORS 



TABLE R505.3.2(1) 
ALLOWABLE SPANS FOR COLD-FORMED STEEL JOISTS— SINGLE SPANS^ " 33 ksi STEEL 



JOIST 
DESIGNATION 


30 PSF LIVE LOAD 


40 PSF LIVE LOAD 


Spacing (inches) 


Spacing (inches) 


12 


16 


19.2 


24 


12 


16 


19.2 


24 


550S 162-33 


11 '-7" 


10'-7" 


9'-6" 


8'-6" 


10'-7" 


9'-3" 


8'-6" 


7'-6" 


550S 162-43 


12'-8" 


ll'-6" 


lO'-lO" 


10'-2" 


11 '-6" 


10'-5" 


9'-10" 


9'-l" 


550S 162-54 


13'-7" 


12'-4" 


11 '-7" 


10'-9" 


12'-4" 


ll'-2" 


10'-6" 


9'-9" 


550S 162-68 


14'-7" 


13'-3" 


12'-6" 


11 '-7" 


13'-3" 


12'-0" 


11 '-4" 


10'-6" 


800S 162-97 


16'-2" 


14'-9" 


13'-10" 


12'-10" 


14'-9" 


13'-4" 


12'-7" 


ll'-8" 


800S 162-33 


15'-8" 


13'- 11" 


12'-9" 


11 '-5" 


14'-3" 


12'-5" 


11 '-3" 


9'-0" 


800S 162-43 


17'-1" 


15'-6" 


14'-7" 


13'-7" 


15'-6" 


14'- 1" 


13'-3" 


12'-4" 


800S 162-54 


18'-4" 


16'-8" 


15 '-8" 


14'-7" 


16'-8" 


15'-2" 


14'-3" 


13'-3" 


800S 162-68 


19'-9" 


17'- 11" 


16'-10" 


15'-8" 


17'- 11" 


16'-3" 


15'-4" 


14'-2" 


800S 162-97 


22'-0" 


20'-0" 


16'-10" 


17'-5" 


20'-0" 


18'-2" 


17'-1" 


15'- 10" 


lOOOS 162-43 


20'-6" 


18'-8" 


17'-6" 


15'-8" 


18'-8" 


16'- 11" 


15'-6" 


13'- 11" 


lOOOS 162-54 


22'-l" 


20'-0" 


18'- 10" 


17'-6" 


20'-0" 


18'-2" 


17'-2" 


15'- 11" 


lOOOS 162-68 


23'- 9" 


21 '-7" 


20'-3" 


18'- 10" 


21'-7" 


19'-7" 


18'-5" 


17'-1" 


lOOOS 162-97 


26'-6" 


24'- 1" 


22'-8" 


21'-0" 


24'- 1" 


21'-10" 


20'-7" 


19'- 1" 


1200S 162-43 


23'-9" 


20'- 10" 


19'-0" 


16'-8" 


21'-5" 


18'-6" 


16'-6" 


13'-2" 


1200S 162-54 


25'-9" 


23'-4" 


22'-0" 


20'- 1" 


23'-4" 


21'-3" 


20'-0" 


17'- 10" 


1200S 162-68 


27'-8" 


25'- 1" 


23'-8" 


21'- 11" 


25'- 1" 


22'- 10" 


21'-6" 


21'-1" 


1200S 162-97 


30'- 11" 


28'- 1" 


26'-5" 


24'-6" 


28'- 1" 


25'-6" 


24'-0" 


22'-3" 



For SI: 1 inch = 25.4 mm, 1 foot = 

a. Deflection criteria: L/480 for live 

b. Floor dead load = 10 psf. 



304.8 mm, 1 pound per square foot : 
loads, L/240 for total loads. 



: 0.0479 kPa. 



BEARING STIFFENER 




FIGURE R505.3.4 
BEARING STIFFENER 



118 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FLOORS 



TABLE R505.3.2{2) 
ALLOWABLE SPANS FOR COLD-FORMED STEEL JOISTS- 



-MULTIPLE SPANS^" 33 ksi STEEL 



JOIST 
DESIGNATION 


30 PSF LIVE LOAD 


40 PSF LIVE LOAD 


Spacing (inches) 


Spacing (inches) 


12 


16 


19.2 


24 


12 


16 


19.2 


24 


550S 162-33 


12'-1" 


10'-5" 


9'-6" 


8'-6" 


10'-9" 


9'-3" 


8'-6" 


7'-6" 


550S 162-43 


14'-5" 


12'-5" 


ll'-4" 


10'-2" 


12'-9" 


11'- 11" 


10'- 1" 


9'-0" 


550S 162-54 


16'-3" 


14'- 1" 


12'- 10" 


ll'-6" 


14'-5" 


12'-6" 


11 '-5" 


10'-2" 


550S 162-68 


19'-7" 


17'-9" 


16'-9" 


15'-6" 


17'-9" 


16'-2" 


15'-2" 


14'-1" 


800S 162-97 


21 '-9" 


19'-9" 


lB'-7" 


17'-3" 


19'-9" 


17'-11" 


16'-10" 


15'-4" 


BOOS 162-33 


14'-8" 


ll'-lO" 


10'-4" 


8'-B" 


12'-4" 


9'- 11" 


B'-7" 


7'-2" 


BOOS 162-43 


20'-0" 


17'-4" 


15'-9" 


14'-1" 


17'-9" 


15'-4" 


14'-0" 


12'-0" . 


BOOS 162-54 


23'-7" 


20'-5" 


18'-8" 


16'-8" 


21'.0" 


lB'-2" 


16'-7" 


14'- 10" 


B00S162-6B 


26'-5" 


23'- 1" 


21'-0" 


18'- 10" 


23'-8" 


20'-6" 


IB'-B" 


16'-9" 


BOOS 162-97 


29'-6" 


26'- 10" 


25'-3" 


22'-B" 


26'- 10" 


24'-4" 


22'-6" 


20'-2" 


1000S162-43 


22'-2" 


lB'-3" 


16'-0" 


13'-7" 


18'- 11" 


15'-5" 


13'-6" 


ll'-5" 


lOOOS 162-54 


26'-2" 


22'-8" 


20'-8" 


18'-6" 


23'-3" 


20'-2" 


18'-5" 


16'-5" 


lOOOS 162-68 


31'- 5" 


27'-2" 


24'- 10" 


22'-2" 


27'- 11" 


24'-2" 


22'- 1" 


19'-9" 


lOOOS 162-97 


35'-6" 


32'-3" 


29'- 11" 


26'-9" 


32'-3" 


29'-2" 


26'-7" 


23'-9" 


1200S 162-43 


21'-B" 


17'-6" 


15'-3" 


12'- 10" 


18'-3" 


14'-B" 


12'-B" 


10'-62 


1200S 162-54 


28'-5" 


24'-8" 


22'-6" 


19'-6" 


25'-3" 


21'-11" 


19'-4" 


16'-6" 


1200S 162-68 


33'-7" 


29'- 1" 


26'-6" 


23'-9" 


29'- 10" 


25'- 10" 


23'-7" 


21'-1" 


1200S 162-97 


41'-5" 


37'-8" 


34'-6" 


30'- 10" 


37'-B" 


33'-6" 


30'-7" 


27'-5" 



For SI: 1 inch = 25.4 mm, 1 foot = 

a. Deflection criteria: L/480 for live 

b. Floor dead load = 10 psf. 



304.8 mm, 1 pound per square foot = 0.0479kPa. 
loads, L/240 for total loads. 



■ SOLID STEEL PLATE, C-SECTION 
OR TRACK (MINIMUM THICKNESS 
OF JOIST) 




SCREWS 1 IN. O.C 
(TYP.) 



For SI: 1 inch = 25.4 mm. 



FIGURE R505.3.6 
HOLE PATCH 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



119 



FLOORS 



TABLE R505.3.2(3) 
ALLOWABLE SPANS FOR COLD-FORMED STEEL JOISTS— MULTIPLE SPANS" " 50 ksi STEEL 



JOIST 
DESIGNATION 


30 PSF LIVE LOAD 


40 PSF LIVE LOAD 


Spacing (inches) 


Spacing (inches) 


12 


16 


19.2 


24 


12 


16 


19.2 


24 


550S 162-33 


13'-11" 


12'-0" 


ll'-O" 


9'-3" 


12'-3" 


10'-8" 


9'-7" 


8'-4" 


550S 162-43 


16'-3" 


14'- 1" 


12'- 10" 


ll'-6" 


14'-6" 


12'-6" 


ll'-5" 


10'-3" 


550S 162-54 


18'-2" 


16'-6" 


15'-4" 


13'-8" 


16'-6" 


14'- 11" 


13'-7" 


12'-2" 


550S 162-68 


19'-6" 


17'-9" 


16'-8" 


15'-6" 


17'-9" 


16'-1" 


15'-2" 


14'-0" 


550S 162-97 


21 '-9" 


19'-9" 


18'-6" 


17'-2" 


19'-8" 


17'- 10" 


16'-8" 


15'-8" 


800S 162-33 


15'-6" 


12'-6" 


10'- 10" 


9'-l" 


13'-0" 


10'-5" 


8'- 11" 


6'-9" 


800S 162-43 


22'-0" 


19'-1" 


17'-5" 


15'-0" 


19'-7" 


16'-11" 


14'-10" 


12'-8" 


800S 162-54 


24'-6" 


22'-4" 


20'-6" 


17'- 11" 


22'-5" 


19'-9" 


17'-11" 


15'- 10" 


800S 162-68 


26'-6" 


24'- 1" 


22'-8" 


21'-0" 


24'- 1" 


21'-10" 


20'-7" 


19'-2" 


800S 162-97 


29'-9" 


26'-8" 


25'-2" 


23'-5" 


26'-8" 


24'-3" 


22'- 11" 


21'-4" 


lOOOS 162-43 


23'-6" 


19'-2" 


16'-9" 


14'-2" 


19'-11" 


16'-2" 


14'-0" 


ll'-9" 


1000S162-54 


28'-2" 


23'- 10" 


21'-7" 


18'- 11" 


24'-8" 


20'- 11" 


18'-9" 


18'-4" 


lOOOS 162-68 


31'- 10" 


28'- 11" 


27'-2" 


25'-3" 


28'- 11" 


26'-3" 


24'-9" 


22'-9" 


lOOOS 162-97 


35'-4" 


32'-l" 


30'-3" 


28'- 1" 


32'- 1" 


29'-2" 


27'-6" 


25'-6" 


1200S 162-43 


22'- 11" 


18'-5" 


16'-0" 


13'-4" 


19'-2" 


15'-4" 


13'-2" 


10'-6" 


1200S162-54 


32'-8" 


28'- 1" 


24'-9" 


21'-2" 


29'-0" 


23'-10" 


20'- 11" 


17'-9" 


1200S 162-68 


37'- 1" 


32'-5" 


29'-4" 


25'- 10" 


33'-4" 


28'-6" 


25'-9" 


22'-7" 


1200S162-97 


41'-2" 


37'-6" 


35'-3" 


32'-9" 


37'-6" 


34'- 1" 


32'- 1" 


29'-9" 



For SI: 1 inch = 25.4 mm, 1 foot = 

a. Deflection criteria: L/480 for live 

b. Floor dead load =10 psf. 



304.8 mm, 1 pound per square foot : 
loads, L/240 for total loads. 



: 0.0479kPa. 



JOIST SECTION INSIDE TRACK 




For SI: 1 inch = 25.4 mm. 



■TRACK 



FIGURE R5()5.3.8 
TRACK SPLICE 



4 SCREWS ON EACH 
SIDE OF SPLICE 



120 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FLOORS 



R505.3.7 Floor cantilevers. Floor cantilevers shall not 
exceed 24 inches (610 mm) as illustrated in Figure 
R505.3. The cantilever back-span shall extend a mini- 
mum of 6 feet (1 830 mm) within the building, and shall be 
fastened to a bearing condition in accordance with Sec- 
tion R505.3.1. Floor cantilevers shall be permitted only 
on the second floor of a two-story building or the first 
floor of a one-story building. Floor framing that is canti- 
levered and supports the cantilevered floor only shall 
consist of single joist members in accordance with Sec- 
tion R505.3.2. Floor framing that is cantilevered and sup- 
ports the cantilevered floor and the roof framing load 
above shall consist of double joist members of the same 
size and material thickness as that for single joist mem- 
bers in accordance with Section R505.3.2, and shall be 
fastened web-to-web with minimum No. 8 screws at 24 
inches (610 mm) maximum on-center spacing top and 
bottom. Built-up floor framing consisting of a C-section 
inside a track section, fastened at the top and bottom 
flanges by minimum No. 8 screws at 24 inches (610 mm) 
maximum on center spacing, is permitted in lieu of the 
web-to-web double joist method. 

R505.3.8 Splicing. Joists and other structural members 
shall not be spliced. Splicing of tracks shall conform with 
Figure R505.3.8. 

R505.3.9 Framing of openings. Openings in floor framing 
shall be framed with header and trimmer joists. Header joist 
spans shall not exceed 8 feet (2438 mm). Header and trim- 
mer joists shall be fabricated from joist and track sections, 
which shall be of a minimum size and thickness as the adja- 
cent floor joists and shall be installed in accordance with 
Figure R505.3. Each header joist shall be connected to trim- 
mer joists with a minimum of four 2-inch-by-2-inch (5 1 mm 
by 51 mm) clip angles. Each clip angle shall be fastened to 
both the header and trimmer joists with four No. 8 screws, 
evenly spaced, through each leg of the clip angle. The clip 
angles shall have a steel thickness not less than that of the 
floor joist. 



shall be placed on the prepared subgrade when the slab is 
below grade. 

Exception: A base course is not required when the 
concrete slab is installed on well-drained or 
sand-gravel mixture soils classified as Group I 
according to the United Soil Classification System in 
accordance with Table R405.1. 

R506.2.3 Vapor retarder. A 6 mil (0.006 inch; 152 fxm) 
polyethylene or approved vapor retarder with joints lapped 
not less than 6 inches (152 mm) shall be placed between the 
concrete floor slab and the base course or the prepared 
subgrade where no base course exists. 

Exception: The vapor retarder may be omitted: 

1 . From garages, utility buildings and other unheated 
accessory structures. 

2. From driveways, walks, patios and other flatwork 
not likely to be enclosed and heated at a later date. 

3. Where approved by the building official, based on 
local site conditions. 

R506.2.4 Reinforcement support. Where provided in 
slabs on ground, reinforcement shall be supported to remain 
in place from the center to upper one third of the slab for the 
duration of the concrete placement. 



SECTION R506 
CONCRETE FLOORS (ON GROUND) 

R506.1 General. Concrete slab-on-ground floors shall be a 
minimum 3.5 inches (89 mm) thick (for expansive soils, see 
Section R403.1.8). The specified compressive strength of con- 
crete shall be as set forth in Section R402.2. 

R506.2 Site preparation. The area within the foundation 
walls shall have all vegetation, top soil and foreign material 
removed. 

R506.2.1 Fill. Fill material shall be free of vegetation and 
foreign material. The fill shall be compacted to assure uni- 
form support of the slab, and except where approved, the fill 
depths shall not exceed 24 inches (610 mm) for clean sand 
or gravel and 8 inches (203 mm) for earth. 

R506.2.2 Base. A 4-inch-thick (102 mm) base course con- 
sisting of clean graded sand, gravel, crushed stone or 
crushed blast-furnace slag passing a 2-inch (5 1 mm) sieve 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



121 



122 2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 6 

WALL CONSTRUCTION 



SECTION R601 
GENERAL 

R601.1 Application. The provisions of this chapter shall con- 
trol the design and construction of all walls and partitions for 
all buildings. 

R601.2 Requirements. Wall construction shall be capable of 
accommodating all loads imposed according to Section R301 
and of transmitting the resulting loads to the supporting struc- 
tural elements. 

R601.2.1 Compressible floor-covering materials. Com- 
pressible floor-covering materials that compress more than 
'/32 inch (0.8 mm) when subjected to 50 pounds (23 kg) 
applied over 1 inch square (645 mm) of material and are 
greater than Vg inch (3 mm) in thickness in the uncom- 
pressed state shall not extend beneath walls, partitions or 
columns, which are fastened to the floor. 



SECTION R602 
WOOD WALL FRAMING 

R602.1 Identification. Load-bearing dimension lumber for 
studs, plates and headers shall be identified by a grade mark of 
a lumber grading or inspection agency that has been approved 
by an accreditation body that complies with DOC PS 20. In lieu 
of a grade mark, a certification of inspection issued by a lumber 
grading or inspection agency meeting the requirements of this 
section shall be accepted. 

R602.1.1 End-jointed lumber. Approved end-jointed lum- 
ber identified by a grade mark conforming to Section 
R602. 1 may be used interchangeably with solid-sawn mem- 
bers of the same species and grade. 

R602.1.2 Structural glued laminated timbers. Glued 
laminated timbers shall be manufactured and identified as 
required in AITC A190.1 and ASTM D 3737. 

R602.1.3 Structural log members. Stress grading of struc- 
tural log members of nonrectangular shape, as typically 
used in log buildings, shall be in accordance with ASTM D 
3957. Such structural log members shall be identified by the 
grade mark of an approved lumber grading or inspection 
agency. In lieu of a grade mark on the material, a certificate 
of inspection as to species and grade issued by a lum- 
ber-grading or inspection agency meeting the requirements 
of this section shall be permitted to be accepted. 

R602.2 Grade. Studs shall be a minimum No. 3, standard or 
stud grade lumber. 

Exception: Bearing studs not supporting floors and 
nonbearing studs may be utility grade lumber, provided the 
studs are spaced in accordance with Table R602.3(5). 

R602.3 Design and construction. Exterior walls of 
wood-frame construction shall be designed and constructed in 



accordance with the provisions of this chapter and Figures 
R602.3(l) and R602.3(2) or in accordance with AF&PA's 
NDS. Components of exterior walls shall be fastened in accor- 
dance with Tables R602.3(l) through R602.3(4). Exterior 
walls covered with foam plastic sheathing shall be braced in 
accordance with Section R602.10. Structural sheathing shall 
be fastened directly to structural framing members. 

R602.3.1 Stud size,4ieight and spacing. The size, height 
and spacing of studs shall be in accordance with Table 
R602.3.(5). 

Exceptions: 

1 . Utility grade studs shall not be spaced more than 
16 inches (406 mm) on center, shall not support 
more than a roof and ceiling, and shall not exceed 8 
feet (2438 mm) in height for exterior walls and 
load-bearing walls or 10 feet (3048 mm) for inte- 
rior nonload-bearing walls. 

2. Studs more than 10 feet (3048 mm) in height 
which are in accordance with Table R602.3.1. 

R602.3.2 Top plate. Wood stud walls shall be capped with a 
double top plate installed to provide overlapping at comers 
and intersections with bearing partitions. End joints in top 
plates shall be offset at least 24 inches (610 mm). Joints in 
plates need not occur over studs. Plates shall be not less than 
2-inches (51 mm) nominal thickness and have a width at 
least equal to the width of the studs. 

Exception: A single top plate may be installed in stud 
walls, provided the plate is adequately tied at joints, cor- 
ners and intersecting walls by a minimum 3-inch-by- 
6-inch by a 0.036-inch-thick (76 mm by 152 mm by 
0.914 mm) galvanized steel plate that is nailed to each 
wall or segment of wall by six 8d nails on each side, pro- 
vided the rafters or joists are centered over the studs with 
a tolerance of no more than 1 inch (25 mm) . The top plate 
may be omitted over lintels that are adequately tied to 
adjacent wall sections with steel plates or equivalent as 
previously described. 

R602.3.3 Bearing studs. Where joists, trusses or rafters are 
spaced more than 16 inches (406 mm) on center and the 
bearing studs below are spaced 24 inches (610 mm) on cen- 
ter, such members shall bear within 5 inches (127 mm) of 
the studs beneath. 

Exceptions: 

1 . The top plates are two 2-inch by 6-inch (38 mm by 
140 mm) or two 3-inch by 4-inch (64 mm by 89 
mm) members. 

2. A third top plate is installed. 

3 . Solid blocking equal in size to the studs is installed 
to reinforce the double top plate. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



123 



WALL CONSTRUCTION 



TABLE R602.3(1) 
FASTENER SCHEDULE FOR STRUCTURAL MEMBERS 



DESCRIPTION OF BUILDING ELEMENTS 


NUMBER AND TYPE OF 
FASTENER^''''= 


SPACING OF FASTENERS 


Joist to sill or girder, toe nail 


3-8d (2-V2"x 0.113") 


— 


1" X 6" subfloor or less to each joist, face nail 


2-8d(2V2"x 0.113") 
2 staples, P//' 


— 


2" subfloor to joist or girder, blind and face nail 


2-16d(3V2"x 0.135") 





Sole plate to joist or blocking, face nail 


16d(3V2"x 0.135") 


16" o.c. 


Top or sole plate to stud, end nail 


2-16d(3V2"x 0.135") 





Stud to sole plate, toe nail 


3-8d(2V2"x 0.113") or 
2-16d(3V2"x 0.135") 




Double studs, face nail 


10d(3"x0.128") 


24" o.c. 


Double top plates, face nail 


10d(3"x0.128") 


24" o.c. 


Sole plate to joist or blocking at braced wall panels 


3-16d(3V2"x 0.135") 


16" o.c. 


Double top plates, minimum 24-inch offset of end joints, face nail in 
lapped area 


8-16d(3'/2"x 0.135") 


— 


Blocking between joists or rafters to top plate, toe nail 


3-8d(2V2"x 0.113") 





Rim joist to top plate, toe nail 


8d(2V2"x 0.113") 


6" o.c. 


Top plates, laps at comers and intersections, face nail 


2-10d(3"x0.128") 


— 


Built-up header, two pieces with V2" spacer 


16d(3V2"x 0.135") 


16" o.c. along each edge 


Continued header, two pieces 


16d(3V2"x 0.135") 


16" o.c. along each edge 


Ceiling joists to plate, toe nail 


3-8d(2V2"x 0.113") 





Continuous header to stud, toe nail 


4-8d(2V2"x 0.113") 


, 


Ceiling joist, laps over partitions, face nail 


3-10d(3"x0.128") 





Ceiling joist to parallel rafters, face nail 


3-10d(3"x0.128") 


— 


Rafter to plate, toe nail 


2-16d(3V2"x 0.135") 


— 


1" brace to each stud and plate, face nail 


2-8d(2V2"x 0.113") 
2 staples, IV4" 


— 


1" X 6" sheathing to each bearing, face nail 


2-8d(2V2"x 0.113") 
2 staples, 1%" 


— 


1" X 8" sheathing to each bearing, face nail 


2-8d(2'/2"x 0.113") 
3 staples, 1%" 


— 


Wider than 1" x 8" sheathing to each bearing, face nail 


3-8d(2V2"x0.113") 
4 staples, P//' 


— 


Built-up corner studs 


10d(3"x0.128") 


24"o.c. 


Built-up girders and beams, 2-inch lumber layers 


10d(3"x0.128") 


Nail each layer as follows: 32" o.c. at 
top and bottom and staggered. Two 
nails at ends and at each splice. 


2" planks 


2-16d(3V2"x 0.135") 


At each bearing 


Roof rafters to ridge, valley or hip rafters: 
toe nail 
face nail 


4-16d(3V2"x 0.135") 
3-16d(3V2"x 0.135") 


— 


Rafter ties to rafters, face nail 


3-8d(2V2"x 0.113") 


— 


Collar tie to rafter, face nail, or 1 V4" x 20 gage ridge strap 


3-10d(3"x0.128") 


— 



(continued) 



124 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



WALL CONSTRUCTION 



TABLE R602.3(1)— continued 
FASTENER SCHEDULE FOR STRUCTURAL MEMBERS 



DESCRIPTION OF BUILDING 
MATERIALS 


DESCRIPTION OF FASTENER"' ='^ 


SPACING OF FASTENERS 


Edges (inches)' Intermediate supports'^'^ (inches) 


Wood structural panels, subfloor, roof and wall sheathing to framing, and partlcleboard wall sheathing to framing 


'i^rii' 


6d common (2" x 0.113") nail (subfloor, wall) 
8d common ilM^' x 0.131") nail (roof)f 


6 


128 


•V-i" 


8d common nail (2V2" x 0.131") 


6 


128 


lVs"-lV4" 


lOd common (3" x 0.148") nail or 
8d (2V2" x 0.131") deformed nail 


6 


12 


other wall sheathing"^ 


V2" structural cellulosic fiberboard 
sheathing 


1 V2" galvanized roofing nail 8d common 
(2V2" X 0.131") nail; staple 16 ga., IV2" long 


3 


6 


^^732" structural cellulosic 
fiberboard sheathing 


1^/4" galvanized roofing nail 8d common 
(2V2" X 0.131") nail; staple 16 ga., IV4" long 


3 


6 


V2" gypsum sheathing'' 


1 V2" galvanized roofing nail; 

6d common (2" x 0.131") nail; staple galvanized 

1 V2" long; 1 V4" screws. Type W or S 


4 


8 


^/g" gypsum sheathing'* 


P/4" galvanized roofing nail; 

8d common (2V2" x 0.131") nail; staple galvanized 

iVg" long; P/g" screws, Type W or S 


4 


8 


Wood structural panels, combination subfloor underlayment to framing 


V4" and less 


6d deformed (2" x 0.120") nail or 
8d common (2V2" x 0.131") nail 


6 


12 


V-1" 


8d common (2V2" x 0.131") nail or 
8d deformed (2V2" x 0.120") nail 


6 


12 


i>V'-iv/ 


lOd common (3" x 0.148") nail or 
8d deformed (2V2" x 0.120") nail 


6 


12 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s; Iksi = 6.895 MPa. 

a. All nails are smooth-common, box or deformed shanks except where otherwise stated. Nails used for framing and sheathing connections shall have minimum aver- 
age bending yield strengths as shown: 80 ksi for shank diameter of 0. 192 inch (20d common nail), 90 ksi for shank diameters larger than 0. 142 inch but not larger 
than 0.177 inch, and 100 ksi for shank diameters of 0.142 inch or less. 

b. Staples are 16 gage wire and have a minimum ^/[5-inch on diameter crown width. 

c. Nails shall be spaced at not more than 6 inches on center at all supports where spans are 48 inches or greater. 

d. Four-foot-by-8-foot or 4-foot-by-9-foot panels shall be applied -vertically. 

e. Spacing of fasteners not included in this table shall be based on Ikble R602.3(2). 

f. For regions having basic wind speed of 110 mph or greater, 8d deformed (2 V2" x 0. 120) nails shall be used for attaching plywood and wood structural panel roof 
sheathing to framing within minimum 48-inch distance from ^ble end walls, if mean roof height is more than 25 feet, up to 35 feet maximum. 

g. For regions having basic wind speed of 1 00 mph or less, nails for attaching wood structural panel roof sheathing to gable end wall framing shall be spaced 6 inches 
on center. When basic wind speed is greater than 100 mph, nails for attaching panel roof sheathing to intermediate supports shall be spaced 6 inches on center for 
minimum 48-inch distance from ridges, eaves and gable end walls; and 4 inches on center to gable end wall framing. 

h. Gypsum sheathing shall conform to ASTM C 79 and shall be installed in accordance with GA 253. Fiberboard sheathing shall conform to ASTM C 208. 

i. Spacing of fasteners on floor sheathing panel edges applies to panel edges supported by framing members and required blocking and at all floor perimeters only. 
Spacing of fasteners on roof sheathing panel edges applies to panel edges supported by framing members and required blocking. Blocking of roof or floor sheath- 
ing panel edges perpendicular to the framing members need not be provided except as required by other provisions of this code. Floor perimeter shall be supported 
by framing members or solid blocking. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



125 



WALL CONSTRUCTION 



TABLE R602.3(2) 
ALTERNATE ATTACHMENTS 



NOMINAL IVIATERIAL THICKNESS 
(inches) 


DESCRIPTION^'' OF FASTENER AND LENGTH 
(inches) 


SPACING"=OF FASTENERS 


Edges 
(inches) 


Intermediate supports 
(inches) 


Wood structural panels subfloor, roof and wall sheathing to framing and particleboard wall sheathing to framing' 


up to V2 


Staple 15 ga. IV4 


4 


8 


0.097 - 0.099 Nail 2V4 


3 


6 


Staple 16 ga. 1% 


3 


6 


'%2 and 5/3 


0.113 Nail 2 


3 


6 


Staple 15 and 16 ga. 2 


4 


8 


0.097 - 0.099 Nail 2V4 


4 


8 


23/32 and % 


Staple 14 ga. 2 


4 


8 


Staple 15 ga. IV4 


3 


6 


0.097 - 0.099 Nail 2V4 


4 


8 


Staple 16 ga. 2 


4 


8 


1 


Staple 14 ga. 2V4 


4 


8 


0.113 Nail 2 V4 


3 


6 


Staple 15 ga. 2V4 


4 


8 


0.097 - 0.099 Nail 2V2 


4 


8 


NOMINAL MATERIAL THICKNESS 
(inches) 


DESCRIPTION^'" OF FASTENER AND LENGTH 
(inches) 


SPACING'^ OF FASTENERS 


Edges 
(inches) 


Body of panel'' 
(inches) 


Floor underlayment; plywood-hardboard-particleboard' 


Plywood 


V4and5/,6 


1 V4 ring or screw shank nail — minimum 
12V, ga. (0.099") shank diameter 


3 


6 


Staple 18 ga., ^/^, V,f; crown width 


2 


5 


/32» /g' ^32' I2 

and ^9/32 


1 V4 ring or screw shank nail — minimum 
I2V2 ga. (0.099") shank diameter 


6 


8^ 


Vg, 23/32 and V4 


1 V2 ring or screw shank nail — minimum 
I2V2 ga. (0.099") shank diameter 


6 


8 


Staple 16 ga. IV2 


6 


8 


Hard board' 


0.200 


1 '/2 long ring-grooved underlayment nail 


6 


6 


4d cement-coated sinker nail 


6 


6 


Staple 18 ga., %long (plastic coated) 


3 


6 


Particleboard 


'/4 


4d ring-grooved underlayment nail 


3 


6 


Staple 18 ga., % long, Vj^ crown 


3 


6 


% 


6d ring-grooved underlayment nail 


6 


10 


Staple 16 ga., iVg long, % crown 


3 


6 


%% 


6d ring-grooved underlayment nail 


6 


10 


Staple 16 ga., iVglong, Vg crown 


3 


6 



For SI: 1 inch = 25.4 mm. 

a. Nail is a general description and may be T-head, modified round head or round head. 

b. Staples shall have a minimum crown width of ^/jg-inch on diameter except as noted. 

c. Nails or staples shall be spaced at not more than 6 inches on center at all supports where spans are 48 inches or greater. Nails or staples shall be spaced at not more 
than 12 inches on center at intermediate supports for floors. 

d. Fasteners shall be placed in a grid pattern throughout the body of the panel. 

e. For 5-ply panels, intermediate nails shall be spaced not more than 12 inches on center each way. 

f. Hardboard underlayment shall conform to ANSI/ AHA A135.4. 



126 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R602.3(3) 
WOOD STRUCTURAL PANEL WALL SHEATHING 



PANEL SPAN RATING 


PANEL NOMINAL THICKNESS 
(inch) 


MAXIMUM STUD SPACING (inches) 


Siding nailed to:^ 


Stud 


Sheathing 


12/0, 16/0, 20/0, or wall —16 o.c. 


'Ue,% 


16 


16" 


24/0, 24/16, 32/16 or wall— 24 o.c. 


/g' /l6' /32' I2 


24 


24'^ 



For SI: 1 inch = 25.4 mm. 

a. Blocking of horizontal joints shall not be required. 

b. Plywood sheathing ^/g-inch thick or less shall be applied with long dimension across studs. 

c. Three-ply plywood panels shall be applied with long dimension across studs. 



TABLE R602.3(4) 
ALLOWABLE SPANS FOR PARTICLEBOARD WALL SHEATHING^ 



THICKNESS 
(inch) 


GRADE 


STUD SPACING 
(inches) 


When siding is nailed to studs 


When siding is nailed to sheathing 


\ 


M-1 Exterior glue 


16 


— 


% 


M-2 Exterior glue 


16 


16 



For SI: 1 inch = 25.4 mm. 

a. Wall sheathing not exposed to the weather. If the panels are appUed horizontally, the end j oints of the panel shall be offset so that four panels comers will not meet. 
All panel edges must be supported. Leave a Vjg-inch gap between panels and nail no closer than^/g inch from panel edges. 



TABLE R602.3(5) 
SIZE, HEIGHT AND SPACING OF WOOD STUDS^ 



STUD SIZE 
(inches) 


BEARING WALLS 


NONBEARING WALLS 


Laterally 

unsupported stud 

height^ 

(feet) 


Maximum spacing 

when supporting 

roof and ceiling 

only 

(inches) 


Maximum spacing 

when supporting 

one floor, roof 

and ceiling 

(inches) 


Maximum spacing 

when supporting 

two floors, roof 

and ceiling 

(inches) 


Maximum spacing 

when supporting 

one floor only 

(inches) 


Laterally 

unsupported stud 

height^ 

(feet) 


Maximum spacing 
(inches) 


2x31^ 


— 


— 


— 


— 


— 


10 


16 


2x4 


10 


24 


16 


— 


24 


14 


24 


3x4 


10 


24 


24 


16 


24 


14 


24 


2x5 


10 


24 


24 


— 


24 


16 


24 


2x6 


10 


24 


24 


16 


24 


20 


24 



For SI: 1 inch = 25.4 mm. 

a. Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where 
justified by analysis. 

b. Shall not be used in exterior walls. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



127 



WALL CONSTRUCTION 




TOP PLATE 



BOTTOM PLATE 



TOP PLATE 




BAND JOIST 
OR BLOCKING 

SILL PLATE. 



y//N\\\y// 



RAFTERS AND CEILING 
JOISTS OR APPROVED 
ROOF TRUSS 



SECOND STORY 




FLOOR JOIST- 
SEE DRILLING AND 
NOTCHING PROVISIONS 
SECTION R502.8 



JOIST IS PERMITTED TO 
BE CUT OR NOTCHED 
BETWEEN THESE LIMITS 



\ |//3SPAN^| 



V3 SPAN 



o 



BAND JOIST OR 
BLOCKING 



BOTTOM PLATE 




-/ 



FOR BLOCKING AND 
BRIDGING—SEE 
SECTION R502.7 



BEARING 
WALL 



LAP JOIST 3 IN. MIN. 
OR SPLICE— SEE 
SECTION R502.6.1 



CRAWL SPACE OR 

BASEMENT 

FOUNDATION 



'/// \\\^ //// n\\\ y// v\\V/// \\V 






SUBFLOOR 



TOP PLATE - 
SEE DRILLING AND 
NOTCHING PROVISIONS 
SECTION R602.6.1 



WALL STUD- 
SEE DRILLING AND 
NOTCHING PROVISIONS 
SECTION R602.6 



JOIST NAILED TO 
STUD 



1 IN. X 4 IN. RIBBON 
CUT INTO STUD- 
SEE SECTION R502.,6 



SEE SECTION R602.8 
FOR FIRE BLOCKING 



WW/// 



PLATFORM FRAMING 



INTERMEDIATE 
BEARING WALL 



MONOLITHIC 

SLAB-ON-GRADE 

FOUNDATION 



BALLOON FRAMING 



For SI: 1 inch = 25.4 mm. 



FIGURE R602.3(1) 
TYPICAL WALL, FLOOR AND ROOF FRAMING 



128 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



SINGLE OR DOUBLE 
TOP PLATE 



CUT PLATE TIED WITH 
,16 GAGE STEEL STRAP. 
SEE SECTION R602.6.1. 



FIREBLOCK AROUND 
PIPE 



WALL STUDS- 
SEE SECTION R602.3 



SUBFLOOR 



SILL PLATE 





STAGGER JOINTS 24 IN. OR 
USE SPLICE PLATES- 
SEE SECTION R602.3.2 



HEADER- 
SEE TABLES R502.5(1) 
AND R502,5(2) 



BOTTOM 
PUTE 



SOUD BLOCKING 
FLOOR JOISTS 



FOUNDATION 
CRIPPLE WALL- 
SEE SECTION R602.9 



FOUNDATION 
WALL STUDS 



1 IN. BY 4 IN. 
DIAGONAL BRACE 
LET INTO STUDS 



ANCHOR BOLTS EMBEDDED IN 
FOUNDATION 6 FT O.C. MAX. 



CORNER AND PARTITION POSTS 



m^ 



JL 



^ 



M^ 




APPLY APPROVED SHEATHING OR BRACE 
EXTERIOR WALLS WITH 1 IN. BY 4 IN. BRACES LET 
INTO STUDS AND PLATES AND EXTENDING FROM 
BOTTOM PUTE TO TOP PLATE, OR OTHER 
APPROVED METAL STRAP DEVICES INSTALLED IN 
ACCORDANCE WITH THE MANUFACTURER'S 
SPECIFICATIONS. SEE SECTION R602.10. 



NOTE: A THIRD STUD AND/OR PARTITION INTERSECTION 
BACKING STUDS SHALL BE PERMITTED TO BE OMITTED 
THROUGH THE USE OF WOOD BACKUP CLEATS, METAL 
DRYWALL CLIPS OR OTHER APPROVED DEVICES THAT 
WILL SERVE AS ADEQUATE BACKING FOR THE FACING 
MATERIALS. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



FIGURE R602.3(2) 
FRAMING DETAILS 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



129 



WALL CONSTRUCTION 



TABLE R602.3.1 

MAXIMUM ALLOWABLE LENGTH OF WOOD WALL STUDS EXPOSED TO WIND SPEEDS OF 100 mph OR LESS 

IN SEISMIC DESIGN CATEGORIES A, B, C and Dq, D^ AND Dj" '= 



HEIGHT 
(feet) 


ON-CENTER SPACING (inches) 


24 


16 


12 


8 


Supporting a roof only 


>10 


2x4 


2x4 


2x4 


2x4 


12 


2x6 


2x4 


2x4 


2x4 


14 


2x6 


2x6 


2x6 


2x4 


16 


2x6 


2x6 


2x6 


2x4 


18 


NA^ 


2x6 


2x6 


2x6 


20 


NA^ 


NA" ■ 


2x6 


2x6 


24 


NA^ 


NA^ : 


NA^ 


2x6 


Supporting one floor and a roof 


>10 


2x6 


2x4, 


2x4 


2x4 


12 


2x6 


2x6 


2x6 


2x4 


14 


2x6 


2x6 


2x6 


2x6 


16 


NA^ 


2x6 


2x6 


2x6 


18 


NA^ 


2x6 


2x6 


2x6 


20 


NA^ 


NA"* 


2x6 


2x6 


24 


NA^ 


NA^ 


NA^ 


2 X 6 


Supporting two floors and a roof 


>10 


2x6 


2x6 


2x4 


2x4 


12 


2x6 


2x6 


2x6 


2x6 


14 


2x6 


2x6: 


2x6 


2x6 


16 


NA^ 


NA'' ■ 


2x6 


2x6 


18 


NA^ 


NA'^ ; 


2x6 


2x6 


20 


NA^ 


NA'' 


NA^ 


2x6 


22 


NA^ 


NA'^ , 


NA^ 


NA.^ 


24 


NA^ 


NA'^ , 


NA^ 


NA" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 
1 pound per square inch = 6.895 kPa, 1 mile per hour = 0.447 m/s. 

a. Design required. 

b. Applicabihty of this table assumes the following: Snow load not exceeding 25 psf ,/^ not less than 1 3 10 psi determined by multiplying the AF&PA NDS tabular 
base design value by the repetitive use factor, and by the size factor for all species except southern pine, E not less than 1 .6 x 1 0^ psi, tributary dimensions for floors 
and roofs not exceeding 6 feet, maximum span for floors and roof not exceeding 1 2 feet, eaves not over 2 feet in dimension and exterior sheathing. Where the condi- 
tions are not within these parameters, design is required. 

c. Utility, standard, stud and No. 3 grade lumber of any species are not permitted. ' 

(continued) 



130 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R602.3.1— continued 

MAXIMUM ALLOWABLE LENGTH OF WOOD WALL STUDS EXPOSED TO WIND SPEEDS OF 100 mph OR LESS 

IN SEISMIC DESIGN CATEGORIES A, B, C, Dq, D^ and D^ 




H = HEIGHT 



1 ROOF LOAD 



1 ROOF LOAD 
1 FLOOR LOAD 



1 FLOOR 




1 ROOF LOAD 

2 FLOOR LOADS 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



131 



WALL CONSTRUCTION 



R602.3.4 Bottom (sole) plate. Studs shall have full bearing 
on a nominal 2-by (38 mm) or larger plate or sill having a 
width at least equal to the width of the studs. 

R602.4 Interior load-bearing walls. Interior load-bearing 
walls shall be constructed, framed and fireblocked as specified 
for exterior walls. 

R602.5 Interior nonbearing walls. Interior nonbearing 
walls shall be permitted to be constructed with 
2-inch-by-3-inch (5 1 mm by 76 mm) studs spaced 24 inches 
(610 mm) on center or, when not part of a braced wall line, 
2-inch-by-4-inch (5 1 mm by 1 02 mm) flat studs spaced at 1 6 
inches (406 mm) on center. Interior nonbearing walls shall 
be capped with at least a single top plate. Interior nonbearing 
walls shall be fireblocked in accordance with Section 
R602.8. 

IR602.6 Drilling and notching-studs. Drilling and notching 
of studs shall be in accordance with the following: 



1. Notching. Any stud in an exterior wall or bearing parti- 
tion may be cut or notched to a depth not exceeding 25 
percent of its width. Studs in nonbearing partitions may 
be notched to a depth not to exceed 40 percent of a single 
stud width. 

2. Drilling. Any stud may be bored or drilled, provided that 
the diameter of the resulting hole is no more than 60 per- 
cent of the stud width, the edge of the hole is no more 
than Vg inch (16 mm) to the edge of the stud, and the hole 
is not located in the same section as a cut or notch. Studs 
located in exterior walls or bearing partitions drilled over 
40 percent and up to 60 percent shall also be doubled 
with no more than two successive doubled studs bored. 
See Figures R602.6(l) and R602.6(2). 

Exception: Use of approved stud shoes is permitted 
when they are installed in accordance with the manu- 
facturer's recommendations. 



TOP PLATES 



BORED HOLE MAX. 
DIAMETER 40 PERCENtX 
OF STUD DEPTH A 



5/8 IN. MIN. TOEDGE 



NOTCH MUST NOT EXCEED 25 
PERCENT OF STUD DEPTH 



BORED HOLES SHALL NOT BE 
LOCATED IN THE SAME CROSS 
SECTION OF CUT OR NOTCH IN 
STUD 




STUD 



% IN. MIN. TO EDGE 



IF HOLE IS BETWEEN 40 PERCENT AND 
60 PERCENT OF STUD DEPTH, THEN STUD 
MUST BE DOUBLE AND NO MORE THAN TWO 
SUCCESSIVE STUDS ARE DOUBLED AND SO 
BORED 



For SI: 1 inch = 25.4 mm. 

NOTE: Condition for exterior and bearing walls. 



FIGURE R602.6(1) 
NOTCHING AND BORED HOLE LIMITATIONS FOR EXTERIOR WALLS AND BEARING WALLS 



132 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TOP PLATES 



BORED HOLE MAX. 
DIAMETER 60 PERCENT \ 
OF STUD DEPTH ^ 



5/glN. MIN. TOEDGE 



NOTCH MUST NOT EXCEED 
40 PERCENT OF STUD DEPTH 



BORED HOLES SHALL NOT BE 
LOCATED IN THE SAME CROSS 
SECTION OF CUT OR NOTCH IN 
STUD 




STUD 



5/g IN. MIN. TO EDGE 



For SI: 1 inch = 25.4 mm. 



FIGURE R602.6(2) 
NOTCHING AND BORED HOLE LIMITATIONS FOR INTERIOR NONBEARING WALLS 



R602.6.1 Drilling and notching of top plate. When piping 
or ductwork is placed in or pardy in an exterior wall or inte- 
rior load-bearing wall, necessitating cutting, drilling or 
notching of the top plate by more than 50 percent of its 
width, a galvanized metal tie of not less than 0.054 inch 
thick (1.37 mm) (16 ga) and 1 Vj inches (38 mm) wide shall 
be fastened across and to the plate at each side of the open- 
ing with not less than eight 16d nails at each side or equiva- 
lent. See Figure R602.6.1. 

Exception: When the entire side of the wall with the 
notch or cut is covered by wood structural panel sheath- 
ing. 

R602.7 Headers. For header spans see Tables R502.5(l) and 
R502.5(2). 

R602.7.1 Wood structural panel box headers. Wood 
structural panel box headers shall be constructed in accor- 
dance with Figure R602.7.2 and Table R602.7.2. 

R602.7.2 Nonbearing walls. Load-bearing headers are not 
required in interior or exterior nonbearing walls. A single 



flat 2-inch-by-4-inch (51 mm by 102 mm) member may be 
used as a header in interior or exterior nonbearing walls for 
openings up to 8 feet (2438 mm) in width if the vertical dis- 
tance to the parallel nailing surface above is not more than 
24 inches (610 mm). For such nonbearing headers, no crip- 
ples or blocking are required above the header. 

R602.8 Fireblocking required. Fireblocking shall be provided 
to cut off all concealed draft openings (both vertical and horizon- 
tal) and to form an effective fire barrier between stories, and 
between a top story and the roof space. Fireblocking shall be 
provided in wood-frame construction in the following locations. 

1 . In concealed spaces of stud walls and partitions, includ- 
ing furred spaces and parallel rows of studs or staggered 
studs; as follows: 

1.1. Vertically at the ceiling and floor levels. 

1.2. Horizontally at intervals not exceeding 10 feet 
(3048 mm). 



2006 INTERNATIONAL RESIDENTIAL CODE® 



133 



WALL CONSTRUCTION 



BCTERIOR OR BEARING WALL, 



NOTCH GREATER THAN 50 
PERCENT OF THE PU^TE WIDTH 




16 GAGE (0.054 IN.) AND 1 .5 IN. WIDE 
METAL TIE FASTENED ACROSS AND 
TO THE PLATE AT EACH SIDE OF THE 
NOTCH WITH 8-16d NAILS EACH SIDE 



TOP PLATES 



For SI: 1 inch = 25.4 mm. 



FIGURE R602.6.1 
TOP PLATE FRAMING TO ACCOMMODATE PIPING 



2. At all interconnections between concealed vertical and 
horizontal spaces such as occur at soffits, drop ceilings 
and cove ceilings. 

3 . In concealed spaces between stair stringers at the top and 
bottom of the run. Enclosed spaces under stairs shall 
comply with Section R3 11.2.2. 

4. At openings around vents, pipes, ducts, cables and wires 
at ceiling and floor level, with an approved material to 
resist the free passage of flame and products of combus- 
tion. 

5 . For the fireblocking of chimneys and fireplaces, see Sec- 
tion R1003. 19. 

6. Fireblocking of cornices of a two-family dwelling is 
required at the line of dwelling unit separation. 

R602.8.1 Materials. Except as provided in Section R602.8, 
Item 4, fireblocking shall consist of 2-inch (5 1 mm) nomi- 
nal lumber, or two thicknesses of 1-inch (25.4 mm) nominal 
lumber with broken lap joints, or one thickness of ^Vgj-inch 
(19.8 mm) wood structural panels with joints backed by 
2V32-inch (19.8 mm) wood structural panels or one thickness 
of V4-inch (19.1 mm) particleboard with joints backed by 
V4-inch (19.1 mm) particleboard, V2-inch (12.7 mm) gyp- 
sum board, or V4-inch (6.4 mm) cement-based millboard. 
Batts or blankets of mineral wool or glass fiber or other 
approved materials installed in such a manner as to be 
securely retained in place shall be permitted as an accept- 
able fire block. Batts or blankets of mineral or glass fiber or 
other approved nonrigid materials shall be permitted for 
compliance with the 10 foot horizontal fireblocking in walls 
constructed using parallel rows of studs or staggered studs. 



Loose-fill insulation material shall not be used as a fire 
block unless specifically tested in the form and manner 
intended for use to demonstrate its ability to remain in place 
and to retard the spread of fire and hot gases. 

R602.8.1.1 Unfaced fiberglass. Unfaced fiberglass batt 
insulation used as fireblocking shall fill the entire cross 
section of the wall cavity to a minimum height of 16 
inches (406 mm) measured vertically. When piping, con- 
duit or similar obstructions are encountered, the insula- 
tion shall be packed tightly around the obstruction. 

R602.8.1.2 Fireblocking integrity. The integrity of all 
fireblocks shall be maintained. 

R602.9 Cripple walls. Foundation cripple walls shall be 
framed of studs not smaller than the studding above. When 
exceeding 4 feet (1219 mm) in height, such walls shall be 
framed of studs having the size required for an additional story. 

Cripple walls with a stud height less than 14 inches (356 
mm) shall be sheathed on at least one side with a wood struc- 
tural panel that is fastened to both the top and bottom plates in 
accordance with Table R602.3(l), or the cripple walls shall be 
constructed of solid blocking. Cripple walls shall be supported 
on continuous foundations. ' 

R602.10 Wall bracing. All exterior walls shall be braced in 
accordance with this section. In addition, interior braced wall 
lines shall be provided in accordance with Section R602. 10. 1.1. 
For buildings in Seismic Design Categories Dq, Dj and D2, walls 
shall be constructed in accordance with the additional require- 
ments of Sections R602.10.9, R602.10.il, and R602.il. 



134 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R602.7.2 
MAXIMUM SPANS FOR WOOD STRUCTURAL PANEL BOX HEADERS^ 



HEADER 

construction" 


HEADER DEPTH 
(inches) 


HOUSE DEPTH (feet) 


24 


26 


28 


30 


32 


Wood structural 
panel — one side 


9 
15 


4 
5 


4 
5 


3 
4 


3 
3 


3 


Wood structural 
panel — both sides 


9 

15 


7 
8 


5 
8 


5 
7 


4 
7 


3 
6 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Spans are based on single story with clear-span trussed roof or two-story with floor and roof supported by interior-bearing walls. 

b. See Figure R602.7.2 for construction details. 



CRIPPUE* 



TOP PLATE* 



STRENGTH AXIS 




HEADER DEPTH 



STRENGTH AXIS 



WOOD 



9 IN. OR 
tSIN. 



STRUCTURAL 
PANEL* « 



INSULATION AS 
REQUIRED 



For SI: 1 inch = 25.4 ram, 1 foot = 304.8 mm. 
NOTES: 

a. The top plate shall be continuous over header. 

b. Jack studs shall be used for spans over 4 feet. SECTION 

c. Cripple spacing shall be the same as for studs. 

d. Wood structural panel faces shall be single pieces of ' ^732- inch-thick Exposure 1 (exterior glue) or thicker, installed on the interior or exterior or both sides of the 
header 

e. Wood structural panel faces shall be nailed to framing and cripples with 8d common or galvanized box nails spaced 3 inches on center, staggering alternate nails 
V2 inch. Galvanized nails shall be hot-dipped or tumbled. 

FIGURE R602.7.2 
TYPICAL WOOD STRUCTURAL PANEL BOX HEADER CONSTRUCTION 




2006 INTERNATIONAL RESIDENTIAL CODE"" 



135 



WALL CONSTRUCTION 



R602.10.1 Braced wall lines. Braced wall lines shall con- 
sist of braced wall panel construction in accordance with 
Section R602.10.3. The amount and location of bracing 
shall be in accordance with Table R602.10.1 and the 
amount of bracing shall be the greater of that required by 
the seismic design category or the design wind speed. 
Braced wall panels shall begin no more than 12.5 feet 
(3810 mm) from each end of a braced wall line. Braced 
wall panels that are counted as part of a braced wall line 
shall be in line, except that offsets out-of-plane of up to 4 
feet (1219 mm) shall be permitted provided that the total 
out-to-out offset dimension in any braced wall line is not 
more than 8 feet (2438 mm). 

R602.10.1.1 Spacing. Spacing of braced wall lines shall 
not exceed 35 feet (10 668 mm) on center in both the lon- 
gitudinal and transverse directions in each story. 

Exception: Spacing of braced wall lines not exceed- 
ing 50 feet shall be permitted where: 

1 . The wall bracing installed equals or exceeds the 
amount of bracing required by Table R602. 10. 1 
multiplied by a factor equal to the braced wall 
line spacing divided by 35 feet and 

2. The length-to- width ratio for the floor or roof 
diaphragm does not exceed 3:1. 

R602.10.2 Cripple wall bracing. 

R602.10.2.1 Seismic design categories other than D2. 

In Seismic Design Categories other than Dj, cripple 
walls shall be braced with an amount and type of bracing 
as required for the wall above in accordance with Table 
R602.10.1 with the following modifications for cripple 
wall bracing: 

1. The percent bracing amount as determined from 
Table R602.10.1 shall be increased by 15 percent 
and 

2. The wall panel spacing shall be decreased to 18 
feet (5486 mm) instead of 25 feet (7620 mm). 

R602.10.2.2 Seismic Design Category Dj. In Seismic 
Design Category D2, cripple walls shall be braced in 
accordance with Table R602.10.1. 

R602.10.2.3 Redesignation of cripple walls. In any 

seismic design category, cripple walls are permitted to be 
redesignated as the first story walls for purposes of deter- 
mining wall bracing requirements. If the cripple walls 
are redesignated, the stories above the redesignated story 
shall be counted as the second and third stories, respec- 
tively. 

R602.10.3 Braced wall panel construction methods. The 

construction of braced wall panels shall be in accordance 
with one of the following methods: 

1 . Nominal 1 -inch-by-4-inch (25 mm by 102 mm) con- 
tinuous diagonal braces let in to the top and bottom 
plates and the intervening studs or approved metal 
strap devices installed in accordance with the manu- 
facturer's specifications. The let-in bracing shall be 
placed at an angle not more than 60 degrees (1.06 



rad) or less than 45 degrees (0.79 rad) from the hori- 
zontal. 

2. Wood boards of ^/g inch (16 mm) net minimum thick- 
ness applied diagonally on studs spaced a maximum 
of 24 inches (610 mm). Diagonal boards shall be 
attached to studs in accordance with Table R602.3(l). 

3. Wood structural panel sheathing with a thickness not 
less than Vjg inch (8 mm) for 16-inch (406 mm) stud 
spacing and not less than Vg inch (9 mm) for 24-inch 
(610 mm) stud spacing. Wood structural panels shall 
be installed in accordance with Table R602.3(3). 

4. One-half-inch (13 mm) or 25/32-inch (20 mm) thick 
structural fiberboard sheathing applied vertically or 
horizontally on studs spaced a maximum of 16 
inches (406 mm) on center. Structural fiberboard 
sheathing shall be installed in accordance with Table 
R602.3(l). 

5 . Gypsum board with minimum Vj-inch (13 mm) thick- 
ness placed on studs spaced a maximum of 24 inches 
(610 mm) on center and fastened at 7 inches (178 mm) 
on center with the size nails specified in Table 
R602.3(l) for sheathing and Table R702.3.5 for inte- 
rior gypsum board. 

6. Particleboard wall sheathing panels installed in 
accordance with Table R602.3(4). 

7. Portland cement plaster on studs spaced a maximum 
of 16 inches (406 mm) on center and installed in 
accordance with Section R703.6. 

8. Hardboard panel siding when installed in accordance 
with Table R703. 4. 

Exception: Alternate braced wall panels constructed in 
accordance with Section R602. 10.6.1 or R602. 10.6.2 
shall be permitted to replace any of the above methods of 
braced wall panels. 

R602.10.4 Length of braced panels. For Methods 2, 3, 4, 
6, 7 and 8 above, each braced wall panel shall be at least 48 
inches (1219 nrni) in length, covering a minimum of three 
stud spaces where studs are spaced 16 inches (406 mm) on 
center and covering a minimum of two stud spaces where 
studs are spaced 24 inches (610 mm) on center. For Method 
5 above, each braced wall panel shall be at least 96 inches 
(2438 mm) in length where applied to one face of a braced 
wall panel and at least 48 inches (1219 mm) where applied 
to both faces. 

Exceptions: 

1. Lengths of braced wall panels for ^continuous 
wood structural panel sheathing shall be in accor- 
dance with Section R602. 10.5. 

2. Lengths of alternate braced wall panels shall be in 
accordance with Section R602. 10.6.1 or Section 
R602. 10.6.2. 

R602.10.5 Continuous wood structural panel sheathing. 

When continuous wood structural panel sheathing is pro- 
vided in accordance with Method 3 of Section R602. 10.3 on 
all sheathable areas of all exterior walls, and interior braced 



136 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R602.10.1 
WALL BRACING 



SEISMIC DESIGN CATEGORY OR 
WIND SPEED 


CONDITION 


TYPE OF BRACE"' = 


AMOUNT OF BRACING^' "' ^ 


Category A and B (S, < 0.35g 
and S^, < 0.33g) or 100 mph or 
less 


One story 
Top of two or three story 


Methodsl,2, 3,4, 5,6,7or8 


Located in accordance with Section R602. 10 and at 
least every 25 feet on center but not less than 16% 
of braced wall line for Methods 2 through 8. 


First story of two story 
Second story of three story 


Methods 1,2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
16% of braced wall line for Method 3 or 25% of 
braced wall hne for Methods 2, 4, 5, 6, 7 or 8. 


First story of three story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
25% of braced wall hne for Method 3 or 35% of 
braced wall line for Methods 2, 4, 5, 6, 7 or 8. 


Category C (S, < 0.6g and 
S^,<0.50g) or less than 110 
mph 


One story 
Top of two or three story 


Methods 1,2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
16% of braced wall Une for Method 3 or 25% of 
braced wall line for Methods 2, 4, 5, 6, 7 or 8. 


First story of two story 
Second story of three story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
30% of braced wall Une for Method 3 or 45% of 
braced wall Une for Methods 2, 4, 5, 6, 7 or 8. 


First story of three story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
45% of braced wall Une for Method 3 or 60% of 
braced wall Une for Methods 2, 4, 5, 6, 7 or 8. 


Categories Dq and Dj 
(S,<1.25gandS,,<0.83g) 
or less than 110 mph 


One story 
Top of two or three story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
20% of braced wall hne for Method 3 or 30% of 
braced waU Une for Methods 2, 4, 5, 6, 7 or 8. 


First story of two story 
Second story of three story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602. 10 and 
at least every 25 feet on center but not less than 
45% of braced wall Une for Method 3 or 60% of 
braced wall Une for Methods 2, 4, 5, 6, 7 or 8. 


First story of three story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
60% of braced waU Une for Method 3 or 85% of 
braced wall Une for Methods 2, 4, 5, 6, 7 or 8. 


Category Dj or less than 
110 mph 


One story 
Top of two story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
25% of braced wall Une for Method 3 or 40% of 
braced waU Une for Methods 2, 4, 5, 6, 7 or 8. 


First story of two story 


Methods 2, 3, 4, 5, 6, 7 or 8 


Located in accordance with Section R602.10 and 
at least every 25 feet on center but not less than 
55% of braced waU line for Method 3 or 75% of 
braced waU Une for Methods 2, 4, 5, 6, 7 or 8. 


Cripple walls 


Method 3 


Located in accordance with Section R602.10 
and at least every 25 feet on center but not less 
than 75% of braced wall line. 



For SI: 1 inch = 25.4 mm, 1 foot - 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 mile per hour = 0.477 m/s. 

a. Wall bracing amounts are based on a soil site class "D." Interpolation of bracing amounts between the S^^ values associated with the seismic design categories shall 
be permitted when a site specific S^^ value is determined in accordance with Section 1613.5 of the International Building Code. 

b. Foundation cripple wall panels shall be braced in accordance with Section R602.10.2. 

c. Methods of bracing shall be as described in Section R602. 10.3. The alternate braced wall panels described in Section R602. 10.6. 1 or R602. 10.6.2 shall also be per- 
mitted. 

d. The bracing amounts for Seismic Design Categories are based on a 15 psf wall dead load. For walls with a dead load of 8 psf or less, the bracing amounts shall be 
permitted to be multiplied by 0.85 provided that the adjusted bracing amount is not less than that required for the site's wind speed. The minimum length of braced 
panel shall not be less than required by Section R602.10.3. 

e. When the dead load of the roof/ceiling exceeds 15 psf, the bracing amounts shall be increased in accordance with Section R301. 2.2.2.1. Bracing required for a 
site's wind speed shall not be adjusted. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



137 



WALL CONSTRUCTION 



wall lines, where required, including areas above and below 
openings, bracing wall panel lengths shall be in accordance 
with Table R602.10.5. Wood structural panel sheathing 
shall be installed at comers in accordance with Figure 
R602.10.5. The bracing amounts in Table R602.10.1 for 
Method 3 shall be permitted to be multiplied by a factor of 
0.9 for wall with a maximum opening height that does not 
exceed 85 percent of the wall height or a factor of 0.8 for 
walls with a maximum opening height that does not exceed 
67 percent of the wall height. 

R602.10.6 Alternate braced wall panel construction 
methods. Alternate braced wall panels shall be constructed 
in accordance with Sections R602. 10.6. 1 and R602. 10.6.2. 

R602.10.6.1 Alternate braced wall panels. Altemate 
braced wall lines constructed in accordance with one of the 
following provisions shall be permitted to replace each 4 
feet (1219 mm) of braced wall panel as required by Section 
R602.10.4. The maximum height and minimum width of 
each panel shall be in accordance with Table R602.10.6: 

1. In one-story buildings, each panel shall be 
sheathed on one face with ^/g-inch-mini- 
mum- thickness (10 mm) wood structural panel 
sheathing nailed with 8d common or galvanized 
box nails in accordance with Table R602.3(l) and 
blocked at all wood structural panel sheathing 
edges. Two anchor bolts installed in accordance 
with Figure R403.1(l) shall be provided in each 
panel. Anchor bolts shall be placed at panel quarter 
points. Each panel end stud shall have a tie-down 
device fastened to the foundation, capable of pro- 
viding an uplift capacity in accordance with Table 
R602.10.6. The tie down device shall be installed 
in accordance with the manufacturer's recommen- 
dations. The panels shall be supported directly on a 



foundation or on floor framing supported directly 
on a foundation which is continuous across the 
entire length of the braced wall line. This founda- 
tion shall be reinforced with not less than one No. 4 
bar top and bottom. When the continuous founda- 
tion is required to have a depth greater than 12 
inches (305 mm), a minimum 12-inch-by- 12-inch 
(305 mm by 305 mm) continuous footing or turned 
down slab edge is permitted at door openings in the 
braced wall line. This continuous footing or turned 
down slab edge shall be reinforced with not less 
than one No. 4 bar top and bottom. This reinforce- 
ment shall be lapped 15 inches (381 mm) with the 
reinforcement required in the continuous founda- 
tion located directly under the braced wall line. 

2. In the first story of two-story buildings, each 
braced wall panel shall be in accordance with Item 
1 above, except that the wood structural panel 
sheathing shall be installed on both faces, sheath- 
ing edge nailing spacing shall not exceed 4 inches 
(102 mm) on center, at least three anchor bolts 
shall be placed at one-fifth points. 

R602.10.6.2 Alternate braced wall panel adjacent to a 
door or window opening. Altemate braced wall panels 
constructed in accordance with one of the following pro- 
visions are also permitted to replace each 4 feet (1219 
mm) of braced wall panel as required by Section 
R602. 10.4 for use adjacent to a window or door opening 
with a full-length header: 

1. In one-story buildings, each panel shall have a 
length of not less than 16 inches (406 mm) and a 
height of not more than 10 feet (3048 mm). Each 
panel shall be sheathed on one face with a single 
layer of Vg-inch-minimum- thickness (10 mm) 



TABLE R602.10.5 
LENGTH REQUIREMENTS FOR BRACED WALL PANELS IN A CONTINUOUSLY SHEATHED WALL^ "> = 



MINIMUM LENGTH OF BRACED WALL PANEL 
(inches) 


MAXIMUM OPENING HEIGHT NEXT TO THE BRACED WALL PANEL 
(% of wall height) 


8-foot wall 


9-foot wall 


10-foot wall 


48 


54 


60 


100 


32 


36 


40 


85 


24 


27 


30 


65 



For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 pound per square foot = 0.0479kPa. 

a. Linear interpolation shall be permitted. 

b. Full-height sheathed wall segments to either side of garage openings that support light frame roofs only, with roof covering dead loads of 3 psf or less shall be per- 
mitted to have a 4:1 aspect ratio, i 

c. Walls on either or both sides of openings in garages attached to fully sheathed dwellings shall be permitted to be built in accordance with Section R602. 10.6.2 and 
Figure R602. 10.6.2 except that a single bottom plate shall be permitted and two anchor bolts shall be placed at 1/3 points. In addition, tie-down devices shall not be 
required and the vertical wall segment shall have a maximum 6: 1 height-to-width ratio (with height being measured from top of header to the bottom of the sill 
plate). This option shall be permitted for the first story of two-story applications in Seismic Design Categories A through C. 



138 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



WALL CONSTRUCTION 



16dNAILAT12IN.O.C 




ORIENTATION OF STUD WIAV VARY.SE£ FIGURE R602.3{2) 



GYPSUM WALL BOARD INSTALLED IN 
ACCORDANCE WfTH CHAPTER 7 



1 



X 



ad NAIL AT 6 IN. 0,C. 
(ALL PANEL EDGES) 



8d NAIL AT 12 IN.O.CON ALL 
FRAMING MEMBERS NOT AT 
PANEL EDGES 



WOOD STRUaURAL PANEL 
INSTALLED IN ACCORDANCE 
WITH TABLE R602.3C1) 



fa) OUTSIDE CORNER DETAIL 



16dNAILAT12(N,O.C 




ORIENTATION OF STUD MAY VARY. SEE FIGURE R602.3(2) 



GYPSUM WALL BOARD INSTALLED IN 
ACCORDANCE WITH CHAPTER 7 (INTERIOR) 



I. 



N 



WOOD STRUaURAL PANEL 
INSTALLED (N ACCORDANCE 
WITH TABLE R602.3(1) 



8d NAIL AT6 IN.O.C.ALL FRAMING 
MEMBERS AT PANEL EDGES AND 12 IN. 
O.C.ON ALLFRAMING MEMBERS NOT 
AT PANEL EDGES 



{b| INSIDE CORNER DETAIL 



For SI: 1 inch = 25.4 mm. 

Gypsum board nails deleted for clarity. 



FIGURE R602.10.5 

TYPICAL EXTERIOR CORNER FRAMING FOR CONTINUOUS STRUCTURAL 

PANEL SHEATHING; SHOWING REQUIRED STUD-TO-STUD NAILING 



wood structural panel sheathing nailed with 8d 
common or galvanized box nails in accordance 
with Figure R602. 10.6.2. The wood structural 
panel sheathing shall extend up over the solid sawn 
or glued-laminated header and shall be nailed in 
accordance with Figure R602. 10.6.2. Use of a 
built-up header consisting of at least two 2 x 12s 
and fastened in accordance with Table R602.3(l) 
shall be permitted. A spacer, if used, shall be 
placed on the side of the built-up beam opposite 
the wood structural panel sheathing. The header 
shall extend between the inside faces of the first 
full-length outer studs of each panel. The clear 
span of the header between the inner studs of each 
panel shall be not less than 6 feet (1829 mm) and 
not more than 1 8 feet (5486 mm) in length. A strap 



with an uplift capacity of not less than 1000 
pounds (4448 N) shall fasten the header to the side 
of the inner studs opposite the sheathing. One 
anchor bolt not less than %-inch-diameter (16 
mm) and installed in accordance with Section 
R403 .1.6 shall be installed in the center of each sill 
plate. The studs at each end of the panel shall have 
a tie-down device fastened to the foundation with 
an uplift capacity of not less than 4,200 pounds 
(18 683 N). 

Where a panel is located on one side of the open- 
ing, the header shall extend between the inside face 
of the first full-length stud of the panel and the bear- 
ing studs at the other end of the opening. A strap 
with an uplift capacity of not less than 1000 pounds 
(4448 N) shall fasten the header to the bearing 



2006 INTERNATIONAL RESIDENTIAL CODE® 



139 



WALL CONSTRUCTION 



TABLE R602.10.6 
MINIMUM WIDTHS AND TIE-DOWN FORCES OF ALTERNATE BRACED WALL PANELS 



SEISMIC DESIGN 

CATEGORY AND 

WINDSPEED 


TIE-DOWN 
FORCE (lb) 


HEIGHT OF BRACED WALL PANEL 


Sheathed Width 


8 ft. 

2' - 4 " 


9 ft. 
2' - 8" 


10 ft. 
2' - 8 " 


11ft. 

3' - 2 " 


12 ft. 
3' - 6 " 


SDC A, B, and C 
Windspeed< 110 
mph 


R602. 10.6.1, Item 1 


1800 


1800 


1800 


2000 


2200 


R602.10.6.1,Item2 


3000 


3000 


3000 


3300 


3600 


SDC Do, Di and 
D2 Windspeed < 
110 mph 


R602. 10.6.1, Item 1 


Sheathed Width 


2' - 8" 


2' - 8" 


2' - 8" 


Note a 


Note a 


1800 


1800 


1800 


— 


— 


R602.10.6.1,Item2 


3000 


3000 


3000 


— 


— 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Not permitted because maximum height is 10 feet. 




EXTENT OF HEADER 
"DOUBLE PORTAL FRAME (TWO BRACED WALL PANELS) 



EXTENT OF HEADER 
SINGLE PORTAL FRAME (ONE BRACED WALL PANEL) 



MIN. 3"X11.25" NET HEADER 



-6' TO 18'- 



FASTEN TOP PLATE TO HEADER WITH TWO 
ROWS OF 1 6D SINKER NAILS AT 3" O.C. TYP 

1000 LB STRAP OPPOSITE SHEATHING 



1000 LB 
STRAP 



FASTEN SHEATHING TO HEADER WITH 8D COMMON OR 
GALVANIZED BOX NAILS IN 3" GRID PATTERN AS SHOWN AND 
3" O.C. IN ALL FRAMING (STUDS, BLOCKING, AND SILLS) TYR 

MIN. WIDTH = 16" FOR ONE STORY STRUCTURES 
MIN. WIDTH = 24" FOR USE IN THE FIRST OF TWO 
STORY STRUCTURES 



MIN. 2x4 FRAMING 

3/8" MIN. THICKNESS WOOD 
STRUCTURAL PANEL SHEATHING 



MIN. 

DOUBLE 

2x4 POST 



MIN. 4200 LB TIE-DOWN DEVICE (EMBEDDED INTO 
CONCRETE AND NAILED INTO FRAMING) . 

SEE SECTION R602. 10.6.2 



TYPICAL PORTAL -~- 

FRAME 
CONSTRUCTION 

FOR A PANEL SPLICE 
(IF NEEDED), PANEL 
EDGES SHALL BE 
BLOCKED, AND OCCUR 
WITHIN 24" OF MID- 
HEIGHT ONE ROW OF 
TYP SHEATH I NG-TO- 
FRAMING NAILING IS 
REQUIRED. 
IF 2X4 BLOCKING IS 
USED, THE 2X4'S MUST 
BE NAILED TOGETHER 
WITH 3 16D SINKERS 



MIN. 1000 LB 
TIE DOWN 
DEVICE 




For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg. 



FIGURE R602.10.6.2 
ALTERNATE BRACED WALL PANEL ADJACENT TO A DOOR OR WINDOW OPENING 



140 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



WALL CONSTRUCTION 



Studs. The bearing studs shall also have a tie-down 
device fastened to the foundation with an uplift 
capacity of not less than 1000 pounds (4448 N). 

The tie-down devices shall be an embedded- 
strap type, installed in accordance with the manu- 
facturer's recommendations. The panels shall be 
supported directly on a foundation which is con- 
tinuous across the entire length of the braced wall 
line. The foundation shall be reinforced with not 
less than one No. 4 bar top and bottom. 

Where the continuous foundation is required to 
have a depth greater than 12 inches (305 mm), a 
minimum 12-inch-by- 12-inch (305 mm by 305 
mm) continuous footing or turned down slab edge 
is permitted at door openings in the braced wall 
line. This continuous footing or turned down slab 
edge shall be reinforced with not less than one No. 
4 bar top and bottom. This reinforcement shall be 
lapped not less than 15 inches (381 mm) with the 
reinforcement required in the continuous founda- 
tion located directly under the braced wall line. 

2. In the first story of two-story buildings, each wall 
panel shall be braced in accordance with Item 1 
above, except that each panel shall have a length of 
not less than 24 inches (610 mm). 

R602.10.7 Panel joints. All vertical joints of panel sheath- 
ing shall occur over, and be fastened to, common studs. Hor- 
izontal joints in braced wall panels shall occur over, and be 
fastened to, common blocking of a minimum 1 Vj inch (38 
mm) thickness. 

Exception: Blocking is not required behind horizontal 
joints in Seismic Design Categories A and B and 
detached dwellings in Seismic Design Category C when 
constructed in accordance with Section R602.10.3, 
braced-wall-panel construction method 3 and Table 
R602.10.1, method 3, or where permitted by the manu- 
facturer's installation requirements for the specific 
sheathing material. 

R602.10.8 Connections. Braced wall line sole plates shall 
be fastened to the floor framing and top plates shall be con- 
nected to the framing above in accordance with Table 
R602.3(l). Sills shall be fastened to the foundation or slab in 
accordance with Sections R403.1.6 and R602.il. Where 
joists are perpendicular to the braced wall lines above, 
blocking shall be provided under and in line with the braced 
wall panels. Where joists are perpendicular to braced wall 
lines below, blocking shall be provided over and in line with 
the braced wall panels. Where joists are parallel to braced 
wall lines above or below, a rim joist or other parallel fram- 
ing member shall be provided at the wall to permit fastening 
per Table R602.3(l). 

R602.10.9 Interior braced wall support. In one-story 
buildings located in Seismic Design Category Dj, interior 
braced wall lines shall be supported on continuous founda- 
tions at intervals not exceeding 50 feet (15 240 mm). In two- 
story buildings located in Seismic Design Category Dj, all 
interior braced wall panels shall be supported on continuous 
foundations. 



Exception: Two-story buildings shall be permitted to 
have interior braced wall lines supported on continuous 
foundations at intervals not exceeding 50 feet (15 240 
mm) provided that: 

1 . The height of cripple walls does not exceed 4 feet 
(1219 mm). 

2. First-floor braced wall panels are supported on 
doubled floor joists, continuous blocking or floor 
beams. 

3. The distance between bracing lines does not 
exceed twice the building width measured parallel 
to the braced wall line. 

R602.10.10 Design of structural elements. Where a build- 
ing, or portion thereof, does not comply with one or more of 
the bracing requirements in this section, those portions shall 
be designed and constructed in accordance with accepted 
engineering practice. 

R602.10.il Bracing in Seismic Design Categories Dq, 

Di and Dj. Structures located in Seismic Design Catego- 
ries Dq, Di and D2 shall have exterior and interior braced 
wall lines. 

R602.10.il. 1 Braced wall line spacing. Spacing 
between braced wall lines in each story shall not exceed 
25 feet (7620 mm) on center in both the longitudinal and 
transverse directions. 

Exception: In one- and two-story buildings, spacing 
between two adjacent braced wall lines shall not 
exceed 35 feet (10 363 mm) on center in order to 
accommodate one single room not exceeding 900 
square feet (84 m^) in each dwelling unit. Spacing 
between all other braced wall lines shall not exceed 25 
feet (7620 mm). 

R602.10.il. 2 Braced wall panel location. Exterior 
braced wall lines shall have a braced wall panel at each 
end of the braced wall line. 

Exception: For braced wall panel construction 
Method 3 of Section R602. 10.3, the braced wall panel 
shall be permitted to begin no more than 8 feet (2438 
mm) from each end of the braced wall line provided 
the following is satisfied: 

1. A minimum 24-inch- wide (610 mm) panel is 
applied to each side of the building comer and 
the two 24-inch (610 mm) panels at the comer 
shall be attached to framing in accordance with 
Figure R602. 10.5; or 

2. The end of each braced wall panel closest to the 
corner shall have a tie-down device fastened to 
the stud at the edge of the braced wall panel 
closest to the comer and to the foundation or 
framing below. The tie-down device shall be 
capable of providing an uplift allowable design 
value of at least 1,800 pounds (8 kN). The 
tie-down device shall be installed in accordance 
with the manufacturer's recommendations. 



2006 INTERNATIONAL RESIDENTIAL CODE** 



141 



WALL CONSTRUCTION 



R602.10.11.3 Collectors. A designed collector shall be 
provided if a braced wall panel is not located at each end 
of a braced wall line as indicated in Section 
R602.10.11.2, or, when using the Section R602.10.11.2 
exception, if abraced wall panel is more than 8 feet (2438 
mm) from each end of a braced wall line. 

R602.10.11.4 Cripple wall bracing. In addition to the 
requirements of Section R602.10.2, where interior 
braced wall lines occur without a continuous foundation 
below, the length of parallel exterior cripple wall bracing 
shall be one and one-half times the length required by 
Table R602.10.1. Where cripple walls braced using 
Method 3 of Section R602. 10.3 cannot provide this addi- 
tional length, the capacity of the sheathing shall be 
increased by reducing the spacing of fasteners along the 
perimeter of each piece of sheathing to 4 inches (102 
mm) on center. 

R602.10.11.5 Sheathing attachment. Adhesive attach- 
ment of wall sheathing shall not be permitted in Seismic 
Design Categories C, Dq, Dj and Dj. 

R602.il Framing and connections for Seismic Design Cat- 
egories Do, Dj and D2. The framing and connections details of 
buildings located in Seismic Design Categories Dq, Dj and D2 
shall be in accordance with Sections R602.11.1 through 
R602.11.3. 

R602.11.1 Wall anchorage. Braced wall hne sills shall be 
anchored to concrete or masonry foundations in accordance 
with Sections R403.1.6 and R602.il. For all buildings in 
Seismic Design Categories Dq, D, and Dj and townhouses in 



Seismic Design Category C, plate washers, a minimum of 
0.229 inch by 3 inches by 3 inches (5.8 mm by 76 mm by 76 
mm) in size, shall be installed between the foundation sill 
plate and the nut. The hole in the plate washer is permitted to 
be diagonally slotted with a width of up to Vjg inch (5 mm) 
larger than the bolt diameter and a slot length not to exceed 
IV4 inches (44 mm), provided a standard cut washer is 
placed between the plate washer and the nut. 

R602.11.2 Interior braced wall panel connections. Inte- 
rior braced wall hues shall be fastened to floor and roof 
framing in accordance with Table R602.3(l), to required 
foundations in accordance with Section R602. 11.1, and in 
accordance with the following requirements: 

1 . Floor joists parallel to the top plate shall be toe-nailed 
to the top plate with at least 8d nails spaced a maxi- 
mum of 6 inches (152 mm) on center. 

2. Top plate laps shall be face-nailed with at least eight 
16d nails on each side of the splice. 

R602.11.3 Stepped foundations. Where stepped founda- 
tions occur, the following requirements apply: 

1 . Where the height of a required braced wall panel that 
extends from foundation to floor above varies more 
than 4 feet (1220 mm), the braced wall panel shall be 
constructed in accordance with Figure R602.11.3. 

2. Where the lowest floor framing rests directly on a sill 
bolted to a foundation not less than 8 feet (2440 mm) 
in length along a line of bracing, the line shall be con- 
sidered as braced. The double plate of the cripple stud 



2x SILL PLATE 



CONCRETE 

STEPPED 

FOOTING 




2 FT MIN. 



(^ 



SPLICE 



'//I v\\\ '//I sVWV// \\V '// 






%7 



.WHERE FOOTING SECTION "A" IS MORE THAN 8 FT 
PROVIDE METAL TIE 16 GA BY1,5BY4FT MIN. EACH 
SIDE OF SPLICE W/ 8-1 6d COMMON NAILS. 



. 2- 2x PLATE 



A 



///) 



FOOTING SECTION "A" 




v// n\\v y// v\v\^/// \\v w/ n\\v v// x\\\^/// 




2k CRIPPLE 
STUD WALL 



W A\\ V// s\\\V// \\v 



For SI: 1 inch 25.4 mm, 1 foot = 304.8 mm. ; 

Note: Where footing Section "A" is less than 8 feet long in a 25-foot-long wall, install bracing at cripple stud wall. 

FIGURE R602.11. 3 
STEPPED FOUNDATION CONSTRUCTION 



142 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



WALL CONSTRUCTION 



wall beyond the segment of footing that extends to the 
lowest framed floor shall be spliced by extending the 
upper top plate a minimum of 4 feet (1219 mm) along 
the foundation. Anchor bolts shall be located a maxi- 
mum of 1 foot and 3 feet (305 and 914 mm) from the 
step in the foundation. 

Where cripple walls occur between the top of the 
foundation and the lowest floor framing, the bracing 
requirements for a story shall apply. 

Where only the bottom of the foundation is stepped 
and the lowest floor framing rests directly on a sill 
bolted to the foundations, the requirements of Section 
R602.11.1 shall apply. 



SECTION R603 
STEEL WALL FRAMING 

R603.1 General. Elements shall be straight and free of any 
defects that would significantly affect structural performance. 
Cold-formed steel wall framing members shall comply with 
the requirements of this section. 

R603.1.1 Applicability limits. The provisions of this section 
shall control the construction of exterior steel wall framing 
and interior load-bearing steel wall framing for buildings not 
more than 60 feet ( 1 8 288 mm) long perpendicular to the joist 
or truss span, not more than 40 feet (12192 mm) wide parallel 
to the joist or truss span, and not more than two stories in 
height. All exterior walls installed in accordance with the pro- 
visions of this section shall be considered as load-bearing 
walls. Steel walls constructed in accordance with the provi- 
sions of this section shall be limited to sites subjected to a 
maximum design wind speed of 1 10 miles per hour (49 m/s) 
Exposure A, B or C and a maximum ground snow load of 70 
psf(3.35kPa). 



R603.1.2 In-line framing. Load-bearing steel studs con- 
structed in accordance with Section R603 shall be located 
direcdy in-line with joists, trusses and rafters with a maxi- 
mum tolerance of V4 inch (19.1 mm) between their center 
lines. Interior load-bearing steel stud walls shall be supported 
on foundations or shall be located directly above load-bear- 
ing walls with a maximum tolerance of V4 inch (19 nmi) 
between the centerline of the studs. 

R603.2 Structural framing. Load-bearing steel wall framing 
members shall comply with Figure R603.2(l) and with the 
dimensional and minimum thickness requirements specified in 
Tables R603.2(l) and R603.2(2). Tracks shall comply with Fig- 
ure R603.2(2) and shall have a minimum flange width of IV4 
inches (32 mm). The maximum inside bend radius for members 
shall be the greater of V32 inch (2.4 mm) or twice the uncoated 
steel thickness. Holes in wall studs and other structural members 
shall comply with all of the following conditions: 

1. Holes shall conform to Figure R603.2(3); 

2. Holes shall be permitted only along the centerline of the 
web of the framing member; 

3. Holes shall have a center-to-center spacing of not less 
than 24 inches (610 mm); 

4. Holes shall have a width not greater than 0.5 times the 
member depth, or 1 V2 inches (38.1 mm); 

5. Holes shall have a length not exceeding 4V2 inches (1 14 
mm); and 

6. Holes shall have a minimum distance between the edge 
of the bearing surface and the edge of the hole of not less 
than 10 inches (254 mm). 

Framing members with web holes violating the above require- 
ments shall be patched in accordance with Section R603.3.5 or 
designed in accordance with accepted engineering practices. 



TABLE R603.2(1) 
LOAD-BEARING COLD-FORMED STEEL STUD SIZES 



MEMBER DESIGNATION^ 


WEB DEPTH 
(inches) 


MINIMUM FLANGE WIDTH 
(inches) 


MAXIMUM FLANGE WIDTH 
(inches) 


MINIMUM LIP SIZE 
(inches) 


350S162-t 


3.5 


L625 


2 


0.5 


550S162-t 


5.5 


1.625 


2 


0.5 



For SI: 1 inch = 25.4 mm; 1 mil = 0.0254 mm. 

a. The member designation is defined by the first number representing the member depth in hundredths of an inch "S" representing a stud or joist member, the second 

number representing the flange width in hundredths of an inch, and the letter "t" shall be a number representing the minimum base metal thickness in mils [See 

Table R603. 2(2)]. 



TABLE R603.2(2) 
MINIMUM THICKNESS OF COLD-FORMED STEEL STUDS 



DESIGNATION (mils) 


MINIMUM UNCOATED THICKNESS (inches) 


REFERENCE GAGE NUMBER 


33 


0.033 


20 


43 


0.043 


18 


54 


0.054 


16 


68 


0.068 


14 



For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



143 



WALL CONSTRUCTION 



FLANGE 



WEB 



DEPTH OF WEB 
(OUTSIDE TO 
OUTSIDE) 




FLANGE 



WEB 




FIGURE R603.2(1) 
C-SECTION 



R603.2.1 Material. Load-bearing steel framing members 
shall be cold-formed to shape from structural quality sheet 
steel complying with the requirements of one of the follow- 
ing: 

1. ASTM A 653: Grades 33, 37, 40 and 50 (Class 1 and 
3). 

2. ASTM A 792: Grades 33, 37, 40 and 50A. 

3 . ASTM A 875 : Grades 33,37, 40 and 50 (Class 1 and 3). 

4. ASTM A 1003: Grades 33, 37, 40 and 50. 

R603.2.2 Identification. Load-bearing steel framing mem- 
bers shall have a legible label, stencil, stamp or embossment 
with the following information as a minimum: 

1. Manufacturer's identification. 

2. Minimum uncoated steel thickness in inches (mm). 

3. Minimum coating designation. 

4. Minimum yield strength, in kips per square inch (ksi) 

(kN). 

R603.2.3 Corrosion protection. Load-bearing steel fram- 
ing shall have a metallic coating complying with one of the 
following: 

1 . A minimum of G 60 in accordance with ASTM A 
653. 

2. A minimum of AZ 50 in accordance with ASTM A 

792. 

3. A minimum of GF 60 in accordance with ASTM A 

875. 

R603.2.4 Fastening requirements. Screws for steel-to-steel 
connections shall be installed with a minimum edge distance 



FIGURE R603.2(2) 
TRACK SECTION 




MAX. 



PENETRATION 
(HOLE. PUNCHOUT) 



r/a" MAX. 



STUD & PUNCHOUT 



For SI: 1 inch = 25.4 mm. 



FIGURE R603.2(3) 
WEB HOLES 



and center-to-center spacing of Vj inch (12.7 mm), shall be 
self-drilling tapping and shall conform to S AE J 78. Structural 
sheathing shall be attached to steel studs with minimum No. 8 
self-drilling tapping screws that conform to SAE J 78. Screws 
for attaching structural sheathing to steel wall framing shall 
have a minimum head diameter of 0.292 inch (7.4 mm) with 
countersunk heads and shall be installed with a minimum edge 
distance of Vg inch (9.5 mm). Gypsum board shall be attached 



144 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



to steel wall framing with minimum No. 6 screws conforming 
to ASTM C 954 and shall be installed in accordance with Sec- 
tion R702. For all connections, screws shall extend through the 
steel a minimum of three exposed threads. All self-drilling tap- 
ping screws conforming to S AE J 78 shall have a Type 11 coat- 
ing in accordance with ASTM B 633. 

Where No. 8 screws are specified in a steel-to-steel con- 
nection the required number of screws in the connection is 
permitted to be reduced in accordance with the reduction 
factors in Table R603.2.4, when larger screws are used or 
when one of the sheets of steel being connected is thicker 
than 33 mils (0.84 mm). When applying the reduction factor 
the resulting number of screws shall be rounded up. 

TABLE R603.2.4 
SCREW SUBSTITUTION FACTOR 



SCREW SIZE 


THINNEST CONNECTED STEEL SHEET (mils) 


33 


43 


#8 


1.0 


0.67 


#10 


0.93 


0.62 


#12 


0.86 


0.56 



For SI: 1 mil = 0.0254 mm. 

R603.3 Wall construction. All exterior steel framed walls and 
interior load-bearing steel framed walls shall be constructed in 
accordance with the provisions of this section and Figure R603.3. 

R603.3.1 Wall to foundation or floor connections. Steel 
framed walls shall be anchored to foundations or floors in 
accordance with Table R603.3.1 and Figure R603.3.1(l) or 
R603.3.1(2). 

R603.3.2 Load-bearing walls. Steel studs shall comply 
with Tables R603.3.2(2) through R603.3.2(21). The tabu- 
lated stud thickness for structural walls shall be used when 
the attic load is 10 psf (0.48 kPa) or less. When an attic stor- 
age load is greater than 10 psf (0.48 kPa) but less than or 
equal to 20 psf (0.96 kPa), the next higher snow load column 
value from Tables R603.3.2(2) through R603.3.2(21) shall 
be used to select the stud size. The tabulated stud thickness 
for structural walls supporting one floor, roof and ceiling 
shall be used when the second floor live load is 30 psf (1 .44 
kPa). When the second floor live load is greater than 30 psf 
(1.44 kPa) but less than or equal to 40 psf (1.92 kPa) the 
design value in the next higher snow load column from 
Tables R603.2(12) through R603.3.2(21) shall be used to 
select the stud size. 

Fastening requirements shall be in accordance with Section 
R603.2.4 and Table R603.3.2(l). Tracks shall have the same 
minimum thickness as the wall studs. Exterior walls with a 
minimum of '^-inch (13 mm) gypsum board installed in 
accordance with Section R702 on the interior surface and 
wood structural panels of minimum Vi^-inch thick (1 1mm) ori- 
ented-strand board or 'Vjj-inch thick (12 mm) plywood 
installed in accordance with Table R603.3.2(l) on the outside 
surface shall be permitted to use the next thinner stud from 
Tables R603.3.2(2) through R603.3.2(13) but not less than 33 
mils (0.84 mm). Interior load-bearing walls with a minimum 
Vj-inch (13 mm) gypsum board installed in accordance with 
Section R702 on both sides of the wall shall be permitted to use 



the next thinner stud from Tables R603.3.2(2) through 
R603.3.2(13) but not less than 33 mils (0.84 mm). 

R603.3.3 Stud bracing. The flanges of steel studs shall be 
laterally braced in accordance with one of the following: 

1 . Gypsum board installed with minimum No. 6 screws 
in accordance with Section R702 or structural sheath- 
ing installed in accordance with Table R603. 3.2(1). 

2. Horizontal steel strapping installed in accordance with 
Figure R603.3 at mid-height for 8-foot (2438 mm) 
walls, and one-third points for 9-foot and 10-foot 
(2743 mm and 3048 mm) walls. Steel straps shall be at 
least 1.5 inches in width and 33 mils in thickness (38 
mm by 0.84 mm). Straps shall be attached to the 
flanges of studs with at least one No. 8 screw. In-Une 
blocking shall be installed between studs at the termi- 
nation of all straps. Straps shall be fastened to the 
blocking with at least two No. 8 screws. 

3. Sheathing on one side and strapping on the other side. 
Sheathing shall be installed in accordance with 
Method #1 above. Steel straps shall be installed in 
accordance with Method #2 above. 

R603.3.4 Cutting and notching. Flanges and hps of steel 
studs and headers shall not be cut or notched. 

R603.3.5 Hole patching. Web holes violating the require- 
ments in Section R603.2 shall be designed in accordance 
with one of the following: 

1. Framing members shall be replaced or designed in 
accordance with accepted engineering practices when 
web holes exceed the following size limits: 

1.1. The depth of the hole, measured across the 
web, exceeds 70 percent of the flat width of 
the web; or 

1.2. The length of the hole measured along the 
web exceeds 10 inches (254 mm) or the depth 
of the web, whichever is greater. 

2. Web holes not exceeding the dimensional require- 
ments in R603. 3.5(1) shall be patched with a solid 
steel plate, stud section, or track section in accordance 
with Figure R603.3.5. The steel patch shall be as a 
minimum the same thickness as the receiving mem- 
ber and shall extend at least 1 inch (25 mm) beyond all 
edges of the hole. The steel patch shall be fastened to 
the web of the receiving member with No. 8 screws 
spaced no more than 1 inch (25 mm) center-to-center 
along the edges of the patch with a minimum edge dis- 
tance of V2 inch (13 mm). 

R603.3.6 Splicing. Steel studs and other structural mem- 
bers shall not be spliced. Tracks shall be spliced in accor- 
dance with Figure R603.3.6. 

R603.4 Corner framing. Comer studs and the top tracks shall 
be installed in accordance with Figure R603.4. 

R603.5 Exterior wall covering. The method of attachmelit of 
exterior wall covering materials to cold-formed steel stud wall 
framing shall conform to the manufacturer's installation 
instructions. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



145 



WALL CONSTRUCTION 



STRUCTURAL 
SHEATHING 




TRACK 



FOUNDATION 
ANCHOR 



STRUCTURAL 
SHEATHING 



BLOCKING 



INTERIOR HORIZONTAL STUD BRACING 
(OR ''/2 IN. GYPSUM BOARD) 



For SI: 1 inch = 25.4 mm. 



MN-LINE FRAMING 



FIGURE R603.3 
STEEL WALL CONSTRUCTION 



TABLE R603.3.1 
WALL TO FOUNDATION OR FLOOR CONNECTION REQUIREMENTS^ "' 



FRAMING CONDITION 


BASIC WIND SPEED (mph) AND EXPOSURE 


85 A/B or Seismic Design 
Categories A, B and C 


85 C or less than 110 A/B 


Less than 110 c 


Wall bottom track to floor joist or track 


1-No. 8 screw at 12" o.c. 


1-No. 8 screw at 12"o.c. 


2-No. 8 screw at 12" o.c. 


Wall bottom track to wood sill per Figure 
R603.3.1(2) 


Steel plate spaced at 4' o.c, 
with 4-No. 8 screws and 
4-lOd or 6-8d common nails 


Steel plate spaced at 3' o.c, 
with 4-No. 8 screws and 
4-lOd or 6-8d common nails 


Steel plate spaced at 2' o.c, 
with 4-No. 8 screws and 
4-lOd or 6-8d common nails 


Wall bottom track to foundation per Figure 
R603.3.1(l) 


V2" minimum diameter 
anchor bolt at 6' o.c. 


V2" minimum diameter 
anchor bolt at 6' o.c. 


V2" minimum diameter 
anchor bolt at 4' o.c. 


Wind uplift connector capacity for 16-inch stud 
spacing'^ 


N/R 


N/R 


651b 


Wind uplift connector capacity for 24-inch stud 
spacing'^ 


N/R 


N/R 


1001b 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound = 4.4 N. 

a. Anchor bolts shall be located not more than 1 2 inches from comers or the terminatidn of bottom tracks (e.g., at door openings or comers). Bolts shall extend a mini- 
mum of 7 inches into concrete or masonry. 

b. All screw sizes shown are minimum. 

c. N/R = uplift connector not required. Uplift connectors are in addition to other connection requirements and shall be apphed in accordance with Section R603 .8 . 



146 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



4 SCREWS IN EACH 
FLANGE 



STUD BLOCKING INSIDE WALL 
TRACK (MIN. THICKNESS AS 
WALL STUD) 



TRACK 



FOUNDATION 



fK. 




■ WALL STUD 



SCREWS AT 
EACH FLANGE 



ANCHOR BOLT 



For SI: 1 inch = 25.4 mm. 



FIGURE R603.3.1(1) 
WALL TO FOUNDATION CONNECTION 



WALL STUD 




FOUNDATION 



3 IN. X 4 IN. X 33 MIL PLATE (MIN.] 
4 SCREWS 
4-10d OR 6-8d COMMON 



ANCHOR BOLT THROUGH 
WOOD SILL 



For SI: 1 inch = 25.4 mm. 



FIGURE R603.3.1 (2) 
WALL TO WOOD SILL CONNECTION 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



147 



WALL CONSTRUCTION 



TABLE R603.3.2(1) 
WALL FASTENING SCHEDULE^ 



DESCRIPTION OF BUILDING ELEMENT 


NUMBER AND SIZE OF FASTENERS^ 


SPACING OF FASTENERS 


Floor joist to track of load-bearing wall 


2-No. 8 screws 


Each joist 


Wall stud to top or bottom track 


2-No. 8 screws 


Each end of stud, one per flange 


Structural sheathing to wall studs 


No. 8 screws 


6" o.c. on edges and 12" o.c. at intermediate 
supports 


Roof framing to wall 


Approved design or tie down in accordance with Section R802. 1 1 



For SI: 1 inch = 25.4 mm. 

a. All screw sizes shown are minimum. 



SCREWS 1 IN. O.C. (TYP.) 




SOLID STEEL PLATE, 
C-SECTION OR TRACK 
MINIMUM THICKNESS 
AS STUD 



For SI: 1 inch = 25.4 mm. 



FIGURE R603.3.5 
HOLE PATCH 



R603.6 Headers. Headers shall be installed above wall open- 
ings in all exterior walls and interior load-bearing walls in 
accordance with Figure R603.6 and Tables R603.6(l) through 
R603.6(8), or shall be designed in accordance with the AISI 
Standard for Cold-formed Steel Framing-Header Design 
(COFS/Header Design). 

R603.6.1 Jack and king studs, and head track. The num- 
ber of jack and king studs shall comply with Table 
R603.6(9). King and jack studs shall be of the same dimen- 
sion and thickness as the adjacent wall studs. Headers con- 
structed of C-shape framing members shall be connected to 
king studs in accordance with Table R603.6.(10). One-half 
the total number of screws shall be applied to the header and 
one-half to the king stud by use of a minimum 2-inch by 
2-inch (51 mm by 51 mm) clip angle or 4-inch-wide (102 
mm) steel plate. The clip angle or plate shall extend the 
depth of the header minus Vj inch (13 mm) and shall have a 
minimum thickness of the header members or the wall 
studs, whichever is thicker. 



Head track spans shall comply with Table R603 .6( 11) and 
shall be in accordance with Figures R603.3 and R603.6. 
Increasing the head track tabular value shall not be prohibited 
when in accordance with one of the following: 

1 . For openings less than 4 feet (1219 mm) in height that 
have a top and bottom head track, multiply the tabular 

' value by 1.75; or 

2. For openings less than 6 feet ( 1 829 mm) in height that 
have a top and bottom head track, multiply the tabular 
value by 1.50. 

1R603.7 Structural sheathing. In areas where the basic wind 
speed is less than 1 10 miles per hour (49 m/s), wood structural 
panel sheathing shall be installed on all exterior walls of build- 
ings in accordance with this section. Wood structural panel 
sheathing shall consist of minimum Vig-inch-thick (11 mm) 
oriented-strand board or 'Vgj-inch-thick (12 mm) plywood and 
shall be installed on all exterior wall surfaces in accordance 
with Section R603.7.1 and Figure R603.3. The minimum 
length of full height sheathing on exterior walls shall be deter- 
mined in accordance with Table R603.7, but shall not be less 
than 20 percent of the braced wall length in any case. The mini- 
mum percentage of full height sheathing in Table R603.7 shall 
include only those sheathed wall sections, uninterrupted by 
openings, which are a minimum of 48 inches (1 120 mm) wide. 
The minimum percentage of full-height structural sheathing 
shall be multiplied by 1.10 for 9-foot-high (2743 mm) walls 
and multiplied by 1.20 for 10-foot-high (3048 mm) walls. In 
addition, structural sheathing shall: 

1 . Be installed with the long dimension parallel to the stud 
framing and shall cover the full vertical height of studs, 
from the bottom of the bottom track to the top of the top 
track of each story. 

2. Be applied to each end (comers) of each of the exterior 
walls with a minimum 48-inch-wide (1219 mm) panel. 

R603.7.1 Structural sheathing fastening. All edges and 
interior areas of wood structural panel sheathing shall be | 
fastened to a framing member and tracks in accordance with 
Table R603.3.2(l). 

R603.7.2 Hold-down requirements. Multiplying the per- 
centage of structural sheathing required in Table R603 .7 by 
. 0.6 is permitted where a hold-down anchor with a capacity 
of 4,300 pounds ( 1 9 kN) is provided at each end of exterior 
walls. Installations of a single hold-down anchor at wall cor- 
ners is permitted. 



148 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 




4 SCREWS ON EACH 
SIDE OF SPLICE 



'STUD SECTION 
INSIDE TRACK 



For SI: 1 inch = 25.4 mm. 



For SI: 1 inch - 25.4 



FIGURE R603.3.6 
TRACK SPLICE 



4 SCREWS AT LAPPED TRACK 




FIGURE R603.4 
CORNER FRAMING 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



149 



WALL CONSTRUCTION 



TABLE R603.3.2(2) 
24-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^ " 

33 ksl STEEL 



WIND 


MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foo1t Studs 


Exp. A/B 


Exp. 
C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85mph 




350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 ■ 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 




350S162 


16 


33 


33 


33 


33 


33 


33 


33 


^ 33 


33 


33 


33 


33 


24 


33 


33 


33 


33 ' 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 : 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 1 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 ! 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 : 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 1 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


43 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 i 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 ' 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 i 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 ! 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 1 


43 


43 


43 


43 


54 


54 


54 


L__54_ 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
lksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



150 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R603.3.2(3) 
24-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^'''^ 

50 ksl STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


Vlmu 
SPEED 


8-Fobt Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot - 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



151 



WALL CONSTRUCTION 



TABLE R603.3.2(4) 
28-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^ " 

33 ksi STEEL 



WIND 
SPEED 


MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


'33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


43 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot - 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic Uve load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



152 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



WALL CONSTRUCTION 



TABLE R603.3.2(5) 
28-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^ "■ = 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 




350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 




350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



153 



WALL CONSTRUCTION 



TABLE R603.3.2(6) 
32-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^"^ 

33 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


g-Foot studs 


10-Foot studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


'33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


.33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


:33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


■33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


,33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


■33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


33 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


33 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



154 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



WALL CONSTRUCTION 



TABLE R603.3.2(7) 
32-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY"" 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


WUHU 

SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


• 33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



155 



WALL CONSTRUCTION 



TABLE R603.3.2(8) 
36-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^ "••= 

33 ksi STEEL 



WIND 
SPEED 


MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


! 20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


: 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


' 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


. 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


, 33 


33 


43 


43 


33 


33 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


I 33 


33 


33 


33 


33 


33 


33 


33 


43 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


43 


43 


33 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


; 33 


33 


33 


33 


33 


33 


33 


43 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


. 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


' 33 


33 


33 


43 


33 


33 


33 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


54 


43 


43 


43 


54 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot - 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



156 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



TABLE R603.3.2(9) 
36-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^''^ 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 




100 
mph 


350S162 


16 


33 


33 


33 


33 


L 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



157 



WALL CONSTRUCTION 



TABLE R603.3.2(10) 
40-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^ "■ = 

33 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


33 


33 


43 


43 


33 


33 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


: 33 


33 


43 


43 


33 


33 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


.. 33 


33 


43 


43 


33 


33 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


54 


33 


33 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


, 33 


33 


33 


43 


33 


33 


33 


43 


— 


100 
mph 


350S162 


16 


33 


33 


33 


43 


' 33 


33 


33 


43 


33 


33 


33 


43 


24 


33 


33 


43 


54 


• 43 


43 


43 


54 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


! 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


43 


' 33 


33 


33 


43 


33 


33 


43 


43 


24 


33 


43 


43 


54 


33 


43 


43 


54 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


' 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


i 33 


33 


33 


43 


33 


33 


33 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



158 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



WALL CONSTRUCTION 



TABLE R603.3.2(11) 
40-FOOT-WIDE BUILDING SUPPORTING ROOF AND CEILING ONLY^ "■"= 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(Inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 J 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


^33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 . 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


43 


43 


43^ 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


33 


43 


43 


33 


33 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil - 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot - 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



159 



WALL CONSTRUCTION 



TABLE R603.3.2(12) 
24-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^" 

33 ksi STEEL 



WIND 
SPEED 


MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


^ 33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


:33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


:33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


'33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


.43 


43 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


:33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


.33 


33 


33 


33 


33 


33 


43 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


:33 


33 


33 


33 


43 


43 


43 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 icPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the \«ill studs. 



160 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



TABLER603.3.2(13) 
24-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^- "■"= 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



161 



WALL CONSTRUCTION 



TABLER603.3.2(14) 
28-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^' "•= 

33 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


:33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


'43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


43 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


43 


43 


43 


43 


43 


24 


43 


43 


43 


43 


43 


43 


54 


54 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour - 0.447 m/s, 1 pound per square foot - 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



162 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



TABLE R603.3.2(15) 
28-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^- "^ 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33_^ 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


33 


43 


43 


43 


43 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil - 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



163 



WALL CONSTRUCTION 



TABLE R603.3.2(16) 
32-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^ "^ 

33 ksi STEEL 



WIND 
SPEED 


MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


,33 


33 


33 


33 


33 


33 


33 


43 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


43 


43 


24 


43 


43 


43 


54 


43 


43 


43 


54 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


43 


33 


33 


43 


43 


43 


43 


43 


43 


24 


43 


43 


43 


54 


43 


54 


54 


54 


54 


54 


54 


68 


550S162 


16 


33 


33 


33 


33 


,33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


43 


43 


43 


43 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. ; 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



164 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



WALL CONSTRUCTION 



TABLE R603.3.2(17) 
32-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^- "■'^ 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(Inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


33 


33 


33 


43 


33 


33 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


33 


33 


33 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


33 


33 


33 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 ^ 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


— 


110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



165 



WALL CONSTRUCTION 



TABLE R603.3.2(18) 
36-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^- "•= 

33 ksi STEEL 



WIND 
SPEED 


MEMBER 
SIZE 


STUD 
SPACING 
(Inches) 


MINIMUM STUD THICKNESS (mils) 


8-Foot Studs 


9-Foot Studs 1 0-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


54 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


. 33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


I43__ 


43 


43 


33 


33 


33 


43 


33 


33 


33 


43 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


: 33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


l^3_ 


43 


54 


' 43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


, 33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


|43_ 


43 


43 


33 


33 


33 


43 


33 


33 


43 


43 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


. 33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


54 


43 


43 


43 


54 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


■ 33 


33 


33 


43 


33 


33 


43 


43 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


43 


I 33 


33 


33 


33 


33 


33 


43 


43 


24 


43 


43 


43 


54 


43 


43 


43 


54 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


: 33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


:33 


33 


33 


43 


33 


33 


43 


43 


— 


100 
mph 


350S162 


16 


33 


33 


33 


43 


33 


33 


43 


43 


43 


43 


43 


43 


24 


43 


43 


43 


54 


'43 


43 


54 


54 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


! 33 


33 


33 


43 


43 


43 


43 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


43 


: 33 


33 


43 


43 


43 


43 


43 


43 


24 


43 


43 


43 


54 


43 


54 


54 


54 


54 


54 


54 


68 


550S162 


16 


33 


33 


33 


33 


■ 33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


: 33 


33 


33 


43 


43 


43 


43 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the vail studs. 



166 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



TABLE R603.3.2(19) 
36-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^- 

50 ksl STEEL 



b,c 







MEMBER 
SIZE 


STUD 
SPACING 
(Inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


33 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


33 


33 


43 


43 


43 


43 


43 


'43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


43 


33 


43 


33 


33 


33 


33 


33 


33 


33 


33 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


33 


33 


43 


43 


43 


43 


43 


43 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


33 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


33 


33 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


33 


— 


100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


43 


43 


43 


43 


43 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


43 


33 


33 


33 


33 


33 


33 


33 


43 




110 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


43 


24 


43 


43 


43 


54 


43 


43 


43 


43 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s 1 pound per square foot = 0.0479 kPa, 
lksi= 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



167 



WALL CONSTRUCTION 



TABLE R603.3.2(20) 
40-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING^ "> 

33 ksi STEEL 



WIND 
SPEED 


MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp.C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


43 


' 33 


33 


33 


43 


33 


33 


33 


43 


24 


43 


54 


54 


54 


,43 


43 


43 


54 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


. 33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


:43 


43 


43 


43 


33 


43 


43 


43 


90 
mph 


— 


350S162 


16 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


33 


43 


24 


43 


54 


54 


54 


43 


43 


43 


54 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


43 


43 


43 


43 


33 


43 


43 


43 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


43 


33 


33 


33 


43 


33 


33 


43 


43 


24 


43 


54 


54 


54 


43 


43 


43 


54 


43 


43 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


43 


43 


43 


43 


33 


43 


43 


43 


no 

mph 


90 
mph 


350S162 


16 


33 


33 


33 


43 


33 


33 


33 


43 


33 


43 


43^ 


43 


24 


43 


54 


54 


54 


43 


43 


43 


54 


43 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


43 


43 


43 


43 


33 


43 


r 43 


43 


— 


100 
mph 


350S162 


16 


33 


33 


33 


43 


33 


33 


43 


43 


33 


43 


43 


43 


24 


43 


54 


54 


54 


54 


54 


54 


54 


43 


54 


54 


68 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


43 


43 


43 


43 


33 


43 


43 


43 


— 


110 
mph 


350S162 


16 


33 


33 


43 


43 


43 


43 


43 


43 


33 


43 


43 


43 


24 


54 


54 


54 


54 


54 


54 


54 


54 


54 


68 


68 


68 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


43 


,43 


43 


43 


43 


33 


43 


43 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour - 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



168 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



TABLE R603.3.2(21) 
40-FOOT-WIDE BUILDING SUPPORTING ONE FLOOR, ROOF AND CEILING" " 

50 ksi STEEL 







MEMBER 
SIZE 


STUD 
SPACING 
(inches) 


MINIMUM STUD THICKNESS (mils) 


SPEED 


8-Foot Studs 


9-Foot Studs 


10-Foot Studs 


Exp. 
A/B 


Exp. C 


Ground Snow Load (psf) 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


85 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


54 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


33 


33 


33 


33 


43 


90 
mph 


— 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


54 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


33 


33 


33 


33 


43 


100 
mph 


85 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


43 


43 


43 


54 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


33 


33 


33 


33 


43 


110 
mph 


90 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


54 


43 


43 


43 


43 


43 


43 


43 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


33 


33 


33 


33 


43 




100 
mph 


350S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


43 


24 


43 


43 


43 


54 


43 


43 


43 


43 


43 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


33 


33 


33 


33 


33 


43 


— 


110 
mph 


350S162 


16 


33 


33 


33 


43 


33 


33 


33 


43 


33 


43 


43 


43 


24 


43 


43 


43 


54 


43 


43 


43 


54 


54 


54 


54 


54 


550S162 


16 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


33 


24 


33 


33 


43 


43 


33 


33 


43 


43 


33 


33 


43 


43 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa, 
1 ksi = 1000 psi = 6.895 MPa. 

a. Deflection criterion: L/240. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic live load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the wall studs. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



169 



WALL CONSTRUCTION 



TABLE R603.6(1) 

BOX-BEAM HEADER SPANS 

Headers supporting roof and ceiling only (33 ksi steel)^- "' '^ 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(20 psf) 


GROUND SNOW LOAD 
(30 psf) 


Building width*^ 


Building width'^ 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


36' 


40' 


2-350S 162-33 


3'- 10" 


3'-5" 


3'-0" 


2'-6" 


2'-2" 


3'-3" 


2'-9" 


2'-4" 


— 


— 


2-350S 162-43 


5'-l" 


4'- 8" 


4'-4" 


4'-0" 


3'-7" 


4'-6" 


4'-2" 


3'-8" 


3'-4" 


2'- 11" 


2-350S 162-54 


5'-9" 


5'-4" 


5'-0" 


4'-9" 


4'-5" 


5'-3" 


4'- 10" 


4'-6" 


4'-2" 


3'- 10" 


2-350S 162-68 


6'-7" 


6'-l" 


5'-9" 


5'-5" 


5'-i" 


6'-0" 


5'-6" 


5'-2" 


4'- 10" 


4'-7" 


2-350S 162-97 


8'-0" 


7'-5" 


7'-0" 


6'-6" 


6'-3" 


7'-3" 


6'-9" 


6'-4" 


6'-0" 


5'-7" 


2-550S 162-33 


5'-8" 


5'-0" 


4'-5" 


3'- 11" 


3'-4" 


4'-9" 


4'-l" 


3'-6" 


2'- 11" 


— 


2-550S 162-43 


7'-2" 


6'-8" 


6'-3" 


5'-8" 


5'-2" 


6'-6" 


5'-ll" 


5'-3" 


4'-9" 


4'-3" 


2-550S 162-54 


8'-2" 


I'-l" 


7'-2" 


6'-9" 


6'-5" 


7'-5" 


6'-ll" 


6'-6" 


6'-0" 


5'-6" 


2-550S162-68 


9'-3" 


8'-7" 


8'-0" 


7'-8" 


7'-3" 


8'-5" 


7'-10" 


7'-4" 


7'-0" 


6'-7" 


2-550S 162-97 


ll'-2" 


10'-5" 


9'- 10" 


9'-3" 


8'- 11" 


10'-2" 


9'-6" 


9'-l" 


8'-5" 


8'-0" 


2-800S162-33 


6'-9" 


5'- 11" 


5'-2" 


4'-6" 


3'- lb" 


5'-6" 


4'-6" 


4'-0" 


— 


— 


2-800S 162-43 


9'-0" 


8'-5" 


7'-8" 


7'-0" 


6'-4" 


8'-l" 


7'-3" 


6'-6" 


5'-9" 


5'-2" 


2-800S 162-54 


10'-9" 


lO'-O" 


9'-5" 


8'- 11" 


8'-4" 


9'-9" 


9'-l" 


8'-6" 


7'-9" 


7'-l" 


2- 800S 162-68 


12'-2" 


11 '-4" 


10'-8" 


10'-2" 


9'-7" 


ll'-l" 


10'-4" 


9'-9" 


9'-3" 


8'-9" 


2-800S 162-97 


14'-9" 


13'-9" 


13'-0" 


12'-3" 


11 '-7" 


13'-5" 


12'-6" 


ll'-lO" 


ll'-2" 


10'-7" 


2- lOOOS 162-43 


lO'-O" 


9'-2" 


8'-4" 


7'-6" 


6'-9" 


8'-9" 


7'- 10" 


7'-0" 


6'-2" 


5'-5" 


2-1000S162-54 


12'-0" 


11 '-2" 


10'-6" 


9'- 11" 


9'-2" 


lO'-ll" 


10'-2" 


9'-3" 


8'-6" 


7'-9" 


2- lOOOS 162-68 


14'-5" 


13'-6" 


12'-8" 


12'-0" 


11 '-5" 


13'-2" 


12'-3" 


11 '-6" 


11 '-0" 


10'-4" 


2-1000S162-97 


17'-5" 


16'-4" 


15'-4" 


14'-6" 


13'-11" 


16'-0" 


14'- 11" 


14'-0" 


13'-3" 


12'-7" 


2- 1200S 162-43 


lO'-lO" 


9'-9" 


8'-9" 


7'- 11" 


7'-l" 


9'-3" 


8'-2" 


7'-2" 


6'-4" 


5'-6" 


2-1200S 162-54 


13'-0" 


12'-2" 


ll'-6" 


10'-7" 


9'-^" 


U'-U" 


U'-O" 


lO'-O" 


9'-0" 


8'-2" 


2- 1200S 162-68 


15'-5" 


14'-5" 


13'-6" 


12'-11" 


12'-3" 


14'-0" 


13'-2" 


12'-4" 


ll'-9" 


10'- 11" 


2- 1200S 162-97 


20'- 1" 


18'-9" 


17'-9" 


16'-9" 


16'-b" 


18'-4" 


17'-2" 


16'-2" 


15'-3" 


14'-7" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. ' 

b. Design load assumptions: 

Roof/Ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the header 



170 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



TABLE R603.6(2) 

BOX-BEAM HEADER SPANS 

Headers supporting roof and ceiling only (33 ksi steel)^' "' '^ 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(50 psf) 


GROUND SNOW LOAD 
(70 psf) 


Building width'^ 


Building width'^ 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


38' 


40' 


2-350S 162-33 











— 





__ 














2-350S 162-43 


3'-2" 


2'-7" 


2'-2" 


— 


— 


2'-0" 







— 


— 


2-350S 162-54 


4'-l" 


3'-6" 


3'-l" 


2'-8" 


2'-3" 


3'-0" 


2'-6" 










2-350S162-68 


4'-9" 


4'-5" 


4'-0" 


3'-7" 


3'-3" 


4'-0" 


3'-4" 


3'-0" 


2'-6" 


2'-l" 


2-350S 162-97 


5'-10" 


5'-5" 


5'-l" 


4'-9" 


4'-6" 


5'-0" 


4'-7" 


4'-4" 


4'-0" 


3'-9" 


2-550S 162-33 


2'-9" 


— 


— 


— 


— 

















2-550S 162-43 


4'-7" 


3'- 11" 


3'-3" 


— 





3'-2" 














2-550S162-54 


5'- 10" 


5'-2" 


4'-6" 


4'-0" 


3'-6" 


4'-5" 


3'-9" 


3'-l" 








2-550S162-68 


6'- 10" 


6'-4" 


5'-9" 


5'-3" 


4'-9" 


5'-7" 


5'-0" 


4'-4" 


3'-9" 


3'-3" 


2-550S 162-97 


8'-4" 


7'-9" 


7'-3" 


6'- 10" 


6'-6" 


7'-2" 


6'-8" 


6'-3" 


5'-ll" 


5'-7" 


2-800S 162-33 





— 





— 




















2-800S 162-43 


5'-7" 


4'-9" 


3'- 11" 


— 




















2-800S 162-54 


7'-7" , 


6'-8" 


5'- 11" 


5'-2" 


4'-6" 


5'-9" 


4'- 10" 











2-800S 162-68 


9'-l" 


8'-4" 


7'-6" 


6'-10" 


6'-3" 


7'-4" 


6'-6" 


5'-9" 


5'-0" 


4'-4" 


2-800S 162-97 


ll'-O" 


10'-4" 


9'-8" 


9'-2" 


8'-9" 


9'-6" 


8'- 11" 


8'-4" 


7'- 11" 


7'-6" 


2-1000S162-43 


6'-0" 


4'- 11" 





— 




















2-1000S162-54 


8'-4" 


7'-4" 


6'-4" 


5'-7" 


4'-9" 


6'-3" 


5'-2" 











2- lOOOS 162-68 


10'-9" 


9'-9" 


8'- 10" 


8'-0" 


7'-3" 


8'-7" 


7-1" 


6'-7" 


5'-9" 


5'-0" 


2-1000S162-97 


13'-1" 


12'-3" 


ir-6" 


lO'-ll" 


10'-4" 


ir-4" 


10'-7" 


lO'-O" 


9'-5" 


8'-ll" 


2- 1200S 162-43 


6'-l" 


— 


— 


— 














— 


— 


2- 1200S 162-54 


8'-9" 


7'-8" 


6'-7" 


5'-9" 





6'-6" 








— 


— 


2- 1200S 162-68 


ll'-6" 


10'-4" 


9'-4" 


8'-4" 


I'-l" 


9'-l" 


8'-0" 


6'- 11" 


6'-0" 





2- 1200S 162-97 


15'-1" 


14'-1" 


13'-3" 


12'-7" 


12'-0" 


13'-1" 


12'-3" 


11 '-6" 


ll'-O" 


10'-2" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for Uve loads, L/240 for total loads. 

b. Design load assumptions: 

Roof/Ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the header 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



171 



WALL CONSTRUCTION 



TABLE R603.6(3) 
BOX-BEAM HEADER SPANS 
Headers supporting one floor, roof and ceiling (33 ksi 



steel)^ 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(20 psf) 


GROUND SNOW LOAD 
(30 psf) 


Building width'^ 


Building width'^ 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


36' 


40' 


2-350S 162-33 





_ 








, 














— 


2-350S 162-43 


2'-6" 











: 


2'-5" 














2-350S 162-54 


3'-6" 


3'-0" 


2'-6" 


— 


: 


3'-4" 


2'- 10" 


2'-4" 


— 


— 


2-350S 162-68 


4'-4" 


3'- 11" 


3'-5" 


3'-0" 


2'-7" 


4'-3" 


3'-9" 


3'-3" 


2'- 10" 


2'-6" 


2-350S 162-97 


5'-4" 


5'-0" 


4'-7" 


4'-4" 


4'-l" 


5'-4" 


4'- 11" 


4'-6" 


4'-3" 


4'-0" 


2-550S162-33 





___ 








, 

















2-550S 162-43 


3'-9" 


3'-0" 


— 


— 


— . 


3'-7" 


2'-ll" 


— 


— 


— 


2-550S 162-54 


5'-0" 


4'-4" 


3'-9" 


3'-2" 





4'-10" 


4'-2" 


3'-6" 


3'-0" 





2-550S162-68 


6'-3" 


5'-6" 


5'-0" 


4'-5" 


4'-0" 


6'-l" 


5'-5" 


4'-9" 


4'-3" 


3'-9" 


2-550S 162-97 


7'-8" 


7'-2" 


6'-8" 


6'-4" 


6'-0" 


7'-6" 


7'-0" 


6'-6" 


6'-2" 


5'- 10" 


2-800S 162-33 











— 


— . 


— 








— 


— 


2-800S 162-43 


4'-6" 











; 


4'-4" 








_ 





2-800S162-54 


6'-6" 


5'-7" 


4'-10" 


4'-l" 


. 


6'-4" 


5'-5" 


4'-7" 








2-800S 162-68 


8'-2" 


7'-3" 


6'-6" 


5'- 10" 


5'-2" 


8'-0" 


7'-0" 


6'-4" 


5'-6" 


5'-0" 


2-800S 162-97 


lO'-l" 


9'-6" 


8'- 11" 


8'-6" 


8'-0" 


lO'-O" 


9'-4" 


8'-9" 


8'-3" 


7'- 11" 


2-lOOOS 162-43 


4'-9" 


— 


— 


— 


— . 


— 


— 


— 


— 


— 


2-1000S162-54 


7'-l" 


6'-0" 


5'-2" 





- 


6'-10" 


5'- 10" 


4'- 11" 


— 


— 


2-1000S162-68 


9'-7" 


8'-6" 


I'-l" 


6'-9" 


6'-0" 


9'-4" 


8'-4" 


7'-4" 


6'-6" 


5'-9" 


2-1000S162-97 


12'-0" 


11 '-3" 


10'-7" 


lO'-O" 


9'-6" 


ll'-ll" 


11'- 1" 


10'-5" 


9'-ll" 


9'-5" 


2- 1200S 162-43 














— - 


— 











— 


2-1200S162-54 


7'-6" 


6'-4" 





— 


: 


7'-2" 


6'-0" 





— 


— 


2- 1200S 162-68 


10'- 1" 


9'-0" 


8'-0" 


7'-0" 


6'-2" 


9'- 11" 


8'-9" 


7'-9" 


6'-9" 


6'-0" 


2-1200S162-97 


14'-0" 


13'-0" 


12'-3" 


ll'-7" 


11 '-P" 


13'-9" 


12'-10" 


12'-0" 


11 '-6" 


10'- 11" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. 

b. Design load assumptions: 

Roof/Ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the header 



172 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



TABLE R603.6(4) 

BOX-BEAM HEADER SPANS 

Headers supporting one floor, roof and ceiling (33 ksi steel)^'''''^ 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(50 psf) 


GROUND SNOW LOAD 
(70 psf) 


Building width<= 


Building wldth*^ 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


36' 


40' 


2-350S162-33 





— 


_ 


— 


— 


— 


— 


— 


— 


— 


2-350S 162-43 


__ 








— 



















2-350S 162-54 


2'-6" 


2'-l" 


— 


— 


— 


— 


— 


— 


— 


— 


2-350S 162-68 


3'-6" 


3'-0" 


2'-6" 


2'-2" 





2'-9" 


2'-2" 





— 





2-350S 162-97 


4'-9" 


4'-5" 


4'-l" 


3'- 10" 


3'-7" 


4'-2" 


3'- 11" 


3'-7" 


3'-4" 


2'- 11" 


2-550S162-33 
































2-550S162-43 
































2-550S162-54 


3'- 11" 


3'-4" 





— 





2'-10" 














2-550S 162-68 


5'-2" 


4'-6" 


3'-ll" 


3'-4" 


2'- 10" 


4'-l" 


3'-5" 


2'-9" 


— 


— 


2-550S 162-97 


6'- 10" 


6'-4" 


6'-0" 


5'-7" 


5'-4" 


6'-l" 


5'-7" 


5'-4" 


4'-9" 


4'-4" 


2-800S 162-33 











— 




















2-800S 162-43 











— 




















2-800S 162-54 


5'-l" 


4'-2" 





— 


— 


— 


— 





— 





2-800S 162-68 


6'-9" 


6'-l" 


5'-2" 


4'-5" 





5'-5" 


4'-6" 











2-800S 162-97 


9'-l" 


8'-6" 


8'-0" 


7'-6" 


r-1" 


8'-2" 


7'-7" 


7'-0" 


6'-5" 


5'- 10" 


2-lOOOS 162-43 


— 


— 


— 


— 


— 


— 


— 




— 


— 


2-1000S162-54 


5'-6" 








— 





— 


— 





— 





2-1000S162-68 


7'- 10" 


6'- 11" 


6'-0" 


5'-2" 





6'-4" 


5'-4" 











2- lOOOS 162-97 


10'- 10" 


lO'-l" 


9'-6" 


9'-0" 


8'-4" 


9'-9" 


9'-2" 


8'-4" 


I'-T 


7'-0" 


2- 1200S 162-43 











— _ 





— 


— 





— 





2- 1200S 162-54 


5'-7" 


— 


— 


— 


— 


— 


— 


— 


— 


— 


2- 1200S 162-68 


8'-4" 


7'-2" 


6'-2" 


— 





6'-6" 














2- 1200S 162-97 


12'-6" 


ll'-8" 


11 '-0" 


10'-4" 


9'-6" 


ll'-3" 


10'-6" 


9'-6" 


8'-8" 


8'-0" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. 

b. Design load assumptions: 

Roof/Ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the header. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



173 



WALL CONSTRUCTION 



TABLE R603.6(5) 

BACK-TO-BACK HEADER SPANS 

Headers supporting roof and ceiling only (33 ksi steel)^' "' *= 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(20 psf) 


GROUND SNOW LOAD 
(30 psf) 


Building width'' 


Building width'' 


24' 


28' 


32' 


36' 


40^ 


24' 


28' 


32' 


36' 


40' 


2-350S162-33 


3'-7" 


3'-l" 


2'-8" 


2'-4" 


— '. 


2'- 11" 


2'-6" 


— 





— 


2-350S 162-43 


5'-0" 


4'-8" 


4'-4" 


3'- 10" 


3'-7" 


4'-6" 


4'-0" 


3'-8" 


3'-4" 


2'- 11" 


2-350S 162-54 


5'-9" 


5'-5" 


5'-0" 


4'-9" 


4'-6" 


5'-3" 


4'- 10" 


4'-6" 


4'-4" 


3'- 11" 


2-350S 162-68 


6'-7" 


6'-2" 


5'-9" 


5'-5" 


5'-2" 


5'- 11" 


5'-7" 


5'-2" 


4'-10" 


4'-7" 


2-350S 162-97 


7'- 11" 


7'-6" 


6'- 11" 


6'-7" 


6'-6" 


7'-4" 


6'-9" 


6'-4" 


5'- 11" 


5'-8" 


2-550S 162-33 


5'-5" 


4'-9" 


4'-4" 


3'-9" 


3'-5" 


4'-7" 


3'- 11" 


3'-5" 


2'- 11" 





2-550S 162-43 


7'-3" 


6'-8" 


6'-2" 


5'-8" 


5'-4" 


6'-6" 


5'- 10" 


5'-5" 


4'- 10" 


4'-6" 


2-550S162-54 


8'-2" 


7'-8" 


7'-2" 


6'-9" 


6'-5" 


7'-5" 


6'- 10" 


6'-6" 


6'-l" 


5'-9" 


2-550S 162-68 


9'-4" 


8'-8" 


8'-7" 


7'-8" 


7'-4" 


8'-6" 


7'- 10" 


7'-5" 


6'-ll" 


6'-7" 


2-550S 162-97 


11 '-3" 


10'-6" 


9'- 11" 


9'-4" 


8'- 10" 


10'-3" 


9'-6" 


8'- 11" 


8'-6" 


8'-0" 


2-800S 162-33 


6'-9" 


5'- 11" 


5'-5" 


4'-9" 


4'-4" 


6'-9" 


5'-0" 


4'-5" 


3'-9" 


— 


2-800S 162-43 


9'-l" 


8'-6" 


7'-9" 


7'-3" 


6'-8" 


8'-3" 


7'-6" 


6'-9" 


6'-3" 


5'-8" 


2-800S 162-54 


10'-9" 


10'- 1" 


9'-6" 


8'- 11" 


8'-6" 


9'-9" 


9'-2" 


8'-7" 


8'-2" 


7'-8" 


2-800S 162-68 


12'-3" 


ll'-5" 


10'-9" 


10'-2" 


9'-8"^ 


ll'-2" 


10'-5" 


9'-9" 


9'-4" 


8'-9" 


2-800S 162-97 


14'-9" 


13'-9" 


13'-0" 


12'-4" 


ll'-8" 


13'-6" 


12'-7" 


U'-IO" 


ll'-2" 


10'-8" 


2-1000S162-43 


10'- 1" 


9'-5" 


8'-8" 


8'-0" 


7'-6" 


9'-l" 


8'-4" 


7'-7" 


6'- 11" 


6'-5" 


2- lOOOS 162-54 


12'-0" 


11 '-5" 


10'-7" 


lO'-O" 


9'-6" 


11 '-0" 


10'-3" 


9'-7" 


9'-l" 


8'-6" 


2-1000S162-68 


14'-6" 


13'-6" 


12'-8" 


12'-0" 


11 '-6" 


13'-2" 


12'-4" 


11 '-7" 


10'- 11" 


10'-6" 


2-1000S162-97 


17'-6" 


16'-5" 


15'-5" 


14'-7" 


13'- 10" 


16'-0" 


14'- 10" 


14'-0" 


13'-4" 


12'-8" 


2-1200S162-43 


U'-O" 


10'-4" 


9'-6" 


8'-9" 


8'-2" 


lO'-O" 


9'-l" 


8'-4" 


7'-7" 


7'-0" 


2- 1200S 162-54 


13'-1" 


12'-3" 


11 '-6" 


10'- 10" 


10'-5" 


11'- 10" 


ll'-l" 


10'-6" 


9'- 10" 


9'-4" 


2-1200S162-68 


15'-6" 


14'-6" 


13'-7" 


12'- 10" 


12'-3" 


14'- 1" 


13'-2" 


12'-5" 


ll'-9" 


ll'-2" 


2- 1200S 162-97 


20'-2" 


18'-9" 


17'-9" 


16'-9" 


16'-b" 


18'-4" 


17'-2" 


16'-2" 


15'-5" 


14'-7" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot - 0.0479kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. 

b. Design load assumptions: 

Roof/Ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the header. 



174 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



WALL CONSTRUCTION 



TABLE R603.6(6) 

BACK-TO-BACK HEADER SPANS 

Headers supporting roof and ceiling only (33 ksi steel)^'''''^ 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(50 psf) 


GROUND SNOW LOAD 
(70 psf) 


Building width<= 


Building width'' 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


36' 


40' 


2-350S 162-33 
































2-350S 162-43 


3'-2" 


2'-8" 


2'-4" 


— 


— 


2'-3" 


— 





— 





2-350S 162-54 


4'-3" 


3'-8" 


3'-5" 


2'- 11" 


2'-8" 


3'-4" 


2'-9" 


2'-5" 


2'-0" 


l'-7" 


2-350S162-68 


4'-9" 


4'-6" 


4'-2" 


3'- 10" 


3'-7" 


4'-l" 


3'-9" 


3'-5" 


3'-l" 


2'-8" 


2-350S 162-97 


5'- 10" 


5'-6" 


5'-2" 


4'- 10" 


4'-7" 


5'-0" 


4'-8" 


4'-5" 


4'-2" 


3'- 10" 


2-550S 162-33 


2'-9" 


— 











— 














2-550S 162-43 


4'-9" 


4'-2" 


3'-8" 


3'-3" 


2'-8" 


3'-6" 


2'- 10" 











2-550S 162-54 


6'-0" 


5'-6" 


4'- 11" 


4'-6" 


4'-l" 


4'- 10" 


4'-4" 


3'- 10" 


3'-6" 


2'- 11" 


2-550S162-68 


6'- 10" 


6'-5" 


5'-ll" 


5'-8" 


5'-4" 


5'-ll" 


5'-6" 


4'- 11" 


4'-7" 


4'-3" 


2-550S 162-97 


8'-5" 


7'-7" 


4'-4" 


6'- 10" 


6'-7" 


7'-3" 


6'-8" 


6'-4" 


5'- 11" 


5'-8" 


2-800S 162-33 


3'-8" 




























2-800S 162-43 


6'-l" 


5'-5" 


4'-9" 


4'-2" 


3'-8" 


4'-7" 


3'-9" 










2-800S 162-54 


8'-0" 


7'-4" 


6'-8" 


6'-l" 


5'-7" 


6'-6" 


5'-8" 


5'-3" 


4'-8" 


4'-3" 


2-800S 162-68 


9'-l" 


8'-6" 


7'- 11" 


7'-7" 


r-1" 


7'- 10" 


7'-5" 


6'-9" 


6'-3" 


5'-9" 


2-800S 162-97 


ll'-l" 


10'-4" 


9'-8" 


9'-2" 


8'-9" 


9'-8" 


8'- 11" 


8'-5" 


7'- 11" 


7'-7" 


2-1000S162-43 


6'-9" 


6'-0" 


5'-5" 


4'-9" 


4'-2" 


5'-2" 


4'-5" 











2- lOOOS 162-54 


8'- 11" 


8'-2" 


7-6" 


6'- 10" 


6'-6" 


7'-4" 


6'-7" 


5'- 10" 


5'-4" 


4'-9" 


2-1000S162-68 


10'-9" 


lO'-l" 


9'-6" 


8'- 11" 


8'-6" 


9'-5" 


8'-9" 


8'-l" 


7'-6" 


6'- 10" 


2-1000S162-97 


13'-1" 


12'-4" 


ll'-6" 


lO'-lO" 


10'-5" 


ll'-5" 


10'-7" 


9'-ll" 


9'-6" 


8'- 11" 


2-1200S162-43 


7'-6" 


6'-7" 


5'- 10" 


5'-2" 


4'-7" 


5'-8" 


4'- 10" 











2- 1200S 162-54 


9'-9" 


8'- 10" 


8'-l" 


7'-6" 


6'- 10" 


7'- 11" 


7'-2" 


6'-6" 


5'-9" 


5'-3" 


2-1200S162-68 


ir-7" 


10'-9" 


10'-2" 


9'-7" 


9'-l" 


10'-2" 


9'-6" 


8'-7" 


7'- 11" 


7'-5" 


2-1200S162-97 


15'-1" 


14'- 1" 


13'-4" 


12'-7" 


12'-0" 


13'-2" 


12'-4" 


11 '-7" 


lO'-ll" 


10'-6" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. 

b. Design load assumptions: 

Roof/Ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by theheader. 



2006 INTERNATIONAL RESIDENTIAL CODE" 



175 



WALL CONSTRUCTION 



TABLE R603.6(7) 
BACK-TO-BACK HEADER SPANS 
Headers supporting one floor, roof and ceiling (33 ksi 



steel)' 



,3, b, c 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(20 psf) 


GROUND SNOW LOAD 
(30 psf) 


Building width'^ 


Building wldth<= 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


36' 


40' 


2-350S162-33 

















— 


— 





— 


— 


2-350S 162-43 


2'-7" 


2'-l" 


— 


— 


— 


2'-6" 


— 


— 


— 


— 


2-350S 162-54 


3'-8" 


3'-3" 


2'-9" 


2'-6" 


2'-l" 


3'-7" 


3'-l" 


2'-8" 


2'-5" 


I'-ll" 


2-350S 162-68 


4'-5" 


4'-0" 


3'-9" 


3'-6" 


3'-l" 


4'-4" 


3'- 11" 


3'-8" 


3'-5" 


3'-0" 


2-350S 162-97 


5'-5" 


4'- 11" 


4'-8" 


4'-5" 


4'-l" 


5'-4" 


4'- 10" 


4'-7" 


4'-4" 


4'-0" 


2-550S 162-33 





— 


— 


— 


— - 


— 


— 


— 


— 


— 


2-550S 162-43 


4'-l" 


3'-6" 


2'- 10" 


2'-5" 


— , 


3'- 11" 


3'-5" 


2'-9" 


— 


— 


2-550S 162-54 


5'-5" 


4'-9" 


4'-4" 


3'- 10" 


3'-6" 


5'-3" 


4'-8" 


4'-3" 


3'-9" 


3'-5" 


2-550S 162-68 


6'-6" 


5'- 10" 


5'-6" 


5'-l" 


4'-8" 


6'-2" 


5'-9" 


5'-5" 


4'- 11" 


4'-7" 


2-550S 162-97 


7'-8" 


7'-2" 


6'-8" 


6'-5" 


5'- 11" 


7'-7" 


7'-0" 


6'-7" 


6'-3" 


5'- 10" 


2-800S162-33 











— 


— 


— 


— 


— 


— 


— 


2-800S 162-43 


5'-4" 


4'-7" 


3'- 10" 


3'-4" 





5'-l" 


4'-5" 


3'-9" 


. 





2-800S 162-54 


7'-3" 


6'-6" 


5'-10" 


5'-4" 


4'-9" 


6'- 11" 


6'-4" 


5'-8" 


5'-3" 


4'-8" 


2-800S 162-68 


8'-5" 


7'-9" 


7'-5" 


6'-9" 


6'-5" 


8'-4" 


7'-8" 


7'-3" 


6'-8" 


6'-3" 


2-800S 162-97 


10'-2" 


9'-6" 


8'- 11" 


8'-6" 


8'-l" 


lO'-O" 


9'-5" 


8'-9" 


8'-5" 


7'- 10" 


2- lOOOS 162-43 


5'-9" 


5'-l" 


4'-5" 


3'-9" 


— " 


5'-8" 


4'- 11" 


4'-4" 


— 


— 


2-1000S162-54 


7'- 11" 


7'-3" 


6'-7" 


5'- 11" 


5'-5" 


7'-9" 


7'-l" 


6'-5" 


5'-9" 


5'-4" 


2-1000S162-68 


9'-ll" 


9'-4" 


8'-9" 


8'-l" 


I'-T 


9'- 10" 


9'-2" 


8'-7" 


7'- 11" 


7'-5" 


2-1000S162-97 


12'-1" 


11 '-4" 


10'-8" 


lO'-O" 


9'-7" 


ll'-ll" 


ll'-l" 


10'-6" 


9'- 10" 


9'-6" 


2-1200S162-43 


6'-6" 


5'-8" 


4'- 10" 


4'-2" 





6'-4" 


5'-6" 


4'-8" 








2- 1200S 162-54 


8'-8" 


7'- 10" 


7'-2" 


6'-6" 


5'- 11" 


8'-6" 


7'-8" 


6'- 11" 


6'-5" 


5'-9" 


2- 1200S 162-68 


10'-8" 


9'- 11" 


9'-5" 


8'-8" 


8'-l" 


10'-6" 


9'-9" 


9'-3" 


8'-6" 


7'- 11" 


2- 1200S 162-97 


13'- 11" 


13'-0" 


12'-4" 


11 '-7" 


ii'-i" 


13'-9" 


12'-10" 


12'- 1" 


11 '-6" 


lO'-lO" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot - 0.0479 kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Roof/Ceiling dead load is 12 psf. 
Second floor live load is 30 psf. 
Roof/ceiling load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by th'e header. 



176 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



TABLE R603.6(8) 
BACK-TO-BACK HEADER SPANS 
Headers supporting one floor, roof and ceiling (33 ksi 



steel)^ 



MEMBER 
DESIGNATION 


GROUND SNOW LOAD 
(50 psf) 


GROUND SNOW LOAD 
(70 psf) 


Building width'^ 


Building width*^ 


24' 


28' 


32' 


36' 


40' 


24' 


28' 


32' 


36' 


40' 


2-350S 162-33 





— 


— 


— 


. — . 











— 


— 


2-350S 162-43 








— 


— 


— 














— 


2-350S162-54 


2'- 11" 


2'-6" 


2'-2" 








2'-4" 














2-350S 162-68 


3'- 10" 


3'-6" 


3'-2" 


2'-9" 


2'-6" 


3'-4" 


2'- 10" 


2'-6" 


2'-3" 


I'-IO" 


2-350S 162-97 


4'-9" 


4'-5" 


4'-2" 


3'- 10" 


3'-8" 


4'-3" 


3'- 10" 


3'-8" 


3'-5" 


3'-2" 


2-550S 162-33 








— 


— 


— 














— 


2-550S 162-43 


3'-l" 


2'-5" 


— 


— 


— 













— 


2-550S162-54 


4'-6" 


3'-10" 


3'-6" 


3'-0" 


2'-7" 


3'-8" 


3'-l" 


2'-7" 


2'-l" 


— 


2-550S 162-68 


5'-7" 


5'-l" 


4'-8" 


4'-4" 


3'-ll" 


4'-10" . 


4'-5" 


3'- 10" 


3'-6" 


3'-3" 


2-550S 162-97 


6'- 10" 


6'-5" 


5'- 11" 


5'-8" 


5'-5" 


6'-2" 


5'-8" 


5'-.5" 


3'-l" 


4'-9" 


2-800S162-33 
































2-800S 162-43 


4'-l" 


3'-5" 


— 


— 

















— 


2-800S 162-54 


6'-0" 


5'-5" 


4'-9" 


4'-4" 


3'-9" 


4'- 11" 


4'-5" 


3'-9" 


3'-2" 


— 


2-800S 162-68 


7'-6" 


6'- 10" 


e-5" 


5'- 10" 


5'-5" 


6'-7" 


5'-10" 


5'-5" 


4'-10" 


4'-6" 


2-800S 162-97 


9'-l" 


8'-6" 


8'-0" 


r-T 


7'-4" 


8'-3" 


7'-8" 


7'-3" 


6'-9" 


6'-6" 


2-1000S162-43 


4'-8" 


3'- 10" 


— 


— 














— 


— 


2-1000S162-54 


6'-9" 


6'-0" 


5'-5" 


4'-10" 


4'-4" 


5'-8" 


4'-10" 


4'-4" 


3'-8" 





2-1000S162-68 


8'-10" 


8'-3" 


7'-7" 


6'- 11" 


6'-6" 


7'-9" 


7'-l" 


6'-6" 


5'- 10" 


5'-5" 


2- lOOOS 162-97 


lO'-lO" 


10'-3" 


9'-7" 


9'-l" 


8'-8" 


9'-9" 


9'-3" 


8'-7" 


8'-3" 


7'-9" 


2-1200S162-43 


5'-l" 


4'_42 


— 


— 


— 








— 


— 


— 


2- 1200S 162-54 


r-5" 


6'-6" 


5'-10" 


5'-4" 


4'-9" 


6'-3" 


5'-5" 


4'-8" 


4'-l" 


— 


2-1200S162-68 


9'-7" 


8'-9" 


8'-l" 


7'-6" 


6'- 11" 


8'-8" 


7'-7" 


6'- 11" 


6'-4" 


5'-9" 


2-1200S162-97 


12'-6" 


11 '-8" 


11'- 1" 


10'-6" 


9'- 11" 


11 '-4" 


10'-7" 


lO'-O" 


9'-6" 


9'-0" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 pound per square inch = 6.895 kPa. 

a. Deflection criteria: L/360 for live loads, L/240 for total loads. 

b. Design load assumptions: 

Second floor dead load is 10 psf. 
Roof/Ceiling dead load is 12 psf. 
Second floor live load is 30 psf. 
Roof/ceiling dead load is 12 psf. 
Attic dead load is 10 psf. 

c. Building width is in the direction of horizontal framing members supported by the header. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



177 



WALL CONSTRUCTION 



TABLE R603.6(9) 
TOTAL NUMBER OF JACK AND KING STUDS REQUIRED AT EACH END OF AN OPENING 



SIZE OF OPENING 
(feet-inches) 


24" O.C. STUD SPACING 


16" O.C. STUD SPACING 


No. of jack studs 


No. of king studs 


No. of jack studs 


No. of king studs 


Up to 3'-6" 


1 


1 


1 


1 


> 3'-6" to 5'-0" 


1 


2 


1 


2 


> 5'-0" to 5'-6" 


1 


2 


2 


2 


> 5'-6" to 8'-0" 


1 


2 


2 


2 


> 8'-0" to 10'-6" 


2 


2 . 


2 


3 


> 10'-6" to 12'-0" 


2 


2 : 


3 


3 


>12'-0"tol3'-0" 


2 


3 


3 


3 


>13'-0"tol4'-0" 


2 


3 , 


3 


4 


> 14'-0" to 16'-0" 


2 


3 ' 


3 


4 


>16'-0"tol8'-0" 


3 


3 ■ 


4 


4 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



TABLE R603.6(10) 
HEADER TO KING STUD CONNECTION REQUIREMENTS^ "^^ 



HEADER SPAN 
(feet) 


BASIC WIND SPEED (mph), EXPOSURE 


85 A/B or Seismic Design 
Categories A, B, C, Dq, D., and Dj 


85 Cor less than 110 A/B 


Less than HOC 


<4' 


4-No. 8 screws 


4-No. 8 screws 


6-No. 8 screws 


> 4' to 8' 


4-No. 8 screws 


4-No. 8 screws 


8 -No. 8 screws 


> 8' to 12' 


4-No. 8 screws 


6-No. 8 screws 


10-No. 8 screws 


> 12'to 16' 


4-No. 8 screws 


8-No. 8 screws 


12-No. 8 screws 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound = 4.448 N. 

a. All screw sizes shown are minimum. 

b. For headers located on the first floor of a two-story building, the total number of screws may be reduced by two screws, but the total number of screws shall be no 
less than four. 

c. For roof slopes of 6: 12 or greater, the required number of screws may be reduced 'by half, but the total number of screws shall be no less than four. 

d. Screwscanbereplacedbyanupliftconnectorwhichhasacapacityof the number of screws multiplied by 164 pounds (e.g., 12-No. 8 screws can be replaced by an 
uplift connector whose capacity exceeds 12 X 164 pounds = 1,968 pounds). 



TABLE R603.6(11) 
HEAD TRACK SPAN (33 ksi Steel) 



BASIC WIND 
SPEED (mph) 


ALLOWABLE HEAD TRACK SPAN^' " 
(ft-in) 


Exposure 


Track Designation 


A/B 


c 


350T1 25-33 


350T1 25-43 


350T1 25-54 


550T1 25-33 


550T1 25-43 


550T1 25-54 


85 




5'-0" 


5'-7" 


6'-2" 


5'- 10" 


6'-8" 


7'-0" 


90 




4'-10" 


5'-5" 


6'-0" 


5'-8" 


6'-3" 


6'-10" 


100 


85 


4'-6" 


5'-l" 


5'-8" 


5'-4" 


5'- 11" 


6'-5" 


110 


90 


4'-2" 


4'-9" 


5^-4" 


5'-l" 


5'-7" 


6'-l" 




100 


3'- 11" 


4'-6" 


5'-0" 


4'- 10" 


5'-4" 


5'- 10" 




110 


3'-8" 


4'-2" 


4^-9" 


4'-l" 


5'-l" 


5'-7" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 nrni, 1 mile per hour = 0.447 m/s. 

a. Deflection Limit: L/240 

b. Head track spans are based on components and cladding wind speeds and a 49-inch tributary span. 



178 



2006 INTERNATIONAL RESIDENTIAL CODE® 



WALL CONSTRUCTION 



2 SCREWS AT 24 IN. O.C. 
(ONE PER HEADER FLANGE) 



2SCREWSAT24IN. O.C. 




(SEE ALTERNATE DETAIL) 



CLIP ANGLE ATTACHED WITH SCREWS 
IN EACH LEG OF CLIP ANGLE, 
MINIMUM ANGLE LENGTH = HEADER 
DEPTH MINUS V2 IN. 



JACKSTUD(S) 
KINGSTUD(S) 



STRUCTURAL 
SHEATHING EXTERIOR 



SCREW AT 24 IN. O.C. THROUGH EXTERIOR 
SHEATHING TO EACH JACK AND KING STUD 



2 SCREWS AT 24" O.C 
ONE PER FLANGE 



C-SHAPES 



TRACK 



TRACK 




TRACK 



CRIPPLE STUD 



TRACK OR C-SHAPE 
ATTACH WITH SCREWS 
(MmmUM DEPTH = HEADER 
DEPTH MINUS H INCH) 



KING STUD{S) 



JACKSTUD(S) 



SCREWS TO SHEATHING TO 
EACH JACK AND KING STUD 
AT 12" ON CENTER 



For SI; 1 inch = 25.4 mm. 



ALTERNATE DETAIL 
(BOX BEAM HEADER) 



FIGURE R603.6 
HEADER DETAIL 



STRUCTURAL SHEATHING 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



179 



WALL CONSTRUCTION 



TABLE R603.7 
MINIMUM PERCENTAGE OF FULL HEIGHT STRUCTURAL SHEATHING ON EXTERIOR WALLS"- *"= ''^ 



WALL SUPPORTING 


ROOF 
SLOPE 


WIND SPEED (mph) AND EXPOSURE 


85A/B 


100A/B 


110A/Bor85C 


100 c 


110C 


Roof and ceiling only 


3:12 


8 


9 


12 


16 


20 


6:12 


12 


15 


20 


26 


35 


9:12 


21 


25 


30 


50 


58 


12:12 


30 


35 


40 


66 


75 


One story, roof and ceiling 


3:12 


24 


30 


35 


50 


66 


6:12 


25 


30 


40 


58 


74 


9:12 


35 


40 


55 


74 


91 


12:12 


40 


50 


65 


100 


115 



For SI: 1 mile per hour = 0.447 m/s. 

a. Linear interpolation shall be permitted. 

b. Bracing amount shall not be less than 20 percent of the wall length after all applicable adjustments are made. 

c. Minimum percentages are based on a building aspect ratio of 1 : 1 . Minimum percentages for the shorter walls of a building shall be multiplied by a factor of 1 . 5 and 
2.0 for building aspect ratios of 1.5:1 and 2:1 respectively. 

d. For hip roofed homes with continuous structural sheathing, the amount of bracing shall be permitted to be multiplied by a factor of 0.95 for roof slopes not exceed- 
ing 7:12 and a factor of 0.9 for roof slopes greater than 7:12. 

e. Sheathing percentages are permitted to be reduced in accordance with Section R603.7.2. 



SECTION R604 
WOOD STRUCTURAL PANELS 

R604.1 Identification and grade. Wood structural panels 
shall conform to DOC PS 1 or DOC PS 2. All panels shall be 
identified by a grade mark or certificate of inspection issued by 
an approved agency. 

R604.2 Allowable spans. The maximum allowable spans for 
wood structural panel wall sheathing shall not exceed the val- 
ues set forth in Table R602.3(3). 

R604.3 Installation. Wood structural panel wall sheathing 
shall be attached to framing in accordance with Table 
R602.3(l). Wood structural panels marked Exposure 1 or 
Exterior are considered water-repellent sheathing under the 
code. 



SECTION R605 
PARTICLEBOARD 

R605.1 Identification and grade. Particleboard shall conform 
to ANSI A208.1 and shall be so identified by a grade mark or 
certificate of inspection issued by an approved agency. 
Particleboard shall comply with the grades specified in Table 
R602.3(4). 



SECTION R606 
GENERAL MASONRY CONSTRUCTION 

R606.1 General. Masonry construction shall be designed and 
constructed in accordance with the provisions of this secdon or 
in accordance with the provisions of ACI 530/ASCE 5/TMS 
402. 

R606.1.1 Professional registration not required. When 
the empirical design provisions of ACI 530/ASCE 5/TMS 
402 Chapter 5 or the provisions of this section are used to 
design masonry, project drawings, typical details and speci- 
fications are not required to bear the seal of the architect or 



engineer responsible for design, unless otherwise required 
by the state law of the jurisdiction having authority. 

R606.2 Thickness of masonry. The nominal thickness of 
masonry walls shall conform to the requirements of Sections 
R606.2.1 through R606.2.4. 

R606.2.1 Minimum thickness. The minimum thickness of 
masonry bearing walls more than one story high shall be 8 
inches (203 mm). Solid masonry walls of one-story dwell- 
ings and garages shall not be less than 6 inches (152 mm) in 
thickness when not greater than 9 feet (2743 mm) in height, 
provided that when gable construction is used, an additional 6 
feet (1 829 mm) is permitted to the peak of the gable. Masonry 
walls shall be laterally supported in either the horizontal or 
vertical direction at intervals as required by Section R606.9. 

R606.2.2 Rubble stone masonry wall. The minimum 
thickness of rough, random or coursed rubble stone 
masonry walls shall be 16 inches (406 mm). 

R606.2.3 Change in thickness. Where walls of masonry of 
hollow units or masonry-bonded hollow walls are decreased 
in thickness, a course of solid masonry shall be constructed 
between the wall below and the thinner wall above, or spe- 
cial units or construction shall be used to transmit the loads 
from face shells or wythes above to those below. 

R606.2.4 Parapet walls. Unreinforced solid masonry para- 
pet walls shall not be less than 8 inches (203 mrn) thick and 
their height shall not exceed four times their thickness. 
Unreinforced hollow unit masonry parapet walls shall be 
not less than 8 inches (203 mm) thick, and their height shall 
not exceed three times their thickness. Masonry parapet 
walls in areas subject to wind loads of 30 pounds per square 
foot (1.44 kPa) located in Seismic Design Category Dg, Dj 
\ or D2, or on townhouses in Seismic Design Category C shall 
' be reinforced in accordance with Section R606.12. 

R606.3 Corbeled masonry. Solid masonry units shall be used 
for corbeling. The maximum corbeled projection beyond the 



180 



2006 INTERNATIONAL RESIDENTIAL CODE® 



WALL CONSTRUCTION 



face of the wall shall not be more than one-half of the wall 
thickness or one-half the wythe thickness for hollow walls; the 
maximum projection of one unit shall not exceed one-half the 
height of the unit or one-third the thickness at right angles to the 
wall. When corbeled masonry is used to support floor or 
roof-framing members, the top course of the corbel shall be a 
header course or the top course bed joint shall have ties to the 
vertical wall. The hollow space behind the corbeled masonry 
shall be filled with mortar or grout. 

R606.4 Support conditions. Bearing and support conditions 
shall be in accordance with Sections R606.4.1 and R606.4.2. 

R606.4.1 Bearing on support. Each masonry wythe shall 
be supported by at least two-thirds of the wythe thickness. 

R606.4.2 Support at foundation. Cavity wall or masonry 
veneer construction may be supported on an 8-inch (203 
mm) foundation wall, provided the 8-inch (203 mm) wall is 
corbeled with solid masonry to the width of the wall system 
above. The total horizontal projection of the corbel shall not 
exceed 2 inches (51 mm) with individual corbels projecting 
not more than one-third the thickness of the unit or one-half 
the height of the unit. 

R606.5 Allowable stresses. Allowable compressive stresses in 
masonry shall not exceed the values prescribed in Table 
R606.5. In determining the stresses in masonry, the effects of 
all loads and conditions of loading and the influence of all 
forces affecting the design and strength of the several parts 
shall be taken into account. 

R606.5.1 Combined units. In walls or other structural 
members composed of different kinds or grades of units, 
materials or mortars, the maximum stress shall not exceed 
the allowable stress for the weakest of the combination of 
units, materials and mortars of which the member is com- 
posed. The net thickness of any facing unit that is used to 
resist stress shall not be less than 1.5 inches (38 mm). 

R606.6 Piers. The unsupported height of masonry piers shall 
not exceed ten times their least dimension. When structural 
clay tile or hollow concrete masonry units are used for isolated 
piers to support beams and girders, the cellular spaces shall be 
filled solidly with concrete or Type M or S mortar, except that 
unfilled hollow piers may be used if their unsupported height is 
not more than four times their least dimension. Where hollow 
masonry units are solidly filled with concrete or Type M, S or N 
mortar, the allowable compressive stress shall be permitted to 
be increased as provided in Table R606.5. 

R606.6.1 Pier cap. Hollow piers shall be capped with 4 
inches (102 mm) of solid masonry or concrete or shall have 
cavities of the top course filled with concrete or grout or 
other approved methods. 

R606.7 Chases. Chases and recesses in masonry walls shall 
not be deeper than one-third the wall thickness, and the maxi- 
mum length of a horizontal chase or horizontal projection shall 
not exceed 4 feet (1219 mm), and shall have at least 8 inches 
(203 mm) of masonry in back of the chases and recesses and 
between adjacent chases or recesses and the jambs of openings. 
Chases and recesses in masonry walls shall be designed and 
constructed so as not to reduce the required strength or required 
fire resistance of the wall and in no case shall a chase or recess 



be permitted within the required area of a pier. Masonry 
directly above chases or recesses wider than 12 inches (305 
mm) shall be supported on noncombustible lintels. 

TABLE R606.5 

ALLOWABLE COMPRESSIVE STRESSES FOR 

EMPIRICAL DESIGN OF MASONRY 



CONSTRUCTION; COMPRESSIVE 
STRENGTH OF UNIT, GROSS AREA 


ALLOWABLE COMPRESSIVE 

STRESSES' GROSS 
CROSS-SECTIONAL AREA" 


Type M or S 
mortar 


Type N 
mortar 


Solid masonry of brick and other 
solid units of clay or shale; sand-lime 
or concrete brick: 

8,000 + psi 

4,500 psi 

2,500 psi 

1,500 psi 


350 
225 
160 
115 


300 
200 
140 
100 


Grouted'^ masonry, of clay or shale; 
sand-lime or concrete: 

4,500+ psi 

2,500 psi 

1,500 psi 


225 
160 
115 


200 
140 
100 


SoHd masonry of soUd concrete 
masonry units: 

3,000+ psi 

2,000 psi 

1,200 psi 


225 
160 
115 


200 
140 
100 


Masonry of hollow load-bearing 
units: 

2,000+ psi 

1,500 psi 

1,000 psi 

700 psi 


140 
115 
75 
60 


120 
100 
70 
55 


Hollow walls (cavity or masonry 
bonded'') solid units: 

2,500+ psi 

1,500 psi 

Hollow units 


160 
115 

75 


140 
100 
70 


Stone ashlar masonry: 
Granite 

Limestone or marble 
Sandstone or cast stone 


720 
450 
360 


640 
400 
320 


Rubble stone masonry: 
Coarse, rough or random 


120 


100 



For SI: 1 pound per square inch = 6.895 kPa. 

a. Linear interpolation shall be used for determining allowable stresses for 
masonry units having compressive strengths that are intermediate between 
those given in the table. 

b. Gross cross-sectional area shall be calculated on the actual rather than nomi- 
nal dimensions. 

c. See Section R608. 

d. Where floor and roof loads are carried upon one wythe, the gross cross-sec- 
tional area is that of the wythe under load; if both wythes are loaded, the 
gross cross-sectional area is that of the wall minus the area of the cavity 
between the wythes. Walls bonded with metal ties shall be considered as 
cavity walls unless the collar joints are filled with mortar or grout. 

R606.8 Stack bond. In unreinforced masonry where masonry 
units are laid in stack bond, longitudinal reinforcement consist- 
ing of not less than two continuous wires each with a minimum 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



181 



WALL CONSTRUCTION 



aggregate cross-sectional area of 0.017 square inch (11 mm^) 
shall be provided in horizontal bed joints spaced not more than 
16 inches (406 mm) on center vertically. 

R606.9 Lateral support. Masonry walls shall be laterally sup- 
ported in either the horizontal or the vertical direction. The 
maximum spacing between lateral supports shall not exceed 
the distances in Table R606.9. Lateral support shall be pro- 
vided by cross walls, pilasters, buttresses or structural frame 
members when the limiting distance is taken horizontally, or by 
floors or roofs when the limiting distance is taken vertically. 

TABLE R606.9 
SPACING OF LATERAL SUPPORT FOR MASONRY WALLS 



CONSTRUCTION 


MAXIMUM WALL LENGTH TO THICKNESS 
OR WALL HEIGHT TO THICKNESS^" 


Bearing walls: 

Solid or solid grouted 
All other 


20 
18 


Nonbearing walls: 
Exterior 
Interior 


18 
36 



For SI: 1 foot = 304.8 mm. 

a. Except for cavity walls and cantilevered walls, the thickness of a wall shall 
be its nominal thiciaiess measured perpendicular to the face of the wall. For 
cavity walls, the thickness shall be determined as the sum of the nominal 
thicknesses of the individual wythes. For cantilever walls, except for para- 
pets, the ratio of height to nominal thickness shall not exceed 6 for solid 
masonry, or 4 for hollow masonry. For parapets, see Section R606.2.4. 

b. An additional unsupported height of 6 feet is permitted for gable end walls. 

R606.9.1 Horizontal lateral support. Lateral support in 
the horizontal direction provided by intersecting masonry 
walls shall be provided by one of the methods in Section 
R606.9.1.1 or Section R606.9. 1.2. 

R606.9.1.1 Bonding pattern. Fifty percent of the units at 
the intersection shall be laid in an overlapping masonry 
bonding pattern, with alternate units having a bearing of 
not less than 3 inches (76 mm) on the unit below. 

R606.9.1.2 Metal reinforcement. Interior nonload- bear- 
ing walls shall be anchored at their intersections, at vertical 
intervals of not more than 16 inches (406 mm) with joint 
reinforcement of at least 9 gage [0.148 in. (4mm)], or V4 
inch (6 mm) galvanized mesh hardware cloth. Litersecting 
masonry walls, other than interior nonloadbearing walls, 
shall be anchored at vertical intervals of not more than 8 
inches (203 mm) with joint reinforcement of at least 9 gage 
and shall extend at least 30 inches (762 mm) in each direc- 
tion at the intersection. Other metal ties, joint reinforcement 
or anchors, if used, shall be spaced to provide equivalent 
area of anchorage to that required by this section. 

R606.9.2 Vertical lateral support. Vertical lateral support 
of masonry walls in Seismic Design Category A, B or C 
shall be provided in accordance with one of the methods in 
Section R606.9.2.1 or Section R606.9.2.2. 

R606.9.2.1 Roof structures. Masonry walls shall be 
anchored to roof structures with metal strap anchors 
spaced in accordance with the manufacturer's instruc- 
tions, '/2-inch (13 mm) bolts spaced not more than 6 feet 
(1829 mm) on center, or other approved anchors. 
Anchors shall be embedded at least 16 inches (406 mm) 



into the masonry, or be hooked or welded to bond beam 
reinforcement placed not less than 6 inches (152 mm) 
from the top of the wall. 

R606.9.2.2 Floor diaphragms. Masonry walls shall be 
anchored to floor diaphragm framing by melal strap anchors 
spaced in accordance with the manufacturer's instructions, 
Vj-inch-diameter (13 mm) bolts spaced at intervals not to 
exceed 6 feet (1829 mm) and installed as shown in Figure 
R606. 1 1 ( 1), or by other approved methods. 

R606.10 Lintels. Masonry over openings shall be supported 
by steel lintels, reinforced concrete or masonry lintels or 
masonry arches, designed to support load imposed. 

R606.il Anchorage. Masonry walls shall be anchored to floor 
and roof systems in accordance with the details shown in Fig- 
ure R606.11(l), R606.11(2) or R606.11(3). Footings may be 
considered as points of lateral support. 

R606.12 Seismic requirements. The seismic requirements of 
this section shall apply to the design of masonry and the con- 
struction of masonry building elements located in Seismic 
Design Category Dq, D, or Dj. Townhouses in Seismic Design 
Category C shall comply with the requirements of Section 
R606.12.2. These requirements shall not apply to glass unit 
masonry conforming to Section R610 or masonry veneer con- 
forming to Section R703.7. 

R606.12.1 General. Masonry structures and masonry ele- 
ments shall comply with the requirements of Sections 
R606. 12.2 through R606. 12.4 based on the seismic design 
category established in Table R301.2(l). Masonry struc- 
tures and masonry elements shall comply with the require- 
■ ments of Section R606.12 and Figures R606.11(l), 
R606.11(2) and R606.il (3) or shall be designed in accor- 
dance with ACI 530/ASCE 5/TMS 402. 

R606.12.1.1 Floor and roof diaphragm construction. 

Floor and roof diaphragms shall be constructed of wood 
structural panels attached to wood framing in accordance 
with Table R602.3(l) or to cold-formed steel floor fram- 
ing in accordance with Table R505.3.1(2) or to 
cold-formed steel roof framing in accordance with Table 
R804.3. Additionally, sheathing panel edges perpendic- 
ular to framing members shall be backed by blocking, 
and sheathing shall be connected to the blocking with 
fasteners at the edge spacing. For Seismic Design Cate- 
gories C, Dq, Dj and D2, where the width-to-thickness 
dimension of the diaphragm exceeds 2-to-l, edge spac- 
ing of fasteners shall be 4 inches (102 mm) on center. 

R606.12.2 Seismic Design Category C» Townhouses 
I located in Seismic Design Category C shall comply with the 
requirements of this section. 

R606. 12.2. 1 Design of elements not part of the lateral 
force-resisting system. 

R606,12.2.1.1 Load-bearing frames or columns. 

Elements not part of the lateral-force-resisting system 
shall be analyzed to determine their effect on the 
response of the system. The frames or columns shall 
be adequate for vertical load carrying capacity and 
; induced moment caused by the design story drift. 



182 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



WALL CONSTRUCTION 



SHEATHING NAILED IN 
ACCORDANCE WITH 
TABLE R602.3(1) 



RAFTER 




BLOCKING 



2 IN. NOMINAL 
PUVTE 



SHEATHING NAILED IN 
ACCORDANCE WITH 
TABLE R602.3(1) 



1/2 IN. BOLT AT 8 FT O.C. 
EMBEDDED4IN. MIN. 




I/2 IN. BOLT AT 8 FT O.C. 
EMBEDDED 4 IN. MIN. 



BOLT EMBEDDED, 
4 IN. 



SEE TABLE FOR BOLT 
SIZE AND SPACING 




LEDGER BOLT 
SIZE AND SPACING 



JOIST 



? 



APPROVED METAL CONNECTOR 
SIN. NOMINAL LEDGER 



JOIST SPAN 


BOLT SIZE AND SPACING 


ROOF 


FLOOR 


10 FT 


1/2 AT 2 FT 6 IN. 
7/aAT3FT6IN. 


V2 AT 2 FT IN. 
7/gAT2FT9IN. 


10-15 FT 


V2ATI FT 9 IN, 
7/8 AT 2 FT 6 IN. 


V2ATI FT 4 IN. 
7/8 AT 2 FT IN. 


1 5-20 FT 


1/2 ATI FT 3 IN. 
7/8AT2FT0IN. 


V2 AT 1 FT IN. 
7/8 ATI FT 6 IN. 



SHEATHING NAILED IN 
ACCORDANCE WITH 
TABLE R602.3(1) 



JOISTS 

PERPENDICULAR 
TO WALL 



SEE TABLE 
ABOVE FOR BOLT 
AND SIZE 
SPACING 




3-1 6d PER JOIST 
SPACING 



3 IN. NOMINAL 
END JOIST 



V2IN. BOLT AT 8 FT O.C, 
EMBEDDED AT 4 IN. MIN 



'EMBEDDED 4 IN. MIN 




JOISTS 
PARALLEL TO 
WALL 



NOTE: Where bolts are located in hollow masonry, the cells in the courses receiving the bolt shall be grouted solid. 
For SI: I inch = 25.4 mm, Ifoot = 304.8 mm, 1 pound per square foot = 0.0479 kR. 

FIGURE R606.1 1(1) 

ANCHORAGE REQUIREMENTS FOR MASONRY WALLS LOCATED IN SEISMIC DESIGN CATEGORY 

A, B OR C AND WHERE WIND LOADS ARE LESS THAN 30 PSF 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



183 



WALL CONSTRUCTION 



ROOF CONNECTORS AT 
48 IN, MAX. O.C. 



#4 BARS AROUND 
OPENINGS 

DETAIL B 



#4 BARS WITHIN 8 IN. OF ENDS 
OF WALLS AND AT CORNERS 




#4BARSAT10FTO.C 



24 IN. OR 
40 db 



#4BARS(MIN.)AT 
DIAPHRAGMS 
CONT THRU C.J. 



#4BARS(IVttN,) 
WITHIN 8 IN. OF 
ALLC.J.'S 



CONTROL JOINT 
(C.J.) 



#4 BARS AT 10 FT O.C. OR W1 ,7 
JOINT REINFORCED AT 16 IN. O.C. 



MINIMUM reinforcement; FOR MASONRY WALLS 



ANCHOR BOLTS 



2 m. PLATE WITH V, IN. ^ BOLTS 
NOT MORE THAN 4TT O.C. 
EMBEDDED 4 IN. MIN 




BOND BEAM STEEL H|; 
TWO Va IN. BARS 



LINTEL STEEL- 
SEE SECTION R606.10 



REINFORCEMENT- 
SEE SECTIONS 
R606.12.2,1.3ancl 
R606. 12.2.2.3 

NOT HEADER^ 
COURSE 



LAP 40 OIA. 

i 



'DOWEL 




3 IN. X 3 IN. X 1/4 IN. CLIP 
ANGLE 4 FT O.C. 
ONE i/g IN. BOLT 



TWO #4 LATERAL TIES WITHIN 
TOP 5 IN. OF COLUMN THAT 
ENCLOSE ANCHOR BOLTS AND 
VERTICAL REINFORCEMENT 



VERTICAL COLUMN 
REINFORCEMENT 



REINFORCEMENT SHALL 
HAVE MIN. 1/4 IN. 
CLEARANCE - 




5 IN. MAX 



COLUMN TIES 



12 IN, MAX. 

BEFORE 

GROUTING 



METAL TIES- 
SEE SECTION R608 



HEADER COURSES 
NOT PERMITTED 



MIN. % IN. GROUT 





WHERE INTERIOR 
STUD PARTITION 
MEETS WALL BOLT 
END STUD WITH 1/2 IN. 
(J! BOLTS 3 FT O.C. 



S 







LAP 40 OIA. 



SECTION 1 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. \ 

FIGURE R606.11 (2) 
REQUIREMENTS FOR REINFORCED GROUTED MASONRY CONSTRUCTION IN SEISMIC DESIGN CATEGORY C 



184 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



ROOF CONNECTORS AT 
48 IN. MAX. O.C. 



#4 BARS AROUND 
OPENINGS 

DETAILS 



#4 BARS WITHIN 8 IN. OF ENDS 
OF WALLS AND AT CORNERS 




#4BARSAT48IN. O.C, 



24 IN. OR 
40 dj, 



#4 8ARS(WlfN.)AT 
DIAPHRAGMS 
CONT THRU C.J. 



#4 BARS {WIN.) 
WITHIN 8 IN. OF 

ALL c.j;s 



CONTROL JOINT 
(C.J.) 



#4 BARS AT 48 IN. O.C. 



MINIMUM REINFORCEMENT FOR MASONRY WALLS 



3 IN, X 31/4 IN. CLIP ANGLE 4 FT O.C, 
ONE 1/2 <|» IN. BOLT, 




BOND BEAM TWO Vg i> IN. 
BARS STEEL 



1/5 IN. BOLTS NOT MORE 
THAN 4 FT O.C. IN CELLS 
WITH VERTICAL ROD 
WHERE POSSIBLE 
EMBEDDED 4 IN, MIN. 



ANCHOR BOLTS 



TWO #4 LATERAL TIES WITHIN 
TOP 5 IN. OF COLUMN WHICH >,. 
ENCLOSE ANCHOR BOLTS AND Z 
VERTICAL REINFORCEMENT 



VERTICAL COLUMN 
REINFORCEMENT 



I 



TIE COURSE 

REINFORCEMENTS- 
SEE SECTIONS R606.12;2.1,3. 
R6D6,12,3.2andR606.12.4 



DOWEL2FT6IN. 
LONG 



I 



I 



SECTION C 



.^iv.^„ 



LINTEL BAR OR 
BARS—SEE 
SECTION R606.10 




SIN. MAX, 



#3 COLUMN 
TIES AT 8 IN. 
MAX. 



% IN. 4) DOWEL 



a/g IN. ^ ROD 



6 IN. 



6 IN. MIN. 



FT- 



6 IN. 



14 IN. 




DETAIL "A" 



FOUNDATION 



INSPECTION OPENING 
NOT REQUIRED IF 
INSPECTED AT THE 
COURSE 



FOUNDATION FOR 
WOOD FLOOR 



FOUNDATION FOR 
CONCRETE FLOOR 



Note: A full bed joint must be provided. All cells containing vertical bars are to be filled to the top of wall and provide inspection opening as shown 
on detail "A," Horizontal bare are to be laid as shown on detail "B." Lintel bars are to be laid as shown on Section C, 

NOTE: A full bed joint must be provided. All cells containing vertical bars are to be filled to the top of wall and provide inspection opening as shown on detail "A." 

Horizontal bars are to be laid as shown on detail "B." Lintel bars are to be laid as shown on Section C. 
For SL 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

FIGURE R606.1 1(3) 
REQUIREMENTS FOR REINFORCED MASONRY CONSTRUCTION IN SEISMIC DESIGN CATEGORY Do, Di OR D2 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



185 



WALL CONSTRUCTION 



R606.12.2.1.2 Masonry partition walls. Masonry 
partition walls, masonry screen walls and other 
masonry elements that are not designed to resist verti- 
cal or lateral loads, other than those induced by their 
own weight, shall be isolated from the structure so 
that vertical and lateral forces are not imparted to 
these elements. Isolation joints and connectors 
between these elements and the structure shall be 
designed to accommodate the design story drift. 

R606.12.2.1.3 Reinforcement requirements for 
masonry elements. Masonry elements listed in Sec- 
tion R606. 12.2. 1.2 shall be reinforced in either the 
horizontal or vertical direction as shown in Figure 
R606.il (2) and in accordance with the following: 

1. Horizontal reinforcement. Horizontal joint 
reinforcement shall consist of at least two lon- 
gitudinal W1.7 wires spaced not more than 16 
inches (406 mm) for walls greater than 4 inches 
(102 mm) in width and at least one longitudinal 
Wl .7 wire spaced not more than 16 inches (406 
mm) for walls not exceeding 4 inches (102 nmi) 
in width; or at least one No. 4 bar spaced not 
more than 48 inches (1219 mm). Where two 
longitudinal wires of joint reinforcement are 
used, the space between these wires shall be the 
widest that the mortar joint will accommodate. 
Horizontal reinforcement shall be provided 
within 16 inches (406 mm) of the top and bot- 
tom of these masonry elements. 

2. Vertical reinforcement. Vertical reinforcement 
shall consist of at least one No. 4 bar spaced not 
more than 48 inches (1219 mm). Vertical rein- 
forcement shall be located within 16 inches 
(406 mm) of the ends of masonry walls. 

R606.12.2.2 Design of elements part of the lat- 
eral-force-resisting system. 

R606.12.2.2.1 Connections to masonry shear 
walls. Connectors shall be provided to transfer forces 
between masonry walls and horizontal elements in 
accordance with the requirements of Section 2.1.8 of 
ACI 530/ASCE 5/TMS 402. Connectors shall be 
designed to transfer horizontal design forces acting 
either perpendicular or parallel to the wall, but not less 
than 200 pounds per linear foot (2919 N/m) of wall. 
The maximum spacing between connectors shall be 4 
feet (1219 mm). Such anchorage mechanisms shall 
not induce tension stresses perpendicular to grain in 
ledgers or nailers. 

R606.12.2.2.2 Connections to masonry columns. 

Connectors shall be provided to transfer forces 
between masonry columns and horizontal elements in 
accordance with the requirements of Section 2.1.8 of 
ACI 530/ASCE 5/TMS 402. Where anchor bolts are 
used to connect horizontal elements to the tops of col- 
umns, the bolts shall be placed within lateral ties. Lat- 
eral ties shall enclose both the vertical bars in the 
column and the anchor bolts. There shall be a mini- 



mum of two No. 4 lateral ties provided in the top 5 
inches (127 mm) of the column. 

R606. 12.2.2.3 Minimum reinforcement require- 
ments for masonry shear walls. Vertical reinforce- 
ment of at least one No. 4 bar shall be provided at 
comers, within 16 inches (406 mm) of each side of 
openings, within 8 inches (203 mm) of each side of 
movement joints, within 8 inches (203 mm) of the 
ends of walls, and at a maximum spacing of 10 feet 
(3048 mm). 

Horizontal joint reinforcement shall consist of at 
leasttwo wiresofWl.7 spaced not more than 16inches 
(406 mm); or bond beam reinforcement of at least one 
No. 4 bar spaced not more than 10 feet (3048 mm) shall 
be provided. Horizontal reinforcement shall also be 
provided at the bottom and top of wall openings and 
shall extend not less than 24 inches (610 mm) nor less 
than 40 bar diameters past the opening; continuously at 
structurally connected roof and floor levels; and within 
16 inches (406 mm) of the top of walls. 

R606.12.3 Seismic Design Category Do or Dj. Structures I 
in Seismic Design Category Dq or Dj shall comply with the I 
requirements of Seismic Design Category C and the addi- 
tional requirements of this section. 

R606. 12.3.1 Design requirements. Masonry elements 
other than those covered by Section R606. 12.2. 1.2 shall 
be designed in accordance with the requirements of 
Chapter 1 and Sections 2.1 and 2.3 of ACI 530/ASCE 
5/TMS 402 and shall meet the minimum reinforcement 
requirements contained in Sections R606. 12.3.2 and 
R606.12.3.2.1. 

Exception: Masonry walls limited to one story in 
height and 9 feet (2743 mm) between lateral supports 
need not be designed provided they comply with the 
minimum reinforcement requirements of Sections 
R606.12.3.2 and R606.12.3.2.1. 

R606. 12.3.2 Minimum reinforcement requirements for 
masonry walls. Masonry walls other than those covered by 
Section R606. 12.2. 1 .3 shall be reinforced in both the verti- 
cal and horizontal direction. The sum of the cross-sectional 
area of horizontal and vertical reinforcement shall be at 
least 0.002 times the gross cross-sectional .area of the wall, 
and the minimum cross-sectional area in each direction 
shall be not less than 0.0007 times the gross cross-sectional 
area of the wall. Reinforcement shall be uniformly distrib- 
uted. Table R606. 12.3.2 shows the mininium reinforcing 
bar sizes required for varying thicknesses of masonry walls. 
The maximum spacing of reinforcement shall be 48 inches 
(1219 mm) provided that the walls are solid grouted and 
constructed of hoUow open-end units, hollow units laid 
with full head joints or two wythes of soUd units. The maxi- 
mum spacing of reinforcement shall be 24 inches (610 mm) 
for all other masonry. 

R606. 12.3.2.1 Shear wall reinforcement require- 
ments. The maximum spacing of vertical and hori- 
zontal reinforcement shall be the smaller of one-third 
the length of the shear wall, one-third the height of the 



186 



2006 INTERNATIONAL RESIDENTIAL CODE® 



WALL CONSTRUCTION 



TABLE R606.1 2.3.2 
MINIMUM DISTRIBUTED WALL REINFORCEMENT FOR BUILDING ASSIGNED TO SEISMIC DESIGN CATEGORY Dq or D, 







MINIMUM REINFORCEMENT AS 






MINIMUM SUM OF THE VERTICAL 


DISTRIBUTED IN BOTH 






AND HORIZONTAL 


HORIZONTAL AND VERTICAL 


MINIMUM BAR SIZE FOR 


NOMINAL WALL THICKNESS 


REINFORCEMENT AREAS^ 


DIRECTIONS" 


REINFORCEMENT SPACED AT 48 


(Inches) 


(square inches per foot) 


(square Inches per foot) 


INCHES 


6 


0.135 


0.047 


#4 


8 


0.183 


0.064 


#5 


10 


0.231 


0.081 


#6 


12 


0.279 


0.098 


#6 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch per foot = 2064 mrr?/m. 

a. Based on the minimum reinforcing ratio of 0.002 times the gross cross-sectional area of the \\all. 

b. Based on the minimum reinforcing ratio each direction of 0.0007 times the gross cross-sectional area of the wall. 



shear wall, or 48 inches (1219 mm). The minimum 
cross-sectional area of vertical reinforcement shall be 
one-third of the required shear reinforcement. Shear 
reinforcement shall be anchored around vertical rein- 
forcing bars with a standard hook. 

R606.12.3.3 Minimum reinforcement for masonry 
columns. Lateral ties in masonry columns shall be 
spaced not more than 8 inches (203 mm) on center and 
shall be at least Vg inch (9.5 mm) diameter. Lateral ties 
shall be embedded in grout. 

R606. 12.3.4 Material restrictions. Type N mortar or 
masonry cement shall not be used as part of the 
lateral-force-resisting system. 

R606.12.3.5 Lateral tie anchorage. Standard hooks for 
lateral tie anchorage shall be either a 135-degree (2.4 rad) 
standard hook or a 180-degree (3.2 rad) standard hook. 

R606.12.4 Seismic Design Category Dj. All structures in 
Seismic Design Category D2 shall comply with the require- 
ments of Seismic Design Category Dj and to the additional 
requirements of this section. 

R606.12.4.1 Design of elements not part of the 
lateral-force-resisting system. Stack bond masonry that 
is not part of the lateral-force-resisting system shall have a 
horizontal cross-sectional area of reinforcement of at least 
0.0015 times the gross cross-sectional area of masonry. 
Table R606. 12.4.1 shows minimum reinforcing bar sizes 
for masonry walls. The maximum spacing of horizontal 
reinforcement shall be 24 inches (610 mm). These ele- 
ments shall be solidly grouted and shall be constructed of 
hollow open-end units or two wythes of solid units. 

TABLE R606.1 2.4.1 

MINIMUM REINFORCING FOR STACKED BONDED 

MASONRY WALLS IN SEISMIC DESIGN CATEGORY D, 



NOMINAL WALL THICKNESS 
(inches) 


MINIMUM BAR SIZE 
SPACED AT 24 INCHES 


6 

8 

10 
12 


#4 
#5 
#5 
#6 



is part of the lateral-force-resisting system shall have a 
horizontal cross-sectional area of reinforcement of at least 
0.0025 times the gross cross-sectional area of masonry. 
Table R606. 12.4.2 shows minimum reinforcing bar sizes 
for masonry walls. The maximum spacing of horizontal 
reinforcement shall be 16 inches (406 mm). These ele- 
ments shall be soUdly grouted and shall be constructed of 
hollow open-end units or two wythes of solid units. 



TABLE R606.1 2.4.2 

MINIMUM REINFORCING FOR STACKED BONDED MASONRY 

WALLS IN SEISMIC DESIGN CATEGORY D, 



NOMINAL WALL THICKNESS 
(Inches) 


MINIMUM BAR SIZE 
SPACED AT 16 INCHES 


6 
8 

10 
12 


#4 
#5 
#5 
#6 



For SI: I inch = 25.4 mm. 

R606. 12.4.2 Design of elements part of the 
lateral-force-resisting system. Stack bond masonry that 



For SI: 1 inch = 25.4 mm. 

R606.13 Protection for reinforcement. Bars shall be com- 
pletely embedded in mortar or grout. Joint reinforcement 
embedded in horizontal mortar joints shall not have less than 
Vg-inch (15.9 mm) mortar coverage from the exposed face. All 
other reinforcement shall have a minimum coverage of one bar 
diameter over all bars, but not less than '^/^ inch (19 mm), except 
where exposed to weather or soil, in which case the minimum 
coverage shall be 2 inches (51 mm). 

R606.14 Beam supports. Beams, girders or other concen- 
trated loads supported by a wall or column shall have a bearing 
of at least 3 inches (76 mm) in length measured parallel to the 
beam upon solid masonry not less than 4 inches (102 mm) in 
thickness, or upon a metal bearing plate of adequate design and 
dimensions to distribute the load safely, or upon a continuous 
reinforced masonry member projecting not less than 4 inches 
(102 mm) from the face of the wall. 

R606.14.1 Joist bearing. Joists shall have a bearing of not 
less than 1 V2 inches (38 mm), except as provided in Section 
R606.14, and shall be supported in accordance with Figure 
R606.11(l). 

R606.15 Metal accessories. Joint reinforcement, anchors, ties 
and wire fabric shall conform to the following: ASTM A 82 for 
wire anchors and ties; ASTM A 36 for plate, headed and 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



187 



WALL CONSTRUCTION 



bent-bar anchors; ASTM A 510 for corrugated sheet metal 
anchors and ties; ASTM A 951 for joint reinforcement; ASTM 
B 227 for copper-clad steel wire ties; or ASTM A 167 for stain- 
less steel hardware. 

R606.15.1 Corrosion protection. Minimum corrosion 
protection of joint reinforcement, anchor ties and wire fab- 
ric for use in masonry wall construction shall conform to 
Table R606. 15.1. 

TABLE R606.15.1 
MINIMUM CORROSION PROTECTION 



MASONRY METAL ACCESSORY 


STANDARD 


Joint reinforcement, interior walls 


ASTM A 641, Class 1 


Wire ties or anchors in exterior walls 
completely embedded in mortar or 
grout 


ASTM A 641, Class 3 


Wire ties or anchors in exterior walls 
not completely embedded in mortar 
or grout 


ASTM A 153, Class B-2 


Joint reinforcement in exterior walls 
or interior walls exposed to moist 
environment 


ASTM A 153, Class B-2 


Sheet metal ties or anchors exposed 
to weather 


ASTM A 153, Class B-2 


Sheet metal ties or anchors completely 
embedded in mortar or grout 


ASTM A 653, Coating 
Designation G60 


Stainless steel hardware for any 
exposure 


ASTM A 167, Type 304 



SECTION R607 
UNIT MASONRY 

R607.1 Mortar. Mortar for use in masonry construction shall 
comply with ASTM C 270. The type of mortar shall be in 
accordance with Sections R607.1.1, R607.1.2 and R607.1.3 
and shall meet the proportion specifications of Table R607. 1 or 
the property specifications of ASTM C 270. 

R607.1.1 Foundation walls. Masonry foundation walls 
constructed as set forth in Tables R404. 1.1(1) through 
R404.1.1(4) and mortar shall be Type M or S. 

R607.1.2 Masonry in Seismic Design Categories A, B 

and C. Mortar for masonry serving as the lateral-force- 
resisting system in Seismic Design Categories A, B and C 
shall be Type M, S or N mortar. 

R607.1.3 Masonry in Seismic Design Categories Do, Di and 

Dj. Mortar for masonry serving as the lateral-force- resisting 
system in Seismic Design Categories Dg, Dy and D2 shall be 
Type M or S portland cement-lime or mortar cement mortar. 

R607.2 Placing mortar and masonry units. 

R607.2.1 Bed and head joints. Unless otherwise required 
or indicated on the project drawings, head and bed joints 
shall be ^/g inch (10 mm) thick, except that the thickness of 
the bed joint of the starting course placed over foundations 
shall not be less than V4 inch (7 mm) and not more than V4 
inch (19 mm). 



R607.2.1.1 Mortar joint thickness tolerance. Mortar 
joint thickness shall be within the following tolerances 
from the specified dimensions: 

1. Bed joint: + Vg inch (3 mm). 

2. Head joint: 74 inch (7 mm), -f- Vg inch (10 mm). 

3. Collar joints: V4 inch (7 mm), + Vg inch (10 mm). 

Exception: Nonload-bearing masonry elements and 
masonry veneers designed and constructed in accor- 
dance with Section R703.7 are not required to meet 
these tolerances. 

R607.2.2 Masonry unit placement. The mortar shall be 
sufficiently plastic and units shall be placed with sufficient 
pressure to extrude mortar from the joint and produce a tight 
joint. Deep furrowing of bed joints that produces voids shall 
not be permitted. Any units disturbed to the extent that ini- 
tial bond is broken after initial placement shall be removed 
and relaid in fresh mortar. Surfaces to be in contact with 
, mortar shall be clean and free of deleterious materials. 

R607.2.2.1 Solid masonry. Solid masonry units shall be 
laid with full head and bed joints and all interior vertical 
joints that are designed to receive mortar shall be filled. 

R607.2.2.2 Hollow masonry. For hollow masonry units, 
head and bed joints shall be filled solidly with mortar for 
a distance in from the face of the unit not less than the 
thickness of the face shell. 

R607.3 Installation of wall ties. The installation of wall ties 
shall be as follows: 

1 . The ends of wall ties shall be embedded in mortar joints. 
! Wall tie ends shall engage outer face shells of hollow 

units by at least Vj inch (13 mm). Wire wall ties shall be 
embedded at least IV2 inches (38 mm) into the mortar 
bed of solid masonry units or solid grouted hollow units . 

2. Wall ties shall not be bent after being embedded in grout 
or mortar. 



SECTION R608 
MULTIPLE WYTHE MASONRY 

R608.1 General. The facing and backing of multiple wythe 
masonry walls shall be bonded in accordance with Section 
R608.1.1, R608.1.2 or R608.1.3. In cavity walls, neither the 
facing nor the backing shall be less than 3 inches (76 mm) nom- 
inal in thickness and the cavity shall not be more than 4 inches 
(102 mm) nominal in width. The backing shall be at least as 
thick as the facing. 

Exception: Cavities shall be permitted to exceed the 4-inch 
( 1 02 mm) nominal dimension provided tie size and tie spac- 
ing have been established by calculation. 

R608.1.1 Bonding with masonry headers. Bonding with 
solid or hollow masonry headers shall comply with Sections 
i R608.1.1.1andR608.1.1.2. 

R608.1.1.1 Solid units. Where the facing and backing 
(adjacent wythes) of solid masonry construction are 
bonded by means of masonry headers, no less than 4 per- 
cent of the wall surface of each face shall be composed of 



188 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 













TABLE R607.1 












MORTAR PROPORTIONS^ " 








PROPORTIONS BY VOLUME (cementitious materials) 








Mortar cement 


Masonry cement 


Hydrated lime'' or 
lime puttv 


Aggregate ratio (measured in 
damp, loose conditions) 


MORTAR 


TYPE 


blended cement 


M 


S 


N 


M 


S 


N 




M 


1 


— 


— 


— 


— 


— 


— 


V4 




Cement-lime 


S 
N 



1 
1 

1 


— 


— 


— 


— 


— 


— 


over V4 to V2 
over V2to IV4 
over lV^to2Vo 






M 


1 


_ 


_ 


1 


— 


— 


— 






M 


— 


1 


— 


— 


— 


— 


— 






Mortar cement 


S 
S 


\ 


~ 


1 


1 


— 


— 


— 


— 


Not less than 2V4 and not 
more than 3 times the sum 




N 


— 


— 


— 


1 


— 


— 


— 




of separate volumes of 
















1 













lime, if used, and cement 




M 


1 








— 




1 






M 


— 








1 




— 






Masonry 


S 


\ 








— 


~- 


1 






cement 


S 
N 
O 


— 








— 


1 


1 
1 







For SI: 1 cubic foot = 0.0283 m^, 1 pound = 0.454 kg. 

a. For the purpose of these specifications, the weight of 1 cubic foot of the respective materials shall be considered to be as follows: 

Portland Cement 94 pounds Masonry Cement Weight printed on bag 

Mortar Cement Weight printed on bag Hydrated Lime 40 pounds 

Lime Putty (Quicklime) 80 pounds Sand, damp and loose 80 pounds of dry sand 

b. Two air-entraining materials shall not be combined in mortar 

c. Hydrated lime conforming to the requirements of ASTM C 207. 



headers extending not less than 3 inches (76 mm) into the 
backing. The distance between adjacent full-length 
headers shall not exceed 24 inches (610 mm) either verti- 
cally or horizontally. In walls in which a single header 
does not extend through the wall, headers from the oppo- 
site sides shall overlap at least 3 inches (76 mm), or head- 
ers from opposite sides shall be covered with another 
header course overlapping the header below at least 3 
inches (76 mm). 

R608.1.1.2 Hollow units. Where two or more hollow 
units are used to make up the thickness of a wall, the 
stretcher courses shall be bonded at vertical intervals not 
exceeding 34 inches (864 mm) by lapping at least 3 
inches (76 mm) over the unit below, or by lapping at ver- 
tical intervals not exceeding 17 inches (432 mm) with 
units that are at least 50 percent thicker than the units 
below. 

R608.1.2 Bonding with wall ties or joint reinforcement. 

Bonding with wall ties or joint reinforcement shall comply 
with Sections R608.1.2.1 through R608.1.2.3. 

R608.1.2.1 Bonding with wall ties. Bonding with wall 
ties, except as required by Section R610, where the facing 
and backing (adjacent wythes) of masonry walls are 
bonded with Vig-inch-diameter (5 mm) wall ties embed- 
ded in the horizontal mortar joints, there shall be at least 
one metal tie for each 4.5 square feet (0.418 m^) of wall 
area. Ties in alternate courses shall be staggered. The 
maximum vertical distance between ties shall not exceed 
24 inches (610 mm), and the maximum horizontal dis- 



tance shall not exceed 36 inches (914 mm). Rods or ties 
bent to rectangular shape shall be used with hollow 
masonry units laid with the cells vertical. In other walls, 
the ends of ties shall be bent to 90-degree (0.79 rad) angles 
to provide hooks no less than 2 inches (51 mm) long. 
Additional bonding ties shall be provided at aU openings, 
spaced not more than 3 feet (914 mm) apart around the 
perimeter and within 12 inches (305 mm) of the opening. 

R608.1.2.2 Bonding with adjustable wall ties. Where 
the facing and backing (adjacent wythes) of masonry are 
bonded with adjustable wall ties, there shall be at least 
one tie for each 2.67 square feet (0.248 m^) of wall area. 
Neither the vertical nor the horizontal spacing of the 
adjustable wall ties shall exceed 24 inches (610 mm). 
The maximum vertical offset of bed joints from one 
wythe to the other shall be 1.25 inches (32 mm). The 
maximum clearance between connecting parts of the ties 
shall be Vjg inch (2 mm). When pintle legs are used, ties 
shall have at least two Vig-inch-diameter (5 mm) legs. 

R608. 1.2.3 Bonding with prefabricated joint rein- 
forcement. Where the facing and backing (adjacent 
wythes) of masonry are bonded with prefabricated joint 
reinforcement, there shall be at least one cross wire serv- 
ing as a tie for each 2.67 square feet (0.248 m^) of wall 
area. The vertical spacing of the joint reinforcement shall 
not exceed 16 inches (406 mm). Cross wires on prefabri- 
cated joint reinforcement shall not be smaller than No. 9 
gage. The longitudinal wires shall be embedded in the 
mortar. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



189 



WALL CONSTRUCTION 



R608.1.3 Bonding with natural or cast stone. Bonding 
with natural and cast stone shall conform to Sections 
R608.1.3.1andR608.1.3.2. 

R608.1.3.1 Ashlar masonry. In ashlar masonry, bonder 
units, uniformly distributed, shall be provided to the 
extent of not less than 10 percent of the wall area. Such 
bonder units shall extend not less than 4 inches (102 mm) 
into the backing wall. 

R608.1.3.2 Rubble stone masonry. Rubble stone 
masonry 24 inches (610 mm) or less in thickness shall 
have bonder units with a maximum spacing of 3 feet (914 
mm) vertically and 3 feet (914 mm) horizontally, and if 
the masonry is of greater thickness than 24 inches (610 
nmn), shall have one bonder unit for each 6 square feet 
(0.557 m^) of wall surface on both sides. 

R608.2 Masonry bonding pattern. Masonry laid in running 
and stack bond shall conform to Sections R608.2.1 and 
R608.2.2. 

R608.2.1 Masonry laid in running bond. In each wythe of 
masonry laid in running bond, head joints in successive 
courses shall be offset by not less than one-fourth the unit 
length, or the masonry walls shall be reinforced longitudi- 
nally as required in Section R608.2.2. 

R608.2.2 Masonry laid in stack bond. Where unit 
masonry is laid with less head joint offset than in Section 



R607.2.1, the minimum area of horizontal reinforcement 
placed in mortar bed joints or in bond beams spaced not 
more than 48 inches (1219 mm) apart, shall be 0.0007 times 
the vertical cross-sectional area of the wall. 



SECTION R609 
GROUTED MASONRY 

R609.1 General. Grouted multiple-wythe masonry is a form 
of construction in which the space between the wythes is sol- 
idly filled with grout. It is not necessary for the cores of 
masonry units to be filled with grout. Grouted hollow unit 
masonry is a form of construction in which certain cells of hol- 
low units are continuously filled with grout. 

R609.1.1 Grout. Grout shall consist of cementitious mate- 
rial and aggregate in accordance with ASTM C 476 and the 
proportion specifications of Table R609.1.1. Type M or 
Type S mortar to which sufficient water has been added to 
produce pouring consistency can be used as grout. 

R609. 1 .2 Grouting requirements. Maximum pour heights 
and the minimum dimensions of spaces provided for grout 
placement shall conform to Table R609.1.2. If the work is 
stopped for one hour or longer, the horizontal construction 
; joints shall be formed by stopping all tiers at the same eleva- 
tion and with the grout 1 inch (25 mm) below the top. 



TABLE R609.1.1 
GROUT PROPORTIONS BY VOLUME FOR MASONRY CONSTRUCTION 



TYPE 


PORTLAND CEMENT 

OR BLENDED CEMENT 

SLAG CEMENT 


HYDRATED LIME 
OR LIME PUTTY 


' AGGREGATE MEASURED IN A DAMP, LOOSE CONDITION 


Fine 


Coarse 


Fine 


1 


to 1/10 


2 V4 to 3 times the sum of the volume 
of the cementitious materials 


— 


Coarse 


1 


to 1/10 


2 V4 to 3 times the sum of the volume 
of the cementitious materials 


1 to 2 times the sum of the volumes of 
the cementitious materials 



TABLER609.1.2 
GROUT SPACE DIMENSIONS AND POUR HEIGHTS 



GROUT TYPE 


GROUT POUR MAXIMUM HEIGHT 
(feet) 


MINIMUM WIDTH OF 

GROUT SPACES^'" 

(inches) 


MINIMUM GROUT''''^ SPACE DIMENSIONS FOR 

GROUTING CELLS OF HOLLOW UNITS 

(inches x inches) 


Fine 


1 


0.75 


1.5x2 


5 


2 


2x3 


12 


2.5 


2.5 X 3 


24 


3 


3x3 


Coarse 


1 


1.5 


1.5x3 


5 


2 


2.5 X 3 


12 


' 2.5 


3x3 


24 


: 3 


3x4 


For SI: 1 inch = 25.4 mm, 1 foot 


= 304.8 mm. 


' 





a. For grouting between masonry wythes. 

b. Grout space dimension is the clear dimension between any masonry protmsion and shall be increased by the horizontal projection of the diameters of the horizontal 
bars within the cross section of the grout space. ! 

c. Area of vertical reinforcement shall not exceed 6 percent of the area of the grout space. 



190 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



R609.1.3 Grout space (cleaning). Provision shall be made 
for cleaning grout space. Mortar projections that project 
more than 0.5 inch (13 mm) into grout space and any other 
foreign matter shall be removed from grout space prior to 
inspection and grouting. 

R609.1.4 Grout placement. Grout shall be a plastic mix 
suitable for pumping without segregation of the constituents 
and shall be mixed thoroughly. Grout shall be placed by 
pumping or by an approved alternate method and shall be 
placed before any initial set occurs and in no case more than 
172 hours after water has been added. Grouting shall be 
done in a continuous pour, in lifts not exceeding 5 feet (1524 
mm). It shall be consolidated by puddling or mechanical 
vibrating during placing and reconsolidated after excess 
moisture has been absorbed but before plasticity is lost. 

R609.1.4.1 Grout pumped through aluminum pipes. 

Grout shall not be pumped through aluminum pipes. 

R609.1.5 Cleanouts. Where required by the building offi- 
cial, cleanouts shall be provided as specified in this section. 
The cleanouts shall be sealed before grouting and after 
inspection. 

R609. 1.5.1 Grouted multiple-wythe masonry. 

Cleanouts shall be provided at the bottom course of the 
exterior wythe at each pour of grout where such pour 
exceeds 5 feet (1524 mm) in height. 

R609.1.5.2 Grouted hollow unit masonry. Cleanouts 
shall be provided at the bottom course of each cell to be 
grouted at each pour of grout, where such pour exceeds 4 
feet (1219 mm) in height. 

R609.2 Grouted multiple-wythe masonry. Grouted multi- 
ple-wythe masonry shall conform to all the requirements speci- 
fied in Section R609.1 and the requirements of this section. 

R609.2.1 Bonding of backup wythe. Where all interior 
vertical spaces are filled with grout in multiple-wythe con- 
struction, masonry headers shall not be permitted. Metal 
wall ties shall be used in accordance with Section R608. 1 .2 
to prevent spreading of the wythes and to maintain the verti- 
cal alignment of the wall. Wall ties shall be installed in 
accordance with Section R608.1.2 when the backup wythe 
in multiple-wythe construction is fully grouted. 

R609.2.2 Grout spaces. Fine grout shall be used when inte- 
rior vertical space to receive grout does not exceed 2 inches 
(51 mm) in thickness. Interior vertical spaces exceeding 2 
inches (5 1 mm) in thickness shall use coarse or fine grout. 

R609.2.3 Grout barriers. Vertical grout barriers or dams 
shall be built of solid masonry across the grout space the 
entire height of the wall to control the flow of the grout hori- 
zontally. Grout barriers shall not be more than 25 feet (7620 
mm) apart. The grouting of any section of a wall between 
control barriers shall be completed in one day with no inter- 
ruptions greater than one hour. 

R609.3 Reinforced grouted multiple-wythe masonry. Rein- 
forced grouted multiple-wythe masonry shall conform to all 
the requirements specified in Sections R609.1 and R609.2 and 
the requirements of this section. 



R609.3.1 Construction. The thickness of grout or mortar 
between masonry units and reinforcement shall not be less 
than V4 inch (7 mm), except that V4-inch (7 mm) bars may be 
laid in horizontal mortar joints at least V2 inch (13 mm) 
thick, and steel wire reinforcement may be laid in horizontal 
mortar joints at least twice the thickness of the wire diame- 
ter. 

R609.4 Reinforced hollow unit masonry. Reinforced hollow 
unit masonry shall conform to all the requirements of Section 
R609.1 and the requirements of this section. 

R609.4.1 Construction. Requirements for construction 
shall be as follows: 

1 . Reinforced hollow-unit masonry shall be built to pre- 
serve the unobstructed vertical continuity of the cells 
to be filled. Walls and cross webs forming cells to be 
filled shall be full-bedded in mortar to prevent leak- 
age of grout. Head and end joints shall be solidly 
filled with mortar for a distance in from the face of the 
wall or unit not less than the thickness of the longitu- 
dinal face shells. Bond shall be provided by lapping 
units in successive vertical courses. 

2. Cells to be filled shall have vertical alignment suffi- 
cient to maintain a clear, unobstructed continuous 
vertical cell of dimensions prescribed in Table 
R609.1.2. 

3. Vertical reinforcement shall be held in position at top 
and bottom and at intervals not exceeding 200 diame- 
ters of the reinforcement. 

4. Cells containing reinforcement shall be filled solidly 
with grout. Grout shall be poured in lifts of 8-foot 
(2438 mm) maximum height. When a total grout pour 
exceeds 8 feet (2438 mm) in height, the grout shall be 
placed in lifts not exceeding 5 feet (1524 mm) and 
special inspection during grouting shall be required. 

5. Horizontal steel shall be fully embedded by grout in 
an uninterrupted pour. 



SECTION R610 
GLASS UNIT MASONRY 

R610.1 General. Panels of glass unit masonry located in 
load-bearing and nonload-bearing exterior and interior walls 
shall be constructed in accordance with this section. 

R610.2 Materials. Hollow glass units shall be partially evacu- 
ated and have a minimum average glass face thickness of Vjs 
inch (5 mm). The surface of units in contact with mortar shall 
be treated with a polyvinyl butyral coating or latex-based paint. 
The use of reclaimed units is prohibited. 

R610.3 Units. Hollow or solid glass block units shall be stan- 
dard or thin units. 

R610.3.1 Standard units. The specified thickness of stan- 
dard units shall be at least 378 inches (98 mm). 

R610.3.2 Thin units. The specified thickness of thin units 
shall be at least 378 inches (79 mm) for hollow units and at 
least 3 inches (76 mm) for solid units. 



2006 INTERNATIONAL RESIDENTIAL CODE** 



191 



WALL CONSTRUCTION 



R610.4 Isolated panels. Isolated panels of glass unit masonry 
shall conform to the requirements of this section. 

R610.4.1 Exterior standard-unit panels. The maximum 
area of each individual standard-unit panel shall be 144 
square feet (13.4 m^) when the design wind pressure is 20 
psf (958 Pa) . The maximum area of such panels subjected to 
design wind pressures other than 20 psf (958 Pa) shall be in 
accordance with Figure R610.4.1. The maximum panel 
dimension between structural supports shall be 25 feet 
(7620 mm) in width or 20 feet (6096 mm) in height. 

R610.4.2 Exterior thin-unit panels. The maximum area of 
each individual thin-unit panel shall be 85 square feet (7.9 
m^). The maximum dimension between structural supports 
shall be 15 feet (4572 mm) in width or 10 feet (3048 mm) in 
height. Thin units shall not be used in applications where the 
design wind pressure as stated in Table R301.2(l) exceeds 
20 psf (958 Pa). 

R610.4.3 Interior panels. The maximum area of each indi- 
vidual standard-unit panel shall be 250 square feet (23.2 
m^). The maximum area of each thin-unit panel shall be 150 
square feet (13.9 m^). The maximum dimension between 
structural supports shall be 25 feet (7620 mm) in width or 20 
feet (6096 mm) in height. 

R610.4.4 Curved panels. The width of curved panels shall 
conform to the requirements of Sections R610.4.1, R610.4.2 
and R610.4.3, except additional structural supports shall be 
provided at locations where a curved section joins a straight 
section, and at inflection points in multicurved walls. 

R610.5 Panel support. Glass unit masonry panels shall con- 
form to the support requirements of this section. 



R610.5.1 Deflection. The maximum total deflection of 
structural members that support glass unit masonry shall not 
exceed V^oo- 

R610.5.2 Lateral support. Glass unit masonry panels shall 
be laterally supported along the top and sides of the panel. 
Lateral supports for glass unit masonry panels shall be 
designed to resist a minimum of 200 pounds per lineal feet 
(2918 N/m) of panel, or the actual apphed loads, whichever 
is greater. Except for single unit panels, latei^al Support shall 
be provided by panel anchors along the top and sides spaced 
a maximum of 16 inches (406 mm) on center or by 
channel-type restraints. Single unit panels shall be sup- 
ported by channel-type restraints. 

Exceptions: 

1 . Lateral support is not required at the top of panels 
that are one unit wide. 

2. Lateral support is not required at the sides of pan- 
els that are one unit high. 

R610.5.2.1 Panel anchor restraints. Panel anchors 
shall be spaced a maximum of 16 inches (406 mm) on 
center in both jambs and across the head. Panel anchors 
shall be embedded a minimum of 12 inches (305 mm) 
and shall be provided with two fasteners so as to resist the 
loads specified in Section R610.5.2. 

R610. 5.2.2 Channel-type restraints. Glass unit 
masonry panels shall be recessed at least 1 inch (25 
mm) within channels and chases. Channel-type 
restraints shall be oversized to accommodate expansion 
material in the opening, packing and sealant between 




MAXIMUM AREA OF PANEL (SQUARE FEET) 



For SI: 1 square foot = 0.0929 m^, 1 pound per square foot = 0.0479 kP^. 



FIGURE R610.4.1 
GLASS UNIT MASONRY DESIGN WIND LOAD RESISTANCE 



192 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



WALL CONSTRUCTION 



the framing restraints, and the glass unit masonry per- 
imeter units. 

R610.6 Sills. Before bedding of glass units, the sill area shall 
be covered with a water base asphaltic emulsion coating. The 
coating shall shall be a minimum of Vg inch (3 mm) thick. 

R610.7 Expansion joints. Glass unit masonry panels shall be 
provided with expansion joints along the top and sides at all 
structural supports. Expansion joints shall be a minimum of Vg 
inch (10 mm) in thickness and shall have sufficient thickness to 
accommodate displacements of the supporting structure. 
Expansion joints shall be entirely free of mortar and other 
debris and shall be filled with resilient material. 

R610.8 Mortar. Glass unit masonry shall be laid with Type S 
or N mortar. Mortar shall not be retempered after initial set. 
Mortar unused within 1 '^ hours after initial mixing shall be 
discarded. 

R610.9 Reinforcement. Glass unit masonry panels shall have 
horizontal joint reinforcement spaced a maximum of 16 inches 
(406 mm) on center located in the mortar bed joint. Horizontal 
joint reinforcement shall extend the entire length of the panel 
but shall not extend across expansion joints. Longitudinal 
wires shall be lapped a minimum of 6 inches (152 mm) at 
splices. Joint reinforcement shall be placed in the bed joint 
immediately below and above openings in the panel. The rein- 
forcement shall have not less than two parallel longitudinal 
wires of size W1.7 or greater, and have welded cross wires of 
size W 1.7 or greater. 

R610.10 Placement. Glass units shall be placed so head and 
bed joints are filled solidly. Mortar shall not be furrowed. Head 
and bed joints of glass unit masonry shall be V4 inch (6.4 mm) 
thick, except that vertical joint thickness of radial panels shall 
not be less than Vg inch (3 mm) or greater than Vg inch (16 mm). 
The bed joint thickness tolerance shall be minus V,6 inch (1.6 
mm) and plus Vg inch (3 mm). The head joint thickness toler- 
ance shall be plus or minus Vg inch (3 mm). 



SECTION R611 

INSULATING CONCRETE FORM 

WALL CONSTRUCTION 

R611.1 General. Insulating Concrete Form (IPC) walls shall 
be designed and constructed in accordance with the provi- 
sions of this section or in accordance with the provisions of 
ACI 318. When ACI 318 or the provisions of this section are 
used to design insulating concrete form walls, project draw- 
ings, typical details and specifications are not required to bear 
the seal of the architect or engineer responsible for design, 
unless otherwise required by the state law of the jurisdiction 
having authority. 

R611.2 Applicability limits. The provisions of this section 
shall apply to the construction of insulating concrete form 
walls for buildings not greater than 60 feet (18 288 mm) in plan 
dimensions, and floors not greater than 32 feet (9754 mm) or 
roofs not greater than 40 feet (12 192 mm) in clear span. Build- 
ings shall not exceed two stories in height above-grade. ICF 
walls shall comply with the requirements in Table R611.2. 
Walls constructed in accordance with the provisions of this sec- 
tion shall be limited to buildings subjected to a maximum 
design wind speed of 150 miles per hour (67 m/s), and Seismic 
Design Categories A, B, C, Dq, Dj and D2. The provisions of | 
this section shall not apply to the construction of ICF walls for 
buildings or portions of buildings considered irregular as 
defined in Section R301. 2.2.2.2. 

For townhouses in Seismic Design Category C and all build- 
ings in Seismic Design Category Dq, Dj or D2, the provisions of | 
this section shall apply only to buildings meeting the following 
requirements. 

1 . Rectangular buildings with a maximum building aspect 
ratio of 2: 1 .The building aspect ratio shall be determined 
by dividing the longest dimension of the building by the 
shortest dimension of the building. 

2. Walls are aligned vertically with the walls below. 



TABLER611.2 
REQUIREMENTS FOR ICF WALLS" 



WALL TYPE AND 
NOMINAL SIZE 


MAXIMUM WALL 
WEIGHT (psf)'= 


MINIMUM WIDTH 

OF VERTICAL 

CORE (inches)^ 


MINIMUM 
THICKNESS OF 
VERTICAL CORE 

(inches)^ 


MAXIMUM SPACING 

OF VERTICAL 

CORES 

(Inches) 


MAXIMUM SPACING 

OF HORIZONTAL 

CORES 

(inches) 


MINIMUM WEB 

THICKNESS 

(inches) 


3.5" Flat" 


44d 


N/A 


N/A 


N/A 


N/A 


N/A 


5.5" Flat 


69 


N/A 


N/A 


N/A 


N/A 


N/A 


7.5" Flat 


94 


N/A 


N/A 


N/A 


N/A 


N/A 


9.5" Flat 


119 


N/A 


N/A 


N/A 


N/A 


N/A 


6" Waffle-Grid 


56 


6.25 


5 


12 


16 


2 


8" Waffle-Grid 


76 


7 


7 


12 


16 


2 


6" Screen-Grid 


53 


5.5 


5.5 


12 


12 


N/A 



For SI: 1 inch = 25.4 mm; 1 pound per cubic foot = 16.018 kg/m?; 1 pound per square foot = 0.0479 kPa. 

a. For width "W", thickness "T", spacing, and web thickness, refer to Figures R611.4 and R611.5. 

b. N/A indicates not applicable. 

c. Wall weight is based on a unit weight of concrete of 150 pcf. The tabulated values do not include any allowance for interior and exterior finishes. 

d. For all buildings in Seismic Design Category A or B, and detached one- and two-family dwellings in Seismic Design Category C the actual wall thickness is per- 
mitted to be up to 1 inch thicker than shown and the maximum wall weight to be 56 psf. Construction requirements and other limitations within Section R61 1 for 
3.5-inch flat ICF walls shall apply. Interpolation between provisions for 3.5-inch and 5.5-inch flat ICF walls is not permitted. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



193 



WALL CONSTRUCTION 



3. Cantilever and setback construction shall not be permit- 
ted. 

4. The weight of interior and exterior finishes applied to 
ICF walls shall not exceed 8 psf (380 Pa). 

5. The gable portion of ICF walls shall be constructed of 
light-frame construction. 

R611.3 Flat insulating concrete form wall systems. Flat ICF 
wall systems shall comply with Figure R61 1.3 and shall have 
reinforcement in accordance with Tables R61 1.3(1) and 
R611.3(2) and Section R611.7. 

R611.4 Waffle-grid insulating concrete form wall systems. 

Waffle-grid wall systems shall comply with Figure R611 .4 and 
shall have reinforcement in accordance with Tables R611.3(l) 



and R61 1.4(1) and Section R611.7. The minimum core 
dimensions shall comply with Table R611.2. 

R611.5 Screen-grid insulating concrete form wall systems. 

Screen-grid ICF wall systems shall comply with Figure R611 .5 
and shall have reinforcement in accordance with Tables 
;R61 1 .3(1) and R61 1 .5 and Section R61 1 .7. The minimum core 
dimensions shall comply with Table R611.2. 

R611.6 Material. Insulating concrete form wall materials 
shall comply with this section. 

R611.6.1 Concrete material. Ready-mixed concrete for 
insulating concrete form walls shall be in accordance with 
Section R402.2. Maximum slump shall not be greater than 6 
inches (152 mm) as determined in accordance with ASTM 



• 



ACTUAL WALL 
THICKNESS 

^INSUUTING FORM 



VERTICAL 
REINFORCEMENT 
IF REQUIRED 



CONCRETE 



PLAN VIEW 




NSULATING FORM 



ISOMETRIC VIEW 



FIGURE R61 1.3 
FLAT ICF WALL SYSTEM 



TABLE R61 1.3(1) 
DESIGN WIND PRESSURE FOR USE WITH TABLES R61 1.3(2), R611 


.4(1), AND R611.5 FOR ABOVE GRADE WALLS^ 


WIND SPEED 
(mphf 


DESIGN WIND PRESSURE (psf) 


Enclosed" 


Partially Enclosed'' 


Exposure*^ 


Exposure"^ 


B 


C 


D i 


B 


C 


D 


85 


18 


24 


29 


23 


31 


37 


90 


20 


27 


32 ■ 


25 


35 


41 


100 


24 


34 


39 ' 


31 


43 


51 


110 


29 


41 


48 ' 


38 


52 


61 


120 


35 


48 


57 


45 


62 


73 


130 


41 


56 


66 


53 


73 


85" 


140 


47 


65 


77 


61 


84^ 


99" 


150 


54 


75 


88'' 


70 


96'' 


114" . 



For SI: 1 pound per square foot = 0.0479 kPa; 1 mile per hour = 0.447 m/s; I foot = 304.8 mm; 1 square foot = 0.0929 n?. 

a. This table is based on ASCE 7-98 components and cladding wind pressures using a mean roof height of 35 ft and a trihitary area of 10 ft-^. 

b. Buildings in wind-borne debris regions as defined in Section R202 shall be considered as "Partially Enclosed" unless glazed openings are protected in accordance 
with Section R301.2.1.2, in which case the building shall be considered as "Enclosed." All other buildings shall be classified as "Enclosed." 

c. Exposure Categories shall be determined in accordance with Section R301.2.1.4. 

d. For wind pressures greater than 80 psf, design is required in accordance with ACI 318 and approved manufacturer guidehnes. 

e. Interpolation is permitted between wind speeds. 



194 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



C 143. Maximum aggregate size shall not be larger than V4 
inch (19 mm). 

Exception: Concrete mixes conforming to the ICF man- 
ufacturer's recommendations. 

In Seismic Design Categories Dq, D, and Dj, the mini- 
mum concrete compressive strength shall be 3,000 psi (20.5 
MPa). 



WALL CONSTRUCTION 



R61 1.6.2 Reinforcing steel. Reinforcing steel shall 
meet the requirements of ASTM A 615, A 706, or A 996. 
Except in Seismic Design Categories Dq, D, and D2, the 
minimum yield strength of reinforcing steel shall be 
40,000 psi (Grade 40) (276 MPa). In Seismic Design 
Categories Dq, Dj and D2, reinforcing steel shall meet the 
requirements of ASTM A 706 for low-alloy steel with a 
minimum yield strength of 60,000 psi (Grade 60) (414 
Mpa). 



TABLE R61 1.3(2) 
MINIMUM VERTICAL WALL REINFORCEMENT FOR FLAT ICF ABOVE-GRADE WALLS^" = " 



Design Wind 
Pressure [Table 
R611.3(1)](psf) 


Maximum 

Unsupported 

Wall Height 

(feet) 


Minimum Vertical Reinforcement'^' ®' * 


Nonload-Bearing Wall 
or Supporting Roof 


Supporting Light-Framed 
Second Story and Roof 


Supporting ICF Second 
Story and Roof 


Minimum Wall Thickness (inches) 


3.59 


5.5 


3.59 


5.5 


3.59 


5.5 


20 


8 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


9 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


10 


#4@38 


#4@48 


#4@40 


#4@48 


#4@42 


#4@48 


30 


8 


#4@42 


#4@48 


#4@46 


#4@48 


#4@48 


#4@48 


9 


#4@32; #5@48 


#4@48 


#4@34; #5@48 


#4@48 


#4@34;#5@48 


#4@48 


10 


Design Required 


#4@48 


Design Required 


#4@48 


Design Required 


#4@48 


40 


8 


#4@30;#5@48 


#4@48 


#4@30;#5@48 


#4@48 


#4@32;#5@48 


#4@48 


9 


Design Required 


#4@42 


Design Required 


#4@46 


Design Required 


#4@48 


10 


Design Required 


#4@32; #5@48 


Design Required 


#4@34; #5@48 


Design Required 


#4@38 


50 


8 


#4 @ 20; #5 @ 30 


#4@42 


#4 @ 22; #5 @ 34 


#4@46 


#4@24;#5@36 


#4@48 


9 


Design Required 


#4@34;#5@48 


Design Required 


#4@34;#5@48 


Design Required 


#4@38 


10 


Design Required 


#4@26;#5@38 


Design Required 


#4@26;#5@38 


Design Required 


#4@28;#5@46 


60 


8 


Design Required 


#4@34;#5@48 


Design Required 


#4@36 


Design Required 


#4@40 


9 


Design Required 


#4@26;#5@38 


Design Required 


#4@28;#5@46 


Design Required 


#4@34;#5@48 


10 


Design Required 


#4@22;#5@34 


Design Required 


#4@22;#5@34 


Design Required 


#4@26;#5@38 


70 


8 


Design Required 


#4@28;#5@46 


Design Required 


#4@30;#5@48 


Design Required 


#4@34;#5@48 


9 


Design Required 


#4@22;#5@34 


Design Required 


#4@22;#5@34 


Design Required 


#4@24;#5@36 


10 


Design Required 


#4@16;#5@26 


Design Required 


#4@18;#5@28 


Design Required 


#4 @ 20; #5 @ 30 


80 


8 


Design Required 


#4@26;#5@38 


Design Required 


#4@26;#5@38 


Design Required 


#4@28; #5@46 


9 


Design Required 


#4@20;#5@30 


Design Required 


#4@20;#5@30 


Design Required 


#4@21;#5@34 


10 


Design Required 


#4 @ 14; #5 @ 24 


Design Required 


#4 @ 14; #5 @ 24 


Design Required 


#4@16;#5@26 



For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s; 1 pound per square inch = 6.895 kPa. 

a. This table is based on reinforcing bars with a minimum yield strength of 40,000 psi and concrete with a minimum specified compressive strength of 2,500 psi. For 
Seismic Design Categories Dq, Dj and D2, reinforcing bars shall have a minimum yield strength of 60,000 psi. See Section R611.6.2. 

b. Deflection criterion is L/240, where L is the height of the wall story in inches. 

c. Interpolation shall not be permitted. 

d. Reinforcement spacing for 3.5 inch walls shall be permitted to be multiplied by 1 .6 when reinforcing steel with a minimum yield strength of 60,000 psi is used. 
Reinforcement shall not be less than one #4 bar at 48 inches (1.2 m) on center 

e. Reinforcement spacing for 5.5 inch (139.7 mm) walls shall be permitted to be multiplied by 1 .5 when reinforcing steel with a minimum yield strength of 60,000 psi 
is used. Reinforcement shall not be less than one #4 bar at 48 inches on center 

f. See Section R61 1 .7. 1 .2 for limitations on maximum spacing of \ertical reinforcement in Seismic Design Categories C, Dq, Dj and D2. 

g. A 3.5-inch wall shall not be permitted if wood ledgers are used to support floor or roof loads. See Section R61 1.8. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



195 



WALL CONSTRUCTION 



TABLE R61 1.4(1) 
MINIMUM VERTICAL WALL REINFORCEMENT FOR WAFFLE-GRID ICF ABOVE-GRADE WALLS^" = 



Design Wind 
Pressure [Table 
R611.3(1)](psf) 


Maximum 

Unsupported Wall 

Height (feet) 


MINIMUIVI VERTICAL REINFORCEMENT^' ^ 


Nonload-Bearing Wall or 
Supporting Roof 


Supporting Light-Framed Second 
Story and Roof 


Supporting ICF Second 
Story and Roof 


Minimum Wall Thickness (inches) 


6 


8 


6 


8 


6 


8 


20 


8 


#4@48 


#4@48 


: #4@48 


#4@48 


#4@48 


#4@48 


9 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


10 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


30 


8 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


9 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


10 


#4@36;#5@48 


#4@48 


#4@36;#5@48 


#4@48 


#4@36;#5@48 


#4@48 


40 


8 


#4@36;#5@48 


#4@48 


#4@48 


#4@48 


#4@48 


#4@48 


9 


#4@36;#5@48 


#4@48 


#4@36;#5@48 


#4@48 


#4@36;#5@48 


#4@48 


10 


#4 @ 24; #5 @ 36 


#4@36;#5@48 


#4@24;#5@36 


#4@48 


#4@24; #5@36 


#4@48 


50 


8 


#4@36;#5@48 


#4@48 


#4@36;#5@48 


#4@48 


#4@36;#5@48 


#4@48 


9 


#4@24;#5@36 


#4@36;#5@48 


#4@24;#5@36 


#4@48 


#4@24;#5@48 


#4@48 


10 


Design Required 


#4@36;#5@48 


Design Required 


#4@36;#5@48 


Design Required 


#4@36;#5@48 


60 


8 


#4@24;#5@36 


#4@48 


#4@24;#5@36 


#4@48 


#4@24;#5@48 


#4@48 


9 


Design Required 


#4@36;#5@48 


Design Required 


#4@36;#5@48 


Design Required 


#4@36;#5@48 


10 


Design Required 


#4@24;#5@36 


Design Required 


#4 @ 24; #5 @ 36 


Design Required 


#4@24;#5@48 


70 


8 


#4@24;#5@36 


#4@36;#5@48 


#4@24;#5@36 


#4@36;#5@48 


#4@24;#5@36 


#4@48 


9 


Design Required 


#4@24;#5@36 


Design Required 


#4@24;#5@48 


Design Required 


#4@24;#5@48 


10 


Design Required 


#4@12;#5@36 


Design Required 


#4 @ 24; #5 @ 36 


Design Required 


#4 @ 24; #5 @ 36 


80 


8 


#4@12;#5@24 


#4@24; #5@48 


#4@12;#5@24 


#4@24;#5@48 


#4@12;#5@24 


#4@36;#5@48 


9 


Design Required 


#4@24;#5@36 


Design Required 


#4@24;#5@36 


Design Required 


#4@24; #5@36 


10 


Design Required 


#4@12;#5@24 


Design Required 


#4@12;#5@24 


Design Required 


#4@12;#5@24 



For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 mile per hour = 0.447 m/s; 1 pound per square inch = 6.895 MPa. 

I a. This table is based on reinforcing bars with a minimum yield strength of 40,000 psi and concrete with a minimum specified compressive strength of 2,500 psi. For 
Seismic Design Categories Dg, Dj and D2, reinforcing bars shall have a minimum yield strength of 60,000 psi. See Section R61 1.6.2. 

b. Deflection criterion is L/240, where L is the height of the wall story in inches. 

c. Interpolation shall not be permitted. 

d. Increasing reinforcement spacing by 1 2 inches shall be permitted when reinforcing steel with a minimum yield strength of 60,000 psi is used or substitution of No. 
4 reinforcing bars for #5 bars shall be permitted when reinforcing steel with a minimum yield strength of 60,000 psi is used at the same spacing required for #5 bars. 
Reinforcement shall not be less than one #4 bar at 48 inches on center 

I e. See Section R61 1 .7. 1 .2 for limitations on maximum spacing of \ertical reinforceihent in Seismic Design Categories C, Dq, D, and D2. 



^L^ 2IN. MIN. 

tP concrete web 



INSULATING 
FORM 




VERTICAL REINFORCEMENT 
IF REQUIRED 



HORIZONTAL CONCRETE CORE 
(HIDDEN) AT 16 IN. O.C. MAX. 



VERTICAL 
CONCRETE CORE 




INSUUVTING FORM 



PLAN VIEW 



ISOMETRIC VIEW 
WAFFLE ICF WALL SYSTEM 



FIGURE R6il1. 4 
WAFFLE-GRID ICF WALL SYSTEM 



196 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



WALL CONSTRUCTION 



TABLE R61 1.5 
MINIMUM VERTICAL WALL REINFORCEMENT FOR SCREEN-GRID ICF ABOVE-GRADE WALLS^"'' 



DESIGN WIND PRESSURE 

[TABLE R61 1.3(1)] 

(psf) 


MAXIMUM UNSUPPORTED 

WALL HEIGHT 

(feet) 


MINIMUM VERTICAL REINFORCEMENr''^ 


Nonload-Bearing Wall or 
Supporting Roof 


Supporting Light-Framed 
Second Story and Roof 


Supporting ICF Second 
Story and Roof 


20 


8 


#4@48 


#4@48 


#4@48 


9 


#4@48 


#4@48 


#4@48 


10 


#4@48 


#4@48 


#4@48 


30 


8 


#4@48 


#4@48 


#4@48 


9 


#4@48 


#4@48 


#4@48 


10 


#4@36; #5@48 


#4@48 


#4@48 


40 


8 


#4@48 


#4@48 


#4@48 


9 


#4@36;#5@48 


#4@36;#5@48 


#4@48 


10 


#4@24;#5@48 


#4@24;#5@48 


#4@24;#5@48 


50 


8 


#4@36;#5@48 


#4@36;#5@48 


#4@48 


9 


#4@24;#5@48 


#4@24;#5@48 


#4@24;#5@48 


10 


Design Required 


Design Required 


Design Required 


60 


8 


#4@24;#5@48 


#4@24;#5@48 


#4@36;#5@48 


9 


#4 @ 24; #5 @ 36 


#4 @ 24; #5 @ 36 


#4@24;#5@36 


10 


Design Required 


Design Required 


Design Required 


70 


8 


#4 @ 24; #5 @ 36 


#4 @ 24; #5 @ 36 


#4 @ 24; #5 @ 36 


9 


Design Required 


Design Required 


Design Required 


10 


Design Required 


Design Required 


Design Required 


080 


8 


#4@12;#5@36 


#4@24; #5@36 


#4@24;#5@36 


9 


Design Required 


Design Required 


Design Required 


10 


Design Required 


Design Required 


Design Required 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s; 1 pound per square inch = 6.895 kPa. 

a. This table is based on reinforcing bars with a minimum yield strength of 40,000 psi and concrete with a minimum specified compressive strength of 2,500 psi . For I 
Seismic Design Categories Dq, D, and D2, reinforcing bars shall have a minimum yield strength of 60,000 psi. See Section R61 1.6.2. I 

b. Deflection criterion is L/240, where L is the height of the wall story in inches. 

c. Interpolation shall not be permitted. 

d. Increasing reinforcement spacing by 1 2 inches shall be permitted when reinforcing steel with a minimum yield strength of 60,000 psi is used. Reinforcement shall 
not be less than one #4 bar at 48 inches on center 

e. See Section R61 1.7.1.2 for limitations on maximum spacing of vertical reinforcement in Seismic Design Categories C, Dg, Dj and D2. I 



INSULATING 
FORM 



\^^ 




12 IN. MAX 



VERTICAL REINFORCEMENT 
F REQUIRED 

HORIZONTAL CONCRETE CORE 
(HIDDEN) AT 12 IN. O.C. MAX. 



VERTICAL 
CONCRETE CORE 



VOIDS 




INSULATING FORM 



PLAN VIEW 



ISOMETRIC VIEW 
SCREEN-GRID IFC WALL SYSTEM 



For SI: 1 inch = 25.4 mm. 



FIGURE R611. 5 
SCREEN-GRID IFC WALL SYSTEM 



2006 INTERNATIONAL RESIDENTIAL CODE® 



197 



WALL CONSTRUCTION 



R61 1.6.3 Insulation materials. Insulating concrete 
forms material shall meet the surface burning character- 
istics of Section R314.3. A thermal barrier shall be pro- 
vided on the building interior in accordance with Section 
R314.4 or Section R702.3.4. 

R611.7 Wall construction. Insulating concrete form walls 
shall be constructed in accordance with the provisions of this 
section and Figure R61 1.7(1). 

R611.7.1 Reinforcement. 

R611.7.1.1 Location. Vertical and horizontal wall rein- 
forcement shall be placed within the middle third of the 
wall. Steel reinforcement shall have a minimum con- 
crete cover in accordance with ACI 318. 

Exception: Where insulated concrete forms are used 
and the form remains in place as cover for the concrete, 
the minimum concrete cover for the reinforcing steel is 
permitted to be reduced to '^1^ inch (19 mm). 

R61 1.7.1.2 Vertical steel. Above-grade concrete walls 
shall have reinforcement in accordance with Sections 
R611.3, R611.4, or R611.5 and R61 1.7.2. Where the 
design wind pressure exceeds 40 psf (1.92 kPa) in accor- 
dance with Table R61 1.3(1) or for townhouses in Seismic 
Design Category C and all buildings in Seismic Design 
Categories Dq, Dj and Dj, vertical wall reinforcement in 
the top-most ICF story shall terminate with a 90-degree 
(1.57 rad) standard hook in accordance with Section 
R6 11.7.1.5. The free end of the hook shall be within 4 
inches (102 mm) of the top of the ICF wall and shall be ori- 
ented parallel to the horizontal steel in the top of the wall. 

For townhouses in Seismic Design Category C, the 
minimum vertical reinforcement shall be one No. 5 bar at 
24 inches (610 mm) on center or one No. 4 at 16 inches 
(407 mm) on center. For all buildings in Seismic Design 
Categories Dq, D, and D2, the minimum vertical rein- 
forcement shall be one No. 5 bar at 18 inches (457 mm) 
on center or one No. 4 at 12 inches (305 mm) on center. 

Above-grade ICF walls shall be supported on concrete 
foundations reinforced as required for the above-grade 
wall immediately above, or in accordance with Tables 
R404.4(l) through R404.4(5), whichever requires the 
greater amount of reinforcement. 

Vertical reinforcement shall be continuous from the 
bottom of the foundation wall to the roof. Lap splices, if 
required, shall comply with Section R61 1.7.1.4. Where 
vertical reinforcement in the above-grade wall is not con- 
tinuous with the foundation wall reinforcement, dowel 
bars with a size and spacing to match the vertical ICF 
wall reinforcement shall be embedded 40 d^ into the 
foundation wall and shall be lap spliced with the 
above-grade wall reinforcement. Alternatively, for No. 6 
and larger bars, the portion of the bar embedded in the 
foundation wall shall be embedded 24 inches in the foun- 
dation wall and shall have a standard hook. 

R611.7.1.3 Horizontal reinforcement. Concrete walls 
with a minimum thickness of 4 inches (102 mm) shall 
have a minimum of one continuous No. 4 horizontal rein- 
forcing bar placed at 32 inches (812 mm) on center with 



one bar within 12 inches (305 mm) of the top of the wall 
story. Concrete walls 5.5 inches (140 mm) thick or more 
shall have a minimum of one continuous No. 4 horizontal 
reinforcing bar placed at 48 inches (1219 mm) on center 
with one bar located within 12 inches (305 mm) of the 
top of the wall story. 

For townhouses in Seismic Design Category C, the 
minimum horizontal reinforcement shall be one No. 5 
bar at 24 inches (610 mm) on center or one No. 4 at 16 
inches (407 mm) on center. For all buildings in Seismic 
Design Categories D,,, D, and D2, the minimum horizon- | 
tal reinforcement shall be one No. 5 bar at 1 8 inches (457 
mm) on center or one No. 4 at 12 inches (305 mm) on 
center. 

Horizontal reinforcement shall be continuous around 
building comers using comer bars or by bending the 
bars. In either case, the minimum lap splice shall be 24 
inches (610 mm). For townhouses in Seismic Design 
Category C and for all buildings in Seismic Design Cate- 
gories Dq, D 1 and D2, each end of all horizontal reinforce- | 
ment shall terminate with a standard hook or lap splice. 

R611.7.1.4 Lap splices. Where lap splicing of vertical 
or horizontal reinforcing steel is necessary, the lap 
splice shall be in accordance with Figure R61 1.7.1.4 
and a minimum of 40 d^, where d^ is the diameter of the 
smaller bar. The maximum distance between 
noncontact parallel bars at a lap splice shall not exceed 
8db. 

R611.7.1.5 Standard hook. Where the free end of a 
reinforcing bar is required to have a standard hook, the 
hook shall be a 1 80-degree bend plus 4 d^, extension but 
not less than 2V2 inches, or a 90-degree bend plus 12 d^ 
extension. 

R611.7.2 Wall openings. Wall openings shall have a mini- 
mum of 8 inches (203 mm) of depth of concrete for flat and 
waffle-grid ICF walls and 12 inches (305 mm) for 
screen-grid walls over the length of the opening. When the 
depth of concrete above the opening is less than 12 inches for 
flat or waffle-grid walls, lintels in accordance with Section 
R61 1 .7.3 shall be provided. Reinforcement around openings 
shaU be provided in accordance with Table R6 11.7(1) and 
Figure R61 1.7(2). Reinforcement placed horizontally above 
or below an opening shall extend a minimum of 24 inches 
(610 mm) beyond the limits of the opening. Wall opening 
reinforcement shall be provided in addition to the reinforce- 
ment required by Sections R611.3, R611.4, R611.5 and 
R61 1 .7. 1 . The perimeter of all wall openings shall be framed 
with a minimum 2-inch by 4-inch plate, anchored to the wall 
with 72-inch (13 mm) diameter anchor bolts spated a maxi- 
mum of 24 inches (610 mm) on center. The bolts shall be 
embedded into the concrete a minimum of 4 inches (102 mm) 
and have a minimum of 1 Vj inches (38 mm) of concrete cover 
to the face of the wall. 

Exception: The 2-inch by 4-inch plate is not required 
where the wall is formed to provide soUd concrete around 
the perimeter of the opening with a minimum depth of 4 
inches (102 mm) for the full thickness of the wall. 



198 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R61 1.7(1) 
MINIMUM WALL OPENING REINFORCEMENT REQUIREMENTS IN ICF WALLS' 



WALL TYPE AND 
OPENING WIDTH (L) (feet) 


MINIMUM HORIZONTAL 
OPENING REINFORCEMENT 


MINIMUM VERTICAL 
OPENING REINFORCEMENT 


Flat, Waffle-, and 

Screen-Grid: 

L<2 


None required 


None required 


Flat, Waffle-, and 

Screen-Grid: 

L>2 


Provide lintels in accordance with Section R61 1.7.3. 
Provide one No. 4 bar within 12 inches from the 
bottom of the opening. Top and bottom lintel 
reinforcement shall extend a minimum of 24 inches 
beyond the Umits of the opening. 


In locations with wind speeds less than or equal to 110 mph 
or in Seismic Design Categories A and B, provide one No. 4 
bar for the full height of the wall story within 12 inches of 
each side of the opening. 

In locations with wind speeds greater than 110 mph, 
townhouses in Seismic Design Category C, or all buildings 
in Seismic Design Categories Dq, Dj and Dj, provide two 
No. 4 bars or one No. 5 bar for the full height of the wall 
story within 12 inches of each side of the opening. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 mJs; 1 pound per square inch = 6.895 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accor- 
dance with ACI 31 8. 



SEE FIGURE 
R611.9 




LIGHT-FRAME ROOF 



SEE FIGURES 
R611.8(1) 
THROUGH 
R611.8(7) 




ICF OR LIGHT-FRAME 
WALL 



SEE FIGURES" 
R611.8(1) 
THROUGH 
R611.8(7) 



/" 




2ND STORY 
WALL HEIGHT 
10 FT MAX. 



i^^ 



LIGHT-FRAME FLOOR 



1ST STORY 
WALL HEIGHT 
10 FT MAX. 



LIGHT-FRAME FLOOR 

(OR CONCRETE SLAB-ON-GRADE) 



BASEMENT, CRAWL SPACE, OR 
SLAB-ON-GRADE FOUNDATION 



For SI: 1 foot = 304.8 mm. 

NOTE: Section cut through flat wall or vertical core of waffle- or screen-grid walls. 



FIGURE R61 1.7(1) 
ICF WALL CONSTRUCTION 



2006 INTERNATIONAL RESIDENTIAL CODE® 



199 



WALL CONSTRUCTION 



R61 1.7.3 Lintels. 

R611.7.3.1 General requirements. Lintels shall be 
provided over all openings greater than or equal to 2 feet 
(610 mm) in width. Lintels for flat ICF walls shall be 
constructed in accordance with Figure R61 1.7(3) and 
Table R61 1.7(2) or R61 1.7(3). Lintels for waffle-grid 
ICF walls shall be constructed in accordance with Fig- 
ure R61 1.7(4) or Figure R61 1.7(5) and Table 
R611.7(4) or R611.7(5). Lintels for screen-grid ICF 
walls shall be constructed in accordance with Figure 
R611.7(6) or Figure R611.7(7). Lintel construction in 
accordance with Figure R611.7(3) shall be permitted 
with waffle-grid and screen-grid ICF wall construction. 
Lintel depths are permitted to be increased by the height 
of the ICF wall located directly above the opening, pro- 
vided that the lintel depth spans the entire length of the 
opening. 

R611.7.3.2 Stirrups. Where required, No. 3 stirrups 
shall be installed in flat, waffle-grid and screen-grid 
wall lintels in accordance with the following: 

1 . For flat walls the stirrups shall be spaced at a max- 
imum spacing of d/1 where d equals the depth of 
the lintel (D) minus the bottom cover of concrete 
as shown in Figure R6 11.7(3). Stirrups shall not 
be required in the middle portion of the span (A) 
per Figure R61 1.7(2), for flat walls for a length 
not to exceed the values shown in parenthesis in 
Tables R6 11.7(2) and R6 11.7(3) or for spans in 
accordance with Table R61 1.7(8). 

2. For waffle-grid walls a minimum of two No. 3 
stirrups shall be placed in each vertical core of 
waffle-grid lintels. Stirrups shall not be required 
in the middle portion of the span (A) per Figure 
R61 1.7(2), for waffle-grid walls for a length not 
to exceed the values shown in parenthesis in 
Tables R61 1.7(4) and R61 1.7(5) or for spans in 
accordance with Table R61 1 .7(8). 

3. For screen-grid walls one No. 3 stirrup shall be 
placed in each vertical core of screen-grid lintels. 

Exception: Stirrups are not required in 
screen-grid lintels meeting the following 
requirements: 

1 . Lintel Depth (D) = 12 inches (305 mm) - 
spans less than or equal 3 feet 7 inches. 

2. Lintel Depth (D) = 24 inches (610 mm) - 
spans less than or equal 4 feet 4 inches. 

R611.7.3.3 Horizontal reinforcement. One No. 4 hor- 
izontal bar shall be provided in the top of the lintel. Hor- 
izontal reinforcement placed within 12 inches (305 
mm) of the top of the wall in accordance with Section 
R61 1 .7. 1 .3 shall be permitted to serve as the top or bot- 
tom reinforcement in the lintel provided the reinforce- 
ment meets the location requirements in Figure 
R611.7(2), R611.7(3), R611.7(4), R611.7(5), 



R61 1.7(6), or R61 1.7(7), and the size requirements in 
Tables R61 1.7(2), R61 1.7(3), R61 1.7(4), R611.7(5), 
R611.7(6), R611.7(7), orR611.7(8). 

R611.7.3.4 Load-bearing walls. Lintels in flat ICF 
load-bearing walls shall comply with Table R61 1.7(2), 
Table RR611.7(3) or Table R61 1.7(8). Lintels in waf- 
fle-grid ICF load-bearing walls shall comply with Table 
R6 1 1 .7(4), Table R6 1 1 .7(5) or Table R6 1 1 .7(8). Lintels 
in screen-grid ICF load-bearing walls shall comply 
with Table R61 1.7(6) or Table R61 1.7(7). 

Where spans larger than those permitted in Table 
R6 11.7(2), Table R6 11.7(3), Table R6 11.7(4), Table 
R61 1.7(5), R61 1.7(6), R61 1.7(7) or R61 1.7(8) are 
required, the hntels shaU comply with Table R6 1 1 .7 (9). 

R611.7.3.5 Nonload-bearing walls. Lintels in 
nonload-bearing flat, waffle-grid and screen-grid ICF 
walls shall comply with Table R61 1.7 (10). Stirrups are 
not required. 

