Skip to main content

Full text of "Small pipe hydronic system"

See other formats


1  I  B  RAHY 

OF  THE 

U  N  IVLR.SITY 

Of    ILLINOIS 

69  7 

no-  1-3 
Cop-  2. 


The  person  charging  this  material  is  re- 
sponsible for  its  return  to  the  library  from 
which  it  was  withdrawn  on  or  before  the 
Latest  Date  stamped  below. 

Theft,    mutilation,    and    underlining    of    books    are    reasons 
for    disciplinary    action    and    may    result    in    dismissal    from 
the   University. 
To  renew  call  Telephone  Center,  333-8400 

UNIVERSITY    OF     ILLINOIS    LIBRARY    AT    URBANA-CHAMPAIGN 


FEB 


BQ 


i :  i!)80 


MAR  \  5  *■ 

MAR  3  1  \m 


L161— O-1096 


Digitized  by  the  Internet  Archive 

in  2012  with  funding  from 

University  of  Illinois  Urbana-Champaign 


http://archive.org/details/smallpipehydroni02harr 


£NG»NEc*;N3  LIBR  I  I 


bONitRENuk 


ENGINEERING  EXPERIMENT  STATION 

MECHANICAL     ENGINEERING     DEPARTMENT 
|  =  B=R  STEAM  AND  WATER  HEATING 
RESEARCH  SERIES  |  =  B  =  R-2 


KCOCMK\.n     JCIMCJ     ■  —  O — H  —  M. 

ENGINEERING  LIBRAE 


SMALL  PIPE  HYDRONIC  SYSTEM 


i« 


By 
WARREN  S.  HARRIS 


Sponsored  by 
INSTITUTE  OF  BOILER  AND  RADIATOR  MANUFACTURERS 


UNIVERSITY  OF  ILLINOIS 

URBANA,  ILLINOIS 

MAY,  1959 


• 


Return  this  book  on  or  before  the 
Latest   Date   stamped  below. 

-••-.-   --■•---    - ■  --> 


"I       

»liriivergity  of  Illiaois  Library 


k-T-fr/ 


L161 — H41 


6f7 

ENGINEERING  LIBRARY 


PREFACE 

The  following  is  intended  as  a  report  of  the  pipe  sizing  procedures 
used  in  designing  the  small-pipe,  hot-water  system  tested  in  the  Research 
Home  during  the  winter  of  1958=59  <=  It  also  contains  a  description  of 
installation  procedures  and  a  discussion  of  test  results °  This  report 
neither  replaces  nor  obsoletes  present  I=B=R  Installation  Guides ,  but 
rather  it  should  suppliment  them<>  There  is  no  change  in  the  method  of 
calculating  heating  loads,  as  given  in  I=B=R  Installation  Guide  H-20,  nor 
in  the  methods  of  selecting  the  heat  distributing  units,  boiler  size,  air 
cushion  tank  size  and  pump  as  directed  in  I=B=R  Installation  Guide  500° 

The  pipe  sizing  tables  in  Guide  No0  500  limit  the  minimum  pipe  size 
in  the  main  to  3/4-  in«  and  in  branches  to  l/2  in  =  In  many  instances  these 
are  larger  than  required.-  In  the  design  of  the  small  pipe  system  these 
pipe  size  limitations  were  disregarded;, 


SMALL  PIPE  HYDRONIC  SYSTEM 


Introduction 

The  broad  objectives  of  the  research  program  conducted  at  the  University 
of  Illinois  for  the  Institute  of  Boiler  and  Radiator  Manufacturers  are  to 
find  ways  to  further  improve  performance  of  hydronic  systems  and  to  reduce 
the  operating  and  installation  costs.   The  heating  project  for  the  winter 
of  1958-59  was  aimed  at  reductions  in  the  cost  of  installation. 

Today  quiet  pumps  are  available  which  will  operate  at  heads  of  more  than 
10  ft.  of  water.  The  system  installed  in  the  I=B=R  Research  Home  during 
the  summer  of  1958  was  designed  to  take  full  advantage  of  the  high  head  of 
the  modern  pump.  Furthermore,  soft  copper  tube  was  used  throughout.  This 
is  readily  bent,  eliminating  the  need  of  many  fittings  required  in  systems 
installed  in  more  conventional  ways.  These  practices  resulted  in  a  reduction 
of  about  $150.00  in  the  cost  of  installing  the  piping  system  for  a  one-pipe, 
hot-water  system  in  a  two-story,  six-room  house  having  a  calculated  heat 
loss  of  4-3,300  Btuh  at  70  F  indoors  and  -10  F  outdoors. 

System  Design 

The  operating  conditions  for  which  the  system  was  designed  were  as 
follows: 

Average  water  temperature  215  F 

Temperature  drop  through 

the  system  20  F 

Temperature  drop  through 

each  room  heating  unit  20  F 

Total  water  circulation  rate         4.3  GFM 

Pump  head  at  above  flow  rate         L4  Ft.  of  water 

Figure  1  is  a  schematic  diagram  of  the  system  with  the  design  water  flow 
rates  for  each  section  of  piping  indicated.   This  system  was  designed  by 
adding  the  equivalent  length  of  the  fittings  to  the  measured  length  of  the 
piping  to  determine  the  equivalent  length  of  the  pipe.  Knowing  the  rate  of 
water  circulation  through  each  section  of  the  piping  and  the  pressure  head 
available ,. it  was  possible  to  make  a  suitable  selection  of  copper  tube  sizes 
from  a  standard  friction  pressure  loss  chart.   It  was  necessary  to  extrapo- 
late the  chart  down  to  nominal  l/U   in.  tube  as  no  chart  could  be  found  con- 
taining tube  sizes  smaller  than  3/8  in. 

