24.301.301 INCORPORATION BY REFERENCE OF UNIFORM PLUMBING CODE
(1) The Department of Labor and Industry adopts and incorporates by reference the
Uniform Plumbing Code, 2006 edition, referred to as the Uniform Plumbing Code, unless
another edition is specifically stated, together with the following appendix chapters and
amendments:
(a) Appendix A, Recommended Rules for Sizing the Water Supply System is adopted.
(b) Appendix B, Explanatory Notes on Combination Waste and Vent Systems is
adopted.
(c) Appendix D, Sizing Stormwater Drainage Systems is adopted.
(d) Subsection 103.1.3, is amended with the addition of the following language: The
requirements for who must be licensed to perform plumbing work is regulated by Title 37,
chapter 69, MCA.
(e) Subsections 102.3, 103.1, 103.2, 103.3, 103.4, 103.5, and 103.6 will be left as is for
use by local governments (i.e., municipalities and counties) but will not be used by the
department and the state of Montana. For the purposes of enforcement by the department,
these subsections are replaced with provisions of Title 50, chapter 60, part 5, MCA.
(i) No permit is required for any minor replacement or repair work, the performance of
which does not have a significant potential for creating a condition hazardous to public
health and safety.
(ii) No permit is required where the installation is exempt under the provisions of
50-60-503 or 50-60-506 , MCA.
(iii) The requirements for permits do not apply to regularly employed maintenance
personnel doing maintenance work on the business premises of their employer unless
work is subject to the permit provisions of these rules.
(iv) Factory-built buildings covered by an insignia issued by the department need not
have a plumbing permit for the construction of the unit; however, a permit will still be
required for on-site work, as provided for in these rules.
(f) Delete Table No. 1 .1 - PLUMBING PERMIT FEES and replace with the following
schedule:
(i) for issuing each permit $20*
(ii) for each plumbing fixture 7
(iii) water service - domestic or commercial 7
(iv) for each building sewer and each trailer park sewer 11
(v) storm drains and storm drainage 7
(vi) for each water heater 7
(vii) for each industrial water pretreatment interceptor,
including its tray and vent, excepting kitchen type grease
interceptors functioning as fixture traps 7
(viii) for installation, alteration, or repair of water piping
and/or water treatment equipment 7
(ix) for repair or alteration of drainage or vent piping 7
(x) for each lawn sprinkler system and fire protection
system or any one meter, including backflow protection devices therefore 7
(xi) for vacuum breakers or backflow protective devices
on tanks, vats, etc., or for installation on unprotected plumbing
fixtures, including necessary water piping
(A) one to four 7
(B) five or more, each 2
(xii) requested plumbing inspection fee
(provided that such service is not in excess of one hour in duration.
and then $25 for each 30 minutes or fractional part thereof
in excess of one hour. Travel and per diem will be charged
as per the state of Montana's existing rate for these items) 45
(xiii) reinspection (provided the $30 does not exceed the
original permit fee, in which case the original fee will be charged) 30
(xiv) for each gas piping system of one to four outlets 7
(xv) for each gas piping system of five or more, per outlet 2
(xvi) for each medical gas piping system serving
one to five inlet(s)/outlet(s) for a specific gas 50
(xvii) for each additional medical gas piping inlet(s)/outlet(s) 5
*except for replacement of water heaters.
(g) Section 218, Definition of Plumbing System, is amended to read: "Includes all
potable water supply and distribution pipes, all plumbing fixtures and traps, all drainage
and vent pipes, building drains and building sewers, including their respective joints and
connections, devices, receptacles, and appurtenances within the property line of any
premises, and includes water heaters and vents for the premises."
(h) Subsection 405.2, Prohibited Urinals, is amended by adding the following:
"Exception: Nonwater supplied urinals may be installed and shall be maintained in
accordance with manufacturer's installation instructions and required maintenance
schedule. A properly sized drain, vent, and water supply line, permanently capped, shall
be installed for future use in the event the owner decides or is ordered to replace the
nonwater supplied urinal with a water supplied urinal."
(i) Table 4-1, Minimum Plumbing Facilities, is deleted and replaced with ARM
24.301.351 Minimum Required Plumbing Fixtures.
G) Subsection 508.14, paragraph one is amended to read as follows: "Gas utilization
equipment, or any equipment that generates a glow, spark, or flame, in residential garages
and in adjacent spaces that open to the garage and are not part of the living space for a
dwelling unit shall be installed so that all burners, burner-ignition devices, and heating
elements are located not less than 18 inches (450 mm) above the floor unless listed as
flammable vapor ignition resistant."
(k) Delete Subsection 603.3.3.
(I) Subsection 603.1, Approval of Devices or Assemblies, is amended to read as
follows: "Before any device or assembly is installed for the prevention of backflow, it shall
have first been approved by the authority having jurisdiction. Devices or assemblies shall
be tested for conformity with recognized standards or other standards acceptable to the
authority having jurisdiction, so long as those standards are consistent with the intent of
this code. All devices or assemblies installed in a potable water supply system for
protection against backflow shall be maintained in good working condition by the person or
persons having control of such devices or assemblies. If found to be defective or
inoperative, the device or assembly shall be repaired or replaced. No device or assembly
shall be removed from use or relocated or other device or assembly substituted, without
the approval of the authority having jurisdiction."
(m) Subsection 603.4.10, is amended with the addition of the following language:
"Boiler feed lines, in single family dwellings on their own private well, may be protected
with a dual check valve with intermediate atmospheric vent when a nontoxic transfer fluid
is utilized in the boiler."
(n) Subsection 604.1, Materials, is amended to read as follows:
(i) "Water pipe and fittings shall be of brass, copper, cast iron, galvanized malleable
iron, galvanized wrought iron, galvanized steel, or other approved materials."
(ii) Cast iron fittings used for water need not be galvanized if over 2 inches (51 mm) in
size.
(iii) Asbestos-cement, PB, CPVC, RE, PEX, PEX-AL-PEX or PVC water pipe
manufactured to recognized standards may be used for cold water distribution systems
outside a building. These approved outside cold water piping materials except for
asbestos-cement may extend to a point within the foundation perimeter of the building
provided that the piping is buried a minimum of 12 inches, the piping is contained within a
protective sleeve where it passes through concrete construction and the piping does not
extend for more than 24 inches out of the ground at such point where it connects to
approved interior cold water piping material.
(iv) All materials used in the water supply system, except valves and similar devices
shall be of a like material, except where otherwise approved by the administrative
authority.
(v) Table 6-4 is amended to add the following: "PB is allowed for hot and cold water
distribution."
(o) Subsection 604.2, the exception is amended to read as follows: Exception: Type M
copper tubing may be used for water piping when piping is above ground in, or on, a
building.
(p) Subsection 701.1 is amended to read as follows: "Drainage piping shall be cast
iron, galvanized steel, galvanized wrought iron, lead, copper, brass. Schedule 40 ABS
DWV, Schedule 40 ABS DWV cellular core. Schedule 40 PVC DWV, Schedule 40 PVC
DWV cellular core, extra strength vitrified clay pipe, or other approved materials having a
smooth and uniform bore, except that:
"(1) Galvanized wrought iron or galvanized steel pipe shall not be used underground,
and it shall be kept at least six inches (152 mm) above ground.
"(2) ABS and PVC DWV piping installations must be installed in accordance with IS 5,
IS 9 and Chapter 15 "Firestop Protection for DWV and Stormwater Application." Except for
individual single family dwelling units, materials exposed within ducts or plenums shall
have a flame-spread index of not more than 25 and a smoke-developed index of not more
than 50, when tested in accordance with the Test for Surface-Burning Characteristics of
the Building Materials (See the building code standards based on ASTM E-84 and
ANSI/UL723).
"(3) Vitrified clay pipe and fittings shall not be used above ground or where pressurized
by a pump or ejector. They shall be kept at least 12 inches (305 mm) below ground.
"(4) Copper tube for drainage and vent piping shall have a weight not less than that of
copper drainage tube type DWV."
(q) Subsection 610.8, second paragraph, is amended to read as follows: No building
supply pipe shall be less than 3/4 inch (19.1 mm) in inside diameter.
(r) Subsection 701.1.4, is amended with the addition of the following language: Copper
tube for underground drainage and vent piping shall have a weight of not less than that of
copper tube type L.
(s) Subsection 707.4, first paragraph, is amended to read as follows: Each horizontal
drainage pipe shall be provided with a cleanout at its upper terminal and each run of
piping, which is more than 50 feet in total developed length, shall be provided with a
cleanout for each 50 feet, or fraction thereof, in length of such piping.
(t) Section 708.0, Grade of Horizontal Drainage Piping, is amended to read as follows:
Horizontal drainage piping shall be run in practical alignment and a uniform slope of not
less than 1/4 of an inch per foot or 2 percent toward the point of disposal provided that,
where it is impractical due to the depth of the street sewer or to the structural features or to
the arrangement of any building or structure to obtain a slope of 1/4 of an inch per foot or 2
percent, any such pipe or piping 2 inches or larger in diameter may have a slope of not
less than 1/8 of an inch per foot or 1 percent.
(u) Subsection 710.1, is amended to read as follows: "Where a fixture is installed on a
floor level that is lower than the next upstream manhole cover of the public or private
sewer serving such drainage piping may be protected from the backflow of sewage by
installing an approved type backwater valve. Fixtures on floor levels above such elevation
shall not discharge through the backwater valve."
(v) Subsection 718.1, the exception is amended to read as follows: Exception: Where it
is impractical, due to the depth of the street sewer or to the structural features or to the
arrangement of any building or structure, to obtain a slope of 1/4 of an inch per foot, any
pipe or piping 3 inches or larger in diameter may have a slope of 1/8 of an inch per foot
and any such pipe or piping 8 inches in diameter or larger may have a slope of 1/16 of an
inch per foot.
(w) Subsection 903.2.1 is amended to read as follows: "Copper tube for underground
drainage and vent piping shall have a weight of not less than that of copper tube Type L."
(x) Subsection 906.1, is amended to read as follows: Each vent pipe or stack shall
extend through its flashing and shall terminate vertically not less that 12 inches above the
roof nor less than 1 foot from any vertical surface.
(y) Subsection 906.3, is amended to read as follows: Vent pipes shall be extended
separately or combined, of full required size, not less than 12 inches above the roof or fire
wall.
(z) Subsection 906.7, is amended to read as follows: Frost and Snow Closure: Where
frost or snow closure is likely to occur in locations having a minimum design temperature
below zero degrees Fahrenheit vent terminals shall be a minimum of 3 inches in diameter,
but in no event smaller than the required vent pipe. The change in diameter shall be made
inside the building at least 1 foot below the roof and terminate not less than 12 inches
above the roof, or as required by the administrative authority.
(aa) Section 908.0, is amended to read as follows: Wet venting.
(ab) Subsection 908.1, is amended to read as follows:
(i) Wet venting is limited to drainage piping receiving the discharge from the trap arm of
one and two fixture unit fixtures that also serves as a vent for not to exceed four fixtures.
(ii) All wet vented fixtures shall be within the same story; provided, further, that fixtures
with a continuous vent discharging into a wet vent shall be within the same story as the
wet vented fixtures.
(ac) Subsection 908.2, is amended to read as follows: The piping between any two
consecutive inlet levels shall be considered a wet vented section. Each wet vented section
shall be a minimum of one pipe size larger than the required minimum waste pipe size of
the upper fixture or shall be one pipe size larger than the required minimum pipe size for
the sum of the fixture units served by such wet vented section, whichever is larger, but in
no case less than 2 inches.
(ad) Chapter 12, Fuel Piping, is deleted and replaced with the International Fuel Gas
Code.
(ae) Chapter 13, Health Care Facilities and Medical Gas and Vacuum Systems, is
deleted. In lieu of Chapter 13, the Department of Labor and Industry adopts and
incorporates by reference the National Fire Protection Association's Standard NFPA99C,
Gas and Vacuum Systems, 2005 edition, referred to as NFPA99C, unless a different
edition date is specifically stated, as the standard for the installation of medical gas and
vacuum systems. The requirements of this rule shall not be construed as to replace or
supersede any additional requirements for testing and certification of medical gas and
vacuum systems, including independent third party certification of systems, as may be
applicable. NFPA99C is a nationally recognized standard setting forth minimum standards
and requirements for medical gas and vacuum systems. A copy of NFPA 99C may be
obtained from the National Fire Protection Association, One Batterymarch Park, P.O. Box
9101, Quincy, MA 02269-91 01.
(2) The purpose of this code is to provide minimum requirements and standards for
plumbing installations for the protection of the public health, safety, and welfare. The
Uniform Plumbing Code is a nationally recognized model code setting forth minimum
standards and requirements for plumbing installations. A copy of the Uniform Plumbing
Code may be obtained from the Department of Labor and Industry, Bureau of Building and
Measurement Standards, P.O. Box 200517, Helena, MT 59620-0517, at cost plus postage
and handling. A copy may also be obtained by writing to the International Association of
Plumbing and Mechanical Officials, 20001 South Walnut Drive, Walnut, CA91789.
History: 50-60-203 . 50-60-504 . 50-60-508 . MCA; [MP , 50-60-201 . 50-60-203 .
50-60-504 . 50-60-508. MCA; NEW , 1978 MAR p. 380, Eff. 3/25/78; AMD , 1978 MAR p.
1480, Eff. 10/27/78; AMD , 1979 MAR p. 1662, Eff. 12/28/79; AMD , 1981 MAR p. 1052,
Eff. 9/18/81; AMD, 1982 MAR p. 2170, Eff. 12/31/82: TRANS .from Dept. of Admin. , Ch.
352, L. 1985, Eff. 7/1/85; AMD , 1986 MAR p. 106, Eff. 1/31/86; AMD , 1989 MAR p. 476,
Eff. 4/28/89; AMD , 1992 MAR p. 1133, Eff. 5/29/92: AMD . 1994 MAR p. 299, Eff. 2/11/94;
AMD , 1996 MAR p. 420, Eff. 2/9/96; AMD , 1997 MAR p. 44, Eff. 1/17/97; AMD , 1997
MAR p. 2061, Eff. 11/18/97: AMD , 1998 MAR p. 2563, Eff. 9/25/98: AMD , 1999 MAR p.
1885, Eff. 10/1/99; AMD , 2000 MAR p. 3168, Eff. 11/10/00: TRANS .from Commerce,
2001 MAR p. 2301: AMD , 2004 MAR p. 571, Eff. 3/12/04; AMD , 2006 MAR p. 567, Eff.
2/24/06; AMD , 2007 MAR p. 112, Eff. 1/26/07.
An American National Standard
lAPMO/ANSI UPC 1-2006
2006
UNIFORM
PLUMBING
CODE
lAPMO.
®
^
.^ tf^^'lona /s,.
v*.
ANSI
MCAA
WORLD PLUMBING
COUNCIL
"^^^^^^I^^K^^"^
REVISION MARKINGS
Code changes from the 2003 edition are marked in the margins as follows:
An arrow denotes a deletion.
I A vertical denotes a change.
TiA TIA indicates that the revision is the result of a Tentative Interim Amendment
^,, For further information on tentative interim amendments see Section 5 of the lAPMO
TIA
jiA Regulations Governing Committee Projects available at http://www.iapmo.org/iapmo/
TIA code_rules-regs.html
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
A reference in brackets [ ] following a section or paragraph indicates material that has
been extracted from another document. This reprinted material is not the complete and
official position of the National Fire Protection Association on the reference subject which
is represented by the standard in its entirety. Text which has been extracted pursuant to
lAPMO's Extract Guidelines is denoted with the use of "NFPA" in the margin. This text
has not been fully processed by lAPMO in accordance with ANSI's public announcement
consensus requirements for an American National Standard (ANS) nor approved by
ANSI's Board of Standards Review, but will be fuUy processed in accordance with those
requirements as part of the next revision cycle for this document.
Information on referenced publications can be found in Chapter 14.
All pressures used in this code are gauge pressures imless otherwise indicated.
Copyright © 2006
by
International Association of Plumbing and Mechanical Officials
All Rights Reserved
No part of this work may be reproduced or recorded in any form or by any means,
except as may be expressly permitted in writing by the publisher.
Twenty-Fourth Edition
First Printing, January 2006
Second Printing, April 2006
Third Printing, May 2006
Fourth Printing, January 2007
Fifth Printing, June 2007
Sixth Printing, October 2007
ISSN 0733-2335
Published by the International Association of Plumbing and Mechanical Officials
5001 E. Philadelphia Street • Ontario, CA 91761-2816 - USA
Main Phone: (909) 472-4100 • Main Fax: (909) 472-4150
897-M
2006 UPC Foreword
The advantages of a uniform plumbing code adopted by various local jurisdictions has long been recognized.
Disorder in the industry as a result of widely divergent plumbing practices and the use of many different,
often conflicting, plumbing codes by local jurisdictions influenced the Western Plumbing Officials Association
(now the International Association of Plumbing and Mechanical Officials [lAPMO]) to form a committee of
plumbing inspectors, master and journeyman plumbers, and sanitary and mechanical engineers, assisted by
public utility companies and the plumbing industry to create a basic plumbing document for general use. The
product of this effort, the first edition of the Uniform Plumbing Code'^^ (UPC^"^) was officially adopted by
lAPMO in 1945. The widespread use of this code over the past five decades by jurisdictions throughout the
United States and internationally is testament to its merit.
With the publication of the 2003 Edition of the Uniform Plumbing Code, another significant milestone was
reached. For the first time in the history of the United States, a plumbing code was developed through a true
consensus process. The 2006 edition represents the most current approaches in the plumbing field and is the
second edition developed under the ANSI consensus process. Contributions to the content of the code were
made by every segment of the built industry, including such diverse interests as consumers, enforcing
authorities, installers /maintainers, insurance, labor, manufacturers, research/standards/testing laboratories,
special experts, and users.
The UPC is designed to provide consumers with safe and sanitary plumbing systems while, at the same time,
allowing latitude for innovation and new technologies. The public at large is encouraged and invited to
participate in lAPMO's open consensus code development process. This code is updated every three years. A
code development timeline and other relevant information is available at lAPMO's website at
www.iapmo.org.
The Uniform Plumbing Code is dedicated to all those who, in working to achieve "the ultimate plumbing code,"
have imselfishly devoted their time, effort, and personal fimds to create and maintain this, the finest plumbing
code in existence today.
The 2006 Uniform Plumbing Code is supported by the American Society of Sanitary Engineering (ASSE), the
Mechanical Contractors Association of America (MCAA), the Plumbing-Heating-Cooling Contractors National
Association (PHCC-NA), the United Association (UA), and the World Plumbing Council (WPC). The presence
of these logos, while reflecting support, does not imply any ownership of the copyright to the UPC, which is
held exclusively by lAPMO. Further, the logos of these associations indicates the support of lAPMO's open,
consensus process being used to develop lAPMO's codes and standards.
The addresses of the organizations are as follows:
ASSE - 901 Canterbury Road, Suite A • Westiake, OH 44145-7201 • (440) 835-3040
MCAA - 1385 Piccard Drive • Rockville, MD 20850 • (301) 869-5800
PHCC-NA - PO Box 6808 • Falls Church, VA 22046 • (800) 533-7694
UA - 901 Massachusetts Avenue NW • Washington, DC 20001 • (202) 628-5823
WPC - WPC Secretary • c/o The Institute of Plumbing • 64 Station Lane • Hornchurch Essex
RM12 6NB • United Kingdom • +44 17-08-47-27-91
Tentative Interim Amendment (TIA)
A Tentative Interim Amendment (TIA) to any Document may be processed if the Council Secretary
determines, after a preliminary review, and consultation with the appropriate Chair, that the Amendment
appears to be of an emergency nature requiring prompt action and has the endorsement of a Member of the
involved Technical Committee;
Section 206.0 Design Flood Elevation - This Tentative Interim Amendment (TIA) was issued on September
26, 2005.
Section 208.0 Flood Hazard Area - This Tentative Interim Amendment (TIA) was issued on September
26. 2005.
Section 301.3 Flood Hazard Resistance - This Tentative Interim Amendment (TIA) was issued on
September 26, 2005.
Section 301.3.1 General - This Tentative Interim Amendment (TIA) was issued on September 26, 2005.
Section301.3.2 Flood hazard areas subject to high velocity wave action - This Tentative Interim
Amendment (TIA) was issued on September 26, 2005.
Section 41 1 .7 - This Tentative Interim Amendment (TIA) was issued on December 7, 2005.
Section 507.8 - This Tentative Interim Amendment (TIA) was issued on December 7, 2005.
Section 603.4.21 Pure water process systems - This Tentative Interim Amendment (TIA) was issued on
December 7, 2005.
Section 603.4.21 .1 Dialysis water systems - This Tentative Interim Amendment (TIA) was issued on
December 7, 2005.
Section 715.3 - This Tentative Interim Amendment (TIA) was issued on September 17, 2003.
Section 1202.0 General. - This Tentative Interim Amendment (TIA) was issued on August 28, 2006.
Section 1216.1 Required Gas Supply. - This Tentative Interim Amendment (TIA) was issued on August
28. 2006.
Section 1217.1 Pipe Sizing Methods. - This Tentative Interim Amendment (TIA) was issued on August
28,2006.
Section 1217.1.1 Longest Length IVlethod. - This Tentative Interim Amendment (TIA) was issued on
August 28, 2006.
Section 1217.1.2 Branch Length Method. - This Tentative Interim Amendment (TIA) was issued on August
28, 2006.
Section 1217.1.3 Hybrid Pressure. - This Tentative Interim Amendment (TIA) was issued on August
28, 2006.
Section 1217.2 Tables for Sizing Gas-Piping Systems. - This Tentative Interim Amendment (TIA) was
issued on August 28, 2006.
Section 1217.3 Sizing Equations. - This Tentative Interim Amendment (TIA) was issued on August 28, 2006.
Figure 12-2 Example Illustrating Use of Tables 12-1 and 12-8 - This Tentative Interim Amendment (TIA)
was issued on August 28, 2006.
Section 1217.4 - This Tentative Interim Amendment (TIA) was issued on August 28, 2006.
Section 1 21 7.5 - This Tentative Interim Amendment (TIA) was issued on August 28, 2006.
Section 1 21 7.6 - This Tentative Interim Amendment (TIA) was issued on August 28, 2006.
Appendix K, K 1 Private Sewage Disposal - General - This Tentative Interim Amendment (TIA) was issued
on September 26, 2005.
Appendix K, K 5 Septic Tank Construction - This Tentative Interim Amendment (TIA) was issued on
September 26, 2005.
VI
Appendix K, Table K-1 Location of Sewage Disposal Systems - This Tentative Interim Amendment (TIA)
was issued on September 26, 2005.
Appendix L, L8.6 Additional Venting Required - This Tentative Interim Amendment (TIA) was issued on
February 7, 2006.
For further information on Tentative Interim Amendments, see Section 5 of the lAPMO Rules Governing
Committee Projects - www.iapmo.org.
VII
COMMITTEE ON UNIFORM PLUMBING CODE
These lists represent the membership at the time the Committee was balloted on the final text of this edition. Since that time, changes in the membership may have
occurred. Please refer to the new members list below.
Terry Swisher, Chairman
State of Oregon, [E]
James Weflen, Secretary
Copper Development Association, [M]
Robert Aagaard, American Society of Sanitary
Engineering [R/S/T]
Rand Ackroyd, Rand Engineering [M]
Rep. Plumbing and Drainage Institute
Julius Ballanco, JB Engineering/Code Consultant PC [SE]
Rep. American Society of Plumbing Engineers
George Bliss, United Association [L]
Sylvanus Bloice, Roots Plumbing Ser\'ices [I/M]
Jeremy Brown, NSF International [R/S/T]
Lawrence Brown, National Association of Home Builders [U]
Paul Cabot, American Gas Association [U]
Richard Church, Plastic Pipe and Fittings Association [M]
Donald Dickerson, Donald Dickerson Associates [SE]
Rickey Fabra, Plumbers & Steamfitters Local [L]
Lawrence Gibson, fntertek Testing Services [R/S/T]
John M. Jacobs, Mechanical Contractors Association of America [I/M]
Robert Kordulak, Plumbing-Heating-Cooling Contractors
National Association [I/M]
Theodore Lemoff, NFPA [R/S/T]
William LeVan, Cast Iron Soil Pipe Institute [M]
Thomas Pape, California Urban Water Conservation Council [C]
Leonard Ramociotti, City of Reno [E]
Phillips Ribbs, PHR Consultant [SE]
Arnold Rodio, Pace Setter Plumbing [I/M]
Anthony Scarano, Plastics Piping Consultant [SE]
Joseph Stemola, National Propane Gas Association (NPGA) [U]
Larry Soskin, Ace Duraflo [I/M]
Amir Tabakh, City of Los Angeles [E]
John Taecker, Underwriters Laboratories [R/S/T]
Don Traylor, State Plumbing Board of Louisiana [E]
David Viola, Plumbing Manufacturers Institute [M]
Alternates
Ian Chang, Intertek Testing Services [R/S/T]
Shannon Corcoran, American Society of Sanitary
Engineering [R/S/T]
James Dingman, Underwriters Laboratories [R/S/T]
Richard Emerson, Plumbing Manufacturers Institute [M]
Bob Friedlander, Construction Code Consultant [M]
Rep. Plastic Pipe aiid Fittings Association
Myron Havis, Copper Development Association [M]
Nasrin Kashefi, NSF International [R/S/T]
Kirk Nelson, Plumbing-Heating-Cooling Contractors
National Association [I/M]
Michael Tharpe, City of Los Angeles [E]
April Trafton, Donald Dickerson Associates [SE]
Fred Volkers, United Association [L]
James Walls, Cast Iron Soil Pipe Institute [M]
Mike Wynne, Plumbers & Steamfitters Local [L]
New Committee Members as of January 2006
Tim CoUings, Salt Lake City, Utah [E] is the new chairman of the
technical committee appointed as of March 2006
Nasser Nikravi, State of California OSHPD [E]
Ray Moore, American Society of Plumbing Enginner [SEl
Nonvoting
Chris Salazar, Ex-Officio, lAPMO [E]*
Carl Marbery, lAPMO Staff Liaison
Morrie Klimboff, Member Emeritus, M Klimboff Consulting [C]*
Ljmne Simnick, lAPMO Saff Liaison
COMMITTEE MEMBERSHIP CLASSIFICATION ABBREVIATIONS
These classifications apply to Technical Committee members and represent their principal interest in the activity of a committee.
M Manufacturer: A representative of a maker or marketer of a product, assembly, or system, or portion thereof, that is affected by the standard.
U User: A representative of an entity that is subject to the provisions of tlie standard or that voluntarily uses the standard.
I/M Inslaller/Maintainer: A representative of an entity that is in the business of ir\stalling or maintaining a product, assembly, or system affected by the standard.
L Labor: A labor representative or employee concerned with safety in tl\e workplace.
R/S/T Research/Standards/Testing Laboratory: A representative of an independent research organization; an organization that develops codes, standards or other similar documents; or
an independent testing laboratory.
E Enforcing Authority: A representative or an agency or an organization that promulgates and/or enforces standards.
I Insurance: A representative of an insurance company, broker, agent, bureau, or inspection agency.
C Consumer: A person who is, or represents, the ultimate purdiaser of a product, system, or ser\'ice affected by the standard, but who is not included in the User classification.
SE Special Expert: A person not representing any of the previous classifications, but who has special expertise in the scope of the standard or portion thereof.
VIII
FORM FOR PROPOSALS ON lAPMO UPC/UMC COMMITTEE DOCUMENT
NOTE: Ail proposals MUST be received by 5:00 Pl\/I PST/PDST on tlie published proposal-closing date.
For further information on the standards-making process, please
contact Codes and Standards Administration at 909-472-41 1
For technical assistance, please call lAPMO at 909-472-41 1 1 or
909-472-4104
FOR OFFICE USE ONLY
LOG#
DATE REC'D:
PLEASE USE SEPARATE FORM FOR EACH PROPOSAL
Please indicate in which format you wish to receive your ROP/ROC: ^ Paper □ Download* D cd-rom
*Note: In choosing the download option, you intend to view the ROP/ROC from our website. NO copy will be sent to you.
Date:
Name:
Telephone #:.
Company:
Street Address:.
.City:.
State:.
Zip:.
Please Indicate Organization Represented (if any):,
1 . a) lAPMO Document Title
b) Section/Paragraph
Document Year
2. Proposal Recommends (check one): D New Text
□ Revise Text
n Delete Text
3. Proposal (Include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed
text should be in legislative format: i.e., use underscore to denote wording to be inserted ( inserted wording ) and strike-
through to denote wording to be deleted ( do l otod word i ng ). PLEASE TYPE OR PRINT LEGIBLY IN BLACK INK.]
Statement of Problem and Substantiation for Proposal: [Note: State the problem that will be resolved by your
recommendations; give the specific reason for your proposal, including copies of tests, research papers, etc. If more than
200 words, it may be abstracted for publication.]
5. □ This proposal is original material. [Note; Original material is considered to be the submitter's own idea based on or as a result
of his/her own experience, thought, or research and, to the best of his/her knowledge, is not copied from another source.]
n This proposal is not original material, its source (if known) is as follows:
I hereby grant lAPMO all and full rights in copyright, in this proposal, and I understand that I acquire no rights in any publication of
lAPMO in which this proposal appears in this or another similar or analogous form.
Signature (Required):
lAPMO CODES DEPARTMENT FAX • (909) 472-41 98 or (909) 472-4246
Mail to: Secretary, Standards Council • lAPMO • 5001 E Philadelphia Street • Ontario • CA • 91761-2816
IX
INSTRUCTIONS FOR SyBMITTING PROPOSALS
- PLEASE READ CAREFULLY -
1 . Type or print in BLACK ink.
2. Indicate the title of the document and the document year. Also indicate the specific
section or paragraph that the proposed amendment applies to.
3. Check the appropriate box to indicate whether this proposal recommends adding new
text, revising existing text, or deleting text.
4. In the space identified as "Proposal", indicate the exact wording you propose as new
or revised text, or the text you propose be deleted.
5. In the space titled "Statement of Problem and Substantiation for Proposal", state the
problem that will be resolved by your recommendation and give the specific reason
for your proposal. Include copies of test results, research papers, fire experience, or
other materials that substantiate your recommendation. [See note below, item (f).]
6. Check the appropriate box to indicate whether or not this proposal is original material,
and, if it is not, indicate the source of the material.
7. Sign the proposal.
If supplementary material (photographs, diagrams, reports, etc.) is included, you may be
required to submit sufficient copies for all members and alternates of the technical committee.
The technical committee is authorized to abstract the "Statement of Problem and
Substantiation for Proposal" if it exceeds 200 words for publication in the Report on Proposals.
NOTE: The lAPMO Regulations Governing Committee Projects in Paragraph 4-3.3 state:
Each proposal shall be submitted to the Council Secretary and shall include: (a) identification
of the submitter and his or her affiliation (i.e., technical committee, organization, company),
where appropriate; (b) identification of the document, edition of the document, and paragraph
of the document to which the proposal is directed; (c) the proposed text of the proposal,
including the wording to be added, revised (and how revised), or deleted; (d) a statement of
the problem and substantiation for proposal; (e) the signature of the submitter; and (f) two
copies of any document(s) (other than an lAPMO document) being proposed as a reference
standard or publication (see 3-3.7).
TABLE OF CONTENTS
Chapter 1 Administration 1
101.0 Title, Scope, General . . .1
101.1 Title • ..1
101.2 Purpose 1
101.3 Plans Required 1
101.4 Scope 1
101.5 Application to Existing
Plumbing System ....;.. 2
102.0 Organization and Enforcement 2
102.1 Authority Having Jurisdiction 2
102.2 Duties and Powers of the
Authority Having Jurisdiction 2
102.3 Violations and Penalties 3
103.0 Permits and Inspections ........... . . . .3
103.1 Permits ... .3
103.2 Application for Permit 3
103.3 Permit Issuance .4
103.4 Fees 5
103.5 Inspections 5
103.6 Connection Approval . . .7
103.7 Unconstitutional 7
103.8 Validity .7
Table 1-1 Plumbing Permit Fees 9
Chapter 2 Definitions 11
201.0 General 11
202.0 Definition of Terms 11
Chapter 3 General Regulations 21
301 .0 Materials - Standards and Alternates . .21
301.1 Minimum Standards 21
301.2 Alternate Materials and Methods of
Construction Equivalency 21
301.3 Flood Hazard Resistance 22
302.0 Iron Pipe Size (IPS) Pipe ......... .22
303.0 Disposal of Liquid Waste 22
304.0 Connections to Plumbing
System Required .22
305.0 Sewers Required .22
306.0 Damage to Drainage System
or Public Sewer 22
307.0 Lidustrial Wastes 23
308.0 Location 23
309.0 Improper Location 23
310.0 Workmanship 23
311.0 Prohibited Fittings and Practices . . .23
312.0 Independent Systems 23
313.0 Protection of Piping, Materials,
and Stiuctures 24
314.0 Hangers and Supports 25
315.0 Trenching, Excavation
and Backfill 25
316.0 Joints and Connections 25
317.0 Increasers and Reducers 27
318.0 Food-Handling
Establishments 27
319.0 TestGauges 27
320.0 Medical Gas and Vacuum Systems . .27
Chapter 4 Plumbing Fixtures and
Fixture Fittings 29
401.0 Materials -General Requirements . . .29
402.0 Water-Conserving
Fixtures and Fittings 29
403.0 Overflows 29
404.0 Strainers and Connections 29
405.0 Prohibited Fixtures 29
406.0 Special Fixtures and Specialties 30
407.0 h\stallation 30
408.0 Water Closets 30
409.0 Urinals 30
410.0 Flushing Devices for Water
Closets and Urinals ..;... .31
411.0 Floor Drains and Shower Stalls ... .31
412.0 Minimum Number of
Required Fixtures 33
413.0 Fixtures and Fixture Fittings
for Persons with Disabilities 34
414.0 Bathtubs and Whirlpool Bathtubs ..34
415.0 Installation of Fixture Fittings .... .34
416.0 Bidets .34
417.0 Future Fixtures ' ...... .34
418.0 Shower and Tub-Shower
Combination Contiol Valves .... . .34
Table 4-1 Minimum Plumbing Facilities .... .35
Chapter 5 Water Heaters Part I 39
501.0 General 39
502.0 Definitions 39
503.0 Permits 40
XI
UNIFORM PLUMBING CODE
504.0 Inspection 40
505.0 Water Heater Requirements 40
506.0 Oil-Burning and
Other Water Heaters 40
507.0 Air for Combustion and Ventilation . . . .40
508.0 Other Water Heater
Installation Requirements 40
509.0 Equipment on Roofs 47
510.0 Venting of Equipment 48
511.0 Sizing of Category I Venting Systems ... 62
512.0 Direct- Vent Equipment 66
Part n Sizing of Venting Systems Serving
Appliances Equipped with Draft
Hoods, Category I Appliances, and
Appliances Listed for Use with
Type B Vents 86
Chapter 6 Water Supply and Distribution . . .95
601.0 Rurming Water Required 95
602.0 Unlawful Connections 95
603.0 Cross-Connection Control 96
604.0 Materials 101
605.0 Valves 102
606.0 Joints and Connections 102
607.0 Gravity Supply Tanks 103
608.0 Water Pressure, Pressure Regulators,
Pressure Relief Valves, and Vacuum
Relief Valves 103
609.0 Installation, Testing, Unions,
and Location 104
610.0 Size of Potable Water Piping 105
611.0 Drinking Water Treatment Units . .107
Table 6-5 Water Supply Fixture Units (WSFU)
and Minimum Fixture
Branch Pipe Sizes 108
Table 6-6 Fixture Unit Table for Determining
Water Pipe and Meter Sizes 109
Chapter 7 Sanitary Drainage Ill
Part I Drainage Systems Ill
701.0 Materials Ill
702.0 Fixture Unit Equivalents 113
703.0 Size of Drainage Piping 113
Table 7-3 Drainage Fixture Unit Values
(DFU) 112
Table 7-4 Discharge Capacity In Gallons per
Minute (Liters per Second) For
Intermittent Flow Only 113
704.0 Fixture Connections (Drainage) . . .113
705.0 Joints and Connections 114
706.0 Changes in Direction of Drainage
Flow 115
707.0 Cleanouts 115
708.0 Grade of Horizontal Drainage
Piping 116
709.0 Gravity Drainage Required 117
710.0 Drainage of Fixtures Located Below
the Next Upstream Manhole or Below
the Main Sewer Level 117
711.0 Suds Relief 118
712.0 Testing 118
Part II Building Sewers 119
713.0 Sewer Required 119
714.0 Damage to Public Sewer or Private
Sewage Disposal System .119
715.0 Building Sewer Materials 119
716.0 Markings 119
717.0 Size of Building Sewers 119
718.0 Grade, Support, and Protection of
Building Sewers 120
719.0 Cleanouts 120
720.0 Sewer and Water Pipes 120
721.0 Location 121
722.0 Abandoned Sewers and Sewage
Disposal Facilities 122
723.0 Building Sewer Test 122
Chapter 8 Indirect Wastes 123
801.0 Indirect Wastes 123
802.0 Approvals . . .'. 123
803.0 Indirect Waste Piping 124
804.0 Indirect Waste Receptors 124
805.0 Pressure Drainage Connections . . .124
806.0 Sterile Equipment 124
807.0 Appliances 124
808.0 Cooling Water 124
809.0 Drinking Fountains 124
810.0 Steam and Hot Water Drainage
Condensers and Sumps 125
811.0 Chemical Wastes 125
812.0 Clear Water Wastes 126
XII
TABLE OF CONTENTS
813.0 Swimming Pools 126
814.0 Condensate Wastes and Control . .126
Chapter 9 Vents 127
901.0 Vents Required 127
902.0 Vents Not Required 127
903.0 Materials 127
904.0 Size of Vents 127
905.0 Vent Pipe Grades and Connections . .128
906.0 Vent Termination 128
907.0 Vent Stacks and Relief Vents 128
908.0 Vertical Wet Venting 129
909.0 Special Venting for Island Fixtures . .129
910.0 Combination Waste and
Vent Systems 129
Chapter 10 Traps and Interceptors 131
1001.0 Traps Required 131
1002.0 Traps Protected by Vent Pipes ....131
1003.0 Traps - Described .131
1004.0 Traps - Prohibited 132
1005.0 Trap Seals 132
1006.0 Floor Drain Traps 132
1007.0 Trap Seal Protection 132
1008.0 Building Traps 132
1009.0 Industrial Interceptors (Clarifiers)
and Separators 132
1010.0 Slaughterhouses, Packing
Establishments, etc 132
1011.0 Minimum Requirements
for Auto Wash Racks 132
1012.0 Commercial and
Industrial Laundries 133
1013.0 Bottling Establishments 133
1014.0 Grease Interceptors 133
1015.0 FOG (Fats, Oils, and Greases)
Disposal System 134
1016.0 Sand Interceptors 135
1017.0 Oil and Flammable
Liquid Interceptors 136
Chapter 11 Storm Drainage 137
1101.0 General 137
1102.0 Materials 137
1103.0 Traps on Storm Drains
and Leaders 139
1104.0 Leaders, Conductors,
and Connections 139
1105.0 Roof Drains , 140
1106.0 Size of Leaders, Conductors, and
Storm Drains 140
1107.0 Values of Continuous Flow 140
1108.0 ControUed-Flow Roof Drainage . . .140
1109.0 Testing 141
Chapter 12 Fuel Piping 149
1201.0 Scope of Gas Piping 149
1202.0 General 149
1203.0 Definitions ,149
1204.0 h\spection 150
1205.0 Certificate of Inspection 150
1206.0 Authority to Render
Gas Service 150
1207.0 Authority to Disconnect 151
1208.0 Temporary Use of Gas 151
1209.0 Gas-Piping System Design,
Materials, and Components . .151
1210.0 Excess Flow Valve .157
1211.0 Gas Piping Installation 158
1212.0 Equipment Connections to Building
Piping .165
1213.0 Liquefied Petroleum Gas Facilities
and Piping 166
1214.0 Pressure Testing and Inspection . . .166
1215.0 Interconnections Between
Gas Piping Systems 168
1216.0 Required Gas Supply 168
1217.0 Required Gas Piping Size 168
Table 12-7 to Table 12-23 171
Chapter 13 Health Care Facilities and Medical
Gas and Vacuum Systems 201
Part I Special Requirements for Health
Care Facilities 201
1301.0 Application 201
1302.0 Medical Gas and Vacuum Piping
Systems -Installation Requirements . .201
1303.0 Protrusions from Walls .201
1304.0 Psychiatric Patient Rooms 201
1305.0 Locations for Ice Storage 201
1306.0 Sterilizers 201
1307.0 Vapor Vents and Stacks
for Sterilizers 202
1308.0 Aspirators 202
XIII
UNIFORM PLUMBING CODE
Part II Medical Gas and Vacuum System . .202
1309.0 Application 202
1310.0 Definitions 202
1311.0 General Requirements 203
1312.0 Plan Review 205
1313.0 System Performance 205
1314.0 Required Pipe Sizing 205
1315.0 Workmanship 205
1316.0 Materials 206
1317.0 Cleaning for Medical
Gas Piping Systems 207
1318.0 Installation of Piping 207
1319.0 Joints 208
1320.0 Valves - Requirements, Locations,
and Labeling 210
1321.0 Pressure-Regulating Equipment ..211
1322.0 Station Outlets /Inlets 212
1323.0 Labeling and Identification 212
1324.0 Alarms 213
1325.0 Medical Air System 213
1326.0 Medical Vacuum Pump System . . .214
1327.0 Testing and Inspection 215
1328.0 System Certification 218
Chapter 14 Mandatory Referenced
Standards 223
Table 14-1 Standards for Materials, Equipment,
Joints, and Connections 223
Table 14-1 hidex 247
Abbreviation in Table 14-1 259
Chapter 15 Firestop Protection 261
1501.0 General Requirements 261
1502.0 Plans and Specifications 261
1503.0 Installation 261
1504.0 Definitions 261
1505.0 Combustion Piping Installations . .261
1506.0 Non-Combustible
Piping Installation 261
1507.0 Required Inspection 262
Chapter 16 Gray Water Systems 263
1601.0 Gray Water Systems - General 263
1602.0 Definition , 263
1603.0 Permit 263
1604.0 Drawings and Specifications 263
1605.0 Inspection and Testing 263
1606.0 Procedure for Estimating Gray
Water Discharge 264
1607.0 Required Area of Subsurface
Irrigation /Disposal Fields 264
1608.0 Determination of Maximum
Absorption Capacity .264
1609.0 Holding Tank Construction 265
1610.0 Valves and Piping 265
1611.0 Irrigation/Disposal Field
Construction .265
1612.0 Special Provisions 266
Part II 273
1613.0 Reclaimed Water Systems -
General 273
1614.0 Definitions 273
1615.0 Permit .273
1616.0 Drawings and Specifications ..... .273
1617.0 Pipe Material/Pipe Identification . .273
1618.0 Installation .274
1619.0 Signs 274
1620.0 Inspection and Testing 275
1621.0 Sizing 276
1622.0 Approved Uses of Reclaimed
Water 276
Appendices Table of Contents 277
Appendix A Recommended Rules for Sizing the
Water Supply System 279
Appendix B Explanatory Notes on Con\bination
Waste and Vent Systems 295
Appendix C Deleted
Appendix D Sizing Stormwater
Drainage Systems 297
Appendix E Manufactured /Mobile Home Parks
and Recreational Vehicle Parks 305
Appendix F Firefighter Breathing Air
Replenishment Systems 317
Appendix I Installation Standards
Table of Content 321
Appendix K Private Sewage Disposal Systems . .421
Appendix L Alternate Plumbing Systems 433
Useful Tables 441
Index 449
XIV
CHAPTER 1
ADMINISTRATION
101.0 Title, Scope, and General.
101.1 Title.
This document shall be known as the "Uniform
Plumbing Code," may be cited as such, and will be
referred to herein as "this code."
101.2 Purpose.
This code is an ordinance providing minimum
requirements and standards for the protection of the
public health, safety, and welfare.
101.3 Plans Required.
The Authority Having Jurisdiction may require the
submission of plans, specifications, drawings, and
such other information as the Authority Having
Jurisdiction may deem necessary, prior to the
commencement of, and at any time during the
progress of, any work regulated by this code.
The issuance of a permit upon plans and
specifications shall not prevent the Authority Having
Jurisdiction from thereafter requiring the correction
of errors in said plans and specifications or from
preventing construction operations being carried on
thereunder when in violation of this code or of any
other pertinent ordinance or from revoking any
certificate of approval when issued in error.
101 .4 Scope.
101.4.1 The provisions of this code shall apply
to the erection, installation, alteration, repair,
relocation, replacement, aiddition to, use, or
maintenance of plumbing systems within this
jurisdiction.
1 01 .4.1 .1 Repairs and Alterations.
101.4.1.1.1 In existing buildings or
premises in which plumbing installations
are to be altered, repaired, or renovated,
deviations from the provisions of this
code are permitted, provided such
deviations are found to be necessary
and are first approved by the Authority
Having Jurisdiction.
101.4.1.1.2 Existing building sewers
and building drains may be used in
cormection with new buildings or new
plumbing and drainage work only
when they are found on examination
and test to conform in all respects to the
requirements governing new work, and
the proper Autiiority Having Jurisdiction
shall notify the owner to make any
changes necessary to conform to this
code. No building, or part thereof, shall
be erected or placed over any part of a
drainage system that is constructed of
materials other than those approved
elsewhere in this code for use under or
within a building.
1 01 .4.1 .1 .3 All openings into a drainage
or vent system, excepting those openings
to which plumbing fixtures are properly
connected or which constitute vent
terminals, shall be permanently plugged
or capped in an approved manner, using
the appropriate materials required by
this code.
1 01 .4.1 .2 Maintenance. The plumbing and
drainage system of any premises under the
Authority Having Jurisdiction shall be
maintained in a sanitary and safe operating
condition by the owner or the owner's
agent.
101.4.1.3 Existing Construction. No provi-
sion of this code shall be deemed to
require a change in any portion of a plumbing
or drainage system or any other work
regulated by this code in or on an existing
building or lot when such work was
installed and is maintained in accordance
with law in effect prior to the effective date
of this code, except when any such plumbing
or drainage system or other work regulated
by this code is determined by the Authority
Having Jurisdiction to be in fact dangerous,
unsafe, insanitary, or a nuisance and a
menace to life, health, or property.
101.4.1.4 Conflicts Between Codes. When
the requirements within the jurisdiction of
this plumbing code conflict with the require-
ments of the mechanical code, this code shall
prevail.
101.4.2 Additions, alterations, repairs, and
replacement of plumbing systems shall comply
with the provisions for new systems except as
otherwise provided in Section 101.5.
101.4.3 The provisions in the appendices are
intended to supplement the requirements of this
code and shall not be considered part of this
code unless formally adopted as such.
101.5-102.2
UNIFORM PLUMBING CODE
101.5 Application to Existing Plumbing System.
101.5.1 Additions, Alterations, or Repairs.
Additions, alterations, or repairs may be made
to any plumbing system without requiring the
existing plumbing system to comply with all the
requirements of this code, provided the addition,
alteration, or repair conforms to that required for
a new plumbing system. Additions, alterations,
or repairs shall not cause an existing system to
become unsafe, insanitary, or overloaded.
101.5.2 Health and Safety. Whenever com-
pliance with all the provisions of this code
fails to eliminate or alleviate a nuisance, or any
other dangerous or insanitary condition that
may involve health or safety hazards, the owner
or the owner's agent shall install such additional
plumbing and drainage facilities or shall make
such repairs or alterations as may be ordered by
the Authority Having Jurisdiction.
101.5.3 Existing Installation. Plumbing
systems lawfully in existence at the time of the
adoption of this code may have their use,
maintenance, or repair continued if the use,
maintenance, or repair is in accordance with the
original design and location and no hazard to
life, health, or property has been created by
such plumbing system.
101.5.4 Changes in Building Occupancy.
Plumbing systems that are a part of any
building or structure undergoing a change in use
or occupancy, as defined in the Building Code,
shall comply to all requirements of this code that
may be applicable to the new use or occupancy.
101.5.5 Maintenance. All plumbing systems,
materials, and appurtenances, both existing and
new, and all parts thereof shall be maintained in
proper operating condition. All devices or safe-
guards required by this code shall be maintained
in conformance with the code edition under
which installed. The owner or the owner's
designated agent shall be responsible for mainte-
nance of plumbing systems. To determine
compliance with this subsection, the Authority
Having Jurisdiction may cause any plumbing
system to be reinspected.
101.5.6 Moved Buildings. Plumbing systems
that are part of buildings or structures moved
into this jurisdiction shall comply with the
provisions of this code for new installations,
except as provided for in Section 103.5.5.2.
102.0 Organization and Enforcement.
102.1 Authority Having Jurisdiction.
The Authority Having Jurisdiction shall be the
Authority duly appointed to enforce this code.
102.2 Duties and Powers of the Authority Having
Jurisdiction.
102.2.1 The Authority Having Jurisdiction may
appoint such assistants, deputies, inspectors, or
other employees as necessary to carry out the
functions of the department and this code.
102.2.2 Right of Entry. Whenever it is
necessary to make an inspection to enforce the
provisions of this code, or whenever the
Authority Having Jurisdiction has reasonable
cause to believe that there exists in any building
or upon any premises any condition or violation
of this code that makes the building or premises
unsafe, insanitary, dangerous, or hazardous, the
Authority Having Jurisdiction may enter the
building or premises at all reasonable times to
inspect or to perform the duties imposed upon
the Authority Having Jurisdiction by this code,
provided that if such building or premises is
occupied, the Authority Having Jurisdiction
shall present credentials to the occupant and
request entry. If such building or premises is
unoccupied, the Authority Having Jurisdiction
shall first make a reasonable effort to locate the
owner or other person having charge or control
of the building or premises and request entry. If
entry is refused, the Authority Having Juris-
diction has recourse to every remedy provided
by law to secure entry.
When the Authority Having Jurisdiction
shall have first obtained a proper inspection
warrant or other remedy provided by law to
secure entry, no owner, occupant, or person
having charge, care, or control of any building or
premises shall fail or neglect, after proper
request is made as herein provided, to promptly
permit entry herein by the Authority Having
Jurisdiction for the purpose of inspection and
examination pursuant to this code.
102.2.3 Stop Orders. Whenever any work is
being done contrary to the provisions of this
code, the Authority Having Jurisdiction may
order the work stopped by notice in writing
served on any persons engaged in the doing or
causing such work to be done, and any such
persons shall forthwith stop work until
authorized by the Authority Having Jurisdiction
to proceed with the work.
102.2.4 Authority to Disconnect Utilities in
Emergencies. The Authority Having Jurisdiction
shall have the authority to disconnect a plumbing
system to a building, structure, or equipment
regulated by this code in case of emergency
where necessary to eliminate an immediate
hazard to life or property.
ADMINISTRATION
102.2-103.2
102.2.5 Authority to Condemn. Whenever the
Authority Having Jurisdiction ascertains that
any plumbing system or portion thereof,
regulated by this code, has become hazardous
to life, health, or property, or has become
insanitary, the Authority Having Jurisdiction
shall order in writing that such plumbing either
be removed or placed in a safe or sanitary
condition, as appropriate. The order shall fix a
reasonable time limit for compliance. No person
shall use or maintain defective plumbing after
receiving such notice.
When such plumbing system is to be
disconnected, written notice shall be given. In
cases of immediate danger to life or property,
such discormection may be made immediately
without such notice.
102.2.6 Liability. The Authority Having
Jurisdiction charged with the enforcement of this
code, acting in good faith and without malice in
the discharge of the Authority Having Jurisdiction's
duties, shall not thereby be rendered personally
liable for any damage that may accrue to
persons or property as a result of any act or by
reason of any act or omission in the discharge of
duties. A suit brought against the Authority
Having Jurisdiction or employee because of such
act or omission performed in the enforcement of
any provision of this code shall be defended by
legal counsel provided by this jurisdiction until
final termination of such proceedings.
102.3 Violations and Penalties.
102.3.1 Violations. It shall be unlawful for any
person, firm, or corporation to erect, construct,
enlarge, alter, repair, move, improve, remove,
convert, demolish, equip, use, or maintain any
plumbing or permit the same to be done in
violation of this code.
102.3.2 Penalties. Any person, firm, or cor-
poration violating any provision of this code
shall be deemed guilty of a misdemeanor, and
upon conviction thereof, shall be punishable by
a fine and /or imprisonment set forth by the
governing laws of the jurisdiction. Each separate
day or any portion thereof, during which any
violation of this code occurs or continues, shall
be deemed to constitute a separate offense.
103.0 Permits and Inspections.
103.1 Permits.
103.1 .1 Permits Required. It shall be unlawful
for any person, firm, or corporation to make any
installation, alteration, repair, replacement, or
remodel any plumbing system regulated by this
code except as permitted in Section 103.1.2, or to
cause the same to be done without first obtaining
a separate plumbing permit for each separate
building or structure.
103.1.2 Exempt Work. A permit shall not be
required for the following:
103.1.2.1 The stopping of leaks in drains,
soil, waste, or vent pipe, provided, however,
that should any trap, drainpipe, soil, waste,
or vent pipe become defective and it
becomes necessary to remove and replace
the same with new material, the same shall
be considered as new work and a permit
shall be procured and inspection made as
provided in this code.
103.1.2.2 (1) The clearing of stoppages,
including the removal and reinstallation of
water closets, or
(2) the repairing of leaks ki pipes, valves, or
fixtures, provided such repairs do not
involve or require the replacement or
rearrangement of valves, pipes, or fixtures.
Exemption from the permit requirements
of this code shall not be deemed to grant
authorization for any work to be done in
violation of the provisions of the code or
any other laws or ordinances of this
jurisdiction.
1 03.1 .3 Licensing. Provision for licensing shall be
determined by the Authority Having Jurisdiction.
103.2 Application for Permit.
103.2.1 Application. To obtain a permit, the
applicant shall first file an application therefore
in writing on a form furnished by the Authority
Having Jurisdiction for that purpose. Every such
application shall:
103.2.1.1 Identify and describe the work to
be covered by the permit for which
application is made.
103.2.1.2 Describe the land upon which the
proposed work is to be done by legal
description, street address, or similar
description that will readily identify
and definitely locate the proposed building
or work.
103.2.1.3 Indicate the use or occupancy for
which the proposed work is intended.
103.2.1.4 Be accompanied by plans, dia-
grams, computations, and other data as
required in Section 103.2.2.
1 03.2.1 .5 Be signed by the permittee or the
permittee's authorized agent, who may be
103.2-103.3
UNIFORM PLUMBING CODE
required to submit evidence to indicate such
authority.
103.2.1 .6 Give such other data and information
as may be required by the Authority Having
Jurisdiction.
103.2.2 Plans and Specifications. Plans,
engineering calculations, diagrams, and other
data shall be submitted in one or more sets with
each application for a permit. The Authority
Having Jurisdiction may require plans,
computations, and specifications to be prepared
by, and the plumbing designed by, an engineer
and /or architect licensed by the state to practice
as such.
Exception: The Authority Having Jurisdiction
may waive the submission of plans, calcu-
lations, or other data if the Authority
Having Jurisdiction finds that the nature of
the work applied for is such that reviewing
of plans is not necessary to obtain com-
pliance within the code.
103.2.3 Information on Plans and Specifications.
Plans and specifications shall be drawn to scale
upon substantial paper or cloth and shall be of
sufficient clarity to indicate the location, nature,
and extent of the work proposed and show in
detail that it will conform to the provisions of
this code and relevant laws, ordinances, rules,
and regulations.
103.3 Permit Issuance.
103.3.1 Issuance. The application, plans, and
specifications and other data filed by an
applicant for a permit shall be reviewed by the
Authority Having Jurisdiction. Such plans may
be reviewed by other departments of this
jurisdiction to verify compliance with applicable
laws under their jurisdiction. If the Authority
Having Jurisdiction finds that the work
described in an application for permit and
the plans, specifications, and other data filed
therewith conform to the requirements of the
code and other pertinent laws and ordinances,
and that the fees specified in Section 103.4 have
been paid, the Authority Having Jurisdiction
shall issue a permit therefore to the applicant.
When the Authority Having Jurisdiction
issues the permit where plans are required, the
Authority Having Jurisdiction shall endorse in
writing or stamp the plans and specifications
"APPROVED." Such approved plans and
specifications shall not be changed, modified, or
altered without authorization from the
Authority Having Jurisdiction, and all work
shall be done in accordance with approved plans.
The Authority Having Jurisdiction may
issue a permit for the construction of a part of a
plumbing system before the entire plans and
specifications for the whole system have been
submitted or approved, provided adequate
information and detailed statements have been
filed complying with all pertinent requirements
of this code. The holder of such permit may
proceed at the holder's risk without assurance
that the permit for the entire building, structure,
or plumbing system will be granted.
103.3.2 Retention of Plans. One set of
approved plans, specifications, and computations
shall be retained by the Authority Having
Jurisdiction until final approval of the
work covered therein. One set of approved plans
and specifications shall be returned to the
applicant, and said set shall be kept on the site of
the building or work at all times during which
the work authorized thereby is in progress.
103.3.3 Validity of Permit. The issuance of a
permit or approval of plans and specifications
shall not be construed to be a permit for, or an
approval of, any violation of any of the
provisions of this code or of any other ordinance
of the jurisdiction. No permit presuming to give
authority to violate or cancel the provisions of
this code shall be valid.
The issuance of a permit based upon plans,
specifications, or other data shaiU not prevent the
Authority Having Jurisdiction from thereafter
requiring the correction of errors in said plans,
specifications, and other data or from preventing
building operations being carried on thereunder
when in violation of this code or of other
ordinances of this jurisdiction.
103.3.4 Expiration. Every permit issued by the
Authority Having Jurisdiction under the
provisions of this code shall expire by limitation
and become null and void if the work authorized
by such permit is not commenced within one
hundred eighty (180) days from the date of such
permit, or if the work authorized by such permit
is suspended or abandoned at any time after the
work is commenced for a period of one hundred
eighty (180) days. Before such work can be
recommenced, a new permit shall first be
obtained to do so, and the fee therefore shall be
one-half the amount required for a new
permit for such work, provided no changes have
been made or will be made in the original plans
and specifications for such work, and provided
further that such suspensions or abandonment
has not exceeded one year.
ADMINISTRATION
103.3-103.5
Any permittee holding an unexpired permit
may apply for an extension of the time within
which work may commence under that permit
when the permittee is unable to commence work
within the time required by this section for good
and satisfactory reasons. The Authority Having
Jurisdiction may extend the time for action by
the permittee for a period not exceeding one
hundred eighty (180) days upon written request
by the permittee showing that circumstances
beyond the control of the permittee have
prevented action from being taken. No permit
shall be extended more than once. In order to
renew action on a permit after expiration, the
permittee shall pay a new full permit fee.
103.3.5 Suspension or Revocation. The
Authority Having Jurisdiction may, in writing,
suspend or revoke a permit issued under the
provisions of this code whenever the permit is
issued in error or on the basis of incorrect
information supplied or in violation of other
ordinance or regulation of the jurisdiction.
103.4 Fees.
103.4.1 Permit Fees. Fees shall be assessed in
accordance with the provisions of this section
and as set forth in the fee schedule Table 1-1. The
fees are to be determined and adopted by this
jurisdiction.
103.4.2 Plan Review Fees. When a plan or
other data is required to be submitted by Section
103.2.2, a plan review fee shall be paid at the
time of submitting plans and specifications for
review.
The plan review fees for plumbing work shall
be determined and adopted by this jurisdiction.
The plan review fees specified in this
subsection are separate fees from the permit fees
specified in this section and are in addition to
the permit fees.
When plans are incomplete or changed so as
to require additional review, a fee shall be
charged at the rate shown in Table 1-1.
103.4.3 Expiration of Plan Review. Applications
for which no permit is issued within one
hundred eighty (180) days following the date of
application shall expire by limitation, and plans
and other data submitted for review may
thereafter be returned to the applicant or
destroyed by the Authority Having Jurisdiction.
The Authority Having Jurisdiction may exceed
the time for action by the applicant for a period
not to exceed one hundred eighty (180) days
upon request by the applicant showing that
circumstances beyond the control of the
applicant have prevented action from being
taken. No application shall be extended more
than once. In order to renew, action on an
application after expiration, the applicant shall
resubmit plans and pay a new plan review fee.
103.4.4 Investigation Fees: Work Without a
Permit.
103.4.4.1 Whenever any work for which a
permit is required by this code has been
commenced without first obtaining said
permit, a special investigation shall be made
before a permit may be issued for such work.
103.4.4.2 An investigation fee, in addition
to the permit fee, shall be collected whether
or not a permit is then or subsequently
issued. The investigation fee shall be equal
to the amount of the permit fee that would
be required by this code if a permit were to
be issued. The payment of such investigation
fee shall not exempt any person from
compliance with all other provisions of this
code, nor from any penalty prescribed by law.
103.4.5 Fee Refunds.
103.4.5.1 The Authority Having Jurisdiction
may authorize the refunding of any fee paid
hereunder that was erroneously paid or
collected.
1 03.4.5.2 The Authority Having Jurisdiction
may authorize the refunding of not more
than a percentage, as determined by this
jurisdiction when no work has been done
under a permit issued in accordance with
this code.
1 03.4.5.3 The Authority Having Jurisdiction
shall not authorize the refunding of any fee
paid except upon written application filed
by the original permittee not later than one
hundred eighty (180) days after the date of
fee payment.
103.5 Inspections.
103.5.1 General. All plumbing systems for
which a permit is required by this code shall be
inspected by the Authority Having Jurisdiction.
No portion of any plumbing system shall be
concealed until inspected and approved. Neither
the Authority Having Jurisdiction nor the
jurisdiction shall be liable for expense entailed in
the removal or replacement of material required
to permit inspection. When the installation of a
plumbing system is complete, an additional and
final inspection shall be made. Plumbing
systems regulated by this code shall not be
connected to the water, the energy fuel supply.
103.5
UNIFORM PLUMBING CODE
or the sewer system uritil authorized by the
Authority Having Jurisdiction.
103.5.1.1 Inspection. No water supply
system or portion thereof shall be covered or
concealed until it first has been tested,
inspected, and approved.
103.5.1.2 Scope. All new plumbing work
and such portions of existing systems as
may be affected by new work, or any
changes, shall be inspected by the Authority
Having Jurisdiction to ensure compliance
with all the requirements of this code and
to ensure that the installation and construc-
tion of the plumbing system is in accordance
with approved plans.
103.5.1.3 Covering or Using. No plumbing
or drainage system, building sewer, private
sewer disposal system, or part thereof, shall be
covered, concealed, or put into use until it has
been tested, inspected, and accepted as
prescribed in this code.
103.5.1.4 Uncovering. If any drainage or
plumbing system, building sewer, private
sewage disposal system, or part thereof,
which is installed, altered, or repaired, is
covered or concealed before being inspected,
tested, and approved as prescribed in this
code, it shall be uncovered for inspection
after notice to uncover the work has been
issued to the responsible person by the
Authority Having Jurisdiction.
103.5.2 Operation of Plumbing Equipment.
The requirements of this section shall not be
considered to prohibit the operation of any
plumbing installed to replace existing equipmient
or fixtures serving an occupied portion of the
building in the event a request for inspection of
such equipment or fixture has been filed with
the Authority Having Jurisdiction not more than
seventy-two (72) hours after such replacement
work is completed, and before any portion of
such plumbing system is concealed by any
permanent portion of the building.
103.5.3 Testing of Systems. All plumbing
systems shall be tested and approved as
required by this code or the Authority Having
Jurisdiction.
103.5.3.1 Test. Tests shall be conducted in
the presence of the Authority Having
Jurisdiction or the Authority Having
Jurisdiction's duly appointed representative.
103.5.3.2 Test Waived. No test or inspection
shall be required where a plumbing system,
or part thereof, is set up for exhibition
purposes and has no connection with a
water or drainage system.
103.5.3.3 Exceptions. In cases where it
would be impractical to provide the required
water or air tests, or for minor installations
and repairs, the Authority Having Jurisdiction
may make such inspection as deemed
advisable in order to be assured that the
work has been performed in accordance
with the intent of this code.
103.5.3.4 Protectively Coated Pipe.
Protectively coated pipe shall be inspected
and tested, and any visible void, damage, or
imperfection to the pipe coating shall be
repaired to comply with Section 313.0 (see
lAPMO IS-13, Hsted in Appendix I).
103.5.3.5 Tightness. Joints and connections
in the plumbing system shall be gastight
and watertight for the pressures required by
test.
103.5.4 Inspection Requests. It shall be the
duty of the person doing the work authorized by
a permit to notify the Authority . Having
Jurisdiction that such work is ready for
inspection. The Authority Having Jurisdiction
may require that every request for inspection be
filed at least one working day before such
inspection is desired. Such request may be in
writing or by telephone, at the option of the
Authority Having Jurisdiction.
It shall be the duty of the person requesting
inspections required by this code to provide
access to and means for proper inspection of
such work.
103.5.4.1 Advance Notice. It shall be
the duty of the person doing the work
authorized by the permit to notify the
Authority Having Jurisdiction, orally or
in writing, that said work is ready for
inspection. Such notification shall be
given not less than twenty-four (24)
hours before the work is to be inspected.
103.5.4.2 Responsibility. It shall be the
duty of the holder of a permit to make sure
that the work will stand the test prescribed
before giving the notification.
The equipment, material, and labor
necessary for inspection or tests shall be
furnished by the person to whom the
permit is issued or by whom inspection
is requested.
103.5.5 Other Inspections. In addition to
the inspections required by this code, the
ADMINISTRATION
103.5 -103.8
Authority Having Jurisdiction may require
other inspections of any plumbing work to
ascertain compliance with the provisions of
this code and other laws that are enforced
by the Authority Having Jurisdiction.
103.5.5.1 Defective Systems. An air test
shall be used in testing the sanitary condition
of the drainage or plumbing system of any
building premises when there is reason to
believe that it has become defective. In
buildings or premises condemned by the
proper Authority Having Jurisdiction
because of an insanitary condition of the
plumbing system or part thereof, the
alterations in such system shall conform to
the requirements of this code.
103.5.5.2 Moved Structures. All parts
of the plumbing systems of any building or
part thereof that is moved from one founda-
tion to another, or from one location to another,
shall be completely tested as prescribed
elsewhere in this section for new work, except
that walls or floors need not be removed
during such test when other equivalent
means of inspection acceptable to the
Authority Having Jurisdiction are provided.
103.5.6 ReJnspections. A reinspection fee
may be assessed for each inspection or reins-
pection when such portion of work for which
inspection is called is not complete or when
required corrections have not been made.
This provision is not to be interpreted as
requiring reinspection fees the first time a
job is rejected for failure to comply with the
requirements of this code, but as controlling
the practice of calling for inspections before
the job is ready for inspection or reinspection.
Reinspection fees may be assessed when the
approved plans are not readily available
to the inspector, for failure to provide access on
the date for which the inspection is requested, or
for deviating from plans requiring the approval
of the Authority Having Jurisdiction.
To obtain reinspection, the applicant shall
file an application therefore in writing upon a
form furnished for that purpose and pay the
reinspection fee in accordance with Table 1-1.
In instances where reinspection fees have
been assessed, no additional inspection of the
work will be performed until the required fees
have been paid.
103.5.6.1 Corrections. Notices of correction
or violation shall be written by the Authority
Having Jurisdiction and may be posted at the
site of the work or mailed or delivered to the
permittee or his authorized representative.
Refusal, failure, or neglect to comply
with any such notice or order within ten
(10) days of receipt thereof, shall be
considered a violation of this code and
shall be subject to the penalties set forth
elsewhere in this code for violations.
103.5.6.2 Retesting. If the Authority
Having Jurisdiction finds that the work
will not pass the test, necessary corrections
shall be made, and the work shall then be
resubmitted for test or inspection.
103.5.6.3 Approval. Upon the satisfactory
completion and final test of the plumbing
system, a certificate of approval shall be
issued by the Authority Having Jurisdiction
to the permittee on demand.
103.6 Connection Approval.
103.6.1 Energy Connections. No person shall
make connections from a source of energy or
fuel to any plumbing system or equipment
regulated by this code and for which a permit is
required until approved by the Authority
Having Jurisdiction.
103.6.2 Other Connections. No person shall
make connection from any water-supply line nor
shall cormect to any sewer system regulated by
this code and for which a permit is required until
approved by the Authority Having Jurisdiction.
103.6.3 Temporary Connections. The Authority
Having Jurisdiction may authorize temporary
connection of the plumbing equipment to the
source of energy or fuel for the purpose of
testing the equipment.
103.7 Unconstitutional.
103.7.1 If any section, subsection, sentence,
clause, or phrase of this code is, for any reason,
held to be unconstitutional, siich decision shall
not affect the validity of the remaining portions
. of this code. The Legislative body hereby
declares that it would have passed this code, and
each section, subsection, sentence, clause, or
phrase thereof, irrespective of the fact that
one or more sections, subsections, sentences,
clauses, and phrases are declared
unconstitutional.
103.8 Validity
103.8.1 If any provision of this code, or the
application thereof to any person or circimistance,
is held invalid, the remainder of the code, or the
application of such provision to other persons or
circumstances, shall not be affected thereby.
103.8 UNIFORM PLUMBING CODE
1 03.8.2 Wherever in this code reference is made
to an appendix, the provisions in the appendix
shall not apply unless specifically adopted.
ADMINISTRATION Table 1-1
TABLE 1-1
Plumbing Permit Fees
Permit Issuance
1. For issuing each permit *
2. For issuing each supplemental permit *
Unit Fee Schedule (in addition to items 1 and 2 above)
1 . For each plumbing fixture on one trap or a set of fixtures on one trap (including water,
drainage piping, and backflow protection therefore) ....*
2. For each building sewer and each trailer park sewer *_
3. Rainwater systems - per drain (inside building) *
4. For each cesspool (where permitted) *
5. For each private sewage disposal system *
6. For each water heater and/or vent *
7. For each gas piping system of one to five outlets *
8. For each additional gas piping system outlet, per outlet *
9. For each industrial waste pretreatment interceptor, including its trap and vent,
except kitchen-type grease interceptors functioning as fixture traps *
10. For each installation, alteration, or repair of water piping and/or water treating equipment, each ..*
11. For each repair or alteration of drainage or vent piping, each fixture *
12. For each lawn sprinkler system on any one meter including backflow protection devices therefore ...*
13. For atmospheric-type vacuum breakers not included in item 12:
1 to 5 *
overs, each *
14. For each backflow protective device other than atmospheric-type vacuum breakers:
2 inch (51 mm) diameter and smaller *
over 2 inch (51 mm) diameter *
15. For each graywater system *
16. For initial installation and testing for a reclaimed water system *
17. For each annual cross-connection testing of a reclaimed water system (excluding initial test) *
18. For each medical gas piping system serving one to five inlet(s)/outlet(s) for a specific gas *
19. For each additional medical gas inlet(s)/outlet(s) *
Other Inspections and Fees
1 . Inspections outside of normal business hours
2. Reinspection fee
3. Inspections for which no fee is specifically indicated
4. Additional plan review required by changes, additions, or
revisions to approved plans (minimum charge - one-half hour).
* Jurisdiction will indicate their fees here.
UNIFORM PLUMBING CODE
10
CHAPTER 2
DEFINITIONS
201.0 General.
For the purpose of this code, the following terms
have the meanings indicated in this chapter.
No attempt is made to define ordinary words,
which are used in accordance with their established
dictionary meanings, except where a word has been
used loosely and it is necessary to define its meaning
as used in this code to avoid misunderstanding.
The definitions of terms are arranged alphabe-
tically according to the first word of the term.
202.0 Definition of Terms.
203.0
-A-
ABS - Acrylonitrile-butadiene-styrene.
Accessible - When applied to a fixture, connection,
appliance, or equipment, "accessible" means having
access thereto, but which first may require the
removal of an access panel, door, or similar
obstruction. "Readily accessible" means direct access
without the necessity of removing any panel, door,
or similar obstruction.
Airbreak - A physical separation which may be a
low inlet into the indirect waste receptor from the
fixture, appliance, or device indirectly connected.
Air Chamber - A pressure surge-absorbing device
operating through the compressibility of air.
Airgap, Drainage - The unobstructed vertical
distance through the free atmosphere between the
lowest opening from any pipe, plumbing fixture,
appliance, or appurtenance conveying waste to the
flood-level rim of the receptor.
Airgap, Water Distribution - The unobstructed
vertical distance through the free atmosphere
between the lowest opening from any pipe or faucet
conveying potable water to the flood-level rim of any
tartk, vat, or fixture.
Anchors - See Supports.
Approved - Acceptable to the Authority Having
Jurisdiction.
Approved Testing Agency - An organization
primarily established for purposes of testing to
approved standards and approved by the Authority
Having Jurisdiction.
Area Drain - A receptor designed to collect surface
or storm water from an open area.
Aspirator - A fitting or device supplied with water
or other fluid under positive pressure that passes
through an integral orifice or constriction, causing a
vacuum.
Authority Having Jurisdiction - The organization,
office, or individual responsible for enforcing the
requirements of a code or standard, or for approving
equipment, materials, installations, or procedures.
The Authority Having Jurisdiction shall be a federal,
state, local, or other regional department or an
individual such as a plumbing official, mechanical
official, labor department official, health department
official, building official, or others having statutory
authority. In the absence of a statutory authority, the
Authority Having Jurisdiction may be some other
responsible party. This definition shall include the
Authority Having Jurisdiction's duly authorized
representative.
204.0 - B -
Backflow - The flow of water or other liquids,
mixtures, or substances into the distributing pipes of
a potable supply of water from any sources other
than its intended source. See Back-Siphonage, Back-
Pressure Backflow.
Backflow Connection - Any arrangement whereby
backflow can occur.
Back-Pressure Backflow - Backflow due to an
increased pressure above the supply pressure, which
may be due to pumps, boilers, gravity, or other
sources of pressure.
Backflow Preventer - A device or means to prevent
backflow into the potable water system.
Back-Siphonage - The flowing back of used,
contaminated, or polluted water from a plumbing
fixture or vessel into a water supply pipe due to a
pressure less than atmospheric in such pipe. See
Backflow.
Backwater Valve - A device installed in a drainage
system to prevent reverse flow.
Bathroom - A room equipped with a shower or
bathtub.
Battery of Fixtures - Any group of two (2) or more
similar, adjacent fixtures that discharge into a
common horizontal waste or soil branch.
Boiler Blowoff - An outlet on a boiler to permit
emptying or discharge of sediment.
Branch - Any part of the piping system other than a
main, riser, or stack.
11
204.0 - 205.0
UNIFORM PLUMBING CODE
Branch, Fixture - See Fixture Branch.
Branch, Horizontal - See Horizontal Branch.
Branch Vent - A vent connecting one or more
individual vents with a vent stack or stack vent.
Building - A structure built, erected, and framed of
component structural parts designed for the housing,
shelter, enclosure, or support of persons, animals, or
property of any kind.
Building Drain - That part of the lowest piping of a
drainage system that receives the discharge from
soil, waste, and other drainage pipes inside the walls
of the building and conveys it to the building sewer
begiiming two (2) feet (610 mm) outside the building
wall.
Building Drain (Sanitary) - A building drain that
conveys sewage only.
Building Drain (Storm) - A building drain that
conveys storm water or other drainage, but no
sewage.
Building Sewer - That part of the horizontal piping
of a drainage system that extends from the end of the
building drain and that receives the discharge of the
building drain and conveys it to a public sewer,
private sewer, private sewage disposal system, or
other point of disposal.
Building Sewer (Combined) - A building sewer
that conveys both sewage and storm water or other
drainage.
Building Sewer (Sanitary) - A building sewer that
conveys sewage only.
Building Sewer (Storm) - A building sewer that
conveys storm water or other drainage, but no
sewage.
Building Subdrain - That portion of a drainage
system that does not drain by gravity into the
building sewer.
Building Supply - The pipe carrying potable water
from the water meter or other source of water supply
to a building or other point of use or distribution on
the lot. Building supply shall also mean water service.
205.0
-C-
Certified Baclcflow Assembly Tester - A person
who has shown competence to test and maintain
backflow assemblies to the satisfaction of the
Authority Having Jurisdiction.
Cesspool - A lined excavation in the ground that
receives the discharge of a drainage system or part
thereof, so designed as to retain the organic matter
and solids discharging therein, but permitting the
liquids to seep through the bottom and sides.
Chemical Waste - See Special Wastes.
Clarif ier - See Interceptor.
Clear Water Waste - Cooling water and condensate
drainage from refrigeration and air-conditioning
equipment; cooled condensate from steam heating
systems; cooled boiler blowdown water.
Clinic Sinl< - A sink designed primarily to receive
wastes from bedpans and having a flush rim, an
integral trap with a visible trap seal, and the same
flushing and cleansing characteristics as a water
closet.
Code - A standard that is an extensive compilation
of provisions covering broad subject matter or that is
suitable for adoption into law independently of other
codes and standards.
Combination Thermostatic/Pressure Balancing
Valve - A mixing valve that senses outlet tempera-
ture and incoming hot and cold water pressure and
compensates for fluctuations in incoming hot and
cold water temperatures and/or pressures to
stabilize outlet temperatures.
Combination Waste and Vent System - A specially
designed system of waste piping embodying the
horizontal wet venting of one or more sinks or floor
drains by nieans of a comnion waste and vent pipe,
adequately sized to provide free movement of air
above the flow line of the drain.
Combined Building Sewer - See Building Sewer
(Combined).
Common - That part of a plumbing system that is so
designed and installed as to serve more than one (1)
appliance, fixture, building, or system.
Conductor - A pipe inside the building that conveys
storm water from the roof to a storm drain,
combined building sewer, or other approved point of
disposal.
Confined Space - A room or space having a volume
less than fifty (50) cubic feet per 1,000 Btu/h (1.4
mV293 W) of the aggregate input rating of all fuel-
burning appliances installed in that space.
Contamination - An impairment of the quality of
the potable water that creates an actual hazard to the
public health through poisoning or through the
spread of disease by sewage, industrial fluids, or
waste. Also defined as High Hazard.
Continuous Vent - A vertical vent that is a
continuation of the drain to which it connects.
Continuous Waste - A drain connecting the
compartments of a set of fixtures to a trap or
connecting other permitted fixtures to a common trap.
CPVC - Chlorinated Poly (Vinyl Chloride).
Critical Level - The critical level (C-L or C/L)
marking on a backflow prevention device or vacuum
breaker is a point conforming to approved standards
12
DEFINITIONS
205.0 - 208.0
TIA
TIA
TIA
FIA
lA
and established by the testing laboratory (usually
stamped on the device by the manufacturer) that
determines the minimum elevation above the flood-
level rim of the fixture or receptor served at which
the device may be installed. When a backflow
prevention device does not bear a critical level
marking, the bottom of the vacuum breaker,
combination valve, or the bottom of any such
approved device shall constitute the critical level.
Cross-Connection - Any connection or
arrangement, physical or otherwise, between a
potable water supply system and any plumbing
fixture or any tank, receptor, equipment, or device,
through which it may be possible for non potable,
used, unclean, polluted, and contaminated water, or
other substances to enter into any part of such
potable water system under any condition.
207.0
-E-
206.0
-D
Department Having Jurisdiction - The Authority
Having Jurisdiction, including any other law
enforcement agency affected by any provision of
this code, whether such agency is specifically named
or not.
Design Flood Elevation - The elevation of the
"design flood," including wave height, relative to the
datum specified on the community's legally
designated flood hazard map.
Developed Length - The length along the center
line of a pipe and fittings.
Diameter - Unless specifically stated, "diameter" is
the nominal diameter as designated commercially.
Domestic Sewage - The liquid and water-borne
wastes derived from the ordinary living processes,
free from industrial wastes, and of such character as
to permit satisfactory disposal, without special
treatment, into the public sewer or by means of a
private sewage disposal system.
Downspout - The rain leader from the roof to the
building storm drain, combined building sewer, or
other means of disposal located outside of the
building. See Conductor and Leader.
Drain - Any pipe that carries waste or waterborne
wastes in a building drainage system.
Drainage System - Includes all the piping within
public or private premises that conveys sewage or
other liquid wastes to a legal point of disposal, but
does not include the mains of a public sewer system
or a public sewage treatment or disposal plant.
Durham System - A soil or waste system in which
all piping is threaded pipe, tubing, or other such
rigid construction, using recessed drainage fittings to
correspond to the types of piping.
Effective Opening - The minimum cross-sectional
area at the point of water supply discharge measured
or expressed in terms of (1) diameter of a circle or. (2)
if the opening is not circular, the diameter of a circle
of equivalent cross-sectional area. (This is applicable
also to airgap.)
Essentially Nontoxic Transfer Fluid - Essentially
nontoxic at practically nontoxic. Toxicity Rating Class
1 (reference "Clinical Toxicology of Commercial
Products" by Gosselin, Smith, Hodge, & Braddock).
Excess Flow Valve - A valve designed to close
when the fuel gas passing through exceeds a
prescribed flow rate.
Existing Work - A plumbing system or any part
thereof that has been installed prior to the effective
date of this code.
208.0
>F-
Fixture Branch - A water supply pipe between the
fixture supply pipe and the water distributing pipe.
Fixture Drain - The drain from the ti-ap of a fixture to
the junction of that drain with any other drain pipe.
Fixture Supply - A water supply pipe connecting
the fixture with the fixture branch.
Fixture Unit - A quantity in terms of which the load-
producing effects on the plumbing system of
different kinds of plumbing fixtures are expressed on
some arbitrarily chosen scale.
Flammable Vapor or Fumes is the concentration of
flammable constituents in air that exceeds 25 percent
of its lower flammability limit (LFL).
Flood Hazard Area - The greater of the following
two areas:
1. The area within a floodplain subject to a 1
percent or greater chance of flooding in any
given year.
2. The area designated as a flood hazard area
on a community's flood hazard map, or
otherwise legally designated.
Flood Hazard Area Subject to High Velocity Wave
Action - Area within the flood hazard area that is
subject to high velocity wave action, and shown on a
Flood Insurance Rate Map or other flood hazard map
as Zone V, VO, VE or Vl-30.
Flood Level - See Flooded.
Flood-Level Rim - The top edge of a receptor from
which water overflows.
Flooded - A fixture is flooded when the liquid
therein rises to the flood-level rim.
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
13
208.0-211.0
UNIFORM PLUMBING CODE
Flush Tank - A tank located above or integral with
water closets, urinals, or similar fixtures for the
purpose of flushing the usable portion of the fixture.
Flush Valve - A valve located at the bottom of a
tank for the purpose of flushing water closets and
similar fixtures.
Flushometer Tank - A tank integrated within an air
accumulator vessel that is designed to discharge a
predetermined quantity of water to fixtures for
flushing purposes.
Flushometer Valve - A valve that discharges a
predetermined quantity of water to fixtures for
flushing purposes and is actuated by direct water
pressure.
FOG Disposal System - A grease interceptor that
reduces nonpetroleum fats, oils, and grease (FOG) in
effluent by separation, and mass and volume
reduction.
209.0 - G -
Gang or Group Shower - Two or more showers in a
common area.
Grade - The slope or fall of a line of pipe in reference
to a horizontal plane. In drainage, it is usually
expressed as the fall in a fraction of an inch (mm) or
percentage slope per foot (meter) length of pipe.
Gravity Grease Interceptor - A plumbing
appurtenance or appUance that is installed in a sanitary
drainage system to intercept nonpetroleum fats, oils,
and greases (FOG) from a wastewater discharge and is
identified by volume, 30-minute retention time,
baffle(s), a minimum of two compartments, a
minimum total volume of 300 gallons, and gravity
separation. [These interceptors comply with the
requirements of Chapter 10 or are designed by a
registered professional engineer.] Gravity grease
interceptors are generally installed outside.
Grease Interceptor - A plumbing appurtenance or
appliance that is installed in a sanitary drainage
system to intercept nonpertroleuni fats, oil, and
greases (FOG) from a wastewater discharge.
Grease Removal Device (GRD) - Any hydro-
mechanical grease interceptor that automatically,
mechanically removes non-petroleum fats, oils and
grease (FOG) from the interceptor, the control of
which are either automatic or manually initiated.
Grease Trap - A device designed to retain grease from
one (1) to a maximum of four (4) fixtures. This term has
been used in previous editions of this code. Refer to
Hydromechanical Grease Interceptor and Gravity
Grease Interceptor, GRD, and FOG disposal system.
210.0
-H
Hangers - See Supports.
High Hazard - See Contamination.
Horizontal Branch - A drain pipe extending
laterally from a soil or waste stack or building drain
with or without vertical sections or branches, which
receives the discharge from one or more fixture
drains and conducts it to the soil or waste stack or to
the building drain.
Horizontal Pipe - Any pipe or fitting that is installed
in a horizontal position or which makes an angle of
less than forty-five (45) degrees with the horizontal.
Hot Water - Water at a temperature greater than or I
equal to 120T (49°C). I
House Drain - See Building Drain.
House Sewer - See Building Sewer.
Hydromechanical Grease Interceptor - A
plumbing appurtenance or appliance that is installed
in a sanitary drainage system to intercept
nonpetroleum fats, oil, and grease (FOG) from a
wastewater discharge and is identified by flow rate,
and separation and retention efficiency. The design
incorporates air entrainment, hydromechanical
separation, interior baffling, and /or barriers in
combination or separately, and one of the following:
A - External flow control, with air intake (vent):
directly connected
B - External flow control, without air intake
(vent): directly connected
C - Without external flow control, directly
connected
D - Without external flow control, indirectly
connected
[These interceptors comply with the requirements of
Table 10-2.] Hydromechanical grease interceptors
are generally installed inside.
211.0
-I-
Indirect Waste Pipe - A pipe that does not connect
directly with the drainage system but conveys liquid
wastes by discharging into a plumbing fixture,
interceptor, or receptacle that is directly connected to
the drainage system.
Individual Vent - A pipe installed to vent a fixture
trap and that connects with the vent system above
the fixture served or terminates in the open air.
industrial Waste - Any and all liquid or water-
borne waste from industrial or commercial
processes, except domestic sewage.
Insanitary - A condition that is contrary to sanitary
principles or is injurious to health.
14
DEFINITIONS
211.0-215.0
Conditions to which "insanitary" shall apply
include the following:
(1) Any trap that does not maintain a proper
trap seal.
(2) Any opening in a drainage system, except
where lawful, that is not provided with an
approved water-sealed trap.
(3) Any plumbing fixture or other waste-
discharging receptor or device that is not
supplied with water sufficient to flush and
maintain the fixture or receptor in a clean
condition.
(4) Any defective fixture, trap, pipe, or fittiag.
(5) Any trap, except where in this code
exempted, directly cormected to a drainage
system, the seal of which is not protected
against siphonage and back-pressure by a
vent pipe.
(6) Any connection, cross-connection, construction,
or condition, temporary or permanent, that
would permit or make possible by any means
whatsoever for any imapproved foreign
matter to enter a water distribution system
used for domestic purposes.
(7) The foregoing enumeration of conditions to
which the term "insanitary" shall apply
shall not preclude the application of that
term to conditions that are, in fact, insanitary.
Interceptor (Clarifier) - A device designed and
installed so as to separate and retain deleterious,
hazardous, or undesirable matter from normal
wastes and permit normal sewage or liquid wastes to
discharge into the disposal terminal by gravity.
Invert -The lowest portion of the inside of a
horizontal pipe.
212.0 -J-
Joint, Brazed - Any joint obtained by joining of
metal parts with alloys that melt at temperatures
higher than 840°F (449°C), but lower than the
melting temperature of the parts to be joined.
Joint, Soldered - A joint obtained by the joining of
metal parts with metallic mixtures or alloys that melt at
a temperature up to and including 840°F (449°C).
214.0
-L-
213.0
No definitions
K-
Labeled - Equipment or materials bearing a label of
a listing agency (accredited conformity assessment
body). See Listed (third-party certified).
Lavatories in Sets - Two (2) or three (3) lavatories
that are served by one (1) trap.
Leader - An exterior vertical drainage pipe for
conveying storm water from roof or gutter drains.
See Downspout.
Liquid Waste - The discharge from any fixture,
appliance, or appurtenance in cormection with a
plumbing system that does not receive fecal matter.
Listed (Third-party certified) - Equipment or
materials included in a list published by a listing
agency (accredited conformity assessment body) that
maintains periodic inspection on current production
of listed equipment or materials and whose listing
states either that the equipment or material complies
with approved standards or has been tested and
found suitable for use in a specified manner.
Listing Agency - An agency accredited by an
independent and authoritative conformity
assessment body to operate a material and product
listing and labeling (certification) system and that is
accepted by the Authority Having Jurisdiction,
which is in the business of listing or labeling. The
system includes initial and ongoing product testing,
a periodic inspection on current production of listed
(certified) products, and makes available a published
report of such listing in which specific information is
included that the material or product conforms to
applicable standards and found safe for use in a
specific manner.
Lot - A single or individual parcel or area of land
legally recorded or validated by other means
acceptable to the Authority Having Jurisdiction on
which is situated a building or which is the site of
any work regulated by this code, together with the
yards, courts, and unoccupied spaces legally
required for the building or works, and that is
owned by or is in the lawful possession of the owner
of the building or works.
Low Hazard - See Pollution.
215.0 -M-
Macerating Toilet System - A system comprised of
a sump with macerating pump and with connections
for a water closet and other plumbing fixtures, which
is designed to accept, grind, and pump wastes to an
approved point of discharge.
IWain - The principal artery of any system of continuous
piping to which branches maybe coraiected.
15
215.0-218.0
UNIFORM PLUMBING CODE
Main Sewer - See Public Sewer.
Main Vent - The principal artery of the venting
system to which vent branches may be connected.
May - A permissive term.
Mobile Home Park Sewer - That part of the
horizontal piping of a drainage system that begins
two (2) feet (610 mm) downstream from the last
mobile home site and conveys it to a public sewer,
private sewer, private sewage disposal system, or
other point of disposal.
216.0 -N-
Nuisance - Includes, but is not limited to:
(1) Any public nuisance known at cormnon law
or in equity jurisprudence.
(2) Whenever any work regulated by this code
is dangerous to human life or is detrimental to
health and property.
(3) Inadequate or unsafe water supply or
sewage disposal system.
217.0 -O-
Offset - A conibination of elbows or bends in a line
of piping that brings one section of the pipe out of
line but into a line parallel with the other section.
Oil Interceptor - See Interceptor.
218.0
-P-
PB - Polybutylene.
PE - Polyethylene.
PE-AL-PE - Polyethylene-aluminum-polyethylene.
PEX - Cross-linked polyethylene.
PEX-AL-PEX - Cross-linked polyethylene —
aluininum-cross-linked polyethylene.
Person - A natural person, his heirs, executor,
administrators, or assigns and shall also include a
firm, corporation, municipal or quasi-municipal
corporation, or governmental agency. Singular
includes plural, male includes fen\ale.
Pipe - A cylindrical conduit or conductor
conforming to the particular dimensions commonly
known as "pipe size."
Plumbing - The business, trade, or work having to
do with the installation, removal, alteration, or repair
of plumbing systems or parts thereof.
Plumbing Appliance - Any one of a special class of
devices or equipment that is intended to perform a
special plumbing function. Its operation and /or
control may be dependent upon one or more
energized components, such as motors, controls,
heating elements, or pressure- or temperature-
sensing elements. Such device or equipment may
operate automatically through one or more of the
following actions: a time cycle, a temperature range,
a pressure range, a measured volume or weight; or
the device or equipment may be manually adjusted
or controlled by the user or operator.
Plumbing Appurtenance - A manufactured device,
a prefabricated assembly, or an on-the-job assembly
of component parts that is an adjunct to the basic
piping system and plumbing fixtures. An
appurtenance demands no additional water supply,
nor does it add any discharge load to a fixture or the
drainage system. It performs some useful function in
the operation, maintenance, servicing, economy, or
safety of the plumbing system.
Plumbing Fixture - An approved-type installed
receptacle, device, or appliance that is supplied with
water or that receives liquid or liquid-borne wastes
and discharges such wastes into the drainage system
to which it may be directly or indirectly connected.
Industrial or commercial tanks, vats, and similar
processing equipment are not plumbing fixtures, but
may be connected to or discharged into approved
traps or plumbing fixtures when and as otherwise
provided for elsewhere in this code.
Plumbing Official - See Authority Having
Jurisdiction.
Plumbing System - Includes all potable water,
building supply, and distribution pipes; all
plumbing fixtures and traps; all drainage and vent
pipes; and all building drains and building sewers,
including their respective joints and connections,
devices, receptors, and appurtenances within the
property lines of the premises and shall include
potable water piping, potable water treating or using
equipment, medical gas and medical vacuum
systems, liquid and fuel gas piping, and water
heaters and vents for same.
Pollution - An impairment of the quality of the
potable water to a degree that does not create a
hazard to the public health but which does adversely
and unreasonably affect the aesthetic qualities of
such potable water for domestic use. Also defined as
Low Hazard.
Potable Water - Water that is satisfactory for
drinking, culinary, and domestic purposes and that
meets the requirements of the Health Authority
Having Jurisdiction.
PP - Polypropylene.
16
DEFINITIONS
218.0-221.0
Pressure - The normal force exerted by a
homoger\eous liquid or gas, per unit of area, on the
wall of the container.
(1) Static Pressure - The pressure existing
without any flow.
(2) Residual Pressure - The pressure available
at the fixture or water outlet after allowance is
made for pressure drop due to friction loss,
head, meter, and other losses in the system
during maximum demand periods.
Pressure-Balancing Valve - A mixing valve that
senses incoming hot and cold water pressures and
compensates for fluctuations in either to stabilize
outlet temperature.
Private or Private Use - Applies to plumbing
fixtures in residences and apartments, to private
bathrooms in hotels and hospitals, and to restrooms
in commercial establishments where the fixtures are
intended for the use of a family or an individual.
Private Sewage Disposal System - A septic tank
with the effluent discharging into a subsurface
disposal field, into one or more seepage pits, or into
a combination of subsurface disposal field and
seepage pit or of such other facilities as may be
permitted under the procedures set forth elsewhere
in this code.
Private Sewer - A building sewer that receives the
discharge from more than one (1) building drain and
conveys it to a public sewer, private sewage disposal
system, or other point of disposal.
Public or Public Use - All buildings or structures
that are not defined as private or private use.
Public Sewer - A common sewer directly controlled
by public authority.
PVC - Poly(vinyl chloride).
I PVDF - Polyvinylidene Fluoride.
219.0 -Q-
No definitions.
220.0 - R -
Receptor - An approved plumbing fixture or device
of such material, shape, and capacity as to
adequately receive the discharge from indirect waste
pipes, so constructed and located as to be readily
cleaned.
Regulating Equipment - Includes all valves and
controls used in a plumbing system that are required
to be accessible or readily accessible.
Relief Vent - A vent, the primary function of which
is to provide circulation of air between drainage and
vent systems or to act as an auxiliary vent on a
specially designed system.
Remote Outlet - When used for sizing water piping,
it is the furthest outlet dimension, measuring from
the meter, either the developed length of the cold-
water piping or through the water heater to the
furthest outlet on the hot-water piping.
Rim - See Flood-Level Rim.
Riser - A water supply pipe that extends vertically
one (1) full story or more to convey water to
branches or fixtures.
Roof Drain - A drain installed to receive water
collecting on the surface of a roof and to discharge it
into a leader, downspout, or conductor.
Roughing-ln - The installation of all parts of the
plumbing system that can be completed prior to the
installation of fixtures. This includes drainage, water
supply, gas piping, vent piping, and the necessary
fixture supports.
221.0
-S-
Sand Interceptor - See Interceptor.
SDR - An abbreviation for "standard dimensional
ratio," which is the specific ratio of the average
specified outside diameter to the minimum wall
thickness for outside controlled diameter plastic pipe.
Seepage Pit - A lined excavation in the ground
which receives the discharge of a septic tank so
designed as to permit the effluent from the septic
tank to seep through its bottom and sides.
Septic Tank - A watertight receptacle that receives
the discharge of a drainage system or part thereof,
designed and constructed so as to retain solids,
digest organic matter through a period of detention,
and allow the liquids to discharge into the soil
outside of the tank through a system of open joint
piping or a seepage pit meeting the requirements of
this code.
Sewage - Any liquid waste containing animal or
vegetable matter in suspension or solution and that
may include liquids containing chen\icals in solution.
Sewage Ejector - A device for lifting sewage by
entraining it on a high-velocity jet stream, air, or
water.
Sewage Pump - A permanently installed
mechanical device, other than an ejector, for
removing sewage or liquid waste from a sump.
Shall - Indicates a mandatory requirement.
Shielded Coupling - An approved elastomeric
sealing gasket with an approved outer shield and a
tightening mechanism.
Shock Arrester - See Water Hammer Arrester.
17
221 .0 - 224.0
UNIFORM PLUMBING CODE
Should - Indicates a recommendation or that which
is advised but not required.
Single-Family Dwelling - A building designed to be
used as a home by the owner of such building, which
shall be the only dwelling located on a parcel of
ground with the usual accessory buildings.
Size and Type of Tubing - See Diameter.
Slip Joint - An adjustable tubing connection,
consisting of a compression nut, a friction ring, and a
compression washer, designed to fit a threaded
adapter fitting or a standard taper pipe thread. .
Slope - See Grade.
Soil Pipe - Any pipe that conveys the discharge of
water closets, urinals, clinic sinks, or fixtures
having similar functions of collection and removal
of domestic sewage, with or without the discharge
from other fixtures, to the building drain or
building sewer.
Special Wastes - Wastes that require some special
method of handling, such as the use of indirect waste
piping and receptors, corrosion-resistant piping,
sand, oil or grease interceptors, condensers, or other
pretreatment facilities.
Stack - The vertical main of a system of soil,
waste, or vent piping extending through one or
more stories.
Stack Vent - The extension of a soil or waste stack
above the highest horizontal drain connected to
the stack.
Standard - A document, the main text of which
contains only mandatory provisions using the
word "shall" to indicate requirements and which is
in a form generally suitable for mandatory
reference by another standard or code or for
adoption into law. Nonmandatory provisions shall
be located in an appendix, footnote, or fine print
note and are not to be considered a part of the
requirements of a standard.
Storm Drain - See Building Drain (Storm).
Storm Sewer - A sewer used for conveying
rainwater, surface water, condensate, cooling water,
or similar liquid wastes.
Subsoil Drain - A drain that collects subsurface or
seepage water and conveys it to a place of disposal.
Sump - An approved tank or pit that receives
sewage or liquid waste and which is located below
the normal grade of the gravity system and which
must be emptied by mechanical means.
Supports - Supports, hangers, and anchors are
devices for properly supporting and securing pipe,
fixtures, and equipment.
222.0 - T -
Tailpiece - The pipe or tubing that connects the
outlet of a plumbing fixture to a trap.
Thermostatic (Temperature Control) Valve - A
mixing valve that senses outlet temperature and
compensates for fluctuations in incoming hot or cold
water temperatures.
Trap - A fitting or device so designed and
constructed as to provide, when properly vented, a
liquid seal that will prevent the back passage of air
without materially affecting the flow of sewage or
wastewater through it.
Trap Arm - That portion of a fixture drain between a
trap and the vent.
Trap Primer - A device and system of piping that
maintains a water seal in a remote trap.
Trap Seal - The vertical distance between the crown
weir and the top dip of the trap.
Crown Weir (Trap Weir) -The lowest point in
the cross-section of the horizontal waterway at
the exit of the trap.
Top Dip (of trap) - The highest point in the
internal cross-section of the trap at the lowest
part of the bend (inverted siphon). By contrast,
the bottom dip is the lowest point in the internal
cross-section.
223.0 - U -
Unconfined Space - A room or space having a
volume equal to at least 50 cubic feet per 1,000 Btu/h
(1.4 m^/293 W) of the aggregate input rating of all
fuel-burning appliances installed in that space.
Rooms communicating directly with the space in
which the appliances are installed, through openings
not furnished with doors, are considered a part of
the unconfined space.
Unsanitary - See Insanitary.
224.0 - V -
Vacuum - Any pressure less than that exerted by the
atmosphere.
Vacuum Breaker - See Backflow Preventer.
Vacuum Relief Valve - A device that prevents
excessive vacuum in a pressure vessel.
Vent - Any pipe provided to ventilate a plumbing
system, to prevent trap siphonage and back-
pressure, or to equalize the air pressure within the
drainage system.
Vent Pipe - See Vent.
18
DEFINITIONS
224.0 - 228.0
Vent Stack - The vertical vent pipe installed
primarily for the purpose of providing circulation of
air to and from any part of the drainage system.
Vent System - A pipe or pipes installed to provide a
flow of air to or from a drainage system or to
provide a circulation of air within such system to
protect trap seals from siphonage and back-pressure.
Vented Flow Control Device - A device installed
upstream, from the hydromechanical grease
interceptor having an orifice that controls the rate of
flow through the interceptor, and an air intake (vent)
downstream from the orifice, which allows air to be
drawn into the flow stream.
Vertical Pipe - Any pipe or fitting that is installed in
a vertical position or that makes an angle of not more
than forty-five (45) degrees with the vertical.
225.0 - W -
Wall-Hung Water Closet - A water closet installed
in such a way that no part of the water closet touches
the floor.
Waste - See Liquid Waste and Industrial Waste.
Waste Pipe - A pipe that conveys only liquid waste,
free of fecal matter.
Water-Conditioning or Treating Device - A device
that conditions or treats a water supply so as to
change its chemical content or remove suspended
solids by filtration.
Water-Distributing Pipe - In a building or premises,
a pipe that conveys potable water from the building
supply pipe to the plumbing fixtures and other
water outlets.
Water Hammer Arrester - A device to absorb
hydraulic shock, either of the air chamber or
mechanical device design.
Water Main (Street Main) - A water supply pipe for
public or community use.
Water Supply System - The building supply pipe,
the water-distributing pipes, and the necessary
connecting pipes, fittings, control valves, backflow
prevention devices, and all appurtenances carrying
or supplying potable water in or adjacent to the
building or premises.
Welded Joint or Seam - Any joint or seam obtained
by the joining of metal parts in the plastic molten
state.
Welder, Pipe - A person who specializes in the
welding of pipes and holds a valid certificate of
competency from a recognized testing laboratory,
based on the requirements of the ASME Boiler and
Pressure Vessels code. Section IX.
Wet Vent - A vent that also serves as a drain.
Whirlpool Bathtub - A bathtub fixture equipped
and fitted with a circulating piping system designed
to accept, circulate, and discharge bathtub water
upon each use.
226.0
No definitions.
227.0
-X-
-Y-
Yoke Vent - A pipe connecting upward from a soil
or waste stack to a vent stack for the purpose of
preventing pressure changes in the stacks.
228.0
No definitions.
-Z-
19
UNIFORM PLUMBING CODE
20
CHAPTER 3
GENERAL REGULATIONS
301 .0 Materials - Standards and Alternates.
301.1 Minimum Standards.
301.1.1 Approvals. All pipe, pipe fittings,
traps, fixtures, material, and devices used in a
plumbing system shall be listed or labeled
(third-party certified) by a listing agency
(accredited conformity assessment body) and
shall conform to approved applicable recognized
standards referenced in this code, and shall be
free from defects. Unless otherwise provided for
in this code, all materials, fixtures, or devices
used or entering into the construction of
plumbing systems, or parts thereof, shall be
submitted to the Authority Having Jurisdiction
for approval.
301.1.2 Marking. Each length of pipe and each
pipe fitting, trap, fixture, material, and device
used in a plumbing system shall have cast,
stamped, or indelibly marked on it the
manufacturer's mark or name, which shall readily
identify the manufacturer to the end user of the
product when such marking is required by the
approved standard that applies. When required
by the approved standard that applies, the
product shall be marked with the weight and the
quality of the product. All materials and devices
used or entering into the coristruction of plumbing
and drainage systems, or parts thereof, shall be
marked and identified in a manner satisfactory to
the Authority Having Jurisdiction. All such
marking shall be done by the manufacturer. Field
marking shall not be acceptable.
301.1.3 Standards. Standards listed or referred
to in this chapter or other chapters cover
materials that will conform to the requirements
of this code, w^hen used in accordance with the
limitations imposed in this or other chapters
thereof and their listing. Where a standard
covers materials of various grades, weights,
quality, or configurations, there may be only a
portion of the listed standard that is applicable.
Design and materials for special conditions or
materials not provided for herein may be used
only by special permission of the Authority
Having Jurisdiction after the Authority Having
Jurisdiction has been satisfied as to their
adequacy. A list of accepted plumbing materials
standards is included in Table 14-1. All lAPMO
Installation Standards are included in Appendix
I for the convenience of the users of this code.
They are not considered as a part of this code
unless formally adopted as such by the
Authority Having Jurisdiction.
301.1.4 Existing Buildings. In existing buildings
or premises in which plumbing installations are
to be altered, repaired, or renovated, the
Authority Having Jurisdiction has discretionary
powers to permit deviation from the provisions
of this code, provided that such a proposal to
deviate is first submitted for proper determi-
nation in order that health and safety require-
ments, as they pertain to plumbing, shall be
observed.
301.2 Alternate Materials and Methods of
Construction Equivalency. Nothing in this code is
intended to prevent the use of systems, methods, or
devices of equivalent or superior quality, strength,
fire resistance, effectiveness, durability, and safety
over those prescribed by this code. Technical
documentation shall be submitted to the Authority
Having Jurisdiction to demonstrate equivalency. The
Authority Having Jurisdiction shall approve the
system method or device when determined to be
equivalent or superior.
However, the exercise of this discretionary
approval by the Authority Having Jurisdiction shall
have no effect beyond the jurisdictional boundaries
of said Authority Having Jurisdiction. Any alternate
material or method of construction so approved shall
not be considered as conforming to the requirements
and /or intent of this code for any purpose other than
that granted by the Authority Having Jurisdiction
when the submitted data does not prove equivalency.
301 .2.1 Testing. The Authority Having Jurisdic-
tion shall have the authority to require tests, as
proof of equivalency.
301.2.1.1 Tests shaU be made in accordance
with approved standards, by an approved
testing agency at the expense of the applicant.
In the absence of such standards, the
Authority Having Jurisdiction shall have the
authority specify the test procedure.
301 .2.1 .2 The Authority Having Jurisdiction
shall have the authority to require tests to be
made or repeated if, at any time, there is
reason to believe that any material or device
no longer conforms to the requirements on
which its approval was based.
21
301.3-306.1
UNIFORM PLUMBING CODE
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
301 .3 Flood Hazard Resistance.
301.3.1 General. Plumbing systems shall be
located above the design flood elevation.
Exception: Plumbing systems are permitted
to be located below the design flood
elevation provided that the systems are
designed and installed to prevent water from
entering or accumulating within their
components and the systems are constructed
to resist hydrostatic and hydrodynamic
loads and stresses, including the effects of
buoyancy, during the occurrence of flooding
to the design flood elevation.
301 .3.2 Flood Hazard Areas Subject to High-
Velocity Wave Action. Plumbing systems in
buildings located in flood hazard areas subject to
high-velocity wave action shall meet the
requirements of Section 301.3.1, and the
plumbing systems, pipes, and fixtures shall not
be mounted on or penetrate through walls that
are intended to breakaway under flood loads as
required by the building code.
301 .4 Alternative Engineered Design.
301.4.1 Design Criteria. An alternative
engineered design shall conform to the intent of
the provisions of this code and shall provide an
equivalent level of quality, strength, effective-
ness, fire resistance, durability, and safety.
Material, equipment, or components shall be
designed and installed in accordance with the
manufacturer's installation instructions.
301.4.2 Permit Application. The registered
professional engineer shall indicate on the design
documents that the plumbing system, or parts
thereof, is an alternative engineered design so
that it is noted on the construction permit
application. The permit and permanent permit
records shall indicate that an alternative
engineered desigri was part of the approved
installation.
301.4.3 Technical Data. The registered
professional engineer shall submit sufficient
technical data to substantiate the proposed
alternative engineered design and to prove that
the performance meets the intent of this code.
301.4.4 Design Documents. The registered
professional engineer shall provide two (2)
complete sets of signed and sealed design
documents for the alternative engineered design
for submittal to the Authority Having Jurisdic-
tion. The design documents shall include floor
plans and a riser diagram of the work. Where
appropriate, the design documents shall indicate
the direction of flow, all pipe sizes, grade of
horizontal piping, loading, and location of
fixtures and appliances.
301.4.5 Design Approval. Where the Authority
Having Jurisdiction determines that the
alternative engineered design conforms to the
intent of this code, the plumbing system shall be
approved. If the alternative engineered design is
not approved, the Authority Having Jurisdiction
shall notify the registered professional engineer
in writing, stating the reasons therefore.
301 .4.6 Inspection and Testing. The alternative
engineered design shall be tested and inspected
in accordance with the submitted testing and
inspection plan and the requirements of this code.
302.0 Iron Pipe Size (IPS) Pipe.
Iron, steel, brass, and copper pipe shall be standard-
weight iron pipe size (IPS) pipe.
303.0 Disposal of Liquid Waste.
It shall be unlawful for any person to cause, suffer, or
permit the disposal of sewage, human excrement, or
other liquid wastes, in any place or manner, except
through and by means of an approved drainage
system, installed and maintained in accordance with
the provisions of this code.
304.0 Connections to Plumbing System Required.
All plumbing fixtures, drains, appurtenances, and
appliances, used to receive or discharge liquid wastes
or sewage, shall be connected properly to the drainage
system of the building or premises, in accordance
with the requirements of this code.
305.0 Sewers Required.
305.1 Every building in which plumbing fixtures are
installed shall have a connection to a public or private
sewer except as provided in Section 305.2.
305.2 When a public sewer is not available for use,
drainage piping from buildings and premises shall
be connected to an approved private sewage
disposal system.
305.3 In cities and /or counties where the installation
of building sewers is under the jurisdiction of a
department other than the Authority Having Jurisdic-
tion, the provisions of this code relating to building
sewers need not apply.
306.0 Damage to Drainage System or Public Sewer.
306.1 It shall be unlawful for any person to deposit,
by any means whatsoever, into any plumbing fixture,
floor drain, interceptor, sump, receptor, or device.
22
GENERAL REGULATIONS
306.1 -312.0
which is connected to any drainage system, public
sewer, private sewer, septic tank, or cesspool, any
ashes; cinders; solids; rags; inflammable, poisonous,
or explosive liquids or gases; oils; grease; or any
other thing whatsoever that would, or could, cause
damage to the drainage system or public sewer.
306.2 Roofs, inner courts, vent shafts, light wells, or
similar areas having rainwater drain, shall discharge
to the outside of the building or to the gutter and
shall not be connected to the sanitary drainage
system unless first approved by the Authority
Having Jurisdiction.
307.0 Industrial Wastes.
307.1 Wastes detrimental to the public sewer system
or detrimental to the functioning of the sewage
treatment plant shall be treated and disposed of as
found necessary and directed by the Authority
Having Jurisdiction.
307.2 Sewage or other waste from a plumbing
system that may be deleterious to surface or
subsurface waters shall not be discharged into the
ground or into any waterway unless it has first been
rendered safe by some acceptable form of treatment
as required by the Authority Having Jurisdiction.
308.0 Location.
308.1 Except as otherwise provided in this code, no
plumbing system, drainage system, building sewer,
private sewage disposal system, or parts thereof
shall be located in any lot other than the lot that is
the site of the building, structure, or premises served
by such facilities.
308.2 No subdivision, sale, or transfer of ownership
of existing property shall be made in such manner
that the area, clearance, and access requirements of
this code are decreased.
309.0 Improper Location.
Piping, fixtures, or equipment shall not be so located
as to interfere with the normal use thereof or with
the normal operation and use of windows, doors, or
other required facilities.
310.0 Workmanship.
310.1 All design, construction, and workmanship
shall be in conformity with accepted engineering
practices and shall be of such character as to secure
the results sought to be obtained by this code.
31 0.2 It is unlawful to conceal cracks, holes, or other
imperfections in materials by welding, brazing, or
soldering or by using therein or thereon any paint,
wax, tar, or other leak-sealing or repair agent.
310.3 Burred ends of all pipe and tubing shall be
reamed to the full bore of the pipe or tube, and all
chips shall be removed.
310.4 Installation Practices. Plumbing systems
shall be installed in a manner conforming to this
code, applicable standards, and the manufacturer's
installation instructions. In instances where the code,
applicable standards, or the manufacturer's
instructions conflict, the more stringent provisions
shall prevail.
31 1 .0 Prohibited Fittings and Practices.
311.1 No double hub fitting, single or double tee
branch, single or double tapped tee branch, side inlet
quarter bend, running thread, band, or saddle shall
be used as a drainage fitting, except that a double
hub sanitary tapped tee may be used on a vertical
line as a fixture connection.
311.2 No drainage or vent piping shall be drilled
and tapped for the purpose of making connections
thereto, and no cast-iron soil pipe shall be threaded.
31 1 .3 No waste connection shall be made to a closet
bend or stub of a water closet or similar fixture.
31 1 .4 Except as hereinafter provided in Sections 908.0,
909.0, and 910.0, no vent pipe shaU be used as a soil or
waste pipe, nor shall any soil or waste pipe be used as
a vent. Also, single-stack drainage and venting
systems with unvented branch lines are prohibited.
31 1 .5 No fitting, fixture and piping connection,
appliance, device, or method of installation that
obstructs or retards the flow of water, wastes,
sewage, or air in the drainage or venting systems, in
an amount greater than the normal frictional
resistance to flow, shall be used unless it is indicated
as acceptable in this code or is approved per Section
301.1 of this code. The enlargement of a three (3) inch
(80 mm) closet bend or stub to four (4) inches (100 I
mm) shall not be considered an obstruction. |
311.6 Except for necessary valves, where inter-
membering or mixing of dissimilar metals occurs,
the point of connection shall be confined to exposed
or accessible locations.
31 1 .7 All valves, pipes, and fittings shall be installed
in correct relationship to the direction of flow.
311.8 Screwed Fittings. Screwed fittings shall be
ABS, cast iron, copper, copper alloy, malleable iron,
PVC, steel, or other approved materials. Threads
shall be tapped out of solid metal or molded in soUd
ABS or PVC.
312.0 Independent Systems.
The drainage system of each new building and of new
work installed in any existing building shall be
separate and independent from that of any other
23
312.0-313.12
UNIFORM PLUMBING CODE
building, and, when available, every building shall
have an independent connection with a public or
private sewer.
Exception: Where one building stands in the
rear of another building on an interior lot, and
no private sewer is available or can be
constructed to the rear building through an
adjoining court, yard, or driveway, the building
drain from the front building may be extended
to the rear building.
313.0 Protection of Piping, Materials, and Structures.
313.1 All piping passing under or through walls
shall be protected from breakage. All piping passing
through or under cinders or other corrosive
materials shall be protected from external corrosion
in an approved manner. Approved provisions shall
be made for expansion of hot water piping. Voids
around piping passing through concrete floors on
the ground shall be appropriately sealed.
313.2 All piping in connection with a plumbing
system shall be so installed that piping or
connections will not be subject to undue strains or
stresses, and provisions shall be made for expansion,
contraction, and structural settlement. No plumbing
piping shall be directly embedded in concrete or
masonry. No structural member shall be seriously
weakened or impaired by cutting, notching, or
otherwise, as defined in the Building Code.
313.3 All trenches deeper than the footing of any
building or structure and paralleling the same shall be
at least forty-five (45) degrees (0.79 rad) therefrom, or
I as approved per Section 301.1 of this code.
31 3.4 No building sewer or other drainage piping or
part thereof, constructed of materials other than
those approved for use imder or within a building,
shall be installed under or w^ithin two (2) feet (610
mni) of any building or structure, or less than one (1)
foot (305 mm) below the surface of the ground.
313.5 Piping subject to corrosion, erosion, or
mechanical damage shall be protected in an
approved manner.
313.6 No water, soil, or waste pipe shall be installed
or permitted outside of a building or in an exterior
wall unless, where necessary, adequate provision is
made to protect such pipe from freezing.
313.7 All piping penetrations of fire-resistance-rated
walls, partitions, floors, floor /ceiling assemblies,
roof/ceiling assemblies, or shaft enclosures shall be
protected in accordance with the requirements of the
Building Code, lAPMO Installation Standards, and
Chapter 15, "Firestop Protection."
313.8 Waterproofing of Openings. Joints at the roof
around pipes, ducts, or other appurtenances shall be
made watertight by the use of lead, copper,
galvanized iron, or other approved flashings or
flashing material. Exterior wall openings shall be
made watertight. Counterflashing shall not restrict
the required internal cross-sectional area of the vent.
313.9 Plastic and copper piping penetrating a |
framing members to within one (1) inch (25.4 mm) of
the exposed framing shall be protected by steel nail
plates not less than 0.0478 inches (18 gauge) (1.3mm)
in thickness. The steel nail plate shall extend along
the framing member a minimurri of 1-1/2 inches
beyond the outside diameter of the pipe or tubing.
Exception: See Section 1211.3.4.
313.10 Sleeves.
313.10.1 Sleeves shall be provided to protect all
piping through concrete and masonry walls and
concrete floors.
Exception: Sleeves shall not be required where
openings are drilled or bored.
313.10.2 Piping through concrete or masonry
walls shall not be subject to any load from
building construction.
313.10.3 In exterior waUs, annular space between
sleeves and pipes shall be sealed and made
watertight, as approved by the Authority Having
Jurisdiction. Any penetration through fire-
resistive construction shall be in accordance with
Section 313.7.
313.10.4 Any pipe sleeve through a firewall shall
have the space around the pipe completely
sealed with an approved fire-resistive material
in accordance with all other codes.
31 3.11 Any structural member weakened or
unpaired by cutting, notching, or otherwise shall be
reinforced, repaired, or replaced so as to be left in a
safe structural condition in accordance with the
requirements of the Building Code.
313.12 Ratproofing.
31 3.1 2.1 Strainer plates on drain inlets shall be
designed and installed so that no opening is
greater than one-half (1/2) inch (12.7 mm) in the
least dimension.
313.12.2 Meter boxes shall be constructed in
such a manner that rats cannot enter a building
by following the service pipes from the box into
the building.
313.12.3 In or on buildings where openings
have been made in walls, floors, or ceilings for
the passage of pipes, such openings shall be
closed and protected by the installation of
approved metal collars securely fastened to the
adjoining structure.
24
GENERAL REGULATIONS
313.12-316.1
313.12.4 Tub waste openings in framed
construction to crawl spaces at or below the first
floor shall be protected by the installation of
approved metal collars or metal screen securely
fastened to the adjoining structure with no
opening greater than one-half (1/2) inch
(12.7mm) in the least dimension.
314.0 Hangers and Supports.
314.1 Suspended piping shall be supported at
intervals not to exceed those shown in Table 3-2.
314.2 All piping shall be supported in such a
manner as to maintain its alignment and prevent
sagging.
314.3 Piping in the ground shall be laid on a firm
bed for its entire length; where other support is
otherwise provided, it shall be approved per Section
301.0 of this code.
314.4 Hangers and anchors shall be of sufficient
strength to support the weight of the pipe and its
contents. Piping shall be isolated from incompatible
materials.
314.5 All piping, fixtures, appliances, and
appurtenances shall be adequately supported in
accordance with this code, the manufacturer's
installation instructions, and as required by the
Authority Having Jurisdiction.
314.6 Hanger rod sizes shall be no smaller than
those shown in Table 3-1.
314.7 All gas piping shall be supported by metal
straps or hooks at intervals not to exceed those
shown in Table 3-2.
TABLE 3-1
Hanger Rod Sizes
Pipe and Tube Size
Rod Size
inches
mm
Inches
mm
1/2-4
12.7-102
3/8
9.5
5-8
127-203
1/2
12.7
10-12
254-305
5/8
15.9
315.0 Trenching, Excavation, and Backfill.
315.1 All trenches deeper than the footing of any
building or structure and paralleling the same shall
be at least forty-five (45) degrees (0.79 rad) therefrom,
I or as approved per Section 301.0 of this code.
31 5.2 Turmeling and driving may be done in yards,
courts, or driveways of any building site. Where
sufficient depth is available to permit, tunnels may
be used between open-cut trenches. Tunnels shall
have a clear height of two (2) feet (610 mm) above
the pipe and shall be limited in length to one-half
(1/2) the depth of the trench, with a maximum
length of eight (8) feet (2438 mm). When pipes are
driven, the drive pipe shall be at least one (1) size
larger than the pipe to be laid.
315.3 Open Trenches. All excavations required to
be made for the installation of a building drainage
system or any part thereof, within the walls of a
building, shall be open trench work and shall be
kept open until the piping has been inspected,
tested, and accepted.
31 5.4 All excavations shall be completely backfilled
as soon after inspection as practicable. Adequate
precaution shall be taken to ensure proper
compactness of backfill around piping without
damage to such piping. Trenches shall be backfilled
in thin layers to twelve (12) inches (305 mm) above
the top of the piping with clean earth, which shall
not contain stones, boulders, cinderfill, frozen earth,
construction debris, or other materials that would
damage or break the piping or cause corrosive
action. Mechanical devices such as bulldozers,
graders, etc., may then be used to complete backfill
to grade. Fill shall be properly compacted. Suitable
precautions shall be taken to ensure permanent
stability for pipe laid in filled or made ground.
316.0 Joints and Connections.
316.1 Types of Joints.
316.1.1 Threaded Joints. Threads on iron pipe
size (IPS) pipe and fittings shall be standard
taper pipe threads in accordance with standards
listed in Table 14-1. Threads on tubing shall be
approved types. Threads on plastic pipe shall be
factory cut or molded. Threaded plastic pipe
shall be Schedule 80 minimum wall thickness.
Tubing threads shall conform to fine tubing
thread standards. When a pipe joint material is
used, it shall be applied only on male threads,
and such materials shall be approved types,
insoluble in water and nontoxic. Cleanout plugs
and caps shall be lubricated with water-
insoluble, nonhardening material or tape.
Thread tape or thread lubricants and sealants
specifically intended for use with plastics shall
be used on plastic threads. Conventional pipe
thread compounds, putty, linseed-oil-based
products, and unknown lubricants and sealants
shall not be used on plastic threads.
316.1.2 Wiped Joints. Joints in lead pipe or
fittings or between lead pipe or fittings and brass
or copper pipe, ferrules, solder rupples, or traps
25
316.1 -316.3
UNIFORM PLUMBING CODE
shall be full-wiped joints. Wiped joints shall
have an exposed surface on each side of a joint
not less than three-fourths (3/4) inch (19.1 mm.)
and at least as thick as the material being joined.
Wall or floor flange lead-wiped joints shall be
made by using a lead ring or flange placed
behind the joint at the wall or floor. Joints
between lead pipe and cast iron, steel, or
wrought iron shall be made by means of a
caulking ferrule or soldering nipple.
316.1.3 Soldered Joints. Joints in copper
tubing shall be made by the appropriate use of
approved copper or copper alloy fittings.
Surfaces to be joined by soldering shall be
cleaned bright by manual or mechanical means.
The joints shall be properly fluxed with an
approved-type flux and made up with approved
solder. All solder and fluxes shall be
manufactured to approved standards. Solders
and fluxes with a lead content that exceeds two-
tenths (0.20) of one (1) percent shall be
prohibited in piping systems used to convey
potable water.
316.1.4 Flared Joints. Flared joints for soft
copper tubing shall be made with fittings
meeting approved standards. The tubing shall
be reamed to the full inside diameter, resized to
round, and expanded with a proper flaring tool.
316.1.5 Flexible Compression Factory-
Fabricated Joints. When pipe is joined by
means of flexible compression joints, such
joints shall conform to approved standards
and shall not be considered as slip joints.
316.1.6 Solvent Cement Plastic Pipe Joints.
Plastic pipe and fittings designed to be joined by
solvent cementing shall comply with appropriate
lAPMO Installation Standards.
ABS pipe and fittings shall be cleaned and
then joined with solvent cement(s).
CPVC pipe and fittings shall be cleaned and
then joined with listed primer(s) and solvent
cement(s).
Exception: Listed solvent cements that do not
require the use of primer shall be permitted
for use with CPVC pipe and fittings,
manufactured in accordance with ASTM
D2846, 1/2 inch through 2 inches in diameter.
PVC pipe and fittings shall be cleaned and
joined with primer(s) and solvent cement(s).
A solvent cement transition joint between
ABS and PVC building drain or building sewer
shall be made using a listed transition solvent
cement.
316.1.7 Brazing and Welding. Brazing and
welding shall conform to the applicable
standard(s) in Table 14-1. Only brazing alloys
having a liquid temperature above 1,000°F shall
be used. All brazing on medical gas systems
shall be performed by certified installers
meeting the requirements of ANSI/ASME Boiler
and Pressure Vessel Code, Section IX, Welding
and Brazing Qualifications, or AWS B2.2,
Standard for Brazing Procedure and Perfor-
mance Qualifications.
316.1.8 Pressure-Lock-Type Connection. Tliis
is a mechanical connection that depends on an
internal retention device to prevent pipe or
tubing separation. Connection is made by
inserting the pipe or tubing into the fitting to a
prescribed depth.
316.1.9 Pressed Fitting. This is a mechanical
connection for joining copper tubing that uses a
crimping tool to affix the O-ring seal copper or
copper alloy fitting to the tubing. The tubing
shall be inserted into the fitting, and the crimp
shall be made using the tool recommended by
the manufacturer.
316.2 Special Joints.
316.2.1 Copper Tubing to Screw Pipe Joints.
Joints from copper tubing to threaded pipe shall be
made by tlie use of brass adapter fittings. The joint
between the copper tubing and the fitting shall be
a soldered brazed flared, or pressed joint and the
connection between the threaded pipe and the
fitting shall be made with a standard pipe size
screw joint. Solder shall conform to the require-
ments of Section 316.1.3. Brazed joints shall conform
to the requirements of Section 316.1.7. Flared joints
shall conform to the requirements of Section 316.1.4.
Pressed joints shaU conform to tlie requirements of
316.1.9.
316.2.2 Unions. Approved unions may be used
in drainage piping when accessibly located in
the trap seal or between a fixture and its trap in
the vent system, except underground or in wet
vents, at any point in the water supply system,
and in gas piping as permitted by Section
1211.3.2(4).
316.2.3 Plastic Pipe to Other Materials. When
connecting plastic pipe to other types of piping,
only approved types of fittings and adapters
designed for the specific transition intended
shall be used.
316.3 Flanged Fixture Connections.
316.3.1 Fixture connections between drainage
pipes and water closets, floor outlet service sinks
and urinals shall be made by means of approved
brass, hard lead, ABS, PVC, or iron flanges
26
GENERAL REGULATIONS
316.3-320.0
caulked, soldered, solvent cemented; rubber
compression gaskets; or screwed to the drainage
pipe. The connection shall be bolted with an
approved gasket, washer, or setting compound
between the fixture and the connection. The bottom
of the flange shall be set on an approved firm base.
31 6.3.2 Closet bends or stubs shall be cut off so as
to present a smooth surface even with the top of
the closet ring before rough inspection is called.
316.3.3 Wall-mounted water closet fixtures shall
be securely bolted to an approved carrier fitting.
The cormecting pipe between the carrier fitting
and the fixture shall be an approved material
and designed to accommodate an adequately
sized gasket. Gasket material shall be neoprene,
felt, or similar approved types.
316.4 Prohibited Joints and Connections.
316.4.1 Drainage System. Any fitting or
connection that has an enlargement, chamber,
or recess with a ledge, shoulder, or reduction of
pipe area that offers an obstruction to flow
through the drain shall be prohibited.
316.4.2 No fitting or connection that offers
abnormal obstruction to flow shall be used. The
enlargement of a three (3) inch (80 mm) closet
bend or stub to four (4) inches (100 mm) shall
not be considered an obstruction.
317.0 increasers and Reducers.
Where different sizes of pipes and fittings are to be
connected, the proper size increasers or reducers or
reducing fittings shall be used between the two sizes.
Brass or cast-iron body cleaniouts shall not be used as
a reducer or adapter from cast-iron drainage pipe to
iron pipe size (IPS) pipe.
318.0 Food-Handling Establishments.
Food or drink shall not be stored, prepared, or
displayed beneath soil or drain pipes, unless those
areas are protected against leakage or condensation
from such pipes reaching the food or drink as
described below. Where building design requires
that soil or drain pipes be located over such areas,
the installation shall be made with the least possible
number of joints and shall be installed so as to
connect to the nearest adequately sized vertical stack
with the provisions as follows:
318.1 All openings through floors over such
areas shall be sealed watertight to the floor
construction.
318.2 Floor and shower drains installed above
such areas shall be equipped with integral
seepage pans.
318.3 All other soil or drain pipes shall be of an
approved material as listed in Table 14-1 and Section
701.0. All materials shall conform to established
standards. Cleanouts shall be extended through the
floor construction above.
318.4 Piping subject to operation at temperatures
that will form condensation on the exterior of the
pipe shall be thermally insulated.
318.5 Where pipes are installed in ceilings above
such areas, the ceiling shall be of the removable
type, or shall be provided with access panels in order
to form a ready access for inspection of piping.
319.0 Test Gauges. Tests required by this code,
which are performed utilizing dial gauges, shall be
limited to gauges having the following pressure
graduations or incrementations.
319.1 Required pressure tests of ten (10) psi (69 kPa)
or less shall be performed with gauges of 1/10
pound (0.7 kPa) incrementation or less.
319.2 Required pressure tests exceeding ten (10)
pounds (69 kPa) but less than one hundred (100)
psi (689 kPa) shall be performed with gauges of
one (1) psi (6.9 kPa) incrementation or less.
319.3 Required pressure tests exceeding one
himdred (100) psi (689 kPa) shall be performed with
gauges incremented for two (2) percent or less of the
required test pressure.
319.4 Test gauges shall have a pressure range not
greater than twice the test pressure applied.
320.0 Medical Gas and Vacuum Systems. All such
piping shall be installed, tested, and verified in
compliance with the appropriate consensus
standards referenced in Chapter 14 and the
requirements of Chapter 13. The Authority Having
Jurisdiction shall require evidence of the competency
of the installers and verifiers.
27
Table 3-2
UNIFORM PLUMBING CODE
TABLE 3-2
Hangers and Supports
Materials
Types of Joints
Horizontal
Vertical
Cast
Lead and Oakum
Compression Gasket
5 feet (1 ,524 mm), except may be
10 feet (3,048 mm) where 10 foot
lengths are installed '^^
Every other joint, unless over 4 feet
(1,219 mm), then support each joint
Base and each floor not to
exceed 15 feet (4,572 mm)
Base and each floor not to
exceed 1 5 feet (4,572 mm)
Cast-Iron Hubless
Shielded Coupling
Every other joint, unless over 4 feet
(1,219 mm), then support each joint '^^■''
Base and each floor not to
exceed 15 feet (4,572 mm)
Copper Tube and Pipe
Soldered or Brazed
1-1/2 inches (40 mm) and smaller, 6 feet
(1 ,829 mm), 2 inches (50 mm) and larger,
10 feet (3,048 mm)
Each floor, not to exceed
10 feet (3,048 mm)=
Steel and Brass Pipe for
Water or DWV
Threaded or Welded
3/4 inch (20 mm) and smaller, 1 feet
(3,048 mm), 1 inch (25 mm) and larger,
12 feet (3,658 mm)
Every other floor, not to
exceed 25 feet (7,620 mm)'
Steel, Brass, and Tinned Threaded or Welded
Copper Pipe for Gas
1/2 inch (15 mm), 6 feet (1829 mm),
3/4 inch (20 mm) and 1 inch (25.4 mm)
8 feet (2,438 mm, 1-1/4 inch (32 mm)
and larger, 10 feet (3,048 mm)
1/2 inch (12.7 mm), 6 feet
(1 ,829 mm), 3/4 inch (19 mm)
and 1 inch (25.4 mm), 8
feet (2,438 mm), 1-1/4
every floor level
Schedule 40 PVC and Solvent Cemented
ABS DWV
All sizes, 4 feet (1 ,219 mm). Allow for
expansion every 30 feet (9,144 mm).^*
Base and each floor. Provide
mid-story guides. Provide
for expansion every 30
feet (9,144 mm).»
CPVC
Solvent Cemented
1 inch (25 mm) and smaller, 3 feet
(914 mm), 1-1/4 inch (932 mm) and
larger, 4 feet (1 ,219 mm)
Base and each floor. Provide
mid-story guides. ^
Lead
Wiped or Burned
Continuous Support
Not to exceed 4 feet
(1,219 mm)
Copper
Mechanical
In accordance with standards acceptable to the Authority Having Jurisdiction
Steel and Brass
Mechanical
In accordance with standards acceptable to the Authority Having Jurisdiction
PEX
Metal Insert and
Metal Compression
32 inches (800 mm)
Base and each floor.
Provide mid-story guides.
PEX-AL-PEX
Metal Insert and
Metal Compression
1/2 inch (12 mm) 1 All sizes
3/4 inch (20 mm) > 98 inches
1 inch (25 mm) J (2,489 mm)
Base and each floor.
Provide mid-story guides.
PE-AL-PE
Metal Insert and
Metal Compression
1/2 inch (12 mm) 1 All sizes
3/4 inch (20 mm) J 98 inches
1 inch (25 mm) (2,489 mm)
Base and each floor.
Provide midstory guides.
Support adjacent to joint, not to exceed eighteen (18) Inches (457 mm).
Brace at not more than forty (40) foot (12,192 mm) inten/als to prevent horizontal movement.
Support at each horizontal branch connection.
Hangers shall not be placed on the coupling.
Vertical water lines may be supported in accordance with recognized engineering principles with regard to expansion and contraction, when first
approved by the Authority Having Jurisdiction.
See the appropriate lAPMO Installation Standard for expansion and other special requirements.
28
CHAPTER 4
PLUMBING FIXTURES AND FIXTURE FITTINGS
401 .0 Materials - General Requirements.
401.1 Quality of Fixtures. Plumbing fixtures shall be
constructed of dense, durable, non-absorbent materials
and shall have smooth, impervious surfaces, free from
unnecessary concealed fouling surfaces. Except as
permitted elsewhere in this code, all fixtures shall
conform in quality and design to nationally recognized
applicable standards included in Table 14-1.
401.2 Lead. See Table 14-1. Sheet lead shall be not
less than the following:
For safe pans not less than four (4) pounds per square
foot (19.5 kg/m') or 1/16 inch (1.6 mm) thick.
401.3 Plumbing fixture fittings covered under the
scope of NSF 61 shall comply with the requirements of
NSF61.
402.0 Water-Conserving Fixtures and Fittings.
402.1 Flush volumes for low-consumption and
water-saver water closets and urinals shall be in
accordance with applicable standards referenced
in Table 14-1.
402.2 Water Closets. Water closets, either flush
tank, flushometer tank, or flushometer valve
operated, shall have an average consumption of
not more than 1.6 gallons (6.1 liters) of water per flush.
402.3 Urinals. Urinals shall have an average water
consumption of not more than 1.0 gallon (3.8 liters) of
water per flush.
402.4 Metered Faucets. Self-closing or self-closing
metering faucets shall be installed on lavatories
intended to serve the transient public, such as those in,
but not limited to, service stations, train stations,
airports, restaurants, and convention halls. Metered
faucets shall deliver not more than 0.25 gallons (1.0
liter) of water per use.
402.5 Emergency Safety Showers. Emergency
safety showers shall not be limited in their water
supply flow rates.
402.6 Installation. Water-conserving fixtures
shall be installed in strict accordance with the
manufacturers' instructions to maintain their
rated performance.
403.0 Overflows.
When any fixture is provided with an overflow, the
waste shall be so arranged that the standing water in
the fixture cannot rise in the overflow when the
stopper is closed or remain in the overflow when the
fixture is empty. The overflow pipe from a fixture
shall be cormected on the house or inlet side of the
fixture trap, except that overflow on flush tax\ks may
discharge into the water closets or urinals served by
them, but it shall be unlawful to connect such
overflows with any other part of the drainage system.
404.0 Strainers and Connections.
404.1 Strainers. All plumbing fixtures, other
than water closets and urinals, shall be equipped
with approved strainers having an approved
waterway area. Strainers serving shower drains
shall have a waterway equivalent to the area of
the tailpiece.
404.2 Connections. Fixtures having concealed
slip joint connections shall be provided with an
access panel or utility space at least twelve (12)
inches (305 mm) in its least dimension and so
arranged without obstructions as to make such
connections accessible for inspection and repair.
404.3 Continuous wastes and fixture tailpieces shall
be constructed from the materials specified in Section
701.0 for drainage piping, provided, however, that
such connections where exposed or accessible may be
of seamless drawn brass not less than No. 20 B&S
Gauge (0.032 inches) (0.8 mm). Each such tailpiece,
continuous waste, or waste and overflow shall not be
less than one and one-half (1-1/2) inches (40 mm) O.D.
for sinks, dishwashers, laundry tubs, bathtubs, urinals,
and similar fixtures, and not less than one and one
quarter (1-1 /4) inches (32 mm) for lavatories, drinking
fountains, and similar small fixtures.
404.4 Approved wye or other directional-type
branch fittings shall be installed in all continuous
wastes connecting or receiving the discharge from
food waste disposal units, dishwashers, clothes
washers, or other force discharge fixtures or
appliances. No dishwasher drain shall be connected to
a sink tailpiece, continuous waste, or trap on the
discharge side of a food waste disposal unit.
405.0 Prohibited Fixtures.
405.1 Water closets having an invisible seal or an
unventilated space or having walls which are not
thoroughly washed at each discharge shall be
prohibited. Any water closet that might permit
siphonage of the contents of the bowl back into the
tank shall be prohibited. Drinking fountains shall not
be installed in public toilet rooms.
29
405.2 - 408.2
UNIFORM PLUMBING CODE
405.2 Prohibited Urinals. Floor-type and wall-hung
type trough urinals shall be prohibited. Urinals that have
an invisible seal or that have an unventilated space or
wall that is not thoroughly washed at each discharge
shall be prohibited.
405.3 Fixed wooden, or tile wash trays or sinks for
domestic use shall not be installed in any building
designed or used for human habitation. No sheet
metal-lined wooden bathtub shall be installed or
reconnected. No dry or chemical closet (toilet) shall be
installed in any building used for human habitation,
unless first approved by the Health Officer.
406.0 Special Fixtures and Specialties.
406.1 Water and Waste Connections. Baptisteries,
ornamental and lily ponds, aquaria, ornamental
fountain basins, and similar fixtures and specialties
requiring water and /or waste connections shall be
submitted for approval to the Authority Having
Jurisdiction prior to installation.
406.2 Restaurant kitchen and other special use sinks
may be made of approved-type bonderized and
galvanized sheet steel of not less than No. 16 U.S.
gauge (0.0625 inches) (1.6 mm). All sheet-metal
plumbing fixtures shall be adequately designed,
constructed, and braced in an Approved manner to
satisfactorily accomplish their intended purpose.
406.3 Special Use Fixtures. Special use fixtures
shall be made of one of the following:
(A) Soapstone
(B) Chemical stoneware
(C) Copper-based alloy
(D) Nickel-based alloy
(E) Corrosion-resistant steel
(F) Other materials suited for the intended use of the
fixture.
406.4 Zinc Alloy Components. Zinc alloy com-
ponents shall meet the applicable nationally
recognized standards and shall be used in accordance
with their listing.
designed, by screws or bolts of copper, brass, or other
equally corrosion-resistant material.
407.4 Wall-Hung Fixtures. Wall-hung fixtures shall
be rigidly supported by metal supporting members so
that no strain is transmitted to the connections. Flush
tanks and similar appurtenances shall be secured by
approved non-corrosive screws or bolts.
407.5 Securing Floor-Mounted, Back-Outlet Water
Closet Bowls. Floor-mounted, back-outlet water
closet bowls shall be set level with an angle of runety
(90) degrees (1.58 rad) between the floor and wall at
the centerline of the fixture outlet. The floor and wall
shall have a flat mounting surface for at least five (5)
inches (127 mm) to the right and left of the fixture
outlet centerline. The fixture shall be secured to the
wall outlet flange or drainage connection and to the
floor by corrosion-resistant screws or bolts. The closet
flange shall be secured to a firm base.
Where floor-mounted, back-outlet water closets
are used, the soil pipe shall not be less than three (3)
inches (80 mm) in diameter. Offset, eccentric, or
reducing floor flanges shall not be used.
407.6 Setting. Fixtures shall be set level and in
proper alignment with reference to adjacent walls.
No water closet or bidet shall be set closer than
fifteen (15) inches (381 mm) from its center to any
side wall or obstruction nor closer than thirty (30)
inches (762 mm) center to center to any similar
fixture. The clear space in front of any water closet or
bidet shall not be less than twenty-four (24) inches
(610 mm). No urinal shall be set closer than twelve
(12) inches (305 mm) from its center to any side wall
or partition nor closer than twenty-four (24) inches
(610 mm) center to center.
407.7 installations for Persons with Disabilities.
Where facilities for persons with disabilities are
required in applicable building regulations, the
facilities shall be installed in accordance with those
regulations.
407.8 Supply Fittings. The supply lines and fittings
for every plumbing fixture shall be so installed as to
prevent backflow as required in Chapter 6.
407.0 Installation.
407.1 Cleaning. Plumbing fixtures shall be installed
in a manner to afford easy access for repairs and
cleaning. Where practical, all pipes from fixtures shall
be run to the nearest wall.
407.2 Joints. Where a fixture comes in contact with
the wall or floor, the joint between the fixture and the
wall or floor shall be made watertight.
407.3 Securing Fixtures. Floor-outlet or floor-
mounted fixtures shall be rigidly secured to the
drainage connection and to the floor, when so
408.0 Water Closets.
408.1 Water closet bowls for public use shall be of the
elongated type. In nurseries, schools, and other similar
places where plumbing fixtures are provided for the
use of children under six (6) years of age, water closets
shall be of a size and height suitable for children's use.
All water closets shall be equipped with seats as
required below.
408.2 Water Closet Seats.
408.2.1 Water closet seats shall be of smooth,
non-absorbent material.
30
PLUMBING FIXTURES AND FIXTURE FITTINGS
408.2 - 41 1 .5
408.2.2 All water closet seats, except those
within dwelling units, shall be either of the open
front type or have an automatic seat cover
dispenser.
408.2.3 Water closet seats shall be properly
sized for the water closet bowl type.
408.2.4 Seats for use in public buildings shall
conform to the standard listed in Table 14-1.
409.0 Urinals.
Every water supply to a urinal shall be protected by
an approved-type vacuum breaker or other
approved backflow prevention device as described
in Section 603.3.
410.0 Flushing Devices for Water Closets and
Urinals.
410.1 Flushing Devices Required. Each water
closet, urinal, clinic sink, or other plumbing fixture
that depends on trap siphonage to discharge its waste
contents shall be provided with a flushometer valve,
flushometer tank, or flush tank designed and installed
so as to supply water in sufficient quantity and rate of
flow to flush the contents of the fixture to which it is
connected, to cleanse the fixture, and to refill the
fixture trap, without excessive water use. Flushing
devices shall meet anti-siphon requirements required
in Chapter 6.
410.2 Automatic Flushing Tanks. Tanks flushing
more than one (1) urinal shall be automatic in
operation and of sufficient capacity to provide the
necessary volume to flush and properly cleanse all
urinals simultaneously. Automatically controlled
flushometer valves may be substituted for flush tanks.
410.3 Flushometer Valves. No manually controlled
flushometer valve shall be used to flush more than
one (1) urinal, and each such urinal flushometer valve
shall be an approved, self-closing type discharging a
predetermined quantity of water. Flushometers shall
be installed so that they will be accessible for repair.
Flushometer valves shall not be used where the water
pressure is insufficient to properly operate them.
When the valve is operated, it shall complete the cycle
of operation automatically, opening fully and closing
positively under the line water pressure. Each
flushometer shall be provided with a means for
regulating the flow through it.
410.4 Water Supply for Flush Tanks. An adequate
quantity of water shall be provided to flush and clean
the fixture served. The water supply for flushing tanks
and flushometer tanks equipped for manual flushing
shall be controlled by a float valve or other automatic
device designed to refill the tar\k after each discharge
and to completely shut off the water flow to the tank
when the tank is filled to operational capacity.
Provision shall be made to automatically supply water
to the fixture so as to refill the trap seal after each
flushing. The water supply to flush tanks equipped for
automatic flushing shall be controlled by a suitable
timing device.
410.5 Overflows in Flush Tanks. Flush tariks shall
be provided with overflows discharging into the
water closet or urinal connected thereto. Overflows
supplied as original parts with the fixture shall be of
sufficient size to prevent tank flooding at the
m.aximum rate at which the tank is supplied with
water under normal operating conditions and when
installed per manufacturer's instructions.
411.0 Floor Drains and Shower Stalls.
411.1 Floor drains shall be considered plumbing
fixtures, and each such drain shall be provided with
an approved-type strainer having a waterway
equivalent to the area of the tailpiece. Floor drains,
floor receptors, and shower drains shall be of an
approved type, suitably flanged to provide a
watertight joint in the floor.
411.2 Location of Floor Drains. Floor drains shall
be installed in the following areas;
411.2.1 Toilet rooms containing two (2) or
more water closets or a combination of one (1)
water closet and one (1) urinal, except in a
dwelling unit.
41 1 .2.2 Commercial kitchens.
41 1 .2.3 Laundry rooms in commercial buildings
and common laundry facilities in multi-family
dwelling buildings.
41 1 .3 Food Storage Areas. If drains are provided in
storerooms, walk-in freezers, walk-in coolers,
refrigerated equipment, or other locations where food
is stored, such drains shall have indirect waste piping.
Separate waste pipes shall be run from each food
storage area, each with an indirect cormection to the
building sanitary drainage system. Traps shall be
provided if required under Section 801.2.2 of this code
and shall be vented.
Indirect drains may be located in freezers or other
spaces where freezing temperatures are maintained,
provided that traps, when supplied, are located where
the seal will not freeze. Otherwise, the floor of the
freezer shall be sloped to a floor drain located outside
of the storage compartment.
41 1 .4 Floor Slope. Floors shall be sloped to floor drains.
411.5 Shower receptors are plumbing fixtures and
shall conform to the general requirements contained
in Section 401.0. Each such shower receptor shall be
constructed of vitrified china or earthenware, ceramic
tile, porcelain-enameled metal, or of such other
31
411.5-411.8
UNIFORM PLUMBING CODE
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
material as may be acceptable to the Authority Having
Jurisdiction. No shower receptor shall be installed
unless it conforms to acceptable standards as
referenced in Table 14-1 or until a specification or a
prototype or both of such receptor has first been
submitted to and approval obtained from the
Authority Having Jurisdiction.
41 1 .6 Each shower receptor shall be an approved type
and be so constmcted as to have a finished dam, curb,
or threshold that is at least one (1) inch (25.4 mm) lower
than the sides and back of such receptor. In no case
shall any dam or threshold be less than two (2) inches
(51 mm) or more than nine (9) inches (229 mm) in
depth when measured from the top of the dam or
threshold to the top of the drain. Each such receptor
shall be provided with an integral nailing flange to be
located where the receptor meets the vertical surface
of the finished interior of the shower compartment.
The flange shall be watertight and extend vertically a
minimum of one (1) inch (25.4 mm) above the top of
the sides of the receptor. The finished floor of the
receptor shall slope uniformly from the sides toward
the drain not less than one-quarter (1/4) inch per foot
(20.9 mm/m), nor more than one-half (1/2) inch per
foot (41.8 mm/m). Thresholds shall be of sufficient
width to accommodate a minimum twenty-two (22)
inch (559 mm) door. Shower doors shall open so as to
maintain a minimum twenty-two (22) inch (559 mm)
unobstructed opening for egress.
Exception: Showers that are designed to
comply with the accessibility standards listed in
Table 14-1.
41 1 .7 All shower compartments, regardless of shape,
shall have a minimum finished interior of one
thousand twenty-four (1,024) square inches (0.66 m^)
and shall also be capable of encompassing a thirty (30)
inch (750 mm) circle. The minimum required area and
dimensions shall be measured at a height equal to the
top of the threshold and at a point tangent to its
centerline. The minimum area and dimensions shall
be maintaiined to a point seventy (70) inches (1778
mm) above the shower drain outlet with no
protrusions other than the fixture valve or valves,
shower head, soap dishes, shelves, and safety grab
bars or rails. Fold-down seats in accessible shower
stalls shall be permitted to protrude into the thirty (30)
inch (750 mm) circle.
Exception No. 1: Showers that are designed to
comply with ICC/ANSI A117.1.
Exception No. 2: The minimum required area
and dimension shall not apply where an existing
bathtub is replaced by a shower receptor having
minimum overall dimensions of 30 inches (750
mm) in width and 60 inches (1,500 mm) in length.
411.8 When the construction of on-site built-up
shower receptors is permitted by the Authority
Having Jurisdiction, one of the following means shall
be employed:
(1) Shower receptors built directly on the
ground:
Shower receptors built directly on the ground
shall be watertight and shall be constructed
from approved-type dense, nonabsorbent
and noncorrosive materials. Each such
receptor shall be adequately reinforced, shall
be provided with an approved, flanged floor
drain designed to make a watertight joint in
the floor, and shall have smooth, impervious,
and durable surfaces.
(2) Shower receptors built aboveground:
When shower receptors are built above-
ground, the subfloor and rough side of
walls to a height of not less than three (3)
inches (76 mm) above the top of the finished
dam or threshold shall be first lined with
sheet plastic,* lead,* or copper,* or shall be
lined with other durable and watertight
materials.
All lining materials shall be pitched one-
quarter (1/4) inch per foot (20.9 mm/m) to weep
holes in the subdrain of a smooth and solidly
formed subbase. All such lining materials shall
extend upward on the rough jambs of the
shower opening to a point no less than three (3)
inches (76 mm) above the top of the finished
dam or threshold and shall extend outward over
the top of the rough threshold and be turned
over and fastened on the outside face of both the
rough threshold and the jambs.
Nonmetallic shower subpans or linings
may be built up on the job site of not less than
three (3) layers of standard, grade fifteen (15)
pound (6.8 kg) asphalt-impregnated roofing
felt. The bottom layer shall be fitted to the
formed subbase and each succeeding layer
thoroughly hot-mopped to that below. All
corners shall be carefully fitted and shall be
made strong and watertight by folding or
lapping, and each corner shall be reinforced
with suitable webbing hot-mopped in place.
All folds, laps, and reinforcing webbing shall
extend at least four (4) inches (102 mm) in all
directions from the corner, and all webbing
shall be of approved type and mesh, producing a
tensile strength of not less than fifty (50) psi
(344.5 kPa) in either direction. Nonmetallic
shower subpans or linings may also consist of
multilayers of other approved equivalent
materials suitably reinforced and carefully
fitted in place on the job site as elsewhere
required in this section.
32
PLUMBING FIXTURES AND FIXTURE FITTINGS
411.8-412.5
Linings shall be properly recessed and
fastened to approved backing so as not to
occupy the space required for the wall covering
and shall not be nailed or perforated at any
point that may be less than one (1) inch (25.4
mm) above the finished dam or threshold. An
approved-type subdrain shall be installed with
every shower subpan or lining. Each such sub-
drain shall be of the type that sets flush with the
subbase and shall be equipped with a clamping
ring or other device to make a tight connection
between the lining and the drain. The subdrain
shall have weep holes into the waste line. The
weep holes located in the subdrain clamping
ring shall be protected from clogging.
All shower lining materials shall conform to
approved standards acceptable to the Authority
Having Jurisdiction.
*Lead and copper subpans or linings shall be insulated
from all conducting substances other than their
connecting drain by fifteen (15) pound (6.8 kg) asphalt
felt or its equivalent, and no lead pan or liner shall be
constructed of material weighing less than four (4)
pounds per square foot (19.5 kg/m^). Copper pans or
liners shall be at least No. 24 B & S Gauge (0.02 inches)
(0.5 mm). Joints in lead pans or liners shall be burned.
Joints in copper pans or liners shall be soldered or
brazed. Plastic pans shall not be coated with asphalt-
based materials.
411.8.1 Tests for Shower Receptors. Shower
receptors shall be tested for watertightness by
filling with water to the level of the rough
threshold. The test plug shall be so placed that
both upper and under sides of the subpan shall
be subjected to the test at the point where it is
clamped to the drain.
41 1 .9 Floors of public shower rooms shall have a
nohskid surface and shall be drained in such a
manner that wastewater from one bather will not
pass over areas occupied by other bathers. Gutters in
public or gang shower roorhs shall have rounded
corners for easy cleaning and shall be sloped not less
than two (2) percent toward drains. Drains in gutters
shall be spaced not more than eight (8) feet (2438
mm) from sidewalls nor more than sixteen (16) feet
(4879 mm) apart.
411.10 Location of Valves and Heads. Control
valves and showerheads shall be located on the
sidewall of shower compartments or be otherwise
arranged so that the showerhead does not discharge
directly at the entrance to the compartment and the
bather can adjust the valves prior to stepping into the
shower spray.
411.11 Water Supply Riser. Every water supply
riser from the shower valve to the showerhead outlet,
whether exposed or not, shall be securely attached to
the structure.
412.0 Minimum Number of Required Fixtures.
412.1 Fixture Count. Plumbing fixtures shall be
provided for the type of building occupancy and
in the minimum number shown in Table 4-1.
412.2 Access to Fixtures.
412.2.1 In multi-story buildings, accessibility to
the required fixtures shall not exceed one (1)
vertical story.
412.2.2 Fixtures accessible only to private offices
shall not be counted to determine compliance
with this section.
412.3 Separate Facilities.
Separate toilet facilities shall be provided for each sex.
Exceptions:
(1) Residential installations.
(2) In occupancies serving ten (10) or fewer
people, one (1) toilet facility, designed for
use by no more than one (1) person at a
time, shall be permitted for use by both
sexes.
(3) In business and mercantile occupancies with
a total floor area of fifteen hundred (1500)
square feet (139.5 m^) or less, one (1)
toilet facility, designed for use by no more
than one (1) person at a time, shall satisfy
the requirements for serving customers and
employees of both sexes.
412.4 Fixture Requirements for Special Occupancies.
412.4.1 Additional fixtures may be required
when unusual environmental conditions or
special activities are encountered.
412.4.2 In food preparation areas, fixture
requirements may be dictated by health codes.
41 2.4.3 Types of occupancy not shown in Table
4-1 shall be considered individually by the
Authority Having Jurisdiction.
412.5 Facilities in Mercantile and Business
Occupancies Serving Customers.
412.5.1 Requirements for customers and
employees shall be jpermitted to be met with a
single set of restrooms accessible to both groups.
The required number of fixtures shall be the
greater of the required number for employees or
the required number for customers.
412.5.2 Fixtures for customer use shall be
permitted to be met by providing a centrally
33
412.5-418.0
UNIFORM PLUMBING CODE
located facility accessible to several stores. The
maximum distance from entry to any store to
this facility shall not exceed five hundred (500)
feet (152.4 m).
412.5.3 In stores with a floor area of one
hundred fifty (150) square feet (13.9 m^) or
less, the requirement to provide facilities for
employees shall be permitted to be met by
providing a centrally located facility accessible
to several stores. The maximum distance from
entry to any store to this facility shall not
exceed three hundred (300) feet (91.4 m).
412.6 Food Service Establishments. Food service
establishments with an occupant load of one hundred
(100) or more shall be provided with separate faicilities
for employees and customers. Customer and
employee facilities may be combined for occupant
loads less than one hundred (100).
412.7 Toilet Facilities for Workers.
Suitable toilet facilities shall be provided and
maintained in a sanitary condition for the use of
workers during construction.
413.0 Fixtures and Fixture Fittings for Persons
with Disabilities.
Plumbing fixtures and fixture fittings for persons with
disabilities shall conform to the appropriate standards
referenced in Table 14-1 of this code. -
413.1 Limitation of Hot Water Temperature for
Public Lavatories.
Hot water delivered from public-use lavatories shall
be limited to a maximum temperature of 120°F. The
water heater thermostat shall not be considered a
control for meeting this provision.
414.0 Bathtubs and Whirlpool Bathtubs.
I Unless otherwise listed, all bathtubs and whirlpool
bathtubs shall comply with the following requirements:
414.1 A removable panel shall be provided to access
and remove the pump. Whirlpool pump access
located in the crawl space shall be located no more
than twenty (20) feet (6096 mm) from an access door,
trap door, or crawl hole.
414.2 The circulation pump shall be located above the
crown weir of the trap.
414.3 The pump and the circulation piping shall be
self-draining to minimize water retention in
accordance with standards referenced in Table 14-1.
414.4 Suction fittings on whirlpool bathtubs shall
comply with the listed standards.
414.5 Limitation of Hot Water in Bathtubs and
Whirlpool Bathtubs. The maximum hot water
temperature discharging from the bathtub and
whirlpool bathtub filler shall be Limited to 120°F. The
water heater thermostat shall not be considered a
control for meeting this provision.
415.0 Installation of Fixture Fittings.
Where two separate handles control the hot and cold
water, the left-hand control of the faucet when facing
the fixture fitting outlet shall provide the means to
alter the hot water temperature from the fixture fitting.
Single-handle mixing valves shall have the flow of
hot water correspond to the markings on the fitting.
416.0 Bidets.
416.1 Materials. Bidets shall conform to the
standards listed in Table 14-1.
416.2 Backflow Protection. The water supply to the
bidet shall be protected according to Chapter 6, which
allows for an airgap or vacuum breaker.
417.0 Future Fixtures.
When provision is made for the future installation of
fixtures, those provided for shall be considered in
determining the required sizes of drain pipes.
Construction for future installations shall be
terminated with a plugged fitting or fittings. Where
the plugged fitting is at the point where the trap of a
fixture may be installed, the plumbing system for such
fixture shall be complete and conform with all
plumbing requirements of this code.
418.0 Shower and Tub-Shower Combination
Control Valves.
Showers and tub-shower combinations in all buildings
shall be provided with individual control valves of the
pressure balance, thermostatic, or combination
pressure balance/ thermostatic mixing valve type that
provide scald and thermal shock protection. These
valves shall conform to ASSE 1016. Gang showers,
when supplied with a single temperature-controlled
water supply pipe, may be controlled by a master
thermostatic mixing valve in lieu of individually
controlled pressure balance, thermostatic, or
combination pressure balance /thermostatic mixing
valves. Handle position stops shall be provided on
such valves and shall be adjusted per the
manufacturer's instructions to deliver a maximum
mixed water setting of 120°F (49°C). The water heater
thermostat shall not be considered a suitable control
for meeting this provision.
34
PLUMBING FIXTURES AND FIXTURE FITTINGS
Table 4-1
TABLE 4-1
Minimum Plumbing Facilities^
Each building shall be provided with sanitary facilities, including provisions for persons with disabilities as prescribed by the Department Having Jurisdiction. For
requirements for persons with disabilities, ICC/ANSI A1 17.1 , Accessible and Usable Buildings and Facilities, may be used.
The total occupant load shall be determined by minimum exiting requirements. The minimum number of fixtures shall be calculated at fifty (50) percent male and
fifty (50) percent female based on the total occupant load.
The occupant load and use of the building or space under consideration shall first be established using the Occupant Load Factor Table A. Once the occupant
load and uses are determined, the requirements of Section 412.0 and Table 4-1 shall be applied to determine the minimum number of plumbing fixtures required.
This table applies to new buildings, additions to a building, changes of occupancy or type in an existing building resulting in increased occupant load (example:
change an assembly room from fixed seating to open seating). Exception: New cafeterias for employee use are the only use exempted from this requirement.
Type of Building
Water Closets"
Urinals^"
Lavatories
Bathtubs or Showers
Drinking Fountains^ '*'=
or Occupancy^
(Fixtures per Person)
(Fixtures per Person)
(Fixtures per Person)
(Fixtures per Person)
(Fixtures per Person)
Assembly places -
Male Female
Male
Male Female
theatres, auditoriums.
1:1-15 1:1-15
0:1-9
1 per 40 1 per 40
convention halls, etc-
2:16-35 3:16-35
1:10-50
for permanent
3: 36-55 4: 36-55
Add one fixture
employee use
Over 55, add 1 fixture
for each additional 40
persons.
for each
additional 50 males.
Assembly places -
Male Female
Male
Male Female
theatres, auditoriums.
1:1-100 3:1-50
1:1-100
1:1-200 1:1-200
1:1-150
convention Halls, etc. -
2:101-200 4:51-100
2:101-200
2:201-400 2:201-400
2:151-400
for public use
3:201-400 8:101-200
3:201-400
3:401-750 3:401-750
3:401-750
11:201-400
4:401-600
Over 750, add one fixture
Over 750, add one fixture
Over 400, add one fixture
Over 600, add 1 fixture
for each additional 500
for each additional 500
for each additional 500
for each additional
persons.
persons.
males and 1 for each
300 males.
additional 125 females.
Dormitories'-
Male Female
Male
Male Female
1 per 8
1 per 150'^
School or labor"
1 per 10 1 per 8
1 per 25
1 per 12 1 per 12
For females, add
Add 1 fixture for each
Over 150, add 1 fixture
Over 12, add one fixture fo
1 bathtub per 30.
additional 25 males (over
for each additional 50
each additional 20 males
Over 150, add 1
10) and 1 for each additional
males.
and 1 for each 15
bathtub per 20.
20 females (over 8).
additional females.
Dormitories -
Male Female
Male
Male Female
1 per 8
for staff use"
1:1-15 1:1-15
2:16-35 3:16-35
3: 36-55 4: 36-55
Over 55, add 1 fixture for
each additional 40 persons.
1 per 50
1 per 40 1 per 40
Dwellings^
Single dwelling
1 per dwelling
1 per dwelling
1 per dwelling
Multiple dwelling or
1 per dwelling or
1 per dwelling or
1 per dwelling or
apartment house"
apartment unit
apartment unit
apartment unit
Hospital waiting rooms
1 per room
1 per room
1 per150''
Hospitals -
Male Female
Male
Male Female
for employee use
1:1-15 1:1-15
2:16-35 3:16-35
3: 36-55 4: 36-55
Over 55, add 1 fixture for
_. each additional 40j)e.rsons.
0:1-9
1:10-50
Add one fixture for each
additional 50 males.
1 per 40 1 per 40
Hospitals
Individual room
1 per room
1 per room
1 per room
Ward room
1 per 8 patients
1 per 10 patients
1 per 20 patients
1 per 150"
Industrial warehouses,
Male Female
Up to 100, 1 per 10
1 shower for
1 per 150"
workshops, foundries.
1:1-10 1:1-10
persons
each 15 persons
and similar
2:11-25 2:11-25
exposed to
establishments -
3: 26-50 3: 26-50
Over 100, 1 per 15
excessive heat or
for employee use
4:51-75 4:51-75
5:76-100 5:76-100
Over 100, add 1 fixture for
each additional 30 persons.
persons'"
to skin contam-
ination with poison-
ous, infectious, or
irritating material
Institutional - other than
Male Female
Male
Male Female
1 per 8
1 per 150"
hospitals or penal
1 per 25 1 per 20
0:1-9
1 per 10 1 per 10
institutions (on each
1:10-50
occupied floor)
Add one fixture for each
additional 50 males.
Institutional - other than
Male Female
Male
Male Female
1 per 8
1 per 1 50"
hospitals or penal
1:1-15 1:1-15
0: 1-9
1 per 40 1 per 40
institutions (on each
2:16-35 3:16-35
1:10-50
occupied floor) -
3: 36-55 4: 36-55
Add one fixture for each
for employee use
Over 55, add 1 fixture for
each additional 40 persons.
additional 50 males.
35
Table 4-1 continued
UNIFORM PLUMBING CODE
Type of Building
Water Closets"
Urinals*^"
lavatories
Bathtubs or Showers
Drinking Fountains*"
or Occupancy''
(Fixtures per Person)
(Fixtures per Person)
(Fixtures per Person)
(Fixtures per Person)
(Fixtures per Person)
Office or public
Male Female
Male
Male Female
1 per 150"
buildings
1:1-100 3:1-50
1:1-100
1:1-200 1:1-200
2:101-200 4:51-100
2: 101-200
2:201-400 2:201-400
3:201-400 8:101-200
3:201-400
3:401-750 3:401-750
11:201-400
4:401-600
Over 750, add one fixture
Over 400, add one fixture
Over 600, add 1 fixture for
for each additional 500
for each additional 500
each additional 300 males.
persons.
males and 1 for each
additional 150 females.
Office or public
Male Female
Male
Male Female
buildings -
1:1-15 1:1-15
0: 1-9
1 per 40 1 per 40
for employee use
2: 16-35 3: 16-35
3: 36-55 4: 36-55
Over 55, add 1 fixture for
each additional 40 persons.
1:10-50
Add one fixture for each
additional 50 males.
Penal institutions -
Male Female
Male
Male Female
1 per 150'=
for employee use
1:1-15 1:1-15
2:16-35 3:16-35
3: 36-55 4: 36-55
Over 55, add 1 fixture for
each additional 40 persons.
0:1-9
1:10-50
Add one fixture for each
additional 50 males.
1 per 40 1 per 40
Penal institutions -
for prison use
Cell
1 per cell
Male
1 per cell
1 per cell block floor
Exercise room
1 per exercise room
1 per exercise room
1 per exercise room
1 per exercise room
1 Public or
Same as Office or Public
Same as Office or Public
Same as Office or Public
Same as Office or Public
1 professional offices'^
Buildings for employee use
Buildings for employee use'*
Buildings for employee use
5
Buildings for employee use"
Restaurants, pubs, and
Male Female '
Male
Male Female
tounges"-^^-^
1:1-50 1:1-50
1:1-150
1:1-150 1:1-150
2:51-150 2:51-150
Over 150, add 1 fixture for
2: 151-200 2: 151-200
3:151-300 4:151-300
each additional 150 males.
3:201-400 3:201-400
Over 300, add 1 fixture for
Over 400, add 1 fixture for
each additional 200 persons.
each additional 400 persons.
Retail or
Male Female
Male
One for each two
0:1-30"
Wholesale Stores
1:1-100 1:1-25
0:0-25
water closets
1:31-150
2:101-200 2:26-100
1:26-100
One additional drinking
3:201-400 4:101-200
2:101-200
fountain for each 150
6:201-300
3:201-400
persons thereafter
8:301-400
4:401-600
Over 400, add one fixture for
Over 600, add one fixture
each additional 500 males and
for each additional
one for each 150 females
300 males
Schools - for staff use
Male Female
Male
Male Female
All schools
1:1-15 1:1-15
2: 16-35 2: 16-35
3: 36-55 3: 36-55
Over 55, add 1 fixture for
each additional 40 persons.
1 per 50
1 per 40 1 per 40
Schools - for student use
Male Female
Male Female
1 per 150"
Nursery
1:1-20 1:1-20
2:21-50 2:21-50
Over 50, add 1 fixture for
each additional 50 persons.
1:1-25 1:1-25
2: 26-50 2: 26-50
Over 50, add 1 fixture for
each additional 50 persons.
Elementary
Male Female
Male
Male Female
1 perl 50"
1 per 30 1 per 25
1 per 75
1 per 35 1 per 35
Secondary
Male Female
Male
Male Female
1 per 150"
1 per 40 1 per 30
1 per 35
1 per 40 1 per 40
Others (colleges,
Male Female
Male
Male Female
1 per 150"
universities, adult
1 per 40 1 per 30
1 per 35
1 per 40 1 per 40
centers, etc.)
Worship places
Male Female
Male
1 per 2 water closets
1 per 150"
educational and
1 per 150 1 per 75
1 per 150
activities Unit
Worship places
Male Female
Male
1 per 2 water closets
1 per 150"
principal assembly place
1 per 150 1 per 75
1 per 150
36
PLUMBING FIXTURES AND FIXTURE FITTINGS
^ The figureis shown are based upon one (1) fixture being the minimum required for the number of persons indicated or any
fraction thereof.
^ Building categories not shown on this table shall be considered separately by the Authority Having Jurisdiction.
^ Drinking fountains shall not be installed in toilet rooms.
" Laundry trays. One (1 ) laundry tray or one (1 ) automatic washer standpipe for each dwelling unit or one (1 ) laundry tray or one
(1) automatic washer standpipe, or combination thereof, for each twelve (12) apartments. Kitchen sinks, one (1) for each
dwelling or apartment unit.
^ For each urinal added in excess of the minimum required, one water closet may be deducted. The number of water closets
shall not be reduced to less than two-thirds (2/3) of the minimum requirement.
^ As required by ANSI Z4.1 , Sanitation in Places of Employment.
' Where there is exposure to skin contamination with poisonous, infectious, or irritating materials, provide one (1 ) lavatory for
each five (5) persons.
^ Twenty-four (24) lineal inches (610 mm) of wash sink or eighteen (18) inches (457 mm) of a circular basin, when provided with
water outlets for such space, shall be considered equivalent to one (1 ) lavatory.
^ Laundry trays, one (1) for each fifty (50) persons. Service sinks, one (1) for each hundred (100) persons.
^° General. In applying this schedule of facilities, consideration shall be given to the accessibility of the fixtures. Conforiiiity purely
on a numerical basis may not result in an installation suited to the needs of the individual establishment. For example, schools
should be provided with toilet facilities on each floor having classrooms.
a. Surrounding materials, wall, and floor space to a point two (2) feet (61 mm) in front of urinal lip and four (4) feet
(1219 mm) above the floor, and at least two (2) feet (610 mm) to each side of the urinal shall be lined with non-
absorbent materials.
b. Trough urinals shall be prohibited.
" A restaurant is defined as a business that sells food to be consumed on the premises.
a. The number of occupants for a drive-in restaurant shall be considered as equal to the number of parking stalls.
b. Employee toilet facilities shall not be included in the above restaurant requirements. Hand-washing facilities shall be
available in the kitchen for employees.
'^ Where food is consumed indoors, water stations may be substituted for drinking fountains. Offices, or public buildings for use
by more than six (6) persons shall have one (1) drinking fountain for the first one hundred fifty (150) persons and one (1)
additional fountain for each three hundred (300) persons thereafter.
^^ There shall be a minimum of one (1) drinking fountain per occupied floor in schools, theatres, auditoriums, dormitories, offices,
or public buildings.
'" The total number of water closets for females shall be at least equal to the total number of water closets and urinals required
for males. This requirement shall not apply to Retail or Wholesale Stores.
For smaller-type Public and Professional Offices such as banks, dental offices, law offices, real estate offices, architectural
offices, engineering offices, and similar uses. A public area in these offices shall use the requirements for Retail or Wholesale
Stores.
A unisex facility (one water closet and one lavatory) may be used when the customer occupant load for the dining area,
including outdoor seating area, is 10 or less and the total number of employees for the space is 4 or less.
Recreation or community room in multiple dwellings or apartment buildings, regardless or their occupant load, shall be
permitted to have separate single-accommodation facilities in common-use areas within tracts or multi-family residential
occupancies where the use of these areas is limited exclusively to owners, residents, and their guests. Examples are
community recreation or multi-purpose areas in apartments, condos, townhouses, or tracts.
A drinking fountain shall not be required in occupancies of 30 or less. When a drinking fountain is not required, then footnotes
3,12, and 13 are not applicable.
37
Table A
UNIFORM PLUMBING CODE
Table A. Occupant Load Factor:
Occupancy*,
Occupant Load Factor (square feet)
(CBC 2001 , Table A-29A)
Group A
3.
Auditoriums, convention halls, dance floors,
lodge rooms, stadiums, and casinos
(use 1/2 "one-half" the number of fixed seating)
Conference rooms, dining rooms, drinking
establishments, exhibit rooms, gymnasiums,
lounges, stages, and similar uses, including
restaurants classified as Group B occupancies
Worship places; principal assembly area,
educational and activity unit
(use 1/2 "one-half" the number of fixed seating)
Group B
Office or public buildings (area accessible to
the public)
Group E
Schools for daycare, elementary, secondary
Educational Facilities Other than Group E
Colleges, universities, adult centers, etc.
Group F
Workshops, foundries and similar establishments
Group H
Hazardous materials fabrication and storage
Group I
Hospital general use area, health care facilities
Group M
Retail or Wholesale stores
Group R
Congregate residence. Group R-1
Group S
Warehouse
15
(where no fixed seating is provided)
30
30
(where no fixed seating is provided)
200
50
50
2,000
2,000
200
200
200
5,000
Any uses not specifically listed shall be based on similar uses listed in this table.
For building or space with mixed occupancies, use appropriate occupancy group for each area (for
example, a school may have an "A" occupancy for the gymnasium, a "B" occupancy for the office, an
"E" occupancy for the classrooms, etc.)
Accessory areas may be excluded (for example: hallway, restroom, stair enclosure)
38
CHAPTER 5
WATER HEATERS
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Parti
501.0 General.
The regulations of this chapter shall govern the
construction, location, and installation of fuel-
burning and other water heaters heating potable
water, together with all chimneys, vents, and their
connectors. The minimum capacity for water heaters
shall be in accordance with the first hour rating listed
in Table 5-1. All design, construction, and work-
manship shall be in conformity with accepted
engineering practices, manufacturer's installation
instructions, and applicable standards and shall be of
such character as to secure the results sought to be
obtained by this code. No water heater shall be
hereinafter installed that does not comply in all
respects with the type and model of each size thereof
approved by the Authority Having Jurisdiction. A
list of accepted gas equipment standards is included
in Table 14-1.
502.0 Definitions.
502.1 Appliance Categorized Vent Diameter/Area.
The minimum vent area /diameter permissible for
Category I appliances to maintain a nonpositive vent
static pressure when tested in accordance with
nationally recogruzed standards. [NFPA 54: 3.3.7]
502.2 Chimney. (See also Gas Vent, and Venting
System.) One or more passageways, vertical or
nearly so, for conveying flue or vent gases to the
outside atmosphere. [NFPA 54: 3.3.17]
502.3 Chimney, Factory-Built. A chimney composed
of listed factory-built components assembled in
accordance with the terms of listing to form the
completed chinmey. [NFPA 54: 3.3.17.2]
502.4 Chimney, Masonry. A field-constructed
chimney of solid masonry units, bricks, stones, listed
masonry chimney units, or reinforced portland
cement concrete, lined with suitable chimney flue
liners. [NFPA 54: 3.3.17.3]
502.5 Chimney, Metal. A field-constructed chimney
of metal. [NFPA 54: 3.3.17.4]
502.6 Combustible Material. As pertaining to
materials adjacent to or in contact with heat-producing
appliances, vent connectors, gas vents, chimneys, steam
and hot water pipes, and warm air ducts, shall mean
materials made of or surfaced with wood, compressed
paper, plant fibers, or other materials that are capable
of being ignited and burned. Such material shall be
considered combustible even though flame-proofed,
ftre-retardant treated, or plastered. [NFPA 54: 3.3.65.1]
502.7 Direct-Vent Appliances. Appliances that are
constructed and installed so that all air for combustion
is derived directly from the outside atmosphere and
all flue gases are discharged to the outside
atmosphere. [NFPA 54: 3.3.6.3]
502.8 Flue Collar. That portion of an appliance
designed for the attachment of a draft hood, vent
connector, or venting system. [NFPA 54: 3.3.45]
502.9 Gas Vent, Type B. A vent for venting-Usted
gas appliances with draft hoods and other Category I
appliances listed for use with Type B gas vents.
[NFPA 54: 3.3.103.2.2]
502.10 Gas Vent, Type L. A vent for venting
appliances listed for use with Type L vents and
appliances listed for use with Type B gas vents.
[NFPA 54: 3.3.103.2.4]
502.11 Indirect-Fired Water Heater. A water heater
consisting of a storage tank equipped with an internal
or external heat exchanger used to transfer heat from
an external source to heat potable water. The storage
tank may contain heated potable water or water
supplied from an external source, such as a boiler.
502.12 Vent. A passageway used to convey flue gases
from gas utilization equipment or their vent connectors
to the outside atmosphere. [NFPA 54: 3.3.103]
502.13 Vent Connector. The pipe or duct that
connects a fuel-gas-burning appliance to a vent or
chimney. [NFPA 54: 3.3.104]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
TABLE 5-r FIRST HOUR RATING
Number of Bathrooms
1 to 1 .5
2 to 2.5
3 to 3.5
Number of Bedrooms
1
2
3
2
3
4
5
3
4 1
5
6
First Hour Rating,^ Gallons
42
54
54
54
67
67
80
67
80
80
80
Note:
1 The first hour rating is found on the "Energy Guide" lable.
2 Non-storage and solar water heaters shall be sized to meet the appropriate first hour rating as shown in the table.
39
502.14-506.1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
502.14 Venting System. A continuous open
passageway from the flue collar or draft hood of a
gas-burning appliance to the outside atmosphere for
the purpose of removing flue or vent gases. [NFPA
54:3.3.96.6]
502.15 Water Heater. An appliance for supplying hot
water for domestic or commercial purposes. [NFPA
54: 3.3.55.7]
503.0 Permits.
It shall be unlawful for any person to install, remove, or
replace or cause to be installed, removed, or replaced
any water heater without first obtaining a permit from
the Authority Having Jurisdiction to do so.
504.0 Inspection.
504.1 Inspection of Chimneys or Vents. This
inspection shall be made after all chimneys, vents, or
parts thereof, authorized by the permit, have been
installed and before any such vent or part thereof has
been covered or concealed.
504.2 Final Water Heater Inspection. This
inspection shall be made after all work authorized by
the permit has been installed. The Authority Having
Jurisdiction will make such inspection as deemed
necessary to be assured that the work has been
installed in accordance with the intent of this code.
No equipment or part thereof shall be covered or
concealed until the same has been inspected and
approved by the Authority Having Jurisdiction.
505.0 Water Heater Requirements.
505.1 Location. Water heater installations in bed-
rooms and bathroom^s shall comply with one of the
following [NFPA 54: 10.28.1]:
(1) Fuel-burning water heaters may be installed in a
closet located in the bedroom or bathroom provided
the closet is equipped with a listed, gasketed door
assembly and a listed self-closing device. The self-
closing door assembly shall ineet the requirements of
Section 505.1.1. The door assembly shall be installed
with a threshold and bottom door seal and shall
meet the requirements of Section 505.1.2. All
combustion air for such installations shall be
obtained from the outdoors in accordance with
Section 507.4. The closet shall be for the exclusive
use of the water heater.
(2) Water heater shall be of the direct vent type.
[NFPA 54: 10.28.1.2]
505.1.1 Self-Closing Doors. Self-closing doors
shall swing easily and freely and shall be
equipped with a self-closing device to cause the
door to close and latch each time it is opened.
The closing mechanism shall not have a hold-
open featiire. [NFPA 80: 6.1.4.2]
505.1.2 Gasketing. Gasketing on gasketed doors
or frames shall be furnished only in accordance
with the published listings of the doors, frame,
or gasketing material manufacturer. [NFPA 80:
6.4.8]
Exception: Where acceptable to the Authority
Having Jurisdiction, gasketing of noncombustible
or limited-combustible material (see NFPA 220)
Standard on Types of Building Construction)
shall be permitted to be applied to the frame,
provided closing and latching of the door are not
inhibited.
505.2 Water heaters of other than the direct-vent
type shall be located as close as practical to the
chimriey oi: gas vent. [NFPA 54: 9.28.1.2]
505.3 Clearance.
505.3.1 The clearances shall not be such as to
interfere with combustion air, draft hood clearance
and relief, and accessibility for servicing. Listed
water heaters shall be installed in accordance with
their listings and the manufacturers' instructions.
[NFPA 54: 10.28.2.1]
505.3.2 Unlisted water heaters shall be installed
with a clearance of 12 inches (300 mm) on all sides
and rear. Combustible floors under unlisted
water heaters shall be protected in an approved
manner. [NFPA 54: 10.28.2.2]
505.4 Pressure-Limiting Devices. A water heater
installation shall be provided with overpressure
protection by means of an approved, listed device,
installed in accordance with the terms of its listing and
the manufacturer's instructions. [NFPA 54: 10.28.3]
505.5 Temperature-Limiting Devices. A water
heater installation or a hot water storage vessel
installation shall be provided with overtemperature
protection by means of an approved, listed device
installed in accordance with the terms of its listing and
the manufacturer's instructions. [NFPA 54: 10.28.4]
505.6 Temperature, Pressure, and Vacuum Relief
Devices. The installation of temperature, pressure,
and vacuum relief devices or combinations thereof,
and automatic gas shutoff devices, shall be installed
in accordance with the terms of their listings and the
manufacturers' instructions. A shutoff valve shall not
be placed between the relief valve and the water
heater or on discharge pipes between such valves
and the atmosphere. The hourly Btu discharge
capacity or the rated steam relief capacity of the
device shall not be less than the input rating of the
water heater. [NFPA 54: 10.28.5]
506.0 Oil-Burning and Other Water Heaters.
506.1 Water heaters deriving heat from fuels or types
of energy other than gas shall be constructed and
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
40
WATER HEATERS
506.1-507.1
in accordance with approved standards. Vents or
chimneys for such appliances shall be approved
types. An adequate supply of air for combustion and
for adequate ventilation of heater rooms or
I compartments shall be provided. Each such appliance
shall be installed in a location approved by the
Authority Having Jurisdiction and local and state
fire-prevention agencies.
506.2 All storage-type water heaters and hot water
boilers deriving heat from fuels or types of energy
other than gas, shall be provided with, in addition to
the primary temperature controls, an overtemperature
safety protection device constructed, listed, and
installed in accordance with nationally recognized
applicable standards for such devices and a
combination temperature and pressure-relief valve.
506.3 Oil-fired water heaters shall be installed in
accordance with NFPA 31, Standard for the Installation
of Oil-Burning Equipment.
506.4 indirect-Fired Water l-leaters
506.4.1 Indirect-fired water heaters shall
conform to applicable sections of the ASME
Boiler and Pressure Vessel Code, or to one of the
other applicable standards shown in Table 14-1.
Each water heater shall bear a label in
accordance with ASME requirements, or an
approved testing agency, certifying and attesting
that such equipment has been tested and
inspected and meets the requirements of the
applicable standards or code.
506.4.2 Indirect-fired water heater that incor-
porate a single-wall heat exchanger shall meet
all of the following requirements:
(1) Connected to a low-pressure hot water
boiler limited to a maximum of 30 psig by an
approved safety or relief valve.
(2) Heater transfer medium is either potable
water or contains fluids having a toxicity rating
or Class of 1.
(3) Bear a label with the word "Caution,"
followed by the following statements:
(a) The heat-transfer medium must be water
or other nontoxic fluid having a toxic rating
or Class of 1 as listed in Clinical Toxicology
of Commercial Products, 5th edition.
(b) The pressure of the heat-transfer
medium must be limited to a maximum of
30 psig by an approved safety or relief
valve.
Note: The word "Caution" and the statements
in letters having a minimum uppercase
height of 0.120 inch (3.05 mm). The
minimum vertical spacing between lines of
type shall be 0.046 inch (1.17 mm).
Lowercase letters shall be compatible with
the uppercase letter size specification.
507.0 Air for Combustion and Ventilation.
507.1 General.
507.1.1 Air for combustion, ventilation, and
dilution of flue gases for gas utilization equipment
installed in buildings shall be obtained by
application of one of the methods covered in
Sections 507.2.1 through 507.7. Gas utilization
equipment of other than natural draft and
Category I vented appliances shall be provided
with combustion, ventilation, and dilution air in
accordance with the equipment manufacturer's
instructions. Where infiltration does not provide the
necessary air, outdoor air shall be introduced in
accordance with methods covered in Sections 507.4
through 507.7. [NFPA 54: 8.3.1.1]
Exception No. 1: This provision shall not
apply to direct-vent appliances. [NFPA 54:
8.3.1.1]
Exception No. 2: Type 1 clothes dryers that
are provided with make-up air in
accordance with section NFPA 54: 8.4.3.
507.1.1.1 Clothes Dryer. A device used to
dry wet laundry by means of heat derived
from the combustion of fuel gases. [NFPA
54: 3.3.18]
507.1.1.2 Clothes Dryer, Type 1. Primarily
used in family living environment. May
or may not be coin-operated for public use.
[NFPA 54: 3.3.18.1]
507.1.1.3 Exhausting to the Outdoors.
Type 1 and Type 2 clothes dryers shall be
exhausted to the outside air. [NFPA 54: 10.4.2]
507.1.1.4 Provisions for Make-Up Air.
Make-up air shall be provided for Type 1
clothes dryers in accordance with the
manufacturers' installation instructions.
[NFPA 54: 10.4.3.1]
507.1.2 Gas appliances of other than natural
draft design and other than Category I vented
appliances shall be provided with combustion,
ventilation, and dilution air in accordance with
the appliance manufacturer's instructions.
[NFPA 54: 9.3.1.2]
507.1 .3 Where used, a draft hood or a barometric
draft regulator shall be installed in the same
room or enclosure as the equipment served so as
to prevent any difference in pressure between the
hood or regulator and the combustion air supply.
[NFPA 54: 9.3.1.4]
507.1.4 Makeup air requirements for the
operation of exhaust fans, kitchen ventilation
systems, clothes dryers, and fireplaces shall be
considered in determining the adequacy of a
space to provide combustion air requirements.
[NFPA 54: 9.3.1.5]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
41
507.2 - 507.4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
507.2 Sndoor Combustion Air. The required
volume of indoor air shall be determined in
accordance with Sections 507.2.1 or 507.2.2 except
that where the air infiltration rate is known to be less
than 0.40 ACH, Section 507.2.2 shall be used. The
total required volume shall be the sum of the
required volume calculated for all appliances located
within the space. Rooms communicating directly
with the space in which the appliances are installed
through openings not furnished with doors, and
through combustion air openings sized and located
in accordance with Section 507.3 are considered a
part of the required volume. [NFPA 54: 9.3.2]
507.2.1 Standard Method. The minimum
required volume shall be 50 cubic feet per 1,000
Btu/hour (4.8 mVkW). [NFPA 54: 9.3.2.1]
507.2.2 Known Air Infiltration Rate Method.
Where the air infiltration rate of a structure is
known, the minimum required volume shall be
determined as follows [NFPA 54: 9.3.2.2]:
(1) For appliances having other than fan-assisted,
comibustion systems: calculate using Equation
5-1 but no smaller than 35 cubic feet per 1,000
Btu/hour (3.4 mVkW). [NFPA 54: 9.3.2.2(1)]
(2) For fan-assisted combustion system appliances,
calculate using Equation 5-2 but no smaller
than 25 cubic feet per 1,000 Bhi/hour (2.4 mVkW).
[NFPA 54: 9.3.2.2(2)]
Equation 5-1:
Required Volume (,f;;e^ > (21ff /ACH)x ( I^^/jg^/l^OOO Btu/h)
Equation 5-2:
Required Volume ya„ > ( 15 ftVACH) x ( y^^/ 1,000 Btu/h)
Where:
Igther ~ ^^^ Appliances other than Fan-Assisted
Input in Btu/hour
Fan-Assisted Appliance Input in Btu/hour
Air Change per Hour (Percent of volume of
space exchanged per hour, expressed as a
decimal)
Indoor Opening Size and Location.
Openings used to connect indoor spaces shall be
sized and located in accordance with the following
[NFPA 54: 9.3.2.3]:
(1) Combining spaces on the same story. Each
opening shall have a minimum free area of
1 in.V 1,000 Btu/h (2200 mmVkW) of the
total input rating of all gas utilization
equipment in the space, but not less than
100 in.' (0.06 m'). One opening shall
commence within 12 inches (300 mm) of the
top, and one opening shall commence
within 12 inches (300 mm) of the bottom of
'■fan ~
ACH
507.3
the enclosure [see Figure 5-7]. The
minimum dimension of air openings shall
be not less than 3 inches (80mm). [NFPA
54:9.3.2.3(1)]
(2) Combining spaces in different stories. The
volumes of spaces in different stories shall be
considered as conrniunicating spaces where
such spaces are connected by one or miore
openings in doors or floors having a total
minimum free area of 2 in. V 1/000 Btu/h
(4,400 mmVkW) of total input rating of all
gas utilization equipment. [NFPA 54: 8.3.2.3(2)]
507.4 Outdoor Combustion Air. Outdoor combustion
air shall be provided through opening(s) to the
outdoors in accordance with methods in Sections
507.4.1 or 507.4.2. The minimum dimension of air
openings shall not be less than 3 inches (80 mm). [NFPA
54:9.3.3]
507.4.1 Two Permanent Openings Method:
Two permanent openings, one commencing
within 12 inches (300 mm) of the top and one
commencing within 12 inches (300 rmn) of the
bottom of the enclosure shall be provided. The
openings shall communicate directly, or by
ducts, with the outdoors or spaces that freely
communicate with the outdoors as follows. [See
Figure 5-8 through 5-11.] [NFPA 54: 9.3.3.1]
(1) Where directly communicating with the
outdoors or where contmunicating to the
outdoors through vertical ducts, each
opening shall have a minimum free area of 1
in.V4000 Btu/h (550 mmVkW) of total input
rating of all equipment in the enclosure. [See
Figures 5-8 and 5-9.] [NFPA 54: 9.3.3.1(1)]
(2) Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in.V2,000
Btu/h (1,100 mmVkW) of total input rating
of all equipment in the enclosure. [See
Figure 5-10] [NFPA 54: 9.3.3.1(2)]
507.4.2 One Permanent Opening Method:
One permanent opening, commencing within 12
inches (300 mm) of the top of the enclosure, shall
be provided. The equipment shall have clearances
of at least 1 inch (25 mm) from the sides and back
and 6 inches (160 mm) from the front of the
appliance. The opening shall directly
communicate with the outdoors or shall
communicate through a vertical or horizontal
duct to the outdoors or spaces that freely
communicate with the outdoors [see
Figure 5-11] and shall have a minimum free area of
the foUowing [NFPA 54: 9.3.3.2] :
(1) 1 in.V3000 Btu/h (700 mmVkW) of the
total input rating of all equipment located in
the enclosure, and [NFPA 54: 9.3.3.2(1)]
(2) Not less than the sum of the areas of all vent
connectors in the space. [NFPA 54: 9.3.3.2(2)]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
I NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
42
WATER HEATERS
507.5 - 507.9
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
TIA NFPA
NFPA
NFPA
ISA NFPA
TIA NFPA
507.5 Combination Indoor and Outdoor Com-
bustion Air. The use of a combination of indoor and
outdoor combustion air shall be in accordance with
Sections 507.5.1, 507.5.2 and 507.5.3 [see example
calculation in NFPA 54 Annex J and this chapter -
Part II] [NFPA 54: 9.3.4].
