<n-vvxv. Jj
A TREATISE
MASONRY COflSTRUCTIO
BY
IEA O. BAKEB, 0. E.,
PROFESSOR OF CIVIL ENGINEERING, UNIVERSITY OF ILLINOIS.
THIRD AND REVISED EDITION.
NEW YORK:
JOHN WILEY & SONS,
53 EAST TENTH STKEET.
1890.
ORUMMOMD ft Mw»
1 to 7 HHPMI BtrMt,
Nuw York,
PKEFACE.
THE present volume is an outgrowth of the needs of the author's
own class-room. The matter is essentially that presented to his
classes for a number of years past., a considerable part having been
used in the form of a blue-print manuscript text-book. It is now
published for the greater convenience of his own students., and with
the hope that it may be useful to others. The author knows of no
work which treats of any considerable part of the field covered by
this volume. Nearly all of the matter is believed to be entirely new.
The object has been to develop principles and methods and to
give such examples as illustrate them, rather than to accumulate
details or to describe individual structures. The underlying prin-
ciples of ordinary practice are explained ; and, where needed, ways
are pointed out whereby it may be improved. The common theo-
ries are compared with the results of actual practice ; and only
those are recommended which have been verified by experiments
or experience, since true theory and good practice are always
in accord. The author has had the benefit of suggestions and
advice from practical masons and engineers, and believes that the
information here presented is reliable, and that the examples cited
represent good practice. The general prices are the average of a
large number actually paid ; tuid the special prices are representa-
tive. The structures illustrated are actual ones. The accredited
illustrations are from well-authenticated copies of working-drawings,
and are presented without any modification whatever ; while those
not accredited are representative of practice so common that a single
name could not properly be attached.
In the preparation of the book the endeavor has been to observe
a logical order and a due proportion between different parts. Great
care has been, taken in classifying and arranging the matter. It
will be helpful to the reader to notice that the volume is divided
successively into parts, chapters, articles, sections having small-cap-
ital black-face side-heads, sections having lower-case black-face wide-
heads, sections having lower-case italic side-heads, and sections hav-
ing simply the serial number. In some cases the major subdivis-
iii
PREFACE.
ions of the sections are indicated by small numerals. The constant
aim has been to present the subject clearly and concisely.
Every precaution has been taken to present the work in a form
for convenient practical use and ready reference. Numerous cross
references are given by section number ; and whenever a figure or a
table is mentioned, the citation is accompanied by the number of
the page on which it may be found. The table of contents shows
the general scope of the book ; the running title assists in finding
the different parts ; and a very full index makes everything in the
book easy of access. There are also a number of helps for the
student, which the experienced teacher will not fail to recognize
and appreciate.
Although the book has been specially arranged for engineering
and architectural students, it is hoped that the information con-
cerning the strengths of the materials, the data for facilitating the
making of estimates, the plans, the tables of dimensions, and the
costs of actual structures, will prove useful to the man of experience.
Considering the large amount of practical details presented and
the great difference in the methods employed by various construc-
tors, it is probable that practical men will find much to criticise.
The views here expressed are, however, the results of observation
throughout the entire country, and of consultation and correspond-
ence with many prominent and practical men, and represent average
good practice. The experienced engineer may possibly also feel
that some subjects should have been treated more fully ; but it is
neither wise nor possible to give in a single volume minute details.
These belong to technical journals, proceedings of societies, and
special reports of particular work.
No pains have been spared in verifying data and checking re-
sults. The tables of cubic contents have been computed by differ-
ent processes by at least two persons, and to at least one more place
than is recorded. Should any error, either of printer or author,
be discovered — as is very possible in a work of so much detail,
despite the great care used,— the writer will be greatly obliged by
prompt notification of the same.
The author gratefully acknowledges his indebtedness to many
engineers for advice and data, and to his former pupil and present
co-laborer, Prof. A. 1ST. Talbot, for many valuable suggestions.
CHAMPAIGN, ILL., July 9, 1889.
TABLE OF CONTENTS.
PART I. THE MATERIALS.
PAGE
CHAPTER I. NATURAL STONE.
INTRODUCTION 1
ART. 1. REQUISITES FOR GOOD BUILDING STONE 8
AJIT. 2. TESTING BUILDING STONE 5
Strength. Crushing Strength : form and size of specimen, cushion,
results. Transverse Strength: methods and results. Elasticity.
Hardness and Toughness. Bibliography 6
Durability. Destructive Agents : mechanical, chemical. Resisting
Agents : chemical composition, physical structure, seasoning. Meth-
ods of Testing Durability : absorptive power, methods and results ;
effect of frost, methods and results ; effect of atmosphere, methods
and results. Methods of Preserving 14
ART. 3. CLASSIFICATION AND DESCRIPTION OF BUILDING STONES. . . S3
Classification : geological, chemical, physical. Description of Trap,
Granite, Marble, Limestone, and Sandstone. Location of Quarries.
Weight of Stone.
CHAPTER II. BRICK.
Process of manufacture. Classification. Requisites for good Brick.
Methods of Testing : absorbing power, transverse strength, crushing
strength ; results. Size. Cost 88
CHAPTER III. LIME AND CEMENT.
CLASSIFICATION 48
ART. 1. COMMON LIME 48
Methods of manufacturing, testing, and pressing. Cost.
ART. 2. HYDRAULIC LIME 50
.ART. 3. HYDRAULIC CEMENT 52
Classification. Description : Portland, Rosendale, Pozzuolana.
ART. 4. METHODS OF TESTING HYDRAULIC CEMENT11 56
Color, Weight, Activity, Soundness, Fineness, Strength. Cost.
ART. 5. SPECIFICATIONS FOR CEMENT 67
German. French. Austrian. English. American.
v
• TABLE OF COXTEKTS.
PABT II PEEPARING AND USING THE MATERI^
CHAPTER IV. MORTAR, CONCRETE, AND ARTIFICIAL STO1
ART. 1. MOBTAR
Sand : requisites, testing, weight, cost. Liine Mortar : preparatl<
and proportions. Cement Mortar : preparation and proportion
Grout. Data for Estimates. Strength of Mortar: tensile, — vari
with age, of various proportions, effect of lime ; compressive ; adii
sive. Cost. Mortar impervious to -water. Sugar in mortar. Free
ing. Change of volume in setting.
ART. 2. CONCKETE
Ingredients. Proportions. Mixing. Laying. Strength. Cost.
ART. 3. ARTIFICIAL STONE
Portland. McMurtrie. Frear. Ransome. Sorel.
CHAPTER Y. QUARRYING.
Methods of Quarrying : by hand tools ; by explosives,— the drill!
the explosives ; by channeling and wedging
CHAPTER VI. STOKE CUTTING.
ART, 1. TOOLS
Eighteen hand tools illustrated and described. Machine tools cL<
scribed.
ART. 2. METHODS OF FORMING THE SURFACES
Four methods illustrated and described.
ART. 3. METHODS OF FINISHING THE SURFACES
Eight methods illustrated and described.
CHAPTER VII. 'STONE MASONRY.
Definitions : parts of the wall, kinds of masonry. Ashlar Masonry
dressing, bond, backing, pointing, mortar required, when employee:
specifications. Squared-stone Masonry : description, uiortar require cj
specifications. Bubble Masonry : description, mortar required, who;
employed, specifications. Slope-wall Masonry. Stone Paving. Rij:
rap. Strength of Stone Masonry : examples, safe pressure. Meat*
urement of masonry. Cost: quarrying, dressing, price of stone
examples— U. S. public buildings, railroads, tunnels, bridge piers
arch culverts ; summary
CHAPTER VIII. BRICK MASONRY.
Mortar. Bond. Compressive Strength: results of experiments
safe pressure. Transverse Strength: strain on lintel. Measuremeii
of Brick-work. Data for Estimates : brick, labor, mortar required
Cost. Specifications : for buildings, sewers, arches. Brick vs. Stem
Masonry. Brick Masonry Impervious to Water. Efflorescence. .
TABLE OF CONTENTS. Til
PART III. FOUNDATIONS.
PAGE
CHAPTER IX. INTRODUCTORY.
DEFINITIONS, AND PLAN OF PROPOSED DISCUSSION 183
CHAPTER X. ORDINARY FOUNDATIONS.
OUTLINE OF CONTENTS 186
ART. 1. THE SOIL 186
Examination of the Site. Bearing power of Soils : rock, clay, sand,
semi-liquid soils ; summary. Methods of Improving Bearing Power :
increasing depth, drainage, springs, consolidating the soil, sand piles,
layers of sand.
ART. 2. DESIGNING THE FOOTINGS 199
Load to be Supported. Area Required. Center of Pressure and
Center of Base. Independent Piers. Effect of Wind. Offsets for
Masonry Footings. Timber Footings. Steel-rail Footings. Inverted
Arches.
ART. 8'. PREPARING THE BED 218
On Rock. On Firm Earth. In Wet Ground : coffer-dam, con-
crete, grillage.
CHAPTER XI. PILE FOUNDATIONS.
DEFINITIONS 216
ART. 1. DESCRIPTIONS, AND METHODS OF DRIVING PILES 216
Description : iron piles ; screw piles ; disk piles ; sheet piles ; bear-
ing piles, — specifications, caps and shoes, splicing. Pile Driving Ma-
chines : drop-hammer, — friction clutch, nipper ; steam-hammer, drop-
hammer vs. steam-hammer ; gunpowder pile-drivers ; driving with
dynamite ; driving with water jet ; jet vs. hammer. Cost of Piles.
Cost of Pile Driving : railroad construction, bridge construction,
bridge repairs, foundations, harbor and river work.
ART. 2. BEARING POWER OF PILES 233
Methods of Determining Supporting Power. Rational Formula.
Comparison of Empirical Formulas : Beaufoy's, Nystrom's, Mason's,
Sander's, McAlpine's, Trautwine's, the Author's. Supporting Power
Determined by Experiment: examples, factor of safety; supporting
power of screw and disk piles.
ART. 3. ARRANGEMENT OF THE FOUNDATION 250
Position of Piles. Sawing-off. Finishing Foundation: piles and
grillage, piles and concrete, lateral yielding. Cushing's Pile Founda-
tion.
CHAPTER XII; FOUNDATIONS UNDER WATER.
DIFFICULTIES TO BE OVERCOME. OUTLINE OF CONTENTS. . . 257
ART. 1. THE COFFER-DAM PROCESS 258
Construction of the Dam. Leakage, pumps. Preparing the
Foundation
TABLE OF CONTENTS.
PAGE:
ART. 2. THE CRIB AND OPEN CAISSON PROCESS M
Definitions. Principle. Construction of the Caisson. Construc-
tion of the Crib. Excavating tne Site.
ART. 3. DREDGING THROUGH WELLS. , . 271
Principle. Excavator. Noted Examples : Poughkeepsie, Atcha-
falaya, and Hawkesbury bridges; brick cylinders. Frictional Resist-
ance. Cost.
ART. 4. PNEUMATIC PROCESS 278
Yacuum Process. Plenum Process. History. Pneumatic Piles,
bearing power. Pneumatic Caissons ; the caisson, the crib, the coffer-
dam, machinery, air-lock. Excavators : sand lift, mud-pump, water
column, blasting. Rate of Sinking. Guiding the Caisson. Noted
Examples : Havre de Grace, Blair, St. Louis, Brooklyn, Forth Bridges.
Physiological Effects of Compressed Air. Examples of Cost : at
Havre de Grace, Blair, and Brooklyn, and in Europe.
ART. 5. THE FREEZING PROCESS 307
Principle. History. Details of Process. Examples. Advantages.
Cost.
ART. 6. COMPARISON OF METHODS 309
PART IV. MASONRY STRUCTURES.
CHAPTER XIII. MASONRY DAMS.
CLASSIFICATION OF DAMS 311
ART. 1. STABILITY OF GRAVITY DAMS 31 &
Principles. Stability against Sliding : destroying forces, resisting
forces, co-efficient of friction, condition of equilibrium, factor of
safety. Stability against Overturning : by moments, — overturning mo-
ment, resisting moment, condition for equilibrium, factor of safety ;
by resolution of forces. Stability against Crushing : method of find-
ing maximum pressure, tension on masonry, limiting pressure.
ART. 2. OUTLINES OF THE DESIGN 326>
"Width on Top. The Profile : theory, examples. The Plan :
straight crest vs. straight toe ; gravity vs. arch dams ; curved gravity
dams. Quality of Masonry. Bibliography.
ART. 3. ROCK-FILL DAMS 334
Wood. Earth. Rock-fill and masonry dams compared.
CHAPTER XIV. RETAINING WALLS.
Definitions. Methods of Failure. Difficulties. ....... 338
ART. 1. THEORETICAL FORMULAS 340
The Three Assumptions. Theories : Coulomb's, Weyrauch's,
Rankine's.
TABLE OF COXTENTS. IX
PAGE
ART. 2. EMPIRICAL RULES 349
English Rules. American Rules. Details of Construction : quality
of masonry, drainage, land ties, relieving arches.
CHAPTER XY. BRIDGE ABUTMENTS.
Discussion of General Forms. Quality of Masonry. Foundation.
Wing Abutment,— design, and table of contents of various sizes.
U -Abutment, — design and table of contents of various sizes. T-Abut-
ment, — design and table of contents of various sizes 353
CHAPTER XVI. BRIDGE PIERS.
SELECTION OP SITE AND ARRANGEMENT OF SPANS. . . . 366
ART. 1, THEORY OF STABILITY 367
Methods of Failure. Stability against Sliding : effect of wind, cur-
rent, ice ; resisting forces. Stability against Overturning : by mo-
ments ; by resolution of forces. Stability against Crushing. Example
of method of computing stability.
ART. 2. DETAILS OF CONSTRUCTION 377
Dimensions: on top, at bottom. Batter. Cross Section. Specifica-
tions. Examples : Cairo, Grand Forks, Blair, Henderson, St. Croix
River ; iron tubular ; -wooden barrel. Tables of Contents of different
styles and sizes of bridge piers. Specifications.
CHAPTER XVII. CULVERTS.
ART. 1. WATER WAY REQUIRED 391
The Factors. The Formulas : Meyer's, Talbot's. Practical method
of finding area of water way.
ART. 2. Box AND PIPE CULVERTS 396
Stone Box Culvert : foundation, end walls, cover, specifications.
Examples : Standard, West Shore, Canadian. Table of Contents and
cost of the various styles and sizes 396
Vitrified Pipe Culverts : Construction. Example. Table of Con-
tents 407
Iron Pipe Culverts : Construction. Size and Weight of Pipe. Ex-
amples : A., T. & S. F., and C., B. & Q. standards. Table of Quan-
tity of Materials Required 412
Timber Culvert : C., M. & St. P. standard box culverts. C., B. <fc
Q. standard barrel culvert 417
ART. 3. ARCH CULVERT ' . . 419
General Form : splay of wing walls, joining wings and body, seg-
mental vs. semi-circular. Examples : diagrams illustrating details, and
also tables giving dimensions, and contents, and cost, of all sizes of
each of the standard forms of the Illinois Central, C., K. & K., A., T.
& S.-F. (both semi-circular and segmental), and a standard form.
Specifications.
TABLE OF CONTENTS.
CHAPTER XVIII. MASONRY ARCHES.
'Definitions : parts and kinds of arches; line of resistance 440
ART. 1. THEORY OF THE MASONRY ARCH 444
External Forces. Methods of Failure. Criteria of Safety : sliding,
rotation, crushing, — unit pressure, open joints. Location of Line of
Resistance : hypothesis of least pressure ; hypothesis of least crown
thrust, joint of rupture ; Winkler's hypothesis ; Navier's principle.
Rational Theory of the Arch : symmetrical load, — two methods ;
unsyminetrical load ; criterion for line of resistance. Scheffler's
Theory : two examples ; erroneous application ; reliability of. Ran-
kine's Theory : curvature of linear arch, method of testing stability,
reliability. Other Theories. Theory of the Elastic Arch. Stability
of Abutments and Piers.
ART. 2. RULES DERIVED FROM PRACTICE 404
Empirical Formulas : thickness of the arch at the crown, — Ameri-
can, French, English practice ; thickness at the springing, — American,
French, English practice ; dimensions of abutments. Dimensions of
Actual Arches and Abutments. Illustrations of Arches. Minor De-
tails: backing, spandrel filling, drainage. Brick Arches ; bond; ex-
amples,—tunnel, Philadelphia sewers, Washington sewers. Specifica-
tions : stone arches, brick arches.
ART. 3. ARCH CENTERS 515
Load to be supported, method of computing. Outline forms of
Centers : solid rib, built rib, braced wooden rib, trussed frame. Ex-
amples : centers for Vosburg tunnel, stone "bridges, and Cabin John
Arch. Striking Centers : method, time.
APPENDIX I. SPECIFICATIONS FOR MASONRY.
General Railroad Masonry 529
Masonry of Railroad Buildings ....". 534
Architectural Masonry 539
Laying Masonry in Freezing Weather 543
LIST OF ILLUSTRATIONS.
FIG. PAGE
1 Method of Failure in Compressive Tests. 6
2 Form of Specimen for Test of Tensile Strength of Cement 62
3 Clamps for Testing Tensile Strength of Cement 62
4 Home-made Cement Testing Machine 63
5 Diagram Showing the EU'ect of Time on the Strength of Mortars 89
6 Diagram Showing the Strength of Cement Mortar 90
7 " " " Effect of Adding Lime to Cement Mortar. .. 92
8 " " " Transverse Strength of Concrete 108
9 Double Face-Hammer 125
10 Face-Hammer. 125
11-15 Cavil, Pick, Ax, Tooth-ax, Bush Hammer 126
16-21 Crandall, Patent Hammer, Hand Hammer, Mallet, Pitching Chisel,
Point 127
22-26 Chisel, Tooth Chisel, Splitting Chisel, Plugs and Feathers, Drills. . 128
27 Method of Forming Plane Surface 129
28,29 " " " Cylindrical Surface 130
30 " " " Warped Surface 131
31 Rough-Pointed Surface 132
32 Firfe Pointed " 133
33 Cross-Crandalled " 133
34 Axed, or Pean -Hammered, Surface.. . '. 133
85 Bush -Hammered, or Patent-Hammered, Surface 134
36 Rubbed Surface 134
37 Diamond-Panel Surface 134
38 Ashlar Masonry 136
39 Broken Ashlar Masonry 136
40 Quarry-faced Squared-Stone Masonry 137
41 Pitch-faced " " " 137
42 Range Rubble " " " 137
43 Broken Range Rubble Masonry 1 37
44 Random Rubble Masonry 137
45 Un coursed " ' ' 137
46 Coursed " " 137
47 Method of Finishing Mortar Joint 162
48 English Bond in Brick-work 163
49 Flemish Bond in " 163
50 Foundations of Interior and Exterior Wall Joined Improperly. . . . 202
51-52 Improper Method of Arranging Footings 203
53 Overturning Effect of Wind on Foundation 204
54 Moment of Inertia of Sections 206
55 Inverted Arch for Foundation 212
56 Nasmyth's Steam Pile-Driver 224
57-59 Diagrams Illustrating Empirical Pile-Driving Formulas 241, 242
60 Construction of Coffer-Dams 259
61 " " Open Caisson 2G8
511 LIST OF ILLUSTRATIONS.
PIG. PAGE
62 Sinking Iron Piles by Dredging 274
63 Pneumatic Piles 282
64 Method of Increasing Bearing Power 283
65 Pneumatic Caisson of Blair Bridge 285
66 Interior View of Caisson of Havre de Grace Bridge. Shows also
Section of Mud Pump 293
67 Method of Sinking Caissons for Brooklyn Bridge 295
68 Diagram Illustrating the Computations of Strains in Masonry Dams. 313
69 Method of Finding Center of Gravity of a Dam 318
70 Stability of Dam determined by Resolution of Forces 320
71 Maximum Pressure on the Foundation of a Dam 321
72 Profile of Quaker Bridge Dam and Krantz's Standard Profile 328
339
341
342
344
Profile of Quaker Bridge Dam and Ki
Diagram Illustrating Computations of
73 Diagram Illustrating Computations of Strains in Retaining Walls
74 " " " " "
75 " " " " "
76
77 Relieving Arches at the Back of Retaining Walls 352
78 Outline of Straight Bridge Abutment 353
79 " "Wing " " 353
80 " " U " " 353
81 " " T " " 353
82 Detailed Plan of Wing Bridge Abutment *. 356
83 " " " U '" " 360
84 » " " T " " 362
85 Channel Pier Cairo Bridge 372
bo Pivot Pier Grand Forks Bridge 380
87 Channel Pier Blair Bridge 383
88 Top of Henderson Bridge Pier 384
89 Arrangement of Stones of a Course in Cairo Pier 385
90 Pier of St. Croix River Bridge , 386
91«. 915 Foundations for Box Culverts 397
92, 93 Methods of Finishing the Ends of Box Culverts 398
94 Detailed Plan of Standard Box Culvert 403
95 " " " Box Culvert— West Shore R. R 404
96 4< " " « «• —Inter-Colonial R. R. of Canada 406
97, 98 End Walls for Vitrified Pipe Culvert 409
99 Detailed Plan of " " " 411
100 Detailed Plan of Cast-iron Pipe Culvert— A., T. & S. F. R R. . . . 414
101 " " " « « « a, B. &Q. R. R 415
102 " " " Timber Box Culvert 418
103-5 Manner of Splaying Wings of Arch Culverts 419
106-9 Junction of Wings to Body of Arch Culvert 420
110 Illustrating Definitions of Parts of an Arch 440
111 " RightArch 442
112 " Skew Arch 442
113 Method of Finding Line of Resistance 443
114-5 " «• an Arch's Failing by Sliding 447
H6-7 « « « « « hyRotating 447
118 Method of Finding Maximum Pressure in an Arch 451
1 19 Lines of Resistance for Maximum Thrust 454
ISO " 'k « •« " and Minimum Thrust 454
121 Method of Finding True Line of Resistance 455
122 " " " Joint of Rupture. 458
123-4 " " " Reduced-Load Contour • 459
125 Application of Rational Theory of the Arch 467
126 Rational Theory of the Arch— General Graphic Solution 470
127 " " " «« Special " " 472
LIST OF ILLUSTRATIONS. Xlii
PIG. PARE
128 Rational Theory of the Arch — Unsymmetrical Load 473
129 Criterion for Position, of Line of Resistance 474
130 Application of Scheffler's Theory of the Arch 475
131 Method of Correcting Position of Joint 476
132 " ofFinding " " " 476
133 Graphical Solution by Scheffler's Theory 480
134 Hydrostatic Arch 484
135 Application of Rankine's Theory of the Arch 486
136 The Linear Arch the Intrados of the Real Arch 488
137 Testing Stability of Arch by Rankine's Theory 489
138 Stability of Abutments and Piers 492
139 Empirical Rule for the Design of an Arch 500
140 Relieving Arches in the Spandrel Filling 506
141 Equilibriated Masonry Arch 507
142 Cylindrical Arch through Spandrel Filling 508
143 Detailed Plan 50-ft. Stone Arch—Pennsylvania R. R. 509
144-6 Bonding for Brick Arches 510
147 Brick Arching and Center Vosburg Tunnel 512
148 Brick Sewers— Philadelphia Standard 513
149 " " Washington " 514
150 MethocJL of Finding Pressure on Arch Center 516
151 Arch Center— Solid Wooden Rib 519
152 " " Built " " 519
153-5 " " Braced " " 522
156-7 " " Trussed Rib 522
1 58 Center for Washington Bridge— 60-f t. span 524
159 " " Cabin John Arcli— 220-ft 525
160 Method of Striking Centers .- 526
FOLDING SHEETS AT END OF VOLUME.
PLATE
I. Detailed Plan Caisson Havre dc Grace Bridge.
II. ' 6-ft. Arch Culvert— Illinois Central R. R.
III. ' 8-ft. " " C.,K. &KR. R.
IV. ' 10-ft. Semi-circular Arch Culvert— A., T. & S. F. R. R.
V. ' 10-ft. Segmental Arch Culvert— A., T. & S. F. R. R.
VI. ' 12-ft.— Standard Arch Culvert.
LIST OF TABLES.
16
NO. PAGE
1 Crushing Strength, of Cubes of Stone 10
2 Transverse Strength of Stone, Brick, and Mortar. . . , 12
3 Co-efficient of Elasticity of Stone, Brick, and Mortar 13
4 Absorptive Power of Stone, Brick, and Mortar 20
Relative Resistance of Different Stone to Frost— two tables 21
" " •• 22
5 Weight of Building Stones ^ 31
6 Transverse Strength of Illinois Brick 40
7 " ^ " Eastern " 41
8 Experiments on Brick with the Watertown Testing Machine 44
9 Tests of Illinois Brick. — Absorption, Transverse, and Compressive
Strength 45
Effect on Strength of Cement of the Rapidity of applying the Stress 68
10 Tensile Strength of Cement Mortars 66
11 Ingredients Required for a Cubic Yard of Mortar of Different Pro-
portions 86
12 Amount of Mortar Required for a Cubic Yard of Masonry 87
Effect of Time on Strength of Mortars— Graphical Table 89
Strength of Cement Mortars — Graphical Table 90
" " Lime-Cement Mortar — Graphical Table 92
18 Adhesive Strength of Mortar 94
Comparative Cost of Different Kinds of Mortar 95
Composition of DiffereDt Grades of Concrete 104
Transverse Strength of Concrete—Graphical Table 108
Crushing Strength of Concrete, 109, 110
Cost of Concrete, Harbor Work Ill
" " if Foundation Work Ill
•* " *' Reservoir 112
14 List of Explosives Containing Nitre-glycerine 124
Safe Pressure on Stone Masonry 151
Estimates of Cost of Masonry 154
Market Price of Stone. 155
15 Cost of Cutting Stone for TL S. Public Buildings 156
Masonry in U. S. Public Buildings 156
Railroad Masonry 157
Tunnel " 157
Bridge-pier Masonry 157
Arch-culvert Masonry 159
Masonry : Summary 160
17
18
19 Strength of Brick Masonry Compared with that of the Brick and
the Mortar 164
20 Relative Strength of Brick and Brick Masonry 166
xiv
LIST OF TABLES. XV
NO. PAGE
21 Labor Required for Brick Masonry 175
22 Compressive Strength under Concentrated Pressure 100
23 Safe Bearing Power of Soils 194
24 Weight of Masonry 200
25 Safe Off-set for Masonry Footing Courses 209
Cost of Pile Driving in Railroad Construction 281
26 " " " for Bridge Repairs 231
27 " " Labor in Driving Piles in Bridge Construction 232
28 Contract Price of Foundation Piles 232
Table Showing the Gain in Efficiency of the Driving Power by Cut-
ting oil" the Broomed Head of the Pile 240
29 Data of Experiments on the Supporting Power of Piles 246
Cost of Foundation by Coif er-i)mn Process 265
30 Co-efficient of Friction of Materials and Surfaces used in Founda-
tions 276
31 Dimensions of. and Quantities of Materials in, Foundations of Havre
de Grace Bridge 290
32 Cost of Pneumatic Foundations of Havre de Grace Bridge 302
33 " l' " " " Blair Bridge 303
34 " " " Piles at Philadelphia 304
" " " Process in Europe— two tables 305, 306
35 " " Various Kinds of Foundations in Europe 310
36 Co-efficient of Friction for Dry Masonry 315
37 Contents of Wing Bridge Abutments of Various Heights 357
38 " " U " " " " " 3C1
39 " " T " " " " " 363
40 " " Pier of Bridge over St. Croix River '387
41 " " Bridge Piers for Various Heights and Sizes 389
42 Dimensions and Contents Standard Box Culvert 403
43 " " " West Shore R. R. Box Culvert 404
44 " " " Double Box Culverts 405
Comparative Estimates of Cost of Box Culvert of different styles. . . . 405
45 Cost and Weight of Vitrified Sewer Pipe 410
46 Masonry Required for Vitrified Pipe Culvert 411
47 Dimensions of Cast-Iron Culvert Pipes 412
48 " " End Walls for Iron Pipe Culverts 414
Cost of Cast-Irou Culvert 417
49 Dimensions and Contents, 111. Cent. Arch Culvert 425
50 " " " 0., K. &N. Arch Culvert 428
51 " " " A.,T. & S. IT. Semi-cir. Arch Culvert 480
52 " " " <. «i ,* Segmental Arch Culvert. . 431
58 " " " Standard Arch Culvert 433
54 Cost of 111. Cent. Arch Culverts 435
" C., K. & N. Arch Culverts 4m
"A., T. & S. F. Semi-circular Arch Culverts 4;$;
Segmental Arch Culverts 4;-jH
56
57
f>8 ' " Standard Arch Culverts
59 Computations to Find Joint of Rupture of an Arch 451)
60, 61 Application of Schemer's Theory of the Arch 477, 478
63 Comparison of Empirical Formulas for Depth of Keystone 498
63 Dimensions of Actual Arches 50'2-3
64 " " " Abutments 505
65 Computation of Pressure on Arch Center 519
MASONRY CONSTRUCTION.
INTRODUCTION.
this general head will bo discussed the subjects relating
to the use of stone and brick as employed by the engineer or archi-
tect in the construction of buildings, retaining walls, bridge piers,
culverts, arches, etc., including the foundations for the same.
For convenience, the subject will be divided as follows :
Part I. Description and Characteristics of the Materials.
Part II. Methods of Preparing and Using the Materials.
Part III. Foundations.
Part IV. Masonry Structures.
" The first cost of masonry should be its only cost. Though superstructures-
decay and drift away, though embankments should crumble and wash out,
masonry should stand as one great mass of solid rock, firm and enduring."
— Anonymow.
PART I.
THE MATERIALS.
CHAPTER I.
NATURAL STONE.
ART. 1. REQUISITES FOB GOOD BUILDING STONE.
1. The qualities which are most important in stone used for
construction are cheapness, durability, strength, and beauty.
2. CHEAPNESS. The primary factor which determines the value
of a stone for structural purposes is its cheapness. The items which
contribute to the cheapness of a stone are abundance, proximity of
quarries to place of use, facility of transportation, and the ease with
which it is quarried and worked.
The wide distribution and the great variety of good building
stone in this country are such that suitable stone should everywhere
be cheap. That such is not the case is probably due either to a
lack of the development of home resources or to a lack of confidence
in home products. The several State and Government geological
surveys have done much to increase our knowledge of the building
stones of this country.
The lack of confidence in home resources has very frequently
caused stones of demonstrated good quality to be carried, far and
wide, and frequently to be laid down upon the outcropping ledges
of material in every way their equal. The first stone house erected
in San Francisco, for example, was built of stone brought from
China ; and at the present day the granites mostly employed there
are brought from New England or from Scotland. Yet there are
no stones in our country more to be recommended than the Califor-
nia granites. Some of the prominent public and private buildings
in Cincinnati are constructed of stone that was carried by water and
*8
NATURAL STOKE. [CHAP. I.
railway a distance ol about 1500 miles. Within 150 miles of Cin-
cinnati, in the sub-carboniferous limestone district of Kentucky,,
tliere are yery extensive deposits of dolomitic limestone that afford
a "beautiful building stone, which can be quarried at no more ex-
pense than that of the granite of Maine. Moreover,, this dolomite
is easily carved, and requires not more than one third the labor to
give it a surface that is needed by granite. Experience has shown
that the endurance of this stone under the influence of weather is
very great ; yet because it has lacked authoritative indorsement
there has been little iharket for it., and lack of confidence in it has
led to the transportation half-way across the continent of a stone
little, if any, superior to it.
Development of local resources follows in the wake of good in-
formation concerning them, for the lack of confidence in home prod-
ucts can not be attributed to prejudice.
The facility with which a stone may be quarried and worked is
an element affecting cheapness. To be cheaply worked, a stone
must not only be as soft as durability will allow, but it should have
no flaws, knots, or hard crystals.
3. DTJBABILITY. IsText in importance after cheapness is dura-
bility. Bock is supposed to be the type of all that is unchangeable
and lasting ; but the truth is that, unless a stone is suited to the'
conditions in which it is placed, there are few substances more liable
to decay and utter failure. The durability of stone is a subject
upon which there is very little reliable knowledge. The question
of endurance under the action of weather and other forces can not
be readily determined. The external aspect of the stone may fail
to give any clue to it ; nor can all the tests we yet know determine
to a certainty, in the laboratory, just how a given rock will with-
stand the effect of our variable climate and the gases of our cities.
If our land were what is known as a rainless country, and if the
temperature were uniform throughout the year, the selection of a
durable building stone would be much simplified. The cities of
northern Europe are full of failures in the stones of important
structures. The most costly building erected in modern times, per-
haps the most costly edifice reared since the Great Pyramid, — the
Parliament House iii London, — was built of a stone taken on the
recommendation of a committee representing the best scientific and
technical skill of Great Britain. The stone selected was submitted
ART. 2.J TESTS OF BUILDING- STONES. 5
to various tests, but the corroding influence of a London atmosphere
was overlooked. The great structure was built, and now it seems
questionable whether it can be made to endure as long as a timber
building would stand, so great is the effect of the gases of the
atmosphere upon the stone. This is only one of the numerous in-
stances that might be cited in which a neglect to consider the
climatic conditions of a particular locality in selecting a building
material has proved disastrous.
' c The great difference which may exist in the durability of stones
of the same kind, presenting little difference in appearance, is
strikingly exemplified at Oxford, England, where 'Christ Church
Cathedral, built in the twelfth or thirteenth century of oolite from
a quarry about fifteen miles away, is in good preservation, while
many colleges only two or three centuries old, built also of oolite
from a quarry in the neighborhood of Oxford, are rapidly crumbling
to pieces. " *
4. STRENGTH. The strength of stone is in some instances a
cardinal quality, as when it is to form piers or columns to support
great weights, or capstones that span considerable intervals. It is
also an indispensable attribute of stone that is to be exposed to
mechanical violence or unusual wear, as in steps, lintels, door- jambs,
etc.
5. BEAUTY. This element is of more importance to the archi-
tect than to the engineer ; and yet the latter can not afford to
neglect entirely the element of beauty in the design of his most
utilitarian structures. The stone should have a durable and pleas-
ing color.
AKT. 2. TESTS OF THE QUALITY OF BUILDING STORES.
6. As a general rule, the densest, hardest, and most uniform
stone will most nearly meet the preceding requisites for a good
building stone. The fitness of stone for structural purposes can be
determined approximately by examining a fresh fracture. It should
be bright, clean, and sharp, without loose grains, and free from any
dull, earthy appearance. The stone should contain no f£ drys," i.e.,
seams containing material not thoroughly cemented together, nor
"crow-foots," i.e., veins containing dark-colored, uncementcd
material.
* Rankine's Civil Engineering, p. 362.
KATURAL STOKE. [CHAP. I.
The quality is usually tested by determining its strength, — par-
ticularly its resistance to crushing. This form of test is resorted
to, not because of the predominating importance of the quality of
strength, nor because of any known relation which exists between
strength and durability, but because of the greater facility with
which the strength can be determined.
STBENGTH.
7. CEUSHING STBENGTH. The crushing strength of a stone is
generally tested by applying measured force to cubes until they are
crushed. Usually, when simply the strength of stone is referred to,
the crushing strength is intended. The results for the crushing
strength vary greatly with the details of the experiments. Several
points, which should not be neglected either in planning a series
of experiments or in using the results obtained by experiment, will
be taken up separately, although they are not entirely independent.
8. Form of Fracture. Homogeneous stones in small cubes appear
•] in all cases to break as shown in Fig. 1. The
forms of the fragments a and b are, approxi-
mately, either conical or pyramidal. The
more or less disk-shaped pieces c and d are de-
tached from the sides of the cube with a kind
of explosion. In the angles e and/, the stone
is generally found crushed and ground into
powder. A homogeneous stone is possibly
imaginary, but some of the artificial stones
described in a succeeding chapter are nearly, if not quite, homo-
geneous.
This general form of breakage occurs also in non-homogeneous
stones when crushed on their beds; but in this case the modification
which the grain of the stone produces must be taken into account. ;
9. Cushions. The nature of the material in contact with the
stone while under pressure is a matter of great moment. If the
materials which press upon the top and bottom of the specimen are
soft and yielding and press out sidewise, they introduce horizontal
forces which materially diminish the apparent crushing strength of
the sfcone. If the pressing surfaces are hard and unyielding, the
resistance of these surfaces adds considerable to the apparent
strength. The thing sought is to secure the same conditions in
ART. 2.] • TESTS OF BUILDING STONES. 7
the experiments that the stone is under in the wall of masonry.
It would at first seem that the pressing surface should be of the
same kind of stone as the specimen to be tested. But the surface
must not be continuous. One stone is seldom placed directly over
another, since, necessarily, for the strength of the structure, we
introduce what is called bond. Usually, then, there are one or two
joints under each stone, which may or may not be filled with mortar.
A wooden cushioi?, one quarter inch thick, placed above and below
the test specimen most nearly represents the conditions actually
existing in the wall, because it spreads mainly in one direction, and
but very little transversely thereto.
Steel, wood, lead, and leather have been used as pressing surfaces.
Under certain limitations, as noted below, the relative crushing
strengths of stones with these different pressing surfaces are 100, 89,
65, and 62 respectively.* The following exceptions to the preced-
ing general rule must be noted. "With, stones of great hardness and
toughness combined, steel and wood give approximately equal
results; with very soft stones, the power of the stone to resist crush-
ing is overcome before sufficient pressure has been developed to
bring the action of the wood fibers on the stone fairly into play, and
consequently the steel and wood again give the same results.
Formerly it was the custom [to interpose sheets of lead between
stones subjected to compression, the object of this use of the lead
being to secure a uniform bearing; but the lead, being soft, squeezes
out sidewise, thus introducing lateral forces which cause the stone
to fail by splitting instead of. by crushing.
Tests of the strength of blocks of stone are useful only in com-
paring different stones, and give no'idea of the strength of structures
built of such stone (see § 222) or of the crushing strength of stone
in large masses in its native bed (see § 273).
Then, since it is not possible to have the stone under the same
conditions while being tested that it is in the actual structure, it is
best to test the stone under conditions that can be accurately de-
scribed and readily duplicated. Therefore it is rapidly coming to
be the custom to test the stone between metal pressing-surfaces.
Under these conditions the strength of the specimen will vary
greatly with the degree of smoothness of its bed-surfaces. Hence,
* Report on Building Stones, in Report of Chief of Engineers, U. S. A., 1875, App.
II; also bound separately, page 29.
8 ^ATTJEAL STONE. . [CHAP. I,
to obtain definite and precise results, these surfaces should be rubbed
or ground perfectly smooth; but as this is tedious and expensive, it
is quite common to reduce the bed-surfaces to planes by plastering,
them with a thin coat of plaster of Paris. With the stronger stones,
specimens with plastered beds will show less strength than those
having rubbed beds, and this difference will vary also with the
length of time the plaster is allowed to harden. With a stone hav-
ing a strength of 5000 to 6000 pounds per square inch, allowing the
plaster to attain its maximum strength, this difference varied from
5 to 20 per cent., the mean for ten trials being almost 10 per cent, of
the strength of the specimen with rubbed beds.
10. Eorm of Test Specimen. The crushing strength of stone is.
generally obtained by compressing cubes of the material. In good
masonry, stones of greater height than the breadth of the bed are
never used; therefore the experiments should not be made on ob-
jects whose height is more than the breadth, unless columnar
strength is desired. Experiments show that slabs of width much
greater than height do not give a definite and easily recognized
point of failure, but that the cube does allow quite sufficient oppor-
tunity for the easily recognized and natural angular breakage of
stone. Experiments also show that, while slabs gire much greater
(sometimes 50 per cent, more) resistance than cubes, those higher
than wide, to the limit of nearly three times the width, are but
little, if any, decreased in resistance by increased altitude. In the
Hodgkinson-Fairbairn experiments on cast iron, the conclusion was-
drawn that the test specimen should have a height of at least 1£
times its diameter. This conclusion is often applied to stone, but
is nevertheless inapplicable, since stone is generally employe! in
such a position that the height is less than the breadth.
11. Size of Cube. Although the cube is the form of test specimen
generally adopted, there is not equal unanimity as to size of the
cube; hence it is necessary to inquire into the effect of the size of
the specimen upon the apparent strength. This inquiry is neces-
sary before we can compare results by different experimenters; and
it is important as indicating the relation between the strength of the
test specimen and that of the block of stone .as laid in the wall.
Hodgkinson tested teak -wood cylinders, £ inch, 1 inch, and £
inches in diameter, the height in each case being twice the diameter,
and obtained results which seemed to show that the strength per
square inch was independent of the bed-area.
ART. 2.] TESTS OF BUILDING STOKES. 9
On the other hand, Gen. Gillmore tested 1-inch., 2-inch, and 3-
inch cubes of Michigan pine, crushed against the ends of the fiber,
which gave a considerable increase in strength per square inch of
bed-area as the size of the cube increased. Gillmore also made
experiments upon cubes of stone varying from ^ inch to 4 inches
on a side, with the result that the relation between the crushing
strength and the size of the cube can be expressed by the formula
y = a Vx,
in which y is the total crushing pressure in pounds per square inch
of bed-area, a is the crushing pressure of a 1-inch cube of the same
material, and x is the length in inches of an edge of the cube under
trial. For two samples of Berea (Ohio) sandstone, a was 7000 and
9500 Ibs. respectively.*
According to tests made with the large and accurate testing-ma-
chine at the Watertown (Mass. ) Arsenal f on cubes of neat cement,
cement mortars, concrete, and Haverstraw sandstone, the strength
of cubes appears to be independent of the bed-area. J Various other
experimenters have uniformly obtained like results. There is no
sufficient reason for believing that the strength of cubes of homo-
geneous stones varies with the size of the cube. The experiments
which indicated a variation of strength with size were doubtless in
error, owing probably to the friction of the testing machine.
12. Dressing the Specimen. It is well known that even large
stones can be broken by striking a number of comparatively light
blows along any particular lino, in which case the force of the blows
gradually weakens the cohesion of the particles. This principle finds
application in the preparation of test specimens of stone. If the
specimen is dressed by hand, the concussion of the tool greatly
affects its internal conditions, particularly with test specimens of
Bmall dimensions. With 2-inch cubes, the tool-dressed specimen
usually shows only about GO per cent, of the strength of the sawed
* Report on Strength of Building Stone, Appendix II, Report of Chief of En-
gineers of U. S. A. for 1875.
t Report on the "Tests of Metals, etc.," for the year ending June 30, 1884-, pp.
126, 166, 167, 197, 212, 213, 215 ; the same being Sen. Ex. Doc. No. 35, 49th Cong.,
1st Session.
% For a more elaborate discussion of this point by the author, see Engineering News
vol. xix. pp. 511-12.
10
NATURAL STONE.
[CHAP. T.
sample. The sawed sample most nearly represents the conditions
of actual practice.
Unfortunately,, experimenters seldom state whether the specimens
were tool-dressed or sawed. The disintegrating effect of the tool
in d ressing is greater with small than with large specimens. This may
account in part for the difference in strength of different sizes of
test specimens. All stones are strongest when laid on their bed, i.e.,
in their natural position; and with sedimentary rocks there is a
very great difference in the two positions. Hence, in preparing the
specimen the natural bed should be marked, and the position in
which it is tested should be noted. Tests of the strength of blocks
of stone are useful only in comparing different stones, and give no
idea of the strength of structures built of such stone (see § 222) or
of the crushing strength of stone in large masses in its natural bed
(see*§ 273).
13. Data on Crushing Strength. The strength of the principal
classes of building stone in use in the United States is about as
follows :
TABLE 1.
CKUSHIN& STRENGTH OF CUBES OF STONE.
ULTIMATE CRUSHING STRENGTH.
KINDS OF STONE.
Poimds per Square Inch.
Tons per Square Foot.
Min.
Max.
Min.
Max.
Trap Rocks of N". J
20,000
12,000
8,000
7,000
5,000
24,000
21,000
20,000
20,000
15,000
1,440
860
580
500
360
1,730
1,510
1,440
1,440
1,080
Granite
Marble
Limestone
Sandstone
14, Crushing Strength of Slabs, Only a few experiments have
been made to determine the crushing strength of slabs of stone.
The strength per square inch of bed-surface was considerably
greater than that for cubes ; but a study of the results of all of the
reliable experiments * fails to discover any simple relation between
* See Report on "Tests of Metals, etc.," for 1884.— Sen. Ex. Doc. No. 35, 49th
Cong., 1st Session,— pp. 126 and 212.
AET. 2.] TESTS OF BUILDING STONES. 11
the crushing strength of cubes and slabs. It is probable that the
•effect of the pressing surface is so great as to completely mask the
variation. due to height of specimen. More experiments on this
-subject are very much needed. /
15. TKANSVERSE STRENGTH. When stones are used for lintels,
etc., their transverse strength becomes important. The ability of a
.stone to resist as a beam depends upon its tensile strength,, since
that is always much less than its compressive strength. A knowl-
edge of the relative tensile and compressive strength of stones is
valuable in interpreting the effect of different pressing surfaces in
compressive tests, and also in determining the thickness required
lor lintels, sidewalks, cover-stones for box culverts, thickness of
footing courses, etc.
Owing to the small cross section of the specimen employed in
determining the transverse strength of stones, — usually a bar 1 inch
square, — the manner of dressing the sample affects the apparent
transverse strength to a greater degree than the compressive strength
(see § 12); and it is even more unfortunate, since the strength of
the stone as used in actual practice is nearly proportional to the
strength of sawed samples.
The following formulas are useful in computing the breaking
load of a slab of stone. Let W represent the concentrated center
load plus half of the weight of the beam itself, in pounds ; and let
Z>, d, and I represent the breadth, depth, and length, in inches,
respectively. Let R = the modulus of rupture, in Ibs. per sq. in. ;
let G = the weight, in pounds, required to break a bar 1 inch
square and 1 foot long between bearings ; and let L = the length
of the beam in feet. Then
The equivalent uniformly distributed weight is equal to twice the
concentrated center load.
Table 2 on the following page gives the values of R, the mod-
ulus of rupture, and of C, the co-efficient of transverse strength,
required in the above formulas.
Example. — To illustrate the method of using the above formulas,
assume that it is desired to know the breaking load for a limestone
slab 3 inches thick, 4 feet wide, and 6 feet long. Then 1) = 48 ;
NATURAL STONE.
[CHAP. i.
TABLE 2.
TBANSVBBSE STRENGTH OF STONE, BRICK, AND MOKTAB.
OF RUPTURE.
MATERIAL.
Mar.
Min.
Aver.
Max.
Min.
Aver.
Blue-stone flagging*
4,511
360
2,700
251
20
150
Granite
2 700
900
1 800
150
50
100
[Limestone
2,500
140
1,500
140
8
8&
" oftlitic, from Ind., sawed.
Marble »
2,590
2 880
2,190
144
2,338
2 160
144
160
122
8
130*
120-
Sandstone
2,340
576
1 260
130
32
70
Slate.
9 000
1 800
5 400
500
100
300
Brick (§59)
1 796
269
800
100
15
45
Concrete — see § 156. %
Mortar, neat Portland, 1 year old. .
Mortar, 1 part Portland cement, 1
part sand, 1 year old
1,158*
945*
64*
52*
Mortar, 1 part Portland cement, 2
parts sand, 1 year old
682*
38*
Mortar, neat Rosendale, 1 year old.
Mortar, 1 part Eosendale cement,
1 part sand, 1 year old
715
690
415
348
600
526
39
38
23
19
33
29
Mortar, 1 part Rosendale cement,
2 parts sand, 1 year old
479
338
405
26
18
22
d = 3 ; I = 72 ; R = 1500 Ibs.,— the "average" value from the
table ; — and C = 83. Substituting these values, we have
2 X 48 X 915QO = 60()() pounds.
W =
3 I
3 X
or, using the other form,
IF- ^£7= ^-—83 = 5976 pounds,
which agrees with the preceding except for omitted decimals.
Hence the breaking load for average quality of limestone is 6000
pounds concentrated along a line half-way between the ends ; the
uniformly distributed load is twice this, or 12,000 pounds. The
* Only one experiment.
ART. 2.]
TESTS OF BUILDING- STONES.
13
•question of what margin should be allowed for safety is one that can
not be determined in the abstract ; it depends upon the accuracy
with which the maximum load is estimated, upon the manner the
load is applied — whether with shock or not, — upon the care with
which the stone was selected,, etc. This subject will be discussed
further in connection with the use of the data of the above table in
-subsequent parts of this volume.
16. ELASTICITY. But very few experiments have been made to
determine the co-efficient of elasticity, the elastic limit, and the
"set" of stone. Data on these points would be valuable in deter-
mining the effect of combining masonry and metal, of joining
different kinds of masonry, or of joining new masonry to old ; in
calculating the effect of loading a masonry arch ; in proportioning
abutments and piers of railroad bridges subject to shock, etc.
The following is all the data that can be found :
TABLE 3.
CO-EFFICIENT OF ELASTICITY OF STONE, BRICK, AND MORTAR.
MATERIAL.
POUNDS PER SQUARE INCH.
Haverstraw Freestone *
Portland Stone (oolite limestone)!
Marblef
Portland Granite:):
Slatef
•Graf ton Limestone J
Richmond GrauiteJ
Brick, medium — mean of 16 experiments*
Louisville Cement Mortar, 4 months old : J
Neat cement
1 part cement, 1 part sand
1 part cement, 2 parts sand
Ulster Co. (K Y.) Cement Mortar, 22 months
old : *
2 parts cement, 3 parts sand
1 part cement, 3 parts sand
Portland Cement Mortar, 22 months old*
9.10,000
1,530,000
2,500,000
5,500,000
7,000,000
8,000,000
13,000,000
3,500,000
800,000
600,000
1,300,000
640,000
535,000
1,525,000
U. S. testing-machine, Watertown, Mass. t Tredgold, as quoted by Stoney.
J History of St. Louis Bridge, pp. 324-28.
14 NATURAL STOisTE. [CHAP. I,
17. Hardness and Toughness. The reader should notice that
these two qualities are essentially different. Hardness of itself is.
not necessarily an element of durability. Both qualities should,
exist in a stone to be used for stoops, pavements, road-metal, the
facing of piers, etc. ISTo experiments have been made in this
country to test the resisting power of stone when exposed to the
different kinds of service. A table of the resistance of stones to-
abrasion is often quoted,* but as it contains only foreign stones,
which are described by local names, it is not of much value.
1 8. BlBLlOGEAPHICAL. A large number of tests have been applied
to the building stones of the United States. For additional results.
and details, see Gillmore's Report on the Building Stones of the U.
S., Appendix II. of the Annual Eeport of the Chief of Engineers,,
TL S. A., for 1875; Vol. X. of the Tenth Census of the U. S., Eeport
on the Quarry Industry, pp. 330-35 ; History of the St. Louia
Bridge, Chapter 25 ; Transactions American Society of Civil
Engineers, Vol. II. pp. 145-51 ; Vol. I. of the Eeport of the
Geological Survey of Minnesota; Eeport for 1884 of " Tests of
Metals, etc.," made at the Watertown Arsenal, under the direction
of the Chief of Ordnance, U. S. A. ; and the Eeports of the various'
State Geological Surveys, and of the commissioners of the various
State capitols and of other public buildings.
From, what has been said above, it is clear that the results should
be used only with a knowledge of the form and size of the specimen
and also a clear understanding of the method of making the experi-
ments.
DURABILITY.
19. "Although the art of building has been practiced from the
earliest times, and constant demands have been made in every age
lor the means of determining the best materials, yet the process of
ascertaining the durability of stone appears to have received but
lictle definite scientific attention, and the processes usually employed
for solving this question are still in a very unsatisfactory state.
Hardly any department of technical science is so much neglected as
that which embraces the study of the nature of stone, and all the
varied resources of lithology in chemical, microscopical, and physical
methods of investigation, wonderfully developed within the last
* For example, Mahan's Civil Engineering, p. 13.
ART. 2.] TESTS OF BUILDING STONES. 15
quarter century, have never yet been properly applied to tlie selec-
tion and protection of stone used for building purposes."*
Examples of the rapid decay of building stones have already been
referred to, and numerous others could be cited., in which a stone
which it was supposed would last forever has already begun to
decay. In every way, the question of durability is of more interest
to the architect than to the engineer ; although it is of enough
importance to the latter to warrant a brief discussion here.
20. DESTRUCTIVE AGENTS. The destructive agents may be clas-
sified as mechanical, chemical, and organic. The last are unim-
portant, and will not be considered here.
21. Mechanical Agents. For our climate the mechanical agents
are the most efficient. These are frost, wind, rain, fire, pressure,
and friction.
The action of frost is usually one of the main causes of rapid
decay. Two elements are involved, — the friability of the material
and its power of absorbing moisture. In addition to the alter-
nate freezing and thawing, the constant variations of temperature
from day to day, and even from hour to hour, give rise to molecular
motions which affect the durability of stone as a building material.
This effect is greatest in isolated columns, — as monuments, bridge
piers, etc.
The effect of rain depends upon the solvent action, of the gases
which it contains, and upon its mechanical effect in the wear of
pattering drops and streams trickling down the face of the wall.
A gentle breeze dries out the moisture of a building stone and
tends to preserve it; but a violent wind wears it away by dashing
sand grains, street dust, ice particles, etc., against its face. The
extreme of such action is illustrated by the vast erosion of the sand-
stone in the plateaus of Colorado, Arizona, etc., into tabular m&sas,
isolated pillars, and grotesquely-shaped hills, by the erosive force of
sand grains borne by the winds. The effect is similar to that of the
sand blast as used in various processes of manufacture. A violent
wind also forces the rain-water, with all the corrosive acids it con-
tains, into the pores of stones, and carries off the loosened grains,
thus keeping a fresh surface of the stone exposed. Again, the
swaying of tall edifices by the wind must cause a continual motion,
* Tenth Census of the U. S., Vol. X., Report on the Quarry Industry, p. 364.
NATURAL STONE. [CHAP. I.
not only in the joints between the blocks,, but among the grains of
the stones themselves. Many of these haye a certain degree of
flexibility., it is true; and yet the play of the grains mast gradually
increase, and a tendency to disintegration result.
Experience in great fires in the cities shows that there is no
.stone which can withstand the fierce heat of a mass of burning
buildings. Sandstones seem to be the least affected by great heat,
.and granite most.
Friction affects sidewalks, pavements, etc., and has already been
referred to (§ 17). It would also affect bridge piers, sea-walls,
•docks, etc.
The effect of pressure in destroying stone is one of the least
importance, provided the load to be borne does not too nearly equal
the crushing strength. The pressure to which stone is subjected
•does not generally exceed one tenth of the ultimate strength as
determined by methods already described.
22. Chemical Agents. The principal ones are acids. Every
constituent of stone, except quartz, is subject to attack by acids;
.and the carbonates, which enter as chief constituents or as cement--
ing materials, yield very readily to such action. Oxygen and am-
monia by their chemical action tend to destroy stones. In cities or
manufacturing districts sulphur acids and carbonic acid have a
very marked effect. These all result from the combustion of gas,
•coal, etc., and some are also the residuary gases of many kinds of
manufactories. The nitric acid in the rain and the atmosphere
•exerts a perceptible influence in destroying building stone.
23. RESISTING AGENTS, The durability of a building stone de-
pends upon three conditions; viz., the chemical and mineralogical
nature of its constituents, its physical structure, and the character
and position of its exposed surfaces.
24. Chemical Composition. The chemical composition of the
principal constituent mineral and of the cementing material has an
important effect upon the durability of a stone.
A siliceous stone, other things being equal, is more durable than
A limestone; but the durability of the former plainly depends upon
the state of aggregation of the individual grains and their cement-
ing bond, as well as on the chemical relation of the silica to the
other chemical ingredients. A dolomitic limestone is more durable
than a pure limestone.
ART. 2.] TESTS OE BUILDING STOKES. 17
A stone that absorbs moisture abundantly and rapidly is apt to
be injured by alternate freezing and thawing; hence clayey constit-
uents are injurious. An argillaceous stone is generally compact,
.and often has no pores visible to the eye; yet such will disintegrate
rapidly either by freezing and thawing, or by corrosive vapors.
The presence of calcium carbonate, as in some forms of marble
and in earthy limestones, renders a building material liable to rapid
attack by acid vapors. In some sandstones the cementing material
is the hydrated form of ferric oxide, which is soluble and easily
removed. Sandstones in which the cementing material is siliceous
.are likely to be the most durable, although they are not so easily
worked as the former. A stone that has a high per cent, of alumina
(if it be also non-crystalline), or of organic matter, or of protoxide
of iron, will usually disintegrate rapidly. Such stones are gen-
erally of a bluish color.
25. Seasoning. The thorough drying of a stone before, and the
preservation of this dryness after, its insertion in masonry are com-
monly recognized as important factors of its durability; but the
•exact nature of the process of seasoning, and of the composition
•of the quarry-sap removed by thorough drying, have never been
determined. The quarry water may contain little else than ordinary
well-water, or may be a solution more or less nearly saturated, at the
•ordinary temperature, with carbonate of calcium, silica, double salts
•of calcium and magnesium, etc. In the latter case, hardening re-
sults from the drying, and an exact knowledge of its nature might
throw important light on the best means for the artificial preserva-
tion of stone. Again, water may exist in large quantity, in chemical
•combination, in the silicates (e.g., chlorite, kaolin, etc.), or in the
hydrated iron oxides which constitute the cement of a building
stone.
26. Physical Structure. The physical properties which con-
tribute to durability are hardness, toughness, homogeneity, con-
tiguity of the grains, and the structure — whether crystalline or
amorphous.
Although hardness (resistance to crushing) is often regarded as
the most important element, yet resistance to weathering does not
necessarily depend upon hardness alone, but upon hardness and the
non-absorbent properties of the stone. A hard material of close
.and firm texture is, however, in those qualities at least, especially
18
NATURAL STOKE. [CHAP. I,
fitted to resist friction, as in stoops,, pavements, and road metal, and
the wear of rain-drops, dripping rain-water, the blows of the waves,.
etc.
Porosity is an objectionable element. An excessive porosity in-
creases the layer of decomposition which is caused by the acids of
the atmosphere and of the rain, and also deepens the penetration of .
frost and promotes its work of disintegration.
If the constituents of a rock differ greatly in hardness, texture,,
solubility, porosity, etc., the weathering is unequal, the surface is
roughened, and the sensibility of the stone to the action of frost is
increased.
The principle which obtains in applying an artificial cement,
such as glue, in the thinnest film in order to secure the greatest
binding force finds its analogy in the building stones. The thinner
the films of the natural cement and the closer the grains of the pre-
dominant minerals, the stronger and more durable the stone. One
source of weakness in the famous brown-stone of New York City
lies in the separation of the rounded grains of quartz and feldspar
by a superabundance of ocherous cement. Of course the further-
separation produced by fissure, looseness of lamination, empty
cavities and geodes, and excess of mica tends to deteriorate still
further a weak building stone.
Experience has generally shown that a crystalline structure re-
sists atmospheric attack better than an amorphous one. This prin-
ciple has been abundantly illustrated in the buildings of New York
City* The same fact is generally true with the sedimentary rocks-
also, a crystalline limestone or good marble resisting erosion better
than earthy limestone. A stone that is compactly and finely granular
will exfoliate more easily by freezing and thawing than one that is-
coarse-grained. A stone that is laminar in structure absorbs mois-
ture unequally and will be seriously affected by unequal expansion
and contraction, — especially by freezing and thawing. Such a stone
will gradually separate into sheets. A stone that has a granular
texture, as contrasted with one that is crystalline or fibrous, will
crumble sooner by frost and by chemical agents, because of the-
easy dislodgment of the individual grains.
The condition of the surface, whether rough or polished, in-
fluences the durability, — the smoother surface being the better.
ART. 2.] TESTS OF BUILDING STONES. 19
The stone is more durable if the exposed surface is vertical than if
inclined. The lamination of the stone should be horizontal.
27. METHODS OF TESTING DURABILITY. It has long been recog-
nized that there are two ways in which we can form a judgment of
the durability of a building stone, and these may be distinguished
as natural and artificial.
28. Natural Methods. These must always take the precedence
whenever they can be used, because they involve (1) the exact
agencies concerned in the atmospheric attack upon stone, and (2)
long periods of time far beyond the reach of artificial experiment.
One method is to visit the quarry and observe whether the ledges
that have been exposed to the weather are deeply corroded, or
whether these old surfaces are still fresh. In applying this test,
consideration must be given to the modifying effect of geological
phenomena. It has been pointed out that "the length of time the
ledges have been exposed, and the changes of actions to which,
they may have been subjected during long geological periods, are
unknown; and since different quarries may not have been exposed
to the same action, they do not always afford definite data for re-
liable comparative estimates of durability, except where different
specimens occur in the same quarry."
North of the glacial limit, all the products of decomposition
have been planed away and deposited as drift-formation over the
length and breadth of the land. The rocks are therefore, in gen-
eral, quite fresh in appearance, and possess only a slight depth of
cap or worthless rock. The same classes of rock, however, in the
South are covered with rotten products from long ages of atmos-
pheric action.
A study of the surfaces of old buildings, bridge piers, monu-
ments, tombstones, etc., which have been exposed to atmospheric
influences for years, is one of the best sources of reliable information
concerning the durability of stone. A durable stone will retain the
tool-marks made in working it, and preserve its edges and corners
sharp and true.
29. Artificial Methods of Testing Durability. The older but
less satisfactory methods are: determining (1) the resistance to
crushing, (2) the absorptive power, (3) the resistance to the expan-
sion of frost, by saturating the stone with some solution which will
crystallize in the pores of the stone and produce an effect similar to
frost, (4) the solubility in acids, and (5) microscopical examination.
NATUKAL STONE.
[CHAP. i.
30. Absorptive Power. The ratio of absorption depends largely
on the density, — a dense stone absorbing less water than a lighter,
more porous one. Compactness is therefore a matter of impor-
tance, especially in cold climates; for if the water in a stone is once
allowed to freeze, it destroys the surface, and the stone very speedily
crumbles away. Other things being equal, the less the absorption
the better the stone.
To determine the absorptive power, dry the specimen and weigh
it carefully; then soak it in water for 24 hours, and weigh again.
The increase in weight will be the amount of absorption. Table 4
shows the weight of water absorbed by the stone as compared with
the weight of the dry stone — that is, if 300 units of dry stone weigh
301 units after immersion, the absorption is 1 in 300, and is recorded
as 1-300.
Dr. Hiram A. Cutting, State Geologist of Vermont, determined
the absorptive power * by placing the specimens in water under the
receiver of an air-pump, and found the ratio of absorption a little
larger than is given in the following table. It is believed that the
results given below more nearly represent the conditions of actual
practice. The values in the ee Max/' column are the means of two
or three of the largest results, and those in the "Min." column of
two or three of the smallest. The value in the last column is the
- mean for 20 or more specimens.
TABLE 4.
ABSORPTIVE POWER OF STONE, BRICK, AKD MORTAR.
JXIND OF MATERIAL.
Max.
Min.
Average.
Granites
1-150
o
1-7*10
Marbles
1-150
o
1-300
Limestones
1-20
1-500
1-38
Sandstones
1-15
1-240
1 24.
Bricks
1-4
1-50
1 10
Mortars
1-2
1-10
1-4
RATIO OF ABSORPTION.
31. Effect of Frost. To determine the probable effect of frost
upon a stone, carefully wash, dry, and weigh samples, and then wet
* Van Nostrand's Engin'g Mag., vol. xxiv. pp. 491-95.
AET. 2.] TESTS OP BUILDING STOKES. 21
them and expose to alternate freezing and thawing, after which
wash, dry, and weigh again. The loss in weight measures the rela-
tive durability.
A quicker way of accomplishing essentially the same result is to
heat the specimens to 500° or 600° F., and plunge them, while hot,
into cold water. The following comparative results were obtained
by the latter method : *
Relative Ratio of Loss.
White brick 1
Red brick 2
Browu-stone (sandstone from Conn.). 5
Nova Scotia sandstone 14
32. Brard's Test. Brard's method of determining the effect of
frost is much used, although it does not exactly conform to the con-
ditions met with in nature. It consists in weighing carefully some
small pieces of the stone, which are then boiled in a concentrated
solution of sulphate of soda and afterwards hung up for a few days
in the open air. The salt crystallizes in the pores of the stone,
expands, and produces an effect somewhat similar to frost, as it
causes small pieces to separate in the form of dust. The specimens
are again weighed, and those which suffer the smallest loss of weight
are the best. The test is often repeated several times. It will be
seen that this method depends upon the assumption that the action
of the salt in crystallizing is similar to that of water in freezing.
This is not entirely correct, since it substitutes chemical and
mechanical action for merely mechanical, to disintegrate the stone,
thus giving the specimen a worse character than it really deserves.
The following results were obtained by this method: f
Relative Ratio of Loss.
Hard brick 1
Light dove-colored sandstone from Seneca, Ohio. ... 2
Coarse-grained sandstone from Nova Scotia 2
Coarse-grained sandstone from Little Falls, N. J 5
Coarse dolomite marble from Pleasantville, N. Y. . . . 7
Coarse-grained sandstone from Conn 13
Soft brick 16
Fine-grained sandstone from Conn 19
* Tenth Census of the U. S., vol. x., Report on the Quarry Industry, p. 384. For
a table showing essentially the same results, sec Van Nostrand's Engin'g Mag., vol.
xiv. p. 537.
t Tenth Census, vol. x., Report of the Quarry Industry, p. 385.
NATURAL STOOT. [CHAP. I.
33. Effect of the Atmosphere. To determine the effect of the
atmosphere of a large city, where coal is used for fuel, soak clean
small pieces of the stone for several days in water which contains one
per cent, of sulphuric and hydrochloric acids, agitating frequently.
If the stone contains any earthy matter likely to be dissolved by the
gases of the atmosphere, the water will be more or less cloudy or
muddy. The following results were obtained by this method: *
Relative Ratio of Loss.
White brick .............. . ...................... 1
Bed brick ......................................... 5
Nova Scotia stone ............. „ ................... 9
Brown-stone ....................................... 30
34. Microscopical Examination. It is now held that the best
method of determining the probable durability of a building stone
is to study its surface, or thin, transparent slices, under a micro-
scope. This method of study in recent years has been most fruit-
ful in developing interesting and valuable knowledge of a scientific
and truly practical character. An examination of a section by means
of the microscope will show, not merely the various substances which
compose it, but also the method according to which they are
arranged and by which they are attached to one another. For
example, " pyrites is considered to be the enemy of the quarryman
and constructor, since it decomposes with ease, and stains and dis-
colors the rock. Pyrites in sharp, well-defined crystals sometimes
decomposes with great difficulty. If a crystal or grain of pyrites is
embedded in soft, porous, light-colored sandstones, like those which
come from Ohio, its presence will with certainty soon demonstrate
itself by the black spot which will form about it in the porous
stone, and which will permanently disfigure and mar its beauty.
If the same grain of pyrites is situated in a very hard, compact, nen-
absorbent stone, the constituent minerals of which are not rifted or
cracked, this grain of pyrites may decompose and the products be
washed away, leaving the stone untarnished. "
35. METHODS OF PRESEKVING, Vitruvius, the Eoman architect,
two thousand years ago recommended that stone should be quamed
in summer when driest, and that it should be seasoned by being
allowed to lie two years before being used, so as to allow the natural
* Tenth Census, vol. x., Report on the Quarry Industry, p. 385.
ART. 3.] CLASSIFICATION" OF BUILDING STORES. 23
sap to evaporate. It is a notable fact, that in the erection of St.
Paul's Cathedral in London, England, Sir Christopher Wren re-
quired that the stone, after being quarried, should be exposed for
three years on the sea-beach, before its introduction into the
building.
The surfaces of buildings are often covered with a coating of
paint, coal-tar, oil, paraffine, soap and alum, rosin, etc., to preserve
them.
Another method of treatment consists in bathing the stone in
[Successive solutions, the chemical actions bringing about the forma-
tion of insoluble silicates in the pores of the stone. Eor example, if
& stone front is first washed with an alkaline fluid to remove dirt,
.and this followed by a succession of baths of silicate of soda or
potash, and the surface is then bathed in a solution of chloride of
lime, an insoluble lime silicate is formed. The soluble salt is then
washed away, and the insoluble silicate forms a durable cement and
checks disintegration. If lime-water is substituted for chlorate of
lime, there is no soluble chlorate to wash away.
There are a great many applications that have been used for the
prevention of the decay of building stones, as paint, oil, coal-tar,
bees-wax, rosin, paraffine, etc., and numerous chemical preparations
similar to that mentioned in the paragraph just above ; but all are
•expensive, and none have proved fairly satisfactory. *
It has already been stated that, in order to resist the effects of
both pressure and weathering, a stone should be placed on its nat-
ural bed. This simple precaution adds considerably to the dura-
bility of any stone.
ART. 3. CLASSIFICATION AND DESCRIPTION OF BUILDING STONES.
36. CLASSIFICATION. Building stones are. variously classified,
.according to geological position, physical structure, and chemical
•composition.
37. Geological Classification. The geological position of rocks
has but little connection with their properties as building materials.
As a general rule, the more ancient rocks are the stronger and the
* For an elaborate and valuable article by Prof. Eggleston on the causes of decay
and the methods of preserving building stones, see Trans. Am. Soc. of C. E., vol.
xv. pp. 647-704 ; and for a discussion on the same, see same volume, pp. 705-16.
JtfATUKAL STOKE. [CHAP. I,
more durable ; but to this there are many exceptions. According
to the usual geological classification, rocks are divided into igneous,
metamorphic, and sedimentary. Greenstone, basalt, and lava are
examples of igneous rocks ; granite, marble, and slate, of meta-
morphic ; and sandstone, limestone, and clay, of sedimentary. Al-
though clay can hardly be classed with building stones, it is not
entirely out of place in this connection, since it 'is employed in
making bricks and cement, which are important elements of
masonry.
38. Physical Classification. "With respect to the structural
character of large masses, rocks are divided into stratified and un-
stratified.
In their more minute structure the unstratified rocks present,
for the most part, an aggregate of crystalline grains, firmly adhering'
together. Granite, trap, basalt, and lava are examples of this class.
In the more minute structure of stratified rocks, the following
varieties are distinguished : 1. Compact crystalline structure ; ac-
companied by great strength and durability, as in quartz-rock and
marble. 2. Slaty structure, easily split into thin layers ; accom-
panied by both extremes of strength and durability, clay-slate and
hornblende-slate being the strongest and most durable. 3. The-
granular crystalline structure, in which crystalline grains either
adhere firmly together, as in gneiss, or are cemented into one mass-
by some other material, as in sandstone ; accompanied by all degrees-
of compactness, porosity, strength, and durability, the lowest ex-
treme being sand. 4. The compact granular structure, in which
the grains are too small to be visible to the unaided eye, as in blue
limestone ; accompanied by considerable strength and durability.
5. Porous, granular structure, in which the grains are not crystal-
line, and are often, if not always, minute shells cemented together;.
accompanied by a low degree of strength and durability. 6. The=
conglomerate structure, where fragments of one material are embed-
ded in a mass of another, as graywacke; accompanied by all degrees-
of strength and durability.
A study of the fractured surface of a stone is one means of
determining its structural character. The even fracture, when the
surfaces of division are planes in definite positions, is characteristic
of a crystalline structure. The uneven fracture, when the broken
surface presents sharp projections, is characteristic of a granular
ART. 3.] CLASSIFICATION OF BUILDING STONES. 25
structure. The slaty fracture gives an even surface for planes of
division parallel to the lamination, and uneven for other directions
of division. The conchoidal fracture presents smooth concave and
convex surfaces, and is characteristic of a hard and compact struct-
ure. The earthy fracture leaves a rough, dull surface, and indi-
cates softness and brittleness.
39. Chemical Classification. Stones are divided into three
classes with respect to their chemical composition, each distin-
guished by the earth which forms its chief constituent ; viz., sili-
ceous stones, argillaceous stones, and calcareous stones.
Siliceous Stones are those in which silica is the characteristic earthy
constituent. With a few exceptions their structure is crystalline-
granular, and the crystalline grains contained in them are hard and
durable ; hence weakness and decay in them generally arise from
the decomposition or disintegration of some softer and more perish-
able material, by which the grains are cemented together, or, when
they are porous, by the freezing of water in their pores. The prin-
cipal siliceous stones are granite, syenite, gneiss, mica-slate, green-
stone, basalt, trap, talc, soapstone, quartz-rock, hornblende-slate,
and sandstone.
Argillaceous or Clayey Stones are those in which alumina, although
it may not always be the most abundant constituent, exists in suf-
ficient quantity to give the stone its characteristic properties. The
principal kinds are porphyry, clay, slate, and graywacke-slate.
Calcareous Stones are those in which carbonate of lime pre-
dominates. They effervesce with the dilute mineral acids, which
combine with the lime and set free carbonic acid gas. Sulphuric
acid forms an insoluble compound with the lime. Nitric and mu-
riatic acids form compounds with it, which are soluble in water.
By the action of intense heat the carbonic acid is expelled in gas-
eous form, and the lime is left in its caustic or alkaline state, when
it is called quicklime. Some calcareous stones consist of pure car-
bonate of lime ; in others it is mixed with sand, clay, and oxide
of iron, or combined with carbonate of magnesia. The durability
of calcareous stones depends upon their compactness, those which
arc porous being disintegrated by the freezing of water, and by the
chemical action of an acid atmosphere. They are, for the most
part, easily wrought. The principal calcareous stones are marble,.
26 NATURAL STONE. [CHAP. I.
compact limestone, granular limestone (the calcareous stone of the
geological classification), and magnesian limestone or dolomite.
40. DESCRIPTION OF BUILDING STONES. A few of the more
prominent classes of building stones will now be briefly described.
41. Trap. Although trap is the strongest of building materials,
and exceedingly durable, it is little used, owing to the great diffi-
culty with which it is quarried and wrought. It is an exceedingly
tough rock, and, being generally without cleavage or bedding, is
especially intractable under the hammer or chisel. It is, however,
sometimes used with excellent effect in cyclopean architecture, the
blocks of various shapes and sizes being fitted together with no
effort to form regular courses. The ' ' Palisades" (the bluff skirting
the western shore of the Hudson Eiver, opposite and above New
York) are composed of trap-rock, — much used for road-metal, street
pavements, and railroad ballast.
42. Granite. Granite is the strongest and most durable of all
tlje stories in common use. It generally breaks with regularity,
.and may be quarried in simple shapes with facility ; but it is ex-
tremely hard and tough, and therefore can only be wrought into
elaborate forms with a great expenditure of labor. For this reason
the use of granite is somewhat limited. Its strength and durability
commend it, however, for foundations, docks, piers, etc., and for
massive buildings ; and for these purposes it is in use the world
over. .
The larger portion of our granites are some shade of gray in
color, though pink and red varieties are not uncommon, and black
varieties occasionally occur. They vary in texture from very fine
and homogeneous to coarsely porphyritic rocks, in which the indi-
vidual grains are an inch or more in length. Excellent granites are
found in New England, throughout the Alleghany belt, in the
Eocky Mountains, and in the Sierra Nevada. Very large granite
quarries exist at Vmalhaven, Maine ; Gloucester and Quincy, Mas-
sachusetts; and at Concord, New Hampshire. These quarries fur-
nish nearly all the granite used in this country. An excellent
granite, -which is largely used at Chicago and in the Northwest, is
found at St. Cloud, Minnesota.
At the Vinalhaven quarry a single block 800 feet long, 20 feet
wide, and 6 to 10 feet thick was blasted out, being afterwards broken
up. Until recently the largest single block ever quarried and
ART. 3.J CLASSIFICATION OF BUILDING STONES. 27
%
dressed in this country was that used for the General Wool Monu-
ment, now in Troy, New York, which measured, when completed,
60 feet in height by 5.-J- feet square at the base, being only 9 feet
shorter than the Egyptian Obelisk now in Central Park, New York.
lu 1887 the Bodwell Granite Company took out from its quarries in
Maine a granite shaft 115 feet long, 10 feet square at the base, and
weighing 850 tons. It is claimed that this is the largest single
quarried stone on record.
43. Marbles. In common language, any limestone which will take
A good polish is called a marble ; but the name is properly applied
only to limestones which have 'been exposed to metamorphic action,
and have thereby been rendered more crystalline in texture, and
have had their color more or less modified or totally removed.
Marbles exhibit great diversity of color and texture. They are
pure white, mottled white, gray, blue, black, red, yellow, or mot-
tled with various mixtures of these colors. Marble is confessedly
the most beautiful of all building materials, but is chiefly employed
for interior decorations.
44. Limestones. Limestones are composed chiefly or largely of
carbonate of lime. There are many varieties of limestone, which
differ in color, composition, and value for engineering and building
purposes, owing to the differences in the character of the deposits
and chemical combinations entering into them. "If the rock is
compact, fine-grained, and has been deposited by chemical agencies,
we have a variety of limestone known as travertine. If it contains
much sand, and has a more or less conclioidal fracture, we have a
siliceous limestone. If the silica is very fine-grained, it is horn-
stone. If the silica is distributed in nodules or flakes, either in
seams or throughout the mass, it is cherty limestone; if it contains
silica and clay in about equal proportions, hydraulic limestone ; if
day alone is the principal impurity, argillaceous limestone ; if iron
is the principal impurity, ferruginous limestone ; if iron and clay
exceed the lime, ironstone. If the ironstone is decomposed, and
the iron hydratetl, it is rottenstone; if carbonate of magnesia forms
one third or less, magnesian limestone ; if carbonate of magnesia
forms more than one third, dolomitic limestone."
The lighter-colored and fine-grained limestones, when sawed and
used as ashlars, are deservedly esteemed as among our best building
materials. They are, however, less easily and accurately worked
28 NATURAL STOISTB. [CHAP. I.
under the chisel than sandstones,, and for this reason and their
greater rarity are far less generally used. The gray limestones, like
that of Lockport, New York,, when hammer-dressed, have the ap-
pearance of light granite, and, since they are easily wrought, they
are advantageously used for trimmings in buildings of brick.
Some of the softer limestones possess qualities which specially
commend them for building materials. For example, the cream-
colored limestone of the Paris basin (calcaire grassier) is so soft that
it may be dressed with great facility, and yet hardens on exposure,
and is a durable stone. Walls laid up of this material are frequently
planed down to a common surface, and elaborately ornamented at
small expense. The Topeka stone, found and now largely used in
Kansas, has the same qualities. It may be sawed out in blocks-
almost as easily as wood, and yet is handsome and durable when
placed in position. The Bermuda stone and coquina are treated in
the same way.
Large quantities of limestones and dolomites are quarried in
nearly all of the Western States. These are mostly of a dull grayish
color, and their uses are chiefly local. The light-colored oolitic
limestone of Bedford, Indiana, is, however, an exception to this-
rule. Not only are the lasting qualities fair and the color pleasing,
but its fine even grain and softness render it admirably adapted, for
carved work. It has been very widely used within the last few
years. This stone is often found in layers 20 and 30 feet thick, and
is much used for bridge piers and other massive work. There are
noted limestone quarries at Dayton and Sandusky, Ohio; at Bedford,
Ellettsville, and Salem, Indiana; at Joliet, Lemont, Grafton, and
Chester, Illinois; and at Cottonwood, Kansas.
45. Sandstones. "Sandstones vary much in color and fitness for
architectural purposes, but they include some of the most beautiful,
durable, and highly valued materials used in construction. What-
ever their differences, they have this in common, that they are
chiefly composed of sand — that is, grains of quartz — to a greater or
less degree cemented and consolidated. They also frequently con-
tain other ingredients, as lime, iron, alumina, manganese, etc., by
which the color and texture are modified. Where a sandstone is.
composed exclusively of grains of quartz, without foreign matter, it
may be snow-white in color. Examples of this variety are known
' in many localities. They are rarely used for building, though capa-
ART. 3.] CLASSIFICATION OF BUILDING STONES. 29
ble of "being employed for that purpose with excellent effect. They
have been more generally valued as furnishing material for the man-
ufacture of glass. The color of sandstones is frequently bright and
handsome, and constitutes one of the many qualities -which have
rendered them so popular. It is usually caused by iron; when gray,
blue, or green, by the protoxide, as carbonate or silicate ; when
brown, by the hydrated oxide ; when red, by the anhydrous oxide.
The purple sandstones usually derive this shade of color from a
small quantity of manganese.
ee The texture of sandstones varies with the coarseness of the
sand of which they are composed, and the degree to which it is con-
solidated. Usually the material which unites the grains of sand
is silica; and this is the best of all cements. This silica has been
deposited from solution, and sometimes fills all the interstices be-
tween the grains. If the process of consolidation has been carried
far enough, or the quartz grains have been cemented by fusion, the
sandstone is converted into quartzite, — one of the strongest and most
durable of rocks, but, in the ratio of its compactness, difficult to
work. Lime and iron often act as cements in sandstones, but both
are more soluble and less strong than silica. Hence the finest and
most indestructible sandstones are such as consist exclusively of
grains of quartz united by siliceous cement. In some sandstones
part of the grains are fragments of feldspar, and these, being liable
to decomposition, are elements of weakness in the stone. The very
fine-grained sandstones often contain a large amount of clay, and
thus, though very handsome, are generally less strong than those
which are more purely siliceous.
" The durability of sandstones varies with both their physical
and chemical composition. When nearly pure silica and well ce-
mented, sandstones are as resistant to weather as granite, and very
much less affected by the action of fire. Taken as a whole, they
may be regarded as among the most durable of building materials.
When first taken from the quarry, and saturated with quarry water
(a weak solution of silica), they are frequently very soft, but on ex-
posure become nmch harder by the precipitation of the soluble siliqa
contained in them.
46. "Since they form an important part of all the groups of
sedimentary rocks, sandstones are abundant in nearly all countries;
and as they are .quarried with great ease, and are wrought with the
30 NATURAL STOJSTE. [CHAP. I,
hammer and chisel with much greater facility than limestones,
granites, and most other kinds of rocks, these qualities,, joined to-
their various and pleasant colors and their durability, have made
them the most popular and useful of building stones. In the
United States we have a very large number of sandstones which an
extensively used for building purposes.
" Among these may be mentioned the Dorcliesler stone of New
Brunswick, and Brown-stone of Connecticut and New Jersey.
These have been much used in the buildings of the Atlantic cities.
The latter has been very popular, but experience has shown it to be
seriously lacking in durability.
" Among the sandstones most frequently employed in the build-
ing of the interior are : —
1. '" The Ohio stone, derived from the Berea grit, a member of
the Lower Carboniferous series in Northern Ohio. The principal
quarries are located at Amherst and Berea. The stone from Am-
herst is generally light drab in color, very homogeneous in texture,
and composed of nearly pure silica. It is very resistant to fire and
weathering, and is, on the whole, one of the best and handsomest
building stones known. The Berea stone is lighter in color than
the Amherst, but sometimes contains sulphide of iron, and is then
liable to stain and decompose.
2. '• Tlie Waverly sandstone, also derived from the Lower Car-
boniferous series, comes from Southern Ohio. This is a fine-
grained homogeneous stone of a light-drab or dove color, works with
facility, and is very handsome and durable. It forms the material
of which many of the finest buildings of Cincinnati are constructed,
and is, justly, highly esteemed there and elsewhere.
3. " The Lake Superior sandstone is a dark, purplish-brown
stone of the Potsdam age, quarried at Bass Island, Marquette, etc.
This is rather a coarse stone, of medium strength, but homogeneous
and durable, and one much used in the Lake cities.
4. " The St. Genevieve stone is a fine-grained sandstone of a del-
icate drab or straw color, very homogeneous in tone and texture.
It is quarried at St. Genevieve, Missouri, and is one of the hand-
somest of all our sandstones.
5. " The Medina sandstone^ which forms the base of the Upper
Silurian series in Western New York, furnishes a remarkably strong
ART. 3.] CLASSIFICATION OF BUILDING- STOKES.
31
and durable stone, much used for pavement and curbing in the
Lake cities.
6. " The coal-measures of Pennsylvania,, Ohio, and other "West-
ern States supply excellent sandstones for building purposes at a
large number of localities. These vary in color from white to dark
red or purple, though generally gray or drab. While strong and
durable, they are mostly coarser and less handsome than the sand-
stones which have been enumerated above. This is the source from
which are derived the sandstones used in purely engineering struc-
tures."*
47. Other Names. There is a great variety of names of more-
or less local application, derived from the appearance of the stone,
the use to which it is put, etc., which it would be impossible to
classify. The same stone often passes under entirely different
names in different localities ; and stones entirely different in their
essential characteristics often pass under the same name.
48. LOCATION OF QUARRIES. For further information concern-
ing location of stone quarries, character of product, etc., see Vol. X.,
Tenth Census, Report on Quarry Industry, pp. 50-101, and also
the reports of the various State geological surveys.
WEIGHT OF STONE.
49. The following table contains the weight of the stones most
frequently met with.
TABLE 5.
WEIGHT OF BUILDING STONES.
KIND OF STONE.
POUNDS PER. CUBIC FOOT.
Min.
Max.
Mean.
Granites
161
178
167
Limestones
146
174
158
Marbles
157
180
170
Sandstones
127
151
139
Slates t . . .
160
175
174
If it is desired to find the exact weight per cubic foot of a given
stone, it is generally easier to find its specific gravity first, and then
* Prof. J. S. Newbcrry.
KATUKAL ST02TE. [CHAP. I.
multiply by 62.4, — the weight, in pounds, of a cubic foot of water.
This rrfethod obviates, on the one hand, the expense of dressing a
.sample to regular dimensions, or, on the other hand, the inaccuracy
•of measuring a rough, irregular piece. Notice, however, that this
method determines the weight of a cubic foot of the solid stone,
which will be more than the weight of a cubic foot of the material
as used for structural purposes. In finding the specific gravity
there is some difficulty in getting the correct displacement of
porous stones, — and all stones are more or less porous. There are
various methods of overcoming this difficulty, which give slightly
different results. The following method, recommended by General
G-illmore, is most frequently used:
All loose grains and sharp corners having been removed from
the sample and its weight taken, it is immersed in water and
weighed there after all bubbling has ceased. It is then taken out
of the water, and, af fcer being compressed lightly in bibulous paper
to absorb the water on its surface, is weighed again. The specific
•gravity is found by dividing the weight of the dry stone by the
•difference between the weight of the saturated stone in air and in
water. Or expressing this in a formula,
W
Specific gravity =
_ w//9
in which W represents the weight of dry stone in air, W the
weight of saturated stone in air, W" the weight of stone immersed
in water.
50. COST OF STONE. See §§ 226-38.
CHAPTER II.
BRICK.
51. BRICK is made by submitting clay, which has been prepared
properly and moulded into shape, to a temperature which converts
it into a semi-vitrified mass.
Common brick is a most valuable substitute for stone. Its
•comparative cheapness, the ease with which it is transported and
handled, and the facility with which it is worked into structures of
any desired form, are its valuable characteristics. It is, when prop-
erly made, nearly as strong as the best building stone. It is but
slightly affected by change of temperature or of humidity; and is
also lighter than stone.
Notwithstanding the good qualities which recommend brick as
.a substitute for stone, it is very little used in engineering structures.
It is employed in the construction of sewers and bridge piers, and
for the lining of tunnels. Brick could many times be profitably
.substituted for iron, stone, or timber in engineering structures.
'This is especially true since recent improvements iri the process of
manufacture have decreased the cost while they have increased the
•quality and the uniformity of the product. The advantages of
employing brick-work instead of stone masonry will be discussed in
•connection with brick masonry in Chapter VIII. Probably one
thing which has prevented the more general use of brick in engi-
neering is the variable quality of the product and the trouble of
proper inspection.