A  preliminary  study  indicated  that  pipe  sizes  for  this  system  would  be 
too  small  to  permit  the  use  of  present  makes  of  one-pipe  fittings.   Therefore, 
the  fitting  illustrated  in  Figc  2  was  improvised.  The  diameter  of  the  ori- 
fice was  such  that  the  resistance  to  water  flow  through  the  orifice  was 
equal  to  the  resistance  offered  by  12  ft.  of  straight  tube  of  the  same 
diameter  as  the  main.  In  selecting  the  pipe  sizes  for  the  main?  the  length 
of  main  was  taken  as  the  measured  length  plus  12  ft.  for  each  orifice  in 
the  circuit*  Since  the  resistance  offered  by  the  return  tee  was  equivalent 
to  about  2  ft.  of  tube  and  at  least  1  ft.  of  tube  was  located  between  the 
supply  and  return  tee,  the  head  available  to  circulate  water  through  the 


Pushing  riser  through  stud  space  to  basement.  When  end 
of  tube  reaches  basement  second  man  pulls  the  end  free  of 
the  sill  and  pulls  enough  into  the  basement  to  make  con- 
nection to  the  main.  Man  above  then  cuts  riser  from  coil, 
leaving  enough  tube  to  make  connection  to  the  heating  unit. 


Top  end  of  riser  is  cleaned  and  soldered 
into  adaptor  in  the  end  of  the  heating  unit. 


-2- 


branch  circuits  was  assumed  to  be  equal  to  the  total  friction  head  in  15  ft, 

of  the  main.   Pipe  sizing  calculations  are  summarized  in  Table  A. 

Nominal  3/4  in.  type  L  copper  tube  was  required  in  the  trunk  main. 
The  branch  mains  consisted  of  nominal  1/2  in.  tube  while  the  radiator 
runouts  and  risers  were  either  3/8  in.  or  l/U   in.  tube,  depending  on  the 
capacity  of  the  room  heating  unit  and  the  length  of  the  piping  connections. 
Sweat  fittings  were  used  throughout  the  system. 

While  the  tube  used  in  this  system  was  smaller  than  that  ordinarily 
used,  it  should  be  pointed  out  that,  at  the  design  water  flow  rate  of  \» 3 
Gpm,  the  maximum  water  velocity  in  the  system  would  be  3  ft.  per  sec.  This 
velocity  is  low  enough  that  there  would  be  no  danger  of  noise  resulting 
from  the  water  flow. 

Table  B  shows  the  estimated  installation  costs  for  both  a  conventional 
one-pipe  and  the  small  pipe  heating  system  for  a  new  six-room,  two-story 
house  similar  to  the  I=B=R  Research  Home,  Estimated  installation  time  was 
based  on  experience  gained  from  the  installation  of  such  systems  in  the 
Research  Home.  The  total  cost  of  materials  in  the  conventional  iron-pipe 
system  was  $104.. 25  as  compared  to  $87.73  for  the  small  pipe  system.   Labor 
costs  for  the  conventional,  and  the  small  pipe  systems  were  $220.50  and  $84.00 
respectively.  These  estimates  cover  only  the  costs  of  pipe,  fittings,  and 
the  time  required  to  install  the  piping  system.   They  do  not  include  the 
cost  of  the  boiler  and  radiation  nor  the  time  required  to  install  these 
items  except  for  connecting  the  piping  system  to  them.  The  total  cost  of 
installing  the  piping  system  for  the  small  pipe  system  was  approximately 
$150.00  less  than  the  installation  cost  of  the  more  conventional  piping 
system. 

Installation  Procedure 

The  real  advantage  of  using  small  diameter,  soft  copper  tubing  for  the 
piping  system  was  in  the  ease  and  speed  of  installation.   The  following 
procedure  was  followed  in  installing  the  experimental  system  in  the  I=B=R 
Research  Home=  The  radiation  in  this  system  consisted  of  cast  iron  base- 
board.  Undoubtedly  a  detailed  study  of  installation  procedures  could 
result  in  some  further  short  cuts,  but  even  so,  the  procedure  listed  below 
resulted  in  a  saving  of  about  4.0  man  hours  as  compared  to  that  required  to 
install  the  same  system  using  the  larger  size  of  iron  pipe  usually  employed 
in  systems  such  as  this  one. 

Step  1.   Assemble  baseboard  heating  units  and  locate  in  rooms  where  they 
are  to  be  installed. 
Two  men  required „ 

Step  2.   Cut  necessary  holes  for  risers. 
One  man  required. 

Step  3«  Rough  in  risers. 

Two  men  required.   Risers  to  second  story  units  were  pushed 
down  through  the  stud  spaces  in  the  walls  from  the  room  to 
the  basement.  Risers  for  first  story  units  were  run  through 
floor  to  basement,   Sufficient  tube  was  left  on  both  base- 
ment and  room  ends  of  the  risers  to  make  connections  to  the 
main  and  the  baseboard.   Prior  to  pushing  the  tube  through 
the  stud  space,  the  end  of  the  tube  was  crimped  with  a  pair 
of  pilars  to  prevent  insulation  or  dirt  from  entering  the  tube. 


After  both  risers  are  soldered  into  the  adaptors  at  the  ends 
of  the  heating  unit,  the  unit  is  pushed  back  into  place  along 
the  wall.  Surplus  riser  slips  through  stud  space  to  basement. 


After  installation  of  room  heating  units  is  completed 
the  basement  ends  of  the  risers  are  cut  to  length  and 
soldered  into  the  tees  in  the  main.  As  the  connection 
to  the  tee  is  completed,  the  main  is  fastened  into  place 
following  the  chalk  line  indicating  its  proper  location. 


•3- 


Step  U>      Connect  risers  to  room  heating  units. 

One  man  required.   The  baseboard  unit  was  laid  on  the  floor 
just  in  front  of  the  wall  along  which  it  was  to  be  located 
and  iron  to  copper  adaptors  were  screwed  into  the  ends. 
Following  this  the  unit  was  placed  in  an  upright  position 
a  few  inches  from  the  wall.  Fireproof  insulating  board  was 
placed  under  the  end  of  the  unit  to  protect  the  floor* 
The  end  of  the  riser  was  cut  and  cleaned  and  sweat  into 
the  fitting  at  the  end  of  the  heating  unit. 

Step  5.   Locate  unit  against  wall. 

Two  men  required.   After  soldering  the  risers  to  the  heating 
unit,  the  heating  unit  was  pushed  back  into  place  along  the 
wall.   The  extra  length  of  the  riser  required  to  reach 
the  heating  unit  when  in  position  for  sweating  was  pushed 
back  into  the  stud  space  for  second  story  units  and  through 
the  floor  into  the  basement  for  first  story  units. 

