Skip to main content

Full text of "Transformer practice : manufacture, assembling, connections, operation and testing"

See other formats


TRANSFORMER  PRACTICE 


TTII'I'lJIinillllllllllllUJIIIILlJJ 


VlkQraw-M  Bock  Qx  7m 

PUBLISHERS     OF     BOOKS     F  O  R^ 

Hectrical  World  "^  Engineering' News-Record 
Power  V  Engineering  and  Mining  Journal-Press 
Chemical  and  "Metallurgical  Engineering 
Electric  Railway  Journal  v  Coal  Age 
American  Machinist  "^  Ingenieria  Intemacional 
Electrical  Merchandising  -^  BusTransportation 
Journal  of  Electricity  and  Western  Industry 
Industrial  Engineer 


TKANSFORMER  PRACTICE 


MANUFACTURE,   ASSEMBLING,    CONNECTIONS, 
OPERATION  AND  TESTING 


BY 

WILLIAM  T.  TAYLOR,  F.R.G.S. 

FELLOW,    A.  I.  E.  E.,    M.  AM.  80C.  M.  E.,   M.  I.  E.  E.,   ETC. 


Second  Edition 

Entirely  Rewritten,  Enlarged  and  Reset 

Tenth  Impression 


McGRAW-HILL  BOOK  COMPANY,  Inc. 

NEW  YORK:    370  SEVENTH  AVENUE 

LONDON:    6  &  8  BOUVERIE  ST.,  E.  C.  4 

1913 


Copyright,  1909,  1913,  by  the 
McGraw-Hill  Book  Company,  Inc. 


PRINTED   IN  THE    UNITED   STATES    OF  AMERICA 


K»«   «      ••••''••• 


THE    MAPLE    PRESS    COMPANY,    YORK,    PA. 


PREFACE  TO  SECOND  EDITION 

The  writer  seeks  to  keep  this  book  practical  and  for  a  reference 
on  all  matters  connected  with  the  operation  of  transformers  and 
static  induction  apparatus.  It  is  particularly  intended  for  those 
who  are  operating  or  constructing  plants  or  transformers  and  is 
written  with  the  view  of  assisting  engineers  out  of  certain  operat- 
ing difficulties  which  they  can  readily  solve  when  they  are 
short  of  the  right  apparatus  and  need  a  temporary  arrange- 
ment such  as  using  certain  changes  of  phases. 

New  schemes  of  any  kind  will  be  appreciated  and  will  add  to 
the  value  of  this  book. 

William  T,  Taylor. 
Chaplanca,  Peru,  South  America, 
August,  1913. 


•  I 


\  'i.'» 


PREFACE  TO  FIRST  EDITION 

Although  much  has  been  written  on  the  fundamental  principles 
of  transformers,  little  data  have  been  published  concerning  their 
connection,  installation  and  operation.  It  was  this  lack  ot 
easily  available  information  and  the  widespread  desire  of 
operators  and  engineers  in  the  field  to  possess  such  information, 
that  led  the  author  to  put  in  type  these  notes,  which  had  been 
written  up  in  the  course  of  a  number  of  years  of  experience  in  the 
field. 

A  working  knowledge  of  the  fundamental  principles  of  electrical 
engineering  is  presupposed,  and  for  this  reason  the  treatment 
does  not  go  into  the  whys  and  wherefores  very  deeply,  but 
simply  states  the  facts  in  as  few  words  as  possible.  To  aid  in 
understanding  quickly  the  phase  relations  and  relative  values  of 
the  various  e.m.fs.  and  currents  involved  in  a  given  system, 
vector  diagrams  are  given  with  all  diagrams  of  circuit  connections. 

W.  T.  Taylor. 
Baramulla,  Kashmir,  India, 
December,  1908. 


VI 


I 


CONTENTS 

Page 

Preface    v 

Chapter 

I.     Introduction 1 

II.     Simple  Transformer  Manipulations 22 

III.  Two-phase  Transformer  Connections         30 

IV.  Three-phase  Transformation  System 39 

V.     Three-phase  Transformer  Difficulties 84 

VI.     Three-phase  Two-phase  Systems  and  Transformation    ....  97 

VII.     Six-phase  Transformation  and  Operation 109 

VIII.     Methods  of  Cooling  Transformers 117 

IX.     Construction,  Installation  and  Operation  of  Large  Transformers  136 

X.     Auto  Transformers 170 

XI.     Con.stant-current  Transformers  and  Operation 178 

XII.     Series  Transformers  and  Their  Operation 186 

XIII.     Regulators  and  Compensators 209 

XIV.     Transformer  Testing  in  Practice 227 

XV.     Transformer  Specifications 258 

Appendix 270 

Index  ....    273 


Vll 


TRANSFORMER  PRACTICE 

CHAPTER  I 
INTRODUCTION 

Development  of  Art  of  Transformer  Construction 

The  development  of  the  alternating-current  transformer  dates 
back  about  25  years.  At  that  time  very  little  was  known  re- 
garding design  for  operation  at  high  voltages,  and  the  engineer 
of  the  present  day  can  scarcely  realize  the  difficulties  encountered 
in  the  construction  of  the  early  transformers. 

The  high-voltage  transformer  made  long-distance  trans- 
mission work  possible,  and  the  increased  distances  of  transmission 
stimulated  the  design  of  large  transformers.  In  the  early  days 
of  transformer  development  as  many  as  15  to  20  transformer 
secondary  windings  have  been  connected  in  series  to  facilitate 
the  operation  of  a  long-distance  transmission  system,  the  maxi- 
mum rating  of  each  transformer  being  not  greater  than  10  kw. 
However,  a  method  of  constructing  large  transformers  has  long 
been  devised  by  which  an  enormous  amount  of  power  may  be 
transformed  in  a  single  unit.  Such  designs  embody  principles 
of  insulation  for  high  voltages  and  various  methods  for  maintain- 
ing a  low  operating  temperature.  Ten  years  ago  a  500-kilowatt 
unit  was  considered  to  be  a  large  size  of  transformer.  The 
history  of  ten  years'  development  has  shown  a  most  interesting 
process  of  evolution:  it  has  marked  more  than  a  tenfold  increase 
in  size  up  to  the  present  day. 

Going  back  to  part  of  the  history  of  transformer  manufacturing 
we  find  that  the  first  transformer  used  by  Faraday  in  his  historic 
experiments  had  for  their  magnetic  circuit  a  closed  ring  of  iron. 
Varley  in  the  year  1856  pointed  out  the  disadvantage  of  leaving 
the  magnetic  circuit  open,  gave  it  a  closed  path  by  bending  back 
and  overlapping  the  end  of  the  straight  iron  wire  core.  In  the 
early  days  of  electric  lighting  Ferranti  modified  Varley's  method 
by  using,  instead  of  iron  wires,  strips  of  sheet  iron  bent  back  and 
interlaced.     The  nearest  approach  to  the  present  day  practice 

1 


2  STATIONARY  TRANSFORMERS 

was  to  embed  link-shaped  coils  in  the  recesses  of  a  core  built  up 
of  shaped  stampings,  afterward  completing  the  magnetic  circuit 
either  with  sheets  of  laminations  or  with  strips  interlaced  with 
the  ends  of  the  prejecting  legs.  There  is  good  reason  to  believe 
that  from  this  construction  the  "Shell"  type  transformer  of  to- 
day received  its  name. 


00  00 


16.000 
15,000 
14,000 
13.000 
12,000 
11.000 

2 10,000 

0) 
Oi 

S   9.000 

<! 

ii  8.000 

t§    7.000 
M 

6,000 

5,000 

4.000 

3.000 

2,000 

1.000 

0 


at      a> 


\ I J 

I 

1 1 

I _^_ 

I 

wm-^,-^^wmm^ 

_ i 1 1 

I 

__I___^___,,,j.: 

— =.^^ 


K.V.-Amp. 


.  K.-Volta 


160 
150 
140 
130 
120 
110 

100  3 

90  I 
80  I 
70 
60 
50 
40 
30 
20 
10 
0 


Fig.  1. — Transformer  development. 

Not  very  many  years  ago  it  was  a  question  among  very 
prominent  engineers  whether  15,000-volt  transformers  could  be 
made  to  work. 

Before  the  time  engineers  conceived  the  idea  of  drying  trans- 
former oil,  it  was  not  uncommon  to  see  transformers  without 
any  solid  material  between  coils — the  oil  space  being  relied  on 
for  insulation.  At  that  time  the  transformer  was  the  only 
limiting  feature  of  transmission.  We  have  only  to  go  back  about 
11  years  to  find  the  first  50,000-  and  60,000-volt  transformer 
actually  operating  (see  Fig.  1).  At  the  present  time  we  are 
actually  operating  transformers  at  145,000  volts  with  as  great 
safety  and  with  less  liability  of  break-down  than  formerly  was 


r 


INTRODUCTION  3 

experienced  in  operating  at  15,000  volts,  and  the  actiial  voltage 
limit  of  the  transformer  is  not  yet  in  sight,  but  on  the  contrary — 
the  transmission  line  itself  is  the  limiting  feature  in  the  voltage 
or  the  distance  of  transmission. 

About  16  years  ago  the  first  20,000-volt  transformer  was  made. 
At  the  present  time  the  commercial  manufacture  of  175,000-volt 
power  transformers  is  being  considered.  Fig.  1  represents  the 
development  of  single  capacity  transformers  up  to  the  year  1913. 
Increased  voltage  means,  of  course,  increased  kv-a  capacity  of 
units,  not  only  as  regards  the  transformers  themselves  but  in 
generators  and  prime  movers. 

Glancing  back  25  years  we  enter  upon  a  time  when  alternating 
currents  were  grievously  fought  in  the  Law  Courts  as  being  a 
current  both  '^  dangerous  and  impracticable." 

Just  about  20  years  ago — the  period  when  three-phase  star 
and  delta  systems  of  electric  distribution  were  recognized  as 
practicable  for  commercial  use — we  find  universal  opposition  to 
high  voltages  (above  1500  volts)  and  large  units  (above  500  kw.). 

Going  back  only  10  years — about  the  period  when  50,000  and 
60,000  volts  were  recognized  as  practicable  for  transmission 
purposes — large  commercial  units  and  large  commercial  electric 
power  systems,  as  recognized  to-day,  were  universally  considered 
as  impossible,  as  absolutely  unreliable  or  decidedly  dangerous. 

In  view   of  the  three   above   decades,   practically   accepted 
throughout  the  entire  engineering  world,  we  actually  have  at  the 
present  time  electric  power  systems  operating  as  one  company 
and  one  centralized  system  delivering  over  200,000  kw.,   and 
single  units  for  commercial  electric  power  purposes,  as: 
Steam  turbines  (horizontal  type)  of  33,000  h.p. 
Steam  turbines  (vertical  type)  of  40,000  h.p. 
Water  turbines  (vertical  type)  of  20,000  h.p. 
Turbo-generators  (horizontal  type)  of  25,000  kw. 
Turbo-generators  (vertical  type)  of  30,000  k  w. 
Generators  (vertical  type)  of  12,500  kw. 
Transformers  (shell-type)  of  14,000  kw. 
and  Transformers  (three-phase  group  of  three)  of  18,000  kw. 

Fundamental  Principles. — The  transformer  consists  primarily 
of  three  parts:  the  primary  winding,  the  secondary  winding,  and 
the  iron  core.  The  primary  winding  is  connected  in  one  cir- 
cuit, the  secondary  in  another,  and  the  core  forms  a  magnetic 
circuit  which  links  the  two  together. 


4 


STATIONARY  TRANSFORMERS 


The  principle  of  the  constant-potential  transformer  is  easily 
explained  if  we  neglect  the  slight  effects  of  resistance  drop  in 
the  windings,  leakage  of  magnetic  flux,  and  the  losses.  The 
primary  winding  is  connected  to  a  source  of  e.m.f,,  which  con- 
nection would  constitute  a  short-circuit  were  it  not  for  the 
periodic  changing  in  value  which  permits  the  flux  produced 
by  the  current  to  generate  a  counter  e.m.f.  which  holds  the 
current  down  to  a  value  just  sufficient  to  produce  that  value  of 
flux  necessary  to  generate  an  e.m.f.  in  the  primary  and  equal 
and  opposite  to  the  impressed  e.m.f.  This  same  flux  is  sur- 
rounded by  the  turns  of  the  secondary  winding,  the  same  e.m.f. 
being  generated  in  each  turn  of  wire  whether  primary  or  secondary. 
If  El  is  the  impressed  e.m.f. 


:e  =  e.m.f.  per  turn. 


wherein  A^^  is  the  number  of  primary  turns, 
number  of  secondary  turns. 


Then  if  A^,  is  the 


■< — ff — > 


and 


£^2  = -^2^  =  secondary  e.m.f. 

~  =~  =  ratio  of  transformation. 
A^2     E^ 


When  Ni  is  greater  than  N2,  the  transformer  is  called  a  "  step- 
down  transformer"  and  when  A^^  is  less  than  N2  it  is  called  a 
"step-up  transformer." 

The  reader  will  understand  that  a  step-up  transformer  may  be 


INTRODUCTION  5 

used  as  a  step-down  transformer,  or  vice  versa.  The  primary  is 
the  winding  upon  which  the  e.m.f.  is  impressed. 

The  primary  and  secondary  windings  of  a  transformer  possess 
both  resistance  and  reactance,  and  the  secondary  values  may  be 
reduced  to  primary  terms  by  multiplying  them  by  the  square  of 
the  ratio  of  transformation.  This  applies  to  the  load  resistance 
and  reactance  as  well.  Thus,  consider  a  circuit  containing  a 
transformer,  a  load,  etc.,  as  shown  in  Fig.  2.  Obviously,  to  main- 
tain the  core  flux  a  magnetizing  current  is  required,  which  of 
course  must  pass  through  the  primary  winding. 

(6)  is  an  exact  duplicate  of  the  transformer  (a).  The  factors 
R  and  Xg  are  respectively  the  resistance  and  reactance  of  the 
primary;  R'X's  the  respective  resistance  and  reactance  of  the 
secondary  winding,  and  R"  and  Xg"  the  load  resistance  and 
reactance.  This  representation  is  about  the  simplest  for  treat- 
ment of  the  transformer  circuits. 

Points  in  the  Selection  of  Transformers — The  electrical  char- 
acteristics of  a  transformer  are  mostly  dependent  upon  the 
quality,  arrangement  and  proportion  of  the  iron  and  copper  that 
enter  into  its  construction.  The  losses  are  of  two  kinds:  the 
copper  loss,  due  to  the  current  through  the  coils;  and  the  iron 
loss,  caused  by  the  reversing  of  the  magnetic  flux  in  the  core. 
These  losses  appear  as  heat,  and  suitable  means  must  be  provided 
for  the  disposal  of  this  heat. 

In  selecting  a  transformer  for  a  given  service,  it  is  advisable 
to  consider  first: 

(a)  The  ratio  of  iron  and  copper  loss,  which  should  be  such 
that  the  total  cost  of  the  losses  is  a  minimum. 

(b)  The  cost  of  the  transformer  for  a  given  service  and  the  cost 
of  its  total  losses  should  be  a  minimum. 

The  cost  of  a  transformer  for  a  given  service  depends  on  the 
amount  which  must  be  paid  for  the  losses  during  the  life  of  the 
transformer  and  on  the  first  cost  of  the  transformer  itself.  In 
considering  the  losses  and  price  paid  for  a  transformer  together, 
the  losses  may  be  conveniently  represented  as  a  capital  cost  by 
dividing  their  annual  cost  by  the  interest  and  depreciation  factor. 

Safety  to  life,  durability,  and  economy  are  essential  features  of 
this  apparatus  in  its  ability  to  give  continuous  and  uninterrupted 
service.  These  factors,  sometimes  in  part  and  sometimes  entire, 
are  sacrificed  to  obtain  a  higher  efficiency,  especially  in  high  volt- 
age transformers  where  so  much  insulation  has  to  be  used.     This 


6  STATIONARY  TRANSFORMERS 

is  not  considered  good  practice  although  the  higher  efficiency 
is  obtained,  and  a  transformer  designed  and  built  with  the 
main  object  of  efficiency  at  the  expense  of  safety  and  reliability 
finally  brings  discredit  to  its  maker.  The  loss  in  revenue  alone 
due  to  the  failure  of  a  large  power  transformer  would  more  than 
offset  the  saving  of  several  years  in  gaining  an  additional  fraction 
of  1  per  cent,  in  efficiency,  not  counting  the  great  loss  of  confi- 
dence and  prestige  on  the  part  of  the  customer.  The  applica- 
tion of  knowledge  gained  by  many  years  of  constant  and  care- 
ful study  of  all  the  properties  and  characteristics  of  trans- 
formers in  actual  practice  has  placed  this  type  of  apparatus 
on  a  plane  which  we  may  now  call  both  safe  and  reliable  for  opera- 
ing  voltages  as  high  as  110,000  volts.  Looking  back  over  the 
development  of  the  transformer  we  do  not  pass  very  many  years 
before  we  enter  the  time  when  large  units  of  moderately  high 
voltage  (20,000  volts)  were  considered  by  manufacturers  a  tedious 
if  not  altogether  a  dangerous  undertaking,  in  fact  quite  as  danger- 
ous as  designing  and  building  a  unit  in  these  days  to  give  an  out- 
put of  20,000  kw.  at  200,000  volts. 

Cooling. — A  well-designed  transformer  should  not  only  main- 
tain a  low  average  temperature  but  the  temperature  should  be  uni- 
form throughout  all  of  its  parts.  The  only  effective  way  of  insur- 
ing uniform  temperature  is  to  provide  liberal  oil  ducts  between  the 
various  parts  of  the  transformer,  and  these  should  be  so  arranged 
in  relation  to  the  high  and  low  voltage  windings  as  to  give  the 
best  results  without  sacrificing  other  important  factors.  Ducts 
necessarily  use  much  available  space  and  make  a  high  voltage 
transformer  of  given  efficiency  more  expensive  than  if  the  space 
could  be  completely  filled  with  copper  and  iron;  in  view  of  the 
reliability  and  low  deterioration  of  a  transformer  of  this  type, 
experience  has  demonstrated  that  the  extra  expense  is  warranted. 

For  various  reasons  the  temperature  rise  in  a  transformer  is 
limited.  The  capacity  for  work  increases  directly  as  the  volume 
of  material,  and  the  radiating  surface  as  the  square  of  the  dimen- 
sions; therefore,  it  is  evident  that  the  capacity  for  work  increases 
faster  than  the  radiating  surface. 

The  amount  of  heat  developed  in  a  transformer  depends  upon 
its  capacity  and  efficiency.  For  instance,  in  a  500-kw.  trans- 
former of  98  per  cent,  efficiency  there  is  a  loss  at  full  load  of 
about  7.5  kw. ;  and  since  this  loss  appears  as  heat,  it  must  be 
disposed  of  in  some  way,  or  the  temperature  of  the  transformer 


INTRODUCTION  7 

will  rise  until  it  becomes  dangerously  high.  This  hea,t  may  be 
removed  in  several  ways;  by  ample  radiation  from  the  surface  of 
the  tank  or  case  in  which  the  transformer  is  operated;  by  the 
circulation  of  water  through  pipes  immersed  in  oil;  or  by  the 
constant  removal  of  the  heated  oil  and  its  return  after  being 
cooled  off. 

The  determination  of  the  temperature  may  be  made  by 
thermometer  or  by  the  measurement  of  resistance.  High  tem- 
perature causes  deterioration  in  the  insulation  as  well  as  an 
increase  in  the  core  loss  due  to  aging.  The  report  of  the 
Standardization  Committee  of  the  American  Institute  of  Elec- 
trical Engineers  specifies  that  the  temperature  of  electrical 
apparatus  must  be  referred  to  a  standard  room  temperature  of 
25°  C,  and  that  a  correction  of  1/2  per  cent,  per  degree  must 
be  made  for  any  variation  from  that  temperature,  adding  if  less 
and  subtracting  if  more. 

The  temperature  rise  may  be  determined  by  the  change  of 
resistance,  using  the  temperature  coefficient  0.39  per  cent,  per 
degree  from  and  at  zero  degrees. 

Whenever  water  is  available  and  not  expensive,  water-cooled 
transformers  are  preferable  to  air-blast  transformers  of  the  large 
and  moderate  sizes  (1,500  to  5,000  kw.),  as  it  permits  operation 
at  lower  temperatures  and  allows  more  margin  for  overloads. 
Where  water  is  not  available,  there  is  a  choice  of  two  kinds 
of  air-cooled  transformers:  the  oil-filled  self-cooled  type,  and 
the  air-blast  type  which  is  cooled  by  a  forced  air  circulation 
through  the  core  and  coils  or  by  blowing  air  on  the  outer  case 
of  the  transformer.  This  type  of  transformer  is  not  very  reliable 
for  voltages  above  35,000  volts,  principally  on  account  of  the 
great  thickness  of  the  solid  insulation  needed  and  the  consequent 
difficulty  in  radiating  heat  from  the  copper. 

A  great  deal  has  been  written  about  the  fire  risks  of  air-blast 
and  oil-filled  transformers,  but  this  is  a  matter  that  depends  as 
much  on  surrounding  conditions  and  the  location  of  the  trans- 
formers as  on  their  construction.  The  air-blast  transformer  con- 
tains a  small  amount  of  inflammable  material  as  compared  with 
the  oil-cooled  transformer,  but  this  material  is  much  more  easily 
ignited.  A  break-down  in  an  air-blast  transformer  is  usually 
followed  by  an  electric  arc  that  sets  fire  to  the  insulation  material, 
and  the  flame  soon  spreads  under  the  action  of  the  forced  circu- 
lation of  air;  although  the  fire  is  of  comparatively  short  duration 


8  STATIONARY  TRANSFORMERS 

it  is  quite  capable  of  igniting  the  building  unless  everything 
near  the  transformer  is  of  fireproof  construction.  The  chance 
of  an  oil-filled  transformer  catching  fire  on  account  of  a  short- 
circuit  in  the  windings  is  extremely  small,  because  oil  will  only 
burn  in  the  presence  of  oxygen,  and,  as  the  transformer  is  com- 
pletely submerged  in  oil,  no  air  can  get  to  it.  Moreover,  the  oil 
used  in  transformers  is  not  easily  ignited;  it  will  not  burn  in  open 
air  unless  its  temperature  is  first  raised  to  about  400°  F.,  and  with 
oil  at  ordinary  temperatures,  a  mass  of  burning  material  can  be 
extinguished  as  readily  by  immersing  it  in  the  oil  as  in  water. 
In  fact,  the  chief  danger  of  fire  is  not  that  the  oil  may  be  ignited 
by  any  defect  or  arc  within  the  transformer,  but  that  a  fire  in  the 
building  may  so  heat  the  oil  as  to  cause  it  to  take  fire.  The  idea 
of  placing  oil-filled  transformers  into  separate  compartments  is  not 
thought  of  so  seriously  as  it  was  some  years  ago,  although  it  does 
not  apply  in  every  case  and  therefore  it  is  necessary  to  consider 
carefully  when  selecting  this  type  of  transformer. 

Of  the  large  number  of  factors  in  the  make-up  of  a  transformer 
only  four  which  the  operating  manager  is  particularly  anxious 
to  know  enter  into  the  operating  costs,  namely:  the  coris  and 
copper  losses,  temperature,  efficiency  and  regulation.  All  of 
these  costs  (since  they  might  be  called  costs  as  they  include  the 
cost  of  generating  such  losses  and  of  suppl}'ing  the  station 
capacity  with  which  they  generate  them)  represent  quite  a  large 
amount  of  energy  during  the  life  of  the  transformer. 

Losses. — The  hysteresis  and  eddy  current  losses  are  generally 
combined  under  the  term  of  "  core  loss,"  this  loss  occurring  in 
all  magnetic  material  which  is  subject  to  alternating  magnetic 
stresses.  The  hysteresis  loss,  as  is  generally  known,  may  be 
defined  as  the  work  done  in  reversing  the  magnetism  in  the 
steel,  and  it  may  be  considered  as  due  to  the  molecular  friction 
from  the  reversal  of  magnetism,  this  friction  manifesting  itself 
as  heat.  The  amount  of  hysteresis  in  a  given  steel  varies  with 
the  composition,  with  the  hardness,  with  the  frequency  of  reversal 
of  magnetism,  with  the  maximum  induction  at  which  the  steel  is 
worked,  and  the  temperature.  The  hysteresis  loss  varies  approxi- 
mately as  the  1.6  power  of  induction,  and  directly  as  the  fre- 
quency. The  eddy  current  loss  varies  inversely  as  the  ohmic 
resistance,  directly  as  the  square  of  the  induction,  and  decreases 
as  the  temperature  increases.  It  is  greater  in  thick  laminations 
than  in  thin  (hysteresis  being  greater  in  hard  steel  than  in  soft 


INTRODUCTION  9 

steels),  it  is  also  greater  as  the  insulation  between  adjacent  lamin- 
ations is  less.  Lowering  the  frequency  of  supply  will  result  in 
increased  hysteresis  and  higher  temperature  in  the  iron;  reducing 
the  frequency  from  say  133  to  125  cycles  will  entail  an  increased 
hysteresis  of  about  4  per  cent.,  and  a  reduction  from  60  to  50 
cycles  will  raise  the  hysteresis  approximately  10  per  cent. 

For  equal  output  there  will  not  exist  any  change  in  the 
copper  loss,  but  in  the  case  of  large  power  transformers  the  in- 
creased temperatures  due  to  excessive  iron  losses  will  materially 
decrease  the  output,  and  the  normal  rated  secondary  current  or 
low  voltage  current  will  become  a  virtual  overload. 

Iron  loss  and  exciting  current  in  addition  to  decreased  kw. 
capacity  of  the  transformer  mean  greater  coal  consumption, 
all  these  factors  being  directly  opposed  to  commercial  operation, 
and  as  this  iron  loss  is  constant  while  the  transformer  is  con- 
nected to  the  system,  no  matter  what  the  load  may  be,  the  total 
yearly  loss  will  represent  a  great  loss  in  revenue.  While  the  iron 
loss  is  practically  constant  at  all  loads,  the  copper  or  P  R  loss 
varies  as  the  square  of  the  current  in  both  the  high  and  low 
voltage  windings.  The  output  is  the  total  useful  energy  de- 
livered to  the  primary,  and  consists  of  the  output  energy  plus 
the  iron  loss  at  the  rated  voltage  and  frequency  plus  the  copper 
loss  due  to  the  load  delivered.  This  loss  is  within  easy  control 
of  the  designer,  as  a  greater  or  less  cross-section  of  copper  may 
be  provided  for  the  desired  per  cent,  regulation.  In  a  transformer 
core  of  a  given  volume  and  area,  the  number  of  turns  for  the 
required  iron  loss  are  fixed.  To  secure  the  desired  copper  loss 
advantage  is  taken  of  a  form  of  coil  wherein  the  mean  length 
per  turn  is  kept  as  low  as  possible  with  the  necessary 
cross-section  of  copper.  If  the  form  of  coil  is  rectangular  it 
is  evident  that  the  mean  length  per  turn  of  the  conductor  would 
be  increased,  provided  the  same  cross-section  or  area  of  the 
core  is  enclosed,  so  in  order  to  secure  the  shortest  length  per  mean 
turn  consistent  with  good  construction  it  is  necessary  to  adopt 
the  square  core  in  which  the  corners  have  been  cut  off.  Also, 
in  order  that  the  greatest  amount  of  conductor  may  be  allowed 
for  the  available  space,  all  wire  entering  into  the  low  and  high 
voltage  windings  is  either  square  or  rectangular  in  shape,  as  by 
using  this  form  of  conductor  the  area  is  increased  by  about  33 
per  cent,  over  that  of  ordinary  round  wire.  This  method  permits 
the  copper  loss  to  be  reduced,  and  at  the  same  time  allows  a 


10  STATIONARY  TRANSFORMERS 

great  part  of  the  total  copper  loss  to  take  place  in  the  high  voltage 
winding.  The  loss  due  to  magnetic  leakage  is  made  negligible  by 
virtue  of  the  compact  construction  and  the  proper  disposition  of 
the  windings  with  relation  to  each  other  and  the  core. 

The  copper  loss  generally  has  a  less  cost  than  the  iron  loss, 
due  to  the  reduction  in  output  charge  because  of  its  short  dura- 
tion, and  also  has  a  slightly  less  capital  cost  due  to  its  diversity 
factor. 

The  losses  due  to  the  magnetizing  current  and  heating  are 
determined  from  manufacturers'  guarantees  or  by  test  as  the 
transformer  is  received  from  the  factory.  The  exciting  cur- 
rent of  a  transformer  is  made  up  of  two  components;  one  being 
the  energy  component  in  phase  with  the  e.m.f.  which  represents 
the  power  necessary  to  supply  the  iron  loss,  the  other  component 
being  in  quadrature  with  the  e.m.f.  which  is  generally  known  as 
the  magnetizing  current  and  is  "wattless"  with  the  exception  of 
a  small  P  R  loss.  The  magnetizing  current  has  very  little  in- 
fluence on  the  value  of  the  total  current  in  a  transformer  when 
it  is  operating  at  full  load,  but  as  the  load  decreases  the  effect 
of  magnetizing  current  becomes  more  prominent  until  at  no  load 
it  is  most  noticeable.  The  greater  the  exciting  current,  the 
greater  is  the  total  current  at  the  peak  of  the  load,  and  hence  the 
greater  must  be  the  generating  station  equipment  and  transmis- 
sion lines  to  take  care  of  the  peak. 

Regulation. — It  is  often  said  that  regulation  reduces  the  voltage 
upon  the  load  and  therefore  causes  a  direct  loss  in  revenue  by  re- 
ducing the  energy  sold.  If,  however,  the  mean  voltage  with  trans- 
former regulation  is  maintained  at  the  same  value  as  the  constant 
voltage  without  regulation,  the  energy  delivered  to  the  customer 
will  be  the  same  in  both  cases,  hence  there  will  be  no  direct  loss  of 
revenue.  As  the  regulation  of  transformers  is  affected  at  high 
power  factor  mostly  by  resistance  and  at  low  power  factor  mostly 
by  reactance,  both  should  be  kept  as  low  as  possible.  With 
non-inductive  load  the  regulation  is  nearly  equal  to  the  ohmic 
drop,  the  inductance  having  but  little  effect.  With  an  inductive 
load  the  inductance  comes  into  effect,  and  the  effect  of  resistance 
is  lessened;  depending  on  the  power  factor  of  the  load.  In 
general,  the  core  type  transformer  has  not  so  good  regulation  as 
the  shell  type  transformer;  the  reason  for  this  is  that  in  the  shell 
type  transformer  there  is  a  better  opportunity  for  interlacing  the 
coils. 


INTRODUCTION  11 

Core  Material. — Several  grades  of  steel  are  manufactured  for 
transformers.  Certain  peculiar  ingredients  are  added  to  the 
pure  iron  in  such  proportions  and  in  such  a  manner  that  the 
resultant  metal  is,  actually  speaking,  neither  iron  nor  steel,  and 
for  the  want  of  a  better  name  it  is  termed  by  the  trade  an  "  alloy 
steel."  The  effect  of  various  substances,  such  as  silicon,  phos- 
phorus, sulphur,  etc.,  has  long  been  a  matter  of  common  knowl- 
edge among  those  familiar  with  the  metallurgy  of  steel,  but  the 
electro-magnetic  properties  of  some  of  the  late  "alloy  steels" 
have  been  known  a  comparatively  short  time.  Some  steels  are 
very  springy  and  resist  bending,  but  ordinary  steels  are  compara- 
tively soft  and  yielding,  and  easily  crease  when  bent.  During 
the  past  few  years  a  great  deal  of  time  has  been  spent  in  experi- 
mental work  to  determine  the  best  shape  of  core  and  the  propor- 
tioning of  the  various  elements  of  a  transformer  to  give  the  high- 
est efficiency  with  minimum  cost. 

If  a  transformer  had  a  perfect  magnetic  iron  circuit  no  losses 
would  occur  due  to  imperfect  iron,  etc.  Losses  do  occur  and  in- 
crease with  the  aging  of  the  iron.  The  cost  of  this  iron  loss  will 
include  the  cost  of  generating  such  loss  and  of  supplying  the  sta- 
tion capacity  with  which  to  generate  it,  and  it  also  includes  the 
cost  of  transmitting  the  energy  consumed  by  the  loss  from  the 
generating  station  to  the  transformer.  The  revenue  affected  by 
imperfect  iron  of  a  low  grade  put  into  the  transformers  operating 
at  the  end  of  a  long-distance  transmission  line  .may  be  divided 
up  as  follows: 

Cost  of  iron  losses  in  the  transformers. 

Cost  of  this  energy  passing  over  the  transmission  line,  affecting 
both  efficiency  and  regulation  for  the  same  amount  of  copper. 

Extra  cost  at  the  generating  station  in  generators,  transformers, 
etc.,  to  take  care  of  this  energy. 

Cost  of  magnetizing  current  in  the  transformers. 

Cost  of  this  additional  current  passing  over  the  transmission 
line. 

Extra  cost  at  thie  generating  station  in  generators,  trans- 
formers, etc.,  to  take  care  of  this  extra  current. 

Insulation. — While  the  quality,  arrangement  and  proportion  of 
the  iron  and  copper  are  essentials  in  transformer  design,  the  proper 
selection,  treatment  and  arrangement  of  the  insulating  material 
require  even  greater  skill  and  wider  knowledge  than  does  the 
proportioning    of    copper    and    iron.     A    transformer  will  not 


12  STATIONARY  TRANSFORMERS 

operate  without  sufficient  insulation,  and  the  less  space  occupied 
by  this  insulation  the  more  efficient  will  it  be,  with  a  given 
amount  of  iron  and  copper. 

At  the  present  time  the  use  of  solid  compounds  for  impregna- 
tion of  the  winding  of  transformers  is  almost  universally  adopted. 
The  use  of  this  compound  marks  a  great  improvement  in  the  mod- 
ern transformer  because  it  helps  to  make  the  coils  mechanically 
stronger  by  cementing  together  the  turns  and  the  insulation 
between  turns  and  layers  in  the  windings. 

All  high-voltage  transformers  and  practically  all  transformers 
of  any  voltage,  are  dried  and  impregnated  by  the  vacuum  process 
which  is  now  considered  to  be  the  most  reliable  insulating 
material  and  method  of  insulating.  For  this  purpose  both 
asphalts  and  resins  are  the  materials  available.  They  can  be 
liquified  by  heat  and  forced  into  the  coil  in  that  condition,  and 
on  cooling  they  harden,  forming  a  solid  mass  (coil  and  material) 
which  is,  if  well  done,  free  from  porosity  and  volatile  solvents. 
The  compound  fills  the  porous  covering  of  the  wire-conductors, 
and  all  other  spaces  in  the  coils  no  matter  how  small,  thus  increas- 
ing the  dielectric  strength  and  preventing  moisture  from  soaking 
into  the  coils.  Before  applying  this  process,  the  coils  are  thor- 
oughly dried  either  in  a  separate  oven  or  in  the  impregnating 
tank.  They  are  then  placed  in  the  impregnating  tank  and 
heat  is  applied  until  the  coils  reach  a  temperature  at  which  the 
impregnating  compound  is  thoroughly  fluid.  The  air  in  the 
tank  is  then  exhausted  by  a  vacuum  pump.  After  the  vacuum 
has  exhausted  the  last  traces  of  moisture  from  the  coils,  hot 
compound  from  another  tank  is  drawn  into  the  impregnating 
tank  until  the  coils  are  thoroughly  covered,  this  condition  being 
maintained  until  the  coils  are  impregnated.  The  pressure  gen- 
erally used  is  60  to  80  lb.  per  square  inch.  The  time  required 
under  vacuum  and  pressure  can  only  be  determined  by  trial  but 
usually  from  three  to  six  hours'  vacuum  will  dry  any  ordinary 
high-voltage  coil  not  unduly  moist. 

At  the  present  time  the  fluid  point  of  some  impregnating  com- 
pounds is  about  95°  C,  but  it  is  possible  that  the  development 
of  synthetic  gums  will  soon  reach  a  stage  which  will  permit 
an   actual   operating  temperature  of  130°  C, 

The  National  Board  of  Fire  Underwriters  specify  that  the 
insulation  of  nominal  2000-volt  transformers  when  heated  shall 
withstand  continuously  for  one  minute  a  difference  of  potential 


INTRODUCTION  13 

of  10,000  volts  (alternating)  between  primary  and  secondary 
coils  and  the  core  and  a  no-load  run  of  double  voltage  for  30 
minutes. 

All  transformers  should  be  subjected  to  insulation  tests  between 
the  primary  and  secondary,  and  the  secondary  and  core.  A 
transformer  may  have  sufficient  strength  to  resist  the  strain  to 
which  it  is  constantly  subjected,  and  yet  due  to  an  imperfection 
in  the  insulation  may  break  down  when  subjected  to  a  slight  over- 
voltage  such  as  may  be  caused  by  the  opening  of  a  high-power 
circuit.  The  application  of  a  high-potential  test  to  the  insulation 
will  break  down  an  inferior  insulation,  or  a  weak  spot  or  part  of 
the  structure  in  the  insulation.  The  duration  of  the  test  may 
vary  somewhat  with  the  magnitude  of  the  voltage  applied  to  the 
transformer.  If  the  test  be  a  severe  one,  it  should  not  be  long 
continued,  for  while  the  insulation  may  readily  withstand  the 
application  of  a  voltage  five  or  even  six  times  the  normal  strain, 
yet  continued  application  of  the  voltage  may  injure  the  insulation 
and  permanently  reduce  its  strength. 

FUNDAMENTAL  EQUATIONS 

In  the  design  of  successful  transformers,  the  following  equa- 
tions are  found  reliable: 

Let  N  =  Total  number  of  turns  of  wire  in  series. 

0   =  Total  magnetic  flux. 

A    =  Section  of  magnetic  circuit  in  square  inches. 

/    =  Frequency  in  cycles  in  seconds. 

B  =  Lines  of  force  per  square  inch. 

E  =  Mean  effective  e.m.f. 

4.44=    J_.  =  V2X;r 

4  4^  f6  N 
then  ^  =  i:^i^^-A  d) 

Equation  (1)  is  based  on  the  assumption  of  a  sine  wave  of 
e.m.f.,  and  is  much  used  in  the  design  of  transformers. 

If  the  volts,  frequency,  and  number  of  turns  are  known,  then 
we  have 

._    gxio«  ,„. 


14  STATIONARY  TRANSFORMERS 

If  the  volts,  frequency,  cross-section  of  core,  and  density  are 
known,  we  have: 

4.44X/XB"XA  '^ 

Magnetic  densities  of  transformers  vary  considerably  with 
the  different  frequencies  and  different  designs. 

Current  densities  employed  in  transformers  vary  from  1000 
to  2000  circular  mils  per  ampere. 

Efliciency. — The  efficiency  of  a  transformer  at  any  load  is  ex- 
pressed as: 

Efficiency  =  — ^     ^  , ^,  — — — ^j —  (4) 

output  +  core  loss -f- copper  loss  ^ 

In  the  case  of  ordinary  transformers  with  no  appreciable 
magnetic  leakage,  the  core  loss  is  practically  the  same  from  no- 
load  to  full  load.  The  only  tests  required,  therefore,  in  order  to 
obtain  the  efficiencies  of  such  transformers  at  all  loads,  with 
great  accuracy,  are  a  single  measurement  by  wattmeter  of  the 
watts  lost  in  the  core,  with  the  secondary  on  open  circuit;  and 
measurements  of  the  primary  and  secondary  winding  resistances, 
from  which  the  P  R  watts  are  calculated  for  each  particular  load. 
The  core  loss,  which  is  made  up  of  the  hysteresis  loss  and  eddy- 
current  loss,  remains  practically  constant  in  a  constant-potential 
transformer  at  all  loads.  In  the  case  of  constant-current  trans- 
formers and  others  having  considerable  magnetic  leakage  when 
loaded,  this  leakage  often  causes  considerable  loss  in  eddy  cur- 
rents in  the  iron,  in  the  copper,  and  in  the  casing  or  other  sur- 
rounding metallic  objects.  It  should  be  borne  in  mind  that  the 
efficiency  will  also  depend  on  the  frequency  and  the  wave-form 
and  that  the  iron  core  may  age;  that  is  to  say,  the  hysteresis  co- 
efficient may  increase  after  the  transformer  has  been  in  use 
some  time.  Generally  speaking,  the  efficiency  of  a  transformer 
depends  upon  the  losses  which  occur  therein,  and  is  understood 
to  be  the  ratio  of  its  net  output  to  its  gross  power  input,  the 
output  being  measured  with  non-inductive  load. 

All -day  Efficiency. — The  point  of  most  importance  in  a 
transformer  is  economy  in  operation,  which  depends  not  only 
upon  the  total  losses,  but  more  particularly  upon  the  iron  or 
core  loss.  For  example,  taking  two  transformers  with  iden- 
tical total  losses,  the  one  showing  the  lower  iron  loss  is  to  be 
preferred,  because  of  the  greater  all-day  efficiency  obtained,  and 


INTRODUCTION  15 

the  resulting  increase  in  economy  in  operation.  This  loss 
represents  the  energy  consumed  in  applying  to  the  iron  the 
necessary  alternating  magnetic  flux,  and  is  a  function  of  the 
quality  of  the  iron  and  the  flux  density  at  which  it  is  worked,  or 
in  other  words,  the  number  of  magnetic  lines  of  force  flowing 
through  it. 

The  all-day  efficiency  mentioned  above  is  the  ratio  of  the 
total  energy  used  by  the  customer,  to  the  total  energy  input 
of  the  transformer  during  twenty-four  hours.  The  usual 
conditions  of  present  practice  will  be  met,  if  based  on  five  hours 
at  full  load  and  nineteen  hours  at  no  load;  therefore,  "all-day" 
efficiency  can  be  obtained  from  the  following  equation: 

All-day  efficiency  = 

Full  loadx  5 

Core  lossX24 -|-/  i2 X5 -hFull  loadx 5  ^^ 

The  importance  to  the  economical  operation  of  a  central 
station  of  testing  for  core  loss  every  transformer  received, 
cannot  be  overestimated.  The  variation  in  core  loss  of  two 
transformers  of  identical  design  may  be  considered,  as  depending, 
not  only  upon  the  constituents  of  the  steel  used,  but  also  upon 
the  method  of  treatment. 

It  has  been  found  in  practice,  that  transformers  having  ini- 
tially low  iron  losses,  after  being  placed  in  service,  would  show 
most  decided  increase  under  normal  conditions.  This  increase 
is  due  to  the  "aging"  of  the  iron.  The  aging  of  iron  de- 
pends on  the  kind  of  material  used,  and  on  the  annealing 
treatment  to  which  it  has  been  subjected.  It  has  been  shown 
that  when  steel  is  annealed  so  as  to  have  a  low  loss,  and  then  sub- 
jected to  a  temperature  of  from  85°C.  to  100°  C,  the  loss  usually 
increases,  in  some  cases  this  increase  being  as  much  as  300  to 
400  per  cent. 

By  some  manufacturers  of  transformers  it  is  claimed  that  the 
steel  used  in  their  cores  is  non-aging,  or  that  it  has  been  artifi- 
cially aged  by  some  process.  However,  it  should  be  remembered 
that  an  absolutely  non-aging  steel  is  not  as  yet  a  commercial 
possibility.  Within  very  short  periods  the  iron  losses  some- 
times increase,  and  under  very  high  temperature  conditions  the 
laminations  will  become  tempered  or  hardened,  whereby  the 
permeability  is  greatly  reduced;  therefore,  the  iron  losses  increase 
with  the  length  of  time  the  transformer  is  in  operation. 


16  STATIONARY  TRANSFORMERS 

The  other  factor  affecting  the  efficiency  of  a  transformer  is 
the  copper  loss.  It  occurs  only  when  the  transformer  is  loaded, 
and  while  it  may  be  considerable  at  full  load  it  decreases  very 
rapidly  as  the  load  falls  off.  As  the  transformer  is  seldom  oper- 
ated at  full  load,  and  in  many  cases  supplies  only  a  partial  load 
for  a  few  hours  each  day,  the  actual  watt-hours  of  copper  loss  is 
far  below  the  actual  watt-hours  of  iron  loss.  However,  for 
equal  full-load  efficiencies,  the  transformer  having  equal  copper 
and  iron  losses  is  cheaper  to  manufacture  than  one  in  which  the 
iron  loss  is  reduced,  even  though  the  copper  loss  is  correspond- 
ingly increased. 

Regulation. — The  ability  of  a  distribution  transformer  to  de- 
liver current  at  a  practically  constant  voltage  regardless  of  the 
load  upon  it,  is  a  very  highly  important  feature.  By  the  use 
of  conductors  of  large  cross-section  and  by  the  proper  inter- 
lacing of  primary  and  secondary  coils,  extremely  close  regula- 
tion may  be  obtained  with  loads  of  various  power-factors,  thus 
tending  to  lengthen  the  life  of  lamps  and  to  improve  the  quality 
of  the  light. 

In  well-designed  transformers,  low  core  loss  and  good  regula- 
tion are  in  direct  opposition  to  one  another  yet  both  are  desired 
in  the  highest  degree.  The  regulation  of  a  transformer  is  under- 
stood to  be  the  ratio  of  the  rise  of  secondary  terminal  voltage  from 
full  load  to  no-load,  at  constant  primary  impressed  terminal  vol- 
tage, to  the  secondary  terminal  voltage.  In  addition  to  the  vastly 
improved  service,  it  is  possible  to  adopt  the  efficient  low-consump- 
tion lamp,  when  the  transformers  in  use  maintain  their  second- 
ary voltage  at  a  practically  constant  value  when  the  load  goes  on 
or  off.  While  so  few  central  stations  are  able  to  keep  their 
voltage  constant  within  2  per  cent,  it  may  be  concluded  that  at 
present  the  point  of  best  practical  regulation  on  transformers 
from  about  5  kw.  up,  lies  between  the  values  of  1.75  per  cent, 
to  2.00  per  cent. 

Regulation  is  a  function  of  the  ohmic  drop  and  the  magnetic 
leakage.  To  keep  the  iron  loss  within  necessary  limits  and  at 
the  same  time  secure  good  regulation  is  an  interesting  problem. 
We  may  reduce  the  resistance  of  the  windings  by  using  fewer 
turns  of  wire,  but  with  fewer  turns  the  iron  is  compelled  to  work 
at  a  higher  flux  density,  and  consequently  with  an  increased  loss. 
If  we  adopt  a  larger  cross-section  to  reduce  the  flux  density 
we  need  a  greater  length  of  wire  for  a  given  number  of  turns  which 


INTRODUCTION  17 

thus  gives  an  increase  in  resistance.  The  remaining  expedient 
only  is  to  use  a  larger  cross-section  of  copper,  while  keeping 
down  the  flux  density  by  employing  a  sufficient  number  of  turns, 
to  secure  the  low  resistance  necessary  for  good  regulation.  For 
ordinary  practice  the  regulation  of  a  transformer  for  non-in- 
ductive loads  may  be  calculated  as  follows: 

%  regulation  =  %  copper  loss  — (%  reactance  drop)^ 


200 


(6) 


For  inductive  loads  the  regulation  may  be  calculated  by  the 
following  equation: 
Per  cent,  regulation  = 

per  cent,  reactance  drop     per  cent,  resistance  drop  . 

SiiT^  ^  Cosl'  ^^ 

wherein  0  is  the  angle  of  phase  displacement  between  the  cur- 
rent and  the  e.  m.  f. 

Regulation  on  inductive  loads  is  becoming  more  important  as 
the  number  of  systems  operating  with  a  mixed  load  (lamps  and 
motors)  is  constantly  increasing.  Many  transformers  while 
giving  fair  regulation  on  non-inductive  loads,  give  extremely 
poor  regulation  on  inductive  loads. 

VECTOR  REPRESENTATION 

In  studying  the  performance  of  transformers  it  is  simple  and 
convenient  to  use  graphical  methods.  The  graphical  method 
of  representing  quantities  varying  in  accordance  with  the  sine 
law  has  been  found  to  be  one  of  the  simplest  for  making  clear 
the  vector  relations  of  the  various  waves  to  one  another. 

The  principle  of  this  method  is  shown  in  Fig.  3,  where  the 
length  of  the  line  o  e  represents  the  magnitude  of  the  quantity 
involved,  and  the  angle  e  o  x  =  d  represents  its  phase  position 
either  in  time  or  space. 

In  an  alternating-current  circuit  the  relation  between  the 
most  important  quantities  may  be  represented  by  the  method 
above  mentioned.  When  such  diagrams  are  used  to  represent 
voltages  or  currents,  the  length  of  the  lines  represents  the  scale 
values  of  the  quantities,  while  the  angles  between  the  lines 
represent  the  angle  of  phase  difference  between  the  various 
quantities.     The  diagrams  are  constructed  from  data  available 


18 


STATIONARY  TRANSFORMERS 


in  each  case.  The  diagram  below  represents  a  circuit  containing 
resistance  and  inductive  reactance.  Since  the  /  R  drop  is 
always  in  phase  with  the  current  and  the   counter  e.m.f.   of 


4X 


Fig.  3. — Vector  diagram. 

self-inductance  in  time-quadrature  with  the  current  which 
produces  the  m.m.f.,  these  two  magnitudes  will  be  represented 
by  two  lines,  o  e^  and  o  e^,  at  right  angles  to  each  other;  their 


Fig.  4. — Assumed  vector  diagram  of  a  transformer,  assuming  an  inductive 

load. 

sum  being  represented  by  o  e^^  representing  the  resultant  value 
of  these  two  e.m.fs.,  and  is,  therefore,  equal  and  opposite  to  the 
e.m.f.,  which  must  be  impressed  on  the  circuit  to  produce  the 


INTRODUCTION 


19 


current,  /,  against  the  counter  e.m.f.  of  self-inductance,  2Tt  fL  I, 
and  the  counter  e.m.f.  of  resistance,  /  R.  Therefore,  by  the 
properties  of  the  angles, 

e^=(I  R),  +  (27tfLiy  (8) 

The  angle  of  lag  of  the  current  behind  the  e.m.f.  is  shown  as 
the  angle  between  the  lines  representing  the  resistance  e.m.f.  and 
that  representing  the  resultant  of  the  resistance  and  the  reactance 
e.m.f.  Since  the  resistance  component  of  the  impressed  e.m.f. 
is  in  phase  with  the  current  and  differs  180  degrees  in  phase 
from  the  resistance  e.m.f.,  its  position  will  be  that  shown  by  the 
line  0  Ci,  and  the  angle  between  that  line  and  o  e^  is  the  angle  of 
lag. 


The  tangent  of  the  angle,  d,  is  equal  to 


o  e. 


0  e^  =  27t  f  L  I  and  o  e^  =  I  R, 
27zfLl     2nfL 


or  tan  0  =  '- 


I  R 


R 


(9) 


Denoting  1  =  1. 


(27tfL=Xs  =  (oL.     =jxs)  (10) 

Like  the  e.m.f.,  the  current  values  can  be  split  into  two  compo- 
nents, one  in  phase  and  one  in  quadrature  with  the  e.m.f.,  the 
same  results  being  obtained  in  both  cases. 

Impedance  is  the  apparent  resistance  in  ohms  of  the  trans- 
former circuit,  and  is  that  quantity  which,  when  multiplied  with 
the  total  current  will  give  the  impressed  volts,  or  /  Z  =  E 

Denoting   Z  as   R+j  x;  where  /  is  an  imaginary   quantity 


V-L,  or  Z  =  R+\/-l  L 


w 


(11) 


In  measuring  the  energy  in  an  alternating  current  circuit  it  is 
not  sufficient  to  multiply  ^  by  /  as  in  the  case  of  direct  current, 
because  a  varying  rate  of  phase  between  the  voltage  and  cur- 
rent has  to  be  taken  into  account.  This  phase  angle  can  be 
determined  by  a  voltmeter,  an  ammeter  and  a  wattmeter, 
and  is  expressed  as 


C08.<f>=-^j 


(12) 


where  P  is  the  actual  power  in  watts  consumed  by  the  load; 


20 


STATIONARY  TRANSFORMERS 


E I  the  apparent  watts,  or  P  R  as  it  is  sometimes  called,  and  Cos  (f> 
the  angle  of  phase  displacement. 

It  is  very  evident  that  when  the  resistance  is  large  compared 


with  the  reactance,  the  angle  of  time-lag  is  practically  zero. 
(See  Fig.  174.)  If  the  reactance  is  very  large  compared  with 
the  resistance,  the  angle  of  lag  will  be  almost  90  time-degrees; 
in  other  words,  the  current  is  in  quadrature  with  the  e.m.f. 


-Bs-* 


/wwvww^ 


-Ihr^ 


(a) 


-S.-*- 


(c) 


-*-Eii 


Fig.  6. 


vf 


x  + 


A  problem  which  can  always  be  solved  by  the  use  of  trans- 
formers, is  the  convertion  of  one  polyphase  system  into  another. 
Since  in  the  original  system  there  must  be  at  least  two  compo- 


i 


INTRODUCTION  21 

nents  of  e.m.f,  which  are  displaced  in  time-phase,  by  vary- 
ing the  values  of  these  components  a  resultant  of  any  desired 
phase.can  be  obtained.  In  phase-splitting  devices  using  inductive 
or  condensive  reactance,  an  e.m.f.  in  quadrature  with  the  im- 
pressed e.m.f.  is  obtained  from  the  reactive  drop  of  the  current 
through  an  inductive  winding,  or  a  condenser,  and  the  necessary 

P  L 

energy  is  stored  as  magnetic  energy,  — ^— ,  in  the  core  of  the 

E^  C 

winding,  or  as  electrostatic  energy,     ^    ,  in  the  dielectric  of  the 

condenser;  but  such  devices  are  of  little  practical  use. 


CHAPTER  II 
SIMPLE  TRANSFORMER  MANIPULATIONS 

There  are  a  number  of  different  ways  of  applying  transformers 
to  power  and  general  distribution  work,  some  of  which  are: 

Single-phase  (one,  two,  three  or  more  wire). 

Two-phase  (three,  four,  five  or  more  wire) . 

Three-phase  delta  (grounded  or  ungrounded) . 

Three-phase  star  (grounded  or  ungrounded). 

Three-phase  Tee  (grounded  or  ungrounded). 

Three-phase  open-delta. 

Three-phase  star  to  star-delta  or  vice  versa. 

Three-phase  star  and  delta  or  vice  versa. 

Three-phase  to  two-phase  or  vice  versa. 

Three-phase  to  two-phase-three-phase  or  vice  versa. 

Three-phase  to  six-phase,  or  vice  versa. 

Two-phase  to  six-phase,  or  vice  versa. 

Three-phase  to  single-phase. 

Two-phase  to  single-phase. 

The  principal  two  precautions  which  must  be  observed  in 
connecting  two  transformers,  are  that  the  terminals  have  the 
same  polarity  at  a  given  instant,  and  the  transformers  have 
practically  identical  characteristics.  As  regards  the  latter  con- 
dition, suppose  a  transformer  with  a  2  per  cent,  regulation  is  con- 
nected in  parallel  with  one  which  has  3  per  cent,  regulation;  at  no 
load  the  transformers  will  give  exactly  the  same  e.m.f .  at  the  term- 
inals of  the  secondary,  but  at  full  load  one  will  have  a  secondary 
e.m.f.  of,  say,  100  volts,  while  the  other  has  an  e.m.f.  of  99  volts. 
The  result  is  that  the  transformer  giving  only  99  volts  will  be 
subject  to  a  back  e.m.f.  of  one  volt,  which  in  turn  will  disturb 
the  phase  relations  and  lower  the  power-factor,  efficiency  and 
combined  capacity;  in  which  case  it  is  much  better  to  operate 
the  secondaries  of  the  two  transformers  separately.  In  order  to 
determine  the  polarity  of  two  transformers  proceed  with  the 
parallel  connection  as  if  everything  were  all  right,  but  connect 
the  terminals  together  through  two  small  strips  of  fuse  wire,  then 
close  the  primary  switch.     If  the  fuse  blows,  the  connections 

22 


SIMPLE  TRANSFORMER  MANIPULATIONS       23 

must  be  reversed;  if  it  does  not,  then  the  connections  may  be 
made  permanent. 

The  primary  and  secondary  windings  of  transformers  may  be 
connected  to  meet  practically  any  requirement.  Fig.  6  repre- 
sents the  ordinary  method  of  connecting  a  single-phase  trans- 
former to  a  single-phase  circuit.  Referring  to  the  graphical 
representation  in  Fig.  6  it  is  shown  that  0  E  p  and  O  E  s  (the 
primary  and  secondary  e.m.fs.)  represent  two  lines  of  constant 
length,  rotating  at  a  uniform  rate  about  0  as  a  center.  The 
direction  of  the  secondary  is  not  strictly  180  electrical  degrees 
out  of  time  phase  with  the  primary,  but  for  convenience  and 
elementary  purposes  it  is  commonly  represented  as  such.  The 
dotted  line  is  vertical  to  0  X,  so  that  as  the  points  E  por  E  s  move 


u 


-1000- 


-1000- 


♦400- 


LqqqqJ 
cm 


-100- 


FiG.  7. — Straight  connection  of 
two  ordinary  single-phase  trans- 
formers. 


nm   (W) 


* 50- 


-50- 


^100 

Fig.  8. — Single-phase  trans^ 
former  with  primary  and  sec- 
ondary coils  both  in  series. 


in  the  circle,  they  occupy  variable  distances  from  0.  As  they 
travel  from  X  through  Y ,  it  is  evident  that  they  have  positive 
and  negative  values,  and  that  these  values  vary  from  zero  to  a 
definite  maximum.  They  pass  through  a  complete  cycle  of 
changes  from  positive  to  negative  and  back  to  positive,  corre- 
sponding to  a  complete  revolution,  both  the  e.m.fs  varying  as 
the  sine  of  the  angle  0  =  0  E  p  A. 

Since  the  changes  of  voltages  in  the  primary  and  secondary 
windings  of  a  transformer  go  through  their  maximum  and  mini- 
mum values  at  the  same  time,  the  result  of  connecting  the  two 
windings  in  series  is  to  produce  a  voltage  which  is  either  the  sum 
or  the  difference  of  the  voltages  of  the  windings,  according  to  the 
mode  of  joining  them.  If  the  windings  of  a  step-up  transformer 
are  joined  in  series  so  that  their  resultant  voltage  is  the  sum  of  the 
voltages  of  the  two  windings,  the  source  of  supply  may  be  con- 


24  STATIONARY  TRANSFORMERS 

nected  to  the  terminals  of  the  composite  winding,  instead  of  at 
the  terminals  of  what  was  originally  the  primary.  If  this  is  done, 
the  windings  of  the  transformer  may  be  reduced  until  the  total 
voltage  of  the  two  windings  equals  the  voltage  of  the  original 
primary  winding. 

Fig.  7  shows  the  way  in  which  two  ordinary  single-phase  trans- 
formers are  connected. 

Fig.  8  shows  one  transformer  which  has  two  secondary  coils 
connected  in  series.  If  this  transformer  be  of  the  core  type  and 
the  two  coils  arranged  on  different  limbs  of  the  core,  it  will  be 
advisable  to  have  the  fuse  in  the  middle  wire  considerably  smaller 
than  the  fuses  on  the  two  outside  wires.  The  reason  for  this  is, 
that  should  one  of  the  fuses  on  the  outside  circuits  blow,  say,  for 
instance  the  fuse  on  leg  A,  the  secondary  circuit  through  this 
half-section  will  be  open-circuited,  and  the  primary  coil  corre- 
sponding to  this  section  will  have  a  greater  impedance  than  the 
other  half  of  the  coil,  the  inductance  of  which  will  be  neutralized 
by  the  load  on  the  other  half  of  the  secondary  coil.  The  result  will 
be  that  the  counter  e.m.f.  of  the  primary  section.  A,  will  be 
greater  than  that  of  section  C,  because  the  two  sections  are  in 
series  with  each  other,  and  the  current  must  be  the  same  in  both 
coils;  therefore,  the  difference  of  potential  between  the  primary 
terminals,  yl,  will  be  greater  than  that  between  the  primary  termi- 
nals of  C,  consequently  the  secondary  voltage  of  C  will  be  greatly 
lowered. 

Manufacturers  avoid  the  above  mentioned  disadvantage  by 
dividing  each  secondary  coil  into  two  sections,  and  connecting  a 
section  of  one  leg  in  series  with  a  section  of  the  coil  on  the  other 
leg  of  the  core,  so  that  the  current  in  either  pair  of  the  secondary 
windings  will  be  the  same  in  coils  about  both  legs  of  the  core. 

Transformers  are  made  for  three-wire  service  having  the  wind- 
ings so  distributed  that  the  voltage  on  the  two  sides  will  not  differ 
more  than  the  regulation  drop  of  the  transformer,  even  with  one- 
half  the  rated  capacity  of  the  transformers  all  on  one  side;  with 
ordinary  distribution  of  load  the  voltage  will  be  practically  equal 
on  the  two  sides. 

Fig.  9  shows  a  single-phase  transformer  with  two  coils  on  the 
primary,  and  two  coils  on  the  secondary.  The  primaries  are 
shown  connected  in  parallel  across  the  1000-volt  mains,  and  the 
secondaries  are  also  connected  in  parallel. 

To  obtain  a  higher  secondary  voltage  the  coils  may  be   con- 


SIMPLE  TRANSFORMER  MANIPULATIONS       25 

iiected  as  shown  in  Fig.  10.  In  this  case  the  primary  coils  are  con- 
nected in  parallel,  and  the  secondary  coils  connected  in  series. 
The  difference  of  potential  across  the  two  leads,  with  the  primaries 
connected  in  parallel  and  the  secondaries  connected  in  series  will 
be  200  volts,  or  100  volts  per  coil. 


z 


-1000- 


- — 1000^     *— 1000 

UxMJUmJ 


;= 


1000- 


-100- 


-doo- 


-100- 


^00     >|-     100- 


-200- 


FlG.  9. 


Fig.  10. 


-1000- 


-^-500     >h    500-> 


•iJO^ 


^50^ 


50 

Fig.  11. 

Fig.  9. — Transformer  with  primary  and  secondary  windings  both  in 
parallel. 

Fig.  10. — Transformer  with  primary  windings  connected  in  parallel  and 
secondary  windings  in  series. 

Fig.  11. — Transformer  with  primary  windings  connected  in  series  and 
secondary  windings  in  parallel. 

Note — ^For  convenience  all  ratios  of  transformation  will  be  understood  to 
represent  ten  to  one  (10  to  1). 

If  we  invert  the  arrangement  shown  in  Fig.  10  by  connect- 
ing the  primary  coils  in  series,  and  connecting  the  secondary 
coils  in  parallel,  we  shall  obtain  a  secondary  voltage  of  50,  as 
represented  in  Fig.  11. 

In  Figs  12-12*  and  13  are  represented  a  right  and  wrong  way  of 


26 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


connecting  transformers  in  scries  or  parallel,  just  as  the  case 
may  be.  The  connections  shown  in  Fig.  12  represent  the  right 
way  of  connecting  two  transformers  in  parallel,  or  in  series,  the 
solid  lines  showing  the  series  connection  and  the  dotted  lines  the 
parallel  connection. 


X 


1000 


1000 


^lOO-H         i-lOO-^ 

L ^ 


-200- 
-100- 


<-iooo-»-^-iooo 
fvwA      Lvwvv 

Uoo^^ioo-J 


ZZ 


-1000- 

lomJ 


1000 


(WLJWi 


-100- 


FiG.  12. — The  right  way  of  connecting  single-phase 
transformers  in  parallel. 


Fig.  13.— The  wrong 
way  of  connecting  sin- 
gle-phase transformers 
in  parallel. 


The  connections  shown  in  Fig.  13  are  liable  to  happen  when 
the  transformers  are  first  received  from  the  factory.  Through 
carelessness,  the  leads  are  often  brought  out  in  such  a  manner  as 
to  short-circuit  the  two  coils  if  connected  as  shown.  In  this 
case  the  sudden  rush  of  current  in  the  primary  windings  would 
burn  out  the  transformer  if  not  protected  by  a  fuse. 


-3000- 


'  cm 


cm  rw] 

-lOOH        -100-^ 


-100- 


-100- 


FiG.  14. 


—Three-wire  secondary 
distribution. 


Fig.  15.— Three  1000- volt 
transformers  connected  in 
series  to  a  3000-volt  circuit. 


The  three-wire  arrangement  shown  in  Fig.  14  differs  in  every 
respect  from  the  three-wire  system  represented  in  Figs.  8  and  10. 
The  two  outside  wires  receive  current  from  the  single-phase 
transformer,  and  the  center,  or  neutral,  wire  is  taken  care  of  by 
a  balancing  transformer  connected  up  at  or  near  the  center  of 


SIMPLE  TRANSFORMER  MANIPULATIONS       27 

distribution.  The  balancing  transformer  need  only  be  of  very 
small  size,  as  it  is  needed  merely  to  take  care  of  the  variation  of 
load  between  the  two  outside  wires. 

It  is  sometimes  desirable  to  use  a  much  higher  voltage  than 
that  for  which  the  transformers  at  hand  have  been  designed,  and 
to  attain  this,  the  secondary  wires  of  two  or  more  transformers 
may  be  connected  in  parallel,  while  the  primary  wires  may  be 
connected  in  series  with  the  source  of  supply. 

This  manner  of  connecting  transformers  is  shown  in  Fig.  15. 
It,  however,  involves  a  high-voltage  strain  inside  the  separate 
transformers,  between  the  high-  and  low-tension  windings,  and 
is  therefore  used  only  in  special  cases  of  necessity. 


r^ 


3 


-1000- 


* 900 > 


00 


Fig.  16.  Fig.  17. 

Fig.  16. — Connection  between  primary  and  secondary  windings,  which 
gives  1100  volts  across  the  secondary  distribution  wires.  Boosting 
transformer. 

Fig.  17. — Connection  between  primary  and  secondary  windings  from 
which  we  obtain  900  volts.     Lowering  transformer. 


L 


While  it  is  possible  to  insulate  for  very  high  voltages,  the 
difficulties  of  insulation  increase  very  rapidly  as  the  voltage  is 
raised,  increasing  approximately  as  the  square  of  the  voltage. 

Consider  the  case  of  a  single-phase  transformer  as  shown  in 
Fig.  7.  There  is  evidently  a  maximum  strain  of  1000  volts  from 
one  high-tension  line  wire  to  the  other,  and  a  strain  of  500  volts 
from  one  line  wire  to  ground,  if  the  circuits  are  thoroughly 
insulated  and  symmetrical.  The  strain  between  high-tension 
and  low-tension  windings  is  equal  to  the  high-tension  voltage, 
plus  or  minus  the  low-tension  voltage,  depending  on  the  arrange- 
ment and  connection  of  the  coils.  With  the  arrangement 
shown  in  Fig.  16,  it  is  quite  possible  to  obtain  1100  volts  between 


28 


STATIONARY  TRANSFORMERS 


the  wire,  B,  and  ground,  and  the  first  indication  of  any  such 
trouble  is  likely  to  be  established  by  a  fire,  or  some  person  coming 
in  contact  with  a  lamp  socket,  or  other  part  of  the  secondary 
circuit  that  is  not  sufficiently  insulated. 

Should  a  ground  exist,  or  in  other  words,  a  short-circuit 
between  the  high-tension  and  low-tension  windings,  it  will,  in 
general,  blow  fuses,  thus  cutting  the  transformer  out  of  service; 
or  the  voltage  will  be  lowered  to  such  an  extent  as  to  call  atten- 
tion to  the  trouble,  but  the  secondary  windings  must  be 
grounded. 

To  avoid  this  danger  to  life,  the  grounding  of  secondaries  of 
distribution  transformers  is  now  advocated  by  all  responsible 


-1000- 


♦—500- 


-500 


^A/\ 


A__ AAA 

50     >t<      60->| 


-900- 


-1000- 


-1000- 


WWW— I— /WWW 

100^         H-lOo 


-1300- 


FiG.  18. 


Fig.  19. 


electric  light  and  power  companies  in  America.  Differences  of 
opinion  have  arisen  as  to  general  details  both  as  regards  the  scope 
of  grounding  and  the  methods  to  be  employed,  but  there  is  never- 
theless a  decided  and  uniform  expression  that  the  low  voltage 
secondaries  of  distribution  transformers  should  be  permanently 
and  effectively  grounded. 

The  National  Electrical  Code  provides  for  the  grounding  of 
alternating-current  secondaries  for  voltages  up  to  250  volts. 
This  voltage  was  decided  upon  after  extensive  investigation  and 
discussion. 

The  principal  argument  for  this  grounding  is  the  protection  of 
life.  A  fault  may  develop  in  the  transformer  itself,  between  the 
primary  and  secondary  wires  which  are  usually  strung  one  set 
above  the  other  (high  voltage  always  above  the  low  voltage 
conductors),  or  a  foreign  circuit  conductor  such  as  an  electrified 
series  arc  or  incandescent  lighting  line  conductor  may  come  into 
metallic  contact  with  a  secondary  line  wire  leading  from  trans- 


SIMPLE  TRANSFORMER  MANIPULATIONS       29 


former.  Both  the  secondary  line  conductors  and  secondary 
transformer  windings  are  liable  to  several  forms  of  faults  and 
danger  due  to  a  high  voltage. 

Some  of  the  accidents  recorded  and  due  to  such  causes,  are  the 
handling  of  portable  incandescent  lamps  and  switching  on  lights 


1000 

500    >U     SCO 


-500^  <— 500- 
7VW\A_.  ^jlAMA/J 


60—^ 


-1100- 


-50^ 


-1000- 


(*^       (*^ 


-500- 


FiG.  20. 


Fig.  21. 


-1000- 


*— 600- 


-500- 


located  in  rooms  with  tile,  cement  or  stone  floors,  by  means  of 
the  switches  attached  to  lamp  sockets. 

Fig.  17  represents  an  arrangement  of  primary  and  secondary 
circuits  that  may  accidentally  be  made.  These  conditions  imme- 
diately establish  a  potential  difference  of  900  volts.  A  great 
number  of  other  single-phase  transformer  combinations  may  be 
used,  some  of  which  are  shown  in  Figs.  18,  19,  20,  21,  and  22. 

If  we  take  a  transformer  with  a  ratio   . 

of  10  to  1,  say  500  and  50  turns  respec- 
tively, and  join  the  two  windings  in 
series,  we  find  the  number  of  turns  re- 
quired is  only  a  total  of  500  if  the  volt- 
age is  applied  to  the  ends  of  the  whole 
winding  since  the  ratio  of  primary  to 
secondary  turns  still  remains  10  to  1, 
and  with  the  same  magnetic  induction 
in  the  core,  the  primary  counter  e.m.f. 
and  the  secondary  e.m.f.  will  both  re- 
main exactly  as  before;  the  ratio  of  pri- 
mary and  secondary  currents  remains  also  the  same  as  before 
but  is  not  produced  in  quite  the  same  manner  since  the  primary 
current  will  flow  into  the  secondary  and  take  the  place  of  part 
of  the  current  which  would  have  been  induced  in  the  first  case 
where  the  windings  are  separated. 


■<-50-»J  K50*< 


-loeo- 


FiG.  22. 


CHAPTER  III 
TWO-PHASE  TRANSFORMER  CONNECTIONS 

So  far  as  transformers  are  concerned  in  two-phase  distribution, 
each  circuit  may  be  treated  independently  of  the  other  as  shown 
in  Fig.  23,  which  is  connected  as  though  each  primary  and  second- 
ary phase  were  only  a  straight,  single-phase  system.  One 
transformer  is  connected  to  one  primary  phase  to  supply  one 
secondary  phase,  independent  of  the  other  phase,  and  the  other 
transformer  is  connected  to  the  other  primary  phase,  supplying 
the  other  secondary  phase. 

In  the  two-phase  system  the  two  e.m.fs,  and  currents  are 
90  time-degrees  or  one-fourth  of  a  cycle  apart.  The  results 
which  may  be  obtained  from  various  connections  of  the  windings 
of  single-phase  transformers,  definitely  related  to  one  another 
in  point  of  time,  may  be  readily  determined  by  diagrams. 

The  vector  diagram  in  which  e.m.fs.  and  currents  are  repre- 
sented in  magnitude  and  phase  by  the  length  and  direction  of 
straight  lines,  is  a  common  method  for  dealing  with  alternating- 
current  phenomena.  To  secure  a  definite  physical  conception 
of  such  diagrams,  it  is  useful  to  consider  the  lines  representing 
the  various  e.m.fs.  and  currents,  as  also  representing  the  windings 
which  are  drawn,  to  have  angular  positions  corresponding 
to  angles  between  the  lines;  the  windings  are  also  considered  to 
have  turns  proportional  in  number  to  the  length  of  the  corre- 
sponding lines  and  to  be  connected  in  the  order  in  which  the  lines 
in  the  diagrams  are  connected. 

The  method  of  connecting  two  transformers  to  a  four-wire, 
two-phase  system  is  shown  in  Fig.  24.  Both  phases,  as  will  be 
seen,  are  independent  in  that  they  are  transformed  in  separate 
transformers. 

A  method  of  connection  commonly  used  to  obtain  economy 
in  copper  is  that  shown  in  Fig.  24  where  the  primaries  of  the 
transformers  are  connected  independently  to  the  two  phases,  and 
the  secondaries,  are  changed  into  a  three-wire  system,  the  center, 
or  neutral  wire  being  about  one-half  larger  than  each  of  the  two 
outside  wires. 

30 


TWO-PHASE  TRANSFORMER  CONNECTIONS      31 

When  two  transformers  having  the  same  ratio  are  connected  in 
parallel  with  a  common  load,  the  total  secondary  current  is 
divided  between  them  very  nearly  in  inverse  proportion  to  their 
impedances.     This  inverse  impedance  is  usually  expressed  as 

p 

(13) 


Z     R  +\/_i  Lw 


Consider,  for  instance,  a  5  kv-a  transformer  with  an  impedance 
of  2.9  per  cent,  and  a  4  kv-a  transformer  having  an  impedance  of 
2.3  per  cent.     The  admittances  will  be 


P\ 

a        n 


x  + 


6'      Ep.    h  .y 

Fig.  23. — Two-phase  four-wire  arrangement. 

5  4 

;r-^=  1.72  ohms  and^^=  1.74  ohms 

The  division  of  a  total  load  of  9  kv-a  on  these  when  connected 
directly  in  parallel  is 

1.72X9 


for  the  5  kv-a  -7^.'^''    =4.57  kv-a  or  91.5  per  cent,  rated  load. 
3.46 

and 

for  the  4  kv-a    '    ^r.    =4.53  kv-a  or  113  per  cent,  rated  load. 
3.46 

the  value  3.46  is  the  total  sum  of  admittances  or  1.74  +  1.72  = 
3.46  ohms. 