52. PROCESS OF MANUFACTURE. The Clay. The quality of the
brick depends primarily upon the kind of clay. Common clays, of
which the common brick is made, consist principally of silicate of
.alumina; but they also usually contain lime, magnesia, and oxide
of iron. The latter ingredient is useful, improving the product by
giving it hardness and strength; hence the red brick of the Eastern
States is often of better quality than the white and yellow brick
made in the West. Silicate of lime renders the clay too fusible,
33
BRICK. [CHAP, n,
and causes the bricks to soften and to become distorted in the pro-
of burning. Carbonate of lime is certain to decompose in
burning, and the caustic lime left behind absorbs moisture, prevents
the adherence of the mortar, and promotes disintegration.
Uncombined silica, if not in excess, is beneficial, as it preserves
the form of the brick at high temperatures. In excess it destroys
the cohesion, and renders the bricks brittle and weak. Twenty-five
per cent, of silica is a good proportion.
53. Moulding. Iu the old process the clay is tempered with
water and mixed to a plastic state in a pit with a tempering wheel,
or in a primitive pug-mill; and then the soft, plastic clay is pressed
into the moulds by hand. This method is so slow and laborious-
that it has been almost entirely displaced by more economical and
expeditious ones in which the work is done wholly by machinery.
There is a great variety of machines for preparing and moulding
the clay, which, however, may be grouped into three classes, accord-
incr to the condition of the clay when moulded: (1) soft-mud
machines, for which the clay is reduced to a soft mud by adding
about one quarter of its volume of water; (2) stiff-mud machines,
for which the clay is reduced to a stiff mud; and (3) dry-clay
machines, with which the dry, or nearly dry, clay is forced into the
moulds by a heavy pressure without having been reduced to a plastic
mass. These machines may also be divided into two classes, accord-
ing to the method of filling the moulds: (1) Those in which a con-
tinuous stream of clay is forced from the pug-mill through a die
and is afterwards cut up into bricks; and (2) those in which the
clay is forced into moulds moving under the nozzle of the pug-mill.
54. Burning. The time of burning varies with the character of
the clay, the form and size of kiln, and the kind of fuel. With the
older processes of burning, the brick, when dry enough, is built up
in sections— by brick-makers called "arches/' — which are usually
about 5 bricks (34- feet) wide, 30 to 40 bricks (20 to 30 feet) deep,
and from 35 to 50 courses high. Each section or " arch" has an
opening— called an " eye" — at the bottom in the center of its width,
which runs entirely through the kiln, and in which the fuel used in
burning is placed. After the bricks are thus stacked up, the entire-
pile is enclosed with a wall of green brick, and the joints between
the casing bricks are carefully stopped with mud. Burning, includ-
ing drying, occupies from 6 to 15 days. The brick is first subjected
CLASSIFICATION OF COMMOX BRICK. 35
to a moderate heat, and when all moisture has been expelled, the
heat is increased slowly until the " arch-brick/' i. e.} those next to
the "eye," attain a white heat. This temperature is kept up until
the burning is complete. Finally, all openings are closed, and the
mass slowly cools.
With the more modern processes of burning, the principal yards
have permanent kilns. These are usually either a rectangular space
surrounded, except for very wide doors at the ends, by permanent
brick walls haying fire-boxes on the outside; or the kiln may be
entirely enclosed — above as well as on the sides — with brick masonry.
The latter are usually circular, and are sometimes made in com-
partments, each of which has a separate entrance and independent
connection with the chimney. The latter may be built within the
kiln or entirely outside, but a downward draught is invariably
secured. The fuel, usually fine coal, is placed near the top of the
kiln, and the down draught causes a free circulation of the flame
and heated gases about the material being burned. While some
compartments are being fired others are being filled, and still
others are being emptied.
55. FIRE BRICK. Fire bricks are used whenever very high
temperatures are to be resisted. They are made either of a very
nearly pure clay, or of a mixture of pure clay and clean sand, or, in
rare cases, of nearly pure silica cemented with a small proportion
of clay. The presence of oxide of iron is very injurious, and, as a
rule, the presence of 6 per cent, justifies the rejection of the brick.
In specifications it should generally be stipulated that fire brick
should contain less than 6 per cent, of oxide of iron, and less than
an aggregate of 3 per cent, of combined lime, soda, potash, and
magnesia. The sulphide of iron — pyrites — is even worse in its
effect on fire brick than the substances first named.
When intended to resist only extremely high heat, silica should
be in excess; and if to be exposed to the action of metallic oxides,
which would tend to unite with silica, alumina should be in excess.
Good fire brick should be uniform in size, regular in shape,
homogeneous in texture and composition, .easily cut, strong, and
infusible.
56. CLASSIFICATION' OF COMMON BRICK. Bricks are classified
according to (1) the way in which they are moulded; (2) their
position in the kiln while being burned; and (3) their form or use.
36 BRICK. [CHAP. n.
1* The method of moulding gives rise to the following terms:
Soft-mud Brick. One moulded from clay which has been reduced
to a soft mud by adding water. It may be either hand-moulded or
machine-moulded.
Stiff-mud Bride. One moulded from clay in the condition of
stiff mud. It is always machine-moulded.
Pressed Brick. One moulded from dry or semi-dry clay.
Re-pressed Brick. A soft-mud brick which,, after being par-
tially dried, has been subjected to an enormous pressure. Ifc is
also called,, but less appropriately,, pressed brick. The object of
the re-pressing is to render the. form more regular and to increase
the strength and density.
Slop Brick. In moulding brick by hand, the moulds are some-
times dipped into water just before being filled with clay, to pre-
vent the mud from sticking to them. Brick moulded by this
process is known as slop brick. It is deficient in color, and has a
comparatively smooth surface, with rounded edges and corners.
This kind of brick is now seldom made.
Sanded Brick. Ordinarily, in making soft-mud brick, sand is
sprinkled into the moulds to prevent the clay from sticking ; the
brick is then called sanded brick. The sand on the surface is of no
serious advantage or disadvantage. In hand-moulding, when sand
is used for this purpose, it is certain to become mixed with the clay
and occur in streaks in the finished brick, which is very undesira-
ble ; and owing to details of the process, which it is here unneces-
sary to explain, every third brick is especially bad.
Machine-made Brick. Brick is frequently described as " ma-
chine-made;" but this is very indefinite, since all grades and kinds
are made by machinery.
2. "When brick was generally burned in the old-style up-draught
kiln, the classification according to position was important ; but
with the new styles of kilns and improved methods of burning, the
quality is so nearly uniform throughout the kiln, that the classifica-
tion is less important. Three grades of brick are taken from the
old-style kiln:
Arch or Clinker Bricks. Those which form the tops and sides of
the arches in which the fire is built. Being over-burned and par-
tially vitrified, they are hard., brittle, and weak.
EEQUISITBS FOll GOOD BRICK. 3?
Body, Cherry, or Hard Bricks. Those taken from the interior
of the pile. The best bricks in the kiln.
Salmon, Pale, or Soft Bricks. Those which form the exterior of
the mass. Being under-burned, they are too soft for ordinary work,
unless it be for filling. The terms salmon and pale refer to the
color of the brick, and hence are not applicable to a brick made of
a clay that does not burn red. Although nearly all brick clays burn
red, yet the localities where the contrary is true are sufficiently
numerous to make it desirable to use a different term in designating
the quality. There is, necessarily, no relation between color, and
strength and density. Brick-makers naturally have a prejudice
against the term soft brick, which doubtless explains the nearly
universal prevalence of the less appropriate term — salmon.
3. The form or use of bricks gives rise to the following classifi-
cation:—
Compass Brick. Those having one edge shorter than the other.
Used in lining shafts, etc.
Feather-edge Brick. Those of which one edge is thinner than
the other. Used in arches ; and more properly, but less frequently,
called voussoir brick.
.Face Brick. Those which, owing to uniformity of size and
color, are suitable for the face of the wall of buildings. Sometimes
face bricks are simply the best ordinary brick ; but generally the
term is applied only to re-pressed or pressed brick made specially for
this purpose. They are a little larger than ordinary bricks (§ 62).
Sewer Brick. Ordinary hard brick, smooth, and regular in
form.
Paving Brick. Very hard, ordinary brick. A vitrified claj
block, very much larger than ordinary brick, is sometimes used for
paving, and is called a paving brick, but more often, and more
properly, a brick paving-block.
57. REQUISITES FOR GOOD BRICK. 1. A good brick should have
plane faces, parallel sides, and sharp edges and angles. 2. It should
bo of fine, compact, uniform texture ; should be quite hard; and
should give a clear ringing sound when struck a sharp blow. 3. It
should not absorb more than one tenth of its weight of water. 4.
Its specific gravity should be 2 or more. 5. The crushing strength
of half brick, when ground flat and pressed between thick metal
38 BRICK. [CHAP. n.
plates, should be at least 7,000 pounds per square inch. C. Its mod-
ulus of rupture should be at least 1,000 pounds per square inch.
1. In regularity of form re-pressed brick ranks first, dry-clay
brick next, then stiff-mud brick, and soft-mud brick last. Regu-
larity of form depends largely upon the method of burning.
2. The compactness and uniformity of texture, which greatly
influence the durability of brick, depend mainly upon the method
of moulding. As a general rule, hand-moulded bricks are best in
this respect, since the clay in them is more uniformly tempered be-
fore being moulded ; but this advantage is partially neutralized by
the presence of sand seanis (§ 56). Machine-moulded soft-mud
bricks rank next in compactness and uniformity of texture. Then
come machine-moulded stiff-mud bricks, which vary greatly in
durability with the kind of machine used in their manufacture.
By some of the machines, the brick is moulded in layers (parallel to
any face, according to the kind of machine), which are not thor-
oughly cemented, and which separate under the action of the frost.
In compactness, the dry-clay brick comes last. However, the rela-
tive value of the products made by the different processes varies
with the nature ot the clay used.
3. The absorptive power is one of the most important elements,
since it greatly affects the durability of the brick, particularly its
resistance to the effect of frost (see §§ 31 and 32). Very soft, un-
der-burned brick will absorb from 25 to 33 per cent, of their weight
of water. Weak, light-red ones,, such as are frequently used in fill-
ing in the interior of walls, will absorb about 20 to 25 per cent. ;
while the best brick will absorb only 4 or 5 per cent. A brick may
be called good which will absorb not more than 10 per cent. See
Table 9 (page 45).
4. The specific gravity of a brick does not indicate its quality,
and depends mainly upon the amount of burning and the kind of
fuel employed. Over-burned arch bricks, being both smaller and
heavier than the better body "bricks, have a considerably greater
specific gravity, although inferior in quality.
5. The crushing strength is not' a certain index of the value of a
brick, although it is always one of the items determined in testing
brick — if a testing-machine is at hand. For any kind of service,
the durability of a brick is of greater importance than its ability,
to resist crushing, — the latter is only remotely connected with dura-
ABSORBING POWER. 3Q
bility. Tests of the crushing strength of individual bricks are use-
ful only in comparing different kinds of brick, and give no idea of
the strength of walls built of such bricks (see § 246). Furthermore,
the crushing strength can not be determined accurately, since it
varies greatly with the size of the specimen and with the details of
the experiments (see § 60).
6. Owing to both the nature of the quality tested and the facility
-with which such a test can be made, • the determination of the
transverse strength is one of the best means of judging of the
quality of a brick. The transverse strength depends mainly upon
the toughness of the brick, — a quality of prime importance in bricks
used for paving, and also a quality greatly affecting the resistance to
frost.
58. ABSORBING- POWER. The less the amount of water absorbed
by a brick the greater, in all probability, will be its durability.
The amount of water absorbed is, then, an important consideration
:*n determining the quality of a brick. There are different methods
in use for determining the amount of water taken up by a brick,
and these lead to slightly different results. Some experimenters dry
the bricks in a hot-air chamber, while some dry them simply by ex-
posing them in a dry room; some experimenters immerse the bricks
in water in the open air, while others immerse them under the re-
ceiver of an air-pump; some immerse whole brick, and some use
small pieces; and, again, some dry the surface with bibulous paper,
while others allow the surface to dry by evaporation. Air-drying
most nearly represents the conditions of actual exposure in ma-
sonry structures, since water not expelled in that way is in such a
condition as not to do any harm by freezing. Immersion in the
open air more nearly represents actual practice than immersion in
a vacuum. The conditions of actual practice are best represented
by testing whole brick, since some kinds have a more or less im-
pervious skin. Drying the surface by evaporation is more accurate
than drying it with paper; however, neither process is susceptible
of mathematical accuracy.
The absorbing power given in Table 9, page 45, was determined
by (1) drying whole brick in a steam-heated room for three weeks,
(2) weighing and (3) immersing them in water for forty-four
hours; and then (4) drying for four hours — until all the water on
the surface was evaporated, — and, finally, (5) again weighing them.
BBICK.
[CHAP, ii.
The results in the table represent the mean of several observations.
If the brick had been kiln- dried, or weighed before the surface-
water was entirely removed, the apparent absorption would have-
been greater.
Comparing the absorbing power of brick a§ given in the table
on page 45 with that of stone on page 20, we see the absorbing
power of the best brick is about equal to that of average lime-
stone and sandstone, and much greater than marble and granite.
For a method of rendering brick non-absorbent, see §§ 263-64.
59. TEANSVEESE STRENGTH. The experiments necessary to
determine the transverse strength of brick are easily made (§ 15) 9
give definite results, and furnish valuable information concerning
the practical value of the brick; hence this test is one of the best in,
use.
Table 6 gives the results of experiments made by the author on
Illinois brick. The averages represent the results of from six to fifteen
TABLE 6.
TKANSVEBSE STRENGTH OF ILLINOIS BRICK.
(Summarized from. Table 9, page 45.)
Ret
No.
KIND OF BRICK.
MODULUS OF RUPTURE IN
LBS. PER SQ. IN.*
CO-EFFICIENT OF TRANS-
VERSE STRENGTH.*
Max.
Mm.
Average.
Max.
Min.
Aver.
1
2
3
4
5
Soft - clay, hand - moulded,
— best 50$ in kiln
2,233
2,354
1,475
495
4,348
846
1,135
764
150
2,235
1,409
1,712
1,114
336
3,217
124
142
82
27
241
47
63
42
8
124
78
95
62
19
178
Soft-clay, machine-mould-
ed,— best 50$ in kiln
Stiff-clay, machine-mould-
ed,— best 50$ in kiln
Dry- clay (pressed)
Secret Process
experiments on brick from three localities. The "Max." and
"Min." columns contain the average of the two highest and the-
two lowest results respectively.
The results in Table 7 were obtained under the direction of the-
Chief Engineer of the Lehigh Valley E. E. Each result represents
* For definition, see § 15.
CRUSHING STRENGTH.
41
the mean of seven to nine experiments on bricks from different
localities. The results in Table 6 are considerably greater than
TABLE 7.
TRANSVERSE STRENGTH OF EASTERN BRICK.
DESIGNATION OF BRICK.
MODULUS OF RUPTURE IN
LBS. PER SQ. IN.
CO-EFFICIENT OF TRANS-
VERSE STRENGTH.
Max.
Min.
Average.
Max.
Min.
Average.
Very hard
1,796
944
645
444
1,045
710
504
269
1,352
805
597
373
100
52
36
25
58
39
28
15
75
45
32
21
Hard
Medium
Soft
those in Table 7, the difference being due probably more to recent
improvements in the manufacture of brick and to the method of
selection than to locality. The brick from which the results in
Table 6 were derived were obtained from manufacturers well known
for the high quality of their products.
60. CRUSHING STRENGTH. It has already been explained (§§ 7
to 14) that the results for the crushing strength of stone vary
greatly with the details of the experiments; but this difference is
even greater in the case of brick than in that of stone. In testing
stone the uniform practice is to test cubes (§ 10) whose faces are
carefully dressed to parallel planes. In testing brick there is no-
settled custom. (1) Some experimenters test half brick while others
test whole ones; (2) some grind the pressed surfaces accurately to
planes, and some level up the surfaces by putting on a thin coat of
plaster of Paris, while others leave them in the rough; and (3) some
test the brick set on end, some on the side, and others laid flat-
wise.
1. Prom a series of experiments* on soft brick, the author con-
cludes that the crushing strength per square inch of a quarter of a
brick is about half that of a whole one; and that a half brick is
about two thirds, and three quarters of a brick about five sixths, as
strong per square inch as a whole one ; or, in other words, the
strength of a quarter, a half, and three quarters of a brick, and a
* Engineering News, vol. xxi. p.
4xJ BRICK. [CHAP. IT.
whole one, are to eacli other as 3, 4, 5, and C respectively. The
reason for this difference is apparent if a whole brick be conceived
as being made up of a number of cubes placed side by side, in which
case it is clear that the interior cubes will be stronger than the
exterior ones because of the side support derived from the latter.
For experiments showing the marked effect of this lateral support,
see § 273. The quarter brick and the half brick have less of this
lateral support than the whole one, and hence have correspondingly
less crushing strength.
2. The strength of the specimen will vary greatly with the degree
of smoothness of its bed-surfaces. To determine the difference
between reducing the pressed surfaces to a plane and leaving them
in the rough, the author selected six bricks of regular form and
apparently of the same strength, and tested three in the rough and
the other three after having reduced the pressed surfaces to planes
by laying on a coating of plaster of Paris, which, after drying, was
ground off to a plane. The amount of plaster remaining on the
surfaces was just sufficient to fill up the depressions. Both sets
were tested in a hydraulic press between cast-iron, parallel (self-
adjusting), pressing surfaces. The average strength of those that
were plastered was 2.06 times the strength of those that were not
plastered. This difference will vary with the relative strength of
the brick and the plaster. The average strength of the bricks whose
surfaces were plastered was 9,170 pounds per square inch, which is
more than that of the plaster used; and therefore it is highly
probable that if the surfaces had been reduced to planes by grind-
ing, the difference in strength would have been still greater. See
also the last paragraph of § 9.
3. As before stated, some experimenters test brick flatwise, some
edgewise, and some endwise. Since bricks are generally employed
in such a position that the pressure is on the broadest face, it seems
a little more satisfactory to lay the brick flatwise while testing it;
but since the only object in determining the crushing strength of
brick is to ascertain the relative strength of different bricks, — the
crushing strength of the brick is only remotely connected with the
crushing strength of the brick-masonry (§ 240),— -the position of the
brick while being tested is not a matter of vital importance. Doubt-
less the principal reason for testing them on, end or edgewise is to
bring them within the capacity of the testing-machine. However,
CIU'HIHHG STRENGTH. 43
there is one good reason against testing brick flatwise; viz.; all
homogeneous granular bodies fail under compression by shearing
along planes at about 45° with the pressed surfaces, and hence if
the height is not sufficient to allow the shearing stresses to act
freely, tin abnormal strength is developed. See also § 10.
The relative .strength of brick tested in the three positions — flat-
wise, edgewise^ and endwise- — varies somewhat with the details of
the experiments; but it is reasonably well settled that the strength
of homogeneous brick flatwise between steel or cast-iron pressing
mirfae.es is one and a half to two times as much as when the brick is
tested on end. A few experiments by the author* seem to indicate
that the strength edgewise is a little more than a mean between the
strength flatwise and endwise. If the brick is laminated (see para-
graph fc-2, & f>7), the relative strength for the three positions — flat-
wise, edgewise, and endwise-— will vary greatly with the direction of
the grain.
61. Comparatively few experiments have been made to deter-
mine the strength of brick, and they are far from satisfactory, since
the manner of making the experiment is seldom recorded. The
<liiToroneOH in the details of the experiments, together with the
<U (Terences in the quality of the bricks themselves, are sufficient to
oause a wide variation in the results obtained by different observers.
The following data are given for reference and comparisons.
The results in Table 8 (page 44) were made with the U. S.
teHt ing- machine at the Watortown (Mass.) Arsenal, f In each
experiment the pressed surfaces were " carefully ground flat and
not in a thin facing of plaster of Paris, and then tested between steel
pressing surfaces.''
The experiments given in Table 0 (page 45) were made by the
author, on Illinois brick. The bricks were crushed between self-
adjusting east-iron pressing surfaces. Although No. 11 shows an
a vorage absorption, a moderate transverse strength, and a high crush-
wg strength, this particular brand of brick disintegrated rapidly by
the frost. Thin is characteristic of this class of brick, and is caused
hy the ehiy'rf being forced into the moulds or through the die in such a
wuvan to leave the brick in lamiiUB, not well cemented together. A
rnt ieal examination of the brick with the unaided eye gave no indi-
* Knijimvrlntj JVrwvr, vol. xxl. p. H8.
f ( 'nmplltMl from this annual reports for 188^-85.
44
BRICK.
[CHAP.
9
•§ .
ill
1C CD
o5 d «-
oo ^o io c?
CQOO lOCOi> OOO OCOO CO CO1OO
§t* CO WOi> C3iOO OCQ£- C4 1O001O
COW Cto-^CO OOOO OiOiO i> COO^t-^
§>s 3
050^00
j> t-T oo co" THOO oold'o'i "^oz> co cooco
In
*1
3
O OJ
CQ -t^> CO .^ •*"*
1 53*
Is
II
5
1 m
0 . .
I ss
SI
CO CO 1O CO
T3N iO CO COCOCO -rH CO i-l COCOCO CO COCOCO
see Report of i
, 1883, p. 220.
of Metals, etc
of MQtals, etc
ildings. £
etals, etc
See Tests
See Teste
<D
0 T3
of Public Bu
ee Tests of M
)iers(§246).
>iers (| 246).
1 1
2 * fl
S ::::::::: : : :
cp .:::::.:....
•2 .-S-g
1155
•S133
fc
O
O c4
PM . ; • . : •
5° C QiQ.
M
lelpbia,* Dobbin's, bar
" Excelsior, '
Hubn's,
{( Dotterer's pre
1: 2 : . :
«S r^ " fd *• nd
CU CD • CU
^ C ^H • M
cc ^^ 03*^3^ H.S!J s
H CO P C^§ ^ f^ ^ r;4 r^j ^ T-j
O «^PQ 8 G03 ri4
feo« ^ •++ g ^ "
3Sted for the Commissioner
unples of bricks used in Pe
imples of bricks used in ex^
imples of brigks used in exi
J
2
PH
^ PQ O fe
*SSSr
§
Id
S
CRUSHING STRENGTH.
45
COMPRESSIVE STRENGTH.
(See §60.)
s&l
•3 -&»
PSjjS
6«st
M«in0 oo T-fc eo o>co
t— co^« as co i— 1 35 oo r-> i—
so ic^rti T-I co o^o "^ ^^ -H.
YH,_r «oV Tp'eo1 co" ofco"
General Explanations —Identically the same brick were tested for absorbing power, for transverse strength, and for crushing strength.
Each rSSTfoi ^bS?ng poWer and transverse strength represents the mean for seven to ten trials, and each result for crushing strength the
mean for thr|^d ^ ^^ ^.^ ^ ^.^ excepfc in being from dsfferent localities.
Fos 3 and 10. Bricks of these brands are giving entire satisfaction in pavements. ,,.,... ...
No«?' 7 and 8 These brick were taken out of a pavement, where thev had shown great durability, for these experiments.
No 13 These brick were token from the face of a building, where they had shown fair durability for seventeen years.
* Poi definition, see § 15. t Not plastered^G.lQO. t A whole brick, on end, showed no signs of crushing under 11 ,083 pounds per square inch.
Condition of
pressed
surfaces.
T3 13 t3
S "8 "8 §*S S
OJ--2 S- o3.£ e§--
a' S %~ U^ ft " "
•§ U ft -a -g
a pa
Average
dimensions
of bed-area,
inches.
^•VN N^i VtS^J Ntf SCO
^ ^^ ^ & ^
XX XXXX XXX
!5? ^J^? ^S! (STnS!
ThW 0*<M COOl 00 COCO
i
! TRANSVERSE STRENGTH.
j (See §59.)
i
-u ,.
S £&
Ihsii
0 0> 0>
3 -0™
00 £8 |£g§ S^^; g ^S5 g
i
j Modulus of
! rupture,*
j Ibs. per
square inch.
r-( <WO C4oOxrT-< O t— OCJ Oi Ot'TM C*
•rHT-l dr-t*-ii-i T-I SO
ABSORPTION.
(See §58.)
,, -* ^
«5gl-S2
•feSglig
£ £ S-3 o3,Q
*-<«.§^'§^
cd
COWQO Or-HQOOO O XO 00 CO t-O O
vHOJo oi-r^^ai os-^co cd oo c*
M
2
£
M
h
o
p
a
Proportion
of kiln
represented
by the brick
tested.
Sss^ §s §3s§ s
« o3
•Si
£§
&JO bfl hfl
13s§ 111' !!§ 1" 1
Pl P4 ft
•s ^ .
X3«w3 &fl
QJ° § S
s s
<C O> 0) 0)
_« —j c a a c
13 T? •!« — >•-! •£
P- - - fl- - - XJ- - ^ i^S -G
3 J 8 § 8 8
s s a s
§i<sl
^^ o
§SSS £::: §S S g fc fr
CO CO tO CO ™ "
380'
w gfc
p§ ®
»-<5*OOrj« W3COC-OO OSO-rH <M 00-^ O
46 BRICK. [CHAP. n.
cation of a laminated structure, and yet compressing the brick in
two positions — sidewise and edgewise — never failed to reveal such
structure. The crushing strength in the table was obtained when
the pressure was applied to the edges of the laminas. In experi-
ments Nos. 12, 13, and 14 the pressed surfaces were so nearly mathe-
matical planes that possibly these bricks stood more than they would
have done if their beds had been plastered. The strength of No. 15
was beyond the capacity of the machine; a whole brick, on end, stood
11,083 Ibs. persq. in. without any cracks or snapping sounds — which
usually occur at about half of the ultimate strength.
Rankine says that fi strong red brick, when set on end, should
require at least 1,100 Ibs. per sq. in. to crush them; weak, red ones,,
550 to 800 Ibs. persq. in.; and fire bricks, 1,700 Ibs. per. sq. in."*
Experiments on the brick in general use in Berlin gave for
"ordinary" brick, on edge, a strength of 2,930 Ibs. per sq. in.; and
for "selected" brick, 3,670 Ibs. per sq. in.f
The brick used in the New York reservoir, when laid flat and
packed with sand, showed an average strength, for four specimens,
of 2,770 Ibs. per sq. in,; and two samples tested between wood
averaged 2,660 Ibs. per sq. in.J Prof. Pike§ tested half brick flat-
wise between sheets of pasteboard with the following results: St.
Louis brick, 6,417 Ibs. per sq. in. (the average of six trials); and
pressed brick, 2,519 Ibs. per sq. in. (the average of thirteen sam-
ples from ten localities).
62. SIZE AND WEIGHT. In England the legal standard size for
brick is 8J X 4| X 2f inches. In Scotland the average size is
.about 9£ X 4i- X 3| inches; in Germany, 9£ X 4J X 2f inches; in
Austria, 1 U X 5J- X 2| inches; in Cuba, 11 X 5J X 2f inches; and
in South America, 12f x 6J X 2| inches.
In the United States there is no legal standard, and the dimen-
sions vary with the maker. In the Eastern States SJ X 4 X 2J
inches is a common size for brick, of which 26 make a cubic foot;
but in the West the dimensions are usually a little smaller. The
National Brick-makers' Association in 1887 and the National
* Civil Engineering, pp. 366 and 769.
t Van Nostrand's Engineering Magazine, vol. xxxiv. p. 240. From abstracts of
the Inst. of C. E.
J Jour. Frank. Inst., vol. Ixv. p. 333; also Trans. Am. Soc. of C. E., vol. ii. pp.
185-86.
§ Jour. Assoc. Engineering Soc., vol. iv. pp. 366-67.
\VKHiIIT, AXD COST. 4.7
Traders and Builders' Association in 1889 adopted S{- x 4 X 2£
inches us the standard size for common brick, and 8| x 4-g- X 2J
for face brick. The price should vary with the size. If, reckoned
ae.eonlintf to cubic, contents, brick 8 x 4 X 2 inches is worth $10
per thousand, brick S| >< 44 x ^|. is worth 112.33 per thousand,
and SA X 41 X &A is worth $1.5 per thousand. Further, where brick
is laid by the thousand, small bricks arc doubly expensive. Since
bricks shrink in burning., in proportion to the temperature to which
they arc exposed, the amount differing with the different kinds of
clays, it is impossible to have the size exactly uniform. He-pressed
and machine-moulded bricks arc more nearly uniform in size than
hand-moulded,
The size of brick and the thickness of the mortar joint should
be such that brick may be laid flat, edgewise, or set vertically, and
still ilt exactly These proportions are seldom realized.
Re-pressed brick weighs about 150 Ibs. per cu. ft. ; common
hard brick, 1*25 ; inferior, soft brick, 100. Common bricks will
average about »t J Ibs. each.
63. COST. Brick is sold by the thousand. At Chicago, in 1887,
the. fi best, se\ver*? brick cost $1) ; common brick, from. $6 to $7.
CHAPTER III.
LIME AND CEMENT.
64. CLASSIFICATION. Considered as materials for use in the
"builder's art, the products derived from the calcination of pure
.and impure limestones are classified as common or fat lime, hy-
draulic lime, and hydraulic cement. Common lime is sometimes
•called air-lime, because a paste or mortar made from it requires ex-
posure to the air to enable it to " set," or harden. The hydraulic
limes and cements are also called water-limes and water- cements,
from their property of hardening under water.
Common lime is used in making the mortar for most architect-
ural masonry, and until recently it was generally employed in en-
gineering masonry ; bat the opinion is rapidly gaining ground that
<only cement mortar should be employed in engineering structures
requiring great strength or subject to shock. On most first class
railroads hydraulic cement mortar is used in all masonry struc-
tures. This change in practice is largely due to the better appre-
ciation of the superiority of hydraulic cement as a building mate-
rial. Although it has been manufactured for about fifty years, the
.amount used was comparatively limited until within the last
twenty years. At present large quantities are imported from
Europe, and very much more is made in this 'country. Hydraulic
lime is neither manufactured nor used in this country.
The following discussion concerning common and hydraulic
limes is given as preliminary to the study of hydraulic cements
rather than because of the importance of these materials in engi-
neering construction.
ART. 1. COMMON LIME.
65. DESCRIPTION. The limestones which furnish the common
lime are seldom, if ever, pure; but usually contain, besides the car-
bonate of lime, from 3 to 10 per cent, of impurities, — such as silica,
48
AKT. 1.] COMMON LIMB. 49
.alumina, magnesia, oxide of manganese, and traces of the alkalies.
Lime — variously designated as common lime, quicklime, or caustic
lime — is a protoxide of calcium, and is produced when marble, or
any other variety of pure or nearly pure carbonate of lime, is cal-
cined with a heat of sufficient intensity and duration to expel the
carbonic acid. It has a specific gravity of 2.&, is amorphous,
highly caustic, has a great avidity for water, and when brought
into contact with it will rapidly absorb nearly a quarter of its
weight of that substance. This absorption is accompanied and fol-
lowed by a great elevation of temperature, by the evolution of hot
and slightly caustic vapor, by the bursting of the lime into pieces ;
and finally the lime is reduced to a powder, the volume of which is
from two and a half to three and a half times the volume of the
original lime — the increase of balk being proportional to the
purity of the limestones. In this condition the lime is said to be
slaked, and is ready for use in making mortar.
The paste of common lime is unctuous and impalpable to sight
.and touch ; hence these limes are sometimes called fat or rich
limes, as distinguished from others known as poor or meager limes.
These latter usually contain more or less silica and a greater propor-
tion of other impurities than the fat limes. In slaking they ex-
hibit a more moderate elevation of temperature ; evolve less vapor ;
are seldom reduced to an impalpable homogeneous powder • yield
thin paste ; and expand less. They are less valuable for mortar
than the fat limes, but are extensively employed as fertilizers.
When used for building purposes they should, if practicable, be
reduced to powder by grinding, in order to remove all danger of
.subsequent slaking.
66. TESTING. Good lime may be known by the following charac-
teristics: 1. Freedom from cinders and clinkers, with not more than
10 per cent, of other impurities, — as silica, alumina, etc. 2. Chiefly in
hard lumps, with but little dust. 3. Slakes readily in water, form-
ing a very fine smooth paste, without any residue. 4. Dissolves in
soft water, when this is added in sufficient quantities. These simple
tests can be readily applied to any sample of lime.
67. PRESERVING-. As lime abstracts water from the atmosphere
and is thereby slaked, it soon crumbles into a fine powder, losing
all those qualities which render it of value in building. On this
account great care must be taken that the lime to be used is freshly
LIME AND t'KMEXT,
burned, as may be known by its being in hard
in powder. Lime is shipped either in bulk or in fa*k •. I"
it is impossible to preserve it for any coiwidornblt' tim*- ; * -1
it may be preserved for some time by storing in a ilr> |» ,»•
Common lime, when mixed to a pasto with watrr, IH,*, '
for an indefinite time in that condition without tli'U-i.*"
protected from contact with the air HO that it will imt »t?t •,
is customary to keep the lime panto in casks, or in f b* N '*»«
boxes in which it was slaked, or hoapiul up on tin* #n»w»K
over with the sand to be subsequently iwor[>orut«*tl \itflf if i.
ing mortar. It is convenient for some purest'* !«* k«'»'p tb
lime on hand in a state of powder, which nwy 1*« t!i*M' .'
under cover, or in bulk, in a room net iipnrt for that J*w j« •
common limes contain impuritioH which piwt'iit » IIIH^^^
form, and prompt slaking of tin* entire^ WHWH, ami IP n*^ ''.
sity of slaking some days before the linw in to IM* uwj !*« 4,
danger to the masonry by Ktibscqucut enlargement c»f \^i\ct<
change of condition.
A paste or mortar of common limo will not harden «t^!« '
3ior in continuously damp placuw oxclndt'd from rnt»t,i» i 4*
air. It will slowly harden in tho air, from ih«* c»rf.Mfr i^*« »
interior, by desiccation and tho gradual ahHorptiun »f r.»*i« «'>
gas, by which process a subcarbomito with un «*vt* » **( ? <
base is formed.
68. COST. Lime is sold by tho barrel (about **uo
by the bushel (75 pounds). At Chicago th<» u\cr»^
was from 55 to 65 cents per barrel.
•ART. 2. l.
69. DESCRIPTION. Hydraulic* limo i« Hkt* n»minoit UIM* »n
it will slake, and differs from it in that it will Imnli'ii nti4* i »
Hydraulic lime may bo either argilltiwwH or Mrn^m f fa> f >(,
is derived from limestones containing from 10 f** *»n |*^i -«»s«
clay, homogeneously mixed with (»rbc«mti« of lirm*!i* th* pm-
ingredient; the latter from silicwtw HmwtoiMM nifiiip^i^ $
12 to 18 per cent, of silica. Small iKjn'i*ntagi»M of „! v
carbonates of magnesia, etc., are generally pnwttt,
During the burning, the carbonic aeiil w fxiHUtl, «i4 »s ,- rf,
and alumina entering into combination with a jwtNfi i,f iL* !
ART. 2.] HYDRAULIC LIME. 51
form both the silicate and the aluminate of lime, leaving in the
burnt product an excess of quick or caustic lime, which induces
slaking, and becomes hydrate of lime when brought into contact
with water. The product owes its hydraulicity to the crystallizing
energy of the aluminate and the silicate of lime.
70. CLASSIFICATION. Argillaceous hydraulic limes are arranged
in three classes, according to their amount of hydraulic energy:
1. Feebly hydraulic — containing 10 to 20 per cent, of impurities.
This slakes in a few minutes, with crackling, heat, and emission of
vapor. If made into a paste and immersed in water in small cakes,
in from 12 to 15 days it will harden so as to resist crushing
between the thumb and finger.
2. Ordinary hydraulic — containing 17 to 24 per cent, of im-
purities. Slakes after an hour or two, with slight heat and fumes,
without crackling. Sets under water in 6 or 8 days.
3. Eminently hydraulic — containing at least 20 per cent, of im-
purities. Slakes very slowly and with great difficulty, with slight
heat. Sets under water in 12 to 20 hours, and becomes hard in 2
to 4 clays.
Artificial hydraulic lime can be manufactured by mixing to-
gether, in suitable proportions, thoroughly slaked common lime
and unburnt clay, tempering the mixture with water, and then
burning it in the form of bricks or rounded balls in an ordinary
lime-kiln. The burnt material can be slaked in the ordinary way.
For the common lime, powdered limestone may be substituted. It
is better, however, when it becomes necessary to resort to artificial
mixtures to produce the hydraulic ingredient of mortar, to make
hydraulic cement, on account of its superior hydraulic energy.
No hydraulic lime is manufactured in the United States. It is
manufactured in several localities in France, notably at Teil and
Scilly, from which places large quantities were formerly brought to
this country.
Hydraulic lime is usually slaked, screened, and packed in sacks
or barrels before being sent to market. The screening takes out a
lumpy unslaked residue, which is often ground and mixed with
lime. This residue is sometimes natural hydraulic cement, in
which case it improves the quality of the lime. Sometimes it is
unburned clay, which constitutes an adulteration. The use of
these' unslaked lumps requires watchfulness, in order that the in-
LIME A.ND CEMENT. [CHAP, III.
trod action of ingredients that are either worthless ev- dangerous
may be avoided.
ART. 3. HYDRAULIC CEMENT.
71. CLASSIFICATION. Hydraulic cements may be divided into
three classes, viz.., Portland, Rosendale, and Pozzuolana. The first
two differ from the third in that the ingredients of which the
former are composed must be roasted before they acquire the
property of hardening under water, while the ingredients of the
latter need only to be pulverized and mixed with water to a paste.
The first two classes include the ordinary hydraulic cements, and
the third class includes the pozznolanas. The former are by far the
more valuable, and since the discovery of the ordinary hydraulic
cements pozzuolana is never used.
72. Portland cement is heavy, slow-setting, and has great ulti-
mate strength. Eosendale is light, quick-setting, and has less ulti-
mate strength. Roughly speaking, the second weighs about two
thirds as much as the first, sets in one tenth of the time, and attains
to about half the ultimate strength of the Portland. There is a
great variety of brands of each class, which differ from each other
in minor particulars.
Pozzuolana cement is so called from Pozzuoli, Italy, near which
place the ingredients of which it is composed were first found.
Portland cement derives its name from the resemblance which hard-
ened mortar made of it bears to a stone found in the isle of Port-
land, off the south coast of England. There is a great diversity
and some confusion in the names employed to designate that cement
which above is called Rosendale. The terms "natural," "Ameri-
can," and " Kosen dale " are frequently used. It is here proposed
to call this cement ROSENDALE, from the place — Rosendale, Ulster
Co., N. Y. — where it was first made.
In Europe the term Roman cement is used to designate a
natural cement of about the same character as Rosendale. This
cement was first known as Parker's, and was afterwards called
Roman, probably on the supposition, or to convey the impression,
that it was the cement employed by the early Romans ; but it is in
no way similar to their cement. They seem to have been ignorant
of the art of conferring hydraulicity upon a limestone by roasting
it. Vicat, of France, discovered this principle in 1818, although
AET. 3.] HYDRAULIC CEMENT. 53
Eoman cement had been made by a tentative process as early as
1796. Portland cement was made first in England about 1843, in
America about 1874 ; Eosendale was first made in the United States
about 1837. A small quantity of fancy cements, known as Parian,
Martin's, Keene's, etc., are imported for use in the production of
terra-cotta trimmings, imitation marble, for extra hard finish on
walls, etc.
7,3. Portland Cement. The natural stone from which the origi-
nal Portland cement is derived contains from 20 to 22 per cent, of
clay and 78 to 80 per cent, of carbonate of lime. The clay itself is
composed of 1J- to 2 parts of silica to 1 of alumina. When cal-
cined at a high, long-continued heat, all or nearly all the silica and
alumina of the clay combines with a portion of the lime ; conse-
quently the burned product does not contain any uncombined, and
therefore inert, silica and alumina to adulterate the cement and
impair its hydraulic properties. As the quantity of uncombined
lime is not sufficient to cause the mass to slake to powder in the
presence of water, the cement must be reduced to powder by grind-
ing between ordinary millstones.
The superiority of Portland cement appears to depend in great
measure upon the presence of the double silicate of lime and
alumina, which is formed only at a high heat. The weight of
Portland cement, as well as its hydraulic energy and its ultimate
strength and hardness, is increased by augmenting (within the
limit? of vitrification) the intensity and duration of the heat em-
ployed in burning. The initial hydraulic activity, however, is di-«
minished by high burning, so that the best Portland cements are
slowest in setting. A cement weighing 100 pounds to the bushel
may be burnt so as to weigh 125 pounds to the bushel, and its
strength will be nearly doubled thereby.
74. Artificial Portland. Fully nineteen twentieths of all the
Portland cement used at the present day is artificial. It is made by
thoroughly mixing together, in suitable proportions, clay and finely
pulverized carbonate of lime (either chalk, marl, or compact lime-
stone), burning the mixture in kilns at a high heat, and then grind-
ing the burnt product to fine powder between ordinary millstones.
In England the ingredients of the cement are mixed together
with a large body of water, and afterwards dried, burned, and
ground. This is called the "wet process." In Germany the in-
54 LIME AtfP CEMENT. [CHAP. III.
gredients are mixed dry. Each process is thought to be well
adapted to the character of the materials employed.
Artificial Portland is made at a number of places in this country,
but to much greater extent at Allentown and Egypt, Penn., than
anywhere else. The brand manufactured at Allen town, " Savior's,"
is nearly, if not quite, equal to the best imported Portland, and has
been extensively used in the last few years. The Portland-cement
industry in this country is in its infancy, the first factory having
been established in 1875. In the past few years other factories
have been built in different parts of the country. In 1886 we im-
ported 650,000 and' made 150,000 barrels of Portland cement.*
The raw material suitable for the manufacture of Portland cement
exists in greafc abundance in nature, and with proper care a high-
class Portland cement might be produced in almost any part of the
country.
75. Eosendale Cement.f By far the greater part J of the hy-
draulic cement used in the United States is of the Eosendale type.
It is made from the argillo-magnesian limestones, that is, lime-
stones of which the principal ingredients are carbonate of lime,
carbonate of magnesia, and clay. The process followed in their
manufacture is essentially the same as for Portland cement. The
stone is quarried, broken into pieces, and burned in a kiln. The
burnt cement is then crushed into small fragments, ground between
ordinary millstones, packed, and sent to market.
A light, quick-setting cement can also be made from an argilla-
ceous limestone containing more than 23 per cent, of clay homo-
geneously mixed through the mass. Any magnesian limestone con-
taining as high as 60 per cent, of carbonate of magnesia may be
presumed to be capable of yielding hydraulic cement of greater or
less value, if properly burned, no matter whether clay be present or
not. Dolomite, or the double carbonate of lime and magnesia,
when burned at a low heat, reduced to powder, and made into
mortar, also exhibits hydraulic properties. Pure carbonate of
magnesia, when burned at a moderate intensity, ground to fine
powder, and made into paste with sea-water, makes a cement which
is superior in hardness and strength to any other, not excepting
even Portland cement.
* U. S. Bureau of Mining Statistics, 1886. t See § 72.
J In 1886, according to the U. S. Bureau of Mining Statistics, it was 85 per cent.
ART. 3.] HYDBAULIC CEMEKT. 55
76. The natural bed of limestones from which, the original
Eosendale is made, covers about one third the State of New York,
-and the western part of Vermont, besides extending in a belt
-through New Jersey, Pennsylvania, Maryland, Virginia, and East
Tennessee. Deposits suitable for the manufacture of natural
cements are found at numerous other points in this country. Is it
too much to assume that there is no very large area in which a stone
•can not be found from which some grade of natural cement can be
made ?
Cement of the Eosendale type is made in large quantities in
Ulster County, and at Akron and Buffalo, IsT. Y.; at Sandusky,
Ohio; Louisville, Ky.; Utica, 111.; Milwaukee, Wis. ; Kansas City,
Mo.; Trinidad, Col.; Kensington, Conn.; and possibly at other
places.
The total production of cement of the Eosendale type in the
United States in 1886 was 4/200,000 barrels, of which nearly half
was produced in Ulster County, jST. Y.
77. Pozzuolana. This is not a very important kind of cement,
since the ingredients are not widely distributed, and also because
the strength of the cement is much less than that of other hydraulic
•cements.'
The substance first known to possess the peculiar property of
hydraulicity was volcanic ashes; and the discovery was made at Poz-
zuoli, near the base of Mount Vesuvius, — hence the name. Vitru-
vius and Pliny both mention that pozzuolana was extensively used
by the Romans before their day; and Vitruvius gives a formula for
its use in monolithic masonry, which with slight variations has
been followed in Italy ever since. It is as follows : " 12 parts poz-
zuolana, well pulverized; 6 parts quartzose sand, well washed; and
9 parts rich lime, well slaked." This constitutes a mortar, which
may be used either as ordinary mortar or as a matrix for filling
in.
'"''Trass, a volcanic earth, closely resembles pozzuolana, and is
-employed substantially in the same way. It is found on the Ehine
between Mayence and Cologne, and in various localities in Holland.
The arenes are a species of ocherous sand containing so large a
proportion of clay that they can be mixed into a paste with water
without the addition of lime, and used in that state for common
mortar. Mixed with rich lime thoy yield hydraulic mortars of
56 LIME AS"D CEMENT. [CHAP. IIL
considerable energy. Many of the natural pozzuolanas are improved
by a slight roasting, and an artificial pozzuolana may be produced
by subjecting clay to a slight calcination."
Brick dust mixed with common lime produces a feebly hydraulic-
mortar. Forge scales from smiths' anvils and the slags from iron
foundries are artificial pozzuolanas.
ART. 4. TESTS OJF CEMENT.*
78. The value of cements varies greatly with their physical prop-
erties; and since one lot of cement is liable to differ very much
from another lot of the same brand, it is very necessary to be able
to test the character of any particular cement. The properties of a
cement which are usually examined to determine its constructive-
value are: (l) color, (2) weight, (3) activity, (4) soundness, (5) fine-
ness, and (6) strength. The last three are the most important.
79. COLOR. The absolute color of a cement indicates but little,.
since it is chiefly due to oxides of iron and manganese, which in no-
way affect the cementitious value; but for any given kind variations
in shade may indicate differences in the character of the rock or in
the degree of burning. With Portland cement, gray or greenish
gray is generally considered best; bluish gray indicates a probable
excess of lime; and brown, an excess of clay. An undue proportion
of under-burned material is generally indicated by a yellowish shade,
with a marked difference between the color of the hard-burned, un-
ground particles retained by a fine sieve and the finer cement
which passes through the sieve.
American cements are generally brown, in light or dark shades,
In Rosendale cement a light color generally indicates an inferior,,
under-burned rock.
80. WEIGHT. Por any particular cement the weight varies with
the degree of heat in burning, the degree of fineness in grinding,
and the density of packing. Other things being the same, the
harder-burned varieties are the heavier. The finer a cement is
ground the more bulky it becomes, and consequently the less it
weighs. Hence light weight may be caused by laudable fine grind-
ing or by objectionable under-burning.
The weight per unit of volume is usually determined by sifting
* Contributed to Engineering News, vol. xv. pp. 283-84.
.ART. 4.] TESTS OF CEMEOT. 57
the cement into a measure as lightly as possible, and striking the
top level with a straight-edge. In careful work the height of fall
is specified. For a method of still greater refinement, see Transac-
tions of the American Society of Civil Engineers, vol. xiii. p. 55.
Since the cement absorbs moisture, the sample must be taken from
the interior of the package. The weight per cubic foot is neither
exactly constant, nor can it be determined precisely; and for the
practical purpose of the user is of very little service in determining-
the value of a cement. However, it is often specified as one of the
requirements to be fulfilled.
The following values,* determined by sifting ihe cement with a
fall of three feet into a box having a capacity of one tenth of a
cubic foot, may be taken as fair averages for ordinary cements. The
difference in weight for any particular kind is mainly due to a dif-
ference in fineness.
Portland, English, and German, . 77 to 90 IDS. per cubic foot.
" fine-ground French, . . 69 " " " (t
" American, 95 " " " "
Roman 54 " " "
Roseudale, 49 to 56 " " " "
LimeofTeD, 50 "
Since a bushel is 1.244 cubic feet, the weight per bushel can be
obtained sufficiently close by adding 25 per cent, to the above quan-
tities. However, it is better to make the cubic foot the standard
unit measure.
81. ACTIVITY. A mortar is said to have set when it has attained
such a degree of induration that its form can not be altered without
causing a fracture, i.e., when it has entirely lost its plasticity.
Some cements set quickly, while others are comparatively slow in
developing the first indications of hydraulicity. This property is
called hydraulic quickness or activity. A quick-setting cement is
especially valuable in constructions under water.
A distinction should be carefully made between hydraulic activ-
ity and hydraulic energy or strength. The former refers to the
time required to attain a small degree of strength, and the latter to
the amount of strength ultimately attained. There is no necessary
relation between time of setting and ultimate strength ; but, as a
* Transactions of the American Society of Civil Engineers, vol. xiv. p. 143.
58 LIME A.ND CEMENT, [CHAI
general rule, the slow-setting cements ultimately attain to a gi
strength than quick-setting ones.
" The effects of a variation of temperature upon the hycL
quickness of mortars — whether derived from hydraulic lime,, hy
lie cement, a mixture of common lime and pozzuolana, or pro<
by artificial means — is very marked: so much so, indeed, that
comparative tests of this kind it is important to adopt some
standard of temperature, not only for the water with whjc
cement is mixed, as well as that in which the cement is imm
hut for the dry ingredients, and the surrounding atmosphere
cements are not equally sensitive to a variation of temperatur<
The activity of cement may be increased by adding a qn
setting cement, — as plaster of Paris, — lime, clay, or even greas
such ingredients, particularly the last, weaken the resulting rr
82. Test of Activity. "To test hydraulic activity, mix c
with 25 to 30 per cent, of its weight of clean water,* having i
perature of between 65° F. and 70° F., to a stiff plastic morta
make one or two cakes or pats 2 or 3 inches in diameter and
-J- inch thick. As soon as the cakes are prepared, immerse in
at 65° F., and note the time required for them to set hard e
to bear respectively a -^-inch wire loaded to weigh J pound,
•g^-incli wire loaded to weigh 1 pound. When the cement bei
light weight, it is said to have begun to set; when it bears the
weight, it is said to have entirely set." Cements, however, v
crease in hardness long after they can just bear the heavy wire,
activity of the cement is measured by the time which elapi
tween the time when the first weight is supported and tha
the second is just borne. Notice that with the wires as abc
weight per unit of surface in the second case is sixteen ti:
much as in the first. Hence it is not necessary to have the
eters as stated, but only to have the pressure per unit o
sixteen times as much in the one case as in the other; th
wire may be used in both tests, the load only being varied.
Different kinds and brands of cement vary greatly in fch
required to set. Some brands of Rosendale cement will s
* The water required to make a stiff paste will vary somewhat with the 1
freshness of the cement. On the average, neat Portland cement mortar
about 25 per cent, of its weight of water, and neat Rosendale about 30 per d
1 part cement to 1 part sand, about 15 per cent, of the total weight of the s
cement; and for 1 cement to 3 sancl, about 12 per cent.
ART. 4] TESTS OF CEMENT. 59
the heavy wire in two minutes, and some brands of Portland in not
less than 12 hours. Cold retards the setting. Freshly-ground cements
set quicker than older ones. The quick-setting cements usually
set so that experimental samples can be handled within 5 to 30
minutes after mixing; the slow-setting cements require from 1 to 8
hours.
83. SOUNDNESS. Soundness refers to the property of not ex-
panding or contracting, or cracking or checking in setting. These
-effects may be due to free lime,, free magnesia, or to unknown
•causes. Testing soundness is therefore determining whether the
•cement contains any active impurity. An inert adulteration or
impurity affects only its economic value; but an active impurity
.affects also its strength and durability.
Soundness may be tested as follows: Immerse in water a
small pat of neat cement mortar with thin edges (§ 82), and ex-
amine it from day to day to see if it becomes contorted or if
cracks show themselves at the edges. If there is cracking or con-
tortion (sometimes called " blowing"), it is due to the hydration
and consequent expansion of the lime or magnesia. If the effect is
clue to lime, the cement can be improved by exposure to the air,
thus allo\ying the free lime to slake. This treatment is sometimes
•called "cooling the cement." The presence of uncombined mag-
nesia is more harmful than that of lime. A number of important
masonry structures have failed in recent years owing to the expan-
sion caused by the hydration of the magnesia in the cement em-
ployed in their construction.
It is generally held that 1£ or 2 per cent, of uncombined mag-
nesia in Portland cement is dangerous, particularly in damp places.
The best Portland cements have very much less than this. Several
standard brands contain only 0.46 to 1.27 per cent, of magnesia.
Since cement of the Rosendale type is made of magnesian lime-
stone, it contains from 5 to 20 per cent, of magnesia. Chemists are
not agreed as to the manner in which the different constituents are
combined, and consequently are not agreed either as to the amount
or effect of free magnesia in such a cement. Fortunately, it is
not necessary to resort to a chemical analysis to determine the
amount of free lime or free magnesia present, for a cement which
successfully stands the above test for soundness for one or two
60 LIME A;NT> CEMESTT. [CHAP. IIL,
days can be used with confidence. The time required to test
soundness can be shortened, or the value of the test increased, by
keeping the water in which the pat is immersed at, say, 100° F.
The soundness of a cement may also be tested by placing some
mortar in a glass tube (a swelled lamp chimney is excellent for this
purpose), and pouring water on top. If the tube breaks, the cement
is unfit for use in damp places. A less delicate and less valuable test
than either of the above is to note whether the cement heats when
mixed with water. A thermometer is sometimes used in making
this test.
Some idea of the quality of cement may be gained by exposing
to the air a small cake of neat cement mortar and observing its
color. "A good cement should be uniform bluish gray throughout,,
yellowish blotches indicating poor cement. The color of the cement,
when left in the air, indicates the quality much better than when
the cement is put into water. " This test is not generally con-
sidered of much value.
Tests of soundness should not only be carefully conducted, but
should extend over considerable time. Occasionally cement is
found * which seems to meet the usual tests for soundness, strength,
etc., and yet after considerable time loses all coherence and falls to
pieces.
84. FINENESS. The question of fineness is wholly a matter of
economy. Cement, until ground, is a mass of partially vitrified
clinker, which is not affected by water, and which has no setting
power. It is only after it is ground that the addition of water in-
duces crystallization. Consequently the coarse particles in a cement
have no setting power whatever, and may for practical purposes
be considered only as so much sand and essentially an adulterant.
There is another reason why it should be well ground. A mortar
or concrete being composed of a certain quantity of inert material
bound together by a cementing material, it is evident that to secure
a strong mortar or concrete it is essential that each piece of aggre-
gate shall be entirely surrounded by the cementing material, so that
no two pieces are in actual contact.
Obviously, then, the finer a cement the greater surface will a
* Trans. Am. Soc. of C, E., vol. xiii. p. 64, and vol. xiv. p. 149.
AET. 4.] TESTS OP CEMENT. 61
given weight cover, and the more economy will there be in its
use.
Fine cement can be produced by the manufacturers in three
ways : 1, by supplying the millstone with comparatively soft,
under-burnt rock, which is easily reduced to powder ; 2, by run-
ning the stones more slowly, so that the rock remains longer be-
tween them ; or, 3, by bolting through a sieve and returning the
unground particles to the stones. The first process produces an
inferior quality of cement, while the second and third add to the
cost of manufacture.
It is possible to reduce a cement to an impalpable powder, but
the proper degree of fineness is reached when it becomes cheaper to
use more cement in proportion to the aggregate than to pay the
extra cost of additional grinding.
85. Measuring Fineness. The degree of fineness of a cement
is determined by measuring the per cent, which will not pass
through sieves of a certain number of meshes per square inch. The
Committee of the American Society of Civil Engineers* recom-
mend the determination " by weight of the per cent, that is re-
jected by sieves of 2,500, 5,476, and 10,000 meshes to the square
inch respectively, the first-mentioned sieve being of No. 35, the
second of No. 37, and the third of No. 40 wire gauge/' These sieves
are usually referred to by the number of meshes per linear inch ;
the first being known as No. 50, the last as No. 100. It is
stated f that, as sold, the number of meshes varies somewhat, and
that the number of wires is generally less, by about 10 per cent.,
than the number of the sieve. The diameter of the holes is about
•equal to the diameter of the wire.
German Portland cements are commonly ground finer than Eng-
lish. "Most English manufacturers grind their cement to such a
degree of fineness that when sifted through a sieve having 2,500
holes (50 by 50) to the square inch, it shall leave a residue of not
more than 10 per cent, by weight. Cement ground to this fineness
will leave from 19 to 20 per cent, of residue on a 4,900 (70 by 70)
sieve, and practically nothing on a 625 (25 by 25) sieved " This is
supposed to be the most economical degree of fineness.
* Trans., vol. xiii. p. 54.
t Trans. Am. Soc. of C. E., vol. xiv. p. 144.
LIMB
[CHAP. III.
Different brands of Rosendale cement vary considerably in their
fineness. Those of the best reputation will leave from 4 to 10 per-
cent, residuum, on the No. 50 sieve ; other brands, from 10 to 23
per cent.
86. STBEtfG-TH. The strength of cement mortar is usually de-
termined by submitting a specimen of known cross section to a
tensile strain. The reason for adopting tensile tests is that com-
paratively light strains produce rupture ; and that, since mortar is
less strong in tension than in compression, in most cases of failure
of. mortar it is broken by tensile stress, even though the masonry
be under compression (§ 9).
87. The Testing-machine. The details of the form of the
specimen to be tested (the briquette) as recommended by the Com-
mittee of the American Society, are given in Fig. 2. The method
of placing the briquette in the machine is shown in Pig. 3. In
FIG. 2.
FIG. a
applying the stress, it is also recommended to make the initial
•strain 0, and increase it regularly at the rate of 400 Ibs. per minute
AKT. 4]
TESTS OF CEMEKT.
until rupture takes place. es For a weak mixture one half the
speed is recommended/' *
There are many machines on the market, made specially for
testing the strength of cement. Eig. 4 represents a cement-test-
ing machine which can be made by an ordinary mechanic at an
expense of only a few dollars. Although it does not have the con-
veniences and is not as accurate as the more elaborate machines,, it
is valuable where the quantity of work will not warrant a more ex-
pensive one, and in many cases is amply sufficient. It was devised
by F. W. Bruce for use at Fort Marion, St. Augustine, Fla., and
reported to the Engineering Neivs \ by Lieutenant W. M. Black,
U. S. A,
FIG. 4.
W, fixed weight. IF', rolling weight. W", counterpoise. I?', block for shearing. Br
block for crushing. (7, tensile strain clips.
The machine consists essentially of a counterpoised wooden
lever 10 feet long, working on a horizontal pin between two broad
uprights 20 inches from one end. Along the top of the long arm
runs a grooved wheel carrying a weight. The distances from the-
fulcrum in feet and inches are marked on the surface of the lever.
The clamp for holding the briquette for tensile tests is suspended
from the short arm, 18 inches from the fulcrum. Pressure for
shearing and compressive stresses is communicated through a loose
upright, set under the long arm at any desired distance (gen-
* The following data are given by H. Faija, an English authority, as showing the
effect of a variation in the speed of applying the strain :
Bate. Tensile Strength.
100 pounds in 120 seconds '. . . 400 pounds.
100 " " 60 " 415 "
100 " " 30 " 430 "
100 " " 15 " 450 "
100 « " i « 493 "
64 LIME ASTD CEMEOT. [CHAP. III.
erally 6 or 12 inches) from the fulcrum. The lower clip for ten-
sile strains is fastened to the bed-plate. On this plate the cube to
be crushed rests between blocks of wood, and to it is fastened an
upright with a square mortise at the proper height for blocks to be
sheared. The rail on which the wheel runs is a piece of light T-
iron fastened on top of the lever. The pin is iron, and the pin-
holes are reinforced by iron washers. The clamps are wood, and are
fastened by clevis joints to the lever arm and bed-plate respec-
tively. When great stresses are desired, extra weights are hung on
the end of the long arm. Pressures of 3,000 pounds have been
developed with this machine.
For detailed drawings of a more elaborate home-made cement-
testing machine, see Engineering News, vol. xv. p. 310, or Pro-
ceedings Engineers' Club of Philadelphia.
88. Mixing the Mortar. — It is customary to test some bri-
quettes made wholly of cement and also some composed of part
sand and part cement, the latter being a check upon the tests for
fineness. For example, finely ground cements,, as compared with
coarsely ground, will give lower results tested neat, and higher
ones with liberal proportions of sand. On the other hand, un-
evenly ground cement — that is, part very fine, and part very
coarse — shows, in comparison with other grades, a high strength
when tested neat, and gives very low results when mixed with sand.
In the first case the coarse particles act like sand, and in the
second there are not enough fine particles to envelop the coarse
particles of cement and sand.
"For tests of mortar composed in part of sand, the sand should
be sharp, well washed and dried, rejecting all that will not pass
the sieve of 400 meshes to the square inch and that will pass a
sieve of 900 meshes to the square inch, — the wire gauge of the
former sieve to be No. 24, and of the latter No. 28."
In comparing different cements great care should be taken to
have the sand of the same quality in each case (§ 116), since the
variation of strength of a cement mixed with different qualities of
sand is often more than the difference in strength between different
brands.
" The proportion of sand, for the mortar of each briquette, should
be carefully determined by weight, and thoroughly and intimately
mixed with the cement in a dry state before water is added; and, so
A&T. 4.] TESTS OP CEMENT. 65
far as possible, all the water that is necessary to produce the desired
•consistency of the resulting mortar should be added at once, and
thereafter the manipulation by the spatula or trowel should be rapid
.and thorough. Care should be taken to introduce the mass into the
moulds and complete the moulding process before incipient setting
begins." * For additional instructions as to mixing the mortar, see
§§ 96 and 99.
The moulds, while being charged and manipulated, should be
laid on glass, slate, or some other non-absorbent material. The
briquette should be removed from the moulds as soon as it is hard
•enough to stand it. The briquettes should be immersed in water at
the end of 24 hours, and should be tested as soon as taken from the
water. If they are exposed to the air, the water may be carried away
by evaporization and leave the mortar a pulverulent mass. Also,
.since the mortar does not ordinarily set as rapidly under water as in
the air (owing to the difference in temperature), it is necessary, for
.accurate work, to note the time of immersion, and also to break the
briquette as soon as it is taken from the water. Notice that, or-
dinarily, cement attains a greater strength when allowed to set under
water, but attains it more slowly.
89. Age of Mortar. It is customary to break part of the bri-
quettes at the end of 7 days and the remainder at the end of 2$ days.
As it is sometimes impracticable to wait 28 days, tests are often
made at the end of 1 and 7 days respectively. The ultimate strength
-of the cement is judged by the increase in strength between the two
•dates. A minimum strength for the two dates is usually specified*.
90. Data on Strength. The report of the Committee of the
American Society of Civil Engineers, on Uniform Tests of Cements
•(Transactions of that Society, vol. xiv. pp. 478-79), gives the results
in the following table as "the average minimum and maximum
tensile strength per square inch which some good cements have at-
tained " when tested under the conditions specified above.
The quantity in the "Min." columns of the following table is
the average strength, for the time specified, of the weaker brands of
•each of the two classes of cement; and similarly the quantity in the
" Max. " columns is the average strength for the stronger brands.
In making tests with any sample of cement, the results are liable to
•considerable variation, depending upon the details of the manipula-
* Report of the Committee of the American Society of Civil Engineers.
66
LIKE AKD CEMENT.
[CHAP. in.
TABLE 10.
TENSILE STRENGTH OF CEMENT MORTARS.
Portland.
Rosendale.
CLEAR CEMENT.
1 day — 1 hour, or until set, in. air, the remainder
of the time in water
Min.
100
250
350
450
Max.
140
550
700
800
Min.
40
60
100
300
30
50
200
Max.
80
100'
150
400
50-
SO
800
1 week — 1 day in air, the remainder of the time
in water
4 weeks — 1 day in air, the remainder of the time
in water
1 year — 1 clay in air, the remainder of the time
in water . .
1 PART CEMENT TO 1 PART SAND.
1 week — 1 day in air, the remainder of the time
in water
4 weeks — 1 day in air, the remainder of the time
in water
1 year — 1 day in air, the remainder of the time
in water -
1 PART CEMENT TO 3 PARTS SANX>.
1 week — 1 day in air, the remainder of the time
in water
80
100
200
125
200
350
4 weeks — 1 day in air, the remainder of the time
in water /
1 year — 1 day in air, the remainder of the time
in water . *
AVERAGE TENSILE STRENGTH
IN POUNDS PER SQUARE INCH.
tion of the mortar and the machine.* Even if the same kind and
quantity of cement, sand,, and water are used, there is liability to an
extreme variation of 20 to 25 per cent, in the average result. Hence,
to properly test any sample of cement, it is essential that several
trials should be made. This is especially important when one in-
voice is to be compared with another or with a standard, since the
details of the experiments are apt to vary from day to day, although
the experimenter may be unconscious of it. In making tests of the-
strength of cements, it should be borne in mind that the strength
* See foot-note, page 63.
ART. 5.] SPECIFICATIONS FOR CEMENT. 67
depends upon the activity, soundness, and fineness of the cement, and
also upon the amount and kind of aggregate, upon the amount and
temperature of the water, and upon the details of the manipulation
in making and testing. Each item affects the strength to an ap-
preciable degree.
For additional data on the strength of mortars composed of dif-
ferent proportions of cement and sand, see § 134.
91. WEIGHT AND COST OF CEMENT. Cement is generally sold by
the barrel. A barrel of Portland cement weighs 400 pounds gross,
or about 375 net. Ulster Co. Eosendale cement weighs 300 pounds
per barrel net; Akron, Milwaukee, Utica, and Louisville Bosen-
dales weigh 265 pounds per barrel net. Cement is also occasionally
shipped in bags and in bulk, in which cases it is sold by weight.
The average price of cement of the Eosendale type at Chicago
during 1887 was $LOO to $1.25 per barrel; Portland averaged from
$3.00 to $3.25 per barrel
AET. 5. SPECIFICATIONS FOR CEMENT.
92. Cement is so variable in quality and intrinsic value that no
considerable quantity should be accepted without testing it to see
that it conforms to a specified standard. A careful study of the
preceding section will enable any one to prepare such specifications
as will suit the special requirements, and also give the instructions
necessary for applying the, tests. In many of the European countries
a uniform system has been devised and put in force by the respec-
tive governments. A few of these specifications will be given to-
serve as guides in preparing others.
ABSTRACTS FROM GERMAN SPECIFICATIONS FOR STANDARD
PORTLAND CEMENT.*
93. "CONSTANCY OF VOLUME. Portland cement shall be of
constant volume. As a preliminary test, admitting of forming a
rapid opinion, the heat test [described in the next paragraph] is
recommended. The decisive test shall be that a paste of neat
cement, made on a glass plate, protected against drying, and placed
* Sw/ineerim/ News, vol. xvi. pp. 316-17. Translated for the Laboratory of the De-
partment of Civil Engineering of Cornell University, Ithaca, N. Y.
68 LIME AND CEMENT. [CHAP. III.
under water, after twenty-four hours shall not show any blowing
cracks or change of shape.
"For making the heat test, a stiff paste of neat cement and
water is made,, and from this, cakes 8 centimetres (3.15 inches) to
10 centimetres (3.94 inches) in diameter and 1 centimetre (0,394
inch) thick, are formed on a smooth impermeable plate covered with
blotting-paper. Two of these cakes, which are to be protected
against drying in order to prevent drying cracks, are placed, after
the lapse of twenty-four hours, or at least only after they have set,
with their smooth surfaces on a metal plate and exposed, for at
least an hour, .to a temperature of from 110° C. to 120° C. (230° to
248° P.") until no" more water escapes. If, after this treatment, the
cakes show no edge cracks, the cement is to be considered, in gen-
eral, of constant volume. If such cracks do appear., the cement is
not to be condemned, but the results of the decisive test with the
cakes hardening on glass plates under water must be waited for. It
must, however, be noticed that the heat test does not admit of a
final conclusion as to the constancy of volume of those cements
which contain more than 3 per cent, of calcium, sulphate (gypsum)
or other sulphur combinations.
" For making the final test, the cake made for the purpose of
determining the time of setting, for slow-setting cements, is placed
under water after the lapse of twenty-four hours — or, at all events,
not until after it is set. For quick-setting cements, this can be
done after a 'shorter period. The cakes, especially those of slow-
setting cements, must be protected against draughts and sunshine
until their final setting. This is best accomplished by keeping them
in a covered box lined with zinc,, or under wet cloths. In this
manner the formation of heat-cracks is avoided, which are generally
formed in the center of the cake, and may be taken by an inexperi-
enced person for cracks formed by blowing.
94. " FINENESS OF GRINDING. Portland cement shall be so
finely ground that a batch of the same shall not leave a residue
of more than 10 per cent, upon a sieve of 900 meshes per square
centimetre (5,806 meshes per square inch). The thickness of the
wire of the sieve shall equal half the space between the wires. For
each test batch, 100 grammes (3£ oz.) of cement shall be used.
95. "TIME OF SETTING. To determine the time of setting, a
slow-setting neat cement shall be mixed three minutes, and a quick-
AET. 5.] SPECIFICATIONS FOR CEMENT. 69
setting neat cement one minute, with water to a stiff paste. A cake
about 1.5 centimetres (0.59 inch) thick, with thin edges, shall be
formed of this paste on a plate of glass. The consistency of the
cement paste for this cake shall be such that, when wrought with a
trowel on the plate, the paste will only begin to run towards
the edge of the same after the paste has been repeatedly jarred.
As a rule, 27 to 30 per cent, of water will suffice to give the necessary
consistency to the paste. As soon as the cake is sufficiently hard-
ened, so that it will resist a slight pressure of the finger-nail, the
cement is to be considered as having set.
"For the exact determination of the time of setting, and for
determining the beginning of the time of setting, — which latter is of
importance in the case of quick-setting cements, since they must be
worked up before they begin to set, — a standard needle 300 grammes
(10 oz.) in weight, and 1 square millimetre (0.0006 square inch) in
cross section is used, A metal ring 4 centimetres (1.575 inches) in
height and 8 centimetres (3.15 inches) clear diameter (inside) is
placed on a glass plate, filled with cement paste of the above con-
sistency, and brought under the needle. The moment at which the
needle is no longer capable of completely penetrating the cement
cakes is considered the beginning of the time of setting. The time
elapsing between this and the moment when the standard needle
no longer leaves an appreciable impression on the hardened cake is
considered the time of setting."
"Cements which do not set in less than two hours are to be
considered slow-setting cements.
96. "TESTS OF STEENGTH. The cohesive power of Portland
cement shall be determined by the testing of a mixture of cement
and sand. At the same time a determination of the strength of the
neat cement is to be recommended. The tests shall be both ten-
sile and compressive, with test pieces of the same form and section.
For each test, in order to obtain correct average results, at least
six test pieces are to be made, and the mean of the four best results
is to be considered the final strength. The tensile test pieces may
be made either by hand or by machinery; but the compressive test
pieces mast be made by machinery.
Sand. " In order to obtain concordant results in the tests, sand
of uniform size of grain and uniform quality must be used. This
standard sand is obtained by washing and drying the purest quartz
70 LIME A^D CEMENT. [CHAP. III.
sand obtainable, sifting the same through, a sieve with 60 meshes
per square centimetre (387 per square inch), thereby separating the
coarsest particles, and by removing from the sand so obtained, by
means of a sieve of 120 meshes per square centimetre (774 per
square inch), the finest particles. The diameter for the wires of the
sieves shall be 0.38 millimetres and 0.32 millimetres (0.015 inch
and 0.013 inch) respectively.
Hand- Mixing. "On a metal or thick glass plate five sheets of
blotting-paper soaked in water are laid, and on these are placed
five moulds wetted with water. 250 grammes (8.75 oz.) of cement
and 750 grammes (26.25 oz.) of standard sand are weighed, and
thoroughly mixed dry in a vessel. Then 100 cubic centimetres (100
grammes or 35 oz.) of fresh water are added, and the whole mass
thoroughly mixed for five minutes. With the mortar so obtained,
the moulds are at once filled, with one filling, so high as to be rounded
on top, the mortar being well pressed in. By means of an iron
trowel 5 to 8 centimetres (1.96 inches to 3.14 inches) wide, 35 centi-
metres (13.79 inches) long, and weighing about 250 grammes (8.75
oz.), the projecting mortar is pounded, first gently and from the
side, then harder into the moulds, until the mortar grows elastic and
water flushes to the surface. A pounding of at least one minute is
absolutely essential. An additional filling and pounding in of the
mortar is not admissible, since the test pieces of the same cement
should have the same densities at the different testing stations. The
mass projecting over the mould is now cut off: with a knife, arid the
surface smoothed. The mould is carefully taken off and the test piece
placed in a box lined with zinc, which is to be provided with a cover,
to prevent a non-uniform drying of the test pieces at different tem-
peratures. Twenty-four hours after being made, the test pieces are
placed under water, and care must be taken that they remain under
water during the whole period of hardening.
Machine-Mixing. Cf After the mould has been clamped on the
bed-plate of the pounding machine, for each test 180 grammes
(6.3 oz.) of the mortar, made as above, is placed in the mould, and
the iron follower is set in. By means of Boehme's hammer appa-
ratus,* with a hammer weighing 2 kilogrammes (4.4 pounds) 150
blows are struck on the follower.
*For illustrated description, see Engineering News, vol. xvii. p, 200.
ART. 5.] SPECIFICATIONS FOE CEMEOT. 71
97. " Good quick-setting cement, in the proportion of 3 parts
by weight of standard sand to 1 part of cement, when tested after
•28 days3 hardening (1 in air and 27 in water), shall have a mini-
mum tensile strength of at least 1G kilogrammes per square centi-
metre (227 pounds per square inch). The compressive strength
shall be at least 10 times the tensile strength.
"For slow-setting cements, the strength after 20 days is less in
general than the one above specified ; therefore, in giving the re-
sults of tests, the time of setting shall also be given."
ABSTRACTS FROM FRENCH SPECIFICATIONS FOR PORTLAND
CEMENT.*
98. " CHEMICAL ANALYSIS. The cement must not contain more
thanl per cent, of sulphuric acid or sulphides in determinable pro-
portion, f Cements containing more than 4 per cent, of ferric oxide,
or in which the ratio of the combined silica and alumina to the lime
is less than 0.44, are to be regarded as doubtful.
99, " MIXING THE MORTAK. In mixing the mortar for testing,
sea water is specified, and both air and water are to be maintained
.at a temperature of 15° to 18° C. (59° to 64.4° F.) during the con-
tinuance of the experiments. The quantity of water is ascertained
by a preliminary experiment, and the four following tests are given
to serve as an indication whether the proportion of water added is
•correct:
"1. The consistence of the mortar should not change if it be
.gauged for an additional period of three minutes after the initial
five minutes.
' ' 2. A small quantity of the mortar dropped from the trowel upon
the marble slab from a height of about 0.50 metres (1.G4 ft.) should
leave the trowel clean, and retain its form approximately without
cracking.
" 3. A small quantity of the mortar worked gently in the hands
should be easily moulded into a ball, on the surface of which water
should appear. When this ball is dropped from a height of 0.50
metres (1.64ft.), it should retain a rounded shape without cracking.
* From Abstracts of Inst. of C. E.
t The percentage of sulphides in the cement is said to be an indication of adul-
teration with blast-furnace slag.
72 LIME AKD CEMENT. [CHAP. HI-
"4. If a slightly smaller quantity of water be used, the mortar
should he crumbly, and crack when dropped upon the slab. On the
other hand, the addition of a further quantity of water — 1 to 2 per
cent, of the weight of the cement — would soften the mortar, ren-
dering it more adhesive, and preventing it from retaining its form
when allowed to fall upon the slab. It is recommended to com-
mence with a rather smaller quantity of water than may be ulti-
mately required, and then to make fresh mixings with a slight
additional quantity of water.
" The mortar is to be mixed with a trowel for five minutes upon
a marble slab."
100. STEENGTH. The form of briquette and method of mould-
ing are the same as required by the German specifications (see § 96);.
the breaking section is 5 square centimetres (0.775 square inch).
" Six briquettes are broken after an interval of 7 days, six after
28 days, and the remaining six after 84 days. The mean of the
three highest figures of each series of tests is taken as the tensile
strength of the cement under examination. The minimum strength
specified for the neat cement in 7 days is 20 kilogrammes per square-
centimetre (284.5 Ibs. per sq. in.); in 28 days, 35 kilogrammes per
square centimetre (497.8 Ibs. per sq. in.); and at least 45 kilogrammes,
per square centimetre (640 Ibs. per sq. in.) in 84 days. If, however,
the strength in 28 days is not more than 5 kilogrammes per square
centimetre (71.12 Ibs. per sq. in.) in excess of that at 7 days, then
it must be at least 55 kilogrammes per square centimetre (782.27
Ibs. per sq. in.) in 28 days, and in any case where this strength is-
not attained at 28 days it must be exceeded in 84.
101. " Tests of cement mixed with sand are also specified. The
standard sand is produced by crushing quartzite obtained from
quarries near Cherbourg, and sifting it through sieves of 64 and 144
meshes per square centimetre (413 and 929 meshes per square inch).*
That which remains between these two sieves is washed and dried.
and constitutes the standard sand. 375 grammes (13.28 oz.) of this-
sand is mixed with 125 grammes (4.41 oz.) of cement, and water is.
added in the proportion of 12 parts by weight to 100 parts of sand
and cement combined. The sand and cement are first carefully
* " The size of mesh of the sieve is not clearly specified, the thickness of the wire?
not being stated."
ART. 5.] SPECIFICATIONS FOR CEMENT. 73
mixed in a basin or capsule, then the whole of the sea water is added
at once,, and the mixture stirred with a spatula for five minutes.
" At the expiration of 7 days the strength of the sand-cement
briquettes should be at least 8 kilogrammes per square centimetre
(113.78 Ibs. per sq. in.), and in 28 days 15 kilogrammes per square
centimetre (213.35 Ibs. per sq, in.). In 28 days the strength should
exceed that at 7 days by 2 kilogrammes per square centimetre (28.45
Ibs. per sq. in.). In 84 days the strength must be greater than at
28 days, and at least 18 kilogrammes per square centimetre (256 Ibs.
per sq. in.). The 84-day tests are only considered indispensable for
those cements which may have stood the two previous tests ; but if,
while the cement is in store, the 84-day tests should be unsatisfac-
tory, it may be rejected."
102. FINENESS OF GRINDING-. " The degree of fineness to which
the cement must be ground is not specified, it being considered that
very fine grinding increases the strength chiefly during the duration
of the tests, and that the subsequent increase of strength is less with
fine than with coarse cement."
103. TIME OF SETTING. Essentially the same as the German
specifications ; see § 95.
<e Any cement commencing to set in less than 30 minutes, or
failing to commence to set within 3 hours, is to be rejected; and
the final set must have taken place within 12 hours. In each case
the time is reckoned from the moment the water is poured upon
the cement."
AUSTRIAN SPECIFICATIONS FOR FINENESS AND STRENGTH OF
CEMENT.*
104. " FOR PORTLAND. Fineness, not more than 20 per cent, to
be left on sieve of 5,806 meshes per square inch. Tensile strength
(1 part cement and 3 parts sand), 1 day in air and 6 in water, 113.78
Ibs. per sq. in.; 1 day in air and 27 in water, 170.68 Ibs. per sq. in.
105. "FOB EOMAN.f Fineness, same as for Portland. Tensile
strength (1 part cement and 3 parts sand) : For quick-setting
cements (taking 15 minutes, or less, to set), 1 day in air and 6 days
* Report of Committee on Uniform Tests of Cement, in Trans. Am. Soc. of C.
E., vol. xiv. p. 480.
t Essentially the same cement as Rosendale ; see § 72.
74 LIME AND CEMENT. [CHAP. III.
in water, 23 Ibs. per sq. in.; 1 day in air and 27 in water, 56.9 Ibs.
per sq. in. For slow-setting cements (taking more than 15 minutes
to set), 1 day in air and 6 days in water, 42.6 Ibs. per sq. in.; 1 day
in air and 27 in water, 85.3 Ibs. per sq. in."
ENGLISH SPECIFICATIONS FOR PORTLAND CEMENT. ^
The following is a summary of the specifications used by Mr.
Henry Faija, an accepted English authority. *
106. " FINENESS to be such that the cement will all pass
through a sieve having 625 holes (252) to the square inch, and leave
only 10 per cent, residue when sifted through a sieve having 2,500
holes (502) to the square inch.
107. " EXPANSION OR CONTRACTION. A pat made and submit-
ted to moist heat and warm water at a temperature, of about 100°
F., shall show no sign of blowing in twenty-four hours.
108. " TENSILE STRENGTH. Briquettes of slow-setting Portland,
which have been gauged, treated, and tested in the prescribed man-
ner, to carry an average tensile strain, without fracture, of at least
176 Ibs. per sq. in. at the expiration of 3 days from gauging ; and
those tested at the expiration of 7 days, to show an increase of at
least 50 per cent, over the strength of those at 3 days, but to carry
a minimum of 350 Ibs. per sq. in.
"For quick-setting Portland, at least 176 Ibs. per sq. in. at 3
days, and an increase at 7 days of 20 to 25 per cent., but a mini-
mum of 400 Ibs. per sq. in. Very high tensile strengths at early
dates generally indicate a cement verging on an unsound one."
TESTS KECOMMESTDED BY THE COMMITTEE OF THE AMERICAN
SOCIETY OF CIVIL EN GINEERS. f
109. "It is recommended that tests for hydraulic cement be
confined to methods for determining fineness, liability to checking
or cracking, and tensile strength ; and for the latter, for tests of 7
days and upward, that a mixture of 1 part of cement to 1 part of
sand for natural cements, and 3 parts of sand for Portland cements,
* As given "by Mr. Faijain Trans. Am. Soc. of C. E., vol. xvii. p. 225.
t Trans. Am. Soc. of 0. E., vol. xiv. pp. 478-85.
ART. 5.] SPECIFICATIONS FOB CEMENT. 7.5
be used, in addition to trials of neat cement. The quantities used
in the mixture should be determined by weight." For the form of
test specimen, method of mixing, etc., see § 87 and § 88.
110. " SAMPLING. There is no uniformity of practice among
•engineers as to the sampling of the cement to be tested, some test-
ing every tenth barrel, others every fifth, and others still every
barrel delivered. Usually, where cement has a good reputation,
,and is used in large masses, such as concrete in heavy foundations
or in the backing or hearting of thick walls, the testing of every
fifth barrel seems to be sufficient; but in very important work,
where the strength of each barrel may in a great measure deter-
mine the strength of that portion of the work where it is used, or
in the thin walls of sewers, etc., etc., every barrel should be tested,
one briquette being made from it.
"In selecting cement for experimental purposes, take the sam-
ples from the interior of the original packages at sufficient depth to
insure a fair exponent of the quality, and store the same in tightly-
closed receptacles impervious to light or dampness until required
for manipulation, when each sample of cement should be so tlior-
' oughly mixed, by sifting or otherwise, that it shall be uniform in
character throughout its mass.
111. " CHECKING OK CRACKING. The test for checking or crack-
ing is an important one, and, though simple, should never be
omitted. It is as follows :
" Make two cakes of neat cement 2 or 3 inches in diameter,
about -J inch thick, with thin edges. !N"ote the time in minutes
that these cakes, when mixed with water to the consistency of a
stiff plastic mortar, take to set hard enough to stand the wire test
recommended by Gen. Gillmore/ — ^-inch diameter wire loaded
with one fourth of a pound, and ^-inch loaded with 1 pound
(see § 82). One of these cakes, when hard enough, should be put in
water and examined from day to day to see if it becomes contorted
or if cracks show themselves at the edges, such contortions or
cracks indicating that the cement is unfit for use at that time. In
some cases the tendency to crack, if caused by the presence of too
much unslaked lime, will disappear with age. The remaining
cake should be kept in the air and its color observed, which, for a
good cement, should be uniform throughout (yellowish blotches
indicating a poor quality), the Portland cements being of a bluish-
76 LIME AKD CEMENT. [CHAP. III.
gray, and the natural cements being light or dark according to the
character of the rock of which they are made. The color of the
cements when left in the air indicates the quality much better than
when they are put in water.
112. "FINENESS. The strength of a cement depends greatly
upon the fineness to which it is ground, especially when mixed
with a large dose of sand. It is therefore recommended that the
tests be made with cement that has passed through a No. 100 sieve
(10,000 meshes to the square inch), made of No. 40 wire (Stubs's-
wire gauge). The results thus obtained will indicate the grade
which the cement can attain, under the condition that it is finely
ground, but it does not show whether or not a given cement offered
for sale shall be accepted and used. The determination of this
question requires that the tests should also be applied to the cement
as found in the market. Its quality may be so high that it will
stand the tests, even if very coarse and granular; and, on the other
hand, it may be so low that no amount of pulverization can redeem
it. In other words, fineness is no sure indication of the value of
a cement, although all cements are improved by fine grinding.
Cement of the better grades is now usually ground so fine that only
from 5 to 10 per cent, is rejected by a sieve of 2,500 meshes per
square inch, and it has been made so fine that only from 3 to 10
per cent, is rejected by a sieve of 32,000 meshes per square inch.
The finer the cement, if otherwise good, the larger dose of sand it
will take, and the greater its value.
113. " Sieves. For ascertaining the fineness of cement, it will be
convenient to use three sieves; viz., No. 50 (2,500 meshes to the
square inch), wire to be of No. 35 Stubs's wire gauge ; No. 74
(5,476 meshes to the square inch), wire to be of No. 37 Stubs's wire
gauge ; No. 100 (10,000 meshes to the square inch), wire to be of
No. 40 Stubs's wire gauge. The object is to determine by weight
the percentage of each sample that is rejected by these sieves, with
a view not only of furnishing the means of comparison between
tests made of different cements by different observers, but indicat-
ing to the manufacturer the capacity of his cement for improve-
ment in a direction always and easily within his reach.
"For ascertaining the fineness of sand, two sieves are recom-
mended ; viz., No. 20 (400 meshes to the square inch), wire to be
ART. 5.] SPECIFICATIONS FOR CEMENT. 77
of No. 28 Stubs's wire gauge ; No. 30 (900 meshes to the square
inch); wire to be of No. 31 Stubs's wire gauge.
" These sieves can be furnished in sets as follows, an arrange-
ment having been made with a manufacturer * of such articles, by
which he agrees to furnish them of the best quality of brass-wire
cloth, set in metal frames, the cloth to be as true to count as it is
possible to make it, and the wire to be of the required gauge.
\ Each set will be inclosed in a box, the sieves being nested.
Set A, three cement sieves, to cost $4.80:
]So. 100 7 inches diameter.
No. 74 6£ "
No. 50 6 "
Set B, two sand sieves, to cost $4.00:
No. 30 8 inches diameter.
No. 20 74- "
114. ^TENSILE STRENGTH. The tests should be applied to the
cements as offered for sale, f If satisfactory results are obtained with
a full dose of sand, the trials need go no further. If not, the coarser
particles should first be excluded by using a No. 100 sieve, in order
to determine approximately the grade the cement would take if
ground fine, for fineness is always attainable, while inherent merit
may not be.
"Standard Sand. The question of a standard sand seems one
•of great importance, for it has been found that sands looking alike
.and sifted through the, same sieves give results varying within rather
wide limits.