R61 1.7.4 Minimum length of wall without openings. The 

wind velocity pressures of Table R611.7.4 shall be used to 
determine the minimum amount of solid wall length in 
accordance with Tables R611.7(9A) through R611.7(10B) 
and Figure R611.7.4. Table R611.7(ll) shall be used to 
determine the minimum amount of solid wall length for 
townhouses in Seismic Design Category C, and all build- 
ings in Seismic Design Categories Dq, Dj and Dj for all | 
types of ICF walls. The greater amount of solid wall length 
required by wind loading or seismic loading shall apply. 
The minimum percentage of solid wall length shall include 
only those solid wall segments that are a minimum of 24 
inches (610 mm) in length. The maximum distance between 
wall segments included in determining solid wall length 
shall not exceed 18 feet (5486 mm). A minimum length of 
24 inches (610 mm) of solid wall segment, extending the 
full height of each wall story, shall occur at all interior and 
exterior comers of exterior walls. 

R611.8 ICF wall-to-floor connections. 

R611.8.1 Top bearing. Floors bearing on the top of ICF 

foundation walls in accordance with Figure R6 11.8(1) 
shall have the wood sill plate anchored to the ICF wall with 
minimum Vj-inch (13 mm) diameter bolts embedded a 
minimum of 7 inches (178 mm) and placed at a maximum 
spacing of 6 feet (1829 mm) on center and not more than 1 2 
I inches (305 mm) from corners. Anchor bolts for waf- 
fle-grid and screen-grid walls shall be located in the cores. 
In conditions where wind speeds are in excess of 90 miles 
per hour (40 m/s), the V2"inch (13 mm) diameter anchor 
bolts shall be placed at a maximum spacing of 4 feet (1219 
mm) on center. Bolts shall extend a minimum of 7 inches 
(178 mm) into concrete. Sill plates shall be protected 
against decay where required by Section R319. 
Cold-formed steel framing systems shall be anchored to 
the concrete in accordance with Section R505.3.1 or Sec- 
tion R603. 3.1. 



200 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



WALL CONSTRUCTION 



TABLE R61 1.7(2) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR ICF LINTELS FOR FLAT LOAD-BEARING WALLS"'' ^'" 

NO. 4 BOTTOM BAR SIZE 



MINIMUM LINTEL 

THICKNESS, T 

(inches) 


LINTEL DEPTH, D 
(inches) 


MAXIMUM CLEAR SPAN, (feet-inches) 
(Number is Middle of Span, A)^ 


Supporting Roof Only 


Supporting Light-Framed 
2nd Story and Roof 


Supporting ICF Second Story 
and Roof 


Ground Snow Load 


30psf 


70psf 


30psf 


70psf 


30psf 


70psf 


3.5 


8 


4-9 
(1-2) 


4-2 
(0-9) 


3-10 
(0-8) 


3-4 
(0-6) 


3-5 
(0-6) 


3-1 
(0-5) 


12 


6-8 
(1-11) 


5-5 
(1-3) 


5-0 
(1-1) 


4-5 
(0-10) 


4-6 
(0-10) 


4-0 
(0-8) 


16 


7-11 
(2-9) 


6-5 
(1-9) 


6-0 
(1-6) 


5-3 
(1-2) 


5-4 
(1-2) 


4-10 
(1-0) 


20 


8-11 
(3-5) 


7-4 
(2-3) 


6-9 
(1-11) 


6-0 
(1-6) 


6-1 

(1-7) 


5-6 

(1-3) 


24 


9-10 
(4-1) 


8-1 
(2-9) 


7-6 
(2-4) 


6-7 
(1-10) 


6-9 
(1-11) 


6-1 
(1-6) 


5.5 


8 


5-2 
(1-10) 


4-2 
(1-2) 


3-10 
(1-0) 


3-5 
(0-9) 


3-5 
(0-10) 


3-1 
(0-8) 


12 


6-8 

(3-0) 


5-5 
(2-0) 


5-0 
(1-9) 


4-5 
(1-4) 


4-6 
(1-4) 


4-1 
(1-1) 


16 


7-10 
(4-1) 


6-5 

(2-9) 


6-0 

(2-5) 


5-3 
(1-10) 


5-4 
(1-11) 


4-10 
(1-7) 


20 


8-10 

(5-3) 


7-3 
(3-6) 


6-9 

(3-1) 


6-0 

(2-4) 


6-1 

(2-5) 


5-6 

(2-0) 


24 


9-8 
(6-3) 


8-0 

(4-3) 


7-5 
(3-8) 


6-7 
(2-11) 


6-8 
(3-0) 


6-0 

(2-5) 


7.5 


8 


5-2 
(2-6) 


4-2 
(1-8) 


3-11 
(1-5) 


3-5 
(1-1) 


3-6 

(1-1) 


3-2 
(0-11) 


12 


6-7 
(4-0) 


5-5 
(2-8) 


5-0 

(2-4) 


4-5 
(1-10) 


4-6 
(1-10) 


4-1 
(1-6) 


16 


7-9 

(5-5) 


6-5 
(3-8) 


5-11 

(3-3) 


5-3 
(2-6) 


5-4 
(2-7) 


4-10 

(2-2) 


20 


8-8 
(6-10) 


7-2 
(4-8) 


6-8 

(4-2) 


5-11 
(3-3) 


6-0 

(3-4) 


5-5 
(2-9) 


24 


9-6 

(8-2) 


7-11 
(5-8) 


7-4 
(5-1) 


6-6 

(3-11) 


6-7 
(4-1) 


6-0 

(3-4) 


9.5 


8 


5-2 
(3-1) 


4-2 
(2-1) 


3-11 
(1-9) 


3-5 
(1-5) 


3-6 

(1-5) 


3-2 
(1-2) 


12 


6-7 
(5-0) 


5-5 
(3-4) 


5-0 
(3-0) 


4-5 
(2-4) 


4-6 

(2-5) 


4-1 
(1-11) 


16 


7-8 
(6-9) 


6-4 

(4-7) 


5-11 

(4-2) 


5-3 
(3-3) 


5-4 
(3-4) 


4-10 
(2-8) 



igth of 40,000 psi and an 
; in the shaded cells shall 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1 pound per square foot = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield stren^ 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used, the span lengths i 
be increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion: L/IAO. 

d. Design load assumptions: 

Floor dead load is 10 psf Attic live load is 20 psf 

Floor live load is 30 psf Roof dead load is 15 psf 

Building width is 32 feet ICF wall dead load is 69 psf 

Light-framed wall dead load is 10 psf 

e. No. 3 stirrups are required at d/2 spacing except no stirrups are required for the distance, (A), shown in the middle portion of the span in accordance with Figure 
R61 1.7(2) and Section R61 1.7 .3.2. 

f. Interpolation is permitted between ground snow loads and between lintel depths. 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



201 



WALL CONSTRUCTION 



TABLE R61 1.7(3) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR ICF LINTELS FOR FLAT LOAD-BEARING WALLS"- "'=''•* 

NO. 5 BOTTOM BAR SIZE 



MINIMUM LINTEL 

THICKNESS, T 

(inches) 


LINTEL DEPTH, D 
(inches) 


MAXIMUM CLEAR iSPAN, (feet-Inches) (Number is Middle of Span, A)^ 


Supporting Roof 


Supporting Light-Framed 2nd Story 
and Roof 


Supporting ICF Second Story and 
Roof 


Ground Snow Load 


30psf 


70psf 


30psf 


70psf 


30psf 


70psf 


3.5 


8 


4-9 
(1-2) 


4-2 
(0-9) 


3-11 
(0-8) 


3-7 
(0-6) 


3-7 
(0-6) 


3-5 
(0-5) 


12 


7-2 
(1-11) 


6-3 

(1-3) 


5-11 

(1-1) 


5-5 
(0-10) 


5-5 
(0-10) 


5-0 
(0-8) 


16 


9-6 

(2-9) 


8-0 
(1-9) 


7-4 
(1-6) 


6-6 

(1-2) 


6-7 
(1-2) 


5-11 
(1-0) 


20 


11-1 

(3-5) 


9-1 

(2-3) 


8-4 
(1-11) 


I 7-5 
i(l-6) 


7-6 
(1-7) 


6-9 

(1-3) 


24 


12-2 
(4-1) 


10-0 
(2-9) 


9-3 

(2-4) 


i 8-2 
1(1-10) 


8-4 
(1-11) 


7-6 
(1-6) 


5.5 


8 


5-6 
(MO) 


4-10 
(1-2) 


4-7 
(1-0) 


4-2 
(0-9) 


4-2 
(0-10) 


3-10 
(0-8) 


12 


8-3 
(3-0) 


6-9 

(2-0) 


6-3 
(1-9) 


5-6 

(1-4) 


5-7- 
(1-4) 


5-0 
(1-1) 


16 


9-9 

(4-1) 


8-0 
(2-9) 


7-5 
(2-5) 


'■ 6-6 

!(i-io) 


6-7 
(1-11) 


6-0 

(1-7) 


20 


10-11 

(5-3) 


9-0 

(3-6) 


8-4 
(3-1) 


; 7-5 

K2-4) 


7-6 
(2-5) 


6-9 

(2-0) 


24 


12-0 
(6-3) 


9-11 

(4-3) 


9-3 

(3-8) 


! 8-2 
1(2-11) 


8-3 
(3-0) 


7-6 

(2-5) 


7.5 


8 


6-1 

(2-6) 


5-2 
(1-8) 


4-9 
: (1-5) 


4-3 
(1-1) 


4-3 
(1-1) 


3-10 
(0-11) 


12 


8-2 
(4-0) 


6-9 

(2-8) 


6-3 

(2-4) 


:5-6 

id-lO) 


5-7 
(1-10) 


5-0 
(1-6) 


16 


9-7 
(5-5) 


7-11 
(3-8) 


7-4 
(3-3) 


= 6-6 
k2-6) 


6-7 
(2-7) 


6-0 

(2-2) 


20 


10-10 
(6-10) 


8-11 
(4-8) 


8-4 
(4-2) 


\ 7-4 
1(3-3) 


7-6 
(3-4) 


6-9 

(2-9) 


24 


11-10 
(8-2) 


9-10 

(5-8) 


9-2 
(5-1) 


: 8-1 

=(3-11) 


8-3 
(4-1) 


7-5 
(3-4) 


9.5 


8 


6-4 
(3-1) 


5-2 
(2-1) 


4-10 
(1-9) 


■ 4-3 
(1-5) 


4-4 
(1-5) 


3-11 
(1-2) 


12 


8-2 
(5-0) 


6-8 

(3-4) 


6-2 
(3-0) 


5-6 

:(2-4) 


5-7 
(2-5) 


5-0 
(1-11) 


16 


9-6 
(6-9) 


7-11 
(4-7) 


7-4 
(4-2) 


\ 6-6 
! (3-3) 


6-7 

(3-4) 


5-11 
(2-8) 


20 


10-8 

(8-4) 


8-10 
(5-10) 


8-3 
(5-4) 


] 7-4 
!(4-2) 


7-5 
(4-3) 


6-9 

(3-6) 


24 


11-7 
(10-0) 


9-9 

(6-11) 


9-0 

(6-5) 


\ 8-1 
■(5-0) 


8-2 
(5-2) 


7-5 
(4-3) 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 pound per square foot = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used the span lengths in the shaded cells shall be 
increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion: L/240. 

d. Design load assumptions: 

Floor dead load is 10 psf Attic live load is 20 psf 

Floor live load is 30 psf Roof dead load is 15 psf ' 

Building width is 32 feet ICF wall dead load is 69 psf 

Light-framed wall dead load is 10 psf j 

e. No. 3 stirrups are required at d/2 spacing except no stirrups are required for the distance, (A), shown in the middle portion of the span in accordance with Figure 
R611.7(2) and Section R61 1.7.3.2. I 

{. Interpolation is permitted between ground snow loads and between lintel depths.; 



202 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



TABLE R61 1.7(4) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR WAFFLE-GRID ICF WALL LINTELS^' "■=■"■' 

NO. 4 BOTTOM BAR SIZE 



NOMINAL LINTEL 

THICKNESS TS" 

(Inches) 


LINTEL 
DEPTH D 
(inches) 


MAXIMUM CLEAR SPAN (feet-lnches) 
(Number is Middle of Span, Af 


Supporting Roof 


Supporting Light-Framed 2nd Story 
and Roof 


Supporting ICF Second Story and 
Roof 


Ground Snow Load 


30psf 


70psf 


30psf 


70psf 


30psf 


70psf 


6 


8 


5-2 
(0-10) 


4-2 
(0-7) 


3-10 
(0-6) 


3-5 
(0-4) 


3-6 
(0-5) 


3-2 
(0-4) 


12 


6-8 

(1-5) 


5-5 
(0-11) 


5-0 
(0-9) 


4-5 
(0-7) 


4-7 
(0-8) 


4-2 
(0-6) 


16 


7-11 
(1-11) 


6-6 

(1-4) 


6-0 
(1-1) 


5-3 
(0-10) 


5-6 
(0-11) 


4-11 
(0-9) 


20 


8-11 
(2-6) 


7-4 
(1-8) 


6-9 

(1-5) 


6-0 
(1-1) 


6-3 

(1-2) 


5-7 
(0-11) 


24 


9-10 

(3-0) 


8-1 
(2-0) 


7-6 
(1-9) 


6-7 
(1-4) 


6-10 
(1-5) 


6-2 

(1-2) 


8 


8 


5-2 
(0-10) 


4-3 
(0-7) 


3-11 
(0-6) 


3-5 
(0-4) 


3-7 
(0-5) 


3-2 
(0-4) 


12 


6-8 

(1-5) 


5-5 
(0-11) 


5-1 
(0-9) 


4-5 
(0-7) 


4-8 
(0-8) 


4-2 
(0-6) 


16 


7-10 
(1-11) 


6-5 

(1-4) 


6-0 

(1-1) 


5-3 
(0-10) 


5-6 
(0-11) 


4-11 
(0-9) 


20 


8-10 
(2-6) 


7-3 
(1-8) 


6-9 

(1-5) 


6-0 
(1-1) 


6-2 

(1-2) 


5-7 
(0-11) 


24 


9-8 
(3-0) 


8-0 
(2-0) 


7-5 
(1-9) 


6-7 

(1-4) 


6-10 

(1-5) 


6-2 
(1-2) 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 psf = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used the span lengths in the shaded cells shall be 
increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion: L/240. 

d. Design load assumptions: 

Floor dead load is 10 psf Attic live load is 20 psf 

Floor live load is 30 psf Roof dead load is 15 psf 

Building width is 32 feet ICF wall dead load is 55 psf 

Light-framed wall dead load is 10 psf 

e. No. 3 stirrups are required at d/2 spacing except no stirrups are required for the distance, (A), shown in the middle portion of the span in accordance with Figure 
R611.7(2) and Section R611. 7.3.2. 

f. Interpolation is permitted between ground snow loads and between lintel depths. 

g. For actual wall lintel width, refer to Table R61 1.2. | 
h. Lintel width corresponds to the nominal waffle-grid ICF wall thickness with a minimum thickness of 2 inches. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



203 



WALL CONSTRUCTION 



TABLE R61 1.7(5) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR WAFFLE-GRID ICF WALL LINTELS"" = "' 

NO. 5 BOTTOM BAR SIZE 



NOMINAL LINTEL 

THICKNESS, T9'' 

(Inches) 


LINTEL DEPTH D 
(Inches) 


MAXIMUM CLEAR SPAN (feet-inches) 
(Number is Middle of Span, A)^ 


Supporting Roof 


Supporting Light-Framed 2nd Story Supporting ICF Second Story and 
and Roof Roof 


Ground Snow Load 


30psf 


70psf 


30psf 


70psf 


30psf 


70psf 


6 


8 


5-4 
(0-10) 


4-8 
(0-7) 


4-5 
' (0-6) 


4-1 
(0-4) 


4-5 
(0-5) 


3-10 
(0-4) 


12 


8-0 
(1-5) 


6-9 

(0-11) 


6-3 

; (0-9) 


5-6 

(0-7) 


6-3 
(0-8) 


5-1 
(0-6) 


16 


9-9 
(1-11) 


8-0 
(1-4) 


7-5 
(1-1) 


}6-6 
(0-10) 


7-5 
(0-11) 


6-1 
(0-9) 


20 


11-0 
(2-6) 


9-1 
(1-8) 


8-5 
(1-5) 


1 
i7-5 

h-1) 


8-5 
(1-2) 


6-11 
(0-11) 


24 


12-2 
(3-0) 


10-0 
(2-0) 


9-3 
(1-9) 


lS-2 

;(i-4) 


9-3 

(1-5) 


7-8 
(1-2) 


8 


8 


6-0 
(0-10) 


5-2 
(0-7) 


4-9 
(0-6) 


4-3 
(0-4) 


4-9 
(0-5) 


3-11 
(0-4) 


12 


8-3 
(1-5) 


6-9 
(0-11) 


6-3 
(0-9) 


. l5-6 
^0-7) 


6-3 

(0-8) 


5-2 
(0-6) 


16 


9-9 
(1-11) 


8-0 
(1-4) 


7-5 
(1-1) 


?6-6 
(0-10) 


7-5 
(0-11) 


6-1 

(0-9) 


20 


10-11 

(2-6) 


9-0 
(1-8) 


8-4 7-5 
(1-5) : (1-1) 


8-4 
(1-2) 


6-11 
(0-11) 


24 


12-0 
(3-0) 


9-11 

(2-0) 


9-2 ! 8-2 
: (1-9) i 11-4) 


9-2 
(1-5) 


7-8 
(1-2) 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 psf = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used the span lengths in the shaded cells shall be 
increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion: L/240. 

d. Design load assumptions: 

Floor dead load is 10 psf Attic live load is 20 psf 

Floor live load is 30 psf Roof dead load is 15 psf 

Building width is 32 feet ICF wall dead load is 53 psf 

Light-framed wall dead load is 10 psf 

e. No. 3 stirrups are required at d/2 spacing except no stirrups are required for the distance, (A), shown in the middle portion of the span in accordance with Figure 
R61 1.7(2) and Section R61 1.7.3.2. 

f Interpolation is permitted between ground snow loads and between lintel depths. ■ 

g. For actual wall lintel width, refer to Table R61 1.2. 

h. Lintel width corresponds to the nominal waffle-grid ICF wall thickness with a minimum thickness of 2 inches. 



204 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



TABLE R61 1.7(6) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR SCREEN-GRID ICF LINTELS IN LOAD-BEARING WALLS'- "'=' *^' '■ ^ 

NO. 4 BOTTOM BAR SIZE 



MINIMUM LINTEL 

THICKNESS, T 

(inches)'^' 


MINIMUM LINTEL 
DEPTH, D 
(inches) 


MAXIMUM CLEAR SPAN (feet-inches) 


Supporting Roof 


Supporting Light-Framed Second 
Story and Roof 


Supporting ICF Second Story and 
Roof 


Maximum Ground Snow Load (psf) 


30 


70 


30 


70 


30 


70 


6 


12 


3-7 


2-10 


2-5 


2-0 


2-0 


NA 


24 


9-10 


8-1 


7-6 


6-7 


6-11 


6-2 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 psf = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used the span lengths in the shaded cells shall be 
increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion: L/240. 
d Design load assumptions: 

Floor dead load is 10 psf 
Floor live load is 30 psf 
Maximum floor clear span is 32 ft 
Light- frame wall dead load is 10 psf 

e. Stirrup requirements: 
Stirrups are not required for lintels 12 inches deep. 
One No. 3 stirrup is required in each vertical core for lintels 24 inches deep. 

f. Interpolation is permitted between ground snow loads. 

g. Flat ICF lintels may be used in lieu of screen-grid lintels, 
h. For actual wall lintel width, refer to Table R61 1.2. 
i. Lintel width corresponds to the nominal screen-grid ICF wall thickness. 



Attic live load is 20 psf 
Roof dead load is 15 psf 
ICF wall dead load is 53 psf 



TABLE R61 1.7(7) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR SCREEN-GRID ICF LINTELS IN LOAD-BEARING WALLS'' "•=•"■ ^' '• ^ 

NO. 5 BOTTOM BAR SIZE 



MINIMUM LINTEL 

THICKNESS, T 

(inches)''' 


MINIMUM LINTEL 
DEPTH, D 
(inches) 


MAXIMUM CLEAR SPAN (feet-inches) 


Supporting Roof 


Supporting Light-Framed Second 
Story and Roof 


Supporting ICF Second Story and 
Roof 


Maximum Ground Snow Load (psf) 


30 


70 


30 


70 


30 


70 


6 


12 


3-7 


2-10 


2-5 


2-0 


2-0 


NA 


24 


12-3 


10-0 


9-3 


8-3 


8-7 


7-8 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1 pound per square foot = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used the span lengths in the shaded cells shall be 
increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturer's tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion: L/240. 
d. 



Attic live load is 20 psf 
Roof dead load is 15 psf 
ICF wall dead load is 53 psf 



Design load assumptions: 
Floor dead load is 10 psf 
Floor live load is 30 psf 
Maximum floor clear span is 32 ft 
Light-frame wall dead load is 10 psf 

e. Stirrup requirements: 

Stirrups are not required for lintels 12 inches deep. 

One No. 3 stirrup is required in each vertical core for lintels 24 inches deep 

f. Interpolation is permitted between ground snow loads. 

g. Flat ICF lintels may be used in Ueu of screen-grid Untels. 
h. For actual wall lintel width, refer to Table R61 1.2. 

i. Lintel width corresponds to the nominal screen-grid ICF wall thickness. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



205 



WALL CONSTRUCTION 



TABLE R61 1.7(8) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR ICF LINTELS WITHOUT STIRRUPS IN LOAD-BEARING WALLS^ ""= "'^ * a" 

(NO. 4 OR NO. 5) BOTTOM BAR SIZE 



MINIMUM LINTEL 

THICKNESS, T 

(inches) 


MINIMUM LINTEL 
DEPTH, D 
(inches) 


MAXIMUM CLEAR SPAN (feet-inches) 


Supporting Roof Only 


Sjupporting Light-Framed Second 
Story and Roof 


Supporting ICF Second Story and 
RoolF 


MAXIMUM GROUND SNOW LOAD (psf) 


30 


70 


30 


70 


30 


70 


Flat ICF Lintel 


3.5 


8 


2-6 


2-6 


2-6 


2-4 


2-5 


2-2 


12 


4-2 


4-2 


4-1 


3-10 


3-10 


3-7 


16 


4-11 


4-8 


4-6 


4-2 


4-2 


3-11 


20 


6-3 


5-3 


' 4-11 


4-6 


4-6 


4-3 


24 


7-7 


6-4 


, 6-0 


5-6 


5-6 


5-2 


5.5 


8 


2-10 


2-6 


; 2-6 


2-5 


2-6 


2-2 


12 


4-8 


4-4 


' 4-3 


3-11 


3-10 


3-7 


16 


6-5 


5-1 


4-8 


4-2 


4-3 


3-11 


20 


8-2 


6-6 


6-0 


5-4 


5-5 


5-0 


24 


9-8 


7-11 


7-4 


6-6 


6-7 


6-1 


7.5 


8 


3-6 


2-8 


2-7 


2-5 


2-5 


2-2 


12 


5-9 


4-5 


4-4 


4-0 


3-10 


3-7 


16 


7-9 


6-1 


5-7 


4-10 


4-11 


4-5 


20 


8-8 


7-2 


6-8 


5-11 


6-0 


5-5 


24 


9-6 


7-11 


'■ 7-4 


6-6 


6-7 


6-0 


9.5 


8 


4-2 


3-1 


: 2-9 


2-5 


2-5 


2-2 


12 


6-7 


5-1 


i 4-7 


3-11 


4-0 


3-7 


16 


7-10 


6-4 


' 5-11 


5-3 


5-4 


4-10 


20 


8-7 


7-2 


: 6-8 


5-11 


6-0 


5-5 


24 


9-4 


7-10 


' 7-3 


6-6 


6-7 


6-0 


Waffle-Grid ICF Lintel 


6 or 8 


8 


2-6 


2-6 


! 2-6 


2-4 


2-4 


, 2-2 


12 


4-2 


4-2 


1 4-1 


3-8 


3-9 


3-7 


16 


5-9 


5-8 


; 5-7 


5-1 


5-2 


4-8 


20 


7-6 


7-4 


1 6-9 


6-0 


6-3 


5-7 


24 


9-2 


8-1 


1 7-6 


6-7 


6-10 


6-2 



For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot = 0.0479 kPa; 1 pound per square inch = 6.895 kPa. 

a. Table values are based on tensile reinforcement with a minimum yield strength of 40,000 psi (276 MPa), concrete with a minimum specified compressive strength 
of 2,500 psi, and a building width (clear span) of 32 feet. , 

b. Spans located in shaded cells shall be permitted to be multiplied by 1 .05 when concrete with a minimum compressive strength of 3,000 psi is used or by 1 . 1 when 
concrete with a minimum compressive strength of 4,000 psi is used. 

c. Deflection criterion is L/240, where L is the clear span of the lintel in inches. ' 

d. Linear interpolation shall be permitted between ground snow loads and between lintel depths. 

e. Lintel depth, D, shall be permitted to include the available height of ICF wall located directly above the lintel, provided that the increased lintel depth spans the 
entirelength of the opening. 

f. Spans shall be permitted to be multiplied by 1.05 for a building width (clear span) of 28 feet. 

g. Spans shall be permitted to be multiphed by 1.1 for a building width (clear span) bf 24 feet or less, 
h. ICF wall dead load is 69 psf. 



206 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



TABLE R61 1.7(9) 
MINIMUM BOTTOM BAR ICF LINTEL REINFORCEMENT FOR LARGE CLEAR SPANS IN LOAD-BEARING WALLS^ "■'=•'' ^' '■ '^ 


MINIMUM LINTEL 

THICKNESS, T*'9 

(inches) 


MINIMUM LINTEL 
DEPTH, D 
(inches) 


MINIMUM BOTTOM LINTEL REINFORCEMENT 


Supporting Light-Frame Roof Only 


Supporting Light-Framed Second 
Story and Roof 


Supporting ICF Second Story and 
Light-Frame Roof 


Maximum Ground Snow Load (psf) 


30 


70 


30 


70 


30 


70 


Flat ICF Lintel, 12 feet- 3 inches Maximum Clear Span 


3.5 


24 


1#5 


1#7 


D/R 


D/R 


D/R 


D/R 


5.5 


20 


1#6 


1#7 


D/R 


D/R 


D/R 


D/R 


24 


1#5 


1#7 


1#7 


1#8 


1#8 


D/R 


7.5 


16 


1#7;2#5 


D/R 


D/R 


D/R 


D/R 


D/R 


20 


1 #6; 2 #4 


1#7; 2 #5 


1 #8; 2 #6 


D/R 


D/R 


D/R 


24 


1 #6; 2 #4 


1 #7; 2 #5 


1 #7; 2 #5 


1 #8; 2 #6 


1 #8; 2 #6 


1 #8; 2 #6 


9.5 


16 


1 #7; 2 #5 


D/R 


D/R 


D/R 


D/R 


D/R 


20 


1 #6; 2 #4 


1 #7; 2 #5 


1 #8; 2 #6 


1 #8; 2 #6 


1 #8; 2 #6 


1 #9; 2 #6 


24 


1 #6; 2 #4 


1 #7; 2 #5 


1 #7; 2 #5 


1 #7; 2 #6 


1 #8; 2 #6 


1 #9; 2 #6 


Flat ICF Lintel, 16 feet-3 inches Maximum Clear Span 


5.5 


24 


1#7 


D/R 


D/R 


D/R 


D/R 


D/R 


7.5 


24 


1 #7; 2 #5 


D/R 


D/R 


D/R 


D/R 


D/R 


9.5 


24 


1 #7; 2 #5 


1 #9; 2 #6 


1 #9; 2 #6 


D/R 


D/R 


D/R 


Waffle-Grid ICF Lintel, 12 feet-3 inches Maximum Clear Span 


6 


20 


1#6 


D/R 


D/R 


D/R 


D/R 


D/R 


24 


1#5 


1 #7; 2 #5 


1 #7; 2 #5 


1 #8; 2 #6 


1 #8; 2 #6 


D/R 


8 


16 


1 #7; 2 #5 


D/R 


D/R 


D/R 


D/R 


D/R 


20 


1 #6; 2 #4 


1 #7; 2 #5 


1 #8; 2 #6 


D/R 


D/R 


D/R 


24 


1#5 


1 #7; 2 #5 


1 #7; 2 #5 


1 #8; 2 #6 


1 #8; 2 #6 


1 #8; 2 #6 


Screen-Grid ICF Lintel, 12 feet-3 inches Maximum Clear Span 


6 


24 


1#5 


1#7 


D/R 


D/R 


D/R 


D/R 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 psf = 0.0479 kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. When reinforcement with a minimum yield strength of 60,000 psi is used the span lengths in the shaded cells shall be 
increased by 1.2 times the table values. 

b. This table is not intended to prohibit the use of ICF manufacturers tables based on engineering analysis in accordance with ACI 318. 

c. D/R indicates design is required. 

d. Deflection criterion: L/240. 

e. Interpolation is permitted between ground snow loads and between lintel depths. 

f. No. 3 stirrups are required a maximum d/2 spacing for spans greater than 4 feet. 

g. Actual thickness is shown for flat hntels; nominal thickness is given for waffle-grid and screen-grid lintels. Lintel thickness corresponds to the nominal waffle-grid 
and screen-grid ICF wall thickness. Refer to Table R61 1.2 for actual wall thickness. 

h. ICF wall dead load varies based on wall thickness using 150 pcf concrete density. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



207 



WALL CONSTRUCTION 



TABLE R61i.7(9A) 
MINIMUM SOLID END WALL LENGTH REQUIREMENTS FOR FLAT ICF WALLS (WIND PERPENDICULAR TO RIDGE)^ 



WALL CATEGORY 


BUILDING 

SIDE WALL 

LENGTH, L 

(feet) 


Roof 
Slope 


WIND VELOCITY PRESSURE FROM TABLE R61 1.7.4 (psf) 


20 


25 


30 


35 


40 


45 


50 


60 


Minimum Solid Wall Length on Building End Wall (feet) 


One-Story or Top Story 
of Two-Story 


16 


<1:12 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


5:12 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


4.25 


4.50 


7:12'* 


4.00 


4.25 


'4.25 


4.50 


4.75 


4.75 


5.00 


5.50 


12:12'' 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


5.75 


6.25 


24 


<1:12 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


4.25 


4.50 


5:12 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


4.50 


4.75 


7:12'' 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


5.75 


6.25 


12:12'' 


4.75 


5.00 


5.25 


5.75 


6.00 


6.50 


6.75 


7.50 


32 


< 1:12 


4.00 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


4.75 


5:12 


4.00 


4.00 


^4.25 


4.50 


4.50 


4.75 


5.00 


5.25 


7:12" 


4.50 


5.00 


,5.25 


5.50 


6.00 


6.25 


6.50 


7.25 


12:12'' 


5.00 


5.50 


'6.00 


6.50 


7.00 


7.25 


7.75 


8.75 


40 


<1:12 


4.00 


4.00 


'4.25 


4.25 


4.50 


4.50 


4.75 


5.00 


5:12 


4.00 


4.25 


4.50 


4.75 


4.75 


5.00 


5.25 


5.50 


7:12'' 


4.75 


5.25 


:5.75 


6.00 


6.50 


7.00 


7.25 


8.00 


12:12'' 


5.50 


6.00 


'■6.50 


7.25 


7.75 


8.25 


8.75 


10.0 


50 


<1:12 


4.00 


4.25 


■4.25 


4.50 


4.75 


4.75 


5.00 


5.50 


5:12 


4.25 


4.50 


^4.75 


5.00 


5.25 


5.50 


5.75 


6.00 


7:12'' 


5.25 


5.75 


:6.25 


6.75 


7.25 


7.75 


8.25 


9.25 


12:12'' 


6.00 


6.75 


7.50 


8.00 


8.75 


9.50 


10.25 


11.5 


60 


<1:12 


4.00 


4.25 


i4.50 


4.75 


5.00 


5.25 


5.25 


5.75 


5:12 


4.50 


4.75 


:5.oo 


5.25 


5.50 


5.75 


6.00 


6.75 


7:12'' 


5.50 


6.25 


6.75 


7.50 


8.00 


8.50 


9.25 


10.25 


12:12'' 


6.50 


7.25 


,8.25 


9.00 


9.75 


10.5 


11.5 


13.0 


First Story of 
Two-Story 


16 


<1:12 


4.00 


4.25 


4.50 


4.75 


5.00 


5.25 


5.25 


5.75 


5:12 


4.50 


4.75 


:5.00 


5.25 


5.50 


5.75 


6.00 


6.75 


7:12" 


4.50 


5.00 


i5.25 


5.75 


6.00 


6.25 


6.75 


7.25 


12:12'' 


5.00 


5.25 


;5.75 


6.25 


6.50 


7.00 


7.25 


8.25 


24 


<1:12 


4.50 


4.75 


5.00 


5.25 


5.50 


5.75 


6.00 


6.75 


5:12 


4.75 


5.25 


'5.50 


6.00 


6.25 


6.75 


7.00 


7.75 


7:12'' 


5.25 


5.75 


6.25 


6.75 


7.00 


7.50 


8.00 


9.00 


12:12'' 


5.50 


6.25 


i6.75 


7.25 


8.00 


8.50 


9.00 


10.25 


32 


<1:12 


4.75 


5.00 


i5.50 


5.75 


6.25 


6.50 


6.75 


7.50 


5:12 


5.25 


5.75 


!6.25 


6.75 


7.25 


7.50 


8.00 


9.00 


7:12'' 


5.75 


6.50 


7.00 


7.75 


8.25 


9.00 


9.50 


10.75 


12:12'' 


6.25 


7.00 


7.75 


8.50 


9.25 


10.0 


10.75 ; 


12.25 


40 


<1:12 


5.00 


5.50 


:5.75 


6.25 


6.75 


7.25 


7.50 


8.50 


5:12 


5.50 


6.25 


6.75 


7.25 


8.00 


8.50 


9.00 


10.25 


7:12'' 


6.25 


7.00 


7.75 


8.75 


9.50 


10.25 


11.0 


12.5 


12:12'' 


7.00 


8.00 


■8.75 


9.75 


10.75 


11.5 


12.5 


14.25 


50 


<1:12 


5.50 


6.00 


6.50 


7.00 


7.50 


8.00 


8.50 


9.50 


5:12 


6.00 


6.75 


7.50 


8.25 


9.00 


9.75 


10.5 I 


11.75 


7:12" 


7.00 


8.00 


9.00 


10.0 


10.75 


11.75 


12.75 


14.5 


12:12" 


7.75 


9.00 


10.0 


11.25 


12.25 


13.50 


14.75 


17.0 


60 


<1:12 


5.75 


6.50 


7.00 


7.50 


8.25 


8.75 


9.50 


10.75 


5:12 


6.75 


7.50 


,8.25 


9.25 


10.0 


10.75 


11.75 : 


13.25 


7:12" 


7.75 


9.00 


iio.o 


11.0 


12.25 


13.25 


14.5 : 


16.75 


12:12" 


8.75 


10.0 


111.5 


12.75 


14.0 


15.5 


16.75 


19.5 



(continued) 



208 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



Footnotes to Table R61 1.7 (9A) 

For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 pound per square foot = 0.0479kPa. 

a. Table values are based on a 3.5 in thick flat wall. For a 5.5 in thick flat wall, multiply the table values by 0.9. The adjusted values shall not result in solid wall lengths 
less than 4ft. 

b. Table values are based on a maximum unsupported wall height of 10 ft. 

c. Linear interpolation shall be permitted. 

d. The minimum solid wall lengths shown in the table are based on a building with an end wall length "W" of 60 feet and a roof slope of less than 7:12. For roof slopes 
of 7:12 or greater and end wall length "W" greater than 30 feet, the minimum solid wall length determined from the table shall be multiplied by: 

l + 0.4[(W-30)/30]. 



TABLE R611.7(9B) 
MINIMUM SOLID SIDEWALL LENGTH REQUIREMENTS FOR FLAT ICF WALLS (WIND PARALLEL TO RIDGE) ^ "'=''' 



WALL CATEGORY 


BUILDING END WALL 
WIDTH, W(feet) 


WIND VELOCITY PRESSURE FROM TABLE R61 1.7.4 (psf) 


20 


25 


30 


35 


40 


45 


50 


60 


One-Story or Top 
Story of Two-Story 




Minimum Solid Wall Length on Building Side Wall (feet) 


16 


4.00 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


4.75 


24 


4.00 


4.25 


4.50 


4.75 


4.75 


5.00 


5.25 


5.50 


32 


4.50 


4.75 


5.00 


5.25 


5.50 


6.00 


6.25 


6.75 


40 


5.00 


5.50 


5.75 


6.25 


6.75 


7.00 


7.50 


8.25 


50 


5.75 


6.25 


7.00 


7.50 


8.25 


8.75 


9.50 


10.75 


60 


6.50 


7.50 


8.25 


9.25 


10.0 


10.75 


11.75 


13.25 


First Story of 
Two-Story 


16 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


5.75 


6.50 


24 


4.75 


5.25 


5.50 


6.00 


6.25 


6.75 


7.00 


8.00 


32 


5.50 


6.00 


6.50 


7.00 


7.50 


8.00 


8.75 


9.75 


40 


6.25 


7.00 


7.50 


8.25 


9.00 


9.75 


10.5 


12.0 


50 


7.25 


8.25 


9.25 


10.25 


11.25 


12.25 


13.25 


15.25 


60 


8.50 


9.75 


11.0 


12.25 


13.5 


15.0 


16.25 


18.75 



For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 pound per square foot = 0.0479kPa. 

a. Table values are based on a 3.5 in thick flat wall. For a 5.5 in thick flat wall, multiply the table values by 0.9. The adjusted values shall not result in solid wall lengths 
less than 4ft. 

b. Table values are based on a maximum unsupported wall height of 10 ft. 

c. Table values are based on a maximum 12:12 roof pitch. 

d. Linear interpolation shall be permitted. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



209 



WALL CONSTRUCTION 



TABLE R611. 7(10) 
MAXIMUM ALLOWABLE CLEAR SPANS FOR ICF LINTELS IN NONLOAD-BEARING WALLS WITHOUT STIRRUPS^""" 

NO. 4 BOTTOM BAR 



MINIMUM LINTEL THICKNESS, T 
(inches) 


MINIMUM LINTEL DEPTH, D 
(inches) 


MAXIMUM CLEAR SPAN 


Supporting 

Light-Framed Nonbearing Wall 

(feet-inches) 


Supporting ICF 

Second Story and Nonbearing Wall 

(feet-inches) 


Flat ICF Lintel 


3.5 


8 


11-1 


3-1 


12 


15-11 


5-1 


16 


16-3 


6-11 


20 


: 16-3 


8-8 


24 


16-3 


10-5 


5.5 


8 


16-3 


4-4 


12 


16-3 


7-0 


16 


16-3 


9-7 


20 


16-3 


12-0 


24 


16-3 


14-3 


7.5 


8 


16-3 


5-6 


12 


16-3 


8-11 


16 


I 16-3 


12-2 


20 


16-3 


15-3 


24 


16-3 


16-3 


9.5 


8 


16-3 


6-9 


12 


16-3 


10-11 


16 


16-3 


14-10 


20 


16-3 


16-3 


24 


16-3 


16-3 


Waffle-Grid ICF Lintel 


6 or 8 


8 


9-1 


2-11 


12 


13-4 


4-10 


16 


16-3 


6-7 


20 


16-3 


8-4 


24 


16-3 


9-11 


Screen-Grid Lintel 


6 


12 


5-8 


4-1 


24 


16-3 


9-1 



For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 pounds per square foot = 0.0479kPa. 

a. This table is based on concrete with a minimum specified compressive strength of 2,500 psi, reinforcing steel with a minimum yield strength of 40,000 psi and an 
assumed equivalent rectangular cross section. 

b. This table is not intended to prohibit the use of ICF manufacturers tables based on engineering analysis in accordance with ACI 318. 

c. Deflection criterion is L/240, where L is the clear span of the hntel in inches. ■ 

d. Linear interpolation is permitted between lintel depths. 



210 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R611. 7(1 OA) 

MINIMUM SOLID END WALL LENGTH REQUIREMENTS FOR WAFFLE AND 

SCREEN-GRID ICF WALLS (WIND PERPENDICULAR TO RIDGE)^'"= 



WALL 
CATEGORY 


BUILDING SIDE 

WALL LENGTH, L 

(feet) 


ROOF SLOPE 


WIND VELOCITY PRESSURE FROM TABLE R61 1.7.4 


20 


25 


30 


35 


40 


45 


50 


60 


Minimum Solid Wall Length on Building End Wall (feet) 


One-Story or 

Top Story of 

Two-Story 


16 


<1:12 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


4.00 


4.25 


5:12 


4.00 


4.00 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


7:12'^ 


4.00 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


6.00 


12:12" 


4.25 


4.75 


5.00 


5.50 


5.75 


6.00 


6.50 


7.00 


24 


<1:12 


4.00 


4.00 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


5:12 


4.00 


4.00 


4.00 


4.25 


4.50 


4.50 


4.75 


5.00 


7:12^^ 


4.50 


4.75 


5.00 


5.50 


5.75 


6.25 


6.50 


7.25 


12:12'' 


5.00 


5.50 


6.00 


6.50 


7.00 


7.25 


7.75 


8.75 


32 


<1:12 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


4.75 


5.00 


5:12 


4.00 


4.00 


4.25 


4.50 


4.75 


5.00 


5.25 


5.75 


7:12*^ 


4.75 


5.25 


5.75 


6.25 


6.50 


7.00 


7.50 


8.50 


12:12'' 


5.50 


6.25 


6.75 


7.50 


8.00 


8.75 


9.25 


10.5 


40 


<1:12 


4.00 


4.00 


4.25 


4.50 


4.50 


4.75 


5.00 


5.50 


5:12 


4.00 


4.25 


4.50 


5.00 


5.25 


5.50 


5.75 


6.25 


7:12'' 


5.25 


5.75 


6.25 


7.00 


7.50 


8.00 


8.50 


9.75 


12:12" 


6.00 


6.75 


7.75 


8.50 


9.25 


10.0 


10.75 


12.25 


50 


<1:12 


4.00 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


6.00 


5:12 


4.25 


4.75 


5.00 


5.25 


5.50 


6.00 


6.25 


7.00 


7:12" 


5.75 


6.50 


7.00 


7.75 


8.50 


9.25 


9.75 


11.25 


12:12" 


6.75 


7.75 


8.75 


9.75 


10.75 


11.5 


12.5 


14.5 


60 


<1:12 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


5.75 


6.50 


5:12 


4.50 


5.00 


5.25 


5.75 


6.00 


6.50 


6.75 


7.75 


7:12" 


6.25 


7.00 


8.00 


8.75 


9.50 


10.25 


11.25 


12.75 


12:12" 


7.50 


8.75 


9.75 


11.0 


12.0 


13.25 


14.25 


16.5 


First Story of 
Two-Story 


16 


<1:12 


4.25 


4.50 


4.75 


5.00 


5.25 


5.50 


5.75 


6.50 


5:12 


4.50 


5.00 


5.25 


5.75 


6.00 


6.50 


6.75 


7.75 


7:12" 


4.75 


5.25 


5.75 


6.25 


6.75 


7.25 


7.75 


8.75 


12:12" 


5.25 


5.75 


6.50 


7.00 


7.50 


8.00 


8.75 


9.75 


24 


<1:12 


4.50 


5.00 


5.25 


5.75 


6.25 


6.50 


7.00 


7.75 


5:12 


5.00 


5.75 


6.25 


6.75 


7.25 


7.75 


8.25 


9.25 


7:12" 


5.75 


6.25 


7.00 


7.75 


8.25 


9.00 


9.75 


11.0 


12:12" 


6.25 


7.00 


7.75 


8.50 


9.50 


10.25 


11.0 


12.75 


32 


<1:12 


5.00 


5.50 


6.00 


6.50 


7.00 


7.50 


8.00 


9.00 


5:12 


5.75 


6.25 


7.00 


7.75 


8.25 


9.00 


9.75 


11.0 


7:12" 


6.50 


7.25 


8.25 


9.00 


10.0 


10.75 


11.75 


13.5 


12:12" 


7.25 


8.25 


9.25 


10.25 


11.25 


12.5 


13.5 


15.5 


40 


<1:12 


5.50 


6.00 


6.50 


7.25 


7.75 


8.50 


9.00 


10.25 


5:12 


6.25 


7.00 


7.75 


8.75 


9.50 


10.25 


11.0 


12.75 


7:12" 


7.25 


8.25 


9.25 


10.5 


11.5 


12.5 


13.75 


15.75 


12:12" 


8.00 


9.50 


10.75 


12.0 


13.25 


14.5 


15.75 


18.25 



(continued) 



2006 INTERNATIONAL RESIDENTIAL CODE® 



211 



WALL CONSTRUCTION 



TABLE R61 1. 7(1 OA)— continued 

MINIMUM SOLID END WALL LENGTH REQUIREMENTS FOR WAFFLE AND 

SCREEN-GRID ICF WALLS (WIND PERPENDICULAR TO RIDGE)^ "«= 



WALL CATEGORY 


BUILDING SIDE 

WALL LENGTH, L 

(feet) 


ROOF SLOPE 


WIND VELOCITY PRESSURE FROM TABLE R61 1.7.4 


20 


25 


30 


35 


40 


45 


50 


60 


Minimum Solid Wall Length on Building End Wall (feet) 


First Story of 
Two-Story 


50 


< 1:12 


6.00 


6.75 


7.50 


8.00 


8.75 


9.50 


10.25 


11.75 


5:12 


7.00 


8.00 


9.00 


10.0 


11.0 


12.0 


13.0 


14.75 


7:12'' 


8.25 


9.50 


10.75 


12.25 


13.5 


14.75 


16.0 


18.75 


12:12^ 


9.25 


11.0 


12.5 


14.0 


15.5 


17.25 


18.75 


22.0 


60 


<1:12 


6.50 


7.25 


8.25 


9.00 


10.0 


10.75 


11.75 


13.25 


5:12 


7.75 


8.75 ' 


10.0 


11.25 


12.25 


13.5 


14.75 


17.0 


7:12^ 


9.25 


10.75 ' 


12.25 


14.0 


15.5 


17.0 


18.5 


21.75 


12:12'^ 


10.5 


12.25, 


14.25 


16.25 


18.0 


20.0 


21.75 


■ 25.5 



For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 pound per square foot = 0.0479kPa. 

a. Table values are based on a 6 in (152.4 mm) thick nominal waffle-grid wall. For a 8 in thick nominal waffle-grid wall, multiply the table values by 0.90. 

b. Table values are based on a maximum unsupported wall height of 10 ft. , 

c. Linear interpolation is permitted. 

d. The minimum solid wall lengths shown in the table are based on a building with an end wall length "W" of 60 feet and a roof slope of less than 7:12. For roof 
slopes of 7: 12 or greater and end wall length "W" greater than 30 feet, the minimum solid wall length determined from the table shall be multiplied by: 1 + 0.4 
[(W-30)/30]. 



TABLE R61 1.7(1 OB) 

MINIMUM SOLID SIDE WALL LENGTH REQUIREMENTS FOR 6-INCH WAFFLE AND 

SCREEN-GRID ICF WALLS (WIND PARALLEL TO RIDGE)^ ""= " 



WALL CATEGORY 


BUILDING END WALL 
WIDTH, W(feet) 


WIND VELOCITY PRESSURE FROM TABLE R61 1 .7.4 (psf) 


20 


25 


■ 
30 


35 


40 


45 


50 60 


Minimum Solid Wall Length on Building Side Wall (feet) 


One-Story or Top 
Story of Two-Story 


16 


4.00 


4.00 


4.00 


4.25 


4.25 


4.50 


4.75 


5.00 


24 


4.00 


4.25 


4.50 


5.00 


5.25 


5.50 


5.75 


6.25 


32 


4.50 


5.00 


5.50 


5.75 


6.25 


6.75 


7.00 


8.00 


40 


5.25 


6.00 


6.50 


7.00 


7.75 


8.25 


8.75 


10.0 


50 


6.50 


7.25 


8.00 


9.00 


9.75 


10.75 


11.5 


13.25 


60 


7.75 


8.75 


10.0 


11.25 


12.25 


13.5 


14.5 


17.0 


First Story of 
Two-Story 


16 


4.50 


4.75 


5.25 


5.50 


5.75 


6.25 


6.50 


7.25 


24 


5.00 


5.75 


6.25 


6.75 


7.25 


7.75 


8.25 


9.50 


32 


6.00 


6.75 


7.50 


8.25 


9.00 


9.75 


10.5 


12.0 


40 


7.00 


8.00 


9.00 


10.0 


11.0 


12.0 


13.0 


15.0 


50 


8.50 


9.75 


11.25 


12.5 


14.0 


15.25 


16.75 


19.5 


60 


10.25 


12.0 


13.75 


15.5 


17.25 


19.0 


21.0 


24.5 



For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 pound per square foot = 0.0479kPa. 

a. Table values are based on a 6 in thick nominal waffle-grid wall. For a 8 in thick nominal waffle-grid wall, multiply the table values by 

b. Table values are based on a maximum unsupported wall height of 10 ft. 

c. Table values are based on a maximum 12:12 roof pitch. 

d. Linear interpolation shall be permitted. 



0.90. 



212 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



WALL CONSTRUCTION 



TABLE R61 1.7(11) 

MINIMUM PERCENTAGE OF SOLID WALL LENGTH ALONG EXTERIOR WALL LINES FOR TOWNHOUSES IN SEISMIC DESIGN 

CATEGORY C AND ALL BUILDINGS IN SEISMIC DESIGN CATEGORIES Dq, D^ AND Dg^" 



SEISMIC DESIGN CATEGORY (SDC) 


MINIMUM SOLID WALL LENGTH (percent) 


One-Story or Top Story of Two-Story 


Wall Supporting Light-Framed 
Second Story and Roof 


Wall Supporting ICF Second Story 
and Roof 


Townhouses in SDC C^ 


20 percent 


25 percent 


35 percent 


D,^ 


25 percent 


30 percent 


40 percent 


D/ 


30 percent 


35 percent 


45 percent 



For SI: 1 inch = 25.4 mm; 1 mile per hour = 0.447 m/s. 

a. Base percentages are applicable for maximum unsupported wall height of 10-feet, light-frame gable construction, and all ICF wall types. These percentages 
assume that the maximum weight of the interior and exterior wall finishes applied to ICF walls do not exceed 8 psf. 

b. For all walls, the minimum required length of solid walls shall be based on the table percent value multiplied by the minimum dimension of a rectangle inscribing 
the overall building plan. 

c. Walls shall be reinforced with a minimum No. 5 bar (Grade 40 or 60) spaced a maximum of 24 inches on center each way or a No. 4 bar spaced a maximum of 1 6 
inches on center each way. (Grade 40 or 60) spaced at a maximum of 16 inches on center each vway. 

d. Walls shall be constructed with a minimum concrete compressive strength of 3,000 psi and reinforced with minimum #5 rebar (Grade 60 ASTM A 706) spaced a 
maximum of 1 8 inches on center each way or No. 4 rebar (Grade 60 ASTM A706) spaced at a maximum of 1 2 inches (304.8 mm) on center each way. The mini- 
mum thickness of flat ICF walls shall be 5.5 inches. 



TABLE R61 1.7.4 

WIND VELOCITY PRESSURE FOR DETERMINATION OF 

MINIMUM SOLID WALL LENGTH^ 



WIND SPEED 
(mph) " 


VELOCITY PRESSURE (psf) 


Exposure '' 


B 


C 


D 


85 


14 


19 


23 


90 


16 


21 


25 


100 


19 


26 


31 


110 


23 


32 


37 


120 


27 


38 


44 


130 


32 


44 


52 


140 


37 


51 


60 


150 


43 


59 


69'= 



For SI: 1 pound per square foot = 0.0479 kPa; 1 mile per hour = 0.447 m/s. 

a. Table values are based on ASCE 7-98 Figure 6-4 using a mean roof height of 
35 ft. 

b. Exposure Categories shall be determined in accordance with Section 
R301.2.1.4. 

c. Design is required in accordance with ACT 318 and approved manufacturer 
guidelines. 

d. Interpolation is permitted between wind speeds. 



R611.8.1.1 Top bearing requirements for Seismic 
Design Categories C, Dq, Dj and Dj. For townhouses in 
Seismic Design Category C, wood sill plates attached to 
ICF walls shall be anchored with Grade A 307, 
Vg-inch-diameter (10 mm) headed anchor bolts embed- 
ded a minimum of 7 inches (178 mm) and placed at a 
maximum spacing of 36 inches (914 mm) on center. For 
all buildings in Seismic Design Category Dq or Dj, wood 
sill plates attached to ICF walls shall be anchored with 
ASTM A 307, Grade A, Vg-inch-diameter (10 mm) 
headed anchor bolts embedded a minimum of 7 inches 
(178 nrni) and placed at a maximum spacing of 24 inches 
(610 mm) on center. For all buildings in Seismic Design 
Category D2, wood sill plates attached to ICF walls shall 



be anchored with ASTM A 307, Grade A, Vg-inch-diam- 
eter (10 mm) headed anchor bolts embedded a minimum 
of 7 inches (178 mm) and placed at a maximum spacing 
of 16 inches (406 mm) on center. Larger diameter bolts 
than specified herein shall not be used. 

For townhouses in Seismic Design Category C, each 
floor joist perpendicular to an ICF wall shall be attached 
to the sill plate with an 18-gage [(0.0478 in.) (1.2 mm)] 
angle bracket using 3 - 8d common nails per leg in accor- 
dance with Figure R611.8(l). For all buildings in Seis- 
mic Design Category Dq or D,, each floor joist 
perpendicular to an ICF wall shall be attached to the sill 
plate with an 18-gage [(0.0478 in.) (1.2 mm)] angle 
bracket using 4 - 8d common nails per leg in accordance 
with Figure R61 1.8(1). For all buildings in Seismic 
Design Category Dj, each floor joist perpendicular to an 
ICF wall shall be attached to the sill plate with an 1 8-gage 
[(0.0478 in.) (1.2 mm)] angle bracket using 6 - 8d com- 
mon nails per leg in accordance with Figure R61 1.8(1). 

For ICF walls parallel to floor framing in townhouses 
in Seismic Design Category C, full depth blocking shall 
be placed at 24 inches (610 mm) on center and shall be 
attached to the sill plate with an 18-gage [(0.0478 in.) 
(1.2 mm)] angle bracket using 5 - 8d conamon nails per 
leg in accordance with Figure R61 1.8(6). For ICF walls 
parallel to floor framing for all buildings in Seismic 
Design Category Dq or D,, full depth blocking shall be 
placed at 24 inches (610 mm) on center and shall be 
attached to the sill plate with an 18-gage [(0.0478 in.) 
(1.2 mm)] angle bracket using 6 - 8d common nails per 
leg in accordance with Figure R61 1 .8(6). For ICF walls 
parallel to floor framing for all buildings in Seismic 
Design Category D2, full depth blocking shall be placed 
at 24 inches (610 mm) on center and shall be attached to 
the sill plate with an 18-gage [(0.0478 in.) (1.2 mm)] 
angle bracket using 9 - 8d common nails per leg in accor- 
dance with Figure R61 1 .8(6). 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



213 



WALL CONSTRUCTION 



NO. 4 CONTINUOUS BAR 
AS REQUIRED IN 
SECTION R61 1.7.1 

TOP OF WALL STORY 




MIDDLE OF SPAN, A. 
NOT REQUIRING STIRRUPS _ 
SEE TABLE R611.7(2). R6t1.7{3), 
R611.7{4). R611.7{5), OR R611.7(8) 

LINTEL REINFORCEMENT 
AS REQUIRED 



-WALL REINFORCEMENT 
AS REQUIRED 



OPEN REINFORCEMENT 
AS REQUIRED PER 
TABLE R611J{1) 



^ 



FIGURE R611 .7(2) 
REINFORCEMENT OF OPERNINGS 



SEE TABLE R61 1.7(2), 

R611J{3).R611JC8). 

R611.7(9)ORR611.7(10). 



1.51N.MIN, 
2.5 IN. MAX 




1.5IN, MIN. I 

2.5 IN. MAX. 



NO. 4 BAR LINTEL 
REINFORCEMENT REQUIRED 



MINIfyiUM NO. 3 STIRRUP 
AS REQUIRED 



NSULATIN6 FORM 



HORIZONTAL LINTEL 
REINFORCEMENT AS REQUIRED 



For SI: 1 inch = 25.4 mm. 
NOTE: Section cut through flat walL 



FIGURE R611. 7(3) 
ICF LINTELS FOR FLAT AND SCREEN-GRID WALLS 



214 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



SEE TABLE R611J(4). . 
R611. 7(5). R61 1.7(8), 
R611.7(9)OR 
R611.7(10). 




1.5IN. MIN. 
2.5 IN. MAX. 



MINIMUM NO. 3 STIRRUP AS 
REQUIRED 

NO. 4 BAR LINTEL 
REINFORCEMENT REQUIRED 



CONCRETE WEB (HIDDEN) 



VERTICAL CONCRETE 
CORE 



INSUUTING FORM 



HORIZONTAL LINTEL 
REINFORCEMENT AS REQUIRED 



For SI: 1 inch = 25.4 mm. 

NOTE: Section cut through vertical core of a waffle-grid lintel. 



FIGURE R61 1.7(4) 
SINGLE FORM HEIGHT WAFFLE-GRID LINTEL 



1,5 IN. MIN. 
2.5 IN. MAX 



SEE TABLE R611.7{4), 
R611.7(5), R611.7(8). 
R611.7(9)ORR611.7(10). 




NO. 4 BAR LINTEL REQUIREMENT 
REQUIRED 



CONCRETE WEB (HIDDEN) 



MINIMUM NO, 3 STIRRUP AS 
REQUIRED 



VERTICAL CONCRETE 
CORE 



INSULATING FORM 



HORIZONTAL LINTEL 
REINFORCEMENT AS REQUIRED 



For SI: 1 inch = 25.4 mm. 

NOTE: Section cut through vertical core of a waffle-grid lintel. 



FIGURE R61 1.7(5) 
DOUBLE FORM HEIGHT WAFFLE-GRID LINTEL 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



215 



WALL CONSTRUCTION 



1-1/2" (36 mm) MINIMUM 
2-1/2" (64 mm) MAXIMUM 



SEE TABLE R61 1.7(6), 
R611.7(7), R611(9), 
ORR611.7(10) 



D 



1-1/2" (36 mm) MINIMUM 
2-1/2" (64 mm) MAXIMUM 



•S^- : ■ ■■•. ^ ^* 



v: .m. 



No. 4 BAR LINTEL REINFORCEMENT 



VERTICAL CONCRETE CORE 



INSULATING FORM 

HORIZONTAL LINTEL REINFORCEMENT 
AS REQUIRED 



FIGURE R611. 7(6) 
SINGLE FORM HEIGHT SCREEN-GRID LINTEL 



t-1/2" (36 mm) MINIMUM \ 7 

2-1/2" (64 mm) MAXIMUM J 



SEE TABLE R611 .7(6), 
R611.7(7), R611(9). 
ORR611.7(10) 



1-1/2" (36 mm) MINIMUM \ 
2-1/2" (64 mm) M/U<IMUM J 




No. 4 BAR LINTEL REINFORCEMENT 

MINIMUM No, 3 STIRRUP AS REQUIRED 

VERTICAL CONCRETE CORE \ 

i 

INSULATING FORM i 



HORIZONTAL LINTEL REINFORCEMENT 
AS REQUIRED 



FIGURE R611. 7(7) 
DOUBLE FORM HEIGHT SCREEN-GRID LINTEL 



R611.8.2 Ledger bearing. Wood ledger boards supporting 
bearing ends of joists or trusses shall be anchored to flat ICF 
walls with minimum thickness of 5.5 inches (140 mm) and 
to waffle- or screen-grid ICF walls with minimum nominal 
thickness of 6 inches (152 mm) in accordance with Figure 
R611.8(2), R611.8(3), R611.8(4) or R611.8(5) and Table 
R61 1.8(1). Wood ledger boards supporting bearing ends of 
joists or trusses shall be anchored to flat ICF walls with min- 
imum thickness of 3.5 inches (140 mm) in accordance with 
Figure R61 1.8(5) and Table R61 1.8(1). The ledger shall be 
a minimum 2 by 8, No. 2 Southern Yellow Pine or No. 2 
Douglas Fir. Ledgers anchored to nonload-bearing walls to 
support floor or roof sheathing shall be attached with '/2 inch 
(12.7 mm) diameter or headed anchor bolts spaced a maxi- 



216 



mum of 6 feet (1829 mm) on center. Anchor bolts shall be 
embedded a minimum of 4 inches (102 nrnii) into the con- 
crete measured from the inside face of the insulating form. 
For insulating forms with a face shell thickness of 1 .5 inches 
(38 mm) or less, the hole in the form shall be a minimum of 4 
inches (102 mm) in diameter. For insulating forms with a 
face shell thicker than 1.5 inches (38 mm), theidiameter of 
the hole in the form shall be increased by 1 inch (25 mm) for 
each V2 inch (13 nmi) of additional insulating form face 
shell thickness. The ledger board shall be in direct contact 
with the concrete at each bolt location. 1 

R611.8.2.1 Ledger bearing requirements for Seismic 
Design Categories C, Do, D^ and Dj. Additional anchor- | 
age mechanisms connecting the wall to the floor system 

2006 INTERNATIONAL RESIDENTIAL CODE® 



WALL CONSTRUCTION 




CONCRETE 



REINFORCEMENT AS REQUIRED 



MAXIMUM 8d,3 



REINFORCEMENT AS REQUIRED 



LAP SPLICE 



FIGURE R61 1.7.1 .4 
LAP SPLICES 



shall be installed at a maximum spacing of 6 feet (1829 
mm) on center for townhouses in Seismic Design Category 
C and 4 feet (1220 mm) on center for all buildings in Seis- 
mic Design Categories Dq, Dj and Dj. The additional 
anchorage mechanisms shall be attached to the ICF wall 
reinforcement and joist rafters or blocking in accordance 
with Figures R611.8(l) through R61 1.8(7). The additional 
anchorage shall be installed through an oversized hole in 
the ledger board that is Vj inch (13 mm) larger than the 
anchorage mechanism diameter to prevent combined ten- 
sion and shear in the mechanism. The blocking shall be 
attached to floor or roof sheathing in accordance with edge 
fastener spacing. Such additional anchorage shall not be 
accomplished by the use of toe nails or nails subject to with- 
drawal nor shall such anchorage mechanisms induce ten- 
sion stresses perpendicular to grain in ledgers or nailers. 
The capacity of such anchors shall result in connections 
capable of resisting the design values listed in Table 
R611.8(2).The diaphragm sheathing fasteners apphed 
directly to a ledger shall not be considered effective in pro- 
viding the additional anchorage required by this section. 

Where the additional anchorage mechanisms consist of 
threaded rods with hex nuts or headed bolts complying 
with ASTM A 307, Grade A or ASTM F 1554, Grade 36, 
the design tensile strengths shown in Table R611.9 shall 
be equal to or greater than the product of the design values 
hsted in Table R611.8(2) and the spacing of the bolts in 
feet (mm). Anchor bolts shall be embedded as indicated in 
Table R611 .9. Bolts with hooks shall not be used. 

R611.8.3 Floor and roof diaphragm construction. Floor 
and roof diaphragms shall be constructed of wood structural 
panel sheathing attached to wood framing in accordance with 
Table R602.3(l) or Table R602.3(2) or to cold-formed steel 
floor framing in accordance with Table R505.3.1(2) or to 
cold-formed steel roof framing in accordance with Table 
R804.3. 

R611.8.3.1 Floor and roof diaphragm construction 
requirements in Seismic Design Categories Dq, D^ and 

D2. The requirements of this section shall apply in addi- 



tion to those required by Section R61 1.8.3. Edge spacing 
of fasteners in floor and roof sheathing shall be 4 inches 
( 1 02 mm) on center for Seismic Design Category Dg or D 1 | 
and 3 inches (76 mm) on center for Seismic Design Cate- 
gory D2. In Seismic Design Categories Dq, D, and D2, all | 
sheathing edges shall be attached to framing or blocking. 
Minimum sheathing fastener size shall be 0.113 inch (3 
mm) diameter with a minimum penetration of P/g-inches 
(35 mm) into framing members supporting the sheathing. 
Minimum wood structural panel thickness shall be V,6 
inch (11 mm) for roof sheathing and ^V32 inch (18 mm) for 
floor sheathing. Vertical offsets in floor framing shall not 
be permitted. 

R611.9 ICF wall to top sill plate (roof) connections. Wood 
sill plates attaching roof framing to ICF walls shall be anchored 
with minimum V2 inch (13 mm) diameter anchor bolt embed- 
ded a minimum of 7 inches (178 mm) and placed at 6 feet (1 829 
mm) on center in accordance with Figure R6 1 1 .9. Anchor bolts 
shall be located in the cores of waffle-grid and screen-grid ICF 
walls. Roof assemblies subject to wind uplift pressure of 20 
pounds per square foot (1.44 kPa) or greater as established in 
Table R30 1.2(2) shall have rafter or truss ties provided in 
accordance with Table R802. 1 1 . 

R611.9.1 ICF wall to top sill plate (roof) connections for 
Seismic Design Categories C, Do, Dj and Dj. The require- | 
ments of this section shall apply in addition to those required 
by Section R61 1 .9. The top of an ICF wall at a gable shall be 
attached to an attic floor in accordance with Section 
R61 1.8.1.1. For townhouses in Seismic Design Category C, 
attic floor diaphragms shall be constructed of structural wood 
sheathing panels attached to wood framing in accordance 
with Table R602.3(l) or Table R602.3(2). Edge spacing of 
fasteners in attic floor sheathing shall be 4 inches (102 mm) 
on center for Seismic Design Category Dq or Di and 3 inches | 
(76 mm) on center for Seismic Design Category D2. In Seis- 
mic Design Categories Dq, Dj and D2, all sheathing edges | 
shall be attached to framing or blocking. Minimum sheathing 
fastener size shall be 0.113 inch (2.8 mm) diameter with a 



2006 INTERNATIONAL RESIDENTIAL CODE® 



217 



WALL CONSTRUCTION 




WIND 

PERPENDICULAR "^\ 
TO RIDGE 



ONE-STORY OR TOP STORY OF 

TWO-STORY 

[TABLE R611.7(9A)ORR611.7(10A)] 

MIN. SOLID WALL LENGTH < A + B + C 

FIRST STORY OF TWO-STORY 
[TABLE R611.7(9A) OR R 611. 7(1 OA)] 
MIN. SOLID WALL LENGTH < D + E 




WIND 
PARALLEL 
TO RIDGE 

L 



ONE-STORY OR TOP STORY OF 
TWO-STORY ! 

[TABLE R611.7(9B) OR R 611.7(108)1 ': 
MIN. SOLID WALL LENGTH < A + B + C 

FIRST STORY OF TWO-STORY ! 

[TABLE R611.7(9B) OR R611.7(10B)] ,' 
MIN. SOLID WALL LENGTH < D + E + F 



NOTE: EACH WALL SEGMENT (A, B, C, D AND F) 
MUST MEET THE MINIMUM SOLID WALL SEGMENT LENGTH 
IN ORDER TO APPLICABLE TO THE MINIMUM SOLID 
WALL LENGTH EQUATIONS ABOVE. 



FIGURE R61 1.7.4 
MINIMUM SOLID WALL LENGTH 



218 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



TABLE R61 1.8(1) 
FLOOR LEDGER-ICF WALL CONNECTION (SIDE-BEARING CONNECTION) REQUIREMENTS^"- 



MAXIMUM FLOOR CLEAR SPAN" 
(feet) 


MAXIMUM ANCHOR BOLT SPACING^ (inches) 


Staggered 

Va-inch-diameter 

anchor bolts 


Staggered 

%-inch-diameter 

anchor bolts 


Two 

Vj-inch-diameter 

anchor bolts' 


Two 

%-inch-diameter 

anchor bolts* 


8 


18 


20 


36 


40 


10 


16 


18 


32 


36 


12 


14 


18 


28 


36 


14 


12 


16 


24 


32 


16 


10 


14 


20 


28 


18 


9 


13 


18 


26 


20 


8 


11 


16 


22 


22 


7 


10 


14 


20 


24 


7 


9 


14 


18 


26 


6 


9 


12 


18 


28 


6 


8 


12 


16 


30 


5 


8 


10 


16 


32 


5 


7 


10 


14 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Minimum ledger board nominal depth shall be 8 inches. The thickness of the ledger board shall be a minimum of 2 inches. Thickness of ledger board is in nominal 
lumber dimensions. Ledger board shall be minimum No. 2 Grade. 

b. Minimum edge distance shall be 2 inches for V2-inch-diameter anchor bolts and 2.5 inches for ^/g-inch-diameter anchor bolts. 

c. Interpolation is permitted between floor spans. 

d. Floor span corresponds to the clear span of the floor structure (i.e., joists or trusses) spanning between load-bearing walls or beams. 

e. Anchor bolts shall extend through the ledger to the center of the flat ICF wall thickness or the center of the horizontal or vertical core thickness of the waffle-grid or 
screen-grid ICF wall system. 

f. Minimum vertical distance between bolts shall be 1.5 inches for V2-inch-diameter anchor bolts and 2 inches for ^/g-inch-diameter anchor bolts. 



minimum penetration of 1% inches (35 mm) into framing 
members supporting the sheathing. Minimum wood struc- 
tural panel thickness shall be 7ig inch (11 mm) for the attic 
floor sheathing. Where hipped roof construction is used, the 
use of a structural attic floor is not required. 

For townhouses in Seismic Design Category C, wood sill 
plates attached to ICF walls shall be anchored with ASTM A 
307, Grade A, Vg-inch (10 mm) diameter anchor bolts 
embedded a minimum of 7 inches (178 mm) and placed at a 
maximum spacing of 36 inches (914 mm) on center. For all 
buildings in Seismic Design Category Dq or Dj, wood sill 
plates attached to ICF walls shall be anchored with ASTM A 
307, Grade A, Vg-inch (10 mm) diameter anchor bolts 
embedded a minimum of 7 inches (178 mm) and placed at a 
maximum spacing of 16 inches (406 mm) on center. For all 
buildings in Seismic Design Category D2, wood sill plates 
attached to ICF walls shall be anchored with ASTM A 307, 
Grade A, Vg-inch (10 mm) diameter anchor bolts embedded 
a minimum of 7 inches (1 78 mm) and placed at a maximum 
spacing of 16 inches (406 mm) on center. 

For townhouses in Seismic Design Category C, each 
floor joist shall be attached to the sill plate with an 18-gage 
[(0.0478 in.) (1.2 mm)] angle bracket using 3 - 8d common 
nails per leg in accordance with Figure R61 1.8(1). For all 



buildings in Seismic Design Category Do or Dj, each floor 
joist shall be attached to the sill plate with an 18-gage 
[(0.0478 in.) (1.2 mm)] angle bracket using 4 - 8d common 
nails per leg in accordance with Figure R6 11.8(1). For all 
buildings in Seismic Design Category D2, each floor joist 
shall be attached to the sill plate with an 18-gage [(0.0478 
in.) (1.2 mm)] angle bracket using 6-8d common nails per 
leg in accordance with Figure R611.8(l). 

Where hipped roof construction is used without an attic 
floor, the following shall apply. For townhouses in Seismic 
Design Category C, each rafter shall be attached to the sill 
plate with an 18-gage [(0.0478 in.) (1.2 mm)] angle bracket 
using 3 - 8d common nails per leg in accordance with Figure 
R61 1 .9. For all buildings in Seismic Design Category Dq or 
Di, each rafter shall be attached to the sill plate with an 
18-gage [(0.0478 in.) (1.2 mm)] angle bracket using 4 - 8d 
common nails per leg in accordance with Figure R611.9. 
For all buildings in Seismic Design Category D2, each rafter 
shall be attached to the sill plate with an 18-gage [(0.0478 
in.) (1.2 mm)] angle bracket using 6-8d common nails per 
leg in accordance with Figure R61 1.9. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



219 



WALL CONSTRUCTION 



TABLE R61 1.8(2) 

DESIGN VALUES (PLF) FOR FLOOR JOIST-TO-WALL ANCHORS REQUIRED FOR TOWNHOUSES 

IN SEISMIC DESIGN CATEGORY C AND ALL BUILDINGS IN SEISMIC DESIGN CATEGORIES Dq, D, AND D/ " 



WALL TYPE 


SEISMIC DESIGN CATEGORY 


C 


Do or Di 


D. 


Flat 3.5 


193 


NP 


NP 


Flat 5.5 


303 


502 


708 


Flat 7.5 


413 


685 


965 


Flat 9.5 


523 


867 


1,223 


Waffle 6 


246 


409 


577 


Waffle 8 


334 


555 


782 : 


Screen 6 


233 


387 


546 ; 



For SI: Ipound per linear foot = 1.488 kg/m. 
NP = Not Permitted 

a. Table values are based on IBC Equation 16-64 using a tributary wall height of 1 1 feet. Table values shall be permitted to be reduced for tributary wall heights less 
than 1 1 feet by multiplying the table values by X/1 1, where X is the tributary wall height. ! 

b. Values may be reduced by 30 percent when used for ASD. ; 



SILL PLATE 



MIN. 7 IN. 
(178 mm) 




LIGHT-FRAME 
CONSTRUCTION ABOVE 



CUP ANGLE M EACH JOIST 
IN SEISMIC DESIGN 
CATEGORIES C, Dq, D^, AND D^ 
PER SECTION R611. 8. 1.1 



ANCHOR BOO" 
AS REQUIRED 

VERTICAL WALL 
REINFORCEMENT 
AS REQUIRED 



ICFWALL 



MIN. NO. 4 BAR 
(CONTINUOUS) 



FIGURE R611. 8(1) 

SECTION CUT THROUGH FLAT WALL OR VERTICAL CORE 

OF WAFFLE- OR SCREEN-GRID WALL 



220 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL CONSTRUCTION 



DOUBLE (SHOWN) OR 
STAGGERED ANCHOR 
BOLT AS REQUIRED 



LAP SPLICE AS 
REQUIRED 



MIN.N0.4BAR 
(CONTINUOUS; 




INSULATING FORM 



LEDGER BOARD 



JOIST 




V— JOIST HANGER 



WALL OUT-OF-PLANE 
ANCHOR IN SEISMIC 
DESIGN CATEGORIES C, 
Do, Di AND D2 
(SEE SECTION R6II.8.2.I; 



Mm. 4-INCH-DIAMETER HOLE 
THROUGH FORM AT EACH 
BOLT LOCATION 



ICFWALL 



VERTICAL WALL REINFORCEMENT 
AS REQUIRED 



For SI: 1 inch = 25.4 mm. 

NOTE: Section cut through flat wall or vertical core of a waffle- or screen-grid wall. 



FIGURE R61 1.8(2) 
FLOOR LEDGER— ICF WALL CONNECTION (SIDE-BEARING CONNECTION) 



DOUBLE (SHOWN) OR 
STAGGERED ANCHOR 
BOLT AS REQUIRED 



LAP SPLICE AS 
REQUIRED 



MJN. NO. 4 BAR 
(CONTINUOUS) 




WALL OUT-OF-PLANE 
ANCHOR IN SEISMIC 
DESIGN CATEGORIES C, 
Do, Dt AND Dg 
(SEE SECTION R611. 8.2.1) 



i < 3 IN. (76 mm) 

-^^^^ ICF WALL 

VERTICAL WALL REINFORCEMENT 
AS REQUIRED 



For SI: 1 inch = 25.4 mm. 

NOTE: Section cut through flat wall or vertical core of a waffle- or screen-grid wall. 



FIGURE R61 1.8(3) 
FLOOR LEDGER— ICF WALL CONNECTION (LEDGE-BEARING CONNECTION) 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



221 



WALL CONSTRUCTION 



LAP SPLICE AS 
REQUIRED 



DOUBLE (SHOWN) OR 
STAGGERED ANCHOR 
BOLT AS REQUIRED 



INSULATING FORM 



MlN.4!N.x4IN.xV4lN 
(102 mm X 102 mm x 6 mm) 
STEEL PUTE FOR 
EACH BOLT 




/- WALL OUT-OF-PLANE 
/ ANCHOR IN SEISMIC 



MIN. NO. 4 BAR 
(CONTINUOUS) 



JOIST HANGER 



DESIGN CATEGORIES C. 

Do, Di. AND Dg 

(SEE SECTION FI61 1.8.2.1) 



MIN. 4-INCH-DIAMETER HOLE 
THROUGH FORM AT EACH 
BOLT LOCATION 



:::^ICFWALL 

•VERTICAL WALL REINFORCEMENT 
AS REQUIRED 



For SI: 1 inch = 25.4 nun. 

NOTE: Section cut through flat wall. 



FIGURE R61 1.8(4) 

WOOD FLOOR LEDGER— ICF WALL SYSTEM CONNECTION 

(THROUGH-BOLT SIDE-BEARING CONNECTION) 



VERTICAL WALL REINFORCEMENT 
AS REQUIRED 



LAP SPLICE AS 
REQUIRED 



DOUBLE (SHOWN) OR 
STAGGERED ANCHOR t i 
BOLT AS REQUIRED"-^^! i^ 



MIN. 4 IN. X 4 IN. X 1/4 IN 
(102 mm X 102 mm x 6 mm) 
STEEL PLATE FOR 
EACH BOLT 



MIN, # 4 BAR 
(CONTINUOUS) 



For SI: 1 inch = 25.4 mm. 

NOTE: Section cut through flat wall. 



INSULATING FORM 




WALL OUT-OF-PLANE 
ANCHOR IN SEISMIC 
DESIGN CATEGORIES C. 
Do, Di, AND Da 
SEE SECTION R611 .8.2.1) 



CFWALL 



VERTICAL WALL REINFORCEMENT 
AS REQUIRED 



FIGURE R6l 1.8(5) 
FLOOR LEDGER— ICF WALL CONNECTION 



222 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WALL CONSTRUCTION 



CLIP ANGLE AT EACH FULL 
DEPTH BLOCKING SEISMIC 
DESIGN CATEGORIES C, 
Do, Di AND Da 



SILL PLATE 



LIGHT-FRAME ABOVE 
~-A/ 



MIN.7iiN. 
(178 mm) 



BLOCKING SHALL RECEIVE 
SHEATHING EDGE NAILING 




r FLOOR JOIST 



STRAP ACROSS WIDTH OF 
BUILDING WITH {4}-8d NAILS 
PER JOIST SPACING 



MIN. NO. 4 BAR 
(CONTINUOUS) 



FIGURE R611. 8(6) 
ANCHORAGE REQUIREMENTS FOR TOP BEARING WALLS FOR TOWNHOUSES IN SEISMIC DESIGN CATEGORY C 
AND ALL BUILDINGS IN SEISMIC DESIGN CATEGORIES Do, Di, AND Da FOR FLOOR FRAMING PARALLEL TO WALL 



BLOCKING SHALL EXTEND THE WIDTH 
OF THE BUILDING AND SHALL RECEIVE 
SHEATHING EDGE NAILING 



DOUBLE (SHOWN) OR 
STAGGERED ANCHOR 
BOOT AS REQUIRED 



LAP SPLICE AS 
REQUIRED 



VERTICAL WALL 
REINFORCEMENT 
AS REQUIRED 




NSULATINQ FORM 



FLOOR JOIST 



BLOCWNG IN LINE WITH WALL 
OUT-OF-PLANE ANCHOR IN SEISMIC 
DESIGN CATEGORIES 0, Dq, D, AND Dg 
PER R61 1.9(2) ~\ 



BLOCKING 







BLOCKING^ 




MIN. NO. 4 BAR 
(CONTINUOUS) 



MIN. 4-INCH-DfAMETER HOLE, 
THROUGH FORM AT EACH 
BOLT LOCATION 

; ICF WALL 

STRAP ACROSS THE WIDTH OF 
BUILDING WITH (5)-16d NAILS 
PER FLOOR JOIST SPACING 



FIGURE R611 .8(7) 

ANCHORAGE REQUIREMENTS FOR LEDGER BEARING WALLS FOR TOWNHOUSES IN SEISMIC DESIGN CATEGORY C AND ALL 

BUILDINGS IN SEISMIC DESIGN CATEGORIES Do, Di AND D2 FOR FLOOR FRAMING PARALLEL TO WALL 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



223 



WALL CONSTRUCTION 



TABLE R61 1.9 
DESIGN TENSILE STRENGTH OF HEADED BOLTS CAST IN CONCRETE^ 



DIAMETER OF BOLT 
(inches) 


MINIMUM EMBEDMENT DEPTH 
(inches) 


DESIGN TENSILE STRENGTH" 
(pounds) 


'U 


2 


1040 


^/g with washer^ 


2V/ 


2540 


V2 with washer^ 


4" ; 


4630 



For SI: 1 pound per square inch = 6.895 kPa. 

a. Applicable to concrete of all strengths. See Notes (c) and (d). 

b. Values are based on ASTM F 1554, Grade 36 bolts. Where ASTM A 307, Grade A headed bolts are used, the strength shall be increased b\/ 1.034. 

c. A hardened washer shall be installed at the nut embedded in the concrete or head of the bolt to increase the bearing area. The washer is not required where the con- 
crete strength is 4000 psi or more. 

d. Embedment depth shall be permitted to be reduced V4-inch where 4000 psi concrete is used. 



CUP ANGLE M EACH ROOF 
FRAMING MEMBER IN SEISMIC 
DESIGN CATEGORIES C, Dq, 
Di AND D2 



PER SECTION R61 1.9.1 




LIGHT-FRAME 
ROOF 



ANCHOR SOU 

(SEE SECTION R61 1.9) 



MINIMUM NO. 4 BAR 
(CONTINUOUS) 



VERTICAL WALL REINFORCEMENT 
AS REQUIRED 



NOTE: Section cut through flat wall or vertical core of a waffle- or screen-grid wall. 



FIGURE R611. 9 
ROOF SILL PLATE— ICF WALL CONNECTION 



SECTION R612 

CONVENTIONALLY FORMED CONCRETE WALL 

CONSTRUCTION 

R612.1 GeneraL Conventionally formed concrete walls with 
flat surfaces shall be designed and constructed in accordance 
with the provisions of Section R61 1 for Flat ICF walls or in 
accordance with the provisions of ACT 318. 



SECTION R613 
EXTERIOR WINDOWS AND GLASS DOORS 

R613.1 GeneraL This section prescribes performance and 
construction requirements for exterior window systems 
installed in wall systems. Windows shall be installed and 
flashed in accordance with the manufacturer's written installa- 
tion instructions. Written installation instructions shall be pro- 
vided by the manufacturer for each window. 

R613.2 Window sills. In dwelling units, where the opening of 
an operable window is located more than 72 inches (1829 mm) 
above the finished grade or surface below, the lowest part of the 



clear opening of the window shall be a minimum of 24 inches 
(610 mm) above the finished floor of the room in which the 
window is located. Glazing between the floor and 24 inches 
(610 mm) shall be fixed or have openings through which a 
4-inch-diameter (102 mm) sphere cannot pass. 

Exceptions: 

1. Windows whose openings will not allow a 
4-inch-diameter ( 1 02 mm) sphere to pass through the 
opening when the opening is in its largest opened 
position. I 

2. Openings that are provided with window I guards that 
comply with ASTM F 2006 or F 2090. \ 

R613.3 Performance. Exterior windows and doors shall be 

I 

designed to resist the design wind loads specified in Table 
R301.2(2) adjusted for height and exposure! per Table 
R301.2(3). ; 

R613.4 Testing and labeling. Exterior windows land shding 
doors shall be tested by an approved independent laboratory, and 
bear a label identifying manufacturer, performance characteris- 



224 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



WALL CONSTRUCTION 



tics and approved inspection agency to indicate compliance with 
AAMA/WDMA/CSA 101/I.S.2/A440. Exterior side-hinged 
doors shall be tested and labeled as conforming to AAMA/ 
WDMA/CSA 101/I.S.2/A440 or comply with Section R613.6. 

Exception: Decorative glazed openings. 

R613.4.1 Comparative analysis. Structural wind load 
design pressures for window and door units smaller than the 
size tested in accordance with Section R613.4 shall be per- 
mitted to be higher than the design value of the tested unit 
provided such higher pressures are determined by accepted 
engineering analysis. All components of the small unit shall 
be the same as those of the tested unit. Where such calcu- 
lated design pressures are used, they shall be validated by an 
additional test of the window or door unit having the highest 
allowable design pressure. 

R613.5 Vehicular access doors. Vehicular access doors shall 
be tested in accordance with either ASTM E 330 or ANSI/ 
DASMA 108, and shall meet the acceptance criteria of 
ANSI/DASMA 108. 

R613.6 Other exterior window and door assemblies. Exte- 
rior windows and door assemblies not included within the 
scope of Section R613.4 or Section R613.5 shall be tested in 
accordance with ASTM E 330. Glass in assemblies covered by 
this exception shall comply with Section R308.5. 

R613.7 Wind-borne debris protection. Protection of exterior 
windows and glass doors in buildings located in wind-borne 
debris regions shall be in accordance with Section R301 .2. 1 .2. 

R613.7.1 Fenestration testing and labeling. Fenestration 
shall be tested by an approved independent laboratory, listed 
by an approved entity, and bear a label identifying manufac- 
turer, performance characteristics, and approved inspection 
agency to indicate compliance with the requirements of the 
following specification: 

1. ASTM E 1886 and ASTM E 1996; or 

2. AAMA 506. 

R613.8 Anchorage methods. The methods cited in this sec- 
tion apply only to anchorage of window and glass door assem- 
blies to the main force-resisting system. 



SHIM OR WOOD BUCK 
THICKNESS 




R613.8.1 Anchoring requirements. Window and glass 
door assemblies shall be anchored in accordance with the 
published manufacturer's recommendations to achieve the 
design pressure specified. Substitute anchoring systems 
used for substrates not specified by the fenestration manu- 
facturer shall provide equal or greater anchoring perfor- 
mance as demonstrated by accepted engineering practice. 

R613.8.2 Anchorage details. Products shall be anchored in 
accordance with the minimum requirements illustrated in 
Figures R613.8(l), R613.8(2), R613.8(3), R613.8(4), 
R613.8(5), R613.8(6), R613.8(7) and R613.8(8). 

R613.8.2.1 Masonry, concrete or other structural 
substrate. Where the wood shim or buck thickness is 
less than IV2 inches (38 mm), window and glass door 
assemblies shall be anchored through the jamb, or by 
jamb clip and anchors shall be embedded directly into 
the masonry, concrete or other substantial substrate 
material. Anchors shall adequately transfer load from the 
window or door frame into the rough opening substrate 
[see Figures R613.8(l) and R613.8(2).] 

Where the wood shim or buck thickness is 1 V2 inches 
(38 mm) or more, the buck is securely fastened to the 
masonry, concrete or other substantial substrate, and the 
buck extends beyond the interior face of the window or 
door frame, window and glass door assemblies shall be 
anchored through the jamb, or by jamb clip, or through 
the flange to the secured wood buck. Anchors shall be 
embedded into the secured wood buck to adequately 
transfer load from the window or door frame assembly 
[Figures R613.8(3), R613.8(4) and R613.8(5)]. 

R613.8.2.2 Wood or other approved framing mate- 
rial. Where the framing material is wood or other 
approved framing material, window and glass door 
assemblies shall be anchored through the frame, or by 
frame clip, or through the flange. Anchors shall be 
embedded into the frame construction to adequately 




FRAME CLIP 
INSTALLATION 



FIGURE R61 3.8(1) 
THROUGH THE FRAME 



APPLY FRAME CLIP TO WINDOW OR DOOR IN ACCORDANCE 
WITH PUBLISHED MANUFACTURER'S RECOMMENDATIONS. 

FIGURE R61 3.8(2) 
FRAME CLIP 



2006 INTERNATIONAL RESIDENTIAL CODE® 



225 



WALL CONSTRUCTION 




TAPERED 
BUCKS ARE 
NOT ALLOWED 




THROUGH THE FRAME ANCHORING METHOD. ANCHORS SHALL 
BE PROVIDED TO TRANSFER LOAD FROM THE WINDOW OR 
DOOR FRAME INTO THE ROUGH OPENING SUBSTRATE. 

FIGURE R613.8(3) 
THROUGH THE FRAME 



Apply anchors through flange in accordance with 
published manufacturer's recommendations. 

FIGURE R61 3.8(5) 
THROUGH THE FLANGE 




FRAME CLIP 
INSTALLATION 



<> 



7> 



FIGURE R61 3.8(6) 
THROUGH THE FRAME 



APPLY FRAME CLIP TO WINDOW OR DOOR FRAME IN ACCOR- 
DANCE WITH PUBLISHED MANUFACTURER'S RECOMMENDA 
TIONS. ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD 
FROM THE FRAME CLIP INTO THE ROUGH OPENING SUB- 
STRATE. 

FIGURE R61 3.8(4) 
FRAME CLIP 

transfer load [Figures R613.8(6), R613.8(7) and 
R613.8(8)]. 

R613.9 Mullions occurring between individual window 
and glass door assemblies. 

R613.9.1 Mullions. Mullions shall be tested by an 
approved testing laboratory in accordance with AAMA 
450, or be engineered in accordance with accepted engi- 
neering practice. Mullions tested as stand-alone units or 
qualified by engineering shall use performance criteria cited 
in Sections R613.9.2, R613.9.3 and R613.9.4. Mullions 



qualified by an actual test of an entire assembly shall com- I 
ply with Sections R613.9.2 and R613.9.4. | 

R613.9.2 Load transfer. MulHons shall be designed to 

transfer the design pressure loads applied by the window 

and door assemblies to the rough opening substrate. 

i 
R613.9.3 Deflection. Mullions shall be capable of resisting 

the design pressure loads applied by the window and door 

assemblies to be supported without deflecting more than 

LI 115, where L is the span of the mullion in inches. 

R613.9.4 Structural safety factor. Mullions shall be capa- 
ble of resisting a load of 1.5 times the design pressure loads 
apphed by the window and door assembhes to be supported 
without exceeding the appropriate material stress levels. If 
tested by an approved laboratory, the 1.5 times the design 
pressure load shall be sustained for 10 seconds, and the per- 



226 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WALL CONSTRUCTION 



manent deformation shall not exceed 0.4 percent of the mul- 
hon span after the 1 .5 tunes design pressure load is removed. 



<* 



e 



T> 



e 



FIGURE R61 3.8(8) 
THROUGH THE FLANGE 



FIGURE R61 3.8(7) 
FRAME CLIP 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



227 



228 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 7 

WALL COVERING 



SECTION R701 
GENERAL 

R701.1 Application. The provisions of this chapter shall con- 
trol the design and construction of the interior and exterior wall 
covering for all buildings. 

R701.2 Installation. Products sensitive to adverse weather 
shall not be installed until adequate weather protection for the 
installation is provided. Exterior sheathing shall be dry before 
applying exterior cover. 



SECTION R702 
INTERIOR COVERING 

R702.1 General. Interior coverings or wall finishes shall be 
installed in accordance with this chapter and Table R702.1(l), 
Table R702. 1(2), Table R702. 1(3) and Table R702.3.5. Interior 
masonry veneer shall comply with the requirements of Section 
R703.7.1 for support and Section R703.7.4 for anchorage, 
except an air space is not required. Interior finishes and materi- 
als shall conform to the flame spread and smoke-density 
requirements of Section R315. 



TABLE R702.1(1) 
THICKNESS OF PLASTER 



PLASTER BASE 


FINISHED THICKNESS OF PLASTER FROM FACE OF LATH, MASONRY, CONCRETE (inches) 


Gypsum plaster 


Portland cement mortar 


Expanded metal lath 


%, minimum^ 


^/g, minimum'' 


Wire lath 


^/g, minimum'* 


V4, minimum (interior)'' 
%, minimum (exterior)'' 


Gypsum lath^ 


V2, minimum 


^1^, minimum (interior)'' 


Masonry walls'^ 


V2, minimum 


V2, minimum 


Monolithic concrete walls'^'' 


Vg, maximum 


Vg, maximum 


Monolithic concrete ceilings'^'' 


^/g, maximum^ 


V2, maximum 


Gypsum veneer base^'^ 


'/16, minimum 


%, minimum (interior)'' 


Gypsum sheathing^ 


— 


^/4, minimum (interior)'' 
Vg, minimum (exterior)'' 



For SI: 1 inch = 25.4 mm. 

a. When measured from back plane of expanded metal lath, exclusive of ribs, or self-furring lath, plaster thickness 

b. When measured from face of support or backing. 

c. Because masonry and concrete surfaces may vary in plane, thickness of plaster need not be uniform. 

d. When applied over a liquid bonding agent, finish coat may be applied directly to concrete surface. 

e. Approved acoustical plaster may be applied directly to concrete or over base coat plaster, beyond the maximum 

f. Attachment shall be in accordance with Table R702.3.5. 

g. Where gypsum board is used as a base for portland cement plaster, weather-resistant sheathing paper complying 



shall be ^1^ inch minimum. 



plaster thickness shown, 
with Section R703.2 shall be provided. 



TABLE R702.1(2) 
GYPSUM PLASTER PROPORTIONS^ 



NUMBER 


COAT 


PLASTER BASE OR LATH 


MAXIMUM VOLUME AGGREGATE PER 100 POUNDS 
NEAT PLASTER" (cubic feet) 


Damp loose sand^ 


Perllte or vermiculite*^ 


Two-coat work 


Base coat 


Gypsum lath 


2.5 


2 


Base coat 


Masonry 


3 


3 


Three-coat work 


First coat 


Lath 


1" 


2 


Second coat 


Lath 


3'' 


2^ 


First and second coats 


Masonry 


3 


3 



For SI: 1 inch = 25.4 mm, 1 cubic foot = 0.0283 m^ 1 pound = 0.454 kg. 

a. Wood-fibered gypsum plaster may be mixed in the proportions of 100 pounds of gypsum to not more than 1 cubic foot of sand where applied on masonry or concrete. 

b. When determining the amount of aggr^ate in set plaster, a tolerance of 10 percent shall be allowed. 

c. Combinations of sand and lightweight aggregate may be used, provided the volume and weight relationship of the combined aggregate to gypsum plaster is maintained. 

d. If used for both first and second coats, the volume of aggregate may be 2.5 cubic feet. 

e. Where plaster is 1 inch or more in total thickness, the proportions for the second coat may be increased to 3 cubic feet. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



229 



WALL COVERING 



TABLER702.1(3) 
PORTLAND CEMENT PLASTER 



MAXIMUM VOLUME AGGREGATE PER VOLUME CEMENTITIOUS MATERIAL^ 


MINIMUM PERIOD 
MOIST COATS 


MINIMUM INTERVAL 
BETWEEN 


Coat 


Portland cement 

plaster'' maximum 

volume aggregate per 

volume cement 


Portland cement-lime plaster"^ 


Maximum volume 

lime per volume 

cement 


Maximum volume 
sand per volume 
cement and lime 


Approximate 

minimum thickness" 

curing (inches) 


First 


4 


% 


4 


3/ e 


48 Hours*^ 


48 Hourss 


Second 


5 


'U 


5 


First and second 
coats 


48 Hours 


7 Days'' 


Finish 


3* 


— 


3' 


% 


— 


Notch 



For SI: 1 inch - 25 A mm, 1 pound = 0.454 kg. 

a. When determining the amount of aggregate in set plaster, a tolerance of 10 percent may be allowed. 

b. From 10 to 20 pounds of dry hydrated lime (or an equivalent amount of lime putty) may be added as a plasticizing agent to each sack of Type I and Type II standard 
Portland cement in base coat plaster. 

c. No plasticizing agents shall be added. 

d. See Table R702.1(l). 

e. Measured from face of support or backing to crest of scored plaster 

f. Twenty-four-hour minimum period for moist curing of interior portland cement plaster 

g. Twenty-four hour minimum interval between coats of interior portland cement plaster. 

h. Finish coat plaster may be applied to interior portland cement base coats after a 48-hour period. 

i. For finish coat, plaster up to an equal part of dry hydrated lime by weight (or an equivalent volume of lime putty) may be added to Type I, Type 11 and Type III stan- 
dard Portland cement. 



R702.2 Interior plaster. Gypsum plaster or portland cement 
plastering materials shall conform to ASTM C 5, C 28, C 35, C 
37, C 59, C 61, C 587, C 588, C 631, C 847, C 897, C 933, C 
1032 and C 1047, and shall be installed or applied in confor- 
mance with ASTM C 843, C 844 and C 1063. Plaster shall not 
be less than three coats when applied over metal lath and not 
less than two coats when applied over other bases permitted by 
this section, except that veneer plaster may be applied in one 
coat not to exceed Vi^ inch (5 mm) thickness, provided the total 
thickness is as set forth in Table R702.1(l). 

R702.2.1 Support. Support spacing for gypsum or metal 
lath on walls or ceilings shall not exceed 16 inches (406 
mm) for Vg inch thick (10 mm) or 24 inches (610 mm) for 
72-inch-thick (13 mm) plain gypsum lath. Gypsum lath 
shall be installed at right angles to support framing with end 
joints in adjacent courses staggered by at least one framing 
space. 

R702.3 Gypsum board. 

R702.3.1 Materials. All gypsum board materials and 
accessories shall conform to ASTM C 36, C 79, C 475, C 
514, C 630, C 931, C 960, C 1002, C 1047, C 1 177, C 1178, 
C 1278, C 1395 or C 1396 and shall be installed in accor- 
dance with the provisions of this section. Adhesives for the 
installation of gypsum board shall conform to ASTM C 557 . 

R702.3.2 Wood framing. Wood framing supporting gyp- 
sum board shall not be less than 2 inches (5 1 mm) nomi- 
nal thickness in the least dimension except that wood 
furring strips not less than 1 -inch-by-2 inch (25 mm by 5 1 
mm) nominal dimension may be used over solid backing 
or framing spaced not more than 24 inches (610 mm) on 
center. 



R702.3.3 Steel framing. Steel framing supporting gypsum 
board shall not be less than 1 .25 inches (32 mm) wide in the 
least dimension. Light-gage nonload-bearing steel framing 
shall comply with ASTM C 645. Load-bearing steel fram- 
ing and steel framing from 0.033 inch to 0.1 12 inch (1 mm 
to 3 mm) thick shall comply with ASTMC 955. 

R702.3.4 Insulating concrete form walls. Foam plastics 
for insulating concrete form walls constructed in accor- 
dance with Sections R404.4 and R61 1 on the interior of hab- 
itable spaces shall be covered in accordance with Section 
R314.4. Use of adhesives in conjunction with; mechanical 
fasteners is permitted. Adhesives used for interior and exte- 
rior finishes shall be compatible with the insulating form 
materials. 

R702.3.5 Application. Maximum spacing of supports and 
the size and spacing of fasteners used to attach gypsum 
board shall comply with Table R702.3.5. Gypsum sheathing 
shall be attached to exterior walls in accordance with Table 
R602.3(l). Gypsum board shall be applied at right angles or 
parallel to framing members. All edges and ends of gypsum 
board shall occur on the framing members, except those 
edges and ends that are perpendicular to the framing mem- 
bers. Interior gypsum board shall not be installed where it is 
directly exposed to the weather or to water. 

R702.3.6 Fastening. Screws for attaching gypsum board to 
wood framing shall be Type W or Type S in accordance with 
ASTM C 1002 and shall penetrate the wood not less than ^/g 
inch (16 mm). Screws for attaching gypsum board to 
light-gage steel framing shall be Type S in accordance with 
ASTM C 1002 and shall penetrate the steel not less than Vg 
inch (10 mm). Screws for attaching gypsum board to steel 
framing 0.033 inch to 0. 1 12 inch (1 mm to 3 mm) thick shall 
comply with ASTM C 954. '; 



230 



2006 INTERNATIONAL RESIDENTIAL CODE^ 

I 



WALL COVERING 



TABLE R702.3.5 
MINIMUM THICKNESS AND APPLICATION OF GYPSUM BOARD 



THICKNESS 

OF GYPSUM 

BOARD 

(inches) 


APPLICATION 


ORIENTATION OF 

GYPSUM BOARD 

TO FRAMING 


MAXIMUM 

SPACING OF 

FRAMING 

MEMBERS 

(inches o.c.) 


MAXIMUM 

SPACING OF 

FASTENERS 

(inches) 


SIZE OF NAILS FOR APPLICATION 
TO WOOD FRAMING^ 


Nails^ 


Screws" 


Application without adhesive 


% 


Ceiling^ 


Perpendicular 


16 


7 


12 


13 gage, 1'// long, ^V^" head; 0.098" diameter, 1'// 
long, annular-ringed; or 4d cooler nail, 0.080" 
diameter, 1^/j," long, V^," head. 


Wall 


Either direction 


16 


8 


16 


% 


Ceiling 


Either direction 


16 


7 


12 


13 gage, l%"long, '9/54" head; 0.098" diameter, 1'//' 
long, annular-ringed; 5d cooler nail, 0.086" 
diameter, l^/g" long, '^/g/' head; or gypsum board 
nail, 0.086" diameter, 1%" long, ^2" head. 


Ceiling'' 


Perpendicular 


24 


7 


12 


Wall 


Either direction 


24 


8 


12 


Wall 


Either direction 


16 


8 


16 


% 


Ceiling 


Either direction 


16 


7 


12 


13 gage, iVg" long, 'V' head; 0.098" diameter, 1%" 
long, annular-ringed; 6d cooler nail, 0.092" 
diameter, 1^/g" long, ^f/' head; or gypsum board 
nail, 0.0915" diameter, 1%" long, ^^/^" head. 


Ceiling^ 


Perpendicular 


24 


7 


12 


Wall 


Either direction 


24 


8 


12 


Wall 


Either direction 


16 


8 


16 


Application with adtiesive 


% 


Ceiling'' 


Perpendicular 


16 


16 


16 


Same as above for ^/g" gypsum board 


Wall 


Either direction 


16 


16 


24 


%0T% 


Ceiling 


Either direction 


16 


16 


16 


Same as above for ^/j" and Vg" gypsum board, 
respectively 


Ceiling'' 


Perpendicular 


24 


12 


16 


Wall 


Either direction 


24 


16 


24 


Two 
Vg layers 


Ceiling 


Perpendicular 


16 


16 


16 


Base ply nailed as above for '/2" gypsum board; face 
ply installed with adhesive 


Wall 


Either direction 


24 


24 


24 



For SI: 1 inch = 25.4 mm. 

a. For application without adhesive, a pair of nails spaced not less than 2 inches apart or more than 2 ' /j inches apart may be used with the pair of nails spaced 1 2 inches 
on center. 

b. Screws shall be Type S or W per ASTM C 1002 and shall be sufficiently long to penetrate wood framing not less than ^/g inch and metal framing not less than ■'/g 
inch. 

c. Where metal framing is used with a clinching design to receive nails by two edges of metal, the nails shall be not less than ^/g inch longer than the gypsum board 
thickness and shall have ringed shanks. Where the metal framing has a nailing groove formed to receive the nails, the nails shall have barbed shanks or be 5d, 1 3 '/2 
gage, 1% inches long, 1%4-inch head for '/2-inch gypsum board; and 6d, 13 gage, 1% inches long, '^/g4-inch head for %-inch gypsum board. 

d. Three-eighths-inch-thick single-ply gypsum board shall not be used on a ceiling where a water-based textured finish is to be applied, or where it will be required to 
support insulation above a ceiling. On ceiling applications to receive a water-based texture material, either hand or spray applied, the gypsum board shall be applied 
perpendicular to framing. When applying a water-based texture material, the minimum gypsum board thickness shall be increased from ^/g inch to '/2 inch for 
16-inch on center framing, and from /j inch to ^/g inch for 24-inch on center framing or 72- inch sag-resistant gypsum ceiling board shall be used. 

e. Type X gypsum board for garage ceilings beneath habitable rooms shall be installed perpendicular to the ceiling framing and shall be fastened at maximum 6 
inches o.c. by minimum 1 Vg inches 6d coated nails or equivalent drywall screws. 



R702.3.7 Horizontal gypsum board diaphragm ceilings. 

Use of gypsum board shall be permitted on wood joists to 
create a horizontal diaphragm in accordance with Table 
R702.3.7. Gypsum board shall be installed perpendicular to 
ceiling framing members. End joints of adjacent courses of 
board shall not occur on the same joist. The maximum 
allowable diaphragm proportions shall be l'/2:l between 
shear resisting elements. Rotation or cantilever conditions 
shall not be permitted. Gypsum board shall not be used in 
diaphragm ceilings to resist lateral forces imposed by 
masonry or concrete construction. All perimeter edges shall 
be blocked using wood members not less than 2-inch (5 1 
mm) by 6-inch (152 mm) nominal dimension. Blocking 
material shall be installed flat over the top plate of the wall to 
provide a nailing surface not less than 2 inches (5 1 mm) in 
width for the attachment of the gypsum board. 



R702.3.8 Water-resistant gypsum backing board. Gyp- 
sum board used as the base or backer for adhesive applica- 
tion of ceramic tile or other required nonabsorbent finish 
material shall conform to ASTM C 630 or C 1 178. Use of 
water-resistant gypsum backing board shall be permitted on 
ceilings where framing spacing does not exceed 12 inches 
(305 mm) on center for '/2-inch-thick (13 mm) or 16 inches 
(406 mm) for Vg-inch-thick (16 mm) gypsum board. 
Water-resistant gypsum board shall not be installed over a 
vapor retarder in a shower or tub compartment. Cut or 
exposed edges, including those at wall intersections, shall 
be sealed as recommended by the manufacturer. 

R702.3.8.1 Limitations. Water resistant gypsum back- 
ing board shall not be used where there will be direct 
exposure to water, or in areas subject to continuous high 
humidity. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



231 



WALL COVERING 



TABLE R702.3.7 
SHEAR CAPACITY FOR HORIZONTAL WOOD-FRAMED 
GYPSUM BOARD DIAPHRAGM CEILING ASSEMBLIES 



MATERIAL 


THICKNESS OF 
MATERIAL 
(min.) (in.) 


SPACING OF FRAMING 
MEMBERS 
(max.) (in.) 


SHEAR VALUE^' " 
(pif of ceiling) 


MINIMUM FASTENER 
S,2EC,d 


Gypsum Board 


'/2 


I60.C. 


90 


5d cooler or wallboard 
nail; iVg-inch long; 0.086- 
inch shank; •V64-inch head 


Gypsum Board 


'/2 


24 o.c. 


70 


5d cooler or wallboard 
nail; iVg-inch long; 0.086- 
inch shank; 'V64-inch head 



For SI: 1 inch = 25.4 mm, 1 pound per linear foot = 1.488 kg/m. 

a. Values are not cumulative with other horizontal diaphragm values and are for short-term loading caused by wind or seismic loading. Values shall be reduced 25 per- 
cent for normal loading. 

b. Values shall be reduced 50 percent in Seismic Design Categories Dq, Dj, D2 and E. 

c. 1'//', #6 Type S or W screws may be substituted for the listed nails. 

d. Fasteners shall be spaced not more than 7 inches on center at all supports, including perimeter blocking, and not less than ^/g inch from the edges and ends of the 
gypsum board. 



R702.4 Ceramic tile. 

R702.4.1 General. Ceramic tile surfaces shall be installed in 
accordance with ANSI A108.1, A108.4, A108.5, A108.6, 
A108.il, A118.1, A118.3, A136.1 and A137.1. 

R702.4.2 Cement, fiber-cement and glass mat gypsum 
backers. Cement, fiber-cement or glass mat gypsum back- 
ers in compliance with ASTM C 1288, C 1325 or C 1178 
and installed in accordance with manufacturers' recom- 
mendations shall be used as backers for wall tile in tub and 
shower areas and wall panels in shower areas. 

R702.5 Other finishes. Wood veneer paneling and hardboard 
paneling shall be placed on wood or cold-formed steel fram- 
ing spaced not more than 16 inches (406 mm) on center. Wood 
veneer and hard board paneling less than ^1^ inch (6 mm) nom- 
inal thickness shall not have less than a Vg-inch (10 mm) gyp- 
sum board backer. Wood veneer paneling not less than 
74-inch (6 mm) nominal thickness shall conform to ANSI/ 
HPVA HP-1. Hardboard paneling shall conform to ANSI/ 
AHAA135.5. 

R702.6 Wood shakes and shingles. Wood shakes and shingles 
shall conform to CSSB Grading Rules for Wood Shakes and 
Shingles and shall be permitted to be installed directly to the 
studs with maximum 24 inches (610 mm) on-center spacing. 

R702.6.1 Attachment. Nails, staples or glue are permitted 
for attaching shakes or shingles to the wall, and attachment 
of the shakes or shingles directly to the surface shall be per- 
mitted provided the fasteners are appropriate for the type of 
wall surface material. When nails or staples are used, two 
fasteners shall be provided and shall be placed so that they 
are covered by the course above. 

R702.6.2 Furring strips. Where furring strips are used, they 
shall be 1 inch by 2 inches or 1 inch by 3 inches (25 mm by 5 1 
mm or 25 mm by 76 mm), spaced a distance on center equal 
to the desired exposure, and shall be attached to the wall by 
nailing through other wall material into the studs. 



SECTION R703 
EXTERIOR COVERING 

R703.1 General. Exterior walls shall provide the building 
with a weather-resistant exterior wall envelope. The exterior 
wall envelope shall include flashing as described in Section 
R703.8. The exterior wall envelope shall be designed and 
constructed in a manner that prevents the accumulation of 
water within the wall assembly by providing a water-resistant 
barrier behind the exterior veneer as required by Section 
R703.2. and a means of draining water that enters the assem- 
bly to the exterior. Protection against condensation in the 
exterior wall assembly shall be provided in accordance with 
Chapter 1 1 of this code. 

Exceptions: 

1. A weather-resistant exterior wall envelope shall not 
be required over concrete or masonry walls designed 
in accordance with Chapter 6 and flashed according 
to Section R703.7 or R703.8. 

2. Compliance with the requirements for a means of 
drainage, and the requirements of Section R703.2 and 
Section R703.8, shall not be required for an exterior 
wall envelope that has been demonstrated to resist 
wind-driven rain through testing of the exterior wall 
envelope, including joints, penetrations and intersec- 
tions with dissimilar materials, in accordance with 
ASTM E 331 under the following conditions: 

2.1. Exterior wall envelope test assemblies shall 
include at least one opening, one control joint, 
one wall/eave interface and one wall sill. All 
tested openings and penetrations sjhall be rep- 
resentative of the intended end-use configura- 
tion. I 

2.2. Exterior wall envelope test assemblies shall 
be at least 4 feet (1219 mm) by 8 feet (2438 
mm) in size. ' 

2.3. Exterior wall assemblies shall be tested at a 
minimum differential pressure of 6.24 pounds 
per square foot (299 Pa). 



232 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



WALL COVERING 



2.4. Exterior wall envelope assemblies shall be 
subjected to a minimum test exposure dura- 
tion of 2 hours. 

The exterior wall envelope design shall be consid- 
ered to resist wind-driven rain where the results of 
testing indicate that water did not penetrate: control 
joints in the exterior wall envelope; joints at the per- 
imeter of openings penetration; or intersections of ter- 
minations with dissimilar materials. 

R703.2 Water-resistive barrier. One layer of No. 15 asphalt 
felt, free from holes and breaks, complying with ASTM D 226 
for Type 1 felt or other approved water-resistive barrier shall be 
applied over studs or sheathing of all exterior walls. Such felt or 
material shall be applied horizontally, with the upper layer 
lapped over the lower layer not less than 2 inches (51 mm). 
Where joints occur, felt shall be lapped not less than 6 inches 
(152 mm). The felt or other approved material shall be continu- 
ous to the top of walls and terminated at penetrations and build- 
ing appendages in a manner to meet the requirements of the 
exterior wall envelope as described in Section R703.1. 

Exception: Omission of the water-resistive barrier is per- 
mitted in the following situations: 

1. In detached accessory buildings. 

2. Under exterior wall finish materials as permitted in 
Table R703.4. 

3. Under paperbacked stucco lath when the paper back- 
ing is an approved weather-resistive sheathing paper. 

R703.3 Wood, hardboard and wood structural panel siding. 

R703.3.1 Panel siding. Joints in wood, hardboard or wood 
structural panel siding shall be made as follows unless other- 
wise approved. Vertical joints in panel siding shall occur over 
framing members, unless wood or wood structural panel 
sheathing is used, and shall be shiplapped or covered with a 
batten. Horizontal joints in panel siding shall be lapped a 
minimum of 1 inch (25 mm) or shall be shiplapped or shall be 
flashed with Z-flashing and occur over solid blocking, wood 
or wood structural panel sheathing. 

R703.3.2 Horizontal siding. Horizontal lap siding shall be 
lapped a minimum of 1 inch (25 mm), or 0.5 inch (13 mm) if 
rabbeted, and shall have the ends caulked, covered with a 
batten, or sealed and installed over a strip of flashing. 

R703.4 Attachments. Unless specified otherwise, all wall 
coverings shall be securely fastened in accordance with Table 
R703.4 or with other approved aluminum, stainless steel, 
zinc-coated or other approved corrosion-resistive fasteners. 
Where the basic wind speed per Figure R301 .2(4) is 1 10 miles 
per hour (49 m/s) or higher, the attachment of wall coverings 
shall be designed to resist the component and cladding loads 
specified in Table R301 .2(2), adjusted for height and exposure 
in accordance with Table R30 1.2(3). 

R703.5 Wood shakes and shingles. Wood shakes and shingles 
shall conform to CSSB Grading Rules for Wood Shakes and 
Shingles. 

R703.5.1 Application. Wood shakes or shingles shall be 
applied either single-course or double-course over nominal 
Vj-inch (13 mm) wood-based sheathing or to furring strips 



over V2-inch (13 mm) nominal nonwood sheathing . A per- 
meable water-resistive barrier shall be provided over all I 
sheathing, with horizontal overlaps in the membrane of not | 
less than 2 inches (51mm) and vertical overlaps of not less 
than 6 inches (152 mm). Where furring strips are used, they 
shall be 1 inch by 3 inches or 1 inch by 4 inches (25 mm by 76 
mm or 25 mm by 102 mm) and shall be fastened horizontally 
to the studs with 7d or 8d box nails and shall be spaced a dis- 
tance on center equal to the actual weather exposure of the 
shakes or shingles, not to exceed the maximum exposure 
specified in Table R703.5.2. The spacing between adjacent 
shingles to allow for expansion shall not exceed 74 inch (6 
mm), and between adjacent shakes, it shall not exceed Vj inch 
(13 mm). The offset spacing between joints in adjacent 
courses shall be a minimum of V/2 inches (38 mm). 

R703.5.2 Weather exposure. The maximum weather 
exposure for shakes and shingles shall not exceed that speci- 
fied in Table R703.5.2. 

R703.5.3 Attachment. Each shake or shingle shall be held 
in place by two hot-dipped zinc-coated, stainless steel, or 
aluminum nails or staples. The fasteners shall be long 
enough to penetrate the sheathing or furring strips by a mini- 
mum of V2 inch (13 mm) and shall not be overdriven. 

R703.5.3.1 Staple attachment. Staples shall not be less 
than 16 gage and shall have a crown width of not less than 
7i6 inch (11 mm), and the crown of the staples shall be par- 
allel with the butt of the shake or shingle. In single-course 
application, the fasteners shall be concealed by the course 
above and shall be driven approximately 1 inch (25 mm) 
above the butt line of the succeeding course and V4 inch (19 
mm) from the edge. In double-course apphcations, the 
exposed shake or shingle shall be face-nailed with two cas- 
ing nails, driven approximately 2 inches (5 1 mm) above the 
butt hne and V4 inch (19 mm) from each edge. In all apphca- 
tions, staples shall be concealed by the course above. With 
shingles wider than 8 inches (203 mm) two additional nails 
shall be required and shaU be naUed approximately 1 inch 
(25 mm) apart near the center of the shingle. 

R703.5.4 Bottom courses. The bottom courses shall be dou- 
bled. 

R703.6 Exterior plaster. Installation of these materials shall I 
be in compUance with ASTM C 926 and ASTM C 1063 and the I 
provisions of this code. | 

R703.6.1 Lath. All lath and lath attachments shall be of cor- 
rosion-resistant materials. Expanded metal or woven wire 
lath shall be attached with 1 Vj-inch-long (38 mm), 11 gage 
nails having a Vig-inch (11.1 mm) head, or 7g-inch-long 
(22.2 mm), 16 gage staples, spaced at no more than 6 inches 
(152 mm), or as otherwise approved. 

R703.6.2 Plaster. Plastering with portland cement plaster 
shall be not less than three coats when applied over metal lath 
or wire lath and shall be not less than two coats when applied 
over masonry, concrete, pressure-preservative treated wood I 
or decay-resistant wood as specified in Section R319.i or | 
gypsum backing. If the plaster surface is completely covered 
by veneer or other facing material or is completely concealed, 
plaster application need be only two coats, provided the total 
thickness is as set forth in Table R702.1(l). 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



233 



WALL COVERING 







TABLE R703.4 
WEATHER-RESISTANT SIDING ATTACHMENT AND MINIMUM THICKNESS 






SIDING MATERIAL 


NOMINAL 

THICKNES^ 

(inches) 


JOINT 
TREATMENT 


WATER- 
RESISTIVE 

BARRIER 
REQUIRED 


TYPE OF SUPPORTS FOR THE SIDING MATERIAL AND FASTENERS""'," 


Wood or wood 
structural 

panel 
sheathing 


Fiberboard 

sheathing into 

stud 


Gypsum 
sheathing 
into stud 


Foam 

plastic 

sheathing 

into stud 


Direct to 
studs 


Number or 
spacing of 
fasteners 


Horizontal 
aluminum^ 


Without 
insulation 


0.0 19f 
0.024 


Lap 


Yes 


0.120 nail 
1 V2" long 


0.120 nail 
1" long 


0.120 nail 
2" long 


0.120 naily 


Not 
allowed 


Same as stud 
spacing 


Lap 


Yes 


0.120 nail 
1 1/2" long 


0.120 nail 
2" long 


0.120 nail 
2" long 


0.120 naily 


Not 
allowed 


With 
insulation 


0.019 


Lap 


Yes 


0.120 nail 
1 V2" long 


0.120 nail 
21/2" long 


0.120 nail 
2V2" long 


0.120 naily 


0.120 nail 
1 1/2" long 


Brick veneer^ 
Concrete masonry 
veneer^ 


2 
2 


Section R703 


Yes 
(Note 1) 


See Section R703 and Figure R703.78 


Hardboard'^ 

Panel siding-vertical 


V,6 


— 


Yes 


Note n 


Noten 


Noten 


Noten 


Noten 


6" panel edges 
12" inter. sup.° 


Hardboard*^ 

Lap-siding-horizontal 


V,6 


Noteq 


Yes 


Notep 


Notep 


Notep 


Notep 


Notep 


Same as stud 

spacing 
2 per bearing 


Steel'' 


29 ga. 


Lap 


Yes 


0.113 nail IV 
Staple-13/4" 


0. 113 nail 2 V 
Staple-21/2" 


0.113 nail 

2'/2" 

Staple-2V4" 


0.113 naily 
Staple^ 


Not allowed 


Same as stud 
spacing 


Stone veneer 


2 


Section R703 


Yes 

(Note 1) 


See Section R703 and Figure R703 .78 


Particleboard panels 


V8-'/2 


— 


Yes 


6d box nail 
(2" X 0.099") 


6d box nail 
(2" X 0.099") 


6d box nail 
(2" X 0.099") 


box nailv 


6d box nail 
(2" X 0.099"), 
Vg not allowed 


6" panel edge, 
12" inter, sup. 


Vs 


— 


Yes 


6d box nail 
(2" X 0.099") 


8d box nail 
(21/2" X 0.1 13") 


8d box nail 
(21/2" X 0.113") 


box naily 


6d box nail 
(2" X 0.099") 


Plywood panel' 
(exterior grade) 


Vg 


— 


Yes 


0.099 nail-2" 


0.113 nail-2V2" 


0.099 nail-2" 


0.113 naily 


0.099 nail-2" 


6" on edges, 
12" inter, sup. 


Vinyl siding"" 


0.035 


Lap 


Yes 


0.120 nail IV2" 
Staple-13/4" 


0.120 nail 2" 
Staple-2'/2" , 


0.120 nail 2" 
Staple-2'/2" 


0.120 naily 
Staple^ 


Not allowed 


Same as stud 
spacing 


Wood) rustic, drop 


^/g Min 


Lap 


Yes 


Fastener penetration into stud-1" 


0.113 nail- 

2V2" 
Staple-2" 


Face nailing up 

' to 6" widths, 

1 nail per 

bearing; 

8" widths 

and over, 

2 nails per 

bearing 


Shiplap 


'%2 Average 


Lap 


Yes 


Bevel 


^/l6 


Butt tip 


Vi6 


Lap 


Yes 


Fiber cement panel 
siding'' 


Vl6 


Notes 


Yes 
Notex 


6d corrosion- 
resistant naiF 


6d corrosion- 
resistant nail' 


6d corrosion- 
resistant nail' 


6d corrosion- 
resistant 
nail'- y 


4d corrosion- 
resistant nail" 


6" o.c. on 

edges, 12" o.c. 

on intermed. 

studs 


Fiber cement lap siding'' 


V,6 


Note V 


Yes 
Notex 


6d corrosion- 
resistant nail' 


6d corrosion- 
resistant nail' 


6d corrosion- 
resistant nail' 


6d corrosion- 
resistant 
nail'- y 


6d corrosion- 
resistant nail* 


Note w 



ForSL 1 inch = 25.4 mm. '; 

a. Based on stud spacing of 16 inches on center where studs are spaced 24 inches, siding shall be applied to sheathing approved for that spacing. : 

b. Nail is a general description and shall be T-head, modified round head, or round head with smooth or deformed shanks. 

c. Staples shall have a minimum crown width of ^/jg-inch outside diameter and be rhanufactured of minimum 16 gage wire. ! 

d. Nails or staples shall be aluminum, galvanized, or rust-preventative coated and shall be driven into the studs for fiberboard or gypsum backing. | 

e. Aluminum nails shall be used to attach aluminum siding. j 

f. Aluminum (0.019 inch) shall be unbacked only when the maximum panel width is 10 inches and the maximum flat area is 8 inches. The tolerance for aluminum 
siding shall be 4-0.002 inch of the nominal dimension. j 

Ig. All attachments shall be coated with a corrosion-resistant coating. ■ 

h. Shall be of approved type. 

{continued) j 



234 



2006 INTERNATIONAL RESIDENTIAL CODE^ 

I 



WALL COVERING 



Footnotes to Table R703.4 — continued 

i. Three-eighths-inch plywood shall not be applied directly to studs spaced more than 1 6 inches on center when long dimension is parallel to studs. Plywood '/2-inch 
or thinner shall not be applied directly to studs spaced more than 24 inches on center. The stud spacing shall not exceed the panel span rating provided by the manu- 
facturer unless the panels are installed with the face grain perpendicular to the studs or over sheathing approved for that stud spacing. 

j. Wood board sidings appUed vertically shall be nailed to horizontal nailing strips or blocking set 24 inches on center. Nails shall penetrate 1 V2 inches into studs, 
studs and wood sheathing combined, or blocking. A weather-resistive membrane shall be installed weatherboard fashion under the vertical siding unless the siding 
boards are lapped or battens are used. 

k. Hardboard siding shall comply with AHA A135.6. 

1. For masonry veneer, a weather-resistive sheathing paper is not required over a sheathing that performs as a weather-resistive barrier when a 1 -inch air space is pro- 
vided between the veneer and the sheathing. When the 1 -inch space is filled with mortar, a weather-resistive sheathing paper is required over studs or sheathing. 

m. Vinyl siding shall comply with ASTM D 3679. 

n. Minimum shank diameter of 0.092 inch, minimum head diameter of 0.225 inch, and nail length must accommodate sheathing and penetrate framing 1 '/2 inches. 

o. When used to resist shear forces, the spacing must be 4 inches at panel edges and 8 inches on interior supports. 

p. Minimum shankdiameter of 0.099 inch, minimum head diameter of 0.240 inch, and nail length must accommodate sheathing and penetrate framing 1 '/2 inches. 

q. Vertical end joints shall occur at studs and shall be covered with a joint cover or shall be caulked. 

r. Fiber cement siding shall comply with the requirements of ASTM C 1186. 

s. See Section R703. 10.1. 

t. Minimum 0.102" smooth shank, 0.255" round head. 

u. Minimum 0.099" smooth shank, 0.250" round head. 

V. See Section R703. 10.2. 

w. Face nailing: 2 nails at each stud. Concealed nailing: one 1 1 gage 1 V2 galv. roofing nail (0.37 1" head diameter, 0. 120" shank) or 6d galv. box nail at each stud. 

X. See Section R703.2 exceptions. 

y. Minimum nail length must accommodate sheathing and penetrate framing 1V2 inches. 

z. Adhered masonry veneer shall comply with the requirements in Sections 6.1 and 6.3 of ACI 530/ASCE 5/TMS-402. 



TABLE R703.5.2 
MAXIMUM WEATHER EXPOSURE FOR WOOD SHAKES AND SHINGLES ON EXTERIOR WALLS^'"^ 

(Dimensions are in inches) 



LENGTH 


EXPOSURE FOR SINGLE COURSE 


EXPOSURE FOR DOUBLE COURSE 


Shingles'' 
16 
18 

24 


7V2 
8V2 
IIV2 


12'' 
14c 

16 


Shakes'* 
18 

24 


8V2 
IIV2 


14 
18 



For SI: 1 inch = 25.4 mm. 

a. Dimensions given are for No. 1 grade. 

b. A maximum 10-inch exposure is permitted for No. 2 grade. 

c. A maximum 1 1 -inch exposure is permitted for No. 2 grade. 



On wood-frame construction with an on-grade floor slab 
system, exterior plaster shall be applied to cover, but not 
extend below, lath, paper and screed. 

The proportion of aggregate to cementitious materials 
shall be as set forth in Table R702.1(3). 

R703.6.2.1 Weep screeds. A minimum 0.019-inch (0.5 
mm) (No. 26 galvanized sheet gage), corrosion-resistant 
weep screed or plastic weep screed, with a minimum ver- 
tical attachment flange of 3V2 inches (89 mm) shall be 
provided at or below the foundation plate line on exterior 
stud walls in accordance with ASTM C 926. The weep 
screed shall be placed a minimum of 4 inches (102 mm) 
above the earth or 2 inches (51 mm) above paved areas 
and shall be of a type that will allow trapped water to 
drain to the exterior of the building. The weather-resis- 



tant barrier shall lap the attachment flange. The exterior 
lath shall cover and terminate on the attachment flange of 
the weep screed. 

R703.6.3 Water-resistive barriers. Water-resistive barri- 
ers shall be installed as required in Section R703.2 and, 
where appHed over wood-based sheathing, shall include a 
water-resistive vapor-permeable barrier with a performance 
at least equivalent to two layers of Grade D paper. 

Exception: Where the water-resistive barrier that is 
applied over wood-based sheathing has a water resis- 
tance equal to or greater than that of 60 minute Grade D 
paper and is separated from the stucco by an intervening, 
substantially nonwater-absorbing layer or designed 
drainage space. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



235 



WALL COVERING 



SEALANT 



FLASHING AND WEEPHOLES 
VENEER 




WALLBOARD 



WATER-RESISTIVE BARRIER OR 
APPROVED WATER-REPELLANT 
SHEATHING 



MASONRY VENEER 



1 IN. AIR SPACE OR 

1 IN. MORTARED SPACE' 



WATER-RESISTIVE BARRIER OR 
APPROVED WATER-REPELLANT 
SHEATHING 



METAL TIE" 
FLASHING 

WEEPHOLE 



«vx////\V^^//// 
////\\>\V//\\V 

x-^A\V//\\\- 
\\V- 



For SI: 1 inch = 25.4 mm. 



WALLBOARD 



SHEATHING 




A/- 



• ANCHOR BOLT 
GROUTED FULL 



FIGURE R703.7 
MASONRY VENEER WALL DETAILS 

(continued) 



236 



2006 INTERNATIONAL RESIDENTIAL CODE' 



WALL COVERING 



ROORNG 



MIN. CLEARANCE OF 
3/4-IN. (19 mm) 

METAL T!Eb 



WATER-RESISTIVE BARRIER OR 
APPROVED VyATER-REPELLANT ^ 
SHEATHING 

MASONRY VENEER 



METAL TIEb 




1 IN. AIR SPACE OR 

1 IN. MORTARED SPACES 



WATER-RESISTIVE BARRIER OR 
APPROVED WATER-REPELLANT 
SHEATHING ^^ 

METAL TIE& 



FUSHINGa 
STEEL LINTELd ~-^ ^^ 

WEEPHOLEa 
SEAUNT 

MASONRY VENEER 




WALLBOARD 

INSUUTION BETWEEN STUDS 



For SI: 1 inch = 25.4 mm. 

a. See Sections R703.7.5, R703.7.6 and R703.8. 

b. See Sections R703.2 and R703.7,4. 

c. See Sections R703.7.4.2 and R703.7.4.3. 

d. See Section R703.7.3. 



FIGURE R703.7— continued 
MASONRY VENEER WALL DETAILS 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



237 



WALL COVERING 



R703.7 Stone and masonry veneer, general. Stone and 
masonry veneer shall be installed in accordance with this chap- 
ter, Table R703.4 and Figure R703.7. These veneers installed 
over a backing of wood or cold-formed steel shall be limited to 
the first story above-grade and shall not exceed 5 inches (127 
mm) in thickness. 

Exceptions: 

1 . For all buildings in Seismic Design Categories A, B 
and C, exterior stone or masonry veneer, as specified 
in Table R703.7(l), with a backing of wood or steel 
framing shall be permitted to the height specified in 
Table R703. 7(1) above a noncombustible foundation. 
Wall bracing at exterior and interior braced wall lines 
shall be in accordance with Section R602.10 or 
R603.7, and the additional requirements of Table 
R703.7(l). 

2. For detached one- or two-family dwellings in Seismic 
Design Categories Dq, Di and Dj, exterior stone or 
masonry veneer, as specified in Table R703.7(2), 
with a backing of wood framing shall be permitted to 
the height specified in Table R703.7(2) above a 
noncombustible foundation. Wall bracing and hold 
downs at exterior and interior braced wall lines shall 
be in accordance with Sections R602. 10 and R602. 1 1 
and the additional requirements of Table R703.7(2). 
In Seismic Design Categories Dq, D, and D2, cripple 
walls shall not be permitted, and required interior 



braced wall lines shall be supported on continuous l| 
foundations. | 

R703.7.1 Interior veneer support. Veneers used as interior 
wall finishes shall be permitted to be supported on wood or 
cold-formed steel floors that are designed to support the 
loads imposed. 

R703.7.2 Exterior veneer support. Except in Seismic 
Design Categories Dq, Dj and Dj, exterior masonry veneers | 
having an installed weight of 40 pounds per square foot ( 1 95 
kg/m^) or less shall be permitted to be supported on wood or 
cold-formed steel construction. When masonry veneer sup- 
ported by wood or cold-formed steel construction adjoins 
masonry veneer supported by the foundation, there shall be 
a movement joint between the veneer supported by the 
wood or cold-formed steel construction and the veneer sup- 
ported by the foundation. The wood or cold-formed steel 
construction supporting the masonry veneer shall be 
designed to limit the deflection to Vgoo of the span for the 
supporting members. The design of the wood or 
cold-formed steel construction shall consider the weight of 
the veneer and any other loads. 

R703.7.2.1 Support by steel angle. A minimum 6 inches 
by 4 inches by Vj^ inch (152 mm by 102 mm by 8 mm) 
steel angle, with the long leg placed vertically, shall be 
anchored to double 2 inches by 4 inches (51 mm by 102 
mm) wood studs at a maximum on-center spacing of 16 
inches (406 mm). Anchorage of the steel angle at every 
double stud spacing shall be a minimum of two 7,6 inch 



TABLE R703.7(1) 

STONE OR MASONRY VENEER LIMITATIONS AND REQUIREMENTS, WOOD 

OR STEEL FRAMING, SEISMIC DESIGN CATEGORIES A, B AND C 



SEISMIC DESIGN 
CATEGORY 


NUMBER OF 
WOOD OR STEEL 
FRAMED STORIES 


MAXIMUM HEIGHT 
OF VENEER ABOVE 
NONCOMBUSTIBLE 
FOUNDATION^ (feet) 


MAXIMUM NOMINAL 
THICKNESS OF 
VENEER (inches) 


MAXIMUM WEIGHT 
OF VENEER (psf)" 


WOOD OR STEEL 
FRAMED STORY 


MINIMUM SHEATHING 

AMOUNT (percent of 

braced wall line 

length)'^ 


AorB 


Steel: 1 or 2 
Wood: 1,2 or 3 


30 


5 


50 


all 


Table R602. 10. lor Table 
R603.7 


C 


1 


30 


5 


50 


1 only 


Table R602. 10. lor Table 
R603.7 


2 


30 


5 


50 


top 


Table R602. 10. lor Table 
R603.7 


bottom 


1.5 times length required 
by Table R602. 10. lor 
1.5 times length required 
by Table R603.7 


Wood only: 3 


30 


5 


50 


top 


Table R602. 10. 1 


middle 


1.5 times length required 
by Table R602. 10.1 


bottom 


1.5 times length required 
by Table R602. 10.1 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.479 kPa. ! 

a. An Additional 8 feet is permitted for gable end walls. See also story height limitations of Section R301.3. 

b. Maximum weight is installed weight and includes weight of mortar, grout, lath and other materials used for installation. Where veneer is placed oii both faces of a 



wall, the combined weight shall not exceed that specified in this table. 
Applies to exterior and interior braced wall lines. 



238 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



WALL COVERING 



TABLE R703.7(2) 
STONE OR MASONRY VENEER LIMITATIONS AND REQUIREMENTS, ONE- AND TWO-FAMILY DETACHED DWELLINGS, WOOD 

FRAMING, SEISMIC DESIGN CATEGORIES Dq, D^ AND D^ 



SEISMIC 

DESIGN 

CATEGORY 


NUMBER 

OF 

WOOD 

FRAMED 

STORIES^ 


MAXIMUM HEIGHT 
OF VENEER ABOVE 
NONCOMBUSTIBLE 

FOUNDATION OR 

FOUNDATION WALL 

(feet) 


MAXIMUM 

NOMINAL 

THICKNESS 

OF VENEER 

(inches) 


MAXIMUM 

WEIGHT OF 

VENEER 

(psf)" 


WOOD 
FRAMED 
STORY 


MINIMUM 

SHEATHING 

AMOUNT (percent 

of braced wall line 

length)^ 


MINIMUM 

SHEATHING 

THICKNESS AND 

FASTENING 


SINGLE 

STORY 

HOLD DOWN 

FORCE (lb)" 


CUMULATIVE 
HOLD DOWN 
FORCE (Ib)^ 


Do 


1 


20^ 


4 


40 


1 only 


35 


Vig-inch wood 
structural panel 
sheathing with 8d 
common nails 
spaced at 4 inches 
on center at panel 
edges, 12 inches 
on center at 
intermediate 
supports. 8d 
common nails at 4 
inches on center at 
braced wall panel 
end posts with 
hold down 
attached. 


N/A 





2 


20f 


4 


40 


top 


35 


1900 





bottom 


45 


3200 


5100 


3 


308 


4 


40 


top 


40 


1900 





middle 


45 


3500 


5400 


bottom 


60 


3500 


8900 


D, 


1 


20f 


4 


40 


1 only 


45 


2100 





2 


20^ 


4 


40 


top 


45 


2100 





bottom 


45 


3700 


5800 


3 


20f 


4 


40 


top 


45 


2100 





middle 


45 


3700 


5800 


bottom 


60 


3700 


9500 


D2 


1 


20f 


3 


30 


1 only 


55 


2300 





2 


20^ 


3 


30 


top 


55 


2300 





bottom 


55 


3900 


6200 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.479 kPa, 1 pound-force = 4.448 N. 

a. Cripple walls are not permitted in Seismic Design Categories Dq, Di and D2. 

b. Maximum weight is installed weight and includes weight of mortar, grout and lath, and other materials used for installation. 

c. Applies to exterior and interior braced wall lines. 

d. Hold down force is minimum allowable stress design load for connector providing uplift tie from wall framing at end of braced wall panel at the noted story to wall 
framing at end of braced wall panel at the story below, or to foundation or foundation wall. Use single story hold down force where edges of braced wall panels do 
not align; a continuous load path to the foundation shall be maintained. [See Figure R703.7(l)(b)]. 

e. Where hold down connectors from stories above align with stories below, use cumulative hold down force to size middle and bottom story hold down connectors. 
[See Figure R703.7(l)(a)]. 

f . The veneer shall not exceed 20 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls, or 30 feet in height with an 
additional 8 feet for gable end walls where the lower 10 feet has a backing of concrete or masonry wall. See also story height limitations of Section R301.3. 

g. The veneer shall not exceed 30 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls. See also story height limi- 
tations of Section R301.3. 



(11 mm) diameter by 4 inch (102 mm) lag screws. The 
steel angle shall have a minimum clearance to underlying 
construction of V,6 inch (2 mm). A minimum of two-thirds 
the width of the masonry veneer thickness shall bear on 
the steel angle. Flashing and weep holes shall be located in 
the masonry veneer wythe in accordance with Figure 
R703.7.2.1. The maximum height of masonry veneer 
above the steel angle support shall be 12 feet, 8 inches 
(3861 mm). The air space separating the masonry veneer 
from the wood backing shall be in accordance with Sec- 
tions R703.7.4 and R703 .7.4.2. The method of supportfor 
the masonry veneer on wood construction shall be con- 
structed in accordance with Figure R703.7.2.1. 

The maximum slope of the roof construction without 
stops shall be 7: 12. Roof construction with slopes greater 
than 7:12 but not more than 12:12 shall have stops of a 
minimum 3 inch x 3 inch x 74 inch (76 mm x 76 mm x 6 
mm) steel plate welded to the angle at 24 inches (610 
mm) on center along the angle or as approved by the 
building official. 



R703.7.2.2 Support by roof construction. A steel angle 
shall be placed directly on top of the roof construction. 
The roof supporting construction for the steel angle shall 
consist of a minimum of three 2-inch by 6-inch (5 1 mm by 
152 nun) wood members. The wood member abutting the 
vertical wall stud construction shall be anchored with a 
minimum of three Vg-inch (16 mm) diameter by 5-inch 
(127 mm) lag screws to every wood stud spacing. Each 
additional roof member shall be anchored by the use of 
two lOd nails at every wood stud spacing. A minimum of 
two-thirds the width of the masonry veneer thickness shall 
bear on the steel angle. Flashing and weep holes shall be 
located in the masonry veneer wythe in accordance with 
Figure R703.7.2.2. The maximum height of the masonry 
veneer above the steel angle support shall be 12 feet, 8 
inches (3861 mm). The air space separating the masonry 
veneer from the wood backing shall be in accordance with 
Sections R703.7.4 and R703.7.4.2. The support for the 
masonry veneer on wood construction shall be con- 
structed in accordance with Figure R703.7.2.2. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



239 



WALL COVERING 



EDGES OF 

BFRACED 

WALL PANELS 

ALIGN. 

HOLD DOWNS 

ALIGN. 



SINGLE STORY 

HOLD DOWN 

FORCE 

-TOP STORY 



BRACED WALL 
PANEL 



CUMULATIVE 

HOLD DOWN 

FORCE 

-MIDDLE STORY 

BRACED WALL 
PANEL 



CUMULATIVE 

HOLD DOWN 

FORCE 

-BOTTOM STORY 




(a) 



(b) 



EDGES OF 

BRACED WALL 

PANELS 

DO NOT ALIGN. 

USE (a) WHERE 

THEY ALIGN. 



BRACED WALL 
PANEL 



SINGLE STORY 
HOLD DOWN 
FORCE - TOP 
STORY 

BRACED WALL 
PANEL 



SINGLE STORY 
HOLD DOWN 
FORCE 
-MIDDLE STORY 



BRACED WALL 
PANEL 

SINGLE STORY 
HOLD DOWN 
FORCE 
-BOTTOM STORY 



(a) Braced wall panels stacked (aligned story to story). Use cumulative hold down force. 

(b) Braced wall panels not stacked. Use single story hold down force. 



FIGURE R703.7(1) 

HOLD DOWNS AT EXTERIOR AND INTERIOR BRACED WALL PANELS 

WHEN USING STONE OR MASONRY VENEER 



SHEATHING 



STUD 



STEEL ANGLE 
ATTACHED TO STUD 
WITH FASTENERS 



FASTENERS 




BRICK VENEER 
VENEER TIE 

FLASHING 
WEEP HOLE 
COUNTERFLASHiNG 
BASE FLASHING 



ROOF SHEATHING 



ROOF FRAMING 



SUPPORT BY STEEL ANGLE 

FIGURE R703.7.2.1 
EXTERIOR MASONRY VENEER SUPPORT BY STEEL ANGLES 



240 



2006 INTERNATIONAL RESIDENtlAL CODE*^ 



WALL COVERING 



SHEATHING 



STUD 



STEEL ANGLE 
ATTACHED TO STUD 
WITH FASTENERS 



FASTENERS 




BRICK VENEER 
VENEER TIE 

FLASHING 
WEEP HOLE 

COUNTERFLASHING 
BASE FLASHING 



TRIPLE RAFTERS 
ATTACHED TO STUDS 



SUPPORT BY ROOF MEMBERS 

FIGURE R703.7.2.2 
EXTERIOR MASONRY VENEER SUPPORT BY ROOF MEMBERS 



The maximum slope of the roof construction without 
stops shall be 7:12. Roof construction with slopes greater 
than 7:12 but not more than 12:12 shall have stops of a 
minimum 3 inch x 3 inch x V4 inch (76 mm x 76 mm x 6 
mm) steel plate welded to the angle at 24 inches (610 nmi) 
on center along the angle or as approved by the building 
official. 

R703.7.3 Lintels. Masonry veneer shall not support any ver- 
tical load other than the dead load of the veneer above. Veneer 
above openings shall be supported on hntels of 
noncombustible materials and the allowable span shall not 
exceed the value set forth in Table R703.7.3. The lintels shall 
have a length of bearing not less than 4 inches (102 mm). 

R703.7.4 Anchorage. Masonry veneer shall be anchored to 
the supporting wall with corrosion-resistant metal ties. 
Where veneer is anchored to wood backings by corrugated 
sheet metal ties, the distance separating the veneer from the 
sheathing material shall be a maximum of a nominal 1 inch 
(25 mm). Where the veneer is anchored to wood backings 
using metal strand wire ties, the distance separating the 
veneer from the sheathing material shall be a maximum of 
4V2 inches (114 mm). Where the veneer is anchored to 
cold-formed steel backings, adjustable metal strand wire ties 
shall be used. Where veneer is anchored to cold-formed steel 
backings, the distance separating the veneer from the sheath- 
ing material shall be a maximum of 4V2 inches (114 mm). 

R703.7.4.1 Size and spacing. Veneer ties, if strand wire, 
shall not be less in thickness than No. 9 U.S. gage [(0. 148 
in.) (4 mm)] wire and shall have a hook embedded in the 
mortar joint, or if sheet metal, shall be not less than No. 



22 U.S. gage by [(0.0299 in.)(0.76 mm)] % inch (22 mm) 
corrugated. Each tie shall be spaced not more than 24 
inches (610 mm) on center horizontally and vertically 
and shall support not more than 2.67 square feet (0.25 
m^) of wall area. 

Exception: In Seismic Design Category Dq, D, or Dj | 
or townhouses in Seismic Design Category C or in 
wind areas of more than 30 pounds per square foot 
pressure (1.44 kPa), each tie shall support not more 
than 2 square feet (0.2 m^) of wall area. 

R703.7.4.1.1 Veneer ties around wall openings. 

Veneer ties around wall openings. Additional metal 
ties shall be provided around all wall openings greater 
than 16 inches (406 mm) in either dimension. Metal 
ties around the perimeter of openings shall be spaced 
not more than 3 feet (9144 mm) on center and placed 
within 12 inches (305 mm) of the wall opening. 

R703.7.4.2 Air space. The veneer shall be separated 
from the sheathing by an air space of a minimum of a 
nominal 1 inch (25 mm) but not more than 4V2 inches I 
(114 mm). I 

R703.7.4. 3 Mortar or grout fill. As an alternate to the 
air space required by Section R703 .7 .4.2, mortar or grout 
shall be permitted to fill the air space .When the air space I 
is filled with mortar, a water-resistive barrier is required | 
over studs or sheathing. When filling the air space, 
replacing the sheathing and water-resistive barrier with a 
wire mesh and approved water-resistive barrier or an 
approved water-resistive barrier-backed reinforcement 
attached directly to the studs is permitted. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



241 



WALL COVERING 





TABLE R703.7.3 
ALLOWABLE SPANS FOR LINTELS SUPPORTING MASONRY VENEERS "•<= 




SIZE OF STEEL ANGLE^^ 
(inches) 


NO STORY ABOVE 


ONE STORY ABOVE 


TWO STORIES ABOVE 


NO. OF V/ OR EQUIVALENT 
REINFORCING BARS'" 


3 X 3 X V4 


6'-0" 


4'-6" 


3'-0" 


1 


4 X 3 X V4 


8'-0" 


6'-0" 


4'-6" 


1 


5x3V2xVi6 


lO'-O" 


8'-0", 


6'-0" 


2 


6x3V2x5/i6 


14'-0" 


9'-6" 


7'-0" 


2 


2-6 X 3V2 X 5/16 


20'-0" 


12'-0" 


9'-6" 


4 



For SI: 1 inch = 25.4 mm, 1 foot =304.8 mm. 

a. Long leg of the angle shall be placed in a vertical position. 

b. Depth of reinforced lintels shall not be less than 8 inches and all cells of hollow masonry lintels shall be grouted solid. Reinforcing bars shall extend not less than i 
inches into the support. 

c. Steel members indicated are adequate typical examples; other steel members meeting structural design requirements may be used. 



R703.7.5 Flashing. Flashing shall be located beneath the 
first course of masonry above finished ground level above 
the foundation wall or slab and at other points of support, 
including structural floors, shelf angles and lintels when 
masonry veneers are designed in accordance with Section 
R703.7. See Section R703.8 for additional requirements. 

R703.7.6 Weepholes. Weepholes shall be provided in the 
outside wythe of masonry walls at a maximum spacing of 33 
inches (838 mm) on center. Weepholes shall not be less than 
^/i6 inch (5 mm) in diameter. Weepholes shall be located 
immediately above the flashing. 

R703.8 Flashing. Approved corrosion-resistant flashing shall 
be applied shingle-fashion in such a manner to prevent entry of 
water into the wall cavity or penetration of water to the building 
structural framing components. The flashing shall extend to the 
surface of the exterior wall finish. Approved corrosion-resis- 
tant flashings shall be installed at all of the following locations: 

1 . Exterior window and door openings. Flashing at exterior 
window and door openings shall extend to the surface of 
the exterior wall finish or to the water-resistive barrier 
for subsequent drainage. 

2. At the intersection of chimneys or other masonry con- 
struction with frame or stucco walls, with projecting lips 
on both sides under stucco copings. 

3 . Under and at the ends of masonry , wood or metal copings 
and sills. 

4. Continuously above all projecting wood trim. 

5. Where exterior porches, decks or stairs attach to a wall or 
floor assembly of wood-frame construction. 

6. At wall and roof intersections. 

7. At built-in gutters. 

R703.9 Exterior insulation finish systems, general. All 

Exterior Insulation Finish Systems (EIFS) shall be installed in 
accordance with the manufacturer's installation instructions 
and the requirements of this section. Decorative trim shall not 
be face nailed through the EIFS. The EIFS shall terminate not 
less than 6 inches (152 mm) above the finished ground level. 

R703.9.1 Water-resistive barrier. All EIFS shall have a 
water-resistive barrier applied between the underlying 



water-sensitive building components and the exterior insula- 
tion, and a means of draining water to the exterior of the 
veneer. A water-resistive barrier shall be compliant with 
ASTM D 226 Type I asphalt saturated felt or equivalent, shall 
be apphed horizontally with the upper layer lapped over the 
lower layer not less than 2 inches (5 1 mm), and shall have all 
vertical joints lapped not less than 6 inches (152 mm). 

R703.9.2 Flashing, general. Flashing of EIFS shall be pro- 
vided in accordance with the requirements of Section 
R703.8. 

R703.10 Fiber cement siding. 

R703.10.1 Panel siding. Panels shall be installed with the 
long dimension parallel to framing. Vertical joints shall 
occur over framing members and shall be sealed with caulk- 
ing or covered with battens. Horizontal joints shall be 
flashed with Z-flashing and blocked with solid wood fram- 
ing. 

R703.10.2 Horizontal lap siding. Lap siding shall be 
lapped a minimum of 1 V4 inches (32 mm) and shall have the 
ends sealed with caulking, covered with an H-section joint 
cover, or located over a strip of flashing. Lap siding courses 
may be installed with the fastener heads exposed or con- 
cealed, according to approved manufacturers' installation 
instructions. 

R703.il Vinyl siding. Vinyl siding shall be certified and 
labeled as conforming to the requirements of ASTM D 3679 
by an approved quality control agency. 

R703.il. 1 Installation. Vinyl siding, soffit and accessories 
shall be installed in accordance with the manufacturer's 
installation instructions. 



242 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 8 

ROOF-CEILING CONSTRUCTION 



SECTION R801 
GENERAL 

R801.1 Application. The provisions of this chapter shall con- 
trol the design and construction of the roof-ceiling system for 
all buildings. 

R801.2 Requirements. Roof and ceiling construction shall be 
capable of accommodating all loads imposed according to Sec- 
tion R301 and of transmitting the resulting loads to the support- 
ing structural elements. 

R801.3 Roof drainage. In areas where expansive or collaps- 
ible soils are known to exist, all dwellings shall have a con- 
trolled method of water disposal from roofs that will collect 
and discharge roof drainage to the ground surface at least 5 feet 
(1524 mm) from foundation walls or to an approved drainage 
system. 



SECTION R802 
WOOD ROOF FRAMING 

R802.1 Identification. Load-bearing dimension lumber for 
rafters, trusses and ceiling joists shall be identified by a grade 
mark of a lumber grading or inspection agency that has been 
approved by an accreditation body that complies with DOC PS 
20. In lieu of a grade mark, a certificate of inspection issued by 
a lumber grading or inspection agency meeting the require- 
ments of this section shall be accepted. 

R802.1.1 Blocking. Blocking shall be a minimum of utility 
grade lumber. 

R802.1.2 End-jointed lumber. Approved end-jointed lum- 
ber identified by a grade mark conforming to Section 
R802. 1 may be used interchangeably with solid-sawn mem- 
bers of the same species and grade. 

R802.1.3 Fire-retardant-treated wood. Fire-retardant- 
treated wood (FRTW) is any wood product which, when 
impregnated with chemicals by a pressure process or other 
means during manufacture, shall have, when tested in 
accordance with ASTM E 84, a listed flame spread index of 
25 or less and shows no evidence of significant progressive 
combustion when the test is continued for an additional 
20-minute period. In addition, the flame front shall not 
progress more than 10.5 feet (3200 mm) beyond the center 
line of the burners at any time during the test. 

R802.1.3.1 Labeling. Fire-retardant-treated lumber and 
wood structural panels shall be labeled. The label shall 
contain: 

1 . The identification mark of an approved agency in 
accordance with Section 1703.5 of the Interna- 
tional Building Code. 

2. Identification of the treating manufacturer. 

3. The name of the fire-retardant treatment. 



4. The species of wood treated. 

5. Flame spread and smoke-developed rating. 

6. Method of drying after treatment. 

7. Conformance to appropriate standards in accor- 
dance with Sections R802.1.3.2 through 
R802. 1.3.5. 

8. For FRTW exposed to weather, or a damp or wet 
location, the words "No increase in the listed clas- 
sification when subjected to the Standard Rain 
Test" (ASTM D 2898). 

R802.1.3.2 Strength adjustments. Design values for 
untreated lumber and wood structural panels as specified 
in Section R802.1 shall be adjusted for fire-retardant- 
treated wood. Adjustments to design values shall be 
based upon an approved method of investigation which 
takes into consideration the effects of the anticipated 
temperature and humidity to which the fire-retar- 
dant-treated wood will be subjected, the type of treat- 
ment and redrying procedures. 

R802.1.3.2.1 Wood structural panels. The effect of 
treatment and the method of redrying after treatment, 
and exposure to high temperatures and high 
humidities on the flexure properties of fire-retar- 
dant-treated softwood plywood shall be determined 
in accordance with ASTM D 5516. The test data 
developed by ASTM D 5516 shall be used to develop 
adjustment factors, maximum loads and spans, or 
both for untreated plywood design values in accor- 
dance with ASTM D 6305. Each manufacturer shall 
publish the allowable maximum loads and spans for 
service as floor and roof sheathing for their treatment. 

R802.1.3.2.2 Lumber. For each species of wood 
treated, the effect of the treatment and the method of 
redrying after treatment and exposure to high tempera- 
tures and high humidities on the allowable design 
properties of fire-retardant-treated lumber shall be 
determined in accordance with ASTM D 5664. The 
test data developed by ASTM D 5664 shall be used to 
develop modification factors for use at or near room 
temperature and at elevated temperatures and humidity I 
in accordance with ASTM D 684 1 . Each manufacturer | 
shall publish the modification factors for service at 
temperatures of not less than 80°F (27°C) and for roof 
framing. The roof framing modification factors shall 
take into consideration the climatological location. 

R802.1.3.3 Exposure to weather. Where fire-retar- 
dant-treated wood is exposed to weather or damp or wet 
locations, it shall be identified as "Exterior" to indicate 
there is no increase in the listed flame spread index as 
defined in Section R802. 1 .3 when subjected to ASTM D 
2898. 



2006 INTERNATIONAL RESIDENTIAL CODE" 



243 



ROOF-CEILING CONSTRUCTION 



R802.1.3.4 Interior applications. Interior fire-retar- 
dant-treated wood shall have a moisture content of not 
over 28 percent when tested in accordance with ASTM D 
3201 procedures at 92 percent relative humidity. Interior 
fire-retardant-treated wood shall be tested in accordance 
with Section R802. 1.3.2.1 or R802. 1.3.2.2. Interior 
fire-retardant-treated wood designated as Type A shall 
be tested in accordance with the provisions of this sec- 
tion. 

R802. 1.3.5 Moisture content. Fire-retardant-treated 
wood shall be dried to a moisture content of 1 9 percent or 
less for lumber and 15 percent or less for wood structural 
panels before use. For wood kiln dried after treatment 
(KDAT) the kiln temperatures shall not exceed those 
used in kiln drying the lumber and plywood submitted 
for the tests described in Section R802.1.3.2.1 for ply- 
wood and R802.1.3.2.2 for lumber. 

R802.1.4 Structural glued laminated timbers. Glued 
laminated timbers shall be manufactured and identified as 
required in AITC A 190.1 and ASTM D 3737. 

R802.1.5 Structural log members. Stress grading of struc- 
tural log members of nonrectangular shape, as typically 
used in log buildings, shall be in accordance with ASTM D 
3957. Such structural log members shall be identified by the 
grade mark of an approved lumber grading or inspection 
agency. In lieu of a grade mark on the material, a certificate 
of inspection as to species and grade issued by a lum- 
ber-grading or inspection agency meeting the requirements 
of this section shall be permitted to be accepted. 

R802.2 Design and construction. The framing details 
required in Section R802 apply to roofs having a minimum 
slope of three units vertical in 12 units horizontal (25 -percent 
slope) or greater. Roof-ceilings shall be designed and con- 
structed in accordance with the provisions of this chapter and 
Figures R606.11(l), R606.11(2) and R606.11(3) or in accor- 
dance with AFPA/NDS. Components of roof-ceilings shall be 
fastened in accordance with Table R602.3(l). 

R802.3 Framing details. Rafters shall be framed to ridge 
board or to each other with a gusset plate as a tie. Ridge board 
shall be at least 1-inch (25 mm) nominal thickness and not less 
in depth than the cut end of the rafter. At all valleys and hips 
there shall be a valley or hip rafter not less than 2-inch (5 1 mm) 
nominal thickness and not less in depth than the cut end of the 
rafter. Hip and valley rafters shall be supported at the ridge by a 
brace to a bearing partition or be designed to carry and distrib- 
ute the specific load at that point. Where the roof pitch is less 
than three units vertical in 12 units horizontal (25-percent 
slope), structural members that support rafters and ceiling 
joists, such as ridge beams, hips and valleys, shall be designed 
as beams. 

R802.3.1 Ceiling joist and rafter connections. Ceiling 
joists and rafters shall be nailed to each other in accordance 
with Table R802.5.1(9), and the rafter shall be nailed to the 
top wall plate in accordance with Table R602.3(l). Ceiling 
joists shall be continuous or securely joined in accordance 
with Table R802.5. 1(9) where they meet over interior parti- 
tions and are nailed to adjacent rafters to provide a continu- 



ous tie across the building when such joists are parallel to 
the rafters. 

Where ceiling joists are not connected to the rafters at the 
top wall plate, joists connected higher in the attic shall be 
installed as rafter ties, or rafter ties shall be installed to pro- 
vide a continuous tie. Where ceiling joists are not parallel to 
' rafters, rafter ties shall be installed. Rafter ties shall be a 
minimum of 2-inch by 4-inch (51 mm by 102 mm) (nomi- 
nal), installed in accordance with the connection require- 
ments in Table R802.5.1(9), or connections of equivalent 
capacities shall be provided. Where ceiling joists or rafter 
ties are not provided, the ridge formed by these, rafters shall 
be supported by a wall or girder designed in; accordance 
with accepted engineering practice. 

Collar ties or ridge straps to resist wind uplift shall be 
connected in the upper third of the attic space in accordance 
with Table R602.3(l). 

Collar ties shall be a minimum of 1-inch by 4-inch (25 
mm by 102 mm) (nominal), spaced not more than 4 feet 
(1219 mm) on center. 

R802.3.2 Ceiling joists lapped. Ends of ceiling joists shall 
be lapped a minimum of 3 inches (76 mm) or butted over 
bearing partitions or beams and toenailed to the bearing 
member. When ceiling joists are used to provide resistance 
to rafter thrust, lapped joists shall be nailed together in 
accordance with Table R602.3(l) and butted joists shall be 
tied together in a manner to resist such thrust. : 

R802.4 Allowable ceiling joist spans. Spans for ceiling joists 
shall be in accordance with Tables R802.4(l) and R802.4(2). 
For other grades and species and for other loading conditions, 
refer to the AF&PA Span Tables for Joists and Rafters. 

R802.5 Allowable rafter spans. Spans for rafters shall be in 
accordance with Tables R802.5.1(l) through R802.5.1(8). For 
other grades and species and for other loading conditions, refer 
to the AF&PA Span Tables for Joists and Rafters. The span of 
each rafter shall be measured along the horizontal projection of 
the rafter. ' 

R802.5.1 Purlins. Installation of purlins to reduce the span 
of rafters is permitted as shown in Figure R802.5 . 1 . Purlins 
shall be sized no less than the required size of the rafters that 
they support. Purlins shall be continuous and shall be sup- 
ported by 2-inch by 4-inch (51 mm by 102 mm) braces 
installed to bearing walls at a slope not less than 45 degrees 
from the horizontal. The braces shall be spaced not more 
than 4 feet (1219 mm) on center and the unbraced length of 
braces shall not exceed 8 feet (2438 mm). 

R802.6 Bearing. The ends of each rafter or ceilinig joist shall 
have not less than 1 V2 inches (38 mm) of bearing jon wood or 
metal and not less than 3 inches (76 mm) on masonry or con- 
crete. I 

R802.6.1 Finished ceiling material. If the finished ceiling 
material is installed on the ceiling prior to the attachment of 
the ceiling to the walls, such as in construction at a factory, a 
compression strip of the same thickness as the finish ceiling 
I material shall be installed directly above the top plate of 
bearing walls if the compressive strength of the; finish ceil- 
ing material is less than the loads it will be required to with- 



244 



2006 INTERNATIONAL RESIDENTIAL CODE® 



ROOF-CEILING CONSTRUCTION 



Stand. The compression strip shall cover the entire length of 
such top plate and shall be at least one-half the width of the 
top plate. It shall be of material capable of transmitting the 
loads transferred through it. 

R802.7 Cutting and notching. Structural roof members shall 
not be cut, bored or notched in excess of the limitations speci- 
fied in this section. 

R802.7.1 Sawn lumber. Notches in solid lumber joists, raf- 
ters and beams shall not exceed one- sixth of the depth of the 
member, shall not be longer than one-third of the depth of 
the member and shall not be located in the middle one-third 
of the span. Notches at the ends of the member shall not 
exceed one-fourth the depth of the member. The tension 
side of members 4 inches (102 mm) or greater in nominal 
thickness shall not be notched except at the ends of the 
members. The diameter of the holes bored or cut into mem- 
bers shall not exceed one-third the depth of the member. 
Holes shall not be closer than 2 inches (5 1 mm) to the top or 
bottom of the member, or to any other hole located in the 
member. Where the member is also notched, the hole shall 
not be closer than 2 inches (5 1 mm) to the notch. 

Exception: Notches on cantilevered portions of rafters 
are permitted provided the dimension of the remaining 
portion of the rafter is not less than 4-inch nominal (102 
mm) and the length of the cantilever does not exceed 24 
inches (610 mm). 

R802.7.2 Engineered wood products. Cuts, notches and 
holes bored in trusses, structural composite lumber, struc- 
tural glue-laminated members or I-joists are prohibited 
except where permitted by the manufacturer's recommen- 
dations or where the effects of such alterations are specifi- 
cally considered in the design of the member by a registered 
design professional. 

R802.8 Lateral support. Rafters and ceiling joists having a 
depth-to-thickness ratio exceeding 5 to 1 based on nominal 
dimensions shall be provided with lateral support at points of 
bearing to prevent rotation. 

R802.8.1 Bridging. Rafters and ceihng joists having a depth- 
to-thickness ratio exceeding 6 to 1 based on nominal dimen- 
sions shall be supported laterally by solid blocking, diagonal 
bridging (wood or metal) or a continuous 1-inch by 3 -inch 
(25 mm by 76 mm) wood strip nailed across the rafters or 
ceiling joists at intervals not exceeding 8 feet (2438 mm). 

R802.9 Framing of openings. Openings in roof and ceiling 
framing shall be framed with header and trimmer joists. When 
the header joist span does not exceed 4 feet (1219 mm), the 
header joist may be a single member the same size as the ceiling 
joist or rafter. Single trimmer joists may be used to carry a sin- 
gle header joist that is located within 3 feet (914 mm) of the 
trimmer joist bearing. When the header joist span exceeds 4 
feet (1219 mm), the trimmer joists and the header joist shall be 
doubled and of sufficient cross section to support the ceiling 
joists or rafter framing into the header. Approved hangers shall 
be used for the header joist to trimmer joist connections when 
the header joist span exceeds 6 feet (1829 mm). Tail joists over 
12 feet (3658 mm) long shall be supported at the header by 



framing anchors or on ledger strips not less than 2 inches by 2 
inches (51 mm by 51 mm). 

R802.10 Wood trusses. 

R802.10.1 Truss design drawings. Truss design drawings, 
prepared in conformance to Section R802.10.1, shall be 
provided to the building official and approved prior to 
installation. Truss design drawings shall include, at a mini- 
mum, the information specified below. Truss design draw- 
ing shall be provided with the shipment of trusses delivered 
to the jobsite. 

1 . Slope or depth, span and spacing. 

2. Location of all joints. 

3. Required bearing widths. 

4. Design loads as applicable. 

4. 1 . Top chord live load (as determined from Sec- I 
tionR301.6). | 

4.2. Top chord dead load. 

4.3. Bottom chord live load. 

4.4. Bottom chord dead load. 

4.5. Concentrated loads and their points of appli- 
cation. 

4.6. Controlling wind and earthquake loads. 

5. Adjustments to lumber and joint connector design 
values for conditions of use. 

6. Each reaction force and direction. 

7. Joint connector type and description (e.g., size, 
thickness or gage) and the dimensioned location of 
each joint connector except where symmetrically 
located relative to the joint interface. 

8. Lumber size, species and grade for each member. 

9. Connection requirements for: 

9.1. Truss to girder-truss. | 

9.2. Truss ply to ply. 

9.3. Field splices. 

10. Calculated deflection ratio and/or maximum 
description for live and total load. 

11. Maximum axial compression forces in the truss 
members to enable the building designer to design 
the size, connections and anchorage of the perma- 
nent continuous lateral bracing. Forces shall be 
shown on the truss design drawing or on supplemen- 
tal documents. 

1 2. Required permanent truss member bracing location. 

R802.10.2 Design. Wood trusses shall be designed in accor- 
dance with accepted engineering practice. The design and 
manufacture of metal-plate-connected wood trusses shall 
comply with ANSI/TPI 1. The truss design drawings shall 
be prepared by a registered professional where required by 
the statutes of the jurisdiction in which the project is to be 
constructed in accordance with Section R 106.1. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



245 



ROOF-CEILING CONSTRUCTION 



TABLE R802.4(1) 

CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 

(Uninhabitable attics without storage, live load = 10 psf, L/A = 240) 



CEILING JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 5 psf 


2x4 


2x6 


2x8 


2x10 


Maximum ceiling joist spans 


(feet - inches) 


(feet - inches) 


(feet - inches) 


(feet - inches) 


12 


Douglas fir-larch SS 
Douglas fir-larch #1 
Douglas fir-larch #2 
Douglas fir-larch #3 
Hem-fir SS 
Hem-fir #1 
Hem-fir #2 
Hem-fu- #3 
Southern pine SS 
Southern pine #1 
Southern pine #2 
Southern pine #3 
Spruce-pine-fir SS 
Spruce-pine-fir #1 
Spruce-pine-fir #2 
Spruce-pine-fir #3 


13-2 
12-8 
12-5 
10-10 
12-5 
12-2 
11-7 
10-10 
12-11 
12-8 
12-5 
11-6 
12-2 
11-10 
11-10 
10-10 


20-8 
19-11 
19-6 
15-10 
19-6 
19-1 
18-2 
15-10 
20-3 
19-11 
19-6 
17-0 
19-1 
18-8 
18-8 
15-10 


Note a 
Note a 
25-8 
20-1 
25-8 
25-2 
24-0 
20-1 
Note a 
Note a 
25-8 
21-8 
25-2 
24-7 
24-7 
20-1 


Note a 
Note a 
Note a 

24-6 
Note a 
Note a 
Note a 

24-6 
Note a 
Note a 
Note a 

25-7 
Note a 
Note a 
Note a 

24-6 


16 


Douglas fir-larch SS 
Douglas fir-larch #1 
Douglas fir-larch #2 
Douglas fir-larch #3 
Hem-fir SS 
Hem-fir #1 
Hem-fir #2 
Hem-fir #3 
Southern pine SS 
Southern pine #1 
Southern pine #2 
Southern pine #3 
Spruce-pine-fir SS 
Spruce-pine-fir #1 
Spruce-pine-fir #2 
Spruce-pine-fir #3 


11-11 

11-6 

11-3 

9-5 

11-3 

11-0 

10-6 

9-5 

11-9 

11-6 

11-3 

10-0 

11-0 

10-9 

10-9 

9-5 


18-9 
18-1 
17-8 
13-9 
17-8 
17-4 
16-6 
13-9 
18-5 
18-1 
17-8 
14-9 
17-4 
16-11 
16-11 
13-9 


24-8 
23-10 
23-0 
17-5 
23-4 
22-10 
21-9 
17-5 
24-3 
23-1 
23-4 
18-9 
22-10 
22-4 
22-4 
17-5 


Note a 
Note a 
Note a 

21-3 
Note a 
Note a 
Note a 

21-3 
Note a 
Note a 
Note a 

22-2 
Note a 

Note a 

1 

Note a 
21-3 


19.2 


Douglas fir-larch SS 
Douglas fir-larch #1 
Douglas fir-larch #2 
Douglas fir-larch #3 
Hem-fir SS 
Hem-fir #1 
Hem-fir #2 
Hem-fir #3 
Southern -pine SS 
Southern pine #1 
Southern pine #2 
Southern pine #3 
Spruce-pine-fir SS 
Spruce-pine-fir #1 
Spruce-pine-fir #2 
Spruce-pine-fir #3 


11-3 
10-10 
10-7 
8-7 
10-7 
10-4 
9-11 
8-7 
11-0 
10-10 
10-7 
9-1 
10-4 
10-2 
10-2 
8-7 


17-8 
17-0 
16-7 
12-6 
16-8 
16-4 
15-7 
12-6 
17-4 
17-0 
16-8 
13-6 
16-4 
15-11 
15-11 
12-6 


23-3 
22-5 
21-0 
15-10 
21-11 
21-6 
20-6 
15-10 
22-10 
22-5 
21-11 
17-2 
21-6 
21-0 
21-0 
15-10 


Note a 

Note a 

25-8 

19-5 

Note a 

Note a 

25-3 

19-5 

Note a 

Note a 

Note a 

20-3 

Note a 

25-8 

25-8 

19-5 



(continued) 



246 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



ROOF-CEILING CONSTRUCTION 



TABLE R802.4(1)— continued 

CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 

(Uninhabitable attics without storage, live load = 10 psf, L/A = 240) 



CEILING JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 5 psf 


2x4 


2x6 


2x8 


2x10 


Maximum ceiling joist spans 


(feet - inches) 


(feet - inches) 


(feet - inches) 


(feet - inches) 




Douglas fir-larch 


SS 


10-5 


16-4 


21-7 


Note a 




Douglas fir-larch 


#1 


10-0 


15-9 


20-1 


24-6 




Douglas fir-larch 


#2 


9-10 


14-10 


18-9 


22-11 




Douglas fir-larch 


#3 


7-8 


11-2 


14-2 


17-4 




Hem-fir 


SS 


9-10 


15-6 


20-5 


Note a 




Hem-fir 


#1 


9-8 


15-2 


19-7 


23-11 




Hem-fir 


#2 


9-2 


14-5 


18-6 


22-7 


24 


Hem-fir 


#3 


7-8 


11-2 


14-2 


17-4 


Southern pine 


SS 


10-3 


16-1 


21-2 


Note a 




Southern pine 


#1 


10-0 


15-9 


20-10 


Note a 




Southern pine 


#2 


9-10 


15-6 


20-1 


23-11 




Southern pine 


#3 


8-2 


12-0 


15-4 


18-1 




Spruce-pine-fir 


SS 


9-8 


15-2 


19-11 


25-5 




Spruce-pine-fir 


#1 


9-5 


14-9 


18-9 


22-11 




Spruce-pine-fir 


#2 


9-5 


14-9 


18-9 


22-11 




Spruce-pine-fir 


#3 


7-8 


11-2 


14-2 


17-4 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



247 



ROOF-CEILING CONSTRUCTION 



TABLE R802.4(2) 

CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 

(Uninhabitable attics with limited storage, live load = 20 psf, L/A = 240) 



CEILING JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


2x4 


2x6 


2x8 2x10 


Maximum ceiling joist spans 


(feet - inches) 


(feet - inches) 


(feet - inches) 


(feet - inches) 


12 


Douglas fir-larch SS 
Douglas fir-larch #1 
Douglas fir-larch #2 
Douglas fir-larch #3 
Hem-fir SS 
Hem-fir #1 
Hem-fir #2 
Hem-fir #3 
Southern pine SS 
Southern pine #1 
Southern pine #2 
Southern pine #3 
Spruce-pine-fir SS 
Spruce-pine-fir #1 
Spruce-pine-fir #2 
Spruce-pine-fir #3 


10-5 
10-0 
9-10 
7-8 
9-10 
9-8 
9-2 
7-8 
10-3 
10-0 
9-10 
8-2 
9-8 
9-5 
9-5 
7-8 


16-4 
15-9 
14-10 
11-2 
15-6 
15-2 
14-5 
11-2 
16-1 
15-9 
15-6 
12-0 
15-2 
14-9 
14-9 
11-2 


21-7 
20-1 
18-9 
14-2 
20-5 
19-7 
18-6 
14-2 
21-2 
20-10 
20-1 
15-4 
19-11 
18-9 
18-9 
14-2 


Note a 

24-6 

22-11 

17-4 

Note a 

23-11 

22-7 

17-4 

Note a 

Note a 

23-11 

18-1 

25-5 

22-11 

22-11 

17-4 


16 


Douglas fir-larch SS 
Douglas fir- larch #1 
Douglas fir-larch #2 
Douglas fir-larch #3 
Hem-fir SS 
Hem-fir #1 
Hem-fir #2 
Hem-fir #3 
Southern pine SS 
Southern pine #1 
Southern pine #2 
Southern pine #3 
Spruce-pine-fir SS 
Spruce-pine-fir #1 
Spruce-pine-fir #2 
Spruce-pine-fir #3 


9-6 
9-1 
8-9 
6-8 
8-11 
8-9 
8-4 
6-8 
9-4 
9-1 
8-11 
7-1 
8-9 
8-7 
8-7 
6-8 


14-11 
13-9 
12-10 
9-8 
14-1 
13-5 
12-8 
9-8 
14-7 
14-4 
13-6 
10-5 
13-9 
12-10 
12-10 
9-8 


19-7 
17-5 
16-3 
12-4 
18-6 
16-10 
16-0 
12-4 
19-3 
18-11 
17-5 
13-3 
18-1 
16-3 
16-3 
12-4 


25-0 
21-3 
19-10 

;15-0 

23-8 
20-8 
19-7 
15-0 
24-7 
23-1 
20-9 
15-8 
23-1 
19-10 
19-10 
15-0 


19.2 


Douglas fir-larch SS 
Douglas fir-larch #1 
Douglas fir-larch #2 
Douglas fir-larch #3 
Hem-fir SS 
Hem-fir #1 
Hem-fir #2 
Hem-fir #3 
Southern pine SS 
Southern pine #1 
Southern pine #2 
Southern pine #3 
Spruce-pine-fir SS 
Spruce-pine-fir #1 
Spruce-pine-fir #2 
Spruce-pine-fir #3 


8-11 
8-7 
8-0 
6-1 
8-5 
8-3 
7-10 
6-1 
8-9 
8-7 
8-5 
6-5 
8-3 
8-0 
8-0 
6-1 


14-0 
12-6 
11-9 
8-10 
13-3 
12-3 
11-7 
8-10 
13-9 
13-6 
12-3 
9-6 
12-11 
11-9 
11-9 
8-10 


18-5 
15-10 
14-10 
11-3 
17-5 
15-6 
14-8 
11-3 
18-1 
17-9 
15-10 
12-1 
17-1 
14-10 
14-10 
11-3 


23-4 

19-5 

18-2 

13-8 

22-3 

18-11 

17-10 

,13-8 

23-1 

21-1 

18-11 

il4-4 

21-8 

il8-2 

|l8-2 

13-8 



(continued) 



248 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.4(2)— continued 
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 
(Uninhabitable attics with limited storage, live load = 20 psf, L/A 



= 240) 



CEILING JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


2x4 


2x6 


2x8 


2x10 


Maximum Ceiling Joist Spans 


(feet - inches) 


(feet - inches) 


(feet - inches) 


(feet - inches) 




Douglas fir-larch 


SS 


8-3 


13-0 


17-1 


20-11 




Douglas fir-larch 


#1 


7-8 


11-2 


14-2 


17-4 




Douglas fir-larch 


#2 


7-2 


10-6 


13-3 


16-3 




Douglas fir-larch 


#3 


5-5 


7-11 


10-0 


12-3 




Hem-fir 


SS 


7-10 


12-3 


16-2 


20-6 




Hem-fir 


#1 


7-6 


10-11 


13-10 


16-11 




Hem-fir 


#2 


7-1 


10-4 


13-1 


16-0 


24 


Hem-fir 


#3 


5-5 


7-11 


10-0 


12-3 


Southern pine 


SS 


8-1 


12-9 


16-10 


21-6 




Southern pine 


#1 


8-0 


12-6 


15-10 


18-10 




Southern pine 


#2 


7-8 


11-0 


14-2 


16-11 




Southern pine 


#3 


5-9 


8-6 


10-10 


12-10 




Spruce-pine-fir 


SS 


7-8 


12-0 


15-10 


19-5 




Spruce-pine-fir 


#1 


7-2 


10-6 


13-3 


16-3 




Spruce-pine-fir 


#2 


7-2 


10-6 


13-3 


16-3 




Spruce-pine-fir 


#3 


5-5 


7-11 


10-0 


12-3 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



249 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(1) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof live load=20 psf, ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








SPECIES AND GRADE 




(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet- 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


11-6 


18-0 


23-9 


Noteb 


Noteb 


11-6 


18-0 


23-5 


Note b 


Noteb 




Douglas fir-larch 


#1 


1-1 


17-4 


22-5 


Noteb 


Noteb 


10-6 


15-4 


19-5 


23-9 


Noteb 




Douglas fir-larch 


#2 


1-10 


16-7 


21-0 


25-8 


Noteb 


9-10 


14-4 


18-2 


22-3 


25-9 




Douglas fir-larch 


#3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 




Hem-fir 


SS 


10-10 


17-0 


22-5 


Noteb 


Noteb 


10-10 


17-0 


22-5 


Note b 


Noteb 




Hem-fir 


#1 


10-7 


16-8 


21-10 


Noteb 


Noteb 


10-3 


14-11 


18-11 


23-2 


Noteb 




Hem-fir 


#2 


10-1 


15-11 


20-8 


25-3 


Noteb 


9-8 


14-2 


17-11 


21-11 


25-5 


12 


Hem-fir 


#3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Southern pine 


SS 


11-3 


17-8 


23-4 


Noteb 


Noteb 


11-3 


17-8 


23-4 


Note b 


Noteb 




Southern pine 


#1 


11-1 


17-4 


22-11 


Noteb 


Noteb 


11-1 


17-3 


21-9 


25-10 


Noteb 




Southern pine 


#2 


10-10 


17-0 


22-5 


Noteb 


Noteb 


10-6 


15-1 


19-5 


23-2 


Noteb 




Southern pine 


#3 


9-1 


13-6 


17-2 


20-3 


24-1 


7-11 


11-8 


14-10 


17-6 


20-11 




Spruce-pine-fir 


SS 


10-7 


16-8 


21-11 


Noteb 


Noteb 


10-7 


16-8 


21-9 


Note b 


Noteb 




Spruce-pine-fir 


#1 


10-4 


16-3 


21-0 


25-8 


Noteb 


9-10 


14-4 


18-2 


22-3 


25-9 




Spruce-pine-fir 


#2 


10-4 


16-3 


21-0 


25-8 


Noteb 


9-10 


14-4 


18-2 


22-3 


25-9 




Spruce-pine-fir 


#3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 




Douglas fir-larch 


SS 


10-5 


16-4 


21-7 


Noteb 


Noteb 


10-5 


16-0 


20-3 


24-9 


Noteb 




Douglas fir-larch 


#1 


10-0 


15-4 


19-5 


23-9 


Noteb 


9-1 


13-3 


16-10 


20-7 


23-10 




Douglas fir-larch 


#2 


9-10 


14-4 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 




Douglas fir-larch 


#3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 




Hem-fir 


SS 


9-10 


15-6 


20-5 


Noteb 


Noteb 


9-10 


15-6 


19-11 


24-4 


Noteb 




Hem-fir 


#1 


9-8 


14-11 


18-11 


23-2 


Noteb 


8-10 


12-11 


16-5 


20-0 


23-3 




Hem-fir 


#2 


9-2 


14-2 


17-11 


21-11 


25-5 


8-5 


12-3 


15-6 


18-11 


22-0 


16 


Hem-fir 


#3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 


Southern pine 


SS 


10-3 


16-1 


21-2 


Noteb 


Noteb 


10-3 


16-1 


21-2 


Note b 


Noteb 




Southern pine 


#1 


10-0 


15-9 


20-10 


25-10 


Noteb 


10-0 


15-0 


18-10 


22-4 


Noteb 




Southern pine 


#2 


9-10 


15-1 


19-5 


23-2 


Noteb 


9-1 


13-0 


16-10 


20-1 


23-7 




Southern pine 


#3 


7-11 


11-8 


14-10 


17-6 


20-11 


6-10 


10-1 


12-10 


15-2 


18-1 




Spruce-pine-fir 


SS 


9-8 


15-2 


19-11 


25-5 


Noteb 


9-8 


14-10 


18-10 


23-0 


Noteb 




Spruce-pine-fir 


#1 


9-5 


14-4 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 




Spruce-pine-fir 


#2 


9-5 


14-4 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 




Spruce-pine-fir 


#3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 




Douglas fir-larch 


SS 


9-10 


15-5 


20-4 


25-11 


Noteb 


9-10 


14-7 


18-6 


22-7 


Noteb 




Douglas fir-larch 


#1 


9-5 


14-0 


17-9 


21-8 


25-2' 


8-4 


12-2 


15-4 


18-9 


21-9 




Douglas fir-larch 


#2 


8-11 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 




Douglas fir-larch 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 




Hem-fir 


SS 


9-3 


14-7 


19-2 


24-6 


Noteb 


9-3 


14-4 


18-2 


22-3 


25-9 




Hem-fir 


#1 


9-1 


13-8 


17-4 


21-1 


24-6 


8-1 


11-10 


15-0 


18-4 


21-3 




Hem-fir 


#2 


8-8 


12-11 


16-4 


20-0 


23-2 


7-8 


11-2 


14-2 


17-4 


20-1 


19.2 


Hem-fir 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


Southern pine 


SS 


9-8 


15-2 


19-11 


25-5 


Noteb 


9-8 


15-2 


19-11 


25-5 


Noteb 




Southern pine 


#1 


9-5 


14-10 


19-7 


23-7 


Noteb 


9-3 


13-8 


17-2 


20-5 


24-4 




Southern pine 


#2 


9-3 


13-9 


17-9 


21-2 


24-10 


8-4 


11-11 


15-4 


18-4 


21-6 




Southern pine 


#3 


7-3 


10-8 


13-7 


16-0 


19-1 


6-3 


9-3 


11-9 


13-110 


16-6 




Spruce-pine-fir 


SS 


9-1 


14-3 


18-9 


23-11 


Noteb 


9-1 


13-7 


17-2 


21-0 


24-4 




Spruce-pine-fir 


#1 


8-10 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 




Spruce-pine-fir 


#2 


8-10 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 




Spruce-pine-fir 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 



(continued) 



250 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(1)— continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof live load=20 psf, ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








lUlaximum rafter spans 


a 








(feet- 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


9-1 


14-4 


18-10 


23-4 


Noteb 


8-11 


13-1 


16-7 


20-3 


23-5 




Douglas fir-larch 


#1 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 




Douglas fir-larch 


#2 


8-0 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 




Douglas fir-larch 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 




Hem-fir 


SS 


8-7 


13-6 


17-10 


22-9 


Noteb 


8-7 


12-10 


16-3 


19-10 


23-0 




Hem-fir 


#1 


8-4 


12-3 


15-6 


18-11 


21-11 


7-3 


10-7 


13-5 


16-4 


19-0 




Hem-fir 


#2 


7-11 


11-7 


14-8 


17-10 


20-9 


6-10 


10-0 


12-8 


15-6 


17-11 


24 


Hem-fir 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 


Southern pine 


SS 


8-11 


14-1 


18-6 


23-8 


Noteb 


8-11 


14-1 


18-6 


22-11 


Noteb 




Southern pine 


#1 


8-9 


13-9 


17-9 


21-1 


25-2 


8-3 


12-3 


15-4 


18-3 


21-9 




Southern pine 


#2 


8-7 


12-3 


15-10 


18-11 


22-2 


7-5 


10-8 


13-9 


16-5 


19-3 




Southern pine 


#3 


6-5 


9-6 


12-1 


14-4 


17-1 


5-7 


8-3 


10-6 


12-5 


14-9 




Spruce-pine-fir 


SS 


8-5 


13-3 


17-5 


21-8 


25-2 


8-4 


12-2 


15-4 


18-9 


21-9 




Spruce-pine-fir 


#1 


8-0 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 




Spruce-pine-fir 


#2 


8-0 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 




Spruce-pine-fir 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing wahs, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiplied by the factors given below: 



Hc/«« 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

Hq = Height of ceiling joists or rafter ties measured verticaUy above the top of the rafter support walls. 
)f = Height of roof ridge measured vertically above the top of the rafter support walls. 



H, 



b. Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



251 



ROOF-CEILING CONSTRUCTION 



TABLER802.5.1(2) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof live load=20 psf, ceiling attached to rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








SPECIES AND GRADE 




(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
iriches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


10-5 


16-4 


21-7 


Noteb 


Noteb 


10-5 


16-4 


21-7 


Note b 


Noteb 




Douglas fir-larch 


#1 


10-0 


15-9 


20-10 


Noteb 


Noteb 


10-0 


15-4 


19-5 


23-9 


Noteb 




Douglas fir-larch 


#2 


9-10 


15-6 


20-5 


25-8 


Noteb 


9-10 


14-4 


18-2 


22-3 


25-9 




Douglas fir-larch 


#3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 




Hem-fir 


SS 


9-10 


15-6 


20-5 


Noteb 


Noteb 


9-10 


15-6 


20-5 


Noteb 


Noteb 




Hem-fir 


#1 


9-8 


15-2 


19-11 


25-5 


Noteb 


9-8 


14-11 


18-11 


23-2 


Noteb 




Hem-fir 


#2 


9-2 


14-5 


19-0 


24-3 


Noteb 


9-2 


14-2 


17-11 


21-11 


25-5 


12 


Hem-fir 


#3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Southern pine 


SS 


10-3 


16-1 


21-2 


Noteb 


Noteb 


10-3 


16-1 


21-2 


Noteb 


Noteb 




Southern pine 


#1 


10-0 


15-9 


20-10 


Noteb 


Noteb 


10-0 


15-9 


20-10 


25-10 


Noteb 




Southern pine 


#2 


9-10 


15-6 


20-5 


Noteb 


Noteb 


9-10 


15-1 


19-5 


23-2 


Noteb 




Southern pine 


#3 


9-1 


13-6 


17-2 


20-3 


24-1 


7-11 


11-8 


14-10 


17-6 


20-11 




Spruce-pine-fir 


SS 


9-8 


15-2 


19-11 


25-5 


Noteb 


9-8 


15-2 


19-11 


25-5 


Noteb 




Spruce-pine-fir 


#1 


9-5 


14-9 


19-6 


24-10 


Noteb 


9-5 


14-4 


18-2 


22-3 


25-9 




Spruce-pine-fir 


#2 


9-5 


14-9 


19-6 


24-10 


Noteb 


9-5 


14-4 


18-2 


22-3 


25-9 




Spruce-pine-fir 


#3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 




Douglas fir-larch 


SS 


9-6 


14-11 


19-7 


25-0 


Noteb 


9-6 


14-11 


19-7 


24-9 


Noteb 




Douglas fir-larch 


#1 


9-1 


14-4 


18-11 


23-9 


Noteb 


9-1 


13-3 


16-10 


20-7 


23-10 




Douglas fir-larch 


#2 


8-11 


14-1 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


, 


Douglas fir-larch 


#3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 




Hem-fir 


SS 


8-11 


14-1 


18-6 


23-8 


Noteb 


8-11 


14-1 


18-6 


23-8 


Noteb 




Hem-fir 


#1 


8-9 


13-9 


18-1 


23-1 


Noteb 


8-9 


12-11 


16-5 


20-0 


23-3 




Hem-fir 


#2 


8-4 


13-1 


17-3 


21-11 


25-5 


8-4 


12-3 


15-6 


18-11 


22-0 


16 


Hem-fir 


#3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 


Southern pine 


SS 


9-4 


14-7 


19-3 


24-7 


Noteb 


9-4 


14-7 


19-3 


24-7 


Noteb 




Southern pine 


#1 


9-1 


14-4 


18-11 


24-1 


Noteb 


9-1 


14-4 


18-10 


22-4 


Noteb 




Southern pine 


#2 


8-11 


14-1 


18-6 


23-2 


Noteb 


8-11 


13-0 


16-10 


20-1 


23-7 




Southern pine 


#3 


7-11 


11-8 


14-10 


17-6 


20-11 


6-10 


10-1 


12-10 


15-2 


18-1 




Spruce-pine-fir 


SS 


8-9 


13-9 


18-1 


23-1 


Noteb 


8-9 


13-9 


18-1 


23-0 


Noteb 




Spruce-pine-fir 


#1 


8-7 


13-5 


17-9 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 




Spruce-pine-fir 


#2 


8-7 


13-5 


17-9 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 




Spruce-pine-fir 


#3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 




Douglas fir-larch 


SS 


8-11 


14-0 


18-5 


23-7 


Noteb 


8-11 


14-0 


18-5 


22-7 


Noteb 




Douglas fir-larch 


#1 


8-7 


13-6 


17-9 


21-8 


25-2 


8-4 


12-2 


15-4 


18-9 


21-9 




Douglas fir-larch 


#2 


8-5 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 




Douglas fir-larch 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 




Hem-fir 


SS 


8-5 


13-3 


17-5 


22-3 


Noteb 


8-5 


13-3 


17-5 


22-3 


25-9 




Hem-fir 


#1 


8-3 


12-11 


17-1 


21-1 


24-6 


8-1 


11-10 


15-0 


18-4 


21-3 




Hem-fir 


#2 


7-10 


12-4 


16-3 


20-0 


23-2 


7-8 


11-2 


14-2 


17-4 


20-1 


19.2 


Hem-fir 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


Southern pine 


SS 


8-9 


13-9 


18-1 


23-1 


Noteb 


8-9 


13-9 


18-1 


23- i 


Noteb 




Southern pine 


#1 


8-7 


13-6 


17-9 


' 22-8 


Noteb 


8-7 


13-6 


17-2 


20-5 


24-4 




Southern pine 


#2 


8-5 


13-3 


17-5 


21-2 


24-10 


8-4 


11-11 


15-4 


18-4 


21-6 




Southern pine 


#3 


7-3 


10-8 


13-7 


16-0 


19-1 


6-3 


9-3 


11-9 


13- lb 


16-6 




Spruce-pine-fir 


SS 


8-3 


12-11 


17-1 


21-9 


Noteb 


8-3 


12-11 


17-1 


21-(} 


24-4 




Spruce-pine-fir 


#1 


8-1 


12-8 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 




Spruce-pine-fir 


#2 


8-1 


12-8 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 




Spruce-pine-fir 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-i 


15-5 



(continued) 



252 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (2)— continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof live load=20 psf, ceiling attached to rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


8-3 


13-0 


17-2 


21-10 


Noteb 


8-3 


13-0 


16-7 


20-3 


23-5 




Douglas fir-larch 


#1 


8-0 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 




Douglas fir-larch 


#2 


7-10 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 




Douglas fir-larch 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 




Hem-fir 


SS 


7-10 


12-3 


16-2 


20-8 


25-1 


7-10 


12-3 


16-2 


19-10 


23-0 




Hem-fir 


#1 


7-8 


12-0 


15-6 


18-11 


21-11 


7-3 


10-7 


13-5 


16-4 


19-0 




Hem-fir 


#2 


7-3 


11-5 


14-8 


17-10 


20-9 


6-10 


10-0 


12-8 


15-6 


17-11 


24 


Hem-fir 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 


Southern pine 


SS 


8-1 


12-9 


16-10 


21-6 


Note b 


8-1 


12-9 


16-10 


21-6 


Noteb 




Southern pine 


#1 


8-0 


12-6 


16-6 


21-1 


25-2 


8-0 


12-3 


15-4 


18-3 


21-9 




Southern pine 


#2 


7-10 


12-3 


15-10 


18-11 


22-2 


7-5 


10-8 


13-9 


16-5 


19-3 




Southern pine 


#3 


6-5 


9-6 


12-1 


14-4 


17-1 


5-7 


8-3 


10-6 


12-5 


14-9 




Spruce-pine-fir 


SS 


7-8 


12-0 


15-10 


20-2 


24-7 


7-8 


12-0 


15-4 


18-9 


21-9 




Spruce-pine-fir 
Spruce-pine-fir 
Spruce-pine-fir 


#1 

#2 
#3 


7-6 
7-6 
6-1 


11-9 
11-9 
8-10 


14-10 
14-10 
11-3 


18-2 
18-2 
13-8 


21-0 
21-0 
15-11 


6-11 
6-11 

5-3 


10-2 
10-2 
7-8 


12-10 

12-10 

9-9 


15-8 
15-8 
11-10 


18-3 
18-3 
13-9 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceihng joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing walls, such as rafter ties, is provided at that location. When ceihng joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiphed by the factors given below: 



Hc/Hr 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

//(- = Height of ceihng joists or rafter ties measured vertically above the top of the rafter support walls. 
Hji - Height of roof ridge measured vertically above the top of the rafter support walls. 
Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



253 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(3) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=30 psf, ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








SPECIES AND GRADE 




(feet - 
inches) 


(feet - 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


10-0 


15-9 


20-9 


Noteb 


Noteb 


10-0 


15-9 


20-1 


24-6 


Noteb 




Douglas fir-larch 


#1 


9-8 


14-9 


18-8 


22-9 


Noteb 


9-0 


13-2 


16-8 


20-4 


23-7 




Douglas fir-larch 


#2 


9-5 


13-9 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 




Douglas fir-larch 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 




Hem-fir 


SS 


9-6 


14-10 


19-7 


25-0 


Noteb 


9-6 


14-10 


19-7 


24-1 


Noteb 




Hem-fir 


#1 


9-3 


14-4 


18-2 


22-2 


25-9 


8-9 


12-10 


16-3 


19-10 


23-0 




Hem-fir 


#2 


8-10 


13-7 


17-2 


21-0 


24-4 


8-4 


12-2 


15-4 


18-9 


21-9 


12 


Hem-fir 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Southern pine 


SS 


9-10 


15-6 


20-5 


Noteb 


Noteb 


9-10 


15-6 


20-5 


Noteb 


Noteb 




Southern pine 


#1 


9-8 


15-2 


20-0 


24-9 


Noteb 


9-8 


14-10 


18-8 


22-2 


Noteb 




Southern pine 


#2 


9-6 


14-5 


18-8 


22-3 


Noteb 


9-0 


12-11 


16-8 


19-11 


23-4 




Southern pine 


#3 


7-7 


11-2 


14-3 


16-10 


20-0 


6-9 


10-0 


12-9 


15-1 


17-11 




Spruce-pine-fir 


SS 


9-3 


14-7 


19-2 


24-6 


Noteb 


9-3 


14-7 


18-8 


22-9 


Noteb 




Spruce-pine-fir 


#1 


9-1 


13-9 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 




Spruce-pine-fir 


#2 


9-1 


13-9 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 




Spruce-pine-fir 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 




Douglas fir-larch 


SS 


9-1 


14-4 


18-10 


23-9 


Noteb 


9-1 


13-9 


17-5 


21-3 


24-8 




Douglas fir-larch 


#1 


8-9 


12-9 


16-2 


19-9 


22-10 


7-10 


11-5 


14-5 


17-8 


20-5 




Douglas fir-larch 


#2 


8-2 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 




Douglas fir-larch 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 




Hem-fir 


SS 


8-7 


13-6 


17-10 


22-9 


Noteb 


8-7 


13-6 


17-1 


20-10 


24-2 




Hem-fir 


#1 


8-5 


12-5 


15-9 


19-3 


22-3 


7-7 


11-1 


14-1 


17-2 


19-11 




Hem-fir 


#2 


8-0 


11-9 


14-11 


18-2 


21-1 


7-2 


10-6 


13-4 


16-3 


18-10 


16 


Hem-fir 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 


Southern pine 


SS 


8-11 


14-1 


18-6 


: 23-8 


Noteb 


8-11 


14-1 


18-6 


23-8 


Noteb 




Southern pine 


#1 


8-9 


13-9 


18-1 


21-5 


25-7 


8-8 


12-10 


16-2 


19-2 


22-10 




Southern pine 


#2 


8-7 


12-6 


16-2 


19-3 


22-7 


7-10 


11-2 


14-5 


17-3 


20-2 




Southern pine 


#3 


6-7 


9-8 


12-4 


14-7 


17-4 


5-10 


8-8 


11-0 


13-0 


15-6 




Spruce-pine-fir 


SS 


8-5 


13-3 


17-5 


22-1 


25-7 


8-5 


12-9 


16-2 


19-9 


22-10 




Spruce-pine-fir 


#1 


8-2 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 




Spruce-pine-fir 


#2 


8-2 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 




Spruce-pine-fir 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 




Douglas fir-larch 


SS 


8-7 


13-6 


17-9 


21-8 


25-2 


8-7 


12-6 


15-10 


19-5 


22-6 




Douglas fir-larch 


#1 


7-11 


11-8 


14-9 


18-0 


20-11 


7-1 


10-5 


13-2 


16-1 


18-8 




Douglas fir-larch 


#2 


7-5 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 




Douglas fir-larch 


#3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 




Hem-fir 


SS 


8-1 


12-9 


16-9 


21-4 


24-8 


8-1 


12-4 


15-7 


19-1 


22-1 




Hem-fir 


#1 


7-9 


11-4 


14-4 


17-7 


20-4 


6-11 


10-2 


12-10 


15-8 


18-2 




Hem-fir 


#2 


7-4 


10-9 


13-7 


16-7 


19-3 


6-7 


9-7 


12-2 


14-10 


17-3 


19.2 


Hem-fir 


#3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


Southern pine 


SS 


8-5 


13-3 


17-5 


22-3 


Noteb 


8-5 


13-3 


17-5 


22-(j 


25-9 




Southern pine 


#1 


8-3 


13-0 


16-6 


19-7 


23-4 


7-11 


11-9 


14-9 


17-6 


20-11 




Southern pine 


#2 


7-11 


11-5 


14-9 


17-7 


20-7 


7-1 


10-2 


13-2 


15-9 


18-5 




Southern pine 


#3 


6-0 


8-10 


11-3 


13-4 


15-10 


5-4 


7-11 


10-1 


11-11 


14-2 




Spruce-pine-fir 


SS 


7-11 


12-5 


16-5 


20-2 


23-4 


7-11 


11-8 


14-9 


18-0 


20-11 




Spruce-pine-fir 


#1 


7-5 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 




Spruce-pine-fir 


#2 


7-5 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 




Spruce-pine-fir 


#3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 



(continued) 



254 



2006 INTERNATIONAL RESIDENTIAL CODE'' 

i 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (3)— continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=30 psf, ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


7-11 


12-6 


15-10 


19-5 


22-6 


7-8 


11-3 


14-2 


17-4 


20-1 




Douglas fir-larch 


#1 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 




Douglas fir-larch 


#2 


6-8 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 




Douglas fir-larch 
Hem-fir 


#3 
SS 


5-0 
7-6 


7-4 
11-10 


9-4 
15-7 


11-5 
19-1 


13-2 
22-1 


4-6 

7-6 


6-7 
11-0 


8-4 
13-11 


10-2 
17-0 


11-10 
19-9 




Hem-fir 


#1 


6-11 


10-2 


12-10 


15-8 


18-2 


6-2 


9-1 


11-6 


14-0 


16-3 




Hem-fir 


#2 


6-7 


9-7 


12-2 


14-10 


17-3 


5-10 


8-7 


10-10 


13-3 


15-5 


24 


Hem-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 


Southern pine 


SS 


7-10 


12-3 


16-2 


20-8 


25-1 


7-10 


12-3 


16-2 


19-8 


23-0 




Southern pine 


#1 


7-8 


11-9 


14-9 


17-6 


20-11 


7-1 


10-6 


13-2 


15-8 


18-8 




Southern pine 


#2 


7-1 


10-2 


13-2 


15-9 


18-5 


6-4 


9-2 


11-9 


14-1 


16-6 




Southern pine 


#3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-9 


7-1 


9-0 


10-8 


12-8 




Spruce-pine-fir 


SS 


7-4 


11-7 


14-9 


18-0 


20-11 


7-1 


10-5 


13-2 


16-1 


18-8 




Spruce-pine-fir 
Spruce-pine-fir 
Spruce-pine-fir 


#1 

#2 
#3 


6-8 
6-8 
5-0 


9-9 
9-9 

7-4 


12-4 
12-4 
9-4 


15-1 
15-1 
11-5 


17-6 
17-6 
13-2 


5-11 
5-11 
4-6 


8-8 
8-8 
6-7 


11-0 
11-0 
8-4 


13-6 
13-6 
10-2 


15-7 
15-7 
11-10 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiplied by the factors given below: 



Mc/Hn 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

//(- = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 
Hif = Height of roof ridge measured vertically above the top of the rafter support walls. 
b. Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



255 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(4) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=50 psf, ceiling not attached to rafters, L/A = 180) 



RAFTER 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








IVIaximum rafter spans 


a 








SPACING 
(inches) 


SPECIES AND GRADE 




(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


8-5 


13-3 


17-6 


22-4 


26-0 


8-5 


13-3 


17-0 


20-9 


24-0 




Douglas fir-larch 


#1 


8-2 


12-0 


15-3 


18-7 


21-7 


7-7 


11-2 


14-1 


17-3 


20-0 




Douglas fir-larch 


#2 


7-8 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 




Douglas fir-larch 


#3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 




Hem-fir 


SS 


8-0 


12-6 


16-6 


21-1 


25-6 


8-0 


12-6 


16-6 


20-4 


23-7 




Hem-fir 


#1 


7-10 


11-9 


14-10 


18-1 


21-0 


7-5 


10-10 


13-9 


16-9 


19-5 




Hem-fir 


#2 


7-5 


11-1 


14-0 


17-2 


19-11 


7-0 


10-3 


13-0 


15-10 


18-5 


12 


Hem-fir 


#3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Southern pine 


SS 


8-4 


13-0 


17-2 


21-11 


Noteb 


8-4 


13-0 


17-2 


21-11 


Noteb 




Southern pine 


#1 


8-2 


12-10 


16-10 


20-3 


24-1 


8-2 


12-6 


15-9 


18-9 


22-4 




Southern pine 


#2 


8-0 


11-9 


15-3 


18-2 


21-3 


7-7 


10-11 


14-1 


16-10 


19-9 




Southern pine 


#3 


6-2 


9-2 


11-8 


13-9 


16-4 


5-9 


8-5 


10-9 


12-9 


15-2 




Spruce-pine-fir 


SS 


7-10 


12-3 


16-2 


20-8 


24-1 


7-10 


12-3 


15-9 


19-3 


22-4 




Spruce-pine-fir 


#1 


7-8 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 




Spruce-pine-fir 


#2 


7-8 


11-3 


14-3 


17-5 


15-2 


7-1 


10-5 


13-2 


16-1 


18-8 




Spruce-pine-fir 


#3 


5-10 


8-6 


10-9 


13-2 


20-3 


5-5 


7-10 


10-0 


12-2 


14-1 




Douglas fir-larch 


SS 


7-8 


12-1 


15-10 


19-5 


22-6 


7-8 


11-7 


14-8 


17-11 


20-10 




Douglas fir-larch 


#1 


7-1 


10-5 


13-2 


16-1 


18-8 


6-7 


9-8 


12-2 


14-11 


17-3 




Douglas fir-larch 


#2 


6-8 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 




Douglas fir-larch 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 




Hem-fir 


SS 


7-3 


11-5 


15-0 


19-1 


22-1 


7-3 


11-5 


14-5 


17-8 


20-5 




Hem-fir 


#1 


6-11 


10-2 


12-10 


15-8 


18-2 


6-5 


9-5 


11-11 


14-6 


16-10 




Hem-fir 


#2 


6-7 


9-7 


12-2 


14-10 


17-3 


6-1 


8-11 


11-3 


13-9 


15-11 


16 


Hem-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 


Southern pine 


SS 


7-6 


11-10 


15-7 


19-11 


24-3 


7-6 


11-10 


15-7 


19-11 


23-10 




Southern pine 


#1 


7-5 


11-7 


14-9 


17-6 


20-11 


7-4 


10-10 


13-8 


16-2 


19-4 




Southern pine 


#2 


7-1 


10-2 


13-2 


15-9 


18-5 


6-7 


9-5 


12-2 


14-7 


17-1 




Southern pine 


#3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-11 


7-4 


9-4 


11-0 


13-1 




Spruce-pine-fir 


SS 


7-1 


11-2 


14-8 


18-0 


20-11 


7-1 


10-9 


13-8 


15-11 


19-4 




Spruce-pine-fir 


#1 


6-8 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 




Spruce-pine-fir 


#2 


6-8 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 




Spruce-pine-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 




Douglas fir-larch 


SS 


7-3 


11-4 


14-6 


17-8 


20-6 


7-3 


10-7 


13-5 


16-5 


19-0 




Douglas fir-larch 


#1 


6-6 


9-6 


12-0 


14-8 


17-1 


6-0 


8-10 


11-2 


13-7 


15-9 




Douglas fir-larch 


#2 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 




Douglas fir-larch 


#3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 




Hem-fir 


SS 


6-10 


10-9 


14-2 


17-5 


20-2 


6-10 


10-5 


13-2 


16-1 


18-8 




Hem-fir 


#1 


6-4 


9-3 


11-9 


14-4 


16-7 


5-10 


8-7 


10-10 


13-3 


15-5 




Hem-fir 


#2 


6-0 


8-9 


11-1 


13-7 


15-9 


5-7 


8-1 


10-3 


12-7 


14-7 


19.2 


Hem-fir 


#3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


Southern pine 


SS 


7-1 


11-2 


14-8 


18-9 


22-10 


7-1 


11-2 


14-8 


18 7 


21-9 




Southern pine 


#1 


7-0 


10-8 


13-5 


16-0 


19-1 


6-8 


9-11 


12-5 


14-10 


17-8 




Southern pine 


#2 


6-6 


9-4 


12-0 


14-4 


16-10 


6-0 


8-8 


11-2 


13-4 


15-7 




Southern pine 


#3 


4-11 


7-3 


9-2 


10-10 


12-11 


4-6 


6-8 


8-6 


10- i 


12-0 




Spruce-pine-fir 


SS 


6-8 


10-6 


13-5 


16-5 


19-1 


6-8 


9-10 


12-5 


15-3 


17-8 




Spruce-pine-fir 


#1 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 




Spruce-pine-fir 


#2 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 




Spruce-pine-fir 


#3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 



(continued) 



256 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (4)— continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=50 psf, ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 




DEAD LOAD = 


20 psf 




2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 


Maximum rafter spans^ 


(feet - 
inches) 


(feet- 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


6-8 


10- 


13-0 


15-10 


18-4 


6-6 


9-6 


12-0 


14-8 


17-0 




Douglas fir-larch 


#1 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 




Douglas fir-larch 


#2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 




Douglas fir-larch 


#3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 




Hem-fir 


SS 


6-4 


9-11 


12-9 


15-7 


18-0 


6-4 


9-4 


11-9 


14-5 


16-8 




Hem-fir 


#1 


5-8 


8-3 


10-6 


12-10 


14-10 


5-3 


7-8 


9-9 


11-10 


13-9 




Hem-fir 


#2 


5-4 


7-10 


9-11 


12-1 


14-1 


4-11 


7-3 


9-2 


11-3 


13-0 


24 


Hem-fir 


#3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 


Southern pine 


SS 


6-7 


10-4 


13-8 


17-5 


21-0 


6-7 


10-4 


13-8 


16-7 


19-5 




Southern pine 


#1 


6-5 


9-7 


12-0 


14-4 


17-1 


6-0 


8-10 


11-2 


13-3 


15-9 




Southern pine 


#2 


5-10 


8-4 


10-9 


12-10 


15-1 


5-5 


7-9 


10-0 


11-11 


13-11 




Southern pine 


#3 


4-4 


6-5 


8-3 


9-9 


11-7 


4-1 


6-0 


7-7 


9-0 


10-8 




Spruce-pine-fir 


SS 


6-2 


9-6 


12-0 


14-8 


17-1 


6-0 


8-10 


11-2 


13-7 


15-9 




Spruce-pine-fir 


#1 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 




Spruce-pine-fir 


#2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 




Spruce-pine-fir 


#3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiplied by the factors given below: 



Hc/Hf, 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

H(^ = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 
H[{ = Height of roof ridge measured vertically above the top of the rafter support walls, 
b. Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



257 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(5) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=30 psf, ceiling aHached to rafters, L/A = 240) 



RAFTFR 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








nMr 1 tn 
SPACING 
(inches) 


SPECIES AND GRADE 




(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


9-1 


14-4 


18-10 


24-1 


Noteb 


9-1 


14-4 


18-10 


24-1 


Noteb 




Douglas fir-larch 


#1 


8-9 


13-9 


18-2 


22-9 


Noteb 


8-9 


13-2 


16-8 


20-4 


23-7 




Douglas fir-larch 


#2 


8-7 


13-6 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 




Douglas fir-larch 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 




Hem-fir 


SS 


8-7 


13-6 


17-10 


22-9 


Noteb 


8-7 


13-6 


17-10 


22-9 


Noteb 




Hem-fir 


#1 


8-5 


13-3 


17-5 


22-2 


25-9 


8-5 


12-10 


16-3 


19-10 


23-0 




Hem-fir 


#2 


8-0 


12-7 


16-7 


21-0 


24-4 


8-0 


12-2 


15-4 


18-9 


21-9 


12 


Hem-fir 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Southern pine 


SS 


8-11 


14-1 


18-6 


23-8 


Noteb 


8-11 


14-1 


18-6 


23-8 


Noteb 




Southern pine 


#1 


8-9 


13-9 


18-2 


23-2 


Noteb 


8-9 


13-9 


18-2 


22-2 


Noteb 




Southern pine 


#2 


8-7 


13-6 


17-10 


22-3 


Noteb 


8-7 


12-11 


16-8 


19-11 


23-4 




Southern pine 


#3 


7-7 


11-2 


14-3 


16-10 


20-0 


6-9 


10-0 


12-9 


15-1 


17-11 




Spruce-pine-fir 


SS 


8-5 


13-3 


17-5 


22-3 


Noteb 


8-5 


13-3 


17-5 


22-3 


Noteb 




Spruce-pine-fir 


#1 


8-3 


12-11 


17-0 


21-4 


24-8 


8-3 


12-4 


15-7 


19-1 


22-1 




Spruce-pine-fir 


#2 


8-3 


12-11 


17-0 


21-4 


24-8 


8-3 


12-4 


15-7 


19-1 


22-1 




Spruce-pine-fir 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 




Douglas fir-larch 


SS 


8-3 


13-0 


17-2 


21-10 


Noteb 


8-3 


13-0 


■ 17-2 


21-3 


24-8 




Douglas fir-larch 


#1 


8-0 


12-6 


16-2 


19-9 


22-10 


7-10 


11-5 


14-5 


17-8 


20-5 




Douglas fir-larch 


#2 


7-10 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 




Douglas fir-larch 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 




Hem-fir 


SS 


7-10 


12-3 


16-2 


20-8 


25-1 


7-10 


12-3 


16-2 


20-8 


24-2 




Hem-fir 


#1 


7-8 


12-0 


15-9 


19-3 


22-3 


7-7 


11-1 


14-1 


17-2 


19-11 




Hem-fir 


#2 


7-3 


11-5 


14-11 


18-2 


21-1 


7-2 


10-6 


13-4 


16-3 


18-10 


16 


Hem-fir 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 


Southern pine 


SS 


8-1 


12-9 


16-10 


21-6 


Noteb 


8-1 


12-9 


16-10 


21-6 


Noteb 




Southern pine 


#1 


8-0 


12-6 


16-6 


21-1 


25-7 


8-0 


12-6 


16-2 


19-2 


22-10 




Southern pine 


#2 


7-10 


12-3 


16-2 


19-3 


22-7 


7-10 


11-2 


14-5 


17-3 


20-2 




Southern pine 


#3 


6-7 


9-8 


12-4 


14-7 


17-4 


5-10 


8-8 


11-0 


13-0 


15-6 




Spruce-pine-fir 


SS 


7-8 


12-0 


15-10 


20-2 


24-7 


7-8 


12-0 


15-10 


19-9 


22-10 




Spruce-pine-fir 


#1 


7-6 


11-9 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 




Spruce-pine-fir 


#2 


7-6 


11-9 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 




Spruce-pine-fir 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 




Douglas fir-larch 


SS 


7-9 


12-3 


16-1 


20-7 


25-0 


7-9 


12-3 


15-10 


19-5 


22-6 




Douglas fir-larch 


#1 


7-6 


11-8 


14-9 


18-0 


20-11 


7-1 


10-5 


13-2 


16-1 


18-8 




Douglas fir-larch 


#2 


7-4 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 




Douglas fir-larch 


#3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 




Hem-fir 


SS 


7-4 


11-7 


15-3 


19-5 


23-7 


7-4 


11-7 


15-3 


19-1 


22-1 




Hem-fir 


#1 


7-2 


11-4 


14-4 


17-7 


20-4 


6-11 


10-2 


12-10 


15-8 


18-2 




Hem-fir 


#2 


6-10 


10-9 


13-7 


16-7 


19-3 


6-7 


9-7 


12-2 


14-10 


17-3 


19.2 


Hem-fir 


#3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


Southern pine 


SS 


7-8 


12-0 


15-10 


20-2 


24-7 


7-8 


12-0 


15-10 


20-2 


24-7 




Southern pine 


#1 


7-6 


11-9 


15-6 


19-7 


23-4 


7-6 


11-9 


14-9 


17-6 


20-11 




Southern pine 


#2 


7-4 


11-5 


14-9 


17-7 


20-7 


7-1 


10-2 


13-2 


15-9 


18-5 




Southern pine 


#3 


6-0 


8-10 


11-3 


13-4 


15-10 


5-4 


7-11 


10-1 


11-11 


14-2 




Spruce-pine-fir 


SS 


7-2 


11-4 


14-11 


19-0 


23-1 


7-2 


11-4 


14-9 


18-0 


20-11 




Spruce-pine-fir 


#1 


7-0 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 




Spruce-pine-fir 


#2 


7-0 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 




Spruce-pine-fir 


#3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 



(continued) 



258 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (5)— continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=30 psf, ceiling attaclied to rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 




Douglas fir-larch 
Douglas fir-larch 


SS 

#1 


7-3 
7-0 


11-4 
10-5 


15-0 
13-2 


19-1 
16-1 


22-6 
18-8 


7-3 
6-4 


11-3 
9-4 


14-2 
11-9 


17-4 
14-5 


20-1 
16-8 




Douglas fir-larch 


#2 


6-8 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 




Douglas fir-larch 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 




Hem-fir 


SS 


6-10 


10-9 


14-2 


18-0 


21-11 


6-10 


10-9 


13-11 


17-0 


19-9 




Hem-fir 


#1 


6-8 


10-2 


12-10 


15-8 


18-2 


6-2 


9-1 


11-6 


14-0 


16-3 




Hem-fir 


#2 


6-4 


9-7 


12-2 


14-10 


17-3 


5-10 


8-7 


10-10 


13-3 


15-5 


24 


Hem-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 


Southern pine 


SS 


7-1 


11-2 


14-8 


18-9 


22-10 


7-1 


11-2 


14-8 


18-9 


22-10 




Southern pine 


#1 


7-0 


10-11 


14-5 


17-6 


20-11 


7-0 


10-6 


13-2 


15-8 


18-8 




Southern pine 


#2 


6-10 


10-2 


13-2 


15-9 


18-5 


6-4 


9-2 


11-9 


14-1 


16-6 




Southern pine 


#3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-9 


7-1 


9-0 


10-8 


12-8 




Spruce-pine-fir 


SS 


6-8 


10-6 


13-10 


17-8 


20-11 


6-8 


10-5 


13-2 


16-1 


18-8 




Spruce-pine-fir 


#1 


6-6 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 




Spruce-pine-fir 
Spruce-pine-fir 


#2 
#3 


6-6 
5-0 


9-9 

7-4 


12-4 
9-4 


15-1 
11-5 


17-6 
13-2 


5-11 
4-6 


8-8 
6-7 


11-0 

8-4 


13-6 
10-2 


15-7 
11-10 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot - 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiplied by the factors given below: 



»CJ»R 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

Hq = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 
Hjf = Height of roof ridge measured vertically above the top of the rafter support walls, 
b. Span exceeds 26 feet in length. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



259 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(6) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=50 psf, ceiling attached to rafters, L/A = 240) 



RAFTFR 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








IVIaximum rafter spans 


a 








riMi 1 en 

SPACING 
(inches) 


SPECIES AND GRADE 




(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 




Douglas fir-larch 


SS 


7-8 


12-1 


15-11 


: 20-3 


24-8 


7-8 


12-1 


15-11 


20-3 


24-0 




Douglas fir-larch 


#1 


7-5 


11-7 


15-3 


18-7 


21-7 


7-5 


11-2 


14-1 


17-3 


20-0 




Douglas fir-larch 


#2 


7-3 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 




Douglas fir-larch 


#3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 




Hem-fir 


SS 


7-3 


11-5 


15-0 


19-2 


23-4 


7-3 


11-5 


15-0 


19-2 


23-4 




Hem-fir 


#1 


7-1 


11-2 


14-8 


18-1 


21-0 


7-1 


10-10 


13-9 


16-9 


19-5 




Hem-fir 


#2 


6-9 


10-8 


14-0 


17-2 


19-11 


6-9 


10-3 


13-0 


15-10 


18-5 


12 


Hem-fir 


#3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Southern pine 


SS 


7-6 


11-10 


15-7 


19-11 


24-3 


7-6 


11-10 


15-7 


19-11 


24-3 




Southern pine 


#1 


7-5 


11-7 


15-4 


19-7 


23-9 


7-5 


11-7 


15-4 


18-9 


22-4 




Southern pine 


#2 


7-3 


11-5 


15-0 


18-2 


21-3 


7-3 


10-11 


14-1 


16-10 


19-9 




Southern pine 


#3 


6-2 


9-2 


11-8 


13-9 


16-4 


5-9 


8-5 


10-9 


12-9 


15-2 




Spruce-pine-fir 


SS 


7-1 


11-2 


14-8 


18-9 


22-10 


7-1 


11-2 


14-8 


18-9 


22-4 




Spruce-pine-fir 


#1 


6-11 


10-11 


14-3 


, 17-5 


20-2 


6-11 


10-5 


13-2 


16-1 


18-8 




Spruce-pine-fir 


#2 


6-11 


10-11 


14-3 


17-5 


20-2 


6-11 


10-5 


13-2 


16-1 


18-8 




Spruce-pine-fir 


#3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 




Douglas fir-larch 


SS 


7-0 


11-0 


14-5 


18-5 


22-5 


7-0 


11-0 


14-5 


17-11 


20-10 




Douglas fir-larch 


#1 


6-9 


10-5 


13-2 


16-1 


18-8 


6-7 


9-8 


12-2 


14-11 


17-3 




Douglas fir-larch 


#2 


6-7 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 




Douglas fir-larch 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 




Hem-fir 


SS 


6-7 


10-4 


13-8 


17-5 


21-2 


6-7 


10-4 


13-8 


17-5 


20-5 




Hem-fir 


#1 


6-5 


10-2 


12-10 


15-8 


18-2 


6-5 


9-5 


11-11 


14-6 


16-10 




Hem-fir 


#2 


6-2 


9-7 


12-2 


14-10 


17-3 


6-1 


8-11 


11-3 


13-9 


15-11 


16 


Hem-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 


Southern pine 


SS 


6-10 


10-9 


14-2 


18-1 


22-0 


6-10 


10-9 


14-2 


18-1 


22-0 




Southern pine 


#1 


6-9 


10-7 


13-11 


17-6 


20-11 


6-9 


10-7 


13-8 


16-2 


19-4 




Southern pine 


#2 


6-7 


10-2 


13-2 


15-9 


18-5 


6-7 


9-5 


12-2 


14-7 


17-1 




Southern pine 


#3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-11 


7-4 


9-4 


11-0 


13-1 




Spruce-pine-fir 


SS 


6-5 


10-2 


13-4 


17-0 


20-9 


6-5 


10-2 


13-4 


16-8 


19-4 




Spruce-pine-fir 


#1 


6-4 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 




Spruce-pine-fir 


#2 


6-4 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 




Spruce-pine-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 




Douglas fir-larch 


SS 


6-7 


10-4 


13-7 


17-4 


20-6 


6-7 


10-4 


13-5 


16-5 


19-0 




Douglas fir-larch 


#1 


6-4 


9-6 


12-0 


14-8 


17-1 


6-0 


8-10 


11-2 


13-7 


15-9 




Douglas fir-larch 


#2 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 




Douglas fir-larch 


#3 


4-7 


6-9 


8-6 


. 10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 




Hem-fir 


SS 


6-2 


9-9 


12-10 


16-5 


19-11 


6-2 


9-9 


12-10 


16-1 


18-8 




Hem-fir 


#1 


6-1 


9-3 


11-9 


14-4 


16-7 


5-10 


8-7 


10-10 


13-3 


15-5 




Hem-fir 


#2 


5-9 


8-9 


11-1 


13-7 


15-9 


5-7 


8-1 


10-3 


12-7 


14-7 


19.2 


Hem-fir 


#3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


Southern pine 


SS 


6-5 


10-2 


13-4 


17-0 


20-9 


6-5 


10-2 


13-4 


17-0 


20-9 




Southern pine 


#1 


6-4 


9-11 


13-1 


16-0 


19-1 


6-4 


9-11 


12-5 


14-10 


17-8 




Southern pine 


#2 


6-2 


9-4 


12-0 


14-4 


16-10 


6-0 


8-8 


11-2 


13-4 


15-7 




Southern pine 


#3 


4-11 


7-3 


9-2 


10-10 


12-11 


4-6 


6-8 


8-6 


10-1 


12-0 




Spruce-pine-fir 


SS 


6-1 


9-6 


12-7 


16-0 


19-1 


6-1 


9-6 


12-5 


15-3 


17-8 




Spruce-pine-fir 


#1 


5-11 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 




Spruce-pine-fir 


#2 


5-11 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 




Spruce-pine-fir 


#3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 



(continued) 



260 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (6)— continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground snow load=50 psf, ceiling attached to rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 




Douglas fir-larch 


SS 


6-1 


9-7 


12-7 


15-10 


18-4 


6-1 


9-6 


12-0 


14-8 


17-0 




Douglas fir-larch 


#1 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 




Douglas fir-larch 


#2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 




Douglas fir-larch 


#3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 




Hem-fir 


SS 


5-9 


9-1 


11-11 


15-2 


18-0 


5-9 


9-1 


11-9 


14-5 


15-11 




Hera-fir 


#1 


5-8 


8-3 


10-6 


12-10 


14-10 


5-3 


7-8 


9-9 


11-10 


13-9 




Hem-fir 


#2 


5-4 


7-10 


9-11 


12-1 


14-1 


4-11 


7-3 


9-2 


11-3 


13-0 


24 


Hera-fir 


#3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 


Southern pine 


SS 


6-0 


9-5 


12-5 


15-10 


19-3 


6-0 


9-5 


12-5 


15-10 


19-3 




Southern pine 


#1 


5-10 


9-3 


12-0 


14-4 


17-1 


5-10 


8-10 


11-2 


13-3 


15-9 




Southern pine 


#2 


5-9 


8-4 


10-9 


12-10 


15-1 


5-5 


7-9 


10-0 


11-11 


13-11 




Southern pine 


#3 


4-4 


6-5 


8-3 


9-9 


11-7 


4-1 


6-0 


7-7 


9-0 


10-8 




Spruce-pine-fir 


SS 


5-8 


8-10 


11-8 


14-8 


17-1 


5-8 


8-10 


11-2 


13-7 


15-9 




Spruce-pine-fir 


#1 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 




Spruce-pine-fir 


#2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 




Spruce-pine-fir 


#3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiplied by the factors given below: 



Hc/H„ 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

//(^ = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 

///; = Height of roof ridge measured vertically above the top of the rafter support walls. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



261 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(7) 

RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD 

(Ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 




DEAD LOAD = 1 


Opsf 




DEAD LOAD = 20 psf 


2x4 


2x6 ^ 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 


Maximum Rafter Spans^ 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 


(feet- 
inches) 




Douglas fir-larch 


SS 


7-7 


11-10 


15-8 


19-5 


22-6 


7-7 


11-10 


15-0 


18-3 


21-2 




Douglas fir-larch 


#1 


7-1 


10-5 


13-2 


16-1 


18-8 


6-8 


9-10 


12-5 


15-2 


17-7 




Douglas fir-larch 


#2 


6-8 


9-9 


12-4 


15-1 


17-6 


6-3 


9-2 


11-8 


14-2 


16-6 




Douglas fir-larch 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 




Hem-fir 


SS 


7-2 


11-3 


14-9 


18-10 


22-1 


7-2 


11-3 


14-8 


18-0 


20-10 




Hem-fir 


#1 


6-11 


10-2 


12-10 


15-8 


18-2 


6-6 


9-7 


12-1 


14-10 


17-2 




Hem-fir 


#2 


6-7 


9-7 


12-2 


14-10 


17-3 


6-2 


9-1 


11-5 


14-0 


16-3 


12 


Hem-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 


Southern pine 


SS 


7-5 


11-8 


15-4 


19-7 


23-10 


7-5 


11-8 


15-4 


19-7 


23-10 




Southern pine 


#1 


7-3 


11-5 


14-9 


17-6 


20-11 


7-3 


11-1 


13-11 


16-6 


19-8 




Southern pine 


#2 


7-1 


10-2 


13-2 


15-9 


18-5 


6-8 


9-7 


12-5 


14-10 


17-5 




Southern pine 


#3 


5-4 


7-11 


10-1 


11-11 


14-2 


5-1 


7-5 


9-6 


11-3 


13-4 




Spruce-pine-fir 


SS 


7-0 


11-0 


14-6 


18-0 


20-11 


7-0 


11-0 


13-11 


17-0 


19-8 




Spruce-pine-fir 


#1 


6-8 


9-9 


12-4 


15-1 


17-6 


6-3 


9-2 


11-8 


14-2 


16-6 




Spruce-pine-fir 


#2 


6-8 


9-9 


12-4 


15-1 


17-6 


6-3 


9-2 


11-8 


14-2 


16-6 




Spruce-pine-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 




Douglas fir-larch 


SS 


6-10 


10-9 


13-9 


16-10 


19-6 


6-10 


10-3 


13-0 


15-10 


18-4 




Douglas fir-larch 


#1 


6-2 


9-0 


11-5 


13-11 


16-2 


5-10 


8-6 


10-9 


13-2 


15-3 




Douglas fir-larch 


#2 


5-9 


8-5 


10-8 


13-1 


15-2 


5-5 


7-11 


10-1 


12-4 


14-3 




Douglas fir-larch 


#3 


4-4 


6-4 


8-1 


9-10 


11-5 


4-1 


6-0 


7-7 


9-4 


10-9 




Hem-fir 


SS 


6-6 


10-2 


13-5 


16-6 


19-2 


6-6 


10-1 


12-9 


15-7 


18-0 




Hem-fir 


#1 


6-0 


8-9 


11-2 


13-7 


15-9 


5-8 


8-3 


10-6 


12-10 


14-10 




Hem-fir 


#2 


5-8 


8-4 


10-6 


12-10 


14-11 


5-4 


7-10 


9-11 


12-1 


14-1 


16 


Hem-fir 


#3 


4-4 


6-4 


8-1 


9-10 


11-5 


4-1 


6-0 


7-7 


9-4 


10-9 


Southern pine 


SS 


6-9 


10-7 


14-0 


17-10 


21-8 


6-9 


10-7 


14-0 


17-10 


21-0 




Southern pine 


#1 


6-7 


10-2 


12-9 


15-2 


18-1 


6-5 


9-7 


12-0 


14-4 


17-1 




Southern pine 


#2 


6-2 


8-10 


11-5 


13-7 


16-0 


5-10 


8-4 


10-9 


12-10 


15-1 




Southern pine 


#3 


4-8 


6-10 


8-9 


10-4 


12-3 


4-4 


6-5 


8-3 


9-9 


11-7 




Spruce-pine-fir 


SS 


6-4 


10-0 


12-9 


15-7 


18-1 


6-4 


9-6 


12-0 


14-8 


17-1 




Spruce-pine-fir 


#1 


5-9 


8-5 


10-8 


13-1 


15-2 


5-5 


7-11 


10-1 


12-4 


14-3 




Spruce-pine-fir 


#2 


5-9 


8-5 


10-8 


13-1 


15-2 


5-5 


7-11 


10-1 


12-4 


14-3 




Spruce-pine-fir 


#3 


4-4 


6-4 


8-1 


9-10 


11-5 


4-1 


6-0 


7-7 


9-4 


10-9 




Douglas fir-larch 


SS 


6-5 


9-11 


12-7 


15-4 


17-9 


6-5 


9-4 


11-10 


14-5 


16-9 




Douglas fir-larch 


#1 


5-7 


8-3 


10-5 


12-9 


14-9 


5-4 


7-9 


9-10 


12-0 


13-11 




Douglas fir-larch 


#2 


5-3 


7-8 


9-9 


11-11 


13-10 


5-0 


7-3 


9-2 


11-3 


13-0 




Douglas fir-larch 


#3 


4-0 


5-10 


7-4 


9-0 


10-5 


3-9 


5-6 


6-11 


8-6 


9-10 




Hem-fir 


SS 


6-1 


9-7 


12-4 


15-1 


17-4 


6-1 


9-2 


11-8 


14-2 


15-5 




Hem-fir 


#1 


5-6 


8-0 


10-2 


12-5 


14-5 


5-2 


7-7 


9-7 


11-8 


13-7 




Hem-fir 


#2 


5-2 


7-7 


9-7 


11-9 


13-7 


4-11 


7-2 


9-1 


11-1 


12-10 


19.2 


Hem-fir 


#3 


4-0 


5-10 


7-4 


9-0 


10-5 


3-9 


5-6 


6-11 


8-6 


9-10 


Southern pine 


SS 


6-4 


10-0 


13-2 


16-9 


20-4 


6-4 


10-0 


13-2 


16-5 


19-2 




Southern pine 


#1 


6-3 


9-3 


11-8 


13-10 


16-6 


5-11 


8-9 


11-0 


13-1 


15-7 




Southern pine 


#2 


5-7 


8-1 


10-5 


12-5 


14-7 


5-4 


7-7 


9-10 


11-9 


13-9 




Southern pine 


#3 


4-3 


6-3 


8-0 


9-5 


11-2 


4-0 


5-11 


7-6 


8-10 


10-7 




Spruce-pine-fir 


SS 


6-0 


9-2 


11-8 


14-3 


16-6 


5-11 


8-8 


11-0 


13-5 


15-7 




Spruce-pine-fir 


#1 


5-3 


7-8 


9-9 


11-11 


13-10 


5-0 


7-3 


•9-2 


11-3 


13-0 




Spruce-pine-fir 


#2 


5-3 


7-8 


9-9 


11-11 


13-10 


5-0 


7-3 


9-2 


11-3 


13-0 




Spruce-pine-fir 


#3 


4-0 


5-10 


7-4 


9-0 


10-5 


3-9 


5-6 


6-11 


8-6 


9-10 



(continued) 



262 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (7)— continued 

RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD 

(Ceiling not attached to rafters, L/A = 180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








lUlaximum rafter spans 


a 








(feet- 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


6-0 


8-10 


11-3 


13-9 


15-11 


5-9 


8-4 


10-7 


12-11 


15-0 




Douglas fir-larch 


#1 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 




Douglas fir-larch 


#2 


4-8 


6-11 


8-9 


10-8 


12-4 


4-5 


6-6 


8-3 


10-0 


11-8 




Douglas fir-larch 


#3 


3-7 


5-2 


6-7 


8-1 


9-4 


3-4 


4-11 


6-3 


7-7 


8-10 




Hem-fir 


SS 


5-8 


8-8 


11-0 


13-6 


13-11 


5-7 


8-3 


10-5 


12-4 


12-4 




Hem-fir 


#1 


4-11 


7-2 


9-1 


11-1 


12-10 


4-7 


6-9 


8-7 


10-6 


12-2 




Hem-fir 


#2 


4-8 


6-9 


8-7 


10-6 


12-2 


4-4 


6-5 


8-1 


9-11 


11-6 


24 


Hem-fir 


#3 


3-7 


5-2 


6-7 


8-1 


9-4 


3-4 


4-11 


6-3 


7-7 


8-10 


Southern pine 


SS 


5-11 


9-3 


12-2 


15-7 


18-2 


5-11 


9-3 


12-2 


14-8 


17-2 




Southern pine 


#1 


5-7 


8-3 


10-5 


12-5 


14-9 


5-3 


7-10 


9-10 


11-8 


13-11 




Southern pine 


#2 


5-0 


7-3 


9-4 


11-1 


13-0 


4-9 


6-10 


8-9 


10-6 


12-4 




Southern pine 


#3 


3-9 


5-7 


7-1 


8-5 


10-0 


3-7 


5-3 


6-9 


7-11 


9-5 




Spruce-pine-fir 


SS 


5-6 


8-3 


10-5 


12-9 


14-9 


5-4 


7-9 


9-10 


12-0 


12-11 




Spruce-pine-fir 


#1 


4-8 


6-11 


8-9 


10-8 


12-4 


4-5 


6-6 


8-3 


10-0 


11-8 




Spruce-pine-fir 


#2 


4-8 


6-11 


8-9 


10-8 


12-4 


4-5 


6-6 


8-3 


10-0 


11-8 




Spruce-pine-fir 


#3 


3-7 


5-2 


6-7 


8-1 


9-4 


3-4 


4-11 


6-3 


7-7 


8-10 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters 

on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be 

multiplied by the factors given below: 



«c/H« 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

H(2 = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 

Hk - Height of roof ridge measured vertically above the top of the rafter support walls. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



263 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(8) 

RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD 

(Ceiling attached to rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 






DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








SPECIES AND GRADE 




(feet - 
inches) 


(feet - 
Inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


6-10 


10-9 


14-3 


18-2 


22-1 


6-10 


10-9 


14-3 


18-2 


21-2 




Douglas fir-larch 


#1 


6-7 


10-5 


13-2 


16-1 


18-8 


6-7 


9-10 


12-5 


15-2 


17-7 




Douglas fir-larch 


#2 


6-6 


9-9 


12-4 


15-1 


17-6 


6-3 


9-2 


11-8 


14-2 


16-6 




Douglas fir-larch 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 




Hem-fir 


SS 


6-6 


10-2 


13-5 


17-2 


20-10 


6-6 


10-2 


13-5 


17-2 


20-10 




Hem-fir 


#1 


6-4 


10-0 


12-10 


15-8 


18-2 


6-4 


9-7 


12-1 


14-10 


17-2 




Hem-fir 


#2 


6-1 


9-6 


12-2 


14-10 


17-3 


6-1 


9-1 


11-5 


14-0 


16-3 


12 


Hem-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 


Southern pine 


SS 


6-9 


10-7 


14-0 


17-10 


21-8 


6-9 


10-7 


14-0 


17-10 


21-8 




Southern pine 


#1 


6-7 


10-5 


13-8 


17-6 


20-11 


6-7 


10-5 


13-8 


16-6 


19-8 




Southern pine 


#2 


6-6 


10-2 


13-2 


15-9 


18-5 


6-6 


9-7 


12-5 


14-10 


17-5 




Southern pine 


#3 


5-4 


7-11 


10-1 


11-11 


14-2 


5-1 


7-5 


9-6 


11-3 


13-4 




Spruce-pine-fir 


SS 


6-4 


10-0 


13-2 


16-9 


20-5 


6-4 


10-0 


13-2 


16-9 


19-8 




Spruce-pine-fir 


#1 


6-2 


9-9 


12-4 


15-1 


17-6 


6-2 


9-2 


11-8 


14-2 


16-6 




Spruce-pine-fir 


#2 


6-2 


9-9 


12-4 


15-1 


17-6 


6-2 


9-2 


11-8 


14-2 


16-6 




Spruce-pine-fir 


#3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 




Douglas fir-larch 


SS 


6-3 


9-10 


12-11 


16-6 


19-6 


6-3 


9-10 


12-11 


15-10 


18-4 




Douglas fir-larch 


#1 


6-0 


9-0 


11-5 


13-11 


16-2 


5-10 


8-6 


10-9 


13-2 


15-3 




Douglas fir-larch 


#2 


5-9 


8-5 


10-8 


13-1 


15-2 


5-5 


7-11 


10-1 


12-4 


14-3 




Douglas fir-larch 


#3 


4-4 


6-4 


8-1 


9-10 


U-5 


4-1 


6-0 


7-7 


9-4 


10-9 




Hem-fir 


SS 


5-11 


9-3 


12-2 


15-7 


18-11 


5-11 


9-3 


12-2 


15-7 


18-0 




Hem-fir 


#1 


5-9 


8-9 


11-2 


13-7 


15-9 


5-8 


8-3 


10-6 


12-10 


14-10 




Hem-fir 


#2 


5-6 


8-4 


10-6 


12-10 


14-11 


5-4 


7-10 


9-11 


12-1 


14-1 


16 


Hem-fir 


#3 


4-4 


6-4 


8-1 


9-10 


11-5 


4-1 


6-0 


7-7 


9-4 


10-9 


Southern pine 


SS 


6-1 


9-7 


12-8 


16-2 


19-8 


6-1 


9-7 


12-8 


16-2 


19-8 




Southern pine 


#1 


6-0 


9-5 


12-5 


15-2 


18-1 


6-0 


9-5 


12-0 


14-4 


17-1 




Southern pine 


#2 


5-11 


8-10 


11-5 


13-7 


16-0 


5-10 


8-4 


10-9 


12-10 


15-1 




Southern pine 


#3 


4-8 


6-10 


8-9 


10-4 


12-3 


4-4 


6-5 


8-3 


9-9 


11-7 




Spruce-pine-fir 


SS 


5-9 


9-1 


11-11 


15-3 


18-1 


5-9 


9-1 


11-11 


14-8 


17-1 




Spruce-pine-fir 


#1 


5-8 


8-5 


10-8 


13-1 


15-2 


5-5 


7-11 


10-1 


12-4 


14-3 




Spruce-pine-fir 


#2 


5-8 


8-5 


10-8 


13-1 


15-2 


5-5 


7-11 


10-1 


12-4 


14-3 




Spruce-pine-fir 


#3 


4-4 


6-4 


8-1 


9-10 


11-5 


4-1 


6-0 


7-7 


9-4 


10-9 




Douglas fir-larch 


SS 


5-10 


9-3 


12-2 


15-4 


17-9 


5-10 


9-3 


11-10 


14-5 


16-9 




Douglas fir-larch 


#1 


5-7 


8-3 


10-5 


12-9 


14-9 


5-4 


7-9 


9-10 


12-0 


13-11 




Douglas fir-larch 


#2 


5-3 


7-8 


9-9 


11-11 


13-10 


5-0 


7-3 


9-2 


11-3 


13-0 




Douglas fir-larch 


#3 


4-0 


5-10 


7-4 


9-0 


10-5 


3-9 


5-6 


6-11 


8-6 


9-10 




Hem-fir 


SS 


5-6 


8-8 


11-6 


14-8 


17-4 


5-6 


8-8 


11-6 


14-2 


15-5 




Hem-fir 


#1 


5-5 


8-0 


10-2 


12-5 


14-5 


5-2 


7-7 


9-7 


11-8 


13-7 




Hem-fir 


#2 


5-2 


7-7 


9-7 


11-9 


13-7 


4-11 


7-2 


9-1 


11-1 


12-10 


19.2 


Hem-fir 


#3 


4-0 


5-10 


7-4 


9-0 


10-5 


3-9 


5-6 


6-11 


8-6 


9-10 


Southern pine 


SS 


5-9 


9-1 


11-11 


15-3 


18-6 


5-9 


9-1 


11-11 


15-3 


18-6 




Southern pine 


#1 


5-8 


8-11 


11-8 


13-10 


16-6 


5-8 


8-9 


11-0 


13-1 


15-7 




Southern pine 


#2 


5-6 


8-1 


10-5 


12-5 


14-7 


5-4 


7-7 


9-10 


11-9 


13-9 




Southern pine 


#3 


4-3 


6-3 


8-0 


9-5 


11-2 


4-0 


5-11 


7-6 


8-10 


10-7 




Spruce-pine-fir 


SS 


5-5 


8-6 


11-3 


14-3 


16-6 


5-5 


8-6 


11-0 


13-5 


15-7 




Spruce-pine-fir 


#1 


5-3 


7-8 


9-9 


11-11 


13-10 


5-0 


7-3 


9-2 


11-3 


13-0 




Spruce-pine-fir 


#2 


5-3 


7-8 


9-9 


11-11 


13-10 


5-0 


7-3 


9-2 


11-3 


13-0 




Spruce-pine-fir 


#3 


4-0 


5-10 


7-4 


9-0 


10-5 


3-9 


5-6 


6-11 


8-6 


9-10 



(continued) 



264 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1 (8)— continued 

RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD^ 

(Ceiling attached to rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x4 


2x6 


2x8 


2x10 


2x12 


2x4 


2x6 


2x8 


2x10 


2x12 








Maximum rafter spans 


a 








(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 


(feet - 
inches) 




Douglas fir-larch 


SS 


5-5 


8-7 


11-3 


13-9 


15-11 


5-5 


8-4 


10-7 


12-11 


15-0 




Douglas fir-larch 


#1 


5-0 


7-4 


9-4 


11-5 


13-2 


4-9 


6-11 


8-9 


10-9 


12-5 




Douglas fir-larch 


#2 


4-8 


6-11 


8-9 


10-8 


12-4 


4-5 


6-6 


8-3 


10-0 


11-8 




Douglas fir-larch 


#3 


3-7 


5-2 


6-7 


8-1 


9-4 


3-4 


4-11 


6-3 


7-7 


8-10 




Hem-fir 


SS 


5-2 


8-1 


10-8 


13-6 


13-11 


5-2 


8-1 


10-5 


12-4 


12-4 




Hem-fir 


#1 


4-11 


7-2 


9-1 


11-1 


12-10 


4-7 


6-9 


8-7 


10-6 


12-2 




Hem-fir 


#2 


4-8 


6-9 


8-7 


10-6 


12-2 


4-4 


6-5 


8-1 


9-11 


11-6 


24 


Hem-fir 


#3 


3-7 


5-2 


6-7 


8-1 


9-4 


3-4 


4-11 


6-3 


7-7 


8-10 


Southern pine 


SS 


5-4 


8-5 


11-1 


14-2 


17-2 


5-4 


8-5 


11-1 


14-2 


17-2 




Southern pine 


#1 


5-3 


8-3 


10-5 


12-5 


14-9 


5-3 


7-10 


9-10 


11-8 


13-11 




Southern pine 


#2 


5-0 


7-3 


9-4 


11-1 


13-0 


4-9 


6-10 


8-9 


10-6 


12-4 




Southern pine 


#3 


3-9 


5-7 


7-1 


8-5 


10-0 


3-7 


5-3 


6-9 


7-11 


9-5 




Spruce-pine-fir 


SS 


5-0 


7-11 


10-5 


12-9 


14-9 


5-0 


7-9 


9-10 


12-0 


12-11 




Spruce-pine-fir 


#1 


4-8 


6-11 


8-9 


10-8 


12-4 


4-5 


6-6 


8-3 


10-0 


11-8 




Spruce-pine-fir 


#2 


4-8 


6-11 


8-9 


10-8 


12-4 


4-5 


6-6 


8-3 


10-0 


11-8 




Spruce-pine-fir 


#3 


3-7 


5-2 


6-7 


8-1 


9-4 


3-4 


4-11 


6-3 


7-7 


8-10 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting 

on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic 

multiplied by the factors given below: 



: the outward push of the rafters 
space, the rafter spans shall be 



Mc/H, 


Rafter Span Adjustment Factor 


1/3 


0.67 


1/4 


0.76 


1/5 


0.83 


1/6 


0.90 


1/7.5 or less 


1.00 



where: 

7/^ = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 

H[{ = Height of roof ridge measured vertically above the top of the rafter support walls. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



265 



ROOF-CEILING CONSTRUCTION 



TABLE R802.5.1(9) 
RAFTER/CEILING JOIST HEEL JOINT CONNECTIONS^"'' ''^'a 



RAFTER 
SLOPE 


RAFTER 
SPACING 
(inches) 


GROUND SNOW LOAD (psf) 


30 


50 


70 


Roof span (feet) 


12 


20 


28 


36 


12 20 


28 


36 


12 


20 


28 


36 


Required number of 16d common nails^''' per heel joint splices''''''^'' 




12 


4 


6 


8 


11 


5 


8 


12 


15 


6 


11 


15 


20 


3:12 


16 


5 


8 


11 


14 


6 


11 


15 


20 


8 


14 


20 


26 




24 


7 


11 


16 


21 


9 


16 


23 


30 


12 


21 


30 


39 




12 


3 


5 


6 


8 


4 


6 


9 


11 


5 


8 


12 


15 


4:12 


16 


4 


6 


8 


11 


5 


8 


12 


15 


6 


11 


15 


20 




24 


5 


9 


12 


16 


7 


12 


17 


22 


9 


16 


23 


29 




12 


3 


4 


5 


7 


3 


5 


7 


9 


4 


7 


9 


12 


5:12 


16 


3 


5 


7 


9 


4 


7 


9 


12 


5 


9 


12 


16 




24 


4 


7 


10 


13 


6 


10 


14 


18 


7 


13 


18 


23 




12 


3 


3 


4 


5 


3 


4 


5 


7 


3 


5 


7 


9 


7:12 


16 


3 


4 


5 


6 


3 


5 


7 


9 


4 


6 


9 


11 




24 


3 


5 


7 


9 


4 


7 


10 


13 


5 


9 


13 


17 




12 


3 


3 


3 


4 


3 


3 


4 


5 


3 


4 


5' 


7 


9:12 


16 


3 


3 


4 


5 


3 


4 


5 


7 


3 


5 


7 


9 




24 


3 


4 


6 


7 


3 


6 


8 


10 


4 


7 


10 


13 




12 


3 


3 


3 


3 


3 


■ 3 


3 


4 


3 


3 


4 


5 


12:12 


16 


3 


3 


3 


4 


3 


3 


4 


5 


3 


4 


5 


7 




24 


3 


3 


4 


6 


3 


4 


6 


8 


3 


6 


8 


10 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. 

a. 40d box nails shall be permitted to be substituted for 16d common nails. 

b. Nailing requirements shall be permitted to be reduced 25 percent if nails are clinched. 

c. Heel joint connections are not required when the ridge is supported by a load-bearing vaW, header or ridge beam. 

d. When intermediate support of the rafter is provided by vertical struts or purlins to a loadbearing wall, the tabulated heel joint connection requirements shall be per- 
mitted to be reduced proportionally to the reduction in span. 

e. Equivalent nailing patterns are required for ceiling joist to ceiling joist lap splices. 

f. When rafter ties are substituted for ceiling joists, the heel joint connection requirement shall be taken as the tabulated heel joint connection requirement for 
two-thirds of the actual rafter-slope. 

g. Tabulated heel joint connection requirements assume that ceiling joists or rafter ties are located at the bottom of the attic space. When ceiling joists or rafter ties are 
located higher in the attic, heel joint connection requirements shall be increased by the following factors: 



Wc/«fl 


Heel Joint Connection 
Adjustment Factor 


1/3 


1.5 


1/4 


1.33 


1/5 


1.25 


1/6 


1.2 


1/10 or less 


1.11 



where: 

H(^ = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. 