507.5.1 Indoor Openings. Where used,
openings connecting the interior spaces shall
comply with Section 507.3. [NFPA 54: 9.3.4(1)]
507.5.2 Outdoor openings shall be located in
accordance with Sections 507.4.1 or 507.4.2.
[NFPA 54: 9.3.4(2)]
507.5.3 Outdoor Openings Size. The outdoor
openings size shall be calculated in accordance
with the following [NFPA 54: 9.3.4(3)]:
(1) The ratio of interior spaces shall be the
available volume of all communicating spaces
divided by tlie required vokime.
(2) The outdoor size reduction factor shall be 1
minus the ratio of interior spaces.
(3) The minimum size of outdoor openings
shall be the full size of outdoor openings
calculated in accordance with Sections
507.4.1 or 507.4.2, multiplied by the
reduction factor. The minimum dimension
of air openings shall not be less than 3 inches
(80 mm). [NFPA 54: 8.3.4(3)(c)]
507.6 Engineered Installations. Engineered
combustion air installations shall provide an
adequate supply of combustion, ventilation, and
dilution air and shall be approved by the Authority
Having Jurisdiction. [NFPA 54: 9.3.5]
507.7 Mechanical Combustion Air Supply. Where
all combustion air is provided by a mechanical air
supply system, the combustion air shall be supplied
from outdoors at the minimum rate of 0.35 feet^/min
per 1,000 Btu/h (0.034 mVmin per kW) for all
appliances located within the space. [NFPA 54: 9.3.6]
507.7.1 Where exhaust fans are installed,
additional air shall be provided to replace the
exhausted air. [NFPA 54: 9.3.6.1]
507.7.2 Each of the appliances served shall be
interlocked to the mechanical air supply
system to prevent main burner operation
where the mechanical air supply system is not
in operation. [NFPA 54: 9.3.6.2]
507.7.3 Where combustion air is provided by
the building's mechanical ventilation system, the
system shall provide the specified combustion
air rate in addition to the required ventilation
air. [NFPA 54: 9.3.6.3]
507.8 Louvers Grilles and Screens.
(A) Louvers and Grilles. The required size of
openings for combustion, ventilation,and
dilution air shall be based on the net free area
of each opening. Where tlie free area through
a design of louver or grille is known, it shall
be used in calculating the size opening
required to provide the free area specified.
Where the design and free area are not
known, it shall be assumed that wood louvers
will have 25 percent free area and metal
louvers and grilles will have 75 percent free
area. Nonmotorized louvers and grilles
shall be fixed in the open position. [NFPA
54: 9.3.7.1]
(B) Screens. Screens shall not be smaller than
1/4-inch mesh. [NFPA 54: 9.3.7.2]
(C) Motorized louvers shall be interlocked with
the equipment so they are proven in tlie full
open position prior to maui burner ignition
and during main burner operation. Means
shall be provided to prevent the main burner
from igniting should the louver fail to open
during burner start-up and to shut down the
main burner if the louvers close during
burner operation. [NFPA 54: 9.3.7.3]
507.9 Combustion Air Ducts. Combustion air ducts
shall comply with the following:
(1) Ducts shall be of galvanized steel or a
material having equivalent corrosion resis-
tance, strength, and rigidity. [NFPA 54: 9.3.8.1]
Exception: Within dwelling units, un-
obstructed stud and joist spaces shall not be
prohibited from conveying combustion air,
provided that not more than one fireblock is
removed.
(2) Ducts shall terminate in an unobstructed
space, allowing free movement of combustion
air to the appliances. [NFPA 54: 9.3.8.2]
(3) Ducts shall serve a single space.
[NFPA 54: 9.3.8.3]
(4) Ducts shall not service both upper and
lower combustion air openings where both
such openings are used. The separation
between ducts serving upper and lower
combustion air openings shall be maintained
to the source of combustion air. [NFPA 54: 9.3.8.4]
(5) Ducts shall not be screened where termi-
nating in an attic space. [NFPA 54:9.3.8.5]
(6) Intakes for combustion air ducts located
exterior to the building shall have tlie lowest
side of the combustion air intake openings
located at least 12 inches (300 mm) vertically
from the adjoining grade level.
(7) Horizontal upper combustion air ducts shall
not slope downward toward the source of
combustion air. [NFPA 54: 9.3.8.6]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
.NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
TIA
NFPA
NFPA
NFPA
NFPA
NFPA
43
507.9-508.11
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(8) The remaining space surrounding a chimney
liner, gas vent, special gas vent, or plastic
piping installed within a masomy chimney
flue, metal or factory-built chimney, shall not
be used to supply combustion air [NFPA 54:
9.3.8.7], unless it is listed and shown in the
manufacturer's installation instructions.
508.0 Other Water Heater Installation Requirements.
508.1 The Authority Having Jurisdiction shall have the
authority to require the use of an approved dielectric
insulator on the water piping connections of water
heaters and related water heating equipment.
508.2 In seismic design categories C, D, E, and F,
water heaters shall be anchored or strapped to resist
horizontal displacement due to earthquake motion.
Strapping shall be at points within the upper one-
third (1/3) and lower one-third (1/3) of its vertical
dimensions. At the lower point, a minimum distance
of four (4) inches (102 mm) shall be maintained
above the controls with the strapping.
508.3 A water heater supported from the ground
shall rest on level concrete or other approved base
extending not less than three (3) inches (76 mm)
above the adjoining ground level.
508.4 When a water heater is located in an attic, attic-
ceiling assembly, floor-ceiling assembly, or floor-
subfloor assembly where damage may result from a
leaking water heater, a watertight pan of corrosion-
resistant materials shall be installed beneath the
water heater with a minimum three-quarter (3/4)
inch (20 mm) diameter drain to an approved location.
508.5 Relief Valve Discharge.
Discharge from a relief valve into a water heater pan
shall be prohibited.
508.6 Added or Converted Equipment. When addi-
tional or replacement equipment is installed or an
appliance is converted to gas from another fuel, the
location in which the equipment is to be operated shall
be checked to verify the following [NFPA 54: 9.1.2]:
508.6.1 Air for combustion and ventilation is
provided where required, in accordance with the
provisions of Section 507.0. Where existing
facilities are not adequate, they shall be
upgraded to Section 507.0 specifications [NFPA
54: 9.1.2(1)].
508.6.2 The installation components and equip-
ment meet the clearances to combustible material
provisions of NFPA 54: 9.2.2. It shall be deter-
mined that the installation and operation of
the additional or replacement equipment does
not render the remaining equipment unsafe for
continued operation. [NFPA 54: 9.1.2(2)]
(The following reference was extracted from NFPA 54.)
9.2.2 Clearance to Combustible Materials. Gas
utilization equipment and their vent connectors shall be
installed with clearances from combustible material so
their operation will not create a hazard to persons or
property. Minimum clearances between combustible
walls and the back and sides of various conventional
types of equipment and their vent connectors are
specified in Chapters 9 and 10. (Reference can also be
made to NFPA 211, Standard for Chimneys, Fireplaces,
Vents, and Solid Fuel-Burning Appliances.)
508.6.3 The venting system is constructed and
sized in accordance with the provisions of this
chapter. Where the existing venting system is
not adequate, it shall be upgraded to comply
with this chapter. [NFPA 54: 9.1.2(3)]
508.7 Types of Gases. It shall be determined
whether the gas-utilization equipment has been
designed for use with the gas to which it will be
connected. No attempt shall be made to convert the
equipment from the gas specified on the rating plate
for use with a different gas without consulting the
installation instructions, the serving gas supplier, or
the equipment manufacturer for complete
instiructions. [NFPA 54: 9.1.3]
508.8 Safety Shutoff Devices for Unlisted LP-Gas
Equipment Used Indoors. Unlisted gas utilization
equipment for use with undiluted liquefied
petroleum gases and installed indoors shall be
equipped with safety shutoff devices of the complete
shutoff type. [NFPA 54: 9.1.4]
508.9 Use of Air or Oxygen Under Pressure. Where
air or oxygen under pressure is used in connection with
the gas supply, effective means such as a back-pressure
regulator and relief valve shall be provided to prevent
air or oxygen from passing back into the gas piping.
Where oxygen is used, installation shall be in accordance
witii NFPA 51, Standard for the Design and Installation of
Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied
Processes. [NFPA 54: 9.1.5]
508.10 Protection of Gas Equipment from Fumes
or Gases Other than Products of Combustion.
Non-direct vent-type gas appliances installed in
beauty shops, barbershops, or other facilities where
chemicals that generate corrosive or flammable
products such as aerosol sprays are routinely used
shall be located in an equipment room separate or
partitioned off from other areas with provisions for
combustion and dilution air from outdoors. Direct
vent equipment shall be installed in accordance with
the appliance manufacturer's installation instructions.
[NFPA 54: 9.1.6.2]
508.11 Process Air. In addition to air needed for
combustion in commercial or industrial processes,
process air shall be provided as required for cooling
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
44
WATER HEATERS
508.11 -508.20
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
of equipment or material, controlling dew point,
heating, drying, oxidation, dilution, safety exhaust,
odor control, air for compressors, and for comfort
and proper working conditions for personnel.
[NFPA 54: 9.1.7]
508.12 Building Structural Members.
508.12.1 Structural members of a building shall
not pass through gas utilization equipment
having an operating temperature in excess of
500°F (260°C). [NFPA 54: 9.1.8.1]
508.12.2 Structural members passing through
gas utilization equipment having an operating
temperature of 500°F (260°C) or less shall be of
noncombustible material. Building columns,
girders, beams, or trusses shall not be installed
within equipment, unless insulation and
ventilation are provided to avoid all
deterioration in strength and linear expansion of
the building structure in either a vertical or a
horizontal direction. [NFPA 54: 9.1.8.2]
508.12.3 Gas utilization equipment shall be
furnished either with load-distributing bases or
with a sufficient number of supports to prevent
damage to either the building structure or
equipment. [NFPA 54: 9.1.8.3]
508.12.4 At the locations selected for installation
of gas utilization equipment, the dynamic and
static load-carrying capacities of the building
structure shall be checked to determine whether
they are adequate to carry the additional loads.
The equipment shall be supported and shall be
connected to the piping so as not to exert undue
stress on the connections. [NFPA 54: 9.1.8.4]
508.13 Flammable Vapors. Gas appliances shall
not be installed in areas where the open use,
handling, or dispensing of flammable liquids
occurs, unless the design, operation, or installation
reduces the potential of ignition of the flammable
vapors. Gas utilization equipment installed in
compliance with Sections 508.14, 508.15, or 508.16
shall be considered to comply with the intent of this
provision. [NFPA 54: 9.1.9]
508.14 Installation in Residential Garages.
(1) Gas utilization equipment in residential
garages and in adjacent spaces that open to
the garage and are not part of the living
space of a dwelling unit shall be installed so
that all burners and burner-ignition devices
are located not less than 18 inches (450 rmn)
above the floor unless listed as flammable
vapor ignition resistant. [NFPA 54: 9.1.10.1]
(2) Such equipment shall be located or
protected so it is not subject to physical damage
by a moving vehicle. [NFPA 54: 9.1.10.2]
(3) When appliances are installed in a separate,
enclosed space having access only from
outside of the garage, such equipment may
be installed at floor level, providing the
required combustion air is taken from the
exterior of the garage. [NFPA 54: 9.1.10.3]
508.15 Installation in Commercial Garages.
508.15.1 Parking Structures. Gas utilization
equipment installed in enclosed, basement, and
underground parking structures shall be
installed in accordance with NFPA 88A, Standard
for Parking Structures. [NFPA 54: 9.1.11.1]
508.15.2 Repair Garages. Gas utilization
equipment installed in repair garages shall be
installed in a detached building or room,
separated iiom repair areas by waUs or partitions,
floors, or floor-ceiling asseimblies that are
constructed so as to prohibit the transmission of
vapors and having a fire-resistance rating of not
less than 1 hour, and that have no openings in the
wall separating the repair area within 8 feet (2.5 m)
of the floor. Wall penetrations shall be fire-
stopped. Air for combustion purposes shall be
obtained from outside the building. The heating
room shall not be used for the storage of com-
bustible materials. [NFPA 54: 9.1.11.2]
Exception No. 1: Overhead heaters where
installed not less than 8 ft (2.5 m) above the
floor shall be permitted.
Exception No. 2: Heating equipment for
vehicle repair areas where there is no
dispensing or transferring of Class I or Class
IT flammable or combustible liquids or
liquefied petroleum gas shall be installed in
accordance with NFPA 30 A, Automotive and
Marine Service Station Code.
[NFPA 54: 8.1.11.2]
508.16 Installation in Aircraft Hangars. Heaters
in aircraft hangars shall be installed in accordance
with NFPA 409, Standard on Aircraft Hangars.
[NFPA 54: 9.1.12]
508.17 Gas Equipment Physical Protection.
Where it is necessary to locate gas utilization
equipment close to a passageway traveled by vehicles
or equipment, guardrails or bumper plates shall be
installed to protect the equipment from damage.
[NFPA 54: 9.1.13]
508.18 Venting of Flue Gases.. Gas utiHzation
equipment shall be vented in accordance with the
provisions of this chapter and NFPA 54, Chapter 10.
[NFPA 54: 9.1.14]
508.19 Extra Device or Attachment. No device or
attachment shall be installed on any gas utilization
equipment that could in any way impair the
combustion of gas. [NFPA 54: 9.1.15]
508.20 Adequate Capacity of Piping. When
additional gas utilization equipment is being
connected to a gas piping system, the existing
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
45
508.20 - 508.27
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
piping shall be checked to determine if it has
adequate capacity. (See Section 1209.4.3.) Where
inadequate, the existing system shall be enlarged as
necessary, or separate gas piping of adequate
capacity shall be run from the point of delivery to
the equipment. [NFPA 54: 9.1.16]
508.21 Avoiding Strain on Gas Piping. Gas
utilization equipment shall be supported and so
connected to the piping as not to exert undue strain
on the cormections. [NFPA 54: 9.1.17]
508.22 Gas Appliance Pressure Regulators.
Where the gas supply pressure is higher than that at
which the gas utilization equipment is designed to
operate or varies beyond the design pressure limits
of the equipment, a gas appliance pressure regulator
shall be installed. [NFPA 54: 9.1.18]
508.23 Venting of Gas Appliance Pressure
Regulators. Venting of gas appliance pressure
regulators shall comply with the following
requirements [NFPA 54: 9.1.19]:
508.23.1 Gas appliance pressure regulators
requiring access to the atmosphere for successful
operation shall be equipped with vent piping
leading outdoors or, if the regulator vent is an
integral part of the equipment, into the
con\bustion chamber adjacent to a continuous
pilot, unless constructed or equipped with a vent
limiting means to limit the escape of gas from the
vent opening in the event of diaphragm failure.
[NFPA 54: 9.1.19(1)]
508.23.2 Vent limiting means shall be employed
on listed gas appliance pressure regulators only.
[NFPA 54: 9.1.19(2)]
508.23.3 In the case of vents leading outdoors,
means shall be employed to prevent water from
entering this piping and also to prevent blockage
of vents by insects and foreign matter.
[NFPA 54: 9.1.19(3)]
508.23.4 Under no circumstances shall a
regulator be vented to the gas utilization equip-
ment flue or exhaust system. [NFPA 54: 9.1.19(4)]
508.23.5 In the case of vents entering the
combustion chamber, the vent shall be located so
the escaping gas will be readily ignited by the
pilot and the heat liberated thereby will not
adversely affect the normal operation of the
safety shutoff system. The terminus of the vent
shall be securely held in a fixed position relative to
the pUot. For manufactured gas, tiie need for a flame
arrester in the vent piping shall be determined.
[NFPA 54: 9.1.19(5)]
508.23.6 Vent lines from a gas appliance
pressure regulator and bleed lines from a
diaphragm-type valve shall not be connected to a
common manifold terniinating in a combustion
chamber. Vent lines shall not terminate in
positive-pressure-type combustion chambers.
[NFPA 54: 9.1.19(6)]
508.24 Bleed Lines for Diaphragm-Type Valves.
Bleed lines shall comply with the following
requirements [NFPA 54: 9.1.20]:
508.24.1 Diaphragm-type valves shall be
equipped to convey bleed gas to the outside
atmosphere or into the combustion chamber
adjacent to a continuous pilot. [NFPA 54: 9.1.20(1)]
508.24.2 In the case of bleed lines leading
outdoors, means shall be employed to prevent
water from entering this piping and also to prevent
blockage of vents by insects and foreign matter.
[NFPA 54: 9.1.20(2)]
508.24.3 Bleed lines shall not terminate in the
gas utilization equipment flue or exhaust
system. [NFPA 54: 9.1.20(3)]
508.24.4 In the case of bleed lines entering the
combustion chamber, the bleed line shall be
located so the bleed gas will be readily ignited by
the pilot and the heat liberated thereby will not
adversely affect the normal operation of the
safety shutoff system. The terminus of the bleed
line shall be securely held in a fixed position
relative to the pilot. For nianufactured gas, the
need for a flame arrester in the bleed line piping
shall be determined. [NFPA 54: 9.1.20(4)]
508.24.5 Bleed lines from a diaphragm-type
valve and vent lines from a gas appliance
pressure regulator shall not be connected to a
common manifold terminating in a combustion
chamber. Bleed lines shall not terminate in
positive-pressure-type combustion chambers.
[NFPA 54: 9.1.20(5)]
508.25 Combination of Equipment. Any com-
bination of gas utilization equipment, attachments,
or devices used together in any manner shall comply
with the standards that apply to the individual
equipment. [NFPA 54: 9.1.21]
508.26 Installation Instructions. The installing
agency shall conform with the equipment
manufacturer's recommendations in completing an
installation. The installing agency shall leave the
manufacturer's installation, operating, and
maintenance instructions in a location on the
premises where they will be readily available for
reference and guidance for the Authority Having
Jurisdiction, service personnel, and the owner or
operator. [NFPA 54: 9.1.22]
508.27 Protection of Outdoor Equipment. Gas
utilization equipment not listed for outdoor
installation but installed outdoors shall be provided
with protection to the degree that the environment
requires. Equipment listed for outdoor installation
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA'
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA"
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
46
WATER HEATERS
508.27 - 509.4
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
shall be permitted to be installed without protection
in accordance with the provisions of its listing. (See
9.2.1.) [NFPA 54: 9.1.23]
(The following references were extracted from NFPA 54.)
9.2 Accessibility and Clearance.
9.2.1 Accessibility for Service. All gas utilization
equipment shall be located with respect to building
construction and other equipment so as to permit
access to the gas utilization equipment. Sufficient
clearance shall be maintained to permit clean-
ing of heating surfaces; the replacement of filters,
blowers, motors, burners, controls, and vent
connections; the lubrication of moving parts where
necessary; the adjustment and cleaning of burners
and pilots; and the proper functioning of explosion
vents, if provided. Tor attic installation, the passage-
way and servicing area adjacent to the equipment
shall be floored.
509.0 Equipment on Roofs.
509.1 General.
(1) Gas-utilization equipment on roofs shall be
designed or enclosed so as to withstand
climactic conditions in the area in which they
are installed. Where enclosures are provided,
each enclosure shall permit easy entry and
movement, shall be of reasonable height, and
shall have at least a 30-inches (760mm)
clearance between the entire service access
panel(s) of the equipment and the wall of
the enclosure. [NFPA 54: 9.4.1.1]
(2) Roofs on which equipment is to be installed
shall be capable of supporting the additional
load or shall be reinforced to support the
additional load. [NFPA 54: 9.4.1.2]
(3) All access locks, screws, and bolts shall be of
corrosion-resistant material. [NFPA 54: 9.4.1.3]
509.2 Installation of Equipment on Roofs.
(1) Gas utilization equipment shall be installed in
accordance with its listing and the
manufacturer's installation instructions.
[NFPA 54: 9.4.2.1]
(2) Equipment shall be installed on a well-
drained surface of the roof. At least 6 feet
(1.8m) of clearance shall be available
between any part of the equipment and the
edge of a roof or similar hazard, or rigidly
fixed rails, guards, parapets, or other
building structures at least 42 inches (1.1 m)
in height shall be provided on the exposed
side. [NFPA 54: 9.4.2.2]
(3) All equipment requiring an external source of
electrical power for its operation shall be
provided with (1) a readily accessible
electrical disconnecting means within sight
of the equipment that will completely
de-energize the equipment, and (2) a 120-V
ac grounding-type receptacle outlet on the
roof adjacent to the equipment. The
receptacle outlet shall be on tlie supply side
of the disconnect switch. [NFPA 54: 9.4.2.3]
(4) Where water stands on the roof at the
equipment or in the passageways to the
equipment, or where the roof is of a design
having a water seal, a suitable platform,
walkway, or both shall be provided above the
waterltne. Such platforms or walkways shall
be located adjacent to the equipment and
control panels so that the equipment can
be safely serviced where water stands on the
roof. [NFPA 54: 9.4.2.4]
509.3 Access to Equipment on Roofs.
509.3.1 Gas utilization equipment located on
roofs or other elevated locatior\s shall be accessible.
[NFPA 54: 9.4.3.1]
509.3.2 Buildings more than 15 feet (4.6 m) in
height shall have an inside means of access to the
roof, unless other means acceptable to the Authority
Having Jurisdiction are used. [NFPA 54: 9.4.3.2]
509.3.3 The inside means of access shall be a
permanent, or fold-away inside stairway or
ladder, terminating in an enclosure, scuttle, or
trap door. Such scuttles or trap doors shall be at
least 22 inches x 24 inches (560 mm x 610 mm) in
size, shall open easily and safely under all
conditions, especially snow; and shall be
constructed so as to permit access from the roof
side unless deliberately locked on the inside.
At least 6 feet (1.8 m) of clearance shaU be avail-
able between the access opening and the edge of
the roof or similar hazard, or rigidly fixed rails
or guards a minimum of 42 inches (1.1 m) in height
shall be provided on the exposed side. Where
parapets or other building structures are utilized in
lieu of guards or rails, they shall be a minimum
of 42 inches (1.1 m) in height. [NFPA 54: 9.4.3.3]
509.3.4 Permanent lighting shall be provided at
the roof access. The switch for such lighting
shall be located inside the building near the
access means leading to the roof. [NFPA 54: 9.4.3.4]
509.4 Appliances in Attics.
509.4.1 Attic Access. An attic in which an
appliance is installed shall be accessible through
an opening and passageway at least as large as
the largest component of the appliance, and not
less tiian 22 inches x 30 inches (560 mm x 760 mm).
[NFPA 54: 9.5.1]
509.4.2 Where the height of tlie passageway is
less than 6 feet (1.8 m), the distance from the
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
47
509.4-510.2
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
passageway access to the appliance shall not
exceed 20 feet (6.1 m) measured along the
centerline of the passageway. [NFPA 54: 9.5.1.1]
509.4.3 The passageway shall be unobstructed
and shall have solid flooring not less than 24
inches (610 mm) wide from the entrance opening
to the appliance. [NFPA 54: 9.5.1.2]
509.4.4 Work Platform. A level working
platform not less thair 30 inches (760 mm) by 30
inches (760 mm) shall be provided in front of the
service side of the appliance. [NFPA 54: 9.5.2]
509.4.5 Lighting and Convenience Outlet. A
permanent 120-volt receptacle outlet and a
lighting fixture shall be installed near the
appliance. The switch controlling the lighting
fixture shall be located at the entrance to the
passageway. [NFPA 54: 9.5.3]
510.0 Venting of Equipment.
510.1 General. This section recognizes that the
choice of venting materials and the methods of
installation of venting systems are dependent on the
operating characteristics of the gas utilization
equipment. The operating characteristics of vented
gas utilization equipment can be categorized with
respect to (1) positive or negative pressure within the
venting system, and (2) whether or not the
equipment generates flue or vent gases that can
condense in the venting system. See NFPA 54 Section
3.3 for the definition of these vented appliance
categories. [NFPA 54: 12.2]
510.2 Specification for Venting.
510.2.1 Connection to Venting Systems.
Except as permitted in Sections 510.2.2 through
510.2.6, all gas utilization equipment shall be
connected to venting systems. [NFPA 54: 12.3.1]
510.2.2 Equipment Not Required to Be
Vented. The following equipment shall not be
required to be vented [NFPA 54: 12.3.2]:
51 0.2.2.1 Listed Ranges. [NFPA 54: 12.3.2(1)]
510.2.2.2 Built-in Domestic Cooking Units
Listed and Marked for Optional Venting.
[NFPA 54: 12.3.2(2)]
510.2.2.3 Listed Hot Plates and Listed
Laundry Stoves. [NFPA 54: 12.3.2(3)]
510.2.2.4 Listed T)^e 1 clothes dryers shall
be exhausted to the outside air.
[NFPA 54: 12.3.2(4)]
510.2.2.5 A single listed booster-type
(automatic instantaneous) water heater,
when designed and used solely for the
sanitizing rinse requirements of a dish-
washing machine, provided that the equip-
ment is installed with the draft hood in place
and unaltered if a draft hood is required, in
a commercial kitchen having a mechanical
exhaust system; where installed in this
manner, the draft hood outlet shall not be
less than 36 inches (910 mm) vertically and 6
inches (150 man) horizontally from any surface
other than the equipment. [NFPA 54: 12.3.2(5)]
510.2.2.6 Listed Refrigerators.
[NFPA 54: 12.3.2(6)]
510.2.2.7 Counter Appliances.
[NFPA 54: 12.3.2(7)]
510.2.2.8 Direct Gas-Fired Makeup Air
Heaters. [NFPA 54: 12.3.2(9)]
510.2.2.9 Other Equipment Listed for
Unvented Use and Not Provided with Flue
Collars. [NFPA 54: 12.3.2(10)]
510.2.2.10 Specialized Equipment of Limited
Input such as Laboratory Burners or Gas
Lights. [NFPA 54:12.3.2(11)] Where any or all
of this equipment in Sections 510.2.2.1
through 510.2.2.10 is installed so the aggregate
input rating exceeds 20 Btu/h/ff (207 W/m^)
of room or space in which it is installed, one
or more shall be provided with venting
systems or other approved means for
removing the vent gases to the outside
atmosphere so the aggregate input rating of
the remaining unvented equipment does not
exceed 20 Btu/h/ft' (207 W/m^). Where the
calculationincludes the volume of an adjacent
room or space, the room or space in which the
equipment is installed shall be directly
connected to the adjacent rooni or space by a
doorway, archway, or other opening of
comparable size that cannot be closed.
510.2.3 Ventilating Hoods. Ventilating hoods
and exhaust systems shall be permitted to be
used to vent gas utilization equipnient installed in
commercial applications (see Section 510.3.5)
and to vent industrial equipment, particularly
where the process itself requires fume disposal.
[NFPA 54: 12.3.3]
510.2.4 Well-Ventilated Spaces. The operation of
industrial gas utilization equipment such that its
flue gases are discharged directly into a large and
well-ventilated space shall be permitted. [NFPA
54: 12.3.4]
510.2.5 Direct-Vent Equipment. Listed direct-
vent gas utilization equipment shall be
considered properly vented where installed in
accordance with the terms of its listing, the
manufacturer's instructions, and Section 510.8(3)
of this code. [NFPA 54: 12.3.5]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
48
WATER HEATERS
510.2-510.5
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
510.2.6 Equipment with Integral Vents. Gas
utilization equipment incorporating integral
venting means shall be considered properly
vented where installed in accordance with its
listing, the manufacturer's instructions, and
Sections 510.8.1 and 510.8.2 of this code. [NFPA
54: 12.3.6]
510.3 Design and Construction.
510.3.1 Minimum Safe Performance. A venting
system shall be designed and constructed so as to
develop a positive flow adequate to remove flue or
vent gases to the outside atmosphere.
510.3.2 Equipment Draft Requirements. A
venting system shall satisfy the draft require-
ments of the equipment in accordance with the
manufacturer's instructions. [NFPA 54: 12.4.1]
510.3.3 Design and Construction. Gas
utilization equipment required to be vented shall
be connected to a venting system designed and
installed in accordance with the provisions of
Sections 510.4 through 510.15 of this code.
[NFPA 54: 12.4.2]
510.3.4 Mechanical Draft Systems.
510.3.4.1 Mechanical draft systems shall be
listed and shall be installed in accordance
with the terms of their listing and both the
appliance and the mechanical draft system
manufacturers' instructions. [NFPA 54: 12.4.3.1]
510.3.4.2 Gas utilization equipment
requiring venting shall be permitted to be
vented by means of mechanical draft
systems of either forced or induced draft
design. [NFPA 54: 12.4.3.2]
Exception: Incinerators.
510.3.4.3 Forced draft systems and all
portions of induced draft systems under
positive pressure during operation shall be
designed and installed so as to prevent
leakage of flue or vent gases into a building.
[NFPA 54: 12.4.3.3]
51 0.3.4.4 Vent connectors serving equipment
vented by natural draft shall not be connected
into any portion of mechanical draft systems
operating under positive pressure.
[NFPA 54: 12.4.3.4]
51 0.3.4.5 Where a mechanical draft system
is employed, provision shall be made to
prevent the flow of gas to the main burners
when the draft system is not performing so as
to satisfy the operating requirements of the
equipment for safe performance.
[NFPA 54: 12.4.3.5]
510.3.4.6 The exit terminals of mechanical
draft systems shall be not less than 7 feet (2.1 m)
above grade where located adjacent to public
walkways and shall be located as specified in
Sections 510.8.1 and 510.8.2 of this code.
[NFPA 54: 12.4.3.6]
510.3.5 Ventilating Hoods and Exhaust
Systems.
510.3.5.1 Ventilating hoods and exhaust
systems shall be permitted to be used to vent
gas utilization equipment installed in
commercial applications. [NFPA 54: 12.4.4.1]
510.3.5.2 Where automaticciUy operated gas
utilization equipment is vented through a
ventilating hood or exhaust system equipped
with a damper or with a power means of
exhaust, provisions shall be made to allow
the flow of gas to the main burners only
when the damper is open to a position to
properly vent the equipment and when the
power means of exhaust is in operation.
[NFPA 54: 12.4.4.2]
510.3.6 Circulating Air Ducts and Furnace
Plenums. No portion of a venting system shall
extend into or pass through any circulating air
duct or furnace plenum. [NFPA 54: 12.4.5.1]
510.4 Type of Venting System to Be Used.
51 0.4.1 The type of venting system to be used shall
be in accordance with Table 5-2. [NFPA 54: 12.5.1]
510.4.2 Plastic Piping. Plastic piping used for
venting equipment listed for use with such
venting materials shall be approved. [NFPA54: 1252]
510.4.3 Special Gas Vent. Special gas vent shall
be listed and installed in accordance with the
terms of the special gas vent listing and the
manufacturer's instructions. [NFPA 54: 12.5.3]
510.5 Masonry, Metal, and Factory-Built
Chimneys.
510.5.1 Listing or Construction.
510.5.1.1 Factory-built chimneys shall be
installed in accordance with their listing and
the manufacturers' instructions. Factory-built
chimneys used to vent appliances that
operate at positive vent pressure shall be
listed for such application. [NFPA 54; 12.6.1.1]
510.5.1.2 Metal chimneys shall be built and
installed in accordance with NFPA 211,
Standard for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances. [NFPA 54: 12.6.1.2]
510.5.1.3 Masonry chimneys shall be built
and installed in accordance with NFPA 211,
Standard for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances, and lined with
approved clay flue lirung, a listed chimney
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
49
510.5
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
lining system, or other approved material'
that will resist corrosion, erosion, softening,
or cracking from vent gases at temperatures
up to 1800°F (982°C). [NFPA 54: 12.6.1.3]
Exception: Masonry chimney flues lined
with a chimney lining system specifically
listed for use with listed gas appliances
with draft hoods. Category I appliances,
and other gas appliances listed for use
with T)Ape B vente shall be permitted. The
liner shall be installed in accordance with the
liner manufacturer's instructions and the
terms of the listing. A permanent identifying
label shall be attached at the point where -
the connection is to be made to the Uner.
The label shall read: "This chimney Uner is
for appliances that bvim gas only. Do not
connect to solid-or liquid-fuel-buming
appliances or incinerators." [NFPA 54:
12.6.1.3]
510.5.2 Termination.
510.5.2.1 A chimney for residential-type or
low-heat gas utilization equipment shall
extend at least 3 feet (0.9 m) above the
highest point where it passes through a roof
of a building and at least 2 feet (0.6 m)
higher than any portion of a building within
a horizontal distance of 10 feet (3.0 m). [See
Figure 5-1.] [NFPA 54: 12.6.2.1]
510.5.2.2 A chimney for medium-heat
equipment shall extend at least 10 feet (3.0 m)
higher than any portion of any building
within 25 feet (7.6 m). [NFPA 54: 12.6.2.2]
510.5.2.3 A chimney shall extend at least 5 feet
(1.5 m) above the highest connected equip-
ment draft hood outlet or flue collar.
[NFPA 54: 12.6.2.3]
51 0.5.2.4 Decorative shrouds shall i>ot be
installed at the termination of factory-built
chimneys except where such shrouds are
listed and labeled for use with the specific
factory-built chimney system and are
installed in accordance with manufacturers'
installation instructions. [NFPA 54: 12.6.2.4]
510.5.3 Size of Chimneys. The effective area of
a chimney venting system serving listed gas
appliances with draft hoods. Category I
appliances, and other appliances listed for use
with Type B vents shall be in accordance with
one of the following methods [NFPA 54: 12.6.3.1]:
(1) This chapter and NFPA 54; Chapter 13.
[NFPA 54: 12.6.3.1(1)]
(2) For sizing an individual chimney venting
system for a single appliance with a draft
hood, the effective areas of the vent
cormector and chimney flue shall be not less
than the area of the appliance flue collar or
draft hood outlet or greater than seven times
the draft hood outlet area. [NFPA 54: 12.6.3.1(2)]
(3) For sizing a chimney venting system connected
to two appliances with draft hoods, the
effective area of the chimney flue shall be
not less than the area of the larger draft hood
outlet plus 50 percent of the area of the
smaller draft hood outlet, or greater than
seven times the smallest drcift hood outlet area.
[NFPA 54: 12.6.3.1(3)]
(4) Other approved engineering methods.
[NFPA 54: 12.6.3.1(5)]
(5) Chimney venting systems using mechanical
draft shall be sized in accordance with approved
engineering methods. [NFPA 54: 12.6.3.1(4)]
Where an incinerator is vented by a chimney
serving other gas utilization equipment, the
gas input to the incinerator shall not be
included in calculating chimney size, provided
the chimney flue diameter is not less than 1
inch (25 mm) larger in equivalent diameter
than the diameter of the incinerator flue outlet.
[NFPA 54: 12.6.3.2]
510.5.4 Inspection of CSiimneys.
(A) Before replacing an existing appliance or
connecting a vent connector to a chimney,
the chimney passageway shall be examined
to ascertain that it is clear and free of
obstructions and shall be cleaned if
previously used for venting solid- or liquid-
fuel-burntng appliances or fireplaces.
[NFPA 54: 12.6.4.1]
(B) Chimneys shall be lined in accordance with
NFPA 211, Standard for Chimneys, Fireplaces,
Vents, and Solid-Fuel Burning Appliances.
[NFPA 54: 12.6.4.2]
(C) Cleanouts shall be examined to determine
that they will remain tightly closed when
not in use. [NFPA 54: 12.6.4.3]
(D) When inspection reveals that an existing
chimney is not safe for the intended
application, it shall be repaired, rebuilt,
lined, relined, or replaced with a vent or
chimney to conform to NFPA 211, Standard
for Chimneys, Fireplaces, Vents, and Solid-
Fuel-Burning Appliances, and shall be
suitable for the equipment to be attached.
[NFPA 54: 12.6.4.4]
510.5.5 Chimney Serving Equipment Burning
Other Fuels.
510.5.5.1 Gas utilization equipment shall
not be comiected to a chimney flue serving a
separate appliance designed to bum solid fuel.
[NFPA 54: 12.6.5.1]
510.5.5.2 Where one chimney serves gas
utilization equipment and equipment
burning liquid fuel, the equipment shall be
connected through separate openings or
shall be connected through a single opening
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
50
WATER HEATERS
Figure 5-1 - Table 5-2
NFPA
NFPA
NFRA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
2 ft (0.6 m)
minimum -
r-10ft(3.0m)--^
/ or less \
3 ft (0.9 m)
minimum
Chimney J^
Chimney
10 ft (3.0 m)
or less
3 ft (0.9 m)
minimum
Chimney
(a) Temiination 10 ft (3.0 m) or Less from Ridge, Wall, or Parapet
More than
• 10 ft (3.0 m)-
Wall or
parapet
~-*fl.
'^^/M<-^.
Note: No height
above parapet
required when
distance from wails
or parapet is more
th^ 10 ft (3.0 m).
3 ft (0.9 m)
minimum
Chimney
Height above any
roofsurface wiflirn
10 ft (3.0 m) horizontally
Ridge
Chimney
(b) Temiination J^ore Than 10 ft (3,0 m) from Ridge, Wail, or Parapet
FIGURE 5-1 Typical Termination Locations for
Chimneys and Single-Wall Metal Pipes Serving
Residential-Type and Low-Heat Equipment
[NFPA 54: Figure 12.6.2.1]
where joined by a suitable fitting located as
close as practical to the chimney. Where two
or more openings are provided into one
chimney flue, they shall be at different
levels. Where the gas utilization equipment
is automatically controlled, it shall be
equipped with a safety shutoff device.
[NFPA 54: 12.6.5.2]
TABLE 5-2
Type of Venting System to Be Used
Gas Utilization Equipment
Type of Venting System
Listed Category I equipment
Listed equipment equipped
with draft hood
Equipment listed for use with
Type B gas vent
system for gas venting
Type B gas vent (510.6)
Chimney (510.5)
Single-wall metal pipe
(510.7)
Listed chimney lining
(510.5.1.3)
Special gas vent listed
for this equipment
(510.4.3)
Listed vented wall furnaces
Type B-W gas vent
(510.6, 510.6.2.2)
Category II equipment
Category III equipment
Category IV equipment
As specified or
furnished
By manufacturers of
listed
equipment (510.4.2,
510.4.3)
Incinerators, outdoors
Single-wall metal pipe
(510.7, 510.7.3)
Incinerators, indoors
Equipment that can be converted
to use of solid fuel
Unlisted combination gas- and
oil-burning equipment
Combination gas- and solid-fuel-
burning equipment
Equipment listed for use with
chimneys only
Unlisted equipment
Chimney (510.5)
Listed combination gas- and
oil-burning equipment
Type L vent (510.6) or
chimney (510.5)
Decorative appliance in
fireplace
vented
Chimney [UMC 907.2(3)]
Gas-fired toilets
Single-wall metal pipe
(510.7, NFPA 54: 9.25.3)
Direct-vent equipment
See 510.2.5
Equipment with Integra
vent
See 510.2.6
[NFPA 54: Table 12.5.1]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
51
Figure 5-2 -510.6
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Listed
cap
Lowe st discharge opening
Listed gas
vent
Root pitch is )^^2
H (minimum) -
Minimum height from roof
to lowest discharge opening
Roof pitch heights
Roof pitch H(minimum) ft.
m
Flat to 6/12
1.0
0.30
Over 6/12 to 7/12
1.25
0.38
Over 7/12 to 8/12
1.5
0.46
Over 8/12 to 9/12
2.0
0.61
Over 9/12 to 10/12
2.5
0.76
Over 10/12 to 11/12
3.25
0.99
Over 11/12 to 12/12
4.0
1.22
Over 12/12 to 14/12
5.0
1.52
Over 14/12 to 16/12
6.0
1.83
Over 16/12 to 18/12
7.0
2.13
Over 18/12 to 20/12
7.5
2.27
Over 20/12 to 21/12
8.0
2.44
FIGURE 5-2 Gas Vent Termination Locations for
Listed Caps 12 in. (300 mm) or Less in Size at
Least 8 ft. (2.4 m) from a Vertical Wall [NFPA 54:
Figure 12.7.2 and Table 12.7.2]
Vr-
Gas furnace
Type B gas vents
Air grilles in
outside walls
Louvered door could
be used in lieu of
outside wall grilles
FIGURE 5-3 Plan View of Practical Separation
Method for Multistory Gas Venting. [NFPA 54:
Figure 12.7.4.2]
510.5.5.3 A listed combination gas- and
solid-fuel-burning appliance connected to a
single chimney flue shall be equipped w^ith a
manual reset device to shut off gas to the
main burner in the event of sustained
backdraft or flue gas spillage. The chirrmey
flue shall be sized to properly vent the
appliance. [NFPA 54: 12.6.5.3]
510.5.5.4 A single chimney flue serving a
listed combination gas- and oil-burning
appliance shall be sized to properly vent the
appliance. [NFPA 54: 12.6.5.4]
510.5.6 Support of Chimneys. All portions of
chimneys shall be supported for the design and
weight of the materials employed. Listed
factory-built chimneys shall be supported and
spaced in accordance with their listings and the
manufacturers' instructions. [NFPA 54: 12.6.6]
510.5.7 Cleanouts. Where a chimney that
formerly carried flue products from liquid- or
solid-fuel-burning appliances is used with an
appliance using fuel gas, an accessible cleanout
shall be provided. The cleanout shall have a
tight-fitting cover and be installed so its upper
edge is at least 6 inches (150 mm) below the
lower edge of the lowest chimney inlet opening.
[NFPA 54: 12.6.7]
510.5.8 Space Surrounding Lining or Vent
510.5.8.1 The remaining space surrounding a
chimney liner, gas vent, special gas vent, or
plastic piping installed within a masonry
chimney flue shaU not be used to vent another
appHance. [NFPA 54: 12.6.8.1]
Exception: The insertion of anotlier liner
or vent within the chimney as provided
in this code and the liner or vent
manufacturer's instructions.
510.5.8.2 The remaining space surrounding
a chimney liner, gas vent, special gas vent,
or plastic piping installed within a masonry
chimney flue shall not be used to supply
combustion air. [NFPA 54: 12.6.8.2]
Exception: Direct-vent gas-fired
appliances designed for installation in a
solid-fuel-burning fireplace where
installed in accordance with the listing
and the manufacturer's instruction.
510.6 Gas Vents.
510.6.1 A gas vent passing through a roof shall
extend through the entire roof flashing, roof jack,
or roof thimble and be terminated with a listed
termination cap. [NFPA 54: 10.6.1(3)]
510.6.1.1 Type B or Type L vents shall
extend in a generally vertical direction with
offsets not exceeding 45 degrees, except that
a vent system having not more than one
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
52
WATER HEATERS
510.6
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
"NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
60-degree offset shall be permitted. Any
angle greater than 45 degrees from the
vertical is considered horizontal. The total
horizontal distance of a vent plus the
horizontal vent connector serving draft-
hood-equipped appliances shall not be
greater than 75 percent of the vertical height
of the vent. [NFPA 54: 10.6.1(4)]
Exception; Systems designed and sized
as provided in this chapter or in accor-
dance with other approved engineering
methods.
510.6.1.2 Vents serving Category I fan-
assisted appliances shall be installed in
accordance with the appliance manufacturer's
instructions and NFPA 54, Chapter 10 or
other approved engineering methods.
[NFPA 54: 12.7.1(3)]
51 0.6.2 A gas vent shall terminate in accordance
with one of the following [NFPA 54: 12.7.2(1)]:
(1) Above the roof surface with a listed cap
or listed roof assembly. Gas vents. 12 inches
(300 mm) in size or smaller with listed
caps shall be permitted to be terminated in
accordance with Figure 5-2, provided they
are at least 8 feet (2.4 m) from a vertical wall
or similar obstruction. All other gas vents
shall terminate not less than 2 feet (0.6 m)
above the highest point where they pass
through the roof and at least 2 feet (0.6 m)
higher than any portion of a building within
10 feet (3.1 m). [NFPA 54: 12.7.2(l)(a)]
(2) Industrial gas utilization equipment as
provided in Section 510.2.4. [NFPA 54: 12.72(l)(c)]
(3) Direct-vent systems as provided in Section
510.2.5. [NFPA 54: 12.7.2(l)(d)]
(4) Equipment with integral vents as provided
in Section 510.2.6. [NFPA 54: 12.7.2(l)(e)]
(5) Mechanical draft systems as provided in
Section 510.3.4. [NFPA 54: 12.7.2(l)(f)]
(6) Ventilating hoods and exhaust systems
as provided in Section 510.3.5. [NFPA 54:
12.7.2(l)(g)]
510.6.2.1 A Type B or a Type L gas vent
shall terminate at least 5 feet (1.5 m) in
vertical height above the highest connected
equipment draft hood or flue collar. [NFPA
54: 12.7.2(2)]
51 0.6.2.2 A Type B-W gas vent shall terminate
at least 12 feet (3.7 m) in vertical height
above the bottom of the wall furnace. [NFPA
54: 12.7.2(3)]
51 0.6.2.3 A gas vent extending through an
exterior wall shall not terminate adjacent to
the wall or below eaves or parapets, except
as provided in Sections 510.2.5 and 510.3.4.
[NFPA 54: 12.7.2(4)]
510.6.2.4 Decorative shrouds shall not be
installed at the termination of gas vents
except where such shrouds are listed for use
with the spiecific gas venting system and are
installed in accordance with manufacturers'
installation instructions. [NFPA 54: 12.7.2(5)]
51 0.6.2.5 All gas vents shall extend through
the roof flashing, roof jack, or roof thimble
and terminate with a listed cap or listed roof
assembly. [NFPA 54: 12.7.2(6)]
51 0.6.2.6 A gas vent shall terminate at least
3 feet (0.9m) above a forced air inlet located
within 10 feet (3.0m). [NFPA 54: 12.7.2(7)]
510.6.3 Size of Gas Vents. Venting systems
shall be sized and constructed in accordance
with NFPA 54, Chapter 13 or other approved
engineering methods and the gas vent and gas
equipment manufacturers' instructions. [NFPA
54: 12.7.3]
510.6.3.1 Category I Appliances. The
sizing of natural draft venting systems
serving one or more listed appliances
equipped with a draft hood or appliances
listed for use with Type B gas vent, installed
in a single story of a building, shall be in
accordance with one of the following
methods. [NFPA 54: 12.7.3.1]
(1) The provisions of this chapter. [NFPA
54: 12.7.3.1(1)]
(2) Vents serving fan-assisted combustion
system appliances, or combinations of
fan-assisted combustion systems and
draft hood-equipped appliances, shall
be sized in accordance with this chapter
or other approved engineering methods.
[NFPA 54: 12.7.3.1(2)]
(3) For sizing an individual gas vent for a
single, draft-hood-equipped appliance,
the effective area of the vent connector
and the gas vent shall be not less than
the area of the appliance draft hood
outlet or greater than seven times the
draft hood outiet area. [NFPA 54: 12.7.3.1(3)]
(4) For sizing a gas vent cormected to two
appliances with draft hoods, the effective
area of the vent shall be not less than the
area of the larger draft hood outlet plus
50 percent of the area of the smaller draft
hood outlet or greater than seven times
the smaller draft hood outlet area.
[NFPA 54: 12.7.3.1(4)]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
53
510.6 -Table 5-3
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(5) Approved engineering practices. [NFPA
54: 12.7.3.1(5)]
510.6.3.2 Category 11, Category III, and
Category IV Appliances. The sizing of gas
vents for Category II, Category III, and
Category IV gas utilization equipment shall
be in accordance w^ith the equipment
manufacturers' instructions. [NFPA 54:
12.7.3.3]
510.6.3.3 Sizing. Chinmey venting systems
using mechanical draft shall be sized in
accordance with approved engineering
methods. [NFPA 54: 12.7.3.4]
510.6.4 Gas Vents Serving Equipment on
More Than One Floor.
510.6.4.1 A common gas vent shall be
permitted in multistory installations to vent
Category I gas utilization equipment located
on more than one floor level, provided the
venting system is designed and installed in
accordance with approved engineering
methods.
For the purpose of this section, crawl spaces,
basements, and attics shall be considered as
floor levels. [NFPA 54: 12.7.4.1]
510.6.4.2 All gas utilization equipment
connected to the common vent shall be
located in rooms separated from a habitable
space. Each of these rooms shall have
provisions for an adequate supply of
combustion, ventilation, and dilution air
that is not supplied from a habitable space.
(See Figure 5-3.) [NFPA 54: 12.7.4.2]
The size of the connectors and
comm^on segments of multistory venting
systems for gas utilization equipment listed
for use with Type B double-wall gas vent
shall be in accordance with Table 5-14,
provided [NFPA 54: 12.7.4.3]:
(1) The available total height (H) for each
segment of a multistory venting system is
the vertical distance between the level of
the highest draft hood outlet or flue collar
on that floor and the centerline of the next
highest interconnection tee. (See Figure
G.l(K).) [NFPA 54: 12.7.4.3(1)]
TABLE 5-3
Clearance for Connectors [NFPA 54: Table 12.8.4.4]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Minimum Distance from Combustible Material
Eq ui pment
Listed Type B
Gas Vent Material
Listed Type L
Vent Material
Single-Wall
M etal Pipe
Factory-Built
Chimney Sections
Listed equipment with
draft hoods and equip-
ment listed for use with
Type B gas vents
As listed
As listed
6 in.
As listed
Residential boilers and
furnaces with listed gas
conversion burner and
with draft hood
6 in.
6 in.
9 in.
As listed
Residential appliances
listed for use with Type L
vents
Not permitted
As listed
9 in.
As listed
Residential incinerators
Not permitted
9 in.
18 in.
As listed
Listed gas-fired toilets
Not permitted
As listed
As listed
As listed
Unlisted residential
appliances with draft
hood
Not permittted
6 in.
9 in.
As listed
Residential and low-heat
equipment other than
those above
Not permitted
9 in.
18 in.
As listed
Medium-heat equipment
Not permitted
Not permitted
36 in.
As listed
For SI units, 1 in.= 25.4 mm.
Note: These clearances shall apply unless the listing of an appliance or connector specifies clearances, in which case the listed clearances
shall apply.
54
WATER HEATERS
510.6-510.7
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(2) The size of the connector for a segment is
determined from its gas utilization equipment
heat input and available connector rise, and
shall not be smaller than the draft hood outlet
or flue collar size. [NFPA 54: 12.7.4.3(2)]
(3) The size of the common vertical vent
segment, and of the interconnection tee at
the base of that segment, shall be based on
the total gas utilization equipment heat
input entering that segment and its available
total height. [NFPA 54: 12.7.4.3(3)]
510.6.5 Support of Gas Vents. Gas vents shall
be supported and spaced in accordance with
their listings and the manufacturers' instructions.
[NFPA 54: 12.7.5]
510.6.6 Marking. In those localities where solid
and liquid fuels are used extensively, gas vents
shall be permanently identified by a label
attached to the wall or ceiling at a point where
the vent connector enters the gas vent. The label
shall read: "This gas vent is for appliances that
bum gas. Do not connect to solid- or liquid-fuel-
burning appliances or incinerators." The
Authority Having Jurisdiction shall determine
whether its area constitutes such a locality.
[NFPA 54: 12.7.6]
510.7 Single-Wall Metal Pipe.
510.7.1 Construction. Single-wall metal pipe
shall be constructed of galvanized sheet steel not
less than 0.0304 inch (0.7 mm) thick or of other
approved, noncombustible, corrosion-resistant
material. [NFPA 54: 12.8.1]
510.7.2 Cold Climate. Uninsulated single-wall
metal pipe shall not be used outdoors in cold
climates for venting gas utilization equipment
in regions where the 99 percent winter design
temperature is below 32° Fahrenheit.
[NFPA 54: 12.8.2]
510.7.3 Termination. The termination of single-
wall metal pipe shall comply with the following
requirements [NFPA 54: 12.8.3]:
510.7.3.1 Single-wall metal pipe shall
terminate at least 5 feet (1.5 m) in vertical
height above the highest connected equip-
ment draft hood outlet or flue collar.
[NFPA 54: 12.8.3(1)]
510.7.3.2 Single-wall metal pipe shall
extend at least 2 feet (0.6 m) above the highest
point where it passes through the roof of a
building and at least 2 feet (0.6 m) higher than
any portion of a building within a horizontal
distance of 10 feet (3.1 m). [See Figure 5-1.]
[NFPA 54: 12.8.3(2)]
51 0.7.3.3 An approved cap or roof assembly
shall be attached to the terminus of a single-
wall metal pipe. [Also see Section 510.7.4.2.]
[NFPA 54: 12.8.3(3)]
510.7.4 Installation with Equipment Permitted
by 510.4.1.
510.7.4.1 Single-wall metal pipe shall be
used only for runs directly from the space
in which the gas utilization equipment is
located through the roof or exterior wall to
the outer air. A pipe passing through a
roof shall extend without interruption
through the roof flashing, roof jacket, or
roof thimble. [NFPA 54: 12.8.4.1]
510.7.4.2 Single-wall metal pipe shall not
originate in any unoccupied attic or
concealed space and shall not pass through
any attic, inside wall, concealed space, or
floor. For the installation of a single-wall
metal pipe through an exterior combustible
wall, see Section 510.10.14.2. [NFPA 54: 12.8.4.2]
510.7.4.3 Single-wall metal pipe used for
venting an incinerator shall be exposed and
readily examinable for its full length and
shall have suitable clearances maintained.
[NFPA 54: 12.8.4.3]
510.7.4.4 Minimum clearances from single-
wall metal pipe to combustible material shall
be in accordance with Table 5-3. Reduced
clearances from single-wall metal pipe to
combustible material shall be as specified for
vent connector in Table 5-4. [NFPA 54: 12.8.4.4]
510.7.4.5 Where a single-wall metal pipe
passes through a roof constructed of
combustible material, a noncombustible,
nonventilating thimble shall be used at the
point of passage. The thimble shall extend at
least 18 inches (460 mm) above and 6 inches
(150 mm) below the roof with the annular
space open at the bottom and closed only at
the top. The thimble shall be sized in
accordance with Section 510.10.14.2. [NFPA
54: 12.8.4.5]
510.7.5 Size of Single-Wall Metal Pipe. Single-
wall metal piping shall comply with the
following requirements [NFPA 54: 12.8.5]:
510.7.5.1 A venting system of a single-wall
metal pipe shall be sized in accordance with
one of the following methods and the gas
equipment manufacturer's instructions
[NFPA 54: 12.8.5(1)]:
(1) For a draft-hood-equipped appliance, in
accordance with this chapter.
[NFPA 54: 12.8.5(l,a)]
(2) For a venting system for a single
appliance with a draft hood, the areas of
the connector and the pipe each shall
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
55
Table 5-4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-4
Reduction of Clearances with Specified Foirms of Protection [NFPA 54: Table 10.2.3(b)]
Where the required clearance with no protection from appliance, vent connector, or
single-wall metal pipe is:
36 in.
18 in.
12 in.
9 in.
6 in.
Allowable Clearances with Specified Protection (in.)
Type of protection applied
to and covering all surfaces
of combustible material
Use Col. 1 for clearances above appliance or horizontal connector. Use Col. 2 for
clearances from appliances, vertical connector, and single-wall metal pipe.
as the required clearance
Sides
Sides
Sides
Sides
Sides
with no protection [See
and
and
and
and
and
Figures 5-4
Above
Rear
Above Rear
Above
Rear
Above Rear
Above
Rear
through 5-6.]
Col.1
Col. 2
Col. 1 Col. 2
Col.1
Col. 2
Col. 1 Col. 2
Col.1
Col. 2
(1)3-1/2 in. thick masonry - 24 ~ 12
wall without ventilated air
space
(2) 1/2 in. insulation board 24 18 12 9
over 1 in. glass fiber or
mineral wool batts
(3) 0.024 sheet metal over 18 12 9 6
1 in. glass fiber or mineral
wool batts reinforced with
wire on rear face with
ventilated air space
(4) 3-1/2 in. thick masonry - 12 ~ 6
wall with ventilated air
space
(5) 0.024 sheet metal with 18 12 9 6
ventilated air space
(6) 1/2 in. thick insulation 18 12 9 6
board with ventilated air
space
(7) 0.024 sheet metal with 18 12 9 6
ventilated air space over
0.024 sheet metal with
ventilated air space
(8) 1 in. glass fiber or 18 12 9 6
mineral wool batts
sandwiched between two
sheets 0.024 sheet metal
with ventilated ak space
6 4
6 4
6 4
6 4
5 3
5 3
5 3
5 3
3 2
3 3
3 3
3 3
For SI tmits, 1 in. = 25.4 mm.
Notes:
1. Reduction of clearances from com.bustible materials shall not interfere with combustion air^ draft hood clearance and relief, and
accessibility of servicing.
2. All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appUance,
disregarding any intervening protection applied to the combustible material.
3. Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or cormector.
4. Where all clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described.
[See Figure 5-5 and Figure 5-6.]
5. There shall be at least 1 in. (25 mm) between clearance reduction systems and combustible walls and ceilings for reduction systems using
a ventilated air space.
6. Where a wall protector is mounted on a single flat wall away from corners, it shall have a minimum 1 inch (25 mm) air gap. To provide
adequate air circulation, the bottom and top edges, or only the side and top edges, or all edges shall be left open.
7. Mineral wool batts (blanket or board) shall have a minimum density of 8 Ib/ff (128 kg/m^) and a minimum melting point of 1,500°F (816°C).
8. Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu in./ft^ /h-°F (0.144 W/m-K)
or less.
9. There shall be at least 1 inch (25 mm) between the appliance and the protector. In no case shall the clearance between the appliance and
the combustible surface be reduced below that allowed in this table.
10. All clearances and thicknesses are minimimi; larger clearances and thicknesses are acceptable.
11. Listed single- wall connectors shall be installed in accordance with the terms of their listing and the manufacturers' instructions.
56
WATER HEATERS
Figure 5-4 -51 0.7
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Construction using combustible — <
material, plastered or unplastered
2
M
M M
M
Combustible wall
^^^^
Sheet metal or
other protection
•* — Gas equipment
or vent connector
Notes:
A - Equals the clearance with no protection specified in
Tables 5-3 and 5-4 and in the sections applying to
various types of equipment.
B - Equals the reduced clearance permitted in
accordance with Table 5-3. The protection applied to the
construction using combustible material shall extend far
enough in each direction to make C equal to A.
FIGURE 5-4 Extent of Protection Necessary to
Reduce Clearances from Gas Equipment or Vent
Connectors. [NFPA 54: Figure 10.3.2.2(1)]
Mounted with side
and top edges open
Mounted with top
and bottom edges
open
Wall protector mounted
on single flat wall
Must be mounted with top
and bottom edges open
Wall protector installed in comer
/ y» Nail or screw anchor
( — Clearance
reduction system
1 in. (25 mm) nonpombustible
spacer such as stacked washers,
small-diameter pipe, tubing, or
eteclrical conduit.
Masonry walls can be attached to combustible walls
using wall ties. Spacers should not be used directly
behind appliance or connector.
FIGURE 5-5 Wall Protection Reduction System.
[NFPA 54: Figure 1 0.3.2.2(2)]
1 in. (25 mm) ^^'
minimum air space
between masonry
and combustible wall
4 in. (100 mm)
nominal brick wa!
Bottom and top course
of bricks staggered for
ventilation
Corrugated
metal wall
ties
A strip of heavy-gauge stee
used for added support
Note: Do not place masonry wall ties directly
behind appliance or connector.
Masonry wall tie
FIGURE 5-6 Masonry Clearance Reduction System.
[NFPA 54: Figure 10.3.2.2(3)]
Minimum Thickness for Galvanized Steel Vent
Connector for Low-Heat Appliances
[NFPA 54: Table 12.11.2.5]
Diameter of
Connector (In.)
Minimum Thickness
(in.)*
Less than 6
6 to less than 10
10 to 12 inclusive
14 to 16 inclusive
Over 16
0.019
0.023
0.029
0.034
0.056
* For SI units, 1 in. = 25.4 mm; 1 in.' = 645 nriml
not be less than the area of the
appliance flue collar or draft hood
outlet, whichever is smaller. The vent
area shall not be greater than seven
times the draft hood outlet area.
[NFPA 54: 12.8.5(l,b)]
(3) Other approved engineering methods.
[NFPA 54: 12.8.5(l,c)]
51 0.7.5.2 Where a single-wall metal pipe is
used and has a shape other than round, it
shall have an equivalent effective area equal
to the effective area of the round pipe for
which it is substituted, and the minimum
internal dimension of the pipe shall be 2
inches (50 mm). [NFPA 54: 12.8.5(2)]
510.7.5.3 The vent cap or a roof assembly
shall have a venting capacity not less than
that of the pipe to which it is attached.
[NFPA 54: 12.8.5(3)]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
57
510.7-510.10
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
. NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
510.7.6 Support of Single-Wall Metal Pipe.
All portions of single-wall metal pipe shall be
supported for the design and weight of the
material employed. [NFPA 54: 12.8.6]
510.7.7 Marking. Single-wall metal pipe shall
comply with the marking provisions of Section
510.6.6. [NFPA 54: 12.8.7]
510.8 Through-the-Wall Vent Termination. (See
Figure 5-12.)
51 0.8.1 A mechanical draft venting system shall
terminate at least 3 feet (0.9 m) above any forced
air inlet located within 10 feet (3.1 m). [NFPA 54:
12.9.1]
Exception No. 1: This provision shall not
apply to the combustion air intake of a
direct-vent appliance.
Exception No. 2: This provision shall not
apply to the separation of the integral
outdoor air inlet and flue gas discharge of
listed outdoor appliances.
510.8.2 A mechanical draft venting system of
other than direct-vent type shall terminate at
least 4 feet (1.2 m) below, 4 feet (1.2 m) horizon-
tally from, or 1 foot (300 mm) above any door,
operable window, or gravity air inlet into any
building. The bottom of the vent terminal shall
be located at least 12 inches (300 mm) above grade.
[NFPA 54: 12.9.2]
510.8.3 The vent terminal of a direct-vent
appliance with an input of 10,000 Btu/h (3 kW)
or less shall be located at least 6 inches (150 mm)
from any air opening into a building, and such
an appliance with an input over 10,000 Btu/h (3
kW) but not over 50,000 Btu/h (14.7 kW) shall be
installed with a 9-inch (230 mm) vent termination
clearance, and an appliance with an input over
50,000 Btu/h (14.7 kW) shall have at least a 12 inch
(300-mm) vent termination clearance. The bottom
of the vent terminal and the air intake shall be
located at least 12 inches (300 mm) above grade.
[NFPA 54: 12.9.3]
510.8.4 Through-the-wall vents for Category II
and Category IV appliances and noncategorized
condensing appliances shall not terminate over
public walkways or over an area where conden-
sate or vapor could create a nuisance or hazard or
could be detrimental to the operation of regu-lators,
relief valves, or other equipment. Where local
experience indicates that condensate is a problem
with Category I and Category III appU-ances, this
provision shaU also apply. [NFPA 54: 12.9.4]
510.9 Condensation Drain.
510.9.1 Provision shall be made to collect and
dispose of condensate from venting systems
serving Category II and Category IV gas
utilization equipment and noncategorized
condensing appliances in accordance with
Section 510.8.4. [NFPA 54: 12.10.1]
510.9.2 Where local experience indicates that
condensation is a problem, provision shall be
made to drain off and dispose of condensate
from venting systems serving Category I and
Category III gas utilization equipment in
accordance with 510.8.4. [NFPA 54: 10.9.2]
510.10 Vent Connectors for Category I Gas
Utilization Equipment.
510.10.1 Where Required. A vent cormector
shall be used to connect gas utilization
equipment to a gas vent, chimney, or single-
wall metal pipe, except where the gas vent,
chimney, or single-wall metal pipe is directly
connected to the equipment. [NFPA 54: 12.11.1]
510.10.2 Materials.
51 0.1 0.2.1 A vent connector shall be made of
noncombustible, corrosion resis-tant material
capable of withstanding the vent gas temper-
ature produced by the gas utilization equip-
ment and of sufficient thickness to withstand
physical damage. [NFPA 54: 12.11.2.1]
510.10.2.2 Where the vent cormector used
for gas utilization equipment having a draft
hood or a Category I appliance is located in
or passes through an unconditioned area,
that portion of the vent connector shall be
Usted Type B, Type L, or listed vent material
having equivalent insulation qualities.
[NFPA 54: 12.11.2.2]
Exception: Single-wall metal pipe
located within the exterior walls of the
building and located in areas having a
local 99 percent winter design temperature
of 5°F or higher.
510.10.2.3 Where the vent connector used
for gas utilization equipment having a draft
hood or a Category I appliance is located in
or passes through attics and crawl spaces,
that portion of the vent connector shall be
listed Type B, Type L, or listed vent material
having equivalent insulation qualities.
[NFPA 54: 12.11.2.3]
510.10.2.4 Vent connectors for residential-
type appliances shall comply with the
following: [NFPA 54: 12.11.2.4]
(1) Vent Connectors Not Installed in Attics,
Crawl Spaces, or Other Unconditioned
Areas. Vent connectors for listed gas
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
58
WATER HEATERS
510.10
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA I
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
appliances having draft hoods and for
appliances having draft hoods and
equipped with listed conversion burners
that are not installed in attics, crawl spaces,
or other unconditioned areas shall be one of
the following:
(a) Type B or Type L vent material.
(b) Galvanized sheet steel not less than
0.018-inches (0.46 mm) thick.
(c) Aluminum (1100 or 3003 alloy or
equivalent) sheet not less than 0.027-
inches (0.69 mm) thick.
(d) Stainless steel sheet not less than 0.012-
inches (0.31 mm) thick.
(e) Smooth interior wall metal pipe having
resistance to heat and corrosion equal to
or greater than that of b, c, or d above.
(f) A listed vent connector.
(2) Vent connectors shall not be covered
with insulation.
Exception; Listed insulated vent
connectors shall be installed according to
the terms of their listing.
510.10.2.5 A vent connector for non-
residential low-heat equipment shall be a
factory-built chimney section or steel pipe
having resistance to heat and corrosion
equivalent to that for the appropriate
galvanized pipe as specified in Table 5-5.
Factory-built chimney sections shall be
joined together in accordance with the
chimney manufacturer's instructions.
[NFPA 54: 12.11.2.5]
510.10.2.6 Vent connectors for medium-
heat equipment and commercial and
industrial incinerators shall be constructed
of factory-built, medium-heat chimney
sections or steel of a thickness not less than
that specified in Table 5-6 and shall comply
with the following: [NFPA 54: 12.11.2.6]
(1) A steel vent connector for equipment
with a vent gas temperature in excess of
1,000°F (538°C) measured at the entrance to
the connector shall be lined with medium-
duty fire brick (ASTM C 64, Specification for
Refractories for Incinerators and Boilers,
Type F) or the equivalent.
(2) The lining shall be at least 2-1/2 inches
(64 mm) thick for a vent connector having a
diameter or greatest cross-sectional dimension
of 18 inches (460 mm) or less.
(3) The lining shall be at least 4-1/2 inches
(110 mm) thick laid on the 4-1/2 inch (110-
mm) bed for a vent connector having a
diameter or greatest cross-sectional
dimension greater than 18 inches (460 mm).
(4) Factory-built chimney sections, if
employed, shall be joined together in
accordance with the chimney manufacturer's
instructions.
TABLE 5-6
Minimum Thickness for Steei Vent Connectors
for Medium-Heat Equipment and Commercial and
Industrial Incinerators
[NFPA 54: Table 12.11.2,6]
Vent Connector Size
Minimum
Diameter (in.)
Area (in.^)
Thickness (in.)
Up to 14
Up to 154
0.053
Over 14 to 16
154 to 201
0.067
Over 16 to 18
201 to 254
0.093
Over 18
Larger than 254 0.123
For SI units, 1 in. = 25.4 mm; 1 in." - 645 mm-.
510.10.3 Size of Vent Connector.
510.10.3.1 A vent connector for gas
utilization equipment with a single draft
hood or for a Category I fan-assisted
combustion system appliance shall be sized
and installed in accordance with this chapter
or other approved engineering methods.
[NFPA 54: 12.11.3.1]
510.10.3.2 For a single appliance having
more than one draft hood outlet or flue
collar, the manifold shall be constructed
according to the instructions of the appliance
manufacturer. Where there are no instruc-
tions, the manifold shall be designed and
constructed in accordance with approved
engineering practices. As an alternate
method, the effective area of the manifold
shall equal the combined area of the flue collars
or draft hood outlets, and the vent connectors
shall have a minimum 1-foot (0.3 m) rise.
[NFPA 54: 12.11.3.2]
510.10.3.3 Where two or more gas appliances
are connected to a common vent or chimney,
each vent connector shall be sized in accord-
ance with this chapter or other approved
engineering methods. [NFPA 54: 12.11.3.3]
As an alternative method applicable only
when all of the appliances are draft-hood-
equipped, each vent connector shall have an
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
59
510.10
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
effective area not less than the area of the
draft hood outlet of the appliance to which it is
connected. [NFPA 54: 12.11.3.4]
510.10.3.4 Where two or more gas appliances
are vented through a common vent connector
or vent manifold,- the common vent connec-
tor or vent manifold shall be located at the
highest level consistent with available head-
room and clearance to combustible material
and shall be sized in accordance with this
chapter or other approved engineering
methods. [NFPA 54: 12.11.3.5]
As an alternate method applicable only
where there are two draft-hood-equipped
appliances, the effective area of the common
vent connector or vent manifold and all
junction fittings shall be not less than the
area of the larger vent connector plus 50
percent of the areas of smaller flue collar
outlets. [NFPA 54: 12.11.3.6]
510.10.3.5 Where the size of a vent connec-
tor is increased to overcome installation
limitations and obtain connector capacity
equal to the equipment input, the size
increase shall be made at the equipment
draft hood outlet. [NFPA 54: 12.11.3.7]
510.10.4 Two or More Appliances Connected
to a Single Vent.
510.10.4.1 Where two or more vent
connectors enter a common gas vent,
chiinney flue, or single-wall metal pipe, the
smaller cormector shall enter at the highest
level consistent with the available headroom
or clearance to combustible material.
[NFPA 54: 12.11.4.1]
510.10.4.2 Vent connectors serving
Category I appliances shall not be connected
to any portion of a mechanical draft system
operating under positive static pressure,
such as those serving Category III or
Category IV appliances. [NFPA 54: 12.11.4.2]
510.10.5 Clearance. Minimum clearances
from vent connectors to combustible material
shall be in accordance with Table 5-3. [NFPA
54: 12.11.5]
Exception: The clearance between a vent
connector and combustible material shall be
permitted to be reduced where the com-
bustible material is protected as specified for
vent connectors in Table 5-4.
510.10.6 Avoid Unnecessary Bends. A vent
cormector shall be installed so as to avoid turns
or other construction features that create
excessive resistance to flow of vent gases. [NFPA
54: 12.11.6]
510.10.7 Joints. Joints between sections of
connector piping and connections to flue collars
or draft hood outlets shall be fastened in
accordance with one of the following methods:
[NFPA 54: 12.11.7]
(1) By sheet metal screws.
(2) Vent cormectors of listed vent material shall
be assembled and connected to flue collars
or draft hood outlets in accordance with the
manufacturers' instructions.
(3) Other approved means.
510.10.8 Slope. A vent connector shall be
installed without any dips or sags and shall
slope upward toward the vent or chimney at
least 1/4 in./ft. (20 mm/m). [NFPA 54: 12.11.8]
Exception: Vent connectors attached to a
mechanical draft system installed in accordance
with the manufacturers' instructions.
510.10.9 Length of Vent Connector.
510.10.9.1 A vent connector shall be as
short as practical and the gas utilization
equipment located as close as practical to
the chimney or vent. [NFPA 54: 12.11.9.1]
510.10.9.2 The maximum horizontal length
of a single- wall connector shall be 75 percent
of the height of the chimney or vent except
for engineered systems. The maximum
length of an individual connector for a
chimney or vent system serving multiple
appliances, from the appliance outlet to the
junction with the common vent or another
connector, shall be 100 percent of the height
of the chimney or vent. [NFPA 54: 12.11.9.2]
51 0.1 0.9.3 The maximum horizontal length
of a Type B double-wall connector shall be
100 percent of the height of the chimney or
vent, except for engineered systems. The
maximum length of an individual connector
for a chimney or vent system serving
multiple appliances, from the appliance
outlet to the junction with the common vent
or another connector, shall be 100 percent of
the height of the chimney or vent. [NFPA
54:12.11.9.3]
510.10.10 Support. A vent connector shall be
supported for the design and weight of the
material employed to maintain clearances and
prevent physical damage and separation of joints.
[NFPA 54: 12.11.10]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
60
WATER HEATERS
510.10-510.12
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
510.10.11 Chimney Connection. Where
entering a flue in a masonry or metal chimney,
the vent connector shall be installed above the
extreme bottom to avoid stoppage. Where a
thimble or slip joint is used to facilitate removal
of the connector, the connector shall be firmly
attached to or inserted into the thimble or slip
joint to prevent the cormector from falling out.
Means shall be employed to prevent the
connector from entering so far as to restrict the
space between its end and the opposite wall of
the chimney flue. [NFPA 54: 12.11.11]
510.10.12 Inspection. The entire length of a
vent connector shall be readily accessible for
inspection, cleaning, and replacement. [NFPA
54: 12.11.12]
510.10.13 Fireplaces. A vent connector shall
not be connected to a chimney flue serving a
fireplace unless the fireplace flue opening is
permanently sealed. [NFPA 54: 12.11.13]
510.10.14 Passage through Ceilings, Floors,
or Walls.
510.10.14.1 A vent connector shall not pass
through any ceiling, floor, or fire-resistance-
rated wall. A single-wall metal pipe
connector shall not pass through any
interior wall.
Exception: Vent connectors made of
listed Type B or Type L vent material
and serving listed equipment with draft
hoods and other equipment listed for
use with Type B gas vents that pass
through walls or partitions constructed
of combustible material shall be installed
with not less than the listed clearance to
combustible material.
510.10.14.2 A vent connector made of a
single-wall metal pipe shall not pass
through a combustible exterior wall unless
guarded at the point of passage by a
ventilated metal thimble not smaller than
the following: [NFPA 54: 12.11.14.2]
(1) For listed appliances equipped with
draft hoods and appliances listed for
use with Type B gas vents, the thim-
ble shall be a minimum of 4 inches (100
mm) larger in diameter than the vent
cormector. Where there is a run of not
less than 6 feet (1.8 m) of vent connector in
the opening between the draft hood
outlet and the thimble, the thimble shall
be a minimum of 2 inches (50 mm) larger
in diameter than the vent connector.
(2) For unlisted appliances having draft
hoods, the thimble shall be a minimum
of 6 inches (150 mm) larger in diameter
than the vent connector.
(3) For residential and low-heat appliances,
the thimble shall be a minimum of 12
inches (300 mm) larger in diameter than
the vent connector.
Exception: In lieu of thimble
protection, all combustible material
in the wall shall be removed from
the vent connector a sufficient
distance to provide the specified
clearance from such vent connector
to combustible material. Any
material used to close up such
opening shall be noncombustible.
510.10.14.3 Vent connectors for medium-
heat equipment shall not pass through walls
or partitions constructed of combustible
material. [NFPA 54: 12.11.14.3]
510.11 Vent Connectors for Category II,
Category III, and Category IV Gas Utilization
Equipment. (See Section 510.4.) [NFPA 54: 12.12]
510.12 Draft Hoods and Draft Controls.
510.12.1 Equipment Requiring Draft
Hoods. Vented gas utilization equipment
shall be installed with draft hoods.
[NFPA 54: 12.13.1]
Exception: Dual oven-type combination
ranges; incinerators; direct-vent
equipment; fan-assisted combustion
system appliances; equipment requiring
chimney draft for operation; single
firebox boilers equipped with
conversion burners with inputs greater
than 400,000 Btu/h (117 kW); equipment
equipped with blast, power, or pressure
burners that are not listed for use with
draft hoods; and equipment designed
for forced venting.
510.12.2 Installation. A draft hood supplied
with or forming a part of listed vented gas
utilization equipment shall be installed
without alteration, exactly as furnished and
specified by the equipment manufacturer.
[NFPA 54: 12.13.2] If a draft hood is not
supplied by the equipment manufacturer
where one is required, a draft
hood shall be installed, be of a listed or
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
61
510.12-511.1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
approved type, and, in the absence of other
instructions, be of the same size as the
equipment flue collar. Where a draft hood is
required with a conversion burner, it shall
be of a listed or approved type. [NFPA 54:
12.13.2.1] Where it is determined that a draft
hood of special design is needed or
preferable for a particular installation, the
installation shall be in accordance with the
recommendations of the equipment
manufacturer and shall be with the approval
of the Authority Having Jurisdiction.
[NFPA 54: 12.13.2.2]
510.12.3 Draft-Control Devices. Where a
draft-control device is part of the gas
utilization equipment or is supplied by the
equipment manufacturer, it shall be installed
in accordance with the manufacturer's
instructions. In the absence of manufacturer's
instructions, the device shall be attached to
the flue collar of the equipment or as near to
the equipment as practical. [NFPA
54: 12.13.3]
510.12.4 Additional Devices. Gas utilization
equipment (except incinerators) requiring
controlled chimney draft shall be permitted
to be equipped with a listed double-acting
barometric draft regulator installed and
adjusted in accordance with the manufacturers'
instructions. [NFPA 54: 12.13.4]
510.12.5 Location. Draft hoods and
barometric draft regulators shall be installed
in the same roon\ or enclosure as the
equipment in such a manner as to prevent
any difference in pressure between the hood
or regulator and the combustion air supply.
[NFPA 54: 12.13.5]
510.12.6 Positioning. Draft hoods and
draft regulators shall be installed in the
position for which they were designed
with reference to the horizontal and
vertical planes and shall be located so that
the relief opening is not obstructed by any
part of the equipment or adjacent
construction. The equipment and its draft
hood shall be located so that the relief
opening is accessible for checking vent
operation. [NFPA 54: 12.13.6]
510.12.7 Clearance. A draft hood shall be
located so that its relief opening is not less
than 6 inches (150 mm) from any surface
except that of the equipment it serves and
the venting system to which the draft
hood is connected. Where a greater or
lesser clearance is indicated on the
equipment label, the clearance shall not be
less than that specified on the label. Such
clearances shall not be reduced. [NFPA
54: 12.13.7]
510.13 Manually Operated Dampers. A
manually operated damper shall not be placed
in any equipment vent connector. Fixed baffles
shall not be classified as manually operated
dampers. [NFPA 54: 12.14]
510.14 Automatically Operated Vent Dampers.
An automatically operated vent damper shall
be of a listed type. [NFPA 54: 12.15]
510.15 Obstructions. Devices that retard the
flow of vent gases shall not be installed in a vent
comiector, chimney, or vent. The following shall
not be considered as obstructions: [NFPA
54: 12.16]
(1) Draft regulators and safety controls
specifically listed for installation in venting
systems and installed in accordance with the
terms of their listing.
(2) Approved draft regulators and safety
controls designed and installed in accor-
dance with approved engineering methods.
(3) Listed heat reclaimers and automatically
operated vent dampers installed in
accordance with the terms of their listing.
(4) Vent dampers serving listed appliances
installed in accordance with this chapter or
other approved engineering methods.
(5) Approved economizers, heat reclaimers,
and recuperators installed in venting
systems of equipment not required to be
equipped with draft hoods, provided the
gas utilization equipment manufacturer's
instructions cover the installation of such a
device in the venting system and
performance in accordance with Sections
510.3.1 and 510.3.2 is obtained.
51 1 .0 Sizing of Category I Venting Systems.
51 1 .1 These venting tables shall not be used where
obstructions (see Section 510.15) are installed in the
venting system. The installation of vents serving
listed appliances with vent dampers shall be in
accordance with the appliance manufacturer's
instructions or in accordance with the following:
[NFPA 54: 13.1.1]
(1) The maximum capacity of the vent system shall
be determined using the NAT Max column.
(2) The minimum capacity shall be determined as
though the appliance were a fan-assisted
appliance, using the FAN Min column to
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
62
WATER HEATERS
511.1
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
determine the mininium capacity of the vent
system. Where the corresponding "FAN Min" is
"NA" the vent configuration shall not be per-
mitted and an alternative venting configuration
shall be utilized.
511.1.1 Where the vent size determined from
the tables is smaller than the appliance draft
hood outlet or flue collar, the use of the smaller
size shall be permitted provided that the
installation complies with all of the following
requirements: [NFPA 54: 13.1.2]
(1) The total vent height (H) is at least 10 feet (3 m).
(2) Vents for appliance draft hood outlets or flue
collars 12 inches (300 mm) in diameter or
smaller are not reduced more than one table
size.
(3) Vents for appliance draft hood outlets or flue
collars larger than 12 inches (300 mm) in
diameter are not reduced more than two
table sizes.
(4) The maximum capacity listed in the tables
for a fan-assisted appliance is reduced by
10 percent (0.90 maximum table capacity).
(5) The draft hood outlet is greater than 4 inches
(100 mm) in diameter. Do not connect a 3-inch
(80mm) diameter vent to a 4-inch (100mm)
diameter draft hood outlet. This provision
shall not apply to fan-assisted appliances.
511.1.2 Single-appliance venting configurations
with zero (0) lateral lengths in Tables 5-8, 5-9,
and 5-12 shall have no elbows in the venting
system. For vent configurations with lateral
lengths, the venting tables include allowance for
two 90-degree turns. For each additional elbow up
to and including 45 degrees, the maximum capacity
listed in the venting tables shall be reduced by 5
percent. For each elbow greater than 45 degrees
up to and including 90 degrees, the maximum
capacity listed in the venting tables shall be
reduced by 10 percent. [NFPA 54: 13.1.3]
51 1 .1 .3 Zero (0) lateral (L) shall apply only to a
straight vertical vent attached to a top outlet
draft hood or flue collar. [NFPA 54: 13.1.4]
511.1.4 Sea level input ratings shall be used
when determining maximum capacity for high-
altitude installation. Actual input (derated for
altitude) shall be used for determining minimum
capacity for high-altitude installation. [NFPA 54:
13.1.5]
511.1.5 For appliances with more than one
input rate, the minimum vent capacity (FAN
Min) determined from the tables shall be less
than the lowest appliance input rating, and the
maximum vent capacity (FAN Max/NAT Max)
determined from the tables shall be greater than
the highest appliance rating input. [NFPA 54:
13.1.6]
511.1.6 Listed corrugated metallic chimney
liner systems in masonry chimneys shall be
sized by using Tables 5-8 or 5-9 for Type B vents
with the maximum capacity reduced by 20 percent
(0.80 maximum capacity) and the minimum
capacity as shown in Tables 5-8 or 5-9.
Corrugated metallic liner systems installed with
bends or offsets shall have their maximum
capacity further reduced in accordance with
Section 511.1.2. The 20 percent reduction for
corrugated metallic chimney liner systems
includes an allowance for one long radius 90-
degree turn at the bottom of the liner. [NFPA 54:
13.1.7]
511.1.7 Where the vertical vent has a larger
diameter than the vent connector, the vertical
vent diameter shall be used to determine the
minimum vent capacity, and the connector
diameter shall be used to determine the
maximum vent capacity. The flow. area of the
vertical vent shall not exceed seven times the
flow area of the listed appliance categorized vent
area, flue collar area, or draft hood outlet area
unless designed in accordance with approved
engineering methods. [NFPA 54: 13.1.9]
511.1.8 Connection to Chimney Liners. Connec-
tions between chimney liners and listed double-
wall connectors shaU be made with listed adapters
designed for such purposes. [NFPA 54: 13.1.8]
511.1.9 Vertical Vent Upsizing 7 x Rule. Where
the vertical vent has a larger diameter than the
vent connector, the vertical vent diameter shall be
used to determine the minimum vent capacity, and
the connector diameter shall be used to determine
the maximum vent capacity. The flow area of the
vertical vent shaU not exceed seven times the flow
area of the listed appliance categorized vent area,
flue collar area, or draft hood outlet area unless
designed in accordance with approved engineering
methods. [NFPA 54: 13.1.9]
511.1.10 Draft Hood Conversion Accessories.
Draft hood conversion accessories for use with
masonry chin\neys venting listed Category I fan-
assisted appliances shall be listed and installed in
accordance with the listed accessory manu-
facturers' installation instructions. [NFPA 54:13.1.10]
511.1.11 Tables 5-8 through 5-12 shall be used
for chimneys and vents not exposed to the
outdoors below the roof line. A Type B vent or
listed chimney lining system passing through an
unused masonry chimney flue shall not be
considered to be exposed to the outdoors. A
Type B vent passing through an unventilated
enclosure or chase insulated to a value of not
less than R8 shall not be considered to be
exposed to the outdoors. Table 5-10 in
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
63
511.1 -511.2
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
combination with Table 5-13 shall be
used for clay-tile-lined exterior masonry
chimneys, provided all of the following are met:
[NFPA 54: 13.1.11]
(1) The vent connector is Type B double wall.
(2) The vent connector length is limited to 1-1/2
feet for each inch (180 mm/mm) of vent
cormector diameter.
(3) The appliance is draft-hood-equipped.
(4) The input rating is less than the maximum
capacity given in Table 5-10.
(5) For a water heater, the outdoor design
temperature shall not be less than 5°F (15°C).
(6) For a space-heating appliance, the input
rating is greater than the minimum capacity
given by Table 5-13.
(7) Where the conditions of (1) through (6)
cannot be met, an alternative venting design
shall be used, such as a listed chimney
lining system.
Exception: Vents serving listed appliances
installed in accordance with the appliance
instructions and the terms of the listing.
51 1.1.12 Corrugated vent connectors shall not be
smaller than the listed appliance categorized
vent diameter, flue collar diameter, or draft
hood outlet diameter. [NFPA 54: 13.1.12]
511.1.13 Vent connectors shall not be upsized
more than two sizes greater than the listed
appliance categorized vent diameter, flue collar
diameter, or draft hood outlet diameter. [NFPA
54: 13.1.13]
511.1.14 In a single run of vent or vent
connector, more than one diameter and type
shall be permitted to be used, provided that all
the sizes and types are permitted by the tables.
[NFPA 54: 13.1.14]
511.1.15 Interpolation shall be permitted in calcu-
lating capacities for vent dimensions that fall
between table entries. (See Part II-Example G.1.3.)
[NFPA 54: 13.1.15]
51 1 .1 .1 6 Extrapolation beyond the table entries
shall not be permitted. [NFPA 54: 13.1.16]
511.1.17 For vent heights lower than 6 feet and
higher than shown in the tables, engineering
methods shall be used to calculate vent capacities.
[NFPA 54: 13.1.17]
511.2 Additional Requirements to IVIultiple
Appliance Vent Table 5-8 through Table 5-22.
511.2.1 Obstructions and Vent Damper.
These venting tables shall not be used where
obstructions (see Section 510.15) are installed
in the venting system. The installation of vents
serving listed appliances with vent dampers
shall be in accordance with the appliance
manufacturers' instructions or in accordance
with the following: [NFPA 54: 13.2.1]
(1) The maximum capacity of the vent
connector shall be determined using the
NAT Max column.
(2) The maximum capacity of the vertical vent
or chimney shall be determined using the
FAN + NAT column when the second
appliance is a fan-assisted appliance, or the
NAT + NAT column when the second
appliance is equipped with a draft hood.
(3) The minimum capacity shall be determined
as if the appliance were a fan-assisted appliance.
(a) The minimum capacity of the vent
connector shall be determined using the
FAN Min column.
(b) The FAN + FAN column shall be used
when the second appliance is a fan-
assisted appliance, and the FAN + NAT
column shall be used when the second
appliance is equipped with a draft
hood, to determine whether the vertical
vent or chimney configuration is not
permitted (NA). Where the vent
configuration is NA, the vent configuration
shall not be permitted and an alter-
native venting configuration shall be
utilized.
51 1 .2.2 The maximum vent connector horizontal
length shall be 18 in. /in. (180 mm/mm) of
connector diameter as shown in Table 5-7.
[NFPA 54: 13.2.2]
51 1 .2.3 The vent connector shall be routed to
the vent utilizing the shortest possible route.
Connectors with longer horizontal lengths than
those listed in Table b-7 are permitted under the
following conditions: [NFPA 54: 13.2.3]
(A) The maximum capacity (FAN Max or NAT
Max) of the vent connector shall be reduced
10 percent for each additional multiple of
the length listed in Table ^-7 . For example,
the maximum length listed for a 4-inches
(100mm) connector is 6 feet (1.8 m). With a
connector length greater than 6 feet (1.8 m) but
not exceeding 12 feet (3.7 m), the maximum
capacity must be reduced by 10 percent
(0.90 maximum vent connector capacity).
With a connector length greater than 12 feet
(3.7 m) but not exceeding 18 feet (5.5 m), the
maximum capacity must be reduced by 20
percent (0.80 niaximum vent capacity).
(B) For a connector serving a fan-assisted
appliance, the minimum capacity (FAN
Min) of the connector shall be determined
by referring to the corresponding single
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
, NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
64
WATER HEATERS
511.2
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
appliance table. For Type B double-wall
connectors. Table 5-8 shall be used. For
single-wall connectors. Table 5-9 shall be
used. The height (H) and lateral (L) shall be
measured according to the procedures for a
single appliance vent, as if the other
appliances were not present.
TABLE 5-7
Vent Connector Maximum Length
[NFPA 54: Table 13.2.2]
Connector Diameter
IVIaximum (in.)
Connector Horizontal
Length (ft.)
5
6
7
8
9
10
12
14
16
18
20
22
24
4-1/2
6
7-1/2
9
10-1/2
12
13-1/2
15
18
21
24
27
30
33
36
For SI units, 1 in. = 25.4 mm; 1 f t = 0.305 m.
[NFPA 54: Table 13.2.2]
511.2.4 Where the vent connectors are
combined prior to entering the vertical portion
of the common vent to form a common vent
manifold, the size of the common vent
manifold and the common vent shall be
determined by applying a 10 percent reduction
(.90 X maximum common vent capacity) to the
Common Vent Capacity part of the common
vent tables. The length of the common vent
connector manifold (LM) shall not exceed 18
in. /in. (180 mm/mm) of common vent
connector manifold diameter (D). (See Part II-
Figure G.l(k).) [NFPA 54: 13.2.4]
511.2.5 Where the common vertical vent is
offset, the maximum capacity of the common
vent shall be reduced in accordance with Section
511.2.6, and the horizontal length of the common
vent offset shall not exceed 18 in. /in. (180
mm/mm) of common vent diameter. [NFPA 54:
13.2.5]
51 1 .2.6 For each elbow up to and including 45
degrees in the common vent, the maximum
common vent capacity listed in the venting
tables shall be reduced by 5 percent. For
each elbow greater than 45 degrees up to and
including 90 degrees, the maximum common
vent capacity listed in the venting tables shall be
reduced by 10 percent. [NFPA 54: 13.2.6]
511.2.7 The vent connector capacities listed
in the common vent sizing tables include
allowance for two 90-degree elbows. For each
additional elbow up to and including 45
degrees, the maximum vent connector
capacity listed in the venting tables shall be
reduced by 5 percent. For each elbow greater
than 45 degrees up to and including 90
degrees, the maximum vent connector
capacity listed in the venting tables shall be
reduced by 10 percent. [NFPA 54: 13.2.7]
511.2.8 Common Vent Minimum Size. The
cross-sectional area of the common vent shall be
equal to or greater than the cross-sectional area
of the largest connector. [NFPA 54: 13.2.8]
511.2.9 Tee and Wye Fittings. Tee and wye
fittings connected to a common vent shall be
considered as part of the common vent and
constructed of materials consistent with that of
the common vent. [NFPA 54: 13.2.9]
511.2.10 At the point where tee or wye fittings
connect to a common vent, the opening size of
the fitting shall be equal to the size of the
common vent. Such fittings shall not be
prohibited from having reduced size openings at
the point of connection of appliance vent
connectors. [NFPA 54: 13.2.10]
511.2.11 Sea level input ratings shall be used
when determining maximum capacity for high-
altitude installation. Actual input (derated for
altitude) shall be used for determining minimum
capacity for high-altitude installation. [NFPA 54:
13.2.11]
511.2.12 The connector rise (R) for each
appliance connector shall be measured from the
draft hood outlet or flue collar to the centerline
where the vent gas streams come together.
[NFPA 54: 13.2.12]
511.2.13 For multiple units of gas utilization
equipment all located on one floor, available
total height (H) shall be measured from the
highest draft hood outlet or flue collar up to the
level of the outlet of the common vent. [NFPA
54: 13.2.13]
511.2.14 For multistory instcillations, available
total height (H) for each segment of the system
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
65
511 .2 -Figure 5-7
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
shall be the vertical distance between the highest
draft hood outlet or flue collar entering that
segment and the centerline of the next higher
interconnection tee. (See Part Il-Figure G.l(j).)
[NFPA 54: 13.2.14]
511.2.15 The size of the lowest connector and
of the vertical vent leading to the lowest
interconnection of a multistory system shall be
in accordance with Tables 5-8 or 5-9 for available
total height (H) up to the lowest interconnection.
(See Part II-Figure G.l(n).) [NFPA 54: 13.2.15]
511.2.16 Where used in multistory systems,
vertical common vents shall be Type B double-
wall and shall be installed with a listed vent cap.
[NFPA 54: 13.2.16]
511.2.17 Offsets in multistory common vent
systems shall be limited to a single offset in each
system, and systems with an offset shall comply
with all of the following: [NFPA 54: 13.2.17]
(1) The offset angle shall not exceed 45 degrees
from vertical.
(2) The horizontal length of the offset shall not
exceed 18 inches for each inch (180 mm/mm)
of common vent diameter of the segment in
which the offset is located.
(3) For the segment of the common vertical vent
containing the offset, the common vent
capacity listed in the common venting tables
shall be reduced by 20 percent (0.80 x maximum
common vent capacity).
(4) A multistory comrnon vent shall not be
reduced in size above the offset.
511.2.18 Where two or more appliances are
connected to a vertical vent or chimney, the flow
area of the largest section of vertical vent or
chimney shall not exceed seven times the
smallest listed appliance categorized vent areas,
flue collar area, or draft hood outlet area unless
designed in accordance with approved
engineering methods. [NFPA 54: 13.2.18]
511.2.19 For appliances with more than one
input rate, the minimum vent connector capacity
(FAN Min) determined from the tables shall be
less than the lowest appliance input rating, and
the maximum vent connector capacity (FAN Max
or NAT Max) determined from the table shall be
greater than the highest appliance input rating.
[NFPA 54: 13.2.19]
511.2.20 Listed corrugated metallic chimney
liner systems in masonry chimneys shall be
sized by using Tables 5-14 or 5-15 for Type B
vents, with the maximum capacity reduced by
20 percent (0.80 maximum capacity) and the
minimum capacity as shown in Tables 5-14 or
5-15. Corrugated nietallic liner systems installed
with bends or offsets shall have their maximum
capacity further reduced in accordance with
Sections 511.2.5 and 511.2.6. The 20 percent
reduction for corrugated metallic chimney liner
systems includes an allowance for one long
radius 90-degree turn at the bottom of the liner.
[NFPA 54: 13.2.20]
511.2.21 Tables 5-14 and 5-15 shall be used for
chimneys and vents not exposed to the outdoors
below the roof line. A Type B vent passing
through an unventilated enclosure or chase
insulated to a value of not less than R8 shall not
be considered to be exposed to the outdoors.
Tables 5-19 and 5-20 shall be used for clay-tile-
lined exterior masonry chimneys, provided all of
the following conditions are met: [NFPA 54:
13.2.23]
(1) Vent cormector is Type B double-wall.
(2) At least one appliance is draft-hood-
equipped.
(3) The combined appliance input rating is less
than the maximum capacity given by Table
5-19 (for NAT + NAT) or Table 5-21 (for
FAN + NAT).
(4) The input rating of each space-heating
appliance is greater than the minimum
input rating given by Table 5-20 (for
NAT + NAT) or Table 5-21 (for FAN + NAT).
Chimney or gas vent
_...,.
1 1 '1 r 1 I 1 1
1
1 1 t ( ' 1 " 1 ' 1 ' t ' I
JL....1
1 1 1 t 1 i 1 1
,,! 1 - -
FIGURE 5-7 All Combustion Air from Indoor
Spaces through Indoor Combustion Air
Openings. [NFPA 54: Figure A.9.3.2.3(1)]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
nfpa"
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
66
WATER HEATERS
511.2-512.0
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
-NFPA
NFPA I
NFPA I
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(5) The vent connector sizing is in accordance
with Table 5-16.
(6) Where these conditions cannot be met, an
alternative venting design shall be used,
such as a listed chimney lining system.
Exception: Vents serving listed appliances
installed in accordance with the appliance
manufacturers' installation instructions.
51 1 .2.22 Vent connectors shall not be increased
more than two sizes greater than the listed
appliance categorized vent diameter, flue collar
diameter, or draft hood outlet diameter. Vent
connectors for draft-hood-equipped appliances
shall not be smaller than the draft hood outlet
diameter. Where vent cormector sizes determined
from the tables for fan-assisted appliances are
smaller than the flue collar diameter, the use of
the smaller sizes shall be permitted provided
that the installation complies with all of the
following conditions: [NFPA 54: 13.2.24]
(1) Vent connectors for fan-assisted appliance
flue collars 12 inches (300 mm) in diameter
or smaller are not reduced by more than one
table size [e.g., 12 inches to 10 in. (300 mm to
250 mm) is a one-size reduction] and those
larger than 12 inches (300 mm) in diameter
are not reduced more than two table sizes
[e.g., 24 inch to 20 inch (610 mm to 510 mm)
is a two-size reduction].
(2) Fan-assisted appliances are common vented
with a draft-hood-equipped appliance.
(3) The vent connector has a smooth interior
wall.
511.2.23 All combinations of pipe sizes,
single-wall, and double-wall metal pipe shall
be allowed within any connector run or
within the common vent, provided ALL of
the appropriate tables permit ALL of the
desired sizes and types of pipe, as if they
were used for the entire length of the subject
connector or vent. Where single-wall and
Type B double-wall metal pipes are used for
vent connectors within the same venting
system, the common vent must be sized
using Tables 5-15 or 5-17 as appropriate.
[NFPA 54: 13.2.25]
511.2.24 Where a table permits more than one
diameter of pipe to be used for a connector or
vent, all the permitted sizes shall be permitted to
be used. [NFPA 54: 13.2.26]
511.2.25 Interpolation shall be permitted in
calculating capacities for vent dimensions that
faU between table entries. (See Part U Annex G.1.3.)
[NFPA 54: 13.2.27]
511.2.26 Extrapolation beyond the table
entries shall not be permitted. [NFPA 54: 13.2.28]
51 1 .2.27 For vent heights lower than 6 feet and
higher than shown in the tables, engineering
methods shall be used to calculate vent capacities.
[NFPA 54: 13.2.28]
512.0 Direct- Vent Equipment. Listed direct-vent
gas utilization equipment shall be considered
properly vented where installed in accordance with
the terms of its listing, the manufacturers'
instructions, and Section 510.8.3. [NFPA 54: 12.3.5]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
67
Figure 5-8 ~ Figure 5-1 1
UNIFORIVI PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NfPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Chimney or ga$ vent
Ventilation touvers
(each end of attte)
Alternate
air iniet
Chimney or gas vent
Ventilation iouvers for
unheated crawl space
FIGURE 5-8 All Combustion Air from Outdoors -
Inlet Air from Ventilated Crawl Space and Outlet
Air to Ventilated Attic. [NFPA 54: Figure
A.9.3.3.1(1)(a)]
Chimney or ps vent
Ventilation louvers
(each end of attic)
FIGURE 5-10 All Combustion Air from Outdoors
through Horizontal Ducts. [NFPA 54: Figure
A.9.3.3.1(2)]
Chimney or gas vent
inlet air diK^
[er«te 1ft (300 iron)
aljove flcwr]
m
I ■ I , I ■ I . I ,1=1
FIGURE 5-9 All Combustion Air from Outdoors
through Ventilated Attic. [NFPA 54: Figure
A.9.3.3.1(1)(b)]
Opening
Alternate
opening
location
FIGURE 5-1 1 All Combustion Air from Outdoors
through Single Combustion Air Opening.
[NFPA 54: Figure A.9.3.3.2]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
68
WATER HEATERS
Figure 5-12 - Figure 5-13
Mechanical
draft \^nt
terminal
(see 5iaai)
Forced air
iniet
Direct vent terminal cleararK^
Minimum clearance, C
Input (Btu/hr) CleargwYce (In.)
10.000 or less
10.001 to 50,000 9
Over 50,000 12
(see 10.8.3)
For SI units: 1 ft = 0.305 m; 1 in. « 25.4 mm;
1 Btu/hr == 0.293 W
FIGURE 5-12 Exit Terminals of Mechanical Draft and Direct- Vent Venting Systems. [NFPA 54: Figure A.12.91
(TC)
99% Winter Design Temperatures for the Contiguous United States
This map is a necessarily generalized guide to temperatures in the contiguous United States. Temperatures shown for areas
such as mountainous regions and large urban centers may not be accurate. The data used to develop this map are from the
1 993 ASHRAE Handbook — Fundamentals (Chapter 24, Table 1 : Climate Conditions for the United States).
For 99% winter design temperatures in Alaska, consult the ASHRAE Handbook — Fundamentals.
99% winter design temperatures for Hawaii are greater than 37°F.
FIGURE 5-13 Range of Winter Design Temperatures Used in Analyzing Exterior Masonry Chimneys in
the United States. [NFPA 54:Figure G.2.4]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA'
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
69
Table 5-8
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-8 Type B Double-Wall Gas Vent
Lateral
L
(ft)
Number of Appliances:
Single
Appliance Type:
Category I
Appliimtxv Vent Connection:
Connected Dirertly to Vent
Vent Diameter -
-/>(m.)
3
^
5
^1
7
8
9
Appliance Input Rating
m Tliousiinds of Btu per Hour
H
m
FAN
NAT
Mas
FAN
NAT
Max
FAN
NAT
Max
FAN
;
NAT
Max
FAN , NAT
FAN
NAT
Max'
FAN
■NAT-
Min
Max
Min
Max
Min
Max
Min
Max '
Min Max Max
Min Nia.x
Min
Max
Mas
f>
78
46
152
m
251
.141
375 '
205
524 2a3
698 ,
' 370
897 ■
■ 470
2
13
51
;^6
18
97 ■
m
27
157
!»»5
32
232
157
44 321 2(7
53 425
285
63
543
-.370
4
21
19
;!4
SO
91
64
39
153
103
30
227
'153
66 316 21 1
79 419
279
93
5,36
!562
6
25
4(i
32
36
9}
61
47
149
iO<!
59
223
119,
78 310 205
93 413
273
110
530
,,854
8
84
50
Ho
»4
27(i
155
415 .
^ 235
583 - 320
780
415
10«0
' 537
2
12
57
40
16
109
75
25
178
120
28
263
ISO
42 365 247'
50 483
■ .322,
00
619
4!8
5
23
53
m
32
103
71
42
171
115
53
253
173
70 356 237
S3 473
313
99
607
407
8
28
49
■ 35
39
98
66
51
164
109
64
247
163
84 347 227
99 463
• 303
117
596
, "3^
!0
88
53
175
100
295
. 166
447
253
031 345
847 ;
. 450
1090
- 585
2
12
01
42
17
118
81-
23
194
129
26
289
195
40 462 273
48 533
S.55
57
684
4S7
5
23
57
40
32
N3
77
41
187
124
52
280 ,
188
68 392 263
SI ,322
'fm
93
671
446
10
30
51
3()
41
104
70
54
176
115
67
267
175
88 376 245
104 ,504 •
, 330
122
651
427
15
«
<.t4
58
19i
H2
327
187
502
ate
716 390
970
. .525
1263
(582
2
11
f)0
. 48
15
1,36
■ 93
20
220
150
22
,339
223
38 475 316
43 6,33
414
53
815
544
5
22
05
43
30
130
87
39
219
142
49
330 ,
217
64 463 300
76 620
403
90
800 ■
529
!0
29
59
41
40
121
82
51
206
1»
64
315
im
84 445 288
99 600
386
116
777
507
15
35
53
37
48
112
76
61
195
_ 128
76
301
198
98 429 275
115 580
373
134
7.55
4»1
20
97
61
202
119
349
202
540
~ , -.307
776 4S0
1057
' 575
13S4
'732
2
10
75
51
14
H9
■ 10O
18
250
166
20
377
249
33 531 346
41 711
470
50
917 ■
612
f)
21
71
48
29
143
96
38
242
liKI
47
367
241
62 519 337
73 697
460
86
902
599
10
28
04
44
38
133
89
50
229
150
62
351
22H
SI 499 321
95 675
• 44.3
112
877
576
},'>
34
58
4ft
4!)
124
,84
59
217
142
73
337 ■■
217
94 481 aitH
111 0,54,
■ -427
129
853
557
20
48
52
35
55
no
78
69
200
134
84
322
206
107 464 295
125 634
■410
143
830
537
30
100
m
213
128
374
220
587
. 336
853 475
1173'
650
1548 ■
855
2
9
81
56
13
166
112
14
283
185
18
432
280
27 613 .394
33 826
:533
42
1072 •
im
5
21
77
54'
28
160
108
36
273
176
45
421
273
38 60O 385
69 81 1
,524
82
10.55
' ik^
10
27
70
f.O
37
150
102
48
202
171
59
405
261
77 580 37 t
91 788
507
107
1028
6!)8
ir>
33
f.4
NA
44
141
m
57
249
163
70
389
,249
90 560 357
103 763
• ,490
124
1002
648
20
36
58
NA
53
132
90
66
237
154
80
374
237
102 542 343
119 743
473
139
977
6SS
30
NA
NA
NA
73
113
NA
88
214
NA
104
346
219
131 .507 321
149 792
, -144
171
929
5*1
50
101
07
216
134
397
932
633 ,
3(13
932 518
1297
.708
1730
952
2
8
80
61
1,1
183
122
14
320
206
15
497
314
22 715 445
26 975 ,
615
33
1276 ■
813
5
20
82
■ NA
27
177
no
35
312
200
43
487
308
53 702 ■ , 438
05 960
MJ5
77
1239
798
10
26
70
NA
35
1(>8
114
43
299
■ 190
56
471
298
7.3 681 - 426
86 9.!5
.589
101
12,30
773
15
59
70
NA
42
158
NA
54
287
.180
66
455 ■
, ass
83 662 413
100 911
.572
117
1203
747
20
NA
NA
NA
m
149
NA
63
275
169
76
440
278
97 042 .401'
113 888
356
131
1176
■ 722
30
NA
KA
NA
m
13!
NA-
84
250
,NA
99
410
259
123 605 376
141 84-1
'mi
161
112.5
670
IW)
NA
NA
NA
218
NA
407
,NA
663 ■
400
997 . 560
1411
770
1998
MHO
2
NA
NA
NA
10
194
NA
12
334
NA
13
StWi
375'
18 831 510
21 1 1 55
• 700
23
1536 ,
mh
5
NA
NA
NA
26
189
NA
33
347
. NA
40
557
%m
52 820 504
00 IMl
692
71
1319
926
10
NA
NA
NA
S3
182
NA
43
335
NA
53
542
36!
68 801 49.3
80 1118
* 079
94
1492
910
15
NA
NA
NA
40
174
NA
50
321
NA
62
528
333
80 782 ■ 4«2
93 1093
«i6
109
1463
R93
20
NA
NA
NA
47
lOti
NA
59
311
NA
71
513
344
90 763 471
103 1073
• 6.3:4
122
i4;{8
880
30
NA
NA
NA
NA
NA
NA
78
290
NA
92
483
NA
115 726 449
131 1029
627
149
1387
849
50
NA
NA
NA
NA
NA
NA,
NA
NA
. NA
147
428
NA
180 051 '405
197 944
,375
217
1288
787
[NlTA54Tablel,3.1<;i)l
70
WATER HEATERS
Table 5-8 continued
Table 5-8 continued
Number of Appliances:
SingI
e
Appliance
T)pe:
Category I
Appliance Vent Connection:
Connected Directly to Vent
Vent Diameter — X) (in. )
10
12
14
U
18
_ «« ,
22
u
Appliance Input Rating in
Thousands of Bt» per Hour
Height Lateral
FAN
NAT
Max
FAN NAT
FAN
NAT
Max
VAH
NAT
Max
FAN
NAT
JMbx
Fj«J
NAT
Max
FAN NAT
F.AN NAT
(ft) (ft)
Min
Max
Min
Max Max
Min
Max
Min
Max
Min
Max
Miti
Max
Min Max Max
Min
Max Max,
e
1121
570
1645 830
2267
1170
2<)S3
1.530
3802
1960
4721
243t»
3737 29.^)
6833 .3520
2
73
f.75
435
103
982 ■ Ofrf)
!38
I34<)
890
178
1769
liTW
225
2250
148?)
2<K»
2782
la30
3W) .3377 Ti20
426
40.30 2670
4
110
BtiH
445
147
975 640
191
1338
880
242
1761
im>
3(.K!
2242
147.3
390
2774
1835
4<;9 3370 2215
.553
4023 2660
6
128
frfil
435
171
967 630
219
1330
»70
276
1733
1150
341
2233
1470
437
2767
1820
.323 3363 '2210
618
4017 26.30
8
1261
660
1858 970
2371
1320
3399
1740
4333
2220
3.387
2730
6355 .3360
7838 4010
2
71
770
513
98
1134 743
130
1543
1020
168
20,30
1340
212
2584
1700
278
3196
2110
,336 .3882 2.360
401
4634 .3050
3
115
75K
503
154
1110 ,733
199
1528
1010
251
2013
1330
311
2.5((3
1683
.398
3180
2090
476 .3863 2.345
362
4612 .3040
8
137
740
490
180
1097 720
231
1314
.iO(H»
289
2000
!320
3.54
23,52
1670
450
3163
2070
337 .1830 ' 2330
630
1602 :«)30
10 (>
1377
720
2036 1060
2825
i
:i450
3742
1923
4782
2430
59.5.3
30.30
72.34 3710
86.S2 44m)
2
m
852
560
93
1214 850
124
1713
il3i!
161
2256
HHO
202
2868
1890
264
3536
2340
319 4322 284!>
378
5153 .3.390
5
112
83U
347
149
1229 829
192
1690
1103
243
2238
146!
300
2849
187!
382
3336
2S18
4.58 4301 2818
.340
31.32 .3,371
10
J42
817
523
187
1204 795
238
1069
wm
298
2209
1430
364
2818
18-10
4.39
.3.504
2280
546 4268 2780
641
.3099 ,3340
15
15<!{i
840
2380 1240
3323
\m
4423
2270
5678
2900
709!;)
.3620
(» 8663 4410
10„393 ,3.300
2
t)3
lOiy
B73
86
1495 985
114
2062
i35ff
147
2719
1770
186
3467
'/am
239
4304
2800
290 5232 3410
346
6231 4080
3
103
mi-i
rni
140
1476 907
182
204!
!327
229
2696
!748
283
3442
2235
3.55
427H
2777
426 5204 3385-
501
6222 4057
10
135
977
635
177
1446 936
227
2009
1^9
283
26,59
1712
346
3402
2193
432
4234
2739
510 3159 ' 3343
.599
6175 4019
13
153
y33
010
202
1418 903
237
1976
12S0
318
2623
1675
385
.3,363
2130
479
4192
2700
.364 5115 '3300
665
6129 3980
20
1730
«30
2637 1350
3701
1900
4948
2520
6.376
mm
7988
4060
9785 4980
11,733 6000
2
59
1150
753
81
1694 1100
107
2343
!520
139
3097
2«i0
173
39.35
2.370
220
4916
3200
269 .3983 3910
321
71.34 4700
->
101
1 133
738
135
1674 1079
174
2320
1498
219
;i071
1978
270
3926
2344
.337
4883
.3174
403 .39.50 3880
475
7119 4662
10
KM
1 105
710
172
HHl 1045
220
2282
1460
273
,3029
1940
334
3880
23m)
113
4835
3!S0
189 5896 38.30
573
7063 4000
15
150
1078
fi88
195
1(509 1018
248
2243
.1425
306
2',)88
1910
372
3835
2463
4.39
4781)
Mm
34! .384! ,3795
631
7007 437.3
20
167
1032
OKi
217
1578 990
273
2210
.1390
335
2948
!880
404
3791
24,30
495
4737
.10,50
.385 5792 .3760
689
69,33 4rm
30
1977
itKifl
3004 4530
4Z52
2170
5725
2920
7420
.3770
9341
47.30
11,483 mm
1,3,848 ' 7060
2
54
135!
865
74
2004 !3iO
98
2786
1800
127
3696
2380
1.59
4734
3030
199
.3900
.3810
211 7194 46.30
283
8617 .3600
5
90
1332
851
127
1981 J289
161
2759
!775
206
36(ir,
2350
252
4701
3020
312
3863
.3783
373 7155 .1622
439
8574 5532
10
123
1301
829
164
UM4 1234
209
2716
1733
239
3617
2300
316
4647
2970
38{)
.5803
,3739,
456 7m)0 4.374
335
8.505 .3471
15
143
1272
mi
187
1(M)S 1220
237
2674
i<i92
292
3570
22r>(»
354
4594
2920
431
5744
.3693 ■
.307 7026 4327
.390
8437 ,3391
20
ffiO
1243
784
207
1873 1185
260
2633
1630
319
3523
22(Mi
384
4542
2«70
467
.3686
.3a30
.348 6964 4480
639
8370 .3310
30
195
1189
745
246
1807 1130
:»)5
2535
ISHS
369
3433
2130
440
4442
2783
540
.3574
.3.365
635 6842 4375
7,39
8239 .322,3
50 ,
2231
1195
3141 1823
4934
'2350
671 1
31440
8774
4460
1
1.129
363.3
13,767 6940
16.694 8430
2
41
1{)20
!01U
66
2431 1513
86
3409
2123
113
4351
2840
141
.5864
S670
171
7339
4i>m
209 8980 3695
251
10,788 68C0
■ f>
<J0
1600
95M)
118
2406 1495
131
3380
2102
191
4520
2813
234
582()
3689
283
7295
4597
3.36 8933 36.34
394
10,737 f 6818
10
UH
1307
972
154
2366 (4f>6
196
3332
2064
243
4464
2767
295
.5763
3,383
335
7224
4342
419 8853 . ,5585
491
10.6.32 6749
15
136
1536
948
177
2327 1437
222
3285
2026
274
4409
2721
3.30
3701
3534
396
7155
4511
465 8779 5.546'
.342
10,570 6710
20
15!
1303
924
195
2288 1408
244
3239
i987
300
43,16
2675
361
5641
3481
433
7086
4479
506 870-1 , 5506
.386
10,488 6670
30
183
1446
876
232
2214 1349
287
3150
,1910
,347
4253
26SI
412
.5523
3431
494
0953
4421
377 8357 S444
672
10,328 6603
100
249!
1310
3925 2030
r.729
wm
7914
4030
10.483
5860
13,454
6700
016,817 8600'
i
20,578 10,300,
2
30
1973
1170
44
3027 1820
72
4313
2550
93
5834
SalM!
120
7391
4600
1.38
9377
.3H<m
169 1 1.803 7af»
204
14,261 88(M)
5
82
1955
1159
107
■mn 1803
136
4282
233!
172
5797
3475
208
75 !8
4.366
245
9.328
.5769
293 11,748 7162
341
14,204 87.36
10
108
lyj:,
1142
142
2961 .i775
180
423!
tm)
223
5737
3434
2(i8
7478
4.309
318
9147
.5717
374 11.6.38 7100
436
14,103 8683
15
126
1892
1124
163
2920 1747
206
4182
2469
252
3678
3392
304
7409
4451
3.38
9367
r>66,3
4 18 11, .369 70.37
487
11,007 • 8610,
20
MJ
1861
1107
181
2880 Ills
226
4133
2438
277
.56 i 9
3951
3.30
7341
4.394
.387
9289
.5613
4.52 11.4.32 6975
523
13,910 8537
30
170
1802
107!
2!5
280S 1663
205
4037
2373
319
5505
3267
378
7209
4279
446
9136
5Sf!9
314 1 1.310 <«!IS«
.392
13,720 8391
50
241
l<i8S
iooo
292
2637 1950
350
3856
2250
4!3
3289
3!00
486
69.56
40.%
572
8841
.530(1
6.39 10,979 mm
752
13,.»4 810(1
For Sr miit-s, 1 in. = 25.4 mm, 1 ft = 0.30.5 in, 1000 Blii/hr- = 0.293 kW^ 1 iii.'-^ = 64.5 mnr.
[NFPA 54 Table 13.1(a)]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
71
Table 5-9
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-9 Type B Double-WaU Vent
Lateral
I
(ft)
Niniiber of
Appliances:
SingI
e
AppI
lancc Type:
Category I
Appliance Vent Connci
(ion:
SingI
eWall Metal Connector
Veni Diameter
-Dim.)
3
4
S
6
7
8
9
ID
12
Appliance Input Rating in ITjoiisands of Btu per
Hour
Height
H
(ft)
FAN
HAT
.Max
FAN
NAT'
Max'
FAN
NAT
Mas
FAN NAT_
FAN
NAT~
Msix-
FAN
NAT
Max
FAN
NAT
Max
FAN
NAT-
Max
FAN
NAT
Urn
Max
Min
Max
Min
Max
MhJ
Max Max
Mill
Max
Min
Max
Min
Max
Min
Max
Min
Max
-Maxj
6
38
77
: 45
59
151
85
85
249
HO
126
373 tm
165
522
284
211
695
369
267
894
469
,371
i1l8
369
537
1639
849
2
39
51
36
m
90
m
85
156
'.94
123
231 136
159
.320
213
201
423
284
251
.541
,3(58
347
673
453
498
979
648
4
NA
NA
33
74
92
63
102
152
102
146
225 152
187
313
208
237
416
277
295
533
.360
409
664
443
584
971
6S8
6
NA
NA
31
83
89
60
114
147
m
163
220 148
207
307
203
263
409
271
327
526
352
449
656
433
638
962
627
8
37
8,3
50
58
104
93
S3
273
1.54
123
412 ; 234
IRl
58(t
Si9
200
777
414
258
1002
.536
360
!2.57
658
.521
1852
967
%
39
56
, m
59
i08
75
83
J 70
119
121
201 179
155
363
2<W>
197
482
,321
246
617
417
339
768
,513
486
1 120
743
5
NA
NA
37
77
102
m
i07
108
114
15!
2,52 .171
193
3.52
235
24.5
470
sn
305
604
4«4
418
754
'300
598
1104
790,
8
NA
NA
33
yo
95
^
122
Ifil
107
175
243 163
223
.342
225
280
4.58
300
344
.591
.392
470
740
486
665
1089
715
]0
37
S7
53
57
174
m
82
293
165
120
444 254
158
628
344
202
844
449
253
1093
.584
351
1373
718
r.07
2031
1057.
2
39
01
41
59
117
m
82
193
1S8
119
287 194,
1.53
400
272
193
535
.354
242
681
4S6
332
849
.559
475
1242
848
5
52
56
■39
7fi
111
70
105
185
122
148
277 186
190
388
201
241
518
344
299
607
443
409
834
544
,584
1224
825-
10
NA
NA
34
97
190
08
132
171
U2
188
261 ■ 171
237
309
241
290
497
.325
363
013
423
492
808
,.520
088
1194
788
\5
()
?*
93
57
50
190
U'l
80
325
186
116
499 2^3
153
713
. 3RS
195
906
.523
244
12.59
681
3.36
1,591
838
488
2374
J237
2
3,S
m
47
57
130
93
8(t
225
1-19
115
337 224
148
■173
3J4
187
631
413
232
812
.543
319
1015
673
4,57
149!
t«3
5
51
03
44
75
128
80
102
210
140
144
326 217
182
4,59
298
231
016
400
287
795
526
.392
997
657
.562
1469
963
10
NA
NA
39
95
110
79
128
201
131
182
308 203
228
4;»i
284
284
.592
3S1
349
768
301
470
906
628
664
1433
928
15
NA
NA
-NA
NA
NA
72
158
180
- 124
220
2U0 192
272
418
269
334
.508
367
4rH
712
4«4
540
937
601
730
1399
894
20
35
yfi
60
54
200
118
"!<
340
20!
114
537 300
149
772
428
190
10.53
.573
238
1379
7SI)
326
175!
927
473
2631
1,346'
2
37
74
59
50
118
99
78
218
,165
113
375 248
114
528
344
182
708
468
227
914
6H
,309
1146
754
443
1689
1098
5
50
OH
,4"
73
140
94
100
239
158
14!
303 239
178
514
334
224
092
4r»-
279
896
'■m
381
1126
7,H4
547
I6C5
1074'
10
NA
NA
41
93
129
80
125
223
HO
177
344 224
222
491
316
277
606
437
339
806
370
457
1092
702
640
1626
1037
15
NA
NA
NA
NA
NA
SO
155
208
136
216
325 - 210
264
469
301
325
04O
419
393
838
549
.526
!0(iO
677
730
1587
100.5
20
NA
NA
NA
NA
NA
NA
!K0
192
120
2.54
.306 196
809
448
285
374
016
400
448
810
.526
592
1028
6.51
80S
1.550
973
SO
31
m
63
53
211
la-
76
372
2W
110
584 334
144
849
472
181
1108
647
229
1542
8S2
312
1971
1056
4.54
2996
1345
2
37
80
56
55
104
in
70
2Si
183
109
429 279
139
010
-392
175
823
.533
219
1069
698
2lH)
1346
863
424
1999
1.308
5
49
74
52
72
157
HlO
98
271
173
136
417 271
171
.595
3«2
215
806
,521
269
1049
rm
3fi6
1324
846
,524
1971
1283
10
NA
NA
NA
91
144
m
122
255
108
171
397 257
213
570
367
265
777
.501
327
1017
(«>2
440
1287
821
620
1927
1243'
15
NA
NA
NA
1!5
131
NA
151
2.39
■157
20.S
377 242
2,55
547
349
312
750
481
379
9.85
638
507
1251
794
702
1884
,1205
20
NA
NA
NA
NA
NA
NA
181
223
NA
246
357 228
298
524
333
360
723
461-
433
955
61.5
570
1216
7(j8
780
1841
1166
30
NA
NA
NA
NA
NA
NA
NA
N.\
NA
NA
NA NA
389
477
.303
461
070
420
.541
895
.574
704
1147
730
9.37
1759
llOi
50
33
<»)
m
51
213
133
73
394
230
105
629 361
138
928
5i'5
176
1292
704
220
1724
948
295
2223
■1!«9
428
3432
1818
2
»>
S4
in-
53
181
12!
73
318
203
104
495 312
J 33
712
413
108
97J
613
209
1273
811
280
!615
1007
401
2120
IS09
5
48
80
NA
70
!74
117
9t
308
198
131
482 305
104
096
435
201
9.53
602
257
12.52
Tfr.
347
1591
991
496
2396
1490
10
NA
NA
NA
89
iOO
NA
lis
292
■1R6
102
401 2S>2
203
071
420
2.53
923
r.83
313
1217
765
418
1551
963
,589
2347
14.55
15
NA
NA
NA
112
I4H
NA
145
275
174
199
441 ' 281)
244
046
. 403
2<.)9
894
sr.2
.363
11. S3
736
48!
1512
934
668
2299
1421
20
NA
NA
NA
NA
NA
NA
170
257
NA
230
420 - 267
285
622
38«t
.345
806
.543
415
11.50
70,3
544
1473
906
741
225!
1387.
.".0
NA
NA
NA
NA
NA
NA
NA
NA
NA
315
376 NA
373
573
NA
442
809
.502
.521
10,30
649
674
1399
848
892
2159
J. 318
KK)
NA
NA
NA
49
2H
NA
00
403
,KA
100
(KiO 3<.}5
131
991
'',.555
166
1401
7fri
207
19<t0
1033
273
2179
1300
395
.3912
2fM2
2
NA
NA
NA
51
192
NA'
70
351
NA
98
503 373
125
828
'.508
158
11,52
698
196
I5.'>2
933
259
1970
1168
.371
.302!
1817
5
NA
NA
-NA
67
180
NA
90
342
NA-
125
.551 366
1.50
813
£501
194
1134
688
240
1,511
921
322
1945
1153
4tHI
2990
1796
10
NA
NA
NA
85
175
NA
11.3
324
NA'
153
532 3.54
191
789
:486-
2.38
1104
672
2'.)3
1477
902
.389
1905
1533
.547
293S
1763'
15
NA
NA
NA
132
102
NA
138
310
• NA
188
511 343
230
764
;473
281
1075
65ft
342
1443
^4
447
1805
1110
618
2888
1730
20
NA
NA
NA
NA
NA
NA
108
295
NA
224
487 NA
270
7.39
4.58
323
1046
639
.391
1410
864
.507
1825
1087
690
2838
inm
SO
NA
NA
NA
NA
NA
NA
231
204
•KA
301
448 NA
3.55
685
. NA
418
988
NA
491
1.143
824
031
i747
104!
8.34
2739
1627
50
NA
NA
NA
N\
NA
NA
NA
iNA
NA
NA
NA NA
540
584
,NIA
617
806
NA
711
1205
NA
895
1591
HA
1138
2547
1489
For SI unite, 1 in. = 25.4 mm, I ft = O.mh m, 1000 Btii/hr = 0.293 kW, 1 in.^ = 64.5 mm-.
[NFPA 54 Table 13.1(b)}
72
WATER HEATERS
Table 5-10
Table 5-10 Masonry Chimney
Number of Appliaaces:
SingI
e
Appliance
Type:
Category I
Appliance Vent Cotuicction:
Typ« B Double-Wall Connector
Type B Double-WaU Comiector Diameter — D (in. )
■^ight Lateral
« i.
ft) (ft)
To be u-scd with chimney atcm within tite size limits at bottom
3
4
5
6
7
8
9
10
12
AppI
iance
Input Rating
in Thousands of Btu per
Hotir
H
FAN
NAT
FAN
MAT
Max
FAN
NAT
Max
FAN
HAT
Max
FAN NAT
FAN
NAT
Ikfax
FAN,
NAT
Max
FAN
NAT
Max
FAN
NAT
Min
Max
Min
Max
Miii
Max
Min
Max
Mill
Max Max
Min Max
Min
Max
Min
Max '
Min
Max
Max
6
a
NA
NA
, »
NA
NA
-,2
NA
NA
m
NA
NA
ISO
NA
NA lai'
NA NA
247
NA
NA
320
NA
NA
401
NA
N,\
.581
')
NA
NA
'3
NA
NA
41»
NA
NA
m
NA
NA
117
NA
NA |f.5
NA NA
231
NA
NA
298
NA
NA
376
NA
.N.\
.56!
8
2
NA
NA
29
NA
NA
' 55
NA
N.\
t)9
NA
NA
143
N'A
NA im
N.\ NA
•im
84
.590
350
100
728
44<>
1.39
1024
651
5
NA
NA
26
NA
NA
52
NA
NA
8R
NA
NA
i:i4
NA
NA 1S3
NA NA
247
NA
NA
328
140
711
423
201
1007
640
8
NA
NA
24
NA
NA
4H
NA
NA
as
NA
NA
127
NA
NA 175
NA NA
239
NA
NA
318
173
«i95
410
231
990
623
fO
'2
NA
NA
SI
NA
NA
m
NA
NA
H«
NA
NA
1<»2
NA
NA 221
(\S 5 to
2»«
82
653
38H
98
810
491-
136
1144
724
:,
NA
NA
as
NA
NA
Tu
NA
N\
<«->
NA
NA
14S
NA
NA a04
NA NA
277
12*
638
'Mih
146
791
4<i0
196
1124
712
10
NA
NA
*&
NA
NA
50
NA
NA
m
•NA
NA
1S9
NA
NA 191
NA NA
263
1.55
610
347
182
762
444
240
1093
668
15
2
NA
NA
»
NA
NA
m
NA
NA
114
NA
NA
17S»
.')3
475 2Bft
M M'.S
336
77
770
441
02
9t>8
,'562
127
1376
,841
3
NA
NA
sr.
NA
NA
62
NA
NA
H!"
NA
NA
l(>4
NA
NA 231
y» 5y-i
31,3
118
759
416
J 39
916 .
533
186
13.52
828
10
NA
NA
28
NA
NA
Tm
NA
NA
07
NA
NA
133
NA
NA I'lfi
12fi .5(>5
zm
148
727
394
173
912
.567
229
1315
777
i:.
NA
NA
.NA
NA
NA
4M
NA
NA
m
NA
NA
141
NA
NA 201
NA NA
281
171
6'J8
375
108
880
485
2.59
1280
742
20
2
NA
NA
m
NA
NA
74
NA
NA
124
NA
NA
S«l
:>i
.522 274
(il f.78
375
7,3
867
401
87
1083 ■
627
121
1548
9.53
.-J
NA
NA
36
NA
NA
• m
NA
NA
116
NA
NA
184
80
503 ,254
93 658
350
113
843
463
133
10.59
597
179
1523
933
iO
NA
NA
NA
NA
NA
60
NA
N.\
107
NA
NA
172
NA
NA 237
122 027
332
143
8U
440
167
1022
, .560
221
1482
• 879
15
NA
NA
■NA
NA
NA
NA
NA
NA
J1-
NA
NA
ir>9
NA
NA 220
NA NA
314
105
780
418
191
987
.541
25 1
1443
840
20
NA
NA
NA
NA
NA
NA
NA
NA
m
NA
NA
\m
NA
N.\ 206
NA NA
2«»
186
750
3517
214
955
513
277
1406
-807
30
2
NA
NA
41
NA
NA
82
NA
NA
!37
NA
NA
2ir»
47
581 ms
57 762
421
68
'085
558
81
1240
717
111
1793
1112
5
NA
NA
NA
NA
NA
76
NA
NA
15>S
NA
NA
im
75
561 281
<K( 741
:«■«
106
962
526
125
1216
683
169
1766
1094
iO
NA
NA
NA
NA
NA
67
NA
-NA
115
NA
NA
im
NA
NA 2Ba
1 15 701.1
a73
135
927
5<J0
158
1176
'6'18
210
1721
1025
15
NA
NA
N.\
NA
NA
NA
NA
NA
107
NA
NA
171
NA
NA 243
NA NA
353
156
893
47(i
181
11.39
621
239
1679
981
20
NA
NA
NA
NA
NA
NA
NA.
NA
yi
NA
NA
}r»3
"NA
NA 227
NA NA
332
176
860
450
203
1 103
,592
264
1638
940
30
NA
NA
NA
KA
NA
NA
NA
N\
NA
NA
NA
NA
NA
NA las
NA NA
3^
NA
NA
416
249
1035
553
318
ISW)
, 877
30
2
NA
NA
NA
NA
NA
92
NA
.NA
lisi
NA
NA
ZH
NA
NA ,3,51
51 SIO
477
01
1 100
633
72
1413
812
99
20.S0
12<13
,7
NA
NA
NA
NA
NA
NA
NA
NA
ir>t
NA
NA
230
NA
NA 323
83 819
445
as
1083
596
110
13H7
774
1.55
2052
JS25
10
NA
NA
NA
NA
NA
NA
NA
NA
138
NA
NA
at. 5
NA
NA :504
NA NA
424
126
1047
567
147
1347
733
195
20(M>
1147
15
NA
NA
NA
NA
NA
NA
NA
NA
127
NA
NA
IWJ
NA
NA 2S2
N.\ NA
WO
146
I0!0
539
170
1307
702
222
1961
1099
20
NA
NA
N.A
NA
•NA
NA.
NA
NA
NA
NA
NA
185
NA
NA 264
NA NA
376
165
977
511
190
1269
669
246
1916
1050
30
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA NA
NA NA
327
NA
NA
468
233
1 191)
623
295
1832
984
Minimum
12
ly
28
m
Mi
63
78
95
132
internal
area of
chimney
(in.^) '
Maximum
49
88
l;17
nw
2r.<)
332
445
5.'K)
792
internal
area of
chimnev
For SI units, 1 in. = 2.5.4 mm, 1 ft = Q3Q') m, 1000 Btu/Iir = 0.293 kW, 1 in.*^ = 645 mm^.
[NFPA 54 Table 13.1 (c)l
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
73
Table 5-1 1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-1 1 Masonry Chimney
Ninnber of Appliances:
SingI
e
Appliance Type:
Category I
Appliance
Vent Connection:
Single-Wall Metal Connector
Single-Wal
Metal Connector Diameter — 1> (in.)
ight Lateral
H L
To be used with chimney
areas tfithin the mx limits at bottom
3
4
5
6
7
8
9
10
12
Appliance Input Rating in TfaousancU of Btu per Hour
H<
(ft) <ft>
FAN
NAT
Max
PAN
NAT
Max-
FAN
NAT
FAM NAT
FAN NAT
FAN NAT
FAN NAT
FAN
NAT
FAN
NAT
Min
Max
Min
Max
Min
Max
Min
MaxJMax
Min
Max Mtat
Min
Max Max
Min
Max Max
Mm
Max
Max
Min
Max
Max
6
2
NA
NA
28
NA
NA
52
NA
NA
86
NA
NA ; 130
NA
NA 180
NA
NA 247
XA
NA 319
NA
NA
400
NA
NA
580
5
NA
NA
25
N,.\
NA
48
XA
NA
8i
NA
XA 116
NA
NA • 164
NA
NA ' 230
NA
NA 297
NA
XA
375
NA
NA
360
8
2
NA
NA
29
NA
NA
55
NA
NA
93
NA
NA , 145
NA
NA 1»7
NA
NA 263
NA
NA 349
382
725
, '445
349
1021
630
5
NA
NA
*»
NA
NA
5i
NA
NA
87
NA
\A ; 133
NA
NA , 182
NA
NA 246
NA
NA 327
NA
NA
•iTi
673
1(M)3
■638
8
NA
NA
23
NA
NA
47
NA
NA
«2
NA
NA • 126
NA
NA ; 174
NA
NA 237
XA
NA 317
NA
NA
408
747
985
621'
10
2
NA
NA
31
NA
NA
61
NA
NA
102
NA
XA 'i 16i
NA
NA 220
210
518 297
271
654 387
373
808
480
336
1142
722
5
NA
NA
28
NA
NA
56'
NA
NA
95
NA
NA \ 147
NA
NA 203
NA
NA 276
334
635 564
459
789
465
057
1121
710
10
NA
NA
24
NA
XA
4»
NA
NA
815
NA
NA : 1S7
NA
XA {8S
NA
NA 265
NA
NA • 343
347
758
441
771
1088
663
15
2
NA
NA
sr.
NA
XA
57
NA
NA
as
NA
\A 178
1(56
473 241)
211
611 333
264
776 44«»
362
965
bm
520
1373
840
5
NA
NA
32
NA
NA
61
NA
NA
lOfi
NA
XA - lf.3
NA
NA 230
261
591 312
325
755 414
444
942
531
637
1348
825
10
NA
XA
27
NA
NA
M
NA
NA
96
NA
XA . 151
NA
NA 214
NA
NA 294
392
722 392
531
907
304
749
1309
.774
15
NA
NA
NA
NA
XA
46
NA
NA
" m
NA
NA ■ 138
NA
NA 198
NA
NA 278
452
692 _ 372
606
873
481
841
1272
■738
a)
2
NA
XA
38
NA
XA
73
NA
NA
123
NA
NA M)
163
520 273
206
673 374
258
864 mi
232
1079
025
508
1541
930
5
NA
NA
35
NA
NA
67
NA
NA
-115
NA
XA . 183
NA
NA . 252
255
655 348
317
842 461
433
1055
594
623
1518
9»
10
NA
NA
NA
NA
NA
59
NA
NA
103
NA
NA 170
NA
NA 2S5
312
622 330
382
806 , 437
517
1016
562
733
1475
873
15
NA
XA
NA
NA
NA
NA
NA
NA
<)5
NA
NA ; 156
NA
NA , 217
NA
NA 311
442
773 , 414
391
979
539
823
1434
835
20
NA
NA
NA
NA
NA
NA
NA
NA
80
NA
XA ; 144
NA
NA 202
XA
NA 292
XA
XA 392
663
944
510
911
1394
800
30
2
NA
NA
41
NA
NA
SI
NA
NA
136
NA
NA '- 215
158
578 302
200
759 420
249
982 556
340
1237
715
489
178<)
1110
5
NA
NA
NA
NA
NA
75
NA
NA
127
NA
NA : 196
NA
NA - -m
245
737 391
3f)6
958 524
417
1210
680
600
1760
109(j(
10
\A
NA
NA
NA
NA
06
NA
NA
IIS
NA
NA - 182
NA
NA . 2<J0
300
703 37ft
370
920 496
500
1168
644
70S
1713
1020
15
NA
NA
NA
NA
NA
NA
NA
NA
105
NA
NA ■ 168
NA
NA 240
NA
NA 349
428
884 , 471
572
1128
. 615
798
1668
•975
%)
NA
NA
NA
NA
NA
NA
NA
NA
m
NA
NA ! 153
NA
XA 223
NA
NA ■ 327
NA
NA 445
643
1089
385
883
1624
932
SO
NA
NA
NA
NA
NA
NA
NA
NA
XA
NA
XA ► NA
NA
NA l«2
NA
NA ; 281
NA
NA 408
NA
XA
544
1055
1539
885
50
2
NA
NA
NA
NA
NA
m
NA
NA
HiO
NA
NA 250
NA
NA S50
191
837 4"5
238
1103 631
323
1408
810
463
207(1
1240
5
NA
NA
NA
NA
NA
NA
XA
NA
149
NA
NA < 228
NA
NA 321
NA
NA 442
293
1078 593
398
1381
770
571
2044
1220
10
NA
NA
NA
NA
XA
NA
XA
NA
136
NA
NA 212
NA
NA 301
NA
NA ■ 420
355
1038 562
447
1337
728
674
1994
1140
15
NA
NA
NA
NA
NA
NA
NA
NA
124
NA
NA ' 195
NA
NA 278
XA
NA 393
NA
NA 333
546
1294
695
761
1945
1090
20
NA
NA
NA
NA
XA
NA
NA
NA
NA
NA
NA . 180
NA
NA 25«
NA
NA 370
NA
NA 5ft4
616
1251
660
844
1898
1040
;!0
NA
NA
NA
NA
XA
Sa
NA
NA
NA
NA
NA NA
NA
NA ■ NA
NA
NA 318
NA
NA 458
NA
NA
610
1009
1805
970
Minimum
12
19
28
38 '
50
63
7«
93
132
internal are'A
of chimney
,^
Maximiim
49
m
137
I9S
269 ,
352
445
350
792
internal area
of chimney
For SI units, 1 in. = 25.4 mm, 1 ft = 0..«505 m, 1000 Btu/hr = 0.293 kW, 1 in.'^ = 645 mm^.
[NFPA 54 Table 13.1(d)]
74
WATER HEATERS
Table 5-12
Table 5-12 Single-Wall Metal Pipe or Type B Asbestos Cement Vent
Number of Appliances:
Single
Appliance Type:
Draft Hood-Equipped
Appliance Vent Connection:
Connected Directly to Pipe or Vent
Diameter - U (in. )
lateral
L
(ft)
To be used witfi chimney areas ttitfain the size limits at bottom
3
4
5
6
7
8
10
12
Height
H
(ft)
Appliance Input Rating in Thousands of Btu per Hour
Maximum i^pliance Input Rating in Thousands of Btu per Hour
6
39
70
116
170
232
312
500
750
2
31
55
94
Ml
194
260
415
620
5
28
51
88
128
177
242
390
600
8
4.2
76
126
185
252
340
542
815
2
32
61
102
154
210
284
451
680
5
29
56
95
141
194
264
4$()
<>48
10
24
49
86
131
180
250
406
625
10
45
84
138
202
279
372
606
912
2
3a
67
HI
168
233
311
505
7()0
5
32
61
104
153
215
289
.480
724
10
27
54
94
143
200
274
455
700
15
NA
46
84
130
186
258
432
666
15
49
91
151
223
312
420
684
1040
2
39
72
122
186
260
350
570
865
5
35
67
110
170
240
325
540
825
10
30
58
105
158
223
308
514
795
15
NA
50
93
144
207
291
488
760
20
NA
NA
82
132
195
273
466
726
20
53
101
163
252
342
470
770
11<W
2
42
80
136
210
286
392
641
990
5
38
74
123
192
264
364
610
945
10
32
65
115
178
246
345
571
910
13
NA
55
104
163
228
326
550
870
20
NA
NA
91
149
214
306
525
832
30
56
108
183
276
384
529
878
1370
2
44
84
148
230
320
441
730
1140
5
NA
78
137
210
296
410
694
1080
10
NA
68
125
196
274
388
656
1050
15
NA
NA
113
177
258
366
625
1000
20
NA
NA
99
163
240
34.4
596
960
30
NA
NA
NA
NA
192
295
540
890
50
NA.
120
210
310
443
590
980
1550
2
NA
95
171
260
370
492
820
1290
5
■ NA
.NA
159
234
342
474
780
1230
10
NA
NA
146
221
318
456
730
1190
15
NA
NA
NA
200
292
407
705
1130
20
NA
NA
NA
185
276
384
670
1080
30
NA
NA
NA
NA
222
330
605
1010
For SI units, 1 in. = 25.4 mm, 1 ft
[NFPA 54 Table 13.1(e)]
■■ O..S05 m, 1000 Btu/hr = 0.293 \\\', 1 in.'' = 645 mm-.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
75
Table 5-13
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-13 Exterior Masonry Chimney
Number of Appliances:
Appliance Type:
Appliance Vent Connection:
Single
Type B Double-Wall Connector
SPECIAI. USE: Minimiun ^Utowable Input Rating
of Space-Heating Appliance in
11iODsan(k of Btu per Hour
Vent Height
H
(ft)
Internal Area of Chimney (in.'')
12
19
28
38
50
63
78
113
Local 99% winter design temperaCttre: 37°1*
or greater
6
8
iO
15
NA
20
NA
NA
123
190
249
184
30
NA
NA
NA
NA
NA
393
334
50
NA
NA
NA
NA
NA
NA
NA
579
I
.«x-al 99%
winter design
teniperaune: 27°F to 36°F
6
68
116
156
180
212
266
8
82
127
167
187
214
263
iO
51
9*7
141
183
201
225
265
15
NA
NA
NA
NA
233
253
274
305
20
NA
NA
NA
NA
NA
307
330
362
30
NA
NA
NA
NA
NA
419
445
485
50
NA
NA
NA
NA
NA
NA
xNA
765
1
.ocal 99%
winter design teinperaiure; 17
F to 26^
6
NA
NA
NA
NA
NA
215
259
349
8
NA
NA
NA
NA
J97
226
264
352
10
NA
NA
NA
NA
214
245
278
358
15
NA
NA
NA
NA
NA
296
331
398
20
NA
NA
NA
NA
NA
352
387
457
30
NA
NA
NA
NA
NA
NA
507
581
50
NA
NA
NA
NA
NA
NA
NA
NA
Local 99%
winter desigr
temperature: a"
Ftol6°F
6
NA
NA,
NA
NA
NA
NA
NA
416
8
NA
NA
NA
NA
NA
NA
312
423
10
NA
NA
NA
NA
NA
289
331
430
15
NA
NA
NA
NA
NA
NA
393
485
20
NA
NA
NA
NA
NA
NA
450
547
30
NA
NA
NA
NA
NA
NA
NA
682
50
NA
NA,
NA
NA
NA
NA
NA
972
Local 99%
winter design
tempeiature: -10"F to 4"F
6
NA
NA
NA
NA
NA
NA,
NA
484
8
NA
NA
NA
NA
NA
NA
NA
494
10
NA
NA
NA
NA
NA
NA
NA
513
15
NA
NA
NA
NA
NA
NA
NA
586
20
NA
NA
NA
NA
NA
NA
NA'
650
30
NA
NA
NA
NA
NA
NA
NA
805
50
NA
NA
NA
NA
NA
NA
NA
1003
lx>cal 99% wnter design temperature: -1 1
°F or low
ex
Not rccommcjided foi
any vent configi
rations
Ft:>r SI units, 1 in. - 25.4 mm, 1 in." - 645 mm^ 1 ii = 0.305 m, 1000 Bin per hr = 0.293 kVV, "C - ("F - 32)/l .8.
Note: Stie Figure G.2.4 for a map .showing local 99 percent winter design temperatiire.s in the United States.
[NFPA 54 Table 13.1(f)]
76
WATER HEATERS
Table 5-14
Table 5-14 Type B Bouble-WaU Vent
Number of Appliances:
Two or More
Appliance Type:
Category I
Appliance Vent Connection:
Type B Doublc-WaJl Connector
Vent Connector Capacity
Type
B Doirbie-Wall Vent and Connector Diameter —
DCui.)
3
4
5
6
7
8
9
10
Vent
Appliance Inpvtt Rating
Limits in Thousands of Btu per Hour
Height
»
(ft)
Rise
R
(ft)
FAN NAT
FAN
NTAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN NAT
FAN
NAT
FAN
NAT
Min
Max Max
Min
Max
Min
Max
Min
Max
Min
\tax
Min
Max Max
Min
Max
Max Min
Max
Max
6
1
22
37 2fi
35
66
46
46
106
72
58
Kvl
104
77
225
■142
92
296 183
im^
376
237
!28
466
' 289
2 ,
23
41 31
37
75
53
48
121
86
60
183
124
79
253
•168
95
333 220
112
424
282
131
526
345
3
24
44 35
38
81
62
49
132
96
62
199
139
82
275
189
97
363 • 248
114
463
317
134
575
386
8
1
22
40 27
35
72
48
49
114
76
64
176
109
84
243
148
100
320 194
118
408
'248
138
507
303
2
23
44 ,32
36
80
57
51
128
90
66
195
129
86
269
175
103
356 230
121
454
294
141
564
858
3
24
47 3fi
37
87
M
53
139
101
67
210
145
88
290
19H
105
384 258
123
492
330
143
612
402
10
1
22
43 28
34
78
50
49
123
78
65
189
113
89
257
154
106
341 200
125
436
257
146
542
314
2
23
47 33
36
86
m
51
136
93
67
2(K>
134
91
282
182
109
374 238
128
179
305
149
596
•372
3
24
50 37
37
92
m
52
146
104
69
220
150
94
303
205
111
402 268
131
515
342
152
fi-12
417
15
1
21
50 ■ 30
33
89
53
47
142
83
64
220
120
88
298
163
110
389 214
134
493
273
162
609
333
2
22
53 35
35
96
63
49
153
99
66
235
142
91
320
193
112
419 253
137
532
323
165
658
394
3
24
55 40
36
102
71
51
163
111
68
248
160
93
339
218
115
445 286
140
565
• 365
167
700
444
20
1
21
54 3J
33
99
56
46
157
87
62
24f)
125
86
334
171
107
430 224
131
552
285
158
681
347
2
22
57 37
34
105
m
48
167
104
64
259
149
89
354
202
110
463 265
134
:587
3S9
161
725
414
3
23
60 42
35
110
74
50
176
116
66
271
168
91
371
228
113
486 300
137
618
383
164
761
466
30
1
20
62 33
31
113
59
45
181
93
60
288
134
83
391
182
103
512 238
125
(H9
305
151
802
372
2
21
64 39
33
118
70
47
190
110
62
299
158
85
408
215
105
535 282
129
679
360
155
810
439
3
22
66 44
34
123
79
48
198
124
64
309
178
88
423
242
108
553 817
132
706
405
158
874
494
50
I
19
71 36
30
133
61
43
216
101
57
349
145
78
477
197
97
627 257
120
797
330
144
981
403
2
21
73 43
32
137
76
45
223
U9
59
358
172
81
490
234
100
645 306
123
820
392'
148
1014
478
3
22
75 48
33
141
86
46
229
134
61
366
194
83
502
263
103
061 343
126
842
441
151
1043
538
100
1
18
ii2 37
28
158
66
40
262
104
53
442
150
73
611
204
91
810 266
112
1038
341
135
1285
■417
2
19
83 . 44
30
161
79
42
267
123
55
447
178
75
619
242
94
822 316
115
1054
405
139
1306
•494
3
20
84 , 50
31
163
■ 89
44
272
138
57
452
200
78
627
272
97
834 355
118
1069
455
142
1327
555
Common Vent Capacity
Type B Double-Wall Common Vent Diameter — » (in.)
4
5
6
7
8
9
10
Vent
Height
H
Combined Apptianc
e Input Rating in Thoiiisands of Btu per Hon
FAN
FAN
NAT
FAN
FAN
NAT
FAN FAN NAT
FAN FAN NAT
FAN FAN
NAT
FAN
FAN
• NAT
FAN
FAN
NAT
(ft)
+FAN
+NAT +NAT
+FAN +NAT
+NAT
+FAN +NAT +NAT
+FAN +NAT +NAT
+FAN +NAT
+NAT
+FAN +NAT +NAT
•fFAN
+NAT
*NAT
6
92
81
05
140
116
103
204 161 147
309 248 200
404 314
2611
547
434
335
672
520
410
8
101
, 90
73
155
129
114
224 178 163
339 275 223
444 348
2911
602
480
378
740
. 577
465
10
110
97
79
169
141
121
243 194 178
367 299, 242
477 377
315
649
522
405
800
627
rr,
15
125
112
91
195
164
1 14
283 228 206
427 352 2«0
556 444
3'i5
753
612
465
924
733
565 ,;
20
136
123
1112
215
183
Kill
314 255 229
475 394 310
621 499
11 15
842
088
523
1035
826
;640
30
152
138
118
244
210
185
361 297 266
547 459 360
720 585
170
979
808
605
1209
975
■7.10 ■
50
167
153
134
279
244
211
421 363 310
641 547 423
854 706
551)
ilM
977
705
1451
1188
.860 \
100
175
163
NA
311
277
\\
189 421 NA
751 658 479
1025 873
(I'J'i
1408
1215
800
1784
1502
975 1
[NFPA 54 Table 1 3.2(a) 1
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
77
Table 5-14 continued
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-14 Continued
Number of Appliances:
Two or More
Appliance
T>pe:
Category I
AppUance Vent Connection:
Type
B Double-Wall Connector
T>T>e
B Double-WaU Vent and Connector Diameter — D (in.)
12
14
16
18
20
22
24
Vent
Appliance Input Rating Limits in Thousands of Btu per Hour
Height
H
m
Rise
R
(ft)
FAN NAT
FAN NAT
FAN NAT
FAN NAT.
FAN
NAT
Max
FAN 'NAT
FAN
NAT
Min
Max Max
Min
Max - Max
Min
Max Max
Min Max Max
Min
Max
Min
Max iMax
Min
Max
Max
6
2
174
764 496
223
1046 ; 653
281
1371 853
346 1772 1080
NA
NA NA
NA
NA NA
NA
NA
NA
4
180
897 616
230
1231 827
287
1617 1081
352 2069 1370
NA
NA NA
NA
NA NA
NA
NA
NA
6
NA
NA NA
NA
NA NA
NA
NA NA
NA NA ISIA.
NA
NA NA
NA
NA NA
NA
NA
NA
8
9
18(5
822 316
238
1126 696
298
1478- 910
365 1920 1150
NA
NA NA
NA
NA NA
NA
NA
NA
4
192
932 644
244
1307 884
305
1719 1150
372 2211 1460
471
2737 1800
560
3319 2180
662
.3937
2590
6
198
1050 772
252
1445 1072
313
1902 1390
380 2434 1770
478
3018 2180
5t)8
3665 2640
669
4373
3130
10
2 .
196
870 ■ 536
249
1195 730
311
1570 955
379 2049 1205'
NA
NA NA
NA
NA NA
NA
NA
NA
4
201
997 664
256
1371 924
318
1804 ,1205
387 2332 1535
486
2887 , 1890
581
3502 2280
686
4175
2710
6
207
10<)5 792
263
1509 1U8
325
1989 1455
395 2556 1865
494
3169 2290
589
3849 2760
694
4503
3270
15
2
214
967 368
272
1334 790
336
1760 lOSO
408 2317 1305'
NA
NA . NA
NA
NA ' NA
NA
NA
■NA
4
221
1085 , 712
279
14TO,1006
344
1978 1320
416 2579 1665
523
3197 ;2060
624
3881 2490
734
4631
2960
6
228
1181 856
286
1632 ■ 1222
351
2157 1610
424 2796 2025
533
3470 2310
634
4216 ;30S0
743
5033
3600
20
2
223
1051 396
291
1443 840
357
1911 1095
430 2533 1385
NA
NA NA
NA
NA • NA
NA
NA
NA
4
230
1 162 748
298
1597 1064
366
2116 1393
438 2778 . I765r
554
3447 2180
661
4190 -2630
772
5005
3130
6
237
1253 900
307
1726 1288
373
2287 1695
450 2984 2145:-
567
8708 ,2650
671
4511 ,3190
785
5392
3790
30
2
216
1217 632
286
1664 910
367
2183,1190
461 2891 1540
NA
NA ■ NA
NA
NA ~ NA
NA
NA
NA
4
223
131ti 792
294
1802 1160
376
2366' 1510
474 3110 \WS
619
3840 2365
728
4861 2860
847
5606
3410
6
231
1400 952
303
1920 1410
384
2524 1830
485 3299 2340
632
4080 1 2875
741
4976 '3480
860
5961
4150
50
2
206
1479 689
273
2023 1007
350
2639,1315
435 3548 1665'
NA
NA. NA
NA
NA NA
NA
NA
•' NA
4
213
1561 . 860
281
2139 1291
359
2814 1685
447 3730 2135
580
4601 26-33
709
5569 3183
851
6633
3790
6
221
1631 1031
290
2242 1375
369
2951 20S5
461 3893 26()5<
594
4808.3208-
724
3826 3885
867
6943
4620
100
2
192
1923 712
254
2644 1050
326
3490 ,1370
402 4707 1740:
NA
NA NA
NA
NA NA
NA
NA
NA
4
200
1984 888
263
2731 ,1346
336
3606 .1760
414 4842 2220
523
5982 2750
639
7254 3330
769
8630
3950
6
208
2035 1064
272
2811 1642
346
3714 ;2150
426 4968 2700,
539
6143 3350
654
7453 4070
786
8892
4810
Common Vent Capacity
Type B Double-Wall Common Vent Diameter — D
(in.)
12
14
16
18
20
22
24
Vent
Combined Appliance Input Rating in Thousands of Btu
per Ho
ur
H
FAN
FAN 'NAT
FAN
FAN
:NAT
FAN
FAN NAT
FAN
FAN NAT
FAN FAN
NAT
FAN
FAN NAT
FAN
FAN
NAT
(ft)
fFAN
+NAT +NAT
+FAN +NAT
'>NAT
+FAN +NAT +NAT
+FAN
-►NAT +NAT
+FAN +NAT
+NAT
+FAN
+NAT +NAT
+FAN
+NAT
+NAT
6
900
696 588
1284
990
■ 815
1735
1336 1063
2253
1732 1345
2838 2180 ,
1660
3488
2677 1970
4206
3226
2S')1)
8
994
773 652
1423
1 103
: 912
1927
1491 1190
2507
1936 1510
3162 2439 '
I860
3890
2998 . 2200
4695
3616
2().S0
10
1076
841 - 712
1542
1200
' 995
2093
1625 ■ 1300
2727
2113 1645
3444 2665
2030
4241
3278 2400
5123
3957
2920
15
1247
986 825
1794
1410
11S8
2440
1910 .1510
3184
2484 1910
4026 3133
2360
4971
3862 , 2790
6016
4670
3100
20
1405
1116 916
2006
158S
1290
2722
2147 1690
3561
2798 2140
4548 3352
2640
5373
4352 i 3120
6749
5261
•WIM)
30
1658
1327 1025
2373
1892
1523
3220
2558 1990
4197
3326 ' 2320
5303 4193
3110
*>539
5157 , 3680
7940
6247
14W)
30
2024
1640 ■ 1280
2911
2347
, 1863
3964
3183 2430
3184
4149 307S
6367 5240
S800
8116
6458 : 4500
9837
7813
-|175
100
2569
2131 , 1870
3732
3076
2450
5125
4202 3200
6749
550<» 4050
8597 ()980
5000
10,681
8648 ■ 5920
13,004
10,49<)
7200
For SI units, 1 in. = 25.4 mm, 1 in.^' = 64,5 mni'-, 1 ft = 0.30.5 m, 1000 Bin per hr = 0.293 kW.
[NFPA 54 Table 13.2(a)]
78
WATER HEATERS
Table 5-15
Table 545 Type B Double-WaU Vent
Niimber of Appliances:
Two or Moi-e
Appliance Type:
Category I
Appliance Vent Cotmection:
Sin^c-Wall Metal Connector
Vent Connector Capacity
Single-Wall Metal Vent Connector Diameter
— jD(in.)
3
4
5
6
7
8
9
10
Vent
Appliance Input Rating
limits! in Thousands of Btu per Hour
Height
H
(ft)
Rise
R
(ft)
FAN
NAT
Max
fan'
NAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN
NtAT
Max
FAN NAT
Min
Max
Min
Max
Min
Max
Min
Max
Mui
Max
Min
Max
Min
Max
Min
Max Max
6
1
NA
NA
26
NA
NA
46
NA
NA
, 71
NA
NA
102
207
223
140
262
293
183
325
373
2S4
447
463 ' 286
2
NA
NA
31
NA
NA
,55
NA
NA
85
168
182
123
215
251
167
271
331
219
334
422
281
458
524 -344
3
NA
NA
34
NA
NA
62
121
131
95
175
198
138
222
273
188
279
361
247
344
462
316
468
574 r 385
8
1
NA
NA
•27
NA
NA
48
NA
NA
76
NA
NA
106
226
240
145
285
316
191
352
403
244
481
502 299-
2
NA
NA
32
NA
NA
57
125
126
89
184
193
127
234
266
173
293
353
228
360
450
292
492
560 , 355
3
NA
NA
■35
NA
NA
64
130
138
100
191
208
144
241
287
197
302
381
256
370
489
328
501
609 400
10
1
NA
NA
28
NA
NA
50
119
121
77
182
186
HO
240
253
150
302
335
196
372
129
252
506
534 ; 308
2
NA
NA
33
84
85
53
124
134
91
189
203
132
248
278
183
311
369
23S
381
473
302
517
589 \ 368
3
NA
NA
36
89-
91
■67
120
144
102
197
217
148
257
299
203
320
398
265
391
511
S^
528
637 ; ^13'
13
I
NA
NA
29
79
87
■82
116
138
81
177
214
1)6
238
291
158
312
380
208
397
482
266
556
596 ' 324
2
NA
NA
34
83
94
62
12!
150
97
185
230
138
246
314
\m
321
411
248
407
522
317
568
646 , 387'
3
NA
NA
39
B7
KK)
70
127
160
109
193
243
157
255
333
215
331
438
281
418
557
360
579
690 ■ 437-
20
1
49
56
30
78
97
54
115
152
84
175
238
120
233
325
165
306
425
217
390
538
'276
546
664 I 336
2
52
59
36
82
103
64
120
163
101
182
252
144
243
346
197
317
453
259
400
574
331
558
709 \ 403
3
55
62
40
87
107
72
125
172
US
190
264
164
252
363
22S
326
476
294
412
607
375
570
750 ; 457
30
1
47
60
31
77
110
57
112
175
89
109
278
129
226
380
175
296
497
230
378
630
2«4
528
779 : 358
2
51
62
37
81
115
67
117
185
106
177
290
152
236
397
208
307
521
274
389
662
349
541
819 ,"425-
3
54
64
42
85
119
76
122
193
120
185
300
172
244
412
235
316
512
309
400
690
394
555
855 j 482"
50
1
46
m
34
75
128
60
109
207
m
162
336
137
217
460
188
284
604
245
364
768
314
507
951 ; 384
2
49
71
40
79
132
72
114
215
1J3
170
345
164
226
473
223
294
023
293
370
793
376
520
983 458
3
52
72
45
83
136
82
119
221
123
178
353
186
235
486
252
304
640
331
387
816
423
535
1013 ; 5!8.
100
1
45
79
34
71
150
61
10-t
249
98
153
424
140
205
585
192
269
774
249
345
993
321
476 1236 ^. 393'
2
48
80
41
75
153
73
110
255
115
m)
428
167
212
593
228
279
788
299
358
1011
383
490 1259 ' 469
3
51
81
46
79
157
■ 85
114
260
129
168
433
190
222
603
256
289
801
SS9
368
1027
431
506 1280 -; 527
Common Vent Capacity
Type B Double-Wall Vent Diameter
-D(in.)
4
5 ■
6
7
S
9
10
Vent
Height
H
C
ombined Appl
ance Input Rating in Thousan
dsof Btnper
Hour
FAN
FAN
NAT
FAN
FAN
NAT
FAN FAN
NAT
FAN FAN NAT
FAN FAN
NAT
FAN
FAN
HAT
FAN
FAN
NAT.
(ft)
+FAN
+NAT
4-NAT
♦•FAN
+NAT
+\AT
+FAN +NAT
+NAT
+FAN+NAT +NAT
fFAN +NAT
+NAT
i-FAN
+NAT
■+NAT
i-FAN +NAT
+NAT
6
NA
78
64
NA
113
'19
200 158
144
304 244 196
398 310
257
541
429
332
665
515
407
8
NA
87
71
NA
126
III
218 173
159
331 269 218
436 312
■ 285
592
473
373
730
569
■460
10
NA
94
76
163
. 137
IJO
237 189
174
357 292 . 236
467 369
309
638
512
, 398
787
617
, 487
15
121
108 :
m
189
159
no
275 221
200
416 313 -274
544 134
357
738
59<)
456
905
718
553
20
131
118
■ 98
208
177
|-.t)
305 247
223
463 383 302
606 487
- 395
824
673
512
1013
808
626
30
145
132
US
236
202
ISO
350 286
257
533 446 ■ 349
703 570
459
958
790
593-
1183
952
723
50
159
145
128
268
233
2(iN
40(> 337
296
622 529 410
833 ()86
535
1139
954
689
1418
1157
838
100
166
153
NA
297
263
NA
469 398
NA
726 633 464
99«) 846
606
1378
1185
780
1741
1459
948
[NFPA 54 Table 13.2(1))]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
79
Table 5-16
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-16 Masonry Chimney
Number of Appliances:
Two or More
Appliance Type:
Category I
Appliance Vent Connection:
Type B Double-Wall Connector
Vent Connector Capacity
Type B Double-Wall Vent Connector Diameter
_D
in.)
3
4
5
6
1
8
9
10
Vent
Appliance Input Rating limits
in Thousands of Btu pet
Houi
Height
H
(ft)
Rise
R
(ft)
FAN
NAT
Max
FAN
NAT
Max
FAN NAT
FAN NAT
FAN
NAT
MaK
FAN
NAT
Max
FAN
NAT
Max
FAN NAT
Min
Max
Min
Max
Min
Max Max
Min
Max Max
Min
Max
Min
Max
Min
Max
Min
Max Max
6
1
24
33
2J
39
62
40
52
106 67
65
194 101
87
274
141
104
370
201
124
479
253
145
599 319
2
26
43
28
41
79
52
53
133 85
67
230 124
89
324
173
i07
436
232
127
562
3«»
148
694 378
3
27
49
34
42
92
61
55
155 97
69
262 143
91.
369
203
109
491
270
129
633
349
151
795 439
8
1
24
3<»
22
39
"2
41
55
117 69
71
213 , 105
94
304
148
113
414
210
134
539
267
156
682 ■ 335
2
26
47
. 29
40
87
•53
57
140 86
73
246 127
97
350
179
116
473
240
137
615
311
160
776 ' 394
3
27
52
34
42
97
62
59
159 98
75
269 145
99
383
206
119
517
276
139
672
358
163
848 452
10
!
24
42
22
38
80
42
55
130 - 71
74
232 108
101
324
153
120
44 4
216
142
582
277
165
739 348
2
26
50
29
40
93
34
57
153 87
76
261 129
103
366
184
123
498
247
145
652
321
168
825 407
3
27
55
35
41
105
63
58
170 100
78
284 148
106
397
209
126
510
281
147
705
366
171
893 463
15
1
24
48
23
38
93
44
54
154 74
72
277 1 14
100
384
164
125
511
229
153
658
297
IS-l
824 ' 375
2
25
55
31
39
105
55
56
174 89
74
299 134
103
419
192
128
558
260
156
718
339
187
900 432
3
26
59
■35
41
115
64
57
189 102
76
319 153
JOS
448
215
131
597
292
159
7(i0
382
M)
9(>0 486
20
1
• 24
52
24
37
102
46
53
172 77
71
313 119
98
437
173
123
584
239
150
752
312
180
943 397
2
25
58
31
39
114
56
55
190 91
73
335 138
101
407
199
126
(525
270
153
805
354
184
1011 452
■ 3
26
63
35
40
123
65
57
204 104
75
353 157
104
493
222
129
661
301
156
851
396
187
1067 505
30
1 •
24
54
26
37
11!
48
52
192" 82
69
357 • 127
96
504
187
119
680
255
145
883
337
175
1115 432
2
25
60
32
38
122
58
54
208 95
72
376 145
99
531
209
122
715
mi
149
928
378
179
1171 484
3
26
O'l
36
40
131
66
56
221 107
74
392 ; 163
101
554
233
125
746
sn
152
968
418
182
1220 535
50
1
23
51
25
36
116
51
51
209 89
67
405 • 143
92
582
213
115
798
294
140
1019
392
168
1334 506
2
24
59
32
37
127
, 61
53
225 !02
70
421 161
95
604
235
118
827
326
143
1085
433
172
1379 558
3
26
6-1
36
39
135
69
55
237 115
72
435 180
98
624
260
121
854
357
147
1118
474
176
1121 611
100
1
23
46
24
35
108
50
49
208 - 92
65
428 : 155
88
040
237
109
907
334
13^1
1222
454
161
1589 596
2
24
53
31
37
120
60
51
224 105
67
444 ' 174
92
mo
260
113
933
368
138
1253
497
165
1620 651
3
25
5<t
35
38
130
68
53
237 118
69
458 193
94
679
285
116
95r)
399
141
1282
540
169
1661 705
Common Vent Capacity
Minimum Internal Area of Masonry Chlnuiey Flue (in.^)
12
19
28
38
50
65
78
113
Vent
Combined Appliance Input Rating in Thousands of Btu per Hour
H
FAN
FAN
NAT
FAN
FAN
NAT
FAN
FAN NAT
FAN
FAN NAT
FAN FAN NAT
FAN FAN
NAT
FAN
FAN NAT
FAN
FAN
NAT
(ft)
hFAN-
hNATH
NAT
(•FAN-t
NATh
-NAT
hFANh
►NAT+NAT
i-FAN+NAT+NAT
i-FAN+NAT+NAT
hFAN+NATn
-NAT
i-FANh
-NAT+NAT
^-FAN
fFAN
+NAT
6
NA
74
25
NA
119
46
NA
178 , 71
NA
257 103
NA 351 ; 143
NA 458
188
NA
582 246
1041
853
W
8
NA
80
28
\A
130
53
NA
!93 82
NA
279 1 19
NA 384 • 163
NA 501
218
724
636 278
1144
937
Jos
10
NA
84
SI
NA
138
56'
NA
207 90
NA
299 131
NA 409 : 177
()06 538
236
776
686 . 302
1226
1010
151
15
NA
N'A
36
NA
152
67-
NA
233 ' 106
NA
334 152
523 467 J 212
682 611
283
874
781 ■ 365
1374
1156
1 16
20
NA
NA
41
\A
NA
75
NA
250 122
NA
368 . 172
565 508 •• 2^3
742 668
325
955
858 419
1513
1286
(>1H
30
NA
NA
NA
NA
NA
NA-
NA
270 137
NA
404 198
615 564 1 278
816 747
381
1062
969 496
1702
1473
719
50
NA
NA
NA
NA
NA
NA
NA
NA NA
NA
NA NA
NA 620 ; .328
879 831
46!
1165
1089 606
1905
1692
922
100
NA
NA
SA
NA
NA
NA
NA
NA. NA
NA
NA NA
NA NA; 348
NA NA
4m
NA
NA ,, 669
2053
1921
l()-)8
[NFPA 54 Table 13.2(c)]
80
WATER HEATERS
Table 5-17
Table 5-17 Masonry Chimney
Number of Appliances:
Two or More
Appliance Type:
Category- 1
Appliance Vent Conneclion:
Single-Wall Metal Conocdor
Vent Connector Capacity
Connector
Riiie
R
m
Single-Wall Metal Vent Connector Diameter -
-0(in.)
3
■ 4,
5
6
7
8
9
10
Vent
Height
H
(ft)
Appliance In
put Rating limits in Thousands of Btu per Hojir
FAN
NAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN
NAT
Max
FAN NAT
FAN
NAT
Mas
FAN
NAT
FAN
NAT
mn
Mas
Min
Max
Mjn
Max
Min
Max
Min
Max Max
Mm
Max
Min
Mas
Max
Min
Max
Max
6
1
NA
NA
21
NA
NA
S9
NA
NA
66
179
191
100
231
271 140
292
300
200
362
474
252
4:99
694
310
2 ■
NA
NA
28
NA
NA
52
NA
NA
84
186
227
123
239
321 172
301
432
231
373
557
299
509
696
376
3
NA
\A
34
NA
NA
61
134
153
97
193
258
142
247
3(i5 2<12
309
491
269
381
634
348
519
793
437
8
1
NA
NA
21
NA
NA
40
NA
NA
68
195
208
103
250
298 146
313
407
207
387
530
203
529
672
331
2
NA
NA
28
NA
NA
52
137
139
85
202
240
125
258
343 177
323
46r>
238
397
()07
309
54.0
766
391
S
NA
NA
S-1
NA
NA
02
143
156
98
210
264
145
266
376 205
332
509
274
407
663
356
551
838
450
10
1
NA
NA
22
NA
NA
41
130
151
70
202
225
106
267
316 151
333
434
213
41.0
571
27S
558
727
343
2
NA
\A
n
NA
NA
53
136
150
86
210
255
128
276
358 181
343
489
244
420
640
317
569
813
-103
3
NA
NA
34
97
102
62
143
166
99
217
277
147
284
389 207,
352
530
279
430
69!
363
580
880
459
15
1
NA
NA
23
NA
NA
43
129
151
73
199
271
112
268
376 16!
349
502
225
445
646
291
623
808
366
2
NA
NA
30
92
103
54
135
170
m
207
295
132
277
411 189
359
518
256
456
706
334
634
884
42'1
3
NA
NA
:«
96
112
63
141
185
101
215
315
151
286
439 213
368
58(i
289
4.66
755
:'.78
646
945
479
20
1
NA
NA
23
87
99
45
128
167
, 76
197
303
ii?
265
425 169
345
569
235
439
734
806
014
921
387
9
NA
NA
SO
91
tti
55
134
185
90
205
325
136
274
455 195
355
610
266
450
787
318
627
986
443
3
NA
NA
35
96
119
64
140
199
103
213
343
154
282
481 219
365
644
298
461
831
391
639
1042
496
30
1
NA
NA
24
8<5
108
47
126
187
80
193
347
124
259
492 ' 183
338
665
250
430
864
330
600
1089
42!
2
NA
NA
31
91
119
57
132
203
93
201
366
142
269
518 205
348
699
282
442
908
372
613
1145
473
3
NA
NA
33
95
127
6r.
138
216
105
209
381
160
277
510 229
358
729
312
4.59
916
412
626
1193
524
50
1
NA
NA
24
85
113
50
124
204
87
188
392
139
252
567 ■ 208
328
778
287
417
1022
383
582
1302
492
2
NA
NA
31
89
123
60
130
218
IW
196
408
158
2()2
588 2S«t
339
806
320
429
1058
425
596
1346
545
3
NA
NA
35
94
131
68
136
231
112
205
422
176
271
607 265
349
831
351
4.40
10<)0
- 466
610
1386
597
U«>
1
NA
NA
23
84
104
49
122
200
89
182
410
151
243
617 232
315
875
328
402
1181
444
560
1537
580
2
NA
NA
30
88
115
59
127
215
102
190
425
169
253
630 254
326
809
961
415
1210
488
575
1570
634
3
NA.
NA
34
93
124
67
133
228
115
199
438
188
262
654 279
337
921
392
427
1238
529
589
1604
687
Common Vent Capacity
Mimmnm Internal Area of Masonry Chimney Flue (in
.')
12
19
28
38
50
63
78
1J3
Vent
Height
H
m
Combined Appliance Input Rating in llioitsands of Btu pt
r Hour
FvUSf FAN
hFAN+NAT
NAT
t-NAT
FAN FAN NAT
i-FAN+NAT+NAT
FAN
^FAN^
F/VN NAT
■NAT+NAT
FAN FAN NAT
hFAN+NAT+NAT
FAN FAN NAT
i-FAN+NAT+NAT
FAN FAN NAT
kFAN+NAT+NAT
FAN
^FAN H
FAN -NAT
"NAT+NAT,
FAN
hFAN
FAN
+FAN
■NAT
+NATj
6
NA
NA
25
NA
118
45
NA
17b 71
NA 255 im
NA 348 142
NA
155
187
NA
579 245
NA
846
. NA
8
NA
NA
28
NA
128
52
NA
190 81
NA 276 118
NA 380 162
NA
497
217
NA
633 : 277
1136
928
-105
10
NA
NA
31
NA
I3(i
56
NA
205 89
NA 295 12*1
NA 405 1 75
NA
532
234
771
680 , 301)
1216
1000
-450
15
NA
NA
36
NA
NA
66
NA
230 105
NA 335 150
NA 400 210
677
602
280
866
772 3(>0
1359
1139
540
20
NA
NA
NA
NA
NA
■ 74
NA
247 120
NA 362 - 170
NA 503 240
76-1
661
321
947
849 . 415
1495
1264
. 04()
30
NA
NA
NA
NA
NA
NA
NA
NA 135
NA 398 193
NA 558 -275
808
730
377
1052
957 490
1682
1447
740
50
NA
NA
NA
NA
NA
NA
NA
NA NA-
NA NA NA
NA 612 325
NA
821
456
1152
1076 «Kt
1879
1672
910
100
NA
NA
NA
NA
NA
NA
NA
NA NA
NA NA NA
NA NA NA
NA
NA
494
NA
NA 6ti3
2006
1885
: 1046
For SI units, 1 in. = 25.4 mm, 1 in.^ = (.)45 nnn''*, 1 ft = 0.305 m, 1 000 Btu per fir = 0.293 kW.
[NFPA 54 Table 13.2(d) J
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
81
Table 5-18 -Table 5-19
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-18 Single-Wall Metal Pipe or Type B Asbestos Cement Vent
Number of Appliances:
Two or More
Appliance T^'pe:
Draft Hood-Equipped
Appliance Vent Connection:
Direct to Pipe or Vent
Vent Connector Capacity
Vent Connector Diameter — D (in. )
Maximum Appliance Input Rating in Thousands of Btu per Hour
ft-8
68
86
98
102
124
147
146
178
204
205
235
275
1
23
44
77
117
179
240
15
2
30
56
92
134
194
265
3
35
64
102
155
216
298
1
25
49
84
129
190
270
30
2
31
58
97
145
211
295
and up
3
36
68
107
164
232
321
Common Vent
Cstpaciiy
Common Vent Diameter — D (in.)
10
12
Total Vent
H
(ft)
Height
Combined Appliance Input Rating in Thousands of
Btu per Hour
6
48
78
111
155
205
320
NA
8
55
89
128
175
234
365
505
10
59
95
136
190
250
396
560
15
71
115
168
228
305
480
690
20
80
129
186
260
340
550
790
30
NA
147
215
300
400
650
940
50
NA
NA
NA
360
490
810
1190
For SI units, 1 in. = 25.4 mm, 1 in.'"^ = 645 mm'^, 1 ft = 0.305 m, 1000 Btu per hr = 0.293 kW.
Note: See Figure G.l(f) and Section 13.2.
[NFPA 54 Table 13.2(e)]
Table 5-19 Exterior Masonry Chimney
Number of Appliances:
Appliance Type:
Appliance Vent Connection:
Two or More
NAT + NAT
l>pe B Doubie-Wall
Connector
SPECIAL USE: Combined Appliance Maximum Input Ratii^ in Thousands of Btu per Hour
Vent
Hei^t
Internal Area of Chimney (in
.')
H
(ft)
12
19
28
38
50
63
78
113
6
25
46
71
103
143
188
246
NA
8
28
.53
82
119
163
218
278
408
10
31
56
90
131
177
236
302
4.54
15
NA
67
106
152
212
283
565
546
20
NA
NA
NA
NA
NA
325
419
648
30
NA
NA
.NA
.NA
NA
NA
496
749
50
NA
NA
NA
NA
NA
NA
NA
922
100
NA
N.4
NA
NA
NA
NA
N.A.
NA
For SI units, 1 in. = 25.4 ram, 1 in.'^ = 645 mm^, 1 ft = 0.305 m, 1000 Btu per hr = 0.293 kW.
[NFPA 54 Table 13.2(f)]
82
WATER HEATERS
Table 5-20
Table 5-20 Exterior Masomy Chimney
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Number of Appliances:
Appliance Type:
Appliance Vent Connection:
Two or More
NAT + NAT
Type B Double-Wall
Connector
SPKCIAL LSK
Minimum
Allo^^able Inpiu Rating ol' Space-Heating Appliance in
Internal Area of Chimney (in.^)
Thousands of Btu
per Ho lu-
Vent
Height
H
(ft)
12
19
28
38
50
63
78
113
Local 99% winter design t
unperature: 37°F or greater
6
.
NA
8
10
15
NA
20
NA
NA
NA
NA
NA
184
30
■ NA
NA ■
NA
NA
NA
393
334
50
NA
NA
NA
NA
NA
NA
NA
579
100
NA
NA
NA
NA
NA
NA
NA
NA
Local 99%
winter design temperature: 27°F
to 36°F
6
68
NA
NA
180
212
NA
8
82
NA
NA
187
214
263
10
51
NA
NA
NA
201
225
265
15
NA
NA
NA
NA
NA
253
274
305
20
NA .
NA
NA
NA
NA
307
330
362
30
NA
NA
NA
NA
NA
NA
445
485
50
NA
NA
■ NA
NA
NA
NA
NA
763
100
NA
NA
NA
NA
NA.
NA
.NA
NA
Local 99%
winter design
temperature: 17'F
to 2(5*F
6
NA
NA
NA
NA
NA
NA
NA
NA
8
NA
NA
NA
NA
NA.
NA
204
352
10
NA
NA
NA
NA
NA
NA
278
358
15
NA
NA
NA
NA
NA
NA
331
398
20
NA
NA
NA
NA
NA
NA.
387
457
30
NA.
NA
NA
NA
NA
NA
NA
581
50
■ NA
NA
NA
NA
NA
NA
NA
862
100
NA
NA
NA
NA
NA
NA
NA
NA
Local 99%
winter design
temperature: 5°F
toie^F
6
NA
NA
NA
NA
NA
NA
NA
NA
8
NA
NA
NA
NA
NA
NA.
NA
NA
10
NA
NA
NA
NA
NA
NA
NA
430
15
NA
NA
NA
NA
.NA
NA
NA.
485
20
NA
NA
NA
NA
NA
NA
NA
547
30
NA
NA
NA
NA
NA
NA
NA
682
. 30
NA
NA
NA
NA
NA
NA
NA
NA
100
NA
NA
NA
NA
NA
NA
NA
NA
Local 99%
winter design temperauire: 4"F or lower
Not recommended for
any vent configurations
For SI units, I in. = 25.4 mm, 1 in.''' - 645 mm'^ 1 ft = 0.305 m, 1000 Bui per hr = 0.293 kW, "C = (°F ~ 32)/1.8.
Note: See Figure 5-13 for a map showing local 99 percent winter design temperatures in the United States.
[NFPA 54 Table 13.2(g)]
83
Table 5-21
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 5-21 Exterior Masonry Chimney
Number of Appliances:
Two or More
^pliance Type:
FAN + NAT
Appliance Vent Connection:
Type B Double-WaU
Connector
SPECIAL L'SE: Combined Appliance Maximum Input Rating in Thousands of Btu per Hour
Vent
Hei^t
Internal Area of
Chimney (in.^)
H
(ft)
12
19
28
38
50
63
78
113
6
74
119
178
257
351
458
582
853
8
80
130
193
279
384
501
636
937
10
84
138
207
299
409
538
686
1010
15
NA
152
233
334
467
611
781
1156
20
NA
NA
250
368
508
668
858
1286
30
NA
NA
NA
404
564
74:7
969
1473
50
NA
NA
NA
NA
NA
831
1089
1692
100
NA
NA
NA
NA
NA
NA
NA
1921
For SI units, 1 in. = 25.4 rnin, 1 in." = 645 min^, 1 ft = 0.305 in, 1000 Btu per hr
[NFPA 54 Table 13.2(h) j
■■ 0.293 kW.
84
WATER HEATERS
Table 5-22
Table 5-22 Exterior Masonry Chimney
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Number of Appliances:
Appliance Type:
Appliance Vent Connection:
Two or More
Type B Double-Wall Connector
SPKCL\L L'SK: Minimum Allnwahtc Input Rating
of Space-Ileating Appliance at tttousaiids of Stii
perHour
Vent
Hei^t
Internal Area of Chimney <in.*)
H
(ft)
12
19
28
S8
50
63
78
113
6
Local 99% %viriter design temperature: S7°F oi
greater
8
10
. 15
NA
20
NA
NA
123
190
249
184
30
NA
NA
NA
334
398
393
334 '
50
NA
NA
NA
NA
NA
714
707
579
100
NA
NA
NA
NA
NA
NA
NA
1600
6
Local 99%
68
winter design
116
tempcratwre: 27''F to 36°F
156
180
212
266
8
82
127
167
187
214
263
10
51
97
141
183
210
225
265
15
NA
111
142
183
233
253
274
305
20
NA
NA
187
230
284
307
330
362
30
NA
NA
NA
330
319
419
445
485
SO
NA
NA
NA
NA
NA
672
705
763
100
NA
NA
NA
NA
NA
NA
NA
1554
6
55
lx)cal 99%
99
winter design temperature: 17°F to 26°F
141 182
215
259
349
8
52
74
111
154
197
226
264
352
10
NA
90
125
169
214
243
278
358
15
NA
NA
167
212
263
296
331
398
20
NA
NA.
212
258
316
352
387
457
80
NA
NA
NA
362
429
470
507
581
50
NA
NA
NA
NA
NA
723
766
862
100
NA
NA
NA
NA
NA
NA
NA
1669
6
NA
78
121
Local 99%
winter design tenjpej'aiure: 5°F to 16°F
166 214
252
301
416
8
NA
94
135
182
230
269
312
423
10
NA
111
149
198
250
289
331
430
15
NA
NA
19S
247
305
346
393
485
20
NA
NA
NA
293
360
408
450
547
m
NA
NA
NA
377
450
581
580
682
50
NA
NA
NA.
NA
. NA
797
853
972
100
NA
NA
NA
NA
NA
NA
NA
1833
6
NA
NA
Local 99%
145
winter design
196
temperature; -WF
249
to4<'F
296
348
484
8
NA
NA
159
213
269
320
371
494
10
NA
NA
175
231
292
839
397
513
15
NA
NA
NA
283
351
404
457
586
20
NA
NA
NA
333
408
468
528
650
30
NA
NA
NA
NA
NA
603
667
805
50
NA
NA
NA
NA
NA.
NA
965
1003
100
NA
NA
NA
NA
NA
NA
NA
NA
Local 99% vwntcr design, temperature: -ll^F or lower
Not recommended for any vent configurations
For SI units, 1 in. = 25.4 mm, 1 in.^ = 645 mni^ 1 ft = 0.305 in, 1000 Btu per hr = 0.293 kW.
Note: See Figxire C.2.4 for a map showing local 99 percent winter design temperatures in the United States,
[NFPA54Tablel3.2(i)]
85
Figure G.1 (a) -G.1(cl)
UNIFORM PLUMBING CODE
PART II
This is originally from NFPA 54, Annex G
which contains additional references from the UPC.
Sizing of Venting Systems Serving Appliances
Equipped with Draft Hoods, Category I
Appliances, and Appliances Listed for Use
with Type B Vents
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
G.l E>iampiesU^i^Siii^eAppIia]K:eVentinglkbIes.SeeFig-
ure G.l (a) through Figure G.l (n) .
Vent cap-^-clZJ
dout^s-watt -
988 vent
\< L-
u
Tile-Bneci masonry -
dilmney
^
lypoBdoutte-ViiaiS
gas^ffintusetlas-{
c(OTnector
Table 5-8 is used when sizing Type B double-wall
gas vent connected directly to the appliance.
Note: The appliance can be either Category I draft-
hood-equipped or fen-assisted type.
HGURE G.l(a) l^pe B DoubIe-\^li Vmt System Serving a
Sing^ Appliance With a l^pe B Double-Wyi Vent
Table S-10 is used when sizing a Type B double-wall gas
vent connector attached to a tile-lined masonry chimney
Notes:
1. 4 is the equivalent cross-sectional area of the tile liner.
2. Hie appliance can be either Category i draft-hood-
equipped or fan-assisted type.
FIGU!(£G.l(c) \^tS^|staiiServin|;aSiii|^A{^lia]K%Witha
Masomy C3iiimiey ami a "1^ B Doul^\^yQi ^;bit Coanect<»
Vent cap—
TypsB
double-wail -
gas vent
1
•
Tlie-lined masonry — »-
chimney
H
1
H
\
Single-wall — *■(
vent connector
A
•
- &
s—
1
Table 5-9 is used when sizing a single-wall metal vent
connector attached to a Type B double-wait gas vent.
Note: The appliance can be either Category I draft-
hood-equipped or fan-assisted type.
FIGURE G.l<b) lype B Dooble-mU Vent System Serving .
Sfai^ Appliance With a Sii^e-Myi Metal Vent Cktonecton
Table 5-11 is used when sizing a single-wall vent
connector attached to a tile-lined masonry chimney.
Notes:
1. 4 is the equivalent cross-sectional area of the tile liner.
2. The appliance can be either Category I draft-hotxi-
equipped or fen-assisted type.
FIGURE G.l(d) \^ System Smfaig a Single A|qdianceUat%
a Masomy Qilmney and a r
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
86
WATER HEATERS
Figure G.1(e)-G.1(h)
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Vent cap
Vent cap
Asbestos cement Type B or single-wall metal vent
serving a single draft-hood-equipped appliance.
(See Table 5-12)
fIGURE G.l(e) Asbest<» C^otent lype B or Sing^e-^Myi
Metal Vent %stem Service a Sinj^e Draft-Hood-Equipped
AppHance.
Table 5-15 is used when sizing single-wall vent
connectors attached to a Type B double-wall
common vent.
Note: Each appliance can be either Category I draft-
hood-equipped or fan-assisted type.
FIGURE G.l(g) Vent System Serving Two or More^pE-
tmces WiQi Type B Double-mil Vent and Sing|e>WUl Metal
Vent Connectors.
Vent cap
"*— Tile-lined masonry
Types
double-\rall
gas vent used
as connectors
Table 5-14 is used when sizing Type B double-wall
gas vent connectors attached to a Type B double-
wall common vent.
Note: Each appliance can be either Category I draft-
hood-equlpped or fan-assisted type.
FIGURE G.l (f) VentSystem Servinf IWo or More Appliances
Wittt Type B Double-mU Vent and l^pe B Double-V/kU Vent
Connef^rs.
Table 5-16 is used when sizing Type B double-wall vent
connectors attached to a tile-lined masonry chimney.
Notes:
1. A is the equivalent cross-sectional area of the tile liner.
2. Each appliance can be either Category I draft-hood-
equipped or fen-assisted type.
FIGURE G.l (h) MasoniyChinmey Serving tWo or More
A|>p]iances With Type B Double»\^yi Vent Connectors.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
87
Table G.1(i) -Table G. 1(1)
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
J, Single-wali vent
" connector
1
-Tile-lined masonry
chimney
TaUe 5-17 is used when sizing singie-wall metal vent
conn«:tors attached to a tlle'lined masonry chimney.
Notes:
1 . ^ is tiie equivalent cross-sectional area of the tiie liner.
2. Each appliance can i>e either Category I draft -
hood-equipped or ^-assisted type.
FIGURE G.l <i) Masomy Chinm^ Serving IWo or More
.^pliatices with Sii^te-\i^ Metal Vent Connectors.