"The material that seems likely to give the best results is the
•crushed quartz used in the manufacture of sand-paper. It is a
commercial product, made in large quantities and of standard
grades, and can be furnished of a fairly uniform quality. It is
clean and sharp, and although the present price is somewhat ex-
cessive (3 cents per pound), it is believed that it can be furnished
in quantity for about $5.00 per barrel of 300 Ibs. As it would be
used for tests only, for purposes of comparison with the local sands,
.and with tests of different cements, not much of it would be re-
quired. The price of the German standard sand is about $1.25
* " Williams's Globe Wire Works, 85 Fulton Street, New York City."
t For the table of values recommended by the committee, see page 66.
78 LIME AND CEMENT. [CHAP. ill.
per 112 pounds ; but the article, being washed river sand, is prob-
ably inferior to crushed quartz. Crushed granite could be furnished
at a somewhat less rate than quartz, and crushed trap for about the
same as granite; but no satisfactory estimate has been obtained for
either of these.
" The use of crushed quartz is recommended by your Committee,
the degree of fineness to be such that it will all pass a No. 20 sieve-
and be caught on a No. 30 sieve. Of the regular grade of crushed
quartz — No. 3, — from 15 to 37 per cent, passes a No. 30 sieve, and
none of it passes a No. 50 sieve. As at present furnished, it would
need resifting to bring it to the standard size; but if there were
sufficient demand to warrant it, it could undoubtedly be furnished
of the size of grain required at little, if any, extra expense."
PART II.
METHODS OF PREPARING AND USING THE
MATERIALS.
CHAPTER IV.
MORTAR, CONCRETE, AND ARTIFICIAL STONE.
AKT. 1. MORTA.K.
115. Mortar is a mixture of the paste of cement or lime with
sand. The paste may be made before adding the sand, or the
materials may be incorporated dry and afterwards tempered to a
plastic condition with water. In common mortar, the cementing
substance is ordinary lime ; in hydraulic mortar, it is hydraulic
cement.
116. SAND. Sand is mixed with lime or cement to reduce the
cost of the mortar ; and is added to lime also to prevent the crack-
ing which would occur if lime were used alone. Any material may
be used to dilute the mortar, provided it has no effect upon the
durability of the cementing material and is not itself liable to de-
cay. Burnt clay, powdered brick, slag, or coal cinders may be used.
Of course the strength of the mortar decreases with the amount of
dilution.
117. Requisites for Good Sand. It is usually specified that sand
for mortar should be clean, and sharp, and free from pebbles.
Although it is customary to require that only clean sand shall
be used in mixing mortar, a small amount of finely powdered, inert
diluting material, as clay for example, will not materially decrease
the strength of the mortar. Clay, when dissolved or finely pulver-
ized, consists of an almost impalpable powder ; and when mixed
with the sand, its particles occupy the interstices between the par-
79
80 MOKTAR. [CHAP. IT.
tides of cement and sand, and are also completely enveloped by
the cementing paste. Clay, dissolved or finely pulverized, mixed
with, cement up to the proportion of 1 to 1, appears to affect the
strength essentially the same as an equal quantity of sand;* and
the mortar is much more dense, plastic, and water-tight, and is
occasionally convenient for plastering surfaces and stopping leaky
joints. Such mortar is not affected by the presence of water.
The cleanness of sand may be tested by rubbing a little of the
dry sand in the palm of the hand, and after throwing it out notic-
ing the amount of dust left on the hand. The cleanness of sand
may also be judged by pressing it together between the fingers
while it is damp ; if the sand is clean, it will not stick together, but
immediately fall apart when the pressure is removed. As a rule,
reasonably clean sand can be had without any extra trouble or ex-
pense.
Sharp sand, i.e., sand with angular grains, is much better than
that with rounded grains, although it is often difficult to obtain.
The sharpness of sand can be determined approximately by rubbing
-•a few grains in the hand, or by crushing it near the ear and noting
if a grating sound is produced; but an examination through a small
lens is better. The requirement that fi the sand shall be sharp" is
practically a dead letter in most specifications.
Sand should be screened to remove the pebbles, the fineness of
the screen depending upon the kind of work in which the mortar
is to be used. Every particle of the sand or " aggregate"' should be
•completely covered with the cement or " matrix ;" and since when
the grains in a given volume are small the magnitude of the total
surface to be covered is greater than when the grains are large, it
follows that fine sand requires a larger proportion of cement than
-coarse sand. Any specification or plan contemplating the use of
coarse sand must, therefore, be altered if fine sand alone is used, else
the quality of the mortar will be impaired. The best sand is that in
which the grains are of different sizes. The more uneven the sizes,
the smaller the voids, and hence less cement is required. The
voids of ordinary sand average from 0.3 to 0.5 of the volume.
118. Cost and Weight of Sand. The price of reasonably good
sand varies from 40 cents to $1.60 per yard, according to locality.
* Trans. Am. Soc. of C. E., vol. xiv. p. 164
ART. 1.] COMMON LIME MORTAR. 81
At Chicago, in 1887, sand cost on the average 40 cents per cubic
yard, delivered at the work.
Sand is sometimes sold by the ton. It weighs, when dry, from
80 to 115 Ibs. per cu. ft., or about 1 to 14- tons per cubic yard.
119. COMMON LIME MOETAR. Mortar made of the paste of
common or fat lime is extensively used on account of (1) its intrin-
sic cheapness, (2) its great economic advantage owing to its great
increase of volume in. slaking, and (3) the simplicity attending the
mixing of the mortar. On account of the augmentation of volume,
the paste of fat lime shrinks in hardening, to such an extent that
it cannot be employed as mortar without a large dose of sand.
As a paste of common lime sets or hardens very slowly, even in
the open air, unless it be subdivided into small particles or thin
films, it is important that the volume of lime paste in common
mortar should be but slightly in excess of what is sufficient to coat all
the grains of sand and to fill the voids between them. If this limit
be exceeded, the strength of the mortar will be impaired. With
most sands the proper proportions will be from 2.5 to 3 volumes
of sand to 1 volume of lime paste. Generally, if either less or
more sand than this be used, the mortar will be injured, — in the
former case from, excess of lime paste, and in the latter from poros-
ity. Notice that the volume of the resulting mortar is about equal"
to the volume of the sand alone.
120. The ordinary method of slaking lime consists in placing
the lumjos in a layer 6 or 8 inches deep in either a water-tight box,
-or a basin formed in the sand to be used in mixing the mortar, and
pouring upon the lumps a quantity of water 2J- to 3 times the vol-
ume of the lime.
This process is liable to great abuse at the hands of the work-
men. They are apt either to use too much water, which reduces
the slaked lime to a semi-fluid condition and thereby injures its
binding qualities ; or, not having used enough water in the first
place, to seek to remedy the error by adding more after the slaking
has well progressed and a portion of the lime is already reduced to
powder, thus suddenly depressing the temperature and chilling the
lime, which renders it granular and lumpy. It is also very impor-
tant that the lime should not be stirred while slaking. The essen-
tial point is to secure the reduction of all the lumps. Covering the
bed of lime with a tarpaulin or with a layer of sand retains the
82 * MORTAR. [CHAP, iv,
heat and accelerates the slaking. All the lime necessary for any
required quantity of mortar should be slaked at least one day before
it is incorporated with the sand.
After the lime is slaked the sand is spread evenly over the paste,,
and the ingredients are thoroughly mixed with a shovel or hoe, a
little water being added occasionally if the mortar is too stiff.
One barrel (230 Ibs.) of lime will make about 8 cubic feet of stiff
paste.
121. The common mortar of quick-lime and sand is not fit for
thick walls, because it depends upon the slow action of the atmos-
phere for hardening it; and, being excluded from the air by the
surrounding masonry, the mortar in the interior of the mass
hardens only after the lapse of years, or perhaps never.* The mor-
tar of cement, if of good quality, sets immediately; and, as far as is
known, continues forever to harden without contact with the air.
Cement mortar is the only material whose strength increases with
age. Owing to its not setting when excluded from the air, common
lime mortar should never be used for masonry construction under
water, or in soil that is constantly wet ; and, owing to its weakness, j*
it is unsuitable for structures requiring great strength, or subject
to shock. Its use in engineering masonry has been abandoned on \
all first-class railroads. Cem'enfc is so cheap, that it could profitably
be substituted for lime in the mortar for ordinary masonry.
122. HYDRAULIC LIME MORTAR. With mortars of hydraulic
lime the volume of sand should not be less than 1.8 times that of the-
lime paste, in order to secure the best results regardless'of cost.
The usual proportions are, however, for ordinary work, the same as
in common mortars, care being taken to incorporate sufficient paste I
to coat all the grains of sand and to fill up the voids between them. !
123. HYDRAULIC CEMENT MORTAR. A paste of good hydraulic j
cement hardens simultaneously and uniformly throughout the mass, !
and its strength is impaired by any addition of sand. The relative
quantities of sand and cement depend somewhat upon the kind of j
work and upon the conditions of the ingredients when measured.
For ordinary use, it is customary to add as much sand as is possi-
ble without making the mortar porous. The proportions may vary , V
* Lime mortar taken from the walls of ancient buildings has been found to be
only 50 to 80 per cent, saturated with carbonic acid after nearly 2,000 years of expos-
ure. Lime mortar 2.000 years old has been found in subterranean vaults, in exactly
the condition, except for a thin crust on top, of freshly mixed mortar.
AKT. 1.] HYDRAULIC-CEMEXT MOUTAE. 83
from 1 part of cement arid 2 parts of sand to 1 part of the former
and 4 of the latter. See § 134.
When the mortar is required in small quantities, as for use in
ordinary masonry, it is mixed about as follows: About half the
sand to be used in a batch of mortar is spread evenly over the bed
of the mortar-box ; and then the dry cement is spread evenly over
the sand ; and finally the remainder of the sand is spread on top.
The sand and cement are then mixed with a hoe or by turning and
re-turning with a shovel.* It is very important that the sand and
cement be thoroughly mixed.
The dry mixture is then shoveled to one end of the box, and
water is poured into the other end. Cements vary greatly in their
capacity for water (see §§ 82 and 99), freshly -ground cements requir-
ing more than those that have become stale. An excess of water
is, however, better than a deficiency, particularly when a very en-
ergetic cement is used, as the capacity of this substance for solidi-
fying water is groat. The sand and cement are then drawn down
with a hoe, small quantities at a time, and mixed with the water
until enough has been added to make a good stiff mortar. This
should be vigorously worked with a hoe for several minutes, to in-
sure a good mixture. The mortar should then leave the hoe clean
when drawn out of it, and very little should stick to the steel.
124. When mortar is required in considerable quantities, as in
mixing concrete, it is mixed by machinery. See § 152.
125. Hydraulic cements sot better and attain a greater strength
under water than in the open air; in the latter, owing to the evapo-
ration of the water, the mortar is liable to dry instead of setting.
This difference is very marked in hot, dry weather. If cement
mortar is to be exposed to the air, it should be shielded from the
direct rays of the sun, and kept moist by sprinkling or otherwise.
126. Rosendale vs. Portland Cement. It is sometimes a ques-
tion whether Portland or Eosenclale cement should be preferred.
Generally this question should be decided on economical grounds,
which makes it a question of relative strengths (see § 134) and rel-
ative prices (see § 138) ; but frequently it is determined by other
considerations. Thus if great ultimate strength is required, then
Portland cement must be used ; but if a quick-setting mortar is de-
sired, then Eosendale cement must be employed.
* See the last paragraph of § 260.
84 MOKTAK. [CHAP. IY.
Unless a quick-setting mortar is required, there is a decided
advantage in using Portland ; for as it hardens more slowly, it is
not so liable to set before reaching its place in the wall. This is an
important item, since with quick-setting cement any slight delay
might necessitate the throwing away of a boxful of mortar or the
removal of a stone to scrape out the partially-set mortar.
It is sometimes very desirable to have a cement which will set
more quickly than Portland, and filially attain a greater strength
than Rosen dale. Under such circumstances a mixture of Portland
and Eosendaie can be used. Cf Such mortar sets about as quickly as
if made with Rosendale cement alone, and acquires great subsequent
strength, due to the Portland cement contained in it, This was
proven by many experimental tests/5* The strength of the mixed
mortar is almost exactly a mean between that of the two mortars
separate.
127. Lime with Cement. The advantages of a slow-setting mor-
tar can be obtained by mixing common lime with a rich Eosendaie
mortar. The lime should le reduced to a paste before being added
to-the cement. The addition of the lime gives the double advantage
of a rather slow-setting mortar and a cheap one, but decreases
the strength of the mortar. No experiments seem to have been
made to determine the activity of a mixture of cement and lime ;
but from, practical experience it is well known that the addition of
lime somewhat retards the setting of cement mortar. The extent
to which the induration of different cements is affected by the ad-
dition of lime seems to vary directly with their activity.
It has long been an American practice to reinforce lime mortar
by the addition of hydraulic cement. The mortar for the ^ordi-
nary brick- work " of the United States public buildings is composed
of " one fourth cement, one half sand, and one fourth lime/' Of
course a cement mortar is better, but it costs more.
For the strength of a mortar composed of lime and cement, see
§135.
128. GROUT. This is merely a thin or liquid mortar of lime or
cement. The interior of a wall is sometimes laid up dry, and the
grout, which is poured on top of the wall, is expected to find its
way downwards and fill all voids, thus making a solid mass of the
wall.
* Trans. Am. Soc. of C. E., vol. xiv. p. 163.
ART. 1.] DATA FOE ESTIMATES. 85
Grout should never be used when it can be avoided. If made
thin, the water only slowly dries out of the wall ; and if made thick,
the grout fills only the upper portion of the wall. To get the
greatest strength, the mortar should have only enough water to
make a stiff paste — the less water the better. If the mortar is stiff,
the brick or stone should be dampene'd before laying ; else the brick
will absorb the water from the mortar before it can set, and thus
destroy the adhesion of the mortar.
129. DATA FOR ESTIMATES. The following data will be found
useful in estimating the amounts of the different ingredients neces-
sary to produce any required quantity of mortar: —
One barrel of lime (230 Ibs.) will make about 2J barrels (0.3
cu. yd.) of stiff lime paste. One barrel of lime paste and three
barrels of sand will make about three barrels (0.4 cu. yds.) of good
lime mortar. One barrel of unslaked lime will make about 6.75
barrels (0.95 cu. yd.) of 1 to 3 mortar.
A barrel of Portland cement weighs 400 pounds gross, or about
375 pounds net. Hudson Eiver Eosendale weighs 300 pounds net
per barrel. Western Eosendale weighs 265 pounds net per barrel.
A barrel of Eosendale, as packed at the manufactories on the
Hudson, will measure from 1.25 to 1.40 barrels, if measured loose.
A barrel of Western Eosendale will make about 1.1 barrels, if meas-
ured loose. A commercial barrel of Portland will make about 1.2
barrels, if measured loose.
One cubic foot of dry cement (shaken down, but not com-
pressed) mixed with 0.33 cubic feet of water will give 0.63 cubic
feet of stiff paste. One barrel (300 pounds) of finely-ground Eosen-
dale cement will make from 3.70 to 3.75 cubic feet of stiff paste; or
79 to 83 pounds of cement powder will make about one cubic foot
of stiff paste. Volume for volume, Portland will make about the
same amount of paste as Eosendale; or 100 pounds of Portland will
make a cubic foot of stiff mortar.
130. The proportions of sand and cement are generally measured
by volumes. In mixing mortars for experimental purposes both
the cement and the sand are measured loose ; but in actual work
the cement is usually delivered in barrels, and consequently the
most convenient unit for the cement is a commercial barrel, while
it is most convenient to measure the sand loose. Cement is some-
86
MORTAR.
[CHAP, iv.
times shipped in bags, but as an integral number of bags, usually
three or four, are equal in weight to a barrel, the barrel of packed
cement and the barrel of loose sand are still the most convenient
units. Occasionally cement is shipped in bulk, in which case the
quantity of cement required may be determined by weighing or by
measuring by volumes loose. If the cement is weighed, as is occa-
sionally done, the proportions can be adjusted readily to either
method of mixing.
The following table shows approximately the quantities of
cement and sand required for a cubic yard of mortar, of different
proportions, mixed in the two ways as above. The quantities in
the table are deduced from the results of actual trials ; but at best
they can be only approximate, since much depends upon the vary-
ing conditions of dampness and dryness, looseness and compactness,
fineness, degree of burning, etc.
TABLE 11.
INGREDIENTS REQUIRED FOR, A GIVEN QUANTITY OF MORTAR OF
DIFFERENT PROPORTIONS.
CEMENT AND SAND REQUIRED TO PRODUCE ONE CUBIC YARD
OF MOHTAR.
THE MORTAR BY
VOLUMES.
Mortar proportioned by volumes
of packed cement and
loose sand.
Mortar proportioned by volumes
of loose cement and
loose sand.
Cement.
Sand.
Cement, baiTels.
Sand,
CM. yds.
Cement, pounds.
Sanrl,
cu. yds.
Portland or
Ulster Co.
Rosendale.
Western
Rosendale.
Portland.
Rosendale.
1
0
7.14
6.43
0.00
2,675
2,110
.00
1
1
4.16
3.74
0.58
1,440
1,150
.67
1
2
2.85
2.57
0.80
900
720
.84
1
3
2.00
1.80
0.90
675
540
.94
1
4
1.70
1.53
0.95
525
420
.98
1
5
1.25
1.13
0.97
425
340
.99
1
6
1.18
1.06
0.98
355
285
1.00
For an example of the method of using this table, see top of puge 88.
. l.J
DATA EOR ESTIMATES.
87
The left-hand side of the table gives the quantity required when
commercial barrel of cement, i. e., a barrel of packed cement is
with a given number of barrels of sand.
When the cement is shipped in bulk, the right-hand side of the
is to be employed in making estimates. The quantities of
•cement in this side of the table can be translated into barrels by
remembering that the net weight per barrel of cement,, although
varying somewhat with manufacturers, size of barrels, fineness, etc.,
is about as follows : Portland, 375 pounds ; Eastern Kosendale, 300
.pounds ; Western Bosenclale, 265 pounds.
Cement is also sometimes shipped in bags. Frequently the
~bags contain an aliquot- part of a barrel, in which case either side
•of the table may be used, according to the method to be employed
in mixing the cement and sand. Sometimes the bags contain an
even number of hundred-weight, in which case the right-hand side
-of the table is most convenient.
131. The following data concerning the amount of mortar re-
•quircd per cubic yard for the different classes of masonry, extracted
from succeeding pages of this volume, are collected here for greater
'Convenience in making estimates.
TABLE 12.
AMOUNT OF MORTAR REQUIRED FOR A CUBIC YARD OF MASONRY.
DESCRIPTION OF MASONRY
VOLUME 01
cubic i
' MORTAR,
jar da.
Min.
Max.
•Ooncrete, broken stoue — no screenings or gravel (see
*& 149-51)
0 50
0 55
.Hough rubble (§214)
0 33
0 40
li,ubblc with joints rough hummer-dressed
0 25
0 30
^Scuuired stone masonry (see § 210) .....
0 15
0 20
.Ashlar, with 12" to 20'' courses and f- to -J-inch joints
(see § 205)
0 07
008
Ashlar, with 20" to 30" courses and i- to f-inch joints
(see § 205)
0 05
006
.Ashlar, largest blocks and closest joints (see § 205)
IBrickwork, f- to ^-inch joints (see § 256)
0.03
0 35
0.04
0.40
" $- to i-inch joints " "
0.25
0.30
" •J-inch joints *' "
0.10
0.15
MOBTAR. [CHAP, IT.
Example. — How much cement and sand will "be required to lay
10 cubic yards of best rubble masonry, using a mortar composed of
1 part packed cement and 3 parts sand? By the preceding table, it
is seen that the best rubble will require 0.33 yards of mortar per
yard of masonry; hence 10 yards of masonry will require 3.3 cubic
yards of mortar. From the table on page 86, it is seen that 1 cubic
yard of the above mortar will require 2 barrels of cement and 0,9
cubic yards of sand; hence 3.3 cubic yards of rnortar will require
6.6 barrels of cement and 2.97 cubic yards of sand.
132. STRENGTH OF MORTAR. The strength of mortar is de-
pendent upon the strength of its cementing material, upon the
strength of the diluting material, and upon the adhesion of the
former to the latter. "When sand is used and the grains are entirely
enveloped with cementing material, the strength of the mortar will
depend upon the strength of the cement and its adhesion; but when
the paste is insufficient to fill the voids, the strength of the mortar
will depend upon the amount of cementing material and its adhesive
power. The strength of the diluting material is an unimportant
consideration.
The kind and amount of strength required of mortar depends
upon the position in which it is employed. If the blocks are large
and well dressed, and if the masonry is subjected to compression
only, then the mortar needs only hardness, or the property of resist-
ing compression; but if the blocks are small or irregular, the mortar
should have the capacity of adhering to the surfaces of the stone or
brick, so as to prevent their displacement; and, if the masonry is
liable to be subjected to lateral or oblique forces, the mortar should
possess both adhesion and cohesion (tensile strength).
133. Tensile Strength. Fig. 5 shows the effect of time on the
tensile strength of cement mortars having different proportions of
sand. The diagram was constructed from the " Eecord of Tests of.
Cement made for Boston Main Drainage Works."" *
" The results were compiled from about 25,000 breakings of
twenty different brands, and fairly represent the average strength
of ordinary good cements of the two kinds." The diagram is-
instructive in several ways. It "shows that Portland cement
acquires its strength more quickly than Rosenclale ; that both
cements (but especially Kosendale) harden more and more slowly
* E. C. Clarke in Trans. Am. Soc. of C. E., vol. xiv. p. 150.
AET. 1.]
STRENGTH OF MORTAR.
as the proportion of sand mixed with them is increased ; that
whereas neat cements and rich mortars attain nearly their ultimate
strength in six months or less, weak mortars continue to harden
for a year or more. The table shows the advantage of waiting as-
long as possible before loading masonry structures, and the possi-
bility of saving cost by using less cement when it can have ample
FIG. 5.— DIAGRAM SHOWING THE EFFECT OF TIME ON THE STRENGTH OF CEMENT MORTARS.
time to harden. It also shows that Portland cement is especially
useful when heavy strains must be withstood within a week."*
The first 24 hours after mixing, Eosendale is the stronger.
The line for the strength of lime mortar probably represents
the maximum value that can be obtained by exposing the mortar
freely to the air in small briquettes. This line is not well deter-
mined.
134. The diagrams of Pig. 6 show the effect of varying the pro-
portions of cement and sand, and also show the relative strength
*E. C. Clarke in Trans. Am. Soc. of C. E., vol. xiv. p. 150L
MOKTAB.
[CHAP. iv.
of Eosendale and Portland mortars at different ages. The dia-
grams represent the average results of a vast number of experi-
ments. All available data were plotted, and the lines indicating
300
100
Age
\
We
M
rta
OJZ34S6701Z3
\
BOO
ZOO
100
\
Age
tf
Mo
rlar
\
1 J
don
Ik
\
\
\
\
\
<&,
\
X.
^
*
— *.
"\
—
6 7
4-00
§300
\
Jf*
of
Mo
rlar
\
6 J
Vlon
Iks
\
\
\
\
\
V
\
\
\
V*
\
^
;**
^
^
2^;
^"•x
' ,
\
000
400
300
zoo
100
0
\
Age
of
M
rial
\
\
1 \
fa
\
\
\
\
\
\
\
\
\
^
^
)>
^
k
"^-
01 Z. $ 4 Sr670Jl£34$'67
Volumes of Sand to / Volume of Cement.
FIG. 6.— DIAGRAM SHOWING THE STRENGTH OF CEMENT MORTARS.
the strength were drawn so as to represent as nearly as possible the
mean of all the experiments, — due attention being given to the
relative reliability of the different results and to the character of
the curve. Since, generally, the individual values plotted were
ART. 1.] STRENGTH OP MORTAR. 91
themselves means, there were no very erratic results, and conse-
quently the lines are quite reliable. There were fewer experiments
for the larger proportions of sand to cement ; hence the curves are
less accurate the larger the proportion of sand. Unusually hurd-
1 aimed (L e., heavy) cements, when tested neat, will show a greater
,-trength than that given by the diagram. Very heavy and care-
fully prepared Portland cements have shown an ultimate strength
of 1,000 to 1,200 pounds per square inch. Very fine cements when
mixed with sand will show greater strength than that given by the
table. The diagrams are intended to give fair working values.
These curves are especially useful in discussing the question of
economy in the use of cement (see §§ 138-40).
Example. — To illustrate the method of using the diagrams, as-
sume that we desire to know the strength of a 1 to 2 Rosendale
cement mortar a year old, and also the proportions of a Portland
cement mortar of equal strength. At the bottom of the lower
right-hand diagram of Fig. 6 find the proportion of sand in the
mortar, which in this case is 2 ; follow the corresponding line up
until it intersects the "Kosendale" line. The elevation of this in-
tersection above the base, as read from the figure at the side of the
diagram, is the strength of the specified mixture, which in this case
is about 170 pounds per square inch. The second part of the
problem, then, is to determine the proportions of a Portland cement
mortar which will have a strength of 170 pounds per square inch.
Find the 170 point on the scale at the side of the diagram, and.
imagine a horizontal line passing through this point and intersecting
the " Portland" line ; from this point of intersection draw a ver-
tical line to the base of the diagram, and this point of intersection
gives the required number of volumes of sand to one volume of
cement, which in this case is 4. Therefore a 1 to 2 Eosendale
mortar a year old has a strength of 170 pounds per square inch;
iind is then equivalent to a 1 to 4 Portland mortar.
135. Fig. 7 shows the effect of mixing lime and cement. The
upper line gives the strength of a mixture of Eosendale cement
and lime, and is fairly well determined. The lines showing the
strength of a mortar composed of sand, and a paste of lime and
cement of the proportions shown at the bottom of the diagram,
are drawn on the assumption that adding sand to a paste of cement
and lime has the same effect, proportionally, as adding sand to a
92
MORTAK.
[CHAI
paste of neat cement. A few experiments seem to support
conclusion, and none have been made which, contradict it.
The addition of lime mortar to cement is more injurious
Portland than with Rosendale. When the lime paste is eqn
or exceeds the cement paste, it makes practically no differed
the strength of the mortar which cement is used. For econo:
considerations, a mixture of Portland cement and lime shoulc
,sW
I
^200
s
~*e
<%'*>
£
Percent
100
-O
SO
70
so
60
SO
30-cfCe:
70-df LL
JO
Composition of the Pasle
FlO. 7. —DIAGRAM SHOWING THE EFFECT OF ADDING LlME TO CEMENT MOB
be chosen when a mortar intermediate between common lie
cement is desired.
Notice that the addition of a small amount of lime pai
but a slight effect upon the strength of the resulting morta
addition of 20 or 25 per cent, of lime will not greatly decre;
strength, but will materially reduce the cost.
136. Compressive Strength. But few experiments hav
made upon the compressive strength of mortar. An exam
of the results of about sixty experiments made with the Wai
-testing-machine seems to show that the compressive strei
mortar, as determined by testing cubes, is from 8 to 10 tir
tensile strength (see § 134) of the same mortar at the sai
See also § 97. Data determined by submitting cubes of m<
a compressive strain are of little or no value as showing the s
of mortar when employed in thin layers, as in the joints of n
The strength per unit of bed area increases rapidly as the ti
of the test specimen decreases, but no experiments have e^
made to determine the law of this increase for mortar.
ART. 1.] ADHESIVE STRENGTH 03
137. Adhesive Strength. Unfortunately very few experiments
have "been made on the adhesive strength of mortars, i. e.j the
power with which mortars stick to brick, stone, etc. It is com-
monly assumed that, after the lapse of a moderate time, the adhe-
sive and cohesive strengths of cement mortars are about equal, and
that in old work the former exceeds the latter. Modern experi-
ments, however, fail to establish the truth of this assumption, and
indicate rather that the adhesion of mortar to brick or stone is
much less, during the first few months, than its tensile strength ;
and also that the relation between the adhesive strength and cohe-
sive strength (the resistance of the mortar to pulling asunder) is
very obscure. The adhesion of mortars to brick or stone varies
greatly with the different varieties of these materials, and particu-
larly with their porosity. The adhesion varies also with the quality
of the cement, the character, grain, and quantity of the sand, the
.amount of water used in tempering, the amount of moisture in the
stone or brick, and the age of the mortar. Some cements which
exhibit high tensile strength give low values for adhesion ; and
conversely, cements which are apparently poor when tested for
•cohesion show excellent adhesive qualities.
The table* on the following page gives all the reliable data known.
A comparison of the table with the diagram on page 90 shows that
the adhesion of a mortar is far less than its tensile strength at the
same age, but fails to show any definite relation between the two.
In the experiments by Dr. Bohme at the Eoyal Testing Laboratory
.at Berlin the mortar was made with standard qiiartz sand, and the
tensile strength of the mortar and its adhesion to common brick
were determined separately. By comparing the tensile and adhesive
strengths at the same ages, it was found that the former was always
about ten times greater than the latter when the mortar consisted of
one part of cement to three or four parts of sand, and from six to
eight times greater when the cement was used neat or with one or
two parts of sand. In the experiments made by Prof. Warren, of
'.Sydney University, New South Wales, the tensile strength of neat
Portland cement mortar was three and a half times its adhesion to
brick. The result of twelve thousand special tests by Mr. Mann
was that pure Portland cement of 425 Ibs. tensile and 5,640 Ibs.
* Compiled by Emil Kuichling, for the report of the Executive Board of the
.City of Rochester, N. Y., for 1SSS.
94
MOHTAE.
[CHAP, iv.
TABLE 13.— ADHESIVE STRENGTH OF MORTARS.
Reference No.
Age, in days, when
tested.
Kind of Cement used.
Materials
Cemented to-
gether.
Average adhesive strength in
pounds per square inch.
Authority.
&
ji
ji
Cement, 1;
sand, 8.
Cement, 1;
sand. 4.
1
2
3
4
6
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
2fi
27
28
29
30
31
82
88
34
85
86
37
38
89
40
41
42
43
44
45
46
47
•H
5'.)
51
52
53
54
55
16
28
30
42
II
90
95
110
180
270
320
lyr
;;
Quick-setting cement
Slow-setting cement.
Portland
Hard brick
*23
Robertson ISM
I. J. Mann. ..18S3
Hard brick
*15
Sawed limest'ne
57
Cut granite .
41
i
Dr. Bohme.!" "
Prof. Warren.. '87
Boistard.
Dr. Boh me.... 1883
Prof. Warren. .'87
Robertson 1858
Gen. Gillmore.'63-
I. J.Mann 18S2
Building News,W
J. White 1832
Bauschinger..l87S
Dr. Bohme..l.'l883.
Bauschmger..l8J3
Rondelet "lS31
n
Polished marble
Bridgewater
brick
38
19
t,
Hydraulic lime
Portland . .......
tBrick
$ "
24.1
168
21.0
102
117
18.7
88
58
9-15
5
15.3
20
26
13.2
9
16
§ "
Quicklime
Lime and cement
Hydraulic lime
Portland
Limestone
tBrick
if. "
35.1
213
30.4
105
146
25.5
45
73
*30
20.9
24
48
17.5
14
45
§ "
Quick-setting cement
Slow-setting cement.
Rosendale
Hard brick
Hard brick
Croton brick. . . .
30.8
27.5
78
1197
15.7
20.8
12.3
12.0
6.8
9.2
5.2
7 £
Portland
Fine-cut granite
Sawed limest'ne
Cut granite..
Polished marble
Bridgewater
brick
1171
1166
ti
«
Sandstone ....
44
Blue lias lime
Staffordshire
brick
*40
Lime andpozzuolana
Portland
Gray stock brick
Common soft "
Hard brick
Wrick
f "
' ' 68.8
*S6
*18
*5
46.9
24*2
t<
54.0
41.9
56.9
88.9
Hydraulic lime
t " .'.".'.'.'..'!!!,"
IT "
39.3
i 28.1
14.2
19. «
226
Portland
Hydraulic li mo .. .
Quicklime
Brick
*33
" {Limestone
Robertson" .'.".'."l85S
I J Mann "*.*1883
|Hard brick
" ... Soft brick
*40
*18
Portland Sawed s late
116°
" 'Portland ston*». .
!5*5
Lime and' pozzuolana
Roseudule
Polished marble
Hard brick
1175
"*8*
j' White ""lR®
firnr.on brink-
68
40
24
Gen. Gillmore 1863
Vicat 1818
Quicklime N >t stated
*21
Ordinary hydraulic
time
« <>
*85
*51
Good hydraulic lime
Portland
u «
*140
u u
Materials in air.
" in water
Gault-clay brick
pressed.
70
Mallet 1829
99
45
78
96
48
40
126
123
44
63
70
47
29
83
62
J. Grant 1871
Stock brick in
air
u
Stock brick in
water
1C
Staf. blue brick
In air
„
Staf. blue brick
in water
Fareham red
hrick in air
Fareham red
brick in water.
u
„
* Proportions of sand not given, but presumably about those indicated in headings of table.
f Standard sand used in mixture. * Clean river-sand used in mixture.
S Crushed sandstone used in mixture.
i Coarse particles in cement sifted out before testing. T Fine river-sand used in mixture.
ABT. 1.]
COST.
95
compressive strength per square inch lias but 60 to 80 Ibs. adhesion,
to limestone, and that the ratio of tensile .to adhesive strength
varies from 5.1 to 9.1.
138. COST OF MOETAE. The analysis of the cost of a cubic yard
of mortar composed of 1 volume of cement (packed) to 2 volumes
of sand (loose) is about as follows :
Cement 2.85 bbls. (see page 86) <
Sand 0. 8 cu. yd. (see page 86) i
Labor, handling materials and mixing £ day <
£1.20 = $3 43
0.40 = 32
1.50 = 50
$4 25
Of course the cost will vary with the composition of the mortar,
but with the table on page 86 and the current prices of materials,
it is easy to compute the cost. The expense for labor is quite varia-
ble, depending upon the distance the ingredients must be moved,
etc. If the mixing is done by machinery, the cost of mixing may
be as low as 25 cents per cubic yard.
139. It is frequently a question as to whether Portland or Rosen-
dale cement is the more economical. This is a question of relative
strengths and relative prices. The diagrams of Fig. 6 show the
relative strength, at different ages, of Eosendale and Portland
mortars of varying proportions of cement and sand.
To illustrate the method of using these diagrams, let it be as-
sumed that a mortar is desired which shall have a strength of 90
to 100 Ibs. at the end of a week. What composition shall the mor-
tar have, and which cement is the cheaper? By the upper left-hand
diagram it is seen that a clear Eosendale and also a 1 to 3 Portland
mortar possesses the requisite strength. The cost of a ciibic yard of
each — if it be assumed that both the cement and sand are measured
loose, i. e., if we use the right-hand side of Table 11 — will be about
as follows:
Rosendale, neat.
Cement (2,140 Ibs.), 7.14 bbls,
@ $1.00
Labor
$7 14
50
Total -cost $7 64
Portland, 1 to 3.
Cement (675 Ibs.), 1.8 bbls. @
$3.00 $540
Sand, 0.94yd. @ $0.40 37
Labor 50
Total cost $6 27
MORTAR.
[CHAP. iv.
Again, at the end of one year a 1 to 2 Eosendale mortar is equal
in strength to a 1 to 4 Portland mortar. The cost of these mortars
is as follows:
Rosendale, 1 to 2.
Cement (720 Ibs.), 2.40 bbls. @
$1.00 ....................... $2 40
Sand, 0.84 cu. yd. @ $0.40. ... 33
Labor ........................ 50
Total cost ........ $3 23
Portland, 1 to 4.
Cement (525 Ibs.), 1.4 bbls. @
13.00..' $4 20
Sand, 0.98 cu. yd. @ $0.40. ... 40
Labor 50
Total cost $5 10
If, in the mixing, the cement be measured in its compacted state,
i. e., if the left-hand side of Table 11 be used, the cost for the first
mortar in the above examples will be $7. 64 and 86.86, respectively;
under the same conditions the second mortar will cost $3.67 and
$5.98, respectively.
140. It will be noticed in the above examples that in the first
•case the Portland is the cheaper, and in the second the Eosendale.
However, outside of any question of strength or first cost, the
slow-setting property of Portland cement gives it a decided advantage
over Eosendale, as has already been discussed (§ 126).
When a very cheap mortar is desired, it is customary to use' cem-
ent with a large dose of sand; but this is objectionable, since the re-
sulting mortar is very porous and consequently disintegrates rapidly.
It is better to add common lime to the cement rather than to in-
crease the quantity of sand. This is, then, a question of relative
.strengths and relative cost, and sometimes also of relative activity.
The diagram on page 92 shows the strength of various mortars with
varying proportions of cement and lime, from which the strength
•of any proposed combination can be determined. The amount
'•t the several ingredients required can be determined by the table
i page 86, having which the cost can easily be computed. Gen.
., ill more frequently urges the economy of mixing lime paste with
cement mortar.
141. MORTAR IMPERVIOUS TO WATER. Nearly every failure of
masonry is due to the disintegration of the mortar in the outside of
the joints. Ordinary mortar — either lime or cement — absorbs water
freely, common, lime mortar absorbing from 50 to 60 per cent, of
its own weight, and the best Portland cement mortar from 10 to
20 per cent. ; and consequently they disintegrate under the action
ART. 1.] IMPERVIOUS TO WATER. 97
of the frost. Mortar may "be made practically non-absorbent by the
addition of alum and potash soap. One per cent. , by weight, of pow-
dered alum is added to the dry cement and sand, and thoroughly
mixed; and about one per cent, of any potash soap (ordinary soft-
soap made from wood ashes is very good) is dissolved in the water
used in making the mortar. The alum and soap combine, and form
compounds of alumina and the fatty acids, which are insoluble in
water. These compounds are not acted upon by the carbonic acid of
the air, and add considerably to the early strength of the mortar, and
•somewhat to its ultimate strength.
With lime mortar, the alum and soap has a slight disadvantage
in that the compounds which render the mortar impervious to water
tilso prevent the air from coming in contact with the lime, and con-
sequently prevent the setting of the mortar. On the other hand,
the alum and soap compounds add considerably to both the early
and the ultimate strength of the mortar. -
This method of rendering mortar impervious is an application of
the principle of Sylvester's method of repelling moisture from ex-
ternal walls by applying alum and soap washes alternately on the
outside of the wall (see § 263). The same principle is applied in
McMurtrie's artificial stone (see § 102). The alum and soap are
easily used, and do not add greatly to the cost of the mortar. The
mixture could be advantageously used in plastering, and in both
cement and lime mortars of outside walls or masonry in damp places.
It has been very successfully used in the plastering of cellar and base-
ment walls. It should be employed in- all mortar used for pointing
<§ ^04).
The addition of a small amount of finely powdered clay decreases
the permeability of mortar (see § 117); but since clay absorbs and
parts with water with the changing seasons, the use of clay is not
efficient in preventing disintegration by freezing and thawing.
142. SUGAR IN MORTAR. Although saccharine matter has been
•employed in India as an ingredient of mortar from time immemorial,
.and reference has been made to it by standard authorities, its effect
is not generally known ; and the subject has attracted considerable
attention in England and America during the past year.
Sugar unites with lime and forms sucrate of lime, — a solid which
possesses considerable strength, dissolves freely in water, and is acted
upon by carbonic acid. AH hydraulic cements contain at least 50
98 MORTAR. [CHAP, iv,
per cent, of lime compounds; hence, if a saccharine substance be
added to mortar, the sugar will unite with the lime and form
su crate of lime. The presence of this compound may be an advantage
or a disadvantage, according to attendant conditions. For example,
if the mortar is composed of common lime and sand, the sucrate of
lime., being stronger than the carbonate, will add to the strength of
the mortar; and as the lime will unite with the sugar more rapidly
than with the carbonic acid of the air, the sugar will also cause the
mortar to set more quickly. In India, the practice is to add 1
pound of the coarsest sugar (or its equivalent in syrup) to each
gallon of water with which the mortar is mixed. This amount of
sugar is said to add one half to the breaking strength of the mor-
tar and to double its cohesive strength. It is better to dissolve the
sugar in the water than to mix it dry with the lime, since some
limes in slaking "bum" the sugar, thereby destroying its strength-
ening effect and also blackening the mortar.
The addition of sugar increases the early strength of lime mortar,
since the sue rate of lime develops its strength more rapidly than the
carbonate. If lime mortar were used in the interior of thick walls,
the addition of a saccharine substance would be beneficial, since
lime mortar thus placed would never become fully saturated with
carbonic acid,* The addition of sugar to cement mortar will accel-
erate or retard the setting of the cement, depending upon (1) the
amount of sugar present (as far as the cement is concerned the sugar
is an adulteration), (2) the relative indurating activity of the sucrate
and the silicate, and (3) the amount of water used (the cement is
hydraulic while the sucrate is non-hydraulic, and hence the former
will set in the presence of water while the latter will not). This
principle may explain the conflicting results obtained from different
experiments. For example, one experimenter f found that sugar
greatly accelerates the setting of Portland cement, causing it to set
in a few minutes; on the other hand, most experimenters J find
that sugar in any proportions retards the setting of Portland cement.
* Lime mortar has been taken from the walls of ancient buildings which were
only 50 to 80 per cent, saturated with, carbonic acid after .an exposure of nearly 2,000
years.
t Engineering News, vol. xvii. p. 6.
I For example. Mechanics, vol. ix. pp. 315-17;— a paper read at the Washington
meeting of the Am. Soc. of M. E., to be published in vol. ix. of the Transactions of
that Society.
ABT. 1.] SUGAR I1ST MORTAR. 99
All experimenters agree that sugar retards the setting of Kosendale
cement.
Sugar added to mortar may decrease or increase the ultimate
strength of the mortar, depending upon (1) the amount of sugar
present and (2) the relative ultimate strength of the compounds
formed. For example, with lime mortar the maximum effect — an
addition of 50 per cent, to the ultimate tensile strength — is ohtained
when the weight of the sugar is equal to about 10 per cent, of the
weight of the lime. With neafc Eosendale cement mortar, the max-
imum effect at the end of three months — an addition of about 20
per cent, to the tensile strength — is obtained with £ to £ per cent*
of sugar. With neat Portland cement mortar the evidence is con-
flicting. One experimenter * obtained a maximum effect — an addi-
tion of 25 per cent, to the strength — with 1 per cent, of sugar; while
another f concluded that "sugar was of no great advantage in com-
bination with the best qualities of Portland cement/' The last
conclusion was corroborated by experiments made by the author.
143. The sucrate of lime, being soluble in water, will in time
be washed out by the ruin ; therefore the addition of a saccharine
substance to mortar is most beneficial in a dry climate, as in India,
for example, A saccharine substance should not be added when
the cement is to be used under water. The compounds of lime
with sugar are attacked by the carbonic acid of the air, and hence
the strengthening effect of the sugar is not permanent when the
mortar is exposed to the weather. Owing to these two facts, the use
of sugar with cement is not of much practical value. Although
sugar adds materially to the strength of lime mortar, the compound
is inferior in strength, cost, and durability to cement mortar.
It is highly probable that the effects obtained by mixing sugar
with mortar can also be obtained by the use of gum-arabic, dextrine,
glucose, or starch. The use of such materials in mortar involves
some interesting questions ; and a study of this subject by an engi-
neer-chemist might lead to valuable results.
Plaster of Paris (sulphate of lime) added to either lime or cement
mortar has the same general effect as adding sugar ; that is to say,
added in quantities not exceeding 5 per cent, it accelerates the
* Mechanics, vol. ix. pp. 815-17 ; a paper read at the Washington meeting of the
Am. Soc. of M. E., to be published in vol. ix. of the Transactions of that Society,
t Engineering News, vol. xvi. p. 833.
100 MORTAR. [CHAP. IV.
setting., and also increases the early and the ultimate strength of
mortar. The addition of plaster of Paris to common cement is the
special feature of selenitic cement, which is much used in England.
144. FREEZING OF MOBTAR. It does not appear that common
lime mortar is seriously injured by freezing, provided it remains
frozen until it has fully set. The freezing retards, but does not en-
tirely suspend, the setting. Alternate freezing and thawing materi-
ally damages the strength and adhesion of lime mortar. Although
the strength of the mortar is not decreased by freezing, it is not
always permissible to lay masonry during freezing weather ; for
example, if, in a thin wall, the mortar freezes before setting and
afterward thaws on one side only, the wrall may settle injuriously.
" Mortar composed of 1 part Portland cement &TL& 3 parts of sand
is entirely uninjured by freezing and thawing. Mortar made of
cements of the Rosendale type, in any proportion, is entirely ruined
by freezing and thawing."* It is probable that this difference is
due to the fact that the expansive force of water, in freezing is less
than the strength of the richer Portland cement mortars and greater
than any Eosendale cement mortar. In the latter case, freezing is
equivalent to agitating the mortar after it has partially set. Mortar
made of over-clayed cement (which condition is indicated by its
quicker setting), of either the Portland or Eosendale type, will not
withstand the action of frost as well as one containing less clay ; for
since the clay absorbs an excess of water, it gives an increased effect
to the action of frost.
It is customary, in making cement mortar which is liable to be
frozen before setting, to add salt to the water with which it is mixed.
The ordinary rule is : "Dissolve 1 pound of salt in 18 gallons of water
when the temperature is at 32° Fahr., and add three ounces of salt
for every 3 degrees of lower temperature." Since the salt contains
carbonic acid, and since lime mortar hardens by the absorption of
this acid, it would seem that salt should strengthen lime mortar ;
but of this there is no experimental proof. The use of salt, and
more especially of sea water, in mortar is objectionable, since the
accompanying salts usually produce efflorescence (see § 265). It is
also probable that fresh water charged with carbonates makes slightly
stronger mortar than pure water. It is not certain that the addi-
tion of salt to Portland cement mortar does either any good or any
* Trans. Am. Soc. of C. E., vol. xvi. pp. 79-84.
AKT. 1.] FREEZING. 101
harm ; it appears to retard slightly the setting,* Eosendale cement
mortar, when mixed with a saturated solution of salt and water.,
does not freeze at the ordinary winter temperature of New York ; f
and hence it is not injured by frost.
When masonry is to be laid in lime mortar during freezing
weather, frequently the mortar is mixed with a minimum of water
and then thinned to the proper consistency by adding hot water
just before using. This is undesirable practice (see § 120). When
the very best results are sought, the brick or stone should be warmed
— enough to thaw off any ice upon the surface is sufficient —
before being laid. They may be warmed either by laying them on.
a furnace, or by suspending them over a slow fire, or by wetting
with hot water.
145. CHANGE OF VOLUME IN SETTING. The Committee of the
American Society of Civil Engineers draw the following conclusions: J
1. Cement mortars hardening in air dimmish in linear dimensions,
at least to the end of twelve weeks, and in most cases progressively.
2. Cement mortars hardening in water increase in like manner, but
to a less degree. 3. The contractions and expansions are greatest
in neat cement mortars. 4. The quick-setting cements show greater
expansions and contractions than the slow-setting cements. 5. The
changes are less in mortars containing sand. G. The changes are
less in water than in air. 7. The contraction at the end of twelve
weeks is as follows: for neat cement mortar, 0.14 to 0.32 per cent.;
for a mortar composed of 1 part cement and 1 part sand, 0. 08 to
0. 1 7 per cent. 8. The expansion at the end of twelve weeks is as
follows: for neat cement, 0.0-i to 0.25 per cent.; for 1 part cement
and 1 part sand, 0.0 to 0.08 per cent. 9. The contraction or ex-
pansion is essentially the same in all directions.
146. ELASTICITY, COMPEESSION, AND SET OP MOETAR. For
data on elasticity see page 13. The evidence is so conflicting that
it is impossible to determine the co-efficient of compression and of
set of mortar, even approximately. For much valuable data on this
and related subjects, see the " Report of Progress of the Committee
* Trans. Am. Soc. of C. E., vol. xvi. p. 81.
t Ibid. p. SB.
J See the " Report of Progress of the Committee on the Compressive Strength of
Cements and the Compression of Mortars and Settlement, of Masonry," in the
Transactions of that Society, vol. xvii. pp. 213-37; also a similar report in vol. xvi.
pp. 717-32.
102 CONCRETE. [CHAP. IT.
on the Compressive Strength of Cements and the Compression of
Mortars and Settlement of Masonry/5 in the Transactions of the
American Society of Civil Engineers, vol. xvi. pp. 717-32, vol. xvii.
pp. 213-17, and also vol. xviii. pp. 264-80. The several annual re-
ports of tests made with the United States Government testing-ma-
chine at Watertown contain valuable data — particularly the report
for 1884, pp. 69-247 — bearing indirectly upon this and related
subjects; but since some of the details of the experiments are want-
ing, and since the fundamental principles are not well enough
understood to carry out intelligently a series of experiments, it is
impossible to draw any valuable conclusions from the data.
ART. 2. CONCRETE.
147. Concrete is a species of artificial stone. It is sometimes
called leton, the French equivalent of concrete.
" Concrete is admirably adapted to a variety of most important
uses. For foundations in damp and yielding soils and for subter-
ranean and submarine masonry, under almost every combination of
circumstances likely to be met with in practice, it is superior to
brick masonry in strength, hardness, and durability; is more
economical; and in some cases is a safe substitute for the best
natural, stone, while it is almost always preferable to the poorer
varieties. For submarine masonry, concrete possesses the advantage
that it can be laid, under certain precautions, without exhausting the
water and without the use of a diving-bell or submarine armor.*
On account of its continuity and its impermeability to water it is an
excellent material to form a substratum in soils infested with springs;
for sewers and conduits; for basement and sustaining walls; for
columns, piers, and abutments; for the hearting and backing of
walls faced with bricks, rubble, or ashlar work; for pavements in
areas, basements, sidewalks, and cellars; for the walls and floors of
cisterns, vaults, etc. Groined and vaulted arches, and even entire
bridges, dwelling-houses, and factories, in single monolithic masses,
with suitable ornamentation, have been constructed of this material
alone.""f
* For a series of papers on Concrete as Applied to Harbor Improvements, see
Proc. Inst. of C. E., vol. Ixxxvii. pp. 65-240.
t Gillmore's Limes, Hydraulic Cements, and Mortars, p. 225.
I
ABT. 2.] INGEEDIENTS. 103
Tlie great value of concrete in all kinds of foundations is slowly
Doming to be appreciated. It is superior to any other form of base.
It enables the engineer to build his superstructure on a monolith
as long, as wide,, and as deep as he may think best, which cannot
fail in parts, but, if rightly proportioned, must go all together — if
it fails at all.
148. iNGrKEDlEETTS. Concrete is composed of (1) the matrix,
-which may be either lime or cement mortar — usually the latter, —
.and (2) the aggregate, which may be any hard material, as gravel,
pebbles, broken shells, stone, broken brick, slag, etc.
The mortar may be made as already described in Art. 1 above.
"Whatever the aggregate, it should be free from dust, earth, or any
weak material. The aggregate should be of different sizes, so that
the smaller shall fit into the voids between the larger. This requires
less cement, and with good aggregate gives a stronger concrete.
Porous substances make the best aggregates, as the mortar does not
stick well to hard, smooth surfaces. Broken stone is the most com-
mon aggregate. It is usual to require that the stone shall be broken
in pieces so as to pass, any way, through a 2-inch ring. The propor-
tion of matrix should slightly exceed the voids in the aggregate.
The proportion of voids may be determined by experiment in
•either of the following ways: 1. Determine the specific gravity of
the solid aggregate, and from that the weight of a unit of volume
of the solid. Weigh a unit of volume of the loose material. The
difference between these weights divided by the first gives the pro-
portion of voids. 2. Wet the loose aggregate thoroughly; fill a
vessel of known capacity with it; and then pour in all the water the
vessel will contain. Measure the volume of water required, and
divide this by the volume of the vessel; the quotient represents the
proportion of voids.
The voids of broken stone, in which the size and shape of the
pieces are nearly uniform, are about 0. 5 of the mass. If the pieces
.tire not uniform, the voids are about 0.4 of the mass. The voids in
gravel vary, but average about 0. 5 of the mass.
149. PKOPOKTIONS. * The usual proportion for concrete is 1
volume of cement mortar to 4 or 5 volumes of broken stone. 1 or 2
volumes of gravel is sometimes added, which decreases the amount
of mortar required, and also increases the strength of the concrete.
104 CONCRETE. [CHAP. IV.
The following proportions will make a first-class Rosendale con-
crete, and one suitable for use wherever a strong concrete is required.
Of course., if Portland cement were substituted for the Eosendale
the concrete would be still better; but this would rarely be done,
owing to the greater expense. The stone should be broken so as te
pass, any way, through a 2^-inch ring.
2 bbls. (300 Ibs. each) of cement ) = aw cu> ^ of mortar>
4 " (0.5 cu. yd.) of sand 5
0.9 cu. yd. of broken stone.
1 cu. yd. of concrete.
The following concrete is considerably cheaper and only a little
less strong than the preceding:
1 bbl. (300 Ibs.) of cement )
2 bbls. (0.25 cu. yd.) of sand ] = °'28 cu' ^ of mortar'
0.5 cu. yd. of gravel.
0.9 " of broken stone.
1 cu. yd, of concrete.
150. According to Gen. Grillmore, the following is the formula
for the concrete used in the foundations built by the U. S. army
engineers:
1 bbl. (300 Ibs.) of cement ) = ^ bbls of mortar.
3 bbls. of sand )
5 "of broken stone, gravel, broken brick, etc.
0.8 cu. yd. of concrete rammed in place.
The composition of a yard of the above concrete is as follows: —
1.25 bbls. of cement ) = QM Qu ^ Qf mor^
.50 cu. yd. of sand )
.90 " of broken stone.
1.00 cu. yd, of concrete rammed in place.
For a cheaper concrete, Gen. G-illmore recommends the addition
of another barrel or barrel and a half of broken stone to the above
mixture; and also, if a still cheaper concrete is desired, the use of
the following formula:
1 bbl. (300 Ibs.) of Rosendale cement = 3.7 cu. ft. paste.
0.33 " of common lime = 2.5
3.5 to 4 bbls. of loose sand.
5 cu, ft. of mortar.
ART. 2.] PROPORTIONS. 105
The concrete consists of 1 volume of this mortar to 24- volumes
<tf ballast. It is desirable in all cases that the mortar for concrete
should be hydraulic, in order to secure simultaneous induration
throughout the entire mass. If this concrete is laid in large masses
or under water, the lime paste is only equivalent to its bulk of inert
material.
151. In building the Mississippi jetties, blocks of concrete were
used which weighed from 25 to 72 tons each. The materials in a
cubic yard, of the concrete after it had set were as follows:
Portland cement 0.16 cubic yard.
Sand 0.45 "
Clean gravel 0.24
Broken stone 0.81 "
Total materials 1.66 cubic yards.
The concrete after setting was only 60 per cent, of the volume
of the dry materials. The contraction during induration was 4 per
cent.*
152. MIXING. The concrete may be mixed by hand or by
machinery.
In the first method, the cement and sand are mixed as described
in the second paragraph of § 123. A basin is then formed by draw-
in^ the sand and cement to the outer edges of the box, and the
water is poured into it. The sand and cement are then thrown
back upon the water, the whole mass thoroughly mixed with the hoe
or shovel, and then leveled off. The broken stone should be
sprinkled with sufficient water to remove all dust arid thoroughly
wet the entire surface; the amount of water required will vary con-
siderably with the absorptive power of the stone and the tempera-
ture of the air. The wet stone is then to be spread evenly over the
top of the mortar, and the whole mass thoroughly mixed by turning
up with a shovel.
When large t) uantities of concrete are required, it is mixed by
machinery. ODB of the simplest machines for this purpose is a
spiral conveyer running in a trough into which the ingredients are
shoveled. A common kind consists of a box or cylinder to receive
the ingredients, revolving slowly about a diagonal or eccentric axis,
In another form, the sand, cement, and water are mixed by an end-
* Cortheil's Jetties of the Mississippi River.
104 CONCRETE. [CHAP. IV*
The following proportions will make a first-class Eosendale con-
crete, and one suitable for use wherever a strong concrete is required.
Of course,, if Portland cement were substituted for the Kosendate
the concrete would be still better; but this would rarely be done,
owing to the greater expense. The stone should be broken so as tc
pass, any way, through a 2-J-inch ring.
2 bbls. (300 Ibs. each) of cement ) Q 55 d f mortar<
4 " (0.5 cu. yd.) of sand ) J
0.9 cu. yd. of broken stone.
1 cu. yd. of concrete.
The following concrete is considerably cheaper and only a little
less strong than the preceding:
1 bbl. (300 Ibs.) of cement )
2 bbls. (0.25 cu. yd.) of sand [ = °'28 cu' ?d> of mortar'
0.5 cu. yd. of gravel.
0.9 " of broken stone.
1 cu. yd. of concrete.
150. According to Gen. Grillmore, the following is the formula
for the concrete used in the foundations built by the U. S. army
engineers:
1 m (800 Ibs.) of cement ) = ^ ^ Q{ ^^
3 bbls. ot sand )
5 "of broken stone, gravel, broken brick, etc.
0.8 cu. yd. of concrete rammed in place.
The composition of a yard of the above concrete is as follows: —
^ bbls* ,of 7^ i = °-56 ™- yd- of morto-
.50 cu. yd. of sand )
.90 " of broken stone.
1.00 cu. yd. of concrete rammed in place.
For a cheaper concrete, Gen. Gillmore recommends the addition
of another barrel or barrel and a half of broken stone to the above
mixture; and also., if a still cheaper concrete is desired, the use of
the following formula:
1 bbl. (300 Ibs.) of Rosendale cement = 3.7 cu. ft. paste.
0.33 " of common lime =2.5 " "
3.5 to 4 bbls. of loose sand.
5 cu. ft. of mortar.
PROPORTIONS. 105
The concrete consists of 1 volume of this mortar to 2|- volumes
<rf ballast. It is desirable in all cases that the mortar for" concrete
should be hydraulic, in order to secure simultaneous induration
throughout the entire mass. If this concrete is laid in large masses
or under water, the lime paste is only equivalent to its bulk of inert
material.
151. In building the Mississippi jetties, blocks of concrete were
used which weighed from 25 to TZ tons each. The materials in a
cubic yard of the concrete after it had set were as follows:
Portland cement 0.16 cubic yard.
Sand 0.45 " "
Clean gravel 0.24 " "
Broken stone 0.81 " **
Total materials 1.66 cubic yards.
The concrete after setting was only 60 per cent, of the volume
of the dry materials. The contraction during induration was 4 per
cent.*
152. MIXING. The concrete may be mixed by hand or by
machinery.
In the first method, the cement and sand are mixed as described
in the second paragraph of § 123. A basin is then formed by draw-
ing the sand and cement to the outer edges of the box, and the
water is poured into it. The sand and cement are then thrown
back upon the water, the whole mass thoroughly mixed with the hoe
or shovel, and then leveled off. The broken stone should be
sprinkled with sufficient water to remove all dust arid thoroughly
wet the entire surface; the amount of water required will vary con-
siderably with the absorptive power of the stone and the tempera-
ture of the air. The wet stone is then to be spread evenly over the
top of the mortar, and the whole mass thoroughly mixed by turning
up with a shovel.
When large <q tiantities of -concrete are required, it is mixed by
machinery. ODO of the simplest machines for this purpose is a
spiral conveyer running in a trough into which the ingredients are
shoveled. A common kind consists of a box or cylinder to receive
the ingredients, revolving slowly about a diagonal or eccentric axis.
In another form, the sand, cement, and water are mixed by an end- ^
* Cortheil's Jetties of the Mississippi River.
104 CONCRETE. [CHAP. IV,
The following proportions will make a first-class Rosen dale con-
crete, and one suitable for use wherever a strong concrete is required.
Of course, if Portland cement were substituted for the Eosendale
the concrete would be still better; but this would rarely be done.,
owing to the greater expense. The stone should be broken so as to-
pass, any way, through a 2-2-inch ring.
2 bbls. (300 Ibs. each) of cement ) 0 5g cu d of mortar_
4 " (0.5 cu. yd.) of sand 5
0.9 cu. yd. of broken stone.
1 cu. yd. of concrete.
The following concrete is considerably cheaper and only a little
less strong than the preceding:
1 bbl. (300 Ibs.) of cement ) A ^
2 bbls. (0.25 cu. yd.) of sand \ = °'28 cu« **• of mortar'
0.5 cu. yd. of gravel.
0.9 " of broken stone.
1 cu. yd. of concrete.
150. According to Gen. G-illmore, the following is the formula
for the concrete used in the foundations built by the U. S. army
engineers:
1 bbl. (300 Ibs ) of cement ) = ^ bw mortar
8 bbls. ot sand J
5 "of broken stone, gravel, broken brick, etc.
0.8 cu. yd. of concrete rammed in place.
The composition of a yard of the above concrete is as follows: —
1.25 bbls. of cement ) = fl g6 cu Qf ^^
.50 cu. yd. of sand )
.90 " of broken stone.
1.00 cu. yd. of concrete rammed in place.
For a cheaper concrete, Gen. Gillmore recommends the addition
of another barrel or barrel and a half of broken stone to the above
mixture; and also, if a still cheaper concrete is desired, the use of
the following formula:
i bbl. (300 Ibs.) of Rosendale cement = 3.7 cu. ft. paste.
0.83 " of common lime = 2.5
3.5 to 4 bbls. of loose sand.
5 cu. ft. of mortar.
. 2.] PBOPORTIONS.
The concrete consists of 1 volume of this mortar to 2£ volumes
erf ballast. It is desirable in all cases that the mortar for" concrete
should be hydraulic, in order to secure simultaneous induration
throughout the entire mass. If this concrete is laid in large masses
or under water, the lime paste is only equivalent to its bulk of inert
material.
151. In building the Mississippi jetties, blocks of concrete were
used which weighed from 25 to 72 tons each. The materials in a
cubic yard of the concrete after it had set were as follows:
Portland cement 0.16 cubic yard.
Sand 0.45 " "
Clean gravel 0.24 " ' '
Broken stone 0.81 " "
Total materials 1.66 cubic yards.
The concrete after setting was only 60 per cent, of the volume
of the dry materials. The contraction during induration was 4 per
cent.*
152. MIXING-. The concrete may be mixed by hand or by
machinery.
In the first method, the cement and sand are mixed as described
in the second paragraph of § 123. A basin is then formed by draw-
ing the sand and cement to the outer edges of the box, and the
water is poured into it. The sand and cement are then thrown
back upon the water, the whole mass thoroughly mixed with the hoe
or shovel, and then leveled off. The broken stone should be
sprinkled with sufficient water to remove all dust arid thoroughly
wet the entire surface; the amount of water required will vary con-
siderably with the absorptive power of the stone and the tempera-
ture of the air. The wet stone is then to be spread evenly over the
top of the mortar, and the whole mass thoroughly mixed by turning
up with a shovel.
When large 'quantities of concrete are required, it is mixed by
machinery. Oi>e of the simplest machines for this purpose is a
spiral conveyer running in a trough into which the ingredients are
shoveled. A common kind consists of a box or cylinder to receive
the ingredients, revolving slowly about a diagonal or eccentric axis.
In another form, the sand, cement, and water are mixed by an end- ^
* CorthelPs Jetties of the Mississippi River.
106 CONCRETE. [CHAP. iv.
less screw working in an inclined cylinder; and the mortar and
stone then are mixed by another similar contrivance. In some oj
the machines the proportions of the ingredients are measured by
the machine itself.
153. LAYING. After mixing, the concrete is conveyed in wheel-
barrows or in buckets swung from, a crane, and compacted in posi-
tion by ramming in layers 6 to 8 inches thick. Concrete should
not be mixed with too much water, but when ready for use should
be quite coherent and capable of standing at a steep slope without
the water running from it; otherwise it will be impossible to com-
pact it by ramming. It should not be plastic and jelly-like under
the rammer, and the ramming should continue only until the water
begins to ooze out on the upper surface. Too severe or long-con-
tinued pounding injures the strength of the concrete by forcing the
broken stone to the bottom of the layer, and by disturbing the in-
cipient set of the cement.
The rammer generally consists of a log of wood with a handle
attached at one end, and is operated by two men.
When one layer is laid on another already partially set, the
entire surface of the latter should be thoroughly wet. When con-
crete is in place, there should be no walking on it for at least 12
hours.
154. Depositing Concrete under Water. In laying concrete
under water, an essential requisite is that the materials shall not fall
from any height, but be deposited in the allotted place in a compact
mass ; otherwise the cement will be separated from the other ingre-
dients and the strength of the work be seriously impaired. If the
concrete is allowed to fall through the water, its ingredients will be
deposited in a series, the heaviest — the stone — at the bottom and
the lightest — the cement — at the top, a fall of even a few feet caus-
ing an appreciable separation. Of course concrete should not be
used in running water, as the cement would be washed out.
A common method of depositing concrete under water is to
place it in a V-shaped box of wood or plate-iron, which is lowered
to the bottom by a crane. The box is so constructed that, on reach-
ing the "bottom, a pin may be drawn out by a string reaching to
the surface, thus permitting one of the sloping sides to swing open
^iind allowing the concrete to fall out. The box is then raised, to tye
refilled. It usually has a lid. Concrete under water should not be
ART. 2.] LAYING. 107
rammed; but, if necessary, may be leveled by a rake or other suit-
able tool immediately after being deposited.
A long box or tube, called a tremie, is also sometimes used. It
-consists of a tube open at top and bottom, built in detachable
sections so that the length may be adjusted to the depth of water.
The tube is suspended from a crane, or movable frame running on a
track, by which it is moved about as the work progresses. The up-
per end is hopper-shaped, and is kept above the water ; the lower
end rests against the bottom. The tremie is filled in the beginning
by placing the lower end in a box with a movable bottom, filling the
tube, lowering all to the bottom, and then detaching the bottom of
the box. The tube is kept full of concrete, as the mass issues from
the bottom more being thrown in at the top.
Concrete has also been successfully deposited under water by
•enclosing it in paper bags, and lowering or sliding them down a
chute into place. The bags get wet and the pressure of the con-
crete soon bursts them, thus allowing the concrete to unite into a
solid mass. Concrete is also sometimes deposited under water by
enclosing it in open-cloth bags, the cement oozing through the
meshes sufficiently to unite the whole into a single mass.
When concrete is deposited in water, a pulpy gelatinous fluid is
washed from the cement and rises to the surface. This causes the
water to assume a milky hue ; hence the term laitance, which French
engineers apply to this substance. It is more abundant in salt water
than in fresh water. It sets very slowly, and sometimes scarcely at
all, and its interposition between the layers of concrete forms strata
of separation. The proportion of laitance is greatly diminished by
using large immersing boxes, or a tremie, or paper or cloth bags.
155. STRENGTH OF CONCRETE. The strength of concrete de-
pends upon the kind and amount of cement, and upon the kind,
size, and strength of the ballast. It is clear that the mortar will
adhere to broken stone better than to pebbles, and that therefore
concrete containing the former is stronger than that containing the
latter. It is also clear that if the sizes of the individual pieces of
the ballast are so adjusted that the smaller fit into the interstices of
the larger,, successively, then the cementing material will act to the
best advantage and consequently the concrete will be stronger.
Ramming the concrete after it is in place brings the pieces of ballast
into closer contact, and consequently makes it stronger. If the bond
108
CONCRETE.
[CHAP. IY,
is equally good, the larger the pieces of ballast the better. The
strength of concrete also depends somewhat upon the strength of
the ballast; but since the strength of the concrete depends almost
entirely upon the adhesion of the mortar to the ballast, the strength
of the latter is not an important element. But few experiments
have been made to determine the strength of concrete; and the
meager results are very discordant, owing, doubtless, to the varying
conditions of the experiments.
156. Transverse Strength. Fig. 8 shows the results of all the
experiments that could be found which were definite or without
internal evidences of unreliability. The data represented by the
i ransverse
of Concrete.
Composed, of
andPe&bles
i7i the
Proportc*
6 r r ? /o // /z /3 w /j ' /6 // *
of&and and Pebbles to / Volume of Cement.
^
FIG. 8.— DIAGRAM SHOWING THE TRANSVERSE STRENGTH OF CONCRETE.
three lines marked Portland were computed from the results of fifty-
five experiments made at Boulogne-sur-Mer by Voisin, published in
Annales des Fonts et Chaussees for 1858. The mortar was composed
of natural Portland cement from Boulogne-sur-Mer, and sand, the
proportions varying from 1 to 1 to 1 to 6. The ballast consisted of
pebbles. Other experiments seem to show that Boulogne cement is
a little stronger than the average of Portland cement; therefore
the results were decreased 10 per cent, before being plotted. The
values, up to a proportion of 1 cement to 2 diluting material, were
determined by experiments upon ordinary mortars. The diagram
agrees fairly well with the results of twelve experiments by Gen,
ABT. 2.] STRENGTH. 109
Gillmore, as given in his treatise on "Coignet Beton and other
Artificial Stones."
The line marked Eosendale was interpolated, and represents the
probable strength of concrete composed of Eosendale cement, sand,
.and pebbles in the proportion shown. The three points marked x
indicate the strength of concrete 6 months old, composed of Port-
land cement, sand, and pebbles 1 inch or less in diameter; and the
point marked * indicates the strength of Eosendale concrete under
the same conditions.! Each of these points represents a single
•experiment.
157. Compressive Strength. Trantwine saysj that cubes of
Portland cement, sand, and broken stone, " well made and rammed,
•should, either in air or in water, require to crush them at different
ages not less than about as follows :
Age in months 1 3 6 9 12
Tons per sq. ft 15 40 65 85 100
Under favorable conditions of materials, workmanship, and weather,
the strengths may be from 50 to 100 per cent, greater."
The compressive strength of 6-inch cubes of concrete, exposed to
the air for six months, as determined in connection with the construc-
tion of the St. Louis Bridge, was as follows : § "With the proportions
of 1 part cement (Akron and Louisville), 1 part sand, and 4 parts
broken limestone, the mean compressive resistance from 9 trials was
1,200 Ibs. per sq. in. (85 tons per sq. ft.); and with the proportions
of 1, 2, 4, respectively, the average resistance from 12 trials was 940
Ibs. per sq. in. (70 tons per sq. ft.).
Tests with the United States testing-machine || at Watertown,
Mass., between steel, gave an average of 1,544 Ibs. per sq. in. (110
tons per sq. ft.) for 4-inch to 16-inch cubes of concrete, 46 months
old, composed of 1 part Eosendale cement paste, 1£ parts sand, and 6
parts broken stone. Under the same conditions, concrete composed
of 1 Eosendale cement paste, 3 sand, and 6 broken stone stood 1,021
Ibs. per sq. in. (73 tons per sq. ft.). Another sample of cement
gave 1,078 Ibs. per sq. in. (77 tons per sq. ft. ) for concrete, 22 months
t Eliot C. Clarke, in Trans. Am. Soc. of C. E., vol. xiv. p. 166.
J Engineer's Pocket-book, p. 679.
§ History St. Louis Bridge, p. 328.
|| Report for 1884,— Senate Ex. Doc. No. 35, 49th Congress, 1st Session,— pp. 166,
190, 198.
110 CONCRETE. [CHAP. iv.
old, composed of 1 part cement paste, 3 sand, 2 gravel, and 4 broken
stone. Ten experiments with a single sample of Portland cement
gave 3,067 Ibs. per sq. in. (219 tons per sq. ft.) for concrete composed
of 1 part cement paste, 3 sand, and 6 broken stone. The concrete
under the Washington Monument, composed of 1 Portland, 2 sand,
3 pebbles, and 4 broken stone, when 0 months old stood ^,000 Ik-,
per sq. in. (144 tons per sq. ft.).
Experiments made in connection with the construction of the
Vyrnwy dam — built to impound water for the supply of Liverpool,
England — gave an average strength from six experiments, for cubes-
of 1 to 2 Portland cement mortar* from 32 to 37 months old,
crushed between pine cushions -J- inch thick, of 4,428 Ibs. per sq. in.
(284.7 tons per sq. ft.); and cubes of concrete composed of gravel
and sufficient 1 to 2 Portland cement mortar to fill the interstices gave-
an average strength, for two cubes 35 and 36 months old, of 3,497
Ibs. per sq. in. (224.9 tons per sq. ft.), and for two cubes 12 and
15 months old, of 4,583 Ibs. per sq. in. (294.7 Ibs. per sq. ft.). The
blocks were made from the concrete actually used in the work, and
were moulded by ordinary workmen without supervision, with the
intention of securing blocks representative of the concrete as laid
in the work. For cubes of the concrete tested between "mill-
boards" (straw-boards), the same series of experiments gave results
as follows : f
AGE OF THE BLOCKS, No. OF Ex- MEAN CRUSHING STRENGTH,
months. PERIMENTS. Ibs. per sq. in. tons per sq. ft.
32-36 3 2,365 170.4
20—30 6 2, 278 1 64. 0
5—8 2 1,742 125.5
1— 2i 7. 1,477 106.4
158. COST. The cost of concrete varies greatly, depending upon
the kind of mortar — whether lime or cement, — upon the richness of
the mortar, upon the proportion of ballast to mortar, upon the cost
of the ingredients and of the labor, etc.
The following is the analysis of the composition and cost of the
concrete employed for laying the foundations of the sea-wall at
Lo veil's Island, Boston Harbor :J
* Tensile strength tested neat, after being 6 days in air and 7 days in water = 633-
Ibs. per sq. in.
t Compiled from Deacon's Report on the Vyrnwy Masonry Dam.
J Compiled from Gillmore's Limes, Hydraulic Cements, and Mortars, p. 247.
AET. 2.] COST OF CONCRETE. Ill
Cement 0.83 bbl. @ $1 54 = $1 2(5
Sand 0.25 cu. yd. @, 70 = 17
Gravel 0.90 cu. yd. © 27 = 24
Total materials 1.27 cu. yds = $1 67
Labor, making mortar 0.00 clay @. $1 20 = $0 08
making concrete 0.11 day @, 1 20 = 13
" transporting concrete 0.06 day @. 1 20 = 08
' ' packing concrete 0.03 day @ 1 20 = 04
Total labor 0.26 day =$033
Tools, implements, etc $0 11
Total cost 1 cu. yd. of concrete, in place 2 11
The proportions for this concrete were 1 cement,, 3 sand, and 4 gravel.
It was unusually cheap, owing partly to the use of pebbles instead
of broken stone. The latter would have cost probably 4 to 6 times
as much as the gravel. The amount of labor required was also un-
usually small, this item alone being frequently 6 to 8 times as much
as in this case.
The following is the analysis* of the cost of nearly 30,000 yards
of concrete as laid for the foundations of a blast-furnace plant near
Troy, ]NT. Y., in 1886. The conditions were unusually favorable
for cheap work.
Cement 1.23 bbls. @ $1 00 = $1 23
Sand 0.10 cu. yd. @ 0 SO = 03
Gravel 0.36 cu. yd. @. 0 30 = 11
Broken Stone 0.74 cu. yd. @ 1 41 = 104
Total materials 1.28 cu. yds = $ 2 41
Labor, handling cement 0.02 day @ $1 00 = $0 02
" \inloadiugstone 0.14 day @, 1 00 = 14
" mixing 0.85 day @ 1 00 = 85
" superintendence 0.01 day @ 9 61 = 10
Total labor 1.02 days = $1 11
Total cost of a cubic yard of concrete, in place $3 52
* Trans. Am. Soc. of (X E., vol. xv. p. 875.
iBTIIKJIAL SOTS. ^
in bridge pier, and
$0 45
Quarrying stone . • • » 50
Transporting stone .. . . . 35
Breaking stone -j_ 80
Cement @ *1.85 per bbl 1Q
Sand, cost of digging ' y ' * •' ' ' * Q5
Water 75
Labor, mixing and laying. - • '• ' og
Incidentals * ' - —
Total cost per cubic yard, in place ** °5
For additional data concerning the cost of concrete, see §§ 233-34.
ART. 3. AETIFICIAL STONE.
ART. 3.] PORTLAND STONE. 113
160. BETON-COIGNET. As made "by its inventor, Coignet, of
Paris, its usual ingredients are : Portland cement, siliceous hydrau-
lic lime (like that obtained at Teil, France), and clean sand, mixed
together with a little fresh water. The proportions are varied con-
siderably for different kinds of work. The dry ingredients are first
moistened very sligh tly with clean water, then thoroughly mixed by
hand, and again mixed in a mill. Moulds are then filled with the
mixture, which is compacted by ramming.
The peculiarities of this stone result from the small quantity of
water used in its manufacture and the thoroughness with which the
mixing is done. It is nothing more than hydraulic concrete, from
which the coarse fragments have been omitted, and upon which
have been conferred all the advantages to be derived from a judi-
cious choice in the quality and proportions of the ingredients, 'and
from their thorough manipulation. It sets quickly, is very strong,
.•and is the best beton or concrete. It may be made into blocks to
be used as cut stone, or it may be built up into immense masses of
.any desired shape by moulding the different parts in place. It is
used to a considerable extent in constructing the walls of houses,
•and in repairing masonry,* — as bridge piers, culverts, etc. It is
used very extensively in France.
In this country a mixture of Rosendale cement and sand is fre-
quently called B6ton-Coignet.
161. PORTLAND STONE. This is a mixture of Portland cement
and sand, or sand and gravel, compacted into form by tamping.
When properly"rnade, it possesses the essential requisites of strength
and hardness in a degree proportionate to the value of the cement
employed. The proportions of 1 measure of dry cement to 2 or 2£
measures of sand will answer for most purposes. The manipulation
should be prolonged and thorough to insure the production of a
homogeneous stone. It is much used for flagging, for which pur-
pose the surface layer, to the thickness of about half an inch, may
advantageously be composed of 1 measure of cement to 1J or 1-J- of
sand, and the coarse gravel should be omitted.
162. McMuBTRiE STONE. This stone, the process for making
which is patented, consists essentially of the Portland stone de-
scribed above, in the pores of which are formed compounds of
* Trans. Am. Soc. of C. E., vol. x. pp. 291-308.
and a
soap
bythe double decomposition of alum
re 96) These compounds are in-
carbonic acid of the air,
of the stone and some-
what to its ultimate strength .^ ^ of abBOrbing
The peculiar ment this stone x ^ ^ ^ mo]p_
Water is decreased by the n*. of the freely.-porous.
tars and most of the artoc ul rto mb ^ ^^ best port.
ffiortar from 50 to 60 per cent- o ^ jw , disintegrat,
land from 10 to *0 per cent. _ ^^^ iter also dissolves
rapidlyunder theac^onot f^ ^^ ^ rf ^^ tl
the salts of magnet l^e' T*' Vj Jn evaporating leaves a white
i-al^^^^C^^^reB L appearance of the
efflorescence on the surface, whio n 3 ^^ we m dlg_
TO11. Eor these reasons ^^J^^ power of the Me-
repute for architectural purpo s The ab J t(> ^ ^
Murtrie stone is about twice that ol g ^ Q£ the
the best limestones, and about one tenj* w ^^
It
Portland cement, to which g,m
usedby the inventor was 1
moistene'd with an
^ ^^
° of shellac of sufficient,
foot of stone.
did
by
3.] SOEEL STOKE. 115
are mixed in the proportion of a gallon of the latter to a
el of the former and rammed into moulds, or it may be
** oiled into slabs for footpaths, etc. At this stage of the process
tlie blocks or slabs may be easily cut into any desired form. They
itro then immersed, under pressure, in a hot solution of chloride o;
cutlcium, after which they are thoroughly drenched with cold water
' -for a longer or shorter period, according to their size — to wash
out the chloride of sodium formed during the operation. In
-15 21 gland grindstones are frequently made by this process.
165. SOREL STONE. Some years ago, M. Sorel, a French chemist,
*1 iwcovered that the oxychloride of magnesium possessed hydraulic
c MI orgy in a remarkable degree. This cement is the basis of the
Morel stone. It is formed by adding a solution of chloride of mag-
tiosixim, of the proper strength and in the proper proportions, to
thc3 oxide of. magnesium. The strength of this stone, as well as its
Imrdncss, exceeds that of any other artificial stone yet produced,
ivntl may, when desirable, be made equal to that of the natural
wtone which furnishes the powder or sand used in its fabrication.
rriic process is patented, and is used mainly in making emery-wheels.
"Hy incorporating large pebbles and cobble-stones in the mixture
the stone can be made quite cheaply, and is therefore suitable for
foundations and plain massive walls.
CHAPTER V.
QUARRYING.
166. THIS is so large a subject that it cannot be more than en-
tered upon here ; for greater detail, see treatises on Quarrying, Rock-
blasting, and Tunneling.
167. SOUKCES OF BUILDING- STONES. The bowlders, which are
scattered promiscuously over the surface of the ground and also
frequently buried in it, furnish an excellent building stone for massive
structures where strength is essential. They are usually of tough
.granite or of a slaty structure, and are difficult to work. Sometimes
they have a cleavage plane or rift, along which they may be split.
They can be broken into irregular pieces by building a lire about
them, and drenching them while hot with water, or they may be
broken by explosives.
Of course by far the greater quantity of stone is taken directly
from quarries. All building-stone deposits have usually a certain
amount of covering, consisting either of a portion of the same de-
posit, which has been disintegrated by atmospheric influences, or of a
later deposit. This covering is called the "cap-rock" or "strip-
ping." In opening the quarry, the solid portions of cap-rock arc
broken up by blasting, and the whole is carted out of the way. After
a sufficient space is stripped, the next step necessary, when the quarry
rock does not stand out in cliffs, is to excavate a narrow space on
one side for a quarry face, either by blasting or by some of the
methods to be described presently.
168. METHODS OF QTTAKKYING. After a considerable area has
thus been laid bare, the stone is quarried in one of three ways.
169. I. By Hand Tools. When the stone is thin-bedded, it may
be quarried by hand-tools alone. The principal tools are pick, crow-
bar, drill, hammer, wedge, and plug and feathers. The layers are
forced apart by the crow-bar or wedges. The flat pieces are broken
up with the hammer or by drilling holes for the plug and feathers.
116
QUARRYING BY EXPLOSIVES. 117
The plug is a narrow wedge with plane faces ; the feathers are
wedges flat on one side and rounded on the other (see Fig. 25).
"When a plug is placed between two feathers, the three will slip into
a cylindrical hole ; if the plug is then driven, it exerts a great force.
If these plugs and feathers are placed a few inches apart in a row.,
and all driven at the same time, the stone will be cracked along the
line of the holes, even though it be comparatively thick.
The drill used to cut the holes for the plug and feathers is a bar
of steel furnished with a wide edge sharpened to a blunt angle and
hardened. It is operated by one man, who holds the drill with one
hand and drives it with a hammer in the other, rotating the drill
between blows. The holes are usually from f to f of an inch in
diameter.
Sandstones and limestones occurring in layers thin enough to
be quarried as above are usually of inferior quality, suitable only
for slope walls, paving, riprap, concrete, etc.
170. II. By Explosives. Generally, the cheapest method of
quarrying small blocks is by the use of explosives. However, ex-
plosives are used mainly for detaching large blocks, which are after-
wards worked up by means of wedges. In this method of quarry-
ing, drill-holes are put down to the depth to which the rock is to
be split, and the requisite amount of powder or other explosive put
in, covered with sand, and fired by a fuse. Sometimes numerous
charges in a line of drill-holes are fired simultaneously by means of
electricity.
Quick-acting explosives, like dynamite, have a tendency to shatter
the stone and break it in many directions, the texture being affected
by the sudden explosion in the same manner as by the blow of a
hammer. Coarse gunpowder is generally preferred for quarrying
stone. Light charges of powder lightly covered with sand are better
than heavy charges tightly tamped ; * and experience goes to show
that better work is done by repeated light blasts in the same hole,
than by a single heavy blast. By means of light charges often re-
peated, a mass of rock may be detached without being broken up,
which would be badly shattered by a single charge strong enough to
detach it.
In each locality the structure of the rock must be carefully
* For an. article showing that an air-space should be left between the* explosive
and the tamping, see Engineering Ncim, vol. xviii. p. 332.
118 QUARRYING. [CHAP. V.
studied with, a view to take advantage of the cleavage planes and
natural joints. For quarrying each class of rocks there is a charac-
teristic method employed, which is, however, varied in detail in
different quarries. The minor details of quarry methods are as
various as the differences existing in the textures, structures,
and modes of occurrence of the rocks quarried. Much depends
upon how the blast is made. The direction in which the rock is
most liable to break depends upon the structure of the rock and
the shape of the drill-hole. Even such an apparently unimportant
matter as the form of the bottom of the drill-hole into which the
explosive is put has a very marked effect. If bored with a hand-
drill, the hole is generally triangular at the bottom, and a blast in
such a hole will break the rock in three directions. In some quar-
ries the lines of fracture are made to follow predetermined directions
by putting the charge of powder into canisters of special forms.*
171. Drills. The holes are bored by jumpers, churn-drills,, or
machine-drills. The first is a drill similar to the one used for drill-
ing holes for plugs and feathers (§ 169), except that it is larger and
longer. It is usually held by one man, who rotates it between the
alternating blows from hammers in the hands of two other men.
Churn-drills are long, heavy drills, usually 6 to 8 feet in length.
They are raised by the workmen, let fall, caught on the rebound,
raised and rotated a little, and then dropped again, thus cutting
a hole without being driven by the hammer. They are more eco-
nomical than jumpers, especially for deep holes, as they cut faster
and make larger holes than hand-drills.
* 172. Machine rock-drills bore much more rapidly than hand-
drills, and also more economically, provided the work is of sufficient
magnitude to justify the preliminary outlay. They drill in any
direction, and can often be used in boring holes so located that they
could not be bored by hand. They are worked either by steam
directly, or by air compressed by steam or water-power and stored
in a tank called a receiver and thence led to the drills through iron
pipes.
A variety of rock-drilling machines has been invented, f but
they can be grouped in two classes, viz., percussion-drills and rotat-
ing drills. The method of action of the percussion-drill is the same
* See Report on Quarry Industry in Vol. X. of the 10th Census, pp. 33, 34.
t For a full account of the more important ones, see Drinker's " Tunneling."
LSG BY EXPLOSIVES. 119
as that of the churn-drill already described. The usual form is
that of a cylinder,, in which a piston is moved by steam or com-
pressed air, and the drill is attached to this piston so as to make a
stroke with every complete movement of the piston. An automatic
device causes it to rotate slightly at each stroke.
173. In the rotating drills, the drill-rod is a long tube, revolving
.about its axis. The end of the tube — hardened so as to form an
annular cutting edge — is kept in contact with the rock, and by its
rotation cuts in it a cylindrical hole, generally with a solid core in
the center. The drill- rod is fed forward, or into the hole, as the
drilling proceeds. The dvbrix is removed from the hole by a con-
stant stream of water which is forced to the bottom of the hole
through the hollow drill-rod, and which carries the debris up
through the narrow space between the outside of the drill-rod and
the sides of the hole.
The diamond drill is the only form of rotary rock-drill exten-
sively used in this country. The tube has a head at its lower end,
in which are set a number oLf carbons or black diamonds. The
diamonds usually project slightly beyond the circumference of the
head, which is perforated to permit the ingress and egress of the
water used in removing the debris from the hole and at the same
time prevent the head from binding in the hole. When it is desir-
able to know the precise nature and stratification of the rock pene-
trated, the cutting points are so arranged as to cut an annular groove
in the rock, leaving a solid core, which is broken off and lifted out
whenever the head is brought up. Where it is not desired to pre-
serve the core intact, a solid, boring-bit is used instead of the core-
bit. They are made of any size up to 15 inches in diameter.
174. Explosives.* The principal explosives are gunpowder,
nitro-glycerine, and dynamite. Only a coarse-grained and cheap
variety of the first is used in quarrying, the others being too sudden
iind too strong in their action.