Step  6.  Indicate  position  of  basement  heating  main  by  chalk  line 
across  the  bottom  of  the  studs. 
Two  men  required. 

Step  7.   Connect  main  to  the  boiler. 

One  man  required.  Work  can  start  at  either  the  supply  or 
return  connection  to  the  boiler.  If  two  men  are  working, 
one  can  start  at  the  boiler  supply  and  the  other  at  the 
return . 

Step  8.  Run  mains. 

One  man  required.   One  end  of  tubing  was  cleaned  and 
sweat  to  the  fitting  at  the  boiler  supply <>   Tubing  was 
bent  as  required  to  follow  the  position  indicated  by  the 
chalk  line.   Tube  was  fastened  to  bottom  of  joists  with 
staples  or  straps  as  work  progressed.  Fasteners  were 
located  about  3  ft.  apart  and  care  was  taken  to  see  that 
they  were  not  tjght  on  the  tube.  This  permitted  freedom  of 
movement  without  causing  expansion  and  contraction  noises. 
Tubing  was  cut  to  length  where  tees  were  required  and  fit- 
tings were  sweat  into  place  before  the  tube  was  fastened 
to  the  bottom  of  the  joists.   The  bottom  end  of  radiator 
risers  were  cut  to  length  and  soldered  to  the  main  in  turn. 
The  orifice  was  inserted  in  all  supply  tees  in  the  position 
indicated  in  Fig.  2.   The  tubing  held  the  washer  in  place. 

If  two  men  were  working,  they  started  at  opposite  ends  of 
the  main  and  worked  toward  each  other,  (if  there  are  two 
or  more  circuits,  they  may  work  on  separate  circuits.) 

Performance  of  small  pipe  system 

Performance  of  the  small  pipe  system  was  observed  in  the  I=B=R  Research 
Home  throughout  the  winter  of  1958-59.   This  was  one  of  the  most  severe 
winters  in  Urbana,  Illinois,  in  recent  years .  Minimum  temperatures  were 
as  low  as  -9  F  and  these  were  accompanied  by  average  wind  speeds  of  about 
10  miles  per  hour  with  gusts  up  to  about  30  miles  per  hour.  All  through  the 
winter  the  operation  of  the  small  pipe  system  was  satisfactory  in  all 


-k- 


respects.   No  difficulty  was  experienced  in  maintaining  the  desired  room 
air  temperatures  even  during  the  coldest  and  most  incliment  weather .  Floor 
to  ceiling  air  temperature  differences  were  the  same  as  those  obtained  in 
previous  years  when  testing  baseboard  heating  systems  having  conventional 
one-pipe  piping  systems. 

Because  of  restrictions  on  the  use  of  gas,  it  was  necessary  to  use  oil 
as  the  fuel  during  the  tests  on  the  small  pipe  system ,   No  other  base- 
board heating  system  has  ever  been  tested  in  the  Research  Home  using  fuel 
oilj  however,  the  oil  consumption  obtained  with  the  small  pipe  system  in 
1958-59  compared  favorably  with  that  obtained  with  the  first  heating 
systems  ever  installed  in  the  Research  Home.   These  early  systems  were 
oil  fired  and  used  small  tube  radiators. 

According  to  the  design  assumptions  the  rate  of  water  circulation 
through  the  trunk  main  should  have  been  4<=3  Gpm.   By  actual  measurement 
it  was  found  to  be  about  5>8  Gpm.   No  actual  measurement  was  made  of  the 
pump  head  developed ,   The  high  measured  water  flow  rate  indicated  that 
either  the  pump  head  was  well  above  the  catalogued  value  or  else  the  total 
resistance  of  the  piping  system  was  less  than  assumed 0   It  is  probable  that 
the  latter  was  the  principal  factor  for  the  following  reasons;   (l)  a 
large  section  of  the  return  trunk  of  the  small  pipe  system  was  not  changed 
from  the  1  inch  iron  pipe  used  in  previous  systems o   This  was  left  in  as 
it  contained  the  flow  measuring  station.-   (2)  the  required  water  flow  rate 
in  some  sections  of  the  piping  was  less  than  the  maximum  carrying  capacity 
and  (3)  in  estimating  the  pipe  resistance  no  allowance  was  made  for  the 
fact  that  the  actual  flow  rate  through  the  parts  of  the  main  located 
between  each  pair  of  risers  was  at  a  reduced  rate  due  to  diversion  of  part 
of  the  water  through  the  radiator  circuit,   The  calculated  friction  pressure 
loss  through  the  main  obtained  by  substituting  1  in.-  iron  pipe  for  3/4-  in. 
copper  tube  in  the  trunk  and  using  the  observed  flow  rate  of  5°8  Gpm  is 
20  ft  of  water =   Since  this  is  a  greater  friction  pressure  loss  than  that 
obtained  by  using  the  tube  sizes  and  flow  rates  indicated  in  Table  A,  it 
is  apparent  that  the  pipe  sizing  procedures  for  the  small  pipe  system 
were  on  the  safe  side.-   Furthermore,,  since  the  calculated  friction  head  for 
actual  conditions  of  operation  exceeded  the  catalogued  pump  head  by  6  ft 
of  water,  it  seems  probable  that  the  allowance  for  fittings  and  orifices 
was  more  than  actually  required .- 