Vent cap
Example: htenif otded common vent connector Lu can
ba no greater than 18 times the common vent connector
manifold inside diameter; that is, a 4 in. (100 mm) inside
diameter common vent connector manifold should not
^ceed 72 in. (1800 mm) in length.
Note: This is an illustration of a typical manifolded \«nt
connector. Different appliance, vent connector, or
common vent types are possible.
F[GUIt£G.l(k) Use of Manifolded Cknnmon Vent Connector.
Vent cap
Asbestos cement Type B or single-wall metal pipe vent
serving two or more draft-hood-equipped appliances.
(See TaUe 5-18 )
flGUREG.lQ) Asbestos Cement lypeB or Sin^e-Wall Metal
Vent System Servii^r Tivo or More Draft-Hood-ik[uipped Ap-
pliances.
Example: Offset common vent
Note: This is an illustration of a typical offset vent.
Different appliance, vent connector, or vent types are
FIGURE G.1<1) Use of Offset Common Vent.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
88
WATER HEATERS
G.1.1 -G 1.2
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
G.1.1 Example 1: Single Draft-Hood-Equipped
Appliance. An installer has a 120,000-Btu/h input
appliance with a 5-inch diameter draft hood outlet
that needs to be vented into a 10-foot-high Type B
vent system. What size vent should be used assuming
(1) a 5-foot lateral single-wall metal vent connector is
used with two 90-degree elbows or (2) a 5-foot lateral
single-wall metal vent connector is used with three 90-
degree elbows in the vent system? See Figure G.1.1.
Solution
Table 5-9 should be used to solve this problem
because single-wall metal vent connectors are being
used with a Type B vent, as follows;
(1) Read down the first column in Table 5-9 until the
row associated with a 10-foot height and 5-foot
lateral is found. Read across this row until a
vent capacity greater than 120,000 Btu/h is
located in the shaded columns labeled NAT Max
for draft-hood-equipped appliances. In this case,
a 5-inch-diameter vent has a capacity of 122,000
Btu/h and can be used for this application.
(2) If three 90-degree elbows are used in the vent
system, the maximum vent capacity listed in the
tables must be reduced by 10 percent (see NFPA
54:13.1.3). This implies that the 5-inch-diameter
vent has an adjusted capacity of only 110,000
Vent connector Tee
u
Tee same size as
segment above
Common vent size
based on ail inputs *
entering this segment
and available total height
Total input-
e^
Rise
^
an
Available total
height H equals
rise plus distance
between tees
Tee same
j^ size as
segment
atiove
Btu^r
input
Increase «3^
vent i
connector T
size if I
necessary Other inputs
from below
Vent connector size
depends on:
• Input
• Rise
• Available total height H
• Table 5-14 connectors
Common vent size
depends on:
• Combined inputs
• Available total height H
• Table 5-14 common vent
Btu/h. In this case, the vent system must be
increased to 6 inches in diameter. See the
following calculations:
122,000 X 0.90 = 110,000 for 5-inch vent
From Table 5-10, select 6-inch vent.
186,000 X 0.90 = 167,000
This figure is greater than the required
120,000. Therefore, use a 6-inch vent and
connector where three elbows are used.
G.1.2. Example 2; Single Fan-Assisted Appliance.
An installer has an 80,000 Btu/h input fan-assisted
appliance that must be installed using 10 feet of
lateral connector attached to a 30-foot high Type B
vent. Two 90 -degree elbows are needed for the
installation. Can a single-wall metal vent cormector
be used for this application? See Figure G.1.2.
Solution
Table 5-9 refers to the use of single-wall metal vent
connectors with Type B vent. In the first column
find the row associated with a 30-foot height and a
10-foot lateral. Read across this row, looking at the
Use individual vent tortop-fioor
appliance if connector
reqaimment for rise or total
height cannot be met
Use vent
connector i
table
Listed cap
Top-floor-
appliance
Use available total
height for top-floor
appliance and
combined input of
all appliances on
common vent
Third interconnection tee"
Availat^e total height
for third-floor appliance
and combined input of
three appliances
(if lop-floor appliance
is not connected,
measure total
height to vent top)
.Second interconnection
lee*
Use available total
height for second-floor
ippliance and combined
heat input of two
Rrst interconnection tee*
Design vent connector for
first-floor appliance as an
individual vent of this total
height for input of first-
floor appliance
FIGURE G.l(m) Muldstoiy Gas Vent Design Procedure for
Each Segment of System.
* Each interconnection tee is same size as
s^ment of common vent directly above
FIGURE G.I(o) Principles of Design of Multistory Vents
Uao^ Vent Connector and Common Vent Design Tables.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
89
G.1.2-G.2.1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
FAN Min and FAN Max columns, to find that a 3-
inch diameter single-wall metal vent connector is not
recommended. Moving to the next larger size single-
wall connector (4 inch), we find that a 4-inch
diameter single-wall metal connector has a
recommended maximum vent capacity of 144,000
Btu/h. The 80,000 Btu/h fan-assisted appliance is
outside this range, so the conclusion is that a single-
wall metal connector could be used to vent the
appliance. Table 5-9 shows the acceptable range of
vent capacities for a 4 inch vent with 5 feet of lateral
to be between 72,000 Btu/h and 157,000 Btu/h.
If the appliance cannot be moved closer to the
vertical vent, then a Type B vent could be used as the
connector material. In this case. Table 5-8 shows
that, for a 30-foot-high vent with 10 feet of lateral,
the acceptable range of vent capacities for a 4-inch-
diameter vent attached to a fan-assisted appliance is
between 37,000 Btu/h and 150,000 Btu/h.
G.1.3. Example 3: Interpolating Between Table
Values. An installer has an 80,000 Btu/h input
appliance with a 4-inch diameter draft hood outlet that
needs to be vented into a 12-foot-high Type B vent.
The vent connector has a 5-ft. lateral length and is also
Type B. Can this appliance be vented using a 4-inch
diameter vent?
Solution
Table 5-8 is used in the case of an all Type B Vent
system. However, since there is no entry in Table 5-8
for a height of 12 feet, interpolation must be used.
Read down the 4-inch diameter NAT Max column to
the row associated with a 10-foot height and 5-foot
lateral to find the capacity value of 77,000 Btu/h.
Read further down to the 15-foot height, 5-foot
lateral row to find the capacity value of 87,000
Btu/h. The difference between the 15-foot height
capacity value and the 10-foot height capacity value
is 10,000 Btu/h. The capacity for a vent system with
a 12-foot height is equal to the capacity for a 10-foot
height plus 2/5 of the difference between the 10-foot
and 15-foot height values, or 77,000 + 2/5 x 10,000 =
81,000 Btu/h. Therefore, a 4-inch diameter vent can
be used in the installation.
G.2 Examples Using Common Venting Tables.
G.2.1 Example 4: Common Venting Two Draft-Hood-
Equipped Appliances. A 35,000-Btu/h water heater is
to be common vented with a 150,000 Btu/h furnace,
using a common vent with a total height of 30 feet.
The connector rise is 2 feet for the water heater with a
horizontal length of 4 feet. The connector rise for the
furnace is 3 feet with a horizontal length of 8 feet.
Assume single-wall metal connectors will be used
with Type B vent. What size connectors and
combined vent should be used in this installation?
TypeB
double-wall ■
gas vent
q~3
1R^
>/
10ft
Single-wall
connecstor
Draft hood-
equipped appliance
120,000-Btu/hr Input
For SI units, 1 ft = 0.305 m.
FIGURE G.1.1 Sin^e Draft Hood-Equipped Appliance
Example I.
30ft
For SI units, 1 ft = 0.305 m.
FIGURE G.I.2 Sin^e Fan-Assisted Appliance — Example 2.
, Combined capacity
•;:j^ 35,000 + 150.C
185,000 Btu/hr
-♦—Type B double-
wall gas vent
Draft hood-
equipped
water heater
35.000 Btu/hr
input
Draft hood-
equipped furnace
150.000 Btu/hr
input
FIGURE G.2. 1 Common Venting Two Draft Hood-Equipped
Appliances — Example 4.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
90
WATER HEATERS
G.2.1 -G.2.2
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
See Figure G.2.1.
Solution
Table 5-15 should be used to size single-wall
metal vent connectors attached to Type B vertical
vents. In the Vent Connector Capacity portion of
Table 5-15, find the row associated with a 30-foot
vent height. For a 2-foot rise on the vent connector
for the water heater, read the shaded columns for
draft-hood-equipped appliances to find that a 3-inch
diameter vent connector has a capacity of 37,000
Btu/h. Therefore, a 3-inch single-wall metal vent
cormector can be used with the water heater. For a
draft-hood-equipped furnace with a 3-foot rise, read
across the appropriate row to find that a 5-inch-
diameter vent connector has a maximum capacity of
120,000 Btu/h (which is too small for the furnace),
and a 6-inch diameter vent connector has a
maximum vent capacity of 172,000 Btu/h. Therefore,
a 6-inch diameter vent connector should be used
with the 150,000 Btu/h furnace. Since both vent
connector horizontal lengths are less than the
maximum lengths listed in Table 5-8, the table values
can be used without adjustments.
In the Common Vent Capacity portion of Table
5-15, find the row associated with a 30-foot vent
height and read over to the NAT + NAT portion of
the 6-inch diameter column to find a maximum
combined capacity of 257,000 Btu/h. Since the two
appliances total only 185,000 Btu/h, a 6-inch
common vent can be used.
G.2.2 Example 5 (a): Common Venting a Draft-
Hood-Equipped Water Heater with a Fan-Assisted
Furnace into a Type B Vent. In this case, a 35,000-
Btu/h input draft-hood-equipped water heater with a
4-inch diameter draft hood outlet, 2-feet of connector
rise, and 4-feet of horizontal length is to be common
vented with a 100,000 Btu/h fan-assisted furnace
with a 4-inch diameter flue collar, 3-feet of connector
rise, and 6-feet of horizontal length. The common
vent consists of a 30-foot height of Type B vent. What
are the recommended vent diameters for each
connector and the common vent? The installer would
like to use a single-wall metal vent connector. See
Figure G.2.2.
Solution (See Table 5-15)
Water Heater Vent Connector Diameter. Since
the water heater vent cormector horizontal length of
4 feet is less than the maximum value listed in Table
5-15, the venting table values can be used without
adjustment. Using the Vent Connector Capacity
portion of Table 5-15, read down the Total Vent
Height (H) column to 30 feet and read across the 2-
feet Connector Rise (R) row to the first Btu/h rating
Combined capacity
35,000+100,000 =
135,000 Btuilir
Type B
-double-wall
gas vent 30 ft
For SI units, 1000 Btu/hr = 0.293 kW, 1 ft = 0.305 m.
FIGURE G.2.2 Common Venting a Draft Hood-Equipped
Water Heater with a Fan-Asristed Furnace into a Type B
Double-WaU Common Vent — Example 5<a).
TABLE G.2.3
Masonry Chimney Liner Dimensions with Circular
Equivalents
Inside
Inside
Diameter
Nominal Dimensions
or Equivalent
Equivalent
Liner Size of Liner
Diameter
Area
(in.)
(in.)
(in.)
(in.^)
4x8
2-1/2x6-1/2
4.0
12.2
5.0
19.6
6.0
28.3
7.0
38.3
8x8
6-3/4 x 6-3/4
7.4
42.7
8.0
50.3
8x12
6-1/2x10-1/2
9.0
63.6
10.0
78.5
12x12
9-3/4 X 9-3/4
10.4
83.3
11.0
95.0
12x16
9-1/2x13-1/2
11.8
107.5
12.0
113.0
14.0
153.9
16x16
13-1/4x13-1/4
14.5
162.9
15.0
176.7
16x20
13x17
16.2
206.1
18.0
254.4
20x20
16-3/4 X 16-3/4
18.2
260.2
20.0
314.1
20x24
16-1/2x20-1/2
20.1
314.2
22.0
380.1
24x24
20-1/4x20-1/4
22.1
380.1
24.0
452.3
24x28
20-1/4x24-1/4
24.1
456.2
28x28
24-1/4x24-1/4
26.4
543.3
27.0
572.5
30x30
25-1/2x25-1/2
27.9
607.0
30.0
706.8
30x36
25-1/2x31-1/2
30.9
749.9
33.0
855.3
36x36
31-1/2x31-1/2
34.4
929.4
36.0
1017.9
For SI units, 1 in. = 25.4 mm, 1 in.^ = 645 mirf.
Note: When liner sizes differ dimensionally from those shown in this
table, equivalent diameters can be determined from published tables for
square and rectangular ducts of equivalent carrying capacity or by
other engineering methods.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
91
G.2.2-G.2.4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
in the NAT Max column that is equal to or greater
than the water heater input rating. The table shows
that a 3-inch vent connector has a maximum input
rating of 37,000 Btu/h. Although this rating is
greater than the water heater input rating, a 3-inch
vent connector is prohibited by Section 511.1.1(5). A
4-inch vent connector has a n\axin\um input rating of
67,000 Btu/h and is equal to the draft hood outlet
diameter. A 4-inch vent connector is selected. Since
the water heater is equipped with a draft hood, there
are no minimuni input rating restrictions.
Furnace Vent Connector Diameter. Using the Vent
Connector Capacity portion of Table 5-15, read down
the Total Vent Height (H) column to 30 feet and
across the 3-foot Connector Rise (R) row. Since the
furnace has a fan-assisted combustion system, find
the first FAN Max column with a Btu/h rating
greater than the furnace input rating. The 4-inch
vent connector has a maximum input rating of
119,000 Btu/h and a minimum input rating of 85,000
Btu/h.
The 100,000-Btu/h furnace in this example falls
within this range, so a 4-inch connector is adequate.
Since the furnace vent connector horizontal length of
6 feet is less than the maximum value listed in Table
5-8, the venting table values can be used without
adjustment. If the furnace had an input rating of
80,000 Btu/h, then a Type B vent connector would be
needed in order to meet the minimum capacity limit,
(see Table 5-14)
Common Vent Diameter. The total input to the
common vent is 135,000 Btu/h. Using the Common
Vent Capacity portion of Table 5-15, read down the
Vent Height (H) column to 30 feet and across this
row to find the smallest vent diameter in the FAN +
NAT column that has a Btu/h rating equal to or
greater than 135,000 Btu/h. The 4-inch common
vent has a capacity of 132,000 Btu/h and the 5-inch
common vent has a capacity of 202,000 Btu/h.
Therefore, the 5-inch common vent should be used in
this example.
Summary: In this example, the installer can use a 4-
inch diameter, single-wall metal vent connector for
the water heater and a 4-inch-diameter, single-wall
metal vent cormector for the furnace. The common
vent should be a 5-inch-diameter Type B vent.
G.2.3 Example 5 (b): Common Venting into an
Interior Masonry Chimney. In this case, the water
heater and fan-assisted furnace of Example 5 (a) are
to be common-vented into a clay-tile-lined masonry
chimney with a 30-foot height. The chimney is not
exposed to the outdoors below the roof line. The
internal dimensions of the clay tile liner are
nominally 8 inches x 12 inches. Assuming the same
vent cormector heights, laterals, and materials found
in example 5 (a), what are the recommended vent
connector diameters, and is this an acceptable
installation?
Solution
Table 5-17 is used to size common venting
installations involving single-wall connectors into
masonry chimneys.
Water Heater Vent Connector Diameter. Using
Table 5-17, Vent Connector Capacity, read down the
Vent Height (H) column to 30 feet, and read across
the 2-foot Connector Rise (R) row to the first Btu/h
rating in the NAT Max column that is equal to or
greater than the water heater input rating. The table
shows that a 3-inch vent connector has a maximum
input of only 31,000 Btu/h, while a 4-inch vent
connector has a maximum input of 57,000 Btu/h. A
4-inch vent connector must therefore be used.
Furnace Vent Connector Diameter. Using the Vent
Connector Capacity portion of Table 5-17, read down
the total Vent Height (H) column to 30 feet and
across the 3-feet Connector Rise (R) row. Because the
furnace has a fan-assisted combustion system, find
the first FAN Max column with a Btu/h rating
greater than the furnace input rating. The 4-inch vent
connector has a maximum input rating of 127,000
Btu/h and a minimum input rating of 95,000 Btu/h.
The 100,000 Btu/h furnace in this example falls
within this range, so a 4-inch connector is adequate.
Masonry Chimney. From Table G.2.3, the
equivalent area for a nominal liner size of 8 inches x
12 inches is 63.6 inchest Using Table 5-17, Common
Vent Capacity, read down the FAN + NAT column
under the Minimum Internal Area of Chimney value
of 63 to the row for 30-foot height to find a capacity
value of 739,000 Btu/h. The combined input rating
of the furnace and water heater, 135,000 Btu/h, is
less than the table value so this is an acceptable
installation.
Section 511.1.9 requires the common vent area to be
no greater than seven times the smallest listed
appliance categorized vent area, flue collar area, or
draft hood outlet area. Both appliances in this
installation have 4-inch-diameter outlets. From Table
G.2.3, the equivalent area for an inside diameter of 4-
inch is 12.2 in.l Seven times 12.2 equals 85.4,, which is
greater than 63.6, so this configuration is acceptable.
G.2.4 Example 5 (c): Common Venting into an
Exterior Masonry Chimney. In this case, the water
heater and fan-assisted furnace of Examples 5(a) and
5(b) are to be common-vented into an exterior
masonry chimney. The chimney height, clay-tile-
liner dimensions, and vent connector heights and
laterals are the same as in Example 5(b). This system
is being installed in Charlotte, North Carolina. Does
this exterior masonry chimney need to be relined? If
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
92
WATER HEATERS
G.2.4
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
SO, what corrugated metallic liner size is
recommeiided? What vent connector diameters are
recommended? See Table G.2.3 and Figure 5-13.
Solution
According to 511.2.18, Type B velit cormectors
are required to be used with exterior masonry
chimneys. Use Table 5-21 and Table 5-22 to size
FAN+NAT common venting installations involving
Type-B double-wall connectors into exterior
masonry chimneys.
The local 99 percent winter design temperature
needed to use Table 5-21 and Table 5-22 can be found
in the ASHRAE Handbook - Fundamentals. For Qiarlotte,
North Carolina, this design temperature is 19°F.
Chimney Liner Requirement. As in Example 5 (b),
use the 63 tn.^ column of Table 5-21 to the 30 ft height
row to find that the combined appliance maximum
input is 747,000 Btu/h. The combined input rating
of the appliance in this insta;llation, 135,000 Btu/h, is
less than the maximum value, so this criterion is
satisfied. Table 5-22, at a 19°F design temperature,
and at the same vent height and internal area used
earlier, shows that the minimum allowable input
rating of a space-heating appliance is 470,000 Btu/h.
The furnace input rating of 100,000 Btu/h is less than
this minimum value. So this criterion is not satisfied,
and an alternative venting design needs to be used,
such as a Type B vent shown in Example 5(a) or a
listed chimney liner system shov^m in the rest of the
example.
According to Section 511.1.6, Table 5-9 or Table
5-10 are used for sizing corrugated metallic liners in
masonry chimneys, with the maximum common
vent capacities reduced by 20 percent. This example
will be continued assuming T)rpe B vent connectors.
Water Heater Vent Connector Diameter. Using
Table 5-14 Connector Capacity, read down the total
Vent Height (H) column to 30 feet, and read across
the 2-foot Connector Rise (R) row to the first
Btu/hour rating in the NAT Max column that is
equal to or greater than the water heater input
rating. The table shows that a 3 in. vent connector
has a maximum capacity of 39,000 Btu/h. Although
this rating is greater than the water heater input
rating, a 3-inch vent connector is prohibited by
511.1.6. A 4 in. vent cormector has a maximum input
rating of 70,000 Btu/h and is equal to the draft hood
outlet diameter. A 4-inch vent connector is selected.
Furnace Vent Connector Diameter. Using Table 5-
14, Vent Connector Capacity, read down the total
Vent Height (H) column to 30 feet, and read across
the 3-foot Connector Rise (R) row to the first Btu/h
rating in the FAN MAX column that is equal to or
greater than the furnace input rating. The 100,000
Btu/h furnace in this example falls within this range,
so a 4-inch connector is adequate.
Chimney Liner Diameter. The total input to the
common vent is 135,000 Btu/h. Using the Common
Vent Capacity portion of Table 5-14, read down the
total Vent Height (H) column to 30 feet and across
this row to find the smallest vent diameter in the
FAN + NAT column that has a Btu/h rating greater
than 135,000 Btu/h. The 4 in. common vent has a
capacity of 138,000 Btu/h. Reducing the maximum
capacity by 20 percent (see 511.2.19) results in a
maximum capacity for a 4-inch corrugated liner of
110,000 Btu/h, less than the total input of 135,000
Btu/h. So a larger liner is needed. The 5-inch
common vent capacity listed in Table 5-14 is 210,000
Btu/h, and after reducing by 20 percent is 168,000
Btu/h. Therefore, a 5-inch corrugated metal liner
should be used in this example.
Single Wall Connectors. Once it has been
established that relining the chimney is necessary.
Type B double-wall vent connectors are not
specifically required. This example could be redone
using Table 5-15 for single-wall vent connectors. For
this case, the vent connector and liner diameters
would be the same as found for Type B double-wall
connectors.
The following is originally from NFPA 54, which
contains additional reference.
Example of Combination of Indoor and Outdoor
Combustion and Ventilation Opening Design.
J.l Example of Combination Indoor and Outdoor
Combustion Air Opening. Determine the required
combination of indoor and outdoor combustion air
opening sizes for the following equipment
installation example.
Example Installation: A fan-assisted furnace and a
draft-hood-equipped water heater with the following
inputs are located in a 15-foot x 30-foot basement
with an 8-foot ceiling. No additional indoor spaces
can be used to help meet the equipment combustion
air needs.
Fan-Assisted Furnace Input: 100,000 Btu/h
Draft-Hood-Equipped Water Heater Input:
40,000 Btu/h
Solution
(1) Determine the total available room volume:
Equipment room volim\e: 15 feet x 30 feet with an
8-foot ceiling = 3,600 feet^
(2) Determine the total required volume: The standard
method to determine combustion air will be
used to calculate the required volume.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
93
G.2.4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
the basement is calculated as follows:
100,000 Btu/h +40,000 Btu/h = 140,000 Btu/h
The Standard Method requires that the required
volume be determined based on 50 cubic feet per
1,000 Btu/hour. Using Table A.9.3.2.1, the
required volume for a 140,000 Btu/h water
heater is 7,000 feet\
Conclusion: Indoor volume is insufficient to
supply combustion air since the total of 3,600 feet^
does not meet the required volume of 7000 feet^.
Therefore, additional combustion air must be
provided from the outdoors.
(3) Determine ratio of the available volume to the
required volume:
3,600 it' = 0.51
7000 ft.^
(4) Determine the reduction factor to be used to
reduce the full outdoor air opening size to the
minimum required based on ratio of indoor
spaces:
1.00 - 0.51 (from Step 3) = 0.49
(5) Determine the single outdoor combustion air
opening size as if all combustion air is to come
from outdoors. In this example, the combustion
air opening directly communicates with the outdoors.
140,000 Bhi/h= 47 in.^
3,000 Btu/in.'
(6) Determine the minimum outdoor combustion
air opening area:
Outdoor opening area = 0.49
(from Step 4) x 47 in.-= 23 in.'
Section 507.3 requires the minimum dimension of the
air opening should not be less than 3 inches.
TABLE A.9.3.2.1
Standard Method Volume, Ail Appliances
Appliance Input
Required Volume
(Btu/h)
(ft.^)
5,000
250
10,000
500
15,000
750
20,000
1,000
25,000
1,250
30,000
1,500
35,000
1,750
40,000
2,000
45,000
2,250
50,000
2,500
55,000
2,750
60,000
3,000
65,000
3,250
70,000
3,500
75,000
3,750
80,000
4,000
85,000
4,250
90,000
4,500
95,000
4,750
100,000
5,000
105,000
5,250
110,000
5,500
115,000
5,750
120,000
6,000
125,000
6,250
130,000
6,500
135,000
6,750
140,000
7,000
145,000
7,250
150,000
7,500
160,000
8,000
170,000
8,500
180,000
9,000
190,000
9,500
200,000
10,000
210,000
10,500
220,000
11,000
230,000
11,500
240,000
12,000
250,000
12,500
260,000
13,000
270,000
13,500
280,000
14,000
290,000
14,500
300,000
15,000
507.4.1 See Figure 5-8 • 507.4.1(1) See Figure 5-9 and
Figure 5-10 • 507.4.1(2) See Figure 5-11 • 507.4.2 See
Figure 5-12 • For information on gas convenience
outlets, see AGA 7-90, Requirements for Gas Convenience
Outlets.
94
CHAPTER 6
WATER SUPPLY AND DISTRIBUTION
601.0 Running Water Required.
601.1 Except where not deemed necessary for safety
or sanitation by the Authority Having Jurisdiction,
each plumbing fixture shall be provided with an
adequate supply of potable running water piped
thereto in an approved manner, so arranged as to
flush and keep it in a clean and sanitary condition
without danger of backflow or cross-connection.
Water closets and urinals shall be flushed by means
of an approved flush tank or flushometer valve. In
jurisdictions that adopt Chapter 16, water closets,
urinals, and trap primers in designated non-
residential buildings may be provided with
reclaimed water as defined and regulated by
Chapter 16 of this code.
Exception: Listed fixtures that do not require
water for their operation and are not connected
to the water supply.
601.2 Identification of a Potable and Nonpotable
Water System. In all buildings where potable water
and nonpotable water systems are installed, each
system shall be clearly identified. Each system shall
be color coded as follows:
601.2.1 Potable Water - Green background
with white lettering.
601 .2.2 Nonpotable Water - YeUow background
with black lettering, with the words "Caution:
Nonpotable water, do not drink."
Each system shall be identified with a
colored band to designate the liquid being
conveyed, and the direction of normal flow shall
be clearly shown. The minimum size of the
letters and length of the color field shall conform
to Table 6-1.
A colored identification band shall be
indicated every twenty (20) feet (6096 mm) but
at least once per room, and shall be visible from
the floor level.
Where vacuum breakers or backflow
preventers are installed with fixtures listed in
Table 14-1, identification of the discharge side
may be omitted. Each outlet on the nonpotable
water line that could be used for special
purposes shall be posted as follows:
"Caution: Nonpotable water, do not drink."
601.2.3 Reclaimed Water - Purple (Pantone
color #512) background and shall be imprinted
in nominal 1/2-inch (12.7 mm) high, black upper-
case letters, with the words "Caution: Reclaimed
water, do not drink."
601.3 Faucets and diverters shall be connected to the
water distribution system so that hot water
corresponds to the left side of the fittings.
TABLE 6-1
Minimum Length of Color Field and Size of Letters
Outside Diameter
[\/linimum Lengtii
Minimum Size
of Pipe or
Covering
of Color Field
of Letters
inches
(mm)
Inches
(mm)
inches
(mm)
1/2 to 1-1/4
(15 to 32)
8
(203)
1/2
(12.7)
1-1/2 to 2
(40 to 50)
8
(203)
3/4
(19.1)
2-1/2 to 6
(65 to 150)
12
(305)
1-1/4
(32)
8 to 10
(200 to 250;
1 24
(619)
2-1/2
(64)
Over 10
(Over 250)
32
(813)
3-1/2
(89)
602.0 Unlawful Connections
602.1 No installation of potable water supply piping
or part thereof shall be made in such a maimer that it
will be possible for used, unclean, polluted, or
contaminated water, mixtures, or substances to enter
any portion of such piping from any tank, receptor,
equipment, or plumbing fixture by reason of back-
siphonage, suction, or any other cause, either during
normal use and operation thereof, or when any such
tank, receptor, equipment, or plumbing fixture is
flooded or subject to pressure in excess of the
operating pressure in the hot or cold water piping.
602.2 No person shall make a connection or allow one
to exist between pipes or conduits carrying domestic
w^ater supplied by any public or private w^ater service
system, and any pipes, conduits, or fixtures
containing or carrying water from any other source or
containing or carrying water that has been used for
any purpose whatsoever, or any piping carrying
chemicals, liquids, gases, or any substances
whatsoever, unless there is provided a backflow
prevention device approved for the potential hazard
and maintained in accordance with this code. Each
point of use shall be separately protected when
potential cross-contamination of individual units exists.
602.3 No plumbing fixture, device, or construction
shall be installed or maintained or shall be connected
to any domestic water supply when such installation
or connection may provide a possibility of polluting
such water supply or may provide a cross-
connection between a distributing system of water
for drinking and domestic purposes and water that
95
602.3 - Table 6-2
UNIFORM PLUMBING CODE
may become contaminated by such plumbing
fixture, device, or construction unless there is
provided a backflow prevention device approved for
the potential hazard.
602.4 No water piping supplied by any private
water supply system shall be connected to any other
source of supply without the approval of the
Authority Having Jurisdiction, Health Department,
or other department having jurisdiction.
603.0 Cross-connection Control.
Cross-connection control shall be provided in ac-
cordance with the provisions of this chapter.
No person shall install any water-operated
equipment or mechanism, or use any water-treating
chemical or substance, if it is found that such
equipment, mechanism, chemical, or substance may
cause pollution or contamination of the domestic
water supply. Such equipment or mechanism may be
permitted only when equipped with an approved
backflow prevention device or assembly.
603.1 Approval of Devices or Assemblies. Before
any device or assembly is installed for the prevention
of backflow, it shall have first been approved by the
Authority Having Jurisdiction. Devices or assemblies
shall be tested for conformity with recognized stan-
dards or other standards acceptable to the Authority
Having Jurisdiction that are consistent with the
intent of this code.
All devices or assemblies installed in a potable
water supply system for protection against backflow
TABLE 6-2
Backflow Prevention Devices, Assemblies, and Methods
Degree of Hazard
Device,
Assembly, or
Method'
Pollution
(Low Hazard)
Contamination
(High Hazard)
Installation ^'
Back Siphonage
Back Pressure
Back Siphonage
Back Pressure
Airgap
X
X
See Table 6-3 in this chapter.
Atmospheric
Vacuum
Breaker
X
X
Upright position. No valve
downstream. Minimum of six (6)
inches (152 mm) or listed distance
above all downstream piping and
flood-level rim of receptor.^ '
1 Spill-Resistant
Pressure-Type
Vacuum
Breaker
X
X
X
Upright position. Minimum of six
(6) inces (152 rmn) or Usted
distance above all downstream
piping and flood-level rim of '
receptor.'
Double Check
Valve Backflow
Preventer
X
X
Horizontal, unless otherwise
listed. Requires one (1) foot
minimum clearance at bottom for
maintenance. May need
platform/ladder for test and
repair. Does not discharge water.
Pressure
Vacuum
Breaker
X
X
Upright position. Mayhave
valves downstream. Minimum of
twelve (12) inches (305 mm) above
all downstream, piping and flood-
level rim of receptor. May
discharge water.
Reduced
Pressure
Principle '
Backflow
Preventer
X
X
X
X
Horizontal unless otherwise
listed. Requires one (1) foot (305
mm) minimum clearance at
bottom for maintenance. May
need platform ladder for test and
repair. May discharge water.
' See description of devices and assemblies in this chapter.
^ Installation in pit or vault requires previous approval by the Authority Having Jurisdiction.
^ Refer to general and specific requireirient for installation.
" Not to be subjected to operating pressvire for more than 12 hours in any 24-hour period.
' For deck-mounted and equipment-moimted vacuum breaker, see Section 603.4.15.
96
WATER SUPPLY AND DISTRIBUTION
603.1 -Table 6-3
shall be maintained in good working condition by
the person or persons having control of such devices
or assemblies. Such devices or assemblies shall be
tested at the time of installation, repair, or relocation
and at least on an annual schedule thereafter, or
more often when required by the Authority Having
Jurisdiction. If found to be defective or inoperative,
the device or assembly shall be repaired or replaced.
No device or assembly shall be removed from use or
relocated or other device or assembly substituted,
without the approval of the Authority Having
Jurisdiction.
Testing shall be performed by a certified
backflow assembly tester.
603.2 Backflow Prevention Devices, Assemblies,
and l\/lethods.
603.2.1 Airgap. The minimum airgap to afford
backflow protection shall be in accordance with
Table 6-3.
603.2.2 Atmospheric Vacuum Breaker (AVB).
An atmospheric vacuum breaker consists of a
body, a checking member, and an atmospheric
opening.
603.2.3 Hose Connection Backflow Preventer.
A hose connection backflow preventer consists of
two independent check valves with an independent
atmospheric vent between and a means of field
testing and draining.
603.2.4 Double Check Valve Backflow Preven-
tion Assembly (DC). A double check valve
backflow prevention assembly consists of
two independently acting internally loaded check
valves, four properly located test cocks, and
two isolation valves.
603.2.5 Pressure Vacuum Breaker Backflow
Prevention Assembly (PVB). A pressure
vacuum breaker backflow prevention assembly
consists of a loaded air inlet valve, an internally
loaded check valve, two (2) properly located test
TABLE 6-3
Minimum Airgaps for Water Distribution"
Fixtures
When not affected
by sidewalls^
Inches (mm)
When affected by
sidewalP
Inches (mm)
Effective openings^ not greater
than one-half (1/2) inch (12.7 mm)
in diameter
1 (25.4)
1-1/2 (38)
Effective openings^ not greater
than three-quarters (3/4) inch
(20 mm) in diameter
1-1/2 (38)
2-1/4 (57)
Effective openings^ not greater
than one (1) inch (25 mm) in
diameter
2 (51)
■
3 (76)
Effective openings' greater than
one (1) inch (25 mm) in diameter
Two (2) times
diameter of
effective opening
Three (3) times
diameter of
effective opening
' Sidewalls, ribs, or similar obstructions do not affect airgaps when spaced from the inside edge of the spout opening a distance
greater than three times the diameter of the effective opening for a single wall, or a distance greater than four times the effective
opening for two intersecting walls.
^ Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening
other than specified in Note 1 above. The effect of three or more such vertical walls or ribs has not been determined. In such cases,
the airgap shall be measured from the top of the wall.
' The effective opening shall be the minimum cross-sectional area at the seat of the control valve or the supply pipe or tubing that
feeds the device or outlet. If two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas
of the individual supply lines or the area of the single outlet, whichever is smaller.
" Airgaps less than one (1) inch (25.4 mm) shall be approved only as a permanent part of a listed assembly that has been tested
under actual backflow conditions with vacuums of to 25 inches (635 mm) of mercury.
97
603.2 - 603.4
UNIFORM PLUMBING CODE
cocks, and two (2) isolation valves. This device
shall be installed indoors only if provisions for
spillage are provided.
603.2.6 Pressure Vacuum Breaker Spill-
Resistant-Type Backflow Prevention
Assembly (SVB). A pressure-type vacuum
breaker backflow prevention assembly consists
of one (1) check valve force-loaded closed and
an air inlet vent valve force-loaded open to
atmosphere, positioned downstream of the check
valve, and located between and including two
(2) tightly closing shutoff valves and test cocks.
603.2.7 Reduced-Pressure Principle Backflow
Prevention Assembly (RP). A reduced-pressure
principle backflow prevention assembly consists
of two independently acting internally loaded
check valves, a differential pressure-relief valve,
four properly located test cocks, and two
isolation valves.
603.3 General Requirements.
603.3.1 All assemblies shall conform to listed
standards and be acceptable to the Authority
Having Jurisdiction, with jurisdiction over the
selection and installation of backflow prevention
assemblies.
603.3.2 Where niore than one (1) backflow
prevention valve is installed on a single premise,
and the valves are installed in one location, each
separate valve shall be permanently identified
by the permittee in a manner satisfactory to the
Authority Having Jurisdiction.
603.3.3 The premise owner or responsible
person shall have the backflow prevention
assenrvbly tested by a certified backflow assembly
tester at the time of installation, repair, or
relocation and at least on an annual schedule
thereafter, or more often when required by the
Authority Having Jurisdiction. The periodic
testing shall be performed in accordance with
the procedures referenced in Table 14-1 by a
tester qualified in accordance with those standards.
603.3.4 Access and clearance shall be provided
for the required testing, maintenance, and repair.
Access and clearance shall require a minimum of
one (1) foot (305 mm) between the lowest
portion of the assembly and grade, floor, or
platform. Installations elevated more than five
(5) feet (1524 mm) above the floor or grade shall
be provided with a permanent platform capable
of supporting a tester or maintenance person.
603.3.5 Direct connections between potable
water piping and sewer-connected wastes shall
not exist under any condition with or without
backflow protection. Where potable water is
discharged to the drainage system, it shall be by
means of an approved airgap of two (2) pipe
diameters of the supply inlet, but in no case shall
the gap be less than one (1) inch (25 m.m).
Connection may be made to the inlet side of a
trap provided that an approved vacuum breaker
is installed not less than six (6) inches (152 mm),
or the distance according to the device's listing,
above the flood-level rim of such trapped
fixture, so that at no time will any such device
be subjected to any back-pressure.
603.3.6 Backflow preventers for hot water over
110°F (43.3°C) shall be a type designed to op-
erate at temperatures of 110°F (43.3°C) or more
without rendering any portion of the assembly
inoperative.
603.3.7 Fixtures, appliances, or appurtenances
with integral backflow preventers or integral
airgaps manufactured as a unit shall be installed
in accordance with their listing requirements
and the manufacturers' instructions.
603.3.8 In cold climate areas, backflow
assemblies and devices shall be protected from
freezing with an outdoor enclosure or by a i
method acceptable to the Authority Having
Jurisdiction.
603.3.9 All drain lines serving backflow devices
or assemblies shall be sized in accordance with
the discharge rates of the manufacturers' flow
charts of such devices or assemblies.
603.3.10 Design and Installation of Plumbing
Fixtures. Plum^bing fixtures shall be installed
such that fixture fittings, complying with the
backflow prevention requirements of ASME
A112.18.1, do not have these requirements
compromised by the designated fixture fitting
mounting surface.
603.4 Specific Requirements.
603.4.1 Water closet and urinal flushometer
valves shall be equipped with an atmospheric
vacuum breaker. The vacuum breaker shall be
installed on the discharge side of the flushometer
valve with the critical level at least six (6) inches
(152 mm), or the distance according to its listing,
above the overflow rim of a water closet bowl or
the highest part of a urinal.
603.4.2 Water closet and urinal tanks shall be
equipped with a ballcock. The ballcock shall be
installed with the critical level at least one (1)
inch (25.4 mm) above the full opening of the
overflow pipe. In cases where the ballcock has no
hush tube, the bottom of the water supply inlet
shall be installed one (1) inch (25.4 mm) above
the full opening of the overflow pipe.
603.4.3 Water closet flushometer tanks shall be
protected against backflow by an approved
backflow prevention assembly, device, or method.
98
WATER SUPPLY AND DISTRIBUTION
603.4
603.4.4 Heat Exchangers.
603.4.4.1 Heat exchangers used for heat
trarisfer, heat recovery, or solar heating shall
protect the potable water system from being
contaminated by the heat transfer medium.
Single-wall heat exchangers used in indirect-
fired water heaters shall meet the require-
ments of Section 506.4.2. Double-wall heat
exchangers shall separate the potable water
from the heat-transfer medium by providing
a space between the two walls that is vented
to tile atmosphere.
603.4.5 Water supply inlets to tanks, vats,
sumps, swimming pools, and other receptors
shall be protected by one of the following
means:
(1) An approved airgap.
(2) A listed vacuum breaker installed on the
discharge side of the last valve with the
critical level not less than six (6) inches (152
mm) or in accordance with its listing.
(3) A backflow preventer suitable for the
contamination or pollution, installed in
accordance with the requirements for that
type of device or assembly as set forth in
this chapter.
603.4.6 Protection from Lawn Sprinklers and
Irrigation Systems.
603.4.6.1 Potable water supplies to systems
having no piomps or coruiections for pumping
equipment, and no chemical injection or
provisions for chemical injection, shall be
protected from backflow by one of the
following devices:
(1) Atmospheric vacuum breaker
(2) Pressure vacuum breaker
(3) Spill-resistant pressure vacuum breaker
(4) Reduced-pressure backflow preventer
603.4.6.2 Where sprinkler and irrigation
systems have pumps, connections for pumping
equipment, or auxiliary air tanks, or are
otherwise capable of creating back-pressiire, the
potable water supply shall be protected by
the following type of device if the backflow
device is located upstream from the source
of back-pressure:
(1) Reduced-pressure backflow preventer
603.4.6.3 Where systems have a backflow
device installed downstream from a potable
water supply pump or a potable water supply
pump connection, the device shall be one of
the following:
(1) Atmospheric vacuum breaker
(2) Pressure vacuum breaker
(3) Spill-resistant pressure vacuum breaker
(4) Reduced-pressure backflow preventer
603.4.6.4 Where systems include a chemical
injector or any provisions for chemical injection,
the potable water supply shall be protected
by the following:
(1) Reduced-pressure backflow preventer
603.4.7 Potable water outlets with hose
attachments, other than water heater drains,
boiler drains, and clothes washer connections,
shall be protected by a nonremovable hose-bibb-
type backflow preventer, a nonremovable hose
bibb-type vacuum breaker, or by an atmospheric
vacuum breaker installed at least six (6) inches
(152 mm) above the highest point of usage
located on the discharge side of the last valve. In
climates where freezing temperatures occur, a
listed self-draining frost-proof hose bibb with an
integral backflow preventer or vacuum breaker
shall be used.
603.4.8 Water-cooled compressors, degreasers,
or any other water-cooled equipment shall be
protected by a backflow preventer installed in
accordance with the requirem.ents of this chapter.
Note:
Water-cooled equipment that produces back-
pressure shall be equipped with the appropriate
protection.
603.4.9 Water inlets to water-supplied
aspirators shall be equipped with a vacuum
breaker installed in accordance with its listing
requirements and this chapter. The discharge
shall drain through an airgap. When the
tailpiece of a fixture to receive the discharge of
an aspirator is used, the airgap shall be located
above the flood-level rim of the fixture.
603.4.10 Potable water makeup connections to
steam or hot water boilers shall be provided
with a listed backflow protection assembly.
603.4.11 Nonpotable Water Piping. In cases
where it is impractical to correct individual
cross-connections on the domestic waterline, the
line supplying such outlets shall be considered a
nonpotable water line. No drinking or domestic
water outlets shall be connected to the non-
potable waterline. Whenever possible, all
portions of the nonpotable waterline shall be ex-
posed, and all exposed portions shall be properly
identified in a manner satisfactory to the
Authority Having Jurisdiction. Each outlet on the
nonpotable waterline that may be used for
drinking or domestic purposes shall be posted:
"Caution: Nonpotable water, do not drink."
603.4.12 Potable water supply to carbonators
shall be protected by either an airgap or a vented
99
603.4
UNIFORM PLUMBING CODE
backflow preventer for carbonated beverage
dispensers installed within the carbonated
beverage dispenser. The carbonated beverage
dispenser shall bear the label of an approved
testing agency, certifying and attesting that such
equipment has been tested and inspected and
meets the requirements of the approved
applicable standard. Carbonated beverage
dispensers without an approved internal airgap
or vented backflow preventer for carbonated
beverage dispensers and carbonated beverage
dispensing systems shall have the water supply
protected with a vented backflow preventer for
carbonated beverage dispensers.
603.4.13 Water Treatment Units. Reverse osmosis
drinking water treatment units shall meet the
requirements of the appropriate standards
referenced in Table 14-1. Waste or discharge
from reverse osmosis or other types of water
treatment units shall enter the drainage system
through an airgap.
603.4.14 Backflow preventers shall not be
located in any area containing fumes that are
toxic, poisonous, or corrosive.
603.4.15 Deck-mounted or equipment-mounted
vacuum breakers shall be installed in accordance
with their listing and the manufacturers'
instructions, with the critical level not less than
one (1) inch (25.4 mm) above the flood-level rim.
603.4.16 Protection from Fire Systems.
603.4.16.1 Except as provided under
Sections 603.4.16.2 and 603.4.16.3, potable
water supplies to fire protection systems
that are normally under pressure, including
but not limited to standpipes and automatic
sprinkler systems, except in one- or two-
family residential sprinkler systems, piped in
materials approved for potable water
distribution systems shall be protected from
back-pressure and back-siphonage by one of
the following testable devices:
(1) Double check valve assembly
(2) Double check detector assembly
(3) Reduced pressure backflow preventer
(4) Reduced pressure detector assembly
Potable water supplies to fire protection
systems that are not normally under
pressure shall be protected from backflow
and shall meet the requirements of the
appropriate standards referencedin Table 14-1.
603.4.16.2 Where fire protection systems
supplied from a potable water system
include a fire department (siamese) connec-
tion that is located less than seventeen
hundred (1,700) feet (518.2 m) from a non-
potable water source that could be used by
the fire department as a secondary water
supply, the potable w^ater supply shall be
protected by one of the following:
(1) Reduced pressure backflow preventor
(2) Reduced pressure detector assembly
Note:
Nonpotable water sources include fire
department vehicles carrying water of
questionable quality or water that is treated
with antifreeze, corrosion inhibitors, or
extinguishing agents.
603.4.16.3 Where antifreeze, corrosion
inhibitors, or other chemicals are added to a
fire protection system supplied from a
potable water supply, the potable water
system shall be protected by one of the
following:
(1) Reduced pressure backflow preventer
(2) Reduced pressure detector assembly
603.4.16.4 Whenever a backflow device is
installed in the potable water supply to a
fire protection system, the hydraulic design
of the system shall account for the pressure
drop through the backflow device. If such
devices are retrofitted for an existing fire
protection system, the hydraulics of the
sprinkler system design shall be checked to
verify that there will be sufficient water
pressure available for satisfactory operation
of the fire sprinklers.
603.4.16.5 Residential Sprinlcler Systems.
When residential sprinkler systemis are
installed using the potable water system,
they shall be installed in accordance with
the standards listed in Table 14-1.
603.4.17 Special Equipment, Water Supply
Protection. Vacuum breakers for washer-hose
bedpans shall be located not less than five (5)
feet (1,524 mm) above the floor. Hose connections
in health care or laboratory areas shall not be less
than six (6) feet (1,829 mm) above the floor.
603.4.18 Portable cleaning equipment, dental
vacuum pumps, and chemical dispensers shall
be protected from backflow by an airgap, an
atmospheric vacuum breaker, a spill-proof
vacuum breaker, or a reduced pressure principle
backflow preventer.
603.4.19 Water Heater Connectors. Flexible
metallic water heater connectors or reinforced
flexible water heater connectors connecting
water heaters to the piping system shall be in
100
WATER SUPPLY AND DISTRIBUTION
603.4-604.13
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
compliance with the appropriate standards
listed in Table 14-1.
60314.20 Combination stop-and-waste valves
or cocks shall not be installed underground.
603.4.21 Pure Water Process Systems. The
water supply to a pure water process system,
such as dialysis water systems, semiconductor
washing systems, and similar process piping
systems, shall be protected from back-pressure
and back-siphonage by a reduced-pressure
principle backflow preventer.
603.4.21.1 Dialysis Water Systems. The
individual connections of the dialysis
related equipment to the dialysis pure water
system do not require additional backflow
protection.
603.4.22 Plumbing Fixture Fittings. Plumbing
fixture fittings with integral backflow protection
shall comply with ASME A112.18.1.
604:0 Materials.
604.1 All pipe, tube, and fittings carrying water used
in potable water systems intended to supply drinking
water shall meet the requirements of NSF 61 as foimd
in Table 14-1. All materials used in the water supply
system, except valves and similar devices, shall be of
a like material, except where otherwise approved by
the Authority Having Jurisdiction.
Materials for building water piping and building
supply piping shall be in accordance with Table 6-4
and the standards in Table 14-1.
604.2 Copper tube for water piping shall have a
weight of not less than Type L.
Exception: Type M copper tubing may be used
for water piping when piping is aboveground
in, or on, a building or underground outside of
structures.
1604.3 All hard-drawn copper tubing for water supply
and distribution in addition to the required incised
marking, shall be marked in accordance with ASTM
B 88 Seamless Copper Water Tube as listed in Table 14-
1. The colors shall be: Type K, green; Type L, blue;
Type M, red.
604.4 Listed flexible copper water cormectors shall be
installed in readily accessible locations, unless
otherwise listed.
604.5 Cast-iron fittings up to and including two (2)
inches (51 mm) in size, when used in connection
with potable water piping/shall be galvanized.
604.6 All malleable iron water fittings shall be
galvanized.
604.7 Piping and tubing that has previously been used
for any purpose other than for potable water systems
shall not be used.
604.8 Approved plastic materials may be used in
water service piping, provided that where metal
water service piping is used for electrical grounding
purposes, replacement piping therefore shall be of
like materials.
Exception: Where a grounding system acceptable
to the Authority Having Jurisdiction is installed,
inspected, and approved, metallic pipe may be
replaced with nonmetallic pipe.
604.9 Solder shall conform to the requirements of
Section 316.1.3.
604.10 Water pipe and fittings with a lead content
which exceeds eight (8) percent shall be prohibited in
piping systems used to convey potable water.
604.1 1 PEX. Cross-linked polyethylene (PEX) tubing
shall be marked with the appropriate standard
designation(s) listed in Table 14-1 for which the tubing
has been approved. PEX tubing shall be installed in
compliance with the provisions of this section.
604.11.1 PEX Fittings. Metal insert fittings,
metal compression fittings, and cold expansion
fittings used with PEX tubing shall be
manufactured to and marked in accordance with
the standards for the fittings in. Table 14-1.
604.11.2 Water Heater Connections. PEX
tubing shall not be installed within the first
eighteen (18) inches (457 mm) of piping
connected to a water heater.
604.12 Flexible Corrugated Connectors. Flexible
corrugated connectors of copper or stainless steel
shall be limited to the following connector lengths:
Water Heater Connectors - twenty-four (24)
inches (609 mm).
Fixture Connectors - thirty (30) inches (762 mm).
Washing Machine Connectors - seventy-two
(72) inches (1827 mm).
Dishwasher and Icemaker Connectors - one
hundred twenty (120) inches (3048 mm).
604.13 PEX-AL-PEX and PE-AL-PE. Crosslinked
polyethylene-aluminum-crosslinked polyethylene
(PEX-AL-PEX) and polyethylene-aluminum-
polyethylene (PE-AL-PE) composite pipe shall be
marked with the appropriate standard designations
listed in Table 14-1 for which the piping has been
listed or approved. PEX-AL-PEX and PE-AL-PE
piping shall be installed in compliance with the
provisioi\s of this section.
604.13.1 PEX-AL-PEX and PE-AL-PE. Fittings
used with PEX-AL-PEX and PE-AL-PE piping
shall be manufactured to and marked in
101
Table 6-4 -606.1
TABLE 6-4
UNIFORM PLUMBING CODE
Material
Water Distribution
Building Supply Pipe : .
Pipe
and Fittings
j . and Fittings
Hot
Cold
Asbestos - Cement
X^
Brass
X
X
. X • '■
Copper
X
X
• . X
Cast Iron
X
X
'x
CPVC
X
X
X
Galvanized Malleable Iron
X
X
X
Galvanized Wrought Iron
X
X
X
Galvanized Steel
X
X
-■:X-..
PE
X
PE-AL-PE
X
X
X
PEX
X
X
• X . •■ .
PEX-AL-PEX
X
X
■ X
PVC
. X •
accordance with the standard for the fittings in
Table 14-1.
604.13.2 Water Heater Connections. PEX-AL-
PEX or PE-AL-PE tubing shall not be installed
within the first eighteen inches (18) (457 mm) of
piping connected to a water heater.
604.14 Water Heater Connectors. Flexible metallic
water heater cormectors or reinforced flexible water
heater connectors connecting water heating to the
piping system shall be in compliance with the
appropriate standards listed in Table 14-1.
605.0 Valves.
605.1 Valves up to and including two (2) inches (51
mm) in size shall be brass or other approved
material. Sizes over two (2) inches (51 mm) may have
cast-iron or brass bodies. Each gate or ball valve shall
be a fuUway type with working parts of non-
corrosive material.
605.2 A fullway valve controlling all outlets shall be
installed on the discharge side of each water meter
and on each unmetered water supply. Water piping
supplying more than one building on any one premises
shall be equipped with a separate fullway valve to each
building, so arranged that the water supply can be
turned on or off to any individual or separate building
provided; however, that supply piping to a single-
family residence and bmlding accessory thereto may be
controlled on one valve. Such shutoff valves shall be
accessible at aU times. A fullway valve shaU be installed
on the discharge piping from water supply tanks at or
near the tank. A fullway valve shall be installed on the
cold water supply pipe to each water heater at or near
the water heater.
605.3 In multidwelling units, one (1) or more shutoff
valves shall be provided in each dwelling unit so
that the water supply to any plumbing fixture or
group of fixtures in that dwelling unit can be shut off
without stopping water supply to fixtures iri other
dwelling units. These valves shall be accessible iri the
dwelling unit that they control.
605.4 All valves used to control two (2) or more
openings shall be fullway gate valves, ball valves, or
other approved valves designed and approved for
the service intended.
605.5 A control valve shall be installed immediately
ahead of each water-supplied appliance and
immediately ahead of each slip joint or appliance
supply.
Parallel water distribution systems shall provide
a control valve either immediately ahead of each
fixture being supplied or installed at the manifold
and shall be identified with the fixture being
supplied.
605.6 All required shutoff or control valves shall be
accessible.
605.7 A single control valve shall be installed on a
water supply line ahead of any automatic metering
valve that supplies a battery of fixtures.
606.0 Joints and Connections.
606.1 Types of Joints.
606.1.1 Flared Joints. Flared joints for soft
copper water tubing shall be made with fittings
meeting approved standards. The tubing shall
be reamed to the full bore, resized to. round, and
expanded with a proper flaring tool.
102
WATER SUPPLY AND DISTRIBUTION
606.1 -608.4
606.1.2 Mechanical Joints. Mechanical joints
for cast-iron water pipe shall conform to
nationally recognized standards.
606.1.3 Mechanically Formed Tee Fittings.
Mechanically extracted collars shall be formed in
a continuous operation consisting of drilling a
pilot hole and drawing out the tube surface to
form a collar having a height not less than three
(3) times the thickness of the branch tube wall.
The branch tube shall be notched to conform
with the inner curve of the run tube and shall have
two (2) dimple /depth stops to ensure that
penetration of the branch tube into the collar is of
sufficient depth for brazing and that the branch
tube does not obstruct the flow in the main line
tube. Etoiple/depth stops shall be in line with the
nm of the tube. The second dimple shall be one
quarter (1/4) inch (6.35 mm) above the first and
shall serve as a visual point of inspection.
All joints shall be brazed in accordance with
Section 316.1.7. Soldered joints shall not be
allowed.
606.2 Use of Joints.
606.2.1 Copper Water Tube. Joints in copper
tubing shall be made by the appropriate use of
approved fittings properly soldered or brazed
together as provided in Section 316.1.3 or 316.1.7
or by means of approved flared or compression
fittings in Section 606.1.1 or 316.1.5. Solder and
soldering flux shall conform to the requirements
of Section 316.1.3. Mechanically formed tee
fittings shall be made by brazing only and shall
conform to the requirements of Section 316.1.7.
606.2.2 Plastic Fittings. Female PVC screwed
fittings for water piping shall be used with
plastic male fittings and plastic male threads only.
606.2.3 Slip Joints. In water piping, slip joints
may be used only on the exposed fixture supply.
607.0 Gravity Supply Tanks.
Gravity tanks for potable water shall be tightly
covered, and have not less than a sixteen (16) square-
inch (10,323 mm^) overflow screened with copper
screen having not less than fourteen (14) nor more
tlian eighteen (18) openings per linear inch (25.4 mm).
608.0 Water Pressure, Pressure Regulators,
Pressure Relief Valves, and Vacuum Relief Valves.
608.1 Inadequate Water Pressure. Whenever the
water pressure in the main or other source of supply
will not provide a residual water pressure of at least
fifteen (15) pounds per square inch (103.4 kPa), after
allowing for friction and other pressure losses, a tank
and a pump or other means that will provide said
fifteen (15) pound (103.4 kPa) pressure shall be
installed. Whenever fixtures and/or fixture fittings
are installed that require residual pressure higher
than fifteen (15) poimds per square inch (103.4 kPa),
that minimum residual pressure shall be provided.
608.2 Excessive Water Pressure. Where static
water pressure in the water supply piping is in |
excess of eighty (80) pounds per square inch (552
kPa), an approved-type pressure regulator preceded
by an adequate strainer shall be installed and the
static pressure reduced to eighty (80) pounds per
square inch (552 kPa) or less. Such regulator(s) shall
control the pressure to all water outlets in the
building unless otherwise approved by the
Authority Having Jurisdiction. Each such regulator
and strainer shall be accessibly located aboveground
or in a vault equipped with a properly sized and
sloped bore-sighted drain to daylight, shall be
protected from freezing, and shall have the strainer
readily accessible for cleaning without removing the
regulator or strainer body or disconnecting the
supply piping. All pipe size determinations shall be
based on eighty (80) percent of the reduced pressure
when using Table 6-6.
608.3 Any water system provided with a check
valve, backflow preventer, or any other normally I
closed device that prevents dissipation of building |
pressure back into the water main shall be provided
with an approved, listed, and adequately sized
expansion tank or other approved device having a
similar function to control thermal expansion. Such
expansion tank or other approved device shall be
installed on the building side of the check valve,
backflow preventer, or other device and shall be
sized and installed in accordance with the manur
facturer's recommendation.
Any w^ater system containing storage water
heating equipment shall be provided with an
approved, listed, adequately sized combination
pressure and temperature relief valve, except for
listed nonstorage instantaneous heaters having an
inside diameter of not more than three (3) inches (80
mm). Each such approved combination temperature
and pressure relief valve shall be installed on the
water-heating device in an approved location based
on its listing requirements and the manufacturer's
instructions. Each such combination temperature
and pressure relief valve shall be provided with a
drain as required in Section 608.5.
608.4 Each pressure relief valve shall be an
approved automatic type with drain, and each such
relief valve shall be set at a pressure of not more than
one hundred fifty (150) pounds per square inch (1035
103
608.4 - 609.6
UNIFORM PLUMBING CODE
kPa). No shutoff valve shall be installed between the
relief valve and the system or in the drain line.
608.5 Relief valves located inside a building shall be
provided with a drain, not smaller than the relief
valve outlet, of galvanized steel, hard-drawn copper
piping and fittings, CPVC, or listed relief valve drain
tube with fittings that will not reduce the internal
bore of the pipe or tubing (straight lengths as
opposed to coils) and shall extend from the valve to
the outside of the building, with the end of the pipe
not more than two (2) feet (610 mm) nor less than six
(6) inches (152 mm) above the ground or the flood
level of the area receiving the discharge and pointing
downward. Such drains may terminate at other
I approved locations. Relief valve drains shall not
' terminate in a building's crawl space. No part of
such drain pipe shall be trapped or subject to
freezing. The terminal end of the drain pipe shall not
be threaded.
608.6 Any water-heating device connected to a
separate storage tank and having valves between
said heater and tank shall be provided with an
approved water pressure relief valve.
608.7 Vacuum Relief Valves. Where a hot-water
storage tank or an indirect water heater is located at
an elevation above the fixture outlets in the hot-
water system, a vacuum relief valve shall be installed
on the storage tank or heater.
609.0 Installation, Testing, Unions, and Location.
609.1 installation. All water piping shall be
adequately supported in accordance with Section
314.0. Burred ends shall be reamed to the full bore of
the pipe or tube. Changes in direction shall be made
by the appropriate use of fittings, except that
changes in direction in copper tubing may be made
with bends, provided that such bends are made with
bending equipment that does not deform or create a
loss in the cross-sectional area of the tubing. Changes
in direction are allowed with flexible pipe and
tubing without fittings in accordance with the
manufacturer's installation instructions. Provisions
shall be made for expansion in hot-water piping. All
piping, equipment, appurtenances, and devices shall
be installed in a workmanlike marvner in conformity
with the provisions and intent of the code. All water
service yard piping shall be at least twelve (12)
inches (305 mm) below the average local frost depth.
The minimum cover shall be twelve (12) inches (305
mm) below finish grade.
609.2 Water pipes shall not be run or laid in the
same trench as building sewer or drainage piping
constructed of clay or materials that are not
approved for use within a building unless both of
the following conditions are met:
609.2.1 The bottom of the water pipe, at all
points, shall be at least twelve (12) inches (305
mm) above the top of the sewer or drain line.
609.2.2 The water pipe shall be placed on a
solid shelf excavated at one side of the common
trench with a minimum clear horizontal distance
of at least twelve (12) inches (305 mm) from the
sewer or drain line.
Water pipes crossing sewer or drainage
piping constructed of clay or materials that are
not approved for use within a building shall be
laid a minimum of twelve (12) inches (305 mm)
above the sewer or drain pipe.
609.3 Water piping installed within a building and
in or under a concrete floor slab resting on the
ground shall be installed in accordance with the
following requirements:
609.3.1 Ferrous piping shall have a protective
coating of an approved type, machine applied
and conforming to recognized standards. Field
wrapping shall provide equivalent protection
and shall be restricted to those short sections
and fittings necessarily stripped for threading.
Zinc coating (galvanizing) shall not be deemed
adequate protection for piping or fittings.
Approved nonferrous piping shall not be
required to be wrapped.
609.3.2 Copper tubing shaU be installed without
joints where possible. Where joints are permitted,
they shall be brazed, and fittings shall be
wrought copper.
Note: For the purpose of this section, "within the
building" shall mean within the fixed limits of
the building foundation.
609.4 Testing. Upon completion of a section or of
the entire hot and cold water supply system, it shall
be tested and proved tight under a water pressure
not less than the working pressure under which it is
to be used. The water used for tests shall be obtained
from a potable source of supply. Except for plastic
piping, a fifty (50) poiind-per-square-tnch (344.5 kPa)
air pressure may be substituted for the water test. In
either method of test, the piping shall withstand the
test without leaking for a period of not less than
fifteen (15) minutes.
609.5 Unions. Unions shall be installed in the water
supply piping within twelve (12) inches (305 mm) of
regulating equipment, water heating, conditioning
tanks, and similar equipment that may require
service by removal or replacement in a maimer that
will facilitate its ready removal.
609.6 Location. Except as provided in Section 609.7,
no building supply shall be located in any lot other
than the lot that is the site of the building or
structure served by such building supply.
104
WATER SUPPLY AND DISTRIBUTION
609.7-610.2
609.7 Nothing contained in this code shall be
construed to prohibit the use of all or part of an
abutting lot to:
609.7.1 Provide access to connect a building
supply to an available public water service when
proper cause and legal easement not in violation
of other requirements have been first established
to the satisfaction of the Authority Having
Jurisdiction.
609.7.2 Provide additional space for a building
supply when proper cause, transfer of owner-
ship, or change of boundary not in violation of
other requirements have been first established to
the satisfaction of the Authority Having
Jurisdiction. The instrument recording such
action shall constitute an agreement with the
Authority Having Jurisdiction, which shall
clearly state and show that the areas so joined or
used shall be maintained as a unit during the
time they are so used. Such an agreement shall
be recorded in the office of the County Recorder
as a part of the conditions of ownership of said
properties, and shall be binding on all heirs,
successors, and assigns to such properties. A
copy of the instrument recording such pro-
ceedings shall be filed with the Authority
Having Jurisdiction.
609.8 Low-Pressure Cutoff Required on Booster
Pumps for Water Distribution Systems. When a
booster pump - excluding a fire pump - is connected
to a water service or underground water pipe, a low-
pressure cutoff switch on the inlet side of the pump
shall be installed within five (5) feet (1,524 mm) of
the inlet. The cutoff switch shall be set for not less
than ten (10) psi (68.9 kPa). A pressure gauge shall be
installed between the shutoff valve and the pump.
609.9 Disinfection of Potable Water System. New
or repaired potable w^ater systems shall be disinfected
prior to use whenever required by the Authority
Having Jurisdiction. The method to be followed shall
be that prescribed by the Health Authority or, in case
no method is prescribed by it, the following:
609.9.1 The pipe system shall be flushed with
clean, potable water until only potable water
appears at the points of outlet.
609.9.2 The system or parts thereof shall be
filled with a water-chlorine solution containing
at least fifty (50) parts per million of chlorine,
and the system or part thereof shall be valved-
off and allowed to stand for twenty-four (24)
hours; or, the system or part thereof shall be
filled with a water-chlorine solution containing at
least two hundred (200) parts per million of
chlorine and allowed to stand for three (3) hours.
609.9.3 Following the allowed standing time,
the system shall be flushed with clean, potable
water until the chlorine residual in the water
coming from the system does not exceed the
chlorine residual in the flushing water.
609.9.4 The procedure shall be repeated if it is
shown by bacteriological examination made by
an approved agency that contamination persists
in the system.
609.10 Water Hammer. All building water supply
systems in which quick-acting valves are installed
shall be provided with devices to absorb the hammer
caused by high pressures resulting from the quick
closing of these valves. These pressure-absorbing
devices shall be approved mechanical devices. Water
pressure-absorbing devices shall be installed as close
as possible to quick-acting valves.
609.10.1 IVIechanical Devices. When listed
mechanical devices are used, the manufacturers'
specifications as to location and method of
installation shall be followed.
610.0 Size of Potable Water Piping.
610.1 The size of each water meter and each
potable water supply pipe from the meter or other
source of supply to the fixture supply branches,
risers, fixtures, connections, outlets, or other uses
shall be based on the total demand and shall be
determined according to the methods and
procedures outlined in this section. Water piping
systems shall be designed to ensure that the
maximum velocities allowed by the code and the
applicable standard are not exceeded.
610.2 Whenever a water filter, water softener,
backflow prevention device, or similar device is
installed in any water supply line, the pressure loss
through such devices shall be included in the
pressure loss calculations of the system, and the
water supply pipe and meter shall be adequately
sized to provide for any such pressure loss.
No water filter, water softener, backflow
prevention device, or similar device regulated by this
code shall be installed in any potable water supply
piping when the installation of such device produces
an excessive pressure drop in any such water supply
piping. In the absence of specific pressure drop
information, the diameter of the inlet or outlet of any
such device or its cormecting piping shall not be less
than the diameter of such water distribution piping
to the fixtures served by the device.
All such devices shall be of a type approved by
the Authority Having Jurisdiction and shall be tested
for flow rating and pressure loss by an approved
laboratory or recognized testing agency to standards
consistent with the intent of this chapter.
105
610.3-610.10
UNIFORM PLUMBING CODE
61 0.3 The quantity of water required to be supplied
to every plumbing fixture shall be represented by
fixture units, as shown in Table 6-5. Equivalent
fixture values shown in Table 6-5 include both hot
and cold water demand.
610.4 Systems within the range of Table 6-6 may be
sized from that table or by the method set forth in
Section 610.5.
Listed parallel water distribution systems shall
be installed in accordance with their listing, but at no
time shall any portion of the system exceed the
maximum velocities allowed by the code.
610.5 Except as provided in Section 610.4, the size of
each water piping system shall be determined in
accordance with the procedure set forth in Appendix
A. For alternate methods of sizing water supply
systems, see Appendix L.
610.6 Except where the type of pipe used and the
water characteristics are such that no decrease in
capacity due to length of service (age of system) may
be expected, all friction-loss data shall be obtained
from the "Fairly Rough" or "Rough" charts in
Appendix A of this code. Friction or pressure losses
in water meter, valve, and fittings shall be obtained
from the same sources. Pressure losses through
water-treating equipment, backflow prevention
devices, or other flow-restricting devices shall be
computed as required by Section 610.2.
610.7 On any proposed water piping installation
sized using Table 6-6, the following conditions shall
be determined:
(1) Total number of fixture units as determined
from Table 6-5, Equivalent Fixture Units, for
the fixtures to be installed.
(2) Developed length of supply pipe from meter
to most remote outlet.
(3) Difference in elevation between the meter or
other source of supply and the highest
fixture or outlet.
(4) Pressure in the street main or other source of
supply at the locality where the installation
is to be made.
(5) In localities where there is a fluctuation of
pressure in the main throughout the day,
the water piping system shall be designed
on the basis of the minimum pressure
available.
610.8 Size of Meter and Building Supply Pipe
Using Table 6-6. The size of the meter and the
building supply pipe shall be determined as follows:
(1) Determine the available pressure at the
water meter or other source of supply.
(2) Subtract one-half (1/2) pound per square
inch pressure (3.4 kPa) for each foot (305
mm) of difference in elevation between such
source of supply and the highest water supply
outlet in the building or on the premises.
(3) Use the "pressure range" group within
which this pressure will fall using Table 6-6.
(4) Select the "length" column that is equal to
or longer than the required length.
(5) Follow down the column to a fixture unit
value equal to or greater than the total
number of fixture units required by the
installation.
(6) Having located the proper fixture unit value
for the required length, sizes of meter and
buildingsupply pipe as found in the two
left-hand columns shall be applied.
No building supply pipe shall be less
than three-quarter (3/4) inch (20 mm) in
diameter.
610.9 Size of Branches. When Table 6-6 is used,
the minimum size of each branch shall be
determined by the number of fixture units to be
served by that branch, the total developed length of
the system, and the meter and street service size as
per Section 610.8. No branch piping is required to
be larger in size than that required by Table 6-6 for
the building supply pipe.
610.10 Sizing for Flushometer Valves. When
using Table 6-6 to size water supply systems serving
flushometer valves, the number of flushometer
fixture units assigned to every section of pipe,
whether branch or main, shall be determined by the
number and category of flushometer valves served
by that section of pipe, in accordance with Table 6-7.
Piping supplying a flushometer valve shall not be
less in size than the valve inlet.
When using Table 6-7 to size water piping, care must
be exercised to assign flushometer fixture units
based on the number and category of fixtures served.
In the exam.ple below, fixture units assigned to each
Sizing Method
Example Using TABLE 6-7
Public Use Fixtures
LAV LAV UR UR WC WC
J L_l I L_J
LAV LAV UR UR WC WC
I I I I I I
H I
LAV UR WC LAV UR WC
_J I I I I I
R Q P O N
106
WATER SUPPLY AND DISTRIBUTION
610.10-611.4
section of pipe are computed as follows: Note: Each
capital letter refers to the section of pipe above it,
unless otherwise shown.
A: 1WC = 40F.U.
B: 2 WC = 70 F.U.
C: 2 WC (70) + 1 UR (20) = 90 F.U.
D: 2 WC (70) + 2 UR (35) = 105 F.U.
E: 2 WC (70) + 2 UR (35) + 1 LAV (1) = 106 F.U.
F: 2 WC (70) + 2 UR (35) + 2 LAV (2) = 107 F.U.
G: 1 LAV = 1 F.U.
H: 2 LAV = 2 F.U.
I: 2 LAV (2) + 1 UR (20) = 22 F.U.
J: 2 LAV (2)+ 2 UR (35) = 37 F.U.
K: 2 LAV (2) + 2 UR (35) + 1 WC (40) = 17 F.U.
L: 2 LAV (2) + 2 UR (35) + 2 WC (70) = 107 F.U.
M: 4 WC (105) + 4 UR (53) + 4 LAV (4) = 162 F.U.
N: 1WC = 40F.U.
O: 1 WC (40) + 1 UR (20) = 60 F.U.
P: 1 WC (40) + 1 UR (20) + 1 LAV (1) = 61 F.U.
Q: 2 WC (70) + 1 UR (20) + 1 LAV (1) = 91 F.U.
R: 2 \NC (70) + 2 UR (35) + 1 LAV (1) = 106 F.U.
S: 2 WC (70) + 2 UR (35) + 2 LAV (2) = 107 F.U.
T: 6 WC (125) + 6 UR (63) + 6 LAV (6) = 194 F.U.
610.11 Sizing Systems for Flushometer Tanks.
The size of branches and mains serving flushometer
tanks shall be consistent with the sizing procedures
for flush tank water closets.
610.12 Sizing for Velocity. Water piping systems
shall not exceed the maximum velocities listed in this
section or Appendix A.
610.12.1 Copper Tube Systems. Maximum
velocities in copper and copper alloy tube and
fitting systems shall be limited to a maximum of
eight (8) feet per second (fps) (2.4 m.ps) in cold
water and five (5) fps in hot water (1.52 mps).
610.12.2 Tubing Systems Using Copper
Alloy Fittings. Maximum velocities through
copper alloy fittings in tubing other than copper
shall be limited to a maximum of eight (8) feet
per second (fps) (2.4 mps) in cold water and five
(5) fps in hot water (1.52 mps).
610.13 Exceptions. The provisions of this section
relative to size of water piping shall not apply to the
following:
(1) Water supply piping systems designed in
accordance with recognized engineering
procedures acceptable to the Authority
Having Jurisdiction.
(2) Alteration of or n\inor additions to existing
installations, provided the Authority Having
Jurisdiction finds that there will be
an adequate supply of water to operate all
fixtures.
(3) Replacement of existing fixtures or
appliances.
(4) Piping that is part of fixture equipment.
(5) Unusual conditions where, in the judgment
of the Authority Having Jurisdiction, an
adequate supply of water is provided to
operate fixtures and equipment.
(6) Nonpotable waterlines as defined in
Sections 601.2.2 and 601.2.3.
(7) The size and material of irrigation water
piping installed outside of any building or
structure and separated from the potable
water supply by means of an approved
airgap or backflow prevention device is not
regulated by this code. The potable water
piping system supplying each such
irrigation system shall be adequately sized
as required elsewhere in this chapter to
deliver the full connected demand of both
the domestic use and the irrigation systems.
611.0 Drinking Water Treatment Units.
611.1 Compliance with Standard. Drinking water
treatment units shall meet the requirements of the
appropriate standard referenced in Table 14-1.
611.2 Airgap Discharge. Discharge from all
drinking water treatment units shall enter the
drainage system through an airgap or an airgap
device that meets the requirements of the appropriate
standards referenced in Table 14-1.
61 1 .3 Connection Tubing. The tubing to and from
drinking water treatment units shall be of a size and
material as recommended by the manufacturer. The
tubing shall comply with the requirements of the
appropriate standards referenced in Table 14-1.
61 1 .4 Sizing of Residential Softeners. Residential-
use water softeners shall be sized per Table 6-8.
107
Table 6-5
UNIFORM PLUMBING CODE
Inch
mm
1/2
15
3/4
20
1
25
TABLE 6-5
Water Supply Fixture Units (WSFU) and Minimum Fixture Branch Pipe Sizes'
Minimum
Fixture Branch Private
Appliances, Appurtenances or Fixtures' Pipe Size"
Bathtub or Combination Bath/Shower (fill) 1/2" 4.0
3/4" Bathtub Fill Valve 3/4" 10.0
Bidet 1/2" 1.0
Clothes washer 1/2" 4.0
Dental Unit, cuspidor 1/2"
Dishwasher, domestic 1/2" 1.5
Drinking Fountain or Watercooler 1/2" 0.5
Hose Bibb... 1/2" 2.5
Hose Bibb, each additional' 1/2" 1.0
Lavatory 1/2" 1.0
Lawn Sprinkler, each head' 1 .0
Mobile Home, each (minimum) 12.0
Sinks
Bar ; 1/2" 1.0
Clinic Faucet 1/2"
Clinic Flushometer Valve
with or without faucet 1"
Kitchen, domestic 1/2" 1 .5
Laundry ..: 1/2" 1.5
Service or Mop Basin 1/2" 1.5
Washup, each set of faucets.......... ...1/2"
Shower, per head 1/2" 2.0
Urinal, 1 .0 GPF Flushometer Valve 3/4" See Footnote '
Urinal, greater than 1.0 GPF Flushometer Valve 3/4" See Footnote '
Urinal, flush tank 1/2" 2.0
Washfountain, circular spray 3/4"
Water Closet, 1.6 GPF Gravity Tank 1/2" 2.5
Water Closet, 1.6 GPF Flushometer Tank 1/2" 2.5
WaterCloset, 1.6 GPF Flushometer Valve 1" SeePootnote'
Water Closet, greater than 1 .6 GPF Gravity Tank 1/2" 3.0
Water Closet, greater than 1 .6 GPF Flushometer Valve 1" seeFootnote^
Public
4.0
10.0
4.0
1.0
1.5
0.5
2.5
1.0
1.0
1.0
2.0
3.0
8.0
1.5
1.5
3.0
2.0
2.0
2.0
4.0
2.5
2.5
5.5
Assembly'
0.75
1.0
3.0
3.5
3.5
7.0
Notes:
' Size of the cold branch pipe, or both the hot and cold branch pipes.
^ Appliances, Appurtenances or Fixtures not included in this Table may be sized by reference to fixtures having a
similar flow rate and frequency of use.
^ The listed fixture unit values represent their load on their cold water service. The separate cold water and hot water
fixture unit value for fixtures having both hot and cold water connections may each be taken as three-quarter ( 3/4)
of the listed total value of the fixture.
" The listed minimum supply branch pipe sizes for individual fixtures are the nominal (I.D.) pipe size.
^ For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons
per minute (GPM), and add it separately to the demand (in GPM) for the distribution system or portions thereof.
^ Assembly [Public Use (See Table 4-1 )].
^ When sizing flushometer systems, see Section 61 0.10.
^ Reduced fixture unit loading for additional hose bibbs is to be used only when sizing total building demand and for
pipe sizing when more than one hose bibb is supplied by a segment of water-distributing pipe. The fixture branch to
each hose bibb shall be sized on the basis of 2.5 fixture units.
108
WATER SUPPLY AND DISTRIBUTION
Table 6-6
TABLE 6-6
Fixture Unit Table for Determining Water Pipe and IVIeter Sizes
Pressure Range - 30 to 45 psi (207 to 310 kPa)
Meter Building
and Supply
Street and
Service, Branches,
Inches Inches 40
3/4
3/4
3/4
1
3/4
1
1-1/2
1
1-1/2
2
1
1-1/2
2
2
(12)
6
16
29
36
-I in***
3/4
1
1
1-1/4 36
1-1/4 54
1-1/4 78
1-1/2 85
1-1/2 150
1-1/2 151
2 85
2 220
2 370
2-1/2 445
60
(18)
5
16
25
31
33
47
68
84
124
129
85
205
327
418
80
(24)
4
14
23
27
31
42
57
79
105
129
85
190
292
390
100
(30)
3
12
21
25
28
38
48
65
91
110
85
176
265
370
Maximum Allowable Length in Feet (meters)
150
(46)
2
9
17
20
24
32
38
56
70
80
85
155
217
330
200
(61)
1
6
15
17
23
28
32
48
57
64
85
138
185
300
250
(76)
1
5
13
15
21
25
28
43
49
53
82
127
164
280
300
(91)
1
5
12
13
19
23
25
38
45
46
80
120
147
265
400
(122)
4
10
12
17
19
21
32
36
38
66
104
124
240
500
(152)
4
8
10
16
17
18
28
31
32
61
85
96
220
Inch
mm
1/2
15
3/4
20
1
25
1-1/4
32
1-1/2
40
2
50
2-1/2
65
600
(183)
3
6
8
13
14
15
26
26
27
57
70
70
198
700
(213)
2
6
6
12
12
12
22
23
23
52
61
61
175
800 900 1000
(244) (274) (305)
2 2 1
6 6 6
6 6 6
12 11 11
12 11 11
12 11 11
21 20 20
21 20 20
21 20 20
49 46 43
57 54 51
57 54 51
158 143 133
Pressure Range - 46 to
3/4 1/2***
3/4
3/4
1
3/4
1
1-1/2
1
1-1/2
2
1
1-1/2
2
2
3/4
1
1
1-1/4
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
2
2
2
2-1/2
7
20
39
39
39
78
78
85
151
151
85
370
370
654
60 psi
7
20
39
39
39
78
78
85
151
151
85
370
370
640
(317 to
6
19
36
39
39
76
78
85
151
151
85
340
370
610
414 kPa)^
5
17
33
36
39
67
78
85
151
151
85
318
370
580
4
14
28
30
39
52
66
85
128
150
85
272
368
535
3
11
23
25
39
44
52
85
105
117
85
240
318
500
2
9
21
23
34
39
44
80
90
98
85
220
2
8
19
20
32
36
39
67
78
84
85
198
280 250
470 440
1
6
17
18
27
30
33
55
62
67
85
170
205
400
1
5
14
15
25
27
29
49
52
55
85
1
4
12
12
22
24
24
41
42
42
85
150 135
165 142
365 335
4
10
10
19
20
20
37
38
38
85
123
123
315
3
9
9
19
19
19
34
35
35
85
110
110
285
3
8
8
17
17
17
32
32
32
83
102
102
3
8
8
16
16
16
30
30
30
80
94
94
267 250
Pressure Range - Over 60 psi (414
3/4
3/4
3/4
1
3/4
1
1-1/2
1
1-1/2
2
1
1-1/2
2
2
7
20
39
39
1/2**^
3/4
1
1
1-1/4 39
1-1/4 78
1-1/4 78
1-1/2 85
1-1/2 151
1-1/2 151
2 85
2 370
2 370
2-1/2 654
7
20
39
39
39
78
78
85
151
151
85
370
370
654
7
20
39
39
39
78
78
85
151
151
85
370
370
654
kPa)*
6
20
39
39
39
78
78
85
151
151
85
370
370
654
5
17
35
38
39
74
78
85
151
151
85
360
370
654
4
13
30
32
39
62
74
85
151
151
85
335
370
650
3
11
27
29
39
53
65
85
130
142
85
3
10
24
26
39
47
54
85
113
122
85
305 282
370 340
610 570
2
8
21
22
34
39
43
81
88
98
85
244
288
510
1
7
17
18
28
31
34
64
73
82
85
1
6
14
14
26
26
26
51
51
64
85
212 187
245 204
460 430
1
6
13
13
25
25
25
48
51.
51
85
172
172
404
1
5
12
12
23
23
23
46
46
46
85
153
153
380
1
4
12
12
22
22
22
43
43
43
85
141
141
4
11
11
21
21
21
40
40
40
85
129
129
356 329
'*Available static pressure after head loss.
''**Building supply, three-quarter (3/4) inch (20 mm) nominal size minimum.
109
Table 6-7 - Table 6-8
UNIFORM PLUMBING CODE
Table 6-7
Flushometer Fixture Units for Water Sizing Using
Table 6-5
Fixture Category: Water Closet w/ Flushometer Valves
Individual
Fixture Units Assigned
Number of
Fixture Units
for Water Closets and
Flushometer
Assigned in
Similar 10-Unit Fixtures
Valves
Decreasing Value
in Accumulative Values
1
40
40
2
30
70
3
20
90
4
15
105
5 or more
10 each
115 plus 10 for each
additional fixture
in excess of 5
Fixture Category: Urinals w/ Flushometer Valves
Individual
Fixture Units Assigned
Number of
Fixture Units
for Urinals and
Flushometer
Assigned in
Similar 5-Urut Fixtures
Valves
Decreasing Value
in Accumulative Values
1
20
20
2
. 15
35
3
10
45
4
.8
53
5 or more
5 each
58 plus 5 for each
additional fixture
in excess of 5
TABLE 6-8
Sizing of Residential Water Softeners
Required Size of
Softener Connection
Number of Bathroom
Groups Served^
3/4 in.
lin.
up to 2
.3
Up to 4
^ Installation of a kitchen sink and dishwasher,
laundry tray, and automatic clothes washer
permitted without additional size increase.
^ An additional water closet and lavatory permitted.
^ Over four bathroom groups, the softener size shall
be engineered for the specific installation.
See also Appendix A, Recommended Rules for Sizing the
Water Supply System, and Appendix L, Alternate
Plumbing Systejns, for alternate methods of sizing water
supply systems.
110
CHAPTER 7
SANITARY DRAINAGE
Part I - Drainage Systems.
701.0 Materials.
701.1 Drainage piping shall be cast iron, galvanized
steel, galvanized wrought iron, lead, copper, brass,
I Stainless Steel 304 or 316L, Schedule 40 ABS DWV,
Schedule 40 PVC DWV, extra-strength vitrified clay
pipe, or other approved materials having a smooth and
uniform bore, except that:
701.1.1 No galvanized wrought-iron or
galvanized steel pipe shall be used underground
and shall be kept at least six (6) inches (152 mm)
aboveground.
701.1.2 ABS and PVC DWV piping installations
shall be installed in accordance with IS 5, IS 9,
and Chapter 15 "Firestop Protection/' Except for
individual single-family dwelling units,
materials exposed within ducts or plenums shall
have a flame-spread index of not more than 25
and a smoke-developed index of not more than
50, when tested in accordance with the Test for
Surface - Burning Characteristics of the Building
Materials. (See the Building Code standards
based on ASTM E-84 and ANSI/UL 723.)
701.1.3 No vitrified clay pipe or fittings shall
be used aboveground or where pressurized by
a pump or ejector. They shall be kept at least
twelve (12) inches (305 mm) belowground.
701.1.4 Copper tube for drainage and vent
piping shall have a weight of not less than that
of copper drainage tube type DWV.
701.1.5 Stainless steel 304 pipe and fittings shall
not be installed underground and shall be kept
at least 6 inches (152 mm) aboveground.
701 .2 Drainage fittings shall be of cast iron, malleable
iron, lead, brass, copper, ABS, PVC, vitrified clay,
stainless steel 304 and 31 6L (304 shall not be installed
underground and shall be kept at least 6 inches (152
mm) aboveground), or other approved materials
having a smooth interior waterway of the same
diameter as the piping served, and all such fittings
shall be compatible with the type of pipe used.
701 .2.1 Fittings on screwed pipe shall be of the
recessed drainage type. Burred ends shall be
reamed to the full bore of the pipe.
701 .2.2 The threads of drainage fittings shall be
tapped so as to allow one-quarter (1/4) inch per
foot (20.9 mm/m) grade.
701 .2.3 Fittings used for drainage shall be of the
drainage type, have a smooth interior water-
way, and be constructed so as to allow one
fourth (1/4) inch per foot (20.9 mm/m) grade.
701.3 Lead.
See Table 14-1. Sheet lead shall be not less than the
following:
For safe pans - not less than four (4) pounds per
square foot (19.5 kg/m^) or 1/16 inch (1.6 mm) thick.
TABLE 7-1
Caulking Ferrules
Pipe Size
(inches)
Inside
Diameter
(inches)
Length
(inches)
l\1inimum
Weight Each
lb. oz.
2
2-1/4
4-1/2
1
3
3-1/4
4-1/2
1
12
4
4-1/4
4-1/2
2
8
Caulking Ferrules (Metric)
Pipe Size
(mm)
Inside
Diameter
(mm)
Length
(mm)
IVIinimum
Weight Each
(kg)
50
80
100
57
83
108
114
114
114
0.454
0.790
1.132
TABLE 7-2
Soldering Bushings
Pipe Size
(inches)
l\/linimum
Weight Each
lb. oz.
Pipe Size
(inches)
l\1inimum
Weight Each
lb. oz.
1-1/4
1-1/2
2
6
.0 8
14
2-1/2
3
4
1 6
2
3 8
Soldering Bushings (Metric)
Pipe Size
(mm)
l\/linimum
Weight Each
(kg)
Pipe Size
(mm)
Minimum
Weight Each
(kg)
32
0.168
65
0.622
40
0.224
80
0.908
50
0.392
100
1.586
111
Table 7-3
UNIFORM PLUMBING CODE
TABLE 7-3
Drainage Fixture Unit Values (DFU)
Min. Size
Trap and
Plumbing Appliance, Appurtenance, or Fixture Trap Arm'
Bathtub or Combination Bath/Shower 1-1/2"
Bidet ..1-1/4"
Bidet 1-1/2"
Clothes Washer, domestic, standpipe' 2"
Dental Unit, cuspidor 1-1/4"
Dishwasher, domestic, with independent drain 1-1/2"'
Drinking Fountain or Watercooler (per head) 1-1/4"
Food-Waste-Grinder, commercial 2"
Floor Drain, emergency 2"
Floor Drain (for additional sizes see Section 702) 2"
Shower, single-head trap 2"
Multi-head, each additional 2"
Lavatory, single 1-1/4"
Lavatory, in sets of two or three 1-1/2"
Washfountain 1-1/2"
Washfountain 2"
Mobile Home, trap 3"
Receptor, indirect waste" ..1-1/2"
Receptor, indirect waste" 2"
Receptor, indirect waste' 3"
Sinks
Bar.. 1-1/2"
Bar 1-1/2"'
Clinical 3"
Commercial with food waste 1-1/2"'
Special Purpose 1-1/2"
Special Purpose 2"
Special Purpose 3"
Kitchen, domestic 1-1/2"'
(with or without food-waste grinder and/or dishwasher)
Laundry 1-1/2"
(with or without discharge from a clothes washer)
Service or Mop Basin '. 2"
Service or Mop Basin 3"
Service, flushing rim 3"
Wash, each set of faucets
Urinal, integral trap 1 .0 GPF' 2"
Urinal, integral trap greater than 1.0 GPF 2"
Urinal, exposed trap 1-1/2"'
Water Closet, 1 .6 GPF Gravity Tank' 3"
Water Closet, 1 .6 GPF Flushometer Tank' 3"
Water Closet, 1 .6 GPF Flushometer Valve' 3"
Water Closet, greater than 1 .6 GPF Gravity Tank' 3"
Water Closet, greater than 1 .6 GPF Flushometer Valve' 3"
' Indirect waste receptors shall be sized based on the total drainage capacity of the fixtures that drain therein to, in accordance with Table 7-4.
^ Provide a 2" (51 mm) minimum drain.
^ For refrigerators, coffee urns, water stations, and similar low demands.
" For commercial sinks, dishwashers, and similar moderate or heavy demands.
= Buildings having a clothes-washing area with clothes washers in a battery of three (3) or more clothes washers shall be rated at six (6) fixture units each for
purposes of sizing common horizontal and vertical drainage piping.
^ Water closets shall be computed as six (6) fixture units when determining septic tank sizes based on Appendix K of this code.
' Trap sizes shall not be increased to the point where the fixture discharge may be inadequate to maintain their self-scouring properties.
" Assembly [Public Use (See Table 4-1)].
(DFU)
Public
2.0
Inch mm
1-1/4 32
1-1/2 40
2 50
2-1/2 65
3 80
Private
2.0
Assembly'
1.0
2.0
3.0
3.0
3.0
1.0
1.0
2.0
2.0
2.0
0.5
0.5
1.0
3.0
3.0
0.0
0.0
2.0
2.0
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
2.0
2.0
2.0
2.0
2.0
3.0
3.0
12.0
See footnote '-^
See footnote '"
See footnote '
1.0
2.0
2.0
6.0
6.0
3.0
3.0
2.0
3.0
3.0
3.0
4.0
4.0
6.0
6.0
2.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
6.0
6.0
2.0
2.0
2.0
2.0
5.0
2.0
2.0
6.0
2.0
2.0
5.0
3.0
4.0
6.0
3.0
4.0
6.0
3.0
4.0
6.0
4.0
6.0
8.0
4.0
6.0
8.0
112
SANITARY DRAINAGE
701 .3 - 704.4
For flashings or vent terminals - not less
than three (3) pounds per square foot (15 kg/m^) or
1.2 mm thick.
Lead bends and lead traps shall not be less than
one-eighth (1/8) inch (3.2 mm) wall thickness.
701.4 Ferrules and Bushings
701.4.1 Caulking ferrules shall be manufactured
from bronze or copper and shall be in accordance
with Table 7-1.
701 .4.2 Soldering bushings shall be of bronze or
copper in accordance with Table 7-2.
702.0 Fixture Unit Equivalents.
The unit equivalent of plumbing fixtures shown in
Table 7-3 shall be based on the size of the trap
required, and the unit equivalent of fixtures and
devices not shown in Table 7-3 shall be based on the
rated discharge capacity in gpm (gallons per minute)
(liters per second) in accordance with Table 7-4.
Maximum trap loadings for sizes up to four (4)
inches (102 mm) are as follows:
1-1/4 in. (32 mm) — 1 unit
1-1/2 in. (40 mm) — 3 imits
2 in. (50 mm) — 4 units
3 in. (80 mm) — 6 units
4 in. (100 mm) — 8 units
Exception: On self-service laundries.
703.0 Size of Drainage Piping.
703.1 The minimum sizes of vertical and/or
horizontal drainage piping shall be determined from
the total of all fixture units coruiected thereto, and
additionally, in the case of vertical drainage pipes, in
accordance with their length.
703.2 Table 7-5 shows the maximum number of
fixture units allowed on any vertical or horizontal
drainage pipe, building drain, or building sewer of a
given size; the maximum number of fixture units
allowed on any branch interval of a given size; and
the maximum length (in feet and meters) of any
vertical drainage pipe of a given size.
TABLE 7-4
Discharge Capacity in Gallons per Minute
(Liters per Second)
For Intermittent Flow Only
GPM
(L/sec)
Up to 7-1/2 (Up to 0.47) Equals 1 Unit
8 to 15 (0.50 to 0.95) Equals 2 Units
16 to 30 (1.00 to 1.89) Equals 4 Units
31 to 50 (1.95 to 3.15) Equals 6 Units
Discharge capacity for over 50 gallons per minute
(3.15 L/sec.) shall be determined by the Authority
Having Jurisdiction.
For a continuous flow into a drainage system,
such as from a pump, sump ejector, air conditioning
equipment, or similar device, two (2) fixture units
shall be allowed for each gallon per minute (0.06
L/sec.) of flow.
703.3 For alternate method of sizing drainage piping,
see Appendix L.
704.0 Fixture Connections (Drainage).
704.1 Drainage piping shall be provided with
approved inlet fittings for fixture connections,
correctly located according to the size and type of
fixture proposed to be cormected.
704.2 Two fixtures set back-to-back, or side-by-side,
within the distance allowed between a trap and its
vent may be served by a single vertical drainage pipe
provided that each fixture wastes separately into an
approved double-fixture fitting having inlet openings
at the same level.
704.3 Pot sinks, scullery sinks, dishwashing sinks,
silverware sinks, commercial dishwashing machines,
silverware-washing machines, and other similar
fixtures shall be connected directl)/^ to the drainage
system. A floor drain shall be provided adjacent to
the fixture, and the fixture shall be connected on the
sewer side of the floor drain trap, provided that no
other drainage line is connected between the floor
drain waste connection and the fixture drain. The
fixture and floor drain shall be trapped and vented
as required by this code.
704.4 Closet Rings (Closet Flanges).
704.4.1 Closet rings (closet flanges) for water
closets or similar fixtures shall be of an approved
type and shall be bronze, copper, hard lead, cast
iron, galvanized malleable iron, ABS, PVC, or
other approved materials. Each such closet ring
(closet flange) shall be approximately seven (7)
inches (175 mm) in diameter and, when installed,
shall, together with the soil pipe, present a one
and one-half (1-1/2) inch (38 mm) wide flange or
face to receive the fixture gasket or closet seal.
704.4.2 Caulked-on closet rings (closet flanges)
shall be not less than one-fourth (1/4) inch
(6.4mm) thick and not less than two (2) inches
(51mm) in overall depth.
704.4.3 Closet rings (closet flanges) shall be
burned or soldered to lead bends or stubs, shall
be caulked to cast-iron soil pipe, shall be solvent
cemented to ABS and PVC, and shall be screwed
113
Table 7-5 -705.1
UNIFORM PLUMBING CODE
TABLE 7-5
Maximum Unit Loading and Maximum Length of Drainage and Vent Piping
Size of Pipe, inches
1-1/4
1-1/2
2
2-1/2
3
4
5
6
8
10
12
(mm)
(32)
(40)
(50)
(65)
(80)
(100)
(125)
(150)
(200)
(250)
(300)
Maximum Units
Drainage Piping'
Vertical
1
2^
16^
32^
48^
256
600
1,380
3,600
5,600
8,400
Horizontal
1
1
8'
14^
35^
216'
428'
720'
2,640'
4,680'
8,200'
n/laximum Lengtii
Drainage Piping
Vertical, feet
45
65
85
148
212
300
390
510
750
(m)
(14)
(20)
(26)
(45)
(65)
(91)
(119)
(155)
(228)
Horizontal (unlimited)
Vent Piping (See note)
Horizontal and Vertical
Maximum Units
1
8'
24
48
84
256
600
1,380
3,600
Maximum Lengths, feet
45
60
120
180
212
300
390
510
750
(m)
(14)
(18)
(37)
(55)
(65)
(91)
(119)
(155)
(228)
^ Excluding trap arm.
^ Except sinks, urinals, and dishwashers.
^ Except six-unit traps or water closets.
" Only four (4) water closets or six-unit traps allowed on any vertical pipe or stack; and not to exceed three (3) water closets
or six-unit traps on any horizontal branch or drain.
= Based on one-fourth (1/4) inch per foot (20.9 mm/m) slope. For one-eighth (1/8) inch per foot (10.4 mm/m) slope, multiply
horizontal fixture units by a factor of 0.8.
Note: The diameter of an individual vent shall not be less than one and one-fourth (1-1/4) inches (31.8 mm) nor less than
one-haif (1/2) the diameter of the drain to which it is connected. Fixture unit load values for drainage and vent piping shall
be computed from Tables 7-3 and 7-4. Not to exceed one-third (1/3) of the total permitted length of any vent may be
installed in a horizontal position. When vents are increased one (1) pipe size for their entire length, the maximum length
limitations specified in this table do not apply.
or fastened in an approved manner to other
materials.
704.4.4 All such closet rings (closet flanges)
shall be adequately designed and secured to
support fixtures connected thereto.
704.4.5 Closet screws, bolts, washers, and
similar fasteners shall be of brass, copper, or
other listed, equally corrosion-resistant
materials. All such screws and bolts shall be of
adequate size and number to properly support
the fixture installed.
705.0 Joints and Connections.
705.1 Types of Joints.
705.1.1 Caull<ed Joints. Caulked joints for cast-
iron bell-and-spigot soil pipe and other similar
joints shall be firmly packed with oakum or
hemp and filled with molten lead to a depth of
not less than one (1) inch (25.4 mm). The lead
shall be caulked thoroughly at the inside and
outside edges of the joint. After caulking, the
finished joint shall not extend more than one-
eighth (1/8) inch (3.2 mm) below the rim of the
hub. No paint, varnish, or other coatings shall be
permitted on the joining material until after the
joint has been tested and approved. Caulked
joints in cast-iron bell-and-spigot w^ater piping
shall be made with nontoxic materials.
705.1.2 Cement l\/lortar Joints. Except for
repairs and connections to existing lines
constructed with such joints, cement mortar
joints shall be prohibited on building sewers.
705.1.3 Burned Lead Joints. Burned (welded)
lead joints shall be lapped, and the lead shall be
fused together to form a uniform weld at least as
thick as the lead being joined.
705.1.4 Asbestos Cement Sewer Pipe Joints.
Joints in asbestos cement pipe shall be a sleeve
coupling of the same composition as the pipe or
of other approved materials, and sealed with
rubber rings or joined by an approved-type
compression coupling. Joints between asbestos
cement pipe and other approved pipe shall be
made by means of an approved adapter coupling.
705.1.5 Pacl<ing Additives Proliibited. The
addition of leak-sealing additives to joint packing
shall be prohibited.
114
SANITARY DRAINAGE
705.1 - 707.3
705.1.6 Molded Rubber Coupling Joints. When
pipe is joined by means of molded rubber
coupling joints, such joints shall conform to
approved standards and shall not be considered
as slip joints. When required, appropriate rubber
bushings shall be used to allow for any difference
in piping material diameters.
705.1.7 Elastomeric Gasketed and Rubber-Ring
Joints. Elastom^eric gasketed and rubber-ring
joints shall comply with the applicable Installa-
tion Standard listed in Appendix I.
705.1.8 Shielded Coupling Joints. When piping
systems are joined by means of shielded
couplings, such couplings shall conform to
approved standards and shall not be considered
as slip joints.
705.1.9 Hubless Cast-Iron Pipe Joints. Joints for
hubless cast-iron soil pipe and fittings shall
conform to appropriate Installation Standards
listed in Appendix I and shall not be considered
as slip joints.
705.2 Use of Joints.
705.2.1 Clay and Sewer Pipe. Joints in vitrified
clay pipe or between such pipe and metal pipe
shall be made as provided in Section 316.1.5,
705.1.2, 705.1.6, or 705.1.8.
705.2.2 Cast-iron Pipe. Joints in cast-iron pipe
shall be made as provided in Section 316.1.1,
316.1.5, 606.1.2, 705.1.1, 705.1.8, or 705.1.9.
705.2.3 Screw Pipe to Cast Iron. Joints between
wrought iron, steel, brass, or copper pipe and
cast-iron pipe shall be either caulked or threaded
joints made as provided in Section 316.1.1 or
705.1.1, or shall be made with approved adapter
fittings.
705.2.4 Lead to Cast Iron, Wrought iron, or Steel.
Joints between lead and cast-iron, wrought-iron,
or steel pipe shall be made by means of wiped
joints to a caulking ferrule, soldering nipple, or
bushing as provided in Section 316.1.2.
705.3 Special Joints.
705.3.1 Slip Joints. In fixture drains and traps,
slip joints of approved materials may be used in
accordance with their approvals.
705.3.2 Expansion Joints. Expansion joints shall
be accessible, except when in vent piping or
drainage stacks, and may be used where nec-
essary to provide for expansion and contraction
of the pipes.
705.3.3 Ground Joint, Flared, or Ferrule
Connections. Brass or copper groimd joint, flared,
or ferrule-type connections that allow adjustment
of tubing, but provide a rigid joint when made up,
shall not be considered as sUp joints.
706.0 Changes in Direction of Drainage Flow.
706.1 Changes in direction of drainage piping shall
be made by the appropriate use of approved fittings
and shall be of the angles presented by a one-
sixteenth (1/16) bend, one-eighth (1/8) bend, or one-
sixth (1/6) bend, or other approved fittings of
equivalent sweep.
706.2 Horizontal drainage lines, cormecting with a
vertical stack, shall enter through forty-five (45)
degree (0.79 rad) wye branches, sixty (60) degree
(1.05 rad) wye branches, combination wye and 1/8
bend branches, sanitary tee or sanitary tapped tee
branches, or other approved fittings of equivalent
sweep. No fitting having more than one (1) inlet at
the same level shall be used unless such fitting is
constructed so that the discharge from one (1) inlet
cannot readily enter any other inlet. Double sanitary
tees may be used when the barrel of the fitting is at
least two (2) pipe sizes larger than the largest inlet,
(pipe sizes recognized for this purpose are 2 in., 2-
1/2 in., 3 in., 3-1/2 in., 4 in., 4-1/2 in., 5 in., 6 in., etc.)
(50, 65, 80, 90, 100, 115, 125, 150 mm, etc.).
706.3 Horizontal drainage lines connecting with
other horizontal drainage lines shall enter
through forty-five (45) degree (0.79 rad) wye
branches, combination wye and one-eighth (1/8)
bend branches, or other approved fittings of
equivalent sweep.
706.4 Vertical drainage lines connecting with
horizontal drainage lines shall enter through forty-
five (45) degree (0.79 rad) wye branches, combination
wye and one-eighth (1/8) bend branches, or other
approved fittings of equivalent sweep. Sixty (60)
degree (1.05 rad) branches or offsets may be used
only when installed in a true vertical position.
707.0 Cleanouts.
707.1 Each cleanout fitting for cast-iron pipe shall
consist of a cast-iron or brass body and an approved
plug. Each cleanout for galvanized wrought-iron,
galvanized steel, copper, or brass pipe shall consist
of a brass plug as specified in Table 7-6, or a standard
weight brass cap, or an approved ABS or PVC plastic
plug, or an approved stainless steel cleanout or plug. |
Plugs shall have raised square heads or approved
countersunk rectangular slots.
707.2 Each cleanout fitting and each cleanout plug or
cap shall be of an approved type.
707.3 Cleanouts shall be designed to be gas and
watertight.
115
707.4 - 708.0
UNIFORM PLUMBING CODE
707.4 Each horizontal drainage pipe shall be
provided with a cleanout at its upper terminal, and
each run of piping, that is more than one hundred
(100) feet (30,480 mm) in total developed length,
shall be provided with a cleanout for each one
hundred (100) feet (30,480 mm), or fraction thereof,
in length of such piping.
Exceptions:
(1) Cleanouts may be omitted on a horizontal
drain line less than five (5) feet (1524 mm) in
length unless such line is serving sinks or
urinals.
(2) Cleanouts may be omitted on any horizontal
drainage pipe installed on a slope of
seventy- two (72) degrees (1.26 rad) or less
from the vertical angle (angle of one-fifth
(1/5) bend).
(3) Excepting the building drain and its
horizontal branches, a cleanout shall not be
required on any pipe or piping that is
above the floor level of the lowest floor of
the building.
(4) An approved type of two-way cleanout
fitting, installed inside the building wall
near the connection between the building
drain and the building sewer or installed
outside of a building at the lower end of a
building drain and extended to grade, may
be substituted for an upper terminal
cleanout.
707.5 An additional cleanout shall be provided in a
drainage line for each aggregate horizontal change of
direction exceeding one hundred and thirty-five (135)
degrees (2.36 rad).
707.6 Each cleanout shall be installed so that it opens
to allow cleaning in the direction of flow of the soil or
waste or at right angles thereto and, except in the case
of wye branch and end-of-line cleanouts, shall be
installed vertically above the flow line of the pipe.
707.7 Each cleanout extension shall be considered as
drainage piping and each ninety (90) degree (1.6 rad)
cleanout extension shall be extended from a wye-type
fitting or other approved fitting of equivalent sweep.
707.8 Each cleanout for an interceptor shall be
outside of such interceptor.
707.9 Each cleanout, unless installed under an
approved cover plate, shall be above grade, readily
accessible, and so located as to serve the purpose for
which it is intended. Cleanouts located under cover
plates shall be so installed as to provide the clearances
and accessibility required by this section.
707.10 Each cleanout in piping two (2) inches (50
mm) or less in size shall be so installed that there is a
clearance of not less than twelve (12) inches (305
mm) in front of the cleanout. Cleanouts in piping
larger than two (2) inches (50 mm) shall have a
clearance of not less than eighteen (18) inches (457
mm) in front of the cleanout. Cleanouts in under-
floor piping shall be extended to or above the finished
floor or shall be extended outside the building when
there is less than eighteen (18) inches (457 mm)
vertical overall, allowing for obstructions such as
ducts, beams, and piping, and thirty (30) inches of
(762 mm) horizontal clearance from the means of
access to such cleanout. No under-floor cleanout
shall be located more than twenty (20) feet (6096
mm) from an access door, trap door, or crawl hole.
707.1 1 Cleanout fittings shall be not less in size than
those given in Table 7-6.
707.12 Cleanouts shall be provided for pressure
drainage systems as classified under Section 710.7.
707.13 Countersimk cleanout plugs shall be installed
where raised heads may cause a hazard.
707.14 When a hubless blind plug is used for a
required cleanout, the complete coupling and plug
shall be accessible for removal or replacement.
708.0 Grade of Horizontal Drainage Piping.
Horizontal drainage piping shall be run in practical
alignment and a Uniform slope of not less than one-
fourth (1/4) inch per foot (20.9 mm/m) or two (2)
percent toward the point of disposal provided that,
where it is impractical due to the depth of the street
sewer or to the structural features or to the
Table 7-8
Cleanouts
Size of Pipe
Size of Cleanout
Threads
(inches)
(inches)
(per inches)
1-1/2
1-1/2
11-1/2
2
1-1/2
11-1/2
2-1/2
2-1/2
8
3
2-1/2
8
4 & larger
3-1/2
8
TABLE 7-6
Cleanouts (Metric)
Size of Pipe
Size of Cleanout
Threads
(mm)
(mm)
(per 25.4 mm)
40
38
11-1/2
50
38
11-1/2
65
64
8
80
64
8
100 & larger
89
8
116
SANITARY DRAINAGE
708.0-710.9
arrangement of any building or structure to obtain a
slope of one-fourth (1/4) of an inch per foot (20.9
mm/m) or two. (2) percent, any such pipe or piping
four (4) inches (100 mm) or larger in diameter may
have a slope of not less than one-eighth (1/8) of an
inch per foot (10.5 mm/m) or one (1) percent, when
first approved by the Authority Having Jurisdiction.
709.0 Gravity Drainage Required.
Wherever practicable, all plumbing fixtures shall be
drained to the public sewer or private sewage
disposal system by gravity.
710.0 Drainage of Fixtures Located Below the Next
Upstream Manliole or Below the Main Sewer Level.
710.1 Where a fixture is installed on a floor level that
is lower than the next upstream manhole cover of the
public or private sewer, serving such drainage piping,
shall be protected from backflow of sewage by
installing an approved type of backwater valve.
Fixtures on floor levels above such elevation shaU not
discharge through the backwater valve.
710.2 Drainage piping serving fixtures that are
located below the crown level of the main sewer
shall discharge into an approved watertight sump or
receiving tank, so located as to receive the sewage or
wastes by gravity. From such sump or receiving
tank, the sewage or other liquid wastes shall be lifted
and discharged into the building drain or building
sewer by approved ejectors, pumps, or other equally
efficient approved mechanical devices.
710.3 A sewage ejector or sewage pump receiving
the discharge of water closets or urinals:
710.3.1 Shall have a minimum discharge
capacity of twenty (20) gallons (75.7 liters) per
minute.
710.3.2 In single dwelling units, the ejector or
pump shall be capable of passing a one and one-
half (1-1/2) inch (38 mm) diameter solid ball,
and the discharge piping of each ejector or
pump shall have a backwater valve and gate
valve, and be a minimum of two (2) inches
(51mm) in diameter.
710.3.3 In other than single-dwelling imits, the
ejector or pump shall be capable of passing a
two (2) inch (51 mm) diameter solid ball, and the
discharge piping of each ejector or pump shall
have a backwater valve and gate valve, and be a
minimum of three (3) inches (80 mm) in diameter.
710.4 The discharge line from such ejector, pump, or
other mechanical device shall be provided with an
accessible backwater or swing check valve and gate
or ball valve. If the gravity drainage line to which
such discharge line connects is horizontal, the
method of connection shall be from the top through
a wye branch fitting. The gate or ball valve shall be
located on the discharge side of the backwater or
check valve.
Gate or ball valves, when installed in drainage
piping, shall be fuUway type with working parts of
corrosion-resistant metal. Sizes four (4) inches
(100mm) or more in diameter shah have cast-iron
bodies, and sizes less than four (4) inches (100 mm),
cast-iron or brass bodies.
710.5 Building drains or building sewers receiving
discharge from any pump or ejector shall be
adequately sized to prevent overloading. Two (2)
fixture units shall be allowed for each gallon per
minute (0.06 L/s) of flow.
710.6 Backwater valves, gate valves, fullway ball
valves, unions, motors, compressors, air tanks, and
other mechanical devices required by this section
shall be located where they will be accessible for
inspection and repair at all times and, unless
continuously exposed, shall be enclosed in a
masonry pit fitted with an adequately sized
removable cover.
Backwater valves shall have bodies of cast iron,
plastic, brass, or other approved materials; shall have
noncorrosive bearings, seats, and self-aligning discs;
and shall be constructed so as to ensure a positive
mechanical seal. Such backwater valves shaU remain
sufficiently open during periods of low flows to avoid
screening of solids and shall not restrict capacities or
cause excessive turbulence during peak loads. Unless
otherwise listed, valve access covers shall be bolted
type with gasket, and each valve shall bear the
manufachirer's name cast into the body and the cover.
710.7 The drainage and venting systems, in connec-
tion with fixtures, sumps, receiving tanks, and
mechanical waste-lifting devices, shall be installed
under the sarrie requirements as provided for in this
code for gravity systems.
710.8 Sumps and receiving tanks shall be watertight
and shall be constructed of concrete, metal, or other
approved materials. If constructed of poured concrete,
the walls and bottom shall be adequately reinforced
and designed to recognized acceptable standards.
Metal sumps or tanks shall be of such thickness as to
serve their intended purpose and shall be treated
internally and externally to resist corrosion.
710.9 All such sumps and receiving tanks shall be
automatically discharged and, when in any "public
use" occupancy, shall be provided with dual pumps
or ejectors arranged to function alternately in normal
use and independently in case of overload or
mechanical failure. The pumps shall have an audio
and visual alarni, readily accessible, that signals
117
710.9-712.3
UNIFORM PLUMBING CODE
pump failure or an overload condition. The lowest
inlet shall have a minimum clearance of two (2)
inches (51 mm) from the high-water or "starting"
level of the sump.
710.10 Sumps and receiving tanks shall be provided
with substantial covers having a bolt-and-gasket-
type manhole or equivalent opening to permit access
for inspection, repairs, and cleaning. The top shall be
provided with a vent pipe that shall extend
separately through the roof or, when permitted, may
be combined with other vent pipes. Such vent shall
be large enough to maintain atmospheric pressure
within the sump under all normal operating
conditions and, in no case, shall be less in size than
that required by Table 7-5 for the number and type
of fixtures discharging into the sump, nor less than
one and one-half (1-1/2) inches (40 mm) in diameter.
When the foregoing requirements are met and the
vent, after leaving the sump, is combined with vents
from fixtures discharging into the sump, the size of
the combined vent need not exceed that required for
the total number of fixtures discharging into the
sump. No vent from an air-operating sewage ejector
shall combine with other vents.
710.11 Air tanks shall be so proportioned as to be of
equal cubical capacity to the ejectors connected
therewith in which there shall be maintained an air
pressure of not less than two (2) pounds for each foot
(3 kg for each m) of height the sewage is to be raised.
No water-operated ejectors shall be permitted.
710.12 Grinder Pump Ejector. Grinder pumps shall
be permitted to be used.
710.13 Macerating Toilet Systems. Listed macerating
toilet systems shall be permitted as an alternate to a
sewage pump system when approved by the
Authority Having Jurisdiction.
710.13.1 Sumps. The sump shall be water- and
gastight.
710.13.2 Discharge Piping. The discharge piping
shall be sized per manufacturer's instructions
and shall be not less than 3/4 inches (20 mm) in
diameter. The developed length of the discharge
piping shall not exceed the manufacturer's
recommendations. A check valve and fullway-
type shutoff valve shall be located within the
discharge line or internally within the device.
710.13.3 Venting. The plumbing fixtures that
discharge into the macerating device shall be
vented per this code. The sump shall be vented
per manufacturer's instructions and such vent
shall be permitted to connect to the fixture
venting.
71 1.0 Suds Relief.
Drainage connections shall not be made into a
drainage piping system within eight (8) feet (2438
mm) of any vertical to horizontal change of direction
of a stack containing suds-producing fixtures.
Bathtubs, laundries, washing machine standpipes,
kitchen sinks, and dishwashers shall be considered
suds-producing fixtures. Where parallel vent stacks
are required, they shall cormect to the drainage stack
at a point eight (8) feet (2,438 mm) above the lowest
point of the drainage stack.
Exceptions:
(1) Single-family residences.
(2) Stacks receiving the discharge from less than
three (3) stories of plumbing fixtures.
712.0 Testing.
712.1 Media. The piping of the plumbing, drainage,
and venting systems shall be tested with water or air
except that plastic pipe shall not be tested with air.
The Authority Having Jurisdiction may require the
removal of any cleanouts, etc., to ascertain whether
the pressure has reached all parts of the system.
After the plumbing fixtures have been set and their
traps filled with water, they shall be submitted to a
final test.
712.2 Water Test. The water test shall be applied to
the drainage and vent systems either in its entirety or
in sections. If the test is applied to the entire system,
all openings in the piping shall be tightly closed,
except the highest opening, and the system filled with
water to point of overflow. If the system is tested in
sections, each opening shall be tightly plugged,
except the highest opening of the section under test,
and each section shall be filled with water, but no
section shall be tested with less than a ten (10) foot
(3048 mm) head of water. In testing successive
sections, at least the upper ten (10) feet (3048 mm) of
the next preceding section shall be tested, so that no
joint or pipe in the building (except the uppermost
ten (10) feet (3048 nrni) of the system) shall have been
submitted to a test of less than a ten (10) foot (3048
mm) head of water. The water shall be kept in the
system, or in the portion under test, for at least fifteen
(15) minutes before inspection starts. The system shall
then be tight at all points.
712.3 Air Test. The air test shall be made by
attaching an air compressor testing apparatus to any
suitable opening and, after closing all other inlets
and outlets to the system, forcing air into the system
until there is a uniform gauge pressure of five (5)
pounds per square inch (34.5 kPa) or sufficient to
balance a column of mercury ten (10) inches (254
mm) in height. The pressure shall be held without
introduction of additional air for a period of at least
fifteen (15) minutes.
118
SANITARY DRAINAGE
713.0-717.0
Part II - Building Sewers.
713.0 Sewer Required.
713.1 Every building in which plumbing fixtures are
installed and every premises having drainage piping
thereon shall have a connection to a public or private
sewer, except as provided in Sections 101.4.1.3, 713.2,
and 713.4.
713.2 When no public sewer intended to serve any lot
or premises is available in any thoroughfare or right
of way abutting such lot or premises, drainage piping
from any building or works shall be connected to an
approved private sewage disposal system.
713.3 Within the limits prescribed by Section 713.4
hereof, the rearrangement or subdivision into smaller
parcels of a lot that abuts and is served by a public
sewer shall not be deemed cause to permit the
construction of a private sewage disposal system, and
aU plumbing or drainage systems on any such smaller
parcel or parcels shall connect to the public sewer.
713.4 The public sewer may be considered as not
being available when such public sewer or any
building or any exterior drainage facility connected
thereto is located more than two hundred (200) feet
(60.8 m) from any proposed building or exterior
drainage facility on any lot or premises that abuts
and is served by such public sewer.
713.5 No permit shall be issued for the installation,
alteration, or repair of any private sewage disposal
system, or part thereof, on any lot for which a
connection with a public sewer is available.
713.6 On every lot or premises hereafter connected
to a public sewer, all plumbing and drainage systems
or parts thereof on such lot or premises shall be
connected with such public sewer.
Exception: Single-family dwellings and buildings
or structures accessory thereto, existing and
connected to an approved private sewage
disposal system prior to the time of cormecting
the premises to the public sewer may, when no
hazard, nuisance, or insanitary condition is
evidenced and written permission has been
obtained from the Authority Having Jurisdiction,
remain connected to such properly maintained
private sewage disposal system when there is
insufficient grade or fall to permit drainage to
the sewer by gravity.
714.0 Damage to Public Sewer or Private Sewage
Disposal System.
714.1 It shall be unlawful for any person to deposit,
by any means whatsoever, into any plumbing fixture,
floor drain, interceptor, sump, receptor, or device
which is connected to any drainage system, public
sewer, private sewer, septic tank, or cesspool, any
ashes; cinders; solids; rags; flammable, poisonous, or
explosive liquids or gases; oils; grease; and any other
thing whatsoever that would or could cause damage
to the public sewer, private sewer, or private sewage
disposal system.
714.2 No rain, surface, or subsurface water shall be
connected to or discharged into any drainage
system, unless first approved by the Authority
Having Jurisdiction.
714.3 No cesspool, septic tank, seepage pit, or
drainfield shall be coimected to any public sewer or
to any building sewer leading to such public sewer.
714.4 The Authority Having Jurisdiction shall review
before approval, the installation of a commercial food
waste grinder connecting to a private sewage disposal
system.
714.5 An approved-type watertight sewage or
wastewater holding tank, the contents of which, due
to their character, must be periodically removed and
disposed of at some approved off-site location, shall
be installed only when required by the Authority
Having Jurisdiction or the Health Officer to prevent
anticipated surface or subsurface contamination or
pollution, damage to the public sewer, or other
hazardous or nuisance conditions.
715.0 Building Sewer Materials.
715.1 The building sewer, beginning two (2) feet (610
mm) from any building or structure, shall be of such
materials as prescribed in this code. |
715.2 Joining methods and materials shall be as
prescribed in this code.
715.3 Replacement of existing building sewer and
building storm sewers using trenchless methodology
and materials shall be installed in accordance with
lAPMO IS-26.
716.0 Markings.
All pipe, brick, block, prefabricated septic tanks,
prefabricated septic tank or seepage pit covers, or
other parts or appurtenances incidental to the
installation of building sewers or private sewage
disposal systems shall conform to the approval
requirements of Chapter 3 of this code.
717.0 Size of Building Sewers.
The minimum size of any building sewer shall be
determ^ined on the basis of the total number of
TIA
TIA
TIA
TIA
TIA
119
717.0-720.0
UNIFORM PLUMBING CODE
fixture units drained by such sewer, in accordance
with Table 7-8. No building sewer shall be smaller
than the building drain.
For alternate methods of sizing building sewers,
see Appendix L.
718.0 Grade, Support, and Protection of Building
Sewers.
718.1 Building sewers shall be run in practical
alignment and at a uniform slope of not less than
one-fourth (1/4) of an inch per foot (20.9 mm/m)
toward the point of disposal.
Exception: When approved by the Authority
Having Jurisdiction and where it is impractical,
due to the depth of the street sewer or to the
structural features or to the arrangement of any
building or structure, to obtain a slope of one-
fourth (1/4) of an inch per foot (20.9 mm/m),
any such pipe or piping four (4) inches (100 mm)
through six (6) inches (150 mm) may have a
slope of not less than one-eighth (1/8) inch per
foot (10.5 mm/m) and any such piping eight (8)
inches (200 rrmi) and larger may have a slope of
not less than one-sixteenth (1/16) of an inch per
foot (5.3 mm/m).
718.2 Building sewer piping shall be laid on a firm
bed throughout its entire length, and any such
piping laid in made or filled-in ground shall be laid
on a bed of approved materials and shall be properly
supported as required by the Authority Having
Jurisdiction.
71 8.3 No building sewer or other drainage piping or
part thereof, which is constructed of materials other
than those approved for use under or within a
building, shall be installed under or within two (2)
feet (610 mm) of any building or structure, or part
thereof, nor less than one (1) foot (305 mm) below the
surface of the ground. The provisions of this
subsection include structures such as porches and
steps, whether covered or uncovered; brpezeways;
roofed porte cocheres; roofed patios; carports;
covered walks; covered driveways; and similar
structures or appurtenances.
719.0 Cleanouts.
719.1 Cleanouts shall be placed inside the building
near the connection between the building drain and
the building sewer or installed outside the building
at the lower end of the building drain and extended
to grade.
Additional building sewer cleanouts shall be
installed at intervals not to exceed one hundred (100)
feet (30,480 mm) in straight runs and for each
aggregate horizontal change in direction exceeding
one hundred thirty-five (135) degrees (2.36 rad).
719.2 When a building sewer or a branch thereof does
not exceed ten (10) feet (3,048 mm) in length and is a
straight-line projection from a building drain that is
provided with a cleanout, no cleanout will be required
at its point of connection to the building drain.
71 9.3 All required building sewer cleanouts shall be
extended to grade and shall comply with all
appropriate sections of Cleanouts, Section 707.0, for
sizing, construction, and materials. When building
sewers are located under buildings, the cleanout
requirements of Section 707.0 shall apply.
719.4 Each cleanout shall be installed so that it opens
to allow cleaning in the direction of flow of the soil or
waste or at right angles thereto and, except in the case
of wye branch and end-of-line cleanouts, shall be
installed vertically above the flow line of the pipe.
719.5 Cleanouts installed under concrete or asphalt
paving shall be made accessible by yard boxes or by
extending flush with paving with approved materials
and shall be adequately protected.
719.6 Approved manholes may be installed in lieu
of cleanouts, when first approved by the Authority
Having Jurisdiction. The maximum distance
between manholes shall not exceed three hundred
(300) feet (91.4 m).
The inlet and outlet connections shall be made
by the use of a flexible compression joint no closer
than twelve (12) inches (305 mm) to and not farther
than three (3) feet (914 mrn) from the manhole. No
flexible compression joints shall be embedded in the
manhole base.
720.0 Sewer and Water Pipes.
Building sewers or drainage piping of clay or materi-
als that are not approved for use within a building
shall not be run or laid in the same trench as the
water pipes unless both of the following
requirements are met:
(1) The bottom of the water pipe, at all points,
shall be at least twelve (12) inches (305 mm)
above the top of the sewer or drain line.
(2) The water pipe shall be placed on a solid
shelf excavated at one side of the common
trench with a minimum clear horizontal
distance of at least twelve (12) inches (305
mm) from the sewer or drain line.
Water pipes crossing sewer or drainage
piping constructed of clay or materials
that are not approved for use within a
building shall be laid a minimum of twelve
(12) inches (305 mm) above that sewer or
drain pipe.
120
SANITARY DRAINAGE
720.0 - Table 7-8
Note:
For the purpose of this section, "within the
building" shall mean within the fixed limits of
the building foundation.
721.0 Location.
721.1 Except as provided in Section 721.2, no
building sewer shall be located in any lot other than
the lot that is the site of the building or structure
served by such sewer nor shall any building sewer
be located at any point having less than the
minimum distances indicated in Table 7-7.
721.2 Nothing contained in this code shall be
construed to prohibit the use of all or part of an
abutting lot to:
(1) Provide access to cormect a building sewer to an
available public sewer when proper cause and
legal easement, not in violation of other
requirements, has been first established to the
satisfaction of the Authority Having Jurisdiction.
(2) Provide additional space for a building sewer
when proper cause, transfer of ownership, or
change of boundary, not in violation of other
requirements, has been first established to the
satisfaction of the Authority Having Jurisdiction.
The instrument recording such action shall
constitute an agreement with the Authority
Having Jurisdiction and shall clearly state and
show that the areas so joined or used shall be
maintained as a unit during the time they are so
used. Such an agreement shall be recorded in the
office of the County Recorder as part of the
conditions of ownership of said properties, and
shall be binding on all heirs, successors, and
assigns to such properties. A copy of the
instrument recording such proceedings shall be
filed with the Authority Having Jurisdiction.
TABLE 7-7
Minimum Horizontal Distance Required From Building Sewer
Buildings or structures' ..2feet (610mm)
Property line adjoining private
property......... Clear'
Water supply wells .50 feet' (15,240 mm)
Streams.. 50 feet (15,240 mm)
On-site domestic water
service line 1 foot' (305 mm)
Public water main .10 feet'' (3,048 mm)
Note:
' Including porches and steps, whether covered or uncovered; breezewayis; roofed portecocheres; roofed patios; carports;
covered walks; covered driveways; and similar structures or appurtenances.
^ See also Section 313.3.
^ All drainage piping shall clear domestic water supply wells by at least fifty (50) feet (15,240 mm). This distance may be reduced
to not less than twenty-five (25) feet (7,620 mm) when the drainage piping is constructed of materials approved for use within a
building.
" See Section 720.0.
^ For parallel construction.
^ For crossings, approval by the Health Department or Authority Having Jurisdiction shall be required.
TABLE 7-8
Maximum/Minimum Fixture Unit Loading on Building Sewer Piping
Size of Pipe,
Inches (mm)
6 and smaller (150)
8 (200)
10 (250)
12 (300)
Slope, Inches per Foot (mm/m)
1/16(5.3) 1/8(10.5) 1/4(20.9)
(As specified in Table 7-5/No minimum loading)
1,950/i,500 2,800/625 3,900/275
3,400/1 ,600 4,900/675 6,800/300
5,600/1 ,700 8,000/725 1 1 ,200/325
See also Appendix K, Private Sewage Disposal Systems. For alternate methods of sizing drainage piping, see
Appendix L
121
722.0 - 723.0
UNIFORM PLUMBING CODE
722.0 Abandoned Sewers and Sewage Disposal
Facilities.
722.1 Every abandoned building (house) sewer, or
part thereof, shall be plugged or capped in an
approved manner within five (5) feet (1,524 mm) of
the property line.
722.2 Every cesspool, septic tank, and seepage pit
that has been abandoned or has been discontinued
otherwise froni further use, or to which no waste or
soil pipe from a plumbing fixture is connected, shall
have the sewage removed therefrom and be
completely filled with earth, sand, gravel, concrete,
or other approved material.
722.3 The top cover or arch over the cesspool, septic
tank, or seepage pit shall be removed before filling,
and the filling shall not extend above the top of the
vertical portions of the sidewalls or above the level
of any outlet pipe until inspection has been called
and the cesspool, septic tank, or seepage pit has been
inspected. After such inspection, the cesspool, septic
tank, or seepage pit shall be filled to the level of the
top of the ground.
722.4 No person owning or controlling any cesspool,
septic tank, or seepage pit on the premises of such
person or in that portion of any public street, alley, or
other public property abutting such premises, shall
fail, refuse, or neglect to comply with the provisions
of this section or upon receipt of notice so to comply
from the Authority Having Jurisdiction.
722.5 Where disposal facilities are abandoned
consequent to connecting any premises with the
public sewer, the permittee making the connection
shall fill all abandoned facilities as required by the
Authority Having Jurisdiction within thirty (30) days
from the time of connecting to the public sewer.
723.0 Building Sewer Test.
Building sewers shall be tested by plugging the end
of the building sewer at its points of connection with
the public sewer or private sewage disposal system
and completely filling the building sewer with water
from the lowest to the highest point thereof, or by
approved equivalent low-pressure air test. The
building sewer shall be watertight at all points.
122
CHAPTER 8
INDIRECT WASTES
801.0 Indirect Wastes.
801.1 Alrgap or Airbreak Required. All indirect
waste piping shall discharge into the building
drainage system through an airgap or airbreak as set
forth in this code. Where a drainage airgap is
required by this code, the mininium vertical distance
as measured from the lowest point of the indirect
waste pipe or the fixture outlet to the flood-level rim
of the receptor shall be not less than one (1) inch
(25.4 mm).
801.2 Food and Beverage Handling Establishments.
Establishments engaged in the storage, preparation,
selling, serving, processing, or other handling of food
and beverage involving the following equipment that
requires drainage shall provide indirect waste piping
for refrigerators, refrigeration coils, freezers, walk-in
coolers, iceboxes, ice-making machines, steam tables,
egg boilers, coffee urns and brewers, hpt-and-cold
drink disperisers, and similar equipment.
801.2.1 Except for refrigeration coils and ice-
making machines, the minimum size of the
iiidirect waste pipe shall not be smaller than the
drain on the unit, but shall not be smaller than
one (1) inch (25 mm), and the maximum
developed length shall not exceed fifteen (15)
feet (4,572 mm). Indirect waste pipe for ice-
making machines shall not be less than the drain
on the unit, but shall not be less than three-
quarters (3/4) inch (20 mm).
801 .2.2 For walk-in coolers, floor drains may be
connected to a separate drainage line discharging
into an outside receptor. The flood-level rim of
the receptor shall be a minimum of six (6) inches
(152 mm) lower than the lowest floor drain. Such
floor drains shall be trapped and individually
vented. Cleanouts shall be provided at every
ninety (90) degree (1.6 rad) turn and shall be
accessibly located. Such waste shall discharge
through an airgap or airbreak into a trapped and
vented receptor, except that a full-size airgap is
required where the indirect waste pipe may be
imder vacuimi.
801 .2.3 Food-preparation sinks, steam kettles,
potato peelers, ice cream dipper wells, and
similar equipment shall be indirectly connected
to the drainage system by means of an airgap.
Bins, sinks, and other equipment having
drainage connections and used for the storage of
unpackaged ice used for human ingestion, or
used in direct contact with ready-to-eat food,
shall be indirectly connected to the drainage
system by means of an airgap. Each indirect
waste pipe from food-handling fixtures or
equipment shall be separately piped to the
indirect waste receptor and shall not combine
with other indirect waste pipes. The piping from
the equipment to the receptor shall not be
smaller than the drain on the unit, and it shall
not be smaller than one-half (1/2) inch (15 mm).
801.3 Bar and Fountain Sink Traps. Where the
sink in a bar, soda foimtain, or counter is so located
that the trap serving the sink cannot be vented, the
sink drain shall discharge through an airgap or
airbreak (see Section 801.2.3) into an approved
receptor that is vented. The developed length from
the fixture outlet to the receptor shall not exceed five
(5) feet (1524 mm).
801.4 Connections from Water Distribution
System. Indirect waste connections shall be
provided for drains, overflows, or relief pipes from
potable water pressure tanks, water heaters, boilers,
and similar equipment that is connected to the
potable water distribution system. Such indirect
waste connections shall be made by means of a
water-distribution airgap constructed in accordance
with Table 6-3.
801.5 Sterilizers. Lines, devices, or apparatus such
as stills, sterilizers, and similar equipment requiring
waste connections and used for sterile materials shall
be indirectly cormected by means of an airgap. Each
such indirect waste pipe shall be separately piped to
the receptor and shall not exceed fifteen (15) feet
(4,572 mm). Such receptors shall be located in the
same room.
801 .6 Drip or Drainage Outlets. Appliances, devices,
or apparatus not regularly classed as plumbing
fixtures, but which have drip or drainage outlets,
may be drained by indirect waste pipes discharging
into an open receptor through either an airgap or
airbreak (see Section 801.2.1).
802.0 Approvals.
No plumbing fixtures served by indirect waste pipes
or receiving discharge therefrom shall be installed
until first approved by the Authority Having
Jurisdiction.
123
803.0 - 808.0
UNIFORM PLUMBING CODE
803.0 Indirect Waste Piping.
Except as hereinafter provided, the size and
construction of indirect waste piping shall be in
accordance with other sections of this code
applicable to drainage and vent piping. No vent
from indirect waste piping shall combine with any
sewer-connected vent, but shall extend separately to
the outside air. Indirect waste pipes exceeding five
(5) feet (1524 mm), but less than fifteen (15) feet
(4,572 mm) in length shall be directly trapped, but
such traps need not be vented.
Indirect waste pipes less than fifteen (15) feet
(4,572 mm) in length shall not be less than the
diameter of the drain outlet or tailpiece of the fixture,
appliance, or equipment served, and in no case less
than one-half (1/2) inch (15 mm) in size. Angles and
changes of direction in such indirect waste pipes
shall be provided with cleanouts so as to permit
flushing and cleaning.
804.0 Indirect Waste Receptors.
804.1 All plumbing fixtures or other receptors
receiving the discharge of indirect waste pipes shall be
approved for the use proposed and shall be of such
shape and capacity as to prevent splashing or flooding
and shall be located where they are readily accessible
for inspection and cleaning. No standpipe receptor for
any clothes washer shaU extend more than thirty (30)
inches (762 mm), nor less than eighteen (18) inches
(457 mm) above its trap. No trap for any clothes
washer standpipe receptor shall be installed below the
floor, but shall be roughed in not less than six (6)
inches (152 mm) and not more than eighteen (18)
inches (457 mm) above the floor. No indirect waste
receptor shall be installed in any toilet room, closet,
cupboard, or storeroom, nor in any other portion of a
building not in general use by the occupants thereof;
except standpipes for clothes washers may be
installed in toilet and bathroom areas when the
clothes washer is installed in the same room.
804.2 Where water service connections are installed
for a clothes washer, an approved method of waste
disposal shall be provided.
805.0 Pressure Drainage Connections.
Indirect waste connections shall be provided for
drains, overflows, or relief vents from the water
supply system, and no piping or equipment carrying
wastes or producing wastes or other discharges
under pressure shall be directly connected to any
part of the drainage system.
The foregoing shall not apply to any approved
sump pump or to any approved pressure-wasting
plumbing fixture or device when the Authority
Having Jurisdiction has been satisfied that the
drainage system is adequately sized to accommodate
the anticipated discharge thereof.
806.0 Sterile Equipment.
Appliances, devices, or apparatus such as stills,
sterilizers, and similar equipment requiring water
and waste and used for sterile materials shall be
drained through an airgap.
807.0 Appliances.
807.1 Appliances, devices, equipment, or other
apparatus not regularly classed as plumbing fixtures,
which are equipped with pumps, drips, or drainage
outlets, may be drained by indirect waste pipes
discharging into an approved type of open receptor.
807.2 When the condensate waste from air-
conditioning coils discharges by direct cormection to
a lavatory tailpiece or to an approved accessible inlet
on a bathtub overflow, the connection shall be
located in the area controlled by the same person
controlling the air-conditioned space.
807.3 When undiluted condensate waste from a fuel-
burning condensing appliance is discharged into the
drainage system, the material in the drainage system
shall be cast iron, galvanized iron, plastic, or other
materials approved for this use.
Exceptions:
(1) When the above condensate is discharged to
an exposed fixture tailpiece and trap, such
tailpiece and trap may be brass.
(2) Any materials approved in Section 701.0
may be used when data is provided that the
condensate waste is adequately diluted.
807.4 No domestic dishwashing machine shall be
directly connected to a drainage system or food
waste disposer without the use of an approved
dishwasher airgap fitting on the discharge side of the
dishwashing machine. Listed airgaps shall be
installed with the flood-level (FL) marking at or
above the flood level of the sirik or drainboard,
whichever is higher.
808.0 Cooling Water.
When permitted by the Authority Having
Jurisdiction, clean running water used exclusively as a
cooling medium in an appliance, device, or apparatus
may discharge into the drainage system through the
inlet side of a fixture trap in the event that a suitable
fixture is not available to receive such discharge. Such
trap connection shall be by means of a pipe connected
to the inlet side of an approved fixture trap, the upper
end terminating iii a funnel-shaped receptacle set
124
INDIRECT WASTES
808.0-811.2
adjacent, and not less than six (6) inches (152 mm)
above the overflow rim of the fixture.
thereto when the normal water level of. such boiler or
boilers is reduced not less than four (4) inches (102 mm).
809.0 Drinking Fountains.
Drinking fountains may be installed with indirect
wastes.
810.0 Steam and Hot Water Drainage Condensers
and Sumps.
810.1 No steam pipe shall be directly connected to
any part of a plumbing or drainage system, nor shall
any water having a temperature above one hundred
and forty (140)°F (60°C) be discharged under
pressure directly into any part of a drainage system.
Pipes from boilers shall discharge by means of
indirect waste piping, as determined by the
Authority Having Jurisdiction or the boiler
manufacturer's recommendations. Such pipes may
be indirectly connected by discharging into an open
or closed condenser or an intercepting sump of an
approved type that will prevent the entrance of
steam or such water under pressure into the
drainage system. All closed condensers or sumps
shall be provided with a vent that shall be taken off
the top and extended separately, full size above the
roof. All condensers and sumps shall be properly
trapped at the outlet with a deep seal trap extending
to within six (6) inches (152 mm) of the bottom of the
tank. The top of the deep seal trap shall have a three-
fourths (3/4) inch (19.1 mm) opening located at the
highest point of the trap to serve as a siphon breaker.
Outlets shall be taken off from the side in such a
manner as to allow a waterline to be maintained that
will permanently occupy not less than one-half (1/2)
the capacity of the condenser or sump. All inlets
shall enter above the waterline. Wearing plates or
baffles shall be installed in the tank to protect the
shell. The sizes of the blowoff line inlet, the water
outlets, and the vent shall be as shown in Table 8-1.
The contents of condensers receiving steam or hot
water under pressure must pass through an open
sump before entering the drainage system.
810.2 Sumps, condensers, or intercepting tanks that
are constructed of concrete shall have walls and
bottom not less than four (4) inches (102 mm) in
thickness, and the inside shall be cement plastered
not less than one-half (1/2) inch (12.7 mm) in
thickness. Condensers constructed of metal shall be
not less than No. 12 U.S. standard gauge (0.109 inch)
(2.77 mm), and all such metal condensers shall be
protected from external corrosion by an approved
bituminous coating.
810.3 Sumps and condensers shall be provided with
suitable means of access for cleaning and shall
contain a volume of not less than twice the volume of
water removed from the boiler or boilers cormected
TABLE 8-1
Pipe Connections in Blowoff
Condensers and Sumps
Boiler Blowoff
Water Outlet
Vent
3/4 in.* (20 mm) 3/4 in.* (20 mm) 2 in. (50 mm)
lin. (25 mm) 1 in. (25 mm) 2-1/2 in. (65 mm)
1-1/4 in. (32 mm) 1-1/4 in. (32 mm) 3 in. (80 mm)
1-1/2 in. (40 mm) 1-1/2 in. (40 mm) 4 in. (100 mm)
2 in. (50 mm) 2 in. (50 mm) 5 in. (125 mm)
2-1/2 in. (65 mm) 2-1/2 in. (65 mm) 6 in. (150 mm)
*To be used only with boilers of 100 square feet (9.29
m^) of heating surface or less.
810.4 Strainers. Every indirect waste interceptor
receiving discharge-containing particles that would
clog the receptor drain shall have a readily
removable beehive strainer.
811.0 Cliemical Wastes.
811.1 Chemical or industrial liquid wastes, that are
likely to damage or increase maintenance costs on the
sanitary sewer system, detrimentally affect sewage
treatment, or contaminate surface or subsurface waters
shall be pretreated to render them innocuous prior to
discharge into a drainage system. Detailed plans and
specifications of the pretreatment facilities shall be
required by the Authority Having Jurisdiction.
Piping conveying industrial, chemical, or
process wastes from their point of origin to sewer-
connected pretreatment facilities shall be of such
material and design as to adequately perform itfe
intended function to the satisfaction of the Authority
Having Jurisdiction. Drainage discharge piping from
pretreatment facilities or interceptors shall conform
to standard drainage installation procedures.
Copper tube shall not be used for chemical or
industrial wastes as defined in this section.
81 1 .2 Each waste pipe receiving or intended to receive
the discharge of any fixture into which acid or
corrosive chemical is placed, and each vent pipe
connected thereto, shall be constructed of PP, PVDF, |
chemical-resistant glass, high-siUcon iron pipe, or lead
pipe with a wall thickness of not less than one-eighth
(1/8) inch (3.2 mm); an approved type of ceramic
glazed or unglazed vitrified clay; or other approved
corrosion-resistant materials.
125
811.3-814.3
UNIFORM PLUMBING CODE
811.3 All jointing materials shall be of approved
type and quality.
811.4 Wherever practicable, all piping shall be
readily accessible and installed with the maximum of
clearance from other services.
811.5 The owner shall make and keep a permanent
record of the location of all piping and venting
carrying chemical waste.
81 1 .6 No chemical vent shall intersect vents for other
services.
811.7 Chemical wastes shall be discharged in a
manner approved by the Authority Having
Jurisdiction.
811.8 The provisions in this section relative to
materials and methods of construction shall not
apply to installations such as photographic or X-ray
dark rooms or research or control laboratories
where minor amounts of adequately diluted
chemicals are discharged.
812.0 Clear Water Wastes.
Water lifts, expansion tanks, cooling jackets,
sprinkler systems, drip or overflow pans, or similar
devices that discharge clear wastewater into the
building drainage system shall discharge through an
indirect waste.
813.0 Swimming Pools.
Pipes carrying wastewater from swimming or
wading pools, including pool drainage and
backwash from filters, shall be installed as an
indirect waste. Where a pump is used to discharge
waste pool water to the drainage system, the pump
discharge shall be installed as an indirect waste.
814.0 Condensate Wastes and Control.
814.1 Condensate Disposal. Condensate from air
washers, air-cooling coils, fuel-burning condensing
appliances, the overflow from evaporative coolers,
and similar water-supplied equipment or similar air-
conditioning equipment shall be collected and
discharged to an approved plumbing fixture or
disposal area. If discharged into the drainage system,
equipment shall drain by means of an indirect waste
pipe. The waste pipe shall have a slope of not less
than 1/8 inch per foot (10.5 mm/m) or one percent
slope and shall be of approved corrosion-resistant
material not smaller than the outlet size as required
in Table 8-2 for air-cooling coils or condensing
fuel-burning appliances, respectively. Condensate or
wastewater shall not drain over a public way.
814.2 Size. Air-conditioning condensate waste pipes
shall be independent of any drainage and waste
system and shall not be smaller than shown in Table
8-2.
TABLE 8-2
Minimum Condensate Pipe Size
Equipment Capacity
Minimum Condensate
in Tons of
Pipe Diameter
Refrigeration (kW)
in Inches
(mm)
Up to 20 (Up to 70.34)
3/4
(20)
21-40 (73.85-140.67)
1
(25)
41-90 (144.19-316.6)
1-1/4
(32)
91-125 (320.03-439.6)
1-1/2
(40)
126-250 (443.12-879.2)
2
(50)
The size of condensate waste pipes may be for
one unit or a combination of units, or as
recommended by the manufacturer. The capacity of
waste pipes assumes a one-eighth (1/8) inch per foot
(10.5 mm/m) or one percent slope, with the
following pipe conditions:
Outside Air - 20%
DB WB
90°F 73°F
(32°C) (23°C)
Room Air - 80%
DB WB
75°F 62.5°F
(24°C) (17°)
Condensate drain sizing for other slopes or other
conditions shall be approved by the Authority
Having Jurisdiction.
Air-conditioning waste pipes shall be con-
structed of materials specified in Chapter 7.
814.3 Point of Discharge. Air-conditioning
condensate waste pipes shall connect indirectly to the
drainage system through an airgap or airbreak to a
properly trapped and vented receptors dry wells,
leach pits, or the tailpiece of plumbing fixtures.
Condensate waste shall not drain over a public
way.
126
CHAPTER 9
VENTS
901 .0 Vents Required.
Each plumbing fixture trap, except as otherwise
provided in this code, shall be protected against
siphonage and back-pressure, and air circulation
shall be ensured throughout all parts of the drainage
system by means of vent pipes installed in
accordance with the requirements of this chapter and
as otherwise required by this code.
902.0 Vents Not Required.
I 902.1 Vent piping may be omitted on an inter-
ceptor when such interceptor acts as a primary
settling tank and discharges through a horizontal
indirect waste pipe into a secondary interceptor.
The second interceptor shall be properly trapped
and vented.
902.2 Traps serving sinks that are part of the
equipment of bars, soda fountains, and counters
need not be vented when the location and
construction of such bars, soda fountains, and
counters is such as to make it impossible to do so.
When such conditions exist, said sinks shall
discharge by means of approved indirect waste pipes
into a floor sink or other approved type of receptor.
903.0 Materials.
903.1 Vent pipe shall be cast iron, galvanized steel,
galvanized wrought iron, copper, brass. Schedule 40
ABS DWV, Schedule 40 PVC DWV, stainless steel
304 or 316L (stainless steel 304 pipe and fittings shall
not be installed underground and shall be kept at
least six inches (152 mm) aboveground), or other
approved materials having a smooth and uniform
bore except that:
903.1.1 No galvanized wrought-iron or
galvanized steel pipe shall be used undergroimd
and shall be kept at least six (6) inches (152 mm)
aboveground.
903.1.2 ABS and PVC DWV piping installations
shall be installed in accordance with IS 5, IS 9,
and Chapter 15 "Firestop Protection." Except for
individual single-family dwelling units,
materials exposed within ducts or plenums shall
have a flame-spread index of not more than 25
and a smoke-developed index of not more than
50 when tested in accordance with the Test for
Surface-Burning Characteristics of the Building
Materials (see the Building Code standards
based on ASTM E-84 and ANSI/UL 723).
903.2 Use of Copper Tubing.
903.2.1 Copper tube for undergroimd drainage
and vent piping shall have a weight of not less
than that of copper drainage tube type DWV.
903.2.2 Copper tube for aboveground drainage
and vent piping shall have a weight of not less
than that of copper drainage tube type DWV.
903.2.3 Copper tube shall not be used for
chemical or industrial wastes as defined in
Section 811.0.
903.2.4 All hard-drawn copper tubing, in
addition to the required incised marking, shall
be marked in accordance with either ASTM
B306, Copper Drainage Tube (DWV), or ASTM
BBS Seamless Copper Water Tube as listed in
Table 14-1. The colors shall be: Type K, green;
T3^e L, blue; Type M, red; Type DWV, yellow.
903.3 Vent fittings shall be cast iron, galvanized
malleable iron or galvanized steel, copper, brass,
ABS, PVC, stainless steel 304 or 316L, or other |
approved materials, except that no galvanized
malleable iron or galvanized steel, or 304 stainless
steel shall be used underground and shall be kept at
least six (6) inches (152 mm) aboveground. Stainless
steel 304 pipe and fittings shall not be installed
underground and shall be kept at least 6 inches (152
mm) aboveground.
903.4 Changes in direction of vent piping shall be
made by the appropriate use of approved fittings,
and no such pipe shall be strained or bent. Burred
ends shall be reamed to the full bore of the pipe.
904.0 Size of Vents.
904.1 The size of vent piping shall be determined
from its length and the total number of fixture units
connected thereto, as set forth in Table 7-5. The
diameter of an individual vent shall not be less than
one and one-fourth (1-1/4) inches (32 mm) nor less
than one-half (1/2) the diameter of the drain to
which it is connected. In addition, the drainage
piping of each building and each connection to a
public sewer or a private sewage disposal system
shall be vented by means of one or more vent pipes,
the aggregate cross-sectional area of which shall not
be less than that of the largest required building
127
904.1 -907.1
UNIFORM PLUMBING CODE
sewer, as determined from Table 7-5. Vent pipes
from fixtures located upstream from pumps, ejectors,
backwater valves, or other devices that in any way
obstruct the free flow of air and other gases between
the building sewer and the outside atmosphere shall
not be used for meeting the cross-sectional area
venting requirements of this section.
Exception: When connected to a common
building sewer, the drainage piping of two (2) or
more buildings located on the same lot and under
one (1) ownership may be vented by means of
piping sized in accordance with Table 7-5,
provided the aggregate cross-sectional area of all
vents is not less than that of the largest required
common building sewer.
904.2 No more than one-third (1/3) of the total
permitted length, per Table 7-5, of any minimum-
sized vent shall be installed in a horizontal position.
Exception: When a minimum-sized vent is
increased one (1) pipe size for its entire length,
the maximum length limitation does not apply.
905.0 Vent Pipe Grades and Connections.
905.1 All vent and branch vent pipes shall be free
from drops or sags, and each such vent shall be level
or shall be so graded and connected as to drip back
by gravity to the drainage pipe it serves.
905.2 Where vents connect to a horizontal drainage
pipe, each vent pipe shall have its invert taken off
above the drainage centerline of such pipe
downstream of the trap being served.
905.3 Unless prohibited by structural conditions,
each vent shall rise vertically to a point not less than
six (6) inches (152 mm) above the flood-level rim of
the fixture. served before offsetting horizontally, and
whenever two or more vent pipes converge, each
such vent pipe shall rise to a point at least six (6)
inches (152 mm) in height above the flood-level rim
of the plumbing fixture it serves before being
connected to any other vent. Vents less than six (6)
inches (152 mm) above the flood-level rim of the
fixture shall be installed with approved drainage
fittings, material, and grade to the drain.
905.4 All vent pipes shall extend undiminished in
size above the roof, or shall be reconnected with a
soil or waste vent of proper size.
905.5 The vent pipe opening from a soil or waste
pipe, except for water closets and similar fixtures,
shall not be below the weir of the trap.
905.6 Two (2) fixtures may be served by a common
vertical pipe when each such fixture wastes separately
into an approved double fitting having inlet openings
at the same level.
906.0 Vent Termination.
906.1 Each vent pipe or stack shall extend through
its flashing and shall terminate vertically not less
than six (6) inches (152 mm) above the roof nor less
than one (1) foot (305 mm) from any vertical surface.
906.2 Each vent shall terminate not less than ten (10)
feet (3048 mm) from, or at least three (3) feet (914
mm) above, any openable window, door, opening,
air intake, or vent shaft, nor less than three (3) feet
(914 mm) in every direction from any lot line, alley
and street excepted.
906.3 Vent pipes shall be extended separately or
combined, of full required size, not less than six (6)
inches (152 mm) above the roof or fire wall.
Flagpoling of vents shall be prohibited except where
the roof is used for purposes other than weather
protection. All vents within ten (10) feet (3048 mm) of
any part of the roof that is used for such other
purposes shall extend not less than seven (7) feet
(2,134 mm) above such roof and shall be securely
stayed.
906.4 Vent pipes for outdoor installations shall
extend at least ten (10) feet (3,048 mm) above the
surrounding ground and shall be securely supported.
906.5 Joints at the roof around vent pipes shall be
made watertight by the use of approved flashings or
flashing material.
906.6 Lead. See Table 14-1. Sheet lead shall be not
less than the following:
For safe pans - not less than four (4) pounds per
square foot (19.5 kg/m^) or 1/16-inch (1.6 mm) thick.
For flashings or vent terminals - not less than
three (3) pounds per square foot (14.7 kg/m^) or 1.2
mm thick.
Lead bends and lead traps shall not be less than
one-eighth (1 /8) inch (3.2 mm) wall thickness.
906.7 Frost or Snow Closure. Where fiost or snow
closure is likely to occur in locations having minimum
design temperature below 0°F (-17.8°C), vent
terminals shall be a minimum of two (2) inches (51
mm) in diameter, but in no event smaller than the
required vent pipe. The change in diameter shall be
made inside the building at least one (1) foot (305 mm)
below the roof in an insulated space and terminate not
less than ten (10) inches (254 mm) above the roof, or as
required by the Authority Having Jurisdiction.
907.0 Vent Stacks and Relief Vents.
907.1 Each drainage stack that extends ten (10) or
more stories above the building drain or other
horizontal drain, shall be served by a parallel vent
128
VENTS
907.1 -910.3
stack, which shall extend undiminished in size from
its upper terminal and connect to the drainage stack at
or immediately below the lowest fixture drain. Each
such vent stack shall also be connected to the drainage
stack at each fifth floor, counting down from the
uppermost fixture drain, by means of a yoke vent, the
size of which shall be not less in diameter than either
the drainage or the vent stack, whichever is smaller.
907.2 The yoke vent connection to the vent stack
shall be placed not less than forty-two (42) inches
(1,067 mm) above the floor level, and the yoke vent
connection to the drainage stack shall be by means of
a wye-branch fitting placed below the lowest
drainage branch connection serving that floor.
908.0 Vertical Wet Venting.
908.1 Wet venting is limited to vertical drainage
piping receiving the discharge from the trap arm of
one (1) and two (2) fixture unit fixtures that also
serves as a vent for not to exceed four (4) fixtures.
All wet-vented fixtures shall be within the same
story; provided, further, that fixtures with a
continuous vent discharging into a wet vent shall be
within the same story as the wet-vented fixtures. No
wet vent shall exceed six (6) feet (1829 mm) in
developed length.
908.2 The vertical piping between any two (2)
consecutive inlet levels shall be considered a wet-
vented section. Each wet-vented section shall be a
minimum of one (1) pipe size larger than the
required minimum waste pipe size of the upper
fixture or shall be one (1) pipe size larger than the
required minimum pipe size for the sum of the
fixture units served by such wet-vented section,
whichever is larger, but in no case less than two (2)
inches (51 mm).
908.3 Common vent sizing shall be the sum of the
fixture units served but, in no case, smaller than the
minimum vent pipe size required for any fixture
served, or by Section 904.0.
908.4 Bathroom Wet Venting.
908.4.1 Where permitted. Any combination of
fixtures within one (1) or two (2) bathrooms
located on the same floor level in dwellings and
guest rooms shall be permitted to be vented by a
wet vent. The wet vent shall be considered the
vent for the fixtures and shall extend from the
connection of the dry vent along the direction of
the flow in the drain pipe to the most
downstream fixture drain connection to the
horizontal branch drain. Only the fixtures
within the bathroom(s) shall connect to the wet-
vented horizontal branch drain. Any additional
fixtures shall discharge downstream of the wet
vent system and be conventionally vented.
908.4.2 Vent Connection. The dry vent
connection to the wet vent shall be an individual
vent or common vent for the lavatory, bidet,
shower, or bathtub.
908.4.3 Size. The wet vent shall be sized based
on the fixture unit discharge into the wet vent.
The wet vent shall be a minium size of 2 inches
for 4 dfu or less, and 3 inches for more than 4 dfu.
909.0 Special Venting for Island Fixtures.
Traps for island sinks and similar equipment shall be
roughed in above the floor and may be vented by
extending the vent as high, as possible, but not less
than the drainboard height and then returning it
downward and connecting it to the horizontal sink
drain immediately downstream from the vertical
fixture drain. The return vent shall be connected to the
horizontal drain through a wye-branch fitting and
shall, in addition, be provided with a foot vent taken
off the vertical fixture vent by means of a wye branch
immediately below the floor and extending to the
nearest partition and then through the roof to the
open air, or may be connected to other vents at a point
not less than six (6) inches (152 mm) above the flood-
level rim of the fixtures served. Drainage fittings shall
be used on all parts of the vent below the floor level,
and a minimum slope of one-quarter (1/4) inch per
foot (20.9 mm/m) back to the drain shall be
maintained; The return bend used under the
drainboard shall be a one (1) piece fitting or an
assembly of a forty-five (45) degree (0.79 rad), a ninety
(90) degree (1.6 rad), and a forty-five (45) degree (0.79
rad) elbow in the order named. Pipe sizing shall be as
elsewhere required in this code. The island sink drain,
upstream of the returned vent, shall serve no other
fixtures. An accessible cleanout shall be installed in
the vertical portion of the foot vent.
910.0 Combination Waste and Vent Systems.
910.1 Combination waste and vent systems shall be
permitted only where structural conditions preclude
the installation of conventional systems as otherwise
prescribed by this code.
910.2 Plans and specifications for each combination
waste and vent system shall first be approved by the
Authority Having Jurisdiction before any portion of
any such system is installed.
910.3 Each combination waste and vent system, as
defined in Chapter 1, shall be provided with a vent
or vents adequate to ensure free circulation of air.
129
910.3-910.7
UNIFORM PLUMBING CODE
Any branch more than fifteen (15) feet (4,572 mm)
in length shall be separately vented in an approved
manner. The minimum area of any vent installed in
a combination waste and vent system shall be at
least one-half (1/2) the inside cross-sectional area
of the drain pipe served. The vent connection shall
be downstream of the uppermost fixture.
91 0.4 Each waste pipe and each trap in any such
system shall be at least two (2) pipe sizes larger than
the sizes required by Chapter 7 of this code, and at
least two (2) pipe sizes larger than any fixture
tailpiece or connection.
910.5 No vertical waste pipe shall be used in any
such system, except the tailpiece or connection
between the outlet of a plumbing fixture and the
trap. Such tailpieces or connections shall be as short
as possible, and in no case shall exceed two (2) feet
(610 mm).
Exception: Branch lines may have forty-five (45)
degree (0.79 rad) vertical offsets.
910.6 An accessible cleanout shall be installed in
each vent for the combination waste and vent
system. Cleanouts may not be required on any wet-
vented branch serving a single trap when the fixture
tailpiece or connection is not less than two (2) inches
(50 mm) in diameter and provides ready access for
cleaning through the trap.
91 0.7 No water closet or urinal shall be installed on
any such system. Other one (1), two (2), or three (3)
unit fixtures remotely located from the sanitary
system and adjacent to a combination waste and
vent system may be connected to such system in the
conventional manner by means of waste and vent
pipes of regular sizes, providing that the two (2) pipe
size increase required in Section 910.4 is based on the
total fixture unit load connected to the system.
Note:
See Appendix B of this code for explanatory notes on
the design of combination waste and vent systems.
130
CHAPTER 10
TRAPS AND INTERCEPTORS
1001.0 Traps Required.
1001.1 Each plumbing fixture, excepting those
having integral traps or as permitted in Section
1001.2, shall be separately trapped by an approved
type of waterseal trap. Not more than one (1) trap
shall be permitted on a trap arm.
1 001 .2 One (1) trap may serve a set of not more than
three (3) single compartment sinks or laundry tubs of
the same depth or three (3) lavatories immediately
adjacent to each other and in the same room if the
waste outlets are not more than thirty (30) inches
(762 mm) apart and the trap is centrally located
when three (3) compartments are installed.
1 001 .3 No food waste disposal unit shall be installed
with any set of restaurant, commercial, or industrial
sinks served by a single trap; each such food waste
disposal unit shall be cormected to a separate trap.
Each domestic clothes washer and each laundry tub
shall be connected to a separate and independent
trap, except that a trap serving a laundry tub may
also receive the waste from a clothes washer set
adjacent thereto. No clothes washer or laundry tub
shall be connected to any trap for a kitchen sink.
1001.4 The vertical distance between a fixture outlet
and the trap weir shall be as short as practicable, but
in no case shall the tailpiece from any fixture exceed
twenty-four (24) inches (610 mm) in length.
1002.0 Traps Protected by Vent Pipes.
1002.1 Each plumbing fixture trap, except as
otherwise provided in this code, shall be protected
against siphonage and back-pressure, and air
circulation shall be assured throughout all parts of
the drainage system by means of a vent pipe installed
in accordance with the requirements of this code.
1002.2 Each fixture trap shall have a protecting vent so
located that the developed length of the trap arm from
the trap weir to the irmer edge of the vent shall be
within the distance given in Table 10-1, but in no case
less than two (2) times the diameter of the trap arm.
1002.3 A trap arm may change direction without the
use of a cleanout when such change of direction does
not exceed ninety (90) degrees (1.6 rad). All
horizontal changes in direction of trap arms shall
comply with Section 706.3.
Exception; For trap arms three (3) inches (80
mm) in diameter and larger, the change of
direction shall not exceed one hundred and
thirty-five (135) degrees (2.36 rad) without the
use of a cleanout.
1002.4 The vent pipe opening from a soil or waste
pipe, except for water closets and similar fixtures,
shall not be below the weir of the trap.
TABLE 10-1
Horizontal Distance of Trap Arms
(Except for water closets and similar fixtures)*
Trap Arm
Inches
Distance
Trap to Vent
Feet Inches
Trap Arm
mm
Distance
Trap to Vent
mm
1-1/4
2
6
32
762
1-1/2
3
6
40
1067
2
5
50
1524
3
6
80
1829
4 & larger
10
100 & larger
3048
Slope one-fourth (1/4) inch
per foot (20.9
mm/m)
*The developed length between the trap) of a water closet or
similar fixture (measured from the top of the closet ring [closet
flange] to the inner edge of the vent) and its vent shall not
exceed six (6) feet (1829 mm).
1003.0 Traps — Described.
1003.1 Each trap, except for traps within an
interceptor or similar device, shall be self-cleaning.
Traps for bathtubs, showers, lavatories, sinks,
laundry tubs, floor drains, urinals, drinking
fountains, dental units, and similar fixtures shall be
of standard design and weight and shall be of ABS,
cast brass, cast iron, lead, PP, PVC, or other
approved material. An exposed and readily
accessible drawn-brass tubing trap, not less than 17
B&S Gauge (0.045 inch) (1.1 mm), may be used on
fixtures discharging domestic sewage.
Exception: Drawn-brass tubing traps shall not
be used for urinals. Each trap shall have the
manufacturer's name stamped legibly in the
metal of the trap, and each tubing trap shall
have the gauge of the tubing in addition to the
manufacturer's name. Every trap shall have a
smooth and uniform interior waterway.
1 003.2 No more than one (1) approved slip joint
fitting may be used on the outlet side of a trap, and
no tubing trap shall be installed without a listed
tubing trap adapter. Listed plastic trap adapters may
be used to connect listed metal tubing traps.
131
1003.3-1011.0
UNIFORM PLUMBING CODE
1003.3 The size (nominal diameter) of a trap for a
given fixture shall be sufficient to drain the fixture
rapidly, but in no case less than nor more than one
(1) pipe size larger than given in Table 7-3. The
trap shall be the same size as the trap arm to which
it is connected.
1004.0 Traps — Prohibited.
No form of trap that depends for its seal upon the action
of movable parts shall be used. No trap that has
concealed interior partitions, except those of plastic,
glass, or similar corrosion-resisting material, shall be
used. "S" traps, bell traps, and crown-vented traps shall
be prohibited. No fixture shall be double trapped. Drum
and bottle traps shall be installed only for special
conditions. No trap shall be iQstalled without a vent,
except as otherwise provided in this code.
1005.0 Trap Seals.
Each fixture trap shall have a water seal of not less
than two (2) inches (51 mm) and not more than four
(4) inches (102 mm), except where a deeper seal is
found necessary by the Authority Having Jurisdiction.
Traps shall be set true with respect to their water
seals and, where necessary, they shall be protected
from freezing.
1006.0 Floor Drain Traps.
Floor drains shall connect into a trap so constructed
that it can be readily cleaned and of a size to serve
efficiently the purpose for which it is intended. The
drain inlet shall be so located that it is at all times in
full view. When subject to reverse flow of sewage or
liquid waste, such drains shall be equipped with an
approved backwater valve.
1007.0 Trap Seal Protection.
Floor drain or similar traps directly connected to the
drainage system and subject to infrequent use shall
be protected with a trap seal primer, except where
not deemed necessary for safety or sanitation by the
Authority Having Jurisdiction. Trap seal primers
shall be accessible for maintenance.
1008.0 Building Traps.
Building traps shall not be installed except where
required by the Authority Having Jurisdiction. Each
building trap when installed shall be provided with
a cleanout and with a relieving vent or fresh-air
intake on the inlet side of the trap, which need not be
larger than one-half the diameter of the drain to
which it connects. Such relieving vent or fresh-air
intake shall be carried above grade and terminate in
a screened outlet located outside the building.
1009.0 Industrial Interceptors (Clarifiers) and
Separators.
1009.1 When Required. Interceptors (clarifiers)
(including grease, oil, sand interceptors [clarifiers],
etc.) shall be required by the Authority Having
Jurisdiction when they are necessary for the proper
handling of liquid wastes containing grease,
flammable wastes, sand, solids, acid or alkaline
substances, or other ingredients harmful to the
building drainage system, the public or private
sewer, or to public or private sewage disposal.
1009.2 Approval. The size, type, and location of each
interceptor (clarifier) or separator shall be approved
by the Authority Having Jurisdiction. Except where
otherwise specifically permitted, no wastes other
than those requiring treatment or separation shall be
discharged into any interceptor (clarifier).
1009.3 Design. Interceptors (clarifiers) for sand and
similar heavy solids shall be so designed and located
as to be readily accessible for cleaning and shall have
a water seal of not less than six (6) inches (152 mm).
1009.4 Relief Vent. Interceptors (clarifiers) shall be
so designed that they will not become air-bound if
closed covers are used. Each interceptor (clarifier)
shall be properly vented.
1009.5 Location. Each interceptor (clarifier) cover
shall be readily accessible for servicing and
maintaining the interceptor (clarifier) in working and
operating condition. The use of ladders or the
removal of bulky equipment in order to service
interceptors (clarifiers) shall constitute a violation of
accessibility. Location of all interceptors (clarifiers)
shall be shown on the approved building plan.
1009.6 Maintenance of Interceptors. Interceptors
shall be maintained in efficient operating condition
by periodic removal of accumulated grease, scum,
oil, or other floating substances and solids deposited
in the interceptor.
1 009.7 Discharge. The waste pipe from oil and sand
interceptors shall discharge as approved by the
Authority Having Jurisdiction.
1010.0 Slaughterhouses, Packing Establishments, etc.
Every fish, fowl, and animal slaughterhouse or
establishment; every fish, fowl, and meat packing or
curing establishment; every soap factory, tallow-
rendering, fat-rendering, and hide-curing establish-
ment shall be connected to and shall drain or
discharge into an approved grease interceptor
(clarifier).
101 1 .0 Minimum Requirements for Auto Wash Racks.
Every private or public wash rack and /or floor or
slab used for cleaning machinery or machine parts
shall be adequately protected against storm or surface
water and shall drain or discharge into an approved |
interceptor (clarifier).
132
TRAPS AND INTERCEPTORS
1012.0-1014.2
1012.0 Commercial and Industrial Laundries.
Laundry eqviipment in con\n\ercial and industrial
buildings that does not have integral strainers shall
discharge into an interceptor having a wire basket or
similar device that is removable for cleaning and that
will prevent passage into the drainage system of
solids one-half (1/2) inch (12.7 mm) or larger in
maximum dimension, such as string, rags, buttons,
or other solid materials detrimental to the public
sewerage system.
1013.0 Bottling Establishments. Bottling plants
shall discharge their process wastes into an
interceptor that will provide for the separation of
broken glass or other solids, before discharging
liquid wastes into the drainage system.
1014.0 Grease Interceptors.
1014.1 Where it is determined by-the Authority
Having Jurisdiction that waste pretreatment is
required, an approved type of grease interceptor(s)
complying with the provisions of this section shall be
correctly sized and properly installed in grease waste
line(s) leading from sinks and drains, such as floor
drains and floor sinks and other fixtures or
equipment in serving establishn\ents such as
restaurants, cafes, lunch counters, cafeterias, bars
and clubs, hotels, hospitals, sanitariums, factory or
school kitchens, or other establishments where
grease may be introduced into the drainage or
sewage system in quantities that can effect line
stoppage or hinder sewage treatment or private
sewage disposal. A grease interceptor shall not be
required for individual dwelling units or for any
private living quarters. Water closets, urinals, and
other plumbing fixtures conveying human waste
shall not drain into or through the grease interceptor.
1014.1.1 Each fixture discharging into a grease
interceptor shall be individually trapped and
vented in an approved manner.
1014.1.2 All grease interceptors shall be
maintained in efficient operating condition by
periodic removal of the accumulated grease and
latent material. No such collected grease shall be
introduced into any drainage piping or public or
private sewer. If the Authority Having Jurisdic-
tion determines that a grease interceptor is not
being properly cleaned or maintained, the
Authority Having Jurisdiction shall have the
authority to mandate the installation of addi-
tional equipment or devices and to mandate a
maintenance program.
1014.1.3 Food Waste Disposal Units and
Dishwashers. Unless specifically required or
permitted by the Authority Having Jurisdiction,
no food waste disposal unit or dishwasher shall
be connected to or discharge into any grease
interceptor. Commercial food waste disposers
shall be permitted to discharge directly into the
building's drainage system.
1014.2 Hydromechanical Grease Interceptors.
1014.2.1 Each plumbing fixture or piece of
equipment connected to a hydromechanical grease
interceptor shall be provided with an approved
type of vented flow control installed in a readily
accessible and visible location. How control devices
shall be designed and installed so that the total flow
through such device or devices shall at no time be
greater than the rated flow of the grease interceptor.
No flow-control device having adjustable or
removable parts shall be approved. The vented
flow-control device shall be located such that no
system vent shall be between the flow-control and
the grease trap inlet. The vent or air inlet of the
flow-control device shaU connect with the sanitary
drainage vent system, as elsewhere required by this
code, or shall terminate through the roof of the
building, and shall not terminate to the free
atmosphere inside the building.
Exception: Listed grease interceptors with
integral flow controls or restricting devices
shall be installed in an accessible location in
accordance with the manufacturers'
instructions.
1014.2.2 The total capacity in gallons (L) of
fixtures discharging into any hydromechanical
grease interceptor shall not exceed two and one-
half (2-1/2) times the certified GPM (L/s) flow
rate of the interceptor as per Table 10-2.
For the purpose of this section, the term
"fixture" shall mean and include each plumbing
fixture, appliance, apparatus, or other equipment
required to be connected to or discharged into a
grease interceptor by any provision of this
section.
1 01 4.2.3 A vent shall be installed downstream
of hydromechanical grease interceptors in
accordance with the requirements of this code.
133
Table 10-2 -1015.1
UNIFORM PLUMBING CODE
Table 10-2
Hydromechanical Grease Interceptor (HGI)
Sizing Chart*
DFU HGI FLOW (gpm)
10
13
20
35
172
216
342
428
576
720
20
25
35
50
75
100
150
200
250
350
500
*Based on intermittent potentially full flow in
drainage lines.
1014.3 Gravity Grease Interceptors. Required
gravity grease interceptors shall comply with the
provisions of Sections 1014.3.1 through 1014.3.7.
1014.3.1 General.
The provisions of this section shall apply to the
design, construction, installation, and testing of
commercial kitchen gravity grease interceptors.
1014.3.2 Waste Discharge Requirements.
1014.3.2.1 Waste discharge in establishments
from fixtures and equipment which may
contain grease, including but not limited to,
scullery sinks, pot and pan sinks, dishwashers,
soup kettles, and floor drains located in areas
where grease-containing materials may exist,
may be drained into the sanitary waste
through the interceptor when approved by the
Authority Having Jurisdiction.
1014.3.2.2 Toilets, urinals, and other
similar fixtures shall not drain through the
interceptor.
1014.3.2.3 All waste shall enter the
interceptor through the inlet pipe only.
1014.3.3 Design.
1014.3.3.1 Gravity Interceptors shall be
constructed in accordance with the applicable
standard in Table 14-1 or the design approved
by the Authority Having Jurisdiction.
1014.3.4 Location.
1014.3.4.1 Each grease interceptor shall be
so installed and connected that it shall be
at all times easily accessible for inspection.
cleaning, and removal of the intercepted
grease. A gravity grease interceptor
complying with lAPMO PS 80, shall not be
installed in any part of a building where
food is handled. Location of the grease
interceptor shall meet the approval of the
Authority Having Jurisdiction.
1014.3.4.2 Interceptors shall be placed as
close as practical to the fixtures they serve.
1 01 4.3.4.3 Each business establishment for
which a gravity grease interceptor is
required shall have an interceptor which
shall serve only that establishment unless
otherwise approved by the Authority
Having Jurisdiction.
1014.3.4.4 Each gravity grease interceptor
shall be located so as to be readily accessible
to the equipment required for maintenance.
1014.3.5 Construction Requirements.
1014.3.5.1 Purpose. Gravity grease
interceptors shall be designed to remove
grease from effluent and shall be sized in
accordance with this section. Gravity grease
interceptors shall also be designed to retain
grease until accumulations can be renioved by
pumping the interceptor. It is recommended
that a sample box be located at the outlet end
of all gravity grease interceptors so that the
Authority Having Jurisdiction can periodi-
cally sample effluent quedity.
1014.3.6 Sizing Criteria.
1014.3.6.1 Sizing. The volume of the
interceptor shall be determined by using
Table 10-3. If drainage fixture units (DFUs)
are not known, the interceptor shall be sized
based on the maximum DFUs allowed for the
pipe size connected to the inlet of the
interceptor. Refer to Table 7-5, Drainage
Piping, Horizontal.
1014.3.7 Abandoned Gravity Grease Intercep-
tors. Abandoned grease interceptors shall be
pumped and filled as required for abandoned
sewers and sewage disposal facilities in Section
722.0.
1015.0 FOG (Fats, Oils, and Greases) Disposal
System.
1015.1 Purpose.
The purpose of this section is to provide the necessary
criteria for the sizing, application, and installation of
FOG disposal systems designated as a pretreatment or
discharge water quality compliance strategy.
134
TRAPS AND INTERCEPTORS
Table 10-3 -1016.2
Table 10-3
Gravity Grease Interceptor Sizing
DFUs (1)
8
21 (3)
35
90 (3)
172
216
307 (3)
342
428
576
720
2112
2640
Interceptor Volume (2)
500 gallons
750 gallons
1,000 gallons
1,250 gallons
1,500 gallons
2,000 gallons ■
2,500 gallons
3,000 gallons
4,000 gallons
5,000 gallons
7,500 gallons
10,000 gallons
15,000 gallons
Notes
(1) Tlie maximum allowable DFUs plumbed to the kitchen drain lines that will be connected to the grease interceptor.
(2) This size is based on: the DFUs, the pipe size from this code; Table 7-5; Useful Tables for flow in half-full pipes (ref : Mohinder Nayynr Piping
Handbook, 3Td Edition, 1992).
(3) Based on 30-minute retention time (ref.: Metcalf & Eddy, hic. Small and Decentralized Wastezuater Management Systems, 3rd Ed. 1998). Romided up
to nominal interceptor volume.
1015.2 Scope.
FOG disposal systems shall be considered engineered
systems and shall comply with the requirements of
section 301.2 of this code.
1015.3 Components, Materials, and Equipment.
FOG disposal systems, including all components,
materials, and equipment necessary for the proper
function of the system, shall comply with sections
301.1.3 or 301.2 of this code.
1015.4 Sizing Application and Installation.
FOG disposal systems shall be engineered, sized,
and installed in accordance with the manufacturers'
specifications and as specified in lAPMO PS 118-
2000, as listed in Chapter 14, Table 14-1 of this code.
1015.5 Performance.
FOG disposal systems shall be tested and certified as
described in lAFMO PS 118-2000, as listed in
Chapter 14, Table 14-1 of this code, and other
national consensus standards applicable to FOG
disposal systems as discharging no more than
lOOmg/L FOG.
Gravity Grease Interceptor Sizing Example:
Given: A restaurant with the following fixtures and
equipment.
one food preparation sink; three floor drains - one in the food
prep area, one in the grill area, and one receiving the indirect
waste from the ice machine; a mop sink; a dishwasher with a
maximum discharge flow rate of 20 gpm discharging into a
dedicated receptor; and two public restrooms, each with one
water closet and one lavatory.
Kitchen Drain Line DFU Count (from Table 7-3):
3 floor drains @ 2 DFUs each = 6 DFUs
Mop sink @ 3 DFUs each = 3 DFUs
Food prep sink @ 3 DFUs each = 3 DFUs
Dishwasher @ 4 DFUs (Table 7-4) = 4 DFUs
Total 16 DFUs
Using Table 10-3, the grease interceptor will be sized at 750
gallons.
1016.0 Sand Interceptors.
1016.1 Where Required.
1016.1.1 Whenever the discharge of a fixture or
drain may contain solids or semi-solids heavier
than water that would be harmful to a drainage
system or cause a stoppage within the system,
the discharge shall be through a sand interceptor.
Multiple floor drains may discharge into one
sand interceptor.
1016.1.2 Sand interceptors are required when-
ever the Authority Having Jurisdiction deems it
advisable to have a sand interceptor to protect
the drainage system.
1016.2 Construction and Size.
Sand interceptors shall be built of brick or concrete,
prefabricated coated steel, or other watertight material.
The interceptor shall have an interior baffle for full
separation of the interceptor into two (2) sections. The
outlet pipe shall be the same size as the inlet pipe of the
sand interceptor, the minimum being three (3) inches
135
1016.2-1017.2
UNIFORM PLUMBING CODE
(80 mm), and the baffle shall have two (2) openings of
the same diameter as the outlet pipe and at the same
invert as the outlet pipe. These openings shall be
staggered so that there cannot be a straight line flow
between any inlet pipe and the outlet pipe. The invert
of the inlet pipe shall be no lower than the invert of the
outlet pipe.
The sand interceptor shall have a minimum
dimension of two (2) feet square (0.2 m^) for the net free
opening of the inlet section and a minimum depth under
the invert of the outlet pipe of two (2) feet (610 mm).
For each five (5) gallons (18.9 L) per minute flow
or fraction thereof over twenty (20) gallons (75.7 L)
per minute, the area of the sand interceptor inlet
section is to be increased by one (1) square foot (0.09
m^). The outlet section shall at all times have a
minimum area of fifty (50) percent of the inlet section.
The outlet section shall be covered by a solid
removable cover, set flush with the finished floor,
and the inlet section shall have an open grating, set
flush with the finished floor and suitable for the
traffic in the area in which it is located.
1016.3 Separate Use. Sand and similar interceptors for
every solid shall be so designed and located as to be
readily accessible for cleaning, shall have a water seal of
not less than six (6) inches (152 mm), and shall be vented.
1017.0 Oil and Flammable Liquid Interceptors.
1017.1 Interceptors Required. All repair garages
and gasoline stations with grease racks or grease
pits, and all factories that have oily, flammable, or
both types of wastes as a result of manufacturing,
storage, maintenance, repair, or testing processes,
shall be provided with an oil or flammable liquid
interceptor that shall be connected to all necessary
floor drains. The separation or vapor compartment
shall be independently vented to the outer air. If two
(2) or more separation or vapor compartments are
used, each shall be vented to the outer air or may
connect to a header that is installed at a minimum of six
(6) inches (152 mm) above the spill Mne of the lowest
floor drain and vented independently to the outer air.
The minimum size of a flammable vapor vent shall not
be less than two (2) inches (50 mm), and, when vented
through a sidewall, the vent shall not be less than ten
(10) feet (3048 mm) above the adjacent level at an
approved location. The interceptor shaU be vented on
the sewer side and shall not connect to a flammable
vapor vent. All oil and flammable interceptors shaU be
provided with gastight cleanout covers that shall be
readily accessible. The waste line shall not be less than
three (3) inches (80 mm) in diameter with a full-size
cleanout to grade. When an interceptor is provided
witli an overflow, it shall be provided with an overflow
Mne (not less than two (2) inches (50 mm) in diameter)
to an approved waste oil tank having a minimum
capacity of five hundred fifty (550) gallons (2,080 L) and
meeting the requirements of the Authority Having
Jurisdiction. The waste oil from the separator shall flow
by gravity or shall be pumped to a higher elevation by
an automatic pump. Pumps shall be adequately sized
and accessible. Waste oil tanlcs shall have a two (2) inch
(50 mm) minimum pump-out connection at grade and
a one and one-half (1-1/2) inch (40 mm) minimum vent
to atmosphere at an approved location at least ten (10)
feet (3,048 mm) above grade.
1017.2 Design of Interceptors. Each manufactured
interceptor that is rated shall be stamped or labeled
by the manufacturer with an indication of its full
discharge rate in gpm (L/s). The full discharge rate to
such an interceptor shall be determined at full flow.
Each interceptor shall be rated equal to or greater
than the incoming flow and shall be provided with an
overflow line to an underground tank.
Interceptors not rated by the manufacturer shall
have a depth of not less than two (2) feet (610 mm)
below the invert of the discharge drain. The outlet
opening shall have not less than an eighteen (18) inch
(457 mm) water seal and shall have a minimum capacity
as follows: where not more than thi'ee (3) motor vehicles
are serviced and /or stored, interceptors shall have a
minimum capacity of six (6) cubic feet (0.2 nf), and one
(1) cubic foot (0.03 m^) of capacity shall be added for
each vehicle up to ten (10) vehicles. Above ten (10)
vehicles, the Authority Having Jurisdiction shall
determine tiie size of the interceptor required. Where
vehicles are serviced only and not stored, interceptor
capacity shall be based on a net capacity of one (1) cubic
foot (0.03 m^) for each one hundred (100) square feet (9.3
m^) of surface to be drained into the interceptor, with a
minimum of six (6) cubic feet (0.2 m^).
136
CHAPTER 11
STORM DRAINAGE
1101.0 General.
1101.1 Where Required. All roofs, paved areas,
yards, courts, and courtyards shall be drained into a
separate storm sewer system, or into a combined
sewer system where a separate storm sewer system
is not available, or to some other place of disposal
satisfactory to the Authority Having Jurisdiction, hi
the case of one- and two-family dwellings, storm
water may be discharged on flat areas such as streets
or lawns so long as the storm water shall flow away
from the building and away from adjoining
property, and shall not create a nuisance.
1101.2 Storm Water Drainage to Sanitary Sewer
Prohibited. Storm water shall not be drained into
sewers intended for sanitary drainage only.
1101.3 Material Uses. Rainwater piping placed
within the interior of a building or run within a vent
or shaft shall be of cast iron, galvanized steel,
wrought iron, brass, copper, lead. Schedule 40 ABS
DWV, Schedule 40 PVC DWV, stainless steel 304 or
316L (stainless steel 304 pipe and fittings shall not be
installed underground and shall be kept at least six
inches (152 mm) aboveground), or other approved
materials, and changes in direction shall conform to
the requirements of Section 706.0. ABS and PVC
DWV piping installations shall be installed in
accordance with IS 5, IS 9, and Chapter 15 "Firestop
Protection." Except for individual single-family
dwelling units, materials exposed within ducts or
plenums shall have a flame-spread index of not more
than 25 and a smoke-developed index of not more
than 50, when tested in accordance with the Test for
Surface-Burning Characteristics of the Building
Materials (see the Building Code standards based on
ASTM E-84 and ANSI/UL 723.).
1101.4 Expansion Joints Required. Expansion
joints or sleeves shall be provided where warranted
by temperature variations or physical conditions.
1101.5 Subsoil Drains.
1101 .5.1 Subsoil drains shall be provided around
the perimeter of buildings having basements,
cellars, or crawl spaces or floors below grade.
Such subsoil drains may be positioned inside or
outside of the footing, shall be of perforated or
open-jointed approved drain tile or pipe not less
than three (3) inches (80 mm) in diameter, and
shall be laid in gravel, slag, crushed rock,
approved three-quarter (3/4) inch (19.1 mm)
crushed recycled glass aggregate, or other
approved porous material with a minimum of
four (4) inches (102 mm) surrounding the pipe
on all sides. Filter media shall be provided for
exterior subsoil piping.
1 1 01 .5.2 Subsoil drains shall be piped to a storm
drain, to an approved water course, to the front
street curb or gutter, or to an alley, or the
discharge from the subsoil drains shall be
conveyed to the alley by a concrete gutter. Where
a continuously flowing spring or groundwater is
encountered, subsoil drains shall be piped to a
storm drain or an approved water course.
1101 .5.3 Where it is not possible to convey the
drainage by gravity, subsoil drains shall
discharge to an accessible sump provided with
an approved automatic electric pump. The sump
shall be at least fifteen (15) inches (375 mm) in
diameter, eighteen (18) inches (457 mm) in
depth, and provided with a fitted cover. The
sump pump shall have an adequate capacity to
discharge all water coming into the sump as it
accumulates to the required discharge point, and
the capacity of the pump shall not be less than
fifteen (15) gpm (1.0 L/s). The discharge piping
from the sump pump shall be a minimum of one
and one-half (1-1/2) inches (40 mm) in diameter
and have a union or other approved quick-
disconnect assembly to make the pump
accessible for servicing.
1101.5.4 For separate dwellings not serving
continuously flowing springs or groundwater,
the sump discharge pipe may discharge onto a
concrete splash block with a minimum length of
twenty-four (24) inches (610 mm). This pipe shall
be within four (4) inches (102 mm) of the splash
block and positioned to direct the flow parallel
to the recessed line of the splash block.
1101.5.5 Subsoil drains subject to backflow
when discharging into a storm drain shall be
provided with a backwater valve in the drain
line so located as to be accessible for inspection
and maintenance.
1101.5.6 Nothing in Section 1101.5 shall prevent
drains that serve either subsoil drains or areaways
of a detached building from discharging to a
properly graded open area, provided that:
(1) They do not serve continuously flowing
springs or groundwater;
(2) The point of discharge is at least ten (10) feet
(3,048 mm) from any property line; and •
137
1101.5-1101.12
UNIFORM PLUMBING CODE
(3) It is impracticable to discharge such drains
to a storm, drain, to an approved water
course, to the front street curb or gutter, or
to an alley.
1101.6 Building Subdrains. Building subdrains
located below the public sewer level shall discharge
into a sump or receiving tank, the contents of which
shall be automatically lifted and discharged into the
drainage system as required for building sumps.
1101.7 Areaway Drains. All open subsurface space
adjacent to a building, serving as an entrance to the
basement or cellar of a building, shall be provided
with a drain or drains. Such areaway drains shall be
two (2) inches (50 mm) minimum diameter for
areaways not exceeding one hundred (100) square
feet (9.3 m^) in area, and shall be discharged in the
manner provided for subsoil drains not serving
continuously flowing springs or groundwater (see
Section 1101.5.2). Areaways in excess of one hundred
(100) square feet (9.3 m^) shall not drain into subsoil.
Areaway drains for areaways exceeding one
hundred (100) square feet (9.3 m^) shall be sized
according to Table 11-2.
1101.8 Window Areaway Drains. Window areaways
not exceeding ten (10) square feet (0.9 m^) in area
may discharge to the subsoil drains through a two
(2) inch (50 mm) pipe. However, window areaways
exceeding ten (10) square feet (0.9 m^) in area shall be
handled in the manner provided for entrance
areaways (see Section 1101.7).
1101.9 Filling Stations and IVIotor Vehicle Washing
Establishments. Public filling stations and motor
vehicle washing establishments shall have the paved
area sloped toward sumps or gratings within the
property lines. Curbs not less than six (6) inches (152
mm) high shall be placed where required to direct
water to gratings or sumps.
1101.10 Paved Areas. Where the occupant creates
surface water drainage, the sumps, gratings, or floor
drains shall be piped to a storm drain or an
approved water course.
1 1 01 .1 1 Roof Drainage.
1101.11.1 Primary Roof Drainage. Roof areas
of a building shall be drained by roof drains or
gutters. The location and sizing of drains and
gutters shall be coordinated with the structural
design and pitch of the roof. Unless otherwise
required by the Authority Having Jurisdiction,
roof drains, gutters, vertical conductors or
leaders, and horizontal storm drains for primary
drainage shall be sized based on a storm of sixty
(60) minutes duration and 100-year return
period. Refer to Table D-1 (in Appendix D) for
100-year, 60-minute storms at various locations.
1101.11.2 Secondary drainage. Secondary
(emergency) roof drainage shall be provided by
one of the methods specified in Section
1101.11.2.1 or 1101.11.2.2.
1101.11.2.1 Roof Scuppers or Open Side.
Secondary roof drainage shall be provided by
an open-sided roof or scuppers where the
roof perimeter construction extends above
the roof in such a manner that water will be
entrapped. An open-sided roof or scuppers
shall be sized to prevent the depth of ponding
water from exceeding that for which the roof
was designed as determined by Section
1101.11.1. Scupper openings shall be a
minimum of 4" high and have a width equal
to the circumference of the roof drain required
for the area served, sized by Table 11-1.
1101.11.2.2 Secondary Roof Drain.
Secondary roof drains shall be provided.
The secondary roof drains shall be located a
minimum of 2 inches above the roof surface.
The maximum height of the roof drains shall
be a height to prevent the depth of ponding
water from exceeding that for which the
roof was designed as determined by Section
1101.11.1. The secondary roof drains shall
connect to a piping system conforming to
Section 1101.11.2.2.1 or 1101.11.2.2.2.