Hif - Height of roof ridge measured vertically above the top of the rafter support walls. 



266 



2006 INTERNATIONAL RESIDElilTIAL CODE 



ROOF-CEILING CONSTRUCTION 



RAFTER SPAN- 
SEE TABLES R802.5. 1(1) 
THROUGH R802.5.1(8) 




RIDGE BOARD 



PURLIN CONTINUOUS 
BETWEEN SUPPORT, 
BRACES 



TOP PLATE- 



NAIL TO JOIST 



V- 



i^ 



2 IN. X 4 IN. PURLIN 

SUPPORT BRACE 

AT4FT. O.C. 



BEARING 
PARTITIONS 



V- 



CEILING JOIST*- 
SEE TABLES R802.4(1) 
AND R802.4(2) 



N- 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 d^ree = 0.018 rad. 

NOTE: Where ceihng joints run perpendicular to the rafters, rafter ties shall be nailed to each rafter near the top of the ceiling joist. 

FIGURE R802.5.1 
BRACED RAFTER CONSTRUCTION 



R802. 10.2.1 Applicability limits. The provisions of this 
section shall control the design of truss roof framing 
when snow controls for buildings not greater than 60 feet 
(1 8 288 mm) in length perpendicular to the joist, rafter or 
truss span, not greater than 36 feet (10 973 mm) in width 
parallel to the joist span or truss, not greater than two sto- 
ries in height with each story not greater than 10 feet 
(3048 mm) high, and roof slopes not smaller than 3:12 
(25-percent slope) or greater than 12:12 (100-percent 
slope). Truss roof framing constructed in accordance 
with the provisions of this section shall be limited to sites 
subjected to a maximum design wind speed of 1 10 miles 
per hour (49 m/s). Exposure A, B or C, and a maximum 
ground snow load of 70 psf (3352 Pa). Roof snow load is 
to be computed as: 0.7 p^. 

R802.10.3 Bracing. Trusses shall be braced to prevent rota- 
tion and provide lateral stability in accordance with the 
requirements specified in the construction documents for 
the building and on the individual truss design drawings. In 
the absence of specific bracing requirements, trusses shall 
be braced in accordance with the Building Component 
Safety Information (BCSI 1-03) Guide to Good Practice for 
Handling, Installing & Bracing of Metal Plate Connected 
Wood Trusses. 

R802.10.4 Alterations to trusses. Truss members shall not 
be cut, notched, drilled, spliced or otherwise altered in any 



way without the approval of a registered design professional. 
Alterations resulting in the addition of load (e.g., HVAC 
equipment, water heater) that exceeds the design load for the 
truss shall not be permitted without verification that the truss 
is capable of supporting such additional loading. 

R802.10.5 Truss to wall connection. Trusses shall be con- 
nected to wall plates by the use of approved connectors having 
a resistance to uplift of not less than 175 pounds (779 N) and 
shall be installed in accordance with the manufacturer's speci- 
fications. For roof assemblies subject to wind uplift pressures 
of 20 pounds per square foot (960 Pa) or greater, as estabUshed 
in Table R301 .2(2), adjusted for height and exposure per Table 
R301.2(3), see section R802.il. 

R802.il Roof tie-down. 

R802.11.1 Uplift resistance. Roof assembUes which are sub- 
ject to wind uplift pressures of 20 pounds per square foot (960 
Pa) or greater shall have roof rafters or trusses attached to their 
supporting wall assemblies by connections capable of provid- 
ing the resistance required in Table R802. 1 1 . Wind upUft pres- 
sures shall be determined using an effective wind area of 100 
square feet (9.3 m2) and Zone 1 in Table R301.2(2), as 
adjusted for height and exposure per Table R301.2(3). 

A continuous load path shall be designed to transmit the 
uplift forces from the rafter or truss ties to the foundation. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



267 



ROOF-CEILING CONSTRUCTION 



TABLE R802.11 
REQUIRED STRENGTH OF TRUSS OR RAFTER CONNECTIONS TO RESIST WIND UPLIFT FORCES^ '''•='^'' 

(Pounds per connection) 



BASIC WIND SPEED 
(mph) (3-second gust) 


ROOF SPAN (feet) 


OVERHANGS" 
(pounds/foot) 


12 


20 


24 


28 


32 


36 


40 


85 


-72 


-120 


-145 


-169 


-193 


-217 


-241 


-38.55 


90 


-91 


-151 


-181 


-212 


-242 


-272 


-302 


-43.22 


100 


-131 


-218 


-262 


-305 


-349 


-393 


-436 


-53.36 


110 


-175 


-292 


-351 


-409 


-467 


-526 


-584 


-64.56 



For SI: 1 inch = 25.4 mm, 1 foot = 305 mm, 1 mph = 0.447 m/s, 1 pound/foot = 14.5939 N/m, 1 pound = 0.454 kg. 

a. The uphft connection requirements are based on a 30 foot mean roof height located in Exposure B. For Exposures C and D and for'other mean roof heights, multi- 
ply the above loads by the Adjustment Coeflicients in Table R30 1.2(3). 

b. The uplift connection requirements are based on the framing being spaced 24 inches on center. Multiply by 0.67 for framing spaced 16 inches on center and multi- 
ply by 0.5 for framing spaced 12 inches on center 

c. The uplift connection requirements include an allowance for 10 pounds of dead load. 

d. The uplift connection requirements do not account for the effects of overhangs. The magnitude of the above loads shall be increased by adding the overhang loads 
found in the table. The overhang loads are also based on framing spaced 24 inches on center. The overhang loads given shall be multiplied by the overhang projec- 
tion and added to the roof uplift value in the table. 

e. The uplift connection requirements are based on wind loading on end zones as defined in Figure 6-2 of ASCE 7. Connection loads for connections located a dis- 
tance of 20% of the least horizontal dimension of the building from the comer of the building are permitted to be reduced by multiplying the table connection value 
by 0.7 and multiplying the overhang load by 0.8. 

f. For wall-to-wall and wall-to-foundation connections, the capacity of the uplift connector is permitted to be reduced by 100 pounds for each full wall above. (For 
example, if a 600-pound rated connector is used on the roof framing, a 500-pound rated connector is permitted at the nect floor level down). 



SECTION R803 
ROOF SHEATHING 

R803.1 Lumber sheathing. Allowable spans for lumber used as 
roof sheathing shall conform to Table R803.1. Spaced lumber 
sheathing for wood shingle and shake roofing shall conform to 
the requirements of Sections R905.7 and R905.8. Spaced lum- 
ber sheathing is not allowed in Seismic Design Category D2. 

TABLE R803.1 
MINIMUM THICKNESS OF LUMBER ROOF SHEATHING 



RAFTER OR BEAM SPACING 
(inches) 


MINIMUM NET THICKNESS 
(Inches) 


24 


'/, 


48* 


IV^T&G 


60" 


12" 



For SI: 1 inch = 25.4 mm. 

a. Minimum 270 F^, 340,000 E. 

b. Minimum 420 F^, 660,000 E. 

c. Minimum 600 F^, 1,150,000 £. 

R803.2 Wood structural panel sheathing. 

R803.2.1 Identification and grade. Wood structural pan- 
els shall conform to DOC PS 1, DOC PS 2 or, when manu- 
factured in Canada, CSA 0437, and shall be identified by a 
grade mark or certificate of inspection issued by an 
approved agency. Wood structural panels shall comply with 
the grades specified in Table R503.2. 1.1(1). 

R803.2.1.1 Exposure durability. All wood structural 
panels, when designed to be permanently exposed in out- 
door applications, shall be of an exterior exposure dura- 
bility. Wood structural panel roof sheathing exposed to 
the underside may be of interior type bonded with exte- 
rior glue, identified as Exposure 1 . 

R803.2.1.2 Fire-retardant-treated plywood. The allow- 
able unit stresses for fire-retardant-treated plywood, includ- 



ing fastener values, shall be developed from an approved 
method of investigation that considers the effects of antici- 
pated temperature and humidity to which the fire-retar- 
dant-treated plywood will be subjected, the type of 
treatment and redrying process. The fire-retardant- treated 
plywood shall be graded by an approved agency. 

R803.2.2 Allowable spans. The maximum allowable spans 
for wood structural panel roof sheathing shall not exceed the 
values set forth in Table R503.2. 1.1(1), or APA E30. 

R803.2.3 Installation. Wood structural panel used as roof 
sheathing shall be installed with joints staggered or not stag- 
gered in accordance with Table R602.3(l), or APA E30 for 
wood roof framing or with Table R804.3 for steel roof framing. 



SECTION R804 
STEEL ROOF FRAMING 

R804.1 General. Elements shall be straight and free of any 
defects that would significantly affect their stmctural perfor- 
mance. Cold-formed steel roof framing members shall comply 
with the requirements of this section. 

R804.1.1 Applicability limits. The provisions of this sec- 
tion shall control the construction of steel roof framing for 
buildings not greater than 60 feet (18 288 mm) perpendicu- 
lar to the joist, rafter or truss span, not greater than 40 feet 
(12 192 mm) in width parallel to the joist span or truss, not 
greater than two stories in height and roof slopes not smaller 

, than 3 : 1 2 (25 -percent slope) or greater than 1 2 : 1 2 ( 1 00 per- 
cent slope). Steel roof framing constructed in accordance 
with the provisions of this section shall be limited to sites 
subjected to a maximum design wind speed of 1 10 miles per 

. hour (49 m/s). Exposure A, B, or C, and a maximum ground 
snow load of 70 pounds per square foot (3350 Pa). 

R804.1.2 In-line framing. Steel roof framing constructed 
in accordance with Section R804 shall be located directly in 
line with load-bearing studs below with a maximum toler- 



268 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



ROOF-CEILING CONSTRUCTION 



ance of V4 inch (19 mm) between the centerline of the stud 
and the roof joist/rafter. 

R804.1.3 Roof trusses. The design, quality assurance, 
installation and testing of cold-formed steel trusses shall be 
in accordance with the AISI Standard for Cold-formed Steel 
Framing-Truss Design (COFS/Truss). Truss members shall 
not be notched, cut or altered in any manner without an 
approved design. 

R804.2 Structural framing. Load-bearing steel roof framing 
members shall comply with Figure R804.2(l) and with the 
dimensional and minimum thickness requirements specified in 
Tables R804.2(l) and R804.2(2). Tracks shall comply with 
Figure R804.2(2) and shall have a minimum flange width of 
174 inches (32 mm). The maximum inside bend radius for 
load-bearing members shall be the greater of V32 inch (2.4 mm) 
or twice the uncoated steel thickness. Holes in roof framing 
members shall comply with all of the following conditions: 

1. Holes shall conform to Figure R804.2(3); 

2. Holes shall be permitted only along the centerline of the 
web of the framing member; 

3. Holes shall have a center-to-center spacing of not less 
than 24 inches (610 mm); 

4. Holes shall have a width not greater than 0.5 times the 
member depth, or 2V2 inches (64 mm); 

5. Holes shall have a length not exceeding 4V2 inches (114 
mm); and 

6. Holes shall have a minimum distance between the edge 
of the bearing surface and the edge of the hole of not less 
than 10 inches (254 mm). 



Framing members with web holes not conforming to these 
requirements shall be patched in accordance with Section 
R804.3.6 or designed in accordance with accepted engineering 
practices. 

R804.2.1 Material. Load-bearing steel framing members 
shall be cold-formed to shape from structural quaUty sheet 
steel complying with the requirements of one of the following: 

1 . ASTM A 653: Grades 33, 37, 40 and 50 (Class 1 and 3). 

2. ASTM A 792: Grades 33, 37, 40 and 50A. 

3. ASTM A 875: Grades 33, 37, 40 and 50 (Class land 3). 

4. ASTM A 1003: Grades 33, 37, 40 and 50. 

R804.2.2 Identification. Load-bearing steel framing mem- 
bers shall have a legible label, stencil, stamp or embossment 
with the following information as a minimum: 

1. Manufacturer's identification. 

2. Minimum uncoated steel thickness in inches (mm). 

3. Minimum coating designation. 

4. Minimum yield strength, in kips per square inch (ksi) . 

R804.2.3 Corrosion protection. Load-bearing steel fram- 
ing shall have a metallic coating complying with one of the 
following: 

1. A minimum of G 60 in accordance with ASTM A 
653. 

2. A minimum of AZ 50 in accordance with ASTM A 

792. 

3. A minimum of GF 60 in accordance with ASTM A 
875. 



TABLE R804.2(1) 
LOAD-BEARING COLD-FORMED STEEL MEMBER SIZES 



NOMINAL MEMBER SIZE 
MEMBER DESIGNATION" 


WEB DEPTH 
(inches) 


MINIMUM FLANGE WIDTH 
(inches) 


MAXIMUM FLANGE WIDTH 
(inches) 


MINIMUM LIP SIZE 
(inches) 


350S162-t 


3.5 


1.625 


2 


0.5 


550S162-t 


5.5 


1.625 


2 


0.5 


800S162-t 


8 


1.625 


2 


0.5 


1000S162-t 


10 


1.625 


2 


0.5 


1200s 162-t 


12 


1.625 


2 


0.5 



For SI: 1 inch = 25.4 mm. 

a. The member designation is defined by the first number representing the member depth in hundredths of an inch, the letter "s" representing a stud or joist member, the 

second number representing the flange width in hundredths of an inch, and the letter "t" shall be a number representing the minimum base metal thickness in mils [see 

Table R804.2(2)]. 

TABLE R804.2(2) 
MINIMUM THICKNESS OF COLD-FORMED STEEL ROOF FRAMING MEMBERS 



DESIGNATION (mils) 


MINIMUM UNCOATED THICKNESS (inches) 


REFERENCED GAGE NUMBER 


33 


0.033 


20 


43 


0.043 


18 


54 


0.054 


16 


68 


0.068 


14 



For SI; 1 inch = 25.4 mm, 1 mil = 0.0254 mm. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



269 



ROOF-CEILING CONSTRUCTION 



FLANGE 




FLANGE 



DEPTH OF WEB 
(OUTSIDE TO 
OUTSIDE) 




SIZE OF TRACK 
NSIDE TO INSIDE) 



WEB 



FIGURE R804.2(1) 
C-SECTION 



FIGURE R804.2(2) 
TRACK SECTION 



C.L 







i 
< 


~ 24 


- - ■■" ~ -'"I ' 


! 
j 






_^.,-.--^]"'---.^ 


/ 






^■'^i^.^ 




' 


1 


4V " 




'MAX. 




..:"■-..'.-' ^.- : 


2'4"IV1AX. — 






1 



C.L. 



.-.-XHz::^ 



^ 



_> 



4V,' 



MAX. 



10" MIN. 



Z — nc 



CENTERLINE OF WEB 



BEARING CONDITION 



m 



For SI: 1 inch = 25.4 mm. 



FIGURE R804.2(3) 
WEB HOLES 



R804.2.4 Fastening requirements. Screws for steel-to- 
steel connections shall be installed with a minimum edge 
distance and center-to-center spacing of Vj inch (13 mm), 
shall be self -drilling tapping, and shall conform to S AE J78. 
Structural sheathing shall be attached to roof rafters with 
minimum No. 8 self-drilling tapping screws that conform to 
SAE J78. Screws for attaching structural sheathing to steel 
roof framing shall have a minimum head diameter of 0.292 
inch (7.4 mm) with countersunk heads and shall be installed 
with a minimum edge distance of Vg inch (10 mm). Gypsum 
board ceilings shall be attached to steel joists with minimum 
No. 6 screws conforming to ASTM C 954 and shall be 
installed in accordance with Section R805. For all connec- 
tions, screws shall extend through the steel a minimum of 
three exposed threads. All self-drilling tapping screws con- 
forming to SAE J78 shall have a minimum Type II coating 
in accordance with ASTM B 633. 



Where No. 8 screws are specified in a steel-to- steel con- 
nection, reduction of the required number of screws in the 
connection is permitted in accordance with the reduction 
factors in Table R804.2.4 when larger screws are used or 
when one of the sheets of steel being connected is thicker 
that 33 mils (0.84 mm). When applying the reduction factor, 
the resulting number of screws shall be rounded up. 

TABLE R804.2.4 
SCREW SUBSTITUTION FACTOR 



SCREW SIZE 


THINNEST CONNECTED STEEL SHEET (mils) 


33 


43 


#8 


1.0 


0.67 


#10 


0.93 


0.62 


: #12 


0.86 


0.56 



For SI: 1 mil = 0.0254 mm. 



270 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



R804.3 Roof construction. Steel roof systems constructed in 
accordance with the provisions of this section shall consist of 
both ceiling joists and rafters in accordance with Figure R804.3 
and fastened in accordance with Table R804.3. 

R804.3.1 Allowable ceiling joist spans. The clear span of 
cold-formed steel ceiling joists shall not exceed the limits set 
forth in Tables R804.3.1(l) through R804.3.1(8). Ceiling 
joists shall have a minimum bearing length of 1.5 inches (38 
mm) and shall be connected to rafters (heel joint) in accor- 
dance with Figure R804.3.1(l) and Table R804.3.1. When 



continuous joists are framed across interior bearing supports, 
the interior bearing supports shall be located within 24 inches 
(610 mm) of midspan of the ceiling joist, and the individual 
spans shall not exceed the apphcable spans in Tables 
R804.3.1(2), R804.3.1(4), R804.3.1(6), R804.3.1(8). Where 
required in Tables R804.3.1(l) through R804.3.1(8), bearing 
stiffeners shall be installed at each bearing location in accor- 
dance with Section R804.3.8 and Figure R804.3.8. When the 
attic is to be used as an occupied space, the ceiling joists shall 
be designed in accordance with Section R505. 



TABLE R804.3 
ROOF FRAMING FASTENING SCHEDULE^" 



DESCRIPTION OF BUILDING ELEMENTS 


NUMBER AND SIZE OF FASTENERS 


SPACING OF FASTENERS 


Ceiling joist to top track of load-bearing wall 


2 No. 10 screws 


Each joist 


Roof sheathing (oriented strand board or plywood) 
to rafters 


No. 8 screws 


6" o.c. on edges and 12" o.c. at interior supports. 
6" o.c. at gable end truss 


Truss to bearing walP 


2 No. 10 screws 


Each truss 


Gable end truss to endwall top track 


No. 10 screws 


12" o.c. 


Rafter to ceiling joist 


Minimum No. 10 screws, per Table 
R804.3.1 


Evenly spaced, not less than V2" from all edges. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa, 1 mil = 0.0254 mm. 

a. Screws shall be applied through the flanges of the truss or ceiling joist or a 54 mil clip angle shall be used with two No. 1 screws in each leg. See Section R804.4 for 
additional requirements to resist uplift forces. 

b. Spacing of fasteners on roof sheathing panel edges applies to panel edges supported by framing members and at all roof plane perimeters. Blocking of roof sheath- 
ing panel edges perpendicular to the framing members shall not be required except at the intersection of adjacent roof planes. Roof perimeter shall be supported by 
framing members or cold-formed blocking of the same depth and gage as the floor members. 



C-SECTION OR TRACK INSTALLED 
AT 4 FT O.C. TO RAFTER SUPPORT 
BRACE 



RAFTER BOTTOM FLANGE BRACING 
(FLAT STRAP, 3508162-33 MIL 
C-SECTION, OR TRACK SECTION) 



RAFTER SPAN 
WITH RAFTER 



SUPPORT BRACE 



V2 IN. GYPSUM 
BOARD 



LOAD-BEARING ' 
WALL 



I I 

I I 
II 
I I 
I I 
I I 
-JJ- 



RAFTER SPAN WITHOUT RAFTER 
SUPPORT BRACE 



RAFTER BOTTOM FLANGE BRACING 
(FLAT STRAP, 3508162-33 MIL 
C-SECTION, OR TRACK SECTION) 




WHEN INSTALLED, RAFTER 
SUPPORT BRACE SHALL BE A 
MINIMUM OF 3508162-33 MIL 
C-SECTION, CONNECTED TO EACH 
CEILING JOIST AND RAFTER WITH 
4 SCREWS AT EACH END (COPE 
FLj(\NGES OF BRACE AT CEILING 
JOIST CONNECTION OR USE 
GUSSET PLATE) 



I I 
I I 
I I 

-U- 



LOAD-BEARING WALL 
SHALL BE INSTALLED WHEN 
RAFTER BRACE IS USED 



M- 



CANTILEVER 
2 FT MAX. 



■ LOAD-BEARING 
WALL 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm. 



FIGURE R804.3 
STEEL ROOF CONSTRUCTiOM 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



271 



ROOF-CEILING CONSTRUCTION 



TABLE R804.3.1(1) 

CEILING JOIST SPANS 

SINGLE SPANS WITH BEARING STIFFENERS 

10 lb per sq ft LIVE LOAD (NO ATTIC STORAGE)^ " = 33 ksi STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist Spacing (inches) 


16 


24 


16 


24 


16 


24 


350S 162-33 


9'-5" 


8'-6" 


12'-2" 


10'-4" 


12'-2" 


10'-7" 


350S 162-43 


10'-3" 


9'-2" 


12'- 10" 


11 '-2" 


12'-10" 


ll'-2" 


350S 162-54 


ll'-l" 


9'- 11" 


13'-9" 


12'-0" 


13'-9" 


12'-0" 


350S 162-68 


12'- 1" 


10'-9" 


14'-8" 


12'-10" 


14'-8" 


12'-10" 


350S 162-97 


14'-4" 


12'-7" 


16'-4" 


■ 14'-3" 


16'-4" 


14'-3" 


550S 162-33 


10'-7" 


9'-6" 


14'- 10" 


12'-10" 


15'-11" 


13'-4" 


550S 162-43 


11 '-8" 


10'-6" 


16'-4" 


14'-3" 


17'-10" 


15'-3" 


550S 162-54 


12'-6" 


11 '-2" 


17'-7" 


15'-7" 


19'-5" 


16'- 10" 


550S 162-68 


13'-6" 


12'-1" 


19'-2" 


17'-1" 


21'-0" 


18'-4" 


550S 162-97 


15'-9" 


13'- 11" 


21 '-8" 


19'-3" 


23'-5" 


20'-5" 


800S 162-33 


12'-2" 


lO'-ll" 


17'-8" 


15'-10" 


19'-10" 


17'-1" 


800S 162-43 


13'-0" 


ll'-9" 


18'- 10" 


17'-0" 


21'-6" 


19'-1" 


800S162-54 


13'-10" 


12'-5" 


20'-0" 


18'-0" 


22'-9" 


20'-4" 


800S 162-68 


14'- 11" 


13'-4" 


21'-3"' 


19'-1" 


24'- 1" 


21 '-8" 


800S 162-97 


17'-1" 


15'-2" 


23'- 10" 


21 '-3" 


26'-7" 


23'- 10" 


lOOOS 162-43 


13'- 11" 


12'-6" 


20'-2" 


18'-3" 


23'-l" 


20'-9" 


1000S162-54 


14'-9" 


13'-3" 


21 '-4" 


19'-3" 


24'-4" 


22'-0" 


lOOOS 162-68 


15'-10" 


14'-2" 


22'-8" 


20'-5" 


25'-9" 


23'-2" 


lOOOS 162-97 


18'-0" 


16'-0" 


25'-3" 


22'-7" 


28'-3" 


25'-4" 


1200S 162-43 


14'-8" 


13'-3" 


21'-4" 


19'-3" 


24'-5" 


21 '-8" 


1200S 162-54 


15'-7" 


14'-0" 


22'-6" 


20'-4" 


25'-9" 


23'-2" 


1200S 162-68 


16'-8" 


14'-11" 


23'- 11" 


21'-6" 


27'-2" 


24'-6" 


lOOOS 162-97 


18'-9" 


16'-9" 


26'-6" 


23'-8" 


29'-9" 


26'-9" 



For Sr. 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 

a. Deflection criterion: L/240 for total loads. 

b. Ceiling dead load = 5 psf. 

c. Bearing stiffeners are required at all bearing points and concentrated load locations. 



272 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



ROOF-CEILING CONSTRUCTION 



TABLER804.3.1(2) 

CEILING JOIST SPANS 

TWO EQUAL SPANS WITH BEARING STIFFENERS 

10 lb per sq ft LIVE LOAD (NO ATTIC STORAGE)" "•= 33 ksi STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist Spacing (inches) 


16 


24 


16 


24 


16 


24 


350S 162-33 


12'-11" 


10'- 11" 


13'-5" 


lO'-ll" 


13'-5" 


10'- 11" 


350S 162-43 


14'-2" 


12'-8" 


15'-10" 


12'-11" 


15'-10" 


12'-11" 


350S 162-54 


15'-6" 


13'-10" 


17'-1" 


14'-6" 


17'-9" 


14'-6" 


350S 162-68 


17'-3" 


15'-3" 


18'-6" 


16'-1" 


19'-8" 


16'- 1" 


350S 162-97 


20'-10" 


18'-4" 


21 '-5" 


18'- 10" 


21'-11" 


18'-10" 


550S 162-33 


14'-4" 


12'-11" 


16'-7" 


14'-1" 


17'-3" 


14'-1" 


550S 162-43 


16'-0" 


14'- 1" 


17'-11" 


16'- 1" 


20'-7" 


16'-10" 


550S 162-54 


17'-4" 


15'-6" 


19'-5" 


17'-6" 


23'-2" 


19'-0" 


550S162-68 


19'-1" 


16'-11" 


20'- 10" 


18'-8" 


25'-2" 


21 '-5" 


550S 162-97 


22'-8" 


19'-9" 


23'-6" 


20'- 11" 


27'-ll" 


25'- 1" 


800S162-33 


16'-5" 


14'- 10" 


19'-2" 


17'-3" 


23'- 1" 


18'-3" 


800S 162-43 


17'-9" 


15'-11" 


20'-6" 


18'-5" 


25'-0" 


22'-6" 


800S 162-54 


19'-1" 


17'-1" 


21'-8" 


19'-6" 


26'-4" 


23'-9" 


800S 162-68 


20'-9" 


18'-6" 


23'- 1" 


20'-9" 


28'-0" 


25'-2" 


800S 162-97 


24'-5" 


21'-6" 


26'-0" 


23'-2" 


31'-1" 


27'-9" 


lOOOS 162-43 


18'-11" 


17'-0" 


21'-11" 


19'-9" 


26'-8" 


24'- 1" 


lOOOS 162-54 


20'-3" 


18'-2" 


23'-2" 


20'- 10" 


28'-2" 


25'-5" 


lOOOS 162-68 


21'-11" 


19'-7" 


24'-7" 


22'-2" 


29'- 10" 


26'-ll" 


lOOOS 162-97 


25'-7" 


22'-7" 


27'-6" 


24'-6" 


33'-0" 


29'-7" 


1200S 162-43 


19'- 11" 


17'-11" 


23'- 1" 


20'- 10" 


28'-3" 


25'-6" 


1200S 162-54 


21'-3" 


19'-1" 


24'-5" 


22'-0" 


29'-9" 


26'- 10" 


1200S 162-68 


23'-0" 


20'-7" 


25'- 11" 


23'-4" 


31'-6" 


28'-4" 


1000S162-97 


26'-7" 


23'-6" 


28'-9" 


25'- 10" 


34'-8" 


31'-1" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 

a. Deflection criterion: L/240 for total loads. 

b. Ceiling dead load = 5 psf. 

c. Bearing stiffeners are required at all bearing points and concentrated load locations. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



273 



ROOF-CEILING CONSTRUCTION 



TABLER804.3.1(3) 

CEILING JOIST SPANS 

SINGLE SPANS WITH BEARING STIFFENERS 

20 lb per sq ft LIVE LOAD (LIMITED ATTIC STORAGE)^' ''■^ 33 ksi STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist S| 


lacing (inches) 


16 


24 


16 


24 


16 


24 


350S162-33 


8'-2" 


7'-2" 


9'-9" 


8'-l" 


9'- 11" 


8'-l" 


350S 162-43 


8'- 10" 


7'- 10" 


11 '-0" 


9'-5" 


ll'-O" 


9'-7" 


350S 162-54 


9'-6" 


8'-6" 


11 '-9" 


10'-3" 


11 '-9" 


10'-3" 


350S 162-68 


10'-4" 


9'-2" 


12'-7" 


ll'-O" 


12'-7" 


ll'-O" 


350S 162-97 


12'-1" 


10'-8" 


14'-0" 


12'-0" 


14'-0" 


12'-0" 


550S 162-33 


9'-2" 


8'-3" 


12'-2" 


10'-2" 


12'-6" 


10'-5" 


550S 162-43 


10'- 1" 


9'-l" 


13'-7" 


ll'-7" 


14'-5" 


12'-2" 


550S 162-54 


10'-9" 


9'-8" 


14'- 10" 


12'- 10" 


15'- 11" 


13'-6" 


550S 162-68 


ll'-7" 


10'-4" 


16'-4" 


14'-0" 


17'-5" 


14'-11" 


550S 162-97 


13'-4" 


U'-IO" 


18'-5" 


16'-2" 


20'-l" 


17'-1" 


800S 162-33 


10'-7" 


9'-6" 


15'-1" 


13'-0" 


16'-2" 


13'-7" 


800S 162-43 


1 r-4" 


10'-2" 


16'-5" 


14'-6" 


18'-2" 


15'-9" 


800S 162-54 


12'-0" 


10'-9" 


17'-4" 


15'-6" 


19'-6" 


17'-0" 


800S 162-68 


12'- 10" 


ll'-6" 


18'-5" 


16'-6" 


20'- 10" 


18'-3" 


800S 162-97 


14'-7" 


12'- 11" 


20'-5" 


18'-3" 


22'- 11" 


20'-5" 


lOOOS 162-43 


12'- 1" 


lO'-ll" 


17'-7" 


15'-10" 


19'- 11" 


17'-3" 


lOOOS 162-54 


12'-10" 


11 '-6" 


18'-7" 


16'-9" 


21 '-2" 


18'- 10" 


lOOOS 162-68 


13'-8" 


12'-3" 


19'-8" 


17'-8" 


22'-4" 


20'- 1" 


1000S162-97 


15'-4" 


13'-8" 


21 '-8" 


19'-5" 


24'-5" 


21'-11" 


1200S162-43 


12'-9" 


ll'-6" 


18'-7" 


16'-6" 


20'-9" 


18'-2" 


1200S 162-54 


13'-6" 


12'-2" 


19'-7" 


17'-8" 


22'-5" 


20'-2" 


1200S162-68 


14'-4" 


12'- 11" 


20'-9" 


18'-8" 


23'-7" 


21 '-3" 


lOOOS 162-97 


16'-1" 


14'-4" 


22'- 10" 


20'-6" 


25'-9" 


23'-2" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 

a. Deflection criterion: L/240 for total loads. 

b. Ceiling dead load = 5 psf. 

c. Bearing stiffeners are required at all bearing points and concentrated load locations. 



274 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



ROOF-CEILING CONSTRUCTION 



TABLER804.3.1(4) 

CEILING JOIST SPANS 

TWO EQUAL SPANS WITH BEARING STIFFENERS 

20 lb per sq ft LIVE LOAD (LIMITED ATTIC STORAGE)^ ""= 33 ksi STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist Spacing (inches) 


16 


24 


16 


24 


16 


24 


350S 162-33 


10'-2" 


8'-4" 


10'-2" 


8'-4" 


10'-2" 


8'-4" 


350S 162-43 


12'-1" 


9'- 10" 


12'-1" 


9'- 10" 


12'-1" 


9'- 10" 


350S 162-54 


13'-3" 


11 '-0" 


13'-6" 


ll'-O" 


13'-6" 


ll'-O" 


350S 162-68 


14'-7" 


12'-3" 


15'-0" 


12'-3" 


15'-0" 


12'-3" 


350S 162-97 


17'-6" 


14'-3" 


17'-6" 


14'-3" 


17'-6" 


14'-3" 


550S 162-33 


12'-5" 


10'-9" 


13'-2" 


10'-9" 


13'-2" 


10'-9" 


550S 162-43 


13'-7" 


12'- 1" 


15'-6" 


12'-9" 


15'-8" 


12'-9" 


550S 162-54 


14'-11" 


13'-4" 


16'- 10" 


14'-5" 


17'-9" 


14'-5" 


550S162-68 


16'-3" 


14'-5" 


18'-0" 


16'-1" 


20'-0" 


16'-4" 


550S 162-97 


19'-1" 


16'-10" 


20'-3" 


IB'-O" 


23'-10" 


19'-5" 


BOOS 162-33 


14'-3" 


12'-4" 


16'-7" 


12'-4" 


16'-7" 


12'-4" 


BOOS 162-43 


15'-4" 


13'- 10" 


17'-9" 


16'-0" 


21 '-8" 


17'-9" 


BOOS 162-54 


16'-5" 


14'-9" 


18'- 10" 


16'-11" 


22'- 11" 


20'-6" 


BOOS 162-68 


17'-9" 


15'-11" 


20'-0" 


18'-0" 


24'-3" 


21'- 10" 


800S 162-97 


20'-8" 


18'-3" 


22'-3" 


19'-11" 


26'-9" 


24'-0" 


lOOOS 162-43 


16'-5" 


14'-9" 


19'-0" 


17'-2" 


23'-3" 


18'-11" 


lOOOS 162-54 


ir-6" 


15'-8" 


20'- 1" 


IB'-l" 


24'-6" 


22'- 1" 


lOOOS 162-68 


18'-10" 


16'- 10" 


21'-4" 


19'-2" 


25'- 11" 


23'-4" 


lOOOS 162-97 


21'-B" 


19'-3" 


23'-7" 


21'-2" 


28'-5" 


25'-6" 


1200S 162-43 


17'-3" 


15'-7" 


20'-l" 


18'-2" 


24'-6" 


18'-3" 


1200S 162-54 


18'-5" 


16'-6" 


21'-3" 


19'-2" 


25'-ll" 


23'-5" 


1200S 162-68 


19'-9" 


17'-8" 


22'-6" 


20'-3" 


27'-4" 


24'-B" 


10008162-97 


22'-7" 


20'- 1" 


24'- 10" 


22'-3" 


29'- 11" 


26'- 11" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 

a. Deflection criterion: Zy24G for total loads. 

b. Ceiling dead load = 5 psf. 

c. Bearing stiffeners are required at all bearing points and concentrated load locations. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



275 



ROOF-CEILING CONSTRUCTION 



TABLER804.3.1(5) 

CEILING JOIST SPANS 

SINGLE SPANS WITHOUT BEARING STIFFENERS 

10 lb per sq ft LIVE LOAD (NO ATTIC STORAGE)^ "33 ksi STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist Spacing (inches) 


16 


24 


16 


24 


16 


24 


350S 162-33 


9'-5" 


8'-6" 


12'-2" 


10'-4" 


12'-2" 


10'-7" 


350S 162-43 


10'-3" 


9'- 12" 


13'-2" 


ll'-6" 


13'-2" 


ll'-6" 


350S 162-54 


U'-l" 


9'- 11" 


13'-9" 


12'-0" 


13'-9" 


12'-0" 


350S 162-68 


12'-1" 


10'-9" 


14'-8" 


12'- 10" 


14'-8" 


12'-10" 


350S 162-97 


14'-4" 


12'-7" 


16'- 10" 


14'-3" 


16'-4" 


14'-3" 


550S 162-33 


10'-7" 


9'-6" 


14'- 10" 


12'-10" 


15'-11" 


13'-4" 


550S 162-43 


11 '-8" 


10'-6" 


16'-4" 


14'-3" 


17'-10" 


15'-3" 


550S162-54 


12'-6" 


ll'-2" 


17'-7" 


15'-7" 


19'-5" 


16'- 10" 


550S 162-68 


13'-6" 


12'- 1" 


19'-2" 


17'-0" 


21'-0" 


18'-4" 


550S162-97 


15'-9" 


13'- 11" 


21'-8" 


19'-3" 


23'-5" 


20'-5" 


800S 162-33 




















800S 162-43 


13'-0" 


ll'-9" 


18'- 10" 


17'-0" 


21 '-6" 


19'-0" 


800S 162-54 


13'-10" 


12'-5" 


20'-0" 


18'-0" 


22'-9" 


20'-4" 


800S 162-68 


14'-11" 


13'-4" 


21'-3" 


19'-1" 


24'- 1" 


21 '-8" 


800S 162-97 


17'-1" 


15'-2" 


23'- 10" 


21 '-3" 


26'-7" 


23'- 10" 


lOOOS 162-43 





— 








— 





1000S162-54 


14'-9" 


13'-3" 


21'-4" 


19'-3" 


24'-4" 


22'-0" 


1000S162-68 


15'-10" 


14'-2" 


22'-8" 


20'-5" 


25'-9" 


23'-2" 


lOOOS 162-97 


18'-0" 


16'-0" 


25'-3" 


22'-7" 


28'-3" 


25'-4" 


1200S 162-43 





— 














1200S 162-54 




















1200S 162-68 


16'-8" 


14'-11" 


23'-ll" 


21'-6" 


27'-2" 


24'-6" 


lOOOS 162-97 


18'-9" 


16'-9" 


26'-6" 


23'-8" 


29'-9" 


26'-9" 



For SI: 1 inch = 25.4 mm, 1 

a. Deflection criterion: L/240 

b. Ceiling dead load = 5 psf . 



foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 
for total loads. 



276 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



TABLE R804.3.1(6) 

CEILING JOIST SPANS 

TWO EQUAL SPANS WITHOUT BEARING STIFFENERS 

10 lb per sq ft LIVE LOAD (NO ATTIC STORAGE)^" 33 ksl STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist Spacing (inches) 


16 


24 


16 


24 


16 


24 


350S 162-33 


ll'-9" 


8'- 11" 


11 '-9" 


8'- 11" 


ll'-9" 


8'- 11" 


350S162-43 


14'-2" 


ll'-7" 


14'- 11" 


ll'-7" 


14'- 11" 


ll'-7" 


350S 162-54 


15'-6" 


13'-10" 


17'- 1" 


13'-10" 


17'-7" 


13'-10" 


350S 162-68 


17'-3" 


15'-3" 


18'-6" 


16'-1" 


19'-8" 


16'-1" 


350S 162-97 


20'- 10" 


18'-4" 


21 '-5" 


18'-9" 


21'-11" 


18'-9" 


550S162-33 


13'-4" 


9'-ll" 


13'-4" 


9'-ll" 


13'-4" 


9'- 11" 


550S 162-43 


16'-0" 


13'-6" 


17'-9" 


13'-6" 


17'-9" 


13'-6" 


550S 162-54 


17'-4" 


15'-6" 


19'-5" 


16'- 10" 


21 '-9" 


16'- 10" 


550S 162-68 


19'-1" 


16'-11" 


20'- 10" 


18'-8" 


24'-ll" 


20'-6" 


550S 162-97 


22'-8" 


20'-0" 


23'-9" 


21'-1" 


28'-2" 


25'- 1" 


800S 162-33 





— 














800S 162-43 


17'-9" 


15'-7" 


20'-6" 


15'-7" 


21'-0" 


15'-7" 


800S 162-54 


19'-1" 


17'-1" 


21'-8" 


19'-6" 


26'-4" 


23'- 10" 


800S 162-68 


20'-9" 


18'-6" 


23'-l" 


20'-9" 


28'-0" 


25'-2" 


800S 162-97 


24'-5" 


21 '-6" 


26'-0" 


23'-2" 


31'-1" 


27'-9" 


lOOOS 162-43 




















lOOOS 162-54 


20'-3" 


18'-2" 


23'-2" 


20'-10" 


28'-2" 


21 '-2" 


lOOOS 162-68 


21'-11" 


19'-7" 


24'-7" 


22'-2" 


29'-10" 


26'- 11" 


lOOOS 162-97 


25'-7" 


22'-7" 


27'-6" 


24'-6" 


33'-0" 


29'-7" 


1200S162-43 





— 













1200S162-54 





— 














1200S 162-68 


23'-0" 


20'-7" 


25'- 11" 


23'-4" 


31'-6" 


28'-4" 


lOOOS 162-97 


26'-7" 


23'-6" 


28'-9" 


25'-10" 


34'-8" 


31'-1" 



For SI: 1 inch = 25.4 

a. Deflection criterion: 

b. Ceiling dead load = 



mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 
L/240 for total loads. 
5 psf. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



277 



ROOF-CEILING CONSTRUCTION 



TABLE R804.3.1(7) 

CEILING JOIST SPANS 

SINGLE SPANS WITHOUT BEARING STIFFENERS 

20 lb per sq ft LIVE LOAD (LIMITED ATTIC STORAGE)^ "33 ksl STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist S| 


3acing (inches) 


16 


24 


16 


24 


16 


24 


350S162-33 


8'-2" 


6'-10" 


9'-9" 


6'-10" 


9'- 11" 


6'- 10" 


350S 162-43 


8'- 10" 


7'- 10" 


ll'-O" 


9'-5" 


ll'-O" 


9'-7" 


350S 162-54 


9'-6" 


8'-6" 


ll'-9" 


10'-3" 


ll'-9" 


10'-3" 


350S 162-68 


10'-4" 


9'-2" 


12'-7" 


ll'-O" 


12'-7" 


ll'-O" 


350S 162-97 


12'-10" 


10'-8" 


13'-9" 


12'-0" 


13'-9" 


12'-0" 


550S 162-33 


9'-2" 


8'-3" 


12'-2" 


8'-5" 


12'-6" 


8'-5" 


550S 162-43 


lO'-l" 


9'-l" 


13'-7" 


11 '-8" 


14'-5" 


12'-2" 


550S 162-54 


10'-9" 


9'-8" 


14'-10" 


12'- 10" 


15'-11" 


13'-6" 


550S 162-68 


ir-7" 


10'-4" 


16'-4" 


14'-0" 


17'-5" 


14'-11" 


550S 162-97 


13'-4" 


ll'-lO" 


18'-5" 


16'-2" 


20'- 1" 


17'-4" 


800S 162-33 




















800S 162-43 


ll'-4" 


10'- 1" 


16'-5" 


13'-6" 


18'-1" 


13'-6" 


800S162-54 


20'-0" 


10'-9" 


17'-4" 


15'-6" 


19'-6" 


27'-0" 


800S 162-68 


12'- 10" 


ll'-6" 


18'-5" 


16'-6" 


20'- 10" 


18'-3" 


800S 162-97 


14'-7" 


12'-11" 


20'-5" 


18'-3" 


22'- 11" 


20'-5" 


1000S162-43 








— 


— 


— 


— 


1000S162-54 


12'-10" 


11 '-6" 


18'-7" 


16'-9" 


21'-2" 


15'-5" 


lOOOS 162-68 


13'-8" 


12'-3" 


19'-8" 


17'-8" 


22'-4" 


20'- 1" 


lOOOS 162-97 


15'-4" 


13'-8" 


21 '-8" 


19'-5" 


24'-5" 


21'-11" 


1200S 162-43 














— 


— 


1200S 162-54 














— 


— 


1200S 162-68 


14'-4" 


12'- 11" 


20'-9" 


18'-8" 


23'-7" 


21 '-3" 


lOOOS 162-97 


16'-1" 


14'-4" 


22'- 10" 


20'-6" 


25'-9" 


23'-2" 



For SI: 1 inch = 25.4 

a. Deflection criterion: 

b. Ceiling dead load - 



mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 
L/240 for total loads. 
5 psf. 



278 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



ROOF-CEILING CONSTRUCTION 



TABLE R804.3.1(8) 

CEILING JOIST SPANS 

TWO EQUAL SPANS WITHOUT BEARING STIFFENERS 

20 lb per sq ft LIVE LOAD (LIMITED ATTIC STORAGE)^'' 33 ksi STEEL 



MEMBER 
DESIGNATION 


ALLOWABLE SPAN (feet-inches) 


Lateral Support of Top (Compression) Flange 


Unbraced 


Mid-Span Bracing 


Third-Point Bracing 


Ceiling Joist Spacing (inclies) 


16 


24 


16 


24 


16 


24 


350S162-33 


8'-l" 


6'-l" 


8'-l" 


6'-l" 


8'-l" 


6'-l" 


350S 162-43 


10'-7" 


8'-l" 


10'-7" 


8'-l" 


10'-7" 


8'-l" 


350S 162-54 


12'-8" 


9'-10" 


12'-8" 


9'- 10" 


12'-8" 


9'- 10" 


350S 162-68 


14'-7" 


11'- 10" 


14'- 11" 


ll'-lO" 


14'- 11" 


11'- 10" 


350S 162-97 


17'-6" 


14'-3" 


17'-6" 


14'-3" 


17'-6" 


14'-3" 


550S 162-33 


8'- 11" 


6'-8" 


8'- 11" 


6'-8" 


8'- 11" 


6'-8" 


550S 162-43 


12'-3" 


9'-2" 


12'-3" 


9'-2" 


12'-3" 


9'-2" 


550S 162-54 


14'- 11" 


ll'-8" 


15'-4" 


11 '-8" 


15'-4" 


ll'-8" 


550S162-68 


16'-3" 


14'-5" 


18'-0" 


15'-8" 


18'-10" 


14'-7" 


550S162-97 


19'-1" 


16'- 10" 


20'-3" 


18'-0" 


23'-9" 


19'-5" 


800S162-33 




















800S 162-43 


13'-11" 


9'- 10" J 


13'-11" 


9'- 10" 


13'- 11" 


9'- 10" 


800S 162-54 


16'-5" 


13'-9" 


18'-8" 


13'-9" 


18'-8" 


13'-9" 


800S 162-68 


17'-9" 


15'-11" 


20'-0" 


18'-0" 


24'- 1" 


18'-3" 


800S 162-97 


20'-8" 


18'-3" 


22'-3" 


19'-11" 


26'-9" 


24'-0" 


lOOOS 162-43 




















lOOOS 162-54 


17'-6" 


13'-11" 


19'-1" 


13'-11" 


19'-1" 


13'-11" 


1000S162-68 


18'- 10" 


16'-10" 


21'-4" 


19'-2" 


25'- 11" 


19'-7" 


lOOOS 162-97 


21 '-8" 


19'-3" 


23'-7" 


21 '-2" 


28'-5" 


25'-6" 


1200S162-43 








__ 











1200S162-54 





— 














1200S 162-68 


19'-9" 


17'-8" 


22'-6" 


19'-8" 


26'-8" 


19'-8" 


1000S162-97 


22'-7" 


20'- 1" 


24'- 10" 


22'-3" 


29'-ll" 


26'- 11" 



For SI: 1 inch = 25.4 mm, 1 

a. Deflection criterion: 17240 

b. Ceiling dead load = 5 psf. 



foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. 
for total loads. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



279 



ROOF-CEILING CONSTRUCTION 



RAFTER 



CEILING JOIST 



HEEL JOINT CONNECTION WITH 
SCREWS (AS REQUIRED) 




TRACK 



LOAD- BEARING STUD 



ROOF TO WALL CONNECTION 
WITH TWO SCREWS THROUGH 
CEILING JOIST FLANGE, 54 MIL 
(Ml N.) ANGLE 



For SI: 1 mil = 0.0254 mm. 



FIGURE R804.3.1(1) 
JOIST TO RAFTER CONNECTION 



TABLE R804.3.1 
NUMBER OF SCREWS REQUIRED FOR CEILING JOIST TO RAFTER CONNECTION^ 



ROOF 
SLOPE 


NUMBER OF SCREWS 


Building width (feet) 


24 


28 


32 


36 


40 


Ground snow load (psf) 


20 


30 


50 


70 


20 


r 

30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


20 


30 


50 


70 


3/12 


5 


6 


9 


11 


5 


7 


10 


13 


6 


8 


11 


15 


7 


8 


13 


17 


8 


9 


14 


19 


4/12 


4 


5 


V 


9 


4 


5 


8 


10 


5 


6 


9 


12 


5 


7 


10 


13 


6 


7 


11 


14 


5/12 


3 


4 


6 


7 


4 


4 


6 


8 


4 


5 


7 


10 


5 


5 


8 


11 


5 


6 


9 


12 


6/12 


3 


3 


5 


6 


3 


4 


6 


7 


4 


4 


6 


8 


4 


5 


7 


9 


4 


5 


8 


10 


7/12 


3 


3 


4 


6 


3 


3 


5 


7 


3 


4 


6 


7 


4 


4 


6 


8 


4 


5 


7 


9 


8/12 


2 


3 


4 


5 


3 


3 


5 


6 


3 


4 


5 


7 


3 


4 


6 


8 


4 


4 


6 


8 


9/12 


2 


3 


4 


5 


3 


3 


4 


6 


3 


3 


5 


6 


3 


4 


5 


7 


3 


4 


6 


8 


10/12 


2 


2 


4 


5 


2 


3 


4 


5 


3 


3 


5 


6 


3 


3 


5 


7 


3 


4 


6 


7 


11/12 


2 


2 


3 


4 


2 


3 


4 


5 


3 


3 


4 


6 


3 


3 


5 


6 


3 


4 


5 


7 


12/12 


2 


2 


3 


4 


2 


3 


4 


5 


2 


3 


4 


5 


3 


3 


5 


6 


3 


4 


5 


7 



For SI: 1 inch = 25.4 mm, 
a. Screws shall be No. 10. 



1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kl^. 



280 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



R804.3.2 Ceiling joist bracing. The bottom flanges of steel 
ceiling joists shall be laterally braced in accordance with Sec- 
tion R702. The top flanges of steel ceiling joists shall be later- 
ally braced with a minimum of 33 mil (0.84 mm) C-section, 
33 mil (0.84 mm) track section or 1 V2 inch by 33 mil (38 mm 
by 0.84 mm) continuous steel strapping as required in Tables 
R804.3.1(l) through R804.3.1(8). Lateral bracing shall be 
installed in accordance with Figure R804.3. C-section, tracks 
or straps shall be fastened to the top flange at each joist with at 
least one No. 8 screw and shall be fastened to blocking with at 
least two No. 8 screws. Blocking or bridging (X-bracing) 
shall be installed between joists in hne with strap bracing at a 
maximum spacing of 12 feet (3658 mm) measured perpen- 
dicular to the joists, and at the termination of all straps. The 
third-point bracing span values from Tables R804.3.1(l) 
through R804.3.1(8) shall be used for straps installed at 
closer spacings than third-point bracing, or when sheathing is 
apphed to the top of the ceiling joists. 

R804.3.3 Allowable rafter spans. The horizontal projec- 
tion of the rafter span, as shown in Figure R804.3, shall not 
exceed the limits set forth in Table R804.3.3(l). Wind 
speeds shall be converted to equivalent ground snow loads 
in accordance with Table R804.3.3(2). Rafter spans shall be 
selected based on the higher of the ground snow load or the 
equivalent snow load converted from the wind speed. When 
required, a rafter support brace shall be a minimum of 
350S 162-33 C-section with maximum length of 8 feet 
(2438 mm) and shall be connected to a ceihng joist and raf- 
ter with four No. 10 screws at each end. 

R804.3.3.1 Rafter framing. Rafters shall be connected 
to a parallel ceiling joist to form a continuous tie 
between exterior walls in accordance with Figures 
R804.3 and R804.3.1(l) and Table R804.3.1. Rafters 
shall be connected to a ridge member with a minimum 
2-inch by 2-inch (5 1 mm by 5 1 mm) clip angle fastened 
with minimum No. 10 screws to the ridge member in 
accordance with Figure R804.3.3.1 and Table 
R804.3.3.1. The clip angle shall have a minimum steel 
thickness as the rafter member and shall extend the full 
depth of the rafter member. The ridge member shall be 
fabricated from a C-section and a track section, which 
shall be of a minimum size and steel thickness as the 
adjacent rafters and shall be installed in accordance 
with Figure R804.3. 3.1. 

R804.3.3.2 Roof cantilevers. Roof cantilevers shall not 
exceed 24 inches (610 mm) in accordance with Figure 
R804.3. Roof cantilevers shall be supported by a header 
in accordance with Section R603.6 or shall be supported 
by the floor framing in accordance with Section 
R505.3.7. 

R804.3.4 Rafter bottom flange bracing. The bottom 
flanges of steel rafters shall be continuously braced with a 
minimum 33-mil (0.84 mm) C-section, 33-mil (0.84 mm) 
track section, or a 1 Va-inch by 33-mil (38 mm by 0.84 mm) 
steel strapping at a maximum spacing of 8 feet (2438 mm) 
as measured parallel to the rafters. Bracing shall be installed 
in accordance with Figure R804.3. The C-section, track sec- 
tion, or straps shall be fastened to blocking with at least two 
No. 8 screws. Blocking or bridging (X-bracing) shall be 



installed between rafters in-line with the continuous bracing 
at a maximum spacing of 12 feet (3658 mm) measured per- 
pendicular to the rafters and at the termination of all straps. 
The ends of continuous bracing shall be fastened to block- 
ing with at least two No. 8 screws. 

R804.3.5 Cutting and notching. Flanges and lips of load- 
bearing steel roof framing members shall not be cut or notched. 
Holes in webs shall be in accordance with Section R804.2. 

R804.3.6 Hole patching. Web holes not conforming to the 
requirements in Section R804.2 shall be designed in accor- 
dance with one of the following: 

1. Framing members shall be replaced or designed in 
accordance with accepted engineering practices when 
web holes exceed the following size limits: 

1.1. The depth of the hole, measured across the 
web, exceeds 70 percent of the flat width of 
the web; or, 

1.2. The length of the hole, measured along the 
web, exceeds 10 inches (254 mm) or the depth 
of the web, whichever is greater. 

2. Web holes not exceeding the dimensional require- 
ments in Section R804.3.6, Item 1 shall be patched 
with a solid steel plate, stud section, or track section in 
accordance with Figure R804.3.6. The steel patch 
shall be of a minimum thickness as the receiving 
member and shall extend at least 1 inch (25 mm) 
beyond all edges of the hole. The steel patch shall be 
fastened to the web of the receiving member with No. 
8 screws spaced no greater than 1 inch (25 mm) cen- 
ter-to-center along the edges of the patch with mini- 
mum edge distance of V2 inch (13 mm). 

R804.3.7 Splicing. Rafters and other structural members, 
except ceiling joists, shall not be spliced. Splices in ceiling 
joists shall only be permitted at interior bearing points and 
shall be constructed in accordance with Figure R804.3.7(l). 
Spliced ceiling joists shall be connected with the same num- 
ber and size of screws on connection. Splicing of tracks 
shall conform to Figure R804.3.7(2). 

R804.3.8 Bearing stiffener. A bearing stiffener shall be 
fabricated from a minimum 33-mil (0.84 mm) C-section or 
track section. Each stiffener shall be fastened to the web of 
the ceiling joist with a minimum of four No. 8 screws 
equally spaced as shown in Figure R804.3.8. Stiffeners shall 
extend across the full depth of the web and shall be installed 
on either side of the web. 

R804.3.9 Headers. Roof-ceiling framing above wall open- 
ings shall be supported on headers. The allowable spans for 
headers in bearing walls shall not exceed the values set forth 
in Table R603.6(l). 

R804.3.10 Framing of opening. Openings in roof and ceil- 
ing framing shall be framed with headers and trimmers 
between ceiling joists or rafters. Header joist spans shall not 
exceed 4 feet (1219 mm). Header and trimmer joists shall be 
fabricated from joist and track sections, which shall be of a 
minimum size and thickness in accordance with Figures 
R804.3.10(l) and R804.3.10(2). Each header joist shall be 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



281 



ROOF-CEILING CONSTRUCTION 







TABLE R804.3.3(1) 
ALLOWABLE HORIZONTAL RAFTER SPANS^''^ 33 ksi STEEL 






lUIEMBER 
DESIGNATION 


ALLOWABLE SPAN MEASURED HORIZONTALLY (feet-inches) 


Ground Snow Load 


20psf 


30psf 


50psf 


70 psf 


Rafter spacing (in) 


16 


24 


16 


24 


16 


24 


16 


! 24 


550S162-33 


14'-0" 


ll'-5" 


ll'-lO" 


9'-8" 


9'-5" 


7'-8" 


B'-l" 


I 6'-7" 


550S 162-43 


16'-6" 


13'-10" 


14'-4" 


11 '-9" 


ll'-5" 


9'-4" 


9'-10" 


j 8'-0" 


550S 162-54 


17'-9" 


15'-6" 


15'-6" 


13'-2" 


12'-11" 


10'-6" 


ll'-l" 


1 9'-0" 


550S 162-68 


19'-0" 


16'-7" 


16'-8" 


14'-7" 


14'-1" 


ll'-lO" 


12'-5" 


10'-2" 


550S162-97 


21 '-2" 


18'-6" 


18'-7" 


16'-2" 


15'-8" 


13'-8" 


14'-0" 


12'-2" 


800S 162-33 


17'-0" 


13'-11" 


14'-5" 


11 '-9" 


11 '-6" 


7'-9" 


8'-6" 


5'-8" 


BOOS 162-43 


21'-1" 


17'-3" 


17'-10" 


14'-7" 


14'-3" 


11 '-7" 


12'-2" 


9'-ll" 


BOOS 162-54 


23'-ll" 


20'-4" 


21'-0" 


17'-3" 


16'-10" 


13'-9" 


14'-5" 


11 '-9" 


B00S162-6B 


25'-9" 


22'-6" 


22'-7" 


19'-5" 


19'-0" 


15'-6" 


16'-3" 


13'-3" 


BOOS 162-97 


2B'-9" 


25'-l" 


25'-2" 


22'-0" 


21'-3" 


18'-7" 


19'-0" 


16'-0" 


lOOOS 162-43 


23'-4" 


19'-1" 


19'-9" 


16'-2" 


15'-9" 


12'-11" 


13'-6" 


lO'-O" 


lOOOS 162-54 


27'-8" 


22'-7" 


23'-5" 


19'-1" 


18'-8" 


15'-3" 


16'-0" 


13'-1" 


1000S162-6B 


30'-ll" 


27'-0" 


27'-2" 


22'-ll" 


22'-5" 


18'-3" 


19'-2" 


15'-8" 


1000S162-97 


34'-7" 


30'-2" 


30'-4" 


26'-6?' 


25'-7" 


22'- 1" 


22'- 10" 


' 18'-11" 


1200S 162-43 


25'-5" 


20'-9" 


21 '-6" 


17'-6" 


17'-1" 


11 '-5" 


12'-6" 


1 8'-6" 


1200S 162-54 


30'-0" 


24'-6" 


25'-5" 


20'-9" 


20'-3" 


16'-7" 


17'-5" 


I 14'-2" 


1200S 162-68 


35'-5" 


28'-ll" 


.30'-0" 


24'-6" 


23'-ll" 


19'-6" 


20'-6" 


! 16'-9" 


1200S162-97 


40'-4" 


35'-3" 


35'-5" 


30'-ll" 


29'-10" 


25'-5" 


26'-B" 


21 '-9" 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot - 

a. Table provides maximum horizontal rafter spans in feet and inches for 

b. Deflection criterion: L/240 for live loads and L/180 for total loads. 

c. Roof dead load =12 psf. 



r 0.0479kPa. 
slopes between 3: 



12 and 12:12. 



TABLE R804.3.3(2) 
BASIC WIND SPEED TO EQUIVALENT SNOW LOAD CONVERSION 



BASIC WIND SPEED 
AND EXPOSURE 


EQUIVALENT GROUND SNOW LOAD (psf) 


Roof slope 


Exp. A/B 


Exp. C 


3:12 


4:12 


5:12 


6:12 


7:12 


8:12 


9:12 


10:12 


11:12 


12:12 


85mph 


— 


20 


20 


20 


20 


20 


20 


30 


30 


30 


30 


100 mph 


85 mph 


20 


20 


20 


20 


30 


30 


30 


30 


50 ': 


50 


UOmph 


100 mph 


20 


20 


20 


20 


30 


50 


50 


50 


50 


50 


— 


UOmph 


30 


30 


30 


50 


50 


50 


70 


70 


70 


— 



For SI: 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa. 



connected to a trimmer joist with a minimum of four 2-inch 
by 2-inch (51 by 51 mm) clip angles. Each clip angle shall be 
fastened to both the header and trimmer joists with four No. 8 
screws, evenly spaced, through each leg of the clip angle. The 
clip angles shall have a steel thickness not less than that of the 
floor joist. 



282 



R804.4 Roof tie-down. Roof assemblies subjectlto wind uplift 
pressures of 20 pounds per square foot (0.96 kN/m^) or greater, 
as established in Table R30 1.2(2), shall have rafter-to-bearing 
wall ties provided in accordance with Table R802. 1 1 . 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



TABLE R804.3.3.1 
NUMBER OF SCREWS REQUIRED AT EACH LEG OF CLIP 
ANGLE FOR RAFTER TO RIDGE MEMBER CONNECTION^ 



BUILDING WIDTH 
(feet) 


NUMBER OF SCREWS 


Ground snow load (psf) 


0to20 


21 to 30 


31 to 50 


51 to 70 


24 


2 


2 


3 


4 


28 


2 


3 


4 


5 


32 


2 


3 


4 


5 


36 


3 


3 


5 


6 


40 


3 


4 


5 


7 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kl^. 
a. Screws shall be No. 10 minimum. 



CLIP ANGLE 



SCREWS IN EACH LEG 
OF CLIP ANGLE 



RAFTER 




For SI: 1 inch = 25.4 mm. 



RIDGE MEMBER SHALL CONSIST OF A 
C-SECTION INSIDE A TRACK SECTION 
SCREWED AT 24 IN. O.C. THROUGH TOP 
AND BOTTOM FLANGES 



FIGURE R804.3.3.1 
RIDGE BOARD CONNECTION 



'SOLID STEEL PLATE, C-SECTION OR TRACK 
(MIN. THICKNESS OF JOIST) 




SCREWS 1 IN. O.C. 
(TYP) 



For SI: 1 inch = 25.4 mm. 



FIGURE R804.3.6 
HOLE PATCHING 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



283 



ROOF-CEILING CONSTRUCTION 



CEILING JOIST 



NUMBER OF SCREWS ON EACH 
SIDE OF SPLICE SHALL BE THE 
SAME AS REQUIRED FOR THE 
HEEL JOINT CONNECTION 



C- OR TRACK SECTION WITH MIN. S;iZE 
AND THICKNESS AS CEILING JOISTS 



CEILING JOIST 




• 



For SI: 1 inch = 25.4 mm. 



FIGURE R804.3.7(1) 
SPLICED CEiLING JOISTS 



JOIST SECTION INSIDE TFiACK 




For SI: 1 inch = 25.4 mm. 



284 



■ TRACK 



FIGURE R804.3.7(2) 
TRACK SPLICE 



FOUR SCREWS ON 
EACH SIDE OF 
SPLICE 



2006 INTERNATIONAL RESIDENTIAL CODE' 



ROOF-CEILING CONSTRUCTION 



CEILING JOIST 



BEARING STIFFENER 




FIGURE R804.3.8 
BEARING STIFFENER 



HEADER 



JOIST/RAFTER 
(TYP.) 



JOIST/RAFTER 



CLIP ANGLE 
(TYP.) 




JOIST/RAFTER (TYP) 



TRIMMER 



For SI: 1 foot = 304.8 mm. 



FIGURE R804.3.10(1) 
ROOF OPENING 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



285 



ROOF-CEILING CONSTRUCTION 



2 IN. CLIP ANGLE WITH FOUR 
SCREWS EACH LEG BOTH SIDES 
OF CONNECTION 



4 SCREWS EACH LEG OF CLIP ANGLE 
(BOTH SIDES OF CONNECTION) 
MIN. LENGTH = JOIST/RAFTER WEB 
DEPTH MINUS V2 IN. 



BUILT-UP HEADER AND TRIMMER JOISTS SHALL 
BE SCREWED TOGETHER AT 24 IN. O.C. MAX. 
THROUGH TOP AND BOTTOM FLANGES (TYP.) 



BUILT-UP HEADER JOISTS SHALL 
CONSIST OF A C-SECTION INSIDE A 
TRACK SECTION 




JOIST/RAFTER 



BUILT-UP HEADER JOISTS SHALL 
CONSIST OF A C-SECTION INSIDE A 
TRACK SECTION 



For SI: 1 inch = 25.4 mm. 



FIGURE R804.3.10(2) 
HEADER TO TRIMMER CONNECTION 



SECTION R805 
CEILING FINISHES 

R805.1 Ceiling installation. Ceilings shall be installed in 
accordance with the requirements for interior wall finishes as 
provided in Section R702. 



SECTION R806 
ROOF VENTILATION 

R806.1 Ventilation required. Enclosed attics and enclosed 
rafter spaces formed where ceilings are applied directly to the 
underside of roof rafters shall have cross ventilation for each 
separate space by ventilating openings protected against the 
entrance of rain or snow. Ventilating openings shall be pro- 
vided with corrosion-resistant wire mesh, with Vg inch (3.2 
mm) minimum to V4 inch (6 mm) maximum openings. 

R806.2 Minimum area. The total net free ventilating area 
shall not be less than V150 of the area of the space ventilated 
except that reduction of the total area to '/300 is permitted, pro- 
vided that at least 50 percent and not more than 80 percent of 
the required ventilating area is provided by ventilators located 
in the upper portion of the space to be ventilated at least 3 feet 
(914 mm) above the eave or cornice vents with the balance of 
the required ventilation provided by eave or cornice vents. As 
an alternative, the net free cross-ventilation area may be 
reduced to V300 when a vapor barrier having a transmission rate 



not exceeding 1 perm (5.7 x 10"^' kg/s 
the warm-in- winter side of the ceiling. 



m^ • Pa) is installed on 



R806.3 Vent and insulation clearance. Where eave or cornice 
vents are installed, insulation shall not block the free flow of 



air. A minimum of a 1-inch (25 nrni) space shall t»e provided 
between the insulation and the roof sheathing and 1 at the loca- I 
tion of the vent. | 

R806.4 Conditioned attic assemblies. Unvented conditioned 
attic assemblies (spaces between the ceiling joists of the top 
story and the roof rafters) are permitted under the following 
conditions: 

1. No interior vapor retarders are installed on the ceiling 
side (attic floor) of the unvented attic assembly. 

2. An air-impermeable insulation is applied in direct con- 
tact to the underside/interior of the structural roof deck. 
"Air-impermeable" shall be defined by ASTM E 283. 

Exception: In Zones 2B and 3B, insulation is not 
required to be air impermeable. 

3. In the warm humid locations as defined in Section 
NllOl.2.1: 

3.1. For asphalt roofing shingles: A 1-perm (5.7 x 
10"'^ kg/s • m^ • Pa) or less vapor retarder (deter- 
mined using Procedure B of ASTM E 96) is 
placed to the exterior of the structural roof deck; 
that is, just above the roof structural isheathing. 

3.2. For wood shingles and shakes: a minimum con- 
tinuous V4-inch (6 mm) vented air space sepa- 
rates the shingles/shakes and the roofing felt 
placed over the structural sheathing. 

4. In Zones 3 through 8 as defined in Section Ni 101 .2, suf- 
ficient insulation is installed to maintain the monthly 
average temperature of the condensing surface above 
45°F (7°C). The condensing surface is defiiled as either 



286 



I 
2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF-CEILING CONSTRUCTION 



the structural roof deck or the interior surface of an 
air-impermeable insulation applied in direct contact with 
the underside/interior of the structural roof deck. 
"Air-impermeable" is quantitatively defined by ASTM 
E 283. For calculation purposes, an interior temperature 
of 68°F (20°C) is assumed. The exterior temperature is 
assumed to be the monthly average outside temperature. 



SECTION R807 
ATTIC ACCESS 

R807.1 Attic access. Buildings with combustible ceiling or 
roof construction shall have an attic access opening to attic 
areas that exceed 30 square feet (2.8 m^) and have a vertical 
height of 30 inches (762 mm) or more. 

The rough-framed opening shall not be less than 22 inches 
by 30 inches (559 mm by 762 mm) and shall be located in a 
hallway or other readily accessible location. A 30-inch (762 
mm) minimum unobstructed headroom in the attic space shall 
be provided at some point above the access opening. See Sec- 
tion M1305.1.3 for access requirements where mechanical 
equipment is located in attics. 



SECTION R808 
INSULATION CLEARANCE 

R808.1 Combustible insulation. Combustible insulation shall 
be separated a minimum of 3 inches (76 mm) from recessed 
luminaires, fan motors and other heat-producing devices. 

Exception: Where heat-producing devices are listed for 
lesser clearances, combustible insulation complying with 
the listing requirements shall be separated in accordance 
with the conditions stipulated in the listing. 

Recessed luminaires installed in the building thermal enve- 
lope shall meet the requirements of Section Nl 102.4.3. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



287 



288 



2006 INTERNATIONAL RESIDiENTIAL CODE" 



CHAPTER 9 

ROOF ASSEMBLIES 



SECTION R901 
GENERAL 

R901.1 Scope. The provisions of this chapter shall govern the 
design, materials, construction and quality of roof assemblies. 



SECTION R902 
ROOF CLASSIFICATION 

R902.1 Roofing covering materials. Roofs shall be covered 
with materials as set forth in Sections R904 and R905. Class A, 
B or C roofing shall be installed in areas designated by law as 
requiring their use or when the edge of the roof is less than 3 
feet (914 mm) from a property line. Classes A, B and C roofing 
required to be listed by this section shall be tested in accor- 
dance with UL 790 or ASTM E 108. Roof assemblies with cov- 
erings of brick, masonry, slate, clay or concrete roof tile, 
exposed concrete roof deck, ferrous or copper shingles or 
sheets, and metal sheets and shingles, shall be considered Class 
A roof coverings. 

R902.2 Fire-retardant-treated shingles and shakes. 

Fire-retardant-treated wood shakes and shingles shall be 
treated by impregnation with chemicals by the full-cell vac- 
uum-pressure process, in accordance with AWRA. CI. Each 
bundle shall be marked to identify the manufactured unit and 
the manufacturer, and shall also be labeled to identify the clas- 
sification of the material in accordance with the testing 
required in Section R902. 1 , the treating company and the qual- 
ity control agency. 



SECTION R903 
WEATHER PROTECTION 

R903.1 General. Roof decks shall be covered with approved 
roof coverings secured to the building or structure in accor- 
dance with the provisions of this chapter. Roof assemblies shall 
be designed and installed in accordance with this code and the 
approved manufacturer's installation instructions such that the 
roof assembly shall serve to protect the building or structure. 

R903.2 Flashing. Flashings shall be installed in a manner that 
prevents moisture from entering the wall and roof through 
joints in copings, through moisture permeable materials and at 
intersections with parapet walls and other penetrations through 
the roof plane. 

R903.2.1 Locations. Flashings shall be installed at wall and 
roof intersections, wherever there is a change in roof slope 
or direction and around roof openings. Where flashing is of 
metal, the metal shall be corrosion resistant with a thickness 
of not less than 0.019 inch (0.5 mm) (No. 26 galvanized 
sheet). 

R903.3 Coping. Parapet walls shall be properly coped with 
noncombustible, weatherproof materials of a width no less 
than the thickness of the parapet wall. 



R903.4 Roof drainage. Unless roofs are sloped to drain over 
roof edges, roof drains shall be installed at each low point of the 
roof. Where required for roof drainage, scuppers shall be 
placed level with the roof surface in a wall or parapet. The scup- 
per shall be located as determined by the roof slope and con- 
tributing roof area. 

R903.4.1 Overflow drains and scuppers. Where roof 
drains are required, overflow drains having the same size as 
the roof drains shall be installed with the inlet flow line 
located 2 inches (5 1 mm) above the low point of the roof, or 
overflow scuppers having three times the size of the roof 
drains and having a minimum opening height of 4 inches 
(102 mm) shall be installed in the adjacent parapet walls 
with the inlet flow located 2 inches (5 1 mm) above the low 
point of the roof served. The installation and sizing of over- 
flow drains, leaders and conductors shall comply with the 
International Plumbing Code. 

Overflow drains shall discharge to an approved location 
and shall not be connected to roof drain lines. 

R903.5 Hail exposure. Hail exposure, as specified in Sections 
R903.5.1 and R903.5.2, shall be determined using Figure 
R903.5. 

R903.5.1 Moderate hail exposure. One or more hail days 
with hail diameters larger than 1.5 inches (38 mm) in a 
20-year period. 

R903.5.2 Severe hail exposure. One or more hail days with 
hail diameters larger than or equal to 2.0 inches (5 1 mm) in a 
20-year period. 



SECTION R904 
MATERIALS 

R904.1 Scope. The requirements set forth in this section shall 
apply to the application of roof covering materials specified 
herein. Roof assemblies shall be applied in accordance with 
this chapter and the manufacturer's installation instructions. 
Installation of roof assemblies shall comply with the apphcable 
provisions of Section R905. 

R904.2 Compatibility of materials. Roof assembhes shall be 
of materials that are compatible with each other and with the 
building or structure to which the materials are applied. 

R904.3 Material specifications and physical characteris- 
tics. Roof covering materials shall conform to the applicable 
standards listed in this chapter. In the absence of applicable 
standards or where materials are of questionable suitability, 
testing by an approved testing agency shall be required by the 
building official to determine the character, quality and limita- 
tions of application of the materials. 

R904.4 Product identification. Roof covering materials shall 
be delivered in packages bearing the manufacturer's identify- 
ing marks and approved testing agency labels when required. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



289 



L j Minimum 1 hall clay/20 years. Moderate Size (1.5 - 5.0 In.) 
■ Minimum 1 hail day/20 years, Severe Size (2.0 - 5.0 «n.) 



DO 

m 

V) 



I 




8 

D 



FIGURE R903.5 
HAIL EXPOSURE MAP 



ROOF ASSEMBLIES 



Bulk shipments of materials shall be accompanied by the same 
information issued in the form of a certificate or on a bill of lad- 
ing by the manufacturer. 



SECTION R905 
REQUIREMENTS FOR ROOF COVERINGS 

R905.1 Roof covering application. Roof coverings shall be 
applied in accordance with the applicable provisions of this 
section and the manufacturer's installation instructions. Unless 
otherwise specified in this section, roof coverings shall be 
installed to resist the component and cladding loads specified 
in Table R301 .2(2), adjusted for height and exposure in accor- 
dance with Table R30 1.2(3). 

R905.2 Asphalt shingles. The installation of asphalt shingles 
shall comply with the provisions of this section. 

R905.2.1 Sheathing requirements. Asphalt shingles shall 
be fastened to solidly sheathed decks. 

R905.2.2 Slope. Asphalt shingles shall be used only on roof 
slopes of two units vertical in 12 units horizontal (2:12) or 
greater. For roof slopes from two units vertical in 12 units 
horizontal (2:12) up to four units vertical in 12 units hori- 
zontal (4:12), double underlayment application is required 
in accordance with Section R905.2.7. 

R905.2.3 Underlayment. Unless otherwise noted, required 
underlayment shall conform to ASTM D 226 Type I, ASTM 
D 4869 Type I, or ASTM D 6757. 

Self-adhering polymer modified bitumen sheet shall 
comply with ASTM D 1970. 

R905.2.4 Asphalt shingles. Asphalt shingles shall have 
self-seal strips or be interlocking, and comply with ASTM 
D 225 or D 3462. 

R905.2.4.1 Wind resistance of asphalt shingles. 

Asphalt shingles shall be installed in accordance with Sec- 
tion R905.2.6. Shingles classified using ASTM D 3161 
are acceptable for use in wind zones less than 110 mph (49 
m/s). Shingles classified using ASTM D 3 161 , Class F, are 
acceptable for use in all cases where special fastening is 
required. 

R905.2.5 Fasteners. Fasteners for asphalt shingles shall be 
galvanized steel, stainless steel, aluminum or copper roof- 
ing nails, minimum 12 gage [0. 105 inch (3 mm)] shank with 
a minimum Vg-inch (10 mm) diameter head, ASTM F 1667, 
of a length to penetrate through the roofing materials and a 
minimum of V4 inch (19 mm) into the roof sheathing. Where 
the roof sheathing is less than V4 inch (19 mm) thick, the fas- 
teners shall penetrate through the sheathing. Fasteners shall 
comply with ASTM F 1667. 

R905.2.6 Attachment. Asphalt shingles shall have the min- 
imum number of fasteners required by the manufacturer. 
For normal application, asphalt shingles shall be secured to 
the roof with not less than four fasteners per strip shingle or 
two fasteners per individual shingle. Where the roof slope 
exceeds 20 units vertical in 12 units horizontal (167 percent 
slope), special methods of fastening are required. For roofs 
located where the basic wind speed per Figure R301 .2(4) is 



110 mph (49 m/s) or higher, special methods of fastening 
are required. Special fastening methods shall be tested in 
accordance with ASTM D 3161, Class F. Asphalt shingle I 
wrappers shall bear a label indicating compliance with I 
ASTM D 3161, Class F. | 

R905.2.7 Underlayment application. For roof slopes from 
two units vertical in 12 units horizontal (17-percent slope), up 
to four units vertical in 1 2 units horizontal (33-percent slope), 
underlayment shall be two layers apphed in the following 
manner. Apply a 19-inch (483 mm) strip of underlayment felt 
parallel to and starting at the eaves, fastened sufficiently to 
hold in place. Starting at the eave, apply 36-inch- wide (914 
mm) sheets of underlayment, overlapping successive sheets 
19 inches (483 mm), and fastened sufficiently to hold in 
place. Distortions in the underlayment shall not interfere with I 
the abihty of the shingles to seal. For roof slopes of four units | 
vertical in 12 units horizontal (33-percent slope) or greater, 
underlayment shall be one layer applied in the following 
manner. Underlayment shall be apphed shingle fashion, par- 
allel to and starting from the eave and lapped 2 inches (51 
mm), fastened sufficiently to hold in place. Distortions in the I 
underlayment shall not interfere with the ability of the shin- | 
gles to seal. End laps shall be offset by 6 feet (1829 mm). 

R905.2.7.1 Ice barrier. In areas where there has been a I 
history of ice forming along the eaves causing a backup I 
of water as designated in Table R301 .2(1), an ice barrier | 
that consists of a least two layers of underlayment 
cemented together or of a self-adhering polymer modi- 
fied bitumen sheet, shall be used in heu of normal 
underlayment and extend from the lowest edges of all I 
roof surfaces to a point at least 24 inches (610 mm) inside | 
the exterior wall line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

R905.2.7.2 Underlayment and high wind. Underlay- 
ment applied in areas subject to high winds [above 110 
mph (49 m/s) per Figure R30 1 .2(4)] shall be applied with 
corrosion-resistant fasteners in accordance with manu- 
facturer's installation instructions. Fasteners are to be 
applied along the overlap not farther apart than 36 inches 
(914 mm) on center. 

R905.2.8 Flashing. Flashing for asphalt shingles shall com- 
ply with this section. 

R905.2.8.1 Base and cap flashing. Base and cap flashing 
shall be installed in accordance with manufacturer's instal- 
lation instructions. Base flashing shall be of either corro- 
sion-resistant metal of minimum nominal 0.019-inch (0.5 
mm) thickness or mineral surface roll roofing weighing a 
minimum of 77 pounds per 100 square feet (4 kg/m^). Cap 
flashing shall be corrosion-resistant metal of minimum 
nominal 0.019-inch (0.5 mm) thickness. 

R905.2.8.2 Valleys. Valley linings shall be installed in 
accordance with the manufacturer's installation instruc- 
tions before applying shingles. Valley finings of the fol- 
lowing types shall be permitted: 

1. For open valley (valley lining exposed) lined with 
metal, the vafiey lining shall be at least 24 inches 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



291 



ROOF ASSEMBLIES 



(610 mm) wide and of any of the corrosion-resis- 
tant metals in Table R905.2.8.2. 

2. For open valleys, valley lining of two plies of min- 
eral surfaced roll roofing, complying with ASTM 
D 3909 or ASTM D 6380 Class M, shall be permit- 
ted. The bottom layer shall be 18 inches (457mm) 
and the top layer a minimum of 36 inches (914 
mm) wide. 

3. For closed valleys (valley covered with shingles), 
valley lining of one ply of smooth roll roofing 
complying with ASTM D 6380 Class S Type III, 
Class M Type II, or ASTM D 3909 and at least 36 
inches wide (914 mm) or valley lining as described 
in Items 1 and 2 above shall be permitted. Spe- 
cialty underlayment complying with ASTM D 
1970 may be used in lieu of the lining material. 

TABLE R905.2.8.2 
VALLEY LINING MATERIAL 



MATERIAL 


MINIMUM 

THICKNESS 

(inches) 


GAGE 


WEIGHT 
(pounds) 


Cold-rolled copper 


0.0216 
nominal 


— 


ASTM B 370, 
16 oz. per 
square foot 


Lead-coated copper 


0.0216 
nominal 


— 


ASTMB 101, 
16 oz. per 
square foot 


High-yield copper 


0.0162 
nominal 


— 


ASTM B 370, 
12 oz. per 
square foot 


Lead-coated 
high-yield copper 


0.0162 
nominal 


— 


ASTMB 101, 

12 oz. per 

square foot 


Aluminum 


0.024 








Stainless steel 





28 





Galvanized steel 


0.0179 


26 (zinc 
coated G90) 


— 


Zinc alloy 


0.027 








Lead 








2V, 


Painted terne 


— 


— 


20 



For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg. 

R905.2.8.3 Crickets and saddles. A cricket or saddle 
shall be installed on the ridge side of any chimney or pen- 
etration more than 30 inches (762 mm) wide as measured 
perpendicular to the slope. Cricket or saddle coverings 
shall be sheet metal or of the same material as the roof 
covering. 

R905.2.8.4 Sidewall flashing. Flashing against a verti- 
cal sidewall shall be by the step-flashing method. 

R905.2.8.5 Other flashing. Flashing against a vertical 
front wall, as well as soil stack, vent pipe and chimney 
flashing, shall be applied according to the asphalt shingle 
manufacturer's printed instructions. 



R905.3 Clay and concrete tile. The installation of clay and 
concrete shall comply with the provisions of this section. Clay 
roof tile shall comply with ASTM C 1 167. 

R905.3.1 Deck requirements. Concrete and clay tile shall 
be installed only over solid sheathing or spaced structural 
sheathing boards. 

R905.3.2 Deck slope. Clay and concrete roof tile shall be 
installed on roof slopes of two and one-half units vertical in 
1 2 units horizontal ( 2'/2: 1 2) or greater. For roof slopes from 
two and one-half units vertical in 12 units horizontal 
(272:12) to four units vertical in 12 units horizontal (4:12), 
double underlayment application is required in accordance 
with Section R905.3.3. 

R905.3.3 Underlayment. Unless otherwise noted, required 
underlayment shall conform to ASTM D 226 Type II; 
ASTM D 2626 Type I; or ASTM D 6380 Class M mineral | 
surfaced roll roofing. 

R905.3.3.1 Low slope roofs. For roof slopes from two 
and one-half units vertical in 12 units horizontal 
(272:12), up to four units vertical in 12 units horizontal 
(4:12), underlayment shall be a minimum of two layers 
underlayment appHed as follows: 

1. Starting at the eave, a 19-inch (483 mm) strip of 
underlayment shall be applied parallel with the 
eave and fastened sufficiently in place. 

2. Starting at the eave, 36-inch- wide (914 mm) strips 
of underlayment felt shall be applied, overlapping 
successive sheets 19 inches (483 mm), and fas- 
tened sufficiently in place. 

R905.3.3.2 High slope roofs. For roof slopes of four 
units vertical in 12 units horizontal (4:12) or greater, 
underlayment shall be a minimum of one layer of 
underlayment felt applied shingle fashion, parallel to and 
starting from the eaves and lapped 2 inches (5 1 mm), fas- 
tened sufficiently in place. 

R905.3.3.3 Underlayment and high wind. Underlay- 
ment applied in areas subject to high wind [over 110 
miles per hour (49 m/s) per Figure R30 1.2(4)] shall be 
applied with corrosion-resistant fasteners in accordance 
with manufacturer's installation instructions. Fasteners 
are to be applied along the overlap not farther apart than 
36 inches (914 mm) on center. 

R905.3.4 Tile. Clay roof tile shall comply with ASTM C 
1167. 

R905.3.5 Concrete tile. Concrete roof tile shall comply 
with ASTM C 1492. 

R905.3.6 Fasteners. Nails shall be corrosion resistant and 
not less than 1 1 gage, V,6-inch (11 mm) head, and of suffi- 
cient length to penetrate the deck a minimum of V4 inch (19 
mm) or through the thickness of the deck, whichever is less. 
Attaching wire for clay or concrete tile shall not be smaller 
than 0.083 inch (2 mm). Perimeter fastening areas include 
three tile courses but not less than 36 inches (914 mm) from 
either side of hips or ridges and edges of eaves and gable 
rakes. 



292 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



ROOF ASSEMBLIES 



R905.3.7 Application. Tile shall be applied in accordance 
with this chapter and the manufacturer's installation instruc- 
tions, based on the following: 

1. Climatic conditions. 

2. Roof slope. 

3. Underlayment system. 

4. Type of tile being installed. 

Clay and concrete roof tiles shall be fastened in accor- 
dance with this section and the manufacturer's installation 
instructions. Perimeter tiles shall be fastened with a mini- 
mum of one fastener per tile. Tiles with installed weight less 
than 9 pounds per square foot (0.4 kg/m^) require a mini- 
mum of one fastener per tile regardless of roof slope. Clay 
and concrete roof tile attachment shall be in accordance 
with the manufacturer's installation instructions where 
applied in areas where the wind speed exceeds 100 miles per 
hour (45 m/s) and on buildings where the roof is located 
more than 40 feet (12 192 mm) above grade. In areas subject 
to snow, a minimum of two fasteners per tile is required. In 
all other areas, clay and concrete roof tiles shall be attached 
in accordance with Table R905.3.7. 

TABLE R905.3.7 
CLAY AND CONCRETE TILE ATTACHMENT 



SHEATHING 


ROOF SLOPE 


NUMBER OF 
FASTENERS 


Solid without battens 


All 


One per tile 


Spaced or solid 
with battens and 
slope < 5:12 


Fasteners not required 


— 


Spaced sheathing 
without battens 


5:12 < slope < 12:12 


One per tile/every 
other row 


12:12 < slope < 24:12 


One per tile 



R905.3.8 Flashing. At the juncture of roof vertical surfaces, 
flashing and counterflashing shall be provided in accor- 
dance with this chapter and the manufacturer's installation 
instructions and, where of metal, shall not be less than 0.019 
inch (0.5 mm) (No. 26 galvanized sheet gage) corro- 
sion-resistant metal. The valley flashing shall extend at least 
1 1 inches (279 mm) from the centerline each way and have a 
splash diverter rib not less than 1 inch (25 mm) high at the 
flow line formed as part of the flashing. Sections of flashing 
shall have an end lap of not less than 4 inches (102 mm). For 
roof slopes of three units vertical in 12 units horizontal 
(25 -percent slope) and greater, valley flashing shall have a 
36-inch-wide (914 mm) underlayment of one layer of Type I 
underlayment running the full length of the valley, in addi- 
tion to other required underlayment. In areas where the 
average daily temperature in January is 25 °F (-4°C) or less, 
metal valley flashing underlayment shall be solid-cemented 
to the roofing underlayment for slopes less than seven units 
vertical in 12 units horizontal (58-percent slope) or be of 
self-adhering polymer modified bitumen sheet. 

R905.4 Metal roof shingles. The installation of metal roof 
shingles shall comply with the provisions of this section. 



R905.4.1 Deck requirements. Metal roof shingles shall be 
applied to a solid or closely fitted deck, except where the 
roof covering is specifically designed to be applied to 
spaced sheathing. 

R905.4.2 Deck slope. Metal roof shingles shall not be 
installed on roof slopes below three units vertical in 12 units 
horizontal (25 -percent slope). 

R905.4.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869, Type I or II. 

R905.4.3.1 Ice barrier. In areas where there has been a 
history of ice forming along the eaves causing a backup 
of water as designated in Table R301.2(l), an ice barrier 
that consists of at least two layers of underlayment 
cemented together or a self-adhering polymer modified 
bitumen sheet shall be used in place of normal 
underlayment and extend from the lowest edges of all 
roof surfaces to a point at least 24 inches (610 mm) inside 
the exterior wall line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

R905.4.4 Material standards. Metal roof shingle roof cov- 
erings shall comply with Table R905. 10.3(1). The materials 
used for metal roof shingle roof coverings shall be naturally 
corrosion resistant or be made corrosion resistant in accor- 
dance with the standards and minimum thicknesses listed in 
Table R905. 10.3(2). 

R905.4.5 Application. Metal roof shingles shall be secured 
to the roof in accordance with this chapter and the approved 
manufacturer's installation instructions. 

R905.4.6 Flashing. Roof valley flashing shall be of corro- 
sion-resistant metal of the same material as the roof cover- 
ing or shall comply with the standards in Table 
R905. 10.3(1). The valley flashing shall extend at least 8 
inches (203 mm) from the center line each way and shall 
have a splash diverter rib not less than V4 inch (19 mm) high 
at the flow line formed as part of the flashing. Sections of 
flashing shall have an end lap of not less than 4 inches (102 
mm). The metal valley flashing shall have a 36-inch-wide 
(914 mm) underlayment directly under it consisting of one 
layer of underlayment running the full length of the valley, 
in addition to underlayment required for metal roof shin- 
gles. In areas where the average daily temperature in Janu- 
ary is 25°F (-4°C) or less , the metal valley flashing 
underlayment shall be solid cemented to the roofing 
underlayment for roof slopes under seven units vertical in 
12 units horizontal (58-percent slope) or self-adhering poly- 
mer modified bitumen sheet. 

R905.5 Mineral-surfaced roll roofing. The installation of min- 
eral-surfaced roll roofing shall comply with this section. 

R905.5.1 Deck requirements. Mineral-surfaced roll roof- 
ing shall be fastened to solidly sheathed roofs. 

R905.5.2 Deck slope. Mineral-surfaced roll roofing shall 
not be applied on roof slopes below one unit vertical in 12 
units horizontal (8-percent slope). 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



293 



ROOF ASSEMBLIES 



R905.5.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869, Type I or II. 

R905.5.3.1 Ice barrier. In areas where there has been a 
history of ice forming along the eaves causing a backup 
of water as designated in Table R301 .2(1), an ice barrier 
that consists of at least two layers of underlayment 
cemented together or a self-adhering polymer modified 
bitumen sheet shall be used in place of normal 
underlayment and extend from the lowest edges of all 
roof surfaces to a point at least 24 inches (610 mm) inside 
the exterior wall line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

R905.5.4 Material standards. Mineral-surfaced roll roof- 
ing shall conform to ASTM D 3909 or ASTM D 6380, 
Class M. 

R905.5.5 Application. Mineral-surfaced roll roofing shall 
be installed in accordance with this chapter and the manu- 
facturer's installation instructions. 

R905.6 Slate and slate-type shingles. The installation of slate 
and slate-type shingles shall comply with the provisions of this 
section. 

R905.6.1 Deck requirements. Slate shingles shall be fas- 
tened to solidly sheathed roofs. 

R905.6.2 Deck slope. Slate shingles shall be used only on 
slopes of four units vertical in 12 units horizontal (33-per- 
cent slope) or greater. 

R905.6.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869, Type I or II. 

R905.6.3.1 Ice barrier. In areas where there has been a 
history of ice forming along the eaves causing a backup 
of water as designated in Table R301 .2(1), an ice barrier 
that consists of at least two layers of underlayment 
cemented together or a self-adhering polymer modified 
bitumen sheet shall be used in lieu of normal 
underlayment and extend from the lowest edges of all 
roof surfaces to a point at least 24 inches (610 mm) inside 
the exterior wall line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

R905.6.4 Material standards. Slate shingles shall comply 
with ASTM C 406. 

R905.6.5 Application. Minimum headlap for slate shingles 
shall be in accordance with Table R905.6.5. Slate shingles 
shall be secured to the roof with two fasteners per slate. Slate 
shingles shall be installed in accordance with this chapter 
and the manufacturer's installation instructions. 

TABLE R905.6.5 
SLATE SHINGLE HEADLAP 



SLOPE 


HEADLAP (inches) 


4:12 < slope < 8:12 


4 


8:12 < slope < 20:12 


3 


Slope < 20:12 


2 



R905.6.6 Flashing. Flashing and counterflashing shall be 
made with sheet metal. Valley flashing shall be a minimum 
of 15 inches (381 mm) wide. Valley and flashing metal shall 
be a minimum uncoated thickness of 0.0179-inch (0.5 mm) 
zinc coated G90. Chimneys, stucco or brick walls shall have 
a minimum of two plies of felt for a cap flashing consisting 
of a 4-inch- wide (102 mm) strip of felt set in plastic cement 
and extending 1 inch (25 mm) above the first felt and a top 
coating of plastic cement. The felt shall extend over the base 
flashing 2 inches (51 mm). 

R905.7 Wood shingles. The installation of wood shingles shall 
comply with the provisions of this section. 

R905.7.1 Deck requirements. Wood shingles shall be 
installed on solid or spaced sheathing. Where spaced 
sheathing is used, sheathing boards shall not be less than 
1 -inch by 4-inch (25 .4 mm by 1 02 mm) nominal dimensions 
and shall be spaced on centers equal to the weather exposure 
to coincide with the placement of fasteners. 

R905.7.1.1 Solid sheathing required. In areas where 
the average daily temperature in January is 25 °F (-4°C) 
or less, solid sheathing is required on that portion of the 
roof requiring the application of an ice barrier. 

R905.7.2 Deck slope. Wood shingles shall be installed on 
slopes of three units vertical in 12 units horizontal (25 -per- 
cent slope) or greater. 

R905.7.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869, Type I or II. 

R905.7.3.1 Ice barrier. In areas where there has been a 
history of ice forming along the eaves causing a backup 
of water as designated in Table R301.2(l), an ice barrier 
that consists of at least two layers of underlayment 
cemented together or a self- adhering polymer modified 
bitumen sheet shall be used in lieu of normal 
underlayment and extend from the lowest edges of all 
roof surfaces to a point at least 24 inches (610 mm) inside 
the exterior wall line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

R905.7.4 Material standards. Wood shingles shall be of 
naturally durable wood and comply with the requirements 
ofTableR905.7.4. 

TABLE R905.7.4 
WOOD SHINGLE MATERIAL REQUIREMENTS 



MATERIAL 


MINIMUM GRADES 


APPLICABLE 
GRADING RULES 


Wood shingles of 
naturally durable wood 


1,2 or 3 


Cedar Shake and 
Shingle Bureau 



For SI: 1 inch = 25.4 mm. 



R905.7.5 Application. Wood shingles shall be installed 
according to this chapter and the manufacturer's installation 
instructions. Wood shingles shall be laid with a side lap not 
less than 172 inches (38 mm) between joints in courses, and 
no two joints in any three adjacent courses shall be in direct 
alignment. Spacing between shingles shall not be less than 74 
inch to Vg inch (6 mm to 10 mm). Weather exposure for wood 
shingles shall not exceed those set in Table R905.7.5. Fasten- 
ers for wood shingles shall be corrosion resistant with a mini- 



294 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF ASSEMBLIES 



mum penetration of '/2 inch (13 mm) into the sheathing. For 
sheathing less than V2 inch (13 mm) in thickness, the fasteners 
shall extend through the sheathing. Wood shingles shall be 
attached to the roof with two fasteners per shingle, positioned 
no more than V4 inch (19 mm) from each edge and no more 
than 1 inch (25 mm) above the exposure Hne. 

TABLE R905.7.5 
WOOD SHINGLE WEATHER EXPOSURE AND ROOF SLOPE 



ROOFING 
MATERIAL 


LENGTH 
(inches) 


GRADE 


EXPOSURE (inches) 


3:12 pitch to 
<4:12 


4:12 pitch or 
steeper 


Shingles of 
naturally durable 
wood 


16 


No. 1 J 


3% 


5 


No. 2 


3% 


4 


No. 3 


3 


3% 


18 


No. 1 


4V4 


5% 


No. 2 


4 


A\ 


No. 3 


3% 


4 


24 


No. 1 


5% 


1\ 


No. 2 


5\ 


6V2 


No. 3 


5 


5V2 



For SI: 1 inch = 25.4 mm. 

R905.7.6 Valley flashing. Roof flashing shall be not less 
than No. 26 gage [0.019 inches (0.5 mm)] corrosion-resis- 
tant sheet metal and shall extend 10 inches (254 nam) from 
the centerline each way for roofs having slopes less than 12 
units vertical in 12 units horizontal (100-percent slope), and 
7 inches (178 mm) from the centerline each way for slopes 
of 12 units vertical in 12 units horizontal and greater. Sec- 
tions of flashing shall have an end lap of not less than 4 
inches (102 mm). 

R905.7.7 Label required. Each bundle of shingles shall be 
identified by a label of an approved grading or inspection 
bureau or agency. 

R905.8 Wood shakes. The installation of wood shakes shall 
comply with the provisions of this section. 

R905.8.1 Deck requirements. Wood shakes shall be used 
only on solid or spaced sheathing. Where spaced sheathing is 
used, sheathing boards shall not be less than 1-inch by 4-inch 
(25 mm by 102 mm) nominal dimensions and shall be spaced 
on centers equal to the weather exposure to coincide with the 
placement of fasteners. Where 1-inch by 4-inch (25 mm by 
102 mm) spaced sheathing is installed at 10 inches (254 mm) 
on center, additional 1-inch by 4-inch (25 mm by 102 mm) 
boards shall be installed between the sheathing boards. 

R905.8.1.1 Solid sheathing required. In areas where 
the average daily temperature in January is 25 °F (-4°C) 
or less, solid sheathing is required on that portion of the 
roof requiring an ice barrier. 

R905.8.2 Deck slope. Wood shakes shall only be used on 
slopes of three units vertical in 12 units horizontal (25-per- 
cent slope) or greater. 



R905.8.3 Underlayment. Underlayment shall comply 
with ASTM D 226, Type I or ASTM D 4869, Type I or II. 

R905.8.3.1 Ice barrier. In areas where there has been a 
history of ice forming along the eaves causing a backup 
of water as designated in Table R301 .2(1), an ice barrier 
that consists of at least two layers of underlayment 
cemented together or a self-adhering polymer modified 
bitumen sheet shall be used in place of normal 
underlayment and extend from the lowest edges of all 
roof surfaces to a point at least 24 inches (610 mm) 
inside the exterior wall line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

R905.8.4 Interlayment. Interlayment shall comply with 
ASTM D 226, Type I. 

R905.8.5 Material standards. Wood shakes shall comply 
with the requirements of Table R905.8.5. 

TABLE R905.8.5 
WOOD SHAKE MATERIAL REQUIREMENTS 



IMATERiAL 


lUIINilUIUiVI 
GRADES 


APPLICABLE GRADING 
RULES 


Wood shakes of naturally 
durable wood 


1 


Cedar Shake and 
Shingle Bureau 


Taper sawn shakes of naturally 
durable wood 


lor 2 


Cedar Shake and 
Shingle Bureau 


Preservative-treated shakes 
and shingles of naturally 
durable wood 


1 


Cedar Shake and 
Shingle Bureau 


Fire-retardant-treated shakes 
and shingles of naturally 
durable wood 


1 


Cedar Shake and 
Shingle Bureau 


Preservative-treated taper sawn 
shakes of Southern pine 
treated in accordance with 
AWPA Standard Ul 
(Commodity Specification 
A, Use Category 3B and 
Section 5.6) 


lor 2 


Forest Products 
Laboratory of the 
Texas Forest 
Services 



R905.8.6 Application. Wood shakes shall be installed 
according to this chapter and the manufacturer's installa- 
tion instructions. Wood shakes shall be laid with a side lap 
not less than VI 2 inches (38 mm) between joints in adja- 
cent courses. Spacing between shakes in the same course 
shall be Vg inch to Vg inch (3 mm to 16 mm) for shakes and 
tapersawn shakes of naturally durable wood and shall be 
'/4 inch to Vg inch (6 mm to 10 mm) for preservative treated 
taper sawn shakes. Weather exposure for wood shakes 
shall not exceed those set forth in Table R905.8.6. Fasten- 
ers for wood shakes shall be corrosion-resistant, with a 
minimum penetration of V2 inch (12.7 mm) into the 
sheathing. For sheathing less than V2 inch (12.7 mm) in 
thickness, the fasteners shall extend through the sheath- 
ing. Wood shakes shall be attached to the roof with two 
fasteners per shake, positioned no more than 1 inch (25 
mm) from each edge and no more than 2 inches (5 1 mm) 
above the exposure line. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



295 



ROOF ASSEMBLIES 



R905.8.7 Shake placement. The starter course at the eaves 
shall be doubled and the bottom layer shall be either 15-inch 
(381 mm), 18-inch (457 mm) or 24-inch (610 mm) wood 
shakes or wood shingles. Fifteen-inch (381 mm) or 18-inch 
(457 mm) wood shakes may be used for the final course at 
the ridge. Shakes shall be interlaid with 18-inch- wide (457 
mm) strips of not less than No. 30 felt shingled between 
each course in such a manner that no felt is exposed to the 
weather by positioning the lower edge of each felt strip 
above the butt end of the shake it covers a distance equal to 
twice the weather exposure. 

TABLE Rg05.8.6 
WOOD SHAKE WEATHER EXPOSURE AND ROOF SLOPE 



ROOFING MATERIAL 


LENGTH 
(inches) 


GRADE 


EXPOSURE (inches) 


4:12 pitch or steeper 


Shakes of naturally durable 
wood 


18 


No. 1 


7V, 


24 


No. 1 


10^ 


Preservative-treated taper 
sawn shakes of Southern 
Yellow Pine 


18 


No. 1 


VI, 


24 


No. 1 


10 


18 


No. 2 


5V, 


24 


No. 2 


7V, 


Taper-sawn shakes of 
naturally durable wood 


18 


No. 1 


1\ 


24 


No. 1 


10 


18 


No. 2 


5V, 


24 


No. 2 


1% 



For SI: 1 inch = 25.4 mm. 

a. For 24-inch by Vg-inch handsplit shakes, the maximum exposure is 7 Vj inches. 

R905.8.8 Valley flashing. Roof valley flashing shall not be 
less than No. 26 gage [0.019 inch (0.5 mm)] corrosion-resis- 
tant sheet metal and shall extend at least 1 1 inches (279 mm) 
from the centerline each way. Sections of flashing shall have 
an end lap of not less than 4 inches (102 mm). 

R905.8.9 Label required. Each bundle of shakes shall be 
identified by a label of an approved grading or inspection 
bureau or agency. 

R905.9 Built-up roofs. The installation of built-up roof s shall 
comply with the provisions of this section. 

R905.9.1 Slope. Built-up roofs shall have a design slope of 
a minimum of one-fourth unit vertical in 12 units horizon- 
tal (2-percent slope) for drainage, except for coal-tar 
built-up roofs, which shall have a design slope of a mini- 
mum one- eighth unit vertical in 12 units horizontal (1 -per- 
cent slope). 



R905.9.2 Material standards. Built-up roof covering mate- 
rials shall comply with the standards in Table R905.9.2. 

R905.9.3 Application. Built-up roofs shall be installed 
according to this chapter and the manufacturer's installation 
instructions. 

R905.10 Metal roof panels. The installation of metal roof 
panels shall comply with the provisions of this section. 

R905.10.1 Deck requirements. Metal roof panel roof cov- 
erings shall be applied to sohd or spaced sheathing, except 
where the roof covering is specifically designed to be 
applied to spaced supports. 

R905.10.2 Slope. Minimum slopes for metal roof panels 
shall comply with the following: 

1. The minimum slope for lapped, nonsoldered-seam 
metal roofs without appUed lap sealant shall be three 
units vertical in 12 units horizontal (25-percent slope). 

2. The minimum slope for lapped, nonsoldered-seam 
metal roofs with applied lap sealant shall be one-half 
vertical unit in 12 units horizontal (4-percent slope). 
Lap sealants shall be applied in accordance with the 
approved manufacturer's installation instructions. 

3. The minimum slope for standing-seam roof systems 
shall be one-quarter unit vertical in 12 units horizon- 
tal (2-percent slope). 

R905.10.3 Material standards. Metal-sheet roof covering 
systems that incorporate supporting structural members 
shall be designed in accordance with the International 
Building Code. Metal-sheet roof coverings installed over 
structural decking shall comply with Table R905. 10.3(1). 
The materials used for metal-sheet roof coverings shall be 
naturally corrosion resistant or provided with corrosion 
resistance in accordance with the standards and minimum 
thicknesses shown in Table R905. 10.3(2). 

R905.10.4 Attachment. Metal roof panels shall be secured 
to the supports in accordance with this chapter and the man- 
ufacturer's installation instructions. In the absence of manu- 
facturer's installation instructions, the following fasteners 
shall be used: 

1. Galvanized fasteners shall be used for steel roofs. 

2. Three hundred series stainless steel fasteners shall be 
used for copper roofs. 

3. Stainless steel fasteners are acceptable for metal 
roofs. 

R905.il Modified bitumen roofing. The installation of modi- 
fied bitumen roofing shall comply with the provisions of this 
section. 



296 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ROOF ASSEMBLIES 



TABLE Rg05.9.2 
BUILT-UP ROOFING MATERIAL STANDARDS 



MATERIAL STANDARD 


STANDARD 


Acrylic coatings used in roofing 


ASTM D 6083 


Aggregate surfacing 


ASTMD1863 


Asphalt adhesive used in roofing 


ASTM D 3747 


Asphalt cements used in roofing 


ASTM D 3019; D 2822; D 4586 


Asphalt-coated glass fiber base sheet 


ASTM D 4601 


Asphalt coatings used in roofing 


ASTM D 1227; D 2823; D 2824; D 4479 


Asphalt glass felt 


ASTM D 2178 


Asphalt primer used in roofing 


ASTM D 41 


Asphalt-saturated and asphalt-coated organic felt base sheet 


ASTM D 2626 


Asphalt-saturated organic felt (perforated) 


ASTM D 226 


Asphalt used in roofing 


ASTM D 312 


Coal tar cements used in roofing 


ASTM D 4022; D 5643 


Coal-tar primer used in roofing, dampproofing and waterproofing 


ASTM D 43 


Coal-tar saturated organic felt 


ASTM D 227 


Coal-tar used in roofing 


ASTM D 450, Types I or II 


Glass mat, coal tar 


ASTM D 4990 


Glass mat, venting type 


ASTM D 4897 


Mineral- surfaced inorganic cap sheet 


ASTM D 3909 


Thermoplastic fabrics used in roofing 


ASTM D 5665; D 5726 



TABLE R905.1 0.3(1) 
METAL ROOF COVERINGS STANDARDS 



ROOF COVERING TYPE 


STANDARD APPLICATION RATE^-HICKNESS 


Galvanized Steel 


ASTM A 653 G90 Zinc Coated 


Stainless Steel 


ASTM A 240, 300 Series Alloys 


Steel 


ASTM A 924 


Lead-coated Copper 


ASTM B 101 


Cold Rolled Copper 


ASTM B 370 minimum 16 oz/square ft and 12 oz/square ft high yield copper for 
metal-sheet roof-covering systems; 12 oz/square ft for preformed metal shingle 
systems. 


Hard Lead 


2 lb/ sq ft 


Soft Lead 


3 lb/ sq ft 


Aluminum 


ASTM B 209, 0.024 minimum thickness for roUformed panels and 0.019 inch 
minimum thickness for pressformed shingles. 


Terne (tin) and terne-coated stainless 


Terne coating of 40 lb per double base box, field painted where applicable in 
accordance with manufacturer's installation instructions. 


Zinc 


0.027 inch minimum thickness: 99.995% electrolytic high grade zinc with alloy 
additives of copper (0.08 - 0.20%), titanium (0.07% - 0.12%) and aluminum 
(0.015%). 



For SI: 1 ounce per square foot = 0.305 kg/m^, 1 pound per square foot = 4.214 kg/nf , 1 inch = 25.4 mm, 1 pound == 0.454 kg. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



297 



ROOF ASSEMBLIES 



TABLE R905.1 0.3(2) 
MINIMUM CORROSION RESISTANCE 



55% Aluminum-zinc alloy 
coated steel 


ASTM A 792 AZ 50 


5% aluminum alloy-coated steel 


ASTM A 875 GF60 


Aluminum-coated steel 


ASTM A 463 T2 65 


Galvanized steel 


ASTM A 653 G-90 


Prepainted steel 


ASTM A 755^^ 



a. Paint systems in accordance with ASTM A 755 shall be applied over steel 
products with corrosion-resistant coatings complying with ASTM A 792, 
ASTM A 875, ASTM A 463, or ASTM A 653. 

R905.11.1 Slope. Modified bitumen membrane roofs shall 
have a design slope of a minimum of one-fourth unit vertical 
in 12 units horizontal (2-percent slope) for drainage. 

R905.11.2 Material standards. Modified bitumen roof 
coverings shall comply with the standards in Table 
R905.11.2. 

TABLE R905.1 1.2 
MODIFIED BITUMEN ROOFING MATERIAL STANDARDS 



MATERIAL 


STANDARD 


Acrylic coating 


ASTM D 6083 


Asphalt adhesive 


ASTM D 3747 


Asphalt cement 


ASTM D 3019 


Asphalt coating 


ASTM D 1227; D 2824 


Asphalt primer 


ASTM D 41 


Modified bitumen roof 
membrane 


ASTM D 6162; D 6163; D 6164; 
D 6222; D 6223; D 6298; 
CGSB 37-56M 



R905.11.3 Application. Modified bitumen roofs shall be 
installed according to this chapter and the manufacturer's 
installation instructions. 

R905.12 Thermoset single-ply roofing. The installation of 
thermoset single-ply roofing shall comply with the provisions 
of this section. 

R905.12.1 Slope. Thermoset single-ply membrane roofs 
shall have a design slope of a minimum of one-fourth unit 
vertical in 12 units horizontal (2-percent slope) for drain- 
age. 

R905.12.2 Material standards. Thermoset single-ply roof 
coverings shall comply with ASTM D 4637, ASTM D 5019 
or CGSB 37-GP-52M. 

R905.12.3 Application. Thermoset single-ply roofs shall 
be installed according to this chapter and the manufacturer's 
installation instructions. 

R905.13 Thermoplastic single-ply roofing. The installation 
of thermoplastic single-ply roofing shall comply with the pro- 
visions of this section. 

R905.13.1 Slope. Thermoplastic single-ply membrane 
roofs shall have a design slope of a minimum of one-fourth 
unit vertical in 12 units horizontal (2-percent slope). 



R905.13.2 Material standards. Thermoplastic single-ply 
roof coverings shall comply with ASTM D 4434, ASTM D I 
6754, ASTM D 6878, or CAN/CGSB 37.54. | 

R905.13.3 Application. Thermoplastic single-ply roofs 
shall be installed according to this chapter and the manufac- 
turer's installation instructions. 

R905.14 Sprayed polyurethane foam roofing. The installa- 
tion of sprayed polyurethane foam roofing shall comply with 
the provisions of this section. 

R905.14.1 Slope. Sprayed polyurethane foam roofs shall 
have a design slope of a minimum of one-fourth unit vertical 
in 12 units horizontal (2-percent slope) for drainage. 

R905.14.2 Material standards. Spray-applied polyure- 
thane foam insulation shall comply with ASTM C 1029. 

R905.14.3 Application. Foamed-in-place roof insulation 
shall be installed in accordance with this chapter and the 
manufacturer's installation instructions. A liquid-applied 
protective coating that complies with Section R905. 15 shall 
be applied no less than 2 hours nor more than 72 hours fol- 
lowing the application of the foam. 

R905.14.4 Foam plastics. Foam plastic materials and 
installation shall comply with Section R314. 

R905.15 Liquid-applied coatings. The installation of liquid- 
apphed coatings shall comply with the provisions of this section. 

R905.15.1 Slope. Liquid-applied roofs shall have a design 
slope of a minimum of one-fourth unit vertical in 12 units 
horizontal (2-percent slope). 

R905.15.2 Material standards. Liquid-appHed roof coat- 
ings shall comply with ASTM C 836, C 957, D 1227, D I 
3468, D 6083 or D 6694. | 

R905.15.3 Application. Liquid-applied roof coatings shall 
be installed according to this chapter and the manufacturer's 
installation instructions. 



SECTION R906 
ROOF INSULATION 

R906.1 General. The use of above-deck thermal insulation 
shall be permitted provided such insulation is covered with an 
approved roof covering and passes FM 4450 or UL 1256. 

R906.2 Material standards. Above-deck thermal insulation 
board shall comply with the standards in Table R906.2. 

TABLE R906.2 
MATERIAL STANDARDS FOR ROOF INSULATION 



Cellular glass board 


ASTM C 552 


Composite boards 


ASTM C 1289, Type HI, IV, V, or 
VI 


Expanded polystyrene 


ASTM C 578 


Extruded polystyrene board 


ASTM C 578 


Perlite Board 


ASTM C 728 


Polyisocyanurate Board 


ASTM C 1289, Type I or Type II 


Wood fiberboard 


ASTM C 208 



298 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



ROOF ASSEMBLIES 



SECTION R907 
REROOFING 

R907.1 General. Materials and methods of application used 
for re-covering or replacing an existing roof covering shall 
comply with the requirements of Chapter 9. 

Exception: Reroofing shall not be required to meet the min- 
imum design slope requirement of one-quarter unit vertical 
in 12 units horizontal (2-percent slope) in Section R905 for 
roofs that provide positive roof drainage. 

R907.2 Structural and construction loads. The structural 
roof components shall be capable of supporting the roof cover- 
ing system and the material and equipment loads that will be 
encountered during installation of the roof covering system. 

R907.3 Re-covering versus replacement. New roof cover- 
ings shall not be installed without first removing existing rbof 
coverings where any of the following conditions occur: 

1 . Where the existing roof or roof covering is water-soaked 
or has deteriorated to the point that the existing roof or 
roof covering is not adequate as a base for additional 
roofing. 

2. Where the existing roof covering is wood shake, slate, 
clay, cement or asbestos-cement tile. 

3. Where the existing roof has two or more applications of 
any type of roof covering. 

4. For asphalt shingles, when the building is located in an 
area subject to moderate or severe hail exposure accord- 
ing to Figure R903.5. 

Exceptions: 

1. Complete and separate roofing systems, such as 
standing-seam metal roof systems, that are designed 
to transmit the roof loads directly to the building's 
structural system and that do not rely on existing roofs 
and roof coverings for support, shall not require the 
removal of existing roof coverings. 

2. Installation of metal panel, metal shingle, and con- 
crete and clay tile roof coverings over existing wood 
shake roofs shall be permitted when the application is 
in accordance with Section R907.4. 

3. The application of new protective coating over exist- 
ing spray polyurethane foam roofing systems shall be 
permitted without tear-off of existing roof coverings. 

R907.4 Roof recovering. Where the application of a new roof 
covering over wood shingle or shake roofs creates a combusti- 
ble concealed space, the entire existing surface shall be covered 
with gypsum board, mineral fiber, glass fiber or other approved 
materials securely fastened in place. 

R907.5 Reinstallation of materials. Existing slate, clay or 
cement tile shall be permitted for reinstallation, except that 
damaged, cracked or broken slate or tile shall not be reinstalled. 
Existing vent flashing, metal edgings, drain outlets, collars and 
metal counterflashings shall not be reinstalled where rusted. 



damaged or deteriorated. Aggregate surfacing materials shall 
not be reinstalled. 

R907.6 Flashings. Flashings shall be reconstructed in accor- 
dance with approved manufacturer's installation instructions. 
Metal flashing to which bituminous materials are to be adhered 
shall be primed prior to installation. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



299 



300 2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 10 

CHIMNEYS AND FIREPLACES 



SECTION R1001 

I MASONRY FIREPLACES 

RlOOl.l General. Masonry fireplaces shall be constructed in 
accordance with this section and the applicable provisions of 
Chapters 3 and 4. 

R1001.2 Footings and foundations. Footings for masonry 
fireplaces and their chimneys shall be constructed of concrete 
or solid masonry at least 12 inches (305 mm) thick and shall 
extend at least 6 inches (152 mm) beyond the face of the fire- 
place or foundation wall on all sides. Footings shall be founded 
on natural, undisturbed earth or engineered fill below frost 
depth. In areas not subjected to freezing, footings shall be at 
least 12 inches (305 mm) below finished grade. 

RlOOl.2.1 Ash dump cleanout. Cleanout openings located 
within foundation walls below fireboxes, when provided, 
shall be equipped with ferrous metal or masonry doors and 
frames constructed to remain tightly closed except when in 
use. Cleanouts shall be accessible and located so that ash 
removal will not create a hazard to combustible materials. 

R1001.3 Seismic reinforcing. Masonry or concrete chimneys 

I in Seismic Design Category Dq, Dj or D2 shall be reinforced. 
Reinforcing shall conform to the requirements set forth in 
Table RlOOl.l and Section R609, Grouted Masonry. 

RlOOl.3.1 Vertical reinforcing. For chimneys up to 40 
inches (1016 mm) wide, four No. 4 continuous vertical bars 
shall be placed between wythes of solid masonry or within 
the cells of hollow unit masonry and grouted in accordance 
with Section R609. Grout shall be prevented from bonding 
with the flue liner so that the flue liner is free to move with 
thermal expansion. For chimneys more than 40 inches 
(1016 mm) wide, two additional No. 4 vertical bars shall be 
provided for each additional flue incorporated into the 
chimney or for each additional 40 inches (1016 mm) in 
width or fraction thereof. 

RlOOl.3.2 Horizontal reinforcing. Vertical reinforcement 
shall be placed within V4-inch (6 mm) ties, or other reinforc- 
ing of equivalent net cross-sectional area, placed in the bed 
joints according to Section R607 at a minimum of every 18 
inches (457 mm) of vertical height. Two such ties shall be 
installed at each bend in the vertical bars. 

IR1001.4 Seismic anchorage. Masonry or concrete chimneys 
in Seismic Design Categories Dq, Dj or D2 shall be anchored at 
each floor, ceiling or roof line more than 6 feet (1829 mm) 
above grade, except where constructed completely within the 
exterior walls. Anchorage shall conform to the requirements of 
Section RlOOl.4.1. 

RlOOl.4.1 Anchorage. Two Vig-inch by 1-inch (5 mm by 25 
mm) straps shall be embedded a minimum of 12 inches (305 
mm) into the chimney. Straps shall be hooked around the outer 
bars and extend 6 inches (152 mm) beyond the bend. Each 
strap shall be fastened to a minimum of four floor ceiUng or 
floor joists or rafters with two Vj-inch (13 mm) bolts. 



R1001.5 Firebox walls. Masonry fireboxes shall be con- 
structed of solid masonry units, hollow masonry units grouted 
solid, stone or concrete. When a lining of firebrick at least 2 
inches (5 1 mm) thick or other approved lining is provided, the 
minimum thickness of back and side walls shall each be 8 
inches (203 mm) of solid masonry, including the lining. The 
width of joints between firebricks shall not be greater than 74 
inch (6 mm). When no lining is provided, the total minimum 
thickness of back and side walls shall be 10 inches (254 mm) of 
solid masonry. Firebrick shall conform to ASTM C 27 or C 
1261 and shall be laid with medium duty refractory mortar con- 
forming to ASTM C 199. 

RlOOl.5.1 Steel fireplace units. Installation of steel fire- 
place units with solid masonry to form a masonry fireplace 
is permitted when installed either according to the require- 
ments of their listing or according to the requirements of this 
section. Steel fireplace units incorporating a steel firebox 
lining, shall be constructed with steel not less than 74 inch (6 
mm) thick, and an air circulating chamber which is ducted to 
the interior of the building. The firebox lining shall be 
encased with solid masonry to provide a total thickness at 
the back and sides of not less than 8 inches (203 mm), of 
which not less than 4 inches (102 mm) shall be of solid 
masonry or concrete. Circulating air ducts used with steel 
fireplace units shall be constructed of metal or masonry. 

R1001.6 Firebox dimensions. The firebox of a concrete or 
masonry fireplace shall have a minimum depth of 20 inches 
(508 mm). The throat shall not be less than 8 inches (203 mm) 
above the fireplace opening. The throat opening shall not be 
less than 4 inches (102 mm) deep. The cross-sectional area of 
the passageway above the firebox, including the throat, damper 
and smoke chamber, shall not be less than the cross-sectional 
area of the flue. 

Exception: Rumford fireplaces shall be permitted provided 
that the depth of the fireplace is at least 12 inches (305 mm) 
and at least one-third of the width of the fireplace opening, 
that the throat is at least 12 inches (305 mm) above the lintel 
and is at least 72o the cross-sectional area of the fireplace 
opening. 

R1001.7 Lintel and throat. Masonry over a fireplace opening 
shall be supported by a lintel of noncombustible material. The 
minimum required bearing length on each end of the fireplace 
opening shall be 4 inches (102 mm). The fireplace throat or 
damper shall be located a minimum of 8 inches (203 mm) 
above the lintel. 

RlOOl.7.1 Damper. Masonry fireplaces shall be equipped 
with a ferrous metal damper located at least 8 inches (203 
mm) above the top of the fireplace opening. Dampers shall 
be installed in the fireplace or the chimney venting the fire- 
place, and shall be operable from the room containing the 
fireplace. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



301 



CHIMNEYS AND FIREPLACES 



TABLE R1 001.1 
SUMMARY OF REQUIREMENTS FOR MASONRY FIREPLACES AND CHIMNEYS 



ITEM 


LETTERS 


REQUIREMENTS 


Hearth slab thickness 


A 


4" 


Hearth extension 

(each side of opening) 


B 


8" fireplace opening < 6 square foot. 
12" fireplace opening > 6 square foot. 


Hearth extension 
(front of opening) 


C 


16" fireplace opening < 6 square foot. 
20" fireplace opening > 6 square foot. 


Hearth slab reinforcing 


D 


Reinforced to carry its own weight and all imposed loads. 


Thickness of wall of firebox 


E 


10" solid brick or 8" where a firebrick lining is used. Joints in 
firebrick V4" maximum. 


Distance from top of opening to throat 


F 


8" 


Smoke chamber wall thickness 
Unlined walls 


G 


6" 

8" 


Chimney 

Vertical reinforcing'' 


H 


Four No. 4 full-length bars for chimney up to 40" wide. Add two 
No. 4 bars for each additional 40" or fraction of width or each 
additional flue. 


Horizontal reinforcing 


J 


V4" ties at 18" and two ties at each bend in vertical steel. 


Bond beams 


K 


No specified requirements. 


Fireplace lintel 


L 


Noncombustible material. 


Chimney walls with flue lining 


M 


SoUd masonry units or hollow masonry units grouted solid with 
at least 4 inch nominal thickness. 


Distances between adjacent flues 


— 


See Section R1003.13. 


Effective flue area (based on area of fireplace opening) 


P 


See Section R1003. 15. 


Clearances: 

Combustible material 
Mantel and trim 
Above roof 


R 


See Sections RlOOl.ll and R1003.18. 
See Section RlOOl.l 1, Exception 4. 
3' at roofline and 2' at 10'. 


Anchorage'' 

Strap 

Number 

Embedment into chimney 
Fasten to 
Bolts 


S 


V'xl" 

Two 

12" hooked around outer bar with 6" extension. 

4 joists 

Two '/j" diameter. 


Footing 
Thickness 
Width 


T 


12"min. 

6" each side of fireplace wall. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m^. 

NOTE: This table provides a summary of major requirements for the construction of masonry chimneys and fireplaces. Letter references are to Figure RlOOl.l, 

which shows examples of typical construction. This table does not cover all requirements, nor does it cover all aspects of the indicated requirements. For the actual 

mandatory requirements of the code, see the indicated section of text. 

a. The letters refer to Figure RlOOl.l. 

b. Not required in Seismic Design Category A, B or C. 



302 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



CHIMNEYS AND FIREPLACES 



(g) BONO BEAM . 
MORTOH CAP 



ftp is • — It ^- srr -■- 

IL-LL bM_JI 



■ a FT MiN. 



/3\ EFFECTIVE 
Viy FLUE W^EA 

(g) BOND SEAM >^/ 



FLUE UNiNG 



(R) BONDffiAM^/ 

©HORIZONTAL J 

REINFORCINSTiESs'^ 



RBNFORCING TIES 



® 



(^FOOTING WIDTH ■ 




@WAaTHICKN^Sv f/ 
^^ PARSE WtW >^ 

NCtRTAR 



l^ SMOKE 

VS/ CHAMBER vJ/ 



VeRTiCM. 

REINF0FK31NQ 



.FIREBOX WALL ^ 
' THICKNESS \^ 

HEARTH 20 IN. 
Mm. FIRffiRICK 



©HEARTH SLAB — i 
THICKNESS ±_ 



^H DUMP OPTIONAL- 
CLEAN OUT 



BBNFORCiNG TIES 
VslN.MIN. 
4 IN, THICK MASONRY UNITS 



/rjv VERTICAL RBNFORCING 
4 ■— Vty ao IN. LAP IF SPLICED TO 



mi¥m_j> 



BARS IN CONCRETE-' 
FCWTING 



' HEARTH 20 IN. MIN. 



BRICK FIREBOX AND CHIMNEY- 
SECTIONAL SIDE VIEW ON WOOD FLOOR 



BRICK FIREBOX AND BLCCK CHIMNEY- 
SECTIONAL SIDE VIEW ON CONCRETE SLAB 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



FIGURE R1001.1 
FIREPLACE AND CHIMNEY DETAILS 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



303 



CHIMNEYS AND FIREPLACES 



R1001.8 Smoke chamber. Smoke chamber walls shall be con- 
structed of solid masonry units, hollow masonry units grouted 
solid, stone or concrete. Corbelling of masonry units shall not 
leave unit cores exposed to the inside of the smoke chamber. 
When a lining of firebrick at least 2 inches (5 1 mm) thick, or a 
hning of vitrified clay at least Vg inch (16 mm) thick, is pro- 
vided, the total minimum thickness of front, back and side 
walls shall be 6 inches (152 mm) of solid masonry, including 
the hning. Firebrick shall conform to ASTM C 27 or C 1261 
and shall be laid with medium duty refractory mortar conform- 
ing to ASTM C 199. Where no lining is provided, the total min- 
imum thickness of front, back and side walls shall be 8 inches 
(203 mm) of solid masonry. When the inside surface of the 
smoke chamber is formed by corbeled masonry, the inside sur- 
face shall be parged smooth. 

RlOOl.8.1 Smoke chamber dimensions. The inside height 
of the smoke chamber from the fireplace throat to the begin- 
ning of the flue shall not be greater than the inside width of 
the fireplace opening. The inside surface of the smoke 
chamber shall not be inclined more than 45 degrees (0.79 
rad) from vertical when prefabricated smoke chamber lin- 
ings are used or when the smoke chamber walls are rolled or 
sloped rather than corbeled. When the inside surface of the 
smoke chamber is formed by corbeled masonry, the walls 
shall not be corbeled more than 30 degrees (0.52 rad) from 
vertical. 

R1001.9 Hearth and hearth extension. Masonry fireplace 
hearths and hearth extensions shall be constructed of concrete 
or masonry, supported by noncombustible materials, and rein- 
forced to carry their own weight and all imposed loads. No 
combustible material shall remain against the underside of 
hearths and hearth extensions after construction. 

RlOOl.9.1 Hearth thickness. The minimum thickness of 
fireplace hearths shall be 4 inches (102 mm). 

RlOOl.9.2 Hearth extension thickness. The minimum 
thickness of hearth extensions shall be 2 inches (51 mm). 



Exception: When the bottom of the firebox opening is 
raised at least 8 inches (203 mm) above the top of the 
hearth extension, a hearth extension of not less than 
Vg-inch-thick (10 mm) brick, concrete, stone, tile or other 
approved noncombustible material is penmitted. 

RlOOl.lO Hearth extension dimensions. Hearth extensions 
shall extend at least 1 6 inches (406 mm) in front of and at least 8 
inches (203 mm) beyond each side of the fireplace opening. 
Where the fireplace opening is 6 square feet (0,6 m^) or larger, 
the hearth extension shall extend at least 20 inches (508 mm) in 
front of and at least 12 inches (305 mm) beyond each side of the 
fireplace opening. 

RlOOl.ll Fireplace clearance. All wood beams, joists, studs 
and other combustible material shall have a clearance of not 
less than 2 inches (51 mm) from the front faces and sides of 
masonry fireplaces and not less than 4 inches (102 mm) from 
the back faces of masonry fireplaces. The air space shall not be 
filled, except to provide fire blocking in accordance with Sec- 
tion RlOOl. 12. 

Exceptions: 

1. Masonry fireplaces listed and labeled for use in con- 
tact with combustibles in accordance with UL 127 
and installed in accordance with the manufacturer's 
installation instructions are permitted to have com- 
bustible material in contact with their exterior sur- 
faces. 

2. When masonry fireplaces are part of masonry or con- 
crete walls, combustible materials shall not be in con- 
tact with the masonry or concrete walls less than 12 
inches (306 mm) from the inside surface of the nearest 
firebox lining. 

3. Exposed combustible trim and the edges of sheathing 
materials such as wood siding, flooring and drywall 
shall be permitted to abut the masonry fireplace side 
walls and hearth extension in accordance with Figure 
RlOOl . 11 , provided such combustible trim or sheath- 



MASONRY 




COMBUSTIBLE SHEATHING 
EDGE ABUTTING MASONRY 
12IN. MIN. FROM FIREBOX 



FRAME WALL 



2 IN. CLEARANCE (AIR SPACE) 
TO COMBUSTIBLE FRAMING 



WOOD MANTEL 



For SI: 1 inch = 25.4 mm. 



FIGURE R1001.11 
CLEARANCE FROM COMBUSTIBLES 



304 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHIMNEYS AND FIREPLACES 



ing is a minimum of 12 inches (305 mm) from the 
inside surface of the nearest firebox Hning. 

4. Exposed combustible mantels or trim may be placed 
directly on the masonry fireplace front surrounding 
the fireplace opening providing such combustible 
materials are not placed within 6 inches (152 mm) of a 
fireplace opening. Combustible material within 12 
inches (306 mm) of the fireplace opening shall not 
project more than Vg inch (3 mm) for each 1-inch (25 
mm) distance from such an opening. 

R1001.12 Fireplace fireblocking. Fireplace fireblocking 
shall comply with the provisions of Section R602.8. 



SECTION R1002 
MASONRY HEATERS 

R1002.1 Definition. A masonry heater is a heating appliance 
constructed of concrete or soUd masonry, hereinafter referred 
to as masonry, which is designed to absorb and store heat from 
a solid-fuel fire built in the firebox by routing the exhaust gases 
through internal heat exchange channels in which the flow path 
downstream of the firebox may include flow in a horizontal or 
downward direction before entering the chimney and which 
delivers heat by radiation from the masonry surface of the 
heater. 

R1002.2 Installation. Masonry heaters shall be installed in 
accordance with this section and comply with one of the fol- 
lowing: 

1 . Masonry heaters shall comply with the requirements of 
ASTME1602;or 

2. Masonry heaters shall be listed and labeled in accor- 
dance with UL 1482 and installed in accordance with the 
manufacturer's installation instructions. 

R1002.3 Footings and foundation. The firebox floor of a 
masonry heater shall be a minimum thickness of 4 inches (102 
mm) of noncombustible material and be supported on a 
noncombustible footing and foundation in accordance with 
Section R1003.2. 

R1002.4 Seismic reinforcing. In Seismic Design Categories 
Dq, Dj and D2, masonry heaters shall be anchored to the 
masonry foundation in accordance with Section R1003.3. 
Seismic reinforcing shall not be required within the body of a 
masonry heater whose height is equal to or less than 3.5 times 
it's body width and where the masonry chimney serving the 
heater is not supported by the body of the heater. Where the 
masonry chimney shares a common wall with the facing of the 
masonry heater, the chimney portion of the structure shall be 
reinforced in accordance with Section R1003. 

R1002.5 Masonry heater clearance. Combustible materials 
shall not be placed within 36 inches (914 mm) of the outside 
surface of a masonry heater in accordance with NFPA 211 Sec- 
tion 8-7 (clearances for solid-fuel-buming appliances), and the 
required space between the heater and combustible material 
shall be fully vented to permit the free flow of air around all 
heater surfaces. 



Exceptions: 

1 . When the masonry heater wall is at least 8 inches (203 
mm) thick of solid masonry and the wall of the heat 
exchange channels is at least 5 inches (127 mm) thick 
of solid masonry, combustible materials shall not be 
placed within 4 inches (102 mm) of the outside sur- 
face of a masonry heater. A clearance of at least 8 
inches (203 mm) shall be provided between the 
gas-tight capping slab of the heater and a combustible 
ceiling. 

2. Masonry heaters tested and listed by an American 
National Standards Association (ANSI)-accredited 
laboratory to the requirements of UL1482 may be 
installed in accordance with the listing specifications 
and the manufacturer's written instructions. 



SECTION R1003 
MASONRY CHIMNEYS 

R1003.1 Definition. A masonry chimney is a chimney con- 
structed of concrete or masonry, hereinafter referred to as 
masonry. Masonry chimneys shall be constructed, anchored, 
supported and reinforced as required in this chapter. 

R1003.2 Footings and foundations. Footings for masonry 
chimneys shall be constructed of concrete or solid masonry at 
least 12 inches (305 mm) thick and shall extend at least 6 inches 
(152 mm) beyond the face of the foundation or support wall on 
all sides. Footings shall be founded on natural undisturbed 
earth or engineered fill below frost depth. In areas not subjected 
to freezing, footings shall be at least 12 inches (305 mm) below 
finished grade. 

R1003.3 Seismic reinforcing. Masonry or concrete chimneys 
shall be constructed, anchored, supported and reinforced as 
required in this chapter. In Seismic Design Category Dq, D, or 
D2 masonry and concrete chimneys shall be reinforced and 
anchored as detailed in Section R1003.3.1, R1003.3.2 and 
R1003.4. In Seismic Design Category A, B or C, reinforcement 
and seismic anchorage is not required. 

R1003.3.1 Vertical reinforcing. For chimneys up to 40 
inches (1016 mm) wide, four No. 4 continuous vertical bars, 
anchored in the foundation, shall be placed in the concrete, 
or between wythes of solid masonry, or within the cells of 
hollow unit masonry, and grouted in accordance with Sec- 
tion R609. 1.1. Grout shall be prevented from bonding with 
the flue liner so that the flue liner is free to move with ther- 
mal expansion. For chimneys more than 40 inches (1016 
mm) wide, two additional No. 4 vertical bars shall be 
installed for each additional 40 inches (1016 mm) in width 
or fraction thereof. 

R1003.3.2 Horizontal reinforcing. Vertical reinforcement 
shall be placed enclosed within V4-inch (6 mm) ties, or other 
reinforcing of equivalent net cross-sectional area, spaced 
not to exceed 18 inches (457 mm) on center in concrete, or 
placed in the bed joints of unit masonry, at a minimum of 
every 18 inches (457 mm) of vertical height. Two such ties 
shall be installed at each bend in the vertical bars. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



305 



CHIMNEYS AND FIREPLACES 



R1003.4 Seismic anchorage. Masonry and concrete chimneys 
and foundations in Seismic Design Category Dq, Di or D2 shall 
be anchored at each floor, ceiling or roof line more than 6 feet 
(1829 mm) above grade, except where constructed completely 
within the exterior walls. Anchorage shall conform to the 
requirements in Section R1003.4.1. 

R1003.4.1 Anchorage. Two V^g-inch by 1-inch (5 mm by 
25 mm) straps shall be embedded a minimum of 12 inches 
(305 mm) into the chimney. Straps shall be hooked around 
the outer bars and extend 6 inches (152 mm) beyond the 
bend. Each strap shall be fastened to a minimum of four 
floor joists with two V2-inch (13 mm) bolts. 

R1003.5 Corbeling. Masonry chimneys shall not be corbeled 
more than one-half of the chimney's wall thickness from a 
wall or foundation, nor shall a chimney be corbeled from a 
wall or foundation that is less than 12 inches (305 mm) thick 
unless it projects equally on each side of the wall, except that 
on the second story of a two-story dwelling, corbeling of 
chimneys on the exterior of the enclosing walls may equal the 
wall thickness. The projection of a single course shall not 
exceed one-half the unit height or one-third of the unit bed 
depth, whichever is less. 

R1003.6 Changes in dimension. The chimney wall or chim- 
ney flue lining shall not change in size or shape within 6 inches 
(152 mm) above or below where the chimney passes through 
floor components, ceiling components or roof components. 

R1003.7 Offsets. Where a masonry chimney is constructed 
with a fireclay flue liner surrounded by one wythe of masonry, 
the maximum offset shall be such that the centerline of the flue 
above the offset does not extend beyond the center of the chim- 
ney wall below the offset. Where the chimney offset is sup- 
ported by masonry below the offset in an approved manner, the 
maximum offset limitations shall not apply. Each individual 
corbeled masonry course of the offset shall not exceed the pro- 
jection limitations specified in Section R1003.5. 

R1003.8 Additional load. Chimneys shall not support loads 
other than their own weight unless they are designed and con- 
structed to support the additional load. Construction of 
masonry chimneys as part of the masonry walls or reinforced 
concrete walls of the building shall be permitted. 

R1003.9 Termination. Chimneys shall extend at least 2 feet 
(610 mm) higher than any portion of a building within 10 feet 
(3048 nrni), but shall not be less than 3 feet (914 mm) above the 
highest point where the chimney passes through the roof. 

R1003.9.1 Spark arrestors. Where a spark arrestor is 
installed on a masonry chimney, the spark arrestor shall 
meet all of the following requirements: 

1 . The net free area of the arrestor shall not be less than 
four times the net free area of the outlet of the chim- 
ney flue it serves. 

2. The arrestor screen shall have heat and corrosion 
resistance equivalent to 19-gage galvanized steel or 
24-gage stainless steel. 

3 . Openings shall not permit the passage of spheres hav- 
ing a diameter greater than V2 inch (13 mm) nor block 



the passage of spheres having a diameter less than Vg 
inch (10 mm). 

4. The spark arrestor shall be accessible for cleaning and 
the screen or chimney cap shall be removable to allow 
for cleaning of the chimney flue. 

R1003.10 Wall thickness. Masonry chimney walls shall be 
constructed of solid masonry units or hollow masonry units 
grouted solid with not less than a 4-inch (102 mm) nominal 
thickness. 

R1003.10.1 Masonry veneer chimneys. Where masonry is 
used to veneer a frame chimney, through-flashing and weep 
holes shall be installed as required by Section R703. 

R1003.il Flue lining (material). Masonry chimneys shall be 
lined. The lining material shall be appropriate for the type of 
appliance connected, according to the terms of the appliance 
Hsting and manufacturer's instructions. 

R1003.il. 1 Residential-type appliances (general). Flue 
lining systems shall comply with one of the following: 

1 . Clay flue lining complying with the requirements of 
ASTM C 315 or equivalent. 

2. Listed chimney lining systems complying with UL 
1777. 

3. Factory -built chimneys or chimney units listed for 
installation within masonry chimneys. 

4. Other approved materials that will resist corrosion, 
erosion, softening or cracking from flue gases and 
condensate at temperatures up to 1,800°F (982°C). 

R1003.11.2 Flue linings for specific appUances. Flue lin- 
ings other than these covered in Section R1003.11.1, 
intended for use with specific types of appliances, shall 
comply with Sections R1003.11.3 through R1003.11.6. 

R1003.11.3 Gas appliances. Flue lining systems for gas 
appliances shall be in accordance with Chapter 24. 

R1003.11.4 Pellet fuel-burning appliances. Flue lining 
and vent systems for use in masonry chimneys with pellet 
fuel-burning appliances shall be limited to the following: 

1. Flue lining systems complying with Section 
R1003.11.1. 

2. Pellet vents listed for installation within masonry 
chimneys. (See Section R1003.1 1.6 for marking.) 

R1003.11.5 Oil-fired appliances approved for use with 
Type L vent. Flue lining and vent systems for use in 
masonry chimneys with oil-fired appliances approved for 
use with Type L vent shall be limited to the following: 

1. Flue lining systems complying with Section 
R1003.il. 1. 

2. Listed chimney liners complying with UL 641. (See 
Section R1003.1 1.6 for marking.) 

R1003.11.6 Notice of usage. When a flue is relined with a 
material not complying with Section R 1 003 . 1 1 . 1 , the chim- 
ney shall be plainly and permanently identified by a label 
attached to a wall, ceiling or other conspicuous location 
adjacent to where the connector enters the chimney. The 



306 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



CHIMNEYS AND FIREPLACES 



label shall include the following message or equivalent lan- 
guage: 

THIS CHIMNEY FLUE IS FOR USE ONLY WITH 
[TYPE OR CATEGORY OF APPLIANCE] APPLI- 
ANCES THAT BURN [TYPE OF FUEL]. DO NOT CON- 
NECT OTHER TYPES OF APPLIANCES. 

R1003.12 Clay flue lining (installation). Clay flue liners shall 
be installed in accordance with ASTM C 1283 and extend from 
a point not less than 8 inches (203 mm) below the lowest inlet 
or, in the case of fireplaces, from the top of the smoke chamber 
to a point above the enclosing walls. The lining shall be carried 
up vertically, with a maximum slope no greater than 30 degrees 
(0.52 rad) from the vertical. 

Clay flue liners shall be laid in medium-duty refractory mor- 
tar conforming to ASTM C 199 with tight mortar joints left 
smooth on the inside and installed to maintain an air space or 
insulation not to exceed the thickness of the flue liner separat- 
ing the flue liners from the interior face of the chimney 
masonry walls. Flue liners shall be supported on all sides. Only 
enough mortar shall be placed to make the joint and hold the 
liners in position. 

R1003.12.1 Listed materials. Listed materials used as flue 
linings shall be installed in accordance with the terms of 
their listings and manufacturer's instructions. 

R1003.12.2 Space around lining. The space surrounding a 
chimney lining system or vent installed within a masonry 
chimney shall not be used to vent any other appliance. 

Exception: This shall not prevent the installation of a 
separate flue lining in accordance with the manufac- 
turer's installation instructions. 

R1003.13 Multiple flues. When two or more flues are located in 
the same chimney, masonry wythes shall be built between adja- 
cent flue linings. The masonry wythes shall be at least 4 inches 
(102 mm) thick and bonded into the walls of the chimney. 

Exception: When venting only one apphance, two flues may 
adjoin each other in the same chimney with only the flue lin- 
ing separation between them. The joints of the adjacent flue 
linings shall be staggered at least 4 inches (102 mm). 

R1003.14 Flue area (appliance). Chimney flues shall not be 
smaller in area than that of the area of the connector from the 
apphance [see Tables R1003.14(l) and R1003.14(2)]. The sizing 
of a chimney flue to which multiple apphance venting systems are 
connected shall be in accordance with Section Ml 805.3. 

R1003.15 Flue area (masonry fireplace). Flue sizing for 
chimneys serving fireplaces shall be in accordance with Sec- 
tion R1003.15.1 or Section R1003.15.2. 

R1003.15.1 Option 1. Round chimney flues shall have a 
minimum net cross-sectional area of at least V,2 of the fire- 
place opening. Square chimney flues shall have a minimum 
net cross-sectional area of Vjo of the fireplace opening. Rect- 
angular chimney flues with an aspect ratio less than 2 to 1 
shall have a minimum net cross-sectional area of Vjo of the 
fireplace opening. Rectangular chimney flues with an aspect 
ratio of 2 to 1 or more shall have a minimum net cross-sec- 
tional area of 7g of the fireplace opening. Cross-sectional 
areas of clay flue linings are shown in Tables R 100 1.1 4(1) 



and R 100 1.1 4(2) or as provided by the manufacturer or as 
measured in the field. 

R1003.15.2 Option 2. The minimum net cross-sectional area 
of the chimney flue shall be determined in accordance with 
Figure R1003.15.2. A flue size providing at least the equiva- 
lent net cross-sectional area shall be used. Cross-sectional 
areas of clay flue Unings are shown in Tables R 1003. 14(1) 
and R 1003. 14(2) or as provided by the manufacturer or as 
measured in the field. The height of the chimney shall be 
measured from the firebox floor to the top of the chimney 
flue. 

TABLE R1 003.1 4(1) 
NET CROSS-SECTIONAL AREA OF ROUND FLUE SIZES^ 



FLUE SIZE, INSIDE DIAMETER 
(inches) 


CROSS-SECTIONAL AREA 
(square inches) 


6 


28 


7 


38 


8 


50 


10 


78 


10% 


90 


12 


113 


15 


176 


18 


254 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mn?. 
a. Flue sizes are based on ASTM C 315. 



TABLE R1 003.1 4(2) 

NET CROSS-SECTIONAL AREA OF SQUARE AND 

RECTANGULAR FLUE SIZES 



FLUE SIZE, OUTSIDE NOMINAL 
DIMENSIONS (inches) 


CROSS-SECTIONAL AREA 
(square inches) 


4.5 X 8.5 


23 


4.5x13 


34 


8x8 


42 


8.5 X 8.5 


49 


8x12 


67 


8.5x13 


76 


12x12 


102 


8.5x18 


101 


13x13 


127 


12x16 


131 


13x18 


173 


16x16 


181 


16x20 


222 


18x18 


233 


20x20 


298 


20x24 


335 


24x24 


431 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm^. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



307 



CHIMNEYS AND FIREPLACES 































"^onn 




269 
214 

168 
124 

91 

82 
58 

37 


















^^^-^ 


































^ 


"^Rnn 
























^^ 


^ 
















^.^.-^ 








^ 


^ 
















^^^.--^ 








^ 


Y^ 






/oOU 










.,,^-^ 








^ 


















,--"^ 




















z4UU 






--'^ 








^^ 


-"^ 












nii-in 


224 










^..^ 


"-^ 












^^ 














■^ 






















^__^ 


-^ 






















187 




-^ 














.^^ 








^Qnn 




























a 










, 















"-^ 


ipnn 




























< 

LU 

_i 




-— -^ 














"-^ 








^ -inn 












_,..^ 
















-SECTIONA 
o 










"^ 
















I'^rm 




- 




















— " 




















--^ 










5 













_— — 












. — — ^ 






__^ 














— ■ 








PX\(\ 


t 76 










__-- 


^ 












_^ 




70 




— 














- 








(i.T\r\ 










_- ■ 



















53 
























" 


400 


32 


















■ 






































■^nn 


























































a CO 


^ 13 14 15 16 17 18 19 20 21 22 23 24 25 
0:3 < 
2 "5 HEIGHT, MEASURED FROM FLOOR g g — 
51^ OF COMBUSTION CHAMBER TO 3 O - 
S&C^ TOP OF FLUE (FT) gllg 



For SI: 1 foot = 304.8 mm, 1 square inch = 645.16 mnn?. 



FIGURE R1 003.1 5.2 
FLUE SIZES FOR MASONRY CHIMNEYS 



R1003.16 Inlet. Inlets to masonry chimneys shall enter from 
the side. Inlets shall have a thimble of fireclay, rigid refractory 
material or metal that will prevent the connector from pulling 
out of the inlet or from extending beyond the wall of the liner. 

R1003.17 Masonry chimney cleanout openings. Cleanout 
openings shall be provided within 6 inches (152 mm) of the 
base of each flue within every masonry chinmey. The upper 
edge of the cleanout shall be located at least 6 inches (152 mm) 
below the lowest chimney inlet opening. The height of the 
opening shall be at least 6 inches (152 mm). The cleanout shall 
be provided with a noncombustible cover. 

Exception: Chimney flues serving masonry fireplaces 
where cleaning is possible through the fireplace opening. 

R1003.18 Chimney clearances. Any portion of a masonry 
chimney located in the interior of the building or within the 



exterior wall of the building shall have a minimum air space 
clearance to combustibles of 2 inches (51 mm). Chimneys 
located entirely outside the exterior walls of the building, 
including chimneys that pass through the soffit or cornice, shall 
have a minimum air space clearance of 1 inch (25 mm). The air 
space shall not be filled, except to provide fire blocking in 
accordance with Section R1003.19. 

Exceptions: 

1 . Masonry chimneys equipped with a chimney lining 
system listed and labeled for use in chimneys in con- 
tact with combustibles in accordance with UL 1777 
and installed in accordance with the manufacturer's 
installation instructions are permitted to have com- 
bustible material in contact with their exterior sur- 
faces. 



308 



2006 INTERNATIONAL RESIDENTIAL CODE® 



CHIMNEYS AND FIREPLACES 




MASONRY ABUTTING 
COMBUSTIBLE SHEATHING 
12 IN. FROM FLUE LINING 



1 IN. CLEARANCE (AIR SPACE) 
TO COMBUSTIBLE SHEATHING 



For SI: 1 inch = 25.4 mm. 



FIGURE R1 003.1 8 
CLEARANCE FROM COMBUSTIBLES 



2. When masonry chimneys are constructed as part of 
masonry or concrete walls, combustible materials 
shall not be in contact with the masonry or concrete 
wall less than 1 2 inches (305 mm) from the inside sur- 
face of the nearest flue lining. 

3. Exposed combustible trim and the edges of sheathing 
materials, such as wood siding and flooring, shall be 
permitted to abut the masonry chimney side walls, in 
accordance with Figure R1003.18, provided such 
combustible trim or sheathing is a minimum of 12 
inches (305 mm) from the inside surface of the nearest 
flue lining. Combustible material and trim shall not 
overlap the comers of the chimney by more than 1 inch 
(25 mm). 

R1003.19 Chimney fireblocking. All spaces between chim- 
neys and floors and ceilings through which chimneys pass shall 
be fireblocked with noncombustible material securely fastened 
in place. The fireblocking of spaces between chimneys and 
wood joists, beams or headers shall be self-supporting or be 
placed on strips of metal or metal lath laid across the spaces 
between combustible material and the chimney. 

R1003.20 Chimney crickets. Chimneys shall be provided 
with crickets when the dimension parallel to the ridgeline is 
greater than 30 inches (762 mm) and does not intersect the 
ridgeline. The intersection of the cricket and the chimney shall 
be flashed and counterflashed in the same manner as normal 
roof-chimney intersections. Crickets shall be constructed in 
compliance with Figure R 1003. 20 and Table R 1003. 20. 

TABLE R1 003.20 
CRICKET DIMENSIONS 



ROOF SLOPE 


H 


12-12 


VjofW 


8-12 


VjofW 


6-12 


V4 0fW 


4- 12 


VeofW 


3-12 


VgofW 



SECTION R1 004 
FACTORY-BUILT FIREPLACES 

R1004.1 General. Factory-built fireplaces shall be Usted and 
labeled and shall be installed in accordance with the conditions 
of the listing. Factory-built fireplaces shall be tested in accor- 
dance with UL 127. 

R1004.2 Hearth extensions. Hearth extensions of approved 
factory-built fireplaces shall be installed in accordance with the 
listing of the fireplace. The hearth extension shall be readily 
distinguishable from the surrounding floor area. 

R1004.3 Decorative shrouds. Decorative shrouds shall not be 
installed at the termination of chimneys for factory-built fire- 
places except where the shrouds are listed and labeled for use 
with the specific factory-built fireplace system and installed in 
accordance with the manufacturer's installation instructions. 

R1004.4 Unvented gas log heaters. An unvented gas log 
heater shall not be installed in a factory-built fireplace unless 
the fireplace system has been specifically tested, listed and 
labeled for such use in accordance with UL 127. 



SECTION R1005 
FACTORY-BUILT CHIMNEYS 

R1005.1 Listing. Factory-built chimneys shall be listed and 
labeled and shall be installed and terminated in accordance 
with the manufacturer's installation instructions. 

R1005.2 Decorative shrouds. Decorative shrouds shall not be 
installed at the termination of factory-built chimneys except 
where the shrouds are listed and labeled for use with the spe- 
cific factory-built chimney system and installed in accordance 
with the manufacturer's installation instructions. 

R1005.3 Solid-fuel appliances. Factory-built chimneys 
installed in dwelling units with solid-fuel-burning appliances 
shall comply with the Type HT requirements of UL 103 and 
shall be marked "Type HT and "Residential Type and Building 
Heating Appliance Chimney." 

Exception: Chimneys for use with open combustion cham- 
ber fireplaces shall comply with the requirements of UL 103 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



309 



CHIMNEYS AND FIREPLACES 




FLUE LINER 



N kWNK^^ t^l 




ROOF LINE 



\ 


/ 






\ 


/ 


^ 7 

V 


^ w * 



For SI: 1 inch = 25.4 mm. 



FIGURE R1 003.20 
CHIMNEY CRICKET 



and shall be marked "Residential Type and Building Heat- 
ing Appliance Chimney." 

Chimneys for use with open combustion chamber appli- 
ances installed in buildings other than dwelling units shall 
comply with the requirements of UL 103 and shall be marked 
"Building Heating Appliance Chimney" or "Residential Type 
and Building Heating Appliance Chimney." 

R1005.4 Factory-built fireplaces. Chimneys for use with fac- 
tory-built fireplaces shall comply with the requirements of UL 

127. 

R1005.5 Support. Where factory-built chimneys are sup- 
ported by structural members, such as joists and rafters, those 
members shall be designed to support the additional load. 

R1005.6 Medium-heat appliances. Factory-built chimneys 
for medium-heat appliances producing flue gases having a 
temperature above 1,000°F (538°C), measured at the entrance 
to the chimney shall comply with UL 959. 



SECTION R1006 
EXTERIOR AIR SUPPLY 

R1006.1 Exterior air. Factory-built or masonry fireplaces 
covered in this chapter shall be equipped with an exterior air 
supply to assure proper fuel combustion unless the room is 
mechanically ventilated and controlled so that the indoor pres- 
sure is neutral or positive. 

R1006.1.1 Factory-built fireplaces. Exterior combustion 
air ducts for factory-built fireplaces shall be a listed compo- 
nent of the fireplace and shall be installed according to the 
fireplace manufacturer's instructions. 

R1006.1.2 Masonry fireplaces. Listed combustion air 
ducts for masonry fireplaces shall be installed according to 
the terms of their listing and the manufacturer's instruc- 
tions. 



R1006.2 Exterior air intake. The exterior air intake shall be 
capable of supplying all combustion air from the exterior of the 
dwelling or from spaces within the dwelling ventilated with 
outside air such as non-mechanically ventilated crawl or attic 
spaces. The exterior air intake shall not be located within the 
garage or basement of the dwelling nor shall the air intake be 
located at an elevation higher than the firebox. The exterior air 
intake shall be covered with a corrosion-resistant screen of 
V4-inch (6 mm) mesh. 

R1006.3 Clearance. Unlisted combustion air ducts shall be 
installed with a minimum 1-inch (25 mm) clearance to com- 
bustibles for all parts of the duct within 5 feet (1524 mm) of the 
duct outlet. 

R1006.4 Passageway. The combustion air passageway shall 
be a minimum of 6 square inches (3870 mm^) and not more 
than 55 square inches (0.035 m^), except that combustion air 
systems for listed fireplaces shall be constructed according to 
the fireplace manufacturer's instructions. 

R1006.5 Outlet. Locating the exterior air outlet in the back or 
sides of the firebox chamber or within 24 inches (610 mm) of 
the firebox opening on or near the floor is permitted. The outlet 
shall be closable and designed to prevent burning material from 
dropping into concealed combustible spaces. 



310 



2006 INTERNATIONAL RESIDENTIAL CODE® 



Part IV — Energy Conservation 



CHAPTER 11 

ENERGY EFFICIENCY 

This chapter has been revised in its entirety; there will be no marginal markings 



SECTION Nil 01 
GENERAL 

Nl 101.1 Scope. This chapter regulates the energy efficiency 
for the design and construction of buildings regulated by this 
code. 

Exception: Portions of the building envelope that do not 
enclose conditioned space. 

Nl 101.2 Compliance. Comphance shall be demonstrated by 
either meeting the requirements of the International Energy 
Conservation Code or meeting the requirements of this chap- 
ter. Climate zones from Figure Nl 101 .2 or Table Nl 101.2 shall 
be used in determining the applicable requirements from this 
chapter. 

Nl 101.2.1 Warm humid counties. Warm humid counties 
are listed in Table Nl 101.2.1. 

N1101.3 Identification. Materials, systems and equipment 
shall be identified in a manner that will allow a determination 
of compliance with the applicable provisions of this chapter. 

N1101.4 Building thermal envelope insulation. An /?-value 
identification mark shall be applied by the manufacturer to 
each piece of building thermal envelope insulation 12 inches 
(305 mm) or more wide. Alternately, the insulation installers 
shall provide a certification listing the type, manufacturer and 
/?- value of insulation installed in each element of the building 
thermal envelope. For blown or sprayed insulation (fiberglass 
and cellulose), the initial installed thickness, settled thickness, 
settled /?- value, installed density, coverage area and number of 
bags installed shall be listed on the certification. For sprayed 
polyurethane foam (SPF) insulation, the installed thickness of 
the area covered and ^-value of installed thickness shall be 
listed on the certificate. The insulation installer shall sign, date 
and post the certificate in a conspicuous location on the job site. 

NllOl.4.1 Blown or sprayed roof/ceiling insulation. The 

thickness of blown in or sprayed roof/ceiling insulation 
(fiberglass or cellulose) shall be written in inches (mm) on 
markers that are installed at least one for every 300 ft^ (28 
m^) throughout the attic space. The markers shall be affixed 
to the trusses or joists and marked with the minimum initial 
installed thickness with numbers a minimum of 1 inch (25 
mm) high. Each marker shall face the attic access opening. 
Spray polyurethane foam thickness and installed R-wahie 
shall be listed on the certificate provided by the insulation 
installer. 

NllOl.4.2 Insulation mark installation. Insulating mate- 
rials shall be installed such that the manufacturer's ^- value 
mark is readily observable upon inspection. 



N1101.5 Fenestration product rating, [/-factors of fenestra- 
tion products (windows, doors and skylights) shall be deter- 
mined in accordance with NFRC 100 by an accredited, 
independent laboratory, and labeled and certified by the manu- 
facturer. Products lacking such a labeled [/-factor shall be 
assigned a default [/-factor from Tables N1101.5(l) and 
Nl 101.5(2). The solar heat gain coefficient (SHGC) of glazed 
fenestration products (windows, glazed doors and skylights) 
shall be determined in accordance with NFRC 200 by an 
accredited, independent laboratory, and labeled and certified 
by the manufacturer. Products lacking such a labeled SHGC 
shall be assigned a default SHGC from Table Nl 101.5(3). 

N1101.6 Installation. All materials, systems and equipment 
shall be installed in accordance with the manufacturer's instal- 
lation instructions and the provisions of this code. 

NllOl.6.1 Protection of exposed foundation insulation. 

Insulation applied to the exterior of basement walls, crawl 
space walls, and the perimeter of slab-on-grade floors shall 
have a rigid, opaque and weather-resistant protective cover- 
ing to prevent the degradation of the insulation's thermal 
performance. The protective covering shall cover the 
exposed exterior insulation and extend a minimum of 6 
inches (152 mm) below grade. 

Nl 101.7 Above code programs. The building official or other 
authority having jurisdiction shall be permitted to deem a 
national, state or local energy efficiency program to exceed the 
energy efficiency required by this chapter. Buildings approved 
in writing by such an energy efficiency program shall be con- 
sidered in compliance with this chapter. 

Nl 101.8 Certificate. A permanent certificate shall be posted 
on or in the electrical distribution panel. The certificate shall be 
completed by the builder or registered design professional. The 
certificate shall list the predominant /?-values of insulation 
installed in or on ceiling/roof, walls, foundation (slab, base- 
ment wall, crawlspace wall and/or floor) and ducts outside con- 
ditioned spaces; [/-factors for fenestration; and the solar heat 
gain coefficient (SHGC) of fenestration. Where there is more 
than one value for each component, the certificate shall list the 
value covering the largest area. The certificate shall list the type 
and efficiency of heating, cooling and service water heating 
equipment. 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



311 



m 

z 
> 

o 

Z 
> 

|- 

m 
(/) 

o 



Marine (C) 




Warm- Hum id 
Below White Line 



Ai! of Alaska ^n Zone 7 
except for the fotlowing 
Boroughs in Zone 8; 

Bethel Northwest Arctic 

Dellingham Southeast Fairbanks 

Fairbanks N. Star Wade Hampton 

Nome Yukon-Koyukuk 
North Slope 



o 
m 



O 

-< 



FIGURE N1101 .2 
CLIMATE ZONES 



ENERGY EFFICIENCY 



TABLEN1101.2 
CLIMATE ZONES BY STATES AND COUNTIES 



Alabama 
Zone 3 except 
Zone 2 
Baldwin 
Mobile 

Alaska 
Zone 7 except 
Zones 

Bethel 
Dellingham 
Fairbanks North Star 
Nome 
North Slope 
Northwest Arctic 
Southeast Fairbanks 
Wade Hampton 
Yukon-Koyukuk 

Arizona 
Zone 3 except 
Zone 2 

La Paz 

Maricopa 

Pima 

Pinal 

Yuma 

Zone 4 

Gila 

Yavapai 

Zone 5 

Apache 

Coconino 

Navajo 

Arkansas 
Zone 3 except 
Zone 4 

Baxter 

Benton 

Boone 

Can-oil 

Fulton 

Izard 

Madison 

Marion 

Newton 

Searcy 

Stone 

Washington 

California 
Zone 3 Dry except 
Zone 2 

Imperial 
Zone 3 Marine 

Alameda 
Marin 



Mendocino 

Monterey 

Napa 

San Benito 

San Francisco 

San Luis Obispo 

San Mateo 

Santa Barbara 

Santa Clara 

Santa Cruz 

Sonoma 

Ventura 

Zone 4 Dry 

Amador 

Calaveras 

El Dorado 

Inyo 

Lake 

Mariposa 

Trinity 

Tuolumne 

Zone 4 Marine 

Del Norte 

Humboldt 

Zone 5 

Lassen 

Modoc 

Nevada 

Plumas 

Sierra 

Siskiyou 

Zone 6 

Alpine 

Mono 

Colorado 
Zone 5 except 
Zone 4 

Baca 

Las Animas 

Otero 

Zone 6 

Alamosa 

Archuleta 

Chaffee 

Conejos 

Costilla 

Custer 

Dolores 

Eagle 

Moffat 

Ouray 

Rio Blanco 

Saguache 

San Miguel 

Zone? 

Clear Creek 

Grand 



Gunnison 

Hinsdale 

Jackson 

Lake 

Mineral 

Park 

Pitkin 

Rio Grande 

Routt 

San Juan 

Summit 



Connecticut 



Zone 5 



Delaware 
Zone 4 

Dist. of Columbia 
Zone 4 

Florida 
Zone 2 except 
Zonel 

Broward 

Dade 

Monroe 

Georgia 
Zone 3 except 
Zone 2 

Appling 

Atkinson 

Bacon 

Baker 

Berrien 

Brantley 

Brooks 

Bryan 

Camden 

Charlton 

Chatham 

Clinch 

Colquitt 

Cook 

Decatur 

Echols 

Effingham 

Evans 

Glynn 

Grady 

Jeff Davis 

Lanier 

Liberty 

Long 

Lowndes 

Mcintosh 

Miller 

(continued) 



Mitchell 

Pierce 

Seminole 

Tattnall 

Thomas 

Toombs 

Ware 

Wayne 

Zone 4 

Banks 

Catoosa 

Dade 

Dawson 

Fannin 

Floyd 

Franklin 

Gilmer 

Gordon 

Habersham 

Hall 

Lumpkin 

Murray 

Pickens 

Rabun 

Stephens 

Towns 

Union 

Walker 

White 

Whitfield 

Hawaii 
Zone 1 Moist 

Idaho 
Zone 6 except 
Zone 5 

Ada 

Benewah 

Canyon 

Cassia 

Clearwater 

Elmore 

Gem 

Gooding 

Idaho 

Jerome 

Kootenai 

Latah 

Lewis 

Lincoln 

Minidoka 

Nez Perce 

Owyhee 

Payette 

Power 

Shoshone 

Twin Falls 



Washington 

Illinois 
Zone 5 except 
Zone 4 

Alexander 

Bond 

Christian 

Clay 

Clinton 

Crawford 

Edwards 

Effingham 

Fayette 

Franklin 

Gallatin 

Hamilton 

Hardin 

Jackson 

Jasper 

Jefferson 

Johnson 

Lawrence 

Macoupin 

Madison 

Marion 

Massac 

Monroe 

Montgomery 

Perry 

Pope 

Pulaski 

Randolph 

Richland 

Saline . 

Shelby 

St clair 

Union 

Wabash 

Washington 

Wayne 

White 

Williamson 

Indiana 
Zone 5 except 
Zone 4 

Brown 

Clark 

Crawford 

Daviess 

Dearborn 

Dubois 

Floyd 

Gibson 

Greene 

Harrison 

Jackson 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



313 



ENERGY EFFICIENCY 



TABLE Nil 01 .2— continued 
CLIMATE ZONES BY STATES AND COUNTIES 



Jefferson 

Jennings 

Knox 

Lawrence 

Martin 

Monroe 

Ohio 

Orange 

Perry 

Pike 

Posey 

Ripley 

Scott 

Spencer 

Sullivan 

Switzerland 

Vanderburgh 

Warrick 

Washington 

Iowa 
Zone 5 except 
Zone 6 

Allamakee 

Black Hawk 

Bremer 

Buchanan 

Buena Vista 

Butler 

Calhoun 

Cerro Gordo 

Cherokee 

Chickasaw 

Clay 

Clayton 

Delaware 

Dickinson 

Emmet 

Fayette 

Floyd 

Franklin 

Grundy 

Hamilton 

Hancock 

Hardin 

Howard 

Humboldt 

Ida 

Kossuth 

Lyon 

Mitchell 

O'Brien 

Osceola 

Palo Alto 

Plymouth 

Pocahontas 

Sac 

Sioux 



314 



Webster 

Winnebago 

Winneshiek 

Worth 

Wright 

Kansas 
Zone 4 except 
Zone 5 
Cheyenne 
Cloud 
Decatur 
EUis 
Gove 
Graham 
Greeley 
Hamilton 
Jewell 
Lane 
Logan 
Mitchell 
Ness 
Norton 
Osborne 
PhiUips 
Rawlins 
RepubUc 
Rooks 
Scott 
Sheridan 
Sherman 
Smith 
Thomas 
Trego 
Wallace 
Wichita 

Kentucky 
Zone 4 

Louisiana 
Zone 2 except 
Zone 3 

Bienville 

Bossier 

Caddo 

Caldwell 

Catahoula 

Claiborne 

Concordia 

De Soto 

East Carroll 

Franklin 

Grant 

Jackson 

La Salle 

Lincoln 

Madison 



Morehouse 


Oceana 


Harrison 


Natchitoches 


Ogemaw 


Jackson 


Ouachita 


Osceola 


Pearl River 


Red River 


Oscoda 


Stone 


Richland 


Otsego 




Sabine 


Presque Isle 


Missouri 


Tensas 


Roscommon 


Zone 4 except 


Union 


Sanilac 


Zone 5 


Vernon 


Wexford 


Adair 


Webster 


Zone? 


Andrew 


West Carroll 


Baraga 


Atchison 


Winn 


Chippewa 


Buchanan 




Gogebic 


Caldwell 


Maine 


Houghton 


Chariton 


Zone 6 except 


Iron 


Clark 


Zone? 


Keweenaw 


Chnton 


Aroostook 


Luce 


Daviess 




Mackinac 


De Kalb 


Maryland 


Ontonagon 


Gentry 


Zone 4 except 


Schoolcraft 


Grundy 


Zones 




Harrison 


Garrett 


Minnesota 


Holt 




Zone 6 except 


Knox 


Massachusetts 


Zone? 


Lewis 


Zone 5 


Aitkin 


Linn 




Becker 


Livingston 


Michigan 


Beltrami 


Macon 


Zone 5 except 


Carlton 


Marion 


Zone 6 


Cass 


Mercer 


Alcona 


Clay 


Nodaway 


Alger 


Clearwater 


Pike 


Alpena 


Cook 


Putnam 


Antrim 


Crow Wing 


Ralls 


Arenac 


Grant 


Schuyler 


Benzie 


Hubbard 


Scotland 


Charlevoix 


Itasca 


Shelby 


Cheboygan 


Kanabec 


Sullivan 


Clare 


Kittson 


Worth 


Crawford 


Koochiching 




Delta 


Lake of the Wood 


Montana 


Dickinson 


Mahnomen 


Zone 6 


Emmet 


Marshall 




Gladwin 


Mille Lacs 


Nebraska 


Grand Traverse 


Norman 


Zones 


Huron 


Otter Tail 




Iosco 


Pennington 


Nevada 


Isabella 


Pine 


Zone S except 


Kalkaska 


Polk 


Zone 3 


Lake 


Red Lake 


Clark 


Leelanau 


Roseau 




Manistee 


St Louis 


New Hampshire 


Marquette 


Wadena 


Zone 6 except 


Mason 


Wilkin 


ZoneS 


Mecosta 




Cheshire 


Menominee 


Mississippi 


Hillsborough 


Missaukee 


Zone 3 except 


Rockingham 


Montmorency 


Zone 2 


Stafford 


Newaygo 


Hancock 





(continued) 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



ENERGY EFFICIENCY 



TABLE Nil 01 .2— continued 
CLIMATE ZONES BY STATES AND COUNTIES 



New Jersey 


Hamilton 


Rockingham 


Oklahoma 


Bon Homme 


Zone 4 except 


Herkimer 


Rutherford 


Zone 3 Moist except 


Charles Mix 


Zone 5 


Jefferson 


Stokes 


Zone 4 Dry 


Clay 


Bergen 


Lewis 


Surry 


Beaver 


Douglas 


Hunterdon 


Madison 


Swain 


Cimarron 


Gregory 


Mercer 


Montgomery 


Transylvania 


Texas 


Hutchinson 


Morris 


Oneida 


Vance 




Jackson 


Passaic 


Otsego 


Wake 


Oregon 


Mellette 


Somerset 


Schoharie 


Warren 


Zone 4 Marine except 


Todd 


Sussex 


Schuyler 


Wilkes 


Zone 5 Dry 


Tripp 


Warren 


St Lawrence 


Yadkin 


Baker 


Union 




Steuben 


Zone 5 


Crook 


Yankton 


New Mexico 


SuUivan 


Alleghany 


Deschutes 




Zone 4 except 


Tompkins 


Ashe 


Gilliam 


Tennessee 


Zone 3 


Ulster 


Avery 


Grant 


Zone 4 except 


Chaves 


Warren 


Mitchell 


Harney 


Zone 3 


Dona Ana 


Wyoming 


Watauga 


Hood River 


Chester 


Eddy 




Yancey 


Jefferson 


Crockett 


Hidalgo 


North Carolina 




Klamath 


Dyer 


Lea 


Zone 3 except 


North Dakota 


Lake 


Fayette 


Luna 


Zone 4 


Zone 7 except 


Malheur 


Hardeman 


Otero 


Alamance 


Zone 6 


Morrow 


Hardin 


Zones 


Alexander 


Adams 


Sherman 


Haywood 


Catron 


Bertie 


Billings 


Umatilla 


Henderson 


Colfax 


Buncombe 


Bowman 


Union 


Lake 


Harding 


Burke 


Burleigh 


Wallowa 


Lauderdale 


Los Alamos 


Calwell 


Dickey 


Wasco 


Madison 


McKinley 


Caswell 


Dunn 


Wheeler 


McNairy 


Mora 


Catawba 


Emmons 




Shelby 


Rio Arriba 


Chatham 


Golden Valley 


Pennsylvania 


Tipton 


San Juan 


Cherokee 


Grant 


Zone 5 except 




San Miguel 


Clay 


Hettinger 


Zone 4 


Texas 


Sandoval 


Cleveland 


La Moure 


Bucks 


Zone 2 Moist except 


Santa Fe 


Davie 


Logan 


Chester 


Zone 2 Dry 


Taos 


Durham 


Mcintosh 


Delaware 


Bandera 


Torrance 


Forsyth 


McKenzie 


Montgomery 


Dimmit 




Franklin 


Mercer 


Philadelphia 


Edwards 


New York 


Gates 


Morton 


York 


Frio 


Zone 5 except 


Graham 


Oliver 


Zone 6 


Kinney 


Zone 4 


Granville 


Ransom 


Cameron 


La Salle 


Bronx 


Guilford 


Richland 


Clearfield 


Maverick 


Kings 


HaUfax 


Sargent 


Elk 


Medina 


Nassau 


Harnett 


Sioux 


McKean 


Real 


New York 


Haywood 


Slope 


Potter 


Uvalde 


Queens 


Henderson 


Stark 


Susquehanna 


Val Verde 


Richmond 


Hertford 




Tioga 


Webb 


Suffolk 


Iredell 


Ohio 


Wayne 


Zapata 


Westchester 


Jackson 


Zone 5 except 




Zavala 


Zone 6 


Lee 


Zone 4 


Rhode Island 


Zone 3 Dry 


Allegany 


Lincoln 


Adams 


Zone 5 


Andrews 


Broome 


Macon 


Brown 




Baylor 


Cattaraugus 


Madison 


Clermont 


South Carolina 


Borden 


Chenango 


McDowell 


Gallia 


Zone 3 


Brewster 


Clinton 


Nash 


Hamilton 




Callahan 


Delaware 


Northampton 


Lawrence 


South Dakota 


Childress 


Essex 


Orange 


Pike 


Zone 6 except 


Coke 


Franklin 


Person 


Scioto 


Zone 5 


Coleman 


Fulton 


Polk 


Washington 

(continued) 


Bennett 


Collingsworth 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



315 



ENERGY EFFICIENCY 



TABLE Nil 01 .2— continued 
CLIMATE ZONES BY STATES AND COUNTIES 



Concho 


Wheeler 


Stephens 


Virginia 


Wyoming 


Cottle 


Wilbarger 


Tarrant 


Zone 4 




Crane 


Winkler 


Titus 




Wisconsin 


Crockett 


Zone 3 Moist 


Upshur 


Washington 


Zone 6 except 


Crosby 


Archer 


Van Zandt 


Zone 4 Marine except 


Zone? 


Culberson 


Bianco 


Wichita 


Zone 5 Dry 


Ashland 


Dawson 


Bowie 


Wise 


Adams 


Bayfield 


Dickens 


Brown 


Wood 


Asotin 


Burnett 


Ector 


Burnet 


Young 


Benton 


Douglass 


El Paso 


Camp 


Zone 4 


Chelan 


Florence 


Fisher 


Cass 


Armstrong 


Columbia 


Forest 


Foard 


Clay 


Bailey 


Douglas 


Iron 


Gaines 


Collin 


Briscoe 


Franklin 


Langlade 


Garza 


Comanche 


Carson 


Garfield 


Lincoln 


Glasscock 


Cooke 


Castro 


Grant 


Oneida 


Hall 


Dallas 


Cochran 


Kittitas 


Price 


Hardeman 


Delta 


Dallam 


Klickitat 


Sawyer 


Haskell 


Denton 


Deaf Smith 


Lincoln 


Taylor 


Hemphill 


Eastland 


Donley 


Skamania 


Vilas 


Howard 


Ellis 


Floyd 


Spokane 


Washburn 


Hudspeth 


Erath 


Gray 


Walla Walla 




Irion 


Fannin 


Hale 


Whitman 


Wyoming 


Jeff Davis 


Franklin 


Hansford 


Yakima 


Zone 6 except 


Jones 


Gillespie 


Hartley 


Zone 6 Dry 


Zone 5 


Kent 


Grayson 


Hockley 


Ferry 


Goshen 


Kerr 


Gregg 


Hutchinson 


Okanogan 


Platte 


Kimble 


Hamilton 


Lamb 


Pend Oreille 


Zone? 


King 


Harrison 


Lipscomb 


Stevens 


Lincoln 


Knox 


Henderson 


Moore 




Sublette 


Loving 


Hood 


Ochiltree 


West Virgina 


Teto 


Lubbock 


Hopkins 


Oldham 


Zone 5 except 




Lynn 


Hunt 


Parmer 


Zone 4 


American Samoa 


Martin 


Jack 


Potter 


Berkely 


Zone 1 Moist 


Mason 


Johnson 


Randall 


Boone 




McCulIoch 


Kaufman 


Roberts 


Braxton 


Guam 


Menard 


Kendall 


Sherman 


Cabell 


Zone 1 Moist 


Midland 


Lamar 


Swisher 


Calhoun 




Mitchell 


Lampasas 


Yoakum 


Clay 


Northern Marianas 


Motley 


Llano 




Gilmer 


Zone 1 Moist 


Nolan 


Marion 


Utah 


Jackson 




Pecos 


Mills 


Zone 5 except 


Jefferson 


Puerto Rico 


Presidio 


Montague 


Zone 3 


Kanawha 


Zone 1 Moist 


Reagan 


Morris 


Washington 


Lincoln 




Reeves 


Nacogdoches 


Zone 6 


Logan 


U.S. Virgin Islands 


Runnels 


Navarro 


Box Elder 


Mason 


Zone 1 Moist 


Schleicher 


Palo Pinto 


Cache 


McDowell 




Scurry 


Panola 


Carbon 


Mercer 




Shackelford 


Parker 


Daggett 


Mingo 




SterUng 


Rains 


Duchesne 


Monroe 




Stonewall 


Red River 


Morgan 


Morgan 




Sutton 


Rockwall 


Rich 


Pleasants 




Taylor 


Rusk 


Summit 


Putnam 




Terrell 


Sabine 


Uintah 


Ritchie 




Terry 


San Augustine 


Wasatch 


Roane 




Throckmorton 


San Saba 




Tyler 




Tom Green 


Shelby 


Vermont 


Wayne 




Upton 


Smith 


Zone 6 


Wirt 




Ward 


Somervell 




Wood 





316 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



ENERGY EFFICIENCY 



TABLE Nil 01 .2.1 
WARM HUMID COUNTIES 



Alabama 

Autauga 

Baldwin 

Barbour 

Bullock 

Butler 

Choctaw 

Clarke 

Coffee 

Conecuh 

Covington 

Crenshaw 

Dale 

Dallas 

Elmore 

Escambia 

Geneva 

Henry 

Houston 

Lowndes 

Macon 

Marengo 

Mobile 

Monroe 

Montgomery 

Perry 

Pike 

Russell 

Washington 

Wilcox 



Arkansas 



Columbia 

Hempstead 

Lafayette 

Little River 

Miller 

Sevier 

Union 

All 



Florida 



Georgia 

All in Zone 2 

Plus 
Ben Hill 
Bleckley 
Bulloch 
Calhoun 
Candler 
Chattahoochee 
Clay 
Coffee 
Crisp 
Dodge 
Dooly 
Dougherty 
Early 
Emanuel 



Houston 

Irwin 

Jenkins 

Johnson 

Laurens 

Lee 

Macon 

Marion 

Montgomery 

Peach 

Pulaski 

Quitman 

Randolph 

Schley 

Screven 

Stewart 

Sumter 

Taylor 

Telfair 

Terrell 

Tift 

Treutlen 

Turner 

Twiggs 

Webster 

Wheeler 

Wilcox 

Worth 

All 



Hawaii 



Louisiana 

All in Zone 2 

Plus 
Bienville 
Bossier 
Caddo 
Caldwell 
Catahoula 
Claiborne 
De Soto 
Franklin 
Grant 
Jackson 
La Salle 
Lincoln 
Madison 
Natchitoches 
Ouachita 
Red River 
Richland 
Sabine 
Tensas 
Union 
Vernon 
Webster 
Winn 



Mississippi 

All in Zone 2 

Plus 
Adams 
Amite 
Claiborne 
Copiah 
Covington 
Forrest 
Franklin 
George 
Greene 
Hinds 
Jefferson 
Jefferson Davis 
Jones 
Lamar 
Lawrence 
Lincoln 
Marion 
Perry 
Pike 
Rankin 
Simpson 
Smith 
Walthall 
Warren 
Wayne 
Wilkinson 

North Carolina 

Brunswick 

Carteret 

Columbus 

New Hanover 

Onslow 

Pender 

South Carolina 

Allendale 

Bamberg 

Barnwell 

Beaufort 

Berkeley 

Charleston 

Colleton 

Dorchester 

Georgetown 

Hampton 

Horry 

Jasper 

Texas 

All in Zone 2 

Plus 
Blanco 
Bowie 
Brown 
Burnet 
Camp 



Cass 

Collin 

Comanche 

Dallas 

Delta 

Denton 

ElUs 

Erath 

Franklin 

Gillespie 

Gregg 

Hamilton 

Harrison 

Henderson 

Hood 

Hopkins 

Hunt 

Johnson 

Haufman 

Kendall 

Lamar 

Lampasas 

Llano 

Marion 

Mills 

Morris 

Nacogdoches 

Navarro 

Palo Pinto 

Panola 

Parker 

Rains 

Red River 

Rockwall 

Rusk 

Sabine 

San Augustine 

San Saba 

Shelby 

Smith 

Somervell 

Tarrant 

Titus 

Upshur 

Van Zandt 

Wood 



All 



All 



All 



All 



All 



American Samoa 



Guam 



Northern Marianas 



Puerto Rico 



U.S. Virgin Islands 



2006 INTERNATIONAL RESIDENTIAL CODE® 



317 



ENERGY EFFICIENCY 



TABLE Nil 01 .5(1) 
DEFAULT GLAZED FENESTRATION (AFACTORS 



FRAME TYPE 


SINGLE PANE 


DOUBLE PANE 


SKYLIGHT 


Single 


Double 


Metal 


1.2 


0.8 


2 


1.3 


Metal with thermal break 


1.1 


0.65 


1.9 


1.1 


Nonmetal or metal clad 


0.95 


0.55 


1.75 


1.05 


Glazed block 


0.6 



TABLE N11 01 .5(2) 
DEFAULT DOOR tAFACTORS 



DOOR TYPE 


U-FACTOR 


Uninsulated metal 


1.2 


Insulated metal 


0.6 


Wood 


0.5 


Insulated, nonmetal edge, max 45% glazing, any glazing double pane 


0.35 



TABLE Nil 01 .5(3) 
DEFAULT GLAZED FENESTRATION SHGC 



SINGLE GLAZED 


DOUBLE GLAZED 


GLAZED BLOCK 


Clear 


Tinted 


Clear 


Tinted 


0.8 


0.7 


0.7 


0.6 


0.6 



SECTION N1 102 
BUILDING THERMAL ENVELOPE 

N1102.1 Insulation and fenestration criteria. The building 
thermal envelope shall meet the requirements of Table 
N1102. 1 based on the climate zone specified in Table Nl lOI .2. 

N1102.1.1 /?-value computation. Insulation material used 
in layers, such as framing cavity insulation and insulating 
sheathing, shall be summed to compute the component 
^- value. The manufacturer's settled i?- value shall be used 
for blown insulation. Computed /^-values shall not include 
an /?- value for other building materials or air films. 

Nl 102.1.2 t/-factor alternative. An assembly with a 
[/-factor equal to or less than that specified in Table 
Nl 102. 1 .2 shall be permitted as an alternative to the /?- value 
in Table Nl 102.1. 

Exception: For mass walls not meeting the criterion for 
insulation location in Section N1102.2.3, the [/-factor 
shall be permitted to be: 

1 . [/-factor of 0. 17 in Climate Zone 1 

2. [/-factor of 0. 14 in Climate Zone 2 

3. [/-factor of 0.12 in Climate Zone 3 

4. [/-factor of 0. 1 in Climate Zone 4 except Marine 

5 . [/-factor of 0.082 in Chmate Zone 5 and Marine 4 



N1102.1.3 Total UA alternative. If the total building thermal 
envelope UA (sum of [/-factor times assembly area) is less 
than or equal to the total UA resulting from using the [/-fac- 
tors in Table Nl 102. 1.2, (multiplied by the same assembly 
area as in the proposed building), the building shall be consid- 
ered in comphance with Table Nl 102. 1 . The UA calculation 
shall be done using a method consistent with the ASHRAE 
Handbook of Fundamentals and shall include the thermal 
bridging effects of framing materials. The SHGC require- 
ments shall be met in addition to UA compliance. 

Nl 102.2 Specific insulation requirements. 

N1102.2.1 Ceilings vt'ith attic spaces. When Section 
Nl 102.1 would require R-38 in the ceiling, R-30 shall be 
deemed to satisfy the requirement for R-38 wherever the 
full height of uncompressed R-30 insulation extends over 
the wall top plate at the eaves. Similarly R-38 shall be 
deemed to satisfy the requirement for R-49 wherever the 
full height of uncompressed R-38 insulation extends over 
the wall top plate at the eaves. 

N1102.2.2 Ceilings without attic spaces. Where Section 
Nl 102.1 would require insulation levels above R-30 and the 
design of the roof/ceihng assembly does not allow sufficient 
space for the required insulation, the minimum required insu- 
lation for such roof/ceihng assembUes shall be R-30. This 
reduction of insulation from the requirements of Section 
Nl 102. 1 shaU be limited to 500 ft^ (46 m^) of ceiUng area. 



318 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



ENERGY EFFICIENCY 



TABLE N1 102.1 
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT 



CLIMATE 
ZONE 


FENESTRATION 
U-FACTOR 


SKYLIGHT" 
U-FACTOR 


GLAZED 

FENESTRATION 

SHGC 


CEILING 
fl-VALUE 


WOOD 

FRAME WALL 

/?- VALUE 


MASS 

WALL 

fl-VALUE 


FLOOR 
ff-VALUE 


BASEMENT^ 

WALL 

fl-VALUE 


SLAB" 

fl-VALUE 

AND DEPTH 


CRAWL 

SPACE WALL 

fl-VALUE 


1 


1.2 


0.75 


0.40 


30 


13 


3 


13 











2 


0.75 


0.75 


0.40 


30 


13 


4 


13 











3 


0.65 


0.65 


0.40^ 


30 


13 


5 


19 








5/13 


4 except 
Marine 


0.40 


0.60 


NR 


38 


13 


5 


19 


10/13 


10, 2 ft 


10/13 


5 and 
Marine 4 


0.35 


0.60 


NR 


38 


19 or 

13 + 5g 


13 


30f 


10/13 


10, 2 ft 


10/13 


6 


0.35 


0.60 


NR 


49 


19 or 

13 + 5S 


15 


30^ 


10/13 


10, 4 ft 


10/13 


7 and 8 


0.35 


0.60 


NR 


49 


21 


19 


30f 


10/13 


10, 4 ft 


10/13 



a. /?-values are minimums. f/-factors and SHGC are maximums. R-19 insulation shall be permitted to be compressed into a 2 X 6 cavity. 

b. The fenestration [/-factor column excludes skylights. The solar heat gain coefficient (SHGC) column applies to all glazed fenestration. 

c. The first R-value applies to continuous insulation, the second to framing cavity insulation; either insulation meets the requirement. 

d. R-5 shall be added to the required slab edge /?- values for heated slabs. 

e. There are no solar heat gain coefficient (SHGC) requirements in the Marine Zone. 

f. Or insulation sufficient to fill the framing cavity, R-19 minimum. 

g. "13+5" means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25% or less of the exterior, R-5 sheathing is not required where 
structural sheathing is used. If structural sheathing covers more than 25% of exterior, structural sheathing shall be supplemented with insulated sheathing of at least 
R-2. 

TABLE Nil 02.1 .2 
EQUIVALENT (/-FACTORS^ 



CLIMATE 
ZONE 


FENESTRATION 
U-FACTOR 


SKYLIGHT 
y-FACTOR 


CEILING 
y-FACTOR 


FRAME 

WALL 

(AFACTOR 


MASS WALL 
U-FACTOR 


FLOOR 
U-FACTOR 


BASEMENT 

WALL 
U-FACTOR 


CRAWL SPACE 

WALL 

U-FACTOR 


1 


1.20 


0.75 


0.035 


0.082 


0.197 


0.064 


0.360 


0.477 


2 


0.75 


0.75 


0.035 


0.082 


0.165 


0.064 


0.360 


0.477 


3 


0.65 


0.65 


0.035 


0.082 


0.141 


0.047 


0.360 


0.136 


4 except 
Marine 


0.40 


0.60 


0.030 


0.082 


0.141 


0.047 


0.059 


0.065 


5 and 
Marine 4 


0.35 


0.60 


0.030 


0.060 


0.082 


0.033 


0.059 


0.065 


6 


0.35 


0.60 


0.026 


0.060 


0.06 


0.033 


0.059 


0.065 


7 and 8 


0.35 


0.60 


0.026 


0.057 


0.057 


0.033 


0.059 


0.065 



a. Nonfenestration {/-factors shall be obtained from measurement, calculation or an approved source. 



N1102.2.3 Mass walls. Mass walls, for the purposes of this 
chapter, shall be considered walls of concrete block, con- 
crete, insulated concrete form (ICF), masonry cavity, brick 
(other than brick veneer), earth (adobe, compressed earth 
block, ranraied earth) and solid timber/logs. The provisions 
of Section Nl 102.1 for mass walls shaU be applicable when 
at least 50 percent of the required insulation /?- value is on the 
exterior of, or integral to, the wall. Walls that do not meet this 
criterion for insulation placement shall meet the wood frame 
wall insulation requirements of Section Nl 102.1. 

Exception: For walls that do not meet this criterion for 
insulation placement, the minimum added insulation 
R- value shall be permitted to be: 



1 . /?-value of 4 in Climate Zone 1 

2. /?- value of 6 in Climate Zone 2 

3. /?- value of 8 in Climate Zone 3 

4. /?- value of 10 in Climate Zone 4 except Marine 

5. i?- value of 13 in climate Zone 5 and Marine 4 

N1102.2.4 Steel-frame ceilings, walls and floors. Steel- 
frame ceilings, walls and floors shall meet the insulation 
requirements of Table Nl 102.2.4 or shall meet the ^/-factor 
requirements in Table N1102.1.2. The calculation of the 
17-factor for a steel-frame envelope assembly shall use a 
series-parallel path calculation method. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



319 



ENERGY EFFICIENCY 



TABLE N1 102.2.4 
STEEL-FRAME CEILING, WALL AND FLOOR INSULATION (ff-VALUE) 


WOOD FRAME R-VALUE REQUIREMENT COLD-FORMED STEEL EQUIVALENT fl-VALUE^ 


Steel Truss Ceilings^ 


R-30 


R-38 or R-30 + 3 or R-26 + 5 


R-38 


R-49 or R-38 + 3 


R-49 


R-38 + 5 


Steel Joist Ceilings'' 


R-30 


R-38 in 2x4 or 2X6 or 2X8 
R-49 in any framing 


R-38 


R-49 in 2 X 4 or 2 X 6 or 2 X 8 or 2 X 10 


Steel Framed Wall 


R-13 


R-13 + 5 or R-15 + 4 or R-21 + 3 


R-19 


R-13 + 9orR-19 + 8orR-25-F7 


R-21 


R-13 +10 or R-19 + 9 or R-25 -i- 8 


Steel Joist Floor 


R-13 


R-19in2x6 
R-19 + R-6in2 X 8 or 2 x 10 


R-19 


R-19 + R-6in2 X 6 
R-19 + R-12in2x 8 or 2 X 10 



For SI: linch = 25.4mm. 

a. Cavity insulation 7?- value is listed first, followed by continuous insulation /?- value. 

b. Insulation exceeding the height of the framing shall cover the framing. 



Nl 102.2.5 Floors. Floor insulation shall be installed to 
maintain permanent contact with the underside of the 
subfloor decking. 

Nl 102.2.6 Basement walls. Exterior walls associated with 
conditioned basements shall be insulated from the top of the 
basement wall down to 10 feet (3048 mm) below grade or to 
the basement floor, whichever is less. Walls associated with 
unconditioned basements shall meet this requirement 
unless the floor overhead is insulated in accordance with 
Sections Nl 102.1 and Nl 102.2.5. 

N1102.2.7 Slab-on-grade floors. Slab-on-grade floors 
with a floor surface less than 12 inches below grade shall be 
insulated in accordance with Table Nl 102. 1 . The insulation 
shall extend downward from the top of the slab on the out- 
side or inside of the foundation wall. Insulation located . 
below grade shall be extended the distance provided in 
Table Nl 102.1 by any combination of vertical insulation, 
insulation extending under the slab or insulation extending 
out from the building. Insulation extending away from the 
building shall be protected by pavement or by a minimum of 
10 inches (254 mm) of soil. The top edge of the insulation 
installed between the exterior wall and the edge of the inte- 
rior slab shall be permitted to be cut at a 45-degree (0.79 rad) 
angle away from the exterior wall. Slab-edge insulation is 
not required in jurisdictions designated by the code official 
as having a very heavy termite infestation. 

N1102.2.8 Crawl space walls. As an alternative to insulating 
floors over crawl spaces, insulation of crawl space walls 
when the crawl space is not vented to the outside is permitted. 



Crawl space wall insulation shall be permanenfly fastened to 
the wall and extend downward from the floor to the finished 
grade level and then vertically and/or horizontally for at least 
an additional 24 inches (610 mm). Exposed earth in unvented 
crawl space foundations shall be covered with a continuous 
vapor retarder. All joints of the vapor retarder shall overlap by 
6 inches (152 mm) and be sealed or taped. The edges of the 
vapor retarder shall extend at least 6 inches (152 mm) up the 
stem wall and shall be attached to the stem wall. 

Nl 102.2.9 Masonry veneer. Insulation shall not be 
required on the horizontal portion of the foundation that 
supports a masonry veneer. 

N1102.2.10 Thermally isolated sunroom insulation. The 

minimum ceiling insulation /?- values shall be R-19 in zones 
1 through 4 and R-24 in zones 5 though 8. The minimum 
wall /?- value shall be R-13 in all zones. New wall(s) separat- 
ing the sunroom from conditioned space shall meet the 
building thermal envelope requirements. 

N1102.3 Fenestration. 

N1102.3.1 {/-factor. An area- weighted average of fenestra- 
tion products shall be permitted to satisfy the (/-factor 
requirements. 

N1102.3.2 Glazed fenestration SHGC. An area-weighted 
average of fenestration products more than 50 percent 
glazed shall be permitted to satisfy the solar heat gain coeffi- 
cient (SHGC) requirements. 

Nl 102.3.3 Glazed fenestration exemption. Up to 15 

; square feet (1.4 m^) of glazed fenestration per dwelling unit 



320 



2006 INTERNATIONAL RESIDENTIAL CODE'* 



ENERGY EFFICIENCY 



shall be permitted to be exempt from f/-factor and solar heat 
gain coefficient (SHGC) requirements in Section Nl 102. 1 . 

Nl 102.3.4 Opaque door exemption. One opaque door 
assembly is exempted from the t/-factor requirement in 
Section Nl 102.1. 

N1102.3.5 Thermally isolated sunroom IZ-factor. For 

zones 4 through 8 the maximum fenestration t/-factor shall 
be 0.50 and the maximum skylight ?7-factor shall be 0.75. 
New windows and doors separating the sunroom from con- 
ditioned space shall meet the building thermal envelope 
requirements. 

Nl 102.3.6 Replacement fenestration. Where some or all 
of an existing fenestration unit is replaced with a new fenes- 
tration product, including sash and glazing, the replacement 
fenestration unit shall meet the applicable requirements for 
[/-factor and solar heat gain coefficient (SHGC) in Table 
N1102.1. 

N1102.4 Air leakage. 

N1102.4.1 Building thermal envelope. The building ther- 
mal envelope shall be durably sealed to limit infiltration. 
The sealing methods between dissimilar materials shall 
allow for differential expansion and contraction. The fol- 
lowing shall be caulked, gasketed, weatherstripped or other- 
wise sealed with an air barrier material, suitable film or solid 
material. 

1. All joints, seams and penetrations. 

2. Site-built windows, doors and skylights. 

3 . Openings between window and door assemblies and 
their respective jambs and framing. 

4. Utility penetrations. 

5. Dropped ceilings or chases adjacent to the thermal 
envelope. 

6. Knee walls. 

7. Walls and ceilings separating the garage from con- 
ditioned spaces. 

8. Behind tubs and showers on exterior walls. 

9. Common walls between dwelling units. 

10. Other sources of infiltration. 

N1102.4.2 Fenestration air leakage. Windows, skylights 
and sliding glass doors shall have an air infiltration rate of 
no more than 0.3 cubic foot per minute per square foot 
[1.5(L/s)/m2], and swinging doors no more than 0.5 cubic 
foot per minute per square foot [2.5(L/s)/m^], when tested 
according to NFRC 400 or AAMAAVDMA/CSA 101/I.S.2/ 
A440 by an accredited, independent laboratory, and listed 
and labeled by the manufacturer. 

Exception: Site-built windows, skylights and doors. 

N1102.4.3 Recessed lighting. Recessed luminaires installed 
in the building thermal envelope shall be sealed to limit air 
leakage between conditioned and unconditioned spaces by 
being: 



1 . IC-rated and labeled with enclosures that are sealed or 
gasketed to prevent air leakage to the ceiling cavity or 
unconditioned space; or 

2. IC-rated and labeled as meeting ASTM E 283 when 
tested at 1 .57 pounds per square foot (75 Pa) pressure 
differential with no more than 2.0 cubic feet per 
minute (0.944 L/s) of air movement from the condi- 
tioned space to the ceiling cavity; or 

3. Located inside an airtight sealed box with clearances 
of at least 0.5 inch (13 mm) from combustible mate- 
rial and 3 inches (76 mm) from insulation. 

Nl 102.5 Moisture control. The building design shall not cre- 
ate conditions of accelerated deterioration from moisture con- 
densation. Above-grade frame walls, floors and ceilings not 
ventilated to allow moisture to escape shall be provided with an 
approved vapor retarder. The vapor retarder shall be installed 
on the warm-in-winter side of the thermal insulation. 

Exceptions: 

1 . In construction where moisture or its freezing will not 
damage the materials. 

2. Frame walls, floors and ceilings in jurisdictions in 
Zones 1, 2, 3, 4A, and 4B. (Crawl space floor vapor 
retarders are not exempted.) 

3. Where other approved means to avoid condensation 
are provided. 

N1102.5.1 Maximum fenestration [/-factor. The area 
weighted average maximum fenestration [/-factor permit- 
ted using tradeoffs from Section N 1102.1.3 in Zones 6 
through 8 shall be 0.55. 

To comply with this section, the maximum [/-factor for 
skylights shall be 0.75 in zones 6 through 8. 



SECTION N1 103 
SYSTEMS 

Nl 103.1 Controls. At least one thermostat shall be installed 
for each separate heating and cooling system. 

Nl 103.1.1 Heat pump supplementary heat. Heat pumps 
having supplementary electric-resistance heat shall have 
controls that, except during defrost, prevent supplemental 
heat operation when the heat pump compressor can meet the 
heating load. 

N1103.2 Ducts. 

N1103.2.1 Insulation. Supply and return ducts shall be 
insulated to a minimum of R-8. Ducts in floor trusses shall 
be insulated to a minimum of R-6. 

Exception: Ducts or portions thereof located completely 
inside the building thermal envelope. 

N1103.2.2 Sealing. Ducts, air handlers, filter boxes and 
building cavities used as ducts shall be sealed. Joints and 
seams shall comply with Section Ml 60 1.3.1. 

N1103.2.3 Building cavities. Building framing cavities 
shall not be used as supply ducts. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



321 



ENERGY EFFICIENCY 



Nl 103.3 Mechanical system piping insulation. Mechanical 
system piping capable of carrying fluids above 105°F (40°C) or 
below 55°F (13°C) shall be insulated to a minimum of R-2. 

Nl 103.4 Circulating hot water systems. All circulating ser- 
vice hot water piping shall be insulated to at least R-2. Circulat- 
ing hot water systems shall include an automatic or readily 
accessible manual switch that can turn off the hot water circu- 
lating pump when the system is not in use. 

Nl 103.5 Mechanical ventilation. Outdoor air intakes and 
exhausts shall have automatic or gravity dampers that close 
when the ventilation system is not operating. 

N1103.6 Equipment sizing. Heating and cooling equipment 
shall be sized as specified in Section M1401.3. 



322 2006 INTERNATIONAL RESIDENTIAL CODE^ 



Part V — Mechanical 



CHAPTER 12 

MECHANICAL ADMINISTRATION 



SECTION M1201 
GENERAL 

M1201.1 Scope. The provisions of Chapters 12 through 24 
shall regulate the design, installation, maintenance, alteration 
and inspection of mechanical systems that are permanently 
installed and used to control environmental conditions within 
buildings. These chapters shall also regulate those mechanical 
systems, system components, equipment and appliances spe- 
cifically addressed in this code. 

M1201.2 Application. In addition to the general administra- 
tion requirements of Chapter 1, the administrative provisions 
of this chapter shall also apply to the mechanical requirements 
of Chapters 13 through 24. 



[EB] SECTION M1 202 
EXISTING MECHANICAL SYSTEMS 

M1202.1 Additions, alterations or repairs. Additions, alter- 
ations, renovations or repairs to a mechanical system shall con- 
form to the requirements for a new mechanical system without 
requiring the existing mechanical system to comply with all of 
the requirements of this code. Additions, alterations or repairs 
shall not cause an existing mechanical system to become 
unsafe, hazardous or overloaded. Minor additions, alterations 
or repairs to existing mechanical systems shall meet the provi- 
sions for new construction, unless such work is done in the 
same manner and arrangement as was in the existing system, is 
not hazardous, and is approved. 

M1202.2 Existing installations. Except as otherwise pro- 
vided for in this code, a provision in this code shall not require 
the removal, alteration or abandonment of, nor prevent the con- 
tinued use and maintenance of, an existing mechanical system 
lawfully in existence at the time of the adoption of this code. 

M1202.3 Maintenance. Mechanical systems, both existing 
and new, and parts thereof shall be maintained in proper operat- 
ing condition in accordance with the original design and in a 
safe and sanitary condition. Devices or safeguards that are 
required by this code shall be maintained in compliance with 
the code edition under which installed. The owner or the 
owner's designated agent shall be responsible for maintenance 
of the mechanical systems. To determine compliance with this 
provision, the building official shall have the authority to 
require a mechanical system to be reinspected. 

2006 INTERNATIONAL RESIDENTIAL CODE® 323 



324 2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 13 

GENERAL MECHANICAL SYSTEM REQUIREMENTS 



SECTION M1301 
GENERAL 

M1301.1 Scope. The provisions of this chapter shall govern 
the installation of mechanical systems not specifically covered 
in other chapters applicable to mechanical systems. Installa- 
tions of mechanical appliances, equipment and systems not 
addressed by this code shall comply with the applicable provi- 
sions of the International Mechanical Code and the Interna- 
tional Fuel Gas Code. 

M1301.1.1 Flood-resistant installation. In areas prone to 
flooding as established by Table R301.2(l), mechanical 
appliances, equipment and systems shall be located or 
installed in accordance with Section R323.1.5. 



SECTION M1302 
APPROVAL 

M1302.1 Listed and labeled. Appliances regulated by this 
code shall be listed and labeled for the application in which 
they are installed and used, unless otherwise approved in accor- 
dance with Section R104.il. 



SECTION M1303 
LABELING OF APPLIANCES 

M1303.1 Label information. A permanent factory-applied 
nameplate(s) shall be affixed to appliances on which shall 
appear, in legible lettering, the manufacturer's name or trade- 
mark, the model number, a serial number and the seal or mark 
of the testing agency. A label shall also include the following: 

1. Electrical appliances. Electrical rating in volts, amperes 
and motor phase; identification of individual electrical 
components in volts, amperes or watts and motor phase; 
and in Btu/h (W) output and required clearances. 

2. Absorption units. Hourly rating in Btu/h (W), minimum 
hourly rating for units having step or automatic modulat- 
ing controls, type of fuel, type of refrigerant, cooling 
capacity in Btu/h (W) and required clearances. 

3. Fuel-burning units. Hourly rating in Btu/h (W), type of 
fuel approved for use with the appliance and required 
clearances. 

4. Electric comfort heating appliances. Name and trade- 
mark of the manufacturer; the model number or equiva- 
lent; the electric rating in volts, amperes and phase; Btu/h 
(W) output rating; individual marking for each electrical 
component in amperes or watts, volts and phase; 
required clearances from combustibles and a seal indi- 
cating approval of the appliance by an approved agency. 

5. Maintenance instructions. Required regular maintenance 
actions and title or publication number for the operation 
and maintenance manual for that particular model and 
type of product. 



SECTION M1 304 
TYPE OF FUEL 

M1304.1 Fuel types. Fuel-fired appliances shall be designed 
for use with the type of fuel to which they will be connected and 
the altitude at which they are installed. Appliances that com- 
prise parts of the building mechanical system shall not be con- 
verted for the use of a different fuel, except where approved and 
converted in accordance with the manufacturer's instructions. 
The fuel input rate shall not be increased or decreased beyond 
the limit rating for the altitude at which the appliance is 
installed. 



SECTION M1305 
APPLIANCE ACCESS 

M1305.1 Appliance access for inspection service, repair and 
replacement. Appliances shall be accessible for inspection, ser- 
vice, repair and replacement without removing permanent con- 
struction, other appliances, or any other piping or ducts not 
connected to the appliance being inspected, serviced, repaired or 
replaced. A level working space at least 30 inches deep and 30 
inches wide (762 mm by 762 mm) shall be provided in front of 
the control side to service an apphance. Installation of room 
heaters shall be permitted with at least an 18-inch (457 mm) 
working space. A platform shall not be required for room heat- 
ers. 

M1305.1.1 Central furnaces. Central furnaces within 
compartments or alcoves shall have a minimum working 
space clearance of 3 inches (76 mm) along the sides, back 
and top with a total width of the enclosing space being at 
least 12 inches (305 mm) wider than the furnace. Furnaces 
having a firebox open to the atmosphere shall have at least a 
6-inch (152 nun) working space along the front combustion 
chamber side. Combustion air openings at the rear or side of 
the compartment shall comply with the requirements of 
Chapter 17. 

Exception: This section shall not apply to replacement 
appliances installed in existing compartments and 
alcoves where the working space clearances are in accor- 
dance with the equipment or appliance manufacturer's 
installation instructions. 

M1305.1.2 Appliances in rooms. Appliances installed in a 
compartment, alcove, basement or similar space shall be 
accessed by an opening or door and an unobstructed pas- 
sageway measuring not less than 24 inches (610 mm) wide 
and large enough to allow removal of the largest appliance 
in the space, provided there is a level service space of not 
less than 30 inches (762 mm) deep and the height of the 
apphance, but not less than 30 inches (762 mm), at the front 
or service side of the appliance with the door open. 

M1305.1.3 Appliances in attics. Attics containing appli- 
ances requiring access shall be provided with an opening 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



325 



GENERAL MECHANICAL SYSTEM REQUIREMENTS 



and a clear and unobstructed passageway large enough to 
allow removal of the largest appliance, but not less than 30 
inches (762 mm) high and 22 inches (559 mm) wide and 
not more than 20 feet (6096 mm) long when measured 
along the centerline of the passageway from the opening to 
the appliance. The passageway shall have continuous solid 
flooring in accordance with Chapter 5 not less than 24 
inches (610 mm) wide. A level service space at least 30 
inches (762 nun) deep and 30 inches (762 mm) wide shall 
be present along all sides of the appliance where access is 
required. The clear access opening dimensions shall be a 
minimum of 20 inches by 30 inches (508 mm) by 762 mm), 
where such dimensions are large enough to allow removal 
of the largest appliance. 

Exceptions: 

1. The passageway and level service space are not 
required where the appliance can be serviced and 
removed through the required opening. 

2. Where the passageway is unobstructed and not 
less than 6 feet (1829 mm) high and 22 inches 
(559 mm) wide for its entire length, the passage- 
way shall be not more than 50 feet (15 250 mm) 
long. 

M1305.1.3.1 Electrical requirements. A luminaire 
controlled by a switch located at the required passage- 
way opening and a receptacle outlet shall be installed at 
or near the appliance location in accordance with Chap- 
ter 38. 

M1305.1.4 Appliances under floors. Underfloor spaces 
containing appliances requiring access shall have an unob- 
structed passageway large enough to remove the largest 
appliance, but not less than 30 inches (762 mm) high and 22 
inches (559 mm) wide, nor more than 20 feet (6096 mm) 
long when measured along the centerline of the passageway 
from the opening to the appliance. A level service space at 
least 30 inches (762 mm) deep and 30 inches (762 mm)wide 
shall be present at the front or service side of the appliance. 
If the depth of the passageway or the service space exceeds 
12 inches (305 mm) below the adjoining grade, the walls of 
the passageway shall be lined with concrete or masonry 
extending 4 inches (102 mm) above the adjoining grade in 
accordance with Chapter 4. The rough-framed access open- 
ing dimensions shall be a minimum of 22 inches by 30 
inches (559 mm by 762 mm), where the dimensions are 
large enough to remove the largest appliance. 

Exceptions: 

1. The passageway is not required where the level 
service space is present when the access is open, 
and the appliance can be serviced and removed 
through the required opening. 

2. Where the passageway is unobstructed and not 
less than 6 feet high (1929 mm) and 22 inches wide 



for its entire length, the passageway shall not be 1 1 
limited in length. | 

M1305.1.4.1 Ground clearance. Appliances supported 
from the ground shall be level and firmly supported on a 
concrete slab or other approved material extending 
above the adjoining ground. Appliances suspended from 
the floor shall have a clearance of not less than 6 inches 
(152 mm) from the ground. 

M1305.1.4.2 Excavations. Excavations for appliance 
installations shall extend to a depth of 6 inches (152 mm) 
below the appHance and 12 inches (305 mm) on all sides, 
except that the control side shall have a clearance of 30 
inches (762 mm). 

M1305.1.4.3 Electrical requirements. A luminaire | 
controlled by a switch located at the required passage- 
way opening and a receptacle outlet shall be installed at 
or near the appliance location in accordance with Chap- 
ter 38. 



SECTION M1 306 

CLEARANCES FROM COMBUSTIBLE 

CONSTRUCTION 

M1306.1 Appliance clearance. Appliances shall be installed 
with the clearances from unprotected combustible materials as 
indicated on the appliance label and in the manufacturer's 
installation instructions. 

M1306.2 Clearance reduction. Reduction of clearances shall 
be in accordance with the appliance manufacturer's instruc- 
tions and Table Ml 306.2. Forms of protection with ventilated 
air space shall conform to the following requirements: 

1. Not less than 1-inch (25 mm) air space shall be provided 
between the protection and combustible wall surface. 

2. Air circulation shall be provided by having edges of the 
wall protection open at least 1 inch (25 n:im). 

3. If the wall protection is mounted on a single flat wall 
away from comers, air circulation shall be provided by 
having the bottom and top edges, or the side and top 
edges open at least 1 inch (25 nmi). 

4. Wall protection covering two walls in a corner shall be 
open at the bottom and top edges at least 1 inch (25 
mm). 

M1306.2.1 Solid fuel appliances. Table M1306.2 shall not 
be used to reduce the clearance required for solid-fuel appli- 
ances listed for installation with minimum clearances of 12 
inches (305 mm) or less. For appliances listed for installa- 
tion with minimum clearances greater than 12 inches (305 
mm). Table M1306.2 shall not be used to reduce the clear- 
ance to less than 12 inches (305 mm). 



326 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



GENERAL MECHANICAL SYSTEM REQUIREMENTS 



TABLE Ml 306.2 
REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION^ "■=■''•«•' a- •^'i" 



TYPE OF PROTECTION APPLIED TO 

AND COVERING ALL SURFACES OF 

COMBUSTIBLE MATERIAL WITHIN THE 

DISTANCE SPECIFIED AS THE 

REQUIRED CLEARANCE WITH NO 

PROTECTION [See Figures Ml 306.1 

and M1 306.2] 


WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, 
VENT CONNECTOR, OR SINGLE WALL METAL PIPE IS: 


36 inches 


18 inches 


12 inches 


9 inches 


6 inches 


Allowable clearances with specified protection (Inches)'' 


Use column 1 for clearances above an appliance or horizontal connector. 
Use column 2 for clearances from an appliance, vertical connector and single-wall metal pipe. 


Above 
column 1 


Sides and 

rear 
column 2 


Above 
column 1 


Sides and 

rear 
column 2 


Above 
column 1 


Sides and 

rear 
column 2 


Above 
column 1 


Sides and 

rear 
column 2 


Above 
column 1 


Sides and 

rear 
column 2 


3 Vj-inch thick masonry wall 
without ventilated air space 


— 


24 


— 


12 


— 


9 


— 


6 


— 


5 


V2-in. insulation board over 1-inch 
glass fiber or mineral wool batts 


24 


18 


12 


9 


9 


6 


6 


5 


4 


3 


24 gage sheet metal over 1-inch 
glass fiber or mineral wool batts 
reinforced with wire on rear face 
with ventilated air space 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 


3V2-inch thick masonry wall with 
ventilated air space 


— 


12 


— 


6 


— 


6 


— 


6 


— 


6 


24 gage sheet metal with ventilated 
air space 


18 


12 


9 


6 


6 


4 


5 


3 


3 


2 


V2-inch thick insulation board with 
ventilated air space 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 


24 gage sheet metal with ventilated 
air space over 24 gage sheet metal 
with ventilated air space 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 


1-inch glass fiber or mineral wool 
batts sandwiched between two 
sheets 24 gage sheet metal with 
ventilated air space. 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 



For SI: 1 inch = 25.4 mm, 1 pound per cubic foot = 16.019 kg/hi^, °C = [(°F)-32/1.8], 1 Btu/(h • ft^ • °F/in.) = 0.001442299 (W/cm^ • °C/cm). 

a. Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing. 

b. Clearances shall be measured from the surface of the heat producing appliance or equipment to the outer surface of the combustible material or combustible assem- 
bly. 

c. Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite appliance or connector 

d. Where all clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described. (See Figures Ml 306.1 and 
M1306.2.) 

e. There shall be at least 1 inch between clearance reduction systems and combustible walls and ceilings for reduction systems using ventilated air space. 

f . If a wall protector is mounted on a single flat wall away from comers, adequate air circulation shall be permitted to be provided by leaving only the bottom and top 
edges or only the side and top edges open with at least a 1-inch air gap. 

g. Mineral wool and glass fiber batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1,500°F. 

h. Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu inch per square foot per hour °F or less. Insulation 

board shall be formed of noncombustible material, 
i. There shall be at least 1 inch between the appliance and the protector In no case shall the clearance between the appliance and the combustible surface be reduced 

below that allowed in this table, 
j. All clearances and thicknesses are minimum; laiger clearances and thicknesses are acceptable, 
k. Listed single-wall connectors shall be permitted to be installed in accordance with the terms of their listing and the manufecturer's instructions. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



327 



GENERAL MECHANICAL SYSTEM REQUIREMENTS 



CONSTRUCTION USING COMBUSTIBLE MATERIAL, 
PLASTERED OR UNPLASTERED 




SHEET METAL OR OTHER 
PROTECTION 



NOTE: "A" equals the required clearance with no protection. "B" equals the reduced clearance permitted in accordance with Table Ml 306.2. The protection applied 
to the construction using combustible material shall extend far enough in each direction to make "C" equal to "A." 

FIGURE M1306.1 
REDUCED CLEARANCE DIAGRAM 




WALL PROTECTOR MOUNTED 
WITH ALL EDGES OPEN 





MOUNTED WITH SIDE AND 
TOP EDGES OPEN 



MOUNTED WITH TOP AND 
BOTTOM EDGES OPEN 



MUST BE MOUNTED WITH 
TOP AND BOTTOM 
EDGES OPEN 




WALL PROTECTOR MOUNTED 
ON SINGLE FLAT WALL 



WALL PROTECTOR 
INSTALLED IN CORNER 



NAIL OR SCREW ANCHOR 



MASONRY WALLS CAN BE ATTACHED TO 
COMBUSTIBLE WALLS USING WALL LINES 

DO NOT USE SPACERS DIRECTLY BEHIND 
APPLIANCE OR CONNECTOR 



A^ 



COMBUSTIBLE 
WALL 



zszszs 



^^ 



1 IN. AIRSPACE 



1 IN. NONCOMBUSTIBLE SPACER 
SUCH AS STACKED WASHERS, 
SMALL DIAMETER PIPE, TUBING OR 
ELECTRICAL CONDUIT 



^ 



CLEARANCE REDUCTION SYSTEM 



For SI: 1 inch = 25.4 mm. 



A^ 



FIGURE M1 306.2 
WALL PROTECTOR CLEARANCE REDUCTION SYSTEM 



328 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



GENERAL MECHANICAL SYSTEM REQUIREMENTS 



SECTION M1307 
APPLIANCE INSTALLATION 

M1307.1 GeneraL Installation of appliances shall conform to 
the conditions of their listing and label and the manufacturer's 
installation instructions. The manufacturer's operating and 
installation instructions shall remain attached to the appliance. 

M1307.2 Anchorage of appliances. Apphances designed to 
be fixed in position shall be fastened or anchored in an 
approved manner. In Seismic Design Categories D, and D2, 
water heaters shall be anchored or strapped to resist horizontal 
displacement caused by earthquake motion. Strapping shall be 
at points within the upper one-third and lower one-third of the 
appliance's vertical dimensions. At the lower point, the strap- 
ping shall maintain a minimum distance of 4 inches (102 mm) 
above the controls. 

M1307.3 Elevation of ignition source. Appliances having an 
ignition source shall be elevated such that the source of ignition 
is not less than 18 inches (457 mm) above the floor in garages. 
For the purpose of this section, rooms or spaces that are not part 
of the living space of a dwelling unit and that communicate 
with a private garage through openings shall be considered to 
be part of the garage. 

M1307.3.1 Protection from impact. Appliances located in 
a garage or carport shall be protected from impact by auto- 
mobiles. 

M1307.4 Hydrogen generating and refueling operations. 

Ventilation shall be required in accordance with Section 
M1307.4.1, M1307.4.2 or M1307.4.3 in private garages that 

(contain hydrogen-generating appliances or refueling systems. 
For the purpose of this section, rooms or spaces that are not part 
of the living space of a dwelling unit and that communicate 
directly with a private garage through openings shall be consid- 
ered to be part of the private garage. 

M1307.4.1 Natural ventilation. Indoor locations intended 
for hydrogen-generating or refueling operations shall be 
limited to a maximum floor area of 850 square feet (79 m^) 
and shall communicate with the outdoors in accordance 
with Sections M1307.4.1.1 and M1307.4.1.2. The maxi- 
mum rated output capacity of hydrogen generating appli- 
ances shall not exceed 4 standard cubic feet per minute (1.9 
L/s) of hydrogen for each 250 square feet (23 m^) of floor 
area in such spaces. The minimum cross-sectional dimen- 
sion of air openings shall be 3 inches (76 mm). Where ducts 
are used, they shall be of the same cross-sectional area as the 
free area of the openings to which they connect. In those 
locations, equipment and appliances having an ignition 
source shall be located so that the source of ignition is not 
within 12 inches (305 mm) of the ceiling. 

M1307.4.1.1 Two openings. Two permanent openings 
shall be constructed within the garage. The upper open- 
ing shall be located entirely within 12 inches (305 mm) 
of the ceiling of the garage. The lower opening shall be 
located entirely within 12 inches (305 mm) of the floor of 
the garage. Both openings shall be constructed in the 
same exterior wall. The openings shall communicate 
directly with the outdoors and shall have a minimum free 
area of V2 square foot per 1,000 cubic feet (1.7 mVlOOO 
m^) of garage volume. 



M1307.4.1.2 Louvers and grilles. In calculating free 
area required by Section Ml 307.4.1, the required size of 
openings shall be based on the net free area of each open- 
ing. If the free area through a design of louver or grille is 
known, it shall be used in calculating the size opening 
required to provide the free area specified. If the design 
and free area are not known, it shall be assumed that 
wood louvers will have a 25 -percent free area and metal 
louvers and grilles will have a 75 -percent free area. Lou- 
vers and grilles shall be fixed in the open position. 

M1307.4.2 Mechanical ventilation. Indoor locations 
intended for hydrogen-generating or refueling operations 
shall be ventilated in accordance with Section 502. 1 6 of the 
International Mechanical Code. In these locations, equip- 
ment and appliances having an ignition source shall be 
located so that the source of ignition is below the mechani- 
cal ventilation outlet(s). 

M1307.4.3 Specially engineered installations. As an alter- 
native to the provisions of Sections Ml 307. 4.1 and 
M1307.4.2, the necessary supply of air for ventilation and 
dilution of flammable gases shall be provided by an approved 
engineered system. 

M1307.5 Electrical appliances. Electrical appliances shall be 
installed in accordance with Chapters 14, 15, 19, 20 and 33 
through 42 of this code. 



SECTION M1308 
MECHANICAL SYSTEMS INSTALLATION 

M1308.1 Drilling and notching. Wood-framed structural 
members shall be drilled, notched or altered in accordance with 
the provisions of Sections R502.8, R602.6, R602.6.1 and 
R802.7. Holes in cold-formed, steel-framed, load-bearing 
members shall be permitted only in accordance with Sections 
R505.2, R603.2 and R804.2. In accordance with the provisions 
of Sections R505.3.5, R603.3.4 and R804.3.5, cutting and 
notching of flanges and lips of cold-formed, steel-framed, 
load-bearing members shall not be permitted. 

M1308.2 Protection against physical damage. In concealed 
locations where piping, other than cast-iron or galvanized steel, 
is installed through holes or notches in studs, joists, rafters or 
similar members less than 1 .5 inches (38 mm) from the nearest 
edge of the member, the pipe shall be protected by shield plates. 
Protective shield plates shall be a minimum of 0.062-inch- 
thick (1 .6 mm) steel, shall cover the area of the pipe where the 
member is notched or bored, and shall extend a minimum of 2 
inches (51 mm) above sole plates and below top plates. 

M1308.3 Foundations and supports. Foundations and sup- 
ports for outdoor mechanical systems shall be raised at least 3 
inches (76 mm) above the finished grade, and shall also con- 
form to the manufacturer's installation instructions. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



329 



330 2006 INTERNATIONAL RESIDENTIAL CODE® 



CHAPTER 14 

HEATING AND COOLING EQUIPMENT 



SECTION M1401 
GENERAL 

M1401.1 Installation. Heating and cooling equipment and 
appliances shall be installed in accordance with the manufac- 
turer's installation instructions and the requirements of this 
code. 

M1401.2 Access. Heating and cooling equipment shall be 
located with respect to building construction and other equip- 
ment to permit maintenance, servicing and replacement. Clear- 
ances shall be maintained to permit cleaning of heating and 
cooling surfaces; replacement of filters, blowers, motors, con- 
trols and vent connections; lubrication of moving parts; and 
adjustments. 

M1401.3 Sizing. Heating and cooling equipment shall be sized 
based on building loads calculated in accordance with ACCA 
Manual J or other approved heating and cooling calculation 
methodologies. 

M1401.4 Exterior installations. Equipment installed out- 
doors shall be listed and labeled for outdoor installation. Sup- 
ports and foundations shall prevent excessive vibration, 
settlement or movement of the equipment. Supports and foun- 
dations shall be level and conform to the manufacturer's instal- 
lation instructions. 

M1401.5 Flood hazard. In areas prone to flooding as estab- 
lished by Table R301.2(l), heating and cooling equipment and 
appliances shall be located or installed in accordance with Sec- 
tion R324. 1.5. 



SECTION M1402 
CENTRAL FURNACES 

M1402.1 General. Oil-fired central furnaces shall conform to 
ANSI/UL 727. Electric furnaces shall conform to UL 1995. 

M1402.2 Clearances. Clearances shall be provided in accor- 
dance with the listing and the manufacturer's installation 
instructions. 

M1402.3 Combustion air. Combustion air shall be supplied in 
accordance with Chapter 17. Combustion air openings shall be 
unobstructed for a distance of not less than 6 inches (152 mm) 
in front of the openings. 



SECTION M1 403 
HEAT PUMP EQUIPMENT 

M1403.1 Heat pumps. The minimum unobstructed total area 
of the outside and return air ducts or openings to a heat pump 
shall be not less than 6 square inches per 1,000 Btu/h (13 208 
mm^/kW) output rating or as indicated by the conditions of the 
listing of the heat pump. Electric heat pumps shall conform to 
UL 1995. 



M1403.2 Foundations and supports. Supports and founda- 
tions for the outdoor unit of a heat pump shall be raised at least 
3 inches (76 mm) above the ground to permit free drainage of 
defrost water, and shall conform to the manufacturer's installa- 
tion instructions. 



SECTION M1 404 
REFRIGERATION COOLING EQUIPMENT 

M1404.1 Compliance. Refrigeration cooling equipment shall 
comply with Section M1411. 



SECTION M1 405 
BASEBOARD CONVECTORS 

M1405.1 General. Electric baseboard convectors shall be 
installed in accordance with the manufacturer's installation 
instructions and Chapters 33 through 42 of this code. 



SECTION M1406 
RADIANT HEATING SYSTEMS 

M1406.1 General. Electric radiant heating systems shall be 
installed in accordance with the manufacturer's installation 
instructions and Chapters 33 through 42 of this code. 

M1406.2 Clearances. Clearances for radiant heating panels or 
elements to any wiring, outlet boxes and junction boxes used 
for installing electrical devices or mounting luminaires shall | 
comply with Chapters 33 through 42 of this code. 

M1406.3 Installation of radiant panels. Radiant panels 
installed on wood framing shall conform to the following 
requirements: 

1. Heating panels shall be installed parallel to framing 
members and secured to the surface of framing members 
or mounted between framing members. 

2. Panels shall be nailed or stapled only through the 
unheated portions provided for this purpose and shall not 
be fastened at any point closer than 74 inch (7 mm) to an 
element. 

3. Unless listed and labeled for field cutting, heating panels 
shall be installed as complete units. 

M1406.4 Installation in concrete or masonry. Radiant heat- 
ing systems installed in concrete or masonry shall conform to 
the following requirements: 

1 . Radiant heating systems shall be identified as being suit- 
able for the installation, and shall be secured in place as 
specified in the manufacturer' s installation instructions. 

2. Radiant heating panels or radiant heating panel sets shall 
not be installed where they bridge expansion joints 
unless protected from expansion and contraction. 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



331 



HEATING AND COOLING EQUIPMENT 



M1406.5 Gypsum panels. Where radiant heating systems are 
used on gypsum assembhes, operating temperatures shall not 
exceed 125°F (52°C). 

M1406.6 Finish surfaces. Finish materials installed over radi- 
ant heating panels or systems shall be installed in accordance 
with the manufacturer's installation instructions. Surfaces shall 
be secured so that nails or other fastenings do not pierce the 
radiant heating elements. 



SECTION l\A1407 
DUCT HEATERS 

M1407.1 General. Electric duct heaters shall be installed in 
accordance with the manufacturer's installation instructions 
and Chapters 33 through 42 of this code. Electric furnaces shall 
be tested in accordance with UL 1995. 

M1407.2 Installation. Electric duct heaters shall be installed 
so that they will not create a fire hazard. Class 1 ducts, duct cov- 
erings and linings shall be interrupted at each heater to provide 
the clearances specified in the manufacturer's installation 
instructions. Such interruptions are not required for duct heat- 
ers listed and labeled for zero clearance to combustible materi- 
als. Insulation installed in the immediate area of each heater 
shall be classified for the maximum temperature produced on 
the duct surface. 

M1407.3 Installation with heat pumps and air condition- 
ers. Duct heaters located within 4 feet (1219 mm) of a heat 
pump or air conditioner shall be listed and labeled for such 
installations. The heat pump or air conditioner shall addition- 
ally be listed and labeled for such duct heater installations. 

M1407.4 Access. Duct heaters shall be accessible for servic- 
ing, and clearance shall be maintained to permit adjustment, 
servicing and replacement of controls and heating elements. 

MI407.5 Fan interlock. The fan circuit shall be provided with 
an interlock to prevent heater operation when the fan is not 
operating. 



3. The furnace register shall be located not less than 12 
inches (305 mm) from doors in any position, draperies or 
similar combustible objects. 

4. The furnace register shall be located at least 5 feet (1524 
mm) below any projecting combustible materials. 

5. The floor furnace burner assembly shall not project into 
an occupied under-floor area. 

6. The floor furnace shall not be installed in concrete floor 
construction built on grade. 

7. The floor furnace shall not be installed where a door can 
swing within 12 inches (305 mm) of the grille opening. 

M1408.4 Access. An opening in the foundation not less than 
18 inches by 24 inches (457 mm by 610 mm), or a trap door not 
less than 22 inches by 30 inches (559 mm by 762 mm) shall be 
provided for access to a floor furnace. The opening and pas- 
sageway shall be large enough to allow replacement of any part 
of the equipment. 

M1408.5 Installation. Floor furnace installations shall con- 
form to the following requirements: 

1 . Thermostats controlling floor furnaces shall be located 
in the room in which the register of the floor furnace is 
located. 

2. Floor furnaces shall be supported independently of the 
furnace floor register. 

3. Floor furnaces shall be installed not closer than 6 inches 
(152 mm) to the ground. Clearance may be reduced to 2 
inches (51 mm), provided that the lower 6 inches (152 
mm) of the furnace is sealed to prevent water entry. 

4 . Where excavation is required for a floor furnace installa- 
tion, the excavation shall extend 30 inches (762 mm) 
beyond the control side of the floor furnace and 12 inches 
(305 mm) beyond the remaining sides. Excavations shall 
slope outward from the perimeter of the base of the exca- 
vation to the surrounding grade at an angle not exceeding 
45 degrees (0.79 rad) from horizontal. 

5. Floor furnaces shall not be supported from the ground. 



SECTION M1 408 
VENTED FLOOR FURNACES 

M1408.1 General. Vented floor furnaces shall conform to UL 
729 and be installed in accordance with their listing, the manu- 
facturer's installation instructions and the requirements of this 
code. 

M1408.2 Clearances. Vented floor Tumaces shall be installed 
in accordance with their listing and the manufacturer's installa- 
tion instructions. 

M1408.3 Location. Location of floor furnaces shall conform 
to the following requirements: 

1 . Floor registers of floor furnaces shall be installed not less 
than 6 inches (152 nmi) from a wall. 

2. Wall registers of floor furnaces shall be installed not less 
than 6 inches (152 mm) from the adjoining wall at inside 
comers. 



SECTION M1 409 
VENTED WALL FURNACES 

M1409.1 General. Vented wall furnaces shall conform to UL 
730 and be installed in accordance with their listing, the manu- 
facturer's installation instructions and the requirements of this 
code. 

M1409.2 Location. The location of vented wall furnaces shall 
conform to the following requirements: 

1 . Vented wall furnaces shall be located where they will not 
cause a fire hazard to walls, floors, combustible furnish- 
ings or doors. Vented wall furnaces installed between 
bathrooms and adjoining rooms shall not circulate air 
from bathrooms to other parts of the building. 

2. Vented wall furnaces shall not be located where a door 
can swing within 12 inches (305 mm) of the furnace air 
inlet or outlet measured at right angles to the opening. 



332 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



HEATING AND COOLING EQUIPMENT 



Doorstops or door closers shall not be installed to obtain 
this clearance. 

M1409.3 Installation. Vented wall furnace installations shall 
conform to the following requirements: 

1. Required wall thicknesses shall be in accordance with 
the manufacturer's installation instructions. 

2. Ducts shall not be attached to a wall furnace. Casing 
extensions or boots shall be installed only when listed as 
part of a listed and labeled appliance. 

3. A manual shut off valve shall be installed ahead of all 
controls. 

M1409.4 Access. Vented wall furnaces shall be provided with 
access for cleaning of heating surfaces; removal of burners; 
replacement of sections, motors, controls, filters and other 
working parts; and for adjustments and lubrication of parts 
requiring such attention. Panels, grilles and access doors that 
must be removed for normal servicing operations shall not be 
attached to the building construction. 



SECTION M1 410 
VENTED ROOM HEATERS 

M1410.1 General. Vented room heaters shall be tested in 
I accordance with ASTM E 1509, UL 896 or UL 1482 and 
installed in accordance with their listing, the manufacturer's 
installation instructions and the requirements of this code. 

M1410.2 Floor mounting. Room heaters shall be installed on 
noncombustible floors or approved assemblies constructed of 
noncombustible materials that extend at least 18 inches (457 
mm) beyond the appliance on all sides. 

Exceptions: 

1. Listed room heaters shall be installed on noncom- 
bustible floors, assemblies constructed of noncom- 
bustible materials or listed floor protectors with mate- 
rials and dimensions in accordance with the appliance 
manufacturer's instructions. 

2. Room heaters listed for installation on combustible 
floors without floor protection shall be installed in 
accordance with the appliance manufacturer's 
instructions. 



SECTION M1 411 
HEATING AND COOLING EQUIPMENT 

M1411.1 Approved refrigerants. Refrigerants used in direct 
refrigerating systems shall conform to the applicable provi- 
sions of ANSI/ASHRAE 34. 

M1411.2 Refrigeration coils in warm-air furnaces. Where a 
cooling coil is located in the supply plenum of a warm-air fur- 
nace, the furnace blower shall be rated at not less than 0.5-inch 
water column (124 Pa) static pressure unless the furnace is 
listed and labeled for use with a cooling coil. Cooling coils 
shall not be located upstream from heat exchangers unless 
listed and labeled for such use. Conversion of existing furnaces 
for use with cooling coils shall be permitted provided the fur- 



nace will operate within the temperature rise specified for the 
furnace. 

M1411.3 Condensate disposal. Condensate from all coohng 
coils or evaporators shall be conveyed from the drain pan outlet 
to an approved place of disposal. Condensate shall not dis- 
charge into a street, alley or other areas where it would cause a 
nuisance. 

M1411.3.1 Auxiliary and secondary drain systems. In 

addition to the requirements of Section M141 1.3, a second- 
ary drain or auxiliary drain pan shall be required for each 
cooling or evaporator coil where damage to any building 
components will occur as a result of overflow from the 
equipment drain pan or stoppage in the condensate drain 
piping. Such piping shall maintain a minimum horizontal I 
slope in the direction of discharge of not less than Vg unit I 
vertical in 12 units horizontal (1 -percent slope). Drain pip- | 
ing shall be a minimum of ^-inch (19 mm) nominal pipe 
size. One of the following methods shall be used: 

1 . An auxiliary drain pan with a separate drain shall be 
installed under the coils on which condensation will 
occur. The auxiliary pan drain shall discharge to a 
conspicuous point of disposal to alert occupants in the 
event of a stoppage of the primary drain. The pan shall 
have a minimum depth of 1.5 inches (38 mm), shall 
not be less than 3 inches (76 mm) larger than the unit 
or the coil dimensions in width and length and shall be 
constructed of corrosion-|;esistant material. Metallic 
pans shall have a minimum thickness of not less than 
0.0276-inch (0.7 mm) galvanized sheet metal. Non- 
metallic pans shall have a minimum thickness of not 
less than 0.0625 inch (1.6 mm). 

2. A separate overflow drain line shall be connected to 
the drain pan provided with the equipment. This over- 
flow drain shall discharge to a conspicuous point of 
disposal to alert occupants in the event of a stoppage 
of the primary drain. The overflow drain line shall 
connect to the drain pan at a higher level than the pri- 
mary drain connection. 

3. An auxiliary drain pan without a separate drain line 
shall be installed under the coils on which condensate 
will occur. This pan shall be equipped with a water 
level detection device conforming to UL 508 that will | 
shut off the equipment served prior to overflow of the 
pan. The auxiliary drain pan shall be constructed in 
accordance with Item 1 of this section. 

4. A water level detection device conforming to UL 508 
shall be provided that will shut off the equipment 
served in the event that the primary drain is blocked. 
The device shall be installed in the primary drain line, 
the overflow drain line or the equipment- supplied 
drain pan, located at a point higher than the primary 
drain line connection and below the overflow rim of 
such pan. 

M1411.3.1.1 Water level monitoring devices. On 

down-flow units and all other coils that have no second- 
ary drain and no means to install an auxiliary drain pan, a 
water-level monitoring device shall be installed inside 
the primary drain pan. This device shall shut off the 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



333 



HEATING AND COOLING EQUIPMENT 



equipment served in the event that the primary drain 
becomes restricted. Externally installed devices and 
devices installed in the drain line shall not be permitted 

M1411.3.2 Drain pipe materials and sizes. Components 
of the condensate disposal system shall be cast iron, galva- 
nized steel, copper, polybutylene, polyethylene, ABS, 
CPVC or PVC pipe or tubing. All components shall be 
selected for the pressure and temperature rating of the 
installation. Condensate waste and drain line size shall be 
not less than ^-inch (19 mm) internal diameter and shall not 
decrease in size from the drain pan connection to the place 
of condensate disposal. Where the drain pipes from more 
than one unit are manifolded together for condensate drain- 
age, the pipe or tubing shall be sized in accordance with an 
approved method. All horizontal sections of drain piping 
shall be installed in uniform alignment at a uniform slope. 

M1411.4 Auxiliary drain pan. Category IV condensing 
appliances shall have an auxiliary drain pan where damage to 
any building component will occur as a result of stoppage in the 
condensate drainage system. These pans shall be installed in 
accordance with the applicable provisions of Section M 141 1.3. 

Exception: Fuel-fired appliances that automatically shut 
down operation in the event of a stoppage in the condensate 
drainage system. 

M1411.5 Insulation of refrigerant piping. Piping and fittings 
for refrigerant vapor (suction) lines shall be insulated with 
insulation having a thermal resistivity of at least R-4 and hav- 
ing external surface permeance not exceeding 0.05 perm [2.87 
ng/(s • m^ • Pa)] when tested in accordance with ASTM E 96. 



M1413.2 Protection of potable water. The potable water sys- 
tem shall be protected from backflow in accordance with the 
provisions in Section P2902. 



SECTION 1414 
FIREPLACE STOVES 

M1414.1 General. Fireplace stoves shall be listed, labeled and 
installed in accordance with the terms of the listing. Fireplace 
stoves shall be tested in accordance with UL 737. 

M1414.2 Hearth extensions. Hearth extensions for fireplace 
stoves shall be installed in accordance with the listing of the 
fireplace stove. The supporting structure for a hearth extension 
for a fireplace stove shall be at the same level as the supporting 
structure for the fireplace unit. The hearth extension shall be 
readily distinguishable from the surrounding floor area. 



SECTION Ml 41 5 
MASONRY HEATERS 

M1415.1 General. Masonry heaters shall be constructed in 
accordance with Section R1002. 