Table  C  shows  the  measured  temperature  drops  in  all  parts  of  the 
heating  system:   ''Tith  the  exception  of  the  drop  through  the  dining  room 
baseboard,  all  were  less  than  the  design  value  of  20  F  which  should  be 
expected  since  the  actual  water  flow  rate  exceeded  the  design  value 0   There 
were  two  factors  contributing  to  the  high  temperature  drop  through  the 
dining  room  baseboard;   In  the  first  place  the  3/8"  tube  used  in  the 
radiator  circuit  was  slightly  undersized,   As  shown  in  Table  A  the  allowable 
friction  head  in  this  circuit  was  745  milinches  per  foot  while  the  friction 
head  in  a  3/8  in.  tube  carrying  0.87  Gpm  is  762  milinches  per  foot.   In 
addition  to  this  the  main  circuit  to  which  this  unit  was  connected  was 
slightly  overloaded  and  furthermore  the  supply  tee  and  orifice  for  the 
dining  room  baseboard  were  located  just  downstream  of  the  supply  tee  for 
the  S.  V.  bedroom  baseboard ,      All  of  these  tended  to  reduce  the  flow 
through  the  dining  room  baseboard .  A  high  temperature  drop  through  a 
room  heating  unit  is  not  as  serious  as  it  appears  since  the  mean  radiator 
temperature  is  decreased  only  one  half  as  much  as  the  temperature  drop 
is  increased  and  the  decrease  in  output  of  the  heating  unit  is  only  about 
0.9  percent  per  degree  Fc   If  it  is  assumed  that  changes  in  water  flow 


rate  have  a  negligible  effect  on  the  output  of  a  baseboard,  the  following 
equation  is  true. 


where 


AT  x  W  =  C 

AT  =  Temperature  drop  through  the  baseboard 

W  =  Water  flow  rate  through  the  baseboard 

C  =  a  constant 

The  water  flow  rates  through  the  individual  baseboard  circuits  were  not  meas- 
ured.  Nevertheless  it  is  true  that  the  ratio  of  the  water  flow  rate  through 
the  radiator  circuit  to  the  water  flow  rate  through  the  main  is  a  constant 
and  therefore,  by  changing  the  value  of  C  in  the  preceeding  equation  the 
water  flow  rate  in  the  main  may  be  substituted  for  the  flow  rate  through 
the  radiator.   In  this  way  it  may  be  shown  that  reducing  the  water  flow 
rate  in  the  system  from  5.8  Gpm  to  4.. 5  Gpm  would  increase  the  average 
temperature  drop  through  the  heating  units  to  about  20  F,  the  design 
value.  This  indicates  that  the  sizing  of  the  orifices  in  the  supply  tees 
and  the  method  of  sizing  the  piping  for  the  radiator  branch  circuits  was 
satisfactory. 

When  the  system  was  first  started,  a  few  expansion  and  contraction 
noises  in  the  piping  system  were  observed.  These  were  traced  to  pipe  straps 
which  were  too  tight  to  permit  movement  of  the  main.  These  were  loosened 
and  from  that  time  on  no  noise  in  the  piping  system  was  observed,  either 
as  a  result  of  expansion  and  contraction  or  from  high  water  velocity. 

No  unusual  venting  problems  were  encountered  even  though  there  were 
places  in  the  piping  system  where  air  could  be  trapped.   The  water  velocity 
was  apparently  sufficient  to  carry  the  air  along  with  the  water  until  it 
reached  either  the  boiler  or  the  radiation  where  the  water  velocity  was 
low  enough  to  permit  separations 

Summary 

The  use  of  small  diameter,  soft,  copper  tube  for  the  construction  of  an 
experimental  one-pipe  hot-water  system  for  the  I=B=R  Research  Home  resulted 
in  a  reduction  of  about  -$150.00  in  the  installation  cost  with  no  sacrifice 
in  the  overall  performance  of  the  system.  The  design  procedures  used 
proved  to  be  on  the  conservative  side  and  may  be  incorporated  in  the  I=B=R 
Installation  Guides  without  introducing  an  entirely  new  method  of  design. 
All  that  would  be  required  is  an  expansion  of  the  pipe  sizing  table  and 
some  comments  on  the  installation  techniques  of  installing  the  small 
diameter  pipe  efficiently. 


Appendix  A, 


Revisions  Required  in  Installation  Guide  500  to  Make  It  Adaptable 

To  Small  Pipe  Systems 

A  revision  of  the  pipe  sizing  table  (Table  3)  in  I=B=R  Installation 
Guide  No,  500  is  required  to  make  this  guide  applicable  to  the  design  of 
small  pipe  systems o  A  suggested  revision  is  shown  in  Table  D.  This  table 
is  applicable  to  copper  tube  only  as  the  friction  heads  of  copper  tube  and 
iron  pipe  are  quite  different  for  the  same  nominal  size  in  the  smaller 
diameters* 

The  carrying  capacities  of  the  radiator  circuits  in  Table  D  are  based 
on  the  use  of  an  orifice  as  illustrated  in  Fig0  2;  or  other  suitable 
device  which  will  develop  a  pressure  head  in  the  radiator  circuit  equi- 
valent to  the  friction  head  in  approximately  12  ftc  of  the  main  to  which 
the  radiator  circuit  is  joined . 

Table  E  summarizes  the  pipe  size  selection  for  the  system  installed 
in  the  I=B=R  Research  Home  using  Table  D  and  the  procedure  described 
on  pages  23  through  25  of  I=B=R  Installation  Guide  No»  500„  Comparing 
the  pipe  sizes  shown  in  Table  E  with  those  in  Table  A  it  is  found  that  the 
use  of  Table  D  and  the  simplified  procedure  resulted  in  the  same  pipe  size 
selection  as  the  more  exact  method  of  using  the  equivalent  length  of  each 
circuit  (Table  A) »  The  dining  room  riser  size  in  Table  E  is  l/2  in.  while 
in  Table  A  it  is  only  3/8  in,  However  it  should  be  noted  that  the  3/8  in* 
tube  was  actually  undersized . 

It  is  also  suggested  that  some  description  of  installation  methods  for 
small  diameter  soft  copper  tube  should  be  included  in  the  revisions  as 
these  procedures  are  not  familiar  to  most  contractors » 


-7- 

Appendix  B 

Method  of  developing  pipe  sizing  table,  Table  D 

Step  1.  Select  a  unit  friction  heado 

Example:  Unit  friction  head  taken  as  600  milinches  per  ft, 
(this  represents  the  third  column  in  Table  D) 

Step  2.  For  each  available  head,  determine  the  equivalent  length  of  the 
circuit  by  dividing  the  available  head  in  milinches  by  the 
unit  friction  head  selected  in  step  1. 

Example:  Available  head  =  8  ft  of  water 

Equivalent  length  s  8  x  12000/600  -  160  Ft. 