1101.11.2.2.1 Separate Piping System.
The secondary roof drainage system
shall be a separate system of piping,
independent of the primary roof
drainage system. The discharge shall be
above grade, in a location observable by
the building occupants or maintenance
personnel. Secondary roof drain systems
shall be sized in accordance with Section
1101.11.1 based on the rainfall rate for
which the primary system is sized.
1101.11.2.2.2 Combined System. The
secondary roof drains shall connect to the
vertical piping of the primary storm
drainage conductor downstream of any
horizontal offset below the roof. The
primary storm drainage system shall
connect to the building storm water that
connects to an underground public storm
sewer. The combined secondary and prim-
ary roof drain systems shall be sized in
accordance with Section 1106.0 based on
double the rainfall rate for the local area.
1101.12 Cleanouts.
1101.12.1 Cleanouts for building storm
drains shall comply with the requirements
of Section 719.0 of this code.
138
STORM DRAINAGE
1101.12-1105.1
1101.12.2 Rain leaders and conductors
connected to a building storm sewer shall
have a cleanout installed at the base of the
outside leader or outside conductor before it
connects to the horizontal drain.
1101.13 All rainwater sumps serving "public
use" occupancy buildings shall be provided with
dual pumps arranged to function alternately in
case of overload or mechanical failure.
1102.0 Materials.
1102.1 Conductors.
1102.1.1 Conductors installed aboveground in
buildings shall be constructed of materials
specified in Table 14-1.
1 1 02.1 .2 The inside of conductors installed above
ground level shall be of seamless copper water
tube. Type K, L, or M; Schedule 40 copper pipe or
Schedule 40 copper alloy pipe; Type DWV copper
drainage tube; service weight cast-iron soil pipe or
hubless cast-iron soil pipe; standard weight
galvanized steel pipe; stainless steel 304 or 316L
(stainless steel 304 pipe and fittings shall not be
installed underground and shall be kept at least 6
inches (152 mm) aboveground); or Schedule 40
ABS or Schedule 40 PVC plastic pipe.
1102.2 Leaders.
1102.2.1 Leaders shall be constructed of
materials specified in Table 14-1.
1102.2.2 Leaders shall be of seamless copper
water tube. Type K, L, or M; Schedule 40 copper
pipe; Schedule 40 copper alloy pipe; type DWV
copper drainage tube; service weight cast-iron soil
pipe or hubless cast-iron soil pipe; aluminum
sheet nietal, galvanized steel sheet metal, or
copper sheet metal; standard weight galvanized
steel pipe; Class DL or XL lead pipe; stainless steel
304 or 316L (stainless steel 304 pipe and fittings
shall not be installed underground and shall be
kept at least 6 inches (152 nun) above-ground); or
Schedule 40 ABS or Schedule 40 PVC plastic pipe.
1102.3 Underground Building Storm Drains. All
underground building storm drains shall be
constructed of materials specified in Table 14-1.
1102.4 Building Storm Sewers. Building storm sewers
shall be constructed of materials specified in Table 14-1.
1102.5 Subsoil Drains.
1102.5.1 Subsoil drains shall be constructed of
materials specified in Table 14-1.
1 1 02.5.2 Subsoil drains shall be open-jointed or
of perforated pipe, vitrified clay, plastic, cast
iron, or porous concrete.
1103.0 Traps on Storm Drains and Leaders.
1103.1 Where Required. Leaders and storm drains,
when connected to a combined sewer, shall be
trapped. Floor and area drains connected to a storm
drain shall be trapped.
Exception: Traps shall not be required where
roof drains, rain leaders, and other inlets are at
locations allowed under Section 906.0, Vent
Termination.
1103.2 Where Not Required. No trap shall be
required for leaders or conductors 1jiat are connected
to a sewer carrying storm water exclusively.
1103.3 Trap Size. Traps, when installed for
individual conductors, shall be the same size as the
horizontal drain to which they are cormected.
1103.4 Method of Installation of Combined Sewer.
Individual storm-water traps shall be installed on the
storm-water drain branch serving each storm-water
inlet, or a single trap shall be installed in the main
storm drain just before its connection with the
combined building sewer. Such traps shall be
provided with an accessible cleanout on the outlet
side of the trap.
1104.0 Leaders, Conductors, and Connections.
1104.1 Improper Use. Leaders or conductors shall
not be used as soil, waste, or vent pipes nor shall
soil, waste, or vent pipes be used as leaders or
conductors.
1104.2 Protection of Leaders. Leaders installed
along alle5rways, driveways, or other locations where
they may be exposed to damage shall be protected
by metal guards, recessed into the wall, or
constructed from ferrous pipe.
1104.3 Combining Storm with Sanitary Drainage.
The sanitary and storm drainage system of a
building shall be entirely separate, except where a
combined sewer is used, in which case the building
storm drain shall be connected in the same
horizontal plane through single wye fittings to the
combined building sewer at least ten (10) feet (3,048
mm) downstream from any soil stack.
1105.0 Roof Drains.
1t05.1 Material.
1105.1.1 Roof drains shall be constructed of
materials specified in Table 14-1.
139
1105.1 -1108.1
UNIFORM PLUMBING CODE
1 1 05.1 .2 Roof drains shall be of cast iron, copper
or copper alloy, lead, or plastic.
1105.2 Dome or Strainer for General Use. All roof
drains and overflow drains, except those draining to
hanging gutters, shall be equipped with strainers
extending not less than four (4) inches (102 mm)
above the surface of the roof immediately adjacent to
the drain. Strainers shall have a minimum inlet area
above the roof level of not less than one and one-half
(1-1/2) times the area of the conductor or leader to
which the drain is connected.
1105.3 Strainers for Flat Decks. Roof drain strainers
for use on sun decks, parking decks, and similar areas
tliat are normally serviced and maintained may be of
the flat surface type. Such roof drain strainers shall be
level with the deck and shall have an available inlet
area of no less than two (2) tinies the area of the
conductor or leader to which the drain is connected.
1105.4 Roof Drain Flashings. Connection between
the roof and roof drains that pass through the roof
and into the interior of the building shall be made
watertight by the use of proper flashing material.
1105.4.1 Where lead flashing material is used, it
shall be a minimum of four (4) pounds per
square foot (19.5 kg/m^).
1105.4.2 Where copper flashing material is
used, it shall be a minimum of twelve (12)
ounces per square foot (3.7 kg/m^).
1106.0 Size of Leaders, Conductors, and Storm
Drains.
1106.1 Vertical Conductors and Leaders. Vertical
conductors and leaders shall be sized on the basis of
the maximum projected roof area and Table 11-1.
1106.2 Size of Horizontal Storm Drains and
Sewers. The size of building storm drains or building
storm sewers or any of their horizontal branches shall
be based upon the maximum projected roof or paved
area to be handled and Table 11-2.
1106.3 Size of Roof Gutters. The size of semi-
circular gutters shall be based on the maximum
projected roof area and Table 11-3.
1106.4 Side Walls Draining onto a Roof. Where
vertical walls project above a roof so as to permit
storm water to drain to the roof area below, the
adjacent roof area may be computed from Table 11-1
as follows:
(1) For one (1) wall - add fifty (50) percent of
the wall area to the roof area figures.
(2) For two (2) adjacent walls - add thirty-five
(35) percent of the total wall areas.
(3) Two (2) opposite walls of same height - add
no additional area.
(4) Two (2) opposite walls of differing heights-
add fifty (50) percent of the wall area above
the top of lower wall.
(5) Walls on three (3) sides - add fifty (50)
percent of the area of the inner wall below
the top of the lowest wall, plus allowance
for the area of the wall above the top of the
lowest wall, per (2) and (4) above.
(6) Walls on four (4) sides - no allowance for
wall areas below the top of the lowest wall -
add for areas above the top of the lowest
wall per (1), (2), (4), and (5) above.
1107.0 Values for Continuous Flow.
Where there is a continuous or semi-continuous
discharge into the building storm drain or building
storm sewer, as from a pump, ejector, air-
conditioning plant, or similar device, one (1) gpm
(3.8 L/min.) of such discharge shall be computed as
being equivalent to twenty-four (24) square feet (2.2
m^) of roof area, based upon a rate of rainfall of four
(4) inches (102 mm) per hour.
1108.0 Controlled-Flow Roof Drainage.
1108.1 Application. In lieu of sizing the storm
drainage system in accordance with Section 1106.0,
the roof drainage may be sized on the basis of
controlled flow and storage of the storm water on the
roof, provided the following conditions are met:
(1) The water from a 25-year-frequency storm
shall not be stored on the roof for more than
twenty-four (24) hours.
(2) During the storm, the water depth on the
roof shall not exceed the depths specified in
Table 11-4.
TABLE 11-4
Controlled-Flow Maximum Roof Water Depth
Roof Rise,*
Max Water Depth at Drain,
Inches (mm)
Inches
(mm)
Flat (Flat)
3
(76)
2 (51)
4
(102)
4 (102)
5
(127)
6 (152)
6
(152)
*Vertical measurement from the roof surface at the drain to the highest
point of the roof surface served by the drain, ignoring any local
depression immediately adjacent to the drain.
(3) No less than two (2) drains shall be installed
in roof areas of ten thousand (10,000) square
feet (929.0 m^) or less, and no less than one
(1) additional drain shall be installed for
140
STORM DRAINAGE
1108.1 -1109.2
each ten thousand (10,000) square feet (929.0
m^) of roof area over ten thousand (10,000)
square feet (929.0 m^).
(4) Each roof drain shall have a precalibrated,
fixed (nonadjustable), and proportional
weir (notched) in a standing water
collar inside the strainer. No mechanical
devices or valves shall be allowed.
(5) Pipe sizing shall be based on the pre-
calibrated rate of flow (gpm) of the pre-
calibrated weir for the maximum allowable
water depth, and Tables 11-1 and 11-2.
(6) The height of stones or other granular
material above the waterproofed surface
shall not be considered in water depth
measurement, and the roof surface in the
vicinity of the drain shall not be recessed to
create a reservoir.
(7) Roof design, where controlled-flow roof
drainage is used, shall be such that the
minimum design roof live load is thirty (30)
pounds per square foot (146.5kg/m^) to
provide a safety factor above the fifteen (15)
pounds per square foot (73.2kg/m^)
represented by the depth of water stored on
the roof as indicated in Table 11-4.
(8) Scuppers shall be provided in parapet walls.
The distance of scupper bottoms above the
roof level at the drains shall not exceed the
maximum distances specified in Table 11-5.
TABLE 11-5
Distance of Scupper Bottoms Above Roof
Maximum Distance of
Scupper Bottom
Roof Rise,*
Above Roof Level at Drains,
Inches (mm)
Inches (mm)
Flat (Flat)
3 (76.2) .
2 (51)
4 (102.0)
4 (102)
5 (127.0)
6 (152)
6 (152.0)
*Vertical measurement from the roof surface at the drain to the highest
point of the roof surface served by the drain, ignoring any local
depression immediately adjacent to the drain.
(9) Scupper openings shall be a minimum of 4
inches high and have a width equal to the
circumference of the roof drain required for
the area served, sized by Table 11-1.
(10) Flashings shall extend above the top of the
scuppers.
(11) At any wall or parapet, forty-five (45)
degree (0.79 rad) cants shall be installed.
(12) Separate storm and sanitary drainage
systems shall be provided within the
building.
(13) Calculations for the roof drainage system
shall be submitted along with the plans to
the Authority Having Jurisdiction for
approval.
1108.2 Setback Roofs. Drains on setback roofs may
be connected to the controlled-flow drainage systems
provided:
(1) The setback is designed for storing water, or
(2) The square footage of the setback drainage
area is converted as outlined in Section
1108.0 to gpm, and the storm-water pipe
sizes in the controlled-flow system are
based on the sum of the loads.
(3) The branch from each of the roof drains that
are not provided with controlled flow shall
be sized in accordance with Table 11-1.
1109.0 Testing.
1109.1 Testing Required. New building storm
drainage systems and parts of existing systems that
have been altered, extended, or repaired shall be
tested as described in Section 1109.2.1 to disclose
leaks and defects.
1109.2 Methods of Testing Storm Drainage
Systems. Except for outside leaders and perforated
or open-jointed drain tile, the piping of storm drain
systems shall be tested upon completion of the rough
piping installation by water or air, and proved tight.
The Authority Having Jurisdiction may require the
removal of any cleanout plugs to ascertain whether
the pressure has reached all parts of the system.
Either of the following test methods shall be used:
1109.2.1 Water Test, After piping has been
installed, the w^ater test shall be applied to the
drainage system, either to the entire system or to
sections. If the test is applied to the entire system,
all openings in the piping shall be tightly closed
except for the highest opening, and the system
shall be filled with water to the point of
overflow. If the system is tested in sections, each
opening shall be tightly plugged except for the
highest opening of the section under test, and
each section shall be filled with water, but no
section shall be tested with less than a ten (10)
foot (3,048 mm) head of water. In testing
successive sections, at least the upper ten (10) feet
(3,048 mm) of the next preceding section shaU be
tested so that no joint of pipe in the building
(except the uppermost ten (10) foot (3,048 mm) of
a roof drainage system, which shall be filled with
141
1109.2
UNIFORM PLUMBING CODE
water to the flood level of the uppermost roof
drain) shall have been submitted to a test of less
than a ten (10) foot (3048 mm) head of water. The
water shall be kept in the system or in the
portion under test for at least fifteen (15) minutes
before inspection starts; the system shall then be
tight at all points.
1109.2.2 Air Test. The air test shall be made by
attaching an air compressor testing apparatus to
any suitable opening after closing all other inlets
and outlets to the system, forcing air into the
system until there is a uniform gauge pressure of
five (5) psi (34.5 kPa) or sufficient pressure to
balance a column of mercury ten (10) inches (254
mm) in height. This pressure shall be held without
introduction of additional air for a period of at
least fifteen (15) minutes. Schedule 40 plastic DWV
systems shall not be tested by the air test method.
1109.2.3 Exceptions. When circumstances
exist that make air and water tests described in
Sections 1109.2.1 and 1109.2.2 above impractical,
see Section 103.5.3.3.
142
STORM DRAINAGE
Table 11-1
TABLE 11-1
Sizing Roof Drains, Leaders, and Vertical Rainwater Piping'
Size of Drain,
Maximum Allowable Horizontal Projected Roof Areas
Leader, or Pipe,
Flow,
Square
Feet at Various Rainfall Rates
Indies
gpm
1 \nJh
2inyh
3\nJh
4 inTh 5 inJh
Sinyh
2
23
2,176
1,088
725
544 435
363
3
67
6440
3,220
2,147
1,610 1,288
1,073
4
144
13,840
6,920
4,613
3,460 2,768
2,307
5
261
25,120
12,560
8,373
6,280 5,024
4,187
6
424
40,800
20,400
13,600
10,200 8,160
6,800
8
913
88,000
44,000
29,333
22,000 17,600
14,667
TABLE 11-1 (Metric)
Sizing Roof Drains, Leaders, and Vertical Rainwater Piping"
Size of Drain
Leader or Pipe, Flow,
mm L/s
Maximum Allowable Horizontal Projected Roof Areas
Square Meters at Various Rainfall Rates
25mm/h 50 mm/h 75 mm/h 100mm/h 125mm/h 150 mm/h
50
1.5
202
101
67
51
40
34
80
4.2
600
300
200
150
120
100
100
9.1
1,286
643
429
321
257
214
125
16.5
2,334
1,117
778
583
467
389
150
26.8
3,790
1,895
1,263
948
758
632
200
57.6
8,175
4,088
2,725
2,044
1,635
1,363
Notes:
1 . The sizing data for vertical conductors, leaders, and drains are based on the pipes flowing 7/24 full.
2. For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the
1 inch/hour (25 mm/hour) column by the desired rainfall rate.
3. Vertical piping may be round, square, or rectangular. Square pipe shall be sized to enclose its equivalent
round pipe. Rectangular pipe shall have at least the same cross-sectional area as its equivalent round pipe,
except that the ratio of its side dimensions shall not exceed 3 to 1 .
143
Table 1 1 -2
UNIFORM PLUMBING CODE
TABLE 11-2
Sizing of Horizontal Rainwater Piping'
Size of
Flow at Maximum Allowable Horizontal Projected Roof Areas
Pipe,
1/8 in^ft. Slope, Square
Feet at Various Rainfall Rates
Inches
gpm
1 inTh 2 mJh
3 inyh
4inyh
5'mJh
6 \nJi\
3
34 3,288 1 ,644
1,096
822
657
548
4
78 7,520 3,760
2,506
1,880
1,504
1,253
5
139 13,360 6,680
4,453
3,340
2,672
2,227
6
222 21,400 10,700
7,133
5,350
4,280
3,566
8
478 46,000 23,000
15,330
1 1 ,500
9,200
7,670
. 10
860 82,800 41 ,400
27,600
20,700
16,580
13,800
12
1,384 133,200 66,600
44,400
33,300
26,650
22,200
15
2,473 238,000 119,000
79,333
59,500
47,600
39,650
Size of Flow at
Pipe, 1/4 inyft. Slope,
inches gpm
Maximum Allowable Horizontal Projected Roof Areas
Square Feet at Various Rainfall Rates
1 inVh
2in7h
SinTh
4inyh
5 inTh
SinTh
3
4
5
6
8
10
12
15
48
110
196
314
677
1,214
1,953
3,491
4,640
10,600
18,880
30,200
65,200
116,800
188,000
336,000
2,320
5,300
9,440
15,100
32,600
58,400
94,000
168,000
1,546
3,533
6,293
10,066
21 ,733
38,950
62,600
112,000
1,160
2,650
4,720
7,550
16,300
29,200
47,000
84,000
928
2,120
3,776
6,040
13,040
23,350
37,600
67,250
773
1,766
3,146
5,033
10,866
19,450
31,350
56,000
Size of Flow at
Pipe, 1/2 InVft. Slope,
Inches gpm
Maximum Allowable Horizontal Projected Roof Areas
Square Feet at Various Rainfall Rates
1 mJh
2mJh
3 inyh
4lnyh
5 inVh
6 in./h
3
4
5
6
8
10
12
15
68
156
278
445
956
1,721
2,768
4,946
6,576
15,040
26,720
42,800
92,000
165,600
266,400
476,000
3288
7,520
13,360
21 ,400
46,000
82,800
133,200
238,000
2,192
5,010
8,900
14,267
30,650
55,200
88,800
158,700
1,644
3,760
6,680
10,700
23,000
41,400
66,600
119,000
1,310
3,010
5,320
8,580
18,400
33,150
53,200
95,200
1096
2500
4450
7140
15,320
27,600
44,400
79,300
Notes:
1 . The sizing data for horizontal piping are based on the pipes flowing full.
2. For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the
1 inch/hour (25 mm/hour) column by the desired rainfall rate.
144
STORM DRAINAGE
Table 11 -2 (Metric)
TABLE 11-2 (Metric)
Sizing of Horizontal Rainwater Piping'
Size of
Flow at l\/laximum Allowable Horizontal Projected
1 Roof Areas
Pipe,
10 mm/m Slope,
Square 1
Meters at Various Rainfall Rates
mm
L/s
25 mm/h
50 mm/h
75 mm/h
100 mm/h
125 mm/h
150 mm/h
80
2.1 305
153
102
76
61
51
100
4.9 700
350
233
175
140
116
125
8.8 1,241
621
414
310
248
207
150
14.0 1,988
994
663
497
398
331
200
30.2 4,273
2,137
1,424
1,068
855
713
250
54.3 7,692
3,846
2,564
1,923
1,540
1,282
300
87.3 12,375
6,187
4,125
3,094
2,476
2,062
375
156.0 22,110
11,055
7,370
5,528
4,422
3,683
Size of Flow at
Pipe, 20 mm/m Slope,
mm Us
Maximum Allowable Horizontal Projected Roof Areas
Square Meters at Various Rainfall Rates
80
100
125
150
200
250
300
375
3.0
6.9
12.4
19.8
42.7
76.6
123.2
220.2
25 mm/h 50 mm/h 75 mm/h 100 mm/h 125 mm/h 150 mm/h
431
985
1,754
2,806
6,057
10,851
17,465
31,214
216
492
877
1,403
3,029
5,425
8,733
15,607
144
328
585
935
2,019
3,618
5,816
10,405
108
246
438
701
1,514
2,713
4,366
7,804
86
197
351
561
1,211
2,169
3,493
6,248
72
164
292
468
1009
1807
2912
5202
Size of Flow at
Pipe, 40 mm/m Slope,
mm L/s
Maximum Allowable Horizontal Projected Roof Areas
Square Meters at Various Rainfall Rates
80
100
125
150
200
250
300
375
4.3
9.8
17.5
28.1
60.3
108.6
174.6
312.0
25 mm/h 50 mm/h 75 mm/h 100 mm/h 125 mm/h 150 mm/h
611
1,400
2,482
3,976
8,547
15,390
24,749
44,220
305
700
1,241
1,988
4,273
7,695
12,374
22,110
204
465
827
1,325
2,847
5,128
8,250
14,753
153
350
621
994
2,137
3,846
6,187
1 1 ,055
122
280
494
797
1,709
3,080
4,942
8,853
102
232
413
663
1,423
2,564
4,125
7,367
Notes:
1 . The sizing data for horizontal piping are based on the pipes flowing full.
2. For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the
1 inch/hour (25 mm/hour) column by the desired rainfall rate.
145
Table 11-3
UNIFORM PLUMBING CODE
TABLE 11-3
Size of Gutters
Diameter of Gutter
in Inches
Maximum Rainfall in
Inches per Hour
1/16 inyft. Slope
2
3
4
5
6
3
340
226
170
136
113
4
720
' 480
360
288
240
5
1,250
834
625
500
416
6
1,920
1,280
960
768
640
7
2,760
1,840
1 ,380
1,100
918
8
3,980
2,655
1,990
1,590
1,325
10
7,200
4,800
3,600
2,880
2,400
Diameter of Gutter
in Inches
Maximum Rainfall in
Inches per Hour
1/8 inTft. Slope
2
3
4
5
6
3
480
320
240
192
160
4
1,020
681
510
408
340
5
1,760
1,172
880
704
587
6
2,720
1,815
1,360
1,085
905
7
3,900
2,600
1,950
1,560
1,300
8
5,600
3,740
2,800
2,240
1,870
10
10,200
6,800
5,100
4,080
3,400
Diameter of Gutter
in Inches
Maximum Rainfall in
Inches per Hour
1/4 InVft. Slope
2
3
4
5
6
3
680
454
340
272
226
4
1,440
960
720
576
480
5
2,500
1,668
1,250
1,000
834
6
3,840
2,560
1,920
1,536
1,280
7
5,520
3,680
2,760
2,205
1,840
8
7,960
5,310
3,980
3,180
2,655
10
14,400
9,600
7,200
5,750
4,800
Diameter of Gutter
in Inches
Maximum Rainfall in
Inches per Hour
1/2 inVft. Slope
2
3
4
5
6
3
960
640
480
384
320
4
2,040
1,360
1,020
816
680
5
3,540
2,360
1,770
1,415
1,180
6
5,540
3,695
2,770
2,220
1,850
7
7,800
5„200
3,900
3,120
2,600
8
11,200
7,460
5,600
4,480
3,730
10
20,000
13,330
10,000
8,000
6,660
146
STORM DRAINAGE
Table 11-3 (Metric)
TABLE 11-
■3 (Metric)
Size of Gutters
Diameter of
Gutter in mm
Maximum Rainfall In Millimeters
per Hour
5.2 mm/m Slope
50.8
76.2
101.6
127.0
152.4
80
31.6
21.0
15.8
12.6
10.5
100
66.9
44.6
33.4
26.8
22.3
125
116.1
77.5
58.1
46.5
38.7
150
178.4
119.1
89.2
71.4
59.5
175
256.4
170.9
128.2
102.2
85.3
200
369.7
246.7
184.9
147.7
123.1
250
668.9
445.9
334.4
267.6
223.0
Diameter of
Gutter in mm
Maximum Rainfall In Millimeters
per Hour
10.4 mm/m Slope
50.8
76.2
101.6
127.0
152.4
80
44.6
29.7
22.3
17.8
14.9
100
94.8
63.3
47.4
37.9
31.6
25
163.5
108.9
81.8
65.4
54.5
150
252.7
168.6
126.3
100.8
84.1
175
362.3
241.5
181.2
144.9
120.8
200
520.2
347.5
260.1
208.1
173.7
250
947.6
631.7
473.8
379
315.9
Diameter of
Gutter In mm
Maximum Rainfall In Millimeters
per Hour
20.9 mm/m Slope
50.8
76.2
101.6
127.0
152.4
80
63.2
42.2
31.6
25.3
21.0
100
133.8
89.2
66.9
53.5
44.6
125
232.3
155.0
116.1
92.9
77.5
150
356.7
237.8
178.4
142.7
118.9
175
512.8
341.9
256.4
204.9
170.9
200
739.5
493.3
369.7
295.4
246.7
250
133.8
891.8
668.9
534.2
445.9
Diameter of
Gutter in mm
Maximum Rainfall In Millimeters
per Hour
41 .7 mm/m Slope
50.8
76.2
101.6
127.0
152.4
80
89.2
59.5
44.6
35.7
29.7
100
189.5
126.3
94.8
75.8
63.2
125
328.9
219.2
164.4
131.5
109.6
150
514.7
343.3
257.3
206.2
171.9
175
724.6
483.1
362.3
289.9
241.4
200
1,40.5
693.0
520.2
416.2
346.5
250
1 ,858.0
1,238.4
929.0
743.2
618.7
147
UNIFORM PLUMBING CODE
148
CHAPTER 12
FUEL PIPING
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1201.0 Scope of Gas Piping.
(A) Coverage of piping systems shall extend
from the point of delivery to the connections
with each gas utilization device. For other
than undiluted liquefied petroleum gas
systems, the point of delivery shall be
considered the outlet of the service meter
assembly, or the outlet of the service
regulator or service shutoff valve where no
meter is provided. For undiluted liquefied
petroleum gas systems, the point of delivery
shall be considered the outlet of the final
pressure regulator, exclusive of the line gas
regulators, in the system. [NFPA 54: 1.1.1.1(A)]
(B) Piping systems requirements shall include
design, materials, components, fabrications,
assembly, installation, testing inspection,
operation, and maintenance. [NFPA 54: 1.1.1.1(C)]
(C) This code shall not apply to the following
(reference standards for some of which
appear in Appendix L [NFPA 54: 1.1.1.2]):
(1) Portable LP-Gas equipment of all
types that is not connected to a
fixed fuel piping system.
(2) Installation of farm equipment such
as brooders, dehydrators, dryers,
and irrigation equipment.
(3) Raw material (feedstock) applications,
except for piping to special
atmosphere generators.
(4) Oxygen-fuel gas cutting and
welding systems.
(5) Industrial gas applications using
gases such as acetylene and acetylenic
compounds, hydrogen, ammonia,
carbon monoxide, oxygen, and nitrogen.
(6) Petroleum refineries, pipeline
compressor or pumping stations,
loading terminals, compounding
plants, refinery tank farms, and
natural gas processing plants.
(7) Large integrated chemical plants or
portions of such plants where
flammable or combustible liquids
or gases are produced by chemical
reactions or used in chemical
reactions.
(8) LP-Gas installations at utility gas
plants.
(9) Liquefied natural gas (LNG)
installations.
(10) Fuel gas piping in power and
atomic energy plants.
(11) Proprietary items of equipment,
apparatus, or instruments such as
gas-generating sets, compressors,
and calorim.eters.
(12) LP-Gas equipment for vaporization,
gas mixing, and gas m^anufacturing.
(13) LP-Gas piping for buildings under
construction or renovations that are
not to become part of the
permanent building piping system —
that is, temporary fixed piping for
building heat.
(14) Installation of LP-Gas systems for
railroad switch heating.
(15) Installation of LP-Gas and comp-
ressed natural gas systems on vehicles.
(16) Gas piping, meters, gas-pressure
regulators, and ottier appurtenances
used by the serving gas supplier in
distribution of gas, other than
undiluted LP-Gas.
1202.0 General.
The regulations of this chapter shall govern the
installation of all fuel gas piping ui or in connection
with any building or structure or within the property
lines of any premises up to 5 psi, other than service
pipe. Fuel oil piping systems shall be installed in
accordance with NFPA 31.
1203.0 Definitions.
For the purposes of this code, these definitions shall
apply to this chapter. Certain terms, phrases, words.,
and their derivatives shall be interpreted as set forth
in this section, provided, however, that whenever the
words "gas meters" appear, they shall be construed
to also mean valves and those devices required for
the regulation of pressure and the measurement of
natural gas being dispensed for any building,
structure, or premises.
1203.1 Appliance Fuel Connector - An assembly
of listed semi-rigid or flexible tubing and fittings to
carry fuel between a fuel-piping outlet and a fuel-
burning appliance.
1 203.2 Fuel Gas - Natural, manufactured, liquefied
petroleum, or a mixture of these.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
149
1203.3-1206.1
UNIFORM PLUMBING CODE
1203.3 Gas Piping - Any installation of pipe,
valves, or fittings that is used to convey fuel gas,
installed on any premises or in any building, but
shall not include:
(1) Any portion of the service piping.
(2) Any approved piping connection six (6) feet
(1,829 mm) or less in length between an
existing gas outlet and a gas appliance
in the same rooni with the outlet.
1203.4 Gas-Piping System - Any arrangement of gas
piping supplied by one (1) meter, and each arrange-
ment of gas piping serying a building, structure, or
premises, whether individually metered or not.
1203.5 Liquefied Petroleum Gas (LPG) Facilities -
Liquefied petroleum gas (LPG) facilities means
tanks, containers, container valves, regulating
equipment, meters, and /or appurtenances for the
storage and supply of liquefied petroleum gas for
any building, structure, or premises.
NFPA 1203.6 Provision for Location of Point of Delivery -
NFPA
NFPA The location of the point of delivery shall be
NFPA acceptable to the serving gas supplier. [NFPA 54: 5.2]
1203.7 Quick-Disconnect Device - A hand-
operated device that provides a means for connecting
and disconnecting an appliance or an appliance
connector to a gas supply and that is equipped with
an automatic means to shut off the gas supply when
the device is disconnected.
1203.8 Service Piping - The piping and equipment
between the street gas main and the gas piping
system inlet that is installed by, and is under the
control and maintenance of, the serving gas supplier.
1203.9 Transition Gas Riser - Any listed or
approved section or sections of pipe and fittings
used to convey fuel gas and installed in a gas piping
system for the purpose of providing a transition
from belowground to aboveground.
1204.0 Inspection.
1204.1 Upon completion of the installation, altera-
tion, or repair of any gas piping, and prior to the use
thereof, the Authority Having Jurisdiction shall be
notified that such gas piping is ready for inspection.
1204.2 All excavations required for the installation
of underground piping shall be kept open until such
time as the piping has been inspected and approved.
If any such piping is covered or concealed before
such approval, it shall be exposed upon the direction
of the Authority Having Jurisdiction.
1 204.3 The Authority Having Jurisdiction shall make
the following inspections and either shall approve
that portion of the work as completed or shall notify
the permit holder wherein the same fails to comply
with this code.
1204.3.1 Rough Piping Inspection.
This inspection shall be made after all gas piping
authorized by the permit has been installed and
before any such piping has been covered or
concealed or any fixture or appliance has been
attached thereto. This inspection shall include a
determination that the gas-piping size, material,
and installation meet the requirements of this code.
1204.3.2 Final Piping Inspection.
This inspection shall be made after all piping
authorized by the permit has been installed and
after all portions thereof that are to be covered or
concealed are so concealed and before any
fixtures, appliance, or shutoff valve has been
attached thereto. This inspection shall be in
accordance with Section 1214.1. Test gauges
used in conducting tests shall comply with
Section 319.0, Test Gauges.
1204.4 In cases where the work authorized by the
permit consists of a minor installation of additional
piping to piping already connected to a gas meter,
the foregoing inspections may be waived at the
discretion of the Authority Having Jurisdiction. In
this event, the Authority Having Jurisdiction shall
make such inspection as deemed advisable in order
to be assured that the work has been performed in
accordance with the intent of this code.
1205.0 Certificate of Inspection.
1205.1 If, upon final piping inspection, the
installation is found to comply with the provisions of
this code, a certificate of inspection may be issued by
the Authority Having Jurisdiction.
1 205.2 A copy of the certificate of such final piping
inspection shall be issued to the serving gas supplier
supplying gas to the premises.
1205.3 It shall be unlawful for any serving gas
supplier, or person furnishing gas, to turn on or
cause to be turned on, any fuel gas or any gas meter
or meters, until such certificate of final inspection, as
herein provided, has been issued.
1206.0 Authority to Render Gas Service.
1206.1 It shall be unlawful for any person, firm, or
corporation, excepting an authorized agent or
employee of a person, firm, or corporation engaged
in the business of furnishing or supplying gas and
whose service pipes supply or connect with the
particular premises, to turn on or reconnect gas
service in or on any premises where and when gas
service is, at the time, not being rendered.
150
FUEL PIPING
1206.2-1209.4
1 206.2 It shall be unlawful to turn on or connect gas
in or on any premises unless all outlets are properly
and securely connected to gas appliances or capped
or plugged with screw joint fittings.
1207.0 Authority to Disconnect.
1207.1 The Authority Having Jurisdiction or the
serving gas supplier is hereby authorized to
disconnect any gas piping or appliance or both that
shall be found not to conform to the requirements of
this code or that may be found defective and in. such
condition as to endanger life or property.
1207.2 Where such disconnection has been made, a
notice shall be attached to such gas piping or
appliance or both that shall state the same has been
disconnected, together with the reasons thereof.
1207.3 It shall be unlawful to remove or disconnect
any gas piping or gas appliance without capping or
plugging with a screw joint fitting the outlet from
which said pipe or appliance was removed. All
outlets to which gas appliances are not connected
shall be left capped gastight on any piping system
that has been installed, altered, or repaired.
Exception: When an approved listed quick-
disconnect device is used.
1208.0 Temporary Use of Gas.
Where temporary use of gas is desired and the
Authority Having Jurisdiction deems the use
necessary, a permit may be issued for such use for a
period of time not to exceed that designated by the
Authority Having Jurisdiction, provided that such
gas-piping system otherwise conforms to the
requirements of this code regarding material, sizing,
and safety.
1209.0 Gas-Piping System Design, Materials, and
Components.
1209.1 Piping Plan.
1209.1.1 Installation of Piping System. Where
required by the Authority Having Jurisdiction, a
piping sketch or plan shall be prepared before
proceeding with the installation. This plan shall
show the proposed location of piping, the size of
different branches, the various load demands,
and the location of the point of delivery.
1209.1.2 Addition to Existing System. When
additional gas utilization equipment is being
connected to a gas-piping system, the existing
piping shall be checked to determine whether it
has adequate capacity (see Section 1209.4.3). If
inadequate, the existing system shall be enlarged
as required, or separate gas piping of adequate
capacity shall be provided.
1209.2 Provision for Location of Point of Delivery.
The location of the point of delivery shall be
acceptable to the serving gas supplier.
1209.3 Interconnections Between Gas-Piping
Systems.
1209.3.1 Interconnections Supplying Separate
Users. Where two or more meters, or two or
more service regulators where meters are not
provided, are located on the same premises and
supply separate users, the gas-piping systems
shall not be interconnected on the outlet side of
the meters or service regulators.
1209.3.2 Interconnections for Standby Fuels.
Where a supplementary gas for standby use is
connected downstream from a meter or a service
regulator where a meter is not provided, a device
to prevent backflow shall be installed. A three-
way valve installed to admit the standby supply
and, at the same time, shut off the regular supply,
shall be permitted to be used for this purpose.
1209.4 Sizing of Gas-Piping Systems.
1209.4.1 General Considerations. Gas-piping
systems shall be of such size and so installed as to
provide a supply of gas sufficient to meet the
niaximum demand without undue loss of pressure
between the point of delivery and the gas
utilization equipment.
1209.4.2 Maximum Gas Demand. The volume
of gas to be provided (in cubic feet per hour) shall
be determined directly from the manufacturer's
input ratings of the gas utilization equipment
served. Where the input rating is not indicated,
the gas supplier, equipment manufacturer, or a
qualified agency shall be contacted or the rating
from Table 12-1 shall be used for estimating the
volume of gas to be supplied. The total connected
hourly load shall be used as the basis for piping
sizing, assuming all equipment is operating at
full capacity simultaneously.
Exception: Sizing shall be permitted to be
based upon established load diversity factors.
151
Table 12-1 -1209.5
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
TABLE 12-1
Approximate Gas Input for Typical Appliances
Appliance Input Btu^. (Approx.)
Space Heating Units
Warm air furnace
Single family
100,000
Multifamily, per unit
60,000
Hydronic boiler
Single family
100,000
Multifamily, per unit
60,000
Space-and Water-Heating Units
Hydronic boiler
Single family
120,000
Multifamily, per unit
75,000
Water-Heating Appliances
Water heater, automatic
storage 30 to 40 gal. tank
35,000
Water heater, automatic
storage 50 gal. tank
50,000
Water heater, automatic instantaneous
Capacity at 2 gal. /minute
142,800
Capacity at 4 gal. /minute
285,000
Capacity at 6 gal. /minute
428,400
Water heater, domestic.
circulating or side-arm
35,000
Cooking Appliances
Range, freestanding.
domestic
65,000
Built-in oven or broiler unit.
domestic
25,000
Built-in top unit.
domestic
40,000
Other Appliances
Refrigerator
3,000
Clothes dryer. Type 1
(domestic)
35,000
Gas fireplace direct vent
40,000
Gas log
80,000
Barbecue
40,000
Gaslight
2,500
For SI units: 1 Bhi per hour = 0.293 W
[NFPA 54: Table 5.4.2.1]
1209.4.3 Sizing Methods. Gas piping shall be
sized in accordance with one of the following:
[NFPA 54: 5.4.3]
(1) Pipe sizing tables or sizing equations in this
chapter.
(2) Other approved engineering methods
acceptable to the Authority Having
Jurisdiction.
(3) Sizing tables included in a listed piping
system manufacturer's installation
instructions.
1209.4.4 Allowable Pressure Drop. The design
pressure loss in any piping system under
maximum "probable flow conditions, from the
point of delivery to the inlet connection of the
gas utilization equipment, shall be such that the
supply pressure at the equipment is greater than
the minimum pressure required for proper
equipment operation. [NFPA 54: 5.4.4]
1209.5 Acceptable Piping Materials and Joining
Methods.
1209.5.1 General.
1209.5.1.1 Materials. Materials used for
piping systems shall comply with the
requirements of this chapter or shall be
acceptable to the Authority Having
Jurisdiction. [NFPA 54: 5.6.1.1]
1209.5.1.2 Used Materials. Pipe, fittings,
valves, or other materials shall not be used
again unless they are free of foreign materials
and have been ascertained to be adequate for
the service intended. [NFPA 54: 5.6.1.2]
1209.5.1.3 Other Materials. Material not
covered by the standards specifications listed
herein shall be investigated and tested to
determine that it is safe and suitable for the
proposed service and, in addition, shall be
recommended for that service by the
manufacturer and shall be acceptable to the
Authority Having Jurisdiction. [NFPA 54: 5.6.1.3]
1209.5.2 Metallic Pipe.
1209.5.2.1 Cast-iron pipe shall not be used.
[NFPA 54: 5.6.2.1]
1209.5.2.2 Steel and wrought-iron pipe
shall be at least of standard weight
(Schedule 40) and shall comply with one of
the following standards: [NFPA 54: 5.6.2.2]
(1) ANSI/ASME B36.10, Welded and
Seamless Wrought-Steel Pipe
(2) ASTM A 53, Standard Specification
for Pipe, Steel, Black and Hot-Dipped, Zinc-
Coated Welded and Seamless
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
152
FUEL PIPING
1209.5
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA ,
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(3) ASTM A 106, Standard Specification for
Seamless Carbon Steel Pipe for High-
Temperature Service
1209.5.2.3 Copper and brass pipe shall riot be
used if the gas contains more than an average
of 0.3 grains of hydrogen sulfide per 100 scf of
gas (0.7 mg/100 L). [NFPA 54: 5.6.2.3]
Threaded copper, brass, or aluminum
alloy pipe shall not be used with gases
corrosive to such material. [NFPA 54: 5.6.2.4]
1209.5.2.4 Aluminum alloy pipe shall
comply with ASTM B 241, Specification for
Aluminum-Alloy Seamless Pipe and Seamless
Extruded Tube (except that the use of alloy
5456 is prohibited) and shall be marked at
each end of each length indicating
compliance. Aluminum alloy pipe shall be
coated to protect against external corrosion
where it is in contact with masonry, plaster, or
insulation or is subject to repeated wettings
by such liquids as water, detergents, or
sewage. [NFPA 54: 5.6.2.5] Aluminum alloy
pipe shall not be used in exterior locations or
underground. [NFPA 54: 5.6.2.6]
1209.5.3 Metallic Tubing. Seamless copper,
aluminum alloy, or steel tubing shall not be used
with gases corrosive to such material. [NFPA 54:
5.6.3]
1209.5.3.1 Steel tubing shall comply with
ASTM A 539, Standard Specification for
Electric Resistance-Welded Coiled Steel Tubing
for Gas and Fuel Oil Lines, or ASTM A 254,
Standard Specification for Copper Brazed Steel
Tubing. [NFPA 54: 5.6.3.1]
1209.5.3.2 Copper and brass tubing shall
not be used if the gas contains more than an
average of 0.3 g of hydrogen sulfide per 100
scf of gas (0.7 mg/100 L). Copper tubing
shall comply with standard Type K or L of
ASTM B 88, Specification for Seamless Copper
Water Tube, or ASTM B 280, Specification for
Seamless Copper Tube for Air-Conditioning and
Refrigeration Field Service. [NFPA 54: 5.6.3.2]
1209.5.3.3 Aluminum alloy tubing shall
comply with ASTM B 210, Specification for
Aluminum-Alloy Drawn Seamless Tubes, or
ASTM B 241, Specification for Aluminum Alloy
Seamless Pipe and Seamless Extruded Tube.
Aluminum alloy tubing shall be coated to
protect against external corrosion where it is
in contact with masonry, plaster, or
insulation or is subject to repeated wettings
by liquids such as water, detergent, or
sewage. Aluminum alloy tubing shall not be
used in exterior locations or underground.
[NFPA 54: 5.6.3.3]
1 209.5.3.4 Corrugated stainless steel tubing
shall be tested and listed in compliance with
the construction, installation, and performance
requirements of ANSI /IAS LC-1, Standard
for Fuel Gas Piping Systems Using Corrugated
Stainless Steel Tubing. [NFPA 54: 5.6.3.4]
1209.5.4 Plastic Pipe, Tubing, and Fittings.
Plastic pipe, tubing, and fittings shall be used
outside underground only and shall conform
with ASTM D 2513, Standard Specification for
Thermoplastic Gas Pressure Pipe, Tubing, and
Fittings. Pipe to be used shall be marked "gas"
and "ASTM D 2513." [NFPA 54: 5.6.4]
Anodeless risers shall comply with the
following: [NFPA 54: 5.6.4.1]
1209.5.4.1 Factory-assembled anodeless
risers shall be recommended by the
manufacturer for the gas used and shall be
leak-tested by the manufacturer in
accordance with written procedures. [NFPA
54: 5.6.4.1(1)]
1 209.5.4.2 Service head adapters and field-
assembled anodeless risers incorporating
service head adapters shall be
recommended by the manufacturer for the
gas used by the manufacturer and shall be
design-certified to meet the requirements of
Category I of ASTM F 1973, Factory
Assembled Anodeless Riser and Transition
Fitting on Polyethylene (PE) Fuel Gas
Distribution Systems and the code of Federal
Regulations, Title 49, Part 192.281(e). The
manufacturer shall provide the user with
qualified installation instructions as
prescribed by the code of Federal
Regulations, Title 49, Part 192.283(b). [NFPA
54: 5.6.4.1(2)]
1209.5.4.3 The use of plastic pipe, tubing,
and fittings in undiluted liquefied
petroleum gas-piping systems shall be in
accordance with NFPA 58, Liquefied
Petroleum Gas Code. [NFPA 54: 5.6.4.1(3)]
1209.5.5 Workmanship and Defects. Gas pipe
or tubing and fittings shall be clear and free from
cutting burrs and defects in structure or
threading, and shall be thoroughly brushed and
chip and scale blown. Defects in pipe, tubing,
and fittings shall not be repaired. Defective
pipe, tubing, and fittings shall be replaced.
[NFPA 54: 5.6.5]
1209.5.6 Protective Coating. Where in contact
with material or atmosphere exerting a corrosive
action, metallic piping and fittings coated with a
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
153
1209.5
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
corrosion-resistant material shall be used.
External or internal coatings or linings used on
piping or components shall not be considered as
adding strength. [NFPA 54: 5.6.6]
1209.5.7 Metallic Pipe Threads.
(A) Specifications for Pipe Threads. Metallic
pipe and fitting threads shall be taper pipe
threads and shall comply with ANSI/ASME
Bl.20.1, Standard for Pipe Threads, General
Purpose (Inch). [MFPA 54: 5.6.7.1]
(B) Damaged Threads. Pipe with threads that
are stripped, chipped, corroded, or otherwise
damaged shall not be used. Where a weld
opens during the operation of cutting or
threading, that portion of the pipe shall not
be used. [NPPA 54: 5.6.7.2]
(C) Number of Threads. Field threading of
metallic pipe shall be in accordance with
Table 12-2. [NFPA 54: 5.6.7.3]
(D) Thread Compounds. Thread (joint)
compounds (pipe dope) shall be resistant to
the action of liquefied petroleum gas or to
any other chemical constituents of the gases
to be conducted through the piping.
TABLE 12-2
Specifications for Threading Metallic Pipe
Approximate Length
Approximate
Iron Pipe
of Threaded
No. of
Size (in.)
Portion (in.)
Threads to Be Cut
1/2
3/4
10
3/4
3/4
10
1
7/8
10
1-1/4
1
11
1-1/2
1
11
2
1
11
2-1/2
1-1/2
12
3
1-1/2
12
4
1-5/8
13
For SI units, 1 in. = 25.4 mm. [NFPA 54: 5.6.7.3]
1209.5.8 Metallic Piping Joints and Fittings.
The type of piping joint used shall be suitable for
the pressure-temperature conditions and shall
be selected giving consideration to joint
tightness and mechanical strength under the
service conditions. The joint shall be able to
sustain the maximum end force due to the
internal pressure and any additional forces due
to temperature expansion or contraction,
vibration, fatigue, or to the weight of the pipe
and its contents. [NFPA 54: 5.6.8]
1209.5.8.1 Pipe Joints. Pipe joints shall be
threaded, flanged, brazed, or welded.
Where nonferrous pipe is brazed, the
brazing materials shall have a melting point
in excess of 1,000°F (538°C). Brazing alloys
shall not contain more than 0.05 percent
phosphorus. [NFPA 54: 5.6.8.1]
1209.5.8.2 Tubing Joints. Tubing joints
shall either be made with approved gas
tubing fittings or be brazed with a material
having a melting point in excess of 1,000°F
(538°C). Brazing alloys shall not contain
more than 0.05 percent phosphorus. [NFPA
54:5.6.8.2]
1209.5.8.3 Flared Joints. Flared joints
shall be used only in systems constructed
from nonferrous pipe and tubing where
experience or tests have demonstrated that
the joint is suitable for the conditions and
where provisions are made in the design to
prevent separation of the joints. [NFPA 54:
5.6.8.3]
1209.5.8.4 Metallic Fittings (Including
Valves, Strainers, Filters). [NFPA 54:
5.6.8.4]
(1) Threaded fittings in sizes larger than 4
in. (100 mm) shall not be used unless
acceptable to the Authority Having
Jurisdiction.
(2) Fittings used with steel or wrought-iron
pipe shall be steel, brass, bronze,
malleable iron, or cast iron.
(3) Fittings used with copper or brass pipe
shall be copper, brass, or bronze.
(4) Fittings used with aluminum alloy pipe
shall be of aluminum alloy.
(5) Cast-iron Fittings.
(a) Flanges shall be permitted.
(b) Bushings shall not be used.
(c) Fittings shall not be used in
systems containing flammable
gas-air mixtures.
(d) Fittings in sizes 4 inches (100 mm)
and larger shall not be used
indoors unless approved by the
Authority Having Jurisdiction.
(e) Fittings in sizes 6 inches (150 mm)
and larger shall not be used
unless approved by the
Authority Having Jurisdiction.
(6) Aluminum Alloy Fittings. Threads shall
not form the joint seal.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
154
FUEL PIPING
1209.5 -1209.6
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(7) Zinc-Aluminum Alloy Fittings. Fittings
shall not be used in systems containing
flammable gas-air n\ixtures.
(8) Special Fittings. Fittings such as
couplings; proprietary-type joints;
saddle tees; gland-type compression
fittings; and flared, flareless, or
compression-type tubing fittings
shall be (1) used within the fitting
manufacturers' pressure-temperature
recommendations; (2) used within the
service conditions anticipated with
respect to vibration, fatigue, thermal
expansion, or contraction; (3) installed
or braced to prevent separation of the
joint by gas pressure or external
physical damage; and (4) acceptable to
the Authority Having Jurisdiction.
1209.5.9 Plastic Piping, Joints, and
Fittings.
Plastic pipe, tubing, and fittings shall be
joined in accordance with the manufacturers'
instructions. The following shall be observed
when making such joints: [NFPA 54: 5.6.9]
(A) The joint shall be designed and installed
so that the longitudinal puUout
resistance of the joint will be at least
equal to the tensile strength of the plastic
piping material. [NFPA 54: 5.6.9(1)]
(B) Heat-fusion joints shall be made in
accordance with qualified procedures that
have been established and proven by test
to produce gastight joints at least as
strong as the pipe or tubing being joined.
Joints shall be made with the joining
method recommended by the pipe
manufacturer. Heat-fusion fittings shall
be marked "ASTM D 2513." [NFPA 54:
5.6.9(2)1
(C) Where compression-type mechanical
joints are used, the gasket material in the
fitting shall be compatible with the
plastic piping and with the gas
distributed by the system. An internal
tubular rigid stiffener shall be used in
conjunction with the fitting. The stiffener
shall be flush with the end of the pipe or
tubing and shall extend at least to the
outside end of the pipe or tubing and
shall extend at least to the outside end of
the compression fitting when installed.
The stiffener shall be free of rough or
sharp edges and shall not be a forced fit
in the plastic. Split tubular stiffeners shall
not be used. [NFPA 54: 5.6.9(3)]
(D) Plastic piping joints and fittings for use
in liquefied petroleum gas-piping
systems shall be in accordance with
Liquefied Petroleum Gas Code, NFPA 58.
[NFPA 54: 5.6.9(4)]
1209.5.10 Flanges. AU flanges shall comply with
ANSI/ASME B16.1, Standard for Cast Iron Pipe
Flanges and Flanged Fittings; ANSI/ASME B16.20,
Standard for Ring-Joint Gaskets and Grooves for Steel
Pipe Flanges; or MSS SP-6, Standard Finishes for
Contact Faces of Pipe Flanges and Connecting-End
Flanges of Valves and Fittings. The pressure-
temperature ratings shall equal or exceed that
required by the application. [NFPA 54: 5.6.10]
(A) Flange Facings. Standard facings shaU be
permitted for use under this code. Where
150-psi (1,090 kPa) steel flanges are bolted to
Class 125 cast-iron flanges, the raised face
on the steel flange shall be removed. [NFPA
54:5.6.10.1]
(B) Lapped Flanges. Lapped flanges shall be used
only aboveground or in exposed locations
accessible for inspection. [NFPA 54: 5.6.10.2]
1209.5.11 Flange Gaskets. The material for
gaskets shall be capable of withstanding the
design temperature and pressure of the piping
system and the chemical constituents of the gas
being conducted without change to its chemical
and physical properties. The effects of fire
exposure to the joint shall be considered in
choosing the material. [NFPA 54: 5.6.11]
(1) Acceptable materials include the following:
[NFPA 54: 5.6.11.1]
(a) Metal or metal-jacketed asbestos (plain
or corrugated)
(b) Asbestos
(c) Aluminum "O" rings and spiral-wound
metal gaskets
(2) When a flanged joint is opened, the gasket
shall be replaced. [NFPA 54: 5.6.11.2]
(3) Full-face gaskets shall be used with all bronze
and cast-iron flanges. [NFPA 54: 5.6.11.3]
1209.6 Gas Meters.
1209.6.1 Capacity. Gas meters shall be selected
for the maximum expected pressure and
permissible pressure drop. [NFPA 54: 5.7.1]
1209.6.2 Location.
(A) Gas meters shall be located in ventilated
spaces readily accessible for examination,
reading, replacement, or necessary
maintenance. [NFPA 54: 5.7.2.1]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
155
1209.6-1209.7
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(B) Gas meters shall not be placed where they
will be subjected to damage, such as
adjacent to a drive w^ay; under a fire escape;
in public passages, halls, or coal bins; or
where they will be subject to excessive
corrosion or vibration. [NFPA 54: 5.7.2.2]
(C) Gas meters shall be located at least 3 feet (0.9
m) from sources of ignition. [NFPA 54: 5.7.2.3]
(D) Gas meters shall not be located where they
will be subjected to extreme temperatures or
sudden extreme changes in temperature.
Meters shall not be located in areas where
they are subjected to temperatures beyond
those recommended by the manufacturer.
[NFPA 54: 5.7.2.4]
1209.6.3 Supports. Gas meters shall be
supported or connected to rigid piping so as not to
exert a strain on the meters. Where flexible
connectors are used to connect a gas meter to
downstream piping at mobile homes in mobile
home parks, the meter shall be supported by a
post or bracket placed in a firm footing or by other
means providing equivalent support. [NFPA 54:
5.7.3]
1209.6.4 Meter Protection. Meters shall be
protected against overpressure, back-pressure,
and vacuum where such conditions are
anticipated. [NFPA 54: 5.7.4]
1209.6.5 Identification. Gas piping at multiple
meter installations shall be marked by a metal
tag or other permanent means attached by the
installing agency, designating the building or
the part of the building being supplied. [NFPA
54:5.7.5]
1209.7 Gas Pressure Regulators.
1209.7.1 Where Required. A line gas pressure
regulator or gas equipment pressure regulator,
as applicable, shall be installed where the gas
supply pressure is higher than that at which the
branch supply line or gas utilization equipment
is designed to operate or varies beyond design
pressure liniits. [NFPA 54: 5.8.1]
1209.7.2 Listing. The line gas pressure regulator
shall be listed in accordance with ANSI Z21.80.
[NFPA 54: 5.8.2]
1209.7.3 Location. The gas pressure regulator
shall be accessible for servicing. [NFPA 54: 5.8.3]
1209.7.4 Regulator Protection. Pressure
regulators shall be protected against physical
damage. [NFPA 54: 5.8.4]
1209.7.5 Venting.
(A) Line Gas Pressure Regulators. [NFPA 54:
5.8.5.1]
(1) An independent vent to the outside of
the building, sized in accordance with
the regulator manufacturer's instructions,
shall be provided where the location of
a regulator is such that a ruptured
diaphragm will cause a hazard. Where
there is more than one regulator at a
location, each regulator shall have a
separate vent to the outside or, if
approved by the Authority Having
Jurisdiction, the vent lines shall be
permitted to be manifolded in
accordance with accepted engineering
practices to minimize back-pressure in
the event of diaphragm failure. [See
NFPA 54:5.9.7] for information on
properly locating the vent.) Materials
for vent piping shall be in accordance
with Section 1209.5.
Exception: A regulator and vent-
limiting means combination listed
as complying with ANSI Z21.80,
Standard for Line Pressure Regulators,
shaU be permitted to be used without
a vent to the outdoors.
(2) The vent shall be designed to prevent
the entry of water, insects, or other
foreign materials that could cause
blockage.
(3) At locations where regulators might be
submerged during floods, a special
antiflood-type breather vent fitting shall
be installed, or the vent line shall be
extended above the height of the
expected flood waters.
(4) A regulator shall not be vented to the
gas equipment flue or exhaust system.
(B) Gas Appliance Pressure Regulators.
Venting of Gas Appliance Pressure Regulators.
Venting of gas appliance pressure regulators shall
comply with the following requirements: [NFPA
54:9.1.19]
(1) Gas appliance pressure regulators requiring
access to the atmosphere for successful operation
shall be equipped with vent piping leading
outdoors or, if the regulator vent is, an integral
part of the equipment, into the combustion
chamber adjacent to a continuous pilot, unless
constructed or equipped with a vent-limiting
means to limit the escape of gas from the vent
opening in the event of diaphragm failure.
(2) Vent-limiting means shall be employed on listed
gas appliance pressure regulators only.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
156
FUEL PIPING
1209.7-1209.11
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA ■
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(4)
(5)
(6)
(3) In the case of vents leading outdoors, means shall
be employed to prevent water from entering this
piping and also to prevent blockage of vents by
insects and foreign matter.
Under no circumstances shall a regulator be
vented to the gas utilization equipment flue or
exhaust system.
In the case of vents entering the combustion
chamber, the vent shall be located so the escaping
gas will be readily ignited by the pilot and the
heat liberated thereby will not adversely affect
the normal operation of the safety shutoff system.
The terminus of the vent shall be securely held in
a fixed position relative to the pilot. For
manufactured gas, the need for aflame arrester in
the vent piping shall be determined.
Vent lines from a gas appliance pressure
regulator and bleed lines from a diaphragm-type
valve shall not be connected to a common
manifold terminating in a combustion chamber.
Vent lines shall not terminate in positive-
pressure- type combustion chambers.
(C) Discharge of Vents [NFFA 54: 5.9.7]
(1) The discharge stacks, vents, or outlet parts of
all pressure-relieving and pressure-limiting
devices shall be located so that gas is safely
discharged into the outside atmosphere.
(2) Discharge stacks or vents shall be designed
to prevent the entry of water, insects, or any
other foreign material that could cause
blockage. The discharge stack or vent line
shall be at least the same size as the outlet of
the pressure-relieving device.
1209.7.6 Bypass Piping. Valved and regulated
bypasses shall be permitted to be placed around
gas line pressure regulators where continuity of
service is imperative. [MFPA54: 5.8.6]
1209.7.7 Identification. Line pressure regulators
at multiple regulator installations shall be
marked by a metal tag or other permanent
means designating the building or the part of the
building being supplied. [NFPA 54: 5.8.7]
1209.8 Back-Pressure Protection.
1209.8.1 Wtiere to Install. Protective devices
shall be installed as close to the utilization
equipment as practical, where the design of
utilization equipment connected is such that
air, oxygen, or standby gases could be forced
into the gas supply system. [NFPA 54: 5.10.1.1]
Gas and air combustion mixers incorporating
double diaphragm "zero" or "atmosphere"
governors or regulators shall require no further
protection unless connected directly to
compressed air or oxygen at pressures of 5 psi
(34 kPa) or more. [NFPA 54: 5.10.1.2]
1209.8.2 Protective Devices. Protective
devices shall include but not be limited to the
following: [NFPA 54: 5.10.2]
(1) Check valves
(2) Three-way valves (of the type that
completely closes one side before starting to
open the other side)
(3) Reverse flow indicators controlling positive
shutoff valves
(4) Normally closed air-actuated positive
shutoff pressure regulators
1209.9 Low-Pressure Protection.
A protective device shall be installed between the
meter and the gas utilization equipment if the
operation of the equipment (i.e., gas compressors) is
such that it could produce a vacuum or a dangerous
reduction in gas pressure at the meter. Such devices
include, but are not limited to, mechanical,
diaphragm-operated, or electrically operated low-
pressure shutoff valves. [NFPA 54: 5.11]
1209.10 Shutoff Valves. Shutoff valves shall be
approved and shall be selected giving consideration
to pressure drop, service involved, emergency use,
and reliability of operation. Shutoff valves of size 1
inch (25 mm) National Pipe Thread and smaller shall
be listed. [NFPA 54: 5.12]
1209.11 Expansion and Flexibility.
1209.11.1 Design. Piping systems shall be
designed to have sufficient flexibility to prevent
thermal expansion or contraction from causing
excessive stresses in the piping material,
excessive bending or loads at joints, or
undesirable forces or moments at points of
connections to equipment and at anchorage or
guide points. Formal calculations or model tests
shall be required only where reasonable doubt
exists as to the adequate flexibility of the
system. [NFPA 54: 5.13.1]
Flexibility shall be provided by the use of
bends, loops, offsets, or couplings of the slip
type. Provision shall be made to absorb thermal
changes by the use of expansiori joints of the
bellows type, or by the use of "ball" or "swivel"
joints. Expansion joints of the slip type shall not
be used inside buildings or for thermal
expansion. Where expansion joints are used,
anchors or ties of sufficient strength and rigidity
shall be installed to provide for end forces due to
fluid pressure and other causes. [NFPA 54: 5.13.1.1]
Pipe alignment guides shall be used with
expansion joints according to the recommended
practice of the joint manufacturer. [NFPA 54:
5.13.1.2]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
157
1209.11 -1211.1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1209.11.2 Special Local Conditions. Where
local conditions include earthquake, tornado,
unstable ground, or flood hazards, special
consideration shall be given to increased
strength and flexibility of piping supports and
connections. [NFPA 54: 5.13.2]
1210.0 Excess Flow Valve. When automatic excess
flow gas shutoff devices (valves) are used, they shall
be listed and approved and shall be sized for the
maximum flow anticipated for the main or branch of
the fuel gas system in which the excess flow valve is
installed.
1211.0 Gas Piping Installation.
1211.1 Piping Underground.
1 21 1 .1 .1 Clearances. Undergroimd gas piping
shall be installed with sufficient clearance from
any other underground structure to avoid
contact therewith, to allow maintenance, and to
protect against damage from proximity to other
structures. In addition, underground plastic
piping shall be installed with sufficient clearance
or shall be insulated from any source of heat so
as to prevent the heat from impairing the
serviceability of the pipe. [JNJFPA 54: 7.1.1]
1211.1.2 Protection Against Damage.
(A) Cover Requirements. Underground piping
systems shall be installed with a minimum
of 18 inches (460 mm) of cover. Where external
damage to the pipe is not likely to result, the
minimum cover shall be 12 inches (300 mm).
Where a minimumi of 12 inches (300 mm) of
cover cannot be provided, the pipe shall be
installed in conduit or bridged (shielded).
[NFPA 54: 7.1.2.1]
(B) Trenches. The trench shall be graded so
that the pipe has a firm, substantially
continuous bearing on the bottom of the
trench. [NFPA 54: 7.1.2.2]
(C) Backfilling. Where flooding of the trench is
done to consolidate the backfill, care shall be
exercised to see that the pipe is not floated
from its firm bearing on the trench bottom.
[NFPA 54: 7.1.2.3]
1211.1.3 Protection Against Corrosion. Gas
piping in contact with earth or other material
that could corrode the piping shall be protected
against corrosion in an approved manner. When
dissimilar metals are joined underground, an
insulating coupling or fitting shall be used.
Piping shall not be laid in contact with cinders.
Uncoated threaded or socket- welded joints shall
not be used in piping in contact with soil or
where internal or external crevice corrosion is
known to occur. [NFPA 54: 7.1.3]
1211.1.4 Protection Against Freezing. Where
the formation of hydrates or ice is known to
occur, piping shall be protected against freezing.
[NFPA 54: 7.1.4]
1211.1.5 Piping Through Foundation Wall.
Underground piping, w^here installed through
the outer foundation or basement wall of a
building, shall be encased in a protective pipe.
The space between the gas piping and the
building shall be sealed to prevent entry of gas
or water. [NFPA 54: 7.1.5]
1211.1.6 Piping Underground Beneath
Buildings. Where the installation of gas piping
underground beneath buildings is unavoidable,
the piping shall be encased in an approved
conduit designed to withstand the superimposed
loads. [NFPA 54: 7.1.6] The conduit shall extend
into a normally usable and accessible portion of
the building and, at the point where the conduit
terminates in the building, the space between the
conduit and the gas piping shall be sealed to
prevent the possible entrance of any gas leakage.
Where the end sealing is of a type that will retain
the full pressure of the pipe, the conduit shall be
designed for the same pressure as the pipe. The
conduit shall extend at least 4 inches (100 mm)
outside the building, be vented above grade to
the outside, and be installed so as to prevent the
entrance of water and insects. [NFPA 54: 7.1.6.1]
1211.1.7 Plastic Pipe.
(A) Connection of Plastic Piping. Plastic
pipe shall be installed outside, iinderground
only. [NFPA 54: 7.1.7.1]
Exception No. 1: Plastic pipe shall be
permitted to terminate aboveground
where an anodeless riser is used.
Exception No. 2: Plastic pipe shall be
permitted to terminate with a wall head
adapter aboveground in buildings,
including basements, where the plastic
pipe is inserted in a piping material
permitted for use in buildings.
(B) Connections made outside and
underground between metallic and plastic
piping shall be made only with ASTM D
2513, Standard Specification for Thermoplastic
Gas Pressure Pipe, Tubing, and Fittings,
Category I transition fittings. [NFPA 54: 7.1.7.2]
(C) An electrically continuous corrosion-
resistant tracer wire (minimum AWG 14) or
tape shall be buried with the plastic
pipe to facilitate locating. One end shall be
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
158
FUEL PIPING
1211.1 -1211.3
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
brought aboveground at a building wall or
riser. [NFPA 54: 7.1.7.3]
1211.2 Installation of Piping.
1211.2.1 Piping installed aboveground shall be
securely supported and located where it will be
protected from physical damage (also see
1211.1.4). Where passing through an outside
wall, the piping shall also be protected against
corrosion by coating or wrapping with an inert
material approved for such applications. Where
piping is encased in a protective pipe sleeve, the
annular space between the gas piping and the
sleeve shall be sealed at the wall to prevent the
entry of water, insects, or rodents. [NFPA 54: 7.2.1]
1211.2.2 Building Structure.
(1) The installation of gas piping shall not cause
structural stresses within building components
to exceed allowable design limits. [NFPA
54: 7.2.2.1]
(2) Approval shall be obtained before any
beams or joists are cut or notched. [NFPA 54:
7.2.2.2] Permission shall be obtained from the
Authority Having Jurisdiction.
1211.2.3 Other than Dry Gas. Drips, sloping,
protection from freezing, and branch pipe
cormections, as provided for in Section 1211.1.4,
1211.6.1, and Section 1211.8, shall be provided
when other than dry gas is distributed and
climactic conditions make such provisions
necessary. [NFPA 54: 7.2.3]
1211.2.4 Gas Piping to be Sloped. Piping for
other than dry gas conditions shall be sloped not
less than 1/4 inch in 15 feet (8 mm in 4572 mm)
to prevent traps. [NFPA 54: 7.2.4]
1211.2.4.1 Ceiling Locations. Gas piping
shall be permitted to be installed in
accessible spaces between a fixed ceiling and
a dropped ceiling, whether or not such
spaces are used as a plenum. Valves shall
not be located in such spaces.
Exception: Equipment shutoff valves
required by this code shall be permitted
to be installed in accessible spaces
containing vented gas utilization
equipment.
1211.2.5 Prohibited Locations. Gas piping
inside any building shall not be installed in or
through a circulating air duct, clothes chute,
chimney or gas vent, ventilating duct,
dumbwaiter, or elevator shaft. This provision
shall not apply to ducts used to provide
combustion and ventilation air in accordance
with Section 507.0 or to above-ceiling spaces as
covered in Section 1211.2.4.1.
1211.2.6 Hangers, Supports, and Anchors.
(A) Piping shall be supported with pipe hooks.
metal pipe straps, bands, brackets, or
hangers suitable for the size of piping; be of
adequate strength and quality; and located
at intervals so as to prevent or damp out
excessive vibration. Piping shall be
anchored to prevent undue strains on
connected equipment and shall not be
supported by other piping. Pipe hangers
and supports shall conform to the
requirements of ANSI/MSS SP-58, Pipe
Hangers and Supports - Materials, Design and
Manufacture. [NFPA 54: 7.2.6.1]
(B) Spacings of supports in gas-piping
installations shall not be greater than shown
in Table 12-3. Spacing of supports for CSST
shall be in accordance with the CSST
manufacturer's instruction. [NFPA 54: 7.2.6.2]
(C) Supports, hangers, and anchors shall be
installed so as not to interfere with the free
expansion and contraction of the piping
between anchors. All parts of the supporting
equipment shall be designed and installed
so they will not be disengaged by
movement of the supported piping.
[NFPA 54: 7.2.6.3]
TABLE 12-3
Support of Piping
steel Pipe, Spacing of Nominal Size of Spacing of
Nominal Size Supports Tubing Supports
of Pipe (ft.) Smooth-wall (ft.)
(in.) (In. O.D.)
1/2
6
1/2
4
3/4 or 1
8
5/8 or 3/4
6
1-1/4 or larger
10
7/8 or 1
8
(horizontal)
(horizontal)
1-1/4 or larger
every floor
1 or larger
every floor
(vertical)
level
(vertical)
level
For SI units: 1 ft. - 0.305 m. [NFPA 54: Table 7.2.6.2]
1211.2.7 Removal of Pipe. Where piping
containing gas is to be removed, the line shall
be first disconnected from all sources of gas
and then thoroughly purged with air, water,
or inert gas before any cutting or welding is
done. (See Section 1214.6.) [NFPA 54: 7.2.7]
1211.3 Concealed Piping in Buildings.
1211.3.1 General. Gas piping in concealed
locations shall be installed in accordance with
this section. [NFPA 54: 7.3.1]
1211.3.2 Connections. Where gas piping is to
be concealed, unions, tubing fittings, right and
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
159
1211.3-1211.5
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
left couplings, bushings, swing joints, and
compression couplings made by combinations of
fittings shall not be used. Connections shall be of
the following type: [NFPA 54: 7.3.2]
(1) Pipe fittings such as elbows, tees, and
couplings.
(2) Joining tubing by brazing (see Section 1209.5.8.2).
(3) Fittings listed for use in concealed spaces
that have been demonstrated to sustain,
without leakage, any forces due to
temperature expansion or contraction,
vibration, or fatigue based on their
geographic location, application, or operation.
(4) Where necessary to insert fittings in gas pipe
that has been installed in a concealed
location, the pipe shall be reconnected by
welding, flanges, or the use of a ground joint
union with the nut center-punched to
prevent loosening by vibration.
1211.3.3 Piping in Partitions. Concealed gas
piping shall not be located in solid partitions.
[NFPA 54: 7.3.3]
1211.3.4 Tubing in Partitions. This provision
shall not apply to tubing that pierces walls,
floors, or partitions or to tubing installed
vertically and horizontally inside hollow walls or
partitions without protection along its entire
concealed length where both of the following
requirements are met: [NFPA 54: 7.3.4]
(1) A steel striker barrier not less than 0.0508
inches (1.3 mm) thick, or equivalent, is
installed between the tubing and the
finished wall and extends at least 4 inches
(100 mm)beyond concealed penetrations of
plates, fire stops, w^all studs, and so on.
(2) The tubing is installed in single runs and is
not rigidly secured.
1211.3.5 Piping in Floors. In industrial
occupancies, gas piping in solid floors such as
concrete shall be laid in channels in the floor and
covered to permit access to the piping with a
minimum of damage to the building. Where
piping in floor channels could be exposed to
excessive moisture or corrosive substances, the
piping shall be protected in an approved
manner. [NFPA 54: 7.3.5.1]
Exception: In other than industrial occupancies
and where approved by the Authority Having
Jurisdiction, gas piping embedded in concrete
floor slabs constructed with portland cement
shall be surrounded with a minimum of 1-1/2
inches (38 mm) of concrete and shall not be in
physical contact with other metallic structures
such as reinforcing rods or electrically neutral
conductors. All piping, fittings, and risers shall
be protected against corrosion in accordance
with Section 1209.5.6. Piping shall not be
embedded in concrete slabs containing quick-set
additives or cinder aggregate. [NFPA 54: 7.3.5.2]
1211.4 Piping in Vertical Chases. (See Section
1202.0.) Where gas piping exceeding 5 psi (34 kPa) is
located within vertical chases in accordance with
Section 1211.5, the requirements of Sections 1211.5.1
through 1211.5.3 shall apply. [NFPA 54: 7.4]
1211.5 Maximum Design Operating Pressure. The
maximum design operating pressure for piping
systems located inside buildings shall not exceed 5
psi (34 kPa) unless one or more of the following
conditions are met: [NFPA 54: 5.5.1]
(1) The piping system is welded.
(2) The piping is located in a ventilated chase or
otherwise enclosed for protection against
accidental gas accumulation.
(3) The piping is located inside buildings or
separate areas of buildings used exclusively
for one of the following:
(a) Industrial processing or heating
(b) Research
(c) Warehousing
(d) Boiler or mechanical equipment rooms
(4) The piping is a temporary installation for
buildings under construction.
1211.5.1 Pressure Reduction. (See Section
1202.0.) Where pressure reduction is required in
branch connections for compliance with Section
1211.5, such reduction shall take place either
inside the chase or immediately adjacent to the
outside wall of the chase. Regulator venting and
downstream overpressure protection shall comply
with Section 1209.7.4 and NFPA Section 5.9. The
regulator shall be accessible for service and repair
and vented in accordance with one of the
following: [NFPA 54: 7.4.1]
(1) Where the fuel gas is lighter than air,
regulators equipped with a vent-limiting
means shall be permitted to be vented into
the chase. Regulators not equipped with a
vent-limiting means shall be permitted to be
vented either directly to the outdoors or to a
point within the top 1 foot (0.3m) of the chase.
(2) Where the fuel gas is heavier than air, the
regulator vent shall be vented only directly
to the outdoors.
1211.5.2 Construction. Chase construction
shall comply with local building codes with
respect to fire resistance and protection of
horizontal and vertical openings. [NFPA 54:
7.4.2]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA'
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
160
FUEL PIPING
1211.5-1211.8
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
"NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
'NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1211.5.3 Ventilation. A chase shall be
ventilated to the outdoors and only at the top.
The openings shall have a minimum free area (in
square inches) equal to the product of one-half
of the maximum pressure in the piping (in psi)
times the largest nominal diameter of that piping
(in inches), or the cross-sectional area of the
chase, whichever is smaller. Where more than
one fuel gas piping system is present, the free
area for each system shall be calculated and the
largest area used. [NFPA 54: 7.4.3]
121 1 .6 Gas Pipe Turns. Changes in direction of gas
pipe shall be made by the use of fittings, or factory
bends. [NFPA 54: 7.5]
1211.6.1 l\/letallic Pipe. Metallic pipe bends
shall comply with the following: [NFPA 54:
7.5.1]
(1) Bends shall be made only with bending
equipment and procedures intended for that
purpose.
(2) All bends shall be smooth and free from
buckling, cracks, or other evidence of
mechanical damage.
(3) The longitudinal weld of the pipe shall be
near the neutral axis of the bend.
(4) The pipe shall not be bent through an arc of
more than 90 degrees.
(5) The inside radius of a bend shall be not less
than six times the outside diameter of the
pipe.
1211.6.2 Plastic Pipe. Plastic pipe bends shall
comply with the following: [NFPA 54: 7.5.2]
(1) The pipe shall not be damaged, and the
internal diameter of the pipe shall not be
effectively reduced.
(2) Joints shall not be located in pipe bends.
(3) The radius of the inner curve of such bends
shall not be less than 25 times the inside
diameter of the pipe.
(4) Where the piping manufacturer specifies the
use of special bending equipment or
procedures, such equipment or procedures
shall be used.
1211.6.3 Elbows. Factory-made welding
elbows or transverse segments cut therefrom
shall have an arc length measured along the
crotch of at least 1 inch (25 mm) for pipe sizes 2
inches and larger. [NFPA 54: 7.5.3]
1211.7 Drips and Sediment Traps.
1211.7.1 Provide Drips Where Necessary. For
other than dry gas conditions, a drip shall be
provided at any point in the line of pipe where
condensate could collect. Where required by the
Authority Having Jurisdiction or the serving gas
supplier, a drip shall also be provided at the
outlet of the meter. This drip shall be so installed
as to constitute a trap wherein an accumulation
of condensate will shut off the flow of gas before
it will run back into the meter. [NFPA 54: 7.6.1]
1211.7.2 Location of Drips. All drips shall be
installed only in such locations that they will be
readily accessible to permit cleaning or
emptying. A drip shall not be located where the
condensate is likely to freeze. [NFPA 54: 7.6.2]
1 21 1 .7.3 Sediment Traps. (See Section 1 21 2.7.)
1211.8 Outlets.
1211.8.1 Location and Installation.
(1) The outlet fittings or piping shall be securely
fastened in place. [NFPA 54: 7.7.1.1]
(2) Outlets shall not be located behind doors.
[NFPA 54: 7.7.1.2]
(3) Outlets shall be located far enough from
floors, walls, patios, slabs, and ceilings to
permit the use of wrenches without
straining, bending, or damaging the piping.
[NFPA 54: 7.7.1.3]
(4) The unthreaded portion of gas piping
outlets shall extend not less than 1 in. (25
mm) through finished ceilings or indoor or
outdoor walls. [NFPA 54: 7.7.1.4]
(5) The unthreaded portion of gas-piping
outlets shall extend not less than 2 inches (50
mm) above the surface of floors or outdoor
patios or slabs. [NFPA 54: 7.7.1.5]
(6) The provisions of Sections 1211.7.1 (4) and (5)
shall not apply to listed quick-disconnect
devices of the flush-mounted type or listed
gas convenience outlets. Such devices shall
be installed in accordance with the manu-
facturers' installation instructions. [NFPA
54: 7.7.1.6]
1211.8.2 Cap All Outlets.
(A) Each outlet, including a valve, shall be
closed gastight with a threaded plug or cap
immediately after installation and shall be
left closed until the gas utilization
equipment is connected thereto. When
equipment is disconnected from an outlet
and the outlet is not to be used again
immediately, it shall be closed gastight.
[NFPA 54: 7.7.2.1]
Exception No. 1: Laboratory equipment
installed in accordance with 1212.2(A)
shall be permitted.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
161
1211.8-1211.13
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Exception No. 2: The use of a listed
quick-disconnect device with integral
shutoff or listed gas convenience outlet
shall be permitted.
(B) Equipment shutoff valves installed in
fireplaces shall be removed and the piping
capped gastight where the fireplace is used
for solid-fuel burning. [NFPA 54: 7.7.2.2]
1211.9 Branch Pipe Connection. When a branch
outlet is placed on a main supply line before it is
known what size pipe will be connected to it, the
outlet shall be of the same size as the line that
supplies it. [NFPA 54: 7.8]
1211.10 i\/lanual Gas Shutoff Valves. (Also see
Section 1212.4.)
1211.10.1 Valves at Regulators. An accessible
gas shutoff valve shall be provided upstream of
each gas pressure regulator. Where two gas
pressure regulators are installed in series in a
single gas line, a manual valve shall not be
required at the second regulator. [NFPA 54: 7.9.1]
1211.10.2 Valves Controlling Multiple
Systems.
(A) Accessibility of Gas Valves. Main gas
shutoff valves controlling several gas piping
systems shall be readily accessible for
operation and installed so as to be protected
from physical damage. They shall be
marked with a metal tag or other permanent
means attached by the installing agency so
that the gas piping systems supplied
through them can be readily identified.
[NFPA 54: 7.9.2.1]
(B) Shutoff Valves for Multiple House Lines.
In multiple-tenant buildings supplied
through a master meter, or through one
service regulator where a meter is not
provided, or where meters or service
regulators are not readily accessible from
the equipment location, an individual
shutoff valve for each apartment or tenant
line shall be provided at a convenient point
of general accessibility.
In a common system serving a number
of individual buildings, shutoff valves shall
be installed at each building. [NFPA 54:
7.9.2.2]
1211.10.3 Emergency Shutoff Valves. An
exterior shutoff valve to permit turning off the
gas supply to each building in an emergency
shall be provided. The emergency shutoff valves
shall be plainly marked as such and their
locations posted as required by the Authority
Having Jurisdiction. [NFPA 54: 7.9.2.3]
1211.11 Prohibited Devices. No device shall be
placed inside the gas piping or fittings that will
reduce the cross-sectional area or otherwise obstruct-
the free flow of gas, except where proper allowance
in the piping system design has been made for such
a device and where approved by the Authority
Having Jurisdiction. [NFPA 54: 7.10]
1211.12 Systems Containing Gas-Air Mixtures
Outside the Flammable Range. Where gas-air
mixing machines are employed to produce mixtures
above or below the flammable range, they shall be
provided with stops to prevent adjustment of the
mixture to within or approaching the flammable range.
[NFPA 54: 7.11]
1211.13 Systems Containing Flammable Gas-Air
Mixtures.
1211.13.1 Required Components. A central
premix system with a flammable mixture in the
blower or compressor shall consist of the
following components: [NFPA 54: 7.12.1]
(1) Gas-mixing machine in the form of an
automatic gas-air proportioning device
combined with a downstream blower or
compressor.
(2) Flammable mixture piping, minimum
Schedule 40 NFS.
(3) Automatic firechecks.
(4) Safety blowouts or backfire preventers for
systems utilizing flammable mixture lines
above 2-1/2 inch (65 mtn) nominal pipe size
or the equivalent.
1211.13.2 Optional Components.
The following components shall also be
permitted to be utilized in any type of central
premix system: [NFPA 54: 7.12.2]
(1) Flowmeters.
(2) Flame arresters.
1211.13.3 Additional Requirements. Gas-
mixing machines shall have nonsparking
blowers and shall be so constructed that a
flashback will not rupture machine casings.
[NFPA 54: 7.12.3]
1211.13.4 Special Requirements for Mixing
Blowers. A mixing blower system shall be
limited to applications with minimum practical
lengths of mixture piping. Limited to a maximum
mixture pressure of 10 inch water column (25 Pa)
and limited to gases containing no more than 10
percent hydrogen.
The blower shall be equipped with a gas-
control valve at its air entrance so arranged that
gas is admitted to the airstream; entering the
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
, NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
162
FUEL PIPING
1211.13-1211.14
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
blower in proper proportions for correct
combustion by the type of burners employed,
the said gas-control valve being of either the
zero governor or mechanical ratio valve type
that controls the gas and air adjustment
simultaneously. No valves or other obstructions
shall be installed between the blower discharge
and the burner or burners. [NFPA 54: 7.12.4]
1211.13.5 Installation of Gas-Mixing
Machines.
(A) The machine shall be located in a large,
well-ventilated area or in a small detached
building or cutoff room provided with room
construction and explosion vents in
accordance with sound engineering
principles. Such rooms or below-grade
installations shall have adequate positive
ventilation. [NFPA 54: 7.12.5.1]
(B) Where gas-mixing machines are installed in
well-ventilated areas, the type of electrical
equipment shall be in accordance with
NFPA 70, National Electrical Code®, for
general service conditions, unless other
hazards in the area prevail. Where gas-
mixing machines are installed in small
detached buildings or cutoff rooms, the
electrical equipment and wiring shall be
installed in accordance with NFPA 70,
National Electrical Code, for hazardous
locations (Articles 500 and 501, Class I,
Division 2). [NFPA 54: 7.12.5.2]
(C) Air intakes for gas-mixing machines using
compressors or blowers shall be taken from
outdoors whenever practical. [NFPA 54:
7.12.5.3]
(D) Controls for gas-mixing machines shall
include interlocks and a safety shutoff valve
of the manual reset type in the gas supply
connection to each machine arranged to
automatically shut off the gas supply in the
event of high or low gas pressure. Except for
open burner installations only, the controls
shall be interlocked so that the blower or
compressor will stop operating following a
gas supply failure. Where a system employs
pressurized air, means shall be provided to
shut off the gas supply in the event of air
failure. [NFPA 54: 7.12.5.4]
(E) Centrifugal gas-mixing machines in parallel
shall be reviewed by the user and
equipment manufacturer before installation,
and means or plans for minimizing these
effects of downstream pulsation and
equipment overload shall be prepared and
utilized as needed. [NFPA 54: 7.12.5.5]
1211.13.6 Use of Automatic Firechecks,
Safety Blowouts, or Backfire Preventers.
Automatic firechecks and safety blowouts or
backfire preventers shall be provided in piping
systems distributing flammable air-gas mixtures
from gas-mixing machines to p>rotect the piping
and the machines in the event of flashback, in
accordance with the following: [NFPA 54: 7.12.6]
(A) Approved automatic firechecks shall be
installed upstream as close as practicable to
the burner inlets following the firecheck
manufacturers' instructions.
(B) A separate manually operated gas valve
shall be provided at each automatic
firecheck for shutting off the flow of gas-air
mixture through the firecheck after a
flashback has occurred. The valve shall be
located upstream as close as practical to the
inlet of the automatic firecheck.
CAUTION:
These valves shall not be reopened after a flashback
has occurred until the firecheck has cooled
sufficiently to prevent reignition of the flammable
mixture and has been reset properly.
(C) A safety blowout or backfiring preventer
shall be provided in the mixture line near the
outlet of each gas-mixing machine where the
size of the piping is larger than 2-1/2 inch
(65 mm) NPS, or equivalent, to protect the
mixing equipment in the event of an
explosion passing through an automatic
firecheck. The manufacturers' instructions
shall be followed when installing these
devices, particularly after a disc has burst.
The discharge from the safety blowout
or backfire preventer shall be located or
shielded so that particles from the ruptured
disc cannot be directed toward personnel.
Wherever there are interconnected
installations of gas-mixing machines with
safety blowouts or backfire preventers,
provision shall be made to keep the mixture
from other machines from reaching any
ruptured disc opening. Check valves shall
not be used for this purpose.
(D) Large-capacity premix systems provided
with explosion heads (rupture disc) to
relieve excessive pressure in pipelines shall
be located at and vented to a safe outdoor
location. Provisions shall be provided for
automatically shutting off the supply of gas-
air mixture in the event of rupture.
1211.14 Electrical Bonding and Grounding.
(A) Each aboveground portion of a gas piping
system that is likely to become energized
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
163
1211.14-1212.3
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
shall be electrically continuous and bonded
to an effective ground-fault current path.
Gas piping shall be considered to be bonded
when it is connected to gas utilization
equipment that is connected to the equip-
ment grounding conductor of the circuit
supplying that equipment. [NFPA 54: 7.13.1]
(B) Gas piping shall not be used as a grounding
conductor or electrode. [NFPA 54: 7.13.2]
1211.15 Electrical Circuits. Electrical circuits shall
not utilize gas piping or components as conductors.
[NFPA 54: 7.14]
Exception: Low-voltage (50 V or less) control
circuits, ignition circuits, and electronic flame
detection device circuits shall be permitted to
make use of piping or components as a part of
an electric circuit.
1211.16 Electrical Connections.
(A) All electrical connections between wiring
and electrically operated control devices in
a piping system shall conform to the
requirements of NFPA 70, National
Electrical Code. (See Section 1211.13.)
[NFPA 54: 7.15.1]
(B) Any essential safety control depending on
electric current as the operating medium
shall be of a type that will shut off (fail safe)
the flow of gas in the event of current
failure. [NFPA 54: 7.15.2]
1212.0 Equipment Connections to Building
Piping.
1212.1 Connecting Gas Equipment. Gas utilization
equipment shall be connected to the building piping
in compliance with Sections 1212.4 and 1212.5 by
one of the following: [NFPA 54: 9.6.1]
(1) Rigid metallic pipe and fittings.
(2) Semirigid metallic tubing and metallic
fittings. Aluminum alloy tubing shall not be
used in exterior locations.
(3) Listed flexible gas connectors in compliance
with ANSI Z21.24, Standard for Connectors for
Gas Appliances. The connector shall be used
in accordance with the terms of their listing
that are completely in the same room as the
equipment.
(4) CSST where installed in accordance with the
manufacturer's instructions.
(5) Listed nonmetallic gas hose connectors in
accordance with 1212.2.
(6) Gas-fired food service (commercial cooking)
equipment listed for use with casters or
otherwise subject to movement for cleaning,
and other large and heavy gas utilization
equipment that can be moved, shall be
connected in accordance with the connector
manufacturer's installation instructions
using a listed appliance connector
complying with ANSI Z21.69, Standard for
Connectors for Movable Gas Appliances.
[NFPA 54: 9.6.1.1]
(7) In 1212.1(2), (3), and (5), the connector or
tubing shall be installed so as to be
protected against physical and thermal
damage. Aluminum alloy tubing and
connectors shall be coated to protect against
external corrosion where they are in contact
with masonry, plaster, or insulation or are
subject to repeated wettings by such liquids
as water (except rain water), detergents, or
sewage.
1212.2 Use of Nonmetallic Gas Hose Connectors.
Listed nonmetallic gas hose connectors shall be used
in accordance with the terms of their listing and as
follows: [NFPA 54: 9.6.2]
(A) indoor. Indoor gas hose connectors shall be
used only to connect laboratory, shop, and
ironing equipment requiring mobility
during operation. An equipment shutoff
valve shall be installed where the comiector
is attached to the building piping. The
connector shall be of minimum length and
shall not exceed 6 feet (1829 mm). The cormector
shall not be concealed and shall not extend
from one room to another or pass through
wall partitions, ceilings, or floors.
(B) Outdoor. Outdoor gas hose connectors are
permitted to connect portable outdoor gas-
fired equipment. An equipment shutoff
valve, a listed quick-disconnect device, or
a listed gas convenience outlet shall be
installed where the cormector is attached to
the supply piping and in such a manner to
prevent the accumulation of water or
foreign matter. This connection shall be
made only in the outdoor area where the
equipment is to be used. The connector
length shall not exceed 15 feet (4572 mm).
1212.3 Connection of Portable and Mobile
Industrial Gas Equipment.
(A) Where portable industrial gas utilization
equipment, or equipment requiring mobility
or subject to vibration, is connected to the
building gas piping system by the use of a
flexible hose, the hose shall be suitable and
safe for the conditions under which it can be
used. [NFPA 54: 9.6.3.1]
(B) Where industrial gas utilization equipment
requiring mobility is connected to the rigid
piping by the use of swivel joints or
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
I NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
164
FUEL PIPING
1212.3-1214.1
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
couplings, the swivel joints or couplings
shall be suitable for the service required,
and only the minimum number required
shall be installed. [NFPA 54: 9.6.3.2]
(C) Where industrial gas utilization equipment
subject to vibration is connected to the
building piping system by the use of all-
metal flexible connectors, the connectors
shall be suitable for the service required.
[NFPA 54: 9.6.3.3]
(D) Where flexible connections are used, they
shall be of the minimum practical length
and shall not extend from one room to
another or pass through any walls,
partitions, ceilings, or floors. Flexible
connections shall not be used in any
concealed location. They shall be protected
against physical or thermal damage and
shall be provided with gas shutoff valves in
readily accessible locations in rigid piping
upstream from the flexible connections.
[NFPA 54: 9.6.3.4]
1212.4 Equipment Shutoff Valves and Connections.
Gas utilization equipment connected to a piping
system shall have an accessible, approved manual
shutoff valve with a nondisplaceable valve member,
or a listed gas convenience outlet [NFPA 54: 9.6.4],
installed within 6 feet (1.8 m) of the equipment it
serves. Where a connector is used, the valve shall be
installed upstream of the connector. A union or
flanged connection shall be provided downstream
from this valve to permit removal of controls.
Shutoff valves serving decorative gas appliances
shall be permitted to be installed in fireplaces if
listed for such use. [NFPA 54: 9.6.4.1]
Gas supply inlet
A
To
equipment -
inlet
"O.
Niji^le-
Cap-
D-
T
3 in. (80 mm)
minimum
i.
Figure 12-1 J\Aethod of Installing a Tee Fitting
Sediment Trap.
1212.5 Quick-Disconnect Devices. Quick-disconnect
devices used to connect equipment to the building
piping shall be listed. [NFPA 54: 9.6.5.1] Where they
are installed indoors, an approved manual shutoff
valve with a nondisplaceable valve member shall be
installed upstream of the quick-disconnect device.
[NFPA 54: 9.6.5.2]
1212.6 Support of Chimneys. Ail portions of
chimneys shall be supported for the design and weight
of the materials employed. Listed factory-built
chimneys shall be supported and spaced in accordance
with their listings and the manufacturers' instructions.
1212.7 Sediment Trap, Where a sediment trap is
not incorporated as a part of the gas utilization
equipment, a sediment trap shall be installed as close
to the inlet of the equipment as practical at the time
of equipment installation. The sediment trap shall be
either a tee fitting with a capped nipple in the bottom
outlet, as illustrated in Figure 12-1, or oth^r device
recognized as an effective sediment trap. Illuminating
appliances, ranges, clothes dryers, decorative vented
appliances for installation in vented fireplaces, gas
fireplaces, and outdoor grills shall not be required to
be so equipped. [NFPA 54: 9.6.7]
1212.8 Installation of Piping. Piping shall be
installed in a maimer not to interfere with inspection,
maintenance, or servicing of the gas utilization
equipment. [NFPA 54: 9.6.8]
1213.0 Liquefied Petroleum Gas Facilities and
Piping.
Liquefied petroleum gas facilities shall comply with
NFPA 58, Liquefied Petroleum Gas Code.
1214.0 Pressure Testing and Inspection.
1214.1 General.
1214.1 .1 Prior to acceptance and initial operation,
all piping installations shall be inspected and
pressure-tested to determine that the materials,
design, fabrication, and installation practices
comply with the requirements of this code.
[NFPA 54: 8.1.1.1]
1214.1.2 Inspection shall consist of visual
examination during or after manufacture,
fabrication, assembly, or pressure tests, as
appropriate. Supplementary types of non-
destructive inspection techniques, such as
magnetic-particle, radiographic, and ultrasonic,
shall not be required unless specifically listed
herein or in the engineering design. [NFPA 54:
8.1.1.2]
1214.1.3 Where repairs or additions are made
following the pressure test, the affected piping
shall be tested. Minor repairs and additions are
not required to be pressure-tested provided that
the work is inspected and connections are tested
with a noncorrosive leak-detecting fluid or other
leak-detecting methods approved by the
Authority Having Jurisdiction. [NFPA 54: 8.1.1.3]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
165
1214.1 -1214.4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1214.1.4 Where new branches are installed from
the point of delivery to new appliances, orJy the
newly installed branches shall be required to be
pressure-tested. Connections between the new
piping and the existing piping shall be tested
with a noncorrosive leak-detecting fluid or
approved leak-detecting methods. [NFPA 54:
8.1.1.4]
1214.1.5 A piping system shall be tested as a
complete unit or in sections. Under no circum-
stances shall a valve in a line be used as a
bulkhead between gas in one section of the
piping system and test medium in an adjacent
section, unless two valves are installed in series
with a valved "telltale" located between these
valves. A valve shall not be subjected to the test
pressure unless it can be determined that the
valve, including the valve-closing mechanism, is
designed to safely withstand the pressure.
[NFPA 54: 8.1.1.5]
1 21 4.1 .6 Regulator and valve assemblies fabricated
independently of the piping system in which they
are to be installed shall be permitted to be tested
with inert gas or air at the time of fabrication.
[NFPA 54: 8.1.1.6]
1214.1.7 Test Medium. The test medium shall
be air, nitrogen, carbon dioxide, or an inert gas.
OXYGEN SHALL NEVER BE USED. [NFPA 54:
8.1.2]
1214.2 Test Preparation.
1214.2.1 Pipe joints, including welds, shall be
left exposed for examination during the test.
[NFPA 54: 8.1.3.1]
Exception: Covered or concealed pipe end
joints that have been previously tested in
accordance with this code.
1 21 4.2.2 Expansion joints shall be provided with
temporary restraints, if required for the
additional thrust load under test. [NFPA 54:
8.1.3.2]
1214.2.3 Appliances and equipment that are not
to be included in the test shall be either
disconnected from the piping or isolated by
blanks, blind flanges, or caps. Flanged joints at
which blinds are inserted to blank off other
equipment during the test shall not be required
to be tested. [NFPA 54: 8.1.3.3]
1214.2.4 Where the piping system is connected
to appliances, equipment, or equipment com-
ponents designed for operating pressures of less
than the test pressure, such appliances, equip-
ment, or equipment components shall be isolated
from the piping system by disconnecting them
and capping the outlets. [NFPA 54: 8.1.3.4]
1214.2.5 Where the piping system is cormected
to appliances, equipment, or equipment com-
ponents designed for operating pressures equal to
or greater than the test pressure, such appliances
and equipment shall be isolated from the piping
system by closing the individual appliance
equipment shutoff valves. [NFPA 54: 8.1.3.5]
1214.2.6 All testing of piping systems shall be
done with due regard for the safety of employees
and the public during the test. Bulkheads,
anchorage, and bracing suitably designed to resist
test pressures shall be installed if necessary. Prior
to testing, the interior of the pipe shall be cleared
of all foreign material. [NFPA 54: 8.1.3.6]
1214.3 Test Pressure.
1214.3.1 Test pressure shall be measured with a
manometer or with a pressure-measuring device
designed and calibrated to read, record, or
indicate a pressure loss due to leakage during
the pressure test period. The source of pressure
shall be isolated before the pressure tests are
made. Mechanical gauges used to measure test
pressures shall have a range such that the
highest end of the scale is not greater than five
times the test pressure. [NFPA 54: 8.1.4.1]
1214.3.2 The test pressure to be used shall be no
less than 1-1/2 times the proposed maximum
working pressure, but not less than 3 psi (20
kPa), irrespective of design pressure. [NFPA 54:
8.1.4.2]
1214.3.3 Test duration shall be not less than 1/2
hour for each 500 cubic feet (14 m^) of pipe
volume or fraction thereof. When testing a
system having a volume less than 10 cubic feet
(0.28 m^) or a system in a single-family dwelling,
the test duration shall be a minimuni of 10
minutes. The duration of the test shall not be
required to exceed 24 hours. [NFPA 54: 8.1.4.3]
1214.4 Detection of Leaks and Defects.
1214.4.1 The piping system shall withstand the
test pressure specified without showing any
evidence of leakage or other defects. Any
reduction of test pressures as indicated by
pressure gauges shall be deemed to indicate the
presence of a leak unless such reduction can be
readily attributed to some other cause. [NFPA
54: 8.1.5.1]
1214.4.2 The leakage shall be located by means
of an approved gas detector, a noncorrosive leak
detection fluid, or other approved leak detection
methods. Matches, candles, open flames, or
other methods that provide a source of ignition
shall not be used. [NFPA 54: 8.1.5.2]
1214.4.3 Where leakage or other defects are
located, the affected portion of the piping system
shall be repaired or replaced and retested. [See
Section 1214.1.3.] [NFPA 54: 8.1.5.3]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
166
FUEL PIPING
1214.5-1215.1
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1214.5 System and Equipment Leakage Test.
1214.5.1 Test Gases. Leak checks using fuel
gas shall be permitted in piping systems that
have been pressure-tested in accordance with
Section 1214.0. [NFPA 54: 8.2.1]
1214.5.2 Before Turning Gas On. Before gas is
introduced into a system of new gas piping, the
entire system shall be inspected to determine that
there are no open fittings or ends and all valves at
unused outlets are closed and plugged or capped.
[NFPA 54: 8.2.2]
1214.5.3 Test for Leakage. Immediately after
the gas is turned on into a new system or into a
system that has been initially restored after an
interruption of service, the piping system shall
be checked for leakage. Where leakage is
indicated, the gas supply shall be shut off until
the necessary repairs have been made. [NFPA
54: 8.2.3]
1214.5.4 Placing Equipment in Operation.
Gas utilization equipment shall not be placed in
operation until after the piping system has been
tested in accordance with Section 1214.5.3 and
purged in accordance with Section 1214.6.2.
[NFPA 54: 8.2.4]
1214.6 Purging.
1214.6.1 Removal From Service. When gas
piping is to be opened for servicing, addition, or
modification, the section to be worked on shall
be turned off from the gas supply at the nearest
convenient point and the line pressure vented to
the outdoors or to ventilated areas of sufficient
size to prevent accumulation of flammable
mixtures. The remaining gas in this section of
pipe shall be displaced with an inert gas as
required by Table 12-5. [NFPA 54: 8.3.1]
TABLE 12-5
Length of Piping Requiring Purging with Inert
Gas for Servicing or Modification
[NFPA 54: Table 8.3.1]
Nominal Pipe
Length of Piping
Size (in.)
Requiring Purging (ft.)
2
>50
3
>30
4
' >15
6
>10
8 or larger
Any length
piping shall be displaced with fuel gas, except
where such piping is required by Table 12-6 to
be purged with an inert gas prior to introduction
of fuel gas. The air can be safely displaced with
fuel gas provided that a moderately rapid and
continuous flow of fuel gas is introduced at one
end of the line and air is vented out at the other
end. The fuel gas flow shall be continued without
interruption until the vented gas is free of air. The
point of discharge shall not be left unattended
during purging. After purging, the vent shall then
be closed. Where required by Table 12-6, the air in
the piping shall first be displaced with an inert
gas, and the inert gas shall then be displaced with
fuel gas. [NFPA 54: 8.3.2]
TABLE 12-6
Length of Piping Requiring Purging with Inert
Gas Before Placing in Operation
[NFPA 54: Table 8.3.2]
Nominal Pipe
Size (in.)
Length of Piping Requiring
Purging (ft.)
3
>30
4
>15
6
>10
8 or larger
Any length
For SI units: 1 ft.
= 0.305
m.
For SI units: 1 f t = 0.305 m.
1214.6.2 Placing in Operation. When piping
full of air is placed in operation, the air in the
1214.6.3 Discharge of Purged Gases. The
open end of piping systems being purged shall
not discharge into confined spaces or areas
where there are sources of ignition unless
precautions are taken to perform this operation
in a safe manner by ventilation of the space,
control of purging rate, and elimination of all
hazardous conditions. [NFPA 54: 8.3.3]
1214.6.4 Placing Equipment in Opereition.
After the piping has been placed in operation, all
equipment shall be purged and then placed in
operation, as necessary. [NFPA 54: 8.3.4]
1215.0 Interconnections Between Gas Piping
Systems [NFPA 54: 5.3]
1215.1 Interconnections Supplying Separate Users.
Where two or more meters, or two or more service
regulators where meters are not provided, are
located on the same premises and supply separate
users, the gas-piping systems shall not be
interconnected on the outlet side of the meters or
service regulators. [NFPA 54: 5.3.1]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
167
1215.2-1217.3
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
1215.2 Interconnections for Standby Fuels.
Where supplementary gas for standby use is
connected downstream from a meter or a service
regulator where a meter is not provided, a device to
prevent backflow shall be installed. [NFPA 54:
5.3.2.1] A three-way valve installed to admit the
standby supply and at the same time shut off the
regular supply shall be permitted to be used for this
purpose. [NFPA 54:5.3.2.2]
1216.0 Required Gas Supply.
1216.1 The following regulations, as set forth in this
section and in Section 1217.0, Required Gas Piping
Size, shall be the standard for the installation of gas
piping. All natural gas regulations and tables are
based on the use of gas having a specific gravity of
sixty hundredths (0.60), supplied at six (6) to eight (8)
inches (152-203 mm) water column pressure at the
outlet of the meter or regulator. Where the natural gas
supplier cannot maintain a minimum inlet pressure of
six (6) inches (152 mm) water column pressure. Table
12-7 allowing a maximum pressure drop of 0.3-inch
(7.6 mm) water column shall be used. For undiluted
liquefied petroleum gas, gas piping may be sized at
eleven (11) inches (279 mm) water column pressure at
the outlet of the meter or regulator and specific
gravity of one and fifty htmdredths (1.50).
Note: Where gas of a different specific gravity is to
be delivered, the serving gas supplier should be
contacted for specific gravity conversion factors to
use in sizing piping systems from the pipe sizing
tables in this chapter.
1216.2 The hourly volume of gas required at each
piping outlet shall be taken as not less than the
maximum hourly rating as specified by the
manufacturer of the appliance or appliances to be
connected to each such outlet.
1216.3 Where the gas appliances to be installed have
not been definitely specified. Table 12-1 may be used
as a reference to estimate requirements of typical
appliances.
To obtain the cubic feet per hour (L/sec.) of gas
required, divide input of appliances by the average
Btu (Watt-hour) heating value per cubic foot (L) of
the gas. The average Btu (Watt-hour) per cubic foot
(L) of the gas in the area of the installation may be
obtained from the serving gas supplier.
1 21 6.4 The size of the supply piping outlet for any
gas appliance shall not be less than one-half (1/2)
inch (15 mm).
The minimum size of any piping outlet for a
mobile home shall be three-quarter (3/4) inch (20 mm).
1217.0 Required Gas Piping Size.
1217.1 Pipe Sizing Methods. Where the pipe size
is to be determined using any of the methods in
Sections 1217.1.1 through 1217.1.3, the diameter of
each pipe segment shall be obtained from the pipe-
sizing tables in Section 1217.2 or from the sizing
equations in Section 1217.3. [NFPA 54: 6.1]
1217.1.1 Longest Length Method. The pipe
size of each section of gas piping shall be
determined using the longest length of piping
from the point of delivery to the most remote
outlet and the load of the section (see calculation
example in Figure 12-2). [NFPA 54: 6.1.1]
1217.1.2 Branch Length Method. Pipe shall be
sized as foUows: [NFPA 54: 6.1.2]
(A) Pipe size of each section of the longest
pipe run from the point of delivery to the
most remote outlet shall be determined
using the longest run of piping and the
load of the section.
(B) The pipe size of each section of branch
piping not previously sized shall be
determined using the length of piping,
from the point of delivery to the most
remote outlet in each branch and the
load of the section.
1217.1.3 Hybrid Pressure. The pipe size for
each section of higher-pressure gas piping shall
be determined using the longest length of piping
from the point of delivery to the most remote
line pressure regulator. The pipe size from the
line pressure regulator to each outlet shall be
determined using the length of piping from the
regulator to the most remote outlet served by the
regulator. [NFPA 54: 6.1.3]
1217.2 Tables for Sizing Gas-Piping Systems.
Tables 12-7 through 12-41 shall be used to size gas
piping in conjunction with one of the methods
described in Sections 1217.1.1 through 1217.1.3.
[NFPA 54: 6.3]
1217.3 Sizing Equations. The inside diameter of
smooth-wall pipe or tubing shall be determined by
the sizing equations 12-1 or 12-2/ using the
equivalent pipe length determined by Sections
1217.1.1 through 12117.1.3. [NFPA 54: 6.4]
TIA
TIAJ
NFPA TIa'
NFPA
NFPA "A
NFPA TIA
NFPA ji .
NFPA ""
NFPA TIA
NFPA TIA
NFPA
NFPA "A
NFPA TIA
NFPA j,^
NFPA ""
NFPA TIA
NFPA TIA
NFPA
NFPA TIA
NFPA TIA
NFPA J.,
NFPA ""
NFPA TIA
NFPA TIA
NFPA ,
NFPA
TIA
NFPA TIA
NFPA T, .
NFPA ""
NFPA TIA
NFPA TIA
NFPA
NFPA TIA
NFPA TIA
NFPA y, .
NFPA ""
NFPA TIA
NFPA TIA
NFPA
NFPA TIA
NFPA TIA
NFPA T, .
NFPA "**
NFPA TIA
NFPA TIA
NFPA
NFPA TIA
NFPA TIA
NFPA j.f.
NFPA ""
NFPA TIA
NFPA TlAi
NFPA I
NFPA TIA^
NFPA TIA
NFPA y. .
NFPA '"*
NFPA TIA
NFPA TIA
NFPA
NFPA "A
NFPA TIA
NFPA J..
NFPA ""
NFPA TIA
NFPA TIA
NFPA
NFPA "A
NFPA TIA
NFPA Ti .
NFPA ""
NFPA TIA
NFPA TIA
NFPA
NFPA "A
NFPA TIA
NFPA J..
NFPA '"
NFPA TIA
NFPA TIA
NFPA
NFPA "A
NFPA TIA
NFPA T, .
NFPA ""
NFPA TIA
NFPA TIA
NFPA ; X
NFPA "A
NFPA TIA
168
FUEL PIPING
1217.3-1217.6
TIA
kTIA
riA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
kTIA
riA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
J^IA
[lA
riA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Equation 12-1 Low-Pressure Gas Formula (Less
than 1.5 psi [10.3 kPa]): [NFPA 54: 6.4.1
D=
QO
381
19.17
\Cr X L/
0.206
where:
D = inside diameter of pipe, inches
Q = input rate appliance(s), cubic feet per hour at
60°F (16°C) and 30-inch (759 mm) mercury
coiumn
?! = upstream pressure, psia (P^ + 14.7)
P2 = downstream pressure, psia (P2 + 14.7)
L = equivaient length of pipe, feet
SH = pressure drop, inches water column (27.7 in.
H20= Ipsi)
Equation 12-2 High-Pressure Gas Formula (1.5 psi
[10.3 kPa] and above): [NFPA 54: 6.4.2]
D-
Q
i0.381
18.93 Ml
EPiizMiil
1^ CrxL J
0.206
where:
D = inside diameter of pipe, inches
Q = input rate appliance(s), cubic feet per hour at
60°F (16°C) and 30 inch (759 mm) mercury
column
Pj = upstream pressure, psia (Pj + 14.7)
P2 - downstream pressure, psia (P2 + 14.7)
L = equivalent length of pipe, feet.
52H = pressure drop, inches water cohimn (27.7 in.
H2O = 1 psi)
TABLE 12-4
Cr and Y for Natural Gas and Undiluted Propane
at Standard Conditions [NFPA 54: Table 6.4.2]
Formula Factors Gas
Cr
Nahiral Gas 0.6094 0.9992
Undiluted Propane 1.2462 0.9910
For SI units, 1 ft.^* = 0.028 m^; 1 ft. = 0.305 m; 1 in.
water column = 0.249 l<Pa; 1 psi = 6.894 kPa; 1,000
Btu/h = 0.293 kW.
1217.4 To determine the size of each section of pipe
in any system within the range of the Table, proceed
as follow^s:
(A) Measure the length of the pipe from the gas
meter location to the most remote outlet on
the system.
(B) Select the length in feet column and row
showing that distance, or the next longer
distance if the table does not give the exact
length.
(C) Starting at the most remote outlet, find in the
row just selected the gas demand for that
outlet. If the exact figure of demand is not
shown, choose the next larger figure in the
row.
(D) At the top of this column will be foim^d the
correct size of pipe.
(E) Using this same row, proceed in a similar
manner for each section of pipe serving this
outlet. For each section of pipe, determine
the total gas demand supplied by that
section. Where gas piping sections serve
both heating and cooling equipment and the
installation prevents both units from
operating simultaneously, only the larg-
er of the two demand loads needs be used in
sizing these sections.
(F) Size each section of branch piping not
previously sized by measuring the distance
from the gas meter location to the most
remote outlet in that branch and follow the
procedures of steps B, C, D, and E above.
Note:
Size branch piping in the order of their distance from
the meter location, beginning with the most distant
outlet not previously sized.
1217.5 For conditions other than those covered by
Section 1217.1, such as longer runs or greater gas
demands, the size of each gas piping system shall be
determined by standard engineering methods
acceptable to the Authority Having Jurisdiction, and
each such system shall be so designed that the total
pressure drop between the meter or other point of
supply and any outlet when full demand is being
supplied to all outlets, will at no time exceed five-
tenths (0.5) inches (12.7 mm) water column pressure.
1217.6 Where the gas pressure may be higher than
fourteen (14) inches (356 mm) or lower than six (6)
inches (152 mm) of water column, or when diversity
demand factors are used, the design, pipe, sizing,
materials, location, and use of such systems first shall
be approved by the Authority Having Jurisdiction.
Piping systems designed for pressures higher than
the serving gas supplier's standard delivery pressure
shall have prior verification from the gas supplier of
the availability of the design pressure.
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
169
Figure 1 2-2 Example
UNIFORM PLUMBING CODE
Figure 12-2 Example Illustrating Use of Tables 12-1 and 12-8
Problem: Determine the required pipe size of each section and outlet of the piping system shown in Figure 12-
2. Gas to be used has a specific gravity of sixty hundredths (0.60) and eleven hundred (1,100) Btu per cubic foot
(11.4 Watt-hour/L), delivered at eight (8) inch (203 nm\) water column pressure.
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
150,000 btu/h
* (43.950 W)
1 f-umace
1
O
1
c
/— ^
H
o>
r-
^^ o«
m
3° 5l
D
LET
Section 3
i Section 2 Section 1 >
20'
1 10' 10'
(6096 mm)
^ (3048 mm).J3048 mmX ,_
J-
O
oS
c
H
4^
f-
°°o
O
— m
3 -
3 ■
c
H
f-
m
4!^ H_
<3 03*
A
H
3 -
W
O
3
Gasr
i/leter
1
r
30 gallon (113.6 1)
Automatic
Water Heats'
3
3
Gas
Refrigerator
Range
Solution:
(1) Maximum gas demand of outlet A —
32 cubic feet per hour (0.21 L/sec.) (from Table 12-1).
Maximum gas demand of outlet B —
3 cubic feet per hour (0.02 L/sec.) (from Table 12-1).
Maximum gas demand of outlet C —
59 cubic feet per hour (0.46 L/sec.) (from Table 12-1).
Maximum gas demand of outlet D —
136 cubic feet per hour (1.1 L/sec.) (150,000 Bhi/hour [43,950 W])
divided by 1,100 Btu per cubic foot (11.4 Watt-hour/L)
(2) The length of pipe from the gas meter to the most remote outlet (outlet A) is 60 feet (18,288 mm).
(3) Using the length in feet column row marked 60 feet (18,288 mm) in Table 12-8:
Outlet A, supplying 32 cubic feet per hour (0.21 L/sec), requires one-half (1/2) inch (15 mm) pipe. Section
1, supplying outlets A and B, or 35 cubic feet per hour (0.24 L/sec.) requires one-half (1/2) inch (15 mm)
pipe.
Section 2, supplying outlets A, B, and C, or 94 cubic feet per hour (0.7 L/sec.) requires three-quarter (3/4)
inch (20 mm) pipe.
Section 3, supplying outlets A, B, C, and D, or 230 cubic feet per hour (1.8 L/sec), requires one inch (25
mm) pipe.
(4) Using the column marked 60 feet (18288 mm) in Table 12-8 (no column for actual length of 55 feet [16,764
mm]: Outlet B supplying 3 cubic feet per hour (0.02 L/sec), requires one-half (1/2) inch (15 mm) pipe.
Outlet C, supplying 59 cubic feet per hour (0.46 L/sec), requires one-half (1/2) inch (15 mm) pipe.
(5) Using the column marked 50 feet (15,240 mm) in Table 12-8:
Outlet D, supplying 136 cubic feet per hour (1.1 L/sec), requires (3/4) inch (20 mm) pipe.
170
FUEL PIPING
Table 12-7
Table 1 2-7 Schedule 40 Metallic Pipe [NFPA Table 6.2(a)]
Gas:
Natural
Inlet Pressure:
Less than 2
psi
Pressure l^op:
0.3 in. w.c.
Specific Gravity:
0.60
Pipe Size (in.)
Nominal:
V4
%
1
VA
m
2
2V4
3
4
5
6
8
10
12
Actual ID:
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
5.047
6.065
7.981
10.020
11.938
Leog^ (ft)
Capacity in Cubic Feet of Gas per Hour
10
131
273
514
1,060
1,580
3,050
4,860
8,580
17,!>00
31,700
51..300
105,000
191,000
303,000
20
90
188
363
726
1,090
2.090
3,340
5,900
12,000
21,800
35,300
72,400
132,000
208,000
30
72
151
284
583
873
1,680
2,680
4,740
9,660
17,500
28,300
.58,2(H)
106,000
167,0(X)
40
62
129
243
499
747
1,410
2.290
4,0.50
8,270
15,0(H)
24.200
49,800
90,4(M)
143,000
50
55
114
215
442
662
1,280
2.030
3,.590
7,3.30
13,300
21,500
44,100
80,100
127,000
60
50
104
195
4<»
(JOO
1.160
1,840
3,260
6,640
12,000
19,500
40,0(M)
72,600
115.000
70
46
95
179
368
552
1,060
1,690
3.000
6,110
11,100
17,900
36,800
66.800
106,000
80
42
89
167
343
514
989
1,580
2,790
5,680
10,3(K)
16,700
34,200
62 J (M)
98,400
90
40
83
157
322
482
928
1,480
2,610
5,330
9,6.50
15,600
32,100
58,.300
92,300
100
38
79
148
30-4
455
877
1,400
2,470
5,040
9,110
14,800
30,.300
55,100
87,200
125
33
70
131
2()9
403
777
1,240
2,190
4,460
8,080
13,100
26,900
48,8(M)
77,300
150
30
63
119
244
366
704
1,120
1,980
4.050
7,320
11,900
24,300
44.200
70,000
175
28
58
109
224
336
648
1,030
1,820
3,720
6,730
10,900
22,400
40,700
64,400
200
26
54
102
209
313
602
960
1,700
3,460
6,260
10,100
20,800
37,900
59,900
250
23
48
90
ia5
til
534
851
1,5(«)
3,070
5,5.50
8,990
]8,5(K)
33,.5(K)
53,100
300
21
43
82
168
251
484
771
1,360
2,780
5,0.30
8,1.50
16,700
30,400
48,1(X)
350
1.9
40
75
1,54
231
445
709
1.250
2..560
4,630
7,490
15.400
28,0(H)
44,-300
400
18
37
70
143
21.5
414
660
1,170
2,380
4,310
6,970
14„300
26,000
41,200
450
17
35
66
135
202
389
619
1,090
2,2.30
4,040
6,540
13,400
24,400
.38,600
500
16
33
62
127
191
367
385
1,0.30
2,110
3,820
6,180
12,7(K)
23,1(K)
.36„500
550
15
31
.59
121
181
349
5.56
982
2,000
3,620
5,870
12.100
21,900
34,700
600
14
30
.56
115
173
333
530
937
1.910
3,460
5,600
11..5{K)
20.900
33,100
6S0
14
29
54
110
165
318
508
897
1,8.30
3,310
5,.360
11,000
20,000
31,700
700
13
27
52
106
1,59
306
488
862
1,760
3,180
5,150
10,600
19,200
30,400
750
13
26
60
102
1.53
295
470
SSO
1,690
3,060
4,960
10,200
18,500
29,300
8«)
12
26
48
99
148
285
454
802
1,640
2,960
4,790
9.840
17.9(K>
28,3(K)
850
12
25
46
95
143
275
439
776
1,580
2,8fJ0
4,640
9,530
17,-300
27,400
900
11
24
45
93
139
267
426
752
1,530
2,780
4.500
9,240
16,800
26,600
950
11
23
44
90
135
259
413
731
1,490
2,700
4,370
8,970
16,300
25,800
1,000
11
23
43
87
131
2.52
402
711
1.450
2,620
4.250
8,720
15,800
2.5,100
1,100
10
21
40
83
124
240
382
675
1,380
2,490
4,030
8.290
15.1(X)
23,800
1,200
NA
20
39
79
119
229
364
644
1,310
2,380
3,850
7,910
14,4{M)
22,700
1,3(X)
NA
20
37
76
114
219
349
617
1.260
2,280
3.680
7,570
13,700
21,800
1,400
NA
19
35
73
109
210
335
592
1,210
2,190
3.540
7,270
13,200
20,900
1,500
NA
18
34
70
105
203
323
571
1.160
2,110
3,410
7,010
12.700
20,100
1,600
NA
18
33
68
102
196
312
551
1,120
2,030
3,290
6.770
12,300
19,500
1,700
NA
17
32
66
98
189
302
533
l,Ot»
1,970
3.190
6,550
11,900
18,800
L8{H)
NA
16
.31
64
95
184
293
517
1,050
i,9U)
3,090
6,3.50
J 1,. 5(H)
i8„300
1,900
NA
16
30
62
93
178
284
502
1,020
1,850
3,000
6,170
11,200
17,700
2,000
NA
16
29
60
90
173
276
488
1,000
1,800
2,920
6,000
10,900
17,200
NA means a flow of less than 10 cfli.
Note: All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
171
Table 12-8
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-8 Schedule 40 Metallic Pipe [NRPA Table 6.2(b)]
Cas:
Natural
Inlet Pressure;
Less than 2 psi
Pressure Drop:
0.5 in. w.c.
Specific Gravity!
0.60
Pipe Size (in.)
Nominal:
Vi
V*
1
VA
VA
2
VA
3
4
5
6
8
10
12
Actual ID:
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
5.047
6.065
7.981
10.020
11.938
Length (ft)
Capacity iti Cubic Feet of Gas per Hour
HI
172
360
678
1,390
2,090
4.-,02O
6,400
11.300
23,100
4i,8(K>
67,600
139,000
252,000
39<),000
20
118
247
466
957
1,430
2,7t)0
4,400
7,780
15,900
28,700
46,.500
95,.500
173,000
275,000
30
95
109
374
768
1,150
2,220
3.530
6,250
12,700
23,0(X)
37,300
76,700
139,000
220,0(K)
40
81
170
320
657
985
1,900
3,020
5,350
10,900
19,700
31,900
65,(500
119,000
189,0m)
50
72
151
284
583
873
1,680
2,f>80
4.740
9,660
17,5W)
28.300
58,200
106,000
167,000
60
65
137
257
528
791
1,520
2,430
4,290
8,760
15,800
25.600
52,700
95,700
152,000
70
60
126
237
486
728
1,4(M)
2,230
3.950
8.050
14.6{K)
23,600
48,.500
88,1 (K>
139,0(K)
80
56
117
220
452
677
1.300
2,080
3,670
7,490
13,600
22,000
45,100
81,900
130,000
90
52
110
207
424
635
1,220
1.950
3,450
7.030
12,700
20,600
42,-300
76,900
122,0a)
100
50
104
195
400
600
\,\m
1,840
3.260
6,640
12,000
19,.500
40.000
72,600
115,000
125
44
92
173
355
532
1,020
1,630
2,890
5,890
10,600
17,200
35,400
64,300
102,000
150
40
83
157
322
482
928
1,480
2,610
5,330
9,650
15,600
32,100
■ 58,3«)
92,300
175
.^7
77
144
296
443
854
1,360
2.410
4,910
8,880
14,400
29,300
53,600
84,900
200
34
71
134
275
412
794
1,270
2,240
4,560
8,260
13,400
27.500
49,900
79,000
250
30
63
119
244
366
704
1,120
1,980
4,050
7,320
11,900
24,.300
44,200
70,000
300
27
57
108
221
331
638
1,020
1,800
3,670
6,630
10,700
22,100
40,100
63,400
350
25
53
99
203
305
587
935
1,650
3,370
6.100
9,880
20,300
36,900
58,400
400
23
49
92
189
283
546
870
1,540
3,140
3,680
9,190
18,900
34.300
54.300
450
22
46
86
177
266
512
816
1,440
2,940
5,330
8,620
17,700
32,200
50,900
300
21
43
82
168
251
484
771
1,360
2,780
5,030
8,150
16,700
30,400
48,100
550
20
41
78
159
239
4.59
732
1,290
2.640
4,780
7,740
15,!K)0
28,900
45,700
(WO
19
39
74
152
228
438
699
1,240
2,520
4,5«)
7,380
15,200
27,5(K)
43,600
650
18
.38
71
145
218
420
669
1,180
2,410
4,360
7,070
14, .500
26,400
41,800
700
17
36
68
140
209
403
(rlS
1,140
2,320
4, UK)
6,790
14,(X)0
25,300
40,1 (K)
750
17
35
66
135
202
389
619
1,090
2,230
4,040
6,540
13,400
24,400
38,600
800
16
34
63
130
195
375
598
1,060
2,160
3,900
6,320
13,000
23,600
37,3(K)
850
16
33
61
126
189
363
579
1.020
2,090
3,780
6,110
12,iJ00
22.800
36,100
900
15
32
.59
122
183
.352
561
992
2,020
3,660
5,930
12,200
22,100
35,000
050
15
31
58
118
178
342
545
963
1,960
3,550
5,760
11,800
21,500
34,000
1,(X(0
1,4
30
56
115
173
333
530
937
1,910
3,460
3,600
11, .500
20,900
33,100
1,100
14
28
53
109
164
316
503
890
1,810
3,280
5,320
10,900
19,8(K)
3I,4(X)
1,200
13
27
51
104
156
301
480
849
1,730
3,130
5,070
10,400
18,000
30,000
1,300
12
26
49
100
150
289
460
813
l,6(i0
3,000
4,8(>0
9,980
18,100
28,7a)
1,400
12
25
47
96
144
277
442
781
1..590
2,880
4,670
9,.590
17,400
27,600
1,500
11
24
45
93
139
267
426
752
1,530
2,780
4,500
9,240
16,800
26,600
1,600
11
23
44
89
134
258
411
727
1,480
2,680
4.340
8,920
16,200
25.6(M)
1,700
11
22
42
86
130
250
398
703
1,430
2,590
4.200
8,630
15,700
24,800
1,800
10
22
41
84
126
242
386
682
1,390
2,520
4,070
8,370
15,200
24.100
1 ,«)0
10
21
40
81
122
235
375
662
1,350
2,440
3,960
8,1.30
14,S*K)
23,400
2,000
NA
20
39
79
119
229
364
644
1,310
2,380
3,850
7,910
14,4(K)
22,700
NA means a flow of less than 10 cfli.
Note: All table entries are rounded to .S .significant digits.
172
FUEL PIPING
Table 12-9
Table 12-9 Schedule 40 MetaUic Pipe [NFPA Table 6.2(c)]
Gas:
Natural
inlet PressMiie:
2.0 psi
Pressure Drop:
1.0 psi
Specific Gmvi^
0,60
Pipe Size (in.)
Nominal:
«/4
%
1
l'/4
VA
2
V/k
3
4
Actual ID:
0.622
0.824
1.049
1.3S0
1.610
2.067
2.469
3.068
4.026
Length (ft)
Capacity in
Cubic Feet of Gas per Hour
10
1,510
3.040
5,560
11,400
17,100
32,9«)
52,500
92,800
189,(M)0
20
1,070
2,150
3,930
8,070
12,100
23,300
37,1,00
65,600
134,000
30
869
1.760
3,210
6„590
9,880
19,000
30,300
53,600
109.000
40
753
1,520
2,780
.5,710
8,550
16,.500
26,300
46,400
94,700
50
673
1,860
2,4<Ki
5,110
7,650
■ 14,700
23,5(X)
41„500
84,700
60
615
1,24«
2,270
4,660
6,980
13,!500
21,400
37.900
77.300
-70
569
1,150
2,100
4,320 •
6,470
12,500
19,900
35,100
71,600
80
532
1,080
1,970
■ 4,040
6,050
11,700
18,600
32,800
67.000
90
502
1,010
1,850
3,810
5.700
11.000
17,500
30,900
63,100
100
, 462
934
1,710
3,510
5,260
10.100
16,100
28,500
58,200
125
414
836
1,530
3,140
4,7tX»
9,060
14,400
25,500
r.2,100
150
372
751
1,370
2,820
4,220
8,130
13,000
22,900
46,700
175
344
695
1,270
2.601
3,910
7,530
12,000
21,200
43,300
200
318
642
1,170
2,410
3,610
6.960
11.100
19,600
40,000
250
279
583
1,040
2,140
.3,210
6,180
9,850
17,400
35.500
300
253
.528
945
1,94:0
2,910
b,m)
8,920
15,800
32,200
350
232
486
869
1.790
2.670
5,1.50
8,210
14.500
29,600
400
216
452
809
1,660
2,490
4,790
7,640
13,500
27,500
450
203
424
759
1,560
2,330
4,500
7,170
12,700
25,800
500
192
401
717
1,470
2,210
4,250
6,770
12,000
24,400
550
182
381
681
1,400
2,090 -
4,030
6,430
11.400
23,200
600
174
3()3
6.50
1,.330
2,000
3,8.50
6.130
10,800
22,100
650
166
348
622
1.280
1,910
3.680
5,870
10,400
21,200
700
160
334
598
1,2.30
1,840
3,54«
5,640
9,970
20,300
750
154
322
576
1,180
1.770
3,410
5,440
9,610
19,600
800
149
311
556
1,140
1,710
3,290
5,2>)0
9,280
18,900
850
144
.301
5.38
1,100
1,650
3,190
5,080
8,980
18,300
900
139
292
522
1,070
1,600
3,090
4,930
8,710
17,800
950
135
283
507
1,040
1,560
3,000
4,780
8,460
17.200
1,000
132
275
493
1,010
1,520
2,920
4,6.50
8,220
16.800
1,100
125
262
468
960
1,440
2,770
4,420
7,810
15,900
1.200
119
250
446
917
1,370
2,640
4,220
7.450
15,200
1,300
114
2-39
427
878
1,320
2,5,30
4,040
7,140
14,600
1,400
110
2.30
411
843
1.260
2,430
3.880
6,860
14,000
1,500
106
221
396
812
1,220
2,34.0
3,740
6,600
13,500
1,600
102
214
382
784
1,180
2,260
3,610
6,380
13,000
1,700
99
207
370
7.59
1,140
2,190
3,490
6,170
12,600
1,800
96
200
358
736
l.KM)
2.120
3,390
5,980
12,200
1,9<M)
93
193
348
715
1,070
2,060
3,290
5,810
11,900
2,000
91
189
339
695
1,040
2.010
3,200
5,650
11, .500
Note: All Uible entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
173
Table 12-10
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 1 2-1 Schedule 40 MetaUic Pipe [NFPA Table 6.2(d)]
Gas:
Natural
Inlet Pressure:
3.0 psi
Pressure Drop:
2.0 psi
Specific Gravity:
0.60
Pipe Size (in.)
Nominal:
H
»/4
I
VA
IH
2
2M.
3
4
Actual ID:
0.622
0.824
1.049
1,380
1,610
2.067
2.469
3.068
4.026
Length (ft)
Capacity in
Cubic Feet of Gas per Hour
10
2„%0
4.920
9.270
19,000
28,500
54,900
87,500
155.000
316,000
20
1,620
3,380
6,370
13,100
19,600
37,700
60,100
106,000
217,000
30
1300
2,720
5,1 10
10,500
15,700
30,300
48,300
85,400
174,000
40
1,110
2,320
4,380
8,9i»0
13,500
25,900
41,3(X)
73,100
149,000
50
985
2,060
3,880
7,970
11,900
23,000
36,6(K)
64,800
132,000
60
892
1,870
3,520
7,220
10,800
20,800
33,200
58,700
120,000
70
821
1,720
3,230
6,640
9,950
19,200
30,500
54,000
110,000
80
764
1,600
3,010
6,180
9,260
17,800
28,400
50.200
102,000
90
717
1,500
2.820
5,800
8,680
16,700
26,700
47,100
96,100
100
677
1,420
2,670
5,470
8,200
15,800
25,200
44,500
90,800
125
600
1,250
2,360
4,850
7,270
14,000
22,300
39,500
80,500
150
.544
l.HO
2,140
4,400
6,590
12,700
20,200
35.700
72,900
175
,500
1.050
1,970
4,040
6,060
11,700
18,600
32,900
67,100
200
465
973
1,830
3,760
5,640
10,900
17,300
30,600
62,400
250
412
862
1,620
3,330
5,000
9,620
15.300
27.100
55,300
soo
,H74
781
1,470
3,020
4,530
8,720
13,900
24,0)00
.50.100
350
344
719
1,.350
2,780
4,170
8,020
12,800
22,600
46,100
400
,^20
(>69
1,260
2,590
3,870
7,460
11,900
21,000
42,900
450
300
627
1.180
2,430
3,640
7,000
11,200
19.700
40,200
500
283
593
1,120
2,290
3,430
6,610
10,500
18,600
38,000
550
269
563
1,060
2,180
3,260
6,280
10.000
17,700
.36,100
600
257
537.
1,010
2,080
3,110
5,990
9,550
16,900
34,400
S50
246
514
969
1,990
2,980
5,740
9,1,50
16.200
33,000
700
236
494
931
1,910
2,860
5,510
8,790
15,.500
31,700
750
228
476
897
1,840
2,760
.5,310
8,470
15,000
30,500
800
220
460
866
1,780
2,660
5,130
8,180
14,500
29,500
850
213
445
838
1,720
2,580
4,960
7.910
14,000
28,500
900
206
431
812
1,670
2,500
4,810
7,670
13,600
27,700
950
200
419
789
1,620
2,430
4,670
7,450
13,200
26,900
1,000
195
407
767
1,580
2,360
4,5.50
7,240
12,800
26,100
1,100
.185
387
729
1,600
2,240
4,320
6,890
12,200
24.800
1,200
177
369
695
1,430
2,140
4,120
6,570
11,600
2.3,700
I, .WO
169
353
666
1,370
2.050
3,940
(j,290
11,100
22,700
1,400
162
340
640
1,310
1,970
3,790
6,040
10,700
21,8<.i0
1,500
166
327
616
1.270
1,900
3,650
5,820
10,.300
21,000
1,()00
151
316
595
1,220
1,830
3,530
5,620
10,000
20,300
1,700
146
306
576
1,180
1.770
3,410
5,440
9,610
19,600
1,800
142
296
558
1,150
1,720
3,310
5.270
9,320
19,000
1,900
138
288
542
1.110
1,670
3,210
5,120
9,050
18,400
2,000
1,34
280
527
1,080
1,620
3,120
4.980
8,800
18.000
Note: All table entries are rounded to 3 significant digits.
174
FUEL PIPING
Table 12-11
Table 12-11 Schedule 40 MetalUc Pipe [NFPA Table 6.2 (e)]
Gas:
Natural
Inlet Pressure:
5.0 psi
Pressure Drop:
3.5 psi
Specific Gravifys
0.60
Pipe Size (in.)
Nominal:
'/4
V4
1
VA
m
2
2Mi
3
4
Actual ID:
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
Length (ft)
Capacity in
Cubic Feet of Gas per Hour
10
3,190
6,430
11,800
24,200
36,200
69,700
111.000
196,000
401,000
20
2,250
4,550
8,320
17,100
25,600
49,300
78.600
139,000
283,000
30
1,840
3,720
6,790
14,000
20,900
40,300
64,200
113.000
231,000
40
1,590
3,220
3,880
12,100
18,100
34,900
53,600
98.200
200,000
50
1,430
2,880
5,260
10,800
16,200
31,200
49,700
87,900
179,000
60
1,300
2,630
4,800
9,860
14,800
28,500
45,400
80,200
164,000
70
1,200
2,430
4,450
9,130
13,700
26,400
42,000
74,300
151,000
80
1,150
2,330
4,260
8.540
12,800
24,700
.39,300
69,.500
142,000
90
1,060
2,150
3,920
8,050
12,100
23,200
37.000
65,500
134,000
100
979
1,980
3,620
7,4.30
11,100
21,400
34.200
60,400
123,000
125
876
1.770
3,240
6,640
9,950
19,200
.30,600
54,000
110,000
150
786
im)
2,910
.5,960
8,940
17,200
27,400
48,500
98,900
175
728
1,470
2,690
5,520
8,270
15,900
25,400
44,900
91,600
200
673
1,360
2,490
5,100
7,650
14,700
23..500
41,500
84,700
250
558
1,170
2,200
4.510
6,760
13,000
20,800
36,700
74,900
300
506
i.om
1,990
4,090
6,130
11,800
18,800
.33,300
67,800
350
465
973
1,830
3,760
5,640
10,900
17,300
.30,600
62,400
400
433
905
1,710
3„500
5,250
10,100
16,1(K)
28,500
58,100
450
406
849
1,600
3,290
4,920
9.480
15,100
26,700
54 ,.500
500
384
802
1,510
.3,100
4,650
8.950
14,300
25,200
51,.tO0
550
364
762
1.440
2,950
4,420
8,500
13,600
24,000
48,900
600
348
727
1.370
2,810
4,210
8,110
12,900
22,900
46,600
650
333
696
1,310
2,690
4,030
7,770
12,400
21,900
44,600
700
320
669
1,260
2„590
3,880
7.460
11,900
21,000
42,900
750
308
644
1,210
2,490
3,730
7,190
11,5(K)
20,300
41,300
800
298
622
1,170
2,410
3,610
6,940
11.100
19,600
39,900
850
288
602
1,130
2,330
3,490
6,720
10,700
18,900
38,600
900
279
584
1,100
2,260
3,380
6,320
10.400
18,400
37,400
950
271
567
1.070
2,190
3,290
6,330
10.100
17,800
36,400
1,000
264 .
551
1,040
2,130
3,200
6,150
9.810
17,300
35,400
1,100
250
524
987
2,030
3,030
5.840
9.320
16„500
33,600
1,200
239
500
941
1,930
2,900
5,580
8,890
15,700
32,000
1.300
229
478
901
1,850
2,770
5,340
8,510
15,000
30,700
1.400
220
460
866
1,780
2,660
5,1.30
8,180
14,500
29,500
1,500
212
443
834
1,710
2,570
4,940
7.880
]3,900
28.400
1,600
205
428
806
1,650
2,480
4,770
7.610
13,400
27,400
1,700
198
414
780
1,600
2,400
4,620
7,360
13,000
26,500
1,800
192
401
756
1,550
2,330
4,480
7,140
12,600
25,700
1,900
186
390
734
1,510
2.260
4.3-50
6,930
12,300
25.000
2.000
181
379
714
1,470
2,200
4,230
6,740
11,900
24,300
Note: All table entries itre rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
175
Table 12-12
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-12 Semi-Rigid Copper Tubing [NFPA Table 6.2(f)]
Gas:
Natural
Inlet Pressure:
Less than 2 psi
Pressure Drop:
0.3 in. w.c.
Specific Gravity:
0.60
Tube Size (in.)
K&JU
W
%
'At
%
%
1
VA
l¥i
2
ACR:
%
'/a
¥»
¥*
%
!'/»
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:*
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
20
42
85
148
210
448
806
1,270
2,650
20
14
29
58
102
144
308
554
873
1,820
30
11
23
47
82
116
247
445
701
1,460
40
10
20
40
70
99
211
381
600
1,250
50
NA.
17
35
62
88
187
.337
532
1,110
60
NA
16
32
56
79
170
306
482
1,000
70
NA
14
2<)
52
73
156
281
443
924
80
NA
13
27
48
68
145
262
413
859
90
NA
13
26
45
64
J 36
245
387
806
100
NA
12
24
43
60
129
232
366
761
125
NA
11
22
38
53
114
206
324
675
150
NA
10
20
34
48
103
186
294
612
175
NA
NA
18
31
45
95
171
270
563
200
NA
. NA
17
29
41
89
159
251
523
250
NA
NA
15
26
37
78
141
223
464
300
NA
NA
13
23
33
71
128
202
420
SSO
NA
NA
12
22
31
65
118
186
387
400
NA
NA
11
20
28
61
110
173
360
450
NA
NA
11
19
27
57
103
162
338
500
NA
NA
10
18
25
54
97
153
319
550
NA
NA
NA
17
24
51
92
145
303
(iOO
NA
NA
NA
16
23
49
88
139
289
(■(50
NA
NA
NA
15
22
47
84
133
277'
700
NA
NA
NA
16
21
45
81
128
266
750
NA
NA
NA
14
20
43
78
123
256
800
NA
NA
NA
14
20
42
75
119
247
850
NA
NA
NA
13
19
4,0
73
115
239
900
NA
NA
.NA
13
18
39
71
111
232
950
NA
NA
NA
13
18
38
69
108
225
1,000
NA
NA
NA
12
17
37
67
105
219
1,100
NA
NA
NA
12
16
35
63
100
208
1,200
NA
NA
NA
11
16
34
60
95
199
1,300
NA
NA
NA
11
15
32
58
91
190
1,400
NA
NA
NA
10
14
31
56
88
183
1,500
NA
NA
NA
NA
14
30
54
84
176
1,600
NA
NA
NA
NA
13
29
52
82
170
1,700
NA
NA
NA
NA
13
28
50
79
164
1,800
NA
NA
NA
NA
13
27
49
77
159
1,900
NA
NA
NA
NA
12
26
47
74
155
2,(XI0
NA
NA
NA
NA
12
25
46
72
151
NA means a flow of less than 10 cfli.
Note: .A.11 table emries are rounded to 3 significant, digits.
'Table capacities are based on T)pe K copper tubing inside diameter (shov\ni) , which has the smallest inside
diameter of tJie copper tubing products.
176
FUEL PIPING
Table 12-13
Table 1 2-1 3 Semi-Rigid Copper Tubing [NFPA Table 6.2(g)]
Gas:
Natui'al
Inlet Pressure:
I.«$s than 2 psi
Presjsure Drop:
O.S in. w.c,
Spedific Gravity:
0.60
Tube Size (in.)
KScU
'/4
%
¥i
%
%
1
VA
VA
2
Nominal:
ACR:
%
H
%
%
%
11/8
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1,125
1.375
1.625
2.125
Inside:'
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in
dubic Feet of Gas per Hour
10
27
55
Hi
195
276
590
1,060
1,680
3,490
20
18
38
77
134
190
406
730
1,150
2,400
30
15
30
61
107
152
.326
586
925
1.9.30
•10
13
26
53
92
131
279
502
791
1,650
50
11
23
47
82
116
247
445
701
1,460
60
10
21
42
74
105
224
403
635
1,.320
70
NA
19
39
68
96
206
371
585
1,220
80
.NA
18
36
63
90
192
,345
544
1,130
90
NA
17
M
59
84
180
324
510
1,060
100
NA
16
32
55
79
170
306 .
482
1,000
125
NA
14
28
50
70
151
271
427
890
150
NA
13
26
45
64
136
245
387
806
175
NA
12
24
41
59
126
226
.356
742
200
NA
11
22
39
55
117
210
331
690
250
NA
NA
20
34
48
103
186
294
612
300
NA
NA
18
31
44
94
169
266
.554
350
NA
NA
16
28
40
86
155
245
510
400
NA
NA
15
26
38
80
144
228
474
450
. NA
NA
14
25
35
75
135
214
445
500
NA
NA
13
23
33
71
128
202
420
550
NA
NA
13
22
32
68
122
192
399
600
NA
NA
12
21
30
64
116
183
381
650
NA
NA
12
20
29
62
111
175
365
700
NA
NA
11
20
28
59
107
168
350
750
NA
NA
11
19
27
57
103
162
338
80C>
NA
NA
10
IS
26
55
99
1.56
.326
850
NA
NA
10
18
25
5.3
96
151
315
9m
NA
NA
NA
17
24
52
93
147
306
950
NA
NA
.NA
17
24
.50
90
143
297
l.WM)
NA
NA
NA
16
23
49
88
139
289
1,100
NA
NA
NA
15
22
46
84
132
274
1,200
NA
.\'A
NA
15
21
44
80
126
262
1,300
NA
NA
NA
14
20
42
76
120
251
U(m
NA
NA
NA
13
19
41
73
116
241
1,500
NA
> NA
NA
13
18
.39
71
111
232
1,600
NA
NA
NA
13
18
38
68
108
224
1,700
NA
NA
NA
12
17
37
66
104
217
1.800
NA
.NA
NA
12
17
36
64
101
210
1,900
NA
NA
NA
11
16
35
62
98
204
2,000
NA
NA
NA
11
16
34
60
95
199
NA means a flow of less than 10 dli.
Note: All table entries are rotmded to 3 significant digits.
'Table capacities are based on Type K. copper tubing inside diameter (shown) , which has the smallest inside
diameter of the copper tubing products.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
177
Table 12-14
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-14 Semi-Rigid Copper Tubing [NBPA Table 6.2(h)]
Gas: Natural
Met Pressure:
Pressure Drop:
Specific Gravity:
Less than 2 psi
1.0 in. W.C.
0.60
SPi-.CIAI. L'Sr.: Tube Si/ing lictwccn Mou.sc Line Re(<;iilator and the Appliance.
Tube Size (in.)
K&L:
W
%
^A
%
%
1
VA
I'A
2
ACR:
%
14
%
%
%
IVs
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:*
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
.39
80
162
283
402
859
1,.550
2.440
5.080
20
27
53
111
195
276
590
1,060
1,680
3,490
30
21
44
89
156
222
474
853
1,350
2,800
40
18
38
77
134
190
406
730
1,1.50
2,400
50
16
33
68
119
168
359
647
1,020
2,1-30
60
15
30
61
107
152
326
586
925
1.930
70
13
28
57
99
140
300
539
851
1,770
80
13
26
53
92
131
279
502
791
1,650
90
12
24
49
86
122
262
471
742
1,550
JOO
IJ
23
47
82
116
247
445
701
1,460
125
NA
20
41
72
103
219
394
622
1,290
J50
.NiA
18
37
65
93
198
357
563
1,170
175
NA
17
34
60
85
183
329
518
1,080
200
NA
16
32
56
79
170
306
482
1,000
250
NA
14
28
50
70
151
271
427
890
300
NA
13
26
45
64
136
245
387
806
350
NA
12
24
41
59
125
226
356
742
400
NA
11
22
39
55
117
210
331
690
450
NA
10
21
36
51
110
197
311
647
500
.NiA
NA
20
34
48
103
186
294
612
530
NA
NA
19
32
46
98
177
279
581
600
NA
NA
18
31
44
94
169
266
554
630
NA
NA
17
30
42
90
162
255
531
700
NA
NA
16
28
40
86
L55
245
510
750
NA
NA
16
27
39
83
150
236
491
800
NA
NA
15
26
38
80
144
228
474.
8.50
•N'A
NA
15
26
36
78
140
. 220
459
900
NA
NA
14
25
35
75
135
214
445
950
NA
NA
14
24
34
73
132
207
432
1,000
.NA
NA
13
23
33
71
128
202
420
l,i00
NA
NA
13
22
32
68
122
192
399
1,200
.NA
NA
12
21
30
64
116
183
381
1,SOO
NA
NA
12
20
29
62
111
175
365
J, 400
NA
NA
11
20
28
.59
107
168
3.50
1,500
NA
NA
11
19
27
57
103
162
338
1,600
.N'A
.NA
10
18
26
55
99
156
326
1,700
NA
NA
10
18
25
53
96
151
315
1,8(K)
NA
NA
NA
17
24
52
93
147
306
1,900
NA
.NA
NA
17
24
50
90
143
297
2,000
NA
NA
NA
16
23
49
88
1.39
289
NA means a flow of less than 10 cfli.
Note: All table entries are rounded to 3 significant digits.
"Table capacities are based on Type K copper tubing inside diameter (.shtnvn), which has the smallest inside
diameter of the copper tubing products.
178
FUEL PIPING
Table 12-15
Table 12-15 Semi-Rigid Copper Tubing [NFPA Table 6.2(i)]
Gas:
Natural
Inlet Pressure:
Less tlian 2.0 psi
Pressure Drop:
17.0in. w.c.
Specific Gravity:
0.60
Tube Size (in.)
Noxniiial:
K&L:
V*
%
V4
%
y«
\
VA
m
2
ACR:
%
>/4
%
%
%
IMt
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:*
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
190
391
796
1,390
1.970
4,220
7,590
12,000
24.900
20
130
269
547
956
1,360
2,900
5,220
8,230
17,100
30
105
216
439
768
1,090
2,330
4.190
6,610
13,800
40
90
185
376
657
932
1,990
3,590
5,630
11,800
50
79
164
333
582
826
1,770
3,180
5,010
10,400
60
72
148
302
528
749
1,600
2,880
4,540
9,460
70
66
137
278
486
689
1,470
2,650
4,180
8,700
80
62
127
258
452
641
1,370
2,460
3,890
8,090
90
58
119
243
424
601
1,280
2,310
3,650
7,590
100
55
113
229
400
568
1,210
2,180
3,44(J
7.170
123
48
100
203
355
503
1,080
1,940
3,050
6,360
150
44
90
184
321
4.56
974
1,750
2,770
5,760
175
40
83
169
296
420
896
1,610
2,540
5,300
200
38
77
157
275
390
834
1,500
2,370
4,930
250
33
69
140
244
346
739
1,330
2,100
4,370
300
30
62
126
221
313
670
1,210
1,900
3,960
350
28
57
116
203
288
616
1,110
1,750
3,640
400
26
53
108
189
268
573
1,030
1,630
3,390
450
24
50
102
177
252
538
968
1,530
3,180
500
23
47
96
168
238
508
914
1,440
3,000
550
22
45
91
159
226
482
868
1,370
2.850
600
21
43
87
152
215
460
829
1,310
2,720
650
20
41
83
145
206
441
793
1,2.50
2,610
700
19
39
80
140
198
423
762
1,200
2,500
750
18
38
77
135
191
408
734
1,160
2,410
800
18
37
74
130
184
394
709
1,120
2,330
850
17
33
72
126
178
381
686
1,080
2,250
900
17
34
70
122
173
370
665
1,050
2,180
950
16
33
68
118
168
359
646
1,020
2,120
1,000
16
32
66
115
163
349
628
991
2,060
1,100
15
31
63
109
155
832
397
941
1,960
1,200
14
29
60
104
148
316
569
898
1.870
1,300
14
28
57
100
142
303
545
8m
1,790
1,400
13
27
35
96.
136
291
524
826
1,720
1,500
13
26
53
93
131
280
505
796
1,660
1,600
12
25
51
89
127
271
487
768
1,600
1.700
12
24
49
86
123
262
472
744
1,550
1,800
11
24
48
84
119
254
457
721
1,500
1,900
11
23
47
81
115
247
444
700
1,460
2,000
11
22
45
79
112
240
432
681
1,420
Note: All table entries are rounded to 3 significant digits.
'Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside
diameter of the copper tubing products.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
179
Table 12-16
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-16 Semi-Rigid Copper Tubing [NFPA Table 6.2 (j)]
Gas:
Natural
Inlet Pressure:
2.0 psi
Pressure Drop:
I.Opsi
Specific Gravity:
0.60
Tube Size (in.)
Nominal:
K&L:
Vi
%
'/4
'A
%
1
W*
m
2
ACR:
%
V2
%
%
'/&
VA
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:*
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.4«1
1.959
Length (ft)
Capacity in
Cubic Feet of Gas per Hour
10
245
506
1,030
1,800
2,550
5,450
9,820
15,500
32,200
20
lf>9
348
708
1,240
1,760
3,750
6,750
10,600
22,200
30
135
279
568
993
1.410
3,010
5,420
8,550
17,800
40
116
239
486
850
1,210
2,580
4,6'10
7,310
15,200
50
103
212
431
754
1,070
2,280
4,110
6,480
13,500
60
93
192
391
683
969
2,070
3,730
5,870
12,200
70
86
177
359
628
891
1,900
3,430
5,400
11,300
80
80
164
3.34
584
829
1.770
3,190
5,030
10,500
90
75
154
314
548
778
1,660
2,990
4,720
9,820
100
71
146
296
518
735
1,.570
2,830
4.450
9,280
125
63
129
263
459
651
1,390
2,500
3,950
8,220
150
57
117
238
416
590
1,260
2,270
3,580
7,450
175
52
108
219
383
543
1,160
2,090
3,290
6,850
200
49
100
204
356
505
1,080
1,940
3,060
6,380
250
43
89
181
315
448
956
1,720
2,710
5,650
30O
39
80
164
286
406
866
1,560
2,460
5.120
350
36
74
150
263
373
797
1,4.30
2,260
4,710
400
33
69
140
245
347
741
1,330
2,100
4,380
450
31
65
131
230
326
696
1,250
1.970
4,110
500
30
61
124
217
308
657
1,180
1,870
3,880
550
28
58
118
206
292
624
1,120
1.770
3,690
600
27
55
112
196
279
595
1,070
1,690
3,520
650
26
53
108
188
267
570
1.030
1,620
3,370
700
25
51
103
181
256
548
986
1,550
3,240
750
24
49
100
174
247
528
950
1,500
3,120
800
23
47
96
168
239
510
917
1,450
3,010
850
22
46
93
163
231
493
888
1,400
2.920
900
22
44
90
158
224
478
861
1,360
2,830
950
21
43
88
153
217
464
836
1,320
2,740
1.000
20
42
85
149
211
452
813
1,280
2,670
i,l(K)
19
40
81
142
201
429
772
1,220
2,540
1,200
18
38
77
135
192
409
737
1,160
2,420
13(X>
18
36
74
129
183
392
705
1,110
2,320
1,400
17
35
71
124
176
376
678
1,070
2,230
1,500
16
34
68
120
170
363
653
1,030
2.140
1.600
16
33
66
116
164
350
630
994
2,070
IJOO
15
31
64
112
159
339
610
962
2,000
1.800
15
30
62
108
154
329
592
933
1,940
1,900
14
30
60
105
149
319
575
906
1,890
2.0(K)
14
29
59
102
145
310
559
881
1,830
Note: All table entries are rotmded to 3 significant digits.
^liible capacities are based on Type K copper tubing inside diameter (shown), which has the sraallest inside
diameter of the copper tubing products.
180
FUEL PIPING
Table 12-17
Table 12-17 Semi-Rigid Copper Tubing [NFPA Table 6.2(k)]
Gas:
Natural
Inlet Pressure:
2,0 psi
Pressure Drop:
1.5 psi
Specific Gravity:
0.60
SPF.CIAI. U.SE: Pipe .Si/ing Between Point of Deliver}- and tite House Line Regulator. Total Load Supplied by a
Single Hou.se Line Regulator Not tlxreeding 130 Clubir Feet pc r Hour.*
Tube Size (in.)
K&L:
V*
%
VI
%
y*
1
I'/i
IW
2
Nominal:
ACR:
y»
W
%
%
%
IH
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:*
0.305
0.402
0.527
0.632
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in
Cubic Feet of Gas per Hour
10
303
625
1,270
2,220
3,150
6,740
12,100
19,100
39,800
20
208
430
874
1,530
2,170
4,630
8,330
1,3,100
27,400
30
167
345
702
1,230
1,740
3,720
6,690
10,600
22,000
40 .
143
295
601
1.050
1,490
3,180
5,730
9,030
18,800
50
127
262
532
931
.1.320
2,820
5,080
8,000
16,700
60
115
237
482
843
1,200
2.560
4,600
7,250
15,100
70
106
218
444
776
l,l(K)
2,350
4,230
6,670
13,900
SO
98
203
413
722
1.020
2,190
3.940
6,210
12,900
90
92
190
387
677
961
2,050
3,690
5,820
12,100
100
87
180
366,
640
907
1,940
3,490
5,500
ll..,500
125
77
159
324
567
804
1.720
3.090
4,880
10,200
150
70
144
294
514
729
1,560
2,800
4,420
9.200
175
64
133
270
472
670
1,430
2,580
4,060
8,460
200
60
124
252
44.0
624
1,330
2,4(K)
3,780
7,870
250
53
110
223
390
553
1,180
2.130
3,350
6,980
300
48
99
202
353
501
1,070
1.930
3,040
6,320
350
44
91
186
325
461
984
1,770
2,790
5,820
400
41
85
173
802
429
916
1.650
2,600
5,410
450
39
80
162
283
402
859
1.550
2,440
5.O80
500
36
75
153
268
380
811
1,460
2,300
4,800
550
,35
72
14.6
254
361
771
1.390
2,190
4,560
600
33
68
139
243
344
735
1.320
2.090
4.350
650
32
65
1,33
232
330
704
1,270
2,000
4,160
700
30
63
128
223
317
676
1,220
1,920
4,000
750
29
60
123
215
305
652
1,170
1.850
3,850
800
28 .
58
119
208
295
629
1,130
1,790
3,720
850
27
57
115
201
285
609
1.100
1,730
3,600
9(K)
27
.55
111
195
276
590
1.060
1,680
3,490
950
26
53
108
189
268
573
1,030
1,630
3,390
1,000
25
52
105
184
261
5.58
1,000
1,380
3,300
1,100
24
49
100
175
248
,5.30
954
1,500
3,130
1,200
23
47
95
167
237
505
910
1,430
2,990
1.300
22
45
91
160
227
484
871
1,370
2,860
1,400
21
43
88
153
218
463
837
1,.320
2,7.50
1,500
20
42
85
148
210
448
806
1,270
2,650
1,600
19
40
82
143
202
432
779
1,230
2,560
1,700
19
39
79
138
196
419
753
1,190
2,470
1,800
18
38
77
134
190
406
731
1,150
2,400
1,900
18
37
74
130
184
394
709
1,120
2,330
2,000
17
36
72
126
179
383
690
1,090
2,270
Note: All table entries aie rounded to 3 significant digits,
*Tab)e capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside
diameter of the copper tubing products.
*Wlien this table is used to size the tubing upstream of a line pressure regulator, the pipe or tttbing down-
stream of the line pressure regulator shall be sized using a pressure drop no greater than 1 in. w.c.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
181
Table 12-18
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-18 Semi-Rigid Copper Tubing [NFPA Table 6.2(1)]
Gas:
Natural
Inlet Pressure:
5.0 psi
Pressure Drop:
3.5 psi
Specific Gravi^
0.60
Tube Size (in.)
K&L:
.V4
ys
Vi
%
Vt
1
V/i
VA
2
Noniiiial:
ACR:
H
H
■%
¥a
%
l'/4
1%
— ■
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:*
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
511
1,050
2,140
3,750
5,320
11,400
20,400
32,200
67,100
20
351
724
1.470
2,580
3,650
7.800
14,000
22,200
46,100
30
282
582
1,180
2,070
2,930
6,270
11,300
17,800
37,000
40
241
498
1,010
1,770
2.510
5,.360
9,660
15,200
31,700
50
214
441
898
1,570
2,230
4,750
8,560
13,.50O
28,100
60
194
400
813
1,420
2,020
4,310
7,7.50
12,200
25,500
70
178
368
748
1,310
1,860
3,960
7,130
11,200
2.3,400
80
166
342
696
1,220
1,730
3,690
6,640
10,500
21.800
90
156
321
653
1.140
1,620
3,460
6,2.30
9,820
20,400
100
147
303
617
1,080
1,530
3,270
5,880
9,270
19,300
125
130
269
547
955
1.360
2,900
5,210
8,220
17,100
150
118
243
495
866
1,230
2,620
4.720
7,450
15,500
175
109
224
456
796
1,130
2,410
4,350
6,850
14,300
200
101
208
424
741
1.050
2.250
4,040
6,370
13,.300
250
90
185
376
657
932
1,990
3,580
5,650
11,800
300
81
167
340
595
844
1,800
3,250
5,120
10.700
350
75
154
313
547
777
1,660
2,990
4,710
9,810
400
69
143
291
50<>
722
1,540
2.780
4,380
9,120
450
65
134
273
478
678
1,450
2,610
4,110
8,560
5(K)
62
127
258
451
640
1,370
2,460
3,880
8,090
550
58
121
245
429
608
1,300
2.340
3,690
7,680
600
56
115
234
409
.580
1,240
2,230
3,520
7.330
650
53
110
224
392
556
1,190
2,140
3,370
7,020
700
51
106
215
376
534
1,140
2,0.50
3,240
6,740
750
49
102
207
362
514
1,100
1,980
.3,120
6,490
800
48
98
200
350
497
1,060
1,910
3,010
6,270
850
46
93
194
339
481
1,0.30
1,8.50
2,910
6,070
900
45
92
188
328
466
1,000
1,790
2,820
5.880
950
43
90
182
319
452
967
1,740
2,740
5,710
1,000
42
87
177
310
440
940
1,690
2,670
5,560
1,100
40
83
169
295
418
893
1,610
2,530
5,280
1,200
38
79
161
281
399
8.52
1.5,30
2,420
5,040
1,300
37
76
154
269
382
816
1,470
2,320
4,820
1,400
35
73
148
259
.367
784
1,410
2,220
4,6.30
1,5(X»
34
70
143
249
.353
755
1,360
2,140
4,460
1,600
33
68
138
241
.341
729
1,310
2,070
4.310
1,700
32
65
133
233
330
705
1,270
2,000
4,170
1,800
31
63
129
226
320
684
1,230
1,940
4,040
1,900
30
62
125
219
311
664
1,200
1,890
3,930
2,000
29
60
122
213
802
646
1,160
1,830
3,820
Note: All table entries are rounded to 3 significant digitus.
"Table capadtTe,s are based on T>'pe K copper tubing inside diameter (shown), which has the smallest inside
diameter of the copper tubing products.
182
FUEL PIPING
Table 12-19 -Table 12-20
Table 12-19 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6.2(m)]
Gas:
Natural
Inlet Pressure:
Less than 2 psl
Pressarc Drop:
0.5 in. w.
c
Specific Gravity:
0.60
Tube Size (EHD)*
How Designation:
13
15
18
19
23
25
30
31
37
46
48
„
62
Length (ft)
Capacity in Cubic Feet of Gas per Mour
5
46
63
115
1S4
225
270
471
546
895
1,790
2,070
3,660
4,140
10
32
44
82
95
161
192
330
383
6.39
1,260
1,470
2,600
2,930
15
25
35
6(i
77
132
IS-
267
310
524
1,030
1.200
2,140
2,400
20
Ti
31
58
67
116
IS?
231
269
■156
888
1,050
1,850
2,080
25
19
27
52
60
104
122
206
240
409
793
9,36
1,660
1,860
30
18
25
47
53
96
112
188
218
374
723
856
1,320
1,700
40
15
21
41
47
83
97
162
188
,325
625
742
1„320
1,470
m
13
19
.S7
42
7.5
87
144
IBS
25)2
5.59
665
1,180
1,320
60
12
17
34
38
68
80
131
153
267
509
608
1,080
1,200
70
11
16
31
36
63
74
121
141
248
471
563
l.OflO
1.110
80
10
15
29
33
60
69
113
132
232
440
527
940
1,040
90
10
M
28
.92
.57
m
107
125
219
415
498
887
983
UK)
9
13
26
.30
54
62
toi
118
208
393
472
843
933
150
7
10
20
23
42
48
78
91
171
320
387
691
762
200
6
9
18
21
38
44
71
82
148
277
336
mi
661
250
5
8
le
19
34
39
63
74
1.33
247
301
338
."iOl
.«MH)
5
7
1.5
17
32
36
57
67
9.5
226
275
492
.540
*EHD = Equi^'alent Hydraulic Diameter, which h a measure of the relative hydraulic efficiency between
different luhing sizes. The greater the vahie of El ID, (;lie greater the gas capacity of tite lulling.
Notes;
(1) Table includes losses for four 90 degree bends and two end fitungs. Tubing nins with latter numbers of
bends and/or fittings shall be increased by an equivalent length of tubing to the following equadon: /, = 1 Sti,
where L is additional length (ft) of tubing and n is the number of additional fittings and/or bends.
(2) All table entries are rounded to 3 significant digits.
Table 1 2-20 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6,2(n)]
Gas:
Natural
Inlet Presisure:
Less than 2 psi
Pressure Drop:
3.0 in. W.C.
Specific Gravity:
0.60
Tube Size (EHD)*
Flow Designation:
1$
15
18
19
23 25
30
31
37
46 48
60
62
Length (ft)
Capadty^ in Cubic Feet of C
rasper Ho
ur
.5
120
160
277
327
529
649
1,180
1,370
2,140
4,430
5,010
8.800
10,100
10
S3
112
197
231
380
462
828
958
1,530
3.200
3,560
6.270
7,160
15
67
90
161
189
313
379
673
778
1,250
2„540
2,910
5,140
5,8.50
20
57
78
140
164
273
329
580
672
1,090
2,200
2.,530
4,460
5,070
25
51
69
125
147
245
295
,518
.599
978
1,960
2,270
4,000
4.540
30
46
63
115
134
225
270
471
546
895
1,790
2,070
3,660
4,140
40
39
54
100
116
196
234
407
471
778
1,550
1,800
3,180
3,590
50
35
48
89
104
176
210
363
421
698
1,380
1,610
2,8.50
3,210
60
32
44
82
95
161
192
330
383
639
1,260
1,470
2,600
2,930
70
29
41
76
88
1.50
178
306
.355
593
1,170
1,360
2,420
2,720
80
27
38
71
82
141
167
285
831
555
1,090
1,280
2,260
2,540
«)
26
36
67
77
133
157
268
311
524
1,030
1,200
2,140
2,400
100
24
34
63
73
126
149
254
295
498
974
1,140
2,030
2,280
150
19
27
52
60
104
122
206
240
409
793
9.36
1,660
1,860
200
17
23
45
52
91
106
178
207
355
686
812
1,440
1,610
2.50
15
21
40
46
82
95
1,59
184
319
613
728
1,290
1,440
300
13
19
37
42
75
87
144
168
234
559
665
1,180
1,320
*EHD = Equivalent Hydraulic Diameter, which is a tneasure of the relative liydraulic efficiency bettveen
different tubing sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
Notes:
(1) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of
l>ends and/or fittings shall be increased by an equivalent length of tubing to the following equation: /., = 1 .3 n,
where L is additional length (ft) of tubing and n is the number of additional fittings and/or bends.
(2) All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
183
Table 12-21 -Table 12-22
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-21 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6.2(o)]
Gas:
Natural
Inlet Pressure:
Less than 2 psi
Fressiwre Brop:
6.0 in. w.c.
Specific Gravity:
0.60
Tube Size (EHD)*
Flow Designation:
13
18
19
23
25
30
"
37
46
48
60
62
Lengrt>(ft)
Capacity in Cubic Feet of Gas per Hour
5
173
229
389
461
737
911
1.690
1.950
3,000
8,280
7,050
12.400
14,260
JO
120
160
277
327
529
649
1,180
1,370
• 2,140
4.430
5,010
8,800
10,100
15
9(i
130
227
267
436
532
960
1,110
1,760
3,610
4,i00
7,210
8,260
20
S$
112
197
231
380
462
828
958
1.330
3,120
3.360
6.270
7,160
25
74
99
I7fi
207
342
414
739
855
1,370
2,790
3,190
5,620
6,400
i«)
67
00
Mil
189
313
379
673
778
1.250
2,.540
2,910
.5.140
5,850
40
37
78
140
164
273
329
580
672
1,090
2,200
2,530
4,4(iO
5,070
r>o
31
69
123
147
243
295
518
599
978
1,960
2,270
4,000
4,540
so
46
63
115
134
225
270
471
546
895 ■
1,790
2,070
3,660
4,140
70
42
58
i06
124
209
250
435
505
830
1,660
1,920
3,.390
3,840
80
39
54
lOO
116
196
234
407
471
778
1,550
1,800
3,180
3,590
90
37
5!
9-1
109
!85
221
383
444
735
1,460
1.700
3.000
3,390
IQO '
35
48
89
104
176
210
363
421
698
1,380
1,610
2,8:'>0
3,210
150
28
39
73
83
143
172
294
342
373
1,130
1.320
2,340
2,630
200
24
34
63
73
126
149
254
295
498
974
1,140
2,030
2,280
250
21
30
57
66
114
134
226
263
447
870
1,020
1,820
2.040
300
19
27
52
60
104
122
206
240
409
793
956
1,660
1,860
"EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydrauHc efficiency txitwcen
different mbing sizes. The greater the value of EIID, the greater the gas capacity of the tubing.
Notes:
(1) Table includes losses for four 9()-<iegree tx;nds and two end fittings. Tubing runs with larger numbers of
bends and/or fittings .shall be increased by an equivalent length of tubing to the following equation: L= X .3n,
where £is addiliona! length (ft) of tubing and nis the number of additional fittings and/or bends.
(2) All table entries are rounded to ,? significant digits.
Table 12-22 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6.2(p)]
Gas:
Natural
Inlet Pressure:
2.0 psi
Pressure Drop:
1.0 psi
Spedftc Gravity!
0.60
Tube Size (EHB)*
How Designation:
13
15
18
19
23
25
30
31
37
46
48
60
62
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
270
353 '
587
700
1,100
1,370
2,590
2,990
4,510
9,600
10,700
18.600
21,600
25
166
220
374
444
709
876
1,620
1,870
2,890
6,040
6,780
11,900
1.3.700
30
151
200
342
405
650
801
1,480
1,700
2.640
5,510
6,200
10,900 .
12,500
40
129
172
297
351
567
696
1,270
1,470
2,300
4,760
5,380
9,440
10,900
50
115
154
266
314
510
624
1,140
1,310
2,060
4,260
4,820
8,470
9,720
75
03
124
218
257
420
512
922
1,070
1,690
3,470
3,950
6,940
7,940
80
89
120
211
249
407
496
892
1,030
1,640
3.360
3,820
6,730
7,690
100
79
107
189
222
.366
445
795
920
1,470
3,000
3,420
6.030
6,880
1.50
64
87
155
182
302
364
646
748
1,210
2,440
2,800
4,940
5,620
200
55
75
135
157
263
317
557
645
1.050
2,110
2,430
4,290
4,870
250
49
67
121
141
2.36
284
497
576
941
1,890
2,180
.3,850
4,360
300
44
61
110
129
217
260
453
525
862
1,720
1,990
3,520
3,980
400
38
52
96
111
189
225
390
453
749
1,490
1,730
3,060
3.450
500
34
46
86
](X)
170
202
348
404
552
1,330
1,550
2,740
S.OilO
*EHD = Equivalent Hydraulic Diameter, which is a measure of tlie relative hydraulic efRciency between
different tubing sizes. The greater the vahte of EHD, the greater the gas capacity of the mbing.
Notes:
(1) Table does not include effect of pressure drop across the Une regulator. Where regulator loss exceeds
% psi, do not usethis table. Ck)nsult with regulator manufacturer for pressure drops and capacity factors.
Pressure drops across a regulator may vary willi flow rate.
(2) CAUTION: C«»pacities sho^vn in table may exceed maximum capacit}' for a selected regulator. Consult
with regulator or tubing manufacturer for guidance.
{3) Table Includes losses lor fbur 90<legrec bends and two end fitdngs. Tubing nins with larger niunber of
bends and/or fittings shall be increased by an equivalent length of tubing according to the following equa-
tion: L ~ 1.3ft, where L is additional length (ft) of tubing and n is tlie number of additional fittings and/or
bends.
(4) All table entries are rounded to 3 .significant digits.
184
FUEL PIPING
Table 12-23 -Table 12-24
Table 12-23 Corrugated Stainless Steel Tubing (CSST)
[NEPA Table 6.2(q):
Gas:
Natural
Inlet Pressure:
5.0 psi
Pressure Drop:
3.5 psi
Specific Gravity:
0.60
Tube Size (EHD)*
Flow Designation:
13
IS
18
19
23
25
30
31
37
46
48
60
62
I>ength (ft)
Capacity in Cubic Feet of Gas per Hour
10
523
674
1,080
1,300
2.000
2,530
4,920
5,660
8,300
18,100
19,800
34,400
40,400
25
322
420
691
827
1,290
1,620
3,080
3,540
5,310
11,400
12,600
22,000
25,600
30
292
382
632
755
1,180
1,480
2,800
3,2,30
4,860
10,400
M,.500
20,100
23,400
40
251
329
549
654
1,030
1,280
2.420
2,790
4.230
8,970
10,000
17,400
20.200
50
223
293
492
586
926
1,150
2,160
2,490
3,790
8,020
8,930
15,6(H)
18,100
75
180
238
403
479
763
944
1,7.50
2,020
3,110
6,.530
7,320
12,800
14,800
80
174
230
391
463
740
915
1,690
1,960
3,020
6,320
7,090
12.400
14,300
100
154
205
350
415
665
820
1,510
1,740
2,710
5,650
6,350
11,100
12,800
150
124
166
287
339
548
672
1.230
1,420
2,220
4,600
5,200
9,130
10,500
200
107
143
249
294
478
584
1,060
1.220
1,930
3,980
4,510
7,930
9,090
250
95
128
223
263
430
524
945
1,090
1,730
3,,550
4,040
7,110
8,140
300
86
116
204
240
394
479
860
995
1,590
3,240
3.690
6,500
7,430
4(K)
74
100
177
208
343
416
742
858
1,380
2,800
3,210
5,650
6,440
500
66
89
159
186
309
373
662
766
1,040
2,500
2,870
5,060
5,760
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between
different tubing sizes. The greater the value of EHD, the greater the ga.s capacity of the tubing.
Notes;
(1) Table does not include effect of pressure drop across line regulator. Wliere regulator loss exceeds 1 psi,
do not use this table. Consult with regulator mamifactiirer for pressure drops and capacity factors. Pres.sure
drop across regulator may v-ary with the flow rate.
(2) C!IAUTION: Capacities shown in table may exceed maximum capacity of selected regulator. Consult with
tubing manufacturer for guidance.
(3) Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of
bends and/or fittings shall be increased by an equivalent length of tubing to the following equation: L = I. 'in,
where /. is additional length (ft) of tubing and n is the number of additional fittings and/or bends.
(4) All table entries are rounded to 3 significant tligits.
lable 12-24 Folyethylene Flastic Tipe [NFPA Table 6.2(r)]
Gas:
Natural
Inlet Pressure:
I.£ss than 2 psi
Pressure Drop:
0.3 in. w.c.
Speciflc Gravity:
0.60
Pipe Size (in.)
Nominal OD:
W
»/4
I
VA
1V4
2
Designation:
SDR 9.83
SDR 11.0
SDR 11.00
SDR 10.00
SDR 11.00
SDR 11.00
Actual ID:
0.660
0.860
1.077
1.328
1.554
1.943
Lei^ltfa (ft)
Capacity in Cubic Feet of Gas per Hour
10
153
,305
551
955
1,440
2,590
20
105
210
379
656
991
1,780
30
84
169
.%4
.527
796
1,4.30
40
72
144
260
451
681
1,220
50
64
128
231
400
604
1,080
60
58
116
209
362
547
983
70
53
107
192
333
503
904
80
50
99
179
310
468
841
90
46
93
168
291
439
789
100
44
88
159
275
415
745
125
39
78
141
243
368
661
150
35
71
127
221
333
.598
175
32
65
117
203
306
551
200
30
60
109
189
285
512
250
27
54
97
167
253
4.54
300
24
48
88
152
229
411
350
22
45
81
139
211
378
400
21
42
75
130
196
352
450
19
39
70
122
184
330
18
37
66
115
174
312
Note: All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
185
Table 12-25
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-25 Polyethylene Plastic Pipe [NFPA Table 6.2(s)]
Gas:
Natural
Inlet Pressure:
Less than 2 psd
Pressure Drop:
0.5 in. w.c.
Specific Gravity:
0.60
Pipe Size (in.)
Nominal OD:
V4
V4
1
VA
IM.
2
Designation:
SDR 9.33
SDR 1 1.0
SDR 11.00
SDR 10.00
SDR 11.00
SDR 11.00
Actual ID:
0.660
0.860
1.077
1.328
1.554
1.943
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
201
403
726
1.260
1,900
3,410
20
138
277
499
865
1,310
2,350
30
111
222
401
695
1,050
1,880
40
95
190
343
594
898
1,610
50
84
169
304
527
796
1,430
60
76
153
276
477
721
1,300
70
70
140
254
439
663
1,190
80
65
131
236
409
617
1,110
90
61
123
221
383
579
1,040
100
58
116
209
362
547
983
125
51
103
185
321
485
871
150
46
93
lf)8
291
439
789
175
43
86
154
268
404
726
200
40
80
144
249
376
675
250
35
71
127
221
333
598
300
32
64
115
200
302
542
350
29
59
106
184
278
499
400
27
55
m
171
258
464
450
26
51
93
160
242
435
500
24
48
88
152
229
411
Note: All table entries are rounded to 3 significant digits.
186
FUEL PIPING
Table 12-26
Table 12-26 Polyethylene Plastic Pipe [NFPA Table 6.2(t)]
Gas:
Natural
Inlet Pressure:
2.0 psi
Pressure Drop:
I.Opsi
Specific Graivi^
0.60
Pipe Size (in.)
Nominal OD:
V4
%
1
VA
IW
2
Designation:
SDR 9.33
SDR 11.0
SDR 11.00
SDR 10.00
SDR 11.00
SDR 11.00
Actual ID:
0.660
0.860
1.077
1.328
1.554
1.943
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
1.860
3,720
6,710
11,600
17,600
31,600
20
1,280
2,560
4,610
7,990
12,100
21,700
30
1,030
2.050
3,710
6,420
9,690
17,400
40
878
1,760
3,170
5,490
8,300
14,900
30
778
1,560
2,810
4,870
7,350
13,200
60
705
1,410
2,550
4,410
6,660
J2,000
70
649
1,300
2.340
4,060
6,130
11,000
80
603
1,210
2,180
3,780
5,700
10,200
90
566
1,130
2,050
3,540
5,350
9,610
100
535
1,070
1,930
3,350
5,050
9,080
125
474
949
1,710
2,970
4,480
8.050
150
429
860
1,550
2,690
4,060
7,290
175
395
791
1,430
2,470
3,730
6,710
200
368
736
1,330
2,300
3,470
6,240
250
326
652
1,180
2,040
3,080
5,530
300
295
591
1,070
1,850
2,790
5,010
350
272
544
981
1,700
2,570
4,610
400
253
506
913
1,580
2,390
4,290
450
237
475
856
1,480
2,240
4.020
500
224
448
809
1,400
2,120
3,800
550
213
426
768
1,330
2,010
3,610
600
203
406
733
1.270
1,920
3,440
650
194
889
702
1,220
1,840
3,300
700
187
374
674
1,170
1,760
3,170
750
180
360
649
1,130
1,700
3,050
800
174
348
627
1,090
1,640
2,9.50
850
168
336
607
1,050
1,590
2,850
900
163
326
588
1,020
1.540
2,770
950
1.58
317
572
990
1,500
2,690
1.000
154
308
556
963
1,450
2,610
1,100
146
293
528
915
1,380
2,480
1.200
139
279
504
873
1,320
2,370
1,300
134
267
482
836
1,260
2.270
1,400
128
257
463
803
1,210
2,180
1,500
124
247
446
773
1,170
2,100
1,600
119
239
431
747
1,130
2,030
1,700
115
231
417
723
1.090
1,960
1,800
112
224
404
701
1.060
1,900
1,900
109
218
393
680
1,030
1,850
2,000
106
212
382
662
1.000
1,800
Note: All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA-
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
187
Table 12-27 -Table 12-28
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-27 Polyethylene Plastic Tubing
[NFPA Table 6.2(u)]
Gas:
Natural
Inlet Pressure:
Less than 2.0 psi
Pressure Drop:
0.3 in. w.c.
Specific Gravity:
0.60
Plastic Tubing Size (CTS)* (in.)
Nominal OD:
1/2
%
Designation:
SDR 7.00
SDR 11.00
Actual ID:
0.445
0.927
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
54
372
20
37
256
30
30
205
40
26
176
50
23
156
60
21
141
70
19
130
80
18
121
90
17
113
100
16
107
125
14
95
150
13
86
175
12
79
200
11
74
226
10
69
250
NA
65
275
NA
62
300
NA
59
350
NA
54
400
NA
51
450
NA
47
500
NA
45
Table 12-28 Polyethylene Plastic Tubmg
[NFPA Table 6.2(v)]
Gas:
Natural
Inlet Pressure:
IjesH than 2.0 psi
Pressure Drop:
0.5 in. w.c.
Specific Gravity:
0.60
Plastic Tubing Size (CTS)* (in.)
Nominal OD:
Vt
Va
Designation:
SDR 7.00
SDR 11.00
Actual ID:
0.445
0.927
Length (ft)
Capacity in Cubic Feet of Gas per Hour
10
72
490
20
49
337
30
39
271
40
34
232
50
30
205
60
27
186
70
25
171
80
23
159
90
22
149
100
21
141
125
18
125
150
17
113
175
15
104
200
14
97
225
13
91
250
12
86
275
11
82
300
11
78
350
10
72
400
NA
67
450
NA
63
500
NA
59
*CTS = Copper tube size.
NA means a flow of less than 10 cfti.
Note: All table entries are rounded to 3 significant digits.
*CTS = Ckjpper tube size.
NA means a flow of less than 10 cfli.
Note: All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
188
FUEL PIPING
Table 12-29
Table 12-29 Schedule 40 Metallic Pipe [NFPA Table 6.3(a)]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Gas:
Inlet Pressure:
Pressure Drop:
Specific Gravity:
Undiluted Propane
10.0 psi
1.0 psi
1.50
SPKCIAl. l.'SK: Pipe Siriiit; Belwet-n iMt.sl Stajre (High Pressuro Kcgtilafor) and Second Slu^c (Low Pressure Rff;ulatt>r)
Pipe Size (in.)
Nominal
1
Inside:
•A
%
1
VA
VA
2
m
.3
4
Actual:
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
Length (ft)
Capacity in Tliousands of Btu
per Hour
10
3,320
6,950
13,100
26,900
40,.300
77,600
124,000
219,000
446,000
20
2,280
4,780
9,000
18,500
27,700
53,300
85,000
150,000
306,000
30
1,830
3,840
7,220
14,8(K)
22,200
42,800
68,200
121,(K)0
246,000
40
1,570
3,280
6,180
. 12,700
19,000
36,600
58,400
103,000
211,000
50
1,390
2,910
5,480
11,300
16,900 .
32,.5O0
51,700
91,500
187.000
60
1,260
2,640
4,970
10,200
15,300
29,400
46,900
82,900
169.000
70
1,160
2,430
4.570
9,380
14,100
27,100
43,100
76,300
156,000
80
1,080
2,260
4,250
8,730
13.100
. 25,200
40,100
70,900
145.000
90
1,010
2,120
3,990
8,190
12,300
23,600
37,700
66,600
136,000
100
956
2,000
3.770
7,730
11,600
22,300
35,600
62,900
128,000
125
848
1,770
,3,340
6,850
10,300
19,8(W
31,500
55,700
114.000
150
768
1,610
3,020
6,210
9,300
17,900
28,600
50,500
103,000
175
706
1.480
2,780
5,710
8,560
16,500
26,300
46,500
94,700
200
657
1,370
2,590
5,320
7,960
15,300
24,400
43,200
88,100
250
582
1,220
2,290
4,710
7,060
13,600
21,700
3f!,.300
78,100
m)
528
1,100
2,080
4,270
6,400
12,.3(K)
19,600
34,700
70,800
350
486
1,020
1,910
3,930
5,880
11, .300
18,100
31,900
65,100
400
452
945
1,780
3,650
5,470
10,5(K)
16,800
29,700
60,600
450
424
886
1,670
8,430
.5,140
9,890
15,800
27,900
56,800
500
400
837
1,580
3,240
4,850
9,340
14,900
26,300
53,700
550
380
795
1,500
3,070
4,610
8,870
14.100
25,000
51,000
600
363
759
1,430
2,930
4,400
8,460
13,500
23,900
48.600
650
347
726
1,370
2,810
4,210
8,110
12.900
22,800
46,600
700
334
698
1.310
2,700
4,040
7,790
12,400
21,900
44,800
730
321
672
1,270
2,600
3,900
7,500
12.000
21,100
43,100
800
310
649
1.220
2,510
3,760
7,240
11,500
20,400
41,600
850
.300
628
1,180
2,430
3,640
7,010
11,200
19,800
40.300
900
291
609
1.150 ■
2,3t>0
3,530
6,800
10,800
19,200
39,100
950
283
.592
1,110
2,290
3,4.30
6.6(K)
10,500
18,600
37.900
1,000
275
575
1,080
2,230
3,330
6,420
10,200
18,100
36,900
1,100
261
546
1,030
2,110
3,170
6,100
9,720
17,200
35,000
1>200
249
521
982
2.020
3,020
5,820
9,270
16,400
33,400
1,300
239
4M
940
1,930
2,890
5,570
8,880
15,700
32,000
1,400
229
480
903
1,8.50
2,780
5,350
8,530
15,100
,30,800
1,500
221
462
870
1,790
2,680
5,160
8,220
14.500
29,600
1,600
213
446
840
1,730
2,590
4,980
7,940
14,000
28,600
1.700
206
432
813
1.670
2,500
4,820
7,680
13,600
27,700
1,800
200
419
789
1.620
2,430
4,670
7,450
13,200
26,900
1,900
194
407
766
1,570
2,360
4,540
7,230
12,800
26,100
2,000
189
395
745
1,530
2,290
4,410
7,030
12,400
25,400
Note: All table entries are rounded to 3 significant digits.
189
Table 12-30
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-30 Schedule 40 Metallic Pipe [NFPA Table 6.3(b)]
Inlet Pressure:
Pressure Drop:
Specific Gravity:
Undiluted Propane
10.0 psi
3.0 psi
SPECIAL USK: Pipe Siring Between First Stasjc fHigh Pressure Kcgulator) and Second Staffc (I/>w Pressure Rej^ator)
Pipe Size (in.)
Nominal
In.<;ide:
-^
»/4
1
VA
m
2
m
3
4
Actual:
0.622
0.824
1.049
1.380
i.610
2.067
2.469
3.068
4.026
Ijength (ft)
Capacity in
Thousands of Btu per Hour
10
5,890
12,300
23.200
47,600
71, .300
1,37.000
219,000
387,000
789,000
20
4,050
8,460
15,900
,32,700
49,000
94,400
150,000
266,000
543,000
30
.3,250
6,790
12,800
26,300
39,400
75,800
121,000
214,000
436,000
40
2,780
5,810
11,000
22,500
33,700
64,900
103,000
183,000
373,000
50
2,460
.5,150
9,710
19,900
29,900
.57,500
91,600
162,000
330,000
60
2,230
4,670
8,790
18,100
27,100
52,1(»
83,000
147,000
299,000
70
2,0.50
4,300
8,0<H)
16,600
24,900
47,900
76,400
135,000
275,<XK)
80
1,910
4,000
7,530
15,500
23,200
44,600
71,100
126,000
256,000
90
1,790
3,750
7,060
14,500
21,700
41,800
66,700
118,000
240,000
100
1,690
3,540
6,670
13,700
20,.500
39,500
63,000
111,000
227,000
125
1,500
3,140
5,910
12,100
18,200
35,(K)0
55,800
98.700
201,000
150
1,360
2,840
5,360
11,000
16,500
31,700
50.600
89,400
182,000
175
1,250
2,620
4,930
10,100
15,200
29,200
46,500
82,300
167,800
200
1,160
2,430
4,580
9,410
14,100
27,200
43,300
76,500
156,100
250
1,030
2,160
4,060
S.S'IO
12,500
24,100
38,400
67,800
138,400
.%0
9.35
1,950
3,680
7,560
11,300
21,800
.34,800
6],.500
125,400
.^50
860
1,800
3,.3go
6,950
10,400
20,100
.32,000
.56,.500
]1.5,.300
400
800
1,670
3,1.50
6,470
9,690
18,700
29,800
,52,600
I07,.300
450
751
1,570
2,960
6,070
9,090
17,500
27,900
49,400
100,700
500
709
1,480
2.790
5,730
8,590
16,500
26,400
46,600
95,100
.550
67.3
1,410
2,650
5.450
8,160
15,700
25,000
44,300
90,300
<»()
642
1,.340
2,5.30
5,200
7,780
15,0(X)
23,900
42,200
86,200
650
615
1,290
2,420
4,980
7,450
14,400
22,900
40,.500
82,.500
700
591
1,240
2,330
4,780
7,160
13,800
22,000
38,900
79,300
750
569
1,190
2,240
4,600
6,900
13,300
21,200
37,400
76,400
800
550
1,150
2,170
4,450
6,660
12,800
20,500
36,200
73,700
850
532
1,110
2,100
4,300
6,450
12,400
19,800
35,000
71, -m)
900
516
1,080
2,030
4,170
6,250
12,000
19,200
33,900
69,200
950
501
1,050
1,970
4,050
6,070
11,700
18,600
32.900
67,200
1,000
■ 487
1,020
1,920
3,940
5,900
11,400
18,100
32,000
65,400
1,100
46.3
968
1,820
3,740
5,610
10,800
17,200
-30,400
62,100
1,200
442
923
1,740
3,570
5,3.50
10,300
16,400
29,000
59,200
1,300
423
884
1,670
3,420
5,120
9.870
15,700
27,800
.56,700
1,400
406
849
1,600
3,280
4,920
9,480
15,100
26,700
54,500
1,500
391
818
1,540
3,160
4,740
9,130
14,600
25,700
52,.500
1/jOO
.378
790
1,490
3,060
4,580
8,820
14,100
24,800
50,700
1,700
.366
765
1,440
2,9(»
4,430
8,530
13.600
24,000
49,000
1,800
355
741
1,400
2,870
4,300
8,270
13,200
2.3,.300
47,600
1,900
.344
720
1,360
2,780
4,170
8,040
12,800
22,600
46,200
2,000
335
700
1,320
2,710
4,060
7,820
12,500
22,000
44,900
Note; All table entries are rounded to 3 significant digits.
190
FUEL PIPING
Table 12-31
Table 12-31 Schedule 40 Metallic Pipe [NFPA Table 6.3(c)]
Gas:
Undiluted Prop
ane
Inlet Pressure:
2.0 psi
Pressure Drop;
1.0 psi
Spedfic Gravity:
1.50
Pipe Size (in.)