Lighting  transformers  are  generally  not  mounted  closely  to- 
gether when  parallel  operation  is  required,  but  are  usually  on  a 
secondary  net-work.  In  such  cases  where  the  drop  due  to  the 
resistance  of  wiring  or  load  between  the  two  transformers  is 


32  STATIONARY  TRANSFORMERS 

considerable,  any  difference  such  as  ordinarily  exists  between 
different  designs  and  different  sizes  would  usually  be  automatically 
compensated  for,  so  that  the  transformers  would  each  take  their 
proper  proportion  of  load. 

Assume  these  same  two  transformers  are  connected  in  parallel 
at  a  distance  of  about  500  ft.  apart.  Assume  also  that  the  center 
of  load  is  200  ft.  from  the  5  kv-a  transformer  and  that  the  second- 
ary wiring  consists  of  a  No.  0  wire.  Neglecting  altogether  the 
reactance  which  will  be  small,  as  wires  will  doubtless  be  fairly 
close  together,  the  drop  due  to  resistance  from  the  4  kv-a  trans- 
former to  the  center  of  load  will  be  1.94  per  cent.,  and  from  the 
5  kv-a  transformer  about  1.62  per  cent.  Adding  these  resistances 
to  the  resistance  component  of  the  impedance  of  the  two  trans- 
formers, the  impedance  of  the  5  kv-a  transformer  will  be  in- 
creased to  4.15  per  cent,  and  the  4  kv-a  transformer  4.01  per 
cent.     The  division  of  the  total  load  will  be 

1  2x9 

for  the  5  kv-a  -^^o— =  4.92  kv-a  or  98.5  per  cent,  rated  load. 

and  ^    '    ^ 

1  0X9 
for  the  4  kv-a    „  ^     =4.08  kv-a  or  102  per  cent,  rated  load. 

the  value  2.2  being  the  sum  of  the  admittances  1.2  +  1.0  =  2.2. 
ohms. 

So  long  as  the  two  transformers  are  not  connected  in  parallel 
it  makes  no  difference  which  secondary  wire  of  any  one  of  the 
two  transformers  is  connected  to  a  given  secondary  wire.  For 
example:  It  is  just  as  well  to  connect  the  two  outside  wires,  a 
and  b,  together,  as  it  is  to  connect  a'  and  b'  as  shown  in  Fig.  24. 
However,  it  makes  no  difference  which  two  secondary  wires  are 
joined  together,  so  long  as  the  other  wires  of  each  transformer  are 
connected  to  the  outside  wires  of  the  secondary  system.  The 
two  circuits  being  90  time-degrees  apart,  the  voltage  between 
a  and  b  is  '\/2  =  1.141  times  that  between  any  one  of  the  outside 
wires  and  the  neutral,  or  common  return  wire.  The  current  in 
c  is  \/2  =  1.141  times  that  in  any  one  of  the  outside  wires. 

Fig.  25  shows  another  method  of  connecting  transformers, 
where  the  common  return  is  used  on  both  primary  and  secondary. 
With  this  method,  there  is  an  unbalancing  of  both  sides  of  the 
system  on  an  induction-motor  load,  even  if  all  the  motors  on 
the  system  should  be  of  two-phase  design.  The  unbalancing  is 
due  to  the  e.m.f.  of  self-induction  in  one  side  of  the  system  being 


TWO-PHASE  TRANSFORMER  CONNECTIONS      33 


in  phase  with  the  effective  e.m.f.  in  the  other  side,  thus  affecting 
the  current  in  both  circuits. 

Various  combinations  of  the  two  methods  shown  in  Figs.  16 
and  18  can  be  made  by  connecting  the  primaries  and  secondaries 


B 


-1000- 


Ismsu 


-1000- 


ysmsu 


mi.-m) 


-100- 


-loo— > 


c 
HI 


Fig.  24. — Two-phase  four-wire  primary  with  three-wire  secondary. 

as   auto-transformers   similar  to   the   single-phase   connections 
just  mentioned. 

The  four  ordinary  methods  of  connecting  transformers  are 
represented  by  vectors  in  Fig.  26,  a,  b,  c  and  d,  showing  relative 
values  of  e.m.fs.  and  currents. 


-1410- 


-1000- 


-1000- 


-100- 


-100- 


-141- 


FiG.  25. — Two-phase  three-wire  primary  with  three-wire  secondary. 
Eah  =  2e  Eah  =  2e 

Ea'h'  =  2e  Eaa'  =  \/2e 


Eab='e 

Ea'a  =  \/2e 

70  =  ^/21 
(C) 


(5) 
Eab  =  2e 

Eaa' =  2\/2e 
Ea'b=2e 
la  and  h  =  i 
766' =  V2* 


34 


STATIONARY  TRANSFORMERS 


Let  E  =  impressed  volts  per  phase  for  A,  B  and  D. 

E  . 
e    =    -  impressed  voltage  per  phase  for  A,  B  and  D. 

e    =E  impressed  voltage  per  phase  for  C. 
I    =i  =  current  per  phase  for  A  and  B. 
Ic  =  current  times  \/2  per  phase  for  D. 
la',  lb,  la,  Ih'  =  \/2  times  the  current  per  phase  for  C. 


U)  J, 


.  ^ 

1 

e 

E 


b' 


E 

(G)  (D) 

Fig.  26. — Two-phase  three-,  four-  and  five-wire  systems. 


Another  arrangement  is  to  connect  the  middles  of  the  two 
transformer  secondaries,  as  shown  in  Fig.  27.  This  method  gives 
two  main  circuits,  a  c  and  df,  and  four  side  circuits,  ad,dc,  cf,  and 
fa.  The  voltage  of  the  two  main  circuits,  between  d  and /is  100, 
and  between  a  and  c  is  100.  But  the  voltage  across  any  one  of 
the  side  circuits  is  one-half  times  that  in  any  one  of  the  main 
circuits,  times  the  square  root  of  two,  or  50X\/2  =  70  volts. 

Another  method  shown  in  Fig.  28,  commonly  called  the  five- 
wire  system,  is  accomplished  by  connecting  the  secondaries  at 
the  middle,  similar  to  the  arrangement  in  Fig.  27,  and  bringing 
out  an  extra  wire  from  the  center  of  each  transformer. 

The  difference  of  potential  between  a  and  e  will  be  100X\/2  = 


TWO-PHASE  TRANSFORMER  CONNECTIONS      35 

141  volts,  that  across  b  d  will  be  50X\/2  =  70  volts,  and  that 
across  any  one  of  the  main  circuits  will  be  100  volts. 

Another  very  interesting  two-phase  transformation  may  be 
obtained  from  two  single-phase  transformers  by  simply  con- 
necting the  two  secondary  windings  together  at  points  a  little  to 
one  side  of  the  center  of  each  transformer  (see  Fig.  29) .     There 


Fig.  27. — Two-phase  star  or  four-phase  connection. 

are  to  be  obtained  75X'\/2  =  106  volts  between  a  and  /; 
\/7o^ 4- 25^  =  79  volts  between  a  and  d,  and  c  and/;  25X\/2  =  35 
volts  between  d  and  c,  and  100  volts  across  each  of  the  secondary 
windings. 


Fig.  28. — Two-phase  five-wire  secondary  distribution. 

It  is  possible  by  a  combination  of  two  single-phase  transformer 
connections,  to  change  any  polyphase  system  into  any  other 
polyphase  system,  or  to  a  single-phase  system. 

The  transformation  from  a  two-phase  to  a  single-phase  system 


36 


STATIONARY  TRANSFORMERS 


is  effected  by  proportioning  the  windings;  or  one  transformer 
may  be  wound  for  a  ratio  of  transformation  of  1000  to  50;  the 

/3\ 

j-j.     The  secondary  of  this 

transformer  is  connected  to  the  middle  of  the  secondary  wind- 
ing of  the  first. 


other  a  ratio  of  1000  to  86.6.  or 


A 

-1000 — H 


uKlfMMJ      liMiKmJ 


B 

-1000 H 


<-75 


6' 
100- 


H>  <-35->  <r25 


105.7- 


-100- 


/ 


Fig.  29. — Two-phase  multi-wire  distribution. 

In  Fig.  30,  a  c  represents  the  secondary  potential  from  a  to  c  in 
one  transformer.  At  the  angle  of  90  degrees  to  a  c  the  line,  c  d, 
represents  in  direction  and  magnitude  the  voltage  between  c  and 
h  of  the  other  transformer.  Across  the  terminals,  a  c,  ch,  and 
a  h,  it  follows  that  three  e.m.fs.  will  exist,  each  differing  in 


-1000- 


U^imilQj 


-1000 — > 


liiim^ 


<-50-*i        *    c    '      h-ee.e-^ 


-100- 


FiG.  30. — Two-phase  to  single-phase  distribution. 


direction  and  value.     The  e.m.f.  across  a  &  is  the  resultant  of 
that  in  a  c  and  c  6  or  100  volts. 

A  complete  list  of  two-phase,  three-  and  four-wire  transformer 
connections  is  shown  in  Fig.  31  and  a  list  of  two-phase  parallel 
combinations  is  shown  in  Fig.  32.  These  might  or  might  not 
represent  a  certain  change  in  the  transformer  leads.     They  are, 


TWO-PHASE  TRANSFORMER  CONNECTIONS      37 

however,  only  intended  to  represent  those  connections  and  com- 
binations which  can  be  made  with  the  leads  symmetrically  located 
on  the  outside  of  the  transformers. 

For  grounding  two-phase  systems  several  methods  are  em- 
ployed, the  best  being  those  given  in  Fig.  33. 

(A)  represents  a  two-phase  four-wire  system,  the  two  single- 
phases  being  independently  operated,  consequently  two  inde- 
pendent grounds  are  necessary. 


A 

B 

A 

B 

A 

B 

A 

B 

n 

\a 

n 

a 

(1) 

b 

n 

2a 

a 

2-> 

6 

a 

> 

a 

<-eV2"-> 

6 

A 

B 

^y\/\ir^ 

/\r->\ir\ 

(3) 


h 


^ 


B 


U\aaaI 


(4). 


pq    f^'^ 


""C^ 


PA 


5 


(6) 


■«v5" — 1 


fA 


-e-v^- 


FiG.  31. — Complete  list  of  two-phase  transformer  connections. 


B 


(B)  also  represents  a  two-phase  four-wire  system  to  be  used 
for  three-phase  and  two-phase  at  the  same  time.  This  is  similar 
to  the  "  Taylor"  system  excepting  that  two  units  instead  of  three 
are  employed.  The  maximum  voltage  to  ground  is  a'— x, 
or  i!;x  0.866. 

(C)  likewise  represents  a  two-phase  four-wire  system  with 
"T"  three-phase  primary.     In  this  case  the  maximum  voltage 


I 


strain  to  ground  is  E^/  -  of  voltage  between  terminals 

(D)  represents  a  two-phase  three-wire  system.     The  maximum 
strain  to  ground  in  this  case  is  full  voltage  of  any  phase. 


38 


STATIONARY  TRANSFORMERS 


{E)  represents  a  "  V  "  two  unit  system.     The  maximum  voltage 
strain  to  ground  is  E  0.866,  or  the  same  as  (B) . 

{F)  represents  the  two-phase  interconnected  four-  or  five-wire 


A 


B 


A     I      B 


(5) 


B 


A 


B 

IWSAl 


(9) 


B 


^A/^/J     INAAN 


a         6  a         6 


r'^^    c^^!^   V~^^    C2X^ 


nr^    1"^^ 


^ 


r^  ,^ 


A^    A^  ^^  AA    AA 
a  b  a         b 


A 


WvaaI         Iwv^    Uaaa 


(H) 


AA 


/^s/\    AA^^^^AA 


b 


Fig.  32. — Two-phase  parallel  combinations. 


system.  The  maximum  voltage  strain  to  ground  is  50  per  cent, 
of  any  phase  voltage  and  the  voltage  across  any  two-phase 
terminals  is  70.7  per  cent,  of  full-phase  voltage. 


CHAPTER  IV 

THREE-PHASE  TRANSFORMATION  SYSTEM 

General  Principles. — In  considering  the  question  of  three-phase 
transformation  we  have  to  deal  with  three  alternating  e.m.fs.  and 
currents  differing  in  phase  by  120  degrees,  as  shown  in  Fig.  34. 

One  e.m.f.  is  represented  by  the  line,  A  B,  another  by  the 
line,  B  C,  and  the  third  by  the  line,  C  A.     These  three  e.m.fs. 


a 

\  1      /'"^^   2 


(i>)b 


Fig.  33. — Methods  of  grounding  two-phase  systems. 

and  currents  may  be  carried  to  three  independent  circuits 
requiring  six  wires,  or  a  neutral  wire,  or  common  return  wire  may 
be  used,  where  the  three  ends  are  joined  together  at  x.  The 
e.m.f.  phase  relations  are  represented  diagrammatically  by  the 
lines,  ax,  b  x,  and  c  x;  also,  A  B,  B  C,  and  C  A.  The  arrows 
only  indicate  the  positive  directions  in  the  mains  and  through 

39 


40 


ST  A  TIONA  R  Y  TEA  NSFORMERS 


the  windings;  this  direction  is  chosen  arbitrarily,  therefore,  it 
must  be  remembered  that  these  arrows  represent  not  the  actual 
direction  of  the  e.m.fs.  or  currents  at  any  given  instant,  but 
merely  the  directions  of  the  positive  e.m.fs.  or  currents  i.e.,  the 
positive  direction  through  the  circuit.  Thus,  in  Fig.  32a  the 
e.m.fs.  or  currents  are  considered  positive  when  directed  from 
the  common  junction  x  toward  the  ends,  ah  c. 

In  passing  through  the  windings  from  a  to  h,  which  is  the  direc- 
tion in  which  an  e.m.f.  must  be  generated  to  give  an  e.m.f.  acting 
upon  a  receiving  circuit  from  main  a  to  main  h,  the  winding,  a, 


Fig.  34. — Graphic  representation  of  three-phase  currents  and  e.m.fs. 

is  passed  through  in  a  positive  direction,  and  the  winding,  6,  is 
passed  through  in  a  negative  direction;  similarly  the  e.m.f.  from 
b  to  c,  and  the  e.m.f.  from  main  c  to  a.  The  e.m.f.  between  a  and 
b  is  30  degrees  behind  a  in  time-phase,  and  its  effective  value  is 


(14) 


2  E  cos  30°  =  ^3  E; 

where  E  is  the  value  of  each  of  the  e.m.fs.  a  b,  and  c. 

With  this  connection  the  e.m.f.  between  any  two  leads,  ab,b  c, 
or  a  c,  is  equal  to  the  e.m.f.  in  each  winding,  a  x,b  x,ov ex  multi- 
plied by  the  square  root  of  three. 

For  current  relations  we  see  in  Fig.  34  that  a  positive  current 
in  winding  1  produces  a  positive  current  in  main  A,  and  that  a 
negative  current  in  winding  2  produces  a  positive  current  in 
main  A ;  therefore,  the  instantaneous  value  of  the  current  in  main 


THREE-PHASE  TRANSFORMATION  SYSTEM      41 

A  is  I1  —  I2,  where  I^  is  the  current  in  winding  1,  and  1 2  is  the 
current  in  winding  2.  Similarly,  the  instantaneous  value  of  the 
current  in  main  B  is  /j  — ^3,  and  in  main  C,  it  is  I^  —  I^.  The 
mean  effective  current  in  main  A  is  30  degrees  behind  7^  in  phase; 
and  its  effective  value  is  the  square  root  of  three  times  the  current 
in  any  of  the  different  phases;  so  that  with  this  connection  the 
current  in  each  main  is  the  square  root  of  three  times  the  current 
in  each  winding. 

When  the  three  receiving  circuits  ah  c  are  equal  in  resistance 
and  reactance,  the  three  currents  are  equal;  and  each  lags  behind 
its  e.m.f.,  ah,h  c,  and  a  c,  by  the  same  amount,  and  all  are  120 
time-degrees  apart.  The  arrangement  shown  in  Fig.  34,  by  the 
lines,  a,  h,  and  c,  is  called  the  "Y"  or  star  connection  of 
transformers.  Each  of  these  windings  has  one  end  connected  to 
a  neutral  point,  x;  the  three  remaining  ends,  ah  c,  commonly 
called  the  receiving  ends,  are  connected  to  the  mains.  The  e.m.f. 
between  the  ends,  or  terminals  of  each  receiving  circuit  is  equal 
to  \/3  E,  where  E  is  the  e.m.f.  between  ax,  h  x,  and  c  x.  The 
current  in  each  receiving  circuit  is  equal  to  the  current  in  the 
mains,  ah  c. 

The  resistance  per  phase  cannot  be  measured  directly  between 
terminals,  since  there  are  two  windings,  or  phases  in  series. 
Assuming  that  all  the  phases  are  alike,  the  resistance  per  phase 
ir,  one-half  the  resistance  between  terminals.  Should  the  resist- 
ances of  the  phases  be  equal,  the  resistance  of  any  phase  may  be 
measured  as  follows: 

The  resistance  between  terminals  a  6  is : 

Resistance  of  a  h  =  R^  +  Ri. 
The  resistance  between  terminals  6  c  is: 

Resistance  of  b  c  —  R^-^-R^. 
The  resistance  between  terminals  a  c  is: 

Resistance  of  a  C  —  R3+R2. 
Therefore : 

_,      Res.  a  b  — Res.  b  c-|-Res.  a  c 
R3= 2 ' 

_,      Res.  6  c  —  Res.  a  c -j- Res.  o  6  ,,  ^. 

^i 2 '  (15) 

^r,      Res.  a  c  — Res.  a  6  -|-Res.  b  c 
R, 2 ■' 


42  STATIONARY  TRANSFORMERS 

The  method  of  connecting  three-phase  circuits  shown  in  Fig.  34, 
where  the  windings,  1,  2  and  3,  are  connected  in  series  a,t  A,  B 
and  C,  is  called  the  delta  connection.  In  this  connection  the 
e.m.f.  on  the  receiving  circuit  is  the  same  as  that  on  the  mains; 
and  the  current  on  each  receiving  circuit  is  equal  to  \/3  times 
that  in  any  winding,  or  \/3I,  where  /  is  the  current  in  1,2,  or  3- 

Assuming  that  all  phases  are  alike,  the  resistance  per  phase  is 

3 

equal  to  the  ratio  of  3  to  2  times  ^  the  resistance  between  A  and 

B.  In  a  delta  connection  there  are  two  circuits  between  A  and  C, 
one  through  phase  1,  and  the  other  through  phases  2  and  3  in 
series.  From  the  law  of  divided  circuits  we  have  the  joint 
resistance  to  two  or  more  circuits  in  parallel  is  the  reciprocal  of 
the  sum  of  the  reciprocals  of  the  resistances  of  the  several  branches. 

37? 
Hence,  -^  is  the  resistance  per  phase  R  being  the  resistance  of 

one  winding  with  two  others  in  parallel.  The  ohmic  drop  from 
terminal  to  terminal  with  current  /  in  the  line,  is 

3 
Ohmic  drop  =  2/X-R.  (16) 

To  transform  three-phase  alternating  current  a  number  of 
different  ways  are  employed.     Several  of  the  arrangements  are: 

1.  Three  single-phase  transformers  connected  in  star  or  in 
delta. 

2.  Two  single-phase  transformers  connected  in  open-delta  or 
in  tee. 

3.  One  three-phase  transformer  connected  in  star  or  in  delta. 
With  three  single-phase  transformers  the  magnetic  fluxes  in 

the   three  transformers   differ   in   phase   by   120  time-degrees. 

With  two  single-phase  transformers  the  magnetic  fluxes  in 
them  differ  in  time-phase  by  120  degrees  or  by  90  degrees  accord- 
ing to  the  connection  employed. 

With  the  three-phase  transformer  there  are  three  magnetic 
fluxes  differing  in  time-phase  by  120  degrees. 

The  single-phase  transformer  weighs  about  25  per  cent,  less 
than  three  separate  transformers  having  the  same  total  rating; 
its  losses  at  full  load  are  also  about  25  per  cent.  less. 

Two  separate  transformers,  V-connected,  weigh  about  the  same 
as  three  single-phase  transformers  for  the  same  power  transmitted ; 
the  losses  are  also  equal. 


THREE-PHASE  TRANSFORMATION  SYSTEM      43 

A  three-phase  transformer  weighs  about  16.5  per  cent,  less  than 
three  separate  transformers;  its  losses  are  also  about  16.5  per 
cent.  less. 

It  is  considered  that  for  transformation  of  three-phase  power 
the  three-phase  transformer  is  to  be  preferred  to  any  other  com- 
bination method. 

In  America  it  is  customary  to  group  together  single-phase 
transformers  for  use  on  polyphase  circuits,  while  in  Europe  the 
polyphase  transformer  is  almost  exclusively  employed.  How- 
ever, a  change  is  being  made  and  more  single-phase  transformers 
are  being  employed  in  Europe  than  formerly.  The  relative 
merits  of  three-phase  transformers  and  groups  of  three  single- 


B 

Fig.  35 


-Graphic  representation  of  three-phase  e.m.fs. 


phase  transformers,  in  the  transmission  and  distribution  of 
power,  form  a  question  that  is  capable  of  being  discussed  from 
various  standpoints. 

A  popular  argument  in  favor  of  the  three-phase  transformer  is 
the  greater  compactness  of  the  transformer  unit;  and  the  favorite 
argument  against  the  three-phase  transformer  is  that  if  it  becomes 
disabled  all  three  sides  of  the  system  must  be  put  out  of  service 
by  disconnecting  the  apparatus  for  repair;  whereas  if  a  similar 
accident  occurs  to  any  one  of  three  single-phase  transformers  in 
a  delta-connected  group,  the  removal  of  the  defective  trans- 
former only  affects  one  side  of  the  system,  and  two-thirds  of  the 
total  transformer  capacity  would  go  on  working.  The  relative 
merits  of  the  three-phase  transformer  and  the  combination  of 


44 


STATIONARY  TRANSFORMERS 


three  single-phase  transformers  that  may  be  employed  for  obtain- 
ing the  same  service  are  frequently  discussed  on  the  basis  of  the 
decrease  in  cost  of  the  several  types  of  transformers  with  increase 
in  rating;  and  on  such  basis  it  has  been  shown  that  the  three- 
phase  transformer  is  the  cheaper,  while  the  other  combinations 
are  more  expensive  on  account  of  requiring  an  equal  or  greater 
aggregate  rating  in  smaller  transformers.  It  should,  how- 
ever, be  borne  in  mind  that  a  three-phase  transformer  is  not, 
generally  speaking,  so  efficient  as  a  single-phase  transformer 
designed  along  the  same  lines  and  wound  for  the  same  total 
output. 


Fig.  36. — Vector  sum  of  effective  e.m.fs. 


It  is  shown  very  clearly  in  Fig.  35  that  a  connection  across  the 
terminals,  B  C,  x  E,  and  x  D,  will  receive  a  voltage  which  is  the 
resultant  of  two  e.m.fs.  differing  in  time-phase  by  120  degrees; 
or  the  result  from  adding  the  e.m.fs.  of  E^  and  E^  at  60  degrees, 
which  is  equivalent  to  E^  \/3. 

It  is  shown  in  Fig.  36,  where  one  phase  of  a  star-connected 
group  of  transformers  is  reversed,  the  resultant  e.m.f.,  x'  y' 
and  X  y,  is  equivalent  to  the  component  e.m.fs.,  x  c',  x  a' 
and  X  b,  X  a;  consequently  the  resultant  of  all  three  e.m.fs.  is 
zero.  This  is  in  accordance  with  Kirchhoff's  law  which  states 
that  where  an  alternating-current  circuit  branches,  the  effective 
current  in  the  main  circuit  is  the  geometric,  or  vector  sum  of  the 
effective  currents  in  the  separate  branches.  The  modifications 
of  the  fundamental  laws  appertaining  to  this  are  discussed  in 
many  books  treating  alternating  currents  in  theory,  and  the 
summary  given  here  is  for  the  purpose  of  comparison.     However, 


THREE-PHASE  TRANSFORMATION  SYSTEM      45 

it  is  noted  in  Fig.  36  that  the  phase  relations  between  o'  and  b', 
b'  and  c',  a  and  c  and  b  and  c  have  been  changed  from  120  degrees 
to  60  degrees  by  reversing  phases  b'  and  c.  The  pressure  between 
a  and  b  and  o'  and  c'  is  £'  \/S,  showing  their  phase  relations  to  be 
unchanged. 

For  example,  in  Fig.  36,  considering  only  secondary  coils  of 
three  single-phase  transformers  that  are  supposed  to  be  connected 
in  star,  but  as  a  matter  of  fact  connected  as  shown,  let  us  assume 
that  E  is  equal  to  100  volts: 

(a)  What  will  be  the  voltage  between  terminals  of  Ea,  E/, 
and  Ea,  Eb,  and  Ee  phases? 

(b)  What  will  be  the  voltage  between  terminals  a'  and  c',  and 
a  and  6? 

(c)  What  will  be  the  voltage  across  a'  y'  and  y'  c\  also  a  y 
and  y  6? 

(a)  The  voltage  acting  on  any  of  these  windings  is  equal  to 
E  v/3 

100X\/3  =  173.2  volts. 

The  voltage  acting  on  Ea  ,  Eb',  etc.,  is 

Ea ;^  X  173.2=0.577  X  173.2=  100  volts. 

v3 

(b)  The  voltage  between  terminals  a'  and  c',  or  a  and  b,  is  equal 
to  \/3  times  the  voltage  acting  on  Ea-  etc.,  or 

E\/3=  100 X  173.2=  173.2  volts. 

(c)  It  is  evident  that  the  two  e.m.fs.,  a'  x'  and  c'  x' ,  are 
equivalent  to  their  resultant,  y'  x' ,  which  is  equal  and  opposite  to 
b'  x' ;  the  dotted  lines,  a'  y'  and  y'  c',  are  equal  to  Ea  ,  Eb' ,  etc.,  at 
120  degrees  apart;  in  other  words, 

1 

E  =  a"  y',eic.,=      -X173.2 
Vo 

=  0.577X173.2  =  100  volts. 

In  Fig.  37  in  shown  a  diagram  of  three-phase  currents  in  which 
X,  y,  z  are  equal  and  120  degrees  apart,  the  currents  in  the  leads, 
o,  6,  c,  are  120  degrees  apart  and  each  equal  to  \/3  times  the  cur- 
rent in  each  of  the  three  circuits  X,  Y  and  Z. 


46 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


The  current  in  each  lead  is  shown  made  up  of  two  equal  compo- 
nents which  are  60  degrees  apart. 

As  an  example  showing  the  use  of  Fig.  35,  assume  a  circuit,  of 
three  single-phase  transformers  delta-connected.  What  will  be  the 


r  0 

Fig.  37. — Geometric  sum  of  three-phase  currents. 


Fig.  38. — Geometric  sum  of  e.m.fs.  at  any  instant  equal  to  zero. 

current  through  X-phase  winding  if  the  current  in  h  lead  is  500 
amperes? 

Since  one  component,  X,  has  in  the  lead  the  same  sign  as  it  has 


THREE-PHASE  TRANSFORMATION  SYSTEM      47 

in  its  own  transformer  winding,  and  the  other  component,  Y,  has 
in  the  lead  the  opposite  sign  to  that  which  it  has  in  its  own  trans- 
former winding,  X,  is  represented  in  lead  by  the  same  vector  as  in 
its  own  transformer  winding;  while  the  other  component,  F,  is 
represented  in  the  lead  by  a  vector  180  degrees  from  that  which 

represents  it  in  its  own  circuit,  therefore,  X   =~^  500. 

v3 

The  instantaneous  values  of  the  currents  in  any  one  wire  of  a 
three-phase  system  are  equal  and  opposite  to  the  algebraic  sum 
of  the  currents  in  the  other  two  sides.  Therefore,  the  algebraic 
sum  of  e.m.fs.  or  currents  at  any  instant  is  equal  to  zero.  This 
fact  is  shown  in  Fig.  38,  the  geometric  sum  of  the  three  lines, 
A,  B,C,  being  equal  to  zero  at  any  instant. 

Single-phase  transformers  may  be  connected  to  a  three-phase 
system  in  any  of  the  following  methods: 

Delta-star  group  with  a  delta-star. 

Star-star  group  with  a  star-star. 

Delta-delta  group  with  a  delta-delta. 

Star-delta  group  with  a  star-delta. 

Delta-star  group  with  a  star-delta. 

Delta-delta  group  with  a  star-star. 

It  must,  however,  be  remembered  that  it  is  impossible  to 
connect  the  following  combinations,  because  the  displacement  of 
phases  which  occurs,  when  an  attempt  is  made  to  connect  the 
secondaries,  will  result  in  a  partial  short-circuit. 

Delta-star  with  a  star-star. 

Delta-delta  with  a  star-delta. 

Delta-star  with  a  delta-delta. 

Star-delta  with  a  star-star. 

As  is  well  known  there  are  four  ways  in  which  three  single- 
phase  transformers  may  be  connected  between  primary  and 
secondary  three-phase  circuits.  The  arrangements  may  be 
described  as  the  delta-delta,  star-star,  star-delta,  and  delta-star. 

In  winding  transformers  for  high  voltage  the  star  connection 
has  the  advantage  of  reducing  the  voltage  on  an  individual  unit, 
thus  permitting  a  reduction  in  the  number  of  turns  and  an 
increase  in  the  size  of  the  conductors,  making  the  coils  easier  to 
wind  and  easier  to  insulate.  The  delta-delta  connection  never- 
theless has  a  probable  advantage  over  the  star-delta  arrangement, 
in  that  if  one  transformer  of  a  group  of  three  should  become 
disabled,  the  two  remaining  ones  will  continue  to  deliver  three- 


48 


STATIONARY  TRANSFORMERS 


phase  currents  with  a  capacity  equal  to  approximately  two- 
thirds  of  the  original  output  of  the  group.  Fig.  39  shows  a  delta- 
delta  arrangement.  The  e.m.f.  between  the  mains  is  the  same 
as  that  in  any  one  transformer  measured  between  terminals.  The 
current  in  the  line  is  \/3  times  that  in  any  one  transformer 
winding. 

Each  transformer  must  be  w^ound  for  the  full-line  voltage  and 
for  57.7  per  cent,  line  current.  The  greater  number  of  turns  in 
the  winding,  together  with  the  insulation  between  turns,  neces- 
sitate a  larger  and  more  expensive  coil  than  the  star  connection. 

For  another  reason  the  delta-delta  connection  may  be  preferable 


Fig.  39. — Delta-delta  connection  of  transformers. 


to  the  star,  inasmuch  as  the  arrangement  is  not  affected  even 

though  one  transformer  may  be  entirely  disconnected,  in  which 

case  it  is  practically  assumed  that  the  two  remaining  transformers 

2 
have  exactly  a  carrying  capacity  of  85  per  cent,  of  ^  =  0.567. 

In  a  delta  connected  group  of  transformers  the  current  in  each 

phase  winding  is  -y='   I  being  the  line  current,  and  if  a  phase 

displacement  exists,  the  total  power  for  the  three  phases  will  be 
V3X^X/XCos^.  (17) 

Assume  the  voltage  between  any  two  mains  of  a  three-phase 
system  to  be  1000  volts;  the  current  in  the  mains,  100  amperes, 
and  the  angle  of  time-lag,  45  degrees.  What  will  be  the  e.m.f. 
acting  on  each  phase,  the  current  in  each  phase,  and  the  output? 

The  e.m.f.  on  each  phase  of  a  delta-connected  group  of  trans- 
formers is  the  same  as  that  across  the  terminals  of  any  one  trans- 


THREE-PHASE  TRANSFORMATION  SYSTEM      49 

former.     The  line  current  is  \/3  times  that  in  each  transformer 
winding,  or  a/3X  57.7  =  100  amperes,  therefore  the  current  in 

each  phase  is  100  X  -y^  =  57.7  amperes.    The  output  being  a/3  E  I- 

Cos  d  = 

1. 732 X 1, 000 X 100 X.7 1  =  123  kw.  approx. 

In  the  star-star  arrangement  each  transformer  has  one  terminal 
connected  to  a  common  junction,  or  neutral  point;  the  three 
remaining  ends  are  connected  to  the  three-phase  mains. 

The  number  of  turns  in  a  transformer  winding  for  star  connec- 
tion is  57.7  per  cent,  of  that  required  for  delta  connection  and  the 


-1000- 


-1000- 


h — 677 ^     H 577 — ^ 


-1000- 


577- 


-67.7-> 


rron 

57.7 


immMj 


-MO- 


nnjn 


^57.7- 


-100- 


100 

Fig.  40. — Star-star  connection  of  transformers. 


cross-section  of  the  conductors  must  be  correspondingly  greater 
for  the  same  output.  The  star  connection  requires  the  use  of 
three  transformers,  and  if  anything  goes  wrong  with  one  of  them, 
the  whole  group  might  become  disabled. 

The  arrangement  shown  in  Fig.  40  is  known  as  the  "star"  or 
"Y"  system,  and  is  especially  convenient  and  economical  in 
distributing  systems,  in  that  a  fourth  wire  may  be  led  from  the 
neutral  point  of  the  three  secondaries. 

The  voltage  between  the  neutral  point  and  any  one  of  the 

outside  wires  is  — ^  of     he  voltage  between  the   outside  wires, 


namely 


V3 


1000 X-7-  =  1,000X0.577  =  577  volts. 

The  current  in  each  phase  of  a  star-connected  group  of  trans- 
formers is  the  same  as  that  in  the  mains. 

Fig.  41   shows  a  star-star  connection  in  which  one  of  the 

4 


50 


ST  A  TIONARY  TRANSFORMERS 


secondary  windings  is  reversed.  It  may  be  noted  that  the  phase 
relations  of  phase  c  have  changed  the  relations  of  a  c  and  b  c  from 
120  degrees  to  60  degrees  by  the  reversal  of  one  transformer 

connection.     The  resultant  e.m.fs.,  ac  and  be,  are  each  — ^  = 

^3 


-1000 — > 
-1000- 


UWUq^ 


< 1000- 


mw 


Fig.  41. — Star-star  connection  of  transformers,  one-phase  reversed. 

57.7,  but  in  reality  should  be  1 00  volts — the  voltage  between  a  and  b 
is  57.7  X\/3  =  100.  In  star-connecting  three  single-phase  trans- 
formers it  is  quite  possible  to  have  one  of  the  transformers 
reversed  as  shown. 


-577- 


UM^M^ 


IM2MMJ 


000 

'«^7.?> 

2 

000" 

<-57.7-> 

a 

000' 

<-57.7-> 

■«-57 

.7-> 

^57.7-> 

Fig.  42. — Star-delta  connections  of  transformers. 


In  the  star-delta  arrangement  shown  in  Fig.  42  the  ratio  of 

transformation  is  — ;^'    or  0.577  times  the  ratio  of  secondary  to 
\/3 

primary  turns,  and  the  e.m.f.  acting  on  each  secondary  circuit  is 

the  same  as  that  between  the  mains. 


THREE-PHASE  TRANSFORMATION  SYSTEM      51 

For  example,  let  us  assume  that  1000  volts  are  impressed  on 
the  primary  mains.  The  voltage  between  any  two  secondary 
mains  is  the  same  as  that  generated  in  each  transformer,  namely, 

57.7  volts,  or  100  X  —y^  =57.7  volts. 
\/3 


Primary 


Fig.  43. — Delta-star  four-wire  connection  of  transformers. 

Fig.  41  shows  a  delta-star  connection  using  three  single-phase 
transformers.  From  the  neutral  point  of  the  secondary  star 
connection,  a  wire  may  be  brought  out,  serving  a  purpose  similar 
to  that  of  the  neutral  wire  in  the  three-wire  Edison  system,  it 


-1000- 


-1000- 


lOOO- 


-100 


-100- 


-100- 


FiG.  44. — Open-delta  or  "V"  connection  of  transformers. 


being  without  current  when  the  load  is  balanced.  The  ratio  of 
transformation  for  the  delta-star  arrangement  is  \/3,  or  1.732 
times  the  ratio  of  secondary  to  primary  turns. 

The  advantage  of  this  secondary  connection  lies  in  the  fact 


52 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


that  each  transformer  need  be  wound  for  only  57.7  per  cent.,  of 
the  voltage  on  the  mains. 

In  the  arrangement,  commonly  called  "V"  or  "open-delta" 
the  voltage  across  the  open  ends  of  two  transformers  is  the 
resultant  of  the  voltages  of  the  other  two  phases;  see  Fig.  44. 
This  method  requires  about  16  per  cent,  more  transformer  capac- 
ity than  any  of  the  previous  three-phase  transformations  shown, 
assuming  the  saijie  efficiency  of  transformation,  heating,  and 
total  power  transformed. 


B 

I 
-1000- 


-1000- 


1000- 


-1000- 


-1000- 


< ^100- 


mmmJ 


KO 


Fig.    45. — "  V "  connection    of    transformers    with    secondary    windings 
connected  in  opposite  directions. 

In  comparing  the  kv-a  capacity  of  two  single-phase  trans- 
formers connected  in  open  delta,  with  three  similar  transformers 
connected  in  delta,  the  kv-a  capacity  is  approximately  1  -^  ^^  = 
58  per  cent.  This  is  due  to  the  fact  that  for  the  delta  connection 
the  current  and  voltage  of  each  transformer  are  in  phase  with 
each  other,  while  for  the  open-delta  connection  the  current  and 
voltage  of  each  transformer  are  30  degrees  out  of  phase  with 
each  other. 

With  the  open-delta  method  a  slight  unbalancing  may  exist, 
due  to  the  different  impedances  in  the  middle  main  and  the  two 
outside  mains,  the  impedance  in  the  middle  main  being  the 
algebraic  sum  of  the  impedances  in  the  two  outside  mains. 

The  open-delta  arrangement,  (where  the  primary  is  connected 
like  that  shown  in  Fig.  45)  is  in  every  respect  equivalent  to  the 
open-delta  connection  represented  in  Fig.  42.  The  primaries  are 
connected  in  a  reverse  direction,  or  180  degrees  apart  in  phase 
with  the  secondary. 


THREE-PHASE  TRANSFORMATION  SYSTEM      53 

The  vector  diagram  shows  the  changed  phase  relations  of 
primary  to  secondary.  By  connecting  two  single-phase  trans- 
formers in  the  opposite  direction,  that  is  to  say,  connecting  the 
secondary  like  that  of  the  primary,  and  the  primary  like  that  of 
the  secondary,  we  obtain  the  same  transformation  characteristics. 

Like  that  of  the  open-delta  arrangement  the  tee  method 
requires  only  two  single-phase  transformers. 

As  regards  the  cost  of  equipment  and  the  e^ciency  in  opera- 
tion the  tee  arrangement  is  equal  to  either  the  open-delta,  the 
star  or  the  delta  methods. 

The  tee  arrangement  is  represented  in  Fig.  46.  The  end  of  one 
transformer  is  connected  to  the  middle  of  the  other. 


1000         > 

<    1000 

1000 

J. 

Um] 

)00 

^imsiSL 

w 


-100- 


-100 


-100- 


.^<^ 


"60^ 


X       86.6 


-^0 


s^ 


Fig.  46. — Tee  or  "T"  connection  of  transformers. 


The  number  of  turns  on  a  6  is  ^    ■    =1.16  times  the  number  of 

v3 

turns  on  x  c.     Its  ability  to  maintain  balanced  phase  relations  is 

no  better  than  the  open-delta  arrangement,  and  in  no  case  is 

it  preferable  to  either  the  star  or  delta  methods  of  connecting 

three  single-phase  transformers. 

It  is  worthy  of  note  that  the  transformer  which  has  one  end 

tapped  to  the  middle  of  the  other  transformer  need  not  be  designed 

for  exactly  ^^^  =  86.6  per  cent,  of  the  voltage;  the  normal  volt- 

age  of  one  can  be  90  per  cent,  of  the  other,  without  producing  det- 
rimental results. 

Another  three-phase  combination  is  shown  in  Fig.  47.  In  this 
case  it  is  assumed  that  the  three  single-phase  transformers 
were  originally  connected  in  star  at  oA,  oB  and  oC  as  shown  by 
dotted  line  in  the  vector  diagram. 


54 


STATIONARY  TRANSFORMERS 


To  change  the  transformation  to  the  combined  system  of  the 
star-delta,  the  end  of  winding  oB  is  connected  with  the  point  o' 
of  the  phase  oA,  and  the  end  0  of  the  phase  oC  with  the  point 
o"of  the  phase  oB  so  that  the  vector  oB  becomes  o'E'  and  oC 
becomes  o"C'.  The  length  of  the  three  vectors  is  proportional 
to  the  number  of  coils  per  phase,  all  coils  having  the  same  num- 


mum      Kwwwl      rmtm 


f&fc 


iX\  ca 


-E 


-E-, 


^^ 


Fig.  4". — Delta  connection  with  50  per  cent,  of  winding  reversed  to  obtain 
another  phase  relation  for  maximum  voltage. 

ber  of  turns.     The  end  o  of  phase  oA  is  connected  to  the  point 
of  the  phase  o"C\ 

Going  over  the  list  of  common  three-phase  connections  we  find 
there  are  only  four  delta-delta  systems  in  common  use,  these  being 
shown  in  Fig.  48. 


Q     kit]    Uj 


Q-O  n 


Fig.  48. — Common  delta  connections. 


These,  and  a  combination  of  them  may  be  so  arranged  as  to 
give  not  less  than  sixteen  different  changes;  all  these  changes 
being  given  in  Fig.  49. 

Taking  away  one  transformer  of  each  of  the  above  combina- 
tions we  find  open-delta  connections  like  those  given  in  Fig.  50. 

On  carefully  looking  over  the  eighteen  different  delta-delta 
combinations  given  in  the  above  figures,  it  will  be  noted  that  the 
first  ten  represent  changes  of  one  or  two  of  the  transformers  while 


THREE-PHASE  TRANSFORMATION  SYSTEM      55 

the  remaining  eight  have  all  their  secondaries  connected  in  a 
direction  opposite  to  their  respective  primary  windings. 

There  are  also  four  common  star-star  connections  in  general  use, 
these  being  shown  in  Fig.  51. 

Like  the  delta-delta,  these  four  star-star  connections  can  be 
arranged  to  give  sixteen  different  combinations  as  will  be  seen 
from  Fig.  52. 

Continuing  further  through  the  series  of  three-phase  connec- 
tions we  come  to  delta-star  or  star-delta  combinations.  The 
star-delta  and  delta-star  in  common  use  are  given  in  Fig.  53. 

iL  ijj  iij   £b=ur4i    lAIAj    uAi'u  LninJ  crtru 

m  f=^  f^  w^  ""f^  w" 


I 


aJyi  cyp^  ^^^#t^  ^Yh^  ^\^  ^Y^\^ 

^^YJY^      Cld~VP       n.^iH     CY?T^ 

Fig.  49. — Uncommon  delta  connections. 

The  uncommon  systems  of  star-delta  transformer  connections 
are  shown  in  Fig.  54.  These  may  be  changed  about  to  delta- 
star  as  desired,  thus  making  twice  the  number.  It  must  be  re- 
membered, however,  that  none  of  them  can  be  changed  about 
from  one  set  of  combinations  to  another. 

POLARITY  IN  THREE-PHASE  TRANSFORMER  CONNECTIONS 

It  is  customary  for  all  transformer  manufacturers  to  arrange 
transformer  windings  so  that  left-  and  right-hand  primary  and 
secondary  leads  are  located  the  same  for  all  classes  and  types.  It 
is  not,  however,  customary  for  operating  companies  and  others 
to  do  so  after  a  transformer  has  been  pulled  to  pieces.  The  major- 
ity seems  to  follow  manufacturer's  prints  and  wiring  diagrams  of 
transformer  connections  coming  from  the  factory,  all  of  which 
are  assumed  to  have  the  same  relative  direction  of  primary  and 


56  STATIONARY  TRANSFORMERS 

secondary  windings,  thus  permitting  similarly  located  leads  leav- 
ing the  transformer  tank  to  be  connected  together  for  parallel 
operation  if  desired  without  the  necessity  of  finding  the  polarity. 
Large  and  moderate-sized  high-voltage  transformers  are  rarely 
used  for  single-phase  service.  They  may  be  of  single  or  three- 
phase  design  but  they  are  used  almost  exclusively  on  three-phase 
systems,  and  connected  in  star  or  delta  or  a  combination  of  the 

^  W    U-b    b^    d-\j     LrSj 

rvp  rvi  rv^  ^T^  ^Vt^  P^ 

Fig.  50. — Uncommon  open-delta  connections. 

two  methods.  Single-phase  units  in  large  and  medium  and  small 
sizes  (6000  to  0.5  kv-a)  are  very  common.  They  afford  a  better 
opportunity  for  different  polarities  than  three-phase  units,  which 
are  also  made  in  large  and  medium  and  small  sizes  (14,000  to 
1.0  kv-a). 

The  delta  and  star  methods  of  connections  generally  referred 
to  as  "  conventional "  are  understood  to  have  all  the  primary 
and  secondary  windings  wound  in  opposite  directions  around 

uJ  u  kJ    u  uJ   uJ        Urrzi    b::^      Lj    I — i  I — i 
cri_rn_r|    p  p   p        n  rj    n      |n_pi_p 

Fig.  51. — Common  star  connections. 

the  core.  This  conventional  method  is  not  always  followed  as 
problems  arise  in  every-day  practice  showing  that  it  is  not  always 
carried  out. 

Three  single-phase  transformers  or  one  three-phase  trans- 
former may  have  their  windings  arranged  in  the  following  manner: 

(1)  The  three  primary  and  secondary  windings  wound  in  the 
same  direction — positive  direction. 

(2)  The  three  primary  and  secondary  windings  wound  in  the 
same  direction — negative  direction. 


THREE-PHASE  TRANSFORMATION  SYSTEM      57 

(3)  The  three  primary  windings  wound  in  opposite  direction 
to  the  secondary  windings — positive  direction. 

(4)  The  three  primary  windings  wound  in  opposite  direction 
to  the  secondary  windings — negative  direction. 

(5)  One  primary  winding  of  the  group  of  three  may  be  wound 
opposite  to  the  remaining  two  primaries  and  the  three 
secondaries — positive  direction. 

J  d  u   u  u  u  u  J  u  uuii  L  u  u  cHx-J 
n  r|  p    n  q  n    p  rj  n    "^^-p-n    H  pi  ^    fhR-P 

Lrbrb  LrhnJ  L  b  u  Lrd-J   J  f  J  u  u  u  L 
(rjJrL_r^   n  rj  n    p_p_p   n  p  p    r\-p-n  n  r|  n 

LrrhJ  JUL     J  L  J  Uxra 

r^  p  p    r^-p_o       p  rj  p  n  p  n 

Fig.  52. — Uncommon  star  connections. 

(6)  One  primary  winding  of  the  group  of  three  may  be  wound 
opposite  to  any  of  the  remaining  two  primaries  and  the 
three  secondaries — negative  direction. 

(7)  Two  primary  windings  of  the  group  of  three  may  be 
wound  opposite  to  the  one  remaining  primary  and  three 
secondary  windings — positive  direction. 

WwJ     k/wJ       Vf*i  W^       WmI        IwmJ  UwJ       Ivwl        Iwyj  Ivwl        kwj       M*\ 

ry^"^    (:^i_iq_r|        ^^i-^    ^     n  n  n 

Fig.  53. — Ck)mmon  star-delta  connections. 

(8)  Two  primary  windings  of  the  group  of  three  may  be 
wound  opposite  to  the  one  remaining  primary  and  the 
three  secondary  windings — negative  direction. 

(9)  One  unit  may  have  its  primary  and  secondary  windings 
different  to  the  two  remaining  units,  as: 

(a)  The  unit  on  the  left — positive  direction. 

(6)  The  center  unit — positive  direction. 

(c)   The  unit  on  the  right — positive  direction. 


58 


STATIONARY  TRANSFORMERS 


(10)  One  unit  may  have  its  primary  but  not  the  secondary 
windings  different  to  the  remaining  two  units,  as  (9) 
but  in  the  negative  direction. 

(11)  Two  units  may  have  their  primary  and  secondary  wind- 
ings different  to  the  remaining  unit,  as: 

(a)  The  left  and  center  units — positive  direction. 

(b)  The  right  and  center  units — positive  direction. 

(c)  The  left  and  right  units — positive  direction. 

(12)  Two  units  may  have  their  primary  but  not  secondary 
windings  different  to  the  one  remaining  unit,  as  (11) 
but  in  the  negative  direction. 


U^     U/w     Iv\aI 

rp  PL_n 

a 
U/sJ    U/vJ    Iv>>a| 


U/s/J      U^       l\/\A 

ryen 


U/M  U/vJ  IwAl 


Iwj  IwJ  L/j     Lj  L/J  u/J 


/ 


iJj  uJ    iL       \it--LLr-\h         uil   uj   lij      U-rHljriwJ 


^ 


nnn    n  p  n 


,  I  I  I, 

U/SaI        P^VsI  I/WM 


UvvrhJ^*lvvg    '  Uv/J  '  LvUrh — I 
1^^     i*^^    i'^'*^       f*^    1*^^    ('^^ 


Fig.  54. — Uncommon  star-delta  connections. 

Transformers  of  the  same  rating  and  of  the  same  make  are  as  a 
rule  assumed  to  have  the  same  polarity,  impedance  and  ratio  of 
transformation.  In  all  cases  where  transformers  are  not  of  the 
same  make  it  is  advisable  that  the  secondary  connections  be 
subjected  to  polarity  tests  before  connecting  them  in  delta  or 
star.     The  mistakes  which  can  be  made,  are: 

(1)  One  or  more  reverse  windings. 

(2)  Internal  leads  crossed. 

(3)  Where  transformers  are  located  some  distance  apart, 


THREE-PHASE  TRANSFORMATION  SYSTEM      59 


A   J,   c 


^    B    (^  ^        B        q         ^        B         0 


UwV^rJ       Lnaa/J        IvnaaI  UaaaJ        U>na^       Ua/vsI  bvvAAl     [aaAaI      'naa^        l^AA'^l     U»'Vv>J       bs/\AN 

rojrn-^    rp  r^  pp   rv^^^g^  rp  r^  pp 


a    "     c 
Aa 


I  Aa  a 

Fig.  55. — Three-phase  polarity  combinations. 


A  B 


V/^/^A         '\f\^-y\  ^AA/<J 


A 


l/V^      2 


/\/^       r^^ 


n 


>x 


B     0 


B         A  ^ 


UiVnaI       UaatJ      JwvvI  |aa/vJ   ^Ka^ 


/\/\ 


ca 


Q 


l/N/^    2  >^^^^      3 


wvJ 


a     b 


1    ,8 


,1^ 


WV\I         Uaa/N         V\A/\I  l\A/vJ        U^/wi        Ka/v/nJ  |a/V/N/sI 


i 


l^^xx     2  xwv     3 


B 


n 


ca 


2  >wv       3 


f^"^  ^/^V^         ^l'^'^ 


a 


2%      3 


8 


Fig.  56. — ^Phase  relations  and  rotation. 


60 


STATIONARY  TRANSFORMERS 


and  where  connections  are  made  at  some  distance, 
the  leads  may  become  crossed. 
The  reversal  of  two  leads  of  either  the  primary  or  secondary 
will  reverse  the  polarity,  this  being  (so  far  as  the  external  connec- 
tions are  concerned)  the  same  as  reversing  one  winding. 

Reversing  the  line  leads  of  a  star-star,  delta-delta,  star-delta 
or  delta-star  will  not  reverse  the  polarity  since  the  transformer 
leads  themselves  must  be  changed  in  order  to  make  the  change 
in  polarity.     This  should  be  particularly  noted  when  parallel 


^ 


Time-Phase  Angle  Primary  Windings'  Secondary  Windings 

Fig.  57. — Complete  cycle  of  polarity  changes. 

operation  is  desired,  for,  though  the  phase  relations  of  two  trans- 
former groups  may  be  the  same  parallel  operation  might  be  impos- 
sible (see  Fig.  55) . 

The  effect  of  a  reversal  of  one  or  two  primary  windings  is  not 
the  same  for  the  four  systems  of  star  and  delta,  but  is : 

For  Star-star:  The  reversal  of  one  or  two  primary  windings 
will  not  produce  a  short-circuit,  but  will  produce  a  difference  in 
phase  relations  and  voltages.  The  maximum  voltage  will  not 
be  greater  than  the  line  voltage  (see  Fig.  58). 

For  Delta-delta:  The  reversal  of  one  or  two  primary  windings 
will  immediately  produce  a  short-circuit  when  the  secondary 


THREE-PHASE  TRANSFORMATION  SYSTEM      61 

delta  is  closed.     The  maximum  voltage  difference  will  be  2E 
or  double-line  voltage  (see  Figs.  59  and  60). 

For  Star-delta:  The  reversal  of  one  or  two  primary  windings 
will  immediately  produce  a  short-circuit  when  the  secondary 
delta  is  closed.  The  maximum  voltage  difference  at  that  point 
which  closes  the  delta  will  be  2E  or  double-line  voltage. 


Reveraed 


a- A 


(b) 


Opposite 
polarity 


B-b 


a- A 


Reversed 


Fig.  58. — Three-phase  polarity  difficulties. 

For  Delta-star:  The  reversal  of  one  or  two  primary  windings 
will  not  produce  a  short-circuit  on  the  secondary  side  when  the 
star  is  made.  The  maximum  voltage  difference  will  be  E  or 
line  voltage,  but  voltages  and  phase  relations  will  be  unequal. 

The  thick,  black  lines  shown  in  Figs.  55,  56,  57,  58,  59  and  60 
represent  secondary  windings. 

Fig.  57  gives  all  the  possible  star  and  delta  polarity  combina- 
tions, or,  sixteen  as  already  explained. 


62 


STATIONARY  TRANSFORMERS 


Wrong 
Connection 


Correct 
Connection 


JvvA/V-i-A/WV — LAA^AJ 


■Reversed 


J'^N/'X-,. 


'z? 

^       a 
(a) 


n 


2E 


^  (a) 


e ,*, — e > 


a-b-c 

.A. 


kvvAl      ^v^^N      l^/vv^|  6 


A-B-C 
E 


B-C-A 


a-A-B 


i?  Vi__: 


arr ' 


-2E H 


Z AC       K'SA,^      UaaaI        IvvvJ/ 


(J 


Fig.  59. — Three-phase  polarity  difficulties. 


THREE-PHASE  TRANSFORMATION  SYSTEM      63 

Fig.  58  shows  the  effects  of  a  reversed  winding  or  transformer. 
Unlike  the  delta-delta  or  star-delta  no  short-circuit  exists  when 
secondary  connections  are  completed. 

Fig.  59  (a)  and  (6)  shows  wrong  and  right  method  of  connecting 
the  delta  secondary  when  one  winding  is  reversed.  Across  Cx 
of  (a)  double-line  voltage  is  obtained  thus  making  the  delta 
secondary  impossible   and   only  operative   when  connected  as 


Correct 
Connection  „ 

q  g  Reversed  . 

a-b-e 


C-A-B 


Reyersed 


Fig.  60. — Three-phase  polarity  diflSculties  with  two  transformers  reversed. 

shown  at  (b) .     Both  (a)  and  (b)  have  their  primary  and  secondary 
windings  wound  in  opposite  directions,  as  also  (h)  and  (i). 

Fig.  60  (a)  and  (b)  also  show  a  correct  and  incorrect  way  of 
connecting  the  windings  in  delta  when  two  transformers  of  a 
group  of  three  are  reversed.  As  before,  double  voltage  or  2E  is 
the  maximum  difference  in  voltage  which  can  exist.  Both  (a) 
and  (6)  and  (/),  (g)  and  (h)  are  assumed  to  have  their  primary  and 


64  STATIONARY  TRANSFORMERS 

secondary  windings  of  the  same  polarity.  The  primaries  and 
secondaries  of  (c)  and  (d)  are  assumed  to  have  opposite  polarity. 

Fig.  57  may  also  have  parallel  operating  polarity  combinations 
represented  as  a  complete  cycle  of  changes. 

From  the  above  it  is  evident  that  from  the  four  systems  of 
delta-delta,  delta-star,  star-star  and  star-delta,  we  obtain  48 
different  combinations. 

Delta  -  Delta  6      a 6      a      c a      c      I c      a     a c      c 

VAV    AVAVAVAVA 

V    /    \     V  acccbbbaabcbab 


a    c       a    c 


Delta -star  c  b  b  a  a  c  a   b  c 

V  Vv.'^>-'  <  >"  O'  '-<  >'  "-< 


b 

star  -  star 
a        b 


c         b     b     b        a     a     a         c     c     b        c     b 


c         a    c 


YX      YAYAYAYAYA 

IX\  a      c       a     c      b       c     b     a       b    a    a       c      b     b       a 


c     c        b 


Star  -  Delta 


c  b  a  c  b  a  a  b  c  a  b 

^  >    c<]  >»  „<  E>.    ,<]  [>»    „<]  [>c    ,<3 

a  a  b  b  c  c  c  c  b  b  « 


PARALLEL  CONNECTIONS 

After  we  have  gotten  through  with  these  various  combinations 
our  next  difficulty  is  in  knowing  just  which  one  combination  can 
be  operated  in  parallel  with  another.  With  the  primary  and 
secondary  windings  arranged  as  is  usual  in  practice,  not  less  than 
eight  different  parallel  combinations  may  be  made  (although 
sixteen  are  possible)  these  being  given  in  Fig.  61.  Other  inter- 
esting series  of  parallel  combinations  are  given  in  Figs.  62,  63, 
64  and  65. 

The  problem  of  paralleling  systems,  no  matter  whether  they 
be  generating  or  transforming,  resolve  themselves  into  such 
factors  as  equal  frequency,  equal  voltages  which  must  be  in  time- 
phase,  etc.  The  manufacturer  is  responsible  for  a  fair  part  of 
the  troubles  of  operating  engineers  from  the  apparatus  point  of 


THREE-PHASE  TRANSFORMATION  SYSTEM      65 

view,  but  the  engineer  himself  shoulders  the  major  portion  of 
responsibility  so  far  as  the  operating  life  of  the  apparatus  is 
concerned  whether  the  apparatus  be  operated  singly  or  in  multi- 
ple.    The  manufacturer  can,  and  endeavors,  to  design  apparatus 


J  U  U  U  u  U  UU 


da- 


U  ul  U  LniAj 

ryyi  rvjYi        Q_q-q  g  q  n       ^Y^  ^^\^V^ 

lAIAj  uUAj         c?iira  uAJAj        Lrb-ta  lAm 
^"^  LI      ^'^       III        ^"^ 

(g)  ih) 

Fig.  61. — Three-phase  parallel  combinations  in  common  practice. 

and  deliver  same  to  the  customer  such  that  identical  polarity, 
equal  capacity  and  equal  voltages  are  obtained  and  satisfactory 
parallel  operation  made  possible.  However,  one  particular 
manufacturer  cannot  be  held  responsible  for  the  methods,  etc., 

J  d  J  L  Lj  L  lAIAj  iF^4s      dxhJ  Lrtrb 

'  la')  (b'y  (o'J 

uAirU    crtte  lAIAu    cbt-ra  lii        LniAj    iL  lii  lL 

1    '     (d')  '    '  re'/       '  r/'; 

u  u  u  Lrhm  J  J  J  L  L  u 

Fig.  62. — Common  three-phase  parallel  combinations. 


of  another  manufacturer  who  may  design  the  same  size  and  class 
of  apparatus  which  differs  in  ratio  of  high-voltage  to  low-voltage 
turns,  in  impedance  and  also  in  its  polarity. 

The  fault  and  responsibility,  generally  speaking,  rests  with  the 


66 


STATIONARY  TRANSFORMERS 


engineers  themselves.  Large  and  moderate  size  transformers 
are  most  always  operated  in  parallel  and  consequently  when  order- 
ing other  transformers  for  the  purpose  of  parallel  operation,  and 
when  the  order  is  from  a  different  maker,  certain  specifications 
should  be  covered  if  the  delta  circulating  currents  are  to  be 
avoided  and  the  apparatus  is  to  be  satisfactorily  operated  in 
parallel. 

In  the  parallel  operation  of  delta  and  star  systems,  two  main 
factors  must  be  kept  in  mind  after  due  consideration  has  been 
given  to  the  design  of  the  apparatus  to  be  placed  in  parallel. 
These  are: 

cj-w-ft  U  u*U      u  J  u  u  u  u      Lrd-Q  J  U  ul 
c:i_pi_r|  p  n  p        rypgL-n  rp  i^  <p        c^/rua  c::bfdtt-j:3 


•^^.w    m^^^Tff  r^_,.ftn 


tru        pu  iL  [T^T3 


Fig.  63. — Uncommon  three-phase  parallel  combinations. 

(a)  No  condition  is  possible  whereby  apparatus  connected  in 
delta  on  both  the  high-voltage  and  low- voltage  sides  can  be  made 
to  parallel  with  another  piece  of  apparatus  connected  either  in 
delta  on  the  high-voltage  side  and  star  on  the  low-voltage  side  or 
in  star  on  the  high-voltage  side  and  delta  on  the  low-voltage  side. 
However,  a  condition  is  possible  whereby  apparatus  connected 
in  delta  on  the  high-voltage  side  and  star  on  the  low-voltage  side 
can  be  made  to  parallel  with  several  combinations  of  another  piece 
of  apparatus  connected  in  star  on  the  high-voltage  side  and  delta 
on  the  low-voltage  side. 

(b)  Some  combinations  of  one  group  of  apparatus  or  one  poly- 
phase unit  connected  exactly  the  same  cannot  be  made  to  operate 
in  parallel,  as,  for  instance,  a  delta-star  may  have  a  combination 
that  will  not  parallel  with  another  polyphase  unit  or  group  of 
apparatus  connected  delta-star. 


THREE-PHASE  TRANSFORMATION  SYSTEM      67 

As  already  stated,  to  secure  perfect  parallel  operation  the  two 
sets  of  apparatus  should  have  exactly  the  same  ratio  of  trans- 
formation, the  same  IR  drop  and  the  same  impedance  drop. 
Too  little  notice  appears  to  be  taken  by  operating  engineers  of 
the  right  size  and  type,  identical  characteristics,  and  the  ability 
of  transformers  to  share  equal  loads  when  operated  in  parallel. 

Even  though  these  conditions  are  obtained  it  will  not  follow 
that  parallel  operation  is  secured  nor  possible.  For  instance, 
assuming  conditions  are  such  that  the  characteristics  of  two  sets 
of  apparatus  are  identical  and  that  they  have  exactly  the  same 


LrbnJ  nhJ-b]      zM:ki  cWn     LtnJ  cJ-d-t 


(a'")  '      '(6"r      '  '     '(c'")"  ' 

Lrl=nJ  J  U  L  Lrfcr-J  J  J  L 

Fig.  64. — Uncommon  three-phase  parallel  combinations. 

ratio  of  high- voltage  to  low-voltage  turns,  the  same  IR  drop  and 
the  same  impedance  drop,  it  will  not  follow  that  by  using  iden- 
tical connections  at  the  case  of  the  apparatus,  that  a  star-star  can 
be  operated  in  parallel  with  another  star-star  or  delta-delta. 

If  the  designs  of  two  polyphase  units  are  such  that  satisfactory 
operation  may  be  carried  out,  the  next  step  for  the  operator  is 
to  ascertain  their  phase  relations;  that  is  to  say,  see  if  their  phase 
relations  between  the  high  voltage  and  low  voltage  are  identical, 
for,  apparatus  coming  from  the  factory  may  or  may  not  have 
the  same  polarity.  If  two  three-phase  transformer  groups 
have  in  themselves  or  between  them  a  difference  in  polarity 
(positive  in  one  and  negative  in  another)  it  will  be  impossible  to 
operate  them  in  parallel  when  arranging  their  external  connec- 
tions symmetrically. 

For  the  satisfactory  parallel  operation  of  three-phase  systems 
it  is  necessary  first  to  ascertain  that : 


68  STATIONARY  TRANSFORMERS 

(a)  Each  single-phase  unit  or  each  phase  of  the  polyphase  unit 
has  the  same  ratio  of  transformation,  the  same  IR  drop  and  the 
same  impedance  drop. 

(h)  The  phase  relation  is  the  same  (see  Fig.  56). 

(c)  The  polarity  is  the  same  (see  Fig.  55) . 

With  a  slight  difference  in  ratio,  unbalanced  secondary  voltages 
or  a  circulating  current  will  result. 

With  a  difference  in  impedence  the  total  efficiency  may  become 
badly  affected,  though  not  so  pronounced  as  that  which  would 
exist  if  each  unit  or  phase  was  tied  directly  together  and  after- 
ward connected  in  star  or  delta. 

^.^  y^wW  Tfu'Tf 

u  L  L)  LrtTiJ       CraFtq  cdkL-u       uraLfcq  fdkitKj 
M  (e"")  ^      \j"")\\   I 

J  L  u  Lnd-u  u  L  L  LttttJ 

'     \g"")  ih""\ 

Fig.  65. — Uncommon  three-phase  parallel  combinations. 

Phase  rotations  sometimes  offers  complications  where  mixed 
systems  of  delta  and  star  are  employed.  To  reverse  phase  rota- 
tion two  lines  (not  transformer  terminal  leads)  must  be  reversed. 

Polarity  complications  are  even  worse  and  sometimes  pre- 
sent much  difficulty.  To  reverse  the  polarity  two  transformer 
leads  (not  line  leads)  must  be  reversed  (see  Figs.  58,  59  and  60). 

Ordinary  parallel  operation  and  ordinary  connections  for 
parallel  operation  are  quite  simple.  Complications  set  in  when 
two  or  more  groups  of  different  system  connections  have  to  be 
operated  in  parallel.  On  some  of  our  present  day  large  and  cen- 
tralized systems,  it  happens  that  certain  "make-shift"  parallel 
combinations  must  be  made  with  the  available  apparatus, 
perhaps  in  the  stations  themselves  or  on  some  part  of  the  general 
distribution  system.  Usually  the  chief  operating  engineer  has 
a  list  of  available  transformers  at  each  station  and  center  which 


THREE-PHASE  TRANSFORMATION  SYSTEM      69 

facilitate  their  adoption  when  urgently  needed.  On  the  occur- 
rence of  a  breakdown  in  any  station  or  center  he  will  issue  an 
order  to  make  up  a  temporary  substitute  of  transformer  or  trans- 
formers as  the  requirement  calls  for.  This  may  mean  a  simple 
change  and  use  of  ordinary  connections,  or  it  may  mean  a  sub- 
stitute of  one  or  more  transformers  of  odd  voltages  or  kw.  capac- 
ity or  both.  In  fact  it  may  mean,  in  order  to  deliver  the 
amount  of  energy  necessary  and  continue  operation,  that  he 
will  have  to  resort  to  connecting  certain  transformers  in  series 
and  others  in  multiple  series,  etc.  It  may  also  mean  that  such 
unusual  parallel  combinations  as  those  shown  in  Figs.  66  and 
66a  will  have  to  be  made. 

A  number  of  delta-star  and  delta-delta  parallel  combinations 
similar  to  above  might  be  made  but  great  care  must  be  taken  to 
phase  out  the  secondary  windings  of  each  group  before  tying 
them  together,  for,  as  in  well  known,  a  straight  delta-star  cannot 


/ 
/ 


Fig.  66. — Unusual  parallel  combinations. 


be  tied  in  with  a  delta-delta  and  vice  versa,  nor  a  star-star  with 
a  delta-star  although  in  a  somewhat  modified  form  this  has  been 
done  in  Fig.  66.  With  these  and  similar  "make-shift"  combina- 
tions of  odd  voltages  and  capacities  engineers  encounter  from 
time  to  time  on  our  larger  systems,  the  essential  points  to  remem- 
ber are  the  difference  in  phase  position  and  rotation  and  also  the 
different  impedences  of  the  various  transformers  differing  very 
much  in  sizes.  The  two  former  difficulties  show  themselves 
immediately  parallel  operation  is  tried  but  the  latter  only 
demonstrates  itself  by  excessive  heating  or  a  bum-out  and  con- 
sequently is  a  serious  point  and  one  very  often  neglected  by 
operating  engineers  in  their  rush  to  get  the  system  in  regular 
working  order. 


70 


STATIONARY  TRANSFORMERS 


When  refering  to  parallel  operation  it  is  oftentimes  stated  that 
two  or  more  three-phase  groups  or  two  or  more  three-phase 
transformers  may  be  connected  in  parallel  on  the  low-  or  high- 
voltage  side  and  yet  it  may  not  be  possible  to  connect  them 
together  on  the  other  side.  This  condition  does  not  constitute 
parallel  operation  of  transformers.  Parallel  operation  of  trans- 
formers is  always  understood  to  mean  that  before  a  condition 
of  parallel  operation  can  exist  both  the  primaries  and  the  sec- 
ondaries respectively  must  be  tied  together,  neither  the  one 
nor  the  other  alone  constituting  parallel  operation. 

CHOICE  OF  CONNECTIONS 

In  the  connection  of  power  transformers  for  transmission  sys- 
tems there  is  a  choice  between  four  main  combinations  for  three- 
phase  and  three-phase  two-phase  systems,  namely,  delta  and 
star,  see  Fig.  67. 


^J- 


Fig.  67. — The  two  common  systems. 

Where  x  =  y  V3,  or  100  per  cent. 

and     y  =  x^/x   or  nearly  57.7  per  cent,  of  full  voltage  between 


lines  in  case  of  the  star  connection; 


or 


100.0^V^3  =  57.7  per  cent. 

The  delta  connection,  where  x  =  100  per  cent.,  the  voltage  is 
that  shown  between  lines;  or  577.7 X\/3  =  100  per  cent, 
and  three-phase  to  two-phase;  namely,  two-transformer   "T" 
and  three-transformer  "T",  see  Fig.  68. 
Where 

x/3 
y  =  —-  =86.6  per  cent,  of  the  voltage  between  trans- 
former terminals  a' ,  V  and  c. 


THREE-PHASE  TRANSFORMATION  SYSTEM      71 


X  =t/— y-100  per  cent.,  or  full  voltage  between  trans- 
^     former  terminals  a\  h'  and  c. 

z  =  Full  terminal  voltage  a',  h'  and  c,  corresponding 

to  a  ratio  of  1.0  to  1.15  of  ahc  values. 


a^ 


\ 


\ 


7' 


/ 
/ 


/ 


V 


Fig.  68. — The  uncommon  systems. 

Star  vs.  Delta. — It  is  shown  in  Fig.  69  that  should  one  of  the 
three  single-phase  transformers  be  cut  out  of  star,  or  one  of  the 
leads  joined  to  the  neutral  point  be  disconnected,  there  will  exist 
only  one  voltage  instead  of  three,  across  the  three  different  phases. 

This  disadvantage  is  detrimental  to  three-phase  working  of 
the  star  arrangement,  inasmuch  as  two  equal  and  normal  phase 


-IDOO- 


B 

>  < 


-1000- 


-1000 


-677 


577- 


-OT.r- 


-100- 


Fig.   69. — Result   of   one  transformer  of    a  star-connected   primary  and 
secondary  group  being  cut  out  of  circuit. 


voltages  of  the  three-phase  system  are  disabled,  leaving  one 
phase  voltage  which  may  be  distorted  to  some  degree,  depending 
on  conditions. 

On  the  other  hand,  should  one  phase,  or  one  transformer  of  a 
delta-connected  group  be  disconnected  from  the  remaining  two, 
as  shown  in  Fig.  70,  there  will  exist  the  same  voltage  between  the 


72 


STATIONARY  TRANSFORMERS 


three  different  phases,  and  practically  the  same  operating  con- 
ditions. 

The  result  obtained  by  cutting  out  of  delta  one  transformer,  is 
simply  the  introduction  of  open  delta,  which  has  a  rating  of  a 
little  over  one-half  the  total  capacity;  or  more  correctly,  the 
rating  of  transformer  capacity  is 

85  per  cent.  X  0.6666  =  0.5665 

of  three  transformers  of  the  same  size  connected  in  delta. 

In  the  past  it  has  frequently  been  urged  against  the  use  of 
three-phase  transformers  with  interlinked  magnetic  circuits  that 
if  one  or  more  windings  become  disabled  by  grounding,  short- 


A  B  C 

^1000 . 


-1000— 


-1000- 


-1000— 


-1000- 


0- 


^rW)  fMF|  pRHTj 


100- 


-100- 


_-_o---H 


-100— 


— -100  — 
-~100 


Fig.   70. — Result  of    a  delta-connected  group  of  transformers  with  one 
transformer  disconnected. 


circuiting,  or  through  any  other  defect,  it  is  impossible  to  operate 
to  any  degree  of  satisfaction  from  the  two  undamaged  windings 
of  the  other  phases,  as  would  be  the  case  if  a  single-phase  trans- 
former were  used  in  each  phase  of  the  polyphase  system. 

All  that  is  necessary  is  to  short-circuit  the  primary  and  second- 
ary windings  of  the  damaged  transformer  upon  itself,  as  shown 
in  Fig.  71.  The  windings  thus  short-circuited  will  choke  down 
the  flux  passed  through  the  portion  of  the  core  surrounded  by 
them,  without  producing  in  any  portion  of  the  winding  a  current 
greater  than  a  small  fraction  of  the  current  which  normally 
exists  at  full  load. 

With  one  phase  short-circuited  on  itself  as  mentioned  above, 
the  two  remaining  phases  may  be  reconnected  in  open  delta  in 


THREE-PHASE  TRANSFORMATION  SYSTEM      73 

tee  or  in  star-delta  for  transforming  from  three-phase  to  three- 
phase;  or  the  windings  may  be  connected  in  series  or  parallel 
for  single-phase  transformation.  This  method  of  getting  over  a 
trouble  is  only  applicable  where  transformers  are  of  the  shell  type. 

The  relative  advantages  of  the  delta-delta  and  delta-star 
systems  are  still,  and  will  always  be  disputed  and  wide  open  for 
discussion.  They  possess  the  following  advantages  and  dis- 
advantages, respectively: 

Delta-delta  (non-grounded).  When  one  phase  is  cut  out  the 
remaining  two  phases  can  be  made  to  deliver  approximately  58 


Fig.   71. — Result  of    operating  a  delta-connected   transformer  with  one 
winding  disabled  and  short-circuited  on  itself. 

per  cent,  of  the  full  load  rating  of  transformer  (in  the  case  of  a 
three-phase  shell  type)  or  three  single-phase  transformers. 

Delta-star  (neutral  grounded).  Advantage  of  reducing  the 
cost  of  high  voltage  line  insulators  for  equal  line  voltage,  which 
is  a  very  large  item  when  dealing  with  long-distance  lines;  their 
size  need  only  be  approximately  58  per  cent,  of  that  used  on  a 
line  using  the  delta  system. 