The pressure exerted by gunpowder when fired in a confined
space depends upon the relative weight and quality of powder used,
iind upon the space occupied by the gases evolved. The absolute
force of gunpowder, the force which it exerts when it exactly fills
the space in which it is confined, has never been satisfactorily asoer-
* For a full account of all the various explosives, sec Drinker's "Tunneling,'7
&nd Drinker's " Modern Explosives."
120 QUABRYIHTGL [CHAP. Y,
tained. It has been variously estimated at from 15,000 to 1,500,000
pounds per square inch. Experiments by Gen. Rodman show that
for the powder used in gunnery the absolute force of explosion is
at least 200,000 pounds per square inch. " In ordinary quarrying.
a cubic yard of solid rock in place (or about 1.9 cubic yards piled
up after being quarried) requires from £ to f pound of powder.
In very refractory rock, lying badly for quarrying, a solid yard may
require from 1 to 2 pounds. In some of the most successful great
blasts for [the Holyhead Breakwater, Wales, (where several thou-
sands of pounds of powder were exploded, usually by galvanism, at
a single shot,) [from 2 to 4 cubic yards (solid) were loosened per
pound of powder ; but in many instances not more than 1 to 1-}
yards. Tunnels and shafts {require 2 to 6 pounds per solid yard,
usually 3 to 5 pounds. Soft, partially decomposed rock frequently
requires more than harder ones." *
The explosion of the powder splits and loosens a mass of rock
whose volume is approximately proportional to the cube of the line
of least resistance, — that is, of the shortest distance from the charge
to the surface of the rock, — and may be roughly estimated at twice
that cube ; but this proportion varies much in different cases. The
ordinary rule for the weight of powder in small blasts is
POWDER, in pounds, = (LIKE OF RESISTANCE, in feet,}* -~ 32.
Powder is sold in kegs of 25 Ibs., costing about $2.00 to $2.25
per keg, exclusive of freight, — which is very high, owing to the risk..
175. Most of the explosives which of late years have been tak-
ing the place of gunpowder consist of a powdered substance, partly
saturated with nitro-glycerine — a fluid produced by mixing glycerine
with nitric and sulphuric acids. Nitro-glycerine, and the powders-
containing it, are always exploded by means of sharp percussion,
which is applied by means of a cap and fuse. The cap is a hollow
copper cylinder, about J inch in diameter and an inch or two in
length, containing a cement composed of fulminate of mercury and
some inert substance. The cap is called single-force, double-force,,
etc., according to the amount of explosive it contains.
The principal advantages of nitro-glycerine as an explosive con-
sist (I) in its instantaneous development of force, due to the fact
that, pound for pound, it produces at least three and a half times.
* Trautwine's Engineer's Pocket-book.
QUARRYING BY EXPLOSIVES. 121
as much gas, and twice as much heat, as gunpowder ; and (2) in its
high specific gravity, which permits the use of small drill-holes.
Nitro -glycerine is rarely used in the liquid state in 'ordinary
quarrying or blasting, owing to the liability of explosion through
accidental percussion, and owing to its liability to leakage. It ex-
plodes so suddenly that very little tamping is required, the mere
.weight of moist sand, earth, or water being sufficient. This fact,
and the additional one that nitro-glycerine is unaffected by i miner-
sion in water and is heavier than water, render it particularly suit-
able for sub-aqueous work, or for holes containing water. If the
rock is seamy, the nitro-glycerine must be confined in water-tight
casings. Such casings, however, necessarily leave some spaces be-
tween the rock and the explosive, which diminishes the effect of the
latter. The liquid condition of nitro-glycerine is useful in causing
it to fill the drill-hole completely, so that there are no empty spaces
in it to waste the force of the explosion. On the other hand, the
liquid form is a disadvantage, because when thus used in seamy
rock without a containing vessel portions of the nitro-glycerine leak
away and remain un exploded and unsuspected, and may cause acci-
dental explosion at a future time.
The price of nitro-glycerine is from 50 to 60 cents per quart.
176. Dynamite is. the name given to any explosive which con-
tains nitro-glycerine mixed with a granular absorbent. If the
absorbent is inert, the mixture is called true dynamite; if the
absorbent itself contains. explosive substances, the mixture is called
false dynamite. The absorbent, by its granular and compressible
condition, acts as a cushion to the nitro-glycerine, and protects it
from percussion and from the consequent danger of explosion, but
does not diminish its power when exploded. Nitro-glycerine
undergoes no change in composition by being absorbed ; and it
then freezes, burns, explodes, etc., under the same conditions as
to pressure, temperature, etc., as when in the liquid form. The
cushioning effect of the absorbent merely renders it more difficult
to bring about sufficient percussive pressure to cause explosion.
The absorption of the nitro-glycerine in dynamite renders the lat-
ter available in horizontal holes or in holes drilled upward. True
dynamite loses only a very small percentage of its explosive power
when saturated with water, but is then much more difficult to ex-
plode.
120 QUARRYING. [CHAP. V,
tained. It has been variously estimated at from 15,000 to 1,500,000
pounds per square inch. Experiments by Gen. Kodman show that
for the powder used in gunnery the absolute force of explosion is
at least 200,000 pounds per square inch. " In ordinary quarrying,
a cubic yard of solid rock in place (or about 1.9 cubic yards piled
up after being quarried) requires from J to f pound of powder.
In very refractory rock, lying badly for quarrying, a solid yard may
require from 1 to 2 pounds. In some of the most successful great
blasts for [the Holyhead Breakwater, Wales, (where several thou-
sands of pounds of powder were exploded, usually by galvanism, at
a single shot,) [from 2 to 4 cubic yards (solid) were loosened per
pound of powder ; but in many instances not more than 1 to 14-
yards. Tunnels and shafts {require 2 to 6 pounds per solid yard,
usually 3 to 5 pounds. Soft, partially decomposed rock frequently
requires more than harder ones." *
The explosion of the powder splits and loosens a mass of rock
whose volume is approximately proportional to the cube of the line
of least resistance, — that is, of the shortest distance from the charge
to the surface of the rock, — and may be roughly estimated at twice
that cube ; but this proportion varies much in different cases. The
ordinary rule for the weight of powder in small blasts is
POWDER, in pounds, = (LINE OF KESISTAKCE, in feet ,y -~ 32.
Powder is sold in kegs of 25 Ibs., costing about $2.00 to $2.25-
per keg, exclusive of freight, — which is very high, owing to the risk.
175. Most of the explosives which of late years have been tak-
ing the place of gunpowder consist of a powdered substance, partly
saturated with nitro-glycerine — a fluid produced by mixing glycerine
with nitric and sulphuric acids. Mtro-glycerine, and the powders,
containing it, are always exploded by means of sharp percussion,
which is applied by means of a cap and fuse. The cap is a hollow
copper cylinder, about J inch in diameter and an inch or two in
length, containing a cement composed of fulminate of mercury and
some inert substance. The cap is called single-force, double-force,,
etc., according to the amount of explosive it contains.
The principal advantages of nitro-glycerine as an explosive con-
sist (I) in its instantaneous development of force, due to the fact
that, pound for pound, it produces at least three and a half times
* Trautwine's Engineer's Pocket-book.
QUARRYING- BY EXPLOSIVES. 121
as much gas, and twice as much heat, as gunpowder ; and (2) in its
high specific gravity, which permits the use of small drill-holes.
Nitro -glycerine is rarely used in the liquid state in 'ordinary
quarrying or blasting, owing to the liability of explosion through
accidental percussion, and owing to its liability to leakage. It ex-
plodes so suddenly that very little tamping is required, the mere
.weight of moist sand, earth, or water being sufficient. This fact,
and the additional one that nitroglycerine is unaffected by immer-
sion in water and is heavier than water, render it particularly suit-
able for sub-aqueous work, or for holes containing water. If the
rock is seamy, the nitroglycerine must be confined in water-tight
casings. Such casings, however, necessarily leave some spaces be-
tween the rock and the explosive, which diminishes the effect of the
latter. The liquid condition of nitroglycerine is useful in causing
it to fill the drill-hole completely, so that there are no empty spaces
in it to waste the force of the explosion. On the other hand, the
liquid form is a disadvantage, because when thus used in seamy
rock without a containing vessel portions of the nitro-glycerme leak
away and remain unexploded and unsuspected, and may cause acci-
dental explosion at a future time.
The price of nitro-glycerme is from 50 to 60 cents per quart.
176. Dynamite is. the name given to any explosive which con-
tains nitro-glycerine mixed with a granular absorbent. If the
absorbent is inert, the mixture is called true dynamite; if the
absorbent itself contains explosive substances, the mixture is called
false dynamite. The absorbent, by its granular and compressible
condition, acts as a cushion to the nitro-glycerine, and protects it
from percussion and from the consequent danger of explosion, but
does not diminish its power when exploded. Nitro-glycerine
undergoes no change in composition by being absorbed ; and it
then freezes, burns, explodes, etc., under the same conditions as
to pressure, temperature, etc., as when in the liquid form. The
cushioning effect of the absorbent merely renders it more difficult
to bring about sufficient percussive pressure to cause explosion.
The absorption of the nitro-glycerine in dynamite renders the lat-
ter available in horizontal holes or in holes drilled upward. True
dynamite loses only a very small percentage of its explosive power
when saturated with water, but is then much more difficult to ex-
plode.
122 QUARRYING. [CHAP. V.
True dynamites must contain at least 50 per cent, of nitro-
glycerine, otherwise the latter will be too completely cushioned
by the absorbent, and the powder will be too difficult to explode.
False dynamites, on the contrary, may contain as small a percentage
of nitro-glycerme as may be desired, some containing as little as 15
per cent. The added explosive substances in the false dynamites
generally contain large quantities of oxygen, which are liberated
upon explosion, and aid in effecting the complete combustion of
iiny noxious gases arising from the nitre-glycerine. The false are
generally inferior to the true dynamites, since the bulk of the
former is increased in a higher ratio than the power; and as the
cost of the work is largely dependent upon the size of the drill-
holes, there is no economic gain.
Dynamites which contain large percentages of nitro-glycorine
explode with great suddenness, tending to break the rock into
small fragments. They are most useful in blasting very hard rock.
In such rock dynamite containing 75 per cent, of nitro-glycerme
is roughly estimated to have about 6 times the force of an equal
•weight of gunpowder ; but in soft rock or clay its power, at equal
cost, is inferior to that of common gunpowder, because its action
is akin to a sudden blow, rather than to a continued push. For
soft or decomposed rocks, sand, and earth, the lower grades of
dynamite, or those containing a smaller percentage of nitro-glycor-
ine, are more suitable. They explode with less suddenness, and
their tendency is rather to upheave large masses of rock than to
• splinter small masses.
"Judgment must be exercised as to the grade and quantity of
explosive to be used in any given case. Where it is not objection-
able to break the rock into small pieces, or where it is desired to do
so for convenience of removal, the higher shattering grades are use-
ful. Where it is desired to get the rock out in large masses, as in
quarrying, the lower grades are preferable. For very difficult work
in hard rock, and for submarine blasting, the highest grades, con-
taining 70 to 75 per cent, of nitro-glycerine, are used. A small
charge does the same execution as a larger charge of lower grade,
and of course does not require the drilling of so large a hole. In
submarine work their sharp explosion is not deadened by the
water. For general railroad work, ordinary tunneling, mining of
ores, etc., the average grade, containing 40 per cent, of nitro-glycer-
NITRO-GLYCERINB EXPLOSIVES. 123
ine, is used ; for quarrying., 35 per cent; for blasting stumps, trees,
piles, etc., 30 per cent,; for sand and earth, 15 per cent."
177. A great variety of dynamites is made. Each manufacturer
usually makes a number of grades, containing different percentages
of nitre-glycerine, and gives to his powder some fanciful name.
Dynamite is sold in cylindrical, paper-covered cartridges, from £ of
.an inch to 2 inches in diameter, and 6 to 8 inches long, or longer,
which are packed in boxes containing 25 or 50 pounds each. They
are furnished, to order, of any required size. The price per pound
ranges from 15 cents for 15 per cent, nitro-glycerine to 50 cents for
75 per cent, nitro-glycerine.
Table 14 (page 124) gives the names of all the explosives con-
taining nitro-glycerine, with the per cent, in each case. *
178. TTT. By Channeling and Wedging. By channeling is meant
the process of cutting long narrow channels in rock to free the sides
of large blocks of stone. Quite a large number of machines have
been invented for doing this work, all of which make the channels
by one form or the other of the machine drills already described
(see the second paragraph of § 172). The machines are mounted
upon a track on the bed of the quarry, and can be moved forward
as the work progresses. If the rock is in layers, it is only necessary
to cut the channels part way through the layer, when the block can
be detached with wedges, the groove guiding the fracture. If the
rock is not in layers, after the necessary channels have been cut
around the block, it is necessary to under-cut the block in order to
release it. This is accomplished by drilling a series of holes along
the bottom, which process is called "gadding" by quarry-men. The
block is then split from its bed by means of wedges. The method
of channeling and wedging is much employed in quarrying marble,
the massive limestones, and the thick-bedded sandstones. The
method is very economical and expeditious, except in granite and
the hardest sandstones. For illustrations of the two principal chan-
neling machines and also quarries being worked by this method, see
Eeport on the Quarry Industry, pp. 44-52, in Vol. X. of the Tenth
Census of the United States.
* W. C. Foster, in Engineering Nem, vol. xix. p. 254. For a list of all the explo-
sives employed as blasting agents, together with a description of their composition
and references to the literature of each, see Engineering News, vol. xix. pp. 533-34,
an& vol. xx. pp. 8-10.
124
QUARRYING.
[CHAP. T.
TABLE 14.
LIST OF EXPLOSIVES CONTAINING NITRO- GLYCERINE.
NAME OF EXPLOSIVE.
Per cent,
of
Nitro-
glycerine.
NAME OF EXPLOSIVE.
Per cent,
of
Nitro-
glycerine.
j£!tna powder No 1 •
65
Glyxoline
" 2XX...
" " " 2 .
50
40
Hecla powder, No. 1XX. .
Gun Sawdust
75
16 to 20
" " " 3X . .
35
No IX
50
« 4X
25
1
40
" " " 5 .
15
1 2X
35
Amnionia powder. ........
16 to 20
2
30
Asbestos powder
varies
3X
25
Atlas powder A.
75
3
20
3 B4-
60
Hercules powder, No. 1XX
75
B...
50
65
CM-
45
2SSS
55
ct :....:::
40
2SS..
50
D4-
35
as...
45
D^:. :.::::
30
2.. .
40
E4-
25
8S. . .
35
St.:.:::::
20
3....
30
F+
15
4S. . .
25
Brady's dynamite
33
4...
20
Brain's powder
40
Horsley's powder (some
Colonia powder
40
varieties)
20
Dualin (Dittmar's)
50
Judson Giant Powder No 2
40
Dynamite (Nobel's, Kiesel-
Judson powder, FFF
20
guhr dynamite),
FF
15
Old No. 1
75
F .. .
10
Old No. 2
40
RRP
5 to 6
Old No. 3
25
Lithof racteur
52
Electric powder
33
Metalline Nitroleum
varies
Explosive gelatine
93
Mica powder, N o 1 ....
40
Forcite, 2 grades
75, 70
i ,< « « g
52
Fulgurite (solid)
60
Miners' Powder Co Js Dy-
(liquid)
90
namite . ...
33
Gelatine dynamite, A
97.5
Neptune powder
32 7
No. 1..
58
Nitro Tolnol
70
" 2..
Gelatine explosive de
- 38.8
Norrbin & Ohlsson's pow-
der
25 to 50
guerre
89.3
Pantopolite
Gelignite .
56 5
Porifera Metroleum
varies
Giant powder, No. 1
75
LRendrock
33 4
New" 1
50
Sebastin No 1
78
. " 2 extra
45
" 2
68
" 2
40
Selenitic powder , .
varies
" 2c
33
Seranim
" XXX..
27
Vigorite(U. S.)
438
tc M
20
Vitrite, No. 1
Giant powder (Nobel's),
« 2
No. 2
20
Vulcan powder
32.6
CHAPTER VI.
STOKE CUTTING.
AKT. 1. TOOLS.
179. Itf order to describe intelligibly the various methods of
preparing stones for use in masonry, it will be necessary to begin
with a description of the tools used in stone-cutting, as the names
of many kinds of dressed stones are directly derived from those of
the tools used in dressing them.
"With a view to securing uniformity in the nomenclature of
building stones and of stone masonry, a committee of the American
Society of Civil Engineers prepared a classification and recommended
that all specifications should be made in accordance therewith. The
old nomenclature was very unsystematic and objectionable on many
grounds. The new system is good in itself, is recommended by the
most eminent authority, has been quite generally adopted by en-
gineers, and should therefore be strictly adhered to. The following
description of the hand tools used in stone cutting is from the
report of the American Society's committee.*
180. HAND TOOLS. "The Double Face Hammer, Fig. 9, is a
heavy tool weighing from 20
to 30 pounds, used for rough-
ly shaping stones as they
oome from the quarry and
for knocking off projections.
This is used only for the
roughest work.
" The Face Hammer, Fig. 10, has one blunt and one cutting
end, and is used for the same
purpose as the double face
hammer where less weight is
required. The cutting end
is used for roughly squaring
stones, preparatory to the use
of finer tools.
< 3"
FIG. 9.— DOUBLE FACE HAMMER.
Fia. 10.— FACE HAMMER.
* Trans. Am. Soc. of C. E., vol. vi. pp. 297-304.
125
126
STOtfE CUTTOTGL
[CHAP. vi.
"The Cavil, Fig. 11, has one blunt and one pyramidal, or
pointed, end, and weighs from 15 to 20 pounds.
It is used in quarries for roughly shaping stone
for transportation.
The Pick, Fig. 12, somewhat resembles the
FIG. ii.— CAVIL. pic^ used in digging, and is used for rough dress-
ing, mostly on limestone and sandstone. Its length varies from
15 to 24 inches, the thickness
at the eye being about 2
inches.
"The Ax, or Pean Ham-
mer, Fig. 13, has two opposite
cutting edges. It is used for
making drafts around the arris,
or edge, of stones, and in re-
ducing faces, and sometimes
joints, to a level. Its length is about 10 inches, and the cutting
edge about 4 inches. It is used after
the point and before the patent ham-
mer.
"The Tooth Ax, Fig. 14, is like
FIG. 13.—A.X. 9 the ax, except that its cutting edges
are divided into teeth, the number of which varies with the kind
of work required. This tool
is not used in granite and
gneiss cutting.
"The Bush Hammer,
Fig. 15, is a square prism of
steel whose ends are cut into
a number of pyramidal points.
FIG. 14.—TooTH Ax.
The length of the hammer is from 4 to 8 inches, and the cutting
face from 2 to 4 inches square.
The points vary in number and
in size with the work to be done.
One end is sometimes made
with a cutting edge like that of
0
FIG. 15.— BUSH HAMMER.
" The Crandall, Fig. 16, is a malleable-iron bar about two feet
AET. 1.]
TOOLS.
127
long, slightly flattened at one end. In this end is a slot 3 inches
long and finch wide. Through this ^.-^p — • -^
slot are passed ten double-headed
points of 5-inch square steel, 9
inches long, which are held in
place by a key.
"The Patent Hammer, Fig.
17, is a double-headed tool so
formed as to hold at each end a set of wide thin chisels. The tool
is in two parts, which are held to-
gether by the bolts which hold the
" chisels. Lateral motion is prevented
by four guards on one of the pieces.
FIG. 16.— CRANDALL.
FIG. 17.— PATENT HAMMER. The tool without the teeth is
'2f X 1£ inches. The teeth are 2f inches wide. Their thickness
varies from -^ to -J- of an inch. This tool is
used for giving a finish to the surface of stones.
"'The Hand Hammer, Fig. 18, weighing
from 2 to 5 pomids, is used in drilling holes, FIG. is.— HAND HAMMER.
and in pointing and chiseling the harder rocks.
"'The Mallet, Fig. 19, is used where the softer limestones and
sandstones are to be cut.
"The Pitching Chixel, Fig. 20,
is usually of 1-J-inch octagonal steel,
spread on the cutting edge to «,
rectangle of •£ X 2-J- inches. It is
used to make a well-defined edge to
the face of a stone, a line being marked on the joint surface to
which the chisel is applied and the portion of the stone outside of
the line broken off by a blow with the hand-hammer on the head
of the chisel.
"The Point, Fig. 21, is made of round or octagonal rods of
steel, from £ inch to 1 inch in diameter. It is made about 12
inches long, with one end brought to a point.
It is used until its length is reduced to about Q ^>
5 inches. It is employed for dressing off the
irregular surface of stones, either for a perma-
nent finish or preparatory to the use of the ax.
According to the hardness of the stone, either the hand-hammer
or the mallet is used with it.
FIG. 19.— MALLET.
~>
FIG. 21.— POINT.
STONE CUTTING
[CHAP. VI.
T in £ inch in diameter
It is used only on mar-
and sandstones
eacll of these holes
ed to the maoliine which,
ART, 2.] METHOD OF FORMING SURFACES. 129
attacks the rough stone and reduces the inequalities somewhat.
After this treatment the stone goes in succession to the stone-
planer, stone-grinder,, and stone-polisher.
Those stones which are homogeneous, strong and tough, and
comparatively free from grit or hard spots, can be worked by ma-
chines which resemble those used for iron ; but the harder, more
brittle stones require a mode of attack more nearly resembling that
•employed in dressing stone by hand. Stone-cutters and stone-
planers employing both forms of attack are made.
Stone-grinders and stone-polishers differ only in the degree of
fineness of the surface produced. They are sometimes called " rub-
bing-machines." Essentially they consist of a large iron plate re-
volving in a horizontal plane, the stone being laid upon it and braced
to prevent its sliding. The abradent is sand, which is abundantly
supplied to the surface of the revolving disk. A small stream of
water works the sand under the stone and also carries away the
debris.
ART. 2. METHOD OF FORMING THE SURFACES.
182. It is important that the engineer should understand the
methods employed by the stone-cutter in bringing stones to any re-
•quired form. The surfaces most frequently required in stone cutting
are plane, cylindrical, warped, helicoidal, conical, spherical, and
sometimes irregular surfaces.
183. PLANE SURFACES. In squaring up a rough stone, the first
thing the stone-cutter does is to draw a line, with iron ore or black
lead, on the edges of the stone, to indicate as nearly as possible the
required plane surface. Then with the hammer and the pitching-
tool he pitches of! all debris or waste material above the lines,
thereby reducing the surface approximately to a plane. With a
chisel he then cuts a draft around the
edges of this surface, •/. e., he forms nar-
row plane surfaces along the edges of the
.stone. To tell when the drafts are in
the same plane, he uses two straight-
edges having parallel sides and equal
widths. See Pig. 27. The projections Fm-27-
on the surface are then removed by the pitching chisel or the point,
until the straight-edge will just touch the drafts and the inter-
mediate surface when applied across the stone in any direction.
130
The surface is usuallv left a little « slack/' i.e., concave, to allcm
room for the mortar"; however, the surface should be bat a very
little concave. . , , , , ,
The surface Is then finished with the «, patent hammer bush
hammer, etc., according to the degree of smoothness required.
184. To form a second plane surface at right angles to the first
one, the workman draws a line on the cut face to form the inter-
section of the two planes ; he also draws a line on the ends of the
stone approximately in the required plane. With the ax or the
chisel he then cuts a draft at each end of the stone until a steel
square fits the angle. He then joins these drafts by two others at.
right angles to them, and brings the whole surface to the same.
plane. The other faces may be formed in the same way.
If the surfaces are not at right angles to each other, a bevel is.
used instead of a square, the same general method being pursued.
185. CYUHDSICAL SURFACES. These may be either concave or
convex. The former are frequently required, as in arches; and the
latter sometimes, as in the outer end of the face-stones of an arch.
The stone is first reduced to a paralellopipedon, after which the
curved surface is produced in either of two ways : (1) by cutting
a circular draft on the two ends and applying a straight-edge along-
the rectilinear elements (Fig. 28); or (2) by cutting a draft along'
the line of intersection of the plane and cylindrical surface, and
applying a curved templet to the required surface (Fig. 29).
FIG. 88. FIG. 29.
186. COUTCAI STJEFACES may be formed by a process very similar
to the first one given above for cylindrical surfaces. Such surfaces
are seldom used.
187. SPHERICAL SURFACES are sometimes employed, as in domes,
They are formed by essentially the same general method as cylin-
drical surfaces.
188. WABPED SURFACES. Under this liead are included what
ALT. 3.1
MI: 1:1 >:>
: : v>:::\
i> r*.!?. Ti\o twlsi rule.- u"e ^t^nired, the
ai1 jfle betiTeeL tl:e upf er aii'l luwer e«l^.e^ rijt ••
1 tli.g hull* of tli3 if ^Liretl twist. Drafts are tLin citt in 4.^^ rLiis < f
the ».< ne until the t'j}i> of tie cwis*. mle>. when L^;!IJU u« In ti=r.
^1), are in a pkne. Tlie remainder of tiie p*<»je •:::._: i;*^.j is rei:* vei
until a stralght-e«3^e, wl t-:* a/j-iieu parallel to rLe L^je : t..^ s.^e,
will just touch the end il rafts and the intermediure surface.
If the surface Is to be twisted at only one end, a parallel rule
and a twist rule are used.
189. MAKIKG THE BBAWITOS. The method of making work-
ing drawings for constructions in stone will appear in subsequent
chapters, in connection with the study of the structures them-
selves: but for detailed instructions, see the text-books on Srere-
otomy or Stone Cutting.
ART. 3. METHODS OF FINISHING THE SURFACES.*
190. "All stones used in building are divided into three classes,
according to the finish of the surface; viz. :
I. Bough stones that are used as they come from the quarry.
IT. Stones roughly squared and dressed.
III. Stones accurately squared and finely dressed.
" In practice, the line of separation between them is not very
distinctly marked, but one ckss gradually merges into the next.
191. I " UimUABEB ST0F1S. This class covers all stone.-?
which are used as they come from the quarry,, without other
preparation than the removal of very acute angles and excessive pro-
jections from the general figure. The term * backing, ' which is
frequently applied to this class of stone., is inappropriate, as it prop-
erly designates material used in a certain relative position in a wall,
whereas stones of this kind may be used in any position.
192. n. " SQUARED STOWES. This class covers all stones that
* This article is taken from the report of the committee of the American Societ j
of Civil Engineers previously referred to.
STOKE CUTTING. [CHAP. VI.
i 0,wi rouffhly dressed on beds and joints. The
are roughly squared and lougmj J .
dressing is usually done with the face hammer or ax, or in soft
.tones with the tooth hammer. In gneiss it may sometimes be
necessarv to use the point. The distinction between this class and
the third lies in the degree of closeness of the joints. A\liere the
dre«sin<, on the joints is such that the distance between the general
planes of the surfaces of adjoining stones is one half inch or more,
the stones properly belong to this class.
"Three subdivisions of this class may be made, depending on
the character of the face of the stones:
" (tt) Quarry-faced stones are those whose faces are left un-
touched as they come from the quarry.
" (5) Pitched-faced stones are those on which the arris is clearly
defined by a line beyond which the rock is cut away by the pitching
chisel, so'as to give edges that are approximately true.
" (c) Drafted Stones are those on which the face is surrounded by
a chisel draft, the space inside the draft being left rough. Ordi-
narily, however, this is done only on stones in which the cutting of
the joints is such as to exclude them from this class..
" In ordering stones of this ciass the specifications should always
state the width of the bed and end joints which are expected, and
also how far the surface of the face may project beyond the plane
of the edge. In practice, the projection varies between 1 inch and
6 inches. It should also be specified whether or not the faces are to
be drafted.
193. IH " CUT STONES. This class covers all squared stones
with smoothly-dressed beds and joints. As a rule, all the edges of
cut stones are drafted, and between the drafts the stone is smoothly
dressed. The face, however, is often left rough where construction
is massive.
"In architecture there are a great many ways in which the faces
of cut stone may be dressed,
but the following are those
that will usually be met in
engineering work:
" Rough-pointed. When it
is necessary to remove an inch
FIG. ai.-BouGH-FonrrBD. or more from the face of a
stone, it is done by the pick or heavy point until the projections
METHODS OF FINISHING SURFACES.
133
3m -J- inch to 1 inch. The stone is then said to be rough-
(Fig. 31). In dressing
le and granite, this
m precedes all others.
ne-pointed. (Fig. 32).
Dother finish is desired,,
)ointing is followed by
inting, which is done
Ine point. Fine point-
sed only where the finish made by it is to be final, and never
iparation for u final finish by another tool.
andalled. This is only a speedy method of pointing, the
eing the same as fine pointing, except that the dots on the
:e more regular. The variations of level are about £ inch,
> rows are made parallel. When other rows at right angles
irst are introduced, the stone is said to be cross-crandalled.
FIG. 32.— FINK-POINTED.
FlG. 33. — CRANDALLED.
FIG. 34.— AXED.
ced, or Pean-hammered, and Patent-hammered. These two
ly in the degree of smoothness of the surface which is pro-
The number of blades in a patent hammer varies from 6 to
le inch; and in precise specifications the number of cuts to
h must be stated, such as 6-cut, 8 -cut, 10-cut, 12-cut. The
f axing is to cover the surface with chisel marks, which are
arallel as far as practicable. Fig. 34. Axing is a final finish.
ooth-axed. The tooth-ax is practically a number of points,
leaves the surface of a stone in the same condition as fine
g. It is usually, however, only a preparation for bush-ham-
, and the work is then done without regard to effect so long
surface of the stone is sufficiently leveled.
ish-hammerecL The roughnesses of a stone are pounded off by
134
the bush hammer, and
STOKE CUTTING.
[CHAP. vi.
FIG. 35.— BUSH-HAMMERED.
the stone is then said to be ' bushed/
This kind of finish is dangerous
on sandstone, as experience has
shown that sandstone thus treated
is very apt to scale. In dressing
limestone which is to have a bush-
hammered finish, the usual se-
quence of operation is (1) rough-
pointing, (2) tooth-axing, and (3)
bush-hammering. Fig. 35.
"Bubbed. In dressing sandstone and marble, it is very common
to give the stone a plane surface at once
by the use of the stone-saw [§ 181]. Any
roughnesses left by the saw are removed
by rubbing with grit or sandstone [§ 181].
Such stones, therefore, have no margins.
They are frequently used in architecture
for string-courses, lintels, door-jambs, etc. ; FIG. 36.—:
aad they are also well adapted for use in facing the walls of lock-
chambers and in other localities where a stone surface is liable to be
nibbed by vessels or other moving bodies. Fig. 3G.
"Diamond Panels. Sometimes the space between the margins
is sunk immediately adjoining them and
then rises gradually until the four planes
form an apex at the middle of the pand.
In general, such panels are called diamond
panels, and the one just described, Fig.
37, is called a sunk diamond panel.
When the surface of the stone rises grad-
ually from the inner lines of the margins
to the middle of the panel, it is called a
diamond panel, Both kinds of finish arc common on bridge
qioins and similar work. The details of this method should bo
given ii the specifications."
FIG. 37.-DLOIOFD PANEL.
CHAPTER VII.
STOKE MASONRY.
194. MASOKTRY is classified (1) according to the nature of the
material — as stone masonry,, brick masonry, and mixed masonry or
that which is composed of stone and brick; — and (2) according to
the manner in which the material is prepared — as rubble or un-
squared-stone masonry, squared-stone masonry,, and ashlar or cut-
stone masonry.
The classification of masonry for engineering purposes is based
almost entirely upon the size and figure of the stones, and upon the
manner in which the joints are formed and executed, the appearance
of the face being a matter of secondary importance.
In preparing specifications, it is not safe to depend alone upon
the terms in common use to designate the various classes of masonry;
but every specification should contain an accurate description of the
•character and quality of the work desired. "Whenever practicable,
.samples of each kind of cutting and masonry should be prepared
beforehand, and be exhibited to the persons who propose to under-
take the work.
195. DEFINITIONS OF PARTS OF THE WALL.* Face, the front
surface of a wall; /back, the inside surface.
Facing, the stone which forms the face or outside of the wall.
Backing, the stone which forms the back of the wall. Filling, the
interior of the wall.
Batter. The slope of the surface of the wall.
Course. A horizontal layer of stone in the wall. If the stones
of each layer are of equal thickness throughout, it is termed regular
coursing ; if the thicknesses are unequal, the term random or un-
equal coursing is applied.
Joints. The mortar-layer between the stones. The horizontal
joints are called 'bed-joints or simply beds ; the vertical joints are
sometimes called the luilds. Usually the horizontal joints are
•called 1>(>ds, and the vertical ones joints.
* The definitions in this chapter are in accordance with the recommendations of
the Committee of the American Society of Civil Engineers previously referred to,
and conform to the best practice. Unfortunately they are not universally adopted.
135
136
STCXtfE MASOKRY.
[CHAP. vii.
Coping. A projecting course of heavy stones on the top of the
wall to protect it.
Pointing. A better quality of mortar put in the face of tile-
joints to help them to resist weathering.
Bond The arrangement of stones in adjacent courses (§ 202).
Stretcher. A stone whose greatest dimension lies parallel to the
face of the wall
Header. A stone whose greatest dimension lies perpendicular
to the face of the wall.
Quoin. A corner-stone. A quoin is a header for one face and a
stretcher for the other.
Dowels. Straight bars of iron which enter a hole in the upper
side of one stone and also a hole in the lower side of the stone next
above.
Cramps. Bars of iron having the ends turned at right angles ta
the body of the bar, which enter holes in the upper side of adjacent
stones.
196. DEFINITIONS OF KINDS OF MASONRY. Ashlar. Cut-stone
masonry, or masonry composed of any of the various kinds of cut •
stone mentioned in
§ 193. See Fig. 38,
From its derivation,
ashlar apparently
means large, square-
blocks ; but practice
,1 ,»
TT
I
FIG. 88.— ASHLAR, FIG. 39.— -BROKEN ASHLAR, g^jj^g 4-Q
synonymous with t( cut-stone," and this secondary meaning has been
retained for convenience.
Broken Ashlar. Cut-stone masonry in which the joints are not
continuous. Fig. 39.
Small Ashlar. Cut-stone masonry in which the stones arc losa.
than one foot thick. The term is not often used.
Rough Ashlar. A term sometimes given to squared-stonc
masonry (§ 197), either quarry-faced or pitch-faced, when laid as
range-work; but ' ' it is more logical and more expressive to call such
masonry squared range- work."
Dimension Stones. Cut-stones, all of whose dimensions have
been fixed in advance, " If the specifications for ashlar masonry
are so written as to prescribe the dimensions to be used, it will not be
necessary to make a new class for masonry composed of such stones. 5>
DEFINITION'S OP KINDS OF MASONRY.
137
197. Squared-stone Masonry. Work in which the stones are
roughly squared and roughly dressed on beds and joints (§ 192). The-
distinction between squared-stone masonry and ashlar (§ 196) lies in
the degree of closeness of the joints. According to the report of
the Committee of the American Society of Civil Engineers, C( when
the dressing on the joints is such that the distance between the
general planes of the surface of adjoining stones is one-half inch or
more, the stones properly belong to this class;" nevertheless, such
masonry is usually classed as ashlar or cut-stone masonry.
Quarry -faced Masonry. That in which the face of the stone
is left as it comes from
III
nzr
i i i r
I , I
.1,1
J L
FIG. 40. FIG. 41.
FIGK 42.— RANGE.
-1-
Vl
1
1
1
—
1
1
-rl
1
1
1
FIG. 43.— BROKEN RANGE.
FIG. 44.— RANDOM.
the quarry. Fig. 40.
Pitched-faced Ma-
sonry. That in which
the face of the stone is
roughly dressed (§ 192,
V). Fig. 41.
Range-work. Masonry in which the course is of the same thick-
ness or rise throughout.
Fig. 42.
Broken Range-work.
Masonry in which the
courses are not continu-
ous throughout. Fig. 43.
Random-work. Ma-
sonry which is not laid in courses at all. Fig. 44.
198. Bubble Masonry. Masonry composed of unsquared stone
(§ 191)-
Uncoursed Rubble. Masonry composed of unsquared stones
laid without any attempt
at regular courses. Fig.
45.
Coursed Rubble. Un-
squared-stone masonry
which is leveled off at
specified heights to an
approximately horizontal
surface. It may be specified that the stone shall be roughly shaped
with the hammer, so as to fit approximately. Fig. 46.
FIG. 45.
UNCOURSED RUBBLE.
FIG. 40.
COURSED RUBBLE.
138 STOKE MASoisriiY. [CHAP. YH.
199. GENEBAL RULES. Rankiiie gives the following rules to be
observed in the building of all classes of stone masonry:
" I. Build the masonry, as far as possible, in a series of courses,
perpendicular, or as nearly so as possible, to the direction of the
pressure which they have to bear; and by breaking joints avoid all
long continuous joints parallel to that pressure.
(i II. Use the largest stones for the foundation course.
" III. Lay all stones which consist of layers in such a manner that
the principal pressure which they have to bear shall act in a direction
perpendicular, or as nearly so as possible, to the direction of the
layers. This is called laying the stone on its natural led, and is of
primary importance for strength and durability.
" IV. Moisten the surface of dry and porous stones before bed-
ding them, in order that the mortar may not be dried too fast and
reduced to powder by the stone absorbing its moisture.
" V. Fill every part of every joint, and all spaces between the
stones, with mortar, taking care at the same time that' such spaces
shall be as small as possible."
Another and very important rule is: the rougher the stones, the
better the mortar should bo. The principal object of the mortar is
to equalize the pressure; and the more nearly the stones are reduced
to closely fitting surfaces, tlio less important is the mortar. Not
infrequently -this rulo is exactly reversed; i. #., the finer the dressing,
the better the quality of the mortar used.
200. ASHLAR MASONRY. For definitions of this class of masonry
and its subdivision, see § 196.
The strength of a mass of ashlar masonry depends upon the
size of the blocks in each course, xtpon the accuracy of the dressing,
and upon the bond.
In order that the stones may nob be liable to be broken across,
no soft stone, such a& the weaker kinds of sandstone and granular
limestone, should have a length greater than 3 times its depth; but
in harder. materials, the length may be 4 or 5 times the depth. The
breadth, in soft materials may range from 1 J to 2 times the depth ;
in hard materials, it may be 3 times the depth.
201. Dressing, The closeness with which stones fit is depend-
ent solely upon the accuracy with which the surfaces in contact are
wrought, or dressed, and is of special importance in the case of
bed-joints, If any part of the surface projects beyond the plane
ASHLAR MASONRY. 139
of the chisel-draft, that projecting part will have to bear an undue
share of the pressure, the joint will gape at the edges, — constituting
•what is called an open joint, — and the whole will be wanting in
stability. On the other hand, if the surface of the bed is concave,
having been dressed down below the plane of the chisel-draft, the
pressure is concentrated on the edges of the stone, to the risk of
splitting them off. Such joints are said to \>G flushed. They are
more difficult of detection, after the masonry has been built, than
open joints ; and are often executed by design, in order to give a
neat appearance to the face of the building. Their occurrence
must therefore be guarded against by careful inspection during
the progress of the stone cutting.
Great smoothness is not desirable in the joints of ashlar masonry
intended for strength and stability ; for a moderate degree of rough-
ness adds at once to the resistance to displacement by sliding, and
to the adhesion of the mortar. When the stone has been dressed
so that all the small ridges and projecting points on its surface are
reduced nearly to a plane, the pressure is distributed nearly uni-
formly, for the mortar serves to transmit the pressure to the small
depressions. Each stone should first be fitted into its place dry,
in order that any inaccuracy of figure may be discovered and cor-
rected by the stone-cutter before it is finally laid in mortar and
settled in its bod.
The thickness of mortar in the joints of the very best ashlar
masonry — for example, the United States post-office and custom-
house buildings in the principal cities — is about -J of an inch ; in
first-class railroad masonry — for example, important bridge piers
and abutments, and large arches — the joints are from £ to f of an
inch; and in second-class railroad masonry — for example, small
bridge piers and abutments, and small arches — the joints do not
exceed f to 1 inch.
A chisel-draft 1|- or 2 inches wide is usually cut at each exterior
corner.
202. Bond. No side- joint of any course should be directly above
a side- joint in the course below ; but the stones should overlap, or
"brealc joint, to an extent of from 1 to 1£ times the depth of the
course. This is called the lond of the masonry. The effect is that
each stone is supported by at least two stones of the course below, and
assists in supporting at least two stones of the course above. The
140 ST03TE MASONRY. [CHAP. VIL,
object is twofold : first, to distribute tlie pressure, so that inequali-
j ties of load oil the upper part of tlie structure (or of resistance at
; the foundation) may be transmitted to and spread over an inereas-
; ing area of bed in proceeding downwards (or upwards) ; and second,
to tie the building together, i. e., to give it a sort of tenacity, both
lengthwise and from face to back, by means of tlie friction of the
stones where they overlap.
The strongest bond is that in which each course at the face of
( the structure contains a header and a stretcher alternately, the
outer end of each header resting on the middle of a stretcher of
the course below, so that rather more than one third of the area of
the face consists of ends of headers. This proportion may be
deviated from when circumstances require it, but in every case it
is advisable that the ends of headers should not form less than one
fourth of the whole area of the face of the structure. A header
should extend entirely through the wall, and should be over the
middle of the stretcher in the course below.
A trick of masons is to use "blind-headers/' or short stones that
\ look like headers on the outside but do not go deeper into the wall
than the adjacent stretchers. When a course has been put on top
of these, they are completely covered up ; and, if not suspected,
the fraud will never be discovered unless the weakness of the wall
; reveals it.
Where very great resistance to displacement of the masonry is
required (as in the upper courses of bridge piers, or over openings,
or where new masonry is joined to old, or where there is danger of
I unequal settlement), the bond is strengthened by dowels or by
\ cramp-irons (§ 195) of, say, IJ-inch round iron set with cement
\ mortar.
\ 203. Backing. Ashlar is usually backed with rubble masonry
\ (| 213), which in such cases is specified as coursed rubble. The
J" stones of the ashlar face should have their beds and joints accurately
squared and dressed for a distance inward from the face of from 1
i to Z times (say, on the average, 1£ times) the depth of the course ;
\ but the backs of these stones may be rough. The proportion and
V length of the headers should be the same as in ashlar. The
'-. - <e tails" of the headers, or the parts which extend into the rubble
-, backing, may be left rough at the back and sides ; but their upper
and lower beds should be dressed to the general plane of the bed of
ASTILAE 3IASOXKY. 141
the course. These fs tails'-' may tuper slightly In breadth, "but should
not taper in depth.
The backing should be carried up at the same time with the
face-work, and in courses of the same depth; and the bed of each
course should be carefully built to the same plane with that of the
ashlar facing. The rear face of the backing should be lined to a
fair surface.
204. Pointing. In laying masonry of any character, whether
with common or hydraulic mortar, the exposed edges of the joints
will naturally be deficient in density and hardness. The mortar in
the joints near the surface is especially subject to dislodsrment,
since the contraction and expansion of the masonry is liable either
to separate the stone from the masonry or to crack the mortar in
the joint, thus permitting the entrance of rain-water, which, freezing,
forces the mortar from the joints. Therefore it is usual, after the
masonry is laid, to refill the joints as compactly as possible, to the
depth of at least half an inch, with mortar prepared especially for
this purpose. This operation is called pointing.
The very best cement mortar should be used for pointing, as the
best becomes dislodged all too soon. Clear Portland cement mor-
tar is the best, although 1 volume of cement to 1 of sand is fre-
quently used in first-class work. The mortar, when ready for use,
should be rather incoherent and quite deficient in plasticity. Before
applying the pointing, the joint should be well cleansed by scrap-
ing and brushing out the loose matter, and then be well moistened.
Of course, the cleansing out of the joints can be most easily done
while the mortar is new and soft. The depth to which the mortar
shall be dug out is not often specified ; it is usually cleaned cut-
about half an inch deep, but should be at least an inch. In the
Brooklyn bridge piers the joints were cleared 14- inches deep.
The mortar is applied with a mason's trowel, and the joint well
calked with a calking iron and hammer. In the very best work,
the joint is also rubbed smooth with a steel polishing tool. Walls
should not be allowed to dry too rapidly after pointing ; therefore,
pointing in hot weather should be avoided.
205. Amount of Mortar. The amount of mortar required for
ashlar masonry varies with the size of the blocks, and also with
the closeness of the dressing. With f- to f-inch joints and 12- to
30-inch courses, there will be about 2 cubic feet of mortar per
STOKE MASOHRY.
[CHAP.
-. vn..
206. When
, aretes, and para
; for hydraulic work, ; r
, ^^ k d
for works iu
SIKSS-H « «-. fjrn — =«'"«" r
SQUARED-STONE MASONRY. 14B
The masonry shall be laid with cement inortar consisting of 1 volume of
cement of the Rosendale type and 2 volumes of sand. Each stone shall be
cleaned and dampened before being set. No hammering on the wall will be
allowed after the course is set; but if any inequalities occur, they must be
carefully pointed off. *
The backing shall be of good-sized, well-shaped stones, laid so as to break
joints and thoroughly bond the work in all directions and leave no spaces
between them over six inches (6") wide, which spaces shall be tilled with
small stones and spalls set in cement mortar.
All foundation courses must be laid with selected, large, flat stones not
less than twelve inches (12") in thickness, nor of less superficial surface than
fifteen (15) square feet.
The coping shall be formed of large flat stones, which shall extend entirely
across the wall when the same is not more than six feet (6') wide. The steps
of wing walls shall be capped with stone covering the entire step and extend-
ing under the step next above at least twelve inches (12"). Coping and step
stones shall be at least twelve inches (12") thick, and have such projections as
the engineer may direct [usually 3 to 6 inches]. The tops and faces of cop-
ings and step stones shall be bush-hammered, and their joints and beds cut
to one quarter inch (£") throughout.
208. SQTTARED-STONE MASONRY. For definitions of this class of
masonry and its subdivisions, see § 197. The distinction between
squared-stone masonry and ashlar lies in the degree of closeness of
the joints. According to the Eeport of the Committee of the
American Society of Civil Engineers, "when the dressing on the
joints is such that the distance between the general planes of the
surfaces of adjoining stones is one half inch or more, the stones
properly belong to this class;" however, such masonry is usually
classed as ashlar or cut-stone masonry.
Squared-stone masonry is usually quarry-faced, random-work,
although range-work is not uncommon. The quoins and the sides
of openings are usually hammer-dressed, which consists in removing
projections so as to secure a rough-smooth surface and is done with
the face-hammer, the ordinary ax, or the tooth-ax. This work is a
necessity where door or window frames are inserted; and it greatly
improves the general effect of the wall, if used wherever a corner
is turned.
209. Squared-stone masonry is distinguished, on the one hand,
from ashlar in having less accurately dressed beds and joints, and,
on the other hand, from rubble in being more carefully constructed.
In ordinary practice, the field covered by this class is not very
definite. Occasionally the specifications for '•' second-class masonry"
T ',
• A':-1.
"""""" a -p ™ to the above aescripbiujo. of pitched-
asused on railroad%C°^™ asonry; but more frequently the terra
faced, range, squared-stone mason y^ ^ ^.^ ^^ ^_
>< second-class masonry 0^etimes designated as third-class
We.» Ordinary rubble » ^ some ^ & ^
fflBB^.tataan^y^^^^'fliHt-cilaaB- masonry" *«e
provement upon present p /^ masonryj « second-class
used to designate asniar Ol a «third_class masonry"
masonry" for squared-stone masomy, ana
for rubble. Eequired. The amount of mortar re-
210. Amount of Mort^ag^y yaries with the size of the stones
quired for s(ll'iared"st0^eo™aTV1.1!JOTirv. as a rough average, one sixth
-. *ii i.V^ /M tin IT TV nT TjllvJ IllwoUiAA jr 5 «-v^ <~> ,
-aB-d with trie quciiiuj ^ ^ , , amount 01 mortar
to ™ imii6 ;^a ; "^- 3- - ~™* . - ™-
.xeotiired lor <* uuu^ j^ ^ red-stone ntuisonry win re-
STt. When laid in 1 to?^^'* O'ul)ic yard of masonry.
5 and sand required for mortars of various
Tlee the table on page^SG. ^ ^ § ^^ rcspectively_
cone Masonry. Squared-stone
and abutments of the lighter
5pan and under, for box-culverts,
specifications are usually about as
es pitched to a straight
VL.CSS, with beds tlirough-
thick, nor measure iu its
10 inches (12"): nor loss than its thick-
\tleast eigM inches (8"). The bed-
inches (8") back from the face shall
need not be laid up in regular
211.
212.
masonry is emx „
• bridge* tor arches of 10-
for basement -walls, etc.
follows:*
The face stones shall have quarry
Each stone shall be dr—^^'
shall be less
ce^t mortar beds, and the pints shall be
* For com]
joints
»-«——«»-—
mry for various purposes, see Appendix L
EUBBLE MASONRY. 145
also be filled with mortar. The spaces between the large stones shall be filled
with spalls set in mortar.
The coping shall be formed of large flat stones of such thickness as the
engineer may direct, but in no case to be less than eight inches (8"). The
upper surface of the coping shall be bush-hammered, and the joints and beds
shall be dressed to one half an inch (£") throughout. Each stone must extend
entirely across the wall when the wall is not more than four feet (4') thick.
213. EUBBLE MASONRY. For definitions connected witli this
•class of masonry, see § 198,
The stones used for rubble masonry should be prepared by
.simply knocking off all the weak angles of the block. It should be
cleansed from dust, etc., and moistened, before being placed on its
bed. This bed is prepared by spreading over the top of the lower
course an ample quantity of good, ordinary-tempered mortar in
which the stone is firmly embedded. The vertical joints should be
•carefully filled with mortar. The interstices between the larger
masses of stone are filled by thrusting small fragments or drippings
of stone into the mortar. In heavy walls of rubble masonry, the
precaution should be observed to give the stones the same position
in the masonry that they had in the quarry, 1. #., to lay them on
their "natural bed," since stone offers more resistance to pressure
in a direction perpendicular to the quarry-bed than in any other.
The directions of the laminae in stratified stones show the position
of the quarry-bed.
To connect the parts well together and to strengthen the weak
points, throughs or binders should be used in all the courses, and
the angles should be constructed of cut or hammered stone.
When carefully executed with good mortar, rubble possesses all the
strength and durability required in structures of an ordinary char-
acter, and is much less expensive than ashlar. The difficulty is in
getting it well executed. The most common defects are (1) not bring-
ing the stones to an even bearing; (2) leaving large vertical openings
between the several stones; (3) laying up a considerable height of
the wall dry, with only a little mortar on the face and back, and
then pouring mortar on the top of the wall; (4) using insufficient
cement, or that of a poor quality. The last defect is usually obviated
by furnishing the cement to the contractor ; and the second and
third defects may be detected by probing the vertical joints with a
.small steel rod. In order to secure good rubble, great skill and
- - -
as used on radroads
faced, range, squared-s on
Second-class masonry ^ 1 •
We.» Ordinary rubble is
ma8onry, but generally simply as rub
provement
so masonry, "second-class
,y, and "third-class masonry"
for rubble. Required. The amount of mortar re-
210. Amcmat of Mo tarKeq ^ ^ ^ rf ^
quired for ^^J-^J^Jnry; as a rough average, one s.xth
«d mtb. the quahty of t118.111^^' por the am0uUt of mortar
,o one quarter of the mass „ mo^t - ^ ^^
xequired for ^^2 mortar squared-stone masonry
S7. When tod m 1 te .8 ^orto 1
re-
Compositions, see
211. Baking
212. Specific^ for
masonry is ^I^.
bridges, for arches d t 1
for basement walls, etc.
, follows*
203 and § 204, respectively.
Squared-stone
^ of the lighter
pan and under, for box-culverts,
«T 'jflflatjoni| are Dually about as
i-
The face stones shall have quarry
Each stone shall be dresse dto a
No stone shall be less than
MS8., on
jointsaadalsothevertica
pitched to a straight
^ wlth ^d. Uu-ougl,.
^ ^^^ _n ^
) norle»Htban iu U»ick-
The bed-
^t from tho face riiall
g ^ ^ Jaid up m
i least one Loader, Un,c feet (3)
pacted lull. .
The backing shall consist °*
least onehalf of the stones _ 1n
•The backing shall be laid m lull
d^U ceraent naortar beds, and the Joints Hlu.ll be
ttlan six inches (6") thick. At
iaU measure two (3) cubic feet
and the vel,ical joints Bhall
,
*^orcompl<
BUBBLE MASONRY. 145
also be filled with mortar. The spaces between the large stones shall be filled
with spalls set in mortar.
The coping shall be formed of large flat stones of such thickness as the
engineer may direct, but in no case to be less than eight inches (8"). The
upper surface of the coping shall be bush-hammered, and the joints and beds
shall be dressed to one half an inch (£") throughout. Each stone must extend
entirely across the wall when the wall is not more than four feet (4') thick.
213. BUBBLE MASONKY. For definitions connected with this
•class of masonry, see § 198.
The stones nsed for rubble masonry should be prepared by
simply knocking off all the weak angles of the block. It should be
cleansed from dust, etc., and moistened, before being placed on its
bed. This bed is prepared by spreading over the top of the lower
course an ample quantity of good, ordinary-tempered mortar in
•which the stone is firmly embedded. The vertical joints should be
•carefully filled with mortar. The interstices between the larger
masses of stone are filled by thrusting small fragments or drippings
•of stone into the mortar. In heavy walls of rubble masonry, the
precaution should be observed to give the stones the same position
in the masonry that they had in the quarry, -L e., to lay them on
their "natural bed," since stone offers more resistance to pressure
in a direction perpendicular to the quarry-bed than in any other.
The directions of the laminae in stratified stones show the position
of the quarry-bed.
To connect the parts well together and to strengthen the weak
points, throughs or binders should be used in all the courses, and
the angles should be constructed of cut or hammered stone.
When carefully executed with good mortar, rubble possesses all the
strength and durability required in structures of an ordinary char-
acter, and is much less expensive than ashlar. The difficulty is in
getting it well executed. The most common defects are (1) not bring-
ing the stones to an even bearing; (2) leaving large vertical openings
between the several stones; (3) laying up a considerable height of
the wall dry, with only a little mortar on the face and back, and
then pouring mortar on the top of the wall; (4) using insufficient
cement, or that of a poor quality. The last defect is usually obviated
by furnishing the cement to the contractor ; and the second and
third defects may be detected by probing the vertical joints with a
small steel rod. In order to secure good rubble, great skill and
146 STONE MASOXRY. [CHAP. VII.
care are required on the part of the mason, and constant watchful-
ness on the part of the Inspector.
A very stable wall can be built of rubble masonry without any
dressing, except a draft on the quoins by which to plumb the cor-
ners and carry them up neatly, and a few strokes of the hammer to
spall off any projections or surplus stone. This style of work is
not generally advisable, as very few mechanics can be relied upon to'
take the proper amount of care in leveling up the beds and filling
the joints; and as a consequence, one small stone may jar loose and
fall out, resulting probably in the downfall of a considerable part of
the wall. Some of the naturally bedded stones are so smooth and
•uniform as to need no dressing or spalling up; a wall of such stones-
is very economical, since there is no expense of cutting and no time
is lost in hunting for the right stone, and yet strong, massive work
is assured. However, many of the naturally bedded stones have
inequalities on their surfaces, and in order to keep them level in the
course it becomes necessary to raise one corner by placing spalls or
chips of stone under the bed, and to fill the vacant spaces well and
full with mortar. It is just here that the disadvantage of this style
of work becomes apparent. Unless the mason places these spalls so*
that the stone rests firmly, i. e., does not rock, it will work loose,
particularly if the structure is subject to shock, as the walls of
cattle- guards, etc. Unless these spalls are also distributed so as to-
support all parts of the stone, it is liable to be broken by the weight
above it. A few such instances in the same work may occasion con-
siderable disaster.
One of the tricks of masons is to put " nigger-heads" (stones-
from which the natural rounded surface has not been taken off)
into the interior of the wall.
214. Rubble masonry 13 sometimes laid without any mortar, as
in slope walls (§ 218), paving (§ 219), etc., in which case it is called
dry rubble; but as such work is much more frequently designated
as slope-wall masonry and stone-paving, it is better to reserve the
term rubble for undressed stone laid in mortar. Occasionally box
culverts are built of the so-called dry rubble; but as such construc-
tion is not to be commended, there is no need of a term to desig-
nate that kind of masonry.
215. Amount of Mortar Required. Jf rubble masonry is com-
posed of small and irregular stones, about one third of the mass-
BUBBLE MASONRY. 147
will consist of mortar; if the stones are larger and more regular,
one fifth to one quarter will be mortar. Laid in 1 to 2 mortar,
ordinary rubble requires from one half to one barrel of cement per
cubic yard of masonry.
For the amount of cement and sand required for mortar of va-
rious compositions, see the table on page 86. -"^
216. When Employed. Bubble masonry of the quality described
above is frequently employed for the smallest sizes of bridge abut-
ments, small arch culverts, box and open culverts, foundations of
buildings, etc., and for backing for ashlar masonry (§ 200).
217. Specifications for Bubble Masonry.* The following re-
quirements, if properly complied with, will secure what is generally
known among railroad engineers as superior rubble.
Rubble masonry shall consist of coursed rubble of good quality laid in
cement mortar. No stone sball be less than six inches (6") in thickness, unless
otherwise directed by the engineer. No stone shall measure less than twelve
inches (12") in its least horizontal dimension, or less than its thickness. At
least one fourth of the stone in the face shall be headers, evenly distributed
throughout the wall. The stones shall be roughly squared on joints, beds, and
faces, laid so as to break joints and in full mortar beds. All vertical spaces
shall be flushed with good cement mortar and then be packed full with spalls.
No spalls will be allowed in the beds. Selected stones shall be used at all
angles, and shall be neatly pitched to true lines and laid on hammer-dressed
beds; draft lines may be required at the more prominent angles.
The top of parapet walls, piers, and abutments shall be capped with stones
extending entirely across the wall, and having a front and end projection of
not less than four inches (4"). Coping stones shall be neatly squared, and laid
with joints of less than one half inch (£"). The steps of wing-walls shall be
capped with stone covering the entire step, and extending at least six inches
(6") into the wall. Coping and step stones shall be roughly hammer- dressed
on top, their outer faces pitched to true lines, and be of such thickness (not
less than six inches) and have such projections as the engineer may direct.
"The specifications for rubble masonry will apply to rubble masonry laid
dry, except as to the use of the mortar (see § 214)."
218. SLOPE-WALL MASONKY. A slope-wall is a thin layer of
masonry used to preserve the slopes of embankments, excavations,
canals, river banks, etc. , from rain, waves, weather, etc. The usual
specifications are as follows: —
The stones must reach entirely through the wall, and be not less than four
inches (4") thick and twelve inches (12") long. They must be laid with broken
joints; and the joints must be as close and free from spalls as possible.
* For complete specifications for masonry for various purposes, see Appendix I.
148 ST03"E MASONRY. [CHAP. VII.
219. STOKE PAVING. Stone paving is used for the inverts of arch
culverts, for protecting the lower end of arches from undermining,
and for foundations of box culverts and small arches. It is usually
classed as dry rubble masonry, although it is occasionally laid with
cement mortar. The usual specifications are about as follows :
Stone paving shall be made of flat stones from eight inches (8'') to fifteen
inches (lo") in depth, set cm edge, closely laid and well bedded in the soil, and
shall present an even top surf ace.
220. RlPEAP. Eiprap is stone laid, without mortar, about the
base of piers, abutments, etc., to prevent scour, and on banks to
prevent wash. When used for the protection of piers, the stones
are dumped in promiscuously, their size depending upon the
material at hand and the velocity of the current; stones of 15 to
25 cubic feet each are frequently employed. When used for the
protection of banks, the riprap is laid by hand to a uniform thick-
ness.
221. STRENGTH OF STONE HASONEY. The results obtained by
testing small specimens of stone (see § 13) are useful in determin-
ing the relative strength of different kinds of stone, but are of no
value in determining the ultimate strength of the same stone when
built into a masonry structure. The strength of a mass of masonry
depends upon the strength of the stone, the size of the blocks, the
accuracy of the dressing, the proportion of headers to stretchers,
and the strength of the mortar. A variation in any one of these
items may greatly change the strength of the masonry.
The importance of the mortar as affecting the strength of
masonry to resist direct compression is generally overlooked. The
mortar acts as a cushion (§ 9) between the blocks of stone, and if
it has insufficient strength it will be squeezed out laterally, pro-
ducing a tensile strain in the stone; weak mortar thus causes the
stone to fail by tension instead of by compression. No experiments
have ever been made upon the strength of stone masonry under the
conditions actually occurring in masonry structures, owing to the
lack of a testing-machine of sufficient strength. Experiments
made upon brick piers (§ 246) 1*2 inches square and from 2 to 10
feet high, laid in mortar composed of 1 volume Portland cement
and 2 sand, show that the strength per square inch of the masonry
is only about one sixth of the strength of the brick. An increase
of 50 per cent, in the strength of the brick produced no appreciable
STKBKGTH OF STO^E MASONRY. 149
effect on the strength of the masonry; but the substitution of
cement mortar (1 Portland and 2 sand) for lime mortar (1 lime and
3 sand) increased the strength of the masonry 70 per cent. The
method of failure of these piers indicates that the mortar squeezed
oni of the joints and caused the brick to fail by tension. Since the
mortar is the weakest element,, the less mortar used the stronger the
wall; therefore the thinner the joints and the larger the, blocks, the
stronger the masonry, provided the surfaces of the stones do not
come in contact.
It is generally stated that the working strain on stone masonry
should not exceed one twentieth to one tenth of the strength of the
stone; but it is clear, from the experiments on the brick piers re-
ferred to above, that the strength of the masonry depends upon the
strength of the stone only in a remote degree. In a general way it
may be said that the results obtained by testing small cubes may
vary 50 per cent, from each other (or say 25 per cent, from the
mean), owing to undetected differences in the material, cutting, and
manner of applying the pressure. Experiments also show that
stones crack at about half of their ultimate crushing strength.
Hence, when the greatest care possible is exercised in selecting and
bedding the stone, the safe working strength of the stone alone
should not be regarded as more than three eighths of the ultimate
strength. A further allowance, depending upon the kind of struc-
ture, the quality of mortar, the closeness of the joints, etc., should
bo made to insure safety. Experiments upon even comparatively
large monoliths give but little indication of the strength of masonry.
The only practicable way of determining the actual strength of
.masonry is to note the loads carried by existing structures. How-
ever, this method of investigation will give only the load which does
not crush the masonry, since probably no structure ever failed owing
to the crushing of the masonry. After an extensive correspondence
and a thorough search through engineering literature, the following
list is given as showing the maximum pressure to which the several
classes of masonry have been subjected.
222. Pressure Allowed. Early builders used much more mas-
sive masonry, proportional to the load to bo carried, than is cus-
tomary at present. Experience and experiments have shown that
such great strength is unnecessary. The load on the monolithic
piers supporting the largo churches in Europe does not exceed 30
150 STONE MASONRY. [CHAP. VII.
tons per sq. ft. (420 Ibs. per sq. in.),* or about one thirtieth of the
ultimate strength of the stone alone. The stone-arch bridge of 140
ft. span at Pont-y-Prydd, over the Taff, in Wales, erected in 1750,
is supposed to have a pressure of 20.7 tons per sq. ft. (290 Ibs. per
sq. in.) on hard limestone rubble masonry laid in lime mortar. A
former bridge at the same place failed with 64 tons per sq. ft.
Rennie subjected good hard limestone rubble in columns 4 feet
square to 22 tons per sq. ft. (300 Ibs. per sq. in. ). f The granite piers
of the Saltash Bridge sustain a pressure of 9 tons per sq. ft. (125
Ibs. per sq. in.).
The maximum pressure on the granite masonry of the towers of
the Brooklyn Bridge is about 28 J- tons per sq. ft. (about 400 Ibs. per
sq. in,). The maximum pressure on the limestone masonry of this
bridge is about 10 tons per sq. ft. (125 Ibs. per sq. in.). The face
stones ranged in cubical contents from 1-J- to 5 cubic yards; the
stones of the granite backing averaged about 1|- cu. yds., and of the
"limestone about 1J cu. yds. per piece. The mortar was 1 volume
of Eosendale cement and 2 of sand. The stones were rough-axed,
or pointed to i-inch bed-joints and J-inch vertical face-joints. J
These towers are very fine examples of the mason's art
In the Rookery Building, Chicago,, granite columns about 3 feet
square sustain 30 tons per sq. ft. without any signs of weakness.
In the Washington Monument, Washington, D. C., -the normal
pressure on the lower joint of the walls of the shaft is 20.2 tons
per sq. ft. (280 Ibs. per sq. in,), and the maximum pressure brought
upon any joint under the action of the wind is 25.4 tons per sq. ft.
(350 Ibs. per sq. in.).§
The pressure on the limestone piers of the St. Louis Bridge was,
before completion, 38 tons per sq. ft. (527 Ibs. per sq. in.); and after
completion the pressure was 19 tons per sq. ft. (273 Ibs. per sq. in.)
on the piers and 15 tons per sq. ft. (198 Ibs. per sq. in.) on the abut-
ments. ||
The limestone masonry in the towers of the Niagara Suspension
* In this connection it is convenient to remember that 1 ton per square foot is
equivalent nearly to 14 (exactly 13.88) pounds per square inch.
tProc. Inst. of C. E., vol. x. p. 341.
% F. Collingwood, asst. engineer, in Trans. Am. Soc. of C. E.
§ Report of Col. T. L. Casey, U. S. A., engineer in charge.
1 History of St. Louis Bridge, pp. 370-74.
MEASUREMENT OF MASONRY. 151
Bridge failed under 36 tons per sq. ffc., and were taken down, — how-
ever, the masonry was not well executed.*
At the South Street Bridge, Philadelphia, the pressure on the
limestone rubble masonry in the pneumatic piles is 15.7 tons per
sq. ft. (220 Ibs. per sq. in.) at the bottom and 12 tons per sq. ft. at
the top. "This is unusually heavy, but there are no signs of weak-
ness.'1'! The maximum pressure on the rubble masonry (laid in
cement mortar) of some of the large masonry dams is from 11 to 14
tons per sq. ft. (154 to 195 Ibs. per sq. in.). The Quaker Bridge
Dam is designed for a maximum pressure of IGf tons per sq. ft.
(230 Ibs. per sq. in.) on massive rubble masonry in best hydraulic
•cement mortar. J
223. Safe Pressure. In the light of the preceding examples
it may be assumed that the safe load for the different classes of
masonry is about as follows, provided each is the best of its class :
Concrete, 5 to 15 tons per square foot.
Rubble, 10 to 15 " "
-Squared stone, 15 to 20 " "
Limestone ashlar, . . . . 20 to 25 " " " "
Granite ashlar, 30 " "
224. MEASUREMENT OF MASONRY. The method of determining
the quantity of masonry in a structure is frequently governed by
trade rules or local custom, and these vary greatly with locality.
Masons have voluminous and arbitrary rules for the measurement
of masonry; for example, the masons and stone-cutters of Boston
at one time adopted a code of thirty-six complicated rules for the
measurement of hammer-dressed granite. As an example of the
indefiniteness and arbitrariness of all such rules, we quote the follow-
ing, which are said to be customary in Pennsylvania : " All open-
ings less than 3 feet wide are counted solid. All openings more
than 3 feet wide are taken out, but 18 inches is added to the
running measurement for every jamb built. Arches are counted
.solid from the spring of the arch, and nothing allowed for arching.
The corners of buildings are measured twice. Pillars less than 3 feet
square are counted on three sides as lineal measurement, multiplied
by the fourth side and depth; if more than 3 feet, the two opposite
* Trans. Am. Soc. of C. E., vol. xvii. pp. 204-12. f Ibid., vol. vii. pp. 305-6.
J Engineering News, vol. xix. p. 75.
152 STONE MASONRY. [CHAP. VH
sides are taken; to each side 18 inches for each jamb is added to
lineal measurement thereof; the whole multiplied by the smaller side
and multiplied by the depth."
A well-established custom has all the force of law, unless due
notice is given to the contrary. The more definite, and therefore
better, method is to measure the exact solid contents of the masonry,
and pay accordingly. In "net measurement" all openings are de-
ducted; in "gross measurement" no openings are deducted.
The quantity of masonry is usually expressed in cubic yards.
The perch is occasionally employed for this purpose; but since the
supposed contents of a perch vary from 16 to 25 cubic feet, the term
is very properly falling into disuse. The contents of a masonry
structure are obtained by measuring to the neat lines of the design.
If a wall is built thicker than specified, no allowance is made for the
masonry outside of the limiting lines of the design; but if the
masonry does not extend to the neat lines, a deduction is made for
the amount it falls short. Of course a reasonable working allow-
ance must be made when determining whether the dimensions of
the masonry meet the specifications or not.
In engineering construction it is a nearly uniform custom to
measure all masonry in cubic yards; but in architectural construc-
tion it is customary to measure water tables, string-courses, etc.,,
by the lineal foot, and window-siHs, lintels, etc., by the square foot.
In engineering, all dressed or cut-stonework, such as copings, bridge
seats, corn iocs, water-tables, etc., is paid for in cubic yards, with
an additional price per square foot for the surfaces that are dressed,
cut, or bush-hammered.
225, Classification of Railroad Masonry. The stone masonry
required in the construction of a railroad is usually classified about
as follows: first-class masonry, second-class masonry, rubble masonry
(sometimes culled third-class masonry, §209), rubble masonry laid
dry (§ 214), stone paving, slope-walls, and riprap. First-class ma-
sonry ia equivalent to ashlar (§§ 200—7);. this head generally includes
bridge abutments and piers of the larger class, and arch culverts of
greater spun than 10 foot. Sometimes second-class masonry is speci-
fied us squared-Btone masonry (§§ 308-12), and sometimes as superior
rubble (§§ 21IM.7); it IB used in less important structures than first-
class masonry,
Frequently specifications recognize also the following classifica-
ESTIMATES OF COST. 153
tion : first-class arch masonry, second-class arch masonry, first-class
bridge-pier masonry, second-class bridge-pier masonry, and pedestal
masonry. The quality of work thus specified is the same as for first-
class and second-class masonry respectively, the only difference
being peculiar to the form of the masonry structure, as will be dis-
cussed in succeeding chapters. The specifications for each structure
should give the quantities of each kind of masonry.
For complete specifications for railroad masonry, see Appendix I.
226. ESTIMATES OF COST OF MASONRY. The following estimates
of the cost of masonry, from Trautwine's Engineer's Pocket-look,*
are pronounced by experts to be as accurate as such averages can
be stated, since every item is liable to great variation. The estimates
are based on the assumption that a mason receives $3.50 and a
laborer $2.00 per day of 8 hours.
227. "Quarrying. After the preliminary expenses of purchas-
ing the site of a good quarry, cleaning off the surface earth and
disintegrated top rock, and providing the necessary tools, trucks,
cranes, etc., the total net expenses for getting out the rough stone
for masonry ready for delivery may be roughly estimated thus :
Stones of such size as two men can readily lift, measured in piles,
will cost per cubic yard from i to \ the daily wages of a quarry
laborer. Large stones, ranging from \ to 1 cubic yard each, got out
by blasting, from 1 to 2 daily wages per cubic yard. Larger stones,
ranging from 1 to 1|- cubic yards each, in which most of the work
irmst be done by wedges in order that the individual stones shall
come out in tolerably regular shape and conform to stipulated dimen-
sions, from 2 to. 4 daily wages per cubic yard. The lower prices are
low for sandstone, while the higher ones are high for granite. Under
ordinary circumstances, about 1£ cubic yards of good sandstone can
be quarried at the same cost as 1 of granite — or, in other words,
calling the cost of granite 1, that of sandstone will be f ; hence the
means of the foregoing limits may be regarded as rather full prices
for sandstone, rather scant for granite, and about fair for limestone
or marble.
228. "Dressing. In the first place, a liberal allowance should
be made for waste. Even Avhen the stone wedges out handsomely
on all sides in large blocks of nearly the required shape and size,
* Published by permission.
154 STOKE MASOKRY. [CHAP. VII.
from -J- to i of the rough block will generally not more than cover
waste of dressing. In moderate-sized blocks (say averaging about
^ a cubic yard each) got out by blasting, from i to £ will not be
too much for stone of medium, character as to straight splitting.
The last allowance is about right for well-scabbled dressing. The
smaller the stones the greater must be the allowance for waste. In
large operations it becomes expedient to have the stones dressed,, as
far as possible, at the quarry, in order to diminish the cost of trans-
portation, which, when the distance is great, constitutes an impor-
tant item — especially when by land and on common roads.
229. " Ashlar. Average size of the stones, say 5 feet long, 2
feet wide, and 1.4 feet thick — or two such stones to a cubic yard.
Then, supposing the stone to be of granite or gneiss, the cost per
cubic yard of ashlar facing will be :
"Getting out the stone from the quarry by "blasting, allow-
ing i for waste in dressing, 1£ cubic yards at $3.00
per yard, $4 00
Dressing 14 sq. ft. of face at 35 cents, 4 90
Dressing 52 sq. ft. of "beds and joints at 18 cents, ... 9 36
Net cost of the dressed stone at the quarry, . . . $18 26
Hauling (say 1 mile), loading, and unloading, * .... 1 20
Mortar, say, 40
Laying, including scaffold, hoisting machinery, etc., . 2 00
ISTet cost $21 86
Profit to contractor, say 15 per cent. , 3 28
Total cost per cubic yard, $25 14
" Dressing will cost more if the faces are to be rounded or
moulded. If the stones are smaller than we have assumed, there
will be more square feet per cubic yard to be dressed. If, in the
foregoing case, the stones be perfectly well dressed on all sides, in-
cluding the back, the cost per cubic yard would be increased about
$10; and if some of the sides be curved, as in arch stones, say $12
or $14; and if the blocks be carefully wedged out to given dimen-
sions, $16 or $18. Under these conditions the net cost of the
dressed stone at the quarry will be $28, $31, and $35 per cubic yard,
respectively.
"If the stone be sandstone with good natural beds, the getting
out may be put at $3.00 per cubic yard. Face dressing at 26 cents
MARKET PRICE OF STOKE. 155
per sq. ft,, say $3.64 per cu. yd. Beds and joints at 13 cents per
sq. ft., say $6.76 per cu. yd. The total cost, then, is $19.55 instead
of $25.14 for granite, and the net cost $17.00 instead of the $21.86
per cu. yd. for granite. The total cost of large, well-scabbled, ranged
sandstone masonry in mortar may be taken at about $10 per cu. yd.
230. " Eubble. With stones averaging about \ cubic yard each,
and common labor at $1 per day, the cost of granite rubble, such
as is generally used as backing for the foregoing ashlar, will be about
as follows :
Getting out the stone from the quarry by blasting, allow-
ing \ for vaste in scabbling, 1-| cu. yds. @ $3.00, . $3 43
Hauling 1 mile, loading and unloading, 1 20
Mortar (2 cu. ft., or 1.6 struck bushels of quicklime, and
10 cu. ft. or 8 struck bushels of sand or gravel, and
mixing), 1 50
Scabbling, laying, scaffolding, hoisting machinery, etc., 2 50
Net cost, $8 63
Profit to contractor, say 15 per cent., 1 30
Total cost per cubic yard, $9 93
ee Common rubble of small stones, the average size being such as
two men can handle, costs to get it out of the quarry about 80 cts.
per yard of pile, or, to allow for waste, say $1.00. Hauling 1 mile,
$1.00. It can be roughly scabbled and laid for $1. 20 more. Mortar,
as above, $1.50. Total net cost, $4.70; or with 15 per cent, profit,
$5.40, at the above wages for labor."
231. MARKET PRICE or STONE. The average market quotations
to builders and contractors for the year 1888 were about as follows,
f.o.l. (free on board) at the quarry :
Granite— rough, $0 40 to $0 50 per cubic foot.
Limestone — common rubble, ... 1 00 " 1 50 per cubic yard.
good range rubble, . , 1 50 " 200 " "
" bridge stone, .... 08 " 10 per cubic foot.
" dimension stone, ... 25 " 35 " f< ff
copings, 20 " 35 " "
Sandstone, 35 " 1 00 per cubic yard.
232. ACTUAL COST. In U. S. Public Buildings. The following
table gives the average contract price during the past few years for
cutting the stone for the United States government buildings : *
* American Architect, vol. xxii. pp. 6, 7.
STOKE MASOBTBY.
.
TABLE 15.
[CHAP,
„
KIND OF SURFACE.
Beds and joints, per sq. ft.
Pean-hammered,
Plain face, 6-cut,
« ** 8-cut,
*« " 10-cut,
«* u 12-cut,
Rubbed,
Tooled,
:
...- —
GRANITE.
MARBLE.
LIMESTONE AND
SANDSTONE.
Min.
$0 30
45
Max.
$0.85
50
65
75
QQ
Min.
$0 20
30
Max.
$0 25
35
Min.
$0 12
15
Max.
|0 15
20
OO
1 1
4
5
20
25
___—————
25
30
.
- —
price for the masonry of
t,eTJaited States
IN U.
VJUS3JL VJ? *f*.**^
KIND OF WORK.
fPLACE.
OATE.
COST
PER
FT,
, —
Random rubble, limestone • • ;
larrisburg, Va...-
Cincinnati, O
1885
1884
1883
1886
1885
1885
1884
1886
1886
1886
1886
1885
1885
1886
1886
issr
issr
issr
issr
188
188
188
188
188
0 20
20
20
35
60
70
68
30
1 3&
1 60
2 00
1 5£
1 65
1 00
2 50
85
7$
1 91
2 12
1 87
2 n
2 41
2 00
2 4.6
i m
2 27
3 00
""
-
Pittsburgh, Pa
« " . . . .
Squared masonry, sandstone - • -
Columbus, 0
Memphis, Tenn.. .
Pittsburgh, Pa. . .
t( "...
«' " . . .
Fort Wayne, Ind -
a tt tt
Memphis, Tenn. .
Dallas, Tex
Coursed masonry, sandstone • • • •
Squared masonry, limestone
* « " granite
Bock-face ashlar,^ ^^egranlte, avg
s^JSSsKSBfi^si;:;
Dressed coping f ished oniy
"WMte sandstone, — IUIU.IHJJ-VU. v ^ j
^A^M^n^oi&^^
Denver, Col. ... - - •
Council Bluffs, la
« *«
t( <t (t
, Rochester, N. T. .
l{ tc « limestone, lowest bid
(t (( n «i average bid —
Rock-face asWar, cut and moulded trim
•miners Middlesex orownsionu
Cut ^moulded, Bedford limestone -
(Louisville, Ky....
.(Dallas, Tex
. Hannibal, Mo
DCS Monies, la. . .
181*
188
188
tt ti (t sandstone, *
., „ tt granite, superstructure
..Pittsburgh, Pa,...
ACTUAL COST. 157
233. Eailroad Masonry. The following are the average prices
actually paid in the construction of the Cincinnati Southern Eail-
road, in 1873-77:*
First-class bridge masonry, per cu. yd., $10 39
Second-class bridge masonry, in cement, per cu. yd., . . 7 40
Second-class bridge masonry, dry, per cu. yd., a ... 7 02
First-class arch masonry, per cu. yd., 11 24
Second-class arch masonry, in cement, per cu. yd., ... 8 61
Second-class arch masonry, dry, per cu. yd., 775
Brick- work in tunnels, per cu. yd., 8 50
Brick-work in buildings, per cu. yd., 7 00
Box-culvert masonry, in cement, per cu. yd., 4 89
Box-culvert masonry, dry, per cu. yd., 4 32
Concrete, per cu. yd., 5 52
Slope walls, per cu. yd., 4 41
Stone paving, per cu. yd. , 2 41
234. Tunnel Masonry. The following are the average pricesf
paid in 1883-87 on the new Croton Aqueduct tunnel which supplies
New York City with water. The mortar was 2 sand to 1 Eosendale
cement.
Dimension-stone masonry (granite), $42 50
Brick-work lining, per cu. yd., 10 14
Brick-work backing, per cu. yd., 8 49
Bubble masonry, lining, per cu. yd 5 05
Concrete lining, 3 stone to 1 Rosen dale cement, per cu. yd., 5 67
Concrete lining, 5 stone to 1 Rosendale, per cu. yd., . . 5 16
Concrete backing, 3 stone to 1 Rosendale, per cu. yd., . 4 73
Concrete backing, 5 stone to 1 Rosendale, per cu. yd., . 4 22
Fine-hammered face (6-cut) for cut stone, per sq. ft., . . 84
Rough-pointed face for cut stone, per sq. ft., .... 50
Additional for all kinds of masonry laid in Portland
cement mortar, 2 to 1, per cu. yd., 1 78
Additional for all kinds of masonry laid in Rosendale
cement mortar, 1 to 1, per cu. yd., 1 20
235. Bridge-pier Masonry. The following are the details of the
cost, to the contractor, of heavy first-class limestone masonry for
bridge-piers erected in 1887 by a prominent contracting firm :
* Report of the Chief Engineer, December 1, 1877, Exhibit 3.
t Report of the Commissioners, Table 4.
158
STOKE MASOHRY.
[CHAP.
Cost of stone (purchased),
Sand and cement, .
Freight, . . • • '
Laying, . - • •• '
Handling materials,
,$4 50
52
. 1 79
. 1 40
65
40
Total cost per cubic yard, . - •
The following data concerning *e cos
fifths cut-stoae acing and tin"
by the same firm. I*"
of ffranite piers
backing-are
tough.
ling opening quarry, ..•••'' 6 75
^uavr^jL^S' *" — .•••*'" 1 w
Cutting to dimensions, . • ..-••' l /O
S2^^.'^-i^^^.^
*"' •••'"' . . .$1431
Backing :-
Quarrying,
Dressing,
Laying,
Sundries,
Total cost per cubic yard, .
Total cost per cubic yard,
The first-class limeston'
— «• t ; rt 4- T^K
. $3 10
a co
. 1 75
. a os
. $10 50
across the Missoun at
°
the piers of the bridges
gjgo) cost the company
**> engineering expenses,
onry in — er piers usually
rfrom $12 to »U per cubic > yard. .n
At Ohieago in 1387 thecontrac pncet i ^
and abutments was .bou as foHov.
t, 8
Eosendale
ACTUAL COST.
159
built in 1887. Scale of wages per day of 10 hours — foreman,,
$3.50 ; cutters, $3.00 ; mortar mixer, $1.50 ; laborer, $1.25 ; water-
boy, 50 cents ; carpenters, $2.50. f
TABLE 17.
ACTUAL COST OF ARCH MASONRY ON INDIANAPOLIS, DECATUB AND SPRING-
FIELD RAILROAD;
ITEMS.
Total.
Per
cu. yd.
Materials : —
Stone — 613 cu. yds. of sandstone @ $1 50
$919 50
$1 50
Cement—ISO bbls. German Portland @, $3 17 = $412 50
40 " English " @ 3 25 = 130 00
30 " Louisville " @ 96 = 28 75
571 25
94
Sand — 7 car-loads @ $5 50
38 50
06
Total for materials
$1.529 25
$2 50
Cutting : —
Cutters and helpers
$1,370 48
$2 24
Templates, bevels, straight-edges, etc
11 00
01
Repairs of cutters' tools
52 39
0&
Water-boy
11 75
02-
Total for cutting
$1,445 62
$2 36-
Laying : —
Masons, 110 days @. $3.50
$384 87
$0 63
Masons' helpers
453 66
74
Mortar mixer
121 72
20
Water-boy
11 75
02
Arch centers, building and erecting
37 65
06
Derrick, stone chute, etc
14 63
02
Laying track
7 70
01
Total for laying
$1 032 08
$1 6S
Pointing
$30 00
$0 05
GRAND TOTAL :
Total for labor
$2,507 60
$4 09
Total for materials
1,529 25
2 50
Total cost of masonry
$4,036 85
$6 59
COST.
238. Summary of Cost. The following table, compiled from a
large amount of data, will be convenient for hasty reference. Of
course any such table must be used with caution, since such items
are subject to great variation.
t Data furnished by Edwin A. Hill, chief engineer.
160
STOJSTE MASONRY.
[CHAP. vir.
TABLE 18.
SUMMARY OF COST OF MASONRY.
DESCRIPTION OP MASONRY.
COST PER CUBIC YARD.
Min.
Max. Average.
Arch masonry, first-class. . . ' $7 OOj
Arch masonry, second-class (in cement) 5 00
Box-culvert masonry, in cement 2 50
Brick masonry (see § 258) 6 00
Bridge masonry, first-class 10 00
Bridge masonry, second-class (in cement) 6 00
Concrete 2 50
Coping 8 00
Dimension-stone masonry, granite 40 00
Paving 1 00
Slope-wall masonry 2 00
Squared-stone masonry ; 6 00
Kiprap 1 00
Eubble, first-class 4 00
Bubble, second-class (in cement) 2 00
$12 00
10 00
5 00
10 00
20 00
12 00
6 00
14 00
60 00
4 00
5 00
10 00
2 50
6 00
5 00
110 00
8 00
3 50
8 00
14 00
10 00
4 00
12 00
50 00
2 00
3 00
7 00
1 50
5 00
3 00
CHAPTER VIII.
BRICK MASONRY.
239. MORTAR. Lime mortar is generally employed for brick
masonry, particularly in architectural constructions. Many oi tht*
leading railroads lay all brick masonry in cement mortar, and in**
practice should be followed more generally. The weakest part ol
•a brick structure is the mortar. The primary purpose oi tho
mortar is to form an adhesive substance between the hriek.s ; tin*
second is to form a cushion to distribute the pressure uniformly
over the surface. If the mortar is weaker than the briek* thn
ability of the masonry to resist direct compression is thereby r<m-
.siderably reduced, For the reason, see §9; for the amount,, Ht*o
the Table 19, page 164.
If the strains upon a wall were only those arising from a dir<*rt
pressure, the strength of the mortar would in most CUHOH !x* of
•comparatively little importance, for the crushing* strength of avt*r-
,age quality mortar is far higher than the dead load which un«l**r
•ordinary circumstances is put upon a wall ; but, as a matter of fu*»t,
in buildings the load is rarely that of a direet crush in# weight *
•other and more important strains being developed by the BjHteiu of
•construction. Thus the roof tends to throw the walls out, tho raf tm*i4
being generally so arranged as to produce a considerable otiiwairtt
thrust against the wall. The action of the wind also prod ueen a mi!«<
.strain which is practically of more importance than. oiUu*r of thi*
•others. In many cases the contents of a building exert an outwurtt
thrust upon the walls ; for example, barrels piled against the j-u<l«M
•of a warehouse produce an outward pressure against the wulln.
In many brick constructions the use of cement mortar is U)KS<>»
lately necessary — as, for example, in tall chimneys,, where the hfiir-
ing is so small that great strength of the cementing material t*
required.
240. The thickness of the mortal*- joints should bo about | to |
-of an inch. Thicker joints are very common, but should, be avoitU»ti.
If the bricks are even fairly good, the mortar is the weaker part of
101
162 BRICK MASOXRY. [CHAP. VIII,
the wall ; hence the less mortar the better. Besides, a thin layer
of mortar is stronger under compression than, a thick one (see § 14).
The joints should be as thin as is consistent with their insuring a uni-
form bearing and allowing rapid work in spreading the mortar. The
joints of outside walls should be thin in order to decrease the dis-
integration by weathering. The joints of insid.e walls are usually
made from f to i inch thick.