Nomina!:
V4
%
1
VA
m
2
214
3
4
Actual ID:
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
Length (ft)
Capacity in
Thousands of Btu per Hour
10
2,680
5,590
10,500
21.600
32,400
62,400
99,500
176.000
359,000
20
1,840
3,850
7.240
14,900
22,300
42,900
68,400
121,000
247,000
30
1,480
3,090
5,820
11,<K»0
17,9(K)
34,.500
54,900
97,100
198,000
40
1,260
2,640
4,980
10,200
15,300
29,500
47,000
83,100
170,000
50
1,120
2.340
4,410
9,060
13,600
26.100
41,700
73,700
150,000
60
1,010
2,120
4,000
8,210
12,300
23,700
37,7(K)
66,700
136,000
70
934
1,950
3,680
7,550
11,300
21.800
34,700
61,400
125,000
80
869
1,820
3,420
7,020
10,.500
20,300
32,300
.57,100
116,000
90
815
1,700
3,210
6,590
9,880
19,000
30,300
33,600
109,000
100
770
1,610
3,030
6,230
9,330
18,000
28,600
50,600
103,(M)0
125
682
1,430
2,690
5,520
8,270
15,900
25,400
44,900
91,500
!50
618
1,290
2,440
5.000
7,490
14,400
23,000
40,700
82,900
175
569
1,190
2,240
4,600
6,890
13,300
21,200
37,400
76,.30O
200
52<)
1,110
2,080
4,280
6,410
12,300
19,700
,34,800
71,0(K)
250
469
981
1,850
3,790
5,680
10,900
17,400
30,800
62,900
3(K)
425
889
1,670
3,440
5,150
9,920
15,8(K»
27,900
57.000
350
391
817
1.540
3,160
4,740
9,120
I4,5(K)
25,700
52,400
400
364
760
1,430
2,940
4.410
8,490
13,500
23,900
48,800
'450
341
714
1,340
2,760
4,130
7,960
12,700
22,400
45,800
500
322
674
1,270
2,610
3,910
7.520
12,000
21,200
43,200
550
306
640
1,210
2,480
3,710
7,140
ii,4(K>
20,100
41,100
600
292
611
1,130
2,360
3,540
6,820
10,900
19,200
39,200
650
280
585
1,100
2,260
3,390
6,530
10.400
18,400
37,500
700
269
562
1,060
2,170
3,260
6.270
9,990
17,700
36,000
750
259
541
1,020
2,090
3,140
6,040
9,6.30
17,000
34,700
800
250
523
985
2,020
3,030
5.830
9,300
16,400
33,500
850
242
506
933
1,960
2.930
5,640
9,000
15,900
32,400
900
235
490
924
1,900
2,840
. 5,470
8.720
15,400
31, .500
950
228
476
897
1,840
2,7«)
5,310
8,470
15,000
30,500
1,000
222
463
873
1,790
2,680
5,170
8,240
14,600
29,700
1.100
210
440
829
1,700
2,550
4,910
7,830
13,800
28,200
1,200
201
420
791
1,620
2,4.30
4,mo
7,470
13,200
26,900
1,300
192
402
7i>7
1,550
2,.330
4,490
7,1.50
12,600
25,8{H)
1,400
185
386
727
1,490
2,240
4,310
6,870
12,100
24,800
1300
178
372
701
1,440
2,160
4,150
6,620
11,700
23,900
1,600
172
359
677
1,.390
2,080
4,010
6,390
11,.300
23,000
1,700
166
348
655
1,340
2,010
3,880
6,180
10,900
22,300
1,8(X>
161
337
635
1.300
1,950
3,760
6,000
10,600
21,600
1,900
157
327
617
1,270
1,900
3.650
5.820
10,300
21,000
2,000
152
318
600
1,230
1,840
3,5,50
5,660
10,000
20,400
Note: All table entries are rotinded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
191
Table 12-32
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-32 Schedule 40 Metallic Pipe [nfpa Table 6.3(d)]
Gas:
UndOutcd Propane
Inlet Pressure:
11.0in.w.c.
Pressure Drop:
0.5 in. w.c.
Specific Gravity:
1.50
SPECL'VL L'5E: Pipe Siung Between Single or SecoLid Stage iLow PivisNiire Regulator) and Appliance
Pipe Size (in.)
Nominal
Inside:
V4
%
I
I'A
154
2
254
3
4
Actual:
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
Lei^ (ft)
Capacity in
Thousands of Blu per Hour
10
291
608
1,150
2,350
3,520
6,790
10,800
19,100
39,000
20
200
418
787
1,620
2,420
4,660
7,430
13,100
26,800
30
160
336
632
1,300
1,940
3,750
5,970
10,600
21,500
40
137
287
541
1.110
1,660
3,210
5,110
9,030
18,400
50
122
255
480
985
1,480
2,840
4,530
8,000
16,300
60
110
231
434
892
1,340
2,570
4,100
7,250
14,800
80
101
212
400
821
1,230
2,370
3,770
6,670
13,600
100
94
197
372
763
1,140
2,200
3,510
6,210
12,700
125
89
185
349
716
1,070
2,070
3,290
5,820
11,900
150
84
175
330
677
1,010
1,9.50
3,110
5,5(W
11,200
175
74
155
292
600
899
1,730
2.760
4,880
9,950
200
67
140
265
543
814
1,570
2,500
4,420
9,010
2i30
62
129
243
.500
749
1,440
2.300
4.060
8,290
300
58
120
227
465
697
1,340
2,140
3,780
7,710
350
51
107
201
412
618
1,190
1,900
3..350
6,840
400
46
97
182
373
560
1,080
1,720
3,040
6,190
450
42
89
167
344
515
991
1,580
2,790
5,700
500
40
83
156
320
479
922
1,470
2,600
5,300
550
37
78
146
300
449
865
1,380
2,-440
4,970
600
35
73
138
283
424
817
1,300
2,300
4,700
650
33
70
131
269
403
776
1,240
2,190 .
4,460
700
32 ,
66
125
257
386
741
1,180
2,090
4,260
750
30
64
120
246
368
709
1,130
2,000
4,080
800
29
61
115
236
354
681
1,090
1,920
3,920
850
28
59
Ml
227
341
656
1,050
1,850
3,770
?KK)
27
.57
107
220
329
634
1,010
1,790
3,640
950
26
55
104
213
319
613
978
1,730
3,530
1,0{K>
25
53
100
206
309
595
948
1,680
3,420
1,100
25
52
97
200
300
578
921
1,630
3,320
1,200
24
50
95
195
292
562
895
1,580
3,230
1,300
23
48
90
185
277
534
850
1,500
3,070
1,400
22
46
86
176
264
509
811
1,430
2,930
1,5TO
21
44
82
169
253
487
777
1,370
2,800
1,600
20
42
79
162
243
468
746
1,320
2,690
1,700
19
40
76
156
234
451
719
1,270
2,590
1,800
19
39
74
151
226
436
694
1,230
2,.500
1,900
18
38
71
146
219
422
672
1,190
2,420
2,000
18
37
69
142
212
409
652
1,150
2,350
Note: All table entries are rounded to ^ significant digits.
192
FUEL PIPING
Table 12-33
Table 12-33 Semi-Rigid Copper Tubing [NFPA Table 6.3(e)]
NFPA
NFPA
NFPA
NFPA
NFPA
.NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Gas:
Inlet Pressure:
Pressure Drop:
Specific Gravily;
Undiluted Propane
lO.Opsi
1.0 psi
SPKCIAI. CSE: Tube Sizing Benvocn First Stage (High Pressure Repihitor) and Second Stage (Low Pres&ure Rcgul&tor)
Tube Size (in.)
K&L:
Vt
%
V4
%
V*
1
VA
VA
2
Nominal:
ACR:
%
V4
%
%
%
m
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.S75
1.625
2.125
Inside:"
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Length (ft)
Capacity in Thousands of Btu per Hour
10
513
1,060
2,150
3,760
5,330
11.400
20,500
32,300
67,400
20
352
727
1,480
2,580
3,670
7,830
14,100
22,200
46,300
30
283
584
1,190
2,080
2,940
6,290
11,300
17,900
37.200
40
242
500
1,020
1.7S0
2.520
5,380
9,690
15.300
31,800
50
215
443
901
1,570
2,230
4,770
8,590
13,500
28.200
60
194
401
816
1,430
2,020
4,320
7,780
12,300
25,600
70
179
369
751
1.310
1,860
3,980
7,160
11,300
23,500
80
166
343
699
1,220
1,730
3,700
6,660
10,500
21,900
90
156
322
655
1,150
1,630
3,470
6,250
9.850
20,500
100
147
304
619
1,080
1,540
3,280
5,900
9.310
19,400
125
131
270
549
959
1,360
2,910
5,230
8,2.50
17,200
150
118
244
497
869
1,230
2,630
4,740
7,470
15,600
175
109
225
■ 457
799
1,130
2.420
4,360
6,880
14,.300
200
101
209
426
744
1,060
2,250
4,060
6,400
13,300
250
90
185
377
659
935
2,000
3,600
6,670
11,800
300
81
168
342
597
847
1,810
3,260
5,140
10,700
350
75
155
314
549
779
1,660
3,000
4,730
9,840
400
70
144
292
511
725
1,550
2,790
4,400
9,160
450
65
135
274
480
680
1,450
2.620
4,130
8,590
500
62
127
259
453
643
1,370
2,470
3,900
8,120
550
59
121
246
430
610
1,300
2,330
3,700
7,710
600
56
115
235
410
582
1,240
2,240
3,530
7,350
650
54
111
225
393
558
1,190
2,140
3,380
7,040
700
51
106
216
378
536
1,140
2,060
3,250
6,770
750
50
102
208
364
516
1.100
1,980
3,130
6,520
800
48
99
201
351
498
1,060
1,920
3,020
6.290
850
46
96
195
340
482
1,030
1,850
2,920
6,090
900
45
93
189
330
468
1,000
1,800
2,840
5.910
950
44
90
183
320
454
970
1,750
2,750
5,730
}xm
42
88
178
311
442
944
1,700
2,680
5,580
1,100
40
83
169
296
420
896
1,610
2,540
5,300
1,200
38
79
161
282
400
855
1,540
2,430
5,050
1,3<K)
37
76
155
270
383
819
1,470
2,320
4,840
1,400
35
73
148
260
368
787
1,420
2,230
4,650
1,500
34
70
143
250
355
758
1,360
2,150
4,480
1,«K)
33
68
138
241
343
732
1,320
2,080
4.330
1,700
32
66
134
234
331
708
1,270
2,010
4,190
1,800
31
64
130
227
321
687
1,240
1,960
4,060
1,900
30
62
126
220
312
667
1.200
1,890
3,940
2,000
29
60
122
214
304
648
1,170
1,840
3,830
Note: All table entries are rounded to 3 significant digits.
*TabIe capacities are based on Type K copper tubing inside diiuiieter (shown) , which has the smallest inside
diameter of the copper tubing products.
193
Table 12-34
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-34 Semi-Rigid Copper Tubing [NFPA Table 6.3(f)]
Gas:
Undiluted Propane
Infet Pressure:
11.0in.%v.c.
Pressure Drop:
0.5 in. w.c.
Spedfic Gravity:
1.50
.SPr.CIAI. USK: Tube Siting livnt-ccn Single or Second Stage (Low Pressuiv Kcgulator) and Appliance
Tube Size (in.)
Nominal:
K&L:
'/*
%
V4
Vs
V*
1
VA
114
2
ACaR:
%
»/4
%
%
%
1V4
1%
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:'
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1.481
1.959
Lengtli (ft)
Capacity in Thousands of Btu per Hour
10
45
93
188
329
467
997
1,800
2,830
5,890
20
31
64
129
226
321
685
1,230
1,9.50
4,050
30
25
51
104
182
258
550
991
1,560
3,250
40
21
44
89
155
220
, 471
848
1,340
2,780
50
19
39
79
138
195
417
752
1,180
2,470
60
17
35
71
125
177
378
681
1,070
2,240
70
16
32
66
115
163
.348
626
988
2,060
80
15
30
61
107
152
324
583
919
1,910
90
14
28
57
100
142
.304
547
862
1.800
100
13
27
54
95
134
287
517
814
1,700
125
11
24
48
84
119
254
458
722
1.500
150
10
21
44
76
108
230
415
654
1,360
175
NA
20
40
70
99
212
382
602
1,250
200
NA
18
37
65
92
197
355
560
1,170
250
NA
16
33
58
82
175
315
496
1,030
300
NA
15
30
52
74
158
285
449
936
350
NA
14
28
48
68
146
262
414
861
400
NA
13
26
45
63
136
244
385
801
450
NA
12
24
42
60
127
229
361
752
500
NA
11
23
40
56
120
216
341
710
550
NA
11
22
38
53
114
205
324
674
600
NA
10
21
36
51
109
196
309
6-43
650
NA.
NA
20
34
49
104
188
296
. 616
700
NA
NA
19
33
47
100
180
284
592
750
NA
NA
18
32
45
96
174
274
570
800
NA
NA
18
31
44
93
168
264
551
850
NA
NA
17
30
42
90
162
256
. 533
900
NA
NA
17
29
41
87
157
248
517
950
NA
.NA
16
28
40
85
153
241
502
1,000
NA
NA
16
27
39
83
149
234
488
1,100
NA
NA
15
26
37
78
141
223
464
1,200
NA
NA
14
25
35
75
135
212
442
1,300
NA
NA
14
24
34
72
129
203
423
1,400
NA
NA
13
23
32
69
124
195
407
1,500
NA
NA
1$
22
31
66
119
188
392
1,600
NA
NA
12
21
30
64
115
182
378
1,700
NA
NA
12
20
29
62
112
176
366
1,800
NA
NA
11
20
28
60
108
170
355
1,900
NA
NA
11
19
27
58
105
166
845
2,000
NA
NA
11
19
27
57
102
161
335
NA means a flow of less than 10,000 Btu/hr.
Note: All table entries are rounded to S .significant digits.
"Table capacities are based on Type K copper tubing in.side diameter (.shown), which has the smallest inside
diameter of the copper tubing products.
194
FUEL PIPING
Table 12-35
Table 12-35 Semi-Rigid Copper Tubing [NFPA Table 6.3(g)]
Gas:
Undiluted Propane
Inlet Pressure:
2.0 psi
Pj^ssure Drop:
1.0 psi
Specific Gravity:
1.50
Tube Size (in.)
Nominal:
K&L:
Vt
n
'A
%
%
1
VA
m
2
ACR:
%
V4
%
»/»
%
IH
m
—
—
Outside:
0.375
0.500
0.625
0.750
0.875
1.125
1.375
1.625
2.125
Inside:'
0.305
0.402
0.527
0.652
0.745
0.995
1.245
1,481
1.959
Length (ft)
Capacity in Thousands of Btu per Hour
10
413
852
1,730
3,030
4,300
9,170
16,500
26,000
54,200
20
284
585
1,190
2.O80
2,950
6,310
11,400
17,900
37,300
30
228
470
956
1,670
2,370
5,060
9,120
14,400
29,900
40
195
402
818
1,430
2,030
4,330
7,800
12,300
25,600
50
173
356
725
1,270
l.SOt)
3,840
6,920
10,900
22,700
60
157
323
657
1,150
1,630
3,480
6,270
9,880
20,()00
70
144
297
605
1,060
1.500
3,200
5,760
9,090
18.900
m
134
276
562
983
• 1,390
2,980
5,360
8.450
17,600
90
126
259
528
922
1,310
2,790
5.030
7,930
16,500
100
119
245
498
871
1,240
2.640
4,750
7,490
15,600
J25
105
217
442
772
1,100
2,340
4,210
6,640
13,800
150
95
197
400
700
992
2,120
3,820
6,020
12,500
175
88
181
368
644
913
1,950
3,510
5,540
11. .500
200
82
168
343
599
849
1,810
3,270
5,150
10,700
250
72
149
304
531
753
1,610
2,900
4,560
9,510
300
66
135
275
481
682
1,460
2,620
4,140
8,610
350
60
124
25S
442
628
1,340
2,410
3,800
7,920
400
56
116
235
41]
584
1,250
2,250
3,540
7,370
450
53
109
221
386
548
1,170
2,110
3,320
6,920
500
50
103
209
365
517
1,110
1,990
3,140
6,530
550
47
97
198
346
491
1,050
1,890
2,980
6.210
600
45
93
189
330
469
1,000
1,800
2,840
5,920
650
43
89
181
316
449
959
1,730
2,720
5,670
700
41
86
174
304
431
921
1,660
2,620
5,450
750
40
82
168
293
415
888
1,600
2,520
5,250
800
39
80
162
283
401
857
1,540
2,430
5,070
850
37
77
157
274
388
829
1,490
2,350
4,900
900
36
75
152
265
376
804
1,450
2,280
4,750
950
35
72
147
258
366
781
1,410
2.220
4,620
1,000
34
71
143
251
356
760
1,370
2,160
4,490
1,100
32
67
136
238
338
721
1,300
2,050
4,270
1,200
31
64
130
227
322
688
1,240
1,950
4,070
1,300
30
61
124
217
309
659
1,190
1,870
3,900
1,400
28
59
120
209
296
633
1,140
1,800
3,740
1,500
27
57
115
201
286
610
1,100
1,730
3,610
1,600
26
55
111
194
276
589
1,060
1,670
3.480
1,700
26
53
108
188
267
570
1,030
1,620
3,370
1,800
25
51
104
182
259
553
1,000
1,570
3,270
1,900
24
30
101
177
251
537
966
1,520
3,170
2,000
23
48
99
172
244
522
940
1.480
3,090
Note: All table entries are rounded to 3 significant digits.
*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside
diameter of the copper tubing products.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
195
Table 12-36 -Table 12-37
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-36 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6.3(h)]
Gas:
Undiluted Propane
Inlet Pressure:
I1.0in.w.c.
Pressure Drop:
0.5 in. w.c.
Specific Gravity:
1.50
TubeS«e<EHD)*
Flow Designation:
13
15
18
19
23
25
30
31
37
46
48
60
62
Length (ft)
Capacity in Thousands of Btu per Hour
5
72
99
181
211
355
426
744
863
1,420
2,830
.3,270
5.780
6,.550
10
50
69
129
150
254
303
521
605
971
1,9^W
2,320
4,110
4,6^10
!,5
39
55
104
121
208
248
422
490
775
1,620
1,900
3,370
3.790
20
34
49
91
106
183
216
365
425
661
1,400
1,650
2,930
3.290
25
30
42
82
94
164
192
325
379
583
1.2,50
1,480
2,6.30
2,940
30
28
39
74
87
151
177
297
344
528
1,140
1,350
2.400
2,680
40
23
33
64
74
131
153
256
297
449
988
1.170
2,090
2,3.30
50
20
30
58
66
118
137
227
265
397
884
1,050
1,870
2,080
60
19
26
53
m
107
126
207
241
359
805
961
1,710
1,900
70
17
25
49
57
99
117
19!
222
330
745
890
1,590
1,760
80
1.5
23
■15
52
94
109
178
208
307
696
833
1,490
1,6,50
ao
15
22
44
50
90
102
169
197
286
656
787
1,400
1.530
100
14
20
41
47
85
98
159
186
270
621
746
1 ,330
1.480
150
11
15
31
36
66
75
123
143
217
506
611
1,090
1.210
2(K)
9
M
28
33
60
69
112
129
183
438
.531
948
1,0.50
250
8
12
25
30
53
61
99
117
163
390
476
8.50
934
300
8
11
23
26
50
57
90
107
147
3,57
434
777
854
*EHD = Equh'alent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between
different tubing .sizes. The greater the value of EHD, the greater the gas capacity of the tubing.
Notes:
(J) Table includes losses for four 90 degree bends and two end fittings. Tubing runs wth larger numbers of
bends and/or fittings shall be increa,sed by an equivalent length of tubing to the following equation: L= I3n,
where £ is additional length (ft) of tubing and « is the number of additional titnngs and/or bends.
(2) All table entries are rounded to 3 significant digits.
Table 12-37 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6.3(i)3
Gas:
Undiluted
Propane
Inlet Pressure:
2.0 psi
Pressure Drop:
1.0 psi
Specific Gravity:
1.50
Tube Size (EH0)*
Flow Bedgnation:
13
15
18
19
23
25
30
31
37
46
48
60
62
Length (ft)
Cap
arity in Thousands of 1
Itu per Hov
LT
10
426
558
927
1,110
1,740
2,170
4,100
4,720
7,1.30
15,200
16,800
29,400
34,200
25
262
347
.591
701
1,120
1,380
2,560
2.950
4,560
9,5.50
10,700
18.800
21,700
SO
2.38
3! 6
540
640
1,0.30
1,270
2,.330
2,690
4,180
8,710
9,790
17,200
19.800
40
203
271
469
5.54
896
1,100
2,010
2,320
3,630
7,5.30
8,500
14,900
17,200
50
181
243
420
496
806
980
1,790
2,070
3,260
6,730
7,610
13,400
15,400
75
147
196
344
406
663
809
1,460
1,690
2,680
5,480
6.230
11.000
12,600
80
140
189
333
393
ftl3
768
1,110
1,630
2,590
5,300
6,010
10,(if)0
12.200
100
124
169
298
350
578
70,3
1,260
1,4.50
2,330
4,740
5.410
9,530
10,900
150
101
137
245
287
477
575
1,020
1.180
1,910
3,860
4,430
7.810
8,890
200
86
lis
213
248
415
.501
880
1,020
1,660
3,340
3,840
6,780
7,710
2.50
77
105
191
222
373
448
785
910
1,490
2,980
3.410
6,080
6,900
.300
69
96
1.73
203
343
411
716
829
:l„360
2,720
3.1,50
5,560
6,300
400
60
82
151
175
298
355
616
716
1,160
2,350
2,730
4,830
5,460
.500
53
72
1.35
158
268
319
550
6.38
1,0.30
2,100
2,450
4,3.30
4,880
*EHD = Equivaleiu Hydraulic Diameter, which is a measure of the relative hydraulic eflFiciency between
different tubing sizes. The greater the value of EHD, the greater the giLS capacity of tlte tubing.
Notes:
(1) Table does not inchide efl'ecl of pressure drop across ihe line regulator. Where regulator loss exceeds
'/4 psi (based on 13 in. w.c. oudet pressure), do not use this table. Consult with regulator manufacturer for
pressure drops and capacity factors. lVes.sure drops acro,ss a regulator may rary with flow rate.
(2) CIAUTION: (Capacities shown in table may exceed maximum capacity for a selected regulator. Consult
with regnlator or tubing mantjfactiner for guidance.
(3) Taliie includes losstis for four 90 degree bends and two end fittings. Tubing runs with latter number of
bends and/or fittings shall be increa.sed by an equivalent: length of tubing according to the following equa-
tion; L ~ 1 .3?}, where /, is additional |{::ngth (ft) of tubing and n is the runnber of additional fittings and/or
bends.
(4) All table entries are rounded to 3 significant digit.s.
196
FUEL PIPING
Table 12-38 -Table 12-39
Table 12-38 Corrugated Stainless Steel Tubing (CSST) [NFPA Table 6.3(j)]
Gas:
Undauted
Propane
Inlet Pressure:
5.0 psi
Pressure Drop:
3.5 psi
Spcdlic GraviQi
1.50
Tube Size (EHD)*
Flow Designation:
n
15
18
19
23
25
30
31
37
46 1 48
60
S2
Length (ft)
Capacitj' in Tfaousands of Btti per H»ur
10
826
1,070
1,710
2,060
3,150
4,000
7,830
8,950
13,100
28.600
31,200
54,400
63,800
25
509
664
1,090
1,310
2,040
2.550
4,860
5,600
8,4,00
18,(K»
19,900
34,700
40,400
30
461
603
999
1,190
1.870
2,340
4,4.30
5,100
7,680
16,400
18,200
31,700
36,900
40
m>
520
867
1,0.30
1,630
2,030
3.820
4,400
6,680
14,200
15,800
27.600
32,000
50
352
463
777
926
1,400
1,820
3,410
3,930
S.SSW
12,700
14,100
24,7(XI
28,(M)0
75
284
376
637
737
1,210
1,490
2,770
3,190
4,920
10,300
11,600
20,300
23,400
80
275
363
6iS
731
1,170
1,450
2,680
3,090
4,770
9,990
11,200
19,600
22,700
too
243
324
5.53
656
1,0.50
l„300
2,390
2,760
4,280
8,9.30
10,000
17,«K)
20,300
150
196
262
453
535
866
1,060
1.940
2,240
3,510
7,270
8,210
14,400
16,600
200
160
226
393
464
755
923
1,680
. 1,930
3,050
6,2«»0
7,130
12,500
14,400
250
150
202
352
415
679
828
1,490
1,730
2,740
5,620
6,390
M,200
12,900
SOO
136
183
322
379
622
757
1,360
1,570
2,510
5.120
5,8-10
10,300
11.700
400
117
158
279
328
542
657
1,170
1,360
2,180
4,430
5,070
8,920
10,200
500
104
140
251
294
488
,589
i.050
1,2 !0
1,930
3,960
4,540
8,000
9,1 10
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efFiciency between
different tubing sizes. Tlie greater the vakie of EUD, the greater the gas capacity of the tubing.
Notes:
(1) Table does not include effect of pressure drop across tlw; line regulator. Where regulator loss exceeds
V4 p.si (based on 13 in. w.c. outlet pressure), do not use this table. Consult with regulator manufacturer for
pres.sure drops and capacity factors. Pressure drops across a regulator may vaiy with flow rate.
(2) CAUTION: Ciipacities shown in table may exceed maximum capacity for a selected regulator. Conauh
with regulator or itihing manufacturer for guidance.
(S) Table includes losses for four 90 degree bends and two end fittings. Tubing riu>s-4vith larger number of
()ends and/or fittings .shatl be increased by an equivalent length of tubing according to the following equa-
tion: L = l.3n, where L is additional length (ft) of tubing and ;* is the number of additional fittings and/or
bends.
(4) All table entries are routided to 3 significant digits.
Table 12-39
Polyethylene Plastic Pipe [nfpa Table 6.3(k)]
Gas:
Undiluted Propane
Inlet Pressure:
11.0 in. w.c.
Pressure Drop:
0.5 in. w.c.
Specific Gravity:
1.50
Pipe Size (in.)
Nominal OD:
•A
%
1
IV4
I'/S
2
Designation:
SDR 9.33
SDR 11.0
SDR 11.00
SDR 10.00
SDR 11.00
SDRH.OO
Actual ID:
0.660
0.860
1.077
1.328
1.554
1.943
I.ength (ft)
Capacity in lliousands of Btu per Hour
10
340
680
1,230
2,130
3,210
5,770
20
233
468
844
1,460
2.210
3,970
SO
187
.375
677
1,170
1,770
,3,180
40
160
.321
580
1,000
!,.520
2,730
50
142
285
514
890
1,340
2,420
60
129
258
466
807
1,220
2,190
70
119
2.37
428
742
1,120
2,010
80
110
221
398
690
1,040
1,870
90
103
207
374
&48
978
1,7(»
100
98
196
353
612
924
i,fm
125
87
173
313
542
819
1,470
1.50
78
1.57
284
491
742
1,330
175
72
145
261
4.52
683
1,2.30
200
67
135
243
420
635
1,140
250
60
119
215
373
563
1,010
300
54
108
19.5
338
510
916
360
50
99
179
311
469
843
4.00
46
92
167
289
436
784
450
43
87
157
271
409
736
500
41
82
148
2.56
.387
695
Note: All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA-
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
197
Table 12-40
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA,
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Table 12-40 Polyethylene Plastic Pipe [NFPA Table 6.3(1)]
Gas:
Undiluted Propane
Inlet Pressure:
2.0 psi
Pressure Drop:
1.0 psi
Specific Gravity:
1.50
Pipe Size (in.)
Nominal OD:
Mt
Y4
1
IVa
\^A
2
Designation:
SDR 9.33
SDR 11.0
SDR 11.00
SDR 10.00
SDR 11.00
SDR 11.00
Actual ID:
0.660
0.860
1.077
1.328
1.554
1.943
Length (ft)
Capacity in Thousands of Btu per Hour
10
3,130
6,260
11,300
19,600
29,500
53.100
20
2,150
4,300
7,760
1,3,400
20,300
36,5(K)
30
1,730
3.450
6,230
10,800
16,300
29.300
40
1,480
2.9()0
5,330 •
9,240
14,000
25,100
50
1,310
2,620
4,730
8,190
12,400
22,200
60
1,190
2,370
4,280
7,420
11.200
20,100
70
1,090
2.180
3,940
6,830
1O,.30O
18,500
80
1.010
2,030
3,670
6,350
9,590
17,200
90
952
1,910
3,440
5,960
9.000
16,200
100
899
1,800
3,250
5,630
8,.500
15,300
125
797
1,600
2,880
4,990
7,530
13,500
150
722
1,450
2,610
4,520
6,8.30
12,300
175
664
1.330
2,400
4,160
6,280
11,300
200
618
1,240
2,230
3,870
5,840
10,500
250
548
1,100
1,980
3,430
5,180
9.300
300
496
994
1,790
3,110
4,690
8,430
350
457
914
1,650
2,860
4,320
7.760
400
425
851
1,530
2,660
4,020
7,220
450
3il9
798
1,440
2,500
3,770
6,770
500
.^77
754
1,360
2.360
3,560
6,390
550
358
716
1,290
2,240
3,380
6,070
600
341
683
1,230
2,140
3,220
5,790
650
327
654
1,180
2,040
3,090
5,550
700
314
628
1,130
1,960
2,970
5,.330
750
302
605
1,090
1.890
2,860
5,140
800
292
585
1,050
1,830
2,760
4,960
850
283
566
1,020
1,770
2,670
4,800
900
274
549
990
1,710
2,590
4,650
950
266
5.33
961
1,670
2,.520
4,.520
1,000
259
518
935
1,620
2,450
4,400
1.100
246
492
888
1,540
2,320
4,170
1,200
2.34
470
847
1,470
2,220
3,980
1,300
225
450
811
1,410
2,120
3,810
1,400
216
432
779
1.350
2,040
3.660
1,500
208
416
751
1,300
1,960
3,530
1,600
201
402
725
1,260
1,900
3,410
1,700
194
389
702
1,220
1,840
3,300
1,800
188
377
(580
1,180
1,780
3,200
1,900
183
366
661
1,140
1,730
3,110
2,000
178
356
643
1,110
1,680
3,020
Note: All table entries are rounded to 3 significant digits.
198
FUEL PIPING
Table 12-41
Table 12-41 Polyethylene Plastic Tubing
[NFPA Table 6.3(m)]
Gas:
Undiluted Propane
Inlet Pressure:
II.O in. w.c.
Pressure Drop:
0.5 in. w.c
Specific Gravity:
1.50
Plastic Tubing Size <CTS) (in.)
Nominal OD:
V^
3/4
Designadon:
SDR 7.00
SDR 11.00
Actual ID:
0.445
0.927
Length (ft)
Capaci^ in Thousands of Btu per Hour
10
121
828
20
83
569
30
67
457
40
57
391
60
51
347
60
46
314
70
42
289
80
39
269
90
37
252
100
35
238
125
31
211
150
28
191
175
26
176
200
24
164
225
22
154
250
21
145
275
20
138
300
19
132
350
18
121
400
16
113
450
15
106
500
15
100
Note: All table entries are rounded to 3 significant digits.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
199
UNIFORM PLUMBING CODE
200
CHAPTER 13
HEALTH CARE FACILITIES AND MEDICAL GAS AND VACUUM SYSTEMS
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Part I - Special Requirements for
Health Care Facilities.
1301.0 Application.
1301.1 Construction and equipment requirements
shall be applied only to new construction and new
equipment, except as modified in individual
chapters. Only the altered, renovated, or modernized
portion of an existing system or individual
component shall be required to meet the installation
and equipment requirements stated in this standard.
If the alteration, renovation, or modernization
adversely impacts existing performance requirements
of a system or component, additional upgrading
shall be required. [NFPA 99: 1.3.2]
1301.2 This chapter applies to the special fixtures
and systems in health care facilities and to the special
plumbing requirements for such facilities. Other
plumbing in such facilities shall comply with other
applicable sections of this code.
1 301 .3 This chapter shall not apply to breathing air
replenishment (BAR) systems.
1302.0 Medical Gas and Vacuum Piping Systems
- Installation Requirements.
The installation of medical gas and vacuum piping
systems shall be in accordance with the requirements
of this chapter and /or the appropriate standards
adopted by the Authority Having Jurisdiction. For
additional standards see Table 14-1.
1302.1 The installation of individual components
shall be made in accordance with the instructions of
the manufacturer. Such instructions shall include
directions and information deemed by the
manufacturer to be adequate for attaining proper
operation, testing, and maintenance of the medical
gas and vacuum systems. Copies of the manu-
facturer's instructions shall be left with the system
owner. [NFPA 99: 5.1.10.6.9.1, 5.1.10.6.9.2, 5.1.10.6.9.3]
1 302.2 The installation of medical gas and vacuum
systems shall be made by qualified, competent
technicians who are experienced in making such
installations. Installers of medical gas and vacuum
systems shall meet the requirements of ANSI/ASSE
Standard 6010, Professional Qualification Standard for
Medical Gas and Vacuum System Installers. [NFPA 99:
5.1.10.6.11.1,5.1.10.6.11.2]
1 302.3 Brazing shall be performed by individuals
who are qualified under the provisions of Section
1311.6. [NFPA 99: 5.1.10.6.11.3]
1302.4 Prior to any installation work, the installer of
medical gas and vacuum piping shall provide and
maintain documentation on the job site for the
qualification of brazing procedures and individual
brazers that is required under Section 1311.6.
[NFPA 99: 5.1.10.6.11.4]
1303.0 Protrusions from Walls.
1303.1 Drinking fountain control valves shall be
flush-mounted or fully recessed when installed in
corridors or other areas where patients may be
transported on a gurney, bed, or wheelchair.
1303.2 Piping exposed in corridors and other areas
where subject to physical damage from the move-
ment of carts, stretchers, portable equipment, or
vehicles shall be protected. [NFPA 99: 5.1.10.6.2.1]
1304.0 Psychiatric Patient Rooms.
Piping and drain traps in psychiatric patient rooms
shall be concealed. Fixtures and. fittings shall be
resistant to vandalism. [NFPA 101]
1305.0 Locations for Ice Storage.
Ice makers or ice storage containers shall be located
in nursing stations or similarly supervised areas to
minimize potential contamination. [See NFPA 101]
1306.0 Sterilizers.
1306.1 General. The requirements of this section
apply to sterilizers and bedpan steamers. Such
equipment shall be installed in accordance with this
code and the manufacturer's installation instructions.
1306.2 Indirect Waste Connections.
Waste drainage from sterilizers and bedpan steamers
shall be connected to the sanitary drainage system
through an airgap in accordance with this chapter
and Chapter 8. The size of indirect waste piping shall
not be less than the size of the drain connection on
the fixture. Each such indirect waste pipe shall not
exceed fifteen (15) feet (4,572 mm) in length and shall
be separately piped to a receptor. Such receptors
shall be located in the same room as the equipment
served. Except for bedpan steamers, such indirect
waste pipes shall not require traps. A trap having a
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
201
1306.2-1310.5
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
minimum, seal of three (3) inches (80 mim) shall be
provided in the indirect waste pipe for a bedpan
steamer.
1307.0 Vapor Vents and Stacks for Sterilizers.
1307.1 General. When a sterilizer has provision for
a vapor vent and such a vent is required by the
manufacturer, the vent shall be extended to the
outdoors above the roof. Sterilizer vapor vents shall
be installed in accordance with the manufacturer's
instructions and shall not be connected to any
drainage system vent.
1308.0 Aspirators.
1308.1 See Section 603.4.9, Water Inlets to Water
Supplied Aspirators. Provisions for aspirators or
other watersupplied suction devices shall be
installed only with the specific approval of the
Authority Having Jurisdiction. Where aspirators are
used for removing body fluids, they shall include a
collection container to collect liquids and solid
particles. Aspirators shall indirectly discharge to the
sanitary drainage system through an airgap in
accordance with Chapter 8. The potable water
supply to an aspirator shall be protected by a
vacuum, breaker or equivalent backflow protection
device in accordance with Section 603.0.
Part II — Medical Gas and Vacuum Systems.
1309.0 Application.
1309.1 The provisions herein shall apply to the
installation, testing, and verification of medical gas
and vacuum piping in hospitals, clinics, and other
health care facilities.
1309.2 The purpose of this chapter is to provide
requirements for the installation, testing, and
verification of medical gas and medical vacuum
systems, from the central supply system to the
station outlets or inlets.
1 309.3 Wherever the terms medical gas or vacuum
occur, the provisions shall apply to all piped systems
for oxygen, nitrous oxide, medical air, carbon
dioxide, helium, medical-surgical vacuum, waste
anesthetic gas disposal, and mixtures thereof.
Wherever the name of a specific gas or vacuum
service occurs, the provision shall apply only to that
gas. [NFPA 99: 5.1.1.2]
1309.4 This chapter does not apply to portable
compressed gas systems.
1309.5 This chapter does not apply to:
(A) Cylinder and container management,
storage, and reserve requirements.
(B) Gas central supply and bulk supply systems,
except as addressed in this chapter.
(C) Electrical connections and requirements.
(D) Motor requirements and controls.
(E) Systems having nonstandard operating
pressures, except as addressed in this chapter.
(F) Waste anesthetic gas disposal (WAGD)
systems.
(G) Surface-mounted medical gas rail systems
1 309.6 The requirements of this chapter shall not be
interpreted to conflict with the requirements of
NFPA 99 Standard for Health Care Facilities. For
requirements of portions of medical gas and medical
vacuum systems not addressed in this chapter or
medical gas and medical vacuuin systems beyond
the scope of this chapter refer to NFPA 99 Standard
for Health Care Facilities.
1309.7 An existing system that is not in strict
compliance with the provisions of the standard
(Code) shall be permitted to be continued in use as
long as the Authority Having Jurisdiction has
determined that such use does not constitute a
distinct hazard to life. [NFPA 99 4-1.4] (Same as the
2002 edition of NFPA 99: 5.1.1.3.)
1310.0 Definitions.
1310.1 Building Supply - The pipe from the source
of supply to a building or structure.
1310.2 Critical Care Area - Those special care
units, intensive care units, coronary care units,
angiography laboratories, cardiac catheterization
laboratories, delivery rooms, operating rooms,
postanesthesia recovery rooms, emergency
departments, and similar areas in which patients are
intended to be subjected to invasive procedures and
connected to line-operated, patient-care-related
electrical appliances. [NFPA 99: 3.3.135.2]
1310.3 General Care Areas - General care areas are
patient bedrooms, examining rooms, treatment
rooms, clinics, and similar areas in which it is
intended that the patient will come in contact with
ordinary appliances such as a nurses-call system,
electric beds, examining lamps, telephones, and
entertainment devices. [NFPA 99: 3.3.135.1]
1310.4 Manifold - A device for connecting outlets of
one or more gas cylinders to the central piping
system for that specific gas. [NFPA 99: 3.3.103]
1310.5 Medical Air - For purposes of this standard,
medical air is air supplied from cylinders, bulk
containers, medical air compressors, or has been
reconstituted from oxygen USP and oil-free, dry
nitrogen NF. Medical air shall be required to have
the following characteristics:
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
202
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
(1) Be supplied from cylinders, bulk containers,
medical air compressor sources, or be
reconstituted from oxygen USP and oil-free
dry nitrogen NF.
(2) Meet the requirements of medical air USP.
(3) Have no detectable liquid hydrocarbons.
(4) Have less than 25 ppm gaseous hydrocarbons.
(5) Have equal to or less than 5 mg/m^ of
permanent particulates sized 1 micron or
larger in the air at normal atmospheric
pressure. [NFPA 99: 3.3.106, 5.1.3.5.1]
1310.6 Medical Gas - Gas used in a medical
facility, including oxygen, nitrous oxide, carbon
dioxide, helium, medical air, and mixtures of these
gases. Standards of purity apply.
1310.7 Medical Gas System - Complete system
consisting of a central supply system (manifold,
bulk, or compressors), including control equipment
and piping extending to station outlets at the points
where medical gases may be required.
1310.8 Medical Vacuum System - See 1310.19,
Vacuum System - Level 1.
1310.9 Nitrogen, NF (Oil-Free, Dry) (Nitrogen for
Brazing and Testing) - Nitrogen complying, as a
minimum, with oil-free, dry nitrogen NF. [NFPA 99:
NFPA I 3.3.120.1]
1310.10 Patient Care Area - Any portion of a health
care facility wherein patients are intended to be
examined or treated. [NFPA 99: 3.3.138]
1310.11 Purge, Flow - The removal of oxygen from
a system by oil-free dry nitrogen during brazing.
1310.12 Purge, System - The removal of nitrogen
from a system with the medical gas required for that
system.
1310.13 SOFM - Standard cubic feet per minute. [NFPA
99: 3.3.159]
1310.14 Special Hazard Area - An area such as a
kitchen or electrical switch-gear room.
1310.15 Station Inlet - An inlet point in a medical-
surgical piped vacuum distribution system at which
the user makes connections and disconnections.
[NFPA 99: 3.3.171]
1310.16 Station Outlet - An inlet point in a piped
medical/surgical vacuum distribution system at
which the user makes connections and
disconnections. [NFPA 99: 3.3.168]
1310.17 Use Point - A room or area of a room
where medical gases are dispensed to a single
patient for medical purposes. A use point is
permitted to be comprised of a number of station
outlets of different gases. [NFPA 99: 3.3.175]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
■NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1310.5-1311.1
1310.18 User Outlet - See Station Outlet.
1310.19 Vacuum System - Level 1 - A system
consisting of central vacuum-producing equipment
with pressure and operating controls, shutoff valves,
alarm warning systems, gauges, and a network of
piping extending to and terminating with suitable
station inlets at locations where patient suction could
be required. [NFPA 99: 3.3.91]
1310.20 Valve, Isolation - A valve that isolates one
piece of equipment from another.
1310.21 Valve, Riser - A valve at the base of a
vertical riser that isolates that riser.
1310.22 Valve, Service - A valve serving horizontal
piping extending from a riser to a station outlet or
inlet.
1310.23 Valve, Source - A single valve at the
source that controls a number of units that make up
the source.
1310.24 Valve, Zone - A valve that controls the gas
or vacuum to a particular area.
1310.25 Waste Anesthetic Gas Disposal - The
process of capturing and carrying away gases vented
from the patient breathing circuit during the normal
operation of gas anesthesia or analgesia equipment.
[NFPA 99: 3.3.178]
1311.0 General Requirements.
1311.1 Oxygen Compatibility - Tubes, valves,
fittings, station outlets, and other piping components
in medical gas systems shall have been cleaned for
oxygen service by the manufacturer prior to
installation in accordance with CGA 4.1, Cleaning
Equipment for Oxygen Service, except that fittings shall
be permitted to be cleaned by a supplier or agency
other than the manufacturer. [NFPA 99: 5.1.10.1.1]
1311.1.1 Components include but are not
limited to containers, valves, valve seats,
lubricants, fittings, gaskets, and interconnecting
equipment including hose. Easily ignitable
materials should be avoided.
Compatibility involves both combustibility
and ease of ignition. Materials that burn in air
will burn violently in pure oxygen at normal
pressure and explosively in pressurized oxygen.
Also, many materials that do not bum in air will
do so in pure oxygen, particularly under
pressure. Metals for containers and piping have
to be carefully selected, depending on service
conditions. The various steels are acceptable for
many applications, but some service conditions
can call for other materials (usually copper or its
alloys) because of their greater resistance to
ignition and lower rate of combustion.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
203
1311.1 -1311.6
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Similarly, materials that can be ignited in air
have lower ignition energies in oxygen. Many
such materials can be ignited by friction at a
valve seat or stem packing or by adiabatic
compression produced when oxygen at high
pressure is rapidly introduced into a system
initially at low pressure.
1311.1.2 Materials used in central supply
systems shall meet the following requirement:
In those portions of systems intended to
handle oxygen or nitrous oxide at gauge
pressures of less than 2,070 kPa (300 psi),
material construction shall be compatible with
oxygen under the temperatures and pressures to
which the components can be exposed in the
containment and use of oxygen, nitrous oxide,
mixtures of these gases, or mixtures containing
more than 23.5 percent oxygen. [NFPA 99:
5.1.3.4.3 (2)]
1311.2 Certification of medical gas and medical
vacuum systems shall conform to the requirements
of Section 1328.0 of this code, the Authority Having
Jurisdiction, and NFPA 99 Standard for Health Care
Facilities section 5.1.12. [NFPA 99: 5.1.12].
1 31 1 .3 Prior to any installation work, the installer of
medical gas and vacuum piping shall provide and
maintain documentation on the job site for the
qualification of brazing procedures and individual
brazers that is required under Section 1311.6. [NFPA
99: 5.1.10.6.11.4]
1 31 1 .3.1 Each length of tube shall be delivered
plugged or capped by the manufacturer and
kept sealed until prepared for installation.
Fittings, valves, and other componients shall be
delivered sealed, labeled, and kept sealed until
prepared for installation. [NFPA 99: 5.1.10.1.2
and 5.1.10.1.3]
1 31 1 .4 All medical gas and medical vacuum systems
shall be supplied from a source consisting of at least
two units - primary and secondary, e.g., a manifold
consisting of two cylinder banks with at least two
cylinders in each bank, a minimum of two air
compressors, or a minimum of two vacuum pumps.
However, two supply pipelines are not required.
1311.5 Health Care Organization personnel shall be
permitted to install piping systems if all the
requirements of this chapter are met during
installation. [NFPA 99: 5.1.10.6.11.5]
1 31 1 .6 Brazing procedures and brazer performance
for the installation of medical gas and vacuum
piping shall be qualified in accordance with either
Section IX, Welding and Brazing Qualifications, of the
ASME Boiler and Pressure Vessel Code, or AWS
B2.2, Standard for Brazing Procedure and Performance
Qualifications, both as modified below. [NFPA 99:
5.1.10.6.12.1]
1311.6.1 Brazers shall be qualified by visual
examination of the test coupon followed by
sectioning. [NFPA 99: 5.1.10.6.12.2]
1311.6.2 The Brazing Procedure Specification
(BPS) shall address cleaning, joint clearance,
overlap, internal purge gas purge gas flow rate,
and filler metal. [NFPA 99: 5.1.10.6.12.3]
1311.6.3 The brazing procedure specification
and the record of brazer performance
qualification shall document filler metal used,
cleaning, joint clearance, overlap, internal purge
gas, and flow rate during brazing of coupon,
and the absence of internal oxidation in the
completed coupon. [NFPA 99: 5.1.10.6.12.4]
1311.6.4 Brazing procedures qualified by a
technically competent group or agency shall be
permitted under the following conditions:
(1) The brazing procedure specification and
the procedure qualification record
meets the requirements of this standard.
(2) The employer obtains a copy of both the
brazing procedure specification and the
supporting qualification records from
the group or agency and signs and dates
these records, thereby accepting
responsibility for the qualifications that
were performed by the group or agency.
(3) The employer qualifies at least one
brazer following each brazing procedure
specification used. [NFPA 99: 5.1.10.6.12.5]
1311.6.5 An employer shall be permitted to
accept brazer qualification records of a previous
employer under the following conditions:
(1) The brazer has been qualified following
the same or an equivalent procedure
that the new employer uses.
(2) The new employer obtains a copy of the
record of brazer performance
qualification tests from the previous
employer and signs and dates these
records, thereby accepting responsibility
for the qualifications performed by the
previous employer. [NFPA 99: 5.1.10.6.12.6]
1311.6.6 Performance qualifications of brazers
shall remain in effect indefinitely unless the
brazer does not braze with the qualified
procedure for a period exceeding six months, or
there is a specific reason to question the ability
of the brazer. [NFPA 99: 5.1.10.6.12.7]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA .
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
204
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
1312.0 Plan Review.
1312.1 Before any medical gas or medical vacuum
system is installed or altered in any hospital,
medical facility, or clinic, duplicate plans and
specifications shall be filed with the Authority
Having Jurisdiction. Approval of the plans shall be
obtained prior to issuance of any permit by the
Authority Having Jurisdiction.
1312.2 Plans and specifications shall show the
following, in detail:
1312.2.1 Plot plan of the site, drawn to scale,
indicating the location of existing or new
cylinder storage areas, property lines,
driveways, and existing or proposed buildings.
1312.2.2 Piping layout of the proposed piping
system or alteration, including alarms, valves,
origin of gases, and user outlets/inlets. The
demand and loading of any piping, existing or
future, shall also be indicated.
1 31 2.2.3 Complete specification of materials.
1312.3 Plans and specifications submitted to the
Authority Having Jurisdiction shall clearly indicate
the nature and extent of the work proposed and shall
show in detail that such work will conform to the
provisions of this code.
1312.4 A record of as-built plans and valve
identification records shall remain on the site at
all times.
1313.0 System Performance.
NFPA 1313.1 Required Operating Pressures. All medical
NFPA ■ • •*
NFPA gas and medical vacuum systems shall be capable of
NFPA delivering service in the pressure ranges listed in Table
NFPA 13-1. [NFPA 99: Table 5.1.11]
1313.2 AAinimum Flow Rates. All medical gas and
medical vacuum systems shall be capable of
supplying the flow rates listed in Table 13-2.
1313.3 Minimum Station Outlets/Inlets. Station
outlets and inlets for medical gas and medical vacuum
systems shall be provided as listed in Table 13-3.
1314.0 Required Pipe Sizing.
1314.1 Where the maximum demand for each
medical gas or vacuum system and the maximum
length of piping between the source equipment and
the most distant station outlet/inlet do not exceed the
values in Table 13-6, the size of pipe of each section of
the system shall be determined using Tables 13-4 and
13-6. The size for systems beyond the range of Table
13-6 shall be determined by using the methods set
forth in Section 1314.3 of this chapter.
1312.0-1315.2
1314.2 To determine the size of each section of pipe
in any system within the range of Table 13-6,
proceed as follows:
1314.2.1 Measure the length of the pipe from
the source equipment location to theinost
remote station inlet/outlet on the system.
1314.2.2 In Table 13-6, select the column
showing that distance, or the next longer
distance if the table does not give the exact
length.
1 31 4.2.3 Starting at the most remote outlet/inlet,
find in the vertical column just selected the
medical gas or vacuum demand for that
inlet/outlet. If the exact figure of demand is not
shown, choose the next larger figure below iii the
column.
1314.2.4 Opposite this demand figure, in the
first column at the left in Table 13-6, will be
found the correct size of pipe.
1314.2.5 Using this same vertical column,
proceed in a similar manner for each section of
pipe serving this inlet/outlet. For each section of
pipe, determine the total gas or vacuum demand
supplied by the section, using Table 13-4.
1314.2.6 Size each section of branch piping not
previously sized by measuring the distance from
the source equipment location to the most
remote inlet /outlet in that branch, and follow
the procedures of Sections 1314.2.2, 1314.2.3,
1314.2.4, and 1314.2.5.
Note:
Size branch piping in the order of the distance from
the source location, begirming with the most distant
outlet not previously sized.
1314.3 For conditions other than those covered by
Section 1314.1 of this section, such as longer runs of
greater gas or vacuum demands, the size of each gas
or vacuum piping system shall be determined by
standard engineering methods acceptable to the
Authority Having Jurisdiction, and each isystem shall
be so designed that the total pressure drop or gain
between the source equipment and any inlet/ outlet
will not exceed the allowable pressures shown in
Table 13-1.
1315.0 Workmanship.
1315.1 All design, construction, and workmanship
shall be in conformity with accepted engineering
practices and shall meet the requirements of this code.
1315.2 Cracks, holes, or other imperfections in
materials shall not be concealed by welding, brazing,
or soldering, or by using paint, wax, tar, or other
leak-sealing or repair agents.
205
1315.3-1316.6
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
..NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1 31 5.3 Burred ends of all tubing shall be deburred
using a deburring tool to the full bore of the tube,
and all chips shall be removed.
1316.0 Materials. The provisions of this section
apply to the field-installed piping for the distribution
of medical piped gases.
1316.1 Tubes, valves, fittings, station outlets, and
other piping components in medical gas systems
shall have been cleaned for oxygen service by the
manufacturer prior to installation in accordance
with CGA 4.1, Cleaning Equipment for Oxygen Service,
except that fittings shall be permitted to be cleaned
by a supplier or agency other than the nianu-
facturer. [NFPA 99: 5.1.10.1.1]
1316.2 Each length of tube shall be delivered
plugged or capped by the manufacturer and kept
sealed until prepared for installation. Fittings,
valves, and other components shall be delivered
sealed, labeled, and kept sealed until prepared for
installation. [NFPA 99: 5.1.10.1.2, 5.1.10.1.3]
1 31 6.3 Tubes shall be hard-drawn seamless copper
ASTM B 819 medical gas tube. Type L, except that
where operating pressures are above a gauge
pressure of 1,275 kPa (185 psi). Type K shall be used
for sizes larger than DN80 (NPS 3) (3-1/8 in. CD.).
ASTM B 819 medical gas tube shall be identified
by the manufacturer's markings "OXY," "MED,"
"OXY/MED," "OXY/ACR," or "ACR/MED" in blue
(Type L) or green (Type K). [NFPA 99: 5.1.10.1.4,
5.1.10.1.5]
Piping for vacuum systems shall be constructed
of any of the following:
(1) Hard-drawn seamless copper tube
(a) ASTM B 88, Standard Specification for
Seamless Copper Water Tube, copper tube
(Types K, L, M).
(b) ASTM B 280, Standard Specification for
Seamless Copper Tubing for Air Condition-
ing and Refrigeration Field Service, copper
ACR tube.
(c) ASTM B 819, Standard Specification for Seam-
less Copper Tube for Medical Gas Systems,
copper medical gas tubing (T)qpe K or L).
(2) Stainless steel tube [NFPA 99: 5.1.10.2.1]
Piping systems shall be designed and sized to
deliver the required flow rates at the utilization
pressures.
Mains and branches in medical gas-piping
systems shall be not less than DN15 (NPS 1/2) (5/8
in. CD.) size.
Mains and branches in medical-surgical vacuum
systems shall be not less than DN20 (NPS 3/4) (7/8
in. CD.) size.
Drops to individual station outlets and inlets shall
be not less than DN15 (NPS 1/2) (5/8 in. CD.) size.
Runouts to alarm panels and connecting tubing
for gauges and alarm devices shall be permitted to
be DN8 (NPS 1/4) (3/8 in. CD.) size. [NFPA 99:
5.1.10.10.1.1-5.1.10.10.1.5]
1316.4 Turns, offsets, and other changes in direction
in welded or brazed medical gas and vacuimi piping
shall be made with wrought-copper capillary fittings
complying with ASME B16.22, Wrought Copper and
Copper Alloy Solder-Joint Pressure Fittings, or
brazed fittings complying with ASME B16.50,
Wrought Copper and Copper Alloy Braze-Joint
Pressure Fittings.
1316.4.1 Cast-copper alloy fittings shall not be
permitted.
1316.4.2 Branch connections in vacuum piping
systems shall be permitted to be made using
mechanically formed, drilled, and extruded tee-
branch connections that are formed in accordance
with the tool manufacturer's instructions and
brazed. [NFPA 99: 5.1.10.3.1, 5.1.10.3.2, 5.1.10.3.3,
5.1.10.5.8 (4)-(7)]
1316.5 The following special fittings shall be
permitted to be used in lieu of brazed joints:
(1) Memory-metal couplings having temperature
and pressure ratings joints not less than that
of a brazed joint.
(2) Listed or approved metallic gas tube fittings
that, when made up, provide a permanent
joint having the mechanical, thermal, and
sealing integrity of a brazed joint.
(3) Dielectric fittings where required by the
manufacturer of special medical equipment
to electrically isolate the equipment from the
piping distribution system.
(4) AxiaUy swaged, elastic strain preload fittings
providing metal to metal seal having pressure
and temperature ratings not less than that of
a brazed joint and, when complete, are
permanent and nonseparable.
1316.6 The following joints shall be prohibited
throughout medical gas and vacuum distribution
pipeline systems:
(1) Flared and compression-type connections,
including connections to station outlets and
inlets, alarm devices, and other components.
(2) Other straight-threaded connections, including
imions.
(3) The use of pipe-crimping tools to permanently
stop the flow.
131 6.6.1 Threaded joints in medical gas and
vacuum distribution piping shall meet the
following requirements:
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA^
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA^
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA-
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
I NFPA
NFPA
NFPA
' NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
206
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
.NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA .
NFPA
NFPA .
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
(1) Be limited to connections to pressure/
vacuum indicators, alarm devices, and
source equipment.
(2) Be tapered pipe threads complying with
ANSI Bl.20.1, Pipe Threads, General
Purpose.
(3) Be made up with polytetrafluoroethylene
(such as Teflon^'^) tape or other thread
sealant recoinmended for oxygen
service, with the sealant applied to the
male threads only. [NFPA 99: 5.1.10.5.8,
5.1.10.5.9 and 5.1.10.4]
1316.7 New or replacement shutoff valves shall be
as follows:
(1) Quarter turn, full ported ball type.
(2) Brass or bronze construction.
(3) Have extensions for brazing.
(4) Have a handle indicating open or closed.
(5) Consist of three pieces permitting in-line
serviceability. [NFPA 99: 5.1.4.3]
1316.8 Soldered joints in copper Level 3 vacuum and
Level 3 gas-powered systems piping shall be made in
accordance with ASTM B 828, Making Capillary Joints by
Soldering of Copper and Copper Alloy Tube and Fittings,
using a lead-free solder filler metal containing not more
than 0.2 percent lead by volume. [NFPA 99: 5.3.10.5]
1317.0 Cleaning for Medical Gas Piping Systems.
1317.1 The interior surfaces of tube ends, fittings, and
other components that were cleaned for oxygen service
by the manufacturer, but become contaminated prior
to being installed, shall be permitted to be recleaned
on-site by the installer by thoroughly scrubbing the
interior surfaces with a clean, hot water-alkaline
solution, such as sodium carbonate or trisodium
phosphate 450 g to 11 L (1 lb. to 3 gal.) of potable water
and thoroughly rinsing them with clean, hot potable
water. Other aqueous cleaning solutions shall be
permitted to be used for on-site recleaning permitted
above, provided that they are as recommended in
CGA Pamphlet G-4.1, Cleaning Equipment for Oxygen
Service, and are listed in CGA Pamphlet 02-PIR,
Directory of Cleaning Agents for Oxygen Service. [NFPA
99: 5.1.10.5.3.10 and 5.1.10.5.3.11]
1317.2 Material that has become contaminated
internally and is not clean for oxygen service shall
not be installed. [NFPA 99: 5.1.10.5.3.12]
1318.0 Installation of Piping.
1318.1 Piping shall be protected against freezing,
corrosion, and physical damage.
1316.6-1318.4
Piping exposed in corridors and other areas
where subject to physical damage from the
movement of carts, stretchers, portable equipment,
or vehicles shall be protected.
Piping underground within buildings or
embedded in concrete floors or walls shall be
installed in a continuous conduit. [NFPA 99:
5.1.10.6.2, 5.1.10.6.2.1, 5.10.6.2.2]
1318.2 Piping risers shall be permitted to be
installed in pipe shafts if protected from physical
damage, effects of excessive heat, corrosion, or
contact with oil.
Piping shall not be installed in kitchens, elevator
shafts, elevator machine rooms, areas with open
flames, electrical service equipment over 600 volts,
and areas prohibited under NFPA 70, National
Electrical Code/except for the following locations:
(1) Room locations for medical air compressor
supply systems and medical-surgical vacuum
pump supply systems.
(2) Room locations for secondary distribution
circuit panels and breakers having a maximum
voltage rating of 600 volts.
. Medical gas piping shall be permitted to be
installed in the same service trench or tunnel with
fuel gas lines, fuel oil lines, electrical lines, steam
lines, and similar utilities provided that the space is
ventilated (naturally or mechanically) and the
ambient temperature around the medical gas piping
is limited to 130°F (54°C ) maximum.
Medical gas piping shall not be located where
subject to contact with oil, including a possible
flooding area in the case of a major oil leak. [NFPA
99: 5.1.10.10.3]
1 31 8.3 Buried piping outside of buildings shall be
installed below the local level of frost penetration.
[NFPA 99: 5.1.10.6.5]
1318.4 The installation procedure for underground
piping shall protect the piping from physical damage
while being backfilled.
If imderground piping is protected by a conduit,
cover, or other enclosure, the following requirements
shall be met:
(1) Access shall be provided at the joints for
visual inspection and leak testing.
(2) The conduit, cover, or enclosure shall be self-
draining and not retain groundwater in
prolonged contact with the pipe.
Buried piping that will be subject to surface
loads shall be buried at a depth that will protect the
piping and its enclosure from excessive stresses.
[NFPA 99: 5.1.10.6.5.4]
The minimum backfilled cover above the top of
the pipe or its enclosure for buried piping outside of
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
207
1318.4-1319.1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
buildings shall be 36 inches (900 mm), except that the
minimum cover shall be permitted to be reduced to
18 inches (450 mm) where physical damage is
otherwise prevented.
Trenches shall be excavated so that the pipe
enclosure has firm, substantially continuous bearing
on the bottom of the trench.
Backfill shall be clean and compacted so as to
protect and uniformly support the pipe enclosure.
A continuous tape or marker placed immediately
above the enclosure shall clearly identify the pipeline
by specific name.
A continuous warning means shall also be
provided above the pipeline at approximately one-
half the depth of bury.
Where underground piping is installed through
a wall sleeve, the ends of the sleeve shall be sealed to
prevent the entrance of groundwater into the
building. [NFPA 99: 5.1.10.6.5 - 5.1.10.6.10]
1318.5 Hose and flexible connectors, both metallic
and nonmetallic, shall be no longer than necessary
and shall not penetrate or be concealed in walls,
floors, ceilings, or partitions. Flexible connectors,
metallic or nonmetallic, shall have a minimum burst
pressure, with a gauge pressure of 6,895 kPa (1,000
psi). [NFPA 99: 5.1.10.6.7]
1318.6 Where a positive-pressure medical gas-
piping distribution system, originally used or
constructed for the use at one pressure and for one
gas, is converted for operation at another pressure or
for another gas, all provisions of NFPA 5.1.10 shall
apply as if the system were new. [NFPA 99:
5.1.10.6.10.1]
A vacuum system shall not be permitted to be
converted for use as a gas system. [NFPA 99:
5.1.10.6.10.2]
1318.7 Piping exposed in corridors and other areas
where subject to physical damage from the
movement of carts, stretchers, portable equipment, or
vehicles shall be protected. [NFPA 99: 5.1.10.6.2.1]
1318.8 Piping shall be supported from the building
structure in accordance with MSS Standard Practice
SP-69, Piping Hangers and Supports - Selection and
Application.[NFFA 99: 5.1.10.6.4.1]
Hangers and supports shall comply with MSS
Standard Practice SP-58, Pipe Hangers and Supports -
Materials, Design, and Manufacture. [NFPA 99:
5.1.10.6.4.2]
Hangers for copper tube shall have a copper finish
and be sized for copper tube. [NFPA 99: 5.1.10.6.4.3]
In potentially damp locations, copper tube hangers
or supports that are in contact with tiie tube shall be
plastic-coated or otherwise be insulated from the tube.
[NFPA 99: 5.1.10.6.4.4]
Maximum support spacing shall be in
accordance with Table 13-7. [NFPA 99: Table
5.1.10.6.4.5]
1318.9 Where required, medical gas and vacuum
piping shall be seismically restrained against
earthquakes in accordance with the applicable
building code. [NFPA 99 5.1.10.6.4.6] Seismic
considerations shall conform to the requirements of
this code and the Authority Having Jurisdiction.
1318.10 Two or more medical gas-piping systems
shall not be tntercoimected for testing or any other
reason. Leak testing shall be accomplished by
separately charging and testing the individual piping
system. [NFPA 99: 5.1.10.6.8.1-2]
1318.11 Piping shall be labeled by stenciling or
adhesive markers that identify the patient medical
gas, the support gas, or vacuum system, and include:
(1) The name of the gas/vacuum system or the
chemical symbol per NFPA 99: Table 5.1.11.
(2) The gas or vacuum system color code per
NFPA 99: Table 5.1.11.
(3) Where positive-pressure gas piping systems
operate at pressures other than the standard
gauge pressure in NFPA 99 Table 5.1.11, the
pipe labeling shall include the operating
pressure in addition to the nan\e of the gas.
[NFPA 99: 5.1.11.1.1]
1319.0 Joints. This section sets forth the require-
ments for pipe joint installation for positive-pressure
medical gas systems.
1319.1 Brazed joints shall be made using a brazing
alloy that exhibits a melting temperature in excess of
1,000°F (538°C) to retain the integrity of the piping
system in the event of fire exposure. [NFPA 99:
5.1.10.5.1.1]
Brazed tube joints shall be the socket type.
[NFPA 99: 5.1.10.5.1.2]
Filler metals shall bond with and be
metallurgically compatible with the base metals
being joined. [NFPA 99: 5.1.10.5.1.3]
Filler metals shall comply with ANSI/AWS
A.5.8, Specification for Brazing Filler Metal. [NFPA 99:
5.1.10.5.1.4]
Copper-to-copper joints shall be brazed using a
copper-phosphorus or copper-phosphorus-silver
brazing filler metal (BCuP series) without flux.
[NFPA 99: 5.1.10.5.1.5]
Flux shall only be used when brazing dissimilar
metals, such as copper and bronze or brass, using a
silver (BAg series) brazing filler material. [NFPA 99:
5.1.10.5.4.1]
Joints to be brazed in place shall be accessible for
necessary preparation, assembly, heating, filler
application, cooling, cleaning, and inspection. [NFPA
99: 5.1.10.5.1.7]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
208
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA I
NFPA I
nfpa'
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
1319.2 Tube ends shall be cut square using a sharp
tubing cutter to avoid deforming the tube. [NFPA 99:
5.1.10.5.2.1]
The cutting wheels on tubing cutters shall be
free from grease, oil, or other lubricant not suitable
for oxygen service. [NFPA 99: 5.1.10.5.2.2]
The cut ends of the tube shall be deburred with a
sharp, clean deburring tool, taking care to prevent
chips from entering the tube. [NFPA 99: 5.1.10.5.2.3]
1319.3 The interior surfaces of tubes, fittings, and
other components that are cleaned for oxygen service
shall be stored and handled to avoid contamination
prior to assembly and brazing. [NFPA 99: 5.1.10.5.3.1]
The exterior surfaces of tube ends shall be
cleaned prior to brazing to remove any surface
oxides. [NFPA 99: 5.1.10.5.3.2]
When cleaning the exterior surfaces of tube
ends, no matter shall be permitted to enter the tube.
[NFPA 99: 5.1.10.5.3.3]
If the interior surfaces of fitting sockets become
contaminated prior to brazing, they shall be
recleaned for oxygen in accordance with NFPA 99
5.1.10.5.3.10 and be cleaned for brazing with a clean,
oil-free wire brush. [NFPA 99: 5.1.10.5.3.4]
Clean, nonshedding, abrasive pads shall be used
to clean the exterior surfaces of tube ends. [NFPA 99:
5.1.10.5.3.5]
The use of steel wool or sand cloth shall be
prohibited. [NFPA 99: 5.1.10.5.3.6]
The cleaning process shall not result in grooving
of the surfaces to be joined. [NFPA 99: 5.1.10.5.3.7]
After being abraded, the surfaces shall be wiped
using a clean, lint-free white cloth. [NFPA 99;
5.1.10.5.3.8]
Tubes, fittings, valves, and other components
shall be visually examined internally before being
joined, to verify that they have not become
contaiivinated for oxygen service and that they are free
of obstructions or debris. [NFPA 99: 5.1.10.5.3.9]
The interior surfaces of tube ends, fittings, and
other components that were cleaned for oxygen
service by the manufacturer, but become
contaminated prior to being installed, shall be
permitted to be recleaned on-site by the installer by
thoroughly scrubbing the interior surfaces with a
clean, hot water-alkaline solution, such as sodium
carbonate or trisodium phosphate 450 g to 11 L (1 lb.
to 3 gal.) of potable water and thoroughly rinsing
them with clean, hot potable water. [NFPA 99:
5.1.10.5.3.10]
Other aqueous cleaning solutions shall be
permitted to be used for on-site recleaning permitted
in NFPA 99:5.1.10.5.3.10, provided that they are as
1319.2- 1319.6
recommended in CGA Pamphlet G-4.1, Cleaning
Equipment for Oxygen Service, and are listed in CGA
Pamphlet 02-DIR, Directory of Cleaning Agents for
Oxygen Service. [NFPA 99: 5.1.10.5.3.11]
Material that has become contaminated
internally and is not clean for oxygen service shall
not be installed. [NFPA 99: 5.1.10.5.3.12]
Joints shall be brazed within eight hours after
the surfaces are cleaned for brazing. [NFPA 99:
5.1.10.5.3.13]
1319.4 Flux shall only be used when brazing
dissimilar metals such as copper and bronze or brass,
using a silver (BAg series) brazing filler metal.
[NFPA 99: 5.1.10.5.4.1]
Surfaces shall be cleaned for brazing in
accordance with Section 1319.3. [NFPA 99: 5.1.10.5.4.2]
Flux shall be applied sparingly to minimize
contamination of the inside of the tube with flux.
[NFPA 99: 5.1.10.5.4.3]
The flux shall be applied and worked over the
cleaned surfaces to be brazed using a stiff bristle
brush to ensure complete coverage and wetting of
the surfaces with flux. [NFPA 99: 5.1.10.5.4.4]
Where possible, short sections of copper tube
shall be brazed onto the noncopper component and
the interior of the subassembly shall be cleaned of
flux prior to installation in the piping system. [NFPA
99: 5.1.10.5.4.5]
On joints DN20 (NFS 3/4) (7/8 in. O.D.) size
and smaller, flux-coated brazing rods shall be
permitted to be used in lieu of applying flux to the
surfaces being joined. [NFPA 99: 5.1.10.5.4.6]
1319.5 Tube ends shall be inserted fully into the
socket of the fitting. [NFPA 99: 5.1.10.5.6.1]
Where flux is permitted, the joint shall be heated
slowly until the flux has liquefied. [NFPA 99:
5.1.10.5.6.2]
After flux is liquefied, or where flux is not
permitted to be used, the joint shall be heated quickly
to the brazing temperature, taking care not to overheat
the joint. [NFPA 99: 5.1.10.5.6.3]
Techniques for heating the joint; applying the
brazing filler metal; and making horizontal,
vertical, and large-diameter joints shall be as stated
in sections on Applying Heat and Brazing and
Horizontal and Vertical Joints in Chapter VII,
Brazed Joints, in the CDA Copper Tube Handbook.
[NFPA 99: 5.1.10.5.6.4]
1 31 9.6 When being brazed, joints shall be continuously
purged with oil-free, dry nitrogen NF to prevent the
formation of copper oxide on the inside surfaces of
the joint. [NFPA 99: 5.1.10.5.5.1]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
209
1319.6-1320.2
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
The source of the purge gas shall be monitored,
and the installer shall be audibly alerted when the
source content is low. [NFPA 99: 5.1.10.5.5.2]
The purge gas flow rate shall be controlled by
the use of a pressure regulator and flow meter or
combination thereof. [NFPA 99: 5.1.10.5.5.3]
Pressure regulators alone shall not be used to
control purge gas flow rates. [NFPA 99: 5.1.10.5.5.4]
In order to ensure that all ambient air has been
removed from the pipeline prior to brazing, an
oxygen analyzer shall be used to verify the
effectiveness of the purge. The oxygen analyzer shall
read below 1 percent oxygen concentration before
brazing is to begin. [NFPA 99: 5.1.10.5.5.5]
During and after installation, openings in the
piping system shall be kept sealed to maintain a
nitrogen atmosphere within the piping to prevent
debris or other contaminants from entering the
system. [NFPA 99: 5.1.10.5.5.6]
While a joint is being brazed, a discharge
opening shall be provided on the opposite side of the
joint from where the purge gas is being introduced.
[NFPA 99: 5.1.10.5.5.7]
The flow of purge gas shall be maintained until
the joint is cool to the touch. [NFPA 99: 5.1.10.5.5.8]
After the joint has cooled, the purge discharge
opening shall be sealed to prevent contamination of
the inside of the tube and maintain the nitrogen
atmosphere within the piping system. [NFPA 99:
5.1.10.5.5.9]
The final connection of new piping to an
existing, in-use pipeline shall be permitted to be
made without the use of a nitrogen purge. [NFPA 99:
5.1.10.5.5.10]
After a final cormection in a positive-pressure
medical gas pipeline is made without a nitrogen
purge, an outlet in the immediate downstream zone
of the affected portions of both the new and existing
in-use piping shall be tested in accordance with
NFPA 99: 5.1.12.3.9, Final Tie-in Test. [NFPA 99:
5.1.10.5.5.11]
When using the autogenous orbital welding
process, joints shall be continuously purged inside
and outside with inert gas(es) in accordance with
the qualified welding procedure. [NFPA 99:
5.1.10.5.5.12]
1 31 9.7 After brazing, the outside of all joints shall
be cleaned by washing with water and a wire brush
to remove any residue and permit clear visual
inspection of the joint. [NFPA 99: 5.1.10.5.7.1]
Where flux has been used, the wash water shall
be hot. [NFPA 99: 5.1.10.5.7.2]
Each brazed joint shall be visually inspected
after cleaning the outside surfaces. [NFPA 99:
5.1.10.5.7.3]
Joints exhibiting the following conditions shall
not be permitted:
(1) Flux or flux residue (when flux or flux-
coated BAg series rods are used with
dissimilar metals).
(2) Base metal melting or erosion.
(3) Unmelted filler metal.
(4) Failure of the filler metal to be clearly visible
all the way around the joint at the interface
between the socket and the tube.
(5) Cracks in the tube or component.
(6) Cracks in the brazed filler metal.
(7) Failure of the joint to hold the test pressure
under the installer-performed initial
pressure test (1329.10) and standing pressure
test (Section 1329.11). [NFPA 99: 5.1.10.5.7.4 ]
Brazed joints that are identified as defective
under conditions 1319.7(2) or (5) shall be replaced.
[NFPA 99: 5.1.10.5.7.5]
Brazed joints that are identified as defective
under Sections 1319.7(1), (3), (4), (6), or (7) shall be
permitted to be repaired, except that no joint shall be
reheated more than once before being replaced.
[NFPA 99: 5.1.10.5.7.6]
1320.0 Valves - Requirements, Locations, and
Labeling.
1320.1 General Requirements. Shutoff valves
accessible to other than authorized personnel shall
be installed in valve boxes with frangible or
removable windows large enough to permit manual
operation of valves. [NFPA 99: 5.1.4.2.1]
Shutoff valves for use in certain areas, such as
psychiatric or pediatric, shall be permitted to be
seciired with the approval of the Authority Having
Jurisdiction to prevent inappropriate access. [NFPA
99: 5.1.4.2.2]
1320.1.1 Where valves are concealed in any
enclosure, the door or entry to the enclosure
shall be identified and color coded with the type
of gas service installed, as described in Section
1323.0. Enclosures shall be of sufficient size to
permit valve operation. Valve handles in the off
position shall prevent closure of the access panel
or door.
1320.2 In-line shutoff valves intended for use to
isolate piping for maintenance or modification shall
meet the following requirements:
(1) Be located in a restricted area.
(2) Be locked or latched open.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
210
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
(3) Be identified in accordance with Section
1323. [NFPA 99: 5.1.4.9.1]
1 320.3 Shutoff valves provided for the connection of
future piping shall meet the following requirements:
(1) Be locked in a restricted area.
(2) Be locked or latched closed.
(3) Be identified in accordance with Section
1323. [NFPA 99: 5.1.4.10]
1320.3.1 Future connection valves shall be
labeled as to gas content. [NFPA 99: 5.1.4.10.1]
1 320.3.2 Downstream piping shall be closed
with a brazed cap with tubing allowance for
cutting and rebrazing. [NFPA 99: 5.1.4.10.2]
1320.3.3 A zone valve shall be located
immediately outside each vital life-support,
critical care, and anesthetizing location in
each medical gas and/or vacuum line, and
located so as to be readily accessible in an
emergency. [NFPA 99: 5.1.4.8.7]
1320.3.4 All gas-delivery columns, hose reels,
ceiling tracks, control panels, pendants,
booms, or other special installations shall be
located downstream of the zone valve. [NFPA
99: 5.1.4.8.7.1]
1320.3.5 Zone valves shall be so arranged that
shutting off the supply of gas to any one
operating room or anesthetizing location will
not affect the others. [NFPA 99: 5.1.4.8.7.2]
1320.4 Source Valve. A shutoff valve shall be
placed at the immediate connection of each source
system to the distribution piping to permit the entire
source, including all accessory devices (such as hair
dryers, final line regulators, etc.), to be isolated from
the facility. [NFPA 99: 5.1.4.4]
1320.4.1 The source valve shall be located in the
immediate vicinity of the source equipment.
[NFPA 99: 5.1.4.4.1]
1320.4.2 The source valve shall be labeled in
accordance with Section 1323.0, Source Valve for
the (Source Name). [NFPA 99: 5.1.4.4.2, 5.1.11.2.3]
1 320.5 Main Valve. A shutoff valve shall be provided
in the main supply line inside of the building, except
where one or more of the following conditions exist:
(1) The source and source valve are located
inside the building served.
(2) The source system is physically mounted to
the waU of the building served and the pipe-
line enters the building in the immediate
vicinity of the source valve. [NFPA 99: 5.1.4.5]
1320.5.1 The main line valve shall be located to
permit access by authorized personnel only (i.e..
1320.2-1321.2
by locating above a ceiling or behind a locked
access door). [NFPA 99: 5.1.4.5.1]
1320.5.2 The main line valve shall be located on
the facility side of the source valve and outside of
the source room, enclosure, or where the main
line first enters the building. [NFPA 99: 5.1.4.5.2]
1320.5.3 The main line shall be labeled in
accordance with Section 1323.0. [NFPA 99:
5.1.4.5.3 and 5.1.11.2.4]
1320.6 Riser Valve. Each riser siipplied from the
main line shall be provided with a shutoff valve
adjacent to the riser connection. Riser valves shall be
permitted to be located above ceilings, but shall
remain accessible and not be obstructed. [NFPA 99:
5.1.4.6,5.1.4.6.1]
1320.7 Zone Valve. All station outlets/inlets shall
be supplied through a zone valve as follows:
(1) The zone valve shall be placed such that a
wall intervenes between the valve and
outlets/inlets that it controls.
(2) The zone valve shall serve only outlets /inlets
located on that same story. [NFPA 99: 5.1.4.8]
1320.7.1 Zone valves shall be readily operable
from a standing position in the corridor on the
same floor they serve. [NFPA 99: 5.1.4.8.1]
1 320.7.2 Zone valves shall be so arranged that
shutting off the supply of medical gas or
vacuum to one zone will not affect the supply of
medical gas or vacuum to another zone or the
rest of the system. [NFPA 99: 5.1.4.8.2]
1320.8 Service Valves. Service valves shall be
placed in the branch piping prior to any zone valve
box assembly on that branch. [NFPA 99: 5.1.4.7.2]
1320.8.1 Only one service valve shall be
required for each branch off of a riser regardless
of how many zone valve boxes are installed on
that lateral. [NFPA 99: 5.1.4.7.1]
1320.8.2 Service valves shall be installed to
allow servicing or modification of lateral branch
piping from a main or riser without shutting
down the entire main, riser, or facility. [NFPA 99:
5.1.4.7]
1321.0 Pressure-Regulating Equipment.
1321.1 Pressure-regulating equipment shall be
installed in the supply main upstream of the final
line-pressure valve. Where multiple piping systems
for the same gas at different operating pressures are
required, separate pressure-regulating equipment,
relief valves, and source shutoff valves shall be
provided for each pressure.
1321.2 Each central supply system shall have a
pressure-relief valve set at fifty (50) percent above
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
211
1321.2-1323.4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
normal line pressure, installed downstream of the
pressure regulator and upstream of any shutoff
valve. This pressure-relief valve shall be permitted to
be set at a higher pressure, provided another
pressure-relief valve set at 50 percent above normal
line pressure is installed in the main supply line.
1321.2.1 All pressure-relief valves shall close
automatically when excess pressure has been
released.
1321.2.2 Pressure-relief valves set at 50 percent
shall be vented to the outside from all gas
systems, except medical air, or if the total
capacity of the supply system is in excess of
3,000 feet^ (85 m^) of gas.
1321.2.3 Pressure-relief valves shall be of brass
or bronze and specially designed for the gas
service involved.
1321.2.4 A pressure-relief valve shall not be
isolated from its intended use by any valve.
1321.3 Pressure Gauges.
Pressure and vacuum indicators shall be readable
from a standing position. Pressure/ vacuum
indicators shall be provided at the following
locations, as a minimum:
(1) Adjacent to the alarm-initiating device for
source main-line pressure and vacuum alarms
in the master alarm system.
(2) At or in area alarm panels to indicate the
pressure /vacuum at the alarm activating
device for each system that is monitored by
the panel.
(3) On the station outlet/inlet side of zone
valves. [NFPA 99: 5.1.8.2.1, 5.1.8.2.2]
1322.0 Station Outlets/Inlets.
Station outlets and inlets shall be installed in strict
accordance with the manufacturers' instructions.
1322.1 After installation of the piping, but before
installation of the station outlets /inlets and other
medical gas and medical gas system components
(e.g., pressure-actuating switches for alarms,
manifolds, pressure gauges, or pressure relief
valves), the line shall be blown clear by means of oil-
free, dry nitrogen.
1323.0 Labeling and Identification. The gas content
of medical gas piping systems shall be readily
identifiable by appropriate labeling with the name
and pressure contained. Such labeling shall be by
means of metal tags, stenciling, stamping, or
adhesive markers, in a manner that is not readily
removable. Where supplementary color identification
of piping is used, it shall be in accordance with the
gases and colors indicated in CGA Pamphlet C-9,
Standard Color-Marking of Compressed Cylinders
Intended for Medical Gas Use, See Table 13-1.
1323.1 Piping shall be labeled by stenciling or
adhesive markers that identify the medical gas,
support gas, or vacuum system and include:
(1) The name of the gas/vacuum system or the
chemical symbol per NFPA 99: Table 5.1.11.
(2) The gas or vacuum system color code per
NFPA 99 Table 5.1.11.
(3) Where positive-pressure gas piping systems
operate at pressures other than the standard
gauge in NFPA 99 Table 5.1.11, the pipe labeling
shall include the operating pressure in addition
to the name of the gas. [NFPA 99: 5.1.11.1.1]
Pipe labels shall be located as follows:
(1) At intervals of not more than 20 ft (6,100 mm).
(2) At least once in or above every room.
(3) On both sides of walls or partitions penetrated
by the piping.
(4) At least once in every story height traversed
by risers. [NFPA 99: 5.1.11.1.2]
1 323.2 Shutoff valves shall be identified as follows:
(1) The name or chemical symbol for the
specific medical gas or vacuum system.
(2) The room or areas served.
(3) A caution to not close or open valve except
in emergency. [NFPA 99: 5.1.11.2.1]
1 323.3 Station outlets and inlets shall be identified as
to the name or chemical symbol for the specific
medical gas or vacuum provided. [NFPA 99 :
5.1.11.3.1]
1323.4 The shutoff valves described in Sections
1320.4, 1320.5, and 1320.6 shall be labeled to reflect
the rooms that are controlled by such valves.
Labeling shall be kept current from initial
construction through acceptance. Valves shall be
labeled in substance as follows:
In-line shutoff valves shall be labeled in substance
as foUows:
CAUTION
(NAME OF MEDICAL GAS) VALVE
DO NOT CLOSE EXCEPT IN EMERGENCY
THIS VALVE CONTROLS SUPPLY TO...
Source valves shall be labeled in substance as
follows:
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA,
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
212
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
SOURCE VALVE
FOR THE (SOURCE NAME).
Main line valves shall be labeled in substance as
follows:
MAIN LINE VALVE FOR THE
(GASA^ACUUM NAME) SERVING THE
(NAME OF BUILDING).
Riser valve(s) shall be labeled in substance as
follows:
RISER FOR THE (GAS/VACUUM NAME)
SERVING (NAME OF THE AREA/BUILDING
SERVED BY THE PARTICULAR RISER).
Service valve(s) shall be labeled in substance as
follows:
SERVICE VALVE FOR THE
(GAS/VACUUM NAME) SERVING
(NAME OF THE AREA/BUILDING
SERVED BY THE PARTICULAR VALVE).
[NFPA 99: 5.1.11.2.3-6]
1324.0 Alarms. All master, area, and local alarm
systems used for medical gas and vacuum systems
shall include the following:
(1) Separate visual indicators for each condition
monitored, except as permitted for local
alarms that are displayed on master alarm
panels.
(2) Visual indicators that remain in alarm until
the situation that has caused the alarm is
resolved.
(3) A cancelable audible indication of each
alarm condition that produces a sound
with a minimum level of 80 dBA at 3 feet
(920 mm).
(4) A means to visually identify a lamp or LED
failure.
(5) Visual and audible indication that the
wiring to an alarm initiating device is
disconnected.
(6) Labeling of each indicator, indicating the
condition monitored.
(7) Labeling of each alarm panel for its area of
surveillance.
(8) Re-initiation of the audible signal if another
alarm condition occurs while the audible
alarm is silenced.
(9) Power for master and area alarms from the
life safety branch of the emergency electrical
system as described in Chapter 4, Electrical
Systems.
1323.4-1325.1
(10) Power for local alarms, dew point sensors,
and carbon monoxide sensors permitted to
be from the same essential electrical branch
as is used to power the air compressor
system.
(11) Wiring from switches or sensors that is
supervised or protected as required by
Section 517.30(C)(3) of NFPA 70, National
Electrical Code, for emergency system circuits.
(12) Assurance by the responsible authority of
the facility that the labeling of alarms, where
room numbers or designations are used, is
accurate and up-to-date.
(13) Provisions for automatic restart after a power
loss of 10 seconds (e.g., during generator
startup) without giving false signals or
requiring manual reset. [NFPA 99: 5.1.9.1(1),
(3), (4), (5), (6), (7)]
1324.1 Fimctioning of all alarm components shall be
verified in accordance with testing and monitoring
requirements of the manufacturer and the Authority
Having Jurisdiction.
1325.0 Medical Air System.
compressors shall be installed
Medical air
in a well-lit,
ventilated, and clean location and shall be accessible.
The location shall be provided with drainage
facilities. The medical air compressor area shall be
located separately from medical gas cylinder system
sources, and shall be readily accessible for
maintenance.
1325.1 Medical air compressors shall be sufficient to
serve the peak calculated demand with the largest
single compressor out of service. In no case shall
there be fewer than 2 (two) compressors. [NFPA 99:
5.1.3.5.11.2]
Medical air compressor systems shall consist of the
following:
(1) Components complying with NFPA 99:
5.1.3.5.4 through NFPA 99: 5.1.3.5.10, arranged
per NFPA 99: 5.1.3.5.11.
(2) An automatic means to prevent backflow
from all on-cycle compressors through all
off -cycle compressors.
(3) A manual shutoff valve to isolate each
compressor from the centrally piped system
and from other compressors for mairitenance
or repair without loss of pressure in the system.
(4) Intake filter-mufflers of the dry type.
(5) Pressure relief valves set at 50 percent above
line pressure.
(6) Piping between the compressor and the source
shutoff valve compatible with oxygen that
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
213
1325.1 -1326.1
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
"nfpa
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
does not contribute to contaminant levels.
[NFPA 99: 5.1.3.5.3.2]
(7) Except as defined in NFPA 99: 5.1.3.5.3.2(1)
through NFPA 99: 5.1.3.5.3.2(6), materials
and devices used between the medical air
intake and the medical air source valve shall
be permitted to be of any design or construc-
tion appropriate for the service, as determined
by the manufacturer. [NFPA 99: 5.1.3.5.3.2]
1 325.2 The medical air compressors shall draw their
air from a source of clean air located where no
contamination is anticipated from engine exhausts,
fuel storage vents, medical-surgical vacuum system
discharges, particulate matter, or odor of any type.
[NFPA 99: 5.1.3.5.13.1]
1325.3 Compressor intake piping shall be hard-
drawn seamless copper, and one of the following:
(1) ASTM B 819, Standard Specification for
Seamless Copper Tube for medical Gas
Systems, medical gas tube.
(2) ASTM B 88, Standard Specification for
Seamless Copper Water Tube, water tube
(Type K or L).
(3) ASTM B 280, Standard Specification for Seam-
less Copper Tubing for Air Conditioning and
Refrigeration Field Service, 280ACR tube.
[NFPA 99: 5.1.3.5.13.4]
The compressor air intake shall be located
outdoors above roof level, at a minimum distance of
10 feet (3,050 mm) from any door, window, exhaust,
other intake, or opening in the building and a
minimum distance of 6,100 mm (20 feet) above the
ground. [NFPA 99: 5.1.3.5.13.2]
If an air source equal to or better than outside air
(e.g., air already filtered for use in operating room
ventilating systems) is available, it shall be permitted
to be used for the medical air compressors with the
following provisions:
(1) This alternate source of supply air shall be
available on a continuous 24-hours-per-day,
7-days-per-week basis.
(2) Ventilating systems having fans with motors
or drive belts located in the air stream shall
not be used as a source of medical air intake.
[NFPA 99: 5.1.3.5.13.3]
Air intakes for separate compressors shall be
permitted to be joined together to one common
intake where the following conditions are met:
(1) The common intake is sized to minimize
back pressure in accordance with the
manufacturer's recommendations
(2) Each compressor can be isolated by manual
or check valve, blind flange, or tube cap to
prevent open inlet piping when compressors
are removed from service and consequent
backflow of room air into the other com-
pressor(s). [NFPA 99: 5.1.3.5.13.5]
1325.3.1 Each medical air compressor shall have
an isolation valve installed so that shutting off or
failure of the largest unit will not affect the
operation of the other unit(s).
1325.4 Drains shall be installed on dryers,
aftercoolers, separators, and receivers.
1325.5 Medical air receivers shall be provided with
proper valves to allow the flow of compressed air to
enter and exit out of separator receive ports during
normal operation and allow the receiver to be by-
passed during service, without shutting down the
medical air system. [NFPA 99: 5.1.3.5.11.4]
1325.6 Medical Air Receivers. Receivers for
medical air shall meet the following requirements:
(1) Be made of corrosion-resistant materials or
otherwise be made corrosion resistant.
(2) Comply with Section VIII, Unfired Pressure
Vessels, of the ASME Boiler and Pressure
Vessel Code.
(3) Be equipped with a pressure-relief valve,
automatic drain, manual drain, sight glass,
and pressure indicator.
(4) Be of a capacity sufficient to prevent the
compressor from short cycling. [NFPA 99:
5.1.3.5.6]
Piping within compressor systems upstream
of the source shutoff valve shall comply with
Sections 1316 and 1319, except that stainless steel
shall be permitted to be used as a piping
material.
1326.0 l\/ledical Vacuum Pump System. The
vacuum plant shall be installed in a well-lit,
ventilated, and clean location with ample accessibility.
The location shall be provided with drainage facilities.
The vacuum plant, when installed as a source, shall be
located separately from other medical vacuum system
sources, and shall be readily accessible for
m.aintenance.
1326.1 Medical-surgical vacuum sources shall
consist of the following:
(1) Two or more vacuum pumps sufficient to
serve the peak calculated demand with the
largest single vacuum pump out of service.
(2) An automatic means to prevent backflow
from any on-cycle vacuum pumps through
any off-cycle vacuum pumps.
(3) A shutoff valve or other isolation means to
isolate each vacuum pump from the
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA-
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
214
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
centrally piped system and other vacuum
pumps for maintenance or repair without
loss of vacuum in the system.
(4) A vacuum receiver.
(5) Piping between the vacuum pump(s),
discharge(s), receiver(s), and the vacuum
source shutoff valve shall be in accordance
with 5.1.10.2, except that stainless, galvanized,
or black steel pipe shall be permitted to be used.
(6) Except as defined in NFPA 99: 5.1.3.6.1.2(1)
through NFPA 99: 5.1.3.6.1.2(5), materials
and devices used between the medical
vacuum exhaust and the medical vacuum
source shall be permitted to be of any design
or construction appropriate for the service,
as determined by the manufacturer. [NFPA
99: 5.1.3.6.1.2(1), (2), (3), (4), (5), (6)]
1326.1.1 Additional pumps shall automatically
activate when the pumps in operation are
incapable of adequately maintaining the
required vacuum.
Automatic or manual alternation of pumps
shall allow division of operating time. If automatic
alternation of pum^ps is not provided, the facility
staff shall arrange a schedule for manual
alternation. [NFPA 99: 5.1.3.6.6.1, 5.1.3.6.6.2]
1326.2 The medical-surgical vacuum pumps shall
exhaust in a manner and location that will minimize
the hazards of noise and contamination to the facility
and its environment.
The exhaust shall be located as follows:
(1) Outdoors.
(2) At least 10 feet (3,050 mm) from any door,
window, air intake, or other openings in
buildings.
(3) At a level different from air intakes.
(4) Where prevailing w^inds, adjacent buildings,
topography, or other influences that would
not divert the exhaust into occupied areas or
prevent dispersion of the exhaust.
The end of the exhaust shall be turned down
and screened or otherwise be protected against
the entry of vermin, debris, or precipitation by
screening fabricated or composed of a non-
corroding material.
The exhaust shall be piped of materials
approved for medical-surgical vacuum piping
under Section 1316.3 (Vacuum tubes).
The exhaust shall be free of dips and loops
that might trap condensate or oil. Where such
low points are unavoidable, a drip leg and
valved drain shall be installed. [NFPA 99:
5.1.3.6.7.1-5.1.3.6.7.5]
1326.1 -1327.1
1326.2.1 Vacuum exhausts from multiple
pumps shall be permitted to be joined together
to one common exhaust where the following
conditions are met:
(1) The common exhaust is sized to
minimize back-pressure in accordance
with the pump manufacturer's recom-
mendations.
(2) Each pump can be isolated by manual
or check valve, blind flange, or tube cap
to prevent open exhaust piping when
pumps are removed for service and
consequent flow of exhaust air into the
room. [NFPA 99: 5.1.3.6.7.6]
1326.3 Receivers for vacuum shall meet the
following requirements:
(1) Be made of ferrous and/or nonferrous
materials.
(2) Comply with Section VIII, Unfired Pressure
Vessels, of the ASME Boiler and Pressure
Vessel Code.
(3) Be capable of withstanding a gauge pressure
of 415 kPa (60 psi) and 29.9 inch (760 mm)
gauge HgV.
(4) Be equipped with a manual drain.
(5) Be of a capacity based on the technology of
the pumps. [NFPA 99: 5.1.3.6.3]
1326.4 Piping between vacmm:i pumps, discharges,
receivers, and the vacuum main line valve shall be in
accordance with Section 1316.1, except that steel pipe
shall be permitted to be either black or galvanized.
1 326.5 Drains shall be installed and terminate in an
approved location.
1327.0 Testing and Inspection.
1327.1 Inspection and testing shall be performed on
all-new^ piped gas systems, additions, renovations,
temporary installations, or repaired systems, to
ensure the facility, by a documented procedure, that
all applicable provisions of this document have been
adhered to and system integrity has been achieved
or maintained. [NFPA 99: 5.1.12.1.1.]
1327.1.1 Tests and inspections required by this
section shall not be interpreted to conflict with
the requirements of NFPA 99 Standard for Health
Care Facilities. Final certification or verification
shall require the completion of all tests and
inspections required by Sections 4-3.4.1.1, 4-
3.4.1.2, and 4-3.4.1.3 of NFPA 99 Standard for
Health Care Facilities. For requirements of the
portions of medical gas and medical vacuum
systems testing and inspection not addressed in
this chapter or medical gas and medical vacuum
systems testing and inspection beyond the scope
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA.
NFPA
nfpa"
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
215
1327.1 -1327.9
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
of this chapter, refer to NFPA 99 Standard for
Health Care Facilities.
1327.2 All systems that are breached and com-
ponents that are subject to additions, renovations, or
replacement (e.g., new gas sources: bulk, manifolds,
compressors, dryers, alarms) shall be inspected and
appropriately tested. [NFPA 99: 5.1.12.1.3]
1327.2.1 Systems shall be deemed breached at
the point of pipeline intrusion by physical
separation or by system component removal,
replacement, or addition.
Breached portions of the systems subject to
inspection and testing shall be confined to only
the specific altered zone and components in the
immediate zone or area that is located
upstream for vacuum systems and down-
stream for pressure gases at the point or area of
intrusion. [NFPA 99: 5.1.12.1.4, 5.1.12.1.5]
1327.3 Advance Notice. It shall be the duty of the
person doing the work authorized by the permit to
notify the Authority Having Jurisdiction, orally or in
writing, that said work is ready for inspection. Such
notification shall be given not less than twenty-four
(24) hours before the work is to be inspected.
1327.4 Responsibility. The equipment, material,
and labor necessary for inspection and testing shall
be furnished by the permit holder or by the person
w^ho is requiring the inspection.
1327.5 Testing. The test shall be conducted in the
presence of the Authority Having Jurisdiction or a
duly appointed representative.
1327.6 Retesting. If the Authority Having
Jurisdiction finds that the work does not pass tests,
necessary corrections shall be made and the work
shall then be resubmitted for test or inspection.
1327.7 Initial Pressure Test - Piped Gas Systems.
Before attachment of system components (e.g.,
pressure-actuating switches for alarms, manifolds,
pressure gauges, or pressure-relief valves), but after
installation of the station outlets and inlets, with test
caps in place, each section of the piping system shall
be subjected to a test pressure of one and a one-half
(1-1/2) times the working pressure [minimum one
hundred-fifty (150) psig (1 Mpa gauge)] with oil-free
dry nitrogen. This test pressure shall be maintained
until each joint has been examined for leakage by
means of soapy water or other equally effective
means of leak detection safe for use with oxygen. The
source shutoff valve shall be closed. Leaks, if any,
shall be located, repaired, and retested in accordance
with this paragraph. [NFPA 99: 5.1.12.2.3.7]
1327.8 Cross-Connection Test - Piped Gas
Systems. It shall be determined that no cross-
connections exist between the various medical gas
and vacuum piping systems. [NFPA 99: 5.1.12.2.4]
All piping systems shall be reduced to
atmospheric pressure. [NFPA 99: 5.1.12.2.4.1]
Sources of test gas shaU be disconnected from aU
piping systems except for the one system being tested.
[NFPA 99: 5.1.12.2.4.2]
The system under test shall be charged with
oil-free, dry nitrogen NF to a gauge pressure of
50 psi (345 kPa). [NFPA 99: 5.1.12.2.4.3]
After the installation of the individual faceplates
with appropriate adapters matching outlet/inlet
labels, each individual outlet/ inlet in each installed
medical gas and vacuum piping system shall be
checked to determine that the test gas is being
dispensed only from the piping system being tested.
[NFPA 99: 5.1.12.2.4.4]
1327.8.1 The source of test gas shall be
disconnected, and the system tested shall be
reduced to atmospheric pressure. The cross-
connection test referenced in NFPA 99
5.1.12.2.4 shall be repeated for each installed
medical gas and vacuum piping system.
[NFPA 99: 5.1.12.2.4.1, 5.1.12.2.4.5]
1327.8.2 Where a m^edical vacuum system is
installed, the cross-connection testing shall
include that piped vacuum system with all
medical gas-piping systems.
1327.8.3 All medical-surgical vacuum systems
shall be in operation so that these vacuum
systems are tested at the same time the medical
gas systems are tested. The proper labeling and
identification of system outlets /inlets shall be
confirmed during these tests. [NFPA 99:
5.1.12.2.4.6]
1327.9 Final Testing Standing Pressure Test -
Piped Gas Systems. After successful completion of
the initial pressure tests imder Section 1327.7, medical
gas distribution piping shall be subject to a standing
pressure test. [NFPA 99: 5.1.12.2.6]
Tests shall be conducted after the final
installation of station outlet valve bodies, face plates,
and other distribution system components (e.g.,
pressure alarm devices, pressure indicators, line
pressure-relief valves, manufactured assemblies,
hose, etc.). [NFPA 99: 5.1.12.2.6.1]
The source valve shall be closed during this test.
[NFPA 99: 5.1.12.2.6.2]
The piping systems shall be subjected to a 24-hour
standing pressure test using oil-free, dry nitrogen NF.
[NFPA 99: 5.1.12.2.6.3]
Test pressures shall be 20 percent above the
normal system operating line pressure. [NFPA 99:
5.1.12.2.6.4]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA,
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
216
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
'NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
1327.9.1 After the piping system is filled with
test gas, the supply valve and all outlets shall be
closed and the source of test gas disconnected.
Tests shall be conducted after the final
installation of station outlet valve bodies, face
plates, and other distribution system
components (e.g., pressure alarm devices,
pressure indicators, line pressure-relief valves,
manufactured assemblies, hose, etc.). [NFPA 99:
5.1.12.2.6.1]
The source valve shall be closed during this test.
[NFPA 99: 5.1.12.2.6.2]
The piping systems shall be subjected to a
24-hour standing pressure test using oil-free,
dry nitrogen NF. [NFPA 99: 5.1.12.2.6.3]
Test pressures shall be 20 percent above
the normal system operating line pressure.
[NFPA 99: 5.1.12.2.6.4]
Leaks, if any, shall be located, repaired (if
permitted), or replaced (if required), and
retested. [NFPA 99: 5.1.12.2.6.6]
At the conclusion of the tests, there shall be
no change in the test pressure other than that
attributed to changes of ambient temperature.
[NFPA 99: 5.1.12.2.6.5]
1327.10 Initial Pressure Test - Piped Vacuum
Systems. Each section of the piping in medical gas
and vacuum systems shall be pressure-tested. [NFPA
99: 5.1.12.2.3.1]
Initial pressure tests shall be conducted as follows:
(1) After installation of station outlets /inlets
rough-in assemblies. Test caps shall be
permitted to be used.
(2) Prior to the installation of components of the
distribution piping system that would be
damaged by the test pressure (e.g.,
pressure/vacuum alarm devices, pres-
sure/vacuum indicators, line pressure-relief
valves, manufactured assemblies with
flexible hose, etc.). [NFPA 99: 5.1.12.2.3.2]
The source shutoff valve shall remain closed
during these tests. [NFPA 99: 5.1.12.2.3.3]
The test pressure for pressure gases shall be
1.5 times the system working pressure but
not less than a gauge pressure of 150 psi
(1,035 kPa). [NFPA 99: 5.1.12.2.3.4]
The test pressure for vacuum shall be not
less than a gauge pressure of 60 psi (415 kPa).
[NFPA 99: 5.1.12.2.3.5]
The test pressure shall be maintained until
each joint has been examined for leakage by
means of soapy water or other equally effective
means of leak detection that is safe for use with
oxygen. [NFPA 99: 5.1.12.2.3.6]
Leaks, if any, shall be located, repaired (if
permitted), replaced (if required), and retested.
[NFPA 99: 5.1.12.2.3.7]
1327.9-1327.13
1327.11 Standing Pressure Test - Piped Vacuum
Systems. After successful completion of the initial
pressure tests under Section 1327.10, vacuum
distribution piping shall be subjected to a standing
vacuum test. [NFPA 99: 5.1.12.2.7]
Tests shall be conducted after installation of all
components of the vacuum system. [NFPA 99:
5.1.12.2.7.1]
The piping systems shall be subjected to a 24-
hour standing vacuum test. [NFPA 99: 5.1.12.2.7.2]
Test pressure shall be between 12 inch (300 mm)
gauge HgV and full vacuum. [NFPA 99: 5.1.12.2.7.3]
During the test, the source of test vacuum shall
be discorvnected from the piping system. [NFPA 99:
5.1.12.2.7.4]
At the conclusion of the test, there shall be no
change in the vacuum other than that attributed to
changes of ambient temperature, as permitted in the
following: [NFPA 99: 5.1.12.2.7.5]
Test vacuum changes due to expansion or
contraction shall be permitted to be determined by
means of the following pressure temperature
relationship:
(1) The calculated final absolute pressure equals
the initial absolute pressure times the final
absolute temperature, divided by the initial
absolute temperature.
(2) Absolute pressure is the gauge pressure
reading plus 14.7 psi (101.4 kPa).
(3) Absolute temperature is the temperature
reading plus 460°F (238°C).
(4) The final allowable gauge pressure reading
equals the final allowable absolute pressure
minus a gauge pressure of 14.7 psi (101.4
kPa). [NFPA 99: 5.1.12.2.7.6]
Leaks, if any, shall be located, repaired (if permitted),
or replaced (if required), and retested. [NFPA 99:
5.1.12.2.7.7]
1327.12 Corrections. Notices of correction or
violation shall be written by the Authority Having
Jurisdiction and may be posted at the site of the work
or mailed or delivered to the permittee or an
authorized representative. Refusal or failure to
comply with any such notice or order within ten (10)
days of receipt thereof shall be considered a violation
of this code, and shall be subject to the penalties set
forth elsewhere in this code for violations.
1327.13 Approval. Upon satisfactory completion of
all tests and certification of the medical gas and
medical vacuum systems, a certificate of approval
shall be issued by the Authority Having Jurisdiction
to the permittee.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA"
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
217
1327.14-1328.4
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
1327.14 Covering or Use. No medical gas or medical
vacuum system or part thereof shall be covered,
concealed, or put into use until it has been tested,
inspected, and accepted as required in this code.
1327.15 Uncovering. Any medical gas and vacuum
system or part thereof that is covered or concealed
before testing and inspected as required in this code
shall be uncovered for inspection, after notice to
uncover the work has been issued to the permittee or
his authorized representative by the Authority
Having Jurisdiction.
1328.0 System Certification.
1328.1 Prior to any medical gas system being placed
in service, each and every system shall be certified,
as described in Section 1328.2.
1328.1.1 Verification tests shall be performed
only after all tests required in Section 1327.0,
Installer-Performed Tests, have been completed.
[NFPA 99: 5.1.12.3.1.1]
Testing shall be conducted by a party
technically competent and experienced in the
field of medical gas and vacuum pipeline testing
and meeting the requirements of ANSI/ASSE
Standard 6030, Medical Gas Verifiers Professional
Qualifications Standard. [NFPA 99: 5.1.12.3.1.3]
Testing shall be performed by a party other
than the installing contractor. [NFPA 99:
5.1.12.3.1.4]
When systems have been installed by in-
house personnel, testing shall be permitted by
personnel of that organization who meet the
requirements of this section. [NFPA 99:
5.1.12.3.1.5]
1 328.2 Certification tests, verified and attested to by
the certification agency, shall include the following:
1328.2.1 Verifying compliance with the
. installation requirements.
1328.2.2 Testing and checking for leakage,
correct zoning, and identification of control
valves.
1328.2.3 Checking for identification and
labeling of pipelines, station outlets, and control
valves.
1 328.2.4 Testing for cross-connection, flow rate,
system pressure drop, and system performance.
1328.2.5 Functional testing of pressure relief
valves and safety valves.
1328.2.6 Functional testing of all sources of
supply.
1328.2.7 Functional testing of alarm systems,
including accuracy of system components.
1328.2.8 Purge flushing of system and filling
with specific source gases.
1328.2.9 Testing for purity and cleanliness of
source gases.
1328.2.10 Testing for specific gas identity at each
station outlet.
1328.3 The inspection and testing reports shall be
submitted directly to the party that contracted for the
testing, who shall submit the report through channels
to the responsible facility authority and any others that
are required. [NFPA 99: 5.1.12.1.6]
Reports shall contain detailed listings of all
findings and results. [NFPA 99: 5.1.12.1.7]
1328.4 A report that includes at least the specific
items mentioned in Section 1328.2 and all other
information required by NFPA 99 Standard for Health
Care Facilities shall be delivered to the Authority
Having Jurisdiction prior to acceptance of the system.
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
218
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
Table 13-1
TABLE 13-1 [NFPA 99 TABLE 5.1.11]
Standard Designation Colors and Operating Pressures for Gas and Vacuum Systems
Gas Service
Abbreviated
Name
Colors
(Background/Text)
Standard
Gauge Pressure
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Medical air
Carbon dioxide
Med Air
CO.
Helium
Nitrogen
Nitrous oxide
He
Nn
NoO
Yellow /black
Gray /black or
gray /white
Brown /white
Black/white
Blue/ white
345-380 kPa
(50-55 psi)
345-380 kPa
(50-55 psi)
345-380 kPa
(50-55 psi)
1,100-1,275 kPa
(160-185 psi)
345-380 kPa
(50-55 psi)
Oxygen
Oxygen /carbon .
dioxide mixture
Medical-surgical vacuum
Waste anesthetic
gas disposal
Other mixtures
O2
O2/CO2 n
(nis%ofC02)
Med Vac
WAGD
Gas A%/ Gas B%
Green /white or
white /green
Green/white
White/black
Violet/white
Colors as above
Major gas for background/
minor gas for text
345-380 kPa
(50-55 psi)
345-380 kPa
(50-55 psi)
360 mm to 760 mm
(15 in. to 30 in. HgV)
Varies with system type
None
Nonmedical air
(level 3 gas-powered device)
Nomnedical and Level 3
vacuum
Laboratory air
Laboratory vacuum
Instrument air
Yellow-and-white diagonal
stripe /black
White-and-black diagonal
stripe /black boxed
Yellow-and-white
checkerboard /black
White-and-black
checkerboard /black boxed
Red/white
None
None
None
None
1,100-1,275 kPa
(160-185 psi)
219
Table 13-2 -Table 13-3
UNIFORM PLUMBING CODE
TABLE 13-2
Minimum Flow Rates
Oxygen
Nitrous Oxide
Medical Compressed Air
Nitrogen
Vacuum
Carbon Dioxide
Helium
.71 CFM per outlet' (20 LPM)
.71 CFM per outlet (20 LPM)
.71 CFM per outlef (20 LPM)
15 CFM (0.42 mVmin.) free air per outlet
1 SCFM (0.03 smVmin.) per inlet'-
.71 CFM per outlef (20 LPM)
.71 CFM per outlet (20 LPM)
Any room designed for a permanently located respiratory ventilator or anesthesia machine shall have an
outlet capable of a flow rate of 180 LPM (6.36 CFM) at the station outlet.
For testing and certification purposes, individual station inlets shall be capable of a flow rate of 3 SCFM,
while maintaining a system pressure of not less than 12 inches (305 mm) at the nearest adjacent vacuum
inlet.
TABLE 13-3
l\/linjmum Outlets/Inlets per Station
Location
Oxygen Medical Medical Nitrous Nitrogen Helium Carbon
Vacuum Air Oxide Dioxide
Patient rooms for
medical / surgical,
obstetrics, and pediatrics
Examination / treatment
for nursing units
Intensive care (all)
Nursery'
General operating rooms
Cystoscopic and invasive
special procedures
Recovery delivery and
labor /delivery/
recovery rooms^
Labor rooms
First aid and emergency
treatment^
Autopsy
Anesthesia workroom
1/bed
1/bed
1/bed
1/bed
1/bed
—
3/bed
3/bed
2/bed
2/bed
2/bed
1/bed
2/room
3 /room*
2/room
2 /room
3 /room"
2/room
2/bed
2/bed
1/bed
2/room
3 /room*
1/room
1/bed
1/bed
1/bed
1/bed
1/bed*
1/bed
— 1 / station 1 / station
1 / station — 1 / station
1/room 1/room^
Includes pediatric nursery.
Includes obstetric recovery.
Emergency trauma rooms used for surgical procedures shall be classified as general operating rooms.
Vacuum inlets required are in addition to any inlets used as part of a scavenging system for removal of
anesthetizing gases.
220
HEALTH CARE FACILITIES AND
MEDICAL GAS AND VACUUM SYSTEMS
Table 13-4 -Table 13-5
TABLE 13-4
System
Sizing - Flow Requirements for Station Inlet/Outlef
Minimum Permissible
Number of
Inlet/Outlet Terminal
Units per Facility
Diversity Percentage
of Average Flow per
Inlet/Outlet Terminal Units
System Flow'
SCFM (liters/minute)
All Pressurized Vacuum
Medical Gas Systems Systems
1-10
100%
Actual Demand See
11-25
75%
7.0 (200) Table
26-50
50%
13.1 (375) 13-5
51-100
50%
17.5 (500)
Flow rates of station inlets /outlets per Table 13-2.
The minimum system flow is the average inlet/outlet flow times the number of station inlets /outlets times the diversity
percentage.
TABLE 13-5
Outlet Rating for Vacuum Piping Systems
Free- Air Allowance,
Expressed as CFM (LPM)
at 1 Atmosphere
Zone Allowances
Corridors-Risers
Main Supply Line-Valves
Location of Medical-Surgical
Vacuum Outlets
Per Room
Per Outlet
Simultaneous
Usage,
Factor Percent
Air to Be
Transported
CFM (LPM)*
Operating Rooms
Major "A"(Radical, Open Heart)
(Organ Transplant)
(Radical Thoracic)
Major "B"(A11 Other Major ORs)
Minor
3.5 (99.1)
3.5 (99.1)
3.5 (99.1)
2.0 (56.6)
1.0 (28.3)
-
100
100
100
100
100
3.5 (99.1)
3.5 (99.1)
3.5 (99.1)
2.0 (56.6)
1.0 (28.3)
Delivery Rooms
1.0 (28.3)
-
100
1.0 (28.3)
Recovery Rooms (Post-
Anesthesia) and
Intensive Care Units (a minimum
of 2 outlets per bed in each
such department)
1st outlet at each bed
2nd outlet at each bed
3rd outlet at each bed
All others at each bed
3.0
1.0
1.0
1.0
(85.0)
(28.3)
(28.3)
(28.3)
50
50
10
10
1.5 (42.5)
. 0.5 (14.2)
0.1 (2.8)
0.1 (2.8)
Emergency Rooms
-
1.0
(28.3)
100
1.0 (28.3)
Patient Rooms
Surgical
Medical
Nurseries
~
1.0
1.0
1.0
(28.3)
(28.3)
1283) _
50
10
10
0.5 (14.2)
0.1 (2.8)
0.1 (2.8)
Treatment and Examining Rooms
0.5
(14.2)
10
0.05 (1.4)
Autopsy Area
-
2.0
(56.6)
20
0.4 (11.3)
Inhalation Therapy, Central
Supply and Instructional Areas
-
1.0
(28.3)
10
0.1 (2.8)
*Free air at 1 atmosphere
221
Table 13-6 -Table 13-7
UNIFORM PLUMBING CODE
<
TABLE 13-6
Size of Gas/Vacuum Piping
Maximum Delivery Capacity^ ir
1 SCFM (LPM)
Jt (m)^
500 (152)
750
Medical Gas Pipe Size
System Inch''
100
Length of Piping in Fee
(30) 250 (76)
(228)
1,000
(304)
Oxygen
1/2
3/4
1
15.0
40.0
50.0
(425)
(1,133)
(1,416)
10.6 (300)
28.3 (801)
50.0 (1,416)
7.4.
19.6
40.2
(209)
(555)
(1,138)
5.9
15.7
32.2
(167)
(445)
(912)
5.1
13.3
27.7
(144)
(377)
(784)
1/2
Nitrous Oxide 3/4
1
15.0
30.0
40.0
(425)
(849)
(1,113)
9.5 (269)
24.7 (699)
40.0 (1,133)
6.5
17.1
34.7
(184)
(484)
(983)
5.3
13.7
28.2
(150)
(388)
(7,98)
4.5
11.7
24.3
(127)
(331)
(688)
Medical Air
1/2
3/4
1
18.1
40.0
50.0
(512)
(1,133)
(1,416)
11.1 (314)
29.9 (847)
50.0 (1,416)
7.8
21.0
42.1
(221)
(595)
(1,192)
6.3
16.5
35.8
(177)
(467)
(1,013)
5.3
14.1
29.2
(151)
(399)
(826)
Vacuum
1
1-1/4
1-1/2
2
22.8
40.1
63.7
132.7
(645)
(1,135)
(1,804)
(3,758)
13.7 (388)
24.5 (694)
38.9 (1,101)
81.4 (2,305)
9.5
16.7
26.8
56.0
(269)
(473)
(759)
(1,586)
7.6
13.3
21.1
45.0
(215)
(377)
(600)
(1,274)
6.5
11.2
17.9
38.3
(184)
(317)
(507)
(1,084)
Nitrogen
1/2
3/4
1
25.0
60.0
110.0
(708)
(1,699)
(3,115)
25.0 (708)
60.0 (1,699)
110.0 (3,115)
25.0
60.0
110.0
(708)
(1,699)
(3,115)
23.8
60.0
110.0
(674)
(1,699)
(3,115)
20.6
54.2
110.0
(583)
(1,535)
(3,115)
' Length of piping includes a 30% allowance for fittings.
^ One-half inch (12.7 mm) diameter pipe is the minimum size allowed Ln medical gas systems.
' Based on the following maximum pressure drops:
Oxygen, nitrous oxide, and medical air - 5 psig (10 in. Hg)
Vacuum - 1.96 psig (4 in. Hg)
Nitrogen - 20 psig (41 in. Hg)
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
TABLE 13-7
Maximum Pipe Support Spacing
Pipe Size
Hanger Spacing
mm
ft.
DN8 (NFS 1 /4) (3/8 in. O.D.)
DNIO (NFS 3/8) (1/2 in. O.D.)
DN15 (NFS 1/2) (5/8 in. O.D)
DN20 (NFS 3/4) (7/8 in. O.D.)
DN25 (NFS 1) (1-1/8 in. O.D.)
DN32 (NFS 1-1/4) (1-3/8 in. O.D.)
DN40 (NFS 1-1/2) (1-5/8 in. O.D.)
and larger
Vertical risers, all sizes
Every floor but not to exceed:
1,520
5
1,830
6
1,830
6
2,130
7
2,440
8
2,740
9
3,050
4,570
10
15
[NFFA 99: 5.1.10.6.4.1]
222
CHAPTER 14
MANDATORY REFERENCED STANDARDS
TABLE 14-1
Standards for Materials, Equipment, Joints, and Connections
Where more than one standard has been listed for the same material or method,
the relevant portions of all such standards shall apply.
Standard Number
Standard Title
Application
1 AHAM DW-l-2004
Household Electric Dishwashers
Appliances
AHAM DW-2PR-92
Plumbing Requirements for Household Dishwashers
Apphances
AHAM FWD-1-92
Food Waste Disposers
Appliances
1 AHAM FWD-2PR-89
Household Food Waste Disposer Units
Appliances
ANSIA13.1-96(R03)
Scheme for the Identification of Piping Systems
Piping
ANSI A21.10-2003
Ductile-Iron and Gray-Iron Fittings, 3 in. through 48 in.
(75 mm through 1,200 nmi), for Water and Other Liquids
(same as AWW A CI 10)
Piping, Ferrous
ANSIA21.11-2000
Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and
Fittings (same as AWWA Clll)
Piping, Ferrous
ANSI A21.51-2002
Ductile-Iron Pipe, Centrifugally Cast, for Water (same as
AWWA C151)
Piping, Ferrous
ANSI A2l!53-2000
DuctQe-Iron Compact Fittings, 3 in. through 24 in.
(76 mm through 610 mm) and 54 in. through
64 in. (1400 mm through 1600 mm), for Water Service
(same as AWWA C153)
Pipmg, Ferrous
ANSI A118.10-99
Load, Bearing, Bonded, Waterproof Membranes for
Thin-Set Ceramic Tile and Dimension Stone Installations
Fixtures
ANSI A137.1-88
Ceramic Tile
Miscellaneous
ANSI B2.1-90
Pipe Threads (Except Dryseal) (replaced by ASME Bl. 20.1-98)
Joints
ANSI/CSA LC 3-2000
Appliance Stands and Drain Pans
Miscellaneous
ANSI A117.1-2003
Accessible and Usable Buildings and Facilities
Miscellaneous
ANSI Z4.1-95
Sanitation in Places of Employment (Table 4-1 Note 6)
Miscellaneous
ANSIZ21.5.1a-2003
Gas Clothes Dryers Type 1 Clothes Dryers
Fuel Gas
ANSIZ21.5.2a-2003
Gas Clothes Dryers Type 2 Clothes Dryers
Fuel Gas
223
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ANSIZ21.10.1-2004
Gas Water Heaters - Volume I - Storage Water Heaters
with Input Ratings of 75,000 Btu per Hour or Less (22 kW)
Appliances
ANSI Z21. 10.3-2004
Gas Water Heaters - Volume in - Storage, with Input
Ratings Above 75,000 Btu per Hour, Circulating and
Instantaneous Water Heaters
Appliances
ANSI Z21.12b-94
Draft Hoods
Appliances
ANSI Z21. 13-2004
Gas-Fired Low-Pressure Steam and Hot- Water Boilers
Appliances
ANSI Z21. 15-97
Manually Operated Gas Valves for Appliances,
Appliance Connector, Valves, and Hose End Valves
Valves
1 ANSI Z21. 22-2000
Relief Valves for Hot- Water Supply Systems
Valves
ANSI Z21.24-2001
Connectors for Gas Appliances
Appliances
ANSI Z21,41-2003
Quick-Disconnect Devices for Use with Gas Fuel Appliances
CSA 6.9-2003
Joints
ANSIZ21.47b-2003
Gas-Fired Central Furnaces
Fuel Gas
ANSIZ21.56-2001
Gas-Fired Fool Heaters
Swimming Pools
CSA 4.7-2001
and Spas
ANSI Z21.69a-2003
Connectors for Movable Gas Appliances
Appliances
CSA 6.16-2003
ANSI Z21.80-2003
Line Pressure Regulators
Fuel Gas
CSA 6.22-M2003
ANSI Z21.81-98
Cylinder Connection Devices
Fuel Gas
CSA 6.25-M98
ANSI Z21. 86-2004
Vented Gas-Fired Space-Heating Appliances
Appliances
CSA 2.32-2004
ANSI Z34.1-93
Certification - Third Party Certification Programs for
Products Processes, and Services
Certification
ANSI Z83.11-2002
Gas Food Service Equipment
Fuel Gas
ANSIZ124.1-95
Plastic Bathtub Units
Fixtures
ANSI Z124.2-95
Plastic Shower Units
Fixtures
ANSI Z124.3-95
Plastic Lavatories
Fixtures
ANSI Z124.4-96
Plastic Water Closet Bowls and Tanks
Fixtures
224
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
ANSI Z124.5-97
Plastic Toilet (Water Closet) Seats
Fixtures
ANSI Z124.6-97
Plastic Sinks
Fixtures
ANSI Z124.7-97
Prefabricated Plastic Spa Shells
Fixtures
ANSI Z124.8-90
Plastic Bathtub Liners
Fixtures
lAPMO/ANSI Z124.9-2004
Plastic Urinal Fixtures (Note 1)
Fixtvires
ANSI Z223.1-2002
National Fuel Gas Code (same as NFPA 54)
Fuel Gas
ISEA Z358.1-2004
Emergency Eyewash and Shower Equipment
Miscellaneous
ARI 1010-2002
Drinking Fountains and Self-Contained,
Mechanically Refrigerated Drinking Water Coolers
Appliances
ASCE 25-99
Earthquake Actuated Automatic Gas Shutoff Devices
Fuel Gas
ASHRAE 90.1-2004
Energy Standard for Buildings Except Low-Rise
Residential Buildings
Miscellaneous
ASME A112.1.2-2004
Air Gaps in Plumbing Systems
Fittings
ASME A112.1.3-2000
Air Gap Fittings for Use with Plumbing Fixtures, Appliances,
and Appurtenances
Fixtures
ASME Al 12.3. 1-93
Stainless Steel Drainage Systems for Sanitary, Storm, and
Chemical Applications, Above and Below Ground (Note 1)
Piping, Ferrous
ASME A112.3.4-2000 (R04)
Macerating Toilet Systems and Related Components
Fixtures
ASME A112.4.1-93(R02)
Water Heater Relief Valve Drain Tubes
Appliances
ASME Al 12.4.2-2003
Water Closet Personal Hygiene Devices
Fixhires
ASME A112.4.3-99 (R04)
Plastic Fittings for Connecting Water Closets to the
Sanitary Drainage System
Piping
ASME Al 12.4.7-2002
Point of Use and Branch Water Submetering Systems
Miscellaneous
ASME A112.6.1M-97 (R02)
Floor- Affixed Supports for Off-the-Floor Plumbing Fixtures
for PubUc Use
Fixtures
ASME A112.6.2-2000 (R04)
Framing- Affixed Supports for Off-the-Floor Plumbing
Fixtures
Fixtures
ASME A112.6.3-2001
Floor and Trench Drains
DWV Components
ASME Al 12.6.4-2003
Roof, Deck, and Balcony Drains
DWV Components
ASME Al 12.6.7-2001
Enameled and Epoxy Coated Cast Iron and PVC Plastic
Sanitary Floor Sinks
Fixtures
225
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ASME A112.14.1-2003
Backwater Valves
Valves
ASME A112.14.3-2000
Grease Interceptors
Fixtures
ASME A112.14.4-2001
Grease Removal Devices
Fixtures
ASME A112.18.1-2005/
Plumbing Supply Fittings
Fixtures
CSA B125.1-05
ASME Al 12.18.2-2005/
Plumbing Waste Fittings
Fittings
CSA B125.2-05
ASME A112.18.3-2003
Backflow Protection Devices and Systems in
Kitchen, Lavatory, and
Plumbing Fixtures
Shower Fittings with
ASME A112.18.6-2003
Flexible Water Connectors
Piping
ASME A112.18.7-99 (R04)
Deck Mounted Bath/Shower Transfer Valves with
Integral Backflow Protection
Valves
ASME A112.19.1M-94 (R04)
Enameled Cast-Iron Plumbing Fixtures
(Supplement 1-1998)
Fixtures
ASME A112.19.2M-2003
Vitreous China Plumbing Fixtures and Hydraulic Fixtures
Requirements for Water Closets and Urinals
Fixtures
ASME A112.19.3M-01(R04)
Stainless Steel Plumbing Fixtures (Designed for
Residential Use)
Fixtures
ASME A112.19.4M-94(R04)
Porcelain-Enameled Formed Steel Plumbing Fixtures
(Supplement 1-1998)
Fixtures
ASME A112.19.5-99
Trim for Water-Closet Bowls, Tanks, and Urinals
Fixtures
ASME A112.19.7M-95
Whirlpool Bathtub Appliances
Fixtures
ASME A112.19.8M-87(R96)
Suction Fittings for Use in Swimming Pools, Wading
Swimcming Pools
Pools, Spas, Hot Tubs, and Whirlpool Bathtub Appliances
and Spas
ASME A112.19.9M-91 (R02)
Non- Vitreous Ceramic Plimibing Fixtures
Fixtures
ASME A112.19.10-2003
Dual Flush Devices for Water Closets
Fixtures
ASME A112.19.12-2000
Wall Mounted and Pedestal Mounted Adjustable and Pivoting
Lavatory and Sink Carrier System
Fixtures
ASME A112.19.13-2002
Electrohydraulic Water Closets
Fixtures
ASME A112.19.14-2001
Six-Liter Water Closets Equipped with a Dual Flashing Device
Fixtures
ASME A112.19.15-2001
Bathtub /Whirlpool Bathtubs with Pressure Sealed Doors
Fixtures
226
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
ASME A112.20.1-2004
Qualification of Installers of High Purity Systems
Swimming Pools & Spas
ASME A112.20.2-2004
Qualification of Installers of Firestop Systems and Devices for
Piping Systems
Certification
ASME A112.21.3M-85 (ROl)
Hydrants for Utility and Maintenance Use (Note 1)
Valves
ASME A112.36.2M-91 (R02)
Cleanouts (Note 1)
DWV Components
ASME Bl.20.1-83 (ROl)
Pipe Threads, General Purpose, Inch
Joints
ASME Bl.20.3-76 (R03)
Dryseal Pipe Threads, Inch
Joints
ASME B16.1-98
Cast-Iron Pipe Flanges and Flanged Fittings, Classes 25,
125, 250, and 800
Piping, Ferrous
ASME B16.3-98
Malleable-Iron Threaded Fittings
Piping, Ferrous
ASME B16.4-98
Gray Iron Threaded Fittings (Includes Revision Services)
Piping, Ferrous
ASME B16.5-2003
Pipe Flanges and Flanged Fittings
Joints
ASME B16.12-98
Iron Threaded Drainage Fittings (Note 1)
Piping, Ferrous
ASME B16.15-85 (R04)
Cast Bronze Threaded Fittings, Classes 125 and 250
Piping, Copper Alloy
ASME B16.18-2001
Cast Copper Alloy Solder Joint Pressure Fittings (Note 1)
Piping, Copper Alloy
ASME B16.21-92
NonmetalUc Flat Gaskets for Pipe Flanges
Joints
ASME B16.22-2001
Wrought Copper and Copper Alloy Solder Joint Pressure
Fittings Alloy
Piping, Copper Alloy
ASME B16.23-2002
Cast Copper Alloy Solder Joint Drainage Fittings - DWV
Piping, Copper Alloy
ASME B16.24-2001
Cast Copper Alloy Pipe Flanges and Flanged Fittings
Piping, Copper Alloy
ASME B16.26-88
Cast Copper Alloy Fittings for Flared Copper Tubes
Piping, Copper Alloy
ASME B16.29-2001
Wrought Copper and Wrought Copper Alloy Solder Joint
Drainage Fittings-DWV Alloy (Note 1)
Piping, Copper Alloy
1 ASME B16.33-2002
Manually Operated MetaUic Gas Valves for Use in Gas
Piping Systems up to 125 psig
Valves
ASME B16.34-96
Valves - Flanged, Threaded, and Welding End
Valves
ASME B16.39-98
Pipe Unions, Malleable Iron Threaded (Includes Revision
Services)
Piping, Ferrous
1 ASME B16.40- 2002
Manually Operated Thermoplastic Gas Shutoff and Valves
in Gas Distribution Systems
Fuel Gas
ASME B16.47-96
Large Diameter Steel Flanges
Piping, Ferrous
227
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ASME B16.50-2001
Wrought Copper and Copper Alloy Braze-Joint Pressure Fittings
Piping, Copper AUoy
ASME B31.1-2004
Power Piping
Piping
ASME B36.10M-2004
Welded and Seamless Wrought Steel Pipe
Piping, Ferrous
ASME B36.19-85(R94)
Stainless Steel
Piping, Ferrous
ASME Section IV
Rules for Construction of Heating Boilers
Miscellcmeous
ASME Section VIII
Rules for Construction of Pressure Vessels
Miscellaneous
ASME Section IX
Welding and Brazing Procedures, Welders, Brazers, and
Welding and Brazing Operators
Certification
1 ASSE 1001-2002
Atmospheric-Type Vacuum Breakers
Backflow Protection
ASSE 1002-99
Anti-Siphon Fill Valves (BaUcocks) for Gravity Water Closet
Flush Tank
Backflow Protection
ASSE 1003-2001
Water Pressure Reducing Valves
Valves ,
ASSE 1004-90
Backflow Prevention Requirements for Commercial
Dishwashing Machines
Backflow Protection
ASSE 1005-99
Water Heater Drain Valves
Valves
ASSE 1006-86
Residential Use Dishwashers
AppUances
ASSE 1007-86
Home Laundry Equipment
AppHances
ASSE 1008-86
Household Food Waste Disposer Units
Appliances
ASSE 1009-90
Commercial Food Waste Grinder Units
Appliances
ASSE 1010-2004
Water Hammer Arresters
Piping
ASSE 1011-2004
Hose-Connection Vacuum Breakers
Backflow Protection
ASSE 1012-2002
Backflow Prevention with Intermediate Atmospheric Vent
Backflow Protection
ASSE 1013-2005
Reduced Pressure Principle Backflow Preventers and Reduced
Pressure Fire Protection Principle Backflow Preventers
Backflow Protection
ASSE 1014-2005
Hand-Held Showers
Fixtures
ASSE 1015-2005
Double-Check Backflow Prevention Assembly and Double
Check Fire Protection Backflow Prevention Assemblies
Backflow Protection
ASSE 1016-2005
Valves for Individual Showers and Tub/Shower Combinations
Valves
ASSE 1017-2003
Temperature Actuated Mixing Valves for Hot Water
Distribution Systems
Valves
228
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
ASSE 1018-2001
Trap Seal Primer Valves, Potable Water Supplied
Valves
ASSE 1019-2004
Vacuum Breaker Wall Hydrant, Freeze-Resistant
Backflow Protection
ASSE 1020-2004
Automatic Draining Type
Pressure Vacuum Breaker Assembly
Backflow Protection
ASSE 1021-2001
Drains Air Gaps for Domestic Dishwasher Applications
Backflow Protection
1 ASSE 1022-2003
Backflow Prevention for Beverage Dispensing Equipment
Backflow Protection
ASSE 1023-79
Hot Water Dispensers, Household Storage Type, Electrical
Appliances
1 ASSE 1024-2003
Dual Check Valve Backflow Preventers
Backflow Prevention
ASSE 1025-78
Diverters for Pltimbing Faucets with Hose Spray,
Anti-Siphon Type, Residential Applications
Valves
1 ASSE 1032-2004
Dual Check Valve T}^e Backflow Preventers for Carbonated
Beverage Dispensers - Post Mix Types
Backflow Protection
1 ASSE 1035-2002
Laboratory Faucet Backflow Preventer
Backflow Protection
ASSE 1037-90
Pressurized Flushing Devices (Flushometers) for Plumbing
Fixtures
Backflow Protection
ASSE 1044-2001
Trap Seal Primer Devices-Drainage Types and Electronic
Design Types
DWV Components
ASSE 1047-2005
Reduced Pressure Detector Fire Protection Backflow
Prevention Assemblies
Backflow Protection
ASSE 1048-2005
Double Check Detector Fire Protection Backflow
Prevention Assemblies
Backflow Protection
ASSE 1052-2004
Hose Connection Backflow Preventers
Backflow Protection
ASSE 1055-97
Chemical Dispensing Systems
Backflow Protection
ASSE 1056-2001
Spill Resistant Vacuum Breakers
Backflow Protection
ASSE 1062-97
Temperature Actuated Flow Reduction (TAFR) Valves for
Individual Fixture Fittings
Valves
ASSE 1066-97
Individual Pressure Balancing In-Line Valves for Individual
Fixture Fittings (Note 9)
Valves
ASSE 1069-2005
Automatic Temperature Control Mixing Valves
Valves
ASSE 1070-2004
Water Temperature Limiting Devices
Valves
ASSE Series 5000-2004
Professional Qualification Standard for Backflow Prevention
Assembly Testers, Repairers, and Surveyors
Backflow Protection
229
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ASSE 6000-2004
Medical Gas Systems Installers, Inspectors, and Verifiers,
Maintenance Personnel and Instructors
Certification
ASTMA47-99(R04)
Ferritic Malleable Iron Castings
Piping, Ferrous
ASTM A 48-2003
Gray Iron Castings
Piping, Ferrous
ASTM A 53-2004a
Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded,
and Seamless
Piping, Ferrous
ASTM A 74-2004a
Cast-Iron Soil Pipe and Fittings (Note 1)
Piping, Ferrous
ASTM A 126-2004
Gray Iron Castings for Valves, Flanges, and Pipe Fittings
Piping, Ferrous
ASTM A 197M-2000
Cupola Malleable Iron (Metric)
Piping, Ferrous
ASTM A 269-2004
Seamless and Welded Austenitic Stainless Steel Tubing for
General Service
Piping, Ferrous
ASTM A 312-2004b
Seamless and Heavy Cold Worked Welded Austenitic
Stainless Steel Pipes
Piping, Ferrous
ASTM A 377-2003
Ductile-Iron Pressure Pipe
Piping, Ferrous
ASTM A 479-2005
Stainless Steel Bars and Shapes for Use in Boilers and Other
Pressure Vessels
Piping, Ferrous
ASTM A 518-99(R03)
Corrosion-Resistant High-Silicon Iron Castings
Piping, Ferrous
ASTMA536-84(R04)
Ductile Iron Castings
Piping, Ferrous
ASTM A 653M-2004a
Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron
Alloy-Coated (Galvannealed) by the Hot-Dip Process
Piping, Ferrous
ASTM A 733-2003
Welded and Seamless Carbon Steel and Austenitic
Stainless Steel Pipe Nipples
Piping, Ferrous
ASTM A 861-2004
High-Silicon Iron Pipe and Fittings (Note 1)
Piping, Ferrous
ASTM A 888-2004a
Hubless Cast-iron Soil Pipe and Fittings for Sanitary and
Storm Drain Waste and Vent Piping Applications
Piping, Ferrous
ASTM B 29-2003
Refined Lead
Joints
ASTM B 32-2004
Solder Metal (Note 4)
Joints
ASTM B 42-2002='
Seamless Copper Pipe, Standard Sizes
Piping, Copper Alloy
ASTM B 43-98(R04)
Seamless Red Brass Pipe, Standard Sizes
Piping, Copper Alloy
230
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
ASTMB 75-2002
Seamless Copper Tube
Piping, Copper Alloy
ASTMB 88-2003
Seamless Copper Water Tube
Piping, Copper Alloy
ASTM B 135-2002
Seamless Brass Tube (Metric)
Piping, Copper Alloy"
ASTM B 152-2000
Copper Sheet, Strip, Plate, and Rolled Bar
Miscellaneous
ASTM B 251-2002-=^
General Requirements for Wrought Seamless Copper
Copper- Alloy Tube
Piping, Copper Alloy
ASTM B 280-2003
SeaiTiIess Copper Tube for Air Conditioning and Refrigeration
Field Service
Piping, Copper Alloy
ASTM B 302-2002
Threadless Copper Pipe, Standard Sizes
Piping, Copper Alloy
ASTM B 306-2002
Copper Drainage Tube (DWV)
Piping, Copper Alloy
ASTM B 370-2003
Copper Sheet and Strip for Building Construction
Miscellaneous
ASTM B 447-2002
Welded Copper Tube
Piping, Copper Alloy
ASTM B 584-2004
Copper Alloy Sand Casting for General Applications (Note 5)
Piping, Copper Alloy
ASTM B 587-97"' (R03)
Welded Brass Tube
Piping, Copper Alloy
ASTM B 687-99
Brass, Copper, and Chromiiun-Plated Pipe Nipples
Piping, Copper Alloy
ASTM B 813-2000"'
Liquid and Paste Fluxes for Soldering Applications of
Copper and Copper Alloy Tube
Joints
ASTM B 819-2000
Seamless Copper Tube for Medical Gas Systems
Piping, Copper Alloy
ASTM B 828-2002
Making Capillary Joints by Soldering of Copper and
Copper Alloy Tube and Fittings
Joints
ASTM C 14-2003
Concrete Sewer, Storm Drain, and Culvert Pipe
Piping, Non-Metallic
ASTM C 296-2000
Asbestos-Cement Pressure Pipe
Piping, Non-Metallic
ASTM C 412-2003
Concrete Drain Tile
Piping, Non-Metallic
ASTM C 425-2004
Compression Joints for Vitrified Clay Pipe and Fittings
Joints
ASTM C 428-97(R02)<^'
Asbestos-Cement Nonpressure Sewer Pipe (Notes 6 and 7)
Piping, Non-Metallic
ASTM C 443-2005
Joints for Circular Concrete Sewer and Culvert Pipe,
Using Rubber Gaskets
Joints
ASTM C 478-2003a
Precast Reinforced Concrete Manhole Sections
Miscellaneous
ASTM C 564-2003a
Rubber Gaskets for Cast-Iron Soil Pipe and Fittings
Joints
231
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ASTM C 700-2002
Vitrified Clay Pipe, Extra Strength, Standard Strength,
and Perforated
Piping, Non-MetalHc
ASTM C 1053-2000
Borosilicate Glass Pipe and Fittings for Drain, Waste,
and Vent (DWV) Applications (Note 1)
Piping, Non-Metallic
ASTM C 1173-2004
Flexible Transition Couplings for Underground
Piping Systems
Joints
ASTM C 1277-2004
Shielded Couplings Joining Hubless Cast-iron Soil
Pipe and Fittings
Piping, Ferrous
ASTM C 1440-2003
Thermoplastic Elastomeric (TPE) Gasket Materials for Drain,
Waste, and Vent (DWV), Sewer, Sanitary and Storm
Plumbing Systems
Piping, Plastic
ASTM C 1460-2004
Shielded Transition Couplings for Use with Dissimilar DWV
Pipe and Fittings Above Ground
Piping, Plastic
ASTM C 1461-2002
Mechanical Couplings Using Thermoplastic Elastomeric
(TPE) Gaskets for Joining Drain, Waste, and Vent (DWV);
Sewer; Sanitary; and Storm Plumbing Systems for Above
and Below Ground
Piping, Plastic
ASTM C 1540-2004
Heavy Duty Shielded Couplings Joining Hubless Cast Iron
Son Pipe and Fittings
Joints
ASTM D 1527-99^'
Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe,
Sch.40and80
Piping, Plastic
ASTM D 1784-2003
Rigid Poly (Vinyl Chloride) (PVC) Compounds and
Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds
Piping, Plastic
ASTMD1785-2004a
Poly(Vinyl Chloride) (PVC) Plastic Pipe, Sch. 40, 80, and 120
Piping, Plastic
ASTM D 1869-95(R00)
Rubber O-rings for Asbestos-Cement Pipe
Joints
ASTM D 2104-2003
Polyethylene (PE) Plastic Pipe, Sch. 40
Piping, Plastic
ASTM D 2235-2004
Solvent Cement for Acrylorutrile-Butadiene-Styrene (ABS)
Plastic Pipe and Fittings
Joints
ASTM D 2239-2003
Polyethylene (PE) Plastic Pipe, (SDR-PR) Based on
Controlled Inside Diameter
Piping, Plastic
ASTMD2241-2004b
Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)
Piping, Plastic
ASTM D 2282-99^^
Acryloniti-ile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR)
Piping, Plastic
ASTM D 2321-2000
Underground Installation of Thermoplastic Pipe for Sewers
and Other Gravity-Flow Applications
Piping, Plastic
232
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
ASTM D 2447-2003 ,
Polyethylene (PE) Plastic Pipe, Sch. 40 and 80 (Based on
Controlled Outside Diameter)
Piping, Plastic
ASTM D 2464-99"^
Threaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings,
Sch. 80 (Note 1)
Piping, Plastic
ASTM D 2466-2002
Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Sch. 40
(Note 1)
Piping, Plastic
ASTM D 2467-2004'=^
Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Sch, 80
(Note 1)
Piping, Plastic
ASTM D 2513-2004a
Thermoplastic Gas Pressure Pipe Tubing and Fittings (Note 1)
Piping, Plastic
ASTM D 2517-2000'='
Reinforced Epoxy Resin Gas Pressure Pipe and Fittings
Piping, Plastic
ASTM D 2564-2004
Solvent Cements for Poly(Vtnyl Chloride) (PVC) Plastic
Piping Systems
Joints
ASTM D 2609-2002
Plastic Insert Fittings for Polyethylene (PE) Plastic Pipe (Note 1)
Piping, Plastic
ASTM D 2657-2003
Practice for Heating Fusion Joining of Polyolefin Pipe
Fittimgs (Note 1)
Joints
ASTM D 2661-2002
Acrylonitrile-Butadiene-Styrene (ABS) Sch. 40 Plastic
Drain, Waste, and Vent Pipe and Fittings (Note 1)
Piping, Plastic
ASTM D 2665-2004a
Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and
Vent Pipe and Fittings (Note 1)
Piping, Plastic
ASTM D 2672-96a (R03)
Joints for IPS PVC Pipe Using Solvent Cement
Joints
ASTM D 2680-2001
Acrylonitrile-Butadiene-Styrene (ABS) and Poly(Vinyl
Chloride) (PVC) Composite Sewer Piping
Pipii\g, Plastic
ASTM D 2729-2003
Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings (Note 1)
Piping, Plastic
ASTM D 2737-2003
Polyethylene (PE) Plastic Tubing
Piping, Plastic
ASTM D 2751-96a
Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe
and Fittings (Note 1)
Piping, Plastic
ASTM D 2846-99'^'
Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and
Cold- Water Distribution Systems
Piping, Plastic
ASTM D 2855-96(R02)
Making Solvent-Cemented Joints with Poly(Vinyl Chloride)
(PVC) Pipe and Fittings
Joints
ASTM D 2996-2001
Filament- Wovmd Fiberglass (Glass-Fiber-Reinforced
Thermosetting Resin) Pipe
Piping, Plastic
ASTMD3034-2004a
Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
Piping, Plastic
ASTM D 3035- 2003a
Polyethylene(PE) Plastic Pipe (DR-PR) (Based on Conhrolled
Outside Diameter)
Piping, Plastic
233
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ASTM D 3122-95(R02)
Solvent Cements for Styrene-Rubber (SR) Plastic Pipe
and Fittings
Joints
ASTMD 3138-2004
Solvent Cements for Transition Joints, AcrylonitrUe-Butadiene-
Styrene (ABS) and Poly (Vinyl Chloride) (PVC)
Non-Pressure Piping Components
Joints
ASTM D 3139-98
Joints for Plastic Pressure Pipes Using Flexible Elastomeric
Seals
Joints
1 ASTM D 3212-96a (R03)^'
Joints for Drain and Sewer Plastic Pipes Using Flexible
Elastomeric Seals
Joints
ASTM D 3311-2002^'
Drain, Waste, and Vent (DWV) Plastic Fittings
Patterns (Note 1)
Piping, Plastic
ASTM D 3965-2004
Rigid Acrylonitrile-Butadiene-Styrene (ABS)
Materials for Pipe and Fittings
Piping, Plastic
ASTM D 4068-2001
Chlorinated Polyethylene (CPE) Sheeting for Concealed
Water-Containment Membrane
Fixtures
ASTM D 4101-2004a
Propylene Plastic Injection and Extrusion Materials
Miscellaneous
ASTM D 4551-96 (ROl)
Poly(Vinyl Chloride) (PVC) Plastic Flexible Concealed
Water-Containment Membrane
Fixtures
ASTM D 6104-97 (R03)
Determining the Performance of Oil/ Water Separators
Subjected to Surface Run-Off
Fixtures
ASTM E 84-2004
Surface Burning Characteristics of Building Materials
Miscellaneous
ASTM E 119-2000a
Fire Tests of Building Construction and Materials
Miscellaneous
ASTM E 814- 2002
Fire Tests of Through-Penetration Fire Stops
Miscellaneous
ASTM F 402-93(R99)
Safe Handling of Solvent Cements, Primers, and Cleaners
Used for Joining Thermoplastic Pipe and Fittings
Joints
ASTM F 405-97
Corrugated Polyethylene (PE) Tubing and Fittings
Piping, Plastic
ASTM F 409-2002
Thermoplastic Accessible and Replaceable Plastic Tube
and Tubular Fittings (Note 1)
Piping, Plastic
ASTM F 437-99
Threaded Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic
Pipe Fittings, Sch. 80
Piping, Plastic
ASTM F 438-2004
Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC)
Plastic Pipe Fittings, Sch. 40
Piping, Plastic
ASTMF439-2002''
Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC)
Plastic Pipe Fittings, Sch. 80
Piping, Plastic
234
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
1 ASTM F 441-2002
Chlorinated Foly(Vinyl Chloride) (CPVC) Plastic Pipe,
Sch. 40 and 80
Piping, Plastic
ASTM F 442-99
Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe
(SDR-PR)
Piping, Plastic
ASTM F 480-2002
Thermoplastic Well Casing Pipe and Couplings Made in
Standard Dimension Ratios (SDR) Schedtde 40 and Schedule 80
Piping, Plastic
ASTM F 493-2004
Solvent Cements for Chlorinated Poly(Vinyl Chloride)
(CPVC) Plastic Pipe and Fittings
Joints
ASTM F 628-2001
Acrylonitrile-Butadiene-Styrene (ABS) Sch. 40 Plastic Drain,
Waste, and Vent Pipe with a Cellular Core, (Note 1)
Piping, Plastic
ASTM F 656-2002
Primers for Use in Solvent Cement Joints of
Poly(Vinyl Chloride) (PVC) Plastic Pipe and Fittings
Joints
ASTM F 667-97
Large Diameter Corrugated Polyethylene Tubing and Fittings
Piping, Plastic
ASTM F 714-2003
Polyethylene (PE) Plastic Pipe (SDR-PR) (Based on Outside
Diameter)
Piping, Plastic
ASTM F 789-2003
Type PS-46 and Type PS-115 Poly(Vinyl Chloride) (PVC)
Plastic Gravity Flow Sewer Pipe and Fittings (Note 1)
Piping, Plastic
ASTM F 794-2003
Poly(Vinyl Chloride) (PVC) Profile Gravity Sewer Pipe
and Fittings Based on Controlled Inside Diameter
Piping, Plastic
ASTM F 810-2001
Smoothwall Polyethylene (PE) Pipe for Use in Drainage and
Waste Disposal Absorption Fields
Piping, Plastic
ASTM F 876-2004a
Crosslinked Polyethylene (PEX) Tubing
Piping, Plastic
ASTM F 877-2002a
Crosslinked Polyethylene (PEX) Plastic Hot- and
Cold- Water Distribution Systems
Piping, Plastic
ASTM F 891-2004
Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe with a
Cellular Core
Piping, Plastic
ASTM F 894-98a
Polyethylene (PE) Large Diameter Profile Wall Sewer and
Drain Pipe
Piping, Plastic
ASTM F 949-2003
Poly(Vinyl Chloride) (PVC) Corrugated Sewer Pipe with a
Smooth Interior and Fittings
Piping, Plastic
ASTM F 1216-2003
Rehabilitation of Existing Pipelines and Conduits by the
Inversion and Curing of a Resin-Impregnated Tube
Piping, Plastic
ASTM F 1281-2003
Crosslinked Polyethylene / Aluminum/ Crosslinked
Polyethylene (PEX-AL-PEX) Pressure Pipe
Piping, Plastic
ASTM F 1282-2003
Polyethylene/Aluminum/Polyethylene (PE-AL-PE)
Composite Pressure Pipe
Piping, Plastic
235
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
ASTM F 1412-2001'^
Folyolefin Pipe and Fittings for Corrosive Waste Drainage
Systems
Piping, Plastic
ASTM F 1476-2001
Gasketed Mechanical Couplings for Use in Piping Application
Joints
ASTM F 1673-2004
Polyvinylidene Fluoride (PVDF) Corrosive Waste
Drainage Systems
Piping, Plastic
ASTM F 1743-96(R03)
Rehabilitation of Existing Pipelines and Conduits by
Pulled-in-Place Installation of Cured-in-Place Thermosetting
Resin Pipe (CIPP)
Piping, Plastic
ASTM F 1807-2004
Metal Insert Fittings with Copper Crimp Ring for SDR 9
Crossltnked Polyethylene (PEX) Tubing
Piping, Plastic
ASTM F 1866-98
Poly(Vinyl Chloride) (PVC) Drainage and DWV
Fabricated Fittings, Schedule 40
Piping, Plastic
ASTM F 1924-2001''
Plastic Mechanical Fitting for Use on Outside Diameter
Controlled Polyethylene Gas Distribution Pipe and Tubing
Piping, Plastic
ASTM F 1948-99a''
Metallic Mechanical Fittings for Use on Outside Diameter
Controlled Thermoplastic Gas Distribution Pipe and Tubing
Piping, Plastic
ASTM F 1960-2003
Cold Expansion Fittings with PEX Reinforcing Rings for Use
with Cross-Linked Polyethylene (PEX) Tubing
Piping, Plastic
ASTM F 1961-2002a
Metal Cold Flare Compression Fittings with Disc Springs
for Crosslinked Polyethylene (PEX) Tubing
Piping, Plastic
ASTM F 1970-2001
Special Engineered Fittings or Appurtenances for Use in Poly
(Vinyl Chloride) (PVC) or Chlorinated Poly(Vinyl Chloride)
(CPVC) Systems
Piping, Plastic
ASTM F 1973-2002
Factory Assembled Anodeless Riser and Transition Fitting
in Polyethylene (PE) Fuel Gas Distribution Systems
Piping, Plastic
ASTM F 1974-2004
Metal Insert Fittings for Polyethylene/Aluminum/Polyethylene
and Crosslinked Polyethylene/Aluminum/Crosslinked
Polyethylene Composite Pressure Pipe
Piping, Plastic
ASTM F 2080-2004
Cold-Expansion Fittings With Metal Compression Sleeves
for Cross-Linked Polyethylene (PEX) Pipe
Piping, Plastic
ASTM F 2098-2001
Stainless Steel Clamps for Securing SDR9 Cross-Linked
Polyethylene (PEX) Tubing to Metal Insert Fittings
Joints
ASTM F 2159-2003
Plastic Insert Fittings Utilizing a Copper Ring for SDR 9
Cross-Linked Polyethylene (PEX) Tubing
Joints
ASTM F 2165-2002
Flexible Pre-Insulated Piping
Piping, Plastic
236
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
ASTM F 2262-2004
Cross-Linked Polyethylene / Alumi num / Cross-Linked
Polyethylene Tubing OD Controlled SDR 9
Piping, Plastic
ASTM F2434-2004
Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR9
Cross-linked Polyethylene (PEX) Tubing and SDR9 Cross-
Linked Polyethylene/ Aluminum/Cross-linked Polyethylene
(PEX-AL-PEX) Tubing
Piping, Plastic
AWS A5.8-2004
Filler Metals for Brazing and Braze Welding
Joints
AWS B2.2-91
Brazing Procedure and Performance Qualification
Certiflcation
AWWA CllO-2003
Ductile-Iron and Gray-Iron Fittings, 3 in. through 48 in.
(75 mm through 1200 mm), for Water and Other Liquids
(same as ANSI A21.10-98)
Piping, Ferrous
AWWAClll-2000
Rubber-Gasket Joints for Ductile-Iron Pressure Pipe
^ and Fittings (same as ANSI A2L11-00)
Piping, Ferrous
AWWAC151-2002
Ductile-Iron Pipe, Centrifugally Cast, for Water
(same as ANSI A21.51-91)
Piping, Ferrous
AWWA C153-2000
Ductile-Iron Compact Fittings, 3 in. through 24 in. (76 mm
through 610 mm) and 54 in. through 64 in. (1400 mm
through 1600 mm), for Water Service
. (same as ANSI A21. 53-00)
Piping, Ferrous
1 AWWA C203-2002
Coal-Tar Protective Coatings and Linings for Steel Water
Pipelines - Enameled and Tape - Hot Applied
Piping
AWWA C213-2001
Fusion-Bonded Epoxy Coating for the Interior and Exterior of
Steel Water Pipelines
Piping, Ferrous
AWWA C215-2004
Extruded Polyolefin Coatings for the Exterior of Steel Water
Pipelines
Piping, Ferrous
AWWA C400-2003
Asbestos-Cement Distribution Pipe, 4 in. through 16 in.
(100 mm through 400 mm) for Water Distribution Systems
Piping, Non-MetaUic
AWWA C500-2002
Gate Valves for Water and Sewerage Systems Valves
Valves
AWWA C504-2000
Rubber-Seated Butterfly Valves
Valves
AWWA C507-99
Ball Valves, 6 in. through 48 in. (150 mm through 1200 mm)
Valves
AWWA C510-97
Double Check Valve Backflow-Prevention Assembly
Backflow Protection
AWWA C511-97
Reduced-Pressure Principle Backflow-Prevention Assemblies
Backflow Protection
I AWWA C606-2004
Grooved- and Shouldered-Type Joints
Joints
237
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
AWWA C900-97
Poly (Vinyl Chloride) (PVC) Pressure Pipe, 4 in. through 12 in.,
for Water Distribution
Piping, Plastic
1 AWWA C901-2002
Polyethylene (PE) Pressure Pipe and Tubing, 1/2 in. (13 mm)
through 3 in. (76 mm), for Water Service
Piping, Plastic
AWWA C907-91
Poly (Vinyl Chloride) (PVC) Pressure Fittings for Water - 4 in.
Through 8 in. (100 mm through 200 mm)
Piping, Plastic
CGA V-1
Compressed Gas Association Standard for Compressed Gas
Cylinder Valve Outlet and Inlet Connection
Valves
CGA S-1.3
Pressure Relief Device Standards-Part 3-Stationary Storage
Containers for Compressed Gases
Fuel Gas
CISPI 301-2004a
Hubless Cast-iron Soil Pipe and Fittings for Sanitary and
Storm Drain, Waste, and Vent Piping Applications (Note 1)
Piping, Ferrous
CISPI 310-2004
Couplings for Use in Connection with Hubless Cast-Iron Soil
Pipe and Fittings for Sanitary and Storm Drain, Waste, and
Vent Piping Applications
Joints
CSA 3-92
U.S. Requirements for Excess Flow Valves
Valves
CSA A257-2003
Concrete Pipe arid Manhole Sections
Piping
CSA B45-2002
Plumbing Fixtures
Fixtures
CSA B45.1-2002
Ceramic Plumbing Fixtures
Fixtures
CSA B45.2-2002
Enameled Cast-Iron Plumbing Fixtures
Fixtures
CSA B45.3-2002
Porcelain-Enameled Steel Plumbing Fixtures
Fixtures
CSA B45.4-2002
Stainless Steel Plumbing Fixtures
Fixtures
CSA B45.5-2002
Plastic Plumbing Fixtures
Fixtures
CSA B45.9-2002
Macerating Systems and Related Components
DWV Components
CSA B45.10-2001
Hydromassage Bathhibs
Fixtures
CSA B45.11-2004
Glass Lavatories
Fixtures
CSA B64-2001
Backflow Preventers and Vacuum Breakers
Backflow Protection
CSA B64.1.1-2P01
Vacuum Breaker, Atmospheric Type (AVB)
Backflow Protection
CSA B64.1.2-2001
Vacuum Breaker, Pressure Type (PVB)
Backflow Protection
CSA B64.2-2001
Vacuum Breaker, Hose Connection Type (HCVB)
Backflow Protection
238
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
CSAB64.2.1. 1-2001-
Vacuum Breaker, Hose Connection Type with Automatic
Drainage Feature (HCVB)
Backflow Protection
CSA B64.4-2001
Backflow Preventers, Reduced Pressure Principle Type (RP)
Backflow Protection
CSA B64.4.1-2001
Backflow Preventers, Reduced Pressure Principle T)^e for
Fire System (RPF)
Backflow Protection
CSA B64.5-2001
Backflow Preventers, Double Check Valve Type (DVCA)
Backflow Protection
CSA B64.5.1-2001
Backflow Preventers, Double Check Valve Type for Fire
System (DVCAF)
Backflow Protection
CSA B64.7-2001
Vacuum Preventers, Laboratory Faucet Type (LFVB)
Backflow Protection
CSA B125-2001
Plumbing Fittings
Valves
CSA B137.1-2002
Polyethylene Pipe, Tubing, and Fittings for Cold Water
Pressure Services
Piping, Plastic
CSA B137.5-2002
Crosslinked Polyethylene (PEX) Tubing Systems for
Pressure Applications
Piping, Plastic
CSA B137.9-2002
Polyethylene/Aluminum/Polyethylene Composite
Pressure-Pipe Systems
Piping, Plastic
CSA B137.10-2002
Crosslinked Polyethylene / Aluminum / Crosslinked
Polyethylene Composite Pressure-Pipe Systems
Piping, Plastic
CSA B181.3-2002
Polyolefin Laboratory Drainage Systems
Piping/Plastic
CSA B242-80(R04)
Groove and Shoulder Type Mechanical Pipe Couplings
Fittings
CSA B272-93 (ROD)
Prefabricated Self-Sealing Roof Vent Flashing
Fittings
CSA B356-2000
Water Pressure Reducing Valves for Domestic Water
Supply Systems
Valves
CSA G401-2001
Corrugated Steel Pipe Products
Fittings
lAPMO PS 1-2004
Prefabricated Septic Tanks
DWV Components
lAPMO PS 4-2004
Drains for Prefabricated and Precast Showers
Fixtures
lAPMO PS 14-2002
Flexible Metallic Field Fabricated Water Connectors
Piping
lAPMO PS 16-2004
Subdrains for Built-Up Shower Pans
Fixtures
lAPMO PS 23-2004
Dishwasher Drain Air Gaps
Backflow Protection
lAPMO PS 25-2002
Metallic Fittings for Joining Polyethylene Pipe for Water
Service and Yard Piping
Joints
239
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
lAPMO PS 33-2004
Flexible PVC Hose for Pools, Hot Tubs, Spas and Jetted Bathtub
Piping, Plastic
lAPMO PS 34-2003
Encasement Sleeve for Potable Water
Pipe and Tubing
Piping
lAPMO PS 36-90
Lead-Free Sealing Compounds for Threaded Joints
Joints
lAPMO PS 37-90
Black Plastic PVC or PE Pressure-Sensitive Corrosion
Preventive Tape
Piping
lAPMO PS 40-2001
Anodeless Transition Riser for Use with PVC Gas Yard Piping
Fuel Gas
lAPMO PS 42-96
Pipe Alignment and Secondary Support Systems
Piping
lAPMO PS 43-91
Cushioned Bathtubs and Whirlpool Bathtub Appliances
Fixtures
1 lAPMO PS 46-2004
Non-Integral Tile Flange Kits
Miscellaneous
lAPMO PS 50-2003
Flush Valves with Dual Flush Devices For Water Closets
Fixtures
lAPMO PS 51-98
Plastic and Metallic Expansion Joints
Joints
LAPMO PS 52-2004b
Siunps and Sewage Ejector Tanks
DWV Components
lAPMO PS 53-92
Grooved Mechanical Pipe Couplings and Grooved End
Fittings
Joints
lAPMO PS 54-2003a
Metallic and Plastic Utility Boxes
Miscellaneous
lAPMO PS 55-92
Bathwaste Strainer Drains
Fixtures
lAPMO PS 57-2002
PVC HydraulicaUy Actuated Diaphragm Type Water
Control Valves
Valves
lAPMO PS 59-92
Septic Effluent and Waste Water Diverter Valves
DWV Components
lAPMO PS 60-96
Sewage Holding Tank Containing Sewage Ejector Pump for
Direct-Moimted Water Closet
DWV Components
lAPMO PS 61-92
Fabricated Stainless Steel Security Water Closets
Fixtures
1 lAPMO PS 63-2004a
Plastic Leaching Chambers
DWV Components
lAPMO PS 64-98
Pipe Flashings
Piping
1 lAPMO PS 65-2002
Air Gap Units for Water Conditioning Equipment Installation
Backflow Protection
lAPMO PS 66-2000
Dielectric Waterway Fittings
Piping
lAPMO PS 67-93
Early-Closure Replacement Flappers or Early-Closure
Replacement Flapper With Mechanical Assemblies -
Fixtures
240
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
1 lAPMO PS 69-2003a
Plastic Bathwaste and Overflow Assemblies
Piping, Plastic
1 lAPMO PS 72-2003
Valves with Atmospheric Vacuum Breakers
Valves
lAPMO PS 73-93
Dental Vacuum Pumps
Miscellaneous
lAPMO PS 76-95
Ballcock or Flushometer Valve Tailpiece Trap Primers and
Trap Primer Receptors/ Adapters
DWV Components
lAPMO PS 79-2003
Multiport Electronic Trap Primer
DWV Components
lAPMO PS 80-2003b
Grease Interceptors and Clarifiers
DWV Components
lAPMO PS 81-2000
Precast Concrete Seepage Pit Liners and Covers
DWV Components
lAPMO PS 82-95
Fiberglass (Glass Fiber Reinforced Thermosetting Resin)
Fittings
Piping, Plastic
lAPMO PS 85-95
Tools for Mechanically Formed Tee Connections in
Copper Tubing
Piping
lAPMO PS 86-95
Rainwater Diverter Valve for Non-Roofed Area Slabs
DWV Components
lAPMO PS 87-95
Diverter and Shutoff Valves for Pool/Spas
Valves
lAPMO PS 88-2002
Pre-Pressurized Potable Water Tanks
Miscellaneous
lAPMO PS 89-95
Soaking and Hydrotherapy (Whirlpool) Bathtubs with
Hydraulic Seatlift
Fixtures
lAPMO PS 90-2003
Elastomeric Test Caps/Cleanout Caps
DWV Components
lAPMO PS 91-95
Plastic Stabilizers for Use with Plastic Closet Bends
Piping, Plastic
lAPMO PS 92-2003
Heat Exchangers
Miscellaneous
lAPMO PS 93-2004a
Water Closet Seats with Spray, Water Closet Seats with Spray
and other Devices with Spray for Water Closet
Fixtures
lAPMO PS 94-2001a
P-Trap, Supply Stop, and Riser Insulated Protector
Miscellaneous
lAPMO PS 95-2001
Drain, Waste, and Vent Hangers and Plastic Pipe
Support Hooks
Piping
1 lAPMO PS 96-2002
Passive Direct Solar Water Heaters
Miscellaneous
lAPMO PS 97-2001
Mechanical Cast-iron Closet Flanges
Piping, Ferrous
lAPMO PS 98-96
Prefabricated Fiberglass Church Baptistries
Fixtures
1 lAPMO PS 99-2004
Terrazzo Marble, Concrete, and Granite Plumbing Fixtures
Fixtures
241
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
lAPMO PS 100-96
Porous Filter Protector for Subdrain Weep Holes
DWV Components
lAPMO PS 101-97
Suction Relief Valves
Valves
1 lAPMO PS 102-2004a
Pedestal Lavatory Trap
DWV Components
lAPMO PS 104-97
Pressure Relief Connection for Dispensing Equipment
Valves
lAPMO PS 105-97
Polyethylene Distribution Boxes
DWV Components
lAPMO PS 106-98
Prefabricated, Tileable Shower Receptors
Fixtures
lAPMO PS 107-98
Aramid-Reinforced Rubber Hose for Use in Non-Potable
Water Radiant Heating and Snow Melting
Piping, Plastic
lAPMO PS 108-98
Restaurant Fire Suppression Systems
Appliances
lAPMO PS 110-99
PVC Cold Water Compression Fittings
Fittings
LAPMO PS 111-99
PVC Cold Water Gripper Fittings
Fittings
lAPMO PS 112-99
PVC Plastic Valves for Cold Water Distribution Systems
Outside a Building and CPVC Plastic Valves for Hot and
Cold Water Distribution Systems
Valves
lAPMO PS 113-99^>
Hydraulically Powered Household Food Waster Grinders
Appliances
lAPMO PS 114-99''
Remote, Floor Box Industrial Water Supply, Air Supply,
Drainage
Miscellaneous
1 lAPMO PS 115-2002
Hot Water Demand or Automatic Activated Hot Water
Pumping Systems
Miscellaneous
lAPMO PS 116-99
Hot Water Circulating Devices Which Do Not Use a Pimip
Miscellaneous
1 IAPMOPS117-2004a
Press Type or Plain End Rubber Gasketed with Nail Connector
Fittings
Fittings for Copper Alloy Installation on Copper Tubing
LAPMO PS 118-2000
FOG (Fats, Oils, Greases) Disposal Systems
DWV Components
lAPMO PS 119-2000
Water Energized Sump Pump
Miscellaneous
IAS 1-91
U.S. Requirements for Indirect Water Heaters for Use with
External Heat Source
Miscellaneous
IAS LC lb-2001
Fuel Gas Piping Systems Using Corrugated Stainless Steel
Fuel Gas
CSA 6.26-M99
Tubing (CSST) Fuel Gas
ISO Guide 65-96
General Requirements for Bodies Operating Product
Certification Systems
Certification
MSS SP-25-98
Standard Marking System for Valves, Fittings, Flanges, and Unions
Piping
242
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
MSS SP-42-2004
Class 150 Corrosion-Resistant Gate-Globe, Angle, and
Check Valves with Flanged and Butt Weld Ends
Piping, Ferrous
MSS SP-44-96
Steel Pipeline Flanges
Piping, Ferrous
MSS SP-58-2002
Pipe Hangers and Supports - Materials, Design,
and Manufacture
Piping
MSS SP-67-2002a
Butterfly Valves
Valves
MSS SP-69-2002
Pipe Hangars and Supports - Selection and Application
Piping
MSSSP-70-98
Cast-Iron Gate Valves, Flanged and Threaded Ends
Valves
MSSSP-71-97
Cast-Iron Swing Check Valves, Flanged and Threaded Ends
Valves
MSS SP-72-99
Ball Valves with Flanged or Butt-Welding Ends for
General Service
Valves
1 MSS SP-73-2003
Brazing Joints for Wrought and Cast Copper AUoy Solder Joint
Pressure Fittings
Joints
MSSSP-78-98
Cast-iron Plug Valves, Flanged and Threaded Ends
Valves
1 MSS SP-80-2003
Bronze Gate-Globe, Angle, and Check Valves
Valves
MSS SP-83-2001
Class 300 Steel Pipe Unions Socket-Welding and Threaded
Piping, Ferrous
MSSSP-89-98
Pipe Hangars and Supports - Fabrication and Installation
Practices
Piping
MSS SP-104-2003
Wrought Copper Solder Joint Pressure Fittings
Piping, Copper Alloy
MSS SP-106-2003
Cast Copper Alloy Flanges and Flanges Fittings, CLass 125,
150, and 300
Piping, Copper Alloy
MSS SP-109-97
Welded Fabricated Copper Solder Joint Pressure Fittings
Piping, Copper Alloy
MSSSP-123-98
Non-Ferrous Threaded and Solder-Joint Unions for Use with
Copper Water Tube
Piping, Copper Alloy
NFPA13R-2002
Installation of Sprinkler Systems in Residential
Occupancies up to and Including Four Stories in Height
Miscellaneous
NFPA 13D-2002
Installation of Sprinkler Systems in One- and Two-Family
Dwellings and Manufactured Hornes
Miscellaneous
NFPA 31-2001
Installation of Oil-Burning Equipment
Miscellaneous
NFPA 54-2002
National Fuel Gas Code (same as ANSI Z223.1)
Fuel Gas
1 NFPA 58-2004
Storage and Handling of Liquefied Petroleum Gases
Fuel Gas
243
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
1 NFPA 85-2004
Boiler and Combustion Systems Hazards Code
Appliances
NFPA 99-2002
Health Care Facilities
Piping
NFPA 99C-2002
Gas and Vacuum Systems
Piping
NFPA 130-2003 .
Fixed Guideway Transit and Passenger Rail Systems
Miscellaneous
NFPA 211-2003
Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
Miscellaneous
NFPA 502-2004 .
Road Timnels, Bridges, and Other Limited Access Highways
Miscellaneous
NFPA 1989-2003
Breathing Air Quality for Fire and Emergency Services
Respiration Protection
Miscellaneous
NSF 3-2003
Commercial Spray-Type Dishwashing and Glasswashing
Machines
Appliances
NSF 12-2003e
Automatic Ice Making Equipment
Appliances
NSF 14-2004'
Plastic Piping Components and Related Materials
Piping, Plastic
NSF 18-2004
Manual Food and Beverage Dispensing Equipment
Appliances
NSF24-88(R96)
Plumbing System Components for Manufactured Homes
and Recreational Vehicles
Miscellaneous
NSF 29-2003
Chemical Feeders for Commercial Dishwashers
Appliances
NSF 40-2000
Residential Wastewater Treatment Systems
DWV Components
NSF 41-99
Non-Liquid Saturated Treatment Systems
DWV Components
NSF42-2002e
Drinking Water Treatment Units-Aesthetic Effects
Appliances
NSF 44-2004
Residential Cation Exchange Water Softeners
Appliances
NSF 46-2004
Evaluation of Components and Devices Used in Wastewater
Treatment Systems
DWV Components
NSF 53-2004
Drinking Water Treatment Units-Health Effects
Appliances
NSF 58-2004
Reverse-Osmosis DrirJ<ing Water Treatment Systems
Appliances
NSF 61-2004
Drinking Water System Components-Health Effects
Miscellaneous
NSF 62-2004
Water Distillation Systems
Appliances
NSPI 1-2003
Public Swimming Pools
Swimming Pools
and Spas
PDI G-101-85
Testing and Rating Procedure for Grease Interceptors with
Appendix of Sizing and Installation Data
DWV Components
244
MANDATORY REFERENCED STANDARDS
Table 14-1
Standard Number
Standard Title
Application
PDI-WH 201-92
Water Hammer Arresters
Piping
1 SAE J 512-97
Automotive Tube Fittings
Fittings
SAE J1670-93
Type F Clamps for Plumbing Applications
Joints
SAMA LF6a
Medical Care Facility Brassware
Miscellaneous
UL 80-2004
Steel Inside Tanks for Oil-Burner Fuel
Miscellaneous
UL 103-2001
Factory-Built Chimneys for Residential Tjrpe and Building
Heating Appliances
Miscellaneous
UL 125-97
Valves for Anhydrous Ammonia and LFG (Other than
Safety Relief)
Valves
UL 132-97
Safety Relief Valves for Anhydrous Ammonia and LFG
Valves
UL 144-99
LFG Regulators
Valves
UL 174-2004
Household Electric Storage Tank Water Heaters
Appliances
UL 252-2003
Compressed Gas Regulations
Valves
UL 296-2003
Oil Burners
Appliances
UL 343-97
Pumps for Oil-Burning Appliances
Pumps
UL 352-97
Constant-Level Oil Valves
Valves
UL 378-93
Draft Equipment
Miscellaneous
UL 399-93
Drinking- Water Coolers
Appliances
1 UL 430-2004
Waste Disposers
Appliances
UL 441-96
Gas Vents
Miscellaneous
UL 443-95
Steel Atixiliary Tanks for Oil-Burner Fuel
Miscellaneous
UL 499-97
Electrical Heating Appliances
Appliances
UL 563-95
Ice Makers
Appliances
UL 569-95
Pigtails and Flexible Hose Connectors for LP-Gas
Fuel Gas
1 UL 723-2004
Standard Test for Surface Burning Characteristics of
Building Materials
Miscellaneous
UL 726-95
Oil-Fired Boiler Assemblies
Appliances
UL 732-95
Oil-Fired Storage Tank Water Heaters
Appliances
245
Table 14-1
UNIFORM PLUMBING CODE
Standard Number
Standard Title
Application
UL 749-97
Household Dishwashers
Appliances
UL 778-2002
Motor-Operated Water Pumps
Pumps
UL 834-2004
Heating, Water Supply, and Power Boilers-Electric
Appliances
UL 921-96
Commercial Electric Dishwashers
Appliances
UL 959-2001
Factory Built, Medium Heat Appliance Chimneys
Miscellaneous
UL 1206-2003
Electric Commercial Clothes Washing Equipment
Appliances
UL 1453-2004
Electric Booster and Commercial Storage Tank Water
Heaters
Appliances
WQA S-300-91
Point-of-Use Low Pressure Reverse Osmosis Drinking
Water Systems
Appliances
Notes:
1 Although this standard is referenced in Table 14-1, some of the pipe, tubing, fittings, valves, or fixtures included in the
standard are not acceptable for use under the provisions of the Uniform Plumbing Code.
4 See Section 316.1.3 for restriction.
5 Alloy C85200 for cleanout plugs.
6 Limited to domestic sewage.
7 Type II only.
9 ASSE 1066 is not intended to linut the maximum outlet temperature at point of use.
10 See Section 315.0 for trenching, excavation, and backfilling requirements when installing building drains and sewers.
Engineers may wish to consult ASTM D 2321 when preparing plans and specifications for sewer mains or specific
projects.
246
MANDATORY REFERENCED STANDARDS Table 14-1 Index
TABLE 14-1INDEX
Standards for Materials, Equipment,
Joints, and Connections
Standard Number page Code Sections
Appliances
AHAM DW-1-2004 223
AHAM DW-2PR-92 223
AHAM FWD-1-92 223
ANSI Z21.10.1-2004 • CSA 4.1a02 224
ANSI Z21.10.3-2004 224
ANSI Z21.12b-94 224
ANSI Z21.13-2004 224
ANSI Z21.24-2001 224 1212.1(3)
ANSI Z21.69-03-CSA 6.16-M03 224 1212.1(6)
ANSI Z21. 86-2004 • CSA 2.32-2004 224
ARI 1010-02 225
ASME A112.4.1-93(R02) 225
ASSE 1006-86 228
ASSE 1007-86 228
ASSE 1008-86 228
ASSE 1009-90 228
ASSE 1023-79 229 : . . .
lAPMOPS 108-98 242
LAPMOPS 113-99'^' 242
NFPA 85-2004 244
NSF 3-2003 244
NSF 12-2003e 244
NSF 18-2004 244
NSF 29-2003 244
NSF 42-2002E 244
NSF 44-2004 244
NSF 53-2004 244
NSF 58-2004 244
NSF 62-2004 244
UL 174-2004 245
UL 296-03 245
UL 399-93 245 ,
UL 430-2004 245
UL 499-97 245
UL 563-95 245
UL 726-95 245
UL 732-95 245
UL 749-97 246
UL 834-2004 246
247
Table 14-1 Index UNIFORM PLUMBING CODE
UL 921-96 246 .
UL 1206-03 246 .
UL 1453-2004 246 .
WQA S-300-91 .246 .
Backflow Protection
ASSE 1001-2002 228 .
ASSE 1002-99 228 ,
ASSE 1004-90 228 ,
ASSE 1011-2004 228 ,
ASSE 1012-2002 228 ,
ASSE 1013-2005 228 ,
ASSE 1015-2005 228 .
ASSE 1019-2004 229 .
ASSE 1020-2004 .229 ,
ASSE 1021-2001 229 ,
ASSE 1022-2003 229 ,
ASSE 1024-2003 229 ,
ASSE 1032-2004 229 ,
ASSE 1035-2002 229 ,
ASSE 1037-90 229
ASSE 1047-2005 229
ASSE 1048-2005 229
ASSE 1052-2004 229
ASSE 1055-97 229
ASSE 1056-2001 229
ASSE Series 5000-2004 229
AWWA C510-97 237
AWWA C511-97 237
CSA B64.1.1-01 238
CSA B64.1.2-01 238
CSA B64.2-01 238
CSA B64.2.1.1-01 239
CSA B64.4.4-01 239
CSA B64.4.1-01 239
CSA B64.5-01 239
CSA B64.5.1-01 239
CSA B64.7-01 239
lAPMO PS 23-2004 239
lAPMO PS 65-2002 240
Certification
I ASME Al 12.20.2-2004 227
ASME Section IX 228
248
MANDATORY REFERENCED STANDARDS Table 14-1 Index
Certification (continued)
I ASSE 6000-2004 230
AWS B2.2-91 237
ISO Guide 65-1996 242
DWV Components
ASME A112.6.3-01 225
ASME A112.36.2M-91(R02) 227
ASSE 1044-2001 229
CSA B45.9-02 238
lAPMO PS 1-04 239
I LAPMO PS 52-2004b 240
lAPMO PS 59-92 240
lAPMO PS 60-96 240
I lAPMO PS 63-2004a 240
lAPMO PS 76-95 241
I lAPMO PS 79-2003 241
I lAPMO PS 80-03b 241
lAPMO PS 81-2000 241
lAPMO PS 86-95 241
I lAPMO PS 90-03 241
lAPMO PS 100-96 242
I lAPMO PS 102-2004a 242
lAPMO PS 105-97 242
LAPMO PS 118-2000 242 1015.4, 1015.5
NSF 40-2000 244
NSF 41-99 244
I NSF 46-2004 244
PDI G-101-85 244
Fittings
CSA B242-80(R04) 239
CSA B272-93(R00) 239
CSA G401-01 239
lAPMO PS 110-99 242
lAPMO PS 111-99 242
lAPMO PS 117-04a 242
SAE J512-97 245
Fixtures
I ANSI A118.10-99 223
ANSI Z124.1-95 224
ANSI Z124.2-95 224
ANSI Z124.3-95 224
249
Table 14-1 Index UNIFORM PLUMBING CODE
Fixtures (continued)
ANSI Z124.4-96 224
ANSI Z124.5-97 225
ANSI Z124.6-97 225
ANSI Z124.7-97 225
ANSI Z124.8-90 225
ANSI Z124.9-2004 225 :
ASME 112.1.3-2000 .225
ASME A112.3.4-2000 (R04) 225
ASME A112.4.2-03 225
ASME A112.6.1M-97 225
ASME Al 12.6.2-2000 (R04) . ; 225
ASME A112.6.7-01 225
ASME A112.14.3-2001 226
ASME A112.14.4-2001 226
ASME A112.19.1M-94(R04) 226
ASME A112.19.2M-03 226
ASME A112.19.3M-2001 (R04) 226
ASME A112.19.4M-94(R04) 226
ASME A112.19.5-99 226
ASME A112.19.7M-95 226
ASME A112.19.9M-91(R02) 226
ASME A112.19.10-03 226
ASME A112.19.12-2000 226
ASME A112.19.13-02 226
ASME A112.19.14-01 226
ASME A112.19.15-01 226 :
ASSE 1014-2005 228
ASTM D 4068-2001 234
ASTM D 4551-96(R01) .234
ASTM D 6104-97 (R03) 234
CSA B45-02 238
CSA B45.1-02 238
CSA B45.2-02 238
CSA B45.3-02 238
CSA B45.4-02 238
CSA B45.5-02 238
CSA B45.10-01 238
lAPMO PS 4-2004 239
lAPMO PS 16-2004a 239
lAPMO PS 43-91 240
lAPMO PS 50-2003 240
LAPMO PS 55-92 240
lAPMO PS 61-92 240
250
MANDATORY REFERENCED STANDARDS
Table 14-1 Index
Fixtures (continued)
lAPMO PS 67-93 240
lAPMO PS 89-95 241
I lAPMO PS 93-2004a 241
lAPMO PS 98-96 241
I lAPMO PS 99-04 241
lAPMO PS 106-98 242
Fuel Gas
ANSI Z21 .80-2003 -CSA 6.22-M03 224 1209.7.2, 1209.7.5(A,1)
ANSI Z21. 81-1998 •CSA 6.25-M98 224
ANSI Z223.1-02 225
lAPMO PS 40-2001 240
IAS LC lb-01«CSA 6.26-M99 242 1209.5.3.4
NFPA 54-2002 243 Chapter 5
NFPA 58-2004 243 Chapters 5 and 12, 1213.0
UL 569-95 245
Joints
ANSI B2.1-90 223
ANSI Z21.41-03«CSA 6.9-M03 224
ASME B1.20.1-83(R01) 227 1316.6.1(2), 1209.5.7(A)
ASME Bl.20.3-76 (R03) 227
ASME B16.5-2003 227
ASME B16.21-92 227
ASME B16.50-2001 228 : 1316.4
ASTM B 29-2003 230
ASTM B 32-04 230
ASTM B 813-00^1 231
ASTM B 828-02 231
ASTM C 425-2004 231
ASTM C 443-2003 231
ASTM C 564-03a 231
ASTM C 1173-2004 . .' 232
ASTM D 1869-95(R00) 232
ASTM D 2235-2004 232
ASTM D 2564-2004 233
ASTM D 2657-2003 233
ASTM D 2672-96a (R03) 233
ASTM D 2855-96 (R02) 233
ASTM D 3122-95 (R02) 234
ASTM D 3138.2004 234
ASTM D 3139-98 234
I ASTM D 3212-96a (ROSy 234
251
Table 14-1 Index UNIFORM PLUMBING CODE
Joints (continued)
ASTM F 402-93(R99) 234 -
ASTM F 493-2004 235
ASTM F 656-2002 235
AWS A5.8-2004 237 1319.1
AWWA C606-2004 237
I CISPI 310-2004a 238
I lAPMO PS 25-2002 239
lAPMO PS 36-90 240
lAPMO PS 51-98 240
lAPMO PS 53-92 240
I MSS SP-73-2003 243
SAE J1670-93 245
Kitchen, Lavatory, and Shower Fittings with Attached Hose Outlets
I ASME A112.18.3-03 226
Miscellaneous
ANSI/ICC A117.1-2003 223 411.7, Table 4-1
ANSI /CSA LC3-2000 223
ANSI Z4.1-1995 223 Table 4-1
ANSI Z358.1-2004 225
ASHRAE 90.1-2004 225
ASME A112.4.7-02 225
ASME Section IV 228
ASME Section VIII Boiler & Pressure Vessel Code .228 1326.2(2)
ASTM B 152-2000 231
ASTM B 370-03 , 231
ASTM C 478-03a 231 . . .
ASTM D 4101-2004a 234
ASTM E 84- 2004 234 701.1.2, 903.1.2, 1101.3
ASTM E 119-2000a 234
ASTM E 814-2002 234
lAPMO PS 54-2003a 240
lAPMO PS 73-93 241
lAPMO PS 88-02 241
lAPMO PS 92-03 241
lAPMO PS 94-2001a 241
lAPMO PS 96-02 241
lAPMO PS 114-99^^ 242
lAPMO PS 115-02 242
lAPMO PS 116-99 242
lAPMO PS 119-2000 242
NFPA 13R-02 243
252
MANDATORY REFERENCED STANDARDS Table 14-1 Index
Miscellaneous (continued)
NFPA 13D-02 243
NFPA 31-2001 243 ; .506.3, 1202.0
NFPA 211-2003 244 508.6.2, 510.5.1.2, 510.5.1.3, 510.5.4
NSF 24-88(R96) 244
NSF 61-04 244
SAMA LF6a 245
UL 80-04 245
UL 103-01 245
UL 378-93 .245
UL 441-96 245 ,
UL 443-95 245
UL 723-2004 245 701.1.2, 903.1.2, 1101.3
Piping
ANSI A13.1-96(R03) .223
ASME A112.4.3-99 (R04) 225
ASME A112.18.6-03 226
ASSE 1010-2004 228
AWWA C203-2002 237
CSA A257-03 238
lAPMO PS 34-03 240
lAPMO PS 37-90 240
lAPMO PS 42-96 240
lAPMO PS 64-98 240
lAPMO PS 66-2000 240
lAPMO PS 85-95 241
lAPMO PS 95-2001 241
MSS SP-25-98 242
MSS SP-58-02 243 1211.2.6, 1318.8
MSS SP-69-02 243 , 1318.8
NFPA 99-2002 244 Chapter 13
NFPA 99C-2002 244
PDI-WH 201-92 245
Piping, Copper Alloy
ASME B16.15-85 (R04) 227
ASME B16.18-2001 227
ASME B16.22-2001 227 1316.4
ASME B16.23-2002 227
ASME B16.24-2001 227
ASME B16.26-88 227
I ASME B16.29-2001 227
j ASTM B 42-2002^^ 230
I ASTM B 43-98(R04) 230
253
Table 14-1 Index UNIFORM PLUMBING CODE
Piping, Copper Alloy (continued)
ASTM B 75-2002 231
ASTM B 88-2003 231 1209.5.3.2, 1316.3, 1325.3
ASTM B 135-2002 231
ASTM B 280-2003 231 1209.5.3.2, 1316.3, 1325.3
ASTM B 302-2002 231
ASTM B 306-2002 231
ASTM B 447-2002 231
ASTM B 584-2004 231
ASTM B 587-97^'(R03) 231
ASTM B 687-99 231
I ASTM B 819-2000 231 1316.3, 1316.3.1, 1325.3
I MSS SP-123-1998 243
Piping, Ferrous
I ANSI A21.10-03 223
ANSI A21.11-2000 223
I ANSI A21.51-02 223
ANSI A21.53-2000 223
ASME A112.3.1-93 225
IASME B16.1-98 227 1209.5.10
ASME B16.3-98 227
ASME B16.4-98 227
ASME B16.12-98 227
ASME B16.39-98 227
ASME B16.47-96 227
ASME B36.10M-2004 228 1209.5.2.2
ASME B36.19-85(R94) 228
ASTM A 47-99 (R04) 230
ASTM A 53-04a 230 1209.5.2.2
ASTM A 74-04a 230
ASTM A 126-2004 230
ASTM A 197M-2000 230
ASTM A 312-04b 230
ASTM A 377-03 230
ASTM A 518-99(R03) 230
ASTM A 536-84(R04) 230
ASTM A 653M-2004a 230
ASTM A 733-2003 230
ASTM A 861-2004 230
ASTM A 888-2004a 230
ASTM C 1277-2004 232
AWWA CllO-2003 237
AWWA Clll-2000 237
AWWA C151-2002 237
254
MANDATORY REFERENCED STANDARDS Table 14-1 Index
Piping, Ferrous (continued)
AWWA C153-2000 237
AWWA C213-2001 237
I AWWA C215-2004 237
CISPI 301-2004a 238
lAPMO PS 97-2001 241
\ MSS SP-42-2004 243
MSS SP-44-96 243
MSS SP-83-2001 243
Piping, Non-Metallic
I ASTM C 14-2003 231
ASTM C 296-2000 231
I ASTM C 412-2003 231
ASTM C 428-97(R02)''^ 231
ASTM C 700-2002 232
ASTM C 1053-2000 232
I AWWA C400-2003 237
Piping, Plastic
ASTM C 1440-2003 232 :
ASTM C 1460-2004 232
ASTM C 1461-2002 232
ASTM D 1527-99^^ 232
ASTM D 1784-03 232
ASTM D 1785-04a ; 232
ASTM D 2104-2003 232
ASTM D 2239-2003 232
ASTM D 2241-2004b 232
ASTM D 2282-99-=^ 232 :
ASTM D 2321-2000 232
ASTM D 2447-2003 233
ASTM D 2464-99^^ 233 ;......