SECTION Ml 41 2 
ABSORPTION COOLING EQUIPMENT 

M1412.1 Approval of equipment. Absorption systems shall 
be installed in accordance with the manufacturer's installation 
instructions. 

M1412.2 Condensate disposal. Condensate from the cooling 
coil shall be disposed of as provided in Section M141 1.3. 

M1412.3 Insulation of piping. Refrigerant piping, brine pip- 
ing and fittings within a building shall be insulated to prevent 
condensation from forming on piping. 

M1412.4 Pressure-relief protection. Absorption systems 
shall be protected by a pressure-relief device. Discharge from 
the pressure-relief device shall be located where it will not cre- 
ate a hazard to persons or property. 



SECTION Ml 41 3 
EVAPORATIVE COOLING EQUIPMENT 

M1413.1 Generah Cooling equipment that uses evaporation 
of water for cooling shall be installed in accordance with the 
manufacturer's installation instructions. Evaporative coolers 
shall be installed on a level platform or base not less than 3 
inches (76 mm) above the adjoining ground and secured to pre- 
vent displacement. Openings in exterior walls shall be flashed 
in accordance with Section R703.8. 



334 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 15 

EXHAUST SYSTEMS 



SECTION M1501 
GENERAL 

M1501.1 Outdoor discharge. The air removed by every 
mechanical exhaust system shall be discharged to the outdoors. 
Air shall not be exhausted into an attic, soffit, ridge vent or 
crawl space. 

Exception: Whole-house ventilation-type attic fans that 
discharge into the attic space of dwelling units having pri- 
vate attics shall be permitted. 



including any transition duct, shall be permitted to be 
in accordance with the dryer manufacturer's installa- 
tion instructions. 

Where large-radius 45-degree (0.8 rad) and 
90-degree (1.6 rad) bends are installed, determination 
of the equivalent length of clothes dryer exhaust duct 
for each bend by engineering calculation in accor- 
dance with the ASHRAE Fundamentals Handbook 
shall be permitted. 



SECTION M1502 
CLOTHES DRYER EXHAUST 

M1502.1 General. Dryer exhaust systems shall be independ- 
ent of all other systems, and shall convey the moisture to the 
outdoors. 

Exception: This section shall not apply to listed and labeled 
condensing (ductless) clothes dryers. 

M1502.2 Duct termination. Exhaust ducts shall terminate on 
the outside of the building. Exhaust duct terminations shall be 
in accordance with the dryer manufacturer's installation 
instructions. Exhaust ducts shall terminate not less than 3 feet 
(914 mm) in any direction from openings into buildings. 
Exhaust duct terminations shall be equipped with a backdraft 
damper. Screens shall not be installed at the duct termination. 

M1502.3 Duct size. The diameter of the exhaust duct shall be 
as required by the clothes dryer's listing and the manufacturer's 
installation instructions. 

M1502.4 Transition ducts. Transition ducts shall not be con- 
cealed within construction. Flexible transition ducts used to 
connect the dryer to the exhaust duct system shall be limited to 
single lengths, not to exceed 8 feet (2438 mm) and shall be 
listed and labeled in accordance with UL 2 158 A. 

M1502.5 Duct construction. Exhaust ducts shall be con- 
structed of minimum 0.016-inch-thick (0.4 mm) rigid metal 
ducts, having smooth interior surfaces with joints running in 
the direction of air flow. Exhaust ducts shall not be connected 
with sheet-metal screws or fastening means which extend into 
the duct. 

M1502.6 Duct length. The maximum length of a clothes dryer 
exhaust duct shall not exceed 25 feet (7620 mm) from the dryer 
location to the wall or roof termination. The maximum length 
of the duct shall be reduced 2.5 feet (762 mm) for each 
45-degree (0.8 rad) bend and 5 feet (1524 mm) for each 
90-degree (1.6 rad) bend. The maximum length of the exhaust 
duct does not include the transition duct. 

Exceptions: 

1 . Where the make and model of the clothes dryer to be 
installed is known and the manufacturer' s installation 
instructions for the dryer are provided to the building 
official, the maximum length of the exhaust duct. 



SECTION M1503 
RANGE HOODS 

M1503.1 General. Range hoods shall discharge to the out- 
doors through a single-wall duct. The duct serving the hood 
shall have a smooth interior surface, shall be air tight and shall 
be equipped with a backdraft damper. Ducts serving range 
hoods shall not terminate in an attic or crawl space or areas 
inside the building. 

Exception: Where installed in accordance with the manu- 
facturer's installation instructions, and where mechanical or 
natural ventilation is otherwise provided, listed and labeled 
ductless range hoods shall not be required to discharge to 
the outdoors. 

M1503.2 Duct material. Single-wall ducts serving range 
hoods shall be constructed of galvanized steel, stainless steel or 
copper. 

Exception: Ducts for domestic kitchen cooking appliances 
equipped with down-draft exhaust systems shall be permit- 
ted to be constructed of schedule 40 PVC pipe provided that 
the installation complies with all of the following: 

1. The duct shall be installed under a concrete slab 
poured on grade; and 

2. The underfloor trench in which the duct is installed 
shall be completely backfilled with sand or gravel; and 

3. The PVC duct shall extend not more than 1 inch (25 
mm) above the indoor concrete floor surface; and 

4. The PVC duct shall extend not more than 1 inch (25 
mm) above grade outside of the building; and 

5. The PVC ducts shall be solvent cemented. 

M1503.3 Kitchen exhaust rates. Where domestic kitchen 
cooking appliances are equipped with ducted range hoods or 
down-draft exhaust systems, the fans shall be sized in accor- 
dance with Section M1507.3. 



SECTION M1504 
INSTALLATION OF MICROWAVE OVENS 

M1504.1 Installation of microwave oven over a cooking 
appliance. The installation of a listed and labeled cooking 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



335 



EXHAUST SYSTEMS 



appliance or microwave oven over a listed and labeled cooking 
appliance shall conform to the terms of the upper appliance's 
listing and label and the manufacturer's installation instruc- 
tions. The microwave oven shall conform to UL 923. 



SECTION Ml 505 
OVERHEAD EXHAUST HOODS 

M1505.1 General. Domestic open-top broiler units shall be 
provided with a metal exhaust hood, not less than 28 gage, with 
V4 inch (6 mm) between the hood and the underside of combus- 
tible material or cabinets . A clearance of at least 24 inches (610 
mm) shall be maintained between the cooking surface and the 
combustible material or cabinet. The hood shall be at least as 
wide as the broiler unit and shall extend over the entire unit. 
Such exhaust hood shall discharge to the outdoors and shall be 
equipped with a backdraft damper or other means to control 
infiltration/exfiltration when not in operation. Broiler units 
incorporating an integral exhaust system, and listed and 
labeled for use without an exhaust hood, need not be provided 
with an exhaust hood. 



SECTION M1 506 
EXHAUST DUCTS 

M1505.1 Ducts. Where exhaust duct construction is not speci- 
fied in this chapter, such construction shall comply with Chap- 
ter 16. 



SECTION M1 507 
MECHANICAL VENTILATION 

M1507.1 GeneraL Where toilet rooms and bathrooms are 
mechanically ventilated, the ventilation equipment shall be 
installed in accordance with this section. 

M1507.2 Recirculation of air. Exhaust air from bathrooms 
and toilet rooms shall not be recirculated within a residence or 
to another dwelling unit and shall be exhausted directly to the 
outdoors. Exhaust air from bathrooms and toilet rooms shall 
not discharge into an attic, crawl space or other areas inside the 
building. 

M1507.3 Ventilation rate. Ventilation systems shall be 
designed to have the capacity to exhaust the minimum air flow 
rate determined in accordance with Table M1507.3. 

TABLE Ml 507.3 

MINIMUM REQUIRED EXHAUST RATES FOR 

ONE- AND TWO-FAMILY DWELLINGS 



AREA TO BE VENTILATED 


VENTILATION RATES 


Kitchens 


100 cfm intermittent or 
25 cfm continuous 


Bathrooms — Toilet Rooms 


Mechanical exhaust capacity of 
50 cfm intermittent or 20 cfm 
continuous 



For SI: 1 cubic foot per minute = 0.00047 19 mVs. 



336 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 16 

DUCT SYSTEMS 



SECTION M1601 
DUCT CONSTRUCTION 

M1601.1 Duct design. Duct systems serving heating, cooling 
and ventilation equipment shall be fabricated in accordance 
with the provisions of this section and ACCA Manual D or 
other approved methods. 

M1601.1.1 Above-ground duct systems. Above-ground 
duct systems shall conform to the following: 

1. Equipment connected to duct systems shall be 
designed to limit discharge air temperature to a maxi- 
mum of 250°F (12rC). 

2. Factory-made air ducts shall be constructed of Class 
or Class 1 materials as designated in Table 
M1601. 1.1(1). 

3.. Fibrous duct construction shall conform to the 
SMACNA Fibrous Glass Duct Construction Stan- 
dards or NAIMA Fibrous Glass Duct Construction 
Standards. 

4. Minimum thickness of metal duct material shall be as 
listed in Table M1601. 1.1(2). Galvanized steel shall 
conform to ASTM A 653. 

5. Use of gypsum products to construct return air ducts 
or plenums is permitted, provided that the air temper- 
ature does not exceed 125°F (52°C) and exposed sur- 
faces are not subject to condensation. 

6. Duct systems shall be constructed of materials having 
a flame spread index not greater than 200. 

7. Stud wall cavities and the spaces between solid floor 
joists to be used as air plenums shall comply with the 
following conditions: 

7.1. These cavities or spaces shall not be used as a 
plenum for supply air. 

7.2. These cavities or spaces shall not be part of a 
required fire-resistance-rated assembly. 

7.3. Stud wall cavities shall not convey air from 
more than one floor level. 



7.4. Stud wall cavities and joist-space plenums 
shall be isolated from adjacent concealed 
spaces by tight-fitting fire blocking in accor- 
dance with Section R602.8. 

TABLE Ml 601 .1.1(1) 
CLASSIFICATION OF FACTORY-MADE AIR DUCTS 



DUCT CLASS 


MAXIMUM FLAME-SPREAD RATING 




1 




25 



M1601.1.2 Underground duct systems. Underground 
duct systems shall be constructed of approved concrete, 
clay, metal or plastic. The maximum duct temperature for 
plastic ducts shall not be greater than 150°F (66°C). Metal 
ducts shall be protected from corrosion in an approved man- 
ner or shall be completely encased in concrete not less than 2 
inches (5 1 mm) thick. Nonmetallic ducts shall be installed 
in accordance with the manufacturer's installation instruc- 
tions. Plastic pipe and fitting materials shall conform to cell 
classification 12454-B of ASTM D 1248 or ASTM D 1784 
and external loading properties of ASTM D 2412. All ducts 
shall slope to an accessible point for drainage. Where 
encased in concrete, ducts shall be sealed and secured prior 
to any concrete being poured. Metallic ducts having an 
approved protective coating and nonmetallic ducts shall be 
installed in accordance with the manufacturer's installation 
instructions. 

M1601.2 Factory-made ducts. Factory-made air ducts or duct 
material shall be approved for the use intended, and shall be 
installed in accordance with the manufacturer's installation 
instructions. Each portion of a factory-made air duct system 
shall bear a hsting and label indicating compliance with UL 
181 and UL 181A or UL 181B. 

M1601.2.1 Duct insulation materials. Duct insulation 
materials shall conform to the following requirements: 

1 . Duct coverings and linings, including adhesives where 
used, shall have a flame spread index not higher than 
25, and a smoke-developed index not over 50 when 
tested in accordance with ASTM E 84, using the speci- 



TABLEM1601.1.1(2) 
GAGES OF METAL DUCTS AND PLENUMS USED FOR HEATING OR COOLING 



TYPE OF DUCT 


SIZE 
(inches) 


MINIMUM THICKNESS 
(inch) 


EQUIVALENT 

GALVANIZED SHEET 

GAGE 


APPROXIMATE 
ALUMINUM 
B & S GAGE 


Round ducts and enclosed rectangular ducts 


14 or less 
over 14 


0.013 
0.016 


30 
28 


26 

24 


Exposed rectangular ducts 


14 or less 
over 14 


0.016 
0.019 


28 
26 


24 

22 



For SI: 1 inch = 25.4 mm. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



337 



DUCT SYSTEMS 



men preparation and mounting procedures of ASTM E 
2231. 

2. Duct coverings and linings shall not flame, glow, 
smolder or smoke when tested in accordance with 
ASTM C 411 at the temperature to which they are 
exposed in service. The test temperature shall not fall 
below 250°F (121 °C). 

3. External duct insulation and factory-insulated flexi- 
ble ducts shall be legibly printed or identified at inter- 
vals not longer than 36 inches (914 mm) with the 
name of the manufacturer; the thermal resistance 
i?- value at the specified installed thickness; and the 
flame spread and smoke-developed indexes of the 
composite materials. All duct insulation product 
/^-values shall be based on insulation only, excluding 
air films, vapor retarders or other duct components, 
and shall be based on tested C- values at 75 °F (24°C) 
mean temperature at the installed thickness, in accor- 
dance with recognized industry procedures. The 
installed thickness of duct insulation used to deter- 
mine its /?-value shall be determined as follows: 

3.1. For duct board, duct liner and factory-made 
rigid ducts not normally subjected to compres- 
sion, the nominal insulation thickness shall be 
used. 

3.2. For ductwrap, the installed thickness shall be 
assumed to be 75 percent (25-percent com- 
pression) of nominal thickness. 

3.3. For factory-made flexible air ducts. The in- 
stalled thickness shall be determined by divid- 
ing the difference between the actual outside 
diameter and nominal inside diameter by two. 

M1601.2.2 Vibration isolators. Vibration isolators 
installed between mechanical equipment and metal ducts 
shall be fabricated from approved materials and shall not 
exceed 10 inches (254 mm) in length. 

M1601.3 Installation. Duct installation shall comply with 
Sections M1601.3.1 through M1601.3.6. 

M1601.3.1 Joints and seams. Joints of duct systems shall be 
made substantially airtight by means of tapes, mastics, 
gasketing or other approved closure systems. Closure sys- 
tems used with rigid fibrous glass ducts shall comply with UL 
181 A and shall be marked "181A-P" for pressure-sensitive 
tape, "181 A-M" for mastic or "181 A-H" for heat- sensitive 
tape. Closure systems used with flexible air ducts and flexible 
air connectors shall comply with UL 18 IB and shall be 
marked "181B-FX" for pressure-sensitive tape or "181B-M" 
for mastic. Duct connections to flanges of air distribution sys- 
tem equipment or sheet metal fittings shall be mechanically 
fastened. Mechanical fasteners for use with flexible nonme- 
tallic air ducts shall comply with UL 18 IB and shall be 
marked 181B-C. Crimp joints for round metal ducts shall 
have a contact lap of at least 1 V2 inches (38 mm) and shall be 
mechanically fastened by means of at least three sheet-metal 
screws or rivets equally spaced around the joint. 

M1601.3.2 Support. Metal ducts shall be supported by 
Vj-inch (13 mm) wide 18-gage metal straps or 12-gage gal- 



vanized wire at intervals not exceeding 10 feet (3048 mm) 
or other approved means. Nonmetallic ducts shall be sup- 
ported in accordance with the manufacturer's installation 
instructions. 

M1601.3.3 Fireblocking. Duct installations shall be 
fireblocked in accordance with Section R602.8. 

M1601.3.4 Duct insulation. Duct insulation shall be 
installed in accordance with the following requirements: 

1. A vapor retarder having a maximum permeance of 
0.05 perm [(2.87 ng/(s m^ Pa)] in accordance with 
ASTM E 96, or aluminum foil with a minimum thick- 
ness of 2 mils (0.05 mm), shall be installed on the 
exterior of insulation on cooling supply ducts that 
pass through nonconditioned spaces conducive to 
condensation. 

2. Exterior duct systems shall be protected against the 
elements. 

3. Duct coverings shall not penetrate a fireblocked wall 
or floor. 

M1601.3.5 Factory-made air ducts. Factory-made air 
ducts shall not be installed in or on the ground, in tile or 
metal pipe, or within masonry or concrete. 

M 1601.3.6 Duct separation. Ducts shall be installed with 
at least 4 inches (102 mm) separation from earth except 
where they meet the requirements of Section M1601.1.2. 

M1601.3.7 Ducts located in garages. Ducts in garages 
shall comply with the requirements of Section R309.1.1. 

M1601.3.8 Flood hazard areas. In areas prone to flooding 
as estabhshed by Table R301.2(l), duct systems shall be 
located or installed in accordance with Section R324.1.5. 

M1601.4 Under-floor plenums. An under-floor space used as 
a supply plenum shall conform to the requirements of this sec- 
tion. Fuel gas lines and plumbing waste cleanouts shall not be 
located within the space. 

M1601.4.1 General. The space shall be cleaned of loose 
combustible materials and scrap, and shall be tighdy 
enclosed. The ground surface of the space shall be covered 
with a moisture barrier having a minimum thickness of 4 
mils (0.1 mm). 

M1601.4.2 Materials. The under-floor space, including the 
sidewall insulation, shall be formed by materials having 
flame-spread ratings not greater than 200 when tested in 
accordance with ASTM E 84. 

M1601.4.3 Furnace connections. A duct shall extend from 
the furnace supply outlet to not less than 6 inches (152 mm) 
below the combustible framing. This duct shall comply with 
the provisions of Section M1601.1. A noncombustible 
receptacle shall be installed below any floor opening into 
the plenum in accordance with the following requirements: 

1 . The receptacle shall be securely suspended from the 
floor members and shall not be more than 18 inches 
(457 mm) below the floor opening. 

2. The area of the receptacle shall extend 3 inches (76 
mm) beyond the opening on all sides. 



338 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



DUCT SYSTEMS 



3. The perimeter of the receptacle shall have a vertical 
lip at least 1 inch (25 mm) high at the open sides. 

M1601.4.4 Access. Access to an under-floor plenum shall 
be provided through an opening in the floor with minimum 
dimensions of 1 8 inches by 24 inches (457 mm by 6 1 mm) . 

M1601.4.5 Furnace controls. The furnace shall be 
equipped with an automatic control that will start the air-cir- 
culating fan when the air in the furnace bonnet reaches a 
temperature not higher than 150°F (66°C). The furnace 
shall additionally be equipped with an approved automatic 
control that limits the outlet air temperature to 200°F 
(93°C). 



SECTION M1 602 
RETURN AIR 

M1602.1 Return air. Return air shall be taken from inside the 
dwelling. Dilution of return air with outdoor air shall be 
permitted. 

M1602.2 Prohibited sources. Outdoor and return air for a 
forced-air heating or cooling system shall not be taken from the 
following locations: 

1. Closer than 10 feet (3048 mm) to an appliance vent out- 
let, a vent opening from a plumbing drainage system or 
the discharge outlet of an exhaust fan, unless the outlet is 
3 feet (914 mm) above the outside air inlet. 

2. Where flammable vapors are present; or where located 
less than 10 feet (3048 mm) above the surface of any 
abutting public way or driveway; or where located at 
grade level by a sidewalk, street, alley or driveway. 

3. A room or space, the volume of which is less than 25 per- 
cent of the entire volume served by such system. Where 
connected by a permanent opening having an area sized 
in accordance with ACCA Manual D, adjoining rooms 
or spaces shall be considered as a single room or space 
for the purpose of determining the volume of such rooms 
or spaces. 

Exception: The minimum volume requirement shall 
not apply where the amount of return air taken from a 
room or space is less than or equal to the amount of 
supply air delivered to such room or space. 

4. A closet, bathroom, toilet room, kitchen, garage, 
mechanical room, furnace room or other dwelling unit. 

5. A room or space containing a fuel-burning appliance 
where such room or space serves as the sole source of 
return air. 

Exceptions: 

1. The fuel-burning appliance is a direct- vent 
appliance or an appliance not requiring a vent in 
accordance with Section Ml 80 1.1 or Chapter 
24. 

2. The room or space complies with the following 
requirements: 

2.1. The return air shall be taken from a 
room or space having a volume exceed- 



ing 1 cubic foot for each 10 Btu/h (9.6 
LAV) of combined input rating of all 
fuel-burning appliances therein. 

2.2. The volume of supply air discharged 
back into the same space shall be 
approximately equal to the volume of 
return air taken from the space. 

2.3. Return-air inlets shall not be located 
within 10 feet (3048 mm) of any appli- 
ance firebox or draft hood in the same 
room or space. 

3. Rooms or spaces containing solid-fuel burning 
appliances, provided that return-air inlets are 
located not less than 10 feet (3048 mm) from 
the firebox of such appliances. 

M1602.3 Inlet opening protection. Outdoor air inlets shall be 
covered with screens having openings that are not less than 
74-inch (6 mm) and not greater than 72-inch (12.7 mm). 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



339 



340 2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 17 

COMBUSTION AIR 



SECTION Ml 701 
GENERAL 

M1701.1 Air supply. Liquid- and solid-fuel-buming appli- 
ances shall be provided with a supply of air for fuel combus- 
tion, draft hood dilution and ventilation of the space in which 
the appliance is installed, in accordance with Section Ml 702 or 
Section Ml 703. The methods of providing combustion air in 
this chapter do not apply to fireplaces, fireplace stoves and 
direct-vent appliances. 

M1701.1.1 Buildings of unusually tight construction. In 

buildings of unusually tight construction, combustion air 
shall be obtained from outside the sealed thermal envelope. 
In buildings of ordinary tightness, insofar as infiltration is 
concerned, all or a portion of the combustion air for 
fuel-burning appliances may be obtained from infiltration 
when the room or space has a volume of 50 cubic feet per 
1,000 Btu/h (4.83 LAV) input. 

M1701.2 Exhaust and ventilation system. Air requirements 
for the operation of exhaust fans, kitchen ventilation systems, 
clothes dryers and fireplaces shall be considered in determin- 
ing the adequacy of a space to provide combustion air. 

M1701.3 Volume dampers prohibited. Volume dampers 
shall not be installed in combustion air openings. 

M1701.4 Prohibited sources. Combustion air ducts and open- 
ings shall not connect appliance enclosures with space in which 
the operation of a fan may adversely affect the flow of combus- 
tion air. Combustion air shall not be obtained from an area in 
which flammable vapors present a hazard. Fuel-fired appli- 
ances shall not obtain combustion air from any of the following 
rooms or spaces: 

1. Sleeping rooms. 

2. Bathrooms. 

3. Toilet rooms. 

Exception: The following appliances shall be permitted to 
obtain combustion air from sleeping rooms, bathrooms and 
toilet rooms: 

1 . Solid fuel-fired appliances provided that the room is 
not a confined space and the building is not of unusu- 
ally tight construction. 

2. Appliances installed in an enclosure in which all com- 
bustion air is taken from the outdoors and the enclo- 
sure is equipped with a solid weatherstripped door 
and self-closing device. 

M1701.5 Opening area. The free area of each opening shall be 
used for determining combustion air. Unless otherwise speci- 
fied by the manufacturer or determined by actual measure- 
ment, the free area shall be considered 75 percent of the gross 
area for metal louvers and 25 percent of the gross area for wood 
louvers. 



M1701.6 Opening location. In areas prone to flooding as 
estabhshed by Table R30 1.2(1), openings shall be located at or 
above the design flood elevation established in Section 
R323.1.5. 



SECTION M1 702 
ALL AIR FROM INSIDE THE BUILDING 

M1702.1 Required volume. Where the volume of the space in 
which fuel-burning appliances are installed is greater than 50 
cubic feet per 1 ,000 Btu/h (4.83 LAV) of aggregate input rating 
in buildings of ordinary tightness, insofar as infiltration is con- 
cerned, normal infiltration shall be regarded as adequate to pro- 
vide combustion air. Rooms communicating directly with the 
space in which the appliances are installed through openings 
not furnished with doors shall be considered part of the 
required volume. 

M1702.2 Confined space. Where the space in which the appli- 
ance is located does not meet the criterion specified in Section 
M1702.1, two permanent openings to adjacent spaces shall be 
provided so that the combined volume of all spaces meets the 
criterion. One opening shall be within 12 inches (305 mm) of 
the top and one within 12 inches (305 mm) of the bottom of the 
space, as illustrated in Figure Ml 702.2. Each opening shall 
have a free area equal to a minimum of 1 square inch per 1 ,000 
Btu/h (2201 mm^/kW) input rating of all appliances installed 
within the space, but not less than 100 square inches (64 415 
mm^). 

M1702.3 Unusually tight construction. Where the space is of 
adequate volume in accordance with Section M1702.1 or Sec- 
tion Ml 702.2, but is within a building sealed so tightiy that 
infiltration air is not adequate for combustion, combustion air 
shall be obtained from outdoors or from spaces freely commu- 
nicating with the outdoors in accordance with Section Ml 703. 



SECTION M1703 
ALL AIR FROM OUTDOORS 

M1703.1 Outdoor air. Where the space in which fuel-burning 
appliances are located does not meet the criterion for indoor air 
specified in Section Ml 702, outside combustion air shall be 
supplied as specified in Section M1703.2. 

M1703.2 Two openings or ducts. Outside combustion air 
shall be supplied through openings or ducts, as illustrated in 
Figures M1703.2(l), M1703.2(2), M1703.2(3) and 
M1703.2(4). One opening shall be within 12 inches (305 mm) 
of the top of the enclosure, and one within 12 inches (305 mm) 
of the bottom of the enclosure. Openings are permitted to con- 
nect to spaces directly communicating with the outdoors, such 
as ventilated crawl spaces or ventilated attic spaces. The same 
duct or opening shall not serve both combustion air openings. 
The duct serving the upper opening shall be level or extend 
upward from the appliance space. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



341 



COMBUSTION AIR 



M1703.2.1 Size of openings. Where directly communicat- 
ing with the outdoors, or where communicating with the 
outdoors by means of vertical ducts, each opening shall 
have a free area of at least 1 square inch per 4,000 Btu/per 
hour (550 mm^/kW) of total input rating of all appliances in 
the space. Where horizontal ducts are used, each opening 
shall have a free area of at least 1 square inch per 2,000 
Btu/per hour ( 1 1 00 mm^/kW) of total input of all appliances 
in the space. Ducts shall be of the same minimum cross-sec- 
tional area as the required free area of the openings to which 
they connect. The minimum cross-sectional dimension of 
rectangular air ducts shall be 3 inches (76 mm). 

M1703.3 Attic combustion air. Combustion air obtained from 
an attic area, as illustrated in Figure M1703.2(3), shall be in 
accordance with the following: 

1. The attic ventilation shall be sufficient to provide the 
required volume of combustion air. 

2. The combustion air opening shall be provided with a 
metal sleeve extending from the appliance enclosure to 
at least 6 inches (152 mm) above the top of the ceiling 
joists and ceiling insulation. 



3. An inlet air duct within an outlet air duct shall be an 
acceptable means of supplying attic combustion air to an 
appliance room provided that the inlet duct extends at 
least 12 inches (305 nmi) above the top of the outlet duct 
in the attic space, as illustrated in Figure M 1703. 3. 

4. The end of ducts that terminate in an attic shall not be 
screened. 

M1703.4 Under-floor combustion air. Combustion air 
obtained from under-floor areas, as illustrated in Figure 
M1703.2(4), shall have free opening areas to the outside equiv- 
alent to not less than twice the required combustion air open- 
ing. 

M1703.5 Opening requirements. Outside combustion air 
openings shall be covered with corrosion-resistant screen or 
equivalent protection having not less than V4-inch (6 mm) 
openings, and not greater than '/j-irich (13 mm) openings. 



CHIMNEY OR VENT 




OPENINGS 



FURNACE 



WATER HEATER 



For SI: 1 square inch = 645.16 mm^, 1 British thermal unit per hour == 0.2931 W. 

NOTE: Each opening shall have a free area of not less than 1 square inch per 1 ,000 Btu/h of the total input rating of all appliances in the enclosure, but not less than 100 
square inches. 

FIGURE M1702.2 
APPLIANCES LOCATED IN CONFINED SPACES— ALL AIR TAKEN FROM ADJACENT SPACES WITHIN THE BUILDING 



342 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



COMBUSTION AIR 



CHIMNEY OR VENT 




WALL OPENING TO THE 
OUTDOORS OR TO AREA 
FREELY COMMUNICATING 
WITH THE OUTDOORS 



FURNACE 



WATER HEATER 



For SI: 1 square inch = 645.16 mm^, 1 British thermal unit per hour = 0.2931 W. 

NOTE: Each opening shall have a free area of not less than 1 square inch per 4,000 Btu/h of the total input rating of all appliances in the enclosure. 

FIGURE M1703.2(1) 

APPLIANCES LOCATED IN CONFINED SPACES— ALL AIR TAKEN 

FROM OUTDOORS THROUGH TWO OPENINGS 



CHIMNEY OR VENT 




FURNACE 



WATER HEATER 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mirf, 1 British thermal unit per hour = 0.2931 W. 

NOTE: Each opening shall have a free area of at least 1 square inch per 2,000 Btu/h of the total input of all apphances in the space. 

FIGURE M1703.2(2) 

APPLIANCES LOCATED IN CONFINED SPACES— ALL AIR TAKEN 

FROM OUTDOORS THROUGH HORIZONTAL DUCTS 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



343 



COMBUSTION AIR 



NO SCREENS ON 
DUCT ENDS 



WITHIN 12 iN. OF 
CEILING 



CONFINED SPACE 



ROOF VENTS 




FURNACE 



WITHIN 12 IN. OF FLOOR 



For SI: 1 inch = 25.4 mm, 1 British thermal unit per hour = 0.2931 W, 1 square inch = 645.16 mm^. 

NOTE: Each opening shall have a free area of at least 1 square inch per 4,000 Btu/h of the total input of all appliances in the space. The attic must be sufficiently vented 
for combustion air to be taken from the attic. 

FIGURE Ml 703.2(3) 
APPLIANCES LOCATED IN CONFINED SPACES— ALL AIR TAKEN FROM OUTDOORS THROUGH VENTILATED ATTIC 



'CHIMNEY OR VENT 



VENTIUTION LOUVERS 
(EACH END OF ATTIC) 



FURNACE 




VENTILATION LOUVERS FOR 
UNHEATED CRAWL SRACE 



For SI: 1 square inch = 645.16 mm^, 1 British thermal unit per hour = 0.2931 W. 

NOTE: The inlet and outlet air openings shall have a free area of not less than I square inch per 4,000 Btu/h of the total input rating of all appliances in the enclosure. 

FIGURE Ml 703.2(4) 

APPLIANCES LOCATED IN CONFINED SPACES— INLET AIR TAKEN FROM 

VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC 



344 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



COMBUSTION AIR 



NO SCREENS ON 
DUCT ENDS 



WITHIN 12 IN. OF- 
CEILING 



CONFINED SPACE • 



ROOF VENTS 




\Z\ 



FURNACE 



r 



) PERMANENT OPENINGS 
/ AND DUCTS 



'WITHIN 12 IN. OF FLOOR 



For SI: 1 inch = 25.4 mm, 1 British thermal unit per hour = 0.2931 V/, 1 square inch = 645.16 mm-^. 

NOTE: Each duct shall have a free area of at least 1 square inch per 4,000 Btu/h of the total input of all appliances in the space. The attic must be sufficiently ventilated 
to provide the required combustion air. 

FIGURE M1703.3 

APPLIANCES LOCATED IN CONFINED SPACES— ALL AIR TAKEN 

FROM OUTDOORS THROUGH VENTILATED ATTIC, INLET DUCT WITHIN OUTLET DUCT 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



345 



346 2006 INTERNATIONAL RESIDENTIAL CODE*' 



CHAPTER 18 

CHIMNEYS AND VENTS 



SECTION Ml 801 
GENERAL 

M1801.1 Venting required. Fuel-burning appliances shall be 
vented to the outdoors in accordance with their listing and label 
and manufacturer's installation instructions except appliances 
listed and labeled for unvented use. Venting systems shall con- 
sist of approved chimneys or vents, or venting assemblies that 
are integral parts of labeled appliances. Gas-fired appliances 
shall be vented in accordance with Chapter 24. 

M1801.2 Draft requirements. A venting system shall satisfy 
the draft requirements of the appliance in accordance with the 
manufacturer's installation instructions, and shall be con- 
structed and installed to develop a positive flow to convey com- 
bustion products to the outside atmosphere. 

M1801.3 Existing chimneys and vents. Where an appUance is 
permanently disconnected from an existing chimney or vent, or 
where an apphance is connected to an existing chimney or vent 
during the process of a new installation, the chimney or vent 
shall comply with Sections M1801.3.1 through M1801.3.4. 

M1801.3.1 Size. The chimney or vent shall be resized as 
necessary to control flue gas condensation in the interior of 
the chimney or vent and to provide the appliance, or appli- 
ances served, with the required draft. For the venting of 
oil-fired appliances to masonry chimneys, the resizing shall 
be done in accordance with NFPA 3 1 . 

M1801.3.2 Flue passageways. The flue gas passageway 
shall be free of obstructions and combustible deposits and 
shall be cleaned if previously used for venting a solid- or liq- 
uid-fuel-burning appliance or fireplace. The flue liner, 
chimney inner wall or vent inner wall shall be continuous 
and free of cracks, gaps, perforations, or other damage or 
deterioration that would allow the escape of combustion 
products, including gases, moisture and creosote. 

M1801.3.3 Cleanout. Masonry chimneys shall be provided 
with a cleanout opening complying with Section RlOOl . 14. 

M1801.3.4 Clearances. Chimneys and vents shall have air- 
space clearance to combustibles in accordance with this 
code and the chimney or vent manufacturer's installation 
instructions. 

Exception: Masonry chimneys equipped with a chim- 
ney lining system tested and listed for installation in 
chimneys in contact with combustibles in accordance 
with UL 1777, and installed in accordance with the man- 
ufacturer's instruction, shall not be required to have a 
clearance between combustible materials and exterior 
surfaces of the masonry chimney. Noncombustible 
firestopping shall be provided in accordance with this 
code. 

M1801.4 Space around lining. The space surrounding a flue 
lining system or other vent installed within a masonry chimney 
shall not be used to vent any other appliance. This shall not pre- 



vent the installation of a separate flue lining in accordance with 
the manufacturer's installation instructions and this code. 

M1801.5 Mechanical draft systems. A mechanical draft sys- 
tem shall be used only with appliances listed and labeled for 
such use. Provisions shall be made to prevent the flow of fuel to 
the equipment when the draft system is not operating. Forced 
draft systems and all portions of induced draft systems under 
positive pressure during operation shall be designed and 
installed to prevent leakage of flue gases into a building. 

M1801.6 Direct-vent appliances. Direct-vent appliances 
shall be installed in accordance with the manufacturer's instal- 
lation instructions. 

M1801.7 Support. Venting systems shall be adequately sup- 
ported for the weight of the material used. 

M1801.8 Duct penetrations. Chimneys, vents and vent con- 
nectors shall not extend into or through supply and return air 
ducts or plenums. 

M1801.9 Fireblocking. Vent and chimney installations shall 
be fireblocked in accordance with Section R602.8. 

M1801.10 Unused openings. Unused openings in any venting 
system shall be closed or capped. 

M1801.il Multiple-appliance venting systems. Two or more 
listed and labeled appliances connected to a common natural 
draft venting system shall comply with the following require- 
ments: 

1 . Appliances that are connected to common venting sys- 
tems shall be located on the same floor of the dwelling. 

Exception: Engineered systems as provided for in 
Section G2427. 

2. Inlets to common venting systems shall be offset such 
that no portion of an inlet is opposite another inlet. 

3. Connectors serving appliances operating under a natural 
draft shall not be connected to any portion of a mechani- 
cal draft system operating under positive pressure. 

M1801.12 Multiple solid fuel prohibited. A sohd-fuel-burn- 
ing appliance or fireplace shall not connect to a chimney pas- 
sageway venting another appliance. 



SECTION M1802 
VENT COMPONENTS 

M1802.1 Draft hoods. Draft hoods shall be located in the 
same room or space as the combustion air openings for the 
appliances. 

M1802.2 Vent dampers. Vent dampers shall comply with Sec- 
tions M1802.2.1 and M1802.2.2. 

M1802.2.1 Manually operated. Manually operated damp- 
ers shall not be installed except in connectors or chimneys 
serving solid-fuel-buming appliances. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



347 



CHIMNEYS AND VENTS 



M1802.2.2 Automatically operated. Automatically oper- 
ated dampers shall conform to UL 17 and be installed in 
accordance with the terms of their listing and label. The 
installation shall prevent firing of the burner when the 
damper is not opened to a safe position. 

M1802.3 Draft regulators. Draft regulators shall be provided 
for oil-fired appliances that must be connected to a chimney. 
Draft regulators provided for solid-fuel-buming appliances to 
reduce draft intensity shall be installed and set in accordance 
with the manufacturer's installation instructions. 

M1802.3.1 Location. Where required, draft regulators 
shall be installed in the same room or enclosure as the appli- 
ance so that no difference in pressure will exist between the 
air at the regulator and the combustion air supply. 



SECTION M1 803 
CHIMNEY AND VENT CONNECTORS 

M1803.1 General. Connectors shall be used to connect 
fuel-burning appliances to a vertical chimney or vent except 
where the chimney or vent is attached directly to the appliance. 

M1803.2 Connectors for oil and solid fuel appliances. Con- 
nectors for oil and solid-fuel-buming appliances shall be con- 
structed of factory-built chimney material, Type L vent 
material or single-wall metal pipe having resistance to corro- 
sion and heat and thickness not less than that of galvanized steel 
as specified in Table M1803.2. 

TABLE M1 803.2 
THICKNESS FOR SINGLE-WALL METAL PIPE CONNECTORS 



DIAMETER OF 
CONNECTOR (inches) 


GALVANIZED SHEET 
METAL GAGE NUMBER 


MINIMUM 
THICKNESS (inch) 


Less than 6 


26 


0.019 


6 to 10 


24 


0.024 


Over 10 through 16 


22 


0.029 



For SI: 1 inch = 25.4 mm. 

M1803.3 Installation. Vent and chimney connectors shall be 
installed in accordance with the manufacturer's installation 
instructions and within the space where the appliance is 
located. Appliances shall be located as close as practical to the 
vent or chimney. Connectors shall be as short and straight as 
possible and installed with a slope of not less than V4 inch (6 mm) 
rise per foot of run. Connectors shall be securely supported and 
joints shall be fastened with sheet metal screws or rivets. 
Devices that obstruct the flow of flue gases shall not be 
installed in a connector unless listed and labeled or approved 
for such installations. 

M1803.3.1 Floor, ceiling and wall penetrations. A chim- 
ney connector or vent connector shall not pass through any 
floor or ceiling. A chimney connector or vent connector 
shall not pass through a wall or partition unless the connec- 
tor is listed and labeled for wall pass-through, or is routed 
through a device listed and labeled for wall pass-through 
and is installed in accordance with the conditions of its list- 
ing and label. Connectors for oil-fired appliances listed and 
labeled for Type L vents, passing through walls or partitions 
shall be in accordance with the following: 



1. Type L vent material for oil appliances shall be 
installed with not less than listed and labeled clear- 
ances to combustible material. 

2. Single-wall metal pipe shall be guarded by a venti- 
lated metal thimble not less than 4 inches (102 mm) 
larger in diameter than the vent connector. A mini- 
mum 6 inches (152 mm) of clearance shall be main- 
tained between the thimble and combustibles. 

M1803.3.2 Length. The horizontal run of an uninsulated 
connector to a natural draft chimney shall not exceed 75 per- 
cent of the height of the vertical portion of the chimney 
above the connector. The horizontal run of a listed connec- 
tor to a natural draft chimney shall not exceed 100 percent of 
the height of the vertical portion of the chimney above the 
connector. 

M1803.3.3 Size. A connector shall not be smaller than the 
flue collar of the appliance. 

Exception: Where installed in accordance with the 
appliance manufacturer's installation instructions. 

M1803.3.4 Clearance. Connectors shall be installed with 
clearance to combustibles as set forth in Table M1803.3.4. 
Reduced clearances to combustible materials shall be in 
accordance with Table M1306.2 and Figure M1306.1. 

TABLE M1 803.3.4 

CHIMNEY AND VENT CONNECTOR CLEAFIANCES 

TO COMBUSTIBLE MATERIALS^ 



TYPE OF CONNECTOR 


MINIMUM 

CLEARANCE 

(inches) 


Single-wall metal pipe connectors: 
Oil and solid-fuel appliances 
Oil appliances listed for use with Type L vents 


18 
9 


Type L vent piping connectors: 
Oil and solid-fuel appliances 
Oil appliances listed for use with Type L vents 


9 

3" 



For SI; 1 inch = 25.4 mm. 

a. These minimum clearances apply to unlisted single-wall chimney and vent 
connectors. Reduction of required clearances is permitted as in Table 
M1306.2. 

b. When hsted Type L vent piping is used, the clearance shall be in accordance 
with the vent listing. 

M1803.3.5 Access. The entire length of a connector shall be 
accessible for inspection, cleaning and replacement. 

M1803.4 Connection to fireplace flue. Connection of appli- 
ances to chimney flues serving fireplaces shall comply with 
Sections M 1 803 .4. 1 through M 1 803 .4.4. 

M1803.4.1 Closure and accessibility. A noncombustible 
seal shall be provided below the point of connection to pre- 
vent entry of room air into the flue. Means shall be provided 
for access to the flue for inspection and cleaning. 

M1803.4.2 Connection to factory-built fireplace flue. A 

different appliance shall not be connected to a flue serving a 
factory-built fireplace unless the appliance is specifically 
listed for such an installation. The connection shall be made 



348 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



CHIMNEYS AND VENTS 



in conformance with the appliance manufacturer's instruc- 
tions. 

Ml 803.4.3 Connection to masonry fireplace flue. A con- 
nector shall extend from the appliance to the flue serving a 
masonry fireplace to convey the flue gases directly into the 
flue. The connector shall be accessible or removable for 
inspection and cleaning of both the connector and the flue. 
Listed direct-connection devices shall be installed in accor- 
dance with their listing. 

M1803.4.4 Size of flue. The size of the fireplace flue shall 
be in accordance with Section Ml 805.3.1. 



SECTION M1804 
VENTS 

M1804.1 Type of vent required. Appliances shall be provided 
with a listed and labeled venting system as set forth in Table 
Ml 804.1. 

TABLE Ml 804.1 
VENT SELECTION CHART 



VENT TYPES 


APPLIANCE TYPES 


Type L oil vents 


Oil-burning appliances listed and 
labeled for venting with Type L vents 


Pellet vents 


Pellet fuel-burning appliances listed and 
labeled for use with pellet vents 



M1804.2 Termination. Vent termination shall comply with 
Sections M1804.2.1 through M1804.2.6. 

M1804.2.1 Tlirougli the roof. Vents passing through a roof 
shall extend through flashing and terminate in accordance 
with the manufacturer's installation requirements. 

M1804.2.2 Decorative slirouds. Decorative shrouds shall 
not be installed at the termination of vents except where the 
shrouds are listed and labeled for use with the specific vent- 
ing system and are installed in accordance with the manu- 
facturer's installation instructions. 

M1804.2.3 Natural draft appliances. Vents for natural 
draft appliances shall terminate at least 5 feet (1524 mm) 
above the highest connected appliance outlet, and natural 
draft gas vents serving wall furnaces shall terminate at an 
elevation at least 12 feet (3658 mm) above the bottom of the 
furnace. 

M1804.2.4 Type L vent. Type L venting systems shall con- 
form to UL 641 and shall terminate with a listed and labeled 
cap in accordance with the vent manufacturer's installation 
instructions not less than 2 feet (610 mm) above the roof and 
not less than 2 feet (610 mm) above any portion of the build- 
ing within 10 feet (3048 mm). 

M1804.2.5 Direct vent terminations. Vent terminals for 
direct- vent appliances shall be installed in accordance with 
the manufacturer's installation instructions. 

M1804.2.6 Mechanical draft systems. Mechanical draft 
systems shall be installed in accordance with their listing. 



the manufacturer's installation instructions and, except for 
direct vent appliances, the following requirements: 

1 . The vent terminal shall be located not less than 3 feet 
(914 mm) above a forced air inlet located within 10 
feet (3048 mm). 

2. The vent terminal shall be located not less than 4 feet 
(1219 mm) below, 4 feet (1219 mm) horizontally 
from, or 1 foot (305 mm) above any door, window or 
gravity air inlet into a dwelling. 

3. The vent termination point shall not be located closer 
than 3 feet (914 mm) to an interior corner formed by 
two walls perpendicular to each other. 

4. The bottom of the vent terminal shall be located at 
least 12 inches (305 mm) above finished ground level. 

5. The vent termination shall not be mounted directly 
above or within 3 feet (914 mm) horizontally of an oil 
tank vent or gas meter. 

6. Power exhauster terminations shall be located not less 
than 10 feet (3048 mm) from lot lines and adjacent 
buildings. 

7. The discharge shall be directed away from the build- 
ing. 

M1804.3 Installation. Type L and pellet vents shall be 
installed in accordance with the terms of their listing and label 
and the manufacturer's installation instructions. 

M1804.3.1 Size of single-appliance venting systems. An 

individual vent for a single appliance shall have a cross-sec- 
tional area equal to or greater than the area of the connector 
to the apphance, but not less than 7 square inches (4515 
mm^) except where the vent is an integral part of a listed and 
labeled appliance. 



SECTION M1805 
MASONRY AND FACTORY-BUILT CHIMNEYS 

M1805.1 General. Masonry and factory-built chimneys shall 
be built and installed in accordance with Sections R1003 and 
R1005, respectively. Flue lining for masonry chimneys shall 
comply with Section R1003.il. 

M1805.2 Masonry chimney connection. A chimney connec- 
tor shall enter a masonry chimney not less than 6 inches (152 
mm) above the bottom of the chimney. Where it is not possible 
to locate the connector entry at least 6 inches (152 mm) above 
the bottom of the chimney flue, a cleanout shall be provided by 
installing a capped tee in the connector next to the chimney. A 
connector entering a masonry chimney shall extend through, 
but not beyond, the wall and shall be flush with the inner face of 
the liner. Connectors, or thimbles where used, shall be firmly 
cemented into the masonry. 

M1805.3 Size of chimney flues. The effective area of a natural 
draft chimney flue for one appliance shall be not less than the 
area of the connector to the appliance. The area of chimney 
flues connected to more than one appliance shall be not less 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



349 



CHIMNEYS AND VENTS 



than the area of the largest connector plus 50 percent of the 
areas of additional chimney connectors. 

Exception: Chimney flues serving oil-fired appliances 
sized in accordance with NFPA 3 1 . 

M1805.3.1 Size of chimney flue for solid-fuel appliance. 

Except where otherwise specified in the manufacturer's 
installation instructions, the cross-sectional area of a flue 
connected to a solid-fuel-burning appliance shall be not less 
than the area of the flue collar or connector, and not larger 
than three times the area of the flue collar. 



350 2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 19 

SPECIAL FUEL-BURNING EQUIPMENT 



SECTION M1901 
RANGES AND OVENS 

M1901.1 Clearances. Freestanding or built-in ranges shall 
have a vertical clearance above the cooking top of not less than 
30 inches (762 mm) to unprotected combustible material. 
Reduced clearances are permitted in accordance with the list- 
ing and labeling of the range hoods or appliances. 

M1901.2 Cooking appliances. Household cooking appli- 
ances shall be listed and labeled and shall be installed in accor- 
dance with the manufacturer's installation instructions. The 
installation shall not interfere with combustion air or access for 
operation and servicing. 



SECTION M1 902 
SAUNA HEATERS 

M1902.1 Locations and protection. Sauna heaters shall be 
protected from accidental contact by persons with a guard of 
material having a low thermal conductivity, such as wood. The 
guard shall have no substantial effect on the transfer of heat 
from the heater to the room. 

M1902.2 Installation. Sauna heaters' shall be installed in 
accordance with the manufacturer's installation instructions. 

M1902.3 Combustion air. Combustion air and venting for a 
nondirect vent-type heater shall be provided in accordance 
with Chapters 17 and 18, respectively. 

M1902.4 Controls. Sauna heaters shall be equipped with a 
thermostat that will limit room temperature to not greater than 
194°F (90°C). Where the thermostat is not an integral part of 
the heater, the heat-sensing element shall be located within 6 
inches (152 mm) of the ceiling. 



SECTION M1 903 
STATIONARY FUEL CELL POWER PLANTS 

M1903.1 General. Stationary fuel cell power plants having a 
power output not exceeding 1,000 kW, shall be tested in accor- 
dance with ANSI Z21.83 and shall be installed in accordance 
with the manufacturer's installation instructions and NFPA 

853. 



SECTION M1 904 
GASEOUS HYDROGEN SYSTEMS 

M1904.1 Installation. Gaseous hydrogen systems shall be 
installed in accordance with the applicable requirements of 
Sections M1307.4 and M1903.1 and the International Fuel 
Gas Code, the International Fire Code and the International 
Building Code. 

2006 INTERNATIONAL RESIDENTIAL CODE® 351 



352 2006 INTERNATIONAL RESIDEENTIAL CODE*^ 



CHAPTER 20 

BOILERS AND WATER HEATERS 



SECTION M2001 
BOILERS 

M2001.1 Installation. In addition to the requirements of this 
code, the installation of boilers shall conform to the manufac- 
turer's instructions. The manufacturer's rating data, the name- 
plate and operating instructions of a permanent type shall be 
attached to the boiler. Boilers shall have all controls set, 
adjusted and tested by the installer. A complete control dia- 
gram together with complete boiler operating instructions shall 
be furnished by the installer. Solid- and liquid-fuel-buming 
boilers shall be provided with combustion air as required by 
Chapter 17. 

M2001.1.1 Standards. Oil-fired boilers and their control 
systems shall be listed and labeled in accordance with UL 
726. Electric boilers and their control systems shall be listed 
in accordance with UL 834. Boilers shall be designed and 
constructed in accordance with the requirements of ASME 
CSD-1 and as applicable, the ASME Boiler and Pressure 
Vessel Code, Sections I and IV. Gas-fired boilers shall con- 
form to the requirements listed in Chapter 24. 

M2001.2 Clearance. Boilers shall be installed in accordance 
with their listing and label. 

M2001.3 Valves. Every boiler or modular boiler shall have a 
shutoff valve in the supply and return piping. For multiple 
boiler or multiple modular boiler installations, each boiler or 
modular boiler shall have individual shutoff valves in the sup- 
ply and return piping. 

Exception: Shutoff valves are not required in a system hav- 
ing a single low-pressure steam boiler. 

M2001.4 Flood-resistant installation. In areas prone to 
flooding as established in Table R301 .2(1), boilers, water heat- 
ers and their control systems shall be located or installed in 
accordance with Section R324.1.5. 



the equipment served. Pressure-relief valves shall be set at the 
maximum rating of the boiler. Discharge shall be piped to 
drains by gravity to within 1 8 inches (457 mm) of the floor or to 
an open receptor. 

M2002.5 Boiler low-water cutoff. All steam and hot water 
boilers shall be protected with a low- water cutoff control. The 
low- water cutoff shall automatically stop the combustion oper- 
ation of the appliance when the water level drops below the 
lowest safe water level as established by the manufacturer. 



SECTION M2003 
EXPANSION TANKS 

M2003.1 General. Hot water boilers shall be provided with 
expansion tanks. Nonpressurized expansion tanks shall be 
securely fastened to the structure or boiler and supported to 
carry twice the weight of the tank filled with water. Provisions 
shall be made for draining nonpressurized tanks without emp- 
tying the system. 

M2003.1.1 Pressurized expansion tanks. Pressurized 
expansion tanks shall be consistent with the volume and 
capacity of the system. Tanks shall be capable of withstand- 
ing a hydrostatic test pressure of two and one-half times the 
allowable working pressure of the system. 

M2003.2 Minimum capacity. The minimum capacity of 
expansion tanks shall be determined from Table M2003.2. 



SECTION M2004 
WATER HEATERS USED FOR SPACE HEATING 

M2004.1 General. Water heaters used to supply both potable 
hot water and hot water for space heating shall be installed in 
accordance with this chapter. Chapter 24, Chapter 28 and the 
manufacturer's installation instructions. 



SECTION M2002 
OPERATING AND SAFETY CONTROLS 

M2002.1 Safety controls. Electrical and mechanical operating 
and safety controls for boilers shall be listed and labeled. 

M2002.2 Hot water boiler gauges. Every hot water boiler 
shall have a pressure gauge and a temperature gauge, or combi- 
nation pressure and temperature gauge. The gauges shall indi- 
cate the temperature and pressure within the normal range of 
the system's operation. 

M2002.3 Steam boiler gauges. Every steam boiler shall have 
a water-gauge glass and a pressure gauge. The pressure gauge 
shall indicate the pressure within the normal range of the sys- 
tem's operation. The gauge glass shall be installed so that the 
midpoint is at the normal water level. 

M2002.4 Pressure-relief valve. Boilers shall be equipped 
with pressure-relief valves with minimum rated capacities for 



SECTION M2005 
WATER HEATERS 

M2005.1 General. Water heaters shall be installed in accor- 
dance with the manufacturer's installation instructions and the 
requirements of this code. Water heaters installed in an attic shall 
conform to the requirements of Section Ml 305. 1.3. Gas-fired 
water heaters shall conform to the requirements in Chapter 24. 
Domestic electric water heaters shall conform to UL 174 or UL 
1453. Commercial electric water heaters shall conform to UL 
1453. Oiled-fired water heaters shall conform to UL 732. 

M2005.2 Prohibited locations. Fuel-fired water heaters shall 
not be installed in a room used as a storage closet. Water heaters 
located in a bedroom or bathroom shall be installed in a sealed 
enclosure so that combustion air will not be taken from the living 
space. Installation of direct- vent water heaters within an enclo- 
sure is not required. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



353 



BOILERS AND WATER HEATERS 



TABLE M2003.2 
EXPANSION TANK MINIMUM CAPACITY^ FOR FORCED HOT-WATER SYSTEMS 



SYSTEM VOLUME" (gallons) 


PRESSURIZED DIAPHRAGM TYPE 


NONPRESSURIZED TYPE 


10 


1.0 


1.5 


20 


1.5 


3.0 


30 


2.5 


4.5 


40 


3.0 


6.0 


50 


4.0 


7.5 


60 


5.0 


9.0 


70 


6.0 


10.5 


80 


6.5 


12.0 


90 


7.5 


13.5 


100 


8.0 


15.0 



For SI: 1 gallon = 3.785 L, 1 pound per square inch giuge = 6.895 kPa, °C = [(°F)-32]/l .8. 

a. Based on average water temperature of 195°F, fill pressure of 12 psig and a maximum operating pressure of 30 psi^ 

b. System volume includes volume of water in boiler, convectors and piping, not including the expansion tank. 



M2005.2.1 Water heater access. Access to water heaters 
that are located in an attic or underfloor crawl space is per- 
mitted to be through a closet located in a sleeping room or 
bathroom where ventilation of those spaces is in accordance 
with this code. 

M2005.3 Electric water heaters. Electric water heaters shall 
also be installed in accordance with the applicable provisions 
of Chapters 33 through 42. 

M2005.4 Supplemental water-heating devices. Potable 
water heating devices that use refrigerant-to-water heat 
exchangers shall be approved and installed in accordance with 
the manufacturer's installation instructions. 



SECTION M2006 
POOL HEATERS 

M2006.1 General. Pool and spa heaters shall be installed in 
accordance with the manufacturer's installation instructions. 
Oil-fired pool heaters shall be tested in accordance with UL 
726. Electric pool and spa heaters shall be tested in accordance 
UL 1261. 

M2006.2 Clearances. In no case shall the clearances interfere 
with combustion air, draft hood or flue terminal relief, or acces- 
sibility for servicing. 

M2006.3 Temperature-limiting devices. Pool heaters shall 
have temperature-relief valves. 

M2006.4 Bypass valves. Where an integral bypass system is 
not provided as a part of the pool heater, a bypass line and valve 
shall be installed between the inlet and outlet piping for use in 
adjusting the flow of water through the heater. 



354 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 21 

HYDRONIC PIPING 



SECTION M21 01 
HYDRONIC PIPING SYSTEMS INSTALLATION 

M2101.1 GeneraL Hydronic piping shall conform to Table 
M2101.1. Approved piping, valves, fittings and connections 
shall be installed in accordance with the manufacturer's instal- 
lation instructions. Pipe and fittings shall be rated for use at the 
operating temperature and pressure of the hydronic system. 
Used pipe, fittings, valves or other materials shall be free of for- 
eign materials. 

M2101.2 System drain down. Hydronic piping systems shall 
be installed to permit draining the system. When the system 
drains to the plumbing drainage system, the installation shall 
conform to the requirements of Chapters 25 through 32 of this 
code. 

M2101.3 Protection of potable water. The potable water sys- 
tem shall be protected from backflow in accordance with the 
provisions listed in Section P2902. 

M2101.4 Pipe penetrations. Openings through concrete or 
masonry building elements shall be sleeved. 

M2101.5 Contact with building material. A hydronic piping 
system shall not be in direct contact with any building material 
that causes the piping material to degrade or corrode. 

M2101.6 Drilling and notching. Wood-framed structural 
members shall be drilled, notched or altered in accordance with 
the provisions of Sections R502.6, R602.6, R602.6.1 and 
R802.6. Holes in cold-formed, steel-framed, load-bearing 
members shall be permitted only in accordance with Sections 
R506.2, R603.2 and R804.2. In accordance with the provisions 
of Sections R505.3.5, R603.3.4 and R804.3.5, cutting and 
notching of flanges and lips of cold-formed, steel-framed, 
load-bearing members shall not be permitted. 

M2101.7 Prohibited tee applications. Fluid in the supply side 
of a hydronic system shall not enter a tee fitting through the 
branch opening. 

M2101.8 Expansion, contraction and settlement. Piping 
shall be installed so that piping, connections and equipment 
shall not be subjected to excessive strains or stresses. Provi- 
sions shall be made to compensate for expansion, contraction, 
shrinkage and structural settiement. 

M2101.9 Piping support. Hangers and supports shall be of 
material of sufficient strength to support the piping, and shall 
be fabricated from materials compatible with the piping mate- 
rial. Piping shall be supported at intervals not exceeding the 
spacing specified in Table M2101.9. 

M2101.10 Tests. Hydronic piping shall be tested hydrostati- 
cally at a pressure of not less than 100 pounds per square inch 
(psi) (690 kPa) for a duration of not less than 15 minutes. 



SECTION M2102 
BASEBOARD CONVECTORS 

M2102.1 General. Baseboard convectors shall be installed in 
accordance with the manufacturer's installation instructions. 
Convectors shall be supported independently of the hydronic 
piping. 



SECTION M21 03 
FLOOR HEATING SYSTEMS 

M2103.1 Piping materials. Piping for embedment in concrete 
or gypsum materials shall be standard-weight steel pipe, cop- 
per tubing, cross-linked polyethylene/aluminum/cross-linked 
polyethylene (PEX-AL-PEX) pressure pipe, chlorinated poly- 
vinyl chloride (CPVC), polybutylene, cross-linked polyethyl- 
ene (PEX) tubing or polypropylene (PP) with a minimum 
rating of 100 psi at 180°F (690 kPa at 82°C). 

M2103.2 Piping joints. Piping joints that are embedded shall 
be installed in accordance with the following requirements: 

1. Steel pipe joints shall be welded. 

2. Copper tubing shall be joined with brazing material hav- 
ing a melting point exceeding 1,000°F (538°C). 

3. Polybutylene pipe and tubing joints shall be installed 
with socket-type heat-fused polybutylene fittings. 

4. CPVC tubing shall be joined using solvent cement joints. 

5. Polypropylene pipe and tubing joints shall be installed 
with socket-type heat-fused polypropylene fittings. 

6. Cross-linked polyethylene (PEX) tubing shall be joined 
using cold expansion, insert or compression fittings. 

M2103.3 Testing. Piping or tubing to be embedded shall be 
tested by applying a hydrostatic pressure of not less than 100 
psi (690 kPa). The pressure shall be maintained for 30 minutes, 
during which all joints shall be visually inspected for leaks. 

SECTION M2104 
LOW TEMPERATURE PIPING 

M2104.1 Piping materials. Low temperature piping for 
embedment in concrete or gypsum materials shall be as indi- 
cated in Table M2 10 1.1. 

M2104.2 Piping joints. Piping joints (other than those in Sec- 
tion M2103.2) that are embedded shall comply with the follow- 
ing requirements: 

1 . Cross-linked polyethylene (PEX) tubing shall be installed 
in accordance with the manufacturer's instructions. 

2. Polyethylene tubing shall be installed with heat fusion 
joints. 

3. Polypropylene (PP) tubing shall be installed in accor- I 
dance with the manufacturer's instructions. I 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



355 



HYDRONIC PIPING 



TABLE M21 01.1 
HYDRONIC PIPING MATERIALS 



MATERIAL 


USE 
CODE^ 


STANDARD" 


JOINTS 


NOTES 


Brass pipe 


1 


ASTM B 43 


Brazed, welded, threaded, 
mechanical and flanged fittings 




Brass tubing 


1 


ASTM B 135 


Brazed, soldered and mechanical 
fittings 




Chlorinated poly (vinyl chloride) (CPVC) 
pipe and tubing 


1,2,3 


ASTM D 2846 


Solvent cement joints, compression 
joints and threaded adapters 




Copper pipe 


1 


ASTM B 42, 
B302 


Brazed, soldered and mechanical 
fittings threaded, welded and 
flanged 




Copper tubing 
(type K, L or M) 


1,2 


ASTM B 75, 

B88,B251, 

B306 


Brazed, soldered and flared 
mechanical fittings 


Joints embedded in concrete 


Cross-linked polyethylene (PEX) 


1,2,3 


ASTM F 876, 
F877 


(See PEX fittings) 


Install in accordance with 
manufacturer's instructions. 


Cross-linked polyethylene/aluminum/ 
cross-Unkedpolyethylene-(PEX-AL-PEX) 
pressure pipe 


1,2 


ASTM F 1281 or 

CAN/ CSA 

B137.10 


Mechanical, crimp/insert 


Install in accordance with 
manufacturer's instructions. 


PEX Fittings 




ASTM F 1807 
ASTM F 1960 
ASTM F 2098 


Copper-crimp/insert fittings, cold 
expansion fittings, stainless steel 
clamp, insert fittings 


Install in accordance with 
manufacturer's instructions 


Plastic fittings PEX 




ASTM F 1807 






Polybutylene (PB) pipe and tubing 


1,2,3 


ASTM D 3309 


Heat-fusion, crimp/insert and 
compression 


Joints in concrete shall be 
heat-fused. 


Polyethylene (PE) pipe, tubing and fittings 
(for ground source heat pump loop 
systems) 


1,2,4 


ASTM D 2513 
ASTM D 3350 
ASTM D 2513 
ASTM D 3035 
ASTM D 2447 
ASTM D 2683 
ASTM F 1055 
ASTM D 2837 
ASTM D 3350 
ASTM D 1693 




Heat-fusion 




Polyproplylene (PP) 


1,2,3 


ISO 15874 
ASTM F 2389 


Heat-fusion joints, mechanical 
fittings, threaded adapters, 
compression joints 




Soldering fluxes 


1 


ASTM B 813 


Copper tube joints 




Steel pipe 


1,2 


ASTM A 53; 
A 106 


Brazed, welded, threaded, flanged 
and mechanical fittings 


Joints in concrete shall be 
welded. Galvanized pipe shall 
not be welded or brazed. 


Steel tubing 


1 


ASTM A 254 


Mechanical fittings, welded 





For SI: °C = [(°F)-32]/1.8. 

a. Use code: 

1. Above ground. 

2. Embedded in radiant systems. 

3. Temperatures below 180°F only. 

4. Low temperature (below 130°F) applications only. 

b. Standards as listed in Chapter 43. 



356 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



HYDRONIC PIPING 



TABLEM2101.9 
HANGER SPACING INTERNALS 



PIPING MATERIAL 


MAXIMUM HORIZONTAL SPACING 
(feet) 


MAXIMUM VERTICAL SPACING 
(feet) 


ABS 


4 


10 


CPVC < 1 inch pipe or tubing 


3 


5 


CPVC >lV4inch 


4 


10 


Copper or copper alloy pipe 


12 


10 


Copper or copper alloy tubing 


6 


10 


PB pipe or tubing 


2.67 


4 


PE pipe or tubing 


2.67 


4 


PEX tubing 


2.67 


4 


PP < 1 inch pipe or tubing 


2.67 


4 


PP> lV4inch 


4 


5 


PVC 


4 


10 


Steel pipe 


12 


15 


Steel tubing 


8 


10 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

M2104.2.1 Polyethylene plastic pipe and tubing for 
ground source heat pump loop systems. Joints between 
polyethylene plastic pipe and tubing or fittings for ground 
source heat pump loop systems shall be heat fusion joints 
conforming to Section M2 104.2. 1.1, electrofusion joints 
conforming to Section M2104.2.1.2 or stab-type insertion 
joints conforming to Section M2104.2.1.3. 

M2104.2.1.1 Heat-fusion joints. Joints shall be of the 
socket-fusion, saddle-fusion or butt-fusion type, fabri- 
cated in accordance with the piping manufacturer's 
instructions. Joint surfaces shall be clean and free of 
moisture. Joint surfaces shall be heated to melt tempera- 
tures and joined. The joint shall be undisturbed until 
cool. Fittings shall be manufactured in accordance with 
ASTM D 2683. 

M2104.2.1.2 Electrofusion joints. Joint surfaces shall 
be clean and free of moisture, and scoured to expose vir- 
gin resin. Joint surfaces shall be heated to melt tempera- 
tures for the period of time specified by the 
manufacturer. The joint shall be undisturbed until cool. 
Fittings shall be manufactured in accordance with 
ASTM F 1055. 

M2104.2.1.3 Stab-type insert fittings. Joint surfaces 
shall be clean and free of moisture. Pipe ends shall be 
chamfered and inserted into the fitting to full depth. Fit- 
tings shall be manufactured in accordance with ASTM D 
2513. 



SECTION M2105 

GROUND SOURCE HEAT PUMP SYSTEM LOOP 

PIPING 

M2105.1 Testing. The assembled loop system shall be pres- 
sure tested with water at 100 psi (690 kPa) for 30 minutes with 
no observed leaks before connection (header) trenches are 
backfilled. Flow rates and pressure drops shall be compared to 
calculated values. If actual flow rate or pressure drop figures 
differ from calculated values by more than 10 percent, the 
problem shall be identified and corrected. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



357 



358 2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 22 

SPECIAL PIPING AND STORAGE SYSTEMS 



SECTION I\/I2201 
OIL TANKS 

M2201.1 Materials. Supply tanks shall be listed and labeled 
and shall conform to UL 58 for underground tanks and UL 80 
for indoor tanks. 

M2201.2 Above-ground tanks. The maximum amount of fuel 
oil stored above ground or inside of a building shall be 660 gal- 
lons (2498 L). The supply tank shall be supported on rigid 
noncombustible supports to prevent settling or shifting. 

M2201.2.1 Tanks within buildings. Supply tanks for use 
inside of buildings shall be of such size and shape to permit 
installation and removal from dwellings as whole units. 
Supply tanks larger than 10 gallons (38 L) shall be placed 
not less than 5 feet (1524 mm) from any fire or flame either 
within or external to any fuel-burning appliance. 

M2201.2.2 Outside above-ground tanks. Tanks installed 
outside above ground shall be a minimum of 5 feet (1524 
mm) from an adjoining property line. Such tanks shall be 
suitably protected from the weather and from physical dam- 
age. 

M2201.3 Underground tanks. Excavations for underground 
tanks shall not undermine the foundations of existing struc- 
tures. The clearance from the tank to the nearest wall of a base- 
ment, pit or property line shall not be less than 1 foot (305 mm). 
Tanks shall be set on and surrounded with noncorrosive inert 
materials such as clean earth, sand or gravel well tamped in 
place. Tanks shall be covered with not less than 1 foot (305 
mm) of earth. Corrosion protection shall be provided in accor- 
dance with Section M2203.7. 

M2201.4 Multiple tanks. Cross connection of two supply 
tanks shall be permitted in accordance with Section M2203.6. 

M2201.5 Oil gauges. Inside tanks shall be provided with a 
device to indicate when the oil in the tank has reached a prede- 
termined safe level. Glass gauges or a gauge subject to break- 
age that could result in the escape of oil from the tank shall not 
be used. 

M2201.6 Flood-resistant installation. In areas prone to 
flooding as established by Table R301.2(l), tanks shall be 
installed at or above the design flood elevation established in 
Section R323 or shall be anchored to prevent flotation, collapse 
and lateral movement under conditions of the design flood. 

M2201.7 Tanks abandoned or removed. Exterior above- 
grade fill piping shall be removed when tanks are abandoned or 
removed. Tank abandonment and removal shall be in accordance 
with the International Fire Code. 



SECTION M2202 
OIL PIPING, FITTING AND CONNECTIONS 

M2202.1 Materials. Piping shall consist of steel pipe, copper 
tubing or steel tubing conforming to ASTM A 539. Aluminum 



tubing shall not be used between the fuel-oil tank and the 
burner units. 

M2202.2 Joints and fittings. Piping shall be connected with 
standard fittings compatible with the piping material. Cast iron 
fittings shall not be used for oil piping. Unions requiring gas- 
kets or packings, right or left couplings, and sweat fittings 
employing solder having a melting point less than 1,000°F 
(538°C) shall not be used for oil piping. Threaded joints and 
connections shall be made tight with a lubricant or pipe thread 
compound. 

M2202.3 Flexible connectors. Flexible metal hose used 
where rigid connections are impractical or to reduce the effect 
of jarring and vibration shall be listed and labeled in accor- 
dance with UL 536 and shall be installed in compliance with its 
label and the manufacturer's installation instructions. Connec- 
tors made from combustible materials shall not be used inside 
of buildings or above ground outside of buildings. 



SECTION M2203 
INSTALLATION 

M2203.1 General. Piping shall be installed in a manner to 
avoid placing stresses on the piping, and to accommodate 
expansion and contraction of the piping system. 

M2203.2 Supply piping. Supply piping used in the installation 
of oil burners and appliances shall be not smaller than Vg-inch 
(9 mm) pipe or Vg-inch (9 mm) outside diameter tubing. Copper 
tubing and fittings shall be a minimum of Type L. 

M2203.3 Fill piping. Fill piping shall terminate outside of 
buildings at a point at least 2 feet (610 mm) from any building 
opening at the same or lower level. Fill openings shall be 
equipped with a tight metal cover. 

M2203.4 Vent piping. Vent piping shall be not smaller than 
lV4-inch (32 mm) pipe. Vent piping shall be laid to drain 
toward the tank without sags or traps in which the liquid can 
collect. Vent pipes shall not be cross connected with fill pipes, 
lines from burners or overflow lines from auxiliary tanks. The 
lower end of a vent pipe shall enter the tank through the top and 
shall extend into the tank not more than 1 inch (25 mm). 

M2203.5 Vent termination. Vent piping shall terminate out- 
side of buildings at a point not less than 2 feet (610 mm), mea- 
sured vertically or horizontally, from any building opening. 
Outer ends of vent piping shall terminate in a weather-proof 
cap or fitting having an unobstructed area at least equal to the 
cross-sectional area of the vent pipe, and shall be located suffi- 
ciently above the ground to avoid being obstructed by snow and 
ice. 

M2203.6 Cross connection of tanks. Cross connection of two 
supply tanks, not exceeding 660 gallons (2498 L) aggregate 
capacity, with gravity flow from one tank to another, shall be 
acceptable providing that the two tanks are on the same hori- 
zontal plane. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



359 



SPECIAL PIPING AND STORAGE SYSTEMS 



M2203.7 Corrosion protection. Underground tanks and bur- 
ied piping shall be protected by corrosion-resistant coatings or 
special alloys or fiberglass-reinforced plastic. 



SECTION M2204 
OIL PUMPS AND VALVES 

M2204.1 Pumps. Oil pumps shall be positive displacement 
types that automatically shut off the oil supply when stopped. 
Automatic pumps shall be listed and labeled in accordance 
with UL 343 and shall be installed in accordance with their list- 
ing. 

M2204.2 Shutoff valves. A readily accessible manual shutoff 
valve shall be installed between the oil supply tank and the 
burner. Where the shutoff valve is installed in the discharge line 
of an oil pump, a pressure-relief valve shall be incorporated to 
bypass or return surplus oil. 

M2204.3 Maximum pressure. Pressure at the oil supply inlet 
to an appliance shall be not greater than 3 pounds per square 
inch (psi) (20.7 kPa). 

M2204.4 Relief valves. Fuel-oil lines incorporating heaters 
shall be provided with relief valves that will discharge to a 
return line when excess pressure exists. 



360 2006 INTERNATIONAL RESIDENTIAL CODE*^ 



CHAPTER 23 

SOLAR SYSTEMS 



SECTION M2301 
SOLAR ENERGY SYSTEMS 

M2301.1 General. This section provides for the design, con- 
struction, installation, alteration and repair of equipment and 
systems using solar energy to provide space heating or cooling, 
hot water heating and swimming pool heating. 

M2301.2 Installation. Installation of solar energy systems 
shall comply with Sections M230 1.2.1 through M230 1.2.9. 

M2301.2.1 Access. Solar energy collectors, controls, 
dampers, fans, blowers and pumps shall be accessible for 
inspection, maintenance, repair and replacement. 

M2301.2.2 Roof-mounted collectors. The roof shall be 
constructed to support the loads imposed by roof-mounted 
solar collectors. Roof-mounted solar collectors that serve as 
a roof covering shall conform to the requirements for roof 
coverings in Chapter 9 of this code. Where mounted on or 
above the roof coverings, the collectors and supporting 
structure shall be constructed of noncombustible materials 
or fire-retardant-treated wood equivalent to that required for 
the roof construction. 

M2301.2.3 Pressure and temperature relief. System 
components containing fluids shall be protected with pres- 
sure- and temperature-relief valves. Relief devices shall be 
installed in sections of the system so that a section cannot be 
valved off or isolated from a relief device. 

M2301.2.4 Vacuum relief. System components that might 
be subjected to pressure drops below atmospheric pressure 
during operation or shutdown shall be protected by a vac- 
uum-relief valve. 

M2301.2.5 Protection from freezing. System components 
shall be protected from damage resulting from freezing of 
heat-transfer liquids at the winter design temperature pro- 
vided in Table R301.2(l). Freeze protection shall be pro- 
vided by heating, insulation, thermal mass and heat transfer 
fluids with freeze points lower than the winter design tem- 
perature, heat tape or other approved methods, or combina- 
tions thereof. 

Exception: Where the winter design temperature is 
greater than 32°F (0°C). 

M2301.2.6 Expansion tanks. Expansion tanks in solar 
energy systems shall be installed in accordance with Section 
M2003 in closed fluid loops that contain heat transfer fluid. 

M2301.2.7 Roof and wall penetrations. Roof and wall 
penetrations shall be flashed and sealed in accordance with 
Chapter 9 of this code to prevent entry of water, rodents and 
insects. 

M2301.2.8 Solar loop isolation. Valves shall be installed to 
allow the solar collectors to be isolated from the remainder 
of the system. Each isolation valve shall be labeled with the 
open and closed position. 



M2301.2.9 Maximum temperature limitation. Systems 
shall be equipped with means to limit the maximum water 
temperature of the system fluid entering or exchanging heat 
with any pressurized vessel inside the dwelling to 180°F 
(82°C). This protection is in addition to the required temper- 
ature- and pressure-relief valves required by Section 
M2301.2.3. 

M2301.3 Labeling. Labeling shall comply with Sections 
M2301.3.1andM2301.3.2. 

M2301.3.1 Collectors. Collectors shall be listed and 
labeled to show the manufacturer's name, model number, 
serial number, collector weight, collector maximum allow- 
able temperatures and pressures, and the type of heat trans- 
fer fluids that are compatible with the collector. The label 
shall clarify that these specifications apply only to the col- 
lector. 

M2301.3.2 Thermal storage units. Pressurized thermal 
storage units shall be Usted and labeled to show the manu- 
facturer's name, model number, serial number, storage unit 
maximum and minimum allowable operating temperatures 
and pressures, and the type of heat transfer fluids that are 
compatible widi the storage unit. The label shall clarify that 
these specifications apply only to the thermal storage unit. 

M2301.4 Prohibited heat transfer fluids. Flammable gases 
and liquids shall not be used as heat transfer fluids. 

M2301.5 Backflow protection. Connections from the potable 
water supply to solar systems shall comply with Section 
P2902.4.5. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



361 



362 2006 INTERNATIONAL RESIDENTIAL CODE'' 



Part VI — Fuel Gas 



CHAPTER 24 

FUEL GAS 



The text of this chapter is excerpted from the 2006 edition of the International Fuel Gas Code and has been modified where neces- 
sary to make such text conform to the scope of apphcation of the International Residential Code for One- and Two-Family Dwell- 
ings. The section numbers appearing in parentheses after each section number represent the location of the corresponding text in the 
International Fuel Gas Code. 



SECTION G2401 (101) 
GENERAL 

G2401.1 (101.2) Application. This chapter covers those fuel- 
gas piping systems, fuel-gas utilization equipment and related 
accessories, venting systems and combustion air configurations 
most commonly encountered in the construction of one- and 
two-family dwellings and structures regulated by this code. 

Coverage of piping systems shall extend from the point of 
delivery to the outlet of the equipment shutoff valves (see 
"Point of delivery"). Piping systems requirements shall include 
design, materials, components, fabrication, assembly, installa- 
tion, testing, inspection, operation and maintenance. Require- 
ments for gas utilization equipment and related accessories 
shall include installation, combustion and ventilation air and 
venting and connections to piping systems. 

The omission from this chapter of any material or method of 
installation provided for in the International Fuel Gas Code 
shall not be construed as prohibiting the use of such material or 
method of installation. Fuel-gas piping systems, fuel-gas utili- 
zation equipment and related accessories, venting systems and 
combustion air configurations not specifically covered in these 
chapters shall comply with the applicable provisions of the 
International Fuel Gas Code. 

Gaseous hydrogen systems shall be regulated by Chapter 7 
of the International Fuel Gas Code. 

This chapter shall not apply to the following: 

1. Liquified natural gas (LNG) installations. 

2. Temporary LP-gas piping for buildings under con- 
struction or renovation that is not to become part of 
the permanent piping system. 

3 . Except as provided in Section G24 1 2. 1 . 1 , gas piping, 
meters, gas pressure regulators, and other appurte- 
nances used by the serving gas supplier in the distri- 
bution of gas, other than undiluted LP-gas. 

4. Portable LP-gas equipment of all types that is not con- 
nected to a fixed fuel piping system. 

5. Portable fuel cell appliances that are neither con- 
nected to a fixed piping system nor interconnected to 
a power grid. 

6. Installation of hydrogen gas, LP-gas and compressed 
natural gas (CNG) systems on vehicles. 



SECTION G2402 (201) 
GENERAL 

G2402.1 (201.1) Scope. Unless otherwise expressly stated, the 
following words and terms shall, for the purposes of this chap- 
ter, have the meanings indicated in this chapter. 

G2402.2 (201.2) Interchangeability. Words used in the pres- 
ent tense include the future; words in the masculine gender 
include the feminine and neuter; the singular number includes 
the plural and the plural, the singular. 

G2402.3 (201.3) Terms defined in other codes. Where terms 
are not defined in this code and are defined in the ICC Electri- 
cal Code, International Building Code, International Fire 
Code, International Mechanical Code ox International Plumb- 
ing Code, such terms shall have meanings ascribed to them as 
in those codes. 



SECTION G2403 (202) 
GENERAL DEFINITIONS 

AIR CONDITIONING, GAS FIRED. A gas-burning, auto- 
matically operated appliance for supplying cooled and/or 
dehumidified air or chilled liquid. 

AIR, EXHAUST. Air being removed from any space or piece 
of equipment and conveyed directly to the atmosphere by 
means of openings or ducts. 

AIR-HANDLING UNIT. A blower or fan used for the pur- 
pose of distributing supply air to a room, space or area. 

AIR, MAKEUP. Air that is provided to replace air being 
exhausted. 

ALTERATION. A change in a system that involves an exten- 
sion, addition or change to the arrangement, type or purpose of 
the original installation. 

ANODELESS RISER. A transition assembly in which plastic 
piping is installed and terminated above ground outside of a 
building. 

APPLIANCE (EQUIPMENT). Any apparatus or equipment 
that utilizes gas as a fuel or raw material to produce light, heat, 
power, refrigeration or air conditioning. 

APPLIANCE, FAN-ASSISTED COMBUSTION. An apph- 
ance equipped with an integral mechanical means to either 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



363 



FUEL GAS 



draw or force products of combustion through the combustion 
chamber or heat exchanger. 

APPLIANCE, AUTOMATICALLY CONTROLLED. 

Apphances equipped with an automatic burner ignition and 
safety shut-off device and other automatic devices, which 
accomplish complete turn-on and shut-off of the gas to the main 
burner or burners, and graduate the gas supply to the burner or 
burners, but do not affect complete shut-off of the gas. 

APPLIANCE, UNVENTED. An appliance designed or 
installed in such a manner that the products of combustion are 
not conveyed by a vent or chimney directly to the outside atmo- 
sphere. 

APPLIANCE, VENTED. An appliance designed and 
installed in such a manner that all of the products of combus- 
tion are conveyed directly from the appliance to the outside 
atmosphere through an approved chimney or vent system. 

(APPROVED. Acceptable to the code official or other author- 
ity having jurisdiction. 

ATMOSPHERIC PRESSURE. The pressure of the weight of 
air and water vapor on the surface of the earth, approximately 
14.7 pounds per square inch (psia) (101 kPa absolute) at sea 
level. 

AUTOMATIC IGNITION. Ignition of gas at the burner(s) 
when the gas controlling device is turned on, including 
reignition if the flames on the bumer(s) have been extinguished 
by means other than by the closing of the gas controlling 
device. 

BAROMETRIC DRAFT REGULATOR. A balanced 
damper device attached to a chimney, vent connector, breech- 
ing or flue gas manifold to protect combustion equipment by 
controlling chimney draft. A double-acting barometric draft 
regulator is one whose balancing damper is free to move in 
either direction to protect combustion equipment from both 
excessive draft and backdraft. 

BOILER, LOW-PRESSURE. A self-contained gas-fired 
appliance for supplying steam or hot water. 

Hot water heating boiler. A boiler in which no steam is 
generated, from which hot water is circulated for heating 
purposes and then returned to the boiler, and that operates at 
water pressures not exceeding 160 psig (1100 kPa gauge) 
and at water temperatures not exceeding 250°F (121°C) at 
or near the boiler outlet. 

Hot water supply boiler. A boiler, completely filled with 
water, which furnishes hot water to be used externally to 
itself, and that operates at water pressures not exceeding 1 60 
psig (1100 kPa gauge) and at water temperatures not 
exceeding 250°F (121°C) at or near the boiler outlet. 

Steam heating boiler. A boiler in which steam is generated 
and that operates at a steam pressure not exceeding 15 psig 
(100 kPa gauge). 

BRAZING. A metal joining process wherein coalescence is 
produced by the use of a nonferrous filler metal having a melting 
point above 1,000°F (538°C), but lower than that of the base 
metal being joined. The filler material is distributed between the 
closely fitted surfaces of the joint by capillary action. 



BTU. Abbreviation for British thermal unit, which is the quan- 
tity of heat required to raise the temperature of 1 pound (454 g) 
of water 1°F (0.56°C) (1 Btu = 1055 J). 

BURNER. A device for the final conveyance of the gas, or a 
mixture of gas and air, to the combustion zone. 

Induced-draft. A burner that depends on draft induced by a 
fan that is an integral part of the appliance and is located 
downstream from the burner. 

Power. A burner in which gas, air or both are supplied at 
pressures exceeding, for gas, the line pressure, and for air, 
atmospheric pressure, with this added pressure being 
applied at the burner. 

CHIMNEY. A primarily vertical structure containing one or 
more flues, for the purpose of carrying gaseous products of 
combustion and air from an appliance to the outside atmo- 
sphere. 

Factory-built chimney. A listed and labeled chimney com- 
posed of factory-made components, assembled in the field 
in accordance with manufacturer's instructions and the con- 
ditions of the listing. 

Masonry chimney. A field-constructed chiminey composed 
of solid masonry units, bricks, stones or concrete. 

CLEARANCE. The minimum distance through air measured 
between the heat-producing surface of the mechanical appli- 
ance, device or equipment and the surface of the combustible 
material or assembly. 

CLOTHES DRYER. An appliance used to dry wet laundry by 
means of heated air. 

Type 1. Factory-built package, multiple production. Pri- 
marily used in the family living environment. Usually the 
smallest unit physically and in function output. 

CODE. These regulations, subsequent amendments thereto, or 
any emergency rule or regulation that the administrative 
authority having jurisdiction has lawfully adopted. 

CODE OFFICIAL. The officer or other designated authority 
charged with the administration and enforcement of this code, 
or a duly authorized representative. 

COMBUSTION. In the context of this code, refers to the rapid 
oxidation of fuel accompanied by the production of heat or heat 
and hght. 

COMBUSTION AIR. Air necessary for complete combus- 
tion of a fuel, including theoretical air and excess air. 

COMBUSTION CHAMBER. The portion of an appliance 
within which combustion occurs. 

COMBUSTION PRODUCTS. Constituents resulting from 
the combustion of a fuel with the oxygen of the air, including 
the inert gases, but excluding excess air. 

CONCEALED LOCATION. A location that cannot be 
accessed without damaging permanent parts of the building 
structure or finish surface. Spaces above, below or behind 
readily removable panels or doors shall not be considered as 
concealed. ' 



364 



2006 INTERNATIONAL RESIDENTIAL CODE<^ 



FUEL GAS 



CONCEALED PIPING. Piping that is located in a concealed 
location (see "Concealed location"). 

CONDENSATE. The liquid that condenses from a gas 
(including flue gas) caused by a reduction in temperature or 
increase in pressure. 

CONNECTOR, APPLIANCE (Fuel). Rigid metallic pipe 
and fittings, semirigid metallic tubing and fittings or a listed 
and labeled device that connects an appliance to the gas piping 
system. 

CONNECTOR, CHIMNEY OR VENT. The pipe that con- 
nects an appliance to a chimney or vent. 

CONTROL. A manual or automatic device designed to regu- 
late the gas, air, water or electrical supply to, or operation of, a 
mechanical system. 

CONVERSION BURNER. A unit consisting of a burner and 
its controls for installation in an appliance originally utilizing 
another fuel. 

CUBIC FOOT. The amount of gas that occupies 1 cubic foot 
(0.02832 m^) when at a temperature of 60°F (16°C), saturated 
with water vapor and under a pressure equivalent to that of 30 
inches of mercury (101 kPa). 

DAMPER. A manually or automatically controlled device to 
regulate draft or the rate of flow of air or combustion gases. 

DECORATIVE GAS APPLIANCE, VENTED. A vented 
appliance wherein the primary function lies in the aesthetic 
effect of the flames. 

DECORATIVE GAS APPLIANCES FOR INSTALLA- 
TION IN VENTED FIREPLACES. A vented appliance 
designed for installation within the fire chamber of a vented 
fireplace, wherein the primary function lies in the aesthetic 
effect of the flames. 

DEMAND. The maximum amount of gas input required per 
unit of time, usually expressed in cubic feet per hour, or Btu/h 
(1 Btu/h = 0.2931 W). 

DESIGN FLOOD ELEVATION. The elevation of the "design 
flood," including wave height, relative to the datum specified on 
the community's legally designated flood hazard map. 

DILUTION AIR. Air that is introduced into a draft hood and 
is mixed with the flue gases. 

DIRECT-VENT APPLIANCES. Appliances that are con- 
structed and installed so that all air for combustion is derived 
directly from the outside atmosphere and all flue gases are dis- 
charged directly to the outside atmosphere. 

DRAFT. The pressure difference existing between the equip- 
ment or any component part and the atmosphere, that causes a 
continuous flow of air and products of combustion through the 
gas passages of the appliance to the atmosphere. 

Mechanical or induced draft. The pressure difference cre- 
ated by the action of a fan, blower or ejector that is located 
between the appliance and the chimney or vent termination. 

Natural draft. The pressure difference created by a vent or 
chimney because of its height, and the temperature differ- 
ence between the flue gases and the atmosphere. 



DRAFT HOOD. A nonadjustable device built into an appli- 
ance, or made as part of the vent connector from an appliance, 
that is designed to (1) provide for ready escape of the flue gases 
from the appliance in the event of no draft, backdraft, or stop- 
page beyond the draft hood, (2) prevent a backdraft from enter- 
ing the appliance, and (3) neutralize the effect of stack action of 
the chimney or gas vent upon operation of the appliance. 

DRAFT REGULATOR. A device that functions to maintain a 
desired draft in the appliance by automatically reducing the 
draft to the desired value. 

DRIP. The container placed at a low point in a system of piping to 
collect condensate and from which the condensate is removable. 

DUCT FURNACE. A warm-air furnace normally installed in 
an air-distribution duct to supply warm air for heating. This 
definition shall apply only to a warm-air heating appliance that 
depends for air circulation on a blower not furnished as part of 
the furnace. 

DWELLING UNIT. A single unit providing complete, inde- 
pendent living facilities for one or more persons, including per- 
manent provisions for living, sleeping, eating, cooking and 
sanitation. 

EQUIPMENT. See "Appliance." 

FIREPLACE. A fire chamber and hearth constructed of 
noncombustible material for use with solid fuels and provided 
with a chimney. 

Masonry fireplace. A hearth and fire chamber of solid 
masonry units such as bricks, stones, listed masonry units or 
reinforced concrete, provided with a suitable chimney. 

Factory-built fireplace. A fireplace composed of listed 
factory-built components assembled in accordance with the 
terms of listing to form the completed fireplace. 

FLAME SAFEGUARD. A device that will automatically shut 
off the fuel supply to a main burner or group of burners when 
the means of ignition of such burners becomes inoperative, and 
when flame failure occurs on the burner or group of burners. 

FLOOD HAZARD AREA. The greater of the following two 
areas: 

1. The area within a floodplain subject to a 1 percent or 
greater chance of flooding in any given year. 

2. This area designated as a flood hazard area on a commu- 
nity's flood hazard map, or otherwise legally designated. 

FLOOR FURNACE. A completely self-contained furnace 
suspended from the floor of the space being heated, taking air 
for combustion from outside such space and with means for 
observing flames and lighting the appliance from such space. 

FLUE, APPLIANCE. The passage(s) within an appliance 
through which combustion products pass from the combustion 
chamber of the appliance to the draft hood inlet opening on an 
appliance equipped with a draft hood or to the outlet of the 
appliance on an appliance not equipped with a draft hood. 

FLUE COLLAR. That portion of an appliance designed for the 
attachment of a draft hood, vent connector or venting system. 

FLUE GASES. Products of combustion plus excess air in 

appliance flues or heat exchangers. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



365 



FUEL GAS 



FLUE LINER (LINING). A system or material used to form 
the inside surface of a flue in a chimney or vent, for the purpose 
of protecting the surrounding structure from the effects of com- 
bustion products and for conveying combustion products with- 
out leakage to the atmosphere. 

I FUEL GAS. A natural gas, manufactured gas, liquefied petro- 
leum gas or mixtures of these gases. 

FUEL GAS UTILIZATION EQUIPMENT. See "Appli 
ance." 

FURNACE. A completely self-contained heating unit that is 
designed to supply heated air to spaces remote from or adjacent 
to the appliance location. 

FURNACE, CENTRAL FURNACE. A self-contained appli- 
ance for heating air by transfer of heat of combustion through 
metal to the air, and designed to supply heated air through ducts 
to spaces remote from or adjacent to the appliance location. 

FURNACE PLENUM. An air compartment or chamber to 
which one or more ducts are connected and which forms part of 
an air distribution system. 

GAS CONVENIENCE OUTLET. A permanently mounted, 
manually operated device that provides the means for connect- 
ing an appliance to, and disconnecting an appliance from, the 
gas supply piping. The device includes an integral, manually 
operated valve with a nondisplaceable valve member and is 
designed so that disconnection of an appliance only occurs 
when the manually operated valve is in the closed position. 

GAS PIPING. An installation of pipe, valves or fittings 
installed on a premises or in a building and utilized to convey 
fuel gas. 

GAS UTILIZATION EQUIPMENT. An apphance that uti- 
lizes gas as a fuel or raw material or both. 

HAZARDOUS LOCATION. Any location considered to be a 
fire hazard for flammable vapors, dust, combustible fibers or 
other highly combustible substances. The location is not neces- 
sarily categorized in the International Building Code as a 
high-hazard use group classification. 

HOUSE PIPING. See "Piping system." 

IGNITION PILOT. A pilot that operates during the lighting 
cycle and discontinues during main burner operation. 

IGNITION SOURCE. A flame spark or hot surface capable 
of igniting flammable vapors or fumes. Such sources include 
appliance burners, burner ignitors and electrical switching 
devices. 

INFRARED RADIANT HEATER. A heater which directs a 
substantial amount of its energy output in the form of infrared 
radiant energy into the area to be heated. Such heaters are of 
either the vented or unvented type. 

JOINT, FLARED. A metal-to-metal compression joint in 
which a conical spread is made on the end of a tube that is com- 
pressed by a flare nut against a mating flare. 

JOINT, MECHANICAL. A general form of gas-tight joints 
obtained by the joining of metal parts through a positive-hold- 
ing mechanical construction, such as flanged joint, threaded 
joint, flared joint or compression joint. 



JOINT, PLASTIC ADHESIVE. A joint made in thermoset 
plastic piping by the use of an adhesive substance which forms 
a continuous bond between the mating surfaces without dis- 
solving either one of them. 

LIQUEFIED PETROLEUM GAS or LPG (LP-GAS). Liq- 
uefied petroleum gas composed predominately of propane, pro- 
pylene, butanes or butylenes, or mixtures thereof that is gaseous 
under normal atmospheric conditions, but is capable of being 
liquefied under moderate pressure at normal temperatures. 

LIVING SPACE. Space within a dwelling unit utilized for liv- 
ing, sleeping, eating, cooking, bathing, washing and sanitation 
purposes. 

LOG LIGHTER, GAS-FIRED. A manually operated 
solid-fuel ignition appliance for installation in a vented 
solid-fuel-burning fireplace. 

MAIN BURNER. A device or group of devices essentially 
forming an integral unit for the final conveyance of gas or a 
mixture of gas and air to the combustion zone, and on which 
combustion takes place to accomplish the function for which 
the appliance is designed. 

METER. The instrument installed to measure the volume of 
gas delivered through it. 

MODULATING. Modulating or throttling is the action of a 
control from its maximum to minimum position in either pre- 
determined steps or increments of movement as caused by its 
actuating medium. 

OFFSET (VENT). A combination of approved bends that 
make two changes in direction bringing one section of the vent 
out of line, but into a line parallel with the other section. 

OUTLET. A threaded connection or bolted flange in a pipe 
system to which a gas-burning appliance is attached. 

OXYGEN DEPLETION SAFETY SHUTOFF SYSTEM 
(ODS). A system designed to act to shut off the gas supply to 
the main and pilot burners if the oxygen in the surrounding 
atmosphere is reduced below a predetermined level. 

PILOT. A small flame that is utilized to ignite the gas at the 
main burner or burners. 

PIPING. Where used in this code, "piping" refers to either 
pipe or tubing, or both. 

Pipe. A rigid conduit of iron, steel, copper, brass or plastic. 

T\ibing. Semirigid conduit of copper, aluminum, plastic or 
steel. 

PIPING SYSTEM. All fuel piping, valves, and fittings from 
the outlet of the point of delivery to the outlets of the equipment 
shutoff valves. 

PLASTIC, THERMOPLASTIC. A plastic that is capable of 
being repeatedly softened by increase of temperature and hard- 
ened by decrease of temperature. 

POINT OF DELIVERY. For natural gas systems, the point of 
delivery is the outiet of the service meter assembly or the outlet 
of the service regulator or service shutoff valve where a meter is 
not provided. Where a valve is provided at the outlet of the ser- 
vice meter assembly, such valve shall be considered to be down- 
stream of the point of delivery. For undiluted liquefied petroleum 



366 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



FUEL GAS 



gas systems, the point of delivery shall be considered to be the 
outlet of the fost regulator that reduces pressure to 2 psig (13.8 
kPa) or less. 

PRESSURE DROP. The loss in pressure due to friction or 
obstruction in pipes, valves, fittings, regulators and burners. 

PRESSURE TEST. An operation performed to verify the 
gas-tight integrity of gas piping following its installation or 
modification. 

READY ACCESS (TO). That which enables a device, appli- 
ance or equipment to be directly reached, without requiring the 
removal or movement of any panel, door or similar obstruction. 

(See "Access.") 

REGULATOR. A device for controlling and maintaining a 
uniform gas supply pressure, either pounds-to-inches water 
column (MP regulator) or inches-to-inches water column 
(appliance regulator). 

REGULATOR, GAS APPLIANCE. A pressure regulator for 
controlling pressure to the manifold of gas equipment. 

REGULATOR, LINE GAS PRESSURE. A device placed in 
a gas line between the service pressure regulator and the equip- 
ment for controlling, maintaining or reducing the pressure in 
that portion of the piping system downstream of the device. 

REGULATOR, MEDIUM-PRESSURE (MP Regulator). 

A line pressure regulator that reduces gas pressure from the 
range of greater than 0.5 psig (3.4 kPa) and less than or equal to 
5 psig (34.5 kPa) to a lower pressure. 

REGULATOR, PRESSURE. A device placed in a gas line for 
reducing, controlling and maintaining the pressure in that por- 
tion of the piping system downstream of the device. 

REGULATOR, SERVICE PRESSURE. A device installed 
by the serving gas supplier to reduce and limit the service line 
gas pressure to delivery pressure. 

RELIEF OPENING. The opening provided in a draft hood to 
permit the ready escape to the atmosphere of the flue products 
from the draft hood in the event of no draft, backdraft or stop- 
page beyond the draft hood, and to permit air into the draft hood 
in the event of a strong chimney updraft. 

RELIEF VALVE (DEVICE). A safety valve designed to fore- 
stall the development of a dangerous condition by relieving 
either pressure, temperature or vacuum in the hot water supply 
system. 

RELIEF VALVE, PRESSURE. An automatic valve which 
opens and closes a relief vent, depending on whether the pres- 
sure is above or below a predetermined value. 

RELIEF VALVE, TEMPERATURE 

Manual reset type. A valve which automatically opens a 
relief vent at a predetermined temperature and which must 
be manually returned to the closed position. 

Reseating or self-closing type. An automatic valve which 
opens and closes a relief vent, depending on whether the 
temperature is above or below a predetermined value. 



RELIEF VALVE, VACUUM. A valve that automatically 
opens and closes a vent for relieving a vacuum within the hot 
water supply system, depending on whether the vacuum is 
above or below a predetermined value. 

RISER, GAS. A vertical pipe supplying fuel gas. 

ROOM HEATER, UNVENTED. See "Unvented room 
heater." 

ROOM HEATER, VENTED. A free-standing gas-fired heat- 
ing unit used for direct heating of the space in and adj acent to that 
in which the unit is located. [See also "Vented room heater."] 

SAFETY SHUTOFF DEVICE. See "Flame safeguard." 

SHAFT. An enclosed space extending through one or more 
stories of a building, connecting vertical openings in succes- 
sive floors, or floors and the roof. 

SPECIFIC GRAVITY. As applied to gas, specific gravity is 
the ratio of the weight of a given volume to that of the same vol- 
ume of air, both measured under the same condition. 

THERMOSTAT 

Electric switch type. A device that senses changes in tem- 
perature and controls electrically, by means of separate 
components, the flow of gas to the burner(s) to maintain 
selected temperatures. 

Integral gas valve type. An automatic device, actuated by 
temperature changes, designed to control the gas supply to 
the burner(s) in order to maintain temperatures between pre- 
determined limits, and in which the thermal actuating ele- 
ment is an integral part of the device. 

1. Graduating thermostat. A thermostat in which the 
motion of the valve is approximately in direct propor- 
tion to the effective motion of the thermal element 
induced by temperature change. 

2. Snap-acting thermostat. A thermostat in which the 
thermostatic valve travels instantly from the closed to 
the open position, and vice versa. 

TRANSITION FITTINGS, PLASTIC TO STEEL. An 

adapter for joining plastic pipe to steel pipe. The purpose of this 
fitting is to provide a permanent, pressure-tight connection 
between two materials that cannot be joined directiy one to 
another. 

UNIT HEATER 

High-static pressure type. A self-contained, automatically 
controlled, vented appliance having integral means for cir- 
culation of air against 0.2 inch (15 mm H2O) or greater static 
pressure. Such apphance is equipped with provisions for 
attaching an outlet air duct and, where the appliance is for 
indoor installation remote from the space to be heated, is 
also equipped with provisions for attaching an inlet air duct. 

Low-static pressure type. A self-contained, automatically 
controlled, vented appliance, intended for installation in the 
space to be heated without the use of ducts, having integral 
means for circulation of air. Such units are allowed to be 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



367 



FUEL GAS 



equipped with louvers or face extensions made in accor- 
dance with the manufacturer's specifications. 

UNVENTED ROOM HEATER. An unvented heating apph- 
ance designed for stationary installation and utilized to provide 
comfort heating. Such appliances provide radiant heat or con- 
vection heat by gravity or fan circulation directly from the 
heater and do not utilize ducts. 

VALVE. A device used in piping to control the gas supply to 
any section of a system of piping or to an appliance. 

Automatic. An automatic or semiautomatic device consist- 
ing essentially of a valve and operator that control the gas 
supply to the burner("s) during operation of an appliance. 
The operator shall be actuated by application of gas pressure 
on a flexible diaphragm, by electrical means, by mechanical 
means or by other approved means. 

Automatic gas shutoff. A valve used in conjunction with an 
automatic gas shutoff device to shut off the gas supply to a 
water heating system. It shall be constructed integrally with 
the gas shutoff device or shall be a separate assembly. 

Equipment shutoff. A valve located in the piping system, 
used to isolate individual equipment for purposes such as 
service or replacement. 

Individual main burner. A valve that controls the gas sup- 
ply to an individual main burner. 

Main burner control. A valve that controls the gas supply 
to the main burner manifold. 

Manual main gas-control. A manually operated valve in 
the gas line for the purpose of completely turning on or shut- 
ting off the gas supply to the appliance, except to pilot or 
pilots that are provided with independent shutoff. 

Manual reset. An automatic shutoff valve installed in the 
gas supply piping and set to shut off when unsafe conditions 
occur. The device remains closed until manually reopened. 

Service shutoff. A valve, installed by the serving gas sup- 
plier between the service meter or source of supply and the 
customer piping system, to shut off the entire piping system. 

VENT. A pipe or other conduit composed of factory-made 
components, containing a passageway for conveying combus- 
tion products and air to the atmosphere, listed and labeled for 
use with a specific type or class of appliance. 

Special gas vent. A vent listed and labeled for use with 
listed Category II, III and IV gas appliances. 

Type B vent. A vent listed and labeled for use with appli- 
ances with draft hoods and other Category I appUances that 
are hsted for use with Type B vents. 

Type BW vent. A vent listed and labeled for use with wall 
furnaces. 

Type L vent. A vent listed and labeled for use with appli- 
ances that are listed for use with Type L or Type B vents. 

VENT CONNECTOR. See "Connector." 



VENT PIPING 

Breather. Piping run from a pressure-regulating device to 
the outdoors, designed to provide a reference to atmo- 
spheric pressure. If the device incorporates an integral pres- 
sure relief mechanism, a breather vent can also serve as a 
relief vent. 

Relief. Piping run from a pressure-regulating or pres- 
sure-limiting device to the outdoors, designed to provide for 
the safe venting of gas in the event of excessive pressure in 
the gas piping system. 

VENTED GAS APPLIANCE CATEGORIES. Apphances 
that are categorized for the purpose of vent selection are classi- 
fied into the following four categories: 

Category I. An appliance that operates with a nonpositive 
vent static pressure and with a vent gas temperature that 
avoids excessive condensate production in the vent. 

Category II. An appliance that operates with a nonpositive 
vent static pressure and with a vent gas temperature that is 
capable of causing excessive condensate production in the 
vent. 

Category III. An appliance that operates vi^ith a positive 
vent static pressure and with a vent gas temperature that 
avoids excessive condensate production in the vent. 

Category IV. An appliance that operates with a positive 
vent static pressure and with a vent gas temperature that is 
capable of causing excessive condensate production in the 
vent. 

VENTED ROOM HEATER. A vented self-contained, 
free-standing, nonrecessed appliance for furnishing warm air 
to the space in which it is installed, direcdy from the heater 
without duct connections. 

VENTED WALL FURNACE. A self-contained vented appli- 
ance complete with grilles or equivalent, designed for incorpo- 
ration in or permanent attachment to the structure of a building, 
mobile home or travel trailer, and furnishing heated air circu- 
lated by gravity or by a fan directly into the space to be heated 
through openings in the casing. This definition shall exclude 
floor furnaces, unit heaters and central furnaces as herein 
defined. 

VENTING SYSTEM. A continuous open passageway from 
the flue collar or draft hood of an appliance to the outside atmo- 
sphere for the purpose of removing flue or vent gases. A vent- 
ing system is usually composed of a vent or a chimney and vent 
connector, if used, assembled to form the open passageway. 

WALL HEATER, UNVENTED TYPE. A room heater of the 
type designed for insertion in or attachment to a wall or parti- 
tion. Such heater does not incorporate concealed venting 
arrangements in its construction and discharges all products of 
combustion through the front into the room being heated. 

WATER HEATER. Any heating appliance or equipment that 
heats potable water and supplies such water to the potable hot 
water distribution system. 



368 



2006 INTERNATIONAL RESIDENTIAL CODE® 



FUEL GAS 



SECTION G2404 (301) 
GENERAL 

G2404.1 (301.1) Scope. This section shall govern the approval 
and installation of all equipment and appliances that comprise 
parts of the installations regulated by this code in accordance 
with Section G2401. 

G2404.2 (301.1.1) Other fuels. The requirements for combus- 
tion and dilution air for gas-fired appliances shall be governed 
by Section G2407. The requirements for combustion and dilu- 
tion air for appliances operating with fuels other than fuel gas 
shall be regulated by Chapter 17. 

G2404.3 (301.3) Listed and labeled. Appliances regulated by 
this code shall be listed and labeled for the application in which 
they are used unless otherwise approved in accordance with 
Section R 104. 1 1 . The approval of unlisted appliances in accor- 
dance with Section R104.il shall be based upon approved 
engineering evaluation. 

G2404.4 (301.8) Vibration isolation. Where means for isola- 
tion of vibration of an appliance is installed, an approved 
means for support and restraint of that appliance shall be pro- 
vided. 

G2404.5 (301.9) Repair. Defective material or parts shall be 
replaced or repaired in such a manner so as to preserve the orig- 
inal approval or listing. 

G2404.6 (301.10) Wind resistance. Apphances and supports 
that are exposed to wind shall be designed and installed to resist 
the wind pressures determined in accordance with this code. 

G2404.7 (301.11) Flood hazard. For structures located in 
flood hazard areas, the appliance, equipment and system instal- 
lations regulated by this code shall be located at or above the 
design flood elevation and shall comply with the flood-resis- 
tant construction requirements of Section R323. 

Exception: The appliance, equipment and system installa- 
tions regulated by this code are permitted to be located below 
the design flood elevation provided that they are designed and 
installed to prevent water from entering or accumulating 
within the components and to resist hydrostatic and hydrody- 
namic loads and stresses, including the effects of buoyancy, 
during the occurrence of flooding to the design flood eleva- 
tion and shall comply with the flood-resistant construction 
requirements of Section R323. 

G2404.8 (301.12) Seismic resistance. When earthquake loads 
are applicable in accordance with this code, the supports shall 
be designed and installed for the seismic forces in accordance 
with this code. 

G2404.9 (301.14) Rodentproofing. Buildings or structures 
and the walls enclosing habitable or occupiable rooms and 
spaces in which persons live, sleep or work, or in which feed, 
food or foodstuffs are stored, prepared, processed, served or 
sold, shall be constructed to protect against the entry of rodents. 

G2404.10 (307.5) Auxiliary drain pan. Category IV condens- 
ing appliances shall be provided with an auxiliary drain pan 
where damage to any building component will occur as a result 
of stoppage in the condensate drainage system. Such pan shall 



be installed in accordance with the applicable provisions of 
Section M1411. 

Exception: An auxiliary drain pan shall not be required for 
appliances that automatically shut down operation in the 
event of a stoppage in the condensate drainage system. 



SECTION G2405 (302) 
STRUCTURAL SAFETY 

G2405.1 (302.1) Structural safety. The building shall not be 
weakened by the installation of any gas piping. In the process 
of installing or repairing any gas piping, the finished floors, 
walls, ceilings, tile work or any other part of the building or pre- 
mises which are required to be changed or replaced shall be left 
in a safe structural condition in accordance with the require- 
ments of this code. 

G2405.2 (302.4) Alterations to trusses. Truss members and 
components shall not be cut, drilled, notched, spliced or other- 
wise altered in any way without the written concurrence and 
approval of a registered design professional. Alterations result- 
ing in the addition of loads to any member (e.g., HVAC equip- 
ment, water heaters) shall not be permitted without verification 
that the truss is capable of supporting such additional loading. 

G2405.3 (302.3.1) Engineered wood products. Cuts, notches 
and holes bored in trusses, structural composite lumber, struc- 
tural glued-laminated members and I-joists are prohibited 
except where permitted by the manufacturer's recommenda- 
tions or where the effects of such alterations are specifically 
considered in the design of the member by a registered design 
professional. 



SECTION G2406 (303) 
APPLIANCE LOCATION 

G2406.1 (303.1) General. Appliances shall be located as 
required by this section, specific requirements elsewhere in 
this code and the conditions of the equipment and appliance 
listing. 

G2406.2 (303.3) Prohibited locations. Appliances shall not 
be located in sleeping rooms, bathrooms, toilet rooms, storage 
closets or surgical rooms, or in a space that opens only into such 
rooms or spaces, except where the installation complies with 
one of the following: 

1. The appliance is a direct- vent appliance installed in 
accordance with the conditions of the listing and the 
manufacturer's instructions. 

2. Vented room heaters, wall furnaces, vented decorative 
appliances, vented gas fireplaces, vented gas fireplace 
heaters and decorative appliances for installation in 
vented solid fuel-burning fireplaces are installed in 
rooms that meet the required volume criteria of Section 
G2407.5. 

3. A single wall-mounted un vented room heater is installed 
in a bathroom and such unvented room heater is 
equipped as specified in Section G2445.6 and has an 
input rating not greater than 6,000 Btu/h (1 .76 kW). The 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



369 



FUEL GAS 



bathroom shall meet the required volume criteria of Sec- 
tion G2407.5. 

4. A single wall-mounted unvented room heater is installed 
in a bedroom and such unvented room heater is equipped 
as specified in Section G2445.6 and has an input rating 
not greater than 10,000 Btu/h (2.93 kW). The bedroom 
shall meet the required volume criteria of Section 
G2407.5. 

5. The appliance is installed in a room or space that opens 
only into a bedroom or bathroom, and such room or 
space is used for no other purpose and is provided with a 
solid weather-stripped door equipped with an approved 
self-closing device. All combustion air shall be taken 
directly from the outdoors in accordance with Section 
G2407.6. 

G2406.3 (303.6) Outdoor locations. Equipment installed in 
outdoor locations shall be either listed for outdoor installation 
or provided with protection from outdoor environmental fac- 
tors that influence the operability, durability and safety of the 
equipment. 



SECTION G2407 (304) 
COMBUSTION, VENTILATION AND DILUTION AIR 

G2407.1 (304.1) General. Air for combustion, ventilation and 
dilution of flue gases for appliances installed in buildings shall 
be provided by application of one of the methods prescribed in 
Sections G2407.5 through G2407.9. Where the requirements 
of Section G2407.5 are not met, outdoor air shall be introduced 
in accordance with one of the methods prescribed in Sections 
G2407.6 through G2407.9. Direct-vent appliances, gas appli- 
ances of other than natural draft design and vented gas appli- 
ances other than Category I shall be provided with combustion, 
ventilation and dilution air in accordance with the appliance 
manufacturer's instructions. 

Exception: Type 1 clothes dryers that are provided with 
makeup air in accordance with Section G2439.4. 

G2407.2 (304.2) Appliance location. Appliances shall be 
located so as not to interfere with proper circulation of combus- 
tion, ventilation and dilution air. 

G2407.3 (304.3) Draft hood/regulator location. Where used, 
a draft hood or a barometric draft regulator shall be installed in 
the same room or enclosure as the appliance served so as to pre- 
vent any difference in pressure between the hood or regulator 
and the combustion air supply. 

G2407.4 (304.4) Makeup air provisions. Makeup air require- 
ments for the operation of exhaust fans, kitchen ventilation sys- 
tems, clothes dryers and fireplaces shall be considered in 
determining the adequacy of a space to provide combustion air 
requirements. 

G2407.5 (304.5) Indoor combustion air. The required vol- 
ume of indoor air shall be determined in accordance with Sec- 
tion G2407.5.1 or G2407.5.2, except that where the air 
infiltration rate is known to be less than 0.40 air changes per 
hour (ACH), Section G2407.5.2 shall be used. The total 
required volume shall be the sum of the required volume calcu- 
lated for all appliances located within the space. Rooms com- 



municating directly with the space in which the appliances are 
installed through openings not furnished with doors, and 
through combustion air openings sized and located in accor- 
dance with Section G2407.5.3, are considered to be part of the 
required volume. 

G2407.5.1 (304.5.1) Standard method. The minimum 
required volume shall be 50 cubic feet per 1,000 Btu/h (4.8 
m3/kW). 

G2407.5.2 (304.5.2) Known air-infiltration-rate 
method. Where the air infiltration rate of a structure is 
known, the minimum required volume shall be determined 
as follows: 

For appliances other than fan assisted, calculate volume 
using Equation 24-1. 

21ft^ '' ^ ^ 

Required Volumegthg, > 



ACH 



l,OOOBtu/hr 



(Equation 24-1) 



For fan-assisted appliances, calculate volume using 
Equation 24-2. 

.3 / 



Required Volumef^^ > 



where: 



15 ft 



ACH 



fan 



l,OOOBtu/hr 



(Equation 24-2) 



hther = AH appliances other than fan assisted (input in 
Btu/h). 

If^„ = Fan-assisted appliance (input in Btu/h). 

ACH = Air change per hour (percent of volume of 
space exchanged per hour, expressed as a deci- 
mal). 

For purposes of this calculation, an infiltration rate 
greater than 0.60 ACH shall not be used in Equations 24-1 
and 24-2. 

G2407.5.3 (304.5.3) Indoor opening size and location. 

Openings used to connect indoor spaces shall be sized and 
located in accordance with Sections G2407.5.3.1 and 
G2407.5.3.2 (see Figure G2407.5.3). 

G2407.5.3.1 (304.5.3.1) Combining spaces on the 
same story. Each opening shall have a minimum free 
area of 1 square inch per 1 ,000 Btu/h (2,200 mm^/kW) of 
the total input rating of all appliances in the space, but not I 
less than 100 square inches (0.06 m^). One opening shall 
commence within 12 inches (305 mm) of the top and one 
opening shall commence within 12 inches (305 mm) of 
the bottom of the enclosure. The minimum dimension of 
air openings shall be not less than 3 inches (76 mm). 

G2407.5.3.2 (304.5.3.2) Combining spaces in differ- 
ent stories. The volumes of spaces in different stories 
shall be considered as communicating spaces where such 
spaces are connected by one or more openings in doors 
or floors having a total minimum free area of 2 square 
inches per 1 ,000 Btu/h (4402 mm^/kW) of total input rat- 
ing of all appliances. I 



370 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FUEL GAS 



CHIMNEY OR GAS VENT 




FURNACE 



WATER 
HEATEF 









O 




OPENING 






CHIMNEY OR GAS VENT 




OPENING 

ALTERNATE OPENING 
LOCATION 



FIGURE G2407.5.3 (304.5.3) 

ALL AIR FROM INSIDE THE BUILDING 

(see Section 2407.5.3) 

G2407.6 (304.6) Outdoor combustion air. Outdoor combus- 
tion air shall be provided through opening(s) to the outdoors in 
accordance with Section G2407.6.1 or G2407.6.2. The mini- 
mum dimension of air openings shall be not less than 3 inches 
(76 mm). 

G2407.6.1 ( 304.6.1) Two-permanent-openings method. 

Two permanent openings, one commencing within 12 
inches (305 mm) of the top and one commencing within 12 
inches (305 mm) of the bottom of the enclosure, shall be 
provided. The openings shall communicate directly, or by 
ducts, with the outdoors or spaces that freely communicate 
with the outdoors. 

Where directly communicating with the outdoors, or 
where communicating with the outdoors through vertical 
ducts, each opening shall have a minimum free area of 1 
square inch per 4,000 Btu/h (550 mm^/kW) of total input 
rating of all appliances in the enclosure [see Figures 
G2407.6.1(l) and G2407.6.1(2)]. 

Where communicating with the outdoors through hori- 
zontal ducts, each opening shall have a minimum free area 
of not less than 1 square inch per 2,000 Btu/h (1,100 
mm^/kW) of total input rating of all appliances in the enclo- 
sure [see Figure G2407.6.1(3)]. 

G2407.6.2 (304.6.2) One-permanent-opening method. 

One permanent opening, commencing within 12 inches 
(305 mm) of the top of the enclosure, shall be provided. The 
appliance shall have clearances of at least 1 inch (25 mm) 
from the sides and back and 6 inches (152 mm) from the 
front of the appliance. The opening shall directly communi- 
cate with the outdoors or through a vertical or horizontal 
duct to the outdoors, or spaces that freely communicate with 
the outdoors (see Figure G2407.6.2) and shall have a mini- 
mum free area of 1 square inch per 3,000 Btu/h (734 



FIGURE G2407.6.2 (304.6.2) 

SINGLE COMBUSTION AIR OPENING, 

ALL AIR FROM OUTDOORS 

(see Section 304.6.2) 

mmVkW) of the total input rating of all appliances located in 
the enclosure and not less than the sum of the areas of all 
vent connectors in the space. 

G2407.7 (304.7) Combination indoor and outdoor combus- 
tion air. The use of a combination of indoor and outdoor com- 
bustion air shall be in accordance with Sections G2407.7.1 
through G2407.7.3. 

G2407.7.1 (304.7.1) Indoor openings. Where used, open- 
ings connecting the interior spaces shall comply with Sec- 
tion G2407.5.3. 

G2407.7.2 (304.7.2) Outdoor opening location. Outdoor 
opening(s) shall be located in accordance with Section 
G2407.6. 

G2407.7.3 (304.7.3) Outdoor opening(s) size. The out- 
door opening(s) size shall be calculated in accordance with 
the following: 

1. The ratio of interior spaces shall be the available vol- 
ume of all communicating spaces divided by the 
required volume. 

2. The outdoor size reduction factor shall be one minus 
the ratio of interior spaces. 

3. The minimum size of outdoor opening(s) shall be the 
full size of outdoor opening(s) calculated in accor- 
dance with Section G2407.6, multiplied by the reduc- 
tion factor. The minimum dimension of air openings 
shall be not less than 3 inches (76 mm). 

G2407.8 (304.8) Engineered installations. Engineered com- 
bustion air installations shall provide an adequate supply of 
combustion, ventilation and dilution air and shall be approved. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



371 



FUEL GAS 



CHIMNEY OR GAS VENT 



FURNACE 



ALTERNATE 

AIR 

INLET 



VENTILATION LOUVERS 

FOR UNHEATED CRAWL SPACE 



VENTILATION LOUVERS 
(EACH END OF ATTIC) 




OUTLET AIR 



WATER HEATER 



INLET AIR 



FIGURE G2407.6.1(1) [304.6.1(1)] 

ALL AIR FROM OUTDOORS— INLET AIR FROM VENTILATED 

CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC (see Section G2407.6.1) 



CHIMNEY OR GAS VENT 



FURNACE 



VENTILATION LOUVERS 
(EACH END OF ATTIC) 




OUTLET AIR 



WATER HEATER 



[INLET AIR DUCT (ENDS 1 FT) ABOVE 
FLOOR] 



For SI: 1 foot = 304.8 mm. 



FIGURE G2407.6.1(2) [304.6.1(2)] 

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC 

(see Section G2407.6.1) 



372 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FUEL GAS 



„ CHIMNEY OR GAS VENT 




FIGURE G2407.6.1(3) [304.6.1(3)] 

ALL AIR FROM OUTDOORS 

(see Section G2407.6.1) 



G2407.9 (304.9) Mechanical combustion air supply. Where 
all combustion air is provided by a mechanical air supply sys- 
tem, the combustion air shall be supplied from the outdoors at a 
rate not less than 0.35 cubic feet per minute per 1,000 Btu/h 
(0.034 mVmin per kW) of total input rating of all apphances 
located within the space. 

G2407.9.1 (304.9.1) Makeup air. Where exhaust fans are 
installed, makeup air shall be provided to replace the 
exhausted air. 

G2407.9.2 (304.9.2) Appliance interlock. Each of the 
appliances served shall be interlocked with the mechanical 
air supply system to prevent main burner operation when the 
mechanical air supply system is not in operation. 

G2407.9.3 (304.9.3) Combined combustion air and ven- 
tilation air system. Where combustion air is provided by 
the building's mechanical ventilation system, the system 
shall provide the specified combustion air rate in addition to 
the required ventilation air. 

G2407.10 (304.10) Louvers and grilles. The required size of 
openings for combustion, ventilation and dilution air shall be 
based on the net free area of each opening. Where the free area 
through a design of louver, grille or screen is known, it shall be 
used in calculating the size opening required to provide the free 
area specified. Where the design and free area of louvers and 
grilles are not known, it shall be assumed that wood louvers will 
have 25 -percent free area and metal louvers and grilles will have 



75-percent free area. Screens shall have a mesh size not smaller 
than V4 inch (6.4 mm). Nonmotorized louvers and grilles shall 
be fixed in the open position. Motorized louvers shall be inter- 
locked with the appliance so that they are proven to be in the I 
full open position prior to main burner ignition and during main 
burner operation. Means shall be provided to prevent the main 
burner from igniting if the louvers fail to open during burner 
start-up and to shut down the main burner if the louvers close 
during operation. 

G2407.il (304.11) Combustion air ducts. Combustion air 
ducts shall comply with all of the following: 

1 . Ducts shall be constructed of galvanized steel complying 
with Chapter 1 6 or of a material having equivalent corro- I 
sion resistance, strength and rigidity. I 

Exception: Within dwellings units, unobstructed 
stud and joist spaces shall not be prohibited from con- 
veying combustion air, provided that not more than 
one required fireblock is removed. 

2. Ducts shall terminate in an unobstructed space allowing 
free movement of combustion air to the appliances. 

3. Ducts shall serve a single enclosure. 

4. Ducts shall not serve both upper and lower combustion 
air openings where both such openings are used. The 
separation between ducts serving upper and lower com- 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



373 



FUEL GAS 



bustion air openings shall be maintained to the source of 
combustion air. 

5. Ducts shall not be screened where terminating in an attic 
space. 

6. Horizontal upper combustion air ducts shall not slope 
downward toward the source of combustion air. 

7. The remaining space surrounding a chimney liner, gas 
vent, special gas vent or plastic piping installed within a 
masonry, metal or factory-built chinmey shall not be 
used to supply combustion air. 

Exception: Direct-vent gas-fired appliances 
designed for installation in a solid fuel-burning fire- 
place where installed in accordance with the manu- 
facturer's instructions. 

8. Combustion air intake openings located on the exterior 
of a building shall have the lowest side of such openings 
located not less than 12 inches (305 mm) vertically from 
the adjoining grade level. 

G2407.12 (304.12) Protection from fumes and gases. Where 
corrosive or flammable process fumes or gases, other than 
products of combustion, are present, means for the disposal of 
such fumes or gases shall be provided. Such fumes or gases 
include carbon monoxide, hydrogen sulfide, ammonia, chlo- 
rine and halogenated hydrocarbons. 

In barbershops, beauty shops and other facilities where 
chemicals that generate corrosive or flammable products, such 
as aerosol sprays, are routinely used, nondirect vent-type appli- 
ances shall be located in a mechanical room separated or parti- 
tioned off from other areas with provisions for combustion air 
and dilution air from the outdoors. Direct- vent appliances shall 
be installed in accordance with the appliance manufacturer's 
installation instructions. 



SECTION G2408 (305) 
INSTALLATION 

G2408.1 (305.1) GeneraL Equipment and appliances shall be 
installed as required by the terms of their approval, in accor- 
dance with the conditions of listing, the manufacturer's instruc- 
tions and this code. Manufacturers' installation instructions 
shall be available on the job site at the time of inspection. 
Where a code provision is less restrictive than the conditions of 
the listing of the equipment or appliance or the manufacturer's 
installation instructions, the conditions of the listing and the 
manufacturer's installation instructions shall apply. 

Unlisted appliances approved in accordance with Section 
2404.3 shall be limited to uses reconmiended by the manufac- 
turer and shall be installed in accordance with the manufac- 
turer's instructions, the provisions of this code and the 
requirements determined by the code official. 

G2408.2 (305.3) Elevation of ignition source. Equipment and 
appliances having an ignition source shall be elevated such that 
the source of ignition is not less than 1 8 inches (457 mm) above 
the floor in hazardous locations and public garages, private 



garages, repair garages, motor fuel-dispensing facilities and 
parking garages. For the purpose of this section, rooms or 
spaces that are not part of the living space of a dwelling unit and 
that communicate directly with a private garage through open- 
ings shall be considered to be part of the private garage. 

Exception: Elevation of the ignition source is not required 
for appliances that are listed as flammable vapor ignition 
resistant. 

G2408.3 (305.5) Private garages. Appliances located in pri- 
vate garages shall be installed with a minimum clearance of 6 
feet (1829 mm) above the floor. 

Exception: The requirements of this section shall not apply 
where the appliances are protected from motor vehicle 
impact and installed in accordance with Section G2408.2. 

G2408.4 (305.7) Clearances from grade. Equipment and 
appliances installed at grade level shall be supported on a level 
concrete slab or other approved material extending above 
adjoining grade or shall be suspended a minimum of 6 inches 
(152 mm) above adjoining grade. 

G2408.5 (305.8) Clearances to combustible construction. 

Heat-producing equipment and appliances shall be installed to 
maintain the required clearances to combustible construction 
as specified in the listing and manufacturer's instructions. Such 
clearances shall be reduced only in accordance with Section 
G2409. Clearances to combustibles shall include such consid- 
erations as door swing, drawer pull, overhead projections or 
shelving and window swing. Devices, such as door stops or 
limits and closers, shall not be used to provide the required 
clearances. 



SECTION G2409 (308) 
CLEARANCE REDUCTION 

G2409.1 (308.1) Scope. This section shall govern the reduc- 
tion in required clearances to combustible materials and com- 
bustible assemblies for chimneys, vents, appliances, devices 
and equipment. 

G2409.2 (308.2) Reduction table. The allowable clearance 
reduction shall be based on one of the methods specified in 
Table G2409.2 or shall utilize an assembly listed for such appli- 
cation. Where required clearances are not listed in Table 
G2409.2, the reduced clearances shall be detennined by linear 
interpolation between the distances listed in the table. Reduced 
clearances shall not be derived by extrapolation below the 
range of the table. The reduction of the required clearances to 
combustibles for listed and labeled appliances and equipment 
shall be in accordance with the requirements of this section 
except that such clearances shall not be reduced where reduc- 
tion is specifically prohibited by the terms of the appliance or 
equipment listing [see Figures G2409.2(l), G2409.2(2) and 
G2409.2(3)]. 

G2409.3 (308.3) Clearances for indoor air-conditioning I 
appliances. Clearance requirements for indoor air-condition- I , 
ing appliances shall comply with Sections G2409.3.1 through 
G2409.3.5. I 



374 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



FUEL GAS 



CONSTRUCTION USING COMBUSTIBLE MATERIAL, 
PLASTERED OR UNPLASTERED 





GAS EQUIPMENT OR 
VENT CONNECTOR 



SHEET METAL OR OTHER 
PROTECTION 



NOTES: 

"A" equals the clearance with no protection. 

"B" equals the reduced clearance permitted in accordance with Table G2409.2. The protection applied to the construction using combustible material shall extend far 
enough in each direction to make "C" equal to "A." 

FIGURE G2409.2(1) [308.2(1)] 

EXTENT OF PROTECTION NECESSARY TO REDUCE CLEARANCES 

FROM GAS EQUIPMENT OR VENT CONNECTORS 




WALL PROTECTOR MOUNTED 
WITH ALL EDGES OPEN 





MOUNTED WITH SIDE 
AND TOP EDGES OPEN 



h- MOUNTED WITH TOP 
AND BOTTOM EDGES 
OPEN 



WALL PROTECTOR MOUNTED 
ON SINGLE FLAT WALL 



MUST BE MOUNTED 
WITH TOP AND BOTTOM 
EDGES OPEN 



WALL PROTECTOR INSTALLED 
IN CORNER 



■^ 



COMBUSTIBLE 
WALL 



■^^ 



1 INCH 



AIR- 
SPACE 



NAIL OR SCREW 
ANCHOR 



CLEARANCE 
REDUCTION SYSTEM 



1-INCH NONCOMBUSTIBLE SPACER SUCH AS STACKED WASHERS, SMALL- 
DIAMETER PIPE, TUBING OR ELECTRICAL CONDUIT. 

MASONRY WALLS CAN BE ATTACHED TO COMBUSTIBLE WALLS USING WALL TIES. 

DO NOT USE SPACERS DIRECTLY BEHIND APPLIANCE OR CONNECTOR. 



For SI: 1 inch = 25.4 mm. 



FIGURE G2409.2(2) [308.2(2)] 
WALL PROTECTOR CLEARANCE REDUCTION SYSTEM 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



375 



FUEL GAS 



«KiW MINIMUM 
M«»OWAJ»>D 

ccKgusnaewAU, 



mrm* «© top (mm. 

OFeRSOtSSTAQQERED 
FORV0rtllATK)N 



A Strap OF HEAVy-GAUCE STCQ. 
US© FCfl ADDED SUPPCSr 

KOIB DO KOT PWC6 ^«aMW 
WALL TIES DiRECTLYBEWaH 

fprnrnm m coNNECTon 



For SI: 1 inch = 25.4 mm. 




FIGURE G240g.2(3) [308.2(3)] 
MASONRY CLEARANCE REDUCTION SYSTEM 



G2409.3.1 (308.3.1) Appliances installed in rooms that 
are large in comparison with the size of the appliances. 

Air-conditioning appliances installed in rooms that are large 
in comparison with the size of the appliance shall be 
installed with clearances in accordance with the manufac- 
turer's instructions. 

G2409.3.2 (308.3.2) Appliances installed in rooms that 
are not large in comparison with the size of the appli- 
ances. Air-conditioning appliances installed in rooms that 
are not large in comparison with the size of the appliance, 
such as alcoves and closets, shall be hsted for such installa- 
tions and installed in accordance with the manufacturer's 
instructions. Listed clearances shall not be reduced by the 
protection methods described in Table G2409.2, regardless 
of whether the enclosure is of combustible or 
noncombustible material. 

G2409.3.3 (308.3.3) Clearance reduction. Air-condition- 
ing appliances installed in rooms that are large in compari- 
son with the size of the appliance shall be permitted to be 
installed with reduced clearances to combustible material, 
provided the combustible material or appliance is protected 
as described in Table G2409.2. 

G2409.3.4 (308.3.4) Plenum clearances. Where the fur- 
nace plenum is adjacent to plaster on metal lath or 
noncombustible material attached to combustible material, 
the clearance shall be measured to the surface of the plaster 
or other noncombustible finish where the clearance speci- 
fied is 2 inches (51 mm) or less. 



G2409.3.5 (308.3.5) Clearance from supply ducts. 

Air-conditioning appliances shall have the clearance from 
supply ducts within 3 feet (914 mm) of the furnace plenum 
be not less than that specified from the furnace plenum. 
Clearance is not necessary beyond this distance. 

G2409.4 (308.4) Central heating boilers and furnaces. 

Clearance requirements for central -heating boilers and fur- 
naces shall comply with Sections G2409.4.1 through 
G2409.4.6. The clearance to these apphances shall not inter- 
fere with combustion air; draft hood clearance and relief; and 
accessibility for servicing. 

G2409.4.1 (308.4.1) Appliances installed in rooms that 
are large in comparison with the size of the appliances. 

Central-heating furnaces and low-pressure boilers installed 
in rooms large in comparison with the size of the appliance 
shall be installed with clearances in accordance with the 
manufacturer's instructions. 

G2409.4.2 (308.4.2) Apphances installed in rooms that 
are not large in comparison with the size of the appli- 
ances. Central-heating furnaces and low-pressure boilers 
installed in rooms that are not large in comparison with the 
size of the appliance, such as alcoves and closets, shall be 
listed for such installations. Listed clearances shall not be 
reduced by the protection methods described in Table 
G2409.2 and illustrated in Figures G2409.2(l) through 
G2409.2(3), regardless of whether the enclosure is of com- 
bustible or noncombustible material. 

G2409.4.3 (308.4.3) Clearance reduction. Central heating 
furnaces and low-pressure boilers installed in rooms that are 
large in comparison with the size of the equipment shall be 
permitted to be installed with reduced clearances to com- 
bustible material provided the combustible material or 
equipment is protected as described in Table G2409.2. 

G2409.4.4 (308.4.5) Plenum clearances. Where the fur- 
nace plenum is adjacent to plaster on metal lath or 
noncombustible material attached to combustible material, 
the clearance shall be measured to the surface of the plaster 
or other noncombustible finish where the clearance speci- 
fied is 2 inches (51 mm) or less. 

G2409.4.5 (308.4.6) Clearance from supply ducts. Cen- 
tral-heating furnaces shall have the clearance from supply 
ducts within 3 feet (914 mm) of the furnace plenum be not 
less than that specified from the furnace plenum. No clear- 
ance is necessary beyond this distance. 

G2409.4.6 (308.4.4) Clearance for servicing appliances. 

Front clearance shall be sufficient for servicing the burner 
and the furnace or boiler. 



SECTION G241 0(309) 
ELECTRICAL 

G2410.1 (309.1) Grounding. Gas piping shall not be used as a 
grounding electrode. 

G2410.2 (309.2) Connections. Electrical connections 
between gas utilization equipment and the building wiring, 
including the grounding of the equipment, shall conform to 
Chapters 33 through 42. 



376 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



FUEL GAS 



TABLE G2409.2 (308.2)^ "'^°"9^ ■* 
REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION 



TYPE OF PROTECTION APPLIED TO 

AND COVERING ALL SURFACES OF COMBUSTIBLE 

MATERIAL WITHIN THE DISTANCE SPECIFIED AS THE 

REQUIRED CLEARANCE WITH NO PROTECTION 

[see Figures G2409.2(1), G2409.2(2), and G2409.2(3)] 


WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM 
APPLIANCE, VENT CONNECTOR, OR SINGLE-WALL METAL PIPE IS: (inches) 


36 


18 


12 


9 


6 


Allowable clearances with specified protection (inches) 


Use Column 1 for clearances above appliance or horizontal connector. Use Column 2 
for clearances from appliance, vertical connector, and single-wall metal pipe. 


Above 
Col. 1 


Sides 

and rear 

Col. 2 


Above 
Col. 1 


Sides 

and rear 

Col. 2 


Above 
Col. 1 


Sides 

and rear 

Col. 2 


Above 
Col. 1 


Sides 

and rear 

Col. 2 


Above 
Col. 1 


Sides 

and rear 

Col. 2 


1. SVj-inch-thick masonry wall without ventilated air- 
space 


— 


24 


— 


12 


— 


9 


— 


6 


— 


5 


2. 'A-inch insulation board over 1-inch glass fiber or 
mineral wool batts 


24 


18 


12 


9 


9 


6 


6 


5 


4 


3 


3 . 0.024-inch (nominal 24 gage) sheet metal over 1 -inch 
glass fiber or mineral wool batts reinforced with wire 
on rear face with ventilated airspace 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 


4. S'A-inch-thick masonry wall with ventilated air- 
space 


— 


12 




6 




6 


— 


6 


— 


6 


5. 0.024-inch (nominal 24 gage) sheet metal with ven- 
tilated airspace 


18 


12 


9 


6 


6 


4 


5 


3 


3 


2 


6. 'A-inch-thick insulation board with ventilated air- 
space 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 


7. 0.024-inch (nominal 24 gage) sheet metal with ven- 
tilated airspace over 0.024-inch (nominal 24 gage) 
sheet metal with ventilated airspace 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 


8. 1-inch glass fiber or mineral wool batts sandwiched 
between two sheets 0.024-inch (nominal 24 gage) 
sheet metal with ventilated airspace 


18 


12 


9 


6 


6 


4 


5 


3 


3 


3 



For SI: 1 inch = 25.4 mm, °C = [(°F - 32)/l .8], 1 pound per cubic foot = 16.02 kgAn^, 1 Btu per inch per square foot per hour per °F - 0.144 WAn^ x K. 

a. Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing. 

b. All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding any interven- 
ing protection applied to the combustible material. 

c. Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite an appliance or connector 

d. For all clearance reduction systems using a ventilated airspace, adequate provision for air circulation shall be provided as described [see Figures G2409.2(2) and 
G2409.2(3)]. 

e. There shall be at least 1 inch between clearance reduction systems and combustible walls and ceilings for reduction systems using ventilated airspace. 

f. Where a wall protector is mounted on a single flat wall away from comers, it shall have a minimum 1-inch air gap. To provide air circulation, the bottom and top 
edges, or only the side and top edges, or all edges shall be left open. 

g. Mineral wool batts (blanket or board) shall have a minimum density of 8 pounds per cubic foot and a minimum melting point of 1500°E 

h. Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu per inch per square foot per hour per °F or less, 
i. There shall be at least 1 inch between the appliance and the protector. In no case shall the clearance between the appliance and the combustible surface be reduced 

below that allowed in this table, 
j. All clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable, 
k. Listed single-wall connectors shall be installed in accordance with the manufacturer's installation instructions. 



SECTION G2411 (310) 
ELECTRICAL BONDING 

G2411.1 (310.1) Gas pipe bonding. Each above-ground por- 
tion of a gas piping system that is likely to become energized 
shall be electrically continuous and bonded to an effective 
ground-fault current path. Gas piping shall be considered to be 
bonded where it is connected to appliances that are connected 
to the equipment grounding conductor of the circuit supplying 
that appliance. 



SECTION G241 2 (401) 
GENERAL 

G2412.1 (401.1) Scope. This section shall govern the design, 
installation, modification and maintenance of piping systems. 
The appHcability of this code to piping systems extends from 
the point of delivery to the connections with the equipment and 
includes the design, materials, components, fabrication, 
assembly, installation, testing, inspection, operation and main- 
tenance of such piping systems. 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



377 



FUEL GAS 



G2412.1.1 (401.1.1) Utility piping systems located 
within buildings. Utility service piping located within 
buildings shall be installed in accordance with the structural 
safety and fire protection provisions of this code. 

G2412.2 (401.2) Liquefied petroleum gas storage. The stor- 
age system for liquefied petroleum gas shall be designed and 
installed in accordance with the International Fire Code and 
NFPA 58. 

G2412.3 (401.3) Modifications to existing systems. In modi- 
fying or adding to existing piping systems, sizes shall be main- 
tained in accordance with this chapter. 

G2412.4 (401.4) Additional appliances. Where an additional 
appliance is to be served, the existing piping shall be checked to 
determine if it has adequate capacity for all appliances served. 
If inadequate, the existing system shall be enlarged as required 
or separate piping of adequate capacity shall be provided. 

G2412.5 (401.5) Identification. For other than steel pipe, 
exposed piping shall be identified by a yellow label marked 
"Gas" in black letters. The marking shall be spaced at intervals 
not exceeding 5 feet (1524 mm). The marking shall not be 
required on pipe located in the same room as the equipment 
served. 

G2412.6 (401.6) Interconnections. Where two or more 
meters are installed on the same premises, but supply separate 
consumers, the piping systems shall not be interconnected on 
the outlet side of the meters. 

G2412.7 (401.7) Piping meter identification. Piping from 
multiple meter installations shall be marked with an approved 
permanent identification by the installer so that the piping sys- 
tem supplied by each meter is readily identifiable. 

G2412.8 (401.8) Minimum sizes. All pipe utilized for the 
installation, extension and alteration of any piping system shall 
be sized to supply the full number of outlets for the intended 
purpose and shall be sized in accordance with Section G2413. 



SECTION G241 3 (402) 
PIPE SIZING 

G2413.1 (402.1) General considerations. Piping systems 
shall be of such size and so installed as to provide a supply of 
gas sufficient to meet the maximum demand without undue 
loss of pressure between the point of delivery and the appli- 
ance. 

G2413.2 (402.2) Maximum gas demand. The volume of gas 
to be provided, in cubic feet per hour, shall be determined 
directly from the manufacturer's input ratings of the appliances 
served. Where an input rating is not indicated, the gas supplier, 
appliance manufacturer or a qualified agency shall be con- 
tacted, or the rating from Table G2413.2 shall be used for esti- 
mating the volume of gas to be supplied. 

The total connected hourly load shall be used as the basis for 
pipe sizing, assuming that all appliances could be operating at 
full capacity simultaneously. Where a diversity of load can be 
established, pipe sizing shall be permitted to be based on such 
loads. 



TABLE G241 3.2 (402.2) 
APPROXIMATE GAS INPUT FOR TYPICAL APPLIANCES 



APPLIANCE 


INPUT BTU/H 
(Approx.) 


Space Heating Units 

Hydronic boiler 

Single family 

Multifamily, per unit 
Warm-air furnace 

Single family 

Multifamily, per unit 


100,000 
60,000 

100,000 
60,000 


Space and Water Heating Units 

Hydronic boiler 
Single family 
Multifamily, per unit 


120,000 
75,000 


Water Heating Appliances 

Water heater, automatic instantaneous 

Capacity at 2 gal./minute 

Capacity at 4 gal./minute 

Capacity at 6 gal./minute 

Water heater, automatic storage, 30- to 
40-gal. tank 

Water heater, automatic storage, 50-gal. tank 

Water heater, domestic, circulating or 
side-arm 


142,800 
285,000 
428,400 

35,000 

50,000 

35,000 


Cooking Appliances 

Built-in oven or broiler unit, domestic 
Built-in top unit, domestic 
Range, free-standing, domestic 


25,000 
40,000 
65,000 


Other Appliances 

Barbecue 

Clothes dryer, Type 1 (domestic) 

Gas fireplace, direct vent 

Gas light 

Gas log 

Refrigerator 


40,000 
35,000 
40,000 

2,500 
80,000 

3,000 



For SI: 1 British thermal unit per hour = 0.293 W; 1 gallon = 3.785 L, 
1 gallon per minute = 3.785 L/m. 



G2413.3 (402.3) Sizing. Gas piping shall be sized in accor- 
dance with one of the following: 

1 . Pipe sizing tables or sizing equations in accordance with 
Section G24 13. 4. 

2. The sizing tables included in a listed piping system's 
manufacturer's installation instructions. 

3. Other approved engineering methods. 



378 



2006 INTERNATIONAL RESIDENTIAL CODE® 



FUEL GAS 



G2413.4 (402.4) Sizing tables and equations. Where Tables 
G2413.4(l) through G2413.4(8) are used to size piping or tub- 
ing, the pipe length shall be determined in accordance with 
Section G2413.4.1, G2413.4.2 or G2413.4.3. 

Where Equations 24-3 and 24-4 are used to size piping or 
tubing, the pipe or tubing shall have smooth inside walls and 
the pipe length shall be determined in accordance with Section 
G2413.4.1, G2413.4.2 or G2413.4.3. 

1. Low-pressure gas equation [Less than 1.5 pounds per 
square inch (psi) (10.3 kPa)]: 

^0.381 

D = (Equation 24-3) 



19.17 



CxL 



2. High-pressure gas equation [1.5 psi (10.3 kPa) and 
above]: 



D 



Q' 



18.93 



(P.'-P.') 



xY 



CxL 



(Equation 24-4) 



where: 
D = 

Q = 



Inside diameter of pipe, inches (mm). 

Input rate appliance(s), cubic feet per hour at 60°F 
(16°C) and 30-inch mercury column. 

Pi = Upstream pressure, psia (P^ + 14.7). 

P2 = Downstream pressure, psia {P2 + 14.7). 

L = Equivalent length of pipe, feet. 

AH= Pressure drop, inch water column (27.7 inch water 
column = 1 psi). 



TABLE G241 3.4 (402.4) 

C, AND /VALUES FOR NATURAL GAS AND 

UNDILUTED PROPANE AT STANDARD CONDITIONS 



GAS 


EQUATION FACTORS 


Cr 


Y 


Natural gas 


0.6094 


0.9992 


Undiluted propane 


1.2462 


0.9910 



For SI: 1 cubic foot = 0.028 m^, 1 foot = 305 mm, 1 inch water column = 
0.249 kPa, 1 pound per square inch = 6.895 kPa, 1 British thermal 
unit per hour - 0.293 W. 

G2413.4.1 (402.4.1) Longest length method. The pipe 
size of each section of gas piping shall be determined using 
the longest length of piping from the point of delivery to the 
most remote outlet and the load of the section. 

G2413.4.2 (402.4.2) Branch length method. Pipe shall be 
sized as follows: 

1 . Pipe size of each section of the longest pipe run from 
the point of delivery to the most remote outlet shall be 



determined using the longest run of piping and the 
load of the section. 

2 . The pipe size of each section of branch piping not pre- 
viously sized shall be determined using the length of 
piping from the point of delivery to the most remote 
outlet in each branch and the load of the section. 

G2413.4.3 (402.4.3) Hybrid pressure. The pipe size for 
each section of higher pressure gas piping shall be deter- 
mined using the longest length of piping from the point of 
delivery to the most remote line pressure regulator. The pipe 
size from the line pressure regulator to each outlet shall be 
determined using the length of piping from the regulator to 
the most remote outlet served by the regulator. 

G2413.5 (402.5) Allowable pressure drop. The design pres- 
sure loss in any piping system under maximum probable flow 
conditions, from the point of delivery to the inlet connection of 
the appliance, shall be such that the supply pressure at the 
appliance is greater than the minimum pressure required for 
proper appliance operation. 

G2413.6 (402.6) Maximum design operating pressure. The 

maximum design operating pressure for piping systems 
located inside buildings shall not exceed 5 pounds per square 
inch gauge (psig) (34 kPa gauge) except where one or more of 
the following conditions are met: 

1. The piping system is welded. 

2. The piping is located in a ventilated chase or otherwise 
enclosed for protection against accidental gas accumula- 
tion. 

3 . The piping is a temporary installation for buildings under 
construction. 

G2413.6.1 (402.6.1) Liquefied petroleum gas systems. 

The operating pressure for undiluted LP-gas systems shall 
not exceed 20 psig (140 kPa gauge). Buildings having sys- 
tems designed to operate below -5°F (-21°C) or with butane 
or a propane-butane mix shall be designed to either accom- 
modate liquid LP-gas or prevent LP-gas vapor from con- 
densing into a liquid. 



SECTION G241 4 (403) 
PIPING MATERIALS 

G2414.1 (403.1) General. Materials used for piping systems 
shall comply with the requirements of this chapter or shall be 
approved. 

G2414.2 (403.2) Used materials. Pipe, fittings, valves or other 
materials shall not be used again unless they are free of foreign 
materials and have been ascertained to be adequate for the ser- 
vice intended. 

G2414.3 (403.3) Other materials. Material not covered by the 
standards specifications listed herein shall be investigated and 
tested to determine that it is safe and suitable for the proposed 
service, and, in addition, shall be recommended for that service 
by the manufacturer and shall be approved by the code official. 

G2414.4 (403.4) Metallic pipe. Metallic pipe shall comply 
with Sections G2414.4.1 and G2414.4.2. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



379 



FUEL GAS 







TABLE G241 3.4(1) [402.4(2)] 
SCHEDULE 40 METALLIC PIPE 






Gas 


Natural 




Inlet Pressure 


Less than 2 psi 




Pressure Drop 


0.5 


in. w.c. 








Specific Gravity 


0.60 




















PIPE SIZE (Inch) 


Nominal 


V2 


'U 


1 


IV4 


IV2 


2 


2V2 


3 


4 


5 


6 


8 


10 


12 


Actual ID 


0.622 


0.824 


1.049 


1.380 


1.610 


2.067 


2.469 


3.068 


4.026 


5.047 


6.065 


7.981 


10.020 


11.938 


Length (ft) 












Capacity 


n Cubic Feet of Gas per Hour 












10 


172 


360 


678 


1,390 


2,090 


4,020 


6,400 


11,300 


23,100 


41,800 


67,600 


139,000 


252,000 


399,000 


20 


118 


247 


466 


957 


1,430 


2,760 


4,400 


7,780 


15,900 


28,700 


46,500 


95,500 


173,000 


275,000 


30 


95 


199 


374 


768 


1,150 


2,220 


3,530 


6,250 


12,700 


23,000 


37,300 


76,700 


139,000 


220,000 


40 


81 


170 


320 


657 


985 


1,900 


3,020 


5,350 


10,900 


19,700 


31,900 


65,600 


119,000 


189,000 


50 


72 


151 


284 


583 


873 


1,680 


2,680 


4,740 


9,660 


17,500 


28,300 


58,200 


106,000 


167,000 


60 


65 


137 


257 


528 


791 


1,520 


2,430 


4,290 


8,760 


15,800 


25,600 


52,700 


95,700 


152,000 


70 


60 


126 


237 


486 


728 


1,400 


2,230 


3,950 


8,050 


14,600 


23,600 


48,500 


88,100 


139,000 


80 


56 


117 


220 


452 


677 


1,300 


2,080 


3,670 


7,490 


13,600 


22,000 


45,100 


81,900 


130,000 


90 


52 


110 


207 


424 


635 


1,220 


1,950 


3,450 


7,030 


12,700 


20,600 


42,300 


76,900 


122,000 


100 


50 


104 


195 


400 


600 


1,160 


1,840 


3,260 


6,640 


12,000 


19,500 


40,000 


72,600 


115,000 


125 


44 


92 


173 


355 


532 


1,020 


1,630 


2,890 


5,890 


10,600 


17,200 


35,400 


64,300 


102,000 


150 


40 


83 


157 


322 


482 


928 


1,480 


2,610 


5,330 


9,650 


15,600 


32,100 


58,300 


92,300 


175 


37 


11 


144 


296 


443 


854 


1,360 


2,410 


4,910 


8,880 


14,400 


29,500 


53,600 


84,900 


200 


34 


71 


134 


275 


412 


794 


1,270 


2,240 


4,560 


8,260 


13,400 


27,500 


49,900 


79,000 


250 


30 


63 


119 


244 


366 


704 


1,120 


1,980 


4,050 


7,320 


11,900 


24,300 


44,200 


70,000 


300 


27 


57 


108 


221 


331 


638 


1,020 


1,800 


3,670 


6,630 


10,700 


22,100 


40,100 


63,400 


350 


25 


53 


99 


203 


305 


587 


935 


1,650 


3,370 


6,100 


9,880 


20,300 


36,900 


58,400 


400 


23 


49 


92 


189 


283 


546 


870 


1,540 


3,140 


5,680 


9,190 


18,900 


34,300 


54,300 


450 


22 


46 


86 


177 


266 


512 


816 


1,440 


2,940 


5,330 


8,620 


17,700 


32,200 


50,900 


500 


21 


43 


82 


168 


251 


484 


771 


1,360 


2,780 


5,030 


8,150 


16,700 


30,400 


48,100 


550 


20 


41 


78 


159 


239 


459 


732 


1,290 


2,640 


4,780 


7,740 


15,900 


28,900 


45,700 


600 


19 


39 


74 


152 


228 


438 


699 


1,240 


2,520 


4,560 


7,380 


15,200 


27,500 


43,600 


650 


18 


38 


71 


145 


218 


420 


669 


1,180 


2,410 


4,360 


7,070 


14,500 


26,400 


41,800 


700 


17 


36 


68 


140 


209 


403 


643 


1,140 


2,320 


4,190 


6,790 


14,000 


25,300 


40,100 


750 


17 


35 


66 


135 


202 


389 


619 


1,090 


2,230 


4,040 


6,540 


13,400 


24,400 


38,600 


800 


16 


34 


63 


130 


195 


375 


598 


1,060 


2,160 


3,900 


6,320 


13,000 


23,600 


37,300 


850 


16 


33 


61 


126 


189 


363 


579 


1,020 


2,090 


3,780 


6,110 


12,600 


22,800 


36,100 


900 


15 


32 


59 


122 


183 


352 


561 


992 


2,020 


3,660 


5,930 


12,200 


22,100 


35,000 


950 


15 


31 


58 


118 


178 


342 


545 


963 


1,960 


3,550 


5,760 


11,800 


21,500 


34,000 


1,000 


14 


30 


56 


115 


173 


333 


530 


937 


1,910 


3,460 


5,600 


11,500 


20,900 


33,100 


1,100 


14 


28 


53 


109 


164 


316 


503 


890 


1,810 


3,280 


5,320 


10,900 


19,800 


31,400 


1,200 


13 


27 


51 


104 


156 


301 


480 


849 


1,730 


3,130 


5,070 


10,400 


18,900 


30,000 


1,300 


12 


26 


49 


100 


150 


289 


460 


813 


1,660 


3,000 


4,860 


9,980 


18,100 


28,700 


1,400 


12 


25 


47 


96 


144 


277 


442 


781 


1,590 


2,880 


4,670 


9,590 


17,400 


27,600 


1,500 


11 


24 


45 


93 


139 


267 


426 


752 


1,530 


2,780 


4,500 


9,240 


16,800 


26,600 


1,600 


11 


23 


44 


89 


134 


258 


411 


727 


1,480 


2,680 


4,340 


8,920 


16,200 


25,600 


1,700 


11 


22 


42 


86 


130 


250 


398 


703 


1,430 


2,590 


4,200 


8,630 


15,700 


24,800 


1,800 


10 


22 


41 


84 


126 


242 


386 


682 


1,390 


2,520 


4,070 


8,370 


15,200 


24,100 


1,900 


10 


21 


40 


81 


122 


235 


375 


662 


1,350 


2,440 


3,960 


8,130 


14,800 


23,400 


2,000 


NA 


20 


39 


79 


119 


229 


364 


644 


1,310 


2,380 


3,850 


7,910 


14,400 


22,700 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch := 6.895 kPa, 1-inch water column - 0.2488 kPa, 

1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m'/h, 1 degree = 0.01745 rad. 
Notes: 

1. NA means a flow of less than 10 cfh. 

2. All table entries have been rounded to three significant digits. 



380 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FUEL GAS 





TABLE G241 3.4(2) [402.4(3)] 
SCHEDULE 40 METALLIC PIP 


E 


Gas 


Natural 




Inlet Pressure 


2.0 psi 




Pressure Drop 


1.0 psi 




Specific Gravity 


0.60 










PIPE SIZE (inch) 


Nominal 


'/2 


'U 


1 


IV4 


IV2 


2 


2V2 


3 


4 


Actual ID 


0.622 


0.824 


1.049 


1.380 


1.610 


2.067 


2.469 


3.068 


4.026 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


10 


1,510 


3,040 


5,560 


11,400 


17,100 


32,900 


52,500 


92,800 


189,000 


20 


1,070 


2,150 


3,930 


8,070 


12,100 


23,300 


37,100 


65,600 


134,000 


30 


869 


1,760 


3,210 


6,590 


9,880 


19,000 


30,300 


53,600 


109,000 


40 


753 


1,520 


2,780 


5,710 


8,550 


16,500 


26,300 


46,400 


94,700 


50 


673 


1,360 


2,490 


5,110 


7,650 


14,700 


23,500 


41,500 


84,700 


60 


615 


1,240 


2,270 


4,660 


6,980 


13,500 


21,400 


37,900 


77,300 


70 


569 


1,150 


2,100 


4,320 


6,470 


12,500 


19,900 


35,100 


71,600 


80 


532 


1,080 


1,970 


4,040 


6,050 


11,700 


18,600 


32,800 


67,000 


90 


502 


1,010 


1,850 


3,810 


5,700 


11,000 


17,500 


30,900 


63,100 


100 


462 


934 


1,710 


3,510 


5,260 


10,100 


16,100 


28,500 


58,200 


125 


414 


836 


1,530 


3,140 


4,700 


9,060 


14,400 


25,500 


52,100 


150 


372 


751 


1,370 


2,820 


4,220 


8,130 


13,000 


22,900 


46,700 


175 


344 


695 


1,270 


2,601 


3,910 


7,530 


12,000 


21,200 


43,300 


200 


318 


642 


1,170 


2,410 


3,610 


6,960 


11,100 


19,600 


40,000 


250 


279 


583 


1,040 


2,140 


3,210 


6,180 


9,850 


17,400 


35,500 


300 


253 


528 


945 


1,940 


2,910 


5,600 


8,920 


15,800 


32,200 


350 


232 


486 


869 


1,790 


2,670 


5,150 


8,210 


14,500 


29,600 


400 


216 


452 


809 


1,660 


2,490 


4,790 


7,640 


13,500 


27,500 


450 


203 


424 


759 


1,560 


2,330 


4,500 


7,170 


12,700 


25,800 


500 


192 


401 


717 


1,470 


2,210 


4,250 


6,770 


12,000 


24,400 


550 


182 


381 


681 


1,400 


2,090 


4,030 


6,430 


11,400 


23,200 


600 


174 


363 


650 


1,330 


2,000 


3,850 


6,130 


10,800 


22,100 


650 


166 


348 


622 


1,280 


1,910 


3,680 


5,870 


10,400 


21,200 


700 


160 


334 


598 


1,230 


1,840 


3,540 


5,640 


9,970 


20,300 


750 


154 


322 


576 


1,180 


1,770 


3,410 


5,440 


9,610 


19,600 


800 


149 


311 


556 


1,140 


1,710 


3,290 


5,250 


9,280 


18,900 


850 


144 


301 


538 


1,100 


1,650 


3,190 


5,080 


■ 8,980 


18,300 


900 


139 


292 


522 


1,070 


1,600 


3,090 


4,930 


8,710 


17,800 


950 


135 


283 


507 


1,040 


1,560 


3,000 


4,780 


8,460 


17,200 


1,000 


132 


275 


493 


1,010 


1,520 


2,920 


4,650 


8,220 


16,800 


1,100 


125 


262 


468 


960 


1,440 


2,770 


4,420 


7,810 


15,900 


1,200 


119 


250 


446 


917 


1,370 


2,640 


4,220 


7,450 


15,200 


1,300 


114 


239 


427 


878 


1,320 


2,530 


4,040 


7,140 


14,600 


1,400 


110 


230 


411 


843 


1,260 


2,430 


3,880 


6,860 


14,000 


1,500 


106 


221 


396 


812 


1,220 


2,340 


3,740 


6,600 


13,500 


1,600 


102 


214 


382 


784 


1,180 


2,260 


3,610 


6,380 


13,000 


1,700 


99 


207 


370 


759 


1,140 


2,190 


3,490 


6,170 


12,600 


1,800 


96 


200 


358 


736 


1,100 


2,120 


3,390 


5,980 


12,200 


1,900 


93 


195 


348 


715 


1,070 


2,060 


3,290 


5,810 


11,900 


2,000 


91 


189 


339 


695 


1,040 


2,010 


3,200 


5,650 


11,500 



For SI: 1 inch = 25.4 mm, 1 foot == 304.8 mm, 

1 British thermal unit per hour = 0.293 

Note: All table entries have been rounded to three si 



1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 
1 W, 1 cubic foot per hour = 0.0283 m'/h, 1 degree = 0.01745 rad. 
gnificant digits. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



381 



FUEL GAS 





TABLE G241 3.4(3) [402.4(7)] 
SEMIRIGID COPPER TUBING 




Gas 


Natural 




Inlet Pressure 


Less than 2 psi 




Pressure Drop 


0.5 in. w.c. 




Specific Gravity 


0.60 












TUBE SIZE (inch) 


Nominal 


K&L 


V4 


\ 


'/2 


% 


% 


1 


1V4 


1V2 


2 


ACR 


\ 


% 


% 


% 


'k 


iVs 


1^/8 





— 


Outside 


0.375 


0.500 


0.625 


0.750 


0.875 


1.125 


1.375 


1.625 


2.125 


Inside 


0.305 


0.402 


0.527 


0.652 


0.745 


0.995 


1.245 


1.481 


1.959 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


10 


27 


55 


111 


195 


276 


590 


1,060 


1,680 


3,490 


20 


18 


38 


77 


134 


190 


406 


730 


1,150 


2,400 


30 


15 


30 


61 


107 


152 


326 


586 


925 


1,930 


40 


13 


26 


53 


92 


131 


279 


502 


791 


1,650 


50 


11 


23 


47 


82 


116 


247 


445 


701 


1,460 


60 


10 


21 


42 


74 


105 


224 


403 


635 


1,320 


70 


NA 


19 


39 


68 


96 


206 


371 


585 


1,220 


80 


NA 


18 


36 


63 


90 


192 


345 


544 


1,130 


90 


NA 


17 


34 


59 


84 


180 


324 


510 


1,060 


100 


NA 


16 


32 


56 


79 


170 


306 


482 


1,000 


125 


NA 


14 


28 


50 


70 


151 


271 


427 


890 


150 


NA 


13 


26 


45 


64 


136 


245 


387 


806 


175 


NA 


12 


24 


41 


59 


125 


226 


356 


742 


200 


NA 


11 


22 


39 


55 


117 


210 


331 


690 


250 


NA 


NA 


20 


34 


48 


103 


186 


294 


612 


300 


NA 


NA 


18 


31 


44 


94 


169 


266 


554 


350 


NA 


NA 


16 


28 


40 


86 


155 


245 


510 


400 


NA 


NA 


15 


26 


38 


80 


144 


228 


474 


450 


NA 


NA 


14 


25 


35 


75 


135 


214 


445 


500 


NA 


NA 


13 


23 


33 


71 


128 


202 


420 


550 


NA 


NA 


13 


22 


32 


68 


122 


192 


399 


600 


NA 


NA 


12 


21 


30 


64 


116 


183 


381 


650 


NA 


NA 


12 


20 


29 


62 


111 


175 


365 


700 


NA 


NA 


11 


20 


28 


59 


107 


168 


350 


750 


NA ■ 


NA 


11 


19 


27 


57 


103 


162 


338 


800 


NA 


NA 


10 


18 


26 


55 


99 


156 


326 


850 


NA 


NA 


10 


18 


25 


53 


96 


151 


315 


900 


NA 


NA 


NA 


17 


24 


52 


93 


147 


306 


950 


NA 


NA 


NA 


17 


24 


50 


90 


143 


297 


1,000 


NA 


NA 


NA 


16 


23 


49 


88 


139 


289 


1,100 


NA 


NA 


NA 


15 


22 


46 


84 


132 


274 


1,200 


NA 


NA 


NA 


15 


21 


44 


80 


126 


262 


1,300 


NA 


NA 


NA 


14 


20 


42 


76 


120 


251 


1,400 


NA 


NA 


NA 


13 


19 


41 


73 


116 


241 


1,500 


NA 


NA 


NA 


13 


18 


39 


71 


111 


232. 


1,600 


NA 


NA 


NA 


13 


18 


38 


68 


108 


224 


1,700 


NA 


NA 


NA 


12 


17 


37 


66 


104 


217 


1,800 


NA 


NA 


NA 


12 


17 


36 


64 


101 


210 


1,900 


NA 


NA 


NA 


11 


16 


35 


62 


98 


204 


2,000 


NA 


NA 


NA 


11 


16 


34 


60 


95 


199 



For SI: 1 inch - 25 A mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 

1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m'/h, 1 degree = 0.01745 rad. 
Notes: 

1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 

2. NA means a flow of less than 10 cfh. 

3. All table entries have been rounded to three significant digits. 



382 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



FUEL GAS 





Gas 


Natural 


TABLE G241 3.4(4) [402.4(10)] 
SEMIRIGID COPPER TUBING 


Inlet Pressure 


2.0 psi 


Pressure Drop 


1.0 psi 




Specific Gravity 


0.60 






TUBE SIZE (inch) 


Nominal 


K&L 


V4 


% 


V2 


'k 


V4 


1 


1V4 


I'll 


2 




ACR 


% 


% 


^8 


\ 


'k 


I'/s 


W 








Outside 


0.375 


0.500 


0.625 


0.750 


0.875 


1.125 


1.375 


1.625 


2.125 


Inside 


0.305 


0.402 


0.527 


0.652 


0.745 


0.995 


1.245 


1.481 


1.959 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


10 


245 


506 


1,030 


1,800 


2,550 


5,450 


9,820 


15,500 


32,200 


20 


169 


348 


708 


1,240 


1,760 


3,750 


6,750 


10,600 


22,200 


30 


135 


279 


568 


993 


1,410 


3,010 


5,420 


8,550 


17,800 


40 


116 


239 


486 


850 


1,210 


2,580 


4,640 


7,310 


15,200 


50 


103 


212 


431 


754 


1,070 


2,280 


4,110 


6,480 


13,500 


60 


93 


192 


391 


683 


969 


2,070 


3,730 


5,870 


12,200 


70 


86 


177 


359 


628 


891 


1,900 


3,430 


5,400 


11,300 


80 


80 


164 


334 


584 


829 


1,770 


3,190 


5,030 


10,500 


90 


75 


154 


314 


548 


778 


1,660 


2,990 


4,720 


9,820 


100 


71 


146 


296 


518 


735 


1,570 


2,830 


4,450 


9,280 


125 


63 


129 


263 


459 


651 


1,390 


2,500 


3,950 


8,220 


150 


57 


117 


238 


416 


590 


1,260 


2,270 


3,580 


7,450 


175 


52 


108 


219 


383 


543 


1,160 


2,090 


3,290 


6,850 


200 


49 


100 


204 


356 


505 


1,080 


1,940 


3,060 


6,380 


250 


43 


89 


181 


315 


448 


956 


1,720 


2,710 


5,650 


300 


39 


80 


164 


286 


406 


866 


1,560 


2,460 


5,120 


350 


36 


74 


150 


263 


373 


797 


1,430 


2,260 


4,710 


400 


33 


69 


140 


245 


347 


741 


1,330 


2,100 


4,380 


450 


31 


65 


131 


230 


326 


696 


1,250 


1,970 


4,110 


500 


30 


61 


124 


217 


308 


657 


1,180 


1,870 


3,880 


550 


28 


58 


118 


206 


292 


624 


1,120 


1,770 


3,690 


600 


27 


55 


112 


196 


279 


595 


1,070 


1,690 


3,520 


650 


26 


53 


108 


188 


267 


570 


1,030 


1,620 


3,370 


700 


25 


51 


103 


181 


256 


548 


986 


1,550 


3,240 


750 


24 


49 


100 


174 


247 


528 


950 


1,500 


3,120 


800 


23 


47 


96 


168 


239 


510 


917 


1,450 


3,010 


850 


22 


46 


93 


163 


231 


493 


888 


1,400 


2,920 


900 


22 


44 


90 


158 


224 


478 


861 


1,360 


2,830 


950 


21 


43 


88 


153 


217 


464 


836 


1,320 


2,740 


1,000 


20 


42 


85 


149 


211 


452 


813 


1,280 


2,670 


1,100 


19 


40 


81 


142 


201 


429 


772 


1,220 


2,540 


1,200 


18 


38 


77 


135 


192 


409 


737 


1,160 


2,420 


1,300 


18 


36 


74 


129 


183 


392 


705 


1,110 


2,320 


1,400 


17 


35 


71 


124 


176 


376 


678 


1,070 


2,230 


1,500 


16 


34 


68 


120 


170 


363 


653 


1,030 


2,140 


1,600 


16 


33 


66 


116 


164 


350 


630 


994 


2,070 


1,700 


15 


31 


64 


112 


159 


339 


610 


962 


2,000 


1,800 


15 


30 


62 


108 


154 


329 


592 


933 


1,940 


1,900 


14 


30 


60 


105 


149 


319 


575 


906 


1,890 


2,000 


14 


29 


59 


102 


145 


310 


559 


881 


1,830 



For SI: 



Notes: 



1 inch - 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 
I British thermal unit per hour = 0.293 1 W, 1 cubic foot per hour = 0.0283 m^/h, 1 degree = 0.01745 rad. 



1. Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 

2. All table entries have been rounded to three signiiicant digits. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



383 



FUEL GAS 





Gas 


Natural 


TABLE G241 3.4(5) [402.4(13)] 
CORRUGATED STAINLESS STEEL TUBING (CSST) 


Inlet Pressure 


Less than 2 psi 


Pressure Drop 


0.5 in. w.c. 




Specific Gravity 


0.60 


TUBE SIZE (EHD) 


Flow 
Designation 


13 


15 


18 


19 


23 


25 


30 


31 


37 


46 


48 


60 


62 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


5 


46 


63 


115 


134 


225 


270 


471 


546 


895 


1,790 


2,070 


3,660 


4,140 


10 


32 


44 


82 


95 


161 


192 


330 


383 


639 


1,260 


1,470 


2,600 


2,930 


15 


25 


35 


66 


77 


132 


157 


267 


310 


524 


1,030 


1,200 


2,140 


2,400 


20 


22 


31 


58 


67 


116 


137 


231 


269 


456 


888 


1,050 


1,850 


2,080 


25 


19 


27 


52 


60 


104 


122 


206 


240 


409 


793 


936 


1,660 


1,860 


30 


18 


25 


47 


55 


96 


112 


188 


218 


374 


723 


856 


1,520 


1,700 


40 


15 


21 


41 


47 


83 


97 


162 


188 


325 


625 


742 


1,320 


1,470 


50 


13 


19 


37 


42 


75 


87 


144 


168 


292 


559 


665 


1,180 


1,320 


60 


12 


17 


34 


38 


68 


80 


131 


153 


267 


509 


608 


1,080 


1,200 


70 


11 


16 


31 


36 


63 


74 


121 


141 


248 


471 


563 


1,000 


1,110 


80 


10 


15 


29 


33 


60 


69 


113 


132 


232 


440 


527 


940 


1,040 


90 


10 


14 


28 


32 


57 


65 


107 


125 


219 


415 


498 


887 


983 


100 


9 


13 


26 


30 


54 


62 


101 


118 


208 


393 


472 


843 


933 


150 


7 


10 


20 


23 


42 


48 


78 


91 


171 


320 


387 


691 


762 


200 


6 


9 


18 


21 


38 


44 


71 


82 


148 


277 


336 


600 


661 


250 


5 


8 


16 


19 


34 


39 


63 


74 


133 


247 


301 


538 


591 


300 


5 


7 


15 


17 


32 


36 


57 


67 


95 


226 


275 


492 


540 



For SI: 1 inch = 25.4 ram, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1-inch water column = 0.2488 kPa, 

1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m^/h, 1 degree = 0.01745 rad. 
Notes: 

1 . Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased by an equivalent 
length of tubing to the following equation: L = 1.3«, where L is additional length (feet) of tubing and n is the number of additional fittings and/or bends. 

2. EHD — Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the 
greater the gas capacity of the tubing. 

3. All table entries have been rounded to three significant digits. 



384 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FUEL GAS 





Gas 


^Jatural 


TABLE G241 3.4(6) [402.4(16)] 
CORRUGATED STAINLESS STEEL TUBING (CSST) 


Inlet Pressure < 


l.O psi 


Pressure Drop 


1.0 psi 




Specific Gravity ( 


D.60 


TUBE SIZE (EHD) 


Flow 
Designation 


13 


15 


18 


19 


23 


25 


30 


31 


37 


46 


48 


60 


62 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


10 


270 


353 


587 


700 


1,100 


1,370 


2,590 


2,990 


4,510 


9,600 


10,700 


18,600 


21,600 


25 


166 


220 


374 


444 


709 


876 


1,620 


1,870 


2,890 


6,040 


6,780 


11,900 


13,700 


30 


151 


200 


342 


405 


650 


801 


1,480 


1,700 


2,640 


5,510 


6,200 


10,900 


12,500 


40 


129 


172 


297 


351 


567 


696 


1,270 


1,470 


2,300 


4,760 


5,380 


9,440 


10,900 


50 


115 


154 


266 


314 


510 


624 


1,140 


1,310 


2,060 


4,260 


4,820 


8,470 


9,720 


75 


93 


124 


218 


257 


420 


512 


922 


1,070 


1,690 


3,470 


3,950 


6,940 


7,940 


80 


89 


120 


211 


249 


407 


496 


892 


1,030 


1,640 


3,360 


3,820 


6,730 


7,690 


100 


79 


107 


189 


222 


366 


445 


795 


920 


1,470 


3,000 


3,420 


6,030 


6,880 


150 


64 


87 


155 


182 


302 


364 


646 


748 


1,210 


2,440 


2,800 


4,940 


5,620 


200 


55 


75 


135 


157 


263 


317 


557 


645 


1,050 


2,110 


2,430 


4,290 


4,870 


250 


49 


67 


121 


141 


236 


284 


497 


576 


941 


1,890 


2,180 


3,850 


4,360 


300 


44 


61 


110 


129 


217 


260 


453 


525 


862 


1,720 


1,990 


3,520 


3,980 


400 


38 


52 


96 


111 


189 


225 


390 


453 


749 


1,490 


1,730 


3,060 


3,450 


500 


34 


46 


86 


100 


170 


202 


348 


404 


552 


1,330 


1,550 


2,740 


3,090 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa, 1-inch water column = 0.2488 kPa, 

1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m^/h, 1 degree = 0.01745 rad. 
Notes: 

1 . Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds V4 psi, DO NOT USE THIS TABLE. Consult with the regula- 
tor manufacturer for pressure drops and capacity factors. Pressure drops across a regulator can vary with flow rate. 

2. CAUTION: Capacities shown in the table might exceed maximum capacity for a selected regulator. Consult with the regulator or tubing manufacturer for guid- 
ance. 

3 . Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased by an equivalent 
length of tubing to the following equation: L = 1 .3n where L is additional length (feet) of tubing and n is the number of additional fittings and/or bends. 

4. EHD — Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the 
greater the gas capacity of the tubing. 

5. All table entries have been rounded to three significant digits. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



385 



FUEL GAS 



TABLE G241 3.4(7) [402.4(19)] 
POLYETHYLENE PLASTIC PIPE 



Gas 

Inlet Pressure 



Pressure Drop 



Specific Gravity 



Natural 

Less than 2 psi 



0.5 in. w.c. 



0.60 



PIPE SIZE (In.) 



For SI: 1 inch = 25.4 mm, 1 foot = 304.J 

1 British thermal unit per hour = 

Note: All table entries have been rounded 



1 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 
0.2931 W, 1 cubic foot per hour = 0.0283 m^/h, 1 degree = 0.01745 rad. 
to three significant digits. 



kPa, 



Nominal OD 


'/a 


'U 


1 


IV4 


IV2 


2 


Designation 


SDR 9.33 


SDR 11.0 


SDR 11.00 


SDR 10.00 


SDR 11.00 


SDR 11.00 


Actual ID 


0.660 


0.860 


1.077 


1.328 


1.554 


1.943 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


10 


201 


403 


726 


1,260 


1,900 


3,410 


20 


138 


277 


499 


865 


1,310 


2,350 


30 


111 


222 


401 


695 


1,050 


1,880 


40 


95 


190 


343 


594 


898 


1,610 


50 


84 


169 


304 


527 


796 


1,430 


60 


76 


153 


276 


477 


721 


1,300 


70 


70 


140 


254 


439 


663 


1,190 


80 


65 


131 


236 


409 


617 


1,110 


90 


61 


123 


221 


383 


579 


1,040 


100 


58 


116 


209 


362 


547 


983 


125 


51 


103 


185 


321 


485 


871 


150 


46 


93 


168 


291 


439 


789 


175 


43 


86 


154 


268 


404 


726 


200 


40 


80 


144 


249 


376 


675 


250 


35 


71 


127 


221 


333 


598 


300 


32 


64 


115 


200 


302 


542 


350 


29 


59 


106 


184 


278 


499 


400 


27 


55 


99 


171 


258 


464 


450 


26 


51 


93 


160 


242 


435 


500 


24 


48 


88 


152 


229 


411 



386 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FUEL GAS 





TABLE G241 3.4(8) [402.4(20)] 
POLYETHYLENE PLASTIC PIPE 




Gas 


Natural 






Inlet Pressure 


2.0 psi 






Pressure Drop 


1 .0 psi 






Specific Gravity 


0.60 








PIPE SIZE (in.) 


Nominal OD 


% 


% 


1 


IV4 


1% 


2 


Designation 


SDR 9.33 


SDR 11.0 


SDR 11.00 


SDR 10.00 


SDR 11.00 


SDR 11.00 


Actual ID 


0.660 


0.860 


1.077 


1.328 


1.554 


1.943 


Length (ft) 


Capacity in Cubic Feet of Gas per Hour 


10 


1,860 


3,720 


6,710 


11,600 


17,600 


31,600 


20 


1,280 


2,560 


4,610 


7,990 


12,100 


21,700 


30 


1,030 


2,050 


3,710 


6,420 


9,690 


17,400 


40 


878 


1,760 


3,170 


5,490 


8,300 


14,900 


50 


778 


1,560 


2,810 


4,870 


7,350 


13,200 


60 


705 


1,410 


2,550 


4,410 


6,660 


12,000 


70 


649 


1,300 


2,340 


4,060 


6,130 


11,000 


80 


603 


1,210 


2,180 


3,780 


5,700 


10,200 


90 


566 


1,130 


2,050 


3,540 


5,350 


9,610 


100 


535 


1,070 


1,930 


3,350 


5,050 


9,080 


125 


474 


949 


1,710 


2,970 


4,480 


8,050 


150 


429 


860 


1,550 


2,690 


4,060 


7,290 


175 


395 


791 


1,430 


2,470 


3,730 


6,710 


200 


368 


736 


1,330 


2,300 


3,470 


6,240 


250 


326 


652 


1,180 


2,040 


3,080 


5,530 


300 


295 


591 


1,070 


1,850 


2,790 


5,010 


350 


272 


544 


981 


1,700 


2,570 


4,610 


400 


253 


506 


913 


1,580 


2,390 


4,290 


450 


237 


475 


856 


1,480 


2,240 


4,020 


500 


224 


448 


809 


1,400 


2,120 


3,800 


550 


213 


426 


768 


1,330 


2,010 


3,610 


600 


203 


406 


733 


1,270 


1,920 


3,440 


650 


194 


389 


702 


1,220 


1,840 


3,300 


700 


187 


374 


674 


1,170 


1,760 


3,170 


750 


180 


360 


649 


1,130 


1,700 


3,050 


800 


174 


348 


627 


1,090 


1,640 


2,950 


850 


168 


336 


607 


1,050 


1,590 


2,850 


900 


163 


326 


588 


1,020 


1,540 


2,770 


950 


158 


317 


572 


990 


1,500 


2,690 


1,000 


154 


308 


556 


963 


1,450 


2,610 


1,100 


146 


293 


528 


915 


1,380 


2,480 


1,200 


139 


279 


504 


873 


1,320 


2,370 


1,300 


134 


267 


482 


836 


1,260 


2,270 


1,400 


128 


257 


463 


803 


1,210 


2,180 


1,500 


124 


247 


446 


773 


1,170 


2,100 


1,600 


119 


239 


431 


747 


1,130 


2,030 


1,700 


115 


231 


417 


723 


1,090 


1,960 


1,800 


112 


224 


404 


701 


1,060 


1,900 


1,900 


109 


218 


393 


680 


1,030 


1,850 


2,000 


106 


212 


382 


662 


1,000 


1,800 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 

1 British thermal unit per hour - 0.2931 W, 1 cubic foot per hour = 0.0283 m'/h, 1 degree =:: 0.01745 rad. 
Note: All table entries have been rounded to three significant digits. 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



387 



FUEL GAS 



G2414.4.1 (403.4.1) Cast iron. Cast-iron pipe shall not be 
used. 

G2414.4.2 (403.4.2) Steel. Steel and wrought-iron pipe 
shall be at least of standard weight (Schedule 40) and shall 
comply with one of the following: 

1. ASMEB 36.10, lOM; 

2. ASTM A 53; or 

3. ASTM A 106. 

G2414.5 (403.5) Metallic tubing. Seamless copper, alumi- 
num alloy or steel tubing shall be permitted to be used with 
gases not corrosive to such material. 

G2414.5.1 (403.5.1) Steel tubing. Steel tubing shall com- 
ply with ASTM A 539 or ASTM A 254. 

G2414.5.2 (403.5.2) Copper tubing. Copper tubing shall 
comply with standard Type K or L of ASTM B 88 or ASTM 
B280. 

Copper and brass tubing shall not be used if the gas con- 
tains more than an average of 0.3 grains of hydrogen sulfide 
per 100 standard cubic feet of gas (0.7 milligrams per 100 
liters). 

G2414.5.3 (403.5.4) Corrugated stainless steel tubing. 

Corrugated stainless steel tubing shall be listed in accor- 
dance with ANSI LC 1/CSA 6.26. 

G2414.6 (403.6) Plastic pipe, tubing and fittings. Plastic 
pipe, tubing and fittings used to supply fuel gas shall be used 
outdoors, underground, only, and shall conform to ASTM D 
2513. Pipe shall be marked "Gas" and "ASTM D 2513." 

G2414.6.1 (403.6.1) Anodeless risers. Anodeless risers 
shall comply with the following: 

1. Factory-assembled anodeless risers shall be recom- 
mended by the manufacturer for the gas used and 
shall be leak-tested by the manufacturer in accor- 
dance with written procedures. 

2. Service head adapters and field-assembled anodeless 
risers incorporating service head adapters shall be 
recommended by the manufacturer for the gas used 
by the manufacturer and shall be designed certified to 
meet the requirements of Category I of ASTM D 
2513, and U.S. Department of Transportation, Code 
of Federal Regulations, Title 49, Part 192.281(e). The 
manufacturer shall provide the user qualified installa- 
tion instructions as prescribed by the U.S. Depart- 
ment of Transportation, Code of Federal Regulations, 
Title 49, Part 192.283(b). 

G2414.6.2 (403.6.2) LP-gas systems. The use of plastic 
pipe, tubing and fittings in undiluted liquefied petroleum 
gas piping systems shall be in accordance with NFPA 58. 

G2414.6.3 (403.6.3) Regulator vent piping. Plastic pipe, 
tubing and fittings used to connect regulator vents to remote 
vent terminations shall be of PVC conforming to UL 651. 
PVC vent piping shall not be installed indoors. 

G2414.7 (403.7) Workmanship and defects. Pipe or tubing 
and fittings shall be clear and free from cutting burrs and defects 



in structure or threading, and shall be thoroughly brushed, and 
chip and scale blown. 

Defects in pipe or tubing or fittings shall not be repaired. 
Defective pipe, tubing or fittings shall be replaced. (See Sec- 
tion G2417. 1.2.) 

G2414.8 (403.8) Protective coating. Where in contact with 
material or atmosphere exerting a corrosive action, metallic 
piping and fittings coated with a corrosion-resistant material 
shall be used. External or internal coatings or linings used on 
piping or components shall not be considered as adding 
strength. 

G2414.9 (403.9) Metallic pipe threads. Metallic pipe and fit- 
ting threads shall be taper pipe threads and shall comply with 
ASMEB 1.20.1. 

G2414.9.1 (403.9.1) Damaged threads. Pipe with threads 
that are stripped, chipped, corroded or otherwise damaged 
shall not be used. If a weld opens during the operation of 
cutting or threading, that portion of the pipe shall not be 
used. 

G2414.9.2 (403.9.2) Number of threads. Field threading 
of metalhc pipe shall be in accordance with Table 
G2414.9.2. 

TABLE G241 4.9.2 (403.9.2) 
SPECIFICATIONS FOR THREADING METALLIC PIPE 



IRON PIPE SIZE 
(inches) 


APPROXIMATE 

LENGTH OF 

THREADED PORTION 

(inches) 


APPROXIIVIATE NO. OF 
THREADS TO BE CUT 


% 


'U 


10 


% 


% 


10 


1 


% 


10 


IV4 


1 


11 


IV2 


1 


11 



For SI: 1 inch = 25.4 mm. 

G2414.9.3 (403.9.3) Thread compounds. Thread Goint) 
compounds (pipe dope) shall be resistant to the action of liq- 
uefied petroleum gas or to any other chemical constituents 
of the gases to be conducted through the piping. 

G2414.10 (403.10) Metallic piping joints and fittings. The 

type of piping joint used shall be suitable for the pressure-tem- 
perature conditions and shall be selected giving consideration 
to joint tightness and mechanical strength under the service 
conditions. The joint shall be able to sustain the maximum end 
force due to the internal pressure and any additional forces due 
to temperature expansion or contraction, vibration, fatigue, or 
to the weight of the pipe and its contents. 

G2414.10.1 (403.10.1) Pipe joints. Pipe joints shall be 
threaded, flanged, brazed or welded. Where nonferrous 
pipe is brazed, the brazing materials shall have a melting 
point in excess of 1,000°F (538°C). Brazing alloys shall not 
contain more than 0.05-percent phosphorus. 

G2414.10.2 (403.10.2) Tubing joints. Tubing joints shall 
either be made with approved gas tubing fittings or be 
brazed with a material having a melting point in excess of 



388 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FUEL GAS 



1 ,000°F (538°C). Brazing alloys shall not contain more than 
0.05-percent phosphorus. 

G2414.10.3 (403.10.3) Flared joints. Flared joints shall be 
used only in systems constructed from nonferrous pipe and 
tubing where experience or tests have demonstrated that the 
joint is suitable for the conditions and where provisions are 
made in the design to prevent separation of the joints. 

G2414.10.4 (403.10.4) Metallic fittings. Metallic fittings, 
including valves, strainers and filters shall comply with the 
following: 

1 . Fittings used with steel or wrought-iron pipe shall be 
steel, brass, bronze, malleable iron, ductile iron or 
cast iron. 

2. Fittings used with copper or brass pipe shall be cop- 
per, brass or bronze. 

3. Cast-iron bushings shall be prohibited. 

4. Special fittings. Fittings such as couplings, 
proprietary-type joints, saddle tees, gland-type com- 
pression fittings, and flared, flareless or compres- 
sion-type tubing fittings shall be: used within the 
fitting manufacturer's pressure-temperature recom- 
mendations; used within the service conditions antici- 
pated with respect to vibration, fatigue, thermal 
expansion or contraction; installed or braced to pre- 
vent separation of the joint by gas pressure or external 
physical damage; and shall be approved. 

G2414.il (403.11) Plastic piping, joints and fittings. Plastic 
pipe, tubing and fittings shall be joined in accordance with the 
manufacturers' instructions. Such joints shall comply with the 
following: 

1 . The joints shall be designed and installed so that the lon- 
gitudinal pull-out resistance of the joints will be at least 
equal to the tensile strength of the plastic piping material. 

2. Heat-fusion joints shall be made in accordance with 
qualified procedures that have been established and 
proven by test to produce gas-tight joints at least as 
strong as the pipe or tubing being joined. Joints shall be 
made with the joining method recommended by the pipe 
manufacturer. Heat fusion fittings shall be marked 
"ASTMD2513." 

3. Where compression-type mechanical joints are used, the 
gasket material in the fitting shall be compatible with the 
plastic piping and with the gas distributed by the system. 
An internal tubular rigid stiffener shall be used in con- 
junction with the fitting. The stiffener shall be flush with 
the end of the pipe or tubing and shall extend at least to 
the outside end of the compression fitting when installed. 
The stiffener shall be free of rough or sharp edges and 
shall not be a force fit in the plastic. Split tubular stiffen- 
ers shall not be used. 

4. Plastic piping joints and fittings for use in liquefied 
petroleum gas piping systems shall be in accordance 
with NFPA 58. 



SECTION G241 5 (404) 
PIPING SYSTEM INSTALLATION 

G2415.1 (404.1) Prohibited locations. Piping shall not be 
installed in or through a circulating air duct, clothes chute, 
chimney or gas vent, ventilating duct, dumbwaiter or elevator 
shaft. Piping installed downstream of the point of delivery shall 
not extend through any townhouse unit other than the unit 
served by such piping. 

G2415.2 (404.2) Piping in solid partitions and walls. Con- 
cealed piping shall not be located in solid partitions and solid 
walls, unless installed in a chase or casing. 

G2415.3 (404.3) Piping in concealed locations. Portions of a 
piping system installed in concealed locations shall not have 
unions, tubing fittings, right and left couphngs, bushings, com- 
pression couplings, and swing joints made by combinations of 
fittings. 

Exceptions: 

1. Tubingjoined by brazing. 

2. Fittings listed for use in concealed locations. 

G2415.4 (404.4) Piping through foundation wall. Under- 
ground piping, where installed below grade through the outer 
foundation or basement wall of a building, shall be encased in a 
protective pipe sleeve. The annular space between the gas pip- 
ing and the sleeve shall be sealed. 

G2415.5 (404.5) Protection against physical damage. In 

concealed locations, where piping other than black or galva- 
nized steel is installed through holes or notches in wood studs, 
joists, rafters or similar members less than 1.5 inches (38 mm) 
from the nearest edge of the member, the pipe shall be pro- 
tected by shield plates. Shield plates shall be a minimum of 
Vig-inch-thick (1.6 mm) steel, shall cover the area of the pipe 
where the member is notched or bored and shall extend a mini- 
mum of 4 inches (102 mm) above sole plates, below top plates 
and to each side of a stud, joist or rafter. 

G2415.6 (404.6) Piping in solid floors. Piping in sohd floors 
shall be laid in channels in the floor and covered in a manner 
that will allow access to the piping with a minimum amount of 
damage to the building. Where such piping is subject to expo- 
sure to excessive moisture or corrosive substances, the piping 
shall be protected in an approved manner. As an alternative to 
installation in channels, the piping shall be installed in a con- 
duit of Schedule 40 steel, wrought iron, PVC or ABS pipe with 
tightly sealed ends and joints. Both ends of such conduit shall 
extend not less than 2 inches (5 1 mm) beyond the point where 
the pipe emerges from the floor. The conduit shall be vented 
above grade to the outdoors and shall be installed so as to pre- 
vent the entry of water and insects. 

G2415.7 (404.7) Above-ground piping outdoors. All piping 
installed outdoors shall be elevated not less than VI2 inches 
(152 mm) above ground and where installed across roof sur- 
faces, shall be elevated not less than VI2 inches (152 mm) 
above the roof surface. Piping installed above ground, out- 
doors, and installed across the surface of roofs shall be securely 
supported and located where it will be protected from physical 
damage. Where passing through an outside wall, the piping 
shall also be protected against corrosion by coating or wrap- 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



389 



FUEL GAS 



ping with an inert material. Where piping is encased in a pro- 
tective pipe sleeve, the annular space between the piping and 
the sleeve shall be sealed. 

G2415.8 (404.8) Protection against corrosion. Metallic pipe 
or tubing exposed to corrosive action, such as soil condition or 
moisture, shall be protected in an approved manner. Zinc coat- 
ings (galvanizing) shall not be deemed adequate protection for 
gas piping underground. Ferrous metal exposed in exterior 
locations shall be protected from corrosion in a manner satis- 
factory to the code official. Where dissimilar metals are joined 
underground, an insulating coupling or fitting shall be used. 
Piping shall not be laid in contact with cinders. 

G2415.8.1 (404.8.1) Prohibited use. Uncoated threaded or 
socket welded joints shall not be used in piping in contact 
with soil or where internal or external crevice corrosion is 
known to occur. 

G2415.8.2 (404.8.2) Protective coatings and wrapping. 

Pipe protective coatings and wrappings shall be approved 
for the application and shall be factory applied. 

Exception: Where installed in accordance with the man- 
ufacturer's installation instructions, field application of 
coatings and wrappings shall be permitted for pipe nip- 
ples, fittings and locations where the factory coating or 
wrapping has been damaged or necessarily removed at 
joints. 

G2415.9 (404.9) Minimum burial depth. Underground pip- 
ing systems shall be installed a minimum depth of 12 inches 
(305 mm) below grade, except as provided for in Section 
G2415.9.1. 

G2415.9.1 (404.9.1) Individual outside appliances. Indi- 
vidual lines to outside lights, grills or other appliances shall 
be installed a minimum of 8 inches (203 mm) below fin- 
ished grade, provided that such installation is approved and 
is installed in locations not susceptible to physical damage. 

G2415.10 (404.10) Trenches. The trench shall be graded so 
that the pipe has a firm, substantially continuous bearing on the 
bottom of the trench. 

G2415.il (404.11) Piping underground beneath buildings. 

Piping installed underground beneath buildings is prohibited 
except where the piping is encased in a conduit of wrought 
iron, plastic pipe, or steel pipe designed to withstand the super- 
imposed loads. Such conduit shall extend into an occupiable 
portion of the building and, at the point where the conduit ter- 
minates in the building, the space between the conduit and the 
gas piping shall be sealed to prevent the possible entrance of 
any gas leakage. If the end sealing is capable of withstanding 
the full pressure of the gas pipe, the conduit shall be designed 
for the same pressure as the pipe. Such conduit shall extend not 
less than 4 inches (102 mm) outside the building, shall be 
vented above grade to the outdoors, and shall be installed so as 
prevent the entrance of water and insects. The conduit shall be 
protected from corrosion in accordance with Section G2415.8. 

G2415.12 (404.12) Outlet closures. Gas outlets that do not 
connect to appliances shall be capped gas tight. 

Exception: Listed and labeled flush-mounted-type 
quick-disconnect devices and listed and labeled gas conve- 



nience outlets shall be installed in accordance with the 
manufacturer's installation instructions. 

G2415.13 (404.13) Location of outlets. The unthreaded por- 
tion of piping outlets shall extend not less than 1 inch (25 mm) 
through finished ceilings and walls and where extending 
through floors, outdoor patios and slabs, shall not be less than 2 
inches (5 1 mm) above them. The outlet fitting or piping shall be 
securely supported. Outlets shall not be placed behind doors. 
Outlets shall be located in the room or space where the appli- 
ance is installed. 

Exception: Listed and labeled flush-mounted-type 
quick-disconnect devices and listed and labeled gas conve- 
nience outlets shall be installed in accordance with the man- 
ufacturer's installation instructions. 

G2415.14 (404.14) Plastic pipe. The installation of plastic 
pipe shall comply with Sections G2415.14.1 through 
G2415.14.3. 

G2415.14.1 (404.14.1) Limitations. Plastic pipe shall be 
installed outside underground only. Plastic pipe shall not be 
used within or under any building or slab or be operated at 
pressures greater than 100 psig (689 kPa) for natural gas or 
30 psig (207 kPa) for LP gas. 

Exceptions: 

1 . Plastic pipe shall be permitted to terminate above 
ground outside of buildings where installed in 
premanufactured anodeless risers or service head 
adapter risers that are installed in accordance with 
that manufacturer's installation instructions. 

2. Plastic pipe shall be permitted to terminate with a 
wall head adapter within buildings where the plas- 
tic pipe is inserted in a piping material for fuel gas 
use in buildings. 

G2415.14.2 (404.14.2) Connections. Connections made 
outside and underground between metallic and plastic pip- 
ing shall be made only with transition fittings categorized as 
Category I in accordance with ASTM D 2513. 

G2415.14.3 (404.14.3) Tracer. A yellow insulated copper 
tracer wire or other approved conductor shall be installed 
adjacent to underground nonmetallic piping. Access shall 
be provided to the tracer wire or the tracer wire shall termi- 
nate above ground at each end of the nonmetallic piping. 
The tracer wire size shall not be less than 1 8 AWG and the 
insulation type shall be suitable for direct burial. 

G2415.15 (404.15) Prohibited devices. A device shall not be 
placed inside the piping or fittings that will reduce the 
cross-sectional area or otherwise obstruct the free flow of gas. 

Exception: Approved gas filters. 

G2415.16 (404.16) Testing of piping. Before any system of 
piping is put in service or concealed, it shall be tested to ensure 
that it is gas tight. Testing, inspection and purging of piping 
systems shall comply with Section G2417. 



390 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FUEL GAS 



SECTION G241 6 (405) 
PIPING BENDS AND CHANGES IN DIRECTION 

G2416.1 (405.1) General. Changes in direction of pipe shall 
be permitted to be made by the use of fittings, factory bends or 
field bends. 

G2416.2 (405.2) Metallic pipe. Metallic pipe bends shall com- 
ply with the following: 

1. Bends shall be made only with bending tools and proce- 
dures intended for that purpose. 

2. All bends shall be smooth and free from buckling, cracks 
or other evidence of mechanical damage. 

3 . The longitudinal weld of the pipe shall be near the neutral 
axis of the bend. 

4. Pipe shall not be bent through an arc of more than 90 
degrees (1.6 rad). 

5 . The inside radius of a bend shall be not less than six times 
the outside diameter of the pipe. 

G2416.3 (405.3) Plastic pipe. Plastic pipe bends shall comply 
with the following: 

1 . The pipe shall not be damaged and the internal diameter 
of the pipe shall not be effectively reduced. 

2. Joints shall not be located in pipe bends. 

3. The radius of the inner curve of such bends shall not be 
less than 25 times the inside diameter of the pipe. 

4. Where the piping manufacturer specifies the use of spe- 
cial bending tools or procedures, such tools or proce- 
dures shall be used. 



SECTION G241 7 (406) 
INSPECTION, TESTING AND PURGING 

G2417.1 (406.1) General. Prior to acceptance and initial oper- 
ation, all piping installations shall be inspected and pressure 
tested to determine that the materials, design, fabrication, and 
installation practices comply with the requirements of this 
code. 

G2417.1.1 (406.1.1) Inspections. Inspection shall consist 
of visual examination, during or after manufacture, fabrica- 
tion, assembly or pressure tests as appropriate. 

G2417.1.2 (406.1.2) Repairs and additions. In the event 
repairs or additions are made after the pressure test, the 
affected piping shall be tested. 

Minor repairs and additions are not required to be pres- 
sure tested provided that the work is inspected and connec- 
tions are tested with a noncorrosive leak-detecting fluid or 
other approved leak-detecting methods. 

G2417.1.3 (406.1.3) New branches. Where new branches 
are installed to new appliances, only the newly installed 
branches shall be required to be pressure tested. Connec- 
tions between the new piping and the existing piping shall 
be tested with a noncorrosive leak-detecting fluid or other 
approved leak-detecting methods. 

G2417.1.4 (406.1.4) Section testing. A piping system shall 
be permitted to be tested as a complete unit or in sections. 



Under no circumstances shall a valve in a hne be used as a 
bulkhead between gasin one section of the piping system 
and test medium in an adjacent section, unless two valves 
are installed in series with a valved "tell-tale" located 
between these valves. A valve shall not be subjected to the 
test pressure unless it can be determined that the valve, 
including the valve closing mechanism, is designed to 
safely withstand the test pressure. 

G2417.1.5 (406.1.5) Regulators and valve assemblies. 

Regulator and valve assemblies fabricated independendy of 
the piping system in which they are to be installed shall be 
permitted to be tested with inert gas or air at the time of fab- 
rication. 

G2417.2 (406.2) Test medium. The test medium shall be air, 
nitrogen, carbon dioxide or an inert gas. Oxygen shall not be 
used. 

G2417.3 (406.3) Test preparation. Pipe joints, including 
welds, shall be left exposed for examination during the test. 

Exception: Covered or concealed pipe end joints that have 
been previously tested in accordance with this code. 

G2417.3.1 (406.3.1) Expansion joints. Expansion joints 
shall be provided with temporary restraints, if required, for 
the additional thrust load under test. 

G2417.3.2 (406.3.2) Equipment isolation. Equipment that 
is not to be included in the test shall be either disconnected 
from the piping or isolated by blanks, blind flanges or caps. 

G2417.3.3 (406.3.3) Appliance and equipment discon- 
nection. Where the piping system is connected to appli- 
ances or equipment designed for operating pressures of less 
than the test pressure, such appliances or equipment shall be 
isolated from the piping system by disconnecting them and 
capping the outlet(s). 

G2417.3.4 (406.3.4) Valve isolation. Where the piping sys- 
tem is connected to appliances or equipment designed for 
operating pressures equal to or greater than the test pressure, 
such appliances or equipment shall be isolated from the pip- 
ing system by closing the individual appliance or equipment 
shutoff valve(s). 

G2417.3.5 (406.3.5) Testing precautions. All testing of 
piping systems shall be done with due regard for the safety 
of employees and the public during the test. Prior to testing, 
the interior of the pipe shall be cleared of all foreign mate- 
rial. 

G2417.4 (406.4) Test pressure measurement. Test pressure 
shall be measured with a manometer or with a pressure-mea- 
suring device designed and calibrated to read, record, or indi- 
cate a pressure loss caused by leakage during the pressure test 
period. The source of pressure shall be isolated before the pres- 
sure tests are made. Mechanical gauges used to measure test 
pressures shall have a range such that the highest end of the 
scale is not greater than five times the test pressure. 

G2417.4.1 (406.4.1) Test pressure. The test pressure to be 
used shall be not less than one and one-half times the pro- 
posed maximum working pressure, but not less than 3 psig 
(20 kPa gauge), irrespective of design pressure. Where the 
test pressure exceeds 125 psig (862 kPa gauge), the test 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



391 



FUEL GAS 



pressure shall not exceed a value that produces a hoop stress 
in the piping greater than 50 percent of the specified mini- 
mum yield strength of the pipe. 

G2417.4.2 (406.4.2) Test duration. The test duration shall 
be not less than 10 minutes. 

G2417.5 (406.5) Detection of leaks and defects. The piping 
system shall withstand the test pressure specified without 
showing any evidence of leakage or other defects. Any reduc- 
tion of test pressures as indicated by pressure gauges shall be 
deemed to indicate the presence of a leak unless such reduction 
can be readily attributed to some other cause. 

G2417.5.1 (406.5.1) Detection methods. The leakage shall 
be located by means of an approved combustible gas detec- 
tor, a noncorrosive leak detection fluid or an equivalent non- 
flammable solution. Matches, candles, open flames or other 
methods that could provide a source of ignition shall not be 
used. 

G2417.5.2 (406.5.2) Corrections. Where leakage or other 
defects are located, the affected portion of the piping system 
shall be repaired or replaced and retested. 

G2417.6 (406.6) Piping system, appliance and equipment 
leakage check. Leakage checking of systems and equipment 
shall be in accordance with Sections G2417.6.1 through 
G2417.6.4. 

G2417.6.1 (406.6.1) Test gases. Fuel gas shall be permitted 
to be used for leak checks in piping systems that have been 
tested in accordance with Section G2417. 

G2417.6.2 (406.6.2) Before turning gas on. Before gas is 
introduced into a system of new gas piping, the entire sys- 
tem shall be inspected to determine that there are no open 
fittings or ends and that all valves at unused outlets are 
closed and plugged or capped. 

G2417.6.3 (406.6.3) Leak check. Immediately after the gas 
is turned on into a new system or into a system that has been 
initially restored after an interruption of service, the piping 
system shall be checked for leakage. Where leakage is indi- 
cated, the gas supply shall be shut off until the necessary 
repairs have been made. 

G2417.6.4 (406.6.4) Placing appHances and equipment 
in operation. Appliances and equipment shall be permitted 
to be placed in operation after the piping system has been 
checked for leakage and determined to be free of leakage 
and purged in accordance with Section G2417.7.2. 

G2417.7 (406.7) Purging. Purging of piping shall comply with 
Sections G2417.7.1 through G2417.7.4. 

G2417.7.1 (406.7.1) Removal from service. When gas 
piping is to be opened for servicing, addition or modifica- 
tion, the section to be worked on shall be turned off from the 
gas supply at the nearest convenient point, and the line pres- 
sure vented to the outdoors, or to ventilated areas of suffi- 
cient size to prevent accumulation of flammable mixtures. 

G2417.7.2 (406.7.2) Placing in operation. When piping 
full of air is placed in operation, the air in the piping shall be 
displaced with fuel gas. The air can be safely displaced with 
fuel gas provided that a moderately rapid and continuous 



flow of fuel gas is introduced at one end of the line and air is 
vented out at the other end. The fuel gas flow should be con- 
tinued without interruption until the vented gas is free of air. 
The point of discharge shall not be left unattended during 
purging. After purging, the vent shall then be closed. 

G2417.7.3 (406.7.3) Discharge of purged gases. The open 
end of piping systems being purged shall not discharge into 
confined spaces or areas where there are sources of ignition 
unless precautions are taken to perform this operation in a 
safe manner by ventilation of the space, control or purging 
rate, and elimination of all hazardous conditions. 

G2417.7.4 (406.7.4) Placing appliances and equipment 
in operation. After the piping system has been placed in 
operation, all appliances and equipment shall be purged and 
then placed in operation, as necessary. 



SECTION G241 8 (407) 
PIPING SUPPORT 

G2418.1 (407.1) General. Piping shall be provided with sup- 
port in accordance with Section G2418.2. 

G2418.2 (407.2) Design and installation. Piping shall be sup- 
ported with pipe hooks, metal pipe straps, bands, brackets or 
hangers suitable for the size of piping, of adequate strength and 
quality, and located at intervals so as to prevent or damp out 
excessive vibration. Piping shall be anchored to prevent undue 
strains on connected equipment and shall not be supported by 
other piping. Pipe hangers and supports shall conform to the 
requirements of MSS SP-58 and shall be spaced in accordance 
with Section G2424. Supports, hangers, and anchors shall be 
installed so as not to interfere with the free expansion and con- 
traction of the piping between anchors. All parts of the support- 
ing equipment shall be designed and installed so they will not 
be disengaged by movement of the supported piping. 



SECTION G241 9 (408) 
DRIPS AND SLOPED PIPING 

G2419.1 (408.1) Slopes. Piping for other than dry gas condi- 
tions shall be sloped not less than 0.25 inch in 1 5 feet (6.4 mm 
in 4572 mm) to prevent traps. 

G2419.2 (408.2) Drips. Where wet gas exists, a drip shall be 
provided at any point in the line of pipe where condensate 
could collect. A drip shall also be provided at the outlet of the 
meter and shall be installed so as to constitute a trap wherein an 
accumulation of condensate will shut off the flow of gas before 
the condensate will run back into the meter. 

G2419.3 (408.3) Location of drips. Drips shall be provided 
with ready access to permit cleaning or emptying. A drip shall 
not be located where the condensate is subject to freezing. 

G2419.4 (408.4) Sediment trap. Where a sediment trap is not 
incorporated as part of the gas utilization equipment, a sedi- 
ment trap shall be installed downstream of the equipment shut- 
off valve as close to the inlet of the equipment as practical. The 
sediment trap shall be either a tee fitting with a capped nipple in 
the bottom opening of the run of the tee or other device 
approved as an effective sediment trap. Illuminating appli- 



392 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



FUEL GAS 



ances, ranges, clothes dryers and outdoor grills need not be so 
equipped. 



be installed in accordance with the appliance manufac- 
turer's instructions. 



SECTION G2420 (409) 
GAS SHUTOFF VALVES 

G2420.1 (409.1) General. Piping systems shall be provided 
with shutoff valves in accordance with this section. 

G2420.1.1 (409.1.1) Valve approval. Shutoff valves shall 
be of an approved type; shall be constructed of materials 
compatible with the piping; and shall comply with the stan- 
dard that is applicable for the pressure and application, in 
accordance with Table G2420.1.1. 

G2420.1.2 (409.1.2) Prohibited locations. Shutoff valves 
shall be prohibited in concealed locations and furnace ple- 
nums. 

G2420.1.3 (409.1.3) Access to shutoff valves. Shutoff 
valves shall be located in places so as to provide access for 
operation and shall be installed so as to be protected from 
damage. 

G2420.2 (409.2) Meter valve. Every meter shall be equipped 
with a shutoff valve located on the supply side of the meter. 

G2420.3 (409.3.2) Individual buildings. In a common system 
serving more than one building, shutoff valves shall be 
installed outdoors at each building. 

G2420.4 (409.4) MP regulator valves. A listed shutoff valve 
shall be installed immediately ahead of each MP regulator. 

G2420.5 (409.5) Equipment shutoff valve. Each appliance 
shall be provided with a shutoff valve separate from the appli- 
ance. The shutoff valve shall be located in the same room as the 
appliance, not further than 6 feet (1829 mm) from the appli- 
ance, and shall be installed upstream from the union, connector 
or quick disconnect device it serves. Such shutoff valves shall 
be provided with access. 

Exception: Shutoff valves for vented decorative appliances 
and decorative appliances for installation in vented fire- 
places shall not be prohibited from being installed in an area 
remote from the appliance where such valves are provided 
with ready access. Such valves shall be permanently identi- 
fied and shall serve no other equipment. 

G2420.5.1 (409.5.1) Shutoff valve in fireplace. Equip- 
ment shutoff valves located in the firebox of a fireplace shall 



SECTION G2421 (410) 
FLOW CONTROLS 

G2421.1 (410.1) Pressure regulators. A line pressure regula- 
tor shall be installed where the appliance is designed to operate 
at a lower pressure than the supply pressure. Line gas pressure 
regulators shall be listed as complying with ANSI Z21.80. 
Access shall be provided to pressure regulators. Pressure regu- 
lators shall be protected from physical damage. Regulators 
installed on the exterior of the building shall be approved for 
outdoor installation. 

G2421.2 (410.2) MP regulators. MP pressure regulators shall 
comply with the following: 

1 . The MP regulator shall be approved and shall be suitable 
for the inlet and outlet gas pressures for the application. 

2. The MP regulator shall maintain a reduced outlet pres- 
sure under lockup (no-flow) conditions. 

3. The capacity of the MP regulator, determined by pub- 
lished ratings of its manufacturer, shall be adequate to 
supply the appliances served. 

4. The MP pressure regulator shall be provided with access. 
Where located indoors, the regulator shall be vented to 
the outdoors or shall be equipped with a leak-limiting 
device, in either case complying with Section G2421 .3. 

5. A tee fitting with one opening capped or plugged shall be 
installed between the MP regulator and its upstream 
shutoff valve. Such tee fitting shall be positioned to 
allow connection of a pressure measuring instrument 
and to serve as a sediment trap. 

6. A tee fitting with one opening capped or plugged shall be 
installed not less than 10 pipe diameters downstream of 
the MP regulator outlet. Such tee fitting shall be posi- 
tioned to allow connection of a pressure measuring 
instrument. 

G2421.3 (410.3) Venting of regulators. Pressure regulators 
that require a vent shall be vented directiy to the outdoors. The 
vent shall be designed to prevent the entry of insects, water and 
foreign objects. 



TABLE G2420.1.1 
MANUAL GAS VALVE STANDARDS 



VALVE STANDARDS 


APPLIANCE SHUTOFF 

VALVE APPLICATION UP 

TO Vj psig PRESSURE 


OTHER VALVE APPLICATIONS 


UP TO Vj psig 
PRESSURE 


UP TO 2 psig 
PRESSURE 


UP TO 5 psig 
PRESSURE 


UP TO 125 psig 
PRESSURE 


ANSIZ21.15 


X 


— 


— 


— 


— 


CSA Requirement 3-88 


X 


X 


X^ 


Xb 


— 


ASMEB 16.44 


X 


X 


X^ 


x" 





ASMEB 16.33 


X 


X 


X 


X 


X 



For SI: 1 pound per square inch gauge = 6.895 kPa. 

a. If labeled 2G. 

b. If labeled 5G. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



393 



FUEL GAS 



Exception: A vent to the outdoors is not required for regula- 
tors equipped with and labeled for utilization with an 
approved vent-limiting device installed in accordance with 
the manufacturer's instructions. 

G2421.3.1 (410.3.1) Vent piping. Vent piping shall be not 
smaller than the vent connection on the pressure regulating 
device. Vent piping serving relief vents and combination 
relief and breather vents shall be run independently to the 
outdoors and shall serve only a single device vent. Vent pip- 
ing serving only breather vents is permitted to be connected 
in a manifold arrangement where sized in accordance with 
an approved design that minimizes back pressure in the 
event of diaphragm rupture. 



SECTION G2422 (411) 
APPLIANCE CONNECTIONS 

G2422.1 (411.1) Connecting appliances. Apphances shall be 
connected to the piping system by one of the following: 

1. Rigid metallic pipe and fittings. 

2. Corrugated stainless steel tubing (CSST) where installed 
in accordance with the manufacturer's instructions. 

3. Listed and labeled appliance connectors in compliance 
with ANSI Z21.24 and installed in accordance with the 
manufacturer's installation instructions and located 
entirely in the same room as the appliance. 

4. Listed and labeled quick-disconnect devices used in con- 
junction with listed and labeled appliance connectors. 

5. Listed and labeled convenience outlets used in conjunc- 
tion with listed and labeled appliance connectors. 

6. Listed and labeled outdoor appliance connectors in com- 
pliance with ANSI Z2L75/CSA 6.27 and installed in 
accordance with the manufacturer's installation instruc- 
tions. 

G2422.1.1 (411.1.2) Protection from damage. Connec- 
tors and tubing shall be installed so as to be protected against 
physical damage. 

G2422.1.2 (411.1.3) Connector installation. Appliance 
fuel connectors shall be installed in accordance with the 
manufacturer's instructions and Sections G2422 1.2.1 
through G2422. 1.2.4. 

G2422.1.2.1 (411.1.3.1) Maximum length. Connectors 
shall have an overall length not to exceed 3 feet (914 
mm), except for range and domestic clothes dryer con- 
nectors, which shall not exceed 6 feet (1 829 mm) in over- 
all length. Measurement shall be made along the 
centerline of the connector. Only one connector shall be 
used for each appliance. 

Exception: Rigid metallic piping used to connect an 
appliance to the piping system shall be permitted to 
have a total length greater than 3 feet (914 mm), pro- 
vided that the connecting pipe is sized as part of the 
piping system in accordance with Section 024 13 and 
the location of the equipment shutoff valve complies 
with Section O2420.5. 



G2422. 1.2.2 (411.1.3.2) Minimum size. Connectors 
shall have the capacity for the total demand of the con- 
nected appliance. 

G2422.1.2.3 (411.1.3.3) Prohibited locations and pen- 
etrations. Connectors shall not be concealed within, or 
extended through, walls, floors, partitions, ceilings or 
appliance housings. 

Exception: Fireplace inserts that are factory 
equipped with grommets, sleeves or other means of 
protection in accordance with the listing of the appli- 
ance. 

G2422.1.2.4 (411.1.3.4) Shutoff valve. A shutoff valve 
not less than the nominal size of the connector shall be 
installed ahead of the connector in accordance with Sec- 
tion O2420.5. 

G2422.1.3 (411.1.4) Movable appliances. Where appli- 
ances are equipped with casters or are otherwise subject to 
periodic movement or relocation for purposes such as rou- 
tine cleaning and maintenance, such appliances shall be 
connected to the supply system piping by means of an 
approved flexible connector designed and labeled for the 
application. Such flexible connectors shall be installed and 
protected against physical damage in accordance with the 
manufacturer's installation instructions. 



SECTION 02423(413) 
CNG GAS-DISPENSING SYSTEMS 

G2423.1 (413.1) General. Motor fuel-dispensing facilities for 
CNO fuel shall be in accordance with Section 413 of the Inter- 
national Fuel Gas Code. 



SECTION 02424(415) 
PIPING SUPPORT INTERVALS 

G2424.1 (415.1) Interval of support. Piping shall be sup- 
ported at intervals not exceeding the spacing specified in Table 
02424. 1 . Spacing of supports for CSST shall be in accordance 
with the CSST manufacturer's instructions. 

TABLE G2424.1 
SUPPORT OF PIPING 



STEEL PIPE, 

NOMINAL SIZE 

OF PIPE 

(inches) 


SPACING OF 

SUPPORTS 

(feet) 


NOMINAL SIZE 
OF TUBING 

SMOOTH-WALL 
(inch O.D.) 


SPACING OF 

SUPPORTS 

(feet) 


% 


6 


% 


4 


'U or 1 


8 


%or% 


6 


IV4 or larger 
(horizontal) 


10 


%orl 
(horizontal) 


8 


1 V4 or larger 
(vertical) 


Every floor 
level 


1 or Larger 
(vertical) 


Every floor 
level 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



394 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



FUEL GAS 



SECTION G2425 (501) 
GENERAL 

G2425.1 (501.1) Scope. This section shall govern the installa- 
tion, maintenance, repair and approval of factory-built and 
masonry chimneys, chimney liners, vents and connectors serv- 
ing gas-fired appliances. 

G2425.2 (501.2) General. Every appliance shall discharge the 
products of combustion to the outdoors, except for appliances 
exempted by Section G2425.8. 

G2425.3 (501.3) Masonry chimneys. Masonry chimneys 
shall be constructed in accordance with Section G2427.5 and 
Chapter 10. 

G2425.4 (501.4) Minimum size of chimney or vent. Chim- 
neys and vents shall be sized in accordance with Section 

G2427. 

G2425.5 (501.5) Abandoned inlet openings. Abandoned 
inlet openings in chimneys and vents shall be closed by an 
approved method. 

G2425.6 (501.6) Positive pressure. Where an appliance 
equipped with a mechanical forced draft system creates a posi- 
tive pressure in the venting system, the venting system shall be 
designed for positive pressure applications. 

G2425.7 (501.7) Connection to fireplace. Connection of 
appliances to chimney flues serving fireplaces shall be in 
accordance with Sections G2425.7.1 through G2425.7.3. 

G2425.7.1 (501.7.1) Closure and access. A 

noncombustible seal shall be provided below the point of 
connection to prevent entry of room air into the flue. Means 
shall be provided for access to the flue for inspection and 
cleaning. 

G2425.7.2 (501.7.2) Connection to factory-built fire- 
place flue. An appliance shall not be connected to a flue 
serving a factory-built fireplace unless the appliance is spe- 
cifically listed for such installation. The connection shall be 
made in accordance with the appliance manufacturer's 
installation instructions. 

G2425.7.3 (501.7.3) Connection to masonry fireplace 
flue. A connector shall extend from the appliance to the flue 
serving a masonry fireplace such that the flue gases are 
exhausted directly into the flue. The connector shall be 
accessible or removable for inspection and cleaning of both 
the connector and the flue. Listed direct connection devices 
shall be installed in accordance with their listing. 

G2425.8 (501.8) Equipment not required to be vented. The 

following appliances shall not be required to be vented: 

1. Ranges. 

2. Built-in domestic cooking units listed and marked for 
optional venting. 

3. Hot plates and laundry stoves. 

4. Type 1 clothes dryers (Type 1 clothes dryers shall be 
exhausted in accordance with the requirements of Sec- 
tion G2439). 

5. Refrigerators. 

6. Counter appliances. 



7. Room heaters listed for unvented use. 

Where the appliances and equipment listed in Items 5 
through 7 above are installed so that the aggregate input rating 
exceeds 20 Btu per hour per cubic foot (207 watts per m^) of 
volume of the room or space in which such appliances and 
equipment are installed, one or more shall be provided with 
venting systems or other approved means for conveying the 
vent gases to the outdoor atmosphere so that the aggregate 
input rating of the remaining unvented appliances and equip- 
ment does not exceed the 20 Btu per hour per cubic foot (207 
watts per m^) figure. Where the room or space in which the 
equipment is installed is directiy connected to another room or 
space by a doorway, archway or other opening of comparable 
size that cannot be closed, the volume of such adjacent room or 
space shall be permitted to be included in the calculations. 

G2425.9 (501.9) Chimney entrance. Connectors shall con- 
nect to a masonry chimney flue at a point not less than 12 inches 
(305 mm) above the lowest portion of the interior of the chim- 
ney flue. 

G2425.10 (501.10) Connections to exhauster. Appliance 
connections to a chimney or vent equipped with a power 
exhauster shall be made on the inlet side of the exhauster. Joints 
on the positive pressure side of the exhauster shall be sealed to 
prevent flue-gas leakage as specified by the manufacturer's 
installation instructions for the exhauster. 

G2425.il (501.11) Masonry chimneys. Masonry chimneys 
utilized to vent appliances shall be located, constructed and 
sized as specified in the manufacturer's installation instruc- 
tions for the appliances being vented and Section G2427. 

G2425.12 (501.12) Residential and low-heat appliances flue 
lining systems. Flue lining systems for use with residen- 
tial-type and low-heat appliances shall be limited to the follow- 
ing: 

1. Clay flue lining complying with the requirements of 
ASTM C 315 or equivalent. Clay flue lining shall be 
installed in accordance with Chapter 10. 

2. Listed chimney lining systems complying with UL 1777. 

3. Other approved materials that will resist, without crack- 
ing, softening or corrosion, flue gases and condensate at 
temperatures up to 1,800°F (982°C). 

G2425.13 (501.13) Category I appliance flue lining systems. 

Flue lining systems for use with Category I appliances shall be 
limited to the following: 

1. Flue lining systems complying with Section G2425.12. 

2. Chimney lining systems listed and labeled for use with 
appliances with draft hoods and other Category I gas 
appliances listed and labeled for use with Type B vents. 

G2425.14 (501.14) Category II, III and IV appUance vent- 
ing systems. The design, sizing and installation of vents for 
Category II, III and IV appliances shall be in accordance with 
the appliance manufacturer's installation instructions. 

G2425.15 (501.15) Existing chimneys and vents. Where an 
appliance is permanently disconnected from an existing chim- 
ney or vent, or where an appliance is connected to an existing 
chimney or vent during the process of a new installation, the 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



395 



FUEL GAS 



chimney or vent shall comply with Sections G2425.15.1 
through G2425. 15.4. 

G2425.15.1 (501.15.1) Size. The chimney or vent shall be 
resized as necessary to control flue gas condensation in the 
interior of the chimney or vent and to provide the appliance 
or appliances served with the required draft. For Category I 
appliances, the resizing shall be in accordance with Section 
G2426. 

G2425.15.2 (501.15.2) Flue passageways. The flue gas 
passageway shall be free of obstructions and combustible 
deposits and shall be cleaned if previously used for venting a 
solid or liquid fuel-burning appliance or fireplace. The flue 
liner, chimney inner wall or vent inner wall shall be continu- 
ous and shall be free of cracks, gaps, perforations, or other 
damage or deterioration that would allow the escape of 
combustion products, including gases, moisture and creo- 
sote. 

G2425.15.3 (501.15.3) Cleanout. Masonry chimney flues 
shall be provided with a cleanout opening having a mini- 
mum height of 6 inches (152 mm). The upper edge of the 
opening shall be located not less than 6 inches (152 mm) 
below the lowest chimney inlet opening. The cleanout shall 
be provided with a tight-fitting, noncombustible cover. 

G2425.15.4 (501.15.4) Clearances. Chimneys and vents 
shall have airspace clearance to combustibles in accordance 
with Chapter 10 and the chimney or vent manufacturer's 
installation instructions. Noncombustible firestopping or 
fireblocking shall be provided in accordance with Chapter 
10. 

Exception: Masonry chimneys equipped with a chim- 
ney lining system tested and listed for installation in 
chimneys in contact with combustibles in accordance 
with UL 1777, and installed in accordance with the man- 
ufacturer's instructions, shall not be required to have 
clearance between combustible materials and exterior 
surfaces of the masonry chimney. 



SECTION G2426 (502) 
VENTS 

G2426.1 (502.1) General. All vents, except as provided in 
Section G2427.7, shall be listed and labeled. Type B and BW 
vents shall be tested in accordance with UL 441. Type L vents 
shall be tested in accordance with UL 641. Vents for Category 
II and III appliances shall be tested in accordance with UL 
1738. Plastic vents for Category IV appHances shall not be 
required to be listed and labeled where such vents are as speci- 
fied by the appliance manufacturer and are installed in accor- 
dance with the appliance manufacturer's installation 
instructions. 

G2426.2 (502.2) Connectors required. Connectors shall be 
used to connect appliances to the vertical chimney or vent, 
except where the chimney or vent is attached directly to the 
appliance. Vent connector size, material, construction and 
installation shall be in accordance with Section G2427. 

G2426.3 (502.3) Vent application. The appHcation of vents 
shall be in accordance with Table G2427.4. 



G2426.4 (502.4) Insulation shield. Where vents pass through 
insulated assemblies, an insulation shield constructed of not 
less than 26 gage sheet (0.016 inch) (0.4 mm) metal shall be 
installed to provide clearance between the vent and the insula- 
tion material. The clearance shall not be less than the clearance 
to combustibles specified by the vent manufacmrer's installa- 
tion instructions. Where vents pass through attic space, the 
shield shall terminate not less than 2 inches (5 1 mm) above the 
insulation materials and shall be secured in place to prevent dis- 
placement. Insulation shields provided as part of a listed vent 
system shall be installed in accordance with the manufacturer's 
installation instructions. 

G2426.5 (502.5) Installation. Vent systems shall be sized, 
installed and terminated in accordance with the vent and appli- 
ance manufacturer's installation instructions and Section 

G2427. 

G2426.6 (502.6) Support of vents. All portions of vents shall 
be adequately supported for the design and weight of the mate- 
rials employed. 

G2426.7 (502.7) Protection against physical damage. In 

concealed locations, where a vent is installed through holes or 
notches in studs, joists, rafters or similar members less than 1 .5 
inches (38 mm) from the nearest edge of the member, the vent 
shall be protected by shield plates. Shield plates shall be a mini- 
mum of Vi6-inch-thick (1.6 mm) steel, shall cover the area of 
the vent where the member is notched or bored and shall extend 
a minimum of 4 inches (102 mm) above sole plates, below top 
plates and to each side of a stud, joist or rafter. 



SECTION G2427 (503) 
VENTING OF EQUIPMENT 

G2427.1 (503.1) General. This section recognizes that the 
choice of venting materials and the methods of installation of 
venting systems are dependent on the operating characteristics 
of the appliance being vented. The operating characteristics of I 
vented appliances can be categorized with respect to: (1) posi- I 
tive or negative pressure within the venting system; and (2) 
whether or not the appliance generates flue or vent gases that 
might condense in the venting system. See Section G2403 for 
the definitions of these vented appliance categories. 

G2427.2 (503.2) Venting systems required. Except as per- 
mitted in Sections G2427.2.1, G2427.2.2 and G2425.8, all 
appliances shall be connected to venting systems. I 

G2427.2.1 (503.2.3) Direct-vent appliances. Listed 
direct- vent apphances shall be installed in accordance with | 
the manufacturer's instructions and Section G2427.8, Item 3. 

G2427.2.2 (503.2.4) Apphances with integral vents. 

Appliances incorporating integral venting means shall be | 
considered properly vented where installed in accordance 
with the manufacturer's instructions and Section G2427.8, I 
Items 1 and 2. 

G2427.3 (503.3) Design and construction. A venting system 
shall be designed and constructed so as to develop a positive 
flow adequate to convey flue or vent gases to the outdoors. ■ 

G2427.3.1 (503.3.1) Appliance draft requirements. A 

venting system shall satisfy the draft requirements of the 



396 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



FUEL GAS 



appliance in accordance with the manufacturer's instruc- 
tions. 

G2427.3.2 (503.3.2) Design and construction. Appliances 
required to be vented shall be connected to a venting system 
designed and installed in accordance with the provisions of 
Sections G2427.4 through G2427.15. 

G2427.3.3 (503.3.3) Mechanical draft systems. Mechani- 
cal draft systems shall comply with the following: 

1. Mechanical draft systems shall be hsted and shall be 
installed in accordance with the manufacturer's 
installation instructions for both the appliance and the 
mechanical draft system. 

2. Appliances, except incinerators, requiring venting 
shall be permitted to be vented by means of mechani- 
cal draft systems of either forced or induced draft 
design. 

3. Forced draft systems and all portions of induced draft 
systems under positive pressure during operation 
shall be designed and installed so as to prevent leak- 
age of flue or vent gases into a building. 

4. Vent connectors serving appliances vented by natural 
draft shall not be connected into any portion of 
mechanical draft systems operating under positive 
pressure. 

5. Where a mechanical draft system is employed, provi- 
sions shall be made to prevent the flow of gas to the 
main burners when the draft system is not performing 
so as to satisfy the operating requirements of the 
appliance for safe performance. 

6. The exit terminals of mechanical draft systems shall 
be not less than 7 feet (2134 mm) above grade where 



located adjacent to public walkways and shall be 
located as specified in Section 503.8, Items 1 and 2. 

G2427.3.4 (503.3.5) Circulating air ducts and furnace 
plenums. No portion of a venting system shall extend into 
or pass through any circulating air duct or furnace plenum. 

G2427.3.5 (503.3.6) Above-ceiling air-handling spaces. 

Where a venting system passes through an above-ceiling 
air-handling space or other nonducted portion of an air-han- 
dling system, the venting system shall conform to one of the 
following requirements: 

1. The venting system shall be a listed special gas vent; 
other venting system serving a Category III or Cate- 
gory IV appliance; or other positive pressure vent, 
with joints sealed in accordance with the appliance or 
vent manufacturer's instructions. 

2. The venting system shall be installed such that fittings 
and joints between sections are not installed in the 
above-ceiling space. 

3. The venting system shall be installed in a conduit or 
enclosure with sealed joints separating the interior of 
the conduit or enclosure from the ceiling space. 

G2427.4 (503.4) Type of venting system to be used. The type 
of venting system to be used shall be in accordance with Table 

G2427.4. 

G2427.4.1 (503.4.1) Plastic piping. Plastic piping used for 
venting appliances listed for use with such venting materials I 
shall be approved. 

G2427.4.2 (503.4.2) Special gas vent. Special gas vent 
shall be listed and installed in accordance with the special 
gas vent manufacturer's installation instructions. | 



TABLE G2427.4 
TYPE OF VENTING SYSTEM TO BE USED 



APPLIANCES 


TYPE OF VENTING SYSTEM 


Listed Category I appliances 

Listed appliances equipped with draft hood 

Appliances listed for use with Type B gas vent 


Type B gas vent (Section G2427.6) 

Chimney (Section G2427.5) 

Single-wall metal pipe (Section G2427.7) 

Listed chimney lining system for gas venting (Section G2427.5.2) 

Special gas vent listed for these appliances (Section G2427.4.2) 


Listed vented wall furnaces 


Type B-W gas vent (Secrions G2427.6, G2436) 


Category II appliances 


As specified or furnished by manufacturers of listed appliances 
(Sections G2427.4.1, G2427.4.2) 


Category III appliances 


As specified or furnished by manufacturers of listed appliances 
(Sections G2427.4.1, G2427.4.2) 


Category IV appliances 


As specified or furnished by manufacturers of listed appliances 
(Sections G2427.4.L G2427.4.2) 


Unlisted appliances 


Chimney (Section G2427.5) 


Decorative appliances in vented fireplaces 


Chimney 


Direct- vent appliances 


See Section G2427. 2.1 


Appliances with integral vent 


See Section G2427.2.2 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



397 



FUEL GAS 



G2427.5 (503.5) Masonry, metal, and factory-built chim- 
neys. Masonry, metal and factory-built chimneys shall comply 
with Sections G2427.5.1 through G2427.5.9. 

G2427.5.1 (503.5.1) Factory-built chimneys. Fac- 
tory-built chimneys shall be installed in accordance with the 
manufacturer's installation instructions. Factory-built 
chimneys used to vent appliances that operate at a positive 
vent pressure shall be listed for such application. 

G2427.5.2 (503.5.3) Masonry chimneys. Masonry chim- 
neys shall be built and installed in accordance with NFPA 
211 and shall be lined with approved clay flue lining, a listed 
chimney lining system or other approved material that will 
resist corrosion, erosion, softening or cracking from vent 
gases at temperatures up to 1,800°F (982°C). 

Exception: Masonry chimney flues serving listed gas 
appliances with draft hoods, Category I appliances and 
other gas appliances listed for use with Type B vents shall 
be permitted to be lined with a chimney Hning system 
specifically listed for use only with such appliances. The 
liner shall be installed in accordance with the liner manu- 
facturer's installation instructions. A permanent identi- 
fying label shall be attached at the point where the 



connection is to be made to the liner. The label shall read: 
"This chimney liner is for appliances that burn gas only. 
Do not connect to solid or liquid fuel-burning appliances 
or incinerators." 

G2427.5.3 (503.5.4) Chimney termination. Chimneys for 
residential-type or low-heat appliances shall extend at least 
3 feet (914 mm) above the highest point where they pass 
through a roof of a building and at least 2 feet (610 mm) 
higher than any portion of a building within a horizontal dis- 
tance of 10 feet (3048 mm) (see Figure G2427.5.3). Chim- 
neys for medium-heat appliances shall extend at least 10 
feet (3048 mm) higher than any portion of any building 
within 25 feet (7620 mm). Chimneys shall extend at least 5 
feet (1524 mm) above the highest connected appliance draft 
hood outlet or flue collar. Decorative shrouds shall not be 
installed at the termination of factory-built chimneys except 
where such shrouds are listed and labeled for use with the 
specific factory-built chimney system and are installed in 
accordance with the manufacturer's installation instruc- 
tions. 

G2427.5.4 (503.5.5) Size of chimneys. The effective area 
of a chimney venting system serving listed appliances with 



10 FT OR LESS 



2 FT 

min; 



-La 

CHIMNEY 



2 FT MIN. 



WALL OR 
PARAPET 



3 FT MIN. 

ir 



JLJL 

CHIMNEY 



MORE THAN 
10 FT 



„Jf 



SEE NOTE a 



WALL OR 
PARAPET _|L\J_ 

CHIMNEY 



3 FT 
MIN. 



10 FT OR LESS 



RIDGE 



3 FT MIN. 





-Lvl 

CHIMNEY 

A. TERMINATION 10 FT OR LESS 
FROM RIDGE, WALL OR PARAPET 

CHIMNEY 

B. TERMINATION MORE THAN 10 FT 
FROM RIDGE, WALL OR PARAPET 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 
NOTES: 

a. No height above parapet required when distance from walls or parapet is more than 10 feet. 

b. Height above any roof surface within 10 feet horizontally. 

FIGURE G2427.5.3 (503.5.4) 
TYPICAL TERMINATION LOCATIONS FOR CHIMNEYS AND SINGLE-WALL METAL PIPES 



398 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FUEL GAS 



draft hoods, Category I appliances, and other appliances 
listed for use with Type B vents shall be determined in 
accordance with one of the following methods: 

1. The provisions of Section G2428. 

2. For sizing an individual chimney venting system for a 
single appliance with a draft hood, the effective areas 
of the vent connector and chimney flue shall be not 
less than the area of the appliance flue collar or draft 
hood outlet, nor greater than seven times the draft 
hood outlet area. 

3. For sizing a chimney venting system connected to 
two appliances with draft hoods, the effective area of 
the chimney flue shall be not less than the area of the 
larger draft hood outlet plus 50 percent of the area of 
the smaller draft hood outlet, nor greater than seven 
times the smallest draft hood outlet area. 

4. Chimney venting systems using mechanical draft 
shall be sized in accordance with approved engineer- 
ing methods. 

5. Other approved engineering methods. 

G2427.5.5 (503.5.6) Inspection of chimneys. Before 
replacing an existing appliance or connecting a vent con- 
nector to a chimney, the chimney passageway shall be 
examined to ascertain that it is clear and free of obstructions 
and it shall be cleaned if previously used for venting solid or 
liquid fuel-burning appliances or fireplaces. 

G2427.5.5.1 (503.5.6.1) Chimney Uning. Chimneys 
shall be lined in accordance with Chapter 10. 

Exception: Existing chimneys shall be permitted to 
have their use continued when an appliance is 
replaced by an appliance of similar type, input rating 
and efficiency. 

G2427.5.5.2 (503.5.6.2) Cleanouts. Cleanouts shall be 
examined to determine they will remain tightly closed 
when not in use. 

G2427.5.5.3 (503.5.6.3) Unsafe chimneys. Where 
inspection reveals that an existing chimney is not safe for 
the intended application, it shall be repaired, rebuilt, 
lined, relined or replaced with a vent or chimney to con- 
form to NFPA 211 and it shall be suitable for the appli- 
ances to be vented. 

G2427.5.6 (503.5.7) Chimneys serving equipment burn- 
ing other fuels. Chimneys serving equipment burning other 
fuels shall comply with Sections G2427.5.6.1 through 
G2427.5.6.4. 

G2427.5.6.1 (503.5.7.1) Solid fuel-burning appli- 
ances. An appliance shall not be connected to a chimney 
flue serving a separate appliance designed to burn solid 
fuel. 

G2427.5.6.2 (503.5.7.2) Liquid fuel-burning appli- 
ances. Where one chimney flue serves gas appliances 
and liquid fuel-burning appliances, the appliances shall 
be connected through separate openings or shall be con- 
nected through a single opening where joined by a suit- 
able fitting located as close as practical to the chimney. 



Where two or more openings are provided into one 
chimney flue, they shall be at different levels. Where the 
appliances are automatically controlled, they shall be 
equipped with safety shutoff devices. 

G2427.5.6.3 (503.5.7.3) Combination gas- and solid 
fuel-burning appliances. A combination gas- and solid 
fuel-burning appliance equipped with a manual reset 
device to shut off gas to the main burner in the event of 
sustained backdraft or flue gas spillage shall be permit- 
ted to be connected to a single chimney flue. The chim- 
ney flue shall be sized to properly vent the appliance. 

G2427.5.6.4 (503.5.7.4) Combination gas- and oil 
fuel-burning appliances. A listed combination gas- and 
oil fuel-burning apphance shall be permitted to be con- 
nected to a single chimney flue. The chimney flue shall 
be sized to properly vent the appliance. 

G2427.5.7 (503.5.8) Support of chimneys. All portions of 
chimneys shall be supported for the design and weight of the 
materials employed. Factory-built chimneys shall be sup- 
ported and spaced in accordance with the manufacturer's 
installation instructions. 

G2427.5.8 (503.5.9) Cleanouts. Where a chimney that for- 
merly carried flue products from liquid or solid fuel-burn- 
ing appliances is used with an appliance using fuel gas, an 
accessible cleanout shall be provided. The cleanout shall 
have a tight-fitting cover and be installed so its upper edge is 
at least 6 inches (152 mm) below the lower edge of the low- 
est chimney inlet opening. 

G2427.5.9 (503.5.10) Space surrounding lining or vent. 

The remaining space surrounding a chimney liner, gas vent, 
special gas vent or plastic piping installed within a masonry 
chimney flue shall not be used to vent another appliance. 
The insertion of another liner or vent within the chinmey as 
provided in this code and the liner or vent manufacturer's 
instructions shall not be prohibited. 

The remaining space surrounding a chimney liner, gas 
vent, special gas vent or plastic piping installed within a 
masonry, metal or factory -built chimney shall not be used to 
supply combustion air. Such space shall not be prohibited 
from supplying combustion air to direct-vent appliances 
designed for installation in a solid fuel-burning fireplace 
and installed in accordance with the manufacturer's installa- 
tion instructions. 

G2427.6 (503.6) Gas vents. Gas vents shall comply with Sec- 
tions G2427.6.1 through G2427.6.10. (See Section G2403, 
Definitions.) 

G2427.6.1 (503.6.1) Installation, general. Gas vents shall 
be installed in accordance with the terms of their listings and 
the manufacturer's instructions. 

G2427.6.2 (503.6.2) Type B-W vent capacity. A Type 
B-W gas vent shall have a listed capacity not less than that of 
the listed vented wall furnace to which it is connected. 

G2427.6.3 (503.6.4) Gas vent termination. A gas vent 
shall terminate in accordance with one of the following: 

1. Gas vents that are 12 inches (305 mm) or less in size 
and located not less than 8 feet (2438 mm) from a ver- 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



399 



FUEL GAS 



tical wall or similar obstruction shall terminate above 
the roof in accordance with Figure G2427.6.3. 

2. Gas vents that are over 12 inches (305 mm) in size or 
are located less than 8 feet (2438 mm) from a vertical 
wall or similar obstruction shall terminate not less 
than 2 feet (610 mm) above the highest point where 
they pass through the roof and not less than 2 feet (610 
mm) above any portion of a building within 10 feet 
(3048 mm) horizontally. 

3. As provided for direct- vent systems in Section 
G2427.2.1. 

4. As provided for appliances with integral vents in Sec- 
tion G2427.2.2. 



5. As provided for mechanical draft systems in Section 

G2427.3.3. 

G2427.6.3.1 (503.6.4.1) Decorative shrouds. Decora- 
tive shrouds shall not be installed at the termination of 
gas vents except where such shrouds are listed for use 
with the specific gas venting system and are installed in 
accordance with manufacturer's installation instruc- 
tions. 

G2427.6.4 (503.6.5) Minimum height. A Type B or L gas 
vent shall terminate at least 5 feet (1524 mm) in vertical 
height above the highest connected appliance draft hood or 
flue collar. A Type B-W gas vent shall terminate at least 12 
feet (3658 mm) in vertical height above the bottom of the 
wall furnace. 



LOWEST DISCHARGE 
OPENING 

LISTED CAP -i I 

T IT 



LISTED GAS 
VENT 




H (MIN.) - 

MINIMUM HEIGHT FROM ROOF 

TO LOWEST DISCHARGE OPENING 



ROOF SLOPE 


H (minimum) ft 


Flat to V,2 


1.0 


Over *5/i2 to V^2 


1.25 


Over ^/i2 to ^/i2 


1.5 


Over «/,2 to Vn 


2.0 


Over 9/i2 to "^/i2 


2.5 


Over i%2 to "/i2 


3.25 


OveriVi2to'2/i2 


4.0 


Over '2/i2 to 14/, 2 


5.0 


Over '4/i2 to »6/,2 


6.0 


Over i«/i2 to i^/i2 


7.0 


Over iV,2 to 20/,2 


7.5 


Over2%2to2V,2 


8.0 



For SI: 1 foot = 304.8 mm. 



FIGURE G2427.6.3 (503.6.4) 

GAS VENT TERMINATION LOCATIONS FOR LISTED CAPS 12 INCHES 

OR LESS IN SIZE AT LEAST 8 FEET FROM A VERTICAL WALL 



400 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



FUEL GAS 



G2427.6.5 (503.6.6) Roof terminations. Gas vents shall 
extend through the roof flashing, roof jack or roof thimble 
and terminate with a listed cap or listed roof assembly. 

G2427.6.6 (503.6.7) Forced air inlets. Gas vents shall ter- 
minate not less than 3 feet (914 mm) above any forced air 
inlet located within 10 feet (3048 mm). 

G2427.6.7 (503.6.8) Exterior wall penetrations. A gas 

vent extending through an exterior wall shall not terminate 
adjacent to the wall or below eaves or parapets, except as 
provided in Sections G2427.2.1 and G2427.3.3. 