Brick should, not be merely laid, but every one should be rubbed
and pressed down in such a manner as to force the mortar into the
pores of the bricks and produce the maximum adhesion ; with quick-
setting cement this is still more important than with lime mortar.
For the best work it is specified that the brick shall be laid with a
" shove joint f that is, that the brick shall first be laid so as to
project over the one below,, and be pressed into the mortar, and
then be shoved into its final position.
Lime mortar is liable to work out of the joints, owing to the-
action of the elements and to changes of temperature. Hence it-
is customary either (1) to lay the face in mortar containing more-
lime than that used for the interior,, or (2) to lay the
face in a mortar containing more or less cement, or
(3), in rare cases, to point the joints with neat cement
mortar. Whatever the kind of mortar used, the finish
of the face of the joint is important. The most
FIG. 47. durable joint is finished as shown in Fig. 47, although,
unfortunately for durability, it is customary to make the slope in
the opposite direction.
241. Since brick have great avidity for water, it is best to-
dampen them before laying. If the mortar is stiff and the brick
dry, the latter absorb the water so rapidly that the mortar does,
not set properly, and will crumble in the fingers when dry. Neglect-
in this particular is the cause of most of the failures of brick-work.
Since an excess of water in the brick can do no harm, it is best to
thoroughly drench them with water before laying. Lime mortar is-
sometimes made very thin, so that the brick will not absorb all the
water. This process interferes with the setting of the mortar, and
particularly with the adhesion of the mortar to the brick. Watery
mortar also contracts excessively in drying (if it ever does dry),
which causes undue settlement and, possibly, cracks or distortion,
Wetting the brick before laying will also remove the dust from the-
surface, which otherwise would prevent perfect adhesion.
BOND.
163
1
1 " ' 1
1
1 1 1
1
1 1 1
1
i 1
1
1 1 1 1
1 1 1
1
1 1
1
1 I 1 1
I 1 L
1
1 1
1
I 1 1 1
1
II II
1
1 1
1
1 1 1 1
1
II II
1
1 1
. 48.— ENGLISH BOND.
242. BOND. The bricks used in a given wall being of uniform
size are laid according to a uniform system, which is called the bond
of the brick-work. As in ashlar masonry, so in brick -work, a header
is a brick whose length lies perpendicular to the face of the wall;
and a stretcher is one whose length lies parallel with the face..
Brick should be made of such a size that two headers and a mortar-
joint will occupy the same length as a stretcher.
243. English Bond. This consists in laying entire courses of
headers and stretchers, which some-
times alternate, as in Fig. 48; but
generally only one course of headers
is laid for every two, three, four, etc.,
courses of stretchers. ' In ordinary
practice the custom is to lay four to six
courses of stretchers to one of head-
ers. The stretchers bind the walls
together lengthwise ; the headers, crosswise. The proportionate
numbers of the courses of headers and stretchers should depend on
the relative importance of transverse and longitudinal strength.
The proportion of one course of headers to two of stretchers is that
which gives equal tenacity to the wall lengthwise and crosswise.
In building brick-work in English bond, it is to be borne in
mind that there are twice as many vertical or side joints in a course
of headers as there are in a course of stretchers ; and that unless
in laying the headers great care be taken to make these joints very
thin, two headers will occupy a little more space* than one stretcher,
and the correct breaking of the joints — exactly a quarter of a brick —
will be lost. This is often the case in carelessly built brick- work, in
which at intervals vertical joints are seen nearly or exactly above
each other in successive courses. -
244. Flemish Bond. This consists of a header and a stretcher
alternately in each course, so placed
that the outer end of each header
lies on the middle of a stretcher in
the course below (Fig. 49). The
number of vertical joints in each
course is the same, so that there is no
risk of the correct breaking of the
joints by a quarter of a brick being
lost; and the wall presents a neater appearance than one built in
1 1
1 I
1 1
1 1
1 1
1 1
1
1.
1 1
1 I
1 1
1 1
1 1
1 1
1 1
1 1
1 f
1 1
1 1
1 1
1 1
1 1
, I I
1 1
1 1
FIG. 49.— FLEMISH BOND.
164
BRICK MASOJSTBY.
[CHAP. vin.
English bond. The latter, however, when correctly built, is
stronger and more stable than Flemish bond.
245. Hoop-iron Bond. Pieces of hoop-iron are frequently laid
fiat in the bed-joints of brick-work to increase its longitudinal
tenacity, about 2 inches of the ends of each piece being bent down
and inserted into the vertical joints. Although thin strips of iron
are generally employed, it would be better to use thicker pieces ; the
value of the iron for this purpose depends wholly upon the rigidity
of the ends which are turned down, and this will vary about as
the square of the thickness. The strip of iron should be nearly
as thick as the mortar-joint. This means of strengthening masonry
is frequently employed over openings and to connect interior brick
walls with stone fronts.
246. COMPBESSIVE STRENGTH OF BEICK MASONRY. Experi-
ments at Water-town, Mass., with the United States testing-machine,
upon piers 12 inches square and from 1 ft. 4 in. to 10 ft. high, gave
results as follows :*
TABLE 19.
STRENGTH OF BRICK MASONRY COMPARED WITH THAT OF THE BRICK AND
THE MORTAR.
£
g
i
1
1
2
3
4
5
6
7
COMPOSITION OF THE MORTAK.
NUMBER OF EXPERIMENTS.
ULTIMATE STRENGTH OF THE PIBR
IN LBS. PER SQ INCH.
STRENGTH OF THE MORTAR (6-iNcn
CUBES CRUSHED BETWEEN STEEL)
IN LBS. PER SQ. IN. MEAN OF
THREE TRIALS.
STRENGTH OF THE
PIER IN TERMS
OF THE STRENGTH
OF THE BRICK.
STRENGTH OF THE PIER IN TERMS OF j
THE STRENGTH OF THE MORTAR. {
Min.
Max.
Mean.
1 lime., 3 sand
15
1
1
1
8
1,508
1,646
1,411
1,972
2,544
124
183
192
162
545
521
3,483
.06
.18
.10
.11
.09
.13
.17
12
9
7
12
4.7
2 mortar (1 lime, 3 sand), 1 Rosen-
dale cement
2 mortar (1 lime, 3 sand), 1 Port-
land cement
1 Rosendale cement, 2 sand
1 Portland cement, 2 sand
.10
.27
Clear Rosendale
Clear Portland cement
1
2,375
.16
0.7
*Report on « Tests of Metols, etc.," for the year ending June 30, 1884, pp. 69-122.
COMPKESSIVE STRENGTH. 165
The brick had an average strength of nearly 15,000 Ibs. per sq,
in., tested flatwise between steel. The mortar was 14£ months old
when it was tested. The piers were built by a common mason, with
only ordinary care; and they were from a year and a half to two
years old when tested. Their strength varied with their height;
and in a general way the experiments show that the strength of a
prism 10 ft. high, laid in either lime or cement mortar, is about two
thirds that of a 1-foot cube. A deduction derived from so few
experiments (22 in all) is not, however, conclusive. The different
lengths of the piers tested occurred in about equal numbers. The
piers began to show cracks at one half to two thirds of their ultimate
strength.
In attempting to draw conclusions from any experiments, it
must be borne in mind continually that the result of a single trial
may possibly be greatly in error. In this case this precaution is
very important, since the difference between experiments apparently
exactly alike was in some cases as much as 50 per cent. A great
variation in the results is characteristic of all experiments on stone,
brick, mortar, etc. Except on the ground of a variation in ex-
periments, it is difficult to explain why mortar No. 4 is weaker than
No. 2, while the masonry is stronger ; or why the masonry of No. 5
is stronger than that of No. 7.
Of course the apparent efficiency of the masonry, as given in the
table, depends upon the manner in which the strengths of the
brick and mortar were determined, as well as upon the method of
testing the masonry. For example, if the brick had been tested on
end the apparent efficiency of the masonry would have been con-
siderably more ; or if the mortar had been tested in thin sheets the
strength of the masonry relative to that of the mortar would not
have been so great.*
247. Some German experiments! gave results as in the table
* It should be mentioned that the mortar with which these piers were built appears
to be much weaker than similar mortar under like conditions. (Compare page 72,
and pages 126, 166, 188, 197 of the Report of Tests of Metals, etc., made at Watertown
in 1884.) Ordinarily, mortar is eight to ten times as strong in compression as in
tension, whereas the first six mortars in the preceding table were but little stronger
in compression than such mortar should have been in tension. The officer in charge
is u unable to offer any explanation. The cement was bought on the market; the
maker's name is not known. The cement was not tested." However, the experi-
ments are consistent with themselves, and therefore show relative strengths correctly,
t Van Nostrand's Engin'g Mag., vol. xxxiv. p. 240, from the Abstracts of the
Inst. of C. E. (London).
166
BRICK MASONRY.
[CHAP. viii.
below. It is not stated how the strength of the brick or of the
masonry was determined. The term cement in the table refers .to
Portland cement. According to the building regulations of Berlin,
the safe load for brick masonry is less than one tenth of the results
in the table.
TABLE 20.
RELATIVE STRENGTH: OF BRICK AND BRICK MASONRY.
KIND OF BRICK.
AVERAGE CRUSH-
ING STRENGTH
OF BRICK, IN LBS.
PER SQ. IN.
ULTIMATE STRENGTH, IN LBS. PER SQ. IN.. OF
BRICK-WORK WITH MORTAR COMPOSED OF—
1 Lime,
2 Sand.
7 Lime,
1 Cement,
16 Sand.
1 Cement,
(5 Sand.
1 Cement,
3 Sand.
Ordinary stock ........
2,930
3,669
5,390
2,617
1,195
2,759
ie masonry in
Df the brick. . .
1,290
1,620
2,870
1,150
530
1,210
1,390
1,760
2.590
1,250
570
1,320
1,610
2,020
2,960
1,440
650
1,520
1,850
2,320
3,410
'1,650
750
1,710
Selected "
Clinker fi
Porous •
Porous perforated
Perforated
Average strength of t
terms of the strength
0.44
0.48
0.55
0.63
Both of the preceding series of experiments show conclusively
that the strength of brick masonry is mainly dependent upon the
strength of the mortar. An increase of 50 per cent, in the strength
of the brick shows no appreciable effect on the strength of the ma-
sonry. Notice, however, that the masonry in the fifth line of Table
19 is 70 per cent, stronger than that in the first, due to the dif-
ference between a good Portland cement mortar and the ordinary
lime mortar. In the second table notice that brick laid in a 1 to 3
Portland cement mortar is nearly 50 per cent, stronger than in a 1
to 2 lime mortar. Similar experiments* show that masonry laid in
mortar composed of 1 part Rosendale cement and 2 parts sand is 56
per cent, stronger than when laid in mortar composed of 1 part
lime and 4 parts sand. A member of the Institute of Civil- Engi-
neers (London) saysf that brick-work laid in lime is only one fourth
as strong as when laid in clear Portland cement. Probably the dif-
ference in durability between cement mortar and lime mortar is
considerably greater than their difference in strength.
* Report of Experiments on Building Materials for the City of Philadelphia with
the U. S. testing-machine at Watertown, Mass., pp. 32, 33.
T Proc. Inst. of C. E., vol. xvii- p. 441.
TBASTSVERSE STKEKGTH. 167
248. Pressure allowed in Practice. The pressure at the base of
a "brick shot-tower in Baltimore, 246 feet high,, is estimated at 6-J-
tons per sq. ft. (about 90 Ibs. per sq. in.). The pressure at the base
of a brick chimney at Glasgow, Scotland,, 468 ft. high, is estimated
.at 9 tons per sq. ft. (about 150 Ibs. per sq. in.); and in heavy gales
this is increased to 15 tons per sq. ft. (210 Ibs. per sq. in. ) on the
leeward side. The leading Chicago architects allow 10 tons per sq.
ft. (140 Ibs. per sq. in.) on the best brick-work laid in 1 to -2 Port-
land cement mortar ; 8 tons for good brick-work in 1 to 2 Eosendale
cement mortar ; and 5 tons for ordinary brick- work in lime mortar.
Ordinary brick piers have been known to bear 40 tons per sq. ft.
(560 Ibs. per sq. in.) for several days without any sign of failure.
Tables 19 and 20 appear to show that present practice is very
conservative with regard to the pressure allowed on brick masonry.
According to Table 19 (page 164), the ultimate strength of the best
brick laid in ordinary lime mortar is 110 tons per sq. ft. ; if laid
in 1 to 2 Portland cement mortar, 180 tons ; and by Table 20 (page
166) the strength of ordinary brick in 1 to 2 lime mortar is 100 tons
per sq. ft., and in 1 to 3 Portland cemerjt mortar 140 tons. Prom
the above, it would seem that reasonably good brick laid in good
lime mortar should be safe under a pressure of 20 tons per sq. ft.,
and that the best brick in good Portland cement mortar should be safe
under 30 tons per sq. ft. The nominal pressure allowed upon brick
masonry depends upon the kind of materials employed ; the degree of
oare with which it is executed ; whether it is for a temporary or per-
manent, an important or unimportant structure ; and, it may be
added, the care with which the nominal maximum load is estimated.
249. TEANSVEESE STEENGTH OF BEICK MASONEY. Masonry is
seldom employed where any strain except direct compression will
come upon it, but sometimes it is subject to transverse strain. The
transverse strength of brick-work depends theoretically upon the
tensile strength of the binck and upon the adhesion and cohesion
of the mortar, but practically the strength of the mortar deter-
mines the strength of the masonry. For example, in the case of
a high wall whose upper portion is overthrown by a lateral force or
pressure of any kind, the failure is due either (1) to the breaking of
the adhesion in the bed-joints and of the cohesion of the side-joints,
or (2) to the rupture " of the mortar in the bed-joints alone. The
latter method of failure, however, is improbable, since the cohesion
166
BRICK MASONRY.
[CHAP. YIII.
below. It is not stated how the strength of the brick or of the
masonry was determined. The term cement in the table refers .to
Portland cement. According to the building regulations of Berlin,
the safe load for brick masonry is less than one tenth of the results
in the table.
TABLE 20.
RELATIVE STRENGTH OF BRICK AND BRICK MASONRY.
KIND OP BRICK.
AVERAGE CRUSH-
ING STRENGTH
OP BRICK, IN LBS.
PER SQ. IN.
ULTIMATE STRENGTH. IN LBS. PER SQ. IN., OF
BRICK-WORK WITH MORTAR COMPOSED OF—
1 Lime,
2 Sand.
7 Lime,
1 Cement,
16 Sand.
1 Cement,
(5 Sand.
1 Cement,
3 Sand.
Ordinary stock
2,930
3,669
5,890
2,617
1,195
2,759
ae masonry in
Df the brick...
1,290
1,620
2,370
, 1,150
530
1,210
1,390
1,760
2.590
1.250
570
1,320
1,610
2,020
2,960
1,440
650
1,520
1,850
2,320
3,410
'1,650
750
1,710
Selected "
Clinker ' *
Porous
Porous perforated
Perforated
Average strength, of t
terms of the strength
0.44
0.48
0.55
0.63
Both of the preceding series of experiments show conclusively
that the strength of brick masonry is mainly dependent upon the
strength of the mortar. An increase of 50 per cent, in the strength
of the brick shows no appreciable effect on the strength of the ma-
sonry, Notice, however, that the masonry in the fifth line of Table
19 is 70 per cent, stronger than that in the first, due to the dif-
ference between a good Portland cement mortar and the ordinary
lime mortar. In the second table notice that brick laid in a 1 to 3
Portland cement mortar is nearly 50 per cent, stronger than in a 1
to 2 lime mortar. Similar experiments* show that masonry laid in
mortar composed of 1 part Bosendale cement and 2 parts sand is 56
per cent, stronger than when laid in mortar composed of 1 part
lime and 4 parts sand. A member of the Institute of Civil- Engi-
neers (London) saysf that brick-work laid in lime is only one fourth
as strong as when laid in clear Portland cement. Probably the dif-
ference in durability between cement mortar and lime mortar is
considerably greater than their difference in strength.
* Report of Experiments on Building Materials for the City of Philadelphia with
the U. S. testing-machine at Watertown, Mass., pp. 32, 33.
T Proc. Inst. of C. E., vol. xvii. p. 441.
TRANSVERSE STRENGTH. 167
248. Pressure allowed ill Practice. The pressure at the base of
a "brick shot-tower in Baltimore, 246 feet high, is estimated at 6£
tons per sq. ft. (about 90 Ibs. per sq. in.). The pressure at the base
-of a brick chimney at Glasgow., Scotland, 468 ft. high, is estimated
at 9 tons per sq. ft. (about 150 Ibs. per sq. in.); and in heavy gales
this is increased to 15 tons per sq. ft. (210 Ibs. per sq. in. ) on the
leeward side. The leading Chicago architects allow 10 tons per sq.
ft. (140 Ibs. per sq. in. ) on the best brick-work laid in 1 to 2 Port-
land cement mortar ; 8 tons for good brick-work in 1 to 2 Eosendale
cement mortar ; and 5 tons for ordinary brick- work in lime mortar.
Ordinary brick piers have been known to bear 40 tons per sq. ft.
(560 Ibs. per sq. in.) for several days without any sign of failure.
Tables 19 and 20 appear to show that present practice is very
conservative with regard to the pressure allowed on brick masonry.
According to Table 19 (page 164), the ultimate strength of the best
brick laid in ordinary lime mortar is 110 tons per sq. ft. ; if laid
in 1 to 2 Portland cement mortar, 180 tons ; and by Table 20 (page
166) the strength of ordinary brick in 1 to 2 lime mortar is 100 tons
per sq. ft., and in 1 to 3 Portland cemerjt mortar 140 tons. From
the above, it would seem that reasonably good brick laid in good
lime mortar should be safe under a pressure of 20 tons per sq. ft.,
and that the best brick in good Portland cement mortar should be safe
under 30 tons per sq. ft. The nominal pressure allowed upon brick
masonry depends upon the kind of materials employed ; the degree of
care with which it is executed ; whether it is for a temporary or per-
manent, an important or unimportant structure ; and, it may be
added, the care with which the nominal maximum load is estimated.
249. TRANSVERSE STRENGTH OF BRICK MASONRY. Masonry is
seldom employed where any strain except direct compression will
oome upon it, but sometimes it is subject to transverse strain. The
transverse strength of brick-work depends theoretically upon the
tensile strength of the brick and upon the adhesion and cohesion
of the mortar, but practically the strength of the mortar deter-
mines the strength of the masonry. For example, in the case of
a high wall whose upper portion is overthrown by a lateral force or
pressure of any kind, the failure is due either (1) to the breaking of
the adhesion in the bed-joints and of the cohesion of the side-joints,
or (2) to the rupture ' of the mortar in the bed-joints alone. The
latter method of failure, however, is improbable, since the cohesion.
166
BEICK MASONRY.
[CHAP. TUT.
below. It is not stated how the strength of the brick or of the
masonry was determined. The term cement in the table refers .to
Portland cement. According to the building regulations of Berlin,
the safe load for brick masonry is less than one tenth of the results
in the table.
TABLE 20.
RELATIVE STEENGTH OF BEICK AND BEICK MASONRY.
.KIND OF BRICK.
AVERAGE CRUSH-
ING STRENGTH
OF BRICK, IN LBS.
PER SQ. IN.
ULTIMATE STRENGTH, IN LBS. PER SQ. IN.. OF
BRICK-WORK WITH MORTAR COMPOSED OF —
1 Liine,
2 Sand.
7 Lime,
1 Cement,
16 Sand.
1 Cement,
0 Sand.
1 Cement,
3 Sand.
Ordinary stock
2,930
3,669
5,390
2,617
1,195
2,759
le masonry in
3f the brick. . .
1,290
1,620
2,370
, 1,150
530
1,210
1,390
1,760
2,590
1.250
570
1,320
1,610
2 020
2,9(50
1,440
650
1,520
1,850
2,320
3,410
• 1,650
750
1,710
Selected v*
Clinker ft
Porous
Porous perforated
Perforated
Average strength, of t
terms of the strength
0.44
0.48
0.55
0.63
Both of the preceding series of experiments show conclusively
that the strength of brick masonry is mainly dependent npon the
strength of the mortar. An increase of 50 per cent, in the strength
of the brick shows no appreciable effect on the strength of the ma-
sonry, Notice, however, that the masonry in the fifth line of Table
19 is 70 per cent, stronger than that in the first, due to the dif-
ference between a good Portland cement mortar and the ordinary
lime mortar. In the second table notice that brick laid in a 1 to 3
Portland cement mortar is nearly 50 per cent, stronger than in a 1
to 2 lime mortar. Similar experiments* show that masonry laid in
mortar composed of 1 part Eosendale cement and 2 parts sand is 56
per cent, stronger than when laid in mortar composed of 1 part
lime and 4 parts sand. A member of the Institute of Civil- Engi-
neers (London) saysf that brick-work laid in lime is only one fourth,
as strong as when laid in clear Portland cement. Probably the dif-
ference in durability between cement mortar and lime mortar is
considerably greater than their difference in strength.
* Report of Experiments on Building Materials for the City of Philadelphia with
the U. 8. testing-machine at Watertown, Mass., pp. 32, 33.
T Proc. Inst. of C. E., vol. xvii. p. 441.
TRANSVERSE STRENGTH. 167
248. Pressure allowed in Practice. The pressure at the base of
n brick shot-tower in Baltimore, 246 feet high, is estimated at 6£
tons per sq. ft. (about 90 Ibs. per sq. in.). The pressure at the base
-of a brick chimney at Glasgow, Scotland, 468 ft. high, is estimated
at 9 tons per sq. ft. (about 150 Ibs. per sq. in.); and in heavy gales
this is increased to 15 tons per sq. ft. (210 Ibs. per sq. in.) on the
leeward side. The leading Chicago architects allow 10 tons per sq.
ft. (140 Ibs. per sq. in. ) on the best brick-work laid in 1 to -2 Port-
land cement mortar ; 8 tons for good brick-work in 1 to 2 Eosendale
cement mortar ; and 5 tons for ordinary brick- work in lime mortar.
Ordinary brick piers haye been known to bear 40 tons per sq. ft.
(560 Ibs. per sq. in.) for several days without any sign of failure.
Tables 19 and 20 appear to show that present practice is very
conservative with regard to the pressure allowed on brick masonry.
According to Table 19 (page 164), the ultimate strength of the best
brick laid in ordinary lime mortar is 110 tons per sq. ft. ; if laid
in 1 to 2 Portland cement mortar, 180 tons ; and by Table 20 (page
166) the strength of ordinary brick in 1 to 2 lime mortar is 100 tons
per sq. ft., and in 1 to 3 Portland cement mortar 140 tons. From
the above, it would seem that reasonably good brick laid in good
lirne mortar should be safe under a pressure of 20 tons per sq. ft.,
and that the best brick in good Portland cement mortar should be safe
under 30 tons per sq. ft. The nominal pressure allowed upon brick
masonry depends upon the kind of materials employed ; the degree of
oare with which it is executed ; whether it is for a temporary or per-
manent, an important or unimportant structure ; and, it may be
added, the care with which the nominal maximum load is estimated.
249. TRANSVERSE STRENGTH OF BRICK MASONRY. Masonry is
seldom employed where any strain except direct compression will
oome upon it, but sometimes it is subject to transverse strain. The
transverse strength of brick-work depends theoretically upon the
tensile strength of the brick and upon the adhesion and cohesion
of the mortar, but practically the strength of the mortar deter-
mines the strength of the masonry. For example, in the case of
a high wall whose upper portion is overthrown by a lateral force or
pressure of any kind, the failure is due either (1) to the breaking of
the adhesion in the bed-joints and of the cohesion of the side- joints,
•or (2) to the rupture ' of the mortar in the bed-joints alone. The
latter method of failure, however, is improbable, since the cohesion.
168 BRICK MASOKRY. [CHAP.
of cement mortars is always much greater than their adhesion (com-
pare §§ 134 and 137); and hence, in estimating the resistance of the
wall to overturning, it becomes necessary to fix values for both the
cohesive and adhesive strength of the mortar at the time when the
structure is first exposed to the action of the lateral force or pres-
sure, and also to ascertain the relative areas of beds and side-joints
in the assumed section of rupture. In good brick-work the aggre-
gate area of the side- joints, in any section parallel to the beds, will
amount to about one seventh of the total area of such section.
Hence, when the masonry is liable to be subjected to transverse
strains the adhesive strength of the mortar is more important than,
its cohesive strength.
The adhesion of mortar to brick or stone has already been dis-
cussed (§ 137). While the experiments uniformly show a relatively
low adhesive power, it is well known that when old walls are de-
molished the adhesion of even common lime mortar is found to be
ver.y considerable. Although the adhesive power of mortar may be>
small as compared with its tensile strength, good brick masonry has
a considerable transverse strength.
Eleven old English experiments,* made in England in 1837, gave
an average resistance to flexure of 274 Ibs. per sq. in. for brick
cemented together with clear Portland cement, the minimum being
200 and the maximum 380. " "Weisbach, upon a basis entirely dif-
ferent from that employed in deducing the preceding results, con-
cludes that the resistance to flexure varies between 180 and 340 Ibs,
per sq. in."
250. Application. To illustrate the practical application of the
fact that brick-work has a transverse strength, let it be required to
compute the strain which may come upon a lintel, or girder used
to support a brick wall over an opening, f
Let H = the height, in feet, of the wall above the opening ;
Hm = the height, in feet, of the wall that produces a maxi-
mum strain on the lintel ;
H8 = the height, in feet, of the masonry when it will just-
support itself over the opening ;
S = the span, in feet ;
t = the thickness, in feet, of the wall ;
* Civil Engineer's and Architect's Jour., vol. i. pp. 30, 45, 102, 135.
t The principle of the following computations is from an editorial in jRbigineerin<y
(London), vol. xiv. pp. 44 and 72.
TRANSVERSE STRENGTH. 161)
R = the modulus of rupture, in pounds per square inch,,
of the brick-work;
W = the weight, in pounds, of a cubic foot of the walL
W varies from 100 to 140 pounds, and for conven-
ience is here assumed to be 144; the error is always
on the safe side.
Consider the masonry as a beam fixed at both ends and loaded
uniformly. Then, by the principles of the resistance of materials,
when the masonry is just self-supporting, one twelfth of the weight
of the wall above the opening multiplied by the span is equal to one
sixth of the tensile strength multiplied by the thickness and also the
square of the depth of the wall. The weight of the wall above the
opening is W S Hst, Hence
li(WBH.f)S = t(l4AK)tH.*,. ... (1)
or
02
* = 0 <*>
Notice that the weight of the wall over any given opening in-
creases as the height, while the resistance increases as the square of
the height. The height for which the masonry is self-supporting
is given by equation (2) ; for a height greater than H8 the masonry
would be more than self-supporting ; and for a height less than H9
the masonry would need extraneous support.
To find the relationship between the height of the wall that is
self-supporting and the height that produces the maximum strain
on the lintel, notice that, since the strength of the wall increases as
IP and the weight as //, the net resistance of the wall increases as
H. Consequently that portion of the wall which will be self-sup-
FT
porting can be represented by the --^- part of the entire weight, and
•H-s
the part that must receive extraneous support can be represented
CO" \
1 — -—] part of the entire weight. Since the weight of
jj.8 j
the wall over a given opening varies as the height, the weight to be
/ TT \
supported by the lintel is proportional to ( 1 — ••~-\Hm ; hence the
greatest strain on the lintel will occur when this expression is a
maximum, — i. e.} when Hm = ^ H8,
170 BEICK MASONRY. [CHAP. VIII.
Substituting this value of Hm in the above expression for the
CTT \
1 -- -~-}Hm y it becomes £ Hs. This shows that
JbLsJ
the maximum load on the lintel is equal to one quarter of the weight
of the self-supporting wall ; or, since Hm = |- Hs, the maximum
load on the girder is equal to one half of the weight of the entire
wall above the opening. Substituting this value of Hm in equation
(2), we have
........ <3>
Hence it appears that the height of the wall producing the niaxi-
(^2
mum strain on the lintel will be equal to ^~^y and that one half of
TC JLli
the wall will then be self-supporting and half will require extraneous
support. Or, in other words, the greatest stress on a lintel due to
a wall of any height will not be greater than that due to a distrib-
uted load of
i WHm St = % W~ St = nearly 15 ^ pounds. . (4)
4: jffc jFfc
251. Examples. To apply the above formula, assume that it is
proposed to cut a 10-foot opening through an old brick wall, and
that it is desirable to know whether the brick-work will be self-sup-
porting, the wall rising 40 feet above the top of the opening. Sub-
stituting the above data in equation (2) gives
40 = rB- ; or R = 1.25 Ibs. per sq. in.
^Hence, to be self-supporting across the opening, the wall must be
capable of supporting a tensile strain of 1.25 pounds per square
inch. It would be poor lime mortar that would not bear eight or
ten times this. Notice that if the wall were only 4 feet high, over
the opening, instead of 40 feet, as above, the strength required
would be 12.5 pounds per square inch.
For another illustration, assume that a brick wall 1 foot thick
is to be built over a 10-foot opening, and that we wish to know
whether a timber 10 inches deep and 12 inches wide will sustain the
load. Assuming the beam as being fixed at the ends, the timber
will sustain a uniformly distributed load of 10 tons with a deflection •
TRANSVERSE STRENGTH. 171
of one twelfth of an inch. This is equivalent to the entire weight
•of the wall when 14 feet high. If the wall is to be carried higher
than this, the girder must be supported temporarily, or time must
Ibe given for the mortar to set.
However, before the wall is 14 feet above the opening, the brick-
work at the bottom will have attained some strength, and therefore
the load on the girder will not be as great as above. The average
strength of the brick-work will always be at least the average between
the strength at the top and the bottom ; that is, the average strength
will always be more than half of that at the bottom. Since 10 tons
is the maximum load allowed on the girder, and since the maximum
load which comes upon it is half of the entire weight of the masonry
itbove the opening,* the timber will receive its maximum load when
the wall is twice 14 feet, or 28 feet, above the opening. The masonry
may be run up 28 feet without necessitating any extraneous support
for the lintel, provided time enough is allowed for the mortar to
•develop the average tensile strength found by substituting in (4)
the maximum load allowed on the girder, and solving for R. Mak-
ing this substitution gives
20000 = / -, from which R = 0.75 Ib. per sq. in.
j.i/
With an average strength of 0.75 Ib. per sq. in., the wall will
"become self-supporting when 70 feet above the opening.
252. Custom differs as to the manner of estimating the pressure
on a girder due to a superincumbent mass of masonry. One extreme
consists in assuming the masonry to be a fluid, and taking the load
on the lintel as the weight of all the masonry above the opening.
The opposite extreme consists in assuming the pressure to be the
weight of the masonry included in a triangle of which the open-
ing is the base and whose sides make 45° with this line. Both of
these methods differ materially from the one discussed above ; and
neither is defensible. As the wall is several days in building, the
masonry first laid attains considerable strength before the wall is
completed; and hence, owing to the cohesion of the mortar, the final
weight on the girder can not be equal to or compared with any fluid
volume.
The principle involved in the second method would be applicable
* See discussion of equation (3), above.
172 BRICK MASONRY. [CHAP. VIII.
to a wall composed wholly of perfectly smootli bricks. In a dry
wall, the angle which the side lines make with the base would
depend upon the bond and upon the relative length and breadth of
the bricks. Assuming the boundary lines to make an angle of 45 °"
o r>
with the base the method gives a load — - times that (§ 250}
which takes account of the transverse strength of the masonry, i. e.y
the frictional and tensile resistance of the wall. If R is relatively-
large and 8 is small, this fraction will be more than unity, under
which conditions the second method is safe. But if R is small and,
S is large, then tins fraction is less than one, which shows that
under these conditions the second method is unsafe.
The method of § 250 is quite simple and perfectly general. The
substantial correctness of this method, illustrated in § 251, is
proven by the fact that large openings are frequently cut through
walls without providing any extraneous support ; and also by the
fact that walls are frequently supported over openings on timbers
entirely inadequate to carry the load if the masonry did not have
considerable strength as a beam. The discussion in § 251 also makes
clear why frequently a temporary support is sufficient. After the
masonry has been laid a short time, the strength of the mortar
causes it to act as a beam. The discussion also shows the advantage
of using cement mortar (or better, quick-setting cement mortar)
when it is desired that the masonry shall early become self-sup-
porting.
253. MEASUREMENT OF BRICK- WORK. The method of determin-
ing the quantity of brick masonry is governed by voluminous trade
rules or by local customs, which are even more arbitrary than those
for stone masonry (§ 224, which see).
The quantity is often computed in perches, but there is no uni-
formity of understanding as to the contents of a perch. It ranges
from 16£ to 25 cubic feet.
Brick- work is also often measured by the square rod of exterior
surface. No wall is reckoned as being less than a brick and a half
in thickness (13 or 13£ inches), and if thicker the measurement is
still expressed in square rods of this standard thickness. Unfor-
tunately the dimensions adopted for a square rod are variable, the
following values being more or less customary : 16|- feet square or
DATA FOB ESTIMATES. 173
square feet, 18 feet square or 324 square feet, and 16£ square
feet.
The volume of a brick is sometimes used as a unit in stating the
oontents of a wall. The contents of the wall are found by multi-
plying the number of cubic feet in the wall by the number of brick
which it is assumed make a cubic foot ; but as the dimensions of
brick vary greatly (see § 62), this method is objectionable. A cubic
foot is often assumed to contain 20 brick, and a cubic yard 600.
The last two quantities are frequently used interchangeably, although
the assumed volume of the cubic yard is thirty times that of the
•cubic foot.
Brick-work is also sometimes measured by allowing a certain
number of brick to each superficial foot, the number varying with
the thickness of the wall. A 4-inch wall (thickness = width of one
brick) is frequently assumed to contain 7 bricks per sq. ft. ; a 9-inch
wall (thickness = width of two bricks), 14 bricks per sq. ft.; a 13-
inch wall (thickness = width of three bricks), 21 bricks per sq. ft.,
•etc. ; the number of brick per square foot of the face of the wall
being seven times the thickness of the wall in terms of the width of
.a brick.
254, The only relief from such arbitrary, uncertain, and indefi-
nite customs is to specify that the masonry will be paid for by the
•cubic yard, — gross or net measurement, according to the structure
or the preference of the engineer or architect.
In engineering the uniform, custom is to measure the exact solid
contents of the wall.
255. DATA FOB ESTIMATES. Number of Brick Required, Since
the size of brick varies greatly (§ 62), it is impossible to state a rule
which shall be equally accurate in all localities. If the brick be of
standard size (8Jx4x2J inches), and laid with |- to f-inch joints,
a cubic yard of masonry will require about 410 brick; or a thousand
brick will lay about 2-J cubic yards. If the joints are £- to f-inch, a
cubic yard of masonry will require about 495 brick; or a thousand
brick will lay about 2 cubic yards. If the joints are -J inch, a cubic
yard of masonry will require about 545 face brick; or a thousand
face brick will lay about 1.8 cubic yards.
In making estimates for the number of bricks required, an al-
lowance must be made for breakage, and for waste in cutting brick
to fit angles, etc. With good brick, in massive work this allowance
174 BRICK MASONRY. [CHAP. VIII.
need not exceed 1 or 2 per cent.; but in buildings 3 to 5 per cent.
is none too muck
256. Amount of Mortar Required. The proportion of mortar
to brick will vary with the size of the brick and with the thickness
of the joints. With the standard size of brick (Six4x3i inches),
a cubic yard of masonry, laid with £- to f-inch joints, will require
from 0,35 to 0.40 of a cubic yard of mortar; or a thousand brick
will require 0.80 to 0.90 of a cubic yard. If the joints are £ to f
inch, a cubic yard of masonry will require from 0. 25 to 0. 30 of a.
cubic yard of mortar; or a thousand brick will require from 0.45 to
0.55 of a cubic yard. If the joints are -J of an inch, a cubic yard of
masonry will require from 0.10 to 0.15 of a cubic yard of mortar;
or a thousand brick will require from 0.15 to 0.20 of a cubic yard.
With the above data, and the table on page 86, the amount of
cement and sand required for a specified number of brick, or for a-
given number of yards of masonry, can readily be determined.
257. Labor Bequired. " A bricklayer, with a laborer to keep him
supplied with materials, will lay on an average, in common house-
walls, about 1,500 bricks per day of 10 working hours; in the neater
outer faces of brick buildings, from 1,000 to 1,200; in good ordinary
street fronts, from 800 to 1,000 ; and in the very finest lower-story
faces used in street fronts, from 150 to 300 according to the number
of angles, etc. In plain massive engineering work, he should aver-
age about 2,000 bricks per day, or 4 cu. yds. of masonry ; and in
large arches, about 1,500, or 3 cu. yds."*
In the United States Government buildings the labor per thou-
sand, including tools, etc., is estimated at seven eighths of the wages,
for ten hours of mason and helper.
Table 21, opposite, f gives the actual labor, per cubic yard, re-
quired on some large and important jobs.
258. COST. In the construction of the Cincinnati Southern R. R. ,
during 1873-77, the brick lining of tunnels cost $8.50 per cu. yd. ;
brick-work in buildings, $7.00.1 The average price paid for the
brick-work in the new Croton Aqueduct tunnel, which supplies New
York City with water, was, including everything, $10.14 per cu. yd.
*Trautwine's Engineer's Pocket-Book, p. 671.
t Trans. Am. Soc. of C. E.
t Beport of the Chief Engineer, Dec. 1, 1877, Exhibit 3.
SPECIFICATIONS. 175
TABLE 21.
LABOR KEQUIKED FOR BRICK MASONRY.
LOCATION AND DESCRIPTION OP THE MASONRY.
WORK REQUIRED. IN
DAYS PER CUBIC YARD.
High Bridge Enlargement, N. Y. City —
Lining wall and flat arches laid with very close joints.
Washington (D. C.) Aqueduct —
Circular conduit, 9 feet in diameter with walls 12
inches thick.
St. Louis Water Works—
Semi-circular conduit, 6 feet in diameter
New York City Storage Reservoir—
Lining of gate-house walls and arches — rough work. .
0.714
0.439
0.364
0.304
for lining, and $8.49 for backing. The mortar was composed of 1
part cement of the Eosendale type and 2 parts of sand.*
In Chicago in 1887, the price of brick laid in lime in interior
walls was about $11 per thousand, equivalent to about $7 per cu. yd.
The wages of masons were from 45 to 50 cents per hour, and of
common labor from 20 to 25 cents per hour.
259. SPECIFICATIONS FOE BRICK MASOBTKY. For Buildings.
There is not even a remote approach to uniformity in the specifica-
tions for the brick- work of buildings. Ordinarily the specifications
for the brick masonry are very brief and incomplete. The following
conform closely to ordinary construction. Of course, a higher grade
of workmanship can be obtained by more stringent specifications. f
The brick in the exterior walls must be of good quality, hard -burned; fine,
compact, and uniform in texture; regular in shape, and uniform in size.j:
One fourth of the "brick in the interior walls may be what is known as soft
or salmon brick (see 2, § 56). The brick must be thoroughly wet before
being laid. The joints of the exterior walls shall be from i to f inch thick. §
The joints of interior division-walls may be from f to £ inch thick. The
mortar shall be composed of 1 part of fresh, well-slaked lime and 2J to 3 parts
* Report of the Aqueduct Commission, 1883-87, Table 4.
t For specifications for masonry for various purposes, see Appendix I.
I See § 57, page 87.
§ For the best work, omit this item and insert the following : The outside walls
shall be faced with the best pressed brick of uniform color, laid in colored mortar, with
joints not exceeding one ciyhth of an inch in thickness. Face brick are made a little
larger (§ 62) than ordinary brick to compensate for the thinner joints.
176 BEICK MASOKRY. [CHAP. VIII.
of clean, sharp sand.* The lime-paste and the sand shall be thoroughly
mixed before being used. The joints shall be well filled with the above
mortar ; no grout shall be used in the work. The bond must consist of five
•courses of stretchers to one of headers, and shall be so arranged as to thor-
oughly bind the exterior and interior portions of the wall to each other.
The contractor must furnish, set up, and take away his own scaffolding ;
he must build in such strips, plugs, blocks, scantling, etc., as are required for
securing the wood-work ; and must also assist in placing all iron-work, as
beams, stairways, anchors, bed-plates, etc., connected with the brick-work.
260. For Sewers. The following are the specifications employed,
in 1885, in the construction of brick sewers in Washington, D. C. :
" The best quality of whole new brick, burned hard entirely through, free
from injurious cracks, with true even faces, and with a crushing strength of
not less than 5,000 pounds per square inch, shall be used, and must be thor-
oughly wet by immersion immediately before laying. Every brick is required
to be laid in full mortar joints, on bottom, sides, and ends, which for each
brick is to be performed by one operation. In no case is the joint to be made
by working in mortar after the brick has been laid. Every second course shall
be laid with a line, and joints shall not exceed three eighths of an inch. The
brick-work of the arches shall be properly bonded, and keyed as directed by
the engineer. ISTo portion of the brick-work shall be laid dry and afterwards
grouted.
" The mortar shall be composed of cement and dry sand, in the proportion
•of 300 pounds of cement and 2 barrels of loose sand, thoroughly mixed dry,
and a sufficient quantity of water afterwards added to form a rather stiff paste.
It shall be used within an hour after mixing, and not at all if once set.
"The cement shall be of the best quality, freshly burned, and equal in
•every respect to the Hound Top or Shepardstown cement, manufactured upon
the formula of the engineer-commissioner of the District of Columbia, capable
•of being worked for twenty minutes in mortar without loss of strength, and
•shall be tested in such manner as the engineer may direct. After being mixed
with water, allowed to set in air for twenty- four hours, and then immersed in
water for six days, the tensile strength must be as follows :
Neat cement 95 Ibs. per sq. inc
One part cement and one part sand 56 " " " tl
" " " " two parts " 32 " " " "
" " " " three'4 " 12 " " " "
"The sand used shall be clean, sharp, free from loam, vegetable matter, or
-other dirt, and capable of giving the above results with the cement.
" The water shall be fresh and clean, free from earth, dirt, or sewerage.
* For masonry that is to be subjected to a heavy pressure, omit this item and
insert the following : The mortar must be composed of 1 part Lime-paste, 1 part cement,
«and 2 parts of dean, sharp sand. Or, if a heavier pressure is to be resisted, specify
that some particular grade of cement mortar is to be used. (See §§ 246 and 247.)
SPECIFICATIONS. 17?
" Tight mortar-boxes shall be provided by the contractor, and no mortar
shall be made except in such boxes.
" The proportions given are intended to form a mortar in which every
particle of sand shall be enveloped by the cement ; and this result must be
attained to the satisfaction of the engineer and under his direction. The
thorough mixing and incorporation of all materials (preferably by machine
labor) will be insisted upon. If by hand labor, the dry cement and sand shall
be turned over with shovels by skilled workmen not less than six times before
the water is added. After adding the water, the paste shall again be turned
over and mixed with shovels by skilled workmen not less than three times be-
fore it is used."
261. For Arches. The specifications for the "brick arch masonry
•on the Atchison, Topeka and Santa .Fe llailroad are as follows :
"The bricks must be of the best quality of smooth, hard-burnt, paving
bricks, well tempered and moulded, of the usual size, compact, well shaped,
free from lime, cracks, and other imperfections, and must stand a pressure
of 4,000 pounds per square inch without crushing. No bats will be allowed
in the work except for making necessary closures. All bricks will be culled
on the ground after delivery, and selected in strict accordance with these
specifications.
" The mortar must be made of 1 measure of good hydraulic [Iloseudale]
•cement and 2 measures of clean, sharp sand — or such other proportion as may
be prescribed by the engineer — well mixed together with clean water, in clean
mortar-beds constructed of boards, and must be used immediately after being
mixed.
" The brick must be laid Hush in cement mortar, and must be thoroughly
wet when laid. All joints and beds must be thoroughly tilled with mortar so
as to leave no empty spaces whatever in the masonry of the walls arid arches,
which must be solid throughout. The thickness of mortar- joints must be as
follows : In the walls and in the arch between bricks of the same ring, not less
than three eighths of an inch ($•") nor more than one half inch (£"). In the arch
between rings, not less than one half inch (-J-") nor more than five eighths of
an inch (!•"). Each brick is to be driven into place by blows of a mallet. The
bricks must be laid in the walls with the ordinary English bond, live stretcher
courses to one header course. They must be laid in the arch in concentric
rings, each longitudinal line of bricks breaking joints with the adjoining
lines in the same ring and in the ring under it. No headers to be used in
the arch."
262. BRICK vs. SToma MASONRY. Brick masonry is not much
used, except in the walls of buildings, in lining tunnels, and in con-
structing sewers, the general opinion being that brick-work is in
every way inferior to stone masonry. This belief may have been
well founded when brick was made wholly by hand, by inexpert
operatives, and imperfectly burned in the old-time kilns, the prod-
178 BRICK MASOSTRY. [CHAP. VIII*
uct being then generally poor ; but things have changed, and since
the manufacture of brick has become a business conducted on a
large scale by enterprising men, with the aid of a variety of machines
and improved kilns, the product is more regular in size and quality
and stronger than formerly. Brick is rapidly displacing stone for
the largest and best buildings in the cities, particularly in Chicago
and St. Petersburg, where the vicissitudes of the climate try masonry
very severely. There are many engineering structures in which,
brick could be profitably employed instead of stone ; as, for example,
the walls of box-culverts, cattle-guards, etc., and the less important
bridge piers and abutments, particularly of highway bridges.
Brick-work is superior to stone masonry in several respects, as
follows : 1. In many localities brick is cheaper than stone, since-
the former can be made near by while the latter must be shipped.
2. As brick can be laid by less skillful masons than stone, it costs-
less to lay it. 3. Brick is more easily handled than stone, and can-
be laid without any hoisting apparatus. 4. Brick requires less fit-
ting at corners and openings. 5. Brick masonry is less liable to-
great weakness through inaccurate dressing or bedding. 6. Brick-
work resists fire better than limestone, granite, or marble, sand-
stone being the only variety of stone that can compare with brick
in this respect. 7. Good brick stands the effect of weathering and
of the acids in the atmosphere better than sandstones, and in dura-
bility even approaches some of the harder stones (see §§ 31, 32).
8. All masonry fails when the mortar in its joints disintegrates or
becomes dislodged; therefore brick masonry will endure the vicissi-
tudes of the weather as well as stone masonry, or even better, since^
the former usually has thinner joints.
Brick- work is not as strong as ashlar masonry, but costs less ;.
while it is stronger and costs more than ordinary rubble.
263. BRICK MASONRY IMPERVIOUS TO WATER. It sometimes be-
comes necessary to prevent the percolation of water through brick
walls. A cheap and effective process has not yet been discovered,
and many expensive trials have proved failures. The following
account* gives the details of two experiments that were entirely suc-
cessful.
" The face Walls of the back bays of the gate-houses of the new
* Abstract of a paper by Wm. L. Dearborn, in Trans. Am. Soc. of C. E., vol. i^
£p. 203-8*
MASONRY IMPERVIOUS TO WATER. 179
Croton reservoir, located north of Eighty-sixth Street, in Central
Park., JSTew York City, were built of the best quality of hard-burnt
brick, laid in mortar composed of hydraulic cement of New York
[Ulster Co. Rosendale] and sand mixed in the proportion of one
measure of cement to two of sand. The space between the walls war;
4 feet, and was filled with concrete. The face walls were laid up
with great care, and every precaution was taken to have the joints
well filled and to insure good work. The walls are 12 inches thick
and 40 feet high; and the bays, when full, generally have 36 feet of
water in them.
" When the reservoir was first filled and the water let into the
gate-houses, it was found to filter through these walls to a consider-
able amount. As soon as this was discovered the water was drawn
out of the bays, with the intention of attempting to remedy or pre-
vent this infiltration. After carefully considering several modes of
accomplishing the object desired,, I [Dearborn] came to the conclu-
sion to try ' Sylvester's Process for Repelling Moisture from Exter-
nal Walls.'
"The process consists in using two washes or solutions for cov-
ering the surface of the walls — one composed of Castile soap and
water, and one of alum and water. The proportions are three
quarters of a pound of soap to one gallon of water, and half a pound
of alum to four gallons of water, both substances to be perfectly
dissolved in water before being used. The walls should be perfectly
clean and dry, and the temperature of the air not above 50° Pahr.
when the compositions are applied.
"The first, or soap-wash, should be laid on, when boiling hot,
with a flat brush, taking care to form a froth on the brick-work.
This wash should remain 24 hours, so as to become dry and hard
before the second, or alum, wash is applied, which should be done
in the same manner as the first. The temperature of this wash,
when applied, maybe 60° or 70° Fahr. ; and this also should remain
24 hours before a second coat of the soap-wash is put on.
These coats are to be applied alternately until the walls are made
impervious to water. The alum and soap thus combined form an
insoluble compound, filling the pores of the masonry and entirely
preventing the water from entering the walls.
"Before applying these compositions to the walls of the bays
some experiments were made to test the absorption of water by
178 BRICK MASONRY. [CHAP. VIII*
net being then generally poor ; bnt things have changed, and since
the manufacture of brick has become a business conducted on a-
large scale by enterprising men, with the aid of a variety of machines
and improved kilns, the product is more regular in size and quality
and stronger than formerly. Brick is rapidly displacing stone for
the largest and best buildings in the cities, particularly in Chicago
and St. Petersburg, where the vicissitudes of the climate try masonry
very severely. There are many engineering structures in which,
brick could be profitably employed instead of stone ; as, for example,
the walls of box-culverts, cattle-guards, etc., and the less important
bridge piers and abutments, particularly of highway bridges.
Brick-work is superior to stone masonry in several respects, as
follows : 1. In many localities brick is cheaper than stone, since
the former can be made near by while the latter must be shipped.
2. As brick can be laid by less skillful masons than stone, it costs-
less to lay it. 3. Brick is more easily handled than stone, and can.
be laid without any hoisting apparatus. 4. Brick requires less fit-
ting at corners and openings. 5. Brick masonry is less liable to-
great weakness through inaccurate dressing or bedding. 6. Brick-
work resists fire better than limestone, granite, or marble, sand-
stone being the only variety of stone that can compare with brick
in this respect. 7. Good brick stands the effect of weathering and
of the acids in the atmosphere better than sandstones, and in dura-
bility even approaches some of the harder stones (see §§ 31, 32).
8. All masonry fails when the mortar in its joints disintegrates or
becomes dislodged; therefore brick masonry will endure the vicissi-
tudes of the weather as well as stone masonry, or even better, since
the former usually has thinner joints.
Brick-work is not as strong as ashlar masonry, but costs less ;,
wMle it is stronger and costs more than ordinary rubble.
263. BUCK MASONRY IMPERVIOUS TO WATER. It sometimes be-
comes necessary to prevent the percolation of water through brick
walls. A cheap and effective process has not yet been discovered,
and many expendve trials have proved failures. The following
account* gives the details of two experiments that were entirely suc-
cessful.
" The face walls of the back bays of the gate-houses of the new
* Abstract of a paper by Wm. L. Dearborn, in Trans. Am. Soc. of C. E., vol. t-
#p. 208-8-
MASONRY IMPERVIOUS TO WATER. 179
Croton reservoir, located north of Eighty-sixth Street, in Central
Park, New York City, were built of the best quality of hard-burnt
brick, laid in mortar composed of hydraulic cement of New York
[Ulster Co. Eosendale] and sand mixed in the proportion of one
measure of cement to two of sand. The space between the walls wa:i
4 feet, and was filled with concrete. The face walls were laid up
with great care, and every precaution was taken to have the joints
well filled and to insure good work. The walls are 12 inches thick
and 40 feet high; and the bays, when full, generally have 36 feet of
water in them.
"When the reservoir was first filled and the water let into the
gate-houses, it was found to filter through these walls to a consider-
able amount. As soon as this was discovered the water was drawn
out of the bays, with the intention of attempting to remedy or pre-
vent this infiltration. After carefully considering several modes of
accomplishing the object desired, I [Dearborn] came to the conclu-
sion to try ' Sylvester's Process for Eepelling Moisture from Exter-
nal Walls/
"The process consists in using two washes or solutions for cov-
ering the surface of the walls — one composed of Castile soap and
water, and one of alum and water. The proportions are three
quarters of a pound of soap to one gallon of water, and half a pound
of alum to four gallons of water, both substances to be perfectly
dissolved in water before being used. The walls should be perfectly
clean and dry, and the temperature of the air not above 50° Fahr.
when the compositions are applied.
" The first, or soap- wash, should be laid on, when boiling hot,
with a flat brush, taking care to form a froth on the brick-work.
This wash should remain 24 hours, so as to become dry and hard
before the second, or alum, wash is applied, which should be done
in the same manner as the first. The temperature of this wash,
when applied, maybe 60° or 70° Fahr. ; and this also should remain
24 hours before a second coat of the soap-wash is put on.
These coats are to be applied alternately until, the walls are made
impervious to water. The alum and soap thus combined form an
insoluble compound, filling the pores of the masonry and entirely
preventing the water from entering the walls.
"Before applying these compositions to the walls of the bays
some experiments were made to test the absorption of water by
180 BEICK MASONRY. [CHAP. VIII.
bricks under pressure after being covered with these washes,, in
order to determine how many coats the walls woiild reqaire to render
them impervious to water. To do this, a strong wooden box large
enough to hold two bricks was made, put together with screws, and
in the top was inserted a 1-inch pipe 40 feet long. In this box
were placed two bricks, after being made perfectly dry, which were
then covered with a coat of each of the washes, as before directed,
and weighed. They were then subjected to a column of water 40
feet high ; and after remaining a sufficient length of time they were
taken out and weighed again, to ascertain the amount of water they
had absorbed. The bricks were then dried, and again coated with
the washes and weighed, and subjected to pressure as before, this
operation being repeated until the bricks were found not to absorb
any water. Four coatings rendered the bricks impenetrable under
the pressure of a 40-foot head. The mean weight of the bricks (dry)
before being coated was 3f Ibs. ; the mean absorption was one half-
pound of water* A hydrometer was used in testing the solutions.
"As this experiment was made in the fall and winter (1863),
after the temporary roofs were put on to the gate-house, artificial
heat had to be resorted to to dry the walls and keep the air . at a
proper temperature. The cost was 10 cents per sq. ft. As soon as
the last coat had become hard, the water was let into the bays, and
the walls were found to be perfectly impervious to water, and they
remain so in 1870, after about 6-J- years.
264. "The brick arch of the footway of High Bridge is the arc
of a circle, 29^- feet radius, and is 12 inches thick; the width on top
is 17 feet, and the length covered is 1,381 feet. The first two
courses of the brick of the arch are composed of the best hard-burnt
brick, laid edgewise in mortar composed of 1 part, by measure, of
hydraulic cement of New York [Ulster Co. Rosendale] and 2 parts
of sand. The top of these bricks, and the inside of the granite
coping against which the two top courses of brick rest, was covered,
when perfectly dry, with a coat of asphalt one half an inch thick,
laid on when the asphalt was heated to a temperature of from 360°
to 518° Fahr. On top of this was laid a course of brick flatwise,
dipped in asphalt, and laid when the asphalt was hot; and the joints
were run full of hot asphalt. On top of this, a course of pressed
brick was laid flatwise in hydraulic cement mortar, forming the
paving and floor of the bridge.
EFFLORESCENCE. 181
" The area of the bridge covered with asphalted brick was 23,065
sq. ft. There were used 9 4, 200 Ibs. of asphalt, 33 barrels of coal tar,
10 cu. yds. of sand, and 93,800 bricks. The asphalt was the Trini-
dad variety ; and was mixed with 10 per cent., by measure, of coal
tar, and 25 per cent, of sand. The time occupied was 109 days of
masons, and 148 days of laborers. Two masons and two laborers
will melt and spread, of the first coat, 1,650 sq. ft. per day. The
total cost of this coat was 5£ cents per sq. ft., exclusive of duty on
asphalt.
" There were three grooves, 2 inches wide by 4 inches deep,
made entirely across the brick arch immediately under the first
coat of asphalt, thus dividing the arch into four equal parts. The
grooves were filled with elastic paint cement. This arrangement
was intended to guard against the evil effects of the contraction of
the arch in winter ; for, since it was expected to yield slightly at
these points and at no other, the elastic cement would prevent any
leakage there. The entire experiment has proved a very successful
one, and the bridge has remained perfectly tight.
"In proposing the above plan for working the asphalt with the
brick -work, the object was to avoid depending on a large continuous
surface of asphalt, as is usual in covering arches, which very fre-
quently cracks from the greater contraction of the asphalt than that
of the masonry with which it is in contact, the extent of the asphalt
on this work being only about one quarter of an inch to each brick.
This is deemed to be an essential element in the success of the im-
pervious covering."
265. EFFLOKESCENCE. Masonry, particularly in moist climate
or in damp places — as cellar walls, — is frequently disfigured by the
formation of a white efflorescence on the surface. This deposit
generally originates with the mortar, but frequently spreads over
the entire face of the wall. The water which is absorbed by the
mortar dissolves the salts of soda, potash, magnesia, etc., contained
in the lime or cement, and on evaporating deposits these salts as a
white efflorescence on the surface. "With lime mortar the deposit
is frequently very heavy, particularly on plastering ; and, usually,
it is heavier with Kosendale than with Portland cement. The
efflorescence sometimes originates in the brick., particularly if the
brick was burned with sulphurous coal, or was made from clay con-
taining iron pyrites; and when the brick gets wet, the water dissolves
182 BBICK MASONRY. [CHAP. VIII.
the sulphates of lime and magnesia, and on evaporating leaves the
crystals of these salts on the surface. Frequently the efflorescence
on the brick is due to the absorption by the brick of the impreg-
nated water from the mortar.
This efflorescence is objectionable because of the unsightly ap-
pearance which it often produces, and also because the crystalliza-
tion of these salts within the pores of the mortar and of the brick
or stone causes disintegration which is in many respects like frost.
As a preventive, Gillmore recommends* the addition of 100 Ibs.
of quicklime and 8 to 12 Ibs. of any cheap animal fat to each barrel
of cement. The lime is simply a vehicle for the fat, which should
be thoroughly incorporated with the lime before slaking. The ob-
ject of the fat is to saponify the alkaline salts. The method is riot
entirely satisfactory, since the deposit is only made less prominent
and less effective, and not entirely removed or prevented.
The efflorescence may be entirely prevented, whatever its origin,
by applying Sylvester's washes (see § 263) to the entire external sur-
faces of the wall ; and, 'since usually the efflorescence is due to the
water absorbed by the mortar, it can generally be prevented, and
can always be much diminished, by using mortar which is itself im-
pervious to water (see § 141). The latter is the cheaper method,
particularly if the impervious mortar be used only for the face of
the joints. If the wall stands in damp ground, one or more of the
horizontal joints just above the surface should be laid in impervious
mortar, or better, the brick for several courses should be rendered
impervious and be laid in impervious mortar to prevent the wall's
absorbing moisture from below.
* "Limes, Hydraulic Cements, and Mortars," p. 296.
III.
FOUNDATIONS.
CHAPTER IX.
INTRODUCTORY.
266. DEFINITIONS. The term foundation is ordinarily used in-
differently for either the lower courses of a structure of masonry or
the artificial arrangement, whatever its character, on which these
•courses rest. For greater clearness, the term foundation will here
be restricted to the artificial arrangement, whether timber or mason-
ry, which supports the main structure ; and the prepared surface
upon which this artificial structure rests will be called the led of
the foundation. There are many cases in which this distinction
•can not be adhered to strictly.
267. IMPOETANCE OF THE STOJECT. The foundation, whether
for the more important buildings or for bridges and culverts, is the
most critical part of a masonry structure. The failures of works of
masonry due to faulty workmanship or to an insufficient thickness
of the walls are rare in comparison with those due to defective
foundations. When it is necessary, as so frequently it is at the
present day, to erect gigantic edifices — as high buildings or long-
span bridges — on weak and treacherous soils, the highest construc-
tive skill is required to supplement the weakness of the natural
foundation by such artificial preparations as will enable it to sustain
such massive and costly burdens with safety.
Probably no branch of the engineer's art requires more ability
and skill than the construction of foundations. The conditions
governing safety are generally capable of being calculated with
as much practical accuracy in this as in any other part of a con-
183
184 FOUNDATIONS: INTRODUCTORY. [CHAP. IX*
•struction ; but, unfortunately, practice is frequently based upon,
empirical rules rather than upon a scientific application of funda-
mental principles. It is unpardonable that any liability to danger
or loss should exist from the imperfect comprehension of a subject-
of such vital importance. Ability is required in determining the
conditions of stability; and greater skill is required -in fulfilling
these conditions, that the cost of the foundation may not be pro-
portionally too great. The safety of a structure may be imperiled,
or its cost unduly increased, according as its foundations are laid,
with insufficient stability, or with provision for security greatly in
excess of the requirements. The decision as to what general method
of procedure will probably be best in any particular case is a ques-
tion that can be decided with reasonable certainty only after long
experience in this branch of engineering ; and after having decided
upon the general method to be followed, there is room for the
exercise of great skill in the means employed to secure the desired
end. The experienced engineer, even with all the information
which he can derive from the works of others, finds occasion for the?
use of all his knowledge and best common sense.
The determination of the conditions necessary for stability can
be reduced to the application of a few fundamental principles which
may be studied from a text-book ; but the knowledge required to
determine beforehand the method of construction best suited to the
case in hand, together with its probable cost, comes only by personal
experience and a careful study of the experiences of others. The
object of Part III. is to classify the principles employed in con-
structing foundations, and to give such brief accounts of actual
practice as will illustrate the applications of these principles.
268. PLAIT OF PBOPOSED DISCUSSION. In a general way, soils
may be divided into three classes : (1) ordinary soils, or those which
are capable, either in their normal condition or after that condition
has been modified by artificial means, of sustaining the load that i»
to be brought upon them ; (2) compressible soils, or those that are
incapable of directly supporting the given pressure with any reason-
able area of foundation ; and (3) semi-liquid soils, or those in which
the fluidity is so great that they are incapable of supporting any
considerable load. Each of the above classes gives rise to a special
method of constructing a foundation.
1. With a soil of the first class, the bearing power may be in-
PLAN OF PROPOSED DISCUSSION. 185
creased by compacting the surface or by drainage ; or the area of
the foundation may be increased by the use of masonry footing
courses, inverted masonry arches, or one or more layers of timbers,
railroad rails, iron beams, etc. Some one of these methods is or-
dinarily employed in constructing foundations on land ; as, for
example, for buildings, bridge abutments, sewers, etc. Usually all
of these methods are inapplicable to bridge piers, i. e., for founda-
tions under water, owing to the scouring action of the current and
also to the obstruction of the channel by the greatly extended base
of the foundation.
2. With compressible soils, the area of contact may be increased
by supporting the structure upon piles of wood or iron, which are-
sustained by the friction of the soil on their sides and by the direct
pressure on the soil beneath their bases. This method is frequently
employed for both buildings and bridges.
3. A semi-fluid soil must generally be removed entirely and the
structure founded upon a lower and more stable stratum. This
method is specially applicable to foundations for bridge piers.
There are many cases to which the above classification is not
strictly applicable.
For convenience in study, the construction of foundations will
be discussed, in the three succeeding chapters, under the heads
Ordinary Foundations, Pile Foundations, and Foundations under
Water. However, the methods employed in each class are not
entirely distinct from those used in the others.
OHAPTBE X.
ORDINARY FOUNDATIONS.
269. IN this chapter will be discussed the method of construct-
ing the foundations for buildings, bridge abutments, culverts, or,
in general, for any structure founded upon dry, or nearly dry,
ground. This class of foundations could appropriately be called
Foundations for Buildings, since these are the most numerous of the
class.
This chapter is divided into three articles. The first treats of
the soil, and includes (a) the methods of examining the site to de-
termine the nature of the soil, (b) a discussion of the bearing power
of different soils, and (c) the methods of increasing the bearing
power of the soil. The second article treats of the method of de-
signing the footing courses, and includes (a) the method of deter-
mining the load to be supported, and (b) the method of increasing
the area of the foundation. The third contains a few remarks con-
cerning the practical work of laying the foundation.
ART. 1. THE SOIL.
270. EXAMINATION OF THE SITE. The nature of the soil to be
"built upon is evidently the first subject for consideration,, and if it
has not already been revealed to a considerable depth, by excava-
tions for buildings, wells, etc., it will be necessary to make an ex-
amination of the subsoil preparatory to deciding upon the details
of the foundation. It will usually be sufficient, after having dug
. the foundation pits or trenches, to examine the soil with an iron
rod or a post-auger from 3 to 5 feet further, the depth depending
upon the nature of the soil, and the weight and importance of the
intended structure.
In soft soil, soundings 40 or 50 feet deep can be made by driving
a small (say f-inch) gas-pipe with a hammer or maul from a tem-
porary scaffold, the height of which will of course depend upon the
length, of the sections of the pipe. If samples of the soil are desired,
186
ART. L] THE SOIL. 187
use a 2-inch pipe open at the lower end. If much of this kind of
-work is to be done,, it is advisable to fit up a hand pile-driving
.machine (see § 335), using a block of wood for the dropping weight.
Borings 50 to 100 feet deep can be made very expeditious! y in
•common soil or clay with a common wood-auger 'turned by men,
with levers 2 or 3 feet long. The auger will bring up samples suf-
ficient to determine the nature of the soil,, but not its compactness,
since it will probably be compressed somewhat in being cut off.
When the testing must be made through sand or loose soil, it
may be necessary to drive down an iron tube to prevent the soil
from falling into the hole. The sand may be removed from the
inside of the tube with an auger, or with the ' : sand-pump" used in
digging artesian wells. When the subsoil is composed of various
strata and the structure demands extraordinary precaution, borings
must be made with the tools employed for boring artesian wells.*
271. If the builder desires to avoid, on the one hand, the unnec-
essarily costly foundations which are frequently constructed, or, on
the other hand, those insufficient foundations evidences of which
are often seen, it may be necessary, after opening the trenches, to
determine the supporting power of the soil by applying a test load.
In the case of the capitol at Albany, 1ST. Y., the soil was tested
by applying a measured load to a square foot and also to a square
yard. The machine used was a mast of timber 12 inches square,
held vertical by guys, with a cross-frame to hold the weights. For
the smaller area, a hole 3 feet deep was dug in the blue clay at the
bottom of the foundation, the hole being 18 inches square at the
top and 14 inches at the bottom. Small stakes were driven into
the ground in lines radiating from the center of the hole, the tops
being brought exactly to the same level ; then any change in the
surface of the ground adjacent to the hole could readily be detected
and measured by means of a straight-edge. The foot of the mast
was placed in the hole, and weights applied. No change in the
surface of the adjacent ground was observed until the load reached
5.9 tons per sq. ft., when an uplift of the surrounding earth was
noted in the form of a ring with an irregularly rounded surface,
the contents of which, above the previous surface, measured 0.09
cubic feet. Similar experiments were made by applying the load to
* For illustrations of tools for this purpose, see Engineering News, vol. 31, p.334.
188 ' ORDIKABY FOUNDATIONS. ' [CHAP. X.
a square yard with essentially the same results. The several loads-
were allowed to remain for some time, and the settlements observed.*
Similar experiments were made in connection with the construc-
tion of the Congressional Library Building, "Washington, D. 0., with,
a frame which rested upon 4 foot-plates each a foot square. The
frame could be moved from place to place on wheels, and the test
was applied at a number of places.
272. BEARING- POWER OF SOILS. It is scarcely necessary to say-
that soils vary greatly in their bearing power, ranging as they
do from the condition of hardest rock, through all intermediate
stages, to a soft or semi-liquid condition, as mud, silt, or marsh.
The best method of determining the load which a specific soil will
bear is by direct experiment (§ 271); but good judgment and ex-
perience, aided by a careful study of the nature of the soil — its com-
pactness and the amount of water contained in it — will enable one to
determine, with reasonable accuracy, its probable supporting power.
The following data are given to assist in forming an estimate of the
load which may safely be imposed upon different soils.
273. Rock. The ultimate crushing strength of stone, as deter-
mined by crushing small cubes, ranges from 180 tons per square
foot for the softest stone — such as are easily worn by running water
or exposure to the weather — to 1,800 tons per square foot for the
hardest stones (see page 10). The crushing strength of slabs, i. e.,
of prisms of a less height than width, increases as the height de-
creases. A prism one half as high as wide is about twice as strong
as a cube of the same material. If a slab be conceived as being made
up of a number of cubes placed side by side, it is then easy to see
why the slab is stronger than a cube. The exterior cubes prevent
the detachment of the disk-like pieces (Fig. 1) from the sides of
the interior cubes ; and hence the latter are greatly strengthened,
which materially increases the strength of the slab. In testing
cubes and slabs the pressure is applied uniformly over the entire
upper surface of the test specimen ; and, reasoning from analogy,
it seems probable that when the pressure is applied to only a small
part of the surface, as in the case of foundations on rock, the strength
will be much greater than that of cubes of the same material.
The table on page 190 contains the results of experiments made
* W. J. McAlpine, the engineer in charge, in Trans. Am. Soc. C. E., vol. ii. p. 287.
AET. 1.] THE SOIL. 189
"by the author, and shows conclusively that a unit of material has a
much greater power of resistance when it forms a portion of a larger
mass than when isolated in the manner customary in making ex-
periments on crushing strength.
The ordinary "crushing strength'5 given in next to the last
column of Table 22 was obtained by crushing cubes of the identical
materials employed in the other experiments. The concentrated
pressure was applied by means of a hardened steel die thirty-eight
sixty-fourths of an inch in diameter (area = 0.277 sq. in.). All the
tests were made between self-adjusting parallel plates of a hydro-
static testing-machine. No packing was used in either series of
experiments ; that is to say, the pressed surfaces were the same in
both series. However, the block of limestone 7 inches thick (Ex-
periments Nos. 8 and 13) is an exception in this respect. This
block had been sawed out and was slightly hollow, and it was
thought not to be worth while to dress it down to a plane. As pre-
dicted before making the test, the block split each time in the di-
rection of the hollow. If the bed had been flat,- the block would
doubtless have shown a greater strength. The concentrated pres-
sure was generally applied near the corner of a large block, and
hence the distance from the center of the die to the edge of the
block is to the nearest edge. Frequently the block had a ragged
^dge, and therefore these distances are only approximate. The
quantity in the last column — "Katio" — is the crushing load per
square inch for concentrated pressures divided by the crushing load
per square inch for uniform pressure.
The experiments are tabulated in an order intended to show that
"the strength under concentrated pressure varies (1) with the thick-
ness of the block and (2) with the distance between the die and
the edge of the material being tested. It is clear that the strength
increases very rapidly with both the thickness and the distance from
the edge to the point where the pressure is applied. Therefore we
•conclude that the compressive strength of cubes of a stone gives
little or no idea of the ultimate resistance of the same material when
in thick and extensive layers in its native bed.
274. The safe bearing power of rock is certainly not less than
•one tenth of the ultimate crushing strength of cubes; that is to say,
the safe bearing power of solid rock is not less than 18 tons per sq.
it. for the softest rock and 180 for the strongest. It is safe to say
190
ORDINARY FOUNDATIONS.
[CHAP,
TABLE 22.
COMPEESSIVE STKENGTH WHEN THE PRESSURE is APPLIED ON ONLY A PART
OF THE UPPER SURFACE.
d
fc
5
"S,
W
w
h
MATERIAL.
THICKNESS OP BLOCK.
CENTER OP DIE PROM
EDGE.
No. OP TRIALS.
CRUSHING STRENGTH
PER SQUARE INCH
— CONCENTRATED
PRESSURE.
S
5
H
&
0
0
fc
1
Lime Mortar
•Hn.
2 in.
4
3,610
2
1 "
2 "
4
18,050
;-
ft
2 <l
9 «
8
86,100
c
4
Brick
Si "
2 "
11
11, 801
i;:
5
Limestone
3 "
2 "
4
31,046
f
fi
Sandstone
3 "
2 "
9,
51,600
c
7
Limestone . ...
4 '*
2 "
8
?5.3(U
?
8
7 "
2 "
?,
64,077
p
3
Sandstone
3 "
2 "
9
51,600
c
9
<t
3 "
3 "
1
59,204
10
i<
3 "
4 "
1
75,810
<
7
Limestone. ... ....
4 "
2 "
8
75,361
?
11
4 "
3 "
3
102,900
19
<(
4 "
4 "
1
111,188
•
8
((
7 ««
2 "
2
64,077
£
18
• <
7 "
4 "
1
87,720
«
14
g£5g
o
1,340
10,500
10,100
2,654
3,453
3.696
4,671
3,453
3,696
4,761
3,453
2.7
1.7
3.6-
5.1
9.0
14.0
16.0
18.5
14.0
16.0
20.5-
16.0'
22.0
24.0
18.5
25.0
Clay, which for years has safely carried, without appreciable settlement,
buildings concentrating 1£ to 2 tons per square foot (20 to 28 pounds
per square inch), when tested in the form of cubes was crushed with 4
to 8 pounds per square inch. In this case the average " ratio" is 4.3.
that almost any rock, from the hardness of granite to that of a soft
crumbling stone easily worn by exposure to the weather or to run-
ning water, when well bedded will bear the heaviest load that can
be brought upon it by any masonry construction.
It scarcely ever occurs in practice that rock is loaded with the
full amount of weight which it is capable of sustaining, as the extent
of base necessary for the stability of the structure is generally suffi-
cient to prevent any undue pressure coming on the rock beneath.
275. Clay. The clay soils vary from slate or shale, which will
support any load that can come upon it, to a soft, damp clay which
will squeeze out in every direction when a moderately heavy pres-
ART. 1.] THE SOIL. 191
sure is brought upon it. Foundations on clay should be laid at
such depths as to be unaffected by the weather ; since clay., at even
considerable depths, will gain and lose considerable water as the
seasons change. The bearing power of clayey soils can be very
much improved by drainage (§ 285), or by preventing the penetra-
tion of w.ter. If the foundation is laid upon undrained clay, care
must be taken that excavations made in the immediate vicinit}7" do
not allow the clay under pressure to escape by oozing away from
under the building. When the clay occurs in strata not horizontal,
great care is necessary to prevent this flow of the soil. When coarse
sand or gravel is mixqd with the clay, its supporting power is greatly
increased, being greater in proportion as the quantity of these
materials is greater. When they are present to such an extent that
the clay is just sufficient to bind them together, the combination
will bear as heavy loads as the softer rocks.
276. The following data on the bearing power of clay will be of
assistance in deciding upon the load that may safely be imposed
upon any particular clayey soil. From the experiments made in
connection with the construction of the capitol at Albany, 1ST. Y.,
as described in § 271, the conclusion was drawn that the extreme
supporting power of that soil was less than 6 tons per sq. ft., and
that the load which might be safely imposed upon it was 2 tons per
sq. ft. ce The soil was blue clay containing from 60 to 90 per cent.
of alumina, the remainder being fine siliceous sand. The soil con-
tains from 27 to 43, usually about 40, per cent, of water ; and vari-
ous samples of it weighed from 81 to 101 Ibs. per cu. ft." In the
case of the Congressional Library (§ 271), the ultimate supporting
power of "yellow clay mixed with sand" was 134- tons per sq. ft.;
and the safe load was assumed to be 2|- tons per sq. ft. Experi-
ments made on the clay under the piers of the bridge across the
Missouri at Bismarck, with surfaces 1J- inches square, gave an aver-
age ultimate bearing power of 15 tons per sq. ft.*
The stiifer varieties of what is ordinarily called clay, when kept
dry, will safely bear from 4 to 6 tons per sq. ft.; but the same clay,
if allowed to become saturated with water, can not be trusted to
bear more than 2 tons per sq. ft. At Chicago, the load ordinarily
put on a thin layer of clay (hard above and soft below, resting on a
* Report of the engineer, Ceo. S. Morison.
192 ORDINARY FOUNDATIONS. [CHAP. X.
thick stratum of quicksand) is 1-J- to 2 tons per sq. ft. ; and the set-
tlement, which usually reaches a maximum in a year, is about 1
inch per ton of load. Experience in central Illinois shows that, if
the foundation is carried down below the action of frost, the clay
subsoil will bear 1£ to 2 tons per sq. ft. without appreciable settling.
Kankine gives the safe load for compressible soils as 1£ bo If tons
per sq. ft.
277. Sand. The sandy soils vary from coarse gravel to fine sand.
The former when of sufficient thickness forms one of the firmest
;and best foundations ; and the latter when saturated with wrater
is practically a liquid. Sand when dry, or wet sand when prevented
from spreading laterally, forms one of the best beds for a founda-
tion. Porous, sandy soils are, as a rule, unaffected by stagnant
water, but are easily removed by running water ; in the former case
they present no difficulty, but in the latter they require extreme
•care at the hands of the constructor, as will be considered later.
278. Compact gravel or clean sand, in beds of considerable
- thickness, protected from being carried away by water, may be
loaded with 8 to 10 tons per sq. ft. with safety. In an experiment
in France, clean river-sand compacted in a trench supported 100
toDS per sq. ft. Sand well cemented with clay and compacted, if
protected from water, will safely carry 4 to 6 tons per sq. ft.
The piers of the Cincinnati Suspension Bridge are founded on a
bed of coarse gravel 12 feet below low- water, although solid lime-
stone was only 12 feet deeper ; if the friction on the sides of the
pier* be disregarded, the maximum pressure on the gravel is 4 tons
per sq. ft. The piers of the Brooklyn Suspension Bridge are founded
44 feet below the bed of the river, upon a layer of sand 2 feet thick
resting upon bed-rock ; the maximum pressure is about 5-^- tons
per sq. ft.
At Chicago sand and gravel about 15 feet below the surface are
successfully loaded with 2 to 2J tons per sq. ft. At Berlin the safe
load for sandy soil is generally taken at 2 to 2£ tons per sq. ft. The
Washington Monument, Washington, D. C., rests upon a bed of
very fine sand two feet thick underlying a bed of gravel and bowl-
ders; the ordinary pressure on certain parts of the foundation is
not far from 11 tons per sq. ft., which the wind may increase to
nearly 14 tons per sq. ft.
* For the amount of such friction, see §§ 418-19 and § 455.
ART. 1.] THE SOIL. 193
279. Semi-Liquid Soils. With a soil of this class, as mud, silt,
•or quicksand, it is customary (1) to remove it entirely, or (2) to
.sink piles, tubes, or caissons through it to a solid substratum, or
(3) to consolidate the soil by adding sand, earth,, stone, etc. The
method of performing these operations will be described later. Soils
of a soft or semi-liquid character should never be relied upon for a
foundation when anything better can be obtained ; but a heavy
superstructure may be supported by the upward pressure of a semi-
liquid soil, in the same way that water bears up a floating body.
According to Bankine,* a building will be supported when the
, ., , . 7 /I + sin a\* ., , . . . .
pressure at its base is w li - — ! — : per unit 01 area, in which ex-
r \1 — sin a I r
pression w is the weight of a unit volume of the soil, li is the depth
of immersion, and a is the angle of repose of the soil. If a = 5°5
then according to the preceding relation the supporting power of
the soil is 1.4 w li per unit of area ; if a = 10°, it is 2.0 w li ; and
if a = 15°, itis2.9?07i. The weight of soils of this class, i. e.,
mud, silt, and quicksand, varies from 100 to 130 Ibs. per cu. ft.
Kankine gives this formula as being applicable to any soil ; but since
it takes no account of cohesion, for most soils it is only roughly ap-
proximate, and gives results too small. The following experiment
.seems to show that the error is considerable. ec A 10-foot square
base of concrete resting on mud, whose angle of repose was 5 to 1
[a = 11 J°], bore 700 Ibs. per sq. ft." f This is 2-J- times the result
by the above formula, using the maximum value of w.
Large buildings have been securely founded on quicksand by
making the base of the immersed part as large and at the same time
as light as possible. Timber in successive layers (§ 309) or grillage
on piles (§ 320) is generally used in such cases. This class of foun-
dations is frequently required in constructing sewers in water-bear-
ing sands, and though apparently presenting no difficulties, such
foundations often demand great skill and ability.
280. It is difficult to give results of the safe bearing power of
•soils of this class. A considerable part of the supporting power is
derived from the friction on the vertical sides of the foundation ;
hence the bearing power depends in part upon the area of the side
•surface in contact with the soil. Furthermore, it is difficult to de-
* See Kankine's Civil Engineering, p. 379.
t Proc. lust, of C. E., vol. xviii. p. 493.
194
ORDINARY FOUNDATIONS.
[CHAP.
termine the exact supporting power of a plastic soil, since a consid-
erable settlement is certain to take place with, the lapse of time*
The experience at New Orleans with alluvial soil and a few experi-
ments* that have been made on quicksand seem to indicate that
with a load of i to 1 ton per square foot the settlement will not be
excessive.
281. Bearing Power: Summary. Gathering together the results
of the preceding discussion, we have the following table :
TABLE 23.
SAFE BEARING POWER OF SOILS.
m KIND OF MATERIAL.
SAFE BEARING POWER
IN TONS PER SQ. FT.
Min.
Max.
Bock — the hardest — in thick layers, in native bed (§ 274)
*' equal to best ashlar masonry (§ 274)
200
25
15
5
4
2
1
8
4
2
0.5
30
20
10
6
4
2
10
6
4
1
" " " " brick " "
" " " poor " " et
Clay in thick beds always dry (§ 276)
«« ** " « moderately dry (§ 276)
*' soft (§ 276)
Gravel and coarse sand well cemented (§ 278)
Sand, compact and well cemented, "
" clean, dry te
Quicksand alluvial soils etc (§ 280)
282. Conclusion. It is well to notice that there are some prac-
tical considerations that modify the pressure which may safely be
put upon a soil. For example, the pressure on the foundation of
a tall chimney should be considerably less than that of the low mas-
sive foundation of a fire-proof vault. In the former case a slight
inequality of bearing power, and consequent unequal settling, might
endanger the stability of the structure ; while in the latter no seri-
ous harm would result. The pressure per unit of area should be
less for a light structure subject to the passage of heavy loads — as,
* Trans. Am. Soc. of C. E., vol. xiv. p. 182 ; J&ngineering, vol. xx. p. 103 ; Proc,
Inst of C. E., vol. xvii. p. 443 ; Cleeman's Railroad Practice, pp. 103-4.
ART. 1.] THE SOIL. 195
for example, a railroad viaduct — than for a heavy structure subject
only to a quiescent load, since the shock and jar of the moving load
are far more serious than the heavier quiescent load.
The determination of the safe bearing power of soils, particular-
ly when dealing with those of a semi-liquid character, is not the
only question that must receive careful attention. In the founda-
tions for buildings, it may be necessary to provide a safeguard
against the soil's escaping by being pressed out laterally into excava-
tions in the vicinity. In the foundations for bridge abutments, it
maybe necessary to consider what the effect will be if the soil around
the abutment becomes thoroughly saturated with water, as it may
during a flood; or what the effect will be if the soil is deprived of
its lateral support by the washing away of the soil adjacent to the
abutment. The provision to prevent the wash and undermining
action of the stream is often a very considerable part of the cost of
the structure. The prevention of either of these liabilities is a prob-
lem by itself, to the solution of which any general discussion will
contribute but little.
283. IMPROVING THE BEARING POWER OF THE SOIL. When
the soil directly under a proposed structure is incapable, in its nor-
mal state, of sustaining the load that will be brought upon it, the
bearing power may be increased (1) by increasing the depth of the
foundation, (2) by draining the site, (3) by compacting the soil, or
(4) by adding a layer of sand.
284. Increasing the Depth. The simplest method of increas-
ing the bearing power is to dig deeper. Ordinary soils will bear
more weight the greater the depth reached, owing to their becom-
ing more condensed from the superincumbent weight. Depth is
especially important with clay, since it is then less liable to be dis-
placed laterally owing to other excavations in the immediate vicin-
ity, and also because at greater depths the amount of moisture in it
will not vary so much.
In any soil, the bed of the foundation should be below the reach
of frost. Even a foundation on bed-rock should be below the frost
line, else water may get under the foundation through fissures, and,
freezing, do damage.
285. Drainage. Another simple method of increasing the bear-
ing power of a soil is to drain it. The water may find its way to
the bed of the foundation down the side of the wall, or by percola-
196 ORDINARY FOUNDATIONS. [CHAP. X.
tion through, the soil, or through a seam of sand. In most cases
the "bed can be sufficiently drained by covering it with a layer of
gravel — the thickness depending upon the plasticity of the soil, —
and then surrounding the building with a tile-drain laid a little
below the foundation. In extreme cases, it is necessary to enclose
the entire site with a puddle-wall to cut off drainage water from a
higher area.
286. Springs. In laying foundations, springs are often met
with, and sometimes prove very troublesome. The water may be
excluded from the foundation pit by driving sheet piles, or by plug-
ging the spring with concrete. If the flow is so strong as to wash
the cement out before it has set, a heavy canvas covered with pitch,
etc., upon which the concrete is deposited, is sometimes used ; or
the water may be carried away in temporary channels, until the
concrete in the artificial bed shall have set, when the water-ways
may be filled with semi-fluid cement mortar. Below is an account
of the method of stopping a very troublesome spring encountered
in laying the foundation of the dry-dock at the Brooklyn Navy
Yard.
"The dock is a basin composed of stone masonry resting on
piles. The foundation is 42 feet below the surface of the ground
and 37 feet below mean tide. In digging the pit for the founda-
tion, springs of fresh water were discovered near the bottom, which
proved to be very troublesome. The upward pressure of the water
was so great as to raise the foundation, however heavily it was loaded.
The first indication of undermining by these springs was the settling
of the piles of the dock near by. In a day it made a cavity in which
a pole was run down 20 feet below the foundation timbers. Into
this hole were thrown 150 cubic feet of stone, which settled 10 feet
during the night ; and 50 cubic feet more, thrown in the following
day, drove the spring to another place, where it burst through a
bed of concrete 2 feet thick. This new cavity was filled with
concrete, but the precaution was taken of putting in a tube so as to
permit the water to escape ; still it burst through, and the opera-
tion was repeated several times, until it finally broke out through a
heavy body of cement 14 feet distant. In this place it undermined
the foundation piles. These were then driven deeper by means of
followers; and a space of L,000 square feet around the spring was
then planked, forming a floor on which was laid a layer of brick in
AET. 1.] THE SOIL. 197
dry cement, and on that a layer of brick set in mortar, and the
foundation was completed over all. Several vent-holes were left
through the floor and the foundation for the escape of the water.
The work was completed in 1851, and has stood well ever since." *
287. Consolidating the Soil. A soft, clayey soil can be greatly
improved by spreading a thin layer of sand, dry earth, or broken
stone over the bed of the foundation and pounding it into the soil.
If the soil is very soft, compacting the surface will be insufficient ;
in this case the soil may be consolidated to a considerable depth by
driving short piles into it. For this purpose small piles — say 6
feet long and 6 inches in diameter — serve better than large ones;
and they can be driven with a hand-maul or by dropping a heavy
block of wood with a tackle attached to any simple frame, or by a
hand pile-driver (§ 335). They may be driven as close together as
necessary, although 2 to 4 feet in the clear is usually sufficient.
The latter method of compacting the soil is far more efficient than
pounding the surface. In the case of impact upon earth, the im-
mediate layers are compressed at once, and by their inertia and
adhesion to the surrounding soil they intercept the effect of the
blow, and thus prevent the consolidation of the lower strata. Even
though the effect of a blow is not communicated to any considerable
depth, the heavy masses of masonry make themselves felt at great
depth, and hence for heavy buildings it is necessary to consolidate
the lower strata. This can be done most easily and most efficiently
by driving piles (see Art. 2).
In this connection it is necessary to remember that clay is com-
pressible, while sand is not. Hence this method of consolidating
soils is not applicable to sand, and is not very efficient in soils
largely composed of it.