ASTM D 2466-2002 233
ASTM D 2467-2004^1 233
ASTM D 2513-2004a 233 1209.5.4, 1209.5.4.2, 1209.5.9, 1211.1.7(B)
ASTM D 2517-2000'=i 233
ASTM D 2609-2002 233
ASTM D 2661-2002 233 :
ASTM D 2665-2004a 233
ASTM D 2680-2001 233
ASTM D 2729-2003 .233
ASTM D 2737-2003 233
ASTM D 2751-96a 233
ASTM D 2846-99''' 233 316.1.6
255
Table 14-1 Index UNIFORM PLUMBING CODE
Piping, Plastic (continued)
ASTM D 2996-2001 233
ASTM D 3034-2004a 233
ASTM D 3035-2003a 233
ASTM D 3311-2002^^ 234
ASTM D 3965-2004 234
ASTM F 405-97 234
ASTM F 409-2002 234
ASTM F 437-99 234
ASTM F 438-2004 234
ASTM F 439-2002^^ 234
ASTM F 441-2002 235
ASTM F 442-99 235
ASTM F480-2002 235
ASTM F 628-2001 235
ASTM F 667-97 235
ASTM F 714-2003 235
ASTM F 789-2003 235
ASTM F 794-2003 235
ASTM F 810-2001 235
ASTM F 876-2004 235
ASTM F 877-2002a 235
ASTM F 891-2004 235
ASTM F 949-2003 235
ASTM F 1216-2003 235
ASTM F 1281-2003 235
ASTM F 1282-2003 235
ASTM F 1412-2001'=^ 236
ASTM F 1673-2004 236
ASTM F 1743-96 (R03) 236
ASTM F 1807-2004 236
ASTM F 1866-98 236
ASTM F 1924-2001^^ 236
ASTM F 1948-99a^^ 236
ASTM F 1960-2003 .236
ASTM F 1961-2002a 236
ASTM F 1970-2001 236
ASTM F 1973-2002 236
ASTM F 2080-2004 236
ASTM F 2165-02 236
ASTMF2262-04 237
AWWA C900-97 238
AWWA C901-2002 238
CSA B 137.1-02 239
256
MANDATORY REFERENCED STANDARDS Table 14-1 Index
Piping, Plastic (continued)
CSA B 137.5-02 239
CSA B 137.9-02 239
CSAB 137.10-02 239
CSA B 181.3-02 239
lAPMO PS 33-04 240
I lAPMO PS 69-03a 241
lAPMO PS 82-95 241 ;
lAPMO PS 91-95 241
lAPMO PS 107-98 242 :
I NSF 14-20041 244
Pumps
UL 343-97 245
UL 778-2002 246
Swimming Pools and Spas
ANSI Z21.56-01»CSA 4.7-2001 224
ASME A112.19.8M-87(R96) 226
ASME A112.20.1-2004 227
NSPI 1-2003 244 ,
Valves
ANSI Z21.15-97 224
ANSI Z21.22-00 224
ASME A112.14.1-75 2003 226
ASME A112.18.1M-2005 226 603.3.10, 603.4.22
ASME A112.18.7-99 (R04) 226
ASME A112.21.3M-85 (ROl) .227
ASME B16.33-2002 227
ASME B16.34-96 227
ASSE 1003-2001 228
ASSE 1005-99 228
ASSE 1016-2005 228 418.0
ASSE 1017-2003 .228
ASSE 1018-2001 229
ASSE 1025-78 229
ASSE 1062-97 229
ASSE 1066-97 229
ASSE 1070-2004 ; . . .229
AWWA C500-2002 237
AWWA C504-2000 237
AWWA C507-99 237
CSA 3-92 238
CSA B 125-01 239
257
Table 14-1 Index UNIFORM PLUMBING CODE
Valves (continued)
CSAB 356-00 .239
lAPMO PS 57-02 .240
lAPMO PS 72-2003 .241 .............:....
lAPMO PS 87-95 .241
lAPMO PS 101-97 .242
lAPMOPS 104-97 ...............: .242 .;.........
lAPMO PS 112-99 .242
MSS SP-67-2002a .243
MSS SP-70-98 243
MSSSP-71-97 .243
MSS SP-72-99 243 ,
MSS SP-78-98 '. 243 ..... .,
MSSSP-80-03 243 ...'.:.....
UL 125-97 .245
UL 132-97 ............................... .245 ........;.
UL 144-99 245
UL 252-03 245
UL 352-97 .245
258
MANDATORY REFERENCED STANDARDS
Table 14-1 Index
ABBREVIATIONS IN TABLE 14-1
AHAM Association of Home Appliance Manufacturers, 1111 19th Street, N.W., Suite 402, Washington
DC 20036.
ANSI American National Standards Institute, Inc., 25 W. 42nd Street, 4th floor. New York, NY 10036.
ARI Air Conditioning and Refrigeration Institute, 400 N, Fairfax Drive> Suite 200, Arlington, VA
22203.
ASCE The American Society of Civil Engineers, 1801 Alexander Bell Drive, Reston, VA 20191.
ASHRAE The American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., 1791 Tullie
Circle, NE, Atianta, GA 30329-2305.
ASME The American Society of Mechanical Engineering, Three Park Avenue, New York, NY 10016.
ASSE American Society of Sanitary Engineering, 901 Canterbury, Suite A, Westlake, Ohio 44145.
ASTM American Society of Testing and Materials, 100 Barr Harbor Drive, West Conshohocken, PA
19428-2959.
AWS American Welding Society, 550 NW Lejuene Road, Miami, EL 33126.
AWWA American Water Works Association, 6666 W. Quincy Avenue, Denver, CO 80235.
CISPI Cast Iron Soil Pipe Instihite, 5959 Shallowf ord Road, Suite 419, Chattanooga, TN 37421 .
CSA Canadian Standards Association, 5060 Spectrum Way, Suite 100, Mississauga, Ontario, L4W
5N6, Canada.
(D) or [D] Discontinued.
el An editorial change since the last revision or reapproval.
FS Federal Specifications, Federal Supply Service, Standards Division, General Services
Adminish-ation, 7th and D Stireets, Washington, DC 20407.
lAPMO International Association of Plumbing and Mechanical Officials, 5001 E. Philadelphia Street,
Ontario, CA 91761.
ICC International Code Council, 5203 Leesburg Pike, Suite 600, Falls Church, VA 22041.
ISO International Organization for Standardization, 1 Rue de Varebre, Casa Postale 56, CH-1211
Geneva 20, Switzerland.
MSS Manufacturers Standardization Society of the Valve and Fittings Industry, 127 Park Street, N.E.,
Vienna, VA 22180.
NFPA National Fire Protection Association, P.O. Box 9101, 1 Batterymarch Park, Quincy,
MA 02269-9101.
NSF NSF International, 789 Dixboro Road, Ann Arbor, MI 481 13-0140
NSPI National Spa and Pool Institute, 2111 Eisenhower Avenue, Alexandria, VA 22314.
PDI Plumbing and Drainage Institute, 800 Turnpike Sti-eet, Suite 300, North Andover, MA 01845.
UL Underwriters' Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062.
WQA Water Quality Association, 4151 Naperville Road, Lisle, IL 60532-1088.
259
Table 14-1 Index UNIFORM PLUMBING CODE
260
CHAPTER 15
FIRESTOP PROTECTION
1501.0 General Requirements.
1501.1 Applicability. All piping penetrations of
required fire-resistance-rated walls, partitions,
floors, floor/ceiling assemblies, roof/ceiling
assemblies, or shaft enclosures shall be protected in
accordance with the requirements of the Building
Code, and this chapter.
1502.0 Plans and Specifications.
1 502.1 Plans and specifications shall indicate with
sufficient detail how penetrations of fire-resistancfe-
rated assemblies shall be firestopped prior to
obtaining design approval.
1503.0 Installation.
1503.1 Firestop materials shall be installed in
accordance with this chapter, the Building Code, and
the manufacturer's instructions.
1504.0 Definitions.
1504.1 Penetration Firestop System. A specific
assemblage of field-assembled materials, or a factory-
made device, which has been tested to a standard test
method and, when installed properly on penetrating
piping materials, is capable of maintaining the fire-
resistance rating of assemblies penetrated.
1504.2 F Rating. The time period that the
penetration firestop system limits the spread of fire
through the penetration, when tested in accordance
with ASTM E 814.
1504.3 T Rating. The time period that the
penetration firestop system, including the
penetrating item, limits the maximum temperature
rise of 325°F above its initial temperature through the
penetration on the nonfire side, when tested in
accordance with ASTM E 814.
I 1505.0 Combustible Piping Installations.
1505.1 Combustible piping installations shall be
protected in accordance with the appropriate fire
resistance rating requirements in the Building Code
that list the acceptable area, height, and type of cons-
truction for use in specific occupancies to assure
compliance and integrity of the fire resistance rating
prescribed.
1505.2 When penetrating a fire-resistance-rated
wall, partition, floor, floor-ceiling assembly, roof-
ceiling assembly, or shaft enclosure, the fire
resistance rating of the assembly shall be restored to
its original rating.
1505.3 Penetrations shall be protected by an
approved penetration firestop system installed as
tested in accordance with ASTM E 119 or ASTM E
814, with a minimum positive pressure differential of
0.01 inch of water. Systems shall have an F rating of
at least 1 hour but not less than the required fire
resistance rating of the assembly being penetrated.
Systems protecting floor penetrations shall have a T
rating of at least 1 hour but not less than the required
fire resistance rating of the floor being penetrated.
Floor penetrations contained within the cavity of a
wall at the location of the floor penetration do not
require a T rating. No T rating shall be required for
floor penetrations by piping that is not in direct
contact with combustible material.
1505.4 When piping penetrates a rated assembly,
combustible piping shall not connect to non-
combustible piping unless it can be demonstrated
that the transition complies with tlie requirements of
Section 1505.3.
1505.5 Insulation and Coverings. Insulation and
coverings on or in the penetrating item shall not be
permitted unless the specific insulating or covering
material has been tested as part of the penetrating
firestop system.
1 505.6 Sleeves. Where sleeves are used, the sleeves
should be securely fastened to the fire-resistance-
rated assembly. The (inside) annular space between
the sleeve and the penetrating item and the (outside)
annular space between the sleeve and the fire-
resistance-rated assembly shall be firestopped in
accordance with the requirements for a sleeve
penetrating item.
1506.0 Non-combustible Piping Installations.
1506.1 Noncombustible piping installations shall be
protected in accordance with the appropriate fire
resistance rating requirements in the Building Code
that list the acceptable area, height, and type of
construction for use in specific occupancies to ensure
compliance and integrity of the fire-resistance rating
prescribed.
1 506.2 When penetrating a fire-resistance-rated wall,
partition, floor, floor-ceiling assembly, roof-ceiling
assembly, or shaft enclosure, the fire-resistance rating
of the assembly shall be restored to its original rating.
Exceptions:
(1) Concrete, mortar, or grout may be used to
fill the annular spaces around cast-iron.
261
1506.2-1507.4
UNIFORM PLUMBING CODE
copper, or steel piping that penetrates
concrete or masonry fire-resistant-rated
assemblies. The nominal diameter of the
penetrating item should not exceed 6 inches
(15.2 cm), and the opening size should not
exceed 144 inches^ (929 cm').
The thickness of concrete, mortar, or
grout should be the full thickness of the
assembly or the thickness necessary to
provide a fire-resistance rating not less than
the required fire-resistance rating of the
assembly penetrated , or
(2) The material used to fill the annular space
shall prevent the passage of flame and hot
gases sufficient to ignite cotton waste for the
time period equivalent to the fire-resistance
ratiug of the assembly, when tested to stan-
dard(s) referenced in Section 1506.3.
1506.3 Penetrations shall be protected by an
approved penetration firestop system installed as
tested in accordance with ASTM E 119 or ASTM E
814, with a minimum positive pressure differential of
0.01 inch of water. Systems shall have an F rating of
at least 1 hour but not less than the required fire-
resistance rating of the assembly being penetrated.
Systems protecting floor penetrations shall have a T
rating of at least 1 hour but not less than the required
fire-resistance rating of the floor being penetrated.
Floor penetrations contained within the cavity of a
wall at the location of the floor penetration do not
require a T rating. No T rating shall be required for
floor penetrations by piping that is not in direct
contact with combustible material.
1506.4 When piping penetrates a rated assembly,
combustible piping shall not connect to non-
combustible piping unless it can be demonstrated
that the transition complies with the requirements of
Section 1506.3.
1 506.5 Unshielded couplings shall not be used to
connect noncombustible piping unless it can be
demonstrated that the fire-resistive integrity of the
penetration is maintained.
1 506.6 Sleeves. Where sleeves are used, the sleeves
should be securely fastened to the fire-resistance-
rated assembly. The (inside) annular space between
the sleeve and the penetrating item and the (outside)
annular space between the sleeve and the fire-
resistance-rated assembly shall be firestopped in
accordance with the requirements for a sleeve-
penetrating item.
1506.7 insulation and Coverings. Insulation and
coverings on or in the penetrating item shall not be
permitted unless the specific insulating or covering
material has been tested as part of the penetrating
firestop system.
1507.0 Required inspection.
1507.1 General. Prior to being concealed, piping
penetrations shall be inspected by the Authority
Having Jurisdiction to verify compliance with the
fire-resistance rating prescribed in the Building Code.
1507.2 The Authority Having Jurisdiction shall
conduct a thorough examination of sufficient
representative installations, including destructive
inspection, to provide verification of satisfactory
compliance with this chapter, the appropriate
manufacturers' installation standards applied by the
installer, construction documents, specifications, and
applicable manufacturers' product information.
1507.3 The Authority Having Jurisdiction shall
determine the type, size, and quantity of pene-
trations to be inspected.
1507.4 The Authority Having Jurisdiction shall
compare the field installations with the documen-
tation supplied by the installer to determine the
following:
(1) The required F ratings (1, 2, 3, or 4 hour) and
T ratings (0, 1, 2, 3, or 4 hour) of the firestop
penetration firestop systems are suitable for
the assembly being penetrated.
(2) The penetrating firestop systems are
appropriate for the penetrating items, as
documented through testing of the systems
conducted by an independent testing agency.
(3) The penetrating firestop system is installed
as tested.
262
Chapter 16
GRAY WATER SYSTEMS
Parti
1601.0 Gray Water Systems - General.
(A) The provisions of this chapter shall apply to
the construction, alteration, and repair of
gray water systems for underground landscape
irrigation. Installations shall be allowed only in
single- family dwellings. The system shall have
no connection to any potable water system and
shall not result in any surfacing of the gray
water. Except as otherwise provided for in this
chapter, the provisions of this code shall be
applicable to gray water installation.
(B) The type of system shall be determined on the
basis of location, soil type, and groundwater
level, and shall be designed to accept all
gray water connected to the system from the
residential building. The system, except as
otherwise approved, shall consist of a holding
tank or tanks that discharge into subsurface
irrigation/disposal fields.
(C) No gray water system or part thereof shall be
located on any lot other than the lot that is the site
of the building or structure that discharges the
gray water, nor shall any gray water system or
part thereof be located at any point having less
than the minimum distances indicated in Table 16-1.
(D) No permit for any gray water system shall be
issued until a plot plan with appropriate data
satisfactory to the Authority Having Jurisdiction
has been submitted and approved. When there
is insufficient lot area or inappropriate soil
conditions for adequate absorption of the
gray water, as determined by the Authority
Having Jurisdiction, no gray water system shall
be permitted.
(E) No permit shall be issued for a gray water system
on any property in a geologically sensitive area
as determined by the Authority Having Jurisdiction.
(F) Private sewage disposal systems existing or to be
constructed on the premises shall comply with
Appendix K of this code. In addition, appropriate
clearances from the gray water systems shall be
maintained as provided in Table 16-1. The
capacity of the private sewage disposal system,
including required future areas, shall not be
decreased or otherwise affected by the existence
or proposed installation of a gray water system
servicing the premises.
1602.0 Definition.
Gray water is untreated household waste water that
has not come into contact with toilet waste. Gray
water includes used water from bathtubs, showers,
and bathrooni wash basins, and water from clothes-
washers and laundry tubs. It shall not include
wastewater from kitchen sinks or dishwashers.
1603.0 Permit.
It shall be unlawful for any person to construct,
install, or alter, or cause to be constructed, installed,
or altered any gray water system in a building or on
a premises without first obtaining a permit to do
such work from the Authority Having Jurisdiction.
1604.0 Drawings and Specifications.
The Authority Having Jurisdiction may require any
or all of the following information to be included
with or in the plot plan before a permit is issued for a
gray w^ater system, or at any time during the
construction thereof:
(A) Plot plan drawn to scale and completely
dimensioned, showing lot lines and structures,
direction and approximate slope of surface,
location of all present or proposed retaining
walls, drainage channels, water supply lines,
wells, paved areas and structures on the plot,
number of bedrooms and plumbing fixtures in
each structure, location of private sewage disposal
system and 100 percent expansion area or
building sewer connecting to the public sewer,
and location of the proposed gray water system.
(B) Details of construction necessary to ensure
compliance with the requirements of this
chapter, together with a full description of the
complete installation, including installation
methods, construction, and materials as required
by the Authority Having Jurisdiction.
(C) A log of soil formations and groundwater level
as deterniined by test holes dug in proximity
to any proposed irrigation area, together with a
statement of water absorption characteristics of
the soil at the proposed site as determined by
approved percolation tests.
Exception: The Authority Having Jurisdiction
may allow the use of Table 16-2 in lieu of
percolation tests.
1605.0 Inspection and Testing.
(A) Inspection.
(1) All applicable provisions of this chapter
and of Section 103.5 of this code shall be
complied with.
263
1605.0-1608.0
UNIFORM PLUMBING CODE
(2) System coniponents shall be properly
identified as to manufacturer.
(3) Holding tanks shall be installed on dry,
level, well-compacted soil if underground or
on a level three (3) inch (76 mm) concrete
slab if aboveground.
(4) Holding tanks shall be anchored against
overturning.
(5) If a design is predicated on soil tests, the
irrigation/disposal field shall be installed at
the same location and depth as the tested
area.
(6) Installation shall conform with the
equipment and installation methods
identified in the approved plans.
(B) Testing.
(1) Holding tanks shall be filled with water to the
overflow line prior to and during inspection.
All seams and joints shall be left exposed,
and the tank shall remadn watertight.
(2) A flow test shall be performed through the
system to the point of gray water irrigation/
disposal. All lines and components shall be
watertight.
1606.0 Procedure for Estimating Gray Water
Discharge.
(A) The number of occupants of each dwelling unit
shall be calculated as follows:
First bedroom 2
Each additional bedroom 1
(B) The estimated gray water flows for each
occupant shall be calculated as follows:
Showers, bathtubs,
and washbasins
Laundry
25 GPD (95LPD)
15 GPD (57 LPD)
(C) The total number of occupants shall be
multiplied by the applicable estimated gray water
discharge as provided above, and the type of
fixtures connected to the gray water system.
Example 1:
Single-family dwelling; three bedrooms with
showers, bathtubs, washbasins; and laundry facilities
all connected to the gray water system:
Total number of occupants = 2 + 1 + 1 = 4
Estimated gray water flow = 4 x (25 + 15) = 160 GPD
(metric) = 4 x (95 + 57) = 608 LPD
Example 2:
Single-family dwelling; four bedrooms witli only the
clothes washer connected to the gray water system:
Total number of occupants = 2 + 1 + 1 + 1 = 5
Estimated gray water flow = 5 x 15 = 75 GPD
(metric) = 5 x 57 = 285 LPD
1607.0 Required Area of Subsurface Irrigation/
Disposal Fields (See Figure 16-5.)
Each valved zone shall have a minimum effective
irrigation area in square feet as determined by Table
16-2 for the type of soil found in the excavation, based
upon a calculation of estimated gray water discharge
pursuant to Section 1606.0 of this chapter, or the size
of the holding tank, whichever is larger. The area of
the irrigation /disposal field shall be equal to the
aggregate length of the perforated pipe sections
within the valved zone multiplied the width of the
proposed irrigation/disposal field. Each proposed
gray water system shall include at least three (3)
valved zones, and each zone shall be in compliance
with the provisions of the section. No excavation for
an irrigation /disposal field shall extend within five (5)
vertical feet of the highest known seasonal ground-
water, nor to a depth where gray water may
contaminate the groundwater or ocean water. The
applicant shall supply evidence of groundwater deptlT
to the satisfaction of the Authority Having Jurisdiction.
1608.0 Determination of IVIaximum Absorption
Capacity.
(A) Wherever practicable, irrigation/ disposal field
size shall be computed from Table 16-2.
(B) In order to determine the absorption quantities of
questionable soils other than those listed in Table
16-2, the proposed site may be subjected to
percolation tests acceptable to the Authority
Having Jurisdiction.
(C) When a percolation test is required, no
gray water system shall be permitted if the test
shows the absorption capacity of the soil is less
than eighty-three hundredths (0.83) gallons per
square foot (33.8 L/m^) or more than five and
twelve hundredths (5.12) gallons per square foot
(208.5 L/m^) of leaching area per twenty-four
(24) hours.
264
GRAY WATER SYSTEMS
1609.0-1611.0
1609.0 Holding Tank Construction. (See Figures
16-1,16-2, 16-3 and1 6-4.)
(A) Plans for all holding tanks shall be submitted to
the Authority Having Jurisdiction for approval.
Such plans shall show all dimensions, structural
calculations, bracings, and such other pertinent
data as may be required. A minimum capacity of
fifty (50) gallons (189 L) is required.
(B) Holding tanks shall be constructed of solid,
durable materials not subject to excessive
corrosion or decay and shall be watertight.
(C) Each holding tank shall be vented as required by
Chapter 9 of this code and shall have a locking,
gasketed access opening or approved equivalent
to allow for inspection and cleaning.
(D) Each holding tank shall have its rated capacity
perm^anently marked on the unit. In addition, a
sign stating GRAY WATER IRRIGATION SYSTEM,
DANGER — UNSAFE WATER shall be
permanently marked on the holding tank.
(E) Each holding tank installed aboveground shall
have an emergency drain separate from that
connecting the tank with the irrigation /disposal
fields and an overflow drain. The emergency
and overflow drains shall have permanent
connections to the building drain or building
sewer, upstream of septic tanks, if any. The
overflow drain shall not be equipped with a
shutoff valve.
(F) The overflow and emergency drainpipes shall
not be less in size than the inlet pipe. The vent
size shall be determined based on the total
gray water fixture imits as outlined in Table 7-5
of this code. Unions or equally effective fittings
shall be provided for all piping connected to the
holding tank.
(G) Each holding tank shall be structurally designed
to withstand all anticipated earth or other loads.
All holding tank covers shall be capable of
supporting an earth load of not less than three
hundred (300) pounds per square foot (1464.6 kg/m^)
when the tank is designed for underground
installation.
(H) If a holding tank is installed underground, the
system must be designed so that the tank
overflow will gravity drain to the existing sewer
line or septic tank. The tank shall be protected
against sewer line backflow by a backwater valve.
(I) IVIaterials.
(1) Holding tanks shall be steel, protected from
corrosion, both externally and internally by
an approved coating or other acceptable
means; shall meet nationally recog-
nized standards for the intended use; and
shall be approved by the Authority Having
Jurisdiction.
(2) Holding tanks constructed of alternate
material may be approved by the Authority
Having Jurisdiction, provided they comply
with approved applicable standards.
1610.0 Valves and Piping. (See Figures 16-1, 16-2,
16-3, and 16-4.)
Gray water piping discharging into the holding tank or
having a direct connection to the sanitary drain or sewer
piping shall be downstream of an approved waterseal-
type trap(s). If no such trap(s) exists, an approved
vented running trap shall be installed upstream of the
connection to protect the building from any possible
waste or sewer gases. All gray water piping shall be
marked or have a continuous tape marked with the
words DANGER — UNSAFE WATER. All valves,
including the three-way valve, shall be readily
accessible and approved by the Authority Having
Jurisdiction. A backwater valve installed pursuant to
this code shall be provided on all holding tank drain
connections to the sanitary drain or sewer piping.
1611.0 Irrigation/Disposal Field Construction. (See
Figure 16-5.)
(A) Perforated sections shall be a minimum three (3)
inch (80 mm) diameter and shall be constructed
of perforated high-density polyethylene pipe,
perforated ABS pipe, perforated PVC pipe, or
other approved materials, provided that sufficient
openings are available for distribution of the
gray water into the trench area. Material,
construction, and perforation of the pipe shall be
in compliance with the appropriate absorption
fields drainage piping standards and shall be
approved by the Authority Having Jurisdiction.
(B) Filter material, clean stone, gravel, slag, or
similar filter material acceptable to the Authority
Having Jurisdiction, varying in size from three-
quarter (3/4) inch (20 mm) to two and one-half
(2-1/2) inch (65 mm) shall be placed in the
trench to the depth and grade required by this
section. The perforated section shall be laid on
the filter material in an approved manner. The
perforated section shall then be covered with
filter material to the minimum depth required
by this section. The filter material shall then be
covered with untreated building paper, straw, or
similar porous material to prevent closure of
voids with earth backfill. No earth backfill shall
be placed over the filter material cover until after
inspection and acceptance.
(C) Irrigation/ disposal fields shall be constructed as
follows:
(See chart on following page)
265
1611.0-Table16-1
UNIFORM PLUMBING CODE
(D) When necessary on sloping ground to prevent
excessive line slopes, irrigation /disposal lines
shall be stepped. The lines between each
horizontal leaching section shall be made with
approved watertight joints and installed on
natural or unfilled ground.
1612.0 Special Provisions
(A) Other collection and distribution systems may
be approved by the local Authority Having
Jurisdiction, as allowed by Section 301.0 of this code.
(B) Nothing contained in this chapter shall be
construed to prevent the Authority Having
Jurisdiction from requiring compliance with higher
requirements than those contained herein, where
such higher requirements are essential to maintain a
safe and sanitary condition.
i\/linimum
Maximum
Number of drain lines per valved zone 1
Length of each perforated line —
Bottom width of trench 12 in. (305 mm)
Spacing of lines, center to center 4 ft. (1219 mm)
Depth of earth cover of lines 10 in. (254 mm)
Depth of filter material cover of lines 2 in. (51 mm)
Depth of filter material beneath lines 3 in. (76 mm)
Grade of perforated lines level 3 in. / 100 ft.
100 ft. (30,840 mm)
18 in. (457 mm)
2 mm/m
TABLE 16-1
Location of Gray Water System
Irrigation/
Minimum Horizontal Distance
Holding Tank
Disposal Field
in Clear Required From:
Feet
(mm)
Feet
(mm)
Building structures^
5'
(1,524 mm)
2'
(610 mm)
Property line adjoining private property
5
(1,524 mm)
5
(1,524 mm)
Water supply wells*
50
(15,240 mm)
100
(30,480 mm)
Streams and lakes*
50
(15,240 mm)
50=
(15,240 mm)
Sewage pits or cesspools
5
(1,524 mm)
5
(1,524 mm)
Disposal field and 100% expansion area
5
(1,524 mm)
45
(1,219 mm)
Septic tank
(0)
5
(1,524 mm)
On-site domestic water service line
5
(1,524 mm)
5
(1,524 mm)
Pressurized public water main
10
(3,048 mm)
10^
(3,048 mm)
Note: When irrigation /disposal fields are installed in sloping ground, the minimum horizontal distance between any
part of the distribution system and the ground surface shall be fifteen (15) feet (4,572 mm).
' Including porches and steps, whether covered or uncovered, breezeways, roofed porte cocheres, roofed patios,
carports, covered walks, covered driveways, and similar structures or appurtenances.
^ The distance may be reduced to zero feet for aboveground tanks when first approved by the Authority Having
Jurisdiction.
^ Assumes a 45-degree (0.79 rad) angle from foundation.
* Where special hazards are involved, the distance required shall be increased as may be directed by the
Authority Having Jurisdiction.
= These minimum clear horizontal distances shall also apply between the irrigation/disposal field and the ocean
mean higher hightide line.
* Plus two (2) feet (610 mm) for each additional foot of depth in excess of one (1) foot (305 mm) below the bottom
of the drain line.
^ For parallel construction /for crossings, approval by the Authority Having Jurisdiction shall be required.
266
GRAY WATER SYSTEMS
Table 16-2
TABLE 16-2
Design Criteria of Six Typical Soils
Type of Soil
Minimum square feet
Maximum absorption
of irrigation/leaching
capacity In gallons
area per 100 gallons
per square foot of
of estimated gray water
irrigation/leaching area
discharge per day
for a 24-hour period
20
5.0
25
4.0
40
2.5
60
1.7
90
1.1
120
0.8
Coarse sand or gravel
Fine sand
Sandy loam
Sandy clay
Clay with considerable
sand or gravel
Clay with small amounts of
sand or gravel
TABLE 16-2
(Metric) Design Criteria of Six Typical Soils
Type of Soil
Minimum square meters
of irrigation/leaching
area per liter of
estimated gray water
discharge per day
Maximum absorption
capacity in liters
per square meter of
irrigation/leaching area
for a 24-hour period
Coarse sand or gravel
Fine sand
Sandy loam
Sandy clay
Clay with considerable
sand or gravel
Clay with small amounts of
sand or gravel
0.005
0.006
0.010
0.015
0.022
0.030
203.7
162.9
101.8
69.2
44.8
32.6
267
Figure 16-1
UNIFORM PLUMBING CODE
Vent shall be within
trap arm distance of
running trap.
Screened Vents
3/32"{2.4mm)mesh
Gray water Source
1/4'
(20.9 mnn/m)
1 /47 foot (20.9 mm/m)
To building drain or sewer,
upstream of septic tank, if any
To irrigation system
(level or sloped)
Minimum of 3 irrigation lines
required for each system.
Cleanout 3 " (76 mm) Concrete Pad
if tank above ground
FIGURE 16-1 Gray Water System Tank - Gravity.
268
GRAY WATER SYSTEMS
Figure 16-2
Vent shall be within
trap arm distance of
running trap.
Screened Vents
3/32"(2.4mm)mesh
1/47 foot
(20.9 mm/m)
Union or equal (typ.)
I
Backwater Valve
with unions
Locking Cover
(access
<r-
1/47foot (20.9 mm/m)
To building drain or sewer,
upstream of septic tank, if any
To irrigation system
(level or sloped)
Minimum of 3 irrigation lines
required for each system.
Sewage Ejector
with probes
Cleanout 3 " (76 mm) Concrete Pad
if tank above ground
FIGURE 16-2 Gray Water System Tank - Pumped.
269
Figure 16-3
UNIFORM PLUMBING CODE
Vent shall be within
trap arm distance of
running trap.
Screened Vents
3/32"{2.4mm)mesh
Graywater Source
VentThruRoof orlO'
(3048 mm) above grade
{support required)
3-Way Valve
6''(152 mm) above top
of highest tank
Capped Inlet
1/47 toot
(20.9 mm/m)
Vented Running Trap,
if required
San Tees
Grade
Overflow jp*^
(no valve)
Wye & 1/8 Bend
Backwater Valve yC^
Inlet
Graywater
Irrigation System
Danger
, Unsafe Water J
Overflow
(no valve)
Graywater
Irrigation System
Danger
.Unsafe Water J
Locking Cover
(access)
Approved
Watertight Tank
Fullway Valve
1/47foot (20.9 mm/m)
To building drain or sewer,
upstream of septic tank, if any
Emergency Drain
(normally closed)
Cleanout
3" (75 mm) Concrete Pad
Cleanout
Grade
To irrigation system .
(level or sloped)
Minimum of 3 irrigation lines
required for each system.
FIGURE 16-3 Gray Water System Multiple-Tank Installation.
270
GRAY WATER SYSTEMS
Figure 16-4
Vent shall be within
trap arm distance of
running trap.
Screened Vents
3/32"(2.4nrim)mesh
Union or equal (typ.)
Backwater Valve
with unions
Gray water
Source
1 /4'7 foot (20.9 nnm/m)
Shutoff Valve
Grade
Backwater Valve
1/47 foot (20.9 mm/m)Cleanout
To building drain or sewer,
upstream of septic tank, if any
Capped Emergency Drain
Gray water Irrigation System
Danger
Unsafe Water
To irrigation system
(level or sloped)
Minimum of 3 irri-
gation lines required
for each system.
Locking Cover (access)
Watertight Tank
approved for
underground use
Sewage Ejector
pump with probes
FIGURE 16-4 Gray Water System Underground Tank - Pumped.
271
Figure 16-5
UNIFORM PLUMBING CODE
To public
sewer
2» (610 mm) min.
ValvedZone
100' {30480 mm)
max.
3" (80 mm)
diameter (typ.)
Property Line
Note: Each valved zone shall have a minimum effective
absorption/irrigation area in square feet predicated on the
estimated graywater discharge in gallons per day and on
the type of soil found in the area. The area of the field
shall be equal to the aggregate length of perforated pipe
sections within the valved zone times the width of the
proposed field.
Soil
Gravel
Grade
Untreated
10" (254 mi
18" (457 mm) 1
min. 1
2" (51 mm )
building paper
3" (80 mm) perforated pipe section
FIGURE 16-5 Gray Water System Typical Irrigation Layout.
272
GRAY WATER SYSTEMS
1613.0-1617.0
Part II
1613.0 Reclaimed Water Systems - General.
(A) The provisions of this chapter shall apply to the
installation, construction, alteration, and repair of
reclaimed water systems intended to supply water
closets, urinals, and trap primers for floor drains and
floor sinks. Use is limited to these fixtures that are
located in nonresidential buildings. Fixtures within
residential buildings are excluded from the list of
approved uses. The reclaimed water system shall
have no connection to any potable water system,
with or without mechanical backflow prevention
devices. If reclaimed water is utilized on the
premises, all potable water supplies shall be
provided with appropriate backflow protection, as
required by the Authority Having Jurisdiction.
Except as otherwise provided for in this appendix,
the provisions of this code shall be applicable to
reclaimed water system installations.
(B) No permit for any reclaimed water system shall
be issued until complete plumbing plans, with
appropriate data satisfactory to the Authority
Having Jurisdiction, have been submitted and
approved. No changes or connections shall be made
to either the reclaimed water system or the potable
water system within any site containing a reclaimed
water system without approval by the Authority
Having Jurisdiction.
(C) Before the building may be occupied, the
installer shall perform the initial cross-connection test
in the presence of the Authority Having Jurisdiction
and other authorities having jurisdiction. The test
shall be ruled successful by the Authority Having
Jurisdiction before final approval is granted.
1614.0 Definitions.
Reclaimed water is water that, as a result of tertiary
treatment of domestic wastewater by a public
agency, is suitable for a direct beneficial use or a
controlled use that would not otherwise occur. The
level of treatment and quality of the reclaimed water
shall be approved by the public health Authority
Having Jurisdiction.
For the purpose of this chapter, tertiary
treatment shall result in water that is adequately
oxidized, clarified, coagulated, filtered, and
disinfected so that at some location in the treatment
process, the seven (7) day median number of total
coliform bacteria in daily samples does not exceed
two and two-tenths (2.2) per one hundred (100)
milliliters, and the number of total coliform bacteria
does not exceed twenty-three (23) per one hundred
(100) milliliters in any sample. The water shall be
filtered so that the daily average turbidity does not
exceed two (2) turbidity units upstream from the
disinfection process.
Specifically excluded from this definition is gray
water, which is defined in Part I of this chapter.
1615.0 Permit.
It shall be unlawful for any person to construct,
install, alter, or cause to be constructed, installed, or
altered any reclaimed water system within a building
or on a premises without first obtaining a permit to
do such work from the Authority Having Jurisdiction.
1616.0 Drawings and Specifications.
The Authority Having Jurisdiction may require any
or all of the following information to be included
with or in the plot plan before a permit is issued for a
reclaimed water systen\.
(A) A plot plan drawn to scale and completely
dimensioned, showing lot lines and structures,
location of all present and proposed potable water
supplies and meters, water wells, streams, auxiliary
water supply and systems, reclaimed water supply
and meters, drain lines, and locations of private
sewage disposal systems and one hundred (100)
percent expansion areas or building sewer connected
to the public sewer.
(B) Details of construction including riser diagrams
or isometrics and a full description of the complete
installation, including installation methods,
construction, and materials as required by the
Authority Having Jurisdiction. To the extent
permitted by structural conditions, all reclaimed
water risers within the toilet room, including
appurtenances such as air/vacuum relief valves,
pressure reducing valves, etc., shall be installed in
the opposite end of the room containing the served
fixtures from tlie potable water risers or opposite walls,
as applicable. To the extent permitted by structural
conditions, reclaimed water headers and branches
off risers shall not be run in the same wall or ceiling
cavity of the toilet room where potable water piping
is run.
(C) Detailed initial and annual testing requirements
as outlined elsewhere in this chapter.
1617.0 Pipe Material/Pipe Identification.
Reclaimed water piping and fittings shall be as
required in this code for potable water piping and
fittings. All reclaimed water pipe and fittings shall be
continuously wrapped with purple-colored Mylar
tape. The wrapping tape shall have a minimum
273
1617.0-1619.0
UNIFORM PLUMBING CODE
nominal thickness of five ten-thousandths (0.0005)
inch (0.127 mm) and a minimum width of two (2)
inches (51 mm). Tape shall be fabricated of
poly(vinyl chloride) with a synthetic rubber adhesive
and a clear polypropylene protective coating or
approved equal. The tape shall be purple (Pantone
color #512) and shall be imprinted in nominal one-
half (1/2) inch (12.7 mm) high, black uppercase
letters, with the words "CAUTION: RECLAIMED
WATER, DO NOT DRINK." The lettering shall be
imprinted in two (2) parallel lines, such that after
wrapping the pipe with a one-half (1/2) inch width
overlap, one (1) full line of text shall be visible.
Wrapping tape is not required for buried PVC pipe
manufactured with purple color integral to the plastic
and marked on opposite sides to read "CAUTION:
RECLAIMED WATER, DO NOT DRINK" in
intervals not to exceed three (3) feet (914 mm).
All valves, except fixture supply control valves
shall be equipped with a locking feature. All
mechanical equipment that is appurtenant to the
reclaimed water system shall be painted purple to
match the Mylar wrapping tape.
1618.0 Installation.
(A) Hose bibbs shall not be allowed on reclaimed
water piping systems.
(B) The reclaimed water system and the potable
water system within the building shall be provided
with the required appurtenances (valves, air/vacuum
relief valves, etc.) to allow for deactivation or
drainage as may be required by this chapter.
(C) Reclaimed water pipes shall not be run or laid in
the same trench as potable water pipes. A ten (10)
foot (3,048 mm) horizontal separation shall be
maintained between pressurized, buried reclaimed
and potable water piping. Buried potable water
pipes crossing pressurized reclaimed water pipes
shall be laid a minimum of twelve (12) inches (305
m^m) above the reclaimed water pipes. Reclaimed
water pipes laid in the same trench or crossing
building sewer or drainage piping shall be installed
in compliance with Sections 609.0 and 720.0 of this
code. Reclaimed water pipes shall be protected
similar to potable water pipes.
1619.0 Signs.
(A) Room Entrance Signs. All installations using
reclaimed water for water closets and /or urinals shall
be identified with signs. Each sign shall contain one-
half (1/2) inch (12.7 mm) letters of a highly visible
color on a contrasting background. The location of
the sign(s) shall be such that the sign(s) shall be
visible to all users. The number and location of the
signs shall be approved by the Authority Having
Jurisdiction and shall contain the following text:
TO CONSERVE WATER, THIS BUILDING USES
RECLAIMED
WATER TO FLUSH TOILETS AND URINALS.
(B) Equipment Room Signs. Each equipment room
containing reclaimed water equipment shall have a
sign posted with the following wording in one (1)
inch (25.4 mm) letters on a purple background:
CAUTION
RECLAIMED WATER, DO NOT DRINK.
DO NOT CONNECT TO DRINKING WATER
SYSTEM.
NOTICE
CONTACT BUILDING MANAGEMENT BEFORE
PERFORMING ANY WORK ON THIS WATER
SYSTEM.
This sign shall be posted in a location that is
visible to anyone working on or near reclaimed
water equipment.
(C) Where tank-type water closets are flushed with
reclaimed water, the tank shall be labeled:
RECLAIMED WATER - DO NOT DRINK
(D) Valve Access Door Signs. Each reclaimed
water valve within a wall shall have its access door
into the wall equipped with a warning sign
approximately six (6) inches by six (6) inches (152
mm x 152 mm) with wording in one half (1/2) inch
(12.7 mm) letters on a purple background. The size,
shape, and format of the sign shall be substantially
the same as that specified in subsection (B) above.
The signs shall be attached inside the access door
frame and shall hang in the center of the access door
frame. This sign requirement shall be applicable to
any and all access doors, hatches, etc., leading to
reclaimed water piping and appurtenances.
(E) Valve Seals. Each valve or appurtenance shall
be sealed in a manner approved by the Authority
Having Jurisdiction after the reclaimed system has
been approved and placed into operation. These
seals shall either be a crimped lead wire seal or a
plastic breakaway seal which, if broken after system
274
GRAY WATER SYSTEMS
1619.0-1620.0
approval, shall be deemed conclusive evidence that
the reclaimed water system has been accessed. The
seals shall be purple with the words "RECLAIMED
WATER" and shall be supplied by the reclaimed
water purveyor or by other arrangements acceptable
to the Authority Having Jurisdiction.
1620.0 Inspection and Testing.
(A) Reclaimed water piping shall be tested as
outlined in this code for testing of potable water
piping.
(B) An initial and subsequent annual cross-
cormection inspection and test shall be performed on
both the potable and reclaimed water systems as
follows:
(1) Visual Dual System Inspection. Prior to
commencing the cross-connection testing, a
dual system inspection shall be conducted
by the Authority Having Jurisdiction and
other authorities having jurisdiction.
(i) Meter locations of the reclaimed water
and potable water lines shall be checked
to verify that no modifications were
made, and that no cross-coimections are
visible.
(ii) All pumps and equipment, equipment
room signs, and exposed piping in
the equipment room shall be checked.
(iii) All valves shall be checked to ensure
that valve lock seals are still in place
and intact. All valve control door signs
shall be checked to verify that no signs
have been removed.
(2) Cross-Connection Test. The following
procedure shall be followed by the applicant
in the presence of the Authority Having
Jurisdiction and other authorities having
jurisdiction to determine whether a cross-
connection occurred.
(i) The potable water system shall be
activated and pressurized. The reclaimed
water system shall be shut down and
completely drained.
(ii) The potable water system shall remain
pressurized for a minimum period of
time specified by the Authority Having
Jurisdiction while the reclaimed water
system is empty. The minimum period
the reclaimed water system is to remain
depressurized shall be determined on a
case-by-case basis, taking into account
the size and complexity of the potable
and reclaimed water distribution
systems, but in no case shall that period
be less than one (1) hour.
(iii) All fixtures, potable and reclaimed,
shall be tested and inspected for flow.
Flow from any reclaimed water system
outlet shall indicate a cross-connection.
No flow from a potable water outlet
would indicate that it may be con-
nected to the reclaimed water system.
(iv) The drain on the reclaimed water
system shall be checked for flow during
the test and at the end of the period.
(v) The potable water system shall then be
completely drained,
(vi) The reclaimed water system shall then
be activated and pressurized.
(vii)The reclaimed water system shall
remain pressurized for a minimum
period of time specified by the
Authority Having Jurisdiction while the
potable water system is empty. The
minimum period the potable water
system is to remain depressurized shall
be determined on a case-by-case basis,
but in no case shall that period be less
than one (1) hour.
(viii) All fixtures, potable and reclaimed, shall
be tested and inspected for flow. Flow
from any potable water system outlet
shall indicate a cross-connection. No
flow from a reclaimed water outlet
would indicate that it may be connected
to the potable water system.
(ix) The drain on the potable water system
shall be checked for flow during the test
and at the end of the period.
(x) If there is no flow detected in any of the
fixtures that would have indicated a
cross-connection, the potable water
system shall be repressurized.
(3) In the event that a cross-connection is
discovered, the following procedure, in the
presence of the Authority Having
Jurisdiction, shall be activated immediately:
(i) Reclaimed water piping to the building
shall be shut down at the meter, and the
reclaimed water riser shall be drained.
(ii) Potable water piping to the building
shall be shut down at the meter.
(iii) The cross-connection shall be uncovered
and disconnected.
275
1620.0-1622.0
UNIFORM PLUMBING CODE
(iv) The building shall be retested following
procedures listed in subsections (B)(1)
and (B)(2) above.
(v) The potable water system shall be
chlorinated with fifty (50) ppm chlorine
for twenty-four (24) hours.
(vi) The potable water system shall be
flushed after twenty-four (24) hours,
and a standard bacteriological test shall
be performed. If test results are
acceptable, the potable water system
may be recharged.
(C) An annual inspection of the reclaimed water
system, following the procedures listed in subsection
1620.0 (B)(1), shall be required. Annual cross-
connection testing, following the procedures listed in
subsection 1620.0 (B)(2), shall be required by the
Authority Having Jurisdiction, unless site conditions
do not require it. In no event shall the test occur less
often than once in four (4) years. Alternate testing
requirements may be allowed by the Authority
Having Jurisdiction for institutional buildings.
The health officer or other designated appointee
may substitute for the Authority Having Jurisdiction
in the above-mentioned inspections and tests.
1621.0 Sizing.
Reclaimed water piping shall be sized as outlined in
this code for sizing potable water piping.
1622.0 Approved Uses of Reclaimed Water.
Reclaimed water is allowed in all nonresidential
buildings to supply fixtures as specified in this
chapter, except where prohibited by statute,
regulation, or ordinance.
276
APPENDICES
The appendices are intended to supplement the provisions of the installation requirements of this code. The
definitions in Chapter 2 are also applicable to the appendices.
CONTENTS
Page
Appendix A
Recommended Rules for Sizing the Water Supply System 279
Appendix B
Explanatory Notes on Combination Waste and Vent Systems 295
Appendix C DELETED
Appendix D
Sizing Storm Water Drainage Systems 297
Appendix E
Manufactured/Mobile Home Parks and Recreational Vehicle Parks. 305
Appendix F
Firefighter Breathing Air Replenishment Systems , 317
Appendix H DELETED
Appendix I
Installation Standards .....:..,..... 321
Appendix K
Private Sewage Disposal Systems 421
Appendix L
Alternate Plumbing Systems 433
277
UNIFORM PLUMBING CODE
278
APPENDIX A
RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM
Because of the variable conditions encountered, it is
impractical to lay down definite detailed rules of
procedure for determining the sizes of water supply
pipes in an appendix, which must necessarily be
limited in length. For a more adequate understanding
of the problems involved, refer to Water-Distributing
Systems for Buildings, Report BMS 79 of the National
Bureau of Standards; and Plumbing Manual, Report
BMS 66, also published by the National Bureau of
Standards.
The following is a suggested order of
procedure for sizing the water supply system.
A 1 Preliminary Information.
A 1.1 Obtain the necessary information
regarding the minimum daily service pressure in the
area where the building is to be located.
A 1 .2 If the building supply is to be metered,
obtain information regarding friction loss relative to
the rate of flow for meters in the range of sizes likely
to be used. Friction-loss data can be obtained from
most manufacturers of water meters. Friction losses
for disk-type meters may be obtained from Chart A-1.
A 1.3 Obtain all available local information
regarding the use of different kinds of pipe with
respect both to durability and to decrease in capacity
with length of service in the particular water supply.
A 2 Demand Load.
A 2.1 Estimate the supply demand for the
building main and the principal branches and
risers of the system by totaling the fixture units on
each. Table A-2, and then by reading the
corresponding ordinate from Chart A-2 or A-3,
whichever is applicable.
A 2.2 Estimate continuous supply demands in
gallons per minute (liters per second) for lawn
sprinklers, air conditioners, etc., and add the sum to
the total demand for fixtures. The result is the
estimated supply demand of the building supply.
A 3 Permissible Friction Loss.
A 3.1 Decide what is the desirable minimum
residual pressure that shall be maintained at the
highest fixture in the supply system. If the highest
group of fixtures contains flushometer valves, the
residual pressure for the group shall not be less than
fifteen (15) psi (103 kPa). For flush tank supplies, the
available residual pressure shall not be less than
eight (8) psi (55 kPa).
A 3.2 Determine the elevation of the highest
fixture or group of fixtures above the water (street)
main. Multiply this difference in elevation by forty-
three hundredths (0.43). The result is the loss in static
pressure in psi (pounds per square inch) (kPa).
A 3.3 Subtract the sum of loss in static pressure
and the residual pressure to be maintained at the
highest fixture from the average minimum daily
service pressure. The result will be the pressure
available for friction loss in the supply pipes, if no
water meter is used. If a meter is to be installed, the
friction loss in the meter for the estimated maximum
demand should also be subtracted from the service
pressure to determine the pressure loss available for
friction loss in the supply pipes.
A 3.4 Determine the developed length of pipe
from the water (street) main to the highest fixture. If
close estimates are desired, compute with the aid of
Table A-3 the equivalent length of pipe for all fittings
in the line from the water (street) main to the highest
fixture and add the sum to the developed length. The
pressure available for friction loss in pounds per
square inch (kPa), divided by the developed lengths
of pipe from the water (street) main to the highest
fixture, times one hundred (100), will be the average
permissible friction loss per one hundred (100) foot
(30,480 mm) length of pipe.
A 4 Size of Building Supply.
A 4.1 Knowing the permissible friction loss per
one hundred (100) feet (30,480 mm) of pipe and the
total demand, the diameter of the building supply
pipe may be obtained from Charts A-4, A-5, A-6, or
A-7, whichever is applicable. The diameter of pipe
on or next above the coordinate point corresponding
to the estimated total demand and the permissible
friction loss will be the size needed up to the first
branch from the building supply pipe.
A 4.2 If copper tubing or brass pipe is to be used
for the supply piping and if the character of the
water is such that only slight changes in the
hydraulic characteristics may be expected. Chart A-4
may be used.
A 4.3 Chart A-5 should be used for ferrous pipe
with only the most favorable water supply in regards
corrosion and caking. If the water is hard or
corrosive. Chart A-6 or A-7 will be applicable. For
extremely hard water, it will be advisable to make
279
Appendix A
UNIFORM PLUMBING CODE
additional allowances for the reduction of capacity of
hot- water lines in service.
A 5 Size of Principal Branches and Risers.
A 5.1 The required size of branches and risers
may be obtained in the same manner as the building
supply, by obtaining the demand load on each
branch or riser and using the permissible friction loss
computed in Section A 3.
A 5.2 Fixture branches to the building supply,
if they are sized for the same permissible friction
loss per one hundred (100) feet (30,480 mm) of
pipe as the branches and risers to the highest level
in the building, may lead to inadequate water
supply to the upper floor of a building. This may
be controlled by (1) selecting the sizes of pipe for
the different branches so that the total friction loss
in each lower branch is approximately equal to
the total loss in the riser, including both friction
loss and loss in static pressure; (2) throttling each
such branch by means of a valve until the
preceding balance is obtained; (3) increasing the
size of the building supply and risers above the
minimum required to meet the maximum
permissible friction loss.
A 5.3 The size of branches and mains serving
flushometer tanks shall be consistent with sizing
procedures for flush tank water closets.
pipe from the pressure-reducing valve to the most
distant fixture of two hundred (200) feet (60,960
mm); and fixtures to be installed with flush valves
for water closets and stall urinals as follows:
If the pipe material and water supply are such
that Chart A-5 applies, the required diameter of the
building supply is three and one-half (3-1/2) inches
(88.9 mm) and the required diameter of the branch to
the hot-water heater is one and one-half (1-1/2)
inches (40 mm).
The sizes of the various branches and risers may
be determined in the same maimer as the size of the
building supply or the branch to the hot-water
system, by estimating the demand fqr the riser or
branch from Chart A-2 or A-3 and applying the total
demand estimate from the branch, riser, or section
thereof to the appropriate flowchart.
A 6 General.
A 6.1 Velocities shall not exceed 10 feet/second
(3.0 m/sec.) or the maximum values given in the
appropriate Installation Standard, except as
otherwise approved by the Authority Having
Jurisdiction.
A 6.2 If a pressure-reducing valve is used in the
building supply, the developed length of supply
piping and the permissible friction loss should be
computed from the building side of the valve.
A 6.3 The allowances in Table A-3 for fittings
are based on nonrecessed threaded fittings. For
recessed threaded fittings and streamlined soldered
fittings, one-half (1/2) the allowances given in the
table will be ample.
A 7 Example.
A 7.1 Assume an office building of four (4)
stories and basement; pressure on the building side
of the pressure-reducing valve of fifty-five (55) psi
(379 kPa) (after an allowance for reduced pressure
falloff at peak demand); an elevation of highest
fixture above the pressure-reducing valve of forty-
five (45) feet (13,716 mm); a developed length of
280
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-1
Friction Losses for Disk-Type Water l\/leters
20
16
■10
(!)
£ 6
(A 4
CO
O
— 1
1
/ ,
/
/
/
/
/ ■ ■ /
/
f
J
/
/
7
/
/
/
i^
/
/
/
/
/
/
. -.... X...-
' . ,
7
/
1
/
.'
/
.■......._/
/
__/ _..z
\
/
/
/
/
, / /
/
/
/
j
/
/
/
/.
/ /
/
/ ■
/
/
/
/ .
/
/
/
/
/
/
/
/
/I
■/ /
/
'
/
/
/
/
f
/
/
/
/
/
/
_/_ _.
/
,'\
1
1
1
/
/
/
/
/
■/
/.
(
/
/
/
/
/
/
/
/
/
/
/
/
/
u
1
■'
/
_
/
• /
/
/
/
/
-/
/
...
—
4 5 678910 20 30 40 50 60 80 100 200 300 400 600 8001000
Flow - Gallons per Minute
Chart A-1 (Metric)
Friction Losses for Disk-Type Water Meters
110.2
(0 68.9
Ol
62.0
.X
55.1
1
48.2
(0
41.3
(0
O
34.5
-1
?7.6
0)
3
(0
20.7
(0
o
13.8
6.9
r—
' \
'', ,
/
'
[—
r-
5"
/ .
■ /
/
T
^
T
4''
i/-
4
f/.
1
^/
i/ ■
f
/
^■>
1
/
/
::>:.- ■■■:
/
/
1
-
—
-
.. ■ ,._ /
/:._ ,_._
/
/
. y
!
/
/ -
/
f
. /
■ /
1
.„..,X.-^ /-
/
/
. ..y
/
/
/ /
/
/
■/
/
7 7
■ /
1
/
/
''
' "~7' '
/
/
/
1
/
/
■
■
/
1
/
/
/
/
/ ' ''^
/ /
/
1
^
/
r /
/
1
/
/
/
/
/
/ -
/
. ■/
/
/■
/
/
L
/
/
-
■ / ■
/
1 ■
/ ■
/
/
/
/
/
/
/
/
/ .
/
/
■ /
/
. / .
■/
/
/
■
in
CM 00 Tf or^co
CO
0)
m
CM 00
o
CO
(O
0)
CM
CO
Tt
o
CM
CO CO ■* in ifxo
CM
CO CO
in
CO
CM
CO
m
h-.
o
CO
CM
CO
in
CO
Flow - Liters per Second
281
Appendix A
UNIFORM PLUMBING CODE
Inch
mm
1/2
15
3/4
20
1
25
TABLE A-2
Water Supply Fixture Units (WSFU) and Minimum Fixture Branch Pipe Sizes^
Private
Public
Assembly^
Minimum
Fixture Branch
Appliances, Appurtenance, or Fixtures^ Pipe Size^'^
Bathtub or Combination Bath/Shower (fill) 1/2"
3/4" Bathtub Fill Valve 3/4"
Bidet 1/2"
Clothes Washer 1/2"
Dental Unit, cuspidor 1/2"
Dishwasher, domestic 1/2"
Drinking Fountain or Watercooler 1/2"
Hose Bibb 1/2"
Hose Bibb, each additional 1/2"
Lavatory 1/2"
Lawn Sprinkler, each head^
Mobile Home, each (minimum)
Sinks
Bar 1/2"
Clinic Faucet 1/2"
Clinic Flushometer Valve
with or without faucet 1"
Kitchen, domestic 1/2"
Laundry 1/2"
Service or Mop Basin 1/2"
Washup, each set of faucets 1/2"
Shower 1/2"
Urinal, 1.0 GPF 3/4"
Urinal, greater than 1.0 GPF 3/4"
Urinal, flush tank 1/2"
Washfountain, circular spray 3/4"
Water Closet, 1.6 GPF Gravity Tank 1/2"
Water Closet, 1.6 GPF Flushometer Tank 1/2"
Water Closet, 1.6 GPF Flushometer Valve 1"
Water Closet, greater than 1.6 GPF Gravity Tank 1/2"
Water Closet, greater than 1.6 GPF Flushometer Valve 1"
Notes:
1 . Size of the cold branch outlet pipe, or both the hot and cold branch outlet pipes.
2. Appliances, Appurtenances, or Fixtures not included in this Table may be sized by reference to fixtures having a similar flow rate
and frequency of use.
3. The listed fixture imit values represent their total load on the cold water service. The separate cold water and hot water fixture
unit value for fixtures having both cold and hot water connections may each be taken as three-quarters (3/4) of the listed total
value of the fixture.
4. The Usted minimum supply branch pipe sizes for individual fixtures are the nominal (I.D.) pipe size.
5. For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons per minute
(GPM) and add it separately to the demand (in GPM) for the distribution system or portions thereof.
6. Assembly [Public Use (See Table 4-1)].
7. Reduced fixture unit loading for additional hose bibbs as used is to be used only when sizing total building demand and for pipe
sizing when more than one hose bibb is supplied by a segment of water distributing pipe. The fixture branch to each hose bibb
shall be sized on the basis of 2.5 fixture tinits.
4.0
4.0
10.0
10.0
1.0
4.0
4.0
1.0
1.5
1.5
0.5
0.5
0.7.
2.5
2.5
1.0
1.0
1.0
1.0
1.0
1.0
1.0
12.0
1.0
2.0
3.0
8.0
1.5
1.5
1.5
1.5
1.5
3.0
2.0
2.0
2.0
3.0
4.0
5.0
4.0
5.0
6.0
2.0
2.0
4.0
3.0
2.5
2.5
3.5
2.5
2.5
3.5
5.0
5.0
8.0
3.0
5.5
7.0
7.0
8.0
10.0
282
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
TABLE A-3
Allowance in Equivalent Length of Pipe for Friction Losis in Valves and Threaded Fittings*
Equivalent Length of Pipe for Various Fittings
90°
45°
90°
Coupling or
Diameter
Standard
Standard
Standard
Straight
Gate
Globe
Angle
of Fitting
Elbow
Elbow
Tee
Run of Tee
Valve
Valve
Valve
Inches
Feet
Feet
Feet
Feet
Feet
Feet
Feet
3/8
1.0
0.6
1.5
0.3
0.2
8
4
1/2
2.0
1.2
3.0
0.6
0.4
15
8
3/4
2.5
1.5
4.0
0.8
0.5
20
12
1
3.0
1.8
5.0
0.9
0.6
25
15
1-1/4
4.0
2.4
6.0
1.2
0.8
35
18
1-1/2
5.0
3.0
7.0
1.5
1.0
45
22
2
7.0
4.0
10.0
2.0
1.3
55
28
2-1/2
8.0
5.0
12.0
2.5
1.6
65
34
3
10.0
6.0
15.0
3.0
2.0
80
40
4
14.0
8.0
21.0
4.0
2.7
125
55
5
17.0
10.0
25.0
5.0
3.3
140
70
6
20.0
12.0
30.0
6.0
4.0
165
80
TABLE A-3 (Metric)
Equivalent Length of Pipe for Various Fittings
90°
45°
90°
Coupling or
Diameter
Standard
Standard
Standard
Straight
Gate
Globe
Angle
of Fitting
Elbow
Elbow
Tee
Run of Tee
Valve
Valve
Valve
mm
mm
mm
mm
mm
mm
mm
mm
10
305
183
457
91
61
2,438
1,219
15
610
366
914
183
122
4,572
2,438
20
762
457
1,219
244
152
6,096
3,658
25
914
549
1,524
274
183
7,620
4,572
32
1,219
732
1,829
366
244
10,668
5,486
40
1,524
914
2,134
457
305
13,716
6,706
50
2,134
1,219
3,048
610
396
16,764
8,534
65
2,438
1,524
3,658
762
488
19,812
10,363
80
3,048
1,829
4,572
914
610
24,384
12,192
100
4,267
2,438
6,401
1,219
823
38,100
16,764
125
5,182
3,048
7,620
1,524
1,006
42,672
21,336
150
6,096
3,658
9,144
1,829
1,219
50,292
24,384
*AIlowances are based on nonrecessed threaded fittings. Use one-half (1/2) the allowances for recessed threaded fittings or
streamlined solder fittings.
283
Appendix A
A 7 Example
UNIFORM PLUMBING CODE
Fixture Units and Estimated Demands
Building Supply Demand
Building Supply
Demand
Branch to Hot Water System
Demand
Fixture Unit in gallons
Kind of
No. of Fixture Unit
Total
ingpm
No. Of
Demand
per minute
Fixtures
Fixtures
Demand
Units (L per sec)
Fixtures
> Calculation
(L per sec)
Water Closets
130
8.0
1040
-
-
-
- .
Urinals
30
4.0
120
-
- .
-
-
Shower heads
12
2.0
24
12
12 X 2 X 3/4=18
-
Lavatories
100
1.0
100
-
100
100x1x3/4=75
-
Service Sinks
27
3.0
81
-
27
27x3x3/4=61
- ■
Total
1,365,252 gpm (15.8
L/s)
154
55 gpm (3.4 L/s)
Allowing for 15 psi (103.4 kPa) at the highest fixture under the maximum demand of 252 gallons per minute
(15.8 L/sec), the pressure available for friction loss is found by the following:
55 - [15 + (45 x 0.43)] = 20.65 psi
Metric: 379 - [103.4 + (13.7 x 9.8)] = 142.3 kPa
The allowable friction loss per 100 feet (30.4 m) of pipe is therefore:
100x20.65 ^200 = 10.32 psi
Metric: 30.4 X 142.3 4 60.8 = 71.1 kPa
284
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
500
Appendix A
400
Q. 300
O
"O
c
i 200
100
Chart A-2
Estimate Curves for Demand Load
i 1 j i i r ''" ''' 1
''' ■ i j ! t
i ■•■ ■ '• j 1 ■ ■ ■■ • ■
i i
^ <*''
^w^
1 ^ g
""■ ~ --f-^ ^ "^^(P'^ ■
rf^i i
1 1 I ^ ii '
i ^ ^
j ^^^
L ^ ^i
^ ^
* -J- ^ i^ "' ■
^^^^
_^r
ji ^
■ ^' "'' 1
1 * h "2^ +
J ■ r- .
^ ^
_^ 1^
^^
^^ !
^ ^'^ i
1 ^ ' , J , 1
' _^ I'
^j
^ ^^
■ ^ ^ir
^ aW
'\ ^ ^ ^v
A^ Jr
i^r^rj ti T'*'! ii'l T r ii
7 ^ n^ ' " No. 2 for system predominantly for flush tanks - -^
-'-y^-X -; ^ ,-' , ;-
if d^ \
i Jr !
I^r i -I ! 4- 4
m i ' ' L '
-j 1 1 r- \ 1 t
1 ■ ■ i J ■ 1 ■■ • i j . . .. _-
500 1000 1500 2000 2500 3000
Fixture Units
31.5
■o 25.4
o
u
0)
%
« 18.9
I
■D
C
(0
E 12.6
0)
Q
6.3
Chart A-2 (Metric)
Estimate Curves for Demand Load
\ r- — r- . -1 \ r— —r- -
t t i L ■
1 \
^ '
tf 1^
i , J ^
.^ ^
* ^
, J ^
^ i -J- ^ ^
^ ji^
1 ^^^
^ ^^
^ ^^
^^
^^T
"t "t ^ '•'^^ '
-.1*
^ F
_^ ^
^ '
^
1 ^^ -u
L. <l J.
^ (f [
1^ rf 1 1
t^'^T'"^ |p
.1^ . . . , ., i^f . . _ ,, X
^_5 — ^-LJ^^i ^ U — |— 1
^ ^^r
1 A ^ Ar
A^ A^
j^ A
' i ji^!?oX""^^°" ''■ ^°''" syst^"^ predominantly for flushometer valves —
- _^^ - No. 2 for system predominantly for flush tanks
- ^f-.r-'- ■-' ^ •'
W Ar
m W 1
r!^
^ 1 {
I \
500 1000 1500
Fixture Units
2000
2500 3000
285
Appendix A
UNIFORM PLUMBING CODE
o.
O
I
100
80
60
« 40
0)
° 20
■a
c
o
o
o
0)
I
T3
C
(8
E
V
Q
Chart A-3
Enlarged Scale Demand Load
^
^
"
ilU
,M1
u.
~.
"
r
"■■
-
-
™
"
"
"
"
'T
^
1^
*
«
*
r
^
^
■«
-
■>
«
y>
*
1«<
^
^
J
-
"
^
*
^
■«■
ji
-<
*
M
J
^
^
«*
«*
^
u
l»
*
^
S»
^
1
K*
•
•■
»*
^
,
,>
p
«*
1^
^
^
^
■*"
^
^
^
^
«*
r
«**
^
«*»
/
^
?
rf
^
>
i
^^
^
^^
_
^
wrm
_
^
^
„
„
^
TTM
■m
^
^
^
20 40 60 80 100 120 140 160 180 200 220 240
Fixture Units
Chart A-3 (Metric)
Enlarged Scale Demand Load
C Q
1 —
^^"
■n^
~T~
KBB
"T-
"-
—
D.O
1
i
L<-
-^
!
»--■
i
a>
^^ili"*
1
c; n
^1^
j^
W ■
• «*'
f->
^
^ '
• •<•
,^ ■
•^ ft
1-*^
*«
_^)^^
i»^
^^
^-^
»•*
■r'
P 1
• ^
-^
2 5
^
^'
•••
)•'
i
^
i
^
•.*■
*
>
i
i**
^K"
1
r
.r>^
1 3
rf*
?
i
■-
<^
!
i
\
/
1
^■H
_^
_..u.
-»
<-!«
1
_J__
„_,
.
20 40 60 80 100 120 140 160 180 200 220 240
Fixture Units
286
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-4
M^^H
M^
^^H^M
^■MM
■^
■"■
^^
" ■
Copper Tubing
Smooth Pipe
^•
J
^
Type M -
"
—
y
Type L -
—
X--
,.
Type K
y^
\
/
/^
M
\
^
,^
.'
,
^e^>
^
•<\
i^
./^
y
\
y
y
\
K
\ _/"
\_^
^
Q.
^y'
\
^.
y
\
"V^
^y\^
^^
\o
^xC
V^
X
\
''^\ y
^ _^
^
\y
^' \
./<\
;r
\y
/
N n
•
X
■^ \
\ v>
\,
^
^
^
,yyy^
^
y
\
\
/
\
\
!^<^'a
^
-^
^
/^
\'\^
X
\
V\
'\
^
"i
\
K'
S V>
K
^-^
VS^^/
\\
y^^
-^
\
\
-^
N
k
;;S^
<5>
^
y
^i
3^^N>
A
\
y
y
y
^ "A
V'
x' \
^\
\
V, ..r\Q,.-
\ ^
/
> ^
Vi? v^
\
V
\ v^^
A^
^
\
.'
/
^Vu
v^ \
\
y
' \
.. r^LJ
\,
y
\
/■ ^
y
^
^
S
./^ >
^
\
\
/^
\j
y.'
A^
x
>
r \^
^
\
v^
' v^
^
\^^
y
>^
V
y
^
/
-^
^ /y
\
\
>
-'^V^
:>^
\
\
/;
_^ ^
^N
\
' \
^
\
<
^-^
\:C^
'^-^
^
>
^"
\
\
-^
\
^'^
>^
^
\
^ yv\
1
y ,
■si
\
\^
^;
V
v'
^ j^ ^
■' \
\-^' \
\ ^
;^
^
■^
,
x>
\ -^--
v'"^
''
V ,
\^
V
/■
V
s ^ -^'
'\
'Vi
c>
•''v
\ \
'^y^
''y\
<"
s^^
,J
\
J
^
Js^r^„.
\
-y
',*<
\
\
v
•
^r-
'
V
■^
\ '' y
-<A
\
\.A2^
\
^
P^
K-
^\
^
^\
^ Xj:^
>'
\^
^;^
''
\
^
X
•/^
^
'
\
<^^v
^.
\
>
T
y "3^
\
\
s
''^
,<^^
X
^
X
^
N
\^
^
y^
1^
^
y_^
i;^^
-^
\
\
^
s
I u.uuu
8000
6000
5000
4000
3000
2000
1000
800
600
500
400
(D
300
3
cr
200
SE
i-i
<u
a
100
80
60
50
(0
C5
40
.£
30
;s
20
0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 5060 80100
Friction Loss - Lbs. per Square-Inch Head per 100-Foot Length
287
Appendix A
UNIFORM PLUMBING CODE
Chart A-4 (Metric)
"~~'
"*
-"
~~~
"
Smooth Pipe
.-'
X
Type M -
"
^
-'
Type L -
y^
J
Type K
y
y
/^
^
K
y
.^^
^
^
^
^
\
\
y^
^
\
y
y
$•
j\e^
^
\ /
y
^<^
J^
\ y^
y
' ^
..^ 3^_.
v^-
/^
\
^
^
^
\
.■^
::^ \
\
i
X
>
X
_^^
^'
-' \
, V
\
1^
>
\
/^JVO
\
x'
\,
^
\
\
\
:^\
^
£~
X-
nr
y\
^ ^/
y
\
^
^
\
K
'1
^
r
^
fe/
\.
y
\
».
-^
K
^
\
^<^^\
V
5
i
5,
"^ \
A
^
/
y
^^ \
^
\
^'
. ^'\ '^
V ^
>
, ^'
^x*
*! ,»^ W
\
y
N
\ ,
■
V
\'k
y
V
r - ^o-^
^
y-
\ ^
\
^
^
^N
V^
^
\
.-/
V^
^v^
^
y
\'"
\,
^
/;-'
' \/
'' _>
•^
A^
\
\
V
^^
r"
::^
7^
^-^A^
^
\
y
^
\
\
<^
/
\
V
(^j^ J
^
'■
X^
o >
^
""^
\
^'
\
^
\
('
y
\
^3^
^^
^
>
^A
Vx^
>
\
r"
\
.-^
n
I
s
5
\
1,
\ />^
V :^
<'
^^
\
^j
^y^ \
\
\
^
' s,
"^y
\ \
\ H
' ^
K' ^
\
/ '
.^\
v
-
V
(.'
"SVl
v.
N
^^
S,
/'
\ •'J-^T'
' V
v^
/^
^^
\s
^ ^i
'^^
V^'^
' P
V
^
\y>^
>
'A
\
\ ^
^
y-^,'
\^
^
\
'y".
^'\
/^
r
\
\
\ - V^
^
y" — ^
^
^^
\
\ ^^
/
\
N
^y\
^
'
\
^ ^
---/^
K'
^\
<
\^
\
\
\
1^'
^
^
1
i
^-^
\ \
.-^
^
^
c]
•
<
^\
\
i-
\
k
\
630.0
504.0
378.0
315,0.
252.0,
189.0
126.0
63.0
50.4
37.8
31.5
25.2
■D
18.9
C
o
12.6
u
0)
0)
i_
<3i
6.3
Q.
(0
5.0
0)
3.8
-J
3.2
c
2.5
^
1.9
o
u.
1.3
0.6
0.5
0.4
0.4
0.3
0.3
0.2
0.1
CM
■* t^
m
<3)
00
h-
CO
If) ■^
CM
o
(35
00
00
h-
r-.
CO
ID
CO
CO Ol
CD
CM
lO
00
y—
■t h-
CO
o>
r^
CO
in
■q-
m
,«.
m
T-
T— T—
CO
CO
CD CD
CO
CM
in
00
■*
t^
CI
no
■^
■^ ■^
CD
o>
CO
CO
CD
CO
CM
CM
CO
Friction Loss - 32.9 Pa/m
288
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-5
^MHH
MIM
-T-
^■^
^
^T
— T^
^" ■
Fairly
Smooth
s,
y
\ ~.^<'C\
^
s,
\
^
^
\
y
s,
-''
_^-
\ :-, \<^
5^v^
\
^
jp
y
^
.^^'
'^ \
k^
\
/
^
i'X V
^X
<(
\
L
^^
;^^ "
^
^
--"'
-V
\
\
\
V
/"
.. 6„
^
/
\
/
\
\
^
k:
s
V
>
\
/
^
y
\
\
/
/
--
y \
A,
«i
'\
\^
\
^
V
v^
\,
^^
y
y
?i\
^--^N.
\^
s
s
^^^
'v
.^"■"^ \-^
■^
y:
" \
^
A,
\
\^^ \
\
N
y
y
^'N
^
N
:<
\
^
<^
X
)
\
^
^
X
\/
S^
y
0,
\
y
y
\ ^
/
\
."■
s \
/^
^
,^
^
^
''v>
y
-^
\
\
/'
s
X
S 'A''^
^
'-'
5r
^
\
y
^
y
A'
\ ^\'2:.
<'
y
\'^ ^
y^
\ ^^y
y^
\
\^
V^
X
^\
"a
V
\,
\
\
^
^
\^
'\
S
^<cO-
\
y^
X
\
\
s
^
/
\
^
^
\
^^y^
^
S^
J
/"
' \
V
\
v^
s \
\
k
>
^
\
K-^'
X
5
/•
\
\
\
'b\K
\
J
X-
" \
\
■ \
V
\
\
N
\
JK
\
\
>^
\'
\
<
-A
'■
^\
\
\
A
i?i
y\
^
^
\
^,
,
k
V/
s,
^>
_ __^
^
^
\
s ^<r^.
V
\
s y
y
\ x'
\
/
N
\
\
y
\
\
■^^
\
A
\
\
^
/^
\[
\
X
^
y-
\
v
^
^^
\
vX\^'
A
\
^
\
\
\
\
^
^
\
i.-
«;:
\ \
V
/
X
\
\
\
i.
\
\
\
\
10,00(
8000
6000
5000
4000
3000
2000
1000
800
600
500
400
300
3
C
i
200
la
a
100
80
(0
c
o
75
C5
60
50
c
40
30
o
u.
0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80100
Friction Loss - Lbs. per Square-Inch IHead per 100-Foot Length
289
Appendix A
UNIFORM PLUMBING CODE
Chart A-5 (Metric)
504.0
Friction Loss - 32.9 Pa/m
290
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-6
^^
aa^m
— — ^
■■^"
-1
^"
^"
— ^
r-
5'
Fairly Rough
>
s,
^ \
X
\,
-^
\—
\
tt^ \
^
\,
-X
s^
\
^
<
\
x^
\
\
^
s
^^
\ .
y^
\
^
>
^.
--'
\ \
^
y
\
\ ^y'
\
\
y
— \
-TF
v^
\
\
\
4^
•,jM> "^
^
N
<
^"
'\
"i
/
\
fo
\
\
^
0^
s ^^
X
^
,^
\
;Oj
^
^
---■
>
^^ ^
I ^
s
''\
V"
^\
s ^
^
< .._ .
V
\
'\
^ j
^
\ ^
si'
^
>
\^
\
A
\
^ \ ^
^
""3\
\^
^
\
''
^
\^
''
\
^
^..--A
X
\
\
>
\
^^
\
N
y^
V^
)
y^
^i
\^
\
\
<^
\
A
\
y^
'^ V
^
Vc
^
--^
\
■^ \
^
>
f^
\
'^\
^
k
^
>
\
,^ ^
K^
\
\
^
^
-^'
\^
i
\^^\
^
<S>
\
\V"
A
\,
A
\
1
^\
''\
^'
\
.-^X*?!-
V
^
r <r
\
J
\
f^^^
i
X
. Vi
^
A'
v^
'
■^
\^
I
^
•^
s V
^y^
s
^
^
\
^«-^V
\
^'
y ^\
\<
\
\ V
"
^
\
s
V
^
A
\
<\
>.Y^\
^
\
\
^ J
Y
\
^'
^^
S
\
\
y^
' V
<
/
>
^
\
'\
M
.-"
/-
A
\
\
^^\
X
^
\
\^
\
^
A
A
^
\
^
^
\
<
X
^
^
^
^
\
\
^y^ \
\^
\ ^
.^
\
■^ \
' ^
^
\^^\^
\
y^
N
^
\
^^-^
\, ^
^r v
\,
V
^
^
V
\^
^
\ \
\
X
"\
^^
/
X
\
\.
\
\ \
4^^
^
\
^'
Y
r\
\
\
\^
\
\
^
Y
^
^
V
H
\
\
S^
\
<\
\
^
\
1
\
-^
\
\
\.
\
A
\
J
\-.
V
\
\
L.
\
\
\
10,000
8000
6000
5000
4000
3000
2000
1000
800
600
500
400
300
200
100
80
0)
Q.
(0
c
o
(0
60
O
50
c
40
30
%
o
u.
20
0.1 0.2 0.3 0.4 0.6 0.8 1 2 3 4 5 6 8 10 20 30 40 50 60 80100
Friction Loss - Lb. per Square-Inch Head per 100-Foot Length
291
Appendix A
UNIFORM PLUMBING CODE
Chart A-6 (Metric)
■^
F""
flB^"
^^
— '
Fairly Rough
i
\
\
- ^\
/
\
^ ■
1
\
\
\
^^"^
\
^
\,
\
<
\
^
\
\
^
\
^^
\ .
^
\
\
\
A
^
^
\
,
\ >-
^
\
\^y^
\
\
^
"^
— ^
\
\
f
\
\
<
'\
\
-^
k
frO
\
\)'
^
5
\
^
^
\
\
; A
>
\
3
A
\
^
^^^^^
j^' N,
'' \^
V ^
'^
<5
■^
\
\^
/'
\ ^
^
\^
^'
^ \0
^
\ ^,,^^
^
^''^
^y^
^
\
.
„^A
^
\
\
V^A
s^V
\
^^
\-;^
^
^
;^
4
\
\
>
Y^
xO
\
-A
\
^^
Y)^
^ \
>
\
\
^\,
\ ^
\
^
[>,
\
i ^
r
^C
\
-^
-
-^
K
\
^xy"
\
h
^
A
\
V
/^
\-^
\y
V'jji
\
>^
\'
-'
\
^ \
j^ \ "To
\
^
\
y\
^
\
^''^^->
<
^
^\
\V
,^\
V
A
--^
/
\
^
\
.^^^
^"
V'^^x
\ ^
\ V'
,
X
\
Y
^
■K ^
, /
\
:^
\
cO
-V^ \
^
\
\
f
\^
\
' \]^
^
\
\
' \
\
A
\
^
A
\^
t
'-^\
^
\
v
\
A
y
\
\
<
\
^
^
-^
\
y-^
\ ^
\
\^
\
'^
V
\
\ ^ — 'y
\
^y
\
^\
\
y
'\ \
\
lV
y^
'
^
\'
\^
K
\ \
\
^
\
^^
^
^
\
^
\
\ N
\^
A\
\
^'
V
v
\
\
x^
\
^
v
^
^
\
.^
\
\
^■^
'^\
\0
^
\
\
\
X
^
\
L.
\j
\
lA
\
v.
w
^
\
\.
\
\
630.0
504.0
378.0
315.0
252.0
189.0
126.0
63.0
50.4
37.8
31.5
25.2
18.9
12.6
c
o
u
0)
6.3
a
5.0
3.8
3.2
(0
2.5
c
1.9
1.3
o
0.6
0.5
0.4
0.4
0.3
0.3
0.2
0.1
1- 1- T- CJ CO
02 CO tD CD CD CM
1- 1- T- C\J CO
00 CO r--; N (D in
<D in ■* CO T^ d)
00 T- Tt r^ CO 00
a> CO CD O) CD C\J
T- ^ T- c\j CO
Friction Loss - 32.9 Pa/m
292
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-7
p-
— v —
r\^
—
—
n
\
■-
--
^
—
Rough
\
\
\
\^
\
_zV
^y'.
\
\
x,
\^
V" \
^y^
^^
\
\
\
^
^
"\
\
\ — — ^
^^
^^
^
S-^'N.
\
V .
— \
\
\
^
N
^
^
^^;
\
^
^
\
V^
<\i
y
\
h
\
^'
/
V
■^
\ .
-^
\
^
\
\
\
,
-V
y'
V
\
^
\
\
\
L-^
'
s
^ — ■
^
^^
^
\
>
yf \
\
€>^
^.
\
y^
^
--'
r
V
\
>^
\ \
V
-^
\
^-^
\
^^^
,•
^\
^
\
\ -V
r\
<i
^
\
3c
^
^>-
\ - .
^
\
p^
1 \
<^
^i
^.
'
^
^
^r'
Y
y^
s
jj\^
\
\
ft
^
k
y<^
^
^
\
\
\
-
■\
r^
r
5^
\
%
}
\
^*^,J%
L
\
\
/-'^
\
i--t>^
\
; ' ■■ -- '
^
*^>
^^
''V'
^^^
\
V ^
S,'?'
^^
^
^
■\
i'
\ ^^
\
^
A,
\
\a>
yy
"\
\^
^
\
Ao>
3c
\
1 ,
V
^
-V,-
J
^
=^V7^
"^^^
\
V
^
^
.-^
.^y^
^
^
?>
\,
^
A
\
^
y^
\
y
^
^ct
^ \
^
A
\
\^^
^^-*
^V^
\
^
^
\
\
^^
\
^
h
^
^
\
<
X
^
N
\
.---
\
^
-
^
\
^^
\ \>
"A^
i
^
\
^^
A
^
\ ^^'
\
^^
\
^
\ "
^^^
^
\
-pi^
^f
^
\
\
\
^
\ .
^.. v
^
' *i
\
\
\-
-A
\^
'V
-^\ \
\
^-\
\,
^
N
^^^
\
^
N\'
■_^
\
Z^^
\
,^-
s^
\
^
^
\
\
\ .
^
K
^
\^/
^
\
>
^
^
\
\
i^.
^\
\
L
-
^
^
\
\^--^^
\
\
\
i.
\
10,000
8000
6000
5000
4000
3000
2000
1000
800
600
500
400
0)
HM
300
3
c
200
s
V.
0)
Q.
il\
100
C
80
o
60
(Q
50
o
40
c
30
%
o
20
UL
10
8
6
5
4
3
0.1
0.2 0.3 0.4 0.6 0.8 1
2 3 4 56 8 10
1
20 30 40 50 60 80100
Friction Loss - Lbs. per Square-Inch Head per 100 Foot Length
293
Appendix A
UNIFORM PLUMBING CODE
Chart A-7 (Metric)
^^^
M^
^■™
T-~
—
■^
--
— ^^
— r
^^
■^
T!
^T" "
Rough
\
\
-^
s,
\
v
s,
\,
s
,^^
\
^■
y
\
\-
"'''^X
^^^
\
^
"
\
^
y'
'\
^
\
^'■
K \
^
^
\
\
^^^^"^
— '
\ \ - -^
\
\
\
^
^
,v
\
^
^
\
%■
^
^
\
^^ V
^^
\
\
\
^'
>
>
^
V
^
^
\
\
^
^\
\
^
\
\
^
N,
\-
^
^
3^
y
\
-^
\
>^
^
^\^
^
\,
\
f^ ^t
4>J
L-\
\
;z::^ .
\^
^
\l
^
\,
,^
N '" V
\
^'
\
y^\
^
^
\
pt
^
\
*)J
\
\
^
\
1$
■^
\
"^
\
pi
\
" ^
^
■^
\
5~r^
^
\
\<
i>
^
V
^A?-
A
^
\
^^-
V
-
■"
-^^
\^^N
P
^
^
7-
^^
^
\
\
^
^\
V^
\ ^
\
- \.-3r;^
\
V-
^
^^
^^
\
' \ -^^^
N/O
^ ^
^
\
cQ,--^
\
^
\
y^ \
\^
^
\^
^'
■^^
A
\
'^ Vfe
\
^
\ -
^
\
-'_.. ^
s^
t^
\
V
^
^
^
^^j-
^o
^
\
Pifi -^
^
\
^
^
\
^'>
\o
^
^
^^
-^ \
\
\^
\
f^
L."^
.^Ko
^
%
^
"
\
\
-^
\
^
^
\
\
^
V
^
:^ W
/
\
\
.-'
S
f^
-
\
\
^^
s \J
\J
\
\
\
-"'
-'l
\-'^'
^
'
^^
It
^^
^
\,
\
\
\
^^
V '
"'''x
" \
\
\
\'
^
'A
\
\
\
^
\
\,
^
'
\
^^'Y
\
\
^^
!^
\
Y^
A
\,
^
^
Nr^
^\
K
^
^^
\
\
^
\
\
\
\
i.
1
\
^
\
^;
i-.
' \^
\
^
-
^
y
\
\^^
!»-
h
\
1
N
630.0
504.0
378.0
315.0
252.0
189.0
126.0
63.0
50.4
37.8
31.5
25.2
18.9
12.6
c
o
u
0)
0)
6.3
5.0
3.8
3.2
0)
Q.
_i
2.5
c
1.9
1.3
i
0.6
0.5
0.4
0.4
0.3
0.3
0.2
0.1
■.-1-1- C\i CT)
r^
CO
UT*
C\J
o
S8
en
n
CD <J)
CO
CD
CM
(M
OO
00 h~
h-
CD
in
C3>
i5 ?
CO CD
(J)
CO
CD
00
CM
1- 1- 1- CM CO
Friction Loss - 32.9 Pa/m
294
APPENDIX B
EXPLANATORY NOTES ON COMBINATION WASTE AND VENT SYSTEMS
(See Section 910.0 of the UPC for specific limitations.)
B 1 Combination waste and vent systems, as
outlined in Section 910.0 of this code, cover the
horizontal wet venting of a series of traps by means
of a common waste and vent pipe. Pipe sizes at least
two (2) pipe sizes larger than those required for a
conventional system are designed to maintain a
wetted perimeter or flow line low enough in the
waste pipe to allow adequate air movement in the
upper portion, thus balancing the system. Sinks,
lavatories, and other fixtures that rough in above the
floor, should not be permitted on a combination
waste and vent system, which, at best, is merely an
expedient designed to be used in locations where it
would be structurally impractical to provide venting
in the conventional manner.
Combination waste and vent systems are
intended primarily for extensive floor or shower
drain installations where separate venting is not
practical, for floor sinks in markets, demonstration or
work tables in school buildings, or for similar
applications where the fixtures are not adjacent to
walls or partitions. Due to its oversize characteristics,
such a waste system is not self-scouring and,
consequently, care should be exercised as to the type
of fixtures connected thereto and to the location of
cleanouts. In view of its grease-producing potential,
restaurant kitchen equipment should not be
connected to a combination waste and vent system.
B 2 Caution must be exercised to exclude
appurtenances delivering large quantities or surges
of water (such as pumps, sand interceptors, etc.)
from combination waste and vent systems in order
that adequate venting will be maintained. Small
fixtures with a waste-producing potential of less
than seven and one-half (7-1/2) gallons per minute
(0.5 L/sec.) may be safely assigned a loading value
of one (1) unit. Long runs should be laid at the
minimum permissible slope in order to keep
tailpieces as short as possible. Tailpieces should not
exceed two (2) feet (610 mm) in length, which may
necessitate slopes up to forty-five (45) degrees (0.79
rad) (see definition of horizontal pipe) on some
branches.
B 3 It is essential that the pneumatics of such a
system be properly engineered, as the air pressure
within the line must at all times balance that of
outside atmosphere in order to prevent either trap
seal loss or air locking between traps. Long mains
shall be provided with additional relief vents
located at intervals not exceeding one hundred
(100) feet (30,480 mm). Each such relief vent should
equal at least one-half (1/2) of the inside cross-
sectional area of the drainpipe served.
B 4 Trap sizes are required to be equivalent to
the branches they serve (two (2) pipe sizes larger
than normal), and tailpieces between fixtures or
floor drains and such traps should be reduced to
normal size.
B 5 Duplicate layout drawings of each such
proposed piping system must be presented to the
Authority Having Jurisdiction and approval
obtained before any installation is made.
Complicated layouts should be checked by
qualified personnel.
B 5.1 Example of Sizing.
A floor drain normally required two (2) inch (50
mm) trap and waste. On a combination waste
and vent system, both trap and waste must be
increased two (2) pipe sizes (through 2-1/2" and
3") (65 mm and 80 mm), which would make the
trap three (3) inch (76 mm). Pipe sizes
recognized for this purpose are 2 in., 2-1/2 in., 3 in.,
3-1/2 in., 4 in., 4-1/2 in., 5 in., 6 in., etc. (50 mm,
65 mm, 76 mm, 90 mm, 100 mm, 115 mm, 125
mm, 150 mm, etc.). The tailpiece between the
floor drain and its trap should be two (2) inches
(51 mm) (or normal size) to ensure that the
amount of wastewater entering the trap only
partially fills the waste branch. A three (3) inch
(76 mm) floor drain would thus require a four
(4) inch (100 mm) trap, a four (4) inch (100 mm)
floor drain, and five (5) inch (125 mm) trap, etc.,
for the reasons previously stated.
WHEN IN DOUBT, CHECK WITH YOUR
LOCAL Authority Having Jurisdiction.
295
UNIFORM PLUMBING CODE
296
APPENDIX D
SIZING STORM WATER DRAINAGE SYSTEMS
D 1 Roof Drainage.
The rainfall rates in Table D-1 should be used for
design unless higher values are established locally.
D 2 Sizing by Flow Rate.
Storm drainage systems can be sized by storm water
flow rates, using the appropriate GPM/square foot of
rainfall listed in Table D-1 for the local area.
Multiplying the listed GPM/square foot by the roof
area being drained by each inlet (in square feet)
produces the gallons per minute (GPM) of required
flow for sizing each drain inlet. The flow rates (GPM)
can then be added to determine the flows in each
section of the drainage system. Required pipe sizes
for various flow rates (GPM) are listed in Table 11-1
and Table 11-2.
D 3 Sizing by Roof Area.
Storm drainage systems can be sized using the roof
area served by each section of the drainage system.
Maximum allowable roof areas with various rainfall
rates are listed in Table 11-1 and Table 11-2, along
with the required pipe sizes. Using this method, it
may be necessary to interpolate between two listed
rainfall rate columns (inches per hour). To determine
the allowable roof area for a listed pipe size at a
listed slope, divide the allowable square feet of roof
for a one (1) inch (25.4 mm/h) rainfall rate by the
listed rainfall rate for the local area. For example, the
allowable roof area for a six (6) inch (152 mm) drain
at one-eighth (1/8) inch (3.2 mm) slope with a
rainfall rate of 3.2 inches (81 mm/h) is 21,400/3.2 =
6,688 square feet (621.3 m^ ).
D 4 Capacity of Rectangular Scuppers.
Table D-2 lists the discharge capacity of rectangular
roof scuppers of various widths with various heads
of water. The maximum allowable level of water on
the roof should be obtained from the structural
engineer, based on the design of the roof.
TABLE D-1
Maximum Rates of Rainfall for Various Cities
The rainfall rates in this table are based on U.S. Weather Bureau
Technical Paper No. 40, Chart 14: 100- Year 60-Minute Rainfall (inches).
States and Cities
Storm Drainage
60-Minute Duration, 100- Year Return
Inches/Hour
GPM/Square Foot
ALABAMA
Birmingham
Himtsville
3.7
3.3
0.038
0.034
Mobile
4.5
0.047
Montgomery
3.8
0.039
ALASKA
Aleutian Islands
1.0
0.010
Anchorage
Bethel
0.6
0.8
0.006
0.008
Fairbanks
1.0
0.010
Juneau
0.6
0.006
ARIZONA
Flagstaff
Phoenix
2.3
2.2
0.024
0.023
Tucson
3.0
0.031
297
Appendix D
UNIFORM PLUMBING CODE
TABLE D-1 Continued
Storm Drainage
States and Cities
60-Minute Duration, 100- Year Return
Inches/Hour
GPM/Square Foot
ARKANSAS
Eudora
3.8
0.039
Ft. Smith
3.9
0.041
Jonesboro
3.5
0.036
Little Rock
3.7
0.038
CALIFORNIA
Eureka
1.5
0.016
Lake Tahoe
L3
0.014
Los Angeles
2.0
0.021
Lucerne Valley
2.5
0.026
Needles
1.5
0.016
Palmdale
3.0
0.031
Redding
1.5
0.016
San Diego
1.5
0.016
San Francisco
1.5
0.016
San Luis Obispo
1.5
0.016
COLORADO
Craig
1.5
0.016
Denver
2.2
0.023
Durango
1.8
0.019
Stratton
3.0
0.031
CONNECTICUT
Hartford
2.8
0.029
New Haven
3.0
0.031
DELAWARE
Dover
3.5
0.036
Rehobeth Beach
3.6
0.037
DISTRICT OF
COLUMBIA
Washington
4.0
0.042
FLORIDA
Daytona Beach
4.0
0.042
Ft. Myers
4.0
0.042
Jacksonville
4.3
0.045
Melbourne
4.0
0.042
Miami
4.5
0.047
Palm Beach
5.0
0.052
Tampa
4.2
0.044
Tallahassee
4.1
0.043
GEORGIA
Atlanta
3.5
0.036
Brunswick
4.0
0.042
Macon
3.7
0.038
Savannah
4.0
0.042
Thomasville
4.0
0.042
298
SIZING STORM WATER DRAINAGE SYSTEMS
Appendix D
TABLE D-1 Continued
States and Cities
Storm Drainage
eO-iVlinute Duration, 100-Year Return
Inches/Hour
GPIVI/Square Foot
HAWAII
Rainfall rates in the Hawaiian Islands vary from 1-1/2 inches/hour to
inches /hour, depending on location and elevation. Consult local data.
IDAHO
Boise
Idaho Falls
Lewiston
Twin Falls
ILLINOIS
Chicago
Harrisburg
Peoria
Springfield
INDIANA
Evansville
Indianapolis
Richmond
South Bend
IOWA
Council Bluffs
Davenport
Des Moines
Sioux City
KANSAS
Goodland
Salina
Topeka
Wichita
KENTUCKY
Bowling Green
Lexington
Louisville
Paducah
LOUISIANA
Monroe
New Orleans
Shreveport
MAINE
Bangor
Kittery
Millinocket
1.0
1.2
1.0
1.1
2.7
3.1
2.9
3.0
3.0
2.8
2.7
2.7
3.7
3.0
3.4
3.6
3.5
3.8
3.8
3.9
2.9
2.9
2.8
3.0
3.8
4.5
4.0
2.2
2.4
2.0
0.010
0.012
0.010
0.011
0.028
0.032
0.030
0.031
0.031
0.029
0.028
0.028
0.038
0.031
0.035
0.037
0.036
0.039
0.039
0.041
0.030
0.030
0.029
0.031
0.039
0.047
0.042
0.023
0.025
0.021
299
Appendix D
UNIFORM PLUMBING CODE
TABLE D-1 Continued
Storm Drainage
States and Cities
60-Minute Duration, 100- Year Return
Inches/Hour
GPM/Square Foot
MARYLAND
Baltimore
3.6
0.037
Frostburg
2.9
0.030
Ocean City
3.7
0.038
MASSACHUSETTS
Adams
2.6
0.027
Boston
2.7
0.028
Springfield
2.7
0.028
MICHIGAN
Detroit
2.5
0.026
Grand Rapids
2.6
0.027
Kalamazoo
2.7
0.028
Sheboygan
2.1
0.022
Traverse City
2.2
0.023
MINNESOTA
Duluth
2.6
0.027
Grand Forks
2.5
0.026
Minneapolis
3.0
0.031
Worthington
3.4
0.035
MISSISSIPPI
Biloxi
4.5
0.047
Columbus
3.5
0.036
Jackson
3.8
0.039
MISSOURI
Independence
3.7
0.038
Jefferson City
3.4
0.035
St. Louis
3.2
0.033
Springfield
3.7
0.038
MONTANA
Billings
L8
0.019
Glendive
2.5
0.026
Great Falls
1.8
0.019
Missoula
1.3
0.014
NEBRASKA
Omaha
3.6
0.037
North Platte
3.5
0.036
Scotts Bluff
2.8
0.029
NEVADA
Las Vegas
1.5
0.016
Reno
1.2
0.012
Winnemucca
1.0
0.010
300
SIZING STORM WATER DRAINAGE SYSTEMS
Appendix D
TABLE D-1 Continued
Storm Drainage
States and Cities
60-Minute Duration,
100- Year Return
Inches/Hour
GPM/Square Foot
NEW HAMPSHIRE
Berlin
2.2
0.023
Manchester
2.5
0.026
NEW JERSEY
Atlantic City
3.4
0.035
Paterson
3.0
0.031
Trenton
3.2
0.033
NEWIVIEXICO
Albuquerque
2.0
0.021
Carlsbad
2.6
0.027
Gallup
2.1
0.022
NEW YORK
Binghamton
2.4
0.025
Buffalo
2.3
0.024
New York City
3.1
0.032
Schenectady
2.5
0.026
Syracuse
2.4
0.025
NORTH CAROLINA
Asheville
3.2
0.033
Charlotte
3.4
0.035
Raleigh
4.0
0.042
Wilmington
4.4
0.046
NORTH DAKOTA
Bismarck
2.7
0.028
Fargo
2.9
0.030
Minot
2.6
0.027
OHIO
Cincinnati
2.8
0.029
Cleveland
2.4
0.025
Columbus
2.7
0.028
Toledo
2.6
0.027
Youngstown
2.4
0.025
OKLAHOMA
Boise City
3.4
0.035
Muskogee
4.0
0.042
Oklahoma City
4.1
0.043
OREGON
Medford
1.3
0.014
Ontario
1.0
0.010
Portland
1.3
0.014
301
Appendix D
UNIFORM PLUMBING CODE
TABLE D-1 Continued
Storm Drainage
States and Cities
60-Minute Duration, 100- Year Return
Inches/Hour
GPM/Square Foot
PENNSYLVANIA
Erie
2.4
0.025
Harrisburg
2.9
0.030
Philadelphia
3.2
0.033
Pittsburgh
2.5
0.026
Scranton
2.8
0.029
RHODE ISLAND
Newport
3.0
0.031
Providence
2.9
0.030
SOUTH CAROLINA
Charleston
4.1
0.043
Columbia
3.5
0.036
Greenville
3.3
0.034
SOUTH DAKOTA
Lemmon
2.7
0.028
Rapid City
2.7
0.028
Sioux Falls
3.4
0.035
TENNESSEE
Knoxville
3.1
0.032
Memphis
3.5
0.036
Nashville
3.0
0.031
TEXAS
Corpus Christi
4.6
0.048
Dallas
4.2
0.044
El Paso
2.0
0.021
Houston
4.6
0.048
Lubbock
3.3
0.034
San Antonio
4.4
0.046
UTAH
Bluff
2.0
0.021
Cedar City
1.5
0.016
Salt Lake City
1.3
0.014
VERMONT
Bennington
2.5
0.026
Burlington
2.3
0.024
Rutland
2.4
0.025
VIRGINIA
Charlottesville
3.4
0.035
Norfolk
4.0
0.042
Richmond
4.0
0.042
Roanoke
3.3
0.034
302
SIZING STORM WATER DRAINAGE SYSTEMS
Appendix D
TABLE D-1 Continued
Storm Drainage
States and Cities
60-Minute Duration, 100- Year Return
Inches/Hour
GPM/Square Foot
WASHINGTON
Seattle
1.0
0.010
Spokane
1.0
0.010
Walla Walla
1.0
0.010
WEST VIRGINIA
Charleston
2.9
0.030
Martinsburg
3.0
0.031
Morgantown
2.7
0.028
WISCONSIN
Green Bay
2.5
0.026
Lacrosse
2.9
0.030
Milwaukee
2.7
0.028
Wausau
2.5
0.026
WYOMING
Casper
1.9
0.020
Cheyenne
2.5
0.026
Evanston
1.3
0.014
Rock Springs
1.4
0.015
303
Appendix D
UNIFORM PLUMBING CODE
TABLE D-2
Discharge from Rectangular Scuppers - Gallons per Minute
Water Head, Width of Scupper in Inches
Inches 6 12 18 24 30
36
1/2
6
13
19
25
32
38
1
17
35
53
71
89
107
1-1/2
31
64
97
130
163
196
2
98
149
200
251
302
2-1/2
136
207
278
349
420
3
177
271
364
458
551
3-1/2
339
457
575
693
4
412
556
700
844
TABLE D-2 (Metric)
Discharge from Rectangular Scuppers - Liters per Second
Water Head Width of Scupper in Millimeters
(mm) 152 305 457 610 762
914
13
0.4
0.8
1.2
1.6
2.0
2.4
25
1.1
2.2
3.3
4.5
5.6
6.8
38
2.0
4.0
6.1
8.2
10.3
12.4
51
6.2
9.4
12.6
15.8
19.1
64
8.6
13.1
17.5
22.0
26.5
76
11.2
17.1
23.0
28.9
34.8
89
21.4
28.8
36.3
43.7
102
26.0
35.1
44.2
53.3
Notes:
1. Table D-2 is based on discharge over a rectangular weir with end contractions.
2. Head is the depth of water above bottom of the scupper opening.
3. The height of the scupper opening should be at least two (2) times the design head.
4. Coordinate the allowable head of water with the structural design of the roof.
304
APPENDIX E
MANUFACTURED/MOBILE HOME PARKS AND
RECREATIONAL VEHICLE PARKS
Part A
Manufactured/Mobile Home (M/H) Park
Definitions and General Requirements
E 1 Manufactured/Mobile Home.
A structure transportable in one (1) or more sections,
which in the traveling mode is eight (8) body feet
(2,438 mm) or more in width and forty (40) body feet
(12,192 mm) or more in length or, when erected on
site, is three hundred twenty (320) or more square feet
(29.7 m^), and which is built on a permanent chassis,
and designed to be used as a dwelling with or without
a permanent foundation when connected to the
required utilities. It includes the plumbing, heating,
air conditioning, and electrical systems contained
therein. For further clarification of definition, see
Federal Regulation 24 CFR.
E 1.1 Manufactured/Mobile Home Accessory
Building or Structure. A building or structure
that is an addition to or supplements the facilities
provided to a M/H. It is not a self-contained,
separate, habitable building or structure.
Examples are awnings, cabanas, ramadas,
storage structures, carports, fences, windbreaks,
or porches.
E 2 Manufactured/Mobile Home Lot. A portion of
a M/H park designed for the accommodation of one
M/H and its accessory buildings or structures for the
exclusive use of the occupants.
E 3 Manufactured/Mobile Home Park. A parcel
(or contiguous parcels) of land that has been so
designated and improved that it contains two (2) or
more M/H lots available to the general public for the
placement thereon of M/H for occupancy.
General
E 4 The M/H park plumbing and drainage systems
shall be designed and installed in accordance with the
requirements of this appendix and the requirements
of this code.
E 5 Before any plumbing or sewage disposal facilities
are installed or altered in any M/H park, duplicate
plans and specifications shall be filed and proper
permits obtained from the department or departments
having jurisdiction. Plans shaU show in detail:
(A) Plot plan of the park drawn to scale,
indicating elevations, property lines,
driveways, existing or proposed buildings,
and the sizes of M/H lots.
(B) Complete specification and piping layout of
proposed plumbing systems or alteration.
(C) Complete specification and layout of
proposed sewage disposal system or alteration.
(D) The nature and extent of the work proposed,
showing clearly that such work will
conform to the provisions of this code.
PartB
Manufactured/Mobile Home Park Drainage
System Construction
E 6 Drainage Systems.
A drainage system shall be provided in all M/H
parks for conveying and disposing of all sewage.
Wherever feasible, connection shall be made to a
public system. All new improvements shall be
designed, constructed, and maintained in accordance
with applicable laws and regulations. Where the
drainage lines of the M/H park are not connected to
a public sewer, all proposed sewage disposal facilities
shall be approved by the Authority Having
Jurisdiction prior to construction.
E 7 Material.
Pipe and fittings installed underground in M/H park
drainage systems shall be of material approved for the
purpose. M/H lot drainage inlets and extensions to
grade shall be of material approved for underground
use within a building.
E 8 Drainage (Sewage) Lines.
All drainage (sewage) collection lines shall be located
in trenches of sufficient depth to be free of breakage
from traffic or other movements and shall be
separated from the park water supply system as
specified in this code. Drainage (sewage) lines shall
have a minimum size and slope as specified in
Tables E-1 and E-2.
E 9 M/H Lot Drainage Inlet and Lateral.
(A) Size. Each lot shall be provided with a
drainage inlet not less than three (3) inches
(76 mm) in diameter.
(B) The lateral line from the inlet to the sewage
drain line shall slope at least one-fourth
(1/4) inch per foot (20.9 mm/m). All joints
shall be watertight.
(C) All materials used for drainage connections
between a M/H and the lot drainage inlet
305
Appendix E
UNIFORM PLUMBING CODE
shall be semi-rigid, corrosion-resistant, non-
absorbent, and durable. The inner surface
shall be smooth.
(D) Provision shall be made for plugging or
capping the sewage drain inlet when a
M/H does not occupy the lot. Surface
drainage shall be diverted away from the
inlet. The rim of the inlet shall extend not
more than four (4) inches (102 mm) above
ground elevation.
E 10 Location of Lot Drain Inlet.
Each lot drainage inlet shall be located in the rear
third section and within four (4) feet (1,219 mm) of
the proposed location of the M/H.
E11 Pipe Size.
(A) Each M/H lot drainage inlet shall be
assigned a waste loading value of twelve
(12) drainage fixture units, and each park
drainage system shall be sized according to
Table E-1 or as provided herein. Drainage
laterals shall be not less than three (3) inches
(76 mm) in diameter.
(B) A park drainage system that exceeds the
fixture unit loading of Table E-1 or in which
the grade and slope of drainage pipe does
not meet the minimum specified in Table
E-2 shall be designed by a registered
professional engineer.
E 12 M/H Drain Connector.
(A) An M/H shall be connected to the lot
drainage inlet by means of a drain cormector
consisting of approved pipe not less than
Schedule 40, appropriate fittings and
connectors, and not less in size than the
M/H drainage outlet. An approved
cleanout shall be provided between the
M/H and the lot drainage inlet. The fitting
connected to the lot drainage inlet shall be a
directional fitting to discharge the flow into
the drainage inlet.
TABLE E-1
Drainage Pipe Diameter and Number of Fixture Units on Drainage System
Size of Drainage Pipe Maximum Number
Inches mm of Fixture Units
2*
51
8
3
76
35
4
102
256
5
127
428
6
152
720
8
203
2640
10
254
4680
12
305
8200
^Except six unit fixtures
TABLE E-2
Minimum Grade and Slope of Drainage Pipe
Slope per
Slope per
Pipe Size
100 ft.
(30.5 m)
Pipe Size
100 ft. (30.5 m)
Inches
mm
Inches
mm
Inches
mm
Inches mm
2
51
25
635
6
152
8 203
3
76
25
635
8
203
4 102
4
102
15
381
10
254
3-1/2 89
5
127
11
279
12
305
3 76
306
MANUFACTURED/MH PARKS AND RV PARKS
Appendix E
(B) A drain connector shall be installed or
maintained with a grade not less than one-
fourth (1/4) inch per foot (20.9 mm/m). A
drain connector shall be gastight and no
longer than necessary to make the
connection between the M/H outlet and the
drain inlet on the lot. A flexible connector
may be used at the lot drainage inlet area
only. Each lot drainage inlet shall be capped
gastight when not in use.
Parte
M/H Park Water Supply
E 13 General Requirements.
An accessible and adequate supply of potable water
shall be provided in each M/H park. Where a public
supply of water of satisfactory quantity, quality, and
pressure is available at or within the boundary of the
park site, connection shall be made thereto and its
supply used exclusively. When a satisfactory public
water supply is not available, a private water supply
system shall be developed and used as approved by
the Authority Having Jurisdiction.
E 14 Lot Service Outlet Size.
Each M/H lot shall be provided with a water service
outlet delivering potable water. The water service
outlet riser shall be not less than three-fourths (3/4)
inch (19.1 mm) nominal pipe size and capable of
delivering twelve (12) water supply fixture units.
E 15 Location of Water Service.
Each lot water service outlet shall be located in the
rear third section and within four (4) feet (1,219 mm)
of the proposed location of the M/H.
E 16 Pressure.
Each M/H park water distribution system shall be so
designed and maintained as to provide a pressure of
not less than tw^enty (20) pounds per square inch
(138 kPa) at each M/H lot at maximum operating
conditions.
E 17 Water Distribution Piping.
Park water distribution systems shall be designed to
deliver a minimum of twelve (12) water supply fixture
units to each lot and installed with materials as set
forth in Chapter 6 and /or Appendix A of this code.
E18 Shutoff Valve.
A separate water shutoff valve shall be installed in
each water service outlet at each M/H lot. Where a
listed backflow protective device is installed, the
service shutoff shall be located on the supply side of
such device.
E19 Backflow Preventer.
Whenever a condition exists in the plumbing of a
M/H that may create a cross-connection, a listed
backflow preventer shall be installed in the water
service line to the M/H at or near the water service
outlet. When a hose bibb or outlet is installed on the
supply outlet riser in addition to the service
connector, a listed backflow preventer shall be
installed on each additional outlet.
E20 Pressure-Relief Valve.
Whenever it is required to install a backflow
preventer at the M/H lot service outlet, a listed
pressure-relief valve shall be installed in the water
service line on the discharge side of the backflow
preventer. Pressure-relief valves shall be set to
release at a pressure not to exceed one hundred fifty
(150) pounds per square inch (1,034 kPa). Pressure-
relief valves shall discharge toward the ground.
Backflow preventers and pressure-relief valves shall
be at least twelve (12) inches (305 mm) above the
ground.
E 21 Mechanical Protection.
All park water service outlets, backflow preventers,
and pressure-relief valves shall be protected from
damage by vehicles or other causes. Such protection
may consist of posts, fencing, or other permanent
barriers.
E22 M/H Water Connector.
An M/H shall be connected to the park water service
outlet by a flexible connector, such as copper tubing
or other approved material not less than three
quarter (3/4) inch nominal (19.1 mm) interior
diameter.
E 23 Water-Conditioning Equipment.
(A) Permit Required. A permit shall be
obtained from the Authority Having
Jurisdiction prior to installing any water-
conditioning equipment on an M/H lot.
Approval of the park operator is required on
all applications for a permit to install such
equipment. If the water-conditioning
equipment is of the regenerating type, and
the park drainage system discharges into a
public sewer, approval of the sanitary
district or agency having jurisdiction over
the public sewer is required.
(B) Approval. Regenerating water-conditioning
equipment shall be listed and labeled by an
approved listing agency.
(C) Installation. Regenerating units shall
discharge the effluent of regeneration into a
trap not less than one and one-half (1-1/2)
inches (38 mm) in diameter connected to the
M/H park drainage system. An approved
air gap shall be installed on the discharge
line a minimum of twelve (12) inches (305
mm) above the ground.
307
Appendix E
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
E 24 Testing.
Installations shall be tested and inspected as
required by Chapter 3 of this code.
PartD
Fuel Supply
E 25 General.
All fuel gas piping systems serving manufactured
homes, accessory buildings, or structures and
communities shall be designed and constructed in
accordance with any applicable provisions of NFPA 54,
National Fuel Gas Code, and NFPA 58, Liquefied Petroleum
Gas Code. NFPA 31, Standard for the Installation of Oil-
Burning Equipment, shall apply to oil fuel-burning
systems and shall conform to the criteria of the
Authority Having Jurisdiction. [NFPA 501A: 4.1.1]
E 25.1 Gas Supply Connections.
Gas supply connections at sites, where provided
from an underground gas supply piping system,
shall be located and arranged to permit
attachment to a M/H occupying the site in a
work-like manner. For the installation of
liquefied petroleum gas (LPG) storage systems,
the applicable provisions of NFPA 58, Liquefied
Petroleum Gas Code, shall be followed. [NFPA
501A: 4.1.2.1, 4.1.2.2]
E 25.2 Location of Gas Supply Connection.
The gas supply to the M/H shall be located
within 4 feet (1.22 m) of the M/H stand.
Exception: The above requirements shall not
apply to gas supply connections for
manufactured homes located on all-weather
wood, concrete, or concrete block foundation
systems or on foundations constructed in
accordance with the local Building Code or, in
the absence of a local code, with a recognized
model building code. [NFPA 501A: 4.1.3]
E 26 Single and Multiple Manufactured Home Site
Fuel Supply Systems.
E 26.1 Gas Piping Installations.
E 26.1.1 Gas Supply Connections -
Underground Gas Piping.
Gas supply connections at sites, where
provided from an imderground gas supply
piping system, shall be located and arranged
to permit attachment in a work-like maimer
to a manufactured home occupying the site.
For the installation of LPG storage systems,
the provisions of NFPA 58, Liquefied
Petroleum Gas Code, shall be followed.
E 26.1.2 Underground gas piping system
installations shall comply with any
308
applicable Building Code and Sections E
26.1.2.1 and E 26.1.2.2. [NFPA 501A: 4.2.1]
E 26.1.2.1 Underground gas piping shall
not be installed beneath that portion of an
M/H site reserved for the location of a
manufactured home or M/H accessory
building or structure unless installed in the
open-ended gastight conduit of Section E
26.1.2.2. [NFPA 501A: 4.2.1.1]
E 26.1.2.2 The open-ended gastight conduit
shall conform to the following: [NFPA 501A:
4.2.1.2]
(1) The conduit shall be not less than
Schedule 40 pipe that is approved for
underground installation beneath
buildings. [NFPA 501A: 4.2.1.2(a)]
(2) The interior diameter of the conduit
shall be not less than 0.5 inches (12.7
mm) larger than the outside diameter of
the gas piping. [NFPA 501 A: 4.2.1.2(b)]
(3) The conduit shall extend to a point not
less than 4 inches (102 mm) beyond the
outside wall of the M/H, accessory
building, or structure, and the outer
ends shall not be sealed. [NFPA 501 A:
4.2.1.2(c)]
(4) Where the conduit terminates within a
M/H, accessory building, or structure, it
shall be readily accessible, and the space
between the conduit and the gas piping
shall be sealed to prevent leakage of gas
into the building. [NFPA 501A: 4.2.1.2(d)]
E 27 Manufactured Home Site Gas Shutoff Valve.
Each M/H site shall have a listed gas shutoff valve
installed upstream^ of the M/H site gas outlet. The
gas shutoff valve shall be located on the outlet riser
at a height of not less than 6 inches (152 mm) above
grade. A gas shutoff valve shall not be located under
any M/H. The outlet shall be equipped with a cap or
plug to prevent discharge of gas whenever the M/H
site outlet is not connected to an M/H. [NFPA 501A:
4.2.2.2(a-d)]
Exception: All gas shutoff valves for
manufactured homes located on foundations
constructed in accordance with the local Building
Code or, in the absence of a local code, with a
recognized model building code.
E 28 Gas Meters.
E 28.1 Support of Meters. Where installed, gas
meters shall be adequately supported by a post
or bracket placed on a firm footing or other
means providing equivalent support and shall
not depend on the gas outlet riser for support.
[NFPA 501A: 4.2.3.1]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
MANUFACTURED/MH PARKS AND RV PARKS
Appendix E
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
E 28.2 Location of Meters. Each gas meter
shall be installed in an accessible location and
shall be provided with unions or other fittings so
that the motor is removed easily and placed in
an upright position. Meters shall not be installed
in unventilated or inaccessible locations or closer
than 3 ft (0.91 m) to sources of ignition. [NFPA
501A: 4.2.3.2]
E 28.3 Meter Shutoff Valve or Cock. All gas
meter installations shall be provided with
shutoff valves or cocks located adjacent to and
on the inlet side of the meters. In the case of a
single meter installation utilizing an LP-Gas
container, the container service valve shall be
permitted to be used in lieu of the shutoff valve
or cock. All gas meter installations shall be
provided with test tees located adjacent to and
on the outlet side of the meters. [NFPA 501A:
4.2.4]
E 29 Multiple Manufactured Home Site Fuel
Distribution and Supply Systems. [ See NFPA
501 A: Section 4.1, 4.3.11, 4.4, and 4.4.5.]
E 30 Manufactured Home Community Natural Gas
Distribution Systems. <
All underground metallic fueL piping systems shall
comply with the cathodic protection requirements of
49 CFR 191 and 192. [NFPA 501A: 4.3.1]
E 31 Manufactured Home Community LPG
Supply Systems.
Where 10 or more customers are served by one LPG
supply system, the installation of the gas supply system
shall be in accordance with 49 CFR 192, Transportation of
Natural and Other Gas by Pipeline: Minimum Federal
Safety Standards. Other liquefied petroleum gas supply
systems and the storage and handling of LPG shall be
in accordance with NFPA 58, Liquefied Petroleum Gas
Code. [NFP A 501A-A3.2]
E 32 Installation of Cathodic Protection Systems.
Where required by the federal standard cited in
NFPA 501 A Section 2.3.1, cathodic protection shall
be installed for corrosion control of buried or
submerged metallic gas piping. [See also NFPA
501 A: Section 4.3.6.1 and 4.3.6.2] [NFPA 501 A: 4,3.3]
E 33 Required Gas Supply.
The minimum hourly volume of gas required at each
M/H site outlet or any section of the M/H
community gas piping system shall be calculated as
shown in Table E 3. [NFPA 501A: 4.3.4.1
E 34 Gas Pipe Sizing and Pressure.
E 34.1 The size of each section of a gas piping
system shall be determined in accordance with
NFPA 54, National Fuel Gas Code, or by other
standard engineering methods acceptable to the
Authority Having Jurisdiction. [NFPA 501A:
4.3.5.1]
E 34.2 Where all connected appliances are
operated at their rated capacity, the supply
pressure shall be not less than 4 ounces per square
inch [7 in. water column (1,743 Pa)]. The gas
supply pressure shall not exceed 8 ounces per
square inch [14 in. water column (3,486 Pa)].
[NFPA 501A: 4.3.5.2]
E 35 Gas Piping Materials.
E 35.1 Metal. Metal gas pipe shall be standard-
weight wrought iron or steel (galvanized or
black), yellow brass containing not more than 75
percent copper, or internally tinned or treated
copper of iron pipe size. Galvanizing shall not be
considered protection against corrosion.
Seamless copper or steel tubing shall be
permitted to be used with gases not corrosive to
such material. Steel tubing shall comply with
ASTM A 539, Standard Specification for Electric-
Resistance-Welded Coiled Steel Tubirig for Gas and
Fuel Oil Lines, or ASTM A 254, Standard
Specification for Copper-Brazed Steel Tubing.
Copper tubing shalL comply with ASTM B 88,
Specification for Seamless Copper Water Tubing
(Type K or Type L), or ASTM B 280, Specification
for Seamless Copper Tubing for Air Conditioning
and Refrigeration Field Service. Copper tubing
(unless tin-lined) shall not be used if the gas
contains more than an average of 0.3 grains of
hydrogen sulfide per 100 standard feef of gas.
[NFPA 501A: 4.3.6.1]
TABLE E-3
Demand Factors for Use in Calculating Gas
Piping Systems in M/H Communities
No. of
Btu/h per
Manufactured
Manufactured
Home
HomeSite
Sites
1
125,000
2
117,00,0
3
104,000
4
96,000
5
92,000
6
87,000 •
7
83,000
8
81,000
9
79,000
10
77,000
11-20
66,000
21-30
62,000
31^0
58,000
41-60
55,000
Over 60
50,000
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
Note:
In extreme climate areas, additional capacities shall be
considered.
309
Appendix E
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
E 35.2 Protection Coatings for Metal Gas
Piping. All buried or submerged metallic gas
piping shall be protected from corrosion by
approved coatings or wrapping materials. All gas
pipe protective coatings shall be approved types,
shall be machine applied, and shall conform to
recognized standards. Field wrapping shall
provide equivalent protection and is restricted to
those short sections and fittings that are
necessarily stripped for threading or welding.
Risers shall be coated or wrapped to a point at
least 6 inches (152 mm) above ground. [NFPA
501A: 4.3.6.2]
E 35.3 Plastic. Plastic piping shall be used
underground only and shall meet the require-
ments of ASTM D 2513, Thermoplastic Gas Pressure
Pipe, Tubing, and Fittings, or ASTM D 2517,
Reinforced Epoxy Resin Gas Pressure Pipe and
Fittings, as well as the design pressure and design
limitations of 49 CFR 192.123, and shall otherwise
conform to the installation requirements thereof.
[NFPA 501A: 4.3.6.3]
E 36 Gas Piping Installations.
E 36.1 Minimum Burial Below Ground Level
and Clearances.
AU gas piping installed below ground level shall
have a nunimum earth cover of 18 inches (451 mm)
and shall be installed with at least 12 inches (305
mm) of clearance in any direction from any other
imderground utility system. [NFPA 501A: 4.3.7.1]
E 36.2 Metallic Gas Piping.
E 36.2.1 All metallic gas piping systems
shall be installed in accordance with
approved plans and specifications, including
provisions for cathodic protection. Each
cathodic protection system shall be designed
and installed to conform to the provisions of
49 CFR 192. [NFPA 501A: 4.3.7.2.1, 4.3.7.2.2]
E 36.2.2 Where the cathodic protection
system is designed to protect only the gas
piping system, the gas piping system shall be
electrically isolated from all other under-
ground metallic systems or installations.
Where only the gas piping system is
cathodically protected against corrosion, a
dielectric fitting shall be used in the M/H gas
connection to insulate the M/H from the
underground gas piping system. [NFPA
501A: 4.3.7.2.3, 4.3.7.2.4]
E 36.2.3 Where a cathodic protection system is
designed to provide all underground metallic
systems and installations with protection
against corrosion, all such systems and
installations shall be electrically bonded
together and protected as a whole. [NFPA
501A: 4.3.7.2.5]
E 36.3 Plastic Gas Piping. Plastic gas piping shall
only be used underground and shall be installed
with an electrically conductive wire for locating the
pipe. The wire used to locate the plastic pipe shall
be copper, not smaller in size than No. 18 AWG,
with insulation approved for direct burial. Every
portion of a plastic gas piping system consisting of
metallic pipe shall be cathodically protected against
corrosion. [NFPA 501A: 4.3.7.3]
E 36.4 Gas Piping System Shutoff Valve. A
readily accessible and identifiable shutoff valve
controlling the flow of gas to the entire M/H
community gas piping system shall be installed
near the point of connection to the service piping
or to the supply connection of an LPG container.
[NFPA 501A: 4.3.7.4]
E 37 Liquefied Petroleum Gas Equipment.
LPG equipment shall be installed in accordance
with the applicable provisions of NFPA 58,
Liquefied Petroleum Gas Code. [NFPA 501A: 4.3.8]
E 38 Oil Supply.
The following three methods of supplying oil to an
individual M/H site shall be permitted:
(1) Supply from an outside underground tank (see
Section 2.4.6)
(2) Supply from a centralized oil distribution
system designed and installed in accordance
with accepted engineering practices and in
compliance with NFPA 31, Standard for the
Installation of Oil-Burning Equipment
(3) Supply from an outside aboveground tank (see
Section 2.4.6) [NFPA 501 A: 4.3.9]
E 38.1 Minimum Oil Supply Tank Size. Oil
supply tanks shall have a minimum capacity
equal to 20 percent of the average annual oil
consumption. [NFPA 501A: 4.3.10]
E 38.2 Oil Supply Connections - General. Oil
supply connections at M/H stands, where
provided from a centralized oil distribution
system, shall be located and arranged to permit
attachment in a work-like manner to a
manufactured home utilizing the stand. The
installation of such facilities shall meet the
provisions of NFPA 31, Standard for the Installation
of Oil-Burning Equipment, and particularly Section
3.8 thereof. [NFPA 501A: 4.3.11]
E 39 Fuel Supply Systems Installation.
E 39.1 Flexible Gas Connector. Each gas
supply connector shall be listed for outside M/H
use, shall be not more than 6 ft (1.83 m) in
length, and shall have a capacity rating adequate
to supply the connected load. [NFPA 501A: 4.4.1]
Exception: All gas supply connections for
manufactured homes located on an all-
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
310
MANUFACTURED/MH PARKS AND RV PARKS
Appendix E
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
weather wood, concrete, or concrete block
foundation system or on a foundation
constructed in accordance with the local
Building Code or, in the absence of a local
code, with a recognized model building code.
E 39.2 Use of Approved Pipe and Fittings of
Extension. Where it is necessary to extend the
M/H inlet to permit connection of the 6 foot
(1.83 m) listed connector to the site gas outlet,
the extension shall be of approved materials of
the same size as the M/H inlet and shall be
adequately supported at no more than 4 foot
(1.22 m) intervals to the M/H. [NFPA 501 A: 4.4.2]
E 39.3 Meclianical Protection. All gas outlet
risers, regulators, meters, valves, or other
exposed equipment shall be protected against
accidental damage. [NFPA 501 A: 4.4.3]
E 39.4 Special Rules on Atmospherically
Controlled Regulators. Atmospherically
controlled regulators shall be installed in such a
manner that moisture cannot enter the regulator
vent and accumulate above the diaphragm. Where
the regulator vent is obstructed due to snow and
icing conditions, shields, hoods, or other suitable
devices shall be provided to guard against closing
of the vent opening. [NFPA 501A: 4.4.4]
E 39.5 Fuel Gas Piping Test. The M/H fuel
gas piping system shall be tested only with air
before it is connected to the gas supply. The
M/H gas piping system shall be subjected to a
pressure test with all appliance shutoff valves in
their closed positions. [NFPA 501A: 4.4.5]
E 39.5.1 The fuel gas piping test shall
consist of air pressure at not less than 10-
inch water column or more than 14 inch
water column [6 oz./in.^ to 8 oz./in.^ (2,490
Pa to 3,486 Pa)]. The system shall be isolated
from the air pressure source and shall
maintain this pressure for 10 minutes or
more without perceptible leakage. Upon
satisfactory completion of the test, the
appliance valves shall be opened, and the
gas appliance connectors shall be tested
with soapy water or bubble solution while
under the pressure remaining in the piping
system. Solutions used for testing for
leakage shall not contain corrosive
chemicals. Pressure shall be measured with
either a manometer, slope gauge, or gauge
that is calibrated in either water inch or psi,
with increments of either 1/10 inch (2.5 mm)
or 1/10 psi (0.6 kPa gauge), as applicable.
Upon satisfactory completion of the test, the
M/H gas supply connector shall be
installed, and the connections shall be tested
with soapy water or bubble solution. [NFPA
501A: 4.4.5.1.1-4.4.5.1.6]
WARNING
Do not overpressurize the fuel gas piping system.
Damage to valves, regulators, and appliances can
occur due to pressurization beyond the maximums
specified. [NFPA 501A: 4.4.5.2]
E 39.5.2 Gas appliance vents shall be
visually inspected to ensure that they have
not been dislodged in transit and are
connected securely to the appliance. [NFPA
501A: 4.4.5.3]
E 39.6 Oil Tanks.
No more than one 660 gallon (2,500 L) tank or
two tanks with aggregate capacity of 660 gallon
(2,500 L) or less shall be comiected to one oil-
burning appliance. Two supply tanks, where
used, shall be cross-connected and provided
with a single fill and single vent as described in
NFPA 31/ Standard for the Installation of Oil-
Burning Equipment, and shall be on a common
slab and rigidly secured one to the other. Tanks
having a capacity of 660 gallon (2,500 L) or less
shall be securely supported by rigid,
noncombustible supports to prevent settling,
sliding, or lifting. [NFPA 501A: 4.4.6]
E 39.6.1 Oil supply tanks shall be installed
in accordance with the applicable provisions
of NFPA 31, Standard for the Installation of
Oil-Burning Equipment. [NFPA 501A: 4.4.6.1]
E 39.6.2 A tank with a capacity no larger
than 60 gallon (230 L) shall be permitted to
be a DOT-5 shipping container (drum) and
so marked, or a tank meeting the provisions
of UL 80, Steel Inside Tank for Oil Burner Fuel.
Tanks other than DOT-5 shipping containers
having a capacity of not more than 660
gallon (2,500 L) shall meet the provisions of
UL 80. Pressure tanks shall be built in
accordance with Section VIII, Pressure
Vessels, ASME Boiler, and Pressure Vessel
Code. [NFPA 501A: 4.4.6.2.1-4.4.6.2.2]
E 39.6.3 Tanks, as described in Sections 2.4.6
and 2.4.6.2, that are adjacent to buildings
shall be located not less than 10 feet (3.05 m)
from a property line that is permitted to be
built upon. [NFPA 501 A: 4.4.6.3]
E 39.6.4 Tanks with a capacity no larger
than 660 gallon (2,500 L) shall be equipped
with an open vent no smaller than 1.5-inch
(38 mm) iron pipe size; tanks with a 500
gallon (1900 L) or less capacity shall have a
vent of 1.25-inch (32 mm) iron pipe size.
' [NFPA 501A: 4.4.6.4]
E 39.6.5 Tanks shall be provided with a
means of determining the liquid level.
[NFPA 501A: 4.4.6.5]
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
311
Appendix E
UNIFORM PLUMBING CODE
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
E 39.6.6 The fill opening shall be a size and
in a location that permits ready filling
without spillage. [NFPA 501A: 4.4.6.6]
E 40 Manufactured Home Accessory Building
Fuel Supply Systems.
Fuel gas supply systems installed in a M/H accessory
building or structure shall comply with the applicable
provisions of NFPA 54, National Fuel Gas Code, and
NFPA 58, Liquefied Petroleum Gas Code. Fuel oil supply
systems shall comply with the applicable provisions
of NFPA 31, Standard for the Installation of Oil-Burning
Equipment.[N¥FA 501 A: 4.5]
E 41 Community Building Fuel Supply Systems
in Manufactured Home Communities.
E 41.1 Fuel Gas Piping and Equipment
Installations.
Fuel gas piping and equipment installed within a
permanent building in a M/H community shall
comply with nationally recognized appliance and
fuel gas piping codes and standards adopted by
the Authority Having Jurisdiction. Where the state
or other political subdivision does not assume
jurisdiction, such fuel gas piping and equipment
installations shall be designed and installed in
accordance with the appropriate provisions of
NFPA 54, National Fuel. Gas Code, or NFPA 58,
Liquefied Petroleum Gas Code. [NFPA 501A: 4.6.1]
E 41.2 Oil Supply Systems in M/H
Communities.
Oil-burning equipment and installation within a
M/H community shall be designed and
constructed in accordance with the applicable
codes and standards adopted by the Authority
Having Jurisdiction. Where the state or other
political subdivision does not assume jurisdiction,
such installation shall be designed and
constructed in accordance with the applicable
provisions of NFPA 31, Standard for the Installation
of Oil-Burning Equipment. [NFPA 501 A: 4.6.2]
E 41.3 Oil-Burning Equipment and
Installation.
Oil-burrung equipment and installation within a
building constructed in a M/H community in
accordance with the local Building Code or a
nationally recognized building code shall
comply with nationally recognized codes and
standards adopted by the Authority Having
Jurisdiction. Where the state or other political
subdivision does not assume jurisdiction, such
oil-burning equipment and installation shall be
designed and installed in accordance with the
appropriate provisions of NFPA 31, Standard for
the Installation of Oil-Burning Equipment. [NFPA
501A: 4.6.3]
312
E 41 .4 Inspections and Tests.
Inspections and tests for fuel gas piping shall be
made in accordance with Chapters 1 and 12 of
this Code.
PartE
Recreational Vehicle Parks Definitions and
General Requirements
E 42 Recreational Vehicle (RV).
A vehicular-type unit primarily designed as
temporary living quarters for recreational, camping,
travel, or seasonal use, that either has its own motive
power, or is mounted on or towed by another
vehicle. The basic entities are camping trailer, fifth-
wheel trailer, motor home, park trailer, travel trailer,
and truck camper.
E 43 Recreational Vehicle Park.
A plot of land upon which two (2) or more
recreational vehicle sites are located, established, or
maintained for occupancy by recreational vehicles of
. the general public as temporary living quarters for
recreation or vacation purpose.
E 44 Recreational Vehicle Site.
Within a recreational vehicle park, a plot of ground
intended for the accommodation of a recreational
vehicle, a tent, or other individual camping unit on a
temporary basis.
E45 General.
All plumbing shall be installed in accordance with
the plumbing codes of the Authority Having
Jurisdiction and with this appendix.
PartF
Recreational Vehicle Park Toilet and Shower
Facilities
E 46 Toilets and urinals shall be provided at one (1)
or more locations in every recreational vehicle park.
They shall be convenient of access and shall be
located within a five hundred (500) foot (152.4 m)
radius from any recreational vehicle site not
provided with an individual sewer connection.
E 47 Facilities for males and females shall be
appropriately marked.
E 48 A minimum of one (1) toilet shall be provided
for each sex up to the first twenty-five (25) sites. For
each additional twenty-five (25) sites not provided
with sewer connections, an additional toilet shall be
provided.
E 49 The interior finish of walls shall be moisture
resistant to a height of four (4) feet (1,219 mm) to
facilitate washing and cleaning.
MANUFACTURED/MH PARKS AND RV PARKS
Appendix E
E 50 The floors shall be constructed of material
impervious to water and shall be easily cleanable.
Any building having water-flush toilets shall be
provided with a floor drain in the toilet room. This
drain shall be provided with mieans to protect the
trap seal as required by this code.
E 51 If water-flush toilets are provided, an equal
number of lavatories shall be provided for up to six
(6) toilets. One additional lavatory shall be provided
for each two (2) toilets when more than six (6) toilets
are required. Each lavatory basin shall have a piped
supply of potable water and shall drain into the
drainage system.
E 52 If separate facilities are provided for men and
women, urinals shall be acceptable for no more than
one-third (1/3) of the toilets required in the men's
facilities, except that one (1) urinal may be used to
replace a toilet in a minimum park. Only individual
stall or wall-hung types of urinals shall be installed.
Floor-type trough units shall be prohibited.
E 53 Toilets shall be of an approved, elongated bowl
type and shall be provided with seats with open fronts.
E 54 Each toilet shall be in a separate compartment
and be provided with a door with a latch for privacy
and a holder or dispenser for toilet paper. Dividing
walls or partitions shall be at least five (5) feet (1,524
mm) high and shall be separated from the floor by a
space not greater than twelve (12) inches (305 mm).
E 55 Toilet compartments shall be not less than
thirty (30) inches (762 mm) in width (no toilet shall
be set closer than fifteen (15) inches (381 mm) from
its center to a side wall) and there shall be not less
than thirty (30) inches (762 mn\) of clear space in
front of each toilet.
E 56 Each toilet room for women shall be provided
with a receptacle for sanitary napkins. The receptacle
shall be of durable, impervious, and readily
cleanable material, and shall be provided with a lid.
E 57 Each shower, if provided, shall have a floor
area of thirty-six (36) inches by thirty-six (36) inches
(914 mm x 914 mm) and shall be capable of
encompassing a thirty (30) inch (762 mm) diameter
circle and shall be of the individual type, and each
shower area shall be visually screened from view,
with a minimum floor area of thirty-six (36) by
thirty-six (36) inches (914 mm x 914 mm) per shower.
Each shall be provided with individual dressing
areas screened from view and shall contain a
minimum of one (1) clothing hook and stool (or
equivalent bench area).
E 58 Each shower area shall be designed to
minimize the flow of water into the dressing area
and shall be connected to the drainage system by
means of a properly vented and trapped inlet. Each
such area shall have an impervious, skid-resistant
surface; wooden racks (duck boards) over shower
floors shall be prohibited.
E 59 Every toilet building shall have a minimum
ceiling height of seven (7) feet (2,134 mm) and,
unless artificial light is provided, a window or
skylight area equal to at least ten (10) percent of the
floor area shall be provided.
All doors to the exterior shall open outward,
be self-closing, and shall be visually screened by
means of a vestibule or wall to prevent direct view
of the interior when the exterior doors are open.
Such screening shall not be required on single
toilet units.
E 60 Every toilet room shall have permanent, non-
closable, screened opening(s), having a total area not
less than five (5) percent of the floor area and
opening directly to the exterior in order to provide
proper ventilation. Listed exhaust fan(s), vented to
the exterior, the rating of which in cubic feet per
minute is at least twenty-five (25) percent of the total
volume of the room(s) served, shall be considered as
meeting the requirements of this subsection. All
openable windows and vents to the outside shall be
provided with fly-proof screens of not less than
number sixteen (16) mesh.
PartG
Recreational Vehicle Park Potable Water Supply
and Distribution
E61 Quality.
The supply or supplies of water shall comply with
the appropriate potable water standards of the state
or local health authority or, in the absence thereof,
with the Drinking Water Standard of the Federal
Environniental Protection Agency. (See 42 CFR Part
72, subpart J.)
E62 Sources.
Only water approved by a regulating agency shall be
acceptable. Where an approved public water supply
system is available, it shall be used. Where the park
has its own water supply system, the components of
the system shall be approved. A water supply
system that is used on a seasonal basis shall be
provided with means for draining.
E 63 Prohibited Connections.
The potable water supply shall not be connected to
any nonpotable or unapproved water supply, nor be
subjected to any backflow or back-siphonage.
E64 Supply.
The water supply system shall be designed and
constructed in accordance with the following:
313
Appendix E
UNIFORM PLUMBING CODE
(A) A minimum of twenty-five (25) gallons (94.6
L) per day per site for sites without
individual water connections.
(B) A minimum of fifty (50) gallons (189.3 L) per
day per site for sites with individual water
connections.
(C) A minimum of fifty (50) gallons (189.3 L) per
day per site if water-flush toilets are
provided in rest rooms.
E 65 Pressure and Volume.
Where water is distributed under pressure to any
individual site, the water supply system shall be
designed to provide a minimum flow pressure of
twenty (20) pounds per square inch (137.8 kPa) with
a minimum flow of two (2) gallons (7.6 L) per minute
at any outlet. The maximum pressure shall not
exceed eighty (80) pounds per square inch (551 kPa).
E66 Outlets.
Water outlets shall be convenient to access and,
when not piped to individual RV sites, shall not be
located farther than three hundred (300) feet (91.4 m)
from any site. Provisions shall be made to prevent
accumulation of standing water or the creation of
muddy conditions at each water outlet.
E67 Storage Tanks.
Water storage tanks shall be constructed of
impervious materials, protected against contami-
nation, and provided with locked, watertight covers.
Any overflow or ventilation openings shall be down-
facing and provided with corrosion-resistant
screening of not less than number twenty-four (24)
mesh to prevent the entrance of insects and vermin.
Water storage tanks shall not have direct connections
to sewers.
E 70 Drinking Fountains.
If provided, drinking fountains shall be in
conformance with the requirements of this code.
Parti
Recreational Vehicle Park Drainage System
E 71 An adequate and approved drainage system
shall be provided in all RV parks for conveying and
disposing of all sewage. Where available, parks shall
be connected to a public sewer system.
E72 Material.
Pipe and fittings installed in the drainage system
shall be of material listed, approved, and installed
per this code.
E 73 The nunimum diameters of drainage laterals,
branches, and mains serving RV sites shall be in
accordance with the following table:
Table E-4
Maximum Number of
Recreational Vehicle
Stands Served
Minimum Pipe Sizes
Inches (ID) Nominal (mm)
o
O
/u
36
4
102
71
5
127
120
6
152
440
8
203
E 74 The sewer lines shall be located to prevent
damage from vehicular traffic.
E 75 Cleanouts shall be provided per Chapter 7 of
this code.
PartH
Recreational Vehicle Park Water Connections
for Individual Recreational Vehicles
E 68 When provided, the water connections for
potable water to individual recreational vehicle sites
shall be located on the left rear half of the site (left side
of RV) within four (4) feet (1,219 rrun) of the stand.
E 69 Each potable water connection shall consist of
a water riser pipe that shall be equipped with a
threaded male spigot located at least twelve (12)
inches (305 mm) but not more than twenty-four (24)
inches (610 mm) above grade level for the
attachment of a standard water hose. The water riser
pipe shall be protected from physical damage per
this code. Tliis connection shall be equipped with a
listed anti-siphon backflow prevention device.
314
Part J
Recreational Vehicle Site Drainage System Inlet
E 76 When provided, the site drainage system inlet
connections for individual RVs shall be located so as to
prevent damage by the parking of RVs or automobiles
and shall consist of a sewer riser extending vertically
to grade. The minimum diameter of the sewer riser
pipe shall be three (3) inches (76 mm), and it shall be
provided with a four (4) inch (102 mm) inlet or a
minimum three (3) inch (76 mm) female fitting.
E 77 When provided, the sewer inlet to individual RV
sites shall be located on the left rear half of the site (left side
of the RV) within four (4) feet (1,219 mm) of the stand.
E 78 The sewer riser pipe shall be firmly imbedded
in the ground and protected against damage from
movement. It shall be provided with a tight-fitting
plug or cap, which shall be secured by a durable
chain (or equivalent) to prevent loss.
MANUFACTURED/MH PARKS AND RV PARKS
Appendix E
PartK
Recreational Vehicle Park Sanitary Disposal
Stations
E 79 One (1) RV sanitary disposal station shall be
provided for each one hundred (100) RV sites, or
part thereof, which are not equipped with individual
drainage system connections.
E 80 Each station shall be level and convenient of
access from the service road and shall provide easy
ingress and egress for recreational vehicles.
E 81 Construction.
Unless other approved means are used, each station
shall have a concrete slab with the drainage system
inlet located so as to be on the road (left) side of the
recreational vehicle. The slab shall be not less than
three (3) feet by three (3) feet (914 mm x 914 mm), at
least three and one-half (3-1/2) inches (89 mm) thick
and properly reinforced. The slab surface is to be
troweled to a smooth finish and sloped from each
side inward to a drainage system inlet.
The drainage system inlet shall consist of a four
(4) inch (102 mm) self-closing, foot-operated hatch of
approved material with the cover milled to fit tight.
The hatch body shall be set in the concrete of the slab
with the lip of the opening flush with its surface to
facilitate the cleansing of the slab with water. The
hatch shall be properly connected to a drainage
system inlet, which shall discharge to an approved
sanitary sewage disposal facility.
E 82 Where the recreational vehicle park is
provided with a piped water supply system, means
for flushing the recreational vehicle holding tank and
the sanitary disposal station slab shall be provided
and shall consist of a piped supply of water under
pressure, terminating in an outlet located and
installed so as to prevent damage by automobiles or
recreational vehicles. The flushing device shall
consist of a properly supported riser terminating at
least two (2) feet (610 mm) above the ground surface,
with a three-fourth (3/4) inch (19.1 mm) valved
outlet adaptable for a flexible hose.
The water supply to the flushing device shall be
protected from backflow by means of a listed
vacuum breaker or backflow prevention device
located downstream from the last shutoff valve.
Adjacent to the flushing arrangement shall be
posted a sign of durable material not less than two
(2) feet by two (2) feet (610 mm x 610 mm) in size.
Inscribed thereon in clearly legible letters shall be the
following:
DANGER - NOT TO BE USED FOR DRINKING OR
DOMESTIC PURPOSES.
PartL
Recreational Vehicle Park Water Supply Stations
E 83 A potable watering station, if provided for
filling recreational vehicle potable water tanks, shall
be located at least fifty (50) feet (15,240 mm) from a
sanitary disposal station. When such is provided,
adjacent to the potable water outlet shall be posted a
sign of durable material not less than two (2) feet by
two (2) feet (610 mm by 610 mm) in size. Inscribed
thereon in clear legible letters on a contrasting
background shall be: POTABLE WATER. NOT TO
BE USED FOR FLUSHING WASTE TANKS. The
potable water shall be protected from backflow by
means of a listed vacuum breaker located
downstream from the last shutoff valve.
PartM
Recreational Vehicle Park Fuel Gas Equipment
and Installations
E 84 All fuel gas equipment and installations shall
comply with Part D of this appendix, except as
otherwise permitted or required b^/^ this code.
315
Appendix E UNIFORM PLUMBING CODE
316
APPENDIX F
FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
NFPA
F 1 Scope.
This chapter covers minimum requirements for
installation of firefighter breathing air replenishment
systems.
F 2 Definitions.
For purposes of this chapter, the following
definitions shall apply:
High-Rise Building. Buildings greater than 75 feet
in height where the building height is measured
from the lowest level of fire department vehicle
access to the floor of the highest occupiable story.
[NFPA 5000: 3.3.58.9]
Interior Cylinder Fill Panels. Lockable interior
panels that provide firefighters the ability to regulate
breathing air pressure and refill SCBA cylinders.
Interior Cylinder Fill Stations and Enclosures. Free-
standing fill containment stations that provide
firefighters the ability to regulate breathing air
pressure and refill SCBA cylinders.
Self-Contained Breathing Apparatus (SCBA). An
atmosphere-supplying respirator that supplies a
respirable air atmosphere to the user from a
breathing source that is independent of the ambient
environment and designed to be carried by the user.
[NFPA 1981: 3.3.38]
F 3 System Components.
Firefighter breathing air replenishment systems shall
contain, as a minimum, the following components.
(A) Exterior Fire Department Connection Panel
(B) Interior Fire Department Air FiU Panel or Station
(C) Interconnected Piping Distribution System
(D) Pressure Monitoring Switch
F 4 Required Installations.
A firefighter air system shall be installed in the
following buildings:
F 4.1 High-rise buildings.
F 4,2 Undergroimd structures that are three or more
floors below grade with an area greater than 20,000
square feet.
F 4.3 Large area structures with an area greater than
200,000 square feet and where the travel distance from
the building centerline to the closest exit is greater
than 500 feet, such as warehouses, manufacturing
complexes, malls, or convention centers.
F 4.4 Underground transportation or pedestrian
tunnels exceeding 500 feet in length.
F 5 Exterior Fire Department Connection Panel
and Enclosure.
F 5.1 Purpose. The exterior fire department
connection panel shall provide the fire department's
mobile air operator access to the system and shall be
compatible with the fire department's mobile air
unit.
F 5.2 Number of Panels. Each building or structure
shall have a minimum of two panels.
F 5.3 Location. Each panel shall be attached to the
building or on a remote monument at the exterior of
the building with a minimum of six (6) foot radius
and 180-degree clear unobstructed access to the front
of the panel. The panel shall be weather-resistant or
secured inside of a weather-resistant enclosure. The
panel shall be located on opposite sides of the
building within 50 feet of an approved roadway or
driveway, or other locations approved by the
Authority Having Jurisdiction.
F 5.4 Construction. The fire department connection
panel shall be installed in a metal cabinet cor\structed
of minimum 18-gauge carbon steel or equivalent. The
cabinet shall be provided with a coating or other
means to protect the cabinet from corrosion.
F 5.5 Vehicle Protection. Where the panel is located
in an area subject to vehicle traffic, impact protection
shall be provided.
F 5.6 Enclosure Marking. The front of the enclosure
shall be marked "FIREFIGHTER AIR SYSTEM". The
lettering shall be in a color that contrasts with the
enclosure front and in letters that are a nvinimum of 2
inches high with 3/8-inch brush stroke.
F 5.7 Enclosure Components. The exterior fire
department connection panel shall contain all of the
necessary gauges, isolation valves, pressure-relief
valves, pressure-regulating valves, check valves,
tubing, fittings, supports, connectors, adapters, and
other necessary components as may be required to
allow the fire department's mobile air unit to cormect
and augment the system with a constant source of
317
Appendix F
UNIFORM PLUMBING CODE
breathing air. Each fire department connection panel
shall contain at least two inlet air connections.
F 5.8 Pressure-Relief Valve. Pressure-relief valves
shall be installed downstream of the pressure
regulator inlet. The relief valve shall meet the
requirements of the CGA S-1.3 and shall not be field
adjustable. The relief valve shall have a set-to-open
pressure not exceeding 1.1 times the design pressure
of the system. Pressure-relief valve discharge shall
terminate so that the exhaust air stream cannot
impinge upon personnel in the area. Valves, plugs or
caps shall not be installed in the discharge of a
pressure-relief valve. Where discharge piping is
used, the end shall not be threaded.
F 5.9 Security. The fire department connection panel
enclosure shall be locked by an approved means.
F 6 Interior Cylinder Fill Panels.
F 6.1 Cabinet Requirements. Each cylinder fill panel
shall be installed in a metal cabinet constructed of
minimum 18-gauge carbon steel or equivalent. The
depth of the cabinet shall not create an exit
obstruction when installed in building stairwells.
With the exception of the shutoff valve, pressure
gauges, fill hoses, and ancillary components, no
system components shall be visible and shall be
contained behind a minimum 18-gauge interior panel.
F 6.2 Clearance and Access. The panel shall be
located a minimum of 36 inches but not more than 60
inches above the finished floor or a stairway landing.
Clear unobstructed access shall be provided to each
panel.
F 6.3 Door. The door shall be arranged such that
when the door is open, it does not reduce the
required exit width or create an obstruction in the
path of egress.
F 6.4 Cabinet Marking. The front of each cylinder fill
panel shall be marked "FIREFIGHTER AIR SYSTEM".
The lettering shall be in a color that contrasts with the
cabinet front and in letters that are a minimum of 2-
inches high with 3/8-inch brush stroke.
F 6.5 Cabinet Components. The cabinet shall be of
sufficient size to allow for the installation of the
following components:
F 6.5.1 The cylinder fill panel shall contain all of
the gauges, isolation valves, pressure-relief valves,
pressure-regulating valves, check valves, tubing,
fittings, supports, connectors, hoses, adapters, and
other components to refill SCBA cylinders.
F 6.6 Cylinder Filling Hose. The design of the
cabinet shall provide a means for storing the hose to
prevent kinking. When the hose is coiled, the
brackets shall be installed so that the hose bend
radius is maintained at 4 inches or greater. Fill hose
connectors for connection to SCBA cylinders shall
comply with the requirements of CGA V-1, number
346 or 347. No other SCBA cylinder fill connections
shall be permitted.
F 6.7 Security. Each panel cover shall be maintained
and locked by an approved means.
F 7 Interior Cylinder Fill Stations and Enclosures.
F 7.1 Location. The location of the closet or room for
each air fill station shall be approved by the
Authority Having Jurisdiction. When approved by
the Authority Having Jurisdiction, the space may be
utilized for other firefighting purposes. The door to
each room enclosing the air filling station enclosure
shall be readily accessible at all times. A minimum
of six (6) foot radius and 180-degree clear imobstruc-
ted access to the front of the air filling station shall
be provided. The enclosure shall have emergency
lighting installed in accordance with NFPA 70.
F 7.2 Security. Each air fill station shall be installed
within a lockable enclosure, closet, or room by an
approved means. Access to fill equipment and
controls shall be restricted to authorized personnel
by key or other means.
F 7.3 Components. The air fill station shall contain
all of the gauges, isolation valves, pressure-relief
valves, pressure-regulating valves, check valves,
tubing, fittings, supports, connectors, hoses, adapters,
and other components to refill SCBA cylinders.
F 7.4 Cylinder Filling Hose. Where hoses are used
the design of the cabinet shall provide a means for
storing the hose to prevent kinking. When the hose
is coiled, the brackets shall be installed so that the
hose bend radius is maintained at 4 inches or greater.
Fill hose connectors for connection to SCBA
cylinders shall comply with the requirements of
CGA V-1, number 346 or 347. For high-pressure
SCBA cylinders (4,500 psi), number 347 connectors
shall be used. For low-pressure SCBA cylinder (3,000
psi and 2,200 psi), number 346 connectors shall be
used. No other SCBA cylinder fill connections shall
be permitted.
F 7.5 Enclosure and Air Filling Station Marking.
Each enclosure, closet, or room shall be marked
FIREFIGHTERS AIR SYSTEM. The lettering shall be
in a color that contrasts with the cabinet front and in
letters that are a minimum of 2 inches high with 3/8-
inch brush stroke.
F 8.0 Materials.
All pressurized components shall be compatible for
use with high-pressure breathing air equipment and
self-contained breathing air apparatus. All
318
FIREFIGHTER BREATHING AIR
REPLENISHMENT SYSTEMS
pressurized breathing air components shall be rated
for a minimum working pressure of 5,000 PSI.
F 8.1 Tubing. Tubing shall be stainless steel
complying with ASTM A269, or other approved
materials that are compatible with breathing air at
the system pressure. Routing of tubing and bends
shall be such as to protect the tubing from
mechanical damage.
F 8.2 Fittings. Fittings shall be constructed of
stainless steel complying with ASTM A479, or other
approved materials that are compatible with
breathing air at the system pressure.
F 8.3 Prohibited Materials. The use of nonmetallic
materials, carbon steel, iron pipe, malleable iron, high-
strength gray iron, or alloy steel shall be prohibited
for breathing air pipe and tubing materials.
F 8.4 Pressure Monitoring Switch. An electric low-
pressure monitoring switch shall be installed in the
piping system to monitor the air pressure. The
pressure switch shall transmit a supervisory signal to
the central alarm monitoring station when the
pressure of the breathing air system is less than 80
percent of the system operating pressure. Activation
of the pressure switch shall also activate an audible
alarm and visual strobe located at the building
annunciator panel. A weather-resistant sign shall be
provided in conjunction with the audible alarm
stating "FIREFIGHTER AIR SYSTEM - LOW AIR
PRESSURE ALARM." Where not part of a building
annunciator panel, the lettering shall be in a
contrasting color, and the letters shall be a minimum
of 2 inches high with 3/8-inch brush stroke.
F 8.5 isolation Valve. A system isolation valve shall
be installed downstream of each air fill station and
shall be located in the panel or within 3 feet of the
station. The isolation valve shall be marked with its
function in letters that are a minimum of 3/16-inches
high with a 1/16-inch brushstroke.
F 9.0 System Requirements.
F 9.1 Protection. All components of the Firefighter
Breathing Air Replenishment System installed in a
building or structure shall be protected by a minimum
two (2) hour fire-resistive construction. All compo-
nents shall be protected from physical damage.
F 9.2 Markings. All components shall be clearly
identified by means of stainless steel or plastic labels
or tags indicating their function. This shall include as
a minimum all fire department connection panels, air
fill stations, air storage system, gauges, valves, air
connections, air outlets, enclosures, and doors.
F 9.3 Tubing Maricings. All tubing shall be clearly
marked "FIREFIGHTERS AIR SYSTEM" and "HIGH
PRESSURE BREATHING AIR" by means of signs or
Appendix F
self-adhesive labels. Signs shall be 1 inch high and
shall be secured to the tubing. Signs shall be made of
brass, stainless steel, or plastic and engraved with
3/8 inch letters with 1/16 inch stroke lettering. Signs
or labels shall be placed at a minimum of 20 foot
intervals and at each fitting, whether the tubing is
concealed or in plain view. All tubing shall have a
sign or label at any accessible point.
F 9.4 Support. Pipe and tubing shall be supported at
the minimum intervals shown in UPC Table 3-2. Pipe
and tubing shall be supported in accordance with
UPC 314.0.
F 10.0 Design Criteria.
F 10.1 Fill Time. The system shall be designed to fill,
at the most remote fill station or panel, a minimum
of two (2) 66 standard cubic foot compressed
breathing air cylinder to a maximum pressure of
4,500 PSIG simultaneously in three (3) minutes or
less. Where greater capacity is required, the
Authority Having Jurisdiction shall specify the
required system capacity.
F 10.2 Fill Panels or Stations Location. Cylinder
fill panels or stations shall be installed in the interior
of buildings as follows:
F 10.2.1 High-Rise Buildings. An interior
cylinder fill panel or station shall be installed
commencing on the third floor and every third
floor thereafter above grade. For underground
floors in buildings with more than five
underground floors, an interior cylinder fill
panel or station shall be installed commencing
on the third floor below grade and every three
floors below grade thereafter, except for the
bottom-most floor.
F 10i2.2 Underground Structures. For
underground floors in buildings with more than
five underground floors, an interior cylinder fill
panel or station shall be installed comn\encing
on the third floor below grade and every three
floors below grade thereafter, except for the
bottom-most floor.
F 10.2.3 Installation Locations. The specific
location or locations on each floor shall be
approved by the Authority Having Jurisdiction.
F 1 1 .0 System Assembly Requirements.
The system shall be an aU-welded system except where
the tubing joints are readily accessible and at the
individual air fill panels or stations. When mechanical
high-pressure tube fittings are used, they shall be
approved for the type of materials to be joined and
rated for the maximum pressure of the system.
319
Appendix F
UNIFORM PLUMBING CODE
F 11.1 Welding Requirements. Welding procedures
shall meet ASME B31.1, Part 4 and Chapter V. Prior
to and during the welding of sections of tubing, a
continuous, regulated dry nitrogen or argon purge at
three PSIG shall be maintained to eliminate
contamination with products of the oxidation or
welding flux. The purge shall commence a
minimum of 2 minutes prior to welding operations
and continue until the welded joint is at ambient
temperature.
F 11.2 Prevention of Contamination. The system
components shall not be exposed to contaminants,
including but not limited to, oils, solvents, dirt, and
construction materials. When contamination of
system components has occurred, the affected
component shall not be installed in the system.
F 12.0 System Acceptance and Certification.
F 12.1 Static Pressure Testing. Following
fabrication, assembly, and installation of the piping
distribution system, exterior connection panel, and
interior cylinder fill panels, the Authority Having
Jurisdiction shall witness the pneumatic testing of
the complete system at a minimum test pressure of
7,500 PSI using oil-free dry air, nitrogen, or argon. A
minimum twenty four (24) hour pneumatic test shall
be performed. During this test, all fittings, joints, and
system components shall be inspected for leaks. A
solution compatible with the system component
niaterials shall be used on each joint and fitting. Any
defects in the system or leaks detected shall be
documented on an inspection report, repaired or
replaced. As an alternate, a pressure-decay test in
accordance with ASME B31.3 shall be permitted.
F 12.2 Low Pressure Switch Test. Upon successful
completion of the twenty four (24) hour static
pressure test, the system's low-pressure monitoring
switch shall be calibrated to not less than 3,000 PSI
descending, and tested to verify that the signal is
annunciated at the building's main fire alarm panel
and by means of an audible alarm and visual strobe
located in a visible location.
F 12.3 Compatibility Check. Each air fill panel and
station and each exterior fire department connection
panel shall be tested for compatibility with the fire
department's SCBA fill fittings.
F 12.4 Material Certifications. The pipe or tubing
material certifications shall be provided to the
Authority Having Jurisdiction.
F 12.5 Air Sampling. Before the system is placed
into service, a minimum of two samples shall be
taken from separate air fill panels and submitted to
an independent certified gas analysis laboratory to
verify the system's cleanliness and that the air
complies with the requirements for breathing air in
accordance with NFPA 1989, section 5.3. The written
report of the analysis shall be submitted to the
Authority Having Jurisdiction, documenting that the
breathing air complies with this section.
F 12.5.1 During the period of air quality
analysis, the air fill panel inlet shall be secured
so that no air can be introduced into the system
and each air fill panel shall be provided with a
sign stating "AIR QUALITY ANALYSIS IN
PROGRESS, DO NOT FILL OR USE ANY AIR
FROM THIS SYSTEM." This sign shall be a
minimum of 8-1/2 inches by 11 inches with
minimum of 1 inch lettering.
F 12.6 Annual Air Sampling. The breathing air
within the system shall be sampled and certified
annually and inspected in accordance with the
procedure in section F12.5.
F 12.7 Final Proof Test. The Authority Having
Jurisdiction shall witness filling of two (2) empty
sixty six (66) cubic foot capacity SCBA cylinders in
three (3) minutes or less using compressed air
supplied by fire department equipment connected to
the exterior fire department connection panel. The
SCBA cylinders shall be filled at the air fill panel or
station farthest from the exterior fire departm.ent
coimection panel. Following this, a minimum of two
(2) air samples shall then be taken from separate air
filling stations and submitted to an independent
certified gas analyst laboratory to verify the system's
cleanliness and that the air m.eets the requirements of
NFPA 1989. The written report shall be provided to
the Authority Having Jurisdiction certifying that the
air analysis complies with the above requirements.
320
"The information contained in this appendix is not part of this American National Standard (ANS) and has not
been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain mate-
rial that has not been subjected to public review or a consensus process. In addition, it does not contain require-
ments necessary for conformance to the standard."
APPENDIX I
INSTALLATION STANDARDS
The following lAPMO Installation Standards are included here for the convenience of the users of the Uniform
Plumbing Code. They are not considered as a part of the Uniform Plumbing Code unless formally adopted as
such. These Installation Standards are independent, stand-alone documents published by the International
Association of Plumbing and Mechanical Officials and are printed herein by the expressed written permission
of lAPMO.
Contents
Page
IS 1-2003 Non-Metallic Building Sewers 323
IS 2-2003 Tile-Lined Roman Bathtubs 327
IS 3-2003 Copper Plumbing Tube, Pipe, and Fittings 333
IS 4-2003 Tile-Lined Shower Receptors (and Replacements) 341
IS 5-2003 ABS Building Drain, Waste, and Vent Pipe and Fittings 345
IS 6-2003 Hubless Cast Iron Sanitary and Rainwater Systems 351
IS 7-2003 Polyethylene (PE) Cold Water Building Supply 353
IS 8-2003 PVC Cold Water Building Supply and Yard Piping 355
IS 9-2003 PVC Building Drain, Waste, and Vent Pipe and Fittings 363
IS 11-2003 ABS Sewer Pipe and Fittings 369
IS 12-2003 Polyethylene (PE) for Gas Yard Piping 373
IS 13-2003 Protectively Coated Pipe 377
IS 15-2003 Asbestos Cement Pressure Pipe for Water Service and Yard Piping 379
IS 18-2003 Extra Strength Vitrified Clay Pipe in Building Drains 385
I IS 20-2005 CPVC Solvent Cemented Hot and Cold Water Distribution Systems 387
IS 21-2003 Welded Copper and Copper Alloy Water Tube 397
IS 26-2003 Trenchless Polyethylene (PE) Pipe for Sewer Laterals 405
IS 27-2003 Odor Control Systems for Water Closets 407
IS 28-2005 Composite PEX-AL-PEX Hot and PE-AL-PE Cold Water Distribution Systems 411
SIS 1-2003 Flexible PVC Hose 415
SIS 2-2003 Assembled Whirlpool Bathtub AppUances 419
321
322
Installation Standard
For
NON-METALLIC BUILDING SEWERS
lAPMO IS 1-2003
1.0 SCOPE
1.1 Installation and material of nonmetallic
building sewer piping shall comply with
this standard and the current edition of the
Uruform Plumbing Code [UPC]tm published
by the International Association of Plumbing
and Mechanical Officials.
Note: The following sections of the 2003 Uniform
Plumbing Code apply to non-metallic building sewer
piping. The standard may include section numbers or
may omit section numbers which pertain to non-
metallic sewers.
301.1
Minimum Standards
310.0
Workmanship
311.0
Prohibited Fittings and Practices
313.0
Protection of Piping Materials and
Structures
315.0
Trenching, Excavation and Backfill
723.0
Building Sewer Test
103.5.3.3
Exceptions
705.1
Types of Joints
705.2
Use of Joints
316.2.3
Plastic Pipe to Other Materials
316.4
Prohibited Joints and Connections
, 317.0
Increasers and Reducers
Chapter 7
Sanitary Drainage
2.0 GENERAL REQUIREMENTS
2.1 After inspection of the sewer pipe, carefully
backfill the trench as prescribed by Sections
314.0 and 315.0 of the Uniform Plumbing
Code.
2.2 The same water test procedure shall apply
to all non-metallic house sewer materials as
required in Section 723.0 of the Uniform
Plumbing Code.
Before laying non-metallic sewer pipe,
prepare the bottom trench so that the piping
shall lay on a firm bed throughout its entire
length as required by Section 718.0 of I the
Uniform Plumbing Code. j
3.0 PRODUCT REQUIREMENTS
3.1 ABS OR PVC-DWV PIPE
3.1.1 Minimum Standards
ABS or PVC Schedule 40 DWV pipe for use
in domestic sewage, excluding special waste,
shall be installed in accordance with
lAPMO Standards IS 5 and IS 9 (latest
edition), whichever is applicable. ABS or
PVC Schedule 40 DWV pipe, LAPMO listed,
may be used in sizes 2 inch (51 mm) and
larger. [UPC 301.11
3.1.2 Markings
3.1.2.1 ABS Pipe. ABS pipe markings shall be in
accordance with D 2661 or F 628. [UPC
716.0]
3.1.2.2 ABS Fittings. ABS fittings markings shall
be in accordance with D 2661. [UPC 716.0]
3.1.2.3 PVC Pipe. PVC pipe markings shall be in
accordance with D 2665. [UPC 716.0]
3.1.2.4 PVC Fittings. PVC fittings markings shall
be in accor-dance with F 2135. [UPC 716.0]
3.1 .3 Protection of Building Sewers
ABS or PVC Schedule 40 pipe shall be
installed a minimum of 1 foot (305 mm)
below the surface of the finished grade.
Underground installation of thermoplastic
sewer pipe shall be in accordance with
ASTM D 2321. [UPC 718.0]
3.1.4 Cleanouts
Cleanouts, extended to within 1 foot (305
mm) of grade, shall be of materials listed for
that use. [UPC 719.0]
3.2 PVC SEWER PIPE
3.2.1 Minimum Standards
3.2.1.1 Pipe
PVC, PSM, SDR 35, ASTM D 3034 and PVC,
PS-46, ASTM F 789 Non-Pressure Pipe may
be used in sizes four (4) inches (102 mm)
and larger. [UPC 301.1]
3.2.1.2 Fittings
All fittings shall be PVC or other listed non-
metallic materials having equivalent
durability and equal or greater strengths.
[UPC 301.1]
3.2.2 Types of Joints
PVC sewer pipe shall be joined by using
compression joints or by other methods
recognized in the UPC. Pipe and fitting
ends shall be lubricated with an approved
soap jelly or soap solution to permit easy
assembly. [UPC 705.1]
3.2.2.1 Use of Joints
PVC sewer pipe shall be installed using the
same type of jointing throughout, except
when connecting to existing piping, piping
323
IS1
UNIFORM PLUMBING CODE
of other materials, in line repairs and
manholes. Transition connections to other
materials shall be made by adapter fittings
or a one-piece molded rubber coupling with
appropriate bushings for the respective
material. [UPC 705.1]
3.2.3 Markings
3.2.3.1 PSM PVC pipe markings shall be in
accordance with D 3034. [UPC 716.0]
3.2.3.2 PSM PVC fitting markings shall be in
accordance with D 3034. [UPC 716.0]
3.2.3.3 PS 46 PVC pipe markings shall be in
accordance with F 789. [UPC 716.0]
3.2.3.4 PS 46 PVC fitting markings shall be in
accordance with F 789. [UPC 716.0]
3.2.4 PVC sewer pipe shall not be installed less
than 1 foot (305 mm) below the surface of
the finished grade and closer than twenty-
four (24) inches (610 mm) from a building.
Underground installation of thermoplastic
sewer pipe shall be in accordance with
ASTM D 2321. [UPC 718.0]
3.2.5 Cleanouts
Cleanouts, extended to within 1 foot (305
mm) of grade, shall be of materials listed for
such use. [UPC 719.0]
3.3 HIGH DENSITY POLYETHYLENE PIPE
3.3.1 Minimum Standards
3.3.1.1 Polyethylene pipe shall be manufactured in
accordance with ASTM F 714 and installed
in accordance with lAPMO IS 26. [UPC
301.1]
3.3.2 Types of Joints
3.3.2.1 HDPE joints shall be made using the
following method:
a) Heat Fusion made in accordance with
ASTM D 2657 or D 3261. [UPC 705.1]
3.3.3 Markings
3.3.3.1 Markings shall be in accordance with F 714.
[UPC 716.0]
3.4
3.4.1
3.4.1.1
POLY VINYL CHLORIDE (PVC)
CORRUGATED SEWER PIPE WITH A
SMOOTH INTERIOR AND FITTINGS
Minimum Standards
Pipe. Corrugated PVC sewer pipe may be
used in sizes four (4) (102 mm), six (6) (152
mm), eight (8) (203 mm), and ten (10) (254
mm) diameters and shall conform to ASTM
F 949. [UPC 301.1]
The profile wall pipe corrugated PVC sewer
pipe as intended for underground use in non
pressure applications for sanitary sewers,
storm sewer, and perforated and unper-
forated pipes for subdrainage. [UPC 301.1]
3.4.1.2 Fittings shall be PVC or other fittings having
equivalent durability or equal or greater
strengths in accordance with ASTM F 949.
[UPC 301.1]
3.4.2 Types and Use of Joints. Corrugated PVC
sewer pipe shall be joined by Molded or
Elastomeric Compression Joints or by other
approved methods. Elastomeric seals
(gaskets) shall meet the requirements of
ASTM F 477. The lubricant used for
assembly shall be as recommended by the
seller and shall have no detrimental affect
on the gasket or on the pipe and fittings.
The PVC cement shall comply with ASTM D
2564 and shall be used in conjunction with a
primer in compliance with ASTM F 656.
The solvent cement shall be used only for
bushings in accordance with ASTM D 2855.
[UPC 316.1, 705.1, 705.3]
Markings
Corrugated PVC sewer pipe markings shall
be in accordance with F 949. [UPC 716.0]
3.4.3.2 Corrugated PVC fittings markings shall be
in accordance with F 949. [UPC 716.0]
3.4.4 Protection of Building Sewer. Corrugated
PVC sewer pipe shall not be installed less
than 1 foot (305 mm) below the surface of
the finished grade and closer than twenty-
four (24) inches (610 mm) from a building.
Underground installation of thermoplastic
sewer pipe shall be in accordance with
ASTM D 2321. [UPC 718.3]
3.4.5 Cleanouts. Cleanouts, extended to within 1
foot (305 mm) of grade, shall be of materials
listed for such use. [UPC 719.0]
3.4.3
3.4.3.1
3.5
3.5.1
3.5.2
3.5.3
ASBESTOS CEMENT SEWER PIPE
Minimum Standards
Asbestos cement sewer pipe shall be Type II
only and may be used only in sizes four (4)
inches (102 mm) and larger. Its use is
limited to domestic sewage. [UPC 301.1]
All fittings used with asbestos cement sewer
pipe shall be asbestos cement or other
approved non-metallic materials having
equivalent durability and providing fittings
with equal or greater strengths. [UPC 705.0]
Asbestos cement sewer pipe and male end
fittings shall be joined by means of a sleeve
coupling and two rubber sealing rings
suitable for the particular size of the pipe
and fittings for which they will be used. The
rubber sealing rings shall be positioned in
interior grooves in the coupling.
The assembled joint shall provide the
necessary compression of the rubber sealing
rings to make a watertight joint. The crush
324
NONMETALLIC BUILDING SEWERS
IS1
strength across the assembled joint shall be
equivalent to the crush strength of the pipe
with which it will be used. [UPC 705.1]
3.5.3.1 The use of unmachined field-cut asbestos
cement sewer pipe is permitted for 3.6.2
necessary length adjustments and at points
of connection to other piping materials.
These adaptions shall be made with either a
one-piece molded rubber coupling with
appropriate bushings or listed adapter
fittings. [UPC 705.1]
3.5.3.2 Approved female fittings shall be provided
with interior grooves in the bell ends in
which rubber sealing rings, suitable for the
particular size of pipe with which the
fittings will be used, are placed. The
compressed rubber sealing ring in the joined
female (bell) fitting end shall provide a
watertight joint. [UPC 705.1]
3.5.3.3 Pipe and fitting ends shall be lubricated with
an approved jelly or soap solution to permit 3.6.3
easy assembly. [UPC 705.1]
3.5.3.4 A listed one-piece molded rubber coupling
with appropriate bushings may be used as
an alternate means of connecting asbestos
cement pipe and male end fittings. [UPC 3.6.4
705.1] 3!6'.4.1
3.5.3.5 Transition from asbestos cement sewer pipe
to another material shall be made by listed 3.6.5
adapter fittings, or a one-piece molded
coupling with appropriate bushings for the
respective material. [UPC 705.1]
3.5.4 Markings
3.5.4.1 Asbestos cement sewer pipe markings shall
be in accordance with C 428. [UPC 716.0]
3.5.4.2 Each coupling sleeve of fitting markings
shall be in accordance with C 428. [UPC
716.0]
3.5.5 No asbestos cement sewer pipe shall be
installed less than 1 foot (305 mm) below the
surface of the ground or closer than two (2)
feet (610 mm) to a building. [UPC 718.3]
3.5.6 Cleanouts shall be asbestos cement or other
approved materials of plug or cap type
installed with rubber ring compression
joints. Cleanouts, extended to within 1 foot
(305 mm) of the surface, shall be of materials
approved for such use. [UPC 719.0] 3.7.2
3.6 CONCRETE SEWER PIPE
3.6.1 Minimum Standards
3.6.1.1 Pipe and Fittings
Concrete sewer pipe may be used in sizes 3.7.2.1
four (4) inches (102 mm) and larger. Concrete
sewer pipe shall conform to ASTM C 14,
Class 2. Transition to other types or sizes of
3.6.6
3.7
3.7.1
3.7.1.
pipe may be made with listed concrete pipe
adapter fittings or listed one-piece molded
rubber coupling with appropriate bushings
or increasers. [UPC 301.1]
Types of Joints
Concrete sewer pipe and fittings shall be
joined by means of flexible rubber sealing
rings, compressed to provide water-tight
joints conforming to ASTM C 443, or by listed
one-piece molded rubber couplings, or hot-
poured joints of listed hot-pour compounds.
Portland cement joints are prohibited except
for repairs or connections to existing lines
constructed with such joints,
concrete sewer pipe shall be joined by
gaskets furnished by the pipe manufacturer
and installed according to the manu-
facturer's instructions. Approved lubricant
shall be used when required for the type of
jokit furnished. [UPC 705.1]
Use of Joints
Except for points of cormection to existing
piping at either end of the sewer, concrete
sewer pipe shall be laid using the same type
of jointing throughout. [UPC 705.2]
Marlcings
Concrete sewer pipe and fittings markings
shall be in accordance with C 14. [UPC 716.0]
Grade, Support and Protection of
Building Sewers
Concrete sewer pipe shall be installed not
less than 1 foot (305 mm) below the ground
and not closer than two (2) feet (610 mm) to
a building. [UPC 718.0]
Cleanouts
Cleanouts shall conform to type of jointing
used and cleanouts extended to within 1
foot (305 mm) of grade, shall be of materials
listed for that use. [UPC 719.0]
VITRIFIED CLAY PIPE
Minimum Standards
Materials. Materials shall comply with the
appropriate standard in Table 14-1 of the
UPC. Vitrified clay sewer pipe, extra
strength only, may be used in sizes three (3)
inches (76 mm) and larger. [UPC 301.1]
Types of Joints
Vitrified clay sewer pipe and fittings shall
be joined by means of preformed flexible
compression joints or listed one-piece
molded rubber coupliags. [UPC 705.1]
Except at point of connection to existing
piping at either end of the sewer, vitrified
clay sewer piping shall be laid using the same
type of jointing throughout. [UPC 705.1]
325
IS1
UNIFORM PLUMBING CODE
3.7.2.2 When installing clay pipe with flexible
compression joints, the mating surfaces shall
be wiped clean of dirt and foreign matter.
An approved lubricant shall be applied to
the joint surfaces. Spigot shall then be
seated full depth into the bell. [UPC 705.1]
3.7.2.3 Listed one-piece molded rubber couplings
shall be permitted for use on vitrified clay
pipe and fittings, sizes three (3) inches (76
mm) through 1 foot (305 mm). [UPC 705.1]
3.7.2.4 Transition to other types of materials or sizes
may be made with the use of listed one-piece
molded, rubber couplings with appropriate
bushings or increasers. [UPC 705.1]
Markings
Vitrified clay sewer pipe and fittings
markings shall be in accordance with C 700.
[UPC 716.0]
No vitrified clay sewer pipe shall be
installed less than 1 foot (305 mm) below
the surface of the ground. [UPC 718.3]
Cleanouts
Cleanouts shall conform to the type of
jointing used and cleanouts extended to
within 1 foot (305 mm) of grade shall be of
materials approved for their use. [UPC 719.0]
3.7.3
3.7.3.1
3.7.4
3.7.5
ADOPTED: 1957
REVISED: 1966, 1971, 1973, 1975, 1976, 1982,
1985, 1990, 1991, 2002, 2003
326
Installation Standard
For
TILE-LINED ROMAN BATH TUBS
lAPMO IS 2-2003
(9) Wire Reinforcing
(See back page 2e)
Ceramic Tile Floor Set in
Portland Cement Mortar
Sub-Floor & Building Felt
2x6 Floor Furring
Finish Floor
2x4 Studs
Top of lining must be at
least 3" above spill-over
point of the finished rim.
(7) Reinforcement
Min. 1/4" -Max. 1/2"
per foot slope to an
approved flanged drain
(See exception, note 2)
Lining shall be pitched
1/4" per foot to weep
holes in drain
Wire Reinforcing
(See back page 2e)
SCALE 1-1/2" = l'-0"
A vapor barrier consisting of at least one layer
of 15 lb. type asphalt saturated felt shall be
between wood surfaces and concrete.
(9) Wire Reinforcing
(See back page 2e)
Finish Floot
(2) Waterproof
Membrane
Lining
(7) Reinforcement
(8) Concrete Shell f-^
Lining shall be
pitched not less
than 1/4" per foot
to weep holes in
drain.
(10) Wall Finish ,
Top of lining must be at least 3" above —
spiU-over point of the finished rim **
Wood Sill and
Anchor Bolt per
UBC
[— Bmlding foundation
Wire Reinforcing
(See back page 2e)
I
Approved Flange Drain
The receptor must rest continuously on soil
approved for building footings or be
supported by adequate structural members.
I Special approval arid >
I reinforcing required if ,
I fixture supports !
I cfni<-hi|-p Jl
SCALE 1-1/2" = r-0"
Illustrations reprinted with permission of the Ceramic Tile Institute
327
IS 2
UNIFORM PLUMBING CODE
METRIC
(9) Wire Reinforcing
(See back page 2e)
Ceramic TUe Floor Set in
Portland Cement Mortar
Wood Floor Joists - Deflection of floor system
limited to 1/360 of the span, including live and
dead loads, for both point and uniform loading.
0.6 X 1.2 m Studs
Top of liniiig must be at
least 76 mm above spill-
over point of the
finished rim.
(7) Reinforcement
Min. 20.8 mm/m - Max.
41.7 mm/m slope to an
approved flanged drain
(See exception, note 2)
Lining shall be pitched
20.8 mm/m to weep
holes in drain
" Wire Reinforcing
(See back page 2e)
SCALE 1.5 mm = 1 mm
A vapor barrier consisting of at least one layer
of 6.8 kg type asphalt saturated felt shall be
between wood surfaces and concrete.
(9) Wire Reinforcing
(See back page 2e)
Finish Floor.
(2) Waterproof
Membrane
Lining
(7) Reinforcement
(8) Concrete Shell j-^
Lining shall be
pitched not less
than 20.8 mm/m
to weep holes in
drain.
(10) Wall Finish .
Top of lirung must be at least 76 mm -
above spill-over point of the finished
rim
Min. 20.8 mm/m - Max.
41.7 mm/m slope to 50.8
mm/m approved flanged
drain (See exception. Note 2)'
Wood SiU and
Anchor Bolt per
UBC
|— Building foundation
" Wire Reinforcing
(See back page 2e)
Approved Flange Drain
The receptor must rest continuously on soil
approved for building footings or be
supported by adequate structural members.
1
Special approval and •
reinforcing required if .
fixture supports !
I <;tpi^hirp ^_ J
SCALE 1.5 mm = 1 mm
Illustrations reprinted with permission of the Ceramic Tile Ii\stitute
328
TILE-LINED ROMAN BATH TUBS
IS 2
1.0 GENERAL REQUIREMENTS 2.11
1 .1 Inspection of Work - All surfaces prepared
by others shall be inspected by the tile
installer before starting tile work and all
unsatisfactory conditions reported to the
Administrative Authority. Starting tile work 2.1 1 .1
by the tile installer shall be considered as
acceptance of surfaces prepared by others.
1 .2 Surfaces - All surfaces to receive tile work
shall be clean, structurally sound, and
conform in every way to the local Building
Code.
(Note: No tile work shall proceed until the
pan and drain construction has been
inspected and approved by the
Administrative Authority, where required.)
2.2
2.3
2.4
2.5
2.6
2.7
2.8
3.0
3.1
2.0 MATERIALS
2.1 Tile Quality and Grade - Tile shall comply
with American National Standard
Specification for Ceramic Tile, A137.1
(equivalent to and incorporating U.S. Dept.
of Commerce Simplified Practice
Recommendation, R61-61 and Federal
Specification SS-T-308b, Tile, Floor, Wall,
and Trim Units, Ceramic).
Cement -■ Cement shall be portland cement
type I or type II, conforming to ASTM C 150.
Sand - Sand shall be damp, clean and
graded ASTM C 778.
Water - Water shall be potable.
Reinforcing shall be 3 inch x 3 inch (76 mm
X 76 mm), 13 x 13 gage or 1-1/2 x 2 (38 mm 3.2
X 51 mm) mesh, 16 x 13 gage steel wire,
conforming to ASTM A82 and A185.
Asphalt shall conform to Federal
Specification SS-A-0666, Type Z, Grade 2,
Class A.
Plastic Roof Cement shall conform to
Federal Specification SS-C153.
Waterproof Felt Membrane - The
waterproof felt membrane shall be at least
15 lb. (6.8 kg) asphalt saturated felt,
conforming to Type 1, Federal Specification
HH-F-191 (a).
2.9 Plastic Membrane shall comply with
applicable standards listed in Table 14-1 of
the UPC.
2.10 Other Membranes - Where the
Administrative Authority approves their
use, non-metallic sub-pans or linings of lead
sheets weighing not less than 4 lbs. per sq.
foot (191.5 Pa) and copper pans of at least
No. 24 B & S gage may be used.
Waterproofing Admixture - The mortar
bed of the receptor shall be mixed with a
waterproof admixture, approved by the
Administrative Authority in the amounts
allowed by such approval.
Currently Approved Mortar Additives
Anti-Hydro - 1 qt. (0.95 I) per sack of
cement.
Plastiment - 1 lb. (0.5 kg) of powder per
sack of cement.
Plastiment - 2 oz. (56.7 g) of fluid per sack of
cement.
Sika 3A - 1 qt. (0.95 1) per sack of cement
Suconem (Red Label) - 1 pint (0.47 I) per
sack of cement.
INSTALLATION
Drains - An approved type drain with sub-
drain shall be installed with every such
shower membrane. Flange of each sub-
drain shall be accurately set exactly level
with sloping sub-floor and shall be
equipped with a clamping ring or other
approved device to make a tight connection
between the membrane and the sub-drain.
The sub-drain shall have weep holes into the
waste line. The drain shall be of such design
that there will be not less than 2 inch (51
mm) depth from the top of the sub-drain
flange to top of the strainer. A ring of
absorbent material must be placed around
the weep holes to keep them open when the
finish materials are installed.
Sloping Sub-Floor and Membrane - All
lining materials shall be pitched not less
than one quarter (1/4) inch per foot (20.8
ihm/m) to weep holes in the sub-drain by
means of a smooth and solidly formed
sloping sub-base. All such lining materials
shall extend upward on the side walls of the
tub to a point not less than four (4) inches
(102 mm) above the top of the finished dam
or threshold and shall extend outward over
the top of the rough threshold and be turned
over and fastened on the outside face of the
rough threshold. All ledge tops within four
(4) inches (102 mm) above the rough
threshold shall be covered with the lining
material. Non-metallic sub-pans or linings
shall be built-up on the job site and shall
consist of not less than three (3) layers of
standard grade fifteen (15) pound (6.8 kg)
asphalt impregnated roofing felt. The
bottom layer shall be mopped to the formed
sub-base with hot asphalt and each
329
IS 2
UNIFORM PLUMBING CODE
succeeding layer thoroughly hot-mopped to
that below, on the basis of twenty (20)
pounds (9.1 kg) of asphalt per layer per
square. All corners shall be carefully fitted
and shall be made strong and watertight by
folding or lapping, and each comer shall be
reinforced with suitable woven glass fiber
webbing hot-mopped in place. All folds,
laps, and reinforcing webbing shall extend
at least four (4) inches (102 mm) in all
directions from the comer and all glass fiber
webbing shall be of approved type and
mesh, producing a tear strength of not less
than fifty (50) pounds per square inch (344.5
kPa) in either direction. Non-metallic
shower sub-pans or linings niay also consist
of multi-layers of other approved equivalent
materials suitably reinforced with glass
fibers and having each layer carefully fitted
and hot mopped in place on the job site as
elsewhere required in this section, according
to manufacturer's recormnended installation
procedures.
Linings shall not be nailed or perforated at
any point which will be less than one (1)
inch (25.4 mm) above the finished dani or
threshold.
Where flexible plastic sheet membranes are
used, comers shall be carefully constructed by
folding or bonding of pre-fabricated
reinforcing corner. Joints in flexible plastic
sheeting shall be constructed with the
appropriate solvent bonding liquid, bodied
solvent cement, or thermal welding.
Where lead and copper pans are used as
membranes, the installation shall be made in
similar manner as required for felt
membranes, except the asphalt moppings,
and, in addition, the pans shall be insulated
from all concrete and mortar surfaces and
from all conducting substances, other than
their connecting drain, by 15 lb. (6.8 kg)
asphalt saturated felt or an approved
equivalent, hot-mopped to the lead or
copper pans. Joints in lead and copper pans
shall not be soldered, but shall be burned or
silver brazed, respectively.
3.3 Tests - Upon installation, all concrete tub
shells shall be tested for water tightness by
being filled to the top of the rough threshold
with water for 24-hours to establish their
water tightness.
3.4 Roman Bath Tub - Floor shall be of ceramic
tile set in portland cement mortar, mixed in
the proportion of one (1) part portland
cement to four (4) parts of mortar sand by
volume and shall be provided with an
approved shower drain designed to make a
water-tight joint at the floor. The mortar
mixture shall be of such consistency that a
troweled surface readily assumes a smooth,
slickened surface. All concrete mortar bases
shall be mixed with an approved
waterproofing admixture and properly
reinforced with 3 inch x 3 inch (76 mm x 76
mm) mesh, 13 x 13 gage or 1-1/2 inch x 2
inch (38 mm x 51 mm) mesh, 16 x 13 gage
cold drawn welded steel wire fabric located
in the approximate center of the mortar bed
and extending up the side walls but, in no
case, less than 1 inch (25.4 mm) above the
finished threshold. Corners shall be lapped
and the reinforcing shall extend over the
threshold and ledges.
The total thickness of the floor mortar shall
not be less than 1-1/4 inch (32 mm) at any
point. The tile floor shall have a minimum
of 1/8 inch (3.2 mm/m) pitch and a
Ceramic Tile
Bond Coat
Mortar Bed
Scratch Coat
Metal Lath
Waterproof Membrane
Exterior Grade Plyw^ood
WOOD FORM
330
TILE-LINED ROMAN BATH TUBS
IS 2
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
3.4.6
3.4.7
3.4.8
3.4.9
maximum of 1/2 inch (12.7 mm/m) pitch
toward the drain per foot. Bath tub walls to
a minimum height to 3 inch (76 mm) and
not less than 1 inch (25.4 mm) above the
finished dam shall be lined with ceramic tile
set in Portland cement mortar, mixed with
an approved waterproofing admixture.
All wood framed bases shall be designed
with a maximum deflection of 1/240 of the
span, Including live and dead loads.
Note: Two stages of construction are
covered - the reinforced concrete shell and
the w^ire reinforced tile lining over the
water-proof membrane.
Approved waterproofing membrane, mortar
bed and finish construction shall conform to
the general requirements of the Uniform
Plumbing Code. Exception: In short
sections where there is no foot traffic, the
finished floor may exceed 1/2 inch per foot
(12.7 mm/m) slope.
Each concrete shell shall be filled to its
overflow^ rim w^ith water and shall remain
watertight for not less than twenty-four (24)
hours before inspection and before the finish
surface is installed.
The finish surface shall be ceramic tile
installed with portland cement mortar
mixed to a proper consistency in the
proportion of one (1) part cement and four
(4) parts mortar sand by volume and having
an approved waterproofing admixture*
included. Ceramic tile joints shall be
thoroughly grouted with approved water-
proofing grout containing an admixture.
The concave interior surfaces shaU be such as
to permit ready cleansing and all comers shall
be rounded or at angles not in excess of 45°.
Grout is not acceptable for rounding comers.
See details below^ on approved comers.
Concealed overflow or built-in waste
stopper may be used if designed and
approved for this application.
For reinforcement in center of pour, use #30
@ 8 inch (203 mm) O.C. both ways.
2000 P.S.I. (13,780 kPa) compressive strength
concrete shall be poured monolithically and
shall have an approved waterproofing
admixture included*. Concrete to have not
less than six (6) sacks of portland cement per
batch.
Reinforcing wire, as specified under
materials in this standard or equal, shall be
wired together in a self-supporting manner.
Nails shall not be used through the
waterproofing membrane to fasten wire
reinforcing.
^Quantities of several approved
waterproofing admixtures required per sack
of cement:
Anti-Hydro - 1 qt. (0.95 1) per sack of
cement.
Plastiment - 1 lb. (0.5 kg) of powder per
sack of cement.
Plastiment - 2 oz. (56.7 g) of fluid per sack of
cement.
Sika 3A - 1 qt. (0.95 1) per sack of cement.
Suconem (Red Label) - 1 pint (0.47 1) per
sack of cement.
ADOPTED: 1966
REVISED: 1 977, 1 982, 1 990, 2003
Ar
Approved Comers Under
L' II i form Plumbing Code
vni
331
IS 2 UNIFORM PLUMBING CODE
332
Installation Standard
For
COPPER PLUMBING TUBE, PIPE, AND FITTINGS
lAPMO IS 3-2003
1.0 SCOPE
1.1 Installation and material of copper tube,
pipe and fittirigs in drainage, vent, and
water systems shall comply with this
standard and the current edition of the
Uniform Plumbing Code [UPCpM,
published by the International Association
of Plumbing and Mechanical Officials
(lAPMO).
Note: The following sections of the Uniform
Plumbing Code shall apply.