G2427.6.8 (503.6.9) Size of gas vents. Venting systems 
shall be sized and constructed in accordance with Section 
G2428 or other approved engineering methods and the gas 
vent and appliance manufacturer's installation instructions. 

G2427.6.8.1 (503.6.9.1) Category I appliances. The 

sizing of natural draft venting systems serving one or 
more listed appliances equipped with a draft hood or 
appliances listed for use with Type B gas vent, installed 
in a single story of a building, shall be in accordance with 
one of the following methods: 

1. The provisions of Section G2428. 

2. For sizing an individual gas vent for a single, 
draft-hood-equipped appliance, the effective area 
of the vent connector and the gas vent shall be not 
less than the area of the appliance draft hood outlet, 
nor greater than seven times the draft hood outlet 
area. 

3. For sizing a gas vent connected to two appliances 
with draft hoods, the effective area of the vent shall 
be not less than the area of the larger draft hood 
outlet plus 50 percent of the area of the smaller 
draft hood outlet, nor greater than seven times the 
smaller draft hood outlet area. 

4. Approved engineering practices. 

G2427.6.8.2 (503.6.9.2) Vent offsets. Type B and L 
vents sized in accordance with Item 2 or 3 of Section 
G2427.6.8. 1 shall extend in a generally vertical direction 
with offsets not exceeding 45 degrees (0.79 rad), except 
that a vent system having not more than one 60-degree 
(1.04 rad) offset shall be permitted. Any angle greater 
than 45 degrees (0.79 rad) from the vertical is considered 
horizontal. The total horizontal distance of a vent plus 
the horizontal vent connector serving draft 
hood-equipped appliances shall be not greater than 75 
percent of the vertical height of the vent. 

G2427.6.8.3 (503.6.9.3) Category II, III and IV appli- 
ances. The sizing of gas vents for Category II, III and IV 
appliances shall be in accordance with the appliance 
manufacturer's instructions. 

G2427.6.8.4 (503.6.9.4) Mechanical draft. Chimney 
venting systems using mechanical draft shall be sized in 
accordance with approved engineering methods. 



G2427.6.9 (503.6.11) Support of gas vents. Gas vents 
shall be supported and spaced in accordance with the manu- 
facturer's installation instructions. 

G2427.6.10 (503.6.12) Marking. In those localities where 
solid and liquid fuels are used extensively, gas vents shall be 
permanently identified by a label attached to the wall or ceil- 
ing at a point where the vent connector enters the gas vent. 
The determination of where such localities exist shall be 
made by the code official. The label shall read: 

"This gas vent is for appliances that bum gas. Do not con- 
nect to solid or liquid fuel-burning appliances or incinera- 
tors." 

G2427.7 (503.7) Single-wall metal pipe. Single-wall metal 
pipe vents shall comply with Sections G2427.7.1 through 
G2427.7.12. 

G2427.7.1 (503.7.1) Construction. Single-wall metal pipe 
shall be constructed of galvanized sheet steel not less than 
0.0304 inch (0.7 mm) thick, or other approved, 
noncombustible, corrosion-resistant material. 

G2427.7.2 (503.7.2) Cold climate. Uninsulated sin- 
gle-wall metal pipe shall not be used outdoors for venting 
appliances in regions where the 99-percent winter design 
temperature is below 32°F (0°C). 

G2427.7.3 (503.7.3) Termination. Single-wall metal pipe 
shall terminate at least 5 feet (1524 mm) in vertical height 
above the highest connected appliance draft hood outlet or 
flue collar. Single- wall metal pipe shall extend at least 2 feet 
(610 mm) above the highest point where it passes through a 
roof of a building and at least 2 feet (610 mm) higher than 
any portion of a building within a horizontal distance of 10 
feet (3048 mm) (see Figure G2427.6.4). An approved cap or 
roof assembly shall be attached to the terminus of a sin- 
gle-wall metal pipe (see also Section G2427.7.8, Item 3). 

G2427.7.4 (503.7.4) Limitations of use. Single-wall metal 
pipe shall be used only for runs directly from the space in 
which the appliance is located through the roof or exterior 
wall to the outdoor atmosphere. 

G2427.7.5 (503.7.5) Roof penetrations. A pipe passing 
through a roof shall extend without interruption through the 
roof flashing, roof jack, or roof thimble. Where a sin- 
gle-wall metal pipe passes through a roof constructed of 
combustible material, a noncombustible, nonventilating 
thimble shall be used at the point of passage. The thimble 
shall extend at least 18 inches (457 mm) above and 6 inches 
(152 mm) below the roof with the annular space open at the 
bottom and closed only at the top. The thimble shall be sized 
in accordance with Section G2427.10.15. 

G2427.7.6 (503.7.6) Installation. Single-wall metal pipe 
shall not originate in any unoccupied attic or concealed 
space and shall not pass through any attic, inside wall, con- 
cealed space, or floor. The installation of a single- wall metal 
pipe through an exterior combustible wall shall comply with 
Section G2427. 10. 15 . Single- wall metal pipe used for vent- 
ing an incinerator shall be exposed and readily examinable 
for its full length and shall have suitable clearances main- 
tained. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



401 



FUEL GAS 



G2427.7.7 (503.7.7) Clearances. Minimum clearances 
from single-wall metal pipe to combustible material shall be 
in accordance with Table G2427.7.7. The clearance from 
single- wall metal pipe to combustible material shall be per- 
mitted to be reduced where the combustible material is pro- 
tected as specified for vent connectors in Table G2409.2. 

G2427.7.8 (503.7.8) Size of single-wall metal pipe. A 

venting system constructed of single- wall metal pipe shall 
be sized in accordance with one of the following methods 
and the appliance manufacturer's instructions: 

1 . For a draft-hood-equipped appliance, in accordance 
with Section G2428. 

2. For a venting system for a single appliance with a 
draft hood, the areas of the connector and the pipe 
each shall be not less than the area of the appliance 
flue collar or draft hood outlet, whichever is smaller. 
The vent area shall not be greater than seven times the 
draft hood outlet area. 

3. Other approved engineering methods. 

G2427.7.9 (503.7.9) Pipe geometry. Any shaped sin- 
gle-wall metal pipe shall be permitted to be used, provided 
that its equivalent effective area is equal to the effective area 
of the round pipe for which it is substituted, and provided 
that the minimum internal dimension of the pipe is not less 
than 2 inches (51 mm). 

G2427.7.10 (503.7.10) Termination capacity. The vent 
cap or a roof assembly shall have a venting capacity not less 
than that of the pipe to which it is attached. 

G2427.7.11 (503.7.11) Support of single- wall metal pipe. 

All portions of single-wall metal pipe shall be supported for 
the design and weight of the material employed. 

G2427.7.12 (503.7.12) Marking. Single-wall metal pipe 
shall comply with the marking provisions of Section 
G2427.6.11. 



G2427.8 (503.8) Venting system termination location. The 

location of venting system terminations shall comply with the 
following (see Appendix C): 

1. A mechanical draft venting system shall terminate at 
least 3 feet (914 mm) above any forced-air inlet located 
within 10 feet (3048 mm). 

Exceptions: 

1 . This provision shall not apply to the combus- 
tion air intake of a direct- vent appliance. 

2. This provision shall not apply to the separation 
of the integral outdoor air inlet and flue gas dis- 
charge of listed outdoor appliances. 

2. A mechanical draft venting system, excluding 
direct-vent appliances, shall terminate at least 4 feet 
(1219 mm) below, 4 feet (1219 mm) horizontally from, 
or 1 foot (305 mm) above any door, operable window, or 
gravity air inlet into any building. The bottom of the vent 
terminal shall be located at least 12 inches (305 mm) 
above grade. 

3. The vent terminal of a direct- vent appliance with an 
input of 10,000 Btu per hour (3 kW) or less shall be 
located at least 6 inches (152 mm) from any air opening 
into a building, and such an appliance with an input over 
10,000 Btu per hour (3 kW) but not over 50,000 Btu per 
hour (14.7 kW) shall be installed with a 9-inch (230 mm) 
vent termination clearance, and an appliance with an 
input over 50,000 Btu/h (14.7 kW) shall have at least a 
12-inch (305 mm) vent termination clearance. The bot- 
tom of the vent terminal and the air intake shall be 
located at least 12 inches (305 mm) above grade. 

4. Through-the-wall vents for Category II and IV appli- 
ances and noncategorized condensing appliances shall 
not terminate over public walkways or over an area 
where condensate or vapor could create a nuisance or 
hazard or could be detrimental to the operation of regula- 
tors, relief valves, or other equipment. Where local expe- 



TABLE G2427.7.7 (503.8.7)^ 
CLEARANCES FOR CONNECTORS 



APPLIANCE 


MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL 


Listed Type B gas 
vent material 


Listed Type L 
vent material 


Single-wall 
metal pipe 


Factory-built 
chimney sections 


Listed appliances with draft hoods and appliances listed for 
use with Type B gas vents 


As listed 


As listed 


6 inches 


As listed 


Residential boilers and furnaces with listed gas conversion 
burner and with draft hood 


6 inches 


6 inches 


9 inches 


As Usted 


Residential appliances listed for use with Type L vents 


Not permitted 


As listed 


9 inches 


As Usted 


Listed gas-fired toilets 


Not permitted 


As listed 


As Usted 


As listed 


Unlisted residential appliances with draft hood 


Not permitted 


6 inches 


9 inches 


As Usted 


Residential and low-heat appliances other than above 


Not permitted 


9 inches 


18 inches 


As listed 


Medium-heat appliances 


Not permitted 


Not permitted 


36 inches 


As listed 



For SI: 1 inch = 25.4 mm. 

a. These clearances shall apply unless the manufacturer's installation instructions for a listed appliance or connector specify different clearances, in which case the 
listed clearances shall apply. 



402 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



FUEL GAS 



rience indicates that condensate is a problem with 
Category I and III appliances, this provision shall also 
apply. 

G2427.9 (503.9) Condensation drainage. Provisions shall be 
made to collect and dispose of condensate from venting sys- 
tems serving Category II and IV appliances and 
noncategorized condensing appliances in accordance with 
Section 503.8, Item 4. Where local experience indicates that 
condensation is a problem, provision shall be made to drain off 
and dispose of condensate from venting systems serving Cate- 
gory I and III appliances in accordance with Section G2427.8, 
Item 4. 

G2427.10 (503.10) Vent connectors for Category I equip- 
ment. Vent connectors for Category I equipment shall comply 
with Sections G2427.10.1 through G2427.10.15. 

G2427.10.1 (503.10.1) Where required. A vent connector 
shall be used to connect an appliance to a gas vent, chimney 
or single- wall metal pipe, except where the gas vent, chim- 
ney or single-wall metal pipe is directly connected to the 
appliance. 

G2427.10.2 (503.10.2) Materials. Vent connectors shall be 
constructed in accordance with Sections G2427.10.1 
through G2427. 10.2.5. 

G2427.10.2.1 (503.10.2.1) General. A vent connector 
shall be made of noncombustible corrosion-resistant 
material capable of withstanding the vent gas tempera- 
ture produced by the appliance and of sufficient thick- 
ness to withstand physical damage. 

G2427.10.2.2 (503.10.2.2) Vent connectors located in 
unconditioned areas. Where the vent connector used 
for an appliance having a draft hood or a Category I 
appliance is located in or passes through attics, crawl 
spaces or other unconditioned spaces, that portion of the 
vent connector shall be listed Type B, Type L or listed 
vent material having equivalent insulation properties. 

Exception: Single-wall metal pipe located within the 
exterior walls of the building in areas having a local 
99-percent winter design temperature of 5°F (-15°C) 
or higher shall be permitted to be used in uncondi- 
tioned spaces other than attics and crawl spaces. 

G2427.10.2.3 (503.10.2.3) Residential-type appliance 
connectors. Where vent connectors for residential-type 
appliances are not installed in attics or other uncondi- 
tioned spaces, connectors for listed appliances having 
draft hoods, appliances having draft hoods and equipped 
with listed conversion burners and Category I appliances 
shall be one of the following: 

1. Type B or L vent material; 

2. Galvanized sheet steel not less than 0.018 inch 
(0.46 mm) thick; 

3. Aluminum (1100 or 3003 alloy or equivalent) 
sheet not less than 0.027 inch (0.69 mm) thick; 

4. Stainless steel sheet not less than 0.012 inch (0.31 
mm) thick; 



5. Smooth interior wall metal pipe having resistance 
to heat and corrosion equal to or greater than that 
of Item 2, 3 or 4 above; or 

6. A listed vent connector. 

Vent connectors shall not be covered with insulation. 

Exception: Listed insulated vent connectors shall be 
installed according to the terms of their listing. 

G2427.10.2.4 (503.10.2.4) Low-heat equipment. A 

vent connector for a nonresidential, low-heat appliance 
shall be a factory-built chimney section or steel pipe hav- 
ing resistance to heat and corrosion equivalent to that for 
the appropriate galvanized pipe as specified in Table 
G2427. 10.2.4. Factory-built chimney sections shall be 
joined together in accordance with the chimney manu- 
facturer's instructions. 

TABLE G2427.1 0.2.4 (503.10.2.4) 

MINIMUM THICKNESS FOR GALVANIZED STEEL VENT 

CONNECTORS FOR LOW-HEAT APPLIANCES 



DIAMETER OF CONNECTOR 
(inches) 


MINIMUM THICKNESS 
(inch) 


Less than 6 


0.019 


6 to less than 10 


0.023 


10 to 12 inclusive 


0.029 


14 to 16 inclusive 


0.034 


Over 16 


0.056 



For SI: 1 inch = 25.4 mm. 

G2427.10.3 (503.10.3) Size of vent connector. Vent con- 
nectors shall be sized in accordance with Sections 
G2427.10.3.1 through G2427.3.5. 

G2427.10.3.1 (503.10.3.1) Single draft hood and 
fan-assisted. A vent connector for an appliance with a 
single draft hood or for a Category I fan-assisted com- 
bustion system appliance shall be sized and installed in 
accordance with Section G2428 or other approved engi- 
neering methods. 

G2427.10.3.2 (503.10.3.2) Multiple draft hood. For a 

single appliance having more than one draft hood outlet 
or flue collar, the manifold shall be constructed accord- 
ing to the instructions of the appliance manufacturer. 
Where there are no instructions, the manifold shall be 
designed and constructed in accordance with approved 
engineering practices. As an alternate method, the effec- 
tive area of the manifold shall equal the combined area of 
the flue collars or draft hood outlets and the vent connec- 
tors shall have a minimum 1-foot (305 mm) rise. 

G2427.10.3.3 (503.10.3.3) Multiple apphances. Where 
two or more appliances are connected to a common vent 
or chimney, each vent connector shall be sized in accor- 
dance with Section G2428 or other approved engineer- 
ing methods. 

As an alternative method applicable only when all of 
the appliances are draft hood equipped, each vent con- 
nector shall have an effective area not less than the area of 
the draft hood outlet of the appliance to which it is con- 
nected. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



403 



FUEL GAS 



G2427.10.3.4 (503.10.3.4) Common connector/mani- 
fold. Where two or more appliances are vented through a 
common vent connector or vent manifold, the common 
vent connector or vent manifold shall be located at the 
highest level consistent with available headroom and the 
required clearance to combustible materials and shall be 
sized in accordance with Section G2428 or other 
approved engineering methods. 

As an alternate method applicable only where there 
are two draft hood-equipped appliances, the effective 
area of the common vent connector or vent manifold and 
all junction fittings shall be not less than the area of the 
larger vent connector plus 50 percent of the area of the 
smaller flue collar outlet. 

G2427.10.3.5 (503.10.3.5) Size increase. Where the 
size of a vent connector is increased to overcome instal- 
lation limitations and obtain connector capacity equal to 
the appliance input, the size increase shall be made at the 
appliance draft hood outlet. 

G2427.10.4 (503.10.4) Two or more appliances con- 
nected to a single vent. Where two or more vent connectors 
enter a common gas vent, chimney flue, or single- wall metal 
pipe, the smaller connector shall enter at the highest level 
consistent with the available headroom or clearance to com- 
bustible material. Vent connectors serving Category I appli- 
ances shall not be connected to any portion of a mechanical 
draft system operating under positive static pressure, such 
as those serving Category HI or IV appliances. 

G2427.10.5 (503.10.5) Clearance. Minimum clearances 
from vent connectors to combustible material shall be in 
accordance with Table G2427.7.7. 

Exception; The clearance between a vent connector and 
combustible material shall be permitted to be reduced 
where the combustible material is protected as specified 
for vent connectors in Table G2409.2. 

G2427.10.6 (503.10.6) Flow resistance. A vent connector 
shall be installed so as to avoid turns or other construction 
features that create excessive resistance to flow of vent 
gases. 

G2427.10.7 (503.10.7) Joints. Joints between sections of 
connector piping and connections to flue collars and draft 
hood outlets shall be fastened by one of the following meth- 
ods: 

1. Sheet metal screws. 

2. Vent connectors of listed vent material assembled and 
connected to flue collars or draft hood outlets in 
accordance with the manufacturers' instructions. 

3. Other approved means. 

G2427.10.8 (503.10.8) Slope. A vent connector shall be 
installed without dips or sags and shall slope upward toward 
the vent or chimney at least V4 inch per foot (21 mm/m). 

Exception: Vent connectors attached to a mechanical 
draft system installed in accordance with the manufac- 
turers' instructions. 



G2427.10.9 (503.10.9) Length of vent connector. A vent 
connector shall be as short as practical and the appliance 
located as close as practical to the chimney or vent. The 
maximum horizontal length of a single- wall connector shall 
be 75 percent of the height of the chimney or vent except for I 
engineered systems. The maximum horizontal length of a I 
Type B double- wall connector shall be 100 percent of the 
height of the chimney or vent except for engineered sys- I 
tems. For a chimney or vent system serving multiple appli- | 
ances, the maximum length of an individual connector, from 
the appliance outlet to the junction with the common vent or 
another connector, shall be 100 percent of the height of the 
chimney or vent. 

G2427.10.10 (503.10.10) Support. A vent connector shall 
be supported for the design and weight of the material 
employed to maintain clearances and prevent physical dam- 
age and separation of joints. 

G2427.10.il (503.10.11) Chimney connection. Where 
entering a flue in a masonry or metal chimney, the vent con- 
nector shall be installed above the extreme bottom to avoid 
stoppage. Where a thimble or slip joint is used to facilitate 
removal of the connector, the connector shall be firmly 
attached to or inserted into the thimble or slip joint to pre- 
vent the connector from falling out. Means shall be 
employed to prevent the connector from entering so far as to 
restrict the space between its end and the opposite wall of 
the chimney flue (see Section G2425.9). 

G2427.10.12 (503.10.12) Inspection. The entire length of a 
vent connector shall be provided with ready access for 
inspection, cleaning, and replacement. 

G2427.10.13 (503.10.13) Fireplaces. A vent connector 
shall not be connected to a chimney flue serving a fireplace 
unless the fireplace flue opening is permanently sealed. 

G2427.10.14 (503.10.14) Passage through ceilings, floors 
or walls. Single-wall metal pipe connectors shall not pass 
through any wall, floor or ceiling except as permitted by 
Sections G2427.7.4 and G2427.10.15. 

G2427.10.15 (503.10.15) Single-wall connector penetra- 
tions of combustible walls. A vent connector made of a sin- 
gle-wall metal pipe shall not pass through a combustible 
exterior wall unless guarded at the point of passage by a ven- 
tilated metal thimble not smaller than the following: 

1 . For listed appliances equipped with draft hoods and 
appliances listed for use with Type B gas vents, the 
thimble shall be not less than 4 inches (102 mm) 
larger in diameter than the vent connector. Where 
there is a run of not less than 6 feet ( 1 829 mm) of vent 
connector in the open between the draft hood outlet 
and the thimble, the thimble shall be permitted to be 
not less than 2 inches (5 1 mm) larger in diameter than 
the vent connector. 

2. For unlisted appliances having draft hoods, the thim- 
ble shall be not less than 6 inches (152 mm) larger in 
diameter than the vent connector. 



404 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FUEL GAS 



3. For residential and low-heat appliances, the thimble 
shall be not less than 12 inches (305 mm) larger in 
diameter than the vent connector. 

Exception: In lieu of thimble protection, all combustible 
material in the wall shall be removed from the vent con- 
nector a sufficient distance to provide the specified clear- 
ance from such vent connector to combustible material. 
Any material used to close up such opening shall be 
noncombustible. 

G2427.il (503.11) Vent connectors for Category II, III and 
IV appliances. Vent connectors for Category II, III and IV 

appliances shall be as specified for the venting systems in 
accordance with Section G2427.4. 

G2427.12 (503.12) Draft hoods and draft controls. The 

installation of draft hoods and draft controls shall comply with 
Sections G2427.12.1 through G2427.12.7. 

G2427.12.1 (503.12.1) Appliances requiring draft 
hoods. Vented appliances shall be installed with draft 
hoods. 

Exception: Dual oven-type combination ranges; 
incinerators; direct-vent appliances; fan-assisted com- 
bustion system appliances; appliances requiring chim- 
ney draft for operation; single firebox boilers equipped 
with conversion burners with inputs greater than 400,000 
Btu per hour (117 kW); appHances equipped with blast, 
power or pressure burners that are not listed for use with 
draft hoods; and appliances designed for forced venting. 

G2427.12.2 (503.12.2) Installation. A draft hood supphed 
with or forming a part of a listed vented appliance shall be 
installed without alteration, exactly as furnished and speci- 
fied by the appliance manufacturer. 

G2427.12.2.1 (503.12.2.1) Draft hood required. If a 

draft hood is not supplied by the appliance manufacturer 
where one is required, a draft hood shall be installed, 
shall be of a listed or approved type and, in the absence of 
other instructions, shall be of the same size as the appli- 
ance flue collar. Where a draft hood is required with a 
conversion burner, it shall be of a listed or approved type. 

G2427.12.2.2 (503.12.2.2) Special design draft hood. 

Where it is determined that a draft hood of special design 
is needed or preferable for a particular installation, the 
installation shall be in accordance with the recommenda- 
tions of the appliance manufacturer and shall be 
approved. 

G2427.12.3 (503.12.3) Draft control devices. Where a 
draft control device is part of the appliance or is supplied by 
the appliance manufacturer, it shall be installed in accor- 
dance with the manufacturer's instructions. In the absence 
of manufacturer's instructions, the device shall be attached 
to the flue collar of the appliance or as near to the appliance 
as practical. 

G2427.12.4 (503.12.4) Additional devices. Apphances 
(except incinerators) requiring a controlled chimney draft 
shall be permitted to be equipped with a listed double-acting 



barometric-draft regulator installed and adjusted in accor- 
dance with the manufacturer's instructions. 

G2427.12.5 (503.12.5) Location. Draft hoods and baro- 
metric draft regulators shall be installed in the same room or 
enclosure as the appliance in such a manner as to prevent 
any difference in pressure between the hood or regulator 
and the combustion air supply. 

G2427.12.6 (503.12.6) Positioning. Draft hoods and draft 
regulators shall be installed in the position for which they 
were designed with reference to the horizontal and vertical 
planes and shall be located so that the relief opening is not 
obstructed by any part of the appliance or adjacent construc- 
tion. The appliance and its draft hood shall be located so that 
the relief opening is accessible for checking vent operation. 

G2427.12.7 (503.12.7) Clearance. A draft hood shall be 
located so its relief opening is not less than 6 inches (152 
mm) from any surface except that of the appliance it serves 
and the venting system to which the draft hood is connected. 
Where a greater or lesser clearance is indicated on the 
appliance label, the clearance shall be not less than that 
specified on the label. Such clearances shall not be reduced. 

G2427.13 (503.13) Manually operated dampers. A manu- 
ally operated damper shall not be placed in the vent connector 
for any apphance. Fixed baffles shall not be classified as manu- 
ally operated dampers. 

G2427.14 (503.14) Automatically operated vent dampers. 

An automatically operated vent damper shall be of a listed type. 

G2427.15 (503.15) Obstructions. Devices that retard the flow 
of vent gases shall not be installed in a vent connector, chimney, 
or vent. The following shall not be considered as obstructions : 

1 . Draft regulators and safety controls specifically listed for 
installation in venting systems and installed in 
accordance with the manufacturer's installation instruc- 
tions. 

2. Approved draft regulators and safety controls that are 
designed and installed in accordance with approved 
engineering methods. 

3. Listed heat reclaimers and automatically operated vent 
dampers installed in accordance with the manufacturer's 
installation instructions. 

4. Approved economizers, heat reclaimers, and recupera- 
tors installed in venting systems of equipment not 
required to be equipped with draft hoods, provided that 
the appliance manufacturer's instructions cover the 
installation of such a device in the venting system and 
performance in accordance with Sections G2427.3 and 
G2427.3.1 is obtained. 

5. Vent dampers serving listed apphances installed in 
accordance with Sections G2428.2.1 and G2428.3.1 or 
other approved engineering methods. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



405 



FUEL GAS 



SECTION G2428 (504) 

SIZING OF CATEGORY I APPLIANCE 

VENTING SYSTEMS 

G2428.1 (504.1) Definitions. The following definitions apply 
to tables in this section. 

APPLIANCE CATEGORIZED VENT DIAME- 
TER/AREA. The minimum vent area/diameter permissible 
for Category I appliances to maintain a nonpositive vent static 
pressure when tested in accordance with nationally recognized 
standards. 

FAN-ASSISTED COMBUSTION SYSTEM. An apphance 
equipped with an integral mechanical means to either draw or 
force products of combustion through the combustion chamber 
or heat exchanger. 

FAN MIN. The minimum input rating of a Category I fan- 
assisted appliance attached to a vent or connector. 

FAN MAX. The maximum input rating of a Category I 
fan-assisted appliance attached to a vent or connector. 

NAT MAX. The maximum input rating of a Category I 
draft-hood-equipped appliance attached to a vent or connector. 

FAN + FAN. The maximum combined appliance input rating 
of two or more Category I fan-assisted appliances attached to 
the common vent. 

FAN + NAT. The maximum combined appliance input rating 
of one or more Category I fan-assisted appliances and one or 
more Category I draft-hood-equipped appliances attached to 
the common vent. 

NA. Vent configuration is not permitted due to potential for 
condensate formation or pressurization of the venting system, 
or not applicable due to physical or geometric restraints. 

NAT + NAT. The maximum combined appliance input rating 
of two or more Category I draft-hood-equipped appliances 
attached to the common vent. 

G2428.2 (504.2) Application of single appliance vent Tables 
G2428.2(l) and G2428.2(2). The application of Tables 
G2428.2(l) and G2428.2(2) shall be subject to the require- 
ments of Sections G2428.2.1 through G2428.2.15. 

G2428.2.1 (504.2.1) Vent obstructions. These venting 
tables shall not be used where obstructions, as described in 
Section G2427.15, are installed in the venting system. The 
installation of vents serving listed appliances with vent 
dampers shall be in accordance with the appliance manufac- 
turer's instructions or in accordance with the following: 

1 . The maximum capacity of the vent system shall be 
determined using the "NAT Max" column. 

2. The minimum capacity shall be determined as if the 
appliance were a fan-assisted appliance, using the 
"FAN Min" column to determine the minimum 



capacity of the vent system. Where the corresponding 
"FAN Min" is "NA," the vent configuration shall not 
be permitted and an alternative venting configuration 
shall be utilized. 

G2428.2.2 (504.2.2) Minimum size. Where the vent size 
determined from the tables is smaller than the appliance 
draft hood outlet or flue collar, the smaller size shall be per- 
mitted to be used provided all of the following are met: 

1 . The total vent height (H) is at least 10 feet (3048 mm). 

2. Vents for appliance draft hood outlets or flue collars 
12 inches (305 mm) in diameter or smaller are not 
reduced more than one table size. 

3. Vents for appliance draft hood outiets or flue collars 
larger than 12 inches (305 mm) in diameter are not 
reduced more than two table sizes. 

4. The maximum capacity listed in the tables for a 
fan-assisted appliance is reduced by 10 percent (0.90 
by maximum table capacity). 

5. The draft hood outlet is greater than 4 inches (102 
nmn) in diameter. Do not connect a 3 -inch-diameter 
(76 mm) vent to a 4-inch-diameter (102 mm) draft 
hood outlet. This provision shall not apply to 
fan-assisted appliances. 

G2428.2.3 (504.2.3) Vent offsets. Single-apphance venting 
configurations with zero (0) lateral lengths in Tables 
G2428.2(l) and G2428.2(2) shall not have elbows in the 
venting system. Single-appliance venting configurations 
with lateral lengths include two 90-degree (1.57 rad) 
elbows. For each additional elbow up to and including 45 
degrees (0.79 rad), the maximum capacity hsted in the vent- 
ing tables shall be reduced by 5 percent. For each additional 
elbow greater than 45 degrees (0.79 rad) up to and including 
90 degrees (1.57 rad), the maximum capacity listed in the 
venting tables shall be reduced by 10 percent. 

G2428.2.4 (504.2.4) Zero lateral. Zero (0) lateral (L) shall 
apply only to a straight vertical vent attached to a top outlet 
draft hood or flue collar. 

G2428.2.5 (504.2.5) High altitude installations. Sea level 
input ratings shall be used when determining maximum 
capacity for high altitude installation. Actual input, derated 
for altitude, shall be used for determining minimum capac- 
ity for high altitude installation. 

G2428.2.6 (504.2.6) Multiple input rate appliances. For 

appliances with more than one input rate, the minimum vent 
capacity (FAN Min) determined from the tables shall be less 
than the lowest appliance input rating, and the maximum 
vent capacity (FAN Max/NAT Max) determined from the 
tables shall be greater than the highest appliance rating 
input. 



406 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



TABLE G2428.2(1) [504.2(1)] 
TYPE B DOUBLE-WALL GAS VENT 



Number of Appliances 


Single 


Appliance Type 


Category I 


Appliance Vent Connection 


Connected directly to vent 



HEIGHT 

(H) 

(feet) 


LATERAL 

(L) 

(feet) 


VENT DIAMETER— (O; inches 


3 


4 


5 


6 


7 


8 


9 


APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


6 








78 


46 





152 


86 





251 


141 





375 


205 





524 


285 





698 


370 





897 


470 


2 


13 


51 


36 


18 


97 


67 


27 


157 


105 


32 


232 


157 


44 


321 


217 


53 


425 


285 


63 


543 


370 


4 


21 


49 


34 


30 


94 


64 


39 


153 


103 


50 


227 


153 


66 


316 


211 


79 


419 


279 


93 


536 


362 


6 


25 


46 


32 


36 


91 


61 


47 


149 


100 


59 


223 


149 


78 


310 


205 


93 


413 


273 


110 


530 


354 


8 








84 


50 





165 


94 





276 


155 





415 


235 





583 


320 





780 


415 





1,006 


537 


2 


12 


57 


40 


16 


109 


75 


25 


178 


120 


28 


263 


180 


42 


365 


247 


50 


483 


322 


60 


619 


418 


5 


23 


53 


38 


32 


103 


71 


42 


171 


115 


53 


255 


173 


70 


356 


237 


83 


473 


313 


99 


607 


^407 


8 


28 


49 


35 


39 


98 


66 


51 


164 


109 


64 


247 


165 


84 


347 


227 


99 


463 


303 


117 


596 


396 


10 








88 


53 





175 


100 





295 


166 





447 


255 





631 


345 





847 


450 





1,096 


585 


2 


12 


61 


42 


17 


118 


81 


23 


194 


129 


26 


289 


195 


40 


402 


273 


48 


533 


355 


57 


684 


457 


5 


23 


57 


40 


32 


113 


77 


41 


187 


124 


52 


280 


188 


68 


392 


263 


81 


522 


346 


95 


671 


446 


10 


30 


51 


36 


41 


104 


70 


54 


176 


115 


67 


267 


175 


88 


376 


245 


104 


504 


330 


122 


651 


427 


15 








94 


58 





191 


112 





327 


187 





502 


285 





716 


390 





970 


525 





1,263 


682 


2 


11 


69 


48 


15 


136 


93 


20 


226 


150 


22 


339 


225 


38 


475 


316 


45 


633 


414 


53 


815 


544 


5 


22 


65 


45 


30 


130 


87 


39 


219 


142 


49 


330 


217 


64 


463 


300 


76 


620 


403 


90 


800 


529 


10 


29 


59 


41 


40 


121 


82 


51 


206 


135 


64 


315 


208 


84 


445 


288 


99 


600 


386 


116 


777 


507 


15 


35 


53 


37 


48 


112 


76 


61 


195 


128 


76 


301 


198 


98 


429 


275 


115 


580 


373 


134 


755 


491 


20 








97 


61 





202 


119 





349 


202 





540 


307 





776 


430 





1,057 


575 





1,384 


752 


2 


10 


75 


51 


14 


149 


100 


18 


250 


166 


20 


377 


249 


33 


531 


346 


41 


711 


470 


50 


917 


612 


5 


21 


71 


48 


29 


143 


96 


38 


242 


160 


47 


367 


241 


62 


519 


337 


73 


697 


460 


86 


902 


599 


10 


28 


64 


44 


38 


133 


89 


50 


229 


150 


62 


351 


228 


81 


499 


321 


95 


675 


443 


112 


877 


576 


15 


34 


58 


40 


46 


124 


84 


59 


217 


142 


73 


337 


217 


94 


481 


308 


111 


654 


427 


129 


853 


557 


20 


48 


52 


35 


55 


116 


78 


69 


206 


134 


84 


322 


206 


107 


464 


295 


125 


634 


410 


145 


830 


537 



(continued) 



> 



TABLE G2428.2(1) [504.2(1)]— continued 
TYPE B DOUBLE-WALL GAS VENT 



Number of Appliances 


Single 


Appliance Type 


Category I 


Appliance Vent Connection 


Connected directly to vent 



-n 

c 
m 

i- 

o 

> 



HEIGHT 

(h; 

(feet) 


LATERAL 

(L) 

(feet) 


VENT DIAMETER— (D; inches 


3 


4 


5 


6 


7 


8 


9 


APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


30 








100 


64 





213 


128 





374 


220 





587 


336 





853 


475 





1,173 


650 





1,548 


855 


2 


9 


81 


56 


13 


166 


112 


14 


283 


185 


18 


432 


280 


27 


613 


394 


33 


826 


535 


42 


1,072 


700 


5 


21 


77 


54 


28 


160 


108 


36 


275 


176 


45 


421 


273 


58 


600 


385 


69 


811 


524 


82 


1,055 


688 


10 


27 


70 


50 


37 


150 


102 


48 


262 


171 


59 


405 


261 


77 


580 


371 


91 


788 


507 


107 


1,028 


668 


15 


33 


64 


NA 


44 


141 


96 


57 


249 


163 


70 


389 


249 


90 


560 


357 


105 


765 


490 


124 


1,002 


648 


20 


56 


58 


NA 


53 


132 


90 


66 


237 


154 


80 


374 


237 


102 


542 


343 


119 


743 


473 


139 


977 


628 


30 


NA 


NA 


NA 


73 


113 


NA 


88 


214 


NA 


104 


346 


219 


131 


507 


321 


149 


702 


444 


171 


929 


594 


50 








101 


67 





216 


134 





397 


232 





633 


363 





932 


518 





1,297 


708 





1,730 


952 


2 


8 


86 


61 


11 


183 


122 


14 


320 


206 


15 


497 


314 


22 


715 


445 


26 


975 


615 


33 


1,276 


813 


5 


20 


82 


NA 


27 


177 


119 


35 


312 


200 


43 


487 


308 


55 


702 


438 


65 


960 


605 


77 


1,259 


798 


10 


26 


76 


. NA 


35 


168 


114 


45 


299 


190 


56 


471 


298 


73 


681 


426 


86 


935 


589 


101 


1,230 


773 


15 


59 


70 


NA 


42 


158 


NA 


54 


287 


180 


66 


455 


288 


85 


662 


413 


100 


911 


572 


117 


1,203 


747 


20 


NA 


NA 


NA 


50 


149 


NA 


63 


275 


169 


76 


440 


278 


97 


642 


401 


113 


888 


556 


131 


1,176 


722 


30 


NA 


NA 


NA 


69 


131 


NA 


84 


250 


NA 


99 


410 


259 


123 


605 


376 


141 


844 


522 


161 


1,125 


670 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 



O 

z 
> 

r- 

33 

m 
</) 

D 

m 



o 
o 

D 

m 



J3 

m 
w 

D 

m 

z 

H 
> 

r- 
o 
o 
o 
m 
® 



TABLE G2428.2(2) [504.2(2)] 
TYPE B DOUBLE-WALL GAS VENT 



Number of Appliances 


Single 


Appliance Type 


Category I 


Appliance Vent Connection 


Single-wall metal connector 



HEIGHT 

(H) 
(feet) J 


LATERAL 

(L) 

(feet) 


VENT DIAMETER— (D) inches 


3 


4 


5 


6 7 


8 


9 


10 


12 


APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


6 





38 


77 


45 


59 


151 


85 


85 


249 


140 


126 


373 


204 


165 


522 


284 


211 


695 


369 


267 


894 


469 


371 


1,118 


569 


537 


1,639 


849 


2 


39 


51 


36 


60 


96 


66 


85 


156 


104 


123 


231 


156 


159 


320 


213 


201 


423 


284 


251 


541 


368 


347 


673 


453 


498 


979 


648 


4 


NA 


NA 


33 


74 


92 


63 


102 


152 


102 


146 


225 


152 


187 


313 


208 


237 


416 


277 


295 


533 


360 


409 


664 


443 


584 


971 


638 


6 


NA 


NA 


31 


83 


89 


60 


114 


147 


99 


163 


220 


148 


207 


307 


203 


263 


409 


271 


327 


526 


352 


449 


656 


433 


638 


962 


627 


8 





37 


83 


50 


58 


164 


93 


83 


273 


154 


123 


412 


234 


161 


580 


319 


206 


777 


414 


258 


1,002 


536 


360 


1,257 


658 


521 


1,852 


967 


2 


39 


56 


39 


59 


108 


75 


83 


176 


119 


121 


261 


179 


155 


363 


246 


197 


482 


321 


246 


617 


417 


339 


768 


513 


486 


1,120 


743 


5 


NA 


NA 


37 


77 


102 


69 


107 


168 


114 


151 


252 


171 


193 


352 


235 


245 


470 


311 


305 


604 


404 


418 


754 


500 


598 


1,104 


730 


8 


NA 


NA 


33 


90 


95 


64 


122 


161 


107 


175 


243 


163 


223 


342 


225 


280 


458 


300 


344 


591 


392 


470 


740 


486 


665 


1,089 


715 


10 





37 


87 


53 


57 


174 


99 


82 


293 


165 


120 


444 


254 


158 


628 


344 


202 


844 


449 


253 


1,093 


584 


351 


1,373 


718 


507 


2,031 


1,057 


2 


39 


61 


41 


59 


117 


80 


82 


193 


128 


119 


287 


194 


153 


400 


272 


193 


531 


354 


242 


681 


456 


332 


849 


559 


475 


1,242 


848 


5 


52 


56 


39 


76 


111 


76 


105 


185 


122 


148 


277 


186 


190 


388 


261 


241 


518 


344 


299 


667 


443 


409 


834 


544 


584 


1,224 


825 


10 


NA 


NA 


34 


97 


100 


68 


132 


171 


112 


188 


261 


171 


237 


369 


241 


296 


497 


325 


363 


643 


423 


492 


808 


520 


688 


1,194 


788 


15 





36 


93 


57 


56 


190 


111 


80 


325 


186 


116 


499 


283 


153 


713 


388 


195 


966 


523 


244 


1,259 


681 


336 


1,591 


838 


488 


2,374 


1,237 


2 


38 


69 


47 


57 


136 


93 


80 


225 


149 


115 


337 


224 


148 


473 


314 


187 


631 


413 


232 


812 


543 


319 


1,015 


673 


457 


1,491 


983 


5 


51 


63 


44 


75 


128 


86 


102 


216 


140 


144 


326 


217 


182 


459 


298 


231 


616 


400 


287 


795 


526 


392 


997 


657 


562 


1,469 


963 


10 


NA 


NA 


39 


95 


116 


79 


128 


201 


131 


182 


308 


203 


228 


438 


284 


284 


592 


381 


349 


768 


501 


470 


966 


628 


664 


1,433 


928 


15 


NA 


NA 


NA 


NA 


NA 


72 


158 


186 


124 


220 


290 


192 


272 


418 


269 


334 


568 


367 


404 


742 


484 


540 


937 


601 


750 


1,399 


894 


20 





35 


96 


60 


54 


200 


118 


78 


346 


201 


114 


537 


306 


149 


772 


428 


190 


1,053 


573 


238 


1,379 


750 


326 


1,751 


927 


473 


2,631 


1,346 


2 


37 


74 


50 


56 


148 


99 


78 


248 


165 


113 


375 


248 


144 


528 


344 


182 


708 


468 


227 


914 


611 


309 


1,146 


754 


443 


1,689 


1,098 


5 


50 


68 


47 


73 


140 


94 


100 


239 


158 


141 


363 


239 


178 


514 


334 


224 


692 


457 


279 


896 


596 


381 


1,126 


734 


547 


1,665 


1,074 


10 


NA 


NA 


41 


93 


129 


86 


125 


223 


146 


177 


344 


224 


222 


491 


316 


277 


666 


437 


339 


866 


570 


457 


1,092 


702 


646 


1,626 


1,037 


15 


NA 


NA 


NA 


NA 


NA 


80 


155 


208 


136 


216 


325 


210 


264 


469 


301 


325 


640 


419 


393 


838 


549 


526 


1,060 


677 


730 


1,587 


1,005 


20 


NA 


NA 


NA 


NA 


NA 


NA 


186 


192 


126 


254 


306 


196 


309 


448 


285 


374 


616 


400 


448 


810 


526 


592 


1,028 


651 


808 


1,550 


973 



(continued) 



TABLE G2428.2(2) [504.2(2)— continued] 
TYPE B DOUBLE-WALL GAS VENT 



Number of Appliances 


Single 


Appliance Type 


Category I 


Appliance Vent Connection 


Single-wall metal connector 



HEIGHT 

(H) 
(feet) 


LATERAL 

(L) 

(feet) 


VENT DIAMETER— (D) inches 


3 


4 


5 


6 


7 


8 


9 


10 


12 


APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


30 





34 


99 


63 


53 


211 


127 


76 


372 


219 


no 


584 


334 


144 


849 


472 


184 


1,168 


647 


229 


1,542 


852 


312 


1,971 


1,056 


454 


2,996 


1,545 


2 


37 


80 


56 


55 


164 


111 


76 


281 


183 


109 


429 


279 


139 


610 


392 


175 


823 


533 


219 


1,069 


698 


296 


1,346 


863 


424 


1,999 


1,308 


5 


49 


74 


52 


72 


157 


106 


98 


271 


173 


136 


417 


271 


171 


595 


382 


215 


806 


521 


269 


1,049 


684 


366 


1,324 


846 


524 


1,971 


1,283 


10 


NA 


NA 


NA 


91 


144 


98 


122 


255 


168 


171 


397 


257 


213 


570 


367 


265 


777 


501 


327 


1,017 


662 


440 


1,287 


821 


620 


1,927 


1,234 


15 


NA 


NA 


NA 


115 


131 


NA 


151 


239 


157 


208 


377 


242 


255 


547 


349 


312 


750 


481 


379 


985 


638 


507 


1,251 


794 


702 


1,884 


1,205 


20 


NA 


NA 


NA 


NA 


NA 


NA 


181 


223 


NA 


246 


357 


228 


298 


524 


333 


360 


723 


461 


433 


955 


615 


570 


1,216 


768 


780 


1,841 


1,166 


30 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


389 


477 


305 


461 


670 


426 


541 


895 


574 


704 


1,147 


720 


937 


1,759 


1,101 


50 





33 


99 


66 


51 


213 


133 


73 


394 


230 


105 


629 


361 


138 


928 


515 


176 


1,292 


704 


220 


1,724 


948 


295 


2,223 


1,189 


428 


3,432 


1,818 


2 


36 


84 


61 


53 


181 


121 


73 


318 


205 


104 


495 


312 


133 


712 


443 


168 


971 


613 


209 


1,273 


811 


280 


1,615 


1,007 


401 


2,426 


1,509 


5 


48 


80 


NA 


70 


174 


117 


94 


308 


198 


131 


482 


305 


164 


696 


435 


204 


953 


602 


257 


1,252 


795 


347 


1,591 


991 


496 


2,396 


1,490 


10 


NA 


NA 


NA 


89 


160 


NA 


118 


292 


186 


162 


461 


292 


203 


671 


420 


253 


923 


583 


313 


1,217 


765 


418 


1,551 


963 


589 


2,347 


1,455 


15 


NA 


NA 


NA 


112 


148 


NA 


145 


275 


174 


199 


441 


280 


244 


646 


405 


299 


894 


562 


363 


1,183 


736 


481 


1,512 


934 


668 


2,299 


1,421 


20 


NA 


NA 


NA 


NA 


NA 


NA 


176 


257 


NA 


236 


420 


267 


285 


622 


389 


345 


866 


543 


415 


1,150 


708 


544 


1,473 


906 


741 


2,251 


1,387 


30 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


315 


376 


NA 


373 


573 


NA 


442 


809 


502 


521 


1,086 


649 


674 


1,399 


848 


892 


2,159 


1,318 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W. 



O 

z 
> 

l- 
3) 

m 
u> 

p 
m 



G2428.2.7 (504.2.7) Liner system sizing and connec- 
tions. Listed corrugated metallic chimney liner systems in 
masonry chimneys shall be sized by using Table 
02428.2(1) or G2428.2(2) for Type B vents with the maxi- 
mum capacity reduced by 20 percent (0.80 x maximum 
capacity) and the minimum capacity as shown in Table 
G2428.2(l) or 02428.2(2). Corrugated metallic liner sys- 
tems installed with bends or offsets shall have their maxi- 
mum capacity further reduced in accordance with Section 
02428.2.3. The 20-percent reduction for corrugated 
metallic chimney liner systems includes an allowance for 
one long-radius 90-degree (1.57 rad) turn at the bottom of 
the liner. 

Connections between chimney liners and listed dou- 
ble-wall connectors shall be made with listed adapters 
designed for such purpose. 

G2428.2.8 (504.2.8) Vent area and diameter. Where the 
vertical vent has a larger diameter than the vent connector, 
the vertical vent diameter shall be used to determine the 
minimum vent capacity, and the connector diameter shall be 
used to determine the maximum vent capacity. The flow 
area of the vertical vent shall not exceed seven times the 
flow area of the listed appliance categorized vent area, flue 
collar area, or draft hood outlet area unless designed in 
accordance with approved engineering methods. 

G2428.2.9 (504.2.9) Chimney and vent locations. Tables 
02428.2(1) and 02428.2(2) shall only be used for chim- 
neys and vents not exposed to the outdoors below the roof 
line. A Type B vent or hsted chimney lining system passing 
through an unused masonry chimney flue shall not be con- 
sidered to be exposed to the outdoors. A Type B vent shall 
not be considered to be exposed to the outdoors where it 
passes through an unventilated enclosure or chase insulated 
to a value of not less than R-8. 

Exception: The installation of vents serving listed appli- 
ances shall be permitted to be in accordance with the 
appliance manufacturer's installation instructions. 

G2428.2.10 (504.2.10) Corrugated vent connector size. 

Corrugated vent connectors shall be not smaller than the 
listed appliance categorized vent diameter, flue collar diam- 
eter, or draft hood outlet diameter. 

G2428.2.11 (504.2.11) Vent connector size limitation. 

Vent connectors shall not be increased in size more than two 
sizes greater than the listed appliance categorized vent 
diameter, flue collar diameter or draft hood outlet diameter. 

G2428.2.12 (504.2.12) Component commingling. In a 

single run of vent or vent connector, different diameters and 
types of vent and connector components shall be permitted 
to be used, provided that all such sizes and types are permit- 
ted by the tables. 

G2428.2.13 (504.2.13) Draft hood conversion accesso- 
ries. Draft hood conversion accessories for use with 



FUEL GAS 



masonry chimneys venting listed Category I fan-assisted 
apphances shall be listed and installed in accordance with 
the manufacturer's installation instructions for such listed 
accessories. 

G2428.2.14 (504.2.14) Table interpolation. Interpolation 
shall be permitted in calculating capacities for vent dimen- 
sions that fall between the table entries (see Example 3, 
Appendix B). 

G2428.2.15 (504.2.15) Extrapolation prohibited. Extrap- 
olation beyond the table entries shall not be permitted. 

G2428.2.16 (504.2.16) Engineering calculations. For vent 
heights less than 6 feet (1829 mm) and greater than shown in 
the tables, engineering methods shall be used to calculate 
vent capacities. 

G2428.3 (504.3) Application of multiple appliance vent 
Tables G2428.3(l) through G2428.3(4). The application of 
Tables 02428.3(1) through 02428.3(4) shall be subject to the 
requirements of Sections 02428.3.1 through 02428.3.22. 

G2428.3.1 (504.3.1) Vent obstructions. These venting 
tables shall not be used where obstructions, as described in 
Section 02427.15, are installed in the venting system. The 
installation of vents serving listed appliances with vent 
dampers shall be in accordance with the appliance manufac- 
turer's instructions or in accordance with the following: 

1 . The maximum capacity of the vent connector shall be 
determined using the NAT Max column. 

2. The maximum capacity of the vertical vent or chim- 
ney shall be determined using the FAN+NAT column 
when the second appliance is a fan-assisted appliance, 
or the NAT-i-NAT column when the second appliance 
is equipped with a draft hood. 

3. The minimum capacity shall be determined as if the 
appliance were a fan-assisted appliance. 

3.1. The minimum capacity of the vent connector 
shall be determined using the FAN Min column. 

3.2. The FAN-i-FAN column shall be used when the 
second appliance is a fan-assisted appliance, 
and the FANh-NAT column shall be used when 
the second appliance is equipped with a draft 
hood, to determine whether the vertical vent or 
chimney configuration is not permitted (NA). 
Where the vent configuration is NA, the vent 
configuration shall not be permitted and an al- 
ternative venting configuration shall be utilized. 

G2428.3.2 (504.3.2) Connector length limit. The vent 
connector shall be routed to the vent utilizing the shortest 
possible route. Except as provided in Section 02428.3.3, 
the maximum vent connector horizontal length shall be 1.5 
feet (457 mm) for each inch (18 mm per mm) of connector 
diameter as shown in Table G2428.3.2. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



411 



FUEL GAS 



TABLE G2428.3(1) [504.3(1)] 
TYPE B DOUBLE-WALL VENT 



Number of Appliances 


Two or more 


Appliance Type 


Category I 


Appliance Vent Connection Type B double- wall connector 



VENT CONNECTOR CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


CONNECTOR 
RISE 

(R) 
(feet) 


TYPE B DOUBLE-WALL VENT AND CONNECTOR DIAMETER— (D) inches 


3 


4 


5 


6 


7 


8 


9 


10 


APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


6 


1 


22 


37 


26 


35 


66 


46 


46 


106 


72 


58 


164 


104 


77 


225 


142 


92 


296 


185 


109 


376 


237 


128 


466 


289 


2 


23 


41 


31 


37 


75 


55 


48 


121 


86 


60 


183 


124 


79 


253 


168 


95 


333 


220 


112 


424 


282 


131 


526 


345 


3 


24 


44 


35 


38 


81 


62 


49 


132 


96 


62 


199 


139 


82 


275 


189 


97 


363 


248 


114 


463 


317 


134 


575 


386 


8 


1 


22 


40 


27 


35 


72 


48 


49 


114 


76 


64 


176 


109 


84 


243 


148 


100 


320 


194 


118 


408 


248 


138 


507 


303 


2 


23 


44 


32 


36 


80 


57 


51 


128 


90 


66 


195 


129 


86 


269 


175 


103 


356 


230 


121 


454 


294 


141 


564 


358 


3 


24 


47 


36 


37 


87 


64 


53 


139 


101 


67 


210 


145 


88 


290 


198 


105 


384 


258 


123 


492 


330 


143 


612 


402 


10 


1 


22 


43 


28 


34 


78 


50 


49 


123 


78 


65 


189 


113 


89 


257 


154 


106 


341 


200 


125 


436 


257 


146 


542 


314 


2 


23 


47 


33 


36 


86 


59 


51 


136 


93 


67 


206 


134 


91 


282 


182 


109 


374 


238 


128 


479 


305 


149 


596 


372 


3 


24 


50 


37 


37 


92 


67 


52 


146 


104 


69 


220 


150 


94 


303 


205 


111 


402 


268 


131 


515 


342 


152 


642 


417 


15 


1 


21 


50 


30 


33 


89 


53 


47 


142 


83 


64 


220 


120 


88 


298 


163 


110 


389 


214 


134 


493 


273 


162 


609 


333 


2 


22 


53 


35 


35 


96 


63 


49 


153 


99 


66 


235 


142 


91 


320 


193 


112 


419 


253 


137 


532 


323 


165 


658 


394 


3 


24 


55 


40 


36 


102 


71 


51 


163 


111 


68 


248 


160 


93 


339 


218 


115 


445 


286 


140 


565 


365 


167 


700 


444 


20 


1 


21 


54 


31 


33 


99 


56 


46 


157 


87 


62 


246 


125 


86 


334 


171 


107 


436 


224 


131 


552 


285 


158 


681 


347 


2 


22 


.57 


37 


34 


105 


66 


48 


167 


104 


64 


259 


149 


89 


354 


202 


110 


463 


265 


134 


587 


339 


161 


725 


414 


3 


23 


60 


42 


35 


110 


74 


50 


176 


116 


66 


271 


168 


91 


371 


228 


113 


486 


300 


137 


618 


383 


164 


764 


466 


30 


1 


20 


62 


33 


31 


113 


59 


45 


181 


93 


60 


288 


134 


83 


391 


182 


103 


512 


238 


125 


649 


305 


151 


802 


372 


2 


21 


64 


39 


33 


118 


70 


47 


190 


110 


62 


299 


158 


85 


408 


215 


105 


535 


282 


129 


679 


360 


155 


840 


439 


3 


22 


66 


44 


34 


123 


79 


48 


198 


124 


64 


309 


178 


88 


423 


242 


108 


555 


317 


132 


706 


405 


158 


874 


494 



COMMON VENT CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


TYPE B DOUBLE-WALL COMMON VENT DIAMETER (D)— inches 


4 


5 


6 7 


8 


9 


10 


COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


6 


92 


81 


65 


140 


116 


103 


204 


161 


147 


309 


248 


200 


404 


314 


260 


547 


434 


335 


672 


520 


410 


8 


101 


90 


73 


155 


129 


114 


224 


178 


163 


339 


275 


223 


444 


348 


290 


602 


480 


378 


740 : 


577 


465 


10 


110 


97 


79 


169 


141 


124 


243 


194 


178 


367 


299 


242 


477 


377 


315 


649 


522 


405 


800 


627 


495 


15 


125 


112 


91 


195 


164 


144 


283 


228 


206 


427 


352 


280 


556 


444 


365 


753 


612 


465 


924 


733 


565 


20 


136 


123 


102 


215 


183 


160 


314 


255 


229 


475 


394 


310 


621 


499 


405 


842 


688 


523 


1,035 


826 


640 


30 


152 


138 


118 


244 


210 


185 


361 


297 


266 


547 


459 


360 


720 


585 


470 


979 


808 


605 


1,209 


975 


740 


50 


167 


153 


134 


279 


244 


214 


421 


353 


310 


641 


547 


423 


854 


706 


550 


1,164 


977 


705 


1,451 


1,188 


860 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.293 1 W 



412 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



FUEL GAS 



TABLE G2428.3(2) [504.3(2)] 
TYPE B DOUBLE-WALL VENT 



Number of Appliances 


Two or more 


Appliance Type 


Category 1 


Appliance Vent Connection 


Single-wall metal connector 



VENT CONNECTOR CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


CONNECTOR 
RISE 

(ff) 
(feet) 


SINGLE-WALL METAL VENT CONNECTOR DIAMETER— (D) inches 


3 


4 


5 


6 


7 


8 


9 


10 


APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


6 


1 


NA 


NA 


26 


NA 


NA 


46 


NA 


NA 


71 


NA 


NA 


102 


207 


223 


140 


262 


293 


183 


325 


373 


234 


447 


463 


286 


2 


NA 


NA 


31 


NA 


NA 


55 


NA 


NA 


85 


168 


182 


123 


215 


251 


167 


271 


331 


219 


334 


422 


281 


458 


524 


344 


3 


NA 


NA 


34 


NA 


NA 


62 


121 


131 


95 


175 


198 


138 


222 


273 


188 


279 


361 


247 


344 


462 


316 


468 


574 


385 


8 


1 


NA 


NA 


27 


NA 


NA 


48 


NA 


NA 


75 


NA 


NA 


106 


226 


240 


145 


285 


316 


191 


352 


403 


244 


481 


502 


299 


2 


NA 


NA 


32 


NA 


NA 


57 


125 


126 


89 


184 


193 


127 


234 


266 


173 


293 


353 


228 


360 


450 


292 


492 


560 


355 


3 


NA 


NA 


35 


NA 


NA 


64 


130 


138 


100 


191 


208 


144 


241 


287 


197 


302 


381 


256 


370 


489 


328 


501 


609 


400 


10 


1 


NA 


NA 


28 


NA 


NA 


50 


119 


121 


77 


182 


186 


110 


240 


253 


150 


302 


335 


196 


372 


429 


252 


506 


534 


308 


2 


NA 


NA 


33 


84 


85 


59 


124 


134 


91 


189 


203 


132 


248 


278 


183 


311 


369 


235 


381 


473 


302 


517 


589 


368 


3 


NA 


NA 


36 


89 


91 


67 


129 


144 


102 


197 


217 


148 


257 


299 


203 


320 


398 


265 


391 


511 


339 


528 


637 


413 


15 


1 


NA 


NA 


29 


79 


87 


52 


116 


138 


81 


177 


214 


116 


238 


291 


158 


312 


380 


208 


397 


482 


266 


556 


596 


324 


2 


NA 


NA 


34 


83 


94 


62 


121 


150 


97 


185 


230 


138 


246 


314 


189 


321 


411 


248 


407 


522 


317 


568 


646 


387 


3 


NA 


NA 


39 


87 


100 


70 


127 


160 


109 


193 


243 


157 


255 


333 


215 


331 


438 


281 


418 


557 


360 


579 


690 


437 


20 


1 


49 


56 


30 


78 


97 


54 


115 


152 


84 


175 


238 


120 


233 


325 


165 


306 


425 


217 


390 


538 


276 


546 


664 


336 


2 


52 


59 


36 


82 


103 


64 


120 


163 


101 


182 


252 


144 


243 


346 


197 


317 


453 


259 


400 


574 


331 


558 


709 


403 


3 


55 


62 


40 


87 


107 


72 


125 


172 


113 


190 


264 


164 


252 


363 


223 


326 


476 


294 


412 


607 


375 


570 


750 


457 


30 


1 


47 


60 


31 


77 


110 


57 


112 


175 


89 


169 


278 


129 


226 


380 


175 


296 


497 


230 


378 


630 


294 


528 


779 


358 


2 


51 


62 


37 


81 


115 


67 


117 


185 


106 


177 


290 


152 


236 


397 


208 


307 


521 


274 


389 


662 


349 


541 


819 


425 


3 


54 


64 


42 


85 


119 


76 


122 


193 


120 


185 


300 


172 


244 


412 


235 


316 


542 


309 


400 


690 


394 


555 


855 


482 



COMMON VENT CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


TYPE B DOUBLE-WALL COMMON VENT DIAMETER— (D) inches 


4 


5 


6 7 8 9 10 


COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


6 


NA 


78 


64 


NA 


113 


99 


200 


158 


144 


304 


244 


196 


398 


310 


257 


541 


429 


332 


665 


515 


407 


8 


NA 


87 


71 


NA 


126 


111 


218 


173 


159 


331 


269 


218 


436 


342 


285 


592 


473 


373 


730 


569 


460 


10 


NA 


94 


76 


163 


137 


120 


237 


189 


174 


357 


292 


236 


467 


369 


309 


638 


512 


398 


787 


617 


487 


15 


121 


108 


88 


189 


159 


140 


275 


221 


200 


416 


343 


274 


544 


434 


357 


738 


599 


456 


905 


718 


553 


20 


131 


118 


98 


208 


177 


156 


305 


247 


223 


463 


383 


302 


606 


487 


395 


824 


673 


512 


1,013 


808 


626 


30 


145 


132 


113 


236 


202 


180 


350 


286 


257 


533 


446 


349 


703 


570 


459 


958 


790 


593 


1,183 


952 


723 


50 


159 


145 


128 


268 


233 


208 


406 


337 


296 


622 


529 


410 


833 


686 


535 


1,139 


954 


689 


1,418 


1,157 


838 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



413 



FUEL GAS 



TABLE G2428.3(3) [504.3(3)] 
MASONRY CHIMNEY 



Number of Appliances 


Two or more 


Appliance Type 


Category I 


Appliance Vent Connection 


Type B double- wall connector 



VENT CONNECTOR CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


CONNECTOR 
RISE 

(fl) 
(feet) 


TYPE B DOUBLE-WALL VENT CONNECTOR DIAMETER— (D) inches 


3 


4 


_ s ' 


6 


7 


8 


9 


10 


APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


6 


1 


24 


33 


21 


39 


62 


40 


52 


106 


67 


65 


194 


101 


87 


274 


141 


104 


370 


201 


124 


479 


253 


145 


599 


319 


2 


26 


43 


28 


41 


79 


52 


53 


133 


85 


67 


230 


124 


89 


324 


173 


107 


436 


232 


127 


562 


300 


148 


694 


378 


3 


27 


49 


34 


42 


92 


61 


55 


155 


97 


69 


262 


143 


91 


369 


203 


109 


491 


270 


129 


633 


349 


151 


795 


439 


8 


1 


24 


39 


22 


39 


72 


41 


55 


117 


69 


71 


213 


105 


94 


304 


148 


113 


414 


210 


134 


539 


267 


156 


682 


335 


2 


26 


47 


29 


40 


87 


53 


57 


140 


86 


73 


246 


127 


97 


350 


179 


116 


473 


240 


137 


615 


311 


160 


776 


394 


3 


27 


52 


34 


42 


97 


62 


59 


159 


98 


75 


269 


145 


99 


383 


206 


119 


517 


276 


139 


672 


358 


163 


848 


452 


10 


1 


24 


42 


22 


38 


80 


42 


55 


130 


71 


74 


232 


108 


101 


324 


153 


120 


444 


216 


142 


582 


277 


165 


739 


348 


2 


26 


50 


29 


40 


93 


54 


57 


153 


87 


76 


261 


129 


103 


366 


184 


123 


498 


247 


145 


652 


321 


168 


825 


407 


3 


27 


55 


35 


41 


105 


63 


58 


170 


100 


78 


284 


148 


106 


397 


209 


126 


540 


281 


147 


705 


366 


171 


893 


463 


15 


1 


24 


48 


23 


38 


93 


44 


54 


154 


74 


72 


277 


114 


100 


384 


164 


125 


511 


229 


153 


658 


297 


184 


824 


375 


2 


25 


55 


31 


39 


105 


55 


56 


174 


89 


74 


299 


134 


103 


419 


192 


128 


558 


260 


156 


718 


339 


187 


900 


432 


3 


26 


59 


35 


41 


115 


64 


57 


189 


102 


76 


319 


153 


105 


448 


215 


131 


597 


292 


159 


760 


382 


190 


960 


486 


20 


1 


24 


52 


24 


37 


102 


46 


.53 


172 


77 


71 


313 


119 


98 


437 


173 


123 


584 


239 


150 


752 


312 


180 


943 


397 


2 


25 


58 


31 


39 


114 


56 


55 


190 


91 


73 


335 


138 


101 


467 


199 


126 


625 


270 


153 


805 


354 


184 


1,011 


452 


3 


26 


63 


35 


40 


123 


65 


57 


204 


104 


75 


353 


157 


104 


493 


222 


129 


661 


301 


156 


851 


396 


187 


1,067 


505 



COMMON VENT CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 


12 


19 


28 


38 


50 


63 


78 


113 


COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


6 


NA 


74 


25 


NA 


119 


46 


NA 


178 


71 


NA 


257 


103 


NA 


351 


143 


NA 


458 


188 


NA 


582 


246 


1,041 


853 


NA 


8 


NA 


80 


28 


NA 


130 


53 


NA 


193 


82 


NA 


279 


119 


NA 


384 


163 


NA 


501 


218 


724 


636 


278 


1,144 


937 


408 


10 


NA 


84 


31 


NA 


138 


56 


NA 


207 


90 


NA 


299 


131 


NA 


409 


177 


606 


538 


236 


776 


686 


302 


1,226 


1,010 


454 


15 


NA 


NA 


36 


NA 


152 


67 


NA 


233 


106 


NA 


334 


152 


523 


467 


212 


682 


611 


283 


874 


781 


365 


1,374 


1,156 


546 


20 


NA 


NA 


41 


NA 


NA 


75 


NA 


250 


122 


NA 


368 


172 


565 


508 


243 


742 


668 


325 


955 


858 


419 


1,513 


1,286 


648 


30 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


270 


137 


NA 


404 


198 


615 


564 


278 


816 


747 


381 


1,062 


969 


496 


1,702 


1,473 


749 


50 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


620 


328 


879 


831 


461 


1,165 


1,089 


606 


1,905 


1,692 


922 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm^, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W 



414 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



FUEL GAS 



TABLE G2428.3(4) [504.3(4)] 
MASONRY CHIMNEY 



Number of Appliances 


Two or more 


Appliance Type 


Category I 


Appliance Vent Connection 


Single-wall metal connector 



VENT CONNECTOR CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


CONNECTOR 
RISE 

(ff) 
(feet) 


SINGLE-WALL METAL VENT CONNECTOR DIAMETER (D)— inches 


3 


4 


5 


6 


7 


8 


9 


10 


APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU/H 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


FAN 


NAT 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


Min 


Max 


Max 


6 


1 


NA 


NA 


21 


NA 


NA 


39 


NA 


NA 


66 


179 


191 


100 


231 


271 


140 


292 


366 


200 


362 


474 


252 


499 


594 


316 


2 


NA 


NA 


28 


NA 


NA 


52 


NA 


NA 


84 


186 


227 


123 


239 


321 


172 


301 


432 


231 


373 


557 


299 


509 


696 


376 


3 


NA 


NA 


34 


NA 


NA 


61 


134 


153 


97 


193 


258 


142 


247 


365 


202 


309 


491 


269 


381 


634 


348 


519 


793 


437 


8 


1 


NA 


NA 


21 


NA 


NA 


40 


NA 


NA 


68 


195 


208 


103 


250 


298 


146 


313 


407 


207 


387 


530 


263 


529 


672 


331 


2 


NA 


NA 


28 


NA 


NA 


52 


137 


139 


85 


202 


240 


125 


258 


343 


177 


323 


465 


238 


397 


607 


309 


540 


766 


391 


3 


NA 


NA 


34 


NA 


NA 


62 


143 


156 


98 


210 


264 


145 


266 


376 


205 


332 


509 


274 


407 


663 


356 


551 


838 


450 


10 


1 


NA 


NA 


22 


NA 


NA 


41 


130 


151 


70 


202 


225 


106 


267 


316 


151 


333 


434 


213 


410 


571 


273 


558 


727 


343 


2 


NA 


NA 


29 


NA 


NA 


53 


136 


150 


86 


210 


255 


128 


276 


358 


181 


343 


489 


244 


420 


640 


317 


569 


813 


403 


3 


NA 


NA 


34 


97 


102 


62 


143 


166 


99 


217 


277 


147 


284 


389 


207 


352 


530 


279 


430 


694 


363 


580 


880 


459 


15 


1 


NA 


NA 


23 


NA 


NA 


43 


129 


151 


73 


199 


271 


112 


268 


376 


161 


349 


502 


225 


445 


646 


291 


623 


808 


366 


2 


NA 


NA 


30 


92 


103 


54 


135 


170 


88 


207 


295 


132 


277 


411 


189 


359 


548 


256 


456 


706 


334 


634 


884 


424 


3 


NA 


NA 


34 


96 


112 


63 


141 


185 


101 


215 


315 


151 


286 


439 


213 


368 


586 


289 


466 


755 


378 


646 


945 


479 


20 


1 


NA 


NA 


23 


87 


99 


45 


128 


167 


76 


197 


303 


117 


265 


425 


169 


345 


569 


235 


439 


734 


306 


614 


921 


347 


2 


NA 


NA 


30 


91 


111 


55 


134 


185 


90 


205 


325 


136 


274 


455 


195 


355 


610 


266 


450 


787 


348 


627 


986 


443 


3 


NA 


NA 


35 


96 


119 


64 


140 


199 


103 


213 


343 


154 


282 


481 


219 


365 


644 


298 


461 


831 


391 


639 


1,042 


496 



COMMON VENT CAPACITY 



VENT 
HEIGHT 

(H) 
(feet) 


MINIMUM INTERNAL AREA OF MASONRY CHIMNEY FLUE (square inches) 


12 


19 


28 


38 


50 


63 


78 


113 


COMBINED APPLIANCE INPUT RATING IN THOUSANDS OF BTU/H 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


FAN 
+FAN 


FAN 
+NAT 


NAT 
+NAT 


6 


NA 


NA 


25 


NA 


118 


45 


NA 


176 


71 


NA 


255 


102 


NA 


348 


142 


NA 


455 


187 


NA 


579 


245 


NA 


846 


NA 


8 


NA 


NA 


28 


NA 


128 


52 


NA 


190 


81 


NA 


276 


118 


NA 


380 


162 


NA 


497 


217 


NA 


633 


277 


1,136 


928 


405 


10 


NA 


NA 


31 


NA 


136 


56 


NA 


205 


89 


NA 


295 


129 


NA 


405 


175 


NA 


532 


234 


171 


680 


300 


1,216 


1,000 


450 


15 


NA 


NA 


36 


NA 


NA 


66 


NA 


230 


105 


NA 


335 


150 


NA 


400 


210 


677 


602 


280 


866 


772 


360 


1,359 


1,139 


540 


20 


NA 


NA 


NA 


NA 


NA 


74 


NA 


247 


120 


NA 


362 


170 


NA 


503 


240 


765 


661 


321 


947 


849 


415 


1,495 


1,264 


640 


30 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


135 


NA 


398 


195 


NA 


558 


275 


808 


739 


377 


1,052 


957 


490 


1,682 


1,447 


740 


50 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


NA 


612 


325 


NA 


821 


456 


1,152 


1,076 


600 


1,879 


1,672 


910 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm^, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



415 



FUEL GAS 



TABLE G2428.3.2 (504.3.2) 
MAXIMUM VENT CONNECTOR LENGTH 



CONNECTOR DIAMETER 


CONNECTOR HORIZONTAL 


Maximum 
(inches) 


Length 
(feet) 


3 


4.5 


4 


6 


5 


7.5 


6 


9 


7 


10.5 


8 


12 


9 


13.5 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

G2428.3.3 (504.3.3) Connectors with longer lengths. 

Connectors with longer horizontal lengths than those listed 
in Section G2428.3.2 are permitted under the following 
conditions: 

1 . The maximum capacity (FAN Max or NAT Max) of 
the vent connector shall be reduced 10 percent for 
each additional multiple of the length listed above. 
For example, the maximum length listed above for a 
4-inch (102 mm) connector is 6 feet (1 829 mm). With 
a connector length greater than 6 feet (1829 mm), but 
not exceeding 12 feet (3658 mm), the maximum 
capacity must be reduced by 10 percent (0.90 x maxi- 
mum vent connector capacity). With a connector 
length greater than 12 feet (3658 mm), but not 
exceeding 18 feet (5486 mm), the maximum capacity 
must be reduced by 20 percent (0.80 x maximum vent 
capacity). 

2. For a connector serving a fan-assisted appliance, the 
minimum capacity (FAN Min) of the connector shall 
be determined by referring to the corresponding sin- 
gle appliance table. For Type B double-wall connec- 
tors, Table 02428.2(1) shall be used. For single- wall 
connectors, Table G2428.2(2) shall be used. The 
height (H) and lateral (L) shall be measured according 
to the procedures for a single appliance vent, as if the 
other appliances were not present. 

G2428.3.4 (504.3.4) Vent connector manifold. Where the 
vent connectors are combined prior to entering the vertical 
portion of the common vent to form a common vent mani- 
fold, the size of the common vent manifold and the common 
vent shall be determined by applying a 10-percent reduction 
(0.90 X maximum common vent capacity) to the common 
vent capacity part of the common vent tables. The length of 
the common vent connector manifold (L^) shall not exceed 
1 V2 feet for each inch (457 mm per mm) of common vent con- 
nector manifold diameter (D) (see Appendix B Figure B- 1 1 ). 

G2428.3.5 (504.3.5) Common vertical vent offset. Where 
the common vertical vent is offset, the maximum capacity of 
the common vent shall be reduced in accordance with Sec- 
tion G2428.3.6. The horizontal length of the common vent 



offset (LJ shall not exceed 1 V2 feet for each inch (457 mm 
per mm) of common vent diameter. 

G2428.3.6 (504.3.6) Elbows in vents. For each elbow up to 
and including 45 degrees (0.79 rad) in the common vent, the 
maximum common vent capacity listed in the venting tables 
shall be reduced by 5 percent. For each elbow greater than 
45 degrees (0.79 rad) up to and including 90 degrees (1.57 
rad), the maximum common vent capacity listed in the vent- 
ing tables shall be reduced by 10 percent. 

G2428.3.7 (504.3.7) Elbows in connectors. The vent con- 
nector capacities listed in the common vent sizing tables 
include allowance for two 90-degree (1.57 rad) elbows. For 
each additional elbow up to and including 45 degrees (0.79 
rad), the maximum vent connector capacity listed in the 
venting tables shall be reduced by 5 percent. For each elbow 
greater than 45 degrees (0.79 rad) up to and including 90 
degrees (1.57 rad), the maximum vent connector capacity 
listed in the venting tables shall be reduced by 10 percent. 

G2428.3.8 (504.3.8) Common vent minimum size. The 

cross-sectional area of the common vent shall be equal to or 
greater than the cross-sectional area of the largest connector. 

G2428.3.9 (504.3.9) Common vent fittings. At the point 
where tee or wye fittings connect to a common vent, the 
opening size of the fitting shall be equal to the size of the 
common vent. Such fittings shall not be prohibited from 
having reduced-size openings at the point of connection of 
appliance vent connectors. 

G2428.3.9.1 (504.3.9.1) Tee and wye fittings. Tee and 

wye fittings connected to a common vent shall be consid- 
ered as part of the common vent and shall be constructed 
of materials consistent with that of the common vent. 

G2428.3.10 (504.3.10) High altitude installations. Sea- 
level input ratings shall be used when determining maxi- 
mum capacity for high altitude installation. Actual input, 
derated for altitude, shall be used for determining minimum 
capacity for high altitude installation. 

G2428.3.11 (504.3.11) Connector rise measurement. 

Connector rise (R) for each appliance connector shall be 
measured from the draft hood outlet or flue collar to the cen- 
terline where the vent gas streams come together. 

G2428.3.12 (504.3.12) Vent height measurement. For 

multiple appliances all located on one floor, available total 
height (H) shall be measured from the highest draft hood 
outlet or flue collar up to the level of the outlet of the com- 
mon vent. 

G2428.3.13 (504.3.17) Vertical vent maximum size. 

Where two or more appliances are connected to a vertical 
vent or chimney, the flow area of the largest section of verti- 
cal vent or chimney shall not exceed seven times the small- 
est listed appliance categorized vent areas, flue collar area, 
or draft hood outlet area unless designed in accordance with 
approved engineering methods. 

G2428.3.14 (504.3.18) Multiple input rate appliances. 

For appliances with more than one input rate, the minimum 
vent connector capacity (FAN Min) determined from the 
tables shall be less than the lowest appliance input rating. 



416 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



FUEL GAS 



and the maximum vent connector capacity (FAN Max or 
NAT Max) determined from the tables shall be greater than 
the highest appliance input rating. 

G2428.3.15 (504.3.19) Liner system sizing and connec- 
tions. Listed, corrugated metallic chimney liner systems in 
masonry chimneys shall be sized by using Table 
G2428.3(l) or G2428.3(2) for Type B vents, with the maxi- 
mum capacity reduced by 20 percent (0.80 x maximum 
capacity) and the minimum capacity as shown in Table 
G2428.3(l) or 02428.3(2). Corrugated metallic liner sys- 
tems installed with bends or offsets shall have their maxi- 
mum capacity further reduced in accordance with Sections 
G2428.3.5 and G2428.3.6. The 20-percent reduction for 
corrugated metallic chimney liner systems includes an 
allowance for one long-radius 90-degree (1.57 rad) turn at 
the bottom of the liner. Where double- wall connectors are 
required, tee and wye fittings used to connect to the com- 
mon vent chimney liner shall be listed double- wall fittings. 
Connections between chimney liners and listed double- wall 
fittings shall be made with listed adapter fittings designed 
for such purpose. 

G2428.3.16 (504.3.20) Chimney and vent location. 

Tables G2428.3(l), G2428.3(2), G2428.3(3) and 
G2428.3(4) shall only be used for chimneys and vents not 
exposed to the outdoors below the roof line. A Type B vent 
or listed chimney lining system passing through an unused 
masonry chimney flue shall not be considered to be exposed 
to the outdoors. A Type B vent shall not be considered to be 
exposed to the outdoors where it passes through an unventi- 
lated enclosure or chase insulated to a value of not less than 
R-8. 

Exception: Vents serving hsted appliances installed in 
accordance with the appliance manufacturer's installa- 
tion instructions. 

G2428.3.17 (504.3.21) Connector maximum and mini- 
mum size. Vent connectors shall not be increased in size 
more than two sizes greater than the listed appliance catego- 
rized vent diameter, flue collar diameter, or draft hood outlet 
diameter. Vent connectors for draft-hood-equipped appli- 
ances shall not be smaller than the draft hood outlet diame- 
ter. Where a vent connector size(s) determined from the 
tables for a fan-assisted appliance(s) is smaller than the flue 
collar diameter, the use of the smaller size(s) shall be per- 
mitted provided that the installation complies with all of the 
following conditions: 

1 . Vent connectors for fan-assisted appliance flue col- 
lars 12 inches (305 mm) in diameter or smaller are not 
reduced by more than one table size [e.g., 12 inches to 
10 inches (305 mm to 254 mm) is a one-size reduc- 
tion] and those larger than 12 inches (305 nmi) in 
diameter are not reduced more than two table sizes 
[e.g., 24 inches to 20 inches (610 mm to 508 mm) is a 
two-size reduction]. 

2. The fan-assisted appliance(s) is common vented with 
a draft-hood-equipped appliances(s). 

3. The vent connector has a smooth interior wall. 



G2428.3.18 (504.3.22) Component commingling. All 

combinations of pipe sizes, single-wall, and double-wall 
metal pipe shall be allowed within any connector run(s) or 
within the common vent, provided all of the appropriate 
tables permit all of the desired sizes and types of pipe, as if 
they were used for the entire length of the subject connector 
or vent. Where single-wall and Type B double-wall metal 
pipes are used for vent connectors within the same venting 
system, the common vent must be sized using Table 
G2428.3(2) or G2428.3(4), as appropriate. 

G2428.3.19 (504.3.23) Draft hood conversion accesso- 
ries. Draft hood conversion accessories for use with 
masonry chimneys venting listed Category I fan-assisted 
appliances shall be listed and installed in accordance with 
the manufacturer's installation instructions for such listed 
accessories. 

G2428.3.20 (504.3.24) Multiple sizes permitted. Where a 
table permits more than one diameter of pipe to be used for a 
connector or vent, all the permitted sizes shall be permitted 
to be used. 

G2428.3.21 (504.3.25) Table interpolation. Interpolation 
shall be permitted in calculating capacities for vent dimen- 
sions that fall between table entries. (See Example 3, 
Appendix B.) 

G2428.3.22 (504.3.26) Extrapolation prohibited. Extrap- 
olation beyond the table entries shall not be permitted. 

G2428.3.23 (504.3.27) Engineering calculations. For vent 
heights less than 6 feet ( 1 829 mm) and greater than shown in 
the tables, engineering methods shall be used to calculate 
vent capacities. 



SECTION G2429 (505) 

DIRECT-VENT, INTEGRAL VENT, MECHANICAL 

VENT AND VENTILATION/EXHAUST 

HOOD VENTING 

G2429.1 (505.1) General. The installation of direct- vent and 
integral vent appliances shall be in accordance with Section 
G2427. Mechanical venting systems shall be designed and 
installed in accordance with Section G2427. 



SECTION G2430 (506) 
FACTORY-BUILT CHIMNEYS 

G2430.1 (506.1) Listing. Factory-built chimneys for building 
heating appliances producing flue gases having a temperature 
not greater than 1,000°F (538°C), measured at the entrance to 
the chimney, shall be listed and labeled in accordance with UL 
103 and shall be installed and terminated in accordance with 
the manufacturer's installation instructions. 

G2430.2 (506.2) Support. Where factory-built chimneys are 
supported by structural members, such as joists and rafters, 
such members shall be designed to support the additional 
load. 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



417 



FUEL GAS 



SECTION G2431 (601) 
GENERAL 

G2431.1 (601.1) Scope. Sections G2432 through G2453 shall 
govern the approval, design, installation, construction, mainte- 
nance, alteration and repair of the appliances and equipment 
specifically identified herein. 



SECTION G2432 (602) 

DECORATIVE APPLIANCES FOR INSTALLATION 

IN FIREPLACES 

G2432.1 (602.1) General. Decorative appliances for installa- 
tion in approved solid fuel burning fireplaces shall be tested in 
accordance with ANSI Z21.60 and shall be installed in accor- 
dance with the manufacturer's installation instructions. Manu- 
ally lighted natural gas decorative appliances shall be tested in 
accordance with ANSI Z21.84. 

G2432.2 (602.2) Flame safeguard device. Decorative appli- 
ances for installation in approved solid fuel-burning fireplaces, 
with the exception of those tested in accordance with ANSI 
Z2 1 . 84, shall utilize a direct ignition device, an ignitor or a pilot 
flame to ignite the fuel at the main burner, and shall be 
equipped with a flame safeguard device. The flame safeguard 
device shall automatically shut off the fuel supply to a main 
burner or group of burners when the means of ignition of such 
burners becomes inoperative. 

G2432.3 (602.3) Prohibited installations. Decorative appli- 
ances for installation in fireplaces shall not be installed where 
prohibited by Secfion G2406.2. 



SECTION G2436 (608) 
VENTED WALL FURNACES 

G2436.1 (608.1) General. Vented wall furnaces shall be tested 
in accordance with ANSI Z21.86/CSA 2.32 and shall be 
installed in accordance with the manufacturer's installation 
instructions. 

G2436.2 (608.2) Venting. Vented wall furnaces shall be vented 
in accordance with Section G2427. 

G2436.3 (608.3) Location. Vented wall furnaces shall be 
located so as not to cause a fire hazard to walls, floors, combus- 
tible furnishings or doors. Vented wall furnaces installed 
between bathrooms and adjoining rooms shall not circulate air 
from bathrooms to other parts of the building. 

G2436.4 (608.4) Door swing. Vented wall furnaces shall be 
located so that a door cannot swing within 12 inches (305 mm) 
of an air inlet or air outlet of such furnace measured at right 
angles to the opening. Doorstops or door closers shall not be 
installed to obtain this clearance. 

G2436.5 (608.5) Ducts prohibited. Ducts shall not be 
attached to wall furnaces. Casing extension boots shall not be 
installed unless listed as part of the appliance. 

G2436.6 (608.6) Access. Vented wall furnaces shall be pro- 
vided with access for cleaning of heating surfaces, removal of 
burners, replacement of sections, motors, controls, filters and 
other working parts, and for adjustments and lubrication of 
parts requiring such attention. Panels, grilles and access doors 
that are required to be removed for normal servicing operations 
shall not be attached to the building construction. 



SECTION G2433 (603) 
LOG LIGHTERS 

G2433.1 (603.1) General. Log lighters shall be tested in accor- 
dance with CS A 8 and shall be installed in accordance with the 
manufacturer's installation instructions. 



SECTION G2434 (604) 

VENTED GAS FIREPLACES 

(DECORATIVE APPLIANCES) 

G2434.1 (604.1) General. Vented gas fireplaces shall be tested 
in accordance with ANSI Z21.50, shall be installed in accor- 
dance with the manufacturer's installation instructions and 
shall be designed and equipped as specified in Section 

G2432.2. 

G2434.2 (604.2) Access. Panels, grilles, and access doors that 
are required to be removed for normal servicing operations 
shall not be attached to the building. 



SECTION G2435 (605) 
VENTED GAS FIREPLACE HEATERS 

G2435.1 (605.1) General. Vented gas fireplace heaters shall 
be installed in accordance with the manufacturer's installation 
instructions, shall be tested in accordance with ANSI Z21.88 
and shall be designed and equipped as specified in Section 
G2432.2. 



SECTION G2437 (609) 
FLOOR FURNACES 

G2437.1 (609.1) General. Floor furnaces shall be tested in 
accordance with ANSI Z21 .86/CSA 2.32 and shall be installed 
in accordance with the manufacturer's installation instructions. 

G2437.2 (609.2) Placement. The following provisions apply 
to floor furnaces: 

1 . Floors. Floor furnaces shall not be installed in the floor of 
any doorway, stairway landing, aisle or passageway of 
any enclosure, public or private, or in an exitway from 
any such room or space. 

2. Walls and comers. The register of a floor furnace with a 
horizontal warm air outlet shall not be placed closer than 
6 inches (152 mm) to the nearest wall. A distance of at 
least 18 inches (457 mm) from two adjoining sides of the 
floor furnace register to walls shall be provided to elimi- 
nate the necessity of occupants walking over the warm 
air discharge. The remaining sides shall be permitted to 
be placed not closer than 6 inches (152 mm) to a wall. 
Wall-register models shall not be placed closer than 6 
inches (152 mm) to a comer. 

3. Draperies. The fumace shall be placed so that a door, 
drapery, or similar object cannot be nearer than 12 inches 
(305 mm) to any portion of the register of the fumace. 

4. Floor construction. Floor fumaces shall not be installed 
in concrete floor constmction built on grade. 



418 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



FUEL GAS 



5. Thermostat. The controlling thermostat for a floor fur- 
nace shall be located within the same room or space as 
the floor furnace or shall be located in an adjacent room 
or space that is permanently open to the room or space 
containing the floor furnace. 

G2437.3 (609.3) Bracing. The floor around the furnace shall 
be braced and headed with a support framework designed in 
accordance with Chapter 5. 

G2437.4 (609.4) Clearance. The lowest portion of the floor 
furnace shall have not less than a 6-inch (152 mm) clearance 
from the grade level; except where the lower 6-inch (152 mm) 
portion of the floor furnace is sealed by the manufacturer to 
prevent entrance of water, the minimum clearance shall be 
reduced to not less than 2 inches (51 mm). Where these clear- 
ances cannot be provided, the ground below and to the sides 
shall be excavated to form a pit under the furnace so that the 
required clearance is provided beneath the lowest portion of the 
furnace. A 12-inch (305 mm) minimum clearance shall be pro- 
vided on all sides except the control side, which shall have an 
18-inch (457 mm) minimum clearance. 

G2437.5 (609.5) First floor installation. Where the basement 
story level below the floor in which a floor furnace is installed 
is utihzed as habitable space, such floor furnaces shall be 
enclosed as specified in Section G2437.6 and shall project into 
a nonhabitable space. 

G2437.6 (609.6) Upper floor installations. Floor furnaces 
installed in upper stories of buildings shall project below into 
nonhabitable space and shall be separated from the 
nonhabitable space by an enclosure constructed of 
noncombustible materials. The floor furnace shall be provided 
with access, clearance to all sides and bottom of not less than 6 
inches (152 mm) and combustion air in accordance with Sec- 
tion G2407. 



SECTION G2438 (613) 
CLOTHES DRYERS 

G2438.1 (613.1) General. Clothes dryers shall be tested in 
accordance with ANSI Z21.5.1 and shall be installed in accor- 
dance with the manufacturer's installation instructions. 



SECTION 02439(614) 
CLOTHES DRYER EXHAUST 

G2439.1 (614.1) Installation. Clothes dryers shall be 
exhausted in accordance with the manufacturer's instructions. 
Dryer exhaust systems shall be independent of all other sys- 
tems and shall convey the moisture and any products of com- 
bustion to the outside of the building. 

G2439.2 (614.2) Duct penetrations. Ducts that exhaust 
clothes dryers shall not penetrate or be located within any 
fireblocking, draftstopping or any wall, floor/ceiling or other 
assembly required by this code to be fire-resistance rated, 
unless such duct is constructed of galvanized steel or aluminum 
of the thickness specified in the mechanical provisions of this 
code and the fire-resistance rating is maintained in accordance 
with this code. Fire dampers shall not be installed in clothes 
dryer exhaust duct systems. 



G2439.3 (614.4) Exhaust installation. Dryer exhaust ducts for 
clothes dryers shall terminate on the outside of the building and 
shall be equipped with a backdraft damper. Screens shall not be 
installed at the duct termination. Ducts shall not be connected or 
installed with sheet metal screws or other fasteners that will 
obstruct the flow. Clothes dryer exhaust ducts shall not be con- 
nected to a vent connector, vent or chimney. Clothes dryer 
exhaust ducts shall not extend into or through ducts or plenums. 

G2439.4 (614.5) Makeup air. Installations exhausting more 
than 200 cfm (0.09 m^/s) shall be provided with makeup air. 
Where a closet is designed for the installation of a clothes dryer, 
an opening having an area of not less than 100 square inches 
(0.0645 m^) for makeup air shall be provided in the closet enclo- 
sure, or makeup air shall be provided by other approved means. 

G2439.5 (614.6) Clothes dryer ducts. Exhaust ducts for 
domestic clothes dryers shall be constructed of metal and shall 
have a smooth interior finish. The exhaust duct shall be a mini- 
mum nominal size of 4 inches (102 mm) in diameter. The entire 
exhaust system shall be supported and secured in place. The 
male end of the duct at overlapped duct joints shall extend in 
the direction of airflow. Clothes dryer transition ducts used to 
connect the appliance to the exhaust duct system shall be metal 
and limited to a single length not to exceed 8 feet (2438 mm) in 
length and shall be listed and labeled for the application. Tran- 
sition ducts shall not be concealed within construction. 

G2439.5.1 (614.6.1) Maximum length. The maximum 
length of a clothes dryer exhaust duct shall not exceed 25 
feet (7620 mm) from the dryer location to the oudet termi- 
nal. The maximum length of the duct shall be reduced VI2 
feet (762 mm) for each 45 degree (0.79 rad) bend and 5 feet 
(1524 mm) for each 90 degree (1.6 rad) bend. 

Exception: Where the make and model of the clothes 
dryer to be installed is known and the manufacturer's 
installation instructions for such dryer are provided to 
the code official, the maximum length of the exhaust 
duct, including any transition duct, shall be permitted to 
be in accordance with the dryer manufacturer's installa- 
tion instructions. 

G2439.5.2 (614.6.2) Rough-in-required. Where a com- 
partment or space for a clothes dryer is provided, an exhaust 
duct system shall be installed. 



SECTION 02440(615) 
SAUNA HEATERS 

G2440.1 (615.1) General. Sauna heaters shall be installed in 
accordance with the manufacturer's installation instructions. 

G2440.2 (615.2) Location and protection. Sauna heaters 
shall be located so as to minimize the possibility of accidental 
contact by a person in the room. 

G2440.2.1 (615.2.1) Guards. Sauna heaters shall be pro- 
tected from accidental contact by an approved guard or bar- 
rier of material having a low coefficient of thermal 
conductivity. The guard shall not substantially affect the 
transfer of heat from the heater to the room. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



419 



FUEL GAS 



G2440.3 (615.3) Access. Panels, grilles and access doors that 
are required to be removed for normal servicing operations, 
shall not be attached to the building. 

G2440.4 (615.4) Combustion and dilution air intakes. 

Sauna heaters of other than the direct- vent type shall be 
installed with the draft hood and combustion air intake located 
outside the sauna room. Where the combustion air inlet and the 
draft hood are in a dressing room adjacent to the sauna room, 
there shall be provisions to prevent physically blocking the 
combustion air inlet and the draft hood inlet, and to prevent 
physical contact with the draft hood and vent assembly, or 
warning notices shall be posted to avoid such contact. Any 
warning notice shall be easily readable, shall contrast with its 
background, and the wording shall be in letters not less than 
0.25 inch (6.4 mm) high. 

G2440.5 (615.5) Combustion and ventilation air. Combus- 
tion air shall not be taken from inside the sauna room. Combus- 
tion and ventilation air for a sauna heater not of the direct- vent 
type shall be provided to the area in which the combustion air 
inlet and draft hood are located in accordance with Section 
G2407. 

G2440.6 (615.6) Heat and time controls. Sauna heaters shall 
be equipped with a thermostat which will limit room tempera- 
ture to 194°F (90°C). If the thermostat is not an integral part of 
the sauna heater, the heat-sensing element shall be located 
within 6 inches (152 mm) of the ceiling. If the heat-sensing ele- 
ment is a capillary tube and bulb, the assembly shall be attached 
to the wall or other support, and shall be protected against phys- 
ical damage. 

G2440.6.1 (615.6.1) Timers. A timer, if provided to control 
main burner operation, shall have a maximum operating 
time of 1 hour. The control for the timer shall be located out- 
side the sauna room. 

G2440.7 (615.7) Sauna room. A ventilation opening into the 
sauna room shall be provided. The opening shall be not less 
than 4 inches by 8 inches (102 mm by 203 mm) located near the 
top of the door into the sauna room. 



SECTION G2441 (617) 
POOL AND SPA HEATERS 

G2441.1 (617.1) General. Pool and spa heaters shall be tested 
in accordance with ANSI Z21.56 and shall be installed in 
accordance with the manufacturer's installation instructions. 



SECTION 02442(618) 
FORCED-AIR WARM-AIR FURNACES 

G2442.1 (618.1) General. Forced-air warm-air furnaces shall 
be tested in accordance with ANSI Z21 .47 or UL 795 and shall 
be installed in accordance with the manufacturer's installation 
instructions. 

G2442.2 (618.2) Forced-air furnaces. The minimum unob- 
structed total area of the outside and return air ducts or open- 
ings to a forced-air warm-air furnace shall be not less than 2 
square inches for each 1,000 Btu/h (4402 mm^AV) output rat- 
ing capacity of the furnace and not less than that specified in the 



furnace manufacturer's installation instructions. The minimum 
unobstructed total area of supply ducts from a forced-air 
warm-air furnace shall be not less than 2 square inches for each 
1,000 Btu/h (4402 mm^AV) output rating capacity of the fur- 
nace and not less than that specified in the furnace manufac- 
turer's installation instructions. 

Exception: The total area of the supply air ducts and outside 
and return air ducts shall not be required to be larger than the 
minimum size required by the furnace manufacturer's 
installation instructions. 

G2442.3 (618.3) Dampers. Volume dampers shall not be 
placed in the air inlet to a furnace in a manner that will reduce 
the required air to the furnace. 

G2442.4 (618.4) Circulating air ducts for forced-air 
warm-air furnaces. Circulating air for forced-air-type, 
warm-air furnaces shall be conducted into the blower housing 
from outside the furnace enclosure by continuous air-tight 
ducts. 

G2442.5 (618.5) Prohibited sources. Outside or return air for 
a forced-air heating system shall not be taken from the follow- 
ing locations: 

1. Closer than 10 feet (3048 mm) from an appliance vent 
outlet, a vent opening from a plumbing drainage system 
or the discharge outlet of an exhaust fan, unless the outlet 
is 3 feet (914 mm) above the outside air inlet. 

2. Where there is the presence of objectionable odors, 
fumes or flammable vapors; or where located less than 
10 feet (3048 mm) above the surface of any abutting pub- 
lic way or driveway; or where located at grade level by a 
sidewalk, street, alley or driveway. 

3. A room or space, the volume of which is less than 25 per- 
cent of the entire volume served by such system. Where 
connected by a permanent opening having an area sized 
in accordance with Section G2442.2, adjoining rooms or 
spaces shall be considered as a single room or space for 
the purpose of determining the volume of such rooms or 
spaces. 

Exception: The minimum volume requirement shall 
not apply where the amount of return air taken from a 
room or space is less than or equal to the amount of 
supply air delivered to such room or space. 

4. A room or space containing an appliance where such a 
room or space serves as the sole source of return air. 

Exception: This shall not apply where: 

1 . The appliance is a direct-vent appliance or an 
appliance not requiring a vent in accordance 
with Section G2425.8. 

2. The room or space complies with the following 
requirements: 

2.1. The return air shall be taken from a 
room or space having a volume exceed- 
ing 1 cubic foot (28 316.85 mm^) for 
each 10 Btu/h (9.6 L/W) of combined 
input rating of all fuel-burning appli- 
ances therein. 



420 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



FUEL GAS 



2.2. The volume of supply air discharged 
back into the same space shall be 
approximately equal to the volume of 
return air taken from the space. 

2.3. Return-air inlets shall not be located 
within 10 feet (3048 mm) of any appli- 
ance firebox or draft hood in the same 
room or space. 

3. Rooms or spaces containing solid-fuel burning 
appliances, provided that return-air inlets are 
located not less than 10 feet (3048 mm) from 
the firebox of such appliances. 

5. A closet, bathroom, toilet room, kitchen, garage, 
mechanical room, boiler room or furnace room. 

G2442.6 (618.6) Screen. Required outdoor air inlets shall be 
covered with a screen having V4-inch (6.4 mm) openings. 
Required outdoor air inlets serving a nonresidential portion of 
a building shall be covered with screen having openings larger 
than 74 inch (6.4 mm) and not larger than 1 inch (25 mm). 

G2442.7 (618.7) Return-air limitation. Return air from one 
dwelling unit shall not be discharged into another dwelUng unit. 



SECTION G2443 (619) 
CONVERSION BURNERS 

G2443.1 (619.1) Conversion burners. The installation of con- 
version burners shall conform to ANSI Z21.8. 



SECTION G2444 (620) 
UNIT HEATERS 

G2444.1 (620.1) General. Unit heaters shall be tested in accor- 
dance with ANSI Z83.8 and shall be installed in accordance 
with the manufacturer's installation instructions. 

G2444.2 (620.2) Support. Suspended-type unit heaters shall 
be supported by elements that are designed and constructed to 
accommodate the weight and dynamic loads. Hangers and 
brackets shall be of noncombustible material. 

G2444.3 (620.3) Ductwork. Ducts shall not be connected to a 
unit heater unless the heater is listed for such installation. 

G2444.4 (620.4) Clearance. Suspended-type unit heaters 
shall be installed with clearances to combustible materials of 
not less than 18 inches (457 mm) at the sides, 12 inches (305 
mm) at the bottom and 6 inches (152 mm) above the top where 
the unit heater has an internal draft hood or 1 inch (25 mm) 
above the top of the sloping side of the vertical draft hood. 

Floor-mounted-type unit heaters shall be installed with 
clearances to combustible materials at the back and one side 
only of not less than 6 inches (152 mm). Where the flue gases 
are vented horizontally, the 6-inch (152 mm) clearance shall be 
measured from the draft hood or vent instead of the rear wall of 
the unit heater. Floor-mounted-type unit heaters shall not be 
installed on combustible floors unless listed for such installa- 
tion. 

Clearance for servicing all unit heaters shall be in accor- 
dance with the manufacturer's installation instructions. 



Exception: Unit heaters listed for reduced clearance shall 
be permitted to be installed with such clearances in accor- 
dance with their listing and the manufacturer's instructions. 



SECTION 02445(621) 
UNVENTED ROOM HEATERS 

G2445.1 (621.1) General. Unvented room heaters shall be 
tested in accordance with ANSI Z 21 . 1 1 .2 and shall be installed 
in accordance with the conditions of the listing and the manu- 
facturer's installation instructions. 

G2445.2 (621.2) Prohibited use. One or more unvented room 
heaters shall not be used as the sole source of comfort heating 
in a dwelling unit. 

G2445.3 (621.3) Input rating. Unvented room heaters shall 
not have an input rating in excess of 40,000 Btu/h (11.7 kW). 

G2445.4 (621.4) Prohibited locations. The location of 
unvented room heaters shall comply with Section G2406.2. 

G2445.5 (621.5) Room or space volume. The aggregate input 
rating of all unvented appliances installed in a room or space 
shall not exceed 20 Btu/h per cubic foot (0.21 kW/m^) of vol- 
ume of such room or space. Where the room or space in which 
the equipment is installed is directly connected to another room 
or space by a doorway, archway or other opening of compara- 
ble size that cannot be closed, the volume of such adjacent 
room or space shall be permitted to be included in the calcula- 
tions. 

G2445.6 (621.6) Oxygen-depletion safety system. Unvented 
room heaters shall be equipped with an oxygen-depletion-sen- 
sitive safety shutoff system. The system shall shut off the gas 
supply to the main and pilot burners when the oxygen in the 
surrounding atmosphere is depleted to the percent concentra- 
tion specified by the manufacturer, but not lower than 18 per- 
cent. The system shall not incorporate field adjustment means 
capable of changing the set point at which the system acts to 
shut off the gas supply to the room heater. 

G2445.7 (621.7) Unvented decorative room heaters. An 

unvented decorative room heater shall not be installed in a fac- 
tory-built fireplace unless the fireplace system has been specif- 
ically tested, listed and labeled for such use in accordance with 
UL 127. 

G2445.7.1 (621.7.1) Ventless firebox enclosures. Ventiess 
firebox enclosures used with unvented decorative room 
heaters shall be listed as complying with ANSI Z21.91. 



SECTION G2446 (622) 
VENTED ROOM HEATERS 

G2446.1 (622.1) General. Vented room heaters shall be tested 
in accordance with ANSI Z21.86/CSA 2.32, shall be designed 
and equipped as specified in Section G2432.2 and shall be 
installed in accordance with the manufacturer's installation 
instructions. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



421 



FUEL GAS 



SECTION G2447 (623) 
COOKING APPLIANCES 

G2447.1 (623.1) Cooking appliances. Cooking appliances 
that are designed for permanent installation, including ranges, 
ovens, stoves, broilers, grills, fryers, griddles, hot plates and 
barbecues, shall be tested in accordance with ANSI Z21.1 or 
ANSI Z21.58 and shall be installed in accordance with the 
manufacturer's installation instructions. 

G2447.2 (623.2) Prohibited location. Cooking appliances 
designed, tested, listed and labeled for use in commercial occu- 
pancies shall not be installed within dwelling units or within 
any area where domestic cooking operations occur. 

G2447.3 (623.3) Domestic appliances. Cooking appliances 
installed within dwelling units and within areas where domes- 
tic cooking operations occur shall be listed and labeled as 
household-type appliances for domestic use. 

G2447.4 (623.4) Range installation. Ranges installed on 
combustible floors shall be set on their own bases or legs and 
shall be installed with clearances of not less than that shown on 
the label. 



SECTION G2448 (624) 
WATER HEATERS 

G2448.1 (624.1) General. Water heaters shall be tested in 
accordance with ANSI Z 21 . 10. 1 and ANSI Z 21. 10.3 and shall 
be installed in accordance with the manufacturer's installation 
instructions. 

G2448.1.1 (624.1.1) Installation requirements. The 

requirements for water heaters relative to sizing, relief 
valves, drain pans and scald protection shall be in accor- 
dance with this code. 

G2448.2 (624.2) Water heaters utilized for space heating. 

Water heaters utilized both to supply potable hot water and pro- 
vide hot water for space-heating applications shall be listed and 
labeled for such applications by the manufacturer and shall be 
installed in accordance with the manufacturer's installation 
instructions and this code. 



SECTION G2449 (627) 
AIR CONDITIONING EQUIPMENT 

G2449.1 (627.1) General. Air conditioning equipment shall 
be tested in accordance with ANSI Z21 .40. 1 or ANSI Z21 .40.2 
and shall be installed in accordance with the manufacturer's 
installation instructions. 

G2449.2 (627.2) Independent piping. Gas piping serving 
heating equipment shall be permitted to also serve cooling 
equipment where such heating and cooling equipment cannot 
be operated simultaneously. (See Section G2413.) 

G2449.3 (627.3) Connection of gas engine-powered air con- 
ditioners. To protect against the effects of normal vibration in 
service, gas engines shall not be rigidly connected to the gas 
supply piping. 

G2449.4 (627.6) Installation. Air conditioning equipment 
shall be installed in accordance with the manufacturer's 



instructions. Unless the equipment is listed for installation on a 
combustible surface such as a floor or roof, or unless the sur- 
face is protected in an approved manner, equipment shall be 
installed on a surface of noncombustible construction with 
noncombustible material and surface finish and with no com- 
bustible material against the underside thereof. 



SECTION G2450 (628) 
ILLUMINATING APPLIANCES 

G2450.1 (628.1) General. Illuminating appliances shall be 
tested in accordance with ANSI Z21.42 and shall be installed 
in accordance with the manufacturer's installation instruc- 
tions. 

G2450.2 (628.2) Mounting on buildings. Illuminating appU- 
ances designed for wall or ceiling mounting shall be securely 
attached to substantial structures in such a manner that they are 
not dependent on the gas piping for support. 

G2450.3 (628.3) Mounting on posts. Illuminating appliances 
designed for post mounting shall be securely and rigidly 
attached to a post. Posts shall be rigidly mounted. The strength 
and rigidity of posts greater than 3 feet (914 mm) in height shall 
be at least equivalent to that of a 2.5-inch-diameter (64 mm) 
post constructed of 0.064-inch-thick (1.6 mm) steel or a 1-inch 
(25 mm) Schedule 40 steel pipe. Posts 3 feet (914 mm) or less 
in height shall not be smaller than V4-inch (19.1 mm) Schedule 
40 steel pipe. Drain openings shall be provided near the base of 
posts where there is a possibility of water collecting inside 
them. 

G2450.4 (628.4) Appliance pressure regulators. Where an 
appliance pressure regulator is not supplied with an illuminat- 
ing appliance and the service line is not equipped with a ser- 
vice pressure regulator, an appliance pressure regulator shall 
be installed in the line to the illuminating appliance. For mul- 
tiple installations, one regulator of adequate capacity shall be 
permitted to serve more than one illuminating appliance. 



SECTION G2451 (630) 
INFRARED RADIANT HEATERS 

G2451.1 (630.1) General. Infrared radiant heaters shall be 
tested in accordance with ANSI Z 83.6 and shall be installed 
in accordance with the manufacturer's installation instruc- 
tions. 

G2451.2 (630.2) Support. Infrared radiant heaters shall be 
fixed in a position independent of gas and electric supply lines. 
Hangers and brackets shall be of noncombustible material. 



SECTION 02452(631) 
BOILERS 

G2452.1 (631.1) Standards. Boilers shall be listed in accor- 
dance with the requirements of ANSI Z21.13 or UL 795. If 
applicable, the boiler shall be designed and constructed in 
accordance with the requirements of ASME CSD-1 and as 
applicable, the ASME Boiler and Pressure Vessel Code, Sec- 
tions I, II, IV, V and IX and NFPA 85. 



422 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



FUEL GAS 



G2452.2 (631.2) Installation. In addition to the requirements 
of this code, the installation of boilers shall be in accordance 
with the manufacturer's instructions and this code. Operating 
instructions of a permanent type shall be attached to the boiler. 
Boilers shall have all controls set, adjusted and tested by the 
installer. A complete control diagram together with complete 
boiler operating instructions shall be furnished by the installer. 
The manufacturer's rating data and the nameplate shall be 
attached to the boiler. 

G2452.3 (631.3) Clearance to combustible material. Clear- 
ances to combustible materials shall be in accordance with Sec- 
tion G2409.4. 



SECTION G2453 (634) 
CHIMNEY DAMPER OPENING AREA 

G2453.1 (634.1) Free opening area of chimney dampers. 

Where an unlisted decorative appliance for installation in a 
vented fireplace is installed, the fireplace damper shall have a 
permanent free opening equal to or greater than specified in 
Table G2453.1. 



TABLE G2453.1 (634.1) 

FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING FLUE GASES 

FROM UNLISTED DECORATIVE APPLIANCES FOR INSTALLATION IN VENTED FIREPLACES 



CHIMNEY HEIGHT 
(feet) 


IWINIWIUM PERMANENT FREE OPENING 
(square inches)^ 


8 


13 


20 


29 


39 


51 


64 


Appliance input rating (Btu per hour) 


6 


7,800 


14,000 


23,200 


34,000 


46,400 


62,400 


80,000 


8 


8,400 


15,200 


25,200 


37,000 


50,400 


68,000 


86,000 


10 


9,000 


16,800 


27,600 


40,400 


55,800 


74,400 


96,400 


15 


9,800 


18,200 


30,200 


44,600 


62,400 


84,000 


108,800 


20 


10,600 


20,200 


32,600 


50,400 


68,400 


94,000 


122,200 


30 


11,200 


21,600 


36,600 


55,200 


76,800 


105,800 


138,600 



For SI: 1 foot = 304.8 mm, 1 square inch = 645.16 mii^, 1,000 Btu per hour = 0.293 kW. 

a. The first six minimum permanent free openings (8 square inches to 51 square inches) correspond approximately to the cross-sectional areas of chimneys having 
diameters of 3 inches through 8 inches, respectively. The 64-square inch opening corresponds to the cross-sectional area of standard 8-inch by 8-inch chimney tile. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



423 



424 2006 INTERNATIONAL RESIDENTIAL CODE^ 



Part VII — Plumbing 



CHAPTER 25 

PLUMBING ADMINISTRATION 



SECTION P2501 
GENERAL 

P2501.1 Scope. The provisions of this chapter shall establish 
the general administrative requirements applicable to plumb- 
ing systems and inspection requirements of this code. 

P2501.2 Application. In addition to the general administration 
requirements of Chapter 1, the administrative provisions of this 
chapter shall also apply to the plumbing requirements of Chap- 
ters 25 through 32. 



SECTION P2502 
EXISTING PLUMBING SYSTEMS 

P2502.1 Existing building sewers and drains. Existing 
building sewers and drains shall be used in connection with 
new systems when found by examination and/or test to con- 
form to the requirements prescribed by this document. 

P2502.2 Additions, alterations or repairs. Additions, alter- 
ations, renovations or repairs to any plumbing system shall 
conform to that required for a new plumbing system without 
requiring the existing plumbing system to comply with all the 
requirements of this code. Additions, alterations or repairs 
shall not cause an existing system to become unsafe, insanitary 
or overloaded. 

Minor additions, alterations, renovations and repairs to 
existing plumbing systems shall be permitted in the same man- 
ner and arrangement as in the existing system, provided that 
such repairs or replacement are not hazardous and are 
approved. 



SECTION P2503 
INSPECTION AND TESTS 

P2503.1 Inspection required. New plumbing work and parts 
of existing systems affected by new work or alterations shall be 
inspected by the building official to ensure compliance with the 
requirements of this code. 

P2503.2 Concealment. A plumbing or drainage system, or 
part thereof, shall not be covered, concealed or put into use 
until it has been tested, inspected and approved by the building 
official. 

P2503.3 Responsibility of permittee. Test equipment, materi- 
als and labor shall be furnished by the permittee. 

P2503.4 Building sewer testing. The building sewer shall be 
tested by insertion of a test plug at the point of connection with 
the public sewer and filling the building sewer with water, test- 
ing with not less than a 1 0-foot (3048 mm) head of water and be 
able to maintain such pressure for 15 minutes. 



P2503.5 DWV systems testing. Rough and finished plumbing 
installations shall be tested in accordance with Sections 
P2503.5.1andP2503.5.2. 

P2503.5.1 Rough plumbing. DWV systems shall be tested 
on completion of the rough piping installation by water or 
air with no evidence of leakage. Either test shall be applied 
to the drainage system in its entirety or in sections after 
rough piping has been installed, as follows: 

1 . Water test. Each section shall be filled with water to a 
point not less than 10 feet (3048 mm) above the high- 
est fitting connection in that section, or to the highest 
point in the completed system. Water shall be held in 
the section under test for a period of 15 minutes. The 
system shall prove leak free by visual inspection. 

2. Air test. The portion under test shall be maintained at 
a gauge pressure of 5 pounds per square inch (psi) (34 
kPa) or 10 inches of mercury column (34 kPa). This 
pressure shall be held without introduction of addi- 
tional air for a period of 15 minutes. 

P2503.5.2 Finished plumbing. After the plumbing fixtures 
have been set and their traps filled with water, their connec- 
tions shall be tested and proved gas tight and/or water tight 
as follows: 

1. Water tightness. Each fixture shall be filled and then 
drained. Traps and fixture connections shall be 
proven water tight by visual inspection. 

2. Gas tightness. When required by the local administra- 
tive authority, a final test for gas tightness of the 
DWV system shall be made by the smoke or pepper- 
mint test as follows: 

2.1. Smoke test. Introduce a pungent, thick smoke 
into the system. When the smoke appears at 
vent terminals, such terminals shall be sealed 
and a pressure equivalent to a 1-inch water 
column (249 Pa) shall be applied and main- 
tained for a test period of not less than 15 min- 
utes. 

2.2. Peppermint test. Introduce 2 ounces (59 mL) 
of oil of peppermint into the system. Add 10 
quarts (9464 mL) of hot water and seal all vent 
terminals. The odor of peppermint shall not be 
detected at any trap or other point in the sys- 
tem. 

P2503.6 Water-supply system testing. Upon completion of 
the water-supply system or a section of it, the system or portion 
completed shall be tested and proved tight under a water pres- 
sure of not less than the working pressure of the system or, for 
piping systems other than plastic, by an air test of not less than 



2006 INTERNATIONAL RESIDENTIAL CODE® 



425 



I 



PLUMBING ADMINISTRATION 



50 psi (345 kPa). This pressure shall be held for not less than 15 
minutes. The water used for tests shall be obtained from a pota- 
ble water source. 

P2503.7 Inspection and testing of backflow prevention 
devices. Inspection and testing of backflow prevention devices 
shall comply with Sections P2503.7.1 and P2503.7.2. 

P2503.7.1 Inspections. Inspections shall be made of all 
backflow prevention assemblies to determine whether they 
are operable. 

P2503.7.2 Testing. Reduced pressure principle backflow 
preventers, double check valve assemblies, double-detector 
check valve assemblies and pressure vacuum breaker 
assemblies shall be tested at the time of installation, imme- 
diately after repairs or relocation and at least annually. 

P2503.8 Test gauges. Gauges used for testing shall be as fol- 
lows: 

1. Tests requiring a pressure of 10 psi or less shall utilize a 
testing gauge having increments of 0.10 psi (0.69 kPa) or 
less. 

2. Tests requiring a pressure higher than 10 psi (0.69 kPa) 
but less than or equal to 100 psi (690 kPa) shall use a test- 
ing gauge having increments of 1 psi (6.9 kPa) or less. 

3. Tests requiring a pressure higher than 100 psi (690 kPa) 
shall use a testing gauge having increments of 2 psi ( 14 kPa) 
or less. 



426 2006 INTERNATIONAL RESIDENTIAL CODE'^ 



CHAPTER 26 

GENERAL PLUMBING REQUIREMENTS 



SECTION P2601 
GENERAL 

P2601.1 Scope. The provisions of this chapter shall govern the 
installation of plumbing not specifically covered in other chap- 
ters applicable to plumbing systems. The installation of plumb- 
ing, appliances, equipment and systems not addressed by this 
code shall comply with the applicable provisions of the Inter- 
national Plumbing Code. 

P2601.2 Connection. Plumbing fixtures, drains and appli- 
ances used to receive or discharge liquid wastes or sewage shall 
be connected to the sanitary drainage system of the building or 
premises in accordance with the requirements of this code. 
This section shall not be construed to prevent indirect waste 
systems. 

P2601.3 Flood hazard area. In areas prone to flooding as 
established by Table R301 .2(1), plumbing fixtures, drains, and 
appliances shall be located or installed in accordance with Sec- 
tion R324. 1.5. 



SECTION P2602 

INDIVIDUAL WATER SUPPLY AND SEWAGE 

DISPOSAL 

P2602.1 General. The water-distribution and drainage system 
of any building or premises where plumbing fixtures are 
installed shall be connected to a public water supply or sewer 
system, respectively, if available. When either a public 
water-supply or sewer system, or both, are not available, or 
connection to them is not feasible, an individual water supply 
or individual (private) sewage-disposal system, or both, shall 
be provided. 

P2602.2 Flood-resistant installation. In areas prone to flood- 
ing as established by Table R301.2(l): 

1. Water supply systems shall be designed and constructed 
to prevent infiltration of floodwaters. 

2. Pipes for sewage disposal systems shall be designed and 
constructed to prevent infiltration of floodwaters into the 
systems and discharges from the systems into flood- 
waters. 



SECTION P2603 
STRUCTURAL AND PIPING PROTECTION 

P2603.1 General. In the process of installing or repairing any 
part of a plumbing and drainage installation, the finished 
floors, walls, ceilings, tile work or any other part of the building 
or premises that must be changed or replaced shall be left in a 
safe structural condition in accordance with the requirements 
of the building portion of this code. 

P2603.2 Drilling and notching. Wood-framed structural 
members shall not be drilled, notched or altered in any manner 
except as provided in Sections R502.8, R602.5, R602.6, 



R802.7 and R802.7.1. Holes in cold-formed steel-framed 
load-bearing members shall be permitted only in accordance 
with Sections R505.2, R603.2 and R804.2. In accordance with 
the provisions of Sections R603.3.4 and R804.3.5 cutting and 
notching of flanges and lips of cold-formed steel-framed 
load-bearing members shall not be permitted. 

P2603.2.1 Protection against physical damage. In con- 
cealed locations, where piping, other than cast-iron or gal- 
vanized steel, is installed through holes or notches in studs, 
joists, rafters or similar members less than 1.5 inches (38 
mm) from the nearest edge of the member, the pipe shall be 
protected by shield plates. Protective shield plates shall be a 
minimum of 0.062-inch-thick (1.6 mm) steel, shall cover 
the area of the pipe where the member is notched or bored 
and shall extend a minimum of 2 inches (5 1 mm) above sole 
plates and below top plates. 

P2603.3 Breakage and corrosion. Pipes passing through or 
under walls shall be protected from breakage. Pipes passing 
through concrete or cinder walls and floors, cold-formed steel 
framing or other corrosive material shall be protected against 
external corrosion by a protective sheathing or wrapping or 
other means that will withstand any reaction from lime and acid 
of concrete, cinder or other corrosive material. Sheathing or 
wrapping shall allow for expansion and contraction of piping to 
prevent any rubbing action. Minimum wall thickness of mate- 
rial shall be 0.025 inch (0.64 nrni). 

P2603.4 Sleeves. Annular spaces between sleeves and pipes 
shall be filled or tightly caulked as approved by the building 
official. Annular spaces between sleeves and pipes in fire-rated 
assemblies shall be filled or tightly caulked in accordance with 
the building portion of this code. 

P2603.5 Pipes through footings or foundation walls. Any 

pipe that passes under a footing or through a foundation wall 
shall be provided with a relieving arch; or there shall be built 
into the masonry wall a pipe sleeve two pipe sizes greater than 
the pipe passing through. 

P2603.6 Freezing. In localities having a winter design temper- 
ature of 32°F (0°C) or lower as shown in Table R301.2(l) of 
this code, a water, soil or waste pipe shall not be installed out- 
side of a building, in exterior walls, in attics or crawl spaces, or 
in any other place subjected to freezing temperature unless ade- 
quate provision is made to protect it from freezing by insulation 
or heat or both. Water service pipe shall be installed not less 
than 12 inches (305 mm) deep and not less than 6 inches (152 
mm) below the frost line. 

P2603.6.1 Sewer depth. Building sewers that connect to 
private sewage disposal systems shall be a minimum of 
[NUMBER] inches (mm) below finished grade at the point of 
septic tank connection. Building sewers shall be a minimum 
of [NUMBER] inches (mm) below grade. 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



427 



GENERAL PLUMBING REQUIREMENTS 



SECTION P2604 
TRENCHING AND BACKFILLING 

P2604.1 Trenching and bedding. Where trenches are excavated 
such that the bottom of the trench forms the bed for the pipe, soUd 
and continuous load-bearing support shall be provided between 
joints. Where over-excavated, the trench shall be backfilled to the 
proper grade with compacted earth, sand, fine gravel or similar 
granular material. Piping shall not be supported on rocks or blocks 
at any point. Rocky or unstable soil shall be over-excavated by two 
or more pipe diameters and brought to the proper grade with suit- 
able compacted granular material. 

P2604.2 Common trench. See Section P2904.4.2. 

P2604.3 Backfilling. Backfill shall be free from discarded 
construction material and debris. Backfill shall be free from 
rocks, broken concrete and frozen chunks until the pipe is cov- 
ered by at least 12 inches (305 mm) of tamped earth. Backfill 
shall be placed evenly on both sides of the pipe and tamped to 
retain proper alignment. Loose earth shall be carefully placed 
in the trench in 6-inch (152 mm) layers and tamped in place. 

P2604.4 Protection of footings. Trenching installed parallel to 
footings shall not extend below the 45-degree (0.79 rad) bearing 
plane of the bottom edge of a wall or footing (see Figure P2604.4). 



\\v //// W^y/P/// AW y// N\\\v// \\v 
y// \\\' y// WW/// \\\^ //// 



y//Awv//\\v 




INSTALL PIPES 
ABOVE THIS LINE 



For SI: 1 degree = 0.018 rad. 

FIGURE P2604.4 
PIPE LOCATION WITH RESPECT TO FOOTINGS 



SECTION P2605 
SUPPORT 

P2605.1 General. Piping shall be supported in accordance 
with the following: 

1 . Piping shall be supported to ensure alignment and pre- 
vent sagging, and allow movement associated with the 
expansion and contraction of the piping system. 

2. Piping in the ground shall be laid on a firm bed for its 
entire length, except where support is otherwise pro- 
vided. 



3. Hangers and anchors shall be of sufficient strength to 
maintain their proportional share of the weight of pipe 
and contents and of sufficient width to prevent distortion 
to the pipe. Hangers and strapping shall be of approved 
material that will not promote galvanic action. Rigid sup- 
port sway bracing shall be provided at changes in direc- 
tion greater than 45 degrees (0.79 rad) for pipe sizes 4 
inches (102 mm) and larger. 

4. Piping shall be supported at distances not to exceed those 
indicated in Table P2605.1. 



SECTION P2606 
WATERPROOFING OF OPENINGS 

P2606.1 General. Roof and exterior wall penetrations shall be 
made water tight. Joints at the roof, around vent pipes, shall be 
made water tight by the use of lead, copper or galvanized iron 
flashings or an approved elastomeric material. Counterflashing 
shall not restrict the required internal cross-sectional area of 
any vent. 



SECTION P2607 
WORKMANSHIP 

P2607.1 General. Valves, pipes and fittings shall be installed 
in correct relationship to the direction of the flow. Burred ends 
shall be reamed to the full bore of the pipe. 



SECTION P2608 
MATERIALS EVALUATION AND LISTING 

P2608.1 Identification. Each length of pipe and each pipe fit- 
ting, trap, fixture, material and device used in a plumbing sys- 
tem shall bear the identification of the manufacturer. 

P2608.2 Installation of materials. All materials used shall be 
installed in strict accordance with the standards under which 
the materials are accepted and approved. In the absence of such 
installation procedures, the manufacturer's installation instruc- 
tions shall be followed. Where the requirements of referenced 
standards or manufacturer's installation instmctions do not 
conform to the minimum provisions of this code, the provi- 
sions of this code shall apply. 

P2608.3 Plastic pipe, fittings and components. All plastic 
pipe, fittings and components shall be third-party certified as 
conforming to NSF 14. 

P2608.4 Third-party testing and certification. All plumbing 
products and materials shall comply with the referenced stan- 
dards, specifications and performance criteria of this code and 
shall be identified in accordance with Section P2608.1. Where 
required by Table P2608.4, plumbing products and materials 
shall either be tested by an approved third-party testing agency 
or certified by an approved third-party certification agency. 

F2608.5 Water supply systems. Water service pipes, water 
distribution pipes and the necessary connecting pipes, fittings, 
control valves, faucets and all appurtenances used to dispense 
water intended for human ingestion shall be evaluated and 
listed as conforming to the requirements of NSF 61. 



428 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



GENERAL PLUMBING REQUIREMENTS 



TABLE P2605.1 
PIPING SUPPORT 



PIPING MATERIAL 


MAXIMUM HORIZONTAL 
SPACING (feet) 


MAXIMUM VERTICAL 
SPACING 


ABS pipe 


4 


10'' 


Aluminum tubing 


10 


15 


Brass pipe 


10 


10 


Cast-iron pipe 


5^ 


15 


Copper or copper alloy pipe 


12 


10 


Copper or copper alloy tubing (V/^ inch diameter and smaller) 


6 


10 


Copper or copper alloy tubing {V/2 inch diameter and larger) 


10 


10 


Cross-linked polyethylene (PEX) pipe 


2.67 (32 inches) 


10'' 


Cross-linked polyethylene/aluminum/cross-Unked polyethylene (PEX-AL-PEX) pipe 


2.67 (32 inches) 


4b 


CPVC pipe or tubing (1 inch in diameter and smaller) 


3 


10'' 


CPVC pipe or tubing (1 V4 inch in diameter and larger) 


4 


10" 


Lead pipe 


Continuous 


4 


PB pipe or tubing 


2.67 (32 inches) 


4 


Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe 


2.67 (32 inches) 


4" 


Polypropylene (PP) pipe or tubing 1 inch and smaller 


2.67 (32 inches) 


10" 


Polypropylene (PP) pipe or tubing, 1 V4 inches and larger 


4 


10" 


PVC pipe 


4 


10" 


Stainless steel drainage systems 


10 


10" 


Steel pipe 


12 


15 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed. 

b. Midstory guide for sizes 2 inches and smaller. 



TABLE P2608.4 
PRODUCTS AND MATERIALS REQUIRING THIRD-PARTY TESTING AND THIRD-PARTY CERTIFICATION 



PRODUCT OR MATERIAL 


THIRD-PARTY CERTIFIED 


THIRD-PARTY TESTED 


Backflow prevention devices 


Required 





Plumbing appliance 


Required 





Plumbing fixtures 





Required 


Potable water supply system components and potable 
water fixture fittings 


Required 


— 


Sanitary drainage and vent system components 


Plastic pipe, fittings, and pipe related components 


All others 


Special waste system components 





Required 


Storm drainage system components 


Plastic pipe, fittings, and pipe related components 


All others 


Subsoil drainage system components 





Required 


Waste fixture fittings 


Plastic pipe, fittings, and pipe related components 


All others 


Water distribution system safety devices 


Required 


— 



2006 SNTERfvJATSOS^AL RESIDENTIAL CODE® 



430 2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 27 

PLUMBING FIXTURES 



SECTION P2701 
FIXTURES, FAUCETS AND FIXTURE FITTINGS 

P2701.1 Quality of fixtures. Plumbing fixtures, faucets and 
fixture fittings shall be constructed of approved materials, shall 
have smooth impervious surfaces, shall be free from defects 
and concealed fouling surfaces, and shall conform to the stan- 
dards cited in this code. Plumbing fixtures shall be provided 
with an adequate supply of potable water to flush and keep the 
fixtures in a clean and sanitary condition without danger of 
backflow or cross connection. 

SECTION P2702 
FIXTURE ACCESSORIES 

P2702.1 Plumbing fixtures. Plumbing fixtures, other than 
water closets, shall be provided with approved strainers. 

P2702.2 Waste fittings. Waste fittings shall conform to ASME 
A112.18.2, ASTMF409, CSA B125 or to one of the standards 
listed in Table P3002.1(l) for above-ground drainage and vent 
pipe and fittings. 

P2702.3 Plastic tubular fittings. Plastic tubular fittings shall 
conform to ASTM F 409 Hsted in Table P2701.1. 

P2702.4 Carriers for wall-hung water closets. Carriers for 
wall-hung water closets shall conform to ASME A 11 2. 6.1 or 
ASME Al 12.6.2. 



SECTION P2703 
TAIL PIECES 

P2703.1 Minimum size. Fixture tail pieces shall be not less than 
IVj inches (38 mm) in diameter for sinks, dishwashers, laundry 
tubs, bathtubs and similar fixtures, and not less than 1 74 inches 
(32 mm) in diameter for bidets, lavatories and similar fixtures. 

SECTION P2704 
ACCESS TO CONNECTIONS 

P2704.1 General. Slip joints shall be made with an approved 
elastomeric gasket and shall be installed only on the trap outlet, 
trap inlet and within the trap seal. Fixtures with concealed 
slip-joint connections shall be provided with an access panel or 
utility space at least 12 inches (305 mm) in its smallest dimen- 
sion or other approved arrangement so as to provide access to 
the slip connections for inspection and repair. 

SECTION P2705 
INSTALLATION 

P2705.1General. The installation of fixtures shall conform to 
the following: 

1 . Floor-outlet or floor-mounted fixtures shall be secured 
to the drainage connection and to the floor, where so 
designed, by screws, bolts, washers, nuts and similar fas- 



teners of copper, brass or other corrosion-resistant 
material. 

2. Wall-hung fixtures shall be rigidly supported so that 
strain is not transmitted to the plumbing system. 

3 . Where fixtures come in contact with walls and floors, the 
contact area shall be water tight. 

4. Plumbing fixtures shall be usable. 

5. The centerline of water closets or bidets shall not be less 
than 15 inches (381 mm) from adjacent walls or parti- 
tions or not less than 1 5 inches (381 mm) from the center- 
line of a bidet to the outermost rim of an adjacent water 
closet. There shall be at least 21 inches (533 mm) clear- 
ance in front of the water closet, bidet or lavatory to any 
wall, fixture or door. 

6. The location of piping, fixtures or equipment shall not 
interfere with the operation of windows or doors. 

7. In areas prone to flooding as established by Table 
R301.2(l), plumbing fixtures shall be located or installed 
in accordance with Section R323.1.5. 

8. Integral fixture-fitting mounting surfaces on manufac- 
tured plumbing fixtures or plumbing fixtures con- 
structed on site, shall meet the design requirements of 
ASME A112.19.2 or ASME Al 12.19.3. 

SECTION P2706 
WASTE RECEPTORS 

P2706.1 General. Every waste receptor shall be of an approved 
type. Plumbing fixtures or other receptors receiving the discharge 
of indirect waste pipes shall be shaped and have a capacity to pre- 
vent splashing or flooding and shall be readily accessible for 
inspection and cleaning. Waste receptors and standpipes shaU be 
trapped and vented and shall connect to the building drainage sys- 
tem. A removable strainer or basket shall cover the waste outlet of 
waste receptors. Waste receptors shall be installed in ventilated 
spaces. Waste receptors shall not be installed in bathrooms or in 
any inaccessible or unventilated space such as a closet. Ready 
access shall be provided to waste receptors. 

Exception: Open hub waste receptors shall be permitted in 
the form of a hub or pipe extending not less than 1 inch (25 
mm) above a water-impervious floor, and are not required to 
have a strainer. 

P2706.2 Standpipes. Standpipes shall extend a minimum of 
18 inches (457 mm) and a maximum of 42 inches (1067 mm) 
above the trap weir. Access shall be provided to all standpipe 
traps and drains for rodding. 

P2706.2.1 Laundry tray connection. A laundry tray waste 
line is permitted to connect into a standpipe for the auto- 
matic clothes washer drain. The standpipes shall not be less 
than 30 inches (762 mm) as measured from the crown weir. 
The outlet of the laundry tray shall be a maximum horizon- 
tal distance of 30 inches (762 mm) from the standpipe trap. 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



431 



PLUMBING FIXTURES 



TABLE P2701.1 
PLUMBING FIXTURES, FAUCETS AND FIXTURE FITTINGS 



MATERIAL 


STANDARD 


Air gap fittings for use with plumbing fixtures, appliances and appurtenances 


ASMEAl 12.1.3 


Bathtub/ whirlpool pressure-sealed doors 


ASMEA112.19.15 


Diverters for faucets with hose spray anti-syphon type, residential application 


ASSE 1025 


Enameled cast-iron plumbing fixtures 


ASMEAl 12.19.1M, 
CSA B45.2 


Floor drains 


ASMEA112.6.3 


Floor-affixed supports for off-the-floor plumbing fixtures for public use 


ASMEA112.6.1M 


Framing-affixed supports for off-the-floor water closets with concealed tanks 


ASMEA112.6.2 


Handheld showers 


ASSE 1014 


Home laundry equipment 


ASSE 1007 


Hose connection vacuum breaker 


ASSE 1052 


Hot water dispensers, household storage type, electrical 


ASSE 1023 


Household dishwashing machines 


ASSE 1006 


Household disposers 


ASSE 1008 


Hydraulic performance for water closets and urinals 


ASMEAl 12. 19.6 


Individual pressure balancing valves for individual fixture fittings 


ASSE 1066 


Individual shower control valves anti-scald 


ASSE 1016, CSA B125 


Macerating toilet systems and related components 


ASMEAl 12.3.4 


Nonvitreous ceramic plumbing fixtures 


ASMEAl 12. 19.9M, 
CSAB45.1 


Plastic bathtub units 


ANSI Z124.1, CSA B45.1 


Plastic lavatories 


ANSI Z124.3, CSA B45.5 


Plastic shower receptors and shower stall 


ANSI Z124.2, CSA B45.5 


Plastic sinks 


ANSI Z 124.6, CSA B45.5 


Plastic water closet bowls and tanks 


ANSI Z 12.4.4, CSA B45.5 


Plumbing fixture fittings 


ASMEAl 12.18.1M, 
CSA B 125 


Plumbing fixture waste fittings 


ASMEAl 12.18.2, 
ASTMF409,CSAB125 


Porcelain-enameled formed steel plumbing fixtures 


ASMEAl 12. 19.4M, 
CSAB45.3 


Pressurized flushing devices for plumbing fixtures 


ASSE 1037 


Specification for copper sheet and strip for building construction 


ASTM B 370 


Stainless steel plumbing fixtures (residential) 


ASMEAl 12.19.3M, 
CSA B45.4 


Suction fittings for use in swimming pools, wading pools, spas, hot tubs and whirlpool bathtub appliances 


ASMEAl 12. 19.8M 


Temperature-actuated, flow reduction valves to individual fixture fittings 


ASSE 1062 


Thermoplastic accessible and replaceable plastic tube and tubular fittings 


ASTM F 409 


Trench drains 


ASMEAl 12.6.3 


Trim for water closet bowls, tanks and urinals 


ASMEAl 12. 19.5 


Vacuum breaker wall hydrant — frost-resistant, automatic-draining type 


ASSE 1019 


Vitreous china plumbing fixtures 


ASMEAl 12. 19.2M 


Wall-mounted and pedestal-mounted, adjustable and pivoting lavatory and sink carrier systems 


ASMEA112.19.12 


Water closet flush tank fill valves 


ASSE 1002, CSA B 125 


Whirlpool bathtub appliances 


ASMEAl 12.19.7M 



432 



200S INTERNATIONAL RESIDENTIAL CODE*^ 



PLUMBING FIXTURES 



P2706.3 Prohibited waste receptors. Plumbing fixtures that 
are used for domestic or culinary purposes shall not be used to 
receive the discharge of indirect waste piping. 

Exceptions: 

1 . A kitchen sink trap is acceptable for use as a receptor 
for a dishwasher. 

2. A laundry tray is acceptable for use as a receptor for a 
clothes washing machine. 



a high limit stop in accordance with ASSE 1016 or CSA B 125. 
The high limit stop shall be set to limit water temperature to a 
maximum of 120°F (49°C). In-line thermostatic valves shall 
not be used for compliance with this section. 

P2708.4 Hand showers. Hand-held showers shall conform to 
ASMEA112.18.1 or CSAB125.1. Hand-held showers shall be 
provide backflow protection in accordance with ASME 
Al 12.18.1 or CSA B 125.1 or shall be protected against 
backflow by a device complying with ASME Al 12.18.3. 



•, 



SECTION P2707 
DIRECTIONAL FITTINGS 

P2707.1 Directional Htting required. Approved direc- 
tional-type branch fittings shall be installed in fixture tailpieces 
receiving the discharge from food waste disposal units or dish- 
washers. 



SECTION P2708 
SHOWERS 

P2708.1 General. Shower compartments shall have at least 
900 square inches (0.6 m^) of interior cross-sectional area. 
Shower compartments shall be not less than 30 inches (762 
mm) in minimum dimension measured from the finished inte- 
rior dimension of the shower compartment, exclusive of fixture 
valves, shower heads, soap dishes, and safety grab bars or rails. 
The minimum required area and dimension shall be measured 
from the finished interior dimension at a height equal to the top 
of the threshold and at a point tangent to its centerline and shall 
be continued to a height of not less than 70 inches (1778 mm) 
above the shower drain outlet. Hinged shower doors shall open 
outward. The wall area above built-in tubs having installed 
shower heads and in shower compartments shall be constructed 
in accordance with Section R702.4. Such walls shall form a 
water-tight joint with each other and with either the tub, recep- 
tor or shower floor. 

Exceptions: 

1. Fold-down seats shall be permitted in the shower, 
provided the required 900-square-inch (0.6 m^) 
dimension is maintained when the seat is in the 
folded-up position. 

2. Shower compartments having not less than 25 inches 
(635 mm) in minimum dimension measured from the 
finished interior dimension of the compartment pro- 
vided that the shower compartment has a minimum of 
1 ,300 square inches (0.838 m^) of cross-sectional area. 

P2708.1.1 Access. The shower compartment access and 
egress opening shall have a minimum clear and unob- 
structed finished width of 22 inches (559 mm). 

P2708.2 Water-supply riser. The water supply riser from the 
shower valve to the shower head outlet shall be secured to the 
permanent structure. 

P2708.3 Shower control valves. Individual shower and 
tub/shower combination valves shall be equipped with control 
valves of the pressure-balance, thermostatic-mixing or combi- 
nation pressure-balance/thermostatic-mixing valve types with 



SECTION P2709 
SHOWER RECEPTORS 

P2709.1 Construction. Shower receptors shall have a finished 
curb threshold not less than 1 inch (25 mm) below the sides and 
back of the receptor. The curb shall be not less than 2 inches (5 1 
mm) and not more than 9 inches (229 mm) deep when mea- 
sured from the top of the curb to the top of the drain. The fin- 
ished floor shall slope uniformly toward the drain not less than 
V4 unit vertical in 12 units horizontal (2-percent slope) nor 
more than V2 inch (13 mm), and floor drains shall be flanged to 
provide a water-tight joint in the floor. 

P2709.2 Lining required. The adjoining walls and floor fram- 
ing enclosing on-site built-up shower receptors shall be lined 
with sheet lead, copper or a plastic liner material that complies 
with ASTM D 4068 or ASTM D 4551. The lining material 
shall extend not less than 3 inches (76 mm) beyond or around 
the rough jambs and not less than 3 inches (76 mm) above fin- 
ished thresholds. Hot mopping shall be permitted in accor- 
dance with Section P2709.2.3. 

P2709.2.1 PVC sheets. Plasticized polyvinyl chloride 
(PVC) sheets shall be a minimum of 0.040 inch (1 mm) 
thick, and shall meet the requirements of ASTM D 4551. 
Sheets shall be joined by solvent welding in accordance 
with the manufacturer's installation instructions. 

P2709.2.2 Chlorinated polyethylene (CPE) sheets. Non- 
plasticized chlorinated polyethylene sheet shall be a mini- 
mum of 0.040 inch (1 mm) thick, and shall meet the require- 
ments of ASTM D 4068. The liner shall be joined in 
accordance with the manufacturer's installation instructions. 

P2709.2.3 Hot-mopping. Shower receptors lined by hot 
mopping shall be built-up with not less than three layers of 
standard grade Type 15 asphalt-impregnated roofing felt. 
The bottom layer shall be fitted to the formed subbase and 
each succeeding layer thoroughly hot-mopped to that 
below. All comers shall be carefully fitted and shall be made 
strong and water tight by folding or lapping, and each comer 
shall be reinforced with suitable webbing hot-mopped in 
place. All folds, laps and reinforcing webbing shall extend 
at least 4 inches (102 mm) in all directions from the corner 
and all webbing shall be of approved type and mesh, pro- 
ducing a tensile strength of not less than 50 pounds per inch 
(893 kg/m) in either direction. 

P2709.3 Installation. Lining materials shall be pitched 
one-fourth unit vertical in 12 units horizontal (2-percent slope) 
to weep holes in the subdrain by means of a smooth, solidly 
formed subbase, shall be properly recessed and fastened to 
approved backing so as not to occupy the space required for the 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



433 



PLUMBING FIXTURES 



wall covering, and shall not be nailed or perforated at any point 
less than 1 inch (25.4 mm) above the finished threshold. 

P2709.3.1 Materials. Lead and copper linings shall be 
insulated from conducting substances other than the con- 
necting drain by 15-pound (6.80 kg) asphalt felt or its equiv- 
alent. Sheet lead liners shall weigh not less than 4 pounds 
per square foot (19.5 kg/m^). Sheet copper liners shall 
weigh not less than 12 ounces per square foot (3.7 kg/m^). 
Joints in lead and copper pans or liners shall be burned or sil- 
ver brazed, respectively. Joints in plastic liner materials 
shall be jointed per the manufacturer's recommendations. 

P2709.4 Receptor drains. An approved flanged drain shall be 
installed with shower subpans or linings. The flange shall be 
placed flush with the subbase and be equipped with a clamping 
ring or other device to make a water-tight connection between 
the lining and the drain. The flange shall have weep holes into 
the drain. 



SECTION P2710 
SHOWER WALLS 

P2710.1 Bathtub and shower spaces. Shower walls shall be 
finished in accordance with Section R307.2. 



SECTION P2711 
LAVATORIES 

P2711.1 ApprovaL Lavatories shall conform to ANSI Z124.3, 
ASME A112.19.1, ASME Al 12.19.2, ASME Al 12.19.3, 
ASME A112.19.4, ASME A112.19.9, CSA B45.1, CSA 
B45.2, CSA B45.3 or CSA B45.4. 

P2711.2 Cultured marble lavatories. Cultured marble vanity 
tops with an integral lavatory shall conform to ANSI Z124.3 or 
CSA B45.5. 

P2711.3 Lavatory waste outlets. Lavatories shall have waste 
outlets not less than 1 V4 inch (32 nrni) in diameter. A strainer, 
pop-up stopper, crossbar or other device shall be provided to 
restrict the clear opening of the waste outlet. 

P2711.4 Movable lavatory systems. Movable lavatory sys- 
tems shall comply with ASME A112.19.12. 



P2712.2 Flushing devices required. Water closets shall be 
provided with a flush tank, flushometer tank or flushometer 
valve designed and installed to supply water in sufficient quan- 
tity and flow to flush the contents of the fixture, to cleanse the 
fixture and refill the fixture trap in accordance with ASME 
A112.19.2 and ASME A112.19.6. 

P2712.3 Water supply for flushing devices. An adequate 
quantity of water shall be provided to flush and clean the fixture 
served. The water supply to flushing devices equipped for 
manual flushing shall be controlled by a float valve or other 
automatic device designed to refill the tank after each discharge 
and to completely shut off the water flow to the tank when the 
tank is filled to operational capacity. Provision shall be made to 
automatically supply water to the fixture so as to refill the trap 
after each flushing. 

P2712.4 Flush valves in flush tanks. Flush valve seats in tanks 
for flushing water closets shall be at least 1 inch (25 mm) above 
the flood-level rim of the bowl connected thereto, except an 
approved water closet and flush tank combination designed so 
that when the tank is flushed and the fixture is clogged or par- 
tially clogged, the flush valve will close tightly so that water 
will not spill continuously over the rim of the bowl or backflow 
from the bowl to the tank. 

P2712.5 Overflows in flush tanks. Flush tanks shall be pro- 
vided with overflows discharging to the water closet connected 
thereto and such overflow shall be of sufficient size to prevent 
flooding the tank at the maximum rate at which the tanks are 
supplied with water according to the manufacturer's design 
conditions. 

P2712.6 Access. All parts in a flush tank shall be accessible for 
repair and replacement. 

P2712.7 Water closet seats. Water closets shall be equipped 
with seats of smooth, nonabsorbent material and shall be prop- 
erly sized for the water closet bowl type. 

P2712.8 Flush tank lining. Sheet copper used for flush tank 
linings shall have a minimum weight of 10 ounces per square 
foot (3 kg/m2). 

P2712.9 Electro-hydraulic water closets. Electro-hydraulic 
water closets shall conform to ASME A112. 19.13. 



SECTION P271 2 
WATER CLOSETS 

P2712.1 Approval. Water closets shall conform to the water 
consumption requirements of Section P2903.2 and shall con- 
form to ANSI Z124.4, ASME A112.19.2, CSA B45.1, CSA 
B45.4 or CSA B45.5. Water closets shall conform to the 
hydraulic performance requirements of ASME Al 12.19.6. 
Water closets tanks shall conform to ANSI Z124.4, ASME 
A112.19.2, ASME Al 12.19.9, CSA B45.1, CSA B45.4 or 
CSA B45.5. Water closets that have an invisible seal and 
unventilated space or walls that are not thoroughly washed at 
each discharge shall be prohibited. Water closets that permit 
backflow of the contents of the bowl into the flush tank shall be 
prohibited. 



SECTION P2713 
BATHTUBS 

P2713.1 Bathtub waste outlets and overflows. Bathtubs shall 
have outlets and overflows at least 1 '^ inches (38 mm) in diam- 
eter, and the waste outlet shall be equipped with an approved 
stopper. 

P2713.2 Bathtub enclosures. Doors within a bathtub enclo- 
sure shall conform to ASME A112.19.15. 

P2713.3 Bathtub and whirlpool bathtub valves. The hot 

water supplied to bathtubs and whirlpool bathtubs shall be lim- 
ited to a maximum temperature of 120°F (49°C) by a water- 
temperamre-timiting device that conforms to ASSE 1070, 
except where such protection is otherwise provided by a com- 
i bination tub/shower valve in accordance with Section P2708 .3 . 



434 



2006 INTERNATIONAL RESIDENTIAL CODE® 



PLUMBING FIXTURES 



SECTION P2714 
SINKS 

P2714.1 Sink waste outlets. Sinks shall be provided with 
waste outlets not less than 1 Vj inches (38 mm) in diameter. A 
strainer, crossbar or other device shall be provided to restrict 
the clear opening of the waste outlet. 

P2714.2 Movable sink systems. Movable sink systems shall 
comply with ASME A112.19.12. 



SECTION P271 5 
LAUNDRY TUBS 

P2715.1 Laundry tub waste outlet. Each compartment of a 
laundry tub shall be provided with a waste outlet not less than 
1 Vj inches (38 mm) in diameter and a strainer or crossbar to 
restrict the clear opening of the waste outlet. 



SECTION P2716 
FOOD WASTE GRINDER 

P2716.1 Food waste grinder waste outlets. Food waste 
grinders shall be connected to a drain of not less than 1 Vj inches 
(38 mm) in diameter. 

P2716.2 Water supply required. Food waste grinders shall be 
provided with an adequate supply of water at a sufficient flow 
rate to ensure proper functioning of the unit. 



SECTION P2717 
DISHWASHING MACHINES 

P2717.1 Protection of water supply. The water supply for 
dishwashers shall be protected by an air gap or integral 
backflow preventer. 

P2717.2 Sink and dishwasher. A sink and dishwasher are per- 
mitted to discharge through a single IVj-inch (38 mm) trap. 
The discharge pipe from the dishwasher shall be increased to a 
minimum of '^1^ inch (19 mm) in diameter and shall be con- 
nected with a wye fitting to the sink tailpiece. The dishwasher 
waste line shall rise and be securely fastened to the underside of 
the counter before connecting to the sink tailpiece. 

P2717.3 Sink, dishwasher and food grinder. The combined 
discharge from a sink, dishwasher, and waste grinder is permit- 
ted to discharge through a single 172 inch (38 mm) trap. The 
discharge pipe from the dishwasher shall be increased to a min- 
imum of V4 inch (19 mm) in diameter and shall connect with a 
wye fitting between the discharge of the food-waste grinder 
and the trap inlet or to the head of the food grinder. The dish- 
washer waste line shall rise and be securely fastened to the 
underside of the counter before connecting to the sink tail piece 
or the food grinder. 



SECTION P271 8 
CLOTHES WASHING MACHINE 

P2718.1 Waste connection. The discharge from a clothes 
washing machine shall be through an air break. 



SECTION P271 9 
FLOOR DRAINS 

P2719.1 Floor drains. Floor drains shall have waste outlets 
not less than 2 inches (5 1 mm) in diameter and shall be pro- 
vided with a removable strainer. The floor drain shall be con- 
structed so that the drain is capable of being cleaned. Access 
shall be provided to the drain inlet. 



SECTION P2720 
WHIRLPOOL BATHTUBS 

P2720.1 Access to pump. Access shall be provided to circula- 
tion pumps in accordance with the fixture manufacturer's 
installation instructions. Where the manufacturer's instruc- 
tions do not specify the location and minimum size of field fab- 
ricated access openings, a 12-inch by 12-inch (304 mm by 304 
mm) minimum size opening shall be installed to provide access 
to the circulation pump. Where pumps are located more than 2 
feet (609 mm) from the access opening, an 1 8-inch by 1 8-inch 
(457 mm by 457 mm) minimum size opening shall be 
installed. A door or panel shall be permitted to close the open- 
ing. In all cases, the access opening shall be unobstructed and 
be of the size necessary to permit the removal and replacement 
of the circulation pump. 

P2720.2 Piping drainage. The circulation pump shall be 
accessibly located above the crown weir of the trap. The pump 
drain line shall be properly graded to ensure minimum water 
retention in the volute after fixture use. The circulation piping 
shall be installed to be self-draining. 

P2720.3 Leak testing. Leak testing and pump operation shall 
be performed in accordance with the manufacturer's installa- 
tion instructions. 

P2720.4 Manufacturer's instructions. The product shall be 
installed in accordance with the manufacturer's installation 
instructions. 



SECTION P2721 
BIDET INSTALLATIONS 

P2721.1 Water supply. The bidet shall be equipped with either 
an air-gap-type or vacuum-breaker-type fixture supply fitting. 

P2721.2 Bidet water temperature. The discharge water tem- 
perature from a bidet fitting shall be limited to a maximum tem- 
perature of 110°F (43°C) by a water-temperature-limiting 
device conforming to ASSE 1070. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



435 



PLUMBING FIXTURES 



SECTION P2722 
FIXTURE FITTING 

P2722.1 General. Fixture supply valves and faucets shall com- 
ply with ASME Al 12.18.1 or CSA B 125 as Hsted in Table 
P2701 . 1 . Faucets and fixture fittings that supply drinking water 
for human ingestion shall conform to the requirements of NSF 
61, Section 9. Flexible water connectors shall conform to the 
requirements of Section P2904.7. 

P2722.2 Hot water. Fixture fittings and faucets that are sup- 
plied with both hot and cold water shall be installed and 
adjusted so that the left-hand side of the water temperature con- 
trol represents the flow of hot water when facing the outlet. 

Exception: Shower and tub/shower mixing valves con- 
forming to AS SE 1016 or CSA B 125, where the water tem- 
perature control corresponds to the markings on the device. 

P2722.3 Hose-connected outlets. Faucets and fixture fittings 
with hose-connected outlets shall conform to ASME 
A112.18.3orCSAB125. 

P2722.4 Individual pressure-balancing in-line valves for 
individual fixture fittings. Where individual pressure-balanc- 
ing in-line valves for individual fixture fittings are installed, the 
valves shall comply with ASSE 1066. Such valves shall be 
installed in an accessible location and shall not be used alone as 
a substitute for the balanced pressure, thermostatic or combina- 
tion shower valves required in Section P2708.3. 



SECTION P2723 
MACERATING TOILET SYSTEMS 

P2723.1 General. Macerating toilet systems shall be installed 
in accordance with manufacturer's installation instructions. 

P2723.2 Drain. The minimum size of the drain from the mac- 
erating toilet system shall be ^U inch (19 mm) in diameter. 



SECTION P2724 

SPECIALTY TEMPERATURE CONTROL 

DEVICES AND VALVES 

P2724.1 Temperature-actuated, flow-reduction devices for 
individual fixtures. Temperature-actuated, flow-reduction 
devices, where installed for individual fixture fittings, shall 
conform to ASSE 1062. Such valves shall not be used alone as 
a substitute for the balanced pressure, thermostatic or combina- 
tion shower valves required for showers in Section P2708.3. 



436 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 28 

WATER HEATERS 



SECTION P2801 
GENERAL 

P2801.1 Required. Each dwelling shall have an approved 
automatic water heater or other type of domestic water-heating 
system sufficient to supply hot water to plumbing fixtures and 
appliances intended for bathing, washing or culinary purposes. 
Storage tanks shall be constructed of noncorrosive metal or 
shall be lined with noncorrosive material. 

P2801.2 Installation. Water heaters shall be installed in accor- 
dance with this chapter and Chapters 20 and 24. 

P2801.3 Location. Water heaters and storage tanks shall be 
located and connected to provide access for observation, main- 
tenance, servicing and replacement. 

P2801.4 Prohibited locations. Water heaters shall be located 
in accordance with Chapter 20. 

P2801.5 Required pan. Where water heaters or hot water stor- 
age tanks are installed in locations where leakage of the tanks 
or connections will cause damage, the tank or water heater shall 
be installed in a galvanized steel pan having a minimum thick- 
ness of 24 gage (0.016 inch) (0.4 mm) or other pans for such 
use. Listed pans shall comply with CSA LC3. 

P2801.5.1 Pan size and drain. The pan shall be not less 
than 1 V2 inches (38 mm) deep and shall be of sufficient size 
and shape to receive all dripping or condensate from the 
tank or water heater. The pan shall be drained by an indirect 
waste pipe having a minimum diameter of % inch (19 mm). 
Piping for safety pan drains shall be of those materials listed 
in Table P2904.5. 

P2801.5.2 Pan drain termination. The pan drain shall 
extend full-size and terminate over a suitably located indi- 
rect waste receptor or shall extend to the exterior of the 
building and terminate not less than 6 inches (152 mm) and 
not more than 24 inches (610 mm) above the adjacent 
ground surface. 

P2801.6 Water heaters installed in garages. Water heaters 
having an ignition source shall be elevated such that the source 
of ignition is not less than 1 8 inches (457 mm) above the garage 
floor. 

P2801.7 Water heater seismic bracing, hi Seismic Design Cate- 
gories Dq, D, and D2 and townhouses in Seismic Design Category 
C, water heaters shaU be anchored or strapped in the upper 
one-third and in the lower one-third of the appUance to resist a 
horizontal force equal to one-third of the operating weight of the 
water heater, acting in any horizontal direction, or in accordance 
with the appUance manufacturer's recommendations. 



SECTION P2802 
WATER HEATERS USED FOR SPACE HEATING 

P2802.1 Protection of potable water. Piping and components 
connected to a water heater for space heating applications shall 



be suitable for use with potable water in accordance with Chap- 
ter 29. Water heaters that will be used to supply potable water 
shall not be connected to a heating system or components pre- 
viously used with nonpotable-water heating appliances. 
Chemicals for boiler treatment shall not be introduced into the 
water heater. 

P2802.2 Temperature control. Where a combination water 
heater-space heating system requires water for space heating at 
temperatures exceeding 140°F (60°C), a master thermostatic 
mixing valve complying with ASSE 1017 shall be installed to 
temper the water to a temperature of 140°F (60°C) or less for 
domestic uses. 



SECTION P2803 
RELIEF VALVES 

P2803.1 Relief valves required. Appliances and equipment 
used for heating water or storing hot water shall be protected 
by: 

1. A separate pressure-relief valve and a separate tempera- 
ture-relief valve; or 

2. A combination pressure- and temperature-relief valve. 

P2803.2 Rating. Relief valves shall have a minimum rated 
capacity for the equipment served and shall conform to 

ANSI Z 21.22. 

P2803.3 Pressure relief valves. Pressure-relief valves shall 
have a relief rating adequate to meet the pressure conditions for 
the apphances or equipment protected. In tanks, they shall be 
installed directly into a tank tapping or in a water line close to 
the tank. They shall be set to open at least 25 psi (172 kPa) 
above the system pressure but not over 150 psi (1034 kPa). The 
relief-valve setting shall not exceed the tanks rated working 
pressure. 

P2803.4 Temperature relief valves. Temperature-relief 
valves shall have a relief rating compatible with the tempera- 
ture conditions of the appliances or equipment protected. The 
valves shall be installed such that the temperature-sensing ele- 
ment monitors the water within the top 6 inches (152 mm) of 
the tank. The valve shall be set to open at a maximum tempera- 
ture of 21 0°F (99°C). 

P2803.5 Combination pressure-Ztemperature-relief valves. 

Combination pressure-Ztemperature-relief valves shall comply 
with all the requirements for separate pressure- and tempera- 
ture-relief valves. 

P2803.6 Installation of relief valves. A check or shutoff valve 
shall not be installed in the following locations: 

1 . Between a relief valve and the termination point of the 
relief valve discharge pipe; 

2. Between a relief valve and a tank; or 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



437 



WATER HEATERS 



3. Between a relief valve and heating appliances or equip- 
ment. 

P2803.6.1 Requirements for discharge pipe. The dis- 
charge piping serving a pressure-relief valve, temperature- 
relief valve or combination valve shall: 

1 . Not be directly connected to the drainage system. 

2. Discharge through an air gap located in the same 
room as the water heater. 

3 . Not be smaller than the diameter of the outlet of the 
valve served and shall discharge full size to the air 
gap. 

4. Serve a single relief device and shall not connect to 
piping serving any other relief device or equipment. 

5. Discharge to the floor, to an indirect waste receptor 
or to the outdoors. Where discharging to the out- 
doors in areas subject to freezing, discharge piping 
shall be first piped to an indirect waste receptor 
through an air gap located in a conditioned area. 

6. Discharge in a manner that does not cause personal 
injury or structural damage. 

7. Discharge to a termination point that is readily 
observable by the building occupants. 

8. Not be trapped. 

9. Be installed to flow by gravity. 

10. Not terminate more than 6 inches (152 mm) above 
the floor or waste receptor. 

1 1 . Not have a threaded connection at the end of the pip- 
ing. 

12. Not have valves or tee fittings. 

13. Be constructed of those materials listed in Section 
P2904.5 or materials tested, rated and approved for 
such use in accordance with ASME Al 12.4.1. 



438 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



CHAPTER 29 

WATER SUPPLY AND DISTRIBUTION 



SECTION P2901 
GENERAL 

P2901.1 Potable water required. Dwelling units shall be 
supplied with potable water in the amounts and pressures speci- 
fied in this chapter. In a building where both a potable and 
nonpotable water-distribution system are installed, each system 
shall be identified by color marking, metal tag or other appropri- 
ate method. Any nonpotable outlet that could inadvertently be 
used for drinking or domestic purposes shall be posted. 



SECTION P2902 
PROTECTION OF POTABLE WATER SUPPLY 

P2902.1 GeneraL A potable water supply system shall be 
designed and installed as to prevent contamination from 
nonpotable liquids, solids or gases being introduced into the 
potable water supply. Connections shall not be made to a pota- 
ble water supply in a manner that could contaminate the water 
supply or provide a cross-connection between the supply and a 
source of contamination unless an approved backflow-preven- 
tion device is provided. Cross-connections between an individ- 
ual water supply and a potable public water supply shall be 
prohibited. 

P2902.2 Plumbing fixtures. The supply lines and fittings for 
every plumbing fixture shall be installed to prevent backflow. 
Plumbing fixture fittings shall provide backflow protection in 
accordance with ASME Al 12.18.1. 

P2902.3 Backflow protection. A means of protection against 
backflow shall be provided in accordance with Sections 
P2902.3.1 through P2902.3.6. Backflow prevention appHca- 
tions shall conform to Table P2902.3, except as specifically 
stated in Sections P2902.4 through P2902.5.5. 

P2902.3.1 Air gaps. Air gaps shall comply with ASME 
Al 12.1.2 and air gap fittings shall comply with ASME 
A 11 2. 1 .3. The minimum air gap shall be measured vertically 
from the lowest end of a water supply outlet to the flood level 
rim of the fixture or receptor into which such potable water 
outlets discharge. The minimum required air gap shall be 
twice the diameter of the effective opening of the outlet, but in 
no case less than the values specified in Table P2902.3. 1 . An 
air gap is required at the discharge point of a reUef valve or 
piping. Air gap devices shall be incorporated in dishwashing 
and clothes washing appliances. 

P2902.3.2 Atmospheric-type vacuum breakers. Pipe- 
applied atmospheric-type vacuum breakers shall conform 
to ASSE 1001 or CSA B64.1.1. Hose-connection vacuum 
breakers shall conform to ASSE 1011, ASSE 1019, ASSE 
1035, ASSE 1052, CSA B64.2, CSA B64.2.1, CSA 
B64.2. 1 . 1 , CSA B64.2.2 or CSA B64.7. These devices shall 
operate under normal atmospheric pressure when the criti- 
cal level is installed at the required height. 



P2902.3.3 Backflow preventer with intermediate atmo- 
spheric vent. Backflow preventers with intermediate atmo- 
spheric vents shall conform to ASSE 1012 or CSA 
CAN/CSA B64.3. These devices shall be permitted to be 
installed where subject to continuous pressure conditions. 
The relief opening shall discharge by air gap and shall be 
prevented from being submerged. 

P2902.3.4 Pressure-type vacuum breakers. Pressure- 
type vacuum breakers shall conform to ASSE 1020 or CSA I 
B64. 1 .2 and spillproof vacuum breakers shall comply with | 
ASSE 1056. These devices are designed for installation 
under continuous pressure conditions when the critical level 
is installed at the required height. Pressure-type vacuum 
breakers shall not be installed in locations where spillage 
could cause damage to the structure. 

P2902.3.5 Reduced pressure principle backflow preven- 
ters. Reduced pressure principle backflow preventers shall 
conform to ASSE 1013, AWWA C51 1, CSA B64.4 or CSA I 
B64.4.1. Reduced pressure detector assembly backflow | 
preventers shall conform to ASSE 1047. These devices shall 
be permitted to be installed where subject to continuous pres- 
sure conditions. The reUef opening shall discharge by air gap 
and shall be prevented from being submerged. 

P2902.3.6 Double check- valve assemblies. Double check- 
valve assemblies shall conform to ASSE 1015, CSA B64.5, I 
CSA B64.5.1 or AWWA C510. Double-detector check- I 
valve assemblies shall conform to ASSE 1048. These 
devices shall be capable of operating under continuous pres- 
sure conditions. 

P2902.4 Protection of potable water outlets. Potable water 
openings and outlets shall be protected by an air gap, reduced 
pressure principle backflow preventer with atmospheric vent, 
atmospheric-type vacuum breaker, pressure-type vacuum 
breaker or hose connection backflow preventer. 

P2902.4.1 Fill valves. Flush tanks shall be equipped with an 
antisiphon fill valve conforming to ASSE 1002 or CSA 
B125. The fill valve backflow preventer shall be located at 
least 1 inch (25 mm) above the full opening of the overflow 
pipe. 

P2902.4.2 Deck-mounted and integral vacuum break- 
ers. Approved deck-mounted vacuum breakers and faucets 
with integral atmospheric or spill-proof vacuum breakers 
shall be installed in accordance with the manufacturer's 
installation instructions and the requirements for labeling 
with the critical level not less than 1 inch (25 mm) above the 
flood level rim. 

P2902.4.3 Hose connection. Sillcocks, hose bibbs, wall 
hydrants and other openings with a hose connection shall be 
protected by an atmospheric-type or pressure-type vacuum 
breaker or a permanently attached hose connection vacuum 
breaker. 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



439 



WATER SUPPLY AND DISTRIBUTION 



TABLE P2902.3 
APPLICATION FOR BACKFLOW PREVENTERS 



DEVICE 


DEGREE OF 
HAZARD^ 


APPLICATION" 


APPLICABLE 
STANDARDS 


Air gap 


High or low hazard 


Backsiphonage or backpressure 


ASMEA112.1.2 


Air gap fittings for use with plumbing fixtures, 
appliances and appurtenances 


High or low hazard 


Backsiphonage or backpressure 


ASMEAl 12.1.3 


Antisiphon-type fill valves for gravity water 
closet flush tanks 


High hazard 


Backsiphonage only 


ASSE 1002 
CSACAN/CSAB125 


Backflow preventer with intermediate 
atmospheric vents 


Low hazard 


Backpressure or backsiphonage 
Sizes V/'-V 


ASSE 1012 
CSA B64.3 


Double check backflow prevention assembly 
and double check fire protection backflow 
prevention assembly 


Low hazard 


Backpressure or backsiphonage 
Sizes %"- 16" 


ASSE 1015, AWWAC5 10 
CSAB64.5,CSAB64.5.1 


Double check detector fire protection backflow 
prevention assembhes 


Low hazard 


Backpressure or backsiphonage 
(Fire sprinkler systems) 
Sizes 2"- 16" 


ASSE 1048 


Dual-check- valve-type backflow preventer 


Low hazard 


Backpressure or backsiphonage 
Sizes 7/ - 1" 


ASSE 1024, CSA B64.6 


Hose connection backflow preventer 


High or low hazard 


Low head backpressure, rated working 
pressure backpressure or backsiphonage. 
Sizes V/'-l" 


ASSE 1052, 
CSAB64.2.1.1 


Hose-connection vacuum breaker 


High or low hazard 


Low head backpressure or backsiphonage 
Sizes V,", 3//', 1" 


ASSE 1011, 
CSAB64.2,CSAB64.2.1 


Laboratory faucet backflow preventer 


High or low hazard 


Low head backpressure and 
backsiphonage 


ASSE 1035, CSA B64.7 


Pipe-applied atmospheric-type vacuum breaker 


High or low hazard 


Backsiphonage only 

Sizes V4"-4" 


ASSE 1001 
CSAB64.1.1 


Pressure vacuum breaker assembly 


High or low hazard 


Backsiphonage only 

Sizes V," - 2" 


ASSE 1020, CSA B64.1.2 


Reduced pressure detector fire protection 
backflow prevention assemblies 


High or low hazard 


Backsiphonage or backpressure 
(Fire sprinkler systems) 


ASSE 1047 


Reduced pressure principle backflow preventer 
and reduced pressure principle fire protection 
backflow preventer 


High or low hazard 


Backpressure or backsiphonage 
Sizes Vg"- 16" 


ASSF 1013, AWWA 

C511 

CSAB64.4,CSAB64.4.1 


Spillproof vacuum breaker 


High or low hazard 


Backsiphonage only 
Sizes V/' - 2" 


ASSE 1056 


Vacuum breaker wall hydrants, frost-resistant, 
automatic draining type 


High or low hazard 


Low head backpressure or 

backsiphonage 

Sizes ^11' - 1" 


ASSE 1019, 
CSA B64.2.2 



For SI: I inch = 25.4 mm. 

a. Low hazard — See Pollution (Section 202). High hazard — See Contamination 

b. See Backpressure (Section 202). See Backpressure, Low Head (Section 202). 



(Section 202). 

See Backsiphonage (Section 202). 



Exceptions: 

1. This section shall not apply to water heater and 
boiler drain valves that are provided with hose 
connection threads and that are intended only for 
tank or vessel draining. 

2. This section shall not apply to water supply valves 
intended for connection of clothes washing 
machines where backflow prevention is otherwise 
provided or is integral with the machine. 



P2902.5 Protection of potable water connections. Connec- 
tions to the potable water shall conform to Sections P2902.5.1 
through P2902.5.5. 

P2902.5.1 Connections to boilers. The potable supply to 
the boiler shall be equipped with a backflow preventer with 
an intermediate atmospheric vent complying with ASSE 
1012 or CSA B64.3. Where conditioning chemicals are 
introduced into the system, the potable water connection 
shall be protected by an air gap or a reduced pressure princi- 
ple backflow preventer complying with ASSE 1013, CSA 
B64.3orAWWAC511. 



440 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WATER SUPPLY AND DISTRIBUTION 



TABLE P2902.3.1 
MINIMUM AIR GAPS 



FIXTURE 


MINIMUM AIR GAP 


Away from a wall^ 
(inches) 


Close to a wall 
(inches) 


Effective openings greater than 1 inch 


Two times the diameter of the 
effective opening 


Three times the diameter of 
the effective opening 


Lavatories and other fixtures with effective opening not greater than V2 inch 
in diameter 


1 


1.5 


Over-rim bath fillers and other fixtures with effective openings not greater 
than 1 inch in diameter 


2 


3 


Sink, laundry trays, gooseneck back faucets and other fixtures with effective 
openings not greater than ^1^ inch in diameter 


1.5 


2.5 



For SI: 1 inch = 25.4 mm. 

a. Applicable where walls or obstructions are spaced from the nearest inside edge of the spout opening a distance greater than three times the diameter of the effective 
opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls. 



P2902.5.2 Heat exchangers. Heat exchangers using an 
essentially toxic transfer fluid shall be separated from the 
potable water by double- wall construction. An air gap open 
to the atmosphere shall be provided between the two walls. 
Heat exchangers utilizing an essentially nontoxic transfer 
fluid shall be permitted to be of single-wall construction. 

P2902.5.3 Lawn irrigation systems. The potable water 
supply to lawn irrigation systems shall be protected against 
backflow by an atmospheric-type vacuum breaker, a pres- 
sure-type vacuum breaker or a reduced pressure principle 
backflow preventer. A valve shall not be installed down- 
stream from an atmospheric vacuum breaker. Where chemi- 
cals are introduced into the system, the potable water supply 
shall be protected against backflow by a reduced pressure 
principle backflow preventer. 

P2902.5.4 Connections to automatic fire sprinkler sys- 
tems. The potable water supply to automatic fire sprinkler 
systems shall be protected against backflow by a double 
check- valve assembly or a reduced pressure principle 
backflow preventer. 

Exception: Where systems are installed as a portion of 
the water distribution system in accordance with the 
requirements of this code and are not provided with a fire 
department connection, isolation of the water supply 
system shall not be required. 

P2902.5.4.1 Additives or nonpotable source. Where 
systems contain chemical additives or antifreeze, or 
where systems are connected to a nonpotable secondary 
water supply, the potable water supply shall be protected 
against backflow by a reduced pressure principle 



backflow preventer. Where chemical additives or anti- 
freeze is added to only a portion of an automatic fire 
sprinkler or standpipe system, the reduced pressure prin- 
ciple backflow preventer shall be permitted to be located 
so as to isolate that portion of the system. 

P2902.5.5 Solar systems. The potable water supply to a 
solar system shall be equipped with a backflow preventer 
with intermediate atmospheric vent complying with ASSE 
1012 or a reduced pressure principle backflow preventer 
complying with ASSE 1013. Where chemicals are used, the 
potable water supply shall be protected by a reduced pres- 
sure principle backflow preventer. 

Exception: Where all solar system piping is a part of the 
potable water distribution system, in accordance with the 
requirements of the International Plumbing Code, and 
all components of the piping system are listed for potable 
water use, cross-connection protection measure shall not 
be required. 

P2902.6 Access. Backflow prevention devices shall be acces- 
sible for inspection and servicing. 



SECTION P2903 
WATER-SUPPLY SYSTEM 

P2903.1 Water supply system design criteria. The water ser- 
vice and water distribution systems shall be designed and pipe 
sizes shall be selected such that under conditions of peak 
demand, the capacities at the point of outlet discharge shall not 
be less than shown in Table P2903.1. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



441 



WATER SUPPLY AND DISTRIBUTION 



TABLE P2903.1 

REQUIRED CAPACITIES AT 

POINT OF OUTLET DISCHARGE 



FIXTURE AT POINT OF OUTLET 


FLOW RATE 

(gpm) 


FLOW 

PRESSURE 

(psi) 


Bathtub 


4 


8 


Bidet 


2 


4 


Dishwasher 


2.75 


8 


Laundry tub 


4 


8 


Lavatory 


2 


8 


Shower 


3 


8 


Shower, temperature controlled 


3 


20 


Sillcock, hose bibb 


5 


8 


Sink 


2.5 


8 


Water closet, flushometer tank 


1.6 


15 


Water closet, tank, close coupled 


3 


8 


Water closet, tank, one-piece 


6 


20 



For SI: 1 gallon per minute = 3.785 L/m, 

1 pound per square inch = 6.895 kPa. 

P2903.2 Maximum flow and water consumption. The maxi- 
mum water consumption flow rates and quantities for all 
plumbing fixtures and fixture fittings shall be in accordance 
with Table P2903.2. 

TABLE P2903.2 

MAXIMUM FLOW RATES AND CONSUMPTION FOR 

PLUMBING FIXTURES AND FIXTURE FITTINGS" 



PLUMBING FIXTURE 
OR FIXTURE FITTING 


PLUMBING FIXTURE 
OR FIXTURE FITTING 


Lavatory faucet 


2.2 gpm at 60 psi 


Shower head'' 


2.5 gpm at 80 psi 


Sink faucet 


2.2 gpm at 60 psi 


Water closet 


1.6 gallons per flushing cycle 



For SI: 1 gallon per minute = 3.785 L/m, 

1 pound per square inch = 6.895 kPa. 

a. A handheld shower spray is also a shower head. 

b. Consumption tolerances shall be determined from referenced standards. 

P2903.3 Minimum pressure. Minimum static pressure (as 
determined by the local water authority) at the building 
entrance for either public or private water service shall be 40 
psi (276 kPa). 

P2903.3.1 Maximum pressure. Maximum static pressure 
shall be 80 psi (55 1 kPa). When main pressure exceeds 80 psi 
(55 1 kPa), an approved pressure-reducing valve conforming 
to ASSE 1003 shall be installed on the domestic water branch 
main or riser at the connection to the water-service pipe. 

P2903.4 Thermal expansion control. A means for controlling 
increased pressure caused by thermal expansion shall be 
installed where required in accordance with Sections 
P2903.4.1andP2903.4.2. 



P2903.4.1 Pressure-reducing valve. For water service sys- 
tem sizes up to and including 2 inches (5 1 mm), a device for 
controlling pressure shall be installed where, because of 
thermal expansion, the pressure on the downstream side of a 
pressure-reducing valve exceeds the pressure-reducing 
valve setting. 

P2903.4.2 Backflow prevention device or check valve. 

Where a backflow prevention device, check valve or other 
device is installed on a water supply system using storage 
water heating equipment such that thermal expansion 
causes an increase in pressure, a device for controlling pres- 
sure shall be installed. 

P2903.5 Water hammer. The flow velocity of the water distri- 
bution system shall be controlled to reduce the possibility of 
water hanuner. A water-hammer arrestor shall be installed 
where quick-closing valves are used. Water-hammer arrestors 
shall be installed in accordance with manufacturers' specifica- 
tions. Water-hammer arrestors shall conform to ASSE 1010. 

P2903.6 Determining water-supply fixture units. Supply 
loads in the building water-distribution system shall be deter- 
mined by total load on the pipe being sized, in terms of 
water-supply fixture units (w.s.f.u.), as shown in Table 
P2903.6, and gallon per minute (gpm) flow rates [see Table 
P2903.6(l)]. For fixtures not listed, choose a w.s.f.u. value of a 
fixture with similar flow characteristics. 

P2903.7 Size of water-service mains, branch mains and ris- 
ers. The minimum size water service pipe shall be % inch (19 
mm). The size of water service mains, branch mains and risers 
shall be determined according to water supply demand [gpm 
(L/m)], available water pressure [psi (kPa)] and friction loss 
caused by the water meter and developed length of pipe [feet 
(m)], including equivalent length of fittings. The size of each 
water distribution system shall be determined according to the 
procedure outlined in this section or by other design methods 
conforming to acceptable engineering practice and approved 
by the administrative authority: 

1. Obtain the minimum daily static service pressure [psi 
(kPa)] available (as determined by the local water 
authority) at the water meter or other source of supply at 
the installation location. Adjust this minimum daily 
static pressure [psi (kPa)] for the following conditions: 

1.1. Determine the difference in elevation between the 
source of supply and the highest water supply out- 
let. Where the highest water supply outlet is located 
above the source of supply, deduct 0.5 psi (3 .4 kPa) 
for each foot (305 mm) of difference in elevation. 
Where the highest water supply outlet is located 
below the source of supply, add 0.5 psi (3 .4 kPa) for 
each foot (305 mm) of difference in elevation. 

1.2. Where a water pressure reducing valve is 
installed in the water distribution system, the 
minimum daily static water pressure available is 
80 percent of the minimum daily static water 
pressure at the source of supply or the set pres- 
sure downstream of the pressure reducing valve, 
whichever is smaller. 



m 



442 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WATER SUPPLY AND DISTRIBUTION 



1.3. Deduct all pressure losses caused by special 
equipment such as a backflow preventer, water 
filter or water softener. Pressure loss data for 
each piece of equipment shall be obtained from 
the manufacturer of such devices. 

1.4. Deduct the pressure in excess of 8 psi (55 kPa) 
caused by installation of special plumbing fix- 
tures, such as temperature controlled showers 
and flushometer tank water closets. 

Using the resulting minimum available pressure, 
find the corresponding pressure range in Table 
P2903.7. 

2. The maximum developed length for water piping is the 
actual length of pipe between the source of supply and 
the most remote fixture, including either hot (through the 
water heater) or cold water branches multiplied by a fac- 
tor of 1 .2 to compensate for pressure loss through fit- 
tings. 

Select the appropriate column in Table P2903.7 equal 
to or greater than the calculated maximum developed 
length. 

3. To determine the size of water service pipe, meter and 
main distribution pipe to the building using the appropri- 
ate table, follow down the selected "maximum devel- 



oped length" column to a fixture unit equal to, or greater 
than the total installation demand calculated by using the 
"combined" water supply fixture unit column of Table 
P2903.6. Read the water service pipe and meter sizes in 
the first left-hand column and the main distribution pipe 
to the building in the second left-hand column on the 
same row. 

4. To determine the size of each water distribution pipe, 
start at the most remote outlet on each branch (either hot 
or cold branch) and, working back toward the main dis- 
tribution pipe to the building, add up the water supply 
fixture unit demand passing through each segment of the 
distribution system using the related hot or cold column 
of Table P2903.6. Knowing demand, the size of each 
segment shall be read from the second left-hand column 
of the same table and a maximum developed length col- 
umn selected in Steps 1 and 2, under the same or next 
smaller size meter row. In no case does the size of any 
branch or main need to be larger that the size of the main 
distribution pipe to the building established in Step 3. 

P2903.8 Gridded and parallel water distribution system 
manifolds. Hot water and cold water manifolds installed with 
gridded or parallel-connected individual distribution lines to 
each fixture or fixture fittings shall be designed in accordance 
with Sections P2903.8.1 through P2903.8.6. 



TABLE P2903.6 
WATER-SUPPLY FIXTURE-UNIT VALUES FOR VARIOUS PLUMBING FIXTURES AND FIXTURE GROUPS 



TYPE OF FIXTURES OR GROUP OF FIXTURES 


WATER-SUPPLY FIXTURE-UNIT VALUE (w.s.f.u.) 


Hot 


Cold 


Combined 


Bathtub (with/without overhead shower head) 


1.0 


1.0 


1.4 


Clothes washer 


1.0 


1.0 


1.4 


Dishwasher 


1.4 


— 


1.4 


Full-bath group with bathtub (with/without shower head) or shower stall 


1.5 


2.7 


3.6 


Half-bath group (water closet and lavatory) 


0.5 


2.5 


2.6 


Hose bibb (sillcock)^ 


— 


2.5 


2.5 


Kitchen group (dishwasher and sink with/without garbage grinder) 


L9 


1.0 


2.5 


Kitchen sink 


1.0 


1.0 


1.4 


Laundry group (clothes washer standpipe and laundry tub) 


1.8 


1.8 


2.5 


Laundry tub 


1.0 


1.0 


1.4 


Lavatory 


0.5 


0.5 


0.7 


Shower stall 


1.0 


1.0 


1.4 


Water closet (tank type) 


— 


2.2 


2.2 



For SI: 1 gallon per minute = 3.785 L/m. 

a. The fixture unit value 2.5 assumes a flow demand of 2.5 gpm, such as for an individual lawn sprinkler device. If a hose bibb/sill cock will be required to furnish a 
greater flow, the equivalent fixture-unit value may be obtained from this table or Table P2903.6(l). 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



443 



WATER SUPPLY AND DISTRIBUTION 



P2903.8.1 Sizing of manifolds. Manifolds shall be sized in 
accordance with Table P2903.8.1. Total gallons per minute 
is the demand for all outlets. 

P2903.8.2 Minimum size. Where the developed length of 
the distribution line is 60 feet (18 288 mm) or less, and the 
available pressure at the meter is a minimum of 40 pounds per 
square inch (276 kPa), the minimum size of individual distri- 
bution lines shall be Vg inch (10 mm). Certain fixtures such as 
one-piece water closets and whirlpool bathtubs shall require a 
larger size where specified by the manufacturer. If a water 



heater is fed from the end of a cold water manifold, the mani- 
fold shall be one size larger than the water heater feed. 

P2903.8.3 Orientation. Manifolds shall be permitted to be 
installed in a horizontal or vertical position. 

P2903.8.4 Support and protection. Plastic piping bundles 
shall be secured in accordance with the manufacturer's 
installation instructions and supported in accordance with 
Section P2605. Bundles that have a change in direction 
equal to or greater than 45 degrees (0.79 rad) shall be pro- 
tected from chafing at the point of contact with framing 
members by sleeving or wrapping. 



TABLE P2903.6{1) 
CONVERSIONS FROM WATER SUPPLY FIXTURE UNIT TO GALLON PER MINUTE FLOW RATES 



SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS 


SUPPLY SYSTEM PREDOMINANTLY FOR FLUSH VALVES 


Load 


Demand 


Load 


Demand 


(Water supply 
fixture units) 


(Gallons per minute) 


(Cubic feet per minute) 


(Water supply 
fixture units) 


(Gallons per minute) 


(Cubic feet per minute) 


1 


3.0 


0.04104 


— 


— 


— 


2 


5.0 


0.0684 


— 


— 


— 


3 


6.5 


0.86892 


— 


— 


— 


4 


8.0 


1.06944 


— 


— 


— 


5 


9.4 


1.256592 


5 


15.0 


2.0052 


6 


10.7 


1.430376 


6 


17.4 


2.326032 


7 


11.8 


1.577424 


7 


19.8 


2.646364 


8 


12.8 


1.711104 


8 


22.2 


2.967696 


9 


13.7 


1.831416 


9 


24.6 


3.288528 


10 


14.6 


1.951728 


10 


27.0 


3.60936 


11 


15.4 


2.058672 


11 


27.8 


3.716304 


12 


16.0 


2.13888 


12 


28.6 


3.823248 


13 


16.5 


2.20572 


13 


29.4 


3.930192 


14 


17.0 


2.27256 


14 


30.2 


4.037136 


15 


17.5 


2.3394 


15 


31.0 


4.14408 


16 


18.0 


2.90624 


16 


31.8 


4.241024 


17 


18.4 


2.459712 


17 


32.6 


4.357968 


18 


18.8 


2.513184 


18 


33.4 


4.464912 


19 


19.2 


2.566656 


19 


34.2 


4.571856 


20 


19.6 


2.620128 


20 


35.0 


4.6788 


25 


21.5 


2.87412 


25 


38.0 


5.07984 


30 


23.3 


3.114744 


30 


42.0 


5.61356 


35 


24.9 


3.328632 


35 


44.0 


5.88192 


40 


26.3 


3.515784 


40 


46.0 


6.14928 


45 


27.7 


3.702936 


45 


48.0 


6.41664 


50 


29.1 


3.890088 


50 


50.0 


6.684 



For SI: 1 gallon per minute = 3.785 L/m, 1 cubic foot per minute - 0.4719 L/s. 



444 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WATER SUPPLY AND DISTRIBUTION 



TABLE P2903.7 

MINIMUM SIZE OF WATER METERS, MAINS AND DISTRIBUTION PIPING 

BASED ON WATER SUPPLY FIXTURE UNIT VALUES 



Pressure Range — 30 to 39 psi 



METER AND 

SERVICE PIPE 

(inches) 


DISTRIBUTION 

PIPE 

(inches) 


MAXIMUM DEVELOPMENT LENGTH (feet) 


40 


60 


80 


100 


150 


200 


250 


300 


400 


500 


% 


V/ 


2.5 


2 


1.5 


1.5 


1 


1 


.5 


.5 








% 


V4 


9.5 


7.5 


6 


5.5 


4 


3.5 


3 


2.5 


2 


1.5 


'U 


1 


32 


25 


20 


16.5 


11 


9 


7.5 


6.5 


5.5 


4.5 


1 


1 


32 


32 


27 


21 


13.5 


10 


8 


7 


5.5 


5 


V4 


1V4 


32 


32 


32 


32 


30 


24 


20 


17 


13 


10.5 


1 


1V4 


80 


80 


70 


61 


45 


34 


27 


22 


16 


12 


1V2 


1V4 


80 


80 


80 


75 


54 


40 


31 


25 


17.5 


13 


1 


IV, 


87 


87 


87 


87 


84 


73 


74 


56 


45 


36 


VI, 


IV, 


151 


151 


151 


151 


117 


92 


79 


69 


54 


43 



Pressure Range — 40 to 49 psi 



METER AND 

SERVICE PIPE 

(inches) 


DISTRIBUTION 

PIPE 

(inches) 


MAXIMUM DEVELOPMENT LENGTH (feet) 


40 


60 


80 


100 


150 


200 


250 


300 


400 


500 


% 


'// 


3 


2.5 


2 


1.5 


1.5 


1 


1 


.5 


.5 


.5 


'u 


% 


9.5 


9.5 


8.5 


7 


5.5 


4.5 


3.5 


3 


2.5 


2 


% 


1 


32 


32 


32 


26 


18 


13.5 


10.5 


9 


7.5 


6 


1 


1 


32 


32 


32 


32 


21 


15 


11.5 


9.5 


7.5 


6.5 


% 


IV4 


32 


32 


32 


32 


32 


32 


32 


27 


21 


16.5 


1 


IV4 


80 


80 


80 


80 


65 


52 


42 


35 


26 


20 


IV, 


IV4 


80 


80 


80 


80 


75 


59 


48 


39 


28 


21 


1 


IV, 


87 


87 


87 


87 


87 


87 


87 


78 


65 


55 


IV, 


IV, 


151 


151 


151 


151 


151 


130 


109 


93 


75 


63 



Pressure Range — 50 to 60 psi 



METER AND 

SERVICE PIPE 

(inches) 


DISTRIBUTION 

PIPE 

(inches) 


MAXIMUM DEVELOPMENT LENGTH (feet) 


40 


60 


80 


100 


150 


200 


250 


300 


400 


500 


% 


v/ 


3 


3 


2.5 


2 


1.5 


1 


1 


1 


.5 


.5 


% 


V4 


9.5 


9.5 


9.5 


8.5 


6.5 


5 


4.5 


4 


3 


2.5 


V4 


1 


32 


32 


32 


32 


25 


18.5 


14.5 


12 


9.5 


8 


1 


1 


32 


32 


32 


32 


30 


22 


16.5 


13 


10 


8 


% 


1V4 


32 


32 


32 


32 


32 


32 


32 


32 


29 


24 


1 


1V4 


80 


80 


80 


80 


80 


68 


57 


48 


35 


28 


IV, 


1V4 


80 


80 


80 


80 


80 


75 


63 


53 


39 


29 


1 


1V2 


87 


87 


87 


87 


87 


87 


87 


87 


82 


70 


IV, 


IV, 


151 


151 


151 


151 


151 


151 


139 


120 


94 


79 



(continued) 



2006 INTERNATIONAL RESIDENTIAL CODE® 



445 



WATER SUPPLY AND DISTRIBUTION 



TABLE P2903.7— continued 

MINIMUM SIZE OF WATER METERS, MAINS AND DISTRIBUTION PIPING 

BASED ON WATER SUPPLY FIXTURE UNIT VALUES 

Pressure Range — greater than 60 psi 



METER AND 

SERVICE PIPE 

(inches) 


DISTRIBUTION 

PIPE 

(inches) 


MAXIMUM DEVELOPMENT LENGTH (feet) 


40 


60 


80 


100 


150 


200 


250 


300 


400 


500 


% 


V/ 


3 


3 


3 


2.5 


2 


1.5 


1.5 


1 


1 


.5 


% 


'U 


9.5 


9.5 


9.5 


9.5 


7.5 


6 


5 


4.5 


3.5 


3 


3/ 
'4 


1 


32 


32 


32 


32 


32 


24 


19.5 


15.5 


11.5 


9.5 


1 


1 


32 


32 


32 


32 


32 


28 


22 


17 


12 


9.5 


% 


1V4 


32 


32 


32 


32 


32 


32 


32 


32 


32 


30 


1 


l'/4 


80 


80 


80 


80 


80 


80 


69 


60 


46 


36 


IV, 


1V4 


80 


80 


80 


80 


80 


80 


76 


65 


50 


38 


1 


1V2 


87 


87 


87 


87 


87 


87 


87 


87 


87 


84 


1% 


1V2 


151 


151 


151 


151 


151 


151 


151 


144 


114 


94 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895kPa. 
a. Minimum size for building supply is ^-inch pipe. 



TABLE P2903.8.1 
MANIFOLD SIZING 



PLASTIC 


METALLIC 


Nominal Size ID 
(inches) 


Maximum^ 
gpm 


Nominal Size ID 
(inches) 


Maximum^ 
gpm 


% 


17 


% 


11 


1 


29 


1 


20 


l'/4 


46 


IV4 


31 


IV2 


66 


l'/2 


44 



For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m, 1 foot per second = 0.3048 m/s. 
NOTE: See Table P2903.6 for w.s.f.u and Table 2903.6(1) for gallon-per-minute (gpm) flow rates, 
a. Based on velocity limitation: plastic — 12 fps; metal — 8 fps. 



P2903.8.5 Valving. Fixture valves, when installed, shall be 
located either at the fixture or at the manifold. If valves are 
installed at the manifold, they shall be labeled indicating the 
fixture served. 

P2903.8.6 Hose bibb bleed. A readily accessible air bleed 
shall be installed in hose bibb supplies at the manifold or at 
the hose bibb exit point. 

P2903.9 Valves. Valves shall be installed in accordance with 
Sections P2903.9.1 through P2903.9.3. 

P2903.9.1 Service valve. Each dwelling unit shall be pro- 
vided with an accessible main shutoff valve near the 
entrance of the water service. The valve shall be of a 
full-open type having nominal restriction to flow, with pro- 
vision for drainage such as a bleed orifice or installation of a 
separate drain valve. Additionally, the water service shall be 
valved at the curb or property line in accordance with local 
requirements. 



P2903.9.2 Water heater valve. A readily accessible 
full-open valve shall be installed in the cold-water supply 
pipe to each water heater at or near the water heater. 

P2903.9.3 Fixture valves and access. Valves serving indi- 
vidual fixtures, appliances, risers and branches shall be pro- 
vided with access. An individual shutoff valve shall be 
required on the fixture supply pipe to each plumbing fixture 
other than bathtubs and showers. 

P2903.9.4 Valve requirements. Valves shall be of an 
approved type and compatible with the type of piping mate- 
rial installed in the system. Ball valves, gate valves, globe 
valves and plug valves intended to supply drinking water 
shall meet the requirements of NSF 61. 

P2903.10 Hose bibb. Hose bibbs subject to freezing, including 
the "frost-proof type, shall be equipped with an accessible 
stop-and-waste-type valve inside the building so that they can 
be controlled and/or drained during cold periods. 



446 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



WATER SUPPLY AND DISTRIBUTION 



Exception: Frostproof hose bibbs installed such that the 
stem extends through the building insulation into an open 
heated or semiconditioned space need not be separately 
valved (see Figure P2903.10). 



SECTION P2904 
MATERIALS, JOINTS AND CONNECTIONS 

P2904.1 Soil and groundwater. The installation of water ser- 
vice pipe, water distribution pipe, fittings, valves, appurte- 
nances and gaskets shall be prohibited in soil and groundwater 
that is contaminated with solvents, fuels, organic compounds 
or other detrimental materials that cause permeation, corro- 
sion, degradation or structural failure of the water service or 
water distribution piping material. 

P2904.1.1 Investigation required. Where detrimental con- 
ditions are suspected by or brought to the attention of the 
building official, a chemical analysis of the soil and ground- 
water conditions shall be required to ascertain the accept- 
ability of the water service material for the specific 
installation. 

P2904.1.2 Detrimental condition. When a detrimental 
condition exists, approved alternate materials or alternate 
routing shall be required. 

P2904.2 Lead content. Pipe and fittings used in the water-sup- 
ply system shall have a maximum of 8 percent lead. 

P2904.3 Polyethylene plastic piping installation. Polyethyl- 
ene pipe shall be cut square using a cutter designed for plastic 
pipe. Except where joined by heat fusion, pipe ends shall be 



chamfered to remove sharp edges. Pipe that has been kinked 
shall not be installed. For bends, the installed radius of pipe 
curvature shall be greater than 30 pipe diameters or the coil 
radius when bending with the coil. Coiled pipe shall not be bent 
beyond straight. Bends shall not be permitted within 10 pipe 
diameters of any fitting or valve. Joints between polyethylene 
plastic pipe and fittings shall comply with Sections P2904.3.1 
and P2904.3.2. 

P2904.3.1 Heat-fusion joints. Joint surfaces shall be clean 
and free from moisture. Joint surfaces shall be heated to 
melting temperature and joined. The joint shall be undis- 
turbed until cool. Joints shall be made in accordance with 
ASTM D 2657. 

P2904.3.2 Mechanical joints. Mechanical joints shall be 
installed in accordance with the manufacturer's installation 
instructions. 

P2904.4 Water service pipe. Water service pipe shall conform 
to NSF 61 and shall conform to one of the standards listed in 
Table P2904.4. Water service pipe or tubing, installed under- 
ground and outside of the structure, shall have a minimum 
working pressure rating of 160 pounds per square inch at 73°F 
(1103 kPa at 23 °C). Where the water pressure exceeds 160 
pounds per square inch (1 103 kPa), piping material shall have a 
rated working pressure equal to or greater than the highest 
available pressure. Water service piping materials not 
third-party certified for water distribution shall terminate at or 
before the full open valve located at the entrance to the struc- 
ture. Ductile iron water service piping shall be cement mortar 
lined in accordance with AWWA CI 04. 



INSULATED 
FRAME WALL 



SUPPLY LINE 




FROSTPROOF 
HOSE BIBB 



FOUNDATION WALL 



HEATED BASEMENT 



FIGURE P2903.10 
TYPICAL FROSTPROOF HOSE BIBB INSTALLATION NOT REQUIRING SEPARATE VALUE 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



447 



WATER SUPPLY AND DISTRIBUTION 



P2904.4.1 Dual check- valve-type backflow preventer. 

Where a dual check- valve backflow preventer is installed on 
the water supply system, it shall comply with ASSE 1024 or 
CSA B64.6. 

P2904.4.2 Water service installation. Trenching, pipe 
installation and backfilling shall be in accordance with Sec- 
tion P2604. Water-service pipe is permitted to be located in 
the same trench with a building sewer provided such sewer 
is constructed of materials listed for underground use within 
a building in Section P3002.1. If the building sewer is not 
constructed of materials listed in Section P3002.1, the 
water-service pipe shall be separated from the building 
sewer by a minimum of 5 feet (1524 mm), measured hori- 
zontally, of undisturbed or compacted earth or placed on a 
solid ledge at least 12 inches (305 mm) above and to one 
side of the highest point in the sewer line. 

Exception: The required separation distance shall not 
apply where a water service pipe crosses a sewer pipe, 
provided that the water service pipe is sleeved to at least 5 
feet (1524 mm), horizontally from the sewer pipe center- 
line, on both sides of the crossing with pipe materials 
hsted in Tables P2904.4, P3002.1(l), P3002.1(2) or 
P3002.2. 



P2904.5 Water-distribution pipe. Water-distribution piping 
within dwelling units shall conform to NSF 61 and shall con- 
form to one of the standards listed in Table P2904.5. All 
hot-water-distribution pipe and tubing shall have a minimum 
pressure rating of 100 psi at 180°F (689 kPa at 82°C). 

P2904.5.1 Under concrete slabs. Inaccessible water distri- 
bution piping under slabs shall be copper water tube mini- 
mum Type M, brass, ductile iron pressure pipe, cross-linked 
polyethylene/aluminum/cross-linked polyethylene (PEX- 
AL-PEX) pressure pipe, polyethylene/aluminum/polyeth- 
ylene (PE-AL-PE) pressure pipe, chlorinated polyvinyl 
chloride (CPVC), polybutylene (PB), cross-linked polyeth- 
ylene (PEX) plastic pipe or tubing or polypropylene (PP) 
pipe or tubing, all to be installed with approved fittings or 
bends. The minimum pressure rating for plastic pipe or tub- 
ing installed under slabs shall be 100 pounds per square inch 
atl80°F(689kPaat82°C). 

P2904.6 Fittings. Pipe fittings shall be approved for installa- 
tion with the piping material installed, and shall conform to the 
respective pipe standards listed in Table P2904.6. Pipe fittings 
used in the water supply system shall also conform to NSF 61 . 



TABLE P2904.4 
WATER SERVICE PIPE 



MATERIAL 


STANDARD 


Acrylonitrile butadiene styrene (ABS) plastic pipe 


ASTM D 1527; ASTM D 2282 


Asbestos-cement pipe 


ASTM C 296 


Brass pipe 


ASTM B 43 


Chlorinated polyvinyl chloride (CPVC) plastic pipe 


ASTM D 2846; ASTM F 441; ASTM F 442; CSA B 137.6 


Copper or copper-alloy pipe 


ASTM B 42; ASTM B 302 


Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) 


ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 


Cross-linked polyethylene/aluminum/cross-linked polyethylene 
(PEX-AL-PEX) pipe 


ASTM F 1281; CSA CAN/CSAB137. 10 


Cross-linked polyethylene/aluminum/high-density polyethylene 
(PEX-AL-HDPE) 


ASTM F 1986 


Cross-linked polyethylene (PEX) plastic tubing 


ASTM F 876; ASTM F 877; CSA B 137.5 


Ductile iron water pipe 


AWWA C151; AWWA CI 15 


Galvanized steel pipe 


ASTM A 53 


Polybutylene (PB) plastic pipe and tubing 


ASTM D 2662; ASTM D 2666; ASTM D 3309; CSA B137.8M 


Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe 


ASTM F 1282; CSA CAN/CSA-B137.9M 


Polyethylene (PE) plastic pipe 


ASTM D 2104; ASTM D 2239; CSA-B137.1 


Polyethylene (PE) plastic tubing 


ASTM D 2737; CSA B 137.1 


Polypropylene (PP) plastic pipe or tubing 


ASTM F 2389; CSA B137.il 


Polyvinyl chloride (PVC) plastic pipe 


ASTM D 1785; ASTM D 2241; ASTM D 2672; CSA B 137.3 


Stainless steel (Type 304/304L) pipe 


ASTM A 312; ASTM A 778 


Stainless steel (Type 316/31 6L) pipe 


ASTM A 312; ASTM A 778 



448 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WATER SUPPLY AND DISTRIBUTION 



TABLE P2904.5 
WATER DISTRIBUTION PIPE 



MATERIAL 


STANDARD 


Brass pipe 


ASTM B 43 


Chlorinated polyvinyl chloride (CPVC) plastic pipe and tubing 


ASTM D 2846; ASTM F 441; ASTM F 442; CSA B 137.6 


Copper or copper-alloy pipe 


ASTM B 42; ASTM B 302 


Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) 


ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 


Cross-Unked polyethylene (PEX) plastic tubing 


ASTM F 877; CSA B 137.5 


Cross-linked polyethylene/aluminum/cross-linked polyethylene 
(PEX-AL-PEX) pipe 


ASTM F 1281; CSACAN/CSA-B137.10 


Cross-linked polyethylene/aluminum/high-density polyethylene 
(PEX-AL-HDPE) 


ASTM F 1986 


Galvanized steel pipe 


ASTM A 53 


Polybutylene (PB) plastic pipe and tubing 


ASTM D 3309; CSA CAN3-B 137.8 


Polyethylene/aluminum/polyethylene (PE-AL-PE) composite pipe 


ASTM F 1282 


Polypropylene (PP) plastic pipe or tubing 


ASTM F 2389; CSA B137.il 


Stainless steel (Type 304/304L) pipe 


ASTM A 312; ASTM A 778 


Stainless steel (Type 316/316L) pipe 


ASTM A 312; ASTM A 778 



TABLE P2904.6 
PIPE FITTINGS 



MATERIAL 


STANDARD 


Acrylonitrile butadiene styrene (ABS) plastic 


ASTM D 2468 


Brass 


ASTM F1974 


Cast-iron 


ASME B16.4; ASME B16.12 


Chlorinated polyvinyl chloride (CPVC) plastic 


ASTM F 437; ASTM F 438; ASTM F 439; CSA B 137.6 


Copper or copper alloy 


ASME B16.15; ASME B16.18; ASME B16.22; 
ASME B 16.23; ASME B 16.26; ASME B 16.29 


Cross-linked polyethylene/aluminum/high-density polyethylene 
(PEX-AL-HDPE) 


ASTM F 1986 


Fittings for cross-linked polyethylene (PEX) plastic tubing 


ASTM F 877; ASTM F 1807; ASTM F 1960; ASTM F 2080; 
ASTM F 2159; CSA B137.5 


Gray iron and ductile iron 


AWWA CllO; AWWA C153 


Malleable iron 


ASME B 16.3 


Polybutylene (PB) plastic 


CSAB137.8 


Polyethylene (PE) plastic 


ASTM D 2609; CSA B 137.1 


Polypropylene (PP) plastic pipe or tubing 


ASTM F 2389; CSA B137.il 


Polyvinyl chloride (PVC) plastic 


ASTM D 2464; ASTM D 2466; ASTM D 2467; CSA B 137.2 


Stainless steel (Type 304/304L) pipe 


ASTM A 312; ASTM A 778 


Stainless steel (Type 316/316L) pipe 


ASTM A 312; ASTM A 778 


Steel 


ASME B 16.9; ASME B16.il; ASME B 16.28 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



449 



WATER SUPPLY AND DISTRIBUTION 



P2904.7 Flexible water connectors. Flexible water connec- 
tors, exposed to continuous pressure, shall conform to ASME 
Al 12.18.6. Access shall be provided to all flexible water con- 
nectors. 

P2904.8 Joint and connection tightness. Joints and connec- 
tions in the plumbing system shall be gas tight and water tight 
for the intended use or required test pressure. 

P2904.9 Plastic pipe joints. Joints in plastic piping shall be 
made with approved fittings by solvent cementing, heat fusion, 
corrosion-resistant metal clamps with insert fittings or com- 
pression connections. Flared joints for polyethylene pipe are 
permitted in accordance with Section P2904.3. 

P2904.9.1 Solvent cementing. Solvent-cemented joints 
shall comply with Sections P2904.9.1.1 through 
P2904.9.1.3. 

P2904.9.1.1 ABS plastic pipe. Solvent cement for ABS 
plastic pipe conforming to ASTM D 2235 shall be 
applied to all joint surfaces. 

P2904.9.1.2 CPVC plastic pipe. Joint surfaces shall be 
clean and free from moisture and an approved primer 
shall be applied. Solvent cement for CPVC plastic pipe, 
orange in color and conforming to ASTM F 493, shall be 
applied to all joint surfaces. The parts shall be joined 
while the cement is wet and in accordance with ASTM D 
2846 or ASTM F 493. Solvent-cement joints shall be 
permitted above or below ground. 

Exception: A primer is not required where all of the 
following conditions apply: 

1 . The solvent cement used is third-party certified 
as conforming to ASTM F 493. 

2. The solvent cement used is yellow in color. 

3. The solvent cement is used only for joining 
Vj-inch (13 mm) through 2-inch (5 1 mm) diam- 
eter CPVC pipe and fittings. 

4. The CPVC pipe and fittings are manufactured 
in accordance with ASTM D 2846. 

P2904.9.1.3 PVC plastic pipe. A purple primer that 
conforms to ASTM F 656 shall be applied to PVC sol- 
vent cemented joints. Solvent cement for PVC plastic 
pipe conforming to ASTM D 2564 shall be applied to all 
joint surfaces. 

P2904.9.1.4 Cross-linked polyethylene plastic (PEX). 

Joints between cross-linked polyethylene plastic tubing 
or fittings shall comply with Section P2904.9. 1.4.1 or 
Section P2904.9. 1.4.2. 

P2904.9.1.4.1 Flared joints. Flared pipe ends shall 
be made by a tool designed for that operation. 

P2904.9.1.4.2 Mechanical joints. Mechanical joints 
shall be installed in accordance with the manufac- 
turer's instructions. Fittings for cross-linked polyeth- 
ylene (PEX) plastic tubing as described in ASTM F 
877, ASTM F 1807, ASTM F 1960, and ASTM F 
2080 shall be installed in accordance with the manu- 
facturer's installation instructions. 



P2904.10 Polypropylene (PP) plastic. Joints between PP 
plastic pipe and fittings shall comply with Section P2904.10.1 
orP2904.10.2. 

P2904.10.1 Heat-fusion joints. Heat fusion joints for poly- 
propylene pipe and tubing joints shall be installed with 
socket-type heat-fused polypropylene fittings, butt-fusion 
polypropylene fittings or electrofusion polypropylene fit- 
tings. Joint surfaces shall be clean and free from moisture. 
The joint shall be undisturbed until cool. Joints shall be 
made in accordance with ASTM F 2389. 

P2904.10.2 Mechanical and compression sleeve joints. 

Mechanical and compression sleeve joints shall be installed 
in accordance with the manufacturer's installation instruc- 
tions. 

P2904.ll Stainless steel. Joints between stainless steel pipe 
and fittings shall comply with Sections P2904.11.1 and 
P2904.11.2. 

P2904.11.1 Mechanical joints. Mechanical joints shall be 
installed in accordance with the manufacturer's instruc- 
tions. 

P2904.11.2 Welded joints. Joint surfaces shall be cleaned. 
The joint shall be welded autogenously or with an approved 
filler metal in accordance with ASTM A 312. 

P2904.12 Threaded pipe joints. Threaded joints shall con- 
form to American National Taper Pipe Thread specifications. 
Pipe ends shall be deburred and chips removed. Pipe joint com- 
pound shall be used only on male threads. 

P2904.13 Soldered joints. Soldered joints in tubing shall be 
made with fittings approved for water piping and shall conform 
to ASTM B 828. Surfaces to be soldered shall be cleaned 
bright. The joints shall be properly fluxed and made with 
approved solder. Solders and fluxes used in potable water-sup- 
ply systems shall have a maximum of 0.2 percent lead. Fluxes 
shall conform to ASTM B 813. 

P2904.14 Flared joints. Flared joints in water tubing shall be 
made with approved fittings. The tubing shall be reamed and 
then expanded with a flaring tool. 

P2904.15 Underground joints. Joints in polybutylene (PB) 
plastic pipe or tubing underground or under a concrete floor 
slab shall be installed using heat fusion, in accordance with the 
manufacturer's installation instructions. Joints in copper pipe 
or tube installed in a concrete floor slab or under a concrete 
floor slab on grade shall be installed using wrought-copper fit- 
tings and brazed joints. 

P2904.16 Above-ground joints. Joints within the building 
between copper pipe, polybutylene tubing or CPVC tubing, in 
any combination with compatible outside diameters, are per- 
mitted to be made with the use of approved push-in mechanical 
fittings of a pressure-lock design. 

P2904.17 Joints between different materials. Joints between 
different piping materials shall be made in accordance with 
Sections P2904.17.1, P2904.17.2 and P2904.17.3 or with a 
mechanical joint of the compression or mechanical sealing 
type having an elastomeric seal conforming to ASTM D 1869 
or ASTM F 477. Joints shall be installed in accordance with the 
manufacturer's instructions. 



450 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



WATER SUPPLY AND DISTRIBUTION 



P2904.17.1 Copper or copper-alloy tubing to galvanized 
steel pipe. Joints between copper or copper-alloy tubing 
and galvanized steel pipe shall be made with a brass fitting 
or dielectric fitting. The copper tubing shall be joined to the 
fitting in an approved manner, and the fitting shall be 
screwed to the threaded pipe. 

P2904.17.2 Plastic pipe or tubing to other piping mate- 
rial. Joints between different grades of plastic pipe or 
between plastic pipe and other piping material shall be made 
with an approved adapter fitting. Joints between plastic pipe 
and cast-iron hub pipe shall be made by a caulked joint or a 
mechanical compression joint. 

P2904.17.3 Stainless steel. Joints between stainless steel 
and different piping materials shall be made with a mechan- 
ical joint of the compression or mechanical-sealing type or a 
dielectric fitting. 

P2904.18 Press joints. Press-type mechanical joints in copper 
tubing shall be made in accordance with the manufacturer's 
instructions using approved tools which affix the copper fitting 
with integral 0-ring to the tubing. 



SECTION P2905 
CHANGES IN DIRECTION 

P2905.1 Bends. Changes in direction in copper tubing are per- 
mitted to be made with bends having a radius of not less than 
four diameters of the tube, providing such bends are made by 
use of forming equipment that does not deform or create loss in 
cross-sectional area of the tube. 



SECTION P2906 
SUPPORT 

P2906.1 General. Pipe and tubing support shall conform to 
Section P2605. 



SECTION P2907 
DRINKING WATER TREATMENT UNITS 

P2907.1 Design. Drinking water treatment units shall meet the 
requirements of NSF 42, NSF 44 or NSF 53. 

P2907.2 Reverse osmosis drinking water treatment units. 

Point-of-use reverse osmosis drinking water treatment units, 
designed for residential use, shall meet the requirements of 
NSF 58. Waste or discharge from reverse osmosis drinking 
water treatment units shall enter the drainage system through 
an air gap or an air gap device that meets the requirements of 
NSF 58. 

P2907.3 Connection tubing. The tubing to and from drinking 
water treatment units shall be of a size and material as recom- 
mended by the manufacturer. The tubing shall comply with 

NSF 14, NSF 42, NSF 44, NSF 53, NSF 58 or NSF 61. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



451 



452 2006 INTERNATIONAL RESIDENTIAL CODE*' 



CHAPTER 30 

SANITARY DRAINAGE 



SECTION P3001 
GENERAL 

P3001.1 Scope. The provisions of this chapter shall govern the 
materials, design, construction and installation of sanitary drain- 
age systems. Plumbing materials shall conform to the require- 
ments of this chapter. The drainage, waste and vent (DWV) 
system shall consist of all piping for conveying wastes from 
plumbing fixtures, appliances and appurtenances, including fix- 
ture traps; above-grade drainage piping; below-grade drains 
within the building (building drain); below- and above-grade 
venting systems; and piping to the pubhc sewer or private septic 
system. 

P3001.2 Protection from freezing. No portion of the above 
grade DWV system other than vent terminals shall be located 
outside of a building, in attics or crawl spaces, concealed in out- 
side walls, or in any other place subjected to freezing tempera- 
tures unless adequate provision is made to protect them from 
freezing by insulation or heat or both, except in locaUties having 
a winter design temperature above 32°F (0°C) (ASHRAE 97.5 
percent column, winter, see Chapter 3). 

P3001.3 Flood-resistant installation. In areas prone to flood- 
ing as estabhshed by Table R301 .2(1), drainage, waste and vent 
systems shall be located and installed to prevent infiltration of 
floodwaters into the systems and discharges from the systems 
into floodwaters. 



SECTION P3002 
MATERIALS 

P3002.1 Piping within buildings. Drain, waste and vent 
(DWV) piping in buildings shall be as shown in Tables 
P3002.1(l) and P3002.1(2) except that galvanized wrought- 
iron or galvanized steel pipe shall not be used underground and 
shall be maintained not less than 6 inches (152 mm) above 
ground. Allowance shall be made for the thermal expansion 
and contraction of plastic piping. 

P3002.2 Building sewer. Building sewer piping shall be as 
shown in Table P3002.2. Forced main sewer piping shall con- 
form to one of the standards for ABS plastic pipe, copper or 
copper-alloy tubing, PVC plastic pipe or pressure-rated pipe 
fisted in Table P3002.2. 

P3002.3 Fittings. Fittings shall be approved and compatible 
with the type of piping being used and shall be of a sanitary or 
DWV design for drainage and venting as shown in Table 
P3002.3. Water pipe fittings shall be permitted in engineer- 
designed systems where the design indicates compliance with 
Section P3 101. 2.1. 

P3002.3.1 Drainage. Drainage fittings shall have a smooth 
interior waterway of the same diameter as the piping served. 
All fittings shall conform to the type of pipe used. Drainage 
fittings shall have no ledges, shoulders or reductions which 
can retard or obstruct drainage flow in the piping. Threaded 



drainage pipe fittings shall be of the recessed drainage type, 
black or galvanized. Drainage fittings shall be designed to 
maintain one-fourth unit vertical in 12 units horizontal 
(2-percent slope) grade. 

P3002.4 Other materials. Sheet lead, lead bends, lead traps and 
sheet copper shall comply with Sections P3002.4.1 through 
P3002.4.3. 

P3002.4.1 Sheet lead. Sheet lead for the following uses 
shall weigh not less than indicated below: 

1. Flashing of vent terminals, 3 psf (15 kg/m^). 

2. Prefabricated flashing for vent pipes, 2V2 psf (12 
kg/m^). 

P3002.4.2 Lead bends and traps. Lead bends and lead 
traps shall not be less than Vg-inch (3 mm) wall thickness. 

P3002.4.3 Sheet copper. Sheet copper for the following 
uses shall weigh not less than indicated below: 

1. General use, 12 ounces per square feet (4 kg/m^). 

2. Flashing for vent pipes, 8 ounces per square feet (2.5 
kg/m^). 



SECTION P3003 
JOINTS AND CONNECTIONS 

P3003.1 Tightness. Joints and connections in the DWV sys- 
tem shall be gas tight and water tight for the intended use or 
pressure required by test. 

P3003.2 Prohibited joints. Running threads and bands shall 
not be used in the drainage system. Drainage and vent piping 
shall not be drilled, tapped, burned or welded. 

The following types of joints and connections shall be pro- 
hibited: 

1 . Cement or concrete. 

2. Mastic or hot-pour bituminous joints. 

3. Joints made with fittings not approved for the specific 
installation. 

4. Joints between different diameter pipes made with 
elastomeric rolling 0-rings. 

5. Solvent-cement joints between different types of plastic 
pipe. 

6. Saddle-type fittings. 

P3003.3 ABS plastic. Joints between ABS plastic pipe or fit- 
tings shall comply with Sections P3003.3. 1 through P3003.3.3. 

P3003.3.1 Mechanical joints. Mechanical joints on drain- 
age pipes shall be made with an elastomeric seal conforming 
to ASTM C 1 173, ASTM D 3212 or CSA B602. Mechanical 
joints shall be installed only in underground systems unless 
otherwise approved. Joints shall be installed in accordance 
with the manufacturer's installation instructions. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



453 



SANITARY DRAINAGE 



TABLE P3002.1(1) 
ABOVE-GROUND DRAINAGE AND VENT PIPE 



MATERIAL 


STANDARD 


Acrylonitrile butadiene styrene (ABS) plastic pipe 


ASTM D 2661; ASTM F 628; CSA B 181.1 


Brass pipe 


ASTM B 43 


Cast-iron pipe 


ASTM A 74; CISPI 301 ; ASTM A 888 


Coextruded composite ABS DWV schedule 40 IPS pipe (solid) 


ASTM F 1488 


Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core) ; 


ASTM F 1488 


Coextruded composite PVC DWV schedule 40 IPS pipe (solid) 


ASTM F 1488 


Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core) 


ASTM FUSS; ASTM F 891 


Coextruded composite PVC IPS-DR, PS 140, PS200 DWV 


ASTM F 1488 


Copper or copper-alloy pipe 


ASTM B 42; ASTM B 302 


Copper or copper-alloy tubing (Type K, L, M or DWV) 


ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 306 


Galvanized steel pipe 


ASTM A 53 


Polyolefm pipe 


CSAB181.3 


Polyvinyl chloride (PVC) plastic pipe (Type DWV) 


ASTM D 2665; ASTM D 2949; CSA B181.2; 
ASTM F 1488 


Stainless steel drainage systems, Types 304 and 316L 


ASMEAl 12.3.1 



TABLE P3002.1(2) 
UNDERGROUND BUILDING DRAINAGE AND VENT PIPE 



MATERIAL 


STANDARD 


Acrylonitrile butadiene styrene (ABS) plastic pipe 


ASTM D 2661; ASTM F 628; CSA B181.1 


Asbestos-cement pipe 


ASTM C 428 


Cast-iron pipe 


ASTM A 74; CISPI 301; ASTM A 888 


Coextruded composite ABS DWV schedule 40 IPS pipe (solid) 


ASTM F 1488 


Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core) 


ASTM F 1488 


Coextruded composite PVC DWV schedule 40 IPS pipe (sohd) 


ASTM F 1488 


Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core) 


ASTM F 891; ASTM F 1488 


Coextruded composite PVC IPS-DR, PS 140, PS200 DWV 


ASTM F 1488 


Copper or copper alloy tubing (Type K, L, M or DWV) 


ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 306 


Polyolefin pipe 


ASTM F 1412; CSA B18I.3 


Polyvinyl chloride (PVC) plastic pipe (Type DWV) 


ASTM D 2665; ASTM D 2949; CSA B181.2 


Stainless steel drainage systems. Type 316L 


ASMEAl 12.3.1 



P3003.3.2 Solvent cementing. Joint surfaces shall be clean 
and free from moisture. Solvent cement that conforms to 
ASTM D 2235 or CSA B 181.1 shall be appUed to all joint 
surfaces. The joint shall be made while the cement is wet. 
Joints shall be made in accordance with ASTM D 2235, 
ASTM D 2661, ASTM F 628 or CSA B 181.1. Solvent- 
cement joints shall be permitted above or below ground. 

P3003.3.3 Threaded joints. Threads shall conform to 
ASME B 1.20.1. Schedule 80 or heavier pipe shall be per- 
mitted to be threaded with dies specifically designed for 
plastic pipe. Approved thread lubricant or tape shall be 
applied on the male threads only. 



P3003.4 Asbestos-cement. Joints between asbestos-cement 
pipe or fittings shall be made with a sleeve coupling of the same 
composition as the pipe, sealed with an elastomeric ring con- 
forming to ASTM D 1869. 

P3003.5 Brass. Joints between brass pipe or fittings shall com- 
ply with Sections P3003.5.1 through P3003.5.3. 

P3003.5.1 Brazed joints. All joint surfaces shall be cleaned. 
An approved flux shall be applied where required. The joint 
shall be brazed with a filler metal conforming to AWS A5 . 8 . 

P3003.5.2 Mechanical joints. Mechanical joints shall be 
installed in accordance with the manufacturer's installation 
instructions. 



454 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



SANITARY DRAINAGE 



TABLE P3002.2 
BUILDING SEWER PIPE 


MATERIAL 


STANDARD 


Acrylonitrile butadiene styrene (ABS) plastic pipe 


ASTM D 2661; ASTM D 2751; ASTM F 628 


Asbestos-cement pipe 


ASTM C 428 


Cast-iron pipe 


ASTM A 74; ASTM A 888; CISPI 301 


Coextruded composite ABS DWV schedule 40 IPS pipe (solid) 


ASTM F 1488 


Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core) 


ASTM F 1488 


Coextruded composite PVC DWV schedule 40 IPS pipe (solid) 


ASTM F 1488 


Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core) 


ASTM F 1488; ASTM F 891 


Coextruded composite PVC IPS-DR-PS DWV, PS 140, PS200 


ASTM F 1488 


Coextruded composite ABS sewer and drain DR-PS in PS35, PS50, PS 100, 
PS 140, PS200 


ASTM F 1488 


Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS 100, 
PS 140, PS200 


ASTM F 1488 


Coextruded composite PVC sewer and drain PS 25, PS 50, PS 100 
(cellular core) 


ASTM F 891 


Concrete pipe 


ASTM C 14; ASTM C 76; CSA A257.1M; CSA A257.2M 


Copper or copper-alloy tubing (Type K or L) 


ASTM B 75; ASTM B 88; ASTM B 251 


Polyethylene (PE) plastic pipe (SDR-PR) 


ASTM F 714 


Polyolefm pipe 


ASTM F 1412; CSA B181.3 


Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR 26, SDR 35, 
SDR41,PS50orPS100) 


ASTM D 2665; ASTM D 2949; ASTM D 3034; ASTM F 
1412; CSA B182.2; CSA B182.4 


Stainless steel drainage systems, Types 304 and 316L 


ASMEAl 12.3.1 


Vitrified clay pipe 


ASTM C 425; ASTM C 700 



TABLE P3002.3 
PIPE FITTINGS 



MATERIAL 


STANDARD 


Acrylonitrile butadiene styrene (ABS) plastic pipe 


ASTM D 3311; CSA B181.I; ASTM D 2661 


Cast-iron pipe 


ASME B 16.12; ASTM A 74; ASTM A 888; CISPI 301 


Coextruded composite ABS DWV schedule 40 IPS pipe 
(solid or cellular core) 


ASTM D 2661; ASTM D 3311; ASTM F 628 


Coextruded composite ABS DWV schedule 40 IPS-DR, PS 140, PS 200 
(solid or cellular core) 


ASTM D 2665; ASTM D 3311; ASTM F 891 


Coextruded composite ABS sewer and drain DR-PS in PS35, PS50, PS 100, 
PS140,PS200 


ASTM D 2751 


Coextruded composite PVC DWV schedule 40 IPS-DR, PS 140, PS200 
(solid and cellular core) 


ASTM D 2665; ASTM D 3311; ASTM F 891 


Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS 100, 
PS 140, PS200 


ASTM D 3034 


Copper or copper alloy 


ASME B 16.23; ASME B 16.29 


Gray iron and ductile iron 


AWWACllO 


Polyolefin 


ASTM F 1412; CSA B181.3 


Polyvinyl chloride (PVC) plastic pipe 


ASTM D 3311; ASTM D 2665; ASTM F 1412; ASTM F 
1866; CSA B 181.2; CSA B 182.4 


Stainless steel drainage systems. Types 304 and 316L 


ASMEAl 12.3.1 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



455 



SANITARY DRAINAGE 



P3003.5.3 Threaded joints. Threads shall conform to 
ASME B 1 .20. 1 . Pipe-joint compound or tape shall be applied 
on the male threads only. 

P3003.6 Cast iron. Joints between cast-iron pipe or fittings 
shall comply with Sections P3003.6.1 through P3003.6.3. 

P3003.6.1 Caulked joints. Joints for hub and spigot pipe 
shall be firmly packed with oakum or hemp. Molten lead 
shall be poured in one operation to a depth of not less than 1 
inch (25 mm). The lead shall not recede more than Vg inch (3 
mm) below the rim of the hub and shall be caulked tight. 
Paint, varnish or other coatings shall not be permitted on the 
jointing material until after the joint has been tested and 
approved. Lead shall be run in one pouring and shall be 
caulked tight. Acid-resistant rope and acidproof cement 
shall be permitted. 

P3003.6.2 Compression gasket joints. Compression gas- 
kets for hub and spigot pipe and fittings shall conform to 
ASTM C 564. Gaskets shall be compressed when the pipe is 
fully inserted. 

P3003.6.3 Mechanical joint coupling. Mechanical joint 
couplings for hubless pipe and fittings shall comply with 
CISPI 3 1 or ASTM C 1 277 . The elastomeric seahng sleeve 
shall conform to ASTM C 564 or CSA B602 and shall have 
a center stop. Mechanical joint couplings shall be installed 
in accordance with the manufacturer's installation instruc- 
tions. 

P3003.7 Concrete joints. Joints between concrete pipe and fit- 
tings shall be made with an elastomeric seal conforming to 
ASTM C 443, ASTM C 1 173, CSA A257.3M or CSA B602. 

P3003.8 Coextruded composite ABS pipe. Joints between 
coextruded composite pipe with an ABS outer layer or ABS fit- 
tings shall comply with Sections P3003.8.1 and P3003.8.2. 

P3003.8.1 Mechanical joints. Mechanical joints on drain- 
age pipe shall be made with an elastomeric seal conforming 
to ASTM C 1 173, ASTM D 3212 or CSA B602. Mechanical 
joints shall not be installed in above-ground systems, unless 
otherwise approved. Joints shall be installed in accordance 
with the manufacturer's installation instructions. 

P3003.8.2 Solvent cementing. Joint surfaces shall be clean 
and free from moisture. Solvent cement that conforms to 
ASTM D 2235 or CSA B181.1 shall be appUed to all joint 
surfaces. The joint shall be made while the cement is wet. 
Joints shall be made in accordance with ASTM D 2235, 
ASTM D 2661, ASTM F 628 or CSA B 18 1.1. Solvent- 
cement joints shall be permitted above or below ground. 

P3003.9 Coextruded composite PVC pipe. Joints between 
coextruded composite pipe with a PVC outer layer or PVC fit- 
tings shall comply with Sections P3003.9.1 and P3003.9.2. 

P3003.9.1 Mechanical joints. Mechanical joints on drain- 
age pipe shall be made with an elastomeric seal conforming 
to ASTM D 3212. Mechanical joints shall not be installed in 
above-ground systems, unless otherwise approved. Joints 
shall be installed in accordance with the manufacturer's 
installation instructions. 

P3003.9.2 Solvent cementing. Joint surfaces shall be clean 
and free from moisture. A purple primer that conforms to 



ASTM F 656 shall be applied. Solvent cement not purple in 
color and conforming to ASTM D 2564, CSA B 137.3 or 
CSA B 181.2 shall be applied to all joint surfaces. The joint 
shall be made while the cement is wet, and shall be in accor- 
dance with ASTM D 2855. Solvent-cement joints shall be 
permitted above or below ground. 

P3003.10 Copper pipe. Joints between copper or copper-alloy 
pipe or fittings shall comply with Sections P3003.10.1 through 
P3003.10.4. 

P3003.10.1 Brazed joints. All joint surfaces shall be 
cleaned. An approved flux shall be applied where required. 
The joint shall be brazed with a filler metal conforming to 
AWS A5.8. 

P3003.10.2 Mechanical joints. Mechanical joints shall be 
installed in accordance with the manufacturer's installation 
instructions. 

P3003.10.3 Soldered joints. Solder joints shall be made in 
accordance with the methods of ASTM B 828. All cut tube 
ends shall be reamed to the full inside diameter of the tube 
end. All joint surfaces shall be cleaned. A flux conforming 
to ASTM B 813 shall be applied. The joint shall be soldered 
with a solder conforming to ASTM B 32. 

P3003.10.4 Threaded joints. Threads shall conform to 
ASME B 1.20.1. Pipe-joint compound or tape shall be 
applied on the male threads only. 

P3003.ll Copper tubing. Joints between copper or cop- 
per-alloy tubing or fittings shall comply with Sections 
P3003.11.1 through P3003.1 1.3. 

P3003.11.1 Brazed joints. All joint surfaces shall be 
cleaned. An approved flux shall be applied where required. 
The joint shall be brazed with a filler metal conforming to 
AWS A5.8. 

P3003.11.2 Mechanical joints. Mechanical joints shall be 
installed in accordance with the manufacturer's installation 
instructions. 

P3003.11.3 Soldered joints. Solder joints shall be made in 
accordance with the methods of ASTM B 828. Cut tube 
ends shall be reamed to the full inside diameter of the tube 
end. All joint surfaces shall be cleaned. A flux conforming 
to ASTM B 813 shall be applied. The joint shall be soldered 
with a solder conforming to ASTM B 32. 

P3003.12 Steel. Joints between galvanized steel pipe or fittings 
shall comply with Sections P3003.12.1 and P3003.12.2. 

P3003.12.1 Threaded joints. Threads shall conform to 
ASME B 1.20.1. Pipe-joint compound or tape shall be 
applied on the male threads only. 

P3003.12.2 Mechanical joints. Joints shall be made with 
an approved elastomeric seal. Mechanical joints shall be 
installed in accordance with the manufacturer's installation 
instructions. 

P3003.13 Lead. Joints between lead pipe or fittings shall com- 
ply with Sections P3003.13.1 and P3003.13.2. 

P3003.13.1 Burned. Burned joints shall be uniformly fused 
together into one continuous piece. The thickness of the 



456 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



SANITARY DRAINAGE 



joint shall be at least as thick as the lead being joined. The 
filler metal shall be of the same material as the pipe. 

P3003.13.2 Wiped. Joints shall be fully wiped, with an 
exposed surface on each side of the joint not less than V4 
inch (19 mm). The joint shall be at least Vg inch (9.5 mm) 
thick at the thickest point. 

P3003.14 PVC plastic. Joints between PVC plastic pipe or fit- 
tings shall comply with Sections P3003.14.1 through 
P3003.14.3. 

P3003.14.1 Mechanical joints. Mechanical joints on drain- 
age pipe shall be made with an elastomeric seal conforming 
to ASTM C 1 173, ASTM D 3212 or CSA B602. Mechanical 
joints shall not be installed in above-ground systems, unless 
otherwise approved. Joints shall be installed in accordance 
with the manufacturer's installation instructions. 

P3003.14.2 Solvent cementing. Joint surfaces shall be 
clean and free from moisture. A purple primer that con- 
forms to ASTM F 656 shall be applied. Solvent cement not 
purple in color and conforming to ASTM D 2564, CSA 
B 137.3 or CSA B 1 8 1 .2 shall be apphed to all joint surfaces. 
The joint shall be made while the cement is wet, and shall be 
in accordance with ASTM D 2855. Solvent-cement joints 
shall be permitted above or below ground. 

P3003.14.3 Threaded joints. Threads shall conform to 
ASME B 1.20.1. Schedule 80 or heavier pipe shall be per- 
mitted to be threaded with dies specifically designed for 
plastic pipe. Approved thread lubricant or tape shall be 
applied on the male threads only. 

P3003.15 Vitrified clay. Joints between vitrified clay pipe or 
fittings shall be made with an elastomeric seal conforming to 
ASTM C 425, ASTM C 1 173 or CSA B602. 

P3003.16 Polyolefin plastic. Joints between polyolefin plastic 
pipe and fittings shall comply with Sections P3003.16.1 and 
P3003.16.2. 

P3003.16.1 Heat-fusion joints. Heat-fusion joints for 
polyolefin pipe and tubing joints shall be installed with 
socket-type heat-fused polyolefin fittings or electrofusion 
polyolefin fittings. Joint surfaces shall be clean and free 
from moisture. The joint shall be undisturbed until cool. 
Joints shall be made in accordance with ASTM F 1412 or 
CSAB181.3. 

P3003.16.2 Mechanical and compression sleeve joints. 

Mechanical and compression sleeve joints shall be installed 
in accordance with the manufacturer's installation instruc- 
tions. 

P3003.17 Polyethylene plastic pipe. Joints between polyeth- 
ylene plastic pipe and fittings shall be underground and shall 
comply with Section P3003.17.1 or P3003.17.2. 

P3003.17.1 Heat fusion joints. Joint surfaces shall be clean 
and free from moisture. All joint surfaces shall be cut, 
heated to melting temperature and joined using tools specif- 
ically designed for the operation. Joints shall be undisturbed 
until cool. Joints shall be made in accordance with ASTM D 
2657 and the manufacturer's installation instructions. 



P3003.17.2 Mechanical joints. Mechanical joints in drain- 
age piping shall be made with an elastomeric seal conform- 
ing to ASTM C 1173, ASTM D 3212 or CSA B602. 
Mechanical joints shall be installed in accordance with the 
manufacturer's installation instructions. 

P3003.18 Joints between different materials. Joints between 
different piping materials shall be made with a mechanical 
joint of the compression or mechanical-sealing type conform- 
ing to ASTM C 1173, ASTM C 1460 or ASTM C 1461. Con- 
nectors and adapters shall be approved for the application and 
such joints shall have an elastomeric seal conforming to ASTM 
C 425, ASTM C 443, ASTM C 564, ASTM C 1440, ASTM D 
1869, ASTM F 477, CSA A257.3M or CSA B602, or as 
required in Sections P3003.18.1 through P3003.18.6. Joints 
between glass pipe and other types of materials shall be made 
with adapters having a TFE seal. Joints shall be installed in 
accordance with the manufacturer's installation instructions. 

P3003.18.1 Copper or copper-alloy tubing to cast-iron 
hub pipe. Joints between copper or copper-alloy tubing and 
cast-iron hub pipe shall be made with a brass ferrule or com- 
pression joint. The copper or copper-alloy tubing shall be 
soldered to the ferrule in an approved manner, and the fer- 
rule shall be joined to the cast-iron hub by a caulked joint or 
a mechanical compression joint. 

P3003.18.2 Copper or copper-alloy tubing to galvanized 
steel pipe. Joints between copper or copper-alloy tubing 
and galvanized steel pipe shall be made with a brass con- 
verter fitting or dielectric fitting. The copper tubing shall be 
soldered to the fitting in an approved manner, and the fitting 
shall be screwed to the threaded pipe. 

P3003.18.3 Cast-iron pipe to galvanized steel or brass 
pipe. Joints between cast-iron and galvanized steel or brass 
pipe shall be made by either caulked or threaded joints or 
with an approved adapter fitting. 

P3003.18.4 Plastic pipe or tubing to other piping mate- 
rial. Joints between different types of plastic pipe or 
between plastic pipe and other piping material shall be made 
with an approved adapter fitting. Joints between plastic pipe 
and cast-iron hub pipe shall be made by a caulked joint or a 
mechanical compression joint. 

P3003.18.5 Lead pipe to other piping material. Joints 
between lead pipe and other piping material shall be made 
by a wiped joint to a caulking ferrule, soldering nipple, or 
bushing or shall be made with an approved adapter fitting. 

P3003.18.6 Stainless steel drainage systems to other 
materials. Joints between stainless steel drainage systems 
and other piping materials shall be made with approved 
mechanical couplings. 

P3003.19 Joints between drainage piping and water closets. 

Joints between drainage piping and water closets or similar fix- 
tures shall be made by means of a closet flange compatible with 
the drainage system material, securely fastened to a structur- 
ally firm base. The inside diameter of the drainage pipe shall 
not be used as a socket fitting for a four by three closet flange. 
The joint shall be bolted, with an approved gasket, flange to fix- 
ture connection complying with ASME Al 12.4.3 or setting 
compound between the fixture and the closet flange. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



457 



SANITARY DRAINAGE 



SECTION P3004 
DETERMINING DRAINAGE FIXTURE UNITS 

P3004.1 DWV system load. The load on DWV-system piping 
shall be computed in terms of drainage fixture unit (d.f .u.) val- 
ues in accordance with Table P3004. 1 . 



SECTION P3005 
DRAINAGE SYSTEM 

P3005.1 Drainage fittings and connections. Changes in 
direction in drainage piping shall be made by the appropriate 
use of sanitary tees, wyes, sweeps, bends or by a combination 
of these drainage fittings in accordance with Table P3005.1. 
Change in direction by combination fittings, heel or side inlets 
or increasers shall be installed in accordance with Table 
P3005.1 and Sections P3005.1.1 through P3005.1.4. based on 
the pattern of flow created by the fitting. 



TABLE P3004.1 
DRAINAGE FIXTURE UNIT (d.f.u.) VALUES FOR VARIOUS PLUMBING FIXTURES 



TYPE OF FIXTURE OR GROUP OF FIXTURES 


DRAINAGE FIXTURE UNIT VALUE (d.f.u.)^ 


Bar sink 


1 


Bathtub (with or without shower head and/or whirlpool attachments) 


2 


Bidet 


1 


Clothes washer standpipe 


2 


Dishwasher 


2 


Floor drain'' 





Kitchen sink 


2 


Lavatory 


1 


Laundry tub 


2 


Shower stall 


2 


Water closet (1.6 gallons per flush) 


3 


Water closet (greater than 1.6 gallons per flush) 


4 


Full-bath group with bathtub (with 1.6 gallon per flush water closet, and With or without 
shower head and/or whirlpool attachment on the bathtub or shower stall) 


5 


Full-bath group with bathtub (water closet greater than 1.6 gallon per flush, and with or 
without shower head and/or whirlpool attachment on the bathtub or shower stall) 


6 


Half -bath group (1.6 gallon per flush water closet plus lavatory) 


4 


Half-bath group (water closet greater than 1.6 gallon per flush plus lavatory) 


5 


Kitchen group (dishwasher and sink with or without garbage grinder) 


2 


Laundry group (clothes washer standpipe and laundry tub) 


3 


Multiple-bath groups'^: 
1.5 baths 

2 baths 
2.5 baths 

3 baths 
3.5 baths 


7 
8 
9 
10 
11 



For SI: 1 gallon = 3.785 L. 

a. For a continuous or semicontinuous flow into a drainage system, such as from a pump or similar device, 1 .5 fixture units shall be allowed per gpm of flow. For a fix- 
ture not listed, use the highest d.f u. value for a similar listed fixture. 

b. A floor drain itself adds no hydraulic load. However, where used as a receptor, the fixture unit value of the fixture discharging into the receptor shall be applicable. 

c. Add 2 d.f u. for each additional full bath. 



458 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



SANITARY DRAINAGE 



TABLE P3005.1 
FITTINGS FOR CHANGE IN DIRECTION 



TYPE OF FITTING 
PATTERN 


CHANGE IN DIRECTION 


Horizontal to 
vertical'' 


Vertical to 
horizontal 


Horizontal to 
horizontal 


Sixteenth bend 


X 


X 


X 


Eighth bend 


X 


X 


X 


Sixth bend 


X 


X 


X 


Quarter bend 


X 


X^ 


X'^ 


Short sweep 


X 


Xa,b 


X^ 


Long sweep 


X 


X 


X 


Sanitary tee 


X'^ 


— 


— 


Wye 


X 


X 


X 


Combination wye 
and eighth bend 


X 


X 


X 



For SI: 1 inch = 25.4 mm. 

a. The fittings shall only be permitted for a 2-inch or smaller fixture drain. 

b. Three inches and larger 

c. For a limitation on multiple connection fittings, see Section P3005.1.1. 

P3005.1.1 Horizontal to vertical (multiple connection 
fittings). Double fittings such as double sanitary tees and 
tee-wyes or approved multiple connection fittings and 
back-to-back fixture arrangements that connect two or more 
branches at the same level shall be permitted as long as 
directly opposing connections are the same size and the dis- 
charge into directly opposing connections is from similar 
fixture types or fixture groups. Double sanitary tee patterns 
shall not receive the discharge of back-to-back water closets 
and fixtures or appliances with pumping action discharge. 

Exception: Back-to-back water closet connections to 
double sanitary tee patterns shall be permitted where the 
horizontal developed length between the outlet of the 
water closet and the connection to the double sanitary tee 
is 18 inches (457 mm) or greater. 

P3005.1.2 Heel- or side-inlet quarter bends, drainage. 

Heel-inlet quarter bends shall be an acceptable means of 
connection, except where the quarter bends serves a water 
closet. A low-heel inlet shall not be used as a wet- vented 
connection. Side-inlet quarter bends shall be an acceptable 
means of connection for both drainage, wet venting and 
stack venting arrangements. 

P3005.1.3 Heel- or side-inlet quarter bends, venting. 

Heel-inlet or side-inlet quarter bends, or any arrangement of 
pipe and fittings producing a similar effect, shall be accept- 
able as a dry vent where the inlet is placed in a vertical posi- 
tion. The inlet is permitted to be placed in a horizontal 
position only where the entire fitting is part of a dry vent 
arrangement. 

P3005.1.4 Water closet connection between flange and 
pipe. One-quarter bends 3 inches (76 mm) in diameter shall 
be acceptable for water closet or similar connections, pro- 
vided a 4-inch by 3-inch (102 mm by 76 mm) flange is 



installed to receive the closet fixture horn. Alternately, a 
4-inch by 3-inch (102 mm by 76 mm) elbow shall be accept- 
able with a 4-inch (102 mm) flange. 

P3005.1.5 Dead ends. Dead ends shall be prohibited except 
where necessary to extend a cleanout or as an approved part 
of a rough-in more than 2 feet (610 mm) in length. 

P3005.1.6 Provisions for future fixtures. Where drainage 
has been roughed-in for future fixtures, the drainage unit 
values of the future fixtures shall be considered in determin- 
ing the required drain sizes. Such future installations shall 
be terminated with an accessible permanent plug or cap fit- 
ting. 

P3005.1.7 Change in size. The size of the drainage piping 
shall not be reduced in size in the direction of the flow. A 
4-inch by 3-inch (102 mm by 76 mm) water closet connec- 
tion shall not be considered as a reduction in size. 

P3005.2 Drainage pipe cleanouts. Drainage pipe cleanouts 
shall comply with Sections P3005.2.1 through P3005.2.11. 

Exception: These provisions shall not apply to pressurized 
building drains and building sewers that convey the dis- 
charge of automatic pumping equipment to a gravity drain- 
age system. 

P3005.2.1 Materials. Cleanouts shall be liquid and gas 
tight. Cleanout plugs shall be brass or plastic. 

P3005.2.2 Spacing. Cleanouts shall be installed not more 
than 100 feet (30 480 mm) apart in horizontal drainage lines 
measured from the upstream entrance of the cleanout. I 

P3005.2.3 Underground drainage cleanouts. When 
installed in underground drains, cleanouts shall be extended 
vertically to or above finished grade either inside or outside 
the building. 

P3005.2.4 Change of direction. Cleanouts shall be 
installed at each fitting with a change of direction more than 
45 degrees (0.79 rad) in the building sewer, building drain 
and horizontal waste or soil lines. Where more than one 
change of direction occurs in a run of piping, only one 
cleanout shall be required in each 40 feet (12 192 mm) of 
developed length of the drainage piping. 

P3005.2.5 Accessibility. Cleanouts shall be accessible. 
Minimum clearance in front of cleanouts shall be 18 inches 
(457 mm) on 3-inch (76 mm) and larger pipes, and 12 inches 
(305 mm) on smaller pipes. Concealed cleanouts shall be 
provided with access of sufficient size to permit removal of 
the cleanout plug and rodding of the system. Cleanout plugs 
shall not be concealed by permanent finishing material. 

P3005.2.6 Base of stacks. Accessible cleanouts shall be 
provided near the base of each vertical waste or soil stack. 
Alternatively, such cleanouts shall be installed outside the 
building within 3 feet (914 mm) of the building wall. 

P3005.2.7 Building drain and building sewer junction. 