It  is  also  possible,  under  certain  conditions,  to  operate  and 
deliver  three-phase  currents  when  one  phase  or  one  line  conductor 
is  on  the  ground. 

The   disadvantages  are: 

Delta-delta  (non-grounded).  Larger  transformer  or  trans- 
formers and  larger  line  insulators  for  the  same  line  voltage. 

Delta-star  (neutral  grounded).  Not  always  in  a  position  to 
operate  when  one  phase  or  one  line  conductor  is  cut  out. 

Table  I  gives  a  comparison  of  the  four  common  three-phase 
systems. 


74 


STATIONARY  TRANSFORMERS 
TABLE  I 


Governing 
factors 

Star-delta  to 
delta-star 

Star-star  to 
any 

Delta-delta 
to  any 

Delta-star  to 
star-delta 

Cheapest  cost.  .  .  . 
Best  operated .... 
Least  potential 
strain. 

Third. 

Third. 

Fourth. 

First. 
Fourth. 
Third. 

Fourth. 

First. 

Second. 

Second. 
Second. 
First. 

Cheapest  Cost. — This  represents  the  lowest  price  for  transform- 
ers and  system  (complete)  of  equal  kw.  capacity  and  terminal 
line  voltage. 

Best  Operated. — All  the  star  connections  are  assumed  to  have 
their  neutral  points  grounded,  and  the  generators  in  each  case 
star-connected  and  grounded.  Each  case  is  figured  to  have 
either  one  line  on  the  ground  or  one  transformer  or  one  phase 
disabled  by  a  burnt-out  unit  or  other  fault. 

Least  Potential  Strain. — This  represents  the  worst  voltage 
strain  that  can  be  placed  on  the  line  and  receiving  station  trans- 
formers, no  matter  what  changes  of  phase  relation  might  occur 
as  the  result  of  open  connections,  short-circuits  or  any  combina- 
tion of  these. 

It  is  quite  evident  that  the  delta-star  to  star-delta  system  is 
the  best  all  round  system  to  have.  It  will  also  be  noted  that 
this  system  takes  a  second  place  of  importance  in  the  "  best 
operated"  list,  for  the  reason  that  a  ground  on  one  line  short- 
circuits  that  phase  whereas  with  the  delta-delta  to  delta-delta 
(assuming  all  other  phases  thoroughly  insulated  which  is  almost 
a  practical  impossibility  on  high  voltage  systems)  the  system  is 
not  interrupted.  Although  a  doubtful  question  it  is  placed  in 
its  favor,  but  beyond  this  weak  point  the  delta-star  to  star-delta 
is  equally  as  good  and  reliable  as  the  delta-delta  to  delta-delta 
and  about  equally  able  to  operate  and  furnish  three-phase  cur- 
rents with  only  two  transformers.  The  right  order  of  importance 
giving  the  best  system  is: 

First.     Delta-star  to  star-delta. 

Second.     Delta-delta  to  delta-delta. 

Third.     Star-delta  to  any  combination. 

Fourth.     Star-star  to  any  combination. 


THREE-PHASE  TRANSFORMATION  SYSTEM      75 

Depending  on  the  voltage  and  size  of  transformers  the  relative 
cost  will  vary,  but  the  advantages  given  are  about  correct  for 
almost  all  high-voltage  systems.  The  same  thing  applies  in  the 
case  of  the  best  system  for  operation,  but  for  general  cases  Table 
I  list  will  be  found  to  be  close.  In  fact,  if  such  questions  as  the 
third  harmonics  and  the  resulting  flow  of  unbalanced  currents 
in  the  closed  delta-delta  to  delta-delta  be  considered,  there  is 
still  something  better  in  favor  of  the  delta-star  to  star-delta 
system. 

An  advantage  somewhat  in  doubt  is,  that  only  one  high- 
voltage  terminal  of  a  delta-star  to  star-delta  system  is  subjected 
to  the  full  incoming  high-voltage  surges,  whereas  the  delta-delta 
system  has  always  two  or  double  the  number  of  high-voltage 
transformer  terminals  connected  to  the  transmission  line,  and, 
of  course,  almost  double  the  chance  of  trouble  due  to  high- 
voltage  surges.  Impulses  coming  in  over  a  line  will  enter  the 
high-voltage  windings  of  transformers  from  both  ends,  and 
even  though  the  effect  be  in  some  degree  divided  if,  say,  two  lines 
are  disturbed,  it  will  not  have  the  same  total  factor  of  safety  as 
would  the  delta-star  to  star-delta  system,  which  has  the  uninter- 
rupted facility  of  dividing  the  impulse  between  two  transformer 
windings.  The  same  impulse  will  also  divide  its  effect  between 
two  or  three  transformer  windings  of  a  delta-delta  system  but 
not  with  the  same  effect  because  of  the  connections. 

In  case  one  line  terminal  is  disturbed  by  an  incoming  surge 
only  one  transformer  winding  of  a  delta-star  to  star-delta 
system  is  effected.  The  disturbance  will,  of  course,  be  greater 
than  that  affecting  a  delta-delta  system,  but  the  difference  will 
not  generally  be  great  enough  to  cause  a  break-down  on  one 
system  and  not  on  the  other;  in  fact  two  transformer  windings 
of  a  delta-delta  system  may,  in  the  majority  of  cases,  be  injured 
to  one  of  the  delta-star  to  star-delta  systems. 

Another  very  important  advantage,  particularly  so  where 
very  high  voltages  are  employed,  not  in  favor  of  either  the  delta- 
delta  or  star-delta  (delta  on  the  high-voltage  side)  is  that  each 
transformer  of  a  group  of  three  has  its  winding  terminals  exposed 
to  every  line  surge  and  consequently  double  the  possibility  of 
trouble  that  can  occur  on  delta-star  to  star-delta  systems  (star 
on  the  high-voltage  line  side);  also,  the  coils  of  a  delta-delta  or 
star-delta  (delta  on  the  high-voltage  side)  have  a  greater  number 
of  turns  of  smaller  cross-section  for  a  given  kw.  capacity  and 


76  STATIONARY  TRANSFORMERS 

consequently  are  more  liable  to  mechanical  failure  than  a  delta- 
star  connected  system  (star  on  the  high-voltage  side). 

A  further  disadvantage  of  the  high-voltage  delta  is  that  if  it  is 
thought  necessary  to  ground  the  delta  as  a  safeguard  for  high- 
voltage  stresses,  it  will  require  a  group  of  transformers  with  inter- 
connected phases  or  a  star-delta  connection;  therefore  additional 
apparatus  is  required  whereas  the  delta-star  system  can  be 
grounded  direct  without  any  additional  expense. 

As  regards  some  of  the  advantages  of  switching,  the  delta-star 
has  a  further  advantage  over  the  delta-delta.  The  delta-star 
(star  on  the  high-voltage  side  or  low-voltage  side)  can  give  claim 
to  an  advantage  by  its  simple,  effective  and  cheap  arrangement 
of  switches  in  all  stations  where  it  is  found  necessary  to  use  air- 
break  disconnecting  or  single-pole  switches  of  any  kind  installed 
on  each  high-  and  low-voltage  lead.  Only  two  such  switches 
instead  of  four  per  transformer  are  needed,  the  remaining  two 
leads  being  solidly  connected  to  a  neutral  bus-bar  grounded 
direct  or  through  a  resistance  as  thought  desirable.  Its  advan- 
tage in  this  respect  is  important  on  very  high-voltage  systems 
where  stations  are  cramped  for  space;  as  an  illustration  of  this 
take  one  three-phase  group  and  we  find : 

Twelve  switches  are  required  for  a  delta-delta  group  of  three 

single-phase  transformers. 
Nine  switches  are  required  for  a  delta-star  group  of  three 

single-phase  transformers. 
Six  switches  are  required  for  a  star-star  group  of  three 
single-phase  transformers. 
In  this  it  is  also  well  to  remember  that  a  spare  single-phase  trans- 
former arranged  to  replace  any  of  the  three  single-phase  trans- 
formers of  the  group,  will  require  the  same  number  of  switches,  or 
twelve,  nine  and  six  respectively.  All  the  switching  referred 
to  here  only  holds  good  when  the  neutral  point  of  the  star  is 
grounded. 

There  exist  a  large  variety  of  system  connections  quite  different 
from  the  common  ones  mentioned  above.  For  instance,  it  is 
not  unusual  now  to  see  in  one  station  a  group  of  three  single- 
phase  transformers  operating  in  parallel  with  two  single-phase 
transformers,  the  two  groups  being  connected  in  delta  and  open- 
delta  respectively.  It  is  well  known  that  the  open-delta  system 
does  not  claim  to  possess  any  merits  over  any  of  the  common  sys- 
tems above  mentioned,  but  it  is  oftentimes  necessary  to  fall  back 


THREE-PHASE  TRANSFORMATION  SYSTEM      77 

on  this  system  as  a  stand-by  or  in  an  emergency  and  from  this 
point  of  view  it  becomes  very  useful.  Now,  in  certain  cases  of 
station  wiring  layout,  particularly  in  those  stations  operating 
above  50,000  volts,  it  might  be  only  possible  to  use  the  delta 
connection  for  parallel  operation  after  considerable  loss  of  time 
rearranging  the  wiring.  The  wiring  layout  of  a  station,  however, 
might  be  such  with  respect  to  the  location  of  transformers  that 
with  a  disabled  unit  of  a  group  of  three  connected  in  delta-delta 
it  would  not  be  possible  to  connect  the  two  remaining  transform- 
ers in  parallel  and  in  open-delta  with  a  group  of  three  others 


A  :b  0 


a      b     c 


ABC 


A"    B' 


Ua/^        Ivwl         vvv"  Iwv       Iwv  lw\^  Ivvvv  V^/^^ 

.   .  (1)  (2)  (3) 


a'   b'    c' 


a       b        c 


j^c  ^.'  p> 


Fig.  72. — Correct  method  of  connecting  the  transformers. 


located  some  distance  away.  Suppose  for  example  that  the 
station  bus-bar  wiring  in  the  high-  and  low-tension  bus-bar 
compartments  is  arranged  to  meet  any  delta  and  open-delta 
combination  and  that  two  groups  of  delta  and  one  group  of  open 
delta-connected  transformers  have  already  been  operating  in 
parallel  and  suddenly  one  of  the  delta  groups  develops  a  burn-out 
on  one  transformer  leaving  two  good  units  for  further  operation. 
The  first  question  to  be  asked  is — what  is  the  best  thing  to  do? 
Or,  what  is  the  best  combination  to  make  to  be  in  a  position  to 
take  care  of  the  biggest  amount  of  energy  put  upon  the  whole 
of  the  remaining  transformers?  If  it  is  kept  in  mind  that  it  is 
impossible  to  get  any  more  than  80  per  cent,  of  the  normal  output 
per  unit  when  an  open-delta  group  is  operating  in  parallel  with 
a  delta  group  of  transformers,  it  will  be  an  easy  matter  to  know 
just  how  to  proceed.  Just  wha.^  can  be  done  and  what  ought 
to  be  done  are  given  in  Fig.  72  and  Fig,  73.     Supposing  groups 


78 


ST  A  TIONAR  Y  TRANSFORMERS 


No.  1  and  No.  2  have  been  operating  in  closed  delta  and  open- 
delta  respectively  and  group  No.  3  has  j  ust  had  a  burn-out  of  one 
unit  (see  Fig.  72),  it  is  quite  evident  that  by  connecting  the  three 
groups  as  shown  more  energy  can  be  delivered  than  is  possible 
with  those  connections  shown  in  Fig.  73.  In  fact,  it  is  possible 
to  deliver  more  energy  from  six  of  the  transformers  shown  in 
Fig.  72  than  from  the  seven  transformers  with  the  connections 
given  in  Fig.  73. 


ABC 


A'     B'    C 


A"   B"    C 


tvN/v4  U/VSaI  IvvN/nI  l/VwJ  I'vA/vJ  bsA/V^  WS'^S^  In/n/vJ 


a      b       c 


a'     b'    c' 


a"    b"    c" 


b         \  b'        l~ 


iS)  ^c" 


b" 


J 


Fig.  73. — Wrong  method  of  connecting  open-delta  transformers  in  parallel. 


Single-phase  vs.  Three-phase  Transformers. — As  the  art  of 
transformer  design  and  manufacture  improves,  the  three-phase 
transformer  is  sure  to  be  as  extensively  used  as  the  single-phase 
transformer,  especially  so  for  high  voltages;  its  only  disadvantage 
being  in  the  case  of  failure  and  interruption  of  service  for  repairs, 
but  this  will  be  offset  by  other  important  features  since  break- 
downs will  be  of  very  rare  occurrence. 

From  the  standpoint  of  the  operating  engineer  (neglecting  the 
losses  in  the  transformer)  the  single-phase  transformer  is  at  the 
present  time  preferable  where  only  one  group  is  installed  and  the 
expense  of  a  spare  unit  would  not  be  warranted  as  in  the  delta- 
delta  system.  If  one  of  the  three  transformers  should  become 
damaged  it  can  be  cut  out  with  a  minimum  amount  of  trouble 
and  the  other  two  can  be  operated  at  normal  temperature  on 
open-delta  at  approximately  58  per  cent,  of  the  total  capacity  of 
the  three.  With  a  three-phase  transformer  a  damaged  phase 
would  cause  considerable  inconvenience  for  the  reason  that  the 
whole  transformer  would  have  to  be  disconnected  from  the 


k 


THREE-PHASE  TRANSFORMATION  SYSTEM      79 

system  before  repairs  of  any  kind  could  be  made,  which,  in  the 
case  of  a  shell-type  transformer,  could  probably  be  operated 
depending  on  the  amount  of  damage,  as  it  is  not  always  possible 
to  tell  the  exact  extent  of  break-down  before  a  thorough  examina- 
tion is  made. 

In  the  absence  of  any  approved  apparatus  that  can  be  relied 
on  to  take  care  of  high-voltage  line  disturbances  such  as  we 
have  on  some  of  our  long-distance  transmission  lines,  the  whole 
burden  being  thrown  on  the  insulation  of  this  important  link 
of  a  power  undertaking,  the  three-phase  transformer  appears 
to  be  handicapped.  Its  break-down  as  mentioned  above 
would  entirely  interrupt  the  service  until  a  spare  transformer  is 
installed  or  the  faulty  one  temporarily  arranged  with  its  faulty- 
short-circuited  winding  in  the  case  of  the  shell-type.  The  en- 
gineer who  has  the  responsibility  of  operating  large  power 
systems  has  not  yet  taken  very  favorably  to  the  three-phase 
transformer  for  this  very  reason,  his  main  object  being  reliability 
of  service  and  not  the  first  cost  or  saving  of  floor  space. 

It  has  for  many  years  been  appreciated  by  American  and 
European  engineers  that  apart  from  the  decrease  in  manufactur- 
ing cost  with  increase  in  size  of  units,  the  three-phase  unit  has 
the  advantage  of  requiring  less  material  and  is  more  efficient 
than  any  other  single-phase  combination  of  transformers  of  the 
same  kw.  capacity.  The  relative  difference  in  the  losses  and 
weights  being: 

Three  single-phase  transformers  weigh  about  17  per  cent,  more 
than  one  three-phase. 

Three  single-phase  transformers  have  about  17  per  cent,  more 
losses  than  one  three-phase. 

Used  in  open  delta,  two  single-phase  transformers  weigh  about 
the  same  as  three  single-phase  transformers. 

Two  single-phase  transformers  have  about  the  same  losses  as 
three  single-phase  transformers. 

Used  in  tee,  two  single-phase  transformers  have  a  sum  total 
weight  of  about  5  per  cent,  less  than  three  single-phase 
transformers. 

Two  single-phase  transformers  have  the  sum  total  weight  of 
about  5  per  cent,  less  than  two  single-phase  transformers 
connected  in  open-delta. 

Two  single-phase  transformers  have  about  5  per  cent,  less 
losses  than  three  single-phase  transformers. 


80  STATIONARY  TRANSFORMERS 

Two  single-phase  transformers  have  about  5  per  cent,  less  losses 
than  two  single-phase  transformers  connected  in  open-delta, 

Where  a  large  number  of  transformers  are  installed  in  one 
building,  say  three  groups  or  above,  it  is  unquestionably  a  great 
saving  over  any  combination  of  single-phase  transformers,  and 
the  possibility  of  using  two  sets  out  of  the  three  or  three  sets  out 
of  the  four,  and  so  on,  offsets  to  a  large  extent  the  important 
drawback  reliability,  and  places  the  three-phase  transformer  on 
almost  an  equal  footing  in  this  respect  as  the  three  single-phase 
transformer  combination.  The  building  is  thereby  reduced  a 
considerable  amount  (also  compartment  insulator  bushings  and 
busbar  high  and  low  voltage  insulators),  besides  simplifying  the 
wiring  layout  in  the  stations. 

To  fulfil  the  requirements  of  a  three-phase  transformer  using 
a  combination  of  single-phase  transformers,  it  is  necessary  to  use: 

Basis. — One  three-phase  transformer  of  100  per  cent.  kw. 
capacity. 

Delta  Connected. — Three  of  33.3  per  cent,  each,  or  a  total  100 
per  cent.  kw.  capacity. 

Star  Connected. — Three  of  33.3  per  cent,  each,  or  a  total  100 
per  cent.  kw.  capacity. 

Open-delta  Connected. — Two  of  57.7  per  cent,  each,  or  total 
115.5  per  cent.  kw.  capacity.  (For  three  units,  173  per  cent, 
kw.  capacity  is  required.)* 

"Scott":  "T"  (Two-Transformer  Connection).— One  of  57.7 
per  cent.  kw.  capacity,  and  one  of  50  per  cent,  kw.,  or  total  107.8 
per  cent.  kw.  capacity.  (For  three  units,  165.6  per  cent.  kw. ; 
capacity  is  required.)* 

"Taylor":  "T"  {Three-Transformer  Connection).— Three  of 
maximum  50  per  cent,  each,  or  total  150  per  cent.  kw.  capacity. 

From  this  it  is  evident  that  the  three  best  combinations  are 
delta,  star,  and  the  three-transformer  "T"  connections.  With 
the  delta  and  "T"  (three-transformer)  systems  a  spare  trans- 
former is  not  warranted,  and  in  case  of  a  break-down  of  a  unit, 
the  minimum  amount  of  time  is  lost  in  cutting  it  out  of  service. 
With  the  open-delta  and  "T"  (two-transformer)  systems,  the  loss 
of  any  unit  stops  the  system  from  operating  three-phase  current. 
A  further  advantage  of  the  three-transformer  methods — delta, 
star,  and  "T "-three  transformer — is,  a  spare  unit  costs  less  than 
one  for  either  the  open-delta  or  the  "T"-two-transformer  methods. 

*  Not  always  in  service,  hence  a  disadvantage. 


THREE-PHASE  TRANSFORMATION  SYSTEM      81 

CONNECTIONS  FOR  GROUNDING  THREE-PHASE  SYSTEMS 

In  Fig.  74  several  methods  are  shown  for  grounding  three- 
phase  systems.  For  (A)  and  (B)  there  is  a  choice  between  the 
ground  shown,  or  the  ground  at  x.     For  (A)  the  ground  as  shown 


Fig.  74. — Method  of  grounding  three-phase  systems. 

represents  a  maximum  difference  of  potential  between  ground 

and  line  terminal  of  —t~  E,  and  — y^  E  for  the  ground  at  x. 

For  {B),  the  maximum  voltage  stress  from  line  terminal  to 
ground  is  full-line  voltage,  but  with  a  ground  made  at  x  the 

6 


82  STATIONARY  TRANSFORMERS 

maximum  voltage  stress  is  only  approximately  87  per  cent,  of 
full  voltage  between  terminals. 

The  delta-star  system  shown  at  (c)  of  Fig.  74  is  the  most 
uncommon  of  any  of  the  systems  given.  Like  (A'),  three  single- 
phase  windings  are  required  before  grounding  can  be  made 
possible.  The  maximum  voltage  strain  from  any  line  terminal 
to  ground  is  E'  +  (0.57  E),  or  assuming  E  =  100,  and  E'  =  100,  we 
have  100  +  (0.57  X 100)  =  157  volts  maximum  strain  from  neutral 
ground  to  star-line  terminal. 

The  diagrams  of  (A'),  (B')  and  (C)  of  Fig.  74  represent  the 
two  well-known  systems  and  their  three  methods  of  grounding. 
The  two  best  methods  for  grounding  are  (A')  and  (B').  The 
method  (C)  is  used  only  where  auxiliary  apparatus  cannot  be 
had  for  grounding  through  the  star  connection. 

The  delta  and  star  systems  shown  at  (B")  and  (C")  represent 
systems  grounded  as  shown  at  (A')  and  (B')  but  with  one  high- 
voltage  terminal  grounded.  For  (A")  the  system  is  insulated 
with  the  exception  of  ground  at  high-voltage  line  terminal. 
Both  B"  and  C"  show  the  effects  of  grounding  either  the  low 
voltage  or  high  voltage  or  both.  Where  both  neutral  points 
are  grounded,  the  high-voltage  stresses  on  the  low-voltage 
windings  when  an  accidental  ground  occurs  on  the  high-voltage 
side  is  reduced  to  a  minimum,  but  is  of  maximum  value  on  sys- 
tems operating  without  grounded  neutrals. 

Three-phase  to  Single-phase  Transformation. — An  interesting 
three-phase  to  single-phase  arrangement  is  given  in  Fig.  75. 
For  this  service  three  single-phase  transformers  or  their  equiva- 
lent (somewhat  special  in  their  construction)  are  required,  the 
magnetizing  current  being  much  stronger  than  that  used  in  the 
ordinary  static  transformer  in  order  that  the  iron  may  be  super- 
saturated. This  modification  will  result  not  only  in  satisfactory 
transformation  of  voltage  and  current,  but  transformation  of 
the  frequency  as  well. 

With  three  transformers  connected  as  shown  in  Fig.  75,  the 
secondary  windings  would  under  ordinary  conditions  show  no 
e.m.f.  across  A-C;  but  if  the  iron  is  saturated  the  secondary 
becomes  so  transformed  that  an  e.m.f.  is  obtained  having  3f  or 
three  times  the  frequency  of  the  primary. 

The  advantage  of  this  arrangement  is  felt  where  arc  and  incan- 
descent lighting  is  required  and  where  the  frequency  is  15-25. 
The  constant  extension  of  electric  traction  on  railways  operating 


THREE-PHASE  TRANSFORMATION  SYSTEM     83 


at  these  frequencies  has  resulted  in  the  use  of  polyphase  lamps  and 
the  triple  frequency  transformer  arrangement.  Single-phase 
railways  are  much  more  general  than  three-phase,  and,  therefore, 
it  is  really  more  important  to  be  able  to  increase  the  frequency 
of  single-phase  than  of  three-phase  current. 

Also,  in  general,  three-phase  high  voltages  and  energy  are 
transmitted  long  distances  to  electric  traction  plants  at  a  fre- 


-E'/S- 


^^ 


-E^i 


Frimary         A' 


■^E^-A  *— ^"-^  -" — E^ 

^v^Sv^  Uv^^/sl  ^^^v^  ^ 

p^  p^  p^  "-^M\  y 


Secondary 


Fig.  75. — Method  of  transforming  from   three-phase  to   single-phase  and 
changing  the  frequency. 

quency  of  60  cycles.  It  is  therefore  important  from  several  view- 
points to  be  able  to  transmit  electric  energy  at,  say,  60-?- 3  =  20 
cycles  and  single-phase;  thus  reducing  the  voltage  drop  due  to 
the  higher  frequency,  and  reducing  cost  of  line  construction, 
insulators  and  its  maintenance  in  general. 


CHAPTER  V 

THREE-PHASE  TRANSFORMER  DIFFICULTIES 

Most  of  the  troubles  which  occur  on  transmission  systems  are 
put  down  to  line  surges,  resonance,  or  some  unknown  phenom- 
enon on  lines,  and  as  a  matter  of  fact  most  of  the  troubles 
might  be  in  the  transformers  themselves,  which  may  be  damaged 
and  their  phase  relations  twisted  so  as  to  produce,  in  some  in- 
stances, many  times  the  normal  voltage. 

The  most  disastrous  troubles  that  can  happen  to  a  three-phase 
system  are  those  of  complex  grounds  and  short-circuits.  Witli 
a  grounded  neutral  star  system,  a  ground  on  any  one  phase  is  a 
short-circuit  of  the  transformers,  and  the  entire  group  becomes 
disabled  until  changes  are  made. 


^         <-4000 


-4000 


< 4000- 


ma) 


-4000- 


-«-4000 

QMJ 


^^^<^^Mm\^f^mmxjimm^ 


-600CO > 


-60000^  ^60000-^ 
103557 


< 60000 


Fig.  76. — One  transformer  short-circuited  and  cut  out  of  delta. 


The  voltage  between  windings  and  the  core  is  limited  to  57.7 
per  cent,  of  that  of  the  line,  and  the  insulation  between  the 
windings  and  the  core  is  likewise  reduced  in  proportion.  The 
voltage  between  mains  and  the  ground  is  57.7  per  cent,  of  the 
line  voltage,  with  a  star  connection,  but  the  neutral  point  may 
move  so  as  to  increase  the  voltage  with  an  ungrounded  system. 
If  one  circuit  is  grounded,  the  voltage  between  the  other  two 
circuits  and  the  ground  is  increased,  and  may  be  as  great  as  the 

84 


THREE-PHASE  TRANSFORMER  DIFFICULTIES    85 

full  line  e.m.f.  Such  unbalancing  would  cause  unequal  heating 
of  the  transformers  and  if  a  four-wire  three-phase  system  of 
distribution  were  employed,  would  prove  disastrous  to  the  regu- 
lation of  the  voltage. 

With  a  star-delta  system  as  shown  in  Fig.  76,  where  a  trans- 
former is  short-circuited  and  cut  out  of  delta  on  the  secondary, 
it  is  possible  to  obtain  V  3  times  the  potential  of  any  one  of  the 
transformers.  In  Fig.  7Q  A  B  C  represents  the  vector  triangle 
of  e.m.fs.  on  the  primary  with  full  line  voltage  or  4000  volts, 
impressed  on  the  transformers,  which  under  normal  conditions 
should  be 

4000  X— 7=  =  2300  volts. 

The  phase  relations  are  changed  to  60  degrees,  converting 
the  original  star  arrangement  to  an  open  delta;  one  phase  is 


Fig.  77. — Primary  e.m.fs.  and  phase  relations. 

reversed,  the  resultant  e.m.f.being  the  same  as  that  across  any 
two  phases.     See  also  vector  diagram.  Fig.  77. 

As  each  transformer  is  only  designed  for  2300  volts  the  e.m.f. 
across  the  secondary  windings  should  be  34,600  volts,  but  in  this 
case  the  voltages  are  34,600  times  V  3  or  60,000  volts. 

The  secondary  vector  e.m.fs.  are  graphically  represented  to  the 
right  of  Fig.  76.  In  order  to  bring  the  resultant  vector  secondary 
e.m.f.,  a  and  c,  in  its  proper  position  the  components  must  be 
drawn  parallel  with  the  primaries. 

One  secondary  winding  is  short-circuited  and  cut  out  of  delta 
leaving  an  open-delta  connection  reversed  in  direction,  its  phase 
relations  being  changed  from  60  to  120  degrees:  increasing  the 
voltage  between  a  and  c  to 

34,600X1732X1732=103,557  volts. 
or\/3X\/3X34,600=  103,577  volts. 


86  STATIONARY  TRANSFORMERS 

This  is  a  very  important  point  to  bear  in  mind,  especially 
when  generators  are  tied  directly  to  the  system  without  fuses  or 
any  protecting  devices. 

The  voltages  impressed  on  the  primary  windings  of  Fig.  7G 
and  77  are: 

Aand  B  =   4000  volts, 
5  and  C  =  4000  volts, 
A  and  C  =   4000  volts. 
E.m.fs.  between  the  primary  neutral  and  any  line,  are: 
A  &nd  A'  =  4000  volts, 

which  should  be  6000X0.577  =  2300  volts; 
B  and  S'  =  0  volts, 

which  should  be  2300  volts; 

C  and  C  =  4000  volts, 

which  should  be  4000X0.577  =  2300  volts. 
The  e.m.fs.  between  the  secondary  lines,  are: 
a  and  6  =  60,000  volts, 

which  should  be  60,000X0.577  =  34,600  volts; 
&  andc  =  103,577  volts, 

which  should  be  103,577^2.99       =  34,600  volts; 
a  and  c  =  60,000  volts, 

which  should  be  60,000X0.577       =  34,600  volts. 
The  increases  in  e.m.f.  across  the  secondary  lines,  are: 
a  and  c  =  173  per  cent,  above  normal, 
b  and  c  =  300  per  cent,  above  normal, 
a  and  &  =  173  per  cent,  above  normal. 
It  is  also  found  that  where  the  neutral  points  of  the  primary 
and  secondary  windings  are  grounded,  the  opening  of  one  or  two 
of  the  three  line  circuits  will  cause  currents  to  flow  through  the 
ground.     A  partial  ground  on  a  line  circuit  will  partially  short- 
circuit  one  transformer  and  cause  current  to  flow  through  the 
ground  and  the  neutral. 

The  actual  strain  between  high-tension  and  low-tension  wind- 
ings is  equal  to  the  high-tension  voltage  plus  or  minus  the  low- 
tension  voltage,  depending  upon  the  arrangement  and  connection 
of  the  coils;  but  as  the  low-tension  voltage  is  usually  a  small  per- 
centage of  that  of  the  high-tension,  it  is  customary  to  assume 
that  the  strain  between  windings  is  equal  to  that  of  the  high- 
tension  voltage  alone. 

If  the  neutral  points  of  the  high-tension  and  low-tension 
windings  are  grounded,  the  iron  core  being  also  grounded,  then 


t 


THREE-PHASE  TRANSFORMER  DIFFICULTIES    87 

as  long  as  the  circuits  are  balanced  the  voltage  strains  will  be  the 
same  as  with  the  windings  ungrounded,  and  balanced;  but  in 
case  of  a  ground  on  either  high-tension  or  low-tension  line,  or  in 
case  of  a  connection  between  high-tension  and  low-tension  wind- 
ings, a  portion  of  the  windings  will  be  short-circuited. 

Assuming  that  all  lines  and  transformers  are  in  good  shape, 
that  is  to  say,  clear  from  grounds  and  short-circuits,  it  is  possible 
to  obtain  any  of  the  following  results  shown  in  Figs.  78, 79,  80  and 
81,  by  connecting  the  receiving  ends  of  transmission  lines  to  a 
wrong  phase  terminal  receiving  three-phase  current  from  another 
source  of  supply,  or  by  switching  together  groups  of  two  or  more 
transformers  of  the  wrong  phase  relations. 


Fig.  78. — Re.sultant  e.m.fs.,  and  phase  relations  of  improper  delta-delta 
and  star-star  connected  group  of  transformers. 

Fig.  78  represents  the  result  of  a  delta-delta  and  star-star 
combination  thrown  together  at  120  degrees  apart,  both  trans- 
mission lines  receiving  three-phase  currents  of  the  same  potential, 
phase  relations,  and  frequency. 

The  resultant  voltage  obtained  in  attempting  to  parallel  two 
groups  of  three  transformers  star  connected  is  \/^  times  the 
e.m.f.  between  any  two  line  wires,  or 

Star     =  (57.7  X  1.732  =  100)  X  (1.732)  =  173.2  volts. 

The  combination  shown  in  Fig.  79  represents  four  groups 
(three  single-phase  transformers  in  each  group)  connected  to  one 
set  of  busbars.  Each  group  receives  three-phase  current  from 
independent  source  of  supply  and  is  so  tied  in  on  the  primary 
and  secondary  busbars  as  to  involve  a  partial  short-circuit. 

In  common  practice  this  combination  is  more  often  likely  to 
happen  on  large  distributing  systems  where  all  transformers  in 


88 


STATIONARY  TRANSFORMERS 


groups  are  tied  together  on  primaries  and  secondaries.  As  wih 
be  noticed,  any  attempt  to  connect  such  a  system  with  all  pri- 
mary windings  and  all  secondary  windings  of  each  group  in 
parallel  will  produce  a  short-circuit. 


Fig.   79. — Representation  of  a  complete  combination  of  delta-delta  and 
delta-star  transformer  group  connections. 


Figs.  80  A  and  B. — Graphic  illustration  of  e.m.fs.  and  phase  displacement 
of  two  delta-delta  to  delta-star  connected  groups  of  transformers. 

With  a  delta-star  presupposed  parallel  operation  it  is  impos- 
sible to  change  the  magnetic  field  to  correct  the  phase  displacement 


THREE-PHASE  TRANSFORMER  DIFFICULTIES    89 

which  occurs,  though  it  is  possible  in  the  case  of  generators  which 
are  necessary  for  permitting  the  30  degrees  electrical  displace- 
ment to  be  corrected  by  a  mechanical  twisting  of  the  phases  with 
respect  to  their  magnetic  fields;  but  with  transformers  it  is 
impossible. 

The  phase  displacements  show  a  star  connection  introduced  in 
which  the  relative  e.m.f.  positions  are  changed  by  an  angle  30 
degrees.  If,  for  example,  we  assume  the  line  potential  to  be 
60,000  volts,  and  we  attempt  to  connect  the  groups  as  shown  in 
diagram,  the  result  will  be  voltages  as  high  as  116,000. 


Fig.  81. — E.m.fs.  and  phase  relation  of  a  delta-delta  to  delta-star  connected 
group  of  transformers. 

The  resultant  e.m.fs.  established  by  this  experiment,  are  shown 
separately  in  Figs.  80  and  81.     They  are  correctly: 

B"   to  B  =   84,840  volts,  which  should  be  =  0 

B''  to  C  =116,000  volts,  which  should  be  =60,000 
A"  to  C  =116,000  volts,  which  should  be  =60,000 
A''  to  B  =116,000  volts,  which  should  be  =60,000 
A'  toB  =  84,840  volts,  which  should  be  =60,000 
A'  to  C  =  31,000  volts,  which  should  be  =60,000 
C  to  B  =116,000  volts,  which  should  be  =60,000 
C  to  B  =116,000  volts,  which  should  be  =60,000 
C  to  C  =  84,840  volts,  which  should  be  =60,000 
B'"  to  B  =  31,000  volts,  which  should  be  =  0 

B"'  to  ^  =  31,000  volts,  which  should  be  =60,000 
A'"  to  A  =   31,000  volts,  which  should  be  =  0 

A"'  to  B  =  84,840  volts,  which  should  be  =60,000 
A  fact  not  very  well  recognized,  is  the  impossibility  of  parallel- 
ing certain  primary  and  secondary  three-phase  systems.     The 
following  combinations  can  be  operated  in  parallel: 


90 


ST  A  TIONARY  TRANSFORMERS 


Delta-star  group  with  a  delta-star. 
Star-star  group  with  a  star-star. 
Delta-delta  group  with  a  delta-delta. 
Star-delta  group  with  a  star-delta. 
Delta-star  group  with  a  star-delta. 
Star-star  group  with  a  delta-delta. 


Fig.  82. — ^Practical  representation  of  a  delta-delta  to  delta-star  connected 
group  of  transformers. 

These  delta-star    combinations    necessitate   changing   trans- 
former ratios  of  primary  and  secondary  turns,  as: 
Delta-star  is  a  constant  of  VS  =1.733  to  1. 

Star-delta  is  a  constant  of  — ;=  =0.577  to  1. 

\/3 

consequently,  special  ratios  of  secondary  to  primary  turns  are 
needed  in  delta-star  or  star-delta  transformers,  in  order  to  pro- 
duce standard  transformation  ratios. 

As  already  explained,  displacement,  of  phase  relations  occur 
on  the  secondary  side  of  transformers  when  two  or  more  groups 
are  connected  delta-delta  and  a  delta-star;  the  delta-delta  having 
a  straight  ratio  and  the  delta-star  a  ratio  of  1  to  0.577;  or  any 
of  the  following  combinations: 

Delta-star  ratio  —=  to  1^  and  star-star  with  ratio  1  to  1,  or 
\/3 

any  ratio. 

.      1 
Delta-delta,  ratio  1  to  1,  with  a  star-star  ratio  ~;Eto  1,  or  any 

vo 

ratio. 


THREE-PHASE  TRANSFOHMEH  DIFFICULTIES    91 

Star-delta,  ratio  1  to  —-^,  and  star-star  with  ratio  1  to  1,  or 

VO 

any  ratio. 

The  phase  relations  occupy  a  relative  shifting  position  of  30 
degrees  on  one  group  of  transformers  to  that  of  the  other.  A 
more  practical  representation  of  the  secondary  voltages  and 
phase  relations  of  a  delta-delta  and  delta-star  is  shown  in  Fig.  82. 

In  order  to  tie  in  a  large  number  of  local  existing  plants  con- 
sisting of  gas,  steam  and  water-driven  generators,  etc.,  with  two- 
and  three-phase  distributing  systems,  special  care  and  thought 
are  required  in  laying  out  the  right  scheme  of  connections.  One 
sometimes  meets  with  a  two-phase  three-  and  four-wire  distri- 
bution and  several  other  kinds  of  systems  of  odd  voltages  and 
frequencies  which  must  be  tied  in  on  the  main  high-voltage  trans- 
mission system  through  transformers  (and  probably  frequency 
changes),  all  of  which  requires  special  knowledge  on  the  part  of 
those  whose  duty  it  is  to  operate  them. 

Consolidated  systems  of  this  kind  generally  have  to  contend 
with  parallel  operation  of  local  power  plants,  this  sometimes 
being  done  directly  from  the  high  voltage  side  or  line  side  of  the 
power  transformers  for  voltages  as  high  as  60,000  volts,  by  the 
application,  of  potential  transformers.  Only  a  small  number 
use  this  method  of  synchronizing  their  auxiliary  stations  and  it 
is  not  considered  good  practice. 

Before  parallel  operation  of  any  kind  is  done  it  is  always 
advantageous  to  know  all  about  the  connections  and  voltages  of 
the  different  transformer  groups.  With  the  delta  and  star 
systems  it  is  (as  has  already  been  explained)  only  possible  to 
parallel  six  combinations  out  of  the  ten  so  commonly  used.  Of 
these  six  combinations  the  transformers  to  be  paralleled  must 
have  equal  impedance  and  equal  ratio  of  resistance  to  impedance. 
With  equal  impedance  the  current  in  each  unit  will  be  in  propor- 
tion to  their  rated  capacity  in  kw.'s,  although  the  sum  of  the 
currents  may  be  greater  than  the  current  in  the  line;  if,  on  the 
other  hand,  the  impedance  of  the  units  is  unequal,  the  current 
in  each  unit  will  be  inversely  proportional  to  its  impedance;  that 
is  to  say,  if  one  unit  has  1  per  cent,  impedance  and  the  other  2 
per  cent,  impedance,  the  first  unit  will  take  twice  as  large  a  per 
cent,  of  its  rated  capacity  as  the  second  unit — the  sum  of  the 
currents  in  the  two  units  may  be  or  may  not  be  equal  to  the  line 
current.     With  equal  ratios  of  resistance  to  reactance  the  current 


92 


STATIONARY  TRANSFORMERS 


in  each  unit  will  be  in  phase  with  the  current  in  the  line,  also  the 
sum  of  the  currents  will  be  the  same  as  the  line  current.  With 
unequal  ratios  of  resistance  to  reactance  the  current  in  each  unit 
will  not  be  in  phase  with  the  current  in  the  line,  therefore  the 
sum  of  the  currents  will  be  greater  than  the  line  current.  If, 
however,  the  impedance  of  the  units  is  the  same,  both  will 
carry  the  same  per  cent,  of  full-load  current;  and  if,  in  addition, 
the  ratio  of  resistance  to  reactance  is  the  same  in  both  cases,  the 
current  in  the  two  units  will  be  in  phase  with  each  other,  and 
their  numerical  sum  will  equal  the  load  current,  thus  there  will 
exist  perfect  parallel  operation. 


^AAAAJ  \ 


Vv«^AA_,_/y/VAA'V^ 


l^'V^V.  ^>N^^  j^S.^^  f^ ^"^^ 

&  \o    c\         \a  a\  b  c\  a  6 


Fig.  83. 


Whatever  scheme  of  transformers  is  decided  on  for  a  given 
system  it  will  always  be  advisable  to  keep  to  that  scheme  if 
possible;  this  is  particularly  applicable  on  some  of  the  larger 
systems  of  100  megawatts  and  over  where  networks  of  high- 
voltage  transmission  lines  and  sub-stations  are  numerous. 

Quite  a  number  of  systems  have  distance  sub-stations  with 
only  two  groups  of  transformers,  both  groups  being  operated  in 
parallel  at  all  times.  Assuming  the  transformers  to  be  con- 
nected in  delta-delta  and  one  transformer  of  one  of  the  groups 
becomes  damaged,  it  might  mean,  if  the  load  is  great,  that  at 
least  one  of  the  other  group  must  be  cut  out.  If  the  load  is  not 
greater  than  80  per  cent,  of  their  total  rating  it  will  be  possible 
under  ordinary  circumstances  to  operate  the  closed  delta  group 
with  the  open-delta  as  shown  in  Fig.  83. 

It  is  not  generally  known  that  there  are  sixteen  different  con- 
nections on  one  transformer  star-connected  group,  and  that  these 
connections  can  be  changed  about  to  obtain  several  parallel 
combinations,  such  as  those  shown  in  Fig.  84  giving  the  time- 
phase  of  0,  30,  60,  and  90  degrees  (electrical). 


THREE-PHASE  TRANSFORMER  DIFFICULTIES    93 


Primary  Conaection  of 
Transformers 


With 


Secondary  Connection  of 
Transformers 


In  Phase 


^^ 


60  degrees  out  of 
phase 


bt--  — 


^ 

Y 
X 


30  degrees  out  of 
phase 


A 


90  degrees  out  of 
phase 


Fig.  84. 


A 


94 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


Not  including  the  straight  star  or  delta  connection  with  a 
time-phase  angle  equal  to  zero,  we  find  that  there  are  no  less  than 
three  different  groups  such  that  transformers  belonging  to  the 
same  group  can  be  connected  in  parallel,  while  if  of  different 
groups,  no  parallel  connection  is  possible  without  a  special 
rearrangement  of  the  internal  connections  of  the  transformers. 


Fig.  85. — High-voltage  line  grounded,  producing  maximum  strain  on  low 
voltage  windings.     (Neutrals  non-grounded.) 

The  troubles   usually  experienced   with   high-voltage  trans- 
formers can  be  classified  as: 

(a)  Puncturing  of  the  insulation  between  adjacent  turns  due 
to  surges,  etc. 

(6)  Shifting  of  coils  duo  to  switching  on  and  off  very  heavy 
loads. 

(c)  Terminals  puncture   (transformer  insulator  bushing   and 
other  leads),  due  to  either  (a)  or  (b)  or  both. 

There  are  a  large  number  of  causes  for  transformer  break- 
downs, some  of  them  being : 

(1)  Insufficient  insulation  between  layers  and  turns. 


THREE-PHASE  TRANSFORMER  DIFFICULTIES    95 

(2)  Insufficient  insulation  on  the  end-turns. 

(3)  Electromagnetic  stresses  too  great. 

(4)  Electrostatic  capacity  of  certain  parts  too  high. 

(5)  Condenser  effect  between  coils,  and  between  windings  and 
ground  too  high. 

(6)  Improper  drying  out  after  construction. 

(7)  For  want  of  a  choke  coil  or  reactance  in  series. 

(8)  Concentrated    condensers   in  parallel  with   transformer 
windings. 


-E- 


B 

W-E-^E- 


^vA^N^  Un^'V^V/^  t'-N/S^.^ 


rrv^:^^^:^ 


—El 


-Ey — ^^e- 


—E^A^JJ,     \     1 


Fig.  86. — Showing  the  effect  of  grounding  the  low-voltage  neutral. 


(9)  Two  or  more  of  the  above  in  connection  with  concentrated 
condensers. 

(10)  Internal  short-circuits. 

(11)  Conditions  of  switching,  surges,  arcing  grounds,  lightning, 
etc. 

(12)  Improper  treatment  of  the  oil. 

(13)  Oil  not  suited  to  the  transformer. 

(14)  Thickening  of  oil  and  clogging  of  cooling  medium  stopped. 

(15)  Leaking  water-coils,  or,  circulation  of  cooling  medium 
stopped. 

(16)  Breathing  action  (prevalent  in  damp  localities). 


96  STATIONARY  TRANSFORMERS 

(17)  Improperly  installed  protective  apparatus. 

(18)  High  winds  which  bring  live  conductors  in  oscillation. 

(19)  Defective  governors  or  prime-movers. 

(20)  Variation  in  speed  of  generators. 

(21)  Variation  in  generator  voltage. 

(22)  Roasting  by  constant  over-load. 

(23)  Puncturing  of  transformer  terminals. 

(24)  When  transformers  are  connected  to  generating  stations 
and  systems  and  bus-bars  having  a  total  kw.  capacity  many 
times  greater. 

Figs.  85,  86,  and  87  show  other  causes  for  break-downs  in  high- 
voltage  transformers.  Three  different  conditions  of  operation 
are  given;  one  for  an  insulated  delta-delta  system  showing  the 
effects  of  a  grounded  live  conductor,  one  for  a  delta-delta  system 
with  the  neutral  point  of  low-voltage  windings  grounded,  and  the 
other  for  a  delta-delta  system  with  both  high-  and  low-voltage 
windings  grounded.  The  approximate  maximum  potential 
strains  are  shown  by  the  vector  relations.  These  serve  to  show 
other  greater  difficulties  which  receiving-station  transformers 
are  subjected  to  in  addition  to  those  usually  impressed  on  the 
transformers  at  the  generating  stations. 


CHAPTER  VI 

THREE-PHASE  TWO-PHASE  SYSTEMS  AND 
TRANSFORMATION 

With  two  or  three  single-phase  transformers  it  is  possible  to 
have  three-phase  primaries  with  two-phase  secondaries,  or  vice 
versa.  For  long-distance  transmission  of  electric  power  the 
three-phase  system  is  universally  adopted  because  it  requires 
less  copper  for  the  line  than  either  the  single-phase  or  the  two- 


M 


Uy^(\ri  l/N/vvJ  U./>^saI 


i^'iddc  kiac 


't 


-Ey- 


-r 


Fig.  87. — This  shows  the  effect  of    grounding    both  the  high-  and  low- 
voltage  neutrals,  resulting  in  minimum  voltage  strain. 

phase  systems  to  transmit  a  given  amount  of  power  with  a  given 
line  loss,  and  with  a  given  line  voltage.  The  two-phase  system 
offers  certain  advantages  over  the  three-phase  system  when 
applied  to  local  distribution  of  electric  power. 

In  Fig.  88  is  shown  the  well  known  three-phase  three-wire  to 
7  97 


98 


ST  A  TIONARY  TRANSFORMERS 


two-phase  four-wire  transformation.     Two  transformers  are  all 
that  is  necessary  in  this  arrangement,  one  of  which  has  a  10  to 

1  ratio  and  the  other  a  10  to  0.866.  or  10  to^. 


Fig.  88. — The  three-phase  two-phase  connection*  (Scott  system). 

One  wire,  6,  of  the  10  to  0.866-ratio  transformer  is  connected 
to  the  middle  point  of  the  10  to  1  ratio  transformer,  the  ends  of 
which  are  connected  to  two  of  the  three-phase  mains,  a  c;  d,  the 


wooo 


-1732 — >< — ^1732 


-1733 


<-iooo-^ 


-1000 


!!!4     ^'H 


W[JW 


100- 


-100- 


Fig.  89. — Three-phase  to  two-phase  star-connected  transformers. 

end  of  the  other  transformer  is  connected  to  the  remaining  wire 
of  the  three-phase  mains. 

It  is  customary  to  employ  standard  transformers  for  the  three- 
phase  two-phase  transformation,  the  main  transformer  having  a 
ratio  of  10  to  1,  and  the  other  transformer  a  ratio  of  9  to  1. 

*  Patent  No.  521051,  June  5th,  1894. 


THREE-PHASE  TWO-PHASE  SYSTEMS 


99 


Hy  a  conibination  of  two  transformers  it  is  possible  to  change 
one  polyphase  system  into  any  other  polyphase  system. 

The  transformation  from  a  three-phase  to  a  two-phase  system 
may  be  effected  by  proportioning  the  windings,  as  shown  in 
Fig.  89.  The  three  transformers  are  wound  with  a  ratio  of 
transformation  of  10  to  1.  The  secondaries  of  two  of  the  trans- 
formers have  two  taps  each,  giving  57.7  per  cent,  and  full  voltage, 
so  that  they  serve  as  one  phase  of  the  two-phase  transformation. 
The  primary  windings  are  connected  in  star. 

The  secondary  windings  are  also  connected  in  star.  In  Fig. 
89,  &  6'  represents  the  secondary  voltage  from  b  to  b'  in  one  trans- 


-lopo- 


'1000^ 


aooo' 


TnnjTnn  nnnnnri  rsr\jw 


-100- 


ra 


-138- 


-200- 


^ 


-100- 


-133- 


FiG.  90. 


former.  At  an  angle  of  90  degrees  to  6  6'  the  line,  a  a',  represents 
in  direction  and  magnitude  the  voltage,  a  to  a',  which  is  the 
resultant  of  the  two  remaining  transformer  e.m.fs.,  giving  577. 
per  cent,  of  the  full  voltage,  57.7  X\/3  =  100.  From  the  prop- 
erties of  the  angles  it  follows  that,  at  the  terminals,  a  a'  and  b  b' , 
two  equal  voltages  will  exist,  each  differing  from  the  other  by 
90  degrees,  and  giving  rise  to  a  two-phase  current. 

Still  another  method  of  getting  two-phase  from  three-phase, 
or  vice  versa,  consists  in  cutting  one  phase,  say  (Fig.  90)  the 
middle  transformer  of  the  delta-connected  group,  in  half,  and 
arranging  one-half  to  the  left  at  6'  c,  and  the  other  half  to  the 
right  at  6"  a. 

The  resultant  of  a  b'  and  &'  b  is  one  side,  or  one  phase  of  the  two- 
phase  transformation. 

The  resultant  of  a  b"  and  b"c,  is  the  other  phase  of  the  two- 
phase  transformation. 


100 


STATIONARY  TRANSFORMERS 


It  is  evident  as  shown  in  Fig.  90  that  the  two-phase  relation 
is  a  trifle  over  90  degrees;  since  the  angle,  6  b"  x  and  b  b'  x,  is 


60  degrees,  and  the  sine  of  60  degrees  is  equal  to 


V3 


0.866.  the 


V3 


tangent  of  the  angles,  b  c  x  and  b  ax,  are  likewise  -^^=0.866. 

Therefore,  the  angle,  ab  c,  must  equal  90  degrees  nearly. 

The  angle,  b  c  a,  whose  tangent  is  0.866  is  an  angle  of  40.67 

degrees;  therefore, 

(6  ca;  =  40.67) +  (&  a  a;  =  40.67)+ (a  6  c  =  98.66)  =40.67 +  40.67 + 

98.66  =  180  degrees,  nearly. 

The  approximate  voltage  obtained  between  c  6  and  fe  a  is  133 

volts. 


Fig.  91. — Three-phase  to  three-phase  two-phase*  (Steimnetz  system). 

With  two  or  more  transformers  it  is  possible  to  transform  from 
three-phase  to  two  distinct  phase  currents  of  three-phase  and 
two-phase  systems.  In  the  arrangement  shown  in  Fig.  91  only 
two  transformers  are  used.  The  two  primary  windings  are  con- 
nected to  the  three-phase  mains.  One  transformer  is  wound 
with  a  ratio  of  transformation  of  10  to  1.  The  other  with  a 
ratio  of  0.866  to  1.  The  primary  and  secondary  windings  of  this 
transformer  are  connected  to  the  middle  of  the  primary  and 
secondary  windings,  respectively,  of  the  first. 

a  b  represents  the  secondary  voltage  from  a  to  6  in  one  trans- 
former. At  right  angles  to  a  6  the  line,  x  c',  represents  in  direc- 
tion and  quantity,  the  voltage,  x  to  c',  of  the  second  transformer. 

*  Patent  No.  809996,  January  16th,  1906. 


THREE-PHASE  TWO-PHASE  SYSTEMS  101 


At  the  terminals,  ab  c,  three  equal  voltages  will  exist,  each 
differing  from  the  other  by  60  degrees,  and  giving  rise  to  a  three- 
phase  current. 


-1000- 


-1000 


U51AMM5J 


-1000- 


UftMiKMiU 


\'  n u 


z 


<— hco— J 


-100- 


-ico 


X 


-ico- 


FiG.  92. — Three-phase  "T"  to  two-phase  four-wire. 

It  also  follows  that,  at  the  terminals  a  b  and  x  c',  two  equal 
voltages  will  exist,  each  differing  from  the  other  by  90  degrees, 
and  giving  rise  to  a  two-phase  current.     As  will  be  noted,  the 


-1000- 


-1000- 


-1000- 


npsm 


m\ 


-8676- 


-100- 


-100- 


-100- 


B' 


Fig.  93. — Three-phase  open  delta  to  three-phase  two-phase  (Taylor  system). 

voltages  obtained  in  the  three-phase  side  are  equal  to  those 
between  any  phase  of  the  two-phase  system. 

The  arrangement  in  general  is  similar  to  that  of  the  ordinary 
"V"  or  open-delta  system. 


102 


STATIONARY  TRANSFORMERS 


Another  combination  somewhat  similar  to  the  above  is  shown 
in  Fig.  93.  The  primary  windings  of  the  two  transformers  are 
connected  in  open-delta.  The  secondary  windings  are  connected 
in  such  a  manner  as  to  give  two  distinct  phase  currents;  one 
kind  differing  in  phase  by  90  degrees,  and  the  other  by  120 
degrees.  From  one  secondary  winding  two  special  taps  of  50 
per  cent,  and  86.6  per  cent,  are  brought  out  to  complete  the 
circuits  of  three-phase  and  two-phase  secondary.  By  this 
method  of  connection  it  is  possible  to  obtain  two-phase  currents 
from  A  A'  and  B  B' ,  also  three-phase  currents  from  x  A' ,  A'  B, 
and  B  x,  the  two-phase  e.m.fs.  will  be  86.6  per  cent,  of  those  of 
the  three  phase. 

The  method  shown  in  Fig.  94  is  a  device  patented  by  the  writer, 


Fig.  94. — Three-phase  delta  to  three-phase  two-phase*  (Taylor  system). 

and  employed  to  operate  both  two-phase  and  three-phase  electric 
translating  devices,  on  one  four- wire  system  of  distribution;  and 
to  operate  independent  systems  in  parallel  circuit  on  said  four- 
wire  system. 

Three  single-phase  transformers  are  used.  The  primary  wind- 
ings are  shown  connected  in  delta,  and  the  secondary  windings 
also  connected  in  delta.  A  distribution  line,  7,  tapped  at  the 
middle  of  the  secondary  winding,  2a;  a  distribution  line,  8,  tapped 

\/3  •      . 

at  -— -  per  cent,  of  the  length  from  one  end  of  the  wmdmg,  3a;  a 

distribution  line,  9,  tapped  on  the  connection  between  the  end 

windings,  2a  and  3a;  a  distribution  line,  10,  tapped  at  -—-  per 


*  Patent  No.  869595,  October  29th,  1907. 


THREE-PHASE  TWO-PHASE  SYSTEMS 


103 


cent,  of  the  length  from  the  end  of  windhig  la,  and  translating 
means  connected  on  said  distribution  lines  both  for  two-  and 
three-phase  on. 

At  la,  2a  and  3a  are  the  secondary  windings  of  said  trans- 
formers. The  secondary  winding,  la,  is  tapped  at  D,  which  is 
about  86.6  per  cent,  of  its  length,  by  the  line,  10;  which  serves  also 
as  a  leg  for  both  the  two-  and  three-phase  circuits. 

The  secondary  winding,  2a,  is  tapped  at  its  central  point  A,  by 
a  line,  7 ;  forming  one  leg  of  the  two-phase  circuit.  The  secondary 
winding,  3a,  is  tapped  at  approximately  86.6  per  cent,  of  its 
length  from  one  end,  at  about  the  point,  B,  by  a  line,  8,  to  serve 


s 


\ 1  ,  I i  ^  ft^ 


Fig.  95. — Three-phase  to  two-phase,  giving  86  per  cent,  standard  trans- 
former taps. 

as  one  leg  of  both  the  three-  and  two-phase  circuits.  C  represents 
the  point  of  a  tap  taken  from  the  junction  of  two  secondary 
windings  which  are  shown  connected  in  the  series  circuit, 
which  serves  as  another  leg  for  both  two-  and  three-phase 
circuits. 

The  arrangement  accomplishes  the  operating  of  non-synchro- 
nous apparatus  of  two-phase  and  three-phase  design  without 
the  aid  of  transformers  or  split-phase  devices.  The  operation 
consists   in   generating   three-phase   alternating  currents  in  the 


104 


^TA  TIONA R  Y  TRA NSFORMERS 


lines,  4,  5  and  6,  transforming  the  same  into  three-phase  cur- 
rents in  the  legs,  8,  9  and  10,  and  into  two-phase  currents  in 
the  legs,  7,  8,  9  and  10;  and  in    operating  translating  devices 


EV3- 


< E > « E > 


^^A/wJ  IAAW\ 


AAA 


c^ 


<     e'     > 


Fig.  96. 


at  G  and  H  in  parallel  with  the  two-  and  three-phase  current 
circuits.     The  two-phase  windings  used  on  the  motors  must  be 


sA/yw/s 


-1000- 


J9         0 
1000 


-1000- 


-1000- 


WSAAA 


-1000 — > 

d 

Fig.  97. 


independent  as  the  interconnected  type  of  winding  would  not 
operate  on  this  system, 

A  three-phase  single-phase  transformation  is  shown  in  Fig.  98. 


THREE-PHASE  TWO-PHASE  SYSTEMS 


105 


The  objection  to  this  connection  is  the  distorted  effect  of  the 
relative  voltages  and  phase  relations  of  the  three-phase  when  a 
single-phase  load  is  put  on  one  of  the  phases.  To  obviate  this  to 
some  extent  it  would  be  necessary  to  give  the  three-phase  voltage 
a  slight  distortion.  The  unbalanced  voltages  and  phase  relation 
when  a  single-phase  load  is  applied  is  shown  by  the  vector  in  Fig. 
98,  it  having  the  effect  of  twisting  the  phase  relation  when  a  load 
is  applied  between  b-c  from  a  symmetrical  point  as  shown  at  the 
point  a'. 


-1000- 


-1000 — >- 


< 1000 — ^ 


Vv/VwJ  \AA/v/W 


/S^V^  /S^>s.^ 


-100- 


-100- 


a 
-100- 


FiG.  98. — Three-phase  to  single-pha.se. 


-1000- 


-^50oH*-eoo-* 


-1000- 


-1000- 


iMKMmJ 


100- 


fToooD"!       nmm 


-100- 


-141- 


FiG.  99. — Another  three-phase  single-phase  secondary  operation. 


It  is  possible  to  take  currents  from  a  three-phase  system 
and  transform  them  into  a  single-phase  current  (see  Fig.  99). 
All  that  is  necessary  is  to  arrange  two  transformers  so  that 
their  connections  are  identical  with  the  ordinary  two-phase  to 
three-phase  transformation,   the   only  difference  being  in  the 


106 


STATIONARY  TRANSFORMERS 


secondary,  which  has  the  two  windings  connected  in  series  for 
supplying  a  single-phase  circuit. 

In  the  ordinary  three-phase  to  two-phase  transformation,  the 
two  components  in  each  half  of  the  winding  differ  in  phase  by  90 


"Taylor* 


"Scott" 


"Meyer' 


"  Steinmetz ' 


v: 


T7 

/ 


Fig.  100. 


Two-phase  transformer  windings. 
Transformer  windings.  — 

Resultant  two-phase  voltages. 
Resultant  three-phase  voltages. 


degrees.     However,  when  the  secondary  circuits  are  connected 
in  series,  these  two  component  currents  are  of  one  phase. 

The  maj  ority  of  three-phase  two-phase  transformer  connections 
employed  are  for  temporary  or  special  purposes.     This  is  particu- 


FiG.  101. — Combination  of  systems  given  in  Fig.  100. 

larly  so  when  only  two  transformers  are  used.  The  systems  used 
in  Europe  and  America  are  shown  in  Fig.  100,  in  the  form  of 
vectors.  In  comparing  these  various  systems  by  means  of  the 
Vectors  given,  it  is  very  interesting  to  note  how  near  they  are  to 


THREE-PHASE  TWO-PHASE  SYSTEMS 


107 


being  one  and  the  same  thing.  The  relations  are  about  the  same 
but  the  transformers  in  each  case  are  connected  quite  dififerently. 
The  combinations  are  shown  in  Fig.  101.  In  (^1)  the  Meyer 
and  Steinmetz  are  combined  into  one;  in  (B)  the  Arnold  and 
Steinmetz  are  combined,  and  in  (C)  the  Scott  and  Taylor  systems 
are  shown  combined  into  one.  All  of  the  systems  given  here 
serve  to  show  their  likeness  and  are  interesting  to  all  those  who 
might  be  in  need  of  emergency  substitutes. 


\ 


Figs.  102  and  103. — Other  three-phase  two-phase  methods  using  standard 

transformer. 


Besides  these  systems  given  in  Figs.  100  and  101  there  are 
other  connections  of  less  value  but  nevertheless  important  in 
that  they  might  be  found  useful  in  some  particular  instant  of 
break-down  of  existing  apparatus,  or  for  temporary  purposes. 
These  are  shown  in  Figs.  102  and  103,  where  (a)  is  composed  of 
two  single-phase  transformers  of  10  to  1  and  9  to  1  ratio 
respectively,  or  of  two  10  to  1  ratio  transformers,  one  of  the 
transformers  being  tapped  at  the  9  to  1  ratio  point  and  connected 
to  the  50  per  cent,  point  of  the  other  transformers.  (6)  is  the  ordi- 
nary delta  connection  with  the  two  halves  of  one  winding  or 
one  single-phase  unit  reversed,  (c)  is  the  ordinary  delta  system 
with  taps  taken  off  as  shown,  (d)  is  the  ordinary  star  with  one 
transformer  secondary  winding  cut  into  three  equal  parts,  (e) 
is  a  "distributed"  star,  1-1  a,  2-2a  and  3-3a  representing  three 


108  STATIONARY  TRANSFORMERS 

single-phase  transformers  with  winding  cut  into  two  equal  parts 
and  connected  as  shown.  (/)  is  a  star  connection  with  one  trans- 
former winding  reversed,  (g)  is  an  ordinary  open-delta  connec- 
tion. With  the  exception  of  (a)  and  (g)  which  consist  of  two 
single-phase  transformers,  all  the  others  are  three-phase  two- 
phase  combinations  using  three  single-phase  transformers. 

By  the  use  of  transformers  other  than  standard  ratios  and 
design,  the  three-phase  two-phase  transformer  combinations 
shown  in  Fig.  104  can  be  made. 


CHAPTER  VII 

SIX-PHASE  TRANSFORMATION  AND  OPERATION 

In  transforming  from  three-phase  to  six-phase  there  are  four 
different  ways  of  connecting  the  secondaries  of  the  transformers: 
namely,  diametrical — ^with  or  without  the  fixed  neutral  point; 
double  star;  double  delta;  and  double  tee.  In  the  first  three  cases 
the  primaries  may  be  connected  either  star  or  delta,  according  to 
the  voltage  that  each  winding  will  stand,  or  to  obtain  a  required 


Fig.  104. — Three-phase  to  two-phase  using  special  transformer  tops. 

secondary  voltage.     In  the  last  case,  the  primary  windings  are 
connected  in  tee. 

For  the  diametrical  connection  three  single-phase  transformers 
may  be  used  with  one  central  tap  from  each  transformer  second- 
ary winding,  or  there  may  be  six  secondary  coils.  For  the 
double-star  or  double-delta  connection  two  independent  second- 
ary coils  are  required  for  each  transformer;  the  second  set  are  all 

109 


110 


STATIONARY  TRANSFORMERS 


reversed,  then  connected  in  a  similar  manner  to  the  first  set. 
Hence,  the  phase  displacement  is  shifted  180  degrees. 

For  the  double-tee  connection  two  single-phase  transformers 
are  required,  one  of  which  has  a  10  to  1  ratio  and  the  other  a  10 

to  0.866,  or  10  to  ^  ratio. 

There  are  two  secondary  coils  giving  10  to  1  ratios,  and  two 
giving  10  to  0.866  ratios. 

In  six-phase  circuits  there  are  coils  with  phase  displacements 
of  60  degrees;  each  coil  must  move  through  180  electrical  degrees 
from  the  position  where  the  current  begins  in  one  direction,  before 


Fig.  105. — Six-phase  diametrical  e.m.fs.  and  phase  relation. 

the  current  begins  to  reverse.  Hence,  for  the  double  star, 
diametrical,  double  delta  and  double-tee  connections  if  the  ends 
of  the  transformer  coils  are  reversed,  the  phase  displacement  of 
the  e.m.f.  is  in  effect  shifted  180  electrical  degrees. 

Take,  for  instance,  the  e.m.fs.,  a  a',  hh'  and  c  c' ,  as  graphically 
explained  in  Figs.  106  and  107,  for  a  diametrical  connection  they 
are  equal  io  2  a  x,  2  h  x,  2  c  x,  etc. 

For  double-star  connection: 

a  ¥,  h'  c,  c  a,  etc.,  is  V  3  times  x  a,  x  h' ,  x  c,  etc. 

For  double-delta  connection: 

xa,  x  b',  X  c,  etc.,  is  —7-  =0.577  per  cent,  of  a  h' ,  h"  c,  c  a,  etc. 
For  double-tee  connection: 


SIX-PHASE  TRANSFORMATION  AND  OPERATION   111 

a  b',  ¥  c,  c  a,  etc.,  is  13.3  per  cent,  more  than  a'  y,  or  a  z. 

The  general  statement  of  relationship  between  e.m.fs.  in  Fig. 
106  may  demonstrate  that  if  the  value  of  a  a',  etc.,  is  represented 
by  the  diameter  of  a  circle,  the  values  of  a'  h,  etc.,  are  repre- 


a 

^'^^^"^^^ 

l^\[     *-^^ 

^^^   ^1^  f 

\    ^V.            ^'**S^ 

.^^    .^^    / 

\          ^s^^            X. 

,/y^  J 

\ 

i\ — .  *       /       1/ 

\ 

\^s^      / 

\         ^^^ 

\          ^Sw/ 

"^^^           ^ 

\         /^\^ 

^^\    / 

\         /                                                     ^^ 

^^                           \   / 

2  A   y 

<^                / 

^^^.         /      ^ 

V-         \y^ 

^^^^^/         ^ 

,/x^\ 

*           / 

___——_  —  ^__  — 

^^^^ 

Fig.  106. — Six-phase  e.m.fs.  graphically  represented. 

sented  by  a  120-degree  chord,  and  the  values  of  a  6,  etc.,  are 
represented  by  a  60-degree  chord  of  the  same  circle. 

If  the  voltage  between,  a  6,  etc.,  is  not  required,  only  three 
secondary  coils  are  needed;  but  if  this  voltage  should  be  required, 


|<        1000—^  <= 1000 — »■  < — looo — ^ 


100 
-60- 


nnnjTi 


-100- 
-50- 


(VS^ 


-100- 


-50»^ 


Fig.  107. — Six-phase  diametrical  connection. 

then  six  secondary  coils  are  needed,  or  three  coils  with  a  center 
tap  like  that  shown  in  Fig.  107.  The  diametrical  connection  of 
transformer  secondaries  as  represented  in  Fig.  107  is  the  most 
commonly  used  of  any  three-phase  to  six-phase  transformations. 
One  secondary  coil  on  each  step-down  transformer  is  all  that  is 


112 


STATIONARY  TRANSFORMERS 


necessary;  whereas  the  double-star,  double-delta,  and  double-tee 
connections  require  two  secondary  coils,  and  therefore  four 
secondary  wires  for  each  transformer. 

The  two  secondary  wires  from  each  transformer  are  connected 
to  the  armature  winding  of  a  rotary  converter  at  points  180  degrees 
apart — such  as  shown  at  a  a' ,  b  h' ,  c  c' ;  therefore,  arrangements 
for  the  diametrical  connection  are  much  simpler  than  any  of  the 
others. 

A  part  of  the  three-coil  secondary  diametrical  connection  may 
be  used  for  induction-motor  service  to  start  the  rotary  converter. 


-1000- 


-1000- 


-1000 


Fig.  108. — Six-phase  diametrical  connection  with  five-point  switch  used  in 
connection  with  motor  for  starting  synchronous  converters. 


and  when  sufficient  speed  is  obtained  the  motor  may  be  cut  out 
of  service.  The  arrangement  is  shown  in  Fig.  108.  By  means  of 
this  connection,  which  is  made  through  the  introduction  of  a 
five-pole  switch,  a  three-phase  e.m.f.  may  be  obtained,  giving  a 
value  equal  to  half  the  e.m.f.  of  each  secondary  winding  times 
V  3.  That  is  to  say,  if  half  the  e.m.f.  of  each  secondary  winding 
is  equal  to  50  volts,  then  assuming  the  switch  to  be  closed,  we 
obtain  50X\/3=86.6  volts. 

Similar  ends  of  the  three  windings  are  connected  to  three  points 
on  one  side  of  the  five-pole  switch.     The  three  wires  on  the  other 


SIX-PHASE  TRANSFORMATION  AND  OPERATION   113 

side  of  the  switch  are  led  off  to  the  three-phase  motor  service.  The 
two  remaining  points  of  the  switch  receive  three  wires  from  the 
neutral  points  of  the  three  secondary  windings.  Connections  are 
so  made  that  when  the  switch  is  closed  a  star-connection  is 
obtained. 

With  the  double-star  arrangement  of  secondary  windings, 
shown  in  Fig.  109,  a  rotary  converter  may  be  connected  to  a  given 
three  of  the  six  secondary  coils,  or  one  rotary  may  be  connected 
to  the  six  secondary  coils.  The  disadvantage  of  star  connection 
is  that  in  case  one  transformer  is  burned  out,  it  is  not  possible  to 
continue  running. 


—1000 — -*p-- 1000 — -^ — ^1000 — > 


Fig.  109. — Six-phase  double-star  connection. 


An  arrangement  for  six-phase  transformation  is  shown  in  Fig. 
1 10,  which  differs  from  that  of  Fig.  109  in  that  the  middle  point  of 
each  transformer  winding  is  tied  together  to  form  a  neutral  point 
for  the  double  star  combination. 

It  is  common  practice  to  connect  the  neutral  wire  of  the  three- 
wire,  direct-current  system  to  the  neutral  point  of  the  star 
connection. 

It  may  be  seen  that  the  similar  ends  of  the  two  coils  of  the  same 
transformer  or  similar  ends  of  any  two  coils  bearing  the  same 
relation  to  a  certain  primary  coil  are  at  any  instant  of  the  same 
polarity. 

The  double-delta  secondary  arrangement  should  preferably  be 
connected  delta  on  the  primary,  as  it  permits  the  system  to  be 
operated  with  only  two  transformers,  in  case  one  should  be  cut 
out  of  circuit. 

8 


114 


STATIONARY  TRANSFORMERS 


One  set  of  the  three  secondary  coils  is  connected  in  delta  in  the 
ordinary  way,  but  the  leads  from  the  second  set  are  reversed  and 
then  connected  in  a  similar  manner. 

It  can  be  seen  from  Fig.  Ill  that  two  distinct  delta  connections 
are  made,  and  in  case  it  is  desired  to  connect  the  six  leads,  ab  c- 
a'  h'  c' ,  to  a  six-phase  rotary  converter  it  is  necessary  that  each 
be  connected  to  the  proper  rings. 

The  double-tee  connection  requires  only  two  transformers,  and 
so  far'as  concerns  the  cost  of  the  equipment  and  the  efficiency  in 


-1000 — > 


-1000 — > 


-1000 — > 


UMMiU  UMMiU  UM^ 

n^    nyn    nnn    n)Fi    cw\   nJFi 


<-50-H  ■^-M 

— • 'V 


-50  VJ- 
-100 — 


-50- 


•^50- 


-501^ 
-100 — 


-50  >S^ 
-50F3=- 
-50VsP- 


-50- 


-50- 


-100- 


-50  vF- 


FiG.  110. — Six-phase  double-star  with  one  neutral  point  for  the  six  secondary 

windings. 

operation  two  tee-connected  transformers  are  preferable  to  the 
delta  or  star  connections.  This  connection  can  be  used  to  trans- 
form two-phase  to  six-phase,  and  from  three-phase  to  six-phase. 

It  is  worthy  of  note  that  the  transformer  with  the  86.6  per  cent, 
winding  need  not  necessarily  be  designed  for  exactly  86.6  per 
cent,  of  the  e.m.f.  of  the  other  transformer;  the  normal  voltage 
of  one  can  be  90  per  cent,  of  the  other,  without  producing  detri- 
mental results. 

Fig.  112  represents  the  tee-connection  for  transforming  from 
three-phase  to  six-phase  e.m.fs. 

With  reference  to  its  ability  to  transform  six-phase  e.m.fs.  and 
maintain  balanced  phase  relations,  the  tee-connection  is  much 
better  than  either  the  delta  or  star  connections. 

Another  interesting  method  of  ti'ansforming  from  three-phase 
or  two-phase  to  six-phase  is  shown  in  Fig.  113.     The  two  trans- 


SIX-PHASE  TRANSFORMATION  AND  OPERATION   115 

formers  bear  the  ratio  of  10  to  1  and  10  to  0.866,  as  explained  in 
the  previous  example.  For  a  two-phase  primary  supply,  A  A' 
is  tapped  on  one  phase,  and  B  B'  is  tapped  on  the  other;  the  line, 
X,  being  cut  loose.     For  a  three-phase  primary  supply  the  lines. 


-1000- 


-1000- 


a^ -^6' 


-1000- 


MJtflQflflfla.J        LflJKlfiflfifl.O.QQJ  LfififiaAflAflflA. 


UaiLn  ,   rvQQOn 


csm 


fm\ 


-100— >f*— 50 — >K-100- 
-8676- 


jnJUULI 


JW| 


-100- 


— 86t6 
6' 
Fig.  Ill . — Six-phase  double-delta  combination. 

A,  A' ,  and  B,  are  connected  to  the  three-phase  mains.     The 
secondary  connections  in  both  cases  remain  the  same. 