288. Sand Piles. Experiments show that in compacting the
soil by driving piles, it is better to withdraw them and immediately/
fill the holes with sand, than to allow the wooden piles to remain.
This advantage is independent of the question of the durability of
the wood. When the wooden pile is driven, it compresses the soil
an amount nearly or quite equal to the volume of the pile, and
when the latter is withdrawn this consolidation remains, at least
temporarily. If the hole is immediately filled with sand this com-
* Delafield's Foundations in Compressible Soils, p. 14r— a pamphlet published by
the Engineer's Department of the U. S. Army.
198 ORDINARY FOUNDATIONS. [CHAP. X.
pression is retained permanently, and the consolidation may be still
farther increased by ramming the sand in in thin layers, owing to
the ability of the latter to transmit pressure laterally. And further,
the sand pile will support a greater load than the wooden pile; for,
since the sand acts like innumerable small arches reaching from
one side of the hole to the other, more of the load is transmitted to
the soil on the sides of the hole. To secure the best results, the
sand should be fine, sharp, clean, and of uniform size.
289. When the piles are driven primarily to compact the soil,
it is customary to load them and also the soil between them, either
by cutting the piles off near the surface and laying a tight platform
of timber on top of them (see § 320), or by depositing a bed of con-
crete between and over the heads of the piles (see § 319).
If the soil is very soft or composed largely of sand, this method
is ineffective; in which case long piles are driven as close together
as is necessary, the supporting power being derived either from the
resting of the piles upon a harder substratum or from the buoyancy
due to immersion in the semi-liquid soil. This method of securing
a foundation by driving long piles is very expensive, and is seldom
resorted to for buildings, since it is generally more economical to
increase the area of the foundation.
290. Layers of Sand. If the soil is very soft, it may be ex-
cavated and replaced by sand. The method of using sand for piles
has been described in § 288, which see. The opportunities for the
use of sand in foundations are numerous, and the employment of
it would, in many constructions, promote economy and stability.
The simplest method of using sand for this purpose is to excavate
a trench or pit to the proper depth, and fill it by depositing succes-
sive layers of sand, each of which should be thoroughly settled by
a heavy beetle before laying the next. To cause the sand to pack
firmly, it should be slightly moistened before being placed in the
trench.
Sand, when used in this way, possesses the valuable property of
assuming a new position of equilibrium and stability should the
soil on which it is laid yield at any of its points ; not only does this
take place along the base of the sand bed, but also along its edges
or sides. The bed of sand must be thick enough to distribute the
pressure on its upper surface over the entire base. Thea-e is no way
of telling what this thickness should be, except by trial.
ABT. 2.] DESIGN ING THE FOOTING. 199
291. The following examples, cited by Trautwine,* are interest-
ing as showing the surprising effect of even a thin layer of sand
•or gravel :
"Some portions of the circular brick aqueduct for supplying
Boston with water gave a great deal of trouble when its trenches
passed through running quicksands and other treacherous soils.
•Concrete was tried, but the wet quicksand mixed itself with it and
Allied it. Wooden cradles, etc., also failed ; and the difficulty was
overcome by simply depositing in the trenches about two feet in
depth of strong gravel.
"Smeaton mentions a stone bridge built upon a natural bed of
gravel only about 2 feet thick, overlying deep mud so soft that an
iron bar 40 feet long sank to the head by its own weight. Although
a wretched precedent for bridge building, this example illustrates
the bearing power of a thick layer of well-compacted gravel."
AKT. 2. DESIGNING THE TOOTING.
292. LOAD TO BE SUPPORTED. The first step is to ascertain the
load to be supported by the foundation. This load consists of three
parts : (1) the building itself, (2) the movable loads on the floors
.and the snow on the roof, and (3) the part of the load that may be
transferred from one part of the foundation to the other by the
force of the wind.
293. The weight of the building is easily ascertained by calcu-
lating the cubical contents of all the various materials in the struct-
ure. If the weight is not equally distributed, care must be taken,
to ascertain the proportion to be carried by each part of the foun-
dation. For example, if one vertical section of the wall is to con-
tain a number of large windows while another will consist entirely
of solid masonry, it is evident that the pressure on the foundation
under the first section will be less than that under the second.
In this connection it must be borne in mind that concentrated
pressures are not transmitted, undiminished, through a solid mass
in the line of application, but spread out in successively radiating
lines ; hence, if any considerable distance intervenes between the
foundation and the point of application of this concentrated load,
* Engineer's Pocket-book (ed. 1885), p. 634.
198 ORDINARY FOUNDATIONS. [CHAP. X.
pression is retained permanently, and the consolidation may be still
farther increased by ramming the sand in in thin layers, owing to
the ability of the latter to transmit pressure laterally. And further,
the sand pile will support a greater load than the wooden pile; for,
since the sand acts like innumerable small arches reaching from
one side of the hole to the other, more of the load is transmitted to
the soil on the sides of the hole. To secure the best results, the
sand should be fine, sharp, clean, and of uniform size.
289. When the piles are driven primarily to compact the soil,
it is customary to load them and also the soil between them, either
by cutting the piles off near the surface and laying a tight platform
of timber on top of them (see § 320), or by depositing a bed of con-
crete between and over the heads of the piles (see § 319).
If the soil is very soft or composed largely of sand, this method
is ineffective; in which case long piles are driven as close together
as is necessary, the supporting power being derived either from the
resting of the piles upon a harder substratum or from the buoyancy
due to immersion in the semi-liquid soil. This method of securing
a foundation by driving long piles is very expensive, and is seldom
resorted to for buildings, since it is generally more economical to
increase the area of the foundation.
290. Layers of Sand. If the soil is very soft, it may be ex-
cavated and replaced by sand. The method of using sand for piles
has been described in § 288, which see. The opportunities for the
use of sand in foundations are numerous, and the employment of
it would, in many constructions, promote economy and stability.
The simplest method of using sand for this purpose is to excavate
a trench or pit to the proper depth, and fill it by depositing succes-
sive layers of sand, each of which should be thoroughly settled by
a heavy beetle before laying the next. To cause the sand to pack
firmly, it should be slightly moistened before being placed in the
trench.
Sand, when used in this way, possesses the valuable property of
assuming a new position of equilibrium and stability should the
soil on which it is laid yield at any of its points ; not only does this
take place along the base of the sand bed, but also along its edges
or sides. The bed of sand must be thick enough to distribute the
pressure on its upper surface over the entire base. Thei-e is no way
of telling what this thickness should be, except by trial.
ART. 2.] DESIGNING THE FOOTING. 199
291. The following examples, cited by Trautwine,* are interest-
ing as showing the surprising effect of even a thin layer of sand
or gravel :
"Some portions of the circular brick aqueduct for supplying
Boston with water gave a great deal of trouble when its trenches
passed through running quicksands and other treacherous soils.
Concrete was tried, but the wet quicksand mixed itself with it and
killed it. Wooden cradles, etc., also failed ; and the difficulty was
overcome by simply depositing in the trenches about two feet in
depth of strong gravel.
"Smeaton mentions a stone bridge built upon a natural bed of
gravel only about 2 feet thick, overlying deep mud so soft that an
iron bar 40 feet long sank to the head by its own weight. Although
a wretched precedent for bridge building, this example illustrates
the bearing power of a thick layer of well-compacted gravel."
AKT. 2. DESIGNING THE FOOTING.
292. LOAD TO BE STTPPOKTED. The first step is to ascertain the
load to be supported by the foundation. This load consists of three
parts : (1) the building itself, (2) the movable loads on the floors
and the snow on the roof, and (3) the part of the load that may be
transferred from one part of the foundation to the other by the
force of the wind.
293. The weight of the building is easily ascertained by calcu-
lating the cubical contents of all the various materials in the struct-
ure. If the weight is not equally distributed, care must be taken
to ascertain the proportion to be carried by each part of the foun-
dation. For example, if one vertical section of the wall is to con-
tain a number of large windows while another will consist entirely
of solid masonry, it is evident that the pressure on the foundation
under the first section will be less than that under the second.
In this connection it must be borne in mind that concentrated
pressures are not transmitted, undiminished, through a solid mass
in the line of application, but spread out in successively radiating
lines ; hence, if any considerable distance intervenes between the
foundation and the point of application of this concentrated load,
* Engineer's Pocket-book (ed. 1885), p. 634.
200
ORDINARY FOUNDATIONS.
[CHAP,
the pressure will be nearly or quite uniformly distributed over the
entire area of the base. The exact distribution of the pressure can
not be computed.
The following data will be useful in determining the weight of
the structure :
TABLE 24.
WEIGHT OF MASONRY.
KIND OF MASONRY.
WEIGHT
IN
LBS. PER CU. FT,
Brick- work, pressed brick, thin joints
" ordinary quality
soft brick, thick joints
Concrete, best
<c porous
Granite or Limestone, well dressed throughout
" " " rubble, well dressed, with mortar
" " " " roughly dressed, with mortar
" " " " well dressed, dry
" " " " roughly dressed, dry
Mortar, dried
Sandstone. (Deduct TV from the result for the corresponding
granite or limestone masonry as above.)
145
125
100
160
130
165
155
150
140
125
100
Ordinary lathing and plastering weighs about 10 Ibs. per sq. ft.
The weight of floors is approximately 10 Ibs. per sq. ft. for dwell-
ings ; 25 Ibs. per sq. ft. for public buildings ; and 40 or 50 Ibs. per
sq. ft. for warehouses. The weight of the roof varies with the kind
of covering, the span, etc. A shingle roof may be taken at 10 Ibs.
per sq. ft., and a roof covered with slate or corrugated iron at 25>
Ibs. per sq. ft.
294. The movable load on the floor depends upon the nature of
the building. For dwellings, it does not exceed 10 Ibs. per sq. ft. ;.
for large office buildings, it is usually taken at 20 Ibs. per sq. ft.;1
for churches, theatres, etc., the maximum load — a crowd of people
— may reach 100 Ibs, per sq. ft. ; for stores, warehouses, factories^
ART. 2.] DESIGNING THE FOOTING. 201
etc., the load will be from 100 to 400 Ibs. per sq. ft., according to
the purposes for which they are used. Floors of large buildings in
which dense crowds of people are liable to congregate may be loaded,
to 100 or even 150 Ibs. per sq. ft. However, there is no probability
that any such aggregation of load will come upon the foundations
as would be represented by 150 pounds for every square foot of
flooring in a building. The amount of moving load to be assigned
for in any particular case is a matter of judgment.
The weight of the snow on the roof will vary from 0, for a
building in a warm climate, to 20 Ibs. per sq. ft., for one with
a flat roof situated in the latitude of New England or northern
Michigan.
Attention must be given to the manner in which the weight of
the roof and floors is transferred to the walls. For example,, if the
floor joists of a warehouse run from back to front, it is evident that
the back and front walls alone will carry the weight of the floors
and of the goods placed upon them, and this will make the pressure
upon the foundation under them considerably greater than under
the other walls. Again, if a stone-front is to be carried on an arch
or on a girder having its bearings on piers at each side of the bnild-
ing, it is manifest that the weight of the whole superincumbent
structure, instead of being distributed equally on the foundation
under the front, will be concentrated on that part of the founda-
tion immediately under the piers.
295. The pressure of the wind against towers, tall chimneys,,
etc., will cause a concentration of the weight of the structure upon
one side of the foundation. The maximum horizontal pressure of
the wind is usually taken as 50 Ibs. per sq. ft. on a flat surface per-
pendicular to the wind, and on a cylinder at about 30 Ibs. per sq.
ft. of the projection of the surface. The pressure upon an inclined
surface, as a roof, is about 1 Ib. per sq. ft. per degree of inclination
to the horizontal. For example, if the roof has an inclination of
30° with the horizontal, the pressure of the wind will be about 30
Ibs. per sq. ft.
The effect of the wind will be considered in §§ 301-4.
296. AREA REQUIRED. Having determined the pressure which
may safely be brought upon the soil, and having ascertained the
weight of each part of the structure, the area required for the foun-
dation is easily determined by dividing the latter by the former.
202 ORDINARY FOUNDATIONS [CHAP. X.
Then, having found the area of foundation, the base of the struct-
ure must be extended by footings of masonry, concrete, timber,
etc., so as to (1) cover that area and (2) distribute the pressure uni-
formly over it. The two items will be considered in inverse order.
297. CENTER OF PRESSURE AND CENTER OF BASE. In construct-
ing a foundation the object is not so much to secure an absolutely
unyielding base as to secure one that will settle as little as possible,
and uniformly. All soils will yield somewhat under the pressure of
any building, and even masonry itself is compressed by the weight
of the load above it. The pressure per square foot should, there-
fore, be the same for all parts of the building, and particularly of
the foundation, so that the settlement may be uniform. This can
be secured only when the axis of the load (a vertical line through
the center of gravity of the weight) passes through the center of
the area of the foundation. If the axis of pressure does not coincide
exactly with the axis of the base, the ground will yield most on the
side which is pressed most ; and as the ground yields, the base as-
sumes an inclined position, and carries the lower part of the struct- .
nre with it, thus producing unsightly cracks, if nothing more.
The coincidence of the axis of pressure with the axis of resist-
ance is of first importance. This principle is self-evident, and yet
the neglect to observe it is the most frequent cause of failure in the
foundations of buildings.
Fig. 50 is an example of the way in which this principle is
violated. The shaded portion
represents a heavily loaded exte-
rior wall, and the light portion a
lightly loaded interior wall. The
foundations of the two walls are
rigidly connected together at
•^ their intersection. The center
" •' of the load is under the shaded
FIG. so. section, and the center of the
area is under the interior of the wall ; consequently the exterior
wall is caused to incline outward, producing cracks at or near the
-corners of the building. Doubtless the two foundations are con-
nected in the belief that an increase of the bearing surface is of first
importance ; but the true principle is that the coincidence of the
axis of pressure with the axis of resistance is the most important.
AET. 2.]
THE FOOTING.
203
Fig. 51 is another illustration of the same principle. The foun-
dation is continuous under the opening,
and hence the center of the foundation is to
the left of the center of pressure; conse-
quently the wall inclines to the right, pro- ^
ducing cracks, usually over' the opening.*
298. The center of the load can be made
to fall inside of the center of foundation by
extending the footings outwards, or by cur- . —
tailing the foundations on the inside. The __ -
latter finds exemplification in the properly FIG. 51.
constructed foundation of a wall containing a number of openings.
For example, in Fig. 52, if the foundation is uniform under the
entire front, the center of pressure must be
outside of the center of the base ; and conse-
quently the two side walls will incline outward,
and show cracks over the openings. If the
width of the foundation under the openings
be decreased, or if this part of the foundation
be omitted entirely, the center of pressure
will fall inside of the center of base and the
walls will tend to incline inwards, and hence
be stable.
299. Conclusions. One conclusion to be
FIG. 52. drawn from the above examples is that the
foundation of a wall should never be connected with that of another
wall either much heavier or much lighter than itself. Both are
equally objectionable.
A second conclusion is that the axis of the load should strike a
little inside of the center of the area of the base, to make sure that
it will not be outside. Any inward inclination of the wall is ren-
dered impossible by the interior walls of the building, the floor-
beams, etc. ; while an outward inclination can be counteracted only
by anchors and the bond of the masonry. A slight deviation of the
axis of the load outward from the center of the base has a marked
effect, and is not easily counteracted by anchors.
* For an account showing the violation of this principle in the construction of
the Cooper Institute Building, New York City, and the method used to remedy it, see
Sanitary Migine&r, vol. xii. pp. 465-68.
£U
A
202 ORDINARY FOUNDATIONS [CHAP. X.
Then, having found the area of foundation,, the base of the struct-
ure must be extended by footings of masonry, concrete, timber,
etc., so as to (1) coyer that area and (2) distribute the pressure uni-
formly over it. The two items will be considered in inverse order.
297. CENTER OF PRESSURE AND CENTER OF BASE. In construct-
ing a foundation the object is not so much to secure an absolutely
unyielding base as to secure one that will settle as little as possible,
and uniformly. All soils will yield somewhat under the pressure of
any building, and even masonry itself is compressed by the weight
of the load above it. The pressure per square foot should, there-
fore, be the same for all parts of the building, and particularly of
the foundation, so that the settlement may be uniform. This can
be secured only when the axis of the load (a vertical line through
the center of gravity of the weight) passes through the center of
the area of the foundation. If the axis of pressure does not coincide
exactly with the axis of the base, the ground will yield most on the
side which is pressed most ; and as the ground yields, the base as-
sumes an inclined position, and carries the lower part of the struct- ,
nre with it, thus producing unsightly cracks, if nothing more.
The coincidence of the axis of pressure with the axis of resist-
ance is of first importance. This principle is self-evident, and yet
the neglect to observe it is the most frequent cause of failure in the
foundations of buildings.
50 is an example of the way in which this principle is
violated. The shaded portion
represents a heavily loaded exte-
rior wall, and the light portion a
lightly loaded interior wall. The
foundations of the two walls are
rigidly connected together at
their intersection. The center
of the load is under the shaded
FIG. so. section, and the center of the
area is under the interior of the wall ; consequently the exterior
wall is caused to incline outward, producing cracks at or near the
corners of the building. Doubtless the two foundations are con-
nected in the belief that an increase of the bearing surface is of first
importance ; but the true principle is that the coincidence of the
axis of pressure with the axis of resistance is the most important.
ART. 2.]
THE FOOTING.
203
I.
.a—
Kg. 51 is another illustration of the same principle. The foun-
dation is continuous under the opening,
and hence the center of the foundation is to
the left of the center of pressure ; conse-
quently the wall inclines to the right, pro-
ducing cracks, usually over' the opening.*
298. The center of the load can be made
to fall inside of the center of foundation by
•extending the footings outwards, or by cur-
tailing the foundations on the inside. The
latter finds exemplification in the properly FIG. si.
constructed foundation of a wall containing a number of openings.
For example, in Fig. 52, if the foundation is uniform under the
entire front, the center of pressure must be
outside of the center of the base ; and conse-
quently the two side walls will incline outward,
and show cracks over the openings. If the
width of the foundation under the openings
be decreased, or if this part of the foundation
be omitted entirely, the center of pressure
will fall inside of the center of base and the
walls will tend to incline inwards, and hence
be stable.
299. Conclusions. One conclusion to be
FIG. 52. drawn from the above examples is that the
foundation of a wall should never be connected with that of another
wall either much heavier or much lighter than itself. Both are
equally objectionable.
A second conclusion is that the axis of the load should strike a
little inside of the center of the area of the base, to make sure that
it will not be outside. Any inward inclination of the wall is ren-
dered impossible by the interior walls of the building, the floor-
beams, etc. ; while an outward inclination can be counteracted only
by anchors and the bond of the masonry. A slight deviation of the
axis of the load outward from the center of the base has a marked
effect, and is not easily counteracted by anchors.
* For an account showing the violation of this principle in the construction of
the Cooper Institute Building, New York City, and the method used to remedy it, see
Sanitary Mtyineer, vol. xii. pp. 465-68.
T T \
204 OEDOTAKY FOUNDATIONS. [CHAP. X.
The above conclusions may be summarized in the following
principle : All foundations should be so constructed as to compress
the ground slightly CONCAVE upwards, rather than CONVEX up-
wards. On even slightly compressible soils, a small difference in
the pressure on the foundation will be sufficient to cause the bed to
become convex upwards. At Chicago, an omission of 1 to 2 per
cent, of the weight (by leaving openings) usually causes sufficient
convexity to produce unsightly cracks. With very slight differences
of pressure on the foundation, it is sufficient to tie the building
together by careful bonding, by hoop-iron built in over openings,
and by heavy bars built in where one wall joins another.
300. INDEPENDENT PIERS. The art of constructing founda-
tions on compressible soil has been brought to a high degree of
development by the architects of Chicago. The special feature of
the practice in that city is what is called "the method of independ-
ent piers ;" that is, each tier of columns, each pier, each wall, etc. ,
has its own independent foundation, the area of which is propor-
tioned to the load on that part.* The interior walls are fastened to
the exterior ones by anchors which slide in slots. For a detailed
account of the methods employed in one of the best and largest
buildings erected there, see Sanitary Engineer, Dec. 10, 1885.
301. EFFECT OF THE WIND. Overturning. The preceding dis-
cussion refers to the total weight that is to come upon the foun-
dation. The pressure of the wind against towers,
tall chimneys, etc., transfers the point of applica-
tion of the load to one side of the foundation. The
method of computing the position of the center
of the pressure on the foundation under the action
of the wind is illustrated in Tig. 53, in which
ABED represents a vertical section, of the-
tower;
a is a point horizontally opposite the center of
Q the surface exposed to the pressure of the
wind and vertically above the center of grav-
ir o
FIG. 53. ity of the tower;
* This method was first made known to the public by Frederick Bauman, of Chi-
cago, in a pamphlet entitled " The Method of Constructing Foundations on Isolated
Piers," published by him in 1872. The above examples and principles are from that
pamphlet.
ART. 2.] DESIGNING THE FOOTING. 205
C is the position of the center of pressure when there is no wind ;
N is the center when the wind is acting.
For convenience, let
P = the maximum pressure on the foundation, per unit of area;
p = the pressure of the wind per unit of area (see § 295);
H = the total pressure of the wind against the exposed surface ;
W = the weight of that part of the structure above the section
considered, — in this case, A B ;
JS = the area of the horizontal cross section ;
/ = the moment of inertia of this section ;
I = the distance A B ;
li = the distance a C ;
d = the distance N C ;
M = the moment of the wind.
"When there is no horizontal force acting, the load on A B is
uniform ; but when there is a horizontal force acting — as, for ex-
ample, the wind blowing from the right, — the pressure is greatest
near A and decreases towards B. To find the law of the variation
of this pressure, consider the tower as a cantilever beam. The
maximum pressure at A will be that due to the weight of the tower
plus the compression due to flexure ; and the pressure at B will be
the compression due to the weight minus the tension due to flexure.
W
The uniform pressure due to the weight is -^-. The strain at A due
Ml
to flexure is, by the principles of the resistance of materials,
Then the maximum pressure per unit of area at A is
and the minimum pressure at JB is
_
~~ 8 21 ........
Equations (1) and (2) are perfectly general ; they are applicable
to any cross section, and also to any system of horizontal and ver-
tical forces. In succeeding chapters they will be employed in
finding the unit pressure in masonry dams, bridge piers, arches,,
etc.
OKDDSfAKY FOUNDATIONS.
[CHAP,
The value of / in the above formulas is given in Fig. 54 for the
sections occurring most frequently in practice. Notice that I is the
dimension parallel to the direction of the wind, and I the dimen-
sion perpendicular to the direction of the wind.
FIG. 54.
302. If the area of the section A B, Pig. 53, is a rectangle,
S=ll, and / = -^ I r. Substituting these values in equation (1)
gives
p== W 6M_
is 0 0 v
The moment of the wind, M, is equal to the product of its total
pressure, Hy and the distance, h, of the center of pressure above
the horizontal section considered; or M— H. h. II is equal to
the pressure per unit of area, p9 multiplied ty the area of the sur-
face exposed to the pressure of the wind. Substituting the above
value of M in equation (3) gives
(4)
bl*
To still further simplify the above formula, notice that rig. 53
gives the proportion
Hi W :: NC :aC,
from which
H.aO=
or, changing the nomenclature,
= Wd.
Notice that the last relation can also be obtained directly by the
principle of moments. Substituting the value of H. 7i9 as above, in
equation (4) gives
W ZWd
Tb "+" ~TP~~> ( ;
which is a convenient form for practical application.
ART. 2.] DESIGNING THE FOOTING. 207
An examination of equation (5) shows that when d = N C = ^ I,
the maximum pressure at A is twice the average. Notice also that
under these conditions the pressure at B is zero. This is equiva-
lent to what is known,, in the theory of arches, as the principle of
the middle third. It shows that as long as the center of pressure
lies in the middle third, the maximum pressure is not more than
twice the average pressure, and that there is no tension at B.
The above discussion of the distribution of the pressure on the
foundation is amply sufficient for the case in hand ; however, the
subject is discussed more fully in the chapter on Stability of Masonry
Dams (see Chapter XIII).
303.. The average pressure per unit on A B has already been
adjusted to the safe bearing power of the soil, and if the maximum
pressure at A does not exceed the ultimate bearing power, the occa-
sional maximum pressure due to the wind will do no harm ; but if
this maximum exceeds or is dangerously near the ultimate strength
of the soil, the base must be widened.
304. Sliding. The pressure of the wind is a force tending to
slide the foundation horizontally. This is resisted by the friction
caused by the weight of the entire structure, and also by the earth,
around the base of the foundation, and hence there is no need, in
this connection, of considering this manner of failure.
305. DESIGNING THE FOOTING. The term footing is usually un-
derstood as meaning the bottom course or courses of masonry which
extend beyond the faces of the wall. It will be used here as apply-
ing to the material — whether masonry, timber, or iron — employed
to increase the area of the base of the foundation. Whatever the
character of the soil, footings should extend beyond the face of the
wall (1) to add to the stability of the structure and lessen the dan-
ger of the work's being thrown out of plumb, and (2) to distribute
the weight of the structure over a larger area and thus decrease
the settlement due to the compression of the ground. To serve
the first purpose, footings must be securely bonded to the body of
the wall; and to produce the second effect, they must have sufficient
strength to resist the transverse strain to which they are exposed.
In ordinary buildings the distribution of the weight is more impor-
tant than adding to the resistance to overturning, and hence only
the former will be considered here.
The area of the foundation may be increased until the inherent
208 OKDINARY FOUNDATIONS. [CHAP. X.
bearing power of the area covered is sufficient to support the load
(1) by extending the bottom courses of masonry, or (2) by the use
of one or more layers of timbers, railroad rails, or steel I-beams, or
(3) by resting the structure upon inverted masonry arches.
306. Off-sets of Masonry Footings. The area of the foundation
having been determined and its center having been located with
reference to the axis of the load (§ 297), the next step is to deter-
mine how much narrower each footing course may be than the one
next below it. The projecting part of the footing resists as a beam
fixed at one end and loaded uniformly. The load is the pressure
on the earth or on the course next below. The off-set of such a
course depends upon the amount of the pressure, the transverse
strength of the material, and the thickness of the course.
To deduce a formula for the relation between these quantities,
let
P = the pressure, in tons per square foot, at the bottom of the
footing course under consideration ;
R = the modulus of rupture of the material, in pounds per
square inch ;
p =1 the greatest possible projection of the footing course, in
inches ;
t = the thickness of the footing course, in inches.
The part of the footing course that projects beyond the one above
it, is a cantilever beam uniformly loaded. From the principles of
the resistance of materials, we know that the upward pressure of the
earth against the part that projects multiplied l>y one half of the
length of the projection is equal to the continued product of one
sixth of the modulus of rupture of the material, the breadth of the
footing course, and the square of the thickness. Expressing this
relation in the above nomenclature and reducing, we get the for-
mula
_^/~S~ ,rv
p — J y y ••••••• (y)
41. O Jr
or, with sufficient accuracy,
Hence the projection available with any given thickness, or the
thickness required for any given projection, may easily be computed
ART. 2.]
THE FOOTING.
209
by equation (7). Notice that with, the off -set given by the above
iormula the stone would be on the point of breaking.
307. The margin to be allowed for safety will depend upon the
care used in computing the loads, in selecting the materials for the
footing courses, and in bedding and placing them. If all the loads
have been allowed for at their probable maximum value, and if the
material is to be reasonably uniform in quality and laid with care,
then a comparatively small margin for safety is sufficient ; but if
all the loads have not been carefully computed, and if the job is to
be done by an unknown contractor, and neither the material nor
the work is to be carefully inspected, then a large margin is neces-
sary. As a general rule, it is better to assume, for each particular
case, a factor of safety in accordance with the attendant conditions
of the problem than blindly to use the results deduced by the
.application of some arbitrarily assumed factor. The following table
is given for the convenience of those who may wish to use 10 as a
factor of safety.
TABLE 25.
SAFE OFF-SET FOB MASONRY FOOTING COURSES, IN TERMS OF THE THICK-
NESS OF THE COURSE, USING 10 AS A FACTOR OF SAFETY.
For limitations, see § 308.
OFF-SET FOR A PRES-
SURE, IN TONS PKR SQ.
KIND OF STONE.
12, IN LBS.
PERSQ. IN.
FT., ON THE BOTTOM OF
THE COURSE, OF
0.5
1.0
2.0
Blue-stone flagging (see page 12)
2,700
3.6
2.6
1.8
Granite (see page 12)
1,800
2.9
2 1
1.5
Limestone (see p&ge 12)
1,500
2 7
1.9
1.3
Sandstone (see page 12j
1,200
2.6
1.8
1.3
Slate (see page 12)
5,400
5.0
3.6
2.5
Best Hard Brick (see pages 40 41)
1,500
2.7
1.9
1.3
Hard Brick (see pages 40 41)
800
1.9
1.4
0.8
( 1 Portland ) 1Q d
•Concrete (see page 108) -1 2 sand - , J
150
0.8
0.6
0.4
( 3 pebbles ) 01Q
( 1 Kosendale ) in -,
Concrete (see page 108) \ 2 sand [ 1U Ws
(3 pebbles j ola
80
0.6
0.4
0.3
To illustrate the method of using the preceding table, assume
that it is desired to determine the off-set for a limestone footing
course when the pressure on the bed of the foundation is 1 ton per
square foot, using 10 as a factor of safety. In the table, opposite
210 OKDIKAKY FOUNDATIONS. [CHAP. X.
limestone, in next to the last column, we find the quantity 1.9,
This shows that under the conditions stated, the off-set may be 1.$
times the thickness of the course.
If it is desired to use any other factor of safety, it is only neces-
sary to substitute for R, in the preceding formula, the desired frac-
tional part of that quantity as given in the second column of the
above table. For example, assume that it is necessary to use lime-
stone in the foundation, and that it is required to draw in the foot-
ing courses as rapidly as possible. Assume also that the pressure,
P, on the base of the foundation is 2 tons per square foot. If the
limestone is of the best, and if it is laid with great care, it will be
sufficient to nse 4 as a factor of safety. Under these conditions^
equation (7) as above gives
That is, the projection may be 2. 3 times the thickness of the course.
308. Strictly, the above method is correct only when the footing
is composed wholly of stones whose thickness is equal to the thick-
ness of the course, and which project less than half their length,
and are also well bedded. The values in the table agree very well
with the practice of the principal architects and engineers for ham-
mer-dressed stones laid in good cement mortar.
The preceding results will be applicable to built footing courses
only when the pressure above the course is less than the safe strength
of the mortar (see § 136 and § 157). The proper projection for
rubble masonry lies somewhere between the values given for stone
and those given for concrete. If the rubble consists of large stones
well bedded in good strong mortar, then the values for this class of
masonry will be but little less than those given in the table. If the
rubble consists of small irregular stones laid with Portland or Rosen-
dale cement mortar, the projection should not much exceed that
given for concrete. If the rubble is laid in lime mortar, the pro-
jection of the footing course should not be more than half that
allowed when cement mortar is used.
Notice that drawing in the footing courses decreases the area
under pressure, and consequently increases the pressure per unit of
area ; hence the successive projections should decrease from t he-
bottom towards the top.
AET. 2.] DESIGNING THE FOOTING. 211
309. Timber Footing. In very soft earth it would be inexpe-
dient to use masonry footings, since the foundation would be very
deep or occupy the space usually devoted to the cellar. One method
of overcoming this difficulty consists in constructing a timber grat-
ing, sometimes called a grillage, by setting a series of heavy timbers. •
firmly into the soil, and laying another series transversely on top of
these. The timbers may be fastened at their intersections by spikes.
or drift-bolts (§ 381) if there is any possibility of sliding, which is
unlikely in the class of foundations here considered. The earth
should be packed in between and around the several beams. A
flooring of thick planks, often termed a platform, is laid on top of
the grillage to receive the lowest course of masonry. In extreme
cases, the timbers in one. or more of the courses are laid close to-
gether. Timber should never be used except where it will be always
wet.
The amount that a course of timber may project beyond the one
next above it can be determined by equation (7), page 208. Making
72 in that equation equal to 1,000 — the value ordinarily used, — and
solving, we obtain the following results for the safe projection: If
the pressure on the foundation is 0.5 ton per square foot, the safe
projection is 7. 5 times the thickness of the course ; if the pressure
is 1 ton per square foot, the safe projection is 5.3 times the thick-
ness of the course ; and if the pressure is 2 tons per square foot, the
safe projection is 3.7 times the thickness of the course. The above
values give a factor of safety of about 10. To use any other factor,
insert in equation (7), above, the corresponding fractional part of the
ultimate transverse strength of the particular timber to be used,
and solve.
310. This method of increasing the area of the footing is much
used at ISTew Orleans. The Custorn-house at that place is founded
upon a plank flooring laid 7 feet below the street pavement. A
timber grillage, consisting of logs 12 inches in diameter laid side by
side, is laid upon the floor, over which similar logs are placed trans-
versely, 2 or 3 feet apart in the clear. The spaces are filled with
concrete, and an additional thickness of 1 foot of concrete is placed
over the whole. The grillage covers the entire site of the building —
300 feet square. The settlement has been very great, and not uni-
form. This is not the fault of the general method employed, but is
212 ORDINARY FOUNDATIONS. [CHAP. X
due to the failure to proportion the area of each part of the founda-
tion to the load to be supported.
311. Steel-rail Footing, Very recently, steel, usually in the form
of railroad rails or I-beams, has been used instead of timber in
foundations. The rails or I-beams are placed side by side, and
concrete is rammed in between them.
Steel is superior to timber for this purpose, in that the latter
can be used only where it is always wet, while the former is not
affected by variations of wetness and dryness. Ten years' experi-
ence in this use of steel at Chicago shows that after a short time
the surface of the metal becomes encased in a coating which pre-
vents further oxidation. The most important advantage, however,
in this use of steel is that the off-set can be much greater with steel
or iron than with wood or stone ; and hence the foundations may he
shallow, and still not occupy the cellar space.
The proper off-set can be computed by a formula similar to that
of § 306. Making these computations, it is found that if the pressure
is 0.5 of a ton per square foot the off-set may bo about 30 times the
height of the rail ; and that if the pressure is 2 tons per foot the
off-set may be 15 times the height of the rail. There is no proba-
bility that in practice off-sets of such extreme lengths will ever be
required.
In the foundation of the Kookery Building, Chicago, the steel-
rail grillage consisted of four courses of rails, with bases nearly in
contact, filled in between with cement mortar, the longitudinal and
transverse courses alternating. The off-sefcs were 3 feet, the pres-
sure being 2 tons per square foot.
312. Inverted Arch. Inverted arches are frequently built under
and between the bases of piers, as shown in Fig. 55. Employed in
this way, the arch simply distributes
the pressure over a greater area; but
it is not well adapted to this use, for
(1) it is nearly impossible to prevent
end piers of a series from being
pushed outward by the thrust of the
Fia<55> arch, and (2) it is generally impos-
sible, with inverted arches, to make the areas of the different parts
of the foundation proportional to the load to be supported (see §
AKT. 3.] PREPARING THE BED. 213
297). The only advantage the inverted arch has over masonry
footings is in the shallower foundation obtained.
313. In a few cases masonry piers have been sunk to a solid sub-
stratum by excavating the material from the inside, and then resting
arches on these piers. This is an expensive method, and has essen-
tially the same objections as the inverted arch.
ART. 3. PREPARING- THE BED.
314. ON BOCK. To prepare a rock bed to receive a foundation
it is generally only necessary to cut away the loose and decayed por-
tions ol' the rock., and to dress it to a plane surface as nearly perpen-
dicular to the direction ol; the pressure as is practicable. If there
are any fissures, they should be filled with concrete. A rock that
is very much broken can be made amply secure for a foundation by
the liberal use of good cement concrete. The piers of the Niagara
Cantilever Bridge are founded upon the top of a bank of bowlders,
which were*, first cemented together with concrete.
Sometimes it is necessary that certain parts of a structure
start from a lower level than the others. In this case care should
be taken (1) to keep the mortar-joints as thin as possible, (2) to lay
the lower portions in co.ment, and (3) to proceed slowly with the
work ; otherwise the greater quantity of mortar in the wall on the
lower portions of the slope will cause greater settling there and a
consequent breaking of the joints at the stopping-places. The
bonding over the oil-sets should receive particular attention.
315. ON" FlEM EARTH. For foundations in such earths as hard
clay, clean dry gravel, or clean sharp sand., it is only necessary to
dig a trench from 3 to G feet deep, so that the foundation may be
below the disintegrating effect of frost. Provision should also be
rmuie for the drainage of the bed of the foundation.
With this class of foundations it often happens that one part of
the structure starts from a lower level than another. When this is
the ease great care is required. All the precautions mentioned in
the second paragraph of § 314 should be observed, and great care
should also bo taken so to proportion the load per unit of area that
the settlement of the foundation maybe uniform. This is difficult
to do, wince a variation <>ir a few feet in depth often makes a great
difference in the supporting power of the soil.
HUNT L1UAFJ
OKDI^AEY FOUNDATIONS. [CHAP. X.
316. IN WET GROUND. The difficulty in soils of this class is in
disposing of the water, or in preventing the semi-liquid soil from
running into the excavation. The difficulties are similar to those
met with in constructing foundations under water — see Chapter XII.
Three general methods of laying a foundation in this kind of soil
will be briefly described.
317. Coffer-Dam. If the soil is only moderately wet — not satu-
rated,— it is sufficient to inclose the area to be excavated with sheet
piles (boards driven vertically into the ground in contact with each
other). This curbing is a simple form of a coffer-dam (Art. 1,
Chap. XII). The boards should be sharpened wholly from one
side ; this point being placed next to the last pile driven causes
them to crowd together and make tighter joints. The sheeting may
be driven by hand, by a heavy weight raised by a tackle and then
dropped, or by an ordinary pile-driver (§§ 335-36). Unless the
amount of water is quite small, it will be necessary to drive a double
row of sheeting, breaking joints. It will not be possible to entirely
prevent leaking. The water that leaks in may be bailed out, or
pumped — either by hand or by steam (see § 395).
To prevent the sheeting from being forced inward, it may be
braced -by shores placed horizontally from side to side a'ncl abutting
against wales (horizontal timbers which rest against the sheet piles).
The bracing is put in successively from the top as the excavation
proceeds ; and as the masonry is built up, short braces between the
sheeting and the masonry are substituted for the long braces which
previously extended from side to side. Iron screws, somewhat
similar to jack-screws, are used, instead of timber shores, in exca-
vating trenches for the foundations of buildings, for sewers, etc.
If one length of sheeting will not reach deep enough, an addi-
tional section can be placed inside of the one already in position,
when the excavation has reached a sufficient depth to require it.
Ordinary planks 8 to 12 inches wide and I-} or 2 inches thick are
used.
For a more extended account of the use of coffer-dams, see
Chapter XII — Foundations Under Water, Art. 1 — Coffer- Darns.
318. In some cases the soil is more easily excavated if it is first
drained. To do this, dig a hole — a sump — into which the water will
drain and from which it may be pumped. If necessary, several
sumps may be sunk, and deepened as the excavation proceeds.
ART. 3.] PREPARING THE BED.
Quicksand or soft alluvium may sometimes be pumped out along
with the water by a centrifugal or a mud pump (§ 395 and § 448).
On large jobs, such material is sometimes taken out with a clam-
shell or Milroy dredge (§ 412).
319. Concrete. Concrete can frequently be used advantage-
ously in foundations in wet soils. If the water can be removed, the
concrete should be deposited in continuous layers, about 6 inches
thick, and gently rammed until the water begins to ooze out on the
upper surface (see § 153). If the water can not be removed, the
€oncrete may be deposited under the water (see § 154), although it
is more difficult to insure good results by this method than when
the concrete is deposited in the open air.*
320. Grillage. If the semi-liquid soil extends to a considerable
depth, or if the soft soil which overlies a solid substratum can not be
removed readily, it is customary to drive piles at uniform distances
over the area, and construct a grillage (see § 380) on top of them.
This construction is very common for bridge abutments (Chapter
XV). The piles should be sawed off (§ 378) below low- water, which
usually necessitates a coffer-dam (§ 317, and Art. 1 of Chapter XII),
.an cl the excavation of the soil a little below the low- water line.
For a more extended account of this method of laying a founda-
tion, see §§ 380-82.
321. In excavating shallow pits in sand containing a small
amount of water, dynamite cartridges have been successfully used to
drive the water out. A hole is bored with an ordinary auger and
the cartridge inserted and exploded. The explosion drives the water
back into the soil so far that, by working rapidly, the hole can be
excavated and a layer of concrete placed before the water returns.
322. CONCLUSION. It is hardly worth while here to discuss this
•subject further. It is one on which general instruction can not be
given. Each case must be dealt with according to the attendant
circumstances, and a knowledge of the method best adapted to any
given conditions comes only by experience.
* For the composition, cost, etc., of concrete, see Art. 2 of Chap. IV. pp. 102-12.
CHAPTER XL
PILE FOUNDATIONS.
323. DEFINITIONS. Pile. Although, a pile is generally under-
stood to be a round timber driven into the soil to support a load,
the term has a variety of applications which it will be well to explain,
Bearing Pile. One used to sustain a vertical load. This is the
ordinary pile, and usually is the one referred to when the word pile
is employed without qualification.
Sheet Piles. Thick boards or timbers driven in close contact
to inclose a space, to prevent leakage, etc. Generally they are con-
siderably wider than thick; but are sometimes square, in which case
they are often called close piles.
False Pile. A timber added to a pile after driving, to supple-
ment its length.
Foundation Pile. One driven to increase the supporting power
of the soil under a foundation.
Screiv Pile. An iron shaft to the bottom of which is attached
a broad-bladed screw having only one or two turns.
Disk Pile. A bearing pile near the foot of which a disk is keyed
or bolted to give additional bearing power.
Pneumatic Pile. A metal cylinder which is sunk by atmos-
pheric pressure. This form of pile will be discussed in the next
chapter (see § 431).
ART. 1. DESCRIPTIONS, AND METHODS OF DRIVING.
3£4, IRON PILES. Both cast and wrought iron are employed for
ordinary bearing piles, sheet piles, and for cylinders. Iron cylin-
ders are generally sunk either by dredging the soil from the inside
(§ 415), or by the pneumatic process (see the next chapter, particu-
larly §§ 431-35). For another method of employing iron cylinders,
see §§ 384-85.
216
ART. 1.] DESCRIPTIONS, AKD METHODS OF DRIVING. 217
Cast-iron piles are beginning to be used as substitutes for com-
mon wooden ones. Lugs or flanges are usually cast on the sides of
the piles, to which bracing may be attached for securing them in
position. A wood block is laid upon the top of the pile to receive
the hammer used in driving it; and, after being driven, a cap with
a socket in its lower side is placed upon the pile to receive the load.
The supporting power is sometimes increased by keying on an iron
disk. The advantages claimed for cast-iron piles are: (1) they are
not subject to decay; (2) they are more readily driven than wooden
ones, especially in stony ground or stiff clay; and (3) they possess
greater crushing strength, which, however, is an advantage only
when the pile acts as a column (see § 355). The principal disadvan-
tage is that they are deficient in transverse resistance to a suddenly
applied force. This objection applies only to the handling of the
piles before being driven, and to such as are liable, after being driven,
to sudden lateral blows, as from floating ice, logs, etc.
Recently, rolled sections of wrought-iron have been employed to a
limited degree for bearing-piles, but present prices prohibit an ex-
tended use of wrought-iron piles. It is possible that iron may take
the place of wood for piles where they are alternately wet and dry,
or where they are difficult to drive; but where the piles are always
wet — as is usually the case in foundation work, — wood is as durable
as iron; and hence, on account of cheapness, is likely to have the
preference.
325. SCREW PILES. These are generally wholly of iron, although
the stem is sometimes wood. The screw pile usually consists of a
rolled-iron shaft, 3 to 8 inches in diameter, having at its foot one or
two turns of a cast-iron screw, the blades of which may vary from 1-J-
to 5 feet in diameter. The piles ordinarily employed for light-
houses exposed to moderate seas or to heavy fields of ice have a
shaft 3 to 5 inches in diameter and blades 3 to 4 feet in diameter,
the screw weighing from 600 to 700 pounds. For bridge piers,
the shafts are from G to 8 inches and the blades from 4 to 6 feet in
diameter, the screw weighing from 1,500 to 4,000 pounds.
Screw piles were invented by Mitchell of Belfast, and are largely
used in Europe, but not to any great extent in this country. They
have been used in founding small light-houses on the sea-shore, for
signal stations in marine surveying, for anchorage for buoys, and
for various purposes inland.
218 PILE FOUNDATIONS. [CHAP. XI.
For founding beacons, etc., the screw pile has the special advan-
tage of not being drawn out by the upward force of the waves against
the superstructure. Even when all cohesion of the ground is de-
stroyed in screwing down a pile, a conical mass, with its apex at the
bottom of the pile and its base at the surface, would have to be
lifted to draw the pile out. The supporting power also is consider-
al 1 i owing to the increased bearing surface of the screw blade.
Screw piles have, therefore, an advantage in soft soil. They could
also be used advantageously in situations where the jar of driving
ordinary piles might disturb the equilibrium of adjacent structures.
326. These piles are usually screwed into the soil by men work-
ing with capstan bars. Sometimes a rope is wound around the
shaft and the two ends pulled in opposite directions by two capstans,
and sometimes the screw is turned by attaching a large cog-wheel to
the shaft by a friction-clutch, which is rotated by a worm-screw
operated by a hand crank. Of course steam or horse-power could
be used for this purpose.
The screw will penetrate most soil1. It will pass through loose
pebbles and stones without much difficulty, and push aside bowlders
of moderate size. Ordinary clay does not present much obstruction;
clean, dry sand gives the most difficulty. The danger of twisting
off the shaft limits the depth to which they may be sunk. Screw
piles with blades 4 feet in diameter have been screwed 40 feet into
a mixture of clay and sand. The resistance to sinking increases
very rapidly with the diameter of the screw; but under favorable
circumstances an ordinary screw pile can be sunk very quickly.
Screws 4 feet in diameter have, in less than two hours, been sunk
by hand-labor 20 feet in sand and clay, the surface of which was
20 feet below the water. For depths of 15 to 20 feet, an average of
4 to 8 feet per day is good work for wholly hand-labor.
For an illustrated and detailed account of the founding of a rail-
road bridge pier on screw piles, see Engineering News, Vol. XIII.
pp. 210-12.
327. DISK PILES. These differ but little from screw piles, a
fiat disk, instead of a screw, being keyed on at the foot of the iron
stem. Disk piles are sunk by the water-jet (§ 343). One of the few
cases in which they have been used in this country was in founding
an ocean pier on Coney Island, near ISTew York City. The shafts
were wrought-iron, lap-welded tubes, Sf inches outside diameter, in
ART. 1.] DESCRIPTIONS, A^D METHODS OF DRIVING. 219
•sections 12 to 20 feet long ; the disks were 2 feet in diameter and
9 inches thick., and were fastened to the shaft by set-screws. Many
of the piles were 57 feet long, of which 17 feet was in the sand.*
328. SAND PILES. Eor an account of the method of using sand
,as piles, see § 288.
329. SHEET PILES. These are flat piles, which, being driven
successively edge to edge, form a vertical or nearly vertical sheet
for the purpose of preventing the materials of a foundation from
spreading, or of guarding them against the undermining action of
water. They may be made either of timber or iron. Ordinarily
.sheet piles are simply thick planks, sharpened and driven edge to
edge. Sometimes they have a tongue on one edge and a correspond-
ing groove on the other, to aid in guiding them into place while
driving. When heavy timbers are employed as sheet piling, wooden
blocks or iron lugs are fastened on the edges to assist in guiding
them into position. Sheet piles should be sharpened wholly, or at
least mainly, from one side, and the long edge placed next to the
pile already driven. This causes them to crowd together and
make comparatively close joints.
When a space is to be inclosed with sheet piling, two rows of
guide piles are first driven at regular intervals of from 6 to 10 feet,
and to opposite sides of these, near the top, are notched or bolted a
pair of parallel string-pieces, or ivales, from 5 to 10 inches square,
so fastened to the guide piles as to leave a space between the wales
equal to the thickness of the sheet piles. If the sheeting is to stand
more than 8 or 10 feet above the ground, a second pair of wales is
required near the level of the ground. The sheet piles are driven
(§§ 334-45) between the wales, working from both ends towards
the middle of the space between a pair of guide piles, so that the
last or central pile acts as a wedge to tighten the whole.
330. WOODEN BEARING PILES. Spruce and hemlock answer
very well, in soft or medium soils, for foundation piles or for piles
always under water ; the hard pines, elm, and beech, for firmer
soils ; and the hard oaks, for still more compact soils. Where the
pile is alternately wet and dry, white or post oak and yellow or
southern pine are generally used.
* For a detailed and illustrated description of this work, see an article by Charles
Macdonald, C.E., in Trans. Am. Soc. of C. E., Vol. VIII. pp. 227-37.
220 PILE FOUNDATIONS. [CHAP. XI
Piles should never be less than 8 inches in diameter at the small
end and never more, than IS inches at the large end. Specifications-
usually require that these dimensions shall not be less than 10 nor
more than 14 inches respectively. Piles should be straight-grained,
should be trimmed close,, and should have the bark removed.
331. Specifications for Piles. The ordinary specifications are
about as follows :*
Piles, whether used in foundations, trestle-work, or pile bridges, shall be
of good quality, sound, white oak'or such other timber as the engineer may
direct, not less than ten inches (10") in diameter at the smaller end and
14 inches (14") at the larger, and of such lengths as the engineer may require.
They must be straight-grained, must be trimmed close, and must have all the
bark taken off before being driven. They must be cut off square at the butt,
and be properly sharpened. If required by the engineer, the point shall be
shod with iron shoes [see § 332], and the head hooped with iron bands of ap-
proved size and form [see § 332], which will be paid for by the pound.
332. Pile Caps and Shoes. To prevent bruising and splitting
in driving,, 2 or 3 inches of the head is usually chamfered off. As
an additional means of preventing splitting, the head is often
hooped with a strong iron band, 2 to 3 inches wide and -J to 1 inch
thick. The expense of removing these bands and of replacing the
broken ones, and the consequent delays, led to the introduction,
recently, of a cap for the protection of the head of the pile. The
cap consists of a cast-iron block with a tapered recess above and
below, the chamfered head of the pile fitting into the lower recess
and a cushion piece of hard wood, upon which the hammer falls,
fitting into the upper one. The cap preserves the head of the pile,
adds to the effectiveness of the blows (§ 361), and keeps the pile head
in place to receive the blows of the hammer.
A further advantage of the pile cap is that it saves piles. In
hard driving, without the cap the head is crushed or broomed to-
such an extent that the pile is adzed or sawed off several times
before it is completely driven, and often after it is driven a portion
of the head must be sawed off to secure sound wood upon which to-
rest the grillage or platform (§ 380). In ordering piles for any
special work where the driving is hard, allowance must be made for
this loss.
Piles are generally sharpened before being driven, and some-
* See also " Piling" in the general specifications for railway masonry, as given in
Appendix I.
ART. l.| OK-srinPTlOXS, AND METHODS OF, DRIVING.
r, particularly in stony ground, the point is protected by an
iron shoe. The shoo may be only two V-shaped loops of bar iron
plueed over (ho point, in planes at right angles to each other, and
spiked to (he piles ; or it may ho a wrongl.it or cast iron socket, of
which thetv arc a number of forms on the market.
333. Splicing Piles. It frequently happens, in driving piles in
s\vampyvphici's, for false-works, etc., that a single pile is not long
enough, in which cast* two aw splieed together. A common method
of doing this is as follows:* after the first pile is driven its head is
cut oil Mpiare, a hole :>< indies in diameter and 12 inches deep is
bored in its head, and an oak treenail, or dowel-pin, 23 inches
long, is driven into the hole; another pile, similarly squared and
bored, is placed upon the lower pile, and the driving continued.
Spliced in this way the pile is deficient in lateral stiffness, and the
tipper section is liahle to houneo off while driving. It is better to
reinforce the .splice hy Hutting the sides of the piles and nailing on,
with say S-inch spikes, four or more pieces £ or I.J inches thick, 4 or
ft incites wide, and 4 to (i feet long. In the erection of the bridge
over the Hudson at Poughkeepsie, N. Y., two piles were thus
spliced together to form a single one UK) feet long.
Piles may he made of uny required length or cross-section by
bolting and fishing together, sidewiso and lengthwise, a number of
Hqunred timbers. Such piles are frequently used as guide piles in
making pneumatic, caissons (§ 43(>). Hollow-built piles, 40 inches
hi diameter and SO feet long, were used for this purpose in con-
Ktruef ing the St. Louis Bridge ($ 457). They were sunk by pump-
nig the wind and water from the inside of them witli a sand pump
44H).
334, PXLE-DKXVXNG MACHINES. Pile-driving machines may be
duxnifii'il neeording to the eharaetcr of the driving power, which
nwy he (1) a fulling weight, (3) the force of an explosive, or (3) the
t*ro*iv<' itetion <»f a jcvt of watcu*. Piles are sometimes set in holes
bored with u wt»ll-angt^r, and the, earth rammed around them. This
in cptite eommon in Iho ecHintrue-tion of small highway bridges in
the pruirie SlaU'H, a 10- or a 12-ine.h auger being1 generally used.
The' various pih^-driving nmehineH will now be briefly described and
<'oin pared.
* Sro ** Tiling" in tho Gcucrul apeciUcatious for Kailroad Masonry, as given in
Ai»|«mdix L
(
222 PILE FOUNDATIONS. [CHAP. XI.
335. Drop-hammer Pile-driver. The usual method of driving
piles is by a succession of blows given with a heavy block of wood
or iron — called a ram,, monkey, or hammer — which is carried by a
rope or chain passing over a pulley fixed at the top of an upright
frame, and allowed to fall freely on the head of the pile. The
machine for doing this is called a drop-hammer pile-driver, or a
monkey pile-driver — usually the former. The machine is generally
placed upon a car or scow.
The frame consists of two uprights, called leaders, from 10 to 60
feet long, placed about 2 feet apart, which guide the falling weight
in its descent. The leaders are either wooden beams or iron chan-
nel-beams, usually the former. The hammer is generally a mass of
iron weighing from 500 fco 4,000 pounds (usually about 2,000) with
grooves in its sides to fit the guides and a staple in the top by which
it is raised. The rope employed in raising the hammer is usually
wound up by a steam-engine placed on the end of the scow or car,
opposite the leaders.
A car pile-driver is made especially for railroad work, the
leaders resting upon an auxiliary frame, by which piles may be
driven 14 to 16 feet in advance of the end of the track ; and the
frame is pivoted so that piles may be driven on either side of the
track. This method of pivoting the frame carrying the leaders is
also sometimes applied to a machine used in driving piles for foun-
dations.
Li railroad construction, it is not possible to use the pile-driving
car with its steam-engine in advance of the track ; hence, in this
kind of work, the leaders are often set on blocking and the ham-
mer is raised by Horses hitched directly to the end of the rope.
Portable engines also are sometimes used for this purpose. Occa-
sionally the weigl.it is raised by men with a windlass, or by pulling
diraitly on the rope.
A machine used for driving sheet piles differs from that de-
scribed above in one particular, viz. : it has but one leader, in. front
of which the hammer moves up and down. With this construction,
the machine can be brought close up to the wall of a coffer-dam
(§ 317 and § 390), and the pile already driven does not interfere
with the driving of the next one.
336. There are two methods of detaching the weight, i. e., of
letting the hammer fall: (1) by a nipper, and (2) by a friction-clutch.
ART, 1.] DESCRIPTIONS, AND METHODS OF DRIVING. 223
1. The nipper consists of a block which slides freely between
the leaders and which carries a pair of hooks, or tongs, projecting
from its lower side. The tongs are so arranged that when lowered
on to the top of the hammer they automatically catch in the staple
in the top of the hammer, and hold it while it is being lifted, until
they are disengaged by the upper ends of the arms striking a pair of
inclined surfaces in another block, the trip, which may be placed
between the leaders at any elevation, according to the height of fall
desired.
With this form of machine, the method of operation is as fol-
lows : The pile being in place, with the hammer resting on the head
of it and the tongs being hooked into the staple in the top of the
hammer, the rope is wound up until the upper ends of the tongs
strike the trip, which disengages the tongs and lets the hammer
fall. As the hoisting rope is unwound the nipper block follows the
hammer, and, on reaching it, the tongs automatically catch in the
staple, and the preceding operations may be repeated. This method
is objectionable owing to the length of time required (a) for the
nipper to descend after the hammer has been dropped, and (b) to
move the trip when the height of fall is changed. Some manufac-
turers of pile-driving machinery remove the last objection by making
an adjustable trip which is raised and lowered by a light line pass-
ing over the top of the leaders. This is a valuable improvement.
When the rope is wound up by steam, the maximum speed is
from 6 to 14 blows per minute, depending upon the distance the
hammer falls. The speed can not be increased by the skill of the
operator, although it could be by making the nipper block heavier.
2. The method by using & friction-clutch, or friction-drum, as it
is often called, consists in attaching the rope permanently to the
staple iu the top of the hammer, and dropping the hammer by set-
ting free the winding drum by the use of a friction-clutch. The
advantages of this method are (a) that the hammer can be dropped
from a'ny height, thus securing a light or heavy blow at pleasure;
and (&) that no time is lost in waiting for the nipper to descend and
in adjusting the trip.
When the rope is wound up by steam, the speed is from 20 to
30 blows per minute, but is largely dependent upon the skill of the
man who controls the friction-clutch. The hammer is caught on
the rebound, is elevated with the speed of ti falling body, and hence
224
PILE FOUNDATIONS.
[CHAP. xi.
the absolute maximum speed is attained. The rope, by which the
hammer is elevated, retards the falling weight ; and hence, for an
equal effect, this form requires a heavier hammer than when the
nipper is used. Although the friction-drum pile-driver is much
more efficient, it is not as generally used as the nipper driver. The
former is a little more expensive in first cost.
337. Steam-hammer Pile-driver. As regards frequency of use,
the next machine is probably the steam-hammer pile-driver, invented
by Nasmytli* in 1839. It consists essentially of a steam cylinder
(stroke about 3 feet), the piston-rod of which carries a weight of
about 3,500 pounds. The steam-cylinder is fastened to and between
the tops of two I-beams about 8 to 10 feet
long, the beams being united at the bottom by
a piece of iron in the shape of a frustum of a
cone, which has a hole through it. The under
side of this connecting piece is cut out so as to
fit the top of the pile. The striking weight, which
works up and down between the two I-beams
as guides, has a cylindrical projection on the
bottom which passes through the hole in the
piece connecting the feet of the guides and
strikes the pile. The steam to operate the ham-
v mer is conveyed from the boiler through a flex-
ible tube. Fig. 5G shows the striking weight of
the latest form of steam-hammer. It differs
from that described above in having four rods
for guides, instead of the two I-beams.
The whole mechanism can be raised and
lowered by a rope passing over a pulley in the
top of the leaders. After a pile has been placed
in position for driving, the machine is lowered
upon the top of it and entirely let go, the pile
being its only support. When steam is admitted
below the piston, it rises, carrying the striking
weight with it, until it strikes a trip, which
FIG. 56. cufcs off the steam, and the hammer falls by its
own weight. At the end of the down stroke the valves are again
* It is ordinarily called Nasmyth's hammer, but Bourdon should at least share
the credit (sec I&igineeriny J\7mv, vol. xiii. pp. 59, 00).
ART, 1.] DESCRIPTION'S, AND METHODS OF DRIVING. 225
Automatically reversed, and the stroke repeated. By altering the
.adjustment of this trip-piece,, the length of stroke (and thus the
force of the blows) can be increased or diminished. The admission
.and escape of steam to and from the cylinder can also be controlled
directly by the attendant, and the number of blows per minute
is increased or diminished by regulating the supply of steam. The
machine can give GO to SO blows per minute.
338. Drop-hammer vs. Steam-hammer. The drop-hammer is
•capable of driving the pile against the greater resistance. The
maximum fall of the drop-hammer is 40 or 50 feet, while that of
the steam-hammer is about 3 feet. The drop-hammer ordinarily
weighs about 1 ton, while the striking weight of the steam-hammer
usually weighs about H- tons. The energy of the maximum blow
•of the drop-hammer is 45 foot-tons (= 45 ft. X 1 ton), and the
•energy of the maximum blow of the steam-hammer is 4.5 foot-tons
(= 3 ft. X K- tons). The energy of the maximum blow of the
drop-hammer is, therefore, about 10 times that of the steam-
hammer.
However, the effectiveness of a blow does not depend alone upon
its energy. A considerable part of the energy is invariably lost by
the compression of the materials of the striking surfaces,, and the
greater the velocity the greater this loss. An extreme illustration
of this would be trying to drive piles by shooting rifle-bullets at
them. A 1-ton hammor falling 45 ft. has 10 times the energy of a
U-ton hammer falling 3 ft, but in striking, a far larger part of the
former than of the latter is lost by the compression of the pile head.
In constructing the foundation of the Brooklyn dry dock, it was
practically demonstrated that "there was little, if any, gain in
having the fall more than 45 fecit." The loss due to the compres-
sion depends upon the material of the pile, and whether the head of
it is bruised or not. The drop-hammer, using the pile-cap and the
friction-drum, can drive a pile against a considerably harder resist-
ance than the steam-hammer.
It is frequently claimed that the steam-hammer can drive a pile
against a greater resistance than the drop-hammer. As compared
with the old stylo drop-hammer, /'. e., without the friction-drum
and the pile-cap, this is probably true. The striking of the weight
upon the head of the pile splits and brooms it very much, which
materially diminishes the effectiveness of the blow. In hard driving
226 PILE FOUNDATIONS. [CHAP.
with the drop-hammer, without the pile-cap, the heads of the piles,
even when hooped, will crush, bulge out, and frequently split for
many feet below the hoop. For this reason, it is sometimes speci-
fied that piles shall not be driven with a drop-hammer.
The rapidity of the blows is an important item as affecting the
efficiency of a pile-driver. If the blows are delivered rapidly,
the soil does not have sufficient time to recompact itself about
the pile. With the steam-driver the blows are delivered in such
quick succession that it is probable that a second blow is de-
livered before the pile has recovered from the distortion produced
by the first, which materially increases the effectiveness of the
second blow. In this respect the steam-hammer is superior to the
drop-hammer, and the friction-clutch driver is superior to the
nipper driver.
In soft soils, the steam-hammer drives piles faster than either
form of the drop-hammer, since after being placed in position on
the head of the pile it pounds away without the loss of any time.
339. In a rough way the first cost of the two drivers — exclusive
of scow or car, hoisting engine, and boiler, which arc the same in
each — is about $80 for the drop-hammer driver, and about $800 for
the steam-driver. Of course these prices will vary greatly. The per
cent, for wear and tear is greater for the drop-hainmor than for the
steam-hammer. For work at a distance from a machine-shop the-
steam-driver is more liable to cause delays, owing to breakage of
some part which can not be readily repaired.
340. Gunpowder Pile-driver. This machine was invented by
Shaw, of Philadelphia, in 1870. The expansive force of gunpowder
is utilized both in driving the pile and in raising the rani. The
essential parts of the machine are the ram and ynn. Tho former
consists of a mass of iron weighing generally about 1,500 pounds,
which terminates below in a sort of piston ; this piston libs tightly
into a chamber in another mass of iron, the gun. The rain travels
between vertical guides much as in the other machines ; and the
gun and rarn are hoisted as is the steam-hammer. The ram having
been raised to the top of the guides, and tlwxgun placed upon the
top of the pile, a cartridge of from 1 to 3 ounces of gunpowder
is placed in the cylinder, or gun, and the ram is allowed to descend.
The piston enters the cylinder, compresses the air, and generator
heat enough to ignite the cartridge, when the expansive force of
ART. 1.] DESCRIPTIONS, AND METHODS OF DRIVING. 227
the powder forces the pile down and the ram up. A cartridge is,
thrown into the gun each time as the ram ascends. The rapidity
of the blows is limited by the skill of the operator and by the heat-
ing of the gun. Thirty to forty blows, of from 5 to 10 feet each,
can be made per minute.
341. The only advantage of this machine is that the hammer
does not come in contact with the head of the pile, and hence does
not injure it. The disadvantages are (1) that it is of no assistance
in handling the pile ; ("2) that it is not economical ; (3) that the
gases soon destroy the gun ; (4) that a leakage of gas occurs as the
gun gets hot, which renders it less efficient as the rapidity of firing
is increased ; and (5) that the gun gets so hot as to explode the
cartridge before the descent of the ram, which,, of course, is an
entire loss of the explosive. Its first cost is great. It is not now
used.
342. Driving Piles with Dynamite. It has been proposed to
drive piles by exploding dynamite placed directly upon the top of
the pile. It is not known that this method has been used except
in a few instances. It would be a slow method, but might prove
valuable where only a few piles were to be driven by saving the
transportation of a machine ; or it might be employed in locations
where a machine could not be operated. The higher grades of
dynamite are most suitable for this purpose.*
343. Driving Piles with. Water Jet. Although the water jet
is not strictly a pile-driving machine, the method of sinking piles
by its use deserves careful attention, because it is often the cheapest
and sometimes the only means by which piles can be sunk in mud,
silt, or sand.
The method is very simple. A jet of water is forced into the
soil just below the point of the pile, thus loosening the soil and
allowing the pile to sink, either by its own weight or with very light
blows. The water may be conveyed to the point of the pile through
a flexible hose held in place by staples driven into the pile ; and
after the pile is sunk, the hose may be withdrawn for use again.
An iron pipe may be substituted for the hose. It seems to make
very little difference, either in the rapidity of the sinking or in the
accuracy with which the pile preserves its position, whether the
nozzle is exactly under the middle of the pile or not.
* For a brief description of explosives, see pp. 119-24.
228 PILE FOUNDATIONS. [CHAP. XI.
The water jet seems to have been first used in engineering in
1852, at the suggestion of General Geo. B. McClellan. It has been
extensively employed on the sandy shores of the Gulf and South
Atlantic States, where the compactness of the sand makes it diffi-
cult to obtain suitable foundations for light-houses, wharves, etc.
Another reason for its use in that section is, that the palmetto piles
— the only ones that will resist the ravages of the teredo — are too
soft to withstand the blows of the drop-hammer pile-driver. By
employing the water jet the necessity for the use of the pile-hammer
is removed, and consequently palmetto piles become available.
The jet has also been employed in a great variety of ways to facili-
tate the passage of common piles, screw and disk piles, cylinders,
caissons, etc., etc., through earthy material,*
344. The efficiency of the jet depends upon the increased fluidity
given to the material into which the piles are sunk, the actual dis-
placement of material being small. Hence the efficiency of the jet is
greatest in clear sand, mud, or soft clay ; in gravel, or in sand con-
taining a large percentage of gravel, or in hard clay, the jet is almost
useless. For these reasons the engine, pump, hose, and nozzle
should be arranged to deliver large quantities of water with a mod-
erate force, rather than smaller quantities with high initial velocity.
In gravel, or in sand containing considerable gravel, some benefit
might result from a velocity sufficient to displace the pebbles and
drive them from the vicinity of the pile ; but it is evident that
any practicable velocity would be powerless in gravel, except for a
very limited depth, or where circumstances favored the prompt
removal of the pebbles.
The error most frequently made in the application of the water
jet is in using pumps with insufficient capacity. Both direct-acting
and centrifugal pumps are frequently employed. The former
affords the greater power ; but the latter has the advantage of a less
first cost, and of not being damaged as greatly by sand in the water
used.
The pumping plant used in sinking the disk-piles for the Coney
Island pier (see § 327), e£ consisted of a Worthington pump with a
12-inch steam cylinder, 8^-inch stroke, and a water cylinder 7£
inches in diameter. The suction hose was 4 inches in diameter,
* See a pamphlet — " The Water Jet as au Aid to Engineering Construction" —
published (1881) by the Engineer Department of the U. S. Army.
ART. 1.] DESCRIPTIONS, AND METHODS OF DRIVING. 229
and the discharge hose, which was of four-ply gum., was 3 inches.
The boiler was upright, 42 inches in diameter, 8 feet high, and
contained 62 tubes 2 inches in diameter. An abundance of steam
was supplied by the boiler, after the exhaust had been turned into
the smoke-stack and soft coal used as fuel. An average of about
160 pounds of coal was consumed in sinking each pile. With the
power above described, it was found that piles could be driven in
clear sand at the rate of 3 feet per minute to a depth of 12 feet ;
after which the rate of progress gradually diminished, until at 18
feet a limit was reached beyond which it was not practicable to
go without considerable loss of time. It frequently happened that
the pile would ' bring up ' on some tenacious material which was
assumed to be clay, and through which the water jet, unaided,
could not be made to force a passage. In such cases it was found
that by raising the pile about 6 inches and allowing it to drop sud-
denly, with the jet still in operation, and repeating as rapidly as
possible, the obstruction was filially overcome ; although in some in-
stances live or six hours were consumed in sinking as many feet." *
In the shore-protection work on the Great Lakes, under the
direction of the United States Army engineers, the pumping plant
"consisted of a vertical tubular boiler, with an attached engine
having an 8 X 12-inch cylinder, and giving about 130 revolutions per
minute to a 42-inch driving-wheel. A No. 4 Holly rotary pump,
with 18-inch pulley, was attached by a belt to the driving-wheel of
the engine, giving about 300 revolutions per minute to the pump.
The pump was supplied with a 4-inch suction pipe, and discharged
through a 3-inch hose about 50 feet in length. The hose was pro-
vided with a nozzle 3 feet in length and 2 inches in diameter. The
boiler., engine, pump, and pile-driver were mounted on a platform
12 feet in width and 24 feet in length." f
345. Jet vs. Hammer. It is hardly possible to make a compari-
son between a water-jet and a hammer pile-driver, as the conditions
most favorable for each are directly opposite. For example, sand
yields easily to the jet, but offers great resistance to driving with
the hammer ; on the other hand, in stiff clay the hammer is much
* Chas. McDonald, in Trans. Am. Soc. of C. K, vol. viii. pp. 227-37.
t "The Water- Jet as an Aid to Engineering Construction," p. 11 ;— a pamphlet
published (1881) by the Engineer Department of the U. S. Army.
230 PILE FOUNDATIONS. [CHAP. XI.
more expeditious. For inland work the hammer is better, owing to
the difficulty of obtaining the large quantities of water required for
the jet ; but for river and harbor work the jet is the most advan-
tageous. Under equally favorable conditions there is little or no
difference in cost or speed of the two methods.*
The jet and the hammer are often advantageously used together,
especially in stiff clay. The efficiency of the water-jet can be greatly
increased by bringing the weight of the pontoon upon which the
machinery is placed, to bear upon the pile by means of a block and
tackle.
346. COST or PILES. At Chicago and at points on the Missis-
sippi above St. "Lams, pine pile', cost from 10 to 15 cents per lineal
foot, according to length and location. Soft-wood pilvx, including
rock elm, can be had in almost any locality for 8 to 10 cents per
foot. Oak piles 20 to 30 feet long cost from 10 to 12 cents per
foot ; 30 to 40 feet long, from 12 to 14 cents per foot ; 40 to GO
feet long, from 20 to 30 cents per foot.
347. COST OF PILE DRIVING. There are many items that affect
the cost of work, which can not be included in a brief summary, but
which must not be forgotten in using such data in making estimates.
Below are the details for the several classes of work.
348. Railroad Construction. The following table is a summary
of the cost, to the contractor, of labor in driving piles (exclusive of
hauling) in the construction of the Chicago branch of the Atchison,
Topeka and Santa Fe E. E. The piles were driven, ahead of the
track, with a horse-power drop-hammer weighing 2,200 pounds.
The average deptli driven was 13 feet. The table includes the
cost of driving piles for abutments for Howe truss bridges and
for the false work for the erection of the same. These two items
add considerably to the average cost. The contractor received
the same price for all classes of work. The work was as varied as
such jobs usually are, piles being driven in all kinds of soil. Owing
to the large amount of railroad work in progress in 1887, the cost
of material and labor was about 10 per cent, higher than the aver-
age of the year before and after. Cost of labor on pile-driver : 1
foreman at $4 per day, 6 laborers at $2, 2 teams at $3.50; total cost
of labor = $23 per day.
* Report of Chief of Engineers U. S. A., 1883, pp. 1264-72.
ART. 1.] DESCRIPTIONS,
METHODS OP DRIVING.
231
COST OF PILE DRIVING IN RAILROAD CONSTRUCTION.
Number of piles included in this report 4,409
" " lineal feet included in this report 109,568
Average length of the piles, in feet 24.8
Number of days employed in driving 494
" " lineal feet driven, per day 221.8
Cost of driving, per pile $2.53
" " " " foot 10.4 cents.
349. Eailroad Repairs'. The following are the data of pile
driving for repairs to bridges ou the Indianapolis, Decatur and
Springfield U. R. The work was done from December 21, 1885, to
January 5, 1886. The piles varied from 12 to 32 feet in length,
the average being a little over 21 feet. The average distance driven
was about 10 feet. The hammer weighed 1,650 pounds; the last
fall was 37 foot, and the corresponding penetration did not exceed
2 inches. The hammer was raised by a rope attached to the draw-
bar of a locomotive — comparatively a very expensive way.
TABLE 26.
COST OF PILES FOE BRIDGE REPAIRS.
ITEMS OF EXPENSE.
TOTAL.
PER PILB.
PER FOOT.
Labor :
JSupjtlu
Loading and unloading pikw, 7J^> days
$16.00
153.75
45.90
71.50
23.49
13.29
11.04
$0.08
0.78
0.23
0.37
0.13
0.06
0.05
0.4 cts.
3.7
1.1
1.6
0.5
0.3
0.3
Brid^o LT Jin IT drivintr 1JJ days
En^Uio crew', transportation and driving, 13 days..
Train crew, *' " " " .
s * KntriiK* supplifs
(5 T)il<* ritiirs and J3 plates ..
Tot(tl ('Tt)cn tc for driving
$334.97
$1.70
7. 9 cts.
tl ' '\ lf)v> f(k(*t oak pilfs at 13J^> cts
$565.92
$2.86
18.5 cts.
TOTAL COKT
$900.89
$4.56
21. 4 cts.
On the same road, 9 piles, each 20 feet long, were driven 9 feet,
for Immping-posts, with a 1, 650-pound hammer dropping 17 feet.
Tho hammer was raised with an ordinary crab-winch and single
line, with double crank worked by four men. The cost for labor was
8.3 cents per foot of pile, and the total expense was 21.8 cents per foot.
350. Bridge Construction. The following table gives the cost
of labor in driving the piles for the Northern Pacific E. R. bridge
ovor the lied River, at Grand Forks, Dakota, constructed in 1887.
The soil was sand and clay. The penetration under a 2,250-pound
hammer falling 30 feet was from 2 to 4 inches. The foreman re-
ceived #5 per day, the stationary engineer $3.50, and laborers $2.
232
PILE FOUNDATIONS.
[CHAP, xi.
TABLE 27.
COST OF LABOR IN DRIVING PILES IN BRIDGE CONSTRUCTION.
o
ti
H
§ el
1 §
M
z
KIND OF LABOR.
5 <
«S
£ § a
PH
£
H^
gs
5 "'2
s
g
fl
£'
Q S
fl
£
Preparation, and. repair of plant
$68 95
$63 (55
$53 50
$37 00
$61 60
432 70
252 92
430 50
215 45
565 80
Sawing and straightening . .
78 75
47 50
179 80*
131 90t"
Total cost . '
$580 40
$316 57
$531 50
$750 30
Number of piles in the structure
224
102
104
121
167
Total number of feet remaining in the structure. .
7,238
3,710
7,023
4,639
7,316
Average length of piles " " " "
32.3
38.2
38.4
43.8
Average length of piles cut off
1 1
4 i
6 6
3 7
Cost per foot of pile remaining in the structure . . .
8.0 cts.
8. 5 cts.
7.6 cts.
9. 3 cts.
10.4 cts.
Average cost for driving, per foot remaining in the structure = 8.8 cents.
* Sawed off under 8 feet of water.
t Including $70.25 for excavating and bailing in order to get at the sawing.
351. Foundation Piles. The contract price for the foundation
piles — white oak — for the railroad bridge over the Missouri River, at
Sibley, Mo., was 22 cents per foot for the piles and 28 cents per foot
for driving and sawing off below water. They were 50 feet longr
and were driven in sand and gravel, in a coffer-dam 16 feet deep,
by a drop-hammer weighing 3,203 pounds, falling 36 feet. The ham-
mer was raised by steam power.
352. In the construction of a railroad in southern Wisconsin
during 1885-87, the contract price — the lowest competitive bid — for
the piles, in place, under the piers of several large bridges averaged
as in the following table. The piles were driven in a strong current
and sawed off under water, hence the comparatively great expense.
TABLE 28.
CONTRACT PRICE OF FOUNDATION PILES.
CONTRACT PRICE PER LINEAL FOOT.
For Part remaining in
Structure.
For Pile Pleads SawacI
off.
Rock Elm
Ordinary
40 cents
15 cents
Pine
"
40 "
20 "
Oak
**
48 "
25 "
Oak
Hard
50 "
30 "
AET. 2.] BEARING POWER OF PILES. 233
353. In 1887 tlie contract price for piles in the foundations of
bridge piers in the river at Chicago was 35 cents per foot of pile
left in the foundation. This price> covered cost of timber (10 to 15
cents) , driving, and cutting off 12 to 14 feet below the surface of
the water, — about 17 feet being left in the foundation.
The cost of driving and salving off may be estimated about
as follows : (17 + 13) feet of pile at 13 cents per foot = $3.90 ; 17
feet of pile, left in the structure, at 35 cents per foot = $5. 95.
$5.95 — $3.90 = $2.05 = the cost per pile of driving and sawing off,,
which is equivalent to nearly 7 cents per foot of total length of pile.
In this case the waste or loss in the pile heads cut off adds consider-
ably to the cost of the piles remaining in the structure. In mak-
ing estimates this allowance should never be overlooked.
354. Harbor and River Work. In the shore-protection work at
Chicago, done in 1882 by the Illinois Central II. E., a crew of 9
men, at a daily expense, for labor, of $17.25, averaged 65 piles per 10
hours in water 7 feet deep, the piles being 24 feet long and being
driven 14 feet into the sand. The cost for labor of handling, sharp-
ening, and driving, was a little over 26 cents per pile, or 1.9 cents
per foot of distance driven, or 1.1 cents per foot of pile.* Both
steam-hummers and water-jets were used, but not together. Notice
that this is very cheap, owing (1) to the use of the jet, (2) to little
loss of time in moving the driver and getting the pile exactly in the
predetermined place, (3) to the piles not being sawed off, and (4)
to the skill gained by the workmen in a long job.
On the Mississippi Kiver, under the direction of the II. S.
Army engineers, the cost in 1882 for labor for handling, sharpen-
ing, and driving, was $3.11 per pile, or 20 cents per foot driven.
The piles were 35 feet long, the depth of water 15.5 feet, and the
depth driven 13.6 feet. The water-jet and drop-hammer were used
together. The large cost was due, in part at least, to the current,
which was from 3 to 6 miles per hour.f
ART. 2. BEARING POWER OP PILES.
355. Two cases must be distinguished .; that of columnar piles or
those whose lower end rests upon a hard stratum, and that of ordi-
nary bearing piles or those whose supporting power is due to the
* Report of the Chief of Engineers, U. S. A., for 1883, ppA266~70.
t Ibid., p. 1260.
234 PILE FOUNDATIONS. [CHAP. XI.
friction of the earth on the sides of the pile. In the first case, the
bearing power is limited by the strength of the pile considered as a
column ; and, since the earth prevents lateral deflection, at least to
a considerable degree, the strength of such a pile will approximate
closely to the crushing strength of the material. This class of piles
needs no further consideration here.
356. METHODS OF DETERMINING SUPPORTING POWER. There
are two general methods of determining the supporting power of
ordinary bearing piles: first, by considering the relation between the
supporting power and the length and size of the pile, the weight of
the hammer, height of fall, and the distance the pile was moved by
the last blow ; or, second, by applying a load or direct pressure to
each of a number of piles, observing the amount each will support,
and expressing the result in terms of the depth driven, size of pile,
and kind of soil. The first method is applicable only to piles driven
by the impact of a hammer ; the second is applicable to any pile,
no matter how driven.
1. If the relation between the supporting power and the length
and size of pile, the weight of the hammer, the height of fall,
and the distance the pile was moved by the last blow can be stated
in a formula, the supporting power of a pile can be found by insert-
ing these quantities in the formula and solving it. The relation
between these quantities must be determined from a consideration
of the theoretical conditions involved, and hence such a formula is
a rational formula.
2. By applying the second method to piles under all the con-
ditions likely to occur in practice, and noting the load supported,
the kind of soil, amount of surface of pile in contact with the soil,
etc., etc., data could be collected by which to determine the sup-
porting power of any pile. A formula expressing the supporting
power in terms of these quantities is an empirical formula-.
t357. RATIONAL FORMULAS. The deduction of a rational for-
mula for the supporting power of a pile is not, strictly, an appro-
priate subject for mathematical investigation, as the conditions can
not be expressed with mathematical precision. However, as there
is already a great diversity of formulas in common use, which give
widely divergent results, a careful investigation of the subject is
necessary. *
The present practice in determining the bearing power of piles is
JLRT. 2.] BEARING POWER OF PILES. 23i
neither scientific nor creditable. Many engineers, instead of in
quiring into the relative merits of the different formulas, take a]
average of all the formulas they can find, and feel that they have
result based on the combined wisdom of the profession. This prac
tice is exactly like that of the ship's surgeon who poured all hi
medicines into a black jug, and whenever a sailor was ailing gav
him a spoonful of the mixture. Other engineers, knowing the grea
diversity and general unreliability of the formulas, reject ther
all and trust to their own experience and judgment. The seli
reliant engineer usually chooses the latter course, while the timi<
one trusts to the former.
To correctly discriminate between the several formulas, it i
necessary to have a clear understanding of all the conditions in
volved. The object of the following discussion is to discover tli
general principles which govern the problem.
353. When the ram strikes the head of the pile, the first effec
is to compress both the head of the pile and the rain. • The mor
the ram and pile are compressed the greater the force required, nut:
finally the force of compression is sufficient to drive the pile throng'
the soil. The amount of the pressure on the head of the pile whe:
it begins to move, is what we wish to determine.
To produce a formula for tlxe pressure exerted upon the pile b
the impact of a descending weight, let
W = the weight of the ram, in tons ;
w = "' " " pile "
S = the section of the ram, in sq. ft.;
.9= " " " pile " "
L = the length of the ram, in feet ;
1= " " " pile "
E = the co-efficient of elasticity of the ram, in tons per sq. ft. ;
h = the height of fall, in feet ;
d = the penetration of the pile, i. e.} the distance the pile :
moved by the last blow, in feet. The distance d is tli
amount the pile as a whole moves, and not the amour
the top of the head moves. This can be found acci
rately enough by measuring the movement of a poim
say, 2 or 3 feet below the head.
P = the pressure, in tons, which will just move the pile the vei
236 , PILE FOUNDATIONS. [CHAP. XI-
small distance d, — that is to say, the pressure produced
by the last blow; or, briefly, P may be called the sup-
porting power.
Then Wh is the accumulated energy of the ram at the instant it
strikes the head of the pile. This energy is spent (1) in compress-
ing the ram, (2) in compressing the head of the pile, (3) in moving
the pile as a whole against the resistance of the soil, (4) in overcom-
ing the inertia of the pile, (5) in overcoming the inertia of the soil
at the lower end of the pile, and (6) by the friction of the ram
against guides and air. These will be considered in order.
1. The energy consumed in compressing the hammer is repre-
sented by the product of the mean pressure and the compression, or
shortening, of the ram. The pressure at any point in a striking
weight varies as the amount of material above that point ; that is to
say, the pressure at any point of the hammer varies inversely as its-
distance from the lower surface. The pressure at the lower surface-
is Py and that at the upper one is zero ; hence the mean pressure
is -J- P. From the principles of the resistance of materials, the com-
pression, or the shortening, is ~™ , in which p is the uniform pres-
sure. Prom the above, p = £ P. Consequently the shortening is-
IPJ,
2SE'
If the fibers of the face of the ram are not seriously crushed, the-
mean pressure will be one half of the maximum pressure due to im-
pact ; or the mean pressure during the time the ram and pile are
1 P1 L
being compressed is -J-P. Then the energy consumed is--^^.
The yielding of the material of the ram is probably small, and might
be omitted, but as it adds no complication, as will presently appear,
it is included.
2. The mean pressure on the head of the pile is £ P, as above*
For simplicity assume that the pile is of uniform section through-
out. To determine the shortening, notice that for the part of the
pile above the ground the maximum pressure is uniform through-
out, but that for the part under the surface the maximum pressure
varies as some function of the length. If the soil were homogeneous,
the pressure would vary about as the length in the ground ; and
AKT. 2.] BEAKOTG POWEB OF PILES. 237
I PI
hence the shortening would be - — . But, remembering that the
hi O 6
resistance is generally greater at the lower end than at the upper,
and that any swaying or vibration of the upper end will still further
diminish the resistance near the top, it is probable that the mean
pressure is below the center. It will here be assumed that the mean
pressure on the fibers of the pile is two thirds of that on the head, '
2 P I
which is equivalent to assuming that the shortening is -, when
t> SB
the pile is wholly immersed. If only a part of the pile is in contact
PV 2 P I Pi 2 \
with the soil, the shortening will be 1- ™ — *• = — ( V -j — M
& se 3 se se\ ~ 3 V
in which V is the exposed portion and ^ the part immersed. For
.simplicity in the following discussion the shortening of the pile
2 P I
will be taken at ~ — . If a formula is desired for the case when
3 se
the top projects above the ground, it will only be necessary to sub-
stitute (f Z' -f- ?J for I in equations (1) and (2) below.
1 P~l
Then the energy lost in the compression of the pile is -- — .
0 S G
3. The energy represented by the penetration of the pile is P d.
4. In the early stage of the contact between the ram and the
pile, part of the energy of the ram is being used up in overcoming the
inertia of the pile ; but in the last stage of the compression, this
•energy is given out by the stoppage of the pile. At most, the effect
of the inertia of the pile is small ; and hence it will be neglected.
5. The energy lost in overcoming the inertia of the soil at the
lower end of the pile will vary with the stiffness of the soil and with
the velocity of penetration. It is impossible to determine the amount
of this resistance, and hence it can not be included in a formula.
Omitting this element causes the formula to give too great a support-
ing power. The error involved can not be very great, and is to be
•covered by the factor of safety adopted.
6. The friction of the ram against the guides and against the air
diminishes the effect of the blow, but the amount of this can not be
computed. Omitting this element will cause the formula for the
supporting power to give too great a result. The friction against
the air increases very rapidly with the height of fall, and hence the
238 PILE FOUNDATION'S. [CHAP. XI..
smaller the fall the more nearly will the formula give the true sup-
porting power.