There shall be a cleanout near the junction of the building 
drain and building sewer. This cleanout shall be either inside 
or outside the building wall, provided that it is brought up to 
finish grade or to the lowest floor level. An approved 
two-way cleanout shall be permitted to serve as the required 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



459 



SANITARY DRAINAGE 



cleanout for both the building drain and the building sewer. 
The cleanout at the junction of the building drain and build- 
ing sewer shall not be required where a cleanout on a 3-inch 
(76 mm) or larger diameter soil stack is located within a 
developed length of 10 feet (3048 mm) of the building drain 
and building sewer junction. 

P3005.2.8 Direction of flow. Cleanouts shall be installed so 
that the cleanout opens to allow cleaning in the direction of 
the flow of the drainage line. 

P3005.2.9 Cleanout size. Cleanouts shall be the same nom- 
inal size as the pipe they serve up to 4 inches (102 mm). For 
pipes larger than 4 inches (102 mm) nominal size, the mini- 
mum size of the cleanout shall be 4 inches (102 mm). 

Exceptions: 

1. "P" trap connections with shp joints or ground 
joint connections, or stack cleanouts that are not 
more than one pipe diameter smaller than the drain 
served, shall be permitted. 

2. Cast-iron cleanouts sized in accordance with the 
referenced standards in Table P3002.3, ASTM A 
74 for hub and spigot fittings or ASTM A 888 or 
CISPI 301 for hubless fittings. 

P3005.2.10 Cleanout equivalent. A fixture trap or a fixmre 
with integral trap, readily removable without disturbing con- 
cealed piping shall be acceptable as a cleanout equivalent. 

P3005.2.11 Connections to cleanouts prohibited. Clean- 
out openings shall not be used for the installation of new fix- 
tures except where approved and an acceptable alternate 
cleanout is provided. 

P3005.3 Horizontal drainage piping slope. Horizontal drain- 
age piping shall be installed in uniform alignment at uniform 
slopes not less than V4 unit vertical in 12 units horizontal 
(2-percent slope) for 2V2-inch (64 mm) diameter and less, and 
not less than Vg unit vertical in 12 units horizontal (1 -percent 
slope) for diameters of 3 inches (76 mm) or more. 

P3005.4 Drain pipe sizing. Drain pipes shall be sized accord- 
ing to drainage fixture unit (d.f.u.) loads. The size of the drain- 
age piping shall not be reduced in size in the direction of flow. 
The following general procedure is permitted to be used: 

1 . Draw an isometric layout or riser diagram denoting fix- 
tures on the layout. 

2. Assign d.f.u. values to each fixture group plus individual 
fixtures using Table P3004.1. 

3. Starting with the top floor or most remote fixtures, work 
downstream toward the building drain accumulating d.f.u. 
values for fixture groups plus individual fixtures for each 
branch. Where multiple bath groups are being added, use 
the reduced d.f.u. values in Table P3004.1, which take 
into account probability factors of simultaneous use. 

4. Size branches and stacks by equating the assigned d.f.u. 
values to pipe sizes shown in Table P3005.4.1. 

5. Determine the pipe diameter and slope of the building 
drain and building sewer based on the accumulated d.f.u. 
values, using Table P3005.4.2. 



P3005.4.1 Fixture branch and stack sizing. 

1 . Branches and stacks shall be sized according to Table 
P3005.4.1. Below grade drain pipes shall not be less 
than IV2 inches (38 mm) in diameter. 

2. Minimum stack size. Drain stacks shall not be smaller 
than the largest horizontal branch connected. 

Exceptions: 

1. A 4-inch by 3-inch (102 mm by 76 mm) 
closet bend or flange. 

2. A 4-inch (102 mm) closet bend into a 3-inch 
(76 mm) stack tee shall be acceptable (see 
Section P3005. 1.4). 

TABLE P3005.4.1 

MAXIMUM FIXTURE UNITS ALLOWED TO BE CONNECTED 

TO BRANCHES AND STACKS 



NOMINAL PIPE SIZE 
(inches) 


ANY HORIZONTAL 
FIXTURE BRANCH 


ANY ONE VERTICAL 
STACK OR DRAIN 


IV/ 


— 


— 


IV^" 


3 


4 


2" 


6 


10 


2V2'' 


12 


20 


3 


20 


48 


4 


160 


240 



For SI: 1 inch = 25.4 mm. 

a. 1 V4-inch pipe size limited to a single-fixture drain or trap arm. See Table 
P3201.7. 

b. No water closets. 

P3005.4.2 Building drain and sewer size and slope. Pipe 
sizes and slope shall be determined from Table P3005.4.2 
on the basis of drainage load in fixture units (d.f.u.) com- 
puted from Table P3004. 1 . 

TABLE P3005.4.2 
MAXIMUM NUMBER OF FIXTURE UNITS ALLOWED TO BE 

CONNECTED TO THE BUILDING DRAIN, 
BUILDING DRAIN BRANCHES OR THE BUILDING SEWER 



DIAMETER OF 
PIPE (inches) 


SLOPE PER FOOT 


Vg inch 


V4 inch 


V2 inch 


V/2^'^ 


— 


Note a 


Note a 


2^ 


— 


21 


27 


2V2'' 


— 


24 


31 


3 


36 


42 


50 


4 


180 


216 


250 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. 1 ' /2-inch pipe size limited to a building drain branch serving not more than 
two waste fixtures, or not more than one waste fixture if serving a pumped 
discharge fixture or garbage grinder discharge. 

b. No water closets. 

P3005.5 Connections to offsets and bases of stacks. Hori- 
zontal branches shall connect to the bases of stacks at a point 
located not less than 1 times the diameter of the drainage stack 
downstream from the stack. Horizontal branches shall connect 
to horizontal stack offsets at a point located not less than 10 



460 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



SANITARY DRAINAGE 



•l 



times the diameter of the drainage stack downstream from the 
upper stack. 



SECTION P3006 
SIZING OF DRAIN PIPE OFFSETS 

P3006.1 Vertical offsets. An offset in a vertical drain, with a 
change of direction of 45 degrees (0.79 rad) or less from the 
vertical, shall be sized as a straight vertical drain. 

P3006.2 Horizontal offsets above the lowest branch. A stack 
with an offset of more than 45 degrees (0.79 rad) from the verti- 
cal shall be sized as follows: 

1 . The portion of the stack above the offset shall be sized as 
for a regular stack based on the total number of fixture 
units above the offset. 

2. The offset shall be sized as for a building drain in accor- 
dance with Table P3005.4.2. 

3 . The portion of the stack below the offset shall be sized as 
for the offset or based on the total number of fixture units 
on the entire stack, whichever is larger. 

P3006.3 Horizontal offsets below the lowest branch. In soil 
or waste stacks below the lowest horizontal branch, there shall 
be no change in diameter required if the offset is made at an 
angle not greater than 45 degrees (0.79 rad) from the vertical. If 
an offset greater than 45 degrees (0.79 rad) from the vertical is 
made, the offset and stack below it shall be sized as a building 
drain (see Table P3005.4.2). 



charged into the building gravity drainage system by automatic 
pumping equipment. 

P3007.2.1 Drainage piping. The system of drainage piping 
below the sewer level shall be installed and vented in a man- 
ner similar to that of the gravity system. Only such drains 
that must be lifted for discharge shall be discharged into 
sumps. All other drains shall be discharged by gravity. 

Exception: Macerating toilet systems shall be permitted 
as an alternate to the sewage pump or ejector system. The 
macerating toilet shall comply with ASME Al 12.3.4 or 
CSA B45.9 and shall be installed in accordance with the 
manufacturers' instructions. 



SECTION P3008 
BACKWATER VALVES 

P3008.1 General. Fixtures that have flood level rims located 
below the elevation of the next upstream manhole cover of the 
public sewer serving such fixtures shall be protected from 
backflow of sewage by installing an approved backwater valve. 
Fixtures having flood level rims above the elevation of the next 
upstream manhole shall not discharge through the backwater 
valve. Backwater valves shall be provided with access. 

P3008.2 Construction. Backwater valves shall have 
noncorrosive bearings, seats and self-aligning discs, and shall 
be constructed to ensure a positive mechanical seal. Valve 
access covers shall be water tight. 



SECTION P3007 
SUMPS AND EJECTORS 

P3007.1 Sewage ejectors or sewage pumps. A sewage ejec- 
tor, sewage pump, or grinder pump receiving discharge from a 
water closet shall have minimum discharge velocity of 1.9 feet 
per second (0.579 m/s) throughout the discharge piping to the 
point of connection with a gravity building drain, gravity sewer 
or pressure sewer system. A nongrinding pump or ejector shall 
be capable of passing a 1 V2-inch-diameter (38 mm) solid ball, 
and the discharge piping shall be not less than 2 inches (5 1 mm) 
in diameter. The discharge piping of grinding pumps shall be 
not less than 1 '/4 inches (32 mm) in diameter. A check valve and 
a gate valve located on the discharge side of the check valve 
shall be installed in the pump or ejector discharge piping 
between the pump or ejector and the drainage system. Access 
shall be provided to such valves. Such valves shall be located 
above the sump cover or, where the discharge pipe from the 
ejector is below grade, the valves shall be accessibly located 
outside the sump below grade in an access pit with a 
removeable access cover. 

Exception: Macerating toilet systems shall be permitted to 
have the discharge pipe sized in accordance with manufac- 
turer's instructions, but not less than 0.75 inch (19 mm) in 
diameter. 

P3007.2 Building drains below sewer (building subdrains). 

Building drains which cannot be discharged to the sewer by 
gravity flow shall be discharged into a tightly covered and 
vented sump from which the contents shall be lifted and dis- 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



461 



462 2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 31 

VENTS 



tf 



SECTION P3101 
VENT SYSTEMS 

P3101.1 General. This chapter shall govern the selection and 
installation of piping, tubing and fittings for vent systems. This 
chapter shall control the minimum diameter of vent pipes, cir- 
cuit vents, branch vents and individual vents, and the size and 
length of vents and various aspects of vent stacks and stack 
vents. Additionally, this chapter regulates vent grades and con- 
nections, height above fixtures and relief vents for stacks and 
fixture traps, and the venting of sumps and sewers. 

P3101.2 Trap seal protection. The plumbing system shall be 
provided with a system of vent piping that will permit the 
admission or emission of air so that the seal of any fixture trap 
shall not be subjected to a pneumatic pressure differential of 
more than 1 inch of water column (249 Pa). 

P3101.2.1 Venting required. Every trap and trapped fix- 
ture shall be vented in accordance with one of the venting 
methods specified in this chapter. 

P3101.3 Use limitations. The plumbing vent system shall not 
be used for purposes other than the venting of the plumbing 
system. 

P3101.4 Extension outside a structure. In climates where the 
97.5-percent value for outside design temperature is 0°F 
(-18°C) or less (ASHRAE 97.5-percent column, winter, see 
Chapter 3), vent pipes installed on the exterior of the structure 
shall be protected against freezing by insulation, heat or both. 
Vent terminals shall be protected from frost closure in accor- 
dance with Section P3 103.2. 

P3101.5 Flood resistance. In areas prone to floodings as 
established by Table R301.2(l), vents shall be located at or 
above the design flood elevation established in Section R324. 1 . 



SECTION P3102 
VENT STACKS AND STACK VENTS 

P3 102.1 Required vent extension. The vent system serving 
each building drain shall have at least one vent pipe that extends 
to the outdoors. 

P3 102.2 Installation. The required vent shall be a dry vent that 
connects to the building drain or an extension of a drain that 
connects to the building drain. Such vent shall not be an island 
fixture vent as permitted by Section P31 12. 

P3102.3 Size. The required vent shall be sized in accordance 
with Section P3 1 13. 1 based on the required size of the building 
drain. 



SECTION P3103 
VENT TERMINALS 

P3103.1 Roof extension. Open vent pipes that extend through 
a roof shall be terminated at least 6 inches (152 mm) above the 



roof or 6 inches (152 mm) above the anticipated snow accumu- I 
lation, whichever is greater, except that where a roof is to be | 
used for any purpose other than weather protection, the vent 
extension shall be run at least 7 feet (2 1 34 mm) above the roof. 

P3103.2 Frost closure. Where the 97.5-percent value for out- 
side design temperature is 0°F (-18°C) or less, every vent 
extension through a roof or wall shall be a minimum of 3 inches 
(76 mm) in diameter. Any increase in the size of the vent shall 
be made inside the structure a minimum of 1 foot (305 mm) 
below the roof or inside the wall. 

P3103.3 Flashings and sealing. The juncture of each vent pipe 
with the roof line shall be made water tight by an approved 
flashing. Vent extensions in walls and soffits shall be made 
weather tight by caulking. 

P3103.4 Prohibited use. Vent terminals shall not be used as a 
flag pole or to support flag poles, TV aerials, or similar items, 
except when the piping has been anchored in an approved man- 
ner. 

P3103.5 Location of vent terminal. An open vent terminal 
from a drainage system shall not be located less than 4 feet 
(1219 mm) directiy beneath any door, openable window, or 
other air intake opening of the building or of an adjacent build- 
ing, nor shall any such vent terminal be within 10 feet (3048 
mm) horizontally of such an opening unless it is at least 2 feet 
(610 mm) above the top of such opening. 

P3103.6 Extension through the wall. Vent terminals extend- 
ing through the wall shall terminate a minimum of 10 feet 
(3048 mm) from the lot hne and 10 feet (3048 mm) above the 
highest adjacent grade within 10 feet (3048 mm) horizontally 
of the vent terminal. Vent terminals shall not terminate under 
the overhang of a structure with soffit vents. Side wall vent ter- 
minals shall be protected to prevent birds or rodents from enter- 
ing or blocking the vent opening. 



SECTION P3104 
VENT CONNECTIONS AND GRADES 

3104.1 Connection. All individual branch and circuit vents 
shall connect to a vent stack, stack vent or extend to the open 
air. 

Exception: Individual, branch and circuit vents shall be 
permitted to terminate at an air admittance valve in accor- 
dance with Section P31 14. 

P3104.2 Grade. Vent and branch vent pipes shall be graded, 
connected and supported to allow moisture and condensate to 
drain back to the soil or waste pipe by gravity. 

P3104.3 Vent connection to drainage system. Every dry vent 
connecting to a horizontal drain shall connect above the center- 
line of the horizontal drain pipe. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



463 



VENTS 



P3104.4 Vertical rise of vent. Every dry vent shall rise verti- 
cally to a minimum of 6 inches (152 mm) above the flood level 
rim of the highest trap or trapped fixture being vented. 

P3104.5 Height above fixtures. A connection between a vent 
pipe and a vent stack or stack vent shall be made at least 6 
inches (152 mm) above the flood level rim of the highest fixture 
served by the vent. Horizontal vent pipes forming branch vents 
shall be at least 6 inches (152 mm) above the flood level rim of 
the highest fixture served. 

P3104.6 Vent for future fixtures. Where the drainage piping 
has been roughed-in for future fixtures, a rough-in connection 
for a vent shall be installed a minimum of one-half the diameter 
of the drain. The vent rough-in shall connect to the vent system 
or shall be vented by other means as provided in this chapter. 
The connection shall be identified to indicate that the connec- 
tion is a vent. 



SECTION P3105 
FIXTURE VENTS 

P3105.1 Distance of trap from vent. Each fixture trap shall 
have a protecting vent located so that the slope and the devel- 
oped length in the fixture drain from the trap weir to the vent fit- 
ting are within the requirements set forth in Table P3 105.1. 

Exception: The developed length of the fixture drain from 
the trap weir to the vent fitting for self-siphoning fixtures, 
such as water closets, shall not be limited. 

TABLE P3105.1 
MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT 



SIZE OF TRAP 
(inches) 


SLOPE 
(Inch per foot) 


DISTANCE FROM 
TRAP (feet) 


l'/4 


'4 


5 


\% 


'4 


6 


2 


'4 


8 


3 


^8 


12 


4 


'8 


16 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 
1 inch per foot = 83.3 mm/m. 

P3105.2 Fixture drains. The total fall in a fixture drain result- 
ing from pipe slope shall not exceed one pipe diameter, nor 
shall the vent pipe connection to a fixture drain, except for 
water closets, be below the weir of the trap. 

P3105.3 Crown vent. A vent shall not be installed within two 
pipe diameters of the trap weir. 



SECTION P3106 
INDIVIDUAL VENT 

P3106.1 Individual vent permitted. Each trap and trapped 
fixture is permitted to be provided with an individual vent. The 
individual vent shall connect to the fixture drain of the trap or 
trapped fixture being vented. 



SECTION P31 07 
COMMON VENT 

P3107.1 Individual vent as common vent. An individual vent 
is permitted to vent two traps or trapped fixtures as a common 
vent. The traps or trapped fixtures being common vented shall 
be located on the same floor level. 

P3107.2 Connection at the same level. Where the fixture 
drains being common vented connect at the same level, the vent 
connection shall be at the interconnection of the fixture drains 
or downstream of the interconnection. 

P3107.3 Connection at different levels. Where the fixture 
drains connect at different levels, the vent shall connect as a 
vertical extension of the vertical drain. The vertical drain pipe 
connecting the two fixture drains shall be considered the vent 
for the lower fixture drain, and shall be sized in accordance 
with Table P3 107.3. The upper fixture shall not be a water 
closet. 

TABLE P31 07.3 
COMMON VENT SIZES 



PIPE SIZE 
(inches) 


MAXIMUM DISCHARGE FROM 
UPPER FIXTURE DRAIN (d.f.u.) 


\% 


1 


2 


4 


2'/2 to 3 


6 



For SI: 1 inch = 25.4 mm. 



SECTION P3108 
WET VENTING 

P3108.1 Horizontal wet vent permitted. Any combination of 
fixtures within two bathroom groups located on the same floor 
level are permitted to be vented by a horizontal wet vent. The 
wet vent shall be considered the vent for the fixtures and shall 
extend from the connection of the dry vent along the direction 
of the flow in the drain pipe to the most downstream fixture 
drain connection. Each fixture drain shall connect horizontally 
to the horizontal branch being wet vented or shall have a dry 
vent. Only the fixtures within the bathroom groups shall con- 
nect to the wet- vented horizontal branch drain. Any additional 
fixtures shall discharge downstream of the horizontal wet vent. 

P3108.2 Vent connections. The dry vent connection to the wet 
vent shall be an individual vent or common vent to the lavatory, 
bidet, shower or bathtub. In vertical wet vent systems, the most 
upstream fixture drain connection shall be a dry-vented fixture 
drain connection. In horizontal wet-vent systems, not more 
than one wet- vented fixture drain shall discharge upstream of 
the dry-vented fixture drain connection. 

P3108.3 Size. Horizontal and vertical wet vents shall be of a 
minimum size as specified in Table P3 108.3, based on the fix- 
ture unit discharge to the wet vent. The dry vent serving the wet 
vent shall be sized based on the largest required diameter of 
pipe within the wet-vent system served by the dry vent. 



464 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



VENTS 



TABLE P31 08.3 
WET VENT SIZE 



TABLE P31 09.4 
WASTE STACK VENT SIZE 



WET VENT PIPE SIZE 
(inches) 


FIXTURE UNIT LOAD 
(d.f.u.) 


IV2 


1 


2 


4 


2V, 


6 


3 


12 


4 


32 



For SI: 1 inch = 25.4 mm. 

P3108.4 Vertical wet vent permitted. A combination of fix- 
tures located on the same floor level are permitted to be vented 
by a vertical wet vent. The vertical wet vent shall be considered 
the vent for the fixtures and shall extend from the connection of 
the dry vent down to the lowest fixture drain connection. Each 
wet- vented fixture shall connect independently to the vertical 
wet vent. All water closet drains shall connect at the same ele- 
vation. Other fixture drains shall connect above or at the same 
elevation as the water closet fixture drains. The dry vent con- 
nection to the vertical wet vent shall be an individual or com- 
mon vent serving one or two fixtures. 

P3108.5 Trap weir to wet vent distances. The maximum 
developed length of wet-vented fixture drains shall comply 
with Table P3 105.1. 



SECTION P31 09 
WASTE STACK VENT 

P3109.1 Waste stack vent permitted. A waste stack shall be 
considered a vent for all of the fixtures discharging to the stack 
where installed in accordance with the requirements of this sec- 
tion. 

P3109.2 Stack installation. The waste stack shall be vertical, 
and both horizontal and vertical offsets shall be prohibited 
between the lowest fixture drain connection and the highest 
fixture drain connection to the stack. Every fixture drain shall 
connect separately to the waste stack. The stack shall not 
receive the discharge of water closets or urinals. 

P3109.3 Stack vent. A stack vent shall be installed for the 
waste stack. The size of the stack vent shall be not less than the 
size of the waste stack. Offsets shall be permitted in the stack 
vent and shall be located at least 6 inches (152 mm) above the 
flood level of the highest fixture, and shall be in accordance 
with Section P3 104.5. The stack vent shall be permitted to con- 
nect with other stack vents and vent stacks in accordance with 
Section P3 113.3. 

P3109.4 Waste stack size. The waste stack shall be sized based 
on the total discharge to the stack and the discharge within a 
branch interval in accordance with Table P3 109.4. The waste 
stack shall be the same size throughout the length of the waste 
stack. 



STACK SIZE 
(inches) 


MAXIMUM NUMBER OF FIXTURE UNITS (d.f.u.) 


Total discharge into 
one branch interval 


Total discharge 
for stack 


l'/2 


1 


2 


2 


2 


4 


2'/, 


No limit 


8 


3 


No limit 


24 


4 


No limit 


50 



For SI: 1 inch = 25.4 mm. 



SECTION P31 10 
CIRCUIT VENTING 

P3110.1 Circuit vent permitted. A maximum of eight fixtures 
connected to a horizontal branch drain shall be permitted to be 
circuit vented. Each fixture drain shall connect horizontally to 
the horizontal branch being circuit vented. The horizontal 
branch drain shall be classified as a vent from the most down- 
stream fixture drain connection to the most upstream fixture 
drain connection to the horizontal branch. 

P3110.2 Vent connection. The circuit vent connection shall be 
located between the two most upstream fixture drains. The vent 
shall connect to the horizontal branch and shall be installed in 
accordance with Section P3 104. The circuit vent pipe shall not 
receive the discharge of any soil or waste. 

P3110.3 Slope and size of horizontal branch. The maximum 
slope of the vent section of the horizontal branch drain shall be 
one unit vertical in 12 units horizontal (8-percent slope). The 
entire length of the vent section of the horizontal branch drain 
shall be sized for the total drainage discharge to the branch in 
accordance with Table P3005.4.1. 

P3110.4 Additional fixtures. Fixtures, other than the circuit 
vented fixtures are permitted to discharge, to the horizontal 
branch drain. Such fixtures shall be located on the same floor as 
the circuit vented fixtures and shall be either individually or 
common vented. 



SECTION P31 11 
COMBINATION WASTE AND VENT SYSTEM 

P3111.1 Type of fixtures. A combination waste and vent sys- 
tem shall not serve fixtures other than floor drains, standpipes, 
sinks, lavatories and drinking fountains. A combination waste 
and vent system shall not receive the discharge of a food waste 
grinder. 

P3111.2 Installation. The only vertical pipe of a combination 
drain and vent system shall be the connection between the fix- I 
ture drain and the horizontal combination waste and vent pipe. I 
The maximum vertical distance shall be 8 feet (2438 mm). 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



465 



VENTS 



P31 11.2.1 Slope. The horizontal combination waste and 
vent pipe shall have a maximum slope of Vj unit vertical in 
12 units horizontal (4-percent slope). The minimum slope 
shall be in accordance with Section P3005.3. 

P3111.2.2 Connection. The combination waste and vent 
pipe shall connect to a horizontal drain that is vented or a 
vent shall connect to the combination waste and vent. The 
vent connecting to the combination waste and vent pipe 
shall extend vertically a minimum of 6 inches (152 mm) 
above the flood level rim of the highest fixture being vented 
before offsetting horizontally. 

P3111.2.3 Vent size. The vent shall be sized for the total fix- 
ture unit load in accordance with Section P3 113.1. 

P3111.2.4 Fixture branch or drain. The fixture branch or 
fixture drain shall connect to the combination waste and 
vent within a distance specified in Table P3 105. 1 . The com- 
bination waste and vent pipe shall be considered the vent for 
the fixture. 

P3111.3 Size. The minimum size of a combination waste and 
vent pipe shall be in accordance with Table P311 1.3. 

TABLE P311 1.3 
SIZE OF COMBINATION WASTE AND VENT PIPE 



DIAMETER PIPE 
(Inches) 


MAXIMUM NUMBER OF FIXTURE UNITS (d.f.u.) 


Connecting to a 

horizontal branch 

or stack 


Connecting to a 
building drain or 
building subdrain 


2 


3 


4 


2'/^ 


6 


26 


3 


12 


31 


4 


20 


50 



For SI: 1 inch = 25.4 mm. 



SECTION P31 12 
ISLAND FIXTURE VENTING 

P3 112.1 Limitation. Island fixture venting shall not be permit- 
ted for fixtures other than sinks and lavatories. Kitchen sinks 
with a dishwasher waste connection, a food waste grinder, or 
both, in combination with the kitchen sink waste, shall be per- 
mitted to be vented in accordance with this section. 

P3112.2 Vent connection. The island fixture vent shall con- 
nect to the fixture drain as required for an individual or com- 
mon vent. The vent shall rise vertically to above the drainage 
outlet of the fixture being vented before offsetting horizontally 
or vertically downward. The vent or branch vent for multiple 
island fixture vents shall extend to a minimum of 6 inches (152 
mm) above the highest island fixture being vented before con- 
necting to the outside vent terminal. 

P3112.3 Vent installation below the fixture flood level rim. 

The vent located below the flood level rim of the fixture being 
vented shall be installed as required for drainage piping in 
accordance with Chapter 30, except for sizing. The vent shall 
be sized in accordance with Section P31 13.1. The lowest point 
of the island fixture vent shall connect full size to the drainage 
system. The connection shall be to a vertical drain pipe or to the 



top half of a horizontal drain pipe. Cleanouts shall be provided 
in the island fixture vent to permit rodding of all vent piping 
located below the flood level rim of the fixtures. Rodding in 
both directions shall be permitted through a cleanout. 



SECTION P31 13 
VENT PIPE SIZING 

P3113.1 Size of vents. The minimum required diameter of 
individual vents, branch vents, circuit vents, vent stacks and 
stack vents shall be at least one-half the required diameter of 
the drain served. The required size of the drain shall be deter- 
mined in accordance with Chapter 30. Vent pipes shall be not 
less thanlV4 inches (32 mm) in diameter. Vents exceeding 40 
feet (12 192 mm) in developed length shall be increased by one 
nominal pipe size for the entire developed length of the vent 
pipe. 

P3113.2 Developed length. The developed length of individ- 
ual, branch, and circuit vents shall be measured from the far- 
thest point of vent connection to the drainage system, to the 
point of connection to the vent stack, stack vent or termination 
outside of the building. 

P3113.3 Branch vents. Where branch vents are connected to a 
common branch vent, the common branch vent shall be sized in 
accordance with this section, based on the size of the common 
horizontal drainage branch that is or would be required to serve 
the total drainage fixture unit (dfu) load being vented. 

P3113.4 Sump vents. Sump vent sizes shall be determined in 
accordance with Sections P3 11 3.4.1 and P3 113.4.2. 

P3113.4.1 Sewage pumps and sewage ejectors other 
than pneumatic. Drainage piping below sewer level shall 
be vented in a manner similar to that of a gravity system. 
Building sump vent sizes for sumps with sewage pumps or 
sewage ejectors, other than pneumatic, shall be determined 
in accordance with Table P31 13.4.1. 

P31 13.4.2 Pneumatic sewage ejectors. The air pressure 
relief pipe from a pneumatic sewage ejector shall be con- 
nected to an independent vent stack terminating as required 
for vent extensions through the roof. The relief pipe shall be 
sized to relieve air pressure inside the ejector to atmospheric 
pressure, but shall not be less than 1 74 inches (32 mm) in 
size. 



SECTION P31 14 
AIR ADMITTANCE VALVES 

P3114.1 General. Vent systems using air admittance valves 
shall comply with this section. Individual and branch-type air 
admittance valves shall conform to ASSE 1051. Stack-type air 
admittance valves shall conform to ASSE 1050. 

P3114.2 Installation. The valves shall be installed in accor- 
dance with the requirements of this section and the manufac- 
turer's installation instructions. Air admittance valves shall be 
installed after the DWV testing required by Section P2503.5.1 
or P2503.5.2 has been performed. 



466 



2006 INTERNATIONAL RESIDENTIAL CODE® 



VENTS 



P3114.3 Where permitted. Individual vents, branch vents, 
circuit vents and stack vents shall be permitted to terminate 
with a connection to an air admittance valve. 

P3114.4 Location. Individual and branch air admittance 
valves shall be located a minimum of 4 inches (102 mm) above 
the horizontal branch drain or fixture drain being vented. 
Stack-type air admittance valves shall be located a minimum of 
6 inches (152 mm) above the flood level rim of the highest fix- 
ture being vented. The air admittance valve shall be located 
within the maximum developed length permitted for the vent. 
The air admittance valve shall be installed a minimum of 6 
inches (152 mm) above insulation materials where installed in 
attics. 



P3114.5 Access and ventilation. Access shall be provided to 
all air admittance valves. The valve shall be located within a 
ventilated space that allows air to enter the valve. 

P3114.6 Size. The air admittance valve shall be rated for the 
size of the vent to which the valve is connected. 

P3114.7 Vent required. Within each plumbing system, a mini- 
mum of one stack vent or a vent stack shall extend outdoors to 
the open air. 



TABLE P31 13.4.1 
SIZE AND LENGTH OF SUMP VENTS 



DISCHARGE 
CAPACITY OF PUMP 

(gpm) 


MAXIMUM DEVELOPED LENGTH OF VENT (feet)^ 


Diameter of vent (inches) 


iV. 


1% 


2 


2% 


3 


10 


No limit'' 


No limit 


No limit 


No limit 


No limit 


20 


270 


No limit 


No limit 


No limit 


No limit 


40 


72 


160 


No limit 


No limit 


No limit 


60 


31 


75 


270 


No limit 


No limit 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 ^llon per minute (gpm) = 3.785 L/m. 

a. Developed length plus an appropriate allowance for entrance losses and friction caused by fittings, changes in direction and diameter. Suggested allowances shall 
be obtained from NBS Monograph 3 1 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more precise value is not 
available. 

b. Actual values greater than 500 feet. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



467 



468 2006 INTERNATIONAL RESIDENTIAL CODE*^ 



CHAPTER 32 

TRAPS 



SECTION P3201 
FIXTURE TRAPS 

P3201.1 Design of traps. Traps shall be of standard design, 
shall have smooth uniform internal waterways, shall be 
self-cleaning and shall not have interior partitions except 
where integral with the fixture. Traps shall be constructed of 
lead, cast iron, cast or drawn brass or approved plastic. Tubular 
brass traps shall be not less than No. 20 gage (0.8 nun) thick- 
ness. Solid connections, slip joints and couplings are permitted 
to be used on the trap inlet, trap outlet, or within the trap seal. 
Slip joints shall be accessible. 

P3201.2 Trap seals and trap seal protection. Traps shall have 
a liquid seal not less than 2 inches (5 1 mm) and not more than 4 

■ inches (102 mm). Traps for floor drains shall be fitted with a 
trap primer or shall be of the deep seal design. 

P3201.3 Trap setting and protection. Traps shall be set level 
with respect to their water seals and shall be protected from 
freezing. Trap seals shall be protected from siphonage, aspira- 
tion or back pressure by an approved system of venting (see 
Section P3 101). 

P3201.4 Building traps. Building traps shall not be installed, 
except in special cases where sewer gases are extremely corro- 
sive or noxious, as directed by the building official. 

P3201.5 Proliibited trap designs. The following types of 
traps are prohibited: 

1. Bell traps. 

2. Separate fixture traps with interior partitions, except 
those lavatory traps made of plastic, stainless steel or 
other corrosion-resistant material. 

I 3. "S" traps. 

4. Drum traps. 

5. Trap designs with moving parts. 

P3201.6 Number of fixtures per trap. Each plumbing fixture 
shall be separately trapped by a water seal trap. The vertical 
distance from the fixture outlet to the trap weir shall not exceed 
24 inches (610 mm) and the horizontal distance shall not 
exceed 30 inches (762 mm) measured from the center line of 
the fixture outlet to the centerline of the inlet of the trap. The 
height of a clothes washer standpipe above a trap shall conform 
to Section P2706.2. Fixtures shall not be double trapped. 

Exceptions: 

1. Fixtures that have integral traps. 

2. A single trap shall be permitted to serve two or three 
like fixtures limited to kitchen sinks, laundry tubs and 
lavatories. Such fixtures shall be adjacent to each 
other and located in the same room with a continuous 
waste arrangement. The trap shall be installed at the 
center fixture where three fixtures are installed. Com- 



mon trapped fixture outlets shall be not more than 30 
inches (762 mm) apart. 

3. Connection of a laundry tray waste line into a 
standpipe for the automatic clothes-washer drain is 
permitted in accordance with Section P2706.2.1. 

P3201.7 Size of fixture traps. Fixture trap size shall be suffi- 
cient to drain the fixture rapidly and not less than the size indi- 
cated in Table P3201.7. A trap shall not be larger than the 
drainage pipe into which the trap discharges. 

TABLEP3201.7 
SIZE OF TRAPS AND TRAP ARMS FOR PLUMBING FIXTURES 



PLUMBING FIXTURE 


TRAP SIZE MINIMUM 
(inches) 


Bathtub (with or without shower head and/or 
whirlpool attachments) 


VI, 


Bidet 


l'/4 


Clothes washer standpipe 


2 


Dishwasher (on separate trap) 


VI, 


Floor drain 


2 


Kitchen sink (one or two traps, with or 
without dishwasher and garbage grinder) 


VI, 


Laundry tub (one or more compartments) 


VI, 


Lavatory 


l'/4 


Shower (based on the total flow rate through 

showerheads and bodysprays) 

Flow rate: 

5.7 gpm and less 

More than 5.7 gpm up to 12.3 gpm 
More than 12.3 gpm up to 25.8 gpm 
More than 25.8 gpm up to 55.6 gpm 


VI, 
■ 2 

3 

4 


Water closet 


Note a 



For SI: 1 inch = 25.4 mm. 

a. Consult fixture standards for trap dimensions of specific bowls. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



469 



470 2006 INTERNATIONAL RESIDENTIAL CODE'' 



Part VIII — Electrical 



CHAPTER 33 

GENERAL REQUIREMENTS 

This Electrical Part (Chapters 33 through 42) is produced and copyrighted by the National Fire Protection Association (NFPA) and 
is based on the 2005 National Electrical Code® (NEC®) (NFPA 70-2005), copyright 2005 National Fire Protection Association, all 
rights reserved. Use of the Electrical Part is pursuant to license with the NFPA. 

The tide National Electrical Code® and the acronym NEC® are registered trademarks of the National Fire Protection Association, Quincy, 
Massachusetts. See Appendix Q, International Residential Code Electrical Provisions/National Electrical Code Cross Reference. 



SECTION E3301 
GENERAL 

E3301.1 Applicability. The provisions of Chapters 33 through 
42 shall establish the general scope of the electrical system and 
equipment requirements of this code. Chapters 33 through 42 
cover those wiring methods and materials most commonly 
encountered in the construction of one- and two-family dwell- 
ings and structures regulated by this code. Other wiring meth- 
ods, materials and subject matter covered in the NFPA 70 are 
also allowed by this code. 

E3301.2 Scope. Chapters 33 through 42 shall cover the instal- 
lation of electrical systems, equipment and components 
indoors and outdoors that are within the scope of this code, 
including services, power distribution systems, fixtures, appli- 
ances, devices and appurtenances. Services within the scope of 
this code shall be limited to 120/240- volt, 0- to 400-ampere, 
single-phase systems. These chapters specifically cover the 
equipment, fixtures, appliances, wiring methods and materials 
that are most commonly used in the construction or alteration 
of one- and two-family dwellings and accessory structures reg- 
ulated by this code. The omission from these chapters of any 
material or method of construction provided for in the refer- 
enced standard NFPA 70 shall not be construed as prohibiting 
the use of such material or method of construction. Electrical 
systems, equipment or components not specifically covered in 
these chapters shall comply with the applicable provisions of 
the NFPA 70. 

E3301.3 Not covered. Chapters 33 through 42 do not cover the 
following: 

1. Installations, including associated lighting, under the 
exclusive control of communications utilities and elec- 
tric utilities. 

2. Services over 400 amperes. 

E3301.4 Additions and alterations. Any addition or alter- 
ation to an existing electrical system shall be made in confor- 
mity with the provisions of Chapters 33 through 42. Where 
additions subject portions of existing systems to loads exceed- 
ing those permitted herein, such portions shall be made to com- 
ply with Chapters 33 through 42. 



SECTION E3302 
BUILDING STRUCTURE PROTECTION 

E3302.1 Drilling and notching. Wood-framed structural 
members shall not be drilled, notched or altered in any manner 
except as provided for in this code. 

E3302.2 Penetrations of fire-resistance-rated assemblies. 

Electrical installations in hollow spaces, vertical shafts and 
ventilation or air-handling ducts shall be made so that the pos- 
sible spread of fire or products of combustion will not be sub- 
stantially increased. Electrical penetrations through 
fire-resistance-rated walls, partitions, floors or ceilings shall be 
protected by approved methods to maintain the fire-resistance 
rating of the element penetrated. Penetrations of fire-resis- 
tance-rated walls shall be limited as specified in Section 
R317.3. 

E3302.3 Penetrations of firestops and draftstops. Penetra- 
tions through fire blocking and draftstopping shall be protected 
in an approved manner to maintain the integrity of the element 
penetrated. 



SECTION E3303 
INSPECTION AND APPROVAL 

E3303.1 Approval. Electrical materials, components and 
equipment shall be approved. 

E3303.2 Inspection required. New electrical work and parts 
of existing systems affected by new work or alterations shall be 
inspected by the building official to ensure compliance with the 
requirements of Chapters 33 through 42. 

E3303.3 Listing and labeling. Electrical materials, compo- 
nents, devices, fixtures and equipment shall be listed for the 
application, shall bear the label of an approved agency and 
shall be installed, and used, or both, in accordance with the 
manufacturer's installation instructions. 



SECTION E3304 
GENERAL EQUIPMENT REQUIREMENTS 

E3304.1 Voltages. Throughout Chapters 33 through 42, the 
voltage considered shall be that at which the circuit operates. 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



471 



GENERAL REQUIREMENTS 



E3304.2 Interrupting rating. Equipment intended to inter- 
rupt current at fault levels shall have a minimum interrupting 
rating of 10,000 amperes. Equipment intended to interrupt cur- 
rent at levels other than fault levels shall have an interrupting 
rating at nominal circuit voltage sufficient for the current that 
must be interrupted. 

E3304.3 Circuit characteristics. The overcurrent protective 
devices, total impedance, component short-circuit current rat- 
ings and other characteristics of the circuit to be protected shall 
be so selected and coordinated as to permit the circuit protec- 
tive devices that are used to clear a fault to do so without exten- 
sive damage to the electrical components of the circuit. This 
fault shall be assumed to be either between two or more of the 
circuit conductors or between any circuit conductor and the 
grounding conductor or enclosing metal raceway. Listed prod- 
ucts applied in accordance with their listing shall be considered 
to meet the requirements of this section. 

E3304.4 Protection of equipment. Equipment identified only 
as "dry locations," "Type 1," or "indoor use only" shall be pro- 
tected against permanent damage from the weather during 
building construction. 

E3304.5 Unused openings. Unused cable or raceway open- 
ings in boxes, cabinets, meter socket enclosures, equipment 
cases or housings shall be effectively closed to afford protec- 
tion substantially equivalent to the wall of the equipment. 
Where metallic plugs or plates are used with nonmetallic 
enclosures they shall be recessed at least V4 inch (6 mm) from 
the outer surface of the enclosure. 

E3304.6 Integrity of electrical equipment. Internal parts of 
electrical equipment, including busbars, wiring terminals, 
insulators and other surfaces, shall not be damaged or contami- 
nated by foreign materials such as paint, plaster, cleaners or 
abrasives, and corrosive residues. There shall not be any dam- 
aged parts that might adversely affect safe operation or 
mechanical strength of the equipment such as parts that are bro- 
ken; bent; cut; deteriorated by corrosion, chemical action, or 
overheating. Foreign debris shall be removed from equipment. 

E3304.7 Mounting. Electrical equipment shall be firmly 
secured to the surface on which it is mounted. Wooden plugs 
driven into masonry, concrete, plaster, or similar materials shall 
not be used. 

E3304.8 Energized parts guarded against accidental con- 
tact. Approved enclosures shall guard energized parts that are 
operating at 50 volts or more against accidental contact. 

E3304.9 Prevent physical damage. In locations where electri- 
cal equipment is likely to be exposed to physical damage, 
enclosures or guards shall be so arranged and of such strength 
as to prevent such damage. 

E3304.10 Equipment identification. The manufacturer's 
name, trademark or other descriptive marking by which the 
organization responsible for the product can be identified shall 
be placed on all electric equipment. Other markings shall be pro- 
vided that indicate voltage, current, wattage or other ratings as 
specified elsewhere in Chapters 33 through 42. The marking 
shall have the durabiUty to withstand the environment involved. 

E3304.il Identification of disconnecting means. Each dis- 
connecting means shall be legibly marked to indicate its pur- 



pose, except where located and arranged so that the purpose is 
evident. The marking shall have the durability to withstand the 
environment involved. 



SECTION E3305 
EQUIPMENT LOCATION AND CLEARANCES 

E3305.1 Working space and clearances. Sufficient access 
and working space shall be provided and maintained around all 
electrical equipment to permit ready and safe operation and 
maintenance of such equipment in accordance with this section 
and Figure E3305.1. 

E3305.2 Working clearances for energized equipment and 
panelboards. Except as otherwise specified in Chapters 33 
through 42, the dimension of the working space in the direction 
of access to panelboards and live parts likely to require examina- 
tion, adjustment, servicing or maintenance while energized shall 
be not less than 36 inches (914 mm) in depth. Distances shall be 
measured from the energized parts where such parts are exposed 
or from the enclosure front or opening where such parts are 
enclosed. In addition to the 36-inch dimension (914 mm), the 
work space shall not be less than 30 inches (762 mm) wide in 
front of the electrical equipment and not less than the width of 
such equipment. The work space shall be clear and shall extend 
from the floor or platform to a height of 6.5 feet (1981 mm). In 
all cases, the work space shall allow at least a 90~degree opening 
of equipment doors or hinged panels. Equipment associated 
with the electrical installation located above or below the electri- 
cal equipment shall be permitted to extend not more than 6 
inches (152 mm) beyond the front of the electrical equipment. 

E3305.3 Dedicated panelboard space. The space equal to the 
width and depth of the panelboard and extending from the floor 
to a height of 6 feet (1829 mm) above the panelboard, or to the 
structural ceiling, whichever is lower, shall be dedicated to the 
electrical installation. Piping, ducts, leak protection apparatus 
and other equipment foreign to the electrical installation shall 
not be installed in such dedicated space. The area above the dedi- 
cated space shall be permitted to contain foreign systems, pro- 
vided that protection is installed to avoid damage to the electrical 
equipment from condensation, leaks and breaks in such foreign 
systems (see Figure E3305.1). 

Exception: Suspended ceilings with removable panels shall I 
be permitted within the 6-foot (1.8 m) dedicated space. | 

E3305.4 Location of working spaces and equipment. 

Required working space shall not be designated for storage. 
Panelboards and overcurrent protection devices shall not be 
located in clothes closets or bathrooms. 

E3305.5 Access and entrance to working space. Access shall 
be provided to the required working space. 

E3305.6 Illumination. Artificial illumination shall be pro- 
vided for all working spaces for service equipment and 
panelboards installed indoors. 

E3305.7 Headroom. The minimum headroom for working 
spaces for service equipment and panelboards shall be 6.5 feet 
(1981 mm). 



472 



2006 INTERNATIONAL RESIDENTIAL CODE 



® 



GENERAL REQUIREMENTS 



FOOTNOTE a 




i FOOTNOTE b 



FOOTNOTE a 



FIGURE ESaOS.I^'"'''''''^ 
WORKING SPACE AND CLEARANCES 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Equipment, piping and ducts foreign to the electrical installation shall not be placed in the shaded areas extending from the floor to a height of 6 feet above the | 
paneiboard enclosure, or to the structural ceiling, whichever is lower. 

b. The working space shall be clear and unobstructed from the floor to a height of 6.5 feet. 

c. The working space shall not be designated for storage. 

d. Panelboards, service equipment and similar enclosures shall not be located in bathrooms, toilet rooms and clothes closets. 

e. Such work spaces shall be provided with artificial lighting where located indoors. 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



473 



GENERAL REQUIREMENTS 



SECTION E3306 
ELECTRICAL CONDUCTORS AND CONNECTIONS 

E3306.1 GeneraL This section provides general requirements 
for conductors, connections and splices. These requirements 
do not apply to conductors that form an integral part of equip- 
ment, such as motors, appliances and similar equipment, or to 
conductors specifically provided for elsewhere in Chapters 33 
through 42. 

E3306.2 Conductor materiaL Conductors used to conduct 
current shall be of copper except as otherwise provided in 
Chapters 33 through 42. Where the conductor material is not 
specified, the material and the sizes given in these chapters 
shall apply to copper conductors. Where other materials are 
used, the conductor sizes shall be changed accordingly. 

E3306.3 Minimum size of conductors. The minimum size of 
conductors for feeders and branch circuits shall be 14 AWG 
copper and 12 AWG aluminum. The minimum size of service 
conductors shall be as specified in Chapter 35. The minimum 
size of class 2 remote control, signahng and power-hmited cir- 
cuits conductors shall be as specified in Chapter 42. 

E3306.4 Stranded conductors. Where installed in raceways, 
conductors of size 8 AWG and larger shall be stranded. A solid 
8 AWG conductor shall be permitted to be installed in a race- 
way only to meet the requirements of Section E4104. 

E3306.5 Individual conductor insulation. Except where oth- 
erwise permitted in Sections E3505.1 andE3808.9, andE4203, 
current-carrying conductors shall be insulated. Insulated con- 
ductors shall have insulation types identified as RH, RHW, 
RHW-2, THHN, THHW, THW, THW-2, THWN, THWN-2, 
TW, UF, USE, USE-2, XHHW or XHHW-2. Insulation types 
shall be approved for the application. 

E3306.6 Conductors in parallel. Circuit conductors that are 
connected in parallel shall be limited to sizes 1/0 AWG and 
larger. Conductors in parallel shall be of the same length, same 
conductor material, same circular mil area and same insulation 
type. Conductors in parallel shall be terminated in the same 
manner. Where run in separate raceways or cables, the raceway 

I or cables shall have the same physical characteristics. Where 
conductors are in separate raceways or cables, the same num- 
ber of conductors shall be used in each raceway or cable. 

E3306.7 Conductors of the same circuit. All conductors of 
the same circuit and, where used, the grounded conductor and 
I all equipment grounding conductors and bonding conductors 
shall be contained within the same raceway, cable or cord. 

E3306.8 Aluminum and copper connections. Terminals and 
I splicing connectors shall be identified for the material of the 
conductors joined. Conductors of dissimilar metals shall not be 
joined in a terminal or splicing connector where physical con- 
tact occurs between dissimilar conductors such as copper and 
aluminum, copper and copper-clad aluminum, or aluminum 
and copper-clad aluminum, except where the device is listed 
for the purpose and conditions of application. Materials such as 
inhibitors and compounds shall be suitable for the application 
and shall be of a type that will not adversely affect the conduc- 
tors, installation or equipment. 

E3306.9 Terminals. Connection of conductors to terminal 
parts shall be made without damaging the conductors and shall 



be made by means of pressure connectors, including set-screw 
type, by means of splices to flexible leads, or for conductor 
sizes of 10 AWG and smaller, by means of wire binding screws 
or studs and nuts having upturned lugs or the equivalent. Ter- 
minals for more than one conductor and terminals for connect- 
ing aluminum conductors shall be identified for the 
application. 

E3306.10 Splices. Conductors shall be spliced or joined with 
splicing devices listed for the purpose. Splices and joints and 
the free ends of conductors shall be covered with an insulation 
equivalent to that of the conductors or with an insulating device 
listed for the purpose. Wire connectors or splicing means 
installed on conductors for direct burial shall be listed for such 
use. 

E3306.10.1 Continuity. Conductors in raceways shall be 
continuous between outlets, boxes, and devices and shall be | 
without splices or taps in the raceway. 

Exception: Splices shall be permitted within 
surface-mounted raceways that have a removable cover. 

E3306.10.2 Device connections. The continuity of a 
grounded conductor in multiwire branch circuits shall not 
be dependent on connection to devices such as receptacles 
and lampholders. The arrangement of grounding connec- 
tions shall be such that the disconnection or the removal of a 
receptacle, luminaire or other device fed from the box does 
not interfere with or interrupt the grounding continuity. 

E3306.10.3 Length of conductor for splice or termina- 
tion. Where conductors are to be spliced, terminated or con- 
nected to fixtures or devices, a minimum length of 6 inches 
(150 mm) of free conductor shall be provided at each outlet, 
junction or switch point. The required length shall be mea- 
sured from the point in the box where the conductor 
emerges from its raceway or cable sheath. Where the open- 
ing to an outlet, junction or switch point is less than 8 inches 
(200 mm) in any dimension, each conductor shall be long 
enough to extend at least 3 inches (75 mm) outside of such 
opening. 



SECTION E3307 
CONDUCTOR AND TERMINAL IDENTIFICATION 

E3307.1 Grounded conductors. Insulated grounded conduc- 
tors of sizes 6 AWG or smaller shall be identified by a continu- 
ous white or gray outer finish or by three continuous white 
stripes on other than green insulation along the entire length of 
the conductors. Conductors of sizes larger than 6 AWG shall be 
identified either by a continuous white or gray outer finish or 
by three continuous white stripes on other than green insulation 
along its entire length or at the time of installation by a distinc- 
tive white or gray marking at its terminations. This marking | 
shall encircle the conductor or insulation. 

E3307.2 Equipment grounding conductors. Equipment 
grounding conductors of sizes 6 AWG and smaller shall be |^ 
identified by a continuous green color or a continuous green 
color with one or more yellow stripes on the insulation or cov- 
ering, except where bare. Conductors with insulation or indi- I 
vidual covering that is green, green with one or more yellow I 



474 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



stripes, or otherwise identified as permitted by this section shall 
not be used for ungrounded or grounded circuit conductors. 

Equipment grounding conductors larger than 6 AWG that 
are not identified as required for conductors of sizes 6 AWG 
and smaller shall, at the time of installation, be permanently 
identified as an equipment grounding conductor at each end 
and at every point where the conductor is accessible, except 
where such conductors are bare. 

The required identification for conductors larger than 6 
AWG shall encircle the conductor and shall be accomplished 
by one of the following: 

1. Stripping the insulation or covering from the entire 
exposed length. 

2. Coloring the exposed insulation or covering green. 

3. Marking the exposed insulation or covering with green 
tape or green adhesive labels. 

Exception: Conductors larger than 6 AWG shall not be 
required to be identified in conduit bodies that do not con- 
tain splices or unused hubs. 

E3307.3 Ungrounded conductors. Insulation on the 
ungrounded conductors shall be a continuous color other than 
white, gray and green. 

Exceptions: 

1 . An insulated conductor that is part of a cable or flexi- 
ble cord assembly and that has a white or gray finish 
or a finish marking with three continuous white 
stripes shall be permitted to be used as an ungrounded 
conductor where it is permanently reidentified to 
indicate its use as an ungrounded conductor at all ter- 
minations and at each location where the conductor is 
visible and accessible. Identification shall encircle the 
insulation and shall be a color other than white, gray, 
and green. 

2. Where a cable assembly contains an insulated con- 
ductor for single-pole, 3-way or 4-way switch loops 
and the conductor with white or gray insulation or a 
marking of three continuous white stripes is used for 
the supply to the switch but not as a return conductor 
from the switch to the switched outlet. In these appli- 
cations, the conductor with white or gray insulation or 
with three continuous white stripes shall be perma- 
nently reidentified to indicate its use by painting or 
other effective means at its terminations and at each 
location where the conductor is visible and accessi- 
ble. 

E3307.4 Identification of terminals. Terminals for attach- 
ment to conductors shall be identified in accordance with Sec- 
tions E3307.4.1 and E3307.4.2. 

E3307.4.1 Device terminals. All devices excluding 
panelboards, provided with terminals for the attachment of 
conductors and intended for connection to more than one 
side of the circuit shall have terminals properly marked for 
identification, except where the terminal intended to be con- 
nected to the grounded conductor is clearly evident. 



GENERAL REQUIREMENTS 



Exception: Terminal identification shall not be required 
for devices that have a normal current rating of over 30 
amperes, other than polarized attachment caps and polar- 
ized receptacles for attachment caps as required in Sec- 
tion E3 307 .4. 2. 

E3307.4.2 Receptacles, plugs, and connectors. Recepta- 
cles, polarized attachment plugs and cord connectors for 
plugs and polarized plugs shall have the terminal intended 
for connection to the grounded (white) conductor identified. 
Identification shall be by a metal or metal coating substan- 
tially white in color or by the word "white" or the letter "W" 
located adjacent to the identified terminal. Where the termi- 
nal is not visible, the conductor entrance hole for the con- 
nection shall be colored white or marked with the word 
"white" or the letter "W." 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



475 



476 2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 34 

ELECTRICAL DEFINITIONS 



SECTION E3401 
GENERAL 

E3401.1 Scope. This chapter contains definitions that shall 
apply only to the electrical requirements of Chapters 33 
through 42. Unless otherwise expressly stated, the following 
terms shall, for the purpose of this code, have the meanings 
indicated in this chapter. Words used in the present tense 
include the future; the singular number includes the plural and 
the plural the singular. Where terms are not defined in this sec- 
tion and are defined in Section R202 of this code, such terms 
shall have the meanings ascribed to them in that section. Where 
terms are not defined in these sections, they shall have their 
ordinarily accepted meanings or such as the context implies. 

ACCESSIBLE. (As apphed to equipment.) Admitting close 
approach; not guarded by locked doors, elevation or other 
effective means. 

ACCESSIBLE. (As applied to wiring methods.) Capable of 
being removed or exposed without damaging the building 
structure or finish, or not permanently closed in by the structure 
or finish of the building. 

ACCESSIBLE, READILY. Capable of being reached quickly 
for operation, renewal or inspections, without requiring those 
to whom ready access is requisite to climb over or remove 
obstacles or to resort to portable ladders, etc. 

AMPACITY. The current in amperes that a conductor can 
carry continuously under the conditions of use without exceed- 
ing its temperature rating. 

APPLIANCE. Utilization equipment, normally built in stan- 
dardized sizes or types, that is installed or connected as a unit to 
perform one or more functions such as clothes washing, air 
conditioning, food mixing, deep frying, etc. 

APPROVED. Acceptable to the authority having jurisdiction. 

ARC-FAULT CIRCUIT INTERRUPTER. A device 
intended to provide protection from the effects of arc-faults by 
recognizing characteristics unique to arcing and by functioning 
to de-energize the circuit when an arc-fault is detected. 

ATTACHMENT PLUG (PLUG CAP) (PLUG). A device 
that, by insertion into a receptacle, establishes connection 
between the conductors of the attached flexible cord and the 
conductors connected permanently to the receptacle. 

AUTOMATIC. Self-acting, operating by its own mechanism 
when actuated by some impersonal influence, as, for example, 
a change in current, pressure, temperature or mechanical con- 
figuration. 

BATHROOM. An area, including a basin, with one or more of 
the following: a toilet, a tub or a shower. 

BONDING. The permanent joining of metallic parts to form 
an electrically conductive path that will ensure electrical conti- 
nuity and the capacity to conduct safely any current likely to be 
imposed. 



BONDING JUMPER. A reliable conductor to ensure the 
required electrical conductivity between metal parts required 
to be electrically connected. 

BONDING JUMPER (EQUIPMENT). The connection 
between two or more portions of the equipment grounding con- 
ductor. 

BONDING JUMPER, MAIN. The connection between the 
grounded circuit conductor and the equipment grounding con- 
ductor at the service. 

BRANCH CIRCUIT. The circuit conductors between the 
final overcurrent device protecting the circuit and the outlet(s). 

BRANCH CIRCUIT, APPLIANCE. A branch circuit that 
supplies energy to one or more outlets to which appliances are 
to be connected, and that has no permanently connected 
luminaires that are not a part of an appliance. 

BRANCH CIRCUIT, GENERAL PURPOSE. A branch cir- 
cuit that supplies two or more receptacle outiets or outlets for 
lighting and appliances. 

BRANCH CIRCUIT, INDIVIDUAL. A branch circuit that 
supplies only one utilization equipment. 

BRANCH CIRCUIT, MULTIWIRE. A branch circuit con- 
sisting of two or more ungrounded conductors having voltage 
difference between them, and a grounded conductor having 
equal voltage difference between it and each ungrounded con- 
ductor of the circuit, and that is connected to the neutral or 
grounded conductor of the system. 

CABINET. An enclosure designed either for surface or flush 
mounting and provided with a frame, mat or trim in which a 
swinging door or doors are or may be hung. 

CIRCUIT BREAKER. A device designed to open and close a 
circuit by nonautomatic means and to open the circuit automat- 
ically on a predetermined overcurrent without damage to itself 
when properly applied within its rating. 

CONCEALED. Rendered inaccessible by the structure or fin- 
ish of the building. Wires in concealed raceways are considered 
concealed, even though they may become accessible by with- 
drawing them [see "Accessible (As applied to wiring meth- 
ods)"]. 

CONDUCTOR 

Bare. A conductor having no covering or electrical insula- 
tion whatsoever. 

Covered. A conductor encased within material of composi- 
tion or thickness that is not recognized by this code as elec- 
trical insulation. 

Insulated. A conductor encased within material of compo- 
sition and thickness that is recognized by this code as elec- 
trical insulation. 

CONDUIT BODY. A separate portion of a conduit or tubing 
system that provides access through a removable cover(s) to 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



477 



ELECTRICAL DEFINITIONS 



the interior of the system at a junction of two or more sections 
of the system or at a terminal point of the system. Boxes such as 
FS and FD or larger cast or sheet metal boxes are not classified 
as conduit bodies. 

CONNECTOR, PRESSURE (SOLDERLESS). A device 
that establishes a connection between two or more conductors 
or between one or more conductors and a terminal by means of 
mechanical pressure and without the use of solder. 

CONTINUOUS LOAD. A load where the maximum current 
is expected to continue for 3 hours or more. 

COOKING UNIT, COUNTER-MOUNTED. A cooking 
appliance designed for mounting in or on a counter and consist- 
ing of one or more heating elements, internal wiring and 
built-in or separately mountable controls. 

COPPER-CLAD ALUMINUM CONDUCTORS. Conduc- 
tors drawn from a copper-clad aluminum rod with the copper 
metallurgically bonded to an aluminum core. The copper forms 
a minimum of 10 percent of the cross-sectional area of a solid 
conductor or each strand of a stranded conductor. 

CUTOUT BOX. An enclosure designed for surface mounting 
and having swinging doors or covers secured directly to and 
telescoping with the walls of the box proper (see "Cabinet"). 

DEAD FRONT. Without live parts exposed to a person on the 
operating side of the equipment. 

DEMAND FACTOR. The ratio of the maximum demand of a 
system, or part of a system, to the total connected load of a sys- 
tem or the part of the system under consideration. 

DEVICE. A unit of an electrical system that is intended to 
I carry or control but not utilize electric energy. 

DISCONNECTING MEANS. A device, or group of devices, 
or other means by which the conductors of a circuit can be dis- 
connected from their source of supply. 

DWELLING 

I Dwelling unit. A single unit, providing complete and inde- 
pendent living facilities for one or more persons, including 
permanent provisions for living, sleeping, cooking and sani- 
tation. 

One-family dwelling. A building consisting solely of one 
dwelling unit. 

Two-family dwelling. A building consisting solely of two 
dwelling units. 

ENCLOSED. Surrounded by a case, housing, fence or walls 
that will prevent persons from accidentally contacting ener- 
gized parts. 

ENCLOSURE. The case or housing of apparatus, or the fence 
or walls surrounding an installation, to prevent personnel from 
accidentally contacting energized parts or to protect the equip- 
ment from physical damage. 

I ENERGIZED. Electrically connected to, or is, a source of 
voltage. 

EQUIPMENT. A general term including material, fittings, 
devices, appliances, luminaires, apparatus and the like used as 
a part of, or in connection with, an electrical installation. 



EXPOSED. (As applied to live parts.) Capable of being inad- 
vertently touched or approached nearer than a safe distance by 
a person. It is applied to parts not suitably guarded, isolated or 
insulated. 

EXPOSED. (As applied to wiring methods.) On or attached to 
the surface or behind panels designed to allow access. 

EXTERNALLY OPERABLE. Capable of being operated 
without exposing the operator to contact with live parts. 

FEEDER. All circuit conductors between the service equip- 
ment, or the source of a separately derived system, or other 
power supply source and the final branch-circuit overcurrent 
device. 

FITTING. An accessory such as a locknut, bushing or other 
part of a wiring system that is intended primarily to perform a 
mechanical rather than an electrical function. 

GROUND. A conducting connection, whether intentional or 
accidental, between an electrical circuit or equipment and the 
earth, or to some conducting body that serves in place of the 
earth. 

GROUNDED. Connected to earth or to some conducting body 
that serves in place of the earth. 

GROUNDED, EFFECTIVELY. Intentionally connected to 
earth through a ground connection or connections of suffi- 
ciently low impedance and having sufficient current-carrying 
capacity to prevent the buildup of voltages that may result in 
undue hazards to connected equipment or to persons. 

GROUNDED CONDUCTOR. A system or circuit conductor 
that is intentionally grounded. 

GROUNDING CONDUCTOR. A conductor used to connect 
equipment or the grounded circuit of a wiring system to a 
grounding electrode or electrodes. 

GROUNDING CONDUCTOR, EQUIPMENT. The con- 
ductor used to connect the noncurrent-carrying metal parts of 
equipment, raceways and other enclosures to the system 
grounded conductor, the grounding electrode conductor or 
both, at the service equipment, or at the source of a separately | 
derived system. 

GROUNDING ELECTRODE. A device that establishes an I 
electrical connection to earth. | 

GROUNDING ELECTRODE CONDUCTOR. The con- 
ductor used to connect the grounding electrode(s) to the equip- 
ment grounding conductor, to the grounded conductor, or to 
both, at the service, at each building or structure where sup- I 
plied by a feeder(s) or branch circuit(s), or at the source of a | 
separately derived system. 

GROUND-FAULT CIRCUIT-INTERRUPTER. A device 
intended for the protection of personnel that functions to 
de-energize a circuit or portion thereof within ah established 
period of time when a current to ground exceeds the value for a 
Class A device. 

GUARDED. Covered, shielded, fenced, enclosed or otherwise 
protected by means of suitable covers, casings, barriers, rails, 
screens, mats or platforms to remove the likelihood of 
, approach or contact by persons or obj ects to a point of danger. 



478 



2006 INTERNATIONAL RESIDENTIAL CODE 



;® 



ELECTRICAL DEFINITIONS 



IDENTIFIED. (As applied to equipment.) Recognizable as 
suitable for the specific purpose, function, use, environment, 
application, etc., where described in a particular code require- 
ment. 

INTERRUPTING RATING. The highest current at rated 
voltage that a device is intended to interrupt under standard test 
conditions. 

ISOLATED. (As applied to location.) Not readily accessible 
to persons unless special means for access are used. 

LABELED. Equipment or materials to which has been 
attached a label, symbol or other identifying mark of an organi- 
zation acceptable to the authority having jurisdiction and con- 
cerned with product evaluation that maintains periodic 
inspection of production of labeled equipment or materials and 
by whose labeling the manufacturer indicates compliance with 
appropriate standards or performance in a specified manner. 

LIGHTING OUTLET. An outlet intended for the direct con- 
nection of a lampholder, a luminaire (lighting fixture) or a pen- 
dant cord terminating in a lampholder. 

LISTED. Equipment, materials or services included in a list 
published by an organization that is acceptable to the authority 
having jurisdiction and concerned with evaluation of products 
or services, that maintains periodic inspection of production of 
listed equipment or materials or periodic evaluation of ser- 
vices, and whose listing states either that the equipment, mate- 
rial or services meets identified standards or has been tested 
and found suitable for a specified purpose. 

LIVE PARTS. Energized conductive components. 

LOCATION, DAMP. Location protected from weather and 
not subject to saturation with water or other liquids but subject 
to moderate degrees of moisture. Examples of such locations 
include partially protected locations under canopies, mar- 
quees, roofed open porches and like locations, and interior 
locations subject to moderate degrees of moisture, such as 
some basements, some bams and some cold-storage ware- 
houses. 

LOCATION, DRY. A location not normally subject to damp- 
ness or wetness. A location classified as dry may be tempo- 
rarily subject to dampness or wetness, as in the case of a 
building under construction. 

LOCATION, WET. Installations underground or in concrete 
slabs or masonry in direct contact with the earth and locations 
subject to saturation with water or other liquids, such as vehi- 
cle-washing areas, and locations exposed to weather. 

LUMINAIRE. A complete lighting unit (lighting fixture) con- 
sisting of a lamp or lamps together with parts designed to dis- 
tribute the light, to position and protect the lamps and ballast, 
where applicable, and to connect the lamps to the power sup- 
ply. 

MULTIOUTLET ASSEMBLY. A type of surface, or flush, or 
freestanding raceway; designed to hold conductors and recep- 
tacles, assembled in the field or at the factory. 

OUTLET. A point on the wiring system at which current is 
taken to supply utilization equipment. 



OVERCURRENT. Any current in excess of the rated current 
of equipment or the ampacity of a conductor. Such current 
might result from overload, short circuit or ground fault. 

OVERLOAD. Operation of equipment in excess of normal, 
full-load rating, or of a conductor in excess of rated ampacity 
that, when it persists for a sufficient length of time, would cause 
damage or dangerous overheating. A fault, such as a short cir- 
cuit or ground fault, is not an overload. 

PANELBOARD. A single panel or group of panel units 
designed for assembly in the form of a single panel, including 
buses and automatic overcurrent devices, and equipped with or 
without switches for the control of light, heat or power circuits, 
designed to be placed in a cabinet or cutout box placed in or 
against a wall, partition or other support and accessible only 
from the front. 

PLENUM. A compartment or chamber to which one or more 
air ducts are connected and that forms part of the air distribu- 
tion system. 

POWER OUTLET. An enclosed assembly that may include 
receptacles, circuit breakers, fuseholders, fused switches, 
buses and watt-hour meter mounting means, intended to supply 
and control power to mobile homes, recreational vehicles or 
boats, or to serve as a means for distributing power required to 
operate mobile or temporarily installed equipment. 

PREMISES WIRING (SYSTEM). That interior and exterior 
wiring, including power, lighting, control and signal circuit 
wiring together with all of their associated hardware, fittings 
and wiring devices, both permanently and temporarily 
installed, that extends from the service point or source of power 
such as a battery, a solar photovoltaic system, or a generator, 
transformer, or converter winding, to the outlet(s). Such wiring 
does not include wiring internal to appliances, luminaires (fix- 
tures), motors, controllers, and similar equipment. 

QUALIFIED PERSON. One who has the skills and knowl- 
edge related to the construction and operation of the electrical 
equipment and installations and has received safety training on 
the hazards involved. 

RACEWAY. An enclosed channel of metal or nonmetallic 
materials designed expressly for holding wires, cables, or 
busbars, with additional functions as permitted in this code. 
Raceways include, but are not limited to, rigid metal conduit, 
rigid nonmetallic conduit, intermediate metal conduit, liq- 
uid-tight flexible conduit, flexible metallic tubing, flexible 
metal conduit, electrical nonmetallic tubing, electrical metallic 
tubing, underfloor raceways, cellular concrete floor raceways, 
cellular metal floor raceways, surface raceways, wireways and 
bus ways. 

RAINPROOF. Constructed, protected or treated so as to pre- 
vent rain from interfering with the successful operation of the 
apparatus under specified test conditions. 

RAIN TIGHT. Constructed or protected so that exposure to a 
beating rain will not result in the entrance of water under speci- 
fied test conditions. 

RECEPTACLE. A receptacle is a contact device installed at 
the outlet for the connection of an attachment plug. A single 
receptacle is a single contact device with no other contact 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



479 



ELECTRICAL DEFINITIONS 



device on the same yoke. A multiple receptacle is two or more 
contact devices on the same yoke. 

RECEPTACLE OUTLET. An outlet where one or more 
receptacles are installed. 

SERVICE. The conductors and equipment for delivering 
energy from the serving utility to the wiring system of the pre- 
mises served. 

SERVICE CABLE. Service conductors made up in the form 
of a cable. 

SERVICE CONDUCTORS. The conductors from the ser- 
vice point to the service disconnecting means. 

SERVICE DROP. The overhead service conductors from the 
last pole or other aerial support to and including the splices, if 
any, connecting to the service-entrance conductors at the build- 
ing or other structure. 

SERVICE-ENTRANCE CONDUCTORS, OVERHEAD 
SYSTEM. The service conductors between the terminals of 
the service equipment and a point usually outside the building, 
clear of building walls, where joined by tap or splice to the ser- 
vice drop. 

SERVICE-ENTRANCE CONDUCTORS, UNDER- 
GROUND SYSTEM. The service conductors between the ter- 
minals of the service equipment and the point of connection to 
the service lateral. 

SERVICE EQUIPMENT. The necessary equipment, usually 
consisting of a circuit breaker(s) or switch(es) and fuse(s), and 
their accessories, connected to the load end of the service con- 
ductors to a building or other structure, or an otherwise desig- 
nated area, and intended to constitute the main control and 
cutoff of the supply. 

SERVICE LATERAL. The underground service conductors 
between the street main, including any risers at a pole or other 
structure or from transformers, and the first point of connection 
to the service-entrance conductors in a terminal box or meter or 
other enclosure, inside or outside the building wall. Where 
there is no terminal box, meter or other enclosure with ade- 
quate space, the point of connection shall be considered to be 
the point of entrance of the service conductors into the build- 
ing. 

SERVICE POINT. Service point is the point of connection 
between the facilities of the serving utility and the premises 
wiring. 

STRUCTURE. That which is built or constructed. 

SWITCHES 

General-use switch. A switch intended for use in general 
distribution and branch circuits. It is rated in amperes and is 
capable of interrupting its rated current at its rated voltage. 

General-use snap switch. A form of general-use switch 
constructed so that it can be installed in device boxes or on 
box covers or otherwise used in conjunction with wiring 
systems recognized by this code. 

Isolating switch. A switch intended for isolating an electric 
circuit from the source of power. It has no interrupting rating 



and is intended to be operated only after the circuit has been 
opened by some other means. 

Motor-circuit switch. A switch, rated in horsepower that is 
capable of interrupting the maximum operating overload 
current of a motor of the same horsepower rating as the 
switch at the rated voltage. 

UTILIZATION EQUIPMENT. Equipment that utilizes elec- 
tric energy for electronic, electromechanical, chemical, heat- 
ing, lighting or similar purposes. 

VENTILATED. Provided with a means to permit circulation 
of air sufficient to remove an excess of heat, fumes or vapors. 

VOLTAGE (OF A CIRCUIT). The greatest 
root-mean-square (rms) (effective) difference of potential 
between any two conductors of the circuit concerned. 

VOLTAGE, NOMINAL. A nominal value assigned to a cir- 
cuit or system for the purpose of conveniently designating its 
voltage class (e.g., 120/240). The actual voltage at which a cir- 
cuit operates can vary from the nominal within a range that per- 
mits satisfactory operation of equipment. 

VOLTAGE TO GROUND. For grounded circuits, the voltage 
between the given conductor and that point or conductor of the 
circuit that is grounded. For ungrounded circuits, the greatest 
voltage between the given conductor and any other conductor 
of the circuit. 

WATERTIGHT. So constructed that moisture will not enter 
the enclosure under specified test conditions. 

WEATHERPROOF. So constructed or protected that expo- 
sure to the weather will not interfere with successful operation. 



480 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 35 

SERVICES 



SECTION E3501 
GENERAL SERVICES 

E3501.1 Scope. This chapter covers service conductors and 
equipment for the control and protection of services and their 
installation requirements. 

I E3501.2 Number of services. One- and two-family dwellings 
shall be supplied by only one service. 

E3501.3 One building or otlier structure not to be supplied 
through another. Service conductors supplying a building or 
other structure shall not pass through the interior of another 
building or other structure. 

E3501.4 Other conductors in raceway or cable. Conductors 
other than service conductors shall not be installed in the same 
service raceway or service cable. 

Exceptions: 

1. Grounding conductors and bonding jumpers. 

2. Load management control conductors having 
over-current protection. 

E3501.5 Raceway seal. Where a service raceway enters from 
an underground distribution system, it shall be sealed in accor- 
dance with Section E3703.6. 

I E3501.6 Service disconnect required. Means shall be pro- 
vided to disconnect all conductors in a building or other struc- 
ture from the service entrance conductors. 

E3501.6.1 Marking of service equipment and discon- 
nects. Service disconnects shall be permanently marked as 
a service disconnect. Service equipment shall be listed for 
the purpose. Individual meter socket enclosures shall not be 
considered service equipment. 

E3501.6.2 Service disconnect location. The service dis- 
connecting means shall be installed at a readily accessible 
location either outside of a building or inside nearest the 
point of entrance of the service conductors. Service discon- 
necting means shall not be installed in bathrooms. Each 
occupant shall have access to the disconnect serving the 
dwelling unit in which they reside. 

E3501.7 Maximum number of disconnects. The service dis- 
connecting means shall consist of not more than six switches or 
six circuit breakers mounted in a single enclosure or in a group 
of separate enclosures. 



SECTION E3502 
SERVICE SIZE AND RATING 

E3502.1 Ampacity of ungrounded conductors. Ungrounded 

service conductors shall have an ampacity of not less than the 
I load served. For one-family dwellings, the ampacity of the 

ungrounded conductors shall be not less than 100 amperes, 3 
I wire. For all other installations, the ampacity of the 

ungrounded conductors shall be not less than 60 amperes. 



E3502.2 Service load. The minimum load for ungrounded ser- 
vice conductors and service devices that serve 100 percent of 
the dwelling unit load shall be computed in accordance with 
Table E3502.2. Ungrounded service conductors and service 
devices that serve less than 100 percent of the dwelling unit 
load shall be computed as required for feeders in accordance 
with Chapter 36. 

TABLE E3502.2 
MINIMUM SERVICE LOAD CALCULATION 



LOADS AND PROCEDURE 



3 volt-amperes per square foot of floor area for general lighting 
and general use receptacle outlets. 



Plus 



1,500 volt-amperes x total number of 20-ampere-rated small 
appliance and laundry circuits. 



Plus 



The nameplate volt-ampere rating of all fastened-in-place, 
permanently connected or dedicated circuit-supplied appliances 
such as ranges, ovens, cooking units, clothes dryers and water 
heaters. 



Apply the following demand factors to the above subtotal: 



The minimum subtotal for the loads above shall be 100 percent of 
the first 10,000 volt-amperes of the sum of the above loads plus 40 
percent of any portion of the sum that is in excess of 10,000 
volt-amperes. 



Plus the largest of the following: 



Nameplate rating(s) of the air-conditioning and cooling 
equipment. 



Nameplate rating(s) of the heating where a heat pump is used 
without any supplemental electric heating. 



Nameplate rating of the electric thermal storage and other heating 
systems where the usual load is expected to be continuous at the 
full nameplate value. Systems quahfying under this selection shall 
not be figured under any other category in this table. 



One-hundred percent of nameplate rating of the heat pump 
compressor and sixty-five percent of the supplemental electric 
heating load for central electric space-heating systems. If the heat 
pump compressor is prevented from operating at the same time as 
the supplementary heat, the compressor load does not need to be 
added to the supplementary heat load for the total central electric 
space-heating load. 



Sixty-five percent of nameplate rating(s) of electric space- 
heating units if less than four separately controlled units. 



Forty percent of nameplate rating(s) of electric space-heating units 
of four or more separately controlled units. 



The minimum total load in amperes shall be the 
volt-ampere sum calculated above divided by 240 volts. 



E3502.2.1 Services under 100 amperes. Services that are 
not required to be 100 amperes shall be sized in accordance 
with Chapter 36. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



481 



SERVICES 



E3502.3 Rating of service disconnect. The combined rating 
of all individual service disconnects serving a single dwelling 
unit shall not be less than the load determined from Table 
E3502.2 and shall not be less than as specified in Section 
E3502.1. 

E3502.4 Voltage rating. Systems shall be three-wire, 
120/240- volt, single-phase with a grounded neutral. 



SECTION E3503 

SERVICE, FEEDER AND GROUNDING 

ELECTRODE CONDUCTOR SIZING 

E3503.1 Grounded and ungrounded service conductor size. 

Conductors used as ungrounded service entrance conductors, 
service lateral conductors, and feeder conductors that serve as 
the main power feeder to a dwelling unit shall be those Usted in 
Table E3503.1. The main power feeder shall be the feeder(s) 
between the main disconnect and the lighting and appliance 
branch-circuit panelboard(s). Ungrounded service conductors 
shall have a minimum size in accordance with Table E3503.1. 
The grounded conductor ampacity shall be not less than the 
maximum unbalance of the load and its size shall be not smaller 



than the required minimum grounding electrode conductor size 
specified in Table E3503.1. 

E3503.2 Ungrounded service conductors for accessory 
buildings and structures. Ungrounded conductors for other 
than dwelling units shall have an ampacity of not less than 60 | 
amperes and shall be sized as required for feeders in Chapter 36. 

Exceptions: 

1 . For limited loads of a single branch circuit, the service | 
conductors shall have an ampacity of not less than 15 | 
amperes. 

2. For loads consisting of not more than two two-wire 
branch circuits, the service conductors shall have an I 
ampacity of not less than 30 amperes. | 

E3503.3 Overload protection. Each ungrounded service con- 
ductor shall have overload protection. 

E3503.3.1 Ungrounded conductor. Overload protection 
shall be provided by an overcurrent device installed in series 
with each ungrounded service conductor. The overcurrent 
device shall have a rating or setting not higher than the 
allowable ampacity specified in Table E3503.1. A set of 



TABLE E3503.1 
SERVICE CONDUCTOR AND GROUNDING ELECTRODE CONDUCTOR SIZING 



CONDUCTOR TYPES AND SIZES— THHN, THHW, THW, THWN, USE, XHHW, 

THW-2, THWN-2, XHHW-2, SE, USE-2 

(Parallel sets of 1/0 and larger conductors are 

permitted in either a single raceway or in separate raceways) 


ALLOWABLE 
AMPACITY 


MINIMUM GROUNDING 
ELECTRODE CONDUCTOR SIZE^ 


Copper 

(AWG) 


Aluminum and copper-clad aluminum 
(AWG) 


Maximum load 
(amps) 


Copper 

(AWG) 


Aluminum 
(AWG) 


4 


2 


100 


8" 


6= 


3 


1 


110 


8" 


6*= 


2 


1/0 


125 


8" 


e 


1 


2/0 


150 


6*= 


4 


1/0 


3/0 


175 


6^^ 


4 


2/0 


4/0 or 
two sets of I/O 


200 


4d 


2" 


3/0 


250 kcmil or 
two sets of 2/0 


225 


4d 


1" 


4/0 or 
two sets of 1/0 


300 kcmil or 
two sets of 3/0 


250 


1" 


1/0" 


250 kcmil 
or two sets of 2/0 


350 kcmil or 
two sets of 4/0 


300 


2" 


1/0" 


350 kcmil 
or two sets of 3/0 


500 kcmil or 
two sets of 250 kcmil 


350 


2d 


1/0" 


400 kcmil 
or two sets of 4/0 


600 kcmil or 
two sets of 300 kcmil 


400 


1/0'' 


3/0" 



For SI: 1 inch = 25.4 mm. 

a. Where protected by a ferrous metal raceway, grounding electrode conductors shall be electrically bonded to the ferrous metal raceway at both ends. 

b. Eight AWG grounding electrode conductors shall be protected with metal conduit or nonmetallic conduit. 

c. Where not protected, 6 AWG grounding electrode conductors shall closely follow a structural surface for physical protection. The supports shall be spaced not 
more than 24 inches on center and shall be within 12 inches of any enclosure or termination. 

d. Where the sole grounding electrode system is a ground rod or pipe as covered in Section E3508.2, the grounding electrode conductor shall not be required to be 
larger than 6 AWG copper or 4 AWG aluminum. Where the sole grounding electrode system is the footing steel as covered in Section E3508.1.2, the grounding 
electrode conductor shall not be required to be larger than 4 AWG copper conductor. 



482 



2006 INTERNATIONAL RESIDENTIAL CODE® 



fuses shall be considered all the fuses required to protect all 
of the ungrounded conductors of a circuit. Single pole cir- 
cuit breakers, grouped in accordance with Section E3501 .7, 
shall be considered as one protective device. 

Exception: Two to six circuit breakers or sets of fuses shall 
be permitted as the overcurrent device to provide the over- 
load protection. The sum of the ratings of the circuit break- 
ers or fuses shall be permitted to exceed the ampacity of the 
service conductors, provided that the calculated load does 
not exceed the ampacity of the service conductors. 

E3503.3.2 Not in grounded conductor. Overcurrent 
devices shall not be connected in series with a grounded ser- 
vice conductor except where a circuit breaker is used that 
simultaneously opens all conductors of the circuit. 

E3503.3.3 Location. The service overcurrent device shall 
be an integral part of the service disconnecting means or 
shall be located immediately adjacent thereto. 

E3503.4 Grounding electrode conductor size. The ground- 
ing electrode conductors shall be sized based on the size of the 
service entrance conductors as required in Table E3503.1. 

E3503.5 Temperature limitations. Except where the equip- 
ment is marked otherwise, conductor ampacities used in deter- 
mining equipment termination provisions shall be based on 
Table E3503.1. 



SERVICES 



SECTION E3504 

OVERHEAD SERVICE-DROP AND SERVICE 

CONDUCTOR INSTALLATION 

E3504.1 Clearances on buildings. Open conductors and 
multiconductor cables without an overall outer jacket shall 
have a clearance of not less than 3 feet (914 mm) from the sides 
of doors, porches, decks, stairs, ladders, fire escapes and balco- 
nies, and from the sides and bottom of windows that open. See 
Figure E3504.1. 

E3504.2 Vertical clearances. Service-drop conductors shall 
not have ready access and shall comply with Sections 
E3504.2.1andE3504.2.2. 

E3504.2.1 Above roofs. Conductors shall have a vertical 
clearance of not less than 8 feet (2438 mm) above the roof 
surface. The vertical clearance above the roof level shall be 
maintained for a distance of not less than 3 feet (914 mm) in 
all directions from the edge of the roof. See Figure 
E3504.2.1. 

Exceptions: 

1 . Conductors above a roof surface subject to pedes- 
trian traffic shall have a vertical clearance from the 
roof surface in accordance with Section 
E3504.2.2. 

2. Where the roof has a slope of 4 inches ( 1 02 mm) in 
12 inches (305 mm), or greater, the minimum 
clearance shall be 3 feet (914 mm). 




3-FOOT CLEARANCE 



CLEARANCE NOT REQUIRED FROM 
NONOPENABLE WINDOWS 



CLEARANCE NOT REQUIRED ABOVE OPENINGS 



CLEARANCE NOT REQUIRED BETWEEN WINDOW 
AND SE CABLE OR CONDUCTORS IN RACEWAY 



For SI: 1 foot = 304.8 mm. 



FIGURE E3504.1 
CLEARANCES FROM BUILDING OPENINGS 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



483 



SERVICES 



3. The minimum clearance above only the overhang- 
ing portion of the roof shall not be less than 18 
inches (457 mm) where not more than 6 feet (1829 
mm) of conductor length passes over 4 feet (1219 
mm) or less of roof surface measured horizontally 
and such conductors are terminated at a 
through-the-roof raceway or approved support. 

4. The requirement for maintaining the vertical clear- 
ance for a distance of 3 feet (914 mm) from the 
edge of the roof shall not apply to the final conduc- 
tor span where the service drop is attached to the 
side of a building. 

E3504.2.2 Vertical clearance from grade. Service-drop 
conductors shall have the following minimum clearances 
from final grade: 

1. For service-drop cables supported on and cabled 
together with a grounded bare messenger wire, the 
minimum vertical clearance shall be 10 feet (3048 
mm) at the electric service entrance to buildings, at 
the lowest point of the drip loop of the building elec- 
tric entrance, and above areas or sidewalks accessed 
by pedestrians only. Such clearance shall be mea- 
sured from final grade or other accessible surfaces. 



2. Twelve feet (3658 mm) — over residential property 
and driveways. 

3 . Eighteen feet (5486 mm) — over public streets, alleys, 
roads or parking areas subject to truck traffic. 

E3504.3 Point of attachment. The point of attachment of the 
service-drop conductors to a building or other structure shall 
provide the minimum clearances as specified in Sections 
E3504.1 through E3504.2.2. In no case shall the point of attach- 
ment be less than 10 feet (3048 mm) above finished grade. 

E3504.4 Means of attachment. Multiconductor cables used 
for service drops shall be attached to buildings or other struc- 
tures by fittings approved for the purpose. 

E3504.5 Service masts as supports. Where a service mast is 
used for the support of service-drop conductors, it shall be of 
adequate strength or be supported by braces or guys to with- 
stand the strain imposed by the service drop. Where race- 
way-type service masts are used, all equipment shall be 
approved. Only power service drop conductors shall be permit- 
ted to be attached to a service mast. 

E3504.6 Supports over buildings. Service-drop conductors 
passing over a roof shall be securely supported. Where practi- 
cable, such supports shall be independent of the building. 



SECTION E3504.2.1 AND EXCEPTION 1 



SECTION E3504.2.1 AND EXCEPTION 3 




SECTION E3504.2.1 
MAINTAIN ALL 
CLEARANCES 3'0" 
MINIMUM BEYOND THE 
EDGE OF THE ROOF. 
SEE EXCEPTION 4. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



FIGURE E3504.2.1 
CLEARANCES FROM ROOFS 



484 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



SERVICES 



SECTION E3505 
SERVICE-ENTRANCE CONDUCTORS 

E3505.1 Insulation of service-entrance conductors. Ser- 
vice-entrance conductors entering or on the exterior of build- 
ings or other structures shall be insulated in accordance with 
Section E3306.5. 

Exceptions: 

1 . A copper grounded conductor shall not be required to 
be insulated where it is: 

1 . 1 . In a raceway or part of a service cable assem- 
bly, 

1 .2. Directly buried in soil of suitable condition, or 

1 .3. Part of a cable assembly listed for direct burial 
without regard to soil conditions. 

2. An aluminum or copper-clad aluminum grounded 
conductor shall not be required to be insulated where 
part of a cable or where identified for direct burial or 
utilization in underground raceways. 

E3505.2 Wiring methods for services. Service-entrance wir- 
ing methods shall be installed in accordance with the applica- 
ble requirements in Chapter 37. 

E3505.3 Spliced conductors. Service-entrance conductors 
shall be permitted to be spliced or tapped. Splices shall be made 
in enclosures or, if directly buried, with listed underground 
splice kits. Conductor splices shall be made in accordance with 
Chapters 33, 36, 37 and 38. 

E3505.4 Protection against physical damage. Underground 
service-entrance conductors shall be protected against physical 
damage in accordance with Chapter 37. 

E3505.5 Protection of service cables against damage. 

Above-ground service-entrance cables, where subject to phys- 
ical damage, shall be protected by one or more of the following: 
rigid metal conduit, intermediate metal conduit. Schedule 80 
rigid nonmetallic conduit, electrical metallic tubing or other 
approved means. 

E3505.6 Locations exposed to direct sunlight. Insulated con- 
ductors and cables used where exposed to direct rays of the sun 
shall comply with one of the following: 

1 . The cables are listed, or listed and marked, as being sun- 
light resistant. 

2. The conductors are listed, or listed and marked, as being 
sunlight resistant. 

3. The conductors and cables are covered with insulating 
material, such as tape or sleeving, that is listed, or listed 
and marked, as being sunlight resistant. 

E3505.7 Mounting supports. Service cables shall be sup- 
ported by straps or other approved means within 12 inches (305 
mm) of every service head, gooseneck or connection to a race- 
way or enclosure and at intervals not exceeding 30 inches (762 
mm). 

E3505.8 Raceways to drain. Where exposed to the weather, 
raceways enclosing service-entrance conductors shall be 
raintight and arranged to drain. Where embedded in masonry, 
raceways shall be arranged to drain. 



E3505.9 Overhead service locations. Connections at service 
heads shall be in accordance with Sections E3505.9.1 through 
E3505.9.7. 

E3505.9.1 Rain-tight service head. Service raceways shall 
be equipped with a rain-tight service head at the point of 
connection to service-drop conductors. 

E3505.9.2 Service cable, service head or gooseneck. Ser- 
vice cable shall be equipped with a rain-tight service head or 
shall be formed into a gooseneck in an approved manner. 

E3505.9.3 Service head location. Service heads, and 
goosenecks in service-entrance cables, shall be located 
above the point of attachment of the service-drop conduc- 
tors to the building or other structure. 

Exception: Where it is impracticable to locate the ser- 
vice head or gooseneck above the point of attachment, | 
the service head or gooseneck location shall be not more 
than 24 inches (610 mm) from the point of attachment. 

E3505.9.4 Separately bushed openings. Service heads 
shall have conductors of different potential brought out 
through separately bushed openings. 

E3505.9.5 Drip loops. Drip loops shall be formed on indi- 
vidual conductors. To prevent the entrance of moisture, ser- 
vice-entrance conductors shall be connected to the 
service-drop conductors either below the level of the service 
head or below the level of the termination of the ser- 
vice-entrance cable sheath. 

E3505.9.6 Conductor arrangement. Service-drop con- 
ductors and service-entrance conductors shall be arranged 
so that water will not enter service raceways or equipment. 

E3505.9.7 Secured. Service cables shall be held securely in 
place. 



SECTION E3506 
SERVICE EQUIPMENT— GENERAL 

E3506.1 Service equipment enclosures. Energized parts of 
service equipment shall be enclosed. 

E3506.2 Working space. In no case shall the working space in 
the vicinity of service equipment be less than that specified in 
Chapter 33. 

E3506.3 Available short-circuit current. Service equipment 
shall be suitable for the maximum fault current available at its 
supply terminals, but not less than 10,000 amperes. 

E3506.4 Marking. Service equipment shall be marked to iden- 
tify it as being suitable for use as service equipment. Individual 
meter socket enclosures shall not be considered service equip- 
ment. 



SECTION E3507 
SYSTEM GROUNDING 

E3507.1 System service ground. The premises wiring system 
shall be grounded at the service with a grounding electrode 
conductor connected to a grounding electrode system as 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



485 



SERVICES 



required by this code. Grounding electrode conductors shall be 
sized in accordance with Table E3503.1. 

E3507.2 Location of grounding electrode conductor con- 
nection. The grounding electrode conductor shall be con- 
nected to the grounded service conductor at any accessible 
point from the load end of the service drop or service lateral to 
and including the terminal or bus to which the grounded service 
conductor is connected at the service disconnecting means. A 
grounding connection shall not be made to any grounded cir- 
cuit conductor on the load side of the service disconnecting 
means, except as provided in Section E3507.3. 

E3507.3 Buildings or structures supplied by feeder(s) or 
branch circuit(s). Buildings or structures supplied by 
feeder(s) or branch circuit(s) shall have a grounding electrode 
or grounding electrode system installed in accordance with 
Section E3508. The grounding electrode conductor(s) shall be 
connected in a manner specified in Section E3507.3.1 or 
E3507.3.2. Where there is no existing grounding electrode, the 
grounding electrode(s) required in Section E3508 shall be 
installed. 

Exception: A grounding electrode shall not be required 
where only one branch circuit supplies the building or struc- 
ture and the branch circuit includes an equipment grounding 
conductor for grounding the noncurrent-carrying parts of all 
equipment. For the purposes of this section, a multiwire 
branch circuit shall be considered as a single branch circuit. 

E3507.3.1 Equipment grounding conductor. An equip- 
ment grounding conductor as described in Section E3808 
shall be run with the supply conductors and connected to the 
building or structure disconnecting means and to the 
grounding electrode(s). The equipment grounding conduc- 
tor shall be used for grounding or bonding of equipment, 
structures or frames required to be grounded or bonded. The 
equipment grounding conductor shall be sized in accor- 
dance with Section E3808.12. Any installed grounded con- 
ductor shall not be connected to the equipment grounding 
conductor or to the grounding electrode(s). 

E3507.3.2 Grounded conductor. Where an equipment 
grounding conductor is not run with the supply conductors 
to the building or structure, and there are no continuous 
metallic paths bonded to the grounding system in both 
buildings or structures involved, and ground-fault protec- 
tion of equipment has not been installed on the common ser- 
vice, the grounded circuit conductor run with the supply 
conductors to the building or structure shall be connected to 
the building or structure disconnecting means and to the 
grounding electrode(s) and shall be used for grounding or 
bonding of equipment, structures, or frames required to be 
grounded or bonded. The size of the grounded conductor 
shall be not smaller than the larger of: 

1. That required by Section E3604.3. 

2. That required by Section E3808.12. 

E3507.4 Grounding electrode conductor. A grounding elec- 
trode conductor shall be used to connect the equipment 
grounding conductors, the service equipment enclosures, and 
the grounded service conductor to the grounding electrode(s). 



E3507.5 Main bonding jumper. An unspliced main bonding 
jumper shall be used to connect the equipment grounding con- 
ductor(s) and the service-disconnect enclosure to the grounded 
conductor of the system within the enclosure for each service 
disconnect. 

E3507.6 Common grounding electrode. Where an ac system 
is connected to a grounding electrode in or at a building or 
structure, the same electrode shall be used to ground conductor 
enclosures and equipment in or on that building or structure. 
Where separate services, feeders or branch circuits supply a 
building and are required to be connected to a grounding elec- 
trode(s), the same grounding electrode(s) shall be used. Two or 
more grounding electrodes that are effectively bonded together 
shall be considered as a single grounding electrode system. 



SECTION E3508 
GROUNDING ELECTRODE SYSTEM 

E3508.1 Grounding electrode system. All electrodes speci- 
fied in Sections E3508.1.1, E3508.1.2, E3508.1.3, E3508.1.4 
and E3508.1.5 that are present at each building or structure 
served shall be bonded together to form the grounding elec- 
trode system. Where none of these electrodes are available, one 
or more of the electrodes specified in Sections E3508.1.3, 
E3508.1.4 and E3508.1.5 shall be installed and used. 

Exception: Concrete-encased electrodes of existing build- 
ings or structures shall not be required to be part of the 
grounding electrode system where the steel reinforcing bars 
or rods are not accessible for use without disturbing the con- 
crete. 

E3508.1.1 Metal underground water pipe. A metal 
underground water pipe that is in direct contact with the 
earth for 10 feet (3048 mm) or more, including any well cas- 
ing effectively bonded to the pipe and that is electrically 
continuous, or made electrically continuous by bonding 
around insulating joints or insulating pipe to the points of 
connection of the grounding electrode conductor and the 
bonding conductors, shall be considered as a grounding 
electrode (see Section E3508.1). Interior metal water pip- 
ing located more than 5 feet (1524 mm) from the entrance to 
the building shall not be used as part of the grounding elec- 
trode system or as a conductor to interconnect electrodes 
that are part of the grounding electrode system. 

E3508.1.1.1 Installation. Continuity of the grounding | 
path or the bonding connection to interior piping shall 
not rely on water meters, filtering devices and similar 
equipment. A metal underground water pipe shall be 
supplemented by an additional electrode of a type speci- 
fied in Sections E3508.1.2 through E3508.1.5. The sup- 
plemental electrode shall be bonded to the grounding 
electrode conductor, the grounded service entrance con- 
ductor, a nonflexible grounded service raceway or any 
grounded service enclosure. 

Where the supplemental electrode is a rod, pipe or 
plate electrode in accordance with Sections E3508.1.4 
and E3508. 1 .5, that portion of the bonding jumper that is 
the sole connection to the supplemental grounding elec- 



486 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



SERVICES 



trode shall not be required to be larger than 6 AWG cop- 
per or 4 AWG aluminum wire. 

E3508.1.2 Concrete-encased electrode. An electrode 
encased by at least 2 inches (5 1 mm) of concrete, located 
within and near the bottom of a concrete foundation or foot- 
ing that is in direct contact with the earth, consisting of at least 
20 feet (6096 mm) of one or more bare or zinc-galvanized or 
other electrically conductive coated steel reinforcing bars or 
rods of not less than V2inch (12.7 mm) diameter, or consisting 
of at least 20 feet (6096 mm) of bare copper conductor not 
smaller than 4 AWG shall be considered as a grounding elec- 
trode. Reinforcing bars shall be permitted to be bonded 
together by the usual steel tie wires or other effective means. 

E3508.1.3 Ground rings. A ground ring encircling the 
building or structure, in direct contact with the earth at a 
depth below the earth's surface of not less than 30 inches 
(762 mm), consisting of at least 20 feet (6096 mm) of bare 
copper conductor not smaller than 2 AWG shall be consid- 
ered as a grounding electrode. 

E3508.1.4 Rod and pipe electrodes. Rod and pipe elec- 
trodes not less than 8 feet (2438 mm) in length and consist- 
ing of the following materials shall be considered as a 
grounding electrode: 

1 . Electrodes of pipe or conduit shall not be smaller than 
trade size V4 (metric designator 21) and, where of iron 
or steel, shall have the outer surface galvanized or 
otherwise metal-coated for corrosion protection. 

2. Electrodes of rods of iron or steel shall be at least Vg 
inch (15.9 mm) in diameter. Stainless steel rods less 
than Vg inch (15.9 mm) in diameter, nonferrous rods 
or their equivalent shall be listed and shall be not less 
than V2 inch (12.7 mm) in diameter. 

E3508.1.4.1 Installation. The rod and pipe electrodes 
shall be installed such that at least 8 feet (2438 mm) of 
length is in contact with the soil. They shall be driven to a 
depth of not less than 8 feet (2438 mm) except that, 
where rock bottom is encountered, electrodes shall be 
driven at an oblique angle not to exceed 45 degrees from 
the vertical or shall be buried in a trench that is at least 30 
inches (762 mm) deep. The upper end of the electrodes 
shall be flush with or below ground level except where 
the aboveground end and the grounding electrode con- 
ductor attachment are protected against physical dam- 
age. 

E3508.1.5 Plate electrodes. A plate electrode that exposes 
not less than 2 square feet (0.186 m^) of surface to exterior 
soil shall be considered as a grounding electrode. Electrodes 
of iron or steel plates shall be at least V4 inch (6.4 mm) in 
thickness. Electrodes of nonferrous metal shall be at least 
0.06 inch (1.5 mm) in thickness. Plate electrodes shall be 
installed not less than 30 inches (762 mm) below the surface 
of the earth. 

E3508.2 Bonding jumper. The bonding jumper(s) used to 
connect the grounding electrodes together to form the ground- 
ing electrode system shall be installed in accordance with Sec- 
tions E3510.2, and E3510.3, shall be sized in accordance with 



Section E3503.4, and shall be connected in the manner speci- 
fied in Section E35 11.1. 

E3508.3 Rod, pipe and plate electrode requirements. 

Where practicable, rod, pipe and plate electrodes shall be 
embedded below permanent moisture level. Such electrodes 
shall be free from nonconductive coatings such as paint or 
enamel. Where more than one such electrode is used, each elec- 
trode of one grounding system shall be not less than 6 feet 
(1 829 mm) from any other electrode of another grounding sys- 
tem. Two or more grounding electrodes that are effectively 
bonded together shall be considered as a single grounding elec- 
trode system. That portion of a bonding jumper that is the sole 
connection to a rod, pipe or plate electrode shall not be required 
to be larger than 6 AWG copper or 4 AWG aluminum wire. 

E3508.4 Resistance of rod, pipe and plate electrodes. A sin- 
gle electrode consisting of a rod, pipe or plate that does not 
have a resistance to ground of 25 ohms or less shall be aug- 
mented by one additional electrode of any of the types speci- 
fied in Sections E3508. 1 .2 through E3508. 1 .5. Where multiple 
rod, pipe or plate electrodes are installed to meet the require- 
ments of this section, they shall be not less than 6 feet (1829 
mm) apart. 



E3508.5 Aluminum electrodes. 

not be permitted. 



Aluminum electrodes shall 



E3508.6 Metal underground gas piping system. A metal 
underground gas piping system shall not be used as a ground- 
ing electrode. 



SECTION E3509 
BONDING 

E3509.1 General. Bonding shall be provided where necessary 
to ensure electrical continuity and the capacity to conduct 
safely any fault current likely to be imposed. 

E3509.2 Bonding of services. The noncurrent-carrying metal 
parts of the following equipment shall be effectively bonded 
together: 

1 . The service raceways or service cable armor. 

2. All service enclosures containing service conductors, 
including meter fittings, and boxes, inteiposed in the ser- 
vice raceway or armor. 

3. Any metallic raceways or armor enclosing a grounding 
electrode conductor. Bonding shall apply at each end and 
to all intervening raceways, boxes and enclosures 
between the service equipment and the grounding elec- 
trode. 

E3509.3 Bonding to other systems. An accessible means 
external to enclosures for connecting intersystem bonding and 
grounding electrode conductors shall be provided at the service 
equipment and at the disconnecting means for any additional 
buildings or structures by at least one of the following means: 

1. Exposed nonflexible metallic service raceways. 

2. Exposed grounding electrode conductor. 



2006 INTERNATIONAL RESIDENTIAL CODE"* 



487 



SERVICES 



3. Approved means for the external connection of a copper 
or other corrosion-resistant bonding or grounding con- 
ductor to the service raceway or equipment. 

E3509.4 Method of bonding at the service. Electrical conti- 
nuity at service equipment, service raceways and service con- 
ductor enclosures shall be ensured by one or more of the 
methods specified in Sections E3509.4.1 through E3509.4.4. 

Bonding jumpers meeting the other requirements of this 
code shall be used around concentric or eccentric knockouts 
that are punched or otherwise formed so as to impair the electri- 
cal connection to ground. Standard locknuts or bushings shall 
not be the sole means for the bonding required by this section. 

E3509.4.1 Grounded service conductor. Equipment shall 
be bonded to the grounded service conductor in a manner 
provided in this code. 

E3509.4.2 Threaded connections. Equipment shall be 
bonded by connections using threaded couplings or 
threaded bosses on enclosures. Such connections shall be 
made wrench tight. 

E3509.4.3 Threadless couplings and connectors. Equip- 
ment shall be bonded by threadless couplings and connec- 
tors for metal raceways and metal-clad cables. Such 
couplings and connectors shall be made wrench tight. Stan- 
dard locknuts or bushings shall not be used for the bonding 
required by this section. 

E3509.4.4 Other devices. Equipment shall be bonded by 
other listed devices, such as bonding-type locknuts, bush- 
ings and bushings with bonding jumpers. 

E3509.5 Sizing bonding juniper on supply side of service 
and main bonding jumper. The bonding jumper shall not be 
smaller than the sizes shown in Table E3503.1 for grounding 
electrode conductors. Where the service-entrance conductors 
are paralleled in two or more raceways or cables, the equipment 
bonding jumper, where routed with the raceways or cables, 
shall be run in parallel. The size of the bonding jumper for each 
raceway or cable shall be based on the size of the ser- 
vice-entrance conductors in each raceway or cable. 

E3509.6 Metal water piping bonding. The metal water pip- 
ing system shall be bonded to the service equipment enclosure, 
the grounded conductor at the service, the grounding electrode 
conductor where of sufficient size, or to the one or more 
grounding electrodes used. The bonding jumper shall be sized 
in accordance with Table E3503. 1 . The points of attachment of 
the bonding jumper(s) shall be accessible. 

E3509.7 Bonding other metal piping. Where installed in or 
attached to a building or structure, metal piping systems, 
including gas piping, capable of becoming energized shall be 
bonded to the service equipment enclosure, the grounded con- 
ductor at the service, the grounding electrode conductor where 
of sufficient size, or to the one or more grounding electrodes 
used. The bonding jumper shall be sized in accordance with 
Table E3808.12 using the rating of the circuit capable of ener- 
gizing the piping. The equipment grounding conductor for the 
circuit that is capable of energizing the piping shall be permit- 
ted to serve as the bonding means. The points of attachment of 
the bonding jumper(s) shall be accessible. 



SECTION E3510 
GROUNDING ELECTRODE CONDUCTORS 

E3510.1 Continuous. The unspliced grounding electrode con- 
ductor shall run to any convenient grounding electrode avail- 
able in the grounding electrode system, or to one or more 
grounding electrode(s) individually. The grounding electrode 
conductor shall be sized for the largest grounding electrode 
conductor required among all of the electrodes connected to it. 

E3510.2 Securing and protection against physical damage. I 

Where exposed, a grounding electrode conductor or its enclo- | 
sure shall be securely fastened to the surface on which it is car- 
ried. A 4 AWG or larger conductor shall be protected where 
exposed to physical damage. A 6 AWG grounding conductor 
that is free from exposure to physical damage shall be permit- 
ted to be run along the surface of the building construction 
without metal covering or protection where it is and securely 
fastened to the construction; otherwise, it shall be in rigid metal 
conduit, intermediate metal conduit, rigid nonmetallic conduit, 
electrical metallic tubing or cable armor. Grounding electrode | 
conductors smaller than 6 AWG shall be in rigid metal conduit, 
intermediate metal conduit, rigid nonmetallic conduit, electri- 
cal metallic tubing or cable armor. 

Bare aluminum or copper-clad aluminum grounding con- | 
ductors shall not be used where in direct contact with masonry 
or the earth or where subject to corrosive conditions. Where 
used outside, aluminum or copper-clad aluminum grounding 
conductors shall not be installed within 18 inches (457 mm) of 
the earth. 

E3510.3 Enclosures for grounding electrode conductors. 

Ferrous metal enclosures for grounding electrode conductors | 
shall be electrically continuous from the point of attachment to 
cabinets or equipment to the grounding electrode, and shall be 
securely fastened to the ground clamp or fitting. Nonferrous ■ 
metal enclosures shall not be required to be electrically contin- I 
uous. Ferrous metal enclosures that are not physically continu- | 
ous from cabinet or equipment to the grounding electrode shall 
be made electrically continuous by bonding each end to the 
grounding conductor. The bonding jumper for a grounding I 
electrode conductor raceway shall be the same size or larger I 
than the required enclosed grounding electrode conductor. | 

Where a raceway is used as protection for a grounding con- 
ductor, the installation shall comply with the requirements of 
Chapter 37. 



SECTION E3511 

GROUNDING ELECTRODE CONDUCTOR 

CONNECTION TO THE GROUNDING ELECTRODES 

E3511.1 Methods of grounding conductor connection to 
electrodes. The grounding or bonding conductor shall be con- I 
nected to the grounding electrode by exothermic welding, | 
listed lugs, listed pressure connectors, listed clamps or other 
listed means. Connections depending on solder shall not be 
used. Ground clamps shall be listed for the materials of the 
grounding electrode and the grounding electrode conductor 
and, where used on pipe, rod or other buried electrodes, shall 
also be listed for direct soil burial or concrete encasement. Not 
more than one conductor shall be connected to the grounding 



488 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



SERVICES 



electrode by a single clamp or fitting unless the clamp or fitting 
is listed for multiple conductors. One of the methods indicated 
in the following items shall be used: 

1. A pipe fitting, pipe plug or other approved device 
screwed into a pipe or pipe fitting. 

2. A listed bolted clamp of cast bronze or brass, or plain or 
malleable iron. 

3. For indoor telecommunications purposes only, a listed 
sheet metal strap-type ground clamp having a rigid metal 
base that seats on the electrode and having a strap of such 
material and dimensions that it is not likely to stretch dur- 
ing or after installation. 

4. Other equally substantial approved means. 

E3511.2 Accessibility. The connection of the grounding elec- 
trode conductor or bonding jumper to the grounding electrodes 
that are not buried or concrete encased shall be accessible. 

E3511.3 Effective grounding path. The connection of the 
grounding electrode conductor or bonding jumper shall be 
made in a manner that will ensure a permanent and effective 
grounding path. Where necessary to ensure effective ground- 
ing for a metal piping system used as a grounding electrode, 
effective bonding shall be provided around insulated joints and 
sections and around any equipment that is likely to be discon- 
nected for repairs or replacement. Bonding conductors shall be 
of sufficient length to permit removal of such equipment while 
retaining the integrity of the bond. 

E3511.4 Protection of ground clamps and fittings. Ground 
clamps or other fittings shall be approved for applications with- 
out protection or shall be protected from physical damage by 
installing them where they are not likely to be damaged or by 
enclosing them in metal, wood or equivalent protective cover- 
ings. 

E3511.5 Clean surfaces. Nonconductive coatings (such as 
paint, enamel and lacquer) on equipment to be grounded shall 
be removed from threads and other contact surfaces to ensure 
good electrical continuity or shall be connected by fittings that 
make such removal unnecessary. 



2006 INTERNATIONAL RESIDENTIAL CODE® 489 



490 2006 INTERNATIONAL RESIDENTIAL CODE'^ 



CHAPTER 36 

BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



SECTION E3601 
GENERAL 

E3601.1 Scope. This chapter covers branch circuits and feed- 
ers and specifies the minimum required branch circuits, the 
allowable loads and the required overcurrent protection for 
branch circuits and feeders that serve less than 100 percent of 
the total dwelling unit load. Feeder circuits that serve 100 per- 
cent of the dwelling unit load shall be sized in accordance with 
the procedures in Chapter 35. 

E3601.2 Branch-circuit and feeder ampacity. Branch-cir- 
cuit and feeder conductors shall have ampacities not less than 
the maximum load to be served. Where a branch circuit or a 
feeder supplies continuous loads or any combination of contin- 
uous and noncontinuous loads, the minimum branch-circuit or 
feeder conductor size, before the application of any adjustment 
or correction factors, shall have an allowable ampacity equal to 
or greater than the noncontinuous load plus 125 percent of the 
continuous load. 

E3601.3 Selection of ampacity. Where more than one calcu- 
lated or tabulated ampacity could apply for a given circuit 
length, the lowest value shall be used. 

Exception: Where two different ampacities apply to adja- 
cent portions of a circuit, the higher ampacity shall be per- 
mitted to be used beyond the point of transition, a distance 
equal to 10 feet (3048 mm) or 10 percent of the circuit 
length figured at the higher ampacity, whichever is less. 

E3601.4 Multi-outlet branch circuits. Conductors of 
multi-outlet branch circuits supplying more than one recepta- 
cle for cord-and-plug-connected portable loads shall have 
ampacities of not less than the rating of the branch circuit. 

E3601.5 Multiwire branch circuits. All conductors for 
multiwire branch circuits shall originate from the same 
panelboard or similar distribution equipment. Where two or 
more devices on the same yoke or strap are supplied by a 
multiwire branch circuit, a means shall be provided at the point 
where the circuit originates to simultaneously disconnect all 
ungrounded conductors of the multiwire circuit. Except where 
all ungrounded conductors are opened simultaneously by the 
branch-circuit overcurrent device, multiwire branch circuits 
shall supply only line-to-neutral loads or only one appliance. 



SECTION E3602 
BRANCH CIRCUIT RATINGS 

E3602.1 Branch-circuit voltage limitations. The voltage rat- 
ings of branch circuits that supply luminaires or receptacles for 
cord-and-plug-connected loads of up to 1,400 volt-amperes or 
of less than V4 horsepower shall be limited to a maximum rating 
of 120 volts, nominal, between conductors. 

Branch circuits that supply cord-and-plug-connected or per- 
manently connected utilization equipment and appliances 



rated at over 1,440 volt-amperes or V4 horsepower and greater 
shall be rated at 120 volts or 240 volts, nominal. 

E3602.2 Branch-circuit ampere rating. Branch circuits shall 
be rated in accordance with the maximum allowable ampere 
rating or setting of the overcurrent protection device. The rat- 
ing for other than individual branch circuits shall be 15, 20, 30, 
40 and 50 amperes. Where conductors of higher ampacity are 
used, the ampere rating or setting of the specified over-current 
device shall determine the circuit rating. 

E3602.3 Fifteen- and 20-ampere branch circuits. A 15- or 

20-ampere branch circuit shall be permitted to supply lighting 
units, or other utilization equipment, or a combination of both. 
The rating of any one cord-and-plug-connected utihzation 
equipment not fastened in place shall not exceed 80 percent of | 
the branch-circuit ampere rating. The total rating of utilization 
equipment fastened in place, other than lighting fixtures, shall 
not exceed 50 percent of the branch-circuit ampere rating 
where lighting units, cord-and-plug-connected utilization 
equipment not fastened in place, or both, are also supplied. 

E3602.4 Thirty-ampere branch circuits. A 30-ampere 
branch circuit shall be permitted to supply fixed utilization 
equipment. A rating of any one cord-and-plug-connected utili- 
zation equipment shall not exceed 80 percent of the branch-cir- 
cuit ampere rating. 

E3602.5 Branch circuits serving multiple loads or outlets. 

General-purpose branch circuits shall supply lighting outlets, 
appliances, equipment or receptacle outlets, and combinations 
of such. The rating of a fastened-in-place appHance or equip- 
ment, where used in combination on the same branch circuit 
with light fixtures, receptacles, and/or other appliances or 
equipment not fastened in place, shall not exceed 50 percent of 
the branch-circuit rating. Multi-outlet branch circuits serving 
lighting or receptacles shall be limited to a maximum 
branch-circuit rating of 20 amperes. 

E3602.6 Branch circuits serving a single motor. Branch-cir- 
cuit conductors supplying a single motor shall have an 
ampacity not less than 125 percent of the motor full-load cur- 
rent rating. 

E3602.7 Branch circuits serving motor-operated and com- 
bination loads. For circuits supplying loads consisting of 
motor-operated utilization equipment that is fastened in place 
and that has a motor larger than Vg horsepower in combination 
with other loads, the total calculated load shall be based on 125 | 
percent of the largest motor load plus the sum of the other 
loads. 

E3602.8 Branch-circuit inductive lighting loads. For circuits 
supplying luminaires having ballasts, the calculated load shall | 
be based on the total ampere ratings of such units and not on the 
total watts of the lamps. 

E3602.9 Branch-circuit load for ranges and cooking appli- 
ances. It shall be permissible to calculate the branch-circuit I 



2006 INTERNATIONAL RESIDENTIAL CODE® 



491 



BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



load for one range in accordance with Table E3604.2(2). The 
branch-circuit load for one wall-mounted oven or one 
counter-mounted cooking unit shall be the nameplate rating of 
the appliance. The branch-circuit load for a counter-mounted 
cooking unit and not more than two wall-mounted ovens all 
supplied from a single branch circuit and located in the same 
room shall be calculated by adding the nameplate ratings of the 
individual appliances and treating the total as equivalent to one 
range. 

E3602.9.1 Minimum branch circuit for ranges. Ranges 
with a rating of 8.75 kVA or more shall be supplied by a 
branch circuit having a minimum rating of 40 amperes. 

E3602.10 Branch circuits serving heating loads. Electric 
space-heating and water-heating appliances shall be consid- 
ered continuous loads. Branch circuits supplying two or more 
outlets for fixed electric space-heating equipment shall be rated 
15, 20, 25 or 30 amperes. 

E3602.il Branch circuits for air-conditioning and heat 
pump equipment. The ampacity of the conductors supplying 
multimotor and combination load equipment shall not be less 
than the minimum circuit ampacity marked on the equipment. 
The branch-circuit overcurrent device rating shall be the size 
and type marked on the appliance and shall be listed for the spe- 
cific purpose. 

E3602.12 Branch circuits serving room air conditioners. A 

room air conditioner shall be considered as a single motor unit 
in determining its branch-circuit requirements where all the 
following conditions are met: 

1 . It is cord- and attachment plug-connected. 

2. The rating is not more than 40 amperes and 250 volts; 
single phase. 

3. Total rated-load current is shown on the room air-condi- 
tioner nameplate rather than individual motor currents. 

4. The rating of the branch-circuit short-circuit and 
ground-fault protective device does not exceed the 
ampacity of the branch-circuit conductors, or the rating 
of the branch-circuit conductors, or the rating of the 
receptacle, whichever is less. 

E3602.12.1 Where no other loads are supplied. The total 
marked rating of a cord- and attachment plug-connected 
room air conditioner shall not exceed 80 percent of the rat- 
ing of a branch circuit where no other appliances are also 
supplied. 

E3602.12.2 Where lighting units or other appliances are 
also supplied. The total marked rating of a cord- and attach- 
ment plug-connected room air conditioner shall not exceed 
50 percent of the rating of a branch circuit where lighting or 
other appliances are also supplied. Where the circuitry is 
interlocked to prevent simultaneous operation of the room 
air conditioner and energization of other outlets on the same 
branch circuit, a cord- and attachment-plug-connected 
room air conditioner shall not exceed 80 percent of the 
branch-circuit rating. 

E3602.13 Branch-circuit requirement — summary. The 

requirements for circuits having two or more outlets, or recep- 



tacles, other than the receptacle circuits of Section E3603.2, are 
summarized in Table E3602.13. Branch circuits in dwelling 
units shall supply only loads within that dwelling unit or loads 
associated only with that dwelling unit. Branch circuits 
required for the purpose of lighting, central alarm, signal, com- 
munications or other needs for public or common areas of a 
two-family dwelling shall not be supplied from equipment that 
supplies an individual dwelling unit. 

TABLE E3602.13 
BRANCH-CIRCUIT REQUIREMENTS— SUMMARY^" 





CIRCUIT FIATING 


15 amp 


20 amp 


30 amp 


Conductors: 

Minimum size (AWG) 
circuit conductors 


14 


12 


10 


Maximum overcurrent- 
protection device rating 
Ampere rating 


15 


20 


30 


Outlet devices: 

Lampholders permitted 
Receptacle rating (amperes) 


Any type 
15 maximum 


Any type 
15 or 20 


N/A 
30 


Maximum load (amperes) 


15 


20 


30 



a. These gages are for copper conductors. 

b. N/A means not allowed. 



SECTION E3603 
REQUIRED BRANCH CIRCUIITS 

E3603.1 Branch circuits for heating. Central heating equip- 
ment other than fixed electric space heating shall be supplied 
by an individual branch circuit. Permanently connected 
air-conditioning equipment, and auxiliary equipment directly 
associated with the central heating equipment such as pumps, 
motorized valves, humidifiers and electrostatic air cleaners, 
shall not be prohibited from connecting to the same branch cir- 
cuit as the central heating equipment. 

E3603.2 Kitchen and dining area receptacles. A minimum 
of two 20- ampere-rated branch circuits shall be provided to 
serve all wall and floor receptacle outlets located in the kitchen, 
pantry, breakfast area, dining area or similar area of a dwelling. 
The kitchen countertop receptacles shall be served by a mini- 
mum of two 20-ampere-rated branch circuits, either or both of 
which shall also be permitted to supply other receptacle outlets 
in the kitchen, pantry, breakfast and dining area including 
receptacle outlets for refrigeration appliances. 

Exception: The receptacle outlet for refrigeration appli- 
ances shall be permitted to be supplied from an individual 
branch circuit rated 15 amperes or greater. 

E3603.3 Laundry circuit. A minimum of one 20- 
ampere-rated branch circuit shall be provided for receptacles 
located in the laundry area and shall serve only receptacle out- 
lets located in the laundry area. ' 

E3603.4 Bathroom branch circuits. A minirnum of one 
20-ampere branch circuit shall be provided to supply bathroom 
receptacle outlet(s). Such circuits shall have no other outlets. 



492 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



Exception; Where the 20-ampere circuit suppHes a single 
bathroom, outlets for other equipment within the same bath- 
room shall be permitted to be supplied in accordance with 
Section E3602. 

E3603.5 Number of branch circuits. The minimum number 
of branch circuits shall be determined from the total calculated 
load and the size or rating of the circuits used. The number of 
circuits shall be sufficient to supply the load served. In no case 
shall the load on any circuit exceed the maximum specified by 
Section E3602. 

E3603.6 Branch-circuit load proportioning. Where the 
branch-circuit load is calculated on a volt-amperes- 
per-square-foot (m^) basis, the wiring system, up to and includ- 
ing the branch-circuit panelboard(s), shall have the capacity to 
serve not less than the calculated load. This load shall be evenly 
proportioned among multioutlet branch circuits within the 
panelboard(s). Branch-circuit overcurrent devices and circuits 
shall only be required to be installed to serve the connected 
load. 



SECTION E3604 
FEEDER REQUIREMENTS 

E3604.1 Conductor size. Feeder conductors that do not serve 
100 percent of the dwelling unit load and branch-circuit con- 
ductors shall be of a size sufficient to carry the load as deter- 
mined by this chapter. Feeder conductors shall not be required 
to be larger than the service-entrance conductors that supply 
the dwelling unit. The load for feeder conductors that serve as 
the main power feeder to a dwelling unit shall be determined as 
specified in Chapter 35 for services. 



E3604.2 Feeder loads. The minimum load in volt-amperes 
shall be calculated in accordance with the load calculation pro- | 
cedure prescribed in Table E3604.2(l). The associated table 
demand factors shall be applied to the actual load to determine 
the minimum load for feeders. 

E3604.3 Feeder neutral load. The feeder neutral load shall be 
the maximum unbalance of the load determined in accordance 
with this chapter. The maximum unbalanced load shall be the 
maximum net calculated load between the neutral and any one | 
ungrounded conductor. For a feeder or service supplying electric 
ranges, wall-mounted ovens, counter-mounted cooking units 
and electric dryers, the maximum unbalanced load shall be con- 
sidered as 70 percent of the load on the ungrounded conductors. 

E3604.4 Lighting and general use receptacle load. A unit 
load of not less than 3 volt-amperes shall constitute the mini- 
mum lighting and general use receptacle load for each square 
foot of floor area (33 VA for each square meter of floor area). 
The floor area for each floor shall be calculated from the out- I 
side dimensions of the building. The calculated floor area shall | 
not include open porches, garages, or unused or unfinished 
spaces not adaptable for future use. 

E3604.5 Ampacity and calculated loads. The calculated load | 
of a feeder shall be not less than the sum of the loads on the 
branch circuits suppUed, as determined by Section E3604, after 
any applicable demand factors permitted by Section E3604 
have been applied. 

Feeder conductors shall have sufficient ampacity to supply 
the load served. In no case shall the calculated load of a feeder | 
be less than the sum of the loads on the branch circuits supplied 
as determined by this chapter after any permitted demand fac- 
tors have been applied. ^ 



TABLE E3604.2(1) 
FEEDER LOAD CALCULATION 



LOAD CALCULATION PROCEDURE 



APPLIED DEMAND FACTOR 



Lighting and receptacles: A unit load of not less than 3 VA per square foot of total floor area 
shall constitute the lighting and 120- volt, 15- and 20-ampere general use receptacle load. 
1,500 VA shall be added for each 20-ampere branch circuit serving receptacles in the 
kitchen, dining room, pantry, breakfast area and laundry area. 



100 percent of first 3,000 VA or less and 35 
percent of that in excess of 3,000 VA. 



Plus 



Appliances and motors: The nameplate rating load of all fastened-in-place appliances other 
than dryers, ranges, air-conditioning and space-heating equipment. 



100 percent of load for three or less appliances. 
75 percent of load for four or more appliances. 



Pius 



Fixed motors: Full-load current of motors plus 25 percent of the full load current of the largest motor. 



Plus 



Electric clothes dryer: The dryer load shall be 5,000 VA for each dryer circuit or the nameplate rating load of each dryer, whichever is greater. 



Plus 



Cooking appliances: The nameplate rating of ranges, wall-mounted ovens, counter-mounted 
cooking units and other cooking appliances rated in excess of 1.75 kVA shall be summed. 



Demand factors shall be as allowed by Table 
E3604.2(2). 



Plus the largest of either the heating or cooling load 



Largest of the following two selections: 

1. 100 percent of the nameplate rating(s) of the air conditioning and cooling, including heat pump compressors. 

2. 100 percent of the fixed electric space heating. 



For SI: 1 square foot = 0.0929 m^. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



493 



BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



TABLE E3604.2(2) 

DEMAND LOADS FOR ELECTRIC RANGES, WALL-MOUNTED OVENS, COUNTER-MOUNTED 

COOKING UNITS AND OTHER COOKING APPLIANCES OVER I^A kVA RATING^'' 



NUMBER OF APPLIANCES 


MAXIMUM 

demand''^ 


DEMAND FACTORS (percent)^ 


Column A 

maximum 12 kVA 

rating 


Column B 

less than 3V2 kVA 

rating 


Column C 

3V2 to 8% kVA 

rating 


1 


8kVA 


80 


80 


2 


llkVA 


75 


65 



a. Column A shall be used in all cases except as provided for in Footnote d. 

b. For ranges all having the same rating and individually rated more than 12 kVA but not more than 27 kVA, the maximum demand in Column A shall be increased 5 
percent for each additional kVA of rating or major fraction thereof by which the rating of individual ranges exceeds 12 kVA. 

c. For ranges of unequal ratings and individually rated more than 8.75 kVA, but none exceeding 27 kVA, an average value of rating shall be computed by adding 
together the ratings of all ranges to obtain the total connected load (using 1 2 kVA for any ranges rated less than 12 kVA) and dividing by the total number of ranges; 
and then the maximum demand in Column A shall be increased 5 percent for each kVA or major fraction thereof by which this average value exceeds 1 2 kVA. 

d. Over 1 .75 kVA through 8.75 kVA. As an alternative to the method provided in Column A, the nameplate ratings of all ranges rated more than 1 .75 kVA but not more 
than 8.75 kVA shall be added and the sum shall be multiplied by the demand factor specified in Column B or C for the given number of appliances. 



SECTION E3605 

CONDUCTOR SIZING 

AND OVERCURRENT PROTECTION 

E3605.1 General. Ampacities for conductors shall be deter- 
mined based in accordance with Table E3605.1 and Sections 
E3605.2 and E3605.3. 

E3605.2 Correction factor for ambient temperatures. For 

ambient temperatures other than 30°C (86°F), multiply the 
allowable ampacities specified in Table E3 605.1 by the appro- 
priate correction factor shown in Table E3605.2. 

E3605.3 Adjustment factor for conductor proximity. 

Where the number of current-carrying conductors in a raceway 
or cable exceeds three, or where single conductors or 
multiconductor cables are stacked or bundled for distances 



greater than 24 inches (610 mm) without maintaining spacing 
and are not installed in raceways, the allowable ampacity of 
each conductor shall be reduced as shown in Table E3605.3. 

Exceptions: 

1 . Adjustment factors shall not apply to conductors in nip- 
ples having a length not exceeding 24 inches (610 mm). 

2. Adjustment factors shall not apply to underground 
conductors entering or leaving an outdoor trench if 
those conductors have physical protection in the form 
of rigid metal conduit, intermediate metal conduit, or 
rigid nonmetallic conduit having a length not exceed- 
ing 10 feet (3048 mm) and the number of conductors 
does not exceed four. 



TABLE E3605.1 
ALLOWABLE AMPACITIES 



CONDUCTOR 
SIZE 


CONDUCTOR TEMPERATURE RATING 


CONDUCTOR 
SIZE 


60°C 


75°C 


90°C 


60°C 


75°C 


90°C 


AWG 
kcmil 


Types 
TW, UF 


Types 

RHW, THHW, 

THW, THWN, USE, 

XHHW 


Types 

RHW-2, THHN, 

THHW, THW-2, 

THWN-2, XHHW, 

XHHW-2, USE-2 


Types 
TW, UF 


Types 

RHW, THHW, 

THW, THWN, USE, 

XHHW 


Types 

RHW-2, THHN, 

THHW, THW-2, 

THWN-2, XHHW, 

XHHW-2, USE-2 


AWG 
kcmll 


Copper 


Aluminum or copper-clad aluminum 


18 
16 
14 
12 
10 
8 


20 
25 
30 
40 


20 

25 
35 
50 


14 
18 

25 
30 
40 
55 


20 
25 
30 


20 
30 
40 




25 
35 
45 


12 
10 

8 


6 

4 
3 
2 
1 


55 
70 
85 
95 
110 


65 
85 
100 
115 
130 


75 
95 
110 
130 
150 


40 
55 
65 
75 
85 


50 
65 
75 
90 
100 


60 

75 
85 
100 
115 


6 

4 
3 

: 2 

! 1 


1/0 
2/0 
3/0 
4/0 


125 
145 
165 
195 


150 
175 
200 
230 


170 
195 

225 
260 


100 
115 
130 
150 


120 
135 
155 
180 


135 
150 

175 
205 


' 1/0 
2/0 

1 3/0 
4/0 



For SI: °C = [(°F)-32]/1.8. 



494 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



TABLE E3605.2 
AMBIENT TEMPERATURE CORRECTION FACTORS 



AMBIENT TEMP. 


FOR AMBIENT TEMPERATURES OTHER THAN 30°C (86°F), MULTIPLY THE ALLOWABLE AMPACITIES SPECIFIED 
IN TABLE E3605.1 BY THE APPROPRIATE FACTOR SHOWN BELOW 


AMBIENT TEMP. 
°F 


CONDUCTOR TEMPERATURE RATING 


60°C 


75°C 


90°C 


60°C 


75°C 


90°C 


Types 
TW, UF 


Types 

RHW, THHW, 

THW, THWN, USE, 

XHHW 


Types 

RHW-2, THHN, 

THHW, THW-2, 

THWN-2, XHHW, 

XHHW-2, USE-2 


Types 
TW, UF 


Types 

RHW, THHW, 

THW, THWN, USE, 

XHHW 


Types 

RHW-2, THHN, 

THHW, THW-2, 

THWN-2, XHHW, 

XHHW-2, USE-2 


Copper 


Aluminum or copper-clad aluminum 


21-25 


1.08 


1.05 


1.04 


1.08 


1.05 


1.04 


70-77 


26-30 


1.00 


1.00 


1.00 


1.00 


1.00 


1.00 


78-86 


31-35 


0.91 


0.94 


0.96 


0.91 


0.94 


0.96 


87-95 


36-40 


0.82 


0.88 


0.91 


0.82 


0.88 


0.91 


96-104 


41-45 


0.71 


0.82 


0.87 


0.71 


0.82 


0.87 


105-113 


46-50 


0.58 


0.75 


0.82 


0.58 


0.75 


0.82 


114-122 


51-55 


0.41 


0.67 


0.76 


0.41 


0.67 


0.76 


123-131 


56-60 





0.58 


0.71 





0.58 


0.71 


132-140 


61-70 





0.33 


0.58 





0.33 


0.58 


141-158 


71-80 


— 


— 


0.41 


— 


— 


0.41 


159-176 



For SI: °C = [(°F)-32]/1.8. 



3 . Adjustment factors shall not apply to type AC cable or 
to type MC cable without an overall outer jacket 
meeting all of the following conditions: 

3.1. Each cable has not more than three cur- 
rent-carrying conductors. 

3.2. The conductors are 12 AWG copper. 

3.3. Not more than 20 current-carrying conductors 
are bundled, stacked or supported on bridle 
rings. A 60 percent adjustment factor shall be 
applied where the current-carrying conduc- 
tors in such cables exceed 20 and the cables 
are stacked or bundled for distances greater 
than 24 inches (610 mm) without maintaining 
spacing. 

TABLE E3605.3 
CONDUCTOR PROXIMITY ADJUSTMENT FACTORS 



NUMBER OF CURRENT-CARRYING 
CONDUCTORS IN CABLE OR RACEWAY 


PERCENT OF VALUES 
IN TABLE E3605.1 


4-6 


80 


7-9 


70 


10-20 


50 


21-30 


45 


31-40 


40 


41 and above 


35 



E3605.4 Temperature limitations. The temperature rating 
associated with the ampacity of a conductor shall be so selected 
and coordinated to not exceed the lowest temperature rating of 
any connected termination, conductor or device. Conductors 
with temperature ratings higher than specified for terminations 
shall be permitted to be used for ampacity adjustment, correc- 



tion, or both. Except where the equipment is marked otherwise, 
conductor ampacities used in determining equipment termina- 
tion provisions shall be based on Table E3605.1 

E3605.4.1 Conductors rated 60°C. Except where the 
equipment is marked otherwise, termination provisions of 
equipment for circuits rated 100 amperes or less, or marked 
for 14 AWG through 1 AWG conductors, shall be used only 
for one of the following: 

1. Conductors rated 60°C (140°F); 

2. Conductors with higher temperature ratings, pro- 
vided that the ampacity of such conductors is deter- 
mined based on the 60°C (140°F) ampacity of the 
conductor size used; 

3. Conductors with higher temperature ratings where 
the equipment is listed and identified for use with 
such conductors; or 

4. For motors marked with design letters B, C, or D con- 
ductors having an insulation rating of 75 °C (167°F) 
or higher shall be permitted to be used provided that 
the ampacity of such conductors does not exceed the 
75°C (167°F) ampacity. 

E3605.4.2 Conductors rated 75°C. Termination provi- 
sions of equipment for circuits rated over 100 amperes, or 
marked for conductors larger than 1 AWG, shall be used 
only for: 

1. Conductors rated 75 °C (167°F). 

2. Conductors with higher temperature ratings provided 
that the ampacity of such conductors does not exceed 
the 75°C (167°F) ampacity of the conductor size 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



495 



BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



used, or provided that the equipment is Hsted and 
identified for use with such conductors. 

E3605,4.3 Separately installed pressure connectors. 

Separately installed pressure connectors shall be used with 
conductors at the ampacities not exceeding the ampacity at 
the listed and identified temperature rating of the connector. 

E3605.4.4 Conductors of Type NM cable. Conductors in 
NM cable assemblies shall be rated at 90°C (194°F). Types 
NM, NMC, and NMS cable identified by the markings 
NM-B, NMC-B, and NMS-B meet this requirement. The 
ampacity of Types NM, NMC, and NMS cable shall be at 
60°C (140°F) conductors and shall comply with Section 
E3605.1 and Table E3605.5.3. The 90°C (194°F) rating 
shall be permitted to be used for ampacity correction and 
adjustment purposes provided that the final corrected or 
adjusted ampacity does not exceed that for a 60°C (140°F) 
rated conductor. Where more than two NM cables contain- 
ing two or more current-carrying conductors are bundled 
together and pass through wood framing that is to be fire- or 
draft-stopped using thermal insulation or sealing foam, the 
allowable ampacity of each conductor shall be adjusted in 
accordance with Table E3605.3. 

E3605.5 Overcurrent protection required. All ungrounded 
branch-circuit and feeder conductors shall be protected against 
overcurrent by an overcurrent device installed at the point 
where the conductors receive their supply. Overcurrent devices 
shall not be connected in series with a grounded conductor. 
Overcurrent protection and allowable loads for branch circuits 
and feeders that do not serve as the main power feeder to the 
dwelling unit load shall be in accordance with this chapter. 

Branch-circuit conductors and equipment shall be protected 
by overcurrent protective devices having a rating or setting not 
exceeding the allowable ampacity specified in Table E3605.1 
and Sections E3605 .2, E3605 .3 and E3605 .4 except where oth- 
erwise permitted or required in Sections E3605.5.1 through 
E3605.5.3. 

E3605.5.1 Cords. Cords shall be protected in accordance 
with Section E3809.2. 

E3605.5.2 Overcurrent devices of the next higher rating. 

The next higher standard overcurrent device rating, above 
the ampacity of the conductors being protected, shall be per- 
mitted to be used, provided that all of the following condi- 
tions are met: 

1. The conductors being protected are not part of a 
multioutlet branch circuit supplying receptacles for 
cord- and plug-connected portable loads. 

2. The ampacity of conductors does not correspond with 
the standard ampere rating of a fuse or a circuit 
breaker without overload trip adjustments above its 
rating (but that shall be permitted to have other trip or 
rating adjustments). 

3. The next higher standard device rating does not 
exceed 400 amperes. 

E3605.5.3 Small conductors. Except as specifically per- 
mitted by Section E3605.5.4, the rating of overcurrent pro- 



tection devices shall not exceed the ratings shown in Table 
E3605.5.3 for the conductors specified therein. 

E3605.5.4 Air-conditioning and heat pump equipment. 

Air-conditioning and heat pump equipment circuit conduc- 
tors shall be permitted to be protected against overcurrent in 
accordance with Section E3602.il. 

E3605.6 Fuses and fixed trip circuit breakers. The standard 
ampere ratings for fuses and inverse time circuit breakers shall 
be considered 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 
110, 125, 150, 175, 200, 225, 250, 300, 350 and 400 amperes. 

TABLE E3605.5.3 
OVERCURRENT-PROTECTION RATING 



COPPER 


ALUMINUM OR COPPER-CLAD ALUMINUM 


Size 
(AWG) 


Maximum 

overcurrent- 

protection- 

device rating" 

(amps) 


Size 
(AWG) 


Maximum 

overcurrent- 

protection- 

device rating* 

(amps) 


14 


15 


12 


15 


12 


20 


10 


25 


10 


30 


8 


30 



a. The maximum overcurrent-protection-device rating shall not exceed the 
conductor allowable ampacity determined by the application of the correc- 
tion and adjustment factors in accordance with Sections E3605.2 and 
E3605.3. 

E3605.7 Location of overcurrent devices in or on premises. 

Overcurrent devices shall: 

1 . Be readily accessible. 

2. Not be located where they will be exposed to physical 
damage. 

3. Not be located where they will be in the vicinity of easily 
ignitible material such as in clothes closets. 

4. Not be located in bathrooms. 

5. Be installed so that the center of the grip of the operating 
handle of the switch or circuit breaker, when in its highest 
position, is not more than 6 feet 7 inches (2.0 m) above the 
floor or working platform. 

Exceptions: 

1. This section shall not apply to supplementary 
overcurrent protection that is integral to utilization 
equipment. 

2. Overcurrent devices installed adjacent to the utiliza- 
tion equipment that they supply shall be permitted to 
be accessible by portable means. 

E3605.8 Ready access for occupants. Each occupant shall 
have ready access to all overcurrent devices protecting the con- 
ductors supplying that occupancy. 

E3605.9 Enclosures for overcurrent devices, bvercurrent 
devices shall be enclosed in cabinets or cutout boxes except 
where an overcurrent device is part of an assembly that pro- 
vides equivalent protection. The operating handle of a circuit 
breaker shall be permitted to be accessible without opening a 
door or cover. 



496 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



BRANCH CIRCUIT AND FEEDER REQUIREMENTS 



SECTION E3606 
PANELBOARDS 

E3606.1 Panelboard rating. All panelboards shall have a rat- 
ing not less than that of the minimum service entrance or feeder 
I capacity required for the calculated load. 

E3606.2 Panelboard circuit identification. All circuits and 
circuit modifications shall be legibly identified as to their clear, 
evident, and specific purpose or use. The identification shall 
include sufficient detail to allow each circuit to be distin- 
guished from all others. The identification shall be included in 
a circuit directory located on the face of the panelboard enclo- 
sure or inside the panel door. 

E3606.3 Panelboard overcurrent protection. Panelboards 
shall be protected on the supply side by not more than two main 
circuit breakers or two sets of fuses having a combined rating 
not greater than that of the panelboard. 

Exception: Individual protection for a panelboard shall not 
be required if the panelboard feeder has overcurrent protec- 
tion not greater than the rating of the panelboard. 

E3606.4 Grounded conductor terminations. Each grounded 
conductor shall terminate within the panelboard on an individ- 
ual terminal that is not also used for another conductor, except 
that grounded conductors of circuits with parallel conductors 
shall be permitted to terminate on a single terminal where the 
terminal is identified for connection of more than one conduc- 
tor. 

E3606.5 Back-fed devices. Plug-in-type overcurrent protec- 
tion devices or plug-in-type main lug assemblies that are 
back-fed and used to terminate field-installed ungrounded sup- 
ply conductors shall be secured in place by an additional fas- 
tener that requires other than a pull to release the device from 
the mounting means on the panel. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



497 



498 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 37 

WIRING METHODS 



SECTION E3701 
GENERAL REQUIREMENTS 

E3701.1 Scope. This chapter covers the wiring methods for 
services, feeders and branch circuits for electrical power and 
distribution. 

E3701.2 Allowable wiring methods. The allowable wiring 
methods for electrical installations shall be those listed in Table 
E3701.2. Single conductors shall be used only where part of 
one of the recognized wiring methods listed in Table E3701.2. 
As used in this code, abbreviations of the wiring-method types 
shall be as indicated in Table E3701.2. 

TABLEE3701.2 
ALLOWABLE WIRING METHODS 



ALLOWABLE WIRING METHOD 


DESIGNATED ABBREVIATION 


Armored cable 


AC 


Electrical metallic tubing 


EMT 


Electrical nonmetallic tubing 


ENT 


Flexible metal conduit 


FMC 


Intermediate metal conduit 


IMC 


Liquidtight flexible conduit 


LFC 


Metal-clad cable 


MC 


Nonmetallic sheathed cable 


NM 


Rigid nonmetallic conduit 


RNC 


Rigid metallic conduit 


RMC 


Service entrance cable 


SE 


Surface raceways 


SR 


Underground feeder cable 


UF 


Underground service cable 


USE 



E3701.3 Circuit conductors. All conductors of a circuit, includ- 
ing equipment grounding conductors and bonding conductors, 
shall be contained in the same raceway, trench, cable or cord. 

E3701.4 Wiring method applications. Wiring methods shall 
be applied in accordance with Table E3701.4. 



SECTION E3702 
ABOVE-GROUND INSTALLATION REQUIREMENTS 

E3702.1 Installation and support requirements. Wiring 
methods shall be installed and supported in accordance with 
Table E3702.1. 

E3702.2 Cables in accessible attics. Cables in attics or roof 
spaces provided with access shall be installed as specified in 
Sections E3702.2.1 and E3702.2.2. 

E3702.2.1 Across structural members. Where run across 
the top of floor joists, or run within 7 feet (2134 mm) of floor 



or floor joists across the face of rafters or studding, in attics 
and roof spaces that are provided with access, the cable shall 
be protected by substantial guard strips that are at least as 
high as the cable. Where such spaces are not provided with 
access by permanent stairs or ladders, protection shall only 
be required within 6 feet (1829 mm) of the nearest edge of 
the attic entrance. 

E3702.2.2 Cable installed through or parallel to framing 
members. Where cables are installed through or parallel to 
the sides of rafters, studs or floor joists, guard strips and run- 
ning boards shall not be required, and the installation shall 
comply with Table E3702.1. 

E3702.3 Exposed cable. In exposed work, except as provided 
for in Sections E3702.2 and E3702.4, cable assemblies shall be 
installed as specified in Sections E3702.3.1 and E3702.3.2. 

E3702.3.1 Surface installation. Cables shall closely fol- 
low the surface of the building finish or running boards. 

E3702.3.2 Protection from physical damage. Where sub- 
ject to physical damage, cables shall be protected by rigid 
metal conduit, intermediate metal conduit, electrical metal- 
lic tubing. Schedule 80 PVC rigid nonmetallic conduit, or 
other approved means. Where passing through a floor, the 
cable shall be enclosed in rigid metal conduit, intermediate 
metal conduit, electrical metallic tubing, Schedule 80 PVC 
rigid nonmetallic conduit or other approved means extend- 
ing not less than 6 inches (152 mm) above the floor. 

E3702.3.3 Locations exposed to direct sunlight. Insulated 
conductors and cables used where exposed to direct rays of 
the sun shall be of a type listed for sunlight resistance, or of a 
type listed and marked "sunlight resistant," or shall be cov- 
ered with insulating material, such as tape or sleeving, that is 
listed or listed and marked as being "sunlight resistant." 

E3702.4 In unfinished basements. Where type SE or NM cable 
is run at angles with joists in unfinished basements, cable assem- 
blies containing two or more conductors of sizes 6 AWG and 
larger and assemblies containing three or more conductors of 
sizes 8 AWG and larger shall not require additional protection 
where attached directly to the bottom of the joists. Smaller 
cables shall be run either through bored holes in joists or on run- 
ning boards. NM cable used on a wall of an unfinished basement 
shall be permitted to be installed in a hsted conduit or tubing. 
Such conduit or tubing shall be provided with a nonmetallic 
bushing or adapter at the point the where cable enters the race- 
way. 

E3702.5 Bends. Bends shall be made so as not to damage the 
wiring method or reduce the internal diameter of raceways. 

For types NM and SE cable, bends shall be so made, and 
other handling shall be such that the cable will not be damaged 
and the radius of the curve of the inner edge of any bend shall be 
not less than five times the diameter of the cable. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



499 



WIRING METHODS 



TABLEE3701.4 
ALLOWABLE APPLICATIONS FOR WIRING METHODS^ 


, b, c, d, e, f, 


g,h,i 










ALLOWABLE APPLICATIONS 
(application allowed where marked with an "A") 


AC 


EMT 


ENT 


FWIC 


IMC 
RMC 
RNC 


LFC^ 


MC 


NM 


SR 


SE 


UF 


USE 


Services 





A 


Ah 


A' 


A 


A' 


A 








A 





A 


Feeders 


A 


A 


A 


A 


A 


A 


A 


A 


— 


Ab 


A 


A" 


Branch circuits 


A 


A 


A 


A 


A 


A 


A 


A 


A 


A^ 


A 


— 


Inside a building 


A 


A 


A 


A 


A 


A 


A 


A 


A 


A 


A 


— 


Wet locations exposed to sunlight 





A 


A" 


Ad 


A 


A 


A 








A 


A^ 


L A^ 


Damp locations 





A 


A 


Ad 


A 


A 


A 








A 


A 


A 


Embedded in noncinder concrete in dry 
location 


— 


A 


A 


— 


A 


— 


— 


— 


— 


— 


— 


— 


In noncinder concrete in contact with grade 





Af 


A 


— 


A' 


— 


— 


— 


— 





— 


— 


Embedded in plaster not exposed to dampness 


A 


A 


A 


A 


A 


A 


A 








A 


A 


— 


Embedded in masonry 





A 


A 


— 


A' 


A 


A 


— 


— 


— 


— 


— 


In masonry voids and cells exposed to 
dampness or below grade line 


— 


Af 


A 


A" 


Af 


A 


A 


— 


— 


A 


A 


— 


Fished in masonry voids 


A 








A 


— 


A 


A 


A 


— 


A 


A 


— 


In masonry voids and cells not exposed to 
dampness 


A 


A 


A 


A 


A 


A 


A 


A 


— 


A 


A 


— 


Run exposed 


A 


A 


A 


A 


A 


A 


A 


A 


A 


A 


A 


A 


Run exposed and subject to physical damage 





— 








AS 


— 


— 


— 


— 


— 


— 


— 


For direct burial 


— 


A' 


— 


^ 


Af 


A 


Af 


— 


— 


— 


,A 


A 



For SI: 1 foot = 304.8 mm. 

a. Liquid-tight flexible nonmetallic conduit without integral reinforcement within the conduit wall shall not exceed 6 feet in length. 

b. The grounded conductor shall be insulated except where used to supply other buildings on the same premises. Type USE cable shall not be used inside buildings. 

c. The grounded conductor shall be insulated. 

d. Conductors shall be a type approved for wet locations and the installation shall prevent water from entering other raceways. 

e. Shall be listed as "Sunlight Resistant." 

f. Metal raceways shall be protected from corrosion and approved for the application. 

g. RNC shall be Schedule 80. 

h. Shall be listed as "SunUght Resistant" where exposed to the direct rays of the sun. 
i. Conduit shall not exceed 6 feet in length. 



500 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WIRING METHODS 



TABLE E3702.1 
GENERAL INSTALLATION AND SUPPORT REQUIREMENTS FOR WIRING METHODS^"' ■=■^•"■''9' *'■'■'■'' 



INSTALLATION REQUIREMENTS 
(Requirement applicable only to wiring methods marked "A" ) 


AC 

MC 


EMT 
IMC 
RMC 


ENT 


FMC 
LFC 


NM 
UF 


RNC 


SE 


SR^ 


USE 


Where run parallel with the framing member or furring strip, 
the wiring shall be not less than 1 ^1^ inches from the edge of 
a furring strip or a framing member such as a joist, rafter or 
stud or shall be physically protected. 


A 


— 


A 


A 


A 


— 


A 


— 


— 


Bored holes in framing members for wiring shall be located 
not less than 1 V4 inches from the edge of the framing 
member or shall be protected with a minimum 0.0625-inch 
steel plate or sleeve, a listed steel plate or other physical 
protection. 


A^ 


— 


A'' 


Ak 


A*^ 


— 


A^ 


— 


— 


Where installed in grooves, to be covered by wallboard, 
siding, paneling, carpeting, or similar finish, wiring methods 
shall be protected by 0.0625-inch-thick steel plate, sleeve, or 
equivalent, a listed steel plate or by not less than 1 V4-inch 
free space for the full length of the groove in which the 
cable or raceway is installed. 


A 


— 


A 


A 


A 


— 


A 


A 


A 


Securely fastened bushings or grommets shall be provided 
to protect wiring run through openings in metal framing 
members. 


— 


— 


A 


— 


A 




A 


— 


— 


The maximum number of 90-degree bends shall not exceed 
four between junction boxes. 


— 


A 


A 


A 


— 


A 


— 


— 


— 


Bushings shall be provided where entering a box, fitting or 
enclosure unless the box or fitting is designed to afford 
equivalent protection. 


A 


A 


A 


A 


— 


A 


— 


A 


— 


Ends of raceways shall be reamed to remove rough edges. 


— 


A 


A 


A 


— 


A 


— 


A 




Maximum allowable on center support spacing for the 
wiring method in feet. 


4.5'^''^ 


10 


3" 


4.5b 


4.5' 


3^* 


2.5^ 


— 


2.5« 


Maximum support distance in inches from box or other 
terminations. 


ll^'f 


36 


36 


12b,g 


12'''' 


36 


12 


— 


12 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 d^ree = 0.009 rad. 

a. Installed in accordance with listing requirements. 

b. Supports not required in accessible ceiling spaces between light fixtures where lengths do not exceed 6 feet. 

c. Six feet for MC cable. 

d. Five feet for trade sizes greater than 1 inch. 

e. Two and one-half feet where used for service or outdoor feeder and 4.5 feet where used for branch circuit or indoor feeder. 

f. Twenty-four inches where flexibility is necessary. 

g. Thirty-six inches where flexibility is necessary, 
h. Within 8 inches of boxes without cable clamps, 
i. Flat cables shall not be stapled on edge. 

j. Bushings and grommets shall remain in place and shall be listed for the purpose of cable protection. 

k. See Sections R502.8 and R802.7 for additional limitations on the location of bored holes in horizontal framing members. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



501 



WIRING METHODS 



E3702.6 Raceways exposed to different temperatures. 

Where portions of a cable, raceway or sleeve are known to be 
subjected to different temperatures and where condensation is 
known to be a problem, as in cold storage areas of buildings or 
where passing from the interior to the exterior of a building, the 
raceway or sleeve shall be fdled with an approved material to 
prevent the circulation of warm air to a colder section of the 
raceway or sleeve. 



SECTION E3703 
UNDERGROUND INSTALLATION REQUIREMENTS 

E3703.1 Minimum cover requirements. Direct buried cable 
or raceways shall be installed in accordance with the minimum 
cover requirements of Table E3703.1. 

E3703.2 Warning ribbon. Underground service conductors 
that are not encased in concrete and that are buried 18 inches 
(457 mm) or more below grade shall have their location identi- 



fied by a warning ribbon that is placed in the trench not less 
than 12 inches (300 mm) above the underground installation. 

E3703.3 Protection from damage. Direct buried conductors 
and cables emerging from the ground shall be protected by 
enclosures or raceways extending from the Eninimum cover 
distance below grade required by Section E3703. 1 to a point at 
least 8 feet (2438 mm) above finished grade. In no case shall the 
protection be required to exceed 18 inches (457 mm) below fin- 
ished grade. Conductors entering a building shall be protected 
to the point of entrance. Where the enclosure or raceway is sub- 
ject to physical damage, the conductors shall be installed in 
rigid metal conduit, intermediate metal conduit, Schedule 80 
rigid nonmetallic conduit or the equivalent. 

E3703.4 Splices and taps. Direct buried conductors or cables 
shall be permitted to be spliced or tapped without the use of 
splice boxes. The splices or taps shall be made by approved 
methods with materials listed for the application. 





TABLE E3703.1 
MINIMUM COVER REQUIREMENTS, BURIAL IN INCHES^' 


b, c, d, e 




LOCATION OF WIRING 
METHOD OR CIRCUIT 


TYPE OF WIRING METHOD OR CIRCUIT 


1 

Direct burial cables or 

conductors 


2 

Rigid metal conduit or 

intermediate metal 

conduit 


3 
Nonmetallic raceways 
listed for direct burial 

without concrete 
encasement or other 
approved raceways 


4 

Residential branch 

circuits rated 120 volts 

or less with GFCI 

protection and 

maximum overcurrent 

protection of 20 

amperes 


5 

Circuits for control of 

irrigation and 

landscape lighting 

limited to not more 

than 30 volts and 

installed with type UF 

or in other identified 

cable or raceway 


All locations not specified 
below 


24 


6 


18 


12 


6 


In trench below 2-inch-thick 
concrete or equivalent 


18 


6 


12 


6 


6 


Under a building 


(In raceway only) 








(In raceway only) 


(In raceway only) 


Under minimum of 4-inch- 
thick concrete exterior slab 
with no vehicular traffic and 
the slab extending not less than 
6 inches beyond the 
underground installation 


18 


4 


4 


6 (Direct burial) 
4 (In raceway) 


6 (Direct burial) 
4 (In raceway) 


Under streets, highways, roads, 
alleys, driveways and parking 
lots 


24 


24 


24 


24 


24 


One- and two-family dwelling 
driveways and outdoor parking 
areas, and used only for 
dwelling-related purposes 


18 


18 


18 


12 


18 


In solid rock where covered by 
minimum of 2 inches concrete 
extending down to rock 


2 (In raceway only) 


2 


2 


2 (In raceway only) 


2 (In raceway only) 

i 



For SI: 1 inch = 25.4 mm. 

a. Raceways approved for burial only where encased concrete shall require concrete envelope not less than 2 inches thick. 

b. Lesser depths shall be permitted where cables and conductors rise for terminations or splices or where access is otherwise required. ' 

c. Where one of the wiring method types listed in columns 1 to 3 is combined with one of the circuit types in columns 4 and 5, the shallower depth of burial shall be 
permitted. 

d. Where solid rock prevents compliance with the cover depths specified in this table, the wiring shall be installed in metal or nonmetallic raceway permitted for 
direct burial. The raceways shall be covered by a minimum of 2 inches of concrete extending down to the rock. 

e. Cover is defined as the shortest distance in inches (millimeters) measured between a point on the top surface of any direct-buried conductor, cable, conduit or other 
raceway and the top surface of finished grade, concrete, or similar cover. 



502 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



WIRING METHODS 



E3703.5 Backfill. Backfill containing large rock, paving mate- 
rials, cinders, large or sharply angular substances, or corrosive 
material shall not be placed in an excavation where such mate- 
rials cause damage to raceways, cables or other substructures 
or prevent adequate compaction of fill or contribute to corro- 
sion of raceways, cables or other substructures. Where neces- 
sary to prevent physical damage to the raceway or cable, 
protection shall be provided in the form of granular or selected 
material, suitable boards, suitable sleeves or other approved 
means. 

E3703.6 Raceway seals. Conduits or raceways shall be sealed 
or plugged at either or both ends where moisture will enter and 
contact live parts. 

E3703.7 Bushing. A bushing, or terminal fitting, with an inte- 
gral bushed opening shall be installed on the end of a conduit or 
other raceway that terminates underground where the conduc- 
tors or cables emerge as a direct burial wiring method. A seal 
incorporating the physical protection characteristics of a bush- 
ing shall be considered equivalent to a bushing. 

E3703.8 Single conductors. All conductors of the same circuit 
and, where present, the grounded conductor and all equipment 
grounding conductors shall be installed in the same raceway or 
shall be installed in close proximity in the same trench. 

Exception: Where conductors are installed in parallel in 
raceways, each raceway shall contain all conductors of the 
same circuit including grounding conductors. 

E3703.9 Ground movement. Where direct buried conductors, 
raceways or cables are subject to movement by settlement or 
frost, direct buried conductors, raceways or cables shall be 
arranged to prevent damage to the enclosed conductors or to 
equipment connected to the raceways. 



2006 INTERNATIONAL RESIDENTIAL CODE® 503 



504 2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 38 

POWER AND LIGHTING DISTRIBUTION 



SECTION E3801 
RECEPTACLE OUTLETS 

E3801.1 General. Outlets for receptacles rated at 125 volts, 15- 
and 20-amperes shall be provided in accordance with Sections 
E3801.2 through E3801.1 1. Receptacle outlets required by this 
section shall be in addition to any receptacle that is part of a 
luminaire or appliance, that is located within cabinets or cup- 
boards, or that is located over 5 .5 feet ( 1 676 mm) above the floor. 

Permanently installed electric baseboard heaters equipped 
with factory-installed receptacle oudets, or outlets provided as 
a separate assembly by the baseboard manufacturer shall be 
permitted as the required outlet or outlets for the wall space uti- 
lized by such permanently installed heaters. Such receptacle 
outlets shall not be connected to the heater circuits. 

E3801.2 Convenience receptacle distribution. In every 
kitchen, family room, dining room, living room, parlor, library, 
den, sun room, bedroom, recreation room, or similar room or 
area of dwelling units, receptacle outlets shall be installed in 
accordance with the general provisions specified in Sections 
E3801.2.1 through E3801. 2.3 (see Figure E3 80 1.2). 

E3801.2.1 Spacing. Receptacles shall be installed so that no 
point measured horizontally along the floor line in any wall 
space is more than 6 feet (1829 mm), from a receptacle out- 
let. 



1 .^=. 



2' 



6' 



12' 



p c 



FIXED PANEL 




FLOOR RECEPTACLE 



AJ 



6" 



12' 



-12'- 



-6'- 



For SI: 1 foot = 304.8 mm. 



FIGURE E3801. 2 
GENERAL USE RECEPTACLE DISTRIBUTION 



E3801.2.2 Wall space. As used in this section, a wall space 
shall include the following: 

1. Any space that is 2 feet (610 mm) or more in width, 
(including space measured around comers), and that 
is unbroken along the floor hne by doorways, fire- 
places, and similar openings. 

2. The space occupied by fixed panels in exterior walls, 
excluding sliding panels. 

3. The space created by fixed room dividers such as rail- 
ings and freestanding bar- type counters. 

E3801.2.3 Floor receptacles. Receptacle outlets in floors 
shall not be counted as part of the required number of recep- 
tacle outlets except where located within 18 inches (457 
mm) of the wall. 

E3801.3 Small appliance receptacles. In the kitchen, pantry, 
breakfast room, dining room, or similar area of a dwelling unit, 
the two or more 20-ampere small-appliance branch circuits 
required by Section E3603.2, shall serve all wall and floor 
receptacle outlets covered by Sections E3801.2 and E3801.4 
and those receptacle outlets provided for refrigeration appli- 
ances. 

Exceptions: 

1. In addition to the required receptacles specified by 
Sections E3801.1 and E3801.2, switched receptacles 
supplied from a general-purpose branch circuit as 
defined in Section E3803.2, Exception 1 shall be per- 
mitted. 

2. The receptacle outlet for refrigeration appliances 
shall be permitted to be supplied from an individual 
branch circuit rated at 15 amperes or greater. 

E3801.3.1 Other outlets prohibited. The two or more 
small-appliance branch circuits specified in Section E3801.3 
shall serve no other outlets. 

Exceptions: 

1 . A receptacle installed solely for the electrical sup- 
ply to and support of an electric clock in any of the 
rooms specified in Section E3801.3. 

2. Receptacles installed to provide power for supple- 
mental equipment and lighting on gas-fired 
ranges, ovens, and counter-mounted cooking 
units. 

E3801.3.2 Limitations. Receptacles installed in a kitchen 
to serve countertop surfaces shall be supplied by not less 
than two small-appliance branch circuits, either or both of 
which shall also be permitted to supply receptacle outlets in 
the same kitchen and in other rooms specified in Section 
E3801.3. Additional small-appUance branch circuits shall 
be permitted to supply receptacle outlets in the kitchen and 
other rooms specified in Section E3801.3. A small-appli- 
ance branch circuit shall not serve more than one kitchen. 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



505 



POWER AND LIGHTING DISTRIBUTION 



E3801.4 Countertop receptacles. In kitchens and dining 
rooms of dwelling units, receptacle outlets for counter spaces 
shall be installed in accordance with Sections E3801.4.1 
through E3801.4.5 (see Figure E3801.4). 




For SI: 1 foot = 304.8 mm. 



FIGURE E3801. 4 
COUNTERTOP RECEPTACLES 



E3801.4.1 Wall counter space. A receptacle outlet shall be 
installed at each wall counter space 12 inches (305 mm) or 
wider. Receptacle outlets shall be installed so that no point 
along the wall line is more than 24 inches (610 mm), mea- 
sured horizontally from a receptacle outlet in that space. 

Exception: Receptacle outlets shall not be required on a 
wall directly behind a range or sink in the installation 
described in Figure E380 1.4.1. 

E3801.4.2 Island counter spaces. At least one receptacle out- 
let shall be installed at each island counter space with a long 
dimension of 24 inches (610 mm) or greater and a short dimen- 
sion of 12 inches (305 mm) or greater. Where a rangetop or 
sink is installed in an island counter and the width of the coun- 
ter behind the rangetop or sink is less than 1 2 inches (300 mm), 
the rangetop or sink has divided the island into two separate 
countertop spaces as defined in Section E380 1.4.4. 

E3801.4.3 Peninsular counter space. At least one recepta- 
cle outlet shall be installed at each peninsular counter space 
with a long dimension of 24 inches (610 mm) or greater and 
a short dimension of 12 inches (305 mm) or greater. A pen- 
insular countertop is measured from the connecting edge. 



*- Outlet within 
24 in. 




Outlet not required 
ifX< 12 in. 




"^ 


Outlet within -► 
24 in. 




X 

























Sink or range extending from face of counter 



Outlets not 
ifX 



Outlet within 24 in. 




Sinl< or range mounted in corner 

For SI: 1 inch = 25.4 mm. 

FIGURE E3801. 4.1 
DETERMINATION OF AREA BEHIND SINK OR RANGE 

E3801.4.4 Separate spaces. Countertop spaces separated 
by range tops, refrigerators, or sinks shall be considered as 
separate countertop spaces in applying the requirements of 
Sections E3801.4.1, E3801.4.2 and E3801.4.3. 

E3801.4.5 Receptacle outlet location. Receptacle outlets 
shall be located not more than 20 inches (508 mm) above the 
countertop. Receptacle outlets shall not be installed in a 
face-up position in the work surfaces or countertops. Recep- 
tacle outlets rendered not readily accessible by appliances 
fastened in place, appliance garages, sinks or rangetops as 
addressed in the exception to Section E3801.4.1, or appli- 
ances occupying dedicated space shall not be considered as 
these required outlets. 

Exception: Receptacle outlets shall be permitted to be 
mounted not more than 12 inches (305 mm) below the 
countertop in construction designed for the physically 
impaired and for island and peninsular countertops 
where the countertop is flat across its entire surface and 
there are no means to mount a receptacle within 20 
inches (457 mm) above the countertop, such as in an 
overhead cabinet. Receptacles mounted below the 
countertop in accordance with this exception shall not be 
located where the countertop extends more than 6 inches 
(152 mm) beyond its support base. 



506 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



POWER AND LIGHTING DISTRIBUTION 



E3801.5 Appliance outlets. Appliance receptacle outlets 
installed for specific appliances, such as laundry equipment, 
shall be installed within 6 feet (1829 mm) of the intended loca- 
tion of the appliance. 

E3801.6 Bathroom. At least one wall receptacle outlet shall be 
installed in bathrooms and such outlet shall be located within 
36 inches (914 mm) of the outside edge of each lavatory basin. 
The receptacle outlet shall be located on a wall that is adjacent 
to the lavatory basin location. 

Receptacle outlets shall not be installed in a face-up position 
in the work surfaces or countertops in a bathroom basin location. 

Exception: The receptacle shall not be required to be 
mounted on the wall or partition where it is installed on the 
side or face of the basin cabinet not more than 12 inches (300 
mm) below the countertop. 

E3801.7 Outdoor outlets. At least one receptacle outlet acces- 
sible at grade level and not more than 6 feet, 6 inches (1981 
mm) above grade, shall be installed outdoors at the front and 
back of each dwelling unit having direct access to grade. 

E3801.8 Laundry areas. At least one receptacle outlet shall be 
installed to serve laundry appliances. 

E3801.9 Basements and garages. At least one receptacle out- 
let, in addition to any provided for laundry equipment, shall be 
installed in each basement and in each attached garage, and in 
each detached garage that is provided with electrical power. 
Where a portion of the basement is finished into one or more 
habitable room(s), each separate unfinished portion shall have 
a receptacle outlet installed in accordance with this section. 

E3801.10 Hallways. Hallways of 10 feet (3048 mm) or more 
in length shall have at least one receptacle outlet. The hall 
length shall be considered the length measured along the cen- 
terline of the hall without passing through a doorway. 

E3801.il HVAC outlet. A 125-volt, single-phase, 15- or 20- 
ampere-rated receptacle outlet shall be installed at an accessi- 
ble location for the servicing of heating, air-conditioning and 
refrigeration equipment. The receptacle shall be located on the 
same level and within 25 feet (7620 mm) of the heating, 
air-conditioning and refrigeration equipment. The receptacle 
outlet shall not be connected to the load side of the HVAC 
equipment disconnecting means. 

Exception: A receptacle outlet shall not be required for the 
servicing of evaporative coolers. 



SECTION E3802 

GROUND-FAULT AND ARC-FAULT 

CIRCUIT-INTERRUPTER PROTECTION 

E3802.1 Bathroom receptacles. All 125-volt, single-phase, 
15- and 20-ampere receptacles installed in bathrooms shall 
have ground-fault circuit-interrupter protection for personnel. 

E3802.2 Garage and accessory building receptacles. All 

125-volt, single-phase, 15- or 20-ampere receptacles installed in 
garages and grade-level portions of unfinished accessory build- 
ings used for storage or work areas shall have ground-fault cir- 
cuit-interrupter protection for personnel (see Section E3802.1 1). 



Exceptions: 

1 . Receptacles that are not readily accessible. 

2. A single receptacle or a duplex receptacle for two apph- 
ances located within dedicated space for each appliance 
that in normal use is not easily moved from one place to 
another, and that is cord- and plug-connected. 

E3802.3 Outdoor receptacles. All 125-volt, single-phase, 15- 
and 20-ampere receptacles installed outdoors shall have 
ground-fault circuit-interrupter protection for personnel. 

Exception: Receptacles as covered in Section E4001.7. 

E3802.4 Crawl space receptacles. Where a crawl space is at 
or below grade level, all 125-volt, single-phase, 15- and 20- 
ampere receptacles installed in such spaces shall have 
ground-fault circuit-interrupter protection for personnel. 

E3802.5 Unfinished basement receptacles. All 125-volt, sin- 
gle-phase, 15- and 20-ampere receptacles installed in unfin- 
ished basements shall have ground-fault circuit-interrupter 
protection for personnel. For purposes of this section, unfin- 
ished basements are defined as portions or areas of the base- 
ment not intended as habitable rooms and limited to storage 
areas, work areas, and the like (see Section E3802.1 1). 

Exceptions: 

1 . Receptacles that are not readily accessible. 

2. A single receptacle or duplex receptacle for two appli- 
ances located within dedicated space for each appli- 
ance that in normal use is not easily moved from one 
place to another, and that is cord- and plug-connected. 

3. A receptacle supplying only a permanently installed 
fire alarm or burglar alarm system. 

E3802.6 Kitchen receptacles. All 125-volt, single-phase, 15- 
and 20-ampere receptacles that serve countertop surfaces shall 
have ground-fault circuit-interrupter protection for personnel. 

E3802.7 Laundry, utility, and bar sink receptacles. All 

125-volt, single-phase, 15- and 20-ampere receptacles that are 
located within 6 feet ( 1 829 mm) of the outside edge of a laundry, I 
utility or wet bar sink shall have ground- fault circuit-interrupter | 
protection for personnel. Receptacle outiets shall not be installed 
in a face-up position in the work surfaces or countertops. 

E3802.8 Boathouse receptacles. All 125-volt, single-phase, 
15- or 20-ampere receptacles installed in boathouses used for 
storage or work areas shall have ground-fault circuit-inter- 
rupter protection for personnel. 

E3802.9 Boat hoists. Ground-fault circuit-interrupter protec- I 
tion for personnel shall be provided for outlets that supply boat I 
hoists supplied by 125-volt, 15- and 20-ampere branch circuits. | 

E3802.10 Electrically heated floors. Ground-fault cir- 
cuit-interrupter protection for personnel shall be provided for 
electrically heated floors in bathrooms, and in hydromassage 
bathtub, spa and hot tub locations. 

E3802.il Exempt receptacles. Receptacles installed under 
exceptions to Sections E3802.2 and E3802.5 shall not be con- 
sidered as meeting the requirements of Section E3801.9. 

E3802.12 Arc-fault protection of bedroom outlets. All 

branch circuits that supply 120-volt, single-phase, 15- and 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



507 



POWER AND LIGHTING DISTRIBUTION 



20-ampere outlets installed in bedrooms shall be protected by a 
combination type or branch/feeder type arc-fault circuit inter- 
rupter installed to provide protection of the entire branch cir- 
cuit. Effective January 1, 2008, such arc-fault circuit 
interrupter devices shall be combination type. 

Exception: The location of the arc-fault circuit interrupter 
shall be permitted to be at other than the origination of the 
branch circuit provided that: 

1 . The arc-fault circuit interrupter is installed within 6 
feet (1 .8 m) of the branch circuit overcurrent device as 
measured along the branch circuit conductors and 

2. The circuit conductors between the branch circuit 
overcurrent device and the arc-fault circuit interrupter 
are installed in a metal raceway or a cable with a 
metallic sheath. 



SECTION E3803 
LIGHTING OUTLETS 

E3803.1 GeneraL Lighting outlets shall be provided in accor- 
dance with Sections E3803.2 through E3803.4. 

E3803.2 Habitable rooms. At least one wall switch-controlled 
lighting outlet shall be installed in every habitable room and 
bathroom. 

Exceptions: 

1. In other than kitchens and bathrooms, one or more 
receptacles controlled by a wall switch shall be con- 
sidered equivalent to the required lighting outlet. 

2. Lighting outlets shall be permitted to be controlled by 
occupancy sensors that are in addition to wall 
switches, or that are located at a customary wall 
switch location and equipped with a manual override 
that will allow the sensor to function as a wall switch. 

E3803.3 Additional locations. At least one wall-switch-con- 
trolled Ughting outlet shall be installed in hallways, stairways, 
attached garages, and detached garages with electric power. At 
least one wall-switch-controlled lighting outlet shall be installed 
to provide illumination on the exterior side of each outdoor 
egress door having grade level access, including outdoor egress 
doors for attached garages and detached garages with electric 
power. A vehicle door in a garage shall not be considered as an 
outdoor egress door. Where one or more lighting outlets are 
installed for interior stairways, there shall be a wall switch at 
each floor level and landing level that includes an entryway to 
control the lighting outlets where the stairway between floor lev- 
els has six or more risers. 

Exception: In hallways, stairways, and at outdoor egress 
doors, remote, central, or automatic control of lighting shall 
be permitted. 

E3803.4 Storage or equipment spaces. In attics, under-floor 
spaces, utility rooms and basements, at least one lighting outlet 
shall be installed where these spaces are used for storage or 
contain equipment requiring servicing. Such lighting outlet 
shall be controlled by a wall switch or shall have an integral 
switch. At least one point of control shall be at the usual point 



of entry to these spaces. The lighting outlet shall be provided at 
or near the equipment requiring servicing. 

SECTION E3804 
GENERAL INSTALLATION REQUIREMENTS 

E3804.1 Electrical continuity of metal raceways and enclo- 
sures. Metal raceways, cable armor and other metal enclosures 
for conductors shall be mechanically joined together into a 
continuous electric conductor and shall be connected to all 
boxes, fittings and cabinets so as to provide effective electrical 
continuity. Raceways and cable assemblies shall be mechani- 
cally secured to boxes, fittings cabinets and other enclosures. 

Exception: Short sections of raceway used to provide cable 
assemblies with support or protection against physical damage. 

E3804.2 Mechanical continuity — raceways and cables. 

Metal or nonmetallic raceways, cable armors and cable sheaths 
shall be continuous between cabinets, boxes, fittings or other 
enclosures or outlets. 

Exception: Short sections of raceway used to provide cable 
assemblies with support or protection against physical dam- 
age. 

E3804.3 Securing and supporting. Raceways, cable assemblies, 
boxes, cabinets and fittings shall be securely fastened in place. 

E3804.3.1 Prohibited means of support,, Cable wiring 
methods shall not be used as a means of support for other 
cables, raceways and nonelectrical equipment. 

E3804.4 Raceways as means of support. Raceways shall be 
used as a means of support for other raceways, cables or 
nonelectric equipment only under the following conditions: 

1 . Where the raceway or means of support is identified for 
the purpose; or 

2. Where the raceway contains power supply conductors 
for electrically controlled equipment and is used to sup- 
port Class 2 circuit conductors or cables that are solely 
for the purpose of connection to the control circuits of the 
equipment served by such raceway; or 

3. Where the raceway is used to support boxes or conduit 
bodies in accordance with Sections E3806.8.4 and 
E3806.8.5. 

E3804.5 Raceway installations. Raceways shall be installed 
complete between outlet, junction or splicing points prior to the 
installation of conductors. 

Exception: Short sections of raceways used to contain con- 
ductors or cable assemblies for protection from physical 
damage shall not be required to be installed complete 
between outiet, junction, or splicing points. 

E3804.6 Conduit and tubing fill. The maximum number of 
conductors installed in conduit or tubing shall be in accordance 
with Tables E3 804.6(1) through E3 804.6(10). \ 

E3804.7 Air handling — stud cavity and joist spaces. Where 
wiring methods having a nonmetallic covering pass through 
istud cavities and joist spaces used for air handling, such wiring 
shall pass through such spaces perpendicular to the long 
dimension of the spaces. 



508 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(1) 
MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING (EMT)^ 



' 








TRADE SIZES 








CONDUCTOR 






(inches) 


















TYPE LETTERS 


SIZE AWG/kcmil 


% 


% 


1 


1V4 


1% 


2 


RHW, RHW-2 


14 

12 


4 
3 


7 
6 


11 
9 


20 
17 


27 
23 


46 
38 




10 


2 


5 


8 


13 


18 


30 




8 




2 


4 


7 


9 


16 




6 




1 


3 


5 


8 


13 




4 




1 


2 


4 


6 


10 




3 




1 


1 


4 


5 


9 




2 




1 


1 


3 


4 


7 




1 





1 


1 


1 


3 


5 




1/0 





1 


1 


1 


2 


4 




2/0 





1 


1 


1 


2 


4 




3/0 








1 


1 


1 


3 




4/0 








1 


1 


1 


3 


TW 


14 


8 


15 


25 


43 


58 


96 




12 


6 


11 


19 


33 


45 


74 




10 


5 


8 


14 


24 


33 


55 




8 


2 


5 


8 


13 


18 


30 


RHw^ RHw-2^ 


14 


6 


10 


16 


28 


39 


64 


THHW, THW, 


12 


4 


8 


13 


23 


31 


51 


THW-2 


10 


3 


6 


10 


18 


24 


40 




8 


1 


4 


6 


10 


14 


24 


RHw^ RHw-2^ 


6 




3 


4 


8 


11 


18 


TW, THW, 


4 




1 


3 


6 


8 


13 


THHW, THW-2 


3 




1 


3 


5 


7 


12 




2 




1 


2 


4 


6 


10 




1 




1 




3 


4 


7 




1/0 





1 




2 


3 


6 




2/0 





1 




1 


3 


5 




3/0 





1 




1 


2 


4 




4/0 










1 


1 


3 


THHN, THWN, 


14 


12 


22 


35 


61 


84 


138 


THWN-2 


12 


9 


16 


26 


45 


61 


101 




10 


5 


10 


16 


28 


38 


63 




8 


3 


6 


9 


16 


22 


36 




6 


2 


4 


7 


12 


16 


26 




4 




2 


4 


7 


10 


16 




3 




1 


3 


6 


8 


13 




2 




1 


3 


5 


7 


11 




1 




1 


1 


4 


5 


8 




1/0 




1 


1 


3 


4 


7 




2/0 





1 


1 


2 


3 


6 




3/0 





1 


1 


1 


3 


5 




4/0 





1 


1 


1 


2 


4 


XHHW, XHHW-2 


14 


8 


15 


25 


43 


58 


96 




12 


6 


11 


19 


33 


45 


74 




10 


5 


8 


14 


24 


33 


55 




8 


2 


5 


8 


13 


18 


30 




6 




3 


6 


10 


14 


22 




4 




2 


4 


7 


10 


16 




3 






3 


6 


8 


14 




2 






3 


5 


7 


11 




1 






1 


4 


5 


8 




1/0 








3 


4 


7 




2/0 









2 


3 


6 




3/0 







1 


1 


3 


5 




4/0 







1 


1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



509 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(2) 
MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL NONMETALLIC TUBING (ENT)^ 











TRADE SIZES 








CONDUCTOR 
SIZE AWG/kcmil 






(inches) 






TYPE LETTERS 


\ 


% 


1 


1V4 


1V2 


2 


RHW, RHW-2 


14 


3 


6 


10 


19 


26 


43 




12 


2 


5 


9 


16 


22 


36 




10 




4 


7 


13 


17 


29 




8 






3 


6 


9 


15 




6 






3 


5 


7 


12 




4 






2 


4 


6 


9 




3 






1 


3 


5 


8 




2 







1 


3 


4 


7 




1 







1 


1 


3 


5 




1/0 








1 


1 


2 


4 




2/0 








1 


1 


1 


3 




3/0 








1 


1 


1 


3 




4/0 








1 


1 


1 


2 


TW 


14 


7 


13 


22 


40 


55 


92 




12 


5 


10 


17 


31 


42 


71 




10 


4 


7 


13 


23 


32 


52 




8 


1 


4 


7 


13 


17 


29 


RHW^ RHW-2% 


14 


4 


8 


15 


27 


37 


61 


THHW, THW, 


12 


3 


7 


12 


21 


29 


49 


THW-2 


10 


3 


5 


9 


17 


23 


38 




8 


1 


3 


5 


10 


14 


23 


RHW^ RHW-2^ 


6 


1 


2 


4 


7 


10 


17 


TW, THW, 


4 


1 


1 


3 


5 


8 


13 


THHW, THW-2 


3 


1 


1 


2 


5 


7 


11 




2 


1 


1 


2 


4 


6 


9 




1 





1 




3 


4 


6 




1/0 





1 




2 


3 


5 




2/0 





1 




1 


3 


5 




3/0 










1 


2 


4 




4/0 










1 


1 


3 


THHN, THWN, 


14 


10 


18 


32 


58 


80 


132 


THWN-2 


12 


7 


13 


23 


42 


58 


96 




10 


4 


8 


15 


26 


36 


60 




8 


2 


5 


8 


15 


21 


35 




6 




3 


6 


11 


15 


25 




4 




1 


4 


7 


9 


15 




3 




1 


3 


5 


8 


13 




2 




,1 


2 


5 


6 


11 




1 




1 


1 


3 


5 


8 




1/0 





1 


1 


3 


4 


7 




2/0 





1 


1 


2 


3 


5 




3/0 





1 


1 


1 


3 


4 




4/0 








1 


1 


2 


4 


XHHW, XHHW-2 


14 


7 


13 


22 


40 


55 


92 




12 


5 


10 


17 


31 


42 


71 




10 


4 


7 


13 


23 


32 


52 




8 




4 


7 


13 


17 


1 29 




6 




3 


5 


9 


13 


21 




4 




1 


4 


7 


9 


: 15 




3 




1 


3 


6 


8 


13 




2 




1 


2 


5 


6 


11 




1 




1 




3 


5 


8 




1/0 





1 




3 


4 


7 




2/0 





1 




2 


3 


6 




3/0 





1 




1 


3 


5 




4/0 










1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



510 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(3) 
MAXIMUM NUMBER OF CONDUCTORS IN FLEXIBLE METALLIC CONDUIT (FMC)' 



TYPE LETTERS 


CONDUCTOR 
SIZE AWG/kcmil 


TRADE SIZES 
(inches) 


% 


% 


1 


1V4 


1% 


2 


RHW, RHW-2 


14 
12 


4 
3 


1 

6 


11 
9 


17 
14 


25 
21 


44 

37 




10 


3 


5 


7 


11 


17 


30 




8 




2 


4 


6 


9 


15 




6 




1 


3 


5 


7 


12 




4 




1 


2 


4 


5 


10 




3 




1 


1 


3 


5 


7 




2 




1 


1 


3 


4 


7 




1 





1 


1 


1 


2 


5 




1/0 





1 


1 


1 


2 


4 




2/0 





1 


1 


1 


1 


3 




3/0 








1 


1 


1 


3 


TW 


14 


9 


15 


23 


36 


53 


94 




12 


7 


11 


18 


28 


41 


72 




10 


5 


8 


13 


21 


30 


54 




8 


3 


5 


7 


11 


17 


30 


RHW% RHW-2^ 


14 


6 


10 


15 


24 


35 


62 


THHW, THW, 
THW-2 


12 
10 


5 
4 


8 
6 


12 
10 


19 
15 


28 

22 


50 
39 




8 


1 


4 


6 


9 


13 


23 


RHW^ RHW-2% 


6 




3 


4 


7 


10 


18 


TW, THW, 
THHW, THW-2 


4 
3 

2 


^ 




3 
3 

2 


5 
4 
4 


7 
6 

5 


13 
11 
10 




1 








2 


4 


7 




1/0 









1 


3 


6 




2/0 









1 


3 


5 




3/0 









1 


2 


4 




4/0 










1 


1 


3 




4/0 










1 


1 


2 


THHN, THWN, 
THWN-2 


14 
12 


13 
9 


22 
16 


33 
24 


52 
38 


76 
56 


134 
98 




10 


6 


10 


15 


24 


35 


62 




8 


3 


6 


9 


14 


20 


35 




6 


2 


4 


6 


10 


14 


25 




4 




2 


4 


6 


9 


16 




3 




1 


3 


5 


7 


13 




2 




1 


3 


4 


6 


11 




1 




1 


1 


3 


4 


8 




1/0 




1 


1 


2 


4 


7 




2/0 





1 


1 


1 


3 


6 




3/0 





1 


1 


1 


2 


5 




4/0 





1 


1 


1 


1 


4 


XHHW, XHHW-2 


14 
12 


9 

7 


15 
11 


23 
18 


36 

28 


53 
41 


94 

72 




10 


5 


8 


13 


21 


30 


54 




8 


3 


5 


7 


11 


17 


30 




6 




3 


5 


8 


12 


22 




4 




2 


4 


6 


9 


16 




3 






3 


5 


7 


13 




2 






3 


4 


6 


11 




1 








3 


5 


8 




1/0 








2 


4 


7 




2/0 









2 


3 


6 




3/0 









1 


3 


5 




4/0 









1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



511 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(4) 
MAXIMUM NUMBER OF CONDUCTORS IN INTERMEDIATE METALLIC CONDUIT (IMCf 











TRADE SIZES 








CONDUCTOR 
SIZE AWG/kcmil 






(inches) 






TYPE LETTERS 


\ 


% 


1 


1V4 


1V, 


2 


RHW, RHW-2 


14 


4 


8 


13 


22 


30 


49 




12 


4 


6 


11 


18 


25 


41 




10 


3 


5 


8 


15 


20 


33 




8 




3 


4 


8 


10 


17 




6 




1 


3 


6 


8 


14 




4 




1 


3 


5 


6 


11 




3 




1 


2 


4 


6 


9 




2 




1 


1 


3 


5 


8 




1 





1 


1 


2 


3 


5 




1/0 





1 


1 


1 


3 


4 




2/0 





1 


1 


1 


2 


4 




3/0 








1 


1 


1 


3 




4/0 








1 


1 


1 


3 


TW 


14 


10 


17 


27 


47 


64 


104 




12 


7 


13 


21 


36 


49 


80 




10 


5 


9 


15 


27 


36 


59 




8 


3 


5 


8 


15 


20 


33 


RHW\ RHW-2^ 


14 


6 


11 


18 


31 


42 


69 


THHW, THW, 


12 


5 


9 


14 


25 


34 


56 


THW-2 


10 


4 


7 


11 


19 


26 


43 




8 


2 


4 


7 


12 


16 


26 


RHW\ RHW-2^ 


6 


1 


3 


5 


9 


12 


20 


TW, THW, 


4 


1 


2 


4 


6 


9 


15 


THHW, THW-2 


3 


1 


1 


3 


6 


8 


13 




2 


1 


1 


3 


5 


6 


11 




1 


1 


1 


1 


3 


4 


7 




1/0 


1 


1 


1 


3 


4 


6 




2/0 





1 


1 


2 


3 


5 




3/0 





1 


1 


1 


3 


4 




4/0 





1 


1 


1 


2 


4 


THHN, THWN, 


14 


14 


24 


39 


68 


91 


149 


THWN-2 


12 


10 


17 


29 


49 


67 


109 




10 


6 


11 


18 


31 


42 


68 




8 


3 


6 


10 


18 


24 


39 




6 


2 


4 


7 


13 


17 


28 




4 


1 


3 


4 


8 


10 


17 




3 


1 


2 


4 


6 


9 


15 




2 


1 




3 


5 


7 


12 




1 


1 




2 


4 


5 


9 




1/0 


1 




1 


3 


4 


8 




2/0 


1 




1 


3 


4 


6 




3/0 







1 


2 


3 


5 




4/0 







1 


1 


2 


4 


XHHW, XHHW-2 


14 


10 


17 


27 


47 


64 


104 




12 


7 


13 


21 


36 


49 


80 




10 


5 


9 


15 


27 


36 


59 




8 


3 


5 


8 


15 


20 


i 33 




6 


1 


4 


6 


11 


15 


1 24 




4 


1 


3 


4 


8 


11 


, 18 




3 


1 


2 


4 


7 


9 


15 




2 


1 




3 


5 


7 


1 12 




1 


1 




2 


4 


5 


9 




1/0 


1 




1 


3 


5 


' 8 




2/0 


1 




1 


3 


4 


6 




3/0 







1 


2 


3 


5 




4/0 







1 


1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



512 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(5) 
MAXIMUM NUMBER OF CONDUCTORS IN LIQUID-TIGHT FLEXIBLE NONMETALLIC CONDUIT (FNMC-B)' 













TRADE SIZES 










CONDUCTOR 








(inches) 






















TYPE LETTERS 


SIZE AWG/kcmil 


'8 


% 


% 


1 


1% 


1V, 


2 


RHW, RHW-2 


14 


2 


4 


7 


12 


21 


27 


44 




12 


1 


3 


6 


10 


17 


22 


36 




10 


1 


3 


5 


8 


14 


18 


29 




8 


1 




2 


4 


7 


9 


15 




6 


1 




1 


3 


6 


7 


12 




4 







1 


2 


4 


6 


9 




3 







1 


1 


4 


5 


8 




2 







1 


1 


3 


4 


7 




1 








1 


1 


1 


3 


5 




1/0 








1 


1 


1 


2 


4 




2/0 








1 


1 


1 


1 


3 




3/0 











1 


1 


1 


3 




4/0 











1 


1 


1 


2 


TW 


14 


5 


9 


15 


25 


44 


57 


93 




12 


4 


7 


12 


19 


33 


43 


71 




10 


3 


5 


9 


14 


25 


32 


53 




8 


1 


3 


5 


8 


14 


18 


29 


RHW^ RGW-2^ 


14 


3 


6 


10 


16 


29 


38 


62 


THHW, THW, 


12 


3 


5 


8 


13 


23 


30 


50 


THW-2 


10 




3 


6 


10 


18 


23 


39 




8 




1 


4 


6 


11 


14 


23 


RHW^ RHW-2^ 


6 






3 


5 


8 


11 


18 


TW, THW, 


4 






1 


3 


6 


8 


13 


THHW, THW-2 


3 






1 


3 


5 


7 


11 




2 







1 


2 


4 


6 


9 




1 





^ 


1 




3 


4 


7 




1/0 








1 




2 


3 


6 




2/0 








1 




2 


3 


5 




3/0 








1 




1 


2 


4 




4/0 













1 


1 


3 


THHN, THWN, 


14 


8 


13 


22 


36 


63 


81 


133 


THWN-2 


12 


5 


9 


16 


26 


46 


59 


97 




10 


3 


6 


10 


16 


29 


37 


61 




8 




3 


6 


9 


16 


21 


35 




6 




2 


4 


7 


12 


15 


25 




4 






2 


4 


7 


9 


15 




3 






1 


3 


6 


8 


13 




2 






1 


3 


5 


7 


11 




1 







1 


1 


4 


5 


8 




1/0 







1 


1 


3 


4 


7 




2/0 








1 


1 


2 


3 


6 




3/0 








1 


1 


1 


3 


5 




4/0 








1 


1 


1 


2 


4 


XHHW, 


14 


5 


9 


15 


25 


44 


57 


93 


XHHW-2 


12 


4 


7 


12 


19 


33 


43 


71 




10 


3 


5 


9 


14 


25 


32 


53 




8 




3 


5 


8 


14 


18 


29 




6 






3 


6 


10 


13 


22 




4 






2 


4 


7 


9 


16 




3 








3 


6 


8 


13 




2 








3 


5 


7 


11 




1 











4 


5 


8 




1/0 











3 


4 


7 




2/0 








\ 




2 


3 


6 




3/0 












1 


3 


5 




4/0 












1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



513 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(6) 
MAXIMUM NUMBER OF CONDUCTORS IN LIQUID-TIGHT FLEXIBLE NONMETALLIC CONDUIT (FNMC-A)' 













TRADE SIZES 










CONDUCTOR 
SIZE 








(inches) 






















TYPE LETTERS 


AWG/kcmil 


'8 


\ 


3/ 


1 


1V4 


1V, 


2 


RHW, RHW-2 


14 


2 


4 


7 


U 


20 


27 


45 




12 


1 


3 


6 


9 


17 


23 


38 




10 


1 


3 


5 


8 


13 


18 


30 




8 


1 




2 


4 


7 


9 


16 




6 


1 




1 


3 


5 


7 


13 




4 







1 


2 


4 


6 


10 




3 







1 


1 


4 


5 


8 




2 







1 


1 


3 


4 


7 




1 








1 


1 


1 


3 


5 




1/0 








1 


1 


1 


2 


4 




2/0 








1 


1 


1 


1 


4 




3/0 











1 


1 


1 


3 




4/0 











1 


1 


1 


3 


TW 


14 


5 


9 


15 


24 


43 


58 


96 




12 


4 


7 


12 


19 


33 


44 


74 




10 


3 


5 


9 


14 


24 


33 


55 




8 


1 


3 


5 


8 


13 


18 


30 


RHW^ RHW-2^ 


14 


3 


6 


10 


16 


28 


38 


64 


THHW, THW, 


12 


3 


4 


8 


13 


23 


31 


51 


THW-2 


10 




3 


6 


10 


18 


24 


40 




8 




1 


4 


6 


10 


14 


24 


RHW^ RHW-2^ 


6 






3 


4 


8 


11 


18 


TW, THW, 


4 






1 


3 


6 


8 


13 


THHW, THW-2 


3 






1 


3 


5 


7 


11 




2 







1 


2 


4 


6 


10 




1 







1 




3 


4 


7 




1/0 








1 




2 


3 


6 




2/0 








1 




1 


3 


5 




3/0 








1 




1 


2 


4 




4/0 













1 


1 


3 


THHN, THWN, 


14 


8 


13 


22 


35 


62 


83 


137 


THWN-2 


12 


5 


9 


16 


25 


45 


60 


100 




10 


3 


6 


10 


16 


28 


38 


63 




8 




3 


6 


9 


16 


22 


36 




6 




2 


4 


6 


12 


16 


26 




4 






2 


4 


7 


9 


16 




3 






1 


3 


6 


8 


13 




2 






1 


3 


5 


7 


11 




1 







1 


1 


4 


5 


8 




1/0 







1 


1 


3 


4 


7 




2/0 








1 


1 


2 


3 


6 




3/0 








1 


1 


1 


3 


5 




4/0 








1 


1 


1 


2 


4 


XHHW, XHHW-2 


14 


5 


9 


15 


24 


43 


58 


96 




12 


4 


7 


12 


19 


33 


44 


74 




10 


3 


5 


9 


14 


24 


33 


55 




8 




3 


5 


8 


13 


18 


30 




6 






3 


5 


10 


13 


22 




4 






2 


4 


7 


10 


16 




3 








3 


6 


8 


14 




2 








3 


5 


7 


11 




1 











4 


5 


8 




1/0 











3 


4 


7 




2/0 












2 


3 


i 6 




3/0 












1 


3 


! 5 




4/0 












1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



514 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(7) 
MAXIMUM NUMBER OF CONDUCTORS IN LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMCf 











TRADE SIZES 








CONDUCTOR SIZE 






(inches) 




















TYPE LETTERS 


AWG/kcmil 


\ 


3/ 


1 


1V4 


1V. 


2 


RHW, RHW-2 


14 


4 


7 


12 


21 


27 


44 




12 


3 


6 


10 


17 


22 


36 




10 


3 


5 


8 


14 


18 


29 




8 




2 


4 


7 


9 


15 




6 




1 


3 


6 


7 


12 




4 




1 


2 


4 


6 


9 




3 




1 


1 


4 


5 


8 




2 




1 


1 


3 


4 


7 




1 





1 


1 


1 


3 


5 




1/0 





1 


1 


1 


2 


4 




2/0 





1 


1 


1 


1 


3 




3/0 








1 


1 


1 


3 




4/0 








1 


1 


1 


2 


TW 


14 


9 


15 


25 


44 


57 


93 




12 


7 


12 


19 


33 


43 


71 




10 


5 


9 


14 


25 


32 


53 




8 


3 


5 


8 


14 


18 


29 


RHW\ RHW-2^ 


14 


6 


10 


16 


29 


38 


62 


THHW, THW, 


12 


5 


8 


13 


23 


30 


50 


THW-2 


10 


3 


6 


10 


18 


23 


39 




8 


1 


4 


6 


11 


14 


23 


RHW% RHW-2\ 


6 




3 


5 


8 


11 


18 


TW, THW, 


4 




1 


3 


6 


8 


13 


THHW, THW-2 


3 




1 


3 


5 


7 


11 




2 




1 


2 


4 


6 


9 




1 




1 




3 


4 


7 




1/0 





1 




2 


3 


6 




2/0 





1 




2 


3 


5 




3/0 





1 




1 


2 


4 




4/0 










1 


1 


3 


THHN, THWN, 


14 


13 


22 


36 


63 


81 


133 


THWN-2 


12 


9 


16 


26 


46 


59 


97 




10 


6 


10 


16 


29 


37 


61 




8 


3 


6 


9 


16 


21 


35 




6 


2 


4 


7 


12 


15 


25 




4 




2 


4 


7 


9 


15 




3 




1 


3 


6 


8 


13 




2 




1 


3 


5 


7 


11 




1 


i 


1 


1 


4 


5 


8 




1/0 




1 


1 


3 


4 


7 




2/0 





1 


1 


2 


3 


6 




3/0 





1 


1 


1 


3 


5 




4/0 





1 


1 


1 


2 


4 


XHHW, 


14 


9 


15 


25 


44 


57 


93 


XHHW-2 


12 


7 


12 


19 


33 


43 


71 




10 


5 


9 


14 


25 


32 


53 




8 


3 


5 


8 


14 


18 


29 




6 




3 


6 


10 


13 


22 




4 




2 


4 


7 


9 


16 




3 






3 


6 


8 


13 




2 






3 


5 


7 


11 




1 








4 


5 


8 




1/0 








3 


4 


7 




2/0 









2 


3 


6 




3/0 







1 


1 


3 


5 




4/0 







1 


1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



515 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(8) 
MAXIMUM NUMBER OF CONDUCTORS IN RIGID METAL CONDUIT (RMCf 











TRADE SIZES 








CONDUCTOR 

SIZE 

AWG/kcmil 






(inches) 






TYPE LETTERS 


\ 


\ 


1 


1V4 


1% 


2 


RHW, RHW-2 


14 


4 


1 


12 


21 


28 


46 




12 


3 


6 


10 


17 


23 


38 




10 


3 


5 


8 


14 


19 


31 




8 




2 


4 


7 


10 


16 




6 




1 


3 


6 


8 


13 




4 




1 


2 


4 


6 


10 




3 




1 


2 


4 


5 


9 




2 




1 


1 


3 


4 


7 




1 





1 


1 


1 


3 


5 




1/0 





1 


1 


1 


2 


4 




2/0 





1 


1 


1 


2 


4 




3/0 








1 


1 


1 


' 3 




4/0 








1 


1 


1 


3 


TW 


14 


9 


15 


25 


44 


59 


98 




12 


7 


12 


19 


33 


45 


75 




10 


5 


9 


14 


25 


34 


56 




8 


3 


5 


8 


14 


19 


31 


RHw^ RHw-2^ 


14 


6 


10 


17 


29 


39 


65 


THHW, THW, 


12 


5 


8 


13 


23 


32 


52 


THW-2 


10 


3 


6 


10 


18 


25 


41 




8 


1 


4 


6 


11 


15 


24 


RHw^ RHw-2^ 


6 




3 


5 


8 


11 


18 


TW, THW, 


4 




1 


3 


6 


8 


14 


THHW, THW-2 


3 




1 


3 


5 


7 


12 




2 




1 


2 


4 


6 


10 




1 




1 




3 


4 


7 




1/0 





1 




2 


3 


6 




2/0 





1 




2 


3 


5 




3/0 





1 




1 


2 


4 




4/0 










1 


1 


3 


THHN, THWN, 


14 


13 


22 


36 


63 


85 


140 


THWN-2 


12 


9 


16 


26 


46 


62 


102 




10 


6 


10 


17 


29 


39 


64 




8 


3 


6 


9 


16 


22 


37 




6 


2 


4 


7 


12 


16 


27 




4 




2 


4 


7 


10 


16 




3 




1 


3 


6 


8 


14 




2 




1 


3 


5 


7 


11 




1 




1 


1 


4 


5 


8 




1/0 




1 


1 


3 


4 


7 




2/0 





1 


1 


2 


3 


6 




3/0 





1 


1 


1 


3 


5 




4/0 





1 


1 


1 


2 


4 


XHHW, XHHW-2 


14 


9 


15 


25 


44 


59 


98 




12 


7 


12 


19 


33 


45 


75 




10 


5 


9 


14 


25 


34 


56 




8 


3 


5 


8 


14 


19 


31 




6 




3 


6 


10 


14 


1 23 




4 




2 


4 


7 


10 


16 




3 






3 


6 


8 


14 




2 






3 


5 


7 


12 




1 








4 


5 


' 9 




1/0 








3 


4 


; 7 




2/0 









2 


3 


6 




3/0 









1 


3 


5 




4/0 









1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



516 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(9) 
MAXIMUM NUMBER OF CONDUCTORS IN RIGID PVC CONDUIT, SCHEDULE 80 (PVC-80)^ 











TRADE SIZES 








CONDUCTOR 
SIZE 






(inches) 


















TYPE LETTERS 


AWG/kcmil 


\ 


\ 


1 


1V4 


1V. 


2 


RHW, RHW-2 


14 


3 


5 


9 


17 


23 


39 




12 


2 


4 


7 


14 


19 


32 




10 


1 


3 


6 


11 


15 


26 




8 


1 




3 


6 


8 


13 




6 


1 




2 


4 


6 


11 




4 


1 




1 


3 


5 


8 




3 







1 


3 


4 


7 




2 







1 


3 


4 


6 




1 







1 


1 


2 


4 




1/0 








1 


1 


1 


3 




2/0 








1 


1 


1 


3 




3/0 








1 


1 


1 


3 




4/0 











1 


1 


2 


TW 


14 


6 


11 


20 


35 


49 


82 




12 


5 


9 


15 


27 


38 


63 




10 


3 


6 


11 


20 


28 


47 




8 


1 


3 


6 


11 


15 


26 


RHw^ RHw-2^ 


14 


4 


8 


13 


23 


32 


55 


THHW, THW, 


12 


3 


6 


10 


19 


26 


44 


THW-2 


10 


2 


5 


8 


15 


20 


34 




8 


1 


3 


5 


9 


12 


20 


RHW^ RHW-2^ 


6 


1 


1 


3 


7 


9 


16 


TW, THW, 


4 


1 


1 


3 


5 


7 


12 


THHW, THW-2 


3 


1 


1 


2 


4 


6 


10 




2 


1 


1 




3 


5 


8 




1 





1 




2 


3 


6 




1/0 





1 




1 


3 


5 




2/0 





1 




1 


2 


4 




3/0 










1 


1 


3 




4/0 










1 


1 


3 


THHN, THWN, 


14 


9 


17 


28 


51 


70 


118 


THWN-2 


12 


6 


12 


20 


37 


51 


86 




10 


4 


7 


13 


23 


32 


54 




8 


2 


4 


7 


13 


18 


31 




6 


1 


3 


5 


9 


13 


22 




4 


1 


1 


3 


6 


8 


14 




3 


1 


1 


3 


5 


7 


12 




2 


1 


1 


2 


4 


6 


10 




1 





1 


1 


3 


4 


7 




1/0 





1 


1 


2 


3 


6 




2/0 





1 


1 


1 


3 


5 




3/0 





1 


1 


1 


2 


4 




4/0 








1 


1 


1 


3 


XHHW, XHHW-2 


14 


6 


11 


20 


35 


49 


82 




12 


5 


9 


15 


27 


38 


63 




10 


3 


6 


11 


20 


28 


47 




8 




3 


6 


11 


15 


26 




6 




2 


4 


8 


11 


19 




4 






3 


6 


8 


14 




3 






3 


5 


7 


12 




2 






2 


4 


6 


10 




1 









3 


4 


7 




1/0 









2 


3 


6 




2/0 









1 


3 


5 




3/0 









1 


2 


4 




4/0 










1 


1 


3 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



517 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3804.6(10) 
MAXIMUM NUMBER OF CONDUCTORS IN RIGID PVC CONDUIT SCHEDULE 40 (PVC-40)^ 





CONDUCTOR 
SIZE 


TRADE SIZES 
(inches) 


TYPE LETTERS 


AWG/kcmil 


V, 


'u 


1 


1V. 


1V, 


2 


RHW, RHW-2 


14 


4 


1 


11 


20 


27 


45 




12 


3 


5 


9 


16 


22 


37 




10 


2 


4 


7 


13 


18 


30 




8 




2 


4 


7 


9 


15 




6 




1 


3 


5 


7 


12 




4 




1 


2 


4 


6 


10 




3 




1 


1 


4 


5 


8 




2 




1 


1 


3 


4 


7 




1 





1 


1 


1 


3 


5 




1/0 





1 


1 


1 


2 


4 




2/0 








1 


1 


1 


3 




3/0 








1 


1 


1 


3 




4/0 








1 


1 


1 


2 


TW 


14 


8 


14 


24 


42 


57 


94 




12 


6 


11 


18 


32 


44 


72 




10 


4 


8 


13 


24 


32 


54 




8 


2 


4 


7 


13 


18 


30 


RHw^ RHw-2^ 


14 


5 


9 


16 


28 


38 


63 


THHW, THW, 


12 


4 


8 


12 


22 


30 


50 


THW-2 


10 


3 


6 


10 


17 


24 


39 




8 


1 


3 


6 


10 


14 


23 


RHw^ RHw-2^ 


6 


1 


2 


4 


8 


11 


18 


TW, THW, 


4 


1 




3 


6 


8 


13 


THHW, THW-2 


3 


1 




3 


5 


7 


11 




2 


1 




2 


4 


6 


10 




1 









3 


4 


7 




1/0 









2 


3 


6 




2/0 









1 


3 


5 




3/0 









1 


2 


4 




4/0 










1 


1 


3 


THHN, THWN, 


14 


11 


21 


34 


60 


82 


135 


THWN-2 


12 


8 


15 


25 


43 


59 


99 




10 


5 


9 


15 


27 


37 


62 




8 


3 


5 


9 


16 


21 


36 




6 




4 


6 


11 


15 


26 




4 




2 


4 


7 


9 


16 




3 






3 


6 


8 


13 




2 






3 


5 


7 


11 




1 






1 


3 


5 


8 




1/0 






1 


3 


4 


7 




2/0 







1 


2 


3 


6 




3/0 







1 


1 


3 


5 




4/0 







1 


1 


2 


4 


XHHW, XHHW-2 


14 


8 


14 


24 


42 


57 


94 




12 


6 


11 


18 


32 


44 


72 




10 


4 


8 


13 


24 


32 


54 




8 


2 


4 


7 


13 


18 


30 




6 




3 


5 


10 


13 


22 




4 




2 


4 


7 


9 


i 16 




3 






3 


6 


8 


13 




2 






3 


5 


7 


11 




1 








3 


5 


8 




1/0 








3 


4 


< 7 




2/0 









2 


3 


6 




3/0 









1 


3 


: 5 




4/0 









1 


2 


4 



For SI: 1 inch = 25.4 mm. 

a. Types RHW, and RHW-2 without outer covering. 



518 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



POWER AND LIGHTING DISTRIBUTION 



SECTION E3805 
BOXES, CONDUIT BODIES AND FITTINGS 

E3805.1 Box, conduit body or fitting — where required. A 

box or conduit body shall be installed at each conductor splice 
point, outlet, switch point, junction point and pull point except 
as otherwise permitted in Sections E3 805. 1.1 through 
E3805.1.7. 

Fittings and connectors shall be used only with the specific 
wiring methods for which they are designed and listed. 

E3805.1.1 Equipment. An integral junction box or wiring 
compartment that is part of listed equipment shall be permit- 
ted to serve as a box or conduit body. 

E3805.1.2 Protection. A box or conduit body shall not be 
required where cables enter or exit from conduit or tubing 
that is used to provide cable support or protection against 
physical damage. A fitting shall be provided on the end(s) of 
the conduit or tubing to protect the cable from abrasion. 

E3805.1.3 Integral enclosure. A wiring device with inte- 
gral enclosure identified for the use, having brackets that 
securely fasten the device to walls or ceilings of conven- 
fional on-site frame construction, for use with nonmetal- 
lic-sheathed cable, shall be permitted in lieu of a box or 
conduit body. 

E3805.1.4 Fitting. A fitting identified for the use shall be 
permitted in lieu of a box or conduit body where such fitting 
is accessible after installation and does not contain spliced 
or terminated conductors. 

E3805.1.5 Buried conductors. Splices and taps in buried 
conductors and cables shall not be required to be enclosed in 
a box or conduit body where installed in accordance with 
Section E3703.4. 

E3805.1.6 Luminaires. Where a luminaire is listed to be 
used as a raceway, a box or conduit body shall not be 
required for wiring installed therein. 

E3805.1.7 Closed loop. Where a device identified and 
listed as suitable for installation without a box is used with a 
closed-loop power-distribution system, a box or conduit 
body shall not be required. 

E3805.2 Metal boxes. All metal boxes shall be grounded. 

E3805.3 Nonmetallic boxes. NonmetalUc boxes shall be used 
only with nonmetallic-sheathed cable, cabled wiring methods, 
flexible cords and nonmetallic raceways. 

Exceptions: 

1 . Where internal bonding means are provided between 
all entries, nonmetallic boxes shall be permitted to be 
used with metal raceways and metal-armored cables. 

2. Where integral bonding means with a provision for 
attaching an equipment grounding jumper inside the 
box are provided between all threaded entries in non- 
metallic boxes listed for the purpose, nonmetallic 
boxes shall be permitted to be used with metal race- 
ways and metal-armored cables. 

E3805.3.1 Nonmetallic-sheathed cable and nonmetallic 
boxes. Where nonmetallic-sheathed cable is used, the cable 



assembly, including the sheath, shall extend into the box not 
less than ^1^ inch (6.4 mm) through a nonmetallic-sheathed 
cable knockout opening. 

E3805.3.2 Securing to box. All permitted wiring methods 
shall be secured to the boxes. 

Exception: Where nonmetallic-sheathed cable is used 
with boxes not larger than a nominal size of 2 V4 inches by 
4 inches (57 mm by 102 mm) mounted in walls or ceil- 
ings, and where the cable is fastened within 8 inches (203 
mm) of the box measured along the sheath, and where the 
sheath extends through a cable knockout not less than ^1^ 
inch (6.4 mm), securing the cable to the box shall not be 
required. 

E3805.3.3 Conductor rating. Nonmetallic boxes shall be 
suitable for the lowest temperature-rated conductor enter- 
ing the box. 

E3805.4 Minimum depth of outlet boxes. Boxes shall have 
an internal depth of not less than 0.5 inch (12.7 mm). Boxes 
designed to enclose flush devices shall have an internal depth 
of not less than 0.938 inch (24 mm). 

E3805.5 Boxes enclosing flush-mounted devices. Boxes 
enclosing flush-mounted devices shall be of such design that 
the devices are completely enclosed at the back and all sides 
and shall provide support for the devices. Screws for support- 
ing the box shall not be used for attachment of the device con- 
tained therein. 

E3805.6 Boxes at luminaire outlets. Boxes for luminare out- 
lets shall be designed for the purpose. At every outiet used 
exclusively for lighting, the box shall be designed or installed 
so that a luminaire may be attached. 

Exception: A wall-mounted luminaire weighing not more 
than 6 lb (3 kg) shall be permitted to be supported on other 
boxes or plaster rings that are secured to other boxes, pro- 
vided the luminaire or its supporting yoke is secured to the 
box with no fewer than two No. 6 or larger screws. 

E3805.7 Maximum luminaire weight. Outlet boxes or fit- 
tings installed as required by Section E3804.3 shall be permit- 
ted to support luminaires weighing 50 lb (23 kg) or less. A 
luminaire that weighs more than 50 lb (23 kg) shall be sup- 
ported independently of the outlet box unless the outlet box is 
listed for the weight to be supported. 

E3805.8 Floor boxes. Where outlet boxes for receptacles are 
installed in the floor, such boxes shall be listed specifically for 
that application. 

E3805.9 Boxes at fan outlets. Outlet boxes and outiet box sys- 
tems used as the sole support of ceiling-suspended fans (pad- 
dle) shall be marked by their manufacturer as suitable for this 
purpose and shall not support ceihng-suspended fans (paddle) 
that weigh more than 70 lb (32 kg). For outiet boxes and outiet 
box systems designed to support ceiling-suspended fans (pad- 
dle) that weigh more than 35 lb (16 kg), the required marking 
shall include the maximum weight to be supported. 

E3805.10 Conduit bodies and junction, pull and outlet 
boxes to be accessible. Conduit bodies and junction, pull and 
outlet boxes shall be installed so that the wiring therein can be 
accessed without removing any part of the building or, in 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



519 



POWER AND LIGHTING DISTRIBUTION 



underground circuits, without excavating sidewalks, paving, 
earth or other substance used to establish the finished grade. 

Exception: Boxes covered by gravel, light aggregate or 
noncohesive granulated soil shall be hsted for the applica- 
tion, and the box locations shall be effectively identified and 
access shall be provided for excavation. 

E3805.il Damp or wet locations. In damp or wet locations, 
boxes, conduit bodies and fittings shall be placed or equipped 
so as to prevent moisture from entering or accumulating within 
the box, conduit body or fitting. Boxes, conduit bodies and fit- 
tings installed in wet locations shall be listed for use in wet 
locations. 

E3805.12 Number of conductors in outlet, device, and junc- 
tion boxes, and conduit bodies. Boxes and conduit bodies 
shall be of sufficient size to provide free space for all enclosed 
conductors. In no case shall the volume of the box, as calcu- 
lated in Section E3 805. 12. 1, be less than the box fill calculation 
as calculated in Section E3805. 12.2. The minimum volume for 
conduit bodies shall be as calculated in Section E3805.12.3. 
The provisions of this section shall not apply to terminal hous- 
ings supplied with motors. 



E3805.12.1 Box volume calculations. The volume of a wir- 
ing enclosure (box) shall be the total volume of the assembled 
sections, and, where used, the space provided by plaster 
rings, domed covers, extension rings, etc., that are marked 
with their volume in cubic inches or are made from boxes the 
dimensions of which are listed in Table E3805.12.1. 

E3805.12.1.1 Standard boxes. The volumes of standard 
boxes that are not marked with a cubic-inch capacity 
shall be as given in Table E3 805. 12.1. 

E3805.12.1.2 Other boxes. Boxes 100 cubic inches 
(1640 cm^) or less, other than those described in Table 
E3 805. 12.1, and nonmetallic boxes shall be durably and 
legibly marked by the manufacturer with their 
cubic-inch capacity. Boxes described in Table 
E3 805. 12.1 that have a larger cubic inch capacity than is 
designated in the table shall be permitted to have their 
cubic-inch capacity marked as required by this section. 

E3805.12.2 Box fill calculations. The volumes in Section 
E3805. 12.2.1 through Section E3805. 12.2.5, as applicable, 
shall be added together. No allowance shall be required for 
small fittings such as locknuts and bushings. 





TABLE E3805.12.1 
MAXIMUM NUMBER OF CONDUCTORS IN METAL BOXES^ 








BOX DIMENSIONS 
(Inches trade size and type) 


MAXIMUM CAPACITY 
(cubic inches) 


MAXIMUM NUMBER OF CONDUCTORS^ 


No. 18 


No. 16 


No. 14 


No. 12 


No. 10 


No. 8 


No. 6 


4 X 1 V4 round or octagonal 


12.5 


8 


7 


6 


5 


5 


4 


2 


4 X 1 V2 round or octagonal 


15.5 


10 


8 


7 


6 


6 


5 


3 


4 X 2V8 round or octagonal 


21.5 


14 


12 


10 


9 


8 


7 


4 


4 X 1 V4 square 


18.0 


12 


10 


9 


8 


7 


6 


3 


4 X 1 '/2 square 


21.0 


14 


12 


10 


9 


8 


7 


4 


4 X 2Vg square 


30.3 


20 


17 


15 


13 


12 


10 


6 


4'Vi6x'V4 square 


25.5 


17 


14 


12 


11 


10 


8 


5 


4'7,6x"/2 square 


29.5 


19 


16 


14 


13 


11 


9 


5 


4'Vi6x2V8 square 


42.0 


28 


24 


21 


18 _^ 


16 


14 


8 


3 X 2 X 1 V2 device 


7.5 


5 


4 


3 


3 


3 


2 


1 


3x2x2 device 


10.0 


6 


5 


5 


4 


4 


3 


2 


3 X 2 X 2V4 device 


10.5 


7 


6 


5 


4 


4 


3 


2 


3 X 2 X 2V2 device 


12.5 


8 


7 


6 


5 


5 


4 


2 


3 X 2 X 2V4 device 


14.0 


9 


8 


7 


6 


5 


4 


2 


3x2x3V2device 


18.0 


12 


10 


9 


8 


7 


6 


3 


4x278x1 1/2 device 


10.3 


6 


5 


5 


4 


4 


3 


2 


4 X 2'/8 X iVg device 


13.0 


8 


7 


6 


5 


5 


4 


2 


4x2V8x2V8device 


14.5 


9 


8 


7 


6 


5 


4 


2 


3V, X 2 X 2'/^ masonry box/gang 


14.0 


9 


8 


7 


6 


5 


4 


2 


3^/4 X 2 X 3 V2 masonry box/gang 


21.0 


14 


12 


10 


9 


8 


7 


4 



For SI: 1 inch = 25.4 mm, 1 cubic inch = 16.4 cm-^. 

a. Where no volume allowances are required by Sections E3805. 12.2.2 through E3805. 12.2.5. 



520 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



POWER AND LIGHTING DISTRIBUTION 



E3805.12.2.1 Conductor fill. Each conductor that origi- 
nates outside the box and terminates or is spliced within 
the box shall be counted once, and each conductor that 
passes through the box without splice or termination 
shall be counted once. A looped, unbroken conductor 
having a length equal to or greater than twice that 
required for free conductors by Section E3306.10.3, 
shall be counted twice. The conductor fill, in cubic 
inches, shall be computed using Table E3805. 12.2.1. A 
conductor, no part of which leaves the box, shall not be 
counted. 

Exception: An equipment grounding conductor or 
not more than four fixture wires smaller than No. 14, 
or both, shall be permitted to be omitted from the cal- 
culations where such conductors enter a box from a 
domed fixture or similar canopy and terminate within 
that box. 

E3805.12.2.2 Clamp fill. Where one or more internal 
cable clamps, whether factory or field supplied, are pres- 
ent in the box, a single volume allowance in accordance 
with Table E3 805 .12.2.1 shall be made based on the larg- 
est conductor present in the box. No allowance shall be 
required for a cable connector with its clamping mecha- 
nism outside the box. 

E3805.12.2.3 Support fittings fill. Where one or more 
fixture studs or hickeys are present in the box, a single 
volume allowance in accordance with Table 
E3 805. 12.2. 1 shall be made for each type of fitting based 
on the largest conductor present in the box. 



TABLE E3805.1 2.2.1 
VOLUME ALLOWANCE REQUIRED PER CONDUCTOR 



SIZE OF CONDUCTOR (AWG) 


FREE SPACE WITHIN BOX 

FOR EACH CONDUCTOR 

(cubic inches) 


No. 18 


1.50 


No. 16 


1.75 


No. 14 


2.00 


No. 12 


2.25 


No. 10 


2.50 


No. 8 


3.00 


No. 6 


5.00 



For SI: 1 cubic inch = 16.4 cm^. 

E3805.12.2.4 Device or equipment fill. For each yoke 
or strap containing one or more devices or equipment, a 
double volume allowance in accordance with Table 
E3805. 12.2. 1 shall be made for each yoke or strap based 
on the largest conductor connected to a device(s) or 
equipment supported by that yoke or strap. 

E3805.12.2.5 Equipment grounding conductor fill. 

Where one or more equipment grounding conductors or 
equipment bonding jumpers enters a box, a single vol- 
ume allowance in accordance with Table E3 805. 12. 2.1 
shall be made based on the largest equipment grounding 



conductor or equipment bonding jumper present in the 
box. 

E3805.12.3 Conduit bodies. Conduit bodies enclosing 6 
AWG conductors or smaller, other than short radius conduit 
bodies, shall have a cross-sectional area not less than twice 
the cross-sectional area of the largest conduit or tubing to 
which it is attached. The maximum number of conductors 
permitted shall be the maximum number permitted by Table 
E3 804.6 for the conduit to which it is attached. 

E3805. 12.3.1 Splices, taps or devices. Only those con- 
duit bodies that are durably and legibly marked by the 
manufacturer with their cubic inch capacity shall be per- 
mitted to contain splices, taps or devices. The maximum 
number of conductors shall be calculated using the same 
procedure for similar conductors in other than standard 
boxes. 



SECTION E3806 

INSTALLATION OF BOXES, CONDUIT 

BODIES AND FITTINGS 

E3806.1 Conductors entering boxes, conduit bodies or fit- 
tings. Conductors entering boxes, conduit bodies or fittings 
shall be protected from abrasion. 

E3806.1.1 Insulated fittings. Where raceways containing 
ungrounded conductors 4 AWG or larger enter a cabinet, 
box enclosure, or raceway, the conductors shall be protected 
by a substantial fitting providing a smoothly rounded insu- 
lating surface, unless the conductors are separated from the 
fitting or raceway by substantial insulating material 
securely fastened in place. 

Exception: Where threaded hubs or bosses that are an 
integral part of a cabinet, box enclosure, or raceway pro- 
vide a smoothly rounded or flared entry for conductors. 

Conduit bushings constructed wholly of insulating mate- 
rial shall not be used to secure a fitting or raceway. The insu- 
lating fitting or insulating material shall have a temperature 
rating not less than the insulation temperature rating of the 
installed conductors. 

E3806.2 Openings. Openings through which conductors enter 
shall be adequately closed. 

E3806.3 Metal boxes, conduit bodies and fittings. Where 
raceway or cable is installed with metal boxes, or conduit bod- 
ies, the raceway or cable shall be secured to such boxes and 
conduit bodies. 

E3806.4 Unused openings. Unused cable or raceway open- 
ings in boxes and conduit bodies shall be effectively closed to 
afford protection substantially equivalent to that of the wall of 
the box or conduit body. Metal plugs or plates used with non- 
metallic boxes or conduit bodies shall be recessed at least 0.25 
inch (6.4 mm) from the outer surface of the box or conduit 
body. 

E3806.5 In vv'all or ceiling. In walls or ceilings of concrete, tile 
or other noncombustible material, boxes employing a 
flush-type cover or faceplate shall be installed so that the front 
edge of the box, plaster ring, extension ring, or listed extender 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



521 



POWER AND LIGHTING DISTRIBUTION 



will not be set back from the finished surface more than V4 inch 
(6.4 mm). In walls and ceilings constructed of wood or other 
combustible material, boxes, plaster rings, extension rings and 
listed extenders shall be flush with the finished surface or pro- 
ject therefrom. 

E3806.6 Plaster, gypsum board and plasterboard. Open- 
ings in plaster, gypsum board or plasterboard surfaces that 
accommodate boxes employing a flush-type cover or faceplate 
shall be made so that there are no gaps or open spaces greater 
than Vg inch (3.2 mm) around the edge of the box. 

E3806.7 Exposed surface extensions. Surface extensions 
from a flush-mounted box shall be made by mounting and 
mechanically securing a box or extension ring over the flush 
box. 

Exception: A surface extension shall be permitted to be 
made from the cover of a flush-mounted box where the 
cover is designed so it is unlikely to fall off, or be removed if 
its securing means becomes loose. The wiring method shall 
be flexible for a length sufficient to permit removal of the 
cover and provide access to the box interior and arranged so 
that any bonding or grounding continuity is independent of 
the connection between the box and cover. 

E3806.8 Supports. Boxes and enclosures shall be supported in 
accordance with one or more of the provisions in Sections 
E3806.8.1 through E3806.8.6. 

E3806.8.1 Surface mounting. An enclosure mounted on a 
building or other surface shall be rigidly and securely fas- 
tened in place. If the surface does not provide rigid and 
secure support, additional support in accordance with other 
provisions of Section E3806.8 shall be provided. 

E3806.8.2 Structural mounting. An enclosure supported 
from a structural member of a building or from grade shall 
be rigidly supported either directly, or by using a metal, 
polymeric or wood brace. 

E3806.8.2.1 Nails and screws. Nails and screws, where 
used as a fastening means, shall be attached by using 
brackets on the outside of the enclosure, or they shall 
pass through the interior within V4 inch (6.4 mm) of the 
back or ends of the enclosure. Screws shall not be permit- 
ted to pass through the box except where exposed threads 
in the box are protected by an approved means to avoid 
abrasion of conductor insulation. 

E3806.8.2.2 Braces. Metal braces shall be protected 
against corrosion and formed from metal that is not less 
than 0.020 inch (.508 mm) thick uncoated. Wood braces 
shall have a cross section not less than nominal 1 inch by 
2 inches (25.4 mm by 5 1 mm). Wood braces in wet loca- 
tions shall be treated for the conditions. Polymeric braces 
shall be identified as being suitable for the use. 

E3806.8.3 Mounting in finished surfaces. An enclosure 
mounted in a finished surface shall be rigidly secured there 
to by clamps, anchors, or fittings identified for the applica- 
tion. 

E3806.8.4 Raceway supported enclosures without 
devices or fixtures. An enclosure that does not contain a 
device(s), other than splicing devices, or support a 



luminaire, lampholder or other equipment, and that is sup- 
ported by entering raceways shall not exceed 100 cubic 
inches (1640 cm^) in size. The enclosure shall have threaded 
entries or have hubs identified for the purpose. The enclo- 
sure shall be supported by two or more conduits threaded 
wrenchtight into the enclosure or hubs. Each conduit shall 
be secured within 3 feet (914 mm) of the enclosure, or 
within 1 8 inches (457 mm) of the enclosure if all entries are 
on the same side of the enclosure. 

Exception: Rigid metal, intermediate metal, or rigid 
nonmetallic conduit or electrical metallic tubing shall be 
permitted to support a conduit body of any size, provided 
that the conduit body is not larger in trade size than the 
largest trade size of the supporting conduit or electrical 
metallic tubing. 

E3806.8.5 Raceway supported enclosures, with devices 
or luminaire. An enclosure that contains a device(s), other 
than splicing devices, or supports a luminaire, lampholder 
or other equipment and is supported by entering raceways 
shall not exceed 100 cubic inches (1640 cm^) in size. The 
enclosure shall have threaded entries or have hubs identified 
for the purpose. The enclosure shall be supported by two or 
more conduits threaded wrench-tight into the enclosure or 
hubs. Each conduit shall be secured within 18 inches (457 
mm) of the enclosure. 

Exceptions: 

1 . Rigid metal or intermediate metal conduit shall be 
permitted to support a conduit body of any size, 
provided that the conduit bodies are not larger in 
trade size than the largest trade size of the support- 
ing conduit. 

2. An unbroken length(s) of rigid or intermediate 
metal conduit shall be permitted to support a box 
used for luminaire or lampholder support, or to 
support a wiring enclosure that is an integral part 
of a luminaire and used in lieu of a box in accor- 
dance with Section E3805. 1 . 1 , where all of the fol- 
lowing conditions are met: 

2.1. The conduit is securely fastened at a point 
so that the length of conduit beyond the last 
point of conduit support does not exceed 3 
feet (914 mm). 

2.2. The unbroken conduit length before the 
last point of conduit support is 12 inches 
(305 mm) or greater, and that portion of the 
conduit is securely fastened at some point 
not less than 12 inches (305 mm) from its 
last point of support. 

2.3. Where accessible to unqualified persons, 
the luminaire or lampholder, measured to 
its lowest point, is not less than 8 feet (2438 
mm) above grade or standing area and at 
least 3 feet (914 mm) measured horizon- 
tally to the 8-foot (2438 mm) elevation 
from windows, doors, porches, fire 
escapes, or similar locations. ; 



522 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



POWER AND LIGHTING DISTRIBUTION 



2.4. A luminaire supported by a single conduit 
does not exceed 12 inches (305 mm) in any 
direction from the point of conduit entry. 

2.5. The weight supported by any single con- 
duit does not exceed 20 pounds (9.1 kg). 

2.6. At the luminaire or lampholder end, the 
conduit(s) is threaded wrenchtight into the 
box, conduit body, or integral wiring 
enclosure, or into hubs identified for the 
purpose. Where a box or conduit body is 
used for support, the luminaire shall be 
secured directly to the box or conduit body, 
or through a threaded conduit nipple not 
over 3 inches (76 mm) long. 

E3806.8.6 Enclosures in concrete or masonry. An enclo- 
sure supported by embedment shall be identified as being 
suitably protected from corrosion and shall be securely 
embedded in concrete or masonry. 

E3806.9 Covers and canopies. Outlet boxes shall be effec- 
tively closed with a cover, faceplate or fixture canopy. 

E3806.10 Metal covers and plates. Metal covers and plates 
shall be grounded. 

E3806.il Exposed combustible finish. Combustible wall or 
ceiling finish exposed between the edge of a fixture canopy or 
pan and the outlet box shall be covered with noncombustible 
material. 



SECTION E3807 
CABINETS AND PANELBOARDS 

E3807.1 Enclosures for switches or overcurrent devices. 

Enclosures for switches or overcurrent devices shall not be 
used as junction boxes, auxiliary gutters, or raceways for con- 
ductors feeding through or tapping off to other switches or 
overcurrent devices, except where adequate space for this pur- 
pose is provided. The conductors shall not fill the wiring space 
at any cross section to more than 40 percent of the cross-sec- 
tional area of the space, and the conductors, splices, and taps 
shall not fill the wiring space at any cross section to more than 
75 percent of the cross-sectional area of that space. 

E3807.2 Damp or wet locations. In damp or wet locations, 
cabinets and panelboards of the surface type shall be placed or 
equipped so as to prevent moisture or water from entering and 
accumulating within the cabinet, and shall be mounted to pro- 
vide an airspace not less than V4 inch (6.4 mm) between the 
enclosure and the wall or other supporting surface. Cabinets 
installed in wet locations shall be weatherproof. For enclosures 
in wet locations, raceways and cables entering above the level 
of uninsulated live parts shall be installed with fittings listed for 
wet locations. 

E3807.3 Position in wall. In walls of concrete, tile or other 
noncombustible material, cabinets and panelboards shall be 
installed so that the front edge of the cabinet will not set back 
of the finished surface more than V4 inch (6.4 mm). In walls 
constructed of wood or other combustible material, cabinets 



shall be flush with the finished surface or shall project there- 
from. 

E3807.4 Repairing plaster, dry wall and plasterboard. Plas- 
ter, drywall, and plasterboard surfaces that are broken or 
incomplete shall be repaired so that there will not be gaps or 
open spaces greater than Vg inch (3.2 mm ) at the edge of the 
cabinet or cutout box employing a flush-type cover. 

E3807.5 Unused openings. Unused cable and raceway open- 
ings in cabinets and panelboards shall be effectively closed to 
afford protection equivalent to that of the wall of the cabinet. 
Metal plugs and plates used with nonmetallic cabinets shall be 
recessed at least V4 inch (6.4 mm) from the outer surface. 
Unused openings for circuit breakers and switches shall be 
closed using identified closures, or other approved means that 
provide protection substantially equivalent to the wall of the 
enclosure. 

E3807.6 Conductors entering cabinets. Conductors entering 
cabinets and panelboards shall be protected from abrasion and 
shall comply with Section E3806.1.1. 

E3807.7 Openings to be closed. Openings through which 
conductors enter cabinets, panelboards and meter sockets shall 
be adequately closed. 

E3807.8 Cables. Where cables are used, each cable shall be 
secured to the cabinet, panelboard, cutout box, or meter socket 
enclosure. 

Exception: Cables with entirely nonmetallic sheaths shall 
be permitted to enter the top of a surface-mounted enclosure 
through one or more sections of rigid raceway not less than 
18 inches (457 mm) nor more than 10 feet (3048 mm) in 
length, provided all the following conditions are met: 

1. Each cable is fastened within 12 inches (305 mm), 
measured along the sheath, of the outer end of the 
raceway. 

2. The raceway extends directly above the enclosure and 
does not penetrate a structural ceiling. 

3. A fitting is provided on each end of the raceway to 
protect the cable(s) from abrasion and the fittings 
remain accessible after installation. 

4. The raceway is sealed or plugged at the outer end 
using approved means so as to prevent access to the 
enclosure through the raceway. 

5. The cable sheath is continuous through the raceway 
and extends into the enclosure beyond the fitting not 
less than '/4 inch (6.4 mm). 

6. The raceway is fastened at its outer end and at other 
points in accordance with Section E3702.1. 

7. The allowable cable fill shall not exceed that permit- 
ted by Table E3807.8. A multiconductor cable having 
two or more conductors shall be treated as a single 
conductor for calculating the percentage of conduit 
fill area. For cables that have elliptical cross sections, 
the cross-sectional area calculation shall be based on 
the major diameter of the ellipse as a circle diameter. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



523 



POWER AND LIGHTING DISTRIBUTION 



TABLE E3807.8 

PERCENT OF CROSS SECTION 

OF CONDUIT AND TUBING FOR CONDUCTORS 



NUMBER OF CONDUCTORS 


MAXIMUM PERCENT OF CONDUIT 

AND TUBING AREA FILLED BY 

CONDUCTORS 


1 


53 


2 


31 


Over 2 


40 



SECTION E3808 
GROUNDING 

E3808.1 Metal enclosures. Metal enclosures of conductors, 
devices and equipment shall be grounded. 

Exceptions: 

1 . Short sections of metal enclosures or raceways used 
to provide cable assemblies with support or protec- 
tion against physical damage. 

2. A metal elbow that is installed in an underground 
installation of rigid nonmetallic conduit and is iso- 
lated from possible contact by a minimum cover of 1 8 
inches (457 mm) to any part of the elbow or that is 
encased in not less than 2 inches (50 mm) of concrete. 

E3808.2 Equipment fastened in place or connected by per- 
manent wiring methods (fixed). Exposed noncurrent-carrying 
metal parts of fixed equipment likely to become energized shall 
be grounded where any of the following conditions apply. 

1 . Where within 8 feet (2438 mm) vertically or 5 feet (1524 
mm) horizontally of earth or grounded metal objects and 
subject to contact by persons; 

2. Where located in a wet or damp location and not isolated; 
or 

3. Where in electrical contact with metal. 

E3808.3 Specific equipment fastened in place or connected 
by permanent wiring methods. Exposed noncurrent-carry- 
ing metal parts of the following equipment and enclosures shall 
be grounded: 

1. Luminaires as provided in Chapter 39. 

2. Motor-operated water pumps, including submersible 
types. Where a submersible pump is used in a metal well 
casing, the well casing shall be bonded to the pump cir- 
cuit equipment grounding conductor. 

E3808.4 Effective ground-fault current path. Electrical 
equipment and wiring and other electrically conductive mate- 
rial likely to become energized shall be installed in a manner 
that creates a permanent, low-impedance circuit facilitating the 
operation of the overcurrent device. Such circuit shall be capa- 
ble of safely carrying the maximum ground-fault current likely 
to be imposed on it from any point on the wiring system where a 
ground fault to the electrical supply source might occur. 

E3808.5 Earth as a ground-fault current path. The earth 
I shall not be considered as an effective ground-fault current 
path. 



E3808.6 Load-side neutral. A grounding connection shall not 
be made to any grounded circuit conductor on the load side of 
the service disconnecting means. 

Exception: A grounding conductor connection shall be 
made at each separate building where required by Section 

E3507.3. 

E3808.7 Load-side equipment. A grounded circuit conductor 
shall not be used for grounding noncurrent-carrying metal 
parts of equipment on the load side of the service disconnecting 
means. 

Exception: For separate buildings, in accordance with Sec- 
tion E3507.3.2 

E3808.8 Types of equipment grounding conductors. The 

equipment grounding conductor run with or enclosing the cir- 
cuit conductors shall be one or more or a combination of the 
following: 

1. A copper, aluminum or copper-clad conductor. This 
conductor shall be solid or stranded; insulated, covered 
or bare; and in the form of a wire or a busbar of any 
shape. 

2. Rigid metal conduit. 

3. Intermediate metal conduit. 

4. Electrical metallic tubing. 

5. Armor of Type AC cable in accordance with Section 
E3808.4. 

6. The combined metallic sheath and grounding conduc- 
tor of interlocked metal tape-type MC cable where 
listed and identified for grounding. 

7. The metallic sheath or the combined metallic sheath 
and grounding conductors of the smooth or corrugated 
tube type MC cable where listed and identified for 
grounding. 

8. Other electrically continuous metal raceways and aux- 
iliary gutters. 

9. Surface metal raceways listed for grounding. 

E3808.8.1 Flexible metal conduit. Flexible metal conduit 
shall be permitted as an equipment grounding conductor 
where all of the following conditions are met: 

1 . The conduit is terminated in fittings listed for ground- 
ing. ' 

2. The circuit conductors contained in the conduit are 
protected by overcurrent devices rated at 20 amperes 
or less. j 

3. The combined length of flexible metal: conduit and 
flexible metallic tubing and liquid-tight flexible metal 
conduit in the same ground return path does not 
exceed 6 feet (1829 mm). 

4. An equipment grounding conductor shall be installed 
where the conduit is used to connect equipment where 
flexibility is necessary after installation. 

E3808.8.2 Liquid-tight flexible metal conduit. Liq- 
uid-tight flexible metal conduit shall be permitted as an | 



524 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



POWER AND LIGHTING DISTRIBUTION 



• 



equipment grounding conductor where all of the following 
conditions are met: 

1 . The conduit is terminated in fittings listed for ground- 
ing. 

2. For trade sizes ^/g through '^ (metric designator 12 
through 16), the circuit conductors contained in the 
conduit are protected by overcurrent devices rated at 
20 amperes or less. 

3. For trade sizes % through IV4 (metric designator 21 
through 35), the circuit conductors contained in the 
conduit are protected by overcurrent devices rated at 
not more than 60 amperes and there is no flexible 
metal conduit, flexible metallic tubing, or liquid-tight 
flexible metal conduit in trade sizes Vg inch or Vj inch 
(9.5 mm through 12.7 mm) in the grounding path. 

4. The combined length of flexible metal conduit and 
flexible metallic tubing and liquid tight flexible metal 
conduit in the same ground return path does not 
exceed 6 feet (1829 mm). 

15. An equipment grounding conductor shall be installed 
where the conduit is used to connect equipment where 
flexibility is necessary after installation. 

E3808.8.3 Nonmetallic sheathed cable (Type NM). In 

addition to the insulated conductors, the cable shall have an 
insulated or bare conductor for equipment grounding pur- 
poses only. Equipment grounding conductors shall be sized 
in accordance with Table E3808.12. 

E3808.9 Equipment fastened in place or connected by per- 
manent wiring methods. Noncurrent-carrying metal parts of 
equipment, raceways and other enclosures, where required to 
be grounded, shall be grounded by one of the following meth- 
ods: 

1. By any of the equipment grounding conductors permit- 
ted by Sections E3808.8 through E3808.8.3. 

2. By an equipment grounding conductor contained within 
the same raceway, cable or cord, or otherwise run with 

I the circuit conductors. Equipment grounding conductors 

shall be identified in accordance with Section E3307.2. 

E3808.10 Methods of equipment grounding. Fixtures and 
equipment shall be considered grounded where mechanically 
connected to an equipment grounding conductor as specified in 

(Sections E3808.8 through E3808.8.3. Wire type equipment 
grounding conductors shall be sized in accordance with Sec- 
tion E3808. 12. 

E3808.il Equipment grounding conductor installation. 

Where an equipment grounding conductor consists of a race- 
way, cable armor or cable sheath or where such conductor is a 
wire within a raceway or cable, it shall be installed in accor- 
dance with the provisions of this chapter and Chapters 33 and 
37 using fittings for joints and terminations approved for instal- 
lation with the type of raceway or cable used. All connections, 
joints and fittings shall be made tight using suitable tools. 

E3808.12 Equipment grounding conductor size. Copper, 

aluminum and copper-clad aluminum equipment grounding 

I conductors of the wire type shall be not smaller than shown in 

Table E3808.12, but shall not be required to be larger than the 



circuit conductors supplying the equipment. Where a raceway 
or a cable armor or sheath is used as the equipment grounding 
conductor, as provided in Section E3808.8, it shall comply with 
Section E3808.4. Where ungrounded connectors are increased 
in size, equipment grounding conductors shall be increased 
proportionally according to the circular mil area of the 
ungrounded conductors. 

TABLE E3808.12 
EQUIPMENT GROUNDING CONDUCTOR SIZING 



RATING OR SETTING OF 

AUTOMATIC OVERCURRENT 

DEVICE IN CIRCUIT AHEAD OF 

EQUIPMENT, CONDUIT, ETC., NOT 

EXCEEDING THE FOLLOWING 

RATINGS (amperes) 


MINIMUM SIZE 


Copper wire No. 
(AWG) 


Aluminum or 

copper-clad 

aluminum wire 

No. (AWG) 


15 


14 


12 


20 


12 


10 


30 


10 


8 


40 


10 


8 


60 


10 


8 


100 


8 


6 


200 


6 


4 


300 


4 


2 


400 


3 


1 



E3808.12.1 Multiple circuits. Where a single equipment 
grounding conductor is run with multiple circuits in the 
same raceway or cable, it shall be sized for the largest 
overcurrent device protecting conductors in the raceway or 
cable. 

E3808.13 Continuity and attachment of equipment 
grounding conductors to boxes. Where circuit conductors are 
spliced within a box or terminated on equipment within or sup- 
ported by a box, any equipment grounding conductors associ- 
ated with the circuit conductors shall be spliced or joined 
within the box or to the box with devices suitable for the use. 
Connections depending solely on solder shall not be used. 
Splices shall be made in accordance with Section E3306.10 
except that insulation shall not be required. The arrangement of 
grounding connections shall be such that the disconnection or 
removal of a receptacle, luminaire or other device fed from the 
box will not interfere with or interrupt the grounding continu- 
ity. 

E3808.14 Connecting receptacle grounding terminal to 
box. An equipment bonding jumper shall be used to connect 
the grounding terminal of a grounding-type receptacle to a 
grounded box except where grounded in accordance with one 
of the following: 

1. Surface mounted box. Where the box is mounted on the 
surface, direct metal-to-metal contact between the 
device yoke and the box shall be permitted to ground the 
receptacle to the box. At least one of the insulating wash- 
ers shall be removed from receptacles that do not have a 
contact yoke or device designed and listed to be used in 
conjunction with the supporting screws to establish the 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



525 



POWER AND LIGHTING DISTRIBUTION 



grounding circuit between the device yoke and 
flush-type boxes. This provision shall not apply to 
cover-mounted receptacles except where the box and 
cover combination are listed as providing satisfactory 
ground continuity between the box and the receptacle. 

2. Contact devices or yokes. Contact devices or yokes 
designed and listed for the purpose shall be permitted in 
conjunction with the supporting screws to establish the 
grounding circuit between the device yoke and 
flush-type boxes. 

3. Floor boxes. The receptacle is installed in a floor box 
designed for and listed as providing satisfactory ground 
continuity between the box and the device. 

E3808.15 Metal boxes. A connection shall be made between 
the one or more equipment grounding conductors and a metal 
box by means of a grounding screw that shall be used for no 
other purpose, or by means of a listed grounding device. 
Sheet-metal screws shall not be used to connect grounding con- 
ductors or connection devices to boxes. 

E3808.16 Nonmetallic boxes. One or more equipment 
grounding conductors brought into a nonmetallic outlet box 
shall be arranged to allow connection to fittings or devices 
installed in that box. 

E3808.17 Clean surfaces. Nonconductive coatings such as 
paint, lacquer and enamel on equipment to be grounded shall 
be removed from threads and other contact surfaces to ensure 
electrical continuity or the equipment shall be connected by 
means of fittings designed so as to make such removal unneces- 
sary. 