If  a  neutral  wire  is  required  as  in  the  case  of  the  three-wire, 
direct-current  system,  it  may  be  taken  from  the  point,  y.     For 


J 

-1000- 


-1000- 


-± 


-1000- 


mm 


mmmw 


KSiSim 


mw 


nrfiSI 


-100- 


W^ 


"■   I  * 


-S6.6- 


-100- 


b' 


.6^  "^100^ 


.^"'"■^V^' 


/ 


/ 

/ 


\ 


\ 


^, 


>' 


6^-- 


\ 
\ 

^- 
/ 


*  Fig.  112, — Six-phase  tee  connections. 


running  a  blower  motor,  or  to  furnish  current  for  running  the 
rotary  converter  up  to  synchronous  speed  by  an  induction  motor 
mounted  on  the  same  shaft,  any  one  of  the  two  secondary  tee- 


116 


STATIONARY  TRANSFORMERS 


connections  may  be  used.  The  three-phase  e.m.f.  obtained 
would  have  a  value  equal  to  the  full  secondary  voltage  used  for  the 
rotary  converter. 


a'     B' 


-1000- 


JiMfiikilQ. 


-1000- 


\smmmj 


-This  wire  for 
three-phase 


I — \mEm 


Tnnnjwrsr-, 


-100- 


-100- 


-u 


3  'n 


Neutral  wire 


.j^  Three-phase 
V        Motor 


Fig.  113.— Six-phase  from  three-phase  or  two-phase. 


Double-delta 

'1 


Delta 


Fig.  114.— General  group  of  six-phase  transformer  combinations. 

Fig.  114  shows  all  the  six-phase  transformer  combinations  in 
use  at  the  present  time. 


CHAPTER  VIII 

METHODS  OF  COOLING  TRANSFORMERS 

Small  transformers  do  not  require  special  cooling  devices  since 
they  have  large  radiating  surface  compared  with  their  losses. 
Large  transformers  will  not  keep  cool  by  natural  radiation;  some 
special  cooling  devices  must  be  provided. 

The  various  cooling  methods  are: 

Self-cooling  dry  transformers. 

Self-cooling  oil-filled  transformers. 

Transformers  cooled  by  forced  current  of  air. 

Transformers  cooled  by  forced  current  of  water. 

Transformers  cooled  by  forced  current  of  oil. 

Transformers  cooled  by  some  combination  of  above  means. 

Self-cooling  Dry  Transformer. — ^Transformers  of  this  kind  are 
usually  of  small  output,  and  do  not  require  any  special  means  of 
cooling,  the  natural  radiation  being  depended  upon  for  cooling. 

Self-cooling  Oil  Transformers. — ^This  arrangement  is  employed 
for  at  least  60  per  cent,  of  transformers  in  use,  the  core  and  coils 
being  immersed  in  oil.  The  two  advantages  gained  by  immersing 
these  transformers  in  oil,  are:  Insulation  punctures  can  in  many 
cases  be  immediately  repaired  by  the  inflow  of  oil,  and  the 
temperature  is  reduced  by  ojfifering  means  of  escape  for  the  heat. 

Many  manufacturers  depend  upon  the  high  insulating  qualities 
of  the  oil  itself,  and,  therefore,  introduce  less  insulating  material 
such  as  cambric  and  mica,  etc.  On  the  other  hand  if  oil  is  punc- 
tured it  will  close  in  again,  unless  the  puncture  be  the  result  of  a 
short-circuit  in  the  transformer,  in  which  case  an  explosion  is 
liable  to  occur,  or  a  fire  started.  In  this  way  electric  plants  have 
been  destroyed. 

For  the  purpose  of  obtaining  the  necessary  radiating  surface, 
tanks  of  the  large  self-cooled  transformers  of  many  manufacturers 
are  made  of  thin  corrugated  steel  or  cast  iron.  The  thin  cor- 
rugated steel  metal  tanks  are  not  sufficiently  strong  to  be  safely 
handled  in  transportation  with  the  transformers  in  them.  A 
slight  blow  is  sufficient  to  cause  the  oil  to  leak  at  the  soldered 

117 


118  STATIONARY  TRANSFORMERS 

seams  between  the  different  sheets  of  thin  steel,  or  at  the  joints 
between  the  sides.  The  cast-iron  case  is  unquestionably  the 
best,  and  the  most  suitable  for  oil  transformers;  the  great  strength 
and  stability  of  cast-iron  cases  insure  the  safe  transportation  of 
the  transformer. 

In  the  design  of  oil-insulated  transformers,  interior  ventilation 
is  provided  by  oil  passages  or  ventilating  ducts,  between  the 
coils,  and  in  the  iron.  These  secure  an  even  distribution  of  heat 
and  a  uniformity  of  temperature  throughout  the  transformer, 
results  which  can  be  secured  only  by  a  free  internal  circulation 
of  oil. 

Without  good  oil  circulation,  transformers  of  large  size  may 
reach  an  internal  temperature  greatly  in  excess  of  that  of  the 
external  surface  in  contact  with  the  oil,  and  in  poorly  designed 
transformers  this  may  lead  to  the  speedy  destruction  of  the  insu- 
lation of  the  coils. 

The  number  and  size  of  the  oil  passages,  or  ventilating  ducts 
are  planned  to  keep  all  parts  of  the  transformer  about  evenly 
cooled.  Such  ducts  necessarily  use  much  available  space  and 
make  a  transformer  of  a  given  efficiency  more  expensive  than  if  the 
space  could  be  completely  filled  with  copper  or  iron.  Experience 
with  oil-insulated  transformers  of  large  size  and  high  voltage  has 
shown  that  oil  increases  the  life  of  the  insulation,  in  addition  to 
acting  as  a  cooling  medium,  and  adds  materially  to  the  capability 
of  the  transformer  to  resist  lightning  discharges,  in  other  words 
such  a  transformer  is  safer  than  a  dry  transformer. 

The  amount  of  heat  developed  in  a  transformer  depends  upon 
its  load  and  its  efficiency.  In  a  500-kw.  transformer  of  98.5  per 
cent,  efficiency  there  is  a  loss  at  full  load  of  7.0  kw.  Since  this 
loss  appears  as  heat,  it  must  be  disposed  of  in  some  way  or  the 
temperature  will  rise  until  it  becomes  dangerously  high. 

The  self-cooled  oil-insulated  transformer  is  now  made  in  sizes 
up  to  3000  kv-a  capacity  and  represents  one  of  the  best  advances 
in  the  manufacture  of  transformers.  This  new  design  is  a  very 
important  development  of  the  art  of  transformer  manufacture. 
This  type  will  be  more  in  demand  than  the  air-cooled  type  (air- 
blast)  where  water  is  or  is  not  available,  is  expensive  or  not  suffi- 
cient. It  requires  a  minimum  amount  of  attention  and  no 
auxiliary  apparatus  or  equipment.  The  great  problem  to  be 
solved  in  this  type  was  that  of  providing  sufficient  surface  to 
radiate  the  heat  generated  and  keep  the  temperature  rise  within 


METHODS  OF  COOLING  TRANSFORMERS        119 

certain  limits.  The  total  amount  of  surface  broken  up  into 
corrugations  depends  on  its  efficiency  which  may  be  defined  as 
the  watts  radiated  per  square  inch  of  surface,  as  well  as  on  the 
amount  of  heat  to  be  radiated.  A  plain  surface  is  found  to  be 
the  most  efficient  as  both  the  air  and  oil  come  into  close  contact 
with  it,  but  as  it  is  broken  up  into  corrugations,  the  efficiency  is 
decreased  slightly.  The  most  modern  self-cooled  type  is  pro- 
vided with  auxiliary  pipes  or  radiators  whereby  the  actual  surface 
of  the  tank  can  be  greatly  increased  and  at  the  same  time  the 
radiating  efficiency  of  the  surface  kept  very  high.  The  method 
of  cooling  consists  essentially  of  fitting  the  outside  of  a  plain 
cast-iron  or  plain  boiler-plate  tank  with  a  number  of  vertically 
arranged  tubes,  the  upper  ends  of  which  enter  the  tank  near  the 
top  and  the  lower  ends  near  the  bottom. 

An  idea  of  the  limitations  in  this  direction  can  be  best  obtained 
by  making  a  rough  comparison  of  two  transformers  of  widely 
different  kv-a  capacities. 

Assume  for  a  small  transformer  100  kv-a  capacity,  and  for  a 
large  transformer  one  of  4000  kv-a  capacity.  Now,  if  the  same 
densities  obtain  in  both  copper  and  iron,  namely,  if  the  larger 
transformer  has  losses  proportional  to  the  increase  in  output,  the 
losses  will  be  increased  4000-^100  =  40  times,  while  the  area  or 
surface  of  radiation  would  only  be  increased  about  one-fourth 
as  much  as  the  losses.  From  this  method  of  comparison  it  is 
seen  that  in  order  to  keep  the  heating  within  proper  limits  it  is 
necessary  considerably  to  increase  the  size  of  the  transformer, 
resulting  in  a  cost  very  much  greater  than  that  of  a  transformer 
having  auxiliary  means  of  cooling.  For  this  reason  self-cooled 
oil-insulated  transformers  are  not  generally  manufactured  in 
sizes  above  2000  kv-a.  For  sizes  up  to  about  500  kv-a,  the  tank 
is  single  corrugated  and  above  this  size  compound  corrugations 
are  used  to  obtain  the  necessary  radiating  surface. 

Hot  air  tends  to  flow  upward,  so  that,  in  providing  for 
station  ventilation,  it  is  essential  that  the  inlet  of  the  cool  air 
should  be  low  down  and  the  outlet  somewhere  near  the  roof, 
the  inflow  and  outflow  of  air  being  well  distributed  about  the 
station. 

Self-cooled  oil-insulated  transformers  of  large  size  should  be 
given  good  ventilation  or  else  the  life  of  the  transformer  will  be 
shortened.  The  first  indication  of  increased  temperature  will  be 
darkening  of  the  oil  and  a  slight  deposit  on  the  inside  surfaces 


120  STATIONARY  TRANSFORMERS 

of  the  transformer.  Once  this  deposit  begins  to  form  the  tend- 
ency is  quickened  because  of  the  decreased  efficiency  of  heat  dissi- 
pation from  the  transformer. 

In  this  type  of  transformer  the  only  remedy  where  the  oil  has 
thickened  to  a  considerable  extent  and  a  deposit  accumulated,  is 
to  thoroughly  clean  the  transformer  by  scraping  off  the  deposit 
and  washing  it  out  with  oil  under  high  pressure. 

Transformers  Cooled  by  Forced  Current  of  Air. — ^This  type  of 
transformer  is  commonly  called  the  "air  blast,"  and  may  be 
wound  for  any  desired  voltage  not  exceeding  40,000. 

Air-blast  transformers  are  cooled  by  a  blast  of  air  furnished 
by  a  blower.  The  blower  may  deliver  air  directly  into  a 
chamber  over  which  the  transformer  is  located,  or  if  it  is 
more  convenient,  the  blower  may  be  located  at  a  distance 
from  the  transformer,  feeding  into  a  conduit  which  leads  to 
the  air  chamber.  The  blower  is  usually  direct  connected  to  an 
induction  motor,  though  it  may  be  driven  by  other  means.  One 
blower  generally  supplies  a  number  of  transformers  in  the  same 
station,  and  the  transformers  are  usually  spaced  above  an  air 
chamber,  in  which  a  pressure  is  maintained  slightly  above  that 
of  the  surrounding  air.  The  air  for  cooling  the  iron  passes  from 
the  lower  housing  selected  to  suit  the  transformer  capacity.  When 
the  efficiency  of  an  air-blast  transformer  is  known,  an  approximate 
estimate  of  the  amount  of  air  required  can  be  made  by  allowing 
150  cu.  ft.  of  air  per  minute  for  each  kilowatt  lost.  For  the  most 
satisfactory  operation,  the  velocity  of  the  air  in  the  chamber 
should  be  as  low  as  possible,  and  should  never  exceed  500  ft.  per 
minute.  That  is,  the  cross-section  of  the  chamber  in  square  feet 
should  at  least  be  equal  to  the  number  representing  the  total 
volume  of  air  required  per  minute  by  the  transformer,  divided 
by  500.  The  power  required  to  drive  the  blower  for  furnishing 
air  to  the  transformers  is  so  small  as  to  be  practically  negligible, 
amounting  in  most  cases  to  only  a  fraction  of  1  per  cent,  of  the 
capacity  of  the  transformers. 

The  three-phase,  air-blast  shell-type  transformer,  when  delta 
connected,  has  the  same  advantage  as  three  single-phase  trans- 
formers of  the  same  total  rating  that  is,  by  disconnecting  and 
short-circuiting  both  windings  of  a  defective  phase,  the  trans- 
former can  be  operated  temporarily  at  two-thirds,  or  thereabout, 
of  the  total  capacity  from  the  two  remaining  windings. 

Coming  under  this  heading  of  transformers  cooled  by  forced 


METHODS  OF  COOLING  TRANSFORMERS        121 

current  of  air,  there  exist  two  methods,  viz.,  oil-insulated  trans- 
formers cooled  by  means  of  an  air-blast  on  the  outside  of  the  tank, 
and  those  in  which  the  air  is  forced  directly  between  the  coils, 
and  through  ducts  in  the  laminations. 

The  forced  air-cooled  transformer  may  be  of  the  shell  type  or 
core  type,  but  preferably  of  the  former  for  large  or  moderate  sizes. 

The  question  of  air-blast  against  oil-cooled  transformers  has 
been  settled  in  practice  long  ago  in  favor  of  the  oil-cooled  type. 
Some  of  the  chief  advantages  claimed  are  the  additional  safety 
due  to  the  presence  of  the  oil  round  the  windings,  and  the  exclu- 
sion of  a  forced  current  of  air  and  consequently  exclusion  of  dirt 
and  dust  from  all  parts  of  the  windings. 

Three-phase  transformers  require  larger  air  chambers  than 
single-phase  transformers  of  the  same  total  capacity.  The  tem- 
perature of  the  out-going  air  compared  with  the  temperature  of 
the  in-going  air  is  the  best  indication  whether  sufficient  air  is 
passing  through  the  transformers,  but  in  general,  and  on  the  basis 
of  25°  C,  the  best  results  are  obtained  when  the  temperature  of 
the  incoming  air  is  not  greater  than  this  value.  Depending  on 
the  temperature  of  the  surrounding  air  or  entering  air,  the  out- 
going air  will  leave  the  transformer  greater  or  smaller  as  the 
case  may  be.  Also,  depending  on  the  design,  the  difference 
in  temperature  of  the  supply  of  air  and  the  air  leaving  the  trans- 
former will  vary  between  12°  and  20°  C. 

The  insulation  of  air-blast  transformers  must  be  impervious 
to  moisture,  and  must  have  superior  strength  and  durability. 
It  must  also  permit  the  ready  discharge  of  the  heat  generated 
in  the  windings,  as  otherwise  the  transformer  temperature  may 
reach  a  value  high  enough  to  endanger  the  life  of  the  insulation. 
In  building  such  a  moisture-proof  insulation,  the  coils  are  dried 
at  a  temperature  above  the  boiling  point  of  water,  by  a  vacuum 
process  which  thoroughly  removes  all  moisture.  After  a  treat- 
ment with  a  special  insulating  material,  they  are  placed  in  drying 
ovens,  where  the  insulating  coating  becomes  hard  and  strong. 
Then  the  coils  are  taped  with  an  overlapped  covering  of  linen  and 
again  treated  and  dried,  there  being  several  repetitions  of  the 
process,  depending  on  the  voltage  of  the  transformer.  The 
insulating  materials  are  so  uniformly  applied  and  the  varnish  so 
carefully  compounded  that  the  completed  insulation  on  the  coils 
is  able  to  withstand  potentials  two  or  three  times  greater  than 
the  same  thickness  of  the  best  insulating  oil. 


122  STATIONARY  TRANSFORMERS 

Transformers  Cooled  by  Forced  Current  of  Water. — This  type 
of  transformer  is  usually  called  "  oil-insulated,  water-cooled." 

Inside  the  cast-iron  tank  and  extending  below  the  surface  of  the 
oil,  are  coils  usually  of  seamless  brass  tubing  through  which  the 
cooling  water  circulates.  These  coils  are  furnished  with  valves 
for  regulating  the  flow  of  water,  and  the  proper  adjustment 
having  once  been  made,  the  transformer  will  run  indefinitely 
with  practically  no  attention.  Another  method  of  cooling  is  by 
drawing  off  the  oil,  cooling  it,  and  pumping  it  back,  the  operation 
being  continuous.  In  the  design  of  oil-insulated,  water-cooled 
transformers,  interior  ventilation  is  provided  by  oil  passages 
between  the  coils,  and  in  the  iron.  These  secure  an  even  distri- 
bution of  heat  and  a  uniformity  of  temperature  throughout  the 
transformer.  Without  good  oil  circulation,  transformers  of 
large  size  may  reach  an  internal  temperature  greatly  in  excess 
of  that  of  the  external  surface  in  contact  with  the  oil.  As  a 
means  of  securing  the  best  regulation,  oil  insulation  is  of  immense 
advantage  inasmuch  as  it  permits  close  spacing  of  the  primary 
and  secondary  windings.  It  effects  great  economy  of  space,  and 
its  fluidity  and  freedom  from  deterioration  greatly  assist  in 
solving  the  difficult  problems  of  transformer  insulation.  Its 
good  qualities  come  into  play  with  remarkable  advantage  in 
building  high-potential  transformers. 

Water-cooling  coils  are  made  of  seamless  tubing  capable  of  with- 
standing a  pressure  of  from  150  to  250  pounds  per  square  inch. 

Transformers  Cooled  by  a  Combination  Method. — ^Transformers 
cooled  by  this  method  require  the  service  of  a  pump  for  circu- 
lating the  oil.  The  oil  is  forced  upward  through  spaces  left  around 
and  between  the  coils,  overflows  at  the  top,  and  passes  down  over 
the  outside  of  the  iron  laminations.  With  such  a  scheme  trans- 
formers can  be  built  of  much  larger  capacities  than  the  largest 
existing  water-cooled  transformers  of  the  ordinary  type,  without 
such  increase  in  size  as  to  show  prohibitive  cost  and  to  necessitate 
transportation  of  the  transformers  in  parts  for  erection  at  the 
place  of  installation.  The  forced-oil  system  allows  the  circulation 
of  the  oil  to  be  increased  to  any  extent,  thereby  producing  a  rapid 
and  positive  circulation  which  greatly  increases  the  cooling 
efficiency  of  the  fluid.  Moreover,  this  method  of  oil  circulation 
ensures  such  uniform  and  positive  cooling  that  much  higher 
indicated  temperatures  may  safely  be  permitted  in  transformers 
operating  at  moderate  overloads. 


METHODS  OF  COOLING  TRANSFORMERS        123 

With  ample  capacity  provided  in  oil-  and  water-circulating 
pumps,  the  transformer  can  without  danger  be  called  upon  to 
carry  extreme  overloads  under  emergency  conditions.  Trans- 
formers of  the  forced-oil  type  have  recently  been  built  for  a  nor- 
mal capacity  of  7500  kilowatts,  and  are  actually  capable  of  carry- 
ing 10,000  kilowatts  continuously  at  a  safe  temperature. 

Of  the  very  large  modern  designs  of  forced-oil  type  transform- 
ers two  methods  of  cooling  are  employed.  The  old  method  was 
to  place  the  cooling  apparatus  outside  of  the  tank,  and  the  new 
method  is  to  place  the  cooling  apparatus  inside  the  transformer 
tank,  the  external  in  this  case  not  being  employed.  Not  unlike 
the  water-cooled  type  the  cooling  coil  is  placed  inside  of  the 
tank  except  that  it  reaches  much  lower  down  into  the  tank  than 
the  water-cooled  type.  A  cylindrical  or  elliptical  metal  casing, 
depending  on  the  form  of  tank,  separates  this  coil  from  the  oil- 
chamber  with  the  exception  of  one  or  two  openings  at  the  bottom. 
The  oil  is  pumped  out  at  the  top  and  into  the  space  enclosing 
the  cooling  coil;  the  static  head  caused  by  the  resulting  difference 
in  level  greatly  increases  the  natural  oil  circulation  through  the 
coils  and  core.  This  method  of  cooling  is  extremely  simple  in 
design  and  is  as  flexible  as  any  water-cooling  system.  It  is  not 
possible  as  in  the  older  system  of  cooling  to  communicate  one 
transformer  trouble  to  another  due  to  moisture  or  a  break- 
down of  any  kind;  it  is  free  to  be  changed  about  without  inter- 
fering with  any  other  transformer  in  the  station,  and  has  several 
advantages  in  case  of  fire.  On  all  very  large  capacitj''  transform- 
ers it  is  customary  to  circulate  sufficient  water  (in  addition  to 
forced-oil  circulation)  tp  dissipate  the  heat  with  a  rise  in  tempera- 
ture of  the  water  of  about  10°  C.  If  the  temperature  of  the  in- 
coming water  is  15°  C,  that  of  the  out-going  should  be  25°  C. 
This  usually  requires  about  one-third  of  a  gallon  per  minute 
per  kilowatt  loss  in  the  transformers.  The  rate  of  flow  of  the 
cooling  oil  through  the  various  coils  and  core  is  generally  about 
25  feet  per  minute,  or  somewhere  between  15  and  30  feet  per 
minute. 

It  is  well  known  that  high-voltage  large-power  transformers 
cannot  run  continuously,  even  at  no-load,  without  the  cooling 
medium,  since  the  iron  loss  alone  cannot  be  taken  care  of  by 
natural  cooling.  A  device  is  now  in  common  use  whereby  an 
alarm  is  given  to  the  operator  when  the  water  has  ceased  to  flow 
through  the  cooling  coils  and  also  when  the  temperature  has  risen 


124 


ST  A  TIONARY  TRANSFORMERS 


above  a  certain  given  value  in  the  transformer.  This  outfit  is 
shown  in  Fig.  115  and  consists  of  a  water  relay  or  balance  which 
is  actuated  by  a  volume  of  water  in  such  a  manner  that  if  the 
water  slacks  off  or  ceases  to  flow,  it  will  light  the  incandescent 
lamp  shown.  The  bell  alarm  is  so  arranged  that  it  will  operate 
as  soon  as  the  temperature  of  the  transformer,  as  indicated  by 
the  thermometer,  reaches  a  certain  limit. 

In  the  water-cooled  transformer,  the  heat  generated  by  losses 
is  disposed  of  as  above  mentioned,  and  the  arrangement  is  so 


Lamp 


0 


K<^ 


Low  VoltapJe  Relay 


Th  ?rmometer 


Resistance 

-x:(^ 

Water  Relay 

Fig.  115. — Water,  thermometer,  and  bell  danger  indicator  for  large  high- 
voltage  power  transformers. 


effective  that  but  very  little  heat  is  dissipated  from  the  tank  and 
consequently  no  advantage  is  derived  from  the  use  of  corrugated 
tanks.  There  are,  however,  installations  of  transformers  where 
a  satisfactory  supply  of  cooling  water  is  not  available  at  all 
periods,  and  also  cases  where  the  meter  rate  of  cooling  water  is 
excessive,  in  which  cases  a  tank  with  corrugations  may  be  used. 
The  usual  design  of  a  tank  with  corrugations  provides  for  approxi- 
mately 70  per  cent,  of  total  capacity  without  cooling  water. 
Its  cost  is,  in  general,  about  10  to  15  per  cent,  greater  than  a 
standard  boiler-iron  tank.  This  corrugated  type  has  been  used 
to  advantage  in  very  cold  climates  where  water-freezing  diffi- 
culties are  common. 

Fig.  116  shows  the  result  of  cutting  off  the  water  supply  of 
a  water-cooled  transformer.  A  five-hour  duration  has  resulted 
in  a  temperature  rise  of  35°  C.  (60  —  25  =  35°  C),  while  a  two 
and  one-quarter  hour  duration  shows  an  increase  in  temperature 
of  17°  C.  (57-40  =  17°  C). 

The  cooling  coil  of  this  type  of  transformer  is  sometimes 


METHODS  OF  COOLING  TRANSFORMERS        125 

coated  on  the  outside  with  a  deposit  from  the  oil  while  the  inside 
is  lined  by  impurities  in  the  cooling  water, 

A  good  method  of  cleaning  the  inside  of  cooling  coils  is  to  pour 
equal  parts  of  hydrochloric  acid  and  commercially  pure  water 
into  the  coil.  After  the  solution  has  been  standing  for  about 
one  hour,  flush  the  coils  out  thoroughly  with  clean  water. 

When  deposit  has  accumulated  on  the  outside  of  the  cooling 
coil,  it  is  necessary  to  remove  it  from  the  tank  for  cleansing. 
The  deposit  can  be  wiped  or  scraped  off. 

Sometimes  moisture  is  condensed  at  the  top  of  this  type 
transformer  when  located  in  a  damp  atmosphere.  To  avoid 
this,  the  transformer  should  be  kept  warm;  that  is,  the  tempera- 
ture of  the  oil  should  never  go  below  10°  C.  In  some  cases  a  form 
of  "breather"  has  been  used,  which  consists  of  a  vessel  of  chloride 
of  calcium,  so  arranged  as  to  allow  the  water  taken  out  of  the  air 
to  drain  off  without  mixing  with  the  air  that  is  going  in  on  account 
of  the  contraction  of  the  transformer  oil  in  cooling.  An  indica- 
tion of  condensation  of  moisture  is  the  accumulation  of  rust  on 
the  underside  of  the  transformer  cover  at  the  top. 

On  all  large  high-voltage  transformer  installations  provision 
should  be  made  for  continuous  sampling  and  filtration  of  the 
oil  in  any  transformer  without  removing  the  unit  from  service. 
This  is  usually  done  by  means  of  valves  at  the  bottom  and  top 
of  transformer  tank  and  withdrawing  the  oil  and  filtering  it  by 
forcing  it,  at  a  200-lb.  pressure,  through  a  series  of  about  twenty- 
five  filter  sections,  each  containing  five  8-in.  by  8-in.  filter  papers, 
making  a  total  thickness  of  almost  0.75  in.  of  paper.  The  paper 
filters  the  oil  and  removes  all  moisture,  returning  it  to  the  tank 
dry  and  clean.  The  capacity  of  oil-containing  tanks  should  not 
be  less  than  the  oil  capacity  of  any  one  transformer,  but  prefer- 
ably slightly  greater  in  capacity  than  the  largest  transformer  in 
the  station.  About  four  hours  should  be  sufficient  to  filter  the 
entire  contents  of  any  transformer  and  on  this  basis  the  capacity 
of  a  filter  equipment  may  be  provided  for. 

TEMPERATURE  DISTRIBUTION 

Core-t3rpe  (vertical  cylindrical  coils,  turns  of  the  conductor 
being  in  a  horizontal  plane). — With  this  type  of  winding  the 
ends  of  the  coils  will  be  somewhat  cooler,  owing  to  the  heat 
which  passes  out  at  those  points.  If  the  temperature  of  the  oil 
adjacent  to  the  top  portion  of  the  coils  is  much  higher  than  at 


126 


STATIONARY  TRANSFORMERS 


the  bottom,  there  will  be  a  tendency  to  transmit  heat  downward 
in  the  coil.  The  heat  transmitted  will  be  small,  but  the  thermal 
resistance  is  high  as  compared  with  the  temperature  difference 
in  this  direction.  The  most  important  result  will  be  that  the 
temperature  of  the  top  portion  of  the  coil  will  be  almost  as 
much  higher  than  the  temperature  of  adjacent  oil  as  that  of  the 


80 


40 


30 


H  80 

I  70 
< 
60 

50 

40 
30 

no 

W 


(a)  Temperature  of  high  voltage  winding  by  reslatance . 

(6)  "  "  low        "  "         "  thermometer. 

i-c)  "  "high 

(.d)  "  "  oil. 

(^)  "  "  water  leaving  cooling  coil . 


0       7       8a 
Hours  Run 

Fig.  116. 


10      11        18        13     14 


bottom  portion  is  above  the  oil  adjacent  to  it,  assuming,  of 
course,  that  the  equivalent  thermal  resistance  from  the  coil 
to  the  oil  is  practically  uniform  throughout  the  length  of  the 
duct.  The  total  average  temperature  of  the  coil  is  therefore 
related  not  to  the  surface  temperature  at  the  bottom  of  the 


METHODS  OF  COOLING  TRANSFORMERS        127 

coil  but  to  a  temperature  which  is  average  for  the  entire  surface 
and  which  may  be  considerably  higher  than  that  at  the  bottom ; 
also,  the  maximum  temperature  at  the  top  of  the  coils  may  be 
considerably  higher  than  the  maximum  average  surface  tem- 
perature, and  should  be  figured  from  the  surface  temperature 
near  the  top  of  the  coil. 

The  difficult  problem  with  natural  circulation  of  the  oil  is: 
correct  distribution  of  temperature  through  the  oil  from  the 
solid  surface  of  the  coils  to  the  surface  of  the  tank,  or  cooling 
coil.  For  a  given  velocity  the  equivalent  thermal  resistance 
is  constant,  the  temperature  drop  from  coils  to  oil  being  directly 
proportional  to  the  watts  per  sq.  in.  discharged  from  the  coils. 
With  forced-oil  circulation  (returning  the  oil  to  the  ducts  at  a 
definite  temperature)  the  whole  problem  of  cooling  is  much 
simplified,  the  only  lacking  element  being  a  definite  knowledge 
of  the  relation  between  the  equivalent  thermal  resistance  at 
the  surface  of  the  coils  and  the  velocity  of  the  oil.  With 
natural  circulation  the  oil  flow  is  caused  by  the  difference  in 
temperature  between  the  average  temperature  of  the  oil  inside 
the  duct  and  that  of  the  outside  oil  between  the  level  of  entrance 
to  and  exit  from  the  duct. 

The  effect  of  the  thickness  of  the  duct  upon  temperature  rise 
will  be  very  different  for  forced-oil  circulation  than  for  natural 
circulation.  With  forced-oil  circulation  a  thin  duct  will  be  better 
than  a  thick  one,  since  the  resulting  higher  velocity  of  the  oil 
will  give  lower  temperature  drop  from  the  surface  of  the  coils 
to  the  oil. 

With  natural  circulation  of  the  oil  a  thick  duct  will  give  practi- 
cally the  same  conditions  as  to  temperature  rise  as  that  obtained 
on  an  external  surface,  the  rise  being  less  than  for  a  thin  duct. 

Thinning  the  duct  does  not  cause  as  great  an  increase  in  tem- 
perature rise  as  might  be  expected,  up  to  a  certain  point,  since, 
though  the  temperature  rise  of  the  oil  while  passing  through 
will  be  greater,  this  temperature  rise  tends  to  produce  a  higher 
Velocity,  and  hence  to  cause  a  smaller  drop  from  the  coils  into 
the  oil,  as  well  as  to  reduce  the  net  temperature  rise  in  the  oil 
itself. 

The  discharge  of  heat  into  the  duct  from  both  sides,  as  compared 
with  its  discharge  from  one  side  only,  is  an  important  matter  in 
connection  with  cooling.  It  is  found  that  with  a  duct  of  a  given 
thickness,  if  the  heat  is  discharged  into  it  from  both  sides,  at  a 


128  STATIONARY  TRANSFORMERS 

given  density  in  watts  per  sq.  in,,  both  the  temperature  rise  of 
the  oil  while  passing  through  the  duct,  and  the  temperature  rise 
of  the  coils  above  adjacent  oil,  will  be  smaller  than  if  the  heat  is 
discharged  into  one  side  of  the  duct  only,  at  the  same  density. 
Thus  twice  the  heat  is  carried  away  by  the  duct,  with  a  smaller 
temperature  rise.  This  smaller  temperature  rise  of  the  oil 
while  passing  through  the  duct,  though  absorbing  twice  the 
heat,  indicates  that  the  velocity  of  flow  is  more  than  double, 
and  this  accounts  for  the  reduced  drop  from  the  coils  into  the 
oil.  The  great  difference  in  velocity  in  the  two  cases  is  accounted 
for  by  the  friction  on  the  side  of  the  duct  where  no  heat  is  dis- 
charged, which  is  much  greater  than  when  heat  is  being 
discharged. 

Shell  type  (vertical  oil-ducts  between  flat  coils).— With  this 
type,  in  general,  the  larger  insulation  is  not  in  the  path  of  heat 
flow,  and  the  insulating  covering  is  thin.  The  equivalent  ther- 
mal resistance  is  uniformly  distributed  throughout  the  length  of 
the  duct,  since  the  rate  of  oil  flow  is  the  same  throughout,  but 
this  resistance  will  change  with  changes  in  the  rate  of  heat 
discharge  because  the  velocity  of  the  oil  will  be  different.  If  the 
heat  generated  in  any  part  of  the  surface  which  is  opposite,  the 
oil  would  receive  heat  at  a  uniform  rate  throughout  its  passage 
through  the  duct,  and  the  difference  between  the  temperature 
of  the  coil  and  that  of  the  oil  would  be  the  same  at  the  top  as  at 
the  bottom.  The  temperature  at  the  top  part  of  the  coil  would 
be  as  much  greater  than  its  temperature  at  the  bottom  as  the 
temperature  of  the  oil  leaving  the  duct  is  greater  than  its  tempera- 
ture at  entrance.  This  would  result  in  the  passage  of  a  con- 
siderable portion  of  heat  downward  through  the  copper,  which 
is  a  good  conductor  of  heat,  the  effect  being  that  more  heat  is 
discharged  per  sq.  in.  from  the  bottom  part  of  the  coil  than 
from  the  top. 

The  temperature  rise  of  the  oil  in  its  passage  through  the  duct 
is  more  rapid  in  the  bottom  portion  of  the  duct  than  at  the  top,  and 
the  temperature  drop  from  the  oil  is  also  greater  in  the  bottom 
portion  of  the  duct  than  at  the  top.  The  temperature  gradient 
in  the  copper  from  the  top  of  the  coil  to  the  bottom  is  thus  reduced, 
giving  a  more  uniform  temperature,  as  well  as  a  lower  average 
temperature.  On  the  other  hand,  though  the  temperature  of 
the  oil  where  it  leaves  the  duct  would  be  the  same,  if  its  velocity 
were  the  same,  since  it  absorbs  the  same  total  heat,  yet  its  average 


METHODS  OF  COOLING  TRANSFORMERS        129 

temperature  throughout  the  duct  will  be  greater  on  account  of 
the  larger  proportion  of  heat  which  it  receives  near  the  bottom. 
This  will  result  in  an  increase  in  the  velocity  of  circulation,  which 
tends  to  reduce  both  the  temperature  rise  of  the  oil  in  the  duct 
and  the  temperature  drop  from  the  coil  into  the  oil,  both  of  these 
actions  affecting  further  reduction  in  the  temperature  of  the 
coils. 

Disc-shape  Coils  (horizontal  position  with  horizontal  ducts 
between). — These  coils  may  be  wound  either  in  single  turn 
layers,  or  with  several  turns  per  layer.  In  the  former  case 
practically  all  the  heat  will  be  thrown  out  into  the  horizontal 
ducts,  but  in  the  latter  the  inner  and  outer  layers  will  discharge 
best  through  layer  insulation  in  the  inner  and  outer  cylindrical 
surfaces.  A  large  portion  of  the  heat  will  find  an  easier  passage 
out  through  the  horizontal  oil  ducts  than  from  layer  to  layer  in 
the  coils.  The  relative  amounts  passing  out  through  the  two 
paths  will  depend  upon  the  circulation  of  the  oil.  If  the  oil  is 
stagnant  in  the  horizontal  ducts,  it  reaches  a  temperature  where 
it  ceases  to  absorb  heat. 

It  is  quite  evident  that  more  solid  matter  of  the  hydrocarbons 
will  deposit  at  those  points  of  the  maximum  temperature;  that 
is,  at  those  points  commonly  known  as  "hot-spots."  If  80  per 
cent,  of  the  transformer  operates  at  a  temperature  of  40°  C.  and 
the  remaining  20  per  cent,  at  80°  C,  the  transformer  is  badly 
designed  and  the  weakest  part  of  the  insulation  is  at  the  point  of 
the  maximum  temperature  rise.  Therefore,  a  knowledge  of  the 
distribution  of  temperature  throughout  a  transformer,  and  of 
the  various  things  which  effect  this  distribution,  is  important 
from  the  standpoint  of  all  those  who  operate  transformers; 
and,  if  we  are  to  avoid  serious  trouble  with  transformers,  trouble 
with  oil,  and  oil  depositing  which  necessitates  frequent  cleaning 
out  of  the  transformers,  it  is  essential  there  should  be  no  "  hot- 
spots." 

Standard  heating  guarantees  for  self-oil-cooled,  air-blast  and 
water-cooled  transformers  are  given  in  the  following  table. 

The  oil-cooled  transformer  measurements  are  based  on  the 
surrounding  air  temperature  of  25°  C.  normal  condition  of 
ventilation,  and  a  barometric  pressure  of  760  mm.  of  mercury. 

The  air-blast  transformer  measurements  are  based  on  an 
ingoing  air  temperature  of  20°  C.  and  a  barometric  pressure  of 
760  mm.  of  mercury. 

9 


130 


ST  A  TIONARY  TRANSFORMERS 


TABLE    II.— HEATING    GUARANTEES    FOR   OIL-COOLED,    AIR- 
BLAST    AND    WATER-COOLED  TRANSFORMERS 


Type  of  trans- 
former 

Temperature  rise  in  degrees  C. 

Full-load 
continuously 

-,_              ,                  50   per    cent. 
25  per  cent,  over-             ,      ,  r      « 
,     J  -.      „  ,              overload  for  2 
load  tor  2  hours            , 

hours 

Oil-cooled 

40 

f  windings  40 
1  core         55 
40 

55 
f  windings  55 
[  core          55 

55 

60 

Air-blast 

60 

Water-cooled 

60 
60 

The  water-cooled  transformer  measurements  are  based  on  a 
normal  supply  of  ingoing  water  at  a  temperature  of  15°  C. 

All  corrections  for  variations  in  the  three  above  types  of 
transformers  are  made  by  changing  the  observed  rise  of  tempera- 
ture by  0.5  per  cent,  for  each  degree  Centigrade  temperature 
variation,  or  for  each  5  mm.  deviation  in  barometric  pressure. 

TRANSFORMER  OIL. 

As  the  subjects  of  treating  transformer  oil  and  the  properties 
of  oil  are  so  broad,  and  have  been  treated  in  a  thorough 
manner  by  other  writers,  only  a  few  important  notes  are  given 
here. 

The  most  important  characteristics  of  transformer  oil  which 
interest  the  operating  engineer  are  summed  up  in  the  following 
table. 


TABLE  III 


Characteristics 

Quality  (A) 

Quality  (B) 

Flash  temperature 

188°  C. 

210°  C. 

-10°  C. 

100  to  105 

0.868 
Dark  amber 

133°  C. 

Burning  temperature. 

Freezing  temperature 

146°  C. 
-16°  C. 

Viscosity 

Specific  gravity  at  15.5°  C 

Color  of  oil 

40  to  42 

0.850 

Similar  to  water 

METHODS  OF  COOLING  TRANSFORMERS        131 

Usually  oil  is  received  abroad  testing  less  than  30,000  volts 
per  0.2  in.,  but  before  it  is  placed  into  the  transformer  it  is 
brought  up  to  a  test  at  least  30,000  volts  per  0.2  in.  for  trans- 
formers designed  for  an  operating  voltage  9f  44,000  volts  and 
under;  not  less  than  a  40,000  volt  test  per  0.2  in.  is  required  for 
transformer  oil  used  in  transformer  operating  above  44,000 
volts. 

At  a  temperature  somewhat  below  the  fire  test  or  burning 
temperature  shown  above,  the  oil  begins  to  give  off  vapors 
which,  as  they  come  from  the  surface  of  the  oil,  may  be  ignited  in 
little  flashes  or  puffs  of  flame,  but  the  oil  itself  will  not  support 
combustion  until  it  has  reached  the  temperature  of  the  fire  test 
as  shown  above.  The  lowest  temperature  at  which  these  ignita- 
ble  vapors  are  given  off  is  called  the  flash  point.  The  differ- 
ence between  flash  point  and  burning  temperature  test  varies 
considerably  in  different  oils  and  the  actual  location  of  the  points 
themselves  varies  somewhat  according  to  the  method  used  in 
their  determination.  A  high  flash  point  and  a  high  fire  test  are 
very  desirable  in  insulating  oils  in  order  that  the  fire  risk  attend- 
ent  on  their  use  may  be  reduced  to  a  minimum.  Viscosity  and 
flash  point  vary  together,  that  is  to  say,  an  oil  having  a  high 
flash  point,  compared  with  another  oil,  will  probably  also  be 
high  in  viscosity.  For  all  transformers  that  depend  entirely 
upon  oil  for  dissipating  the  heat  as  in  the  oil-filled  self-cooled  type, 
a  relatively  high  flash  point  is  of  the  utmost  importance. 

For  oil-filled  water-cooled  transformers  it  is  customary  to  use 
another  grade  of  oil  than  that  used  in  the  self-cooled  type,  the 
oil  operating  at  a  lower  average  temperature,  consequently  a 
high  flash  is  not  of  the  utmost  importance.  There  are  several 
grades  of  mineral  seal  oil  with  flash  points  varying  from  130°  C, 
used  in  water-cooled  transformers. 

A  very  small  quantity  of  water  in  transformer  oil  will  lower 
its  insulation  to  a  marked  degree;  moisture  to  the  extent  of  0.06 
per  cent,  reduces  the  dielectric  strength  of  the  oil  to  about  50  per 
cent,  of  the  value  when  it  is  free  from  moisture.  The  most 
satisfactory  method  of  testing  insulating  oils  for  the  presence  of 
water  is  to  measure  the  break-down  voltage  required  to  force  a 
spark  through  a  given  gap  between  two  brass  balls  immersed 
in  a  sample  of  the  oil.  Free  oil  from  moisture  should  have  a 
break-down  voltage  of  at  least  25,000  volts  between  brass 
knobs  0.5  inch  in  diameter  and  separated  by  a  0.15  in.  space. 


132  STATIONARY  TRANSFORMERS 

Often  it  is  desired  to  determine  the  insulating  qualities  of  an 
oil  when  there  are  no  high  voltage  testing  transformer  and 
apparatus  available  for  making  a  test.  When  this  is  the  case, 
a  very  good  idea  of  the  insulating  properties  of  the  oil  can  be 
obtained  by  testing  for  the  presence  of  water  with  anhydrous 
copper  sulphate.  To  prepare  the  anhydrous  copper  sulphate, 
heat  some  copper  sulphate  crystals  (blue-vitriol)  on  top  of  a 
hot  stove.  The  heat  will  drive  out  the  water  of  crystallization, 
leaving  as  a  residue  a  white  powder,  which  is  known  as  anhy- 
drous copper  sulphate. 

Fill  a  test  tube  with  a  sample  of  the  oil,  add  a  small  quantity 
of  the  anhydrous  copper  sulphate,  and  shake  well.  If  there  is 
any  moisture  present  in  the  oil,  it  will  combine  with  the  anhy- 
drous copper  sulphate,  forming  a  distinctly  blue  solution.  This 
test  is  quite  delicate  and  a  very  small  quantity  of  moisture  can 
be  detected  by  it.  If  this  test  does  not  show  the  presence  of 
water  it  is  quite  safe  to  assume  that  the  insulating  properties  of 
the  oil  are  fairly  high. 

When  obtaining  a  sample  of  oil  for  testing,  always  get  the 
sample  of  oil  from  the  bottom  of  the  tin  or  barrel,  because,  as 
water  is  heavier  than  oil,  the  maximum  quantity  of  water  will 
always  be  found  at  the  bottom.  To  obtain  a  sample  from  the 
bottom,  use  a  long  glass  tube  of  small  diameter,  hold  the  thumb 
tightly  over  one  end  and  plunge  it  to  the  bottom  of  the  barrel. 
Remove  the  thumb  letting  the  air  escape,  then  press  the  thumb 
tightly  over  the  end  of  the  tube  and  withdraw  it  with  the  sample 
of  oil. 

The  real  importance  of  the  light  oil  known  to  the  trade  as 
mineral  seal  oil  is  that  it  tends  to  decrease  the  deposit  thrown 
down  on  the  bottom  of  the  transformer  tank,  cooling-coils 
and  the  transformer  coils  themselves.  The  (A)  class  referred  to 
here  is  a  dark-colored  oil  having  a  specific  gravity  somewhat 
higher  than  the  mineral  oil,  its  flash  and  fire  points  are  much 
higher  but  when  subjected  to  continued  heating  it  throws  down 
a  deposit  tending  to  clog  up  the  oil  ducts  of  the  transformer 
and  impede  the  circulation  of  the  oil.  So  far  as  is  known  this 
deposit  is  caused  entirely  by  the  effect  of  the  heat  on  the  oil. 
It  can  be  removed  by  filtering  through  a  bed  of  lime  and  then  a 
sand  bed,  or  preferably  by  using  one  of  the  oil-drying  outfits 
now  on  the  market.  The  (B)  class  oil  is  light  and  practically 
white,  and  is  usually  referred  to  as  mineral  seal  oil;  it  has  rather 


METHODS  OF  COOLING  TRANSFORMERS        133 

low  flash  and  fire  points  but  does  not  throw  down  a  deposit 
when  subjected  to  long  and  continuous  heating.  The  usual  life  of 
transformer  oils  depends  altogether  on  the  thoroughness  with 
which  the  oil  is  protected  against  absorption  of  moisture,  and, 
when  heavy  oils  are  used,  the  temperature  at  which  the  trans- 
formei*s  are  operated,  the  higher  the  operating  temperature  the 
more  rapid  are  thin  oils  affected.  It  is  the  general  practice  to  use 
the  mineral  seal  oil  in  water-cooled  transformers  because  of  its 
tendency  to  keep  down  the  temperature  and  also  because  it  is 
practically  free  from  the  slimy  deposit  referred  to  above.  With 
the  use  of  class  (A)  oil  the  deposit  would,  besides  accumulating 
and  probably  clogging  the  oil-ducts,  close  in  around  the  cooling- 
coils  causing  a  consequent  increase  in  the  temperature  of  the  oil 
and  this  in  turn  would  decrease  the  efficiency  of  the  transformer. 
No  specific  information  can  be  given  as  to  the  length  of  time 
throughout  which  an  oil  may  be  in  use  continuously;  it  might 
last  five  years  or  it  might  last  only  five  months,  but  under 
ordinary  service  conditions  the  oil  for  high-voltage  transform- 
ers should  be  good  for  at  least  18  months.  Several  good  oil 
drying  and  purifying  outfits  are  now  in  common  use,  the  prin- 
cipal elements  of  this  modern  outfit  being  an  electric  oven,  a 
pump  and  strainer,  filter-press  and  blotting  paper.  The  interior 
of  the  oven  is  provided  with  rods  for  supporting  and  separating  the 
blotting  paper  to  facilitate  rapid  and  thorough  drying.  A 
thermometer  is  attached  to  the  oven  and  a  switch  is  provided 
for  regulation  of  the  temperature.  For  drying  and  filtering 
oil,  five  layers  of  0.025-in.  blotting  paper  are  used  between 
sections  of  the  press.  The  separation  of  this  filtering  material 
is  of  the  greatest  importance.  Special  care  must  be  exercised 
in  drying  the  blotting  paper,  which  should  be  suspended  from 
the  rods  in  such  a  way  that  air  is  accessible  to  both  sides  of 
each  sheet.  The  blotting  paper  should  be  dried  at  least  24 
hours  at  a  temperature  not  over  85°  C,  and  then  put  into  a  tank 
of  dry  oil  the  instant  it  is  removed  from  the  oven  and  before  it  is 
cooled,  as  exposure  to  normal  air  for  a  few  minutes  is  sufficient 
to  neutralize  the  drying.  It  should  not  come  into  contact  with 
the  hands  because  of  the  danger  of  absorbing  perspiration.  A 
small  quantity  of  anhydrous  calcium  chloride  placed  in  the  oven 
will  take  up  the  moisture  in  the  air  and  quicken  the  process. 
A  higher  temperature  than  that  given  above  might  scorch  the 
blotting  paper  or  impair  its  mechanical  strength.     As  the  paper 


134  STATIONARY  TRANSFORMERS 

is  somewhat  weakened  by  saturating  with  oil,  it  should  be  care- 
fully handled  after  removal  from  the  bath.  A  tank  of  suitable 
size  for  the  paper  should  be  filled  with  dry,  clean  oil  and  the  paper 
should  be  submerged  in  the  oil.  The  paper  should  be  carefully 
suspended  in  the  tank,  the  bottom  edge  of  the  paper  being  kept 
3  or  4  in.  from  the  bottom.  The  oil  level  should  be  at  least 
2  in.  above  the  top  of  the  paper.  A  strainer  is  provided  to 
prevent  anything  of  appreciable  size  from  entering  and  in- 
juring the  pump.  It  is  easily  accessible  and  should  be  cleaned 
occasionally.  The  rating  in  gallons  per  minute  is  usually  for 
average  conditions  in  filtering  clean  heavy  oil  or  dirty  light  oil. 
The  best  oil  temperature  for  filtering  is  between  25  and  75°  C. 
In  the  installation  of  this  outfit  the  pump  should  be  placed  so 
that  oil  falls  by  gravity  and  as  fast  as  the  pump  will  take  it. 
With  clean  oil  the  pressure  and  volume  will  remain  nearly  con- 
stant, the  volume  being  nearly  proportional  to  the  pressure, 
but  with  dirty  oil  the  pressure  will  increase  very  rapidly.  With 
dirty  oil  and  paper  the  volume  increases  much  more  slowly 
than  the  pressure  and  there  is  little  gained  by  an  increase  in 
pressure  over  75  pounds  per  square  inch.  In  general,  class  (B) 
oil  is  filtered  twice  as  fast  as  the  class  (A)  oil,  and  the  greater 
capacity  is  obtained  by  frequent  renewal  of  paper,  the  total 
capacity  per  day  depending  largely  on  the  time  consumed  in  the 
operation.  In  placing  paper  in  the  press,  care  should  be  taken  to 
have  the  holes  in  the  paper  corresponding  with  those  in  the  plates. 
Oil  is  admitted  at  any  pressure  not  over  100  pounds  per  square 
inch.  The  pressure  will  at  first  be  very  low,  gradually  increasing 
as  the  paper  clogs  with  dirt.  It  is  found  that  after  three  re- 
placements of  the  paper,  the  dielectric  strength  of  the  oil  is  apt 
,to  fall  off,  and  that  it  is  best  to  discard  the  full  charge  of  paper 
and  begin  again.  The  amount  of  oil  which  can  be  filtered  through 
one  set  of  papers  depends  entirely  on  the  quality  and  tempera- 
ture, hot  oil  being  filtered  with  great  facility  because  of  its  low 
viscosity.  By  this  process  oil  may  be  dried  to  withstand  a 
puncture  test  from  40,000  to  60,000  volts  with  a  standard  spark 
gap  consisting  of  two  0.5  in.  diameter  discs  spaced  2/10  in. 
apart.  With  oil  of  an  average  quality  as  regards  moisture  and 
foreign  matter  one  treatment  will  usually  remove  all  sediment 
and  bring  the  puncture  voltage  to  40,000  volts  or  more.  Oil 
which  has  been  damaged  by  overheating  from  continuous  over- 
load or  bad  burn-out  may  be  treated  in  this  purifying  outfit, 


METHODS  OF  COOLING  TRANSFORMERS        135 

and  the  sediment  removed  although  the  oil  will  still  be  darker  in 
color  than  it  was  originally.  If  the  oil  is  thickened  to  a  slimy 
nature,  it  will  quicken  the  operation  to  heat  it  to  75°  C.  just 
before  running  it  through  the  press. 


90 
80 

5™ 

-foo 
1-2 

£   v50 

55 

»40 

1 

19.2 

V 

J 

[C.284 

20 

\ 

'"'* — 



10 

Water- Parts  In  10,000  by  Volume 

Fig.  117. — Curve  showing  the  effects  of  water  in  oil. 

The  curve  Fig.  117  very  clearly  shows  the  serious  effects  of 
water  in  amounts  less  than  0.010  per  cent.  It  shows  that  the 
water  present  in  the  oil  must  not  exceed  0.001  per  cent,  in 
order  to  obtain  a  dielectric  strength  of  40,000  volts  in  the 
standard  test  (0.2  in.  between  0.5  in.  disc). 


1^ 


CHAPTER   IX 

CONSTRUCTION,  INSTALLATION  AND  OPERATION  OF  LARGE 
TRANSFORMERS 

There  are  various  types  of  transformers  on  the  market  differ- 
ing so  much  in  design  that  it  is  difficult  to  tell  exactly  whether 
they  are  of  one  or  the  other  design  (shell  or  core  type) ;  in  fact, 
what  some  manufacturers  call  a  shell  transformer  others  call 
a  core-type  transformer.  However,  the  design  and  construc- 
tion of  transformers  referred  to  here  are  strictly  of  the  core 
and  shell  types  respectively,  of  high-voltage  large-capacity 
design,  and  of  American  manufacture. 

Transformers  are  always  sent  from  the  factory  as  completely 
assembled  in  their  tanks  as  their  size  and  transportation  facilities 
in  the  countries  they  have  to  pass  through  will  warrant.  When 
they  are  sent  disassembled,  which  is  usually  the  case  if  they 
are  for  very  high  voltages  and  large  capacity,  the  tanks  are 
usually  protected  for  shipment  abroad  but  left  unprotected  for 
home  shipment;  the  coils  are  carefully  packed  in  weatherproof 
boxing,  and  the  core  if  of  the  shell  type  is  packed  in  strong  wooden 
boxes  of  moderate  size  (in  a  loose  state) ,  the  core  of  the  core  type 
being  shipped  already  assembled  each  leg  being  packed  in  one 
box  and  the  end-laminations  in  separate  boxes.  Whether  the 
transformer  is  built  up  at  its  destination  or  sent  already  assembled, 
it  should  be  thoroughly  inspected  before  being  permanently 
put  into  the  tank.  If  the  transformer  is  sent  from  the  factory 
in  its  tank,  which  is  very  seldom  done,  it  should  be  removed  and 
thoroughly  inspected  and  cleaned  before  giving  it  a  "heat-run." 

Let  us  deal  first  with  the  core-type  transformer  which  consists 
essentially  of  two  or  three  cores  and  yokes  which  when  assembled 
form  a  complete  magnetic  circuit.  These  cores  and  yokes  are 
made  up  of  laminated  stampings  which  vary  from  0.010  to  0.025 
in.  in  thickness  according  to  the  frequency  of  the  system  on 
which  they  are  to  be  used  and  the  different  manufacturers. 
The  laminations  are  insulated  from  each  other  by  a  coat  of 
varnish  or  paper  to  limit  the  flow  of  eddy  currents. 

It  is  shown  in  Fig.  1 18  that  there  are  three  cores  of  equal  cross- 

136 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    137 

section  joined  by  a  top  and  bottom  yoke  of  the  same  cross-section 
as  the  cores,  and  that  upon  each  core  are  placed  the  low  and  high 
voltage  windings  for  one  phase.  The  low  and  high  voltage 
windings  are  connected  so  that  the  fluxes  in  the  cores  are  120  elec- 
trical degrees  apart,  making  their  vector  sum  equal  to  zero  at  any 
instant. 

The  usual  designs  of  core-type  transformers  made  by  the  best 
manufacturers  have  a  uniform  distribution  of  dielectric  flux 
between  high  and  low  voltage  windings,  excepting  at  the  ends  of 


A 

. 

i 

C 

■ 

Fig.  118. — Three-phase  core-type  transformer. 

the  long  cylinders  where  the  dielectric  flux  will  be  greater  and  its 
distribution  irregular. 

As  already  stated,  the  core-type  transformer  has  its  lamina- 
tions shipped  already  assembled,  wrapped  in  insulating  material 
of  horn-fiber  and  bound  with  strong  binding  tape  which  serves  as 
a  binding  to  keep  the  laminations  of  the  assembled  sections 
intact.  The  different  sections  are  assembled  on  wooden  pins  of 
the  size  of  the  holes  in  the  laminations;  first,  in  one  direction, 
and  then  this  end  in  the  opposite  direction,  alternating  spaces 
thus  being  left  for  assembling  the  end  laminations.  The  approxi- 
mate number  of  laminations  per  inch  required  in  building  up 


138  STATIONARY  TRANSFORMERS 

tliese  laininuted  sections  may  be  detoniiiiied  from  the  informa- 
tion that  the  iron  solid,  would  be  about  90  per  cent,  of  the 
height  of  the  built  up  laminations,  36  and  64  laminations  per 
inch  being  about  the  number  of  laminations  required  for  the  two 
standard  thicknesses,  0.025  and  0.10  in.  respectively.  The 
required  number  of  laminations  are  built  in  an  insulating  channel 
piece,  and  on  the  top  of  the  channel  piece  and  the  pile  of  lamina- 
tions another  channel  piece  is  placed,  the  whole  being  pressed 
down  to  dimensions  and  the  channel  pieces  stuck  together  with 
shellac  under  the  influence  of  pressure  and  heat.  The  various 
sections  are  then  assembled  with  wooden  pins  to  hold  them 
together,  these  remaining  in  the  holes  permanently,  and  the 
assembled  sections  clamped  to  dimensions  and  finally  wound 
with  a  layer  of  strong  binding  tape  of  half-lap,  which  should  not 
extend  beyond  the  beginning  of  the  spaces  for  the  end-laminations. 

The  core  is  now  built  up,  the  next  process  being  to  insert  the 
end  laminations  at  the  bottom,  their  number  corresponding  to 
the  spaces  left  for  them,  making  them  so  fit  into  the  spaces  as  to 
form  butt-joints.  These  laminations  are  assembled  while  the 
cores  or  "legs"  are  resting  in  an  horizontal  position.  While  in 
this  position  the  bottom  clamp  with  its  insulation  is  fastened 
over  the  end  laminations  and  the  whole  raised  by  the  help  of  an- 
other clamp  and  cross-bars  to  a  vertical  position,  with  open  ends 
upward.  The  clamping  bolts  are  then  placed  in  a  loose  state, 
reliance  being  put  on  the  bolts  (which  hold  the  bottom  clamps 
in  position)  to  keep  the  cores  in  a  vertical  position  during  the 
assembly  of  coil-supports  and  coils. 

The  coils,  which  are  of  a  cylinder  form,  are  raised  by  means 
of  a  stout  tape  and  slipped  over  the  cores.  All  of  the  coils  which 
connect  together  at  the  bottom  should  be  connected  immedi- 
ately after  the  coils  are  in  position.  Between  the  cylinder  low- 
voltage  coils  and  the  high-voltage  coils  is  placed  a  cylinder 
shaped  insulating  separator,  the  separator  being  held  in  posi- 
tion by  means  of  spacing  strips  of  wood.  All  connections  be- 
tween outside  coils  can  be  conveniently  made  before  the  spacing 
strips  are  inserted  between  the  high  and  low-voltage  windings, 
when  the  coils  may  be  easily  turned  to  such  positions  as  will 
leave  the  coil  connections  as  distant  as  possible  from  the  side  of 
the  steel  tank.  The  top  connections  should  be  made  after  all 
the  coils  of  the  high-voltage  winding  are  in  position.  A  press- 
board  insulating  piece  or  casing  is  finally  placed  over  the  whole 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    139 

assembly  of  coils  and  tied  around  with  tape.  The  connections 
or  taps  and  the  terminal  leads  are  brought  out  at  the  top  and 
supported  in  a  similar  manner  to  those  mentioned  in  the  assembly 
of  shell-type  transformers. 

The  shell-type  water-cooled  transformers  and  forced  oil-cooled 
transformers  are  built  in  larger  sizes  than  the  core  type  trans- 
formers, the  former  size  having  been  built  in  6000  kv-a  single- 
phase  units  and  14,000  kv-a  three-phase  units. 

The  shell-type  transformers  shown  in  Fig.  119  consist  of  three 
single-phase  transformers  placed  in  one  tank,  the  laminated 
cores  being  constructed  to  form  a  single  structure.  The  reduc- 
tion of  iron  for  the  magnetic  circuit  amounts  to  from  10  to 
20  per  cent,  of  that  used  in  three  single-phase  transformers 
placed  side  by  side. 

In  this  type  it  is  difficult  to  insulate  the  large  number  of 
edges  and  sharp  corners  exposed  between  adjacent  high  and  low 
voltage  windings  and  between  windings  and  core.  At  these 
points  the  dielectric  density  is  very  great,  and  it  is  much  more 
difficult  to  insulate  them  than  the  ends  of  the  cylinder  coils  of  a 
core-type  transformer,  and  much  more  insulation  is  required  and 
consequently  a  larger  space-factor.  In  fact,  a  60,000  volt — 2000 
kv-a — 25  cycle  transformer  of  the  core  type  will  have  a  space- 
factor  of  the  windings  (ratio  between  the  total  section  of  copper 
conductors  to  the  total  available  winding  space)  of  about  28  per 
cent.,  whereas,  in  the  shell  type  of  the  design  shown  in  Fig.  119 
the  space-factor  is  only  about  17  per  cent.  The  result  of  this 
increased  space-factor  in  the  winding  of  a  shell  type  transformer 
is  lower  efficiency  and  worse  regulation,  and  consequently  a 
heavier  and  more  expensive  transformer  for  a  given  capacity  and 
efficiency.  It  is  sometimes  recommended  to  use  graded  insula- 
tion in  high-voltage  transformers  between  the  high-voltage  and 
low-voltage  windings  or  between  the  windings  and  core  because 
of  the  unequal  distribution  of  the  dielectric  flux.  In  all  prop- 
erly designed  transformers  for  high  voltages,  the  only  change 
in  the  grade  of  insulation  is  at  the  ends  of  the  windings,  this 
being  the  only  grading  considered  necessary. 

In  assembling  the  coils  of  a  shell-type  transformer,  this  being 
the  first  thing  to  be  done  in  the  assembly  of  this  type,  care  should 
be  taken  to  eliminate  dirt  and  dust,  and  the  coils  at  all  times 
should  be  kept  clean  and  dry.  In  unboxing  the  coils,  each  one 
should  be  wiped  oflf  with  a  dry  cloth  and  stacked  in  the  right 


140 


ST  A  TIONARY  TRANSFORMERS 


order  of  assembly.  The  assembly  of  coils  is  begun  in  an  hori- 
zontal plane,  and  stacked  one  above  the  other  as  shown  in  Fig. 
121,  the  outer  press-board  insulation  piece  being  set  on  two 
wooden-horses,  correctly  spaced,  depending  on  the  size  of  the 
transformer  to  be  assembled.     The  first  coil,  taken  from  the  top 


Fig.  119. — Three-phase  shell-type  transformer. 

of  the  stack  is  placed  in  position  with  its  inner  edges  insu- 
lated by  means  of  channel-shaped  insulation  pieces.  Each  coil 
before  it  is  placed  in  the  assembly  has  the  same  shaped  insula- 
tion pieces  on  its  outer  edges;  insulation  separators  are  arranged 


Fig.  120. — Single-phase  transformer  iron  assembly. 

in  symmetrical  order  for  both  the  low  and  high-voltage  coils 
with  wooden  filling  blocks  and  channel  pieces  set  at  the  inside 
top  and  bottom  of  coils.  The  assembly  of  these  coils  if  of 
large  size  can  easily  be  lowered  into  position. 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    141 

Tlic  iron  laminations  must  be  laid  with  great  care,  steel  being 
used  to  keep  the  alignment,  on  which  the  laminations  butt. 
(See  Fig.  120). 

In  connecting  the  coils  together,  all  the  soldering  is  best  done 
as  the  assembly  progresses,  also  all  taping  of  the  connections, 
since  the  short  stub  connections  are  only  accessible  at  this  stage 
of  erection.  Before  commencing  to  solder,  a  cloth  should  be 
spread  over  the  ends  of  coils  to  prevent  splashing  solder  on 
them  which  might  get  inside  of  the  coils  and  ultimately  cause  a 
burn-out.  During  the  assembly  of  coils,  great  care  should  be 
taken  to  keep  them  and  the  insulation  separator  in  alignment. 
To  facilitate  this,  all  the  insulation  separators  are  slit  at 
their  four  corners  and  a  long  round  strip  of  wood  is  threaded 
through  as  the  coils  are  being  built  up.  After  the  assembly  of 
coils  and  the  placing  of  the  outside  top  insulating  piece  or  collar 
position,  the  whole  is  clamped  down  to  dimensions.  While  the 
end  clamps  are  holding  down  the  coils  to  dimensions,  strong 
cloth  tape  is  wound  around  the  coils,  between  the  two  clamps, 
under  considerable  tension,  the  ends  of  tape  being  finally  secured 
by  sewing  them  down,  after  which  the  whole  is  painted  with 
a  black,  insulating  air-drying  varnish. 

Getting  the  assembled  coils  from  the  horizontal  position  in  which 
they  rest  to  the  vertical  position  necessary  for  the  assembly  of 
iron  and  completion  of  transformer,  requires  the  greatest  care 
especially  where  transformers  are  of  a  larger  size  than  2000  kv-a. 
This  is  accomplished  by  means  of  blocking  the  space,  inside  of 
coils,  leaving  sufficient  space  in  the  center  of  coil-space  for  a 
lifting  piece.  The  rope  or  cable  for  lifting  should  be  slid  over  the 
rounded  ends  of  the  lifting  piece,  care  being  taken  that  the 
wooden  spacer  is  sufficiently  high  about  the  coils  to  prevent 
striking  the  sling  when  swinging  to  vertical  position. 

The  bottom  end  frame  or  core  support  is  now  ready  to  be 
set  into  position  where  it  is  desired  to  build  up  the  iron, 
which  is  arranged  in  a  similar  manner.  The  coils  should 
be  exactly  vertical.  Lapping  of  the  laminations  should  be 
avoided,  otherwise  difficulty  will  be  experienced  in  getting 
in  all  of  them.  Raw-hide  mallets  should  be  used  for  driving 
the  laminations  into  line;  or  in  case  these  mallets  are  not 
available,  hard  wood  pieces  pressed  against  the  laminations 
may  be  hammered.  During  the  building  up  of  the  laminations 
they  should  be  pressed  down  two  or  three  times,  depending  on 


142 


STATION ARY  TRANSFORMERS 


160  Turns 
188  Turns 
188  Turns 


PI  Not  Crossed 
P2  Crossed 
P3  Not  Crossed 

P4  Crossed 
P5  Not  Crossed 
P6  Crossed 

P7  Not  Crossed 

P8  Crossed 
P9  Crossed 

PIO  Crossed 
Pll  Not  Crossed 
P12  Crossed 


Not  Crossed 


S7  Crossed 

S6  Not  Crossed 


S5  Crossed 

S4  Not  Crossed 


S3  Crossed 

S2  Not  Crossed 


SI  Crossed 


Fig.  121.— Assembly  of  coils  for  a  shell-type  transformer. 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    143 

the  size  of  transformer  being  built.  For  this  clamping,  the 
top  iron  frame  is  usually  lowered  and  forced  down  with  espe- 
cially made  clamps  or  the  regular  clamping  bolts  may  be  used  if 
the  threading  on  them  is  sufficient  to  lower  the  clamp  to  the 
required  dimensions;  these  clamps  or  bolts  may  be  left  in  posi- 
tion over  night  if  any  difficulty  is  found  in  getting  in  the  lamina- 
tions. In  the  case  of  transformers  without  a  top  piece  or  frame, 
an  especially  constructed  rigid  frame  of  wood  may  be  used.  The 
laminations  should  be  built  up  to  such  a  height  as  will  permit 
the  core-plate  to  be  forced  into  position  under  considerable 
driving.  It  is  always  a  difficult  matter  to  put  in  all  of  the  lamin- 
ations that  come  from  the  factory  as  special  facilities  for  pres- 
sing are  available  there.  After  the  laminations  have  been 
clamped  down,  the  low-  and  high-voltage  leads  should  be  sup- 
])orted  and  insulated  in  a  right  manner;  care  being  taken  in 
supporting  the  leads  to  see  that  they  are  properly  spaced,  for  if 
they  are  placed  too  close  together  a  short-circuit  might  occur. 
At  the  cast-iron  frames,  the  insulator  bushings  used  for  this 
purpose  are  held  by  metal  supports  to  the  frame,  and  at  the 
point  where  the  leads  pass  through  the  bushings,  cement  is 
used  to  hold  the  leads  into  position.  Both  the  high  and  low 
voltage  winding  end-leads  connect  to  the  terminal-board  which 
is  located  above  the  assembled  coils  and  core.  In  the  case  of 
oil-cooled  and  water-cooled  transformers  all  the  leads  are  brought 
out  at  the  top;  usually' air-blast  transformers  have  their  leads 
terminate  at  the  base  or  part  at  the  base  and  part  at  the  top  of 
assembled  coils. 

In  lowering  transformers  into  their  tanks,  care  must  be  taken 
to  get  the  bottom  cross-bar,  into  which  the  tie-bolts  are  screwed 
into  the  correct  position,  which  requires  that  the  transformers 
should  be  properly  centered  in  the  tank. 

Of  the  two  types  of  transformers,  the  core  type  is  the  easiest 
one  to  assemble,  and  a  full  description  of  one  particular  method 
of  assembly  of  this  type  might  well  be  said  to  cover  practi- 
cally every  manufacture,  whereas  the  shell  type  varies  in  many 
ways  and  is  a  difficult  piece  of  apparatus  to  assemble,  especially 
in  the  larger  sizes. 

Air-blast  transformers  are  regularly  built  in  capacities  up  to 
4000  kv-a  and  for  voltages  as  high  as  33,000  volts.  The  effi- 
ciency of  this  type  of  transformer,  in  good  designs  and  with  the 
required  amount  of  air  pressure,  is  sometimes  better  than  the  oil- 


144  STATIONARY  TRANSFORMERS 

filled  water-cooled  type  of  the  same  capacity  and  voltage.  Its 
general  design  is  very  much  like  the  ordinary  shell-type  trans- 
former with  the  exception  of  a  few  modifications  in  the  iron 
assembly  where  certain  air-spaces  are  left  open  for  the  circula- 
tion of  air.  The  air  space  area  in  these  transformers  is  consider- 
ably in  excess  of  the  actual  area  required  for  the  pressure  of  air 
specified  for  cooling.  For  this  reason  dampers  are  provided  to 
regulate  the  air  so  that,  where  a  number  of  transformers  are  in- 
volved, each  transformer  will  receive  its  portion.  The  air  always 
enters  the  transformer  at  the  bottom  and  divides  into  sepa- 
rate paths,  flowing  upward  through  the  coils  and  ducts  con- 
trolled by  the  dampers  at  top  of  the  transformer  casing,  and 
through  the  core  ducts  controlled  by  a  damper  at  the  side  of 
the  casing. 

This  type  of  transformer  is  always  shipped  already  assembled 
so  that  in  the  larger  sizes  great  care  is  necessary  in  handling 
them.  For  shipment  abroad  the  larger  sizes  would,  of  course, 
have  to  be  disassembled,  but  as  this  is  of  rare  occurrence  the 
above  holds  for  practically  all  sizes. 

These  transformers  are  placed  over  an  air-chamber  made  of 
brick  or  concrete  the  sides  being  made  smooth  to  minimize  fric- 
tion and  eddy  currents  of  air.  From  the  blower  to  the  chamber 
should  be  as  free  as  possible  of  angles,  and  where  these  occur, 
they  should  be  well  rounded  off.  Sufficient  space  should 
be  allowed  for  the  location  of  the  high-  and  low-voltage 
leads,  and  necessary  repairs  and  inspection.  Three-phase 
transformers  have  larger  air-chambers  than  single-phase  trans- 
formers of  the  same  aggregate  capacity.  The  temperature  of 
the  out-going  air  compared  with  the  temperature  of  the  incoming 
air  is  the  best  indication  whether  sufficient  air  is  passing  through 
the  transformers;  if  there  is  not  more  than  20°  C.  difference,  the 
supply  of  air  will  be  found  sufficient.  As  transformers  are 
generally  designed  on  the  basis  of  25°  C.  the  best  results  are 
obtained  when  the  temperature  of  the  in-coming  air  is  not  greater 
than  this  value. 

Installation  of  Transformers. — ^In  the  installation  of  high 
voltage  transformers  of  the  self-cooled  oil-filled,  water-cooled 
oil-filled,  forced-oil-cooled  oil-filled,  and  the  air-blast  types,  the 
following  points  of  importance  should  be  born  in  mind : 

(a)  In  generating  and  receiving  stations  the  transformers 
should  be  so  situated  that  a  burn-out  of  any  coil,  a  boiling  over 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    145 

of  the  oil,  or  burning  of  the  oil  in  any  unit  will  not  interfere  with 
the  continuity  of  service. 

(b)  In  generating  and  receiving  stations  the  transformers 
should  be  so  located  that  the  high  voltage  wiring  from  trans- 
formers to  bus-bars  is  reduced  to  a  minimum. 

(c)  The  transformer  tanks,  which  are,  of  course,  made  of  a 
metallic  or  non-combustible  material,  should  be  permantly  and 
effectively  grounded,  preferably  to  the  ground  cables  to  which 
the  station  lightning  arresters  are  connected. 

(d)  Sufficient  working  space  should  be  allowed  around  each  unit 
to  facilitate  the  making  of  repairs  and  for  necessary  inspection. 

(e)  During  the  entire  process  of  assembly  of  transformers  of 
low  or  high  voltage,  the  best  and  most  careful  workmanship  is 
of  utmost  impoi'tance. 

(f)  (This  might  be  considered  as  the  last  process  in  the  instal- 
lation of  transformers  but  by  no  means  the  least  important.) 
Extra  special  knowledge  and  care  is  necessary  on  the  part  of  all 
those  whose  duty  it  is  to  dry  out  transformers — ^the  difficulty  is 
not  in  drying  out  the  coils,  as  is  usually  supposed,  but  the  drying 
of  the  whole  insulaiion  surrounding  them  and  the  core.  No 
matter  what  the  factor  of  safety  the  transformer  has  been  built 
for  it  avails  little  in  the  case  of  carelessness  or  neglect  to  dry  out 
the  transformer  properly. 

Before  transformers  leave  the  factory  they  are  given  a  high- 
voltage  test,  the  standard  being,  to  apply  twice  the  rated  voltage 
between  the  high-  and  low-voltage  windings,  the  latter  being 
connected  to  the  iron  core.  The  main  object  of  applying  this 
test  which  induces  twice  the  rated  voltage  to  one  of  the  windings, 
is  to  determine  whether  the  various  portions  of  the  coils  are 
properly  insulated  from  each  other.  It  is  now  believed  that 
the  greater  causes  of  failure  in  high- voltage  transformers  are 
punctures  between  turns  and  not  between  the  high  and  low- 
voltage  windings. 

To  install  properly  and  place  in  good  working  order  high-volt- 
age power  transformers  is  quite  as  important  as  their  design, 
since  upon  this  depends  the  life  of  the  transformer.  All  trans- 
formers of  high  voltage  should  be  thoroughly  dried  out  on 
arriving  from  the  factory,  and  all  transformers  which  show 
evidence  of  being  unduly  moist,  or  that  they  have  been  subjected 
to  conditions  that  would  cause  them  to  be  unduly  moist,  should 
be  taken  special  care  of  in  the  drying  process. 