359. Equating the energy of the falling weight with that con-
sumed in compressing the pile and ram, and in the penetration of
the pile, as discussed in paragraphs 1, 2, and 3 above, we have
4
Solving equation (1) gives
p=y wh
3 L * e + 4 I ti E ' (S Lse + 41 8 E)*
6 tf S E s e
3 /, s e + 4 Z # J2' ' v '
An examination of equation (2) shows that the pressure upon the
pile varies with the height of fall, the weight, section, length, and
co-efficient of elasticity of both ram and pile, and with the penetra-
tion. It is easy to see that the weight of the ram and the height
of the fall should be included. The penetration is the only element
which varies with the nature of the soil, and so of course it also
should be included. It is not so easy to see that the length, section,
and co-efficient of elasticity of the material of the pile and ram
should be included. If any one will try to drive a large nail into
hard wood with a piece of leather or rubber intervening between
the hammer and the head of the nail, he will be impressed with the
fact that the yielding of the leather or rubber appreciably diminishes
the effectiveness of the blow. Essentially the same thing occurs in
trying to drive a large nail with a small hammer, except that in this
case it is the yielding of the material of the hammer which dimin-
ishes the effect of the blow. In driving piles, the materials of the
pile and ram act as the rubber in the first illustration; and, reason-
ing by analogy, those elements which determine the yielding of the
materials of the pile and ram should be included in the formula.
Obviously, then, the pressure due to impact will be greater the
harder the material of the pile. Notice also that if the head of the
pile is bruised, or "broomed," the yielding will be increased; and,
consequently, the pressure due to the blow will be decreased.
AET. 2.] BEAKDSTG POWEE OF PILES. 23 9
360. The Author's Formula for Practice. To simplify equation
(2), put
6 S E s e
3 L'se + TT8l<!~~'
and then equation (2) becomes
P = V*q Wb + f(F-qd ..... (3)
Equation (3) can be simplified still further by computing q for
the conditions as they ordinarily occur in practice- Of course, in
this case it will only be possible to assume some average value for
the various quantities. Assume the section of the pile to be 0.8 sq.
ft.; the section of the ram, 2 sq. ft.; the length of the ram, 2.5 ft.;
the length of the pile,* 25 ft. ; the co-efficient of elasticity of the
ram, 1,080,000 tons per sq. ft.; and the co-efficient of elasticity of
the pile, 108,000 tons per sq. ft. (an average value for oak, elm,
pine, etc., but not for palmetto and other soft woods). Computing
the corresponding value of g, we find it to be 5,160; but to secure
round numbers,, we may take it at 5,000, which also gives a little
additional security.
Equation (3) then becomes
P = 100 ( V W h + (50 ciy - 50 d), . . . (4)
which i.s- the form to be used in practice.
Equation (4) is approximate because of the assumptions made in
deducing equation (1), and also because of the average value taken
for q\ but probably the error occasioned by these approximations is
not material.
361. Notice that, since the co-efficient of elasticity of sound
material was used in deducing the value of q, equation (4) is to be
applied only on condition that the last blow is struck upon sound
wood; and therefore the head of the test pile should be sawed off so
as to present a solid surface for the last, or test, blow of the hammer.
(Tkis limitation is exceedingly important.) Since the penetration
per blow can be obtained more accurately by taking the mean dis-
tance for two or three blows than by measuring the distance for a
single one, it is permissible to take the mean penetration of two or
* The quantity to be used here is the length out of the ground plus about two
thirds of the part in the ground (see paragraph 2 of § 353).
240
PILE FOUNDATIONS.
[CHAP. xi.
three blows; but their number and force should be such as not to
crush the head of the pile.
In this connection the following table, given by Don. J. Whitte-
more, in the Transactions of the American Society of Civil Engi-
neers, vol. xii. p. 442,, to show the gain in efficiency of the driving
power by cutting off the bruised or broomed head of the pile, is very
instructive. The pile was of green Norway pine; the ram was of
the Nasmyth type, and weighed 2,800 pounds.
TABLE SHOWING THE GAIN IN EFFICIENCY OF THE DRIVING POWER BY
CUTTING OFF THE BROOMED HEAD OF THE PILE.
3d ft. of penetration required 5 blows.
4th " « " 15
5th " " " 20
6th " " " 29
7th " " " 35
8th " " " 46
9th " " 61
10th. " " " 73
llth " " " 109
12th " t( tf 153
13th " <( " 257
14th " " " 684
Head of the pile adzed oft'.
15th ft. of penetration required 275
16th " " " 572
17th " " " 832
18th " " " 825
Head of the pile adzed off.
19th ft. of penetration required 213
20th " " " 275
21st " " " 371
22d " " " . 378
Total number of blows, 5,228
Notice that the average penetration per blow was 2 J times greater
during the 15th foot than during the 14th; and nearly 4 times
greater in the 19th than in the 18th. It does not seem unreason-
able to believe that the first blows after adzing the head off were
correspondingly more effective than the later ones; consequently,
it is probable that the first blows for the 15th foot of penetration
were more than 5 times as efficient as the last ones for the 14th foot,
and also that the first blows for the 19th foot were 8 or 10 times
more efficient than the last ones for the 18th foot. Notice also that
since the head was only "adzed off/' it is highly probable that the
.spongy wood was not entirely removed.
ABT. 2.] BEARING POWER OF PILES. 241
If the penetration for the last blow 'before the head was adzed off
were used in the formula, the apparent supporting power would be
very much greater than if the penetration for the first blow after
adzing off is employed. This shows how unscientific it is to pre-
scribe a limit for the penetration without specifying the accompany-
ing condition of the head of the pile,, as is ordinarily done.
362. Weisbach's Formula. Equation (2), page 238, is essentially
•equivalent to Weisbach's formula for the supporting power of a pile.
Weisbacli assumes that the pressure is uniform throughout, and
obtains the formula*
, . , rr 8 E . T_ s e
m which // = — j~ , and H^ = -y.
Ju (f
363. Bankine's Formula. Equation (2), page 238, is also essen-
tially equivalent to Eankine's formula ; and differs from it, only
because he assumes the pressure to vary directly as the length of
the pile, and neglects the compression of the ram. Eankine's
formula is f
_
,/TWZse 4J*V Zdse
-v -i- ,
Equation (2) differs from Weisbach's and Eankine's on the safe
side.
364. EMPIRICAL FOBMITLAS. General Principles. (1) An empiri-
cal formula should be of correct form; (2) the constants in it should
be correctly deduced ; and (3) the limits within which it is applica-
ble should be stated.
For example, suppose that it were desired to determine the
•equation of the straight line A B, Fig. 57.
Since the given line is straight, we will as-
sume that the empirical formula is of the
form y = m x. We might find m by measur-
ing the ordinates 1, 2, 3, and place m equal
bo their mean. If 1, 2, 3, be the numerical
values of the respective ordinates, the for-
mula becomes y = 2 x, which gives the line
0 0. The mean ordinate to 0 0 is equal to FlG- 57-
the mean ordinate to A B, but the two are not by any means the
* Mechanics of Engineering, 6th ed. (Coxe's Translation), p. 701.
i Civil Engineering, p. 603.
243, PILE FOUNDATIONS. [CHAP. XI,
same line. It is evident that this empirical formula is of the wrong"
form.
For another illustration, assume that some law is correctly repre-
sented by the curve A B, Fig. 58. The form
of the empirical formula may be such as to
give the curve CD. These curves coincide
exactly at two points, and the mean ordinate
to the two is the same. To use a com-
mon expression, we may say that, "on. the
average, the empirical formula agrees exactly
FIG. 58. with the facts ;" but it is, nevertheless, not
even approximately true. The constants were not correctly de-
duced.
Even if of the correct form and correctly deduced, an empirical
formula can be safely applied only within the
limits of those values from which it was deter-
mined. For example, a law may be repre-
sented by the curve A B, Fig. 59. From
observations made in the region C E, the em- FIG. i
pirical formula has been determined, which gives the curve 0 E D7
which between the limits 0 and E is all that can be desired, but
-which is grossly in error between the limits .Z?and D. To use an
empirical formula intelligently, it is absolutely necessary that the
limits within which it is applicable should be known.
Of course, the observations from which the empirical formula
was deduced can not be used to test the correctness of the formula;
such a procedure can check only the mathematical work of deriving
the constants.
Elementary as the preceding principles are, many empirical
formulas are worthless owing to a disregard of these conditions in
deducing them.
365. Comparison of Empirical Formulas. We will now briefly
consider the empirical formulas that are most frequently employed
to determine the supporting power of piles.*
Haswell's formula for the dynamic effect of a falling body is f
P = 4.426 W V, "as deduced from experiments. "
The experiments consisted in letting a weight of a few ounces.
* For explanation of the nomenclature, see p. 235.
t Haswell's Engineers1 and Mechanics' Pocket-Book, p. 419.
AET. 2.] BEARING POWER OP PILES. 243
fall a few inches upon a coiled spring ; and hence the formula is
entirely inapplicable to pile driving.
Beaufoy's formula is P = 0.5003 W F2, ""as determined by
experiment." This formula was deduced under the same conditions
as HaswelFs, and hence is useless for pile driving. The difference
between the formulas is due to the fact that Haswell used only one
weight and one spring, and varied the height of the fall, while Beau-
foy employed one weight and springs of such relative stiffness as
would stop the weight in nearly the same distance for different
heights of fall.* Notice that HaswelPs, and also Beaufoy's formula,
would give the same bearing power for all soils, other things being
the same.
W3 7 i
Ny strom's formula \ is P = 7-777-; ^r-r In a later book,! Nvs-
J J ' (W + w)-d -
trom gives the formula P = -- — — , assuming that "about 25 per
TC Cv
cent, of the energy of the ram is lost by the crushing of the head of
the pile." Both of these formulas are roughly approximate, theo-
retical formulas, although frequently cited as "practical formulas."
TP h
Mason's formula § is P = -. w ' . As in the preceding
^ Yr ~Y~ 10 J (i
cases, this is frequently referred to as a " practical formula ;" but an
examination of the original memoir shows that it is wholly a theo-
retical formula with 'no pretensions of being anything else. It is
also sometimes referred to as having been " tested by a series of
experiments ;" but apparently the only basis for this is that the
piles upon which Fort Montgomery (House's Point, N. Y.) stood
from 1846 to 1850 without any sign of failure, when tested by this
formula, showed a co-efficient of safety of 3TV The evidence is not
conclusive: (1) the factor is large enough to cover a considerable
error in the formula; (2) since the formula assumes that all of the
energy in the descending ram is expended in overcoming the resist-
ance to penetration, the computed bearing power is too small, and
consequently the co-efficient of safety is even greater than as stated;
* Van Nostrand's Engin'g Mag., vol. xvii. p. 325.
t Nystrom's Pocket-Book, p. 158.
J New Mechanics, p. 134.
§ Resistance of Piles, J. L. Mason, p. 8; No. 5 of Papers on Practical Engineering,
published by the Engineering Department of the U. S. Army.
244 PILE FOUNDATIONS. [CHAP. XI.
and (:>) it is probably safe to say that after a pile lias stood a short
time its Louring power is greater than at the moment the driving
ceased, owing to the settlement of the earth about it.
Sander's formula* is Pf = — r-y. in which Pf is the safe bear-
O (I
ing power. This formula was deduced on the assumptions that the
energy of the falling weight was wholly employed in forcing the
pile into the ground., — /. t>., on the assumption that P d == IF//, or
p = ™_^^ — anc] t}ul£ -yie mj>e }oac[ was one eighth of the ultimate
supporting power. It is therefore a roughly approximate, theoreti-
cal formula.
Notice that, since some of the energy is always lost, P d, the
energy represented by tho movement of the pile, must always be
less than \YJi, the energy of the hammer; henco, P is always less
than——; or, in mathematical language, P<~~— . This relation is
very useful for determining the greatest possible value of the sup-
porting power. P will always be considerably less than— y- ; and
a
this difference is greater the lighter the weight, the greater the
fall, the softer the material of the pile, or the more the head is
bruised. When d is very small, say £ inch or less, the difference is
so groat as to make this relation useless.
MeAtyiiw'x formula f is P = SO ( W + 0.258 I/A — 1). It was
deduced from experiments made in connection with the construc-
tion of the Brooklyn dry-dock. The author of the formula states
that it " is applicable only with hammers weighing more than a ton,
and only for soil similar to that for which it was deduced, i.e.,
quicksand.35 f
Traulioine'x formula, J in the nomenclature of page 233, is
~ 52 W |///. TJ _ „ _ f> ,1-, T
p = „„ — l£ waa (led need Irorn the observed supporting
1, — p .l*v (.!>
power of piles driven in soft soil. Strictly speaking, it is ap-
plicable only under conditions similar to those from which it was
* Jour. Frank. Inst, 8d scries, vol. xxii. p. — .
t Ibid., vol. Iv. pp. 101-02.
% Engineer's Pocket-Book, Ed. 1.885, p. 643.
ABT. 2.] BEARING- POWER OF PILES. 245
deduced; and hence it is inapplicable for hard driving and to piles
whose heads are not bruised about the same amount as were the
experimental ones. JSTo formula can be accurate which does not, in
someway, take cognizance of the condition of the head of the pile.
For example., experiments JSTos. 3 and 4 of the table on page 246 are
the same except in the condition of the heads of the piles, and yet
the load supported by the former was 2-|- times that supported by the
latter. This formula is not applicable to piles driven with a steam
hammer, since according to it the energy represented by the sinking
of the pile is greater than the total energy in the descending weight.
For example, if W = 1| tons, li — 2 feet, and d = 1 inch ='TV of a
Wli
foot, the formula P < ~~j— becomes P < 36 tons. Traut wine's
formula gives P = 49 tons ; that is to say, Trau twine's formula
makes the supporting power one third more than it would be if no
energy were lost.
366. The Author's Empirical Formula. Certain assumptions
and approximations were made in deducing equation (3), page 239.
If it is thought not desirable to trust entirely to theory, then the
formula
P= ^rqWTr+^W — qd . . . . (7)
may be considered as giving only the form which the empirical
formula should have. Under this condition q becomes a numerical
co-efficient to be determined by experiment, which must be made
by driving a pile and measuring d, after which the sustaining power
must be determined by applying a direct pressure. The last, or
test, blow should be struck on sound wood.
367. Table 29 gives all the experiments on the supporting
power of piles for which the record is complete. Unfortunately
these experiments do not fulfill the conditions necessary for a proper
determination of q in equation (7). It is known that in some of the
cases the head of the pile was considerably broomed, and there is
internal evidence that this was so in the others.
The data of the following table substituted in equation (7) give
values of q from 1.5 to 337, with an average of 130. The range of
these results shows the inconsistency of the experiments, and the
smallness of the average shows that the last blow was* not struck OP
sound wood. This value of q is of no practical lisa
246
PILE FOUNDATIONS.
[CHAP. XL
TABLE 29.
DATA OF EXPERIMENTS ON THE SUPPORTING POWER OF PILES.
as
S3
|S
*l
g
IN
o £~
°fa
SH'
Q^fi
si
gS .
SB
«g
>%*
AUTHORITY. '
o fc
aw
H Hi
Z 55
JZJ^
*
fe
S
O
1
0.455
5
0.031
30.2
Circular of the Office of Chief of Engineers
U. S. A., Nov. 12, '81, pp. 2, 3.
2
0.8
36
1.5
7.3
Trautwine's Pocket-Book, ed. 1«85, p. 643.
3
1.12
30
0.042
112.0
Jour. Frank. lust., vol. 55, p. 101.
4
1.1
30
0.042
45.9
Delafield's "Foundations in Compiesaible Soils,"
pp. 17, 18; — a pamphlet published by En-
gineers' Department of U. S. A.
5
0!95
29
0.125
50.0
Trautwine in Railroad Gazette, July 8, 1887, p.
453.
368. As confirming the reliability of ihsform of equations (3),
(4), and (7), it is interesting to notice that A. C. Hertiz* found,
from the records of the driving and afterwards pulling up of nearly
400 piles, the following relation :
Wh
P
500'
which may be put in the form
P = 4/500 Wh + (250 dy - 250 cl . . . . (8)
Equation (8) has exactly the form of equation. (3), page 239.
although deduced in an entirely different way. The value (250) of
the constant q in equation (8) is less than that in equation (4),
page 239, which shows that the heads of the piles were broomed.
The value of q in equation (8) is greater than that deduced from the
clata of Table 29, which shows that the piles from which equation
(8) was determined were not bruised as much as those in the above
table.
369. SUPPOETING POWER DETEEMINED BY EXPERIMENT. It is
not certain that the bearing power of a pile when loaded with a con-
tinued quiescent load will be the same as that during the very short
* Proc. Inst. of C. E., vol. Ixiv. pp. 311-15 ; republished in Van Nostrand's Maga-
zine, vol. xxv. pp. 273-76.
AKT. 2.] BEARING POWER OF PILES. 247
period of the blow. The friction on the sides of the pile will have
& greater effect in the former case, while the resistance to penetra-
tion of the point will be greater in the latter. This, and the fact
that the supporting power of piles sunk by the water-jet can be
•determined in no other way, shows the necessity of experiments to
determine the bearing power under a steady load.
Unfortunately no extended experiments have been made in this
direction. "We can give only a collection of as many details as pos-
sible concerning the piles under actual structures and the loads
which they sustain. In this way, we may derive some idea of the
sustaining power of piles under various conditions of actual practice.
370. Ultimate Load. In constructing a light-house at Proctors-
ville, La., in 1856-57, a test pile, 12 inches square, driven 29.5 feet,
bore 29.9 tons without settlement, but with 31.2 tons it "settled
slowly." The soil, as determined by borings, had the following
character : " For a depth of 9 feet there was mud mixed with
sand ; then followed a layer of sand about 5 feet thick, next a layer
•of sand mixed with clay from 4 to G feet thick, and then followed
fine clay. By draining the site the surface was lowered about 6
inches. The pile, by its own weight, sank 5 feet 4 inches." The
iibove load is equivalent to a frictional resistance of 600 Ibs. per
,sq. ft. of surface of pile in contact with the soil. This pile is No.
1 of the table on page 246.
At Philadelphia in 1873, a pile was driven 15 ft. into "soft river
mud, and 5 hours after 7.3 tons caused a sinking of a very small
fraction of an inch ; under 9 tons it sank f of an inch, and under
15 tons it sank 5 ft." The above load is equivalent to 320 Ibs.
per sq. ft. of surface of contact. This pile is No. 2 of the table on
page 246.
In the construction of the dock at the Pensacola navy yard, a pile
driven 16 feet into clean white sand sustained a direct pressure of
43 tons without settlement, while 45 tons caused it to rise slowly;
.and it required 46 tons to draw a pile that had been driven 1C feet
into the sand. This is equivalent to a frictional resistance of 1,900
Ibs. per sq. ft. This pile is No. 4 of the table on page 246.
" In the construction of a foundation for an elevator at Buffalo,
N. Y., a pile 15 inches in diameter at the large end, driven 18 ft.,
bore 25 tons for 27 hours without any ascertainable effect. The
weight was then gradually increased until the total load on the
24:8 PILE FOUNDATION'S. [CHAP. XI.
pile was 37£ tons. Up to this weight there had been no depression
of the pile,, but with 37^ tons there was a gradual depression which
aggregated |- of an inch, beyond which there was no depression
until the weight was increased to 50 tons. With 50 tons there was.
a further depression of -J of an inch, making the total depression
1£ inches. Then the load was increased to 75 tons, under which
the total depression reached 3|- inches. The experiment was not
carried beyond this point. The soil, in order from the top, was.
as follows : 2 ft. of blue clay, 3 ft. of gravel, 5 ft. of stiff red clay,
2 ft. of quicksand, 3 ft. of red clay, 2 ft. of gravel and sand, and
3 ft. of very stiff hlue clay. All the time during this experiment-
there were three pile-drivers at work on the foundation, thus keep-
ing up a tremor in the ground. The water from Lake Erie had
free access to the pile through the gravel."* This is equivalent
to a frictional resistance of 1,850 Ibs. per sq. ft. This is pile ]S7o. 5
of the table on page 246.
371. In making some repairs at the Hull docks, England,
several hundred sheet-piles were drawn out. They were 12 X 101
inches, driven an average depth of 18 feet in stiff blue clay, and
the average force required to pull them was not less than 35.8
tons each. The frictional resistance was at least 1,875 Ibs. per sq,
ft. of surface in contact with the soil, f
372. Safe Load. The piles under the bridge over the Missouri
at Bismarck, Dakota, were driven 32 ft. into the sand, and sustain
20 tons each — equivalent to a frictional resistance of 600 Ibs. per sq,
ft. The piles at the Plattsmouth bridge, driven 28 ft. into the
sand, sustain less than 13^- tons, of which about one fifth is live-
load, — equivalent to a frictional resistance of 300 Ibs. per sq. ft.
At the Hull docks, England, piles driven 16 ft. into " alluvial
mud " sustain at least 20 tons, and according to some 25 tons ; for
the former, the friction is about 800 Ibs. per sq. ft. The piles
under the Eoyal Border bridge "were driven 30 to 40ft. into sand
and gravel, and sustain 70 tons each/* — the friction being about
1,400 Ibs. per sq. ft.
373. "The South Street bridge approach, Philadelphia, fell by
the sinking of the foundation piles under a load of 24 tons each.
* By courtesy of John C. Trantwine, Jr., from private correspondence of John EL
Payne and W. A. Haven, engineers in charge.
tProc. Inst. of C. E., vol. Ixiv. pp. 311-15.
ART. 2.] BEARING- POWER, OF PILES. 249
They were driven to an absolute stoppage by a 1-ton hammer fall-
ing 32 feet. Their length was from 24 to 41 feet. The piles were
driven through mud, then tough clay, and into hard gravel."*
A possible explanation of the failure of these piles is that they
vibrated under the moving load, which allowed the water to work
its way down the sides of the piles and thus decrease the bear-
ing power ; but it is more probable that the last blow was struck
on a broomed head, which would greatly reduce the penetration,,
and that consequently their supporting power was overestimated.
According to Trautwine's formula — the only one of all the pre-
ceding which is even approximately applicable to this case — their
supporting power was 164 tons.
374. SUPPORTING POWER or SCREW AND DISK PILES. The sup-
porting power depends upon the nature of the soil and the depth to
which the pile is sunk. A screw pile " in soft mud above clay and
sand " supported 1.8 tons per sq. ft. of blade, f A disk pile in
"quicksand" stood 5 tons per sq. ft. under vibrations. J Charles
McDonald, in constructing the iron ocean-pier at Coney Island, as-
sumed that the safe load upon the flanges of the iron disks sunk into
the sand, was 5 tons per sq. ft.; but " many of them really support
as much as G.3 tons per sq. ft. continually and are subject to occa-
sional loads of 8 tons per sq. ft., without causing any settlement
that can be detected by the eye."§
375. FACTOR OF SAFETY. On account of the many uncertainties
in connection with piles, a wide margin of safety is recommended by
all authorities. The factor of safety ranges from 2 to 12 according
to the importance of the structure and according to the faith in the
formula employed or the experiment taken as a guide. At best,
the formulas can give only the supporting power at the time when,
the driving ceases. If the resistance is derived mainly from fric-
tion, it is probable that the supporting power increases for a time
after the driving ceases, since the co-efficient of friction is usually
greater after a period of rest. If the supporting power is derived
mainly from the resistance to penetration of a stiff substratum, the
bearing power for a steady load will probably be smaller than the
* Trans. Am. Soc. of C. E., vol. vii. p. 264.
tProc. Inst. of C. E., vol. xvii. p. 451.
I Ibid., p. 443.
§ Trans. Am. Soc. C. E., vol. viii. p. 230.
250 PILE FOUNDATIONS. [CHAP. XI.
force required to drive it, as most materials require a less force to
change their form slowly than rapidly. If the soil adjoining the
piles becomes wet, the supporting power will be decreased; and
vibrations of the structure will have a like effect.
The formulas in use for determining the supporting power of
piles are so unreliable, that it is quite impossible to determine the
factor of safety for any existing structure with anything like accu-
racy.
The factor to be employed should vary with the nature of the
structure. For example, the abutments of a stone arch should bo
constructed so that they will not settle at all ; but if a railroad pile
trestle settles no serious damage is done, since the track can be
shimmed up occasionally. In a few cases, a small settlement has
taken place in a railroad trestle when the factor of safety was 3 or
4, as computed by equation (4), page 239.
ART. 3. ARRANGEMENT OF THE FOUNDATION.
376. DISPOSITION OF THE PILES. The length of the piles to be
used is determined by the nature of the soil, or the conveniences
for driving, or the lengths most easily obtained. The safe bearing
power maybe determined from the data presented in §§ 370-73, or,
better, by driving a test pile and applying equation (4), page 239.
Then, knowing the weight to be supported, and having decided
upon the length of piles to be used, and having ascertained their
safe bearing power, it is an easy matter to determine how many piles
are required. Of course, the number of piles under the different
parts of a structure should be proportional to the weights of those
parts.
If the attempt is made to drive piles too close together, they are
liable to force each other up. To avoid this, the centers of the
piles should be, at least, 2£ or 3 feet apart. Of course, they may
be farther apart, if a less number will give sufficient supporting
power, or if a greater area of foundation is necessary to prevent
overturning.
When a grillage (§ 380) is to be placed on the head of the piles,
great care must be taken to get the latter in line so that the lowest
course of grillage timber, in this case called capping, may rest
squarely upon all the piles of a row. In driving under water, a
ART. 3.] ARRANGEMENT OF THE FOUNDATION. 251
convenient way of marking the positions of the piles is to construct
a light frame of narrow boards, called a spider, in which the posi-
tion of the piles is indicated by a small square opening. This frame
may be held in place by fastening it to the sides of the coffer-dam,
or to the piles already driven, or to temporary supports. Under
ordinary circumstances, it is reasonably good work if the center
of the pile is under the cap. Piles frequently get considerably out
of place in driving, in which case they may sometimes be forced
back with a block and tackle or a jack-screw. When the heads of
the piles are to be covered with concrete, the exact position of the
piles is comparatively an unimportant matter.
In close driving, it is necessary to commence at the center
of the area and work towards the sides ; for if the central ones are
left until the last, the soil may become so consolidated that they
can scarcely be driven at all.
377. Butt vs. Top Down. According to Kankine * all piles
should be driven large end down, having first been sharpened to a
point 1-J- to 2 times as long as the diameter of the pile. This is at
least of doubtful utility. If the pile is supported wholly by fric-
tion, then the supporting power will be greater when the small end
is down. If the soil is semi-liquid, the buoyancy would be slightly
greater when the large end is down ; but the buoyancy constitutes
but a very small part of the supporting power, and the difference
in buoyancy between top and bottom down is still less. If the pile
derives its support mainly from a solid substratum, then its bearing
power would be greater with the large end down ; but, in this case,
it should not be sharpened. For close driving, it is frequently
recommended that, to prevent the. piles from forcing each other up,
they should be driven butt end down. Notice, however, that if
the soil is non-compressible, as pure sand, or if the piles are driven
so close as to compress the soil considerably, it will rise and carry
the piles with it, whether they were driven with the big or the little
end down. Piles are generally driven small end down, but never-
theless practical experience shows that there are conditions in which
it is apparently impossible to drive them in this way, even in
comparatively isolated positions. These conditions appear to occur
most frequently in swamps, and in connection with quicksand.
* "Civil Engineering," p. 602.
252 PILE FOUNDATION'S. [CHAP. XI-
378. SA WING-OFF THE PILES. When piles are driven/ it is-
generally necessary to saw them off either to bring them to the
same height, or to get the tops lower than they can be driven, or to-
secure sound wood upon which to rest the timber platform that
carries the masonry. When above water, piles are usually sawed off
by hand ; and when below, by machinery — usually a circular saw on
a vertical shaft held between the leaders of the pile driver or mounted
upon a special frame, and driven by the engine used in driving the
piles. The saw-shaft is sometimes attached to a vertical shaft held
between the leaders by parallel bars, by which arrangement the saw
can be swung in the arc of a circle and several piles be cut off with-
out moving the machine. The piles are sometimes sawed off with
what is called a pendulum saw, i.e., a saw-blade fastened between
two arms of a rigid frame which extends into the water and is free-
to swing about an axis above. The saw is swung by men pushing
on the frame. The first method is the better, particularly when
the piles are to be sawed off under mud or silt.
Considerable care is required to get the tops cut off in a hori-
zontal plane. It is not necessary that this shall be done with mathe-
matical accuracy, since if one pile does stand up too far the excess,
load upon it will either force it down or crush the cap until the
other piles take part of the weight. Under ordinary conditions, it
is a reasonably good job if piles on land are sawed within half an
inch of the same height ; and under water, within one inch. When
a machine is used on land, it is usually mounted upon a track and
drawn along from pile to pile, by which device, after having leveled
up the track, a whole row can be sawed off with no further atten-
tion. When sawing under water, the depth below the surface is-
indicated by a mark on the saw-shaft, or a target on the saw-
shaft is observed upon with a leveling instrument, or a leveling rod
is read upon some part of the saw-frame, etc. In sawing piles off
under water, from a boat, a great deal of time is consumed (par-
ticularly if there is a current) in getting the boat into position
ready to begin work.
Piles are frequently sawed off under 10 to 15 feet of water, and
occasionally under 20 to 25 feet.
379. FINISH™* THE FOUNDATION. There are two cases: (1)
when the heads of the piles are not under water 5 and (2) when they
are under water.
JLRT. 3.] ARRANGEMENT OF THE FOUNDATION. 253
1. "When the piles are not under water there are again two cases :
(a) when a timber grillage is used ; and (b) when concrete alone is
used.
2. When the piles are sawed off under water, the timber struct-
ure (in this case called a crib) which intervenes between the piles
and the masonry is put together first, and then sunk into place. The
construction is essentially the same as when the piles are not under
water., but differs from that case in the manner of getting the tim-
ber into its final resting place. . The methods of constructing foun-
dations under water, including that by the use of timber cribs, will
be discussed in Art. "2 of the next chapter.
380. Piles and Grillage. This is a stout frame of one or more
courses of timber drift-bolted or pinned to the tops of the piles
and to each other, upon which a floor of thick boards is placed to
receive the bottom courses of masonry. For illustrated examples.,
see Fig. 84, page 362, Fig. 86, page 380, and Fig. 90, page 386.
The timbers which rest upon the heads of the piles, called caps,
,are usually about 1 foot square, and are fastened by boring a hole
through each and into the head of the pile and driving into the
hole a plain rod or bar of iron having about 25 per cent, larger cross
section than the hole.
381. These rods are called drift-bolts, and are usually either
& rod 1 inch in diameter (driven into a f-incli auger hole), or a
bar 1 inch square (driven into a ~J-inch hole). Formerly jag-bolts,,
•or rag-bolts, /. e., bolts whose sides were jagged, or barbed, were
used for this and similar purposes ; but universal experience sho\vs
that smooth rods hold much the better. In some experiments
made at the Poughkeepsie bridge (§ 414), it was found that a 1-inch
rod driven into a {f-inch hole in hemlock required on the average
a force of 2-J- tons per linear foot of rod to withdraw it; and a 1-inch
rod driven into a f-inch hole in white or Norway pine required
.5 tons per linear foot of rod to withdraw it. The old-style jag-
bolt was square because it was more easily barbed • and probably
this is the reason why square drift-bolts are now more common.
Another advantage of the round drift-bolt, over the square one, is
that the latter does not cut or tear the wood as much as the former.
The ends of the rods should, be slightly rounded with a hammer.
Transverse timbers are put on top of the caps and drift-bolted
to them. Old bridge-timbers, timbers from false works, etc., are
254 PILE FOUNDATIONS. [CHAP. XI.
frequently used, and are ordinarily as good for this purpose as new.
As many courses may be added as is necessary, each perpendicular
to the one below it. The timbers of the top course are laid close
together, or, as before stated, a floor of thick boards is added on top
to receive the masonry.
This form of construction is very common in the foundations of
bridge abutments. Of course no timber should be used in a foun-
dation, except where it will always be wet.
382. PILES AND CONCRETE. A thick layer of concrete, resting
partly on the heads of the piles and partly on the soil between
them, is frequently employed instead of the timber grillage as above.
Objection is sometimes made to the platform (§ 380) as a bed for a
foundation that, owing to the want of adhesion between wood and
mortar, the masonry might slide on2 from the platform if any un-
equal settling should take place. To obviate this, the concrete is
frequently substituted for the grillage and platform.
However, there is but slight probability that a foundation will
ever fail on account of the masonry's sliding on timber, since, ordi-
narily, this could take place only when the horizontal force is
nearly half of the downward pressure.* This could occur only
with dams, retaining walls, or bridge abutments, and rarely, if
ever, with these.. One of the fundamental principles of all masonry
construction is to build the courses perpendicular to the line of
pressure, which condition alone would prevent slipping. Any pos-
sibility of slipping can be prevented also by omitting one or more
of the timbers in the top course — the omitted timbers being per-
pendicular to the direction of the forces tending to produce sliding,
— or by building the top of the grillage in the form of steps, or by
driving drift-bolts into the platform and leaving their upper ends
projecting.
Although the use of concrete, as above, may not be necessary to
prevent sliding, it adds materially to the supporting power of the
foundation ; it utilizes the bearing power of the soil between the
piles as well as the supporting power of the piles themselves,
which is a very important consideration in soft soils. Another ad-
vantage of this form of construction is that the concrete can be laid
without exhausting the water or sawing off the piles. Frequently
* See Table 36, page 315.
ART. 3.] ARRANGEMENT OF THE FOUNDATION. 355
concrete can also be used advantageously in connection with, timber
grillage to pack in around the timbers.
.383. LATERA:I>YIELDING. Notice that, although the masonry
may not slide oif from the timber platform (§ 382), the foundation
may yield laterally by the piles themselves being pushed over. If
the piles reach a firm subsoil, it will help matters a little to remove
the upper and more yielding soil from around the tops of the piles
and fill in with broken stone ; or a wall of piles may be driven
around the foundation — at some distance from it, — and timber
braces be placed between the wall of piles and the foundation.
"When the foundation can not be buttressed in front, the structure
may be prevented from moving forward by rods which bear on the
face of the wall and are connected with plates of iron or blocks of
stone imbedded in the earth at a distance behind the wall (see
§ 551), or the thrust of the earth against the back of the wall may
be decreased by supporting the earth immediately behind the
foundation proper upon a grillage and platform resting on piles, or
the same result may be attained by constructing relieving arches
against the back of the wall (see § 552).
384. CTTSHING'S PILE FOUNDATION. The desire to utilize the
cheapness and efficiency of ordinary piles as a foundation for bridge
piers and at the same time secure greater durability than is pos-
sible with piles alone, led to the introduction of what is known as
Cushing's pile foundation, first used in 1868. at India Point, Rhode
Island. It consists of square timber piles in intimate contact with
each other, forming a solid mass of bearing timber. Surrounding
the pile cluster is an envelope of cast or wrought iron, sunk in the
mud or silt only enough to protect the piles, all voids between piles
and cylinders being filled with hydraulic concrete.
Several such foundations have been used, and have proved
satisfactory in every respect. The only objection that has ever
been urged against them is that the piles may rot above the water
line. If they do rot at all, it will be very slowly ; and time alone
can tell whether this is an important objection.
In making a foundation according to the Gushing system, the
piles may be driven first and the cylinder sunk over them, or the
piles can be driven inside the cylinder after a few sections are
in place.- In the latter case, however, the cylinders may be sub-
jected to undue strains and to subsequent damage from shock and
PILE FOUNDATIONS. [CHAP. XI.
vibration; and besides, the sawing off of the piles would be very
difficult and inconvenient, an-d they would have to be left at irreg-
ular heights and with battered tops. On the other hand, if the
piles are driven first, there is danger of their spreading and there-
by interfering with the sinking of the cylinder.
The special advantages of the Gushing piers are : (1) cheapness,
(2) ability to resist scour, (3) small contraction of the water way,
and (4) rapidity of construction.
385. Example. The railroad bridge over the Tenas Eiver, near
Mobile, rests on Gushing piers. There are thirteen, one being a
pivot pier. Each, excepting the pivot pier, is made of two cast-
iron cylinders, 6 feet in exterior diameter, located 16 feet between
•centers. The cylinders were cast in sections 10 feet long, of metal
H inches thick, and united by interior flanges 2 inches thick and
3 inches wide. The sections are held together by 40 bolts, each
1 J inches in diameter. The lower section in each pier was pro-
vided with a cutting-edge, and the top section was cast of a length
.sufficient to bring the pier to its proper elevation.
The pivot pier is composed of one central cylinder 6 feet in
diameter, and six cylinders 4 feet in diameter arranged hexagonally.
The radius of the pivot circle, measuring from the centers of cylin-
ders, is 12-|- feet. Each cylinder is capped with a cast-iron plate
2J inches thick, secured to the cylinder with twenty 1-inch bolts.
The piles are sawed pine, not less than "10 inches square at the
small end. They were driven first, and the cylinder sunk over
them. In each of the large cylinders, 12 piles, and in each of the
smaller cylinders, 5 piles, were driven to a depth not less than 20
feet below the bed of the river. The piles had to be in almost per-
fect contact for their whole length, which was secured by driving
their points in contact as near as possible, and then pulling their
tops together and holding them by 8 bolts 1J- inches in diameter.
In this particular bridge the iron cylinders were sunk to a depth
not less than 10 feet below the river bed ; but usually they are not
sunk more than 3 to 7 feet. The piles were cut off at low water,
the water pumped out of the cylinder, and the latter then filled to
the top with concrete.
CHAPTER XII.
FOUNDATIONS UNDER WATER.
386. The class of foundations to be discussed in this chapter
-could appropriately be called Foundations for Bridge Piers, since
the latter are about the only ones that are laid under water. In this
class of work two difficulties have to be overcome, both of which
require great resources and care on the part of the engineer. The
first is found in the means to be used in preparing the bed of the
foundation, and the second in preserving it from the scouring action
of the water.
Preventing the undermining of the foundation is generally not a
matter of much difficulty. In quiet water or in a sluggish stream
but little protection is required ; in which case it is sufficient to de-
posit a mass of loose stone, or riprap, around the base of the pier.
If there is danger of the riprap's being undermined, the layer must
be extended farther from the base, or be made so thick that, if
undermined, the stone will fall into the cavity and prevent further
damage. A willow mattress sunk by placing stones upon it is an
economical and efficient means of protecting a structure against
.scour. A pier may be protected also by inclosing it with a row of
piles and depositing loose rock between the pier and the piles. In
minor structures the foundation may be protected by driving sheet
piles around it.
If a large quantity of stone be deposited around the base of the
pier, the velocity of the current, and consequently its scouring
action, will be increased. Such a deposit is also an obstruction to
navigation, and therefore is seldom permitted. In many cases the
only absolute security is in sinking the foundation below the scour-
ing action of the water. The depth necessary to secure this adds to
the difficulty of preparing the bed of the foundation.
387. The principal difficulty in laying a foundation under water
consists in excluding the water. If necessary, masonry can be laid
under water by divers ; but this is very expensive and is rarely re-
sorted to.
25?
258 FOUNDATIONS UNDER WATER. [CHAP. XII.
There are five methods in use for laying foundations under water:
(1) the method of excluding the water from the bed of the founda-
tion by the use of a coffer-dam; (2) the method of founding the
pier, without excluding the water, by means of a timber crib sur-
mounted by a water-tight box in which the masonry is laid; (3) the
method of sinking iron tubes or masonry wells to a solid substratum
by excavating inside of them; (4) the method in which the water is
excluded by the presence of atmospheric air; and (5) the method of
freezing a wall of earth around the site, inside of which the excava-
tion can be made and the masonry laid. These several methods will
be discussed separately in the order named.
ART. 1. THE COFFER-DAM PROCESS.
388. A coffer-dam is an inclosure from which the water is pumped
and in which the masonry is laid in the open air. This method con-
sists in constructing a coffer-dam around the site of the proposed
foundation, pumping out the water, preparing the bed of the foun-
dation by driving piles or otherwise, and laying the masonry on the
inside of the coffer-dam. After the masonry is above the water the
coffer-dam can be removed.
389. CONSTRUCTION OF THE DAM.* The construction of coffer-
dams varies greatly. In still, shallow water, a well-built bank of
clay and gravel is sufficient. If there is a slow current, a wall of
bags partly filled with clay and gravel does fairly well; a row of
cement barrels filled with gravel and banked up on the outside has
also been used. If the water is too deep for any of the above-
methods, a single or double row of sheet piles may be driven and
banked up on the outside with a deposit of impervious soil sufficient
to prevent leaking. If there is much of a current, the puddle on
the outside will be washed away; or, if the water is deep, a large'
quantity of material will be required to form the puddle-wall; and
hence the preceding methods are of limited application.
390. The ordinary method of constructing a coffer-dam in deep
water or in a strong current is shown in Fig. 60. The area to be
inclosed is first surrounded by two rows of ordinary piles, m, m. On
the outside of the main piles, a little below the top, are bolted two-
* See also § 317, page 214.
AET. 1.]
THE COFFER-DAM PROCESS.
259
longitudinal pieces, w, w, called wales; and on the inside are fastened
two similar pieces, g, g, which serve as guides for the sheet piles, s, s,
while being driven. A rod, r, connects the top of the opposite
main piles to prevent spreading when the puddle is put in. The
timber, t, is put on primarily to carry the footway, /*, and is some-
times notched over, or otherwise fastened to, the pieces wy ID to pre-
vent the puddle space from spreading. 1) and 1) are braces extend-
ing from one side of the coffer-dam to the other. These braces are
put in position successively from, the top as the water is pumped
FIG. 60.
out; and as the masonry is built up, they are removed and the sides
of the dam braced by short struts resting against the pier.
The resistance to overturning is derived principally from the
main piles, m, m. The distance apart and also the depth to which
they should be driven depends upon the kind of bottom, the depth
of water, and the danger from floating ice, logs, etc. Rules and
formulas are here of but little use, judgment and experience being
the only guides. The distance between the piles in a row is usually
from 4 to 6 feet.
The dimensions of the sheet piles (§ 329) employed will depend
upon the depth and the number of longitudinal waling pieces used.
Two thicknesses of ordinary 2-inch plank are generally employed.
Sometimes for the deeper dams, the sheet piles are timbers 10 or 12
inches square.
The thickness of the dam will depend upon (1) the width of gang*,
way required for the workmen and machinery, (2) the thickness re-
260 FOUNDATIONS UNDER TTATER. [CHAP. XII.
quired to prevent overturning, and (3) the thickness of puddle
necessary to prevent leakage through the wall. The thickness of
shallow dams will usually be determined by the first consideration ;
but for deep dams the thickness will be governed by the second or
third requirement. If the braces, b, I, are omitted, as is sometimes
done for greater convenience in working in the coffer-dam, then the
main piles, m, my must be stronger and the dam wider in order to
resist the lateral pressure of the water. A rule of thumb frequently
nsed for this case is: "For depths of less than 10 feet make the
width 10 feet, and for depths over 10 feet give an additional thick-
ness of 1 foot for each additional 3 feet of wall." Trautwine's rule
is to make the thickness of the puddle-wall three fourths of its
height; but in no case is the wall to be less than 4 feet thick. If
the coffer-dam is wrell braced across the inclosed area, the puddle-
"wall may vary from 3 feet for shallow depths to 10 feet for great
depths; the former width has been successfully employed for depths
of 18 to 20 feet, although it is considerably less than is customary.
The puddle-wall should be constructed of impervious soil, of
which gravelly clay is best. It is a common idea that clay alone, or
clay and fine sand, is best. With pure clay, if a thread of water ever
so small finds a passage under or through the puddle, it will steadily
wear a larger opening. On the other hand, with gravelly clay, if
the water should wash out the clay or fine sand, the larger particles
will fall into the space and intercept first the coarser sand, and
next the particles of loam which are drifting in the current of water;
and thus the whole mass puddles itself better than the engineer
could do it with his own hands. An embankment of gravel is com-
paratively safe, and becomes tighter every day. While a clay em-
bankment may be tighter at first than a gravelly one, it is always
liable to breakage. Before putting in the puddling, all soft mud
and loose soil should be removed from between the rows of sheet
piles. The puddling should be deposited in layers, and compacted
as much as is possible without causing the sheet piles to bulge so
much as to open the joints.
391. Coffer-dams are sometimes constructed by building a strong
crib, and sinking it. The crib may be composed either of uprights
framed into caps and sills and covered on the- outside with tongued'
and grooved planks, or of squared timbers laid one on top of the
other, log-house fashion, and well calked. The outer uprights are
ART. 1.] THE COFFEE-DAM PROCESS. 261
braced against the inside uprights and sills to prevent crushing
inwards. This crib may be built oil land, launched, towed to its
final place, and sunk by piling stones on top or by throwing them
into cells of the crib-work which are boarded up for that purpose.
The bottom of the stream may be leveled off to receive the crib by
dredging, or the dam may be made tight at the bottom by driving
sheet piles around it. The crib must be securely bolted together
(see § 381) vertically, or the buoyancy of the water will lift off the
upper courses.
A movable coffer-dam is sometimes constructed in the same
general way, except that it is made in halves to allow of removal
from around the' finished pier. The two halves are joined together
by fitting timbers between the projecting courses of the crib, and
then passing long bolts vertically through the several courses. Some
of the compartments are made water-tight to facilitate the move-
ment of the crib from place to place.*
Coffer-dams are also built by sinking an open crib, similar to the
above, and then sheeting it on the outside by driving piles around
it after it is sunk. Eor shallow depths, this method is very efficient.
392. Sometimes two coffer-dams are employed, one inside of the
other, the outer one being used to keep out the water, and the inner
one to keep the soft material from flowing into the excavation. The
outer one may be constructed in any of the ways described above.
The inner one is usually a frame-work sheeted with boards, or a crib
of squared timbers built log-house fashion with tight joints. The
inner crib is sunk (by weighting it with stone) as the excavation
proceeds. The advantages of the use of the inner crib are (1) that
the coffer-dam is smaller than if the saturated soil were allowed to
take its natural slope from the inside of the dam to the bottom of
the excavation ; (2) the space between the crib and the dam can be
kept full of impervious material in case of any trouble with the out-
side dam ; (3) the feet of the sheet piling are always covered, which
lessens the danger of undermining or of an inflow of water and mud
under the dam ; and (4) it also reduces to a minimum the material
to be excavated.
393. Iron has been used in a few instances as a sheeting for cof-
fer-dams. Plates are riveted together to form the walls, and stayed
* For an illustrated example, see Proc. Engineer's Club of Philadelphia, vol. iv.
No. 4.
262 FOUNDATIONS UNDER, WATEK. [CHAP. XII.
on the inside by horizontal rings made of angle iron. Wood is
cheaper and more easily wrought, and therefore generally preferred.
394. LEAKAGE. A serious objection to the use of coffer-dams is
the difficulty of preventing leakage under the dam. One of the
simplest devices to prevent this is to deposit a bank of gravel around
the outside of the dam ; then if a vein of water escapes below the
sheet piling, the weight of the gravel will crush down and fill the
hole before it can enlarge itself enough to do serious damage. If the
coffer-dam is made of crib-work, short sheet piles may be driven
around the bottom of it ; or hay, willows, etc., may be laid around
the bottom edge, upon which puddle and stones are deposited ; or
a broad flap of tarpaulin may be nailed to the lower edge of the
crib and spread out loosely on the bottom, upon which stones and
puddle are placed. A tarpaulin is frequently used when the
bottom is very irregular, — in which case it would cost too much to
level off the site of the clam ; and it is particularly useful where the
bottom is rocky and the sheet piles can not be driven.
When the bed of the river is rock, or rock covered with but a
few feet of mud or loose soil, a coffer-dam only sufficiently tight to
keep out the mud is constructed. The mud at the bottom of the
• inclosed area is then dredged out, and a bed of concrete deposited
under the water (§ 154). Before the concrete has set, another coffer-
dam is constructed, inside of the first one, the latter being made water-
tight at the bottom by settling it into the concrete or by driving
sheet piles 'into it. However, the better and more usual method is
to sink the masonry upon the bed of concrete by the method de-
scribed in Art. 2 (pages 266-71).
It is nearly impossible to prevent considerable leakage, unless the
bottom of the crib rests upon an impervious stratum or the sheet
piles are driven into it. Water will find its way through nearly any
depth or distance of gravelly or sandy bottom. Trying to pump a
river dry through the sand at the bottom of a coffer-dam is expen-
sive. However, the object is not to prevent all infiltration, but only
to so reduce it that a moderate amount of bailing or pumping will
keep the water out of the way. Probably a coffer-dam was never
built that did not require considerable pumping; and not infre-
quently the amount is very great, — so great, in fact, as to make it
clear that some other method of constructing the foundation should
have been chosen.
ART. 1.] THE COFFER-DAM PROCESS. 263
Seams of sand are very troublesome. Logs or stones under tlie
edge of the dam are also a cause of considerable annoyance. It is
sometimes best to dredge away the mud and loose soil from the site
•of the proposed coffer-dam ; but,, when this is necessary, it is usu-
ually better to construct the foundation without the use of a coffer-
dam,— see Art. 2 of this chapter (page 266). Coffer-dams should
be used only in very shallow water, or when the bottom is clay or
some material impervious to water.
395. Pumps. In constructing foundations, it is frequently neces-
sary to do considerable bailing or pumping. The method to be em-
ployed in any particular case will vary greatly with the amount of
water present, the depth of the excavation, the appliances at hand,
etc. The pumps generally used for this kind of work are (1) the ordi-
nary wooden hand-pump, (2) the steam siphon, (3) the pulsometer,
and (4) the* centrifugal pump. Eotary and direct-acting steam
pumps are not suitable for use in foundation work, owing to the
deleterious effect of sand, etc., in the water to be pumped.
L Hand Power. When the lift is small, water can be bailed
out faster than it can be pumped by hand ; but the labor is propor-
tionally more fatiguing. The ordinary hand foundation-pump con-
sists of a straight tube at the bottom of which is fixed a common
flap valve, and in which works a piston carrying another valve. The
tube is either a square wooden box or a sheet-iron cylinder, — usually
the latter, since it is lighter and more durable. The pump is oper-
ated by applying the power directly to the upper end of the piston-
rod, the pump being held !n position by stays or ropes. There are
more elaborate foundation-pumps on the market.
2. The steam siphon is the simplest of all pumps, since it has
no movable parts whatever. It consists essentially of a discharge
pipe — open at both ends — through the side of which enters a smaller
pipe having its end bent up. The lower end of the discharge pipe
dips into the water ; and the small pipe connects with a steam boiler.
The steam, in rushing out of the small pipe, carries with it the air
in the upper end of the discharge pipe, thus tending fco form a
vacuum in the lower end of that pipe ; the water then rises in the
discharge pipe and is carried out with the steam. Although it is
possible by the use of large quantities of steam to raise small quan-
tities of water to a great height, the steam siphon is limited prac-
tically to lifting water only a few feet. Its cheapness and simplicity
264 FOUNDATIONS UNDEH WATER. [CHAP. XII
are recommendations in its favor, and its efficiency is not much less
than that of other forms of pumps. A common form of the steam
siphon resembles, in external appearance, the Eads sand-pump
represented in Fig. 66 (page 293).
3. The pulsometer is an improved form of the steam siphon. It
may properly be called a steam pump which dispenses with all mov-
able parts except the valves. The height to which it may lift water
is practically unlimited.
4. The centrifugal pump* consists of a set of blades revolving in-
a short cylindrical case which connects at its center with a suction
(or inlet) pipe, and at its circumference with a discharge pipe. The
blades being made to revolve rapidly, the air in the case is carried
outward by the centrifugal force, tending to produce a vacuum in
the suction pipe ; the water then enters the case and is discharged,
likewise. The distance from the water to the pump is limited by
the height to which the ordinary pressure of the air will raise the
water ; f but the height to which a centrifugal pump can lift the
water is limited only by the velocity of the outer ends of the revolv-
ing blades. "When a quick application with a discharge of large
quantities of water is the most important consideration, the cen-
trifugal pump is of great value. Since there are no valves in action
while the pump is at work, the centrifugal pump will allow sand
and large gravel — in fact almost anything that can enter between,
the arms — to pass. Pumps having a 6-inch to 10-inch discharge
pipe are the sizes most frequently used in foundation work.
396. PREPARING THE FOUNDATION. After the water is pumped
out, the bed of the foundation may be prepared to receive the
masonry by any of the processes described in §§ 2.>3~91, which see.
Ordinarily the only preparation is to throw out, usually with hand
shovels, the soft material. The masonry may be started directly
upon the hard substratum, or upon a timber grillage resting on
the soil (§§ 309-10) or on piles (§ 380).
397. COST. It is universally admitted that estimates for the
cost of foundations under water are very unreliable, and none are
more so than those contemplating the use of a coffer-dam. The
estimates of the most experienced engineers frequently differ greatly
* Frequently, but improperly, called a rotary pump.
t Some foyns of centrifugal pumps must "be immersed in the liquid to be raised.
ART. 1.] THE COFFER-DAM PROCESS. 265
from the actual cost. The difficulties of the case have already been
discussed (§ 394).
For the cost of piles and driving, see §§ 346-54. The timber
will cost, according to locality, anywhere from $15 to $25 per
thousand feet, board measure. The cost of labor in placing the
timber can not be given, since it varies greatly with the design, size,
depth, etc. The iron, in drift-bolts, screw-bolts, *and spikes, is
usually estimated at 34- to 5 cents per pound in place. Excavation
in coffer-dams frequently costs as high as $1 to $1.50 per cubic
yard, including the necessary pumping.
398. Example. The following example is interesting as show-
ing the cost under the most favorable conditions. The data are for
a railroad bridge across the Ohio River at Point Pleasant, W. Va.*
There were three 250-foot spans, one 400-foot, and one 200-foot.
There were two piers on land and four in the water ; and all ex-
tended about 90 feet above low water. The shore piers were
founded on piles — driven in the bottom of a pit — and a grillage, con-
crete being rammed in around the timber. The foundations under
water were laid by the use of a double coffer-dam (§ 392). The
water was 10 feet deep ; and the soil was 3 to 6 feet of sand and
gravel resting on dry, compact clay. The foundations consisted of
a layer of concrete 1 foot thick on the clay, and two courses of
timbers. The quantities of materials in the six foundations, and
the total cost, are as follows :
Pine timber in cribs inside of coffer-dams, and in foundations, 273,210 ft. B.M.
Oak timber in colter dams, main and sheet piling 244,412 " "
Poplar timber in cofl'er-dams 3, 597 *' "
Round piles in foundation and coffer-dams 13,571 lin, ft.
Excavation in foundations 4,342 cu. yds.
Concrete " " 649 " "
Kiprap 997 " "
The total cost of foundations, including labor of all kinds, derricks, barges,
engines, pumps, iron, tools, ropes, and everything necessary for the rapid com-
pletion of the work, was $64,652.62.
In the construction of the bridge over the Missouri River, near
Plattsmouth, Neb., a concrete foundation 49 feet long, 21 feet
wide, and 32 feet deep, laid on shore, the excavation being through
clay, bowlders, shale, and soapstone, to bed-rock (32 feet below
* Engineering News, vol. xiii. p4. 338.
266 FOUNDATION'S UNDER WATER. [CHA3?- -
surface of the water), cost $39,607.24 or $42.81 per yard for
concrete laid.*
399. For the relative cost of foundations,, see Art. 6, page £
400. CONCLUSION. Uncertainty as to what trouble and expen
coffer-darn will develop usually causes engineers to choose some ot
method of laying the foundations for bridge piers. Coffex"~clj
are applicable in shallow depths only ; hence one objection to foil
ing bridge piers by this process, particularly in rivers subject
scour or liable to ice gorges, is the danger of their being eitlior
dennined or pushed off the foundation. When founded in muc
sand, the first mode of failure is most to be feared. This dange
diminished by the use of piles or large quantities of riprap ;
such a foundation needs constant attention. When founded
rock, there is a possibility of the piers being pushed off the four
tion ; for, since it is not probable that the coffer-dam can be pu.m
perfectly dry and the bottom cleaned before laying the mason r
depositing the concrete, there is no certainty that there is g
union between the base of the pier and the bed-rock.
Coffer-dams are frequently and advantageously employed
laying foundations in soft soils not under water, as described
§§316-21 (pages 214-15).
ART. 2. THE CRIB AITD OPEN-CAISSON PROCESS.
401. DEFINITIONS. Unfortunately there is an ambiguity in
use of the word caisson. Formerly it always meant a strong,, wa
tight box having vertical sides and a bottom of heavy timbers
which the pier is built and which sinks,, as the masonry is adc
until its bottom rests upon the bed prepared for it. With tlic
troduction of the compressed-air process, the term caisson was
plied to a strong, water-tight box — open at the bottom and el<
at the top — upon which the pier is built, and which sinks to
bottom as the masonry is added. At present, the word caisson \
erally has the latter meaning. In the pneumatic process, a ws
tight box — open at the top — is usually constructed on the roo
the working chamber ("pneumatic chamber"), inside of which
masonry is built ; this box also is called a caisson. The cai;
* Exclusive of cost of buildings, tools, and engineering expenses. These :
amounted to 6 per cent, of the total cost of the entire bridge. ,
ART. 2.] THE CRIB AND OPEN-CAISSON PROCESS. 267
open at the bottom is sometimes called an inverted caisson, and the
one open at the top an erect caisson. The latter when built over
an inverted, or pneumatic,, caisson, is sometimes called a coffer-dam.
For greater clearness the term caisson will be used for the inverted,
or pneumatic, caisson ; and the erect caisson, which is built over a
pneumatic caisson, will be called a coffer-dam. A caisson employed
in other than pneumatic work will be called an open caisson.
402. PRINCIPLE. This method of constructing the foundation
consists in building the pier in the interior of an open caisson,
which sinks as the masonry is added and finally rests upon the bed
prepared for it. The masonry usually extends only a foot or two
below extreme low water, the lower part of the structure being com-
posed of timber crib-work, called simply a crib. The open caisson is
built on the top of the crib, which is practically only a thick bottom
for the box. The timber is employed because of the greater facil-
ity with which it may be put into place, as will appear presently.
Timber, when always wet, is as durable as masonry ; and ordinarily
there is not much difference in cost between timber and stone.
If the soil at the bottom is soft and unreliable, or if there is
danger of scour in case the crib were to rest directly upon the bot-
tom, the bed is prepared by dredging away the mud (§ 407) to a
sufficient depth or by driving piles which are afterwards sawed off
(§ 378) to a horizontal plane.
403. CONSTRUCTION OF THE CAISSON. The construction of the
caisson differs materially with its depth. The simplest form is
made by erecting studding by toe- nailing or tenoning them into
the top course of the crib and spiking planks on the outside. For
a caisson G or 8 feet deep, which is about as deep as it is wise to
try with this simple construction, it is sufficient to use studding 6
inches wide, 3 inches thick, and 6 to 8 feet long, spaced 3 feet apart,
mortised and tenoned into the deck course of the crib. The sides
and floor (the upper course of the crib) should be thoroughly calked
with oakum. The sides may be braced from, the masonry as the
sinking proceeds. When the crib is grounded and the masonry is
iibove the water, the sides of the box or caisson are knocked off.
"When the depth of water is more than 8 to 10 feet, the caisson
is constructed somewhat after the general method shown in Fig. 61.
The sides are formed of timbers framed together and a covering .of
thick planks on the outside. The joints are carefully calked to
268
FOUNDATIONS UNDER WATER,
[CHAP.
make the caisson water-tight. In deep caissons, the sides can be-
built up as the masonry progresses,, and thus not be in the way of
the masons. The sides and bottom are held together only by the
heavy vertical rods ; and after the caisson has come to a bearing
upon the soil and after the masonry is above the water, the rods are
detached and the sides removed, the bottom only remaining as a
part of the permanent structure.
For an illustration of the form of caisson employed in sinking a-
foundation by the compressed-air process, see Plate I.
404. The caisson should be so contrived that it can be
FIG. 61.
grounded, and afterwards raised in case the bed is found not to
be accurately leveled. To effect this, a small sliding gate is some-
times placed in the side of the caisson for the purpose of filling it
with water at pleasure. By means of this gate, the caisson can be
filled and grounded; and by closing the gate and pumping out the
water, it can be set afloat. The same result can be accomplished by
putting on and taking off stone.
Since the caisson is a heavy, unwieldy mass, it is not possible to
control the exact position in which it is sunk ; and hence it should
be larger than the base of the proposed pier, to allow for a little ad-
justment to bring the pier to the desired location. The margin to
ART. 2.] THE CRIB AKD OPEST-CAISSON PROCESS. 269
"be allowed will depend upon the deptli of water, size of caisson,,
facilities, etc. A foot all round is probably noiie too much under
favorable conditions, and generally a greater margin should be
allowed.
405. CONSTRUCTION or THE CRIB. The crib is a timber struct-
ure below the caisson,, which transmits the pressure to the bed of
the foundation. A. crib is essentially a grillage (see § 309 and § 380)
which, instead of being built in place, is first constructed and then
sunk to its final resting place in a single mass. A crib is usually
thicker, i. e.} deeper, than the grillage. If the pressure is great, the
orib is built of successive courses of squared timbers in contact; but
if the pressure is small, it is built more or less open. In either
case, if the crib is to rest upon a soft bottom, a few of the lower
courses are built open so that the higher portions of the bed may
be squeezed into these cells, and thus allow the crib to corne to an
even bearing. If the crib is to rest upon an uneven rock bottom,
the site is first leveled up by throwing in broken stone. If the bot-
tom is rough or sloping, the lower courses of the crib are sometimes
made to conform to the bottom as nearly as possible, as determined
from soundings. This method requires care and judgment to pre-
vent the crib from sliding off from the inclined bed, and should be
used with great caution, if at all.
The crib is usually built afloat. Owing to the buoyancy of the
water, about one third of a crib made wholly of timber would pro-
ject above the water, and would require an inconveniently large
weight to sink it ; therefore, it is best to incorporate considerable
stone in the crib-work. If the crib is more or less open, this is
done by putting a floor into some of the open spaces or pockets,
winch are then filled with stone. If the crib is to be solid, about
every third timber is omitted and the space filled with broken stone.
The timbers of each course should be securely drift-bolted (§ 381)
to those of the course below to prevent the buoyancy of the upper
portion from pulling the crib apart, and also to prevent any possi-
bility of the upper part's sliding on the lower.
406. TIMBER IN FOUNDATIONS. The free use of timber in
-foundations is the chief difference between American and European
methods of founding masonry in deep water. The consideration
that led to its introduction in. foundations was its cheapness. Many
of the more important bridges built some years ago rest upon crib-
270 FOUNDATIONS UJSTDEK WATER. [CHAP. XII,
work of round logs notched at their intersection and secured by
drift-bolts. At present, cribs are always built of squared timber.
As a rule, there is now but very little difference between the cost
of timber and masonry in foundations. The principal advantage
in the use of the timber in foundations under water is the facility
with which it is put into position. Soft wood or timber which
in the air has comparatively little durability, is equally as good
for this purpose as the hard woods. It has been conclusively proved
that any kind of timber will last practically forever, if completely
immersed in water.
407, EXCAVATING THE SITE. When a pier is to be founded in
a sluggish stream, it is only necessary to excavate a hole in the
bed of the stream, in which the crib (or the bottom of the caisson)
may rest. The excavation is usually made with a dredge, any form
of which can be employed. The dipper dredge is the best, but the
clam-shell or the endless chain and bucket dredge are sometimes
used. If the bottom is sand, mud, or silt, the soil maybe removed
(1) by pumping it with the water through an ordinary centrifugal
pump (§ 395), — the suction hose of which is kept in contact with,
or even a little below, the bottom, — or (2) by the Eads sand-pump
(§ 448). With either of these methods of excavating, a simple frame
or light coffer-dam may be sunk to keep part of the loose soil from
running into the excavation.
408. If the stream is shallow, the current swift, and the bottom
soft, the site may be excavated or scoured out by the river itself.
To make the current scour, construct two temporary wing-dams,
which diverge up stream from the site of the proposed pier. The
wings can be made by driving stout stakes or small piles into the
bed of the stream, and placing solid panels — made by nailing ordi-
nary boards to light uprights — against the piles with their lower edge
on the bottom. The wings concentrate the current at the location
of the pier, increase its velocity, and cause it to scour out the bed of
the stream. This process requires a little time, usually one to three
days, but the cost of construction and operation is comparatively
slight.
When the water is too deep for the last method, it is sometimes
possible to suspend the caisson a little above the bed of the stream,
in which case the current will remove the sand and silt from under
it. At the bridge over the Mississippi at Quincy, 111., a hole 10 feet
ART. 3.] DREDGING THROUGH WELLS. 271
deep was thus scoured out. If the water is already heavily charged
with sediment, it may drop the sediment on striking the crib and
thus fill up instead of scour out. Notwithstanding the hole is
liable to be filled up by the gradual action of the current or by a
sudden flood, before the crib has been placed in its final position,
this method is frequently more expeditious and less expensive than
using a coffer-dam.
409. If the crib should not rest squarely upon the bottom, it
can sometimes be brought down with a water-jet (§ 343) in the
hands of a diver. However, the engineer should not employ a
diver unless absolutely necessary, as it is very expensive.
410. If the soft soil extends to a considerable depth, or if the
necessary spread of foundation can not be obtained without an un-
desirable obstruction of the channel, or if the bottom is liable to
scour, then piles may be driven, upon which the crib or caisson may
finally rest. Before the introduction of the compressed-air process,
this was a very common method of founding bridge piers in our
western rivers ; and it is still frequently employed for small piers.
The method of driving and sawing off the piles has already been
described — see Chapter XI.
The mud over and around the heads of the piles may be sucked
off with a pump, or it may be scoured out by the current (§ 408).
The attempt is sometimes made to increase the bearing power of the
foundation by filling in between the heads of the piles with broken
stone or concrete ; but this is not good practice, as the stone does
but little good, is difficult to place, and is liable to get on top of the
piles and prevent the crib from coming to a proper bearing.
ART. 3. DREDGING THROUGH WELLS.
411. A timber crib is frequently sunk by excavating the material
through apartments left for that purpose, thus undermining the
crib and causing it to sink. Hollow iron cylinders, or wells of
masonry with a strong curb, or ring, of timber or iron beneath them,
are sunk in the same way.
This method is applicable to foundations both on dry land and
under water. It is also sometimes employed in sinking shafts in
tunneling and mining.
412. EXCAVATORS. The soil is removed from under the crib
272 FOUNDATIONS rTNDEB WATER. [CHAP. XII.
with a clam-shell dredge, or with an endless chain and bucket
dredge, or with the Eads sand-pump, or, for small jobs, with the
sand^pump employed in driving artesian wells.
The clam-shell dredge consists of the two halves of a hemi-
spherical shell, which rotate about a horizontal diameter ; the edges
of the shell are forced into the soil by the weight of the machine
itself, and the pull upon the chain to raise the excavator draws the
two halves together, thus forming a hemispherical bucket which
incloses the material to be excavated. The Morris and Gumming
dredge consists of two quadrants of a short cylinder, hinged and
-operated similarly to the above. The Milroy dredge (represented at
A in Fig. 62, page 274) appears to have the preference for this kind
of work. It consists of a frame from which are suspended a num-
ber of spherical triangular spades which are forced vertically into
the ground by their own weight ; the pull upon the excavator to
lift it out of the mud draws these triangles together and encloses
the earth to be excavated. There are several forms of dredges
similar to the above, but differing from them in details.
For a description of the Eads sand-pump, see § 448.
413. In one case in France, the soil was excavated by the aid of
•compressed air. An 8-inch iron tube rested on the bottom, with its
top projecting horizontally above the water ; and compressed air was
discharged through a small pipe into the lower end of the 8-inch
tube. The weight of the air and water in the tube was less than
an equal height of the water outside ; and hence the water in the
tube was projected from the top, and carried with it a portion of the
mud, sand, etc. Pebbles and stones of considerable size were thus
thrown out. See § 447.
414. NOTED EXAMPLES. — Poughkeepsie Bridge. The Pough-
keepsie bridge, which crosses the Hudson at a point about 75 miles
above New York City, is founded upon cribs, and is the boldest ex-
ample of timber foundation on record. It is remarkable both for
the size of the cribs and for the depth of the foundation.
There are four river piers. The crib for the largest is 100 feet
long, 60 feet wide at the bottom -and 40 feet at the top, and 104
feet high. It is divided, by one longitudinal and six transverse
walls, into fourteen compartments through which the dredge worked.
The side and division walls terminate at the bottom with a 12" X
12" oak stick, which served as a cutting edge. The exterior walls
ART. 3.] DREDGING THROUGH WELLS. 2^3
and the longitudinal division wall were built solid,, of triangular
cross section, for 20 feet above the cutting edge, and above that
they were hollow. The gravel used to sink the crib was deposited
in these hollow walls. The longitudinal walls were securely tied to
each other by the end and cross division walls, and each course of
timber was fastened to the one below by 450 1-inch drift-bolts 30
inches long. The timber was hemlock, 12 inches square. The
fourteen compartments in which the clam-shell dredges worked
were 10 X 12 feet in the clear. The cribs were kept level while
sinking by excavating from first one and then the other of the com-
partments. Gravel was added to the pockets as the crib sunk.
When hard bottom was reached, the dredging pockets were filled
with concrete deposited under water from boxes holding one cubic
yard each and opened at the bottom by a latch and trip-line.
After the crib was in position, the masonry was started in a
floating caisson which finally rested upon the top of the crib.
Sinking the crib and caisson separately is a departure from the
ordinary method. Instead of using a floating caisson, it is generally
considered better to construct a coffer-clam on top of the crib, in
which to start the masonry. If the crib is sunk first, the stones
which are thrown into the pockets to sink it are liable to be left
projecting above the top of the crib and thus prevent the caisson
from coming to a full and fair bearing.
The largest crib was sunk through about 53 feet of water, 20
feet of mud, 45 feet of clay and sand, and 17 feet of sand and
gravel. It rests, at 134 feet below high water, upon a bed of gravel
16 feet thick overlying bed-rock. The timber work is 110 feet high,
including the floor of the caisson, and extends to 14 feet below high
water (7 feet below low water), at which point the masonry com-
mences and rises 39 feet. On top of the masonry a steel tower 100
feet high is erected. The masonry in plan is 25 X 87 feet, and has
nearly vertical faces. The lower chord of the channel span is 130
feet and the rail is 212 feet above high water.
The other piers are nearly as large as the one here described.
The cribs each contain an average of 2, 500, 000 feet, board measure,
of timber and 350 tons of wrought iron.
415. Atchafalaya Bridge. This bridge is over the Atchafalaya
bayou or river, at Morgan City, La., about 80 miles west of New
Orleans. The soil is alluvial to an unknown depth, and is subject
274
FOUNDATIONS UNDER WATER.
[CHAP. xir.
to rapid and extensive scour ; and no stone suitable for piers could
be found within reasonable distance. Hence iron cylinders were
adopted. They are foundation and pier combined. The cylinders
were sunk 120 feet below high water — from 70 to 115 feet below the
mud line — by dredging the material from the inside with a Milroy
excavator. Fig. 62 shows the excavator and the appliances for
handling the cylinders.
FIG. 62.— SINKING IRON PILE BY DREDGING.
The cylinders are 8 feet in outside diameter. Below the level
of the river bed, they are made of cast iron 1J inches thick, in
lengths of 10} feet ; the sections were bolted together through in-
side flanges with 1-inch bolts spaced 5 inches apart. Above the
river bottom, the cylinders are made of wrought-iron plates f inches-
thick, riveted together to form short cylindrical sections with angle-
iron flanges. The bolts and spacing to unite the sections are the
same as in the cast-iron portions.
The cylinders were filled with concrete and capped with a heavy
ART. 3.] DREDGING THROUGH WELLS. 275
cast-iron plate. Two such, cylinders, braced together, form the pier
between two 250-feet spans of a railroad bridge.
The only objection to such piers relates to their stability. These
have stood satisfactorily since 1870.
416. Hawkesbury Bridge. The bridge over the Hawkesbury '
Eiver in south-eastern Australia is remarkable for the depth of the
foundation. It is founded upon elliptical iron caissons 48 X 20 feet
at the cutting edge, which rest upon a bed of hard gravel 126 feet
below the river bed, 185 feet below high water, and 227 feet below
the track on the bridge. The soil penetrated was mud and sand.
The caissons were sunk by dredging through three tubes, 8 feet in
diameter, terminating in bell-mouthed extensions, which met the
cutting edge. The spaces between the dredging tubes and the
outer shell were filled with gravel as the sinking progressed. The
caissons were filled to low water with concrete, and above, with cut-
stone masonry.
417. Brick Cylinders. In Germany a brick cylinder was sunk
256 feet for a coal shaft. A cylinder 25£ feet in diameter was sunk
76 feet through sand and gravel, when the frictional resistance
became so great that it could be sunk no further. An interior
cylinder, 15 feet in diameter, was then started in the bottom of the
larger one, and sunk 180 feet further through running quicksand.
The soil was removed without exhausting the water.
A brick cylinder — outer diameter 46 feet, thickness of wall 3
feet — was sunk 40 feet in dry sand and gravel without any difficulty.
It was built 18 feet high (on a wooden curb 21 inches thick), and
weighed 300 tons before the sinking was begun. The interior earth
was excavated slowly, so that the sinking was about 1 foot per day,
— the walls being built up as it sank,
In Europe and India masonry bridge piers are sometimes sunk
by this process, a sufficient number of vertical openings being left
through which the material is brought up. It is generally a tedious
and slow operation. To lessen the friction a ring of masonry is some-
times built inside of a thin iron shell. The last was the method em-
ployed in putting down the foundations for the new Tay bridge.*
418. FBICTIONAL RESISTANCE. The friction between cylinders
and the soil depends upon the nature of the soil, the depth sunk,
and the method used in sinking. If the cylinder is sunk by either
* For an illustrated account, see Engiiw&ring News, vol. xiv. pp'. 66-68.
276
FOUNDATION'S UNDER WATER.
[CHAP. xii.
of the pneumatic processes (§§ 425 and 426), the flow of the water
or the air along the sides of the tube greatly diminishes the fric-
tion. It is impossible to give any very definite data.
The following table * gives the values of the co-efficient of fric-
tion f for materials and surfaces which occur in sinking foundations
for bridge piers. Each result is the average of at least ten experi-
ments. "All materials were rounded off at their face to sledge
shape and drawn lengthwise and horizontally over the gravel or
sand,, the latter being leveled and bedded as solid as it is likely
to be in its natural position. The riveted sheet iron contained
twenty-five rivets on a surface of 2.53 X 1.67 = 4.22 square feet;
the rivet-heads were half-round and |f inch in diameter." Notice
that for dry materials and also for wet gravel and sand, the frictional
resistance at starting is smaller than during motion,, which is con-
trary to the ordinary statement of the laws of friction.
TABLE 80.
CO-EFFICIENT OF FRICTION OF MATERIALS AND SURFACES USED IN FOUN-
DATIONS.
KIND OF MATERIALS.
FOR DRY
MATERIALS.
FOR WET
MATERIALS.
— <*_,„•
'Si0 6
asf
3-53
*?a
.— O
«!
fl«M '
'5c° §
«gf
3**
faC,.'
•r .2
Is
WS
Sheet iron without rivets on gravel and sand
0.40
0.40
0.37
0.43
0.41
0.54
0.73
0.56
0.65
0.66
0.46
0.49
0.47
0.54
0.51
0.63
0.84
0.61
0.70
0.73
0.33
0.47
0.36
0.41
0.41
0.37
0.52
0.47
0.47
0.08
0.44
0.55
0.50
0.48
0.50
0.32
0.50
0.38
0.53
0.48
" " with " " " " "
C&st iron (unplaned) on gravel and sand
Granite (roughly worked) on gravel and saucl
Pine (sawed) on oravt'l and sand .
Sheet iron without rivets on sand
" " with " " "
Cast iron (unplaned) on sand
Granite (roughly worked) on sand
Pine (sawed) on sand
419. Values from Actual Practice. Cast Iron. During the
construction of the bridge over the Seine at Orival, a cast-iron
* By A. Schmoll in " Zeitschrift des Vereines Deutscher Ingenieure," as repub-
lished in Selected Abstracts of Inst. of C. E., vol. Hi. pp. 298-302.
t The co-efficient of friction is equal to the total friction divided ly the total
normal pressure; that is to say, it is the friction per unit of pressure perpendicular
to the surfaces in contact.
AET. 3.] DREDGING THROUGH WELLS. 277
cylinder, standing in an extensive arid rather uniform bed of gravel,
and having ceased to move for thirty-two hours, gave a f rictional re-
sistance of nearly 200 Ibs. per sq. ft.* At a bridge over the Danube
near Stadlau, a cylinder sunk 18.75 feet into the soil (the ]ower 3.75
feet being " solid clay") gave a frictional resistance of 100 Ibs. per
sq. ft.* According to some European experiments, the friction of
cast-iron cylinders in sand and river mud was from 400 to 600 Ibs.
per sq. ft. for small depths, and 800 to 1,000 for depths from 20 to
30 feet, f At the first Harlem River bridge, New York City, the
frictional resistance of a cast-iron pile, while the soil around it was
still loose, was 528 Ibs. per. sq. ft. of surface ; and later 716 Ibs. per sq.
ft. did not move it. From these two experiments, McAlpine, the en-
gineer in charge, concluded that "1,000 Ibs. per sq. ft. is a safe value
for moderately fine material." J At the Omaha bridge, a cast-iron
pile sunk 27 feet in sand, with 15 feet of sand on the inside, could not
be withdrawn with a pressure equivalent to 154 Ibs. per sq. ft. of
surface in contact with the soil ; and after removal of the sand from
the inside, it moved with 210 Ibs. per sq. ft.§
WrougJit Iron. A wrought-iron pile, penetrating 19 feet into
coarse sand at the bottom of a river, gave 280 Ibs. per sq. ft. ; an-
other, in gravel, gave 300 to 335 Ibs. per sq. ft.||
Masonry. In the silt on the Clyde, the friction on brick and
concrete cylinders was about 3^ tons per sq. ft.^f The friction on
the brick piers of the Dufferin (India) Bridge, through clay, was
900 Ibs. per sq. ft.**
Pneumatic Caissons. For data on the frictional resistance of
pneumatic caissons, see § 455.
Piles. Eor data on the frictional resistance of ordinary piles,
see §§ 370-71.
420. COST. It is difficult to obtain data under this head,
since but comparatively few foundations have been put down
by this process. Furthermore, since the cost varies so much with
* Van Nostrand's Engin'g Mag., vol. xx. pp. 121-22.
t Proc. Inst. of C. E., vol. 1. p. 131.
J McAlpine in Jour. Frank. Inst., vol. Iv. p, 105 ; also Proc. Inst, of C. E., vol.
xxvii. p. 286.
§ Van NostrancTs Engin'g Mag., vol. viii. p. 471.
I Proc. Inst. of C. E., vol. xv. p. 290.
1 Ibid., vol. xxxiv. p. 35.
** 'Engineering News, vol. xix. p. 160.
#78 FOUNDATIONS UNDER WATER. [CHAP. XII.
the depth of water, strength of current, kind of bottom, danger of
floods, requirements of navigation, etc., etc., no such data are valu-
able unless accompanied by endless details.
Cribs. The materials in the cribs will cost, in place, about as
follows : timber from $30 to $40 per thousand feet, board measure ;
drift and screw bolts from 3-J- to 5 cents per pound ; concrete from
$4 to $6 per cubic yard. Under ordinarily favorable conditions, the
sinking by dredging will cost about $1 per cubic yard.
Iron Tubes. Wr ought-iron plate work will cost, exclusive of
freight, from 3 to 4|- cents per pound ; cast-iron tubes, exclusive of
freight, 1|- to 2 cents per pound.
421. For the relative cost of different methods, see Art. 6
of this chapter.
422. CONCLUSION. A serious objection to this method of sink-
ing foundations is the possibility of meeting wrecks, logs, or other
obstructions, in the underlying materials ; but unless the freezing
process (see Art. 5 of this chapter) shall prove all that is claimed
for it, the method by dredging through tubes or wells is the only
one that can be applied to depths which much exceed 100 feet— the
limit of the pneumatic process.
AKT. 4. PNEUMATIC PBOCESS.
424. The principle involved is the utilization o'f the difference
between the pressure of the air inside and outside of an air-tight
chamber. The air-tight chamber may be either an iron cylinder,
which becomes at once foundation and pier, or a box — open below
and air-tight elsewhere — upon the top of which the masonry pier
rests. The former is called a pneumatic pile ; the latter a pneu-
matic caisson. The pneumatic pile is seldom used now. There
are two processes of utilizing this difference of pressure, — the
vacuum and i~h& plenum.
425. VACUUM PROCESS. The vacuum process consists in ex-
hausting the air from a cylinder, and using the pressure of the at-
mosphere upon the top of the cylinder to force it down. Exhausting
the air allows the water to flow past the lower edge into the air-
chamber, thus loosening the soil and causing the cylinder to sink.
By letting the air in, the water subsides, after which the exhaustion
may be repeated and the pile sunk still farther. The vacuum
ABT. 4.] PNEUMATIC PROCESS. 279
should be obtained suddenly, so that the pressure of the atmosphere
shall have the effect of a blow ; hence, the pile is connected by a
large flexible tube with a large air-chamber — usually mounted upon
a boat,, — from which the air is exhausted. When communication is
opened between the pile and the receiver, the air rushes from the
former into the latter to establish equilibrium, and the external
pressure causes the pile to sink.
To increase the rapidity of sinking, the cylinders may be forced
down by a lever or by an extra load applied for that purpose. In
case the resistance to sinking is very great, the material may be re-
moved from the inside by a sand-pump (§ 448), or a Milroy or clam-
shell dredge (§ 412) ; but ordinarily no earth is removed from the
inside. Cylinders have been sunk by this method 5 or 6 feet by a
.single exhaustion, and 34 feet in 6 hours.
The vacuum process has been superseded by the plenum process.
426, PLENUM, on COMPRESSED-AIR, PROCESS. The plenum, or
compressed-air, process consists in pumping air into the air-charnber,
so as to exclude the water, and forcing the pile or caisson down by
,a load placed upon it. An air-lock (§ 431) is so arranged that the
workmen can pass into the caisson to remove the soil, logs, and
bowlders, and to watch the progress of the sinking, without re-
leasing the pressure. The vacuum process is applicable only in mud
or sand; but the compressed-air process can be applied in all kinds
of soil.
427. HISTORY or PNEUMATIC PROCESSES. It is said that Papin,
the eminent physicist — born at Blois in 1647, — conceived the idea
of employing a continued supply of compressed air to enable work-
men to build under a large diving-bell. In 1779, Coulomb pre-
sented to the Paris Academy of Science a paper detailing a plan for
executing all sorts of operations under water by the use of com-
pressed air. His proposed apparatus was somewhat like that now
in general use.
In England in 1831, Earl Dundonald, then Lord Cochrane, took
out a patent for a device for sinking tubular shafts through earth
and water, by means of compressed air. His air-lock was much like
modern ones, and was to be placed at the top of the main shaft.
His invention was made with a view to its use in tiinneling under
the Thames, and in similar enterprises. In 1841, Bush also took
out a patent in England for a plan of sinking foundations by the
280 FOUNDATIONS UNDER WATER [CHAP. XII,
aid of compressed air. A German, by name G. Pfaun Muller, made
a somewhat similar design for a bridge at Mayence, in 1850 ; but as
his plan was not executed, it was, like the patents of Cochrane and
Bush, little known till legal controversies in regard to patent-rights
dragged them from obscurity.
428. The first practical application of the plenum process was
made in France in 1841 by M. Triger. In order to reach a vein of
coal on a sandy island in the Loire, opposite to Chalons, he sunk
an iron tube about 40 inches in diameter, some 60 feet, by the
blows of heavy weights. The fine sand was removed from the in-
terior by means of a scoop bucket. On reaching a layer of coarse
gravel, he could not force the tube through. He therefore capped
his tube with an air-lock, and by compressed air forced out the
water which had all the while filled the tube, and sent workmen to
the bottom. The pressure he used was never greater than two at-
mospheres. The water was discharged through a small tube, into
which, several feet from the bottom, a jet of air was allowed to
enter, thus diminishing the specific gravity of the column till it
was rapidly blown out. In 1845, Triger read a paper on the sinking-
of a tube about 6 feet in diameter to a depth of 82 feet by the same
method, and suggested the use of it for the construction of deep
foundations for bridges.
Dr. Potts, of England, generally has the credit of inventing the
vacuum process, for which he took out a patent in 1848. Many
times in sinking foundations by the vacuum process, the com-
pressed-air process was resorted to so that men could enter the pile
to remove obstructions ; and finally the many advantages of the
compressed-air process caused it to entirely supersede the vacuum-
process. At present the term " pneumatic process " is practically
synonymous with compressed-air process.
* 429. The first foundations sunk entirely by the compressed-air
process were the pneumatic piles for the bridge at Eochester, Eng-
land, put down in 1851. The depth reached was 61 feet.
The first pneumatic caisson was employed at Kehl, on the east-
ern border of France, for the foundations of a railroad bridge across
the Ehine.
430. The first three pneumatic pile foundations in America,
were constructed in South Carolina between 1856 and 1860. Im-
mediately after the civil war, a number of pneumatic piles were
AUT. 4.] PNEUMATIC PUOCESS*
k in western rivers for bridge piers. The first pneumatic cais-
sons in America were those for the St. Louis bridge (i< 457), put.
down iu IS 10. At tluit time those were the largest caissons ever
constructed, and the depth reached— 101) feet 8J inches— has not
Vet been exceeded,
Of lull1 years, the pneumatic caisson has alrnoBt entirely auper-
Beded the pneumatic pile* ; in faet the plenum-pneumatic caisson
has almost entirely superseded, except in very shallow water or in
water over about SO or lot) ft. deep, all other methods of founding
bridge piers.
431. PNE0M4TIC PILES, Although paeumaHe eylindersare now
rarely employed, they will be briefly doseribed because of their
historic interest.
The cylinders are made of either wrought or east iron. The
wrotight-iron cylinders an* composed of plates, about half an inc.h
thick, riveted together and strengthened by angle irons on the "n-
side, and reinforced at the euttting edge by plates on the, outside
both to increase the stiffness and to make the hole a little larger so
us to diminish friction. The cast-iron cylinders are composed of
sections, from i» to 10 feet long and *J to 8 feet in diameter, bolted
together by inside tlauges, the lower section being east with a sharp
cdifc to facilitate penetration. Two of these tubes, braced together,
are employed for ordinary bridge* piers; ami six small ones around
n large one for u pivot pier. They are filled with concrete, with a
few courses of masonry or a heavy iron cap at the top.
Fig. ^ shows the arrangement of the essential parts of a pneu-
matic pile. The apparatus as shown is arranged for sinking by the
plenum process ; for the vacuum process the arrangement differs
i-itlv in a few ol»vi«»ns particulars. The upper section eonstit-ntcK
the r/iV-lw/*'. The doors if and b both open downwards. To enter
the evlintler, the \v«. jnen pass into tht* air-lock, ami close the
door //, Opening the * -*k // allows the compri'SstMl air to i»ntt»r th<^
lock ; and wht*i$ the pressure is equal on both sides, the door h in
opened and the workmen pass down the cylinder by means, of H ladder.
To save lc*ss uf uir, the air-lock .should be opened very seldom, or
made very small if iv«{uircd to lu» opened often.
The nir-supplv pipe connects with a reservoir of compressed air
on n liiirgc. If the air were pumped directly into the pile without
the intervention of it storage reservoir, as was done in the early a-p-
282
UNDEB WATER.
[CHAP.
plications of the plenum process, even a momentary stoppage of tti
engine would endanger the lives of the workmen.
432. The soil may be excavated by ordinary hand tools, elevate1
to the air-lock by a windlass and bucket, and passed out throng'
the main air-lock. Sometimes a double air-lock with one large aru
one small compartment is used, the former being opened only to l<j
gangs of workmen pass and the latter to allow the passage of tlx
FIG. 63. — PNEUMATIC PILE.
skip, or bucket, containing the excavated material. Sometimes a
auxiliary lock, g f, is employed. The doors /* and g are so con:
nected by parallel bars (not shown) that only one can be opened ji
a time. The excavated material is thrown into the chute, tla
door /is closed, which opens g, and the material discharges itsel
on the outside.