Step  3.  For  each  equivalent  lengthy  determine  the  measured  length  from 

table  F.   Round  out  measured  length  to  nearest  10  ft.  and  record 
in  upper  portion  of  Table  D  under  total  length  of  circuit. 
Examples  160/1,63  =  98  fto  Record  100  ft. 

Step  U»     For  selected  unit  friction  head  (Step  l),  determine  the  carrying 
capacity  of  main  sizes  from  an  accepted  friction  pressure  loss 
chart.  Record  to  nearest  0,1  Gpm  opposite  trunk  or  circuit  in  Table  D 
Example:   Unit  friction  head  =  600  milinches  per  ft. 

Carrying  capacity  3/4-  in.  type  L  copper  tube  = 
4,0  Gpm, 

Step  5.  Multiply  the  selected  unit  friction  head  (step  l)  by  15  to  determine 
the  available  head  to  overcome  friction  in  the  branches. 
Example: 600  x  15  =  9000  milinches 

Step  6,  Assume  the  equivalent  length  of  the  branch  to  be  30  ft.  This  was 
the  average  equivalent  length  of  a  branch  circuit  in  the  I=B=R 
Research  Home, 

Step  7  o  Divide  the  available  h^ad  determined  in  Step  5  by  the  equivalent 
length  of  the  branch  (Step  6), 

Example:  9000/30  =  300  milinches  per  ft. 

Step  8.  For  each  unit  friction  head  in  branch  (Step  7)  determine  the 
carrying  capacity  of  each  branch  size  from  accepted  friction 
pressure  loss  charts.  Record  to  nearest  0.1  Gpm  in  Table  D, 
Examples   Unit  friction  head  =  300  milinches  per  ft. 

Carrying  capacity  3/8  in  type  L  copper  tube  =  0,5 
Gpm, 


Appendix  C 
Determination  of  Orifice  Size 


The  size  of  the  orifice  required  to  increase  the  equivalent  length  of  the 
main  by  12  ft.  may  be  determined  by  the  following  formula. 


Q  =  KA*/2gh   or   A  =  Q/K  ^'2gh 


where 


Q  =  Flow  rate  in  cu,  ft,  per  sec, 

A  =  Orifice  area  in  sq.  ftc 

K  =  Orifice  coefficient  (assumed  as  0.65) 

g  =  Gravitational  acceleration,  ft.  per  sec^  (32.2) 

h  =  Head  Loss  through  orifice  in  ft.  of  water 

It  is  apparent  that  the  area  of  the  orifice  is  a  function  of  the  flow 
rate.  However,  the  changes  in  flow  rate  normally  encountered  in  any  main 
of  a  given  size  in  a  conventional  heating  system  are  not  large  enough  to 
have  much  effect  on  the  orifice  size. 

Sample  calcula t  i  on : 

Main  size  =  l/2  in. 
Flow  rate  =1.0  Gpm 

Unit  pressure  loss  in  main  =  330  milinches  per  ft, 
(from  friction  pressure  loss  chart) 

h  =  12  x  330/12000  =  0,33  ft.  of  water 


A  =  1.0/450  x  1/0.65  x  1//6TT4  x  0.33  =  0,000738  sq.  ft.  or 

^^^        0,106  sq,  in, 
Diameter  of  orifice  =  */0o  106/0, 786  =  0.384  in. 

Using  the  above  procedure  and  selecting  flow  rates  corresponding  to 
representative  carrying  capacities  of  the  main  the  following  orifice 
diameters  were  found  to  be  required  to  increase  the  equivalent  length  of 
the  main  by  approximately  12  ft. 


Main  size  Orifice  diam 

in.  in, 

3/8  0,27 

1/2  0,38  (13/32  or  0,41  in,  was  used  in  the 

installation  in  the  I=B=R  Research 
Home) 


3/4  0.61 


(h 

U 

1 

c 

+3 

+» 

o 

f-.    cO 

^  <jj 

•H 

O  De 

o^ 

Xi  -P 

T3 

O    O 

iooo      o 

O  en 

o  o      o 

O    «M 

<3 

G    CD 

1  m  mvO        ^4 

o  o 

O  s£>          O 

cS  ° 

9 

•H  CO 

!ff\NCf\        vO 

N0 

X 

H 

i    •»    *    ««          • 

*-P 

•»       »                 •         «t  4J 

•H    (3 

mo  «h      \d 

CTNtx, 

^rv-4       H 

rH  tn 

c 

S  -H 

en  CM  so        injt- 

ITv  nO        6-  0s 

5 

• 

H  c> 

4» 

X!     • 
o  +s 

■-     • 

O 

C     &H 

~                          H 

•H 

•H 

o  o  o      o 

O  e-  CM  O  t>-  m 
\0  t-  CV  vO  t-  O 

o  o      o 

OOMvOiA^ 

h 

H    fc 

w  m  to        CO 

«TN  O          O 

\OvOvO  -4tOvO 

En 

•H    CD 

t-  t-  rH          t-i 

P\W(\   CNCNin 

C~-pH         H 

fr\  cr\  t-  C^  -s4  CM 

s  a 

H         rH 

H        H 

« 

<D   X! 

'3   W) 

1 

>   C 

e--  e-  CM        toK* 

vO          vO   -4  m  m 

<n      nHtvn 

-4->t       O 

to 

»T\         tO  CM  CM  O 

1$ 

-4-  CM  m       ~4|c-- 

IrH 

t>-  in       \0 

to 

H 

cr\         HntVst 

cr 

W 

•o 

CD  Xi 

y  w 

1 

1 

to  c 

e-  O  e-           |cn 

t^       0s  t~-  to  to 

vO  0^           Ikn 

vO          r^  m  »n  CT\ 

ed    m 

H  en               IvO 

CM         CM         H  CM 

CM  Cf\             Js£) 

CM         H(\ir|C> 

«Q 

+> 

G  Cm 

CD    O 

5j  <H 

O    CO     •    © 
X»    >  *>  X> 

~                   1 

iH  -H  fe    3 

O  tO  m        tOIrH 

O^       e—  e^  t-  t— 

to  U>       O 

cn 

O       c~-  e^  e«-  c~- 

W    ^    ZEh 

-4         rH          -sHrH 

sfH        v£) 