10 


146  STATIONARY  TRANSFORMERS 

Testing  Cooling  Coils — Before  high-voltage  transformers 
are  put  into  operation  they  are  subject  to  a  "heat-run," 
and  in  the  case  of  transformers  with  cooling  coils,  the  coils 
are  made  subject  to  a  pressure  test.  These  coils  must  be 
assembled  before  the  heat  run  can  be  made.  If  the  coils 
show  evidence  of  rough  usage,  such  as  heavy  indentations  and 
disarrangement  of  layers,  the  coils  should  be  given  the  usual 
tests  to  determine  whether  a  break  has  resulted.  The  method 
for  testing  for  leaks  is  to  fill  the  cooling  coil  full  of  water, 
establish  a  pressure  of  80  to  100  lb.  per  square  inch,  disconnect 
the  source  of  pressure,  holding  the  water  in  the  cooling  coil  by 
means  of  a  valve,  and  note  whether  the  pressure  gauge  between 
the  valve  and  the  cooling  coil  maintains  the  indication  through- 
out a  period  of  about  one  hour.  Care  should  be  taken  that  no 
air  is  left  in  the  cooling  coil  in  filling  it  with  water.  In  removing 
the  source  of  pressure  it  is  preferable  to  disconnect  entirely  from 
the  cooling  coil,  in  order  both  to  make  sure  that  the  source  of 
pressure  is  entirely  removed  and  to  note  whether  the  lowering 
of  the  pressure  indicated  by  the  gauge  connected  to  cooling  coil, 
is  due  to  leakage  through  the  cooling  coil  valve  or  to  leakage 
through  a  hole  in  the  cooling  coil.  If  the  gauge  indicates  a 
lowering  of  pressure  in  the  cooling  coil,  it  should  be  inspected 
throughout  its  entire  length  until  the  hole  is  discovered.  The 
water  will  gradually  form  at  the  hole  and  begin  to  drip.  After 
the  cooling  coil  is  filled  with  water,  a  small  air-pump  may  be 
used  for  giving  the  required  pressure,  in  case  there  is  not  a  satis- 
factory water  source  for  obtaining  the  pressure.  As  the  test 
is  only  to  determine  whether  the  cooling  coil  has  a  leak  in  it,  it 
will  in  no  case  be  necessary  to  establish  a  greater  pressure  than 
JOO  lb.  per  square  inch.  Some  engineers  prefer  to  submerge 
the  cooling  coil  in  a  liquid,  under  an  air  pressure  of  80  to  100  lb. 
per  square  inch  for  a  period  of  about  one  hour,  and  note  the 
bubbles  rise  to  the  surface  of  the  liquid. 

Drying-out  Transformers. — Several  methods  exist  for  drying 
out  high-voltage  transformers,  the  best  being  considered  as 
follows: 

1.  Short-circuit  either  the  high  or  low- voltage  winding  and 
admit  sufficient  current  to  raise  the  temperature  of  the  windings 
to  approximately  80°  C.  The  amount  of  heat  necessary  to 
effect  this  temperature  will  range  between  one-third  and  one- 
fifth  of  the  full-load  current,  depending  on  the  room  temperature 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    147 

and  design  of  transformer.  Tlic  impedance  volts  necessary  to 
give  the  specified  range  in  current,  vary  from  0.4  per  cent.,  to 
1.5  per  cent,  of  the  rated  voltage  of  the  winding  to  which  the 
impedance  voltage  is  applied.  In  any  case,  the  current  ad- 
mitted must  be  so  regulated  that  the  temperature  of  the  wind- 
ings does  not  exceed  the  80°  C.  limit. 

The  temperature  of  the  transformer  windings  may  be  deter- 
mined by  the  increase  in  resistance,  or,  if  facilities  for  this  method 
are  not  available,  the  bulb  of  a  spirit  thermometer  may  be  placed 
in  direct  contact  with  the  low-voltage  winding  at  the  top.  Low- 
voltage  winding  is  specified  for  the  reason  that  to  place  the  bulb 
of  the  thermometer  in  contact  with  the  high-voltage  winding 
may  not  give  the  temperature  of  the  coils;  the  insulating  pieces 
set  around  the  coils  of  the  high-voltage  winding  being  built  up 
on  the  copper  under  the  tape  to  such  a  height  as  to  prevent  the 
thermometer  recording  the  temperature  of  the  copper.  The 
bulb  of  the  thermometer  should  be  placed  down  between  the 
low-voltage  coils  as  far  as  possible.  Mercury  thermometers 
must  never  be  used  for  this  purpose  because  of  their  liability  to 
break.  The  drying  process  should  be  carried  on  while  the  trans- 
former is  out  of  its  tank  in  order  to  give  as  good  a  circulation  of 
air  as  is  possible  under  the  conditions. 

The  following  table  is  considered  to  be  within  safe  limits  for 
carrying  on  the  drying  process  although  discretion  must  be  used 
as  in  the  case  of  an  unduly  moist  transformer  and  where  the  kw. 
capacity  and  voltage  enter  into  consideration.  That  is  to  say, 
a  transformer  coming  under  the  heading  of  44,000  to  70,000 
volts,  having  a  kw.  capacity  of  200  kw.  and  less,  can  be  taken  as 
safe  if  the  heat-run  period  is  only  carried  on  for  60  hours  instead 
of  72,  or  a  transformer  coming  under  the  heading  of  22,000  to 
33,000  volts,  having  a  kw.  capacity  of  200  kw.  or  less  may  be 
considered  safe  if  the  heat-run  period  is  carried  on  for  only 
24  hours  instead  of  48  hours;  assuming  all  transformers  in  normal 
condition: 

It  is  impossible  to  give  anything  but  an  approximate  estimate 
of  the  number  of  hours  necessary  to  dry  out  a  transformer  of  a 
given  size  and  voltage.  Much  will  depend  on  the  condition  of 
the  transformer  when  it  is  received  from  the  factory,  whether 
in  an  unduly  moist  condition  or  dry. 

(2)  This  method  is  to  dry  the  transformer  and  oil  simulta- 
neously under  the  influence  of  heat  and  vacuum,  the  transformer 


148 


STATIONARY  TRANSFORMERS 


TABLE    IV— APPROXIMATE    HOURS    NECESSARY    IN    DRYING 
OUT   HIGH- VOLTAGE  POWER  TRANSFORMERS 




Voltage  of  system 

Hours  of  heat-run 

Kilowatt  capacity 

22,000  to    33,000 

38 

200  and  above 

22,000  to    33,000 

48 

500  to  1000 

22,000  to   33,000 

60 

1000  to  2000 

22,000  to    33,000 

72 

2000  and  above 

33,000  to   44,000 

52 

200  to    500 

33,000  to   44,000 

64 

500  to  1000 

33,000  to   44,000 

72 

1000  to  2000 

33,000  to   44,000 

84 

2000  and  above 

44,000  to    66,000 

64 

200  to    500 

44,000  to   66,000 

72 

500  to  1000 

44,000  to    66,000 

84 

1000  to  2000 

44,000  to    66,000 

92 

2000  and  above 

66,000  to   88,000 

84 

500  to  1000 

66,000  to   88,000 

96 

1000  to  2000 

66,000  to    88,000 

118 

2000  and  above 

88,000  to  110,000 

96 

500  to  1000 

88,000  to  110,000 

118 

1000  to  2000 

88,000  to  110,000 

130 

2000  and  above 

110,000  to  145,000 

140 

2000  and  above 

being  dried  inside  of  its  tank.  The  tank  is  first  made  vacuum 
tight,  this  being,  in  the  majority  of  cases  a  difficult  task  to  do  and 
is  only  accomplished  after  considerable  time  has  elapsed  with 
the  vacuum  pump  under  operation,  by  closing  the  holes  indicated 
by  the  whistling  noise  of  the  entering  air.  The  leaks  are  stopped 
by  using  putty,  which  should  be  fairly  stiff  in  order  to  keep  it 
from  being  drawn  into  the  tank.  If  the  puttying  is  done  a  day 
or  two  before  the  drying  process  is  begun,  thus  giving  the  putty 
a  chance  to  harden,  it  will  be  found  much  easier  to  obtain  the 
required  vacuum. 

One  of  the  transformer  windings  is  short-circuited  as  in  method 
(1),  although  the  actual  temperature  in  this  case  is  allowed  to 
reach  90°  C.  instead  of  80°  C,  and  the  temperature  is  determined 
by  the  increase  in  resistance.  The  temperature  of  the  oil  should 
be  maintained  at  approximately  80°  C.  during  the  drying 
process.  When  starting  the  heat-run  it  is  found  advantageous  to 
bring  the  temperature  up  quickly,  and  to  do  this,  full-load 
current  might  be  given  until  the  approximate  temperature  is 
reached,  after  which  it  should  be  reduced  to  the  specified  value. 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    149 

In  addition  to  heating  by  electric  current  a  certain  amount  of 
heat  should  be  applied  under  the  bottom  of  the  base  of  the 
transformer.  The  most  satisfactory  method  of  applying  heat 
to  the  base  is  to  use  grid  resistances  supplied  with  sufficient 
current  to  maintain  the  grids  at  full  red  heat.  The  grids  should 
be  distributed  under  the  base  so  as  to  make  the  heating  fairly 
general,  and  not  confined  to  one  portion  of  the  surface.  In  case 
some  other  method  of  heating  the  base  is  used,  extreme  care 
should  be  taken  that  the  supply  of  the  heat  does  not  become  too 
intense,  otherwise  the  oil  may  be  injured.  The  idea  of  supply- 
ing heat  to  the  base  is  to  maintain  uniform  temperature  of  the 
oil  throughout  the  transformer  structure  at  a  uniform  tem- 
perature of  80°  C.  It  is  found  that  the  temperature  of  the 
windings  reaches  90°  C.  considerably  in  advance  of  the  oil's  reach- 
ing 80°  C;  and,  for  this  reason,  it  is  necessary  either  to  disconnect 
the  current  occasionally  or  to  reduce  it  to  a  small  percentage  of 
full-load  current.  The  base  heating  should  be  relied  on  to 
maintain  the  oil  at  a  temperature  of  80°  C.  as  long  as  it  will, 
which  may  be  almost  constantly,  provided  a  sufficient  quantity 
of  heat  is  applied.  These  specified  limits  of  hours  referred  to 
above  are  for  the  actual  time  the  process  must  be  carried  on 
after  the  oil  has  reached  a  temperature  of  80°  C.  and  after  a 
vacuum  of  20  in.  has  been  established,  and  does  not  refer  to  the 
time  necessary  to  reach  the  80°  C.  point  and  20  in.  of  vacuum. 

When  electric  current  is  not  available,  steam  at  a  low  pressure 
may  be  used  for  heating,  the  steam  being  admitted  through  the 
cooling  coil.  Also,  steam  may  be  used  for  the  base  heating;  in 
which  case  the  entire  bottom  surface  of  the  base  should  be  sub- 
jected to  the  heat  of  the  steam.  Care  should  be  taken  in  ad- 
mitting steam  through  the  cooling  coils  that  the  temperature  of 
the  oil  does  not  exceed  the  Hmit.  This  method  of  applying  heat 
at  the  base  is  not  recommended,  principally  because  the  steam 
condenses  on  all  parts  of  the  transformer  tank. 

(3)  This  method  of  drying  transformers  requires  the  circulation 
of  heated  air  through  the  transformer  coils  and  core  while  it  is 
in  the  tank.  The  source  of  heated  air  should  be  connected  to 
the  base  valve  and  the  top  cover  of  tank  be  partly  removed.  The 
temperature  of  the  air  inside  of  the  tank  should  be  maintained 
at  approximately  80°  C,  and  the  process  should  be  carried  on 
under  this  temperature  for  a  period  of  three  days  for  units  of 
moderate  size,  the  same  discretion  being  used  as  mentioned  in 


150  STATIONARY  TRANSFORMERS 

methods  (1)  and  (2).  The  temperature  of  the  heated  air  as  it 
enters  the  transformer  should  not  exceed  100°  C.  This  method 
of  drying  transformers  is  especially  adapted  to  localities  where 
no  electric  current  is  available. 

The  oil  may  be  dried  by  the  vacuum  method  mentioned  in 
(2),  or  by  blowing  heated  air  through  it,  referred  to  in  the  above 
method.  Where  the  vacuum  method  is  used,  the  tank  must  be 
filled  to  within  a  few  inches  of  the  top,  so  that  the  cover  may  be 
kept  sufficiently  warm  to  prevent  condensation  of  moisture.  In 
case  the  transformer  tank  without  its  transformer  is  used  for  this 
purpose,  it  is  sometimes  necessary  to  put  temporary  bracing 
inside  of  the  tank  to  prevent  collapsing  under  vacuum;  this  does 
not  refer  to  the  tank  of  cylinder  form.  A  12-hour  run  under 
a  temperature  of  80°  C.  with  not  less  than  20  in.  of  vacuum 
should  be  quite  sufficient  to  dry  transformer  oil.  All  large 
installations  are  provided  with  tanks  for  this  purpose,  the  tanks 
being  of  the  cylinder  form. 

The  necessary  heat  for  bringing  the  temperature  of  the  oil  up 
to  80°  C.  may  be  obtained  by  placing  a  steam  coil  or  an  electric 
heater  in  the  bottom  of  the  tank.  Assuming  that  the  tank  in 
which  the  oil  is  being  dried,  will  radiate  approximately  0.25 
watts  per  square  inch,  the  amount  of  electric  energy  required 
to  maintain  the  oil  at  the  specified  temperature  may  quite 
easily  be  estimated.  The  electric  heater  should  be  about  double 
the  size  estimated  for  the  purpose  of  shortening  the  time  neces- 
sary to  reach  the  desired  temperature.  Whether  a  steam  coil 
or  an  electric  heater  is  used  it  must  be  placed  directly  on  the 
bottom  of  the  tank  as  it  is  necessary  to  maintain  the  oil 
temperature  about  uniform  throughout.  In  case  steam  is 
used,  its  pressure  should  not  be  greater  than  10  lb.  per  square 
inch. 

The  same  tank  may  be  used  for  drying  oil  by  means  of  forced 
circulation  of  air.  In  this  case  it  is  necessary  to  run  the  piping 
from  the  valve  in  the  base  of  transformer  up  above  the  oil  level, 
and  then  down  to  the  air  pump,  the  top  of  the  tank  having  an 
adjustable  opening  for  permitting  the  air  to  circulate.  The 
oil  must  be  heated  to  a  temperature  of  approximately  100°  C, 
and  the  process  continued  until  the  oil  becomes  dry  as  deter- 
mined by  test. 

Comparison  of  Shell  and  Core -type  Transformers. — Trans- 
formers of  any  type  should  not  be  selected  at  random  but  only 


CONISTRUCTION  OF  LARGE  TRANSFORMERS    151 

after  careful  investigation  of  design,  reliability  and  simplicity 
to  repair. 

In  general  the  shell  type  transformer  is  a  difficult  piece  of 
apparatus  to  repair  in  case  of  a  break-down;  the  difficulty  in- 
creases in  almost  direct  proportion  with  increase  in  capacity, 
and  in  the  larger  sizes  it  becomes  advisable  to  send  for  a  trans- 
former man  from  the  factory  to  do  repairs.  This  disadvantage 
has  been  and  is  to-day  considered  the  only  cause  of  a  large 
number  of  power  companies  operating  their  lines  at  high  volt- 
ages choosing  the  core-type  transformer. 

Experienced  transmission  engineers  never  fail  to  realize  the 
severe  conditions  to  which  transformers  are  subjected  to  in 
practice,  and  whenever  they  ask  manufacturers  for  transformers 
to  connect  to  their  high-voltage  lines,  seldom  fail  to  go  thoroughly 
into  the  factor  of  insulation,  which,  to  them,  means  continuity 
and  uninterrupted  service.  It  is  well-known  that  the  insulation 
of  a  high- voltage  transformer  is  subject  to  very  severe  potential 
strains,  some  of  which,  are: 

(a)  Sudden  increase  in  generator  voltage. 

(b)  Sudden  increase  in  line  voltage  from  local  causes. 

(c)  Direct  and  indirect  lightning  discharges. 

(d)  Ground  on  one  of  the  lines — depending  on  the  connection. 

(e)  Internal  or  external  arcing  grounds. 

(f)  Line  surges,  etc. 

Reliable  data  taken  from  a  number  of  power  companies  oper- 
ating long-distance  high-voltage  transmission  lines,  show,  that 
the  shell-type  transformer  has  been  more  reliable  than  the 
core  type  for  high-voltage  service. 

With  such  large  sizes  as  there  are  operating  to-day,  this  class 
of  apparatus  can  very  well  be  considered  as  one  of  the  most 
important,  if  not  the  most  important  piece  of  apparatus  con- 
nected to  a  transmission  system,  and  its  reliability  to  satis- 
factorily operate  for  long  periods  of  time,  after  it  has  once  been 
put  into  service,  is  looked  on  with  much  interest  and  wonder 
from  every  side.  To  think,  as  some  do,  that  once  a  transformer 
has  been  put  into  successful  operation  it  will  continue  to  operate 
indefinitely  in  a  satisfactory  manner  without  any  attention  is 
a  wrong  idea.  It  requires  attention,  and  must  be  given  atten- 
tion or  else  it  will  not  give  good  service. 

Late  modifications  in  the  grading  of  insulation  on  the  end 
turns  of  the  core-type  transformer  has  given  it  a  better  stand- 


152  ST  A  TIONA  R  Y  TRA  NSFORMERS 

ing,  and  it  is  now  considered  to  give  better  service  and  can  be  de- 
pended upon  in  this  regard  equally  as  well  as  the  shell-type 
transformer. 

Some  of  the  most  important  advantages  and  disadvantages  of 
these  two  general  types  might  be  summed  up  as  follows: 

Advantages  in  Favor  of  the  Shell-type. — Greater  radiating 
surface  of  coils  and  core  resulting  in  a  lower  temperature  in  all 
parts  of  transformer.  This  point  has  an  important  bearing  on 
the  insulation;  the  life  of  the  transformer  depending  on  the 
strength  of  the  insulation  of  the  hottest  part. 

Interlacing  of  coils  resulting  in  lower  reactance  voltages,  hence 
closer  regulation. 

Mechanically  stronger  and  better  able  to  withstand  the  electro- 
magnetic stresses.  As  the  electro-magnetic  stresses  are  pro- 
portional to  the  square  of  the  current,  a  short-circuit  of  many 
times  the  normal  full-load  current  will  produce  abnormal  strain 
in  the  transformer. 

Satisfactory  series-parallel  operation.  This  often  being  neces- 
sary on  large  transmission  systems. 

Advantages  in  Favor  of  the  Core  Type. — ^Easier  to  repair. 

Disadvantages  of  the  Shell  Type. — Difficult  to  remove  a  coil. 

Disadvantages  of  the  Core  Type. — ^With  low-voltage  winding 
designed  for  22,000  volts  and  above,  the  amount  of  insulation 
next  to  the  core  means  a  larger  mean  turn  of  winding;  the  tem- 
perature and  P  R  loss  being  increased  thereby. 

Radiating  surface  on  the  low-voltage  winding  very  poor, 
resulting  in  higher  temperatures.  It  is  a  disadvantage  if,  say, 
90  per  cent,  of  the  transformer  operates  at  a  temperature  of 
50°  C.  and  the  remaining  10  per  cent,  at  80°  C.  as  this  point  is 
tihe  weakest  link  in  the  insulation. 

The  arrangement  of  coils  (concentric)  results  in  poorer  regula- 
tion and  higher  reactance  voltages. 

Less  mechanical  bracing  because  of  its  design  and  form. 

Not  possible  to  operate  a  three-phase  (delta-delta)  trans- 
former in  case  one  winding  becomes  damaged. 

It  is  obviously  true  that  equally  good  results  can  be  obtained 
with  either  the  core-type  or  shell-type  construction,  but  the  de- 
sign of  one  or  the  other  would  depart  from  the  regular  standard 
expressed  above  if  equal  performances  and  reliability  of  opera- 
tion for  equal  conditions  of  load,  etc.,  are  desired.  The  differ- 
ence is  slight  but  nevertheless   in  favor  of  the  shell-type  con- 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    153 

struction,  particularly  from  the  operating  point  of  view,  with  the 
exception  of  repairs,  should  a  break-down  occur. 

The  shell-type  transformer  is  cheaper  than  the  core-type  with 
dear  copper  space  (large  copper  space  factor  and  ordinary  iron) . 
And  likewise,  the  core-type  transformer  is  cheaper  than  the  shell- 
type  with  relatively  cheap  copper  space  (low  copper  space 
factor  and  alloyed  iron).  In  other  words,  shell-  and  core-type 
transformers  cost  as  nearly  as  possible  equal  amounts  when 
equal  volumes  of  copper  and  iron  spaces  are  equally  expensive. 

Operation  of  Transformers. — The  general  idea  is  that  trans- 
formers do  not  require  any  care  or  attention  but  that  they  will 
operate  quite  satisfactorily  after  having  been  put  in  service  and  no 
further  attention  is  necessary.  This  is,  however,  not  the  way  to 
get  good  results,  although  in  some  fortunate  cases  it  might  apply 
and  has  applied.  Many  losses  of  large  power  transformers  have 
been  recorded  resulting  from  the  cessation  of  the  cooling  medium, 
all  of  which  could  have  been  saved  if  proper  care  had  been  given  to 
them.  Hourly  temperature  reading  is  the  best  indication  of  any- 
thing wrong  in  this  direction.  As  is  well  known,  high-voltage 
transformers  designed  to  operate  with  some  form  of  cooling  medium 
cannot  run  continuously,  even  at  no  load,  without  the  cooling 
medium,  since  the  iron  loss  alone  cannot  be  taken  care  of  by 
natural  cooling.  In  case  the  circulation  has  been  stopped  by 
any  cause,  the  transformer  may  be  operated  until  the  coils  at  the 
top  of  transformer  in  the  case  of  an  air-blast,  or  until  the  oil  in 
case  of  a  water-cooled  transformer,  reaches  an  actual  temper- 
ature of  80°  C.  This  temperature  limit  under  ordinary  condi- 
tions will  permit  the  transformer  to  continue  delivering  power 
for  about  three  hours;  a  very  close  watch  must  be  kept  of  the 
temperature  and  the  transformer  must  be  taken  out  of  service  as 
soon  as  it  reaches  this  limit. 

The  efficiency  of  a  transformer  is  usually  considered  to  be  its 
most  important  feature  by  the  majority  of  central  station 
engineers  and  managers  operating  distribution  systems.  By 
transmission  engineers  this  factor  is  not  considered  to  be  the 
most  important,  the  most  important  being  the  insulation  and 
mechanical  strength  of  the  transformer,  and  consequently  its 
reliability.  The  efficiency  is  no  doubt  an  important  feature  and 
should  not  be  neglected  in  the  choice  of  a  transformer  but  it 
cannot  be  considered  as  the  most  important  feature  of  a  large 


154  STATIONARY  TRANSFORMERS 

high-voltage  power  trunsforiucr.     The  writer  believes  the  right 
order  of  importance  to  be: 

1.  Reliability,  or  ability  to  supply  continuous  and  uninter- 
rupted service. 

2.  Safety,  or  a  condition  conforming  with  safety  to  life  and 
property. 

3.  Efficiency,  or  a  condition  met  with  after  proper  allowance 
has  been  made  to  conform  with  1  and  2. 

Reliability  as  referred  to  here  means  many  things  both  inter- 
nal and  external.  It  might  be  stated,  but  not  generally,  that 
efficiency  is  the  principal  point  in  discussing  transformers  from 
their  operating  point  of  view.  Where  large  high-voltage  power 
transformers  are  concerned,  efficiency  can  be  said  to  take  the 
third  place  of  importance,  and  probably  second  place  where 
low-voltage  city  distribution  transformers  are  concerned. 

Excepting  cases  of  lightning  and  roasting  of  coils  due  to 
constant  overload,  the  low-voltage  transformer  (as  used  for 
city  lighting  and  motor  service)  is  free  from  harm.  Not  so  with 
the  large  high-voltage  power  transformers  such  as  we  are  using 
at  the  present  day  in  connection  with  long-distance  transmis- 
sion systems.  Causes  of  failure  are  numerous;  that  is  to  say, 
causes  that  would  and  sometimes  do  bring  about  burn-outs  of 
coils,  moving  of  both  coils  and  iron,  and  complete  failure  of  a 
transformer. 

Use  and  Value  of  Reactance. — A  transformer  may  be  absolutely 
reliable  electrically  but  be  weak  mechanically  which  might 
bring  about  its  wreck. 

We  know  the  short-circuit  stresses  are  inversely  proportional 
to  the  leakage  reactance  of  the  transformer,  therefore  on  large 
systems  of  large  power  the  use  of  high  reactance  or,  more 
correctly,  high  automatic  reactance,  is  required  that  will  vary 
with  the  current.  Several  interesting  methods  are  from  time 
to  time  suggested  and  some  of  them  experimented  upon,  but, 
to  keep  the  current  down  to  even  15  times  normal  current  on  a 
"dead"  short-circuit  and  brace  the  transformer  to  take  care  of 
such  a  shock  and  be  certain  that  the  transformer  is  quite  strong 
enough  to  take  care  of  other  severe  mechanical  stresses  we 
need  more  experience.  Some  of  the  methods  tried  and  in 
their  experimental  stage,  are : 

(a)  Use  of  reactance,  internal  or  external,  or  both. 

(6)  Use  of  resistance  in  the  neutral  of  grounded  systems. 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    155 

(c)  Use  of  induction  generators  at  the  generating  stations 
in  place  of  the  ordinary  synchronous  machine. 

(d)  Strengthening  of  the  transformers  themselves. 
Experience  has  already  demonstrated  that  due  to  excessive 

short-circuit  current  a  limiting  reactance  of  some  form  or  other 
must  be  provided  for  large  power  transformers  operating  on 
systems  of  large  kilowatt  capacity,  its  design  being  either 
stationary  or  rotary;  that  is  to  say,  an  inductive  reactance  or 
an  induction  generator.  With  a  stationary  reactance  it  is  quite 
possible  to  arrange  to  have  it  automatically  switched  into 
circuit,  or  switched  out  of  circuit  as  the  case  might  warrant 
when  a  short-circuit  occurs.  This  would  mean  that  it  is  used  only 
when  required  and  is  always  out  of  circuit  under  normal  operating 
conditions. 

The  ability  of  a  modern  high-voltage  power  transformer  to 
withstand  short-circuits  is  of  far  greater  importance  than 
good  regulation.  Modern  practice  does  indicate  larger  reactance 
in  both  generators  and  transformers  when  operating  in  connec- 
tion with  long-distance  high-voltage  systems,  and  regulation 
of  6  per  cent,  or  worse  is  not  considered  very  bad.  Where  ordinary 
city  distribution  transformers  are  used  regulation  is  of  another 
order.  With  our  larger  systems,  larger  stations  and  larger 
transformers,  reactance  of  a  certain  given  value  in  addition 
to  that  originally  put  into  the  system,  station  and  transformers 
is  virtually  important  and  may  be  necessary  if  a  limit  is  to  be 
provided  to  check  the  enormous  amount  of  power  that  can  be 
developed  in  a  short  circuit. 

Causes  of  excessive  current  and  consequent  mechanical  strains 
are:  short-circuits  between  lines,  short-circuits  between  trans- 
former terminals  and  leads  and  bus-bars,  and  grounds  on  star- 
connected  systems  with  grounded  neutral  and  other  systems 
with  grounded  neutral. 

In  order  to  arrive  at  the  mechanical  stresses  occuring  in  a 
transformer  due  to  a  short-circuit  it  is  simply  necessary  to  use 
certain  expressions  in  terms  of  the  terminal  voltage,  short- 
circuit  current,  and  the  distance  between  primary  and  secondary 
coils.  For  example: — Take  a  5000-volt,  5000-kw.,  25-cycle  trans- 
former, full-load  current  in  the  primary  being  577  amperes  and 
measured  reactance  of  the  windings,  is  2.9  per  cent. 

If  (as  is  usually  done)  the  reactance  of  the  windings  be  given 
in  per  cent,  of  the  impressed  voltage,  the  short-circuit  voltage 


156  STATIONARY  TRANSFORMERS 

will  be  equal  to  the  full-load  current  divided  by  the  percentage 
reactance,  or: 

/  577 

/°=  1^  =  0029  =20,000  amperes  (18) 

which  represents  an  amount  in  excess  of  30  times  normal  full- 
load  current. 

If  (/)  is  the  force  in  grams  produced  between  primary  and 
secondary  windings,  and  (/)  the  distance  between  their  magnetic 
centers,  the  mechanical  work  done  in  moving  one  set  of  coils 
through  the  distance  (l)  against  the  force  (/)  would  be: 

^=/.^i.X  10^  joules  (19) 

At  short-circuit  very  little  magnetic  flux  passes  through  the 
secondary  coils  of  a  transformer,  but  if  the  system  is  sufficiently 
large  to  maintain  constant  voltage  at  the  terminals  of  the 
transformer  during  a  period  of  short-circuit,  full  magnetic  flux 
passes  through  the  primary  coils.  Such  a  condition  can  never 
exist  sufficient  to  maintain  a  constant  voltage  at  the  terminals 
of  transformers  located  at  the  end  of  long-distance  transmission 
lines,  but  for  comparatively  short  distances  and  on  systems  of 
practically  unlimited  power  behind  the  transformers  (sufficient 
to  roast  them)  and  of  close  regulation,  it  is  possible  to  get 
results  that  will  do  so  much  damage  as  to  wreck  them  entirely. 
Thus  a  transformer  with  a  2.9  per  cent,  reactance  would  give  a 
short-circuit  current  at  constant  voltage  of  30  times  full-load 
current,  and  one  with  a  reactance  of  2.3  per  cent,  would  give  40 
times  full-load  current,  while  one  with  4  per  cent,  reactance 
would  produce  only  a  short-circuit  current  of  25  times.  This, 
then,  certainly  demonstrates  that  more  reactance  in  the  trans- 
former circuit  for  better  protection  is  required,  and  that  the 
reactance  should  be  designed  proportional  to  the  current  so  as 
to  be  effective. 

The  terminal  voltage  at  the  transformer  during  short-circuit 
is  taken  from  the  leakage  inductance  of  the  transformer,  there- 
fore : 

810  E  1°  0.706  E  r.     ,   „ 

— ^ g.c.m.= jr-j mch  lb,  (20) 

is  the  force  exerted  on  the  transformer  coils  and  represents  the 
work  done  in  moving  the  secondary  coils  until  their  magnetic 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    157 

centers  coincide  with  those  of  the  primary  coils  (an  impossible 
condition)  which  would  cause  zero  reactance  flux  to  pass  between 
primary  and  secondary  coils. 

Now  assuming  that  the  transformer  in  question  has  three 
primary  coils  between  four  secondary  coils,  and  the  distance 
between  the  magnetic  centers  of  the  adjacent  coils,  or  half-coils, 
is  three  inches.  The  force  exerted  on  such  a  transformer  and 
its  respective  coils  would  be  something  like: 

=  940,000  lb.  =426  tons. 

This  force  is  exerted  between  the  six  faces  of  the  three  primary 
coils  and  the  corresponding  faces  of  the  secondary  coils,  and  on 
every  coil  face  is  exerted  the  force  of: 

^     426     ^,  , 
-^=  -„    =71  tons 
6        6 

If  the  distance  between  adjacent  coils  had  been  1.7  inches  the 
force  exerted  on  the  transformers  would  have  been  1,750,000  lb,, 
and  if  the  distance  had  been  4.3  inches  instead  of  three  inches, 
the  force  exerted  on  the  transformer  would  have  been  under  400 
tons,  or  about  65  tons  for  each  coil;  this  is  the  average  force, 
which  varies  between  0  and  130  tons. 

In  the  design  of  such  a  reactance  coil  the  following  formula 
is  used : 

4.44 /<i6A^ 
E Jos—  0) 

in  which  (/)  is  the  frequency,  (A^)  the  number  of  turns,  ((f))  the 
flux  enclosed  by  the  conductor.  The  flux  produced  by  a  coil 
without  an  iron  core  being: 

9  =  ~j^  (21) 

where  {N)  is  the  number  of  turns,  {d)  the  inside  diameter,  (A) 
a  constant  which  equals  0.28+0.125—  (jA      and  /  the  current 

in  the  coil. 

The  tendency  of  leakage  flux  is  not  uniform  throughout  the 
width  of  the  coil  of  a  transformer,  but  is  greater  at  the  center  of 

1  (I)  is  the  length  and  D  the  mean  diameter  of  the  solenoid. 


158  STATIONARY  TRANSFORMERS 

the  coil  (if  the  coil  be  imbedded  in  iron).  If,  then,  a  short- 
circuit  should  occur,  the  coil  will  have  a  tendency  to  buckle, 
and  should  it  not  be  sufficiently  strong  to  overcome  this  tendency, 
and  its  equilibrium  be  disturbed,  the  forces  of  conductor  upon 
conductor  will  not  lie  in  the  same  plane,  and  hence  are  liable  to 
break  the  insulation  tape  bindings,  and  heap  up  on  each  other 
at  the  point  of  most  intense  density. 

The  shell-type  transformer  coils  have  the  tendency  to  twist 
at  their  outer  corners,  and  the  vertical  portions  of  the  coils  to 
form  into  cable. 

The  core-type  transformer  coils  have  the  tendency  to  be 
forced  upward  or  downward  into  the  iron  core  (the  heaviest 
current  coils  being,  in  most  instances,  forced  out  of  position). 
If,  however,  the  centers  of  the  primary  and  secondary  are  exactly 
coincident  the  entire  force  would  be  exerted  in  a  horizontal 
direction,  and  there  would  be  no  tendency  for  any  of  the  coils 
to  move  vertically.  Whether  the  primary  or  secondary  is  forced 
up  depends  upon  which  coil  has  its  center  line  above  the  center 
line  of  the  other. 

It  is  only  recently  that  the  power-limiting  capabilities  of 
reactance  have  come  to  the  fore.  This  has  largely  been  due  to 
the  marked  movement  toward  consolidation  and  concentration 
in  the  central  station  industry  resulting  in  unified  systems  of 
gigantic  proportions,  the  loads  upon  which  may  fluctuate 
suddenly  through  a  wide  range  or,  still  worse,  short-circuits  on 
such  high  powered  systems  may  give  rise  to  rushes  of  current 
the  volume  of  which  was  hitherto  unknown  in  previous  systems. 
In  the  last  few  years  we  have  come  to  larger  and  larger  systems, 
and  consequently  greater  difficulties  of  operation.  The  con- 
centration of  power  for  economical  reasons  in  these  huge  power 
plants,  the  dependence  for  vast  industrial  enterprises  and  for 
our  ever  increasing  transportation  systems,  as  well  as  for  lighting 
and  industrial  power  from  ten,  twenty  or  thrity  substations 
distributed  over  vast  areas  and  supplying  large  cities,  make  it 
absolutely  essential  that  they  shall  l^e  protected  against  disturb- 
ance, and  that  every  possible  precaution  should  be  taken,  which 
experience  or  ingenuity  can  provide,  against  irregularity  in  opera- 
tion, because  if  these  huge  transformer  systems  are  going  to  be 
subjected  to  disturbance  and  interruption  of  service  other  factors 
affecting  their  regulation  and  efficiency  must  be  sacrificed  to  gain 
this  end,  if  need  be. 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    159 

The  advantages  of  iron  and  air  reactance  coils  in  a  power 
station  are  many,  provided  the  former  type  is  worked  at  a  suf- 
ficiently low  magnetic  density  so  that  it  will  not  become  satur- 
ated at  the  maximum  peak  of  a  short-circuit  current,  and  pro- 
vided the  latter  type  has  not  too  strong  an  external  magnetic 
leakage,  and  that  both  types  are  used  only  when  needed.  They 
are  effective  in  protecting  transformers  against  surges,  lightning, 
and  short-circuits. 

At  11 0,000  volts  and  over  a  phenomenon  makes  itself  felt,  especi- 
ally in  large  transformers,  which  is  negligible  at  lower  voltages; 
the  distributed  capacity  of  the  high-voltage  transformer  winding. 
At  lower  voltages,  the  transformer  capacity  (c)  is  negligible, 
and  the  transformer  thus  is  an  inductive  apparatus,  and  as  such 
is  free  from  all  high-frequency  disturbances,  such  as  traveling 
waves,  impulses,  stationary  oscillations,  etc.  High-frequency 
currents  cannot  enter  the  transformer,  but  produce  high  voltage 
between  the  end  turns,  protection  against  which  is  given  by  the 
high  insulation  of  the  end  turns  of  the  transformer,  and  also  the 
external  or  internal  choke  coil.  At  very  high  voltage  the 
electrostatic  capacity  of  the  transformer  becomes  appreciable, 
and  the  high-potential  coils  of  the  transformer  then  represent  a 
circuit  containing  distributed  capacity,  inductance,  resistance 
and  conductance.  In  the  high-voltage  winding  of  a  transformer 
the  inductance  is  high  in  value  and  the  capacity  low,  that  is, 
comparatively  speaking  lower  than  the  respective  constants  in  a 
high-voltage  transmission  line.  The  result,  in  general,  is  that 
the  oscillations  are  higher  in  voltage  and  lower  in  current,  in  the 
former.  The  danger  to  which  a  transformer  is  exposed  by  high- 
frequency  disturbances  from  the  line  side,  is  not  limited  to  the 
end  turns  only,  but  damage  may  be  done  anywhere  inside  of  the 
transformer. 

A  choke  coil  or  reactance  between  the  transmission  line  and 
transformer  might  or  might  not  in  this  case  become  a  source  of 
danger.  It  protects  the  transformer  from  certain  line  disturb- 
ances but  does  not  protect  the  transformer  itself  from  disturb- 
ances which  originate  inside  its  windings;  in  fact  the  addition  of 
this  choke  coil  has  the  tendency  to  throw  back  the  disturbance 
and  thereby  increase  the  internal  voltage  and  destructiveness. 

Recently  it  has  become  customary  to  specify  that  transformers 
of  large  sizes  and  high  voltages  must  not  have  less  than  ap- 
proximately 5  per  cent,  reactance  for  the  protection  of  trans- 


160  STATIONARY  TRANSFORMERS 

formers,  switches,  generators  and  all  parts  of  the  system  against 
the  high  mechanical  stresses  due  to  excessive  currents. 

To  increase  the  reactance  of  a  given  transformer  one  or  several 
modifications  are  possible,  as,  for  instance: 

(1)  Decreasing  the  dimensions  of  the  windings  in  the  direction 
in  which  the  leakage  flux  passes  through  the  wire-space. 

(2)  Decreasing  the  number  of  groups  of  intermixed  primary 
and  secondary  coils,  the  number  of  turns  of  each  group  being 
correspondingly  reduced. 

(3)  Increasing  the  total  number  of  turns  in  primary  and 
secondary. 

(4)  Increasing  the  length  of  turns  in  primary  and  secondary. 
From  the  viewpoint  of  safety  to  the  transformer  itself  by  the 

introduction  of  higher  reactance  within  the  transformer,  little 
practical  benefit  is  derived. 

No  hard  and  fast  rule  can  be  given  for  the  correct  location  of 
reactance.  There  are  several  reasons  against  making  it  all  a 
part  of  the  transformer.  Of  course,  so  far  as  the  generating 
stations  are  concerned  inductive  reactance  in  any  form  in 
connection  with  high  systems  is  important,  but  where  trans- 
formers are  located  at  the  end  of  long  transmission  lines  it  may 
or  may  not  be  necessary  to  use  it.  To  make  a  large  transformer 
of  large  power  with  high  reactance  is  not  an  easy  matter,  as  the 
general  principles  of  design  and  the  economic  utilization  of 
materials  obtain  for  us  only  low  factors,  and  in  order  to  make 
a  transformer  of  high  reactance  we  have  to  increase  its  cost  and 
its  ampere  turns,  with  of  course  more  copper  and  more  winding 
space,  and  consequently  a  larger  core  and  a  bigger  transformer 
for  the  same  output.  If  it  is  desired  to  increase  the  reactance 
by  increasing  the  space  between  the  primary  and  secondary 
windings,  the  same  results  are  obtained  and  the  efficiency  of 
the  transformer  is  reduced.  Placing  reactance  in  the  transformer 
itself  is  very  effective  on  short-circuit,  whereas  an  external 
current-limiting  reactance  will  not  generally  be  so  effective 
because  it  is  not  on  general  principles  designed  for  the  short- 
circuit  current  and  its  value  consequently  is  about  frustrated  by 
magnetic  saturation.  A  reactance  is  required  only  during  the 
short-circuit.  In  that  case,  why  then  should  an  expensive  and 
inefficient  transformer  be  considered  when  a  short-circuit 
might  occur  only  once  in  five  years;  would  it  not  be  much  better 
to  arrange  a  reactance  external  so  that  its  maximum  flux  on 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    161 

short-circuit  is  about  equal  to  its  voltage  flux?  If  a  reactance 
is  put  in  to  limit  the  short-circuit  current,  the  reactance  must 
be  there  when  the  short-circuit  occurs.  All  long  transmission 
lines  possess  magnetic  reactance  which  tend  to  reduce  the  volt- 
age so  that  less  reactance  will  be  required  for  similar  trans- 
formers located  at  the  end  of  the  line  than  those  at  the  generating 
station. 

Earthing  the  Neutral  of  Transformers. — The  chief  advantage 
of  resistance  in  the  neutral  of  a  star-connected  system  is  to  limit 
the  earth  current  on  short-circuit.  To  arrive  at  a  close  value  of 
resistance  that  will  limit  the  earth  current  at  all  times  is  not 
easy,  in  fact  in  most  cases  impossible;  the  ideal  condition  being 
where  the  load  and  voltage  of  the  system  are  not  disturbed. 
The  two  extreme  conditions  of  operation  are  the  insulated  system 
and  solid-grounded  system.  Of  these  two,  experience  so  far  has 
proved  the  better  to  be  the  grounded  system,  and  whether  we 
ground  through  resistance  or  "dead"  ground  the  method  depends 
entirely  on  the  system  itself.  Both  methods  will  work  satis- 
factory while  certain  conditions  of  operation  exist  and  likewise 
both  will  vary  under  one  particular  condition,  it  being  better  or 
worse  in  one  or  the  other  depending  on  the  kind  of  disturbance. 
It  seems  to  appear  that  the  best  way  to  limit  the  current  and 
disconnect  the  circuit  at  the  same  time,  in  preference  to  ground- 
ing through  resistance,  would  be  to  add  automatic  resistance 
in  the  line  side  which  would  come  into  effect  when  the  line 
current  reached  a  given  value  and  actuate  the  oil  switches.  A 
broken  insulator  or  ground  of  any  kind  on  the  line,  develops  a 
short-circuit  which  will  interrupt  the  service  depending  on  the 
exactness  of  the  resistance  in  the  grounded  circuit  and  neutral; 
generally  speaking  the  service  is  interrupted  whether  there  be 
resistance  in  the  grounded  neutral  or  not.  It  is  often  stated 
that  with  one  line  down  and  grounded  in  an  insulated  delta  system 
(a  non-grounded  delta  system),  an  interruption  or  short-circuit 
will  not  occur.  This  statement  is  very  vague  and  might  lead 
those  who  have  not  had  experience  with  very  high- voltage  system 
(voltages  above  60,000  volts)  to  believe  that  in  the  majority  of 
cases  it  is  correct.  It  may  be  stated  that  it  is  not  correct  for 
neither  the  non-grounded  star  or  delta  systems  operate  at  these 
high  voltages  except  in  very  unusual  cases. 

The  primary  or  secondary  may  be  put  to  earth  or  ground  through 
a  group  of  star-connected  transformers  as  shown  in  Fig.  122,  or, 
11 


162 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


if  these  transformers  are  not  available  and  a  ground  connection 
must  be  used,  a  substitute  might  be  made  similar  to  Fig.  123. 
With  this  connection  grounded  as  shown,  the  maximum  insulation 
strain  between  any  of  its  secondary  or  primary  windings  respec- 
tively to  ground  (whichever  side  might  be  grounded)  will  be  87 
per  cent,  of  full  voltage  between  terminals,  but  with  the  trans- 
former method  of  grounding  and  under  the  same  operating  con- 
ditions the  maximum  strain  will  not  be  greater  than  58  per  cent, 
of  full  voltage  between  terminals.     Grounding  the  neutral  point 


Fig.  122. — Method  of  grounding  an  insulated  delta  system  through  induc- 
tance coils. 


of  the  high-voltage  windings  of  transformers  connected  to  a 
transmission  line  will  immediately  operate  the  relays  or  circuit- 
breakers  should  one  of  the  line  conductors  fall  to  the  ground. 
Grounding  the  neutral  point  of  the  secondary,  or  low-voltage 
windings,  will  not  operate  the  relays  unless  some  special  provision 
has  been  made,  and  even  so,  before  the  relays  or  circuit-breakers 
are  actually  operated  the  secondary  or  low- voltage  windings  are 
made  subject  to  very  high-voltage  stresses.  The  best  method  of 
all  is  to  ground  the  neutral  points  of  both  the  high-  and  low-voltage 
windings  necessary,  and  where  delta-delta  systems  are  used,  ground 
the  windings  as  shown  in  Fig.  123.  A  common  condition  found 
in  practice  is  the  non-grounded  delta-delta  system.  On  systems 
where  the  ground  connection  is  used,  the  character  of  the  ground 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    163 

connection  iind  the  ground  itself  should  be  considered  at  the 
worst  time  of  the  year  only,  inspection  and  tests  at  other  times 
of  the  year  being  of  little  or  no  value  and  should  not  enter  into 
the  design  of  the  resistor  and  its  earth  resistance,  and  the  earth 
connection  itself.  Grounding  through  a  limiting  resistance 
gives  certain  advantages,  and  grounding  solid  has  the  disadvan- 
tage of  mterrupting  the  service  at  all  times  in  case  of  any  other 
ground  developing  in  the  metallic  circuit.  Its  use  is  helpful  in 
reducing  mechanical  stresses  and  in  largely  overcoming  dangerous 
surges  set  up  due  to  arcing  grounds,  etc. 


Fig.  123. — Method  of  direct  grounding  an  insulated  delta  system. 


Earth  Connections. — The  old  method  of  making  earth  connec- 
tions consisted  in  excavating  a  large  hole,  placing  an  expensive 
copper  plate  in  this  hole  surrounding  it  with  a  load  of  coke.  At  the 
present  time  this  method  is  generally  considered  to  be  not 
only  a  waste  of  money,  but  of  less  efficiency  than  the  multiple 
pipe-earths.  Their  resistances  are  no  lower  even  where  perforated 
and  treated  with  special  compounds,  their  current  capacity  no 
greater  and  their  life  and  constancy  no  better. 

For  very  small  areas  such  as  pipe-earths,  the  resistance  of  an 
earth  connection  depends  greatly  upon  the  exposed  area  of 
the  metal  plate  to  earth. 

A  simple  contact  of  a  metal  conductor  with  a  normally  moist 
earth  will  give  a  high  resistance  of  enormously  variable  values 
due  to  the  variations  in  contact. 


164  STATIONARY  TRANSFORMERS 

An  ordinary  pipe  resting  on  the  ground  was  found  to  give 
an  average  of  2000  ohms.  The  same  pipe  driven  6  feet  into  the 
ground  gave  15  ohms,  and  the  same  pipe  resting  on  dry  pebble 
gave  several  thousands  of  ohms. 

As  the  pipe  penetrates  the  earth,  it  is  found  that  each  addi- 
tional foot  adds  a  conductance  about  proportional  to  the  added 
length. 

The  specific  resistance  of  the  earth  will  depend  upon  what 
chemicals  exist  around  the  metal  plate  and  how  much  moisture 
there  is  present.  In  a  dry  sand-bank  the  resistance  is  prac- 
tically infinite.  In  a  salt  marsh  the  specific  resistance  is 
extremely  low,  being  about  one  ohm.  Resistances  of  earth 
connections  will  vary  greatly  even  in  the  same  locality. 

The  engineer  is  interested  mostly  in  the  earth  connection  in 
the  immediate  vicinity  of  the  earth  pipe  or  plate;  because  in 
the  main  body  of  the  earth,  the  area  of  cross-section  through 
which  there  is  current,  is  so  enormously  great  that  even  if  the 
specific  resistance  is  very  high  the  total  resistance  becomes 
negligibly  small.  If  the  earth  plate  should  lie  in  the  dry  non- 
conducting stratum  of  the  top  layer,  it  is  advisable  to  get 
some  means  of  introducing  better  conductivity,  not  only  in  the 
contact  between  the  plate  and  the  earth,  but  also  between  the 
earth  conducting  layer  deeper  down.  The  best  means  of 
accomplishing  this  is  to  pour  a  salt  solution  around  the  iron 
pipe  and  allow  it  to  percolate  down  to  a  good  conducting 
stratum.  In  order  that  this  solution  may  not  be  washed  out 
by  the  natural  filtration  of  rain  water,  it  is  well  to  leave  a 
considerable  quantity  of  crystal  salt  around  the  pipe  at  the 
surface,  so  that  rain  water  flowing  through  will  dissolve  the 
salt  and  carry  it  continuously  to  the  lower  strata.  Salt  has  the 
additional  value  of  holding  moisture. 

Objections  have  from  time  to  time  been  made  to  the  use  of 
salt  in  stating  that  it  would  be  destructive  to  the  metal  of  the 
pipe.  Under  the  usual  conditions  it  is  found  that  the  chemical 
action  on  an  iron  pipe  is  of  negligible  value.  Iron  pipe  is  very 
cheap,  and  it  would  be  better  practice  to  use  the  salt,  even  if  it 
did  destroy  the  pipe  within  a  period  of  years  which  it  does 
not. 

If  it  is  desired  to  decrease  the  resistance  of  earth  connections, 
it  is  necessary  to  drive  earth  pipes  that  are  separated  by  a  distance 
sufficient  to  keep  one  out  of  the  dense  field  of  current  of  the 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    165 

other.  The  current  density  in  the  earth  around  a  pipe-earth 
drops  off  approximately  as  the  square  of  the  distance.  A  good 
method  is  to  drive  multiple  pipes  at  least  6  ft.  apart  and  con- 
nect them  together,  and  the  resistance  will  decrease  almost  in 
proportion  to  the  number  of  pipes. 

The  more  salt  water  placed  around  a  pipe-earth,  the  less 
the  potential  gradient  near  the  pipe.  Inversely  the  drier  the 
earth,  the  more  the  concentration  of  potential  near  the  pipe. 

Earth  pipes  have  a  certain  maximum  critical  value  of  current 
which  they  will  carry  continuously  without  drying  out.  The 
application  of  a  high  voltage  might  have  so  bad  an  effect  that 
the  earth  around  a  pipe  will  be  dried  quickly  and  the  earth- 
plate  lose  its  effectiveness  as  a  ground.  As  the  moisture  is 
boiled  out  and  evaporated  at  the  surface  of  the  pipe,  the  sur- 
rounding moisture  in  the  earth  is  being  supplied,  but  the  vapor 
generated  tends  to  drive  away  this  moisture  from  the  pipe. 

The  diameter  of  the  pipe  effects  the  resistance  comparatively 
little.  Doubling  the  diameter  of  a  pipe  decreases  the  resistance 
by  a  small  percentage. 

Switching. — In  laying  out  systems  which  must  of  necessity  be 
more  or  less  complicated,  the  question  of  continuity  of  service 
should  be  always  kept  in  mind  and  placed  first  in  importance. 
At  the  present  time  there  are  in  operation  many  intricate  systems 
with  tie-lines  between  receiving  stations  and  generating  sta- 
tions. This  arrangement  presents  difficulty  in  providing  pro- 
tection on  account  of  the  interconnections  and  disturbance  in 
any  one  line  may  cause  an  interruption  of  a  large  portion  of  the 
system. 

Systems  are  sometimes  "overrelayed,"  relays  which  the  oper- 
ator cannot  thoroughly  understand  being  installed.  The  result 
is  that  he  oftentimes  renders  some  of  them  inoperative  by 
plugging  with  wood  to  prevent  what  he  considers  unnecessary 
interruptions  of  service,  which  may  be  at  the  expense  of  needed 
protection  to  the  transformers.  Before  deciding  upon  the 
system  of  connections  a  careful  study  should  be  made  to  deter- 
mine the  simplest  possible  arrangement,  when  taking  into  account 
not  only  the  delivery  of  energy  under  normal  conditions,  but  also 
continuity  of  service  under  abnormal  conditions. 

Low-voltage  moderate  capacity  transformer  switching  is 
simple.  High-voltage  power  transformers  connected  to  large 
systems  are  not  quite  so  simple  in  their  arrangement  of  switching 


166 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


and  their  protection  from  both  internal  and  external  short-circuits 
and  other  faults. 

Figs.  124,  125  and  120  show  four  different  methods  for  high- 
voltage  transformer  protection  and  their  switching.  The  series 
relays  may  be  attached  directly  to  the  switches  which  thoy 
operate,  while  those  relays  energized  by  means  of  series  trans- 
formers and  potential  transformers  (differential  relays)  are  usually 


Series 
Primary  Eelay 


Disconnecting  Switches 


lelay  SI   OH 

>    Switch 
hes   r^        Dteco: 


on 

Switch 

Dteconnecttog  Swltcihes 


110,000  Volt        Bus  Bars 

-Disconnecting  Switches *]; 

on  Switches . 


Series  Primary 
Relays      ~~ 


Disconnecting 
Switches 


[o]  on  Switch 


Power 
Transformers 


6.  Disconnecting 
/       Switch 


Bus  Bars 

Fig.  124. — Method  of  switching  and  protection  of  transformers. 

attached  to  the  switchboard  panels  located  on  the  operating 
gallery. 

Series  relays,  or  secondary  relays  (relays  energized  from  the 
secondaries  of  series  transformers)  or  both,  may  be  used  on  high- 
voltage  circuits.  The  oil-switches  marked  A,  B,  C,  etc.,  are 
operated  by  means  of  intermediate  low-voltage  switches  which 
receive  their  energy  from  an  auxiliary  source  of  supply  or  the  same 
source  as  the  case  may  be;  these  small  switches  are  located  on 
the  main  switchboard.  The  disconnecting  switches  are  of  the 
air-break  single-pole  type  and  are  usually  located  at  that  point 
where  a  break  in  the  circuit  is  most  desired,  for  interchanging,  or 
isolating  a  circuit,  bus-bar,  etc. 

If  a  transformer  is  switched  direct  on  to  a  high-voltage  system 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    167 

there  may  be  a  rush  of  current  equivalent  in  its  suddenness  to 
what  usually  occurs  in  high-frequency  experiments,  and  the  exact 
amount  of  the  rush  will  depend  largely  on  the  local  capacity  of 
the  high-voltage  switches  and  their  connections,  that  is,  the 
distance  they  are  located  from  the  transformers  to  which  they 
are  connected. 

The  usual  shocks  to  the  end  turns  of  transformers  due  to 
switching  are  dependent  upon  the  load,  character  of  the  load, 


Disconnecting 
Switch 


110,000  Volt 


o  Disconnecting 
Switch 


Oil  Switch 


Inverse  tlme- 

Umlt  series  Relay 

for  "A"  Switch 


Series 
Transformer 
Tlme-llinlt  over-load 
Relay  for  C  Switch  |6| 


Disconnecting  ^t 
Switch         (/ 


on  Switch 


Series 
Transformer 


Power  Trans^formers 


yr 


I         •  Keverse  c 
:p-'^||forA*H 


Series 
Transformer 
Reverse  cnrrent  Relay 
Switches 


I  Disconnecting 
Switch 


•f  To  Low  Voltage  Bus  Bars  t 
Fig.  125. — Two  methods  of  switching  and  protecting  transformers. 


type  of  switch  (oil  type  or  air,  and  single-  or  multi-break),  the 
time  allowed  for  opening,  and  the  method  of  switching.  As 
regards  the  switching  itself,  there  are  several  ways  in  which 
transformers  can  be  switched  on  to  a  line,  as  for  example: 

(1)  Switching  in  the  transformers  on  an  open  line. 

(2)  Switching   non -energized   transformers   on    an    energized 
line. 

(3)  Switching  energized   line   on  to  energizied  transformers. 

(4)  Switching  in  the  transformers  and  afterward  raising  the 
voltage  at  generating  station. 

(5)  Switching   under   any   of  the  above  conditions  but  with 
resistance  or  reactance  in  series. 


168 


STATIONARY  TRANSFORMERS 


(0)  Switching  on  the  low-voltage  side  of  transformers. 

(7)  Switching  on  the  high-voltage  side  of  transformers. 

(8)  Switching  energized  transformers  on  long  transmission 
lines  with  transformers  already  switched  in  at  the  receiving 
station,  but  "dead." 

(9)  Switching  in  transformers  during  lightning  storms, 
line  disturbances,  etc. 

(10)  Switching  in  transformers  using  oil-switches. 

(11)  Switching  in  transformers  using  air-break  switches. 


Series  Transformer 


Disconnecting 
Switcli 


Disconnecting 
Vh\       Switch 
-^[pjoil  Switch 


Bus  Bars 

o^Si  Disconnecting' 
Switch 


Definite  Time 
limit  Relay  for 
A  &  D  Switches 


Inverse  Tlme- 
lijiiit  Relay  for 
B  &  E  Switches 


Non-automatic 
Oil  Switch 


Series  Transformer 
Disconnecting 
Switch 

Oil  Switch 


Disconnecting 
Switch 


Generator  Busses 
Fig.  126. — Another  method  of  transformer  switching  and  protection. 

Most  of  the  methods  above  shown  are  bad  and  may  lead 
to  excessive  surges  being  thrown  on  the  windings  of  the  trans- 
formers. Next  to  (4),  the  best  method  is  to  do  all  switching 
on  the  low-voltage  side  whenever  possible  using  only  3-pole 
oil-switches  in  the  case  of  three-phase  circuits.  The  method 
(4)  is  generally  not  possible  because  of  the  necessity  of  lowering 


CONSTRUCTION  OF  LARGE  TRANSFORMERS    169 

the  voltage  of  the  system.  The  next  preferential  method  is 
where  a  receiving  station  is  "dead"  and  has  to  be  energized 
all  high-voltage  switches  being  closed  first. 

A  very  important  point  about  switching  is  the  time-limit. 
If  it  is  necessary  to  open  a  circuit  instantaneously  on  very 
large  loads,  switching  can  be  made  large  enough  to  do  the  work, 
but  where  economy  of  design  is  required,  a  time-limit  should  be 
used,  and,  probably,  a  reactance  to  limit  the  flow  of  current. 
The  time-limit  with  its  relay  will  therefore  take  care  of  that 
amount  of  current  which  it  is  set  for  and  will  permit  the  switch 
to  open  up  to  the  load  under  which  it  is  able  to  operate  safely. 
If  a  reactance  is  used  in  connection  with  switches  of  this  kind, 
it  might  be  well  to  provide  for  some  arrangement  whereby  it 
can  be  brought  into  use  only  when  it  is  needed  or,  for  instance, 
when  the  circuit  is  actually  being  opened. 

Aside  from  the  above  methods  of  closing  circuits,  there 
are  two  conditions  of  opening  circuits  which  should  be  avoided, 
as: 

(1)  Opening  a  long  transmission  line  under  heavy  load,  on 
the  high-voltage  side. 

(2)  Opening  a  long  transmission  line  on  the  high-voltage  side 
with  no-load. 

Method  (1)  refers  principally  to  short-circuits,  and  method 
(2)  to  a  high-voltage  line  required  to  be  made  "dead."  If  a 
live  circuit  is  to  be  cut  out  at  all  it  should  be  done  from  the  low- 
voltage  side  no  matter  what  the  load  conditions  are. 

High-voltage  switches  for  large  power  transformers  should 
be  of  the  most  substantial  mechanical  construction  and  capable 
of  safely  breaking  a  circuit  under  extreme  conditions.  For 
comparatively  small  installations  it  is  still  customary  to  use 
expulsion  fuse-switches  installed  inside  of  a  delta  connection, 
that  is,  one  on  each  lead  or  6  for  a  three-phase  group.  This 
is  not  good  practice  for  the  reason  that  with  a  blown-out  fuse 
(leaving  the  delta  open)  a  bad  phase  distortion  may  occur. 
Where  connections  of  this  kind  are  necessary,  they  should  be 
made  through  air-break  switches  and  not  fused  switches. 


CHAPTER  X 

AUTO  TRANSFORMERS 

The  ordinary  auto-transformer  is  a  transformer  having  but  one 
winding.  The  primary  voltage  is  usually  applied  across  the 
total  winding,  or  in  other  words,  across  the  total  number  of  turns, 
and  the  secondary  circuit  is  connected  between  two  taps  taken 
off  from  the  same  winding,  the  voltage  ratio  being  equal  to  the 
ratio  of  numbers  of  turns. 

The  auto-transformer  shown  in  Fig.  127  has  two  taps  brought 
out  at  a  and  h.     Thus  the  whole  or  part  of  the  winding  vasiy  be 


innn 

pOOr 

.000000000000. 

vOO./n 

c      50        > 

uuu 

inftfi 

lUOU 

1100 

Fig.  127. — Step-up  auto-transformer. 

used  to  raise  the  voltage  or  lower  the  voltage  simply  by  changing 
the  connections. 

For  example,  the  primary  a  b,  is  wound  for  1000  volts,  a  c 
and  b  d  each  being  wound  for  50  volts.  As  will  be  seen,  by 
taking  a  tap  out  from  a  and  d,  the  secondary  gives  1000-1-50  = 
1050  volts.  And  by  moving  to  the  far  end  of  the  winding,  a, 
the  voltage  maybe  raised  from  1050-1-50  =  1100  volts.  In  order 
to  obtain  550  volts  all  that  is  necessary  is  to  bring  two  leads  out 
from  X  and  d,  or  x  and  c;  the  secondary  then  gives  1050—500  = 
550  volts. 

170 


AUTO  TRANSFORMERS 


171 


For  pressure  regulation  auto-transformers  are  very  convenient, 
being  used  to  some  extent  for  regulating  the  voltage  of  trans- 
mission lines.  They  are  also  used  for  starting  induction  motors; 
and  lately  they  have  been  used  for  single-phase  railway  service, 
rectifiers,  low  voltage  (5-15-27- volts), lighting,  etc. 

For  series  incandescent  systems  a  transformer  similar  to  that 
shown  in  Fig.  127  may  be  used.  A  portion  of  the  winding,  a  b,  is 
common  to  both  primary  and  secondary.  The  secondary 
voltage,  c  d,  is  greater  than  the  primary,  a  b,  by  the  voltage  of 
the  winding,  b  d  and  c  a.  The  voltage,  6  d  or  c  a,  is  thus  added 
to  the  primary  to  form  the  secondary  voltage  of  the  circuit. 

By  reversing  the  connections  of  the  winding,  6  d  and  c  a,  how- 
ever, it  may  be  made  to  subtract  its  voltage  from  the  primary, 


Fig.  128. — Step-down  auto-transformer. 

a  6;  in  which  case  the  secondary  voltage  becomes  less  than  the 
initial  primary  voltage;  (Fig.  128).  Further,  by  bringing  a 
number  of  leads  from  parts  of  the  winding,  b  d  or  c  a,  the  second- 
ary voltage  may  be  increased  or  decreased  by  successive  steps  as 
the  different  leads  are  connected  to  the  secondary  circuit.  For  a 
given  transformation  of  energy,  an  auto-transformer  will  be  con- 
siderably smaller  than  an  ordinary  transformer,  and  consequently 
its  losses  will  be  less  and  the  efficiency  higher.  The  amount  of 
power  delivered  to  the  service  mains  at  an  increased  voltage  is 
very  much  greater  than  the  power  actually  transformed  from  the 
primary  to  the  secondary  of  the  transformer.  In  fact,  the  power 
actually  transformed  is  equal  to  the  increase  of  voltage  multiplied 
by  the  total  current  delivered;  and  the  output,  or  actual  rating 
of  the  transformer  is  based  upon  the  power  transformed. 

Example. — ^The  voltage  of  a  long-distance  transmission  line  is 
to  be  raised  from  40,000  to  45,000  volts,  and  the  maximum 
current  to  be  handled  is  750  amperes.     What  is  the  rating  of 


172 


STATIONARY  TRANSFORMERS 


auto-transformer  required  for  this  service?     and  what  will  be  the 
actual  power  delivered  over  the  line? 

The  actual  rating  of  the  auto-transformer  will  be, 

5000X750  =  3750  kilowatts. 
The  total  power  delivered  to  the  line  will  be, 
45,000  +  750  =  33,750  kilowatts. 

In  Fig.  128  the  secondary  voltage  is  smaller  than  the  primary. 
The  voltages,  b  d  and  c  a,  are  thus  subtracted  from  the  primary 
to  form  the  secondary  voltage  of  the  circuit.  The  auto-trans- 
former may  thus  act  as  a  step-up  or  step-down  transformer. 

The  action  of  an  auto-transformer  is  similar  to  that  of  the 
ordinary  transformer,  the  essential  difference  between  the  two 
lies  in  the  fact  that  in  the  transformer  the  primary  and  secondary 
windings  are  separate  and  insulated  from  each  other,  while  in 
the  auto-transformer  a  portion  of  the  winding  is  common  to  both 


-1000- 


-100- 


-1100- 


FiG.  129. — Two-phase  auto-transformation. 

primary  and  secondary.  The  primary  and  secondary  currents 
in  both  types  of  transformers  are  in  the  opposite  direction  to 
each  other,  and  thus  in  an  auto-transformer  a  portion  of  the 
winding  carries  only  the  difference  between  the  primary  and 
secondary  currents. 

In  the  foregoing  explanation  of  auto-transformation  the 
ordinary  transformer  will  be  used  instead  of  the  auto-transformer. 

Two-phase,  four-wire,  auto-transformation  as  shown  in  Fig. 
129,  where  the  secondary  winding  is  made  to  assist  the  primary, 
may  be  considered  as  two  ordinary  single-phase  circuits.  The 
ratio  of  transformation  in  this  case  is  10  to  1,  therefore  we  obtain 
by  the  connection  as  shown,  a  secondary  voltage  of  1100. 

By  reversing  the  secondary  connection  it  is  possible  for  us  to 
get  1000  - 100  =  900  volts. 


AUTO  TRANSFORMERS 


173 


If  we  should  take  one  end  of  the  secondary  windhig  and  connect 
it  as  shown  in  Fig.  130  we  would  obtain  50  per  cent,  of  the  primary 
voltage  plus  100,  which  is  the  total  secondary  voltage.  Then 
assuming  the  primary  and  secondary  to  have  a  four-wire,  that  is 
to  say,  two  independent  single-phase  systems,  we  would  have  a 


a 

o' 

b 

6' 

^—1000^ 

- 

* — 1000—^ 

^600^-500- 

^imo" 

l*-100— 

-500* 

-HJOO^ 

^-100-* 

" 600—* 

« — occ 

— *- 

a  Ob  d 

Fig.  130. — Two-phase  four-wire  auto-transformation. 

secondary  voltage  of  500  plus  100=  600  volts.  The  points,  x 
and  y,  are  taps  brought  out  from  the  middle  points  of  the 
windings. 

Another  two-phase  auto-transformation  is  represented  in  Fig. 
131.     Both  primary  and  secondary  areconnected  to  a  three-wire 


Fig.  131. — Two-phase  three-wire  auto-transformation. 

system  from  which  we  obtain  a  secondary    voltage   of    1100 
between  a'   h   and    h  c' ,  and  1550  volts  between  a'  and  c',  or 

1100X1.41  =  1550  volts. 

A  very  interesting  combination  giving  a  five-wire,  two-phase 
transformation  is  shown  in  Fig.  132.  From  this  arrangement  it 
is  seen  that  quite  a  number  of  different  voltages  and  phase 


174 


STATIONARY  TRANSFORMERS 


relations  can  be  obtained,  and  by  simply  shifting  the  connection 
at  X  we  increase  and  decrease  the  resultant  voltages. 

At  a  re  rf  and  c  x  d  the  respective  phases  that  constitute  the 
four-phase  relation  have  been  changed  from  45  degrees  to  a 


o'     6 


-1000 > 


«-500 


^-nmPi 


-100- 


-1100- 


< 300- 


"f ^1000 » 


600->k-500- 


U — 100 — > 


-1100- 
-500- 


FiG.  132. — Two-phase  five-wire  auto-tranformation. 

slightly  higher  value,  the  voltage  increasing  in  proportion  to  the 
increase  of  phase  difference. 

The  three-phase  arrangement  shown  in  Fig.  133  is  a  method  of 
auto-transformation  by  which  we  are  enabled  to  supply  approxi- 


-IflOO- 


immJ  liK^^mJ 


-1000- 


-1000 — *■ 


immJ 


n^^'^'iij^ 


-100 


-^00- 
-1040 


-1040- 


-1040- 


-100- 


FiG.  133. — Three-phase  star  auto-transformation. 

mately  1040  volts  to  the  secondary  mains,  1,  2  and  3,  from  a 
1732-volt  primary  source  of  supply,  using  three  transformers 
with  a  ratio  of  10  to  1,  or  =  1000  to  100  volts. 
Between  points  ah,h  c,  a  c,  we  obtain 


500  X\/3=  866  volts. 


AUTO  TRANSFORMERS  175 

Between  points  1  2,  2  3,  and  1  3,  there  exists  approximately 
500  +  100  X  \/3  =  1040  volts. 

The  three-phase  delta  connection  shown  in  Fig.  134,  with  its 
three  secondary  windings  left  open-circuited,  may  be  used  where 


-loco- 


< 1000 *■  < ^1000 — > 


M^^sinJwmsiSiSirisismsi^ 


a  l  b  c 


-im- 


|<-ioo^ 

c          a 
-500 =H 


-SCO 


Fig.    134. — Three-phase   auto-transformation   with   secondaries   open 

circuited. 

a  three-phase  500-volt  motor  is  installed.  The  secondary  wind- 
ings, if  required,  may  be  used  at  the  same  time  for  lighting  or 
power.  To  obtain  a  100-volt  lighting  service  it  will  be  necessary 
to  connect  the  secondary  windings  in  delta,  running  a  three-wire 
distribution  to  the  source  of  supply,  ah  c.     This  method  of 


Fig.  135. — Three-phase  delta  auto-transformation. 

connecting  transformers  is  often  found  useful  in  places  where 
transformers  of  correct  ratio  are  not  obtainable. 

The  combination  shown  in  Fig.  135  has  its  secondary  windings 
connected  in  circuit  with  the  primary  windings.  Like  Fig.  133 
a  tap  is  brought  out  from  the  middle  of  each  winding;  but  instead 


176 


STATIONARY  TRANSFORMERS 


of  leading  out  to  the  secondary  distribution,  it  is  connected  to  one 
end  of  the  secondary  winding  as  shown  at  1,  2  and  3;  the  result 
of  which  represents  a  phase  displacement  as  shown  in  the  vector 
diagram. 


Fig.  136. — Three-phase  double-star  auto-traiisformation. 

Using  the  same  transformers  as  in  the  previous  examples, 
connecting  A  B  C  to  a  500X\/3=866  volt  supply,  it  is  possible 
for  us  to  obtain  a  number  of  different  voltages  for  the  second- 
ary distribution,  such  as  three  at   1000,  three  at  600,  three 


-1732- 


-1783 


-1000- 


-100- 


< ^1732- 


-1000- 


-500»^- 


—1000 — >\ 


-500V3- 


B^ 


Fig.    137. — Three-phase  star  auto-transformation  with  secondaries  open- 
circuited. 


at  520,  six  at  500,  three  at  173,  and  three  at  100  volts,  re- 
spectively (Fig.  136).  According  to  the  raito  of  transformation 
applied  at  the  secondary  distribution  it  is  understood  that  the 
kilowatt  capacity  of  the  transformers  will  vary. 

Another  three-phase  combination  is  shown  in  Fig.  137,  where 
it  is  shown  that  the  primary  windings  are  connected  in  star,  and 


AUTO  TRANSFORMERS 


177 


the  three  leads,  ABC,  are  connected  to  a  1732-volt  supply. 
From  the  middle  of  each  primary  winding  a  tap  is  brought  out 
at  a  6  and  c. 

The  secondary  voltage  across  ab,  b  c  and  a  c  is  500X\/3  =866 
volts.     The  100-volt  secondary  winding  may  be  used  for  power 


-1350- 


-1000- 


Lm|Mi>-[ 


-1850- 


-1^- 


-1000- 


U^^^ioaoMm^^ 


-1000- 


^100- 
-500- 


-500 


"^100- 
-500- 


FiG.  138. — Three-phase  auto-transformation  using  primary  windings  only. 

and  lighting,  single  or  polyphase,  depending  upon  the  size  and 
design  of  the  transformer. 

Fig.  138  represents  a  three-phase  transformation,  using  only 
the  primary  windings.  One  end  of  each  primary  winding  is 
connected  to  the  middle  point  of  another  primary  winding. 
Three-phase,  1350  volts,  impressed  on  A  B  C  will  give  500 
volts  on  1-2,  2-3,  and  1-3. 


12 


CHAPTER  XI 

CONSTANT-CURRENT  TRANSFORMERS  AND  OPERATION 

For  operating  arc-  and  incandescent  lighting  systems  from 
constant-potential,  alternating-current  mains,  the  constant- 
current  transformer  is  frequently  used.  It  is  designed  to  take  a 
nearly  constant  current  at  varying  angles  of  lag  from  constant- 
potential  circuits,  and  to  deliver  a  constant  current  from  its 
secondary  winding  to  a  receiving  circuit  of  variable  resistance. 

Thus  the  transformer  operates  automatically  with  respect 
to  the  load,  making  it  possible  to  cut  out  any  number  of  lamps, 
from  full  rated  load  to  zero  load,  while  still  maintaining  a  con- 
stant current  on  the  line.  The  self-regulating  characteristic 
is  obtained  by  constructing  the  transformer  in  such  a  manner 
that  either  the  primary  or  secondary  coil  is  balanced  through 
a  system  of  levers  against  a  counterweight,  which  permits  the 
distance  between  primary  and  secondary  coil  to  vary.  This 
automatically  increases  or  decreases  the  reactance  of  the  circuit 
in  such  amount  as  to  hold  the  current  constant  irrespective  of 
the  load. 

For  the  majority  of  series  incandescent  systems  the  constant- 
current  transformer  will  be  found  lower  in  initial  cost  and  more 
reliable  in  service  than  the  reactive  coil  method,  as  it  combines  in 
one  element  the  advantages  of  a  regulating  device  and  an  insulat- 
ing transformer. 