103.5.3 Testing of systems
301.1 Minimum standards
310.0 Workmanship
311.0 Prohibited fittings and practices
313.0 Protection of piping materials and
structures
314.0 Hangers and supports
316.1 Types of joints
316.2 Special joints
316.4 Prohibited joints and connections
317.0 Increasers and reducers
604.0 Materials
604.1 Water piping
604.2 Water piping
604.3 Marking of tubing
604.4 Flexible water connectors
604.7 Restriction of used piping
606.1.1 Flared joints
606.2.1 Use of joints, copper water tube
608.0 Relief valve drain
609.0 Installation, inspection, testing
610.0 Size of potable piping
701.1.4 Drainage and vent piping
704.4.1 Closet Flanges
705.3.3 Ground joint, flared or ferrule
connections
707.1 Cleanouts
701.0 Materials, drainage piping
811.1 Chemical or industrial waste piping
903.0 Materials, vent piping
903.2 Use of copper tubing
1101.3 Materials, rain water piping
1105.1 Materials, roof drains
Table 14-1 Standards:
ASME B 16.18 Cast Copper Alloy Solder-Joint
Pressure Fittings
ASME B 16.22 Wrought Copper and Copper Alloy
Solder-Joint Pressure Fittings
ASME B 16.23 Cast Bronze Solder-Joint Drainage
Fittings - DWV
ASME B 16.29 Wrought Copper and Copper Alloy
Solder-Joint Drainage Fittings
ASME B 16.50 Wrought Copper and Copper Alloy
Braze-Joint Pressure Fittings
ASTM B 32 Specification for Solder Metal
ASTM B 42 Specification for Seamless Copper
Pipe, Standard Sizes
ASTM B 75 Specification for Seamless Copper
Tubes
ASTM B 88 Specification for Seamless Copper
Water Tube
ASTM B 302 Specification for Threadless Copper
Pipe, Standard Sizes
ASTM B 306 Specification for Copper Drainage
Tube (DWV)
ASTM B 813 Liquid and Paste Fluxes for
Soldering Applications of Copper
and Copper AUoy Tube
ASTM B 828 Standard Practice for Making
Capillary Joints by Soldering of
Copper and Copper Alloy Tube
and Fittings
Appendix A Chart A-4 Friction loss per 100 ft.
(30.5 m)
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1 .1 Materials. Materials shall comply with the
appropriate standard in Table 14-1 of the
UPC. [UPC 301.1]
Note: The nominal or standard size of
copper plumbing tube is always 0. 125 inch
(3.175 mm) or one-eighth (1/8) inch (3.175
mm) smaller than the actual outside
diameter dimension of the tube. For
example, 3 inch (76 mm) nominal size
copper plumbing tube measures 3-1/8 inch
(79 mm) O.D., 1/2 inch (12.7 mm) nominal
size copper plumbing tube measures 5/8
inch (15.9 mm) O.D., etc.
333
IS 3
2.1.2
2,1.3
2.1.4
2.1.5
2.2
2.2.1
Markings. Markings shall be visible for
inspection. Products that are covered by this
standard shall be identified in accordance
with the standard found in Table 14-1.
Tube and Threadless Pipe.
Water tube (Types K, L, M), drainage tube
(Type DWV), and threadless pipe (TP), shall
bear the following incised marking at not
over 18 inch (457 mm) intervals:
(a) Manufacturer's name or trademark;
and,
(b) Tube type
Pipe (Copper and Copper Alloy)
Pipe shall bear the following incised marking
at not over 18 inch (457 mm) intervals:
(a) Manufacturer's name or trademark;
and,
(b) Pipe type.
Fittings
Fittings shall bear the following markings:
(a) Manufacturer's name or trademark, and
(b) "DWV" on drainage fittings.
Type of Joints
General Information
Copper tube and fittings may be joined in a
number of ways, depending on the purpose
of the system. Soldering and brazing with
capillary fittings are the methods used most.
The American Welding Society (AWS)
defines soldering as a joining process which
takes place below 840°F (449°C) and brazing
as a similar process which occurs above 840°F
(449°C) but below the melting point of the
base metals. In actual practice for copper
systems, most soldering is done at
temperatures from about 350°F (177°C) to
550°F (288°C), while most brazing is done at
temperatures ranging from 1100°F (593°C) to
1500°F (816°C). The choice between soldering
or brazing will generally depend on
operating conditions. Solder joints are
generally used where the service temperature
does not exceed 250°F (121°C), while brazed
joints are used where greater tensile strength
is required to resist vibration, or pressure or
temperature cycling, or where system
temperatures are as high as 350°F (177°C).
Although brazed joints offer higher joint
strength in general, the annealing of the tube
and fitting which results from the higher heat
used in the brazing process can cause the
rated pressure of the system to be less than
that of a soldered joint. This fact should also
be considered in choosing which joining
process to use.
UNIFORM PLUMBING CODE
Mechanical joints are used frequently for
some underground connections, for joints
where the use of heat is impractical and for
joints that may have to be disconnected
from time to time. [UPC 316.1]
2.2.2 Fittings for Soldered, Brazed, and
Mechanical Joints
Cast fittings are available in all standard tube
sizes and in a wide variety of types to cover
needs for plumbing. They can be either
soldered or brazed, although brazing cast
fittings requires care. Wrought copper
pressure fittings are also available over a
wide range of sizes and types. These, too,
can be joined by either soldering or brazing
and wrought fittings are preferred where
brazing is the joining method. Otherwise, the
choice between cast and wrought fittings is
largely a matter of the user's preference and
availability. According to the American
Welding Society, the strength of a brazed
joint wiU meet or exceed that of the tube and
fitting being joined when the joint overlap
and tiie depth of the filler metal penetration
is a minimum of three times the thickness of
the thinner base metals (tube or fitting) and a
well-developed fillet (cap) is present. The
strength of a brazed copper tube joint does
not vary much with different filler metals but
depends on maintaining the proper clearance
between the outside of the tube and the
socket (cup) of the fitting. Copper tube and
solder-type pressure fittings are accurately
made for each other, and the tolerances
permitted for each assure the capillary space
will be within the limits necessary for a joint
of satisfactory strength. However, the depths
of the socket are considerable deeper than the
three times required by AWS. There are
standards available for the manufacture of
fittings made specifically for brazing, these
include ASME B 16.50 and MSS SP 73. When
fittings are made to these standards, they
cannot be soldered. They must be brazed.
2.2.2.1 Mechanical Joints
Flared-tube fittings provide metal-to-metal
contact similar to ground joint unions; both
can be easily taken apart and reassembled.
Grooved end mechanical fittings are also
available in sizes 2-inches to 6-inches.
Mechanical joint fittings are especially useful
where residual water cannot be removed
from the tube and soldering is difficult.
Mechanical joints may be required where a
fire hazard exists and the use of a torch to
make soldered or brazed joints is not
334
COPPER PLUMBING TUBE, PIPE AND FITTINGS
IS 3
allowed. Also, soldering under wet
conditions can be very difficult and
mechanical joints may be preferred under
such circumstances.
2.2.3 Solders
Most solders referenced in ASTM B 32 can
be used to join copper tube and fittings in
potable water systems.
Note: Users of the Uniform Plumbing Code
are reminded that provisions of the Federal
Safe Drinking Water Act of 1986 (SDWA),
which all must obey, forbid the use of solder
which contains in excess of 0.2% of lead, in
potable water systems. The provisions of the
act are incorporated in all ordinances,
statutes, state and municipal regulations by
reference and by operation of law.
The selection of a solder depends on the
operating pressure and temperature of the
system. Consideration should also be given
to the stresses on the joint caused by thermal
expansion and contraction. However,
stresses due to temperature changes should
not be significant in two commonly
encountered cases: when tube lengths are
short, or when expansion loops are used in
long tube runs.
Solder is generally used in wire form, but
paste-type solders are also available. These
are finely granulated solders in suspension
in a paste flux. These solder /flux pastes
must meet the requirements of ASTM B 813.
When using paste-type solders, observe
these four rules:
1. Wire solder must be applied in addition
to the paste to fill the voids and assist in
displacing the flux, otherwise the
surfaces may be well "tinned" and yet
there may not be a good joint with a
continuous bond. Use the same type of
solder (e.g., 50-50 or 95-5) as that used
in the paste.
2. The paste mixture must be thoroughly
stirred if it has been standing in the can
for more than a very short time, as the
solder has a tendency to settle rapidly to
the bottom.
3. The flux cannot be depended on to
clean the tube. Cleaning should be
done manually as is recommended for
any other flux and solder.
4. Remove any excess flux. Solders are
available that contain small amounts of
silver or other additives to impart special
properties. Such solders may require
special fluxes. The manufacturer's
recommendations should be consulted
regarding proper procedures and fluxes
for such solders and about the expected
properties.
2.2.4 Soldering Flux
The functions of the soldering flux are to
remove residual traces of oxides, to promote
wetting and to protect the surfaces to be
soldered from oxidation during heating. The
flux should be applied to clean surfaces and
only enough should be used to lightly coat the
areas to be joined.
An oxide filn\ may reform quickly on
copper after it has been cleaned. Therefore,
the flux should be applied as soon as
possible after cleaning.
CAUTION
Careless workmanship, especially during
flux applications, can result in corrosion of
the tube long after the system has been
installed. If excessive flux is used, the
residue inside the tube can cause corrosion.
In an extreme case, such residual flux can
actually lead to perforation through the tube
wall causing leakage. To guard against this
danger, it is important (1) to choose a flux
that is manufachired to ASTM B 813, and (2)
to use only the minimum amount actually
needed to make the joint.
2.3 Solder Joints
2.3.1 Soldering and brazing both involve basic
steps, based on ASTM Standard Practice B
828, which must be executed with care and
craftsmanship. The steps are:
(1) Measuring
(2) Cutting
(3) Reaming
(4) Cleaning
(5) Fluxing
(6) Assembly and support
(7) Heating
(8) Applying the filler metal
(9) Cooling and cleaning
Each step contributes to a strong,
dependable joint.
2.3.2 Measuring
Measuring the length of each tube segment
must be accurate. Inaccuracy can
compromise joint quality. If the tube is too
short it will not reach all the way into the
socket of the fitting and a proper joint
caimot be made. If the tube segment is too
long there is a danger of cocking the tube in
the fitting and putting strain pn the system
which could affect service life.
335
IS 3
2.3.3
2.3.4
2.3.5
Cutting
Once the tube is measured, it can be cut.
Cutting can be accomplished in a number of
different ways to produce a satisfactory
square end. The tube can be cut with a disc-
type tube cutter, a hacksaw, an abrasive
wheel, or with a stationary or portable
handsaw. Care must be taken that the tube is
not deformed while being cut. Regardless of
the method, the cut must be square with the
run of the tube so that the tube will seat
properly in the fitting socket.
Reaming
All pipe and tube shall be reamed to the full
ID. of the pipe and tube to remove the small
burr created by the cutting operation. If this
rough, inside edge is not removed erosion-
corrosion may occur due to localized
turbulence and high velocity.
Tools used to ream tube ends include the
reaming blade on the tube cutter, half-round
or round files, a pocket knife, or a suitable
deburring tool. With annealed tube, care
must be taken not to deform the tube end by
applying too much pressure. Both the inside
and the outside of the tube may require
removal of the burr, especially in large
diameters.
Cleaning
The removal of all oxides and surfaces soil is
crucial if filler metal is to flow properly into
the joint. Failure to remove them can
interfere with capillary action and may
lessen the strength of the joint and cause
failure.
Mechanical cleaning is a simple operation.
The end of the tube should be lightly
abraded using sand cloth or nylon abrasive
pads for a distance only slightly more than
the depth of the fitting socket. The socket of
the fitting should also be cleaned using sand
cloth, abrasive pads, or a properly sized
fitting brush.
Copper is a relatively soft metal. If too much
material is removed, a loose fit will result
and interfere with satisfactory capillary
action in making the joint. The capillary
space between tube and fitting is
approximately 0.004 inch (0.10 mm). Solder
or brazing filler metal can fill this gap by
capillary action. This spacing is critical for
the filler metal to flow into the gap and form
a strong joint.
Surfaces once cleaned should not be touched
with bare hands or oily gloves. Skin oils.
UNIFORM PLUMBING CODE
lubricating oils, and grease impair filler
metal flow and wetting.
2.3.6 Fluxing
Stir the flux before use. Flux will dissolve
and remove traces of oxide from the cleaned
surfaces to be joined, protect the cleaned
surfaces from reoxidation during heating
and promote wetting of the surfaces by the
solder. A thin, even coating of flux should
be applied with a brush to both tube and
fitting as soon as possible after cleaning. Do
not apply with fingers. Chemicals in the
flux can be harmful if carried to the eyes,
mouth, or open cuts.
2.3.7 Assembly and Support
After both tube and fitting surfaces are
properly fluxed, they should be assembled,
niaking sure the tube seats against the base
of the fitting socket. A slight twisting
motion ensures even distribution by the flux.
Remove any excess flux. Care must be taken
to assure that the tube and fittings are
properly supported to ensure a uniform
capillary space around the entire
circumference of the joint. Uniformity of
capillary space will ensure good filler metal
penetration if the guidelines of successful
joint making are followed. Excessive joint
clearance can cause the filler metal to crack
under stress or vibration.
The joint is now ready for soldering. Joints
prepared and ready for soldering should be
completed the same day and not left
unfinished overnight.
2.3.8 Heating
WARNING: When dealing with an open
flame, high temperatures, and flammable
gases, safety precautions must be observed
as described in the ANSI /ASC Z49.1
Standard.
Heat is generally applied using an air /fuel
torch. Such torches use acetylene or an LP
gas. Electric resistance tools can also be used.
Begin heating with the flame perpendicular
to the tube on the bottom. The copper tube
conducts the initial heat into the fitting
socket for even distribution of heat in the
joint area. The extent of this preheating
depends upon the size of the joint.
Experience will indicate the amount of time
needed. Preheating of the assembly should
include the entire circumference of the tube
in order to bring the entire assembly up to a
suitable preheat condition. However, for
joints in the horizontal position, avoid
336
COPPER PLUMBING TUBE, PIPE AND FITTINGS
IS 3
directly preheating the top of the joint to
avoid burning the soldering flux. The
natural tendency of heat to rise will ensure
adequate preheat of the top of the assembly.
Next, move the flame onto the fitting socket.
Sweep the flame alternately from the fitting
socket back onto the tube a distance equal to
the depth of the fitting socket. Touch the
solder to the joint. If the solder does not
melt, remove it and continue the heating
process. Be careful not to overheat or to
direct the flame into the fitting cup. This
could cause the flux to burn and destroy its
effectiveness. When the solder begins to
melt, the heat should be directed to the base
of the cup to aid capillary action in drawing
the molten solder into the fitting socket
towards the heat source.
2.3.9 Applying the Filler Metal
For joints in the horizontal position, start
applying the solder slightly off-center at the
bottom of the joint. When the solder metal
begins to melt from the heat of the tube and
fitting, do not use the torch to melt the
solder; push the solder straight into the joint
while keeping the torch at the base of the
fitting socket and slightly ahead of the point
of application of the solder. Continue this
technique across the bottom of the fitting
and up the side to the top of the fitting.
Return to the beginning, overlapping
slightly by re-melting the solder at the point
and proceed up the other side to the top,
again overlapping slightly.
For joints in the vertical position, a similar
sequence of overlapping passes should be
made, starting wherever is convenient.
Molten solder will be drawn into the joint
by capillary action regardless of whether the
solder is being fed upward, downward, or
horizontally. IMPORTANT: Always
remember to let the heat lead the alloy. Do
not apply the filler metal in front of the heat.
2.3.10 Cooling and Cleaning
After the joint has been completed, natural
cooling is best. Shock cooling with water
may cause unnecessary stress on the joint
and result in eventual failure. When cool,
clean off any remaining flux with a wet rag.
2.3.11 Testing
Test all completed assemblies for joint
integrity following the procedures described
in the body of this code. Completed systems
should be flushed to remove excess flux and
debris as soon as possible after completion.
2.4 Brazed Joints
2.4.1 Brazing is another commonly used method
for joining copper tube. Making brazed
joints is similar to making soldered joints
with respect to measuring, cutting, reaming,
cleaning, assembly, and support. And as in
soldering, the brazing filler metal is melted
by the heat of the tube and fitting and
drawn into the joint by capillary action.
The major differences between soldering
and brazing are the:
• Type of flux used;
• Composition of filler metal; and
• Amount of heat required to melt the filler
metal.
2.4.2 Brazing Flux
The fluxes used for brazing copper joints are
different in composition from soldering
fluxes. The two types cannot be used
interchangeably. Unlike soldering fluxes,
brazing fluxes are water based. Similar to
soldering fluxes, brazing fluxes dissolve and
remove residual oxide from the metal
surfaces, protect the metal from reoxidation
during heating and promote wetting of the
surfaces to be joined by the brazing filler
metal.
Fluxes also provide the craftsman with an
indication of temperature. Application of
the flux is the same as when soldering. If
the outside of the fitting and the heat-
affected area of the tube are covered with
flux (in addition to the end of the tube and
the cup), oxidation will be prevented and
the appearance of the joint will be greatly
improved.
2.4.3 Brazing Filler Metals
Brazing filler metals suitable for joining
copper tube systems are of two classes.
Classified according to their components,
they are: BCuP (Brazing-Copper Phosphorus)
and BAg (Brazing-Silver).
BCuP filler metals are preferred for joining
copper tube and fittings if codes and
construction specifications allow it. The
phosphorus in them acts as a fluxing agent
and the lower percentage of silver makes
them relatively low cost. When using copper
tube, wrought copper fittings, and BCuP
brazing filler metal, fluxing is optional.
However, when cast fittings are brazed, flux
must be used.
2.4.4 Heating
WARNING: When dealing with an
open flame, high temperatures, and
337
IS 3
UNIFORM PLUMBING CODE
flammable gases, safety precautions must be
observed as described in the ANSI/ASC
Z49.1 Standard. Oxy/fuel torches are
generally used for brazing because of their
higher temperatures. However, recent
innovations in tip design make air /fuel
torches useful for brazing on a wide range of
sizes for brazing.
The heating operation is the same as for
soldering. Heat the tube first, beginning
about one inch from the edge of the fitting,
sweeping the flame around the tube in short
strokes at right angles to the axis of the tube.
It is very important that the flame be in
motion and not remain on any one point
long enought to damage the tube. Switch the
flame to the fitting at the base of the fitting
socket. Heat uniformly, sweeping the flame
from the fitting to the tube. Avoid excessive
heating of cast fittings or they may crack.
2.4.5 Applying Brazing Filler Metal
Apply the brazing filler metal at the point
where the tube enters the socket of the
fitting. When the proper temperature is
reached, the filler metal will flow readily
into the space between the tube and fitting
socket, drawn in by the natural force of
capillary action.
Keep the flame away from the filler metal
itself as it is fed into the joint. The
temperature of the tube and fitting at the
joint should be high enough to melt the filler
metal. Keep both the tube and fitting heated
by moving the flame back and forth fom one
to the other as the filler metal is drawn into
the joint.
When the joint is properly made the filler
metal will be drawn into the fitting socket
by capillary action, and a continuous fillet
(cap) of filler metal will be visible
completely around the joint. To aid in the
development of this fillet during brazing,
the flame should be kept slightly ahead of
the pint of filler metal application.
When brazing horizontal joints, it is
preferable to first apply the filler metal
slightly off-center of the bottom of the joint,
proceeding across the bottom of the joint
and continuing up the side to the top of the
joint. Then return to the beginning point,
overlapping slightly. This procedure is
identical to that used for soldering. Also,
similar to the soldering process, make sure
the operations overlap.
On vertical joints, it is immaterial where the
joint is made. If the opening of the fitting
socket is pointing down, care should be
taken to avoid overheating the tube, as this
may cause the brazing filler metal to run
down the outside of the tube.
If the filler metal fails to flow, or has the
tendency to ball-up, it indicates either that
there is oxide on the surfaces being joined or
that the parts to be joined are not hot
enough. If the filler metal refuses to enter
the joint, the fitting cup is not hot enough.
Most poorly made braze joints result from
either the tube or the fitting not being hot
enough. If filler metal tends to flow over the
outside of either part of the joint, it indicates
that part is overheated in comparison to the
other. When the joint is completed, a
continuous fillet should be visible
completely around the joint.
Larger diameter tube is more difficult to heat
to the desired teniperature. The use of a
heating tip or rosebud may be necessary to
maintain the proper temperature over the
area being brazed. Once total heat contiol is
attained, foUow the same procedures used for
smaller tube.
2.4.6 Cooling and Cleaning
When the brazed joint is finished, allow it to
cool naturally. Flux residues and some
oxides formed by heating can be removed
by washing with hot water and brushing
with a stainless steel wire brush.
2.4.7 Testing
Test all completed assembles for joint
integrity following the procedures described
in the body of this code. Completed systems
should be flushed to remove excess flux and
debris as soon as possible after completion.
2.4.8 Purging
Some installations, such as medical gas,
high-purity gas, and ACR systems, require
the use of an inert gas during the brazing
process. The purge gas displaces oxygen
from the interior of the system while it is
being subjected to the high temperatures of
brazing and therefore eliminates the
possibility of oxide formation on the interior
of the tube surface.
2.5 Flared Joints
2.5.1 Flared Joints with Impact Flaring Tools
Step 1 Cut the tube to the required length.
Step 2 Remove all burrs. This is very
important to assure metal-to-metal
contact.
338
COPPER PLUMBING TUBE, PIPE AND FITTINGS
IS 3
Step 3 Soft temper tube, if deformed,
should be brought back to
roundness with a sizing tool. This
tool consists of a plug and sizing
ring.
Step 4 Slip the coupling nut over the end
of the tube.
Step 5 Insert flaring tool into the tube end.
Step 6 Drive the flaring tool by hammer
strokes, expanding the end of the
tube to the desired flare. This
requires a few moderately light
strokes.
Step 7 Assemble the joint by placing the
fitting squarely against the flare.
Engage the coupling nut with the
fitting threads. Tighten with two
wrenches, one on the nut and one
on the fitting.
2.5.2 Flared Joints with Screw-Type Flaring
Tools
Steps 1-4 Same as for impact flaring
previously described.
Step 5 Clamp the tube in the flaring block
so that the end of the tube is
slightly above the face of the block.
Step 6 Place the yoke of the flaring tool on
the block so that the beveled end of
the compressor cone is over the
tube end.
Step 7 Turn the compressor screw down
firmly, forming the flare between
the chamber in the flaring block
and the beveled compressor cone.
Step 8 Remove the flaring tool. The joint
can now be assembled as in Step 6
for impact flaring.
2.6 Sizing, Velocity
To avoid excess system noise and the
possibility of erosion-corrosion, flow
through copper tube systems should not
exceed velocities of 8 feet per second for
cold water and 5 feet per second in hot
water up to approximately 140°F (60°C)
[UPC 610.0]
In systems where water temperatures
routinely exceed 140°F (60°C), lower
velocities such as 2 to 3 feet per second
should not be exceeded. In addition, where
1/2-inch and smaller tube sizes are used, to
guard against localized high velocity
turbulence due to possible faulty
workmanship (e.g. burrs at ,tube ends which
were not properly removed) or unusually
numerous, abrupt changes in flow direction,
lower velocities should be considered.
Due to constant circulation and elevated
water temperatures, particular attention
should be paid to velocities in circulation
hot water systems. Both the supply and
return piping should be sized such that the
maximum velocity does not exceed the
above recommendations. Care should be
taken to ensure that the circulating pump is
not oversized and the return piping is not
undersized, both common occurrences in
installed copper piping systems.
3.0 GENERAL INFORMATION
3.1 It is not possible to cover all the variables of
a plumbing system; however, the following
information may prove helpful:
Expansion Loops - Copper tube, like all
piping materials, expands and contracts
with temperature changes. Therefore, in a
copper tube system subjected to excessive
temperature changes, the line tends to
buckle or bend when it expands unless
compensation is built into the system.
Severe stresses on the joints may also occur.
Such stresses, buckles, or bends are
prevented by the use of expansion joints or
by installing offsets, "U" bends, coil loops,
or similar arrangements in the tube
assembly. These specially shaped tube
segments take up expansion and contraction
without excessive stress. The expansion of a
length of copper tube may be calculated
from the formula:
Temperature Rise (°F) x Length (feet) x 12
(inches per foot) x
Expansion Coefficient (in. per in. per °F) =
Expansion (inches), or
Temperature Rise (°C) x Length (meter) x
1000 (mm per meter) x
Expansion Coefficient (mm per mm per °C)
= Expansion (mm).
Calculations for expansion and contraction
should be based on the average coefficient
of expansion of copper, v^hich is 0.0000094
per °F (1.692 x 10-5 per °C), between 70°F
(21°C) and 212°F (100°C). For example, the
expansion of each 100 feet (3048 mm) of
length of any size tube heated from room
temperature (70°F) (21°C) to 170°F (77°C) (a
100°F (38°C) rise) is 1.128 inches (28.7 mm).
339
IS 3
UNIFORM PLUMBING CODE
3.2
3.3
3.3.1
100° X 100 ft X 12 in. /ft X
0.0000094 in./in./°F = 1.128 in., or
55.6° X 30.48 m x 1000 mm/m x 1.692 x
10-5 min/mm/°C = 28.7 mm
Tube Supports - See Table 3-2 and Section
314.0 in the Uniform Plumbing Code.
Bending
Copper tube, properly bent, will not collapse
on the outside of the bend and will not buckle
on the inside of the bend. Tests demonstrate
that the bursting strength of a bent copper
tube can be greater than it was before
bending. Because copper is readily formed,
expansion loops and other bends necessary in
an assembly are quickly and simply made if
the proper method and equipment are used.
Simple hand tools employing mandrels, dies,
forms, and fillers, or power-operated bending
machines are used.
Both ar\nealed tube and bending-temper tube
can be bent with hand benders. The proper
size bender for each size tube must be used.
Usually the size of the tool corresponds to the
nominal outside diameter of the tube, not the
standard tube size. For a guide to the typical
bend radii, see the following bending guide
for copper tube.
ADOPTED: 1969
REVISED: 1973, 1975, 1987, 1989, 1993,
2000, 2003
BENDING GUIDE FOR COPPER TUBE
Minimum
Tube Size,
Tube Type
Temper
Bend Radius,
Type of Bending
Inches (mm)
Indies (mm)
Equipment
1/4 (6.4)
K,L
Annealed
3/4
(19.1)
Lever type
3/8 (9.5)
K,L
Annealed
1-1/2
(38)
Lever or gear type
3
(76)
None; by hand*
K,L,M
Drawn
1-3/4
(44)
Gear type
1/2 (12.7)
K,L
Annealed
2-1/4
(57)
Lever or gear type
4-1/2
(114)
None; by hand*
K,L,M
Drawn
2-1/2
(64)
Gear type
3/4 (19.1)
K,L
Annealed
3
(76)
Lever or gear type
K
4-1/2
(114)
None; by hand*
L
6
(152)
None, by hand*
K
Drawn
3
(76)
Gear type
K,L
4
(102)
Heavy-duty gear type
1 (25.4)
K,L
Annealed
4
(102)
Gear type
7-1/2
(191)
None; by hand*
1-1/4 (32)
K,L
Annealed
9
(229)
None; by hand*
* When bending by hand, without the use of bending equipment, a circular wooden disc is
used. The radius of the disc should be about 1/4 to 1/2 inch less than the minimum bend
radius shown.
340
Installation Standard
For
TILE-LINED SHOWER RECEPTORS (and Replacements)
lAPMO IS 4-2003
FORWARD
This standard specification for the
installation of tile-lined shower receptors is
the result of extensive study and research by
the following:
Ceramic Tile Institute of America
Associated Tile Contractors of Southern
California, Inc.
Tile Layers Local No. 18 of I.U.B.A.C,
United States and Canada
Tile Helpers Local No. 18 of I.U.B.A.C, of
the United States and Canada
APPROVED CONSTRUCTION OF TILE-LINED SHOWER RECEPTORS
STANDARD SPECIFICATION FOR THE INSTALLATION OF
TILE-LINED SHOWER RECEPTORS
Receptor lining must extend 3
(76 mm) above top of finished
dam and outward on face of
rough jamb.
Finish height of dam to be at
least 2" (51 mm) above high
point of shower drain.
Receptor lining must extend
3" (76 mm) above top of
finished dam and outward on
face of rough jamb.
Fur out or notch studs to
receive lining.
Keep lining flush with face of
studs or furring.
Mortar setting bed with
approved waterproofing
additive.
See Section 2.5.
Receptor lining turned over dam
and thoroughly tacked outside.
No punctures less tiian 1 " (25.4
mm) above the finished dam or
threshold on the interior and top
of dam or threshold.
Receptor fining shall be pitched
not less than 1/4" per foot (20.8
mm/m) to weep holes in dratn.
For receptor lining see Section 4.2
Flange of approved type sub drain set
exactly level with sub floor with clamping
ring or other device to make tight
connection with receptor i'mlng
1024 (0.66m2) minimum floor area
finish floor to have minimum of 1/4"
(20.8 mm/m) and maximum of 1/2"
(41 .7 mm/m) pitch to drain per foot.
Minimum of 0.05 inch (1 .3 mm) thickness strainer
341
IS 4
UNIFORM PLUMBING CODE
1.0 SCOPE
1 .1 Installation and material of tile-lined shower
receptors shall comply with this standard
and the current edition of the Uniform
Plumbing Code [UPC]TM, published by the
International Association of Plumbing and
Mechanical Officials (lAPMO).
Note: The following sections of the Uniform
Plumbing Code shall apply.
412.1 Floor drains
412.5 Shower receptors
412.6 Shower receptor approval
412.7 Shower compartments
412.8 On-site built-up shower
412.9 Floors of public shower rooms
2.0 GENERAL REQUIREMENTS
2.1 Inspection of Work - All surfaces prepared
by others shall be inspected by the tile
installer before starting tile work and all
unsatisfactory conditions reported to the
Administrative Authority. Starting tile work
by the tile installer shall be considered as
acceptance of surfaces prepared by others.
2.2 Surface - All surfaces to receive tile work
shall be clean, structurally sound, and
conform in every way to the local building
code.
{Note: No tile work shall proceed until the
pan and drain construction has been
inspected and approved by the
Administrative Authority, where required.)
3.0 PRODUCT REQUIREMENTS
3.1 Materials
3.1.1 Tile Quality and Grade - Tile shall comply
with American National Standard
Specification for Ceramic Tile, A137.1
(equivalent to and incorporating U.S. Dept.
of Commerce Simplified Practice
Recommendation, R61-61 and Federal
Specification SS-T-308b, Tile, Floor, Wall,
and Trim Units, Ceramic), or CTI 69.5.
3.1 .2 Cement - Cement shall be portland cement
type I or type II, conforming to ASTM CI 50.
3.1.3 Sand - Sand shall be damp, clean and
graded ASTM C 778.
3.1 .4 Water - Water shall be potable.
3.1.5 Reinforcing shall be 2.5 lbs. per sq. yard
(1.1 kg per m2) or greater galvanized metal
lath conforming to ANSI A42.3 or 2 inches x
2 inches (51 mm x 51 mm), 16/16 gage or 3
inches x 3 inches (76 mm x 76 mm) mesh, 13
X 13 gage or 1-1/2 inches x 2 inches (38 mm
X 51 mm) mesh, 16 x 13 gage steel, wire
conforming to ASTM A 82 and A 185.
3.1.6 Asphalt shall conform to Federal
Specification SS-A-0666, Type Z, Grade 2,
Class A.
3.1.7 Plastic Roof Cement shall conform to
Federal Specifications SS-C-153.
3.1.8 Water Resistant Felt Membrane - The
water resistant felt membrane shall be at
least 15 lb. (6.8 kg) asphalt saturated felt
conforming to Type 1, Federal Specification
HH-F-191 (a).
3.1.9 Plastic Membrane shall comply with
applicable standards listed in Table 14-1 of
the UPC.
3.1.10 Other Membranes - Where the
Administrative Authority approves their use,
non-metallic sub-pans or linings or lead
sheets weighing not less than 4 lbs. per sq.
foot (191.5 Pa) and copper pans of at least No.
24 B & S gage (Brown & Sharp 0.0201 inches)
or greater in thickness may be used.
3.1.11 Waterproofing Admixture - The mortar
bed of the receptor shall be mixed with a
waterproof admixture approved by the
Administrative Authority in the amounts
allowed by such approval.
3.2 CURRENTLY APPROVED MORTAR
ADDITIVES
Anti-Hydro — 1 qt. (0.95 I) per sack of
cement.
Plastiment — 1 lb. (0.5 kg) of powder per
sack of cement.
Plastiment — 2 oz. (56.7 g) of fluid per sack of
cement.
Sika 3A — 1 qt. (0.95 I) per sack of cemient.
Suconem (Red Label) — 1 pint (0.47 I) per
sack of cement.
4.0 INSTALLATION REQUIREMENTS
4.1 Shower Drains - An approved type shower
floor drain with sub-drain shall be installed
with every such shower membrane. Flange
of each sub-drain shall be accurately set
exactly level with sloping sub-floor and
shall be equipped with a clamping ring or
other approved device to make a tight
connection between the membrane and the
sub-drain. The sub-drain shall have weep
holes into the waste line. The weep holes
located in the subdrain clamping ring shall
be protected from becoming clogged during
the placement of finish materials. The drain
shall be of such design that there will be not
342
TILE-LINED SHOWER RECEPTORS
IS 4
less than 2" (51 mm) depth from the top of
the sub-drain flange to top of the strainer.
Unless otherwise approved by the
Administrative Authority, drains shall be
located in the approximate center of the
shower area.
4.2 Sloping Sub-Floor and Shower
Membrane All lining materials shall be
pitched one quarter (1/4) inch per foot (20.8
mm/m) to weep holes in the sub-drain by
means of a smooth and solidly formed
sloping sub-base. All such lining materials
shall extend upward on the side walls and
rough jambs of the shower opening to a
point not less than three (3) inches (76 mm)
above the top of the finished dam or
threshold and shall extend outward over the
top of the rough threshold and be turned
over and fastened on the outside face of
both the rough threshold and the jambs.
4.2.1 Non-metallic shower sub-pans or linings
may be built-up on the job site of not less
than three (3) layers of standard grade
fifteen (15) pound (6.8 kg) asphalt
impregnated roofing felt. The bottom layer
shall be fitted to the formed sub-base and
each succeeding layer thoroughly hot-
mopped to that below, with hot asphalt
conforming to Fed. Spec. SS-A0666 T)rpe Z,
Grade 2, Class A on the basis of twenty (20)
pounds (9.1 kg) of asphalt per layer per
square. All corners shall be carefully fitted
and shall be made strong and water-tight by
folding or lapping, and each corner shall be
reinforced with suitable webbing hot-
mopped in place. All folds, laps and
reinforcing webbing shall extend at least
four (4) inches (102 mm) in all directions
from the corner and all webbing shall be of
approved type and mesh, producing a
tensile strength of not less than fifty (50)
pounds per square inch (344.5 kPa per
square meter) in either direction.
4.2.2 Non-metallic shower sub-pans or linings
may also consist of single or multi-layers of
other approved equivalent materials,
suitably reinforced and carefully fitted in
place on the job site, as elsewhere required
in this section according to manufacturer's
recommended installation procedures.
Where flexible plastic sheet membranes are
used, comers shall be carefully constructed
by folding or bonding of prefabricated
reinforcing corner. Joints in flexible plastic
sheeting shall be constructed with the
appropriate solvent bonding liquid, bodied
solvent cement or thermal welding.
4.2.3 Where lead and copper pans are used as
membranes, the installation shall be made in
similar manner as required for felt
membranes except the asphalt moppings,
and in addition the pans shall be insulated
from all concrete and mortar surfaces and
from all conducting substances other than
their connecting drain by 15 lb. (6.8 kg)
asphalt saturated felt or an approved
equivalent hot mopped to the lead or copper
pan. Joints in lead and copper pans shall not
be soldered, but shall be burned or silver
brazed respectively.
4.2.4 All linings shall be properly recessed and
fastened to approved backing so as not to
occupy the space required for the wall
covering and shall not be nailed or
perforated at any point which will be less
than one (1) inch (25.4 mm) above the
finished dam or threshold.
4.3 Tests. Upon installation, all linings shall be
tested for water tightness by being filled to
the top of the rough threshold with water
for a period of time sufficient to establish
their water tightness. (Usually twenty-four
(24) hours with no loss of water. See the
local Administrative Authority for exact
time limit.)
A test plug shall be so placed that both the
upper and under sides of the lining shall be
subjected to test at its point of contact with
the sub-drain. When the test plug is
removed, all of the test water shall drain out
by gravity through the weep holes. A ring of
non-absorbent material must be placed
around the weep holes to keep them open
when the finish materials are installed.
4.4 Receptor. Shower floor shall be of ceramic
tile set in portland cement mortar mixed in
the proportion of one (1) part portland
cement to four (4) parts of mortar sand by
volume and shall be provided with an
approved shower drain designed to make a
water-tight joint at the floor. The mortar
mixture shall be of such consistency that a
troweled surface readily assumes a smooth
screeded surface. All concrete mortar bases
shall be mixed with an approved
waterproofing admixture and properly
reinforced with 2.5 lbs. per square yard (1.1
kg per square m) or more galvanized metal
lath or 2 inches x 2 inches (51 mm x 51 mm),
16/16 gage or 3 inches x 3 inches (76 rrun x
343
IS 4
UNIFORM PLUMBING CODE
76 min) mesh, 13 x 13 gage or 1-1/2 inches x
2 inches (38 mm x 51 mm) mesh, 16 x 13
gage cold drawn welded steel wire fabric
located in the approximate center of the
mortar bed and extending at least 3 inches
(76 mm) at any point. The finished floor
shall be not less than 2 inches (51 mm)
measured from the top surface of the
membrane. The high point of the tile floor
shall be not less than 2 inches (51 mm) or
more than 9 inches (229 mm) below the top
of the finished dam and shall have a
n\inimun\ of 1/4 inch (6.4 mm/m) and a
maximum of 1/2 inch (19.1 mm/m) pitch
per foot toward the drain. Shower walls to a
minimum height of 3 inch (76 mm) and not
less than 1 inch (25.4 mm) above the
finished dam shall be lined with ceramic tile
set in Portland cement mortar.
4.5 Floors of public shower rooms shall have a
, non-skid surface and shall be drained in
such a manner that waste water from one
bather will not pass over areas occupied by
other bathers. Gutters in public or gang
shower rooms shall have rounded corners
for easy cleaning and shall be sloped not less
than two (2) percent toward drains. Drains
in such gutters shall be spaced not more
than eight (8) feet (2438 mm) from side walls
or more than sixteen (16) feet (4877 mm)
apart.
4.6 Shower walls, including shower walls over
bathtubs, shall be constructed of dense, non-
absorbent waterproof materials such as
ceramic tile set in portland cement mortar or
approved cementitious backer unit when no
materials are adversely affected by moisture
to a height of not less than six (6) feet (1829
mm) above the floor.
EXISTING TILE
MORTAR BED
SNIP PAPER
AND METAL LATH
FLASHING IN PLACE
CONTINUOUS CAULKING
FLASHING INSERTED
FLASHING IN PLACE
NEW LINING
Figure 2
ADOPTED: 1966
REVISED: 1977, 1982, 1990, 1992, 1996, 2003
344
Installation Standard
For
ABS BUILDING DRAIN, WASTE, AND VENT PIPE AND FITTINGS
lAPMO IS 5-2003
1.0 SCOPE
1 .1 This installation standard shall apply to ABS
building drain, waste and vent systems as
governed by the Uniform Plumbing Code.
Material Standard ASTM D 2661, "Standard
Specification of Acrylonitrile-Butadiene-
Styrene (ABS) Schedule 40 Plastic Drain,
Waste and Vent Pipe and Fittings," or
ASTM F 628, "Acrylonitrile-Butadiene-
Styrene (ABS) Schedule 40 Plastic, Drain,
Waste and Vent Pipe with a Cellular Core,"
shall form a part of this standard.
1.2 Installation, material and inspection shall
comply with the current edition of the
Uniform Plumbing Code [UPC]TM as
published by the International Association
of Plumbing and Mechanical Officials and
shall also comply with this standard.
The Building Official shall be consulted
about penetration of fire separations, height
and area or other limitations.
Note:
Note:
903.0 Materials (Venting)
903.4 Straining or Bending Pipe
1003.0 Traps Described
1101.3 Materials Uses
Table 14-1
Pipe and Fittings:
ASTM D 2661 D3311
ASTM D2122 F402
ASTM F628
ABBREVIATIONS
ASTM American Society for Testing and Materials
lAPMO International Association of Plumbing and
Mechanical Officials
UPC Uniform Plumbing Code
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Pipe
ABS pipe is furnished in straight lengths.
The pipe is black in color. The pipe wall is
the same thickness as that of Schedule 40
(IPS) standard steel pipe.
ABS pipe markings shall be in accordance
with D 2661 or F 628. [UPC 301.1.2]
2.1.2 Fittings
Fittings are black. Refer to Tables in ASTM
D2661 and D3311 for dimensions and
tolerances for pipe, fitting sockets, and
laying lengths.
ABS fitting markings shall be in accordance
with D 2661 or F 628. [UPC 301.1.2]
2.1.3 Solvent Cement
Solvent cement shall be as specified in
ASTM Standard D 2235. Solvent cement
labels shall be in accordance with D 2235.
2.2 Protection of Piping
2.2.1 Storage
Pipe and fittings should not be stored in
direct sunlight. However, exposure to direct
sunlight during normal construction periods
is not considered harmful. Pipe shall be
stored in such a manner as to prevent
sagging or bending. -
^Although referenced in this standard, some of the fittings shown in the standard are not acceptable under
the Uniform Plumbing Code.
The following sections of the Uniform
Plumbing Code apply.
101.4.1.
1 Repair and Alterations
103.5
Inspections
203.0
Definition ABS
301.1
Minimum Standards
311.8
Fittings Screwed
310.0
Workmanship
311.0
Prohibited Fittings and Practices
313.0
Protection of Piping, Materials, and
Structures
314.0
Hangers and Supports
316.1.1
Threaded Joints
316.1.6
Type of Joints - Solvent Cement
Plastic Pipe Joints
316.2.3
Plastic Pipe to Other Material
316.3.1
Flanged Fixture Connections
316.4
Prohibited Joints and Connections
316.0
Increasers and Reducers
701.0
Materials (Drainage)
704.4
Closet Flanges
707.1
Cleanout Fittings
345
IS 5
2.2.2
2.2.3
2.2.4
2.2.5
Expansion And Contraction
Thermal expansion and contraction of
plastic drain waste and vent systems shall
be taken into consideration. Thermal
expansion and contraction may be
controlled by several methods: offset,
expansion joints or restraints. Regardless of
method utilized, certain conditions shall be
met. 2.2.6
(a) Support, but do not rigidly restrain
piping at changes of direction.
(b) Do not anchor pipe rigidly in walls.
(c) Holes through framing members must
be adequately sized to allow for free
movement.
DWV installations with frequent changes in
direction will compensate for thermal
expansion and contraction. Expansion joints
may be utilized in vertical straight runs in
excess of thirty (30) feet (9144 mm) provided 2.3
they are installed per manufacturer's 2.3.1
installation instructions.
Except piping buried below ground,
horizontal and vertical piping should be
installed with restraint fittings or a
minimum twenty-four (24) inches (610 mm)
45° offset every thirty (30) feet (9144 mm). 2.3.2
Thermal expansion for installations subject
to temperature changes may be determined
from Table 1. The linear expansion shown is
independent of the diameter of the pipe.
[UPC 313.0]
Exposed Piping
Piping shall not be exposed to direct
sunlight. Exception: Vent piping through
roof. Plumbing vents through roof, exposed
to sunlight, shall be protected by water base
synthetic latex paints. Adequate support
shall be provided where ABS piping is
exposed to wind, snow, and ice loading.
Protection From Damage
Piping passing through wood studs or
plates shall be protected from puncture by
steel nail plates not less than 18 gauge.
Piping shall be protected from concrete form
oil. [UPC 313.9] 2.4
Antl-Freeze Protection 2.4.1
Anti-Freeze Protection - ABS pipe and traps
can be protected from freezing by the use of
one of the following solutions or mixtures:
(a) 4 quarts (3.8 liters) of water mixed with
5 quarts (4.8 liters) of glycerol
(b) 2-1/2 lbs. (1.1 kg) of magnesium
chloride dissolved in one gallon (3.8
liters) of water
UNIFORM PLUMBING CODE
(c) 3 lbs. (1.4 kg) of table salt dissolved in
one gallon (3.8 liters) of water.
The salt solutions are effective to
approximately 10°F (-12°C). If lower
temperatures are anticipated, the pipe
should be drained or the glycerol solution
should be used. [UPC 313.0]
Piping Installed in Fire Resistive
Construction
All piping penetrations of fire resistance
rated walls, partitions, floor, floors /ceiling
assem^blies, roof/ ceiling assemblies, or shaft
enclosures shall be protected in accordance
with the requirements of the Building Code,
lAPMO Installation Standards and Chapter
15 "Firestop Protection for DWV and
Stormwater Applications". [UPC 313.7]
Hangers and Supports
Abrasion
Hangers and straps shall not compress,
distort, cut, or abrade the piping and shall
allow free movement of pipe. Pipe exposed
to damage by sharp surfaces shall be
protected. [UPC 314.0]
Support
Support all piping at intervals of not more
than four (4) feet (1219 mm), at end of
branches, and at change of direction or
elevation. Supports shall allow free
movement, but shall restrict upward
movement of lateral runs so as not to create
reverse grade. Vertical piping shall be
supported at each story or floor level.
Alignment of vertical piping shall be
maintained between floors with the use of a
mid-story guide. Support trap arms in
excess of three (3) feet (914 mm) in length as
close as possible to the trap. Closet rings
shall be securely fastened with corrosive
resistant fasteners to the floor with the top
surface one-quarter (1/4) inch (6.4 mm)
above the finish floor. [UPC 314.0]
Traps
Connection to Traps
Traps shall be connected by means of listed
trap adapters.[UPC 1003.0]
346
ABS BUILDING DWV PIPE AND FITTINGS
IS 5
TABLE 1
Thermal Expansion Table
Chart Shows Length Changes in Inches vs. Degrees Temperature Change
Coefficient of Linear Expansion: e = 5.5 x 10'^ in/in °F
Length
(feet)
40°F
SOT
60°F
70T
80°F
90T
100°F
20
0.536
0.670
0.804
0.938
1.072
1.206
1.340
40
1.070
1.340
1.610
1.880
2.050
2.420
2.690
60
1.609
2.010
2.410
2.820
3.220
3.620
4.020
80
2.143
2.680
3.220
3.760
4.290
4.830
5.360
100
2.680
3.350
4.020
4.700
5.360
6.030
6.700
TABLE 1 (Metric)
Thermal Expansion Table
Chart Shows Length Changes in Millimeters vs. Degrees Temperature Change
Coefficient of Linear Expansion: e = 0.3 mm
-1.
mm
°C
Length
(mm)
4X
10°C
16°C
2rc
27X
32°C
38°C
6096
13.6
17.0
20.4
23.8
27.2
30.6
34.0
12192
27.2
34.0
40.8
47.8
52.1
61.5
68.3
18288
40.9
51.1
61.2
71.6
81.8
92.0
102.1
24384
54.4
68.1
81.8
95.5
110.0
122.7
136.1
30480
68.1
85.1
102.1
119.4
136.1
153.2
170.2
Example:
Highest Temperature expected
100°F
(38°C)
Lowest Temperature
I expected
50°F
(10°C)
-50^
tio°e)
Length of run - 60 feet (18288 nmi) from chart, read 2.010 inches (51 mm)
linear expansion that must be provided for.
2.5 Joints
2.5.1 Caulked Joints
Make connections or transitions to bell-and-
spigot cast iron soil pipe and fittings, and to
bell-and-spigot pipe and fittings of other
materials with listed mechanical
compression joints designed for this use, or
caulked joints made in an approved manner.
In caulking, pack the joint with oakum or
hemp and fill with molten lead to a depth of
not less than (1) inch (25.4 mm). Allow a
period of four (4) minutes for cooling,
following which, caulk the lead at the inside
and outside edges of the joint. Lead shall not
be overheated. Heat lead to melting point
only. [UPC 705.1]
Note: Caulked joints should be avoided if
possible.
2.5.2 Solvent Cement Joints
2.5.2.1 Selection. Solvent cement shall be
recommended for ABS by the manufacturer.
Follow manufacturer's recommendations
for types of solvent cement for such
conditions as temperature over 100°F (38°C),
or humidity over 60%. [UPC 316.1.6]
2.5.2.2 Handling (to maintain effectiveness).
Solvent cement containers no larger than 1
gallon (3.8 liters) should be used in the field
(to avoid thickening due to evaporation).
Keep container closed and in the shade
when not in use. Keep applicator
submerged in solvent cement between
applications. When solvent cement becomes
thicker, THROW IT AWAY. Solvent cement
shall NOT be thinned.
347
IS 5
UNIFORM PLUMBING CODE
2.5.2.3 Size of Applicator. Applicator should be
about one half the pipe diameter. Do not use
small applicator on large pipes. Ordinary
pure bristle paint brush or applicators
furnished with product are satisfactory.
2.5.2.4 Application. Solvent cement shall be
applied deliberately, but without delay (two
people may be needed to make large joints).
Use special care when temperature is over
100°F (38°C) or humidity is over 60%.
2.5.3 SAFETY REQUIREMENTS AND
PRECAUTIONS
2.5.3.1 General. Solvents contained in ABS
plastic pipe cements are classified as
airborne contaminants and flammable and
combustible liquids. Precautions listed in
this appendix should be followed to avoid
injury to personnel and the hazard of fire.
2.5.3.2 Safety Precautions. Prolonged breathing
of solvent vapors should be avoided. When
pipe and fittings are being joined in partially
enclosed areas, a ventilating device should
be used in such a manner to minimize the
entry of vapors into the breathing areas.
2.5.3.3 Solvent cements should be kept away
from all sources of ignition, heat, sparks
and open flame.
2.5.3.4 Containers for solvent cements should be
kept tightly closed except when the
cement is being used.
2.5.3.5 All rags and other materials used for
mopping up spills should be kept in a
safety waste receptacle which should be
emptied daily.
2.5.3.6 Most of the solvents used in ABS pipe
cements can be considered eye irritants
and contact with the eye should be
avoided for it may cause eye injury.
Proper eye protection and the use of
chemical goggles or face shields is
advisable where the possibility of
splashing exists in handling solvent
cements. In case of eye contact, flush with
plenty of water for 15 minutes and call a
physician immediately.
2.5.3.7 Repeated contact with the skin should be
avoided. Proper gloves impervious to and
unaffected by the solvents should be worn
when frequent contact with the skin is
likely. Application of the solvents or
solvent cements with rags and bare hand
is not recommended. Brushes and other
suitable applicators can be used
effectively for applying the solvent cement,
thus avoiding skin contact. In the event of
excessive contact, remove contaminated
clothing and wash skin with soap and
water.
Step 1 Cut pipe square with hand saw
and miter box, mechanical cut-off
saw, or tube cutter designed for
plastic.
Step 2 Ream inside and chamfer outside
of pipe (to elin\inate all burrs).
Step 3 Clean all dirt, moisture, and
grease from pipe and socket. Use
a clean, dry rag.
Step 4 Check dry fit of pipe in fitting.
Pipe should enter fitting socket
from 1/3 to 3/4 depth of socket.
Step 5 Apply a light coat of ABS solvent
cement to inside of socket using
straight outward strokes (to keep
excess solvent out of socket). This
is also to prevent solvent cement
damage to pipe. For loose fits,
apply a second coat of solvent
cement. Time is important at this
stage. See Section 2.5.2.4.
Step 6 While both the inside socket
surface and the outside surface of
the pipe are SOFT and WET with
solvent cement, forcefully bottom
the pipe in the socket, giving the
pipe a one-quarter turn, if
possible. The pipe must go to the
bottom of the socket.
Step 7 Hold the joint together imtil tight
(partial set).
Step 8 Wipe excess cement from the
pipe. A properly made joint will
normally show a bead around its
entire perimeter. Any gaps may
indicate insufficient cement or the
use of light bodied cement on
larger diameters where heavy
bodied cement should have been
used.
Step 9 The system shall not be tested
until the joints have cured (set) at
least as long as recommended by
the manufacturer.
2.5.4 Threaded Joints
Threads on iron pipe size (IPS) pipe and
fittings shall be standards listed in Table 14-
1. Threads on tubing shall be approved
types. Threads on plastic pipe shall be
factory cut or molded. Threaded plastic pipe
shall be Schedule 80 minimum wall
348
ABS BUILDING DWV PIPE AND FITTINGS IS 5
thickness. Tubing threads shall conform to
fine tubing thread standards. When a pipe
joint material is used, it shall be applied
only on male threads and such materials
shall be approved types, insoluble in water
and nontoxic. Cleanout plugs and caps shall
be lubricated with water-insoluble, non-
hardening material or tape. Only listed
thread tape or thread lubricants and sealants
specifically intended for use with plastics
shall be used on plastic threads.
Conventional pipe thread compounds,
putty, linseed oil base products, and
unknown lubricants and sealants shall not
be used on plastic threads. [UPC 316.1.1]
2.5.5 Special Joints
2.5.5.1 Plastic Pipe to Other Materials
When cormecting plastic pipe to other types
of piping, use only listed fittings and
adapters, designed for the specific transition
intended. [UPC 316.2.3]
2.6 Prohibited Joints and Connections
(a) Drainage system - Any fitting or
connection which has an enlargement,
chamber or recess with a ledge,
shoulder or reduction of pipe area, that
offers an obstruction to flow through the
drain is prohibited.
(b) No fitting or connection that offers
abnormal obstruction to flow shall be
used. The enlargement of a three (3)
inch (76 mm) closet bend or stub to four
(4) inches (102 mm) shall not be
considered an obstruction. [UPC 316.4]
ADOPTED: 1966
REVISED: 1971, 1974, 1975, 1976, 1977,
1981, 1982, 1983, 1987, 1989,
1990,1992,2003
349
IS 5 UNIFORM PLUMBING CODE
350
Installation Standard
For
HUBLESS CAST IRON SANITARY AND RAINWATER SYSTEMS
lAPMO IS 6-2003
1.0 SCOPE
1.1 This installation standard is for use with
listed systems of hubless cast iron pipe and
fittings, utilizing listed couplings.
1 .2 This standard shall serve to supplement any
existing applicable standards and
requirements of appropriate codes and laws
regulating use of hubless cast iron pipe and
fittings in building sewer, drainage, waste,
vent, and rainwater systems, and to provide
the necessary requirements for installation,
use and inspection of piping and fittings for
this purpose. This system may be used in
any location where cast iron pipe is
acceptable under the Uniform Plumbing
Code.
1.3 The provisions of this standard are not
intended to prevent the use of any alternate
material or method of construction,
provided it meets the requirements of the
standard.
Note: The following sections of the Uniform
Plumbing Code apply to this standard:
101.4.1.1
Repair and Alterations
301.1
Minimum Standards (Material)
310.0
Workmanship
311.0
Prohibited Fittings and Practices
313.0
Protection of Piping Materials
and Structures
314.0
Hangers and Supports
316.4
Prohibited Joints and Connections
317.0
Increasers and Reducers
Table 3-1
Hanger Rod Sizes
Table 3-2
Support Spacing
701.0
Materials (Drainage)
704.4
Closet Flanges
705.1
Type of Joints
705.3.2
Expansion Joints
707.14
Cleanout Plugs
712.2 and
712.3
Testing
Table 7-3
Sizing
Table 7-5
Sizing
903.0
Materials (Venting)
1003.0
Traps Described
Chapter 11:
Storm Drainage
1101.3 Materials Uses
1101.11 Roof Drainage
Table 14-1 Plumbing Material Standards
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
Hubless pipe, fittings and couplings shall be
manufactured in strict compliance with
appropriate standards acceptable to lAPMO.
[UPC 301.1]
2.2 Markings
2.2.1 All hubless system components shall be
clearly marked with the following:
(a) Manufacturer's name or manufacturer's
registered trademark; the markings
shall be adequate to readily identify the
maker or manufacturer to the end user
of the product;
(b) Products listed by lAPMO that are
covered by this standard shall be
labeled with the designated lAPMO
certification mark;
(c) Country of origin; and
(d) Any other markings required by law.
2.2.2 Pipe shall be legibly and continuously
marked along the full length of the barrel.
[UPC 301.1.2]
2.2.3 Markings on fittings shall be cast raised
letters and not be located in the W
dimension as found in the product standard.
With the exception of the fittings with
notations in the standards allowing for
optional positioning lugs fittings have a
raised lug. When properly positioned, the
gasket in other than wider body couplings
will rest against but will not cover the lug.
Gaskets for wider body couplings will cover
the lug. [UPC 301.1.2]
2.3 All installations shall be made so that the
components can be readily identified. When
laying hubless pipe in a ditch, the
identification shall be on the top side of the
pipe. When in walls, the identification shall
be on a side readily visible to the inspector.
351
IS 6
2.4
2.5
2.5.1
2.5.2
2.5.3
2.5.4
2.5.5
2.5.6
2.6
Workmanship
All piping systems shall be installed and
supported in a workmanlike manner. [UPC
310.0]
Hangers and Supports
Support and stability of all components of a
hubless cast iron sanitary and rainwater
system shall be given prime consideration.
[UPC 314.0]
Vertical hubless systems shall be supported
per Table 3-2 of the Uniform Plumbing
Code.
Horizontal hubless systems shall be
supported per Table 3-2 of the Uniform
Plumbing Code. Supports shall be adequate
to maintain alignment and prevent sagging
and shall be placed within eighteen (18)
inches (457 mm) of the joint.
Joints shall be supported at least at every
other joint except that when the developed
length between supports exceeds four (4)
feet (1219 mm) they shall be provided at
each joint. Supports shall also be provided
at each horizontal branch connection. Such
support shall be placed immediately
adjacent to the coupling.
Suspended lines shall be suitably braced to
prevent horizontal movement.
Closet bends, trap arms and similar
branches shall be secured against movement
in any direction.
Hubless systems, in the ground shall be laid
on a firm bed for its entire length except
where support is otherwise provided which
is adequate in the judgment of the
Administrative Authority. [UPC 314.3]
Vertical sections and their connecting
branches shall be adequately staked and
fastened to driven steel pipe or reinforcing
bars so as to remain stable while backfill is
placed or concrete is poured.
Joints
During installation assembly, hubless pipe
and fittings shall be inserted into the gasket
and firmly seated against a center stop.
Center stop ring or fittings shall not create
an enlargement chamber or recess with a
ledge, shoulder, or reduction of pipe area or
offer an obstruction to flow. In order to
provide a sound joint with field cut lengths
of pipe, the ends shall be cut square.
Coupling assemblies shall be properly
positioned and uniformly tightened to the
UNIFORM PLUMBING CODE
torque required by lAPMO listing. The use
of an adequate torque wrench
recommended by the manufacturer of the
coupling assemblies shall be used. [UPC
705.1]
2.6.1 Listed adapters designed for the specific
transition intended shall be used for the
intermembering transition of different
piping materials.
2.6.2 The connection of closet rings, floor and
shower drains, and similar "slip over" fittings
to hubless pipe and fittings and the connection
of hubless pipe and fittings to conventional
pipe hubs shall be accomplished by the use of
caulked lead joints, or other listed connections.
ADOPTED: 1966
REVISED: 1972, 1974, 1975, 1982, 1989, 1991,
1993,1995,2000,2003
352
Installation Standard
For
POLYETHYLENE (PE) COLD WATER BUILDING SUPPLY AND YARD PIPING
lAPMO IS 7-2003
1.0 SCOPE
1 .1 This standard shall govern the installation of
polyethylene (PE) cold water building
supply and yard piping. (See Section 604.1
of the Uniform Plumbing Code and Section
2.7 of this standard for allowable location
and pressure). Installation, material and
inspection shall comply with the current
edition of the Uniform Plumbing Code
[UPC]TM published by the International
Association of Plumbing and Mechanical
Officials, and shall also comply with this
standard.
Note: The following sections of the Uniform
Plumbing Code apply to polyethylene piping.
103.5.3 Testing of systems
218.0 Definition of PE
310.0 Workmanship
313.0 Protection of Piping, Materials, and
Structures
314.0 Supporting in the Ground
315.0 Backfilling
316.2.3 Cormection to Other Materials
Chapter 6 Water Distribution
609.0 Locations
609.1 Depth of Piping
609.4 Testing
Table 14-1 Fittings (and Fasteners) for Joining
PE Pipe, lAPMO PS 25
Plastic Insert Fittings for
Polyethylene (PE) Plastic Pipe.
ASTM D 2609
PE Pipe, ASTM D 2239
ABBREVIATIONS
ASTM American Society for Testing and
Materials
lAPMO International Association of Plumbing
and Mechanical Officials
NSF National Sanitation Foundation
PS Material and Property Standard
published by lAPMO
UPC Uniform Plumbing Code published by
lAPMO
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Material. Material shall conform to the
appropriate standard in Table 14-1. See
note ahead of Chapter 2 of this standard.
2.1 .2 Pipe. PE pipe is plastic and black.
2.1.3 Fittings. Fittings are copper alloy or
nylon barbed insert fittings.
2.2 Markings
2.2.1 Piping. PE pipe markings shall be in
accordance with D 2239. [UPC 301.1.2]
2.2.2 Fittings. PE fitting markings shall be in
accordance with D 2239. [UPC 301.1.2]
2.2.3 Bands. Bands shall be marked with at
least the following:
(a) Manufacturer's name or trademark;
(b) Model;
(c) Stainless steel. Series 300; and
(d) Bands listed by lAPMO that are
covered by this standard shall be
labeled with the UPC logo to show
compliance with this standard.
2.2.4 Position of Markings. The identifying
markings on pipe and fittings shall be
visible for inspection without moving
materials.
2.3 Protection of Piping
2.3.1 Storage. Unprotected pipe should not be
stored in direct sunlight. The pipe shall be
stored in a w^ay to protect it from
mechanical damage (slitting, puncturing,
etc.). [UPC 313.0]
2.3.2 Thermal Expansion. The pipe shall be
snaked in the trench bottom with enough
slack to provide for thermal expansion
and contraction. The normal slack created
by residual coiling is generally sufficient
for this purpose. If, however, the pipe has
been allowed to straighten before it is
placed in the trench, six (6) inches (152
mm) per one hundred (100) feet (30480
mm) of length shall be allowed for this
purpose.
353
IS 7
2.3.3
2.4
2.5
2.5.1
2.5.2
2.6
2.6.1
Exposed Piping. Vertical piping may
extend a maximum of twenty-four (24)
inches (610 mm) above grade when
located on the exterior of the building or
structure and protected from mechanical
damage to the satisfaction of the
Administrative Authority. Where
exposed to sunlight, the pipe shall be
wrapped with at least 0.040 in. (1.02 mm)
of tape.
Trenchiing and Cover. Trench bottoms
shall be uniformly graded and shall be of
either undisturbed soil or shall consist of a
layer or layers of compacted backfill so
that minimum settlement will take place.
[UPC 315.0]
Joints
Procedure. Polyethylene pipe joints shall
be made as follows (see Section 2.2.1):
Step 1. Pipe shall be cut square, using a
cutter designed for plastic pipe,
and chamfer ends to remove
sharp edges.
Step 2. Place two strap-type stainless
steel bands over the pipe.
Step 3. Check that fittings are properly
sized for pipe, as tubing fittings
are not of proper size.
Step 4. Force the end of the pipe over the
barbed insert fittings, making
contact with the fitting shoulder
(the end of the pipe may be
softened by placing in hot water).
Step 5. Position the clamps 180° apart
and tighten evenly, so as to make
a leak-proof joint. [UPC 316.1]
Other Joints. Polyethylene pipe shall not
be threaded. Joints made with adhesives
or "solvent cementing" techniques are
prohibited.
IVIaterials
Location. Polyethylene piping shall be
installed only outside the foundation of
any building or structure or parts thereof.
It shall be buried in the ground for its
entire length except vertical piping may
be extended above grade per Section
313.3. It shall not be installed within or
under any building or structure or mobile
home or commercial coach, or parts
thereof. The term "building or structure or
parts thereof" shall include structures
such as porches and steps, whether
UNIFORM PLUMBING CODE
covered or uncovered, roofed porte-
cocheres, roofed patios, carports, covered
walks, covered driveways, and similar
structures or appurtenances. [UPC 604.0]
2.6.2 Harmful Materials. Polyethylene that has
been in contact with gasoline, lubricating
oil, or aromatic compounds, shall not be
installed.
2.7 Installation
2.7.1 Pipe. Kinked pipe shall not be used. PE
pipe shall not be flared. [UPC 609.0]
2.7.2 Fittings. Compression type couplings
and fittings shall be used only when
installing one and one-half (1-1/2) inch
(38 mm) and larger pipe. Stiffeners that
extend beyond the clamp or nut shall not
be used. [UPC 609.0]
2.7.3 Bends. Changes in direction may be made
by bends. The installed radius of pipe
curvature shall be not less than thirty (30)
pipe diameters, or the coil radius when
bending with the coil. Coiled pipe shall not
be bent beyond straight. Bends shall not be
permitted closer than ten (10) pipe
diameters of any fitting or valve.
2.7.4 Maximum Working Pressure. Working
pressure shall not exceed 160 psi (1.10
mPa).
2.7.5 Identification. A label shall be fastened to
the main electric meter panel stating "This
structure has a non-metallic water
service".
2.8 Sizing
2.8.1 Piping shall be sized in accordance with
UPC Section 610.0. When UPC Appendix
A is applicable, use UPC Chart A-4
(Copper Tubing Type L). Flow velocity
shall not exceed 8 fps (2.4 m/s). [UPC
610.1]
ADOPTED: 1968
REVISED: 1969, 1971, 1972, 1973, 1975, 1978,
1981, 1982, 1983, 1989, 1990, 2003
354
Installation Standard
For
PVC COLD WATER BUILDING SUPPLY AND YARD PIPING
lAPMO IS 8-2003
1.0 SCOPE
1 .1 This standard shall govern the installation of
PVC piping (with solvent cemented or
elastomeric gasketed joints) in cold water
building supply and yard piping. (See
Section 2.6.1 and 2.7.2 for allowable location
and pressure.) Installation, material and
inspection shall comply with the current
edition of the Uniform Plumbing Code
[UPC]TM published by the International
Association of Plumbing and Mechanical
Officials, and shall also comply with this
standard.
Note: The following sections of the Uniform
Plumbing Code apply to PVC water piping.
218.0
310.0
313.0
314.0
315.0
316.1.6
316.2.3
Chapter 6
606.2
604.0
609.0
Chapter 14
ASTM
Definition of PVC
Workmanship
Protection of Piping, Materials and
Structures
Hangers and Supports
Trenching, Excavation, and Backfill
Solvent-Cement Plastic Pipe Joints
Plastic Pipe to Other Materials
Water Supply and Distribution
Use of Joints
Materials
Depth of Piping Installation, Testing,
Unions, and Location
American Society for Testing and
Materials
lAPMO International Association of Plumbing
and Mechanical Officials
NSF NSF International
UPC Uniform Plumbing Code published by
lAPMO
APPLICABLE STANDARDS
Type of PVC for Pipe and Fittings
PVC 1120 or 1220
Pipe
Bell-End Poly (vinyl chloride)
PVC Pipe
PVC Schedule 40
ASTM Standard
D1784
D2672
D1785
Type of PVC for Pipe and Fittings ASTM Standard
PVC Schedule 80 D1785
PVC 160 psi (1102.4 kPa) (SDR 26)
PVC200psi (1378 kPa) (SDR 21)
PVC 250 psi (1722.5 kPa) (SDR 17)
PVC 315 psi (2170.4 kPa) (SDR 13.5) D 2241
Fittings
Schedule 40 (Socket) D 2466
Schedule 80 (Socket) D 2467
Schedule 80 (Threaded) D 2464
Solvent Cement
PVC Solvent Cement D 2564
Primers
PVC Primers F 656
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
Material. Materials shall conform to the
appropriate standard in Table 14-1 of the
Uniform Plumbing Code. See note ahead of
Chapter 2 of this standard. [UPC 301.1]
2.2 Pipe and Fittings. Pipe and fittings are
manufactured from PVC plastic.
2.3 Markings
2.3.1 Pipe. PVC pipe markings shall be in
accordance with D 1785 or D 2241. [UPC
301.1.2]
2.3.2 Fittings. PVC fitting markings shall be in
accordance with D 2464 or D 2466 or D 2467.
[UPC 301.1.2]
*Note: Size and material designation may be omitted
on smaller fittings.
2.3.3 Solvent Cement. Solvent cement container
markings shall be in accordance with D
2564.
2.3.3.1 Color. Solvent cement shall not be purple in
color.
2.3.4 Primers. Primer container markings shall
be in accordance with F 656.
2.3.4.1 Color. Primer shall be purple.
2.3.4.2 Position of Markings. The identifying
markings on pipe and fittings shall be
visible for inspection without moving
materials.
2.4 Protection of Piping
2.4.1 Storage. Unprotected pipe should not be
stored in direct sunlight. The pipe shall be
355
IS 8
UNIFORM PLUMBING CODE
stored in a way to protect it from
mechanical damage (slitting, puncturing,
etc.). Exposure to sunlight during normal
construction periods is not harmful. PVC
solvent cements should be stored in a cool
place, except when actually in use at the job
site. The solvent cement manufacturer's
specific storage recommendations should be
followed. [UPC 313.0]
2.4.2 Alignment. Pipe and fittings shall be
aligned properly without strain.
2.4.3 Thermal Expansion. Pipe (except pipe
with elastomeric gasketed joints) shall be
"snaked" in the trench bottom with enough
slack, at least 6 inches (152.4 mm) per 100
feet (30480 mm), to compensate for thermal
expansion and contraction before stabilizing
piping. Stabilize piping by bringing it
approximately to operating temperature
before testing and backfilling by one of the
following methods:
(a) Shade backfill. Leave all joints
exposed so that they can be
examined during pressure test.
(b) Fill with water at operating
temperature.
(c) Allow to stand overnight.
2.4.4 Exposed Piping. Vertical piping may
extend a maximum of 24 in. (610 mm) above
grade when located on the exterior of the
building or structure and protected from
mechanical damage to the satisfaction of the
Administrative Authority. Where exposed
to sunlight, the pipe shall be wrapped with
at least 0.040 in. (1.0 mm) of tape or
otherwise protected from UV degradation.
2.5 Trenching, Cover and Backfill
2.5.1 Trenching and Cover. Trench bottoms
shall be uniformly graded and shall be of
either undisiturbed soil or shall consist of a
layer or layers of compacted backfill so that
minimum settlement will take place. [UPC
315.0]
2.5.2 Backfill. Selected backfill shall be used.
Tamp the backfill that is placed around the
pipe so as to provide firm continuous
support and proper compaction. Backfill at
least 12 inches (305 mm) over pipes, except
that joints shall be left exposed. After
inspection and pressure test, complete
backfill.
2.5.3 Elastomeric Joints. Backfill immediately
after installing pipe.
Note: This is to maintain equal spaces
within the joints for contraction and
expansion.
2.6 Joints
2.6.1 Solvent Cement Joints
2.6.1.1 Selection. Follow manufacturer's
recommendations for types of solvent
cement for such conditions as temperature
over 100°F (38°C), humidity over 60% or use
of Schedule 80 fittings. [UPC 316.0]
2.6.1.2 Handling (to maintain effectiveness).
Package solvent cement in containers no
larger than 1 quart (1 liter). Keep solvent
cement can closed and in the shade when not
in use. Keep applicator submerged in solvent
cement between applications. When solvent
cement becomes thicker, THROW IT AWAY.
Solvent cement shall NOT be thinned.
2.6.1.3 Size of Applicator. Applicator should be
about one half the pipe diameter. Do not use
small applicator on large pipes.
2.6.1.4 Primers. All solvent cement PVC joints
shall be made using a listed primer in
compliance with ASTM F 656 and as
specified in Section 316.1.6 of the UPC.
2.6.1.5 Application. Solvent cement shall be
applied deliberately, but without delay (two
men may be needed to make large joints).
Use special care when temperature is over
100°F (38°C) or humidity is over 60%.
2.6.1.6 Procedure
Note: Do not tal<e SHORT CUTS. Most
failures are caused by short cuts. DON'T
take a chance.
2.6.2 safety requirements and
precautions!
2.6.2.1 General. Solvents contained in PVC plastic
pipe cements are classified as airborne
contaminants and flammable and combustible
liquids. Precautions listed in this appendix
should be followed to avoid injury to personnel
and the hazard of fire.
2.6.2.2 Safety Precautions. Prolonged breathing of
solvent vapors should be avoided. When pipe
and fittings are being joined in partially
enclosed areas, a ventilating device should be
used in such a manner to minimize the entry
of vapors into the breathing areas.
2.6.2.3 Solvent cements should be kept away from all
sources of ignition, heat, sparks, and open
flame.
2.6.2.4 Containers for solvent cements should be
kept tightly closed except when the cement
is being used.
2.6.2.5 All rags and other materials used for
mopping up spills should be kept in a safety
waste receptacle which should be emptied
daily.
356
PVC COLD WATER BUILDING
SUPPLY AND YARD PIPING
2.6.2.6 Most of the solvents used in PVC pipe
cements can be considered eye irritants
and contact with the eye should be avoided
for it may cause eye injury. Proper eye
protection and the use of chemical goggles
or face shields is advisable where the
possibility of splashing exists in handling
solvent cements. In case of eye contact,
flush with plenty of water for 15 minutes and
call a physician immediately.
2.6.2.7 Repeated, contact with the skin should be
avoided. Proper gloves impervious to and
unaffected by the solvents should be worn
when frequent contact with the skin is likely.
Application of the solvents or solvent cements
with rags and bare hands is not recom-
mended. Brushes and other suitable
applicators can be used effectively for
applying the solvent cement, thus avoiding
skin contact. In the event of excessive
contact, remove contaminated clothing and
wash skin with soap and water.
CAUTION: Primers are toxic. Don't allow
them to touch skin. Suitable gloves
are advised.
Step 1. Cut pipe square with hand saw and
miter box, niechanical cut-off saw
or tube cutter designed for plastic.
Step 2. Ream and chamfer pipe (to
eUminate sharp edges, beads, and
all burrs).
Step 3. Clean all dirt, moisture and grease
from pipe and fitting socket. Use a
clean, dry rag.
Step 4. Check dry fit of pipe in fitting. Pipe
should enter fitting socket from 1/3
to 3/4 depth of socket.
Step 5. Soften inside socket surface by
applying an aggressive primer.
Step 6. Soften mating outside surface of
pipe to depth of socket by applying
a liberal coat of the (aggressive)
primer. Be sure entire surface is
softened.
Step 7. Again coat inside socket surface
with the (aggressive) primer. Then,
without delay, apply solvent
cement liberally to outside of pipe.
Use more than enough to fill any
gaps.
Step 8. Apply a light coat of PVC solvent
cement to inside of socket using
straight outward strokes (to keep
excess solvent out of socket). This is
also to prevent solvent cement damage
to pipe. For loose fits, apply a second
IS 8
coat of solvent cement. Time is
important at this stage. See Section
2.5.1.4.
Step 9. While both the inside socket surface
and the outside surface of the pipe
are SOFT and WET with solvent
cement, forcefully bottom the pipe
in the socket, giving the pipe a one-
quarter turn, if possible. The pipe
must go to the bottom of the socket.
Step 10. Hold the joint together until tight.
Step 11. Wipe excess cement from the pipe. A
properly made joint will normally
show a bead around its entire
perimeter. Any gaps may indicate
insufficient cement or the use of Ught
bodied cement on larger diameters
where heavy bodied cement should
have been used.
Step 12. Do not disturb joint for the
following periods:
30 minutes minimum at 60°F to
100°F (16°C to 38°C).
1 hour minimum at 40°F to 60°F
(4°C to 16°C).
2 hours minimum at 20°F to 40°F (-
7°C to 4°C).
4 hours minimum at 0°F to 20°F (-
18°C to -7°C).
Handle the newly assembled joints
carefully during these periods. If
gaps (step 11) or loose fits are
encountered in the system, double
these periods.
Step 13. The system shall not be pressurized
until the joints have cured (set) at
least as long as recommended by the
manufacturer. If manufacturer's
recommendation is not available, the
following cure times are required:
2.6.3 Threaded Joints. Joints shall be tightened
approximately 1/2 turn past hand tight,
using a strap wrench.
Caution: Handtight refers to number of
threads to reach handtight with metal pipe.
Pipe can be bottomed in small sizes of PVC
by hand pressure alone. Do not overtighten.
2.6.4 Elastomeric Gaslceted Joints, Procedure:
Step 1. For field cuts, cut end of pipe
square with handsaw and miter
box, mechanical saw or a tube
cutter designed for plastic.
Step 2. Ream and bevel end of pipe (unless
already done by manufacturer).
Step 3. If dirty, remove gasket, dean gasket and
groove and replace ring.
357
IS 8
UNIFORM PLUMBING CODE
Step 4. Mark pipe in a contrasting color to
indicate the proper insertion depth
as recommended by the manufac-
turer (unless already done by
manufacturer).
Step 5. Apply lubricant recommended by
pipe manufacturer to end of pipe. Do
not apply lubricant to gasket or the
groove unless otherwise specifically
recommended by the manufacturer.
Step 6. Insert pipe into fitting imtil mark on
pipe is even with fitting.
Note: This depth of insertion is
required to properly allow for thermal
expansion and contraction. During
joint assembly, the previously
installed length of pipe should be
held so that the existing joints are
not pushed together or pulled apart.
DO NOT USE METAL STRAPS,
CHAINS (OR THE LIKE) FOR
ASSEMBLY.
2.7 Material
2.7.1 Location. PVC piping shall be installed
only outside the foundation of any building
or structure or parts thereof. It shall be
buried in the ground for its entire length
except vertical piping may be extended
above grade per Section 2.4.4. It shall not be
installed within or under any building or
structure or mobile home or commercial
coach or parts thereof. The term "building or
structure or parts thereof" shall include
TABLE 1
IVIINIIVIUI\/I CURE TIIVIE, IN
TEST PRESSURE FOR
structures such as porches and steps,
whether roofed or not, roofed porte-
cocheres, roofed patios, carports, covered
walks, covered driveways and similar
structures or appurtenances. [UFC.604.0]
2.8 Installation, Testing, and Identification
2.8.1 Deflection. Elastomeric gasketed pipe may be
deflected in accordance with the manu-
facturer's recommendations provided that it
shall not be permanently staked or blocked to
maintain this deflection. [UPC 609.0]
2.8.2 Maximum Working Pressure. Maximum
working pressure shall be as follows (see
chart on following page).
2.8.3 Saddles. PVC pressure pipe saddles are
limited to underground use outside the
building. The branch of the saddle shall be a
minimum of two pipe sizes smaller than the
main. Saddles shall be installed as required
by their listings.
2.8.4 Thrust Blocking. In lines with rubber
gasketed joints, thrust blocks shall be
installed at all:
(a) Changes in direction, as at tees and bends
(b) Changes in size, as at reducers
(c) Stops, as at dead ends
(d) Valves, where thrusts may be expected.
Thrust block sizes shall be based on the
maximum line pressure, pipe size and kind
of soil. Refer to Table 2 for thrust at fittings
for a pressure of 100 psi (689 kPa).
HOURS*
PIPE
Sizes 1/2"
(12.7 mm)
to 1-1/4"
(32 mm)
Sizes 1-1/2" to 3"
(38 mm) (76 mm)
Sizes 3-1/2" to 8"
(89 mm) (203 mm)
Temperature
Range
During
Cure
Period
Up to
180 psi
(1240.2
kPa)
Above 180
to 370 psi
(1240.2 to
2549.3 kPa)
Up to
180 psi
(1240.2
kPa)
Above 180
to 315 psi
(1240.2 to
2170.4 kPa)
Up to
180 psi
(1240.2
kPa)
Above 180
to 315 psi
(1240.2 to
2170.4 kPa)
60°F-100°F
(16°C-38°C)
Ihr
6hr
2hr
12 hr
6hr
24 hr
40°F-60°F
(4°C-16°C)
2hr
12 hr
4hr
24 hr
12 hr
48 hr
10°F-40°F
(-12°C+4°C)
8hr
48 hr
16 hr
96 hr
48 hr
8 days
*If gaps or loose fits are encountered in the system, double these cure times.
358
PVC COLD WATER BUILDING
SUPPLY AND YARD PIPING
TABLE 2
THRUST AT FITTINGS IN POUNDS AT 100 psi
Pipe Size
90°
45°
22-1/2°
Dead Ends
Inches
Bends
Bends
Bends
and Tees
1-1/2
415
225
115
295
2
645
350
180
455
2-1/2
935
510
260
660
3
1395
755
385
985
3-1/2
1780
962
495
1260
4
2295
1245
635
1620
5
3500
1900
975
2490
6
4950
2710
1385
3550
8
8300
4500
2290
5860
10
12,800
6900
3540
9050
12
18,100
9800
5000
12,800
TABLE 3
THRUST AT FITTINGS IN PASCALS AT
689 kPa OF WATER PRESSURE
Example for Table 2:
For a pressure of 150 psi (1033.5 kPa) on a
4 inch (102 mm) tee. Table 2 indicates
1620 pounds (7209 N) for 100 psi (689
kPa). Therefore, total thrust for 150 psi
(1033.5 kPa) will equal 1-1/2 times 1620
poimds (7209 N) for a total thrust of 2430
poimds (10810 N).
To determine the bearing area of thrust
blocks, refer to Table 4 for the safe
bearing load of the soil and divide the
total thrust by this safe bearing load.
TABLE 4
SAFE BEARING LOADS OF VARIOUS SOILS
Safe Bearing Load
Soil Lbs./sq. ft.
kPa
Mulch, Peat, etc.
Soft Clay
1000
6890
Sand
2000
13,780
Sand and Gravel
3000
20,670
Sand and Gravel Cement
with Clay
4000
27,360
Hard Shale
10,000
68,900
Example:
2.9
2.9.1
2.9.2
Pipe Size
90°
45°
22-1/2°
Dead Ends
mm
Bends
Bends
Bends
and Tees
2.9.3
38
1846.8
1001.3
511.8
1312.8
51
2870.3
1557.5
801.0
2024.8
64
4160.8
2269.5
1157.0
3937.0
76
6207.8
3359.8
1713.3
4383.3
2.10
89
7921.0
4280.9
2202.8
5607.0
2.10.1
102
10,212.8
5540.3
2815.8
7209.0
127
15,575.0
8455.0
4338.8
11,080.5
152
22,027.5
12,059.5
6163.3
15,797.5
203
36,935.0
20,025.0
10,190.5
26,077.0
254
56,960.0
30,705.0
15,753.0
40,272.5
305
80,545.0
43,610.0
22,250.0
56,960.0
18 8
Assume a 4000 pound (17,800 N) total
thrust was computed. The soil condition
is sand. The required bearing area of the
thrust block is 4,000 lbs. (17,800 N)
divided by 2000 lbs. (13, 780 kPa) or 2
square feet (0. 19 rrf).
Testing
Rubber Gasketed Joints. Properly
sized thrust blocks, either permanent or
temporary, shall be installed at ail
required points before testing. See
Section 2.8.4. When concrete thrust
blocks are installed, wait at least 24
hours before pressure testing.
Solvent Cement Joints. The entire
system shall be purged before testing to
eliminate all solvent cement vapors and
air.
CAUTION: Water test only.
Identification. A label shall be fastened
to the main electrical meter panel
stating, "This structure has a
nonmetallic water service".
Sizing
Piping shall be sized in accordance with
UPC Section 610.0. When UPC
Appendix A is applicable, use UPC
Chart A-5 (Fairly smooth). Flow
velocity shall not exceed 8 fps (2.4 m/s).
[UPC 610.0]
This standard is a combination of sections from the
previous standards IS 8 and IS 14. IS 8 was originally
adopted in 1968 and revised in 1971, 1972, 1973, and
1975. IS 14 was originally adopted in 1972 and
revised in 1975. Upon adoption of this rewrite, IS 14
was deleted.
Rewrite ratified by membership: 1978
Revised: 1980, 1981, 1984, 1986, 1989, 1991,
1992,1995,2003
^ Appendix XI, Safety Requirements and Precautions from
ASTM D 2564 Solvent Cements for Poly (Vinyl Chloride)
(PVC) Plastic Pipe and Fittings is reprinted with permission
from the American Society for Testing and Materials, 1916
Race Street, Philadelphia, PA 19103, copyright.
359
IS 8
UNIFORM PLUMBING CODE
TABLE 5
Fittings
Schedule
Sizes 1
Maximum
Pipe
Working Pressure
160 psi (SDR 26)
40
l/2"thru8"incL
160 psi - 1102.4 kPa
(1102.4 kPa)
(12.7 mm - 203 mm)
80
l/2"thru8"incL
(12.7 mm - 203 mm)
160 psi- 1102.4 kPa
200 psi (SDR 21)
40
l/2"thru4"incL
200 psi - 1378 kPa
(1378 kPa)
(12.7 mm - 102 mm)
80
l/2"thru8"incL
(12.7 mm - 203 mm)
200 psi - 1378 kPa
250 psi (SDR 17)
40
l/2"thru3"incL
250 psi - 1722.5 kPa
(1722.5 kPa)
(12.7 mm - 76 mm)
80
1/2" thru 8" incL
(12.7 mm - 203 mm)
250 psi - 1722.5 kPa
315 psi (SDR 13.5)
40
1/2" thru 1-1/2" incl.
315 psi - 2170.4 kPa
(2170.4 kPa)
(12.7 mm - 38 mm)
80
1/2" thru 4" incl
(12.7 mm - 102 mm)
315 psi - 2170.4 kPa
Schedule 40
40
1/2" thru 1-1/2" incl
320 psi - 2204.8 kPa
80
(12.7 mm - 38 mm)
40
2" thru 4" incl
220 psi - 1515.8 kPa
80
(51 mm - 102 mm)
40
5" thru 8" incl.
(127 rmn - 203 mm)
160 psi - 1102.4 kPa
Schedule 80
40
1/2" thru 1-1/2" ii\cL
(12.7 mm - 38 mm)
320 psi - 2204.8 kPa
40
2" thru 4" incl.
(51mm - 102 mm)
220 psi - 1515.8 kPa
40
5" thru 8" incl.
(127 mm - 203 mm)
160 psi - 1102.4 kPa
80
l/2"thru4"incL
(12.7 mm - 102 nrnr)
320 psi - 2204.8 kPa
80
5" thru 8" incl.
(127 mm - 203 mm)
250 psi - 1722.5 kPa
360
PVC COLD WATER BUILDING
SUPPLY AND YARD PIPING
LOCATION OF THRUST BLOCKS
(Standard and metric combined)
A Comparison of Tlirust-Blocl< Areas
IS 8
'M*UiirtrrtLi.ttalir»iiii*ii<iif
Figure 1
361
IS 8
UNIFORM PLUMBING CODE
16 sq. ft.
(1.49 m2)
6" Class 150 (152 mm)
10" Class 150 (254 mm)
Figure 2
362
Installation Standard
For
PVC BUILDING DRAIN, WASTE AND VENT PIPE AND FITTINGS
lAPMO IS 9-2003
1.0 SCOPE
1.1 This installation standard shall apply to
PVC building drain, waste, and vent
systems as governed by the Uniform
Plumbing Code. Material Standard ASTM
D2665, "Standard Specification for Poly
(Vinyl Chloride) (PVC) Plastic Drain, Waste
and Vent Pipe and Fittings", shall form part
of this installation standard.
1.2 Installation, material and inspection shall
comply with the current edition of the
Uniform Plumbing Code [UPC]™
published by the International Association
of Plumbing and Mechanical Officials and
shall also comply with this standard.
Note: The Building Official shall be consulted about
penetration of fire separations, height and
area, or other limitations.
Note: The following sections of the Uniform
Plumbing Code apply.
704.4 Closet Flanges
707.1 Cleanout Fittings
903.0 Materials (Venting)
903.4 Straining or Bending Pipe
1003.0 Traps Described
1101.3 Materials Uses
Table 14-1 Pipe and Fittings
ASTM D 2665 D 2122
ASTM D 3311^
ABBREVIATIONS
ASTM American Society for Testing and Materials
lAPMO International Association of Plumbing and
Mechanical Officials
UPC Uniform Plumbing Code
2.0
2.1
2.1.1
2.1.2
01.4.1.1
Repair and Alterations
103.5
Inspections
2.1.3
103.5.3
Testing of Systems
218.0
Definition PVC
301.1
Minimum Standards
2.1.3.1
311.8
Screwed Fittings
2.1.4
310.0
Workmanship
311.0
Prohibited Fittings and
Practices
2.1.4.1
313.0
Protection of Piping,
2.2
Materials and Structures
2.2.1
314.0
Hangers and Supports
316.1.6
Type of Joints - Solvent
Cement Plastic Pipe Joints
316.2
Special Joints
316.3
Flanged Fixture Connections
316.4
Prohibited Joints and
Connections
317.0
Increasers and Reducers
701.0
Materials (Drainage)
PRODUCT REQUIREMENTS
Minimum Standards
Pipe. PVC pipe markings shall be in
accordance with D 2665.^ [UPC 301.1.2]
Fittings. PVC fitting markings shall be in
accordance with D 2665 or D 3311. [UPC
301.1.2]
Solvent Cement. Solvent cement label
markings shall be in accordance with D
2564.
Solvent cements shall not be purple in color.
Primers. Primer container markings shall
be in accordance with F 656.
Primer shall be purple.
Workmanship
Alignment
All piping systems components shall be
aligned properly without strain. Pipe shall
not be bent or pulled into position. Vertical
piping shall be maintained in straight
alignment between floors with midstory
guides.
Pipe and fittings shall be so positioned that
identifying markings shall be readily visible
for inspection. [UPC 310.0]
^ Although referenced in this standard, some of the fittings shown in the standard are not acceptable under the Uniform Plumbing
Code.
^ It is common practice to dual mark Schedule 40 DWV and potable water piping in which compliance with each applicable
standard is met.
363
IS 9
UNIFORM PLUMBING CODE
2.3 Protection of Piping
2.3.1 Storage
Pipe and fittings should not be stored in
direct sunlight; however, exposure to
sunlight during normal construction periods
is not considered harmful. Pipe shall be
stored in such a manner as to prevent
sagging or bending. [UPC 313.0]
2.3.2 Expansion and Contraction
Thermal expansion and contraction of
plastic drain waste and vent systems shall
be taken into consideration. Thermal
expansion and contraction may be
controlled by several methods: offset,
expansion joints, or restraints.
Regardless of method utilized, certain
conditions shall be met:
(a) Support, but do not rigidly restrain
piping at changes of direction.
(b) Do not anchor pipe rigidly in walls.
(c) Holes through framing members must
be adequately sized to allow for free
movement.
DWV installation with frequent changes in
direction will compensate for thermal
expansion and contraction.
Expansion joints may be utilized in vertical
straight runs in excess of 30 feet (9144 mm)
provided they are installed per
manufacturer's installation instructions.
Except piping buried below ground,
horizontal and vertical piping should be
installed with restraint fittings or a
minimum of 24 inches (610 mm) 45° offset
every 30 feet (9144 mm). Thermal expansion
for installation subject to temperature
changes may be determined from Table 3-1.
The linear expansion shown is independent
of the diameter of the pipe.
2.3.3 Exposed Piping
Piping shall not be exposed to direct
sunlight. Exception: Vent piping through
roof. Plumbing vents through roof, exposed
to sunlight, shall be protected by water base
synthetic latex paints.
Adequate support shall be provided where
PVC piping is exposed to wind, snow and
ice loading.
2.3.4 Protection from Damage
Piping passing through wood studs or
plates shall be protected from puncture by
minimum 1/16 inch (1.6 mm) thick steel
plate.
Piping shall be protected from concrete
form oil.
2.3.5 Anti-Freeze Protection
PVC pipe and traps can be protected from
freezing by the use of one of the following
solutions of mixtures:
(a) 4 quarts (3.8 liters) of water mixed with
5 quarts (4.8 liters) of glycerol
(b) 2-1/2 lbs. (1.1 kg) of magnesium
chloride dissolved in one (1) gallon (3.8
liters) of water
(c) 3 lbs. (1.4 kg) of table salt dissolved in
one (1) gallon (3.8 liters) of water.
The salt solutions are effective to
approximately 10°F (-12°C). If lower
temperatures are anticipated, the pipe
should be drained or the glycerol solution
should be used.
2.4 Piping Installed in Fire Resistive
Construction
Where piping is installed and penetrates
required fire resistive construction, the fire
resistive integrity of the construction shall
be as required by the Administrative
Authority, or when not established by the
Building Code, by qualified testing methods
approved by the Administrative Authority.
Approval shall be obtained prior to
installing any such piping.
2.5.0 Hangers and Supports
2.5.1 Abrasion
Hangers and straps shall not compress,
distort, cut, or abrade the piping and shall
allow free movement of pipe. Pipe, exposed
to damage by sharp surfaces, shall be
protected. [UPC 314.0]
2.5.2 Support
Support all horizontal piping at intervals of
not more than four (4) feet (1219 mm), at
end of branches, and at change of direction
or elevation. Supports shall allow free
movement, but shall restrict upward
movement of lateral runs so as not to create
reverse grade. Vertical piping shall be
supported at each story or floor level.
Alignment of vertical piping shall be
maintained between floors with the use of a
mid-story guide. Support trap arms in
excess of three (3) feet (915 mm) in length as
close as possible to the trap. Closet flanges
shall be securely fastened with corrosive
resistant fasteners to the floor with top
surface one-quarter (1/4) inch (6.4 mm)
above finish floor.
364
PVC BUILDING DWV PIPE AND FITTINGS
IS 9
TABLE 1
PVC-DWV TYPE I
THERMAL EXPANSION TABLE
Chart Shows Length Change in Inches
vs. Degrees Temperature Change
Coefficient of Linear Expansion: e = 2.9 x lO'^ in/in °F
Length
(feet)
40T
SOT
60T
70°F
SOT
SOT
100T
20
0.278
0.348
0.418
0.487
0.557
0.626
0.696
40
0.557
0.696
0.835
0.974
1.114
1.235
1.392
60
0.835
1.044
1.253
1.462
1.670
1.879
2.088
80
1.134
1.392
1.670
1.949
2.227
2.506
2.784
100
1.392
1.740
2.088
2.436
2.784
3.132
3.480
TABLE 1 (Metric)
PVC-DWV TYPE I
THERMAL EXPANSION TABLE
Chart Shows Length Change in Millimeters
vs. Degrees Temiperature Change
Coefficient of Linear Expansion: o.2 mm
mm
°C
Length
(mm)
4X
10X
16°C
2rc
2TC
32°C
38°C
6096
7.1
8.8
10.6
12.4
14.2
15.9
17.7
12192
14.2
17.7
21.2
24.7
28.3
31.4
35.4
18288
21.2
26.5
31.8
37.1
42.4
47.7
53.0
24384
28.8
35.4
42.4
49.5
56.6
63.7
70.7
30480
35.4
44.2
53.0
61.9
70.7
79.6
88.4
Example:
Highest temperature expected 100°F (38°C)
Lowest temperature expected 50° F (10°C)
-50^(1O°C)-
Length of run - 60 feet (18288 mm) from chart, read 1.044 inches (26.5 mm)
linear expansion that must be provided for.
2.6 Traps
2.6.1 Connection to Traps
Traps shall be connected by means of listed
trap adapters. [UPC 1003.0]
2.7 Joints
2.7.1 Caulked Joints
Make connections or transitions to bell-and-
spigot cast iron soil pipe fittings, and to bell-
and-spigot pipe and fittings of other
materials with listed mechanical
compression joints designed for this use, or
caulked joints made in an approved manner.
In caulking, pack the joint with oakum or
hemp and fill with molten lead to a depth of
not less than one (1) inch (25.4 mm). Allow a
period of four (4) minutes for cooling.
following which, caulk the lead at the inside
and outside edges of the joint. Lead shall not
be overheated. [UPC 705.1.1]
2.7.2 Solvent Cement Joints
(Additional information is available in
ASTM D2855.)
2.7.3 Selection. Follow manufacturer's recom-
mendations for type of solvent cement for
such conditions as temperature over 100°F
(38°C), or humidity over 60%.
2.7.4 Handling (to maintain effectiveness).
Solvent cement and primer containers no
larger than 1 quart (1 liter) should be used in
the field (to avoid thickening due to
evaporation). Keep containers closed and in
the shade when not in use. Keep applicator
365
IS 9
UNIFORM PLUMBING CODE
2.7.6
2.7.7
submerged in solvent cement between
applications. When solvent cement becomes
thicker, THROW IT AWAY. Solvent cement
shall NOT be thinned.
2.7.5 Size of Applicator. Applicator should be
about one-half the pipe diameter. Do not use
small applicator on large pipes. Ordinary
pure bristle paint brushes or applicators
furnished with product are satisfactory.
[UPC 316.1.6]
Primers. A listed primer in compliance
with ASTM F 656 shall be used on all PVC
DWV joints.
Application. Solvent cement and primer
shall be applied deliberately, but without
delay (two men may be needed to make
large joints). Use special care when
temperature is over 100°F (38°C) or
humidity is over 60%.
2.7.8 SAFETY REQUIREMENTS AND
PRECAUTIONS
2.7.8.1 General. Solvents contained in PVC plastic
pipe cements are classified as airborne
contaminants and flammable and
combustible liquids. Precautions listed in
this appendix should be followed to avoid
injury to personnel and the hazard of fire.
2.7.8.2 Safety Precautions. Prolonged breathing
of solvent vapors should be avoided. When
pipe and fittings are being joined in partially
enclosed areas, a ventilating device should
be used in such a manner to minimize the
entry of vapors into the breathing areas.
2.7.8.3 Solvent cements should be kept away from
all sources of ignition, heat, sparks, and
open flame.
2.7.8.4 Containers for solvent cements should be
kept tightly closed except when the cement
is being used.
2.7.8.5 All rags and other materials used for
mopping up spills should be kept in a safety
waste receptacle which should be emptied
daily.
2.7.8.6 Most of the solvents used in PVC pipe
cements can be considered eye irritants and
contact with the eye should be avoided for it
may cause eye injury. Proper eye protection
and the use of chemical goggles or face
shields is advisable where the possibility of
splashing exists in handling solvent
cements. In case of eye contact, flush with
plenty of water for 15 minutes and call a
physician immediately.
2.7.8.7 Repeated contact with the skin should be
avoided. Proper gloves impervious to and
unaffected by the solvents should be worn
when frequent contact with the skin is likely.
Application of the solvents or solvent
cements with rags and bare hand not
recommended. Brushes and other suitable
applicators can be used effectively for
applying the solvent cement, thus avoiding
skin contact. In the event of excessive
contact, remove contaminated clothing and
wash skin with soap and water.
Step 1 Cut pipe square with hand saw and
miter box, mechanical cut-off saw
or tube cutter designed for plastic.
Step 2 Ream inside and chamfer outside of
pipe (to eliminate all burrs).
Step 3 Clean all dirt, moisture and grease
from pipe and socket. Use a clean,
dry rag.
Step 4 Check dry fit of pipe in fitting. Pipe
should enter fitting socket from 1/3
to 3/4 depth of socket.
Step 5 Soften inside socket surface by
applying an aggressive primer.
Step 6 Soften mating outside surface of
pipe to depth of socket by applying
a liberal coat of the (aggressive)
primer. Be sure the entire surface is
softened.
Step 7 Again coat inside socket surface
with the (aggressive) primer. Then,
without delay, apply solvent
cement liberally to outside of pipe.
Use more than enough to fill any
gaps.
Step 8 Apply a light coat of PVC solvent
cement to inside of socket using
straight outward strokes (to keep
excess solvent out of socket). This
is also to prevent solvent cement
damage to pipe. For loose fits,
apply a second coat of solvent
cement. Time is important at this
stage. See Section 2.7.6.
Step 9 While both the inside socket surface
and the outside surface of the pipe
are SOFT and WET with solvent
cement, forcefully bottom the pipe
in the socket, giving the pipe a one-
quarter turn, if possible. The pipe
must go to the bottom of the socket.
Step 10 Hold the joint together until tight.
(Partial set).
Step 11 Wipe excess cement from the pipe.
A properly made joint will
normally show a bead around its
entire perimeter. Any gaps may
366
PVC BUILDING DWV PIPE AND FITTINGS IS 9
indicate insufficient cement or the
use of light bodied cement on larger
diameters where heavy bodied
cement should have been used.
Step 12 The system shall not be tested until
the joints have cured (set) at least as
long as recommended by the
manufacturer.
2.7.9 Threaded Joints
Listed adapter fittings shall be used for the
transition to threaded connections. No
threaded PVC female fitting(s) or joint(s)
shall be located in a non-accessible location.
The joint between the PVC pipe and adapter
fittings shall be of the solvent cement type.
Only listed thread tape or thread lubricant,
specifically intended for use with plastics,
shall be used. Conventional pipe thread
compounds, putty, linseed oil base products,
and unknown mixtures shall not be used.
Pipe and fittings which have come in contact
with the above non-approved mixtures shall
be removed and replaced with new
materials.
Where a threaded joint is made, obtain
tightness by maximum hand tightening plus
additional tightening with a strapwrench
not to exceed one full turn.
2.7.10 Special Joints
2.7.10.1 Connection to Non-Plastic Pipe
When cormecting plastic pipe to other types
of piping, use listed fittings and adapters
designed for the specific use intended. [UPC
316.2]
2.7.1 1 Prohibited Joints and Connections
(a) Drainage System - Any fitting or
connection which has an enlargement,
chamber or recess with a ledge,
shoulder, or reduction of pipe area, that
offers an obstruction to flow through
the drain is prohibited.
(b) No fitting or connection that offers
abnormal obstruction to flow shall be
used. The enlargement of a three (3)
inch (76 mm) closet bend or stub to four
(4) inches (102 mm) shall not be
considered an obstruction. [UPC 316.4]
ADOPTED: 1968
REVISED: 1971, 1974, 1975, 1976, 1977, 1981,
1982, 1983, 1987, 1989, 1990, 1991,
1992,1995,2003
367
IS 9 UNIFORM PLUMBING CODE
368
Installation Standard
For
ABS SEWER PIPE AND FITTINGS
I APMO IS 11-2003
1.0 SCOPE
1 .1 This Installation Standard shall apply to ABS,
Building Sewer Pipe and Fittings as governed
by the Uniform Plumbing Code. Material
Standard ASTM D 2751, Standard
Specification for Acrylonitrile-Butadiene-
Styrene (ABS) Sewer Pipe and Fittings shall
form part of this Installation Standard.
Materials shall be limited to building sewers
receiving domestic sewage excluding special
and industrial waste.
Note: The following sections of the Uniform
Plumbing Code apply.
103.5
Inspection and Testing
101.4.1.1
Repairs and Alterations
203.0
Definition ABS
206.0
Domestic Sewage
301.1
Minimum Standards
310.0
Workmanship
312.0
Independent Systen\s
313.3 and 313.4
Protection of Piping, Materials,
2.3
and Structures
2.3.1
314.0
Hangers and Supports
315.0
Trenching, Excavation, and
Backfill
316.1
Types of Joint
317.0
Increasers / Reducers
705.1.1
Caulked Joints
705.1.7
Elastomeric Gasketed and
Rubber-Ring Joints
2.4
713.0
Sewer Required
2.4.1
715.0
Building Sewer Materials
718.0
Grade, Support, and Protection
of Building Sewers
719.0
Cleanouts
.720.0
Sewer and Water Pipes
723.0
Building Sewer Test
Table 14-1
ASTM D2751'
O IT
1 Although this standard is referenced in Table 14-1, some of
the tube or fittings shown in the standard are not acceptable
for use under the Uniform Plumbing Code.
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Pipe. ABS pipe is furnished in straight
lengths. Refer to Tables in D 2751 for
dimensions and tolerances for pipe and pipe
sockets.
ABS pipe markings shall be in accordance
with D 2751. [UPC 301.1.2]
2.1.2 Fittings. Refer to Tables in ASTM D 2751
for dimensions and tolerances for fitting
sockets, spigots, and laying lengths.
ABS fitting markings shall be in accordance
with D 2751. [UPC 301.1.2]
2.1.3 Solvent Cement. Solvent cement shall be
as specified in ASTM Standard D 2235.
Solvent cement label markings shall be in
accordance with D 2235.
2.2 Workmanship
All piping system components shall be
aligned properly without strain. Pipe shall
not be bent or pulled into position after
being solvent cemented. Pipe and fittings
shall be so positioned that identifying
markings shall be readily visible for
inspection. [UPC 310.0]
Protection of Piping
Storage
Pipe and fittings should not be stored for
long periods in direct sunlight. However,
exposure to direct sunlight during normal
construction periods is not harmful. Pipe
shall be stored in such a manner as to
prevent sagging or bending.
Trenching, Excavation, and Backfill
Trenching
The width of the trench at any point below
the top of the pipe should not be greater
than necessary to provide adequate room
for joining the pipe and compacting the side
fills. [UPC 315.0]
2.5 Alignment and Grade
The pipe should be bedded true to line and
grade, uniformly and continuously
supported on firm, stable material.
Blocking shall not be used to bring the pipe
to grade. The bedding shall conform to
Section 718.0 of the Uniform Plumbing
Code.
2.6 Backfill
The backfill shall conform to Section 315.4
of the Uniform Plumbing Code.
369
IS 11
UNIFORM PLUMBING CODE
2.7 Joints
2.7.1 Caulked Joints
Make connections or transitions to bell-and-
spigot cast iron soil pipe and fittings, and to
bell-and-spigot pipe and fittings of other
materials with approved mechanical
compression joints designed for this use, or
caulked joints made in an approved
manner. In caulking, pack the joint w^ith
oakum or hemp and fill with molten lead to
a depth of not less than one (1) inch (25.4
mm). Allow a period of four (4) minutes for
cooling, following which, caulk the lead at
the inside and outside edges of the joint.
Lead shall not be overheated. [UPC 705.1.1]
Note: Caulked joints should be avoided if
possible.
2.7.2 Gasket-Type Joints
Pipe shall be cut square with saws or pipe
cutters designed specifically for plastic pipe;
protect pipe and fittings from serrated
holding devices and abrasion.
1. Wipe the pipe spigot, rubber gasket,
and inside of the socket clean of all dirt
and moisture.
2. Coat the socket and gasket evenly with
a vegetable base paste lubricant.
3. Slide the gasket on the spigot and
against the backup ring and snap it to
remove any twist.
4. Force the spigot into the socket. Check
that the joint is properly connected by
using any thin feeler gauge that the
gasket is not looped back over the
backup ring.
2.7.3 Solvent Cement Joints
2.7.3.1 Selection. Solvent cement shall be
recommended for ABS by the manufacturer.
Follow manufacturer's recommendations
for types of solvent cement for such
conditions as temperature over 100°F
(38°C), or humidity over 60%.
2.7.3.2 Handling (to maintain effectiveness).
Solvent cement containers no larger than 1
quart (1 liter) should be used in the field (to
avoid thickening due to evaporation). Keep
container closed and in the shade when not
in use. Keep applicator submerged in
solvent cement between applications. When
solvent cement becomes thicker, THROW IT
AWAY. Solvent cement shall NOT be
thinned.
2.7.3.3 Size of Applicator. Applicator should be
about one half the pipe diameter. Do not
use small applicator on large pipes.
Ordinary pure bristle paint brush or
applicators furnished with product are
satisfactory.
2.7.3.4 Application. Solvent cement shall be
applied deliberately, but without delay (two
men may be needed to make large joints).
Use special care when temperature is over
100°F (38°C) or humidity is over 60%.
2.7.4 SAFETY REQUIREMENTS AND
PRECAUTIONS
2.7.4.1 General. Solvents contained in ABS plastic
pipe cements are classified as airborne
contaminants and flammable and
combustible liquids. Precautions listed in
this appendix should be followed to avoid
injury to personnel and the hazard of fire.
2.7.4.2 Safety Precautions. Prolonged breathing
of solvent vapors should be avoided. When
pipe and fittings are being joined in partially
enclosed areas, a ventilating device should
be used in such a manner to minimize the
entry of vapors into the breathing areas.
2.7.4.3 Solvent cements should be kept away from
all sources of ignition, heat, sparks, and
open flame.
2.7.4.4 Containers for solvent cements should be
kept tightly closed except when the cement
is being used.
2.7.4.5 AH rags and other materials used for mopping
up spills should be kept in a safety waste
receptacle which should be emptied daily.
2.7.4.6 Most of the solvents used in ABS pipe
cements can be considered eye irritants and
contact with the eye should be avoided for it
may cause eye injury. Proper eye protection
and the use of chemical goggles or face
shields is advisable where the possibility of
splashing exists in handling solvent
cements. In case of eye contact, flush with
plenty of water for 15 minutes and call a
physician immediately.
2.7.4.7 Repeated contact w^ith the skin should be
avoided. Proper gloves impervious to and
unaffected by the solvents should be worn
when frequent contact with the skin is
likely. Application of the solvents or solvent
cements with rags and bare hand is not
recommended. Brushes and other suitable
applicators can be used effectively for
applying the solvent cement, thus avoiding
skin contact. In the event of excessive
contact, remove contaminated clothing and
wash skin with soap and water.
Step 1 Cut pipe square with hand saw and
miter box, mechanical cut-off saw,
or tube cutter designed for plastic.
370
ABS SEWER PIPE AND FITTINGS IS 1 1
Step 2 Ream inside and chamfer outside of
pipe (to eliminate all burrs).
Step 3 Clean all dirt, moisture, and grease
from pipe and socket. Use a clean,
dry rag.
Step 4 Check dry fit of pipe in fitting. Pipe
should enter fitting socket from 1/3
to 3/4 depth of socket.
Step 5 Apply a light coat of ABS solvent
cement to inside of socket using
straight outward strokes (to keep
excess solvent out of socket). This is
also to prevent solvent cement
damage to pipe. For loose fits,
apply a second coat of solvent
cement. Time is important at this
stage. See Section 2.7.3.4.
Step 6 While both the inside socket surface
and the outside surface of the pipe
are SOFT and WET with solvent
cement, forcefully bottom the pipe
in the socket, giving the pipe a one-
quarter turn, if possible. The pipe
must go to the bottom of the socket.
Step 7 Hold the joirit together until tight
(partial set).
Step 8 Wipe excess cement from the pipe.
A properly made joint will normally
show a bead around its entire
perimeter. Any gaps may indicate
insufficient cement or the use of
light bodied cement on larger
diameters where heavy bodied
cement should have been used.
Step 9 The system shall not be tested until
the joints have cured (set) at least as
long as recommended by the
manufacturer.
2.7.5 Special Joints
2.7.5.1 Connection to Non-Plastic Pipe
When connecting plastic pipe to other types
piping, use only approved types of fittings
and adapters, designed for the specific
transition intended.
ADOPTED: 1976
REVISED: 1981, 1987, 2003
371
IS 1 1 UNIFORM PLUMBING CODE
372
Installation Standard
For
POLYETHYLENE (PE) FOR GAS YARD PIPING
lAPMO IS 12-2003
1.0 SCOPE
1 .1 This standard shall govern the installation of
polyethylene (PE) natural and liquified
petroleum gas yard piping. Installation,
material and inspection shall comply with
the current edition of the Uniform Plumbing
Code [UPC]TM published by the
International Association of Plumbing and
Mechanical Officials and shall also comply
with this standard.
Note: The following sections of tfie Uniform
Plumbing Code apply to PE gas piping:
202.0
310.0
313.0
314.0
315.0
316.2.3
Chapter 12
1204.3.2
1210.1
1211.19
1213.0
1218.0
Table 14-1
Definition of PE
Workmanship
Protection of Piping, Materials and
Structures
Hangers and Supports
Trenching, Excavation, and Backfill
Plastic Pipe to Other Materials
Fuel Piping
Final Piping Inspection
Location of PE
Tracer Wire
Liquified Petroleum Gas Facilities
and Piping
Medium Pressure Gas Piping
Systems
Materials:
Pipe and Tube
PE3406
PE2306
Fittings:
Copper Alloy
PE2306,
PE2406
PE3408
ASTM D 2513
PE2406
ANSI B16.26
PE3408
PE3406
ASTM D 2513
ABBREVIATIONS
ANSI American National Standards Institute
ASTM American Society for Testing and
Materials
lAPMO International Association of Plumbing
and Mechanical Officials
UPC Uniform Plumbing Code published by
lAPMO
2.0
2.1
2.1.1
2.1.2
2.1.3
2.1.4
2.2
2.2.1
2.2.2
2.2.3
2.3
2.3.1
PRODUCT REQUIREMENTS
Minimum Standards
Materials. Pipe, tubing, and fittings shall
conform to the appropriate standards in
Table 14-1 of the Uniform Plumbing Code.
See note ahead of Chapter 2 of this
standard. [UPC 301.1]
Pipe. PE pipe is plastic of 1/2 inch (12.7
mm) or larger size. One-half inch (12.7
mm) pipe shall be SDR 9. Pipe sizes less
than 3 inches (76 mm) shall be SDR 11.
Pipes 3 inches (76 mm) and larger shall be
SDR 11.5 or lower*.
Tubing. PE tubing is plastic and shall be
limited to the following:
Tubing Size
Inches (mm) SDR*
1/4 (6,4) 6
3/8 (9.5) 8
1/2 (12.7) 7
*Note: The lower the SDR number, the
thicker the wall.
Fittings. Heat fusion fittings shall be PE
2306, PE 2406, PE 3408, PE 3406, or other
listed materials. Mechanical connectors
for PE pipe and tubing and for transition
fittings shall be approved compression
type couplings or other special listed
joints.
Markings
Pipe and Tubing. Pipe and tubing
markings shall be in accordance with D
2513. [UPC 301.1.2]
Fittings. Fitting markings shall be in
accordance with D 2513 or B16.26. [UPC
301.1.2]
Position of Markings. The identifying
markings on pipe, tubing, and fittings
shall be visible for inspection without
moving materials.
Protection of Piping
Storage. Unprotected pipe should not be
stored in direct sunlight. The pipe shall
be stored in a way to protect it from
mechanical damage (slitting, puncturing,
etc.). Exposure to sunlight during normal
construction periods is not harmful. [UPC
313.0]
373
IS 12
UNIFORM PLUMBING CODE
2.4 Thermal Expansion
2.4.1 Snaking. The pipe and tubing shall be
"snaked" in the trench bottoni with enough
slack to provide for thermal expansion and
contraction before stabilizing. The normal
slack created by residual coiling is generally
sufficient for this purpose. If, however, the
pipe has been allowed to straighten before
it is placed in the trench, 6 inches (152 mm)
per 100 feet (30480 mm) of pipe length shall
be allowed for this purpose.
2.4.2 Stabilizing. Pipe and tubing temperature
shall be stabilized by one of the following
n\ethods:
(a) Shade backfill. Leave all joints
exposed so they can be examined
during the pressure test.
(b) Allow to stand overnight.
2.5 Trenching and Backfill
2.5.1 Trenching. Trenching bottoms shall be
smooth and regular of either undisturbed
soil or a layer of compacted backfill so that
minimum settlenient will take place. Pipe
or tubing shall not be wedged or blocked.
Voids shall be filled and compacted to
level of trench bottom. The minimum
cover shall be 18 inches (457 mm) below
finish grade. [UPC 315.0]
Exceptions:
(1) Tubing for gas lights shall be buried a
minimum of 12 inches (305 mm) below
finish grade where gas flow is restricted to
10 cubic feet per hour (8 x lO-^m^/s) at its
source by a mechanical means or a fixed
orifice.
Note: Local climatic conditions may affect
required burial depth.
(2) Piping may terminate a maximum of
one foot above ground when encased in a
listed anodeless transition riser.
2.5.2 Backfill. The pipe and tubing temperature
shall be stabilized before backfilling. See
Section 2.4.2.
2.6 Types of Joints
PE joints shall be made as follows:
2.6.1 Heat Fusion Joints. Heat fusion joints
shall be niade according to the
manufacturer's procedures using
recommended heat times, temperature
and joining pressures.
2.6.2 Mechanical Joints. Mechanical joints
shall be assembled in an approved manner
with tools recomniended by the fitting
manufacturer. Mechanical joints shall be
made with listed mechanical fittings.
2.7
2.7.1
2.7.2
2.8
2.8.1
2.8.2
2.9
2.9.1
2.9.2
2.9.3
2.10
2.10.1
2.10.2
2.10.3
Special Joints
Listed transition fittings or listed
mechanical fittings shall be used when
making joints between PE and steel or PE
and copper.
Transition fittings shall be installed
outside of meter vaults with metallic
piping extending into the vaults a
sufficient distance to permit the use of
backup wrenches.
Inspections
Temperature. Pipe temperatures shall be
stabilized before testing. See Section 2.4.2.
[UPC 1204.0]
Piping shall be subjected to the pressure
test required in Section 1204.0 of the
Uniform Plumbing Code. [UPC 1204.3.2]
Materials
Location. PE pipe and tubing shall be
installed only outside the foundation of any
building or structure or parts thereof. It
shall be buried in the ground for its entire
length with cover as provided in Section
2.5.1. It shall not be installed within or
under any building or structure or mobile
home or commercial coach or parts thereof.
The term "building or structure or parts
thereof" shall include structures such as
porches and steps, whether covered or
uncovered, roofed porte-cocheres, roofed
patios, carports, covered walks, covered
driveways and similar structures or
appurtenances. [UPC 1210.0]
Exception: Tubing may extend into gas
light support columns provided it is not
exposed to external damage.
Maximum Working Pressure. Gas
pressure shall not be more than 5 psi (34.5
kPa) for natural gas nor more than 10 psi
(69 kPa) for liquified petroleum gas.
Gas Supplier. Installation shall be
acceptable to the serving gas supplier.
Installation of Gas Piping
Types of Joints. See Sections 2.6 and 2.7
of this standard. [UPC 1211.0]
Prohibited Joints. PE pipe shall not be
joined by a threaded joints. Joints made
with adhesives or solvent cement shall be
prohibited.
Identification. Plastic gas yard piping shall
be permanently identified by attaching a
metal tag to the meter end of the piping
system stating, "Plastic Yard Piping".
374
PE FOR GAS YARD PIPING
IS 12
2.11
2.11.1
2.11.2
Sizing
Pipe. Pipe shall be sized as required by
Section 1217.0 or 1218.0 of the UPC. [UPC
1217.0]
Tubing. Tubing shall be sized from Table
1. [UPC 1217.0]
ADOPTED: 1971
REVISED: 1975, 1977, 1978, 1981,1983, 1985,
1989, 1990, 1991, 1993, 2003
TABLE 1
SIZE OF PLASTIC GAS TUBING
Maximum Delivery Capacity in Cubic Feet of Gas per Hour (CFH)
of Tubing Carrying Natural Gas of 0.60 Specific Gravity
Nominal
Tubing
Internal
Size
Diameter
Length in
Feet
Inches
Inches
10
20
30
40 50 60
70
80
90
100
125
1/4
0.250
18
12
10
8 7 7
6
6
5
5
4
3/8
0.375
51
35
28
24 21 19
18
16
16
15
13
150
200
250
300 350 400
450
500
550
600
1/4
0.250
4
3
3
3 3 2
2
2
2
2
3/8
0.375
12
10
9
8 7 7
6
6
6
6
TABLE 1 (Metric)
SIZE OF PLASTIC GAS TUBING
Maximum Delivery Capacity in Cubic Meters of Gas per Secorid (m^/s)
of Tubing Carrying Natural Gas of 0.60 Specific Gravity
Nominal
Tubing
Internal
Size
Diameter
Length in
Meters
mm
mm
3.0
6.1
9.1
12.2
15.2
18.3
6.4
6.4
1.4
1.0
0.8
0.6
0.56
0.56
9.5
9.5
4.1
2.8
2.2
1.9
1.7
1.5
21.3
24.4
27.4
30.5
38.1
45.7
6.4
6.4
0.5
0.5
0.4
0.4
0.3
0.3
9.5
9.5
1.4
1.3
1.2
1.2
1.0
0.96
61.0
76.2
91.4
106.7
121.9
137.2
6.4
6.4
0.2
0.2
0.2
0.2
0.16
0.16
9.5
9.5
0.8
152.4
0.7
167.6
0.6
182.9
0.56
0.56
0.5
6.4
6.4
0.16
0.16
0.16
9.5
9.5
0.5
0.5
0.5
375
IS 12 UNIFORM PLUMBING CODE
376
Installation Standard
For
PROTECTIVELY COATED PIPE
lAPMO IS 13-2003
1.0 SCOPE
1.1 Installation and material of protective pipe
coatings shall comply with this Standard
and the current edition of the Uniform
Plumbing Code [UPC]™ published by the
International Association of Plumbing and
Mechanical Officials (lAPMO).
Note: The following sections of the Uniform Plumbing
Code shall apply to protectively coated pipe.
301.2 Marking
302.0 Iron pipe size (IPS) pipe
310.0 Workmanship
311.0 Prohibited fittings and practices
313.5 Protection required
314.0 Hangers and supports
604.0 Materials - water piping
609.3.1 Coated protection required
1210.0 Materials - gas piping
1211.6 Coated protection required and
coating material approval required
2.0
2.1
2.1.1
2.1.1.1
2.1.1.2
2.1.1.3
2.1.2
2.1.2.1
PRODUCT REQUIREMENTS
Minimum Standards
Materials
Coating. Piping shall be coated by a
listed coating applicator in accordance
with AWWA C203, AWWA C213, or
AWWA C215.
Tape. Tape for field application shall
comply with PS 37, Black Plastic PVC or PE
Pressure-Sensitive Corrosion Preventive
Tape.
Primer. Primer for field application shall
be compatible with the tape and be as
recommended by the tape manufacturer.
Markings
Pipe. Protectively coated pipe shall be
legibly marked at least every two (2) feet
(610 mm) as follows:
(a) Applicator's name or trademark;
(b) Pipe manufacturer's naine;
(c) Pipe standard designation i.e., ASTM
or API;
(d) Pipe material type i.e., black,
galvanized;
(e) Pipe size and schedule;
(f) Coating material;
(g) Holiday test voltage;
(h) Products listed by lAPMO that are
covered by this standard shall be
labeled with the designated lAPMO
certification mark; and
(i) Any other required markings. [UPC
301.1.2]
2.1.2.2 Tape. Tape for field applications should
be legibly marked at least every two (2)
feet (610 mm) with the manufacturer's
name and tape model identification.
2.2 Protection of Piping and Fittings
2.2.1 Field Joints. Field joints shall be made as
follows, except as specified in 2.2.2. Clean
and dry surfaces to be protected. [UPC
313.0]
Step 1 Oil and grease, if present, shall be
removed with suitable non-oily
type solvent such as Heptane or
Trichlorethylene. Materials, such
as kerosene and gasoline, shall
not be used.
Step 2 For coated pipe, remove coating
approximately 3 inches (76 mm)
from end of pipe or from repair
area and bevel to expose shoulder
of coating at area to be field
wrapped.
Step 3 For taped pipe, remove tape and
overwrapping so as to expose
approximately 3 inches (76 mm)
of pipe at area to be field
wrapped.
Step 4 For welded pipe, grind down
sharp welds and weld spatter to a
minimum 1/8 inch (3.2 mm)
radius. Wire brush the weld area
thoroughly taking care to remove
as much mil scale and surface
rust as possible. Remove any
loose or charred coating caused
during welding.
Step 5 Apply listed primer, as
recommended by the manu-
facturer of the tape being applied,
over the protected area and
adjacent 1 inch (25.4 mm) of
protected area.
Step 6 Spirally wrap listed tape by a half
overlap double wrap of minimum
10 mil tape stretched around the
377
IS 13
UNIFORM PLUMBING CODE
2.2.2
fitting, thread, and other un-
protected areas to provide a
minimum 40 mil thickness. A
maximum of two (2) inch (51
mm) wide tape shall be used for
field application.
Exception: Unless otherwise
listed by lAPMO, a maximum of
one (1) inch (25.4 mm) wide tape
shall be used on change of
direction fittings for piping sizes
up to and including two (2) inch
(51 mm).
Other Methods. Other materials
approved for field joints or repair shall be
applied as per manufacturer's
recommendations and the listing
requirements.
2.3 Damage in Shipment. Coated piping
shall be protected against damage in
shipment.
2.3.1 Handling and Storage. Coated piping
shall be handled and stored in a manner
to prevent damage.
2.3.2 Handling by Installer. Movement of pipe
from truck or into trench shall be done in
such a manner as to avoid abrasion, or
damage from dropping.
2.4 Backfill. All excavations shall be
completely backfilled as soon after
inspection as possible. [UPC 315.0]
2.5 Inspection. All coated piping shall be
inspected and tested and any visible void,
damage or imperfection to the pipe
coating shall be repaired as to comply
with Section 2.2.
2.5.1 Equipment. The equipment, material,
and labor necessary for inspection or tests
shall be furnished by the person to whom
the permit is issued or by whom
inspection is requested.
ADOPTED: 1971
REVISED: 1975, 1978, 1982, 1984, 1991, 2000,
2003
378
Installation Standard
For
ASBESTOS CEMENT PRESSURE PIPE FOR WATER SERVICE AND YARD PIPING
lAPMO IS 15-2003
1.0 SCOPE
1 .1 This standard shall govern the installation of
asbestos cement pressure pipe and fittings
with elastomeric gasketed joints in hot and
cold water building supply and yard piping.
For allowable location and pressure, see
Sections 2.4 and 2.5.2 of this standard.
Installation, material, and inspection shall
comply with the current edition of the
Uniform Plumbing Code [UPC]TM published
by the International Association of Plumbing
and Mechanical Officials, and shall also
comply with this standard.
Note: The following sections of the Uniform
Plumbing Code apply to asbestos cement pressure
piping systems.
Table 14-1 Materials
310.0 Workmanship
313.0 Protection of Piping, Materials
and Structures
314.0 Hangers and Supports
315.0 Trenching, Excavation, and
Backfill
Chapter 6 Water Supply and Distribution
Chapter 2 DEFINITIONS
202.0 AC Asbestos Cement
Chapter 14 ASTM American Society for Testing
and Materials
lAPMO International Association of
Plumbing and Mechanical
Officials
UPC Uniform Plumbing Code
published by lAPMO
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Material. Materials shall conform to the
appropriate standard in Table 14-1 of the
Uniform Plumbing Code.
Applicable Standards
AC Pipe ASTM C296
Fittings AWWA/ANSI A21.10
Rings ASTM D1869
Joints AWWA/ANSI A21.il
2.1 .2 Pipe. Pipe is asbestos cement.
2.1.3 Fittings. Fittings are cast iron or other
listed materials.
2.1.4
2.14.1
2.1.4.2
2.1.4.3
2.1.4.4
2.2
2.2.1
2.2.2
2.3
2.3.1
2.3.2
Markings
Pipe. Pipe markings shall be in
accordance with C 296. [UPC 301.1.2]
Fittings. Fitting markings shall be in
accordance with A21.10. [UPC 301.1.2]
Couplings. Couplings shall be marked
with at least the following:
(a) Manufacturers name or trademark;
(b) Class and nominal size; and
(c) Letter "T".
Position of Markings. The identifying
markings on pipe and fittings shall be
visible for inspection without moving
materials unless otherwise acceptable to
the Administrative Authority.
Trenching, Cover, and Backfill
Trenching and Cover. Trench bottoms
shall be uniformly graded and shall be of
either undisturbed soil or shall consist of a
layer or layers of compacted backfill so
that minimum settlement will take place.
The trench bottoms shall be at least 12
inches (305 mm) below the average local
frost depth. The minimum cover shall be
18 inches (458 mm) below the finish
grade. [UPC 315.0]
Backfill. After finishing pressure testing
of the line, backfill a minimum of twelve
(12) inches (305 mm) deep over the top of
the pipe and fittings. Backfill should be
select material placed around the pipe in a
manner to provide a firm continuous
support. Tamp v^ell to secure proper
compaction.
Note: All joints shall be exposed during
test.
Joints
Joints in asbestos cement pipe shall be a
sleeve coupling of the same composition
as the pipe, or of other listed materials,
and sealed with rubber rings or joined by
other listed compression type coupling.
[UPC 705.1.4]
Joints between asbestos cement pipe and
other approved pipes shall be made by
means of listed adapter couplings. Special
heat resistant rings as recommended by
the manufacturer must be used for
temperatures in excess of 140°F (60°C).
379
IS 15
2.3.3
2.3.4
2.3.5
2.3.6
2.4
2.4.1
2.5
2.5.1
Before assembling the joint, the coupling
grooves, pipe ends, and rubber gasket
must be cleaned. The rubber gaskets are
then positioned in the grooves.
Use the pipe manufacturer's joint
lubricant recommended for potable water
application. Apply lubricant to the
machined end of the pipe only, never to
the rubber gasket or groove, unless
specifically recommended otherwise by
the manufacturer.
The end of the pipe and the coupling or
fitting bell shall be assembled using a bar
and wood block or a pipe puller.
"Stabbing" or "popping" the pipe into the
coupling (pipe is suspended and swung
into the bell) is not reconmiended.
When a field cut is made, cut the pipe
square, using hand pipe-cutters which use
a cutting edge, or hand saws. To properly
enter the rubber gasketed joint, the end of
the pipe must be machined before
insertion, using hand machining tools.
Materials
Location. Asbestos cement piping shall
be installed only outside the foundation of
any building or structure or parts thereof.
It shall be buried in the ground for its
entire length except vertical piping may
be extended above grade per Section 313.0
of the Uniform Plumbing Code. It shall
not be installed within or under any
building or structure or mobile home or
commercial coach or parts thereof. The
term "building or structure or parts
thereof" shall include structures such as
porches and steps, roofed porte-cocheres,
roofed patios, carports, covered walks,
covered driveways, and similar structures
or appurtenances. [UPC 604.1]
Installation, Testing, and Identification
Alignment and Deflection. Pipe and
fittings shall be aligned properly without
strain. Pipe may be deflected in
accordance with the manufacturer's
recommendations provided that it shall
not be permanently staked or blocked to
maintain this deflection. If soft soil
conditions exist, deflected joints may be
permanently blocked or staked to
maintain the deflection. The amount of
deflection shall b.e: 5° for sizes 4 inch
(101.6 mm) through 12 inch (305 mm); 4°
for 14 inch (356 mm) and 16 inch (407
mm); 3-1/2° for 18 inch (457 mm) through
2.5.2
UNIFORM PLUMBING CODE
24 inch (610 mm) for pipe belled on the
job site. For factory-belled couplings, one
half (1/2) the above deflections by size
shall be allowed.
Working Pressure. Maximum working
pressure shall be as follows:
MATERIALS, SIZES AND MAXIMUM WORKING
PRESSURES
Pipe
Sizes 1
Maximum Pres
Class 100
4-
24 inch incl.
100 psi
(102-
- 610 mm incl.)
(689 kPa)
Class 150
4 -
- 24 inch incl.
150 psi
(102-
- 610 mm incl.)
(1033 kPa)
Class 200
4-
■ 24 inch incl.
200 psi
(102-
- 610 mm incl.)
(1378 kPa)
2.5.3
2.5.4
2.5.5
2.5.6
2.5.7
2.5.7.1
2.5.7.2
Laterals and Saddles. Installation of
laterals, saddles, or tapped couplings in
AC piping shall be as required by their
listings.
Thrust Blocking. Thrust blocks shall be
installed at:
(a) Changes in direction, as at tees and
bends;
(b) Changes in size, as at reducers;
(c) Stops, as at dead ends; and
(d) Valves, where thrusts may be
expected.
The size and type of thrust block shall be
based on the pressure rating of the pipe
(or line test pressure, if greater than
piping rating), pipe size and kind of soil
2.5.4(b). Refer to Table 1 for thrust at
fittings for a pressure of one hundred
(100) pounds per square inch (689 kPa).
To determine the bearing area of thrust
blocks, refer to Table 2 for the safe bearing
load of the soil and divide the total thrust
by this safe bearing load.
Thrust blocks shall be located as shown
on Chart 1.
Testing
The portion of the line being tested
should be complete with thrust blocks or
properly sized temporary thrust blocking.
The line may be pressure tested
immediately after installation, provided
however, that if poured concrete thrust
blocks have been utilized, they have had a
24-hour period to attain an initial cure.
[UPC 609.4]
The entire system shall be filled with
water, purged of air, and tested at a
pressure at least equal to the eventual
operating pressure for at least one (1)
hour before inspection and backfilling of
380
ASBESTOS CEMENT PRESSURE PIPE FOR
WATER SERVICE AND YARD PIPING
trench. It is recommended that the test
pressure not exceed the working pressure
of the pipe.
CAUTION: AIR TESTING IS
PROHIBITED.
2.5.7.3 Identification. A label shall be fastened to
the main electrical meter panel stating,
"This structure has a non-metallic water
service.
2.6
Sizing. Piping shall be sized in
accordance with UPC Section 610.0.
When UPC Appendix A is applicable.
IS 15
Chart A-5 (Fairly Smooth Pipe) may be
used. Flow velocities shall be limited to a
maximum of 8 fps (2.4 m/s). When using
UPC, Table 6-3, required by UPC Section
610.0, velocities shall also be checked and
limited using UPC Chart A-5. [UPC 610.0]
Example: For a pressure of 150 psi (1033.5 kPa) on
a 4 inch (102 mm) tee, Table 609.1.4(a) indicates
1850 pounds (8232.5 N) for 100 psi (689 kPa).
Therefore, total thrust for 150 psi (1033.5 kPa) will
equal 1-1/2 times 1850 pounds (82,32.5 N).
TABLE 1
Thrust at Fittings in Pounds at 100 psi of Water Pressure
Pipe Dead Ends
Size Class and Tees 90° Bend 45° Bend 22 1/2° Bend
4"
6"
10"
12"
14"
16"
18"
20"
24"
100
150
200
1,720
1,850
1,850
2,440
2,610
2,610
1,320
1,420
1,420
660
720
720
100
150
200
3,800
3,800
3,800
5,370
5,370
5,370
2,910
2,910
2,910
1,470
1,470
1,470
100
150
200
6,580
6,580
6,580
9,300
9,300
9,300
5,040
5,040
5,040
2,550
2,550
2,550
100
150
200
9,380
10,750
10,750
13,270
15,200
15,200
7,190
8,240
V 8,240
3,640
4,170
4,170
100
150
200
13,330
15,310
15,310
18,860
21,640
21,640
10,240
11,720
11,720
5,170
5,940
5,940
100
150
200
17,930
20,770
20,770
23,360
29,360
29,360
13,740
15,910
15,910
6,960
8,060
8,060
100
150
200
23,210
26,880
26,880
32,820
38,010
38,010
17,880
20,590
20,590
9,000
10,430
10,430
100
150
200
31,000
34,400
38,600
44,200
48,500
54,400
23,850
26,400
29,650
11,950
13,400
14,900
100
150
200
38,400
42,600
47,800
54,200
60,000
67,400
29,500
32,600
36,700
14,700
16,500
18,600
100
150
200
55,000
61,500
69,000
78,000
86,700
97,200
42,200
47,200
52,900
21,100
23,900
26,800
381
IS 15 UNIFORM PLUMBING CODE
TABLE 1 (Metric)
Thrust at Fittings in Newtons at 689 kPa of Water Pressure
Pipe
Dead Ends
Size
Class
and Tees
90° Bend
45° Bend
22 1/2° Be
102
100
7654
10,858
5874
2937
150
8232.5
11,614.5
6319
3204
200
8232.5
11,614.5
6319
3204
152
100
16,910
23,896.5
12,949.5
6541.5
150
16,910
23,896.5
12,949.5
6541.5
200
16,910
23,896.5
12,949.5
6541.5
203
100
29,281
41,385
22,428
11,347.5
150
29,281
41,385
22,428
11,347.5
200
29,281
41,385
22,428
11,347.5
254
100
41,741
59,051.5
31,995.5
16,198
150
47,837.5
67,640
36,668
18,556.5
200
47,837.5
67,640
36,668
18,556.5
305
100
59,318.5
83,927
45,568
23,006.5
150
68,129.5
96,298
52,154
26,433
200
68,129.5
96,298
52,154
26,433
356
100
79,788.5
103,952
61,143
30,973
150
92,426.5
130,652
70,799.5
35,867
200
92,426.5
130,652
70,799.5
35,867
406
100
103,284.5
146,049
79,566
40,050
150
119,616
169,144.5
91,625.5
46,413.5
200
119,616
169,144.5
91,625.5
46,413.5
457
100
137,950
196,690
106,132.5
53,177.5
150
153,080
215,825
117,480
59,630
200
171,770
242,080
131,942.5
66,305
508
100
170,880
241,190
131,275
65,415
150
189,570
267,000
145,070
73,425
200
212,710
299,930
163,315
82,770
610
100
244,750
347,100
187,790
93,895
150
273,675
385,815
210,040
106,355
200
307,050
432,540
235,405
119,260
382
ASBESTOS CEMENT PRESSURE PIPE FOR IS 1 5
WATER SERVICE AND YARD PIPING
TABLE 2
Safe Bearing Loads for Various Soils
Soil Safe Bearing Load
LbsySq. Ft.
(kPa)
Mulch, Peat, etc.
Soft Clay
1000
6890
Sand
2000
13,780
Sand and Gravel
3000
20,670
Sand and Gravel
Cemented w/Clay
4000
27,360
Hard Shale
10,000
68,900
Example: Assume a 4000 pound (17,800 N) total
thrust was computed. The soil condition is sand.
The required bearing area of the thrust block is 4000
lbs. (17,800 N) divided by 2000 lbs. (13,780 kPa) or
2 sq. ft. (0. 19 m2)
ADOPTED: 1975
REVISED: 1981,1982,2003
383
IS 15
UNIFORM PLUMBING CODE
CHART 1
6" Class 150 (152 mm) 10" Class 150 (254 mm)
384
Installation Standard
For
EXTRA STRENGTH VITRIFIED CLAY PIPE IN BUILDING DRAINS
lAPMO IS 18-2003
1.0 SCOPE
1.1 This standard shall govern the installation of
extra strength vitrified clay pipe in gravity
building drains. (See Section 2.2 for allowable
location.) Installation, material, and inspection
shall comply with the current edition of the
Uniform Plumbing Code [UPC]TM published by
the International Association of Plumbing and
Mechanical Officials and this standard.
Note: The following sections of the Uniform
Plumbing Code apply to vitrified clay pipe.
103.5 Inspections
103.5.3 Testing of Systems
103.5.3.3 Exceptions
103.5.4.2 Responsibility
204.0 Definitions, Building Drain
310.0 Workmanship
313.0 Protection of Piping, Materials, and
Structures
314.3 Supporting in the Groimd
315.0 Trenching, Excavation, and Backfill
316.1.4 Flare Joints
Chapter 7 Sanitary Drainage
701 .1 .3 Location of Piping and Use in
Pressurized Drainage Systems
705.2 Use of Joints
712.2 Water Test
712.3 Air Test
720.0 Sewer and Water Pipes
Table 14-1 Extra Strength
Vitrified Clay Pipe ASTM C 700
Fittings, Couplings,
Molded Rubber ASTM C 425
Chapter 2 DEFINITIONS
Chapter 14
ASTM American Society for Testing and
Materials
lAPMO International Association of Plumbing
and Mechanical Officials
UPC Uniform Plumbing Code published by
lAPMO
2.1.2
2.1.2.1
2.1.2.2
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Materials. Pipe and fittings shall be a
minimum 3 inch (76 mm) in size, "Extra
Strength" and couplings shall be molded
rubber sewer couplings. They shall
conform to the applicable standards in
Table 14-1 of the UPC. [UPC 301.1]
Markings
Pipe and Fittings. Pipe and fitting
markings shall be in accordance with
C 700. [UPC 301.1.2]
Couplings. Couplings assemblies shall be
marked with at least the following:
(a) Manufacturer's name or trademark on
rubber couplings and take-up band or
screw take-up housing;
(b) Size, on rubber coupling;
(c) Year of manufacture on rubber
coupling;
(d) Grade of material on take-up band or
screw take-up housing; and
(e) Couplings and components listed by
lAPMO that are covered by this
standard shall be labeled with the
designated lAPMO certification mark
to show compliance with this standard.
2.2 Burial and Separation
2.2.1 Burial. Pipe and fittings shall be buried
12 inches (305 mm) minimum.
2.2.2 Separation. Pipe and fittings shall not be
run or laid in the same trench with water
piping unless both the following
conditions are met:
(1) The bottom of the water pipe, at all
points, shall be at least 12 inches (305
mm) above the top of the drain line;
and
(2) The water pipe shall be placed on a
solid shelf excavated at one side of
the common trench. [UPC 720.0]
385
IS 18
UNIFORM PLUMBING CODE
2.3 Type of Joints
Joints shall be made with couplings or
with flexible compression factory
fabricated joints. [UPC 316.0]
2.3.1 Use of Joints
Transitions between clay and other
materials shall be made with molded
rubber sewer couplings and appropriate
bushings or reducers. [UPC 705.2]
ADOPTED: 1980
REVISED: 1982, 1985, 2003
386
Installation Standard
for
CPVC SOLVENT CEMENTED HOT AND COLD WATER DISTRIBUTION SYSTEMS
lAPMO IS 20-2005
1.0 SCOPE
1 .1 This standard shall govern the installation of
CPVC piping (IPS pipe and SDR-11 tubing)
in potable hot and cold water distributing
systems within buildings (For allowable
locations and pressure, see Sections 2.9.2
and 2.9.4) Installation, material, and
inspection shall comply with the current
edition of the Uniform Plumbing Code
[UPC]TM, published by the International
Association of Plumbing and Mechanical
Officials, and shall also comply with this
standard.
Note: The following sections of the Uniform
Plumbing Code apply to CPVC IPS piping and SDR-
1 1 tubing.
103.5 Inspections
301 . 1 Minimum Standards
310.0 Workmanship
311.0 Prohibited Fittings and Practices
313.0 Protection of Piping, Materials
and Structures
314.0 Hangers and Supports
316.2.3 Plastic Pipe to Other Materials
Chapter 6 Water Supply and Distribution
Chapter 2* Definitions
205.0 CPVC Chlorinated Poly (Vinyl Chloride)
Pipe or tubing'Tipe" or "Piping"
includes both pipe and piping,
unless specified as "IPS Pipe" or
"tubing".
Table 14-1
Chlorinated Poly (Vinyl Chloride) (CPVC)
Plastic Hot and ColdWater Distribution
System ASTMD2846
Chlorinated Poly (Vinyl Chloride) (CPVC)
Plastic Pipe, Schedules 40 and 80
ASTM F 441
Socket Type Chlorinated Poly (Vinyl
Chloride) (CPVC) Plastic Pipe Fittings
Schedule 40 ASTM F 438
Socket Type Chlorinated Poly (Vinyl
Chloride) (CPVC) Plastic Pipe Fittings
Schedule 80 ASTM F 439
Solvent Cements for Chlorinated Poly (Vinyl
Chloride) (CPVC) Plastic Pipe and Fittings
ASTM F 493
ABBREVIATIONS
ASTM American Society for Testing and
Materials
lAPMO International Association of
Plumbing and Mechanical Officials
NSF National Sanitation Foundation
International
UPC Uniform Plumbing Code published
by lAPMO
*The first three numbers refer to the corresponding
section of the UPC.
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1 .1 Materials. Materials shall comply with the
following:
Materials ASTM
Standard
Raw Material-CPVC 23447 D 1784
IPS Pipe
Sch. 40 (1/2 in., 3/4 in. and 1 in.) F441
(12.7 mm, 19.1 mm, and 25.4 mm)
Sch. 80 (1/2 in. -2 in.) F441
(12.7 mm - 51 mm)
Tubing
SDR 11 (1/2 in. thru 2 in.) D2846
(12.7 mm - 51 mm)
Fittings
Sch. 40 (1/2 in., 3/4 in. & 1 in.) F 438
(12.7 mm, 19.1 mm, and 25.4 mm)
Sch. 80 (1/2 in. -2 in.) F439
(12.7 mm - 51 mm)
Tube Fittings (1 /2 in. - 2 in.) D 2846
(12.7 mm - 51 mm)
2.1.2 Primer. Listed primers shall be used that
are compatible with the type of listed CPVC
cement and pipe used. The primer shall be a
true solvent for CPVC, containing no slow
drying ingredient. Cleaners shall not be
allowed to be used as a substitute or
equivalent for a listed primer.
Exception: Listed solvent cements that do not
require the use of -primer shall he permitted for
387
IS 20
UNIFORM PLUMBING CODE
use with CPVC pipe and fittings, manufactured
in accordance with ASTM D 2846, 1/2 inch
through 2 inches in diameter.
Note: Manufacturer shall provide test data
from an independent testing laboratory
acceptable to the Administrative Authority
that their CPVC pipe, together with
recommended fittings has a Short Term
Working Pressure (STWP) and Temperature
Rating of 150 psi (1030 kPa) at 210° F
(99°C) for 48 hours or more.
2.1.3 Material. Pipe and fittings are plastic and
are usually light gray for IPS pipe and
fittings, and tan for SDR 11 tubing and
fittings.
2.2 Markings
2.2.1 Pipe and Tubing. IPS pipe and tubing
markings shall be in accordance with F 441
or D 2846. [UPC 301.1.2]
2.2.2 Fittings. Fitting markings shall be in
accordance with F 438 or F 439 or D 2846.
[UPC 301.1.2]
Note: Standard number may be omitted on
smaller fittings when marked with four raised
dots.
2.2.3 Solvent Cement. Container labeling of
CPVC solvent cement shall be in accordance
with F 493.
2.2.3.1 Color. Solvent cements requiring the use of
primer shall be colored orange. Solvent
cements that do not require the use of a
primer shall be colored yellow.
2.2.4 Primer. Primer container markings shall be
in accordance with F 656.
2.2.4.1 Color. Primer shall be colored so as to
make its use obvious on a finished joint, but
shall not be colored orange or yellow.
2.2.5 Position of Markings. Identification
markings shall be visible for inspection
without moving materials.
2.2.6 Alignment. Piping and fittings shall be
aligned properly without strain.
Method of marking
(5x Size) (4 Dots)
0.01 5" -0.040"
/■ o>v— __(0.4 mm - 1 .0 mm)
/ v^-^-s^- Dia. dots(4)
O Q equally spaced
\ Q /-^- 1/4" (6.4 mm) Dia.
-3/16"-
(4.8 mm)
Suggested location
of marking code
Alternative Dot
Profiles 1 0x Size
2.3 Protection of Materials
2.3.1 Abrasion. Pipe or tubing passing through
drilled or notched metal studs or joists or
hollow shell masonry walls shall be
protected from abrasion due to thermal
expansion and contraction by elastomeric or
plastic sleeves or grommets or other
approved means. Straight runs may have
protection at maximum 3 feet (915 mm)
intervals. [UPC 313.0]
2.3.2 Puncture. Steel plate protection shall be
installed when required by the
Administrative Authority or section 313.9 of
the Uniform Plumbing Code..
2.3.3 Storage and Handling. Pipe shall be stored
in a way to protect it from mechanical
damage (slitting, pimcturing, etc.). It shall
be stored under cover to keep it clean and
avoid long term exposure to sunlight.
Exposure to sunlight during normal
construction periods is not harmful. CPVC
solvent cements should be stored in a cool
place except when actually in use on the job
site. The solvent cement manufacturer's
specific storage instruction should be
followed.
2.3.4 Freezing. In areas where the system must
be drained to protect it from freezing,
horizontal lines shall be graded to drain.
2.3.5 Overheating:
(a) Tubing shall not be positioned or
closer to devices that generate heat
such that the temperature around
the CPVC tubing is greater than
180°F
(b) Do not apply direct flame onto
CPVC.
2.4 Thermal Expansion
2.4.1 General. Allowance for thermal expansion
and contraction shall be provided by
approved means. Allovk^ance shall be based
on an expansion rate of 3.5 inches (89 mm)
per 100 feet (30,480 mm) of length of run per
100°F (38°C) temperature change.
Note: Expansion rate is independent of the
size of the pipe.
2.4.2 Offsets and Loops. Thermal expansion
may be provided for by use of expansion
loops, offsets, or changes of direction. From
Table 1 determine the length "L" that is
required. Note that "L" is based on length of
run, diameter of pipe, and maximum
temperature of water.
2.5 Clearance. Adequate clearance shall be
provided between piping and structure
388
GPVC SOLVENT CEMENTED HOT AND COLD
WATER DISTRIBUTION SYSTEMS
(such as bored holes and sleeves) to allow
for free longitudinal movement.
2.6 Hangers and Supports
2.6.1 Vertical Piping. Vertical piping shall be
supported at each floor or as specified by
the design engineer to allow for
expansion/contraction. Piping shall have a
mid-story guide. [UPC 314.0]
2.6.2 Horizontal Piping. Unless an engineered
design is provided and approved by the
Administrative Authority, the following
provisions shall apply. Horizontal piping 1
inch (25.4 mm) or smaller shall be supported
at maximum 3 foot (914 mm) intervals.
Piping 1-1/4 inch (32 mm) or larger shall be
supported at maximum 4 foot (1219 mm)
intervals.
2.6.3 Hangers and Anchors. Piping shall not be
anchored rigidly to a support, but rather
secured with smooth hangers or straps that
provide for a degree of movement and that
prevent damage to the pipe. Hangers or
straps with sharp or abrasive edges shall not
be used. Hangers that pinch the piping
shall not be used.
2.7 Solvent Cement Joints
2.7.1 SAFETY REQUIREMENTS AND
PRECAUTIONS^
(a) General. Solvents contained in CPV
plastic pipe' cements are classified as
airborne contaminants and flammable
and combustible liquids. Precautions
listed in this appendix should be
IS 20
followed to avoid injury to personnel
and the hazard of fire.
(b) Prolonged breathing of solvent vapors
should be avoided. When pipe and
fittings are being joined in partially
enclosed areas, a ventilating device
should be used in such a manner to
minimize the entry of vapors into the
breathing areas.
(c) Solvent cements should be kept away
from all sources of ignition, heat, sparks
and open flame.
(d) Containers for solvent cements should
be kept tightly closed except when the
cement is being used.
(e) All rags and other m.aterials used for
mopping up spills should be kept in a
safety waste receptacle which should be
emptied daily.
(f) Most of the solvents used in CPVC pipe
cements can be considered eye irritants
and contact with the eye should be
avoided for it may cause eye injury.
Proper eye protection and the use of
chemical goggles or face shields are |
advisable where the possibility of
splashing exists in handling solvent
cements. In case of eye contact, flush
with plenty of water for 15 minutes and
call a physician immediately.
(g) Repeated contact with the skin should
be avoided. Proper gloves impervious
to and unaffected by the solvents
should be worn when frequent contact
TABLE 1
Developed Length " L" of Expansion Loops
Length of Run in Feet (mm)
20
(6096)
40
(12192)
60 (18288)
80
(24384)
100
(30480)
Nominal Size
Inches
(mm)
Loop Length
"L" in Inches
(mm)
1/2
(12.7)
22
(6706)
31
(9449)
38 (11582)
44
(13411)
50
(15240)
3/4
(19.1)
26
(7925)
37
(11278)
46 (14021)
52
(15850)
58
(17678)
1
(25.4)
30
(9144)
42
(12802)
52 (15850)
60
(18288)
67
(20422)
1-1/4
(32)
33
(10058)
47
(14326)
57 (17374)
66
(39917)
74
(22555)
1-1/2
(38)
36
(10973)
51
(15545)
62 (18898)
72
(21946)
80
(24384)
2
(51)
41
(12497)
58
(17678)
71 (21641)
82
(24994)
91
(27737)
389
IS 20
UNIFORM PLUMBING CODE
Example: Pipe Size - 1/2 inch (12.7 mm) Length of Run - 60 feet (18288 mm): (38") (965 mm) (from table).
Support
Guides
/
L/5
/
L74
2L/5
(15 1/4")
(387 mm)
L/5 L/5
Loop
60' (18288 mm) Run
.
L/2
(19")
(483 mm)
L/4
Offset
Change in
Direction
L
(38")
(965 mm)
with the skin is Hkely. Application of
the solvents or solvent cements with
rags and bare hands is not
recommended. Brushes and other
suitable applicators can be used
effectively for applying the solvent
cement, thus avoiding skin contact. In
the event of excessive contact, remove
contaminated clothing and wash skin
with soap and water.
2.7.2 Selection. Follow the manufacturer's
recommendations for type of solvent cements
for such conditions as temperatures over
100°F (38°C), or humidity over 60%.
2.7.3 Handling (to maintain effectiveness).
Package solvent cement in containers no
larger than 1 quart (1 liter). Keep solvent
cement can closed and in the shade when
not in use. Keep applicator submerged in
solvent cement between applications.
Discard solvent cement when it thickens
appreciably or gels. Solvent cement shall not
be thinned.
2.7.4 Primer. A listed primer in compliance with
ASTM F 656 shall be used with CPVC
solvent cements that require the use of a
primer. CPVC solvent cements that do not
require the use of a primer are permitted for
joints up to 2 inches in size.
2.7.5 Size of Applicator. Applicator should be
about one half the pipe diameter. Do not
use small applicator on large pipes.
2.7.6 Procedures
Step 1. Cut pipe square with hand saw and
mitre box, mechanical cutoff saw or
tube cutter designed for plastic.
Step 2. Ream and chamfer pipe (to
eliminate sharp edges, beads, and
all burrs).
Step 3. Clean all dirt, moisture, and grease
from pipe and fitting socket. Use a
clean, dry rag.
Step 4. Check dry fit of pipe in fittings.
Pipe should enter fitting socket 1/4
to 3/4 of socket depth. On larger
sizes of Sch. 80 fittings, a looser fit
may be expected. This is a normal
condition, and requires care to
apply an adequate amount of
cement.
Step 5. Apply CPVC primer, if required, i
(see Section 2.7.4) to inside of fitting 1
socket. Take care to avoid
puddling.
Step 6. Apply CPVC primer, if required, to |
outside surface of pipe to depth of
fitting socket.
Step 7. When using solvent cements i
requiring a primer, wait until I
primer surface is tacky. DO NOT
attempt to soften (dissolve) the
surface as is required for PVC.
Step 8. Apply a liberal coat of CPVC
solvent cement to the outside
surface of the pipe to the depth of
the fitting socket.
Step 9. Apply a light coat of CPVC solvent
cement to inside of fitting socket.
Apply a second liberal coat of
cement to the pipe end. Take
particular care in cementing larger
sizes of Sch. 80 fittings. Be sure all
surfaces are coated.
Step 10. While both the inside socket surface
and the outside surface of the pipe
are WET with solvent cement,
forcefully bottom the pipe in the
socket, giving the pipe a quarter
turn while inserting, if possible.
1 Appendix XI. Safety Requirements And Precautions, from ASTMD 2564-88 Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Pipe and
Fittings is reprinted with permission from the American Society for Testing and Materials, 1916 Race St., Philadelphia, PA 19103, copyright.
390
CPVC SOLVENT CEMENTED HOT AND COLD
WATER DISTRIBUTION SYSTEMS
Step 11. Hold the joint together for 10 to 15
seconds to assure that the pipe
remains bottomed against the pipe
stop.
Step 12. Do not disturb the joint for at least
30 minutes.
Note: The joint is weal< until tiie
cement is dry. If the joint is adjusted
after it is set, the joint will be ruined.
See Table 2 for recommended set
time.
Step 13. Wipe excess cement from the pipe.
A properly made joint will show a
bead of cement around its entire
perimeter. Any gaps may indicate
insufficient cement.
Step 14. The system shall not be pressurized
until the joints have cured (set) at
least as long as recommended by
the manufacturer. If the manufac-
turer's recommendation is not
available, the following cure times
are required. See Table 2.
2.7.7 Prohibited Joints. Piping shall not be
threaded. Female screwed fittings, with
CPVC threads, shall be prohibited. Joints
made with adhesives shall be prohibited.
2.7.8 Threaded Joints. When threads are
required, molded male adapters shall be
used.
2.7.9 Location. CPVC threaded joints shall be
accessible.
2.7.10 Lubricants. Only thread tape or thread
lubricant approved specifically for use with
CPVC shall be used. Conventional pipe
thread compounds, putty, linseed oil based
products, and unknown mixtures are
prohibited.
2.7.11 Tightening. Joints shall be tightened
approximately 1-1/2 turns past hand tight.
CAUTION: Hand tight refers to the number
of threads to reach hand tight with metal pipe.
Small sizes of CPVC can be bottomed by
hand pressure alone. DO NOT overtighten.
2.7.12 Special Joints
2.7.12.1 Transition Joints. Transitions from CPVC
tubing to metal piping and valves shall be
made only with listed transition fittings
suitable for that purpose. When required, the
transition fittings shall be designed in such a
manner that it can be anchored to a building
member to prevent rotation. [UPC 316.2]
2.7.1 2.2 Soldering. Soldered metal joints shall not
be made closer than 18 inches (457 mm) to
any already installed plastic to metal
adapter in the same water line.
IS 20
2.7.12.3 Hose Bibbs. Hose bibbs shall be cormected
only to metal system components which are
adequately anchored to the building
structure. The CPVC plastic system shall
terminate in wall.
2.8 Pressure Relief Valves
2.8.1 CPVC Piping. CPVC piping used for
temperature and /or pressure relief valve
drain lines shall be graded to the outlet end
and shall be supported at 3 foot (914 mm)
intervals both vertically and horizontally.
2.9 Installation, Inspection and Testing
2.9.1 Finish Nipples. Finish nipples shall be
connected to drop ear elbows or other
fittings listed for preventing rotation. Finish
nipples shall not be CPVC but CPVC stub
outs for fixture connections shall be
permitted. [UPC 609.0]
2.9.2 Location. CPVC tubing shall not be installed
so as to be subjected to direct sunlight after
installation, and shall not be installed on the
surface of the building unless it is protected
by paint or a protective covering.
2.9.3 Water Heaters. There shall be a minimum
of six (6) inches (152 mm) of metallic piping
between a gas water heater connection and
CPVC tubing. Piping shall not be installed
down stream from any instantaneous type
(coil or immersion) water heater or closer
than six (6) inches (152 mm) developed
length upstream.
2.9.4 Under Slab. Pipe shall be installed in
trench with uniform support. Trenches shall
be backfilled to a depth of six (6) inches (152
mm) with clean earth, sand, or other
approved material which shall not contain
sharp rocks, boulders, cinder fill, or other
materials which w^ould damage or break the
piping. Pipe shall be stubbed up and all
ends shall be capped. The system shall be
filled with water and all air shall be bled off.
The system shall be pressure tested under a
water pressure which is not less than the
working pressure under which it is to be
used for a minimum of two (2) hours. All
leaks shall be corrected. Foam pipe
insulation shall be installed on all stub ups
to prevent damage during concrete pour
and finishing.
2.9.5 Identification. A permanent sign with the
legible words "This building has non-
metallic interior water piping" shall be
fastened on or inside the main electric
service panel.
391
IS 20
UNIFORM PLUMBING CODE
TABLE 2
Joint Cure Schedule
Temperature
Range of Pipe
and Fittings
during assembly
and cure
Minimum Joint
Set Time, hrs.
(Step 12)
Minimum Cure Time
before testing,
hrs. (Step 14)
Minimum Time
before putting
system into service
at 80 psi/160°F
(71 °C), hrs.
Pipe Size
1/2-1 in.
(12.7-25.4 mm)
1-1/4 -2 in.
(32-51 mm)
°F °C
60-100 16-38
40-60 4-16
1/2
1
1
2
2
4
24
48
TABLE 3
8 Feet per Second
Pipe
Size
Pipe Sch. 40
GPM Ft.* FV**
FU FU
Pipe
GPM
Sch. 80
Ft.* FV**
FU FU
Tubing SDR 11
GPM Ft.* FV**
FU FU
1/2
3/4
1
1-1/4
1-1/2
2
8 9-
13 19
22 33
37 74 5
51 129 50
81 ?95 170
6
11
18
32
44
74
7
15
26
55 15
104 36
?45 174
5 6 ~
10 13
17 24
25 42 8
35 66 20
59 170 73
*Flush Tank Fixture Units
**Flush Valve Fixture Units
Table 3 (Metric)
2.4 Meters per Second
Pipe
Pipe
Sch. 40
Pipe
Sch. 80
Tubing
SDR 11
Size
L/minFt.* FV**
L/min
Ft.* FV**
L/min
Ft.* FV**
FU FU
FT FU
FU FU
12.7
30.3
9
22.7
7
18.9
6
19.1
49.2
19
41.6
15
37.9
13
25.4
83.3
33
68.1
26
64.3
24
32
140.0
74 5
121.1
55 15
94.6
42 8
38
193.0
129 50
166.5
104 36
132.5
66 20
51
JII6.6
295 170
280.1
245 124
223.3
170 73
*Flush Tank Fixture Units
**Flush Valve Fixture Units
2.9.6
2.9.7
2.10
2.10.1
Position of Marl<ing. When installed,
piping and fittings shall be positioned so
that when practical, identifying markings
shall be readily visible for inspection.
Testing. Air testing is prohibited.
Sizing
Method. Piping shall be sized in accordance
with UPC Section 610.0. When Appendix A
is applicable, use Chart 1 or 2 as
appropriate. Flow velocities shall be limited
to a maximum of 8 feet per second (2.4
mps). See Table 3. [UPC 610.1]
ADOPTED: 1982
REVISED: 1984, 1985, 1989, 1990, 1991, 1992,
1993, 1995, 1996, 1997, 2000, 2003,
2005
392
CPVC SOLVENT CEMENTED HOT AND COLD
WATER DISTRIBUTION SYSTEMS
Friction Loss in Lbs. per Sq. In. pen 00 Ft. Run
0.1 .2 .3 .4 .5 .6 .7 .8 1 i 3 4 5 S 7 8 10 20 30
IS 20
5060 80 100
CHART 1
o
Plastic SDR II
Tubing
Vety Smooth
C = 150
— 1
-
*^
^
?•
y
^
^
r^
f^
^'
^x
,^
'f
,''
/
**
/
«*■
(^
*>
^
i^
y
\
,y
^
.^
f?
t*
<
/"
\
\
,/
y
<<'
/
ft'
,aP?
\
V
«•
i^
x^
y
,of>1
>
s
f
n
^
y
<*
^
L
\
^
y^
y
^
f
*
«•
\
t
l*^
H
¥>
'.
-^
^
^
f^
^
^
*<
J
<
\
s
y
\
\
^
v*
y^
I**
^
y
y
X
^
*"
\
\:'
I*
l*
V
^
K
;»*
\
b
<,
^
\^
V
y
y
y
\
¥
•^
\
ir'
Am^
"A
<*>
'\ 1
—
—
?"
^
™^
, \
\
^''V
\
y
V
<,
«l
\
1
L
.-^
M
tt
/
\
»•
^
r
s
\
^
V
V
\
^
V
y
^
^^
\
I>
_^
X'
V
f
\
•
\
^ \jf
\
^
l**
^
4
*
y
s
^
o;'
N
<1
■n
k
IP-
S;
\
V
*''
>
*-
^
J
>^
\
\
y
\il^
^
\
X
^
V
^
\
tP
\
v.^
\.
\
y
V
^
y
V
V
\
\
\
\
\
X
>
»>
\
\
^
>
\
\
\
\
X
X
•^
.*'
^
1
V'
(C
y
\
^
y
V
V
>
\
\
\
y^*
y
^
^
^
y
i"
\
s
\
\
V
>
\
\
\
\
\
_jt
k
\
\
\
y
^
y
\
>
.X
^
>
\
V
V
^^
^
*
\
1
V
\
\
\
\
^»^_
^
i*
>
V
\
>
>
\
V
>
\
s
\
>
s
\
>
i
<f
*
t^
\
s
\
s
\
V
\
^
^
>*
\
Ik
\
>
^
s
\
>
s
_>
\
\
\
V
\.
*s
y
\
^
J
^
k.
^„
>
V
^
V
N
,2 ,3 ,4 .5 ,6 ,7 .8 1 2 3 4 5 6 7 8 10 20 30 40 SO 60 80 100
Friction Loss in Lbs. per Sq. In. per 100 Ft. Run
CHART 2
Friction Loss in Lbs. per Sq. In. per 100 Ft. Run
.4 .5 .6 .7 .8 1 2 3 4 6 6 7 8 10 20 30 40 50 60 80 100
Q
SS 5
& 4
Sched
40 IPS
^
■^
y
y
Vary Smooth
C= 150
if^
*
-/
y
y
y
y
^
^'
**i
y
iif
li
^
y
i0*
^
*^
>
f
>
\
V
,«
."^
y
.^4
.,eV,
\
\
>
J
y
y
ON^
r
\
^
X
\
,^
^
^
.^
V
;
^
.
\t
^
y
,
«f
' \
V
y
Y
^
\
y
**
:^-
y
^
V
\
'"
V
^
'
>
y
y
^
^
'
^
.y
\
/^
y
1^
y
^
y
A
\
t^
^
«•
C
y
\
S
f
^
^
V
^
««
y
y
/"
y"
y
^
y
\
y
p;
ft
\
\
f
\
\
s
^
y
ii>
X
y
X
\
^
("^
y
r*
i \-^
^
\
X"
.
^
1 ,
V
<ii1""\.
.
~ ~
\
,y
¥"
V
\
\
^
\
V"
i^
\
cy'
I
y
i»^
'^
y
^
\
i>
^-
Sj
V
\
y
^
<>
*^
^
■^
^x*
N
\
,**
\
\
\
y
\
,«#
•^
^^
Cf
J
f
w
\
\
\
J
y
\
«»
^*
\
^
\
^
y
,^
<*
\t5
^
(
>
V
V
\
N
if
y
\
mf
**
\
nH
r
>
\
s
\
\
\
\
y
\
<*
<^
^
\
^i
\
\
\
\
^L
y
\
^y
y
A
^
\
*>
.*'
*^
»<
*
\
1
%
^
>
\
y
\
>
\
^
"y
\
L'
\
>
V
\
\
r"
y
k
\
\
\
V
>
L
k
y
\
V
\S'
\
\
\
\
s
j»
y
V
\
y
T
^
V
\
^
\
V
y
>
k
k
^
\
N
\
\
^
s
k
\
V
\
1
^
\
s
t
s
^
\
\
\
\
>
\
N
\^
\
-1
V,
y
^
\
»k.
S
.5.6,7.8 1 2 3 4 5 6 7 8 10 20 30 40 50 60 80 100
Friction Loss in Lbs. per Sq. In. per 100 Ft. Run
393
IS 20
UNIFORM PLUMBING CODE
CPVC Pipe SDR 11 (ASTM D 2846)
Calculated Loop (offset) Lengths with 0r of approx. 80°F
Length of Run in Feet
Nominal
40 60 80
100
Pipe Size
Loop Length (£) in inches
1/2"
22 27 31
34
3/4"
26 32 36
41
1"
29 36 41
46
1-1/4"
32 40 46
51
1-1/2"
35 43 50
56
2"
40 49 57
64
Assume Modulus & Stress at 160°F
CPVC Pipe Schedule 80 (ASTM F441)
Calculated Loop (offset) Lengths with 0r of approx. 80°F
Length of Run in Feet
Nominal
Pipe Size
40 60 80
Loop Length (£) in inches
100
2-1/2"
3"
4"
6"
8"
10"
47 57 66
52 63 73
58 72 83
71 87 100
81 99 114
90 111 128
74
82
92
112
128
143
Assume Modulus & Stress at 160°F
CPVC Pipe Schedule 11 (ASTM D 2846)
Calculated Loop (offset) Lengths with 0r of approx. 100°F
Length of Run in Feet
Nominal
20 40 60 80
100
Pipe Size
Loop Length (£) in inches
1/2"
17 24 30 34
39
3/4"
.20 29 35 41
46
1"
23 33 40 46
52
1-1/4"
26 36 44 51
57
1-1/2"
28 , 39 48 56
62
2"
32 '45 55 64
71
Assume Modulus & Stress at 160°F
£ = V 3ED(0L)/2S
Where £ - loop length in inches
E = modulus of elasticity at maximum temperature, psi
D = outside diameter of pipe, inches
0L = change in length due to change in temperature, inches
S = working stress at maximum temperature, psi
394
CPVC SOLVENT CEMENTED HOT AND COLD
WATER DISTRIBUTION SYSTEMS
IS 20
CPVC Pipe Schedule 80 (ASTM F441)
Calculated Loop (offset) Lengths with 0r of approx. 100°F
Length of Rim in Feet
Nominal
Pipe Size
40 60 80
Loop Length (£) in inches
100
2-1/2"
3"
4"
6"
8"
10"
52 64 ' 74
58 71 82
65 80 92
79 97 112
91 111 128
101 124 143
83
91
103
125
143
160
Assume Modulus & Stress at 160°F
Thermal
Expansion (inches)
Length of
0r SOT 0r ioo°F
Run (feet)
20
0.65 0.82
40
1.31 1.63
60
1.96 2.45
80
2.61 3.26
100
3.26 4.08
0L = Lp X C X 01
0L = change in length of pipe in inches
Lp = length of pipe in inches
C = coefficient of thermal expansion for CPVC, 3.4 X 10'^ in/in/ °F
0r = change in temperature in °F
395
IS 20 UNIFORM PLUMBING CODE
396
Installation Standard
For
WELDED COPPER AND COPPER ALLOY WATER TUBE
lAPMO IS 21-2003
1.0 SCOPE
This standard shall govern the installation of
welded copper and copper alloy water tube
in potable hot and cold water systems.
Installation, material, and inspection shall
comply with the current edition of the
Uniform Plumbing Code [UPC]™ published
by the International Association of Plumbing
and Mechanical Officials and this standard.
Note: The following sections of the Uniform
Plumbing Code apply to welded copper and copper
alloy water tube.
103.5.3 Test of Systems
301.1 Minimum Standards
310.0 Workmanship
311.0 Prohibited Fittings and Practices
313.0 Protection of Piping, Materials,
and Structures
314.0 Hangers and Supports
316.1 Types of Joints
316.1.2 Wiped Joints
316.1.3 Solder and Sweat Joints
316.2 Special Joints
316.2.1 Copper Tubing to Screw Pipe Joints
317.0 Increasers and Reducers
Chapter 6 Water Distribution
604.0 Materials
604.1 Materials, Water Pipe and Fittings
604.2 Water Piping
604.3 Marking of Tubing
604.4 Flexible Water Connectors
604.7 Restriction of Used Piping
606.1.1 Flared Joints
606.2.1 Use of Joints, Copper Water Tube
608.0 Relief Valve Drains
609.0 Iristallation, Inspection, and Testing
610.0 Size of Portable Water Piping
705.3.3 Ground Joint, Flared or Ferrule
Cormections
811.1 Chemical or Industrial Waste
903.2 Use of Copper Tubing
Table 14-1 Standards
ANSI B 16.18
ANSI B 16.22
ASTM B 447
Cast Copper Alloy Solder-Joint
Pressure Fittings
Wrought Copper and Copper
Alloy Solder Joint Pressure
Fittings
Standard Specification for
Welded Copper Tube
Appendix A Chart A-4 Friction Loss
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Materials. Materials shall comply with
the appropriate standard in Table 14-1 of
the UPC.
Note: The nominal or standard size of
copper and copper alloy welded water
tube is always 0. 125 inch (3.8 mm) or 1/8
inch (3.8 mm) smaller than the actual
outside diameter dimension of the tube.
For example, 3 inch (76 mm) nominal size
copper plumbing, tube measures 3- 1/8
inch (79.2 mm) O.D., 1/2 inch (12.7 mm)
nominal size copper plumbing tube
measures 5/8 inch (15.9 mm) O.D., etc.
2.2 Use of Copper Tubing
2.2.1 Markings. Markings shall be visible for
inspection. [UPC 903.2]
2.2.1.1 Water tube shall bear the following
incised marked at not over 18 inch (457
mm) intervals:
(a) Manufacturer's name or trademark;
(b) Tube type; and
(c) Country of origin.
2.2.1.2 All hard drawn tube shall be identified
throughout its entire length by a colored
marking not less than 3/16 inch in height,
including legend repeated at intervals not
greater than 3 feet (914 mm). The legend
shall include the type of tube, welded,
ASTM specification, name or trademark of
the manufacturer or both, and the country
of origin.
(a) Tube listed by lAPMO that is covered
by this standard shall be labeled with
the designated lAPMO certification
mark to show compliance with this
standard.
397
IS 21
UNIFORM PLUMBING CODE
2.3 Joints
2.3.1 General Information. Copper tube and
fittings maybe joined in a number of
ways, depending on the purpose of the
system. Soldering and brazing with
capillary fittings are the methods used
most.
The American Welding Society defines
soldering as a joining process which takes
place below 840°F (449°C) and brazing as
a similar process which occurs above
840°F (449°C) but below the melting point
of the base metals. In actual practice for
copper systems, most soldering is done at
temperatures ranging from about 350°F to
550°F (177° to 288°C), while most brazing
is done at temperatures ranging from
1100° F to 1500°F (593°C to 816°C). The
choice between soldering or brazing will
generally depend on operating conditions.
Solder joints are generally used where the
service temperature does not exceed 205°F
(96°C), while brazed joints can be used
where greater strength is required, or
where system temperatures are as high as
400°F (204°C). [UPC 316.1]
2.3.2 Fittings for Soldered, Brazed, and
Flared Joints. Fittings are available in all
standard tube sizes and in a wide variety
of types to cover needs for plumbing. They
can be either soldered or brazed, although
brazing cast fittings requires care.
Wrought copper pressure fittings are also
available over a wide range of sizes and
types. These, too, can be joined by either
soldering or brazing and wrought fittings
are preferred where brazing is the joining
method. Otherwise, the choice between
cast and wrought fittings is largely a
matter of the user's preference. Flared-tube
fittings provide metal-to-metal contact
similar to ground joint unions; both can be
easily taken apart and reassembled. They
are especially useful where residual water
cannot be removed from the tube and
soldering is difficult. Flared joints may be
required where a fire hazard exists and the
use of a torch to make soldered or brazed
joints is not allowed.
2.3.3 Solders
Note: Users of the Uniform Plumbing
Codes are reminded ttiat provisions of ttie
Federal Clean Drinking Act of 1986, which
ail must obey, forbid the use of solder
which contains in excess of 0.2% of lead,
by weight in potable water systems. The
2.3.4
provisions of the act are incorporated in all
ordinances, statutes, state and municipal
regulations by reference and by operation
of law.
The selection of a solder depends on the
operating pressure and temperature of the
line. Consideration should also be given
to the stresses on the joint caused by
thermal expansion and contraction.
However, stresses due to temperature
changes should not be significant in two
commonly encountered cases: when tube
lengths are short, or when expansion
loops are used in long tube runs.
Solder is generally used in wire form, but
paste-type solders are also available. These
are finely granulated solders in suspension
in a paste flux. When using paste-type
solders, observe these four rules:
1. Wire solder must be applied in
addition to the paste to fill the voids
and assist in displacing the flux,
otherwise the surfaces may be well
"tinned" and yet there may not be a
good joint with a continuous bond.
2. The paste mixture must be thoroughly
stirred if it has been standing in the
can for more than a very short time, as
the solder has a tendency to settle
rapidly to the bottom.
3. The flux cannot be depended on to
clean the tube. Cleaning should be
done manually as is recommended
for any other flux and solder.
4. Remove any excess flux.
Solders are available containing small
amounts of silver or other additives to
impart special properties. Such solders
may require special fluxes. The
manufacturer's recommendations should
be consulted regarding proper procedures
and fluxes for such solders and about the
expected properties.
Soldering Flux
The functions of the soldering flux are to
remove residual traces of oxides, to
promote wetting, and to protect the
surfaces to be soldered from oxidation
during heating. The flux should be
applied to clean surfaces and only enough
should be used to lightly coat the areas to
be joined.
An oxide film may reform quickly on
copper after it has been cleaned.
Therefore, the flux should be applied as
soon as possible after cleaning.
398
WELDED COPPER AND
COPPER ALLOY WATER TUBE
CAUTION
Careless workmanship, especially during
flux applications, can result in corrosion
of the tube long after the system has been
installed. If excessive flux is used, the
residue inside the tube can cause
corrosion. In an extreme case, such
residual flux can actually lead to
perforation through the tube wall causing
leakage. To guard against this danger, it is
important (1) to choose a flux that is not
too corrosive, and (2) to use only the
minimum amount actually needed to
make the joint.
2.3.5 Solder Joints
Soldering and brazing both involve basic
steps, which must be executed with care
and craftsmanship. The steps are:
(1) Measuring
(2) Cutting
(3) Reaming
(4) Cleaning
(5) Fluxing
(6) Assembly and support
(7) Heating
(8) Applying the filler metal
(9) Cooling and cleaning
Each step contributes to a strong,
dependable Joint.
2.3.5.1 Measuring
Measuring the length of each tube
segment must be accurate. Inaccuracy can
compromise joint quality. If the tube is too
short it will not reach all the way into the
socket of the fitting and a proper joint
cannot be made. If the tube segment is too
long, there is danger of cocking the tube in
the fitting and putting strain on the
system which could affect service life.
2.3.5.2 Cutting
Once the tube is measured it can be cut.
Cutting can be accomplished in a number
of different ways to produce a satisfactory
square end. The tube can be cut with a
disc-type tube cutter, a hacksaw, an
abrasive wheel, or with a stationary or
portable handsaw. Care must be taken
that the tube is not deformed while being
cut. Regardless of method, the cut must be
square with the run of the tube so that the
tube will seat properly in the fitting
socket.
2.3.5.3 Reaming
All pipe and tube shall be reamed to the
full I.D. of the pipe and tube.
IS 21
Tools used to ream tube ends include the
reaming blade on the tube cutter, half-
round or round files, a pocket knife, and a
suitable deburring tool. With annealed
tube, care must be taken not to deform the
tube end by applying too much pressure.
Both the inside and the outside of the tube
may require removal of the burr.
2.3.5.4 Cleaning
The removal of oxides and surface soil is
crucial if filler metal is to flow properly
into the joint. Unremoved oxide, surface
soil, and oil can interfere with the strength
of the joint and cause failure.
Mechanical cleaning is a simple operation.
The end of the tube should be abraded
lightly using sand cloth or nylon abrasive
pads for a distance only slightly more
than the depth of the fitting socket. The
socket of the fitting should also be cleaned
using sand cloth, abrasive pads, or a
properly sized fitting brush.
Copper is a relatively soft metal. If too
much material is removed, a loose fit will
result and interfere with satisfactory
capillary action in making the joint. The
capillary space between the tube and
fitting is approximately 0.004 inch (0.1
mm). Solder or brazing filler metal can fill
this gap by capillary action. This spacing
is critical for the filler metal to flow into
the gap and form a strong joint.
Surfaces, once cleaned, should not be
touched with bare hands or oily gloves.
Skin oils, lubricating oils, and grease
impair solder flow and wetting.
2.3.5.5 Fluxing
Stir the flux before use. A good flux will
dissolve and remove traces of oxide from
the cleaned surfaces to be joined, protect
the cleaned surfaces from reoxidation
during heating and promote wetting of
the surfaces by the solder. A thin, even
coating of flux should be applied with a
brush to both tube and fitting. Do not
apply with fingers. Chemicals in the flux
can be harmful if carried to the eyes or
open cuts.
2.3.5.6 Assembly and Support
After both tube and fitting surfaces are
properly fluxed, they should be
assembled, making sure the tube seats
against the base of the fitting socket. A
slight twisting motion ensures even
distribution by the flux. Remove excess
399
IS 21
UNIFORM PLUMBING CODE
flux. Care must be taken to assure that the
tube and fittings are properly supported
with a uniform capillary space around the
entire circumference of the joint.
Uniformity of capillary space will ensure
good filler metal penetration if the
guidelines of successful joint making are
followed. Excessive joint clearance can
cause the filler metal to crack under stress
or vibration.
The joint is now ready for soldering. Joints
prepared and ready for soldering should
be conipleted the same day and not left
unfinished overnight.
2.3.5.7 Heating
Because an open flame may be used for
soldering, and because flammable gases
are used, safety precautions must be
observed. The heat is generally applied
using an air /fuel torch. Such torches use
acetylene or an LP gas. Electric resistance
tools can also be used.
Heating should begin with the flame
perpendicular to the tube. The copper
tube conducts the initial heat into the
fitting socket for even distribution of heat
inside and out. The extent of this
preheating depends upon the size of the
joint. Experience will indicate the amount
of time needed. The flame should now be
moved onto the fitting. Then move the
flame from the fitting socket back onto the
tube a distance equal to the depth of the
fitting socket. Touch the solder to the
joint. If the solder does not melt, remove it
and continue the heating' process. Be
careful not to overheat or to direct the
flame into the fitting cup. This could cause
the flux to burn and destroy its
effectiveness. When the melting
temperature of the solder has been
reached, heat may be applied to the base
of the cup to aid capillary action in
drawing the solder into the cup.
2.3.5.8 Applying tlie Filler Metal
For tube in a horizontal position, start
applying the solder slightly off-center at
the bottom of the joint. Proceed across the
bottom of the fitting and up to the top
center position. Return to the point of
beginning, overlap the starting point, and
then proceed up the incompleted side to
the top, again, overlapping the solder.
For joints in the vertical position, a similar
sequence of overlapping passes should be
made, starting wherever is convenient.
Molten solder will be drawn into the joint
by capillary action regardless of whether
the solder is being fed upward,
downward, or horizontally.
2.3.5.9 Cooling and Cleaning
After the joint has been completed,
natural cooling is best. Shock cooling with
water may cause unnecessary stress on
the joint and result in eventual failure.
When cool, clean off any remaining flux
with a wet rag.
2.3.6 Brazed Joints
Brazing is the second most commonly
used method for joining copper tube.
Making brazed joints is sinular to making
soldered joints with respect to measuring,
cutting, reaming, cleaning, assembly and
support. And as in soldering, the brazing
filler metal is melted by the heat of the
tube and fitting and draw^n into the joint
by capillary action. [UPC 316.1.7]
The major differences between soldering
and brazing are the:
• Type of flux used,
• Composition of filler metal, and
• Amount of heat required to melt the
filler metal.
2.3.6.1 Brazing Flux
The fluxes used for brazing copper joints
are different in composition from
soldering fluxes. The two types cannot be
used interchangeably. Brazing fluxes are
water based, whereas most soldering
fluxes are petroleum based. Similar to
soldering fluxes, brazing fluxes dissolve
and remove residual oxide from the metal
surface, protect the metal from
reoxidation during heating and promote
wetting of the surfaces to be joined by the
brazing filler metal.
Fluxes also provide the draftsman with an
indication of temperature. Application of
the flux is the same as when soldering. If
the outside of the fitting and the heat-
affected area of the tube are covered with
flux (in addition to the end of the tube and
the cup), oxidation will be prevented and
the appearance of the joint will be greatly
improved.
2.3.6.2 Brazing Filler Metals
There are two general types of brazing
filler metal used for joining copper tube.
Classified according to their components.
400
WELDED COPPER AND
COPPER ALLOY WATER TUBE
they are: BCuP (Brazing-Copper-
Phosphorous) and BAg (Brazing-Silver).
BCuP filler metals are preferred for
joining copper tube and fittings. The
phosphorous in them acts as a fluxing
agent and the lower percentage of silver
makes them relatively low cost. When
using copper tube, wrought copper
fittings, and BCuP brazing filler metal,
fluxing is optional. However, when cast
fittings are brazed, flux must be used.
2.3.6.3 Heating
Oxy/fuel torches are generally used for
brazing because of the higher
temperatures required.
Recent innovations in tip design make
air /fuel torches useful on a wider range of
sizes for brazing.
When working at brazing temperatures,
safety precautions must be followed and
care taken to protect both the operator
and the materials being used.
The heating operation is the same as for
soldering. First preheat the tube and then
the tube and fitting. When the filler metal
starts to melt, apply heat at the base of the
fitting socket to help draw the brazing
filler metal in by capillary action.
2.3.6.4 Applying Brazing Filler Metal
Remember to allow the heat of the joint,
not the flame, to melt the filler metal. The
melted filler metal will be drawn into the
joint by capillary action. It is very
important that the flame be in continuous
motion. It must not be allowed to remain
on any one point long enough to burn
through the tube or fitting.
If the filler metal fails to flow, or has the
tendency to ball-up, it indicates either that
there is oxide on the surfaces being joined
or that the parts to be joined are not hot
enough. If the filler metal refuses to enter
the joint, the fitting cup is not hot enough.
If it tends to flow over the outside of
either part of the joint it indicates that part
is overheated. When the joint is
completed, a continuous fillet should be
visible completely around the joint.
Large diameter tube is more difficult to
heat to the desired temperature. The use of
a heating tip or rosebud may be necessary
to maintain the proper temperature over
the area being brazed. Once total heat
control is attained, follow the same
procedures used for smaller tube.
IS 21
2.3.6.5 Cooling and Cleaning
When the brazed joint is finished, allow it
to cool naturally. Flux residues and some
oxides formed by heating can be removed
by washing with hot water and brushing
with a stainless steel wire brush.
2.3.7 Flared Joints
2.3.7.1 Flared Joints with Impact Flaring
Tools:
Step 1 Cut the tube to the required
length.
Step 2 Remove all burrs. This is very
important to assure metal-to-
metal contact.
Step 3 Slip the coupling nut over the
end of the tube.
Step 4 Insert flaring tool into the tube
end.
Step 5 Drive the flaring tool by hammer
strokes, expanding the end of the
tube to the desired flare. This
requires a few moderately light
strokes.
Step 6 Assemble the joint by placing the
fitting squarely against the flare.
Engage the coupling nut with the
fitting threads. Tighten with two
wrenches, one on the nut and one
on the fitting. [UPC 606.1.1]
2.3.7.2 Flared Joints with Screw-Type Flaring
Tools:
Steps 1-3 Same as for impact flaring
previously described.
Step 4 Clamp the tube in the flaring
block so that the end of the tube
is slightly above the face of the
block.
Step 5 Place the yoke of the flaring
tool on the block so that the
beveled end of the compressor
cone is over the tube end.
Step 6 Turn the compressor screw
down firmly, forming the flare
between the chamber in the
flaring block and the beveled
compressor cone.
Step 7 Remove the flaring tool. The
joint can now be assembled as
in Step 6 for impact flaring.
[UPC 606.2.1]
401
IS 21
UNIFORM PLUMBING CODE
3.0
3.1
3.2
2.4 Sizing
2.4.1 Velocity.
Note: There are various hydraulic
formulas for the flow of water in pipe. With
high velocity and attendant turbulent flow,
there can be excessive noise and piping
wear. [UPC 610.1]
The designer should aim for maximum
flow velocities in the range of 5 to 8 feet
per second (1.5 - 2.4 meters per second) to
minimize noise and erosion problems. For
the smallest tube sizes, the designer is
wise to work at the bottom of this range,
as a n\aximum, to guard against local high
velocities building up due to faulty
workmanship (e.g. burrs at tube ends
which are not properly reamed) or
unusually numerous changes in flow
direction.
GENERAL INFORMATION
It is not possible to cover all the variables of
a plumbing system; however, the following
information may prove helpful:
Expansion Loops - Copper tube, like all
piping materials, expands and contracts with
temperature changes. Therefore, in a copper
tube system subjected to excessive
temperature changes, the line tends to
buckle or bend when it expands unless
compensation is built into the system. Severe
stresses on the joints may also occur. Such
stresses, buckles, or bends are prevented by
the use of expansion joints or by installing
offsets, "U" bends, coil loops, or similar
arrangements in the tube assembly. These
specially shaped tube segments take up
expansion and contraction without excessive
stress. The expansion of a length of copper
tube may be calculated from the formula:
Temperature Rise (°F) x length (feet) x
12 (inches per foot) x
Expansion Coefficient (inch per inch per °F) =
Expansion (inches), or
Temperature Rise (°C) x Length (meter) x 1000 (mm
per meter) x Expansion Coefficient
(mm per mm per °C) = Expansion (mm).
Calculations for expansion and contraction
should be based on the average coefficient
of expansion of copper which is 0.0000094
per degree F (1.692 x 10"5 per degree C),
between 70°F and 212°F (21 °C and 100°C).
For example, the expansion of each 100 feet
(30.5 meters) of length of any size tube
heated from room temperature (70°F) to
170°F (a 100°F (55.6°C) rise) is 1.128 inches
(28.7 mm).
100°Fx 100 feet X 12 inch/foot x 0.0000094
inch/inch/°F =1.128 inch, or
55.6°C X 30.48 mm x 1000 mm/m x 1.692x10-5
mm/mm/°C = 28. 7 mm
3.3 Tube Supports - See Section 314.0 and
Table 3-2 of the Uniform Plumbing Code.
3.4 Bending - Copper tube, properly bent, will
not collapse on the outside of the bend and
will not buckle on the inside of the bend.
Tests demonstrate that the bursting strength
of a bent copper tube can be greater than it
was before bending. Because copper is
readily formed, expansion loops and other
bends necessary in an assembly are quickly
and simply made if the proper method and
equipment are used. Simple hand tools
employing mandrels, dies, forms, and fillers,
or power-operated bending machines, are
used.