CM 

cr  c 

liH 

rH 

W  -H 

I                           CO     CO 

•P    UD 

c  c 

CD  «H 

«ih    >  rH  4* 

o  o  d  -p 

X)     >    T\ 

o  -^O 

O       t^  t«-  t>-  c~- 

-40 

qn       e^  t-  e^  t>- 

•  H   iH  &h 

CM         iH 

CM  H 

£W    3 

&              CTCl-l 

w  o 

S 

■P     • 

U   «H    O 

O    O    © 

4»OB 

O  O  O         O 

»r\  CM  O  (^  CM  O 

O  H 

»f\  cr,  o  rH  c*>  O 

ct)  rH\ 

•     •     •            • 

•      ••••• 

•     • 

•    ••••• 

*££ 

en  en  en       en 

iH  iH  H  H  iH  O 

C^  Cn 

rH  rH  H  H  H  O 

* 

^ 

* 
CM  CO  tO  «0  tO  pH 

^f,CM 

CM  tO  ^0V<S*^ 

C    CD    CD 

-H      rU        N 

<^<*«^ 

www 

x.  X. 

N.>v    x^^v  NwV^ 

H  C^  <r\  C^\  c^n  r^> 

<r\H 

r4  C^S  C*\  i-4  r*  r4 

a  s  -h 

CN  en  rH 

•      • 

•     • 

OH  w 

Q,  43 

P.-P 

s 

^    CD 

co  cd 

^    CD 

_  co  cd 

>  ®  « 

N  W  C\         en 

CM  O  -«*  e-  to  »rv 

CM  O 

CM  en  t-vO  rH  CM 
o  m  to  cm  en  cm 

O  -P  2 
rH    CO  K 

en  en  iH         H 

c^  pH 

•     •     •           • 

•     ••••• 

•     • 

•     ••••• 

fe  tt5  o 

-4  ^*  CM         CM 

rH 

-4  CM 

t-i 

-P 

3  X>    O   *     X! 

e    CO  "H  TJ    O 

•h  a  +3  co  c 

X    O    CJ    CD  «H 

vOvOvO         n£> 

c<^        PMftO  sf 

->*  vr       ^ 

en       m  O  0>  in 

to       >*H  o  en 

\p  \D  <X>         vO 
0^  t>  0s        0s 

o  O       O 

>*        -4-  O  if\  -^ 

to  to      to 

en       e—  ~4  ^O  en 

CO 

CO 

CD    CD 

•          • 

CD    CD 

• 

CD    O 

ts     tj  e 

CD    O 

tj      a 

H   <*H 

CD           CD    O 

•H         t-t  ri 

©        9 
m       o 

c? 

<m 

cd      no 

X!                <H 

o  f-i 

t^-H 

pcj 

T3           >»«H 

rt        •   • 

-P       • 

oil 

T3    G.O  '3 

•         •          • 

I*       w    •  -P    • 

rH    h  rH 

+  -o    p,0    cO 

•                  X!   u 
>             •  Xi    O  -H 

•H    O    &,         -p 

>    CO    > 

CD    (X        -P 

a  4»  43    CO 

o>  r4 

CO  XI  U3    3  <*    O 

•            •  «H    CD    Cfl 

to      &  ^  ^:  j 

<D<h    34    O 

•          «H    CO  nH  43 

wc 

1-3  »o    CO  CO 

H 

»-s    CO  CO 

EH 

CO         Q  00  «  CO 

o 


4> 


•d 

-o 

cd 

CD 

CD 

H 

w 

9 

A 

4> 

to 

1 

a 

Pm 

M 

Q> 

H 

• 

43 

c 

cO 

•H 

rH 

•H 

N* 

CO 

V 

> 

H 

< 

* 

* 

* 

TABLE  B. 

ESTIMATED  INSTALLATION  COSTS  -  NEW  CONSTRUCTION 
Conventional  Iron  Pipe  vs  Small  Diameter  Copper  Tube 


Conventional  iron 
pipe  system 


Small  diameter  copper 
tube  system 


Item 


Quantity 


Cost    Quantity 


Cost 


Pipe  or  Tube 

341  Ft0 

$47.90 

323  Ft. 

$64.26 

Fittings 

159 

56o35 

85 

23.47 

Labor 
$3.50  per  hour 

63  Hr. 

220.50 

24  Hr.* 

84.00 

Total 


$324.75 


$171.73 


*  =  Estimated  for  new  construction  by  installer 
of  system  in  I=B=R  Research  Home 


TABLE  Co 


WATER  TEMPERATURE  DROPS,  SMALL  PIPE  SYSTEM 


Location 

Temp. 
Drop  F 

Location 

Temp. 
Drop,  F 

Kitch.  Rad. 

18.3 

Bath  Rad. 

13.5 

Din.  Baseboard 

25.6 

S0W0Bed.Basebd.l7.2 

Liv. 

10o2 

N.W.  " 

14.3 

Vest.  Rad. 

5.3 

N.Eo  " 

12.0 

Lav. 

17.6 

Av 

.  all  heating 
units 

15.0 

Stair.  " 


15.8 


Boiler 


16.4* 


*  temperature  rise 


O 

o 

o 

O 

o 

O 

• 

• 

* 

• 

CM 

• 

• 

-* 

H 

• 

• 

r-i 

st 

i-i 

• 

• 

C*\ 
sO 

CM 
i-i 
rH 

to 
cm 

rH 

3 

rH 

• 
• 
• 

• 
• 
• 

• 
• 
• 

• 
• 
• 

O 

O 

O 

H 

O 

O 

• 

O 

o 

o 

O 

O 

O 

o 

O 

O 

• 

fr, 

H 

• 

in 

CM 

i-i 

• 

pTi 

in 

CM 

H 

cm 

st 

m 
to 

* 

H 

to 

rH 
H 

to 

CM 
i-i 

• 
• 
• 

• 

o 

O 

• 

• 
o 

• 
O 

• 
O 

• 

• 

rH 

• 
o 

O 

• 

O 

• 
• 

o 

O 

o 

O 

o 

O 

O 

O 

O 

o 

C^l 

rH 

• 

vO 

CM 

rH 

• 

vO 

vO 

CM 

H 

CO 
CM 

tr\ 

in 

-St 
m 

CM 
vO 

rH 

to 
to 

* 

CM 
i-i 
i-i 

• 

o 

• 
O 

• 

• 

o 

• 
O 

• 
O 

• 

• 

r-i 

• 

o 

• 

o 

O 

• 

o 

o 

Q 

o 

O 

O 

o 

O 

o 

O 

o 

r-i 

• 

t— 

CM 

r-i 

• 

to 

NO 

CM 

r-i 

cm 

to 

m 

cm 

rr> 

m 

CM 

(T« 

vO 

C_) 

cm 

cm 

o. 