One  type  of  transformer  consists  of  a  core  of  the  double 
magnetic  type  with  three  vertical  limbs  and  two  flat  coils 
enclosing  the  central  limb.  The  lower  coil,  which  is  fixed,  is 
the  primary,  while  the  upper  one,  or  secondary,  is  carried  on  a 
balanced  suspension,  and  is  free  to  move  along  the  central  limb 
of  the  core. 

The  repulsion  between  the  fixed  and  moving  windings  of  the 
system  for  a  given  position  is  directly  proportional  to  the  current 
in  the  windings. 

For  series  enclosed,  arc-lighting  on  alternating-current  circuits 
the  constant-current  transformer  is  universally  used.  This  type 
usually  consists  of  a  movable  secondary  and  fixed  primary  wind- 

178 


CONSTANT-CURRENT  TRANSFORMERS 


179 


ings,  surrounded  by  a  laminated  iron  core.  Tliis  core  and  the 
yokes  at  the  top,  bottom  and  sides,  form  a  double  magnetic  cir- 
cuit, as  shown  in  Fig.  139. 

The  magnetic  flux  which  passes  through  the  primary  winding, 
flows  partly  through  the  secondary  winding.  The  secondary 
winding  is  made  movable  and  partly  counterbalanced  by  a 
weight  so  that  an  increase  in  the  current  causes  the  secondary 
to  be  pushed  further  away  from  the  primary.  The  weight  is  so 
adjusted  as  to  sustain  the  coil  against  the  leakage  flux,  and 
simply  by  changing  the  amount  of  counterweight  the  trans- 
former can  be  adjusted  to  m'aintain  any  desired  current. 


1J?     iP 

Fig.  139. — Type  of  constant-current  transformer  for  arc  lighting  systems. 

In  small  transformers,  which  have  but  one  movable  coil,  the 
counterweight  equals  the  weight  of  the  coil  less  the  electrical 
repulsion,  and  a  reduction  in  the  counterweight  will  produce  an 
increase  in  the  current.  In  large  transformers,  having  two  sets 
of  movable  coils  balanced  one  against  the  other,  the  counter- 
weight serves  merely  to  draw  the  primary  and  secondary  coils 
together  in  opposition  to  the  repulsion  effect.  In  this  case, 
a  decrease  in  the  counterweight  is  followed  by  a  decrease  in  the 
current. 

The  counterweight  attachment  is  made  adjustable  because 
the  repulsion  exerted  by  a  given  current  in  the  coils  is  not  the 
same  at  all  positions  of  the  coils,  being-  greater  when  the  pri- 
maries and  secondaries  are  close  together  and  less  when  the  pri- 


180  STATIONARY  TRANSFORMERS 

maries  are  separated.  When  the  primaries  and  secondaries  are 
separated  by  the  maximum  distance,  the  effective  force  tending 
to  draw  them  together  should  be  less  than  when  they  are  in 
full-load  position;  that  is,  when  the  primaries  and  secondaries 
are  close  together. 

For  capacities  of  100  lamps,  or  less,  there  is  one  primary  and 
one  secondary  coil,  the  primary  being  stationary,  and  the 
secondary,  or  constant-current  coil  is  suspended  and  so  balanced 
by  weights  that  the  repulsion  between  it  and  the  primary  changes 
the  distance  between  them  with  variations  of  load,  the  current 
in  the  secondary  being  kept  constant. 

For  capacities  of  100,  or  more,  there  are  two  primary  and  two 
secondary  coils.  A  separate  circuit  of  lamps  may  be  operated 
from  each  secondary,  the  two  circuits  being  operated  at  different 
currents  if  desired. 

The  maximum  load  of  each  circuit,  when  operated  separately, 
will  be  one-half  the  total  capacity  of  the  transformer.  However, 
when  it  is  necessary  to  operate  the  two  circuits  at  unequal 
loads,  the  load  of  one  circuit  being  less,  and  of  the  other  greater, 
than  one-half  the  rated  capacty  of  the  transformer,  the  coils 
may  be  connected  together  in  the  multi-circuit  arrangement, 
which  will  allow  loads  up  to  the  total  capacity  of  the  trans- 
former to  be  carried  upon  one  circuit. 

For  capacities  of  250,  or  more,  there  may  be  one  or  two  primary 
and  two  secondary  coils,  two  circuits  being  operated  from  each 
secondary,  thus  giving  four  circuits  from  the  transformer.  It  is 
not  necessary  that  the  loads  on  the  two  circuits  from  each  coil  be 
balanced,  and,  if  desired,  the  total  load  can  be  carried  on  one  cir- 
cuit alone,  provided  the  insulation  of  the  line  is  such  as  to  admit 
the  high  voltage  which  will  be  introduced.  Constant-current 
transformers  are  of  the  air-  and  oil-cooled  type.  The  air-cooled 
type  is  surrounded  by  a  corrugated  sheet  iron  or  cast-iron  casing 
with  a  base  and  top  of  cast  iron.  The  oil-cooled  type  is  sur- 
rounded by  a  cast-iron  case,  providing  ample  cooling  surface. 
The  working  parts  are  immersed  in  oil,  which  assists  in  conduct- 
ing away  the  heat. 

Constant-current  transformers  are  usually  located  in  stations 
where  electric  energy  is  generated,  received  or  transformed,  as, 
for  instance,  a  receiving  station  at  the  end  of  a  long  high-voltage 
line;  although  in  large  cities  they  are,  for  convenience,  located 
in  district  sub-stations  and  close  to  distribution  centers. 


CONSTANT-CURRENT  TRANSFORMERS  181 

They  are  made  to  operate  on  60-  125-cycle  and  even  133-cycle 
systems,  and  for  any  reasonable  primary  voltage.  It  is  cus- 
tomary to  furnish  a  60-  125-cycle  transformer  for  a  125-  133-cycle 
system. 

The  constant-current  transformer  will  maintain  constant 
current  even  more  accurately  than  the  constant  potential 
transformer  maintains  uniform  potential,  and  its  regulation  over 
a  range  from  full-load  to  one-third  its  rated  capacity  will  come 
within  1.5  per  cent,  if  properly  adjusted. 

The  efficiencies  of  constant-current  transformers  with  a  full 
load  of  arc  lamps  vary  at  60  cycles  from  about  96  per  cent,  for 
the  100-lamp  transformer  to  about  94.5  per  cent,  for  the  25-lamp 
transformer. 

Another  constant-current  transformer  known  as  the  "edge- 
wise wound"  type  is  fast  replacing  the  older  type  mentioned 
above. 

From  this  modern  method  of  construction  several  advantages 
are  derived,  principal  among  which  is  the  almost  absolute  im- 
possibility of  an  internal  short-circuit,  as  the  voltage  between 
any  two  adjacent  conductors  consists  of  only  the  volts  per  turn 
of  the  transformer,  or  at  the  most  about  10  volts. 

The  construction  of  this  type  is  somewhat  different.  The 
core  is  built  up  of  thin  laminations  of  sheet  steel  and  has  a  center 
leg  of  cruciform  shape.  This  form  of  construction  not  only 
tends  to  support  itself,  thereby  requiring  a  very  thin  angle  for 
securely  clamping  the  laminse  and  decreasing  the  eddy  current 
in  the  clamp,  but  the  form  of  construction  also  gives  the  most 
economical  flux  path  as  well  as  permitting  a  smaller  diameter 
coil. 

The  primary  and  secondary  consist  of  four  concentric  edge- 
wise wound  coils  of  double  cotton  covered  rectangular  wire.  The 
four  sections  are  assembled  together  concentrically  with  wooden 
spacing  strips  to  maintain  at  all  points  an  air-duct  of  sufficient 
width.  Two  surfaces  of  each  conductor  are  therefore  exposed 
to  the  currents  of  air  passing  through  the  air-ducts,  thereby  in- 
creasing the  effective  radiating  surface  of  each  coil  by  about  three- 
fold. The  large  radiating  surface  with  the  consequent  cool  run- 
ning allows  a  very  high  current  density  which  permits  of  less 
copper  per  ampere-turn,  less  weight,  less  floor  space,  and,  of 
course,  a  cheaper  transformer  for  the  same  kilowatt  rating  than 
the  older  type  above  mentioned. 


182 


STATIONARY  TRANSFORMERS 


Construction  of  Transformer. — The  core  of  this  efficient  and 
most  modern  type  of  constant-current  transformer  is  built  up 
of  laminations  of  specially  annealed  iron,  which  are  sheared  to  the 
required  length  and  width.  Each  sheet  or  lamina)  is  treated  by 
coating  the  surfaces  with  a  species  of  japan,  which  serves  to 
I'educe  materially  the  eddy  current  loss  in  the  core.  This  japan 
is  applied  by  passing  each  individual  sheet  between  rolls  which 
are  constantly  kept  moist  with  the  japan.  After  passing  the  rolls, 
the  pieces  of  iron  are  carried  along  a  travelling  table,  where  they 
are  dried  by  passing  nozzles  through  which  air  is  blown. 


Short-Circuit, 
Flug 


*•«<— >H    l-x-^^J 


Fig.  140. — Connections  for  single,  or  multiple  of  series  arc  or  incandescent 

circuits. 


Like  the  core-type  constant  potential  transformer  the  construc- 
tion commences  with  the  iron,  the  iron  legs  being  assembled 
in  a  horizontal  position.  After  all  the  laminations  have  been 
stacked  together  and  wrapped  with  the  necessary  sheets  of 
"horn-fiber,"  the  whole  assembly  should  be  placed  in  a  press 
under  considerable  pressure  which  will  reduce  the  weight  of  the 
iron  to  the  required  dimensions.  In  the  factory  an  hydraulic 
press  is  generally  used,  the  pressure  applied  being  equivalent  to 
several  tons;  the  temperature  is  also  increased  to  about  250°  F. 
There  are  three  legs  in  each  transformer — two  of  rectangular 
shape,  and  one  of  "cruciform"  shape  which  is  larger  in  cross- 
section  than  the  two  rectangular  legs — each  leg  being  assembled 
and  handled  separately  until  completed,  after  which  the  three  are 
raised  vertically  and  accurately  spaced  for  the  placing  of  end 
laminations.     After  the  end  laminations  have  been  put  in  and 


CONSTANT-CURRENT  TRANSFORMERS         183 

the  whole  assembly  made  ready  for  the  placuig  of  coils,  the 
completed  iron  core  is  turned  upside  down. 

The  form  of  coil  for  this  modern  type  constant-current  trans- 
former is  similar  in  every  respect  to  a  large  majority  of  those 
used  in  constant  potential  power  and  lighting  transformers.  It  is 
cylindrical  in  form  and  consists  of  rectangular  shaped  wires,  the 
width  being  several  times  the  thickness.  All  the  coils  are  placed 
on  the  center  leg  which  is  the  one  of  cruciform  dimensions.  In 
all,  there  are  four  coils  located  concentrically  with  insulating 
spaces  between  each  coil.  For  arc  and  incandescent  lighting  it  is 
customary  to  make  the  lowest  voltage  coil  the  movable  coil.  For 
use  with  mercury  arc  rectifier  systems  the  primary  coil  is  the 
movable  coil,  while  the  secondary  coil  is  the  movable  coil  for 
series  alternating-current  lighting. 

The  fabrication  of  this  class  of  coil  for  constant-current  trans- 
formers is  interesting.  In  the  winding  of  the  coil  a  collapsible 
cylindrical  former  is  used  which  has  the  same  inside  diameter 
as  the  required  inside  diameter  of  the  coil.  The  wire  is  set  on 
edge  and  wound  in  this  manner  around  the  former.  In  the 
winding,  the  wire  is  fed  through  a  friction  device  to  give  the 
required  tension,  the  starting  end  of  the  wire  being  clamped  to 
a  flanged  collar  revolving  with  the  winding  form.  The  wire  is 
pressed  firmly  against  the  collar  by  another  collar,  which  loosely 
fits  the  winding  form  and  is  held  stationary;  next  follows  another 
flanged  collar  which  presses  heavily  against  the  stationary 
collar,  thereby  forcing  the  several  turns  of  wire  very  tightly 
against  one  another.  The  flanged  collar  thus  travels  slowly  along 
the  winding  former,  so  that  for  one  revolution  of  the  machine,  or 
turning  lathe,  it  travels  a  distance  equal  to  the  insulated  thick- 
ness of  one  turn  of  the  wire.  After  the  coil  has  been  finished  and 
taken  from  the  collapsible  former  it  is  set  into  a  clamp  and 
baked  at  a  temperature  of  about  180°  F.  in  a  well-ventilated  oven, 
thereby  removing  all  moisture;  and,  while  still  hot,  is  dipped  in 
a  tank  containing  insulating  varnish.  This  heating  and  dipping 
is  repeated  several  times  until  the  coil  becomes  self-sustaining 
and  until  the  insulation  will  take  up  no  more  varnish.  The 
coil  is  then  wound  with  tape,  each  turn  overlapping  the  pre- 
ceding turns  by  one-half  to  one-third  its  width.  Various  kinds 
of  tape  are  used  in  the  insulating  of  coils,  such  as  cotton  tape, 
which  is  varnished  after  applying,  varnished  cambric  tape, 
which  is  treated  after  applying,  and  mica  tape.     Mica  tape  is 


184 


ST  A  TIONA  R  Y  TRA  NSFORMERS 


only  used  on  very  high-voltage  transformers.  Where  cotton 
tape  is  employed  it  receives  a  brushing  of  the  best  quality  of 
insulating  varnish,  is  then  baked,  revarnished  and  rebaked, 
this  process  being  repeated  several  times  for  each  tape. 

The  regulation  of  this  transformer  comes  within  one-tenth  of 
1  amp.  above  or  below  normal  current  from  full-load  to 
no-load. 

Fig.  140  (A),  (B)  and  (C)  show  three  different  methods  of 
connecting  the  secondaries  of  constant-current  transformers  for 
single,  or  multiple  of  series  arc  or  incandescent  circuits.     Method 


C.T. 


Tx 


Fig.  141. — Method   of  operation  from  three-phase  primaries,    using   two 
constant  current  transformers  in  each  case. 


(A)  represents  a  simple  circuit;  (B)  a  single  secondary  winding 
with  two  circuits  operated  in  series  or  singly  as  desired;  (C) 
shows  a  multi-circuit  secondary,  each  circuit  being  operated 
independently. 

Fig.  141  (A)  and  (B)  represents  two  methods  of  operating 
constant-current  transformers  and  series-arc  lighting  from 
three-phase  primaries.  The  secondaries  of  (A)  show  two  inde- 
pendent circuits,  each  circuit  being  supplied  from  separate 
transformers,  the  primaries  of  which  are  wound  for  2000  volts  and 
2000X\/3/2  volts  respectively.  The  secondaries  of  (B)  also 
show  two  independent  secondary  circuits,  each  being  in  two  parts 
as  shown. 

Before  shipment,  constant-current  transformers  are  made 
subject  to  an  insulation  test  of  10,000  volts  between  secondary, 
primary  and  all  parts;  also  between  primary,  secondary  and  all 


CONSTANT-CURRENT  TRANSFORMERS 


185 


parts.  The  duration  of  the  insulation  test  is  one  minute.  If 
however,  the  primary  voltage  is  above  5000,  which  is  very  rarely 
the  case,  the  insulation  test  is  twice  normal  voltage. 

The  modern  type  of  constant-current  transformer  referred  to 
above,  has  a  guaranteed  temperature  rise  not  exceeding  55°  C. 
based  on  a  room  temperature  of  25°  C.  If  the  temperature  of 
the  room  is  greater  than  25°  C,  0.5  per  cent,  for  each  degree' 
difference  should  be  added  to  the  observed  rise  of  temperature; 
if  less,  subtracted. 

The  record  tests  of  a  100-lamp  6.6  amp.,  air-cooled  constant- 
current  transformer  are  shown  below. 


CONSTANT-CURRENT  TRANSFORMER  RECORD  TEST 
Full-load  =100  lamps— 6.6  amp.  —60  cycles 


Test 


Lights  connected 


100 

90 

80 

70 

1215 

1050 

892 

892 

656 

635 

611 

504 

9500 

8660 

7950 

6940 

29.0 

27.3 

25 

21.8 

96.1 

96.6 

96.1 

95.8 

94.3 

94.9 

94.8 

94.5 

92.5 

92.5 

92.4 

92.0 

89.1 

89.2 

89.1 

88.5 

72.6 

71.8 

69.6 

69.7 

55.2 

54.3 

52.9 

53.0 

37.8 

37.2 

36.2 

36.3 

26.1 

25.7 

25.0 

25.0 

60 


Core  loss  in  watts 

Copper  loss  in  watts 

Sec.  open-circuit  voltage 

Pri.  current  at  2200  voltage 

(Temperature  rise  after  12  hours'  run 

55°  C.) 
Efficiency  in  per  cent,  at  full-load.  .  .  . 

At  75  per  cent,  full-load 

At  50  per  cent,  full-load 

At  33  per  cent,  full-load 

Power  factor  in  per  cent,  at  full-load . 

At  75  per  cent,  full-load 

At  50  per  cent,  full-load 

At  33  per  cent,  full-load 


892 

402 

6930 

18.7 


98.5 
94.1 
91.4 

70.2 
53.2 
36.4 


When  operating  a  load  of  6 . 6  amp,  lamps  plus  7 . 5  per  cent, 
line  loss,  the  voltage  and  power  factor  at  the  lamp  are : 
Volts  per  lamp  4- line  loss =83  per  cent. 
Power  factor  of  lamp        =  84  per  cent. 


CHAPTER  XII 

SERIES  TRANSFORMERS  AND  THEIR  OPERATION 

The  characteristics  of  the  series  transformer  are  not  very 
generally  known.  It  is  used  in  connection  with  alternating- 
current  amnaeters  and  wattmeters  where  the  voltage  of  the 
circuit  is  so  high  as  to  render  it  unsafe  to  connect  the  instrument 
directly  into  the  circuit  and  when  the  current  to  be  measured  is 
greater  than  the  capacity  of  the  instrument,  and  it  is  also  used 
in  connection  with  relays. 

The  series  transformer  was  first  considered  and  used  in  con- 
nection with  street  lighting  systems,  but  was  an  entire  failure. 

im 

n 


Sa<-^*r- 


Ip         ^P  *•  o  7^ 

Fig.  142.  Fig.  143. 

Figs.  142  and  143. — ^Fundamental  series  transformer  vector  relations. 

For  almost  20  years  it  kept  in  the  background  until  it  came  into 
commercial  use  in  connection  with  measuring  instruments. 

At  this  time  its  accuracy  was  equal  to  any  other  instrument 
on  the  market  and  as  the  accuracy  of  instruments  improved,  the 
demand  for  a  more  accurate  device  increased.  Also  with  the 
introduction  of  higher  voltages  better  insulation  was  required, 
insulation  that  would  not  only  protect  the  instruments  but  also 
the  operator.  As  time  went  on  it  was  found  essential  to  use  a 
magnetic  circuit  without  joints  in  order  to  keep  the  magnetizing 
current  within  reasonable  limits  compared  with  the  accuracy  of 
transformation.  To  accomplish  this  a  core  was  made  of  sheet- 
iron  rings  the  primary  and  secondary  windings  being  placed  on 
this  core.  For  high  voltages,  insulation  became  a  serious  problem. 
The  number  of  turns  of  insulation  had  to  be  increased.  This 
meant  a  considerable  waste  of  time  and  money,  and  even  after 
they  were  once  in  place  it  was  difficult  to  take  care  of  the  heat 

186 


SERIES  TRANSFORMERS  187 

from  the  windings.  To  overcome  the  necessity  of  using  an 
extensive  number  of  turns  of  insulation  a  new  type  was  developed 
in  which  the  low  voltage  secondary  was  wound  on  the  core, 
while  the  insulating  material  consisted  of  telescoping  tubes  held 
apart  by  suitable  spacing  strips. 

Up  to  recent  years  it  was  considered  quite  sufficient  to  insulate 
the  series  transformer  with  the  same  margin  of  safety  as  that 
allowed  in  constant-voltage  transformers;  that  is,  double  the 
line  voltage.  For  several  reasons  it  was  deemed  advisable  to 
require  an  insulation  test  of  three  times  that  of  the  operating 
circuit.  It  is  evident  that  as  the  secondary  is  usually  grounded 
it  is  liable  to  receive  and  provide  a  path  for  a  lightning  discharge; 
moreover,  it  furnishes  current  to  instruments,  and  protecting 
devices,  and  might  be  a  source  of  danger  to  the  attendant. 

The  transformer  consists  of  an  iron  magnetic  circuit  inter- 
linked with  two  electric  circuits.  The  primary  is  connected  in 
series  with  the  line,  the  current  of  which  is  to  be  measured,  and 
the  secondary  is  connected  to  instruments,  etc.  It  is  evident  that 
the  meter  readings  will  go  up  and  down  with  the  primary  current; 
though  the  ratio  of  the  instrument  to  the  primary  current  may 
not  be  the  same  at  all  times,  any  one  value  of  the  current  will 
always  give  the  same  reading.  In  well  designed  transformers 
the  ratio  of  primary  to  secondary  current  is  nearly  constant  for 
all  loads  within  the  designed  limits. 

In  the  case  of  a  series  transformer  with  its  primary  connected 
to  the  line  and  its  secondary  on  open  circuit,  the  primary  current 
will  set  up  a  magnetic  field  in  the  iron  of  the  transformer,  which 
will  cause  a  drop  in  voltage  across  the  primary.  The  same  mag- 
netic flux  will  also  cut  the  secondary  and  generate  in  its  winding 
an  e.m.f.  the  value  of  which  is  equal  to  the  voltage  drop  across 
the  primary  multiplied  by  the  ratio  of  the  secondary  to  primary 
turns.  When  the  secondary  is  open-circuited  the  iron  of  the 
transformer  is  worked  at  a  high  degree  of  saturation,  which  pro- 
duces an  abnormally  large  secondary  voltage.  This  condition 
gives  rise  to  serious  heating  of  the  transformer  as  well  as  great 
strains  upon  the  insulation. 

If  the  secondary  circuit  be  closed  through  a  resistance  there 
will  be  a  secondary  current,  which  allows  a  larger  resultant  flux 
in  the  core  the  less  the  value  of  the  current,  which  flux  generates 
the  secondary  e.m.f.  An  increase  in  the  secondary  resistance 
does  not  mean  a  proportionate  decrease  in  the  secondary  current, 


188  STATIONARY  TRANSFORMERS 

it  only  means  such  a  decrease  in  the  current  as  would  increase  the 
resulting  magnetic  flux  and  secondary  e.m.f.  sufficiently  to  main- 
tain the  current  through  the  increased  resistance.  Under 
ordinary  conditions  the  resistance  in  the  secondary  circuit  is  low, 
so  that  the  secondary  e.  m.  f.  is  low  and  also  the  resultant  mag- 
netic flux. 

If  the  secondary  be  short-circuited  so  that  there  is  no  magnetic 
leakage  between  the  windings,  and  current  put  on  the  line,  a 
magnetic  flux  will  be  set  up  in  the  primary.  This  flux  produces 
an  e.m.f.  in  the  secondary  which  sets  up  a  current  opposed  to 
that  in  the  primary.  The  result  is  that  the  flux  threading  the 
windings  will  be  reduced  to  a  value  which  will  produce  a  sufficient 


0 


io  A 

Fig.  144. — Direction  of  three-phase  currents — chosen  arbitrarily  for  con- 
venience. 


voltage  to  establish  current  through  the  secondary  resistance. 
Thus  the  magnetomotive  force  of  the  primary  current  is  less  than 
that  of  the  secondary  current,  by  an  amount  such  that  the  flux 
produced  thereby  generates  the  voltage  required  to  send  the 
secondary  current  through  the  resistance  of  the  secondary 
circuit,  the  vector  sum  of  the  secondary  current  and  the  mag- 
netizing current  being  equal  to  the  primary  current. 

When  the  secondary  resistance  is  increased,  there  will  be  a 
decrease  in  the  secondary  current  which  allows  a  larger  resultant 
flux,  which  in  turn  decreases  the  secondary  e.m.f.,  which  in- 
creases the  secondary  current.  When  a  stable  condition  is 
reached  there  is  a  greater  secondary  e.m  f.  and  a  less  secondary 
current.  In  order  to  determine  the  characteristics  of  a  series 
transformer  it  is  in  general  necessary  to  know  the  resistances 
and  reactances  of  the  primary  and  secondary  windings  of  the 
transformer  and  of  the  external  secondary  circuit,  and  the 
amount  and  power-factor  of  the  exciting  current  at  the  various 
operating  flux  densities  in  the  transformer.  If  no  magnetizing 
current  were  required,  the  secondary  ampere-turns  would  be  in 


SERIES  TRANSFORMERS  189 

approximate  equilibrium  with  tlie  primary  ampere-turns  and 
consequently  the  ratio  of  the  primary  to  the  secondary  current 
would  be  the  inverse  of  the  number  of  turns.  In  order  to  attain 
this  ratio  as  nearly  as  possible  the  iron  is  worked  considerably 
below  the  "knee"  of  the  B-H  curve,  so  that  very  little  magnetiz- 
ing force  is  required. 

The  series  transformer  is  worked  at  about  one-tenth  the 
magnetic  density  of  the  shunt  transformer,  due  to  the  fact  that  a 
large  cross-section  of  iron  is  used.  It  is  readily  understood 
that  a  series  transformer  differs  very  much  mechanically  and 
electrically  from  a  shunt  transformer;  the  latter  maintaining  a 
practically  constant  voltage  on  the  secondary  irrespective  of  the 
load,  while  the  former  must  change  its  secondary  voltage  in  order 
to  change  its  secondary  current. 

The  fundational  expression  for  the  current  of  a  series  trans- 
former is  the  same  as  for  a  constant  potential  transformer,  or 

^  =  ^  =  k  or  N  s  =  KN  V  (22) 

I  s     N  p  ^  ^    ^ 

where 

I  p  =  primary  current.     I  s  =  secondary  current. 

N  p  =  primary  turns  of  wire  in  series. 

A^  s  =  secondary  turns  in  series. 

K  =  constant  =  ratio  of  transformation. 

If  the  ratio  of  transformation  is  known  and  primary  turns 

fixed,  the  secondary  turns  are  equal  to  primary  turns  multiplied 

by  the  ratio  of  transformation. 

Assuming  a  one  to  one  ratio  and  a  non-inductive  secondary 

load,  the  diagram  shown  in  Fig.  142  is  obtained.     The  primary 

current  and  e.m.f.  are  equal  and  opposite  in  phase  to  the  secondary 

current  and  e.m.f.  and  as  the  load  is  non-inductive  the  primary 

current  is  in  time  phase  with  the  primary  voltage. 

where 

0  I  p  =  primary  current.  0  E  p  =  primary  e.m.f. 

O  I  s  =  secondary  current.         0  E  s  =  secondary  e.m.f. 

and  0  I  m  =  magnetizing  current. 

In  actual  operation  the  secondary  current  is  in  time  phase  with 

the  secondary  e.m.f.  if  the  secondary  load  is  non-inductive,  but 

the  primary  current  lags  behind  the  primary  e.m.f.,  as  shown 

in  Fig.  143  by  the  angle  0. 

The  secondary  ampere-turns  0  I  s,  and   the   primary  turns 


190  STATIONARY  TRANSFORMERS 

0  I  p  being  equal  to  the  line  current  multiplied  by  the  primary 
turns  is  made  up  of  two  components  /  p  and  /  p'-O  I  p'.  I  p' 
being  that  part  which  supplies  the  core  loss,  and  0  I  p'  that  part 
which  is  equal  and  opposite  to  the  secondary  ampere-turns. 
The  iron  loss  and  "wattless"  components  ase  I  p'  I  p"  and  /  p. 
In  a  well  designed  series  transformer,  the  secondary  ampere- 
turns  for  non-inductive  secondary  load  can  be  taken  as  equal 
to  0  /  p-l  p'  I  p",  there  fore  secondary  amperes  is 

To  determine  this,  it  is  merely  necessary  to  find  the  ampere- 
turns  0  I  p  supplying  the  iron  loss,  subtract  this  value  from  the 
primary  ampere-turns  /  p  and  I  p' ,  and  divide  by  the  secondary 
turns  /  s. 

To  determine  the  iron  loss  it  is  necessary  to  know  the  loss 
in  watts  per  unit  weight  of  iron  at  a  given  frequency  and  varying 
induction.  Let  P  represent  the  watts  loss  at  a  given  frequency 
and  induction,  /  the  iron  loss  current,  N  s  secondary  turns,  then 

p 

Iron  loss  current  =  ^  (24) 

and 

P  N  s 

ampere- turns  (iron  loss)  =1  N  s  =  — ^^ —  (25) 


secondary  ampere-turns  =  1  p  N  p p—  (26) 


E 
and 

N  p    P 
secondary  amperes  =  /  Pj^-  —  p  (27) 

1  s 
If  the  ratio  of  transformation  is  made  equal  to  -^—  the  second- 

^  1  p 

P 

ary  current  will  be  less  than  the  desired  value  by  the  amount  ^ 

amperes.     The  error  in  the  transformation  is 

As     PXlOO  .... 

per  cent,  error  of  rj—=i— — — -^  (28; 

^  I p     I  sXi^ 

To  compensate  for  this  error  the  secondary  turns  must  be  slightly 

I  p 
diminished  from  the  ratio  j^  N  s  so  that  the  secondary  current 

will  equal  Is. 


SERIES  TRANSFORMERS 


191 


Assume  that  the  secondary  is  on  short-circuit,  and  for  con- 
venience, that  there  is  no  magnetic  leakage  between  primary 
and  secondary.  At  the  moment  the  current  is  started,  flux  is 
set  up  in  the  primary  winding.  This  flux  produces  an  e.m.f. 
in  the  secondary  which  sets  up  a  current  opposed  to  that 
in  the  primary.  The  result  is  that  the  flux  threading  the  two 
windings  will  be  reduced  to  a  value  producing  only  sufficient 
voltage  to  cause  current  through  the  secondary  resistance, 
thus  restoring  approximate  equilibrium  between  the  primary 
and   secondary   currents.     Thus  the   magnetomotive  force  of 


Fig.  145. — Method  of  obtaining  equal  three-phase  current  readings  by  the 
use  of  two-  or  three-series  transformers. 


the  primary  current  is  less  than  that  of  the  secondary  current 
by  an  amount  such  that  the  flux  produced  generates  the  voltage 
required  to  send  the  secondary  current  through  the  resistance 
the  vector  sum  of  this  current  and  the  magnetizing  current 
being  equal  to  the  primary  current. 

A  series  transformer  should  maintain  a  practically  constant 
ratio  between  its  primary  and  secondary  through  its  full  range 
of  load.  Such  a  condition  can  only  be  approached  but  not 
absolutely  reached,  since  the  magnetizing  current  becomes  a 


192  STATIONARY  TRANSFORMERS 

formidable  factor  in  preventing  a  constant  ratio.  A  minimum 
magnetizing  current  is  accomplished  in  commercial  transformers 
by  having  an  abundance  of  iron  in  the  core,  thus  working  the 
iron  at  a  very  low  magnetic  density,  permitting  the  current  ratio 
of  the  primary  to  the  secondary  to  vary  approximately  in  inverse 
ratio  to  the  number  of  turns.  As  iron  is  worked  considerably 
below  the  "knee"  of  the  B-H.  curve,  a  good  range  of  load  is 
allowed  for  ammeters,  wattmeters  and  relays  to  be  operated  on 
the  secondary. 

In  either  a  delta-  or  star-connected  three-phase  system  the 
currents  in  the  three  leads  are  displaced  120  degrees  from  each 
other  and  one  of  the  leads  may  be  considered  a  common  return 
for  the  other  two.  Assuming  the  instantaneous  direction  of 
current  in  leads  A  and  C  to  follow  the  arrows  shown  in  Fig.  144, 
then  the  direction  of  the  current  in  B  will  follow  the  arrow  in 
the  opposite  direction.  With  a  delta-connected  system  the 
current  in  lead  A  is  the  resultant  of  that  in  the  two  phases  B  A 
and  C  A ;  the  current  in  lead  B  is  the  resultant  of  that  in  the 
two  phases  A  B  and  C  B;  and  the  current  in  C  is  the  resultant 
of  that  in  A  C  and  B  C.  With  the  star  connection,  the  direction 
of  the  two  currents  A  and  C  are  in  opposite  directions  to  the 
neutral  point,  and  the  current  B  toward  the  neutral  point  0. 

If  all  the  secondaries  of  series  transformer  are  not  arranged  in 
the  same  direction,  it  will  be  found  that  the  phase  relation 
between  the  three  phases  will  be  either  60  or  120  degrees.  In 
either  a  delta-  or  star-connected  group  of  transformers  it  becomes 
necessary  to  reverse  the  secondary  leads  with  respect  to  the  others 
when  a  change  of  phase  relation  is  desired.  A  connection  com- 
prising two  series  transformers  is  shown  in  Fig.  145  where  A  and 
C  are  connected  to  two  ammeters,  and  the  opposite  end  of  second- 
ary winding  connected  to  a  common  wire  at  0.  In  the  vector 
diagram  it  is  shown  that  0  A  is  equal  to  the  current  in  lead  A 
both  in  magnitude  and  direction  and  0  C  the  current  in  lead 
C  which  has  a  phase  relation  oi  120  degrees.  The  resultant 
current  that  is  in  the  common  wire  O  is  equal  in  magnitude 
and  direction  to  0  B'.  The  ammeter  (2)  indicates  the  current 
in  lead  B,  and  its  reading  is  equal  to  the  value  shown  in 
Fig.  145. 

Assume  that  one  of  the  transformers  is  reversed  as  at  C , 
Fig.  146.  Referring  to  the  vector  diagram,  0  A  represents  the 
current  in  lead  A  both  in  value  and  direction,  0  C  the  current 


SERIES  TRANSFORMERS 


193 


in  lead  C,  and  the  resultant  current  A  C  represents  in  value 
and  direction  the  current  through  the  ammeter  (2).  The  re- 
sultant current  A  C  is  displaced  from  that  of  lead  B  by  90 
degrees,  and  is  found  to  be  V3  as  great  sls  A  0,  0  B  or  0  C. 
Thus,  if  the  two  transformers  0  A  and  0  C  are  wound  to  give  5 
amperes  on  their  secondaries  with  full  load  current  in  the  primary, 
the  current  across  A  C  will  be  5X'\/3=8,66  amperes.  So  that 
in  connecting  series  transformers  and  it  is  found  that  one  of  the 
phase  currents  bear  V  3  relation,  it  is  simply  necessary  to  reverse 
one  of  the  transformer  secondary  leads. 


Fig.  146. — ^Another  method  of  using  two-  and  three-series  transformers 
with  three  ammeters. 


The  volt-amperes  on  each  transformer  of  a  two-transformer 
connection  like  Fig.  147  are  equal  to  \/s  times  the  volt-amperes 
of  load  A  B  C;  but  the  phase  angle  between  voltage  and  current 
is  charged  30°  in  the  lagging  direction  on  transformer  A,  and  in 
the  leading  direction  on  transformer  B.  For  power-factor  of  the 
secondary  loads  A,  B  and  C  varying  from  100  per  cent,  to  0  per 
cent,,  the  power-factor  of  the  equivalent  load  on  transformer  A 
will  vary  from  y/s  leading  to  1/2  lagging;  while  on  transformer^ 
it  will  vary  from  \/2  lagging  to  a  negative  1/2. 
Where  (a)  is  for  equal  loads  on  each  phase  and  equal  power- 
factors. 
(6)   Equal  loads  and  non-inductive. 

13 


194 


STATIONARY  TRANSFORMERS 


(c)  Equal  loads  (loads  A  and  B  non-inductive)  and  C  50 
per  cent,  power-factor. 

(d)  Equal  loads  (loads  A  and  B  non-inductive)  C  10  per 
cent,  power-factor. 

A  tendency  with  lagging  power-factor  in  load  C  is  to  increase 
the  equivalent  load  on  the  transformer  A  which  is  connected  to 
the  leading  phase,  and  to  diminish  the  equivalent  load  on  trans- 
former B  which  is  connected  in  the  lagging  phase.  Low  power- 
factor  on  both  A  and  B  combined  with  high  power-factor  in  C 
produces  similar  results. 

There  are  a  number  of  different  ways  of  connecting  two  or 


Fig.  147. — Varying  phase  relations  due  to  varying  loads  and  power  factors 
through  the  series  transformers. 

more  series  transformers  to  a  polyphase  system.  One  or  more 
may  be  used  in  connection  with  alternating-current  relays  for 
operating  circuits  for  overload,  reverse  power,  reverse  phase, 
and  low  voltage.  Some  of  the  connections  for  this  purpose  are 
shown  in  Figs.  148  to  149. 

One  series  transformer  is  sufficient  for  opening  the  circuit  of 
a  single-phase  system,  and  at  the  same  time  is  used  in  connection 
with  an  ammeter  and  wattmeter  as  shown  in  Fig.  148.  For  three- 
phase  working,  one,  two  or  three  series  transformers  may  be 
used  for  relays,  ammeters  and  wattmeters.  It  is  often  recom- 
mended that  three  series  transformers  should  be  used  for  three- 


SERIES  TRANSFORMERS 


195 


phase  systems,  but  in  the  majority  of  cases  two  are  sufficient 
to  give  satisfactory  results.     In  Fig.  149  one  is  shown  connected 


-100- 


vP9.OQ.00U 


Wm 


-10000-*^ 


Fia.  148. — Simple  series  transformer  connection. 


c 


KSismsuu-^ — ^itsumsu 


QOQCQQ_>- 


Fig.  149. — Method  of  connecting  a  series  transformer,  ammeter,  and  relay 
on  a  delta  connected  three-phase  system. 

to  one  leg  of  a  three-phase  delta  system.     Its  secondary  circuit 
is  connected  through  a  relay  and  an  ammeter. 


196 


STATIONARY  TRANSFORMERS 


In  connection  with  overload  relays  one  series  transformer 
may  be  used  for  operating  a  three-phase  system,  and  when 
operating  three-phase  wattmeters,  two  are  all  that  is  'required. 
The  connection  shown  in  Fig.  150  will  be  found  to  give  good 
results,  as  each  transformer  has  its  own  tripping  arrangement. 

Three  transformers  are  quite  common  operating  together  on  a 
three-phase,  star-connected  system,  neutral  point  grounded  or 
ungrounded. 

If  all  the  secondary  windings  are  not  arranged  in  the  same 
direction  the  phase  relations  between  one  outside  wire  and  the 


-400- 


UlAAflJLr 


iL 


-400- 


Lr-rrH- 


J 


a 


-400- 


nnnnnn 


•eooo- 


-6000- 


6000- 


FiG.  150. — Method  of  connecting  two  series  transformers  and  relays  to  a 
three-phase  system. 


middle  wire,  and  the  middle  and  the  other  outside  wire  will  be 
60  degrees  instead  of  120  degrees.  In  order  to  obtain  a  phase 
relation  of  120  degrees  between  each  winding,  one  of  the  second- 
ary windings  must  be  reversed. 

Fig.  151  represents  three  series  transformers  with  all  the 
secondary  windings  connected  in  one  direction.  It  makes  no 
difference  whether  the  method  of  connection  be  delta  or  star,  it 
becomes  necessary  to  reverse  one  transformer  with  respect  to 
the  others  when  120  or  60  degrees  displacement  is  required. 

A  connection  very  much  used  where  one  relay  is  required, 
is  shown  in  Fig.   152,  in  which  the  series  transformers  have 


SERIES  TRANSFORMERS 


197 


-10)0- 


-1000 s> 


* ^1000 > 


w 

00— >j      h*^ioo 


^ 


^ 


w 


< 173 ^ 


h — 100—^ 


-* ^173- 


i_«— -i-T— i=F 


-173- 


FiG.  151. — Method  of  connecting  three  series  transformers,  three  ammeters 
and  three  relays  on  a  three-phase  star  connected  system. 


-m- 


-10)0- 


1000 — > 


-577-^ 


.  QOQ06QQ  J     ULMMiJJlJ      UilMMJU 


< 1000- 


r-^wr»-|   j-'Tnnp-|    r-fws^^ 


t 


Fig.  152. — Three-phase  star  arrangement  showing  two  series  transformers 
connected  in  opposition. 


198 


STATIONARY  TRANSFORMERS 


their  opposite  terminals  connected.  The  secondary  phase 
relations  tend  to  operate  in  parallel  so  that  when  a  current 
exists  in  the  primary  of  one  transformer  a  current  will  also  exist 
in  the  secondary  and  relay,  but  will  not  be  great  enough  to  operate 
the  trip  coil.  If  a  short-circuit  should  occur  on  any  one  phase  of 
the  two  outside  wires  A  C,  the  secondary  will  become  over- 
loaded and  its  voltage  will  rise  to  a  value  above  that  of  the 
secondary  of  the  other  transformer;  this  will  tend  to  reverse  the 
current  in  the  latter  transformer,  which  in  turn  will  allow  the 


v<- 


Six  phase 

Fig.  153. — Method  of  connecting  two  series  transformers  with  instruments 
and  relays  to  a  two-  or  three-phase  system  inducing  six-phase  secondary 
currents. 


primary  flux  to  raise  the  voltage  to  the  value  of  the  former 
transformer;  this  voltage  will  cause  the  additional  current  to 
overload  and  operate  the  relay.  This  current  value  will  not  be 
twice  the  current  through  the  two  transformers,  but  will  be  the 
algebraic  sum  of  the  currents  at  120  degrees  apart,  or  \/S  times 
the  current  in  each  leg.  For  example:  If  two  series  trans- 
formers are  wound  for  5  amperes  on  their  secondaries  with  normal 
current  through  their  primaries,  the  algebraic  sum  of  the  two 
'currents  is 

\/3X  5  =  8.66  amperes. 
Fig.  153  shows  a  two-phase  arrangement  of  connecting  two 


SERIES  TRANSFORMERS 


199 


series  transformers  for  working  instruments  and  relays.  It  will 
be  noticed  in  all  the  connections  shown  that  the  secondaries 
of  all  transformers  are  grounded  on  one  side. 

In  Fig.  153  the  system  is  so  arranged  that  two-phase  or  three- 
phase  currents  will  give  a  six-phase  secondary,  depending  upon 
the  connection  made  at  point  x.  The  series  transformer  con- 
nections are  so  arranged  that  the  instruments  will  work  satis- 
factorily with  any  of  the  two  independent  phase  currents. 

The  Y  represents  the  neutral  point  of  the  secondary  power 


Wm 


a 


UflflAJLr' 


C^S 


'-vAfliULr 


r; 


u] 


1L 


-vjjflfl4^ 


1! 


wsom 


ABO 

Fig.  154. — Three-phase  star  arrangement  showing  two  series  transformers, 
two  wattmeters,  and  three  ammeters. 


transformers,  and  may  be  used  as  a  neutral  wire  in  connection 
with  a  direct-current  system  of  supply. 

Another  interesting  connection  is  shown  in  Fig.  154,  in  which 
currents  are  measured  in  the  three  phases  by  the  use  of  two 
series  transformers.  The  geometrical  sum  of  the  currents  in 
the  primaries  where  the  two  series  transformers  are  installed, 
is  measured  by  the  ammeter  shown  connected  to  the  grounded 
side  of  the  transformers.  The  value  obtained  is  that  of  the 
current  through  the  middle  wire. 

The  potential  sides  of  the  two  wattmeters  may  be  connected 
to  the  secondary  leads  of  two-shunt  transformers;  in  the  figure 
they  are  shown  connected  directly  to  the  mains. 


200 


STATIONARY  TRANSFORMERS 


In  general,  single  and  polyphase  combinations  of  series  trans- 
former connections  are  covered  by  the  use  of  one  to  four  trans- 
formers. In  three-phase  work  either  the  star,  delta,  open-delta, 
reversed  open-delta  and   "Z"  connections    might  be  applied. 


tM/'*^'^ 


y'<^^/>/>^'K. 


'^^^^^^i 


>  a 


Fig.  155. — Three  transformer  delta  and  star  connections. 

(See  figs.  155,  156,  157.)  The  connection  shown  in  Fig.  155  is 
not  unlike  the  ordinary  constant  potential  transformer  delta.  In 
this  connection  the.  currents  in  the  secondary  leads  A  and  B 
are  the  same,  but  the  current  through  C  is  V3.  For  relays 
it  is  thought  to  be  much  better  than  the  delta  connection. 


-tUf^ 


W- 


^ 


H^H^ 


^NHk 


VM^»\ 


V-co^ 


Fig.  156 — Two  transformer  "  V"  and  inverted  "  V"  connections. 


It  is  also  possible  to  measure  three-phase  currents  with  two 
series  transforiners  and  only  one  ammeter.  The  arrangement 
is  shown  in  Fig.  158.  To  read  the  current  through  the  trans- 
former on  the  left,  the  two  switches,  a  and  b,  are  closed.     To 


SERIES  TRANSFORMERS 


201 


read  the  current  in  the  middle  line,  h  and  c  are  closed;  the  current 
through  the  transformer  on  the  right  is  measured  by  closing  the 
two  switches,  c  and  d. 

When  measurements  are  not  being  taken  it  is  necessary  that 
the  switches,  a  and  d,  should  be  closed;  as  the  iron  of  the  two 
transformers  is  worked  at  a  high  degree  of  saturation,  which 
produces  an  abnormally  large  secondary  voltage,  giving  rise  to  a 
serious  heating  of  the  transformer. 

Since  series  transformers  are  connected  directly  in  series  with 
the  line,. if  not  properly  installed,  they  will" offer  a  convenient 
path  for  the  escape  of  high  frequency  charges  which  may  occur 
on  the  line,  and  which  in  discharging,  not  only  burn  out  the 
transformer,  but  are  likely  to  form  an  arc  and  probably  cause  a 
fire,  or  loss  of  life. 


■rmWr 


fHHi^ 


fWf^ 


^ 


W^ 


Fig.  157. — Three  transformer  special  connections. 

The  process  of  drying  out  air-insulated  series  transformers  is 
accomplished  by  simply  passing  normal  current  through  the 
winding  until  the  transformer  is  thoroughly  warmed.  This  may 
be  done  by  short-circuiting  the  secondary  through  an  ammeter 
and  sending  enough  alternating  current  through  the  primary  to 
give  normal  current  on  the  secondary,  the  primary  current  being 
obtained  from  a  low  voltage  source.  If  not  convenient  to  obtain 
low  voltage  alternating  current  the  same  result  may  be  accom- 
plished by  passing  normal  direct  current  through  the  primary 
long  enough  to  thoroughly  warm  the  transformer. 

In  case  of  oil-cooled  transformers,  the  winding  should  be  dried 
out  by  this  same  process  before  the  transformer  is  filled  with 
oil.  In  doing  this  the  temperature  of  the  coils  should  not  be 
allowed  to  exceed  65°  C,  which  may  mean  the  use  of  a  current 
much  less  than  normal,  owing  to  the  fact  that  there  is  no  oil 
in  the  transformer. 


202 


STATIONARY  TRANSFORMERS 


All  secondaries  and  casings  of  transformers  should  be  grounded, 
and  likewise  the  instruments  to  which  they  are  connected.  This 
serves  the  double  purpose  of  protecting  the  switchboard  attend-, 
ant  and  freeing  the  instruments  from  the  effects  of  electrostatic 
charges  which  might  otherwise  collect  on  the  cases  and  cause 
errors. 

If  for  any  reason  it  becomes  necessary  to  remove  an  instru- 
ment or  any  current  carrying  device  from  the  secondary  circuit 
of  a  series  transformer,  the  secondary  should  be  short-circuited 


r^rnjr^   r^iy^jr*-!   r-npsv^ 


Fig.  158. — Method  of  connecting  two  series  transformers  and  one  ammeter 
to  a  three-phase  system,  to  measure  the  current  in  any  lead. 


by  a  wire  or  some  other  means.  Series  transformers  should  be 
considered  as  a  part  of  the  line  circuit.  When  it  becomes 
necessary  to  change  secondary  connections,  the  ground  wire 
should  be  inspected  to  see  that  it  is  in  good  condition.  The 
operator  should  also  stand  in  a  dry  board  or  other  insulating 
material. 

By  reason  of  phase  displacement  in  series  transformers,  watt- 
meters, when  used  with  series  transformers,  will  have  certain 
errors  due  to  such  displacement.  The  following  table  applies 
to  certain  types  of  series  transformers,  the  actual  percentage  of 


SERIES  TRANSFORMERS 


203 


error  varying  slightly  in  different  manufacturers  for  the  same 
rating  in  capacity. 

When  a  wattmeter  is  used  in  a  circuit  for  100  per  cent,  power- 
factor,  the  approximate  errors  will  be: 


TABLE  VI 


Transformer 
capacity 
(watts) 

1-5  Watt  load 

or 
1-5  current  load 

1-2  Watt 

or 

current  load 

Full  watt 

or 

current  load 

(a)    2 
(6)  10 
(c)  30 
((f)  30 

-2.0% 
+  0.5% 
+  0.5% 
+  0.5% 

-2.0% 
-0.5% 
-0.5% 
-0.5% 

-2.0% 
-1.5% 
-1.5% 
-1.5% 

The  current  ratios  remain  true  and  cause  no  error  when  used 
with  ammeters  between  the  limits  of  one-tenth  load  and  50  per 
cent,  overload. 

When  potential  transformers  are  used  as  well,  the  tendency 
of  the  two  (series  and  potential  transformers)  is  to  neutralize 
the  error. 

When  a  wattmeter  is  used  in  a  circuit  of  50  per  cent,  power- 
factor,  the  approximate  errors  may  be : 

TABLE  VII 


Transformer 
capacity 

(watts) 

1-2   current 

or 

watt  load 

1-5  current 

or 
watt  load 

Full  current 

or 

watt  load 

Double  cur- 
rent or 
watt  load 

(a)  2 

(b)  10 

(c)  30 
{d)  30 

+  4.0% 
+  4.0% 
+  2.0% 
+  2.0% 

+  12.0% 
+   7.0% 
+   5.0% 
+   5.0% 

+  2.0% 
+  1.5% 

0.0 

0.0 

+  2.0% 
-1.5% 
-0.5% 
-0.5% 

If  the  wattmeter  is  calibrated  with  the  series  transformer  at 
100  per  cent,  power-factor,  the  error  at  50  per  cent,  power-factor 
may  become: 


204 


STATIONARY  TRANSFORMERS 
TABLE  VIII 


Transformer 
capacity 

(watts) 

1-2  current 

or 
watt  load 

1-5  current 

or 
watt  load 

Full  current 

or 

watt  load 

Double  cur- 
rent or 
watt  load 

(a)    2 
(6)  10 
(c)  30 
(d)30 

+  6.0% 

+  4.5% 
+  2.5% 
+  2.5% 

+  14.0% 
+   6.5% 

+   4.5% 
+   4.5% 

+  4.0% 
+  3.0% 
+  1.5% 
+  1.5% 

+  4.0% 

0.0 
+  1.0% 
+  1.0% 

At  power-factors  of  less  than  50  per  cent,  the  errors  will  greatly 
increase. 

It  will  be  seen  that  if  the  wattmeter  is  calibrated  with  the  series 
transformer,  greater  accuracy  may  be  obtained  when  used  in 
a  circuit  of  approximately  the  same  power  factor,  but  that  the 
error  at  a  lower  power-factor  becomes  greater. 

The  plus  sign  ( +  )  means  that  the  wattmeter  will  indicate  more 
than  the  true  power  by  the  percentage  shown.  The  minus  sign 
( — )  means  that  the  wattmeter  will  indicate  error  in  the  opposite 
direction. 

Excepting  (d)  which  indicates  a  wound  primary  type  trans- 
former, (a),  (h)  and  (c)  are  for  transformers  of  the  open  type 
intended  to  slip  over  bus-bar  or  switch-stud  as  well  as  the  wound 
primary  type  transformer  (5  amp.  secondary). 

It  is  sometimes  desired  to  use  for  meter  test  and  other  puiposes, 
inverted  series  transformers;  that  is,  "step-up  current  trans- 
former." Fig.  159  shows  an  arrangement  using  two  series  trans- 
formers of  any  desired  ratio  but  equal;  No.  2  transformer  is 
inverted,  and,  depending  on  the  ratio  of  transformation,  may  be 
employed  to  step  up  the  current  to  any  desired  value.  Assum- 
ing that  both  transformers  are  for  40  to  1  ratio  (200-5  amp.),  it  is 
evident,  from  the  diagram  that  the  standard  testing  instrument 
in  No.  1  transformer  circuit  has  a  5-ampere  current  coil  and  the 
service  meter  200  amperes  in  its  current  coil  when  a  5-ampere 
load  is  flowing  through  the  circuit  load  b. 

For  some  time  past,  the  series  transformer  has  been  used  for 
low-voltage  scries  street  lighting  in  connection  with  series  arc 
lighting  systems. 

For  the  purpose  of  lighting,  its  primary  winding  is  connected 

Tables  VI,  VII  and  VIII  are  representative  of  a  certain  type  of  series 
transformer  and  should  therefore  not  be  considered  general. 


SERIES  TRANSFORMERS 


205 


in  series  with  the  series  arc  lighting  system,  so  that  under  all 
conditions  of  load  on  the  secondary  the  primary  winding  carries 
the  full  current  of  the  arc  circuit  (see  Chapter  XI)  which  is  main- 
tained at  its  normal  value  by  the  constant  current  transformer. 
Its  connections  are  shown  in  Fig.  160. 

For  satisfactory  operation  of  the  series  incandescent  lamp,  it 
is  desirable  to  obtain  as  near  constant  current  as  possible  in  the 
secondary  winding.  Of  course,  to  obtain  constant-current  regu- 
lation under  abnormal  conditions  of  load  is  impossible,  but  it 
has  been  found  in  practice  that  with  open  circuit  voltage  on  the 
secondary  not  exceeding  150  per  cent,  of  the  full-load  voltage,  and 
the  current  at  100-75  and  50  per  cent,  load  not  varying  more  than 
2  per  cent.,  the  regulation  of  the  transformer  and  lamps  on  the 
secondary  is  satisfactory. 


.standard  W, 


<  «~_l  In  verterf 


To  Load 

Fig.  159.  Fig. 

Fig.  159. — Series  transformer  used  to  step-up  current,  as  for  instance, 
with  a  primary  load  of  5-40  volt  lamps,  700  amperes  are  obtained. 

Fig.  160. — Method  of  using  series  transformer  or  series  arc  lighting  cir- 
cuits for  low-voltage  series  incandescent  lighting. 

Certain  classes  of  lighting  require  lower  potential  than  that 
obtained  from  series  arc  circuits,  and  to  provide  for  this,  light 
and  power  companies  are  often  compelled  to  run  multiple  cir- 
cuits from  the  central  station  or  substation  at  a  considerable 
expense.  By  using  a  series  transformer  on  the  series  arc  lighting 
circuit,  a  low-voltage  circuit  may  be  run  when  required,  thus 
obviating  a  large  item  of  expense  and  providing  a  very  flexible 
system  of  distribution. 

The  ratio  of  transformation  of  series  transformers  used  for 
lighting  purposes  has  generally  been  1-1,  bur  there  is  no  diffi- 
culty in  winding  either  primary  or  secondary  for  any  reasonable 
current.  ' 


206  STATIONARY  TRANSFORMERS 

The  core  of  this  transformer  is  of  the  shell  type,  built  up  of 
circular  punchings  with  two  symmetrical  pieces  in  each  layer. 
On  the  center  leg  or  tognue  of  the  core  are  assembled  the  form- 
wound  coils.  The  primary  coil  fits  simply  over  the  secondarp  coil, 
but  is  so  insulated  that  it  will  withstand  a  break-down  test  of 
20,000  volts  to  the  secondary  coil  and  also  to  the  core.  Its 
appearance  is  not  unlike  the  well-known  telephone  line  insulating 
transformer  which  is  used  in  connection  with  long-distance 
high-voltage  transmission  work. 

In  this  series  transformer  there  exists  a  drooping  voltage  char- 
acteristic in  the  secondary.  Its  purpose  is  to  limit  the  open- 
circuit  voltage  on  the  secondary.  It  has  been  obtained  by  so 
proportioning  the  magnetic  circuit  that  the  section  is  contracted 
in  several  parts  to  permit  saturation  of  the  iron  with  no  current 
in  the  secondary  winding. 

There  exist  quite  a  number  of  meter  connections  which  may  be 
used  on  power  transformer  systems.  Some  of  these  are  given 
below:  series  and  potential  transformers  being  used  in  each  case. 

Fig.  161(A)  shows  the  simplest  three-wire  three-phase  meter 
arrangement,  in  which  a  single-phase  wattmeter  has  its  potential 
coil  connected  to  the  secondary  of  a  potential  transformer,  and  its 
current  coil  to  the  secondary  of  a  series  transformer.  If  the 
power  transform  should  have  an  accessible  neutral  point,  at  the 
location  x,  the  potential  transformer  may  be  connected  according 
to  the  dotted  line. 

Fig.  161(B)  shows  the  next  simplest  three-wire  three-phase 
wattmeter  arrangement,  in  which  two  single-phase  wattmeters 
are  involved.  This  method  of  measuring  electrical  energy  in 
three-phase  circuits  for  any  condition  of  unbalanced  voltage  or 
current  is  the  correct  one. 

Fig  161(C)  connection  is  for  a  three-wire  three-phase  system. 
The  wattmeter  has  its  current  coil  connected  to  one  phase  through 
a  series  transformer  (c.  t.),  and  its  potential  coil  to  a  "Y"  impe- 
dance, each  branch  of  which  has  equal  reactance  and  resistance 
such  as  to  give  the  proper  voltage  to  the  potential  coil  of  the 
meter. 

Fig  161(D)  connection  is  not  unlike  (B).  The  polyphase  or 
two-element  wattmeter  is.  employed  here,  and  should  always  be 
used  in  preference  to  two  single-phase  meters.  It  has  a  slightly 
better  accuracy  if  we  consider  that  the  record  of  the  meter  as  a 
whole  is  obtained  without  the  possibility  of  error  that  comes  from 


SERIES  TRANSFORMERS 


207 


P.W.M. 


W.M.1 


W,M 


Fig.  161. — Other   important  uses  for  series  transformers  on  three-phase 

systems. 


208  STATIONARY  TRANSFORMERS 

reading  the  two  single-phase  meters  separately  and  adding  their 
sum  total  together  afterward. 

Fig  1Q1{E)  and  (F)  show  two  arrangements  of  the  three  single- 
phase  wattmeter  method  for  a  three-phase  three-wire  system. 
The  potential  transformers  are  connected  in  star-star.  This 
method  is  not  recommended  because  of  unequal  loading  which 
might  occur  on  the  secondary  side.  With  unbzlanced  load  on  the 
secondary,  the  voltages  might  become  very  unequal,  and  with  an 
accidental  short-circuit  on  one  transformer  its  primary  impedence 
may  be  so  reduced  that  the  remaining  two  transformers  would  be 
subjected  to  almost  \/S  times  their  normal  voltage. 

Fig  161  (GO  shows  a  three- wattmeter  method  in  which  three 
series  transformers,  and  three  potential  transformers  are  used, 
the  latter  being  connected  in  star-delta.  This  method  should 
always  be  used  in  preference  to  methods  (E)  and  (F)  for  the  reason 
the  balanced  voltages  on  the  primary  are  established  by  exchange 
of  current  through  the  secondary  circuits  of  the  three  transformers 
in  case  the  secondary  loads  are  unbalanced.  Abnormal  voltages 
are  prevented  in  the  individual  transformers  and  meters. 

Fig.  1Q1{H)  shows  a  four-wire  three-phase,  three-wattmeter 
method.  The  potential  transformers  are  connected  in  star-star, 
but  the  objection  referred  to  in  (E)  and  (F)  is  practically  elimi- 
nated. The  arrangement  is  the  same  as  three  independent  single- 
phase  systems  with  one  conductor  of  each  phase  combined  into  a 
common  return.  This  method  of  measuring  energy  is  considered 
to  be  superior  to  the  three-wattmeter  method  shown  in  (E),  (F), 
and  (G),  for  the  reason  that  no  inter-connection  of  potential 
transformers  is  required  and  because  the  wattmeters  cannot  be 
subjected  to  variations  of  voltage  greater  than  those  properly 
belonging  to  the  circuit. 

Fig  161(7)  shows  a  four- wire,  three-phase,  polyphase  wattmeter 
method.  This  method  is  preferable  to  method  (H)  and  offers 
greater  simplicity  and  convenience. 


CH.APTER  XIII 

REGULATORS  AND  COMPENSATORS 

Potential  Feeder  Regulators. — Almost  all  regulators  are  of  the 
transformer  type,  with  their  primary  windings  connected  across 
the  lines  and  their  secondary  windings  connected  in  series  with 
the  circuit  the  voltage  of  which  is  to  be  controlled, 

A  type  of  single-phase  feeder  regulator  is  shown  in  Fig.  162. 
It  consists  of  a  laminated  iron  ring  with  four  deep  slots  on  its 
inner  surface,  in  which  the  primary  and  secondary  windings 
are  placed.     The  laminated  core  is  mounted  on  a  spindle  and 


Xi 

> 

0^ 

/ 

\o 

o\ 

^ 

\ 

Fig.  162. — Type  of  single-phase  feeder  regulator. 

so  arranged  that  it  can  be  turned  to  any  desired  position  by 
means  of  a  hand  wheel.  In  the  position  indicated  by  C  C,  the 
core  carries  the  magnetic  flux  due  to  the  primary  winding,  P, 
in  one  direction  through  the  secondary  winding,  S;  and  in  the 
position  indicated  by  C  C"  the  core  carries  the  magnetic  flux 
due  to  the  primary  winding,  P,  in  the  other  direction  through 
the  secondary  winding,  S.  That  is,  when  the  core  is  in  the  posi- 
tion C  C  the  generated  voltage  in  the  secondary  winding  has  its 
14  209 


210 


STATIONARY  TRANSFORMERS 


highest  value.  When  the  core  is  midway  between  C  C  and  C  C 
the  generated  voltage  in  the  secondary  winding  is  zero,  and  the 
feeder  voltage  is  not  affected.  When  the  core  is  in  the  position, 
C  C ,  the  generated  voltage  in  the  secondary  winding  is  again  at 
its  greatest  value,  but  in  such  a  direction  as  to  oppose  the  gener- 
ator voltage. 

On  account  of  the  air-gap  between  the  primary  and  secondary 
windings,  inductive  reactance  is  intro- 
duced in  the  line  which  requires  com- 
pensating. 

The  Stillwell  regulator  is  another 
type  of  transformer  for  raising  and  lower- 
ing the  voltage  of  feeder  circuits.  It 
consists  of  a  primary  winding  which 
is  connected  across  the  feeder  circuit, 
and  a  secondary  winding  in  series  with 
the  circuit  the  voltage  of  which  is  to  be 
varied.  By  means  of  a  switch  arm, 
more  or  less  of  the  secondary  winding 
may  be  introduced  into  the  circuit,  thus 
"boosting"  by  a  corresponding  amount 
the  voltage  of  the  generator.  A  reverse 
switch  is  provided  to  which  the  primary 
winding  is  connected,  so  that  the  volt- 
age may  be  added  by  moving  the  switch  arm  to  the  right,  and 
subtracted  by  moving  the  switch  arm  to  the  left. 

A  regulator  built  along  the  lines  mentioned  above,  with  an 
arrangement  for  connecting  the  various  sections  of  the  secondary 
winding  to  a  dial  switch  and  reversing  switch,  is  shown  in  Fig. 
163.  The  feeder  potential  can  be  controlled  in  the  following 
manner:  Starting  with  the  regulator  in  position  of  maximum 
boost,  that  is,  with  the  dial  switch  turned  to  the  extreme  left  as 
far  as  it  will  go,  a  continuous  right-hand  movement  of  the  dial 
switch  for  two  complete  revolutions  is  obtained.  During  the 
first  revolution  the  switch  cut  outs,  step  by  step,  the  ten  sections 
of  the  secondary  winding.  When  the  first  revolution  has  been 
completed,  the  voltage  on  the  feeder  is  the  same  as  that  of  the 
generator,  no  secondary  winding  being  included.  A  further 
movement  of  the  switch  in  the  same  direction  automatically 
throws  a  reversing  switch;  and  continuing  the  movement  of  the 
dial  switch,  still  in  the  same  direction,  the  secondary  windings 


Fig. 


163.— Type  of  Still- 
well  regulator. 


REGULATORS  AND  COMPENSATORS 


211 


are  again  switched  in,  step  by  step,  this  time  with  reversed 
polarity;  so  that  when  the  second  revolution  is  complete  the 
whole  secondary  winding  is  again  included  in  the  feeder,  but 
now  opposing  the  voltage  of  the  generator.  Thus  by  one  com- 
plete movement  of  the  switch,  covering  two  revolutions  in  one 
direction  the  complete  range  between  the  maximum  boost  and 
maximum  depression  of  the  feeder  voltage  is  covered. 

In  incandescent  lighting  service  a  potential  regulator  is 
particularly  valuable.  Within  the  ordinary  limits  of  commercial 
practice  the  candle-power  of  an  incandescent  lamp  will  vary 
approximately  5  per  cent,  for  every  1  per  cent,  variation  in  the 


>^immmm^ 


-1000- 


knfmm\ 


-400- 


'■nsmmmm^ 


-1400- 


-1000- 


I -"00-*^ 


-600- 


Fig.  164. — Type  of  regulator  used  with  series  incandescent  systems. 


voltage  at  the  terminals.  That  is  to  say,  if  a  16-c-p.  100-volt 
lamp  be  burned  at  106  volts  it  will  give  about  21  c-p.,  or  at  94 
volts  about  11  c-p.  This  fact  shows  at  once  the  urgent  necessity 
for  keeping  the  voltage  of  an  incandescent  system  adjusted 
within  inperceptible  degrees.  A  method  that  has  given  somewhat 
satisfactory  service  with  series  incandescent  systems  is  shown  in 
Fig.  164.  It  consists  in  a  primary  winding  which  is  connected 
across  the  main  lines.  Attached  to  one  end  of  the  primary 
winding  is  a  secondary  winding.  The  secondary  voltage,  1,  3, 
is  greater  than  the  primary,  1,  2,  by  the  voltage  of  the  winding, 
2,  3.  The  voltage,  2,  3,  is  thus  added  to  the  primary  to  form 
the  secondary  voltage  of  the  circuit.  By  reversing  the  connec- 
tions of  the  windings,  2,  3,  it  may  be  made  to  subtract  its 
voltage  from  the  primary,  1,  2,  in  which  case  the  secondary 
voltage,  1,  3,  becomes  less  than  the  initial  primary  voltage;  see 


212  STATIONARY  TRANSFORMERS 

Fig.  165.  Further,  by  bringing  a  number  of  leads  from  parts 
of  the  winding,  2,  8,  the  secondary  voltage,  1,  3,  may  be  in- 
creased or  decreased  step  by  step  as  the  different  leads  of  2,  3, 
are  connected  to  the  secondary  circuit. 

In  Fig.  165  is  shown  the  connections  of  this  form  of  regulator, 
or  compensator.     1,   2,   represents  the  primary  winding   con- 
nected across  the  circuit.     From  a  portion  of  the  secondary 
winding,  3,  4,  taps  are  brought  to  the  contact  blocks  shown  in 
the  diagram.     The  two  arms,  7,  8,  connect  these 
ZZ     contact    blocks   to   two   sliding  contacts,  5,  6. 


1000 


The  arms,  7,  8,  may  be  operated  by  a  handwheel, 
3TW55jn*  one  in  direct  contact  and  the  other  through  a 
^^      gearing,  so    that  a  rotation  of  the  handwheel 

turns  one  arm  clockwise  and  the  other  counter- 
■*     ^^       H     clockwise. 

-pj^  jgg rp  The  secondary  voltage  of  the  circuit  is  that 

of  series  incandes-  ^^  *^®  primary,  increased  or  decreased  by  the 
cent  regulator  voltage  between  the  arms,  7,  8.  In  the  neutral 
that  reduces  the  position,  both  arms  rest  on  one  central  contact 
initial      primary  bi^g]^^  ^nd  the  difference  of  potential  between 

them  is  zero.  In  order  to  decrease  the  voltage 
at  the  lamps,  the  handwheel  is  turned  to  the  right,  and  the  volt- 
age decreased  step  by  step,  until  the  final  position  is  reached 
with  each  arm  on  an  extreme  contact  block.  To  increase  the 
voltage  at  the  lamps,  the  handwheel  is  turned  to  the  left,  the 
two  arms  being  gradually  separated  on  the  contact  blocks; 
and  the  difference  of  potential  between  the  arms  is  effected 
step  by  step  until  in  the  final  position,  each  arm  rests  on  an  ex- 
treme contact,  and  the  secondary  winding  is  connected  into  the 
circuit  and  its  total  voltage  thus  added  to  the  initial  voltage 
of  the  system.  This  type  of  regulator,  as  will  be  seen,  is  in  the 
order  of  an  ordinary  auto-transformer  with  regulating  taps  ar- 
ranged on  its  secondary  winding. 

The  induction  type  regulator  differs  from  the  transformer 
type  in  that  all  the  primary  and  secondary  windings  are  con- 
stantly in  use.  There  are  types  that  vary  the  secondary  voltage 
either  by  moving  part  of  the  iron  core  or  one  of  the  windings, 
or  one  of  the  windings  (primary  or  secondary)  and  part  of  the 
iron  core;  the  whole  or  part  of  the  magnetic  flux  generated  by 
the  primary  threads  the  secondary  according  to  the  position  of 
the  moving  part. 


REGULATORS  AND  COMPENSATORS  213 

This  type  of  regulator  is  either  self-cooled  oil  immersed,  oil- 
immersed  water-cooled,  or  forced  air-cooled  depending  on  the 
capacity. 

Single-phase  regulators  have  only  one  excitation  winding,  the 
magnetizing  flux  is  an  alternating  one  and  its  direction  is  always 
parallel  to  that  diameter  of  the  movable  core  which  passes 
through  the  center  of  the  exciting  coil,  but  its  direction  may  be 
varied  with  respect  to  the  stationary  core,  and,  consequently, 
with  the  respect  to  the  stationary  or  series  winding. 

With  the  armature  in  such  a  relation  to  the  field  that  the 
primary  winding  induces  a  flux  opposed  to  that  induced  by  the 
secondary,  the  voltage  induced  by  the  primary  in  the  secondary 
is  added  directly  to  the  line  voltage,  but  is  subtracted  when  th6 
direction  of  the  flux  is  the  same,  the  complete  range  being 
obtained  by  rotating  the  armature  through  an  angle  of  180 
degrees.  As  the  core  is  rotated  gradually,  the  relative  direction 
of  the  primary  flux,  and,  consequently,  the  amount  forced 
through  the  secondary  coils,  is  similarly  varied  and  produces  a 
gradually  varying  voltage  in  the  secondary  from  the  maximum 
positive,  through  zero,  to  the  maximum  negative  value.  The 
induced  voltage,  is,  however,  added  directly  to,  or  subtracted 
directly  from  the  line  voltage. 

The  primary  or  rotating  core  contains  two  windings;  the  active 
windings  connected  across  the  line,  and  a  second  winding  short- 
circuited  on  itself  and  arranged  at  right  angles  to  the  active 
winding.  The  object  of  this  short-circuited  winding  is  to  de- 
crease the  reactance  of  the  regulator,  and  its  operation  is  as 
follows:  As  the  primary  and  the  short-circuited  windings  are 
both  on  the  movable  core  and  permanently  .fixed  at  right  angles 
to  each  other,  the  flux  generated  by  the  primary  passes  on  either 
side  of  the  short-circuited  coil,  and  is,  therefore,  not  affected  by  it 
in  any  way  whatever;  for  as  long  as  no  flux  passes  through  this 
coil  there  is  no  current  in  it.  This  condition  is,  however,  only 
true  when  the  armature  is  in  the  maximum  boost  or  maximum 
lower  position  with  current  in  the  series  winding,  and  in  any 
position  of  the  armature  with  no  current  in  the  secondary. 

With  the  armature  in  the  neutral  or  no  boost  or  lower  position 
the  flux  generated  by  the  current  in  the  secondary  passes  equally 
on  either  side  of  the  primary  coils,  which  cannot,  therefore, 
neutralize  the  flux  generated  by  the  secondary. 

If  the  primary  core  were  not  provided  ^ith  a  short-circuited 


214  STATIONARY  TRANSFORMERS 

winding,  and  rotated  from  maximum  position  so  as  to  reduce  the 
primary  flux  passing  through  the  secondary,  and  if  the  line 
current  remained  constant,  a  gradually  increasing  voltage  would 
be  required  to  force  the  current  through  the  series  windings, 
and  a  correspondingly  increasing  flux  would  have  to  be  generated. 
This  voltage  would  become  a  maximum  with  the  armature  in 
the  neutral  position,  due  to  the  fact  that  in  this  position  the 
primary  windings  are  at  right  angles  to  the  series  windings  and 
therefore  entirely  out  of  inductive  relation  to  them.  The  current 
in  the  secondary,  therefore,  would  act  as  a  magnetizing  current, 
and  a  considerable  part  of  the  line  voltage  would  have  to  be 
used  to  force  the  current  through  these  coils.  The  voltage  so 
absorbed  would  be  at  right  angles  to  the  line  voltage,  and  the 
result  would  be  a  poor  power  factor  on  the  feeder. 

The  short-circuited  coil  on  the  armature  which  is  in  a  direct 
inductive  relation  to  the  series  coils  when  the  armature  is  in  the 
neutral  position,  acts  as  a  short-circuit  on  the  secondary  winding, 


^-E, 


Fig.  166. — Phase  positions  of  primary  and  secondary  voltages  of  a  single- 
phase  induction  regulator. 

and  thereby  reduces  the  voltage  necessary  to  force  full  load 
current  through  this  winding  to  only  a  trifle  more-  than  that 
represented  by  the  resistance  drop  across  the  secondary  and 
short-circuited  windings.  This  short-circuiting  of  the  secondary 
is  gradual,  from  zero  to  the  maximum  boosting  position  of  the 
regulator  to  the  maximum  short-circuiting  in  the  neutral  position, 
so  that  by  the  combined  effect  of  the  primary  and  short-circuited 
coils  the  reactance  of  the  secondary  is  kept  v/ithin  reasonable 
limits. 

The  operation  of  the  short-circuited  coil  does  not  increase  the 
losses  in  the  regulator,  but  rather  tends  to  keep  them  constant 
for  a  given  secondary  circuit.  In  rotating  the  armature  from 
either  maximum  to  the  neutral  position,  the  current  in  the 
primary  diminishes  as  the  current  in  the  short-circuited  coil 
increases,  so  that  the  total  ampere-turns  of  the  primary  plus 


REGULATORS  AND  COMPENSATORS  215 

the  ampere-turns  of  the  short-circuited  winding  are  always 
approximately  equal  to  the  ampere-turns  of  the  secondary. 