3.4.1 Both annealed tube and bending-temper
tube can be bent with hand benders. The
proper size bender for each size tube must be
used. Usually the size of the tool
corresponds to the nominal outside diameter
of the tube, not the standard tube size. For a
guide to the typical bend radii, see the
following bending guide for copper tube.
ADOPTED:
REVISED:
1980
1989,2003
402
WELDED COPPER AND
COPPER ALLOY WATER TUBE
IS 21
BENDING GUIDE FOR COPPER TUBE
Tube Size,
In. (mm)
Tube Type
Temper
Minimum
Bend Radius,
In. (mm)
Type of Bending
Equipment
1/4 (6.4)
K,L
Annealed
3/4 (19.1)
Lever type
3/8 (9.5)
K,L
K,L,M
Annealed
Drawn
1-1/2 (38)
3 (76)
1-3/4 (45)
Lever or gear type
None; by hand*
Gear Type
1/2 (12.7)
K,L
K,L,M
Annealed
Drawn
2-1/4 (57)
4-1/2 (114)
2-1/2 (64)
Lever or gear type
None; by hand*
Gear type
3/4(19.1)
K,L
K
L
K
K,L
Annealed
Drawn
3 (76)
4-1/2 (114)
6 (152)
3 (76)
4 (102)
Lever of gear type
None; by hand*
None; by hand*
Gear type
Heavy-duty gear t5rpe
1 (25.4)
K,L
Annealed
4 (102)
7-1/2 (191)
Gear type
None; by hand*
1-1/4(31.8)
K,L
Annealed
9 (229)
None; by hand*
* When bending by hand, without the use of bending equipment, a circular
wooden disc is used. The radius of the disc should be about 1/4 to 1/2 inch (6.4 to
12.7 mm) less than the minimum bend radius shown.
403
IS 21 UNIFORM PLUMBING CODE
404
1.0
1.1
Note:
Installation Standard
for
TRENCHLESS INSERTION OF
POLYETHYLENE (PE) PIPE FOR SEWER LATERALS
lAPMO IS 26-2003
SCOPE
This standard shall govern the Trenchless
Installation of Polyethylene (PE) pipe for use
in sanitary and storm sewers. The installed
pipe shall comply with the requirements of
the Uniform Plumbing Code (UPC™)
published by the International Association
of Plumbing and Mechanical Officials
(lAPMO) as to grade and connections to
existing pipe and shall also comply with this
standard.
The following sections of tfie Uniform
Plumbing Code apply.
103.5.3 Testing of Systems
103.5.4.2 Responsibihty
103.5.5 Other Inspections
103.5.5.1 Defective Systems
103.6.2 Other Connections
218.0 Definition of PE
301.1 Minimum Standards
310.0 Workmanship
313.0 Protection of Piping,
Materials, and Structures
315.0 Trenching, Excavation, and
Backfill
316.2.3 Plastic Pipe to Other
Materials
Chapter 7 Sanitary Drainage
701.2 Fittings
ABBREVIATIONS
ASTM American Society for Testing Materials
lAPMO International Association of Plumbing and
Mechanical Officials
UPC Uniform Plumbing Code
2.0 PRODUCT REQUIREMENTS
2.1 Minimum Standards
2.1.1 Materials
Materials shall comply with the following:
The polyethylene pipe used is covered by
the ASTM standards listed later in this
standard. [UPC 301.1]
Materials
HDRE Extra High Molecular
Weight 3408 SDR 17 Pipe
Socket-Type PE Fittings
for Outside Diameter-Controlled
Polyethylene Pipe
ASTM
Standard
F714
D2683
Note: The HDPE 3408 SDR 17 pipe used in this
process was selected because of its ability to
retain its circular shape even when bent on a 4-
foot radius during and after installation.
2.1.2
Table 14-1 Standards
ASTM D 1412
ASTM D 2239
ASTM D 2683
ASTM D 2447
ASTM D 2657
ASTM D 3261
ASTM F 714
ASTM F 894
lAPMO PS 25
2.2
Protection of Pipe
2.2.1
Storage and Handlinc
Pipe shall be stored in a way to protect it
from mechanical damage (slitting,
puncturing, etc.). It shall be stored under
cover to keep it clean and avoid long term
exposure to sunlight. Exposure to sunlight
during normal construction periods is not
harmful.
2.3 Types of Joints.
PE joints shall be made as follows:
2.3.1 Molded Rubber Coupling Joints
Molded rubber coupling joints shall be
installed in accordance with Appendix I of
the UPC and with Section 705.1.6.
2.3.2 Shielded Coupling Joints
Shielded coupling joints shall be installed in
accordance with Appendix I of the UPC and
with Section 705.1.8.
405
IS 26
UNIFORM PLUMBING CODE
2.3.4 Hubless Cast Iron Pipe Joints
Hubless cast iron pipe joints shall be
installed in accordance with Appendix I of
the UPC and with Section 705.1.9.
2.3.5 Heat Fusion Joints.
Heat fusion joints shall be made according
to the manufacturer's procedure, installation
instructions, and either ASTM D 2659 or
ASTM D 3261 and shall meet the
requirements of Section 701.1 of the UPC.
2.4 Trenciiiess Installation of sewers will be as
follows:
I. Preliminary Steps
Inspect the inside of the sewer line
using a television camera and video
tape recorder to ascertain the line
condition. Mark the details revealed
by the video inspection including:
1. The ground surface to
show the location of the
lateral tie of the city wye.
2. The line location with an
arrow in the street pointing
back at the lateral.
3. The property denoting the
lateral location.
4. The locations of the
proposed excavations.
Obtain utility line identification
service contact information and all
applicable permits.
II. Excavation
In addition to the above markings,
the local utility companies will
mark utilities. Considerations are
soil density; clearance from
obstacles, utilities, and structures;
location of bends; and water service
locations. Excavations and shoring
shall be in accordance with
jurisdictional safety requirements.
III. Setup
Fuse the proper length of
polyethylene pipe in accordance
with ASTM D 2657 or ASTM D 2657
and fuse the end to a small length
that is attached to the pulling head.
A rod pusher cable is pushed
through the damaged host pipe and
attached to the pulling cable, which
is then drawn through the pipe. The
clevis end of the cable is attached to
the pulling head. The pulling
equipment is then set up according
to the manufacturers instructions.
IV. Pulling
Pull the pulling head through. Once
the pull is done, complete the
connection to the existing piping.
2.5 Cleanouts
Cleanouts shall be installed in accordance
with UPC Section 707.
2.6 Inspections
The completed piping shall be internally
inspected by television camera unless
waived by the Administrative Authority.
[UPC 103.5]
2.7 Testing
Completed piping shall be subjected to
testing in accordance with Section 712.0 or
723.0 of the UPC.
ADOPTED: 1999
REVISED: 2002,2003
406
Installation Standard
for
ODOR CONTROL SYSTEMS FOR WATER CLOSETS
lAPMO IS 27-2003
1.0 SCOPE
1 .1 This standard shall govern the installation of
Odor Control Systems for Water Closets.
Installation, material and inspection shall
comply with the requirements of the
Uniform Plumbing Code (UPC™) published
by the International Association of
Plumbing and Mechanical Officials
(lAPMO) and this standard.
Note: The Building Official shall be consulted about
penetration of fire separations, height and area or
other limitations.
Note: The following sections of the Uniform
Plumbing Code apply to Odor Control Systems for
Water Closets.
Inspection
Definitions
Minimum Standards
Workmanship
Prohibited Fittings and Practices
Screwed Fittings
Protection of Piping, Materials and
Structures
Hangars and Supports
Joints and Connections
Prohibited Joints and Connections
Increasers and Reducers
Sanitary Drainage
Materials (Drainage)
Fittings
Materials (Venting)
Material Uses
Materials
Cast Bronze Solder-Joint Drainage
Fittings - DWV
Wrought Copper and Copper
Alloy Solder-Joint Drainage Fittings
Cast Iron Soil Pipe and Fittings
Specification for Hubless Cast Iron
Soil Pipe and Fittings for Sanitary
and Storm Drain, Waste, and Vent
Piping Applications
Specification for Seamless Copper
Pipe, Standard Sizes
ASTM B 302 Specification for Threadless Copper
Pipe, Standard Sizes
103.5
Chapter 2
301.1
310.0
311.0
311.8
313.0
314.0
316.0
316.4
317.0
Chapter 7
701.0
701.2
903.0
1101.3
Table 14-1
ASME B 16.23
ASME B 16.29
ASTM A 74
ASTM A 888
ASTM B 306
ASTM B 828
ASTM D 2564
ASTM D 2661
ASTM D 2665
ASTM D 3311
ASTM B 42
ASTM F 402
ASTM F 628
ASTM F 656
ASTM F 891
CISPI 301
lAPMO IS 3
lAPMO IS 5
lAPMO IS 6
lAPMO IS 9
UL 1004
Specification for Copper Drainage
Tube (DWV)
Standard Practice for Making
Capillary Joints by Soldering of
Copper and Copper Alloy Tube
and Fittings
Solvent Cements for Poly (Vinyl
Chloride) (PVC) Plastic Piping
Systems
Acrylonitrile-Butadiene-Styrene
(ABS) Sch. 40 Plastic Drain, Waste
and Vent Pipe and Fittings
Poly (Vinyl Chloride) (PVC) Plastic
Drain, Waste, and Vent Pipe and
Fittings
Drain, Waste, and Vent (DWV)
Plastic Fitting Patterns (note:
although referenced in this
standard, some of the fittings
shown in the standard are not
acceptable under the Uniform
Plumbing Code.)
Safe Handling of Solvent Cement,
Primers, and Cleaners Used for
Joining Thermoplastic Pipe and
Fittings
Acrylonitrile-Butadiene-Styrene
(ABS) Sch. 40 Plastic Drain, Waste
and Vent Pipe with a Cellular Core
Primers for Use in Solvent Cement
Joints of Poly (Vinyl Chloride)
(PVC) Plastic Pipe and Fittings
Coextruded Poly (Vinyl Chloride)
(PVC) Plastic Pipe with a Cellular
Core
Hubless Cast iron Soil Pipe and
Fittings for Sanitary and Storm
Drain, Waste and Vent Piping
Applications
Copper Plumbing Tube, Pipe and
Fittings
ABS Building Drain, Waste and
Vent Pipe and Fittings
Hubless Cast Iron Sanitary and
Rainwater Systems
PVC Building Drain, Waste and
Vent Pipe and Fittings
Electric Motors
407
IS 27
UNIFORM PLUMBING CODE
2.0
2.1
2.1.1
2.1.2
2.2
2.2.1
2.2.2
2.2.3
PRODUCT REQUIREMENTS
Minimum Standards
Materials
All materials shall comply with the
appropriate standards in Table 14-1 of the
UPC.
All pipe and fittings shall be made from
approved DWV materials and shall be
installed in accordance with the
requirements of Chapter 7 of the Uniform
Plumbing Code entitled. Sanitary Drainage.
In addition, all pipe and fittings shall be
installed in accordance with the applicable
lAPMO Installation Standard. [UPC 701.0]
Odor Control System Components
Inlet Connection - Tlie inlet for DWV odor
control systems shall be connected at the
tailpiece of the flushometer operated water
closet using a listed tee. The tee shall
immediately transition to the odor control
riser using approved DWV pipe and fittings.
Riser — The odor control riser shall be made
from listed DWV pipe no smaller than 2-1/2
inch diameter. This minimum riser size was
selected to adequately handle the required
minimum odor control air flow rate. The
riser height shall be a minimum of 6 feet as
measured from the connection at the
sanitary tee to the overhead connection at
the odor control manifold. The minimum
riser height was selected to adequately
handle the maximum possible water rise
generated during the flushometer flushing
cycle.
Manifold - The odor control manifold,
including all horizontal piping within the
odor control system, shall be 1/8" per foot
horizontally sloped back to the last riser.
The manifold shall be made from approved
DWV material no smaller than the pipe size
as determined by using Table 1 of this
Installation Standard. No traps are
permitted within the odor control piping
system.
Note: The attached Figures 1 and 2 illustrate
the basic configuration to be used for the
design of any Odor Control System installed
in accordance with this Installation
Standard.
2.3
2.3.1
2.3.2
2.4
2.4.1
2.4.2
2.5
2.5.1
System Sizing
Minimum Inlet Flow Rate - The odor
control system shall provide a minimum
average air flow rate of 5 cfm at each inlet
connection (tee).
Minimum Inlet Draft - The odor control
systern shall provide a minimum average
draft of 1/4 inch WC (water column) as
measured inside the inlet connection (tee),
or a minimum of 0.10 inch of WC at the
small perforations in the top rim of the
water closet bowl.
Exhaust Fan
The exhaust fan shall be listed for
installation in outdoor and wet locations
and in conditioned air streams up to 140°F
and shall comply with the applicable
requirements of UL 1004.
The odor control system exhaust fan shall be
installed in accordance with local building
and electrical code requirements and shall
comply with drainage venting termination
requirements of the Uniform Plumbing
Code.
System Testing
Measure the suction pressure at any
perforation of the water closet rim. The
minimum reading should be 0.10 inch of
water column.
Note: For conditions other than those
covered in Table 1 the exliaust manifold and
the main exhaust riser to the odor control
system exhaust fan shall be sized to
maintain an average air velocity of 300 ±50
feet per minute.
ADOPTED: 2001
REVISED: 2003
408
ODOR CONTROL SYSTEMS
FOR WATER CLOSETS
IS 27
TABLE 1
MAXIMUM ALLOWABLE NUMBER OF WATER CLOSETS
CONNECTED TO AN EXHAUST MANIFOLD
Pipe Diameter (inch)
2-1/2
3
4
5
6
8
Maximum No. of Water Closets
2
3
6
8
10
22
STANDARD "TEE" TO
FIT DRAIN TUBE
WATER CLOSET
ODOR CONTROL SYSTEM
EXHAUST HEADER @ 6'-0" MlN.
ABOVE POINT "A". SIZE AS
PER TABLE I .
PLUMBING CHASE
2-1/2" RISER (MlN.)
OINT "A" (REF.)
VENT
ASTE CARRIER
Figure 1
409
IS 27
UNIFORM PLUMBING CODE
-UP TO EXH. FAN
Figure 2
410
Installation Standard
For
COMPOSITE PEX-AL-PEX HOT AND PE-AL-PE COLD
WATER-DISTRIBUTION SYSTEMS
IS 28-2005
1.0 SCOPE
1 .1 This standard shall govern the installation of
composite piping in potable hot and cold
water distribution systems within and
under buildings and shall apply only to
PEX-AL-PEX and PE-AL-PE piping meeting
the requirements of ASTM F 1281 and
ASTM F 1282 and fittings meeting the
requirements of ASTM F 1974. Installation,
materials, and inspection should comply
with the current edition of the Uniform
Plumbing Code published by the
International Association of Plumbing and
Mechanical Officials, and shall also comply
with this standard and manufacturer's
installation recommendations.
NOTE: The following sections of the Uniform
Plumbing Code shall apply to composite
PEX-AL-PEX and PE-AL-PE tubing.
310.0 Workmanship
313.0 Protection of Piping, Materials,
and Structures
316.1 Types of Joints
316.2.3 Plastic Pipe to Other Materials
Chapter 6 Water Supply and Distribution
Chapter 2* DEFINITIONS
ASTM American Society for Testing and
Materials
lAPMO International Association of
Plumbing and Mechanical Officials
PEX-AL-PEX Crosslinked Polyethylene-
Aluminum-Crosslinked Polyethylene
PE-AL-PE Polyefhylen Aluminum-Polyethylene
UPC Uniform Plumbing Code as
published by lAPMO
2.0 PRODUCT REQUIREMENTS
2.1 Materials and Fittings
2.1.1 Materials. Materials shall comply with the
following requirements:
Materials
Crosslinked Polyethylene-
Aluminum-Crosslinked
Polyethylene (PEX-AL-PEX)
Polyethylene- Aluminum-
ASTM
Standard
F1281
2.1.2
2.1.3
2.2
2.2.1
Polyethylene (PE-AL-PE)
Metal Insert Fittings for
PEX-AL-PEX and PE-AL-PE
composite pipe
F1282
F1974
Piping. PEX-AL-PEX composite pipe shall
comply with ASTM F 1281. PE-AL PE
composite pipe shall comply with ASTM F
1282.
Fittings. Fittings shall be metal insert type
and shall comply with ASTM F 1974.
Fittings are limited to the following t5^es:
(a) Insert fittings or compression type
fittings; and
(b) Special listed fittings of other types.
Connections to galvanized pipe or
fittings shall be specifically
designed for that purpose.
NOTE 1: Manufacturers of fittings shall
recommend assembly procedures.
Markings
Piping. Composite piping shall be legibly
marked at intervals of not more than 5 ft.
(1.5 m) with at least the following:
(a) Manufacturer's name or trademark;
(b) ASTM F 1281(PEX-AL-PEX) or
F 1282 (PE-AL-PE);
(c) Piping size;
(d) Material type - PEX-AL-PEX or PE-
AL-PE;
(e) Pressure ratings for water and the
temperature for which the temperature
rating is valid;
(f) Mark of an acceptable certification
agency; and
(g) Manufacturer's date and material code.
[UPC 301.1.2]
The elevated temperature and pressure
ratings for PEX-AL-PEX and PE-AL-PE in
accordance with ASTM F 1281 and ASTM F
1282 are:
PEX-AL-PEX
(orange colored)
200 psi
125 psi
at 73°F
at 180°F
PEX-AL-PE
(blue colored)
200 psi
100 psi
at 73°F
at 180°F
411
IS 28
2.2.2 Fittings. Fittings shall be marked with at
least the following:
(a) Manufacturer's name or trademark or
other acceptable markings; and
(b) The mark of an acceptable certification
agenc; and
(c) If size permits, ASTM F 1974. [UPC
301.1.2]
2.2.3 Position of Markings. When practical,
markings shall be visible for inspection.
Markings shall be visible prior to
installation.
2.3 Protection of Piping
2.3.1 Abrasion. Piping passing through metallic
studs, joists, or hollow masonry walls shall
be protected from abrasion or sharp edges
by elastomeric or plastic sleeves, grommets,
conical shaped punch holes or other
approved means.
2.3.2 Puncture. Steel plate protection, minimum
18 gauge, shall be installed when the tubing
is within 1 in. (25 mm) of the nailing surface.
[UPC 313.9]
2.4
2.4.1
2.4.2
2.4.3
Exposed Piping
General - Where exposed tubing may be
subjected to mechanical damage it must be
protected.
Freezing. In areas where the system must be
drained to protect the system from freezing,
horizontal lines shall be graded to drain.
Storage. Piping shall be stored in a way to
protect the system from mechanical damage
(slitting, puncturing, etc.). Piping should be
stored undercover to keep it clean and avoid
long term exposure to sunlight. Consult
piping manufacturer for recommended
limits for outside storage.
2.5 Thermal Expansion
2.5.1 General. The linear expansion rate for PEX-
AL-PEX and PE-AL-PE is 1.56 in. (39.6 mm)
per 100 ft. (30m) of tube per 100°F (55°C)
change in temperature. No accommodation
for thermal expansion is required.
2.5.2 Clearance. Bored holes and sleeves shall
provide adequate clearance between the
piping and structure to allow for free
longitudinal movement.
2.6 Hangers and Supports
2.6.1 Vertical Piping. Vertical piping shall be
supported at every floor. Piping shall have
a mid-story guide.
UNIFORM PLUMBING CODE
2.6.2 Horizontal Piping. Horizontal piping shall
be supported according to the following
Table 1.
Table 1
Support Spacing
Nominal Diameter
1/2", 3/4", and 1"
Spacing
8' 2" (2489 mm)
2.6.3
2.7
2.8
2.8.1
2.8.2
2.8.3
2.8.3.1
2.8.4
Hangers and Anchors. Piping shall not be
anchored rigidly to a support, but shall be
secured with hangers or straps that provide
for a degree of movement and that prevent
damage to the tubing. Do not use hangers or
straps with sharp or abrasive edges. Do not
use hangers that pinch the piping. [UPC 314.0]
Inspection and Testing
A. Inspection. All tubing shall be properly
seated on to the fitting per the manu-facturer's
instructions. For crimp fittings, each crimped
joint shall be checked. Buckled, gouged, or
obviously damaged pipe shall not be used.
Consult manu-facturer's recommendations for
repair procedures.
B. Testing. Upon completion of a section
or of the entire hot and cold water supply
system it shall be tested and proved tight
under a water pressure or air test not less
than the working pressure under which it is
to be used. The water used for tests shall be
obtained from a potable source. The system
shall withstand the test without leaking for a
period of not less than fifteen (15) minutes.
Joints and Connections
Procedure. Piping should be cut with a
pipe cutter designed specifically for
composite pipe. Piping shall be cut square,
i.e. perpendicular to the length. No other
cutting m^ethods shall be used and care must
be taken to remove any excess material,
flashing, or burrs.
Tools. Fitting manufacturer's recommended
tool shall be used with the composite insert
fitting systems. For specific procedures,
follow the manufacturer's recommendations.
Transition Joints
Fittings. Transitions for composite tubing to
metal piping or valves shall be made only
with transition fittings intended for that
purpose.
Joints. Joints shall not be allowed in piping
installed in or under a concrete slab resting
on grade unless for repair within a building
412
COMPOSITE PEX-AL-PEX HOT AND PE-AL-PE
COLD WATER-DISTRIBUTION SYSTEMS
structure. All repair joints must be properly
protected with a heat shrink sleeve. All slab
penetrations shall be sleeved.
2.9 Pressure Relief Valves
2.9.1 PEX-AL-PEX Piping. PEX-AL-PEX piping
used for temperature and /or pressure relief
valve drain lines shall be graded to the outlet
end and shall be supported at a maximum of
8 ft. 2 in. (2489 mm) interval horizontally.
Vertical piping shall be supported at every
floor. Vertical piping shall have a mid-story
guide.
2.10 Installation
2.10.1 Bends. Piping shall be installed by bending
the composite pipe by hand to a minimum
radius of 5 times the nominal pipe diameter.
External bend supports or sleeves are not
required as the composite piping is rigid
after bending.
2.10.2 Damage. Kinked, buckled, gouged, or other
obvious damaged pipe shall not be used.
2.10.3 Finish Nipples. Finish nipples shall be
connected to drop ear fittings to prevent
rotation. Finish nipples shall not be PEX.
2.10.4 Hose Bibs. The piping directly connected
to any hose bib shall be so anchored that the
load on the hose bib will not strain the
composite piping.
2.10.5 Heated Joints. An open flame shall not be
applied to PEX-AL-PEX or PE-AL-PE piping
when brazing, soldering, or welding joints.
2.10.6 Working Pressure and Temperature.
Long term working pressures for the PEX-
AL-PEX shall not exceed a maximum of 125
psi (860 kPa) and the long term working
temperature shall not exceed 180°F (82°C).
Long term working pressures for the PE-AL-
PE shall not exceed a maximum of 100 psi
(690 kPa) and the long term working
temperature shall not exceed 180°F (82°C).
2.10.7 Exposure to Sunlight. Only UV stabilized
composite piping can be subjected to direct
sunlight after installation and can be
installed on the surface of the building.
Composite pipe contains an ultraviolet (UV)
inhibitor to withstand limited exposure to
UV light. Manufacturer's recommends
placing the unused portion of a coil back in
the product's box rather than storing in the
sunlight while not in use.
2.10.8 Water Heater Connections. PEX-AL-PEX
or PE-AL-PE piping shall not be installed
within the first eighteen inches (18) (457
mm) of piping connected to a water heater.
[UPC 604.13.2]
IS 28
2.10.9 Water Hammer Arrestors. A composite hot
water system will withstand repeated
pressure surges, well in excess of its rated
pressure. The Uniform Plumbing Code
requires a means of attenuating water
hammer. Consequently, water hammer
arrestors shall be required when solenoid
valves or other quick closing devices are
used in the system. In designing for such
situations, it is advisable to consult the pipe
or fittings manufacturer for recommended
surge pressure limits. Water hammer and
surge pressure calculations are reviewed in
Chapter 7, AWWA Manual M-11. [UPC
609.10]
2.11 Sizing
2.1 1 .1 Method. Piping shall be sized in accordance
with UPC Section 610.0.
When UPC Appendix A is applicable, use
Table A2. Add equivalent lengths from^
Table A3 when determining developed
length.
Maximum velocities through PEX-AL-PEX
and PE-AL-PE copper alloy fittings shall be
limited to eight (8) feet per second (fps) (2.4
mps) in cold water and five (5) feet per
second (fps) (1.52 mps) in hot water. [UPC
610.0]
413
IS 28
UNIFORM PLUMBING CODE
Table 2
Flow
Rate
1/2"
3/4"
1"
U.S.
GPM
i
\
Head Loss
PsI/c.ft. ■;
Velocity
Ftys
Head
Loss
Psi/cft.
Velocity
Ftys
Head Loss
f Psi/cft.
a-;
Velocity
Ftys
0.1
0.02
0.2
0.002
0.07
0.001
0.04
0.2
0.1
0.4
0.01
0.1
0.002
0.08
0.3
0.2
0.6
0.02
0.2
0.005
0.1
0.4
0.3
0.7
0.03
0.3
0.009
0.2
0.5
0.5
0.9
0.04
0.3
0.01
0.2
0.6
0.6
1.1
0.05
0.4
0.02
0.3
0.7
0.9
1.3
0.07
0.5
0.02
0.3
0.8
1.1
1.5
0.09
0.5
0.03
0.3
0.9
1.4
1.7
0.1
0.6
0.04
04
1.0
1.6
1.8
0.1
0.7
0.05
0.4
2.0
5.9
3.7
0.5
1.3
0.2
0.9
3.0
12.5
5.5
1.0
2.0
0.4
1.3
4.0
21.3
7.3
1.8
2.6
0.6
1.7
5.0
2.7
3.3
0.9
2.1
6.0
3.8
4.0
1.3
2.5
7.0
5.0
4.6
1.7
3.0
8.0
6.4
5.3
2.2
3.4
9.0
8.0
5.9
2.7
3.8
10.0
9.7
6.6
3.3
4.2
11.0
11.6
7.2
3.9
4.6
12.0
13.6
7.9
4.6
5.0
13.0
5.3
5.5
14.0
6.1
5.9
15.0
6.9
6.3
16.0
7.8
6.3
17.0
8.7
6.7
18.0
9.7
7.1
19.0
10,7
7.6
20.0
11.8
8.0
Table 3
Developed Length
Sizes, Inches
Type of Fittings ;
Equivalent
Length of Pipe
(Feet)
1/2
Couplings
Adapters
Elbows
Tees (Branch Flow)
Tees (On the Run)
2
2
7.5
8
2.5
3/4
Couplings
Adapters
Elbows
Tees (Branch Flow)
Tees (On the Run)
2
2
8.5
10.5
2.5
1
Couplings
Adapters
Elbows
Tees (Branch Flow)
Tees (On the Run)
2
2
9
11
2.5
414
Installation Standard
For
FLEXIBLE PVC HOSE
lAPMO SIS 1-2003
This standard shall govern the installation of
Flexible PVC Hose (with solvent cemented joints) in
Pools, Hot Tubs, Spas and Jetted Bathtubs.
Installation, material and inspection shall
comply with the current edition of the Uniform
Swimming Pool Code and Uniform Plumbing Code
published by the International Association of
Plumbing and Mechanical Officials, and shall also
comply with this Standard.
NOTE: The following sections of the Uniform
Swimming Pool Code and Uniform Plumbing
Code apply to Flexible PVC Hose.
Definitions
Materials
Piping
Joints and Connections
Tests
USPC
201.0
Table 6-1
309.0
314.0
317.0
UPC
218. Definitions of PVC
Table 14-1 Materials
310.0 Workmanship
313.0 Protection of Piping, Material, and
Structures
315.0 Backfilling
ABBREVIATIONS
ASTM American Society for Testing and Materials
lAPMO International Association of Plumbing and
Mechanical Officials
UPC Uniform Plumbing Code
USPC Uniform Swimming Pool, [Spa and Hot
Tub] Code
1.0 MINIMUM STANDARDS
1.1 Material. Materials shall perform to the
appropriate standard in Table 6 -1 of the
Uniform Swimming Pool Code.
1.2 Applicable Standards. For applicable
standards, see Table 6 -1 of the Uniform
Swimming Pool Code.
2.0 MARKINGS
2.1 Hoses, fittings, solvent cement and primer
used shall be marked with the designated
lAPMO certification mark to show
compliance with this standard.
3.0 PROTECTION OF HOSES
3.1 Storage. Unprotected hose shall not be
stored in direct sunlight. The hose shall be
stored in a way to protect it from mechanical
damage (slitting, puncturing, etc.). Exposure
to sunlight during normal construction
periods is not harmful. PVC solvent cement
shall be stored in a cool place, except when
actually in use at the job site. The solvent
cement manufacturer's specific storage
recommendations shall be followed.
3.2 Thermal Expansion. Hose shall be "snaked"
in the trench bottom with enough slack, at
least 6 in. (152.4 mm) per 100 ft. (30.5 m), to
compensate for thermal expansion and
contraction before stabilizing hose. Stabilize
hose by bringing it approximately to
operating temperature before testing and
backfilling by one of the following methods:
(a) Backfill with a layer of soil for shading.
(b) Fill with water at operating temperature.
(c) Allow to stand overnight.
3.3 Exposed Hose. Hose above grade when
located on the exterior of the building or
structure shall be protected from mechanical
damage to the satisfaction of the
Administrative Authority. Where exposed
to sunlight, the hose shall be wrapped with
at least 0.040 in. (1.0 mm) of tape or other
approved method acceptable to the
Administrative Authority.
4.0 TRENCHING, COVER, AND BACKFILL
4.1 Trenching and Cover. Trench bottoms
shall be uniformly graded and shall be of
either undisturbed soil or shall consist of a
layer or layers of compacted backfill so that
minimum settlement w^ill take place.
4.2 Backfill. Selected backfill shall be used to
provide firm continuous support and proper
compaction. Backfill over hose, except that
joints shall be left exposed. After inspection
and pressure test, complete backfill to a
minimum of 12 in. (0.3 m) cover.
5.0 INSTALLATION
5.1 Solvent Cement Joints
5.1.1 Selection. Solvent cement shall be
recommended for flexible PVC hose by the
415
SIS1
UNIFORM PLUMBING CODE
5.1.2
5.1.3
5.1.4
5.1.5
5.1.5.1
manufacturer. Follow manufacturer's
recommendations for types of solvent
cemerit for flexible PVC hose.
Handling (to maintain effectiveness). Use
solvent cement in containers no larger than 1
quart (1, liter). Keep solvent cement can
closed and in the shade when not in use.
Keep applicator submerged in solvent
cement between application. When solvent
cement becomes thicker, THROW IT AWAY.
Solvent cement shall NOT be thinned.
Size of Applicator. Follow manufacturer's
recommendations.
Application. Follow., manufacturer's
recommendations .
General Principles
To consistently make good joints, the
following should be clearly understood and
adhered to:
(a) The joining surfaces must be softened
(dissolved) and made semi-fluid.
Sufficient cement must be applied to fill
the gap between hose and fitting.
Assembly of hose and fittings must be
made while the surfaces are still wet and
fluid. :
(d) Joint strength develops as the cement
. dries. In the tight part of the joints the
. surfaces will tend to fuse together; in the
loose part the cement will bond to both
surfaces.
(e) When solvent welding flexible PVC hose
to other .than PVC fittings, follow
manufacturer's installation instructions.
5.1.5.2 Penetration and dissolving can be achieved
by the cement itself, by a suitable primer, or
by the use of both primer and cement. A
suitable primer will penetrate and dissolve
the plastic more quickly than cement alone.
In cold weather more time and additional
applications are required (see Fig. 1).
5.1.5.3 More than sufficient cement to fill the loose
part of the joint must be applied (see Fig. 2).
Besides filling the gap, adequate cement
(b)
(c)
^^m^—
\
yyj^^S^aa^)
Figure 1
Areas of Hose and Fittings to be Softened
(Dissolved) and Penetrated
layers, will penetrate the surfaces and also
remain wet until the joint is assembled.
5.1.5.4 If the cement coatings on the hose and
fittings are wet and fluid when assembly
Figure 2
Cement Coatings of Sufficient Thickness
takes place, they will tend to flow together
and become one cement layer. Also, if the
cement is wet the surfaces beneath them will
still be soft, and these dissolved Surfaces in
the tight part of the. joint will tend to fuse
togetlier (see Fig. 3).
5.1.5.5 As the solvent dissipates, the cement layer
and the dissolved surfaces will harden with
a corresponding increase in joint strength. A
Figure 3
Assembly of Surfaces While They Are Wet and Soft
good joint will take the required working
pressure long before the joint is fully dry and
final strength is obtained. In the tight (fused)
part of the joint, strength will develop more
quickly than in the looser (bonded) part of the
joint. Completed joints should not be
disturbed until they have cured sufficiently to
withstand handling. Joint strength develops
as the cement, dries. Information about
development of bond strength of solvent
cemented joints is available (see Fig. 4).
416
FLEXIBLE PVC HOSE
SIS1
Bonded Surges
Fused Suifsuces
i
ii*©«er^
Figure 4
Bonded and Fused Surfaces of Joined Hoses
5.1.6 Procedure
NOTE: Do not take SHORT CUTS. Most
failures are caused by short cuts. DON'T
TAKE A CHANCE.
Step 1 Cut hose square with hand saw and
miter box, mechanical cut-off saw,
or tube cutter designed for plastic.
Step 2 Ream and chamfer hose (to
eliminate sharp edges, beads and all
burrs).
Step 3 Clean all dirt, moisture, and grease
from hose and fitting socket. Use a
clean, dry rag.
Step 4 Check dry fit of hose in fitting. Hose
should enter fitting socket from 1/3
to 3/4 depth of socket.
Step 5 Soften inside socket surface by
applying an aggressive primer
which is a true solvent for PVC and
is recommended by the
manufacturer.
Step 6 Soften mating outside surface of
hose to depth of socket by applying
a liberal coat of the (aggressive)
primer. Be sure entire surface is
softened.
Step 7 Again coat inside socket surface
with the (aggressive) primer. Then,
without delay, apply solvent cement
liberally to outside of hose. Use
more than enough to fill any gaps.
Step 8 Apply a light coat of PVC solvent
cement to inside of socket using
straight outward strokes (to keep
excess solvent out of socket). This is
also to prevent solvent cement
damage to hose. For loose fits, apply
a second coat of solvent cement.
Time is important at this stage. (See
5.1.4)
Step 9 While both the inside socket surface
and the outside surface of the hose
are SOFT and WET with solvent
cement, forcefully bottom the hose
in the socket, giving the hose a one-
quarter turn, if possible. The hose
must go to the bottom of the socket.
Step 1 Hold the joint together until tight.
Step 11 Wipe excess cement from the hose.
A properly made joint will normally
show a bead around its entire
perimeter. Any gaps may indicate
insufficient cement or the use of
light bodied cement on larger
diameters where heavy bodied
cement should have been used.
Step 12 Do not disturb joint for the
following periods:
3d minutes minimum at 60°F to 100°F
(16°C to 38°C)
1 hour minimum at 40°F to 60°F (4°C to
16°C)
2 hours miiumum at 20°F to 40°F (-7°C to
4°C)
4 hours minimum at 0°F to 20°F (-18°C to -
7°C)
Handle the newly assembled joints
carefully during these periods. If
gaps (step 11) or loose fits are
encountered in the system, double
these periods.
Step 13 The system shall not be pressurized
until the joints have cured (set) at
least as long as recommended by
the manufacturer. If manufacturer's
recommendation is not available,
the cure times as shown in Table 1
are required.
5.1 .7 Installation and Testing
5.1.7.1 Installation. The hose shall be properly
supported to prevent excessive sagging.
5.1.7.2 Testing.
(a) All pool, spa, and hot tub piping shall be
inspected and approved before being
covered or concealed, except as
permitted by sections 3.2 and 4.2. It shall
be tested and proved tight to the
satisfaction of the Administrative
Authority, under a static water or air
pressure test of not less than 35 psi (241
kPa) for 15 minutes.
EXCEPTION: All exposed equipment
need not be tested as required in this
section.
(b) All swimming pool, spa, or hot tub
installations must be completed, filled
with water, and in operation before final
inspection.
417
SIS1
UNIFORM PLUMBING CODE
5.1.8 SAFETY REQUIREMENTS AND
PRECAUTIONS^
5.1.8.1 General. Solvents contained in PVC plastic
hose cements are classified as airborne
contaminants and flammable and
combustible liquids. Precautions listed in
this section should be followed to avoid
injury to personnel and the hazard of fire.
'CAUTION: Primers are toxic. Don't allow them to touch skin. Suitable
gloves are advised.
5.1.8.2 SAFETY PRECAUTIONS
1. Prolonged breathing of solvent vapors
should be avoided. When hose and
fittings are being joined in partially
enclosed areas, a ventilating device
should be used in such a manner to
minimize the entry of vapors into the
breathing areas.
2. Solvent cements should be kept away
from all sources of ignition, heat, sparks
and open flame.
3. Containers for solvent cements should
be kept tightly closed except when the
cement is being used.
4. All rags and other materials used for
mopping up spills should be kept in a
safety waste receptacle which should be
emptied daily.
5. Most of the solvents used in PVC hose
cements can be considered eye irritants
and contact with the eye should be
avoided for it may cause eye injury.
Proper eye protection and the use of
chemical goggles or face shields is
advisable where the possibility of
splashing exists in handling solvent
cements. In case of eye contact, flush
with plenty of water for 15 min. and call
a physician immediately.
6. Repeated contact with the skin should
be avoided. Proper gloves impervious to
and unaffected by the solvents should
be worn when frequent contact with the
skin is likely. Application of the solvents
or solvent cements with rags and bare
hands is not recommended. Brushes and
other suitable applicators can be used
effectively for applying the solvent
cement, thus avoiding skin contact. In
the event of excessive contact, remove
contaminated clothing and wash skin
with soap and water.
ADOPTED: 1989
REVISED: 2003
Table 1
Minimum Cure Time, in Hours'^^
Test Pressure for Hose
Sizes 1/2" to 1 1/4"
Sizes 1-1/2" to 3"
Sizes 3-1/2" to 8"
12.7 mm to 31 .8 mm
38.1 mm to 76.2 mm
88.9 mm
to 203.2 mm
Temp. Range
Up to
Above 180
Up to
Above 180
Up to
Above 180
During Cure
180psi
to370psi
180psi
to315psi
180psi
to315psi
Period
(1240.2
(1240.2 to
(1240.2
(1240.2 to
(1240.2
(1240.2 to
kPa)
2549.3 kPa)
kPa)
2170.4 kPa)
kPa)
2170.4 kPa)
60°F-100°F
1 hr
6hr
2hr
12 hr
6hr
24 hr
{16°C-38°C)
40T-60°F
2hr
12 hr
4hr
24 hr
12 hr
48 hr
(4°C-16°C)
10°F-40°F
(-12°C+4°C)
8hr
48 hr
16 hr
96 hr
48 hr
8 days ,
It is important to note that at temperatures colder than 20°F (-6.7°C) on sizes that
exceed 3 in. (76.2 mm), test results indicate that many variables exist in the actual
cure rate of the joint. The data expressed in these categories represent only
estimated averages. In some cases, cure will be achieved in less time, but
isolated test results indicate that even longer periods of cure may be required.
These cure schedules are based on laboratory test data obtained on Net Fit Joints
(NET FIT= in a dry fit the pipe bottoms snugly in the fitting socket without meeting
interference). The relative humidity in these tests was 50% or less. Higher relative
humidity may require longer cure periods.
418
Installation Standard
For
ASSEMBLED WHIRLPOOL BATH APPLIANCES
lAPMO SIS 2-2003
1 . Purpose and Scope
To ensure the proper installation of fittings and
pumps to maintain no more than the maximum,
allowed water retention for each system installed on
each different make/model of bathtub. This is a field
inspection to be done by the Adniinistrative
Authority, and because of this, there will be special,
specific points of reference included in the
installation instructions to locate jet-suction fitting-
pump elevations.
2. Testing
To receive USPC listing, the manufacturer of the
kit /or assembler of the whirlpool bath appliance
shall provide sample tubs /systems to an approved
testing laboratory and said tubs shall be tested to
ANSI A112.19.7M. The sample tubs shall represent
the parameters described below:
Tub Volume^ No. of Jets
Sample #1 Largest Greatest
Sample #2 Largest Least
Sample #3 Smallest Greatest
Sample #4 Smallest Least
1 As measured in gallon, to the overflow
2 As rated in gallons per minute (GPM)
Pump Size^
Largest
Smallest
Largest
Smallest
4. Labeling Requirements
Labels shall be permanently affixed to the appliances
to be visible from the access door upon final
inspection. Labels shall contain the following inform-
ation :
(a) Title: Assembled Whirlpool Bathtub Appliances
(b) Assembler's Company Name
(c) Date Assembled
(d) Kit Manufacturer Model Number
(e) USPC certification mark with registration ®
ADOPTED:
REVISED:
1990
2003
3. Instructions
A complete set of installation instructions shall be
provided with each appliance or kit and shall
include the following:
(a) A side view drawing showing location of jets,
suction fittings, pumps, piping and any other
parts of the whirlpool system that affect the
water retention of the entire system. A point or
points of reference shall be chosen by the
manufacturer to enable the Administrative
Authority to verify these locations after
installation of the tub.
(b) Cross reference shall be made as to the kit and
the tub (make and model) for which it is listed.
(c) A drawing showing the pump mounting and all
hardware to be used.
(d) Recommendations for piping support.
419
SIS 2 UNIFORM PLUMBING CODE
420
APPENDIX K
PRIVATE SEWAGE DISPOSAL SYSTEMS
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
flA
lA
K 1 Private Sewage Disposal - General.
(A) Where permitted by Section 713.0, the building
sewer may be connected to a private sewage disposal
system complying with the provisions of this
appendix. The type of system shall be determined on
the basis of location, soil porosity, and groundwater
level, and shall be designed to receive all sewage
from the property. The system, except as otherwise
approved, shall consist of a septic tank with effluent
discharging into a subsurface disposal field, into one
(1) or more seepage pits, or into a combination of
subsurface disposal field and seepage pits. The
Authority Having Jurisdiction may grant exceptions
to the provisions of this appendix for permitted
structures that have been destroyed due to fire or
natural disaster and that cannot be reconstructed in
compliance with these provisions provided that such
exceptions are the minimum necessary.
(B) Where the quantity or quality of the sewage is such
that the above system camiot be expected to function
satisfactorily for commercial, agricultural, and
industrial plumbing systems; for installations where
appreciable amounts of industrial or indigestible
wastes are produced; for occupancies producing
abnormal quantities of sewage or liquid waste; or when
grease interceptors are required by other parts of this
code, the method of sewage treatment and disposal
shall be first approved by the Authority Having
Jurisdiction. Special sewage disposal systems for minor,
limited, or temporary uses shall be first approved by
the Authority Having Jurisdiction.
(C) Disposal systems shall be designed to utilize the
most porous or absorptive portions of the soil
formation. Where the groundwater level extends to
within twelve (12) feet (3658 mm) or less of the ground
surface or where the upper soil is porous and the
underlying stratum is rock or impervious soil, a septic
tank and disposal field system shall be installed.
(D) Disposal systems shall be located outside of flood
hazard areas.
Exception: Wliere suitable sites outside of flood
hazard areas are not available, disposal systems
may be located in flood hazard areas on sites
where the effects of inimdation under conditions
of the design flood are minimized.
(E) All private sewage disposal systems shall be so
designed that additional seepage pits or subsurface
drain fields, equivalent to at least one hundred (100)
percent of the required original system, may be
installed if the original system cannot absorb all the
sewage. No division of the lot or erection of
structures on the lot shall be made if such division or
structure impairs the usefulness of the one hundred
(100) percent expansion area.
(F) No property shall be improved in excess of its
capacity to properly absorb sewage effluent by the
means provided in this code.
Exception: The Authority Having Jurisdiction
may, at its discretion, approve an alternate
system.
(G) No private sewage disposal system, or part
thereof, shall be located in any lot other than the lot
that is the site of the building or structure served by
such private sewage disposal system, nor shall any
private sewage disposal system or part thereof be
located at any point having less than the minimum
distances indicated in Table K-1.
Nothing contained in this code shall be construed
to prohibit the use of all or part of an abutting lot to
provide additional space for a private sewage
disposal system or part thereof when proper cause,
transfer of ownership, or change of boundary not in
violation of other requirements has been first
established to the satisfaction of the Authority
Having Jurisdiction. The instrument recording such
action shall constitute an agreement with the
Authority Having Jurisdiction, which shall clearly
state and show that the areas so joined or used shall
be maintained as a unit during the time they are so
used. Such agreement shall be recorded in the office
of the County Recorder as part of the conditions of
ownership of said properties and shall be binding on
all heirs, successors, and assigns to such properties. A
copy of the instrument recording such proceedings
shall be filed with the Authority Having Jurisdiction.
(H) When there is insufficient lot area or improper
soil conditions for adequate sewage disposal for the
building or land use proposed, and the Authority
Having Jurisdiction so finds, no building permit
shall be issued and no private sewage disposal shall
be permitted. Where space or soil conditions are
critical, no building permit shall be issued until
421
Appendix K
UNIFORM PLUMBING CODE
engineering data and test reports satisfactory to the
Authority Having Jurisdiction have been submitted
and approved.
(I) Nothing contained in this appendix shall be
construed to prevent the Authority Having
Jurisdiction from requiring compliance with
additional requirements than those contained herein,
where such additional requirements are essential to
maintain a safe and sanitary condition.
(J) Alternate systems may be used only by special
permission of the Authority Having Jurisdiction after
being satisfied of their adequacy. This authorization
may be based on extensive field and test data from
conditions similar to those at the proposed site, or
may require such additional data as may be necessary
to provide assurance that the alternate system will
produce continuous and long-range results at the
proposed site, at least equivalent to systems which are
specifically authorized.
If demonstration systems are to be considered for
installation, conditions for installation, maintenance,
and monitoring at each such site shall first be
established by the Authority Having Jurisdiction.
Aerobic Systems. Approved aerobic systems may be
substituted for conventional septic tanks provided
the Authority Having Jurisdiction is satisfied that
such systems will produce results at least equivalent
to septic tanks, whether their aeration systems are
operating or not.
K 2 Capacity of Septic Tanlcs.
The liquid capacity of all septic tanks shall conform
to Tables K-2 and K-3 as determined by the number
of bedrooms or apartment units in dwelling
occupancies and the estimated waste /sewage design
flow^ rate or the number of plumbing fixture units as
determined from Table 7-3 of this Code, whichever is
greater in other building occupancies. The capacity
of any one septic tank and its drainage system shall
be limited by the soil structure classification, as
specified in Table K-4.
K 3 Area of Disposal Fields and Seepage Pits.
The minimum effective absorption area in disposal
fields in square feet (m^), and in seepage pits in
square feet (m^) of sidewall, shall be predicated on
the required septic tank capacity in gallons (liters)
and/or estimated waste/sewage flow rate,
whichever is greater, and shall conform to Table K-4
as determined for the type of soil found in the
excavation, and shall be as follows:
(1) When disposal fields are installed, a
minimum of one hundred and fifty (150)
square feet (14 m") of trench bottom shall be
provided for each system exclusive of any
hard pan, rock, clay, or other impervious
formations. Sidewall area in excess of the
required twelve (12) inches (305 mm) and
not to exceed thirty-six (36) inches (914 mm)
below the leach line may be added to the
trench bottom area when cornputing
absorption areas.
(2) Where leaching beds are permitted in
lieu of trenches, the area of each such
bed shall be at least fifty (50) percent
greater than the tabular requirements
for trenches. Perimeter sidewall area in
excess of the required twelve (12) inches
(305 mm) and not to exceed thirty-six
(36) inches (914 mm) below the leach
line may be added to the trench bottom
area when computing absorption areas.
(3) No excavation for a leach line or leach
bed shall extend within five (5) feet
(1,524 mm) of the water table nor to a
depth where sewage may contaminate
the underground water stratum that is
usable for domestic purposes.
Exception: In areas where the records
or data indicate that the groundwaters
are grossly degraded, the five (5) foot
(1,524 mm) separation requirement may
be reduced by the Authority Having
Jurisdiction. ITie applicant shall supply
evidence of groundw^ate'r depth to the
satisfaction of the Authority Having
Jurisdiction.
(4) The minimum effective absorption area in
any seepage pit shall be calculated as the
excavated sidewall area below the inlet
exclusive of any hardpan, rock, clay, or other
impervious formations. The minimum
required area of porous formation shall be
provided in one or more seepage pits. No
excavation shall extend within ten (10) feet
(3,048 mm) of the water table nor to a depth
where sewage may contaminate under-
ground water stratum that is usable for
domestic purposes.
Exception: In areas where the records or
data indicate that the groundwaters are
grossly degraded, the ten (10) foot (3,048
mm) separation requirement may be
reduced by the Authority Having
Jurisdiction.
422
PRIVATE SEWAGE DISPOSAL SYSTEMS
Appendix K
The applicant shall supply evidence of
groundwater depth to the satisfaction of the
Authority Having Jurisdiction.
(5) Leaching chambers shall be sized on the bot-
tom absorption area (nominal unit width) in
square feet. The required area shall be calcu-
lated using Table K-4 with a 0.70 multiplier.
K 4 Percolation Test.
(A) Wherever practicable, disposal field and seepage
pit sizes shall be computed from Table K-4. Seepage
pit sizes shall be computed by percolation tests,
unless use of Table K-4 is approved by the Authority
Having Jurisdiction.
(B) In order to determine the absorption qualities of
seepage pits and of questionable soils other than
those listed in Table K-4, the proposed site shall be
subjected to percolation tests acceptable to the
Authority Having Jurisdiction.
(C) When a percolation test is required, no private
disposal system shall be permitted to serve a building
if that test shows the absorption capacity of the soil is
less than 0.83 gallons per square foot (33.8 L/m^) or
more than 5.12 gallons per square foot (208 L/m^) of
leaching area per 24 hours. If the percolation test
shows an absorption rate greater than 5.12 gallons per
square foot (208 L/m^) per 24 hours, a private disposal
system may be permitted if the site does not overlie
groundwaters protected for drinking water supplies, a
minimum thickness of two (2) feet (610 mm) of the
native, soil below the entire proposed system is re-
placed by loamy sand, and the system design is based
on percolation tests made in the loamy sand.
(D) Septic tanks shall have a minimum of two (2)
compartments. The inlet compartment of any septic
tank shall be not less than two- thirds (2/3) of the
total capacity of the tank, nor less than five hundred
(500) gallons (2.0 m"*) liquid capacity, and shall be at
least three (3) feet (914 mm) in width and five (5) feet
(1,524 mm) in length. Liquid depth shall be not less
than two (2) feet (610 mm) and six (6) inches (152
mm) nor more than six (6) feet (1,829 mm). The
secondary compartment of any septic tank shall have
a minimum capacity of two hundred fifty (250)
gallons (1.0 m^) and a maximum capacity of one-
third (1/3) of the total capacity of such tank. In septic
tanks having over a fifteen hundred (1,500) gallon
(6.0 m^) capacity, the secondary compartment may be
not less than five (5) feet (1,524) in length.
(E) Access to each septic tank shall be provided by
at least two (2) manholes twenty (20) inches (508
mm) in minimum dimension or by an equivalent
removable cover slab. One access manhole shall be
located over the inlet and one (1) access manhole
shall be located over the outlet. Wherever a first
compartment exceeds twelve (12) feet (3,658 mm) in
length, an additional manhole shall be provided over
the baffle wall.
(F) The inlet and outlet pipe openings shallnot be
larger in size than the connecting sewer pipe. The
vertical leg of round inlet and outlet fittings shall not
be less in size than the connecting sewer pipe nor
less than four (4) inches (102 mm). A baffle-type
fitting shall have the equivalent cross-sectional area
of the connecting sewer pipe and not less than a four
(4) inch (100 mm) horizontal dimension when
measured at the inlet and outlet pipe inverts.
K 5 Septic Tank Construction.
(A) Plans for all septic tanks shall be submitted to
the Authority Having Jurisdiction for approval. Such
plans shall show all dimensions, reinforcing,
structural calculations, and such other pertinent data
as may be required.
(B) Septic tank design shall be such as to produce a
clarified effluent consistent with accepted standards
and shall provide adequate space for sludge and
scum accumulations.
(C) Septic tanks shall be constructed of solid durable
materials not subject to excessive corrosion or decay
and shall be watertight.
(G) The inlet and outlet pipe or baffle shall extend
four (4) inches (100 mm) above and at least twelve (12)
inches (305 mm) below the water surface. The invert
of the inlet pipe shall be at a level not less than two (2)
inches (51 mm) above the invert of the outlet pipe.
(H) Inlet and outlet pipe fittings or baffles and
compartment partitions shall have a free vent area
equal to the required cross-sectional area of the house
sewer or private sewer discharging therein to provide
free ventilation above the water surface from the
disposal field or seepage pit through the septic tank,
house sewer, and stack to the outer air.
(I) The sidewalls shall extend at least nine (9) inches
(229 mm) above the liquid depth. The cover of the
423
Appendix K
UNIFORM PLUMBING CODE
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
septic tank shall be at least two (2) inches (51 mm)
above the back vent openings.
(J) Partitions or baffles between compartments shall
be of solid, durable material and shall extend at least
four (4) inches (102 mm) above the liquid level. An
inverted fitting equivalent in size to the tank inlet,
but in no case less than four (4) inches (102 mm) in
size, shall be installed in the inlet compartment side
of the baffle with the bottom of the fitting placed
midway in the depth of the liquid. Wooden baffles
are prohibited.
(K) Structural Design.
(1) General. Each such tank shall be structurally
designed to withstand all anticipated earth or
other loads. All septic tank covers shall be
capable of supporting an earth load of not less
than five hundred (500) poimds per square foot
(23.9kPa) when the maximum coverage does not
exceed three (3) feet (914 mm).
(2) Flood Loads. In flood hazard areas, tanks
shall be anchored to counter buoyant forces
during conditions of the design flood. The vent
termination and service manhole of the tank
shall be a minimum of 2 feet (610 mm) above the
design flood elevation or fitted with covers
designed to prevent the inflow of floodwater or
the outflow of the contents of the tanks during
conditions of the design flood.
(L) Septic tanks installed under concrete or blacktop
paving shall have the required manholes accessible
by extending the manhole openings to grade in a
manner acceptable to the Authority Having
Jurisdiction.
(M) Materials.
(1) Concrete Septic Tanks.
All materials used in constructing a septic
tank shall be in accordance with applicable
standards in Chapter 14, Table 14-1.
(2) Steel Septic Tanks.
The minimum wall thickness of any steel
septic tank shall be No. 12 U.S. gauge (0.109)
(2.8 mm), and each such tank shall be
protected from corrosion both externally
and internally by an approved bitu-
minous coating or by other acceptable means.
(3) Alternate Materials.
(i) Septic tanks constructed of alternate
materials may be approved by the
Authority Having Jurisdiction when
complying with approved applicable
standards.
(ii) Wooden septic tanks are prohibited.
(N) Prefabricated Septic Tanks.
(1) Manufactured or prefabricated septic tanks
shall comply with all approved applicable
standards and be approved by the
Authority Having Jurisdiction.
(2) Independent laboratory tests and engineering
calculations certifying the tank capacity and
structural stability shall be provided as
required by the Authority Having Jurisdiction.
K 6 Disposal Fields.
(A) Distribution lines shall be constructed of clay tile
laid with open joints, perforated clay pipe,
perforated bituminous fiber pipe, perforated high-
density polyethylene pipe, perforated ABS pipe,
perforated PVC pipe, or other approved materials,
provided that sufficient openings are available for
distribution of the effluent into the trench area.
(B) Before placing filter material or drain lines in a
prepared excavation, all smeared or compacted
surfaces shall be removed from trenches by raking to
a depth of one (1) inch (25.4 mm) and the loose
material removed. Clean stone, gravel, slag, or
similar filter material acceptable to the Authority
Having Jurisdiction, varying in size from three
fourths (3/4) inch to two and one-half (2-1/2) inches
(19.1 mm to 64 mm), shall be placed in the trench to
the depth and grade required by this section. Drain
pipe shall be placed on filter material in an approved
manner. The drain lines shall then be covered with
filter material to the minimum depth required by
this section, and this material covered with imtreated
building paper, straw, or similar porous materiail to
prevent closure of voids with earth backfill. No earth
backfill shall be placed over the filter material cover
until after inspection and acceptance.
Exception: Listed or approved plastic leaching
chambers may be used in lieu of pipe and filter
material. Chamber installations shall follow the
rules for disposal fields, where applicable, and
shall conform to manufacturer's installation
instructions.
(C) A grade board staked in the trench to the depth
of filter material shall be utilized when the
distribution line is constructed w^ith drain tile or a
flexible pipe material that will not maintain
alignment without continuous support.
424
PRIVATE SEWAGE DISPOSAL SYSTEMS
Appendix K
Minimum
Maximum
Number of drain lines per field
1
—
Length of each line
-
100 ft. (30,480 mm)
Bottom width of trench
18 in. (457 mm)
36 in. (914 mm)
Spacing of lines, center-to-center
6 ft. (1 ,829 mm)
-
Depth of earth cover of lines
[preferred -18 in. (457 mm)]
12 in. (305 mm)
-
Grade of lines
level
3in./100ft. (25mm/m)
Filter material under drain lines
12 in. (305 mm)
—
Filter material over drain lines
2 in. (51 mm)
—
(D) When seepage pits are used in combination with
disposal fields, the filter material in the trenches
shall terminate at least five (5) feet (1,524 mm) from
the pit excavation, and the line extending from such
points to the seepage pit shall be approved pipe with
watertight joints.
(E) Where two (2) or more drain lines are installed,
an approved distribution box of sufficient size to
receive lateral lines shall be installed at the head of
each disposal field. The inverts of all outlets shall be
level, and the invert of the inlet shall be at least one
(1) inch (25.4 mm) above the outlets. Distribution
boxes shall be designed to ensure equal flow and
shall be installed on a level concrete slab in natural
or compacted soil.
(F) All laterals from a distribution box to the
disposal field shall be approved pipe with watertight
joints. Multiple disposal field laterals, wherever
practicable, shall be of uniform length.
(G) Connections between a septic tank and a
distribution box shall be laid with approved pipe
with watertight joints on natural ground or
compacted fill.
(H) When the quantity of sewage exceeds the
amount that can be disposed in five hundred (500)
lineal feet (152.4 m) of leach line, a dosing tank shall
be used. Dosing tanks shall be equipped w^ith an
automatic siphon or pump that discharges the tank
once every three (3) or four (4) hours. The tank shall
have a capacity equal to sixty (60) to seventy-five (75)
percent of the interior capacity of the pipe to be
dosed at one time. Where the total length of pipe
exceeds one thousand (1,000) lineal feet (304.8 m),
the dosing tank shall be provided with two (2)
siphons or pumps dosing alternately and each
serving one-half (1/2) of the leach field.
(I) Disposal fields shall be constructed as follows:
(See chart above.)
Minimum spacing between trenches or leaching beds
shall be four (4) feet (1,219 mm) plus two (2) feet (610
mm) for each additional foot (305 mm) of depth in
excess of one (1) foot (305 mm) below the bottom of
the drain line. Distribution drain lines in leaching
beds shall not be more than six (6) feet (1,829 mm)
apart on centers, and no part of the perimeter of the
leaching bed shall be more than three (3) feet (914
mm) from a distribution drain line. Disposal fields,
trenches, and leaching beds shall not be paved over or
covered by concrete or any material that can reduce or
inhibit any possible evaporation of sewer effluent.
(J) When necessary on sloping ground to prevent
excessive line slope, leach lines or leach beds shall be
stepped. The lines between each horizontal section
shall be made with watertight joints and shall be
designed so each horizontal leaching trench or bed
shall be utilized to the maximum capacity before the
effluent shall pass to the next lower leach line or bed.
The lines between each horizontal leaching section
shall be made with approved watertight joints and
installed on natural or unfilled ground.
K 7 Seepage Pits.
(A) The capacity of seepage pits shall be based on the
quantity of liquid waste discharging thereinto and on
the character and porosity of the surrounding soil,
and shall conform to Section K 3 of this appendix.
(B) Multiple seepage pit installations shall be served
through an approved distribution box or be
connected in series by m^eans of a watertight
connection laid on undistributed or compacted soil;
the outlet from the pit shall have an approved
vented leg fitting extending at least twelve (12)
inches (305 mm) below the inlet fitting.
425
Appendix K
UNIFORM PLUMBING CODE
(C) Each seepage pit shall be circular in shape and
shall have cin excavated diameter of not less than four
(4) feet (1,219 mm). Each such pit shall be lined with
approved-type whole new hard-burned clay brick,
concrete brick, concrete circular-type cesspool blocks,
or other approved materials. Approval shall be
obtained prior to construction for any pit having an
excavated diameter greater than six (6) feet (1,829 mm).
(D) The lining in every seepage pit shall be laid on a
firm foundation. Lining materials shall be placed
tight together and laid with joints staggered. Except
in the case of approved-type precast concrete circular
sections, no brick or block shall be greater in height
than its width, and shall be laid flat to form at least a
four (4) inch (102 mm) wall. Brick or block greater
than twelve (12) inches (305 mm) in length shall have
chamfered matching ends and be scored to provide
for seepage. Excavation voids behind the brick,
block, or concrete liner shall have a minimum of six
(6) inches (152 mm) of clean three-fourths (3/4) inch
(19.1 mm) gravel or rock.
(E) All brick or block used in seepage pit
construction shall have a minimum compressive
strength of twenty-five hundred (2,500) pounds per
square inch (17,237 kPa).
(F) Each seepage pit shall have a minimum sidewall
(not including the arch) of ten (10) feet (3,048 mm)
below the inlet.
(G) The arch or dome of any seepage pit may be
constructed in one of three w^ays:
(1) Approved-type hard-burned clay brick or
solid concrete brick or block laid in cement
mortar.
(2) Approved brick or block laid dry.
In both of the above methods, an approved
cement mortar covering of at least two (2)
inches (51 mm) in thickness shall be applied,
said covering to extend at least six (6) inches
(152 mm) beyond the sidewalls of the pit.
(3) Approved-type one or two-piece reinforced
concrete slab of twenty-five hundred (2,500)
pounds per square inch (17237 kPa)
minimum compressive strength, not less
than five (5) inches (127 mm) thick and
designed to support an earth load of not less
than four hundred (400) pounds per square
foot (19.2 kPa). Each such cover shall be
provided with a nine (9) inch (229 mm)
minimum inspection hole with plug or
cover and shall be coated on the underside
with an approved bituminous or other
nonpermeable protective compound.
(H) The top of the arch or cover must be at least
eighteen (18) inches (457 mm) but not more than four
(4) feet (1219 mm) below the surface of the ground.
(I) An approved vented inlet fitting shall be
provided in every seepage pit so arranged as to
prevent the inflow from damaging the sidewall.
Exception: When using a one- or two-piece
concrete slab cover inlet, fitting may be a one-
fourth (1/4) bend fitting discharging through an
opening in the top of the slab cover. On multiple
seepage pit installations, the outlet fittings shall
be per Section K 7(B) of this appendix.
K8 Cesspools.
(A) A cesspool shall be considered only as a
temporary expedient pending the construction of a
public sewer; as an overflow facility when installed
in conjunction with an existing cesspool; or as a
means of sewage disposal for limited, minor, or
temporary uses, when first approved by the
Authority Having Jurisdiction.
(B) Where it is established that a public sewer
system w^ill be available in less than tw^o (2) years
and soil and groimdwater conditions are favorable to
cesspool disposal, cesspools without septic tanks
may be installed for single-family dwellings or for
other limited uses when first approved by the
Authority Having Jurisdiction.
(C) Each cesspool, when permitted, shall conform to
the construction requirements set forth in Section K 7
of this appendix for seepage pits and shall have a
minimum sidewall (not including arch) of twenty (20)
feet (6,096 mm) below the inlet, provided, however,
that when a strata of gravel or equally pervious
material of four (4) feet (1,219 mm) in thickness is
found, the depth of such sidewall need not be more
than ten (10) feet (3,048 mm) below the inlet.
(D) When overflow cesspools or seepage pits are
added to existing installations, the effluent shall
leave the existing pit through an approved vented
leg extending at least twelve (12) inches (305 mm)
downward into such existing pit and having its
outlet flow line at least six (6) inches (152 mm) below
the inlet. All pipe between pits shall be laid with
approved watertight joints.
426
PRIVATE SEWAGE DISPOSAL SYSTEMS
Appendix K
Grease and Garbage, Commercial Kitchens
Number of Waste Retention Storage Interceptor
meals per x flow x time x factor = size (liquid
peak hour rate capacity)
Number of
vehicles
per hour
Sand-Siit Oil, Auto Washers
Waste Retention Storage
flow
rate
time
factor
Interceptor
size (liquid
capacity)
Silt-Lint Grease, Laundries, Laundromats
Number of 2 cycles Waste Retention Storage
machines x per hour x flow x time ;
rate
Interceptor
Factor = size
(liquid
capacity)
Waste Flow Rate
See Table K-3 of this appendix for estimated flow rates.
Retention Times
Commercial kitchen waste:
Dishwasher and/or disposal 2.5 hours
Single service kitchen:
Single serving with disposal 1.5 hours
Sand-silt oil 2.0 hours
Lint-silt (laundry) 2.0 hours
Storage Factors
Fully equipped commercial kitchen 8 h. operation: 1
16 h. operation: 2
24 h. operation: 3
Single service kitchen 1.5
Auto washers self-serve: 1.5
employee operated: 2
Laundries, laundromats 1 .5 (allows for rock filter)
K 9 Commercial or Industrial Special Liquid-
Waste Disposal.
(A) When liquid v\rastes contain excessive amounts
of grease, garbage, flammable wastes, sand, or other
ingredients that may affect the operation of a private
sewage disposal system, an interceptor for such
wastes shall be installed.
(B) Installation of such interceptors shall comply with
Section 1009.0 of this code, and their location shall be
in accordance with Table K-1 of this appendix.
(C) A sampling box shall be installed when required
by the Authority Having Jurisdiction.
(D) Interceptors shall be of approved design and be
of not less than two (2) compartments. Structural
requirements shall be in compliance with the
applicable subparts of Section K 5 of this appendix.
(E) Interceptors shall be located as close to the
source as possible and be accessible for servicing. All
necessary manholes for servicing shall be at grade
level and be gastight.
(F) Waste discharge from interceptors may be
connected to a septic tank or other primary system or
be disposed into a separate disposal system.
(G) Recommended Design Criteria. (Formula may
be adapted to other types of occupancies with
similar wastes.) See charts on this page.
K10 Inspection and Testing.
(A) Inspection.
(1) Applicable provision of Section 103.5 of this
code and this appendix shall be complied
with. Plans may be required per Section
101.3 of this code.
427
Appendix K
UNIFORM PLUMBING CODE
TIA
TIA
TIA
(2) System components shall be properly
identified as to manufacturer. Septic tanks or
other primary systems shall have the rated
capacity permanently marked on the unit.
(3) Septic tanks or other primary systems shall be
installed on dry, level, well-compacted soil.
(4) If design is predicated on soil tests, the
system shall be installed at the same location
and depth as the tested area.
(B) Testing.
(1) Septic tanks or other primary components
shall be filled with water to flow line prior to
requesting inspection. All seams or joints
shall be left exposed (except the bottom),
and the tank shall remain watertight.
(2) A flow test shall be performed through
the system to the point of effluent disposal.
All lines and components shall be watertight.
Capacities, required air space, and fittings
shall be in accordance with the provisions set
forth in this appendix.
K 11 Abandoned Sewers and Sewage Disposal
Facilities.
(A) Every abandoned building (house) sewer, or
part thereof, shall be plugged or capped in an
approved manner within five (5) feet (1,524 mm) of
the property line.
(B) Every cesspool, septic tank, and seepage pit that
has been abandoned or has been discontinued
TABLE K-1
Location of Sewage Disposal System
Minimum Horizontal Distance
Seepage Pit
In Clear Required From:
Building Sewer
Septic Tank
Disposal Field
or Cesspool
Buildings or structures'
2 feet (610 mm)
5 feet (1,524 mm)
8 feet (2,438 mm)
8 feet (2,438 mm)
Property line adjoining
private property
Clear^
5 feet (1,524 mm)
5 feet (1,524 mm)
8 feet (2,438 mm)
Water supply wells
50feetM15,240mm)
50 feet (15,240 mm)
100 feet (30.5 m)
150 feet (45.7 m)
Streams and other
50 feet (15,240 mm)
50 feet (15,240 mm)
100 feet^(1 5,240 mm)'
150feef (30.5 m)'
bodies of water
Trees
-
10 feet (3,048 mm)
-
10 feet (3,048 mm)
Seepage pits or cesspools
-
5 feet (1 ,524 mm)
5 feet (1 ,524 mm)
12 feet (3,658 mm)
Disposal field
-
5 feet (1,524 mm)
4 feet* (1,219 mm)
5 feet (1,524 mm)
On-site domestic water
service line
1 foot^ (305 mm)
5 feet (1 ,524 mm)
5 feet (1,524 mm)
5 feet (1,524 mm)
Distribution box
-
-
5 feet (1,524 mm)
5 feet (1,524 mm)
Pressure public water main
lOfeet^ (3,048 mm)
10 feet (3,048 mm)
10 feet (3,048 mm)
10 feet (3,048 mm)
TIA
Note:
When disposal fields and/or seepage pits are installed in sloping ground, the minimum horizontal distance between any part of the
leaching system and ground surface shall be fifteen (15) feet (4,572 mm).
' Including porches and steps, whether covered or uncovered, breezeways, roofed porte cocheres, roofed patios, carports, covered
walks, covered driveways, and similar structures or appurtenances.
^ See also Section 313.3 of the Uniform Plumbing Code.
^ All drainage piping shall clear domestic water supply wells by at least fifty (50) feet (15,240 mm). This distance may be reduced to not
less than twenty-five (25) feet (7,620 mm) when the drainage piping is constructed of materials approved for use within a building.
" Plus two (2) feet (610 mm) for each additional one (1) foot (305 mm) of depth in excess of one (1) foot (305 mm) below the bottom of the
drain line. (See also Section K 6.)
= See Section 720.0 of the Uniform Plumbing Code.
^ For parallel construction - For crossings, approval by the Health Department shall be required.
' These minimum clear horizontal distances shall also apply between disposal fields, seepage pits, and the mean high tide line.
428
PRIVATE SEWAGE DISPOSAL SYSTEMS
Appendix K
TABLE K-2
Capacity of Septic Tanks*
Single-Family
Multiple Dwelling
Other Uses:
Minimum
Dwellings -
Units or
Maximum Fixture
Septic
Tank
Number
Apartments - One
Units Served
Capacity in
of Bedrooms
Bedroom Each
per Table 7-3
Gallons
(Liters)
1 or 2
15
750
(2,838)
3
20
1,000
(3,785)
4
2 units
25
1,200
(4,542)
5 or 6
3
33
1,500
(5,678)
4
45
2,000
(7,570)
5
55
2,250
(8,516)
6
60
2,500
(9,463)
7
70
2,750
(10,409)
8
80
3,000
(11,355)
9
90
3,250
(12,301)
10
100
3,500
(13,248)
*Note:
Extra bedroom, 150 gallons (568 liters) each.
Extra dwelling units over 10,250 gallons (946 liters) each.
Extra fixture units over 100,25 gallons (95 liters) per fixture unit.
Septic tank sizes in this table include sludge storage capacity and the connection of domestic food waste
disposal units without further volume increase.
TABLE K-3
Estimated Waste/Sewage Flow Rates
Because of the many variables encountered, it is not possible to set absolute values for waste/sewage flow
rates for all situations. The designer should evaluate each situation and, if figures in this table need
modification, they should be made with the concurrence of the Authority Having Jurisdiction.
Type of Occupancy Gallons (liters) Per Day
1 . Airports 1 5 (56.8) per employee
5 (18.9) per passenger
2. Auto washers Check with equipment manufacturer
3. Bowling alleys (snack bar only) 75 (283.9) per lane
4. Camps:
Campground with central comfort station 35 (132.5) per person
Campground with flush toilets, no showers 25 (94.6) per person
Day camps (no meals served) 15 (56.8) per person
Summer and seasonal 50 (189.3) per person
5. Churches (Sanctuary) 5 (18.9) per seat
with kitchen waste 7 (26.5) per seat
6. Dance halls 5 (18.9) per person
7. Factories
No showers 25 (94.6) per employee
With showers 35 (132.5) per employee
Cafeteria, add 5 (18.9) per employee
8. Hospitals 250 (946.3) per bed
Kitchen waste only 25 (94.6) per bed
Laundry waste only 40 (151.4) per bed
9. Hotels (no kitchen waste) 60 (227.1) per bed (2 person)
429
Appendix K UNIFORM PLUMBING CODE
TABLE K-3 (Continued)
Type of Occupancy Gallons (liters) Per Day
10. Institutions (Resident) 75 (283.9) per person
Nursing home 125 (473.1) per person
Resthome 125 (473.1) per person
1 1 . Laundries, self-service
(minimum 10 hours per day) 50 (189.3) per wash cycle
Commercial Per manufacturer's specifications
12. Motel 50 (189.3) per bed space
with kitchen 60 (227.1) per bed space
13. Offices 20 (75.7) per employee
14. Parks, mobile homes 250 (946.3) per space
picnic parks (toilets only) 20 (75.7) per parking space
recreational vehicles -
without water hook-up 75 (283.9) per space
with water and sewer hook-up 100 (378.5) per space
15. Restaurants - cafeterias 20 (75.7) per employee
toilet 7 (26.5) per customer
kitchen waste 6 (22.7) per meal
add for garbage disposal 1 (3.8) per meal
add for cocktail lounge 2 (7.6) per customer
kitchen waste - Disposable service 2 (7.6) per meal
16. Schools - Staff and office 20 (75.7) per person
Elementary students 15 (56.8) per person
Intermediate and high 20 (75.7) per student
with gym and showers, add 5 (18.9) per student
with cafeteria, add 3 (11.4) per student
Boarding, total waste 100 (378.5) per person
17. Service station, toilets 1000 (3785) for 1st bay
500 (1892.5) for each additional bay
18. Stores 20 (75.7) per employee
public restrooms, add 1 per 10 sq. ft. (4.1/m') of floor space
19. Swimming pools, public 10 (37.9) per person
20. Theaters, auditoriums 5 (18.9) per seat
drive-in 10 (37.9) per space
(a) Recommended Design Criteria. Sewage disposal systems sized using the estimated waste/sewage flow
rates should be calculated as follows:
(1 ) Waste/sewage flow, up to 1 ,500 gallons/day (5,677.5 L/day)
Flow X 1 .5 = septic tank size
(2) Waste/sewage flow, over 1 ,500 gallons/day (5,677.5 L/day)
Flow X 0.75 + 1 ,1 25 = septic tank size
(3) Secondary system shall be sized for total flow per 24 hours.
(b) Also see Section K 2 of this appendix.
430
PRIVATE SEWAGE DISPOSAL SYSTEMS
Appendix K
TABLE K-4
Design Criteria of Five Typical Soils
Maximum absorption
Required sq. ft.
capacity
in gals./sq. ft.
of leaching area/
of leaching area for
Type of Soil
100 (
gal. (mVL)
a 24 hr.
period (Um )
Coarse sand or gravel
20
(0.005)
5.0
(203.7)
Fine sand
25
(0.006)
4.0
(162.9)
Sandy loam or sandy clay
40
(0.010)
2.5
(101.8)
Clay with considerable sand
or gravel
90
(0.022)
1.1
(44.8)
Clay with small amount of sand
or gravel
120
(0.030)
0.8
(32.6)
TABLE K"5
Required Square Feet of
Leaching Area/100 gal.
Septic Tank Capacity
(mVL)
Maximum Septic Tank
Size Allowable
Gallons (liters)
20-25
40
90
120
(0.005-0.006)
(0.010)
(0.022)
(0.030)
7500
5000
3500
3000
(28,387.5)
(18,925.0)
(13,247.5)
(11,355.0)
431
Appendix K
UNIFORM PLUMBING CODE
otherwise from further use, or to which no waste or
soil pipe from a plumbing fixture is connected, shall
have the sewage removed therefrom and be
completely filled with the earth, sand, gravel,
concrete, or other approved material.
(C) The top cover or arch over the cesspool, septic
tank, or seepage pit shall be removed before filling,
and the filling shall not extend above the top of the
vertical portions of the sidewalls or above the level
of any outlet pipe until inspection has been called
and the cesspool, septic tank, or seepage pit has been
inspected. After such inspection, the cesspool, septic
tank, or seepage pit shall be filled to the level of the
top of the ground.
(D) No person owning or controlling any cesspool,
septic tank, or seepage pit on the premises of such
person or in that portion of any public street, alley,
or other public property abutting such premises shall
fail, refuse, or neglect to comply with the provisions
of this section or upon receipt of notice so to comply
with the Authority Having Jurisdiction.
(E) Where disposal facilities are abandoned
consequent to connecting any premises with the
public sewer, the permittee making the connection
shall fill all abandoned facilities as required by the
Authority Having Jurisdiction within thirty (30) days
from the time of connecting to the public sewer.
K12 Drawings and Specifications.
The Authority Having Jurisdiction, Health Officer, or
other department having jurisdiction may require
any or all of the following information before a
permit is issued for a private sewage disposal system
or at any time during the construction thereof.
(A) Plot plan drawn to scale, completely dimen-
sioned, showing direction and approximate slope of
surface, location of all present or proposed retaining
walls, drainage channels, water supply lines or wells,
paved areas and structures on the plot, number of
bedrooms or plumbing fixtures in each structure,
and location of the private sewage disposal system
with relation to lot lines and structures.
(G) A log of soil formations and groundwater levels
as determined by test holes dug in close proximity to
any proposed seepage pit or disposal field, together
with a statement of water absorption characteristics
of the soil at the proposed site, as determined by
approved percolation tests.
(B) Details of construction necessary to ensure
compliance with the requirements of this appendix
together with a full description of the complete
installation including quality, kind, and grade of all
materials, equipment, construction, workmanship,
and methods of assembly and installation.
432
APPENDIX L
ALTERNATE PLUMBING SYSTEMS
L1.0 Scope.
L 1.1 The intent of this appendix is to provide
clarification of procedures for the design and
approval of engineered plumbing systems, alternate
materials, and equipment not specifically covered in
other parts of the code.
L 1 ,2 The provisions of this appendix apply to the
design, installation, and inspection of an engineered
plumbing system, alternate material, and equipment.
L 1 .3 The Authority Having Jurisdiction has the
right to require descriptive details of an engineered
plumbing system, alternate material, or equipment
including pertinent technical data to be filed.
L 1 .4 Components, materials, and equipment must
conform to standards and specifications listed in
Table 14-1 of this code and other national consensus
standards applicable to plumbing systems and
materials.
L 1.5 Where such standards and specifications are
not available, alternate materials and equipment
must be approved per the provisions of Section 301.2
of this code.
L 2.0 Engineered Plumbing Systems.
L 2.1 Definition. Engineered Plumbing System: A system
designed for a specific building project with drawings
and specifications indicating plumbing materials to be
installed, all as prepared by a person registered or
licensed to perform plumbing design work.
L 2.2 Inspection and Installation. In other than one-
and two-family dweUings, the designer of the system is
to provide periodic inspection of the installation on a
schedule found suitable to the Authority Having
Jurisdiction. Prior to the final approval, the designer
must verify to the Authority Having Jurisdiction that
the installation is in compliance with the approved
plans, specifications, and data and such amendments
thereto. The designer must also certify to the Auth-
ority Having Jurisdiction that the installation is in com-
pliance with the applicable engineered design criteria.
L 2.3 Owner Information. The designer of the system
must provide the building owner with information
concerning the system, considerations applicable for
any subsequent modifications to the system, and
maintenance requirements as applicable.
L 3.0 Water Heat Exchangers.
L 3.1 Heat exchangers used for heat transfer, heat
recovery, or solar heating shall protect the potable
water system from being contaminated by the heat-
transfer medium.
L 3,2 Single- wall heat exchangers shall be permitted
if they satisfy all of the following requirements:
(1) The heat- transfer medium is either potable
water or contains essentially nontoxic
transfer fluids having a toxicity rating or
class of 1 (see Section 207.0).
(2) The pressure of the heat-transfer medium is
maintained at less than the normal
minimum operating pressure of the potable
water system.
Exception: Steam complying with
Section L 3.2 (1) above.
(3) The equipment is permanently labeled to
indicate that only additives recognized as
safe by the FDA shall be used in the heat-
transfer medium.
L 3.3 Other heat exchanger designs may be
permitted where approved by the Authority Having
Jurisdiction.
L 4.0 Fixture Unit Values for Bathroom Groups.
L 4.1 Tables L-1 and L-2 reflect the fixture unit loads
for the fixtures in bathrooms as groups, rather than
as individual fixtures. Such fixtures include water
closets, lavatories, and bathtubs or showers. The
tables reflect diversity in the use of fixtures within a
bathroom and between multiple bathrooms.
L 4.2 The listed water supply fixture unit values in
Table L-1 reflect the load of entire bathroom groups
on the cold-water service. Individual hot and cold
water branch piping to the fixtures should be sized
according to Chapter 6 and Appendix A.
L 4.3 The listed drainage fixture unit values in Table
L-2 reflect the load of entire bathroom groups on the
sanitary drainage system. Where fixtures within
bathrooms connect to different branches of the
drainage system, the fixture unit values for the
individual fixtures shall be used, as listed in Table 7-
3 of this Code.
L 5.0 Vacuum Drainage Systems.
L 5.1 Vacuum drainage systems shall be considered
engineered systems and shall comply with the
requirements of L 1.0 and L 2.0.
L 5.2 Vacuum drainage systems, including piping
tank assemblies, vacuum pump assembly, and other
components necessary for the proper function of the
system shall be engineered and installed in
accordance with the manufacturer's specifications.
433
Appendix L
UNIFORM PLUMBING CODE
TABLE L-1
Water Supply Fixture Units (WSFU) for Bathroom Groups'
Bathroom Groups having 1 .6 GPF Gravity-Tank Water Closets
Half-bath or Powder Room
1 Bathroom Group
1-1/2 Bathrooms
2 Bathrooms
2-1/2 Bathrooms
3 Bathrooms
Each Additional 1/2 Bath
Each Additional Bathroom Group
Bathroom Groups having 1 .6 GPF Pressure-Tank Water Closets
Half-bath or Powder Room
1 Bathroom Group
1-1/2 Bathrooms
2 Bathrooms
2-1/2 Bathrooms
3 Bathrooms
Each Additional 1/2 Bath
Each Additional Bathroom Group
Bathroom Groups having 3.5 GPF Gravity-Tank Water Closets
Half-bath or Powder Room
1 Bathroom Group
1-1/2 Bathrooms
2 Bathrooms
2-1/2 Bathrooms
3 Bathrooms
Each Additional 1/2 Bath
Each Additional Bathroom Group
Bath Group (1 .6 GPF Flushometer Valve)
Bath Group (3.5 GPF Flushometer Valve)
Kitchen Group (Sink and Dishwasher)
Laundry Group (Sink and Clothes Washer)
Notes:
1 . A bathroom group, for the purposes of this table, consists of one water closet, up to two lavatories, and
either one bathtub or one shower.
2. A half-bath or powder room, for the purposes of this table, consists of one water closet and one lavatory.
Individual
Serving 3 or
Dwelling
more Dwelling
Units
Units
3.5
2.5
5.0
3.5
6.0
7.0
8.0
9.0
0.5
1.0
3.5
2.5
5.0
3.5
6.0
7.0
8.0
9.0
0.5
1.0
4.0
3.0
6.0
5.0
8.0
10.0
11.0
12.0
0.5
1.0
6.0
4.0
8.0
6.0
2.0
1.5
5.0
3.0
Plans and specifications shall be submitted to the
Authority Having Jurisdiction for review and
approval prior to installation.
L 5.3 Fixtures. Fixtures used in vacuum drainage
systems shall comply with L 1.4 and L 1.5.
L 5.4 Drainage Load. The pump discharge load
from the collector tanks shall be in accordance with
Chapter 7 of this Code.
L 5.5 Water Supply Fixture Units. Water supply
fixture units shall be based on the values in Chapter
6 of this Code. The load requirement of a vacuum-
type water closet shall be determined per
manufacturer's specification.
L 5.6 Traps and Cleanouts. For gravity fixtures,
traps and cleanouts shall be per approved plans.
L 6.0 Special Venting of Fixtures.
L 6.1 Batteries of Fixtures (Battery Venting).
L 6.1 .1 A maximum of eight (8) floor-outlet water
closets, showers, bathtubs, or floor drains
connected in battery on a horizontal branch drain
shall be permitted to be battery-vented. The drain
from each fixture being battery-vented shall
connect horizontally to the horizontal wet-vented
drain branch. The horizontal wet-vented branch
drain shall be considered as a vent extending from
434
ALTERNATE PLUMBING SYSTEMS
Appendix L
TABLE L-2
Drainage Fixture Unit Values (DFU) for Batliroom Groups
Bathroom Groups having 1 .6 GPP Gravity-Tanl< Water Closets
Half-bath or Powder Room
1 Bathroom Group
1-1/2 Bathrooms
2 Bathrooms
2-1/2 Bathrooms
3 Bathrooms
Each Additional 1/2 Bath
Each Additional Bathroom Group
Bathroom Groups having 1 .6 GPF Pressure-Tank Water Closets
Half-bath or Powder Room
1 Bathroom Group
1-1/2 Bathrooms
2 Bathrooms
2-1/2 Bathrooms
3 Bathrooms
Each Additional 1/2 Bath
Each Additional Bathroom Group
Bathroom Groups having 3.5 GPF Gravity-Tank Water Closets
Half-bath or Powder Room
1 Bathroom Group
1-1/2 Bathrooms
2 Bathrooms
2-1/2 Bathrooms
3 Bathrooms
Each Additional 1/2 Bath
Each Additional Bathroom
Bath Group (1 .6 GPF Flushometer Valve)
Bath Group (3.5 GPF Flushometer Valve)
Individual
Serving 3 or
Dwelling
more Dwelling
Units
Units
3.0
2.0
5.0
3.0
6.0
7.0
8.0
9.0
0.5
1.0
3.5
2.5
5.5
3.5
6.5
7.5
8.5
9.5
0.5
1.0
3.0
2.0
6.0
4.0
8.0
10.0
11.0
12.0
0.5
1.0
5.0
3.0
6.0
4.0
Notes:
1 . A bathroom group, for the purposes of this table, consists of not more than one water closet, up to two
lavatories, and either one bathtub or one shower.
2. A half-bath or powder room, for the purposes of this table, consists of one water closet and one lavatory.
the downstream fixture drain connection to the
most upstream fixture connection.
L 6.1.2 Back-outlet water closets having
carriers conforming to Section 407.4 shall be
permitted to be battery-vented provided they
connect horizontally to the horizontal wet-
vented section.
L 6.1 .3 Trap arm lengths for fixtures shall not
exceed those as indicated in Table 10-1.
L 6.1.4 A battery vent shall be connected to the
horizontal wet-vented branch drain between the
two (2) most upstream fixture drains.
L 6.1.5 The entire length of the wet-vented
section of the horizontal branch drain shall be
uniformly sized for the total drainage discharge
connected thereto as per Table 7-5. The maximum
slope of the horizontal drain shall be three-
eighths (3/8) inch (10 mm) per foot (300 mm).
L 6.1.6 A relief vent shall be provided on each
wet-vented horizontal branch drain below the
upper-most floor. The relief vent shall connect to
the horizontal branch drain between the stack
and the first upstream fixture drain.
L 6.1 .7 Battery vents and relief vent connections
shall be taken off vertically from the top of the
horizontal drain.
Battery vents and relief vents shall not be
used as vertical wet vents.
435
Appendix L
UNIFORM PLUMBING CODE
L 6.1.8 Lavatories and drinking fotintains shall
be permitted to connect horizontally to the
horizontal wet-vented branch drain provided
that they are located on the same floor as the
battery-vented fixtures and each is provided
with either an individual or common vent.
L 6.1 .9 Batteries of more than eight (8) battery
vented fixtures shall have a separate battery vent
for each group of eight (8) or less fixtures, and^
the horizontal branch drain in each group shall
be sized for the total drainage into the branch,
including all upstream branches and the fixtures
within the particular group.
L 6.1.10 All battery vents and relief vents shall
be sized according to Section 904.0, but shall be
not less than one-half (1/2) the area of the drain
pipe that they serve and shall comply with
Section 905.0
L 6.2 Single Bathroom or Single Toilet Room.
L 6.2.1 An individually vented lavatory in a
single bathroom or single toilet room shall be
permitted to serve as the wet vent for one (1)
water closet and /or one (1) bathtub or shower
stall, or one (1) water closet and/or one (1)
bathtub/shower combination if all of the
following conditions are met:
(1) The wet vent, and the dry vent extending
from the wet vent, shall be two (2) inch (50
mm) minimum pipe size.
(2) The wet vent pipe opening shall not be
below the weir of the trap that it serves.
Vent sizing, grades, and connections shall
comply with Sections 904.0 and 905.0.
(3) The horizontal branch drain serving both the
lavatory and the bathtub or shower stall
shall be two (2) inch (50 mm) minimum pipe
size.
(4) The length of the trap arm from the bathtub
or shower stall complies with the limits in
Table 10-1.
(5) The distance from the outlet of the water
closet to the connection of the wet vent
complies with the limits in Table 10-1.
(6) The horizontal branch drain serving the
lavatory and the bathtub or shower stall
shall connect to the horizontal water closet
branch above its centerline. When the
bathroom or toilet room is the top-most load
on a stack, the horizontal branch serving the
lavatory and the bathtub or shower stall
shall be permitted to connect to the stack
below the water-closet branch.
(7) No fixture other than those listed in L 6.2.1
shall discharge through a single bathroom
or single toilet room wet-vented system.
L 6.3 Double Bathtubs, Bathtub/Shower
Combinations, Shower Stalls, and Lavatories.
Two (2) lavatories, each rated at 1.0 drainage fixture
unit (DFU), and two (2) bathtubs, bathtub /shower
combinations, or shower stalls, installed in adjacent
bathrooms, shall be permitted to drain to a
horizontal drain branch that is two (2) inch (50 mm)
minimum pipe size, with a common vent for the
lavatories and no individual vents for the bathtubs,
bathtub /shower combinations, or shower stalls,
provided that the wet vent from the lavatories and
their dry vent is two (2) inch (50 mm) minimum
pipe size and the length of all trap arms comply with
the limits in Table 10-1.
L 7.0 Circuit Venting.
L 7.1 Circuit vent permitted. Circuit venting shall
be designed by a registered professional engineer as
an engineered design. A maximtim of eight fixtures
connected to a horizontal branch drain shall be
permitted to be circuit vented. Each fixture drain shall
connect horizontally to the horizontal branch being
circuit vented. The horizontal branch drain shall be
classified as a vent from the most downstream fixture
drain connection to the most upstream fixture drairi
connection to the horizontal branch.
L 7.1.1 Multiple circuit-vented branches.
Circuit-vented horizontal branch drains are
permitted to be cormected together. Each group
of a maximum of eight fixtures shall be
considered a separate circuit vent and shall
conform to the requirements of this section.
L 7.2 Vent size and connection. The circuit vent
shall be a minimum of 2 inches (50 mm) in diameter
and the cormection shall be located between the two
m.ost upstream fixture drains. The vent shall connect
to the horizontal branch on the vertical. The circuit
vent pipe shall not receive the discharge of any soil
or waste.
L 7.3 Slope and size of horizontal branch. The
maximum slope of the vent section of the horizontal
branch drain shall be 1 inch per foot (25 mm per 305
mm). The entire length of the vented section of the
horizontal branch drain shall be sized for the total
drainage discharge to the branch.
L 7.3.1 Size of multiple circuit vent. Multiple
circuit vented branches shall be permitted to
connect on the same floor level. Each separate
circuit-vented horizontal branch that is
interconnected shall be sized independently in
accordance with Section L 7.3. The downstream
circuit-vented horizontal branch shall be sized
436
ALTERNATE PLUMBING SYSTEMS
Appendix L
for the total discharge into the branch, including
the upstream branches and the fixtures within
the branch.
L 7.4 Relief vent. A 2-inch (50 mm) relief vent shall
be provided for circuit-vented horizontal branches
receiving the discharge of four or more water closets
and connecting to a drainage stack that receives the
discharge of soil or waste from upper horizontal
branches.
L 7.4.1 Connection and installation. The
relief vent shall connect to the horizontal branch
drain between the stack and the most
downstream fixture drain of the circuit vent.
The relief vent shall be installed on the vertical
to the horizontal branch.
L 7.4.2 Fixture drain or branch. The relief
vent is permitted to be a fixture drain or fixture
branch for a fixture located within the same
branch interval as the circuit-vented horizontal
branch. The maximum, discharge to a relief vent
shall be four fixture units.
L 7.5 Additional fixtures. Fixtures, other than the
circuit-vented fixtures, are permitted to discharge to
the horizontal branch drain. Such fixtures shall be
located on the same floor as the circuit-vented
fixtures and shall be either individually or common
vented.
L8.0 Single-Stack Vent System
L 8.1 Where permitted. Single-stack venting shall
be designed by a registered professional engineer as
an engineered design. A drainage stack shall be
permitted to serve as a single-stack vent system
when sized and installed in accordance with Sections
L 8.2 through L 8.9. The drainage stack and branch
piping in a single-stack vent system shall provide for
the flow of liquids, solids, and air without the loss of
fixture trap seals. .
L 8.2 Stack Size. Drainage stacks shall be sized
according to Table L-3. A maximum of two water
closets shall be permitted to discharge to a 3-inch (80
mm) stack. Stacks shall be uniformly sized based on
the total connected drainage fixture unit load, with
no reductions in size.
L 8.2.1 Stack Vent. The drainage stack vent
shall have a stack vent of the same size
terminating to the outdoors.
L 8.3 Branch Size. Horizontal branches connecting
to a single-stack vent system shall be sized according
to Table 7-5.
Exceptions:
(1) No more than one water closet within 18
inches (457 mm) of the stack horizontally shall
be permitted on a 3-inch (80 mm) horizontal
branch.
(2) A water closet within 18 inches (457 mm) of a
stack horizontally and one other fixture with up
to 1-1/2 inch (40 mm) fixture drain size shall be
permitted on a 3-inch (80 mm) horizontal branch
when connected to the stack through a sanitary
tee.
L 8.4 Length of horizontal branches.
L 8.4.1 Water closets shall be no more than four
(4) feet (1,219 mm) horizontally from the stack.
Exception: Water closets shall be permitted to
be up to eight (8) feet (2,438 mm) horizontally
from the stack when comiected to the stack
through a sanitary tee.
L 8.4.2 Fixtures other than water closets shall be
no more than twelve (12) feet (3658 mm)
horizontally from the stack.
L 8.4.3 The length of any vertical piping from a
fixture trap to a horizontal branch shall not be
considered in computing the fixture's horizontal
distance from the stack.
L 8.5 Maximum vertical drops from fixtures.
Vertical drops from fixture traps to horizontal
branch piping shall be one size larger than the trap
size, but not less than two (2) inch (50 mm) in
diameter. Vertical drops shall be four (4) feet (1219
mm) maximum length. Fixture drains that are not
increased in size, or have a vertical drop exceeding 4
feet shall be individually vented.
L 8.6 Additional venting required. Additional
venting shall be provided when more than one water
closet is on a horizontal branch and where the
distance from a fixture trap to the stack exceeds the
limits in Section L 8.4. Where additional venting is
required, the fixture (s) shall be vented by individual
vents, common vents, wet vents, circuit vents, or a
combination waste and vent pipe. The dry vent
extensions for the additional venting shall connect to
a branch vent, vent stack, stack vent, or be extended
outdoors and terminate to the open air.
L 8.7 Stack Offsets. Where there are no fixture
drain connections below a horizontal offset in a
stack, the offset does not need to be vented. Where
there are fixture drain connections below a
horizontal offset in a stack, the offset shall be vented.
There shall be no fixture connections to a stack
within 2 feet above and below a horizontal offset.
L 8.8 Separate Stack Required. Where stacks are
more than two stories high, a separate stack shall be
provided for the fixtures on the lower two stories.
The stack for the lower two stories may be comiected
to the branch of the building drain that serves the
stack for the upper stories at a point that is at least 10
437
Appendix L
UNIFORM PLUMBING CODE
pipe diameters downstream from the base of the
upper stack.
L 8.9 Sizing Building Drains and Sewers. In a
single-stack vent system, the building drain and
branches thereof shall be sized in accordance with
Table 7-5, and the building sewer shall be sized in
accordance with Table 7-8.
438
ALTERNATE PLUMBING SYSTEMS Appendix L
Table L-3
Single-Stack Size
Stack Size
Maximum Connected Drainage Fixture Units
(inches)
Stacks Less than 75
Stack 75 Feet to Less than
Stack 160 Feet or
Feet in Height
160 Feet in Height
Greater in Height
3
24
NP
NP
4
225
24
NP
5
480
225
24
6
1,015
480
225
8
2,320
1,015
480
10
4,500
2,320
1,015
12
8,100
4,500
2,320
15
13,600
8,100
4,500
439
Appendix L UNIFORM PLUMBING CODE
440
USEFUL TABLES
Conversion Table
''The information contained in these tables are not part of this American National Standard (ANS) and
have not been processed in accordance with ANSI's requirements for an ANS. As such, these tables may
contain material that has not been subjected to public review or a consensus process. In addition, they do
not contain requirements necessary for conformance to the standard."
MULTIPLY BY TO OBTAIN
Acres 43,560 Square feet
Acre-feet 43,560 Cubic feet
Acre-feet 325,851 Gallons
Atmospheres 76.0 Cm of mercury
Atmospheres 29.92 Inches of mercury
Atmospheres 33.90 Feet of water
Atmospheres 14.70 Pounds /square inch
Btu/minute 12.96 Foot-Pounds/ second
Btu/minute 0.02356 Horsepower
Centimeters 0.3937 Inches
Centimeters of mercury 0.01316 Atmospheres
Centimeters of mercury 0.4461 Feet of water
Centimeters of mercury 27.85 Pounds /square feet
Centimeters of mercury 0.1934 Pounds/square inch
Cubic feet 1728 Cubic inches
Cubic feet 0.03704 Cubic yards
Cubic feet 7.48052 Gallons
Cubic feet 29.92 Quarts (liquid)
Cubic feet/minute 472.0 Cubic cms /second
Cubic feet/minute 0.1247 Gallons /second
Cubic feet/minute 62.43 Pounds of water/minute
Cubic feet/ second 0.0646317 Million gallons/ day
Cubic feet/second 448.831 Gallons /minute
Cubic yards 27 Cubic feet
Cubic yards 202.0 Gallons
Feet of water 0.02950 Atmospheres
Feet of water 0.8826 Inches of mercury
Feet of water 62.43 Pounds/square feet
Feet of water 0.4335 Poimds/square inch
Feet/minute 0.01667 Feet/second
Feet/minute 0.01136..... Miles/hour
Feet/second 0.6818 Miles/hour
Feet/second 0.01136 Miles/minute
Gallons 3785 Cubic centimeters
Gallons 0.1337 Cubic feet
441
UNIFORM PLUMBING CODE
MULTIPLY BY TO OBTAIN
Gallons 231 Cubic inches
Gallons 4 Quarts (liquid)
Gallons water 8.3453 Pounds of water
Gallons /minute 0.002228 Cubic feet/second
Gallons/minute 8.0208 Cubic feet/hour
Gallons water /minute..... 6.0086 Tons of water/24 hours
Inches..! 2.540 Centimeters
Inches of mercury 0.03342 Atmospheres
Inches of mercury 1.133 Feet of water
Inches of mercury 0.4912 Pounds/square inch
Inches of water 0.002458 Atmospheres
Inches of water .0.07355 Inches of mercury
Inches of water 5.202 Pounds/square feet
Inches of water 0.03613 Pounds/square inch
Liters 1000 Cubic centimeters
Liters 61.02 Cubic inches
Liters 0.2642 Gallons
Miles 5280 Feet
Miles/hour 88 Feet/minute
Miles/hour 1.467 Feet/second
Millimeters 0.1 Centimeters
Millimeters 0.03937 Inches
Million gallons /day .1.54723 Cubic feet /second
Pounds of water 0.01602 Cubic feet
Pounds of water 27.68 Cubic inches
Poimds of water 0.1198 Gallons
Pounds /cubic inch 1728 Pounds/cubic feet
Pounds/square foot 0.01602 Feet of water
Pounds/square inch 0.06804 Atmospheres
Pounds/square inch 2.307 Feet of water
Pounds/square inch 2.036 Inches of mercury
Quarts (dry) 67.20 Cubic inches
Quarts (liquid) 57.75 Cubic inches
Square feet 144 Square inches
Square miles 640..... Acres
Square yards 9 Square feet
Temperature (°C) + 273 1 Abs. temperature (°C)
Temperature (°C) + 17.28 1.8 Temperature (°F)
Temperature (°F) + 460 1 Abs. temperature (°F)
Temperature (°F) - 32 5/9 Temperature (°C)
Tons (short) 2000 Pounds
Tons of water/24 hours 83.333 Pounds water/hour
Tons of water/24 hours 0.16643 Gallons /minute
Tons of water/24 hours 1.3349 Cubic feet/hour
442
USEFUL TABLES
Areas and Circumferences of Circles
Diameter
Circumference
Area
nches
mm
Inches
mm
Inches'
mm*
1/8
6
0.40
10
0.01227
8.0
1/4
8
0.79
20
0.04909
31.7
3/8
10
1.18
30
0.11045
71.3
1/2
15
1.57
40
0.19635
126.7
3/4
20
2.36
60
0.44179
285.0
1
25
3.14
80
0.7854
506.7
1-1/4
32
3.93
100
1.2272
791.7
1-1/2
40
4.71
120
1.7671
1,140.1
2
50
6.28
160
3.1416
2,026.8
2-1/2
65
7.85
200
4.9087
3,166.9
3
80
9.43
240
7.0686
4,560.4
4
100
12.55
320
12.566
8,107.1
5
125
15.71
400
19.635
12,667.7
6
150
18.85.
480
28.274
18,241.3
7
175
21.99
560
38.485
24,828.9
8
200
25.13
640
50.265
32,428.9
9
225
28.27
720
63.617
41,043.1
10
250
31.42
800
78.540
50,670.9
EQUAL PERIPHERIES
S = 0.7854 D
D = 1 .2732 S
S = 0.8862 D
D = 1.1284 S
S = 0.2821 C
EQUAL AREAS
Area of square (S') =
1 .2732 X area of circle
Area of square (S) =
0.6366 X area of circle
C =nD = 2jtR
C:
= 3.5446 Varea
D:
= 0.3183 C = 2R
D:
= 1.1283 l/area
Area =jiR2 = 0.7854 D2
Area = 0.07958 C2 =jrD2
ji = 3.1416
443
UNIFORM PLUMBING CODE
Flow in Partly Filled (One-Half Full) Pipes
(Based on Manning's Formula with n = .012)
gpmx6.31 = L/s
ft/sec X .305 = m/s
in. X 25.4 = mm
o o o ■<-
in to h- 00 cjs
10,000
9,(X)0
8.000
7.000
6,000
5,000
4,000
3.000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
5
3
a
c
5
c
o
o
o
d
o
o
6
d
c
c
6
o
o o
d d
o
d
6
d
o
d
o
d
o
o
o
o
o
d
o
For 3/4 Full
Multiply Qx1.9
VX1.15
«•
y
,•
^
>i^
y^
^
^
t^
^
k
^
^
y
,^
-"
^.,1
y^
<:
X
-^
\
y
*^
-^
,^
\
^t^
\^if^ \
A
>
\
>
^
\ \
\
\
s,
^
y
^ ^
vf
\
t^
\ ji
'"'N
V.
>
y
■^
L
^
V
s%\
>^
-^
\
X^-'^
\
V
V
^
\
s
\
X
\
\
-"""^X
\
X
'^>
Sy
>
\
\
\
^
-^
\
^C
^
y
>
\
\
A
A
V
\
V
\
s
S^
8>
^^
>
V^
\
\
»rf^
)>
<
^
\
^ >
K
*^
\
n^
x*^
^
>^
\
^
\
\
y
^
\
^.
>
\
^
^
\
\
\
>
\
\
\
<
^
\
^
\.<^
X
\
\
,*
\
_X'''\
\
^^
M
V
V
^
\
^
<^
\
c
\
N
,y^'
s..
^
«*'
Z'^
\
\
i,
^
^
\
k
\
>
c
y^
^
\
L
rf*"
•
y^ \
\
\
y*
\
V
^
^
■ j>
^
^
\
s
\
'■■>^'
\
\
\
\
^
^
^
y
s
x^
\
\
\
\
V
<^
^
^
y^
^
X
y
*^
\
9
\
.'i^
^
>
y
>
J**
10,000
1,000
100
10
SLOPE (FT./FT.)
444
USEFUL TABLES
Flow in Partly Filled (Full) Pipes
(Based on Manning's Formula with n = .012)
10.000
9,000
8.000
7,000
6,000
5.000
2,000
1,000
900
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
gpm X 6.31 ^ L/s
ft/sec X .305 = m/s
in. X 25-4 = mm
U3 (^ CO O)
o o o o •-
o o o o o
3 O
c
o
o
o
o
c
o
o o
o
o
o
o
o
o
o
o
y
^
at
y
^
^'
y'
V'
y
""■""S^
V
1.
' y
y
y
y
y
\%
K
y
y
y
^
y
^
\
v
V.
V
\
y
^
^
?
^
\
\
\
\
\
\
\
\
y
\
y
\
\ V-
^^
\
JV
\
\
V^\
^^
\
^3^
>
^<'
\
^ \
\
\
\
^
V^
\
y
\
y
y
\
^^>\^
\
^y
y\
\
k,,„, ,
— ^
V
\
\
^ ^
x.^
^r
\
%■"
^
•n,:
\
\
\
V
<<<'
^
\
y^
i
*'"
x
y^
\
y
\
\
\
^
^'
\
\
y \
^
c
\
\
^
^
\
y
y
\
\
\ ^■''!^
\^
\.
y^
)>>
y
\
y
^
\^
^
\
\
V
y
y
•
\ *
^iiX'"'^
\
\
\
\
\
y
\
y
\
^^
^'
\
.-^' \
\y
\
^
^^
>
i"^
y
s.
a ^
\
\
y^
rf*
\>
ly
\
\
^'
A
s
,>v
\
\
^y
x*
\
\
\
V
1
.^
^
\
\
V
y
y
^
^
^^
y
y
y
A
e *
y
y
^
y
^
y^
^
^vv^
>*
^
y^
y
y
y
•
10,000
,000
100
10
SLOPE (FT/FT.)
445
UNIFORM PLUMBING CODE
METRIC SYSTEM
(INTERNATIONAL SYSTEM OF UNITS - SI)
For the users of this code, we are including a short explanation and some conversion tables to aid in the
conversion of our familiar English units to the forthcoming SI units.
This is written with the code users in mind, and will detail only those measurements used in everyday work
and calculations. For the scientific units, we recommend the use of ANSI Z210.1, "Metric Practice Guide."
GENERAL COMMENTS
Our present system of measuring involves the three dimensions of force, length and time. The SI units involve
mass, length, and time. The change of force to mass has meaning in scientific and engineering work, but for
practical use in ordinary construction, we will show kilogram to pounds conversion values, although an exact
conversion would be pounds force divided by the acceleration due to gravity to mass units.
In the same manner, the SI units for temperature expressed in Kelvins and based on absolute zero will be
given as degrees Celsius, which is the more familiar and practical Centigrade degrees.
The SI system measures angles in radians where there are 2 pi radians in a circle, but using a 1.5708 bend to
change from a vertical stack to a horizontal house drain is not as easy as calling out a 1/4 bend or an ell for
water piping.
The foregoing notes are intended to show that in making conversions from one unit system to another, a
little common sense niust be used and the degree of accuracy needed to do the job at hand.
The following tables are set up using this approach and using the preferred SI units.
446
USEFUL TABLES
METRIC SYSTEM
(INTERNATIONAL SYSTEM OF UNITS - SI)
TO CONVERT
INTO
MULTIPLY BY
Atmospheres
Cm of mercury
76.0
Btu
Joules
1,054.8
Btu/hour
Watts
0.2931
Btu/minute
Kilowatts
0.01757
Btu/minute
Watts
17.57
Centigrade
Fahrenheit
(°C X 9/5) + 32°
Circumference
Radians
6.283
Cubic centimeters
Cubic inches
0.06102
Cubic feet
Cubic meters
0.02832
Cubic feet
Liters '
28.32
Cubic feet/minute
Cubic cm/ second
472.0
Cubic inches
Cubic cm
16.39
Cubic inches
Liters
0.01639
Cubic meters
Gallons (U.S. liquid)
264.2
Feet
Centimeters
30.48
Feet
Meters
0.3048
Feet
Millimeters
304.8
Feet of water
Kg /square cm
0.03048
Foot-Pounds
Joules
1.356
Foot-pounds / minute
Kilowatts
2.260 X 10-^
Foot-pounds / second
Kilowatts
1.356 X 10-^
Gallons
Liters
3.785
Horsepower
Watts
745.7
Horsepower-hours
Joules
2.684 X 10*^
Horsepower-hours
Kilowatt-hours
0.7457
Joules
Btu
9.480 X 10-*
Joules
Foot-pounds
0.7376
Joules
Watt-hours
2.778 X 10*
Kilograms
Pounds
2.205
Kilograms
Tons (short)
1.102 X 10-3
Kilometers
Miles
0.6214
Kilometers/hour
Miles /hour
0.6214
Kilowatts
Horsepower
1.341
Kilowatt-hours
Btu
3,413
Kilowatt-hours
Foot-pounds
2.655 X 10^
Kilowatt-hours
Joules
3.6 X 10^
Liters
Cubic feet
0.03531
447
UNIFORM PLUMBING CODE
METRIC SYSTEM
(INTERNATIONAL SYSTEM OF UNITS - SI)
(Continued)
TO CONVERT
INTO
MULTIPLY BY
Liters
Gallons (U.S. liquid)
0.2642
Meters
Feet
3.281
Meters
Inches
39.37
Meters
Yards
L094
Meters /second
Feet /second ,
3.281
Meters /second
Miles/hr
2.237
Miles (statute)
Kilometers
1.609
Miles /hour
Meters /minute
26.82
Millimeters
Inches
0.03937
Ounces (fluid)
Liters
0.02957
Pints (liquid)
Cubic centimeters
473.2
Pounds
Kilograms
0.4536
PSI
Pascals
6,895
Quarts (liquid)
Liters
0.9463
Radians
Degrees
57.30
Square inches
Square millimeters
645.2
Square meters
Square inches
1,550
Square millimeters
Square inches
1.550x10-^
Watts
Btu/hour
3.4129
Watts
Btu/minute
0.05688
Watts
Foot-pounds /second
0.7378
Watts
Horsepower
1.341 X 10-'
When the plumbing industry, including plumbers, suppliers, and manufacturers, actually begins the metric
conversion program, it will undoubtedly follow^ the guidelines of committees selected from all phases of the
construction industry as set up under the American National Metric Council.
The final preferred units used will be those that apply to our industry and will be of the magnitude to
simplify and ease job calculations and avoid confusion and ambiguity.
The conversion looks complex and confusing, but when the metric system was first proposed in France, an
attempt was made to include a ten-hour day, a ten-day week, and ten months to the year, but cooler heads
prevailed and our time still follows the sun and seasons. Likewise, assigning new units or numbers to the
quantities we must work with cannot change the basic hydraulic principles that plumbers have worked with
throughout history.
Information on conversion factors is provided by ANSI, the American National Metric Council, and the
Division of Designatronics, Inc.
448
INDEX
© 2006 International Association of Plumbing and Mechanical Officials. All rights reserved.
The copyright in this index is separate and distinct from the copyright in the document that it indexes. The
licensing provisions set forth for the document are not applicable to this index. This index may not be
reproduced in whole or in part by any means without the express written permission of lAPMO.
Abandoned cesspools, grease interceptors,
septic tanks, and seepage pits 722.0, Appendix K
Absorption area, capacity of Table K-4, Appendix K
Access panels 203.0, 404.2, 414.1
Accessible, definition 203.0
Accessibility of:
Backwater valves 710.0, 1006.0
Chemical waste system 811.0
Cleanouts 707.0, 719.0
Fixtures for inspection, repairs, and cleaning .... 407.0
Floor drain traps 1006.0
Gas meters : 1209.6
Grease traps or interceptors 1009.0
Industrial interceptors and separators ......... 1009.0
Receptors 804.0
Regulator and relief valves 608.0
Septic tanks Appendix K
Shutoff and control valves 605.0, 1211.9
Slip joints , 404.2
Sump and receiving tanks 810.0
Valves, gas 1211.9
Valves, water 605.0
Water heateris 505.0
Acrylonitrile-butadiene-styrene (ABS) 203.0, 701.0,
707.1,903.0
Additions 101.4.1
Additives, packing, prohibited .- . ; 705.1.5
Advance notice for inspections 103.5.4.1
Airbreak:
Definition 203.0
Required 801.1
Airgap:
Defirution 203.0
Required .603.3.5, 801.1, 806.0, 807.4
Air intakes, vent termination near 906.0
Air tank, for sumps 710.0
Air tests:
Gas piping system 1214.0
Water piping system 103.5.3.3
Alterations and repairs:
Deviations allowed 101.4.1.1.1, 301.1,4
Gas piping 1211.0
Alternate materials 301.0
Anchors and hangers . see Supports, 221.0
Appliance:
Connectors 1212.0
Gas, demand requirements 1216.0, Table 12-1
Indirect waste type 806.0-808.0
Application for permit 103.2
Approval required:
Appliances, fixtures . . . . 301.0, 406.0, 505.0, 508.0, 610.0
Backflow preventers , 603.0
Ballcocks : .603.4.2
Cesspool Appendix K
Chemical waste system 811.0
Combination waste and vent system 910.0,
Appendix B
Completed plumbing work 103.5.1
Devices 603.1
Flue, vents 510.2
Grease trap 1011.0
Indirect waste receptors 804.0
Industrial interceptors and separators 1009.0
Materials, specifications, standards 301.0, 707.0
Plans 101.3
Seepage pit Appendix K
Septic tank and disposal system Appendix K
Special fixtures 406.0
Vacuum breakers 603.0, 603.2.2
Water heaters, gas 505.0
Water heaters, oil 506.0
Approved, general definition 203.0
Approved testing agency 203.0
Area Drain, definition 203.0
Asbestos cement pipe joint 705.1.4
Aspirator, definition 203.0
Aspirators, protection 603.4.9
Attachment, vertical piping 314.0
Authority Having Jurisdiction 203.0
Authority to:
Disconnect gas 1207.0
Render gas service 1206.0
Automatic:
Clothes washer stand pipe 804.0
Flushing tanks 410.2
Flush valves 410.1&3
Priming device, for floor drains 1007.0
Siphon, septic tank Appendix K
Auto wash racks 1011.0
-B-
Backfilling 315.0
Backflow 204.0, 603.0, 1002.0
Backflow cormection 204.0, 603.0
Backflow preventer see Cross-Connections,
Back-Siphonage, 204.0, 205.0
Backing for fixtures 404.4
Back-pressure backflow 204.0, 603.0
Back-siphonage see Cross-Connections,
Backflow Preventer, 204.0, 205.0
Back-siphonage of traps, protection 1002.0
Back-to-back fixtures 704.0
Backwater valve 204.0, 710.0
Ballcocks, approval required 603.4.2
Baptistries 406.1
Bathtub, prohibited type 405.0
Bell and spigot joints 705.1
Bell h-aps, prohibited , 1004.0
Benching of trenches 315.0, 720.0
Blow off condensers 810.0
Boiler blowoff :
Definition 204.0
Prohibited discharge 810.0
449
UNIFORM PLUMBING CODE
Bolts, noncorrosive 407.4
Bowl wax or gaskets 316.3
Branch, definition 204.0
Branch, fixture, definition 204.0
Branch, horizontal, definition 204.0
Branch vent, definition 204.0
Brass connections, ground joint 705.3.3
Brass pipe 701.0, 604.0, 903.0, 1209.5.2.3
Brazing or welding joints 310.2, 316.1.7
Btu rating, gas appliances 1209.4.2
Building, definition : 204.0
Building drain (sanitary)
Defirution 204.0
Size of 703.0
Building drain (storm), definition 204.0
Buildings over sewer 101.4.1.1.2
Building sewer Chapter 7, Part II
Cleanouts 719.0
Combined, definition 204.0
Damage to 306.0
Definition 204.0
Distance from building and below ground .313.0, 720.0
Grade and support of 718.0
Location of 308.0, 313.0, 718.0, 721.0, Table 7-7
Material of 715.0
Must be on same lot as buildings 308.0
Required 305.0, 713.0
Sanitary, definition 204.0
Size of 717.0
Storm, definition 204.0
Testing of 723.0
Water pipe in trench 720.0
Building sewers and drains, existing 101.4.1.1.2
Building subdrain, definition 204.0
Building supply, definition 204.0
Burned lead joints 705.1.3
Burred ends 310.3, 609.1, 701.2.1, 903.4, 1209.5.5
Bushings, solder 701.4.2, Table 7-2
-C-
Capacity of:
Disposal field Appendix K
Seepage pits Appendix K
Water closet tanks 402.0
Cast-iron soil pipe and fittings
Joints and connections 705.2.2
Support of 314.0
Caulked joints 705.1.1
Caulking, waterproofing 407.0
Caulking ferrules 701.4, 705.3.3, Table 7-1
Cement mortar joints, prohibited 705.1.2
Certificate of Final Approval 103.5.6.3, 1205.0
Certification by:
Backflow assembly testers 205.0, 603.1
Medical gas certifiers 1328.1.1
Medical gas installers 1311.3
Medical gas systems 1311.2
Pipe welder 225.0
Cesspool: Appendix K
Abandoned 722.0
Connections to sewer prohibited 714.3
Definition 205.0
Distance from lot line, building, surface Table K-1
Must be on same lot as building 308.0
Change in direction of drainage piping 706.0
Change in direction of gas piping 1211.5
Check valves:
In gas systems 1211.12.6
In water systems ....;... 608.3
Chemical toilet, prohibited 405.3
Chemical waste 205.0, 811.0
Clarifier 205.0, 1009.0
Clay, vitrified 701.0
Joints and connections 705.2.1
Cleanout plugs or caps 707.1- 3, 707.13, 707.14,
Cleanouts .707.0, 719.0
Clearance for:
Water heaters 505.3.1, 505.3.2
Water heater vents 510.0
Clear water waste, definition 205.0
Clinic sink, definition 205.0
Closet bends, prohibited type 311.0
• Maximum length 1002.2
Closet rings 316.3, 316.3.2, 704.0, 704.4
Closet screw bolts 704.4.5
Clothes washer stand pipe 804.0
Code:
Definition 205.0
Validity of 103.8
Combination fixture 1001.0
Combination waste and vent system 205.0, 910.0, Appendix B
Combustible material, definition 502.6
Combustion air, required 507.0
Common 205.0, 905.0
Common vent, gas 510.6.4
Compartments for:
Water heaters 505.0
Compression joints 316.1.5
Concealed slip joints 404.2
Concealing of work prohibited before inspection 103.5.1 .1,
103.5.1.3, 1204.0
Condensers and sumps 810.0
Control, shutoff valves 605.0, 1211.9, 1212.4
Connection:
At septic tank Appendix K
Indirect waste piping 803.0
To plumbing system, required 304.0
To sewer, required 305.0, 713.0
Connector, gas 1212.0
Connector, vent 510.10, 510.11
Construction, existing 101.4.1.3
Contamination 205.0, Table 6-2
Continuous vent, definition 205.0
Continuous waste:
Definition 205.0
Materials 404.3
Multiple fixtiares 1001.0
Cooling units:
Drains 801.0
Potable water waste pipes 808.0
Cooling water, connection permitted 808.0
Copper and lead pans 411.8
Copper pipe or tubing:
Connection to screwed pipe 316.2.1
Fittings for 604.0, 701.0, 903.0, 1209.5.8.4
Forming 609.1
Joints and connections 606.2.1
Location and use of 604.0, 701.1.4, 811.1, 903.0
Marking of 604.3
QuaUty and weight of material 604.2, 701.1.4
Support of 314.0
Corrections, inspection 103.5.6.1-2
450
INDEX
Corrosion, protection from 313.5, 609.3, 1211.1.3
Cover plate 707.9, 710.10
CPVC— CMorinated poly (vinyl chloride) 205.0, 604.1,
Critical level 205.0, 603.4.5
Cross-connections see Backflow, Back-Siphonage
Approval of preventive devices 601.0-603.0
Backflow preventers 602.0-603.0
Control .601.0-603.0
Critical level 603.4.5
Definition .205.0
Prohibited 601.0-603.0
Vacuum breakers 603.2.2, 603.2.5, 603.2.6
Cross-linked polyethylene (PEX), definition ......... .218.0
Cutting of structural members 313.2
-D-
Damage to drainage and sewer systems ....... 306.0, 714.0
Dangerous or insanitary plumbing 101.5.2
Defective material, gas 1214.0
Defective systems, testing of 103.5.5.1
Definition of terms Chapter 2, 502.0, 1203.0
Demand, gas appliance .1209.4.2
Department Having Jurisdiction, definition 206.0
Detrimental wastes 307.0, 1009.0
Developed length:
Defirution 206.0
Trap arm 1002.0, Table 10-1
Diameter, definition 206.0
Dielectric insulator 508.1
Direct connection of water piping to sewer 602.0-602.2,
805.0, 807.1, 808.0
Direct vent water heater .502.7, 505.1
Direction, change of 706.0-707.0, 719.0
Discharge capacity, fixture 702.0
Dishwasher cormection, domestic 807.4
Disposal fields for septic tanks Appendix K>
Table K-1
Disposal of:
Food waste 404.4, 714.4, 1001.3, 1014.1.3
Liquid waste 303.0
Distance of trap from vent 1002.2, Table 10-1
Distribution boxes, disposal fields Appendix K
Domestic sewage, definition , 206.0
Doors, shower stalls 411.6
Double traps, prohibited 1004.0
Dosing tanks Appendix K
Downspout, definition 206.0
Drain:
Building, definition 204.0
Fixture, definition 208.0
Floor 411.0, 1006.0
House, definition 210.0
Sub-drains (showers) 411.8
Drainage:
Below curb and main sewer level 710.0
By gravity required 709.0
Change in direction . see Change in direction, drainage
Cormection to sump 710.0
Connection to sewer or private
disposal system 305.0, 713.0
Damage to 306.0, 714.0
Defective .103.5.5.1
Durham or recessed screwed fittings 701.2, 701.2.1
Fittings, material 311.8, 701.2, 707.0
Grade or fall 708.0, 718.0
Indirect wastes chapter 8
Length between trap and vent 1002.2, Table 10-1
Material of 301.0, 701.0, 811.0
Protection of 313.0
Sizes of, minimum 703.0
Steam and hot water 810.0
Support 314.0, 718.0
Waste and vent Table 7-5
Drilling, improper notching 313.11
DriiJcing fountains 405.1, 809.0
Drum traps, vented 1004.0
Durham system, definition 206.0
-E-
Easements for sewers 308.1, 721.2
Effective opening, definition 207.0
Ejectors 710.0
Example, illustrating use of gas tables 1217.0
Excavations 315.0, 1204.0
Exceptions:
Connection to sewer 713.6
Independent systems 312.0
Tests 103.5.3.3
Vent size Table 7-5, 904.0
Water piping 610.13, 720.0
Excessive water pressure 608.2
Existing work 101.4.1.3, 207.0, 301.1.4
Expansion joints 705.3.2
Expansion of pipe, provision for 313.2
_F-
Fall of sewers 718.0
Faucets 601.0, 601.3
Fees 103.3-5, Table 1-1
Ferrules, caulking 701.4, 705.3.3, Table 7-1
Fill> for building sewers 718.0
Final inspection, certificate .103.5.6.3, 1205.0
Fittings:
Cleanout 707.0, Table 7-6
Drainage 701.2
Gas piping 1209.5.4, 1209.5.8, 1209.5.9
IrUet, for fixture connections 704.1
Material of 604.0, 710.4, 1209.5
Prohibited 311.0, 604.10, 903.3, 1209.5
Screwed . 311.8
Threaded 311.8
Water piping 604.0
Fixture:
Branch, definition 208.0
Connections 704.0
Drain, definition 208.0
Flanged connection 316.3
Supply 208.0, 601.1, 610.0
Unit 208.0, 702.0
Urut flow rate 610.3, 702.0
Fixtures see Plumbing Fixtures
Flagpoling of vents 906.3
Flammable Vapor or Fumes 208.0
Flanges 316.1-3, 704.4
Flared joints 606.1.1, 705.3.3
Flashing 313.8, 510.6.1, 906.5
Flood level 208.0, 807.4
Flood-level rim .208.0, 603.3.5
Flooded, defirution 208.0
Floor drains 411.0
Backwater valve required 1006.0
Trap location and type 411.0, 1006.0
451
UNIFORM PLUMBING CODE
Water supply 601.0
Water trap supplies (primers) 1007.0
Floor flanges see Flanges
Floors, under shower compartments 411.0
Flow rates, in fixture units 610.3, 702.0
Flue collar 502.8
Flush tanks 208.0, 601.0
Flush valves, definition 208.0
Flushometer tank '. . . .208.0, 603.4.3
Flushometer valve . . .208.0, 603.4.1, 610.10, Tables 6-5 & 6-7
Flux, solder .316.1.3
Food-handling equipment 801.2
Food waste disposal unit 404.4, 714.4, 1014.1.3
Freezing, protection of pipes 313.6, 609.1
-G-
Gang or group showers, definition 209.0
Garbage grinder see Food Waste Dosposal Unit
Food waste disposer 1014.1.3, 404.4
Gas Chapter 12
Appliance connectors 1203.1, 1212.1
Appliance demand 1209.4.2, Table 12-1
Authority to disconnect 1207.0
Authority to render service 1206.0
Capping or plugging outlets required .....;... 1207.3
Connectors 1212.1
Definition 1203.0
Demand, appliance Table 12-1, 1209.4.2
Disconnecting appliances 1207.0
General .1202.0
Hourly volume, rating 1216.2
Inspection 103.5, 1204.0
Installation of 1202.0, 1211.0
Leaks 1214.0
Liquefied Petroleum '1213.0
Location of meters and access thereto 1209.6
Material oi 1209.0
Meters 1209.6
Meters, location 1209.6
Piping, definition 1203.3
Piping size . . . 1216.0, 1217.0, Table 12-7 to Table 12-41
Piping system, definition 1203.4
Plans required 101.3
Service piping, definition 1203.8
Test .1214.0
Temporary use of 1208.0
Undergroimd piping .1211.1
Utility supplying 1203.6, 1205.0
Gas piping:
Access to meter 1209.6.2
Defects, cracks, splits, prohibited 310.0
Definition 1203.0
Inspection and testing 1204.0, 1214.0
Installation 1211.2
Material . ; .1209.5
Required gas supply 1216.0
Size 1216.0, 1217.0
Supporting fixtures 1211.2.6, Table 12-3
Unions , 1211.3.2(4)
Gas water heater; see definition 502.15
Approval requirements 501.0
Clearances 505.3
Combustion air required .507.0
Draft hoods .510.12
Inspections 504.0
Oil burning or other ; . 506.0
Permits required 503.0
Pressure-relief valves 608.0
Prohibited locations 505.1
Protection 505.0, 506.0, 510.0
Sealed combustion 502.7, 510.2.5
Vent required ... 510.2.1
Gas water heater vent:
Approved type required 510.6
Area of .510.6.3
Common vent 510.10.4
Connector 510.10
Damper prohibited 510.15
Definitions 502.0
Drafthoods .....510.12
Engineered system 510.7.5.1
Existing masonry chimneys 510.5.4
Hood, cap or cowl 510.6.2
Inspections 504.0
Location and support 510.6.5, 510.7.6
Location of draft hood and connectors ....... 510.12.5
Material 510.10.2
Mechanical draft systems 510.3.4
Protection and support 510.6.5
Required 510,2.1
Sizeof 511.0
Termination .-. 510.6.2
Grade:
Building sewer 718.0
Definition 209.0
Horizontal drainage • • . • .708.0
Gravity drainage required ; 709.0
Gravity supply tariks 607.0
Gray water systems .Chapter 16
Grease interceptors Chapter 10
Definition 209.0
Design and construction Chapter 10
Where required .1009.0-1014.0
Grease traps:
Construction and design 1014.0
Definition .209.0
Sizes Table 10-2
Ground joint connections 705.3.3
Grounding 604.8
-H-
Hangers see Supports
Harmful waste see Waste, detrimental and harmful
Health and safety .101.2, 101.5.2
High hazard 210.0, Table 6-1
Horizontal branch .210.0, 703.0
Horizontal pipe, definition 210.0
Horizontal-to-horizontal drainage fittings 706.0
Horizontal-to-vertical drainage fittings 706.0
Horizontal vent pipes Table 7-5, 904.0
Hose connections 603.2.3, 1212.0.
Hot-mopped shower pans see Shower pans
Hot water boiler ; . Table 14-1
Hot water pipe sizing ; .610.0
House drain .see Building sewer
House sewer see Building sewer
-I-
Identification:
Copper tubing . . ; ............. ...604.3
Gas piping 1209.6.5, 1209.7.7
Piping, fittings, h-aps, and fixtures ..... 301.1.2, 1003.1
Required 301.0
Water lines, nonpotable — . .601.2
452
INDEX
Increasers 316.4, 317.0
Independent system of sewers 312.0
Indirect waste:
Appliances 807.0
Condensers and sumps 810^2
CooHng water 808.0
Drinking fountains 809.0
Food-handling equipment ; 801.2
Sterilizing equipment 801.5, 806.0
Indirect waste piping:
Approval required 802.0
Cleanouts 803.0
Connections 801.1, 805.0
Definition : 211.0
■ Hot water 810.0
Maximum length 803.0
Required 801.0
Size of 803.0
Steam and hot water .810.0
Vents 803.0
Indirect waste receptors:
Approval required 802.0
For clothes washers 804.0
Materials 802.0
Prohibited location 804.1
Required water supply 601.0, 1007.0
Size of 804.1
Individual vent 211.0, Table 7-5, 1014.0
Industrial interceptors and separators 1009.0-1012.0
Iridusfrial wastes 211.0, 307.0
Approval required 811.1, 1009.2
Disposal .811.0
Materials 811.2, 1009.2
Pretreatment 811.1
Inlet fittings for fixture connections 704.2
Insanitary:
Construction .101.4 1.3
Definition 211.0
Inspection and testing:
Abandoned sewers, cesspools 722.0, K 11
Advance notice for 103.5.4.1, 1204.0
Building sewer 723.0
Certificate 103.5.6.3, 1205.0
Concealment of work, prohibited
before inspection 103.5.1.1, 103.5.1.3, 1204.0
Disposal fields Appendix K
Final 103.5.6.3, 504.2, 1204.3.2
Fliies and vents .504.0
Gas piping, rough emd final '. 1204.3
Labor and material for ...;.... .103.5.4.2
Water heaters 504.0
Water piping 103.5.1.1
bispector see Authority Having Jurisdiction
Installation of:
Building sewer: 715.0, 717.0, 718.0
■ Cleanouts 707.0, 719.0, 803.0, Table 7-6
Devices to prevent cross-connections 602.0, 603:0
■ Drainage piping system Chapter 7
Fbctures 407.0
Floor drains and shower stalls 411.0
Gas piping systems 1211.0
Overflows 403.0
Urinals 402.3, 405.2, 407.0, 409.0410.0
Vents Chapter 9
Water piping system 609.0
Insulator, dielectric 508.1
Intake, air, vent termination near 906.2
Integral traps .1001.1, Table 7-3
Intercepting hoppers or sink see Receptors
Interceptors:
Abandoned 1014.3.7
Auto wash rack . ; 1011.0
Cleaning required 1009.6
Cleanouts, location 707.8
Definition : . . . .209.0
, Design 1014.3.3
Effluent sampling 1014.3.5.1
Grease , 1009.0-1015.0
Industrial .1009.0
Location 1009.5, 1014.3.4
Maintenance 101.4.1.2, 1009.6
Packing establishments 1010.0
Required .1009.1
Sizing 1014.2.2, 1014.3.6, 1015.4
Slaughterhouse 1010.0, 1014.2.2
Vent 902.0
Waste discharge requirements 1014.1
Intermixing of metals prohibited 311.6, 508.1, 604.1
Invert, definition 211.0
Iron pipe size (IPS) pipe 302.0
Island fixture, venting 909.0
-J-
Joints and connections:
Additives prohibited 705.1.5
Brazed 212.0, 316.1.7, 609.3.2
Cast iron 705.1, 705.2
Cement mortar, prohibited 705.1.2
Compoi-mds, thread lubricants 316.1.1
Compression 316.1.5, 606.2.1
Copper to iron 311.6, 316.2.1
Copper tube 316.2.1, 606.2.1
Earthenware to metal 316.3.1
Elastomeric gasketed 705.1.7
Expansion 705.3.2
, Fixture . , 316.3, 407.0
Flexible : 316.1.5
Floor-mounted 316.3, 704.0
Gas and watertight .103.5.3.5
Gaspiping 1209.5
Ground joint unions 705.3.3
Hubless cast iron '. 705.1.9
Increasers and reducers .317.0
Lead 316.1.2, 705.1, 705.2.4
Mecharucal .'. .606.1.2
Molded rubber 705.1.6
Prohibited fittings and practices .... 311.0, 316.4, 317.0
Rubber ring 705.1.7
Screwed . - 316.1.1
Shield coupling 705.1.8
Slip 404.2, 705.3.1, 1003.2
Soldered or sweat 212.0, 316.1.3
Solvent cement 316.1.6
Special 316.2
Threaded .316.1.1
Tightaiess 103.5.3.5
Tubing 316.1.3, 316.2.1, 606.2.1, 1209.5
Union 316.2.2, 609.5, 1211.3.2
453
UNIFORM PLUMBING CODE
Vitrified clay 705.2.1
Welded 225.0, 705.1.3, 1211.3.2
Wiped 316.1.2
Jurisdiction, Department Having, definition 206.0
-K-
Kitchen sinks, prohibited types 405.3
-L-
Labeled, definition 214.0
Labor for tests 103.5.4.2
Laboratories, chemical 811.0
Laundry tubs 1003.1
Lavatories 413.1
Lavatories in sets, definition 214.0
Lawn sprinklers 603.4.6
Lead joints see Joints, Lead and Connections
Lead:
Sheet 401.2, 701.3
Shower receptor 411.8
Lead pipe:
Traps and bends 701.3
Leader, definition 214.0
Leaks, gas piping 1214.0
Length:
Developed, definition 206.0
Drainage piping 703.0, Table 7-5
Vent piping Table 7-5, 904.0
Length and size of gas pipes 1217.0
Liquefied petroleum gas (LPG) 1201.0, 1203.5, 1213.0
Liquid waste:
Definition 214.0
Disposal of 303.0
Listed 214.0
Listing Agency, definition 214.0
Loading, fixture unit Tables 6-5, 7-3 & 7-4
Location of:
Backwater valve 710.1, 710.4, 710.6, 1006.0
Fbchires 309.0
Gas meters and risers 1209.1
Gas valves 1209.1
Industrial interceptors and separators 1009.0
Plumbing or sewer on lot 308.0, 721.0, Table 7-7
Pressure-relief, regulator, or check valves 608.0, 1209.7
Private sewage disposal system Appendix K
Secondary protection, water heaters 506.2
Shutoff valves 605.0, 1209.10, 1211.9.2 .
Temperature reUef valves 608.3
Vent terminals 510.6.2, 906.0
Water heaters 505.0, 508.0
Lot, definition 214.0
Lot line, termination of vents from 906.0
Low hazard 214.0, Table 6-2
Lubricants, thread 316.1.1, 705.1.5, 1209.5.7(d)
-M-
Macerating Toilet System, definition 215.0, 710.13
Main, definition 215.0
Sewer see Public Sewer
Vent, definition 215.0
Water main 225.0
Maintenance 101.4.1.2, 1007.0, 1009.6, 1014.6
Material:
Alternate 301.0, 406.3
Approval required 301.0
Backwater and gate valves 605.4, 710.4, 710.6
Building drain .701.0
Building sewer 715.0
Cesspool Appendix K
Cleanouts 707.0
Combustible, definition 502.6
Condensers 810.2
Drainage systems 701.0
Fittings 301.0, 311.0, 707.2, 710.4, 710.6, 1209.5
Gas piping .1209.5
Marking of 301.0, 604.3, 710.6, 716.0, 1003.1
Protection of 315.4, 1211.1
Septic tank Appendix K
Showers 411.0
Shower control valves 418.0
Soil and waste pipes 701.0
Specifications, standards 301.0
Sumps 710.8
Thread lubricants 316.1.1, 1209.5.7(d)
Traps 1212.7
Valves and fittings .605.0
Vents 903.0
May, definition ;215.0
Meat packing and slaughterhouses ; 1010.0
Medical gas systems '. Chapter 13
Metals, intermixing prohibited 311.6
Meters, gas:
Location of 1209.6.2
Meters, water 610.1, 610.8, Appendix A
Minimum standards 301.0
Mobile home parks and
recreational vehicle parks Appendix E
Mortar, cement joints prohibited 705.1.2
-N-
Natural gas, specific gravity 1216.0
Nipples, soldering 316.1.2
Non-corrosive bolts : 407.3, 407.4
Notching 313.2
Nonpotable water piping 603.4.11, 610.13(6)
Notice of inspection 103.5.4.1
Nuisance .101.4.1.3, 216.0, 713.6
-O-
Obstiuctions to flow 311.5, 316.4.1-2
Offset 217.0, 510.6.1.1, 706.4, 905.3
Oil interceptors 1009.0
Opening, effective, definition 207.0
Open trench work 315.3
Overflow:
For gravity supply tank 607.0
Plumbing fixture 403.0
Rim, flood-level rim 208.0, 403.0
Oxygen and gas interconnected 1211.12
-P-
Packing additives prohibited 705.1.5
Packing houses, grease interceptors required 1010.0
Penalties 102.3.2, 103.5.6.1
Percolation tests Appendix K
Permit, required 101.3, 103.4.4.1, 103.5.1, 503.0
Photographic studio sinks, wastefrom 811.8
Piping:
Building, adjacent to 313.4
Building supply size 610.0
454
INDEX
Cleanout 707.0, 719.0
Compounds, thread lubricants 316.1.1, 1209.5.7(d)
Diameter, definition 206.0
Drainage, horizontal, grade of 708.0
Drainage piping, size of 703.0
Embedded in masonry or concrete 313.2
Gas, definition of 1203.2
Gas, size of 1216.0, 1217.0
Hangers and supports 314.0, 1211,2.6, Table 12-3
Horizontal , definition 210.0
Hot water, size of 610.0
Improper location 309.0
Interconnection of gas systems 1211.11,1211.12
Joints 103.5.3.5, 316.0, 317.0, 606.0, 705.0
Nonpotable water 603.4.11
Protection from freezing , 313.6
Protection required 313.0, 315.0, 609.3, 1211.0
Size of; see Diameter 302.0, 703.0, 904.0, 610.0,
1216.0, 1217.0
Reaming 310.3, 609.1, 701.2.1, 903.4, 1209.5.5
Sizes of 302.0, 904.0
Soil, definition 221.0
Special wastes 221.0, Chapter 8
Threads 311.8, 316.1.1, 701.2.2, 1209.5.7
Tube, forming 609.1
Underground .... 316.2.2, 604.2, 701.1.1, 903.1.1, 903.3,
1211.1
Vent 224.0, Chapter 9
Vertical 224.0, Table 3-2, Chapters 7 & 9
Waste 225.0, Chapters 7 & 8
Waste, indirect 211.0, Chapter 8
Water, materials 604.0
Water, size of 610.0
Water-distributing, definition 225.0
Welder, definition 225.0
Wrapping 609.3.1, 1211.1.3
Pit, seepage 221.0, Table 1-1, 122.0, Appendix K
Plans required or may be required 101.3, 802.0
Plastic joint solvent cement 316.1.6
Plugs, caps, cleanout 707.1-2
Plugging, fixture outlets '. 101.4.1.1.3
Plumbing:
Additions and alterations 101.4.1
Appliance, definition 218.0
Appurtenance, definition 218.0
Connected to sewer or private
disposal system 304.0, 305.0, 713.0
Defective, test of 103.5.5.1, 103.5.6.2
Definition 218.0
Inspection of 103.5
Installation, material for Chapter 7
Official see Authority Having Jurisdiction
Repair 101.4.1.1.1-2
System, definition 218.0
Test required 103.5.3
Uncovered for inspection 103.5.1.4
Plumbing fixtures 218.0, 401.1
Accessibility 407.1, 407.6
Alternate materials 301.2, 406.3
Backing of 407.2, 407.4
Back-to-back .704.2
Below curb or sewer level 710.1-2
Chemical resistant 406.3
Clearance from wall, toilet, urinal 407.6
Connections, drainage 316.3, 404.0, 406.0, 704.1
Control valves 605.0
Distance from traps . . .1001.2, 1001.4, 1002.2, Table 10-1
Floor drains and showers 411.0, 1006.0
Improper location of 309.0
Indirect connection 804.1
Indirect waste 804.0
Installation of 407.0
Island 909.0
Joints 316.0, 404.0, 406.1-407.0
Material of 401.0, 406.3, 411.0
Must be cormected to sewer 304.0, 305.0
Must be provided with trap 1001.0
Overflows 403.0
Prohibited 311.0, 311.5, 405.0, 410.3, 910.0
Required 411.1
Setting 316.3.1, 407.6
Size of waste for 702.0, 703.0, Table 7-3
Special fixtures 406.0
Standards 401.0
Strainers and connections 404.0
Supply and waste connection, access to 404.2
Supply fittings 407.8
Unit equivalent . . . 610.3, 702.0, 703.0, Tables 6-5, 7-3 & 7-4
Water supply required 601.0
Pollution 218.0
Polyethylene (PE) 604.1
Polypropylene (PP), definition 218.0
Polyvinyl Chloride (PVC) 218.0, 604.1, 701.1, 701.2
Potable water;
Definition 218.0
Protection of 602.0, 603.0
Supply required 601.0
Unlawful connection to ; 602.0
Poured joints 705.1.1
Pressure drainage connections prohibited 805.0
Pressure, excessive, water 608.2
Pressure losses, water 610.0
Pressure regulator, when required 608.2-6
Pressure, regulator, gas .1209.7
Pressure-relief valve 505.4, 505.6, 506.2, 608.0
Preventer, backflow 204.0, 603.2
Primary settling tarJ< 902.1
Private or private use, definition 218.0
Private sewage:
Capacity of system Appendix K
Construction Appendix K
Disposal system 218.0, Appendix K
General 103.5.1.3, Appendix K
Location 721.0, Table 1-1, Appendbc K
Private sewer, definition 218.0
Private water supply 602.2, 602.4
Prohibited:
Additives, packing ; 705.1.5
Cement mortar joints : .705.1.2
Concealment of defects 310.2, 1214.4.3
Concealment of work before inspection .103.5.1, 705.1.1
Connections, rainwater 306.2
Connections, waste .... 403.0, 801.1, 801.2, 805.0, 806.0
Cormections, water 602.0
Copper tubing, use of 903.2.3, 1209.5.2.3
Damage to drainage system 306.1, 313.0
Defective material 103.1.2.1, 301.1.1, 1214.4
Direct drainage 603.3.5, 801.1, 810.1
Double trap fixture 1004.0
Drinking fountain location 405.1
Fittings : 311.0, 316.4
Fixtures 311.5, 405.0, 408.2
455
UNIFORM PLUMBING CODE
Food waste disposal, connection to .... 1001.3, 1014.1.3
Gas water heaters in bathroom, bedroom 505.1
Industrial waste disposal 307.0
Joints and connections .316.4, 606.2.2, 705.1
Liquefied petroleum gas . . . ; 1213.0
Pipes in masonry 313.2
Practices 101.4.1.1.2, 310.2, 311.0, 313.2, 313.4,
313.6,316.4,602.0,714.0
Receptors, location of 804.1
Trapjoints 1003.0
Traps . . . . ; .1004.0
Trough type urinals . . . . ; 405.2
Union couplings in gas piping 1211.3.2(4)
Urinals and water closets on
combination waste and vent 910.7
Water piping in drainage or sewer trench . . .720.0
Zinc alloy die cast components .406.4
Property line, termination of vent 906.2
Protection from:
Corrosion 313.1, 313.5, 609.3.1, 1209.5.6
Freezing ....;.... , 313.6
Protection of :
Piping materials and structures 313.0, 1209.5
Potable water supply ....:... .603.0
Trap seal ...1002.1,1005.0,1007.0.
Water heaters 505.3, 506.2
Public, or public use, definition 218.0
Public sewer, definition .218.0
Public shower floors 411.1
-Q-
Quality and weight of materials,
general regulations Chapter 3
Quality of fixtures ...... 401.1
Quick-disconnect device 1212.5
-R-
Rain and surface water drains 306.2, 714.2
Rainwater systems Chapter 11, Appendix D
Rate of flow, fixture unit . . 610.0, Table 6-5, 702.0, Table 7-3
Reaming pipes 310.3, 606.1.1, 701.2.1, 903.4, 1209.5.5
Receiving tank or sump ........ .710.2-3, 710.7-10, 710.13.1
Receptors:
Accessible 804.1, 811.4
Approval required .802.0, 804.1
Cormected indirectly to sewer 801.1-2
Definition 220.0
Indirect Waste .804.0
Maximum distance from fixture 804.1
Required ..........'... 801.1-2,811.1
Shower, shower stalls 411.0
Size of trap, vent, waste 803.0
Type and size ; . . 804.1
Recessed or Durham fittings 206.0, 701.2.1
Reclaimed water Chapter 16
Recommended loadings, sewage
disposal .Table 7-5, Appendix K
Reducer, where required 317.0
Refrigerators ...........: .Table 7-3, 801.2
Regulators/gas supply ...........;....... 1202.0, 1209.7.4
Regulators, relief valves on water supply 608.2-6
Relief vent ....'...:... .220.0, 907.0
Connections .....; 805.0
For closed condensers, sumps, interceptors 810.1-2,
1009.0
Remote outlet, defiiution 220.0
Repairing:
Defective gas pipe, prohibited 1207.0
Defective pipe and fittings , ''. 101.5.2
Repairs and alterations to plumbing and
drainage system 101.4.1.1
Required:
Plans .101.3
Plumbing fixtures .' .411.1
Sewer cormections 304.0, 305.0
Vents ; 901.0
Responsible for testing 103.5.4.2
Restauranty grease trap ;1014.1
Retesting '. . . .103.5.6.2
Rim:
Definition ; . 220.0
Flood level 208;0, 603.3.5, 603.4.9, 905.3, 909.0
Rise:
Horizontal vent .1 .905.3
Vents above fixture .905.3
Riser .220.0, 610.1
Roof drains 220.0, 306.2
Roof supply tanks 607.0
Roof, termination of vents above 510.6.2, 906.1,
906.3,906.7
Roughing-in, definition 220.0
Running water, required 601.1
-S-
Saddle, sleeve, band outlets, prohibited 311.1
Safety and health , 101.5.2
Safety devices 505.0, 603.3-14, 608.0,
Sand interceptor:
Cleanout for 707.8
Definition ....:....,.... see Interceptor
Design .1009.1, 1009.3
Required 1016.1
Required for steam exhaust or blow off 810.0, Table 8-1
Secondary 902.1
Type of ti-ap 1009,2
Vent, required and not required 901.0,902.0,
1002.1-2, 1002.4
Water seals .1007.0
Sanitary tees, permissible use 706.2
Screw pipe, supporting of .......; 314.0
Screw pipe to cast iron 705.2.3
Screw pipe to copper tubing 316.2.1
SDR, defiiution 221.0
Seal, trap; see Trap, seal .1005.0, 1007.0
Screw joints ... .316.2.1, 705.2.3
Secondary energy protection .505.3, 506.2
Secondary sand interceptors 902.0
Secondary temperature limiting device , . 506.2
Seepage lines .Appendix K
Seepage pit Appendix K
Abandoned Appendix K
Construction Appeiidix K
Location .721.0, Table 7-7
Size ; .Appendix K
Soil absorption Appendix K
Self-cleaning traps .Table 7-3, 1003.1
Separate plumbing and drainage systems 312.0
Separate venting .811.6, 906.3
Separator .... .1009.0
Septic tanks . . 221.0, Appendix K
Abandoned 722.2-5, Appendix K
Connections to sewer prohibited ...... . . . . . 714.3
Location of ... 721.0, Table 7-7
456
INDEX
Wastes, connection to 714.3
Service, authority to render gas 1206.0
Service piping, gas, definition , 1203.8
Setting fixtures : 316.3.1, 407.6
Settling tank 902.1
Sewage:
Defirution 221.0
Disposal of 303.0, 305.0, 709.0, 713.0, 714.0,
Sewage disposal system, private Appendix K
Construction 713.3
Holding tank 714.5
Location 721.0, Table 1-1
Sewage ejector, definition 221.0
Sewage pump, definition 221.0
Sewers Chapter 7
Abandoned 722.0
Adjacent to walls 715.1, 718.3, Table 1-1
Available 305.2, 713.2, 713.4
Building, material of 701.0, 715.1
Building sewer 204.0, Chapter 7
Cleanouts 719.0
Connection to, required .304.0, 305.0, 713.0
Construction of 715.0-719.0, Table 1-1
Damage to 306.1, 714.1, 811.1
Depth of .708.0, 718.3
Easements for 721.2
Ejectors 710.2
Existing .101.4.1.1.1-2, 312.0, 705.1.2, 713.6
Grade and support of 708.0, 713.6, 718.0
Independent system required 312.0
Inspection, order of 103.5.1
Installed on made or filled-in ground 718.2
Location . . . .308.0, 313.0, 718.0, 720.0, 721.0, Table 1-1
Materials 101.4.1.1.2, 715.1, 718.3, 720.0
Mobile home 215.0, Appendix E
Must be on same lot as building . . . . 308.1, 312.0, 721.1
Pipe joints 705.1, 705.3.1
Private sewage disposal system 218.0, 305.1-2,
713.1-2,713.6
Public, definition '.. .218.0
Public, damage to 306.1, 714.1
Required 305.1-2, 713.1-2, 713.6
Size of building 710.5, 717.0, Table 7-8
Testing of :...... 101.4.1.1.2
Water pipe in trench 720.0
Shall, definition 221.0
Sheet lead 411.8, 701.3
Shielded couplings 221.0, 705.1.8
Shock arrester, definition 221.0
Short turn 1/4 bend, prohibited 311.5, 706.1
Should, definition 221.0
Shower stall or compartment 411.7
Showers, gang, drainage 209.0, 411.9, Table 7-3
Shower pans .411.8
Shower receptors 411.8
Shutoff valves ,605.0, 710.4, 1211.9
Single-family dwelling, definition 221.0
Sinks:
Chemical, special use 406.3
Island ; 909.0
Prohibited 405.3
Sinks and laimdry tubs .1001.2-3
Types prohibited .... 405.3
Size of:
Building sewer ...... 703.0, 705.0, 717.0, Tables 7-3, 7-8
Cesspool .Appendix K
Combination waste and vent piping 805.0, 910.0,
Appendix B
Combustion air vents 506.1, 507.0
Disposal field Appendix K
Drainage piping, minimum 703.0, 707.3, 707.10,
Table 7-3
Gas piping system 1216.0, 1217.0
Indirect waste pipes 803.0
Pipe cleanout 707.11, Table 7-6
Seepage pit Appendix K
Septic tank Table 7-3, Appendix K
Trap 702.0, Table 7-3, 910.4, 910.6, 1003.3, 1006.0
Vent pipes 710.10, Table 7-5, 810.1, 904.0, 905.4,
906.3,908.2,908.3,910.3,
Vent stack Table 7-5, 904.0, 907.1
Water piping 609.0, 610.0
Slaughterhouses 1010.0
Slip joints 316.1.5, 705.1.6, 705.1.8-9, 705.3.1, 705.3.3
Slip joints, traps 705.3.1, 1003.2
Slope see Grade
Softener 610.2
Soil pipe 221.0, 311.2, 311.4, 311.6, 704.4.1,
704.4.3, 705.1.9, 722.2, 1002.4
Soil porosity Appendix K
Soil stack, minimum size 703.0
Solder, bushings and ferrules 316.1.2, 701.4.2,
Tables 7-1 & 7-2
Solder fluxes 316.1.3
Solder joints 212.0, 316.1.2-3, 316.2.1, 316.3.1,
606.2.1,705.3.4
Spacing:
Gas risers or meters 1209.2, 1211.5
Pipe supports 314.1, 314.7, Table 3-1
Special fixtures 406.0, 406.3
Special joints 316.2.1
Special waste pipe see Industrial Waste
Special wastes:
Acid and chemical 811.0
Definition 221.0
High temperatures 810.1, Table 8-1
Laundries, bottling works, wash racks 702.0, 711.0,
1012.0, 1013.0
Specific gravity, natural gas 1216.1
Specifications for materials Chapter 3, Table 14-1
Stack .221.0, 311.4, 705.3.2, 711.0, 904.0, 906.1, 907.0
Standards for materials Chapter 3, Table 14-1
Standpipe, clothes washer 804.1
Steam exhaust condenser or blow off 810.0, Table 8-1
Sterile equipment .806.0
Storage tanks:
Gravity 607.0
Hot water 506.2
Storm drain, definition '. 221.0
Storm sewer, definition 221.0
Strainers .404.1, 410.1
S-trap prohibited 1004.0
Street main; see Water main 225.0, 610.7, Table 6-5
Structural condition safety 313.11
Studding and joists, cutting of 313.2
Sub-drain, shower stalls 411.8
Submittal of plans 101.3, 103.2.1.4, 103.3.1, 103.4.2-3
Subsoil drain, definition 221.0
Substitute materials 301.2
Subsurface disposal field Appendix K
Suds relief ^ .711.0
Sump:
Boiler room, installation 810.1, 810.3
Building, backwater devices 710.2
457
UNIFORM PLUMBING CODE
Building drainage systems below sewer level .... 710.2
Condensers 810.0, Table 8-1
Construction 810.2
Definition 221.0
Pump cormection permitted 710.2-3, 710.9, 805.0,
Table 7-4
Pump discharges, conversion to fixture units . . . 710.4,
Table 7-4
Sewage 710.0
Vent 710.7, 710.10, 810.1, Table 8-1
Supply:
Control valves, water 605.0
Fittings, fixtures 407.8
Fixture, defirution 208.0
Hot water . . -. 601.3, 602.1, 604.1
Non-potable water 603.4.11
Pipe, size of 610.0, Table 6-5
Potable water, protection .603.0, 603.2.5
Tank, water 607.0, 608.1, 608.3
Trap, seal 1004.0, 1005.0, 1007.0
Water, quality of, source of 601.1
Supports and hangers .221.0, 314.0,Table 3-2, 510.10.10, 609.1
906.4, 1211.2.6, Table 12-3
Surface water, discharge 307.2, 714.2, 811.1
Surrounding material, urinals 407.4-5
Sweatjoints 316.1.3, 316.2.1
System:
Combination waste and vent . . . .■ 205.0, 910.0
Defective, testing of 103.5.5.1
Drainage 206.0, 712.0
Durham, defirution 206.0
Gas piping, size of 1216.0, 1217.0
Independent 312.0
Interconnection of gas piping 1211.11, 1211.12
Plumbing, definition 218.0
Vent 224.0, 712.0
Water supply 225.0, 609.0, 712.0
-T-
Tailpiece:
Connection 807.2, 910.5-6
Maximum length of 910.5
Tanks:
Automatic flushing, urinals 410.2
Boiler blow off; see Condensers
and Sumps 810.1, Table 8-1
Flush 208.0, 403.0, 407.4, 410.2, 601.1, 603.3.8,
Table 7-3
Gravity supply 607.0
Hot water storage - 608.3, 608.6
Inlet to 603.4.2, 603.4.5, 710.9, 810.1
Liquefied petroleum 1203.5, 1213.0, 1217.4
Material 710.8, 810.2
Primary settling 902.1
Septic see Septic Tank
Water closet 403.0, 405.1, 601.1, 603.4.2-3
Water supply 602.1, 607.0, 608.1, 608.3
Water supply, overflow 603.4.2, 607.0, 805.0
Temperature-limiting devices 505.5
Temperature-relief valves 505.5, 505.6
Temporary use of gas 1208.0
Termination of vents 510.6.2, 906.1
Tests:
Advance notice for 103.5.4.1
Air 103.5.3.3, 103.5.3.5, 1214.1.7
Alternate materials, methods 301.2.1
Building sewer 101.4.1.1.2, 103.5.1.3-4, 723.0
Concealing of work prohibited
before inspection 103.5.1.1, 103.5.1.3-4, 1204.0
Exceptions 103.5.3.3, 12044
Final 103.5.6.3, 712.1, 1204.3.2
Labor and material for 103.5.4.2, 1204.2
Percolation Appendix K
Required 103.5.3
Responsibility for : 103.5.4.2
Sanitary plumbing 103.5.5.1
Shower receptors 411.8.1
Testing agency 301.2.1, 610.2
Waived 103.5.3.2
Water supply system 103.5.1.1, 103.5.3.3, 610.2
Threaded joints 316.1.1, 316.2.1, 705.2.3
Threaded fittings 311.2, 316.1.1, 316.2.1, 705.2.3
Thread lubricants 316.1.1, 1209.5.7(d)
Three-compartment sinks 1001.2
Toilets:
Connections 316.4.2
Prohibited type 405.1
Trap 222.0, 1003.0
Arm 222.0, 1002.2-3, Tables 7-3, & 10-1
Drum 1004.0
Exceptions for 1001.2-3, 1002.3
Floor drain 1003.1, 1006.0, 1007.0
For sumps, condensers 810.1
For three-compartment sinks or three lavatories 1001.2
From fixture, distance of 1001.4
From vent, distance of 704.2, 1002.2, Table 10-1
Grease 209.0, 1014.0, Tables 1-1, 7-3, & 10-2
Ground metal joints 705.3.3
Horizontal distance from vent 704.2, 1002.2, Table 10-1
Indirect connection required 801.0
Industrial interceptors and separators 1009.0
Integral 1001.0
Material of 103.1.2.1, 301.1.1-2, 807.3, 1003.1
Minimum size 702.0, 1003.3, Tables 7-3 & 7-5
Prohibited types 1004.0
Protection 603.3.8, 1002.1-2
Required 1001.0
Seal 222.0, 1005.0, 1007.0
Separate for each fixture 1001.1
Size 1003.3, Table 10-1
Slip joints in 705.3.1, 1003.2
Union joint in water seal 316.2.2, 1003.2
Unit loading 702.0, Table 7-5
Vents for 103.1.2.1, 810.1, 901.0, 905.2, 905.5,
908.1, 909.0,910.5, 1002.0, Tables 7-5 & 10-1
Vent not required for 902.0
Water seal 1005.0
Weir 905.5, 1001.4, 1002.2, 10024
Vyhere required 1001.0
Trenching, excavation, and backfilling . . . 315.0, 718.0, 720.0
Trough urinals, prohibited 405.2
Tubing, copper 316.1.3, 316.2.1, 604.1^, 604.7, 606.1.1, 606.2.1,
609.3.2, 701.1.4, 705.3.3
Tubing, gas connectors 1212.1, 1212.3
Tiirmeling 315.2
-U-
Unconfined space, definition 223.0
Underground:
Copper tubing 604.2, 701.1.4
Dosing tanks Appendix K
Drainage material 316.2.2, 701.0
Gas piping 1211.1
458
INDEX
Vent material 316.2.2, 701.1.4, 903.1.1, 903
Water pipes 609.0, 720.0
Uruons:
Couplings, in gas piping 1211.0
In vents 316.2.2
Joint in seal of trap 1003.2
Where allowed 316.2.2, 1211.3.2(4)
Unit, fixture 208.0, 610.3, 702.0, Tables 6-5 to 6-7 & 7-3
Unit loading of traps 702.0
Unlawful connections 602.0
Unsanitary, definition 223.0
Urinals .316.3.1, 402.3, 403.0, 405.1, 407.6, 409.0, 601.1,
707.4(1), 1003.1, Tables 7-3 & 7-5
Use of alternate material 301.2
Use, private, definition 218.0
Vacuum breaker ..... 224.0, 409.1, 603.2, Tables 1-1, 6-2, 6-3
Vacuum relief valve, definition 224.0
Validity of code 103.7.1, 103.8
Valves 311.7, 605.0
Backwater 710.0
Check 603.2.4, Table 6-2
Flush, definition 208.Q
Flushometer 410.2-3, 610.10, Table 6-7
For drainage 710.4
For water 605.0
Hose outlet protection 603.3.8
Required 605.0, 1211.9
Temperature and pressure relief 608.0
Vent or vent pipe:
Below trap weir 905.5, 1002.4
Branch, definition 204.0
Changes in direction of 903.4
Chemical 811.2, 811.5-6
Combination waste system design 205.0, 910.0,
Appendix B
Common vent 205.0, 908.3
Connections 311.2, 805.0, 905.1, Table 8-1
Connectors 510.10
Continuous, definition 205.0
Distance of trap from 1002.2, Table 10-1
Double fitting for 704.2, 905.0
Drain and waste Table 7-3, Chapter 7
Fittings Table 7-5
Fixtures, back-to-back 704.2, 905.6
Flagpoling, prohibited 906.3
Flashing for 313.8, 906.1, 906.5
Grade of 905.1, 905.3
Height above fixture 905.3, 909.0
Height above ground 510.8.3
Horizontal Table 7-5, 904.2, 905.3
Indirect waste 801.1-2, 803.0, 805.0, 810.1, 902.0
Individual, definition 211.0
Interceptors 902.1, 1009.0
Island sinks and fixtures 909.0
Length of Table 7-5, 904.0
Material for 811.2, 903.0
Method of installation 311.5, 903.0, 906.4
Minimum size in each building Table 7-5, 904.0
Not required 803.0, 902.0
Not to be used as soil or waste pipe 311.4
Opening location 905.5, 1002.4
Parallel, connection ; 907.1
Pipe, grade and connection 905.1, 905.3
Prohibited location of 903.1.1-2, 903.3
Receptors 811.2
Relief 220.0, 805.0, 907.0, 1009.4
Required 710.0, 901.0, 904.1
Required separately on every trap 901.0, 902.1,
1002.1-2
Sizing Table 7-3, 710.0, 904.0, 905.4, 908.0, 910.4
Special 909.0
Stack 224.0, 311.4, 906.1, 907.0
Steam, exhaust 810.0
Sump 710.7, 710.10, 810.1, Table 8-1
System, definition '. 224.0
Ten stories or more . . . . , 907.1
Termination 510.6.2, 906.0
Undiininished through roof 905.4, 907.1
Unit loading Table 7-5
Vertical wet see Wet Vent
Wet see Wet Vent
Yoke : 227.0, 907.0
Vent connector 510.10
Vent or vent flue 502.0
Vertical pipe: 224.0, 703.0, 704.2, 905.6, 908.2, 910.5
Unit loading length-drainage piping Table 7-5
Piping, support of Table 3-2
Vertical-to-horizontal drainage fittings . . 706.4, 905.2-3, 909.0
Vertical wet venting see Wet Vent
Violation, notices of 103.5.6.1
Vitrified clay 701.1.3, 705.2.1, 811.2
-W-
Wall, extension through 313.1
Wall-himg fixtures, installation of . . 316.3.3, 407.1-2, 407.4-6
Wall-himg water closets, definition 225.0
Wall, recess or channel in 313.2
Wash racks, auto 1011.0
Waste Chapter 7
Chemical laboratory, photographic 811.0
Cooling water 801.0, 808.0
Combination 205.0, 901.0, Appendix B
Continuous 205.0, 404.3-4, Table 7-3
Detrimental or harmful 306.1, 307.0, 811.1, 1009.1
Food, disposal unit see Food waste disposal unit
Indirect 211.0, Table 7-3, Chapter 8, 902.0
Industrial . . . .211.0, 307.0, 811.1, 903.2.3, 1001.3, 1009.0,
1010.0, 1014.0, 1015.0
Liquid . . .214.0, 303.0, 304.0, 710.2, 811.1, 1006.0, 1009.1
Pipe, definition 218.0
Buildings over 10 stories '. 907.1
For refrigerators Table 7-3, 801.2
Indirect 211.0, 801.0, 805.0
Accessibility , 804.1
Airbreak 801.0
Airgap for 801.0, 806.0
Installation of 313.6, Table 4-1, 802.0,
803.0, 810.0
Material of, inside building 701.0
Number of fixtures allowed on Table 7-5
Size of Tables 7-3 & 7-5
Pretreatment required 811.1
Receptor, prohibited location 804.1
Special, definition 221.0
Stack, definition 221.0
Water:
Additions to existing work 101.5.1, 610.13(2),(3)
Building supply 604.1, 609.5, 610.0, Table 6-5
Conditioning 225.0, 603.0, 611.4, 610.2
Distributing pipe, definition 225.0
Distribution system Chapter 6
459
UNIFORM PLUMBING CODE
Filter 610.2
Hammer arrester, defmition 225.0
Main, definition 225.0
Non-potable lines 603.4.11, 610.13(6)
Piping:
Grounding 604.8
In sewer trench 315.4, 609.2, 720.0
Installation of 603.3.8, 604.8, 609.0, 720.0
Material 604.0
Sizing 610.0, Tables 6-4 & 6-5
Test 103.5.3
Potable . . .218.0, 316.1.3, 501.0, 602.0-603.0, 604.5,
604.7, 604.10, 607.0, 608.2, 610.1-2, 610.13(7)
Pressure:
Excessive 608.2-6
Inadequate 608.1
Loss 610.0
Regulators and relief valves 608.2-6
Private supply 602.4, Table 6-4
Prohibited materials 604.10
Protection of potable 603.0
Required 601.1, 610.3
Service, size 610.0, Table 6-5
Softener 610.2
Supply:
Cross-connectors 601.1, 602.3, 603.0
Flushometer valves see Flushometer valves
To fixhires 610.0, Tables 6-4 & 6-5
System, definition 225.0
Supply tank 603.4.2, 607.0
Temperature-limiting device 505.5, 506.2
Test 103.5, 610.2
Unlawful:
Connections 602.0
Devices 602.3
Valves, control 605.0
Water closets 316.3.1, 401.1, 403.0, 405.1, 407.0,
601.1, 603.4.1-3, 610.3, 910.7, Tables 6-5 & 7-3
Water heaters:
Access 509.3, 509.4
Clearances 505.3
Combustion air for 507.0
Definition 502.15
Gas 508.0, 1203.2
Oil-burning and other 506.0
Pressure-relief valve 608.3-6
Prohibited location , 505.1 . .
Protection .508.0
Waterproofing:
Fixture setting 316.3.1, 408.0
Flashings 313.8, 906.5
Openings 313.8
Water-sealed traps see Traps
Water softener 610.2
Water test:
Building sewers 103.5
Plumbing, drainage and vent system 103.5, 712.0
Water treatment device see Water Conditioning
Weep holes, sub-drain of shower stalls 411.8
Weight of flashing, lead 701.3
Weights and quality of materials .... Chapter 3, 604.0, 906.6
Welded lead joints 705.1.3
Welder, pipe, definition 225.0
Welding or brazing joints 316.1.7, 705.1.3
Well, distance from sewage disposal 721.1, Table 1-7
Wet vent 225.0, 316.2.2, 908.0, 910.6
Whirlpool bathtub, definition ....... 225.0
Window, termination of vents from 906.2
Wiped joints .316.1.2, 705.2.4
Wooden sinks and laundry trays 405.3
Work, concealed 103.5.1-3, 504.2, 1204.3.1-2,
Work, existing .101.4-5, 207.0
Work, exposed, where required ... 103.5.1-4, 504.2,
1204.3.1-2,1211.3
Workmanship .310.0, 609.1
Wrapping of pipe .313.1,609.3.1
Wrought iron (galvanized) .... .316.1.2, 604.6,604.8, 701.1.1
705.2.3-4,707.1,903.1
Wye connections 404.4, 706.0, 707.6-7, 710.4, 719.4,
907.2,909.0
-X- .■
X-ray darkrooms 811.8
-Y- ■ ■■ ,
Yard piping, gas 1211.0
-Z-
Zinc alloy die cast components , 406.4
460
Errata for
2006 Uniform Plumbing Code - 8th Printing
The following is a list of changes that we found after the eighth printing of the 2006 Uniform Plumbing Code.
These changes may or may not apply to your code book. However, we do encourage you to check your
code book with this list to ensure that all the changes are updated. Thank you.
Appendix A
Charts A-4
through A-7: The X and Y values for Charts A-4 through A-7 were revised to reflect the
correct conversion formula.
Chapter 5
Section 510.2.5 The reference to Section 510.8(3) has been changed to correctly refer to
Section 510.8.3
Chapter 6
Table 6-3 In the fixtures column, the conversion for % inch has been revised to read
19 mm.
06/25/08
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-4
Copper Tubing
Smooth Pipe
Type M
Type L
Type K
ai 0.2 0.3 0,4 0.5 0.6 0.B 1 Z 3 4 5 6 8 10 20 30 40 50 60 60 100
Friction Loss in Head. In Lbs. per Square-Inch per 100-Foot Length
319
Appendix A
2007 CALIFORNIA PLUMBING CODE
Chart A-4 (Metric)
630.0
S04.0
37S.0
31S.0
252.0
1B9.0
126-0
Copper Tubing
Smooth Pipe
Type M
Type L
Type K
63.0
S0.4
378
31.5
26.2
18.9
12B
T3
C
o
o
o
d3
Q.
8.3
'3
5.0
c
3.a
3.2
%
LL
2.5
1.9
Friction Loss in Head, In KfioPascals per 100 Meters Length
320
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-5
Fairly
Smooth
0.1 Q£ 0.3 QA 0^0^ D.e 1 2 3 4 S 6 S 10 20 30 40 GO 60 80 100
Friction Loss In Head, In Lbs. per Square-Inch per 100- Foot Length
321
Appendix A
2007 CALIFORNIA PLUMBING CODE
Chart A-5 (Metric)
^^"
\
^y^
. ^
^ 1
Fairly
Smooth
V/^ \^ \ ^,,--^ [
^■'-''X -.-'^''''X Xux'^"''''^^ »^
--Xi ^t\^ j^c
X .•-'"■^M ' X ^i-'-^x ' I i ^^.x*^
<■
^ \^:^^in\
^
\ —
\
>;
>^\ ^W"^ \
\
\j^ 1
, \ ^y'y^^
\
\
5;
\
^
V\j^
^
>^;
\j'^ \
K
;^
>(
^
\ ^
.Jk
JL
t^
.--"^
N
\\ \^ \
1
v^
\
V
^
\
\
V"''"^ \.-^^<\ \0^^
<
y
\
^\ ^--A^ \ y^^
V^ -f-'"'^ \
y^ \
\y\ J<'^^^^ X^r'^Q
A
X
j.^^S' *oi^
^^
■^
\
y
^^^>-Ar \
>>
f^ \
^
Ji^^ V V V,^; '
\ ^^'^\^
"V
^.^
\^ \<% \^ \ ^..^
o .
^
•^
>C \ -^ ^^ \ ■
^^
>
v^ ^>A VI
FN
i->
^_y><('
\/ii
\
r V^V
^ V^
■^
v^ Xa^ >
\\ P^^
\ y<
-^yy^yyy^k^
y<y\ P
y^"
\*^ ^^
^v^^
V'^'^'^X' \ ^
j^^\
.y^^i \ y''^\
■^V^
^ Ay — 3^''^
M<\ ^y^
/''j^ \ ^^ 1 ^
^^
\ ^ \ ^
V^^ V
\y^
^X'^^^ ^^ \
. 3r \^
V— 4
\
WA J\ \ .
^
'-K
Jv X.^
\
^
\
^
\VV^
. \
/A
^
^
Vv
^
\
v\
\^
630.0
S04.0
375.0
315.0
262.0
189.0
126,0
50.4
37,a
31.5
£5.2
•0
C
n
1S.9
c>
(U
C/3
rij&
(D
Q.
CO
^
(D
_J
6.3
C
5.0
S
3.fi
U-
3.2
2.5
1,9
1.3
0.6
0-5
0.4
0-25
0.2
0.13
0.06
— n <o — to
-- -^ •-CM
SD oj o csi r% ^
OT •- n
Friction Loss in IHead, In KiloPascals per 100 Meters Length
322
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-6
1
>
k \ 1 ^ \ ^ \
^\
1
\ ^
\l^ vk \
^
^
Fairly \
Rough
' >i
.y^
^ ^
\L-^
i-^
N,
V ^\
.jf
r
V -'^"'^^
\
^'
V^"^"''^ \
K,
r 1
V V ^
\ ^e^^^^ ^^ \ .
^^\
\ \ \
^
K
1 \
^^^MTi.
\
f
\ \ ^
\
^
h
" ^
\' \
— ^
C^r"^.>^
\
5-BV^
\^
^^
. ; ,
,^^^
\ \ VA \--^
-^r^^^
i>(
\ ^""^/V
> V,.-''^ \
<
■%
1
1
>^v:^
>^
\ \
^-A^ \
j>C\ v^
\^ >^
X
\ ']Jk
i\>r\\
^
^..^ V"""^ \?-^
'^'
\
-""'x \^ ' \' ^^^ \ \ 'P^ \
^
^r^-X^
\
>
>r \^ J<- -.
V
jf'^'^ V""'''
\ V ..-^x ^
\
^J^ \ ^"""X. J
\
^
v._i_i_A >^ ,.^. , ^J
j<^ \^ ^^ ^
^ ^
\ Tl^ VA /^ \ ; /I
\
\
v^-^\ ,^A^ '
^
^
\
,^\c\X
A
OcV\^
r f-
i
\
y
a"^^ V^'
^'' 'Sg'^^^ ^
^
^
—
^
;
NJ— :^ ^-\, "l^x-^^^.tT--^-- -v^ - \ — '
X
' —
L^ J.,.
^ ^
-\r.
v^\ \
^^
-A \ \ 1 M
k \
\ 1 V i\ \l \y-^
II
\^'\a±\ \ \ ^W>A \
^^^^^^ j>%
\ j-"''^ \ \ \ .y'^x \
.-""A '
^
ill ^Ar"'^ \ ,V'''\ \ '2*5^
\
\
^ ^\^
'"''^ \ '\ '
vV\ V
\
\
10,000
6,000
5,000
4,Q00
3,000
2,000
1,000
aoo
600
5W
400
d)
"3
c
S
ZOO
0>
Q.
(0
c
o
100
(0
m
c
^
60
o
20
0.1
0.2 0.3 0.4 0.5 0.6 0.8 1
4 5 6 a 10
20 30 40 50 80 80 100
Friction Loss in Head, In Lbs. per Square- Inch per 100- Foot Length
323
Appendix A
2007 CALIFORNIA PLUMBING CODE
Chart A-6 (Metric)
Fairly
Rough
1
\ N
\
\, :; ^\ x^-
K
p^
V
\ 1
\
\
'^ V^ \
^
X 1
\
1
^
V'
^
!
\
\ 1
\
L^
\
^'""'^'^^ \ J^^^
\
\
\ ^
A
X
^'
X
^
\
. X ^
^^
}\
x^
V
^
^
^
\ x^ .>r
\ \ \ V^^ V"
^
N
\
[.^
l\
X
-^
\
^
X'
^<C \^
^A^
■
L.
\ j^
\
\ \?)^i-\ \ ^
'"'''^ 1
A
!
.."'^
\ j-^^'^A
\
K \^ X Ac
Ax >A,, u^
^
J^ \
'^>r \ <^^ L_K
^
^'
:l^-^--A^^
A^
V' \
r
1 .x^i?-
\ V
^
^
1
--*
\^
\ ^^ VA .^ \r A'^^
^
\^
^.-^
V
^
\
\
^■<
'x
^^\ i^
\ ^..fT \ V3 J ^r^
^v
~<
^
\ v^A^
^
-X
^
\
!>J Xp^^
\
\
^
k
1 V^^^-'^'^^X x^
^
V
V
^.-^/^ .
\
*'(
fiAA:
X
V
^-'
--^^^ ^
\
Ej^v-^
^
n
\x? ^^'^"'^
1 \.
A
^
\
.^
\ X^''''''\i
\
\^
\(.?^,^^^
■^
v''
1
N
■^
^
>
^
\
X j^A \
^
t
-*"
^
^-'^X
^v^^
A
^<^
■^
S;^ — \^~^^% —
T
'
■
— r~r
i.**^ \
^\
< V
^
^
\
J^
1 ^x^
V
.-^'
X A\ V >-\ \ \
L^ 1 1
' ""^
3f^
^i V-^ \ A^ \ \ . \^
\
^^^ \
i 1 Jt^
\^
\
'k
, X X >^
>
A
^^
V.^^"^
\ ^^
^\
\
\
\
^^
A
^^
^,.^K
\
\
H-
V^\ \ :^
^
\
s
\
-^
^
[>('
.^
^^
\\
^
x
[L
L.
\
\
530.0
504.0
373-0
315.0
2S2.0
189.0
126,0
BS.O
50,4
37-fl
31.5
252
T3
C
n
i8.y
C)
tu
CO
12.6
(b
Q.
«
^
(U
_J
6.3
c
5.0
S
o
3.8
U-
3:2
2.5
1.9
1.3
0.6
0.5
0.4
0.3
0.25
- 0.2
0.06
m — 1^ o CM
(A en -- P)
o m 1^
Friction Loss in Head, In KiioPascais per 100 Meters Length
324
RECOMMENDED RULES FOR
SIZING THE WATER SUPPLY SYSTEM
Appendix A
Chart A-7
Rough
0.2 0.3 0,4 0.5 0.6 0.8 1
4 5 6 a 10
20 30 40 50 60 eo 100
Friction Loss in Head, In Lbs. per Square- Inch per 100- Foot Length
325
Appendix A
2007 CALIFORNIA PLUMBING CODE
^^_
Chart A-7 (Metric)
^
^
Rough
\
t\ A: 1
—
\l
1 \ --^'^ 1 IV^ All
\
^-.--^ J^-'-'^X
' 1
^
\
\
\
\
^
^\
kl -""^ -''''^
\i
1
^
^
^^
J
I \ \. >
_\, \,
^
^s*"^
\ ^--'^x
\
^
x'
^
^
$
\ jtf
.^^^ ■ \
Z>^
\
V^, \ 3c<
J»r NH^
—
\
p"^
^
J\ \ \ ^
•\
.^ \ 3r
.
ii!
>
_^.
j^
\
^
f \ X-"^^
^-
! N
-^ \ -^ \-^
\''
Y L*-
T
\r >^ >>
k
1 J
^A
\ ^\\ ""^-^
>?^
['■ ,
\
"•""^^ K^.""^ rtfs \^
^^^^^V'^^
>r
tt
-i.^-""'''^ \
\3r
\^
-^
\
V
' ' ^ — ;3i'*^'" \
1
[ ■ r-u
T
^
-^
A
r ' \^\
-^t^ — A^ v>^
i^„ V;>^ \
^
^
^^^
^^
i^,-\> ^A"''^ \
h^^
^
A
X
-
^^^^ >^:
■^
^ Y^ ^'^ \
V
1 \
\% >r 1
^ 1
J<p
^^<
ri
^„,x-^
\i
Xl
\
i- !iP^-A^ X^'-^
^
\l
^^-:' \l^
A
\'
\^ V'''\-
^
-^
^
.-■'A^
"^\
i--^
\
r
[^
^
A
1\ \ '2g
■\
N
^
i
>
•^ VcP
A
-^■^
lV'^^^^
^
\
^^^
\ '
l3c
-i<
\
^
^
\ V^ \
^
\
1.
\ ' J
L,*'^^^
^-^
V-A \
"
V^"^
1
^ ^
r \
r \
1
\ -A \ \
H
j
^,-^\
. >t^
\
i ,
)>f \ \ ! 1
'i.y
^^ \^-^' ' \
^x-*"^
\
>
\ \ \ J^
\
\
.-"""^^V ^^rrf"
V''^ \ ^J-'-^A
1
\ \ Jf'''^
^
.^''^'^1 \
\
\:
f-^
>
1
i
^^
^
^
k
y 1 ^.-''A^ \ \
1 Vy-"''^ \ \
\-
f
S30.0
504.0
37S.0
31S.0
2G2.0
189.0
126,0
B3.0
50,4
37.S
31,5
252
T3
C
n
i8,y
C)
(U
CO
12,6
(b
Q.
CO
^
(D
_J
B,3
c
5.0
s
o
3.8
U-
3.2
2.5
1.3
0,6
0,5
0.4
0.3
0,25
0,13
0.OS
(J) r^ TO " sj
m — 1^ o pj
en -^ OT CO ai
Friction Loss in l-lead, in KiioPascais per 100 Meters Lengtii
326
Errata for
2006 Uniform Plumbing Code - 7th Printing
The following is a list of changes that we found after the seventh printing of the 2006 Uniform Plumbing
Code. These changes may or may not apply to your code book. However, we do encourage you to check
your code book with this list to ensure that all the changes are updated. Thank you.
Chapter 4
Table 4-1: [TIA UPC-023-06] The first sentence of the second paragraph at the top of
Table 4-1, "The total occupant load shall be determined by minimum existing
requirements" has been deleted as the result of a TIA.
Chapter 5
Section 507.4.1: The reference to Figures 5-8 through 5-1 1 has been deleted to correlate with
NFPA 54, National Fuel Gas Code.
Chapter 12
Section 121 1.1 6(A) The reference to Section 1211.13 has been changed to correctly refer to
Section 1211.14.
IS 9
Tablet
The example at the bottom of Table 1 for the "Lowest temperature expected"
contains misplaced fraction lines.
IS 20
Table:
The A symbol in the tables on pages 394 - 395 were inadvertently changed
to0.
06/16/08
Errata for
2006 Uniform Plumbing Code - 5th Printing
The following is a list of changes that we found after the fifth printing of the 2006 Uniform Plumbing Code.
These changes may or may not apply to your code book. However, we do encourage you to check your
code book with this list to ensure that all the changes are updated. Thank you.
Chapter 5
Section 502.9:
The extract number reads: [NFPA 54: 3.3.105.2.2]. Revise the extract
number to read: [NFPA 54: 3.3.103.2.2]
Section 502.10:
Section 502.12:
The extract number reads: [NFPA 54: 3.3.105.2.4]. Revise the extract
number to read: [NFPA 54: 3.3.103.2.4]
The extract number reads: [NFPA 54: 3.3.105]. Revise the extract number to
read: [NFPA 54: 3.3.1 03]
Section 502.13:
The extract number reads: [NFPA 54: 3.3.106]. Revise the extract number to
read: [NFPA 54: 3.3.104]
Section 502.14:
The extract number reads: [NFPA 54: 3.3.98.7]. Revise the extract number to
read: [NFPA 54: 3.3.96.6]
Section 507.3(1): This paragraph references Figure 5-12. Revise: [See Figure 5-12] to read:
[See Figure 5-7]
Section 507.4.1: The end of this paragraph references Figure 5-7. Revise: [See Figure 5-7] to
read: [See Figures 5-8 through 5-11].
Section 510.6.2(1): The extract number reads: [NFPA 54: -/ 0.6.2(1 )(a)]. Revise the extract
number to read: [NFPA 54: 12.7.2{^){a)]
Section 510.6.3:
This paragraph references NFPA 54, Chapter 3. Revise reference to read:
NFPA 54, Chapter 13.
Section 511.2: The title references Tables 5-7 through 5-22. Revise the table references to
read: Table 5-8 through 5-22.
Table 5-20:
The note at the bottom of this table references Figure G.2.4. Revise this
reference to read: Figure 5-13.
Chapter 5. Annex G
G.1.2, Solution: The first line of the solution for G.I. 2 (pg 89) references Table 5-10. Revise
this reference to read: Table 5-9
G.I. 3, Example 3: Revise this paragraph to match the contents of its extract as stated in 2006
NFPA 54:
G.1.3. Example 3: Interpolating Between Table Values. An installer has an 80,000 Btu/h input
appliance with a 4-inch diameter draft hood outlet that needs to be vented into a 12-foot high
Type B vent . The vent connector has a 5-foot lateral length and is also Type B. Can this
appliance be vented using a 4-inch diameter vent?
Table G.2.3: The inside liner dimension for a 20x20 incli nominal liner size reads "16-
1/2x^6-3/4." Revise the inside liner dimension to read: 16-3/4x16-3/4
The equivalent area for a nominal liner size of 20x24 inches having an inside
diameter of 22 inches currently reads: 308.1 (in/
area to read: 380.1.
Revise the equivalent
The equivalent area for a nominal liner size of 24x24 inches having an inside
diameter of 22.1 inches currently reads: 308.1 (in.^). Revise the equivalent
area to read: 380.1.
The 30x30 inch nominal liner size has a second inside diameter equal to 30.0
inches with an equivalent area equal to 706.8 square inches. Revise the
table to display the additional inside diameter and equivalent area.
G.2.2, Solution:
(First paragraph, pg 92) This paragraph references Section 511.2.-/8. Revise
this reference to read: Section 5^^.1.1(5).
G.2.3, Ex. 5(b): (Masonry Chimney, Paragraph 2) The first line of this paragraph references
Section 511.2.4. Revise this reference to read: Section 5^^.1.9.
G.2.4, Ex. 5(c): (Solution, first paragraph, pg 93) The first line references 13.2.18. Revise
reference to read 511.2.18. Line 3 of this paragraph instructs the use of
Table 5-21(a) and Table 5-21(b). Revise the tables to read: Table 5-21 and
Table 5-22.
(Solution, second paragraph) Line 2 of this paragraph instructs the use of
Table 5-21(a) and Table 5-21(b). Revise the tables to read: Table 5-21 and
Table 5-22.
(Chimney Liner Requirement, paragraph 1) Line 2 of this paragraph
references Table 5-21 (a). Revise this reference to read: Table 5-21. Line 7 of
this paragraph references Table 5-21(b). Revise this reference to read: Table
5-22.
(Chimney Liner Diameter) Line 9 of this paragraph references 13.2.^9.
Revise this reference to read: 5^7.2.19.
Chapter 13
Section 1318.11(2): Table 5.1.11 should read NFPA 99; Table 5.1.11.
Installation Standards. IS 2
Image:
The image on page 331 (Approved Corners Under Uniform Plumbing Code)
has an overlapping duplicate title. Revise this image to clarify the title.
Installation Standards. IS 11
2.7.2:
2.7.2.1
Revise this section number to read 2.7.5.
Revise this section number to read 2.7.5.1
10.02.07
Errata for
2006 Uniform Plumbing Code
2"^ printing Soft Cover & 1'* Printing Loose Leaf
The following is a list of changes that we found after the second printing of the 2006 Uniform Plumbing
Code. These changes may or may not apply to your code book. However, we do encourage you to check
your code book with this list to ensure that all changes are updated. Thank you.
Page vi Tentative Interim Amendment (TIA): Please add Section 507.8 to the list. It should read,
"Section 507.8- This Tentative Interim Amendment (TIA) was issued on December 7, 2005."
Chapter 5
Section 507.8 Louvers Grilles and Screens: Remove the bar on the left and replace it with TIA.
The section should now look like the following:
TIA 507.8 Louvers Grilles and Screens.
^'"^ (A) Louvers and Grilles. The required size of
TIA
TIA
openings for combustion, ventilation, and
Chapter 6
Section 604.3: The correct ASTM reference should read ASTM B88 Seamless Copper Water
Tube as listed in Table 14-1.
Section 603.2.5 Pressure Vacuum Breaker Backflow Prevention Assembly (DC): The last
sentence of the paragraph should read, "This device shall be installed indoors only if provisions
for spillage are provided."
Chapter 10
Section 1003.2: The paragraph should read, "No more than one (1) approved slip joint fitting may
be used on the outlet side of a trap, and no tubing trap shall be installed without a listed tubing
trap adapter. Listed plastic trap adapters may be used to connect listed metal tubing traps.
Chapter 12
Section 1209.5.4.2: Revise Reference ASTM D2513 to read ASTM F1 973.
Section 1211.6 Gas Pipe Turns: Revise this section to read, "Changes in direction of gas pipe
shall be made by the use of fittings or factory bends. [NFPA 54:7.5]
Section 1214.2.5: Revise paragraph to read, "Where the piping system is connected... such
appliances and equipment shall be isolated from the piping system by closing the individual
appliance equipment shutoff valves."
Section 1214.5.3 Test for Leakage: Delete "tested" and replace it with "checked". The
paragraph should now read, "...the piping system shall be checked ior leakage."
Table 12-32 Schedule 40 Metallic Pipe:
The Inlet Pressure and Pressure Drop should be 11.0 in w.c. and 0.5 in w.c. respectively.