st 

st 

in 

vO 

vO 

e^ 

cr 

O 

o 

u 

o 

(_) 

o 

i-i 

o 

o 

O 

o 

o 

O 

a 

o 

o 

o 

O 

O 

o 

st 

I-i 

• 

e- 

<r\ 

I-i 

■ 

O 

t-- 

c^v 

i-i 

• 

c\ 

to 

•<t 

o 

VT\ 

rH 

C-- 

CM 

•st 

z 

i-i 

o 

cm 

CM 

C?\ 

-st 

st 

m 

ITi 

vD 

C-- 

O 

c_> 

o 

o 

o 

CM 

o 

O 

O 

o 

O 

O 

o 

o 

O 

o 

O 

o 

st 

rH 

• 

to 

C^l 

rH 

• 

CM 

to 

r<\ 

i-i 

• 

H 

m 

i-i 

£ 

CM 

to 

CM 

c*> 

to 

st 

to 
-** 

CM 

CM 

EH 

• 

o 

• 

o 

• 

• 

o 

• 
o 

• 

o 

• 

• 
CM 

• 

o 

• 
O 

• 

o 
I-i 

• 

o 

o 

o 

o 

O 

o 

O 

o 

o 

O 

in 

rH 

• 

o 

«r\ 

r-i 

• 

(^\ 

to 

C"\ 

• 
-P 
o 
c 

r-i 

rH 

c_> 
cm 

sr 

to 

CM 

CM 
rr, 

0^ 

^ 

•<t 

St 

in 

O 

Pi 

M 

• 
o 

• 

o 

• 

• 

o 

• 
o 

• 

o 

• 
CM 

o 

O 

• 

o 

O 

o 

o 

o 

O 

o 

O 

o 

O 

o 

in 

CM 

i-i 

o 

tr> 

CM 

H 

in 

t> 

c\ 

CM 

iH 

CD 

cd 
m 

3 

to 

rH 

CM 

in 

CM 

to 

CM 

CM 

0^ 

CTN 

■st 

g 

• 
O 

• 

o 

9 

o 

• 

o 

• 
o 

• 
O 

• 

o 

• 

CM 

• 

o 

O 
■st 

O 
CM 

• 

o 

rH 

O 

o 

O 

O 

O 

O 

O 

o 

o 

O 

in 

CM 

rH 

o 

-4 

CM 

rH 

v£> 

o 

Eh 
M 

ED 

O 
i-i 

rH 

rH 

3 

CM 
CM 

in 
CM 

to 

CM 

CM 
■st 

ti 

• 
o 

• 
O 

• 

o 

• 

o 

• 

o 

• 
O 

• 
O 

CM 

• 

o 

O 
st 

O 
CM 

• 
O 

H 

O 

O 

O 

o 

O 

O 

O 

O 

O 

O 

in 

CM 

r-i 

o 

■st 

CM 

r-i 

to 

o 

O 

o 

3 

4 

rH 

Jm 

m 
CM 

to 

CM 

r-i 

c*> 

n 

• 
o 

• 
O 

• 

o 

• 

• 

o 

O 

• 

O 

CM 

• 

r-i 

• 

O 

O 

• 
O 

o 

O 

o 

O 

O 

8 

CM 

O 

O 

O 

o 

\D 

CM 

r-i 

I-i 

st 

CM 

H 

O 

r-i 

st 

CM 

H 

b 

EC 
Eh 

to 

o 
f-l 

H 

m 
rH 

to 

i-i 

en 
CM 

CM 

to 

CM 

st 

H 
M 
O 

• 

o 

• 

o 

• 

O 

• 

I-i 

• 

o 

• 
O 

* 

O 

• 

i-i 

• 
O 

O 

• 
O 

m 

m 

O 

O 

O 

O 

O 

O 

O 

o 

vO 

CM 

r-i 

CM 

st 

CM 

rH 

rH 

i-i 

st 

CM 

rH 

f- 

O 

CM 
H 

* 

vO 
H 

to 

H 

rH 
CM 

CM 

IT\ 
CM 

I-i 

g 

• 

o 

o 

• 

O 

• 
i-i 

• 

o 

O 

• 

O 

• 
<■•> 

• 
r-i 

O 

• 
O 

• 
O 

9 

o 

o 

O 

o 

O 

O 

O 

o 

O 

o 

vO 

CM 

r-i 

CM 

st 

CM 

rH 

CM 

r-i 

st 

CM 

r-i 

j 

c^ 

o^ 

rH 

c\ 

in 

C-- 

(T> 

rH 

<TN 

to 

w 

• 

• 

• 

• 

• 

• 

• 

** 

i-i 

H 

r-{ 

H 

H 

CM 

CM 

CM 

o 

o 

o 

rH 

(_) 