In  Fig.  166  there  is  shown  graphically  the  values  and  time- 
phase  position  of  primary  and  secondary  voltages  of  a  single- 
phase  induction  regulator. 

When  the  mechanical  position  in  electrical  degrees  of  the 
moving  part  is  shifted  to  0  F  on  0  X  following  the  curve  of  the 
semi-circle  in  the  position  of  negative  boost,  or  0  Y'  and  0  X' 
in  the  position  of  positive  boost,  the  secondary  voltage  can  be 
considered  to  have  the  values  0  C  and  0  A  respectively,  and  0  C 
and  0  A'  respectively. 

When  the  mechanical  part  occupies  a  mechanical  position  of 
90  electrical  degrees  from  the  position  0  E  s'  and  0  E  s  the  value 
0  B  oi  the  secondary  voltage  is  zero,  because  the  flux  due  to  the 
primary  exciting  current  passes  through  the  secondary  core 
parallel  to  the  secondary  windings.  The  resultant  voltage  is 
equal  to  the  primary  voltage. 

The  kilowatt  capacity  of  any  regulator  is  equal  to  the  normal 
line  current  to  be  regulated  times  the  maximum  boost  of  the 
regulator,  and  as  the  lower  is  always  equal  to  the  boost,  the 
total  range  is  equal  to  twice  the  kilowatt  capacity  or  100  per 
cent,  with  a  1  to  2  ratio. 

Kilowatt  capacity  of  a  single-phase  regulator  is  maximum 
boost  or  lower  times  the  current,  or  the  maximum  boost  or 
lower  might  be  expressed  in  terms  of  kilowatts  divided  by  the 
secondary  current.  For  a  two-phase  type  it  is  one-half  this 
amount.  In  a  three-phase  type  the  boost  or  lower  across  the 
lines  is  equal  to  the  regulator  capacity  in  kilowatts  multiplied 
by  V  3  and  divided  by  the  secondary  current. 

Regulators  of  the  induction  type  should  not  be  used  for  any 
other  primary  voltage  or  frequency  differing  more  than  10 
per  cent,  from  that  for  which  they  are  designed,  because  an 
increase  in  voltage  or  a  decrease  in  frequency  increases  the 
magnetizing  current  and  the  losses  and  an  increase  in  frequency 
increases  the  impedance.  The  deviation  of  10  per  cent,  allowed 
must  not  occur  in  both  the  frequency  and  the  voltage  unless 
these  deviations  tend  to  neutralize  each  other.  For  instance,  a 
regulator  should  not  be  subjected  to  a  10  per  cent,  increase  in 
voltage  and  the  same  per  cent,  decrease  in  frequency,  but  it 
will  operate  satisfactorily  if  both  voltage  and  frequency  are 
increased  within  the  aEiount  given. 


216 


STATIONARY  TRANSFORMERS 


Induction  regulators  may  be  operated  by  hand,  either  directly 
or  through  a  sprocket  wheel  and  chain;  by  a  hand-controlled 
motor,  or  automatically-controlled  motor.  If  operated  by  hand 
controlled  motor,  the  motor  may  be  of  the  alternating-current 
or  direct-current  type,  but  preferably  of  the  alternating-current 
type  and  polyphase.  If  automatically  controlled,  the  operating 
motor  should  preferably  be  of  the  polyphase  type  as  the  direct- 
current  motor  is  not  very  well  adapted  for  this  purpose.  When 
the  regulator  is  operated  by  a  motor,  the  motor  should  be  con- 
trolled by  a  double-pole  double-throw  switch  mounted  on 
the  switchboard  or  in  any  other  convenient  location.  Closing 
the  switch  one  way  or  the  other  will  start  the  motor  so  as  to 
operate  the  regulator  to  obtain  a  boost  or  lower  in  the  line 
voltage  as  may  be  desired,  and  when  the  correct  line  voltage  is 
obtained  the  regulator  movement  should  be  stopped  by  opening 


_L 


Regulators 


Tt — r 


egruiaiors 


-Eie- 


-E±e- 


Eegixlators 

-E^e 


Fig.  167. — Connections  of  single-phase  regulators  operating  on  a  three-phase 

system. 


the  switch.  Generally  a  limit  switch  is  provided  which  stops 
the  movement  of  the  regulator  by  opening  the  motor  circuit  as 
soon  as  the  regulator  has  reached  either  the  extreme  positions 
depending  on  the  direction  of  rotation,  but  which  automatically 
closes  the  circuit  again  as  soon  as  the  regulator  armature  recedes 
from  the  extreme  positions.  The  operation  of  each  limit  switch 
does  not  interfere  with  the  movement  of  the  regulator  in  the 
direction  opposite  to  which  it  may  be  going. 

When  a  single-phase  regulator  is  used  in  one  phase  of  a  three- 
phase  system,  the  secondary  wiring  is  connected  in  series  with 
the  line  and  the  primary  between  the  lines,  see  Fig.  167.  Under 
these  conditions  there  is  a  difference  in  phase  between  the  current 
in  the  two  windings  and  the  effective  voltage  of  the  secondary 
is  therefore  reduced  from  its  normal  value. 

If  three  single-phase  regulators  are  used,  each  phase  can  be 


REGULATORS  AND  COMPENSATORS  217 

adjusted  to  the  range  equal  to  the  effective  range  of  the  regulator, 
so  that  the  voltage  between  the  phases  is  not  that  due  to  the 
effective  voltage  per  regulator,  but  that  due  to  the  effective  voltage 
of  each  regulator  times  Vo.  In  this  case,  if  10  per  cent,  regu- 
lation across  the  phases  of  a  three-phase  three-wire  system  is 
desired,  only  57.7  per  cent,  of  the  10  per  cent,  regulation  per 
line  is  needed;  thus,  the  boosting  or  lowering  need  not  have  a 
greater  rating  than  3  to  7,5  per  cent,  instead  of  10  per  cent, 
which  is  the  size  necessary  where  one  regulator  is  used. 

In  general  the  capacity  in  kw.  of  a  three-phase  regulator  is  rated  at 
E.I.\/S,  where  E  is  the  volts  boost  or  lower  and  I  the  amperes 
in  feeder  circuit.  For  six-phase  rotary  converter  service,  kw. 
capacity  of  regulator  is:  (double-delta  connection)  =J5J.  7.  3.46 
(29)  and  (diametrical  connection)  =E.  I.  3  (30). 

For  fKjlyphase  circuits  the  system  may  be  regulated  by  intro- 
ducing the  so-called  "induction  regulator."  This  form  of 
regulator  has  a  primary  and  a  secondary  winding.  The  primary 
winding  is  connected  across  the  main  line,  and  the  secondary 
winding  in  series  with  the  circuit.  The  voltage  generated  in 
each  phase  of  the  secondary  winding  is  constant,  but  by  varying 
the  relative  positions  of  the  primary  and  secondary,  the  effect- 
ive voltage  of  any  phase  of  the  secondary  on  its  circuit  is  varied 
from  maximum  boosting  to  zero  and  to  maximum  lowering.  In 
order  to  avoid  the  trouble  of  adjusting  the  voltages  when  each 
phase  is  controlled  independently,  polyphase  regulators  are 
arranged  to  change  the  voltage  in  all  phases  simultaneously 
They  can  be  operated  by  hand  wheels  or  motors.  When  operated 
by  hand,  the  movable  core  is  rotated  by  means  of  a  handwheel 
and  shaft.  When  it  is  desired  to  operate  the  regulator  from  a 
distant  point,  the  apparatus  is  fitted  with  a  small  motor  which 
is  arranged  through  suitable  gearing  to  turn  the  movable  core. 
The  motor  may  be  of  the  direct-current  or  induction  type, 
and  controlled  at  any  convenient  place. 

The  theory  of  this  form  of  regulator  is  described  graphically 
in  Fig.  168  in  which  the  voltage  of  one  phase  of  the  regulator 
is,  eo  =  generator  voltage  or  the  e.m.f.  impressed  on  the  primary: 
ao  =  e.m.f.  generated  in  the  secondary  windings,  and  is  constant 
with  constant  generator  e.m.f. :  6' a' =  secondary  e.m.f.  in  phase 
with  the  generator  e.m.f.  :e'a'  =  line  e.m.f.,  or  resultant  of  the 
generator  e.m.f.  and  the  secondary  e.m.f. 

The  construction  of  the  regulator  is  such  that  the  secondary 


218  STATIONARY  TRANSFORMERS 

voltage,  oa,  is  made  to  assume  any  desired  phase  relation  to 
the  primary  e.m.f.,  as  of,  oh,  oc,  etc. 

When  its  phase  relation  is  as  represented  by  of,  which  is  the 
position  when  the  north  poles  and  the  south  poles  of  the  primary 
and  secondary  windings  are  opposite,  the  secondary  voltage  is  in 
phase  with  the  primary  voltage  and  is  added  directly  to  that  of 
the  generator. 

The  regulator  is  then  said  to  be  in  the  position  of  maximum 
boost,  and  by  rotating  the  armature  with  reference  to  the  fields, 
the  phase  relation  can  be  changed  to  any  extent  between  this  and 
directly  opposed  voltages.  When  the  voltage  of  the  secondary 
is  directly  opposed  to  that  of  the  primary,  its  phase  relation  is  as 


e'  I'      a' 

Fig,  168. — Graphical  representation  of  an  induction  regulator, 

represented  by  o  d  in  the  diagram,  while  o  h  represents  the  shape 
relation  of  the  secondary  when  in  the  neutral  position. 

The  electrical  design  of  the  induction  regulator  is  very  similar 
to  that  of  the  induction  motor.  Its  efficiency  is  somewhat 
higher  than  the  average  induction  motor  of  the  same  rating. 
The  primary  winding  is  placed  on  the  movable  core  and  has  either 
a  closed  delta  or  star  connection,  while  the  secondary  or  stationary 
winding  is  placed  on  the  stationary  core  and  is  an  open  winding, 
each  section  or  phase  being  connected  in  series  with  the  corre- 
sponding phase  of  the  line. 

The  maximum  arc  through  which  the  primary  moves  is  60 
degrees  for  a  six-pole  and  90  degrees  for  a  four-pole.  Induction 
potential  regulators  are  built  for  single-phase,  two-phase,  three- 
phase  and  six-phase  circuits. 

Compensators  are  used  in  connection  with  starting  alternating- 
current  motors,  and  to  some  extent  they  are  used  in  connection 
with  voltmeters  in  the  generating  station. 

Compensators  for  starting  alternating-current  motors  consist 
of  an  inductive  winding  with  taps..    For  polyphase  work  the 


REGULATORS  AND  COMPENSATORS 


219 


compensator  consists  of  one  coil  for  each  phase  ab  c,  Fig.  169 
with  each  coil  placed  on  a  separate  leg  of  a  laminated  iron  core. 
Each  coil  is  provided  with  several  taps,  so  that  a  number  of 
voltages  may  be  obtained,  any  one  of  which  may  be  selected  for 
permanent  connection  to  the  switch  for  starting  the  motor. 

When  the  three-phase  winding  is  used  the  three  coils  are  con- 
nected in  star,  the  line  is  connected  to  the  three  free  ends  of 
the  coils,  and  the  motor  when  starting  is  connected  to  the  taps 
as  represented  in  Fig.  169. 


Motor 

Fig.  169. — Three-phase  motor 

compensator. 


*      I   Motor  ' 
Fig.  170. — Two-phase   induction 
compensator. 


As  it  is  difficult  to  predetermine  the  best  starting  voltages  for 
each  case,  for  motors  rated  at  from  5  to  15  h.p.,  taps  of  40,  60, 
and  80  per  cent,  of  the  line  voltage  are  provided,  according  to 
individual  requirements. 

The  most  essential  part  of  the  compensator  is  an  auto-trans- 
former, the  principle  of  which  has  already  been  explained. 
The  switch  for  operating  the  starting  compensator  is  immersed 
in  oil.  In  starting,  the  switch  moves  from  the  off  position  to 
the  starting  position,  where  the  lowest  voltage  is  applied  to  the 
motor,  or  the  position  where  the  starting  torque  is  the  lowest  that 
can  be  obtained.     As  sopn  as  the  motor  speeds  up,  the  switch  may 


220  STATIONARY  TUANSFORMERS 

be  thrown  over  to  the  running  position;  the  compensator  winding 
is  then  cut  out  and  the  motor  is  connected  to  the  line  through 
suitable  fuses  or  circuit  breakers.  The  switch  is  generally 
provided  with  a  safety  device  which  is  used  to  prevent  the 
operator  from  throwing  the  motor  directly  on  the  line,  thereby 
causing  a  rush  of  current. 

Compensators  are  designed  to  bring  the  motor  up  to  speed 
within  one  minute  after  the  switch  has  been  thrown  into  the 
starting  position.  It  is  important  that  the  switch  be  kept  in 
the  starting  position  until  the  motor  has  finished  accelerating, 
to  prevent  an  unnecessary  rush  of  current  when  the  switch  is 
thrown  to  the  running  position. 

In  two-phase  compensators  the  line  is  connected  to  the  ends 
of  the  two  coils,  and  the  starting  connections  of  the  motor  to 
the  taps  as  shown  in  Fig.  170. 

The  switch  for  operating  the  starting  compensator  and  motor 
is  the  same  as  that  used  on  the  three-phase  service. 

Other  designs  are  used,  one  of  which  operates  the  compensator 
as  follows:  For  starting  the  motor  the  switch  handle  moves 
from  the  off  position  to  the  first  starting  position,  where  a  low 
voltage  is  applied  to  the  motor;  then  to  a  second  starting  position 
where  a  higher  voltage  is  applied;  and  then  to  the  running 
position,  where  the  motor  is  connected  directly  across  the  line, 
the  compensator  being  disconnected  from  the  circuit.  For 
stopping,  the  switch  handle  is  moved  to  a  notch  still  further 
along  than  the  running  position,  the  movement  of  the  switch 
handle  being  in  the  same  direction  as  in  starting.  In  the  latter 
position  the  switch  handle  is  released  to  that  it  can  be  moved 
back  to  the  off  position  ready  to  start  again. 

The  other  form  of  compensator  used  to  indicate  the  variations 
of  voltage  at  the  point  of  distribution  under  all  conditions  of 
load  without  appreciable  error  between  no-load  and  overload, 
consists  of  three  parts:  a  series  transformer,  a  variable  reactance, 
and  a  variable  resistance.  The  compensator  is  adjusted  to 
allow  for  the  resistance  and  inductive  reactance  of  the  line.  If 
these  are  properly  adjusted,  a  local  circuit  is  obtained  corre- 
sponding exactly  with  the  line  circuit,  and  any  change  in  the  line 
produces  a  corresponding  change  in  the  local  circuit,  causing  the 
voltmeter  always  to  indicate  the  potential  at  the  end  of  the  line 
or  center  of  distribution,  according  to  which  is  desired.  It  is 
well  known  that  the  drop  in  a  direct-current  circuit  is  dependent 


REGULATORS  AND  COMPENSATORS 


221 


upon  the  resistance,  but  in  an  alternating-current  circuit  it  is 
due  not  only  to  the  resistance  of  the  lines,  but  also  to  the  react- 
ance. The  reactance  usually  causes  the  drop  to  be  greater  than 
it  would  if  the  resistance  were  the  only  factor.  Therefore,  it  is 
necessary  that  a  compensator  should  give  accurately  the  voltage 
at  the  load  at  all  times,  whatever  may  be  the  current  and 
power-factor. 


Fig.  171. — ^Form  of  compensator  used  to  indicate  the  variation  of  voltage  at 
the  point  of  distribution  under  all  conditions  of  load. 

Fig.  171  shows  a  series  transformer  in  series  with  the  line;  and 
having,  therefore,  in  its  secondary  circuit  a  current  always  propor- 
tional to  the  current  in  the  line.  The  reactors  and  resistors  are 
both  so  wound  that  any  proportion  of  the  winding  can  be  cut  in 
or  out  of  the  voltmeter  circuit,  so  modifying  the  reading  of  the 
station  voltmeter  that  it  corresponds  with  the  actual  voltage  at 
the  point  of  consumption,  regardless  of  the  current,  power- 
factor,  reactance,  and  resistance  in  the  line.  For  balanced  two- 
and  three-phase  circuits  one  compensator  is  sufficient. 

In  adjusting  this  type  of  compensator,  it  is  advisable  to 
calculate  the  ohmic  drop  for  full-load  and  set  the  resistance 
arm  at  the  point  which  will  give  the  required  compensation  and 
then  adjust  the  reactance  arm  until  the  voltmeter  reading 
corresponds  to  the  voltage  at  the  point  or  receiving  station 
selected  for  normal  voltage.  This  compensator  is  commonly 
called  the  "  Line-drop  compensator. " 


222 


STATIONARY  TRANSFORMERS 


Its  connections  proper,  as  used  in  practice  at  the  present  time 
are  shown  in  Fig.  172,  Each  line  of  which  the  voltage  at  the 
center  of  distribution  is  to  be  indicated  or  recorded  in  the  station, 
must  be  provided  with  a  voltmeter  as  shown  in  Fig.  172,  No.  1, 
which  must  be  adjusted  for  the  ohmic  and  reactive  drop  of 
each  line  respectively.  For  example,  take  such  a  line  giving 
the  factors  shown  in  Fig.  173;  where  R  is  ohmic' resistance  of 
10,  Xs  is  the  reactance  of  10  ohms,  and  E  is  the  load  voltage. 
To  fulfil  the  conditions  of  E  =  100,  it  is  necessary  that  the  voltage 
of  supply  or  generator  voltage  be  increased  to  nearly  110.5, 
and  the  voltmeter  No.  2  of  Fig.  160  will  indicate  this  value. 
With  unity  power  factor  it  will  be  noted  that  the  total  live 
drop  is  due  almost  entirely  to  the  line  resistance  R,  and  is  prac- 
tically independent  of  the  line  reactance. 


Current 
Transformer 


j;  fji    Line  Drop 
— — ■  Compensator 

Fig.  172. — Connections  for  live-drop  compensator. 

As  the  power  factor  of  the  line  decreases,  the  effective  voltage 
produced  by  the  reactance  increases,  until  at  an  imaginary  zero 
-power-factor  load  the  total  drop  is  due  almost  entirely  to  the 
reactance. 

The  voltage  diagram  of  such  a  circuit  is  shown  in  Fig.  174, 
where  R  and  Xs  and  E  are  as  before,  but  the  line  has  an  80  per 
cent,  power-factor  load.  The  vector  line  Eg  in  this  case  represents 
114  which  gives  £'  =  100.  For  the  above  or  any  other  live 
conditions  for  which  the  compensator  is  set  it  is  correct  for  all 
loads;  for,  as  the  drop  m  voltage  in  the  line  decreases,  due  to 
decreasing  load,  the  voltage  drop  in  the  compensator  decreases 
in  equal  measure.  For  other  power  factors  a  simple  adjust- 
ment will  be  incorrect. 

Automatic    regulation    of   single-phase    feeders    presents    no 


REGULATORS  AND  COMPENSATORS 


223 


diflficulties,  in  that  there  is  but  one  definite  point  to  regulate 
and  the  "boost"  or  "lower"  of  the  regulator  is  directly  added 
to  or  subtracted  from  the  voltage  of  the  feeder.  If  regulation 
at  the  station  is  desired,  only  a  potential  transformer  is  necessary 
— if  regulation  for  compensation  of  drop  at  some  distant  point 
is  desired,  a  series  transformer  connected  in  series  with  the 
feeder  is  added. 


E  =10 


JP— 100 


It  very  often  happens  that  one  phase  of  a  three-phase  feeder 
is  used  for  lighting  and  a  single-phase  regulator  installed.  In 
making  such  an  installation,  the  regulator  must  have  its  seconday 
winding  in  series  with  the  line,  its  primary  being  connected  across 
the  phase.  Now,  if  the  load  on  this  feeder  is  purely  lighting, 
the  power  factor  would  remain  constant  and  approximately 
100  per  cent.,  but  should  the  power  factor  vary  considerably, 


Eg^lU 


'\oi_^^ 


•^  Constants 


Fig.  174. 


it- may  cause  the  current  to  be  out  of  phase  with  the  voltage  to 
such  an  extent  that  satisfactory  compensation  may  not  be  ob- 
tained. For  such  service  the  best  arrangement  would  be  to 
use  two  cross-connected  series  transformers,  one  connected  in 
series  with  each  conductor  as,  for  instance,  A  and  B  of  the  phase 
across  which  the  primary  of  the  regulator  is  excited.  With 
this  connection  (see  Fig.  175)  the  line  drop  compensator  is 
set  to  compensate  for  ohmic  and  inductive  drop  to  the  load 
center  and  the  voltage  will  automatically  be  maintained  at  the 
desired  value  irrespective  of  changes  in  load  or  power  factor. 


224 


ST  A  TIONAR  Y  TRANSFORMERS 


Hand    regulation    has    long    been    replaced    with    automatic 
regulators.     With  the  development  of  the  automatic  regulator 


D.T. 


Fig.  175. — Single-phase  regulator  and  voltage-drop  compensator  connections 
to  a  three-phase  system. 


Regulator 


'1^ 


C.T. 


Regulators 


-o       o 


C.V 
9       <? 


T=f 


y  Y  y 

Fig.  176. — Two  single-phase  regulators  on  three-phase  system,  showing  the 
use  of  the  contact  making  voltmeter. 

there   has  followed   a   perfection  of  the   contact-making  volt- 
meter, which  displaces  the  operator  and  regulates  the  voltage 


REGULATORS  AND  COMPENSATORS  225 

automatically.  This  instrument  is  composed  of  a  solenoid 
with  two  windings;  a  shunt  winding  which  is  connected  in 
parallel  with  the  secondary  of  a  potential  transformer,  and  a 
series  winding  (differential  with  respect  to  the  shunt  winding) 
which  is  connected  in  series  with  the  secondary  of  the  series 
transformer,  the  primary  of  which  is  in  series  with  the  feeder 
circuit.  A  movable  core  passes  through  the  center  of  the 
solenoid,  and  to  the  top  of  this  core  is  attached  a  pivoted  lever. 
The  lever  carries  at  its  other  end  a  set  of  contacts  which  make 
contact  with  an  upper  and  a  lower  stationary  contact.  The 
lever  is  set  by  means  of  a  spring  acting  against  the  core,  so  that 
its  contacts  are  midway  between  the  upper  and  lower  stationary 
contacts  when  normal  voltage  is  on  the  shunt  coil  of  the  meter. 
The  stationary  contacts  form,  when  closed,  a  circuit  to  one  or 
the  other  of  two  coils  of  a  relay  switch,  which  in  turn  controls 
a  motor  on  the  regulator  cover.  Any  deviation  of  voltage  from 
normal  causes  contact  to  be  made  and  the  regulator  corrects 
for  this  change,  bringing  the  voltage  back  to  normal.  When 
compensating  for  line  drop  to  a  distant  point  the  current  coil 
is  used  and  as  the  load  increases,  the  regulator  boosts  the  voltage 
by  the  proper  amount.  In  this  manner  the  meter  can  be  set 
so  that  constant  voltage  can  be  maintained  at  a  great  distance 
from  the  regulator. 

The  connections  of  this  instrument  for  a  feeder  circuit  where 
lighting  is  connected  on  only  two  phases  of  a  three-phase  system 
and  motors  connected  to  the  same,  are  shown  in  Fig.  1 76.  Two  sin- 
gle-phase regulators  and  three  series  t{||hsf ormers  (one  transformer 
in  each  conductor)  are  necessary.  If  the  series  transformer  in 
the  middle  conductor  or  phase  were  not  installed,  proper  com- 
pensation could  not  be  secured,  owing  to  both  phase  displace- 
ment and  an  unbalancing  of  current  in  the  three  phases. 

Three  single-phase  regulators  are  usually  employed  when 
lighting  and  power  are  taken  from  all  the  three  phases  of  a 
three-phase  system.  One  three-phase  regulator  may  be  used,  in 
which  case  it  is  better  to  employ  only  two  series  transformers 
cross-connected,  so  as  to  get  an  average  of  unbalanced  current. 
With  single-phase  regulators  as  shown  in  Fig.  177  each  phase  can 
be  adjusted  independently  of  the  others  and  constant  voltage 
established  at  the  load  center  of  each.  For  this  reason  it  is  better 
to  use  three  single-phase  regulators  in  preference  to  one  three- 
phase  regulator. 

15 


226 


ST  A  TIONAR  Y  TRANSFORMERS 


For  three-phase  four-wire  systems,  three  single-phase  regula- 
tors are  employed  having  their  secondaries  connected  in  series 
with  a  phase  conductor  and  their  primaries  excited  from  phase 
conductors  to  neutral.  This  method  is  equivalent  to  three 
independent  single-phase  circuits. 


if 


y         y 

Fig.  177. — An  installation  giving  perfect  regulation  when  properly  installed 

and  operated. 


% 


CHAPTER  XIV 

TRANSFORMER  TESTING  IN  PRACTICE 

In  order  to  determine  the  characteristics  of  a  transformer 
the  following  tests  are  made: 

1.  Insulation. 

2.  Temperature. 

3.  Ratio  of  transformation. 

4.  Polarity. 

5.  Iron  or  core  loss. 

6.  Resistances  and  P  R. 

7.  Copper  loss  and  impedance. 

8.  Efficiency. 

9.  Regulation. 

10.  Short-circuit  test. 

Insulation. — The  insulation  of  commercial  transformers  should 
be  given  the  following  tests : 

a.  Normal  voltage  with  overload. 

b.  Double  voltage  for  30  minutes  and  three  times  the  normal 
voltage  for  five  minutes.  (Distribution  2000  to  6000  volt 
transformers  only.) 

c.  Between  primary,  core  and  frame. 

d.  Between  primary  and  secondary. 

e.  Between  the  secondary,  core  and  frame. 

The  National  Board  of  Fire  Underwriters  specify  that  the 
insulation  of  nominal  2100-volt  transformers,  when  heated, 
should  withstand  continuously  for  one  minute  a  difference  of 
potential  of  10,000  volts  alternating  current  between  the  primary 
and  secondary  coils  and  the  core. 

For  testing  the  insulation  of  transformers,  a  high-potential 
testing  set  with  spark-gap  is  required.  The  testing  set  should, 
preferably,  have  low  reactance  so  that  the  variation  in  voltage, 
due  to  leading  and  lagging  currents,  will  not  be  large.  The 
voltages  will  be  practically  in  the  ratio  of  the  turns,  and  the 
high-tension  voltages  may  be  determined  by  measuring  the  low- 
tension  voltages  and  multiplying  by  the  ratio  of  transformation. 

227 


228 


STATIONARY  TRANSFORMERS 


Where  a  suitable  electrostatic  voltmeter  is  available  the  high- 
tension  voltage  is  obtained  by  direct  measurement. 

In  applying  insulation  tests,  it  is  important  that  all  primary 
terminals  should  be  connected  together  as  well  as  all  secondary 
terminals,  in  order  to  secure  a  uniform  potential  strain  throughout 
the  winding.  In  testing  between  the  primary  and  secondary  or 
between  the  primary  and  core  and  frame,  the  secondary  must 
be  connected  to  the  core  and  frame,  and  grounded. 

In  making  the  test,  connect  as  shown  in  Fig.  178.  The  spark- 
gap  should  be  set  to  discharge  at  the  desired  voltage,  which 
may  be  determined  directly  by  means  of  test  with  static  volt- 
meter, or  by  the  spark-gap  table  giving  sparking  distances  in  air 
between  opposed  sharp  needle-points  for  various  effective  sinu- 
soidal voltages  in  inches  and  in  centimeters. 

TABLE  IX.— SPARKING  DISTANCES 

Table  of  Sparking  Distances  in  Air  between  Opposed  Sharp  Needle- 
Points,  for  Various  Effective  Sinusoidal  Voltages,  in  inches  and  in 
centimeters. 


Kilovolts 
(Sq.  root  of 
mean  square) 

Distance 

Kilovolts 
(Sq.  root  of 
mean  square) 

Distance 

Inches 

Cms, 

Inches 

Cms. 

5 

0.225 
0.47 
0.725 
1.0 
1.3 
1.625 
2.0 
2.45 
2.95 
3.55 
4.65 
5.85 
7.1 
8.35 
9.6 
10.75 
11.85 
12.90 

0.57 
1.19 
1.84 
2.54 
3.3 
4.1 
5.1 
6.2 
7.5 
9.0 
11.8 
14.9 
18.0 
21.2 
24.4 
27.3 
30.1 
32.8 

140 

13.95 

15.0 

16.05 

17.10 

18.15 

19.20 

20.25 

21.30 

22.35 

23.40 

24.45 

25.50 

26.50 

27.50 

28.50 

29.50 

30.50 

35  4 

10 

150 

38.1 

15 

160 

40  7 

20 

170 

43.4 

25 

180. 

46  1 

30 

190 

48.8 

35 

200 

51.4 

40 

210 

54  1 

45 

220 

56.8 

50 

230 

59.4 

60....    

240 

62.1 

70 

250 

64.7 

80 

260. 

67.3 

90 

270 

69.8 

100 

280 

72.4 

110 

290 

300 

74.9 

120 

77.4 

130 

TRANSFORMER  TESTING  IN  PRACTICE        229 


Testing  Transformer 


After  every  discharge  the  needle  points  should  be  renewed. 
The  insulation  test  which  should  be  applied  to  the  winding  of  a 
transformer  depends  upon  the  voltage  for  which  the  transformer 
is  designed.  For  instance,  a  2100-volt  primary  should  with- 
stand a  difference  of  potential  of  10,000  volts,  and  a  200-volt 
secondary  should  therefore  be  tested  for  at  least  2000  volts. 
The  length  of  time  of  the  insulation  test,  varies  with  the  magni- 
tude of  the  voltage  applied  to  the  transformer,  which,  if  severe, 
should  not  be  continued  long,  as 
the  strain  may  injure  the  insula- 
tion and  permanently  reduce  its 
strength. 

Transformers  are  sometimes 
tested  by  their  own  voltage.  One 
side  of  the  high-tension  winding 
is  connected  to  the  low-tension 
winding,  and  the  iron,  and  the 
transformer  operated  at  a  voltage 
above  the  normal  to  give  the 
necessary  test  voltage.  The  same 
test  is  repeated  when  the  other 
end  of  the  high-tension  winding  is 
connected  and  the  one  side  dis- 
connected. 

In  making  insulation  tests  great 
care  should  be  taken  to  protect  not  only  the  operator  but  others 
adjacent  to  the  apparatus  under  test.  If  it  is  necessary  to 
handle  the  live  terminals,  only  one  should  be  handled  at  a  time, 
and  whenever  possible,  it  should  be  insulated  beyond  any  possi- 
bility of  the  testing  set  being  grounded. 

Another  insulation  test  called  "over-potential  test"  is  made 
for  the  purpose  of  testing  the  insulation  between  adjacent  turns 
and  also  between  adjacent  layers  of  the  windings.  In  applying 
the  over-potential  test,  the  exciting  current  of  a  transformer  is 
always  increased. 

This  test  usually  consists  of  applying  a  voltage  three  to  four 
times  the  normal  voltage  to  one  of  the  windings  with  the  other 
winding  open-circuited.  If  this  test  is  to  be  made  on  a  2000- 
volt  winding,  at  three  times  its  normal  voltage,  6000  volts  may 
be  applied  to  one  end  of  the  winding  in  question,  or: 


Fig.  178. — Method  of  connecting 
apparatus  for  insulation  test. 


230  STATIONARY  TRANSFORMERS 

3000  volts  to  a  1000-volt  winding, 
1200  volts  to  a    400-volt  winding, 
300  volts  to  a    100-volt  winding. 
In  general,  this  test  should  be  applied  at  high  frequency  so  that 
the  exciting  currents  referred  to  above  may  be  reduced.     The 
higher  the  frequency  the   less  will   be  the  amount  of  current 
required    to  make  the  test.     It  is  recommended  that  60  cycles 
be  the  least  used,  and  for  60-cycle  transformers  133-cycle  cur- 
rents be  applied,  and  for  25-cycle  transformers  60  cycles. 

The  highest  voltage  transformer  built  up  to  the  present  time 
for  power  and  industrial  purposes  was  tested  at  280,000  volts,  or 
double  voltage  for  which  it  was  designed. 

Double  voltage  is  applied  to  test  the  insulation  between  turns 
and  between  sections  of  coils,  these  being  the  cause  of  practically 
85  per  cent,  of  transformer  burnouts.  A  better  and  surer  test 
than  this  would  be  to  apply  twice  the  normal  voltage  for  one 
minute  followed  by  another  test  for  five  minutes  at  one  and  one- 
half  times  normal  voltage.  The  latter  test  is  to  discover  any 
defect  that  may  have  developed  during  the  double-voltage  test, 
and  yet  not  have  become  apparent  in  the  short  time  the  double 
voltage  was  applied. 

The  application  of  a  high  voltage  to  the  insulation  of  a  trans- 
former is  the  only  real  method  of  determining  whether  the 
dielectric  strength  is  there.  Mechanical  examination  of  the  keen- 
est kind  is  false,  and  measurement  of  insulation  resistance  is  not 
very  much  better;  since  insulation  may  or  may  not  show  resist- 
ance when  measured  by  a  voltmeter  with  low  voltage,  but  offer 
comparatively  little  resistance  to  a  high-voltage  current. 

In  working  the  high-voltage  test  between  the  primary  and  the 
core  or  the  secondary,  the  secondary  should  always  be  grounded 
for  the  reason  that  a  high  voltage  strain  is  induced  between  the 
core  and  the  other  winding  which  may  be  greater  than  the 
strain  to  which  the  insulation  is  subjected  to  under  normal 
operation,  and,  of  course,  greater  than  it  is  designed  to  stand 
constantly.  When  testing  between  the  primary  or  high-vol- 
tage side  of,  say,  a  high  ratio  transformer,  and  the  core,  the 
induced  voltage  strain  between  the  low-voltage  winding  and 
core  may  be  very  high  and  the  secondary  may  be  broken 
down  by  an  insulation  test  applied  to  the  high-voltage  side 
under  conditions  which  would  not  exist  during  normal  operation 
of  the  transformer.     The  shorter  the  time  the  voltage  is  kept 


TRANSFORMER  TESTING  IN  PRACTICE        231 

on,  with  correspondingly  higher  voltage  to  get  the  desired 
severity  of  test,  the  less  will  be  the  deterioration  of  the  insu- 
lation. Every  transformer  should  be  tested  with  at  least 
twice  its  rated  voltage,  the  reason  for  this  being  necessary  is 
because  of  the  many  abnormal  conditions  of  operation  which 
occur.  On  a  very  high  voltage  system,  if  one  side  of  the  winding 
becomes  grounded,  the  whole  rated  voltage  is  exerted  between 
the  winding  and  the  iron  core;  and  sometimes  during  normal 
operation  (so  far  as  exterior  observtion  indicates)  a  difference  of 
potential  will  occur,  lasting  but  a  small  fraction  of  a  second  or 
minute,  which  might  be  as  high  as  the  testing  voltage  required. 

Practically  all  high-voltage  transformers  are  wound  with  copper 
strip  or  ribbon,  one  turn  per  layer,  the  coils  being  insulated 
uniformly  throughout  excepting  the  end  turns  which  are  some- 
times insulated  to  withstand  voltages  of  5000  volts  between 
turns.  Take  the  case  of  a  transformer  with  a  normal  voltage 
between  turns  of  80  volts,  it  would  mean  that  in  applying  the 
standard  voltage  test,  i.e.,  twice  the  rated  high-tension  voltage 
between  the  high-voltage  winding  and  low-voltage  winding 
connecting  the  latter  to  the  core  we  shall  receive  220,000  volts 
across  a  110,000-volt  winding,  or  an  induced  voltage  of  160  volts 
between  turns. 

Several  years  ago  it  was  agreed  to  lower  the  standard  high- 
voltage  test  specifications  to  1.5  times  the  rated  voltage,  and  all 
sorts  of  breakdowns  happened  until  a  change  was  made  to  the 
higher  test.  The  double  voltage  test  is  not  too  high  and  not  too 
severe  a  test  no  matter  how  high  the  rated  voltage  of  the  trans- 
former might  be  for  power  and  industrial  purposes.  For  com- 
mercial testing  transformers  it  will  not  apply.  Such  a  trans- 
former was  recently  made  for  400,000  volts  and  before  it  was 
shipped  from  the  factory  it  was  given  a  full  half-hour  test  at 
650,000  volts  with  the  center  of  the  high-voltage  winding  grounded. 
Since  then  one  has  been  made  for  750,000  volts.  About  the 
highest  test  made  so  far,  on  commercial  power  transformers 
was  that  of  a  14,000  kv-a  100,000  volt  transformer  which  was 
given  270,000  volts  across  its  high-voltage  winding  to  all  other 
parts.  This  transformer  was  for  a  60-cycle  system  and  covered 
a  floor  space  of  23  ft.  X 8.5  ft,,  it  being  18  ft.  high.  Another 
transformer  of  10,000  kv-a  at  70,000  volts  operating  on  a  25-cycle 
system  was  give  a  high-voltage  test  of  180,000  volts.  The 
former  transformer  was  fitted  with  oil-filled  terminal  bushings 


232  STATIONARY  TRANSFORMERS 

and  during  the  test  of  these  bushings  at  270,000  volts,  no  corona 
was  visible  even  when  in  utter  darkness.  The  latter  trans- 
former was  fitted  with  the  condenser  type  of  terminal  bushings 
which  is  made  up  of  alternate  layers  of  insulating  and  conducting 
material. 

In  the  operation  of  transformers  it  has  been  found  that  we  are 
confronted  with  the  difficult  problem  of  taking  care  of  the  voltage 
rise  between  turns  that  may  not  increase  the  line  voltage  suf- 
ficient to  be  noticeable  but  be  so  high  in  the  transformer  itself 
and  only  effective  across  a  few  turns  as  to  short-circuit  and 
burn-out  that  part  where  the  excessive  voltage  is  concentrated. 
In  fact  it  is  quite  possible  to  get  100  times  normal  voltage  across 
a  small  percentage  of  the  total  turns  and  at  the  same  time  have 
no  appreciable  increase  in  voltage  at  the  terminals  of  the 
tra,nsformer. 

With  or  without  extra  insulation  on  the  end  turns  of  trans- 
formers operating  on  high-voltage  systems,  the  voltage  difference 
on  the  end  turns  due  to  switching,  etc.,  is  there,  and  the  only 
way  out  of  the  difficulty  is  to  provide  sufficient  insulation  to 
make  it  safe  irrespective  of  the  external  choke  coils  which  are 
always  provided. 

This  double  voltage  test  is  made  after  the  transformer  has 
been  thoroughly  dried  out  and  the  quality  of  oil  brought  up  to 
standard.  In  the  past  some  makers  placed  too  much  reliance  on 
oil  as  an  insulator  and  consequently  left  out  much  solid  insula- 
tion; the  result  was  that  many  burnouts  occurred,  because  the 
oil  could  not  be  relied  upon  always,  its  insulating  proportions 
decreasing  with  age.  In  many  cases  burnouts  occurred  immedi- 
ately the  transformers  were  put  into  service  after  the  drying-out 
process  had  been  completed,  and  the  voltage  slowly  brought  up 
to  the  desired  value. 

Temperature. — The  temperature  or  heat  test  of  a  transformer 
may  be  applied  in  several  ways,  all  of  which'  are  arranged  to 
determine  as  nearly  as  possible  the  working  temperature  condi- 
tions of  the  transformer  in  actual  service. 

Before  starting  a  temperature  test,  transformers  should  be 
left  in  the  room  a  sufficient  length  of  time  for  them  to  be  affected 
alike  by  the  room  temperature. 

If  a  transformer  has  remained  many  hours  in  a  room  at  con- 
stant temperature  so  that  it  has  reached  approximately  uniform 
temperature  throughout,  the  temperature  of  the  surface  may 


TRANSFORMER  TESTING  IN  PRACTICE        233 

be  taken  to  be  that  of  the  interior,  or  internal  temperature.  If, 
however,  the  transformer  is  radiating  heat  to  the  room,  the 
temperature  of  the  surface  will  be  found  to  give  little  indication 
of  the  temperature  of  the  interior. 

To  ascertain  the  temperature  rise  of  a  transformer,  thermom- 
eters are  sometimes  used,  which  give  only  comparative  results 
in  temperature  and  such  measurements  are,  therefore,  useful  only 
in  ascertaining  an  increase  in  temperature  during  the  heat  run. 
If  thermometers  are  used  they  should  be  screened  from  local  air- 
currents  and  placed  so  that  they  can  be  read  without  being 
removed.  If  it  is  desired  to  obtain  temperature  curves,  ther- 
mometer readings  should  be  taken  at  half-hour  intervals  through- 
out the  test  and  until  the  difference  between  the  room  temper- 
ature and  that  of  the  transformer  under  test  is  constant. 

In  order  to  determine  temperature  rise  by  measurement  of 
resistance,  it  is  necessary  to  determine  first  what  is  called  "cold" 
resistance  by  thermometer  measurements  after  the  trans- 
former has  remained  in  a  room  of  constant  temperature  for  a 
sufficient  length  of  time  to  reach  a  uniform  temperature  through- 
out its  windings. 

The  temperature  rise  by  resistance  gives  the  average  rise 
throughout  the  windings  of  the  transformer,  and  to  obtain 
average  temperature  rise  of  each  of  the  windings,  separate 
resistance  readings  should  be  taken  of  each. 

The  temperature  rise  by  means  of  resistance  may  be  deter- 
mined by  the  use  of  the  following  equation: 

R  =  Ro(l +0.0040;  (31) 

or  by  equation 

Resistance  at  S°C  =  ~^^^~R'  (32) 

where  R'  is  the  resistance  at  any  temperature  t. 
where  R^  is  the  resistance  at  room  temperature;  R  the  resistance 
when  heated,  and  t  the  rise  in  temperature.  The  temperature 
coefficient  of  resistance  is  taken  at  0.004  as  25°  C.  Considering 
the  above  equation,  the  temperature  rise  corrected  to  25°  C.  may 
be  determined  in  the  following  manner. 

Example:  Let  room  temperature  be  20°  C,  and  absolute 
temperature  of  transformer  60°  C.  Ascertain  correct  tem- 
perature rise. 


234 


STATIONARY  TRANSFORMERS 


The  temperature  is  apparently  60  —  20  =  40°  C,  but  since  the 
room  temperature  is  5°  lower  than  the  standard  requirements, 
a  correction  of  0.5X5  =  2.5  per  cent,  must  be  added  giving  a 
corrected  temperature  of 


100X2.5X40 
100 


=  41°  C. 


pic 


Thus  with  a  room  temperature  of  20°  C.  the  rise  in  temperature 
calculated  from  the  above  equation  should  be  added  by  2.5  per 
cent.,  or  with  a  room  temperature  of  35°  C,  the  rise  in  temper- 
ature should  be  decreased  by  5  per  cent.;  and  with  a  room 

temperature  of  15°  C,  the  rise  in 

temperature   should   be    increased 
by  5  per  cent.,  and  so  on. 

If  the  room  temperature  differs 
from  25°  C.  the  observed  rise  in 
temperature  should  be  corrected 
by  0.5  for  each  degree  centigrade. 
This  correction  is  intended  to  com- 
pensate for  the  change  in  the  radia- 
tion constant  as  well  as  for  the 
error  involved  in  the  assumption 
that  the  temperature  coefficient  is 
0.004,  or  more  correctly,  0.0039, 
remains  constant  with  varying 
room  temperatures. 

To  measure  the  increase  of  re- 
sistance let  us  take  the  follow- 
ing example.  The  primary  resis- 
tance of  a  certain  transformer  is 
8  ohms,  and  at  its  maximum  operating  temperature,  9  ohms. 
Temperature  of  room  during  test  is  30°  C.  Ascertain  cor- 
rected temperature  rise. 

The  primary  resistance  taken  at  a  temperature  of  30°  C, 
when  referred  to  temperature  coefficient  of  0.4  per  cent,  per 


2000 

Sinn! 

100- 


Umj!jImJ       UjiMWHL 


m 

-3000- 
-4000- 


"mmmm 


Fig.  179. — Method  of  con- 
necting transformers  and  instru- 
ment for  an  over-potential  test 


For  water-cooled  transformers,  the  standard  temperature  of  reference  for  incoming  cooling 
water  should  be  25°  C,  measured  at  thfe  intake  of  the  transformer.  In  testing  water-cooled 
transformers  it  is  important  to  maintain  the  temperature  of  the  ingoing  water  within  5°  C. 
of  the  surrounding  air,  but  where  this  is  impracticable,  the  reference  ambient  temperature 
should  be  taken  as  that  indicated  by  the  resistance  of  the  windings,  when  the  disconnected 
transformer  is  being  supplied  with  the  normal  amount  of  cooling  water  and  the  temperature  of 
the  windings  has  become  constant. 


TRANSFORMER  TESTING  IN  PRACTICE        235 

degree,  represents  a  rise  of  30X0.4  =  12  per  cent,  above  its  value 
at  zero  centigrade,  which  is 

8X100     ^,,    , 
— 11  o~  =  ♦  •  14  ohms. 

The  maximum  operating  temperature  of  10  ohms  represents 

a  rise  of 

(9-7.14)   100 

if-jT- =  26.05  per  cent. 

above  value  at  zero,  and  is  equal  to 

absolute  temperature. 

Deducting  from  this  the  room  temperature  at  30°,  the  apparent 
rise  =  35°  C.  Since  the  room  temperature  during  test  was  5° 
above  standard  requirements,  a  correction  of  0.5X5,  or  2.5  per 
cent,  must  be  substracted,  giving  a  corrected  rise  of 

35X90 


100 


=  3.15°  C. 


It  is  well  known  that  high  temperatures  cause  deterioration 
in  the  insulation  as  well  as  increase  in  the  core  loss. 

The  average  temperature  rise  of  the  coils  of  transformers  can 
be  more  accurately  determined  from  the  hot  and  cold  resist- 
ances, and  is  calculated  as  follows: 

Temp,  rise  (°C)  =  (238.  l  +  r)(^'>°^R^-l)  (33) 

T  =  temperature  at  which  cold  resistance  is  taken. 

As  already  stated  above,  if  the  final  room  temperature  is  less 
than  25°  C,  the  temperature  rise  should  be  corrected  by  adding 
0.5  of  1  per  cent,  for  each  degree  less;  if  room  temperature  is 
greater  than  25°  C,  subtract  0.5  of  1  per  cent.,  for  each  degree 
greater.  While  these  readings  are  being  taken  the  exciting 
current  and  the  load  current  are  held  constant  and  the  ther- 
mometers are  read  at  30  or  60  minute  intervals  for  a  period 
of  several  hours  and  until  the  constant  temperature  has  been 
reached.     The  thermometers   should   be   placed   in  the   room, 

The  A.  I.  E.  E.  recommend  that  in  the  case  of  resistance  measurements,  the  temperature 
coefficient  of  coMer  siiall  be  deduced  from  the  formula  1/(234.  5-T).    Thus,  at  an  initial  tem- 

Ferature  T  is  4Cr  C.  the  temperature  coefficient  or  increase  in  resistance  per  degree  C.  rise  is 
/(274.5)  b0..00364. 


236 


STATIONARY  TRANSFORMERS    • 


in  the  oil,  on  the  cores,  tank  and  various  other  parts  of  the 
transformer  when  possible, 

A  method  of  heat-run  used  to  some  extent,  and  known  as  the 
^'Opposition"  test,  is  shown  in  Fig.  180.  In  this  test  two  trans- 
formers of  the  same  capacity,  voltage  and  frequency  are  required 
and  connected  as  shown  in  diagram.  The  two  secondary  wind- 
ings are  connected  in  parallel,  and  the  two  primary  windings 
connected  in  series  in  such  a  way  as  to  oppose  each  other.  The 
two  secondary  leads  receive  exciting  current  at  the  proper  voltage 
and  frequency,  while  the  primary  leads  receive  a  current  equal 
to  the  desired  load  current ;  the  wattmeter  in  the  primary  circuit 


PEl«L. 


£F31 


Fig.  180. — Method  of  connecting  apparatus  for  heat  test,  known  as  "oppo- 
sition" test. 


measures  the  total  copper  loss,  and  that  in  the  secondary  the 
total  core  loss. 

Another  method  often  used  and  called  the  "motor  generator 
test"  is  shown  in  Fig.  181.  In  this  test  two  transformers  are 
used,  having  their  high-tension  windings  connected  together. 
Proper  voltage  is  applied  to  the  low-tension  winding  of  one  of  the 
transformers,  and  the  low-tension  winding  of  the  other  trans- 
former is  connected  to  the  same  source.  Then  with  the  switch 
s  open,  the  wattmeter  reads  the  core  losses  of  both  transformers, 
and  with  s  closed,  it  reads  the  total  loss.  Subtracting  the  core 
loss  from  the  total,  the  copper  loss  is  obtained.  This  method 
requires  (as  is  also  the  case  in  the  opposition  test)  that  only  the 
losses  be  supplied  from  the  outside. 


TRANSFORMER  TESTING  IN  PRACTICE        237 

At  the  present  time  the  flow  point  of  the  impregnating  com- 
pounds gives  a  temperature  limit  of  about  90°  C.  It  is  possible 
that  the  development  of  synthetic  gums  will  soon  reach  a  stage 
to  permit  of  actual  operating  temperatures  of  at  least  125°  to 
150°  C.  The  only  difficulty  with  such  an  operating  temperature 
will  be  with  the  oil. 

Certain  practices  of  drying  out  transformers  are  applicable 
to  temperature  tests  (see  Chapter  IX).  In  drying  out  trans- 
formers it  is  always  more  convenient  to  short-circuit  the  low- 
voltage   winding   and   impress   sufficient  voltage   on   the   high- 


FiG.  181. — Another  method  of  connecting  apparatus  for  heat  test  known 
as  "motor  generator"  test. 


voltage  winding  to  cause  about  20  to  30  per  cent,  current  to  flow 
through  the  transformer  coils.  This  current  is  found  quite  suffi- 
cient to  raise  the  temperature  of  the  coils  to  the  desired  limit. 

To  make  normal  current  flow  through  the  windings  when  the 
secondary  is  short-circuited  requires  a  voltage  of  about  3,3  per 
cent,  of  the  high  voltage  winding,  according  to  the  way  the  wind- 
ings are  connected  (series  or  parallel).  For  example:  It  is 
desired  to  dry  out  a  100,000  volt,  10,000  kw.  single-phase  trans- 
former; a  5000  kw.,  a  2500  kw.,  and  a  1250  kw.  of  the  same 
voltage,  etc.  What  will  be  the  voltage  necessary  to  circulate 
20  and  30  per  cent,  of  noiynal  current  through  the  coils  of  the 
transformers?  The  answer  to  this  is  best  given  in  the  following 
table : 


238 


ST  A  TIONA  R  Y  TRA  NSFORMERS 
TABLE  XI 


Conditions  of  test 


Capacity  of  transformers  in  kw. 


10,000 

5000 

2500 

100 

50 

25 

3300 

3300 

3300 

20 

10 

5 

660 

660 

660 

30 

15 

7.5 

990 

990 

990 

1250 


Normal  high-voltage  current  at  100,- 
000  volts  on  full-load. 

Voltage  required  to  circulate  same 
when  low-voltage  winding  is  short- 
circuited. 

At  20  per  cent,  normal  current.  .  .  . 

Voltage  required  for  20  per  cent. . . 

At  30  per  cent,  normal  current 

Voltage  required  for  30  per  cent. .  . 


12.5  amp. 
3300  volts 


2.5  amp. 

660  volts 

3.75  amp. 

990  volts 


If  one  is  obliged  by  circumstances  to  short-circuit  the  high- 
voltage  winding,  the  same  per  cent,  voltage  holds  good.  As- 
suming the  low  voltage  to  be  5000  volts,  it  will  require  33  volts 
for  20  per  cent,  normal  current,  and  50  volts  for  30  per  cent, 
normal  current.  With  the  high-voltage  winding  connected  for 
50,000  volts,  the  current  values  given  above  will  be  doubled  but 
the  temperature  conditions  will  remain  about  the  same. 

The  maximum  values  of  temperature  for  large  transformers  is 
a  rise  of  40°  C.  under  rated  load,  this  value  having  for  its  basis  a 
room  temperature  of  25°  C,  For  rated  overloads  the  limiting 
temperature  rise  is  55°  C.  In  an  earlier  part  it  has  been  stated 
that,  in  general,  it  is  found  that  transformers  will  operate  quite 
,satisfactorily  when  worked  at  their  limiting  temperatures;  that  is 
to  say,  around  that  point  where  the  best  efficiency  and  full-load 
is  obtained.  A  condition  of  this  kind  might  mean  that  for  short 
periods  of  time  an  overload  is  required,  hence  a  high  ratio  of 
copper  and  iron  loss,  and  decreased  first  cost  of  transformers. 

High  temperatures  are  objectionable  in  transformers.  Their 
effect  on  the  insulation  at  temperatures  about  100°  C.  means 
gradual  deterioration;  their  effect  on  the  copper  loss  is  a  decided 
objection,  this  loss  increasing  about  10  per  cent,  with  an  increase 
of  25°  C.  in  the  temperature;  their  effect  on  the  oil  is  to  increase 
the  deposition  of  hydrocarbon  on  the  windings  and  internal 
cooling  apparatus,  and  a  further  bad  effect  is  their  tendency  to 


TRANSFORMER  TESTING  IN  PRACTICE        239 

increase  the  "aging"  of  the  iron  (not  including  the  present 
improved  silicon  steel). 

To  get  at,  and  measure,  the  maximum  temperature  affect- 
ing the  insulation  is  almost  impossible  and  only  the  average 
temperature  is  measured  during  a  regular  test,  the  temperature 
being  taken  at  the  top  of  the  oil  and  not  at  the  immediate 
surface  of  contact  with  the  coils  or  core  of  the  transformer. 

The  Standardization  Rules  of  the  A.I.E.E.  state  that  the 
rise  in  temperature  of  a  transformer  should  be  based  on  the 
temperature  of  the  surrounding  air.  The  cooling  medium  for 
oil-insulated  self-cooled  and  for  forced-air  cooled  transformers 
is  the  surrounding  air,  but  for  oil-insulated  water-cooled  trans- 
formers the  cooling  medium  is  water,  and  the  temperature 
rise  to  be  considered  in  this  type  is  that  of  the  ingoing  water  and 
not  the  temperature  of  the  surrounding  air.  On  this  basis  a 
transformer  of  this  type  will  be  about  10°  C.  less  than  one 
specified  on  the  basis  of  the  temperature  of  the  surrounding  air. 

The  class  of  oil  used  for  insulating  purposes  has  a  great 
effect  on  the  temperature.  An  increase  in  the  viscosity  of  the 
oil  means  an  increase  in  the  frictional  resistance  to  its  flowing. 
The  velocity  of  circulation  is  reduced,  thereby  causing  an  in- 
creased rise  in  the  temperature. 

As  yet  it  has  not  been  possible  to  formulate  a  correct  theory 
of  the  laws  of  cooling  for  general  cases  which  will  indicate 
once  for  all  that  combination  of  conditions  which  is  most  favor- 
able to  cooling,  and  enable  one  to  say  with  considerable  accuracy 
not  only  what  will  be  the  average  temperature  rise  in  any 
given  case,  but  also  what  will  be  the  maximum  rise. 

Ratio  of  Transformation. — The  ratio  of  a  transformer  is  tested 
when  the  regulation  test  is  made.  It  is  the  numerical  relation 
between  the  primary  and  secondary  voltage.  The  ratio  of  a  trans- 
former must  be  correct,  otherwise  the  service  will  be  unsatisfac- 
tory, because  the  secondary  voltage  will  be  too  high  or  too  low. 

For  successful  parallel  operation,  correct  ratios  are  essential; 
otherwise  cross-currents  will  be  established  through  the  windings. 

A  method  of  ratio  test  is  shown  in  Fig.  182,  where  the  primary 
of  the  transformer  under  test  is  in  parallel  with  the  primary 
of  the  standard  ratio  transformer,  and  the  two  secondary  wind- 
ings are  connected  in  series^ 

Standard  transformer  ratios  are  usually  an  exact  multiple 
of  5  or  10. 


240 


STATIONARY  TRANSFORMERS 


TABLE  XII.— TABLE    OF    TEMPERATURE    COEFFICIENTS    OF 

RESISTIVITY    IN    COPPER    AT    DIFFERENT    INITIAL 

TEMPERATURES  CENTIGRADE 


Initial 

temperature 

cent. 


Temp,  coefficient 

in  per  cent,  per 

degree  cent. 


Initial 

temperature 

cent. 


Temp,  coefficient 

in  per  cent,  per 

degree  cent. 


0  0.4200 

1   0.4182 

25   0.3801 


2 

0.4165 

3  

0  4148 

4  

0.4131 

5  

0.4114 

6  

0  4nQ7 

7 

0.4080 

8  

0.4063 

9  

0  4047 

10  

0.4031 

11  

0.4015 

12  

0  .^999 

13  

0 . 3983 

14  

0.3967 

15 

0  .^9.'i1 

16  

0.3936 

17  

0.3920 

18  

0  .'^90.'i 

19  

0.3890 

20  

0.3875 

21  

0  .^SfiO 

22  

0.3845 

23  

0.3830 

24 

n  .'^Sl.'^ 

26   0.3786 

27 0.3772 


28  

0.3758 

29  

n  .-^744 

30 

0.3730 

31  

0  3716 

32  

0  .S702 

33  

0.3689 

34 

0.3675 

35  

0  .S662 

36  

0.3648 

37  

0.3635 

38  

0  .-^622 

39  

0.3609 

40  

0.3596 

41  

0  .«i.^83 

42  

0.3570 

43  

0.3557 

44  

0  .•^.'145 

45  

0.3532 

46  

0.3520 

47 

0  .^fiOS 

48  

0.3495 

49  

0 . 3482 

50  

0  .*^471 

Low-voltage  distribution  transformer  ratios  are  (low-voltage 
windings)  110,  220,  440  or  550  volt  to  (primary  voltage  wind- 
ing) 1,110/2,200,  3,300,  6,600  and  10,000  volts. 


TRANSFORMER  TESTING  IN  PRACTICE        241 

High-voltage  transformers  are  wound  for  11,000, 22,000, 33,000, 
44,000,  66,000,  88,000,  110,000  and  140,000  volts. 

Occasionally  transformers  are  required  with  ratio-taps  on 
the  primary  winding  so  that  they  may  be  operated  at  the  maxi- 
mum, intermediate  or  minimum  ratio. 


7  7 


ImAMOAMmJ    lQfi.Q.0QQ.O.QO.Q.Qj  Primary 
— ^DqOO^         I       ^^^'^ — I  Secondary 


S.E  D.T. 

Sw  tch 


Fig.  182. — Method  for  ratio  of  transformation  test. 

The  advantages  of  such  taps  are  (a)  voltage  compensation  due 
to  line  drop;  (6)  the  possibility  of  operating  the  complete  system 
on  any  of  the  intermediate  ratios,  (assuming  neutralized  system). 

Both  of  these  advantages  are  sometimes  desirable  but  it  would 
be  better  to  obtain  them  by  other  means  than  cutting  down 
the  normal  rating  of  the  transformer. 

It  is  evident  that  if  the  primary  voltage  is  maintained  constant 
while  operating  on  any  of  the  intermediate  taps,  the  transformer 
is  operated  at  a  greater  voltage  per  turn  and  therefore  at  a 
greater  iron  loss  than  when  the  total  winding  is  used.  The 
copper  loss  is  reduced  somewhat  so  that  the  total  full-load 
losses  are  not  materially  increased.  The  all-day  efficiency  is  re- 
duced very  materially  since  the  iron  loss  exists  for  24  hours 
of  the  day  and  the  copper  loss  only  about  three  to  four  or  five 
hours.  And,  as  regards  compensating  for  excessive  line  drop, 
it  is  true  that  if  the  transformer  is  connected  for  a  lower  ratio 
and  at  such  places  as  have  excessive  line  drop,  the  decreased 


16 


242 


STATIONARY  TRANSFORMERS 


primary  voltage  impressed  upon  the  decreased  primary  turns 
will  produce  approximately  normal  core  loss  and  the  desired 
secondary  voltage  during  the  period  of  full-load  on  the  system. 
However,  during  light  load,  when  a  heavy  current  is  no  longer 
in  the  primary  and  an  excessive  drop  no  longer  exists,  the 
transformer  connected  and  operating  on  any  of  the  intermediate 
or  lower  ratio  taps  will  be  subjected  to  full  primary  voltage 
impressed   on  the  reduced   primary  turns,   and   the  core  loss 

of  the  transformer  will  become  ex- 
cessive and  the  secondary  voltage  in- 
creased to  a  dangerous  limit,  that  is  to 
say,  dangerous  so  far  as  burn-outs  of 
incandescent  lamps  are  concerned,  for, 
whoever  should  happen  to  turn  on  their 
lamps  during  the  period  of  light-load 
operation,  is  sure  to  suffer  from  exces- 
sive lamp  burn-outs.  Operation  at  10. 
per  cent,  above  normal  voltage  for  which 
the  lamp  is  designed,  reduces  its  life  to 

-n       100     T.^    X    r  15  per  cent,  of  its  normal  value.     Conse- 

FiG.  183. — Effect  of  con-         ^,1  .  . 

necting  two  transformers  of  q^ently  by  operatmg  a  transformer  on 
different  ratios  in  parallel,     its   intermediate   ratio-taps,  offers  the 

disadvantage  of  excessive  core  loss  for 
at  least  20  to  21  hours  in  the  day,  and  excessive  burning  out  of 
lamps  during  the  same  period  of  time. 

Decreasing  the  ratio  of  a  transformer  from,  say,  10-1  to  9-1 
and  maintaining  the  voltage  constant,  increase  the  core  loss  ap- 
proximately 20  per  cent. 

A  difference  of  about  10  per  cent,  in  ratios  of  primary  and  sec- 
ondary voltages  will  result  in  a  circulation  of  about  100  per  cent, 
full-load  current.  And  a  difference  of  2  per  cent,  in  the  ratios 
may  result  in  a  circulation  of  20  per  cent,  full-load  current,  or  a  1 
per  cent,  difference  in  ratio  may  result  in  a  10  per  cent,  circula- 
tion of  full-load  current;  thus  showing  the  absolute  necessity 
for  having  the  ratios  always  exactly  the  same.  For  example; 
take  Fig.  183  and  assume  that  the  percentage  impedance  volts 
of  each  transformer  is  5  per  cent.,  and  the  measured  difference 
between  points  a  and  h  shows  21  volts.  What  will  be  the 
circulating  current  with  open  secondaries? 

The  21  volts  is  effective  in  circulating  current  through  the  trans- 
former windings  against  the  impedance  of  the  transformers  the 


TRANSFORMER  TESTING  IN  PRACTICE        243 


amount  of  current  being  expressed  in  per  cent.,  as 

I  per  cent.  =  — y^—  (34) 

where  k  is  the  difference  in  voltage  ratio  and  Z°  the  total  imped- 
ance volts  of  the  two  transformers. 

The  circulating  current  in  this  case  will  be  100  per  cent.,  or 

21X100 


kXlOO 


21 


=  100 


-300- 


npsT-—npm 


Taking  the  transformers  at  2000  kv-a  each,  it  is  evident  that 
there  will  be  10,000  amp.  flowing  through  the  secondary  windings 
of  one  transformer  and  9100  amp.  through  the  secondary  wind- 
ings of  the  other  when  a  and  b  are  connected  together. 

Before  connecting  any  two  trans- 
formers in  parallel  it  is  advisable  first  to 
measure  the  voltage  difference  between 
a  and  b  points  shown  in  Fig.  183. 

Polarity. — The  most  simple  method 
for  testing  the  polarity  is  to  connect  the 
primary  and  secondary  windings  of 
the  transformers  in  parallel,  placing  a 
fuse  wire  in  series  with  the  secondary 
winding.  If  the  transformers  are  of 
opposite  polarity  the  connection  will 
short-circuit  the  one  transformer  on 
the  other,  and  the  fuse  will  blow. 
Many  burnouts  are  due  to  wrong  con- 
nections of  this  kind. 

Transformers  are  generally  assembled 
so  that  certain  selected  leads  are 
brought  out  the  same  in  all  trans- 
formers of  the  same  type.     See  Fig.  184, 

The  primary  terminal  (a)  should  be  of  opposite  polarity  to  the 
secondary  terminal  (A).  If  we  apply  200  volts  to  the  primary, 
a  b,  of  the  transformer,  the  voltage  between  a  B  should  be 
greater  than  the  voltage  applied  to  a  b,  if  the  transformer  is  of 
the  correct  polarity,  or  less  if  of  opposite  polarity;  that  is  to  say. 


-200 +z- 


B 

Fig.  184. — Simple  method 
for  testing  the  polarity  of 
transformers. 


The  A.  I.  E.  E.  recommend  that  the  terminals  of  single-phase  transformers  shall  be  marked^ 

A B 

X Y 

A B 


(1)  High-  and  low-voltage  windings  in  phase: 

(2)  High-  and  low-voltage  windings  180°  apart  in  phase: 


(3)  High-  and  low-voltage  windings  in  phase  possessing  more  than  two 

windings: 

(4)  An  out-going  neutral  tap  (50  per  cent.)  as: 

(5)  For  three-phase  transformers  as: 


Y. 
A. 
X. 
X' 

A. 

X.. 


N 
..B. 


.X 

.B 

Y 

.Y' 

.C 
..Z 


244 


ST  A  TIONARY  TRANSFORMERS 


if  two  single-phase  transformers,  both  of  positive  polarity  or  both 
of  negative  polarity,  are  to  be  operated  in  parallel,  they  should  be 
connected  together  as  shown.  If  all  traiisformers  are  alike,  they 
may  have  the  same  polarity,  but  if  some  are  of  different  designs 
or  are  made  by  different  manufacturers,  their  polarity  may  be 
different. 

Single-phase  polarity  is  very  easily  determined;  not  so  with 
polyphase  transformers  since  both  phase  relation  and  rotation 


Positive 
Polarity  = 


B 
NOI 


E-e 


^E-> 
NO  2 


I    Negative 

VJ  Polarity  — 

E-e 


abba 
Fig.  185. — ^Positive  and  negative  polarity  of  single-phase  transformers. 

must  be  considered;  in  fact  polyphase  polarity  may  mean  a  large 
number  of  possible  combinations. 

Considering  first,  the  test  for  polarity  of  single-phase  trans- 
formers, it  is  best  to  consider  the  direction  of  voltages  to  know 
whether  they  are  in  phase  or  in  opposition,  that  is,  180  degrees 
out  of  phase.  Positive  polarity  means  that  if,  during  the  test, 
A-b  is  the  sum  of  voltage  A-B  and  a-h,  positive  polarity  is  ob- 

'  ■  i 


'Noi 


iryivn      ryyv-n 


n 


Fig.  186. — Method  of  finding  threee-phase  polarity. 

tained.  Negative  polarity  means  that  if,  the  voltage  between 
A-b  is  the  value  of  secondary  voltage  less  than  A-B  and  a-h 
negative  polarity  is  obtained.     See  Fig.  185. 

In  Fig.  185  we  have: 
Positive  polarity  =  No.  1  transformer  ={A  —  B)-\-(a—h)=E->re. 
and 
Negative  polarity  =  No.  2  transformer  ={A  —  B)  —  {a—h)=E  —  e. 


TRANSFORMER  TESTING  IN  PRACTICE        245 

This  means  that,  in  order  to  connect  No.  1  and  No.  2  in  parallel, 
different  leads  must  be  connected  together.  A  A,  BB  on  one  side 
and  aa,  bb  on  the  other  side.  It  is  always  better,  however,  when 
a  positive  polarity  transformer  is  to  be  connected  in  parallel  with 
a  negative  polarity  transformer,  to  reverse  the  connections  of 
cither  the  high-voltage  winding  or  the  low-voltage  winding  of  one 
of  the  transformers. 

Fig.  186  shows  the  method  of  finding  whether  two  three-phase 
transformers  have  the  same  polarity. 

In  making  the  above  test  similarly  located  terminals  should  be 
connected  together  as  shown.  If  no  voltage  is  indicated  between 
leads  x'  and  x  or  between  y'  and  y,  the  polarities  are  the  same  and 
the  connections  can  be  made  and  if  desired,  put  into  regular 
operation.     If,  however,  there  is  a  difference  of  voltage  between 


a        c 


Fig.  187. — Testing  for  polarity  in  .three-phase  systems. 

y'  —  y  or  x'  —  x,  or  both,  the  polarity  of  the  two  groups  is  not  the 
same  and  parallel  operation  is  impossible.  It  is  necessary  to 
determine  the  polarity  of  each  three-phase  transformer  separately. 

The  correct  connections  under  these  circumstances,  are  given 
in  Fig.  187. 

Iron  or  Core  Loss. — The  core  loss  includes  the  hysteretic  and 
eddy-current  losses.  The  eddy-current  loss  is  due  to  currents 
produced  in  the  laminations,  and  the  hysteretic  loss  is  due  to 
molecular  friction.  The  core  loss  remains  practically  constant 
at  all  loads,  and  wUl  be  the  same  whether  measured  from  the 
primary  or  secondary  side,  the  exciting  current  in  either  case 
being  the  same  per  cent,  of  the  full  load.  The  economical  opera- 
tion of  a  lighting  plant  depends  in  a  large  measure  on  the  selection 
of  an  economical  transfornjer.  An  economical  transformer  is 
seldom  the  one  of  lowest  first  cost,  nor  is  it  necessarily  the  one 
having  the  smallest  full-load  losses.     It  is  the  one  which  has  the 


246  STATIONARY  TRANSFORMERS 

most  suitable  division  of  losses  for  the  service  for  which  it  is  to  be 
used. 

The  hysteresis  loss  is  dependent  on  the  iron  used,  and  in  a  given 
transformer  varies  in  magnitude  with  the  1.6  power  of  the 
(induction)  or  magnetic  density.  An  increase  in  voltage  applied 
to  a  transformer  causes  an  increase  in  core  loss  (see  following 
table),  while  an  increase  in  the  frequency  results  in  a  corre- 
sponding decrease  in  core  loss — the  density  varying  directly  as 
the  voltage  and  inversely  as  the  frequency.  The  eddy  current 
loss  varies  in  magnitude  with  the  conductivity  of  the  iron  and 
the  thickness  of  laminations.  Both  the  hysteresis  and  eddy 
current  losses  decrease  slightly  as  the  temperature  of  the  iron 
increases,  and  if  the  temperature  be  increased  sufficiently  the 
hysteresis  loss  might  disappear  entirely  while  the  eddy  current 
loss  will  show  a  decrease  with  increased  resistance  of  the  iron  due 
to  this  temperature.  Thus  at  full-load,  or  in  other  words,  an 
increase  in  temperature  to  the  limiting  temperature  rise  of  40°  C. 
may  cause  a  decrease  in  core  loss  of  about  5  per  cent,  depending 
on  the  wave  form  of  the  impressed  voltage.  For  ordinary  steel 
used  in  transformers,  a  given  core  loss  at  60  cycles  may  consist  of 
72  per  cent,  hysteresis  and  28  per  cent,  eddy  current  loss,  the 
hysteresis  loss  decreasing  with  increased  frequency  while  tlie  eddy 
current  loss  is  increased  with  increased  frequency. 

Low  power  factor  of  exciting  current  is  not  in  itself  very 
objectionable.  This  can  best  be  explained  by  taking  two  trans- 
formers, one  made  up  of  ordinary  iron  and  the  other  of  modern 
silicon  steel  or  "alley-steel,"  Take,  for  example,  two  5kw, 
transformers.  The  one  made  up  of  ordinary  iron  will  have  a  core 
loss  of  about  64  watts  while  that  made  of  silicon  steel  will  have  a 
core  loss  of  only  45  watts;  and,  taking  the  exciting  current  of 
both  to  be  2  per  cent,  of  the  full-load  current,  we  have  the  follow- 
ing power  factors: 

Transformer  with  ordinary  iron: 

64 

=  64  per  cent,  power  factor 


5000X0.02 

and 

Transformer  with  silicon  steel 


45 
5000x0.02^^^  P^^  ^^^*"  P^^^^'  factor. 


TRANSFORMER  TESTING  IN  PRACTICE        247 

which  means  that  on  no-load  the  one  using  ordinary  iron  has 
19  per  cent,  better  power  factor. 

As  stated  above,  the  lower  the  frequency  the  greater  will  be 
the  iron  loss.  In  ordinary  commercial  transformers  a  given  core 
loss  at  60  cycles  may  consist  of  72  per  cent,  hysteresis  and  28 
per  cent,  eddy-current  loss,  while  at  125  cycles  the  same  trans- 
former may  have  50  per  cent,  hysteresis  and  50  per  cent,  eddy- 
current  loss.  The  core  loss  is  also  dependent  upon  the  wave- 
form of  the  applied  e.m.f.  A  flat  top  wave  gives  a  greater  loss 
than  a  peaked  wave  and  vice  versa. 

With  a  sinusoidal  wave  of  e.m.f.  applied  on  a  transformer,  the 
exciting  current  is  distorted,  due  to  the  effect  of  hysteresis.  If 
resistance  is  introduced  into  the  primary  circuit,  however,  the 


HjiJiJlftiiiL^     Transformer 


Fig.  188. — Iron  or  core  loss  transformer  test. 


exciting  current  wave  becomes  more  sinusoidal  and  the  generated 
e.m.f  .-wave  more  peaked,  the  effect  of  these  distortions  tending 
to  reduce  the  exciting  current  and  core  loss.  Since  the  magnetic 
density  varies  with  the  voltage  and  inversely  with  the  frequency, 
an  increase  in  voltage  applied. to  the  transformer  causes  an 
increase  in  core  loss,  while  an  increase  in  frequency  results  in  a 
corresponding  decrease  in  core  loss. 

Of  the  several  methods  in  use  for  determining  core  loss,  the 


248 


STATIONARY  TRANSFORMERS 


following  method  is  the  simplest  to  apply  and  gives  very  accurate 
results.     See  Fig.  188. 