E3808.18 Bonding other enclosures. Metal raceways, cable 
armor, cable sheath, enclosures, frames, fittings and other 
metal noncurrent-carrying parts that serve as grounding con- 
ductors, with or without the use of supplementary equipment 
grounding conductors, shall be effectively bonded where nec- 
essary to ensure electrical continuity and the capacity to con- 
duct safely any fault current likely to be imposed on them. Any 
nonconductive paint, enamel and similar coating shall be 
removed at threads, contact points and contact surfaces, or con- 
nections shall be made by means of fittings designed so as to 
make such removal unnecessary. 

E3808.19 Size of equipment bonding juniper on load side of 
service. The equipment bonding jumper on the load side of the 
service overcurrent devices shall be sized, as a minimum, in 
accordance with Table E3808. 1 2, but shall not be required to be 
larger than the circuit conductors supplying the equipment. An 
equipment bonding conductor shall be not smaller than No. 14 
AWG. 

A single common continuous equipment bonding jumper 
shall be permitted to bond two or more raceways or cables 
where the bonding jumper is sized in accordance with Table 
E3808.12 for the largest overcurrent device supplying circuits 
therein. 

E3808.20 Installation — equipment bonding jumper. The 

equipment bonding jumper shall be permitted to be installed 
inside or outside of a raceway or enclosure. Where installed on 
the outside, the length of the equipment bonding jumper shall 
not exceed 6 feet (1829 mm) and shall be routed with the race- 



way or enclosure. Where installed inside of a raceway, the 
equipment bonding jumper shall comply with the requirements 
of Sections E3808.9, Item 2; E3808.13; E3808.15; and 
E3808.16. 



SECTION E3809 
FLEXIBLE CORDS 

E3809.1 Where permitted. Flexible cords shall be used only 
for the connection of appliances where the fastening means and 
mechanical connections of such appliances are designed to 
permit ready removal for maintenance, repair or frequent inter- 
change and the appliance is listed for flexible cord connection. 
Flexible cords shall not be installed as a substitute for the fixed 
wiring of a structure; shall not be run through holes in walls, 
structural ceilings, suspended ceilings, dropped ceilings or 
floors; shall not be concealed behind walls, floors, ceilings or 
located above suspended or dropped ceilings. 

E3809.2 Loading and protection. The ampere load of flexible 
cords serving fixed appliances shall be in accordance with 
Table E3809.2. This table shall be used in conjunction with 
applicable end use product standards to ensure selection of the 
proper size and type. Where flexible cord is approved for and 
used with a specific listed appliance, it shall be considered to be 
protected where applied within the appliance listing require- 
ments. 

E3809.3 SpUces. Flexible cord shall be used only in continu- 
ous lengths without spHces or taps. 

E3809.4 Attachment plugs. Where used in accordance with 
Section E3809.1, each flexible cord shall be equipped with an 
attachment plug and shall be energized from a receptacle out- 
let. 

TABLE E3809.2 
MAXIMUM AMPERE LOAD FOR FLEXIBLE CORDS 



CORD SIZE 
(AWG) 


CORD TYPES S, SE, SEO, SJ, SJE, SJEO, SJO, 

SJOG, SJT, SJTO, SJTOO, SO, SCO, SRD, SRDE, 

SRDT, ST, STD, SV, SVO, SVOO, SVTO, SVTOO 


Maximum ampere load 


Three current-carrying 
conductors 


Two current-carrying 
conductors 


18 
16 
14 
12 


7 
10 
15 
20 


10 
13 
18 

25 



526 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



CHAPTER 39 

DEVICES AND LUMINAIRES 



SECTION E3901 
SWITCHES 

E3901.1 Rating and application of snap switches. Gen- 
eral-use snap switches shall be used within their ratings and 
shall control only the following loads: 

1. Resistive and inductive loads, including electric-dis- 
charge lamps, not exceeding the ampere rating of the 
switch at the voltage involved. 

2. Tungsten-filament lamp loads not exceeding the ampere 
rating of the switch at 120 volts. 

3. Motor loads not exceeding 80 percent of the ampere rat- 
ing of the switch at its rated voltage. 

E3901.2 CO/ALR snap switches. Snap switches rated 20 
amperes or less directly connected to aluminum conductors 
shall be marked CO/ALR. 

E3901.3 Indicating. General-use and motor-circuit switches 
and circuit breakers shall clearly indicate whether they are in 
the open OFF or closed ON position. Where single-throw 
switches or circuit breaker handles are operated vertically 
rather than rotationally or horizontally, the up position of the 
handle shall be the ON position. 

E3901.4 Time switches and similar devices. Time switches 
and similar devices shall be of the enclosed type or shall be 
mounted in cabinets or boxes or equipment enclosures. A bar- 
rier shall be used around energized parts to prevent operator 
exposure when making manual adjustments or switching. 

E3901.5 Grounding of enclosures. Metal enclosures for 
switches or circuit breakers shall be grounded. Where nonme- 
tallic enclosures are used with metal raceways or metal- 
armored cables, provisions shall be made for maintaining 
grounding continuity. 

Metal boxes for switches shall be effectively grounded. 
Nonmetallic boxes for switches shall be installed with a wiring 
method that provides or includes an equipment grounding con- 
ductor. 

E3901.6 Access. All switches and circuit breakers used as 
switches shall be located to allow operation from a readily 
accessible location. Such devices shall be installed so that the 
center of the grip of the operating handle of the switch or circuit 
breaker, when in its highest position, will not be more than 6 
feet 7 inches (2007 mm) above the floor or working platform. 

E3901.7 Wet locations. A switch or circuit breaker located in a 
wet location or outside of a building shall be enclosed in a 
weatherproof enclosure or cabinet. Switches shall not be 
installed within wet locations in tub or shower spaces unless 
installed as part of a listed tub or shower assembly. 

E3901.8 Grounded conductors. Switches or circuit breakers 
shall not disconnect the grounded conductor of a circuit except 
where the switch or circuit breaker simultaneously disconnects 
all conductors of the circuit. 



E3901.9 Switch connections. Three- and four-way switches 
shall be wired so that all switching occurs only in the 
ungrounded circuit conductor. Color coding of switch connec- 
tion conductors shall comply with Section E3307.3. Where in 
metal raceways or metal-jacketed cables, wiring between 
switches and outlets shall be in accordance with Section 
E3306.7. 

Exception: Switch loops do not require a grounded conduc- 
tor. 

E3901.10 Box mounted. Flush-type snap switches mounted in 
boxes that are recessed from the finished wall surfaces as cov- 
ered in Section E3806.5 shall be installed so that the extension 
plaster ears are seated against the surface of the wall. 
Flush-type snap switches mounted in boxes that are flush with 
the finished wall surface or project therefrom shall be installed 
so that the mounting yoke or strap of the switch is seated 
against the box. 

E3901.il Snap switch faceplates. Faceplates provided for 
snap switches mounted in boxes and other enclosures shall be 
installed so as to completely cover the opening and, where the 
switch is flush mounted, seat against the finished surface. 

E3901.11.1 Faceplate grounding. Snap switches, includ- 
ing dimmer and similar control switches, shall be effectively 
grounded and shall provide a means to ground metal face 
plates, whether or not a metal faceplate is installed. Snap 
switches shall be considered effectively grounded where 
either of the following conditions is met: 

1. The switch is mounted with metal screws to a metal 
box or to a nonmetallic box with integral means for 
grounding devices. 

2. An equipment grounding conductor or equipment 
bonding jumper is connected to an equipment 
grounding termination of the snap switch. 

Exception: Where a grounding means does not 
exist within the snap-switch enclosure or where 
the wiring method does not include or provide an 
equipment ground, a snap switch without a 
grounding connection shall be permitted for 
replacement purposes only. A snap switch wired 
under the provisions of this exception and located 
within reach of earth, grade, conducting floors, or 
other conducting surfaces shall be provided with a 
faceplate of nonconducting, noncombustible 
material or shall be protected by a ground-fault cir- 
cuit interrupter. 

E3901.12 Dimmer switches. General-use dimmer switches 
shall be used only to control permanently installed incandes- 
cent luminaires (lighting fixtures) except where listed for the 
control of other loads and installed accordingly. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



527 



DEVICES AND LUMINAIRES 



SECTION E3902 
RECEPTACLES 

E3902.1 Rating and type. Receptacles and cord connectors 
shall be rated at not less than 15 amperes, 125 volts, or 15 
amperes, 250 volts, and shall not be a lampholder type. Recep- 
tacles shall be rated in accordance with this section. 

E3902.1.1 Single receptacle. A single receptacle installed 
on an individual branch circuit shall have an ampere rating 
not less than that of the branch circuit. 

E3902.1.2 Two or more receptacles. Where connected to a 
branch circuit supplying two or more receptacles or outlets, 
receptacles shall conform to the values listed in Table 
E3902.1.2. 

TABLEE3902.1.2 

RECEPTACLE RATINGS FOR VARIOUS SIZE 

MULTI-OUTLET CIRCUITS 



CIRCUIT RATING (amperes) 


RECEPTACLE RATING (amperes) 


15 


15 


20 


15 or 20 


30 


30 


40 


40 or 50 


50 


50 



E3902.2 Grounding type. Receptacles installed on 15- and 
20-ampere-rated branch circuits shall be of the grounding type. 

E3902.3 CO/ALR receptacles. Receptacles rated at 20 
amperes or less and directly connected to aluminum conduc- 
tors shall be marked CO/ALR. 

E3902.4 Faceplates. Metal face plates shall be grounded. 

E3902.5 Position of receptacle faces. After installation, 
receptacle faces shall be flush with or project from face plates 
of insulating material and shall project a minimum of 0.015 
inch (0.381 mm) from metal face plates. Faceplates shall be 
installed so as to completely cover the opening and seat against 
the mounting surface. 

Exceptions: 

1. Listed kits or assemblies encompassing receptacles 
and nonmetallic faceplates that cover the receptacle 
face, where the plate cannot be installed on any other 
receptacle, shall be permitted. 

2. Listed nonmetallic faceplates that cover the recepta- 
cle face to a maximum thickness of 0.040 inches (1 
mm) shall be permitted. 

E3902.6 Receptacle mounted in boxes. Receptacles mounted 
in boxes that are set back from the finished wall surface as per- 
mitted by Section E3 806.5 shall be installed so that the mount- 
ing yoke or strap of the receptacle is held rigidly at the finished 
surface of the wall. Receptacles mounted in boxes that are flush 
with the wall surface or project therefrom shall be so installed 
that the mounting yoke or strap is seated against the box or 
raised cover. 

E3902.7 Receptacles mounted on covers. Receptacles 
mounted to and supported by a cover shall be held rigidly 
against the cover by more than one screw or shall be a device 



assembly or box cover listed and identified for securing by a || 
single screw. 

E3902.8 Damp locations. A receptacle installed outdoors in a 
location protected from the weather or in other damp locations 
shall have an enclosure for the receptacle that is weatherproof 
when the receptacle cover(s) is closed and an attachment plug 
cap is not inserted. An installation suitable for wet locations 
shall also be considered suitable for damp locations. A recepta- 
cle shall be considered to be in a location protected from the 
weather where located under roofed open porches, canopies 
and similar structures and not subject to rain or water runoff. 

E3902.9 Fifteen- and 20-ampere receptacles in wet loca- 
tions. Where installed in a wet location, 15- and 20-ampere, 
125- and 250-volt receptacles shall have an enclosure that is 
weatherproof whether or not the attachment plug cap is 
inserted. 

E3902.10 Other receptacles in wet locations. Where a recep- 
tacle other than a 15- or 20-amp, 125- or 250-volt receptacle is | 
installed in a wet location and where the product intended to be 
plugged into it is not attended while in use, the receptacle shall 
have an enclosure that is weatherproof both when the attach- 
ment plug cap is inserted and when it is removed. Where such 
receptacle is installed in a wet location and where the product 
intended to be plugged into it will be attended v/hile in use, the 
receptacle shall have an enclosure that is weatherproof when 
the attachment plug cap is removed. 

E3902.il Bathtub and shower space. A receptacle shall not 
be installed within or directly over a bathtub or shower stall. | 

E3902.12 Flush mounting with faceplate. In damp or wet 
locations, the enclosure for a receptacle installed in an outlet 
box flush-mounted in a finished surface shall be made weather- | 
proof by means of a weatherproof faceplate assembly that pro- 
vides a water-tight connection between the plate and the 
finished surface. I 



SECTION E3903 
FIXTURES 

E3903.1 Energized parts. Luminaires, lampholders, lamps 
and receptacles shall not have energized parts normally 
exposed to contact. 

E3903.2 Luminaires near combustible material. 

Luminaires shall be installed so that combustible material will 
not be subjected to temperatures in excess of 90°C (194°F). 

E3903.3 Exposed conductive parts. The exposed metal parts 
of luminaires shall be grounded or insulated frorii ground and 
other conducting surfaces. Lamp tie wires, mounting screws, 
clips and decorative bands on glass spaced at least 1 .5 inches 
(38 mm) from lamp terminals shall not be required to be 
grounded. 

E3903.4 Screw-shell type. Lampholders of the screw-shell 
type shall be installed for use as lampholders only. 

E3903.5 Recessed incandescent luminaires. Recessed incan- 
descent luminaires shall have thermal protection and shall be 
listed as thermally protected. 



528 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



DEVICES AND LUMINAIRES 



Exceptions: 

1 . Thermal protection shall not be required in recessed 
luminaires listed for the purpose and installed in 
poured concrete. 

2. Thermal protection shall not be required in recessed 
luminaires having design, construction, and thermal 
performance characteristics equivalent to that of ther- 
mally protected luminaires, and such luminaires are 
identified as inherently protected. 

E3903.6 Thermal protection. The ballast of a fluorescent 
luminaire installed indoors shall have integral thermal protec- 
tion. Replacement ballasts shall also have thermal protection 
integral with the ballast. A simple reactance ballast in a fluores- 
cent luminaire with straight tubular lamps shall not be required 
to be thermally protected. 

E3903.7 High-intensity discharge luminaires. Recessed 
high-intensity luminaires designed to be installed in wall or 
ceiling cavities shall have thermal protection and be identified 
as thermally protected. Thermal protection shall not be 
required in recessed high-intensity luminaires having design, 
construction and thermal performance characteristics equiva- 
lent to that of thermally protected luminaires, and such 
luminaires are identified as inherently protected. Thermal pro- 
tection shall not be required in recessed high-intensity dis- 
charge luminaires installed in and identified for use in poured 
concrete. A recessed remote ballast for a high-intensity dis- 
charge luminaire shall have thermal protection that is integral 
with the ballast and shall be identified as thermally protected. 

E3903.8 Wet or damp locations. Luminaires installed in wet 
or damp locations shall be installed so that water cannot enter 
or accumulate in wiring compartments, lampholders or other 
electrical parts. All luminaires installed in wet locations shall 
be marked SUITABLE FOR WET LOCATIONS. All 
luminaires installed in damp locations shall be marked SUIT- 
ABLE FOR WET LOCATIONS or SUITABLE FOR DAMP 
LOCATIONS. 

E3903.9 Lampholders in wet or damp locations. 

Lampholders installed in wet or damp locations shall be of the 
weatherproof type. 

E3903.10 Bathtub and shower areas. Cord-connected 
luminaires, chain-, cable-, or cord-suspended-luminaires, 
lighting track, pendants, and ceiling-suspended (paddle) fans 
shall not have any parts located within a zone measured 3 feet 
(914 mm) horizontally and 8 feet (2438 mm) vertically from 
the top of a bathtub rim or shower stall threshold. This zone is 
all encompassing and includes the zone directly over the tub or 
shower. Luminaires located in this zone shall be listed for damp 
locations and where subject to shower spray, shall be listed for 
wet locations. 

E3903.il Luminaires in clothes closets. For the purposes of 
this section, storage space shall be defined as a volume 
bounded by the sides and back closet walls and planes extend- 
ing from the closet floor vertically to a height of 6 feet(1829 
mm) or the highest clothes-hanging rod and parallel to the 
walls at a horizontal distance of 24 inches (610 mm) from the 
sides and back of the closet walls respectively, and continuing 
vertically to the closet ceiling parallel to the walls at a horizon- 



tal distance of 12 inches (305 mm) or the width of the shelf, 
whichever is greater. For a closet that permits access to both 
sides of a hanging rod, the storage space shall include the vol- 
ume below the highest rod extending 12 inches (305 mm) on 
either side of the rod on a plane horizontal to the floor extend- 
ing the entire length of the rod (see Figure E3903. 1 1). 

The types of luminaires installed in clothes closets shall be 
limited to surface-mounted or recessed incandescent 
luminaires with completely enclosed lamps, and sur- 
face-mounted or recessed fluorescent luminaires. Incandes- 
cent luminaires with open or partially enclosed lamps and 
pendant luminaires or lamp-holders shall be prohibited. 
Luminaire installations shall be in accordance with one or more 
of the following: 



1, 



Surface-mounted incandescent luminaires shall be 
installed on the wall above the door or on the ceiling, pro- 
vided there is a minimum clearance of 12 inches (305 
mm) between the fixture and the nearest point of a stor- 
age space. 



12" OR 
SHELF 
WIDTH 



12" OR 
SHELF 
WfDTH 




ROD 

HEIGHT 

0R6' 



12" OR 
SHELF 
WIDTH 




For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

FIGURE E3903.11 
CLOSET STORAGE SPACE 



2006 INTERNATIONAL RESIDENTIAL CODE® 



529 



DEVICES AND LUMINAIRES 



2. Surface-mounted fluorescent luminaires shall be 
installed on the wall above the door or on the ceiling, pro- 
vided there is a minimum clearance of 6 inches (152 mm) 
between the fixture and the nearest point of a storage 
space. 

3. Recessed incandescent luminaires with a completely 
enclosed lamp shall be installed in the wall or the ceiling 
provided there is a minimum clearance of 6 inches (152 
mm) between the luminaire and the nearest point of a 
storage space. 

4. Recessed fluorescent luminaires shall be installed in the 
wall or on the ceiling provided there is a minimum clear- 
ance of 6 inches (152 mm) between the fixture and the 
nearest point of a storage space. 

E3903.12 Luminaire wiring — general. Wiring on or within 
luminaires shall be neatly arranged and shall not be exposed to 
physical damage. Excess wiring shall be avoided. Conductors 
shall be arranged so that they are not subjected to temperatures 
above those for which the conductors are rated. 

E3903.12.1 Polarization of luminaires. Luminaires shall 
be wired so that the screw shells of lampholders will be con- 
nected to the same luminaire or circuit conductor or termi- 
nal. The grounded conductor shall be connected to the 
screw shell. 

E3903.12.2 Luminaires as raceways. Luminaires shall not 
be used as raceways for circuit conductors except where 
such luminaires are listed and marked for use as a raceway. 



SECTION E3904 
LUMINAIRE INSTALLATION 

E3904.1 Outlet box covers. In a completed installation, each 
outlet box shall be provided with a cover except where covered 
by means of a luminaire canopy, lampholder or device with a 
faceplate. 

E3904.2 Combustible material at outlet boxes. Combustible 
wall or ceiling finish exposed between the inside edge of a 
luminaire canopy or pan and the outlet box to which the 
luminaire connects shall be covered with a noncombustible 
material. 

E3904.3 Access. Luminaires shall be installed so that the con- 
nections between the luminaire conductors and the circuit con- 
ductors can be accessed without requiring the disconnection of 
any part of the wiring. 

E3904.4 Supports. Luminaires and lampholders shall be 
securely supported. A luminaire that weighs more than 6 
pounds (2.72 kg) or exceeds 16 inches (406 mm) in any dimen- 
sion shall not be supported by the screw shell of a lampholder. 

E3904.5 Means of support. Outlet boxes or fittings installed 
as required by Sections E3805 and E3806 shall be permitted to 
support luminaires. 

E3904.6 Exposed ballasts. Luminaires having exposed bal- 
lasts or transformers shall be installed so that such ballasts or 
transformers are not in contact with combustible material. 

E3904.7 Combustible low-density cellulose fiberboard. 

Where a surface-mounted luminaire containing a ballast is 



installed on combustible low-density cellulose fiberboard, the 
luminaire shall be listed for this purpose or it shall be spaced | 
not less than 1.5 inches (38 mm) from the surface of the fiber- 
board. Where such luminaires are partially or wholly recessed, 
the provisions of Sections E3904.8 and E3904.9 shall apply. 

E3904.8 Recessed luminaire clearance. A recessed luminaire 
that is not identified for contact with insulation shall have all 
recessed parts spaced at least 0.5 inch (12.7 mm) from combus- 
tible materials. The points of support and the finish trim parts at 
the opening in the ceiling or wall surface shall be permitted to 
be in contact with combustible materials. A recessed luminaire 
that is identified for contact with insulation, Type IC, shall be 
permitted to be in contact with combustible materials at 
recessed parts, points of support, and portions passing through 
the building structure and at finish trim parts at the opening in 
the ceiling or wall. 

E3904.9 Recessed luminaire installation. Thermal insulation 
shall not be installed above a recessed luminaire or within 3 
inches (76 mm) of the recessed luminaire's enclosure, wiring 
compartment or ballast except where such luminaire is identi- 
fied for contact with insulation. Type IC. 



SECTION E3905 
TRACK LIGHTING 

E3905.1 Installation. Lighting track shall be permanently 
installed and permanently connected to a branch circuit having | 
a rating not more than that of the track. 

E3905.2 Fittings. Fittings identified for use on lighting track 
shall be designed specifically for the track on which they are to 
be installed. Fittings shall be securely fastened to the track, 
shall maintain polarization and grounding, and shall be 
designed to be suspended directly from the track. Only lighting 
track fittings shall be installed on lighting track. Lighting track 
fittings shall not be equipped with general-purpose receptacles. 

E3905.3 Connected load. The connected load on lighting 
track shall not exceed the rating of the track. 

E3905.4 Prohibited locations. Lighting track shall not be 
installed in the following locations: 

1. Where likely to be subjected to physical damage. 

2. In wet or damp locations. 

3. Where subject to corrosive vapors. 

4. In storage battery rooms. 

5. In hazardous (classified) locations. 

6. Where concealed. 

7. Where extended through walls or partitions. 

8. Less than 5 feet (1524 mm) above the finished floor 
except where protected from physical daihage or the 
track operates at less than 30 volts rms open^circuit volt- 
age. 

9. Where prohibited by Section E3903. 10. 

E3905.5 Fastening. Lighting track shall be securely mounted 
so that each fastening will be suitable for supporting the maxi- 
mum weight of luminaires that can be installed. Except where 



530 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



DEVICES AND LUMINAIRES 



identified for supports at greater intervals, a single section 4 
feet (1219 mm) or shorter in length shall have two supports 
and, where installed in a continuous row, each individual sec- 
tion of not more than 4 feet (1219 mm) in length shall have one 
additional support. 

E3905.6 Grounding. Lighting track shall be grounded in 
accordance with Chapter 38, and the track sections shall be 
securely coupled to maintain continuity of the circuitry, polar- 
ization and grounding throughout. 



2006 INTERNATIONAL RESIDENTIAL CODE® 531 



532 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 40 

APPLIANCE INSTALLATION 



SECTION E4001 
GENERAL 

E4001.1 Scope. This section covers installation requirements 
for appliances and fixed heating equipment. 

E4001.2 Installation. Appliances and equipment shall be 
installed in accordance with the manufacturer's installation 
instructions. Electrically heated appliances and equipment 
shall be installed with the required clearances to combustible 
materials. 

E4001.3 Flexible cords. Cord-and-plug-connected appliances 
shall use cords suitable for the environment and physical con- 
ditions likely to be encountered. Flexible cords shall be used 
only where the appliance is listed to be connected with a flexi- 
ble cord. The cord shall be identified as suitable for the purpose 
in the installation instructions of the appliance manufacturer. 
Receptacles for cord-and-plug-connected appliances shall be 
accessible and shall be located to avoid physical damage to the 
flexible cord. Except for a listed appliance marked to indicate 
that it is protected by a system of double-insulation, the flexible 
cord supplying an appliance shall terminate in a ground- 
ing-type attachment plug. A receptacle for a cord-and-plug- 
connected range hood shall be supplied by an individual 
branch circuit. Specific appliances have additional require- 
ments as specified in Table E4001.3 (see Section E3809). 

TABLEE4001.3 
FLEXIBLE CORD LENGTH 



APPLIANCE 


MINIMUM CORD 
LENGTH (inches) 


MAXIMUM CORD 
LENGTH (inches) 


Kitchen waste 
disposal 


18 


36 


Built-in dishwasher 


36 


48 


Trash compactor 


36 


48 


Range hoods 


18 


36 



For SI: 1 inch = 25.4 mm. 



E4001.4 Overcurrent protection. Each appliance shall be 
protected against overcurrent in accordance with the rating of 
the appliance and its listing. 



E4001.4.1 Single nonmotor-operated appliance. The 

overcurrent protection for a branch circuit that supplies a 
single nonmotor-operated appliance shall not exceed that 
marked on the appliance. Where the overcurrent protection 
rating is not marked and the appliance is rated at over 13.3 
amperes, the overcurrent protection shall not exceed 150 
percent of the appliance rated current. Where 150 percent of 
the appliance rating does not correspond to a standard 
overcurrent device ampere rating, the next higher standard 
rating shall be permitted. Where the overcurrent protection 
rating is not marked and the appliance is rated at 13.3 
amperes or less, the overcurrent protection shall not exceed 
20 amperes. 

E4001.5 Disconnecting means. Each appliance shall be pro- 
vided with a means to disconnect all ungrounded supply con- 
ductors. For fixed electric space-heating equipment, means 
shall be provided to disconnect the heater and any motor con- 
troller(s) and supplementary overcurrent-protective devices. 
Switches and circuit breakers used as a disconnecting means 
shall be of the indicating type. Disconnecting means shall be as 
set forth in Table E4001.5. 

E4001.6 Support of ceiling-suspended paddle fans. Ceil- 
ing-suspended fans (paddle) shall be supported independently 
of an outlet box or by a listed outlet box or outlet box system 
identified for the use and installed in accordance with Section 
E3805.9. 

E4001.7 Snow-melting and deicing equipment protection. 

Outdoor receptacles that are not readily accessible and are sup- 
plied from a dedicated branch circuit for electric snow-melting 
or deicing equipment shall be permitted to be installed without 
ground-fault circuit-interrupter protection for personnel. How- 
ever, ground-fault protection of equipment shall be provided 
for fixed outdoor electric deicing and snow-melting equip- 
ment. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



533 



APPLIANCE INSTALLATION 



TABLEE4001.5 
DISCONNECTING MEANS 



DESCRIPTION 


ALLOWED DISCONNECTING MEANS 


Permanently connected appliance rated at not over 300 
volt-amperes or Vg horsepower. 


Branch-circuit overcurrent device. 


Permanently connected appliances rated in excess of 300 
volt-amperes or Vg horsepower. 


Branch circuit breaker or switch located within sight of appliance or such 
devices in any location that are capable of being locked in the open position. 
The provision for locking or adding a lock to the disconnecting means shall be 
installed on or at the switch or circuit breaker used as the disconnecting means 
and shall remain in place with or without the lock installed. 


Appliances listed for cord-and-plug connection. 


A separable connector or attachment plug and receptacle provided with access. 


Permanently installed heating equipment with motors rated 
at not over Vg horsepower with supplementary overcurrent 
protection. 


Disconnect, on the supply side of fuses, in sight from the supplementary 
overcurrent device, and in sight of the heating equipment or, in any location, if 
capable of being locked in the open position. 


Heating equipment containing motors rated over Vg 
horsepower with supplementary overcurrent protection. 


Disconnect permitted to serve as required disconnect for both the heating 
equipment and the controller where, on the supply side of fuses, arid in sight 
from the supplementary overcurrent devices, if the disconnecting means is also 
in sight from the controller, or is capable of being locked off. 


Heating equipment containing no motor rated over Vg 
horsepower without supplementary overcurrent protection. 


Branch-circuit switch or circuit breaker where within sight from the heating 
equipment or capable of being locked off. 


Heating equipment containing motors rated over Vg 
horsepower without supplementary overcurrent protection. 


Disconnecting means in sight from motor controller or as provided for heating 
equipment with motor rated over Vg horsepower with supplementary 
overcurrent protection. 


Air-conditioning condensing units and heat pump units. 


A readily accessible disconnect within sight from unit as the only allowable 
means.'' 


AppUances and fixed heating equipment with unit switches 
having a marked OFF position. 


Unit switch where an additional individual switch or circuit breaker serves as a 
redundant disconnecting means. 


Thermostatically controlled fixed heating equipment. 


Thermostats with a marked OFF position that directly open all ungrounded 
conductors, which when manually placed in the OFF position are designed so 
that the circuit cannot be energized automatically and that are located within 
sight of the equipment controlled. 



a. The disconnecting means shall be permitted to be installed on or within the unit. It shall not be located on panels designed to allow access to the unit. 



534 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



CHAPTER 41 

SWIMMING POOLS 



SECTION E4101 
GENERAL 

E4101.1 Scope. The provisions of this chapter shall apply to 
the construction and installation of electric wiring and equip- 
ment associated with all swimming pools, wading pools, deco- 
rative pools, fountains, hot tubs and spas, and hydromassage 
bathtubs, whether permanently installed or storable, and shall 
apply to metallic auxiliary equipment, such as pumps, filters 
and similar equipment. Sections E4102 through E4106 provide 
general rules for permanent pools, spas and hot tubs. Section 
E4107 provides specific rules for storable pools. Section 
E4108 provides specific rules for spas and hot tubs. Section 
E4109 provides specific rules for hydromassage bathtubs. 

E4101.2 Definitions. 

CORD-AND-PLUG-CONNECTED LIGHTING ASSEM- 
BLY. A lighting assembly consisting of a cord-and-plug-con- 
I nected transformer and a luminaire intended for installation in 
the wall of a spa, hot tub, or storable pool. 

DRY-NICHE LUMINAIRE. A luminaire intended for instal- 
lation in the wall of a pool or fountain in a niche that is sealed 
against the entry of pool water. 

FORMING SHELL. A structure designed to support a 
I wet-niche luminaire assembly and intended for mounting in a 
pool or fountain structure. 

FOUNTAIN. Fountains, ornamental pools, display pools, and 
reflection pools. The definition does not include drinking foun- 
tains. 

HYDROMASSAGE BATHTUB. A permanendy installed 
bathtub equipped with a recirculating piping system, pump, 
and associated equipment. It is designed so it can accept, circu- 
late and discharge water upon each use. 

MAXIMUM WATER LEVEL. The highest level that water 
can reach before it spills out. 

NO-NICHE LUMINAIRE. A luminaire intended for instal- 
lation above or below the water without a niche. 

PACKAGED SPA OR HOT TUB EQUIPMENT ASSEM- 
BLY. A factory-fabricated unit consisting of water-circulating, 
heating and control equipment mounted on a common base, 
intended to operate a spa or hot tub. Equipment may include 
pumps, air blowers, heaters, luminaires, controls and sanitizer 
generators. 

PERMANENTLY INSTALLED SWIMMING AND 
WADING POOLS. Those that are constructed in the ground 
or partially in the ground, and all others capable of holding 
water with a depth greater than 42 inches (1067 mm), and all 
pools installed inside of a building, regardless of water depth, 
whether or not served by electrical circuits of any nature. 

POOL COVER, ELECTRICALLY OPERATED. 

Motor-driven equipment designed to cover and uncover the 



water surface of a pool by means of a flexible sheet or rigid 
frame. 

SELF-CONTAINED SPA OR HOT TUB. A factory-fabri- 
cated unit consisting of a spa or hot tub vessel with all 
water-circulating, heating and control equipment integral to 
the unit. Equipment may include pumps, air blowers, heaters, 
luminaires, controls and sanitizer generators. 

SPA OR HOT TUB. A hydromassage pool, or tub for recre- 
ational or therapeutic use, not located in health care facilities, 
designed for immersion of users, and usually having a filter, 
heater, and motor-driven blower. They are installed indoors or 
outdoors, on the ground or supporting structure, or in the 
ground or supporting structure. Generally, a spa or hot tub is 
not designed or intended to have its contents drained or dis- 
charged after each use. 

STORABLE SWIMMING OR WADING POOL. Those 
that are constructed on or above the ground and are capable of 
holding water with a maximum depth of 42 inches (1067 mm), 
or a pool with nonmetallic, molded polymeric walls or inflat- 
able fabric walls regardless of dimension. 

THROUGH- WALL LIGHTING ASSEMBLY. A lighting 
assembly intended for installation above grade, on or through 
the wall of a pool, consisting of two interconnected groups of 
components separated by the pool wall. 

WET-NICHE LUMINAIRE. A luminaire intended for 
installation in a forming shell mounted in a pool or fountain 
structure where the luminaire will be completely surrounded 
by water. 



SECTION E4102 

WIRING METHODS FOR POOLS, SPAS, HOT TUBS 

AND HYDROMASSAGE BATHTUBS 

E4102.1 General. Wiring methods used in conjunction with per- 
manently installed swimming pools, spas, hot tubs or 
hydromassage bathtubs shall be installed in accordance with 
Table E4102.1 and Chapter 37 except as otherwise stated in this 
section. Storable swimming pools shall comply with Section 
E4107. 

E4102.2 Flexible cords. Flexible cords used in conjunction 
with a pool, spa, hot tub or hydromassage bathtub shall be 
installed in accordance with the following: 

1 . For other than underwater luminaires, fixed or stationary 
equipment, rated at 20 amperes or less shall be permitted to 
be connected with a flexible cord to facilitate the removal or 
disconnection for maintenance or repair. For other than 
storable pools, the flexible cord shall not exceed 3 feet (914 
mm) in length. Cords that supply swimming pool equip- 
ment, shall have a copper equipment grounding conductor 
not smaller than 12 AWG and shall be provided with a 
grounding-type attachment plug. 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



535 



SWIMMING POOLS 



2. Flexible cord that is supplied as part of a listed 
underwater swimming pool lighting luminaire shall be 
permitted to be installed in any of the permitted wiring 
methods from the luminaire to a deck box or other 
enclosure. Splices shall not be made within a raceway. 
The equipment grounding conductor shall be an insu- 
lated copper conductor that is not smaller than the sup- 
ply conductors and not smaller than 16 AWG. 

3 . A listed packaged spa or hot tub installed outdoors that is 
GFCI protected, shall be permitted to be cord and plug 
connected provided that such cord does not exceed 15 
feet (4572 mm) in length. 

4. A listed packaged spa or hot tub rated at 20 amperes or 
less and installed indoors shall be permitted to be cord 
and plug connected to facilitate maintenance and repair. 



5. For other than underwater and storable pool lighting 
luminaire, the requirements of Item 1 shall apply to any 
cord equipped luminaire that is located within 16 feet 
(4877 mm) radially from any point on the water surface. 

E4102.3 Double insulated pool pumps. A listed cord-and- 
plug-connected pool pump incorporating an approved system 
of double insulation that provides a means for grounding only 
the internal and nonaccessible, noncurrent-carrying metal 
parts of the pump shall be connected to any wiring method rec- 
ognized in Chapter 37 that is suitable for the location. Where 
the bonding grid is connected to the equipment grounding con- 
ductor of the motor circuit in accordance with Section 
E4104.2, Item 4, the branch circuit wiring shall comply with 
Sections E4102.1 and E4105.5. 



TABLE E4102.1 
ALLOWABLE APPLICATIONS FOR WIRING METHODS 


a, b, c, d, e, f, g, h 










WIRING LOCATION OR PURPOSE 
(Application allowed where marked with an "A") 


AC, FIVIC, NM, 
SR, SE 


EMT 


ENT 


IIVIC, RMC, 
RNC 


LFIWJC 


LFNMC 


UF 


IVIC 


Flex 
Cord 


Panelboard(s) that supply pool equipment: 
from service equipment to panelboard 


Ab,e 


A'^ 


— 


A 


— 


A 


A^ 


A*" 


— 


Wet-niche and no-niche luminaires: from 
branch circuit OCPD to deck or junction box 


— 


A'^ 


A'' 


A 


— 


A 


— 


A' 


— 


Wet- niche and no-niche luminaires: from deck 
or junction box to forming shell 


— 


— 


— 


A'l 


— 


A 


— 


— 


Ah 


Dry niche: from branch circuit OCPD to 
luminaires 


— 


A^ 


A" 


A 


— 


A 


— 


Ab 


— 


Pool-associated motors: from branch circuit 
OCPD to motor 


A" 


A'^ 


A" 


A 


Af 


A 


A" 


A 


Ah 


Packaged or self-contained outdoor spas and 
hot tubs with underwater luminaire: from 
branch circuit OCPD to spa or hot tub 


— 


A"^ 


A" 


A 


Af 


Af 


— 


— 


Ah 


Packaged or self-contained outdoor spas and 
hot tubs without underwater luminaire: from 
branch circuit OCPD to spa or hot tub 


A" 


A"^ 


A" 


A 


A' 


Af 


A'' 


A 


Ah 


Indoor spa and hot tubs, hydromassage 
bathtubs, and other pool, spa or hot tub 
associated equipment: from branch circuit 
OCPD to equipment 


A" 


A'^ 


Ab 


A 


A 


A 


A 


A 


Ah 


Connection at pool lighting transformers 


— 


A'^ 


A'' 


A 


AS 


Ag 


— 


A" 


— 



For SI: 1 foot = 304.8 mm. ! 

a. For all wiring methods, see Section E4105 for equipment grounding conductor requirements. 

b. Limited to use within buildings. 

c. Limited to use on or within buildings. 

d. Metal conduit shall be constructed of brass or other approved corrosion resistant metal. : 

e. Permitted only for existing installations in accordance with the exception to Section E4105.6. 

f. Limited to use at pool, spa or hot tub equipment where flexibility is necessary. For spas and hot tubs, the maximum length shall be 6 feet (1.8 m). 

g. Limited to use in individual lengths not to exceed 6 feet (1.8 m). The total length of all individual runs of LFMC and LFNMC shall not exceed 10 feet (3 m). 
LFNMC Type B shall be limited to lengths not exceeding 10 feet (3 m). 

h. Flexible cord shall be installed in accordance with Secdon E4 102.2. • 



536 



2006 INTERNATIONAL RESIDENTIAL CODE* 



SWIMMING POOLS 



SECTION E4103 
EQUIPMENT LOCATION AND CLEARANCES 

E4103.1 Receptacle outlets. Receptacles outlets shall be 
installed and located in accordance with Sections E4 103. 1.1 
through E4103. 1 .6. Distances shall be measured as the shortest 
path that an appliance supply cord connected to the receptacle 
would follow without penetrating a floor, wall, ceiling, door- 
way with hinged or sliding door, window opening, or other 
effective permanent barrier. 

E4103.1.1 Location. Receptacles that provide power for 
water-pump motors or other loads directly related to the cir- 
culation and sanitation system shall be permitted to be 
located between 5 feet and 10 feet (1524 mm and 3048 mm) 
from the inside walls of pools and outdoor spas and hot tubs, 
and, where so located, shall be single and of the locking and 
grounding type and shall be protected by ground-fault cir- 
cuit interrupters. 

Other receptacles on the property shall be located not less 
than 10 feet (3048 m) from the inside walls of pools and out- 
door spas and hot tubs except where permitted by Section 
E4103.1.3. 

E4103.1.2 Where required. At least one 125-volt, 15- or 
20-ampere receptacle supplied by a general-purpose branch 
circuit shall be located a minimum of 10 feet (3048 mm) 
from and not more than 20 feet (6096 mm) from the inside 
wall of pools and outdoor spas and hot tubs except as per- 
mitted by Section E4103.1.3. This receptacle shall be 
located not more than 6 feet, 6 inches (1981 mm) above the 
floor, platform or grade level serving the pool, spa or hot tub. 

E4103.1.3 Restricted space. Where a pool is within 10 feet 
(3.0 m) of a dwelling and the dimensions of the lot preclude 
meeting the required distances of Sections E4 103. 1.1 and 
E4 1 03 . 1 .2, not more than one receptacle outlet shall be permit- 
ted provided that such outlet is not less than 5 feet (1.5 m) mea- 
sured horizontally from the inside wall of the pool. 

E4103.1.4 GFCI protection. All 15- and 20-ampere, single 
phase, 125-volt receptacles located within 20 feet (6096 
mm) of the inside walls of pools and outdoor spas and hot 
tubs shall be protected by a ground-fault circuit-interrupter. 
Receptacles that supply pool pump motors and that are rated 
15 or 20 amperes, 125 volts through 250 volts, single phase, 
shall be provided with GFCI protection. 

E4103.1.5 Indoor locations. Receptacles shall be located 
not less than 5 feet (1524 mm) from the inside walls of 
indoor spas and hot tubs. A minimum of one 1 25-volt recep- 
tacle shall be located between 5 feet (1524 mm) and 10 feet 
(3048 mm) from the inside walls of indoor spas or hot tubs. 

E4103.1.6 Indoor GFCI protection. All 125-volt recepta- 
cles rated 30 amperes or less and located within 10 feet 
(3048 mm) of the inside walls of spas and hot tubs installed 
indoors, shall be protected by ground-fault circuit-inter- 
rupters. 

E4103.2 Switching devices. Switching devices shall be 
located not less than 5 feet (1 .5 m) horizontally from the inside 
walls of pools, spas and hot tubs except where separated from 
the pool, spa or hot tub by a solid fence, wall, or other perma- 
nent barrier. Switching devices located in a room or area con- 



taining a hydromassage bathtub shall be located in accordance 
with the general requirements of this code. 

E4103.3 Disconnecting means. One or more means to discon- | 
nect all ungrounded conductors for all utilization equipment, 
other than lighting, shall be provided. Each of such means shall I 
be readily accessible and within sight from the equipment it I 
serves. 

E4103.4 Luminaires and ceiling fans. Lighting outlets, 
luminaires, and ceiling-suspended paddle fans shall be 
installed and located in accordance with Sections E4103.4.1 
through E4103.4.5. 

E4103.4.1 Outdoor location. In outdoor pool, outdoor 
spas and outdoor hot tubs areas, luminaires, lighting outlets, 
and ceiling-suspended paddle fans shall not be installed 
over the pool or over the area extending 5 feet (1524 mm) 
horizontally from the inside walls of a pool except where no 
part of the luminaire or ceiling-suspended paddle fan is less 
than 12 feet (3658 mm) above the maximum water level. 

E4103.4.2 Indoor locations. In indoor pool areas, the limi- 
tations of Section E4103.4.1 shall apply except where the 
luminaires, hghting outlets and ceiling-suspended paddle 
fans comply with all of the following conditions: 

1 . The luminaires are of a totally enclosed type; 

2. A ground-fault circuit interrupter is installed in the 
branch circuit supplying the luminaires or ceil- 
ing-suspended (paddle) fans; and 

3. The distance from the bottom of the luminaire or ceil- 
ing-suspended (paddle) fan to the maximum water 
level is not less than 7 feet, 6 inches (2286 mm). 

E4103.4.3 Existing lighting outlets and luminaires. 

Existing lighting outlets and luminaires that are located 
within 5 feet (1524 mm) horizontally from the inside walls 
of pools and outdoor spas and hot tubs shall be permitted to 
be located not less than 5 feet (1524 mm) vertically above 
the maximum water level, provided that such luminaires 
and outlets are rigidly attached to the existing structure and I 
are protected by a ground-fault circuit-interrupter. | 

E4103.4.4 Indoor spas and hot tubs. 

1. Luminaires, lighting outlets, and ceiling-suspended 
paddle fans located over the spa or hot tub or within 5 
feet (1524 mm) from the inside walls of the spa or hot 
tub shall be a minimum of 7 feet, 6 inches (2286 mm) 
above the maximum water level and shall be pro- 
tected by a ground-fault circuit interrupter. 

Luminaires, lighting outlets, and ceiling-sus- 
pended paddle fans that are located 12 feet (3658 mm) 
or more above the maximum water level shall not 
require ground-fault circuit interrupter protection. 

2. Luminaires protected by a ground-fault circuit inter- 
rupter and complying with Item 2.1 or 2.2 shall be 
permitted to be installed less than 7 feet, 6 inches 
(2286 mm) over a spa or hot tub. 

2. 1 . Recessed luminaires shall have a glass or plas- 
tic lens and nonmetallic or electrically isolated 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



537 



SWIMMING POOLS 



metal trim, and shall be suitable for use in damp 
locations. 

2.2. Surface-mounted luminaires shall have a glass or 
plastic globe and a nonmetallic body or a metallic 
body isolated from contact. Such luminaires shall 
be suitable for use in damp locations. 

E4103.4.5 GFCI protection in adjacent areas. 

Luminaires and outlets that are installed in the area extend- 
ing between 5 feet (1524 mm) and 10 feet (3048 mm) from 
the inside walls of pools and outdoor spas and hot tubs shall 
be protected by ground-fault circuit-interrupters except 
where such fixtures and outlets are installed not less than 5 
feet (1524 mm) above the maximum water level and are rig- 
idly attached to the structure. 

E4103.5 Overhead conductor clearances. Except where 
installed with the clearances specified in Table E4103.5, the 
following parts of pools and outdoor spas and hot tubs shall not 
be placed under existing service-drop conductors or any other 
open overhead wiring; nor shall such wiring be installed above 
the following: 

1. Pools and the areas extending 10 feet (3048 mm) hori- 
zontally from the inside of the walls of the pool; 

2. Diving structures; or 

3. Observation stands, towers, and platforms. 

Utility-owned, -operated and -maintained communications 
conductors, community antenna system coaxial cables and the 
supporting messengers shall be permitted at a height of not less 
than 10 feet (3048 mm) above swimming and wading pools, div- 
ing structures, and observation stands, towers, and platforms. 



E4103.6 Underground wiring. Underground wiring shall not 
be installed under or within the area extending 5 feet(1524 mm) 
horizontally from the inside walls of pools and outdoor hot tubs 
and spas except where the wiring is installed to supply pool, spa 
or hot tub equipment or where space limitations prevent wiring 
from being routed 5 feet (1524 mm) or more horizontally from 
the inside walls. Where installed within 5 feet (1524 mm) of the 
inside walls, the wiring method shall be rigid metal conduit, 
intermediate metal conduit or a nonmetallic raceway system. 
Metal conduit shall be corrosion resistant and suitable for the 
location. The minimum raceway burial depth shall be in accor- 
dance with Table E4103.6. 



SECTION E4104 
BONDING 



required by 



E4104.1 Performance. The equipotential bonding 

this section shall be installed to eliminate voltage gradients in 

the pool area as prescribed. 

E4104.2 Bonded parts. The following parts shall be bonded 
together: 

1. All metallic parts of pool, spa and hot tub structures, 
including the reinforcing metal of pool, spa and hot tub 
shells, coping stones, and decks. The usual steel tie wires 
shall be considered suitable for bonding the reinforcing 
steel together, and welding or special clamping shall not 
be required. Such tie wires shall be made tight. Where 
reinforcing steel is effectively insulated by a listed 
encapsulating nonconductive compound, at the time of 
manufacture and installation, it shall not be required to 
be bonded. Where reinforcing steel is encapsulated with 



TABLE E4103.5 
OVERHEAD CONDUCTOR CLEARANCES 



^ ^_--- ^^ 


INSULATED SUPPLY OR SERVICE DROP 
CABLESrO-750 VOLTS TO GROUND, 

SUPPORTED ONAND CABLED 

TOGETHER WITH AN EFFECTIVELY 

GROUNDED BARE MESSENGER OR 

EFFECTIVELY GROUNDED NEUTRAL 

CONDUCTOR 

(feet) 


ALL OTHER SUPPLY OR SERVICE DROP CONDUCTORS 
(feet) 


Voltage to ground 


0-15 kV 


Greater than 15 to 50 kV 


A. Clearance in any direction to 
the water level, edge of water 
surface, base of diving platform, 
or permanently-anchored raft 


22.5 


25 


27 


B. Clearance in any direction to 
the diving platform 


14.5 


17 


18 



For SI: 1 foot = 304.8 mm. 



TABLE E4103.6 
MINIMUM BURIAL DEPTHS 



WIRING METHOD 


UNDERGROUND WIRING (inches) ! 


Rigid metal conduit 


6 


Intermediate metal conduit 


6 : 


Nonmetallic raceways listed for direct burial without concrete encasement 


18 


Other approved raceways^ 


18 



For SI: 1 inch = 25.4 mm. 

a. Raceways approved for burial only where concrete-encased shall require a concrete envelope not less than 2 inches in thickness. 



538 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



SWIMMING POOLS 



a nonconductive compound or another conductive mate- 
rial is not available, provisions shall be made for an alter- 
nate means to eliminate voltage gradients that would 
otherwise be provided by unencapsulated bonded rein- 
forcing steel. 

2. All metal forming shells and mounting brackets of 
no-niche luminaires except where a listed low-voltage 
lighting system with a nonmetallic forming shell is used 
that does not require bonding. 

3. All metal fittings within or attached to pool, spa and hot 
tub structures. Isolated parts that are not over 4 inches 
(102 mm) in any dimension and do not penetrate into the 
pool structure more than 1 inch (25.4 mm) shall not 
require bonding. The metal bands or hoops used to 
secure wooden staves for a hot tub or spa shall not be 
required to be bonded. 

4. Metal parts of electrical equipment associated with pool, 
spa and hot tub water circulating systems, including 
pump motors and metal parts of equipment associated 
with pool covers, including electric motors. Accessible 
metal parts of listed equipment incorporating an 
approved system of double insulation and providing a 
means for grounding internal nonaccessible, 
noncurrent-carrying metal parts shall not be bonded by a 
direct connection to the equipotential bonding grid. The 
means for grounding internal nonaccessible, noncurrent 
carrying metal parts shall be an equipment grounding 
conductor run with the power-supply conductors in the 
case of motors supplied with a flexible cord, or a ground- 
ing terminal in the case of motors intended for permanent 
connection. Where a double-insulated water-pump 
motor is installed under the provisions of this section, a 
solid 8 AWG copper conductor that is of sufficient 
length to make a bonding connection to a replacement 
motor shall be extended from the bonding grid to an 
accessible point in the motor vicinity. Where there is no 
connection between the swimming pool bonding grid 
and the equipment grounding system for the premises, 
this bonding conductor shall be connected to the equip- 
ment grounding conductor of the motor circuit. 

5. Electrical devices and controls not associated with pools, 
spas or hot tubs and located within 5 feet (1 .5 m) of such 
units. 

6. Metal-sheathed cables and raceways, metal piping and 
all fixed metal parts that are within 5 feet (1 524 mm) hor- 
izontally of the inside walls of the pool, spa or hot tub and 
that are within 12 feet (3658 mm) above the maximum 
water level of the pool or any observation stands, towers 
or platforms, or from any diving structures, and that are 
not separated from the pool by a permanent barrier. 

7. For pool water heaters rated at more than 50 amperes and 
having specific instructions regarding bonding and 
grounding, only those parts designated to be bonded 
shall be bonded and only those parts designated to be 
grounded shall be grounded. 

~E4104.3 Parts not required to be bonded. Small conductive 
surfaces not likely to become energized, such as towel bars, 
mirror frames, and air and water jets and drain fittings that are 



not connected to metallic piping, and similar equipment 
installed on or within indoor spas and hot tubs shall not be 
required to be bonded. 

E4104.4 Methods of bonding. It shall not be the intent to 
require that the 8 AWG or larger sohd copper bonding conduc- 
tor be extended or attached to any remote panelboard, service 
equipment, or any electrode, but only that it shall be employed 
to eliminate voltage gradients in the pool area as prescribed. 
Bonding shall be accomplished by one or more of the following 
methods: 

1 . Equipotential bonding grid. The parts specified in Sec- 
tion E4104.2 above shall be connected to an 
equipotential bonding grid with a solid copper conduc- 
tor, insulated, covered, or bare, not smaller than 8 AWG 
or rigid metal conduit of brass or other identified corro- 
sion resistant metal conduit. Connection shall be made 
by exothermic welding or by listed pressure connectors 
or clamps that are labeled as being suitable for the pur- 
pose and that are made of stainless steel, brass, copper or 
copper alloy. 

The equipotential bonding grid shall conform to the 
contours of the pool and shall extend within or under 
paved walking surfaces for 3 feet (1 m) horizontally 
beyond the inside walls of the pool and shall be permitted 
to be any of the following: 

Exception: The equipotential bonding grid shall not 
be required to be installed under the bottom of or ver- 
tically along the walls of vinyl lined polymer wall, 
fiberglass composite, or other pools constructed of 
nonconductive materials. Any metal parts of the pool, 
including metal structural supports, shall be bonded 
in accordance with Section E4104. 1 . For the purposes 
of this section, poured concrete, pneumatically 
applied (sprayed) concrete, and concrete block, with 
painted or plastered coatings, shall be considered as 
conductive materials. 

1.1. The structural reinforcing steel of a concrete pool 
or deck where the reinforcing rods are bonded 
together by the usual steel tie wires made up tight 
or the equivalent. Where deck reinforcing steel is 
not an integral part of the pool, the deck reinforc- 
ing steel shall be bonded to the other parts of the 
bonding grid using a solid conductor not smaller 
than 8 AWG. Connections shall be in accordance 
with Item 1.4. 

1 .2. The wall of a bolted or welded metal pool. 

1.3. As an alternative means, the system shall be con- 
structed as specified in Items 1.3.1 through 1.3.3: 

1.3.1. Materials and connections. The 
equipotential bonding grid shall be 
constructed of bare solid copper con- 
ductors not smaller than 8 AWG. Such 
conductors shall be bonded to each 
other at all points of crossing. Connec- 
tions shall be made as required by 
Item 1.4. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



539 



SWIMMING POOLS 



1.3.2. Grid structure. The equipotential 
bonding grid shall cover the contour 
of the pool and the pool deck extend- 
ing 3 feet (1 m) horizontally from the 
inside walls of the pool. The 
equipotential bonding grid shall be 
arranged in a 12 inch (300 mm) by 12 
inch (300 mm) network of conductors 
in a uniformly spaced perpendicular 
grid pattern with tolerance of 4 inches 
(100 mm). 

1.3.3. Securing. The below-grade grid shall 
be secured within or under the pool 
and deck media. 

1.4. Connections. Where structural reinforcing steel 
or the walls of bolted or welded metal pool struc- 
tures are used as an equipotential bonding grid 
for nonelectrical parts, the connections shall be 
connected by exothermic welding, listed pres- 
sure connectors, listed clamps, or other listed 
means. Connection devices or fittings that 
depend solely on solder shall not be used. Sheet 
metal screws shall not be used to connect bond- 
ing conductors or connection devices. 

2. For indoor hot tubs and spas, metal to metal mounting on 
a common frame or base. 

3. For indoor hot tubs and spas the interconnection of 
threaded metal piping and fittings. 

4. For indoor hot tubs and spas the provision of a solid cop- 
per bonding jumper, insulated, covered, or bare, not 
smaller than 8 AWG. 



SECTION E4105 
GROUNDING 

E4105.1 Equipment to be grounded. The following equip- 
ment shall be grounded: 

1. Through- wall lighting assemblies and underwater 
luminaires other than those low-voltage systems listed 
for the application without a grounding conductor. 

2. All electrical equipment located within 5 feet (1524 mm) 
of the inside wall of the pool, spa or hot tub. 

3. All electrical equipment associated with the recirculat- 
ing system of the pool, spa or hot tub. 

4. Junction boxes. 

5. Transformer enclosures. 

6. Ground-fault circuit-interrupters. 

7. Panelboards that are not part of the service equipment 
and that supply any electrical equipment associated with 
the pool, spa or hot tub. 

E4105.2 Luminaires and related equipment. Through-wall 
lighting assemblies, wet-niche, dry-niche, or no-niche 
luminaires shall be connected to an insulated copper equip- 
ment grounding conductor sized in accordance with Table 
E3808.12 but not smaller than 12 AWG. The equipment 



grounding conductor between the wiring chamber of the sec- 
ondary winding of a transformer and a junction box shall be 
sized in accordance with the overcurrent device in such circuit. 
The junction box, transformer enclosure, or other enclosure in 
the supply circuit to a wet-niche or no-niche luminaire and the 
field-wiring chamber of a dry-niche luminaire shall be 
grounded to the equipment grounding terminal of the 
panelboard. The equipment grounding terminal shall be 
directly connected to the panelboard enclosure. The equipment 
grounding conductor shall be installed without joint or splice. 

Exceptions: 

1. Where more than one underwater luminaire is sup- 
plied by the same branch circuit, the equipment 
grounding conductor, installed between the junction 
boxes, transformer enclosures, or other enclosures in 
the supply circuit to wet- niche luminaires, or between 
the field-wiring compartments of dry-niche 
luminaires, shall be permitted to be terminated on 
grounding terminals. 

2. Where an underwater luminaire is supplied from a 
transformer, ground-fault circuit-interrupter, 
clock-operated switch, or a manual snap switch that is 
located between the panelboard and a junction box 
connected to the conduit that extends directly to the 
underwater luminaire, the equipment grounding con- 
ductor shall be permitted to terminate on grounding 
terminals on the transformer, ground-fault cir- 
cuit-interrupter, clock-operated switch enclosure, or 
an outlet box used to enclose a snap switch. 

E4105.3 Nonmetallic conduit. Where a nonmetallic conduit 
is installed between a forming shell and a junction box, trans- 
former enclosure, or other enclosure, a 8 AWCr insulated cop- 
per bonding jumper shall be installed in this conduit except 
where a listed low-voltage lighting system not requiring 
grounding is used. The bonding jumper shall be terminated in 
the forming shell, junction box or transformer enclosure, or 
ground-fault circuit-interrupter enclosure. The termination of 
the 8 AWG bonding jumper in the forming shell shall be cov- 
ered with, or encapsulated in, a listed potting compound to pro- 
tect such connection from the possible deteriorating effect of 
pool water. 

E4105.4 Flexible cords. Wet-niche luminaires that are sup- 
plied by a flexible cord or cable shall have all exposed 
noncurrent-carrying metal parts grounded by an insulated cop- 
per equipment grounding conductor that is an integral part of 
the cord or cable. This grounding conductor shall be connected 
to a grounding terminal in the supply junction box, transformer 
enclosure, or other enclosure. The grounding conductor shall 
not be smaller than the supply conductors and not smaller than 
16 AWG. 

E4105.5 Motors. Pool-associated motors shall be connected to 
an insulated copper equipment grounding conductor sized in 
accordance with Table E3808.12, but not smaller than 12 
AWG. Where the branch circuit supplying the motor is 
installed in the interior of a one-family dwelling or in the inte- 
rior of accessory buildings associated with a one-family dwell- 
ing, using a cable wiring method permitted by Table E4102.1, 
an uninsulated equipment grounding conductor ishall be per- 



540 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



SWIMMING POOLS 



mitted provided that it is enclosed within the outer sheath of the 
cable assembly. 

E4105.6 Panelboards. A panelboard that is not part of the ser- 
vice equipment, or source of a separately derived system shall 
have an equipment grounding conductor installed between its 
grounding terminal and the grounding terminal of the applica- 
ble service equipment or source of a separately derived system. 
The equipment grounding conductor shall be insulated, shall 
be sized in accordance with Table E3808.12, and shall be not 
smaller than 12 AWG. 

Exception: An existing feeder between an existing remote 
panelboard and service equipment shall be permitted to run 
in flexible metal conduit or an approved cable assembly that 
includes an equipment grounding conductor within its outer 
sheath. The equipment grounding conductor shall not be 
connected to the grounded conductor in the remote 
panelboard. 

E4105.6.1 Separate buildings. A feeder to a separate 
building or structure shall be permitted to supply swimming 
pool equipment branch circuits, or feeders supplying swim- 
ming pool equipment branch circuits, provided that the 
grounding arrangements in the separate building meet the 
requirements of Section E3507.3. Where installed in other 
than existing feeders covered in the exception to Section 
E4105.6, a separate equipment grounding conductor shall 
be an insulated conductor. 

E4105.7 Cord-connected equipment. Where fixed or station- 
ary equipment is connected with a flexible cord to facilitate 
removal or disconnection for maintenance, repair, or storage, 
as provided in Section E4102.2, the equipment grounding con- 
ductors shall be connected to a fixed metal part of the assembly. 
The removable part shall be mounted on or bonded to the fixed 
metal part. 

E4105.8 Other equipment. Other electrical equipment shall 
be grounded in accordance with Section E3808. 



SECTION E41 06 
EQUIPMENT INSTALLATION 

E4106.1 Transformers. Transformers used for the supply of 
underwater luminaires, together with the transformer enclo- 
sure, shall be listed as a swimming pool and spa transformer. 
Such transformers shall be of an isolated winding type with an 
ungrounded secondary that has a grounded metal barrier 
between the primary and secondary windings. 

E4106.2 Ground-fault circuit-interrupters. Ground-fault 
circuit-interrupters shall be self-contained units, cir- 
cuit-breaker types, receptacle types or other approved types. 

E4106.3 Wiring on load side of ground-fault circuit-inter- 
rupters and transformers. For other than grounding conduc- 
tors, conductors installed on the load side of a ground-fault 
circuit-interrupter or transformer used to comply with the pro- 
visions of Section E4 106.4, shall not occupy raceways, boxes, 
or enclosures containing other conductors except where the 
other conductors are protected by ground-fault circuit inter- 
rupters or are grounding conductors. Supply conductors to a 
feed-through type ground-fault circuit interrupter shall be per- 



mitted in the same enclosure. Ground-fault circuit interrupters 
shall be permitted in a panelboard that contains circuits pro- 
tected by other than ground-fault circuit interrupters. 

E4106.4 Underwater luminaires. The design of an underwa- 
ter luminaire supplied from a branch circuit either directly or 
by way of a transformer meeting the requirements of Section 
E4 106.1, shall be such that, where the fixture is properly 
installed without a ground-fault circuit-interrupter, there is no 
shock hazard with any likely combination of fault conditions 
during normal use (not relamping). In addition, a ground-fault 
circuit-interrupter shall be installed in the branch circuit sup- 
plying luminaires operating at more than 15 volts, so that there 
is no shock hazard during relamping. The installation of the 
ground-fault circuit-interrupter shall be such that there is no 
shock hazard with any likely fault-condition combination that 
involves a person in a conductive path from any ungrounded 
part of the branch circuit or the luminaire to ground. Compli- 
ance with this requirement shall be obtained by the use of a 
listed underwater luminaire and by installation of a listed 
ground-fault circuit-interrupter in the branch circuit. 
Luminaires that depend on submersion for safe operation shall 
be inherently protected against the hazards of overheating 
when not submerged. 

E4106.4.1 Maximum voltage. Luminaires shall not be 
installed for operation on supply circuits over 150 volts 
between conductors. 

E4106.4.2 Luminaire location. Luminaires mounted in 
walls shall be installed with the top of the fixture lens not 
less than 18 inches (457 mm) below the normal water level 
of the pool, except where the luminaire is listed and identi- 
fied for use at a depth of not less than 4 inches (102 mm) 
below the normal water level of the pool. A luminaire facing 
upward shall have the lens adequately guarded to prevent 
contact by any person. 

E4106.5 Wet-niche luminaires. Forming shells shall be 
installed for the mounting of all wet-niche underwater 
luminaires and shall be equipped with provisions for conduit 
entries. Conduit shall extend from the forming shell to a suit- 
able junction box or other enclosure located as provided in Sec- 
tion E4106.9. Metal parts of the luminaire and forming shell in 
contact with the pool water shall be of brass or other approved 
corrosion-resistant metal. 

The end of flexible-cord jackets and flexible-cord conductor 
terminations within a luminaire shall be covered with, or 
encapsulated in, a suitable potting compound to prevent the 
entry of water into the luminaire through the cord or its conduc- 
tors. In addition, the grounding connection within a luminaire 
shall be similarly treated to protect such connection from the 
deteriorating effect of pool water in the event of water entry 
into the luminaire. 

Luminaires shall be bonded to and secured to the forming 
shell by a positive locking device that ensures a low-resistance 
contact and requires a tool to remove the luminaire from the 
forming shell. 

E4106.5.1 Servicing. All luminaires shall be removable 
from the water for relamping or normal maintenance. 
Luminaires shall be installed in such a manner that personnel 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



541 



SWIMMING POOLS 



can reach the luminaire for relamping, maintenance, or 
inspection while on the deck or equivalently dry location. 

E4106.6 Dry-niche luminaires. Dry-niche luminaires shall be 
provided with provisions for drainage of water and means for 
accommodating one equipment grounding conductor for each 
conduit entry. Junction boxes shall not be required but, if used, 
shall not be required to be elevated or located as specified in 
Section E4106.8 if the luminaire is specifically identified for 
the purpose. 

E4106.7 No-niche luminaires. No-niche luminaires shall be 
listed for the purpose and shall be installed in accordance with 
the requirements of Section E4 106.5. Where connection to a 
forming shell is specified, the connection shall be to the mount- 
ing bracket. 

E4106.8 Through-wall lighting assembly. A through-wall 
lighting assembly shall be equipped with a threaded entry or 
hub, or a nonmetallic hub, for the purpose of accommodating 
the termination of the supply conduit. A through- wall lighting 
assembly shall meet the construction requirements of Section 
E4105.4 and be installed in accordance with the requirements 
of Section E4106.5 Where connection to a forming shell is 
specified, the connection shall be to the conduit termination 
point. 

E4106.9 Junction boxes and enclosures for transformers or 
ground-fault circuit interrupters. Junction boxes for under- 
water luminaires and enclosures for transformers and 
ground-fault circuit-interrupters that supply underwater 
luminaires shall comply with the following: 

E4106.9.1 Junction boxes. A junction box connected to a 
conduit that extends directly to a forming shell or mounting 
bracket of a no-niche luminaire shall be: 

1. Listed as a swimming pool junction box; 

2. Equipped with threaded entries or hubs or a nonme- 
tallic hub; 

3 . Constructed of copper, brass, suitable plastic, or other 
approved corrosion-resistant material; 

4. Provided with electrical continuity between every 
connected metal conduit and the grounding terminals 
by means of copper, brass, or other approved corro- 
sion-resistant metal that is integral with the box; and 

5. Located not less than 4 inches (102 mm), measured 
from the inside of the bottom of the box, above the 
ground level, or pool deck, or not less than 8 inches 
(203 mm) above the maximum pool water level, 
whichever provides the greatest elevation, and shall 
be located not less than 4 feet (1219 mm) from the 
inside wall of the pool, unless separated from the pool 
by a solid fence, wall or other permanent barrier. 
Where used on a lighting system operating at 15 volts 
or less, a flush deck box shall be permitted provided 
that an approved potting compound is used to fill the 
box to prevent the entrance of moisture; and the flush 
deck box is located not less than 4 feet (1219 mm) 
from the inside wall of the pool. 

E4106.9.2 Other enclosures. An enclosure for a trans- 
former, ground-fault circuit-interrupter or a similar device 



connected to a conduit that extends directly to a forming 
shell or mounting bracket of a no-niche luminaire shall be: 

1 . Listed and labeled for the purpose, comprised of cop- 
per, brass, suitable plastic, or other approved 
corrosion-resistant material; 

2. Equipped with threaded entries or hubs or a nonme- 
tallic hub; 

3. Provided with an approved seal, such as duct seal at 
the conduit connection, that prevents circulation of air 
between the conduit and the enclosures; 

4. Provided with electrical continuity between every 
connected metal conduit and the grounding terminals 
by means of copper, brass or other approved corro- 
sion-resistant metal that is integral with the enclo- 
sures; and 

5. Located not less than 4 inches (102 mm), measured 
from the inside bottom of the enclosure, above the 
ground level or pool deck, or not less than 8 inches 
(203 mm) above the maximum pool water level, 
whichever provides the greater elevation, and shall be 
located not less than 4 feet (1219 mm) from the inside 
wall of the pool, except where separated from the pool 
by a solid fence, wall or other permanent barrier. 

E4106.9.3 Protection of junction boxes and enclosures. 

Junction boxes and enclosures mounted above the grade of 
the finished walkway around the pool shall not be located in 
the walkway unless afforded additional protection, such as 
by location under diving boards or adjacent to fixed struc- 
tures. 

E4106.9.4 Grounding terminals. Junction boxes, trans- 
former enclosures, and ground-fault circuit-interrupter 
enclosures connected to a conduit that extends directly to a 
forming shell or mounting bracket of a no-niche luminaire 
shall be provided with grounding terminals in a quantity not 
less than the number of conduit entries plus one. 

E4106.9.5 Strain reUef. The termination of a flexible cord 
of an underwater luminaire within a junction box, trans- 
former enclosure, ground-fault circuit-interrupter, or other 
enclosure shall be provided with a strain relief. 

E4106.10 Underwater audio equipment. Underwater audio 
equipment shall be identified for the purpose. 

E4106.10.1 Speakers. Each speaker shall be mounted in an 
approved metal forming shell, the front of which is enclosed 
by a captive metal screen, or equivalent, that is bonded to 
and secured to the forming shell by a positive locking device 
that ensures a low-resistance contact and requires a tool to 
open for installation or servicing of the speaker. The form- 
ing shell shall be installed in a recess in the wall or floor of 

the pool. j 

I 
E4106.10.2 Wiring methods. Rigid metal conduit or inter- 
mediate metal conduit of brass or other identified corro- 
sion-resistant metal, rigid nonmetallic conduit, or liquid 
tight flexible nonmetallic conduit (LFNC-B) shall extend 
from the forming shell to a suitable junction box or other 
enclosure as provided in Section E4 106.9. Where rigid non- 
metallic conduit or liquid tight flexible nonmetallic conduit 



542 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



SWIMMING POOLS 



is used, an 8 AWG solid or stranded insulated copper bond- 
ing jumper shall be installed in this conduit with provisions 
for terminating in the forming shell and the junction box. 
The termination of the 8 AWG bonding jumper in the form- 
ing shell shall be covered with, or encapsulated in, a suitable 
potting compound to protect such connection from the pos- 
sible deteriorating effect of pool water. 

E4106.10.3 Forming shell and metal screen. The forming 
shell and metal screen shall be of brass or other approved 
corrosion-resistant metal. All forming shells shall include 
provisions for terminating an 8 AWG copper conductor. 

E4106.il Electrically operated pool covers. The electric 
motors, controllers, and wiring for pool covers shall be located 
not less than 5 feet (1524 mm) from the inside wall of the pool 
except where separated from the pool by a wall, cover, or other 
permanent barrier. Electric motors installed below grade level 
shall be of the totally enclosed type. The electric motor and 
controller shall be connected to a circuit protected by a 
ground-fault circuit-interrupter. The device that controls the 
operation of the motor for an electrically operated pool cover 
shall be located so that the operator has full view of the pool. 

E4106.12 Electric pool water heaters. All electric pool water 
heaters shall have the heating elements subdivided into loads 
not exceeding 48 amperes and protected at not more than 60 
amperes. The ampacity of the branch-circuit conductors and 
the rating or setting of overcurrent protective devices shall be 
not less than 125 percent of the total nameplate load rating. 

E4106.13 Pool area heating. The provisions of Sections 
E4106.13.1 through E4106.13.3 shall apply to all pool deck 
areas, including a covered pool, where electrically operated 
comfort heating units are installed within 20 feet (6096 mm) of 
the inside wall of the pool. 

E4106.13.1 Unit heaters. Unit heaters shall be rigidly 
mounted to the structure and shall be of the totally enclosed 
or guarded types. Unit heaters shall not be mounted over the 
pool or within the area extending 5 feet (1524 mm) horizon- 
tally from the inside walls of a pool. 

E4106.13.2 Permanently wired radiant heaters. Electric 
radiant heaters shall be suitably guarded and securely fas- 
tened to their mounting devices. Heaters shall not be 
installed over a pool or within the area extending 5 feet 
(1524 mm) horizontally from the inside walls of the pool 
and shall be mounted not less than 12 feet (3658 mm) verti- 
cally above the pool deck. 

E4106.13.3 Radiant heating cables prohibited. Radiant 
heating cables embedded in or below the deck shall be pro- 
hibited. 

E4106.14 Double insulated pool pumps. A listed 
cord-and-plug-connected pool pump incorporating an 
approved system of double insulation that provides a means for 
grounding only the internal and nonaccessible, non-cur- 
rent-carrying metal parts of the pump shall be permitted to be 
used with permanently installed swimming pools. Branch cir- 
cuit wiring to the pump shall comply with Section E4102.3. 



SECTION E4107 
STORABLE SWIMMING POOLS 

E4107.1 Pumps. A cord-connected pool filter pump for use 
with storable pools shall incorporate an approved system of 
double insulation or its equivalent and shall be provided with 
means for grounding only the internal and nonaccessible 
noncurrent-carrying metal parts of the appliance. 

The means for grounding shall be an equipment grounding 
conductor run with the power-supply conductors in a flexible 
cord that is properly terminated in a grounding-type attach- 
ment plug having a fixed grounding contact. 

E4107.2 Ground-fault circuit-interrupters required. Elec- 
trical equipment, including power-supply cords, used with 
storable pools shall be protected by ground-fault circuit-inter- 
rupters. All 125 -volt receptacles located within 20 feet (6.0 m) 
of the inside walls of a storable pool shall be protected by a 
ground-fault circuit interrupter. In determining these dimen- 
sions, the distance to be measured shall be the shortest path that 
the supply cord of an appliance connected to the receptacle 
would follow without passing through a floor, wall, ceiling, 
doorway with hinged or sliding door, window opening, or other 
effective permanent barrier. 

E4107.3 Luminaires. Luminaires for storable pools shall not 
have exposed metal parts and shall be listed for the purpose as 
an assembly. In addition, luminaires for storable pools shall 
comply with the requirements of Section E4107.3.1 or 
E4107.3.2. 

E4107.3.1 Fifteen (15) volts or less. A luminaire installed 
in or on the wall of a storable pool shall be part of a cord- and 
plug-connected lighting assembly. The assembly shall: 

1. Have a luminaire lamp that operates at 15 volts or 
less; 

2. Have an impact-resistant polymeric lens, luminaire 
body, and transformer enclosure; 

3 . Have a transformer meeting the requirements of section 
E4106.1 with a primary rating not over 150 volts; and 

4. Have no exposed metal parts. | 

E4107.3.2 Not over 150 volts. A lighting assembly without 
a transformer, and with the luminaire lamp(s) operating at 
not over 150 volts, shall be permitted to be cord- and 
plug-connected where the assembly is listed as an assembly 
for the purpose and complies with all of the following: 

1. It has an impact-resistant polymeric lens and 
luminaire body. 

2. A ground-fault circuit interrupter with open neutral 
protection is provided as an integral part of the assem- 
bly. 

3. The luminaire lamp is permanently connected to the 
ground-fault circuit interrupter with open-neutral 
protection. 

4. It comphes with the requirements of Section E4106.4. 

5. It has no exposed metal parts. 

E4107.4 Receptacle locations. Receptacles shall be not less I 
than 10 feet (3.0 m) from the inside walls of a pool. In deter- I 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



543 



SWIMMING POOLS 



mining these dimensions, the distance to be measured shall be 
the shortest path that the supply cord of an appliance connected 
to the receptacle would follow without passing through a floor, 
wall, ceiling, doorway with hinged or sliding door, window 
opening, or other effective permanent barrier. 



SECTION E4108 
SPAS AND HOT TUBS 

E4108.1 Ground-fault circuit-interrupters. The outlet(s) 
that supplies a self-contained spa or hot tub, or a packaged spa 
or hot tub equipment assembly, or a field-assembled spa or hot 
tub with a heater load of 50 amperes or less, shall be protected 
by a ground-fault circuit-interrupter. 

A listed self-contained unit or listed packaged equipment 
assembly marked to indicate that integral ground-fault circuit- 
interrupter protection is provided for all electrical parts within 
the unit or assembly, including pumps, air blowers, heaters, 
luminaires, controls, sanitizer generators and wiring, shall not 
require that the outlet supply be protected by a ground-fault cir- 
cuit interrupter. 

A combination pool/hot tub or spa assembly commonly 
bonded need not be protected by a ground-fault circuit inter- 
rupter. 

E4108.2 Electric water heaters. Electric spa and hot tub water 
heaters shall be listed and shall have the heating elements sub- 
divided into loads not exceeding 48 amperes and protected at 
not more than 60 amperes. The ampacity of the branch-circuit 
conductors, and the rating or setting of overcurrent protective 
devices, shall be not less than 125 percent of the total name- 
plate load rating. 

E4108.3 Underwater audio equipment. Underwater audio 
equipment used with spas and hot tubs shall comply with the 
provisions of Section E4106.10. 

E4108.4 Emergency switch for spas and hot tubs. A clearly 
labeled emergency shutoff or control switch for the purpose of 
stopping the motor(s) that provides power to the recirculation 
system and jet system shall be installed at a point that is readily 
accessible to the users, adjacent to and within sight of the spa or 
hot tub and not less than 5 feet (1 .5 m) away from the spa or hot 
tub. This requirement shall not apply to single-family dwell- 
ings. 



this code relative to the installation of electrical equipment in 
bathrooms. 

E4109.3 Accessibility. Hydromassage bathtub electrical 
equipment shall be accessible without damaging the building 
structure or building finish. 

E4109.4 Bonding. All metal piping systems and all grounded 
metal parts in contact with the circulating water shall be 
bonded together using a solid copper bonding jumper, insu- 
lated, covered, or bare, not smaller than 8 AWG. 



SECTION E4109 
HYDROMASSAGE BATHTUBS 

E4109.1 Ground-fault circuit-interrupters. Hydromassage 
bathtubs and their associated electrical components shall be 
protected in accordance with Section E4108. All 125- volt, sin- 
gle-phase receptacles not exceeding 30 amperes and located 
within 5 feet (1524 mm) measured horizontally of the inside 
walls of a hydromassage tub shall be protected by a 
ground-fault circuit interrupter(s). 

E4109.2 Other electric equipment. Luminaires, switches, 
receptacles, and other electrical equipment located in the same 
room, and not directly associated with a hydromassage bath- 
tub, shall be installed in accordance with the requirements of 



544 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



CHAPTER 42 

CLASS 2 REMOTE-CONTROL, SIGNALING 
AND POWER-LIMITED CIRCUITS 



SECTION E4201 
GENERAL 

E4201.1 Scope. This chapter contains requirements for power 
supplies and wiring methods associated with Class 2 
remote-control, signaling, and power-limited circuits that are 
not an integral part of a device or appliance. Other classes of 
remote-control, signaling and power-limited conductors shall 
comply with Article 725 of NFPA 70. 

E4201.2 Definitions. 

CLASS 2 CIRCUIT. That portion of the wiring system 
between the load side of a Class 2 power source and the con- 
nected equipment. Due to its power limitations, a Class 2 cir- 
cuit considers safety from a fire initiation standpoint and 
provides acceptable protection from electric shock. 

REMOTE-CONTROL CIRCUIT. Any electrical circuit that 
controls any other circuit through a relay or an equivalent device. 

SIGNALING CIRCUIT. Any electrical circuit that energizes 
signaling equipment. 



SECTION E4202 
POWER SOURCES 

E4202.1 Power sources for Class 2 circuits. The power 
source for a Class 2 circuit shall be one of the following: 

1 . A listed Class 2 transformer. 

2. A listed Class 2 power supply. 

3. Other listed equipment marked to identify the Class 2 
power source. 

4. Listed information technology (computer) equipment 
limited power circuits. 

5. A dry cell battery provided that the voltage is 30 volts or 
less and the capacity is equal to or less than that available 
from series connected No. 6 carbon zinc cells. 

E4202.2 Interconnection of power sources. A Class 2 power 
source shall not have its output connections paralleled or other- 
wise interconnected with another Class 2 power source except 
where listed for such interconnection. 



SECTION E4203 
WIRING METHODS 

E4203.1 Wiring methods on supply side of Class 2 power 
source. Conductors and equipment on the supply side of the 
power source shall be installed in accordance with the appro- 
priate requirements of Chapters 33 through 40. Transformers 
or other devices supplied from electric light or power circuits 
shall be protected by an over current device rated at not over 20 
amperes. The input leads of a transformer or other power 



source supplying Class 2 circuits shall be permitted to be 
smaller than 14 AWG, if not over 12 inches (305 mm) long and 
if the conductor insulation is rated at not less than 600 volts. In 
no case shall such leads be smaller than 18 AWG. 

E4203.2 Wiring methods and materials on load side of the 
Class 2 power source. Class 2 cables installed as wiring within 
buildings shall be listed as being resistant to the spread of fire 
and listed as meeting the criteria specified in Sections 
E4203.2.1 through E4203.2.3. Cables shall be marked in 
accordance with Section E4203.2.4. Cable substitutions as 
described in Table E4203.2 and wiring methods covered in 
Chapter 37 shall also be permitted. 

TABLE E4203.2 
CABLE USES AND PERMITTED SUBSTITUTIONS 



CABLE 
TYPE 


USE 


PERMITTED SUBSTITUTIONS^ 


CL2P 


Class 2 
Plenum Cable 


CMP, CL3P 


CL2 


Class 2 Cable 


CMP, CL3P, CL2P, CMR, CL3R, 
CL2R CMC, CM, CL3 


CL2X 


Class 2 Cable, 
Limited Use 


CMP, CL3P CL2P, CMR, 
CL3R, CL2R, CMC, CM, 
CL3, CL2, CMX, CL3X 



a. For identification of cables other than Class 2 cables, see NFPA 70. 

E4203.2.1 Type CL2P cables. Cables installed in ducts, 
plenums and other spaces used to convey environmental air 
shall be Type CL2P cables listed as being suitable for the use 
and listed as having adequate fire-resistant and low 
smoke-producing characteristics. 

E4203.2.2 Type CL2 cables. Cables for general-purpose 
use, shall be listed as being resistant to the spread of fire and 
listed for the use. 

E4203.2.3 Type CL2X cables. Type CL2X Umited-use 
cable shall be listed as being suitable for use in dwellings 
and for the use and in raceways and shall also be listed as 
being flame retardant. Cables with a diameter of less than 
0.25 inches (6.4 mm) shall be permitted to be installed with- 
out a raceway. 

E4203.2.4 Marking. Cables shall be marked in accordance 
with Table E4203.2. Voltage ratings shall not be marked on 
cables. 



SECTION E4204 
INSTALLATION REQUIREMENTS 

E4204.1 Separation from other conductors. In cables, com- 
partments, enclosures, outlet boxes, device boxes, and race- 
ways, conductors of Class 2 circuits shall not be placed in any 
cable, compartment, enclosure, outlet box, device box, race- 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



545 



CLASS 2 REMOTE-CONTROL, SIGNALING AND POWER-LIMITED CIRCUITS 



way, or similar fitting with conductors of electric light, power, 
Class 1 and nonpower-limited fire alarm circuits. 

Exceptions: 

1. Where the conductors of the electric light, power. 
Class 1 and nonpower-limited fire alarm circuits are 
separated by a barrier from the Class 2 circuits. In 
enclosures. Class 2 circuits shall be permitted to be 
installed in a raceway within the enclosure to separate 
them from Class 1, electric light, power and 
nonpower-limited fire alarm circuits. 

2. Class 2 conductors in compartments, enclosures, 
device boxes, oudet boxes and similar fittings where 
electric light, power. Class 1 or nonpower-limited fire 
alarm circuit conductors are introduced solely to con- 
nect to the equipment connected to the Class 2 cir- 
cuits. The electric light, power, Class 1 and 
nonpower-limited fire alarm circuit conductors shall 
be routed to maintain a minimum of V4 inch (6.4 nmi) 
separation from the conductors and cables of the 
Class 2 circuits; or the electric light power, Class 1 
and nonpower-limited fire alarm circuit conductors 
operate at 150 volts or less to ground and the Class 2 
circuits are installed using Types CL3, CL3R, or 
CL3P or permitted substitute cables, and provided 
that these Class 3 cable conductors extending beyond 
their jacket are separated by a minimum of ^1^ inch 
(6.4 mm) or by a nonconductive sleeve or 
nonconductive barrier from all other conductors. 

E4204.2 Other applications. Conductors of Class 2 circuits 
shall be separated by not less than 2 inches (5 1 mm) from con- 
ductors of any electric light, power. Class 1 or nonpower-lim- 
ited fire alarm circuits except where one of the following 
conditions is met: 

1. All of the electric light, power. Class 1 and 
nonpower-limited fire alarm circuit conductors are in 
raceways or in metal- sheathed, metal-clad, nonmetal- 
lic-sheathed or Type UF cables. 

2. All of the Class 2 circuit conductors are in raceways or in 
metal-sheathed, metal-clad, nonmetallic- sheathed or 
Type UF cables. 

E4204.3 Class 2 circuits with communications circuits. 

Where Class 2 circuit conductors are in the same cable as com- 
munications circuits, the Class 2 circuits shall be classified as 
communications circuits and shall meet the requirements of 
Article 800 of NFPA 70. The cables shall be hsted as communi- 
cations cables or multipurpose cables. 

Cables constructed of individually listed Class 2 and com- 
munications cables under a common jacket shall be permitted 
to be classified as communications cables. The fire-resistance 
rating of the composite cable shall be determined by the perfor- 
mance of the composite cable. 

E4204.4 Class 2 cables with other circuit cables. Jacketed 
cables of Class 2 circuits shall be permitted in the same enclo- 
sure or raceway with jacketed cables of any of the following: 

1. Power-limited fire alarm systems in compliance with 
Article 760 of NFPA 70. 



2. Nonconductive and conductive optical fiber cables in 
compliance with Article 770 of NFPA 70. 

3 . Communications circuits in compliance v/ith Article 800 
of NFPA 70. 

4. Community antenna television and radio distribution 
systems in compliance with Article 820 of NFPA 70. 

5. Low-power, network-powered broadband communica- 
tions in compliance with Article 830 of NFPA 70. 

E4204.5 Installation of conductors and cables. Cables and 
conductors installed exposed on the surface of ceilings and 
sidewalls shall be supported by the building stnicture in such a 
manner that they will not be damaged by normal building use. 
Such cables shall be supported by straps, staples, hangers, or 
similar fittings designed so as to not damage the cable. The 
installation shall comply with Table E3702.1 regarding cables 
run parallel with framing members and furring: strips. The 
installation of wires and cables shall not prevent access to 
equipment nor prevent removal of panels, including suspended 
ceiling panels. Raceways shall not be used as a means of sup- 
port for Class 2 circuit conductors, except where the supporting 
raceway contains conductors supplying power to the function- 
ally associated equipment controlled by the Class 2 conduc- 
tors. 



546 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



Part IX— Referenced Standards 



CHAPTER 43 

REFERENCED STANDARDS 



This chapter hsts the standards that are referenced in various sections of this document. The standards are listed herein by the 
promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this 
document that reference the standard. The application of the referenced standard shall be as specified in Section R102.4. 



AAMA 



American Architectural Manufacturers Association 

1 827 Walden Office Square, Suite 550 

Schaumburg, IL 60173 

Referenced 
in code 

Title section number 

Specifications for Windows, Doors and Unit Skylights R308.6.9, R613.4, Nl 102.4.2 

Voluntary Performance Rating Method for Mulled Fenestration Assemblies R613.9.1 

Voluntary Specifications for Hurricane Impact and Cycle Testing of Fenestration Products R613.7.1 



Standard 
reference 
number 



101/I.S.2/A440- 

450—00 

506—00 



-05 



ACI 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



318—05 



332—05 
530—05 

530.1—05 



American Concrete Institute 
38800 Country Club Drive 
Farmington Hills, MI 48333 

jntle 

Building Code Requirements for Structural Concrete. R402.2, R404.1, Table R404.1.1(5), R404.4, R404.4.6.1, Table R404.4(l), 

Table R404.4(2), Table R404.4(3), Table R404.4(4), Table R404.4(5), R611.1, 

Table R61 1.3(1), Table R611.7(l), Table R61 1.7(2), Table R61 1.7(3), Table R61 1.7(4), 

Table R61 1.7(5), Table R61 1.7(6), Table R61 1.7(7), Table R61 1.7(9), 

Table R611.7(10),R611.7.1.1, Table R611.7.4,R612.1 

Requirements for Residential Concrete Construction R404.1, Table R404. 1 . 1 (5) 

Building Code Requirements for Masonry Structures R404.1, R606.1, R606.1.1, R606.12.1, 

R606. 12.2.2.1, R606.12.2.2.2, R606.12.3.1 

Specifications for Masonry Structures R404.1, R606.1, R606.1.1, 

R606.12.1, R606.12.2,2.1, R606.12.2.2.2, R606.12.3.1 



ACCA 



Air Conditioning Contractors of America 
2800 Shiriington Road, Suite 300 
Arlington, VA 22206 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



Manual D— 95 
Manual J— 02 



Residential Duct Systems 

Residential Load Calculation — Eighth Edition . 



.M1601.1,M1602.2 
M1401.3 



AFPA 



NDS— 05 
WFCM— 2001 



American Forest and Paper Association 
1 1 1 19th Street, NW, Suite 800 
Washington, DC 20036 



Standard 




Referenced 


reference 




in code 


number 


Tide 


section number 



National Design Specification (NDS) for Wood Construction — with 2005 Supplement 
Wood Frame Construction Manual for One- and Two-family Dwellings 



R404.2.2, R502.2, 

Table R503.1, R602.3, R802.2 
R301.2.1.] 



2003 INTERNATIONAL RESIDENTIAL CODE^ 



547 



REFERENCED STANDARDS 



AFPA— 93 
T.R. No. 7—87 



AFPA — continued 

Span Tables for Joists and Rafters 

Basic Requirements for Permanent Wood Foundation System 



.R502.3, R802.4, R802.5 
R401.1 



AHA 



American Hardboard Association 

1 2 1 West Northwest Highway 

Palatine, IL 60067 ; 

' Referenced 
' in code 

Title section number 

Basic Hardboard Table R602.3(l) 

Prefinished Hardboard Paneling R702.5 

Hardboard Siding i .Table R703.4 



Standard 
reference 
number 



A135.4— 04 
A135.5— 04 
A135.6— 98 



AISI 



Header — 04 
PM— 2001 

Truss— 04 



American Iron and Steel Institute 
1 140 Connecticut Ave, Suite 705 
Washington, DC 20036 

Title 

Standard for Cold-formed Steel Framing-Header Design R603.6 

Standard for Cold-formed Steel Framing-Prescriptive Method for One- and 

Two-family Dwellings (including 2004 Supplement) R301.1.1, R301.2.1.1(4), R301.2.2.4.1, R301.2.2.4.5 

Standard for Cold-formed Steel Framing-Truss Design R804.1.3 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



AITC 



American Institute of Timber Construction 
7012 S. Revere Parkway, Suite 140 
Englewood, CO 80112 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



AITC A 190.1—02 



Structural Glued Laminated Timber R502.1.5, R602.1.2, R802.1.4 



ANSI 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



A108.1A— 99 
A108.1B— 99 

A108.4— 99 
A108.5— 99 
A108.6— 99 
A108.il— 99 
Al 18.1— 99 
Al 18.3— 99 

A136.1— 99 
A137.1— 88 
A208.1— 99 
LCI— 97 

Z21.1— 03 



American National Standards Institute 
25 West 43rd Street, Fourth Floor 
New York, NY 10036 

Title 

Installation of Ceramic Tile in the Wet-set Method, with Portland Cement Mortar R702.4.1 

Installation of Ceramic Tile, Quarry Tile on a Cured Portland Cement Mortar Setting Bed with 

Dry-set or Latex-Portland Mortar R702.4.1 

Installation of Ceramic Tile with Organic Adhesives or Water Cleanable Tile-setting Epoxy Adhesive R702.4.1 

Installation of Ceramic Tile with Dry-set Portland Cement Mortar or Latex-Portland Cement Mortar R702.4. 1 

Installation of Ceramic Tile with Chemical Resistant, Water Cleanable Tile-setting and -grouting Epoxy : • ■ ■ ■ R702.4.1 

Interior Installation of Cementitious Backer Units : . . . .R702.4.1 

American National Standard Specifications for Dry-set Portland Cement Mortar R702.4.1 

American National Standard Specifications for Chemical Resistant, Water Cleanable Tile-setting and 

Grouting Epoxy and Water Cleanable Tile-setting Epoxy Adhesive i . . . .R702.4.1 

American National Standard Specifications for Organic Adhesives for Installation of Ceramic Tile J . . . . R702.4. 1 

American National Standard Specifications for Ceramic Tile R702.4.1 

Particleboard R503.3.1, R605.1 

Interior Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing ' 

—with Addenda LC la-1999 and LC lb-2001 [. . .G2414.5.3 

Household Cooking Gas Apphances— with Addenda Z21.1a-2003 and Z21.1b-2003 i G2447.1 



548 



2003 INTERNATIONAL RESIDENTIAL CODE® 



REFERENCED STANDARDS 



Z2 1.5. 1—02 
Z21.8— 94(R2002) 
Z21.10.1— 04 
Z21.10.3— 01 

Z21.11.2— 02 
Z21.13— 04 
Z21.15— 97(R2003) 

Z21.22— 99(R2003) 
Z2 1.24-97 

Z21.40.1— 96(R2002) 
Z21.40.2— 96(R2002) 

Z21.42— 93(R2002) 
Z2 1.47— 03 
Z2 1.50— 03 
Z21.56— 01 
Z21.58— 95(R2002) 
Z2 1.60— 03 
Z21.69— 02 
Z21.75/CSA6.27— 01 
Z2 1.80— 03 
Z2 1.84— 02 

Z2 1.86— 04 
Z2 1.88— 02 
Z21.91— 01 
Z83.6— 90(R1998) 
Z83.8— 02 
Z124.1— 95 
Z124.2— 95 
Z124.3— 95 
Z124.4— 96 
Z124.6— 97 



ANSI — continued 

Gas Clothes Dryers— Volume I— Type I Clothes Dryers— with Addenda Z21.5.1a-2003 G2438.1 

Installation of Domestic Gas Conversion Burners G2443. 1 

Gas Water Heaters — Volume I — Storage, Water Heaters with Input Ratings of 75,000 Btu per hour or Less G2448. 1 

Gas Water Heaters — Volume III — Storage, Water Heaters with Input Ratings above 75,000 Btu per hour, 

Circulating and Instantaneous Water Heaters— with Addenda Z21.10.3a-2003 and Z21.10.3b-2004 G2448.1 

Gas-fired Room Heaters— Volume II — Unvented Room Heaters — with Addenda Z2 1.1 1.2a- 2003 G2445.1 

Gas-fired Low-Pressure Steam and Hot Water Boilers G2452.1 

Manually Operated Gas Valves for Appliances, Appliance Connector Valves and Hose End Valves 
—with Addenda Z21.15a-2001 (R2003) G2420.1.1 

Relief Valves for Hot Water Supply Systems— with Addenda Z21.22a-2000 (R2003) and 21.22b-2001 (R2003) P2803.2 

Connectors for Gas Appliances G2422. 1 

Gas-fired Heat Activated Air Conditioning and Heat Pump Apphances — with Z21.40.1a-97(R2002) G2449.1 

Gas-fired Work Activated Air Conditioning and Heat Pump Appliances (Internal Combustion) 

—with Addenda Z2 1.40.2a- 1997 (R2002) G2449.1 

Gas-fired Illuminating Appliances G2450. 1 

Gas-fired Central Furnaces R617.1, G2442.1 

Vented Gas Fireplaces— with Addenda Z21.50a-2003 G2434.1 

Gas-firedPoolHeaters— with Addenda Z21.56a-2004 and Z21.56b— 2004 R616.1, G2441.1 

Outdoor Cooking Gas Appliances— with Addenda Z21.58a-1998(R2002) and Z21.58b-2002 R622.1, G2447.1 

Decorative Gas Apphances for Installafion in Sohd Fuel Burning Fireplaces — with Addenda Z21.60a-2003 G2432.1 

Connectors for Movable Gas Appliances with Addenda Z21.69a — 2003 G2422.1 

Connectors for Outdoor Gas Appliances G2422. 1 

Line Pressure Regulators G2421 . 1 

Manually-listed, Natural Gas Decorative Gas Appliances for Installation in Solid Fuel Burning Fireplaces 

—with Addenda Z21.84a -2003 G2432.1, G2432.2 

Gas-fired Vented Space Heating Appliances G2436. 1 , G2437.1, G2446.1 

Vented Gas Fireplace Heaters— with Addenda A21.88a-2003 and Z2 1.88b— 2004 G2435.1 

Ventless Firebox Enclosures for Gas-fired Unvented Decorative Room Heaters G2445.7.1 

Gas-fired Infrared Heaters G2442.1, G2449.1, G2451.1 

Gas-fired Unit Heaters and Gas-fired Duct Furnaces— with Addenda Z83.8a-2003 G2444. 1 

Plastic Bathtub Units Table P2701.1 

Plastic Shower Receptors and Shower Stalls Table P2701.1 

Plastic Lavatories Table P2701.i, P2711.1, P271I.2 

Plastic Water Closet Bowls and Tanks Table P2701.1, P27 12.1 

Plastic Sinks Table P2701.1 



APA 



APA-The Engineered Wood Association 
PO. Box 11700 
Tacoma,WA 98411-0700 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



APA E30— 03 



Engineered Wood Construction Guide R503.2.2, R803.2.2, R803.2.3 



ASCE 



5—05 

6—05 
7—05 
32—01 



American Society of Civil Engineers 
1801 Alexander Bell Drive 
Reston, VA 20191 

Title 

Building Code Requirements for Masonry Structures R404.1, R606.1, R606.1.I, 

R606.12.1, R606.12.2.2.1, R606.12.2.2.2, R606.12.3.1 

Specifications for Masonry Structures R404.1, R606.1, R606.1.1, R606.12.1, R606.12.2.2.1, R606.12.2.2.2, R606.12.3.1 

Minimum Design Loads for Buildings and Other Structures R301.2.1.1 

Design and Construction of Frost Protected Shallow Foundations R403. 1.4.1 



Standard 




Referenced 


reference 




in code 


number 


Tide 


section number 



2003 INTERNATIONAL RESIDENTIAL CODE*" 



549 



REFERENCED STANDARDS 



ASHRAE 



American Society of Heating, Refrigerating 
and Air-Conditioning Engineers, Inc. 
1791 Tullie Circle, NE 
Atlanta, GA 30329 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



34—2004 
ASHRAE— 2004 



Designation and Safety Classification of Refrigerants 
ASHRAE Fundamentals Handbook— 2001 



.....M1411.1 

, Nl 102.1.3, M1502.6, P3001.2, P3002.3, P3101.4, P3103.2 



ASME 



American Society of Mechanical Engineers 

Three Park Avenue 

New York, NY 10016-5990 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



A 17. 1—2004 
A18.1— 2003 
A112.1.2— 1991(R2002) 
A112.1.3— 2000 
Al 12.3.1— 93 

Al 12.3.4—2000 
A112.4.1— 1993(R2002) 
Al 12.4.3— 1999 
A112.6.1M— 1997(R2002) 
Al 12.6.2— 2000 
All 2.6.3—2001 
A112.18. 1—2003 
Al 12.18.2— 2002 
A112.18.3M— 2002 
Al 12.18.6— 2003 
A112.19.1M— 1994(R1999) 
Al 12.19.2—2003 

A112.19.3M— 2000 
Al 12.19.4M— 1994(R1999) 
Al 12.19.5— 1999 
Al 12.19.6— 1995 
A112.19.7M— 1995 
A112.19.8M— 1987(R1996) 
A112.19.9M— 1991(R2002) 
Al 12. 19. 12— 2000 

A112.19.13— 2001 
A112.19.15— 2001 
Bl.20.1— 1983(R2001) 
B16.3— 1998 
B16.4— 1998 
B 16.9— 2003 
B16.il— 2001 
B16.12— 1998 
B16.15— 1985(R]994) 
B16.18— 2001 
B 16.22— 2001 
B 16.23—2002 
B 16.26— 1988 
B16.28— 1994 
B 16.29— 2001 
B 16.33— 2002 
B 16.44-01 
B36.10M— 2000 



Safety Code for Elevators R323. 1 

Safety Standard for Platforms and Stairway Chair Lifts R323.2 

Air Gaps in Plumbing Systems P2902.3.1, Table P2902.3 

Air Gap Fittings for Use with Plumbing Fixtures, Appliances, and Appurtenances Table P2701. 1, P2902.3.1 

Performance Standard and Installation Procedures for Stainless Steel Drainage Systems for Sanitary Storm 

and Chemical Applications Above and Below Ground : . . . Table P3002.1(l), Table P3002.1(2), P3002.2, P3002.3 

Macerating Toilet Systems and Related Components Table P2701.1, P3007.2.1 

Water Heater Relief Valve Drain Tubes P2803.6.2 

Plastic Fittings for Connecting Water Closets to the Sanitary Drainage System P3003.19, P3003.4.5 

Floor Affixed Supports for Off-the-floor Plumbing Fixtures for Public Use P2702.4, Table P2704.1 

Framing- Affixed Supports for Off-the-floor Water Closets with Concealed Tanks Table P2701.1, P2702.4 

Floor and Trench Drains Table P2701. 1 

Plumbing Fixture Fittings Table P2701.1, P2708.4, P2722.1, P2902.2 

Plumbing Fixture Waste Fittings Table P2701.1, P2702.2 

Performance Requirements for Backflow Protection Devices and Systems in Plumbing Fixture Fittings .... P2708.4, P2722.3 

Flexible Water Connectors P2904.7 

Enameled Cast Iron Plumbing Fixtures— with 1998 and 2000 Supplements Table P2701.1, P2711.] 

Vitreous China Plumbing Fixtures — and Hydraulic Requirements 

for Water Closets and Urinals Table P2701.1, P2705.1, P2711.1, P2712.1, P2712.2 

Stainless Steel Plumbing Fixtures (Designed for Residential Use)— with 2002 Supplement. . Table P2701.1, P2705.1, P2711.1 

Porcelain Enameled Formed Steel Plumbing Fixtures— with 1998 and 2000 Supplements Table P2701.1, P2711.1 

Trim for Water-closet Bowls, Tanks, and Urinals Table P2701.1 

Hydraulic Performance Requirements for Water Closets and Urinals Table P2701.1, P2712.1, P2712.2 

Whirlpool Bathtub Appliances Table P2701.1 

Suction Fittings for Use in Swimming Pools, Wading Pools, Spas, Hot Tubs, and Whirlpool Bathtub Appliances . . Table P270] . 1 

Non-vitreous Ceramic Plumbing Fixtures— with 2002 Supplement Table P2701.1, P27.1 1.1, P2712.1 

Wall Mounted and Pedestal Mounted, Adjustable and Pivoting Lavatory and 

Sink Carrier Systems Table P2701.1, P2711.4, P2714.2 

Electrohydrauhc Water Closets P2712.9 

BathtubAVhirlpool Bathtubs with Pressure Sealed Doors Table P2701.1, P2713.2 

Pipe Threads, General Purpose (Inch) G2414.9, P3003.3.3, P3003.5.3, P3003.10.4, P3003.12.1, P3003.14.3 

Malleable Iron Threaded Fittings Classes 150 and 300 Table P2904.6 

Gray-iron Threaded Fittings Classes 125 and 250 Table P2904.6 

Factory-made Wrought Steel Buttwelding Fittings Table P2904.6 

Forged Fittings, Socket-welding and Threaded Table P2904.6 

Cast Iron Threaded Drainage Fittings Table P2904.6 

Cast Bronze Threaded Fittings Table P2904.6 

Cast Copper Alloy Solder Joint Pressure Fittings Table P2904.6 

Wrought Copper and Copper Alloy Solder Joint Pressure Fittings Table P2904.6 

Cast Copper Alloy Solder Joint Drainage Fittings (DWV) Table P2904.6, Table P3002.3 

Cast Copper Alloy Fittings for Flared Copper Tubes Table P2904.6 

Wrought Steel Buttwelding Short Radius Elbows and Returns Table P2904.6 

Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings-DWV Table P2904.6 Table P3002.3 

Manually Operated Metallic Gas Valves for Use in Gas Piping Systems up to 125 psig (Sizes 7, through 2) ...... . G2420.1.1 

Manually Operated Metallic Gas Valves For Use in House Piping Systems Table G2420. 1 . 1 

Welded and Seamless Wrought-steel Pipe \. . .G2414.4.2 



550 



2003 INTERNATIONAL RESIDENTIAL CODE'' 



REFERENCED STANDARDS 



BPVC— 2001 
CSD- 1—2002 



ASME — continued 

ASME Boiler and Pressure Vessel Code (2001 Edition) (Sections I, II, IV, V, VI & IX) M2001.] .1, G2452.1 

Controls and Safety Devices for Automatically Fired Boilers M200 1.1.1, G2452.1 



ASSE 



American Society of Sanitary Engineering 
28901 Clemens Road, Suite A 
Westlake, OH 44145 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



1001—02 
1002—99 

1003—01 
1006—89 
1007—92 
1008—89 
1010—96 
1011—93 
1012—02 

1013—99 

1014—90 
1015—99 

1016—96 

1017—99 
1019—97 

1020—98 
1023—79 
1024—04 
1025—78 

1035—02 
1037—90 
1047—99 

1048—99 

1050—02 
1051—02 

1052—93 
1056—01 
1062—97 

1066—97 
1070—04 



Performance Requirements for Atmospheric Type Vacuum Breakers Table P2902.3, P2902.3.2 

Performance Requirements for Antisiphen Fill 

Valves (Ballcocks) for Gravity Water Closet Flush Tank . Table P2701.1, Table P2902.3, P2902.4. 1 

Performance Requirements for Water Pressure Reducing Valves P2903.3.1 

Performance Requirements for Residential Use Dishwashers Table P2701.1 

Performance Requirements for Home Laundry Equipment Table P2701.1 

Performance Requirements for Household Food Waste Disposer Units Table P2701 . 1 

Performance Requirements for Water Hammer Arresters P2903.5 

Performance Requirements for Hose Connection Vacuum Breakers Table P2902.3, P2902.3.2 

Performance Requirements for Backflow Preventers with Intermediate Atmospheric Vent Table P2902.3 

P2902.3.3, P2902.5.1, P2902.5.5 

Performance Requirements for Reduced Pressure Principle Backflow Preventers and 

Reduced Pressure Fire Protection Principle Backflow Preventers Table P2902.3, P2902.5.5, P2902.5.1, P2902.5.5 

Performance Requirements for Hand-held Shower Table P2701. 1 

Performance Requirements For Double Check Backflow Prevention Assemblies and Double Check Fire 

Protection Backflow Prevention Assembhes Table P2902.3, P2902.3.6 

Performance Requirements for Individual Thermostatic, Pressure Balancing and 

Combination Control Valves for Bathing Facihties Table P2701.1, P2708.3, P2722.2 

Performance Requirements for Temperature Actuated Mixing Valves for Hot Water Distribution Systems P2802.2 

Performance Requirements for Wall Hydrants, Freezeless, Automatic 

Automatic Draining, Anti-backflow Types Table P2701 .1, Table P2902.3 

Performance Requirements for Pressure Vacuum Breaker Assembly Table P2902.3, P2902.3.4 

Performance Requirements for Hot Water Dispensers Household Storage Type Electrical Table P2701.1 

Performance Requirements for Dual Check Valve Type Backflow Preventers Table P2902.3 

Performance Requirements for Diverters for Plumbing Faucets with Hose Spray, 

Anti-siphon Type, Residential Applications Table P2701 .1 

Performance Requirements for Laboratory Faucet Backflow Preventers Table P2902.3, P2902.3.2 

Performance Requirements for Pressurized Flushing Devices for Plumbing Fixtures Table P270 1 . 1 

Performance Requirements for Reduced Pressure Detector Fire Protection Backflow 

Prevention Assembhes P2902.3.5, Table P2902.3 

Performance Requirements for Double Check Detector Fire Protection Backflow 

Prevention Assemblies P2902.3.6, Table P2902.3 

Performance Requirements for Stack Air Admittance Valves for Sanitary Drainage Systems P3 1 14. 1 

Performance Requirements for Individual and Branch Type Air Admittance Valves for Plumbing 

Drainage Systems P3 1 14. 1 

Performance Requirements for Hose Connection Backflow Preventers Table P270 1.1, Table P2902.3, P2902.3.2 

Performance Requirements for Spill Resistant Vacuum Table P2902.3, P2902.3.4 

Performance Requirements for Temperature Actuated, Flow Reduction Valves to 

Individual Fixture Fittings Table P2701.1, P2724.1 

Performance Requirements for Individual Pressure Balancing Valves for Individual Fixture Fittings . . Table P2701.1, P2722.4 
Performance Requirements for Water Temperature Limiting Devices P2713.3, P2721.2 



ASTM 



A 36/A 36M— 04 
A 53/A 53M--02 

A 74— 04 



ASTM International 

100 Barr Harbor Drive 

West Conshohocken, PA 19428 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Specification for Carbon Structural Steel R606.15 

Specification for Pipe, Steel, Black and Hot-dipped, Zinc-coated Welded and Seamless Table M2101.1, G24 14.4.2, 

Table P2904.4.1, Table P2904.5, Table P3002.1(l) 

Specification for Cast ton Soil Pipe and Fittings Table P3002.1(l), Table P3002.1(2), Table P3002.2 

Table P3002.3, P3005.2.9 



2003 INTERNATIONAL RESIDENTIAL CODE^ 



551 



REFERENCED STANDARDS 



A 106—04 

A 126—04 

A 153—03 

A 167—99 

A 197/A197M— 00 

A 240—04 

A 254—97(2002) 
A312/A312M— 04a 

A 377—03 
A463/A 463M-02a 
A510M— 03 
A 539—99 

A615/A0615M— 04a 
A641/A0641M— 03 
A 653/A 0653M— 04a 

A 706/A 706/M— 04a 

A 755/A 755M— 01 (2003) 

A 778—01 

A 792/A 792M— 03 

A 875/A 875M— 02a 

A 888—04 

A 924-04 

A 95 1—02 

A 996/A 996M— 04 

A 1003/A 1003M— 00 

B 32—03 
B 42— 02e01 
B 43—98(2004) 

B 75—02 

B 88—03 

B 101—02 
B 135—02 
B 209—04 
B 227—04 
B251— 02e01 

B 280—02 
B 302—02 
B 306—02 
B 370—03 
B 447—02 
B 633— 98e01 
B695— 00 
B 813— OOeOl 



ASTM — continued 

Specification for Seamless Carbon Steel Pipe for High Temperature Service Table M2101 .1, G2414.4.2 

Specification for Gray Iron Castings for Valves, Flanges and Pipe Fittings Table P3002.1(l) 

Specification for Zinc Coating (Hot Dip) on Iron and Steel Hardware R319.3, Table R606.15.1 

Specification for Stainless and Heat-resisting Chromium-nickel Steel Plate, Sheet, and Strip R606.15, Table R606.15.1 

Specification for Cupola Malleable Iron .Table P3002.1 

Standard Specification for Chromium and Chromium-nickel Stainless Steel 

Plate, Sheet and Strip for Pressure Vessels and for General Applications Table R905. 10.3(1) 

Specification for Copper Brazed Steel Tubing Table M2101.1, G2414.5.1 

Specification for Seamless and Welded Austenitic Stainless Steel Pipes Table P2904.4.1, Table P2904.5, 

Table P2904.6,P2904. 11.2 

Index of Specification for Ductile Iron Pressure Pipe Table P2904.4 

Standard Specification for Steel Sheet, Aluminum-coated by the Hot-Dip Process Table R905. 10.3(2) 

Specification for General Requirements for Wire Rods and Coarse Round Wire, Carbon Steel R606.15 

Specification for Electronic-resistance-welded Coiled Steel Tubing for Gas and Fuel Oil Lines M2202.1, G2414.5.1 

Specification for Deformed and Plain Billet-steel Bars for Concrete Reinforcement R404.4.6.1, R61 1.6.2 

Specification for Zinc-coated (Galvanized) Carbon Steel Wire Table R606.15.1 

Specification for Steel Sheet, Zinc-coated (Galvanized) or Zinc-iron Alloy-coated (Galvanized) 

by the Hot-dip Process R505.2.1, R505.2.3, R603.2.1, R603.2.3, Table R606.15.1, 

R804.2.1,R804.2.3, Table R905.10.3(l) M1601.1.1 

Specification for Low-alloy Steel Deformed and Plain Bars for Concrete Reinforcement R404.4.6.1, R61 1.6.2 

Specification for Steel Sheet, Metallic Coated by the Hot-dip Process and Prepainted by the 

Coil-coating Process for Exterior Exposed Building Products Table R905. 10.3(2) 

Specification for Welded Unannealed Austenitic Stainless Steel 

Tubular Products Table P2904.4, Table P2904.5, Table P2904.6 

Specification for Steel Sheet, 55% Aluminum-zinc Alloy-coated by the 

Hot-dip Process R505.2.1, R603.2.1, R603.2.3, R804.2.1, R804.2.3 

Specification for Steel Sheet, Zinc-5%, Aluminum Alloy-coated by the Hot-dip Process R505.2.1, R505.2.3, 

R603.2.1, R603.2.1, R603.2.3, R804.2.1, 
R804.2.3, Table R905. 10.3 
Specification for Hubless Cast Iron Soil Pipe and Fittings for Sanitary and 

Storm Drain, Waste, and Vent Piping Apphcation Table P3002.1(l), Table P3002.1(2), 

Table P3002.2, Table P3002.3, P3005.2.9 
Standard Specification for General Requirements for Steel Sheet, 

Metallic-Coated by the Hot-Dip Process Table .R905. 10.3(1) 

Specification for Masonry Joint Reinforcement R606.15 

Specifications for Rail-Steel and Axel-Steel Defomied Bars for Concrete Reinforcement R404.4.6.1, R61 1.6.2 

Standard Specification for Steel Sheet, Carbon, Metallic- 

and Nonmetallic-Coated for Cold-formed Framing Members R505.2.1, R603.2.1, R804.2.1 

Specification for Solder Metal P3003.10.3, P3003.11.3 

Specification for Seamless Copper Pipe, Standard Sizes Table M2101.1, G2413.5.2, Table P2904.5, Table P3002.1(l) 

Specification for Seamless Red Brass Pipe, Standard Sizes Table M2101.1, G2413.5.2, Table P2904.4, 

Table P2904.5, Table P3002. 1(1) 

Specification for Seamless Copper Tube Table M2101.1, Table P2904.4, Table P2904.5, 

Table P3002.1(l), Table P3002.1(2), Table P3002.2 

Specification for Seamless Copper Water Tube Table M2101.1, G2414.5.2, Table P2904.4, Table P2904.5, 

Table P3002.1(l), Table P3002.1(2), Table P3002.2 

Specification for Lead-Coated Copper Sheet and Strip for Building Construction Table R905. 10.3(1) 

Specification for Seamless Brass Tube Table M2 101.1 

Specification for Aluminum and Aluminum-alloy Sheet and Plate Table 905.10.3(1) 

Specification for Hard-drawn Copper-clad Steel Wire R606.15 

Specification for General Requirements for Wrought Seamless Copper and 

Copper-alloy Tube Table M2101.1, Table P2904.4,j Table P2904.5 

Table P3002.1(l), Table P3002. 1(2),: Table P3002.2 

Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service G2414.5.2 

Specification for Threadless Copper Pipe, Standard Sizes Table M2101.1, Table P2904.5, Table P3002.1(l) 

Specification for Copper Drainage Tube (DWV) Table M2101.1, Table P3002.1(l), Table P3002. 1(2), Table P3002.2 

Specification for Copper Sheet and Strip for Building Construction Table R905. 10.3(1),: Table P2701.1 

Specification for Welded Copper Tube Table P2904.4,; Table P2904.5 

Specification for Electrodeposited Coatings of Zinc on Iron and Steel R505.2.4, R603.2.4, R804.2.4 

Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and Steel R319.3 

Specification for Liquid and Paste Fluxes for Soldering Applications of 

Copper and Copper Alloy Tube Table M2101.1, P2904.13, P3003.3.4 

P3003.16.3, P3003.11.3 



552 



2003 INTERNATIONAL RESIDENTIAL CODE' 



,® 



REFERENCED STANDARDS 



B 



B— 02 



C5— 03 

C 14—03 

C 27—98(2002) 

C 28/C28M— OOeOl 

C34— 03 

C 35—95(2001) 

C 36/C 0036M— 03 

C 37/C 0037M— 01 

C55— 03 

C 59/C 0059M— 00 

C61/C0061M— 00 

C 62—04 

C 67-03ae01 

C 73-99a 

C 76— 04a 

C79/C 79— 04a 

C 90—03 

C 129—03 

CI 40— 03 

C 143/C 0143M— 03 

C 145—85 

C 199—84(2000) 

C 207—04 

C 208—95(2001) 

C 21 6— 04a 

C 270—04 

C 296—00 

C 315—02 

C 406—00 

C 41 1—97 

C 425—04 

C428— 97(2002) 

C 443—03 

C 475/C 475M— 02 

C 476—02 

C 514—01 

C552— 03 

C 557—03 

C564— 04a 

C 578—04 

C 587—02 

C 588/C 588M— 01 

C 630/0630M— 03 

C 631— 95a (2000) 

C 645—04 

C 652— 04a 

C 700—02 

C 728—97'-' 

C 836—03 

C 843— 99e01 
C 844—99 
C 847— (2000) 
C 887—79(2001) 
C 897-00 
C926— 98a 
C931/C931M— 04 



ASTM— continued 

Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings P2904.13, 

P3003.10.3,P3003.11.3 

Specification for Quicklime for Structural Purposes R702.2 

Specification for Concrete Sewer, Storm Drain and Culvert Pipe Table P3002.2 

Specification for Standard Classification of Fireclay and High-alumina Refractory Brick RlOOl .5, RlOOl .8 

Specification for Gypsum Plasters R702.2 

Specificadon for Structural Clay Load-Bearing Wall Tile Table R301 .2(1) 

Specificafion for Inorganic Aggregates for Use in Gypsum Plaster R702.2 

Specificafion for Gypsum Wallboard R702.3. 1 

Specification for Gypsum Lath R702.2 

Specification for Concrete Brick R202, Table R301.2(l) 

Specification for Gypsum Casting and Molding Plaster R702.2 

Specification for Gypsum Keene's Cement R702.2 

Specification for Building Brick (Solid Masonry Units Made from Clay or Shale) R202, Table R301 .2(1) 

Test Methods of Sampling and Testing Brick and Structural Clay Tile R905.3.5 

Specification for Calcium Silicate Face Brick (Sand Lime Brick) R202, Table R301.2(l) 

Specification for Reinforced Concrete Culvert, storm Drain, and Sewer Pipe Table P3002.2 

Specification for Treated Core and Nontreated Core Gypsum Sheathing Board Table R602.3(l), R702.3.1 

Specification for Load-bearing Concrete Masonry Units Table R301.2(l) 

Specification for Nonload-bearing Concrete Masonry Units Table R30 1.2(1) 

Test Methods of Sampling and Testing Concrete Masonry Units and Related Units R905.3.5 

Test Method for Slump or Hydraulic Cement Concrete R404.4.5, R611.6.] 

Specification for Solid Load-bearing Concrete Masonry Units R202, Table R30 1.2(1) 

Test Method for Pier Test for Refractory Mortar R1001.9, R1003.5, R1003.8 

Specification for Hydrated Lime for Masonry Purposes Table R607.1 

Specification for Cellulosic Fiber Insulating Board Table R602.3(l) 

Specification for Facing Brick (Solid Masonry Units Made from Clay or Shale) R202, Table R301.2(l) 

Specification for Mortar for Unit Masonry R607. 1 

Specification for Asbestos Cement Pressure Pipe Table P2904.4 

Specification for Clay Flue Linings Table RlOOl. 1 1(1), Table RlOOl. 11(2), RlOOl. 8.1, G2425. 12 

Specifications for Roofing Slate R905.6.4 

Test Method for Hot-surface Performance of High-temperature Thermal Insulation M 1 60 1 .2 . 1 

Specification for Compression Joints for Vitrified Clay Pipe and Fittings Table P3002.2, 

P3003.15,P3003.18 

Specification for Asbestos-Cement Nonpressure Sewer Pipe Table P3002.2 

Specification for Joints for Concrete Pipe and Manholes, Using Rubber Gastets P3003.7, P3003.18 

Specification for Joint Compound and Joint Tape for Finishing Gypsum Wallboard R702.3.1 

Specification for Grout for Masonry R609. 1 . 1 

Specification for Nails for the Application of Gypsum Wallboard R702.3.1 

Standard Specification for Cellular Glass Thermal Insulation Table R906.2 

Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing R702.3. 1 

Specification for Rubber Gaskets for Cast Iron Soil Pipe and Fittings P3003.6.2, P3003.6.3, P3003.1 8 

Specification for Rigid, Cellular Polystyrene Thermal Insulation R403.3, Table R906.2 

Specification for Gypsum Veneer Plaster R702.2 

Specification for Gypsum Base for Veneer Plasters R702.2 

Specification for Water-resistant Gypsum Backing Board R702.3.1, R702.4.2 

Specification for Bonding Compounds for Interior Gypsum Plastering R702.2 

Specification for Nonstructural Steel Framing Members R702.3.3 

Specification for Hollow Brick (Hollow Masonry Units Made from Clay or Shale) R202, Table R30 1.2(1) 

Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated Table P3002.2 

Standard Specification for Perlite Thermal Insulation Board Table R906.2 

Specification for High Solids Content, Cold Liquid- Applied Elastomeric Waterproofing 

Membrane for Use with Separate Wearing Course R905. 1 5.2 

Specification for Application of Gypsum Veneer Plaster R702.2 

Specification for Application of Gypsum Base to Receive Gypsum Veneer Plaster R702.2 

Specification for Metal Lath R702.2 

Specification for Packaged, Dry, Combined Materials for Surface Bonding Mortar R406. 1 

Specification for Aggregate for Job-mixed Portland Cement-based Plasters R702.2 

Specification for Application of Portland Cement Based-Plaster R703.6 

Specification for Exterior Gypsum Soffit Board R702.3.1 



2003 INTERNATIONAL RESIDENTIAL CODE'' 



553 



REFERENCED STANDARDS 



C 933—04 
C 954—00 

C955— 03 

C 957—04 

C 960/C960M— 04 
C 1002—01 

C 1029—02 
C 1032—04 
C 1047—99 
C 1063—03 
C 1157—03 
C 1167—03 
C 1173—02 

C1177/C1177M— 04 
C1178/C1178M— 04 
C 1186—02 
C 1261—04 
C 1277—04 

C 1278/C 1278M— 03 

C1283— 03e01 

CI 288— 01 

CI 289— 03 

C 1325—04 

C 1395/C 1395M— 04 

C 1396M— 04 

C 1440-99e01 

C 1460—04 

C 1461—02 

C 1492—03 
D41— eOl 
D 43-00 
D 225—04 
D 226— 97a 

D 227—03 

D 312-00 

D 422—63(2002) 

D 449—03 

D 450— 96(00)e01 

D 1227-00 

D 1248—02 

D 1527— 99e01 

D 1693—01 

D 1784—04 

D 1785—04 
D 1863—03 
D 1869—95(2000) 
D 1970—01 



ASTM— continued 

Specification for Welded Wire Lath ' R702.2 

Specification for Steel Drill Screws for the Application of Gypsum 

Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 

0.1 12 in. (2.84 mm) in Thickness R505.2.4, R603.2.4, R702.3.6, R804.2.4 

Specification for Load-Bearing (Transverse and Axial) Steel Studs, Runners (Tracks), and Bracing or 

Bridging for Screw Application of Gypsum Panel Products and Metal Plaster Bases R702.3.3 

Specification for High-solids Content, Cold Liquid- Applied Elastomeric Waterproofing 

Membrane for Use with Integral Wearing Surface R905.15.2 

Specification for Predecorated Gypsum Board R702.3.1 

Specification for Steel Drill Screws for the Application of Gypsum Panel Products or 

Metal Plaster Bases R702.3.1, R702.3.6, Table R702.3.4 

Specification for Spray- Applied Rigid Cellular Polyurethane Thermal Insulation R905.14.2 

Specification for Woven Wire Plaster Base : R702.2 

Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base R702.2, R702.3.1 

Specification for Installation of Lathing and Furring to Receive Interior and Exterior Portland Cement-Based Plaster . . R702.2 

Performance Specification for Hydraulic Cements R402.2 

Specification for Clay Roof Tiles R905.3, R905.3.4, R905.3.5 

Specification for Flexible Transition Couphngs for Underground Piping Systems P3003.3, P3003.3.5, P3003.7, 

P3003.8.1, P3003.14.1, P3003.15, P3003.17.2, P3003.18 

Specification for Glass Mat Gypsum Substrate for Use as Sheathing : R702.3.1 

Specification for Glass Mat Water-Resistant Gypsum Backing Panel R702.3.1, R702.3.8, R702.4.2 

Specification for Flat Nonasbestos Fiber Cement Sheets R703.4 

Specification for Firebox Brick for Residential Fireplaces R1001.5, R1001.8 

Specification for Shielded Couplings Joining Hubless 

Cast Iron Soil Pipe and Fittings Table P3002.1, Table P3002.2, P3003.6.3 

Specification for Fiber-Reinforced Gypsum Panels R702.3.1 

Practice for Installing Clay Flue Lining , R1003.12 

Standard Specification for Discrete Non-asbestos Fiber-Cement Interior Substrate Sheets R702.4.2 

Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board Table R906.2 

Standard Specification for Non-abestos Fiber-Mat Reinforced Cement Interior Substrate Sheets R702.4.2 

Specification for Gypsum Ceiling Board R702.3.1 

Specification for Gypsum Board R702.3.1 

Specification for Thermoplastic Elastomeric (TPE) Gasket Materials for Drain, Waste 

and Vent (DWV), Sewer, Sanitary and Storm Plumbing Systems P3003.18 

Specification for Shielded Transifion Couplings for Use with Dissimilar DWV Pipe and 

Fittings Above Ground Table P3002.1, Table P3002.2, P3003.18 

Specification for Mechanical Couplings Using Thermoplastic Elastomeric (TPE) Gaskets for Joining Drain, 

Waste, and Vent (DWV) Sewer, Sanitary and Storm Plumbing Systems for Above and 

Below Ground Use Table P3002.'l, Table P3002.2, P3003.18 

Specification for Concrete Roof Tile R905.3.5 

Specification for Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing Table R905.9.2, Table R905.1 1.2 

Specification for Coal Tar Primer Used in Roofing, Damproofing and Waterproofing Table R905.9.2 

Specificadon for Asphalt Shingles (Organic Felt) Surfaced with Mineral Granules R905.2.4 

Specificadon for Asphalt-Saturated (Organic Felt) Used in Roofing and Waterproofing R703.2, R703.9.1, Table R905.2.3, 

R905.4.3, R905.5.3, R905.5.4, R905.6.3, R905.7.3, R905.8.3, R905. 8.4, Table 905.9.2 

Specification for Coal Tar Saturated (Organic Felt) Used in Roofing and Waterproofing Table R905.9.2 

Specification for Asphalt Used in Roofing Table R905.9.2 

Test Method for Particle-size Analysis of Soils R403.1.7.5.1 

Specification for Asphalt Used in Dampproofing and Waterproofing R406.2 

Specification for Coal-Tar Pitch Used in Roofing , Dampproofing and Waterproofing Table R905.9.2 

Specification for Emulsified Asphalt Used as a Protective Coating for Roofing . . Table R905.9.2, Table R905.U.2, R905.15.2 

Specification for Polyethylene Plastics Extrusion Materials for Wire and Cable ' ... M 1 60 1 . 1 .2 

Specificadon for Acrylonite-Butadiene-Styrene (ABS) Plastic Pipe, Schedules 40 and 80 Table P2904.4 

Test Method for Environmental Stress-cracking of Ethylene Plastics Table M2 101.1 

Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and 

Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds M1601.1.2 

Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80 and 120 '. Table P2904.4 

Specificadon for Mineral Aggregate Used in Built-up Roofs Table R905.9.2, Table R906.3.2 

Specification for Rubber Rings for Asbestos-cement Pipe P2904.17, P3003.4, P3003.18 

Specification for Self-adhering Polymer Modified Bitumen Sheet Materials Used as 

Steep Roofing Underlayment for Ice Dam Protection R905.2.3, R905.2.8.3 



554 



2003 INTERNATIONAL RESIDENTIAL CODE'' 



REFERENCED STANDARDS 



D 2104—03 
D 2178— 97a 
D 2235—01 

D 2239—03 
D 2241— 04a 
D 2282— 99e01 
D 2412—02 
D 2447—03 
D 2464—99 
D 2466—02 
D 2467—04 
D 2468— 96a 
D 25 13— 04a 

D 2564—02 

D 2609—02 
D 2626—04 
D 2657—97 
D 2661—02 

D 2662— 96a 
D 2665— 04ae01 

D 2666— 96a(2003) 
D 2672—03 
D 2683—98 

D 2737—03 

D 2751— 96a 

D 2822— 91(1 997)e01 

D 2823— 90(1 997)e' 

D 2824—04 

D 2837—04 

D 2846/D 2846M— 99 

D 2855-96(2002) 

D 2898—94(1999) 
D 2949— Ola 

D 3019— eOl 

D 3034—04 
D 3035— 03a 
D 3161— 03b 
D 3201—94(2003) 
D3212— 96a(2003) 

D 3309— 96a(2002) 

D 3311—02 
D 3350— 02a 
D 3462—04 
D 3468—99 

D 3679—04 



ASTM — continued 

Specification for Polyethylene (PE) Plastic Pipe, Schedule 40 Table P2904.4 

Specification for Asphalt Glass Felt Used in Roofing and Waterproofing Table R905.9.2 

Specification for Solvent Cement for Acrylonitrile-Butadiene-Styrene 

(ABS) Plastic Pipe and Fittings P2904.9.1.1, Table P3002.1, Table P3002.2 

P3003.3.2, P3003.8.2 

Specification for Polyethylene (PE) Plastic Pipe (SIDR-PR) Based on Controlled Inside Diameter Table P2904.4 

Specificafion for Poly (Vinyl Chloride) (PVC) Pressure-rated Pipe (SDR-Series) Table P2904.4 

Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR) Table P2904.4 

Test Method for Determination of External Loading Characteristics of Plastic Pipe by I^allel-plate Loading Ml 60 1.1.2 

Specification for Polyethylene (PE) Plastic Pipe Schedules 40 and 80, Based on Outside Diameter Table M2 101.1 

Specification for Threaded Poly (Vmyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80 Table P2904.6 

Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40 Table P2904.6 

Specification for Poly (Vmyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80 Table P2904.6 

Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe Fittings, Schedule 40 Table P2904.6 

Specification for Thermoplastic Gas Pressure Pipe, Tubing, and Fittings Table M2101.1, M2104.2.1.3, G2414.6, 

G2414.6.1, G2414.1 1, G2415.14.3 
Specification for Solvent Cements for Poly (Vmyl Chloride) (PVC) 

Plastic Piping Systems P2904.9.1.3, Table P3002.1, Table P3002.2 

P3003.9.2, P3003.14.2 

Specification for Plastic Insert Fittings for Polyethylene (PE) Plastic Pipe Table P2904.6 

Specification for Asphalt-Saturated and Coated Oiganic Felt Base Sheet Used in Roofing R905.3.3, Table R905.9.2 

Standard Practice for Heat Fusion-joining of Polyolefin Pipe Fittings P2904.3.1, P3003.17.1 

Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, 

Waste, and Vent Pipe and Fittings Table P3002.1(l), Table P3002.1(2), Table P3002.2, Table P3002.3, 

Table P3002.4, P3003.3.2, P3003.8.2 

Specification for Polybutylene (PB) Plastic Pipe (SDR-PR) Based on Controlled Inside Diameter Table P2904.4 

Specification for Poly (Vmyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings Table P3002.1(l) 

Table P3002.1(2), Table P3002.2, P3002.3, Table P3002.4 

Specification for Polybutylene (PB) Plastic Tubing Table P2904.4 

Specification for Joints for IPS PVC Pipe Using Solvent Cement Table P3002.1, Table, P3002.2, Table P2904.4 

Specification for Socket-Type Polyethylene Fittings for Outside Diameter-controlled 

Polyethylene Pipe and Tubing Table M2101 .1, M2104.2.] .1 

Specification for Polyethylene (PE) Plastic Tubing Table P2904.4 

Specification for Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe and Fittings Table P3002.2, Table P3002.3 

Specification for Asphalt Roof Cement Table R905.9.2, Table R905.] 1.2 

Specification for Asphalt Roof Coatings Table R905.9.2, Table R905. 1 1 .2 

Specification for Aluminum-Pigmented Asphalt Roof Coatings, Non-fibered, Asbestos Fibered, 

and Fibered without Asbestos Table R905.9.2, Table R905.11.2 

Test Method for Obtaining Hydrostatic Design Basis for Thermoplastic Pipe Materials Table M2101.1 

Specification for Chlorinated Poly (Vmyl Chloride) (CPVC) Plastic Hot- and 

Cold-water Distribution Systems Table M2101.1, Table P2904.4, Table P2904.5, P2904.9.1.2 

Standard Practice for Making Solvent-Cemented Joints with Poly (Vmyl Chloride) (PVC) 

Pipe and Fittings P3003.9.2, P3003.14.2 

Test Methods for Accelerated Weathering of Fire-retardant-treated Wood for Fire Testing R802. 1.3.3, R902.2 

Specification for 3.25-in. Outside Diameter Poly (Vmyl Chloride) (PVC) Plastic Drain, 

Waste, and Vent Pipe and Fittings Table P3002.I(1), Table P3002.1(2), Table P3002.2, Table P3002.3 

Specification for Lap Cement Used with Asphalt Roll Roofing, Non-fibered, Asbestos Fibered, 

and Non-asbestos Fibered Table R905.9.2, Table R905.1 1.2 

Specification for Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings . . . Table P3002.2, P3002.3, Table P3002.4 

Specification for Polyethylene (PE) Plastic Pipe (DR-PR) Based On Controlled Outside Diameter Table M2101.1 

Test Method for Wind Resistance of Asphalt Shingles (Fan Induced Method) R905.2.4. 1 , R905.2.6 

Test Method for Hygroscopic Properties of Fire-retardant Wood and Wood-base Products R802. 1.3.4 

Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals Table P3002.2, P3003.3.1, 

P3003.8.1, P3003.9.1, P3003.14.1, P3003.17.2 
Specification for Polybutylene (PB) Plastic Hot- and 

Cold-water Distribution Systems Table M2101.1, Table P2904.4, Table P2904.5 

Specification for Drain, Waste, and Vent (DWV) Plastic Fittings Patters P3002.3 

Specification for Polyethylene Plastic Pipe and Fitting Materials Table M2101.1 

Specification for Asphalt Shingles Made From Glass Felt and Surfaced with Mineral Granules R905.2.4 

Specification for Liquid-applied Neoprene and Chlorosulfanated Polyethylene Used in 

Roofing and Waterproofing Table R905.15.2 

Specification for Rigid Poly (Vmyl Chloride) (PVC) Siding Table R703.4 



2003 INTERNATIONAL RESIDENTIAL CODE'' 



555 



REFERENCED STANDARDS 



D 3737—03 

D 3747— 79(2000)e01 

D 3909— 97b 

D 3957—03 

D 4022— 94(2000)e01 

D 4068—01 

D 4318—00 

D 4434—04 

D 4479-00 

D 4551—96(2001) 

D 4586-00 

D 4601—98 

D 4637—04 

D 4829—03 

D 4869—04 

D 4897—01 
D 4990— 97a 
D 5019-96 eOl 
D 5055—04 
D 5516—03 

D 5643— 94(2000)e01 
D 5664—02 

D 5665— 99a 
D 5726—98 
D 6083— 97a 
D 6162— 00a 

D 6163— OOeOl 

D 6164-00 

D 6221-00 
D 6222—02 

D 6223—02 

D 6298—00 

D 6305— 02e01 

D 6380—01" 
D 6694—01 
D 6754—02 
D 6757—02 
D 6841—03 

D 6878—03 
E84— 04 

E 96— OOeOl 
E 108—04 
E 119-00 
E 136— 99e01 
E 283—04 



ASTM— continued 

Practice for Establishing Allowable Properties for Structural Glued Lanunated Timber (Glulam) R502.1.5, R602.1.2, R802.1.4 

Specification for Emulsified Asphalt Adhesive for Adhering Roof Insulation Table R905.9.2, Table R905.11.2 

Specification for Asphalt Roll Roofing (Glass Felt) Surfaced 

with Mineral Granules R905.2.8.2, R905.3.3, R905.5.4, Table R905.9.2, Table R906.3.2, 

Standard Practices for Estabhshing Stress Grades for Structural 

Members Used in Log Buildings R502.1.6, FL602.1.3, R802.1.5 

Specification for Coal Tar Roof Cement, Asbestos Containing Table R905.9.2 

Specification for Chlorinated Polyethylene (CPE) Sheeting for Concealed Water Containment Membrane P2709.2.2 

Test Methods for Liquid Limit, Plastic Limit and Plasticity Index of Soils R403. 1 .7.5. 1 

Specification for Poly (Vinyl Chloride) Sheet Roofing R905.13.2 

Specification for Asphalt Roof Coatings-Asbestos-free Table R905.9.2 

Specification for Poly (Vinyl) Chloride (PVC) Plastic Flexible Concealed Water-containment Membrane P2709.2.1 

Specification for Asphalt Roof Cement-Asbestos-free Table R905.9.2 

Specification for Asphalt-coated Glass Fiber Base Sheet Used in Roofing Table R905.9.2 

Specification for EPDM Sheet Used in Single-ply Roof Membrane .R905.12.2 

Test Method for Expansion Index of Soils R403. 1.8.1 

Specification for Asphalt-Saturated (Organic Felt) Underlayment Used in Steep Slope Roofing R905.2.3, R905.4.3, 

R905.5.3, R905.6.3, R905.7.3, R905.8.3 

Specification for Asphalt Coated Glass-fiber Venting Base Sheet Used in Roofing Table R905.9.2 

Specification for Coal Tar Glass Felt Used in Roofing and Waterproofing Table R905.9.2 

Specification for Reinforced Non- Vulcanized Polymeric Sheet Used in Roofing Membrane R905.12.2 

Specification for Establishing and Monitoring Structural Capacities of Prefabricated Wood I- Joists R502.1.4 

Test Method for Evaluating the Flexural Properties of Fire-Retardant-treated Softwood 

Plywood Exposed to the Elevated Temperatures R802.1.3.2.1 

Specification for Coal Tar Roof Cement Asbestos-free Table R905.9.2 

Test Methods For Evaluating the Effects of Fire-Retardant Treatments and Elevated Temperatures on 

Strength Properties of Fire-retardant-treated Lumber R802. 1.3.2.2 

Specification for Thermoplastic Fabrics Used in Cold-applied Roofing and Waterproofing Table R905.9.2 

Specification for Thermoplastic Fabrics Used in Hot-applied Roofing and Waterproofing Table R905.9.2 

Specification for Liquid Applied Acrylic Coating Used in Roofing . Table R905.9.2, Table R905.1 1.2, Table R905.15.2 

Specification for Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials 

Using a Combination of Polyester and Glass Fiber Reinforcements Table R905.11.2 

Specification for Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials 

Using Glass Fiber Reinforcements Table R905.1 1 .2 

Specification for Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials 

Using Polyester Reinforcements Table R905.11.2 

Specification for Reinforced Bituminous Flashing Sheets for Roofing and Waterproofing Table R905.1 1.2 

Specification for Atactic Polypropelene (APP) Modified Bituminous Sheet Materials 

Using Polyester Reinforcement Table R905.11.2 

Specification for Atactic Polypropelene (APP) Modified Bituminous Sheet Materials 

Using a Combination of Polyester and Glass Fiber Reinforcement Table R905.1 1.2 

Specification for Fiberglass Reinforced Styrene-Butadiene-Styrene (SBS) Modified 

Bituminous Sheets with a Factory Appfied Metal Surface Table R905.1 1.2 

Practice for Calculating Bending Strength Design Adjustment Factors for Fire-Retardant- 

Treated Plywood Roof Sheathing : .R802.1.3.2.1 

Standard Specification for Asphalt Roll Roofing (Organic Felt) R905.2.8.2 

Standard Specification Liquid- Applied Silicone Coating Used in spray Polurethane Foam roofing' R905.15.2 

Standard Specification for Ketone Ethylene ester Based Sheet Roofing' R905.13.2 

Standard Specification for Inorganic Underlayment for Use with Steep Slope Roofing Products' R905.2.3 

Standard Practice for Calculating Design Value Treatment Adjustment Factors \ 

for Fire-retardant-treated Lumber .R802. 1.3.2.2 

Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing' .R905.13.2 

Test Method for Surface Burning Characteristics of Building Materials R202, R314.1.1, R3 14.2.6, 

R314.3, R315.3, R316.1, R316.2, 
R802.1.3, M1601.2.1, M1601.4.2 

Test Method for Water Vapor Transmission of Materials R202, R806.4, M141 1.4, M1601.3.4 

Test Methods for Fire Tests of Roof Coverings k902.1, R902.2 

Test Methods for Fire Tests of Building Construction and Materials R314.1.2, R317.1, R317.3.1 

Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C j R202 

Test Method for determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, 

and Doors Under specified Pressure Differences Across the Specimen '• R806.4 



556 



2003 INTERNATIONAL RESIDENTIAL CODE"" 



REFERENCED STANDARDS 



E 330—02 

E 331-00 

E 814—02 
E 970-00 
E 1509—04 
E 1602—03 
E 1886—04 

E 1996—04 

E 2231—04 

F 409—02 

F 437—99 
F 438—04 
F439— 02e01 
F441/F441M— 02 

F 442/F 442M— 99 
F 477— 02e01 
F 493—04 
F 628—01 

F 656— 02 

F 714—03 
F 789— 95a 

F 876— 04 
F 877— 02e01 

F891— OOeOl 

F 1055— 98e01 

F 1281—03 

F 1282—03 

F 1412—01 
F 1488—03 
F 1667—03 
F 1807—04 

F 1866—98 

F 1960—04 

F 1974—04 

F 1986— 00a 

F 2006—00 

F 2080—04 



ASTM— continued 

Test Method for Structural Performance of Exterior Windows, Curtain Walls, and 

Doors by Uniform Static Air Pressure Difference R613.3 

Test Method for Water Penetration of Exterior Windows, Skylights, Doors 

and Curtain Walls by uniform Static Air Pressure Difference R703.1 

Test Method for Fire Tests of Through-Penetration Firestops R317.3.1.2 

Test Method for Critical Radiant Flux of Exposed Attic Floor Insulation Using a Radiant Heat Eneigy Source R316.5 

Standard Specification for Room Heaters, Pellet Fuel-burning Type M1410.1 

Guide for Construction of Solid Fuel Burning Masonry Heaters R1002.2 

Test Method for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters 
Impacted by Missies and Exposed to Cyclic Pressure Differentials R301.2.1.2, R613.7.1 

Specification for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters 

Impacted by Windbome Debris in Hurricanes R301.2.1.2, R613.7.1 

Standard Practice for Specimen Preparation and Mounting of Pipe and Duct 

Insulation Materials to Assess Surface Burning Characteristics M1601.2.1 

Specification for Thermoplastic Accessible and Replaceable Plastic Tube and Tubular Fittings Table P2701.] , P2702.2, 

P2702.3 

Specification for Threaded Chlorinated Poly (Vmyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80 Table P2904.6 

Specification for Socket-type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40 Table P2904.6 

Specification for Socket-type Chlorinated Poly (Vmyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80 Table P2904.6 

Specification for Chlorinated Poly (Vmyl Chloride) (CPVC) Plastic Pipe, 
Schedules 40 and 80 Table P2904.4, Table P2904.5 

Specification for Chlorinated Poly (Vmyl Chloride) (CPVC) Plastic Pipe (SDR-PR) Table P2904.4, Table P2904.5 

Specification for Elastomeric Seals (Gaskets) for joining Plastic Pipe P2904.17, P3003.18 

Specification for Solvent Cements for Chlorinated Poly (Vmyl Chloride) (CPVC) Plastic Pipe and Fittings P2904.9.1 .2 

Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, 

and Vent Pipe with a Cellular Core Table 3002.1(1), Table P3002.1(2), Table P3002.2, 

Table P3002.3, P3003.3.2, P3003.8.2 

Specification for Primers for Use in Solvent Cement Joints of Poly (Vmyl Chloride) 

(PVC) Plastic Pipe and Fittings P2904.9.1.3, Table P3002.1, Table P3002.2, 

P3003.9.2, P3003.14.2 

Specification for Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Outside Diameter Table P3002.2 

Specification for Type PS-46 and Type PS-1 15 Poly (Vmyl Chloride) (PVC) 
Plastic Gravity Flow Sewer Pipe and Fittings Table P3002.2 

Specification for Cross-linked Polyethylene (PEX) Tubing Table M2101.1, Table P2904.4 

Specification for Cross-linked Polyethylene (PEX) Plastic Hot- and 

Cold-water Distribution Systems Table M2101.1, Table P2904.4, 

P2904.9. 1.4.2, Table P2904.5, Table 2904.6 

Specification for Coextruded Poly (Vinyl Chloride) (PVC) Plastic Pipe 

with a Cellular Core Table P3002.1(l), Table P3002.1(2), 

Table P3002.2, Table 3002.3, Table P3002.4 

Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter 

Controlled Polyethylene Pipe and Fittings Table M2101.1, M2104.2.1.2 

Specification for Crosshnked Polyethylene/ Aluminum/Crosslinked 
Polyethylene (PEX-AL-PEX) Pressure Pipe Table M2101.1, Table P2904.4, Table P2904.5 

Specification for Polyethylene/Aluminum/Polyethylene (PE-AL-PE) 
Composite Pressure Pipe Table P2904.4, Table P2904.5 

Specification for Polyolefin Pipe and Fittings for Corrosive Waste Drainage Table P3002.2, Table P3002.3, P3003. 16.1 

Specification for Coextruded Composite Pipe Table P3002.1(l), Table P3002.1(2), Table P3002.2 

Specification for Driven Fasteners, Nails, Spikes, and Staples R905.2.5 

Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR9 

Cross-linked Polyethylene (PEX) Tubing Table M2101.1, Table P2904.6, P2904.9. 1.4.2 

Specification for Poly (Vmyl Chloride) (PVC) Plastic Schedule 40 Drainage 

and DWV Fabricated Fittings Table P3002.4 

Specification for Cold Expansion Fittings with PEX Reinforcing Rings for Use with 

Cross-Hnked Polyethylene (PEX) Tubing Table M2101.1, Table P2904.6, P2904.9.1.4.2 

Specification for Metal Insert Fittings for Polyethylene/ Aluminum/Polyethylene and Crosslinked 
Polyethylene/ Aluminum/Crosslinked Polyethylene Composite Pressure Pipe Table P2904.6 

Multilayer Pipe Type 2, Compression Joints for Hot and Cold Drinking Water Systems Table P2904.4, 

Table P2904.5, Table P2904.6 
Standard/Safety Specification for Window Fall Prevention Devices for Non-Emergency 
Escape (Egress) and Rescue (Ingress) Windows R613.2 

Specification for Cold-expansion Fittings with Metal Compression-Sleeves for 
Crosslinked Polyethylene (PEX) Pipe P2904.6, P2904.9.1 .4.2 



2003 INTERNATIONAL RESIDENTIAL CODE^ 



557 



REFERENCED STANDARDS 



F 2090— 01 A 

F 2098—01 
F 2389—04 



ASTM— continued 

Specification for Window Fall Prevention Devices 

— with Emergency Escape (Egress) Release Mechanisms 613.2 

Standard Specification for Stainless Steel Clamps for SDR9 PEX Tubing to Metal Insert Fittings Table M2101.1 

Standard for Pressure-rated Polypropylene (PP) Piping Systems Table M2101.1, Table P2904.4, Table P2904.5, 

Table P2904.6,P2904. 10.1 



AWS 



American Welding Society 
550 N. W. LeJeune Road 
Miami, FL 33126 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



A5.8— 04 



Specifications for Filler Metals for Brazing and Braze Welding P3003.5.1, P3003.10.1, P3003.1 1.1 



AWPA 



American Wood-Preservers' Association 
RO. Box 5690 
Granbury, Texas 76049 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



CI — 100 All Timber Products — Preservative Treatment by Pressure Processes R902.2 

C33 — 00 Standard for Preservative Treatment of Structural Composite Lumber by Pressure Processes R324.1 

M4— 02 Standard for the Care of Preservative-treated Wood Products R319.1.1, R320.1.2, R320.3.1 

Ul— 04 USE CATEGORY SYSTEM: User Specification for Treated Wood 

Except Section 6 Commodity Specification H R319.1, R324.1.7, R402.1.2, R504.3, Table R905.8.5 



AWWA 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



C 104— 98 
Clio— 98 
CI 15— 99 
C151/A21.51— 02 
CI 53— 00 
C510— 00 
C511— 00 



American Water Works Association 
6666 West Quincy Avenue 
Denver, CO 80235 

Title 

Standard for Cement-Mortar Lining for Ductile-iron Pipe and Fittings for Water , P2904.4 

Standard for Ductile-iron and Gray-iron Fittings, 3 Inches through 48 Inches, for W&ter Table P2904.6, Table P3002.3 

Standard for Flanged Ductile-iron Pipe with Ductile-iron or Gray-iron Threaded Flanges Table P2904.4 

Standard for Ductile-iron Pipe, Centrifugally Cast, for Water Table P2904.4 

Standard for Ductile-iron Compact Fittings for Water Service Table P2904.6. 1 

Double Check Valve Backflow Prevention Assembly Table P2902.3 

Reduced-Pressure Principle Backflow Prevention Assembly Table P2902.3, P2902.3.5, P2902.5.1 



CGSB 



37-GP— 52M— (1984) 
37-GP— 56M— (1980) 

CAN/CGSB-37.54— 95 



Canadian General Standards Board 

Place du Portage ]11,6B1 

1 1 Laurier Street 

Gatineau, Quebec, Canada KIA 1G6 

Title 

Roofing and Waterproofing Membrane, Sheet Applied, Elastomeric |. . .R905.12.2 

Membrane, Modified Bituminous, Prefabricated and Pvcinforced for Roofing — 

with December 1985 Amendment Table R905.11.2 

Polyvinyl Chloride Roofing and Waterproofing Membrane . .R905.13.2 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



558 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



CISPI 



REFERENCED STANDARDS 



Cast Iron Soil Pipe Institute 
5959 Shallowford Road, Suite 419 
Chattanooga, TN 37421 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



301- — 04 Standard Specification for Hubless Cast Iron Soil Pipe and Fittings for Sanitary 

and Storm Drain, Waste and Vent Piping Applications TableP3002.1(l), Table P3002.1(2), Table P3002.2, 

Table P3002.3, Table 3002.4, P3005.2.9 
3 10— 04 Standard Specification for Coupling for Use in Connection with Hubless Cast Iron Soil Pipe 
and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications Table P3002.1, Table P3002.2, P3003.6.3 



CPSC 



16 CFR Part 1201- 

(1977) 

16 CFR Part 1209- 

(1979) 

16 CFR Part 1404- 

(1979) 



Consumer Product Safety Commission 
4330 East West Highway 
Bethesda,MD 20814-4408 



Standard 




Referenced 


reference 




in code 


number 


Tide 


section number 



Safety Standard for Architectural Glazing R308.1.1, R308.3 

Interim Safety Standard for Cellulose Insulation R316.3 

Cellulose Insulation R3 1 6.3 



CSA 



Canadian Standards Association 
5060 Spectrum Way, Suite 100 
Mississauga, Ontario, Canada L4W 5N6 



Standard 




Referenced 


reference 




in code 


number 


Tide 


section number 



CSA Requirement 3 — 8J 
8-93 (Revision 1, 1999) 

0325.0—92 
0437-Series— 93 
A 257. IM— 92 
A 257.2M— 92 
A 257.3M— 92 

101/I.S.2/A440— 05 
B45.1— 02 
B45.2— 02 
B45.3— 02 
B45.4— 02 
B45.5— 02 
B45.9— 02 
B64.1.1— 01 
B64.1.2— 01 
B64.2— 01 
B64.2.1— 01 
B64.2.1.1— 01 
B64.2.2— 01 
B64.3— 01 

B64.4— 01 
B64.4.1— 01 
B64.5— 01 
B64.5.1— 01 
B64.7— 01 
B 125— 01 
B 125.1—05 



Manually Operated Gas Valves for Use in House Piping Systems Table G2420.1 .1 

Requirements for Gas Fired Log Lighters for Wood Burning Fireplaces 

— with Revisions through January 1999 G2433. 1 

Construction Sheathing (Reaffirmed 1998) R503.2.1 

Standards on OSB and Waferboard (Reaffirmed 2001) R503.2.1, R803.2.1 

Circular Concrete Culvert, Storm Drain, Sewer Pipe and Fittings Table P3002.2 

Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe and Fittings Table P3002.2 

Joints for Circular Concrete Sewer and Culvert Pipe, Manhole Sections, 

and Fittings Using Rubber Gaskets P3003.7 

Specifications for Windows, Doors and Unit SkyHghts R308.6.9, R613.4, Nl 102.4.2 

Ceramic Plumbing Fixtures Table P2701.1, P2711 .1, P2712.1 

Enameled Cast Iron Plumbing Fixtures Table 2701.1, P271 1.1 

Porcelain Enameled Steel Plumbing Fixtures Table P2701.1, Table P2702.2, P2711.1 

Stainless Steel Plumbing Fixtures Table P2701.1, P271 1.1, P2712.1 

Plastic Plumbing Fixtures Table P2701.1, P2711.2, P2712.1 

Macerating Systems and Related Components P3007.1, P3007.2.1 

Vacuum Breakers, Atmospheric Type (PVB) Table P2902.2, P2902.2 

Vacuum Breakers, Pressure Type (PVB) Table P2902.2, P2902.2 

Vacuum Breakers, Hose Connection Type (HCVB) Table P2902.2, P2902.2.2 

Vacuum Breakers, Hose Connection Type (HCVB) with Manual Draining Feature Table P2902.2, P2902.2.2 

Vacuum Breakers, Hose Connection Dual Check Type (HCDVB) Table P2902.2, P2902.2.2 

Vacuum Breakers, Hose Connection Type (HCVB) with Automatic Draining Feature Table P2902.2, P2902.2 

Backflow Preventers, Dual Check Valve type 

with Atmospheric Port (DCAP) Table P2902.2, P2902.2.2, P2902.2.3, P2902.4.1 

Blackflow Preventers, Reduced Pressure Principle Type (RP) Table P2902.2, P2902.2.3, P2902.2.5, P2902.4.1 

Backflow Preventers, Reduced Pressure Principle Type for Fire Systems (RPF) Table P2902.2, P2902.2.5 

Backflow Preventers, Double Check Valve Type (DCVA) Table P2902.2, P2902.2.6 

Backflow Preventers, Double Check Valve Type for Fire Systems (DCVAF) Table P2902.2, P2902.2.6 

Vacuum Breakers, Laboratory Faucet Type (LFVB) Table P2902.2, P2902.2.2 

Plumbing Fittings Table P2701.1, P2702.2, P2708.3, P2722.1, P2722.2, P2722.3 

Plumbing Supply Fitdngs P2708.4 



2003 INTERNATIONAL RESIDENTIAL CODE^ 



559 



REFERENCED STANDARDS 



B137.1— 02 

B 137.2—02 i 

B137.3— 02 

B137.5— 02 

B 137.6— 02 

B 137.8— 02 
B 137.9—02 
B137.10— 02 

B137.il— 02 
B181.1— 02 

B 181.2—02 

B 181. 3— 02 
B 182.2— 02 
B 182.4— 02 
B602— 02 

LC3— 00 

CAN/CSA A257.3M— 92 
CAN/CSAB64.1.1— 01 
CAN/CSA B64.2— 01 
CAN/CSA B64.2.2— 01 
CAN/CSA B64.3— 01 
CAN/CSA B64.4— 01 
CAN/CSA B 137.9— 99 
CAN/CSA B137.10M— 02 



CSA — continued 

Polyethylene Pipe, Tubing and Fittings for Cold Water Pressure Services Table P2904.4, Table P2904.6 

PVC Injection-moulded Gasketed Fittings for Pressure Applications Table P2904.6 

Rigid Poly (Vinyl Chloride) (PVC) Pipe for Pressure Applications Table P2904.4, P3003.9.2, P3003.14.2 

Cross-linked Polyethylene (PEX) Tubing Systems for Pressure Applications . . . Table P2904.4, Table P2904.5, Table P2904.6 
CPVC Pipe, Tubing and Fittings For Hot and Cold Water 

Distribution Systems Table P2904.4, Table P2904;5, Table 2904.6 

Polybutylene (PB) Piping for Pressure Applications Table 2904.4, Table P2904.5, Table 2904.6 

Polyethylene/ Aluminum/Polyethylene Composite Pressure-Pipe Systems Table 2904.4.1 

Crosslinked Polyethylene/ Aluminum/Crosslinked Polyethylene 

Composite Pressure-Pipe Systems Table P2904.4.1, Table P2904.5, Table M2101.1 

Polypropylene (PP-R) Pipe and Fittings for Pressure Applications Table P2904.4.1, Table 2904.5, Table P2904.6 

ABS Drain, Waste and Vent Pipe and Pipe Fittings Table P3002.1(l), Table P3002.1(2), Table P3002.2, 

Table P3002.4, P3003.3.2, P3003.8.2 

PVC Drain, Waste and Vent Pipe and Pipe Fittings Table P3002.1(l), Table P3002.1(2), Table P3002.2, 

Table P3002.3, P3003.9.2, P3003.14.2 

Polyolefm Laboratory Drainage Systems Table P3002.2, P3003.16.1 

PVC Sewer Pipe and Fittings (PSM Type) Table P3002.1(l), Table P3002.1(2), Table P3002.2, Table P3002.3 

Profile PVC Sewer Pipe & Fittings Table P3002.2, Table P3002.3 

Mechanical Couplings for Drain, Waste and Vent Pipe and Sewer Pipe P3003.3. 1, P3003.6.3, P3003.7, 

P3003.8.1, P3003.14.1, P3003.15, P3003.17 

Appliance Stands and Drain Pans P2801.5 

Joints for Circular Concrete Sewer and Culvert Pipe, Manhole Sections, and Fittings Using Rubber Gaskets P3003.3.5 

Vacuum Breakers, Atmospheric Type (AVB) Table P2902.2, P2902.2.2 

Vacuum Breakers, Hose Connection Type (HCVP) Table P2902.2, P2902.2.2 

Vacuum Breakers, Hose Connection Type (HCVP) with Automatic Draining Feature Table P2902.2, P2902.2.2 

Backflow Preventers, Dual Check Valve Type with Atmospheric Port (DCAP) Table P2902.2, P2902.2.3, P2902.4.1 

Backflow Preventers, Reduced Pressure Principle Type (RP) Table P2902.2, P2902.2.5 

Polyethylene/Aluminum/Polyethylene Composite Pressure Pipe Systems Table P2904.4.1 

Crosslinked Polyethylene/ Aluminum/Polyethylene Composite Pressure 
Pipe Systems Table P2904.4.1, Table P2904.5, Table M2101.1 



CSSB 



Cedar Shake & Shingle Bureau 
515 116th Avenue, NE, Suite 275 
Bellevue, WA 98004-5294 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



CSSB— 97 



Grading and Packing Rules for Western Red Cedar Shakes and Western Red Shingles 

of the Cedar Shake and Shingle Bureau R702.6, R703.5, Table R905.7.4, Table R905.8.5 



DASMA 



Door and Access Systems Manufacturers 
Association International 
1300 Summer Avenue 
Cleveland, OH 44115-2851 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



108—2002 



Standard Method for Testing Garage Doors: Determination of Structural Performance 
Under Uniform Static Air Pressure Difference 



.R902.2 



DOC 



United States Department of Commerce . 

100 Bureau Drive Stop 3460 

Gaithersburg, MP 20899 

Referenced 

in code 

Title section number 

Construction and Industrial Plywood R404.2.1, Table R404.2.3, R503.2.1, R604.1, R803.2.1 

Performance Standard for Wood-based Structural-use Panels R404.2.1, Table R404.2.3, R503.2.1, R604.1, R803.2.1 

American Softwood Lumber Standard R404.2.1, R502.1, R602.1, R802.1 



Standard 
reference 
number 



PS 1—95 
PS 2—92 
PS 20—99 



560 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



REFERENCED STANDARDS 



DOTn 



Department of Transportation 
400 Seventh St. S.W. 
Washington, DC 20590 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 


49 CFR, 






Parts 192.281(e) & 






192.283 (b) 


Transportation of Natural and Other Gas by Pipeline: Minimum Federal Safety Standards 


G2414.6.1 









FEMA 



Federal Emergency Management Agency 
500 C Street, SW 
Washington, DC 20472 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



TB-2— 93 
FIA-TB-11— 01 



Flood-resistant Materials Requirements 

Crawlspace Construction for Buildings Located in Special Flood Hazard Area. 



R324.1.7 
..R408.7 



FM 



4450— (1989) 
4880— (2001) 



Factory Mutual Global Research 
Standards Laboratories Department 
1151 Boston Providence Turnpike 
Norwood, MA 02062 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Approval Standard for Class 1 Insulated Steel Deck Roofs — with Supplements through July 1992 . . 

American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, 
Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, 
Interior or Exterior Finish Systems 



R906.1 



.R314.3 



GA 



Gypsum Association 

810 First Street, Northeast, Suite 510 

Washington, DC 20002-4268 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



GA-253— 99 



Recommended Standard Specification for the Application of Gypsum Sheathing Table R602.3(l) 



HPVA 



Hardwood Plywood & Veneer Association 
1 825 Michael Faraday Drive 
Reston, Virginia 20190-5350 



Standard 
reference 
number 



Tide 



Referenced 

in code 

section number 



HP- 1—2000 



The American National Standard for Hardwood and Decorative Plywood R702.5 



ICC 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



IBC— 06 
ICC EC— 06 
lEBC— 06 
lECC— 06 
IPC- 06 
IFGC— 06 



International Code Council 
5203 Leesburg Pike, Suite 600 
Falls Church, VA 22041 

Title 

International Building Code" R110.2, R322.1,R324.1, R324.1.5,R403.1.8, RlOOl.8.2, G2402.3 

ICC Electrical Code®— Administrative Provisions R107.3, G2402.3 

International Existing Building Code® R101.2, G2401.1 

International Energy Conservation Code® R104. 1 1 

International Fire Code® R102.7, G2402.3, G2412.2, G2423.1 

International Fuel Gas Code® R104.il, G2401.1 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



561 



REFERENCED STANDARDS 



IMC— 06 
IPC— 06 
IPSDC— 06 
IPMC— 06 
SBCCI SSTD 10—99 



ICC — continued 

International Mechanical Code® R104.ll, M2106.1, G2402.3 

International Plumbing Code® R104.il, G2402.3 

International Private Sewage Disposal Code® R324.1.6 

International Property Maintenance Code® , . R102.7 

Standard for Hurricane Resistant Construction R301.2.1.] 



ISO 



International Organization for Standardization 
1, rue de Varembe, Case postale 56 
CH-1211 Geneva 20, Switzerland 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



15874—2002 



Polypropylene Plastic Piping Systems for Hot and Cold Water Installations Table M2101 . 1 



MSS 



Manufacturers Standardization Society of the Valve and Fittings Industry 
127 Park Street, Northeast 
Vienna, VA 22180 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



SP-58— 93 



Pipe Hangers and Supports — Materials, Design and Manufacture G2418.2 



NAIMA 



North American Insulation Manufacturers Association 
44 Canal Center Plaza, Suite 310 
Alexandria, VA 22314 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



AH 116 06—02 



Fibrous Glass Duct Construction Standards, Fifth Edition .M1601.1.1 



NCMA 



National Concrete Masonry Association 
2302 Horse Pen Road 
Hemdon, VA 20171-3499 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



TR 68-A— 75 
TR 68B(2001) 



Design and Construction of Plain and Reinforced Concrete Masonry and Basement and Foundation Walls. 
Basement Manual Design and Construction Using Concrete Masonry 



R404.1 
.R404.1 



NFPA 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



13—02 

31—01 

58—04 

70—05 

72—02 

85—04 

211—03 

259—04 

286-00 

501—03 
853—03 



National Fire Protection Association 
Battery march Park 
Quincy, MA 02269 

Title 

Installation of Sprinkler Systems R317.1 

Installation of Oil-burning Equipment' M1801.3.1, M1805.3 

Liquefied Petroleum Gas Code 02412.2, G2414.6.2 

National Electrical Code E3301.1, E3301.2, E4201.1, Table E4203.2, E4204.3, E4204.4 

National Fire Alarm Code , R313.1 

Boiler and Construction Systems Hazards Code . l G2452.1 

Chimneys, Fireplaces, Vents and Sohd Fuel Burning Apphances R1002.5 

Test Method for Potential Heat of Building Materials : R314.2.5 

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling j 

Interior Finish to Room Fire Growth R314.3, R315.4 

Standard on Manufactured Housing R202 

Standard for the Installation of Stationary Fuel Cell Power Systems : M1903.1 



562 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



REFERENCED STANDARDS 



NFRC 



100—2001 
200—2001 

400—2001 



National Fenestration Rating Council, Inc. 

8484 Georgia Avenue, Suite 320 

Silver Spring, MD 20910 

R( 

sectio 

Procedure for Determining Fenestration Product U-fectors-Second Edition Nl 101.5 

Procedure for Determining Fenestration product Solar Heat Gain CoeiFicients and 

Visible Transmittance at Normal Incidence — Second Edition N1101.5 

Procedure for Determining Fenestration Product Air Leakage Nl 102.4.2 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



NSF 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



14—2003 
42— 2002e 
44—2004 
53— 2002e 
58—2004 
61— 2003e 



NSF International 
789 N. Dixboro Road 
Ann Arbor, MI 48105 

Title 

Plastic Piping System Components and Related Materials P2608.3, P2907.3 

Drinking Water Treatment Units— Anesthetic Effects P2907.1, P2907.3 

Residential Cation Exchange Water Softeners P2907.1, P2907.3 

Drinking Water Treatment Units— Health Effects P2907.1, P2907.3 

Reverse Osmosis Drinking Water Treatment Systems P2907.2, P2907.3 

Drinking Water System Components— Health Effects .... P2608.5, P2722.1, P2903.9.4, P2904.4, P2904.5, P2904.6, P2907.3 



SAE 



Society of Automotive Engineers 
400 Commonwealth Drive 
Warrendale, PA 15096 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



J 78— (1998) 



Steel Self-drilling Tapping Screws R505.2.4, R603.2.4, R804.2.4 



CJ TV/i' A f~^ 1^ \ 4021 Lafayette Center Road 



Sheet Metal & Air Conditioning Contractors National Assoc, Inc. 



Chantilly, VA 22021 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



SMACNA— 03 



Fibrous Glass Duct Construction Standards (2003) M1601.1.1 



TMS 



402—05 



602—05 



The Masonry Society 

3970 Broadway, Suite 201-D 

Boulder, CO 80304 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Building Code Requirements for Masonry Structures 
Specification for Masonry Structures 



R404.1, R606.1, R606.1.1, 

R606.12.1, R606.12.2.2.1,R606.1 1.2.2.2, R606.12.3.1 

R404.1 , R606.1 , R606.1.] , 

R606.12.1, R606. 12.2.2.1, R606.12.2.2.2, R606.12.3.1 



TPI 



Truss Plate Institute 

583 D'Onofrio Drive, Suite 200 

Madison, WI 53719 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



TPI 1—2002 



National Design Standard for Metal-plate-connected Wood Truss Construction R502. 11.1, R802. 1 0.2, 



2006 INTERNATIONAL RESIDENTIAL CODE® 



563 



REFERENCED STANDARDS 



UL 



Underwriters Laboratories, Inc. 
333 Pfingsten Road 
Northbrook, IL 60062 



Standaid 




Referenced 


reference 




in code 


number 


Title 


section number 



17—94 
58—96 
80—96 
103—2001 

127—99 
174—04 
181—96 
181 A— 98 

181B— 95 

217—1997 
325—02 

343—97 

441—96 

508—99 

536—97 

641—95 

651—05 

726—98 

727—98 

729—03 

730—03 

732—95 

737—96 

790—04 

795—99 

834—04 

896—93 

959—01 

923—02 

1040—96 

1256—02 

1261—01 

1453—04 

1479—03 

1482—98 

1715—97 

1738—93 

1777—04 

1995—98 

2158A— 96 



Vent or Chimney Connector Dampers for Oil-fired Appliances — with Revisions through September 1999 Ml 802.2.2 

Steel Underground Tanks for Flammable and Combustible Liquids — with Revisions through July 1998 M2201.1 

Steel Tanks for Oil-burner Fuel— with Revisions Through June 2003 M2201.1 

Factory-built Chimneys for Residential Type and Building Heating Appliances 
—with Revisions through December 2003 R202, R1005.3, G2430.1 

Factory-built Fireplaces— with Revisions through November 1999 RlOOl.ll, R1004.1, R1004.4, R1005.4, G2445.7 

Household Electric Storage Tank Water Heaters — with Revisions through October 1999 M2005.1 

Factory-made Air Ducts and Air Connectors — with Revisions through May 2003 M1601.2, M1601 .3.1 

Closure Systems for Use with Rigid Air Ducts and Air Connectors — 

with Revisions through December 1998 M1601.2, M1601.3.1 

Closure Systems for Use with Flexible Air Ducts and Air Connectors — 

with Revisions through August 2003 M1601.2, M1601.3.1 

Single and Multiple Station Smoke Alarms — with Revisions Through January 2004 R313.1 

Standard for Door, Drapery, Gate, Louver and Window Operations and Systems 

—with Revisions through March 2003 R309.6 

Pumps for Oil-Burning Appliances — with Revisions through May 2002 M2204.1 

Gas Vents — with Revisions through December 1999 G2426.1 

Industrial Control Equipment ,.. .M 1411. 3.1 

Flexible Metallic Hose — with Revisions through June 2003 M2202.3 

Type L, Low-temperature Venting Systems— with Revisions through April 1999 .... R202, RlOOl.11.5, M1804.2.4, G2426.1 

Schedule 40 and Schedule 80 Rigid PVC Conduit and Fittings G2414.6.3 

Oil-fired Boiler Assemblies— with Revisions through January 2001 M2001.1.1, M2006.1, G2425.1 

Oil-fired Central Furnaces — with Revisions through January 1999 M1402.1 

Oil-fired Floor Furnaces M1408.1 

Oil-fired Wall Furnaces \ M1409.1 

Oil-fired Storage Tank Water Heaters — with Revisions through January 1999 .M2005.1 

Fireplaces Stoves — with Revisions through January 2000 .M1414.1 

Standard Test Methods for Fire Tests of Roof Coverings R902.1 

Commercial-Industrial Gas Heating Equipment G2442.1, G2452.1 

Heating, Water Supply, and Power Boilers-Electric M2001 .1 .1 

Oil-burning Stoves — with Revisions through May 2004 M1410. 1 

Medium Heat Appliance Factory-built Chimneys R1005.6 

Microwave Cooking Appliances — with Revisions through January 2003 .M1504.1 

Fire Test of Insulated Wall Construction — with Revisions through June 2001 R314.3 

Fire Test of Roof Deck Construction R906.1 

Electric Water Heaters for Pools and Tubs — with Revisions through June 2004 M2006. 1 

Electronic Booster and Commercial Storage Tank Water Heaters '. . . . .M2005.1 

Fire Tests of Through-Penetration Firestops R317.3.1.2 

Solid-fuel Type Room Heaters— with Revisions through January 2000 R1002.2, R1002.5, M1410.1 

Fire Test of Interior Finish Material — with Revisions through March 2004 R3 14.4 

Venting Systems for Gas-burning Appliances, Categories II, III and IV — with Revisions through December 2000. . . . G2426.1 

Standard for Chimney Liners R1003.1.8, R1003.il. 1, M1801.3.4, G2425. 12, G2425. 15.4 

Heating and Cooling Equipment— with Revisions through August 1999 M1402.1, M1403.1, M1407.1 

Outline of Investigation for Clothes Dryer Transition Duct M1502.4 



ULC 



Underwriters' Laboratories of Canada 

7 Grouse Road 

Scarborough, Ontario, Canada MIR 3A9 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



S 102—1988 



Standard Methods for Test for Surface Burning Characteristics 
of Building Materials and Assemblies — with 2000 Revisions 



.R3I6.2 



564 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



REFERENCED STANDARDS 



Window & Door Manufacturers Association 
1400 East Touhy Aveni 
DesPlainesJL 60018 



A^n A/T A ^^^^ ^^^^ ^'^"^y Avenue, Suite 470 



Standard Referenced 

reference in code 

number Title section number 

101/I.S2/A440— 05 Specifications for Windows, Doors and Unit Skylights R308.6.9, R61 3.4, Nl 102.4.2 



2003 INTERNATIONAL RESIDENTIAL CODE® 565 



566 



2003 INTERNATIONAL RESIDEENTIAL CODE^ 



APPENDIX A (IFGS) 

SIZING AND CAPACITIES OF GAS PIPING 

(This appendix is informative and is not part of the code. This appendix is an excerpt from the 2006 International Fuel Gas 
Code, coordinated with the section numbering of the International Residential Code.) 



A.l General piping considerations. The first goal of deter- 
mining the pipe sizing for a fuel gas piping system is to make 
sure that there is sufficient gas pressure at the inlet to each 
appliance. The majority of systems are residential and the 
appliances will all have the same, or nearly the same, require- 
ment for minimum gas pressure at the appliance inlet. This 
pressure will be about 5-inch water column (w.c.) (1.25 kPa), 
which is enough for proper operation of the appliance regulator 
to deliver about 3.5-inches water column (w.c.) (875 kPa) to the 
burner itself. The pressure drop in the piping is subtracted from 
the source delivery pressure to verify that the minimum is avail- 
able at the appliance. 

There are other systems, however, where the required inlet 
pressure to the different appliances may be quite varied. In such 
cases, the greatest inlet pressure required must be satisfied, as 
well as the farthest appliance, which is almost always the criti- 
cal appliance in small systems. 

There is an additional requirement to be observed besides 
the capacity of the system at 100-percent flow. That require- 
ment is that at minimum flow, the pressure at the inlet to any 
appliance does not exceed the pressure rating of the appliance 
regulator. This would seldom be of concern in small systems if 
the source pressure is '/j psi (14-inch w.c.) (3.5 kPa) or less but 
it should be verified for systems with greater gas pressure at the 
point of supply. 

To determine the size of piping used in a gas piping system, the 
following factors must be considered: 

(1) Allowable loss in pressure from point of delivery to 
equipment. 

(2) Maximum gas demand. 

(3) Length of piping and number of fittings. 

(4) Specific gravity of the gas. 

(5) Diversity factor. 

For any gas piping system, or special appliance, or for condi- 
tions other than those covered by the tables provided in this 
code, such as longer runs, greater gas demands or greater pres- 
sure drops, the size of each gas piping system should be deter- 
mined by standard engineering practices acceptable to the code 
official. 

A.2 Description of tables 

A.2.1 General. The quantity of gas to be provided at each 
outlet should be determined, whenever possible, directly 



from the manufacturer's gas input Btu/h rating of the 
appliance that will be installed. In case the ratings of the 
appliances to be installed are not known, Table G2413.2 
shows the approximate consumption (in Btu per hour) of 
certain types of typical household appliances. 

To obtain the cubic feet per hour of gas required, divide 
the total Btu/h input of all appliances by the average Btu 
heating value per cubic foot of the gas. The average Btu per 
cubic foot of the gas in the area of the installation can be 
obtained from the serving gas supplier. 

A.2.2 Low pressure natural gas tables. Capacities for gas 
at low pressure [less than 2.0 psig (13.8 kPa gauge)] in cubic 
feet per hour of 0.60 specific gravity gas for different sizes 
and lengths are shown in Table G2413.4(l) for iron pipe or 
equivalent rigid pipe, in Table G24 13.4(3) for smooth wall 
semi-rigid tubing, in Table G2413.4(5) for corrugated stain- 
less steel tubing and in Table G2413.4(7) for polyethylene 
plastic pipe. Tables G2413.4(l), G2413.4(3), G2413.4(5) 
and G2413.4(7) are based upon a pressure drop of 0.5-inch 
w.c. (125 Pa). In using these tables, an allowance (in equiva- 
lent length of pipe) should be considered for any piping run 
with four or more fittings [see Table A.2.2]. 

A.2.3 Undiluted liquefied petroleum tables. Capacities in 
thousands of Btu per hour of undiluted liquefied petroleum 
gases based on a pressure drop of 0.5-inch w.c. (125 Pa) for 
different sizes and lengths are shown in the International 
Fuel Gas Code. See Appendix A of that code. 

A.2.4 Natural gas specific gravity. Gas piping systems that 
are to be supplied with gas of a specific gravity of 0.70 or 
less can be sized directly from the tables provided in this 
code, unless the code official specifies that a gravity factor 
be applied. Where the specific gravity of the gas is greater 
than 0.70, the gravity factor should be applied. 

Application of the gravity factor converts the figures 
given in the tables provided in this code to capacities for 
another gas of different specific gravity. Such application is 
accomplished by multiplying the capacities given in the 
tables by the multipliers shown in Table A.2.4. In case the 
exact specific gravity does not appear in the table, choose 
the next higher value specific gravity shown. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



567 



APPENDIX A 



TABLE A.2.2 
EQUIVALENT LENGTHS OF PIPE FITTINGS AND VALVES 





SCREWED FITTINGS^ 


90° WELDING ELBOWS AND SMOOTH BENDS^ 


457EII 


907EII 


180° close 
return bends 


Tee 


R/d='\ 


/VC/=1V3 


R/d=2 


R/d=4 


fl/f/:=6 


R/d=6 


/f factors 


0.42 


0.90 


2.00 


1.80 


0.48 


0.36 


0.27 


0.21 


0.27 


0.36 


Ud' ratio* n = 


14 


30 


67 


60 


16 


12 


9 


7 


9 : 


12 


Nominal 

pipe size, 

inches 


Inside 
diameter d, 

inches, 
Schedule 40^ 




L = Equivalent Length In Feet of Schedule 40 (Standard-Weight) Straight Pipe 


i 
6 1 




% 


0.622 


0.73 


1.55 


3.47 


3.10 


0.83 


0.62 


0.47 


0.36 


0.47 


0.62 


\ 


0.824 


0.96 


2.06 


4.60 


4.12 


1.10 


0.82 


0.62 


0.48 


0.62 


0.82 


1 


1.049 


1.22 


2.62 


5.82 


5.24 


1.40 


1.05 


0.79 


0.61 


0.79 


1.05 


IV4 


1.380 


1.61 


3.45 


7.66 


6.90 


1.84 


1.38 


1.03 


0.81 


1.03 


1.38 


\% 


1.610 


1.88 


4.02 


8.95 


8.04 


2.14 


1.61 


1.21 


0.94 


1.21 


1.61 


2 


2.067 


2.41 


5.17 


11.5 


10.3 


2.76 


2.07 


1.55 


1.21 


1.55 


2.07 


2% 


2.469 


2.88 


6.16 


13.7 


12.3 


3.29 


2.47 


1.85 


1.44 


1.85 


2.47 


3 


3.068 


3.58 


7.67 


17.1 


15.3 


4.09 


3.07 


2.30 


1.79 


2.30 


3.07 


4 


4.026 


4.70 


10.1 


22.4 


20.2 


5.37 


4.03 


3.02 


2.35 


3.02 


4.03 


5 


5.047 


5.88 


12.6 


28.0 


25.2 


6.72 


5.05 


3.78 


2.94 


3.78 


5.05 


6 


6.065 


7.07 


15.2 


33.8 


30.4 


8.09 


6.07 


4.55 


3.54 


4.55 


6.07 


8 


7.981 


9.31 


20.0 


44.6 


40.0 


10.6 


7.98 


5.98 


4.65 


5.98 


7.98 


10 


10.02 


11.7 


25.0 


55.7 


50.0 


13.3 


10.0 


7.51 


5.85 


7.51 


10.0 


12 


11.94 


13.9 


29.8 


66.3 


59.6 


15.9 


11.9 


8.95 


6.96 


8.95 


11.9 


14 


13.13 


15.3 


32.8 


73.0 


65.6 


17.5 


13.1 


9.85 


7.65 


9.85 


13.1 


16 


15.00 


17.5 


37.5 


83.5 


75.0 


20.0 


15.0 


11.2 


8.75 


11.2 


15.0 


18 


16.88 


19.7 


42.1 


93.8 


84.2 


22.5 


16.9 


12.7 


9.85 


12.7 , 


16.9 


20 


18.81 


22.0 


47.0 


105.0 


94.0 


25.1 


18.8 


14.1 


11.0 


14.1 


18.8 


24 


22.63 


26.4 


56.6 


126.0 


113.0 


30.2 


22.6 


17.0 


13.2 


17.0 


22.6 



continued 



568 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX A 



TABLE A.2.2— continued 
EQUIVALENT LENGTHS OF PIPE FITTINGS AND VALVES 





MITER ELBOWS^ (No. of miters) 


WELDING TEES 


VALVES (screwed, flanged, or 


welded) 


1-45° 


1-60° 


1-90° 


2.9005 


3-90°^ 


Forged 


Miter^ 


Gate 


Globe 


Angle 


Swing 
Check 


fc factor = 


0.45 


0.90 


1.80 


0.60 


0.45 


1.35 


1.80 


0.21 


10 


5.0 


2.5 


L/tf' ratio'' n = 


15 


30 


60 


20 


15 


45 


60 


7 


333 


167 


83 


Nominal 

pipe size, 

inches 


Inside 
diameter d, 

inches, 
Schedule 40^ 


L = Equivalent Length In Feet of Schedule 40 (Standard-Weight) Straight Pipe^ 


\ 


0.622 


0.78 


1.55 


3.10 


1.04 


0.78 


2.33 


3.10 


0.36 


17.3 


8.65 


4.32 


% 


0.824 


1.03 


2.06 


4.12 


1.37 


1.03 


3.09 


4.12 


0.48 


22.9 


11.4 


5.72 


1 


1.049 


1.31 


2.62 


5.24 


1.75 


1.31 


3.93 


5.24 


0.61 


29.1 


14.6 


7.27 


l'/4 


1.380 


1.72 


3.45 


6.90 


2.30 


1,72 


5.17 


6.90 


0.81 


38.3 


19.1 


9.58 


VI, 


1.610 


2.01 


4.02 


8.04 


2.68 


2.01 


6.04 


8.04 


0.94 


44.7 


22.4 


11.2 


2 


2.067 


2.58 


5.17 


10.3 


3.45 


2.58 


7.75 


10.3 


1.21 


57.4 


28.7 


14.4 


2V2 


2.469 


3.08 


6.16 


12.3 


4.11 


3.08 


9.25 


12.3 


1.44 


68.5 


34.3 


17.1 


3 


3.068 


3.84 


7.67 


15.3 


5.11 


3.84 


11.5 


15.3 


1.79 


85.2 


42.6 


21.3 


4 


4.026 


5.04 


10.1 


20.2 


6.71 


5.04 


15.1 


20.2 


2.35 


112.0 


56.0 


28.0 


5 


5.047 


6.30 


12.6 


25.2 


8.40 


6.30 


18.9 


25.2 


2.94 


140.0 


70.0 


35.0 


6 


6.065 


7.58 


15.2 


30.4 


10.1 


7.58 


22.8 


30.4 


3.54 


168.0 


84.1 


42.1 


8 


7.981 


9.97 


20.0 


40.0 


13.3 


9.97 


29.9 


40.0 


4.65 


222.0 


111.0 


55.5 


10 


10.02 


12.5 


25.0 


50.0 


16.7 


12.5 


37.6 


50.0 


5.85 


278.0 


139.0 


69.5 


12 


11.94 


14.9 


29.8 


59.6 


19.9 


14.9 


44.8 


59.6 


6.96 


332.0 


166.0 


83.0 


14 


13.13 


16.4 


32.8 


65.6 


21.9 


16.4 


49.2 


65.6 


7.65 


364.0 


182.0 


91.0 


16 


15.00 


18.8 


37.5 


75.0 


25.0 


18.8 


56.2 


75.0 


8.75 


417.0 


208.0 


104.0 


18 


16.88 


21.1 


42.1 


84.2 


28.1 


21.1 


63.2 


84.2 


9.85 


469.0 


234.0 


117.0 


20 


18.81 


23.5 


47.0 


94.0 


31.4 


23.5 


70.6 


94.0 


11.0 


522.0 


261.0 


131.0 


24 


22.63 


28.3 


56.6 


113.0 


37.8 


28.3 


85.0 


113.0 


13.2 


629.0 


314.0 


157.0 



For SI: 1 foot = 305 mm, 1 degree = 0.01745 rad. 

Note: Values for welded fittings are for conditions where bore is not obstructed by weld spatter or backing rings. If appreciably obstructed, use values for "Screwed 
Fittings." 

1. Flanged fittings have three-fourths the resistance of screwed elbows and tees. 

2. Tabular figures give the extra resistance due to curvature alone to which should be added the full length of travel. 

3. Small size socket-welding fittings are equivalent to miter elbows and miter tees. 

4. Equivalent resistance in number of diameters of straight pipe computed for a value of (/'- 0.0075) from the relation (n - k/4f). 

5. For condition of minimum resistance where the centerline length of each miter is between d and 2V2<i. 

6. For pipe having other inside diameters, the equivalent resistance may be computed from the above n values. 

Source: Crocker, S. Piping Handbook, 4th ed., Table XIV, pp. 100-101 . Copyright 1945 by McGraw-Hill, Inc. Used by permission of McGraw-Hill Book Company. 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



569 



APPENDIX A 



TABLE A.2.4 

MULTIPLIERS TO BE USED WITH TABLES G241 3.4(1) 

THROUGH 02413.4(8) WHERE THE SPECIFIC GRAVITY 

OF THE GAS IS OTHER THAN 0.60 



SPECIFIC 
GRAVITY 


MULTIPLIER 


SPECIFIC 
GRAVITY 


MULTIPLIER 


0.35 


1.31 


1.00 


0.78 


0.40 


1.23 


1.10 


0.74 


0.45 


1.16 


1.20 


0.71 


0.50 


1.10 


1.30 


0.68 


0.55 


1.04 


1.40 


0.66 


0.60 


1.00 


1.50 


0.63 


0.65 


0.96 


1.60 


0.61 


0.70 


0.93 


1.70 


0.59 


0.75 


0.90 


1.80 


0.58 


0.80 


0.87 


1.90 


0.56 


0.85 


0.84 


2.00 


0.55 


0.90 


0.82 


2.10 


0.54 



A.2.5 Higher pressure natural gas tables. Capacities for 
gas at pressures of 2.0 psig (13.8 kPa) or greater in cubic feet 
per hour of 0.60 specific gravity gas for different sizes and 
lengths are shown in Table G24 13.4(2) for iron pipe or 
equivalent rigid pipe, Table G24 13.4(4) for semi-rigid tub- 
ing, Table G2413.4(6) for corrugated stainless steel tubing 
and Table 02413.4(8) for polyethylene plastic pipe. 

A.3 Use of capacity tables 

A.3.1 Longest length method. This sizing method is con- 
servative in its approach by applying the maximum operat- 
ing conditions in the system as the norm for the system and 
by setting the length of pipe used to size any given part of the 
piping system to the maximum value. 

To determine the size of each section of gas piping in a sys- 
tem within the range of the capacity tables, proceed as follows, 
(also see sample calculations included in this Appendix). 

(1) Divide the piping system into appropriate segments 
consistent with the presence of tees, branch lines 
and main runs. For each segment, determine the gas 
load (assuming all appliances operate simulta- 
neously) and its overall length. An allowance (in 
equivalent length of pipe) as determined from Table 
A.2.2 shall be considered for piping segments that 
include four or more fittings. 

(2) Determine the gas demand of each appUance to be 
attached to the piping system. Where Tables 
02413.4(1) through 02413.4(8) are to be used to 
select the piping size, calculate the gas demand in 
terms of cubic feet per hour for each piping system 
outlet. 

(3) Where the piping system is for use with other than 
undiluted liquefied petroleum gases, determine the 
design system pressure, the allowable loss in pres- 
sure (pressure drop), and specific gravity of the gas 
to be used in the piping system. 



(4) Determine the length of piping from the point of 
delivery to the most remote outlet in the build- 
ing/piping system. 

(5) In the appropriate capacity table, select the row show- 
ing the measured length or the next longer length if the 
table does not give the exact length. This is the only 
length used in determining the size of any section of 
gas piping. If the gravity factor is to be applied, the val- 
ues in the selected row of the table are muMpMed by the 
appropriate multiplier from Table A.2.4. 

(6) Use this horizontal row to locate ALL gas demand 
figures for this particular system of piping. 

(7) Starting at the most remote outlet, find the gas 
demand for that outlet in the horizontal row just 
selected. If the exact figure of demand is not shown, 
choose the next larger figure left in the row. 

(8) Opposite this demand figure, in the first row at the 
top, the correct size of gas piping will be found. 

(9) Proceed in a similar manner for each oudet and each 
section of gas piping. For each section of piping, deter- 
mine the total gas demand supplied by that section. 

When a large number of piping components (such as 
elbows, tees and valves) are installed in a pipe run, additional 
pressure loss can be accounted for by the use of equivalent 
lengths. Pressure loss across any piping component can be 
equated to the pressure drop through a length of pipe. The 
equivalent length of a combination of only four elbows/tees 
can result in a jump to the next larger length row, resulting in a 
significant reduction in capacity. The equivalent lengths in feet 
shown in Table A.2.2 have been computed on a basis that the 
inside diameter corresponds to that of Schedule 40 (stan- 
dard-weight) steel pipe, which is close enough for most pur- 
poses involving other schedules of pipe. Where a more specific 
solution for equivalent length is desired, this may be made by 
multiplying the actual inside diameter of the pipe in inches by 
n/12, or the actual inside diameter in feet by n {n can be read 
from the table heading). The equivalent lengtli values can be 
used with reasonable accuracy for copper or brass fittings and 
bends although the resistance per foot of copper or brass pipe is 
less than that of steel. For copper or brass valves, however, the 
equivalent length of pipe should be taken as 45 percent longer 
than the values in the table, which are for steel pipe. 

A.3.2 Branch length method. This sizing method reduces 
the amount of conservatism built into the traditional Lon- 
gest Length Method. The longest length as measured from 
the meter to the furthest remote appliance is only used to 
size the initial parts of the overall piping system. The Branch 
Length Method is applied in the following manner: 

(1) Determine the gas load for each of the connected 
appliances. 

(2) Starting from the meter, divide the piping system 
into a number of connected segments, and deter- 
mine the length and amount of gas that each segment 
would carry assuming that all appliances were oper- 
ated simultaneously. An allowance (in equivalent 
length of pipe) as determined from Table A.2.2 



570 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



APPENDIX A 



should be considered for piping segments that 
include four or more fittings. 

(3) Determine the distance from the outlet of the gas meter 
to the appliance furthest removed from the meter. 

(4) Using the longest distance (found in Step 3), size 
each piping segment from the meter to the most 
remote appliance outlet. 

(5) For each of these piping segments, use the longest 
length and the calculated gas load for all of the con- 
nected appliances for the segment and begin the siz- 
ing process in Steps 6 through 8. 

(6) Referring to the appropriate sizing table (based on 
operating conditions and piping material), find the 
longest length distance in the first column or the next 
larger distance if the exact distance is not listed. The 
use of alternative operating pressures and/or pressure 
drops will require the use of a different sizing table, 
but will not alter the sizing methodology. In many 
cases, the use of alternative operating pressures 
and/or pressure drops will require the approval of 
both the code official and the local gas serving utility. 

(7) Trace across this row until the gas load is found or the 
closest larger capacity if the exact capacity is not hsted. 

(8) Read up the table column and select the appropriate 
pipe size in the top row. Repeat Steps 6, 7 and 8 for 
each pipe segment in the longest run. 

(9) Size each remaining section of branch piping not 
previously sized by measuring the distance from the 
gas meter location to the most remote outlet in that 
branch, using the gas load of attached appliances 
and following the procedures of Steps 2 through 8. 

A.3.3 Hybrid pressure method. The sizing of a 2 psi (13.8 
kPa) gas piping system is performed using the traditional 
Longest Length Method but with modifications. The 2 psi 
(13.8 kPa) system consists of two independent pressure 
zones, and each zone is sized separately. The Hybrid Pres- 
sure Method is applied as follows. 

The sizing of the 2 psi (13.8 kPa) section (from the meter 
to the line regulator) is as follows: 

(1) Calculate the gas load (by adding up the name plate 
ratings) from all connected appUances. (In certain cir- 
cumstances the installed gas load may be increased 
up to 50 percent to accommodate future addition of 
appliances.) Ensure that the line regulator capacity is 
adequate for the calculated gas load and that the 
required pressure drop (across the regulator) for that 
capacity does not exceed V4 psi (5.2 kPa) for a 2 psi 
(13.8 kPa) system. If the pressure drop across the reg- 
ulator is too high (for the connected gas load), select a 
larger regulator. 

(2) Measure the distance from the meter to the hne regu- 
lator located inside the building. 

(3) If there are multiple line regulators, measure the dis- 
tance from the meter to the regulator furthest 
removed from the meter. 



(4) The maximum allowable pressure drop for the 2 psi 
(13.8 kPa) section is 1 psi (6.9 kPa). 

(5) Referring to the appropriate sizing table (based on 
piping material) for 2 psi ( 1 3 . 8 kPa) systems with a 1 
psi (6.9 kPa) pressure drop, find this distance in the 
first column, or the closest larger distance if the 
exact distance is not listed. 

(6) Trace across this row until the gas load is found or the 
closest larger capacity if the exact capacity is not hsted. 

(7) Read up the table column to the top row and select 
the appropriate pipe size. 

(8) If there are multiple regulators in this portion of the 
piping system, each line segment must be sized for 
its actual gas load, but using the longest length pre- 
viously determined above. 

The low pressure section (all piping downstream of the 
line regulator) is sized as follows: 

(1) Determine the gas load for each of the connected 
appliances. 

(2) Starting from the hne regulator, divide the piping sys- 
tem into a number of connected segments and/or 
independent paraUel piping segments, and determine 
the amount of gas that each segment would carry 
assuming that all appliances were operated simulta- 
neously. An allowance (in equivalent length of pipe) 
as determined from Table A.2.2 should be considered 
for piping segments that include four or more fittings. 

(3) For each piping segment, use the actual length or 
longest length (if there are sub-branchlines) and the 
calculated gas load for that segment and begin the 
sizing process as follows: 

(a) Referring to the appropriate sizing table 
(based on operating pressure and piping ma- 
terial), find the longest length distance in the 
first column or the closest larger distance if 
the exact distance is not listed. The use of al- 
ternative operating pressures and/or pressure 
drops will require the use of a different sizing 
table, but will not alter the sizing methodol- 
ogy. In many cases, the use of alternative op- 
erating pressures and/or pressure drops may 
require the approval of the code official. 

(b) Trace across this row until the appliance gas 
load is found or the closest larger capacity if 
the exact capacity is not listed. 

(c) Read up the table column to the top row and 
select the appropriate pipe size. 

(d) Repeat this process for each segment of the 
piping system. 

A.3.4 Pressure drop per 100 feet method. This sizing 
method is less conservative than the others, but it allows the 
designer to immediately see where the largest pressure drop 
occurs in the system. With this information, modifications 
can be made to bring the total drop to the critical appliance 
within the limitations that are presented to the designer. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



571 



APPENDIX A 



Follow the procedures described in the Longest Length 
Method for Steps (1) through (4) and (9). 

For each piping segment, calculate the pressure drop 
based on pipe size, length as a percentage of 100 feet (30 
480 mm), and gas flow. Table A.3.4 shows pressure drop per 
100 feet (30 480 mm) for pipe sizes from Vj inch (12.7 mm) 
through 2 inch (51 mm). The sum of pressure drops to the 
critical appliance is subtracted from the supply pressure to 
verify that sufficient pressure will be available. If not, the 
layout can be examined to find the high drop section(s) and 
sizing selections modified. 

Note: Other values can be obtained by using the following 
equation: 



Desired Value = MBH x 



Desired Drop 
Table Drop 



For example, if it is desked to get flow through V4-inch (19. 1 
mm) pipe at 2 inches/100 feet, multiple the capacity of 
3/4-inch pipe at 1 inch/ 100 feet by the square root of the pres- 
sure ratio: 



141 MBH X 



2"w.c. 
Vw.c. 



147 X 1.414 = 20^ MBH 



(MBH = 1000 Btu/h) 

A.4 Use of sizing equations. Capacities of smooth wall pipe or 
tubing can also be determined by using the following formulae: 

(1) High Pressure [1.5 psi (10.3 kPa) and above]: 



(2=181.6. 



C^ ■ fba-L 



■ 2237 D^-^^^ 



(p"-P2)y 



C-L 



0.541 



(2) Low Pressure [Less than 1.5 psi (10.3 kPa)]: 
(2=1873 



D^ AH 



= 2313/)^ 



where: 



^ AH ^°"^ 



C-L 



Q = Rate, cubic feet per hour at 60°F and 30-inch mercury 
column 

D = Inside diameter of pipe, in. 

P, = Upstream pressure, psia 

P2 = Downstream pressure, psia 

Y = Superexpansibihty factor = 1/supercompressibility fac- 
tor 

C, = Factor for viscosity, density and temperature* 



= 0.00354 ST I - 



Note: See Table 402.4 for Y and C^ for natural gas and 
propane. 

S = Specific gravity of gas at 60°F and 30-inch mercury 
column (0.60 for natural gas, 1.50 for propane), or = 
1488|X 

T = Absolute temperature, °F or = f + 460 

t = Temperature, °F 

Z = Viscosity of gas, centipoise (0.012 for natural gas, 
0.008 for propane), or = 1488^ 

fba = Base friction factor for air at 60°F(CF=1) 

L = Length of pipe, ft 

AH = Pressure drop, in. w.c. (27.7 in. HjO = 1 psi) 

(For SI, see Section G2413.4) 

A.5 Pipe and tube diameters. Where the internal diameter is 
determined by the formulas in Section G2413.4, Tables A.5.1 
and A.5. 2 canbe used to select the nominal or standard pipe 
size based on the calculated internal diameter. 



C,- fba-L 



TABLE A.3.4 

THOUSANDS OF Btu/h (MBH) OF NATURAL GAS PER 100 FEET OF PIPE AT 

VARIOUS PRESSURE DROPS AND PIPE DIAMETERS 



PRESSURE DROP PER 

100 FEET IN INCHES 

W.C. 


PIPE SIZES (inch) 


V2 


% 


1 


l'/4 


IV2 


2 


0.2 


31 


64 


121 


248 


372 


716 


0.3 


38 


79 


148 


304 


455 


877 


0.5 


50 


104 


195 


400 


600 


1160 


1.0 


71 


147 


276 


566 


848 


1640 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



572 



2006 INTERNATIONAL RESIDENTIAL CODE® 



APPENDIX A 



TABLE A.5.1 
SCHEDULE 40 STEEL PIPE STANDARD SIZES 



NOMINAL SIZE 
(in.) 


INTERNAL 

DIAMETER 

(In.) 


NOMINAL 
SIZE 
(in.) 


INTERNAL 

DIAMETER 

(in.) 


'/4 


0.364 


l\ 


1.610 


% 


0.493 


2 


2.067 


% 


0.622 


2V2 


2.469 


% 


0.824 


3 


3.068 


1 


1.049 


3V2 


3.548 


IV4 


1.380 


4 


4.026 



A.6 Use of sizing charts. A third method of sizing gas piping is 
detailed below as an option that is useful when large quantities 
of piping are involved in a job (e.g., an apartment house) and 
material costs are of concern. If the user is not completely 
familiar with this method, the resulting pipe sizing should be 
checked by a knowledgeable gas engineer. The sizing charts 
are applied as follows. 

(1) With the layout developed according to Section 
R 106. 1.1 of the code, indicate in each section the 
design gas flow under maximum operation conditions. 
For many layouts, the maximum design flow will be the 
sum of all connected loads. However, in some cases, 
certain combinations of appliances will not occur 
simultaneously (e.g., gas heating and air conditioning). 
For these cases, the design flow is the greatest gas flow 
that can occur at any one time. 

(2) Determine the inlet gas pressure for the system being 
designed. In most cases, the point of inlet will be the gas 
meter or service regulator, but in the case of a system 
addition, it could be the point of connection to the exist- 
ing system. 

(3) Determine the minimum pressure required at the inlet 
to the critical appliance. Usually, the critical item will 
be the appliance with the highest required pressure for 
satisfactory operation. If several items have the same 
required pressure, it will be the one with the greatest 
length of piping from the system inlet. 

(4) The difference between the inlet pressure and critical 
item pressure is the allowable system pressure drop. 
Figures A. 6(a) and A. 6(b) show the relationship 
between gas flow, pipe size and pipe length for natural 
gas with 0.60 specific gravity. 

(5) To use Figure A.6(a) (low pressure apphcations), cal- 
culate the piping length from the inlet to the critical uti- 
lization equipment. Increase this length by 50 percent 
to allow for fittings. Divide the allowable pressure drop 
by the equivalent length (in hundreds of feet) to deter- 
mine the allowable pressure drop per hundred feet. 
Select the pipe size from Figure A.6(a) for the required 
volume of flow. 

(6) To use Figure A.6(b) (high pressure applications), cal- 
culate the equivalent length as above. Calculate the 
index number for Figure A.6(b) by dividing the differ- 
ence between the squares of the absolute values of inlet 



TABLE A.5.2 
COPPER TUBE STANDARD SIZES 


TUBE TYPE 


NOMINAL OR 
STANDARD SIZE 
inches j 


INTERNAL DIAMETER 
inches 


K 


'/4 


0.305 


L 


'/4 


0.315 


ACR (D) 


% 


0.315 


ACR (A) 


\ 


0.311 


K 


% 


0.402 


L 


% 


0.430 


ACR (D) 


\ 


0.430 


ACR (A) 


% 


0.436 


K 


'I2 


0.527 


L 


% 


0.545 


ACR (D) 


\ 


0.545 


ACR (A) 


% 


0.555 


K 


% 


0.652 


L 


% 


0.666 


ACR (D) 


% 


0.666 


ACR (A) 


% 


0.680 


K 


% 


0.745 


L 


% 


0.785 


ACR 


% 


0.785 


K 


1 


0.995 


L 


1 


1.025 


ACR 


iVs 


1.025 


K 


IV4 


1.245 


L 


IV4 


1.265 


ACR 


1% 


1.265 


K 


1% 


1.481 


L 


1% 


1.505 


ACR 


1% 


1.505 


K 


2 


1.959 


L 


2 


1.985 


ACR 


2% 


1.985 


K 


2% 


2.435 


L 


2% 


2.465 


ACR 


2% 


2.465 


K 


3 


2.907 


L 


3 


2.945 


ACR 


3Vs 


2.945 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



573 



APPENDIX A 



o 




Q. 


1 


LL 


0.9 


O 


0.8 


ti 


0,7 


o 


U.b 


o 


0,5 


T- 




d 


0.4 


5 


0.3 


c 




■ — ' 




a. 
n 


0.2 






•D 




(1) 








3 







0.10 


0.09 



0.08 
0.07 
0.06 
0.05 

0.04 
0.03 



0.02 



0.01 



V2 



3/4 



VA 



V/2 



272 












^ 




^ — 


... . 




•7- 





■"■ 




J' 


/ 




7- 




r 




^ 


T 
















/ 




/ 






> 




/ 




/ 










f 
















/ 




/ 






/ 




/ 




f 








/ 


















/ 


/ 






k 






/ 


1 








i 


r 


















/ 


/ 






/ 






/ 


/ 


J 






/ 




















/ 


/ 




/ 


( 






/ 


/ 


/ 




y 


f 




















f 

1 


/ 




/ 








f 

1 . 


1 , 


/ 


y 


/ 






1 




















y 








y 




/ 






/ 


1 












/ 


/ 


/ 


/ 


^ 




/ 






/ 


/ 




/ 


1 


f 












/ 






/ 


/ 




^ 


( 








/ 






' 






















/ 


/ 


x9' ' 










/ 






























f 




/ 








i / 


/ 












( 
















1 1 




?F 


/ 






i 


f / 


/ 












J 






/ 








/ 


/ 


T'4 








1 




f 


/ 








J 


f 






/ 








/ 


/ 


J 








1 






/ 




, 


i 


f 








/ 






\l 


r 


/ 


/J 


^ 






/ 






i 


/ 






/ 








/ 






/ 


f 




/ ^/ 

/ d / 






/ 




1 




/ 




> 


/ 










/ 


/ 


/^ 








' 1 


/ 


/ 


k 


/ 


/ 


f 


1 1 


/ 


/ 


/ 














/ 










/ 




/ 




r 




f 






/ 










i 






/ 






/ 




/ 




/ 


1 






i 






r 










f 






/ 






( 




/ 




^ 


/ 






1 




J 












1 




J 






1 






/ 


y 




/ 




/ 






/ 










> 






1 






/ 






1 


/ 


J 






/ 






/ 










/ 






/ 




/ 








1 


/ 


/ 




y 








/ 








/ 








/ 


i 


1 








1 




/ 


J 


/ 






1 1 


f 






1 








/ 




/ 










1 


/ 


/ 


1 






1 
1 








/ 


f 






f 


/ 


/ 


f 




h 


1 


f 


/ / 


/ 


/ 




/ 


/ 








/ 


/ 




/ 


/ 


1 


10 2 


3 


4 


5 


06 





80 


100 2C 


)0 


4( 


)0 


6( 


)0 


80C 


1-1000 20 


00 


4000 


600C 


) 


10,C 



Gas volume (standard ft /hr gas: specific gravity = 0.60) 



FIGURE A.6(a) 
CAPACITY OF NATURAL GAS PIPING, LOW PRESSURE (0.60 WC) 



and outlet pressures by the equivalent length (in hun- 
dreds of feet). Select the pipe size from Figure A.6(b) 
for the gas volume required. 

A.7 Examples of piping system design and sizing 

A.7.1 Example 1: Longest length method. Determine the 
required pipe size of each section and outlet of the piping 
system shown in Figure A.7.1, with a designated pressure 
drop of 0.5-inch w.c. (125 Pa) using the Longest Length 
Method. The gas to be used has 0.60 specific gravity and a 
heating value of 1,000 Btu/ft^ (37.5 MJ/m^). 

Solution: 

(1) Maximum gas demand for Outlet A: 
Consumption (rating plate input, or Table G 24 13.2 if necessary) 
Btu of gas 



Consumption 75,000 



35,000 Btu per hour rating 
1,000 Btu per cubic foot 

Maximum gas demand for Outlet B 



= 35 cubic feet per hour = 35cfh 



= 75cfh 



Btu of gas 1,000 
Maximum gas demand for Outlet C: 



Consumption 35,000 



= 35cfh 



Btu of gas 1,000 

Maximum gas demand for Outlet D: 
Consumption 100,000 



Btu of gas 



1,000 



100 cfh 



(2) The length of pipe from the point of delivery to the 
most remote outlet (A) is 60 feet (18 288 mm). This 
is the only distance used. i 

(3) Using the row marked 60 feet (18 288 nim) in Table 
G2413.4(l): \ 

(a) Outiet A, supplying 35 cfh (0.99 m'/hr), re- 
quires Vg-inch pipe. 



574 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



APPENDIX A 



%" 1" VA° V/2° 2" 2V2" 3" 



4" 5" 6" 8" 10" 12" 



Index number = 
^1 ^2 



Dist. 



(100) 



Dist. = Eq. length, ft 2 

Pj = Initial press, abs. psi 
P2= Final press, abs. psi 






10,000 100,000 1,000,000 

Gas volume (standard ft^/hr gas: specific gravity = 0.60 



10,000,000 



FIGURE A.6 (b) 
CAPACITY OF NATURAL GAS PIPING, HIGH PRESSURE (1.5 psi and above) 



(b) Outlet B, supplying 75 cfh (2.12 m'/hr), re- 
quires V^-inch pipe. 

(c) Section 1, supplying Outlets A and B, or 1 10 
cfh (3.11 m^/hr), requires V^-inch pipe. 

(d) Section 2, supplying Outlets C and D, or 135 
cfh (3.82 m^/hr), requires V^-inch pipe. 

(e) Section 3, supplying Outlets A, B, C and D, or 
245 cfh (6.94 mVhr), requires 1-inch pipe. 



Outlet D 
furnace 
lOOJDOOBtu/h 



Outlet C •— 

40 gal. automatic 
water heater 
35p00Bta/h 



Sections 



20 ft 



10ft 



> 



Section 2 
20 ft 



Section 1 
10ft 



15ft 



Point of 
delivery 



M5ft 



5ft 



Outlet A 
clothes dryer 
35p00Btu/h 



Outlet B * -^ 
range/oven unit 
75p00Btu/h 

FIGURE A.7.1 
PIPING PLAN SHOWING A STEEL PIPING SYSTEM 



(4) If a different gravity factor is applied to this exam- 
ple, the values in the row marked 60 feet (18 288 
mm) of Table 02413.4(1) would be multiplied by 
the appropriate multiplier from Table A.2.4 and the 
resulting cubic feet per hour values would be used to 
size the piping. 

Section A. 7.2 through A7.4 note: These examples are based on 
tables found in the International Fuel Gas Code. 

A.7.2 Example 2: Hybrid or dual pressure systems. 

Determine the required CSST size of each section of the 
piping system shown in Figure A.7.2, with a designated 
pressure drop of 1 psi (6.9 kPa) for the 2 psi (13.8 kPa) sec- 
tion and 3-inch w.c. (0.75 kPa) pressure drop for the 13-inch 
w.c. (2.49 kPa) section. The gas to be used has 0.60 specific 
gravity and a heating value of 1,000 Btu/ft^ (37.5 MJ/ m^), 

Solution 

(1) Size 2 psi (13.8 kPa) line using Table 402.4(16). 

(2) Size 10-inch w.c. (2.5 kPa) lines using Table 
402.4(14). 

(3) Using the following, determine if sizing tables can 
be used. 

(a) Total gas load shown in Figure A.7.2 equals 
110 cfh (3.11 mVhr). 

(b) Determine pressure drop across regulator [see 
notes in Table 402.4 (16)]. 

(c) If pressure drop across regulator exceeds V^ 
psig (5.2 kPa), Table 402.4 (16) cannot be 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



575 



APPENDIX A 



used. Note: If pressure drop exceeds V^psi (5.2 
kPa), then a larger regulator must be selected or 
an alternative sizing method must be used. 



2psig 

gas meter 

110 cfh 



M 



Section B 



Furnace 
60 cfh 



Section 

\) heater 
30 cfh 



!!5!lA,4^ III 

10 in! 7 ^®c*'°" 

2 psig ^ — ^ vv.c. iDj 1 

zone zone ^M_ 



Dryer 
20 cfh 



Length of runs: 
A = 100 ft 
B = 15ft 
C = 10ft 
D = 25ft 



Key: 

Hi Manifold 
X Shut-off valve 
[>^ Pressure regulator 
[m] Gas meter 



FIGURE A.7.2 
PIPING PLAN SHOWING A CSST SYSTEM 

(d) Pressure drop across the line regulator [for 
1 10 cfh (3.11 m'/hr)] is 4-inch w.c. (0.99 kPa) 
based on manufacturer's performance data. 

(e) Assume the CSST manufacturer has tubing 
sizes or EHDs of 13, 18, 23 and 30. 

(4) Section A [2 psi (13.8 kPa) zone] 

(a) Distance from meter to regulator = 1 00 feet (30 
480 mm). 

(b) Total load supplied by A = 110 cfh (3.11 
mVhr) (furnace + vv'ater heater + dryer). 

(c) Table 402.4 (16) shows that EHD size 18 
should be used. 

Note: It is not unusual to oversize the supply 
line by 25 to 50 percent of the as-installed 
load. EHD size 18 has a capacity of 189 cfh 
(5.35 m^/hr). 

(5) Section B (low pressure zone) 

(a) Distance from regulator to furnace is 15 feet 
(4572 mm). 

(b) Load is 60 cfh (1.70 m'/hr). 

(c) Table 402.4 (14) shows that EHD size 13 
should be used. 

(6) Section C (low pressure zone) 

(a) Distance from regulator to water heater is 1 
feet (3048 mm). 

(b) Load is 30 cfh (0.85 mVhr). 

(c) Table 402.4 (14) shows that EHD size 13 
should be used. 

(7) Section D (low pressure zone) 



(a) Distance from regulator to dryer is 25 feet 
(7620 mm). 

(b) Load is 20 cfh (0.57 m'/hr). 

(c) Table 402.4(14) shows that EHD size 13 
should be used. 

A.7.3 Example 3: Branch length method. Determine the 
required semi-rigid copper tubing size of each section of the 
piping system shown in Figure A.7.3, with a designated 
pressure drop of 1-inch w.c. (250 Pa) (using the Branch 
Length Method). The gas to be used has 0.60 specific grav- 
ity and a heating value of 1,000 Btu/ft^ (37.5 MJ/m^). 

Solution 

(1) Section A 



(a) 



(b) 



(c) 



The length of tubing from the point of deliv- 
ery to the most remote appliance is 50 feet (15 
240 mm), A -h C. 

Use this longest length to size Sections A and 
C. 



(2) 



Using the row marked 50 feet (15 240 mm) in 
Table 402.4(8), Section A, supplying 220 cfh 
(6.2 rn/hi) for four appliances requires 1-inch 
tubing. 

Section B 

(a) The length of tubing from the point of deliv- 
ery to the range/oven at the end of Section B is 
30 feet (9144 mm), A -hB. 

(b) Use this branch length to size Section B only. 

(c) Using the row marked 30 feet (9144 mm) in 
Table 402.4(8), Section B, supplying 75 cfh 
(2.12 mVhr) for the range/oven requires 
Vj-inch tubing. 



M 



ool Range/oven 
°° 75 cfh 



Section B 



Section A 
220 cfh 




Section C 



Section D 



Section E 



Water 
heater 
35 cfh 



Furnace 
80 cfh 



D 

Dryer 
30 cfh 



Length of runs: 
A =20 ft 
B = 10ft 
C = 30ft 
D = 10ft 
E = 10ft 



Key: 

iU Manifol^ 
X Shut-off valve 
H Gas meter 

Total gas load = 220 cfh 



FIGURE A.7.3 
PIPING PLAN SHOWING A COPPER TUBING SYSTEM 



576 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



APPENDIX A 



(3) Section C 

(a) The length of tubing from the point of deliv- 
ery to the dryer at the end of Section C is 50 
feet (15 240 mm), A + C. 

(b) Use this branch length (which is also the lon- 
gest length) to size Section C. 

(c) Using the row marked 50 feet (15 240 mm) in 
Table 402.4(8), Section C, supplying 30 cfh 
(0.85 m^/hr) for the dryer requires Vg-inch tub- 
ing. 

(4) Section D 

(a) The length of tubing from the point of deliv- 
ery to the water heater at the end of Section D 
is 30 feet (9144 mm), A -i- D. 

(b) Use this branch length to size Section D only. 

(c) Using the row marked 30 feet (9144 mm) in 
Table 402.4(8), Section D, supplying 35 cfh 
(0.99 m^/hr) for the water heater requires 
Vg-inch tubing. 

(5) Section E 

(a) The length of tubing from the point of deliv- 
ery to the furnace at the end of Section E is 30 
feet (9144 mm), A -HE. 

(b) Use this branch length to size Section E only. 

(c) Using the row marked 30 feet (9144 mm) in 
Table 402.4(8), Section E, supplying 80 cfh 
(2.26 m/hi) for the furnace requires V^-inch 
tubing. 

A.7.4 Example 4: Modification to existing piping system. 

Determine the required CSST size for Section G (retrofit 
application) of the piping system shown in Figure A.7.4, with 
a designated pressure drop of 0.5-inch w.c. (125 Pa) using the 
branch length method. The gas to be used has 0.60 specific 
gravity and a heating value of 1,000 Btu/ft^ (37.5 MjW). 



Barbecue 
40 cfh 

rxi 



Section A 



T 



Section B 



Section G 

Section C 



Section F 



Section E 



Section D 



Furnace 
80cfti 



Water 
lieater 
30 cfh 



Range/ 
overn 
75 cfh 



Length of runs: 
A=15ft E = 5ft 

B = 10ft F = 10ft 

C = 15ft G = 15ft 

D = 20ft 



Key: 
X Shut-off valve 
[m] Gas meter 



FIGURE A.7.4 

PIPING PLAN SHOWING A MODIFICATION 

TO EXISTING PIPING SYSTEM 



Solution 

(1) The length of pipe and CSST from the point of deliv- 
ery to the retrofit appliance (barbecue) at the end of 
Section G is 40 feet (12 192 mm), A + B -i- G. 

(2) Use this branch length to size Section G. 

(3) Assume the CSST manufacturer has tubing sizes or 
EHDsof 13, 18,23and30. 

(4) Using the row marked 40 feet ( 1 2 1 92 mm) in Table 
402.4(13), Section G, supplying 40 cfli (1.13 m^/hr) 
for the barbecue requires EHD 18 CSST. 

(5) The sizing of Sections A, B, F and E must be 
checked to ensure adequate gas carrying capacity 
since an appliance has been added to the piping sys- 
tem (see A.7.1 for details). 

A.7.5 Example 5: Calculating pressure drops due to 
temperature changes. A test piping system is installed on a 
warm autumn afternoon when the temperature is 70°F 
(21°C). In accordance with local custom, the new piping 
system is subjected to an air pressure test at 20 psig (138 
kPa). Overnight, the temperature drops and when the 
inspector shows up first thing in the morning the tempera- 
tiire is 40°F (4°C). 

If the volume of the piping system is unchanged, then the 
formula based on Boyle's and Charles' law for determining 
the new pressure at a reduced temperature is as follows: 

where: 

Tj = Initial temperature, absolute (Tj + 459) 

T2 = Final temperature, absolute (T2 -1- 459) 

Pi = Initial pressure, psia (P, -1- 14.7) 

P2 = Final pressure, psia (P2 -1- 14.7) 

(70 + 459) ^ (20+14.7) 
(40 + 459) (P2+I4.7) 



529 
499 



34.7 



(P, +14.7) 



(P, +14.7) X 



(R +14.7) = 



529 
499 

34.7 
1.060 



= 34.7 



P2 =32.7 - 14.7 

P2 =lSpsig 

Therefore, the gauge could be expected to register 1 8 psig 
(124 kPa) when the ambient temperature is 40°F (4°C). 

A7.6 Example 6: Pressure drop per 100 feet of pipe method. 

Using the layout shown in Figure A.7.1 and AH = pressure 
drop, in w.c. (27.7 in. H2O = 1 psi), proceed as follows: 

(1) Length to A = 20 feet, with 35,000 Btu/hr. 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



577 



APPENDIX A 



in. w.c. 



X 0.3 inch w.c. = 0.06 



(2) Length to B = 15 feet, with 75,000 Btu/hr. 

For V4-inch pipe, A//= '^^'%oofeetX0.3 inch w.c. = 0.045 
in. w.c. 

(3) Section 1 = 10 feet, with 1 10,000 Btu/hr. Here there is a 
choice: 



X 0.2 inch w.c. = 0.02 in 



Fori inch pipe: AH=>of-V,oofeet 
w.c. 



For 3/4-inch pipe: AH = '^ ^^^Vioo feet x [0-5 inch w.c. + 

(1 10,000 Btu/hr-104,000 Btu/hr)/ V ('1 O in<-tip>c 

'(147,000 Btu/hr- 104,000 Btu/hr) '^ (.i-vJ HH^IlCij 

W.C. - 0.5 inch w.c.)] = 0.1 x 0.57 inch w.c.= 0.06 inch 
w.c. 

Note that the pressure drop between 104,000 Btu/hr 
and 147,000 Btu/hr has been interpolated as 110,000 
Btu/hr. 

(4) Section 2 = 20 feet, with 1 35,000 Btu/hr. Here there is a 
choice: 

For 1-inch pipe: A// = ^o ^et/^^^ ^^^^ x [0.2 inch w.c. -i- 
(Ai4,ooo Btu/hr)/^^^^^^^^ ^^^^^ ^ AO.l iuch W.C.)] = 0.05 inch 
w.c.)] 

For 3/4-inch pipe: A// = 20 f^^V,oo f^^, x 1 .0 inch w.c. =0.2 
inch w.c.) 

Note that the pressure drop between 121,000 Btu/hr 
and 148,000 Btu/hr has been interpolated as 135,000 
Btu/hr, but interpolation for the V4-inchpipe (trivial for 
104,000 Btu/hr to 147,000 Btu/hr) was not used. 

(5) Section 3 = 30 feet, with 245,000 Btu/hr. Here there is a 
choice: 



For 1-inch pipe: AH = 30feet/^,,f^^, 
inch w.c. 



X l.Oinches w.c. = 0.3 



For 1 V4-inch pipe: AH=^^ f^^Vjoo feet x 0-2 inch w.c. = 
0.06 inch w.c. 

Note that interpolation for these options is ignored 
since the table values are close to the 245,000 Btu/hr 
carried by that section. 

(6) The total pressure drop is the sum of the section 
approaching A, Sections 1 and 3, or either of the fol- 
lowing, depending on whether an absolute minimum is 
needed or the larger drop can be accommodated. 

Minimum pressure drop to farthest appliance: 

A// = 0.06 inch w.c. -h 0.02 inch w.c. + 0.06 inch w.c. = 
0.14 inch w.c. 

Larger pressure drop to the farthest appliance: 

AH = 0.06 inch w.c. -1- 0.06 inch w.c. -1- 0.3 inch w.c. = 
0.42 inch w.c. 

Notice that Section 2 and the run to B do not enter into 
this calculation, provided that the appliances have sim- 
ilar input pressure requirements. 

For SI units: 1 Btu/hr = 0.293 W, 1 cubic foot = 0.028 
m^, 1 foot = 0.305 m, 1 inch w.c. = 249 Pa. 



578 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX B (IFGS) 

SIZING OF VENTING SYSTEMS SERVING APPLIANCES EQUIPPED 

WITH DRAFT HOODS, CATEGORY I APPLIANCES, AND 

APPLIANCES LISTED FOR USE WITH TYPE B VENTS 

(This appendix is informative and is not part of the code. This appendix is an excerpt from the 
2006 International Fuel Gas Code, coordinated with the section numbering of the International Residential Code.) 



EXAMPLES USING SINGLE 
APPLIANCE VENTING TABLES 

Example 1: Single draft-hood-equipped appliance. 

An installer has a 120,000 British thermal unit (Btu) per hour 
input appliance with a 5 -inch-diameter draft hood outlet that 
needs to be vented into a 10-foot-high Type B vent system. 
What size vent should be used assuming (a) a 5-foot lateral sin- 
gle-wall metal vent connector is used with two 90-degree 
elbows, or (b) a 5-foot lateral single- wall metal vent connector 
is used with three 90-degree elbows in the vent system? 

Solution: 

Table G2428.2(2) should be used to solve this problem, because 
single-wall metal vent connectors are being used with a Type B 
vent. 

(a) Read down the first column in Table G2428.2(2) until 
the row associated with a 10-foot height and 5-foot lat- 
eral is found. Read across this row until a vent capacity 



greater than 120,000 Btu per hour is located in the 
shaded columns labeled "NAT Max" for draft-hood- 
equipped appliances. In this case, a 5 -inch-diameter 
vent has a capacity of 122,000 Btu per hour and may be 
used for this application. 

(b) If three 90-degree elbows are used in the vent system, 
then the maximum vent capacity listed in the tables 
must be reduced by 10 percent (see Section G2428.2.3 
for single appliance vents). This implies that the 5- 
inch-diameter vent has an adjusted capacity of only 
1 10,000 Btu per hour. In this case, the vent system must 
be increased to 6 inches in diameter (see calculations 
below). 

122,000 (0.90) = 110,000 for 5-inch vent 
From Table 02428.2(2), Select 6-inch vent 
186,000 (0.90) = 167,000; This is greater than the 
required 120,000. Therefore, use a 6-inch vent and 
connector where three elbows are used. 



VENT CAP— £ 



TYPE B DOUBLE-WALL— 
GAS VENT 




^ 



For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W 
Table G2428.2(l) is used when sizing Type B double- wall gas vent connected 
directly to the appliance. 

Note: The appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-1 

TYPE B DOUBLE-WALL VENT SYSTEM SERVING A SINGLE 

APPLIANCE WITH A TYPE B DOUBLE-WALL VENT 



TYPE B DOUBLE-WALL- 
GAS VENT 



SINGLE-WALL VENT- 
CONNECTOR 



a 



For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.293 IW 
Table G2428.2(2) is used when sizing a single-wall metal vent connector 
attached to a Type B double-wall gas vent. 

Note: The appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-2 

TYPE B DOUBLE-WALL VENT SYSTEM SERVING 

A SINGLE APPLIANCE WITH A SINGLE-WALL 

METAL VENT CONNECTOR 



2006 INTERNATIONAL RESIDENTIAL CODE* 



.® 



579 



APPENDIX B 



TILE-LINED MASONRY- 
CHIMNEY 




I [ — — VENT CAP 



TYPE B DOUBLE-WALL— 
GAS VENT USED AS 
CONNECTOR 



^ 



Table 504.2(3) of the International Fuel Gas Code is used when sizing a Type B 
double-wall gas vent connector attached to a tile-lined masonry chimney. 

Note: "A" is the equivalent cross-sectional area of the tile liner. 

Note: The appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-3 

VENT SYSTEM SERVING A SINGLE APPLIANCE 

WITH A MASONRY CHIMNEY OF TYPE B 

DOUBLE-WALL VENT CONNECTOR 




Asbestos cement Type B or single- wall metal vent serving a single draft-hood- 
equipped appliance [see Table 504.2(5) of the International Fuel Gas Code]. 

FIGURE B-5 

ASBESTOS CEMENT TYPE B OR SINGLE-WALL 

METAL VENT SYSTEM SERVING A SINGLE 

DRAFT-HOOD-EQUIPPED APPLIANCE 



TILE-LINED MASONRY- 
CHIMNEY 



SINGLE-WALL VENT- 
CONNECTOR 




-- A 



EL 



^ 



/f=F 



—TYPE B DOUBLE-WALL 
COMMON VENT 



J— VENT GAP 



TYPE B DOUBLE-WALL 
GAS VENT USED AS 
CONNECTORS 




Table 504.2(4) of the International Fuel Gas Code is used when sizing a single- 
wall vent connector attached to a tile-lined masonry chimney. 

Note: "A" is the equivalent cross-sectional area of the tile liner. 

Note: The appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-4 

VENT SYSTEM SERVING A SINGLE APPLIANCE 

USING A MASONRY CHIMNEY AND A 

SINGLE-WALL METAL VENT CONNECTOR 



Table 02428.3(1) is used when sizing Type B double-wall vent connectors 
attached to a Type B double- wall common vent. 

Note: Each appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-6 

VENT SYSTEM SERVING TWO OR MORE APPLIANCES 

WITH TYPE B DOUBLE-WALL VENT AND TYPE B 

DOUBLE-WALL VENT CONNECTOR 



580 



2006 INTERNATIONAL RESIDENTIAL CODE<^ 



APPENDIX B 



-VENT CAP 



-TYPE B DOUBLE-WALL 
COMMON VENT 



TILE-LINED MASONRY 
CHIMNEY 





Table G2428.3(2) is used when sizing single-wall vent connectors attached to a 
Type B double-wall common vent. 

Note: Each appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-7 

VENT SYSTEM SERVING TWO OR MORE APPLIANCES 

WITH TYPE B DOUBLE-WALL VENT AND 

SINGLE-WALL METAL VENT CONNECTORS 



Table G2428.3(4) is used when sizing single-wall metal vent connectors 
attached to a tile-lined masonry chimney. 

Note: "A" is the equivalent cross- sectional area of the tile liner. 

Note: Each appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-9 

MASONRY CHIMNEY SERVING TWO OR MORE APPLIANCES 

WITH SINGLE-WALL METAL VENT CONNECTORS 



TYPE B DOUBLE-WALL 
H GAS VENT USED AS 
CONNECTORS 



^ 



VENT CAP 



-TILE-LINED MASONRY 
CHIMNEY 



LB 



^ 



CONNECTOR 
RISE "R" 




Table G2428.3(3) is used when sizing Type B double-wall vent connectors 

attached to a tile-lined masonry chimney. 

Note: "A" is the equivalent cross-sectional area of the tile Unen 

Note: Each appliance may be either Category I draft hood equipped or fan- 
assisted type. 

FIGURE B-8 

MASONRY CHIMNEY SERVING TWO OR MORE APPLIANCES 

WITH TYPE B DOUBLE-WALL VENT CONNECTOR 




Asbestos cement Type B or single-wall metal pipe vent serving two or more 
draft-hood-equipped appliances [see Table 504.3(5) of the International Fuel 
Gas Code]. 

FIGURE B-10 

ASBESTOS CEMENT TYPE B OR SINGLE-WALL 

METAL VENT SYSTEM SERVING TWO OR MORE 

DRAFT-HOOD-EQUIPPED APPLIANCES 



2006 INTERNATIONAL RESIDENTIAL CODE® 



581 



APPENDIX B 




r^Oi 



VENT CONNECTOR 




•COMMON VENT SIZE BASED — 
ON ALL INPUTS ENTERING THIS 
SEGMENT, AND AVAILABLE 
TOTAL HEIGHT 



MANIFOLD COMMON 
VENT CONNECTOR 



•AVAILABLE TOTAL HEIGHT 
■H' EQUALS RISE PLUS 
DISTANCE BETWEEN TEES 




Example: Manifolded Common Vent Connector L„ shall be no greater than 18 
times the common vent connector manifold inside diameter; i.e., a 4-inch (102 
mm) inside diameter common vent connector manifold shall not exceed 72 
inches (1829 mm) in length (see Section G2428.3.4). 

Note: This is an illustration of a typical manifolded vent connector. Different 
appliance, vent connector, or common vent types are possible. Consult Section 
G2426.3. 

FIGURE B-11 
USE OF MANIFOLD COMMON VENT CONNECTOR 



VENT CAP 



V777777777777777} 



Vent connector size depends on: 

• Combined inputs 

• Rise 

• Available total height "H" 

• Table G2428.3(l) connectors 



Common vent size depends on: 

• Input 

• Available total height "//" 

• Table 02428.3(1) common vent 



FIGURE B-13 

MULTISTORY GAS VENT DESIGN PROCEDURE 

FOR EACH SEGMENT OF SYSTEM 




USE INDIVIDUAL 
VENT FOR 
TOP FLOOR 
APPLIANCE IF 
CONNECTOR 
REQUIREMENT FOR 
RISE OF TOTAL 
HEIGHT CANNOT 
BE MET 



I AVAIUBLE TOTAL 
I HEIGHT FOR TOP 
FLOOR APPLIANCE 



CONNECTOR TABLE 



TOP FLOOR . 
APPLIANCE 



&. 



USE AVAILABLE TOTAL HEIGHT F( 
TOP FLOOR APPLIANCE AND 
COMBINE INPUT OF ALL APPLIAN 
ON COMMON VENT 



€h- 



AVAILABLE TOTAL 
HEIGHT FOR 
THIRD-FLOOR 
. APPLIANCE 



CONNECTOR TABLE 



THIRD FLOOR 
APPLIANCE 



s. 



^=«— 



THIRD INTERCONNECTION TEE 

-AVAILABLE TOTAL HEIGHT AND 
THIRD-FLOOR APPLIANCE AND 
COMBINED INPUT OF THREE 
APPLIANCES (IF TOP FLOOR 
APPLIANCE IS NOT CONNECTE 
MEASURED TOTAL HEIGHT TO 
VENT TOP) 

SECOND INTERCONNECTION T 



AVAILABLE TOTAL 
HEIGHT FOR 
SECOND-FLOOR 
APPLIANCE 



CONNECTOR TABLE 



SECOND-FLOOR— I- 2 
APPLIANCE 



s. 



a^ 



- USE AVAILABLE TOTAL HEIGHT 
SECOND-FLOOR APPLIANCE Al 
COMBINED HEAT INPUT OF TWi 
APPLIANCES 

FIRST INTERCONNECTION TEE 



FIRST-FLOOR - 
APPLIANCE 



Example: Offset Common Vent 

Note: This is an illustration of a typical offset vent. Different appliance, vent 
connector, or vent types are possible. Consult Sections 02428.2 and G2428.3. 

FIGURE B-12 
USE OF OFFSET COMMON VENT 




DESIGN VENT CONNECTOR;FOR FIRI 
FLOOR APPLIANCE AS AN INDIVIDUA 
VENT OF THIS TOTAL HEIGHT FOR IN 
OF FIRST FLOOR APPLIANCE 



-TEE WITH CAP OPTIONAL 



•EACH INTERCONNECTION TEE IS SAME SIZE AS THE 
SEGMENT OF COMMON VENT DIRECTLY ABOVE 



Principles of design of multistory vents using vent connector and common vent 
design tables (see Sections 02428.3.1 1 through 02428.3.13). 

FIGURE B-1 4 
MULTISTORY VENT SYSTEMS 



582 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



APPENDIX B 



^ 



TYPE B DOUBLE-WALL - 
GAS VENT 



10ft 



ELBOW 



SINGLE WALL 
CONNECTOR 




DRAFT HOOD EQUIPPED APPLIANCE 
120,000 BTU/H INPUT 



^ 



TYPE-B DOUBLE-WALL- 
GAS VENT 



-10 FT LATERAL- 



h 



30 FT 



o 



V 



^ 



VENT CONNECTOR 



FAN ASSISTED APPLIANCE 
80,000 BTU/H INPUT 



For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.293 1 W 

FIGURE B-1 5 (EXAMPLE 1) 
SINdLE DRAFT-HOOD-EQUIPPED APPLIANCE 



For SI: 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W 

FIGURE B-1 6 (EXAMPLE 2) 
SINGLE FAN-ASSISTED APPLIANCE 



Example 2: Single fan-assisted appliance. 

An installer has an 80,000 Btu per hour input fan-assisted 
appliance that must be installed using 10 feet of lateral connec- 
tor attached to a 30-foot-high Type B vent. Two 90-degree 
elbows are needed for the installation. Can a single-wall metal 
vent connector be used for this application? 

Solution: 

Table G2428.2(2) refers to the use of single-wall metal vent 
connectors with Type B vent. In the first column find the row 
associated with a 30-foot height and a 10-foot lateral. Read 
across this row, looking at the FAN Min and FAN Max col- 
umns, to find that a 3-inch-diameter single-wall metal vent 
connector is not recommended. Moving to the next larger size 
single wall connector (4 inches), note that a 4-inch-diameter 
single-wall metal connector has a recommended minimum 
vent capacity of 9 1 ,000 Btu per hour and a recommended max- 
imum vent capacity of 144,000 Btu per hour. The 80,000 Btu 
per hour fan-assisted appliance is outside this range, so the con- 
clusion is that a single-wall metal vent connector cannot be 
used to vent this appliance using 10 feet of lateral for the con- 
nector. 

However, if the 80,000 Btu per hour input appliance could be 
moved to within 5 feet of the vertical vent, then a 4-inch single- 
wall metal connector could be used to vent the appliance. Table 
G2428.2(2) shows the acceptable range of vent capacities for a 
4-inch vent with 5 feet of lateral to be between 72,000 Btu per 
hour and 157,000 Btu per hour. 



If the appliance cannot be moved closer to the vertical vent, 
then Type B vent could be used as the connector material. In 
this case. Table G2428.2(l) shows that for a 30-foot-high vent 
with 10 feet of lateral, the acceptable range of vent capacities 
for a 4-inch-diameter vent attached to a fan-assisted appliance 
is between 37,000 Btu per hour and 150,000 Btu per hour. 

Example 3: Interpolating between table values. 

An installer has an 80,000 Btu per hour input appliance with a 
4-inch-diameter draft hood outlet that needs to be vented into a 
12-foot-high Type B vent. The vent connector has a 5-foot lat- 
eral length and is also Type B. Can this appliance be vented 
using a 4-inch-diameter vent? 

Solution: 

Table G2428.2(l) is used in the case of an all Type B vent sys- 
tem. However, since there is no entry in Table G2428.2(l) for a 
height of 12 feet, interpolation must be used. Read down the 4- 
inch diameter NAT Max column to the row associated with 10- 
foot height and 5-foot lateral to find the capacity value of 
77,000 Btu per hour. Read further down to the 15-foot height, 
5-foot lateral row to find the capacity value of 87,000 Btu per 
hour. The difference between the 15-foot height capacity value 
and the 10-foot height capacity value is 10,000 Btu per hour. 
The capacity for a vent system with a 12-foot height is equal to 
the capacity for a 10-foot height plus V^ of the difference 
between the 10-foot and 15 -foot height values, or 77,000 + 2/5 
(10,000) = 81,000 Btu per hour. Therefore, a 4-inch-diameter 
vent may be used in the installadon. 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



583 



APPENDIX B 



EXAMPLES USING COMMON VENTING TABLES 

Example 4: Common venting two draft-hood-equipped 
appliances. 

A 35,000 Btu per hour water heater is to be common vented 
with a 150,000 Btu per hour furnace using a common vent with 
a total height of 30 feet. The connector rise is 2 feet for the 
water heater with a horizontal length of 4 feet. The connector 
rise for the furnace is 3 feet with a horizontal length of 8 feet. 
Assume single- wall metal connectors will be used with Type B 
vent. What size connectors and combined vent should be used 
in this installation? 

Solution: 

Table 02428.3(2) should be used to size single- wall metal vent 
connectors attached to Type B vertical vents. In the vent con- 
nector capacity portion of Table G2428.3(2), fmd the row asso- 
ciated with a 30-foot vent height. For a 2-foot rise on the vent 
connector for the water heater, read the shaded colunms for 
draft-hood-equipped appliances to fmd that a 3 -inch-diameter 
vent connector has a capacity of 37,000 Btu per hour. There- 
fore, a 3 -inch single- wall metal vent connector may be used 
with the water heater. For a draft-hood-equipped furnace with a 
3-foot rise, read across the appropriate row to fmd that a 5-inch- 
diameter vent connector has a maximum capacity of 120,000 
Btu per hour (which is too small for the furnace) and a 6-inch- 
diameter vent connector has a maximum vent capacity of 
172,000 Btu per hour. Therefore, a 6-inch-diameter vent con- 
nector should be used with the 150,000 Btu per hour furnace. 
Since both vent connector horizontal lengths are less than the 
maximum lengths listed in Section G2428.3.2, the table values 
may be used without adjustments. 



In the common vent capacity portion of Table (32428.3(2), 
fmd the row associated with a 30-foot vent height and read over 
to the NAT -i- NAT portion of the 6-inch-diameter column to 
fmd a maximum combined capacity of 257,000 Btu per hour. 
Since the two appliances total only 185,000 Btu per hour, a 6- 
inch common vent may be used. 

Example 5a: Common venting a draft-hood-equipped 
water heater with a fan-assisted furnace into a Type B vent. 

In this case, a 35,000 Btu per hour input draft-hood-equipped 
water heater with a 4-inch-diameter draft hood outlet, 2 feet of 
connector rise, and 4 feet of horizontal length is to be common 
vented with a 100,000 Btu per hour fan-assisted furnace with a 
4-inch-diameter flue collar, 3 feet of connector rise, and 6 feet 
of horizontal length. The common vent consists of a 30-foot 
height of Type B vent. What are the recommended vent diame- 
ters for each connector and the common vent? The installer 
would like to use a single-wall metal vent connector. 

Solution: - [Table G2428.3(2)] 

Water Heater Vent Connector Diameter. Since the water heater 
vent connector horizontal length of 4 feet is less than the maxi- 
mum value listed in Section G2428.3.2, the venting table val- 
ues may be used without adjustments. Using the Vent 
Connector Capacity portion of Table G2428.3(2), read down 
the Total Vent Height (H) column to 30 feet and read across the 
2-foot Connector Rise (R) row to the first Btu per hour rating in 
the NAT Max column that is equal to or greater than the water 
heater input rating. The table shows that a 3-inch vent connec- 
tor has a maximum input rating of 37,000 Btu per hour. 
Although this is greater than the water heater input rating, a 3- 
inch vent connector is prohibited by Section G2428.3.17. A 4- 



C 



^ 



COMBINED CAPACITY 

35,000 + 1 50,000 = 1 85,000 BTU/H 



-Pr-PE B DOUBLE-WALL 
GAS VENT 



SINGLE WALL 
CONNECTORS 




DRAFT HOOD-EQUIPPED 

WATER HEATER 

35,000 BTU/H INPUT 



DRAFT HOOD-EQUIPMENT 

FURNACE 

150,000 BTU/H INPUT 



TYPE B DOUBLE-WALL - 
GAS VENT 



COMBINED CAPACITY 

35,000 -f 1 00,000 = 1 35,000 BTU/H 




FIGURE B-17 (EXAMPLE 4) 
COMMON VENTING TWO DRAFT- 
HOOD-EQUIPPED APPLIANCES 



FIGURE B-18 (EXAMPLE 5A) 

COMMON VENTING A DRAFT HOOD WITH A FAN-ASSISTED 

FURNACE INTO A TYPE B DOUBLE-WALL COMMON VENT 



584 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



APPENDIX B 



inch vent connector has a maximum input rating of 67,000 Btu 
per hour and is equal to the draft hood outlet diameter. A 4-inch 
vent connector is selected. Since the water heater is equipped 
with a draft hood, there are no minimum input rating restric- 
tions. 

Furnace Vent Connector Diameter. Using the Vent Connec- 
tor Capacity portion of Table G2428.3(2), read down the Total 
Vent Height (//) column to 30 feet and across the 3-foot Con- 
nector Rise (R) row. Since the furnace has a fan-assisted com- 
bustion system, find the first FAN Max column with a Btu per 
hour rating greater than the furnace input rating. The 4-inch 
vent connector has a maximum input rating of 1 19,000 Btu per 
hour and a minimum input rating of 85,000 Btu per hour. The 
100,000 Btu per hour furnace in this example falls within this 
range, so a 4-inch connector is adequate. Since the furnace vent 
connector horizontal length of 6 feet does not exceed the maxi- 
mum value hsted in Section G2428.3.2, the venting table val- 
ues may be used without adjustment. If the furnace had an input 
rating of 80,000 Btu per hour, then a Type B vent connector 
[see Table G2428.3(l)] would be needed in order to meet the 
minimum capacity limit. 

Common Vent Diameter. The total input to the common vent 
is 135,000 Btu per hour. Using the Common Vent Capacity 
portion of Table G2428.3(2), read down the Total Vent Height 
(H) column to 30 feet and across this row to find the smallest 
vent diameter in the FAN -i- NAT column that has a Btu per hour 
rating equal to or greater than 135,000 Btu per hour. The 4-inch 
common vent has a capacity of 1 32,000 Btu per hour and the 5- 
inch common vent has a capacity of 202,000 Btu per hour. 
Therefore, the 5 -inch common vent should be used in this 
example. 