O 

O 

r> 

i-i 

O 

O 

o 

s 

g 

m 

o 

O 

O 

O 

O 

O 

O 

O 

O 

rH 

S0 

CM 

r-i 

CM 

st 

CM 

rH 

st 

CM 

st 

CM 

r-i 

NO 

to 

O 
H 

CM 
H 

3 

m 

rH 

to 

H 

O 

CM 

CM 
(M 

CM 

s 

1 

O 

• 

o 

• 
O 

• 

• 

O 

• 
O 

• 
O 

• 

• 

H 

• 

O 

• 

O 

• 
O 

O 

o 

O 

O 

o 

O 

O 

O 

O 

O 

t^ 

CM 

r-i 

CA 

in 

CM 

r-l 

in 

CM 

in 

CM 

rH 

vO 

e^ 

O 

H 

r-l 

3 

to 

rH 

o 

CM 

st 
CM 

o 

• 

o 

O 

• 

o 

• 

I-i 

• 
o 

• 
O 

O 

• 
c*\ 

• 
rH 

• 
O 

• 
O 

• 

O 

m 

m 

o 

O 

O 

O 

o 

o 

O 

O 

fc- 

CM 

H 

■st 

in 

CM 

r-i 

t- 

C<N 

in 

CM 

rH 

m 

v£> 

to 

O 
rH 

t-i 
r-i 

r-i 

rt 

r-i 

to 

rH 

i-i 
CM 

1-4 

• 

o 

• 

O 

• 
O 

• 
rH 

O 

• 

o 

• 
O 

• 

• 
r-l 

• 
o 

O 

• 

O 

o 

O 

o 

O 

O 

O 

o 

O 

O 

O 

to 

CM 

i-i 

st 

in 

CM 

r-i 

O 

St 

in 

CM 

rH 

m 

v£> 

c^ 

to 

O 
H 

r-i 
rH 

CM 

4 

rH 

• 

o 

• 

O 

• 

o 

• 

rH 

• 
o 

O 

• 

O 

• 

st 

• 
r-i 

• 
O 

O 

• 

O 

o 

O 

o 

O 

O 

O 

O 

o 

O 

O 

o 

r*\. 

CM 

C*- 

vO 

c\ 

CM 

sO 

vO 

sO 

e> 

CM 

st 

VTN 

vO 

e- 

to 

O 

O 

r-i 

CM 

3 

• 

o 

• 
O 

• 

o 

• 
rH 

• 

o 

• 

o 

• 
O 

• 

st 

• 

rH 

• 

o 

• 
O 

O 

o 

m 

o 

o 

V\ 

m 

o 

O 

IT\ 

ir\ 

o 

r^ 

CM 

O 

t- 

<r\ 

CM 

CM 

to 

e- 

c> 

CM 

ca 

C\ 

st 

m 

m 

vO 

C-- 

to 

to 

o 

rH 

• 

I-i 

• 
o 

• 

o 

• 

CM 

• 

o 

• 

o 

• 
O 

in 

r-i 

• 
o 

O 

O 

lable 
d  in 
f  Water 

ja 

Si 

Si 

CO 

£. 

o 

si 

Si 

o 

S3 

Si 

S3 

o 

CD 

r^     "t3 

O 

c 

M  -P 

o 

u 

M  -p 

O 

u 

o 

c 

H 

•H 

3  p« 

c 

3  0 

§ 

c 
cd 

Q   *rl 
3     E» 

C 

cd 

c 

c 

cd 

to 
.fl 

st 

m 

vO 

e— 

to 

o 

o 

rH 

H 
H 

CM 

r-i 

4 

CO 

£Z 

M 

Eh    U 

C& 

£ 

CQ 

Eh    U 

to 

to 

to 

CO 

CD 

•H 

•H 

a)   a> 
>  EC     • 

Eh 

a. 

=    O 

; 

vO 

=     O 

£ 

£ 

vO 

s    o 

z 

s 

s 

vO 

■H 

to 

-st 

rH 

CM 

<o 

-st 

r-i 

-d- 

CM 

to 

-4- 

rH 

P-. 

^s  U 

^N 

•v 

^s  U 

•N. 

^s 

\ 

^>  fa 

\ 

> 

s 

> 

c\  o 

r-\ 

O^ 

r-i    O 

r^i 

rH 

C\ 

<r\  o 

t-i 

C^l 

I-I 

CN 

TABLE  E. 
PIPE  SIZE  SELECTION  USING  TABLE  D. 


Section 
(Fig.  1) 

Flow  Rate 
GPM 

Ja  +  dhi 

4.32 

abed 

2.13 

Totals 

N.  W.  Bed. 

1.02  Supply 
.45  Return 

N.  E.  Bed. 

•44 

Liv. 

.57 

Vest. 

.48 

Lav. 

.15 

Ja  +  dhi 

4.32 

a  f  e  d 

2.19 

Totals 

S.  W.  Bed. 

1.02  Supply 
.53  Return 

Din. 

.87 

Bath. 

.26 

Kitch. 

.31 

Stair. 

.22 

Measured 
Length ,  Ft . 

26 

JlL. 
63  +  48  =  111 


26 

65  +  60  =  125 


Pipe  Size 
(Table  D)* 


3/4 
1/2 

1/2 
3/8 

3/8 

3/8 

3/8 

3/16 

3/4 
l/2+ 

1/2 
3/8 

1/2 

1/4 

1/4 

1/4 


*  Available  Pump  Head  =  14  Ft.  of  Water 


TABLE  F. 

EQUIVALENT  VS  MEASURED  LENGTH 

Measured  =  (L) 
Lengths 

Ratio  of 
Equivalent  Length  =  (R) 
Measured  Length 

Equivalent 
Length 

50 

lo72 

86 

75 

lo67 

125 

100 

1.63 

163 

125 

1.59 

199 

150 

lc56 

234 

200 

1.50 

300 

250 

1.45 

363 

300 

1.41 

423 

350 

1.38 

483 

4.00 

lo35 

540 

450 

.   1.33 

599 

500 

1.31 

655 

600 

lo29 

774 

700 

1.27 

889 

800 

1.26 

1008 

Equivalent  Length  =  (R)(L) 


.C  © 
+>  o 

•H  -H 

©  Jb    © 

<D  O      © 


A 

V 

/  \   • 

\     \/ 

X 

CO 

8 

M 
H«0 

H  0s 


B2 

a 

to 


£ 


0 


I 

h 

in 

z 

h 

< 

X 


i 

co 

CD 


ID 
ID 
h 

> 

J 

Q. 
CL 
D 
(/} 

U. 

o 
J 

h 

111 

G 


k\\\\\\\y 
TT 


9  %o 


7,f    , 


^^? 


/ 


/ 


CM