There  are  occasions  when  the  core  losses  of  a  transformer  are 
known  while  operating  at  a  given  frequency  and  voltage  but 
when  it  is  desired  to  correct  these  results  for  operation  under 
other  conditions  other  figures  are  necessary.  In  order  to  deter- 
mine approximately  the  losses  of  a  60-cycle  transformer  when 
operating  at  other  than  rated  voltage,  the  losses  at  rated  voltage 
may  be  multiplied  by  the  factors  given  in  the  following  table: 

TABLE  XIII.— VARIATION  OF  CORE  LOSS  IN  A  60-CYCLE 
TRANSFORMER  WITH  VARYING  VOLTAGE 


Rated  voltage  of  transformer 

Operating  voltage 

2000 

2100 

2200 

2300 

2400 

2500 

2600 

Losses 

2000 

1.00 
1.09 
1.11 
1.23 
1.37 

0.91 
0.98 
1.00 
1.11 
1.22 
1.35 
1.49 

0.83 
0.89 
0.91 
1.00 
1.10 
1.21 
1.33 
1.46 

0.76 
0.82 
0.83 
0.91 
1.00 
1.10 
1.20 
1.31 

0.70 
0.75 
0.77 
0.84 
0.92 
1.00 
1.09 
1.19 

.    2080 
2100 
2200 
2300 
2400 
2500 
2600 

0.70 
0.71 
0.77 
0.84 
0.92 
1.00 
1.09 

0.66 
0.72 
0.78 
0.85 
0.92 
1  00 

The  values  given  in  the  above  table  are  only  approximate 
-because  the  variations  with  varying  voltage  depend  largely 
upon  the  quality  of  steel  and  the  density  at  which  the  trans- 
formers are  operated. 

Resistances. — ^The  resistance  of  the  primary  and  the  secondary 
of  a  transformer  may  be  determined  by  several  different  methods, 
the  most  common  of  which  are  "fall  of  potential"  and  "wheat- 
stone  bridge"  methods.  For  commercial  use  the  most  satis- 
factory method  is  the  fall  of  potential.  In  this  method  the 
resistance  may  be  determined  by  Ohms  law: 

Resistance  =-r .  (38) 

Amperes 


TRANSFORMER  TESTING  IN  PRACTICE        249 

The  measurement  requires  continuous  current  and  a  continu- 
ous-current voltmeter  and  ammeter.  With  the  connection 
shown  in  Fig.  189,  assume,  for  example,  the  ammeter  reading  to 
be  2.5  amperes,  and  voltmeter  reading  to  be  11  volts.  What  is 
the  resistance  of  coil? 

The  resistance  of  voltmeter  used  in  test  is  500  ohms,  and  the 
temperature  of  transformer  coil  is  30  degrees  centigrade.  There- 
fore, current  taken  by  voltmeter  at  1 1  volts  is, 

^  =  0.022  amp. 

Current  in  transformer  coil  =2.5  —  0.022  =  2.478  amp. 

The  ammeter  reading  includes  the  current  in  the  voltmeter, 


lJ  I 


—*<  Res. 


nmmD 


Fig.  189. — Method  of  finding  the  resistance  of  a  transformer. 

and  in  order  to  prevent  error  the  resistance  of  the  voltmeter 
must  be  much  greater  than  that  of  the  resistance  to  be  measured. 
Resistance  of  transformer  coil  at  30  degrees  centigrade  is, 

11 


2.478 


=  4.48  ohms. 


It  is  important  that  measurements  be  taken  as  quickly  as 
possible,  especially  if  the  current  be  near  the  full-load  values,  and 
it  is  equally  important  in  alJ  cases  that  the  voltmeter  needle  be 
at  rest  before  the  observation  is  taken,  otherwise  the  values 
obtained  will  not  be  reliable.     It  is  possible  to  have  a  current  of 


250 


STATIONARY  TRANSFORMERS 


sufficient  strength  to  heat  the  coil  so  rapidly  as  to  cause  it  to 
reach  a  constant  hot  resistance  before  the  measurement  is  taken. 
The  resistance  of  the  transformer  coil  at  25°  C,  which  is  the 
temperature  coefficient  of  0.42  per  cent,  per  degree  from  and  at 
0°C.,  is, 

4.48XJ00 

(0.42X5) +100 


i:-^  v^^  =  4.39  ohms. 


If  the  temperature  of  windings  is  different  for  each  observation, 
then  resistance  must  be  calculated  for  each  and  the  average  taken. 
If  the  temperature  of  the  windings  is  the  same  for  air  observa- 
tions, then  the  average  voltage  and  current  may  first  be  deter- 
mined and  the  resistance  calculated  from  the  average  values. 

Copper  Loss  and  Impedance. — ^When  a  transformer  is  delivering 
power,  copper  loss  takes  place,  varying  as  the  square  of  the 


Primary 
Secondary 


Fig.  190. — Copper  loss  and  impedance. 

current.     It  is  due  to  the  resistance  of  the  windings  and  to  the 
eddy  currents  within  the  conductors  themselves. 

The  copper  loss  may  be  measured  at  the  same  time  as  the 
impedance-drop  measurement  by  introducing  a  wattmeter  as 
shown  in  Fig.  190.  It  may  also  be  calculated  from  currents 
through  conductors  and  resistance  of  conductors,  as  follows: 

P  =  h^Ri  +  h^R2,  in  watts, 


TRANSFORMER  TESTING  IN  PRACTICE        251 

wherein  P  is  the  power  lost;  /j,  the  primary  current;  1 2,  the 
secondary  current;  j^i  the  primary  resistance;  and  R2  the  second- 
ary resistance. 

The  variation  of  copper  loss  with  varying  voltage  on  2200  to 
2600  volt  60-cycle  transformers  is  given  in  the  following  table: 

TABLE  XIV.— VARIATION   OF   COPPER   LOSS    WITH   VARYING 
VOLTAGE  ON  60-CYCLE  2200  TO  2600  VOLT  TRANSFORMERS 


Ratio  voltage 

Varying 
voltage 

2000 

2080 

2100 

2200 

2300 

2400 

2500 

2600 

Losses 

2000 

1.00 
0.98 
0.91 
0.83 
0.76 

1.08 
1.00 
0.98 
0.89 
0.82 
0.75 

1.10 
1.02 
1.00 
0.91 
0.83 
0.77 
0.71 

1.21 
1.12 
1.10 
1.00 
0.91 
0.84 
0.77 
0.72 

1.32 
1.22 
1.20 
1.10 
1.00 
0.92 
0.85 
0.78 

1.44 
1.33 
1.30 
1.19 
1.09 
1.00 
0.92 
0.85 

2080 

1.44 
1.42 
1.29 
1.19 
1.09 
1.00 
0.93 

2100 
2200 
2300 
2400 
2500 

53 
40 

28 
17 
08 

2600 

00 

In  testing  a  three-phase  transformer  for  copper  loss  and 
impedance  the  measurements  can  be  made  conveniently  by 
connecting  both  the  high-voltage  and  the  low-voltage  windings 
in  delta  and  opening  up  any  one  corner  of  the  delta  on  either  the 
high-voltage  or  low-voltage  side  as  desired  and  convenient  for 
supply  voltage,  and  inserting  a  wattmeter,  voltmeter  and  ammeter 
and  impressing  sufficient  single-phase  voltage  across  this  corner 
at  the  proper  frequency  to  cause  normal  full-load  current  to  flow 
through  the  windings.  The  wattmeter  reading  will  give  the 
copper  loss,  and  this  reading  divided  by  the  normal  full-load 
input  in  the  transformer  will  represent  the  per  cent,  copper  loss. 
One-third  of  the  voltage  measured  on  the  voltmeter  divided  by 
the  normal  voltage  of  the  winding  of  one  phase  represents  the 
percentage  impedence  drop. 

The  impedance  in  alternating-current  circuits  is  similar  to  re- 


252  STATIONARY  TRANSFORMERS 

sistance  in  continuous-current  circuits,  that  is  to  say,  the  ex- 
pression 

r       ^       r^  x  G.m.f.  .^^^ 

/  =  D  =  Current  =     ~  . (42) 

R  Resistance  ^     ^ 

for  continuous-current  circuits  is  replaced  in  alternating-current 
circuits  by  the  equivalent  expression, 

~ \/R^+{X's^ ~    ~ i mpedance ~R-jx~Uj^^ -fhw    ^^"^ ^ 

where  /  is  the  current;  E  the  impressed  e.m.f. ;  Xg  the  inductive 
reactance;  and  J^  the  resistance  of  the  circuit. 

The  impedance  of  a  transformer  is  made  up  of  two  components 
at  right  angles  to  each  other.  (Reactance  and  resistance.)  It 
is  expressed  as 

Z  =  \/R^+X^=  {R-jx)R  +  v'^T  Lw  (45) 

Reactance  may  be  inductive,  Xg,  or  condensive  Xc',  this  latter 
factor  is  never  considered  when  dealing  with  transformers. 

X.  =  2.fL  and  X,  =^-l_  =  _J__  (46) 

wherein /is  the  frequency  in  cycles  per  second;  L  is  the  induct-, 
ance  in  henrys;  and  C  is  the  capacity  in  farads. 

The  impedance  of  a  transformer  is  measured  by  short-circuiting 
one  of  the  windings,  impressing  an  e.m.f.  on  the  other  winding 
and  taking  simultaneous  measurements  of  voltage  and  current. 

The  impedance  voltage  varies  very  nearly  with  the  frequency. 
In  standard  transformers  the  impedance  voltage  varies  from 
1  to  4  per  cent.,  depending  upon  the  size  and  design  of  the 
transformer. 

Efficiency. — ^The  efficiency  of  a  transformer  is  the  ratio  of  its 
net  output  to  its  input.  The  output  is  the  total  useful  power 
delivered  and  the  input  is  approximately  the  total  power  delivered 
to  the  primary;  and  consists  of  the  output  power  plus  the  iron 
loss  at  the  rated  voltage  and  frequency,  plus  the  copper  loss  due 
to  the  load  delivered. 

Example:  Find  the  full-load,  and  half-load  efficiency  of  a 
5-kw.,  2000  to  200-volt,  60-cycle  transformer  having  an  iron 
loss  of  70  watts,  a  primary  resistance  of  10.1  ohms,  a  secondary 
resistance  of  0.066  ohms. 


TRANSFORMER  TESTING  IN  PRACTICE        253 

The  efficiency  of  the  transformer  under  consideration  is  taken 

as  follows: 

Full  Load: 

Primary  I^  R 63  watts 

Secondary  PR 42  watts 

Core  loss 70  watts 

Total  Losses 175  watts 

Output  = 5,000  watts 

Input  =  5,000 +  175 5,175  watts 

Full  load  efF.  =  t^v?==96.6  per  cent. 
5,175 

Half  Load: 

Primary  and  Secondary 26  watts 

Core  loss 70  watts 

Total  Losses 96  watts 

Output  = 2,500  watts 

Input  =  2,500 +  96 2,596  watts 

One-half  load  eff.  =^^^-=96.2  per  cent. 

It  will  be  noted  that  the  iron  loss  remains  constant  at  all 
loads  but  the  copper  loss  varies  as  the  square  of  the  load  current. 
The  copper  loss  remains  the  same  in  all  transformers  of  a  given 
design  and  size,  it  is,  therefore,  only  necessary  to  make  these 
tests  on  one  transformer  of  each  rating  and  type. 

The  copper  loss  should  preferably  be  determined  from  the 
resistances  of  the  windings,  rather  than  from  the  copper  loss 
test  by  wattmeter.  For  other  than  full-load,  the  copper  loss 
varies  as  the  square  of  the  load,  the  core  loss  remaining  constant 
at  all  loads.  The  all-day  efficiency  takes  into  account  the  time 
during  which  these  losses  are  supplied  and  is  expressed  as: 

Per  cent,  all-day  eff.  = 

100 +watthours  output  .     .„v 

w.-hrs.  output +w.-hrs.  copper  loss-j-w.-hrs.  core  loss  ^ 

The  exact  copper  loss  of  a  transformer  must  be  known  in  order 
to  calculate  the  efficiency.  The  core  loss  should  be  taken  at 
exactly  the  rated  voltage  of  the  transformer  and,  when  possible, 
with  a  sine  wave  current,  otherwise  considerable  discrepancies 
may  occur. 

Regulation. — ^The  regulation  of  a  transformer  with  a  load  of 
given  power-factor  is  the  percentage  of  difference  of  the  full 
load  and  no  load  secondary  voltages  with  a  constant  applied 


254  STATIONARY  TRANSFORMERS 

primary  voltage.  It  may  be  ascertained  by  applying  full  load 
to  the  transformer  and  noting  the  secondary  voltage,  then 
removing  the  load  and  noting  the  secondary  open-circuit  voltage. 

The  secondary  voltage  drop  will  be  very  much  greater  with 
an  inductive  load,  such  as  induction  motors  or  arc  lamps,  than 
it  will  be  with  incandescent  lamps. 

The  regulation  can  be  determined  by  direct  measurement  or 
calculation  from  the  measurements  of  resistance  and  reactance 
in  the  transformer.  Since  the  regulation  of  any  transformer  is 
only  a  few  per  cent,  of  the  impressed  voltage,  and  as  errors  of 
observation  are  liable  to  be  fully  1  per  cent.,  the  direct  method  of 
measuring  regulation  is  not  at  all  reliable.  By  connecting  the 
transformer  to  a  circuit  at  the  required  voltage  and  frequency, 
using  a  lamp  load  or  water  rheostat  on  the  secondary  the  regula- 
tion may  be  determined.  This  method,  is,  however,  unsatis- 
factory, and  much  more  reliance  can  be  placed  on  the  results  of 
calculation. 

Several  methods  have  been  proposed  for  the  calculation  of 
regulation,  but  the  following  is  found  quite  accurate  for  inductive 
and  non-inductive  loads. 

For  inductive  loads: 

%  regulation  =%X  smd+%1  R  cos  d.  (48) 

=  %  E:,  sin  d+%Er  cos  0. 

Per  cent.  Ex    =the  per  cent,  reactance  drop. 

Per  cent.  Er     =per  cent,  total  resistance  drop. 

^  =  the  angle  of  lag  of  load  current  delivered. 

Example. — ^Find  the  regulation  of  a  transformer  which  has 
a  reactance  drop  of  3.47  per  cent,  and  a  resistance  drop  of  2.0 
per  cent,  when  delivering  a  load  to  a  circuit  having  a  power- 
factor  of  87  per  cent. 

The  cos  ^  =  0.87  is  30  degrees.     The  sine  of  angle  30  degrees  is 
0.5.     Then  from  the  above  formula: 
Per  cent,  regulation  =  3.47x0.5 +  2X0.87  =  3.48. 

For  non-inductive  loads: 

%  Regulation  =%IR-  ^^~q^^^  (49) 

Per  cent.  I  R  =  per  cent,  resistance  drop. 
%  X  =  'V%  impedance  drop^— %  resistance  drop^=  %  react- 
ance drop. 
I  =  V%  exciting  current^—  %  iron  loss  currents 


TRANSFORMER  TESTING  IN  PRACTICE        255 


256  STATIONARY^  TRANSFORMERS 

For  non-inductive  load  O  —  O,  sin  O  —  O,  cos  0  =  1,  we  have, 
therefore: 

%  regulation  =%  Er 

The  above  formula  is  practically  correct  for  small  values  of 
angle  6,  but  the  error  becomes  greater  as  0  increases. 

Another  simple  and  accurate  method  in  use  for  calculating 
regulation  is, 

For  non-induction  loads: 

TV   2 

%  regulation  =7  7^20^  ^^°^ 

and  for  inductive  loads: 

%  regulation  =d  4- 2QQ  (51) 

where  d  is  component  drop  in  phase  with  the  terminal  voltage 
and  k  is  the  component  drop  in  quadrature  with  the  terminal 
voltage,  IR  is  total  resistance  drop  in  per  cent,  of  rated  voltage 
and  IX  is  reactance  drop  in  per  cent. 

Take  for  example  a  7.5  kw.  60-cycle  single-phase  transformer 
with  a  10  to  1  ratio,  secondary  voltage  at  full  load  =  208  volts  and 

Sec.  resistance  =0.0635  ohms.  Primary  resistance  =4.3 
ohms. 

Sec.  7/2  =  2.165  volts  =  0.985  %.     Primary  772  =  14.65  volts  = 
0.667  %. 
and 

IX  =  V{%  impedance  drop) 2- 77^2=  1.8  % 

For  non-inductive  load,  using  the  formula  above,  we  have 

%  regulation  =  1.65  +^|^  =  1.67  % 

and 

For  inductive  load  with  a  power  factor  of,  say,  80%,  we  have 

0  462 
%  regulation  =  2.3  +  ^^  =  2.33  % 

where  2.3  is  taken  from  formula,  and  is: — 

d  =  w  7X  +  772  Cos  ^  =  (0.6  X 1 .8)  4-  (1 .65  X  0.8)  =  2.3 

The  value  IX  (reactance  drop  in  volts)  may  also  be  expressed  by  the  formula 


V(B.--£^) 


where  E  is  the  rated  primary  voltage,  E^  being  the  impedance  voltage  and  is  found  by  short- 
circuiting  the  secondary  winding  and  measuring  the  volts  necessary  to  send  rated-load  current 
through  the  primary.     P  is  the  impedance  watts  as  measured  in  the  short-circuit  teat. 


TRANSFORMER  TESTING  IN  PRACTICE        257 

and 

0.46  is  from  formula,  and  is: — 

k  =  w  IR- IX  Cos  ^  =  (0.6 XI. 65) -(1.8X0.8)  =046 

where  w  is  the  wattless  factor  of  load. 

Short-circuit  Test. — For  some  time  past  it  has  been  the  practice 
of  certain  transformer-testing  departments  in  America  to  subject 
certain  types  of  transformers  over  a  given  k-v-a.  capacity  to 
short- circuit  tests  of  from  5  to  25  times  rated  current. 

It  is  now  well  known  that  the  cause  of  many  burn-outs  is 
due  to  the  large  amount  of  power  back  of  the  transformers.  It 
has  also  been  shown  that  a  certain  milling  occurs  in  transformers, 
and  after  repeated  short-circuits  the  transformer  breaks  down,  its 
coils  being  twisted  in  the  shell  type  and  displaced  in  the  core 

type. 

The  short-circuit  test  is  usually  done  at  special  times  of  the 
night  so  as  not  to  affect  the  voltage  regulation  of  the  system. 
One  winding  of  the  transformer  is  connected  to  the  power  system 
(always  many  times  the  capacity  of  the  transformers)  and  the 
other  winding  suddenly  short-circuited.  The  tendency  of  the 
coils  to  flare  out  due  to  the  excessive  magnetic  repulsion  is  the 
most  important  point  of  the  test.  This  test  is  of  very  short 
duration,  as  the  current  sometimes  reaches  as  high  a  value  as 
25  to  30  times  full-load  current. 


17 


CHAPTER  XV 
TRANSFORMER  SPECIFICATIONS. 

High-voltage  transformer  specifications  are  always  interesting 
in  that  other  more  severe  mechanical  and  electrical  stresses  have 
to  be  considered  in  their  design,  and  the  arrangement  of  coils, 
their  form  and  make-up  are  so  different.  Below  is  given  a  wind- 
ing specification  of  a  high-voltage  transformer  which  was 
specially  made  for  an  existing  transformer  operating  at  a  lower 
voltage  (the  same  iron  being  used  over  again). 

WINDING   SPECIFICATION   FOR  A  WATER-COOLED  OIL-FILLED 
60-CYCLE  900-KW.  22,700-39,300  TO  2200-VOLT  SINGLE- 
PHASE  TRANSFORMER. 

Primary  Winding 

Conductor  cross-section,  two  0.170  in.  X  0.080  in.  double  cotton 

covered. 
Weight,  750  lb.  double  cotton  covered. 

Inside  Section.  Outside  Section. 

Turna     /  8  B.T.  coils  of  32  and  32  \  /  pz,  pa,  pt,  p&,  pe,  p?,  pa, 

618  in.    \  2  B.T.  coils  of  27  and  26  /      "•      \         p^,  pi,  and  pn,. 

Winding  taps  made  at  end  of  fifth  turn  inside  end  of  outside 

section  ps,  p^. 
Insulation  between  turns   (8300  ft.)   0.015  in.  thick  by  3/16  in. 

wide,  consisting  of  two  0.005  in.  hercules  parchment  and  one 

0.005  in.  mica. 

Reinforced  Turn  Insulation 

26-turn  section,  last  12  turns  (triple)  turn  insulated,  and  all  turns 

0.012  \.CK 
26-turn  section,  all  other  turns  (double)  turn  insulated,  and  all 

turns  0.012  V.C. 
26-turn  section,  all  turns  (double)  turn  insulated,  and  all  turns 

0.012  V.C. 

1  V.C.  =  varnish  cambric. 

258 


TRANSFORMER  SPECIFICATIONS  259 

Coils  pi  and  pio  special  collars  of  1  3/32  in.  pressboard. 
All  wood  strips  to  be  of  3/4  in.  wide  by  3/16  in. 
Pressboard  strips  to  be  of  1  1/2  in.  wide  by  3/16  in. 
Taping  of  coils  to  be  of  0.229  in. 
Wire  vacuum,  1. 
Coil  dimensions:  bare,  7  5/16  in.  by  1/2  in.;  insulated, 

7  3/8  in.  by  9/16  in. 
Dimensions  of  coils  with  special  collars:  bare,  7  5/16  in. 
by  5/8  in.;  insulated,  7  3/8  in.  by  11/16  in. 

Secondary  Winding 

Conductor  cross-section,  four  0.300  in.  X  0.115  in.,  two 
of  double  cotton  covered  and  two  of  bare. 

Weight,  370  lb.  double  cotton  covered  and  370  lb.  bare. 

60  turns  in  8  S.S.  coils  of  15  turns  each,  4  coils  in  series, 
2  in  parallel. 

Insulation  between  turns,  1340  ft.,  0.025  in.  thick  by 
5/16  in.  wide,  consisting  of  two  0.010  in.  hercules  parch- 
ment and  one  0.005  in.  mica. 

Coil  dimensions:  bare,  7  3/4  in.  X  5/16  in.;  insulated, 
7  13/16  in.  X  3/8  in. 

Coils  for  special  collars  of  1  3/32  in. 

Insulation  Specification 

After  winding  the  coils  they  must  be  securely  clamped  to 
dimensions  called  for  in  the  winding  specifications,  after  which 
they  are  to  have  the  terminals  attached. 

Before  the  coils  are  dipped  they  should  have  a  preliminary 
baking  for  12  hours  at  250°  F.  (120°  C),  or  longer  if  necessary, 
thoroughly  to  dry  out  any  moisture  and  shellac  in  the  turn 
insulation  and  collars.  The  coils  should  be  twice  dipped  when 
hot  in  0.07-B  japan  and  baked  12  hours  at  250°  F.  after  each 
dipping. 

After  the  coils  have  been  dipped  they  are  to  receive  one  pintag 
of  0.007  in.  cotton  tape  for  varnish  treatment.  The  taping  is 
to  be  put  on  according  to  directions  given  below. 

Before  putting  on  the  taping  the  coils  should  be  brushed  over 
with  a  thin  coat  of  0.028  in.  sticker  to  hold  the  tape  to  the  coils. 
The  taping  should  receive  five  brushings  of  0.094  in.  varnish  of 
specific  gravity  875,  and  should  be  baked  after  each  brushing  at 
least  five  hours,  or  until  hard,  at  a  temperature  of  180°  F.  (85  to 


260  STATIONARY  TRANSFORMERS 

95  °C.).  After  each  taping  the  coils  should  be  allowed  to  cool  to 
at  least  100°  F.  (38"  C.)  before  the  next  varnishing  is  given. 

The  taping  should  be  put  on  with  one-half  lap,  except  at  the 
corners  of  the  coils,  where  it  should  overlap  not  more  than  one- 
eighth  at  the  outside  edge. 

With  single  section  coils  there  should  be  added,  before  the  taping 
is  put  on,  one  thickness  of  No.  2  cotton  drill,  which  is  to  be  placed 
over  the  connecting  straps.  The  drill  should  extend  at  least 
1  1/2  in.  each  side  of  the  strap,  and  must  be  neatly  and  firmly- 
tied  down  with  twine  and  sewed  together  at  the  outside  edge  of 
the  coil,  A  tongue  of  the  drill  should  extend  up  the  outside  of 
the  strap  as  far  as  the  terminal,  and  should  be  secured  to  the 
strap  with  a  wrapping  of  cotton  tape. 

Below  is  given  a  form  of  general  specification  as  presented  to 
purchasers  of  transformers.  The  former  is  for  a  high-voltage 
shell-type  transformer  and  the  latter  for  a  high-voltage  core-type 
transformer. 


GENERAL  SPECIFICATIONS  FOR  A  RECTANGULAR  "SHELL-TYPE" 

WATER-COOLED  OIL-FILLED  70,000-VOLT  25-CYCLE 

SINGLE-PHASE  TRANSFORMER. 

General  Construction. — Each  transformer  to  consist  of  a  set  of 
flat  primary  and  secondary  coils,  placed  vertically  and  surrounded 
by  a  built-up  steel  core,  the  coils  being  spaced  so  as  to  admit  of 
the  free  circulation  of  oil  between  them,  which  acts  not  only  as 
an  insulator  but  as  a  cooling  medium  by  conveying  the  heat 
from  the  interior  portions  of  the  transformer  to  the  tank  by 
natural  circulation. 

The  transformer  to  be  enclosed  in  a  boiler-iron  tank,  the  base 
and  cover  being  of  cast  iron.  The  tank  to  be  secured  to  the  base 
with  a  joint  made  oil-tight  by  heavy  riveting  and  caulking. 

A  coil  of  pipe  for  water  circulation  to  be  placed  in  the  oil  in  the 
upper  part  of  the  tank  over  the  cover  and  surrounding  the  ends 
of  the  windings,  the  combined  surface  of  the  coil  and  tank  being 
sufficient  to  dissipate  the  heat  generated  and  thus  maintain  the 
oil  and  -all  parts  of  the  transformer  at  a  low  temperature. 

Core. — The  core  to  be  built  up  of  steel  laminations  of  high  per- 
meability and  low  hysteresis  loss.  The  laminations  also  to  be 
carefully  annealed  and  insulated  from  each  other  to  reduce 
eddy-current  losses. 


TRANSFORMER  SPECIFICATIONS  261 

Windings. — The  primary  and  secondary  windings  to  be  sub- 
divided into  several  coils,  each  built  up  of  fiat  conductors,  wound 
with  one  turn  per  layer  so  as  to  form  thin,  high  coils  which  will 
present  a  large  radiating  surface  to  the  coil.  The  conductors  to 
be  cemented  together  with  a  special  insulating  compound,  after 
which  an  exterior  insulating  wrapping  to  be  applied  and  separately 
treated  with  an  insulating  varnish,  making  a  very  durable 
insulation. 

A  solid  insulating  diaphragm  to  be  placed  between  adjacent 
primary  and  secondary  coils,  and  to  be  rigidly  held  in  position 
by  spacing  channels  covering  the  edges  of  the  coils. 

The  assembled  coils,  except  at  the  ends,  to  be  completely 
enclosed  by  sheets  of  solid  insulation,  which  will  interpose  a  sub- 
stantial barrier  at  all  points  between  the  winding  and  the  core. 

Oil. — Each  transformer  to  have  sufficient  oil  completely  to 
immerse  the  core,  windings,  and  cooling  coil.  In  order  to  secure 
the  best  insulating  qualities  and  a  high  flashing-point,  the  oil 
to  be  specially  refined  and  treated  and  tested  for  this  use. 

A  valve  for  drawing  off  the  oil  to  be  located  in  the  base  of  the 
tank. 

Water-cooling  Coil. — To  consist  of  heavy  wrought-iron  lap- 
welded  pipe  with  electrically  welded  joints,  and  to  stand  a  test 
of  at  least  1000  lb.  pressure  per  square  inch. 

The  duty  of  the  cooling  coil  is  to  absorb  that  portion  of  the  heat 
that  cannot  be  dissipated  by  natural  radiation  from  the  tank, 
which  will  be  made  to  fit  the  transformer  closely,  and  thus 
minimize  the  amount  of  oil  and  floor  space. 

Leads. — The  primary  and  secondary  leads  to  be  brought  out 
through  the  cover,  and  to  consist  of  heavy  insulated  cables 
brought  through  porcelain  bushings  of  ample  surface  and  thick- 
ness. 

Performance. — After  a  run  of  24  hours  at  rated  load,  frequency, 
and  voltage,  the  rise  in  temperature  or  any  part  of  the  trans- 
former, as  measured  by  thermometer,  and  the  rise  in  temperature 
of  the  coils,  as  measured  by  the  increase  in  resistance,  not  to 
exceed  40°  C,  provided  the  temperature  of  the  circulating  water 
is  not  greater  than  25"  C,  and  that  the  supply  of  water  is  normal. 
If  the  temperature  of  the  water  differs  from  25°  C,  the  observed 
rise  in  temperature  shoul^  be  corrected  by  0.5  per  cent,  for  each 
degree. 

The  insulation  between  the  primary  coils  and  the  core,  and 


262  STATIONARY  TRANSFORMERS 

that  between  the  primary  and  secondary  coils,  to  stand  a  test  of 
140,000  volts  alternating  current  for  1  minute,  and  between  the 
secondary  coils  and  the  core  a  test  of  double  the  normal  voltage 
for  the  same  length  of  time. 

The  transformer  to  carry  an  overload  of  25  per  cent,  for  two 
hours  without  the  temperature  rise  exceeding  55°  C. 

The  transformer  to  give  full  kilowatt  output  when  operating 
at  90  per  cent,  power  factor  without  exceeding  the  above  tem- 
perature rise. 

GENERAL   SPECIFICATIONS  FOR  A  70,000-VOLT  25-CYCLE 
"CORE-TYPE"    OIL-COOLED    SINGLE- 
PHASE   TRANSFORMER. 

Core. — The  cores  to  be  built  up  with  laminated  iron  sheets 
of  high  permeability,  low  hysteretic  loss,  and  not  subject  to  ap- 
preciable magnetic  deterioration.  The  sheets  to  be  carefully 
annealed  and  insulated  from  each  other  in  order  to  reduce  eddy- 
current  losses. 

Windings. — The  primary  and  secondary  windings  to  be  thor- 
oughly insulated  from  each  other  and  from  the  core  and  frame, 
and  to  stand  a  potential  much  greater  than  the  rated  voltage  of 
the  transformer. 

Oil. — Each  transformer  to  have  sufficient  oil  to  cover  the  core 
and  winding  when  placed  in  the  tank.  The  oil  to  be  specially 
treated  and  refined  in  order  to  secure  good  insulating  qualities 
and  a  high  flashing-point. 

Terminals  and  Connections. — The  primary  and  secondary  leads 
to  be  carefully  insulated  and  taken  from  the  tank  through  por- 
celain bushings,  which  shall  have  sufficient  surface  to  prevent 
perceptible  leakage  to  the  frame  of  the  transformer. 

Performance. — After  a  run  of  twenty-four  hours  at  rated  load, 
voltage,  and  frequency  the  rise  in  temperature  of  any  part  of  the 
transformer  as  measured  by  thermometer,  and  of  the  coils  as 
measured  by  the  increase  in  resistance,  not  to  exceed  45°  C, 
provided  the  temperature  of  the  surrounding  air  is  not  greater 
than  25°  C.  and  the  conditions  of  ventilation  are  normal.  If 
the  temperature  of  the  surrounding  air  differs  from  25°  C.  the 
observed  rise  in  temperature  should  be  corrected  by  0,5  per  cent, 
for  each  degree. 

Insulation  between  the  primary  winding  and  the  core,  and  be- 
tween the  primary  and  secondary  windings,  to  stand  a  test  of 
140,000  volts  alternating-current  for  one  minute,  and  between 


TRANSFORMER  SPECIFICATIONS  263 

the  secondary  winding  and  the  core  a  test  of  10,000  volts  alter- 
nating current  for  the  same  length  of  time. 

The  transformer  to  carry  an  overload  of  50  per  cent,  for  two 
hours  without  undue  heating  of  any  of  the  parts. 

Every  manufacturer  has  his  own  particular  way  of  arranging 
transformer  specifications.  One  finds  it  suits  his  purpose  to 
give  but  a  general  description  while  another  will  sometimes  present 
useful  information  and  give  a  detailed  specification  covering  the 
complete  characteristics  of  the  transformer,  including  a  complete 
test  record  and  general  mechanical  and  electrical  description. 

One  of  the  best  specifications  and  one  of  great  interest  to  all 
operating  engineers  is  made  up  as  follows: 

Transforyner  Detailed  Specification.' — Form X X 

Tank Cribs Total  I^R per  cent.    IR 

H.T.   cable No long.   L.    T.  cable 

No. long.  H.T.  brushing  (terminal)  No L.T.  bush- 
ing (terminal)  No Winding Length Depth 

.......   Width. ......  Weight  of  coils  and  core  .......   Net 

weight  of  oil Weight  of  tank  and  cribs Total  weight 

Gallons  of  oil Steel  curve K.  V.  A Type 

Frequency Volts  ^.T Phase VoltsL.T. 

Amperes 

Iron  Core. — Steel End  irons X Iron  clusters 

per  leg Core  irons X Narrow   iron    clusters 

per  leg Corners Weight  of  core Window ..... 

X Volume   of   core Exciting   current Core 

section X and square    inches.     Length 

of  mag.  path Core  loss,  amperes Mag.  amperes 

per.  cent. 

H.  T.  Winding — Amperes Volts Turns Tap- 
outs No.  of  layers Sections  per  lag Insula- 
tion coil  to  core Insulation  between  layers Turns 

in  each  layer  per  section Length  of  section Space 

of  ends Space  between  sections Insulation  exten- 
sion  Space  around   core Size  of  conductor 

Diam.   of  conductor Lbs.  per  M.  ft Weight 

Thickness  of  coil Mean  turn Copper  density 

Resistance  (R) Volts  per  turn Max,  volts  per  layer 

/2/2 IR 

L.  T.  Winding. — Volts Amperes Taps No. 

of  layers Insulation   between  layers ......  Section    per 


264  STATIONARY  TRANSFORMERS 

leg Turns  in  each  layer  per  section Space  between 

sections Space  at  ends Diam.  of  conductor 

Space  around  core Length  of  sections Weight 

Insulation  extension Size  of  conductor Lbs.  per  M. 

ft Mean  turn Thickness  of  coil (R)  Resist- 
ance   Max.  volts  per  layer Copper  density 

Volts  per  turn IR im 

Like  all  customers'  specifications  these  two  are  not  complete 
as  they  do  not  specify  the  efficiency  and  regulation  (these  two 
important  factors  being  on  the  test  record  sheet  only);  the 
dielectric  test  of  the  oil;  the  temperature  of  the  water  necessary 
to  cool  the  oil;  the  method  of  supporting  the  transformer;  lifting 
the  transformer,  nor  the  method  employed  in  moving  the  trans- 
former whether  it  be  on  steel-rails,  a  four-wheel  truck  or  on  a 
racket-frame. 

The  general  characteristics  of  a  transformer  are  always  given 
in  the  test  record  sheets.  A  good  example  of  such  a  sheet  is 
given  below  and  is  for  a  high-voltage  power  transformer. 

TEST   RECORD   SHEET   FOR    HIGH-VOLTAGE    POWER 
TRANSFORMER  (SHELL  TYPE) 

1000     kw.,    25   cycle,    60,000-volt  shell-type,   single-phase 

transformer  (water  cooled). 
H.  T.  winding  30,000  60,000  volts;  L.T.  winding  2300  volts. 
H.  T.  amperes  16.66;  L.  T.  amperes  435. 
Heat  Run. — 

Run  for  8  hours  at  2300  volts  L.  T.,  and  18.5  amperes  H.  T. 

(a). 
Run  for  2  hours   at    2300  volts  L.  T,,  and  23.2  amperes 

H.  T.  (6). 
■Temperatures  (degrees  C.  at  end  of  run). — 

H.  T.  by  resistance  35.0  for  (a)  and  50.0  for  (6). 
L.  T.  by  resistance  37.0  for  (6) . 
Temperature  of  oil  18.0  for  (a)  and  23.5  for  (b). 
Temperature  of  water  leaving  the  transformer  10.0  for  (a) 

and  (6). 
Temperature  of  frame  of  transformer  12.0  for  (a)  and  16.5 

for  (b). 
Resistances. — 

H.  T.  resistance  at  25°  C.  is  1796,  and  for  (b)  is  21.32  ohms. 
L.  T.  resistance  at  25°  C.  is  0.0223  and  for  (b)  is  0.02545  ohms. 


TRANSFORMER  SPECIFICATIONS  265 

Insulation. — 

Voltage  applied  to  primary  and  secondary  and  core  for  one 
minute  is  120,000  volts. 

Voltage  applied  to  L.  T.  and  core  for  one  minute  is  5000 
volts. 

(Application  of  alternating  current). 

Efficiency. — 
At  125%  full-load,  guaranteed  eff.  98.0%  and  commercial  eff.  98.38%. 
At  100%  full-load,  guaranteed  eff.  97.8%  and  commercial  eff.  98.36%. 
At  75%  full-load,  guaranteed  eff.  97.4%  and  commercial  eff.  98. 11%. 
At  50%  full-load,  guaranteed  eff.  96.7%  and  commercial  eff.  96.93%. 
At  25%  full-load,  guaranteed  eff.  93.9%  and  commercial  eff.  94.52%. 
Regulation  (100  per  cent.  P.  F.). — 

Guaranteed  regulation  =  1.0  per  cent. 
Commercial  regulation  =  1.037  per  cent. 

General. — 

Core  loss  in  watts  =  7.335  watts. 

Excitation  in  amperes  =  14.3. 

Impedance  volts  =  1.653.     ((a)  =1.822  volts.) 

Impedance  watts  =  9.560.     ((a)  =11.720  watts.) 

Water  per  minute  =  2.6  gallons. 

(ingoing  water  25°  C). 

Detailed  Specifications. — 

Height  over  cover  =  135  in. 

Floor  space  =  110  in.  X59  in. 

Total  weight  (without  oil)  =30,000  lb. 

Gallons  of  oil  required  =  1300. 

Weight  of  oil  =  10,400  lb. 

Weight  of  tank  and  base  =  7500  lb. 

Weight  of  large  cover  =  2450  lb. 

Weight  of  small  cover  =  550  lb. 

Weight  of  cooling  coils  and  casing  =  2500  lb. 

Dimensions  of  coils  and  casing  =  70  in.  X37  in.  X32  in. 

Cooling  coil  (size  of  pipe)  =1.5  in. 

Length  of  cooling  coil  pipe  =  830  ft. 

Cooling  coil  pipe  dimensions  =  30  in.  X53  in.  X96  in. 

Weight  of  cooling  coil  =  2200  lb. 

Weight  of  iron  cover  =14,000  lb. 


266  STATIONARY  TRANSFORMERS 

TEST  RECORD  SHEET  FOR  HIGH-VOLTAGE  POV/ER 
TRANSFORMERS  (CORE  TYPE) 

200-kw.,   25   cycle,   57,500  volts  core  type,   water-cooled 

single-phase  transformer. 
H.  T.  winding  28,750,  57,500  volts;  L.  T.  winding  2300  volts. 
H.  T.  amperes  =  3.5;  L,  T.  amperes  =  87. 
Heat  Run. — 

Run  for  11  hours  at  2300  volts  L.  T.,  and  87  amperes  L.  T. 

current  (a). 
Run  for  2  hours  at  2300  volts  L.  T.,  and  130.5  amperes  L.  T. 

current  (6). 
Temperatures  (degrees  C.  at  end  of  run) . — 

H.  T.  by  resistance  30.0  for  (a)  and  49.5  for  (b). 
L.  T.  by  resistance  38.5  for  (6). 
Temperature  of  oil  21.5  for  (a)  and  28.0  for  (6). 
Temperature  at  top  of  frame  is  19.5  for  (a)  and  25.0  for  (6). 
Temperature  at  bottom  of  frame  is  9.5  for  (a)  and  12.5  for  (6), 
Room  temperature  for  (a)  is  18.5  and  for  (b)  17.5°  C. 
Resistance.— 

H.  T.  resistance  at  25°  C.  is  56.6  ohms  on  winding  connected 

for  28,750  volts. 
H,  T.  resistance  for  (6)  is  68.1  ohms. 
L.  T.  resistance  for  25°  C.  is  0.1168  ohms,  and  for  (b)  is 

0.1307  ohms. 
Insulation. — 

H.  T.  to  L.  T.  and  core  115,000  volts  alternating  current 

for  one  minute. 
L.  T.  and  core  10,000  volts  alternating  current  for  one  minute. 
Efficiency.-^ 

At  100%  load  guaranteed  eff.  96.7%  and  commercial  eff.  97.9%. 
At  75%  load  guaranteed  eff.  96.2%  and  commercial  eff.  97.8%. 
At  50%  load  guaranteed  eff.  95. 0%  and  commercial  eff.  96.8%. 
At    25%  load  guaranteed  eff.  91.2%  and  commercial  eff.  94.5%. 

Regulation  (100  per  cent.  P.  F.  =1.6  per  cent.). — 
General. 

Core  loss  in  watts  =2.865. 

Excitation  in  amperes  =10.3. 

Impedance  volts  (57,500  volt  winding)  =1.017. 

Impedance  watts  =1.750. 


TRANSFORMER  SPECIFICATIONS  267 

Detailed  Specifications. 

Height  over  all  =103  in. 

Floor  space  =47  in,  X64  in. 

Total  net  weight  (without  oil)  =  10,000  lb. 

Weight  of  oil  =3,000  lb. 

Gallons  of  oil  required  =150. 

H.  T.  voltage  taps  =57,500,  55,000,  47,500  and  45,000  volts. 
Up  to  the  present  time  natural-cooled  oil-insulated  single-phase 
transformers  have  been  built  in  sizes  of  3000  kv-a,  and  air-cooled 
transformers  up  to  4500  kv-a  at  33,000  volts. 

Comparing  the  various  types  of  European  and  American  made 
transformers  in  so  far  as  their  over-all  dimensions,  kilowatts  per 
square  foot,  kilowatts  per  cubic  foot,  cubic  foot  of  air  per  minute, 
gallons  of  oil  for  a  given  size,  etc.,  we  find  there  exists  quite  a 
difference.  For  instance,  taking  two  of  the  largest  sizes  made  in 
the  respective  countries,  we  have,  for  the  air-cooled  type: 

4000-KW.,  33,000-VOLT,  AIR-COOLED  SINGLE-PHASE 
TRANSFORMER 

(American  manufacture) 
(Dimensions,  90  in.  X74  in.  X137  in.  high) 

Kilowatts  per  square  foot 86 . 5 

Kilowatts  per  cubic  foot 7  6 

Cubic  feet  of  air  per  minute 6. 750 

Frequency 25 

1700-KV-A.,  6600- VOLT,   AIR-COOLED   (OIL  INSULATED)   THREE- 
PHASE  TRANSFORMER 

(European  manufacture) 
(Dimensions,  86  in.  X25  in.  X98  in.  high) 

Kilowatts  per  square  foot 55 

Kilowatts  per  cubic  foot 6.r 

Gallons  of  oil 640 

Gallons  per  kilowatt 0. 376 

Cubic  feet  of  air  per  minute 7 .  500 

Frequency 25 

The  European  type  referred  to  here  is  oil-insulated  and  cooled 
by  means  of  an  air  blast  at  the  outside  of  the  tank.  The  Ameri- 
can type  referred  to  here  is  commonly  known  as  the  air-blast 
transformer  and  is  cooled  by  forced  air  circulation  through  core 
and  coils. 


268  STATIONARY  TRANSFORMERS 

Also,  comparing  the  largest  water-cooled  oil-insulated  trans- 
former made  in  Europe  with  an  ordinary  4000  kw.  standard 
American  design  of  the  same  type,  we  have: 

4000-KW.,  33,000-VOLT,  OIL-INSULATED  WATER-COOLED 
SINGLE-PHASE  TRANSFORMER 

(American  manufacture) 
Dimensions,  107  in.  X63  in.  X150  in.  high) 

Kilowatts  per  square  foot 86 

Kilowatts  per  cubic  foot 6 .  85 

Gallons  of  oil 1950 

Gallons  per  kilowatt 0.49 

Full-load  efficiency 98.9  per  cent. 

Half -load  efficiency 98 . 5  per  cent. 

Gallons  of  water  per  minute 19 . 5 

Frequency 25 

5250-KV-A.,  45,000- VOLTS  OIL-INSULATED,  WATER-COOLED, 
THREE-PHASE  TRANSFORMER 

(European  manufacture) 
(Dimensions,  82  in.  X59  in.  X136  in.  high) 

Kilowatts  per  square  foot 162 

Kilowatts  per  cubic  foot 14.2 

Gallons  of  oil 1130 

Gallons  per  kilowatt 0. 215 

Efficiency  at  full-load 98 .  95  per  cent. 

Efficiency  at  50  per  cent,  load 98.85  per  cent. 

Regulation  (P.  F.  =  1.0) 0. 62  per  cent. 

Regulation  (P.  F.  =0.8) 3 . 0  per  cent. 

Frequency 50 

Transformers  of  a  much  greater  size  than  5,000  kv-a  at  45,000 
volts  have  not  yet  been  built  in  Europe.  In  American  single- 
phase  units  of  7500  kw.,  and  three-phase  units  of  14,000  kw, 
are  in  operation  at  voltages  above  100,000  volts. 

The  three  following  high-voltage  power  transformers  will 
serve  to  show  what  is  being  done  in  this  direction: 

7500-KW.,   60,000-VOLT,  OIL-INSULATED,   FORCED  OIL-COOLED, 
SHELL-TYPE  THREE-PHASE  TRANSFORMER 

Kilowatts  per  square  foot 80 

Kilowatts  per  cubic  foot 5.65 

Gallons  of  oil 4000 

Gallons  of  oil  per  kilowatt. 0.53 

Efficiency  at  full-load 98 .  95  per  cent. 

Weight  without  oil 42 . 5  tons. 

Frequency 25 


TRANSFORMER  SPECIFICATIONS  269 

5750-KW.,   138,500-VOLT,  OIL-INSULATED,  WATER-COOLED, 
SHELL-TYPE  SINGLE-PHASE  TRANSFORMER 

Kilowatts  per  square  foot 71 

Kilowatts  per  cubic  foot 5.3 

Gallons  of  oil 2500 

Gallons  of  oil  per  kilowatt  0.7 

Efficiency  at  full-load 98 . 8  per  cent. 

Efficiency  at  75  per  cent,  load 98.7  per  cent. 

Efficiency  at  50  per  cent,  load 98.3  per  cent. 

Efficiency  at  25  per  cent,  load 96.9  per  cent. 

Total  weight  in  tons 28 

Frequency 60 

Test  voltage 280,000  volts. 

(Length  of  high-voltage  winding  is  4  miles) 

10,000-KW.,  100,000-VOLT,  OIL-INSULATED,  FORCED  OIL-COOLED, 
SHELL-TYPE  THREE-PHASE  TRANSFORMER 

Kilowatts  per  square  foot 58 . 7 

Kilowatts  per  cubic  foot 3 .  25 

Gallons  of  oil 1500 

Gallons  of  oil  per  kilowatt 0.75 

Efficiency  at  full-load 99  per  cent. 

Weight  without  oil 60  tons. 

Frequency 60 

(The  primary  winding  (high-voltage  winding)  consists  of  10  miles  of  copper 

conductor) 

Practically  every  high-voltage  alternating-current  three-phase 
system  operating  at  55,000  volts  and  above  are  given  in  the 
table  "Modern  High-voltage  Power  Transformers  operating  at 
the  Present  Time."  The  transformer  connections  are  as  38  for 
star  against  21  for  delta  (the  star  connections  being  in  some  cases 
solid  grounded  and  in  others  grounded  through  a  high  resistance 
— while  the  delta  connections  are  all  insulated).  In  Chapter  IV 
several  important  advantages  and  disadvantages  are  given  for 
delta  and  star  connections,  in  looking  through  the  list  of  the 
highest  voltage  transformer  installations  practice  appears  to 
point  toward  the  star  connection. 


APPENDIX 


♦MODERN  HIGH  VOLTAGE  POWER  TRANSFORMERS  OPERA- 
TING AT  THE  PRESENT  TIME. 


Operating  systems 


§      I  °  S 

i!  £  as 

X I        «     C8     P 


1.  Sierra  and  San  Francisco 

2.  Power  Company 

3.  Eastern  Michigan  Power  Co.  . . . 

4.  Hydro-pjlectric  Power  Comm-n. 
Hydro-Electric  Power  Comm-n. 

5.  Mexican  Northern  Power  Co.  .  . 

6.  Great  Western  Power  Company. 
Great  Western  Power  Company. 

7.  Mississippi  River  Power  Co.  .  .  . 

8.  Grand  Rapids  Mich.  Power  Co. 

9.  Georgia  Power  Company 

10.  Truckee  River  G.  E.  Company.  . 

11.  Yadkin  River  Power  Company.  . 

12.  Great  Falls  Water  P.  &  T.  Co.. 

13.  Southern  Power  Company 

14.  Central  Colorado  Power  Co.  .  .  . 

15.  Tata  Hydro-Electric  Power  Co. . 

16.  No.  State  Hydro-Electric  Co.  .  . 

17.  Yadkin  River  Power  Company. . 

18.  Shawinigan  Power  Company. . . . 
Shawinigan  Power  Company. . . . 

19.  Central  Colorado  P.  Company.. 

20.  Rio  de  Janeiro  L.  &  P.  Co 

21.  Appalachian  Power  Company. . . 
Appalachian  Power  Company. . . 

22.  Sao  Paulo  Electric  Company.  .  . 

23.  Tata  Hydro-Electric  Company.. 

24.  Mexican  L.  &  P.  Co.  Ltd 

Mexican  L.  &  P.  Co.  Ltd 

25.  Madison  Riven  Power  Company 

26.  Utah  Light  &  Power  Company  . 

27.  Butte  Elect.  L.  &  P.  Company  . , 

28.  Telluride  Power  Company 

29.  Katsura-Gawa  Hydro-Elect.  Co. 

30.  Southern  Calif.  Edison  Co 

31.  Pennsylvania  W.  &  Power  Co  . . 


3,750 

Star. . . 

60 

2,233 

Star. . . 

60 

3.000 

Delta  . 

60 

1,250 

Delta  . 

25 

.750 

Delta  . 

25 

2,500 

Star. . . 

60 

10.000 

Delta  . 

60 

5,000 

Delta  . 

60 

9,000 

Star... 

25 

3,750 

Delta  . 

60 

3,333 

Star... 

60 

1,000 

Star. . . 

60 

6,250 

Star. . . 

60 

2,400 

Delta  . 

60 

3,000 

Delta  . 

60 

3,333 

Star... 

60 

3,333 

Star. . . 

60 

2,750 

Star. . . 

60 

2,500 

Star. . . 

60 

14,000 

Delta  . 

60 

12,000 

Delta  . 

60 

2,500 

Delta  . 

60 

2,000 

Star. . . 

60 

6,000 

Delta  . 

60 

1,500 

Delta  . 

60 

1,500 

Star. . 

60 

3,120 

Star. . . 

60 

6,000 

Star. . . 

60 

5,600 

Star. . . 

60 

900 

Delta  . 

60 

333 

Delta  . 

60 

333 

Delta  . 

60 

1,500 

Star. . . 

60 

3,500 

Star. . . 

50 

1.667 

Star. . . 

50 

10,000 

Star. . . 

3 

25 

140,000 
104.000 
140.000 
110,000 
110,000 
110.000 
110.000 
90.000 
110.000 
1 10,000 
110,000 
104,000 
104,000 
102,000 
101.200 
100,000 
100,000 
100,000 
100,000 
100.000 
85,000 
90,000 
88.000 
88.000 
85.000 
88,000 
85,000 
85,000 
81,000 
80.000 
80.000 
80.000 
80.000 
77.000 
75.000 
70.000 


•The  connection  of  systems  given  here  is  not  strictly  correct  «is  changes  from  delta 
to  star  and  from  star  to  delta  are  constantly  being  made  to  suit  new  conditions. 

t  This  denotes  single  or  three-phase  transformer — the  systems  themselves  in  all  the 
above  cases  being  three-phase. 

270 


APPENDIX 


271 


MODERN  HIGH  VOLTAGE  POWER  TRANSFORMERS  OPERA- 
TING AT  THE  PRESENT  TIME.— (Continued.) 


Operating  systems 


32.  Missouri  River  Power  Co 

33.  Southern  Wisconsin  Power  Co.  . 

34.  Kern  River  Power  Company. . . . 

35.  Northern  Calif.  Power  Co 

36.  Yakima  Valley  Power  Company 

37.  Central  Georgia  Power  Co 

38.  Northern  Hydro-Electric  Co 

39.  Eastern  Tennessee  Power  Co. .  . 

40.  Idaho-Oregon  L.  &  P.  Company 

41.  Spokane  &   Inland  E.  R.  Co  . . . 

42.  Nagoya  Electric  Power  Co 

43.  Toronto  Power  Company , 

44.  Washington  Water  Power  Co.  .  . 

45.  Mexican  L.  &  P.  Co.  Ltd 

46.  East-Creek  L.  &  P.  Company. . . 

47.  Great  Northern  Power  Co 

48.  Niagara-Falls  Power  Company. 

49.  Pacific  Coast  &  Electric  Co 

50.  Guanajuato  Power  &  E.  Co.  .  .  . 

51.  Jhelum  River  Electric  Co 

52.  Michiacan  Power  Company.  .  .  . 

53.  Elect.  Development  Company. . 
61.  Puget^Sound  Power  Company. . 

55.  Canadian-Niagara  Power  Co 

50.  Portland  L.  &  P.  Company 

57.  Calif.  Gas  &  Electric  Co 

58.  Pacific  Coast  Power  Company . . 
69.  Winnipeg  L.  &  P.  Company. . .  . 
60. 


Transformer 
kilowatt 
capacity 

§0 

"  IS 
0   5. 

1,500 

Star. . . 

1,000 

Delta  . 

750 

Star. . . 

4,000 

Star. . . 

1,000 

Star. . . 

2,500 

Star. . . 

1,100 

Star. . . 

1.100 

Star. . . 

750 

Delta  . 

1,500 

Star... 

1,000 

Star. . . 

6,000 

Star  . . 

2,200 

Star  . . 

2,000 

Star. . . 

2,800 

Delta  . 

3,000 

Delta  . 

1,750 

Delta  . 

1.750 

Star... 

1,000 

Star. . . 

1.000 

Delta  . 

1.300 

Star. . . 

2.670 

Delta  . 

2,333 

Star. . . 

1,250 

Star... 

3,367 

Star. . . 

849 

Star. . . 

3,333 
1,800 

Star. . . 
Delta  . 

a  .    a 


60 

60 
50 
60 
60 
60 
25 
60 
60 
25&60 
GO 
25 
60 
60 
25 
25 
60 
60 
60 
25 
60 
25 
60 
26 
60 
60 
60 
60 


u     ^  O 

O  M  V 

"S  *  to 

O  —  >> 

«  o  « 


70,000 

70,000 
67,500 
66,000 
66,000 
66,000 
66,000 
66.000 
66,000 
66,000 
50,000 
60,000 
60,000 
60,000 
60,000 
60,000 
60.000 
60,000 
60,000 
60,000 
60,000 
60,000 
60,000 
67,000 
57,000 
55,000 
55,000 
65,000 


The  subject  of  transformers  cannot  very  well  be  concluded 
without  a  reference  to  the  effects  of  altitude  on  their  operation. 
It  is  deemed  safe  to  say  that  not  one  of  the  above  mentioned 
systems  took  this  effect  of  altitude  into  consideration  when 
specifying  their  system  requirements,  yet  each  and  all  were 
careful  to  note  that  the  common  every  day  specifications  and 
tests  were  complied  with. 

With  the  exception  of  water-cooled  oil  transformers,  manu- 
facturers should  specify  the  temperature  rise  and  efficiency  of 
transformers  at  service-altitudes.  This  is  very  important  for 
the  reason  that  insulation,  temperature  and  efficiency  values 
are  quite  different  at  high  altitudes  to  those  at  sea  level.  For 
example,  at  an  altitude  of  3,500  ft.  above  sea  level  a  higher 
kv-a  rating  should  be  allowed  a  given  unit  and,  when  a  trans- 


272  APPENDIX 

former  is  rated  for  operation  at  this  altitude,  the  normal  per- 
missible temperature  rise  should  be  reduced  by  approximately 
1  per  cent,  for  every  additional  350-ft.  rise  at  which  it  is  put 
into  service,  that  is  to  say:  at  an  altitude  of  10,500  ft.  the  per- 
permissible  temperature  rise  would  be  approximately  10,500 
•V- 350  =30  per  cent.  LESS,  thus  we  see  that  for  higher  altitudes 
a  given  transformer  will  have  a  different  rating  for  a  given 
service. 


INDEX 


Ability  of  a  transformer  to  deliver      Centralized  system  over  200,000  kw., 
current  at  a  constant  volt-  3 

age,  16 

Admittance,  31,  32 

Advantage    of    the    delta-delta    to 
delta-delta,  74,  75 
delta-star  to  star-delta  system, 
74,  75 

Advantages  of  iron  and  air  reactance 
coils,  159 

Aging  of  the  iron,  11,  15 

Air  and  iron  reactance  coils,  159 

Air-blast  transformers,  7,  120,  144 

Air-chambers  for  transformers,  144 

Air-cooling  of  transformers,  120-122 

All-day  efficiency,  14,  15 

Alloy  steel  in  transformers,  11,  246 

Alternating  currents  dangerous  and 
impracticable,  3 
fought  in  the  Law  Courts,  3 

American  and  European  engineers, 
79 

American  I.  E.  E.,  239 

Amount    of    heat    developed    in    a 
transformer,  6 
hysteresis  in  a  given  steel,  8 

Anhydrous  copper  sulphate,  132 

Arc-series  lighting,  178-185 

Assembly  of  large  power  transform- 
ers, 136-148 

Auto-transformers  and  transforma- 
tion, 33,  170-177 

Automatic  regulators,  224-226 


Balancing  transformer,  26,  27 

Best  shape  of  transformer  core,  11 

Best  operated  system,  74 

Blotting  paper,  133 

Breathing  action,  125 

Building  of  fire-proof  construction,  8 

Capacity  in  kw.,  3,  52 
Causes  of  transformer  failure,  145, 
154 


Central  station  engineers  and  man- 
agers, 153 

Cheap    copper    space    and    alloyed 
iron,  153 

Cheapest  cost  of  system,  74 

Changing  of  frequency  (using  trans- 
formers), 83 

Change  any  polyphase  system  into 
any  other  system,  35 

Chief  danger  of  fire,  8 

Choice  of  transformer  system  con- 
nections, 70,  74 

Cleaning    of    transformer    cooling- 
coils,  125 

Close  regulation,  156 

Coefficients  of  resistivity  in  copper 
—Table,  240 

Comparison  of  shell  and  ore  type 
transformers,  150-153 

Comparison    of     single-phase     and 
polyphase  transformers,  43 

Comparative  weights  of  transform- 
ers, 42 

Commercial  manufacture  of  175,000 
volt  power  transformers,  3 

Common  return  wire,  32,  39,  49 

Combination     method     of     cooling 
transformers,  122 

Compensators,  218-220 

Connections    for    grounding    three- 
phase  transformers,  81 

Connections    for     grounding     two- 
phase  transformers,  39 

Consolidation  and  concentration  of 
systems,  158 

Constant  current  transformers,  14, 
178,  185 
potential  transformers,  4,  etc. 

Construction  of  large  power  trans- 
formers, 136  144 
of  constant  current  transform- 
ers, 182-184 


18 


273 


274 


INDEX 


Contact-making  voltmeter,  224-226 
Control  of  the  designer,  9 
Conversion  of  one  polyphase  system 

into  another,  20 
Conventional  connections  for  trans- 
formers, 56 
Cooling  of  transformers,  6,  117-130 
Cooling-coil  cleansing,  125 
Cooling  medium,  153 
Copper  or  I^  R  loss  in  transformers, 

9,  16,  250-252 
Cost  of  a  given  volume  and  area,  9,11 
Core  of  the  transformer  for  a  given 

service,  5,  75,  153 
loss  or  iron  loss,  8,  11,  14,  245- 

248 
type  transformers,  10,  24,  125, 

136, 137-139,  150-153,  158, 

262 
Cost  of  total  losses,  6 
Current,  short-circuit,  154,  156,  257 
transformers,  186-208 

Dangerous  and   impracticable  cur- 
rent, 3 
'Dead,"  short-circuit,  154 
Dear    copper    space    and    ordinary 

iron,  153 
Delta-connected  systems,  42,  53 
-star  systems,  47,  53,  73 
-star  merits,  53,  73 
-delta  systems,  47,  54,  73 
-delta  merits,  48,  53,  73 
Demerits  of  the  delta-delta  system, 

74-75 
-Design  of  oil-insulated  transformers, 

118 
Determination  of  temperature  rise,  7 
Development  of  transformers,  2 

of  the  art  of  transformer   con- 
struction, 1 
Diametrical  system,  116 
Difference  of  potential,  34 

of  opinion  as  regards  grounding, 
28 
Difficulties  of  three-phase  operation, 

84-96 
Different  ways  of   applying   trans- 
formers, 22 


Disadvantage    of     the    delta-delta 
system,  74,  75 
of  the  "T"  (two  transformer) 
system,  80 
Disc-shape  coils,  129 
Distribution  transformers,  28 
Disturbed  system  due  to  incoming 

surges,  75 
Dividing    each    secondary    coil  of 

transformers,  24 
Double-delta  system,  109,  113,  116 
-star  system,  109,  114,  116 
-tee,  system,  114,  116 
Drop  due  to  load,  31,  32 
Drying  of  insulation,  145 

out  of  power  transformers,  146- 
148 
Duration  of  tests,  13 

Early  development  of  transformers, 
1 

Earth  connections,  163 

Earthing  of  the  neutral  of  trans- 
formers, 161 

Economy  of  copper,  30 

Eddy-current  loss,  8,  245-247 

Edison,  Thos.  A.,  three-wire  system, 
51 

Effect  of  various  iron  substances,  1 1 

Efficiency  of  transformers,  14,  16, 
153,  252,  253 

Electrical  characteristics  of  a  trans- 
former, 5 

Electro-magnetic  properties  of  alloy- 
steel,  11 

Electro-static  capacity  of  parts  too 
high,  95 

Equal  output  and  change  in  copper 
loss,  9 

Engines,  3 

Exciting  current,  9,  10 

External  and  internal  choke-coils,  159 

Factory,  transformers  from  the,  26 
Faraday's  historic  experiments,  1 
Favor  of  the  shell-type  transformer, 

152 
of   the   core-type   transformer, 

152 


INDEX 


275 


Feeder-regulators,  209-220 
Ferranti's  S.  Z.  de.,  modification  of 

Varley's  method,  1 
Filter-paper,  125 

Fire-risks  of  air-blast  transformers,  7 
Five-wire  two-phase  system,  34 
Fluid  of  some   impregnating   com- 
pounds, 12 
Fluxes  (magnetic)  in  transformers,  42 
Forced  current  of  air-cooling,  120 

current  of  water-cooling,  122 

oil  circulation,  127 
Form  of  transformer  coil,  9 
Four-wire  two-phase  system,  30,  33 
Freezing  of  water,  124 
Frequency    changer    (using    trans- 
formers), 83 
Fundamental  equations  in  design,  13 

principals,  3 
Fused-switches,  169 

General  construction,  260 

Generators,  3 

Generating  and  receiving  stations, 

144 
Governing  factors  of  systems,  74 
Grading  of   insulation  on  the   end 

turns,  151 
Graphical  methods,  17, 23,  40,  43,  44, 

46,  53,  111 
Greater   coal   consumption   due   to 

exciting  current,  9 
generating   station   equipment, 

10 
Ground  connections,  163-165 
Grounded  systems,  28,  37,  29,  74, 

81-82,  84,  161 
Grounding  of  the  neutral  point,  39, 

74,  76,  81,  161 

Heat  test  of  transformers,  232,  233 
High  frequency  currents,  159 

voltage  operation  of  transform- 
ers, 2 
stresses,  76,  79,  86 
surges,  74,  75 
transformer  troubles,  94 
installations,   125,   136-144 
specifications,  258,  267 


History  of  alternating  currents,  3 
of  delta  and  star  systems,  3 
of     50,000     and     60,000     volt 
systems,  3 
Hourly  temperature  readings,  153 
Hydrochloric  acid-cleaning  of  coils, 

125 
Hysteresis,  8,  10,  245-248 
loss,  8 

I  R  drop,  18,  19,  67,  91 
12  R  loss,  9,  16,  20 
Incoming  surges,  75 
Increased     hysteresis     and     higher 
temperatures,  9 
temperatures   due   to   excessive 
iron  losses,  9 
Inductive  load  on  transformers,    10, 
17 
reactance  (XJ,  18 
Inherent  reactance,  154 
Impedence  (Z),  19,  24,  31,  67,  91, 

250-252 
Important  advantages  of  the  delta- 
star  to  star-delta,  74,  75 
factors   in   the    make-up    of    a 
transformer,  8 
Impregnating  of  transformer  coils, 

11 
Improper     drying     out     of     trans- 
formers, 95 
Impulses  from  transmission  line,  75 
Installation  of  large  power   trans- 
formers, 144—148 
Instantaneous  values  of  the  currents, 

40,  47 
Insulation,  11,  117,  227,  228 

specification,  259 
Internal  and  external  choke-coils, 

59 
Iron  and  air  reactance  coils,  159 

or  core  loss,  8,  9,  11,  14,  245-248 

Joints  of  ground  wire,  162,  164 

Kirchhoff's  law,  44 
Kv-a  capacity  of  transformers,  3,  52 
K-w  capacity  of  transformers,  69,  74, 
80 


276 


INDEX 


Lamps,  arc  and  incandescent,  178- 
185 

Large     commercial     power     trans- 
formers, generators,  etc.,  3 

Law  courts  and  alternating  currents, 
3 

Leakage    reactance    of    the    trans- 
former, 154 

Least  potential  strain  on  system,  74 

Liberal  oil  ducts  between  the  vari- 
ous parts,  6 

Lighting  transformers,  31 

Limiting  feature  of  transmission,  2 
resistance,  163 

Limit  of  temperature  rise  in  trans- 
formers, 6 

Line-drop  compensator,  221-225 

Long-distance  transmission  lines,  151 

Losses,  8,  79 

Loss  due  to  magnetic  leakage,  10 
to  magnetizing  current,  10 
in  revenue  due  to  transformer 
failure,  6 

Low  average  operating  temperature, 
6 

Lowering  the  frequency  of  supply,  9, 
83 

Lowest  price  for  transformers,  74 

Magnetic  densities  of  transformers, 
14 
leakage,  16 

Magnetizing  currents  in  transform- 
ers, 11 

Mechanical  failure  of  transformers, 
76,  152,  153,  155,  160 

Mercury    thermometers    for    tem- 
perature readings,  147 

Merits  of  the  delta-star  to  star-delta 
system,  74,  75 
of  three-phase  units,  43 

Method  of  connecting   three-phase 
systems,  42 
two-phase  systems,  30,  33 
of  insulating  transformers,  11 

Methods    of    cooling    transformers, 
117-130 

Meyer  and  Steinmetz   systems  the 
same  thing,  106  (Fig.  101  A) 


Modern  high  voltage  power  trans- 
formers, 270,  271 

Moving  of  coils  and  core,  94,  154, 
160 

Motor  auto-starters,  219,  220 

National    Board    of    Fire    Under- 
writers, 227 
National  Electrical  Code,  28 
Negative  direction,  40,  56,  244,  245 
Neutral  point,  39,  49,  76,  81,  86, 161 

Ohm's  Law,  248,  252 

Ohmic  drop,  16,  42 

Oil  for  transformers,  127,  130-135 
-filled  self-cooled  transformers,  7 
transformers  in  separate  com- 
partments, 8,  144 

Open-delta  "V"  system,  51,  52,  53, 
72 

Operation  of  transformers,  153-169, 
178-184 

Operating  at  the  end  of  long  lines,  1 1 
engineer's  difficulties,  64 

Operation  of  constant  current  trans- 
formers, 178-185 

Opposition-test,  236 

Over-potential  test,  229 

Parallel  operation,  22,  38,  56,  64,  66, 

78,  91,  239 
Phase  relations,  22,  59,  68,  74,  87 
Phase-splitting  methods,  21 
Points    in    the    selection    of    trans- 
formers, 5 
Polarity  of  transformers,  55,  58,  59- 

64,  243-245 
Polyphase  regulators,  220-226 
Positive  direction,  40,  56,  244-245 
Power  (P)  or  electrical  energy,  31 
factor,  10,  16,  19,  22,  203-204 
limiting    capabilities    of   react- 
ance, 158 
transformers,   43,   56,   66,   123, 
145,  153,  267-271 
Practicable  50,000  and  60,000  volt 

systems,  3 
Primary  windings  of  transformers, 
with  R  and  X.,  5 


INDEX 


277 


Principal   argument   for   grounding 

transformers,  28 
Puncturing  of  the  insulation  between 

turns,  94,  117 

Raising  current,  205 
Ratio  of  high  voltage  to  low  voltage 
turns,  65,  67 
of  iron  and  copper  loss,  5 
of  transformation,  65,  67,  239- 
241 
Reactance,   internal    and    external, 

154,  160 
Recognized  commercial  operation  of 

60,000  volts,  3 
Receiving  station  transformers,  74 
Record  sheet  of  tests,  264-269 
Regulation,  10,  16,  22,  155,  223,  253- 

256 
Regulators  and  compensators,  209, 

226 
Relays    for    protection    of     trans- 
formers, 165-167 
Reliability  of  transformers  in  service, 

80,  151,  154 
Resistance  (R),  18,  41,  248-250 
per  phase,  31 
of  wiring,  31 
Revenue  effected  imperfect  iron  of  a 
low  grade,  1 1 
loss  due  to  transformer  failure,  6 
Roasting  of   oils   due  to  over-load, 
154 

Safety  to  life  and  property,  5,  154 
Salt  for  the  earth  connections,  165 
Scott,  Chas.  F.,  system,  53,  80,  98, 

106 
Secure  the  desired  copper  loss,  9 
Self-cooling   transformers,    117-120, 

144 
induction,  18 
Short-circuits,  28 

-circuit  stresses,  154,  156,  257 
Shell  type  transformer,  2,  10,  73,  79, 

128,  139-144,  260 
Series  enclosed  arc  lighting,  178-180 
lighting  from  constant  current 

transformers,  205 


Series-pai'allel  operation,  152 
step-up  transformer,  205 
transformers,  186-208 
Simple  transformer  manipulations,22 
Single-phase  systems,  22,  42,  83 

from  three-phase,  82,  83 
Six-phase  transformation  and  opera- 
tion, 109-116 
Solid  compounds  for  impregnation 
of  windings,  11 
insulation,  11 
Spark-gap— Table,  228 
Specifications  of  transformers,  258- 

270 
Star  or  "Y"  system,  41-53 

-delta  system,  47,  53,  73,  74 
merits,  47,  73,  74 
-star  system,  47,  53,  55 
versus  delta,  71,  73,  74 
Station  equipment  and  transmission 

lines  greater,  10 
Standard  rules  of  the  A.  I.  E.  E., 
239 
voltage  test,  231 
Steam  turbines  of  40,000  h.p.   ca- 
pacity, 3 
Steinmetz,   Chas.   P.,   system,    100, 

106 
Step-up  current  transformers,  205 
-down  transformers,  4 
-up  transformers,  4,  23 
Strain  between  high  and  low  voltage 

windings,  27 
Stillwell,  Lewis  B.,  regulator,  210 
Surges,  75,  159,  163 
System  giving  cheapest  cost,  74 
Switches,  76,  165 

Switching  and  its  advantages,   76, 
165,  109-116 

Taylor,  William  T.,  system,  37,  71, 

80,  106,  255 
"T"  two-transformer  system,  37,  53, 
71,  80,  98 
three-transformer    system,    37, 
71,  80 
Telephone  transformers,  206 
Temperature  rise  of  the  oil,  128 
of  electrical  apparatus,  7,  147 


278 


INDEX 


Temperatures,   123,   125,   128,   152, 

232-239 
Terminals  and  connections,  262 
Test  record  sheets,  264-267 
Testing  cooling  coils  for  transform- 
ers, 146 
Tests    specified    by    the     National 
Board  of  Fire  Underwriters, 
12 
of  copper  loss  and  impedence, 

250-252 
of  efficiency,  252,  253 
of  iron  or  core  loss,  245-252 
of  insulation,  13,  227-232 
of  polarity,  243-245 
of  ratio  of  transformation,  239- 

243 
of  regulation,  253-256 
of  resistance   and  I   R.,    248- 

250 
of  short-circuits,  257 
of  temperature,  232-239 
Third  harmonics,  75 
Three-phase  systems,  22,  39,  53 
to  single-phase,  82,  104,  105 
to  six-phase,  109-116 
to  two-phase,  53,  97-109 
two-phase  methods,  107,  109 
group  of  18,000  kw.,  3 
Three-wire  service  transformers,  24, 
26 
two-phase  systems,  30,  33 
Time-limit  relays,  169 

-phase,  40 
To  secure  the  desired  copper  loss,  9 
Tra,nsmis8ion  engineers,  153 
Transformer  development,  1 
of  14,000  kw  capacity,  3 
regulation,  10,  16,  17 
Transformers  of  identical  character- 
istics, 22 
in  separate  compartments,  8 
Troubles  experienced  with  high  volt- 
age transformers,  94 
Turbines,  3 

Turbo-generators  of  30,000  kw.,  3 
Two-phase  systems,  22,  30,  33 
to  three-phase,  22,  53 
three,  four  and  five  wire,  34 


Two-phase, to  single-phase,  35,  36 
multi-wire  distribution,  36 
parallel  combinations,  38 
three-phase  methods,  107,  109 

Unbalancing,  32,  52,  68,  75,  85 
Unduly  moist  transformers,  145 
Unlimited  power  behind  transform- 
ers, 156 
Use  of  reactance,  internal  and  ex- 
ternal, 154 
of  resistance  in  the  neutral  of 
grounded  systems,  154 
Useful  energy  delivered,  9 

Vacuum  process  of  impregnation,  11 

Varley's  method,  1 

"V"  or  open-delta  system,  42,  51, 

53,  72 
Variation  of  core  loss,  248 

of  copper  loss,  251 
Vector  representation,  17,  30,  33,  40, 

44,  46,  53,  116 
Viscosity,  130,  132 
Voltage  compensator,  221-224 
Voltmeter — contact-making,  224, 225 

Water  available  and  not  expensive,  7 

-cooled    transformers,    7,     122, 
144,  258,  261 

-freezing  difficulties,  124 

-wheels,  3 
Wattmeter,  203,  204,  207 
Watts  radiated  per  square  inch  of 

surface,  119 
Weak  link  in  the  insulation,  152 

mechanically,  transformers,  154 
Weight,  comparative,  42,  79 
Windings,  specifications,  261,  262 

Xg  or  inductive  reactance,  18 

Y  or  admittance,  31 

"Y"  or  star  connection,  41 

three-phase  to   two-phase  sys- 
tem, 98 

"Z"  (series  transformer)  connection, 
200,  201 


L