Summary. In this example, the installer may use a 4-inch- 
diameter, single- wall metal vent connector for the water heater 
and a 4-inch-diameter, single- wall metal vent connector for the 
furnace. The common vent should be a 5 -inch-diameter Type B 
vent. 

Example 5b: Common venting into a masonry chimney. 

In this case, the water heater and fan-assisted furnace of Exam- 
ple 5 a are to be common vented into a clay tile-lined masonry 
chimney with a 30-foot height. The chimney is not exposed to 
the outdoors below the roof line. The internal dimensions of the 
clay tile liner are nominally 8 inches by 12 inches. Assuming 
the same vent connector heights, laterals, and materials found 
in Example 5a, what are the recommended vent connector 
diameters, and is this an acceptable installation? 

Solution: 

Table G2428.3(4) is used to size common venting installations 
involving single- wall connectors into masonry chimneys. 

Water Heater Vent Connector Diameter. Using Table 
G2428.3(4), Vent Connector Capacity, read down the Total 
Vent Height (H) column to 30 feet, and read across the 2-foot 
Connector Rise (R) row to the first Btu per hour rating in the 
NAT Max column that is equal to or greater than the water 
heater input rating. The table shows that a 3-inch vent connec- 
tor has a maximum input of only 3 1 ,000 Btu per hour while a 4- 
inch vent connector has a maximum input of 57,000 Btu per 
hour. A 4-inch vent connector must therefore be used. 



Furnace Vent Connector Diameter. Using the Vent Connec- 
tor Capacity portion of Table G2428.3(4), read down the Total 
Vent Height (H) column to 30 feet and across the 3-foot Con- 
nector Rise (R) row. Since the furnace has a fan-assisted com- 
bustion system, find the first FAN Max column with a Btu per 
hour rating greater than the furnace input rating. The 4-inch 
vent connector has a maximum input rating of 127,000 Btu per 
hour and a minimum input rating of 95,000 Btu per hour. The 
100,000 Btu per hour furnace in this example falls within this 
range, so a 4-inch connector is adequate. 

Masonry Chimney. From Table B- 1 , the equivalent area for a 
nominal liner size of 8 inches by 12 inches is 63.6 square 
inches. Using Table G2428.3(4), Common Vent Capacity, read 
down the FAN -i- NAT column under the Minimum Internal 
Area of Chimney value of 63 to the row for 30-foot height to 
find a capacity value of 739,000 Btu per hour. The combined 
input rating of the furnace and water heater, 135,000 Btu per 
hour, is less than the table value, so this is an acceptable instal- 
lation. 

Section G2428.3.13 requires the common vent area to be no 
greater than seven times the smallest listed appliance catego- 
rized vent area, flue collar area, or draft hood outlet area. Both 
appliances in this installation have 4-inch-diameter outlets. 
From Table B-1, the equivalent area for an inside diameter of 4 
inches is 12.2 square inches. Seven times 12.2 equals 85.4, 
which is greater than 63.6, so this configuration is acceptable. 

Example 5c: Common venting into an exterior masonry 
chimney. 

In this case, the water heater and fan-assisted furnace of Exam- 
ples 5 a and 5b are to be common vented into an exterior 
masonry chimney. The chimney height, clay tile liner dimen- 
sions, and vent connector heights and laterals are the same as in 
Example 5b. This system is being installed in Charlotte, North 
Carolina. Does this exterior masonry chimney need to be 
relined? If so, what corrugated metallic liner size is recom- 
mended? What vent connector diameters are recommended? 

Solution: 

According to Section 504.3.20 of the International Fuel Gas 
Code, Type B vent connectors are required to be used with 
exterior masonry chimneys. Use Table 504.3(7) of the Interna- 
tional Fuel Gas Code to size FAN-i-NAT common venting 
installations involving Type-B double wall connectors into 
exterior masonry chimneys. 

The local 99-percent winter design temperature needed to 
use Table 504.3(7) can be found in the ASHRAE Handbook of 
Fundamentals. For Charlotte, North Carolina, this design tem- 
perature is 19°F. 

Chimney Liner Requirement. As in Example 5b, use the 63 
square inch Internal Area columns for this size clay tile liner. 
Read down the 63 square inch column of Table 504.3(7a) of the 
International Fuel Gas Code to the 30-foot height row to find 
that the combined appliance maximum input is 747,000 Btu 
per hour. The combined input rating of the appliances in this 
installation, 135,000 Btu per hour, is less than the maximum 
value, so this criterion is satisfied. Table 504.3(7b), at a 19°F 
design temperature, and at the same vent height and internal 
area used above, shows that the minimum allowable input rat- 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



585 



APPENDIX B 



ing of a space-heating appliance is 470,000 Btu per hour. The 
furnace input rating of 100,000 Btu per hour is less than this 
minimum value. So this criterion is not satisfied, and an alter- 
native venting design needs to be used, such as a Type B vent 
shown in Example 5a or a listed chimney liner system shown in 
the remainder of the example. 

According to Section G2428.3.15, Table G2428.3(l) or 
G2428.3(2) is used for sizing corrugated metallic liners in 
masonry chimneys, with the maximum common vent capaci- 
ties reduced by 20 percent. This example will be continued 
assuming Type B vent connectors. 

Water Heater Vent Connector Diameter. Using Table 
02428.3(1), Vent Connector Capacity, read down the Total 
Vent Height (H) column to 30 feet, and read across the 2-foot 
Connector Rise (R) row to the first Btu/h rating in the NAT Max 
column that is equal to or greater than the water heater input rat- 
ing. The table shows that a 3 -inch vent connector has a maxi- 
mum capacity of 39,000 Btu/h. Although this rating is greater 
than the water heater input rating, a 3-inch vent connector is 
prohibited by Section G2428.3.17. A 4-inch vent connector 
has a maximum input rating of 70,000 Btu/h and is equal to the 
draft hood outiet diameter. A 4-inch vent connector is selected. 

Furnace Vent Connector Diameter. Using Table G2428.3(l), 
Vent Connector Capacity, read down the Vent Height (//) col- 
umn to 30 feet, and read across the 3-foot Connector Rise (R) 
row to the first Btu per hour rating in the FAN Max column that 
is equal to or greater than the furnace input rating. The 100,000 
Btu per hour furnace in this example falls within this range, so a 
4-inch connector is adequate. 

Chimney Liner Diameter. The total input to the common 
vent is 135,000 Btu per hour. Using the Common Vent Capac- 
ity Portion of Table 02428.3(1), read down the Vent Height (H) 
column to 30 feet and across this row to find the smallest vent 
diameter in the FAN+NAT column that has a Btu per hour rat- 
ing greater than 135,000 Btu per hour. The 4-inch common 
vent has a capacity of 1 38,000 Btu per hour. Reducing the max- 
imum capacity by 20 percent (Section 02428.3.15) results in a 
maximum capacity for a 4-inch corrugated liner of 1 10,000 Btu 
per hour, less than the total input of 135,000 Btu per hour. So a 
larger liner is needed. The 5-inch common vent capacity listed 
in Table 02428.3(1) is 210,000 Btu per hour, and after reduc- 
ing by 20 percent is 168,000 Btu per hour. Therefore, a 5-inch 
corrugated metal liner should be used in this example. 

Single-Wall Connectors. Once it has been established that 
relining the chimney is necessary, Type B double-wall vent 
connectors are not specifically required. This example could be 
redone using Table 02428.3(2) for single- wall vent connec- 
tors. For this case, the vent connector and liner diameters would 
be the same as found above with Type B double-wall connec- 
tors. 



TABLE B-1 

MASONRY CHIMNEY LINER DIMENSIONS 

WITH CIRCULAR EQUIVALENTS" 



NOMINAL LINER 
SIZE (inches) 


INSIDE 

DIMENSIONS OF 

LINER (Inches) 


INSIDE 

DIAMETER OR 

EQUIVALENT 

DIAMETER 

(inches) 


EQUIVALENT 

AREA 

(square inches) 


4x8 


2V2 X 6V2 


4 


: 12.2 


5 


19.6 


6 


: 28.3 


7 


: 38.3 


8x8 


6V4 X 6^/4 


7.4 


42.7 


8 


' 50.3 


8x12 


6V2 X IOV2 


9 


63.6 


10 


78.5 


12x12 


93/4 X 9V4 


10.4 


83.3 


11 


95 


12x16 


9'/2Xl3V2 


11.8 


107.5 


12 


113.0 


14 


153.9 


16x16 


13'/4Xl3V4 


14.5 


162.9 


15 


176.7 


16x20 


13x17 


16.2 


[ 206.1 


18 


254.4 


20x20 


I6V4 X I6V4 


18.2 


260.2 


20 


314.1 


20x24 


16V2x20'/2 


20.1 


314.2 


22 


380.1 


24x24 


2OV4 X 20V4 


22.1 


380.1 


24 


452.3 


24x28 


2OV4 X 20V4 


24.1 


456.2 


28x28 


24 V4 X 24'/4 


26.4 


543.3 


27 


572.5 


30x30 


25'/2x25V2 


27.9 


607 


30 


706.8 


30x36 


25V2x31'/2 


30.9 


749.9 


33 


855.3 


36x36 


3l'/2X3l'/2 


34.4 


929.4 


36 


: 1017.9 



For SI: 1 inch = 25.4 mm, I square inch = 645.16 mm^. 

a. Where Hner sizes differ dimensionally from those shown in Table B-1, 
equivalent diameters may be determined from published tables for square 
and rectangular ducts of equivalent carrying capacity or by other engineering 
methods. 



586 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



z 


5°F 


l- 
73 


(-15°C) 


m 
w 


17T_^ 


a 
m 


(-8°C) 


^ 


z 






H 


I 


> 


K 


r- 


i\/ 


o 
o 

D 
m 


2rF / / 


(-3°C) / 





-10T 
(-23°C) 



37° F 

(3°C) 




-10T 
(-23°C) 



37° F 

(3°C) 



FIGURE B-19 



588 2006 INTERNATIONAL RESIDENTIAL CODE 



® 



APPENDIX C (IFGS) 

EXIT TERMINALS OF MECHANICAL DRAFT AND 
DIRECT-VENT VENTING SYSTEMS 

(This appendix is informative and is not part of the code. This appendix is an excerpt from the 
2006 International Fuel Gas Code, coordinated with the section numbering of the International Residential Code.) 



DIRECT VENT TERMINAL 

INPUT (BTU/HR) CLEARANCE (M) 

10.000 OR LESS 

10.001 TO 50,000 
OVER 50,000 
[SEE SECTION G2427.8, 
ITEM 3] 

MECHANICAL DRAFT VENT 
TERMINAL [SEE SECTION 
G2427.8, ITEM 2] 




^MECHANICAL DRAFT 
VENT TERMINAL 
[SEE SECTION 
G2427.8, ITEM 1] 



GRADE 
3 FT MIN. 

FORCED AIR INLET 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per hour = 0.2931 W 

APPENDIX C 
EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT VENTING SYSTEMS 



2006 INTERNATIONAL RESIDENTIAL CODE' 



.® 



589 



590 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX D (IFGS) 

RECOMMENDED PROCEDURE FOR SAFETY INSPECTION OF AN 
EXISTING APPLIANCE INSTALLATION 



(This appendix is informative and is not part of the code. This appendix is an excerpt from the 
2006 International Fuel Gas Code, coordinated with the section numbering of the International Residential Code.) 



The following procedure is intended as a guide to aid in deter- 
mining that an appliance is properly installed and is in a safe 
condition for continuing use. 

This procedure is predicated on central furnace and boiler 
installations, and it should be recognized that generalized pro- 
cedures cannot anticipate all situations. Accordingly, in some 
cases, deviation from this procedure is necessary to determine 
safe operation of the equipment. 

(a) This procedure should be performed prior to any 
attempt at modification of the appliance or of the instal- 
lation. 

(b) If it is determined there is a condition that could result in 
unsafe operation, the appliance should be shut off and 
the owner advised of the unsafe condition. 

The following steps should be followed in making the safety 
inspection: 

1 . Conduct a check for gas leakage. (See Section G24 17.6.) 

2. Visually inspect the venting system for proper size and 
horizontal pitch and determine there is no blockage or 
restriction, leakage, corrosion and other deficiencies 
that could cause an unsafe condition. 

3. Shut off all gas to the appliance and shut off any other 
fuel-gas-buming appliance within the same room. Use 
the shut-off valve in the supply line to each appli- 
ance. 

4. Inspect burners and crossovers for blockage and corro- 
sion. 

5. Applicable only to furnaces. Inspect the heat 
exchanger for cracks, openings or excessive corrosion. 

6. Applicable only to boilers. Inspect for evidence of 
water or combustion product leaks. 

7. Insofar as is practical, close all building doors and win- 
dows and all doors between the space in which the 
appliance is located and other spaces of the building. 
Turn on clothes dryers. Turn on any exhaust fans, such 
as range hoods and bathroom exhausts, so they will 
operate at maximum speed. Do not operate a summer 
exhaust fan. Close fireplace dampers. If, after complet- 
ing Steps 8 through 13, it is believed sufficient combus- 
tion air is not available, refer to Section G2407 of this 
code for guidance. 

8. Place the appliance being inspected in operation. Fol- 
low the lighting instructions. Adjust the thermostat so 
appliance will operate continuously. 



9. Determine that the pilot(s), where provided, is burning 
properly and that the main burner ignition is satisfactory 
by interrupting and reestablishing the electrical supply 
to the appliance in any convenient manner. If the appli- 
ance is equipped with a continuous pilot(s), test the pilot 
safety device(s) to determine if it is operating properly 
by extinguishing the pilot(s) when the main burner(s) is 
off and determining, after 3 minutes, that the main 
burner gas does not flow upon a call for heat. If the 
appliance is not provided with a pilot(s), test for proper 
operation of the ignition system in accordance with the 
appliance manufacturer's lighting and operating 
instructions. 

10. Visually determine that the main burner gas is burning 
properly (i.e., no floating, lifting, or flashback). Adjust 
the primary air shutter(s) as required. 

If the appliance is equipped with high and low flame 
controlling or flame modulation, check for proper main 
burner operation at low flame. 

1 1 . Test for spillage at the draft hood relief opening after 5 
minutes of main burner operation. Use a flame of a 
match or candle or smoke. 

12. Turn on all other fuel-gas-buming appliances within the 
same room so they will operate at their full inputs. Fol- 
low lighting instructions for each appliance. 

13. Repeat Steps 10 and 11 on the appliance being 
inspected. 

14. Return doors, windows, exhaust fans, fireplace damp- 
ers and any other fuel-gas-buming appliance to their 
previous conditions of use. 

15. Applicable only to furnaces. Check both the limit con- 
trol and the fan control for proper operation. Limit con- 
trol operation can be checked by blocking the 
circulating air inlet or temporarily disconnecting the 
electrical supply to the blower motor and determining 
that the limit control acts to shut off the main bumer gas. 

16. Applicable only to boilers. Determine that the water 
pumps are in operating condition. Test low water cut- 
offs, automatic feed controls, pressure and temperature 
limit controls, and relief valves in accordance with the 
manufacturer's recommendations to determine that 
they are in operating condition. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



591 



592 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX E 

MANUFACTURED HOUSING USED AS DWELLINGS 



SECTION AE1 01 
SCOPE 

AElOl.l General. These provisions shall be applicable only 
to a manufactured home used as a single dwelling unit installed 
on privately owned (nonrental) lots and shall apply to the fol- 
lowing: 

1. Construction, alteration and repair of any foundation 
system which is necessary to provide for the installation 
of a manufactured home unit. 

2. Construction, installation, addition, alteration, repair or 
maintenance of the building service equipment which is 
necessary for connecting manufactured homes to water, 
fuel, or power supplies and sewage systems. 

3. Alterations, additions or repairs to existing manufac- 
tured homes. The construction, alteration, moving, 
demolition, repair and use of accessory buildings and 
structures and their building service equipment shall 
comply with the requirements of the codes adopted by 
this jurisdiction. 

These provisions shall not be applicable to the design and 
construction of manufactured homes and shall not be deemed 
to authorize either modifications or additions to manufactured 
homes where otherwise prohibited. 

Exception: In addition to these provisions, new and 
replacement manufactured homes to be located in flood 
hazard areas as established in Table R301 .2(1) of the Inter- 
national Residential Code shall meet the applicable require- 
ments of Sections R324 of the International Residential 
Code. 



SECTION AE1 02 
APPLICATION TO EXISTING MANUFACTURED 
HOMES AND BUILDING SERVICE EQUIPMENT 

AE102.1 GeneraL Manufactured homes and their building 
service equipment to which additions, alterations or repairs are 
made shall comply with all the requirements of these provi- 
sions for new facilities, except as specifically provided in this 
section. 

AE102.2 Additions, alterations or repairs. Additions made 
to a manufactured home shall conform to one of the following: 

1. Be certified under the National Manufactured Housing 
Construction and Safety Standards Act of 1974 (42 
U.S.C. Section 5401, et seq.). 

2. Be designed and constructed to conform with the appli- 
cable provisions of the National Manufactured Housing 
Construction and Safety Standards Act of 1974 (42 
U.S.C. Section 5401, et seq.). 

3. Be designed and constructed in conformance with the 
code adopted by this jurisdiction. 



Additions shall be structurally separated from the manufac- 
tured home. 

Exception: A structural separation need not be provided 
when structural calculations are provided to justify the 
omission of such separation. 

Alterations or repairs may be made to any manufactured 
home or to its building service equipment without requiring the 
existing manufactured home or its building service equipment 
to comply with all the requirements of these provisions, pro- 
vided the alteration or repair conforms to that required for new 
construction, and provided further that no hazard to life, health 
or safety will be created by such additions, alterations or 
repairs. 

Alterations or repairs to an existing manufactured home 
which are nonstructural and do not adversely affect any struc- 
tural member or any part of the building or structure having 
required fire protection may be made with materials equivalent 
to those of which the manufactured home structure is con- 
structed, subject to approval by the building official. 

Exception: The installation or replacement of glass shall be 
required for new installations. 

Minor additions, alterations and repairs to existing building 
service equipment installations may be made in accordance 
with the codes in effect at the time the original installation was 
made subject to approval of the building official, and provided 
such additions, alterations and repairs will not cause the exist- 
ing building service equipment to become unsafe, insanitary or 
overloaded. 

AE102.3 Existing installations. Building service equipment 
lawfully in existence at the time of the adoption of the applica- 
ble codes may have their use, maintenance or repair continued 
if the use, maintenance or repair is in accordance with the origi- 
nal design and no hazard to life, health or property has been 
created by such building service equipment. 

AE 102.4 Existing occupancy. Manufactured homes which 
are in existence at the time of the adoption of these provisions 
may have their existing use or occupancy continued if such use 
or occupancy was legal at the time of the adoption of these pro- 
visions, provided such continued use is not dangerous to life, 
health and safety. 

The use or occupancy of any existing manufactured home 
shall not be changed unless evidence satisfactory to the build- 
ing official is provided to show compliance with all applicable 
provisions of the codes adopted by this jurisdiction. Upon any 
change in use or occupancy, the manufactured home shall cease 
to be classified as such within the intent of these provisions. 

AE102.5 Maintenance. All manufactured homes and their 
building service equipment, existing and new, and all parts 
thereof shall be maintained in a safe and sanitary condition. All 
device or safeguards which are required by applicable codes or 
by the Manufactured Home Standards shall be maintained in 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



593 



APPENDIX E 



conformance with the code or standard under which it was 
installed. The owner or the owner's designated agent shall be 
responsible for the maintenance of manufactured homes, 
accessory buildings, structures and their building service 
equipment. To determine compliance with this subsection, the 
building official may cause any manufactured home, accessory 
building or structure to be reinspected. 

AE102.6 Relocation. Manufactured homes which are to be 
relocated within this jurisdiction shall comply with these provi- 
sions. 



SECTION AE201 
DEFINITIONS 

AE201.1 General. For the purpose of these provisions, certain 
abbreviations, terms, phrases, words and their derivatives shall 
be construed as defined or specified herein. 

ACCESSORY BUILDING. Any building or structure, or por- 
tion thereto, located on the same property as a manufactured 
home which does not qualify as a manufactured home as 
defined herein. 

BUILDING SERVICE EQUIPMENT. Refers to the plumb- 
ing, mechanical and electrical equipment including piping, 
wiring, fixtures and other accessories which provide sanita- 
tion, lighting, heating ventilation, cooling, fire protection and 
facilities essential for the habitable occupancy of a manufac- 
tured home or accessory building or structure for its designated 
use and occupancy. 

MANUFACTURED HOME. A structure transportable in one 
or more sections which, in the traveling mode, is 8 body feet 
(2438 body mm) or more in width or 40 body feet (12 192 body 
mm) or more in length or, when erected on site, is 320 or more 
square feet (30 m^), and which is built on a permanent chassis 
and designed to be used as a dwelling with or without a perma- 
nent foundation when connected to the required utilities, and 
includes the plumbing, heating, air-conditioning and electrical 
systems contained therein; except that such term shall include 
any structure which meets all the requirements of this para- 
graph except the size requirements and with respect to which 
the manufacturer voluntarily files a certification required by 
the secretary (HUD) and complies with the standards estab- 
lished under this title. 

For mobile homes built prior to June 15, 1976, a label certi- 
fying compliance to the Standard for Mobile Homes, NFPA 
501, ANSI 119.1, in effect at the time of manufacture is 
required. For the purpose of these provisions, a mobile home 
shall be considered a manufactured home. 

MANUFACTURED HOME INSTALLATION. Construc- 
tion which is required for the installation of a manufactured 
home, including the construction of the foundation system, 
required structural connections thereto and the installation of 
on-site water, gas, electrical and sewer systems and connec- 
tions thereto which are necessary for the normal operation of 
the manufactured home. 

MANUFACTURED HOME STANDARDS. The Manufac- 
tured Home Construction and Safety Standards as promulgated 



by the United States Department of Housing and Urban Devel- 
opment. 

PRIVATELY OWNED (NONRENTAL) LOT. A parcel of 
real estate outside of a manufactured home rental community 
(park) where the land and the manufactured home to be 
installed thereon are held in common ownership. 



SECTION AE301 ! 

PERMITS 

AE301.1 Initial installation. A manufactured home shall not 
be installed on a foundation system reinstalled or altered with- 
out first obtaining a permit from the building official. A sepa- 
rate permit shall be required for each manufactured home 
installation. When approved by the building oflicial, such per- 
mit may include accessory buildings and structures and their 
building service equipment when the accessory buildings or 
structures will be constructed in conjunction with the manufac- 
tured home installation. 

AE301.2 Additions, alterations and repairs to a manufac- 
tured home. A permit shall be obtained to alter, remodel, 
repair or add accessory buildings or structures to a manufac- 
tured home subsequent to its initial installation. Permit issu- 
ance and fees therefor shall be in conformance with the codes 
applicable to the type of work involved. 

An addition made to a manufactured home as defined in 
these provisions shall comply with these provisions. 

AE301.3 Accessory buildings. Except as provided in Section 
AE301.1, permits shall be required for all accessory buildings 
and structures and their building service equipment. Permit 
issuance and fees therefor shall be in conformance with the 
codes applicable to the types of work involved. 

AE301.4 Exempted work. A permit shall not be required for 
the types of work specifically exempted by the applicable 
codes. Exemption from the permit requirements of any of said 
codes shall not be deemed to grant authorization for any work 
to be done in violation of the provisions of said codes or any 
other laws or ordinances of this jurisdiction. 



SECTION AE302 
APPLICATION FOR PERMIT 

AE302.1 Application. To obtain a manufactured home instal- 
lation permit, the applicant shall first file an application in writ- 
ing on a form furnished by the building oificial for that 
purpose. At the option of the building official, every such appli- 
cation shall: 

1 . Identify and describe the work to be covered by the per- 
mit for which application is made. 

2. Describe the land on which the proposed work is to be 
done by legal description, street address or similar 
description that will readily identify and definitely locate 
the proposed building or work. 

3. Indicate the use or occupancy for which the proposed 
work is intended. 



594 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX E 



4. Be accompanied by plans, diagrams, computations and 
specifications and other data as required in Section 
AE302.2. 

5 . Be accompanied by a soil investigation when required by 
Section AE502.2. 

6. State the valuation of any new building or structure or 
any addition, remodeling or alteration to an existing 
building. 

7. Be signed by permittee, or permittee's authorized agent, 
who may be required to submit evidence to indicate such 
authority. 

8. Give such other data and information as may be required 
by the building official. 

AE302.2 Plans and specifications. Plans, engineering calcu- 
lations, diagrams and other data as required by the building 
official shall be submitted in not less than two sets with each 
application for a permit. The building official may require 
plans, computations and specifications to be prepared and 
designed by an engineer or architect licensed by the state to 
practice as such. 

Where no unusual site conditions exist, the building official 
may accept approved standard foundation plans and details in 
conjunction with the manufacturer's approved installation 
instructions without requiring the submittal of engineering cal- 
culations. 

AE302.3 Information on plans and specifications. Plans and 
specifications shall be drawn to scale on substantial paper or 
cloth and shall be of sufficient clarity to indicate the location, 
nature and extent of the work proposed and shown in detail that 
it will conform to the provisions of these provisions and all rel- 
evant laws, ordinances, rules and regulations. The building 
official shall determine what information is required on plans 
and specifications to ensure compliance. 



SECTION AE303 
PERMITS ISSUANCE 

AE303.1 Issuance. The application, plans and specifications 
and other data filed by an applicant for permit shall be reviewed 
by the building official. Such plans may be reviewed by other 
departments of this jurisdiction to verify compliance with any 
applicable laws under their jurisdiction. If the building official 
finds that the work described in an application for a permit and 
the plans, specifications and other data filed therewith conform 
to the requirements of these provisions and other data filed 
therewith conform to the requirements of these provisions and 
other pertinent codes, laws and ordinances, and that the fees 
specified in Section AE304 have been paid, the building offi- 
cial shall issue a permit therefor to the applicant. 

When the building official issues the permit where plans are 
required, the building official shall endorse in writing or stamp 
the plans and specifications APPROVED. Such approved plans 
and specifications shall not be changed, modified or altered 
without authorization from the building official, and all work 
shall be done in accordance with the approved plans. 

AE303.2 Retention of plans. One set of approved plans and 
specifications shall be returned to the applicant and shall be 



kept on the site of the building or work at all times during which 
the work authorized thereby is in progress. One set of approved 
plans, specification and computations shall be retained by the 
building official until final approval of the work. 

AE303.3 Validity of permit. The issuance of a permit or 
approval of plans and specifications shall shall not be construed 
to be a permit for, or an approval of, any violation of any of the 
provisions of these provisions or other pertinent codes of any 
other ordinance of the jurisdiction. No permit presuming to give 
authority to violate or cancel these provisions shall be valid. 

The issuance of a permit based on plans, specifications and 
other data shall not prevent the building official from thereafter 
requiring the correction of errors in said plans, specifications 
and other data, or from preventing building operations being 
carried on thereunder when in violation of these provisions or 
of any other ordinances of this jurisdiction. 

AE303.4 Expiration. Every permit issued by the building offi- 
cial under these provisions shall expire by limitation and 
become null and void if the work authorized by such permit is 
not commenced within 180 days from the date of such permit, 
or if the work authorized by such permit is suspended or aban- 
doned at any time after the work is commenced for a period of 
180 days. Before such work can be recommenced, a new per- 
mit shall be first obtained, and the fee therefor shall be one-half 
the amount required for a new permit for such work, provided 
no changes have been made or will be made in the original 
plans and specifications for such work, and provided further 
that such suspension or abandonment has not exceeded one 
year. In order to renew action on a permit after expiration, the 
permittee shall pay a new full permit fee. 

Any permittee holding an unexpired permit may apply for an 
extension of the time within which work may commence under 
that permit when the permittee is unable to commence work 
within the time required by this section for good and satisfac- 
tory reasons. The building official may extend the time for 
action by the permittee for a period not exceeding 180 days 
upon written request by the permittee showing that circum- 
stances beyond the control of the permittee have prevented 
action from being taken. No permit shall be extended more than 
once. 

AE303.5 Suspension or revocation. The building official 
may, in writing, suspend or revoke a permit issued under these 
provisions whenever the permit is issued in error or on the basis 
of incorrect information supplied, or in violation of any ordi- 
nance or regulation or any of these provisions. 



SECTION AE304 
FEES 

AE304.1 Permit fees. The fee for each manufactured home 
installation permit shall be estabhshed by the building official. 

When permit fees are to be based on the value or valuation of 
the work to be performed, the determination of value or valua- 
tion under these provisions shall be made by the building offi- 
cial. The value to be used shall be the total value of all work 
required for the manufactured home installation plus the total 
value of all work required for the construction of accessory 
buildings and structures for which the permit is issued as well 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



595 



APPENDIX E 



as all finish work, painting, roofing, electrical, plumbing, heat- 
ing, air conditioning, elevators, fire-extinguishing systems and 
any other permanent equipment which is a part of the accessory 
building or structure. The value of the manufactured home 
itself shall not be included. 

AE304.2 Plan review fees. When a plan or other data are 
required to be submitted by Section AE302.2, a plan review fee 
shall be paid at the time of submitting plans and specifications 
for review. Said plan review fee shall be as established by the 
building official. Where plans are incomplete or changed so as 
to require additional plan review, an additional plan review fee 
shall be charged at a rate as established by the building official. 

AE304.3 Other provisions. 

AE304.3.1 Expiration of plan review. Applications for 
which no permit is issued within 180 days following the 
date of application shall expire by limitation, and plans and 
other data submitted for review may thereafter be returned 
to the applicant or destroyed by the building official. The 
building official may extend the time for action by the appli- 
cant for a period not exceeding 1 80 days upon request by the 
applicant showing that circumstances beyond the control of 
the applicant have prevented action from being taken. No 
application shall be extended more than once. In order to 
renew action on an application after expiration, the appli- 
cant shall resubmit plans and pay a new plan review fee. 

AE304.3.2 Investigation fees: work without a permit. 

AE304.3.2.1 Investigation. Whenever any work for 
which a permit is required by these provisions has been 
commenced without first obtaining said permit, a special 
investigation shall be made before a permit may be 
issued for such work. 

AE304.3.2.2 Fee. An investigation fee, in addition to the 
permit fee, shall be collected whether or not a permit is 
then or subsequently issued. The investigation fee shall 
be equal to the amount of the permit fee required. The 
minimum investigation fee shall be the same as the mini- 
mum fee established by the building official. The pay- 
ment of such investigation fee shall not exempt any 
person from compliance with all other provisions of 
either these provisions or other pertinent codes or from 
any penalty prescribed by law. 

E304.3.3 Fee refunds. 

AE304.3.3.1 Permit fee erroneously paid or collected. 

The building official may authorize the refunding of any fee 
paid hereunder which was erroneously paid or collected. 

AE304.3.3.2 Permit fee paid when no work done. The 

building official may authorize the refunding of not more 
than 80 percent of the permit fee paid when no work has 
been done under a permit issued in accordance with these 
provisions. 

AE304.3.3.3 Plan review fee. The building official may 
authorize the refunding of not more than 80 percent of 
the plan review fee paid when an application for a permit 
for which a plan review fee has been paid is withdrawn or 
canceled before any plan reviewing is done. 



The building official shall not authorize the refunding 
of any fee paid except upon written application by the 
original permittee not later than 1 80 days after the date of 
the fee payment. 



SECTION AE305 
INSPECTIONS 

AE305.1 General. All construction or work for which a manu- 
factured home installation permit is required shall be subject to 
inspection by the building official, and certain types of con- 
struction shall have continuous inspection by special inspec- 
tors as specified in Section AE306. A survey of the lot may be 
required by the building official to verify that the structure is 
located in accordance with the approved plans. 

It shall be the duty of the permit applicant to cause the work 
to be accessible and exposed for inspection purposes. Neither 
the building official nor this jurisdiction shall be liable for 
expense entailed in the removal or replacement of any material 
required to allow inspection. 

AE305.2 Inspection requests. It shall be the duty of the person 
doing the work authorized by a manufactured home installa- 
tion permit to notify the building official that such work is 
ready for inspection. The building official may require that 
every request for inspection be filed at least one working day 
before such inspection is desired. Such request may be in writ- 
ing or by telephone at the option of the building official. 

It shall be the duty of the person requesting any inspections 
required either by these provisions or other apphcable codes to 
provide access to and means for proper inspection of such work. 

AE305.3 Inspection record card. Work requiring a manufac- 
tured home installation permit shall not be commenced until 
the permit holder or the permit holder's agent shall have posted 
an inspection record card in a conspicuous place on the pre- 
mises and in such position as to allow the building official con- 
veniently to make the required entries thereon regarding 
inspection of the work. This card shall be maintained in such 
position by the permit holder until final approval has been 
issued by the building official. 

AE305.4 Approval required. Work shall not be done on any 
part of the manufactured home installation beyond the point 
indicated in each successive inspection without first obtaining 
the approval of the building official. Such approval shall be 
given only after an inspection has been made of each succes- 
sive step in the construction as indicated by each of the inspec- 
tions required in Section AE305.5. There shall be a final 
inspection and approval of the manufactured home installation, 
including connections to its building service equipment, when 
completed and ready for occupancy or use. 

AE305.5 Required inspections. 

AE305.5.1 Structural inspections for the manufactured 
home installation. Reinforcing steel or structural frame- 
work of any part of any manufactured home foundation sys- 
tem shall not be covered or concealed without first obtaining 
the approval of the building official. The building official, 
upon notification from the permit holder or the permit 
holder's agent, shall make the following inspections and 



596 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX E 



shall either approve that portion of the construction as com- 
pleted or shall notify the permit holder or the permit holder's 
agent wherein the same fails to comply with these provi- 
sions or other applicable codes: 

1. Foundation inspection: To be made after excavations 
for footings are completed and any required reinforc- 
ing steel is in place. For concrete foundations, any 
required forms shall be in place prior to inspection. 
All materials for the foundation shall be on the job, 
except where concrete from a central mixing plant 
(commonly termed "transit mixed") is to be used, the 
concrete materials need not be on the job. Where the 
foundation is to be constructed of approved treated 
wood, additional framing inspections as required by 
the building official may be required. 

2. Concrete slab or under-floor inspection: To be made 
after all in-slab or underfloor building service equip- 
ment, conduit, piping accessories and other ancillary 
equipment items are in place but before any concrete 
is poured or the manufactured home is installed. 

3 . Anchorage inspection: To be made after the manufac- 
tured home has been installed and permanently 
anchored. 

AE305.5.2 Structural inspections for accessory building 
and structures. Inspections for accessory buildings and 
structures shall be made as set forth in this code. 

AE305.5.3 Building service equipment inspections. All 

building service equipment which is required as a part of a 
manufactured home installation, including accessory build- 
ings and structures authorized by the same permit, shall be 
inspected by the building official. Building service equip- 
ment shall be inspected and tested as required by the appli- 
cable codes. Such inspections and testing shall be limited to 
site construction and shall not include building service 
equipment which is a part of the manufactured home itself. 
No portion of any building service equipment intended to be 
concealed by any permanent portion of the construction 
shall be concealed until inspected and approved. Building 
service equipment shall not be connected to the water, fuel 
or power supply or sewer system until authorized by the 
building official. 

AE305.5.4 Final inspection. When finish grading and the 
manufactured home installation, including the installation 
of all required building service equipment, is completed and 
the manufactured home is ready for occupancy, a final 
inspection shall be made. 

AE305.6 Other inspections. In addition to the called inspec- 
tions specified above, the building official may make or require 
other inspections of any construction work to as certain com- 
pliance with these provisions or other codes and laws which are 
enforced by the code enforcement agency. 



SECTION AE306 
SPECIAL INSPECTIONS 

AE306.1 General. In addition to the inspections required by 
Section AE305, the building official may require the owner to 



employ a special inspector during construction of specific 
types of work as described in this code. 



SECTION AE307 
UTILITY SERVICE 

AE307.1 General. Utility service shall not be provided to any 
building service equipment which is regulated by these provi- 
sions or other applicable codes and for which a manufactured 
home installation permit is required by these provisions until 
approved by the building official. 



SECTION AE401 
OCCUPANCY CLASSIFICATION 

AE401.1 Manufactured homes. A manufactured home shall 
be limited in use to use as a single dwelling unit. 

AE401.2 Accessory buildings. Accessory buildings shall be 
classified as to occupancy by the building official as set forth in 
this code. 



SECTION AE402 
LOCATION ON PROPERTY 

AE402.1 General. Manufactured homes and accessory build- 
ings shall be located on the property in accordance with appli- 
cable codes and ordinances of this jurisdiction. 



SECTION AE501 
DESIGN 

AE501.1 General. A manufactured home shall be installed on 
a foundation system which is designed and constructed to sus- 
tain within the stress limitations specified in this code and all 
loads specified in this code. 

Exception: When specifically authorized by the building 
official, foundation and anchorage systems which are con- 
structed in accordance with the methods specified in Sec- 
tion AE600 of these provisions, or in the United States 
Department of Housing and Urban Development Hand- 
book, Permanent Foundations for Manufactured Housing, 
1984 Edition, Draft, shall be deemed to meet the require- 
ments of this Appendix E. 

AE501.2 Manufacturer's installation instructions. The 

installation instructions as provided by the manufacturer of the 
manufactured home shall be used to determine permissible 
points of support for vertical loads and points of attachment for 
anchorage systems used to resist horizontal and uphft forces. 

AE501.3 Rationality. Any system or method of construction 
to be used shall admit to a rational analysis in accordance with 
well-established principles of mechanics. 



2006 INTERNATIONAL RESIDENTIAL CODE® 



597 



APPENDIX E 



SECTION AE502 
FOUNDATION SYSTEMS 

AE502.1 General. Foundation systems designed and con- 
structed in accordance with this section may be considered as a 
permanent installation. 

AE502.2 Soil classification. The classification of the soil at 
each manufactured home site shall be determined when 
required by the building official. The building official may 
require that the determination be made by an engineer or archi- 
tect licensed by the state to conduct soil investigations. 

The classification shall be based on observation and any 
necessary tests of the materials disclosed by borings or exca- 
vations made in appropriate locations. Additional studies 
may be necessary to evaluate soil strength, the effect of mois- 
ture variation on soil-bearing capacity, compressibility and 
expansiveness. 

When required by the building official, the soil classification 
design bearing capacity and lateral pressure shall be shown on 
the plans. 

AE502.3 Footings and foundations. Footings and founda- 
tions, unless otherwise specifically provided, shall be con- 
structed of materials specified by this code for the intended use 
and in all cases shall extend below the frost line. Footings of 
concrete and masonry shall be of solid material. Foundations 
supporting untreated wood shall extend at least 8 inches (203 
mm) above the adjacent finish grade. Footings shall have a 
minimum depth below finished grade of 12 inches (305 mm) 
unless a greater depth is recommended by a foundation investi- 
gation. 

Piers and bearing walls shall be supported on masonry or 
concrete foundations or piles, or other approved foundation 
systems which shall be of sufficient capacity to support all 
loads. 

AE502.4 Foundation design. When a design is provided, the 
foundation system shall be designed in accordance with the 
applicable structural provisions of this code and shall be 
designed to minimize differential settlement. Where a design is 
not provided, the minimum foundation requirements shall be 
as set forth in this code. 

AE502.5 Drainage. Provisions shall be made for the control 
and drainage of surface water away from the manufactured 
home. 

AE502.6 Under-floor clearances — ventilation and access. 

A minimum clearance of 12 inches (305 mm) shall be main- 
tained beneath the lowest member of the floor support framing 
system. Clearances from the bottom of wood floor joists or per- 
imeter joists shall be as specified in this code. 

Under-floor spaces shall be ventilated with openings as 
specified in this code. If combustion air for one or more 
heat-producing appliances is taken from within the under-floor 
spaces, ventilation shall be adequate for proper appliance oper- 
ation. 

Under-floor access openings shall be provided. Such open- 
ings shall be not less than 1 8 inches (457 mm) in any dimension 
and not less than 3 square feet (0.279 m^) in area and shall be 



located so that any water supply and sewer drain connections 
located under the manufactured home are accessible. 



SECTION AE503 
SKIRTING AND PERIMETER ENCLOSURES 

AE503.1 Skirting and permanent perimeter enclosures. 

Skirting and permanent perimeter enclosures shall be installed 
only where specifically required by other laws or ordinances. 
Skirting, when installed, shall be of material suitable for exte- 
rior exposure and contact with the ground. Permanent perime- 
ter enclosures shall be constructed of materials as required by 
this code for regular foundation construction. 

Skirting shall be installed in accordance with the skirting 
manufacturer's installation instructions. Skirting shall be ade- 
quately secured to assure stability, to minimize vibration and 
susceptibility to wind damage, and to compensate for possible 
frost heave. 

AE503.2 Retaining walls. Where retaining walls are used as a 
permanent perimeter enclosure, they shall resist the lateral dis- 
placements of soil or other materials and shall conform to this 
code as specified for foundation walls. Retaining walls and 
foundation walls shall be constructed of approved treated 
wood, concrete, masonry or other approved materials or com- 
bination of materials as for foundations as specified in this 
code. Siding materials shall extend below the top of the exterior 
of the retaining or foundation wall or the joint between siding 
and enclosure wall shall be flashed in accordance with this 
code. 



SECTION AE504 
STRUCTURAL ADDITIONS 



AE504.1 General. Accessory buildings shall not be structur- 
ally supported by or attached to a manufactured home unless 
engineering calculations are submitted to substantiate any pro- 
posed structural connection. 

Exception: The building official may waive the submission 
of engineering calculations if it is found that the nature of 
the work applied for is such that engineering calculations 
are not necessary to show conformance to these provisions. 



SECTION AE505 
BUILDING SERVICE EQUIPMENT 

AE505.1 General. The installation, alteration, repair, replace- 
ment, addition to or maintenance of the building service equip- 
ment within the manufactured home shall conform to 
regulations set forth in the Manufactured Home Standards. 
Such work which is located outside the manufactured home 
shall comply with the applicable codes adopted by this jurisdic- 
tion. 



598 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



APPENDIX E 



SECTION AE506 
EXITS 

AE506.1 Site development. Exterior stairways and ramps 
which provide egress to the pubhc way shall comply with 
applicable provisions of this code. 

AE506.2 Accessory buildings. Every accessory building or 
portion thereof shall be provided with exits as required by this 
code. 



SECTION AE507 

OCCUPANCY, FIRE SAFETY AND ENERGY 

CONSERVATION STANDARDS 

AE507.1 General. Alterations made to a manufactured home 
subsequent to its initial installation shall conform to the occu- 
pancy, fire-safety and energy conservation requirements set 
forth in the Manufactured Home Standards. 



SECTION AE600 

SPECIAL REQUIREMENTS FOR 

FOUNDATION SYSTEMS 

AE600.1 General. Section AE600 is applicable only when 
specifically authorized by the building official. 



SECTION AE601 
FOOTINGS AND FOUNDATIONS 

AE601.1 General. The capacity of individual load-bearing 
piers and their footings shall be sufficient to sustain all loads 
specified in this code within the stress limitations specified in 
this code. Footings, unless otherwise approved by the building 
official, shall be placed level on firm, undisturbed soil or an engi- 
neered fill which is free of organic material, such as weeds and 
grasses. Where used, an engineered fill shall provide a minimum 
load-bearing capacity of not less than 1,000 psf (48 kN/m^). 
Continuous footings shall conform to the requirements of this 
code. Section AE502 of these provisions shall apply to footings 
and foundations constructed under the provisions of this section. 



SECTION AE602 
PIER CONSTRUCTION 

AE602.1 General. Piers shall be designed and constructed to 
distribute loads evenly. Multiple section homes may have con- 
centrated roof loads which will require special consideration. 
Load-bearing piers may be constructed utilizing one of the 
methods listed below. Such piers shall be considered to resist 
only vertical forces acting in a downward direction. They shall 
not be considered as providing any resistance to horizontal 
loads induced by wind or earthquake forces. 

1. A prefabricated load-bearing device that is listed and 
labeled for the intended use. 

2. Mortar shall comply with ASTM C 270 Type M, S or N; 
this may consist of one part portland cement, one-half 
part hydrated lime and four parts sand by volume. Lime 
shall not be used with plastic or waterproof cement. 



3 . A cast-in-place concrete pier with concrete having speci- 
fied compressive strength at 28 days of 2,500 psi (17 225 
kPa). 

Alternate materials and methods of construction may be 
used for piers which have been designed by an engineer or 
architect licensed by the state to practice as such. 

Caps and leveling spacers may bejised for leveling of the 
manufactured home. Spacing of piers shall be as specified in 
the manufacturer's installation instructions, if available, or by 
an approved designer. 



SECTION AE603 
HEIGHT OF PIERS 

AE603.1 General. Piers constructed as indicated in Section 
AE602 may have heights as follows: 

1 . Except for corner piers, piers 36 inches (914 mm) or less 
in height may be constructed of masonry units, placed 
with cores or cells vertically. Piers shall be installed with 
their long dimension at right angles to the main frame 
member they support and shall have a minimum 
cross-sectional area of 128 square inches (82 560 mm^). 
Piers shall be capped with minimum 4-inch (102 mm) 
solid masonry units or equivalent. 

2. Piers between 36 and 80 inches (914 mm and 2032 mm) 
in height and all comer piers over 24 inches (610 mm) in 
height shall be at least 16 inches by 16 inches (406 mm 
by 406 mm) consisting of interlocking masonry units 
and shall be fully capped with minimum 4-inch (102 
mm) solid masonry units or equivalent. 

3. Piers over 80 inches (2032 mm) in height may be con- 
structed in accordance with the provisions of Item 2 
above, provided the piers shall be filled sohd with grout 
and reinforced with four continuous No. 5 bars. One bar 
shall be placed in each comer cell of hollow masonry unit 
piers or in each comer of the grouted space of piers con- 
stmcted of solid masonry units. 

4. Cast-in-place concrete piers meeting the same size and 
height limitations of Items 1 , 2 and 3 above may be sub- 
stituted for piers constmcted of masonry units. 



SECTION AE604 
ANCHORAGE INSTALLATIONS 

AE604.1 Ground anchors. Ground anchors shall be designed 
and installed to transfer the anchoring loads to the ground. The 
load-carrying portion of the ground anchors shall be installed 
to the full depth called for by the manufacturer's installation 
directions and shall extend below the estabhshed frost line into 
undisturbed soil. 

Manufactured ground anchors shall be listed and installed in 
accordance with the terms of their listing and the anchor manu- 
facturer's instructions and shall include means of attachment of 
ties meeting the requirements of Section AE605. Ground 
anchor manufacturer's installation instmctions shall include 
the amount of preload required and load capacity in various 
types of soil. These instructions shall include tensioning 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



599 



APPENDIX E 



adjustments which may be needed to prevent damage to the 
manufactured home, particularly damage that can be caused by 
frost heave. Each ground anchor shall be marked with the man- 
ufacturer's identification and listed model identification num- 
ber which shall be visible after installation. Instructions shall 
accompany each listed ground anchor specifying the types of 
soil for which the anchor is suitable under the requirements of 
this section. 

Each approved ground anchor, when installed, shall be capa- 
ble of resisting an allowable working load at least equal to 
3,150 pounds (14 kN) in the direction of the tie plus a 50 per- 
cent overload [4,725 pounds (21 kN) total] without failure. 
Failure shall be considered to have occurred when the anchor 
moves more than 2 inches (5 1 mm) at a load of 4,725 pounds 
(21 kN) in the direction of the tie installation. Those ground 
anchors which are designed to be installed so that loads on the 
anchor are other than direct withdrawal shall be designed and 
installed to resist an applied design load of 3,150 pounds (14 
kN) at 40 to 50 degrees from vertical or within the angle limita- 
tions specified by the home manufacturer without displacing 
the tie end of the anchor more than 4 inches (102 mm) horizon- 
tally. Anchors designed for connection of multiple ties shall be 
capable of resisting the combined working load and overload 
consistent with the intent expressed herein. 

When it is proposed to use ground anchors and the building 
official has reason to believe that the soil characteristics at a 
given site are such as to render the use of ground anchors advis- 
able, or when there is doubt regarding the ability of the ground 
anchors to obtain their listed capacity, the building official may 
require that a representative field installation be made at the site 
in question and tested to demonstrate ground anchor capacity. 
The building official shall approve the test procedures. 

AE604.2 Anchoring equipment. Anchoring equipment, 
when installed as a permanent installation, shall be capable of 
resisting all loads as specified within these provisions. When 
the stabilizing system is designed by an engineer or architect 
licensed by the state to practice as such, alternative designs 
may be used, providing the anchoring equipment to be used is 
capable of withstanding a load equal to 1 .5 times the calculated 
load. All anchoring equipment shall be listed and labeled as 
being capable of meeting the requirements of these provisions. 
Anchors as specified in this code may be attached to the main 
frame of the manufactured home by an approved ^/ig-inch-thick 
(4.76 mm) slotted steel plate anchoring device. Other anchor- 
ing devices or methods meeting the requirements of these pro- 
visions may be permitted when approved by the building 
official. 

Anchoring systems shall be so installed as to be permanent. 
Anchoring equipment shall be so designed to prevent self-dis- 
connection with no hook ends used. 

AE604.3 Resistance to weather deterioration. All anchoring 
equipment, tension devices and ties shall have a resistance to 
deterioration as required by this code. 

AE604.4 Tensioning devices. Tensioning devices, such as 
turnbuckles or yoke-type fasteners, shall be ended with clevis 
or welded eyes. 



SECTION AE605 
TIES, MATERIALS AND INSTALLATION 

AE605.1 General. Steel strapping, cable, chain or other 
approved materials shall be used for ties. All ties shall be fas- 
tened to ground anchors and drawn tight with turnbuckles or 
other adjustable tensioning devices or devices supplied with 
the ground anchor. Tie materials shall be capable of resisting an 
allowable working load of 3,150 pounds (14 kN) with no more 
than 2 percent elongation and shall withstand a 50 percent 
overload [4,750 pounds (21 kN)]. Ties shall comply with the 
weathering requirements of Section AE604.3. Ties shall con- 
nect the ground anchor and the main structural frame. Ties shall 
not connect to steel outrigger beams which fasten to and inter- 
sect the main structural frame unless specifically stated in the 
manufacturer's installation instructions. Connection of cable 
ties to main frame members shall be Vg-inch (15.9 mm) 
closed-eye bolts affixed to the frame member in an approved 
manner. Cable ends shall be secured with at least two U-bolt 
cable clamps with the "U" portion of the clamp installed on the 
short (dead) end of the cable to assure strength equal to that 
required by this section. 

Wood floor support systems shall be fixed to perimeter foun- 
dation walls in accordance with provisions of this code. The 
minimum number of ties required per side shall be sufficient to 
resist the wind load stated in this code. Ties shall be evenly 
spaced as practicable along the length of the manufactured 
home with the distance from each end of the home and the tie 
nearest that end not exceeding 8 feet (2438 mm). When contin- 
uous straps are provided as vertical ties, such ties shall be posi- 
tioned at rafters and studs. Where a vertical tie and diagonal tie 
are located at the same place, both ties may be connected to a 
single anchor, provided the anchor used is capable of carrying 
both loadings. Multisection manufactured homes require diag- 
onal ties only. Diagonal ties shall be installed on the exterior 
main frame and slope to the exterior at an angle of 40 to 50 
degrees from the vertical or within the angle limitations speci- 
fied by the home manufacturer. Vertical ties which are not con- 
tinuous over the top of the manufactured home shall be 
attached to the main frame. 



SECTION AE606 
REFERENCED STANDARDS 

ASTMC 270-04 Specification for Mortar 

for Unit Masonry AE602 

NFPA 501-03 Standard on Manufactured 

Housing AE201 



600 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



APPENDIX F 

RADON CONTROL METHODS 



SECTION AF1 01 
SCOPE 

AFlOl.l General. This appendix contains requirements for 
new construction in jurisdictions where radon-resistant con- 
struction is required. 

Inclusion of this appendix by jurisdictions shall be deter- 
mined through the use of locally available data or determina- 
tion of Zone 1 designation in Figure AFIOI. 



SECTION AF1 02 
DEFINITIONS 

AF102.1 General. For the purpose of these requirements, the 

terms used shall be defined as follows: 

SUBSLAB DEPRESSURIZATION SYSTEM (Passive). A 

system designed to achieve lower sub-slab air pressure relative 
to indoor air pressure by use of a vent pipe routed through the 
conditioned space of a building and connecting the sub- slab 
area with outdoor air, thereby relying on the convective flow of 
air upward in the vent to draw air from beneath the slab. 
SUBSLAB DEPRESSURIZATION SYSTEM (Active). A 
system designed to achieve lower sub-slab air pressure relative 
to indoor air pressure by use of a fan-powered vent drawing air 
from beneath the slab. 

DRAIN TILE LOOP. A continuous length of drain tile or per- 
forated pipe extending around all or part of the internal or 
external perimeter of a basement or crawl space footing. 
RADON GAS. A naturally-occurring, chemically inert, radio- 
active gas that is not detectable by human senses. As a gas, it 
can move readily through particles of soil and rock and can 
accumulate under the slabs and foundations of homes where it 
can easily enter into the living space through construction 
cracks and openings. 

SOIL-GAS-RETARDER. A continuous membrane of 6-mil 
(0.15 mm) polyethylene or other equivalent material used to 
retard the flow of soil gases into a building. 
SUBMEMBRANE DEPRESSURIZATION SYSTEM. A 
system designed to achieve lower-sub-membrane air pressure 
relative to crawl space air pressure by use of a vent drawing air 
from beneath the soil-gas-retarder membrane. 



SECTION AF1 03 
REQUIREMENTS 

AF103.1 General. The following construction techniques are 
intended to resist radon entry and prepare the building for 
post-construction radon mitigation, if necessary (see Figure 
AF102). These techniques are required in areas where desig- 
nated by the jurisdiction. 

AF103.2 Subfloor preparation. A layer of gas-permeable 
material shall be placed under all concrete slabs and other floor 
systems that directly contact the ground and are within the 
walls of the living spaces of the building, to facilitate future 



installation of a sub-slab depressurization system, if needed. 
The gas-permeable layer shall consist of one of the following: 

1 . A uniform layer of clean aggregate, a minimum of 4 inches 
(102 mm) thick. The aggregate shall consist of material that 
will pass through a 2-inch (5 1 mm) sieve and be retained by 
a V4-inch (6.4 mm) sieve. 

2. A uniform layer of sand (native or fill), a minimum of 4 
inches (102 mm) thick, overlain by a layer or strips of 
geotextile drainage matting designed to allow the lateral 
flow of soil gases. 

3. Other materials, systems or floor designs with demon- 
strated capability to permit depressurization across the 
entire sub-floor area. 

AF103.3 Soil-gas-retarder. A minimum 6-mil (0.15 mm) [or 
3-mil (0.075 mm) cross-laminated] polyethylene or equivalent 
flexible sheeting material shall be placed on top of the gas-per- 
meable layer prior to casting the slab or placing the floor 
assembly to serve as a soil-gas-retarder by bridging any cracks 
that develop in the slab or floor assembly and to prevent con- 
crete from entering the void spaces in the aggregate base mate- 
rial. The sheeting shall cover the entire floor area with separate 
sections of sheeting lapped at least 12 inches (305 mm). The 
sheeting shall fit closely around any pipe, wire or other penetra- 
tions of the material. All punctures or tears in the material shall 
be sealed or covered with additional sheeting. 

AF103.4 Entry routes. Potential radon entry routes shall be 
closed in accordance with Sections AF103.4.1 through 
AF103.4.10. 

AF103.4.1 Floor openings. Openings around bathtubs, 
showers, water closets, pipes, wires or other objects that 
penetrate concrete slabs or other floor assemblies shall be 
filled with a polyurethane caulk or equivalent sealant 
applied in accordance with the manufacturer's recommen- 
dations. 

AF103.4.2 Concrete joints. All control joints, isolation 
joints, construction joints and any other joints in concrete 
slabs or between slabs and foundation walls shall be sealed 
with a caulk or sealant. Gaps and joints shall be cleared of 
loose material and filled with polyurethane caulk or other 
elastomeric sealant applied in accordance with the manu- 
facturer's recommendations. 

AF103.4.3 Condensate drains. Condensate drains shall be 
trapped or routed through nonperforated pipe to daylight. 

AF103.4.4 Sumps. Sump pits open to soil or serving as the 
termination point for sub-slab or exterior drain tile loops shall 
be covered with a gasketed or otherwise sealed lid. Sumps 
used as the suction point in a sub-slab depressurization sys- 
tem shall have a lid designed to accommodate the vent pipe. 
Sumps used as a floor drain shall have a lid equipped with a 
trapped inlet. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



601 



APPENDIX F 



AF103.4.5 Foundation walls. Hollow block masonry 
foundation walls shall be constructed with either a continu- 
ous course of solid masonry, one course of masonry grouted 
solid, or a solid concrete beam at or above finished ground 
surface to prevent passage of air from the interior of the wall 
into the living space. Where a brick veneer or other masonry 
ledge is installed, the course immediately below that ledge 
shall be sealed. Joints, cracks or other openings around all 
penetrations of both exterior and interior surfaces of 
masonry block or wood foundation walls below the ground 
surface shall be filled with polyurethane caulk or equivalent 
sealant. Penetrations of concrete walls shall be filled. 

AF103.4.6 Dampproofing. The exterior surfaces of por- 
tions of concrete and masonry block walls below the ground 
surface shall be dampproofed in accordance with Section 
R406 of this code. 

AF103.4.7 Air-handling units. Air-handling units in crawl 
spaces shall be sealed to prevent air from being drawn into 
the unit. 

Exception: Units with gasketed seams or units that are 
otherwise sealed by the manufacturer to prevent leakage. 

AF103.4.8 Ducts. Ductwork passing through or beneath a 
slab shall be of seamless material unless the air-handling 
system is designed to maintain continuous positive pressure 
within such ducting. Joints in such ductwork shall be sealed 
to prevent air leakage. 

Ductwork located in crawl spaces shall have all seams 
and joints sealed by closure systems in accordance with 
Section M1601. 3.1. 

AF103.4.9 Crawl space floors. Openings around all pene- 
trations through floors above crawl spaces shall be caulked 
or otherwise filled to prevent air leakage. 

AF103.4.10 Crawl space access. Access doors and other 
openings or penetrations between basements and adjoining 
crawl spaces shall be closed, gasketed or otherwise filled to 
prevent air leakage. 

AF103.5 Passive submembrane depressurization system. 

In buildings with crawl space foundations, the following com- 
ponents of a passive sub-membrane depressurization system 
shall be installed during construction. 

Exception: Buildings in which an approved mechanical 
crawl space ventilation system or other equivalent system is 
installed. 

AF103.5.1 Ventilation. Crawl spaces shall be provided 
with vents to the exterior of the building. The minimum net 
area of ventilation openings shall comply with Section 
R408.1 of this code. 

AF103.5.2 Soil-gas-retarder. The soil in crawl spaces shall 
be covered with a continuous layer of minimum 6-mil (0. 15 
mm) polyethylene soil-gas-retarder. The ground cover shall 
be lapped a minimum of 12 inches (305 mm) at joints and 
shall extend to all foundation walls enclosing the crawl 
space area. 

AF103.5.3 Vent pipe. A plumbing tee or other approved 
connection shall be inserted horizontally beneath the sheet- 
ing and connected to a 3- or 4-inch-diameter (76 mm or 102 



mm) fitting with a vertical vent pipe installed through the 
sheeting. The vent pipe shall be extended up through the 
building floors, terminate at least 12 inches (305 mm) above 
the roof in a location at least 10 feet (3048 mm) away from 
any window or other opening into the conditioned spaces of 
the building that is less than 2 feet (610 mrn) below the 
exhaust point, and 10 feet (3048 nrni) from any window or 
other opening in adjoining or adjacent buildings. 

AF103.6 Passive subslab depressurization system. In base- 
ment or slab-on-grade buildings, the following components of 
a passive sub-slab depressurization system shall be installed 
during construction. 

AF103.6.1 Vent pipe. A minimum 3-inch-diameter (76 mm) 
ABS, PVC or equivalent gas-tight pipe shall be embedded 
vertically into the sub-slab aggregate or other permeable 
material before the slab is cast. A "T" fitting or equivalent 
method shall be used to ensure that the pipe opening remains 
within the sub-slab permeable material. Alternatively, the 
3-inch (76 mm) pipe shall be inserted directly into an interior 
perimeter drain tile loop or through a sealed sump cover 
where the sump is exposed to the sub-slab aggregate or con- 
nected to it through a drainage system. 

The pipe shall be extended up through the building floors, 
terminate at least 12 inches (305 mm) above the surface of 
the roof in a location at least 10 feet (3048 mm) away from 
any window or other opening into the conditioned spaces of 
the building that is less than 2 feet (610 mm) below the 
exhaust point, and 10 feet (3048 mm) from any window or 
other opening in adjoining or adjacent buildings. 

AF103.6.2 Multiple vent pipes. In buildings where interior 
footings or other barriers separate the sub-slab aggregate or 
other gas-permeable material, each area shall be fitted with 
an individual vent pipe. Vent pipes shall connect to a single 
vent that terminates above the roof or each individual vent 
pipe shall terminate separately above the roof. 

AF103.7 Vent pipe drainage. All components of the radon 
vent pipe system shall be installed to provide positive drainage 
to the ground beneath the slab or soil-gas-retarder. 
AF103.8 Vent pipe accessibility. Radon vent pipes shall be 
accessible for future fan installation through an attic or other 
area outside the habitable space. 

Exception: The radon vent pipe need not be accessible in an 
attic space where an approved roof-top electrical supply is 
provided for future use. 

AF103.9 Vent pipe identification. All exposed and visible 
interior radon vent pipes shall be identified with at least one 
label on each floor and in accessible attics. The label shall 
read:"Radon Reduction System." 

AF103.10 Combination foundations. Combination base- 
ment/crawl space or slab-on-grade/crawl space foundations 
shall have separate radon vent pipes installed in each type of 
foundation area. Each radon vent pipe shall terminate above the 
roof or shall be connected to a single vent that terminates above 
the roof. 

AF103.11 Building depressurization. Joints in air ducts and 
plenums in unconditioned spaces shall meet the requirements 
of Section Ml 601. Thermal envelope air infiltration require- 
ments shall comply with the energy conservation provisions 



602 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX F 



in Chapter 1 1 . Firestopping shall meet the requirements con- 
tained in Section R602.8. 

AF103.12 Power source. To provide for future installation 
of an active sub-membrane or sub-slab depressurization 
system, an electrical circuit terminated in an approved box 
shall be installed during construction in the attic or other 
anticipated location of vent pipe fans. An electrical supply 
shall also be accessible in anticipated locations of system 
failure alarms. 



2006 INTERNATIONAL RESIDENTIAL CODE® 603 



APPENDIX F 




LEGEND 

ZONE 1 HIGH POTENTIAL (GREATER THAN 4 pCi/L^) 

ZONE 2 MODERATE POTENTIAL (FROM 2 TO 4 pCi/L) 

ZONES LOW POTENTIAL (LESS THAN 2 pCi/L) 



a. pCi/L standard for picocuries per liter of radon gas. EPA recommends that all homes that measure 4 pCi/L and greater be mitigated. 

The United States Environmental Protection Agency and the United States Geological Survey have evaluated the radon potential in the United States and have 
developed a map of radon zones designed to assist building officials in deciding whether radon-resistant features are applicable in new construction. 

The map assigns each of the 3,141 counties in the United States to one of three zones based on radon potential. Each zone designation reflects the average 
short-term radon measurement that can be expected to be measured in a building without the implementation of radon control methods. The radon zone designa- 
tion of highest priority is Zone 1 . Table 1 of this appendix lists the Zone 1 counties illustrated on the map. More detailed information can be obtained from state-spe- 
cific booklets (EPA-402-R-93-021 through 070) available through State Radon Offices or from U.S. EPA Regional Offices. 

FIGURE AF1 01 
EPA MAP OF RADON ZONES 



604 



2006 INTERNATIONAL RESIDENTIAL CODE® 



APPENDIX F 









TABLE AF1 01(1) 












HIGH RADON POTENTIAL (ZONE 1) COUNTIES^ 






ALABAMA 


CONNECTICUT 


Morgan 


Wabash 


Thomas 


Cass 


Washington 


Calhoun 


Fairfield 


Moultrie 


Warren 


Trego 


Hillsdale 


Watonwan 


Clay 


Middlesex 


Ogle 


Washington 


Wallace 


Jackson 


Wilkin 


Cleburne 


New Haven 


Peoria 


Wayne 


Washington 


Kalamazoo 


Winona 


Colbert 


New London 


Piatt 


Wells 


Wichita 


Lenawee 


Wright 


Coosa 




Pike 


White 


Wyandotte 


St. Joseph 


Yellow Medicine 


Franklin 


GEORGIA 


Putnam 


Whitley 




Washtenaw 




Jackson 


Cobb 


Rock Island 




KENTUCKY 




MISSOURI 


Lauderdale 


De Kalb 


Sangamon 


IOWA 


Adair 


MINNESOTA 


Andrew 


Lawrence 


Fulton 


Schuyler 


All Counties 


Allen 


Becker 


Atchison 


Limestone 


Gwinnett 


Scott 




Barren 


Big Stone 


Buchanan 


Madison 




Stark 


KANSAS 


Bourbon 


Blue Earth 


Cass 


Morgan 


IDAHO 


Stephenson 


Atchison 


Boyle 


Brown 


Clay 
Clinton 


Talladega 


Benewah 


Tazewell 


Barton 


Bullitt 


Carver 




Blaine 


Vermilion 


Brown 


Casey 


Chippewa 


Holt 


CALIFORNIA 


Boise 


Warren 


Cheyenne 


Clark 


Clay 


Iron 


Santa Barbara 


Bonner 


Whiteside 


Clay 


Cumberland 


Cottonwood 


Jackson 


Ventura 


Boundary 


Winnebago 


Cloud 


Fayette 


Dakota 


Nodaway 
Platte 




Butte 


Woodford 


Decatur 


Franklin 


Dodge 


COLORADO 


Camas 




Dickinson 


Green 


Douglas 




Adams 


Clark 


INDIANA 


Douglas 


Harrison 


Faribault 


MONTANA 


Arapahoe 


Clearwater 


Adams 


EUis 


Hart 


Fillmore 


Baca 


Custer 


Allen 


Ellsworth 


Jefferson 


Freeborn 


Beaverhead 


Bent 


Elmore 


Bartholomew 


Finney 


Jessamine 


Goodhue 


Big Horn 


Boulder 


Fremont 


Benton 


Ford 


Lincoln 


Grant 


Blaine 


Chaffee 


Gooding 


Blackford 


Geary 


Marion 


Hennepin 


Broadwater 


Cheyenne 


Idaho 


Boone 


Gove 


Mercer 


Houston 


Carbon 


Clear Creek 


Kootenai 


Carroll 


Graham 


Metcalfe 


Hubbard 


Carter 


Crowley 


Latah 


Cass 


Grant 


Monroe 


Jackson 


Cascade 


Custer 


Lemhi 


Clark 


Gray 


Nelson 


Kanabec 


Chouteau 


Delta 


Shoshone 


Clinton 


Greeley 


Pendleton 


Kandiyohi 


Custer 


Denver 


Valley 


De Kalb 


Hamilton 


Pulaski 


Kittson 


Daniels 


Dolores 




Decatur 


Haskell 


Robertson 


Lac Qui Parle 


Dawson 


Douglas 


ILLINOIS 


Delaware 


Hodgeman 


Russell 


Le Sueur 


Deer Lodge 


El Paso 


Adams 


Elkhart 


Jackson 


Scott 


Lincoln 


Fallon 


Elbert 


Boone 


Fayette 


Jewell 


Taylor 


Lyon 


Fergus 


Fremont 


Brown 


Fountain 


Johnson 


Warren 


Mahnomen 


Flathead 


Garfield 


Bureau 


Fulton 


Kearny 


Woodford 


Marshall 


Gallatin 


Gilpin 


Calhoun 


Grant 


Kingman 




Martin 


Garfield 


Grand 


Carroll 


Hamilton 


Kiowa 


MAINE 


McLeod 


Glacier 


Gunnison 


Cass 


Hancock 


Lane 


Androscoggin 


Meeker 


Granite 


Huerfano 


Champaign 


Harrison 


Leavenworth 


Aroostook 


Mower 


Hill 


Jackson 


Coles 


Hendricks 


Lincoln 


Cumberland 


Murray 


Jefferson 


Jefferson 


De Kalb 


Henry 


Logan 


Franklin 


Nicollet 


Judith Basin 


Kiowa 


De Witt 


Howard 


Marion 


Hancock 


Nobles 


Lake 


Kit Carson 


Douglas 


Huntington 


Marshall 


Kennebec 


Norman 


Lewis and Clark 


Lake 


Edgar 


Jay 


McPherson 


Lincoln 


Olmsted 


Liberty 


Larimer 


Ford 


Jennings 


Meade 


Oxford 


Otter Tail 


Lincoln 


Las Animas 


Fulton 


Johnson 


Mitchell 


Penobscot 


Pennington 


Madison 


Lincoln 


Greene 


Kosciusko 


Nemaha 


Piscataquis 


Pipestone 


McCone 


Logan 


Grundy 


Lagrange 


Ness 


Somerset 


Polk 


Meagher 


Mesa 


Hancock 


Lawrence 


Norton 


York 


Pope 


Mineral 


Moffat 


Henderson 


Madison 


Osborne 




Ramsey 


Missoula 


Montezuma 


Henry 


Marion 


Ottawa 


MARYLAND 


Red Lake 


Park 


Montrose 


Iroquois 


Marshall 


Pawnee 


Baltimore 


Redwood 


Phillips 


Morgan 


Jersey 


Miami 


Philhps 


Calvert 


Renville 


Pondera 


Otero 


Jo Daviess 


Monroe 


Pottawatomie 


Carroll 


Rice 


Powder River 


Ouray 


Kane 


Montgomery 


Pratt 


Frederick 


Rock 


Powell 


Park 


Kendall 


Noble 


Rawlins 


Harford 


Roseau 


Prairie 


Phillips 


Knox 


Orange 


Republic 


Howard 


Scott 


Ravalli 


Pitkin 


La Salle 


Putnam 


Rice 


Montgomery 


Sherburne 


Richland 


Prowers 


Lee 


Randolph 


Riley 


Washington 


Sibley 


Roosevelt 


Pueblo 


Livingston 


Rush 


Rooks 




Steams 


Rosebud 


Rio Blanco 


Logan 


Scott 


Rush 


MASS. 


Steele 


Sanders 


San Miguel 


Macon 


Shelby 


Russell 


Essex 


Stevens 


Sheridan 


Summit 


Marshall 


Steuben 


Saline 


Middlesex 


Swift 


Silver Bow 


Teller 


Mason 


St. Joseph 


Scott 


Worcester 


Todd 


Stillwater 


Washington 


McDonough 


Tippecanoe 


Sheridan 




Traverse 


Teton 


Weld 


McLean 


Tipton 


Sherman 


MICHIGAN 


Wabasha 


Toole 


Yuma 


Menard 


Union 


Smith 


Branch 


Wadena 


Valley 




Mercer 


Vermillion 


Stanton 


Calhoun 


Waseca 


Wibaux 



a. EPA recommends that this county listing be supplemented with other available State and local data to further understand the radon potential of Zone 1 area. 

(continued) 



2006 INTERNATIONAL RESIDENTIAL CODE"^ 



605 



APPENDIX F 



TABLE AF1 01(1)— continued 
HIGH RADON POTENTIAL (ZONE 1) COUNTIES^ 



Yellowstone 


Carroll 


Allen 


National Park 




Ashland 




NEW JERSEY 


Auglaize 


NEBRASKA 


Hunterdon 


Belmont 


Adams 


Mercer 


Butler 


Boone 


Monmouth 


Carroll 


Boyd 


Morris 


Champaign 


Burt 


Somerset 


Clark 


Butler 


Sussex 


Clinton 


Cass 


Warren 


Columbiana 


Cedar 




Coshocton 


Clay 


NEW MEXICO 


Crawford 


Colfax 


Bemahllo 


Darke 


Cuming 


Colfax 


Delaware 


Dakota 


Mora 


Fairfield 


Dixon 


Rio Arriba 


Fayette 


Dodge 


San Miguel 


Franklin 


Douglas 


Santa Fe 


Greene 


Fillmore 


Taos 


Guernsey 


Franklin 




Hamilton 


Frontier 


NEW YORK 


Hancock 


Furnas 


Albany 


Hardin 


Gage 


Allegany 


Harrison 


Gosper 


Broome 


Holmes 


Greeley 


Cattaraugus 


Huron 


Hamilton 
Harlan 
Hayes 


Cayuga 

Chautauqua 

Chemung 


Jefferson 

Knox 

Licking 


Hitchcock 


Chenango 


Logan 


Hurston 


Columbia 


Madison 


Jefferson 


Cortland 


Marion 


Johnson 


Delaware 


Mercer 

Miami 

Montgomery 


Kearney 
Knox 


Dutchess 
Erie 


Lancaster 


Genesee 


Morrow 

Muskingum 

Perry 

Pickaway 

Pike 

Preble 


Madison 


Greene 


Nance 
Nemaha 


Livingston 
Madison 


Nuckolls 


Onondaga 


Otoe 


Ontario 


Richland 


Pawnee 


Orange 


Ross 
Seneca 


Phelps 


Otsego 


Pierce 


Putnam 


Shelby 
Stark 


Platte 


Rensselaer 


Polk 


Schoharie 


Summit 


Red Willow 


Schuyler 


Tuscarawas 


Richardson 


Seneca 


Union 


Saline 


Steuben 


Van Wert 


Sarpy 


Sullivan 


Warren 


Saunders 


Tioga 


Wayne 
Wyandot 


Seward 


Tompkins 


Stanton 


Ulster 




Thayer 


Washington 


PENNSYLVANIA 


Washington 


Wyoming 


Adams 


Wayne 


Yates 


Allegheny 


Webster 




Armstrong 


York 


N. CAROLINA 


Beaver 




Alleghany 


Bedford 


NEVADA 


Buncombe 


Berks 


Carson City 


Cherokee 


Blair 


Douglas 


Henderson 


Bradford 


Eureka 


Mitchell 


Bucks 


Lander 


Rockingham 


Butler 


Lincoln 


Transylvania 


Cameron 


Lyon 


Watauga 


Carbon 


Mineral 




Centre 


Pershing 


N. DAKOTA 


Chester 


White Pine 


All Counties 


Clarion 
Clearfield 


NEW 


OHIO 


Clinton 


HAMPSHIRE 


Adams 


Columbia 



Cumberland 


Marshall 


Bath 


Dauphin 


McCook 


Bland 


Delaware 


McPherson 


Botetourt 


Franklin 


Miner 


Bristol 


Fulton 


Minnehaha 


Brunswick 


Huntingdon 


Moody 


Buckingham 


Indiana 


Perkins 


Buena Vista 


Juniata 


Potter 


Campbell 


Lackawanna 


Roberts 


Chesterfield 


Lancaster 


Sanborn 


Clarke 


Lebanon 


Spink 


Clifton Forge 


Lehigh 


Stanley 


Covington 


Luzerne 


Sully 


Craig 


Lycoming 


Turner 


Cumberland 


Mifflin 


Union 


Danville 


Monroe 


Walworth 


Dinwiddle 


Montgomery 


Yankton 


Fairfax 


Montour 




Falls Church 


Northampton 


TENNESEE 


Fluvanna 


Northumberland 


Anderson 


Frederick 


Perry 


Bedford 


Fredericksburg 


Schuylkill 


Blount 


Giles 


Snyder 


Bradley 


Goochland 


Sullivan 


Claiborne 


Harrisonburg 


Susquehanna 


Davidson 


Henry 


Tioga 


Giles 


Highland 


Union 


Grainger 


Lee 


Venango 


Greene 


Lexington 


Westmoreland 


Hamblen 


Louisa 


Wyoming 


Hancock 


Martinsville 


York 


Hawkins 


Montgomery 




Hickman 


Nottoway 


{HODE ISLAND 


Humphreys 


Orange 


Kent 


Jackson 


Page 


Washington 


Jefferson 


Patrick 




Knox 


Pittsylvania 


S. CAROLINA 


Lawrence 


Powhatan 


Greenville 


Lewis 


Pulaski 




Lincoln 


Radford 


S. DAKOTA 


Loudon 


Roanoke 


Aurora 


Marshall 


Rockbridge 


Beadle 


Maury 


Rockingham 


Bon Homme 


McMinn 


Russell 


Brookings 


Meigs 


Salem 


Brown 


Monroe 


Scott 


Brule 


Moore 


Shenandoah 


Buffalo 


Perry 


Smyth 


Campbell 


Roane 


Spotsylvania 


Charles Mix 


Rutherford 


Stafford 


Clark 


Smith 


Staunton 


Clay 


SuUivan 


Tazewell 


Codington 


Trousdale 


Warren 


Corson 


Union 


Washington 


Davison 


Washington 


Waynesboro 


Day 


Wayne 


Winchester 


Deuel 


Williamson 


Wythe 


Douglas 


Wilson 




Edmunds 




WASHINGTON 


Faulk 


UTAH 


Clark 


Grant 


Carbon 


Ferry 


Hamlin 


Duchesne 


Okanogan 


Hand 


Grand 


Pend Oreille 


Hanson 


Piute 


Skamania 


Hughes 


Sanpete 


Spokane 


Hutchinson 


Sevier 


Stevens 


Hyde 


Uintah 


W. VIRGINIA 


Jerauld 


VIRGINIA 


Berkeley 


Kingsbury 


Alleghany 


Brooke 


Lake 


Amelia 


Grant 


Lincoln 


Appomattox 


Greenbrier 


Lyman 


Augusta 


Hampshire 



Hancock 

Hardy 
Jefferson 
Marshall 
Mercer 
Mineral 
Monongalia 
Monroe 
Morgan 

Ohio 

Pendleton 

Pocahontas 

Preston 

Summers 

Wetzel 

WISCONSIN 

Buffalo 

Crawford 

Dane 

Dodge 

Door 

Fond du Lac 

Grant 

: Green 

Green Lake 

Iowa 

Jefferson 

Lafayette 

Langlade 

Marathon 

Menominee 

Pepin 

Pierce 

Portage 

Richland 

Rock 

Shawano 

St. Croix 

Vernon 

Walworth 

Washington 

Waukesha 

Waupaca 

Wood 

WYOMING 

Albany 

Big Horn 

Campbell 

Carbon 

Converse 

Crook 

Fremont 

Goshen 

Hot Springs 

Johnson 

Laramie 

Lincoln 

Natrona 

Niobrara 

Park 

Sheridan 

Sublette 

Sweetwater 

i Teton 

Uinta 

Washakie 



a. EPA recommends that this county listing be supplemented with other available State and local data to further understand the radon potential of Zone 1 area. 

I 

606 2006 INTERNATIONAL RESIDENTIAL CODE*^ 



APPENDIX F 



TYPICAL SUB-SLAB DEPRESSURIZATION 
PASSIVE RADON SYSTEM 




PASSIVE RADON SYSTEM VENTED 
THROUGH SUMP 




GRADE 
GRAVEL 



POLYETHYLENE 
SHEETING 



LIVING AREA 



BASEMENT 



SLAB 



\ 



SUMP 
COVERS 



<<<<<<<<<\::':::-\: GBMEL:\y: 



POLYETHYLENE 
SHEETING 



:^':w^ ■:■'.{"' 



oi iR/in niT ' 



I 



SUMP PIT' 



PASSIVE RADON SYSTEM USING 
DRAIN-TILE LOOP 



SUB-MEMBRANE DEPRESSURIZATION SYSTEM 
FOR CRAWL SPACE 




POLYETHYLENE 
SHEETING 



GRADE 
GRAVEL 



DRAIN TILE LOOP 




POLYETHYLENE 
SHEETINGy 



PERFORATED 
DRAIN TILE 



FIGURE AF1 02 
RADON-RESISTANT CONSTRUCTION DETAILS FOR FOUR FOUNDATION TYPES 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



607 



608 2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX G 

SWIMMING POOLS, SPAS AND HOT TUBS 



SECTION AG1 01 
GENERAL 

AGlOl.l General. The provisions of this appendix shall con- 
trol the design and construction of swimming pools, spas and 
hot tubs installed in or on the lot of a one- or two-family dwell- 
ing. 



SECTION AG1 02 
DEFINITIONS 

AG102.1 General. For the purposes of these requirements, the 
terms used shall be defined as follows and as set forth in Chap- 
ter 2. 

ABOVE-GROUND/ON-GROUND POOL. See "Swim 
ming pool." 

BARRIER. A fence, wall, building wall or combination 
thereof which completely surrounds the swimming pool and 
obstructs access to the swimming pool. 

HOT TUB. See "Swimming pool." 

IN-GROUND POOL. See "Swimming pool." 

RESIDENTIAL. That which is situated on the premises of a 
detached one- or two-family dwelling or a one-family town- 
house not more than three stories in height. 

SPA, NONPORTABLE. See "Swimming pool." 

SPA, PORTABLE. A nonpermanent structure intended for 
recreational bathing, in which all controls, water-heating and 
water-circulating equipment are an integral part of the product. 

SWIMMING POOL. Any structure intended for swimming 
or recreational bathing that contains water over 24 inches (610 
mm) deep. This includes in-ground, above-ground and 
on-ground swimming pools, hot tubs and spas. 

SWIMMING POOL, INDOOR. A swimming pool which is 
totally contained within a structure and surrounded on all four 
sides by the walls of the enclosing structure. 

SWIMMING POOL, OUTDOOR. Any swimming pool 
which is not an indoor pool. 



SECTION AG1 03 
SWIMMING POOLS 

AG103.1 In-ground pools. In-ground pools shall be designed 
and constructed in conformance with ANSI/NSPI-5 as listed in 
Section AGIOS. 

AG103.2 Above-ground and on-ground pools. Above- 
ground and on-ground pools shall be designed and constructed 
in conformance with ANSI/NSPI-4 as listed in Section AG 108. 



SECTION AG1 04 
SPAS AND HOT TUBS 

AG104.1 Permanently installed spas and hot tubs. Perma- 
nently installed spas and hot tubs shall be designed and con- 
structed in conformance with ANSI/NSPI-3 as listed in 
Section AGIOS. 

AG104.2 Portable spas and hot tubs. Portable spas and hot 
tubs shall be designed and constructed in conformance with 
ANSI/NSPI-6 as listed in Section AGIOS. 



SECTION AG1 05 
BARRIER REQUIREMENTS 

AG105.1 Application. The provisions of this chapter shall 
control the design of barriers for residential swimming pools, 
spas and hot tubs. These design controls are intended to pro- 
vide protection against potential drownings and near- 
drownings by restricting access to swimming pools, spas and 
hot tubs. 

AG105.2 Outdoor swimming pool. An outdoor swimming 
pool, including an in-ground, above-ground or on-ground 
pool, hot tub or spa shall be surrounded by a barrier which shall 
comply with the following: 

1. The top of the barrier shall be at least 4S inches (1219 
mm) above grade measured on the side of the barrier 
which faces away from the swimming pool. The maxi- 
mum vertical clearance between grade and the bottom of 
the barrier shall be 2 inches (51 mm) measured on the 
side of the barrier which faces away from the swimming 
pool. Where the top of the pool structure is above grade, 
such as an above-ground pool, the barrier may be at 
ground level, such as the pool structure, or mounted on 
top of the pool structure. Where the barrier is mounted on 
top of the pool structure, the maximum vertical clearance 
between the top of the pool structure and the bottom of 
the barrier shall be 4 inches (102 mm). 

2. Openings in the barrier shall not allow passage of a 
4-inch-diameter (102 mm) sphere. 

3. Solid barriers which do not have openings, such as a 
masonry or stone wall, shall not contain indentations or 
protrusions except for normal construction tolerances 
and tooled masonry joints. 

4. Where the barrier is composed of horizontal and vertical 
members and the distance between the tops of the hori- 
zontal members is less than 45 inches (1143 mm), the 
horizontal members shall be located on the swimming 
pool side of the fence. Spacing between vertical mem- 
bers shall not exceed IV4 inches (44 mm) in width. 
Where there are decorative cutouts within vertical mem- 
bers, spacing within the cutouts shall not exceed P/4 
inches (44 mm) in width. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



609 



APPENDIX G 



5. Where the barrier is composed of horizontal and vertical 
members and the distance between the tops of the hori- 
zontal members is 45 inches (1 143 mm) or more, spacing 
between vertical members shall not exceed 4 inches (102 
mm). Where there are decorative cutouts within vertical 
members, spacing within the cutouts shall not exceed 1% 
inches (44 mm) in width. 

6. Maximum mesh size for chain link fences shall be a 
274-inch (57 mm) square unless the fence has slats fas- 
tened at the top or the bottom which reduce the openings 
to not more than P/4 inches (44 mm). 

7. Where the barrier is composed of diagonal members, 
such as a lattice fence, the maximum opening formed by 
the diagonal members shall not be more than VI ^ inches 
(44 mm). 

8. Access gates shall comply with the requirements of Sec- 
tion AG105.2, Items 1 through 7, and shall be equipped 
to accommodate a locking device. Pedestrian access 
gates shall open outward away from the pool and shall be 
self-closing and have a self-latching device. Gates other 
than pedestrian access gates shall have a self-latching 
device. Where the release mechanism of the self-latch- 
ing device is located less than 54 inches (1372 mm) from 
the bottom of the gate, the release mechanism and open- 
ings shall comply with the following: 

8.1. The release mechanism shall be located on the 
pool side of the gate at least 3 inches (76 mm) 
below the top of the gate; and 

8.2. The gate and barrier shall have no opening larger 
than '/2 inch (13 mm) within 18 inches (457 mm) 
of the release mechanism. 

9. Where a wall of a dwelling serves as part of the barrier, 
one of the following conditions shall be met: 

9.1. The pool shall be equipped with a powered safety 
cover in compliance with ASTM F 1346; or 

9.2. Doors with direct access to the pool through that 
wall shall be equipped with an alarm which pro- 
duces an audible warning when the door and/or its 
screen, if present, are opened. The alarm shall be 
listed in accordance with UL 2017. The audible 
alarm shall activate within 7 seconds and sound 
continuously for a minimum of 30 seconds after 
the door and/or its screen, if present, are opened 
and be capable of being heard throughout the 
house during normal household activities. The 
alarm shall automatically reset under all condi- 
tions. The alarm system shall be equipped with a 
manual means, such as touch pad or switch, to 
temporarily deactivate the alarm for a single open- 
ing. Deactivation shall last for not more than 15 
seconds. The deactivation switch(es) shall be 
located at least 54 inches (1372 mm) above the 
threshold of the door; or 

9.3. Other means of protection, such as self-closing 
doors with self-latching devices, which are 
approved by the governing body, shall be accept- 
able so long as the degree of protection afforded 



is not less than the protection afforded by Item 
9.1 or 9.2 described above. 

10. Where an above-ground pool structure is used as a bar- 
rier or where the barrier is mounted on top of the pool 
structure, and the means of access is a ladder or steps: 

10.1. The ladder or steps shall be capable of being 
secured, locked or removed to prevent access; or 

10.2. The ladder or steps shall be surrounded by a 
barrier which meets the requirements of Sec- 
tion AG 105. 2, Items 1 through 9. When the lad- 
der or steps are secured, locked or removed, any 
opening created shall not allow the passage of a 
4-inch-diameter (102 mm) sphere. 

AG105.3 Indoor swimming pool. Walls surrounding an 
indoor swimming pool shall comply with Section AG105.2, 
Item 9. 

AG105.4 Prohibited locations. Barriers shall be located to 
prohibit permanent structures, equipment or similar objects 
from being used to climb them. 

AG105.5 Barrier exceptions. Spas or hot tubs with a safety 
cover which comphes with ASTM F 1346, as listed in Section 
AG 1 07 , shall be exempt from the provisions of this appendix. 



SECTION AG1 06 

ENTRAPMENT PROTECTION FOR SWIMMING 

POOL AND SPA SUCTION OUTLETS 

AG106.1 General. Suction outlets shall be designed to pro- 
duce circulation throughout the pool or spa. Single-outlet sys- 
tems, such as automatic vacuum cleaner systems, or multiple 
suction outlets, whether isolated by valves or otherwise, shall 
be protected against user entrapment. 

AG106.2 Suction fittings. Pool and spa suction outlets shall 
have a cover that conforms to ANSI/ASME Al 12. 19.8M, or an 
1 8 inch X 23 inch (457 mm by 584 mm) drain grate or larger, or | 
an approved channel drain system. 

Exception: Surface skimmers 

AG106.3 Atmospheric vacuum relief system required. Pool 
and spa single- or multiple-outlet circulation systems shall be 
equipped with atmospheric vacuum relief should grate covers 
located therein become missing or broken. This vacuum relief 
system shall include at least one approved or engineered 
method of the type specified herein, as follows: 

1. Safety vacuum release system conforming to ASME 
A112.19.17;or 

2. An approved gravity drainage system. 

AG106.4 Dual drain separation. Single or multiple pump cir- 
culation systems have a minimum of two suction outlets of the 
approved type. A minimum horizontal or vertical distance of 3 
feet (914 mm) shall separate the outlets. These suction outlets 
shall be piped so that water is drawn through them simulta- 
neously through a vacuum-relief-protected line to the pump or 
pumps. 

AG106.5 Pool cleaner fittings. Where provided, vacuum or 
pressure cleaner fitting(s) shall be located in an accessible posi- 



610 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX G 



tion(s) at least 6 inches (152 mm) and not more than 12 inches UL 

(305 mm) below the minimum operational water level or as an UL2017-2000 Standard for General-purpose 

attachment to the skimmer(s). Signahng Devices and Systems-with Revisions 

through June 2004 AG105.2 



SECTION AG1 07 
ABBREVIATIONS 



AG107.1 General. 



ANSI — American National Standards Institute 
1 1 West 42nd Street, New York, NY 10036 

ASME — American Society of Mechanical Engineers 

Three Park Avenue 

New York, NY 10016-5990 

ASTM— ASTM International 

100 Barr Harbor Drive, West Conshohocken, PA 19428 

NSPI — National Spa and Pool Institute 

2111 Eisenhower Avenue, Alexandria, VA 22314 

UL — Underwriters Laboratories, Inc. 
333 Pfingsten Road 
Northbrook, Illinois 60062-2096 



SECTION AG1 08 
STANDARDS 

AG108.1 General. 

ANSI/NSPI 

ANSI/NSPI-3-99 Standard for Permanently Installed 
Residential Spas AG104.1 

ANSI/NSPI-4-99 Standard for Above-ground/On-ground 
Residential Swimming Pools AG103.2 

ANSI/NSPI-5-99 Standard for Residential In-ground 
SwimmingPools AG103.1 

ANSI/NSPI-6-99 Standard for Residential 

PortableSpas AG104.2 

ANSI/NSPI-5-2003 Standard for Residential 

In-ground Swimming Pools AG103.1 

ANSI/ASME A112.19.8M-1987 (R1996) Suction 

Fittings for Use in Swimming Pools, 

Wading Pools, Spas, Hot Tubs and 

Whirlpool Bathing Appliances AG106.2 

ASTM 

ASTM F 1346-91 (2003) Performance Specification 

for Safety Covers and Labeling Requirements for 

All Covers for Swimming Pools, Spas and 

Hot Tubs AG105.2,AG105.5 

ASME 

ASME Al 12.19.17 Manufacturers Safety Vacuum 
Release Systems (SVRS) for Residential and 
Commercial Swimming Pool, Spa, Hot Tub and 
WadingPool AG106.3 



2006 INTERNATIONAL RESIDENTIAL CODE® 61 1 



612 2006 INTERNATIONAL RESIDENTIAL CODE"* 



APPENDIX H 

PATIO COVERS 



SECTION AH1 01 
GENERAL 

AHlOl.l Scope. Patio covers shall conform to the require- 
ments of this appendix chapter. 



SECTION AH1 02 
DEFINITION 

Patio covers. One-story structures not exceeding 12 feet (3657 
mm) in height. Enclosure walls shall be permitted to be of any 
configuration, provided the open or glazed area of the longer 
wall and one additional wall is equal to at least 65 percent of the 
area below a minimum of 6 feet 8 inches (2032 mm) of each 
wall, measured from the floor. Openings shall be permitted to 
be enclosed with (1) insect screening, (2) approved translucent 
or transparent plastic not more than 0.125 inch (3.2 mm) in 
thickness, (3) glass conforming to the provisions of Section 
R308, or (4) any combination of the foregoing. 



SECTION AH1 03 
PERMITTED USES 

AH103.1 General. Patio covers shall be permitted to be 
detached from or attached to dwelling units. Patio covers shall 
be used only for recreational, outdoor living purposes and not 
as carports, garages, storage rooms or habitable rooms. 



SECTION AH1 04 
DESIGN LOADS 

AH104.1 General. Patio covers shall be designed and con- 
structed to sustain, within the stress limits of this code, all dead 
loads plus a minimum vertical live load of 10 pounds per square 
foot (0.48 kN/m^) except that snow loads shall be used where 
such snow loads exceed this minimum. Such covers shall be 
designed to resist the minimum wind loads set forth in Table 
R301.2(l). 



SECTION AH1 05 
LIGHT AND VENTILATION/EMERGENCY EGRESS 

AH105.1 General. Exterior openings required for light and 
ventilation shall be permitted to open into a patio structure 
con-forming to Section AHlOl, provided that the patio struc- 
ture shall be unenclosed if such openings are serving as emer- 
gency egress or rescue openings from sleeping rooms. Where 
such exterior openings serve as an exit from the dwelling unit, 
the patio structure, unless unenclosed, shall be provided with 
exits conforming to the provisions of Section R310 of this 
code. 



SECTION AH1 06 
FOOTINGS 

AH106.1 General. In areas with a frosthne depth of zero as 
specified in Table R30 1 .2( 1 ), a patio cover shall be permitted to 
be supported on a slab on grade without footings, provided the 
slab conforms to the provisions of Section R506 of this code, is 
not less than 3.5 inches (89 mm) thick and the columns do not 
support live and dead loads in excess of 750 pounds (3.34 kN) 
per column. 



SECTION AH1 07 
SPECIAL PROVISIONS FOR ALUMINUM SCREEN 
ENCLOSURES IN HURRICANE-PRONE REGIONS 

AH107.1 General. Screen enclosures in hurricane-prone 
regions shall be in accordance with the provisions of this Sec- 
tion. 

AH107.1.1 Habitable spaces. Screen enclosures shall not 
be considered habitable spaces. 

AH107.1.2 Minimum ceiling height. Screen enclosures 
shall have a ceiling height of not less than 7 feet (21 34 mm). 

AH107.2 Definitions. 

SCREEN ENCLOSURE. A building or part thereof, in whole 
or in part self-supporting, and having walls of insect screening 
and a roof of insect screening, plastic, aluminum, or similar 
lightweight material. 

AH107.3 Screen enclosures. 

AH107.3.1 Thickness. Actual wall thickness of extruded 
aluminum members shall be not less than 0.040 inches ( 1 .02 
mm). 

AH107.3.2 Density. Screen density shall be a maximum of 
20 threads per inch by 20 threads per inch mesh. 

AH107.4 Design. 

AH107.4.1 Wind load. Structural members supporting 
screen enclosures shall be designed to support minimum 
wind loads given in Table AH107.4(1) and AH107.4(2). 
Where any value is less than 10 psf (0.479 kN/m^) use 10 psf 
(0.479 kN/m2). 

AH107.4.2 Deflection limit. For members supporting 
screen surfaces only, the total load deflection shall not 
exceed 1/60. Screen surfaces shall be permitted to include a 
maximum of 25 percent solid flexible finishes. 

AH107.4.3 Importance factor. The wind factor for screen 
enclosures shall be 0.77 in accordance with Table 1604.5 of 
the International Building Code. 

AH107.4.4 Roof live load. The minimum roof live load 
shall be 10 psf (0.479 kN/m^). 



2006 INTERNATIONAL RESIDENTIAL CODE® 



613 



APPENDIX H 



AH107.5 Footings. In areas with a frost line is zero, a screen 
enclosure shall be permitted to be supported on a concrete slab 
on grade without footings, provided the slab conforms to the 
provisions of Section R506, is not less than 3 Vj inches (89 mm) 
thick, and the columns do not support loads in excess of 750 
pounds (3.36 kN) per column. 



TABLE AH1 07.4(1) 

DESIGN WIND PRESSURES FOR ALUMINUM SCREEN ENCLOSURE FRAMING 

WITH AN IMPORTANCE FACTOR OF 0.77^ "'"= 



LOAD 
CASE 


WALL 


Basic Wind Speed (mph) 


100 


110 


120 


130 


140 


150 


Exposure Category Design Pressure (psf) 


C 


B 


c 


B 


C 


B 


C 


B 


C 


B 


C 


B 


A'* 


Windward and leeward walls (flow thru) and 
windward wall (non-flow thru) LAV = 0-1 


12 


8 


14 


10 


17 


12 


19 


14 


23 


16 


26 


18 


A'' 


Windward and leeward walls (flow thru) and 
windward wall (non-flow thru) LAV = 2 


13 


9 


16 


11 


19 


14 


22 


16 


26 


18 


30 


21 


B^ 


Windward: Non-gable roof 


16 


12 


20 


14 


24 


17 


28 


20 


32 


23 


37 


26 


B^ 


Windward: Gable roof 


22 


16 


27 


19 


32 


23 


38 


27 


44 


31 


50 


36 




ROOF 




Allf 


Roof-screen 


4 


3 


5 


4 


6 


4 


7 


5 


8 


6 


9 


7 


Allf 


Roof-solid 


12 


9 


15 


11 


18 


13 


21 


15 


24 


17 


28 


20 



For SI: 1 mile per hour = 0.44 m/s, 1 pound per square foot = 0.0479kPa, 1 foot = 304.8 mm. 

a. Values have been reduced for 0.77 Importance Factor in accordance with Table 1604.5 of the International Building Code. 

b. Minimum design pressure shall be 10 psf in accordance with Section 1609.1.2 of the International Building Code. 

c. Loads are applicable to screen enclosures with a mean roof height of 30 feet or less. For screen enclosures of different heights the pressures given shall be adjusted 
by multiplying the table pressure by the adjustment iactor given in Table AH107.4(2). 

d. For Load Case A flow thru condition the pressure given shall be applied simultaneoiisly to both the upwind and downwind screen walls acting in the same direction 
as the wind. The structure shall also be analyzed for wind coming from the opposite direction. For the non-flow thru condition the screen enclosure wall shall be 
analyzed for the load applied acdng toward the interior of the enclosure. 

e. For Load Case B the table pressure multiplied by the projected frontal area of the screen enclosure is the total drag force, including drag on screen surfaces parallel 
to the wind, which must be transmitted to the ground. Use Load Case A for members directly supporting the screen surface perpendicular to the wind. Load Case B 
loads shall be applied only to structural members which carry wind loads from more than one surfece. 

f. The roof structure shall be analyzed for the pressure given occurring both upward and downward. 



TABLE AH1 07.4(2) 
HEIGHT ADJUSTMENT FACTORS 



IVIEAN 


EXPOSURE 


Roof Height (ft) 


B 


c 


15 


1 


0.86 


20 


1 


0.92 


25 


1 


0.96 


30 


1 


1.00 


35 


1.05 


1.03 


40 


1.09 


1.06 


45 


1.12 


1.09 


50 


1.16 


1.11 


55 


1.19 


1.14 


60 


1.22 


1.16 



For SI: 1 foot = 304.8 mm. 



614 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



APPENDIX I 

PRIVATE SEWAGE DISPOSAL 



SECTION AM 01 
GENERAL 

AIlOl.l Scope. Private sewage disposal systems shall con- 
form to the International Private Sewage Disposal Code. 



2006 INTERNATIONAL RESIDENTIAL CODE® 61 5 



616 



2006 INTERNATIONAL RESIDENTIAL CODE^^ 



[EB] APPENDIX J 

EXISTING BUILDINGS AND STRUCTURES 



SECTION AJ1 01 
PURPOSE AND INTENT 

AJlOl.l General. The purpose of these provisions is to 
encourage the continued use or reuse of legally existing build- 
ings and structures. These provisions are intended to permit 
work in existing buildings that is consistent with the purpose of 
the International Residential Code. Compliance with these 
provisions shall be deemed to meet the requirements of the 
International Residential Code. 

AJ101.2 Classification of work. For purposes of this appen- 
dix, all work in existing buildings shall be classified into the 
categories of repair, renovation, alteration and reconstruction. 
Specific requirements are established for each category of 
work in these provisions. 

AJ101.3 Multiple categories of work. Work of more than one 
category may be part of a single work project. All related work 
permitted within a 12-month period shall be considered a sin- 
gle work project. Where a project includes one category of 
work in one building area and another category of work in a 
separate and unrelated area of the building, each project area 
shall comply with the requirements of the respective category 
of work. Where a project with more than one category of work 
is performed in the same area or in related areas of the building, 
the project shall comply with the requirements of the more 
stringent category of work. 



SECTION AJ1 02 
COMPLIANCE 

AJ102.1 General. Regardless of the category of work being 
performed, the work shall not cause the structure to become 
unsafe or adversely affect the performance of the building; 
shall not cause an existing mechanical or plumbing system to 
become unsafe, hazardous, insanitary or overloaded; and 
unless expressly permitted by these provisions, shall not make 
the building any less conforming to this code or to any previ- 
ously approved alternative arrangements than it was before the 
work was undertaken. 

AJ102.2 Requirements by category of work. Repairs shall 
conform to the requirements of Section AJ301. Renovations 
shall conform to the requirements of Section AJ401. Alter- 
ations shall conform to the requirements of Section AJ501 and 
the requirements for renovations. Reconstructions shall con- 
form to the requirements of Section AJ601 and the require- 
ments for alterations and renovations. 

AJ102.3 Smoke detectors. Regardless of the category of 
work, smoke detectors shall be provided where required by 
Section R3 13. 2.1. 

AJ102.4 Replacement windows. Regardless of the category 
of work, when an existing window, including sash and glazed 
portion is replaced, the replacement window shall comply with 
the requirements of Chapter 1 1 . 



AJ102.5 Flood hazard areas. Work performed in existing 
buildings located in a flood hazard area as established by Table 
R301.2(l) shall be subject to the provisions of Section 
R105.3.1.1. 

AJ102.6 Equivalent alternatives. These provisions are not 
intended to prevent the use of any alternate material, alternate 
design or alternate method of construction not specifically pre- 
scribed herein, provided any alternate has been deemed to be 
equivalent and its use authorized by the building official. 

AJ102.7 Other alternatives. Where compliance with these 
provisions or with this code as required by these provisions is 
technically infeasible or would impose disproportionate costs 
because of structural, construction or dimensional difficulties, 
other alternatives may be accepted by the building official. 
These alternatives may include materials, design features 
and/or operational features. 

AJ102.8 More restrictive requirements. Buildings or sys- 
tems in compliance with the requirements of this code for new 
construction shall not be required to comply with any more 
restrictive requirement of these provisions. 

AJ102.9 Features exceeding International Residential Code 
requirements. Elements, components and systems of existing 
buildings with features that exceed the requirements of this 
code for new construction, and are not otherwise required as 
part of approved alternative arrangements or deemed by the 
building official to be required to balance other building ele- 
ments not complying with this code for new construction, shall 
not be prevented by these provisions from being modified as 
long as they remain in compliance with the applicable require- 
ments for new construction. 



SECTION A J1 03 
PRELIMINARY MEETING 

AJ103.1 General. If a building permit is required at the request 
of the prospective permit applicant, the building official or his 
designee shall meet with the prospective applicant to discuss 
plans for any proposed work under these provisions prior to the 
application for the permit. The purpose of this preliminary 
meeting is for the building official to gain an understanding of 
the prospective applicant's intentions for the proposed work, 
and to determine, together with the prospective applicant, the 
specific applicability of these provisions. 



SECTION AJ1 04 
EVALUATION OF AN EXISTING BUILDING 

AJ104.1 General. The building official may require an exist- 
ing building to be investigated and evaluated by a registered 
design professional in the case of proposed reconstruction of 
any portion of a building. The evaluation shall determine the 
existence of any potential nonconformities with these provi- 
sions, and shall provide a basis for determining the impact of 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



617 



APPENDIX J 



the proposed changes on the performance of the building. The 
evaluation shall use the following sources of information, as 
applicable: 

1 . Available documentation of the existing building. 

1.1. Field surveys. 

1.2. Tests (nondestructive and destructive). 

1.3. Laboratory analysis. 

Exception: Detached one- or two-family dwellings that are 
not irregular buildings under Section R301. 2.2.2.2 and are 
not undergoing an extensive reconstruction shall not be 
required to be evaluated. 



SECTION AJ1 05 
PERMIT 

AJ105.1 Identification of work area. The work area shall be 
clearly identified on all permits issued under these provisions. 



SECTION AJ201 
DEFINITIONS 

AJ201.1 General. For purposes of this appendix, the terms 
used are defined as follows. 

ALTERATION. The reconfiguration of any space, the addi- 
tion or elimination of any door or window, the reconfiguration 
or extension of any system, or the installation of any additional 
equipment. 

CATEGORIES OF WORK. The nature and extent of con- 
struction work undertaken in an existing building. The catego- 
ries of work covered in this Appendix, listed in increasing order 
of stringency of requirements, are repair, renovation, alteration 
and reconstruction. 

DANGEROUS. Where the stresses in any member; the condi- 
tion of the building, or any of its components or elements or 
attachments; or other condition that results in an overload 
exceeding 150 percent of the stress allowed for the member or 
material in this code. 

EQUIPMENT OR FIXTURE. Any plumbing, heating, elec- 
trical, ventilating, air conditioning, refrigerating and fire pro- 
tection equipment, and elevators, dumb waiters, boilers, 
pressure vessels, and other mechanical facilities or installa- 
tions that are related to building services. 

LOAD-BEARING ELEMENT. Any column, girder, beam, 
joist, truss, rafter, wall, floor or roof sheathing that supports any 
vertical load in addition to its own weight, and/or any lateral 
load. 

MATERIALS AND METHODS REQUIREMENTS. Those 
requirements in this code that specify material standards; details 
of installation and connection; joints; penetrations; and continu- 
ity of any element, component or system in the building. The 
required quantity, fire resistance, flame spread, acoustic or ther- 
mal performance, or other performance attribute is specifically 
excluded from materials and methods requirements. 

RECONSTRUCTION. The reconfiguration of a space that 
affects an exit, a renovation and/or alteration when the work 



area is not permitted to be occupied because existing means of 
egress and fire protection systems, or their equivalent, are not 
in place or continuously maintained; and/or there are extensive 
alterations as defined in Section AJ501.3. 

REHABILITATION. Any repair, renovation, alteration or 
reconstruction work undertaken in an existing building. 

RENOVATION. The change, strengthening or addition of 
load-bearing elements; and/or the refinishing, replacement, 
bracing, strengthening, upgrading or extensive repair of exist- 
ing materials, elements, components, equipment and/or fix- 
tures. Renovation involves no reconfiguration of spaces. 
Interior and exterior painting are not considered refinishing for 
purposes of this definition, and are not renovation. 

REPAIR. The patching, restoration and/or minor' replacement 
of materials, elements, components, equipment and/or fixtures 
for the purposes of maintaining those materials, elements, com- 
ponents, equipment and/or fixtures in good or sound condition. 

WORK AREA. That portion of a building affected by any ren- 
ovation, alteration or reconstruction work as initially intended 
by the owner and indicated as such in the permit. Work area 
excludes other portions of the building where incidental work 
entailed by the intended work must be performed, and portions 
of the building where work not initially intended by the owner 
is specifically required by these provisions for a renovation, 
alteration or reconstruction. 



SECTION AJ301 
REPAIRS 

AJ301.1 Materials. Except as otherwise required herein, work 
shall be done using like materials or materials permitted by this 
code for new construction. 

AJ301.1.1 Hazardous materials. Hazardous materials no 
longer permitted, such as asbestos and lead-based paint, 
shall not be used. 

AJ301.1.2 Plumbing materials and supplies. The follow- 
ing plumbing materials and supplies shall not be used: 

1 . All-purpose solvent cement, unless listed for the spe- 
cific application; 

2. Flexible traps and tailpieces, unless listed for the spe- 
cific application; and 

3. Solder having more than 0.2 percent lead in the repair 
of potable water systems. 

AJ301.2 Water closets. When any water closet is replaced 
with a newly manufactured water closet, the replacement water 
closet shall comply with the requirements of Section P2903.2. 

AJ301.3 Safety glazing. Replacement glazing in hazardous 
locations shall comply with the safety glazing requirements of 
Section R308.1. 

AJ301.4 Electrical. Repair or replacement of existing electri- 
cal wiring and equipment undergoing repair with like material 
shall be permitted. 

Exceptions: 

1. Replacement of electrical receptacles shall comply 
with the requirements of Chapters 33 through 42. 



618 



2006 INTERNATIONAL RESIDENTIAL CODE® 



APPENDIX J 



2. Plug fuses of the Edison-base type shall be used for 
replacements only where there is no evidence of 
overfusing or tampering per the applicable require- 
ments of Chapters 33 through 42. 

3. For replacement of nongrounding-type receptacles 
with grounding-type receptacles and for branch cir- 
cuits that do not have an equipment grounding con- 
ductor in the branch circuitry, the grounding 
conductor of a grounding type receptacle outlet shall 
be permitted to be grounded to any accessible point on 
the grounding electrode system, or to any accessible 
point on the grounding electrode conductor, as 
allowed and described in Chapters 33 through 42. 



SECTION AJ401 
RENOVATIONS 

AJ401.1 Materials and methods. The work shall comply with 
the materials and methods requirements of this code. 

AJ401.2 Door and window dimensions. Minor reductions in 
the clear opening dimensions of replacement doors and win- 
dows that result from the use of different materials shall be 
allowed, whether or not they are permitted by this code. 

AJ401.3 Interior finish. Wood paneling and textile wall cov- 
erings used as an interior finish shall comply with the flame 
spread requirements of Section R315. 

AJ401.4 Structural. Unreinforced masonry buildings located 
in Seismic Design Category D2 or E shall have parapet bracing 
and wall anchors installed at the roofline whenever a reroofing 
permit is issued. Such parapet bracing and wall anchors shall 
be of an approved design. 



SECTION AJ501 
ALTERATIONS 

AJ501.1 Newly constructed elements. Newly constructed 
elements, components and systems shall comply with the 
requirements of this code. 

Exceptions: 

1 . Openable windows may be added without requiring 
compliance with the light and ventilation require- 
ments of Section R303. 

2. Newly installed electrical equipment shall comply 
with the requirements of Section AJ501.5. 

AJ501.2 Nonconformities. The work shall not increase the 
extent of noncompliance with the requirements of Section 
AJ601, or create nonconformity with those requirements 
which did not previously exist. 

AJ501.3 Extensive alterations. When the total area of all the 
work areas included in an alteration exceeds 50 percent of the 
area of the dwelling unit, the work shall be considered as a 
reconstruction and shall comply with the requirements of these 
provisions for reconstruction work. 

Exception; Work areas in which the alteration work is 
exclusively plumbing, mechanical or electrical shall not be 
included in the computation of total area of all work areas. 



AJ501.4 Structural. The minimum design loads for the struc- 
ture shall be the loads applicable at the time the building was 
constructed, provided that no dangerous condition is created. 
Structural elements that are uncovered during the course of the 
alteration and that are found to be unsound or dangerous shall 
be made to comply with the applicable requirements of this 
code. 

AJ501.5 Electrical equipment and wiring. 

AJ501.5.1 Materials and methods. Newly installed elec- 
trical equipment and wiring relating to work done in any 
work area shall comply with the materials and methods 
requirements of Chapters 33 through 42. 

Exception: Electrical equipment and wiring in newly 
installed partitions and ceilings shall comply with all 
applicable requirements of Chapters 33 through 42. 

AJ501.5.2 Electrical service. Service to the dwelling unit 
shall be a minimum of 100 ampere, three-wire capacity and 
service equipment shall be dead front having no live parts 
exposed that could allow accidental contact. Type "S" fuses 
shall be installed when fused equipment is used. 

Exception: Existing service of 60 ampere, three-wire 
capacity, and feeders of 30 ampere or larger two- or 
three- wire capacity shall be accepted if adequate for the 
electrical load being served. 

AJ501.5.3 Additional electrical requirements. When the 
work area includes any of the following areas within a 
dwelling unit, the requirements of Sections AJ501.5.3.1 
through AJ501.5.3.5 shall apply. 

AJ501.5.3.1 Enclosed areas. Enclosed areas other than 
closets, kitchens, basements, garages, hallways, laundry 
areas and bathrooms shall have a minimum of two 
duplex receptacle outlets, or one duplex receptacle outlet 
and one ceiling or wall type lighting outlet. 

AJ501.5.3.2 Kitchen and laundry areas. Kitchen areas 
shall have a minimum of two duplex receptacle outlets. 
Laundry areas shall have a minimum of one duplex 
receptacle outlet located near the laundry equipment and 
installed on an independent circuit. 

AJ501.5.3.3 Ground-fault circuit-interruption. 

Ground fault circuit interruption shall be provided on 
newly installed receptacle outlets if required by Chapters 
33 through 42. 

AJ501.5.3.4 Lighting outlets. At least one lighting out- 
let shall be provided in every bathroom, hallway, stair- 
way, attached garage and detached garage with electric 
power to illuminate outdoor entrances and exits, and in 
utility rooms and basements where these spaces are used 
for storage or contain equipment requiring service. 

AJ501.5.3.5 Clearance. Clearance for electrical service 
equipment shall be provided in accordance with Chap- 
ters 33 through 42. 

AJ501.6 Ventilation. All reconfigured spaces intended for 
occupancy and all spaces converted to habitable or occupiable 
space in any work area shall be provided with ventilation in 
accordance with Section R303. 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



619 



APPENDIX J 



AJ501.7 Ceiling height. Habitable spaces created in existing 
basements shall have ceiling heights of not less than 6 feet 8 
inches (2032 mm). Obstructions may project to within 6 feet 4 
inches (1930 mm) of the basement floor. Existing finished ceil- 
ing heights in nonhabitable spaces in basements shall not be 
reduced. 

AJ501.8 Stairs. 

AJ501.8.1 Stair width. Existing basement stairs and hand- 
rails not otherwise being altered or modified shall be per- 
mitted to maintain their current clear width at, above, and 
below existing handrails. 

AJ501.8.2 Stair headroom. Headroom height on existing 
basement stairs being altered or modified shall not be 
reduced below the existing stairway finished headroom. 
Existing basement stairs not otherwise being altered shall be 
permitted to maintain the current finished headroom. 

AJ501.8.3 Stair landing. Landings serving existing base- 
ment stairs being altered or modified shall not be reduced 
below the existing stairway landing depth and width. Exist- 
ing basement stairs not otherwise being altered shall be per- 
mitted to maintain the current landing depth and width. 



structures. Performance of work shall be required only on the 
side of the wall of the dwelfing unit that is part of the work area. 

AJ601.4 Ceiling height. Habitable spaces created in existing 
basements shall be permitted to have ceiling heights of not less 
than 6 feet 8 inches (2032 mm). Obstructions may project to 
within 6 feet 4 inches (1930 mm) of the basement floor. Exist- 
ing finished ceiling heights in nonhabitable spaces in base- 
ments shall not be reduced. 



SECTION AJ601 
RECONSTRUCTION 

AJ601.1 Stairways, handrails and guards. 

AJ601.1.1 Stairways. Stairways within the work area shall 
be provided with illumination in accordance with Section 
R303.6. 

AJ601.1.2 Handrails. Every required exit stairway that has 
four or more risers, is part of the means of egress for any 
work area, and is not provided with at least one handrail, or 
in which the existing handrails are judged to be in danger of 
collapsing, shall be provided with handrails designed and 
installed in accordance with Section R3 1 1 for the full length 
of the run of steps on at least one side. 

AJ601.1.3 Guards. Every open portion of a stair, landing or 
balcony that is more than 30 inches (762 mm) above the 
floor or grade below, is part of the egress path for any work 
area, and does not have guards or in which the existing 
guards are judged to be in danger of collapsing, shall be pro- 
vided with guards designed and installed in accordance with 
Section R3 12. 

AJ601.2 Wall and ceiling finish. The interior finish of walls 
and ceilings in any work area shall comply with the require- 
ments of Section R315. Existing interior finish materials that 
do not comply with those requirements shall be removed or 
shall be treated with an approved fire-retardant coating in 
accordance with the manufacturer's instructions to secure 
compliance with the requirements of this section. 

AJ601.3 Separation walls. Where the work area is in an 
attached dwelling unit, walls separating dwelling units that are 
not continuous from the foundation to the underside of the roof 
sheathing shall be constructed to provide a continuous fire sep- 
aration using construction materials consistent with the exist- 
ing wall or complying with the requirements for new 



620 



2006 INTERNATIONAL RESIDENTIAL CODE'* 



APPENDIX K 

SOUND TRANSMISSION 



SECTION AK1 01 
GENERAL 

AKlOl.l General. Wall and floor-ceiling assemblies separat- 
ing dwelling units including those separating adjacent town- 
house units shall provide air-borne sound insulation for walls, 
and both air-borne and impact sound insulation for floor-ceil- 
ing assemblies. 



SECTION AK1 02 
AIR-BORNE SOUND 

AK102.1 General. Air-borne sound insulation for wall and 
floor-ceiling assemblies shall meet a Sound Transmission 
Class (STC) rating of 45 when tested in accordance with 
ASTM E 90. Penetrations or openings in construction assem- 
blies for piping; electrical devices; recessed cabinets; bathtubs; 
soffits; or heating, ventilating or exhaust ducts shall be sealed, 
lined, insulated or otherwise treated to maintain the required 
ratings. Dwelling unit entrance doors, which share a common 
space, shall be tight fitting to the frame and sill. 



SECTION AK1 03 
STRUCTURAL-BORNE SOUND 

AK103.1 General. Floor/ceiling assemblies between dwelling 
units or between a dwelling unit and a public or service area 
within a structure shall have an Impact Insulation Class (IIC) 
rating of not less than 45 when tested in accordance with 
ASTM E 492. 



SECTION AK1 04 
REFERENCED STANDARDS 

ASTM E 90-04 Test Method for Laboratory 

Measurement of Airborne Sound Transmission 

Loss ofBuilding Partitions and Elements AK102 

ASTM E 492-04 (1996)e Specification for 

Laboratory Measurement of Impact Sound 

Transmission through Floor-ceiling Assemblies 

Using the Tapping Machine AK103 

2006 INTERNATIONAL RESIDENTIAL CODE® 621 



622 



2006 INTERNATIONAL RESIDENTIAL CODE' 



APPENDIX L 

PERMIT FEES 



TOTAL VALUATION 

$1 to $ 500 

$501 to $2,000 
$2,001 to $40,000 
$40,001 to $100,000 
$100,001 to $500,000 
$500,001 to $1,000,000 
$1,000,001 to $5,000,000 
$5,000,001 and over 



FEE 

$24 

$24 for the first $500; plus $3 for each additional $ 100 or fraction 
thereof, to and including $2,000 

$69 for the first $2,000; plus $1 1 for each additional $1,000 or 
fraction thereof, to and including $40,000 

$487 for the first $40,000; plus $9 for each additional $1,000 or 
fraction thereof, to and including $100,000 

$1,027 for the first $100,000; plus $7 for each additional $1,000 or 
fraction thereof, to and including $500,000 

$3,827 for the first $500,000; plus $5 for each additional $1,000 or 
fraction thereof, to and including $1,000,000 

$6,327 for the first $1,000,000; plus $3 for each additional $1,000 
or fraction thereof, to and including $5,000,000 

$18,327 for the first $ 5,000,000; plus $1 for each additional $1,000 
or fraction thereof 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



623 



624 



2006 INTERNATIONAL RESIDENTIAL CODE*^ 



APPENDIX M 

HOME DAY CARE— R-3 OCCUPANCY 



SECTION AM1 01 
GENERAL 

AMlOl.l General. This appendix shall apply to a home day 
care operated within a dwelling. It is to include buildings and 
structures occupied by persons of any age who receive custo- 
dial care for less than 24 hours by individuals other than parents 
or guardians or relatives by blood, marriage, or adoption, and 
in a place other than the home of the person cared for. 



SECTION AM1 02 
DEFINITIONS 

EXIT ACCESS. That portion of a means of egress system that 
leads from any occupied point in a building or structure to an 
exit. 



SECTION AM1 03 
MEANS OF EGRESS 

AM103.1 Exits required. If the occupant load of the resi- 
dence is more than nine, including those who are residents, 
during the time of operation of the day care, two exits are 
required from the ground-level story. Two exits are required 
from a home day care operated in a manufactured home 
regardless of the occupant load. Exits shall comply with Sec- 
tion R311. 

AM103.1.1 Exit access prohibited. An exit access from 
the area of day-care operation shall not pass through bath- 
rooms, bedrooms, closets, garages, fenced rear yards or 
similar areas. 

Exception: An exit may discharge into a fenced yard if 
the gate or gates remain unlocked during day-care hours. 
The gates may be locked if there is an area of refuge 
located within the fenced yard and more than 50 feet (15 
240 mm) from the dwelling. The area of refuge shall be 
large enough to allow 5 square feet (0.5 m^) per occupant. 

AM103.1.2 Basements. If the basement of a dwelling is to 
be used in the day-care operation, two exits are required 
from the basement regardless of the occupant load. One of 
the exits may pass through the dwelling and the other must 
lead directly to the exterior of the dwelling. 

Exception: An emergency and escape window comply- 
ing with Section R310 and which does not conflict with 
Section AM 103. 1.1 may be used as the second means of 
egress from a basement. 

AM103.1.3 Yards. If the yard is to be used as part of the 
day-care operation it shall be fenced. 

AM103.1.3.1 Type offence and hardware. The fence 
shall be of durable materials and be at least 6 feet (1529 
mm) tall completely enclosing the area used for the 
day-care operations. Each opening shall be a gate or door 



equipped with a self-closing and self-latching device to 
be installed at a minimum of 5 feet (1528 mm) above the 
ground. 

Exception: The door of any dwelling which forms 
part of the enclosure need not be equipped with 
self-closing and self-latching devices. 

AM103.1.3.2 Construction of fence. Openings in the 
fence, wall or enclosure required by this section shall 
have intermediate rails or an ornamental pattern that do 
not allow a sphere 4 inches (102 mm) in diameter to pass 
through. In addition, the following criteria must be met: 

1. The maximum vertical clearance between grade 
and the bottom of the fence, wall or enclosure shall 
be 2 inches (51 mm). 

2. Solid walls or enclosures that do not have open- 
ings, such as masonry or stone walls, shall not con- 
tain indentations or protrusions except for tooled 
masonry joints. 

3. Maximum mesh size for chain link fences shall be 
lV4-inches (32 nun) square unless the fence has 
slats at the top or bottom which reduce the opening 
to no more than P/4 inches (44 mm). The wire shall 
not be less than 9 gage [(0.148 in.) (3.8 mm)]. 

AM103.1.3.3 Decks. Decks that are more than 12 inches 
(305 mm) above grade shall have a guard in comphance 
with Section R3 12. 

AM103.2 Width and height of an exit. The minimum width 
of a required exit is 36 inches (914 mm) with a net clear width 
of 32 inches (813 nrni). The minimum height of a required exit 
is 6 feet 8 inches (2032 mm). 

AM103.3 Type of lock and latches for exits. Regardless of 
the occupant load served, exit doors shall be openable from the 
inside without the use of a key or any special knowledge or 
effort. When the occupant load is 10 or less, a night latch, dead 
bolt or security chain may be used, provided such devices are 
openable from the inside without the use of a key or tool and 
mounted at a height not to exceed 48 inches (1219 mm) above 
the finished floor. 

AM103.4 Landings. Landings for stairways and doors shall 
comply with Section R311 except that landings shall be 
required for the exterior side of a sliding door when a home 
day-care is being operated in a Group R-3 Occupancy. 



SECTION AM1 04 
SMOKE DETECTION 

AM104.1 General. Smoke detectors shall be installed in 
dwelling units used for home day-care operations. Detectors 
shall be installed in accordance with the approved manufac- 
turer's instructions. If the current smoke detection system in 
the dwelling is not in compliance with the currently adopted 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



625 



APPENDIX M 



code for smoke detection, it shall be upgraded to meet the cur- 
rently adopted code requirements and Section AM 103 before 
daycare operations commence. 

AM104.2 Power source. Required smoke detectors shall 
receive their primary power from the building wiring when that 
wiring is served from a commercial source and shall be 
equipped with a battery backup. The detector shall emit a sig- 
nal when the batteries are low. Wiring shall be permanent and 
without a disconnecting switch other than those required for 
over-current protection. Required smoke detectors shall be 
interconnected so if one detector is activated, all detectors are 
activated. 

AM104.3 Location. A detector shall be located in each bed- 
room and any room that is to be used as a sleeping room and 
centrally located in the corridor, hallway or area giving access 
to each separate sleeping area. When the dwelling unit has 
more than one story, and in dwellings with basements, a detec- 
tor shall be installed on each story and in the basement. In 
dwelling units where a story or basement is split into two or 
more levels, the smoke detector shall be installed on the upper 
level, except that when the lower level contains a sleeping area, 
a detector shall be installed on each level. When sleeping 
rooms are on the upper level, the detector shall be placed at the 
ceiling of the upper level in close proximity to the stairway. In 
dwelling units where the ceiling height of a room open to the 
hallway serving the bedrooms or sleeping areas exceeds that of 
the hallway by 24 inches (610 mm) or more, smoke detectors 
shall be installed in the hallway and in the adjacent room. 
Detectors shall sound an alarm audible in all sleeping areas of 
the dwelling unit in which they are located. 



626 2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX N 

VENTING METHODS 



(This appendix is informative and is not part of the code. 
This appendix provides examples of various of venting methods.) 




2 IN. 



TUB 



2 IN. 



SIN. 



2 IN. 



WC 



r 

1/1^/2 IN. 
I 

LAV 




"\ 



IV. 



3 IN. 



2 IN. 



A. TYPICAL SINGLE-BATH ARRANGEMENT 



B. TYPICAL POWDER ROOM 




2 IN. 



3^ \ 

2 IN. 11/2 ,N. 



SHOWER 



SHOWER 



TUB 




1^2 IN. 



C. MORE ELABORATE SINGLE-BATH 
ARRANGEMENT 



For SI: 1 inch = 25.4. 



D. COMBINATION WET- AND STACK-VENTING 
WITH STACK FITTING 



FIGURE N1 
TYPICAL SINGLE-BATH WET-VENT ARRANGEMENTS 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



627 



APPENDIX N 



1V2IN 



uw L 

iVdIN. ' 



TUB 



wc 



IV2IN. 2 IN. 





2 IN. 1V; 



Otub 

2 IN. 



3 IN. 



A. TYPICAL BACK-TO-BACK BATHS 
LAV 



IV2IN. TUB 



TUB 



WC 




1V2IN. 



3 IN. 
B. DOUBLE BATHS WITH FIXTURES ON COMMON HORIZONTAL BRANCH, COMMON WET VENT 

1V2IN., 



1 1/4 IN. 



h. 



\. 



i^ 



N| ^^^1V4IN. 



TUB 




WC 



SIN. 



C. DOUBLE BATHS WITH WASTE FIXTURES ON COMMON HORIZONTAL BRANCH, INDIVIDUAL WET VENTS 

For SI: 1 inch = 25.4. 

FIGURE N2 
TYPICAL DOUBLE-BATH WET-VENT ARRANGEMENTS 



628 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX N 



SIN. 



IV4IN. 




LAV 



For SI: 1 inch = 25.4 mm. 



FIGURE N3 
TYPICAL HORIZONTAL WET VENTING 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



629 



APPENDIX N 



WC 




wc 



A, VERTICAL WET VENTING 



I /''■'/2IN. 




LAV 



For SI: 1 inch = 25.4 mm. 



B. HORIZONTAL WET VENTING 



FIGURE N4 
TYPICAL METHODS OF WET VENTING 



630 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX N 



IV4IN. 



For SI: 1 inch = 25.4 mm. 




FIGURE N5 
SINGLE STACK SYSTEM FOR A TWO-STORY DWELLING 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



631 



APPENDIX N 



2V2 IN. 



2V2 IN. 



CLOTHES 
WASHER 
STAN DPI PE 



2 IN. 



KITCHEN 
GROUP 





LAUNDRY 
TUB 



IV2IN. 



2V? IN. 



For SI: 1 inch = 25.4 mm. 



FIGURE N6 
WASTE STACK VENTING 



632 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX N 



LAUNDRY 



KITCHEN 
GROUP 




^^hm 



CLOTHES 

WASHER 

STANDPIPE 



For SI: 1 inch ='25.4 mm. 



FIGURE N7 
CIRCUIT VENT WITH ADDITIONAL NONCIRCUIT VENTED BRANCH 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



633 



634 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX O 

GRAY WATER RECYCLING SYSTEMS 



Note: Section P2601.2 of the International Residential Code requires all plumbing fixtures that receive water or waste to dis- 
charge to the sanitary drainage system of the structure. To allow for the use of a gray water recycling system, Section P2601.2 
of the International Residential Code should be revised to read as follows: 



P2601.2 Connections. Plumbing fixtures, drains and appli- 
ances used to receive or discharge liquid wastes or sewage shall 
be directly connected to the sanitary drainage system of the 
building or premises, in accordance with the requirements of 
this code. This section shall not be construed to prevent indirect 
waste systems. 

Exception: Bathtubs, showers, lavatories, clothes washers 
and laundry trays are not required to discharge to the sani- 
tary drainage system where those fixtures discharge to an 
approved gray water recycling system. 



SECTION A01 01 
GENERAL 

AOlOl.l Scope. The provisions of this appendix shall govern 
the materials, design, construction and installation of gray 
water systems for flushing of water closets and urinals and for 
subsurface landscape irrigation [see Figures AO 10 1.1(1) and 
AO101.1(2)]. 

AO101.2 Definition. The following term shall have the mean- 
ing shown herein. 

GRAY WATER. Waste discharged from lavatories, bathtubs, 
showers, clothes washers and laundry trays. 

AO101.3 Permits. Permits shall be required in accordance 
with Section R105 of the International Residential Code. 

AO101.4 Installation. In addition to the provisions of Section 
AOlOl, systems for flushing of water closets and urinals shall 
comply with Section AO102 and systems for subsurface land- 
scape irrigation shall comply with Section AO103. Except as 
provided for in Appendix O, all systems shall comply with the 
provisions of the International Residential Code. 

AO101.5 Materials. Above-ground drain, waste and vent pip- 
ing for gray water systems shall conform to one of the stan- 
dards listed in Table P3002.1(l) of the International 
Residential Code. Gray water underground building drainage 
and vent pipe shall conform to one of the standards listed in 
Table P3002.1(2) of the International Residential Code. 

AO101.6 Tests. Drain, waste and vent piping for gray water 
systems shall be tested in accordance with Section P2503 of the 
International Residential Code. 

AO101.7 Inspections. Gray water systems shall be inspected 
in accordance with Section P2503 of the International Resi- 
dential Code. 

AO101.8 Potable water connections. Only connections in 
accordance with Section AO 102.3 shall be made between a 
gray water recycling system and a potable water system. 



AO101.9 Waste water connections. Gray water recycling 
systems shall receive the waste discharge only of bathtubs, 
showers, lavatories-, clothes washers and laundry trays. 

AOIOI.IO Filtration. Gray water entering the reservoir shall 
pass through an approved filter such as a media, sand or 
diatomaceous earth filter. 

AOIOI.10.1 Required valve. A full-open valve shall be 
installed downstream of the last fixture connection to the 
gray water discharge pipe before entering the required filter. 

AOlOl.ll Collection reservoir. Gray water shall be collected 
in an approved reservoir constructed of durable, nonabsorbent 
and corrosion-resistant materials. The reservoir shall be a 
closed and gas-tight vessel. Access openings shall be provided 
to allow inspection and cleaning of the reservoir interior. 

AO101.12 Overflow. The collection reservoir shall be 
equipped with an overflow pipe of the same diameter as, or 
larger than, the influent pipe for the gray water. The overflow 
shall be indirectly connected to the sanitary drainage system. 

AO101.13 Drain. A drain shall be located at the lowest point of 
the collection reservoir and shall be indirectly connected to the 
sanitary drainage system. The drain shall be the same diameter 
as the overflow pipe required in Section AO101.12. 

AO101.14 Vent required. The reservoir shall be provided with 
a vent sized in accordance with Chapter 3 1 of the International 
Residential Code and based on the diameter of the reservoir 
influent pipe. 



SECTION A01 02 

SYSTEMS FOR FLUSHING WATER 

CLOSETS AND URINALS 

AO 102.1 Collection reservoir. The holding capacity of the 
reservoir shall be a minimum of twice the volume of water 
required to meet the daily flushing requirements of the fixtures 
supplied with gray water, but not less than 50 gallons (189 L). 
The reservoir shall be sized to limit the retention time of gray 
water to a maximum of 72 hours. 

AO102.2 Disinfection. Gray water shall be disinfected by an 
approved method that uses one or more disinfectants such as 
chlorine, iodine or ozone. 

AO102.3 Makeup water. Potable water shall be supplied as a 
source of makeup water for the gray water system. The potable 
water supply shall be protected against backflow in accordance 
with Section P2902 of the International Residential Code. A 
full-open valve shall be located on the makeup water supply 
line to the collection reservoir. 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



635 



APPENDIX O 



POTABLE 
MAKEUP 
WATER 
SUPPLY 



V 
A 



7 

— CKH 



BACKFLOW 

PREVENTION 

DEVICE 



GRAY WATER 
INFLUENT 

^ — \xH 



FILTER 
SYSTEM 



TANK-\ 
DRAIN \ 



rixH 



I 



GRAY WATER 
RESERVOfR 



VENT 






OVERFLOW 



/— INDIRECT DISCHARGE 
* TO SANITARY 
y/ DRAINAGE 
Y SYSTEM 



-tx^ 



INDIRECT DISCHARGE 
TO SANITARY DRAINAGE 
SYSTEM 



EFFLUENT TO 
FLUSHING FIXTURES 



DISINFECTION COLORING 

UNIT DYE INJECTION 

UNIT 



FIGURE AO101 .1(1) 
GRAY WATER RECYCLING SYSTEM FOR FLUSHING WATER CLOSETS AND URINALS 



GRAY WATER 
INFLUENT 



-IXI FILTER 

SYSTEM 



TANK~\ 
DRAIN \ 



« VENT 

I 

J 

J 

I 

! 
I 
I 
! 
I 



r^xH 



I 






GRAY WATER 
RESERVOIR 



OVERFLOW 



f 



r 



INDIRECT DISCHARGE 
TO SANITARY 
DRAINAGE 
SYSTEM 



-fxHXl 



iL. I 



CHECK VALVE 



■INDIRECT DISCHARGE 
TO SANITARY DRAINAGE 
SYSTEM 




IRRIGATION ZONE 



IRRIGATION ZONE 



IRRIGATION ZONE 



FIGURE A01 01. 1(2) 
GRAY WATER RECYCLING SYSTEM FOR SUBSURFACE LANDSCAPE IRRIGATION 



636 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



APPENDIX 



AO102.4 Coloring. The gray water shall be dyed blue or green 
with a food grade vegetable dye before such water is supplied 
to the fixtures. 

AO 102.5 Materials. Distribution piping shall conform to one 
of the standards listed in Table P2904.5 of the International 
Residential code. 

AO102.6 Identification. Distribution piping and reservoirs 
shall be identified as containing nonpotable water. Piping iden- 
tification shall be in accordance with Section 608.8 of the Inter- 
national Plumbing Code®. 



SECTION A01 03 

SUBSURFACE LANDSCAPE 

IRRIGATION SYSTEMS 

AO103.1 Collection reservoir. Reservoirs shall be sized to 
limit the retention time of gray water to a maximum of 24 
hours. 

AO103.1.1 Identification. The reservoir shall be identified 
as containing nonpotable water. 

AO103.2 Valves required. A check valve, and a full-open 
valve located on the discharge side of the check valve, shall be 
installed on the effluent pipe of the collection reservoir. 

AO103.3 Makeup water. Makeup water shall not be required 
for subsurface landscape irrigation systems. Where makeup 
water is supplied, the installation shall be in accordance with 
Section AO102.3. 

AO103.4 Disinfection. Disinfection shall not be required for 
gray water used for subsurface landscape irrigation systems. 

AO103.5 Coloring. Gray water used for subsurface landscape 
irrigation systems shall not be required to be dyed. 

AO103.6 Estimating gray water discharge. The system shall 
be sized in accordance with the demands per day per occupant 
based on the type of fixtures connected to the gray water sys- 
tem. The discharge shall be calculated by the following equa- 
tion: 



C =AXB 



(Equation AO-1) 



A = Number of occupants: 

Number of occupants shall be determined by the 
actual number of occupants but not less than two 
occupants for 1 bedroom and one occupant for each 
additional bedroom. 

B = Estimated flow demands for each occupant: 

25 gallons per day (95 Lpd) per occupant for showers, 
bathtubs and lavatories and 15 gallons per day (57 
Lpd) per occupant for clothes washers or laundry 
trays. 

C = Estimated gray water discharge based on the total 
number of occupants. 

AO103.7 Percolation tests. The permeability of the soil in the 
proposed absorption system shall be determined by percolation 
tests or permeability evaluation. 



AO103.7.1 Percolation tests and procedures. At least 
three percolation tests shall be conducted in each system 
area. The holes shall be spaced uniformly in relation to the 
bottom depth of the proposed absorption system. More per- 
colation tests shall be made where necessary, depending on 
system design. 

AO103.7.1.1 Percolation test hole. The test hole shall 
be dug or bored. The test hole shall have vertical sides 
and a horizontal dimension of 4 inches to 8 inches (102 
mm to 203 mm). The bottom and sides of the hole shall 
be scratched with a sharp-pointed instrument to expose 
the natural soil. All loose material shall be removed from 
the hole and the bottom shall be covered with 2 inches 
(5 1 mm) of gravel or coarse sand. 

AO103.7.1.2 Test procedure, sandy soils. The hole shall 
be filled with clear water to a minimum of 12 inches (305 
mm) above the bottom of the hole for tests in sandy soils. 
The time for this amount of water to seep away shall be 
determined and this procedure shall be repeated if the 
water from the second filling of the hole seeps away in 10 
minutes or less. The test shall proceed as follows: Water 
shall be added to a point not more than 6 inches (152 mm) 
above the gravel or coarse sand. Thereupon, from a fixed 
reference point, water levels shall be measured at 10-min- 
ute intervals for a period of 1 hour. Where 6 inches (152 
mm) of water seeps away in less than 10 minutes, a shorter 
interval between measurements shall be used, but in no 
case shall the water depth exceed 6 inches (152 mm). 
Where 6 inches (152 mm) of water seeps away in less than 
2 minutes, the test shall be stopped and a rate of less than 3 
minutes per inch (7 s/mm) shall be reported. The final 
water level drop shall be used to calculate the percolation 
rate. Soils not meeting the requirements of this section 
shall be tested in accordance with Section AO 103. 7. 1.3. 

AO103.7.1.3 Test procedure, other soils. The hole shall 
be filled with clear water, and a minimum water depth of 
12 inches (305 mm) shall be maintained above the bottom 
of the hole for a 4-hour period by refilling whenever nec- 
essary or by use of an automatic siphon. Water remaining 
in the hole after 4 hours shall not be removed. Thereafter, 
the soil shall be allowed to swell not less than 16 hours or 
more than 30 hours. Immediately after the soil swelUng 
period, the measurements for determining the percolation 
rate shall be made as follows: Any soil sloughed into the 
hole shall be removed, and the water level shall be 
adjusted to 6 inches (152 mm) above the gravel or coarse 
sand. Thereupon, from a fixed reference point, the water 
level shall be measured at 30-minute intervals for a period 
of 4 hours, unless two successive water level drops do not 
vary by more than 0.62 inch (16 mm). At least three water 
level drops shall be observed and recorded. The hole shall 
be filled with clear water to a point not more than 6 inches 
(152 mm) above the gravel or coarse sand whenever it 
becomes nearly empty. The water level shall not be 
adjusted during the three measurement periods except to 
the limits of the last measured water level drop. When the 
first 6 inches (152 mm) of water seeps away in less than 30 
minutes, the time interval between measurements shall be 
10 minutes and the test run for 1 hour. The water depth 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



637 



APPENDIX O 



shall not exceed 5 inches (127 mm) at any time during the 
measurement period. The drop that occurs during the final 
measurement period shall be used in calculating the per- 
colation rate. 

AO103.7.1.4 Mechanical test equipment. Mechanical 
percolation test equipment shall be of an approved type. 

AO103.7.2 Permeability evaluation. Soil shall be evalu- 
ated for estimated percolation based on structure and texture 
in accordance with accepted soil evaluation practices. Bor- 
ings shall be made in accordance with Section AO 103.7.1 
for evaluating the soil. 

AO103.8 Subsurface landscape irrigation site location. The 

surface grade of all soil absorption systems shall be located at a 
point lower than the surface grade of any water well or reser- 
voir on the same or adjoining property. Where this is not possi- 
ble, the site shall be located so surface water drainage from the 
site is not directed toward a well or reservoir. The soil absorp- 
tion system shall be located with a minimum horizontal dis- 
tance between various elements as indicated in Table AO103.8. 
Private sewage disposal systems in compacted areas, such as 
parking lots and driveways, are prohibited. Surface water shall 
be diverted away from any soil absorption site on the same or 
neighboring lots. 

TABLE A01 03.8 
LOCATION OF GRAY WATER SYSTEM 



ELEMENT 


MINIMUM HORIZONTAL DISTANCE 


HOLDING TANK 
(feet) 


IRRIGATION 
DISPOSAL 
FIELD (feet) 


Buildings 


5 


2 


Property line adjoining 
private property 


5 


5 


Public water main 


10 


10 


Seepage pits 


5 


5 


Septic tanks 





5 


Streams and lakes 


50 


50 


Water service 


5 


5 


Water wells 


50 


100 



For SI: 1 foot = 304.8 mm. 

AO103.9 Installation. Absorption systems shall be installed 
in accordance with Sections AO103.9.1 through AO103.9.5 to 
provide landscape irrigation without surfacing of gray water. 

AO103.9.1 Absorption area. The total absorption area 
required shall be computed from the estimated daily gray 
water discharge and the design-loading rate based on the 
percolation rate for the site. The required absorption area 
equals the estimated gray water discharge divided by the 
design-loading rate from Table AO 103.9.1. 

AO103.9.2 Seepage trench excavations. Seepage trench 
excavations shall be a minimum of 1 foot (305 mm) to a 
maximum of 5 feet (1524 mm) wide. Trench excavations 
shall be spaced a minimum of 2 feet (610 mm) apart. The 



soil absorption area of a seepage trench shall be computed 
by using the bottom of the trench area (width) multiplied by 
the length of pipe. Individual seepage trenches shall be a 
maximum of 100 feet (30 480 mm) in developed length. 

TABLE A01 03.9.1 
DESIGN LOADING RATE 



PERCOLATION RATE 
(minutes per inch) 


DESIGN LOAD FACTOR 
(gallons per square foot per day) 


to less than 10 


1.2 


10 to less than 30 


0.8 


30 to less than 45 


0.72 


45 to 60 


0.4 



For SI: 1 minute per inch = 2.362 s/mm; 1 gallon per square foot = 40.743 
L/m^. 



AO103.9.3 Seepage bed excavations. Seepage bed excava- 
tions shall be aminimum of 5 feet (1524 mm) wide and have 
more than one distribution pipe. The absorption area of a 
seepage bed shall be computed by using the bottom of the 
trench area. Distribution piping in a seepage bed shall be 
uniformly spaced a maximum of 5 feet (1524 mm) and a 
minimum of 3 feet (914 mm) apart, and a maximum of 3 feet 
(914 mm) and a minimum of 1 foot (305 mm) from the side- 
wall or head wall. 

AO103.9.4 Excavation and construction. The bottom of a 
trench or bed excavation shall be level. Seepage trenches or 
beds shall not be excavated where the soil is so wet that such 
material rolled between the hands forms a soil wire. All 
smeared or compacted soil surfaces in the sidewalls or bot- 
tom of seepage trench or bed excavations shall be scarified 
to the depth of smearing or compaction and the loose mate- 
rial removed. Where rain falls on an open excavation, the 
soil shall be left until sufficiently dry so a soil wire will not 
form when soil from the excavation bottom is rolled 
between the hands. The bottom area shall then be scarified 
and loose material removed. 

AO103.9.5 Aggregate and backfill. A minimum of 6 
inches (152 mm) of aggregate ranging in size from Vj to 2^ 1 2 
inches (13 mm to 64 mm) shall be laid into the trench below 
the distribution piping elevation. The aggregate shall be 
evenly distributed a minimum of 2 inches (5 1 mm) over the 
top of the distribution pipe. The aggregate shall be covered 
with approved synthetic materials or 9 inches (229 mm) of 
uncompacted marsh hay or straw. Building paper shall not 
be used to cover the aggregate. A minimum of 9 inches (229 
mm) of soil backfill shall be laid above the covering. 

AO103.10 Distribution piping. Distribution piping shall be 
not less than 3 inches (76 mm) in diameter. Materials shall 
comply with Table AO103.10. The top of the distribution pipe 
shall be not less than 8 inches (203 mm) below the original sur- 
face. The slope of the distribution pipes shall be a minimum of 
2 inches (51 mm) and a maximum of 4 inches (102 mm) per 
100 feet (30 480 mm). 

AO103.il Joints. Distribution pipe shall be joined in accor- 
dance with Section P3003 of the International Residential 
Code. •' 



638 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



APPENDIX 



TABLE A01 03.10 
DISTRIBUTION PIPE 



MATERIAL 


STANDARD 


Polyethylene (PE) plastic pipe 


ASTM F 405 


Polyvinyl chloride (PVC) plastic pipe 


ASTM D 2729 


Polyvinyl chloride (PVC) plastic pipe 
with pipe stiffness of PS 35 and PS 50 


ASTM F 1488 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



639 



640 2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX P 

SPRINKLING 



The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



APlOl Fire sprinklers. An approved automatic fire sprinkler 
system shall be installed in new one- and two-family dwellings 
and townhouses in accordance with Section 903.3.1 of the 
International Building Code. 




2006 INTERNATIONAL RESIDENTIAL CODE® 641 




642 2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX Q 

ICC INTERNATIONAL RESIDENTIAL CODE ELECTRICAL 
PROVISIONS/NATIONAL ELECTRICAL CODE CROSS-REFERENCE 



This table is a cross-reference of the International Residential Code, Chapters 33 through 42, 
and the 2005 National Electrical Code (NFPA 70-2005). 



International Residential Code 



National Electrical Code 



CHAPTER 33 

SECTION E3301 

E3301.1 
E3301.2 
E3301.3 
E3301.4 

SECTION E3302 

E3302.1 
E3302.2 
E3302.3 

SECTION E3303 

E3303.1 
E3303.2 
E3303.3 

SECTION E3304 

E3304.1 

E3304.2 

E3304.3 

E3304.4 

E3304.5 

E3304.6 

E3304.7 

E3304.8 

E3304.9 

E3304.10 

E3304.il 

SECTION E3305 

E3305.1 
Figure E3305.1 



E3305.2 


E3305.3 


E3305.4 


E3305.5 


E3305.6 


E3305.7 


SECTION E3306 


E3306.1 



GENERAL REQUIREMENTS 

GENERAL 

Applicability None 

Scope 90.2 

Not covered 90.2 

Additions and alterations None 

BUILDING STRUCTURE PROTECTION 

Drilling and notching None 

Penetrations of fire-resistance-rated assemblies 300.21 

Penetrations of firestops and draftstops 300.21 

INSPECTION AND APPROVAL 

Approval 1 10.2 

Inspection required None 

Listing and labeling 1 10.3 

GENERAL EQUIPMENT REQUIREMENTS 

Voltages 1 10.4 

Interrupting rating 1 10.9 

Circuit characteristics 1 10.10 

Protection of equipment 110.11 

Unused openings 110.12(A) 

Integrity of electrical equipment 1 10. 12(C) 

Mounting 110.13(A) 

Energized parts guarded against accidental contact 1 10.27(A) 

Prevent physical damage 1 10.27(B) 

Equipment identification 11 0.21 

Identification of disconnecting means 1 10.22 

EQUIPMENT LOCATION AND CLEARANCES 

Working space and clearances 1 10.26 

Working space and clearances 1 10.26(A) 

Footnote 1 110.26(F)(1)(a) 

Footnote 2 1 10.26(A)(3) and 1 10.26(E) 

Footnote 3 1 10.26(B) 

Footnote 4 230.70(A), 240.24(D) and 240.24(E) 

Footnote 5 110.26(D) 

Working clearances for energized equipment and panelboards 110.26(A)(1), (2), & (3) 

Clearances over panelboards 1 10.26(F)(1)(a) 

Location of clear spaces 1 10.26(B), 230.70(A) and 240.24(D) & (E) 

Access and entrance to working space 1 10.26(C)(1) 

Illumination 1 10.26(D) 

Headroom 1 10.26(E) 



ELECTRICAL CONDUCTORS AND CONNECTIONS 

General 



Articles 110, 300 and 310 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



643 



APPENDIX Q 



E3306.2 

E3306.3 

E3306.4 

E3306.5 

E3306.6 

E3306.7 

E3306.8 

E3306.9 

E3306.10 

E3306.10.1 

E3306.10.2 
E3306.10.3 

SECTION E3307 

E3307.1 

E3307.2 

E3307.3 

E3307.4 

E3307.4.1 

E3307.4.2 

CHAPTER 34 
SECTION 3401 

CHAPTER 35 

SECTION E3501 

E3501.1 

E3501.2 

E3501.3 

E3501.4 

E3501.5 

E3501.6 

E3501.6.1 

E3501.6.2 

E3501.7 

SECTION E3502 

E3502.1 

E3502.2 

E3502.2.1 

Table E3502.2 

E3502.3 

E3502.4 

SECTION E3503 

E3503.1 
Table E3503.1 



Conductor material 1 10.5 

Minimum size of conductors 3 10.5 

Stranded conductors 310.3 

Individual conductor insulation 310.2(A) and 310.8 

Conductors in parallel 310.4 

Conductors of the same circuit 300.3(B) 

Aluminum and copper connections 1 10. 14 

Terminals 1 10.14(A) 

Splices 110.14(B) 

Continuity 300.13(A) 

Exception 300.13(A) 

Device connections 250.148 and 300.13(B) 

Length of conductor for splice or termination 300.14 

CONDUCTOR IDENTIFICATION 

Grounded conductors 200.6(A), 200.6(B) and 310.12(A) 

Equipment grounding conductors 250.119 and 310.12(B) 

Ungrounded conductors 310.12(C), 310.12(C), Exception and 200.7(C)(1) & (C)(2) 

Identification of terminals 200.10 

Device terminals 200.10(A) 

Receptacles, plugs, and connectors 200.10(B) 



ELECTRICAL DEFINITIONS 
GENERAL 

SERVICES 



Article 100, Definitions 



E3503.2 



E3503.3 
E3503.3.1 



GENERAL SERVICES 

Scope 230.1 

Number of services 230.2 

One building or other structure not to be supplied through another 230.3 

Other conductors in raceway or cable 230.7 

Raceway seal 230.8 

Service disconnect required 230.70 

Marking of service equipment and disconnects 230.66 and 230.70(B) 

Service disconnect location 230.70 and 230.72(C) 

Maximum number of disconnects 230.71(A) 

SERVICE SIZE AND RATING 

Rating of ungrounded conductors 230.79(C) and (D) 

Service load 220.82(A) 

Services under 100 amperes None 

Minimum service load calculation 220.82 (B) and (C) 

Rating of service disconnect 230.79 & 230.80 

Voltage rating 220.82(a) 

SERVICE, FEEDER AND GROUNDING ELECTRODE CONDUCTOR SIZING 

Grounded and ungrounded service conductor size 310.15(B)(6) 

Service conductor and grounding electrode conductor sizing. Table 310.15(B)(6) and Table 250.66 

Footnote 1 250.64(E) 

Footnote 2 250.64(B) 

Footnote 3 250.64(B) 

Footnote 4 .^ 250.66(A) and (B) 

Ungrounded service conductors for accessory buildings and structures 230.79(D) 

Exception 1 and 230.79(A) 

Exception 2 and 230.79(B) 

Overload protection 230.90 

Ungrounded conductor 230.90(A) 



644 



2006 INTERNATIONAL RESIDENTIAL CODE® 



APPENDIX Q 



E3503.3.2 
E3503.3.3 
E3503.4 
E3503.5 

SECTION E3504 

E3504.1 
Figure E3504.1 
E3504.2 
E3504.2.1 



Figure E3504.2.1 
E3504.2.2 



E3504.3 
E3504.4 
E3504.5 
E3504.6 

SECTION E3505 

E3505.1 



E3505.2 

E3505.3 

E3505.4 

E3505.5 

E3505.6 

E3505.7 

E3505.8 

E3505.9 

E3505.9.1 

E3505.9.2 

E3505.9.3 

E3505.9.4 
E3505.9.5 
E3505.9.6 
E3505.9.7 

SECTION E3506 

E3506.1 
E3506.2 
E3506.3 
E3506.4 

SECTION E3507 

E3507.1 

E3507.2 
E3507.3 

E3507.3.1 



Exception 230.90(A), Exception No. 3 

Not in grounded conductor 230.90(B) 

Location 230.91 

Grounding electrode conductor size 250.66 

Temperature limitations " 1 10.14(C)(1) 

OVERHEAD SERVICE-DROP AND SERVICE CONDUCTOR INSTALLATION 

Clearances on buildings 230.9 

Clearances from building openings 230.9 

Vertical clearances 230.24 

Above roofs 230.24(A) 

Exception 1 230.24(A), Exception No. 1 

Exception 2 230.24(A), Exception No. 2 

Exception 3 230.24(A), Exception No. 3 

Exception 4 230.24(A), Exception No. 4 

Clearances from roofs 230.24 

Vertical clearance from grade 230.24(B) 

Item 1 . . 230.24(B)(1) 

Item 2 230.24(B)(2) 

Item 3 230.24(B)(4) 

Point of attachment 230.26 

Means of attachment 230.27 

Service masts as supports 230.28 

Supports over buildings 230.29 

SERVICE-ENTRANCE CONDUCTORS 

Insulation of service-entrance conductors 230.41 

Exception 1 230.41, Exception 

Exception 2 230.41, Exception 

Wiring methods for services 230.43 

Spliced conductors 230.46 

Protection against physical damage 230.49 

Protection of service cables against damage 230.50(A) 

Direct sunlight exposure 310.8(D) 

Mounting supports 230.51 

Raceways to drain 230.53 

Overhead service locations 230.54 

Rain-tight service head 230.54(A) 

Service cable, service head or gooseneck 230.54(B) 

Service head location 230.54(C) 

Exception 230.54(C), Exception 

Separately bushed openings 230.54(E) 

Drip loops 230.54(F) 

Conductor arrangement 230.54(G) 

Secured 230.54(D) 

SERVICE EQUIPMENT— GENERAL 

Service equipment enclosures 230.62 

Working space 1 10.26 

Available short-circuit current None 

Marking 230.66 

SYSTEM GROUNDING 

System service ground 250.20(B)(1) and 250.24(A) 

Location of grounding electrode conductor connection 250.24(A)(1) and (A)(5) 

Buildings or structures supplied by feeder(s) or branch circuit(s) 250.32(A) 

Exception 250.32(A), Exception 

Equipment grounding conductor 250.32(B)(1) and Table 250.122 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



645 



APPENDIX Q 



E3507.3.2 
E3507.4 
E3507.5 
E3507.6 

SECTION E3508 

E3508.1 

E3508.1 

E3508.1.1 

E3508. 1.1.1 

E3508.1.2 

E3508.1.3 

E3508.1.4 

E3508. 1.4.1 

E3508.1.5 

E3508.2 

E3508.3 

E3508.4 

E3508.5 

E3508.6 

SECTION E3509 

E3509.1 

E3509.2 

E3509.3 

E3509.4 

E3509.4.1 

E3509.4.2 

E3509.4.3 

E3509.4.4 

E3509.5 

E3509.6 

E3509.7 

SECTION E3510 

E3510.1 
E3510.2 
E3510.3 

SECTION E3511 
TRODES 

E3511.1 
E3511.2 
E3511.3 
E3511.4 
E3511.5 

CHAPTER 36 

SECTION E3601 

E3601.1 
E3601.2 
E3601.3 
E3601.4 
E3601.5 

SECTION E3602 

E3602.1 
E3602.2 

646 



Grounded conductor 250.32(B)(2) 

Grounding electrode conductor 250.24(D) 

Main bonding jumper 250.28 

Common grounding electrode 250.58 

GROUNDING ELECTRODE SYSTEM 

Grounding electrode system 250.50 

Exception 250.50 Exception 

Metal underground water pipe 250.52(A)(1) 

Installation 250.53(D) and 250.53(E) 

Concrete-encased electrode 250.502(A)(3) 

Ground Rings 250.52(A)(4), 250.53(F) 

Rod and pipe electrodes 250.52(A)(5) 

Installation 250.53(G) 

Plate electrodes 250.52(A)(6) and 250.53(H) 

Bonding Jumper 250.53(C) 

Rod, pipe and plate electrode requirements 250.53(A) and (G) 

Resistance of rod, pipe and plate electrodes 250.56 

Aluminum Electrodes 250.52(B)(2) 

Metal underground gas piping system 250.52(B)(1) 

BONDING 

General 250.90 

Bonding of service equipment 250.92(A) 

Bonding to other systems 250.94 

Method of bonding at the service 250.92(B) 

Grounded service conductor 250.92(B)(1) 

Threaded connections 250.92(B)(2) 

Threadless couplings and connectors 250.92(B)(3) 

Other devices 250.92(B)(4) 

Sizing bonding jumper on supply side of service and main bonding jumper 250.102(C) 

Metal water piping bonding 250.104(A) 

Bonding other metal piping 250. 104(B) 

GROUNDING ELECTRODE CONDUCTORS 

Continuous 250.64(C) and (E) 

Securing and protection against physical damage 250.64(A) and (B) 

Enclosures for grounding electrode conductors 250.64(E) 

GROUNDING ELECTRODE CONDUCTOR CONNECTION TO GROUNDING ELEC- 

Methods of grounding connection to electrodes 250.70 

Accessibility 250.68(A) 

Effective grounding path 250.68(B) 

Protection of ground clamps and fittings 250.10 

Clean surfaces 250. 12 

BRANCH CIRCUIT AND FEEDER REQUIREMENTS 

GENERAL 

Scope None 

Branch-circuit and feeder ampacity 210.19(A) and 215.2(A)(1) 

Selection of ampacity 310.15(A)(2) 

Multioutlet branch circuits 210.19(A)(2) 

Multiwire branch circuits 210.4 

BRANCH CIRCUIT RATINGS 

Branch-circuit voltage limitations 210.6(A) and (B) 

Branch-circuit ampere rating 210.3 

2006 INTERNATIONAL RESIDENTIAL CODE® 



APPENDIX Q 



E3602.3 

E3602.4 

E3602.5 

E3602.6 

E3602.7 

E3602.8 

E3602.9 

E3602.9.1 

E3602.10 

E3602.il 

E3602.12 

E3602.12.1 

E3602.12.2 

E3602.13 

Table E3602. 13 

SECTION E3603 

E3603.1 
E3603.2 
E3603.3 
E3603.4 
E3603.5 
E3603.6 

SECTION E3604 

E3604.1 
E3604.2 
E3604.3 
Table E3604.3(l) 

Table E3604.3(2) 

E3604.4 
E3604.5 
E3604.6 
E3604.7 

SECTION E3605 

E3605.1 

Table E3 605.1 

E3605.2 

Table E3605.2 

E3605.3 

Table E3605.3 

E3605.4 

E3605.4.1 

E3605.4.2 

E3605.4.3 

E3605.4.4 

E3605.5 

E3605.5.1 

E3605.5.2 

E3605.5.3 

E3605.5.4 

E3605.6 

E3605.7 

E3605.8 



Fifteen- and 20-ampere branch circuits 210.23(A) 

Thirty-ampere branch circuits 210.23(B) 

Branch circuits serving multiple loads or outlets 210.23(A) 

Branch circuits serving a single motor 430.22(A) 

Branch circuits serving motor-operated and combination loads 220.4(A) 

Branch-circuit inductive lighting loads 220.4(B) 

Branch-circuit load for ranges and cooking appliances Table 220.19, Note 4 

Minimum branch circuit for ranges 210.19(A)(3) 

Branch circuits serving heating loads 422.13 and 424.3(A) 

Branch circuits for air-conditioning and heat pump equipment . . . 440.35, 440.4(B) and 440.62(A) 

Branch circuits serving room air conditioners 440.62(A) 

Where no other loads are supplied 440.62(B) 

Where lighting units or other appliances are also supplied 440.62(C) 

Branch-circuit requirement — summary 210.24 and 210.25 

Branch-circuit requirement — summary Table 210.24 

REQUIRED BRANCH CIRCUITS 

Branch circuits for heating 422.12 and 422.12 Exception 

Kitchen and dining area receptacles 210.52 (B)(1) 

Laundry circuit 210.23(A) Exception and 210.11(C)(2) 

Bathroom branch circuits 210.11(C)(3) 

Number of branch circuits 210.11(A) 

Branch-circuit load proportioning 210.1 1(B) 

FEEDER REQUIREMENTS 

Conductor size Table 310.15(B)(6), Sections 215.2 (A)(3), (A)(4) and 220.10(A) 

Minimum feeder conductor size 215.2(A)(2) 

Feeder loads Table 220.1 1 

Feeder load calculation Table 220.11, Table 220.30(C), Sections 220.14, 220.15, 

220.17, 220.18 and 220.19 
Demand loads for electric ranges, wall-mounted ovens, counter-mounted 

cooking units and other cooking appliances over P/4 kVA rating Table 220.19 

Feeder neutral load 220.22 

Lighting and convenience receptacle load 220.3(A), Table 220.3(A) 

Ampacity and computed loads 220. 10 

Feeder and branch-circuit conductors 240.21(A) 

CONDUCTOR SIZING AND OVERCURRENT PROTECTION 

General 310.15(A) 

Allowable ampacities Tables 310.16 and 240.4 D 

Correction factors for ambient temperatures Table 310.16 

Ambient temperature correction factors Table 310.16, Correction factors 

Adjustment factor for conductor proximity 310.15(B)(2)(a) 

Conductor proximity adjustment factors Table 310.15(B)(2)(a) 

Temperature limitations 1 10.14(C) 

Conductors rated 60°C 110.14(C)(1)(a) 

Conductors rated 75°C 110.14(C)(1)(b) 

Separately installed pressure connectors 110.14(C)(2) 

Conductors of type NM cable 334.80 and 334.112 

Overcurrent protection required Table 310.15(B)(6), Sections 240.4, 240.5, 240.21 

Cords 240.5 

Overcurrent devices of the next higher size 240.4(B) 

Small conductors 240.4(D) 

Air conditioning and heat pump equipment 240.4(G) 

Fuses and fixed trip circuit breakers Section 240.6 

Location of overcurrent devices in or on premises 240. 24(A), (C),(D),(E) 

Ready access for occupants Section 240.24(B) 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



647 



APPENDIX Q 



E3605.9 

SECTION E3606 

E3606.1 
E3606.2 
E3606.3 
E3606.4 
E3606.5 

CHAPTER 37 

SECTION E3701 

E3701.1 
E3701.2 
Table E370 1.2 
E3701.3 
E3701.4 
Table E370 1.4 

SECTION E3702 

E3702.1 
Table E3702.1 
E3702.2 
E3702.2.1 
E3702.2.2 

E3702.3 

E3702.3.1 

E3702.3.2 

E3702.3.3 

E3702.4 

E3702.5 

E3702.6 

SECTION E3703 

E3703.1 

Table E3703.1 

E3703.2 

E3703.3 

E3703.4 

E3703.5 

E3703.6 

E3703.7 

E3703.8 

E3703.9 

CHAPTER 38 

SECTION E3801 

E3801.1 

E3801.2 

E3801.2.1 

E3802.2.2 

E3801.2.3 

E3801.3 

E3801.3.1 

E3801.3.2 

E3801.4 

E3801.4.1 



Enclosures for overcurrent devices Section 240.30 (A) and (B) 

PANELBOARDS 

Panelboard rating 408.13 

Panelboard circuit identification 408.4 

Panelboard overcurrent protection 408.16(A) 

Grounded conductor terminations 408.41 

Back-fed devices 408.36(F) 

WIRING METHODS 

GENERAL REQUIREMENTS 

Scope Section 300. 1 

Allowable wiring methods Sections 1 10.8 and 300.3(A) 

Allowable wiring methods None 

Circuit conductors 300.3(B) 

Wiring method applications Chapter 3 and Section 300.2 

Allowable applications for wiring methods Chapter 3 and Section 300.2 

ABOVE-GROUND INSTALLATION REQUIREMENTS 

Installation and support requirements Chapter 3 

General installation and support requirements for wiring methods Chapter 3 

Cables in accessible attics 320.23 and 334.23 

Across structural members 320.23(A) and 334.23 

Cable installed through or parallel to 

framing members 320.17, 320.23(A), 334.17, 334.23 and 300.4(B) 

Exposed cable 320.15 and 334.15 

Surface installation 334.15(A) 

Protection from physical damage. 334.15(B) 

Locations exposed to direct sunlight 310.8(D) 

In unfinished basements 334.15(C) 

Bends 320.24 and 334.24 

Raceways exposed to different temperatures Section 300.7(A) 

UNDERGROUND INSTALLATION REQUIREMENTS 

Minimum cover requirements 300.5(A) 

Minimum cover requirements, burial in inches Table 300.5 

Warning ribbon 300.5(D)(3) 

Protection from damage 300.5(D) 

Splices and taps 300.5(E) 

Backfill 300.5(F) 

Raceway seals 300.5(G) 

Bushing 300.5(H) 

Single conductors 300.5(1) 

Ground movement Section 300. 5(J) 

POWER AND LIGHTING DISTRIBUTION 

RECEPTACLE OUTLETS 

General 210.50 and 210.52 

General-use receptacle distribution 210.52(A) 

Spacing 210.52(A)(1) 

Wall space 210.52(A)(2) 

Floor receptacles 210.52(3) 

Small appliance receptacles 210.52(B)(1) 

Other outlets prohibited 210.52(B)(2) 

Limitations 210.52(B)(3) 

Countertop receptacles 210.52(C) 

Wall counter space 210.52(C)(1) 



648 



2006 INTERNATIONAL RESIDENTIAL CODE"" 



APPENDIX Q 



E3801.4.2 

E3801.4.3 

E3801.4.4 

E3801.4.5 

E3801.5 

E3801.6 

E3801.7 

E3801.8 

E3801.9 

E3801.10 

E3801.il 

SECTION E3802 

E3802.1 

E3802.2 

E3802.3 

E3802.4 

E3802.5 

E3802.6 

E3802.7 

E3802.8 

E3802.9 

E3802.10 

E3802.il 

E3802.12 

SECTION E3803 

E3803.1 
E3803.2 
E3803.3 
E3803.4 

SECTION E3804 

E3804.1 
E3804.2 
E3804.3 
E3804.3.1 
E3804.4 
E3804.5 
E3804.6 

Tables E3804.6(l)- 
E3804.6(10) 

E3804.7 

CHAPTER E3805 

E3805.1 

E3805.1.1 

E3805.1.2 

E3805.1.3 

E3805.1.4 

E3805.1.5 

E3805.1.6 

E3805.1.7 

E3805.2 

E3805.3 

E3805.3.1 

E3805.3.2 



Island counter spaces 210.52(C)(2) 

Peninsular counter space 210.52(C)(3) 

Separate spaces 210.52(C)(4) 

Receptacle outlet location 210.52(C)(5) 

Appliance outlets 210.50(C) 

Bathroom 210.52(D) 

Outdoor outlets 210.52(E) 

Laundry areas 210.52(F) 

Basements and garages 210.52(G) 

Hallways 210.52(H) 

HVAC outlet 210.63 

GROUND-FAULT AND ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION 

Bathroom receptacles 210.8(A)(1) 

Garage and accessory building receptacles 210.8(A)(2) 

Outdoor receptacles 210.8(A)(3) 

Crawl space receptacles 210.8(A)(4) 

Unfinished basement receptacles 210.8(A)(5) 

Kitchen receptacles 210.8(A)(6) 

Laundry, utility and wet bar sink receptacles 210.8(A)(7) 

Boathouse receptacles 210.8(A)(8) 

Boat hoists 210.8(C) 

Electrically heated floors 424.44(G) 

Exempt receptacles 210.8(A)(2) 

Bedroom outlets 210.12 

LIGHTING OUTLETS 

General 210.70(A) 

Habitable rooms 210.70(A)(1) 

Additional locations 210.70(A)(2) 

Storage or equipment spaces 210.70(A)(3) 

GENERAL INSTALLATION REQUIREMENTS 

Electrical continuity of metal raceways and enclosures 300.10 

Mechanical continuity — raceways and cables 300.12 

Securing and supporting 300. 1 1 (A) 

Prohibited means of support 300.1 1(C) 

Raceways as means of support 300.1 1(B) 

Raceway installations 300. 1 8 

Conduit and tubing fill 300.17 and Chapter 9, Table 1 

Maximum number of conductors in conduit or tubing 300.17 and Chapter 9, Table 1, Note 1 

Air handling — stud cavity and joist spaces Section 300.22(C), Exception 

BOXES, CONDUIT BODIES, AND FITTINGS 

Box, conduit body or fitting — where required 300.15 

Equipment 300.15(B) 

Protection 300.15(C) 

Integral enclosure 300.15(E) 

Fitting 300.15(F) 

Buried conductors 300.15(G) 

Luminaires 300.15(J) 

Closed loop 300.15(M) 

Metal boxes 3 14.4 

Nonmetallic boxes 3 14.3 

Nonmetallic-sheathed cable and nonmetallic boxes 314.17(C) 

Securing to box 314.17(B) and (C) 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



649 



APPENDIX Q 



E3805.3.3 

E3805.4 

E3805.5 

E3805.6 

E3805.7 

E3805.8 

E3805.9 

E3805.10 

E3805.il 

E3805.12 

E3805.12.1 

Table E3 805. 12.1 

E3805. 12.1.1 

E3805. 12.1.2 

E3805.12.2 

E3805. 12.2.1 

Table E3805. 12.2.1 

E3805. 12.2.2 

E3805. 12.2.3 

E3805. 12.2.4 

E3805. 12.2.5 

E3805.12.3 

E3805. 12.3.1 

SECTION E3806 

E3806.1 

E3806.1.1 

E3806.2 

E3806.3 

E3806.4 

E3806.5 

E3806.6 

E3806.7 

E3806.8 

E3806.8.1 

E3806.8.2 

E3806.8.2.1 

E3806.8.2.2 

E3806.8.3 

E3806.8.4 

E3806.8.5 

E3806.8.6 

E3806.9 

E3806.10 

E3806.il 

SECTION E3807 

E3 807.1 
E3807.2 
E3807.3 
E3807.4 
E3807.5 
E3807.6 
E3807.7 
E3807.8 



Conductor rating 314.17(C) 

Minimum depth of outlet boxes 3 14.24 

Boxes enclosing flush-mounted devices 314.19 

Boxes at luminaire (lighting fixture) outlets 314.27(A) 

Maximum luminaire (fixture) weight 314.27(B) 

Floor boxes 314.27(C) 

Boxes at fan outlets 314.27(D) 

Conduit bodies, junction, pull and outlet boxes to be accessible 314.29 

Damp or wet locations 314.2 

Number of conductors in outlet, device, and junction boxes and conduit boxes 314.16 

Box volume calculations 314.16(A) 

Maximum number of conductors in metal boxes Table 314.16 

Standard boxes 314.16(A)(1) 

Other boxes 314.16(A)(2) 

Box fill calculations 314.16(B) 

Conductor fill 314.16(B)(1) and Table 314.16 

Volume allowance required per conductor Table 314.16 

Clamp fill 314.16(B)(2) 

Support fittings fill 314.16(B)(3) 

Device or equipment fill 314.16(B)(4) 

Equipment grounding conductor fill 314.16(B)(5) 

Conduit bodies 314.16(C)(1) 

Splices, taps or devices 314.16(C)(2) 

INSTALLATION OF BOXES, CONDUIT BODIES AND FITTINGS 

Conductors entering boxes, conduit bodies or fittings 314.17 

Insulated fittings 300.4(F) 

Openings 314.17(A) 

Metal boxes, conduit bodies and fittings 314.17, 314.17(B) 

Unused openings 1 10. 12(A) 

In wall or ceiling 314.20 

Plaster, gypsum board and plasterboard 314.21 

Exposed surface extensions 3 14.22 

Supports 314.23 

Surface mounting 314.23(A) 

Structural mounting 3 14.23(B) 

Nails 314.23(B)(1) 

Braces 314.23(B)(2) 

Mounting in finished surfaces 3 14.23(C) 

Raceway supported enclosures without devices or fixtures 314.23(E) 

Raceway supported enclosures with devices or fixtures 314.23(F) 

Enclosures in concrete or masonry 314.23(G) 

Covers and canopies 3 14.25 

Metal covers and plates 314.25(A) 

Exposed combustible finish 314.25(B) 

CABINETS AND PANELBOARDS 

Enclosures for switches or overcurrent devices 312.8 

Damp or wet locations 3 12.2(A) 

Position in wall 312.3 

Repairing plaster, drywall and plasterboard 312.4 

Unused openings 110.12(A), 408.7 

Conductors entering cabinets 300.4(F) and 312.5(B) 

Openings to be closed 312.5(A) 

Cables 312.5(C) 



650 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX Q 



SECTION E3808 

E3808.1 
E3808.2 

E3808.3 

E3808.4 

E3808.5 

E3808.6 

E3808.7 

E3808.8 

E3808.8.1 

E3808.8.2 

E3808.8.3 

E3808.9 

E3808.10 

E3808.il 

E3808.12 

Table E3 808. 12 

E3808.12.1 

E3808.13 

E3808.14 

E3808.15 

E3808.16 

E3808.17 

E3808.18 

E3808.19 

E3808.20 

SECTION E3809 

E3809.1 
E3809.2 
Table E3809.2 
E3809.3 
E3809.4 

CHAPTER 39 

SECTION E3901 

E3901.1 

E3901.2 

E3901.3 

E3901.4 

E3901.5 

E3901.6 

E3901.7 

E3901.8 

E3901.9 

E3901.10 

E3901.il 

E3901.11.1 

E3901.12 

SECTION E3902 

E3902.1 
E3902.1.1 
E3902.1.2 
Table E3902. 1.2 



GROUNDING 

Metal enclosures 250.86 

Equipment fastened in place or connected by permanent wiring methods (fixed) 250.1 10(1), 

(2), and (3) 

Specific equipment fastened in place or connected by 

permanent wiring methods 250.1 12(J), (L), and (M) 

Performance of fault current path 250.4(A)(5) 

Earth as a grounding conductor 250.4(A)(5) 

Load-side neutral 250.24(A)(5) 

Load-side equipment 250.142 (B) 

Types of equipment grounding conductors 250.1 18 

Flexible metal conduit 250.118(5) 

Liquid-tight flexible metal conduit 250.1 18(6) 

Nonmetallic sheathed cable (Type NM) 334.108 

Equipment fastened in place or connected by permanent wiring methods 250.134 

Methods of equipment grounding 250 Part (VII) 

Equipment grounding conductor installation 250.120 

Equipment grounding conductor size 250.122(A) and (B) 

Equipment grounding conductor sizing Table 250.122 

Multiple circuits 250.122(C) 

Continuity and attachment of equipment grounding conductors to boxes 250.148 

Connecting receptacle grounding terminal to box 250.146(A), (B), and (C) 

Metal boxes 250.8, 250.148(C) 

Nonmetallic boxes 250.148(D) 

Clean surfaces 250.12 

Bonding other enclosures 250.96(A) 

Size of equipment bonding jumper on load side of service 250.102(D) 

Installation — equipment bonding jumper 250.102(E) 

FLEXIBLE CORDS 

Where permitted 400.7 and 400.8 

Loading and protection 240.4, 240.5(A), 240.5(B)(1), 400.5, and 400.13 

Maximum ampere load for flexible cords Table 400.5(A) 

Splices 400.9 

Attachment plugs 400.7(B) 

DEVICES AND LIGHTING FIXTURES 

SWITCHES 

Rating and application of snap switches 404.14(A) 

CO/ALR snap switches 404.14(C) 

Indicating 404.7 

Time switches and similar devices 404.5 

Grounding of enclosures 404. 12 

Access 404.8(A) 

Wet locations 404.4 

Grounded conductors 404.2(B) 

Switch connections 404.2(A) 

Box mounted 404.10(B) 

Snap switch faceplates 404.9(A) 

Faceplate grounding 404.9(B) 

Dimmer switches 404. 14(E) 

RECEPTACLES 

Rating and type 406.2(A)(B) 

Single receptacle 210.21(B)(1) 

Two or more receptacles 210.21(B)(3) 

Receptacle ratings for various size multioutlet circuits Table 210.21(B)(3) 



2006 INTERNATIONAL RESIDENTIAL CODE' 



® 



651 



APPENDIX Q 



E3902.2 

E3902.3 

E3902.4 

E3902.5 

E3902.6 

E3902.7 

E3902.8 

E3902.9 

E3902.10 

E3902.il 

E3902.12 

SECTION E3903 

E3903.1 

E3903.2 

E3903.3 

E3903.4 

E3903.5 

E3903.6 

E3903.7 

E3903.8 

E3903.9 

E3903.10 

E3903.il 

Figure E3903.il 

E3903.12 

E3903.12.1 

E3903.12.2 

SECTION E3904 

E3904.1 
E3904.2 
E3904.3 
E3904.4 
E3904.5 
E3904.6 
E3904.7 
E3904.8 
E3904.9 

SECTION E3905 

E3905.1 
E3905.2 
E3905.3 
E3905.4 
E3905.5 
E3905.6 

CHAPTER 40 

SECTION E4001 

E4001.1 

E4001.2 

E4001.3 

Table E400 1.3 

E4001.4 

E400 1.4.1 

E4001.5 



Grounding type 406.3(A) 

CO/ALR receptacles 406.2(C) 

Faceplates 406.5(B) 

Position of receptacle faces 406.4(D), and 406.5 

Receptacles mounted in boxes 406.4(A), and 406.4(B) 

Receptacles mounted on covers 406.4(C) 

Damp locations 406.8(A) 

15- and 20-ampere receptacles in wet locations 406.8(B)(1) 

Other receptacles in wet locations 406.8(B)(2) 

Bathtub and shower space 406.8(C) 

Flush mounting with faceplate 406.8(E) 

LUMINAIRES 

Energized parts 410.3 

Luminaires near combustible material 410.5 

Exposed conductive parts 410.18(A) 

Screw-shell type 410.47 

Recessed incandescent luminaires 410.65(C) 

Thermal protection 410.73(E) 

High-intensity discharge luminaires 410.73(F) 

Wet or damp locations 410.4(A) 

Lampholders in wet or damp locations 410.49 

Bathtub and shower area 410.4(D) 

Luminaires in clothes closets 410.8(A), (B), (C), and (D) 

Closet storage space Figure 410.8 

Luminaire wiring — general 410.22 

Polarization of luminaires 410.23 

Luminaires as raceways 410.31 

LUMINAIRE INSTALLATION 

Outlet box covers 410.12 

Combustible material at outlet boxes 410. 13 

Access 410.16(B) 

Supports 410.15(A) 

Means of support 410.16(A) 

Exposed ballasts 410.76(A) 

Combustible low-density cellulose fiberboard 410.76(B) 

Recessed fixture clearance 410. 66(A)(1), (A)(2) 

Recessed fixture installation 410.66(B) 

TRACK LIGHTING 

Installation 410.101(A) and (B) 

Fittings 410.101(A) and (D) 

Connected load 410.101(B) 

Prohibited locations 410.101(C) 

Fastening 410.104 

Grounding 410.105(B) 

APPLIANCE INSTALLATION 

GENERAL 

Scope 422.1 and 424.1 

Installation 110.3(6) and 422.17 

Flexible cords 422.16 

Flexible cord length 422.16(B)(1), (2) and (4) 

Overcurrent protection 422. 1 1 

Single nonmotor-operated appliance 422.1 1(E) 

Disconnecting means 422.30, 422.35 and 424.19 



652 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



APPENDIX Q 



TableE4001.5 

E4001.6 

E4001.7 

CHAPTER 41 

SECTION E4101 

E4101.1 
E4101.2 

SECTION E4102 

E4102.1 
E4102.2 
E4102.3 

SECTION E4103 

E4103.1 

E4103.1.1 

E4103.1.2 

E4103.1.3 

E4103.1.4 

E4103.1.5 

E4103.1.6 

E4103.2 

E4103.3 

E4103.4 

E4103.4.1 

E4103.4.2 

E4103.4.3 

E4103.4.4 

E4103.4.5 

E4103.5 

Table E4 103. 5 

Figure E4 103. 5 

E4103.6 

Table E4103.6 

SECTION E4104 

E4 104.1 
E4 104.2 
E4104.3 
E4 104.4 

SECTION E4105 

E4105.1 

E4 105.2 

E4105.3 

E4105.4 

E4105.5 

E4105.6 

E4105.6.1 

E4105.7 

E4105.8 

SECTION E4106 

E4 106.1 
E4106.2 
E4106.3 
E4106.4 



Disconnecting means 422.31(A),(B), 422.34, 422.35, 424.19, 424.20 and 440.14 

Support of ceiling-suspended paddle fans 422.18 

Snow-melting and deicing equipment protection 210.8(A)(3) Exception and 426.28 

SWIMMING POOLS 

GENERAL 

Scope Section 680. 1 

Definitions 680.2 

WIRING METHODS FOR POOLS, SPAS, HOT TUBS AND HYDROMASSAGE BATHTUBS 

General . . 680.7, 680.23(B), 680.21(A), 680.23(F), 680.25(A), 680.40, 680.42, 680.43 and 680.70 

Flexible cords 680.7(A), (B), 680.22(B)(5), 680.42, and 680.43 Exception 

Double insulated pool pumps 680.21(B) 

EQUIPMENT LOCATION AND CLEARANCES 

Receptacle outlets 680.22(A)(6) 

Location 680.22(A)(1) 

Where required 680.22.(A)(3) 

Restricted space 680.22(A)(4) 

GFCI protection 680.22(A)(5) 

Indoor locations 680.43(A) and (A)(1) 

Indoor GFCI protection 680.43(A)(2) 

Switching devices 680.22(C), 680.43(C), 680.72 

Disconnecting means 680.12 

Luminaires and ceiling fans 680.22(B) 

Outdoor location 680.22(B)(1) 

Indoor location 680.22(B)(2) 

Existing lighting outlets and luminaires 680.22(B)(3) 

Indoor spas and hot tubs 680.43(B) 

GFCI protection in adjacent areas 680.22(B)(4) 

Overhead conductor clearances 680.8 

Overhead conductor clearances Table 680.8 

Overhead conductor clearances Figure 680.8 

Underground wiring 680. 10 

Underground wiring Table 680. 10 

BONDING 

Performance 680.26(A) 

Bonded parts 680.26(B), 680.26(E), 680.42(B) and 680.43(D)(4) 

Parts not required to be bonded 680.43(D)(4) Exception 

Methods of bonding 680.26(A), 680.26(C), 680.26(D), 680.42(B) and 680.43(E) 

GROUNDING 

Equipment to be grounded 680.6 

Luminaires and related equipment 680.23(F)(2), 680.24(F) 

Nonmetallic conduit 680.23(B)(2)(b) 

Flexible cords 680.23(B)(3) 

Motors 680.21(A)(1) 

Panelboards 680.25(B) and (B)(1) 

Separate Buildings 680.25(B)(2) 

Cord-connected equipment Section 680.7 

Other equipment 680.6 and Article 250 Parts V, VI, and VII 

EQUIPMENT INSTALLATION 

Transformers 680.23(A)(2) 

Ground-fault circuit-interrupters 680.5 

Wiring on load side of ground- fault circuit-interrupters and transformers 680.23(F)(3) 

Underwater luminaires 680.23(A)(1),(A)(3) and (A)(7) 



2006 INTERNATIONAL RESIDENTIAL CODE® 



653 



APPENDIX Q 



E4 106.4.1 

E4106.4.2 

E4106.5 

E4106.5.1 

E4106.6 

E4106.7 

E4106.8 

E4106.9 

E4106.9.1 

E4106.9.2 

E4106.9.3 

E4106.9.4 

E4106.9.5 

E4106.10 

E4106.10.1 

E4106.10.2 

E4106.10.3 

E4106.il 

E4106.12 

E4106.13 

E4106.13.1 

E4106.13.2 

E4106.13.3 

E4106.14 

SECTION E4107 

E4107.1 

E4107.2 

E4107.3 

E4107.3.1 

E4107.3.2 

E4107.4 

SECTION E4108 

E4108.1 
E4108.2 
E4108.3 
E4108.4 

SECTION E4109 

E4109.1 
E4109.2 
E4109.3 
E4109.4 

CHAPTER 42 

SECTION E4201 

E4201.1 
E4201.2 

SECTION E4202 

E4202.1 
E4202.2 

SECTION E4203 

E4203.1 



Maximum voltage 680.23(A)(4) 

Luminaire location 680.23(A)(5) and (A)(6) 

Wet-niche luminaires 680.23(B)(1), (B)(2), (B)(4) and (B)(5) 

Servicing 680.23(B)(6) 

Dry-niche luminaires 680.23(C)(1) and (C)(2) 

No-niche luminaires 680.23(D) 

Through- wall lighting assembly 680.23(E) 

Junction boxes and enclosures for transformers or 

ground-fault circuit interrupters 680.24(A) through (E) 

Junction boxes 680.24(A)(1) and (A)(2) 

Other enclosures 680.24(B)(1) and (2) 

Protection of junction boxes and enclosures 680.24(C) 

Grounding terminals 680.24(D) 

Strain relief 680.24(E) 

Underwater audio equipment 680.27(A) 

Speakers 680.27(A)(1) 

Wiring methods 680.27(A)(2) 

Forming shell and metal screen 680.27(A)(3) 

Electrically operated pool covers 680.27(B)(1) and (B)(2) 

Electric pool water heaters 680.9 

Pool area heating 680.27(C) 

Unit heaters 680.27(C)(1) 

Permanently wired radiant heaters 680.27(C)(2) 

Radiant heating cables prohibited 680.27(C)(3) 

Double insulated pool pumps Section 680.21(B) 

STORABLE SWIMMING POOLS 

Pumps 680.31 

Ground-fault circuit-interrupters required 680.32 

Luminaires 680.33 

Fifteen (15) volts or less 680.33(A) 

Not over 150 volts 680.33(B) 

Receptacle locations 680.34 

SPAS AND HOT TUBS 

Ground-fault circuit-interrupters 680.44(A) and (C) 

Electric water heaters 680.9 

Underwater audio equipment 680.43(G) 

Emergency switch for spas and hot tubs 680.41 

HYDROMASSAGE BATHTUBS 

Ground-fault circuit-interrupters 680.71 

Other electric equipment 680.72 

Accessibility 680.73 

Bonding 680.74 

CLASS 2 REMOTE CONTROL, SIGNALING, AND POWER-LIMITED CIRCUITS 

GENERAL 

Scope 725.1 

Definitions Article 100 and Section 725.2 

POWER SOURCES 

Power sources for Class 2 circuits 725.41(A) 

Interconnection of power sources 725.41(B) 

WIRING METHODS 

Wiring methods on supply side of Class 2 power source 725.51 



654 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



APPENDIX Q 



E4203.2 

Table E4203.2 

E4203.2.1 

E4203.2.2 

E4203.2.3 

E4203.2.4 

SECTION E4204 

E4204.1 
E4204.2 
E4204.3 
E4204.4 
E4204.5 



Wiring methods and materials on load side of the 

Class 2 power source 725.52, 725.61, 725.82, Table 725.61 

Cable uses and permitted substitutions 725.61 and Table 725.61 

Type CL2P cables 725.61(A) and 725.82(A) 

Type CL2 Cables 725.82(C) 

Type CL2X Cables 725.61(E)(4) and 725.82(D) 

Marking 725.82(L) 

INSTALLATION REQUIREMENTS 

Separation from other conductors 725.55(A), (B), (C), (D) 

Other applications 725.55(J) 

Class 2 circuits with communication circuits 725.56(D) 

Class 2 cables with other circuit cables 725.56(E)(1) through (5) 

Installation of conductors and cables 725.7, 725.8, 725.58, 300.11(B)(2) 



2006 INTERNATIONAL RESIDENTIAL CODE® 



655 



656 2006 INTERNATIONAL RESIDENTIAL CODE'' 



INDEX 



A 

ABSORPTION COOLING EQUIPMENT M1412 

ACCESS 

To appliances M1305 

To attic R807 

To crawl space R408.3 

To equipment M1401 .2 

To floor furnace M1408.4 

To plumbing connections P2704 

To plumbing fixtures P2705 

ACCESSIBLE 

Definition R202 

Readily accessible, definition R202, E3401 

ACCESSORY STRUCTURE 

Definition R202 

ADDRESS (Site) R321 

ADMINISTRATIVE Chapter 1 

Authority R104 

Entry R104.6 

Inspections R109 

Permits R105 

Purpose R101.3 

Violations R113 

AIR 

Combustion Chapter 17 

Combustion (from attic areas) M1 703.3 

Combustion (from under-floor areas) . . . M1 703.4 

Combustion air, definition R202 

Ducts M1703.2 

Indoor combustion M1702 

Outdoor combustion M1703 

Return M1602 

AIR CONDITIONERS 

Branch circuits E3602.1 1 

Room air conditioners E3602.12 

ALLOWABLE SPANS 

Of floor joists R502.3, R505.3.2 

Of headers R602.7, R603.6 

Of rafters and ceiling joists R802.4, R802.5, 

R804.3.1, R804.3.3 

ALTERNATE MATERIALS (see MATERIALS). . R104.1 1 

AMPACITY E3401 

ANCHOR BOLTS R403.1.6 

APPEAL 

Board of R112.1 

Right of R112 

APPLIANCE 

Access to M1 305 



Attic furnace M1 305. 1.3 

Clearance for M1306 

Connectors, fuel-gas Chapter 24 

Definition R202 

Definition applied to electrical 

equipment E3401 

Electrical appliance disconnection 

means E4001 .5 

Electrical appliance installation E4001 

Equipment (general) Chapter 14 

Floor furnace Ml 408 

Flue area R1003.14 

Fuel-burning Chapter 24 

Heating and cooling Chapter 14 

Installation M1307 

Labeling M1303 

Open-top broiler units Ml 505.1 

Ranges M1901 

Room heaters Ml 410 

Special fuel-burning equipment Chapter 19 

Vented (decorative) Chapter 24 

Wall furnace M1409 

Warm-air furnace Ml 402 

Water heaters Chapter 20, Chapter 24 

APPLICATION 

Plywood R703.3 

APPROVAL M1302 

APPROVED 

Definition R202 

Definition applied to electrical equipment . . E3401 

AREA 

Disposal, private sewage disposal P2602 

Flue (appliances) R1 003.1 4 

Flue masonry R1 003.1 5 

ARMORED CABLE Table E3701 .2 

ASPHALT SHINGLES R905.2 

ATTACHMENT PLUG (PLUG CAP) (CAP) 

Definition E3401 

ATTIC 

Access R807 

Combustion air Ml 703.3 

B 

BACKFILL 

For piping P2604 

BACKFLOW, DRAINAGE 

Definition R202 

BACKWATER VALVE R202 



2006 INTERNATIONAL RESIDENTIAL CODE*' 



657 



INDEX 



BALCONY, EXTERIOR 

Definition R202 

BASEMENT WALL 

Definition R202 

Insulation N1102.2.6 

BATH AND SHOWER SPACES R307 

BATHROOM E3401 

Exhaust M1507.3 

Group R202, Table P3004.1 

BATHTUB 

Enclosure P2713 

Hydromassage E4109 

Whirlpool R2720 

BEAM SUPPORTS R606.14 

BEARING 

Of joists R502.6 

BIDETS P2721 

BOILER 

Definition R202 

Requirements Chapter 20 

BONDING E3509, E4104 

Definition applied to 
electrical installations E3401 

BONDING JUMPER E3401 

Bonding of service equipment E3509.2 

Bonding to other systems E3509.3 

Main bonding jumper E3507.5 

Metal water piping bonding E3508.1 .1 

Sizing bonding jumpers E3509.5 

BORED HOLES (see NOTCHING) 

BOXES E3806 

Nonmetallic boxes E3805.3 

Support of boxes E3804.3 

Where required E3805.1 

BRANCH CIRCUIT E3401 , Chapter 36 

Branch circuit ampacity E3601 .2 

Branch circuit ratings E3602 

Branch circuits required E3603 

BUILDING 

Definition R202 

Drain, definition R202 

Existing, definition R202 

Sewer, definition R202 

BUILDING OFFICIAL 

Definition R202 

Inspection and tests of 
fuel-gas piping Chapter 24 

BUILDING PLANNING 

Ceiling height R305 

Decay protection R31 9 

Design criteria R301 



Dwelling unit separations R317 

Emergency escape R310 

Exterior wall location R302 

Finishes R31 5 

Foam plastic R314 

Garages and carports R309 

Glazing R308 

Guardrails R312 

Handrails R31 1 .5.6, R31 1 .6.3 

Insulation R31 6 

Landing R31 1.4.3, R311.5.4, R311.6.2 

Light, ventilation and heating R303 

Means of egress R31 1 

Minimum room area R304 

Planning Chapter 3 

Plumbing fixture clearances R307 

Ramps R311.6 

Radon protection Appendix F 

Sanitation R306 

Site address R321 

Smoke alarms R31 3 

Stairways R31 1 .5 

Termite protection R320 

Vapor retarders R31 8 

BUILDING THERMAL ENVELOPE 

Definition R202 

Requirements N1102 

BUILT-UP GIRDERS (see GIRDERS) 

BUILT-UP ROOFING (see ROOFING) 

c 

CABINETS AND PANELBOARDS E3807 

CAPACITY 

Expansion tank M2003.2 

CARPORT R309.4 

CEILING 

Finishes R805 

Height R305 

CEILING FANS E4103.4 

CENTRAL FURNACES (see FURNACES) 

CHASES R606.7 

CHIMNEYS 

And fireplaces Chapter 1 

Clearance R1003.18 

Corbeling R1003.5 

Crickets R1 003.20 

Design (masonry) R1 003.1 

Factory-built R1005 

Fireblocking R1003.19 

Flue area R1003.14, R1003.15 

Flue lining R1003.1 1 



658 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



INDEX 



Load R1003.8 

Masonry and factory built, size IVIISOS 

Multiple flue R1003.14 

Spark arrestors R1003.9.1 

Termination R1 003.9 

Wall thickness R1003.10 

CIRCUIT BREAKER 

Definition E3401 

CIRCUIT BREAKER RATING 

Class 2 remote-control, signaling and 
power-limited circuits Chapter 42 

CLAY 

Tiles R905.3 

CLEANOUT 

Definition R202 

Drainage P3005.2 

Masonry chimney R1 003.1 7 

CLEARANCE 

Above cooking top M1 901.1 

For appliances . M1306.1 

For chimneys R1001.15 

Reduction methods M1306.2 

Vent connector R1803.3.4 

CLEARANCES 

Around electrical equipment E3305.1, E3504.1, 

E3504.2, E3504.3 

CLOTHES CLOSETS 

Lighting fixtures E3903.1 1 

CLOTHES DRYERS Ml 502, Chapter 24 

CLOTHES WASHING MACHINES P2718 

COLUMNS R407 

COMBUSTIBLE 

Materials . . R202 

COMBUSTION AIR 

Air Chapter 17 

Attic M1703.3 

Definition R202 

Indoor M1702 

Outdoor M1703.1 

Supply M1701.1 

Under-floor M1703.4 

COMMON VENT 

Definition R202 

Requirements N1801.11 

CONCRETE 

Compressive Strength R402.2 

Floors (on ground) R506 

Tile (roof) R905.3 

Weathering Figure R301.2(3), R402.2 

CONCRETE-ENCASED ELECTRODE E3508.1.2 



CONDUCTOR E3306 

Ampacity E3605.1 

Definition E3401 

Identification E3307 

Insulation E3306.5 

Material E3306.2 

Parallel E3306.6 

Size E3306.3, E3604.1 

Ungrounded conductors E3503.1 

CONDUIT BODY 

Definition E3401 

CONNECTION 

Access to connections P2704 

For fuel-burning appliances Chapter 24 

For fuel-oil piping M2202 

Joints P2904 

Plumbing fixture P2601 .2 

To water supply P2902.1 

CONNECTIONS 

Aluminum E3306.8 

Device E3306.10.2 

CONNECTOR 

Chimney and vent M1803 

Vent, definition R202 

CONNECTOR, PRESSURE (SOLDERLESS) 

Definition E3401 

CONSTRUCTION 

Cavity wall masonry R606.4.2 

Flood-resistant R324 

Floors Chapter 5 

Footings R403 

Foundation walls R404 

Foundations Chapter 4 

Grouted masonry R609 

Masonry R606, R607, R608, R609, R610 

Material R402 

Reinforced hollow unit masonry R609.4 

Roofs Chapter 8 

Steel framing R505, R603, R804 

Wood framing R502, R602, R802 

Walls Chapter 6 

CONTINUOUS LOAD 

Definition E3401 

CONTINUOUS WASTE 

Definition R202 

CONTROL 

Devices Chapter 24 

CONTROLS 

For forced-air furnaces Chapter 24 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



659 



INDEX 



COOKING UNIT, COUNTER-MOUNTED 

Definition E3401 

COOLING 

Absorption cooling equipment M1 41 2 

Access to equipment I\/I1401 .2 

Evaporative cooling equipment M1413 

Installation M1401 .1 

Refrigeration cooling equipment M1404 

Return air-supply source M1602 

Screen inlet protection M1 602.3 

COPPER-CLAD ALUMINUM CONDUCTORS 

Definition E3401 

CORDS 

Flexible E4001 .3, E4102.2 

COURT 

Definition R202 

COVER REQUIREMENTS E3703.1 

COVERING 

Exterior R703 

Interior R702 

Roof Chapter 9 

Wall Chapter 7 

CRAWL SPACE R408, N1 102.2.8 

CRITERIA 

Design R301 

CROSS CONNECTION 

Definition R202 

D 

DAMPER, VOLUME 

Definition R202 

DECAY 

Protection against R31 9 

DECK 

Definition R202 

DECORATIVE APPLIANCES 

Vented Chapter 24 

DEFINITIONS 

Building R202 

Electrical E3401 

Mechanical System R202 

Plumbing R202 

DESIGN 

Criteria R301 

DIRECTIONAL 

Fittings, plumbing P2707 

DISCONNECTING MEANS 

Definition E3401 

Identification E3304.1 1 

DISHWASHING MACHINES P2717 



660 



DOORS 

Exit R311.4.1 

Glass R613 

DRAFT HOOD 

Definition R202 

DRAFTSTOPPING R502.12 

DRAIN 

Floor .P2719 

Shower receptors P2709 

DRAINAGE 

Cleanouts P3005.2 

Foundation R405 

Inspection and tests P2503 

DRILLING AND NOTCHING (see NOTCHING) 

DRIP LOOPS E3505.19.5 

DRYERS 

Domestic clothes M1502 

DUCTS Chapter 16 

Installation Ml 601 .3 

Insulation N1 103.2 

Material .M1601.1 

System, definition R202 

DWELLING 

Definition. . R202, E3401 

DWELLING UNIT 

Definition R202, E3401 

Separation R31 7 

E 

ELECTRICAL 

Appliance (labeling) Ml 303 

Inspection E3303 

ELECTRICAL METALLIC TUBING .... Table E3804.6 

ELECTRICAL NONMETALLIC 
TUBING Table E3701.4 

ELECTRICAL RESISTANCE HEATERS 

Baseboard convectors M1405 

Duct heaters M1407 

Radiant heating M1406 

ELECTRODES 

Grounding E3508 

EMERGENCY ESCAPE R202, R310 

ENERGY CONSERVATION Chapter 1 1 

ENCLOSURE 

Definition E3401 

ENTRY R104.6 

EQUIPMENT 

Definition applied to electrical equipment . . E3401 

General, mechanical Chapter 14 

Heating and cooling Chapter 14 

2006 INTERNATIONAL RESIDENTIAL CODE® 



INDEX 




EXCAVATIONS 

For appliance installation M 1305. 1.4.2 

EXTERIOR 

Covering R703 

Insulation finish systems R703.9 

Lath R703.6.1 

Plaster R703.6 

EXTERIOR WALL 

Definition R202 

Thermal performance N1 102 

F 

FACEPLATES E3901.11, E3902.4 

FACTORY BUILT 

Chimneys R1005, M1805 

Fireplace stoves R1 005.3 

Fireplaces R1004 

FASTENING Table R602.3(1) 

FAUCETS P2701 

FEEDER 

Ampacity E3604.5 

Conductor size E3604.1 

Feeder neutral load ....;. E3604.3 

Loads E3604.2 

Requirements E3604 

FENESTRATION 

Definition R202 

L/-factor and SHGC rating N1 101 .5 

L/-factor and SHGC requirements N1 102.3 

FINISHES 

Flame spread and smoke density R315 

For ceilings R805 

Interior R315, R702 

FIRE BLOCKING 

Barrier between stories R602.8 

Chimney R1003.19 

Fireplace R1001.12 

FIREPLACES Chapter 10 

Clearance R1001.11 

Corbeling R1 001 .8 

Factory-built R1004 

Fire blocking R1001.12 

Walls R1001.5 

FITTING 

Definition applied to electrical 
installations E3401 

FITTINGS 

DWV piping P3002.3 

Prohibited joints P3003.2 

Water supply P2904.6 

FIXTURE INSTALLATION E3904 



FIXTURE UNIT 

Drainage, definition R202 

Unit valves P2903.9.3 

Water supply, definition R202 

FIXTURES 

Clearances E3904.8 

Plumbing fixture, definition R202 

Plumbing fixture, general Chapter 27 

Trap seals . P3201 .2 

FLAME SPREAD R315 

FLASHING R703.7.5, R703.8, R903.2, R905 

FLEXIBLE CORDS E3809, E4001.3, E4102.2 

FLEXIBLE METAL CONDUIT .... E3701.4, E3808.8.1 
FLOOR FURNACE 

Access M1408.4 

Clearance M1408.2 

Definition R202 

General M1408.1 

Installation M1408.5 

Location M1408.3 

FLOORS 

Concrete (on ground) R506 

Steel framing R505 

Treated-wood (on ground) R504 

Wood framing R502 

FLUE 

Area R1003.14, R1003.15 

Lining R1003.11, R1003.12 

Multiple .R1003.13 

FOAM PLASTICS R314 

FOOD-WASTE GRINDERS P2716 

FOOTINGS R403 

FOUNDATIONS Chapter 4 

Cripple walls R602.10.2, R602.11.3 

Frost protection R403.1.4.1 

Inspection R109.1 .1 

Walls R404 

FRAME 

Inspection R109.1.4 

FREEZE PROTECTION OF PLUMBING P2603.6 

FUEL-BURNING APPLIANCES 
(see APPLIANCE, definition) 

Identification Chapter 24 

FUEL-GAS Chapter24 

FUEL-OIL 

Oil tanks M2201 

Piping, fittings and connections M2202 

Pumps and valves M2204 

FURNACES 

Clearance of warm-air furnaces M1402.2 

Exterior M1401 .4 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



661 



INDEX 



Floor (see FLOOR FURNACE) 
Wall (see WALL FURNACE) 

Warm-air M1402, Chapter 24 

FUSES E3605.6 



GARAGES R309 

GAS 

Appliance labeling Chapter 24 

GAS PIPING SYSTEM NOT TO BE 
USED AS GROUNDING ELECTRODE. . . Chapter 24 

GIRDERS R502.5 

GLAZING R308 

Aggregate R303.1 

Protection of openings R301 .2.1 .2 

GRADE 

Definition R202 

Of lumber R502.1, R602.1, R802.1 

Plane, definition R202 

Slope of piping, definition R202 

GROUND 

Definition of electrical E3401 

Floors (on ground) R504, R505, R506 

Joint connection P2904.8 

GROUND-FAULT CIRCUIT-INTERRUPTER 

PROTECTION E3802. E4103, E4106, 

E4107, E4108 

GROUND SOURCE HEAT PUMP M2105 

GROUNDED 

Definition E3401 

GROUNDED CONDUCTOR 

Definition E3401 

Identification E3307 

GROUNDED, EFFECTIVELY 

Definition E3401 

GROUNDING 

Effective grounding path E351 1 .3 

Of equipment E3808, E4105.1 

GROUNDING CONDUCTOR 

Definition E3401 

Equipment E3401, E3507.3.1, E3808 

GROUNDING ELECTRODE CONDUCTOR . . E3507.4 

Connection E3507.2, E351 1 

Definition E3401 

Size E3503.4 

GROUNDING ELECTRODE SYSTEM E3508 

GROUNDING ELECTRODES E3508, E3508.1 

Resistance of E3508 

GROUTED MASONRY (see MASONRY) R609 

Reinforced R609.3 



GUARDED 

Definition applied 

to electrical equipment E3401 

GUARDING OF ENERGIZED PARTS E3304.8 

GUARDS R312 

Definition R202 

GYPSUM 

Wallboard R702.3 

H 

HABITABLE SPACE 

Definition R202 

HALLWAYS R311.3 

HANDRAILS R311.5.6, R311.6.3 

Definition R202 

HEADERS 

Wood R602.7 

Steel R603.6 

HEARTH R1001.9 

Extension R1001.9, R1001.10 

HEATERS 

Baseboard M1405 

Central furnaces M1402 

Duct M1407 

Heat pumps M1403 

Masonry R1 002 

Pool M2006, Chapter 24 

Radiant M1406 

Sauna Chapter 24 

Unvented G2445 

Vented room M1410, Chapter 24 

Water Chapter 20 

HEATING R303.8 

HEATING EQUIPMENT Chapter 14 

HEIGHT 

Ceiling R305 

HOLLOW-UNIT MASONRY 
(see MASONRY) R608.1 .1 .2 

Reinforced R609.4 

HORIZONTAL 

Pipe, definition R202 

Vent length M1803.3.2 

HOT TUBS E41 01, Appendix G 

HOT WATER 

Definition R202 

Distribution pipe rating P2904.5 

Heaters M2005, Chapter 24 

Piping insulation Nil 03.4 

HYDROGEN GENERATING AND 
REFUELING M1307.4 



662 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



INDEX 



• 



HYDRONIC HEATING SYSTEMS 

Baseboard convectors M2102 

Boilers M2001 

Expansion tanks . . I\/I2003 

Floor heating systems M21 03 

Operating and safety controls M2002 

Piping systems installation M2101 

Water heaters . ( M2005 

I 
IDENTIFIED 

Definition applied to 
electrical equipment E3401 

INDIVIDUAL 

Branch circuit, definition E3401 

Sewage disposal systems R202, P2602 

Water supply and sewage 
disposal systems P2602 

INLET 

To masonry chimneys R1001.13 

INSPECTION 

Card AE305.3 

Excavation for piping P2604.1 

Fuel-supply system Chapter 24 

Of plumbing system P2503 

On site R109.1 

INSTALLATION 

Existing Appendix J 

Of appliances M1307 

Of cooling and heating equipment. M1401.1 

Of ducts M1601.3 

Of floor furnaces M1408.5 

Of flue liners R1 001 .9 

Of plumbing fixtures P2705 

Of wall furnaces M1409.3 

INSULATION R316 

R-value requirements Chapter 1 1 

INTERIOR 

Lath R702.2 

Other finishes R702.5 

Plaster R702.2 

Wall covering Chapter 7 

INTERMEDIATE METAL CONDUIT. . . . E3701, E3804 

INTERRUPTING RATING E3304.2 

Definition E3401 

J 

JOINTS, PIPE 

And connections P2904, P3003 

Slip P3003.3.7 



JOIST 

Bearing R502.6, R606.14.1 

JUMPERS 

Bonding E3509 

JUNCTION BOXES E3805, E41 06.8.1 

K 
KITCHEN 

Definition R202 

KITCHEN RECEPTACLES E3603.2, E3801 



L VENT TERMINATION M1804.2.4 

LABELED 

Definition R202 

Definition applied to 

electrical equipment E3401 

Fenestration N1101.5, N1 102.4.2 

LABELING 

Appliances M1 303 

Definition R202 

LAMPHOLDERS E3903, E3904 

LANDINGS R31 1 .4.3, R31 1 .5.4, R31 1 .6.2 

LATERAL SUPPORT R606.9, R61 0.5.2 

LATH 

Exterior R703.6.1 

Interior R702.2 

LAUNDRY CIRCUIT E3603.3 

LAUNDRY TUBS P2715 

LAVATORIES P2711 

Clearances R307 

Waste outlets P271 1 .3 

LEAD 

Bends and traps P3002.4.2 

Caulked joints P3003.6.1 

Flashing P3002.4.1 

LIABILITY R104.8 

LIGHT, VENTILATION AND HEATING R303 

LIGHTING 

Fixture installation E3904 

Fixtures in clothes closets E3903.1 1 

Fixtures (luminaries) E3903, E3904, E4106 

LIGHTING OUTLETS E3803 

Definition E3401 

Required lighting outlets E3803 

LINING 

Flue R1003.11, R1003.13 

LINTEL R606.10, R61 1.7.3, R703.7.3, R1001.7 

LIQUID-TIGHT FLEXIBLE 

CONDUIT E3701.4, E3808.8.2 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



663 



INDEX 



LISTED 

Definition applied 
to electrical equipment E3401 

LISTED and LISTING 

Definition applied to building and 

mechanical provisions R202 

Mechanical appliances M1 302.1 

LOAD 

Additional R1003.8 

Roof R301 .6 

Seismic risk map Figure R301.2(2) 

Snow load map Figure R301 .2(5) 

Wind speed map Figure R301.2(4) 

LOADS 

Branch circuit loads E3602, E3603.6 

Dead load R301.4 

Feeder load E3604.2 

Feeder neutral load E3604.3 

Horizontal load AE602.1 

Live load R301 .5 

Service load E3502.2 

LOADS, LIVE AND DEAD 

Definition R202 

LOCATION 

Of furnaces M1408.3, M1409.2 

LOCATION (DAMP) (DRY) (WET) 

Definitions E3401 

LUMBER 

Grade R502.1 , R602.1 , R802.1 

M 

MACERATING TOILET P2723 

MANUFACTURED HOME 

Definition R202 

Provisions Appendix E 

MASONRY 

Anchorage R606.1 1 

Attachment R703.4 

Cavity wall R606.4 

Chases R606.7 

General R606 

Grouted R609 

Hollow unit R202, R607.2.2.2, R608.1 .1 .2 

Inspection R109.1.4 

Reinforced grouted R609.3 

Reinforced hollow unit R609.4 

Seismic requirements R606.12 

Solid, definition R202 

Veneer R703.7 



MATERIALS 

Alternate . . .R104.11 

Combustible R202, R1003.18, R1003.19 

R1001,11,R1001.12 

For ducts M1601 

For fixture accessories P2702 

For flue liners R1003.1 1 

For fuel-supply systems Chapter 24 

For hearth extension R1001 .9 

For siding R703.3 

Hydronicpipe M2101, M2103, M2104 

Plumbing pipe P2904, P3002 

MECHANICAL 

Inspection R109.1.2 

System requirements Chapter 13 

Ventilation dampers N1 103.5 

MEDIUM PRESSURE FUEL-GAS 
PIPING SYSTEM Chapter 24 

MEMBRANE 

Penetration R31 7.3.2 

Polyethylene R504.2.2 

Water proofing R406.2 

Weather-resistant R703.2 

METAL ^^ 

Ducts .Chapter 16 ^f 

Roof panels R905.10 

Roof shingles R905.4 

METAL-CLAD CABLE Table E3701.2 

METHODS 

Water distribution pipe sizing Table P2903.7 

MODIFICATIONS R104.10 

MOISTURE CONTROL N1 102.5 

MORTAR 

Joints R607.2.1.1 

MOTORS 

Motor branch circuits E3602.6, E3602.7 

MULTIPLE 

Appliance venting systems Ml 801. 11 

Flues R1003.13 

MULTIWIRE BRANCH CIRCUITS E3601.4 

N 
NONCOMBUSTIBLE MATERIAL 

Definition R202 

NONMETALLIC BOXES E3805.3, E3808.16 

NONMETALLIC RIGID CONDUIT E3701.4 

NONMETALLIC-SHEATHED 

CABLE E3605.4.4, E3701 .4, 

E3805.3.1, E3808.8.3 



664 



2006 INTERNATIONAL RESIDENTIAL CODE'^ 



INDEX 



• 



NOTCHING 

Electrical E3302.1 

For plumbing piping P2603.2 

For mechanical systems. M1308 

Steel joists R505.3.5 

Steel studs R603.3.4 

Wood joists R502.8, R802.7.1 

Wood studs R602.6 

Wood top plates R602.6.1 

O 

OCCUPIED SPACE 

Definition R202 

OIL 

Piping and connections M2202 

Supply pumps and valves M2204 

Tanks M2201 

OPEN-TOP GAS BROILER UNITS M1505.1 

OPENING 

Requirements, combustion air M1 702.2, 

M1703.2.1 

Waterproofing of piping penetrations. . . . P2606.1 
OUTLET 

Definition Chapter 24, E3401 

OVEN, WALL-MOUNTED 

Definition applied to 

electrical provisions E3401 

OVERCURRENT 

Definition E3401 

OVERCURRENT PROTECTION E3605 

OVERCURRENT-PROTECTION RATING .... E3605.6 

OVERLOAD 

Definition E3401 

P 

PARAPETS R31 7.2.2, R606.2.4 

PANELBOARD 

Definition E3401 

PANELBOARDS E3606 

Clearance and dedicated space E3305.2, 

E3305.3 

Headroom E3305.7 

PARTICLEBOARD 

Floor R503.3 

Walls . .R605 

PERMITS R105 

PIERS R606.6 

PJPE 

Insulation N1103.3, N1 103.4 

Materials listing Table M2101.1, P2608 



Protection P2603 

Standards, drain, 

waste and vent Table P3002.1(1), 

P3002.1(2) 

Standards, sewer Table P3002.2 

Standards, water supply P2904 

PIPING 

Connections and materials . . Table M2101 .1 , P2904 

Drain, waste and vent P3002.1 

Fuel-gas size determination Chapter 24 

Protection P2603 

Sizing methods, water distribution P2903 

Support M2101 .9, Chapter 24, P2605 

PLANNING 

Building Chapter 3 

PLANS R106 

PLASTER 

Exterior R703.6 

Interior R702.2 

PLENUM 

Definition R202 

Definition, electrical installations E3401 

PLUMBING 

Fixture clearances R307 

Fixtures Chapter 27 

Inspection R109.1.2 

Materials P2702.2, P2904, P3002 

Requirements and definitions R202 

System, definition R202 

Traps Chapter 32 

Vents Chapter 31 

PLYWOOD 

Application R703.3 

Materials, walls R604 

POTABLE WATER 

Definition R202 

PRESSURE, WATER SUPPLY 

Maximum P2903.3.1 

Minimum P2903.3 

PRIVATE 

Sewage disposal system Appendix I 

PROHIBITED 

Receptors P2706.3 

Return air sources Ml 602.2 

Traps P3201.5 

Water closets P2712.1 

PROTECTION 

Against decay and termites R319, R320 

Against radon Appendix F 

Of ferrous gas piping Chapter 24 

Of potable water supply P2902 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



665 



INDEX 



PURLINS R802.5.1 

PURPOSE R101.3 



H-VALUE 

Computation N1102.1.1 

Definition R202 

RACEWAY 

Definition E3401 

Raceway installations E3804 

Raceway seals E3501 .5, E3703.6 

Raceways as means of support E3804.4 

RADON 

Map Appendix F 

RAFTERS 

Grade of lumber R802.1 

Spans R802.5, Tables R802.5.1(1)— 

R802.5.1(8) 

RAINPROOF 

Definition applied to 
electrical provisions E3401 

RAINTIGHT 

Definition applied to 
electrical provisions E3401 

RAMPS R311.6 

RANGES 

Branch circuits for ranges E3602.9 

RANGES AND OVENS 

Vertical clearance above cooking top . . . M1 901.1 

READILY ACCESSIBLE 

Definition R202 

Definition, electrical installations E3401 

RECEPTACLE 

Definition E3401 

RECEPTACLE OUTLET 

Definition E3401 

Required outlets E3801 

RECEPTACLES 

Rating, type and installation E3902 

RECEPTORS 

Plumbing fixtures and traps Chapter 27 

Shower receptor materials P2709.3.1 

Waste P2706 

RECESSED LUMINAIRES E3903.5, E3903.11, 

E3904.8, E3904.9, 

Sealed N1102.4.3 

REQUIREMENTS 

Connections for fuel-burning 

appliances Chapter 24 

Return air M1602.1 



RESISTANCE TO GROUND 

Electrodes E3508.4 

RESISTANT SIDING MATERIAL (see MATERIALS) 

RETURN-AIR LIMITATION Ml 602.2 

RIDGE BOARD R802.3 

RIGID METALLIC CONDUIT E3808 

RIGID NONMETALLIC CONDUIT E3701.4 

ROOF 

Coverings R905 

Drainage R903.4 

Flashing R703.8, R903.2, R905 

Steel framing R804 

Wood framing R802 

ROOF-CEILING CONSTRUCTION 

(see CONSTRUCTION) Chapter 8 

Insulation Nil 02.2 

Wind uplift R802.11 

ROOFING 

Built-up R905.9 

Liquid-applied coating R905.15 

Modified bitumen R905.1 1 

Sprayed polyurethane foam R905.14 

Thermoplastic single-ply R905.13 

Thermoset single-ply R905.12 

ROOM 

Heaters, vented Ml 410 

Minimum Sizes R304 

s 

SANITATION R306 

SEISMIC RISK MAP Figure R301.2(2) 

SEPTIC TANK 

Definition R202 

SERVICE 

Definition E3401 

SERVICE CABLE 

Definition E3401 

SERVICE CONDUCTORS 

Definition E3401 

Drip loops E3505.19.5 

Insulation E3505.1 

Overload protection E3503.3 

Rating of ungrounded service 

conductors E3502.1 

Size E3503.1 

SERVICE DISCONNECT 

Location E3501 .6.2 

Marking of E3501 .6.1 

Maximum number of E3501 .7 

Rating of E3502.3 



• 



666 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



INDEX 



• 



• 



• 



Required E3501 .6 

SERVICE DROP 

Clearances E3504.1 , E3504.2 

Definition E3401 

Point of attachment E3504.3 

SERVICE-ENTRANCE CONDUCTORS, 
OVERHEAD SYSTEM 

Definition E3401 

SERVICE-ENTRANCE CONDUCTORS, 
UNDERGOUND SYSTEM 

Definition E3401 

SERVICE EQUIPMENT 

Definition E3401 

SERVICE LATERAL 

Definition E3401 

SERVICE LOAD E3502.2 

SERVICE POINT 

Definition E3401 

SERVICE VOLTAGE RATING E3502.4 

SERVICES Chapter 35 

SEWAGE 

Disposal, private P2602 

SEWER, BUILDING 

Definition R202 

Size P3005.4.2 

Testing P2503.4 

SHAKES 

Wood R702.6, R703.5, R905.8 

SHINGLE 

Asphalt shingles R905.2 

Metal R905.4 

Slate R905.6 

Wood R905.7 

SHOWER 

Compartment R307.2 

Receptor P2709 

Stall dimensions P2708 

Walls P2710 

SHUTOFF VALVE (see VALVES) 

SIDING 

Exterior coverings R703 

SINKS P2714 

SITE 

Address R321 

Preparation R504.2, R506.2 

SIZE 

Of combustion air openings Chapter 17 

Of rooms R304 

Of trap P3201 .7 



SIZING METHODS 

Water piping P2903.7 

SKYLIGHTS R308.6, N1 102.3.5, N1 102.4.1 

SLATE SHINGLES R905.6 

SMOKE DENSITY R315 

SMOKE ALARMS R313 

SNOW LOAD MAP R301.2(5) 

SOLAR HEAT GAIN 

COEFFICIENT (SHGC) N1101.5, 

N1101.8, N1102.3 

SOLAR ENERGY SYSTEMS M2301 

SPANS 

Steel (allowable) R505.3.2, R804.3.3 

Wood (allowable) R502.3, R802.5 

SPAS E4108 

SPLICES E3306.10 

SPLICES AND TAPS E3703.4 

STACK BOND R606.7 

STAIRWAYS R311.5 

STANDARDS Chapter 43, Appendix G 

STEEL 

Fireplace units R1 001 .5.1 

Floor construction R505 

Roof-ceiling construction R804 

Walls R603 

STORY 

Definition R202 

STOVES 

Factory-built fireplace Ml 41 4 

STRUCTURAL AND PIPING PROTECTION . . . P2603 
STUDS 

Wood R602.2, R602.3 

Spacing R602.3.1 

Steel R603.2, R603.3 

SUPPLY 

Combustion air Chapter 17 

Fuel systems Chapter 24 

Oil supply pumps and valves M2204 

Required gas Chapter 24 

Return air M1602 

Water Chapter 29 

SUPPORT 

Of ducts M1601.3.2 

Of joists R502.6 

Of masonry chimneys R1 001 .3.1 

Of pipe M2101.9, Chapter 24, P2605 

SUPPORT REQUIREMENTS FOR WIRING 

METHODS E3702.1 

SWIMMING POOLS Chapter 41 , Appendix G 



2006 INTERNATIONAL RESIDENTIAL CODE'' 



667 



INDEX 



SWITCHES 

Definition E3401 

Rating and application E3901 

SYSTEMS 

IVIechanical venting Chapter 18, Ciiapter 24 

Plumbing, drainage, waste 
and venting Chapters 25, 30 and 31 

T 

TAIL PIECES P2703 

TANK 

For fuel oil-burning appliances M2201 

Septic, definition R202 

TEMPERATURE ISOLINES Figure R301.2{1) 

TEMPERATURE LIMITATIONS E3605.4 

TERMINALS E3306.9 

TERMINATION 

Of chimneys R1 001 .9 

Of vents (general) M1804.2 

TERMITES 

Infestation probability map Figure R301.2(6) 

TEST 

For leaks in supply piping Chapter 24 

Of building sewers P2503.4 

Of plumbing systems P2503 

THERMAL ISOLATION R202, N1 102.2.10, 

N1 102.3.3 

THICKNESS 

Of chimney walls R1001.10 

TIES 

Veneer R703.7.4.1 

TILE 

Shingles (clay and concrete) R905.3 

TOWNHOUSE 

Definition R202 

Scope .R101.2 

Separation R317.2 

TRACK LIGHTING E3905 

TRAP Chapter 32 

Arm, definition R202 

TRUSSES 

Steel R804.1.3 

Wood R502.11, R802.10 

TYPE OF VENTING SYSTEMS 
REQUIRED Chapter 18, Chapter 24 

U 

(/-FACTOR 

Alternative N1 102.1 .2 

Definition R202 



UNDER FLOOR 

Access to furnaces Ml 305.1 .4 

Combustion air M1 703.4 

Plenums M1601.4 

Space R408 

UNDERGROUND INSTALLATION 
REQUIREMENTS 

Duct systems M1601 .1 .2 

Electrical cable E3703 

Wiring E4103.6 

UTILIZATION EQUIPMENT 

Definition E3401 

V 

VALVES 

Backwater P3008 

Meter Chapter 24 

Oil-supply M2204 

Relief, water heater P2803 

Shutoff, fuel-gas Chapter 24 

Shutoff, fuel oil M2204.2 

Water heaters P2903.9.2 

Water supply P2903.9 

VAPOR RETARDERS R318, N1 102.2.8, N1 102.5 

Definition R202 

VENEER 

Masonry R703.7 

VENT 

B or BW vent Chapter 24 

Definition Chapter 24 

L vent M1804.2.4, Chapter 24 

Plumbing system, definition R202 

Termination Ml 804.2, M2203.5, P3103.3 

VENTED 

Decorative appliances Chapter 24 

Floor furnaces Ml 408 

Room heaters M1410 

Wall furnaces M1409 

VENTILATION 

Bathroom and kitchen M1507 

For hydrogen systems Ml 307.4 

Roof R806 

Under floor R408.1 

VENTING (Mechanical) 

Chimney and vent connectors Ml 803 

Components Ml 802 

General M1801 

Required M1801, M2203.4 

Systems Chapter 1 8 



• 



• 



• 



668 



2006 INTERNATIONAL RESIDENTIAL CODE^ 



INDEX 



• 



# 



VENTING (Plumbing) 

Air admittance valves P3114 

Circuit P3110 

Combination waste and vent system P31 11 

Common P3107 

Connections and grades P3104 

Fixture P3105 

Individual P3106 

Island fixture P31 12 

Pipe sizing P31 13 

Stacks and stack vents P3102 

Systems P3101 

Terminals P3103 

Waste stack P3109 

Wet P3108 

VERTICAL 

Clearances above cooking top M1901.1 

Pipe, definition R202 

VIOLATIONS 

And penalties R1 13 

VOLTAGE 

Definition E3401 

VOLTAGE RATING (Services) E3502.4 

VOLTAGE TO GROUND 

Definition E3401 

VOLTAGES E3304.1 

W 
WALL FURNACE (see APPLIANCE) 

General M1409.1 

Installation M1409.3 

Location M1409.2 

WALLBOARD 

Gypsum R702.3 

WALLS 

Steel framing R603 

Bracing, steel R603.3.3 

Bracing, wood R602.10 

Construction Chapter 6 

Covering Chapter 7 

Cripple R602.9 

Deflection R301 .7 

Exterior covering R703 

Finishes R315, R702 

Fireplace R1003.5 

Foundation R404 

Insulating concrete form R61 1 

Mass N1 102.2.3 

Steel framing R603 

Thickness, masonry chimneys R1 003.10 



Wood framing R602 

WARM-AIR FURNACES M1402 

Access to M1401 .2 

Clearance from M1402.2 

WASTE 

Continuous, definition R202 

WATER 

Distribution system, definition R202 

Heater, definition R202 

Heaters Chapters 20, 24 and 28 

Individual supply and sewage disposal. . . . P2602 

Piping sizing methods P2903 

Supply and distribution Chapter 29 

Supply system, definition R202 

WATER CLOSET R306.1 

WATERPROOFING 

And dampproofing R406 

Of openings through roofs and walls P2606 

WATERTIGHT 

Definition applied to 
electrical provisions E3401 

WEATHERPROOF 

Definition applied to 
electrical provisions E3401 

WHIRLPOOL BATHTUBS P2720 

WIND SPEED MAP Figure R301 .2(4) 

WINDOW.. R613 

WIRING METHODS Chapter 37 

WOOD 

Floor construction R502 

Foundation walls R404.2 

Roof-ceiling construction R802 

Shakes R905.8 

Shingles R905.7 

Trusses R502.11, R802.10 

Walls R602 

WORKING SPACE E3506.2 

Around electrical equipment. . . E3305.1, E3305.2 

WORKMANSHIP, PLUMBING P2607 



YARD 



Definition R202 



2006 INTERNATIONAL RESIDENTIAL CODE*" 



669 



• 



# 



• 



670 2006 INTERNATIONAL RESIDENTIAL CODE'' 



Savings. Services. Success. 




ooe Loyncii 



®. 



^n 



Your career deserves 
the added prestige that 
comes with membership in 
the International 
Code Council The 
International Code 
Council offers complete 
support for building 
safety and fire prevention 
professionals. Sign up 
today to begin enjoying 
hese exclusive benefits. 



FREE code opinions for ALL International Code Council 
(ICC®) members 

Substantial discounts on l-Codes®, code commentaries, 
supplements, updates, referenced standards and other 
publications; in-person, online and telephone seminars; 
and technical services including plan review 



FREE code book with new membership (Save up to $100)* 

Subscription to Building Safety Journor" (ICC's magazine). 
Building Safety Bulletin (ICC's newsletter), and eNews 
(ICC's electronic newsletter) included in mem.ber dues 

FREE job postings in the members-only area of the ICC Web site 

FREE (upon request) monographs and other publications 
regarding proposed revisions to the !-Codes 

National representation in organizations involving standards 
development, code administration and code enforcement matters 

Voting privileges for preliminary hearings on proposed changes 
to any of the !-Codes** 

Access to the member-only area of the International Code 
Council Web site www./ccsofe.org. This area contains o 
seorchable membership directory, an order area showing 
member discount pricing, and other valuable services 
available only to International Code Council members 

An International Code Council membership card, wall 
certificate and international Code Council logo decals to 
identify your commitment to the community and to the safety 
of people worldwide 

*A new member has nof had an acfive membership with ICC, BOCA, 
ICBO or SBCCI wifhin the last five years. 

**Contact your Member Services Representative for details on 
voting privileges. 



€d 



C3(o)(0)(0)'=l\ 



wo§oO wmmic 



y(§(§§(o]feo®[fgj/( 






'4] @F 




ifcmipik" Sk'llpkm, IPimpit 




Please refer to Tracking Number 
66-05-274 when applying. 



INTERNATIONAL 
CODE COUNCIL® 

People Helping People 
Build a Safer World™ 



Membership Application 

This form may be photocopied 

MEMBERSHIP CATEGORIES AND DUES*— ANNUAL MEMBERSHIP 

Special membership structures are also available for Educational Insfifufions and Federal Agencies. 

For more information, please visit www.iccsafe.org/membership or call 1-888-ICC-SAFE (422-7233), x33804. 

GOVERNMENTAL MEMBER** 

Government/Municipality (including agencies, departments or units) engaged in administration, formulation or 
enforcement of laws, regulations or ordinances relating to public health, safety and welfare. Annual member dues 
(by population) are shown below. Please verify the current ICC membership status of your employer prior to applying. 



D Up to 50,000 $100 



050,001-150,000 $180 0150,001+ $280 



**A Governmental Member may designate 4 to 12 voting representatives (based on population) who are employees or officials of that 
governmental member and are actively engaged on a full- or part-time basis in the administration, formulation or enforcement of laws, 
regulations or ordinances relating to public health, safety and welfare. Number of representatives is based on population. All dues for 
representatives have been included in the annual member dues payment. Please call 1-888-ICC-SAFE (422-7233), x33804 for 
information about how to designate your voting representatives. 

U CORPORATE MEMBERS ($300) An association, society, testing laboratory, manufacturer, company or corporation 



INDIVIDUAL MEMBERS 
D PROFESSIONAL ($150) 
D COOPERATING ($150) 

D CERTIFIED ($75) 
D ASSOCIATE ($35) 
D STUDENT ($25) 

D RETIRED ($20) 



A design professional duly licensed or registered by any state or other recognized governmental agency 

An individual who is interested in International Code Council purposes and objectives and would 
like to take advantage of membership benefits 

An individual who holds a current Legacy or International Code Council certification 

An employee of a current ICC Governmental Member 

An individual who is enrolled in classes or a course of study including at least 12 hours of 
classroom instruction per week 

A former governmental representative, corporate or individual member who has retired 



New Governmental and Corporate Members will receive a free package of 7 code books. New Individual Members will receive one free code book. Upon 
receipt of your completed application and payment, you will be contacted by an ICC Member Services Representative regarding your free code 
package or code book. For more information, please visit www.iccsafe.org/membership or call 1-888-iCC-SAFE (422-7233), x33804. 

Please print clearly or type information below: 



Name ^^H 


Name of Jurisdiction, Association, Institute or Company, etc. 


Title 


Billing Address 


City State 


Zip-l-4 


Street Address for Shipping 


City State 


Zip-l-4 


E-mail 


Telephone 


Tax Exempt Number (If applicable, must attach copy of tax exempt license if claiming an exemption) 
Payment Information: 



VISA, MC, AMEX or DISCOVER Account Number 

Return this application to: 
International Code Council 

Attn: Membership 

5360 Workman Mill Road 
Whittier,CA 90601 -2298 



Exp. Date 

Toll Free: 1-888-ICC-SAFE (1-888-422-7233), x33804 

FAX: (562) 692-6031 (Los Angeles District Office) 

Or, apply online at wv/w.iccsafe.org/membership. 

Please refer to Tracking Number 66-05-274 when applying. 



If you have any questions about membership in the International Code Council, 
call 1-888-ICC-SAFE (1-888-422-7233), x33804 and request a Member Services Representative. 



REP 66-05-274 



*Membership categories and dues subject to change. 
Please visit www.iccsafe.org/membership for the most current information. 



2006 International Residential Code Errata 



FIRST PRINTING (Updated September 12, 2006) 



CHAPTER 1 
ADMINISTRATION 

R 109. 1.5.2 Reinforced masonry, insulating concrete form (ICF) and conventionally formed concrete wall inspection. 

R e inforc e d masonry walls, insulating concr e t e form (ICF) walls and conv e ntionally form e d concr e t e walls locat e d in S e ismic D e sign 
Cat e gori e s DO, Dl, D2 and E shall b e insp e ct e d aft e r th e plumbing, m e chanical and e l e ctric syst e ms e mb e dd e d wittiin tti e walls, and 
r e inforcing st ee l ar e in plac e and prior to th e plac e m e nt of grout or concr e t e . Insp e ction shall v e rify th e corr e ct siz e , location, spacing, 
and lapping of r e inforcing. For masonry walls, insp e ction shall also v e rify that th e location of grout cl e anouts and siz e of grout 
spac e s comply with th e r e quir e m e nts of this cod e . (Posted 9-12-06) 



2006 International Residential Code Errata Page 1 of 6 



FIRST PRIISTTING (Updated J uly 25, 2007) 



CHAPTERS 
BUILDING PLANNING 

R301.2.1.2 Protection of openings. (No change to charging statement) 

Exception: Wood structural panels with a minimum of 7/16 inch (11 mm) and a maximum span of 8 feet (2438 mm) shall 
be permitted for opening protection in one- and two- story buildings. Panels shall be precut so that they shall be attached to 
the framing surrounding tiie opening containing the product with the glazed opening. Panels shall be secured with the 
attachment hardware provided. Attachments shall be designed to resist the component and cladding loads determined in 
accordance with eifeer Table R301.2(2) or S e ction 1609.6.5 of th e Int e rnational Building Cod e . 
(Remainder of exception unchanged, Posted 7-25-07) 

R301.2.2.1.1 Alternate determination of seismic design category. The Seismic Design Categories and corresponding Short Period 
Design Categories and corresponding Short Period Design Spectral Response Accelerations, S^g shown in Figure R301. 2(2) are based 

on soil Site Class D, as defined in S e ction 1615.1.1 Section 1613.5.2 of the International Building Code. If soil conditions are other 
than Site class D, the Short Period Design Spectral Response A ccel oration, Sj) g for a site can be determined according to Section 

1615.1 Section 1613.5 of the International Building Code. The value of Sq g determined according to S e ction 1615.1 Section 1613.5 

of the International Building Code is permitted... 
(Remainder of section unchanged, posted 7-25-07) 

Table R302.1 Exterior Walls 



Exterior Wall Element 


Minimum 
Fire-resistance rating 


Minimum Fire Separation 
Distance 


Projections 


(Fire-resistance rated) 


1 hour on the underside 


4.2 feet 


(Not fire-resistance rated) 


liours 


5 feet 



(Remainder of the Table is unchanged, posted 9-12-06) 



R314.3 Surface burning characteristics. ... shall have a flame- spread index of not more than 75 and shall have a smoke- developed 
index or not more than 450 when tested in the maximum thickness of 4 inch e s, provid e d th e e nd us e is approv e d in accordanc e with 
S e ction R314.6 using th e thickn e ss and d e nsity int e nd e d for us e intended for use in accordance with ASTM E84. Loose- fill type 
foam plastic insulation shall be tested as board stock for the flame spread index and smoke- developed index. 
(Exception unchanged, posted 9-12-06) 

R314.7 Termite damage. The use of foam plastics in areas o f "very heavy" termite infestation probability shall be in accordance 
with Section R320.4 R320.5 . 
(Posted 7-25-07) 

R324.1.7 Flood-resistant materials. (No change to charging statement and item #1) 

2. Materials and installation methods used for flooring and interior and exterior walls and wall coverings shall conform to 
the provisions of FEMA/FIA-TB:2. 
(Posted 7-25-07) 

R324.2 Flood hazard areas (including A Zones). ... All buildings and structures constructed in whole or in part in flood hazard 
areas shall be designed and constructed in accordance with Sections R324.2.1 and through R324.2.3. 

(Posted 7-25-07) 
R324.3 Coastal high-hazard areas (including V Zones) ... Buildings and structures constructed in whole or in part in coastal high- 
hazard areas shall be d e signat e d designed and constructed in accordance with Sections R324.3.1 through R324.3.6. 

(Posted 7-25-07) 



2006 International Residential Code Errata 



Page 1 of 1 



FIRST PRINTING (Updated September 12, 2006) 



CHAPTERS 
FLOORS 

Table R503.2.1(l) 

ALLOWABLE SPANS AND LOADS FOR WOOD STRUCTURAL PANELS FOR ROOF AND SUBFLOOR 

SHEATHING AND COMBINATION SUBFLOOR UNDERLAY MENT 



SPAN RATING 


ALLOWABLE LIVE LOAD 


(Remainder of Table unchanged) 


SPAN 
@ 16" o.c. 


SPAN 
@ 24" o.c. 


4(^20 


305 


30130 



(Posted 9-12-06) 



2006 International Residential Code Errata 



Page 3 of 6 



FIRST PRINTING (Updated September 12, 2006) 



CHAPTER 6 

WALL CONSTRUCTION 



Table R602.10.1 
WALL BRACING 



SEISMIC DESIGN CATEGORY OR 
WIND SPEED 



CONDITION 



TYPE OF BRACE 



AMOUNTOF BRACING 



Category C (S^ < 0.6g and S^^^ < 
0.50g) or less than 110 mph 



One story 
Top of two or three story 



Method 1,2, 3, 4, 5, 6, 7 or 8 



Locat e d i n accordanc e w i th S e ct i on 
R602.10 and at le ast e v e ry 25 f ee t 
on c e nt e r but not le ss than 30% of 
brac e d wa ll li n e for M e thod 3 or 
45% of brac e d wa ll li n e for M e thods 
2,-1, 5, 6, 7 or 8. 

Located in accordance with Section 
R602.10 and at least every 25 feet 
on center but not less than 16% of 
braced wall line for Method 3 or 
25% of braced wall line for Methods 
2, 4, 5, 6, 7 or 8. 



First story of two story 
Second story of three story 



Method2,3, 4, 5, 6, 7or8 



Locat e d i n accordanc e w i th S e ct i on 
R602.10 and at le ast e v e ry 25 f ee t 
on c e nt e r but not le ss than 16% of 
brac e d wa ll li n e for M e thod 3 or 
25% of brac e d wa ll li n e for M e thods 
2, -1 ,5, 6, 7 or 8. 

Located in accordance with Section 
R602.10 and at least every 25 feet 
on center but not less than 30% of 
braced wall line for Method 3 or 
45% of braced wall line for Methods 
2, 4, 5, 6, 7 or 8. 



(Remainder of the Table is unchanged, posted 9-12-06) 



2006 International Residential Code Errata 



Page 4 of 6 



FIRST PRINTING (Updated September 12, 2006) 



CHAPTER 9 

ROOF ASSEMBLIES 

R905.4.3 Underlayment. Underlayment shall comply with ASTM D 226 , Typel orASTM D 4869, Type I or II. 
R905.5.3 Underlayment. Underlayment shall comply with ASTM D 226 , Typel orASTM D 4869, Typel or II. 
R905.6.3 Underlayment. Underlayment shall comply with ASTM D 226 , Typel orASTM D 4869, Typel or II. 
R905.7.3 Underlayment. Underlayment shall comply with ASTM D 226 , Typel orASTM D 4869, Typel or II. 
R905.8.3 Underlayment. Underlayment shall comply with ASTM D 226 , Typel orASTM D 4869, Typel or II. 
(Posted 9-12-06) 



2006 International Residential Code Errata Page 5 of 6 



2006 Inbeniational Residential Code- Ch^)ber24 Errata 



Note that these errata are based on the first printing of the code and may have been 
corrected in later printings. 

CHAPTER 24 

1) In Table G2453.1, the last entry in the 6 foot chimney height row (first entry in 64 sq. inch column) should read 
80,000 instead of 8,000. 

2) The metric conversions in Sections G2428.3.4 and G2428.3.5 should be (18mm per mm) instead of (457mm per 
mm). 

3) Add the following sentence to the end of the exception to Section G 2420.5; "Piping from the shutoff valve to within 
3 feet (914mm) of the appliance connection shall be sized in accordance with Section G2413." 

4) Add the following sentence to the end of Section G2439.5.1; 'The maximum length of the exhaust duct does not 
include the transition duct." 

5) Section G2427.7.12 should reference Section G2427.6.10 instead of G2427.6.11. 

6) Delete Section G2427.6.3 and renumber subsequent sections G2427.6.4 through G2427.6.11 and Figure 
G2427.6.4 accordingly. 

7) Section G2427.10.2 should reference Sections G2427.10.2.1 through G2427.10.4. 

8) Delete the exception in Sections G2428.2.9 and G2428.3.16. 

9) Delete the definition of "CONNECTOR" in Section G2403. 

10) Section G2451.2 should read; "Infrared radiant heaters shall be fixed in a position independent of gas and electric 
supply lines. Hangers and brackets shall be of noncombustible material." 

(Posted: January 3, 2008) 



2006 International Residential Code - C hapter 24 E trata Page 1 of 1 



FIRST PRINTING (Updated September 12, 2006) 



CHAPTER 43 
REFERENCED STANDARDS 



AW PA 



American Wood- Preservers' Association 
P.O. Box 5690 
Granbuiy, Texas 76049 



Standard 

Reference 

Number 



Title 



Referenced 
in code 
section number 



Cl-00 



All Timber Products - Preservative Treatment by Pressure Processes R902.2 



(Remainder of the Section is unchanged, posted 9-12-06) 



2006 International Residential Code Errata 



Page 6 of 6