Mud and sand are blown out with the sand-lift (§ 447) or sand
pump (§ 448) without the use of any air-lock.
433. The cylinders are guided in their descent by a frame-wox*
resting upon piles or upon two barges. One of the chief difficulties i
ART. 4.]
PNEUMATIC PROCESS.
283
sinking pneumatic piles is to keep them vertical. If the cylinder
becomes inclined., it can generally be righted (1) by placing wooden
wedges under the lower side of the cutting edge, or (2) by excavat-
ing under the upper side so that the air may escape and loosen the
material on that side, or (3) by drilling holes through the upper-
most side of the cylinder through which air may escape and loosen
the soil, or (4) by straining the top over with props or tackle. If
several pneumatic piles are to form a pier, they should be sunk one
at a time, for when sunk at the same time they are liable to run
together.
434. Bearing Power. The frictional resistance of iron cylinders
has been discussed in §§ 418-19, page 275-77, which see.
McAlpine, in sinking the piers of the Harlem bridge, New York
City, devised a very valuable but simple
and cheap method of increasing the bear-
ing power of a pneumatic cylinder (see r___
J?ig. 64). He attached to the lower end i;':\v; ••':•••' •>
of the cylindrical column a hollow conical <v:-\;":V "
iron section, the large end of which is ../$;S-:
much larger than the main cylinder. V;/>:
The base of the pier was still further in- ^Vy
creased by driving short sheet piles v ;.;.-;
obliquely under the lower edge of the 'v>>
conical base and removing the soil from
under them, after which the whole was filled in with concrete.*
In cold climates the contraction of the iron cylinder upon the
masonry filling might rupture the former; hence, it is sometimes
recommended to fill the pile below the frost line with asphaltic con-
crete. It has also been proposed to line the cylinders with thick,
soft wood staves, which will compress under the contraction of the
iron cylinder. However, the danger from this cause is not very
serious; for, after the concrete has set, it is strong enough to
support the load if the iron case were removed.
435. After the cylinder has reached the required depth, concrete
enough to seal it is laid in compressed air; and when this has
set, the remainder can be laid in the open air. A short distance
at the top is usually filled with good masonry, and a heavy iron cap
put over all.
Fia 64.
* Jour. Frank. Inst., yol. Iv. pp. 98 and 177.
284 FOUNDATIONS UNDEE WATER. [CHAP.
436. PNEUMATIC CAISSONS. A pneumatic caisson is an immense
box — open below, but air-tight and water-tight elsewhere, — upon the
top of which the masonry pier is built. The essential difference
between the pneumatic pile and the pneumatic caisson is one of de-
gree rather than one of quality. Sometimes the caisson envelops
the entire masonry of the pier ; but in the usual form the masonry
envelops the iron cylinder and rests upon an enlargement of the
lower end of it. The pneumatic pile is sunk to the final depth be-
fore being filled with concrete or masonry; but with the caisson
the masonry is built upward while the whole pier is being sunk
downward, the masonry thus forming the load which forces the
caisson into the soil. A pneumatic caisson is, practically, a gigantic
diving bell upon the top of which the masonry of the pier rests.
Fig. 65 is a section of a pier of the bridge across the Missouri
Eiver near Blair, Neb.,* and shows the general arrangement of the
pier and pneumatic caisson. The tube extending through the mid-
dle of the caisson and pier, known as the air-shaft, is for the ascent
and descent of the men. The air-lock — situated at the junction of
the two cylinders which form the air-shaft — consists of a short sec-
tion of a large cylinder which envelops the ends of the two sections-
of the air-shaft, both of which communicate with the air-lock by
doors as shown in Fig. 65. The apartment in which the men are
at work is known as the working chamber or air-chamber. The
small cylinders shown on each side of the air-shaft are employed in
supplying concrete for filling the working chamber when the sinking
is completed. The pipes seen in the air-chamber and projecting
above the masonry are employed in discharging the mud and sand,
as will be described presently. The timbers which appear in the
lower central portion of the working chamber are parts of the trusses
which support the central portions of the roof of the caisson.
The masonry is usually begun about 2 feet below low water, the
space intermediate between the masonry and the roof of the working
chamber being occupied by timber crib- work, either built solid or
filled with concrete. In Fig. 65 the masonry rests directly upon
the roof of the air-chamber, which construction was adopted for the
channel piers of this bridge to reduce to a minimum the obstruction
to the flow of the water.
Frequently a coffer-dam is built upon the top of the crib (see
* From the report of Geo. S. Morison, cMef engineer of the "bridge.
ART. 4.]
PKEUMATIC PROCESS.
285
Plate I); but in this particular case the masonry was kept above the
surface of the water, hence no coffer-dam was employed. When
. 65.— PNEUMATIC CAISSON.— BLAIR BRIDGE.
the coffer-dam is not used, it is necessary to regulate the rate of
sinking by the speed with which the masonry can be built, which is
liable to cause inconvenience and delay. When the coffer-dam is
286 FOUNDATIONS UNDER WATER. [CHAP.
dispensed with, it is necessary to go on with the construction of the
masonry whether or not the additional weight is needed in sinking
tne caisson.
437. The details of the construction of pneumatic caissons can
be explained best by the description of a particular case.
438. FOUNDATION OF THE HAVEE BE GRACE BKIDGE. Folding
Plate I * shows the details of the construction of the caisson, crib,
and coffer-dam employed in 1884 in sinking pier 'No. S of the
Baltimore and Ohio E. R. bridge across the Susquehanna Kiver at
Havre de Grace, Md. The timber work of Fig. 66 (page 293) also
shows some of the details of the construction of the walls of the
working chamber.
439. The Caisson. The details of the construction of the caisson
areas follows: Six courses of timber, 12 X 12 inch, one lying on top
of the other, formed the skeleton of the walls of the working cham-
ber. These timbers were first put up with a batter of f of an inch
horizontal to 1 foot vertical; they were not halved at the corners,
but every alternate piece was carried through with a full section,
"log-house" fashion. These timbers were fastened at the corners,
intersections., and several intermediate points, with drift-bolts (§ 381)
1 inch square and 22 inches long. Inside of this timber shell, three
courses of 3-inch plank, placed diagonally, were spiked to the hori-
zontal timbers and to each 'other by 6-inch and 7-inch boat-spikes.
Inside of the diagonal planking was another course of 3-inch plank
placed vertically and well spiked, the head of each spike being
wrapped with oakum to prevent leakage. The vertical seams were
thoroughly calked.
A strong and thoroughly braced truss (see also Fig. 66, page 293)
was next erected longitudinally through the center of the working
chamber. The first course in the deck of the working chamber was
men placed in position on the central truss and side walls. The work-
ing chamber was 9 feet 3 inches high from bottom of shoe to the
underside of deck, which was higher than required for working, but
was adopted so as to permit greater depth of the central truss. Out-
side of the horizontal timbers, after they had been adzed to a true
surface, were then placed the 12- by 14-inch sticks (shown at the ex-
* Compiled from the original working drawings. The accompanying description
is from personal inspection aided by an article in Engineering News by Col. Wm. M.
Patton, engineer in charge.
ART. 4.] PNEUMATIC PROCESS. 28?
trernc loft of Fig. GO) 15 foot long, extending 2 foot below the bottom
horizontal timber and having their lower ends beveled as shown.
These timbers extended G feet above the horizontal members,
and were shouldered at the upper end so that three of the deck
courses rested upon them. "Four screw-bolts were passed through.
each outside post and through the entire wall; and, in addition to
these, two drift-bolts, 1 inch square and 30 inches long, in each ver-
tical served to more thoroughly bind the wall together. This com-
pound of timber and planking formed the walls of the working
chamber. After the first deck course was in place, a few pieces of
the second course were laid diagonally to give it stiffness; the under-
side of this deck or roof was then lined with planks and thoroughly
calked, and a false bottom put into the working chamber prepara-
tory to launching it.
After the caisson was launched the deck courses, eight in all,
•were put on. The first course was made oi; single-length timbers,
reaching from inside to inside of the vertical wall posts, and resting
on top ol: the horizontal timbers and. inside planking and also on the
top chord, of the central truss, and being fastened to these members
by 22-inch drift-bolts. The second course was laid diagonally and
was made ol! varying lengths of timbers. The third course was laid
from side to side across the caisson, and the fourth course longi-
tudinally and routing on the shoulders of the 12 X 14- inch verticals.
The fifth course was laid across, the sixth diagonally- — crossing the
second course,— and the seventh and eighth courses extended to the
extreme outside limits of the caisson and. rested, on the heads of the
vertical posts. This general arrangement of the top cmirses, resting
as they did on the heads and. shoulders of the outside verticals, gave
a direct bearing on the posts and relieved the wall bolts of the great
shearing strain to which they would otherwise have been subjected.
The outside posts wore bolted to the deck courses by one 3-foot
screw-bolt and two 30-inch drift-bolts, fastening them to the longi-
tudinal and diagonal courses respectively. The several deck courses
were bolted to each other by 22-inch drift-bolts (not shown in the
illustrations), spaced 5 .foot apart along each stick. All the timbers
in the deck wore bejlded in cement mortar and the vertical joints
were grouted, so as to give a full and uniform bearing for each stick
and also decrease the leakage and danger from fire.
The center truss (HOC also Fig. GG) was constructed to bear a mil-
288 FOUNDATIONS UNDER WATER. [CHAP. XII.
formly distributed, load,, or to act as a cantilever. It was "composed
of a top and "bottom chord, each made of two 12 X 12 inch sticks,
with posts and diagonals of wood, and vertical and diagonal tie-rods
1-J- inch in diameter; the iron vertical rods extended through the
first deck courses, and the top chord was also bolted to the deck
with drift-bolts. The object of this was to enable the truss to act
.as a stiffening rib to the deck, independently of its action as a
girder. The bottom chord was also extended to the ends, and by
means of straps and bolts acted both as a strut and tie-brace for the
ends of the caisson, and constituted the only end bracing.
The sides of the caissons were braced against outside pressures by
16x16 inch timbers abutting against the walls and bottom chord of
the center truss, and against pressure from the inside by 2-inch iron
tie-rods extending from out to out of the caisson, none of which are
shown. All the timber used, except the planking and outside posts
.and the bracing in the working chamber, was 12 X 12 inch. Iron
straps, extending 6 feet on the sides and ends, were placed at the
corners and bolted to the caisson timbers. These straps were made
of bar-iron 3x1 inch and prevented spreading of the walls of the
caisson under excessive pressure within. Planks were spiked to the
lower part of the posts ; and also a narrow plank, called a shoe, was
.spiked under -the bottom of the posts (see Fig. 66).
440. "The construction was simple and strong ; in no case was
there any bending or springing of .the walls. The arrangement of
the cutting edge with square shoulders was a departure from the
ordinary V-shape (compare Figs. 65 and 66, pages 285 and 293),
und was found to possess many advantages. It enabled the men to
better regulate the sinking of the caisson by giving an increased bear-
ing surface. With this support, the material could be cleaned out
from under one side or end ; the caisson could be leveled ; and, if
the material was softer in one spot than another, the caisson could
be prevented from tipping. It further afforded a good surface for
blocking up when it was found desirable to support the caisson
during the removal of the material ; and it gave also greater security
in case of a ' blow-out ' or the failure of air-pressure. " *
"When it is anticipated that gravel or bowlders will be met w-ith
in sinking, the cutting edge is usually shod with iron. The iron
•cutting edge was omitted in all the caissons for this bridge, and it is
* Col. Win. M. Patton, engineer in charge for the railroad company.
ART. 4,1 PNKUMATK' PKOOKSS. 289
Claimed that the experience here shows that "in no case is an iron
shoo either advantageous or necessary."
441. The Crib. The construction of the crib is shown very fully
in Pluto I. The timbers were ail 1.53 X 12 inches square^ bolted to
each other by ^-inch drift-bolts— spaced f> or (J feet apart,,— and
wen* dovetailed at the corners and connections. The parts of all
the. walls of the crib were firmly bolted to the deck of the caisson.
Ordinarily the division walls of the crib are built vertically from
top to bottom ; but in this case, they wore oil-set, as shown, to
secure a better bond in the mass of concrete. If the walls are built
solid from top to bottom, the concrete filling is thereby divided into
a. number of separate monolithic columns; but in the construction
as above, the concrete forms practically a single solid mass. The,
walls are built solid, owing In the dittieulfy of getting the concrete
thoroughly packed in around so many timbers. Largo stones, such
an could be handled by one man, were bedded in mortar as the siuv
eessivo layers of eoiMTcfo were formed, and over and around theso
another layer of concrete was rammed. In most localities there is
but little dilTerencc in rust between a solid timber crib ami one with
timber pockets tilled with concrete,
442. The Coffer-dam. Uprights were first placed at intervals of
about ,"».l feet, and connected by mortise and tenon to caps and
Mils. This frame-work was held down to tbe crib by rods 2 inches
in diameter, having hooks at the lower end which passed into eye-
bolt.3 in the siden of the crib. On the sides of the dam, the upper
end of those rods panned through l".l X \* inch timbers resting on
the nides of the dam and projecting about « foot outside ; and. at the
pjuKs of the dam, they passed through short pieces bolted to one of
the t*n»*K timber* and projecting beyond the end of tho dam,
Owing to the great depth required, tho coffer-dam wan built in
^eetions, the connecting rods being made* in sections with swivel
connections The Heeoml section WHH not added until tho depth
Hunk required it,. When tbe top section of tho dam was put on,
thi* projecting en«U of the timbers through which tho connecting
rod* patwd wore xuwtul off. The. bottom section wan sheeted with
throe cours(*K of It-inrh plank, ami tho top Heetion with two thick-
!H'HHi»H. The joint between tho eolTor-dam and tho crib, and alno
the shi'otwg, wen* well calked.
The Kiden of the t2of?f*r-dum were braced against tho pressure of
290
FOUNDATIONS UNDER WATER.
[CHAP. xir.
the water, by 12 X 12 inch timbers resting on the top of each sec-
tion, and by a system of bracing in the middle of each section.
When the masonry was completed, the coffer-dam was removed by
disconnecting the vertical rods.
443. Machinery Barge. The machinery barge was an ordinary
fiat-boat fitted up for the purpose. At one end of the barge there
were three boilers each of fifty horse-power. In the middle were
two large air-compressors, designed by the contracting engineer,
Gen. Win. Sooy, Smith. One furnished all the compressed air re-
quired, the other being ready for use in case of any accident or
break-down. At the other end of the boat were two Worth ington
steam pumps to furnish water for fche excavating plant used in the
caisson. There were also a small engine and a dynamo which fur-
nished the current for the electric lamps used in the caisson and, at
night, on the outside.
444. Material Required. Table 31 gives the dimensions and
quantities of materials in the pneumatic foundations of this bridge^
and Table 32 (page 302) gives the cost
TABLE 81.
DIMENSIONS AND QUANTITIES OF MATERIALS IN FOUNDATIONS OF
HAVRE DE GRACE BRIDGE.*
II.
in.
IV.
VIII.
ix;
DIMENSIONS:
Caissons* — length, at bottom in feet
63.3
67 3
79 4
70 9
78 2
width " " " kt
25.9
25.9
32.8
32.6
42.3
height from cutting edge, in feet. .
height of working chamber, in feet
Cribi — length, in feet
17.2
9.2
61.5
17.2
9.2
61.5
17.2
9.2
77.6
17.2
9.2
69.1
19.3
9.2
76.4
width " " ....
24 2
24 2
31 1
30 8
40 5
height, " "
40.0
42.0
22.2
41.0
32.8
QUANTITIES:
Timber in the caisson, feet, board measure.
.4 <-4 ... Ct.jb, "• " "
" " " coffer-dam." " fc*
Concrete in working chamber, cubic yards. . .
" " crib, shafts, etc., 'l ** ...
4* below cutting edge, " *' ...
Iron, screw- bolts, pounds
203,473
179,939
2,068
330
1,649
000
11,318
215,565
197,910
31,517
401
1,893
623
15,651
316,689
143,993
108,518
631
1,635
126
32,881
281,540
219,680
85,759
559
2,581
526
31 026
465,125-
203,824
126,532
839
3,172
624
33,435-
drift-bolts *'
34 181
36 832
40909
44861
59 245
spikes, "
4,638
700
11 730
10'039
11 237
cast washers, *'
2472
2572
3 392
3235
3535
NUMBER OF THE PIER.
* The data by courtesy of Sooysrnith & Co., contractors for the pneumatic foundations.
445. POSITION OF THE AIR-LOCK. Before the construction of
the St. Louis bridge, the air-lock had always been placed at the top
ART. 4.] PNEUMATIC PROCESS. 291
of the air-shaft, and was of such construction that to lengthen the
shaft, as the caisson sunk,, it was necessary to detach the lock, add
a section to the shaft, and then replace the lock on top. This was
not only inconvenient and an interruption to the other work, "but
required the men to climb the entire distance under compressed
air, which is exceedingly fatiguing (see § 460). To overcome these
objections, Eads placed the air-lock at the bottom of the shaft.
This position is objectionable, since in case of a " blow-out," i. e.,
a rapid leakage of air, — not an unfrequent occurrence, — the men
may not be able to get into the lock in time to escape drowning. If
the lock is at the top, they can get out of the way of the water by
climbing up in the shaft.
At the Havre de Grace bridge, the air-shaft was constructed of
wrought iron, in sections 15 feet long. The air-lock was made by
placing diaphragms on the inside flanges of the opposite ends of the
top section. A new section and a third diaphragm could be added
without disturbing the air-lock; and when the third diaphragm
was in place, the lower one was removed preparatory to using it
again. Some engineers compromise between these two positions,
and leave the air-lock permanently at some intermediate point in
the pier (see Fig. 65, page 285).
446. EXCAVATOBS. In the early application of the pneumatic
method, the material was excavated with shovel and pick, elevated
in buckets or bags by a windlass, and stored in the air-lock. When
the air-lock was full, the lower door was closed, and the air in the
lock was allowed to escape until the upper door could be opened,
and then the material was thrown out. This method was expensive
and slow.
In the first application of the pneumatic process in America
(§430), Gen. Wm. Sooy Smith invented the auxiliary air-lock, g f,
Fig. 63 (page 282), through which to let out the excavated mate-
rial. The doors, / and g, are so connected together that only one
of them can be opened at a time. The excavated material being
thrown into the chute, the closing of the door / opens g, and the
material slides out. This simple device is said to have increased
threefold the amount of work that could be done.
447. Sand-lift, This is a device, first used by Gen. Wm. Sooy
Smith, for forcing the sand and mud out of the caisson by means
of the pressure in the working chamber. It consists of a pipe,
292 FOUNDATIONS UNDER WATER. [CHAP. XII.
reaching from the working chamber to the surface (see Fig. 63 and
Plate I), controlled by a valve in the working chamber. The sand
is heaped up around the lower end of the pipe, the valve opened,
and the pressure forces a continuous stream of air, sand,, and water
up and out. For another application of this principle, see § 413.
In sand, this method of excavating is very efficient, being eight
to ten times as expeditious as the auxiliary air-lock. Of course,
the efficiency varies with the depth, i. e.y with the pressure. When
the soil is so impervious that the water in the working chamber can
not be forced out under the edge of the caisson, it is made to pass
through the sand-lift pipe.
The "goose-neck/' or elbow at the top of the discharge pipe, is
worn away very rapidly by the impact of the ascending sand and
pebbles. At the Havre de Grace bridge, it was of chilled iron 4
inches thick on the convex side of the curve, and even then lasted
only two days. At the Brooklyn bridge, the discharge pipe ter-
minated with a straight top, and the sand was discharged against a
block of granite placed in an inclined position over the upper end.
Although the sand-lift is efficient, there are some objections to
it : (1) forcing the sand out by the pressure in the cylinder de-
creases the pressure, which causes, particularly in pneumatic piles or
small caissons, the formation of vapors so thick as to prevent the
workmen from seeing; (2) the diminished pressure allows the
water to flow in under the cutting edge ; and (3) if there is much
leakage, the air-compressors are unable to supply the air fast
enough.
448, Mud-pump. During the construction of the St. Louis
bridge, Oapt. Eads invented a mud-pump, which is free from the
above objections to the sand-lift, and which in mud or silt is more
efficient than it. This device is generally called a sand-pump, but
is more properly a mud-pump.
The principle involved in the Eads pump is the same as that
employed in the atomizer, the inspirator, ,and the injector; viz., the
principle of the induced current. This principle is utilized by dis-
charging a stream of water with a high velocity on the outside of a
small pipe, which produces a partial vacuum in the latter ; when
the pressure of the air on the outside forces the mud through the
small pipe and into the current of water by which the mud is
carried away. The current of water is the motive power.
ART. 4.]
PNEUMATIC PROCESS.
293
Pig. 66 is an interior view of the caisson of the Baltimore and
Ohio R. E. bridge at Havre de Grace, Md., and shows the general
arrangement of the pipes and mud-pump. The pump itself is a
294: FOUNDATIONS UNDER WATER. [CHAP. xn.
hollow pear-shaped casting, about 15 inches in diameter and 15
inches long, a section of which is shown in the corner of Fig. 66.
The water is forced into the pump at a, impinges against the coni-
cal casing, d, flows around this lining and escapes upwards through
a narrow annular space, /. The interior casing gives the water an
even distribution around the end of the suction pipe. The flow of
the water through the pump can be regulated by screwing the suc-
tion pipe in or out, thus closing or opening the annular space, /.
To prevent the too rapid feeding or the entrance of lumps, which
might choke the pipe, a strainer — simply a short piece of pipe,
plugged at the end, having a series of ~|-inch to |-inch holes bored
in it — was put on the bottom of the suction pipe. The discharge
pipe of the mud-pump terminates in a "goose-neck" through
which the material is discharged horizontally.
The darkly shaded portions of the section of the pump wear
away rapidly ; and hence they are made of the hardest steel and
constructed so as to be readily removed. Different engineers have
different methods of providing for the renewal of these parts, the
outline form of the pump varying with the method employed. The
pump used at the St. Louis bridge was cylindrical in outline, but
otherwise essentially the same as the above.
449. In order to use the mud-pump, the material to be exca-
vated is first mixed into a thin paste by playing upon it with a jet
of water. This pump is used only for removing mud, silt, and soil
containing small quantities of sand ; pure sand or soil containing
large quantities of sand is " blown out " with the sand-lift.
The water is delivered to the mud-pump under a pressure, ordi-
narily, of 80 or 90 pounds to the square inch. At the St. Louis
bridge, it was found that a mud-pump of 3^-inch bore was capable
of raising 20 cubic yards of material 120 feet per hour, the water
pressure being 150 pounds per square inch.*
450. Water-column. A combination of the pneumatic process
and that of dredging in the open air through tubes has been em-
ployed extensively in Europe. It seems to have been used first at
the bridge across the Rhine at Kehl. The same method was used
at the Brooklyn bridge. The principle is rudely illustrated in
* History of the St. Louis Bridge, p. 213.
ART. 4.]
PNEUMATIC PROCESS.
295
Jlir
A>
-
Lock
J^tf^.
1
*
!
j
/ Working
_•"-'."
Chamber- \
I, ,.•,.«! "-illUllMIII
- —
^"NS-
.
J^
Fia. 67.
Fig. 67. The central shaft, which is open top and bottom, projects
.a little below the catting edge,
and is kept full of water, the
greater height of water in the
column balancing the pressure
of the air in the chamber. The
workmen simply push the mate-
rial under the edge of a water-
shaft, from whence it is exca-
vated by a dredge (§ 412).
451. Blasting. Bowlders or
points of rock may be blasted in
compressed air without any ap-
preciable danger of a " blow-
out*' or of injuring the ear-
drums of the workmen. This
point was settled in sinking the foundations of the Brooklyn bridge ;
,and since then blasting has been resorted to in many cases. Bowl-
ders are sometimes " carried down/* i. e., allowed to remain on the
.surface of the soil in the working chamber as the excavation pro-
ceeds, and subsequently imbedded in the concrete with which the
air-chamber is tilled.
452. RATE OE SINKING. The work in the caisson usually con-
tinues day and night, winter and summer. The rate of progress
varies, of course, with the kind of soil, and particularly with the
number of bowlders encountered. At the Havre de Grace bridge,
the average rate of progress was 1.37 ft. per day ; at Plattsmouth,
2.22 ft. ; and at Blair, 1.75 ft. per day.
453. GUIDING THE CAISSON. Formerly it was the custom to
control the descent of the caisson by suspension screws connected
with a frame-work resting upon piles or pontoons. In a strong
current or in deep water, it may be necessary to support the caisson
partially in order to govern its descent ; but ordinarily the suspension
is needed only until the caisson is well imbedded in the soil. The
caisson may be protected from the current by constructing a break-
water above and producing dead water at the pier site.
After the soil has been reached, the caisson can be kept in its
course by removing the soil from the cutting edge on one side or
the other of the caisson. In case the caisson does not settle down.
296 FOUNDATIONS UNDER WATER. [CHAP. XII,
after the soil has been removed from under the cutting edge, a re-
duction of a few pounds in the air pressure in the working chamber
is usually sufficient to produce the desired result. At the Havre d&
Grace bridge, it was found that by allowing the discharged mate-
rial to pile up against the outside of the caisson, the latter could
bemoved laterally almost at will. The top of the caisson was made-
3 feet larger, all round, than the lower course of masonry, to allow
for deviation in sinking. The deviation of the caisson, which was-
founded 90 feet below the water, was less than 18 inches, even,
though neither suspension screws nor guide piles were employed.
In sinking the foundations for the bridge over the Missouri
Eiver near Sibley, Mo., it was necessary to move the caisson con-
siderably horizontally without sinking it much farther. This was
accomplished by placing a number of posts— 12 inches square —
in an inclined position between the roof of the working chamber
and a temporary timber platform resting on the ground below.
When these posts had been wedged up to a firm bearing, the
air pressure was released. The water flowing into the caisson
loosened the soil on the outside, and the weight of the caisson com-
ing on the inclined posts caused them to rotate about their lower
ends, which forced the caisson in the desired direction. In this
way, a lateral movement of 3 or 4 feet was secured while sinking
about the same distance.
A caisson is also sometimes moved laterally, while sinking,
by attaching a cable which is anchored off to one side and kept
taut.
454. A new method of controlling the descent of the caisson has
been recently introduced, which is specially valuable in swift cur-
rents or in rivers subject to sudden rises. It was used first in the
construction of the piers for a bridge across the Yazoo River near
Vicksburg, Miss. A group of 72 piles, each 40 feet long, was driven
into the river bed, and sawed off under the water ; the caisson was
then floated into place, and lowered until the heads of the piles-
rested against the roof of the working chamber. As the work
proceeded, the piles were sawed off to allow the caisson to sink.
One of the reasons for employing piles in this case, was that, if the
caisson did not finally rest upon bed-rock, they would assist in sup-
porting the pier.
That such ponderous masses can be so certainly guided in their
ART. 4.] PNEUMATIC PROCESS. 297
descent to bed-rock, is not the least valuable nor least interesting
fact connected with, this method of sinking foundations.
455. FRICTIONAL RESISTANCE. At the Havre de Grace bridge.
the normal frictional resistance on the timber sides of the pneumatic
caisson was 280 to 350 Ibs. per sq. ft. for depths of 40 to 80 feet,
the soil being silt, sand, and mud ; when bowlders were encoun-
tered, the resistance was greater, and when the air escaped in large
quantities the resistance was less. At the bridge over the Missouri
River near Blair, Neb., the frictional resistance usually ranged be-
tween 350 and 450 Ibs. per sq. ft., the soil being mostly fine sand
with some coarse sand and gravel and a little clay. At the Brook-
lyn bridge the frictional resistance at times was 600 Ibs. per sq. ft.
At Cairo, in sand and gravel, the normal friction was about 600 Ibs.
per sq. ft.
For data on the friction of iron cylinders and masonry shafts,
see §§ 418-19, pages 275-77; and for data on the friction of ordi-
nary piles, see §§ 370-72, pages 247-48.
456. FILLING THE AIR-CHAMBER. When the caisson has
reached the required depth, the bottom is leveled off — by blasting,
if necessary, — and the working chamber and shafts are filled with
concrete. Sometimes only enough concrete is placed in the bottom
to seal the chamber water-tight, and the remaining space is filled
with sand. This was done at the east abutment of the St. Louis
bridge, the sand being pumped ia from the river with the sand-
pump previously used for excavating the material from under the
caisson.
457. NOTED EXAMPLES. The St. Louis Bridge. The founda-
tions of the steel -arch bridge over the Mississippi at St. Louis are
the deepest ever sunk by the pneumatic process, and at the time of
construction (1870) they were also very much the largest. The
caisson of the east abutment was an irregular hexagon in plan,
83 X 70 feet at the base, and 64 X 48 feet at the top — 14 feet above
the cutting edge. The working chamber was 9 feet high. The
cutting edge finally rested on the solid rock 94 feet below low
water. The maximum emersion was 109 feet 8-J- inches, the greatest
depth at which pneumatic work has yet been done. The other
caissons were almost as large as the one mentioned above, but were
not sunk as deep.
The caissons wore constructed mainly of wood ; but the side
298 FOUNDATIONS UNDER WATER. [CHAP. xn.
walls and the roof were covered with plate iron to prevent leakage,
and strengthened by iron girders on the inside. This was the first
pneumatic caisson constructed in America ; and the use of large
quantities of timber was an important innovation, and has become
one of the distinguishing characteristics of American practice. In
all subsequent experience in this country (except as mentioned in
§ 458), the iron lining for the working chamber has been dispensed
with. The masonry rested directly upon the roof of the caisson,
i. e.y no crib-work was employed. In sinking the first pneumatic
foundation an iron coffer-dam was built upon the top of the caisson ;
but the last — the largest and deepest — was sunk without a coffer-
dam,— a departure from ordinary European practice, which is occa-
sionally followed in this country (see § 436).
458. The Brooklyn Bridge. The foundations of the towers of
the suspension bridge over the East Kiver, between New York City
and Brooklyn, are the largest ever sunk by the pneumatic process.
The foundation of the New York tower, which was a little larger
and deeper than the other, was rectangular, 172 x 102 feet at the
bottom of the foundation, and 157 X 77 feet at the bottom of the
masonry. The caisson proper was 31-J- feet high, the roof being a
solid mass of timber 22 feet thick. The working chamber was 9|-
feet high. The bottom of the foundation is 78 feet below mean
high tide, and the bottom of the masonry is 46| feet below the
same. From the bottom of the foundation to the top of the
balustrade on the tower is 354 feet, the top of the tower being 276
feet above mean high tide.
To make the working chamber air-tight, the timbers were laid
in pitch and all seams calked ; and in addition, the sides and the
roof were covered with plate iron. As a still further precaution,
the inside of the air-chamber was coated with varnish made of rosin,
menhaden oil, and Spanish brown.
For additional details see the several annual reports of the en-
gineers in charge, and also numerous articles in the engineering
newspapers and magazines from 1869 to 1872.
459. Forth Bridge. For an illustrated account of the pneumatic
foundation work of the bridge across the Frith of Forth, Eng-
land, see Engineering News, vol. xiii. pages 242-43. The caissons
employed there differed from those described above (1) in being
made almost wholly of iron, (2) in an elaborate system of cages for
ART. 4.] PNEUMATIC PROCESS. 299
hoisting the material from the inside,, and (3) in the use of inter-
locked hydraulic apparatus to open and close the air-locks. Each
of the two deep-water piers consists of four cylindrical caissons
70 feet in diameter the deepest of which rests 96 feet below high
tide.
460. PHYSIOLOGICAL EFFECT OF COMPRESSED AIR. In the ap-
plication of the compressed-air process., the question of the ability
of the human system "to bear the increased pressure of the air be-
comes very important.
After entering the air-lock, as the pressure increases, the first
sensation experienced is one of great heat. As the pressure is still
further increased a pain is felt in the ear,, arising from the abnormal
pressure upon the ear-drum. The tubes extending from the back
of the month to the bony cavities over which this membrane is
stretched, are so very minute that compressed air can not pass
through them with a rapidity sufficient to keep up the equilibrium
of pressure on both sides of the drum (for which purpose the tubes
were designed by nature), and the excess of pressure on the outside
causes the pain. These tubes can be distended, thus relieving the
pain, by the act of swallowing, or by closing the nostrils with the
thumb and finger, shutting the lips tightly, and inflating the
cheeks. Either action facilitates the passage of the air through
these tubes, and establishes the equilibrium, desired. The relief is
only momentary, and the act must be repeated from time to time,
as the pressure in the air-lock increases. This pain is felt only
while the air in the lock is being "equalized," i. e., while the air is
being admitted, and is most severe the first time compressed air is
encountered, a little experience generally removing all unpleasant
sensations. The passage through the lock, both going in and com-
ing out, should be slow ; that is to say, the compressed air should
be let in and out gradually, to give the pressure time to equalize
itself throughout the various parts of the body.
When the lungs and whole system are filled thoroughly with
the denser air, the general effect is rather bracing and exhilarating.
The increased amount of oxygen breathed in compressed air very
much accelerates the organic functions of the body, and hence labor
in the caisson is more exhaustive than in the open air ; and on get-
ting outside again, a reaction with a general feeling of prostration
sets in. At moderate depths, however, the laborers in the caisson,
300 FOUNDATIONS UNDER WATER. [CHAP. XII,
after a little experience, feel no bad effects from the compressed air,
either while at work or afterwards.
Eemaining too long in the working chamber causes a form of
paralysis, recently named caisson disease, which is sometimes fatal.
The injurious effect of compressed air is much greater on men ad-
dicted to the use of intoxicating liquors than on others. Only
sound, able-bodied men should be permitted to work in the caisson,
In passing through the air-lock on leaving the air-chamber,, the
workman experiences a great loss of heat owing (1) to the expan-
sion of the atmosphere in the lock, (2) to the expansion of the free
gases in the cavities of the body, and (3) to the liberation of the
gases held in solution by the liquids of the body. Hence, on com-
ing out the men should be protected from currents of air, should
drink a cup of strong hot coffee, dress warmly,, and lie down for a
short time.
461. No physiological difficulty is encountered at small depths :
but this method is limited to depths not much exceeding 100 feet.,
owing to the deleterious effect of the compressed air upon the work-
men. At the east abutment of the St. Louis bridge (§ 457), the
caisson was sunk 110 feet below the surface of the water. Except
in this instance, the compressed-air process has never been applied
at a greater depth than about 90 feet. Theoretically, the depth, in
feet, of the lower edge of the caisson below the surface divided by
33 is equal to the number *of atmospheres of pressure. The press-
ure is never more than this, and sometimes, owing to the fric-
tional resistance to the flow of the water through the soil, it is a
little less. Therefore the depth does not exactly indicate the
pressure ; but the rule is sufficiently exact for this purpose. At St.
Louis, at a depth of 110 feet, the men were able to work in the
compressed air only four hours per day in shifts of two hours each,
and even then worked only part of the time they were in the air-
chamber.
With reasonable care, the pneumatic process can be applied afc
depths less than 80 or 90 feet without serious consequences. At
great depths the danger can be greatly decreased by observing the
following precautions, in addition to those referred to above : (1) In
hot weather cool the air before it enters the caisson ; * (2) in cold
* This was done in 1888 at the bridge over the Ohio River at Cairo, 111.— prob-
ably the first example. The temperature of the air was reduced 20° F.
ART. 4.] PNEUMATIC PROCESS. 301
weather warm the air in the lock when the men come out ; and
(3) raise and lower them by machinery.
For an exhaustive account of the various aspects of this subject,
see Dr. Smith's article on the " Physiological Effect of Compressed
Air/' in he Keport of the Engineer of the Brooklyn Bridge.*
462. COST. The contract for pneumatic foundation is usually
let at specified prices per unit for the materials left permanently in
the structure and for the material excavated, including the neces-
sary labor and tools. The prices for material in place are about as
follows : Timber in caisson proper, from $40 to $50 per thousand
feet, board measure, according to the locality in which the work is
done ; and the timber in the crib- work and coffer-dam about $5 to
$7 per thousand less. The concrete, which is usually composed of
broken stone and sufficient 1 to 2 or 1 to 3 Portland cement mortar
to completely fill the voids, costs, exclusive of the cement, from $5 to
$7 per cubic yard for that in the crib, and about twice this sum for
that in the air-chamber and under the cutting edge. The wrought-
iron spikes, drift-bolts, screw-bolts, and cast-iron washers cost from
3J- to 6 cents per pound. f The caisson and filling costs from $14 to
$20 per cubic yard ; and the crib and filling from $8 to $10.
The price for sinking, including labor, tools, machinery, etc.,
ranges, according to the kind of soil, from 18 to 40, or even 50,
cents per cubic foot of the volume found by multiplying the area
of the caisson at the cutting edge by the final depth of the latter
below low water. In sand or silt the cost is 18 to 20 cents, and in
stiff clay and bowlders 40 to 50 cents.
463. Examples. The table on page 302 gives the details of the
•cost of the pneumatic foundation of the Havre de Grace bridge, as
fully described in §§ 438-44.
The table on page 303 gives the details of the cost of the pneu-
matic caissons of the bridge across the Missouri River near Blair,
JSTeb. The caissons (Pig. 65, page 285) were 54 feet long, 24 feet wide,
and 17 feet high. In the two shore piers, ISTos. I and IV of the
table, the caissons were surmounted by cribs 20 feet high ; but in
the channel piers, the masonry rested directly upon the roof of the
* Prize Essay of the Alumni Association of the College of Physicians and Sur-
geons of New York City, 1873.
t There are usually from 140 to 150 pounds of iron per thousand feet (board meas-
ure) of timber.
302
FOUNDATION'S UNDER WATER.
[CHAP. XIT.
TABLE 32.
COST, TO THE R. R. Co., OF FOUNDATIONS OF HAVRE DE G-BACE BRIDGE.*
NUMBER OF THE PIER.
ITEMS.
II.
III.
IV.
VIII.
IX.
Depth of cutting edge below low water,
feet
68.3
55.5
112,124
94,504
$9,522.54
1,456.12
5,775.00
16.82
8,421.14
1,291.14
14,016.50
10.76
96.78
14.45
22,424.80
000
70.7
58.7
123,402
106,269
$10,088.44
1,587.15
7,017.50
18.37
9,262.19
1,454.85
16,090.50
11.10
1.375.00
236.15
24,680.40
10,902.50
59.9
32.3
159,588
84,014
$14,820.94
2,59<US
13,247.50
19.19
6,738.87
1,179.36
13,897.50
10.91
5,078.64
892.29
31,917.60
2,205.00
76.0
55.2
189,578
127,586
$13,176.07
2.242.40
18,987.50
24.34
8,936.58
1,749.35
21,943.50
9.91
4,013.52
684.20
37,915.60
9,205.00
65.0
32.6
231,691
107,836
$21,767.85
3,295.38
25,602.50
22.10
9,538.96
1,445.93
26,962.00
10.09
5,921.70
899.22
46,338 20
10,920.00
Depth of cutting edge below mud line,
feet
Displacement below low water, cu. ft.
** ** mud line, cu. ft . .
Caisson : timber, @, $46.80 per M
iron, © 5J4 cts. per Ib
concrete. @ $17.50 per cu. yd.
total cost, per net cu. yd
Crib : timber, @ $46.80 per M
iron, @, 5*4 cts. per Jb. . ..
concrete, ® $8.50 per net cu. yd. .
total cost, per cu. yd
Coffer-dam: timber, ® $46.80 per M
iron, @ 5J4 cts. per Ib
Cost of sinking, (& 20 cts. per cu. ft. of
displacement below low water
Concrete below cutting edge, <& $17.50 . .
Total cost of foundation
63,018.47
19.93
71,792.18
21.58
90,368.93
25.20
109,648.72
23.30
141,772.44
23.4.4
Total cost per cu. yd. of foundation be-
low masonry, including coffer-dams.
Average total cost of the foundation, to R. R. Co., per net cubic yard $22.69.
caisson. The work was done, in 1882-83, by the bridge company's
men under the direction of the engineer.
464. In 1869-72, thirteen cylinders were sunk by the plenum-
pneumatic process for the piers of a bridge over the Schuylkill
River at South Street, Philadelphia. There were three piers, one
of which was a pivot pier. There were two cylinders, 8 feet in
diameter and 82 feet long, sunk through 22 feet of water and 30
feet of " sand and tough compact mud intermingled with bowlders •"
two cylinders, 8 feet in diameter and 57 feet long, sunk through 22
feet of water and 5 feet of soil as above ; one cylinder, 6 feet in
diameter and 64 feet long, sunk through 22 feet of water and 18
feet of soil as above ; and 8 columns, 4 feet in diameter and aggre-
gating 507 feet, sunk through 22 feet of water and 18 feet of soil
as above. A 10-foot section of the 8-foot cylinder weighed 14,600
pounds, of the 6-foot, 10,800 pounds, and of the 4-foot, 6,800
pounds. The cylinders rested upon bed-rock, and were bolted to
* Data by courtesy of Sooysmith <fe Co., contracting engineers for the pneumatic
foundations.
ART. 4.]
PNEUMATIC PROCESS.
It. The actual cost to the contractor, exclusive of tools and ma-
chinery, was as in Table 34 (page 304).
TABLE 38.
COST OF PNEUMATIC FOUNDATIONS OF BLAIR BRIDGE.*
ITEMS.
NUMBER OF THE PIER.
I.
II.
III.
IV.
Total distance caisson was lowered after comple-
tion
55.6 ft.
51.9 "
•17.7' "
$11,753.51
14.81
7,308.1(5
54.5 ft.
58.3 l4
51.0 "
$18,380.50
15.18
no.s ft.
53.4 "
•19.4 "
$18,819.84
10.74
08.5 ft.
57.0 "
54.7 "
$11,252.45
13.77
0,303.46
7.59
1,521.08
7,084.20
7.1 cts.
9.G u
100 "
$20,101.85
15.85
Final depth of cutting; edge below surface of water
*' ** u " '* ** mud line
Caisson and filling1, cost of .
Crib and filling, cost of
44 " '* i% " per cubic yard
Air-lock, shafts, etc., cost o f
H.H5
1,481.00
5,778.58
8.0 cts.
8.0 "
9 8 *'
1,507.48
5,020.87
8.0 cts.
8.8 "
8.5 "
$19,583.85
83.87
1,530.80
6,888.10
9.5 cts.
9.9 "
10.8 "
$88,844.80
87.08
Sinking caisson, cost of, including erection and re-
moval of machinery
Sinking eaisHon, cont. of, per cubic Coot of displace-
ment below position of cutting edge when
caisson wan completed . .
Sinking caisson, cosr. of, per cubic foot of displace-
ment below surface of water
Sinking caisson, cost of, per cubic foot of displace-
To tal cost t of foundat ion
$80,875.70
15.98
Average cost t of the foundations, per cubic yard $80.70.
465. "Excavation in the Brooklyn caisson J cost for labor
only, including the men on top, about $5.25 per cubic yard
[19 cents per cubic foot]. Illuming the six air-compressors
added to this $;$.(>() per hour, or about 47 cents per yard ; lights
added $0.5(> more ; and those with other contingencies nearly
equaled the cost of labor. The great cost was due to the excessive
hardness of the material over much of the surface, the caisson finally
resting, for nearly its whole extent, on a mass of bowlders or hard-
pan. The concrete in the caisson cost, for every expense, about
* Compiled from the report of (Joo. 8. Morison, chief engineer of the bridge.
t Exclusive of engineering expenses and cost of tools, machinery, and buildings.
In a note to the author, Mr. Mormon, thc.englneer of the bridge Hays : "It is impoa-
Bible to divide the building*, tools, and engineering cxponsos between the substruct-
uro and other portions of the work. The bulk of the items of tooln and machinery
[$1SV«J9.88']T however, relates to the foundation**." The engineering expenses and
buildings wore nearly :J per cont. of the, total cost of the entire bridge. The cost of
toolH and machinery was equal to a little over IJi per cent of the ooHt of the founda-
tionH UH above. Including those) items would add nearly one sixth to the amounts in
the lost three linos.
t For a brief description, wo, fl 458.
304
FOUNDATIONS UNDER WATER.
[CHAP. xn.
TABLE 34.
COST OF PNEUMATIC PILES AT PHILADELPHIA IN 1869-73.*
ITEMS OF EXPENSE.
4-ft.
6-ft.
8- ft.
•Cost of cast iron @, $59 50 per ton
$11,239.36
489.84
1,266.79
6,693.50
$2,053.75
93.31
358.40
911.88
$13,577.90
670.02
2,779.97
9,036.51
" " bolts, @. 9^ cents per Ib
" " grouted rubble masonry (exclusive of labor), @, $5.40
per cu. yd ...
u 'l sinking and laying masonry
Total cost of the cylinders in place
$19,689.49
$23.10
2.50
13.20
$3,417.34
$33.54
5.60
14.25
$26,064.40
$51.25
10.00
32.51
Oost of iron per lineal foot of cylinder
a " materials for mason /y per lineal foot of cylinder
" " sinking and laying masonry per lineal foot of cylinder
Total cost,t per lineal foot, of cylinder in place
$38.80
$53.39
$93.76
DIAMETER OF CYLINDERS.
$15.50 per cubic yard. The caisson and filling together aggregated
16,898 cubic yards ; and the approximate cost per yard for every
expense was $20.71. "J The foundation therefore cost about $30
per cubic yard.
The pneumatic foundations for the channel piers of the bridge
over the Missouri at Plattsmouth, Neb.,, cost as follows : One
foundation, consisting of a caisson 50 ft. long, 20 ft. wide, and 15.5
ft. high, surmounted by a crib 14.15 ft. high, sunk through 13 ft.
of water and 20 ft. of soil, cost $19.29 per cubic yard of net volume.
Another, consisting of a caisson 50 ft. long, 20ft. wide, and 15.5
ft. high, surmounted by a crib 36.25 ft. high, sunk through 10
ft. of water and 44 ft. of soil, cost $14.45 per cubic yard of net
volume. §
466. European Examples. The following*]" is interesting as
showing the cost of pneumatic work in Europe :
" At Moulins, cast-iron cylinders, 8 feet 24- inches in diameter,
with a filling of concrete and sunk 33 feet below water into marl,
•cost $62.94 per lineal foot, or $29.71 for the iron work, and $33.23
* Compiled from an article by D. McN. Stauffer, engineer in charge, in Trans. Am.
;Soc. of C. E., vol. vii. pp. 287-309.
t Exclusive of tools and machinery.
I F. Collingwood, assistant engineer Brooklyn bridge, in Trans. Am. Soc. of C. E.
§ Compiled from the report of Geo. S. Morison, chief engineer of the bridge.
1T By Jules Gaudard, as translated from the French by L. F. Vernon-Harcourt for
the Proceedings of the Institute of Civil Engineers (London).
ABT. 4.] PNEUMATIC PROCESS. 305
for sinking and concrete. At Argentenil, with cylinders 11 feet 10
inches in diameter, the sinking alone cost $42.12 per lineal foot
.[nearly $10 per cubic yard], where a cylinder was sunk 53i feet in
three hundred and ninety hours. [The total cost of this founda-
tion was $34.09 per cubic yard, see table on page 310.] At Orival,
where a cylinder was sunk 49 feet in twenty days, the cost of sinking-
was $36.83 per lineal foot. At Bordeaux, with the same-sized
-cylinders, a gang of eight men conducted the sinking of one cylin-
der, and usually 34 cubic yards were excavated every twenty-four
hours. The greatest depth reached was 55f feefc below the ground,
.and 7 L feet below high water. In the regular course of working, a
cylinder was sunk in from nine to fifteen days, and the whole opera-
tion, including preparations and filling with concrete, occupied on
the average 25 days. One cylinder, or a half pier, cost on the aver-
age $11,298.40, of which $1,461 was for sinking. M. Morandiere
estimates the total cost of a cylinder sunk like those at Argenteuil,
to a depth of 50 feet, at $7,012.80.
467. " Considering next the cost of piers of masonry on wrought-
iron caissons of excavation, the foundations of the Lorient viaduct
over the Scorfi cost the large sum of $24.11 per cubic yard, owing to
difficulties caused by the tides, the labor of removing the bowlders
from underneath the caisson, and the large cost of plant for only
two piers. The foundation of the Kohl bridge cost still more, about
$28.23 * per cubic yard ; but this can not be regarded as a fair in-
.stance, being the first attempt [see § 429] of the kind.
" The foundations of the Nantes bridges, sunk 56 feet below
low-water level, cost about $14.84 per cubic yard. The average
cost per pier was as follows :
Oaisson (41 feet 4 inches by 14 feet 5 inches), 50 tons of wrought
iron @ $116.88 $5,844
Coffer-dam, 3 tons of wrought iron @, $58.44 175
Excavation, 916 cubic yards @ $4.47 4,091
•Concrete 4,188
Masonry, plant, etc 1,870
Average cost per pier $16,168
"One pier of the bridge over the Meuse at "Rotterdam, with a
* Notice the slight inconsistency between this quantity and the one in the third
line from the last of the table on page 310, both feeing from the same article.
306 FOUNDATIONS UNDER WATER. [CHAP. XII,
caisson of 222 tons and a coffer-dam casing of 94 tons, and sunk 75
feet below high water, cost $70,858, or $13.97 per cubic yard.
" The Vichy bridge has five piers built on caissons 34 feet by 13-
feet, and two abutments on caissons 26 feet by 24 feet. The foun-
dations were sunk 23 feet in the ground, the upper portion con-
sisting of shingle and conglomerated gravel, and the last 10 feet of
marl. The cost of the bridge was as follows :
Interest for eight months, and depreciation of plant worth $19,480. . $ 3,896
Cost of preparations, approach bridge, and staging 4,904
Caissons (seven), 150| tons @ $113.38 17,10S
Sinking 9, 823
Concrete and masonry 5,303-
Contractor's bonus and general expenses , 6,107
Total cost of five foundations $47,141
The cost per cubic yard of the foundation below low water was
$16.69, of which the sinking alone cost $3.50 in gravel, and $4.37
in marl.
"At St. Maurice, the cost per cubic yard of foundation was.
$15. 94, exclusive of staging."
468. CONCLUSION. Except in very shallow or very deep water,,
the compressed-air process has almost entirely superseded all others.
The following are some of the advantages of this method. 1. It is-
reliable, since there is no danger of the caisson's being stopped,,
before reaching the desired depth, by sunken logs, bowlders, etc.,
or by excessive friction, as in dredging through tubes or shafts in
cribs. 2. It can be used regardless of the kind of soil overlying the
rock or ultimate foundation. 3. It is comparatively rapid, since
the sinking of the caisson and the building up of the pier go on at
the same time. 4. It is comparatively economical, since the weight
added in sinking is a part of the foundation and is permanent, and
the removal of the material by blowing out or by pumping is as
uniform and rapid at one depth as at another, — the cost only being
increased somewhat by the greater depth. 5. This method allows
ample opportunity to examine the ultimate foundation, to level the
"bottom, and to remove any disintegrated rock. 6. Since the rock
can be laid bare and be thoroughly washed, the concrete can be com-
menced upon a perfectly clean surface ; and hence there need be no
question as to the stability of the foundation.
ART, 5.] THE FREEZING PIKKVKSK. 307
ART. r>. Tun KKKKZINU PROCESS.
469. PRINCIPLE. The. presence of water has always been the
great obstacle in foundation work and in shaft sinking, and it
is only very recently that any one thought of transforming the
liquid soil into a. solid wall of iee about the space to be excavated*
The method of doing this consists in inclosing the site to be ex-
cavated, by driving into the ground a number of tithes through
which a freezing mixture is made to circulate. These consist of a
large tube, ('.lowed at the lower end, inclosing a smaller one, open at
the lower end. The. freezing mixture is forced down the inner
tube, and rises through the outer erne. At the top, these tubes
connect, with a reservoir, a refrigerating machine, and a pump.
The freezing liquid is cooled by an ice-making machine, and then
forced through the. tubes until a wall of earth is frozen around
them of sufficient thickness to stand the external pressure, when
the, excavation can proceed as in dry ground.
470. HlSTOKY. This method was invented by K. II. PooLseh,
M.D., of Asoherslcben, Prussia, in 188-1. It has been applied in
but three cases. The first, warf at the Archibald colliery, near
Sehweidlingen, Prussia, where- a vein of quicksand, ^0 feet thick, was
encountered at. a depth of about 1,50 Feet below the, surface. Hero
twenty-throe pipes wore ustul, and .'{"> days consumed in the freezing
process, under local difficult ion. The second was at the ('entrurn
mine, near Berlin, when* about, 107 foot, of quicksand, etc., was
penetrated. Engineers had boon baffled for years in their aUomptH
to Hink a shaft hen* ; but m **f»! days Mr. Poe.tseh had, with only 1(>
freezing tubes, secured a 0-foot wall of ice around the shaft area, and
the shaft wan excavated and curbed without difficulty. The third
piece of work WHH at the Him ilia mine, Fensterwal.de, Austria, in
1885, where- an H|-foot nhaft wan nunk through 115 feet of quick-
sand.*
471. DETAILS OP THE PBOCESS. In the last ease mentioned
above, 4A 12 circulatory tubes were used, sunk in a circle about 14
foot in diameter, from Isi to 15 dayn being required to sink them a
depth of about 100 foot. The outnido tuben were 8| iue-hoH in
AH thirt volumt* in going thrmigh th«» pn*HHt this method IK bolng apjilltnl In two
in this country— Iron, Mountain, Mit;h.f ami Wyoming, Pcmnu— in Binkhig
308 FOUNDATIONS UNDER WAT Ell. [CHAP. XII.
diameter, and made of plate iron 0.15 inch thick. The tubes were
stmk by aid of the water-jet. They were given a very slight incli-
nation outward at the bottom to avoid any deviation in sinking
that might interfere with the line of the shaft. The freezing
liquid employed was a solution of chloride of calcium, which con-
.geals at a temperature of -35° C. ( -31° P.). The circulation of
the liquid through the tubes was secured by a small pump with
a piston 6 inches in diameter and a 15-inch stroke. At the begin-
ning of the operation, this pump made 30 double strokes per min-
ute, which was equivalent to the passage of 0.6 gallon of the liquid
through each tube per minute ; at the end of the operation, when
it was only necessary to maintain the low temperature, the pump
strokes were reduced to 15 per minute. The refrigerating machine
employed was one of a model guaranteed by the maker to produce
1,100 pounds of ice per hour. The motive-power was supplied by
a small engine of about 5 horse-power. The ammoniac pump had
a piston 2.8 inches in diameter and a 9.2-inch stroke, and made 30
strokes per minute. The pressure maintained was about 10 atmos-
pheres. The quantity of ammoniacal liquid necessary to charge
the apparatus was 281 gallons ; and under normal conditions the
daily consumption of this liquid was 0.78 gallon.
"The actual shaft excavation was commenced 53 clays after the
freezing apparatus had been set in motion. The freezing machine
was in operation 240 days. The work was done without difficulty,
and a progress of 1.64 feet per day was made. The timbering was
very light, but no internal pressure of any kind was observed. The
brick masonry used for finally lining the shaft was about 11 inches
thick. When the shaft was finished, the tubes were withdrawn
without difficulty, by circulating through them a hot, instead of a
cold, solution of the chloride of calcium, thus thawing them loose
from the surrounding ice. The tubes were entirely uninjured, and
could be used again in another similar operation.
472. fi The material in the above plant is estimated to have cost
$15,000, and $4,800 more for mounting and installation. The daily
expense of conducting the freezing process is estimated at $11. The
total expense for putting down the shaft is estimated at $128 66 per
linear foot/'* The last is equivalent to about $2.25 per cubic foot.
* Migineering N&ios, vol. xiv. pp. 24, 25, translated from Le Gtnie Civil of June 13.
1885.
ART. ().'] COMPARISON OF MICTHODS. 309
473. Modification for Foundations under Water. For sinking
foundations underwater, two met hods of applying this process have
been proposed. One of these1 consists in combining the pneumatic,
and freezing processes. A pneumatic caisson is to be sunk a short,
distance into the river-bed, and then the congealing tuboK are
applied, and the entire mass between the caisson and the rock is
frozen solid. When the freezing is completed, the caisson will be
practically sealed against the entrance of water, and the air-lock can
be removed and the masonry built up as in the open air.
The other method consists in sinking an open caisson to the
river-bed, and putting the five/.ing tubes down through the water.
When the congelation is Completed, the water can be pumped out
and the work conducted in the open air.
474. ADVANTAGES CLAIMED, It is claimed for this process that
it is expeditious and economical, and also that it is particularly
valuable in that it makes possible an accurate estimate of the total
cost before* the work is commenced,-- a condition of affairs unat-
tainable by any other known method in equally ditlieult ground. It
has an advantage over the pneumatic process in that it is not limited
by depth. It can he applied horizontally us well UH vertically, and
hence is specially useful in sub-aqueous tunneling, particularly in
noils which, with compressed air. are trcac.hcrotiH.
475. DIFFICULTIES ANTICIPATED. So far it has been used only
in sinking shafts for mines. Two tliflirultics. arc anticipated in ap-
plying it to sink foundations for bridge piers in river beds; viss.,
(1) the dillieulty in sinking the pipes, owing to striking sunken logs,
bowlders, etc,; and (v) the possibility of encountering running
water, which will thaw the ice-walk Those dillleulticH are not in-
surmountable, but experience only can demonstrate how HcriouB
they arc.
470. COST. Sec JJ 47'-, and compare with table on page JMO.
Airr. f», COMPARISON OK MHTHODS.
477. The following comparison of the different methods in from
an artic.lt* by Jules Uaudnrd on Foundations, as translated by \j, F.
Vernon-Haivourt for the proceedings of the Institute of Civil Kn-
gineorH (London)* Kxe«»pt us showing approximate relative costs in
Kurope, it is not of murh value, owing to improvement made since
the article wus written, to the differences between European and
310
FOUNDATION'S UNDER WATER.
[CHAP. xir.
American practice, and to differences in cost of materials in the two
countries.
478. " M. Croizette Desnoyers has framed a classification of the
methods of foundations most suitable for different depths, and also
an estimate of the cost of each. These estimates, however, must be
considered merely approximate, as unforeseen circumstances pro-
duce considerable variations in works of this nature.
TABLE 35.
COST OF VARIOUS KINDS OF FOUNDATIONS IN EUROPE.
KIND OF FOUNDATION.
DEPTH
IN FEKT.
COST PER
CUBIC YARD.
Min.
Max.
Min.
Max.
On piles after compression of the ground, shallow depth. . .
20
33
33
33
50
50
20
33
33
33
33
$2.92
4.39
7.30
2.92
4.39
14.85
4.37
9.00
13.39
$24.
29.
34.
40.
$4.39
7.30
9.00
4.39
13.39
17.77
9.00
11.93
16.17
11
71
09
17
u tt tt kk »4 it 44 greater depth
By sinking wells
By pumping
k* " under favorable circumstances
26
26
20
20
" " " unfavorable circumstances
On concrete under water, small amount of silt
" " " " large " " "
By means of compressed air* under favorable circumstances. . .
" " " " '* " unfavorable circumstances:
Lorient viaduct
[50 ft.]
po " 1
[50 « ]
Kehl bridge t
Argenteuil bridge
Bordeaux bridge
* See also §§ 466-67. t See foot-note on page 305.
"When the foundations consist of disconnected pillars or piles,
the above prices must be applied to the whole cubic content, includ-
ing the intervals between the parts ; but of course at an equal cost
solid piers are the best.
479. f ' For pile-work foundations the square yard of base is prob-
ably a better unit than the cubic yard. Thus the foundations of
the Vernon bridge, with piles from 24 to 31 feet long, and with
cross-timbering, concrete, and caisson, cost $70 per square yard of
base. According to estimates made by M. Picquenot, if the foun-
dations had been put in by means of compressed air, the cost would
have been $159.64 ; with a caisson, not water-tight, sunk down,
$66.27 ; with concrete poured into a space inclosed with sheeting,
$62.23 ; and by pumping, $83.56 per square yard of base."
IV.
MASON it V STRUCTURES.
CHAPTKU XIII;
JVI ASONf H V DAMS.
480. It us not the intention here to discuss every feature of
masonry dams ; thai ban been done in the special reports and arti-
cles referred to at the end of this chapter. The Fundamental prin-
ciples will IK* considered, particularly with reference to their appli-
cation in the subsequent study of retaining walls, bridge* abutments,
bridge piers, and arches. The discussions of this chapter are
applicable to masonry darns, reservoir walls, or to any wall which
counteracts the pressure of water mainly by its weight,
There an* two ways in which a masonry dam may resist tho
thrust of the water; vi/,., (1) by the inertia of its masonry, and
(%) an an arch. 1. The* horizontal thrust of the water may be held
in equilibrium by the resistance* of the masonry to sliding forward
or to overturning. A dam which nets in this way in called a t/rtt /'////
t/tnn. 2. The thrust of the water may he resisted by being trans-
mitted laterally to the side-hills (abutments) by the arch-like action
of the masonry. A dam which acts in thin way in called an arched
dam.
Only two dams of the pun* arch type have ever been built. Tho
almost exclusive, use of the gravity type is due to the uncertainty
of our knowledge' concerning the laws governing the stability of
masonry arches. This, chapter will be devoted mainly to gravity
dams, those of the arch type being considered only Incidentally,
Arelu\s will 1m discussed fully in Chapter XVI II.
an
312 MASONRY DAMS. [CHAP. XIII,
ART. 1. STABILITY OF GRAVITY DAMS.
481. PRINCIPLES. By the principles of hydrostatics we know
(1) that the pressure of a liquid upon any surface is equal to the
weight of a volume of the liquid whose base is the area of the im-
mersed surface and whose height is the vertical distance of the center
of gravity of that surface below the upper surface of the water ; (2)
that this pressure is always perpendicular to the pressed surface •
.and (3) that, for rectangular surfaces, this pressure may be con-
sidered as a single force applied at a distance below the upper
surface of the liquid equal to f- of the depth.
482. A gravity dam may fail (1) by sliding along a horizontal
joint, or (2) by overturning about the front of a horizontal joint,
or (3) by crushing the masonry, particularly at the front of
any horizontal joint. However, it is admitted that by far the
greater number of failures of dams is due to defects in the founda-
tion. The method of securing a firm foundation has already been
discussed in Part III ; and, hence, this subject will be considered
here only incidentally. There is not much probability that a dam
will fail by sliding forward, but it may fail by overturning or by the
crushing of the masonry. These three methods of failure will' be
considered separately and in the above order.
483. In the discussions of this article it will be necessary to-
consider only a section of the wall included between two vertical
planes— a unit distance apart — perpendicular to the face of the-
wall, and then so arrange this section that it will resist the loads and
pressure put upon it ; that is, it is sufficient,, and more convenient,,
to consider the dam as only a unit, say 1 foot, long.
484. NOMENCLATURE. The following nomenclature will be used
throughout this chapter :
JJ=the horizontal pressure, in pounds, of the water against a,
section of the back of the wall 1 foot long and of a height
equal to the height of the wall.
W= the weight, in pounds, of a section of the wall 1 foot long.
w = the weight, in pounds, of a cubic foot of the masonry.
h = the height, in feet, of the wall ; i. e., li = E F9 Pig. 68.
/ = the length of the base of the cross section; i. e., I = A By
Fig. 68.
t = the width of the wall on top ; L e., t = D E, Fig. 68.
ART. 1.]
STABILITY OF GRAVITY DAMS.
313
5 = the batter of the wall, i. c.9 the inclination of the surface
per foot of rise — V "being used for the butter oE the up-
stream face and 5X for that of the downstream face.
~x = A 0= the distance from the down-stream face of any joint to
the point in which a vertical through the center of gravity
of the wall pierces the plane of the. base.
d = the distance the center of pressure deviates from the center
of the base.
62.5 = the weight, in pounds, of a euhic, foot of water.
485. STABILITY AGAINST SLIDING. The horizontal pressure of
the water tends to slide the dam forward, and m resisted by the
friction dne to the weight of the wall.
486. Sliding Force. The horizontal pressure of the* water
against an elementary section of the wall, by principle (i) of g *181,
is equal to the area of the section multiplied by half the height of
the wall, and that product by the weight of a cubic, unit of water; or
= n x i x i n x cx>.r> = 3
k\
(0
Notice that H is the same whether the. pressed area in inclined or
vertical; that is to say, H is the horizontal component of the, total
pressure on the surface.
487. Resisting Forces. The weight of an elementary section of
the wall is equal to the area of the vertical
cross section multiplied by the weight of a
cubic unit of the masonry. The area of
the cross section, A B ED, Fig. 08, equals
EFX D £+i EFx FB+% I) G X A O
Then the weight of the elementary sec-
tion of the wall is
W = w (ht -(- -|- If V •+- -| Ji* b ) . ('>) •
. • M - \ j ac F
The vertical pressure of the water on Km, «K.
the inclined face increases the prensure on the, foutulation, and,
consequently, adds to the resistance against sliding. The. vertical
pressure on EB is equal to the horizontal projection of that area
multiplied by the distance of the center of gravity of the mirfaoo
below the top of the water and by the weight of a cubic unit of
314 MASOKRY DAMS. [CHUP. XIII.
water, or, the vertical pressure ^FExIX^fiX 62.5 = li ~bf X
%kX 62.5 = 31.25 A8 i'.
488. If the earth rests against the heel of the dam (the bot-
tom of the inside face), it will increase the pressure on the foun-
dation, since earth weighs more than water ; on the other hand, the
horizontal pressure of the earth will be a little greater than that of
an equal height of water. However, since the net resistance with
the earth upon the heel of the wall is greater than with an equal
depth of water, it will be assumed that the water extends to the
bottom of the wall.
If the water finds its way under and around the foundation of
the wall, even in very thin sheets, it will decrease the pressure of
the wall on the foundation, and, consequently, decrease the
stability of the wall. The effective weight of the submerged por-
tion of the wall will be decreased 62|- Ibs. per cu. ft. However, the
assumption that water in hydrostatic condition finds its way under
or into a dam is hardly admissible ; hence the effect of buoyancy
will not be considered.*
489. Co-efficient of Friction. The values of the co-efficient of
friction most frequently required in masonry computations are given
in the table on page 315. There will be frequent reference to this
table in subsequent chapters ; and therefore it is made more full
than is required in this connection. The values have been collected
from the best authorities, and are believed to be fair averages. See
also the table on page 276.
490. Condition for Equilibrium. In order that the wall may
not slide, it is necessary that the product found by multiplying the
co-efficient of friction by the sum of the weight of the wall and the
vertical pressure of the water shall be greater than the horizontal
pressure of the water. That is to say, in order that the dam may
not slide it is necessary that /2 (W-}- 31.25/^6') shall be greater
than H\ or, in mathematical language,
H 31.25 /*«
r<'Wjr 3L25 ^ V ^ w (h t + $• A2 V + i 7^ 5J + 31.25 7^a Z>'
* Since the above was written, Jas. B. Francis presented a paper (May 16,
"before the American Society of Civil Engineers, which seems to show that water
pressure is communicated, almost undiminished, through a layer of Portland cement
mortar (1 part cement and 2 parts sand) 1 foot thick.
1.]
STABILITY OF GRAVITY DAMS.
315
TABLE 36.
C/O-EFFICIENTS OF FKICTION FOR DRY MASONRY.
DESCRIPTION OP THE MASONRY.
CO-EFFICIENT.
Soft limestone on soft limestone, both, well dressed 0.75
Brick-work on brick-work, with, slightly damp mortar 0.75
Hard brick-work on hard brick- worK, with slightly damp mortar . 0 . 70
Point-dressed granite on like granite. r . 0. 70
" " " tl well-dressed granite 0.65
Oommon brick on common brick. 0 . 65
" " " hard limestone 0.65
Hard limestone on hard limestone, with rnoist mortar 0.65
J3eton blocks (pressed) on like beton blocks 0.65
Pine-cut granite on pressed * * " 0 . 60
"Well-dressed granite on well dressed granite , 0.60
Polished limestone on polished limestone 0 . 60
"Well-dressed granite on like granite, with fresh mortar 0.50
Oommon brick on common brick, with wet mortar 0.50
Polished marble on common brick 0.45
Point-dressed granite on gravel 0 . 60
" dry clay t).50
"sand 0.40
" " " moist ; clay 0.33
"Wrought iron on well-dressed limestone 0. 50
" '* hard, well- dressed limestone, wet 0.25
Oak, flatwise, on limestone 0 . 65
" endwise, on limestone 0.40
which reduced becomes
>
62.5 h
_ _
w (2 t + h (V + b,) + 62.5 li V "
. . (4)
The weight of a cubic foot of masonry, w, varies between 125 Ibs.
for concrete or poor brick- work, and 160 Ibs. for granite ashlar.
Dams are usually built of rubble, which weighs about 150 Ibs. per
cu. ft. To simplify the formula, we will assume that the masonry
weighs 125 Ibs. per cu. ft.; i. e.3 that the weight of a cubic foot of
masonry is twice that of water. This assumption is on the safe side,
whatever the kind of masonry.* Making this substitution in (4),
* Increased safety generally requires increased cost of construction, and hence
it is not permissible to use approximate data simply because the error is on the side
toward safety. It will be shown that there is no probability of any dam's failing by
sliding, and that the size, and consequently the volume and cost, are determined by
the dimensions required to prevent crushing and overturning; hence this approxima-
tion involves no increase in the cost.
316 MASONRY DAMS. [CHAP. XHL.
and dropping the term 2 Ji V in the denominator., — since to do so
makes but little difference and is on the safe side, — we have
Other things being the same, the thinner the wall at the top,
the easier it will slide. If the section of the wall is a triangle, i. e.,
if t = 0, then by equation (5) we see that the dam is safe against
sliding when
An examination of the table on page 315 shows that there is no
probability that the co-efficient of friction will be less than 0.5; and
inserting this value of JJL in (6) shows that sliding can not tak'e place
if (V + 5a) > or = 1. To prevent overturning, the sum of the
batters are usually = or > 1 (see Fig. 72, p. 328) ; and, besides, a
considerable thickness at the top (see § 509) is needed to resist the
shock of waves, etc. Hence there is no probability of the dam's
failing by sliding forward. Further, the co-efficient of friction in
the table on page 315 takes no account of the cohesion of the mor-
tar, which may have a possible maximum value, for best Portland
mortar, of 36 tons per sq. ft. (500 Ibs. per sq. in.); and this gives
still greater security. Again, the earth on, and also in front of, the
toe of the wall adds greatly to the resistance against sliding. Fi-
nally, it is customary to build masonry dams of uncoursed rubble
(§§ 213-17), to prevent the bed- joints from becoming channels for
the leakage of water; and hence the stones are thoroughly inter-
locked,— which adds still further resistance. Therefore it is certain
that there is no danger of any masonry dam's failing by sliding for-
ward under the pressure of still water.
491. It has occasionally happened that dams and retaining walls
have been moved bodily forward, sliding on their base; but such an
occurrence is certainly unusual, and is probably the result of the
wall's having been founded on an unstable material, perhaps on an
inclined bed of moist and uncertain soil. In most that was said in
Part III concerning foundations, it was assumed that the founda-
ART. 1.] STABILITY OF GRAVITY DAMS. 317
tion was required to support only a vertical load. When the struct-
ure is subjected also to a lateral pressure, as in dams, additional
means of security are demanded to prevent lateral yielding.
When the foundation rests upon piles a simple expedient is to
drive piles in front of and against the edge of the bed of the founda-
tion; but obviously this is not of much value except when the piles
reach a firmer soil than that on which the foundation directly rests.
If the piles reach a firm subsoil, it will help matters a little if the
upper and more yielding soil is removed from around the top of the
pile, and the place filled with broken stone, etc. Or a wall of piles
may be driven around the foundation at some distance from it, and
timber braces or horizontal buttresses of masonry may be placed at
intervals from the foundation to the piles. A low masonry wall is
sometimes used, instead .of the wall of piles, and connected with the
foot of the main wall by horizontal buttresses, whose feet, on the
counter-wall, are connected by arches in a horizontal plane in order
to distribute the pressure more evenly.
In founding a dam upon bed-rock, the resistance to sliding on
the foundation may be greatly increased by leavin'g the bed rough ;
and, in case the rock quarries out with smooth surfaces, one or more
longitudinal trenches may be excavated in the bed of the foundation,
,and afterwards be filled with the masonry.
In the proposed Quaker Bridge dam the maximum horizontal
thrust of the water is equal to 0.597 of the weight of the masonry.
492. STABILITY AGAINST OVEETTJENING. The horizontal pres-
sure of the water tends to tip the wall forward about the front oi!
any joint, and is resisted by the moment of the weight of the wall.
For the present, it will be assumed that the wall rests upon, a rigid
base, and therefore can fail only by overturning as a whole.
The conditions necessary for stability against overturning can be
completely determined either by considering the moments of the
several forces, or by the principle of resolution of forces. In the
following discussion the conditions will be first determined by mo-
ments, and afterward by resolution of forces.
493. A. BY MOMENTS. The Overturning Moment. The pressure
of the water is perpendicular to the pressed surface. If the water
presses against an inclined face, then the pressure makes the same
angle with the horizontal that the surface does with the vertical.
Since there is a little difficulty in finding the arm of this force, it is
318
MASONRY DAMS.
[CHAP. xiri.
more convenient to deal with the horizontal and vertical components
of the pressure.
The horizontal pressure of the water can be found by equation
(1), page 313. The arm of this force is equal to -J- li (principle 3,
§ 481). Hence the moment tending to overturn'the wall is equal fr-
^\ 31.25 h* =
h*,
(7)
which, for convenience, represent by Ml .
494. The Eesisting Moments. The forces resisting the over-
turning are (1) the weight of the wall and (2) the vertical pressure
of the water on the inclined face.
The weight of the wall can be computed by equation (3), page
313. It acts vertically through the center of gravity of the cross
section. .
The center of gravity can be found algebraically or graphically.
There are several ways in. each case., but
the following graphical solution is the sim-
plest. In Fig. 69, draw the diagonals D B
and A E, and lay off A J = E I\ then
draw D J, and mark the middle of it Q.
The center of gravity, 0, of the area
A B E D is at a distance from Q towards
B equal to -J- Q B. This method is appli-
cable to any four-sided figure.
The position of the center of gravity can
also be found algebraically by the principle
that the moment of the entire mass about
any point, as A, is equal to the' moment of the part A D G, plus
the moment of the portion D E F G, pins the moment of the part
$ ft f? — all about the same point, A. Stating this principle alge-
braically gives
| h b, (i V tj
b,) + i 7i* V (£ li V + t + li V}
(8)
in which x = the distance A 0. Solving (8) gives
_
v + sn + A ». +
+ v
• (9)
ART. 1.] STABILITY OF GRAVITY DAMS. 319
The arm of the weight is A 0 (= x), and therefore the mo-
ment is
WX A C=w[ht + %h*(Z>' + !>>)] x, . . . (10)
which, for convenience, represent by J/~2 .
495. The vertical pressure of the water on the inclined face,
E B, has been computed in § 487, which see. This force acts ver-
tically between ^7and S, at a distance from B equal to -J- F B\ the
arm of this force is A B — \ FB = I — \ h V = lilv + t + f liV .
Therefore, the moment of the vertical pressure on the inclined
face is
31.25 tf V (111, + t + f h V), .... (11)
which, for convenience, represent by M9 . Of course, if the pressed
face is vertical, JIf3 will be equal to zero.
496. The moment to resist overturning is equal to the sum of
(10) and (11) above, or Mz + M2 .
The moment represented by the sum of J/2 and Ms can be deter-
mined directly by considering the pressure of the water as acting
perpendicular to E B at -J- E B from B ; the arm of this force is a
line from A perpendicular to the line of action of the pressure. If
the cross section were known, it would be an easy matter to measure
this arm on a diagram; but, in designing a dam, it is necessary to
know the conditions requisite for stability before the cross section
can be determined, and hence the above method of solution is the
better.
497. Condition for Equilibrium. In order that the wall may
not turn about the front edge of a joint, it is necessary that the
overturning moment, Ml , as found by equation (7), shall be greater
than the sum of the resisting moments, J/2 and Jf3 , as found by
equations (10) and (11); or, in other words, the factor against over-
turning = -^j^ (12)
498. Factor of Safety against Overturning. In computing the
stability against overturning, the vertical pressure of the water
against the inside face is frequently neglected; i.e., it is assumed
that J/g , as above, is zero. This assumption is always on the safe
side. Computed in this way, the factor of safety against overturn-
ing for the proposed Quaker Bridge dam, which when completed
[CHAP. XIII-
MASOSET DAMo
"the world, varies between
be considerably the ^/T^ the vertical component m
and 3.68. l&antz,* ^° ^ f ^ to 5.55 as safe, the larger
L-e serious conse-
Q
- d ag already
against overturning is yff
o,
^
"
M< study of Reservoir Walls:
" Mahan's translation, p. 53.
ART. 1.] STABILITY OP GRAVITY DAMS. 321
sidered. When the reservoir is empty, the pressure tending to
produce crushing is the weight of the dam alone, which pressure is
distributed uniformly over the horizontal area of the wall. When
the reservoir is full, the thrust of the water modifies the distribution
•of the pressure, increasing the pressure at the front of the wall and
•decreasing it at the back. We will now determine the law of the
variation of the pressure.
Let A B, Fig. 71, represent the base of a vertical section of the
dam ; or A B may represent the rect-
angular base (whose width is a unit) of
any two bodies which are pressed against
,-each other by any forces whatever.
If = the resulting moment (about A) of
all the external forces. In the
case of a dam, M= If, — M^ — see
equations (7) and (11).
W = the total normal pressure on A B.
In the case of a dam, W = the weight of the masonry.
P = the maximum pressure, per unit of area, at A.
p = the change in unit pressure, per unit of distance> from A
towards B.
x = any distance from A towards B.
P — p x = the pressure per unit at a distance x from A.
Y = a general expression for a vertical force.
The remainder of the nomenclature is as in § 484, page 312.
Taking moments about A gives
(P -px) dx. x = 0; . . . (13)
pl* = 0 ...... (14)
For equilibrium, the sum of the forces normal to A B must also
be equal to zero ; or
2Y=-W+ r(P-px)dx = 0, . . . (15)
t'o
from which
zw. ...... (16)
322 MASONRY DAMS. [CHAP. XIII.
502. Maximum Pressure. Combining (16) with (14) and re
4ucing, ' _
4^ SWx 6M
r-~~i F^ + T" ...... ( }
[f the stability against overturning be determined algebraically,, i. e.,
by equation (12), then 3/and x are known, and P can be computed
by equation (17).
If the wall is symmetrical x = -J- 1, and (17) becomes
Equation (18) is a more general form of equation (1), page 205,,
since in the latter there is but one external force acting, and that
is horizontal.
W
In equation (18), notice that — is the uniform pressure on A B
ft -»r
due to the weight of the wall ; also that — - is the increase of pres-
i
sure at A due to the tendency to overturn, and that consequently
the uniform pressure at B is decreased a like amount.
503. The maximum pressure may be found also in another way.
Assume that N, Fig. 71, is the center of pressure. Let pl (= B L)
represent the pressure at B, and j0fl (= A L) that at A ; and any
intermediate ordinate of the trapezoid A B L K will represent the
pressure at the corresponding point. Then, since the forces acting
on A B must be in equilibrium for translation, the area of the
trapezoid will represent the entire pressure»on the base A B. Stated
algebraically, this is
^-±^Z= W. . ...... (19)
Also, since the 'forces acting on AB must be in equilibrium for
rotation, the moment of the pressure to the right of N must be-
equal to that to the left ; that is to say, the center of gravity of the
trapezoid A B LJTmust lie in the line NJ. By the principles of
analytical mechanics, the ordinate A N to the center of gravity
ABLKis
(80)
v '
ART. 1.] STABILITY OP GRAVITY DAMC. 323
Solving (19) and (20) gives
4TTr /"> TT7"""""
I/I/ r\ I/I/ />«
*; 11 ___ u yy x (21)
If the wall is a right-angled triangle with the right angle at Af
x = -g-Z, which, substituted in the above expression, shows that the?
2 W
pressure at A is — — , and also that the pressure at B is zero, — all
of which is as it should be. Equation (21) is a perfectly general
expression for the pressure between any two plane surfaces pressed
together ly normal forces. Notice that equation (21) is identical
with the first two terms of the right-hand side of equation (17).
The form of (21) can be changed by substituting for x its value
£ I — d ; then
= W 6 Wd (2<>)
I I*
Equation (22) gives the pressure at A due to the weight of the
wall ; but it will also give the maximum pressure on the base due
to both the vertical and the horizontal forces, provided d be taken
as the distance from the middle of the base to the point in which
the resultant of all the forces cuts the base. Therefore we may
write
p=W+6Wd^ (23)
504. Equation (23) is the equivalent of equation (17), page 322.
It is well to notice that equation (23) is limited to rectangular hori-
zontal cross-sections, since it was assumed that the pressure on the
section varies as the distance back from the toe. If the stability
against overturning is determined algebraically, as by equation (12),
then equation (17) is the more convenient ; but if the stability is
determined graphically, as in Fig. 70, then equation (22) is the
2 W
simpler. Notice that if d = -fa I, P = — r— , which is in accordance
l
with what is known in the theory of arches as the principle of the
middle third ; that is, as long as the center of pressure lies within
the middle third of the joint, the maximum pressure is not more
than twice the mean, and there is no tension in any part of the
joint.
324 MASONRY DAMS. [CHAP. XIII.
W
Notice, in equation (23), that -j- is the uniform load on the base;
L
and also that — ^ — is the increase of pressure due to the eccentric-
ity of the load. It is immaterial whether the deviation d is caused
by the form of the wall or by forces tending to produce overturn-
ing.
505. Tension on the Masonry. By an analysis similar to that
above, it can be shown that the decrease in pressure at B, due to
the overturning moment, is equal to the increase at A. If d = ^ /,
then by equation (23) the increase at A and decrease at B is PF,
that is to say, the pressure at A is 2 W and that at B is zero.
Therefore, if the center of pressure departs more than 1 1 from the
center of the base, there will be a minus pressure, /. e. tension, at
B. Under this condition, the triangle A FA"7, in Fig. 71, page
321, represents the total pressure, and the triangle J9 FZ'the total
tension on the masonry, — A Kr being the maximum pressure at A,
and B Lf the maximum tension at B.
If a good quality of cement mortar is used, it is not unreason-
able to count upon a little resistance from tension. As a general
rule, it is more economical to increase the quantity of stone than the
quality of the mortar ; but in dams it is necessary to use a good
mortar to prevent (1) leakage, (2) disintegration on the water side,
and (3) crushing. If the resistance due to tension is not included
in the computation, it is an increment to the computed margin of
safety.
506. If the masonry be considered as incapable of resisting by
tension, then when d in equation (23) exceeds -J I the total pres-
sure will be borne on A V; Fig. 71. In this case A N' (the distance
from A to the point where the resultant pierces the base) will be
less than $ L The area of the triangle A V K' ~\AK' x A V =
-J- P X 3 A N'. Since it is assumed that the portion VB is inca-
pable of resisting by tension, the entire weight will be borne by A V;
and therefore the area of A V K' will represent the total weight W.
Hence iP xZAN' = W, or
2 W 2W
~~
To illustrate the difference between equations (23) and (24),
ART. 1.] STABILITY OF GRAVITY DAMS. 325
assume that the distance from the resultant to the center of the base
is one quarter of the length of the base, i. e.y assume that d = %L
Then, by equation (23), the maximum pressure at A is
W fi W7 W
° vv l ^
and by equation (24) it is
2 W
That is to say, if the masonry is capable of resisting tension, equa-
tion (25) shows that the maximum pressure is 2-J- times the pressure
due to the weight alone ; and if the masonry is incapable of resist-
ing tension, equation (26) shows that the maximum pressure is 2|
times the pressure due to the weight alone.
Notice that equation (24) is not applicable when d is less than
\l ] in that case, equation (23) must be used.
507. Limiting Pressure. As a preliminary to the actual design-
ing of the section, it is necessary to fix upon the maximum pressure
per square foot to which it is proposed to subject the masonry. Of
course, the allowable pressure depends upon the quality of the
masonry, and also upon the conditions assumed in making the com-
putations. It appears to be the custom, in practical computations,
to neglect the vertical pressure on the inside face of the dam, i. e.}
to assume that J/3 , equation (11), page 319, is zero ; this assumption
is always on the safe side, and makes the maximum pressure oh the
outside toe appear greater than it really is. Computed in this way,
the maximum pressure on rubble masonry in cement mortar in
some of the great dams of the world is from 11 to 14 tons per sq.
ft. The proposed Quaker Bridge dam is designed for a maximum
pressure of 16.6 tons per sq. ft. on massive rubble in Portland
cement mortar.
For data on the strength of stone and brick masonry, see §§
221-23 and §§ 246-48, respectively.
508. The actual pressure at the toe will probably be less than
that computed as above. It was assumed that the weight of the
wall was uniformly distributed over the base ; but if the batter is
considerable, it is probable that the pressure clue to the weight of
the wall will not vary uniformly from one side of the base to the
326 MASOKRY DAMS. [CHAP. XIII.
other, but will be greater on the central portions. The actual
maximum will, therefore, probably occur at some distance back
from the toe. Neither the actual maximum nor the point at which
v it occurs can be determined.
Professor Eankine claims that the limiting pressure for the out-
side toe should be less than for the inside toe. Notice that the
preceding method determines the maximum vertical pressure.
When the maximum pressure on the inside toe occurs, the only
force acting is the vertical pressure ; but when the maximum on
the outside occurs, the thrust of the water also is acting, and there-
fore the actual pressure is the resultant of the two. With the pres-
ent state of our knowledge, we can not determine the effect of a
horizontal component upon the vertical resistance of a block of stone,
but it must weaken it somewhat.
AET. 2. OUTLINES OF THE DESIGN.
509. WIDTH ON TOP. As far as the forces already considered
are concerned, the width of the wall at the top might be nothing,
since at this point there is neither a pressure of water nor any
weight of masonry. But in practice we must consider the shock of
waves and ice, which in certain cases may acquire great force and
prove very destructive to the upper portion of the dam. This force
can not be computed, and hence the width on top must be assumed.
This width depends to a certain extent upon the height and length
of the dam. The top of large dams may be used as a roadway.
Krantz* says that it is "scarcely possible to reduce the top width
below 2 metres (6.5 ft.) for small ponds, nor necessary to make it
more than 5 metres (16.4 ft.) for the largest."
Pig. 72, page 328, gives the width on top of Krantz's profile type,
and also of the profile recommended by the engineers of the
Aqueduct Commission for the proposed Quaker Bridge dam.
510. THE PEOFILE. In designing the vertical cross section of a
gravity dam to resist still water, it is necessary to fulfill three con-
ditions : (1) To prevent sliding forward, equation (4), page 315,
must be satisfied; (2) to resist overturning, equation (12), page 319,
must be satisfied ; and (3) to resist crushing, equation (23), page
323, or (24), page 324, must be satisfied. As these equations really
* " Study of Reservoir Walls," Mahan's translation, p. 35.
ART. 2.] OUTLINES OF THE DESIGN. 327
involve only three variables, vix. : A, /;,, and b',— the height of the
Khun anil the bat tor of the two faces,— they ('an be satisfied 'exactly.
It has been shown that there is no danger of the dam's sliding Tor-
ward even if the width on top is zero ; and hence there are practi-
cally but two conditions to be fulfilled and two variables to bo
determined. To prevent overturning when the reservoir is full,
•equation (12) must be satisfied ; and to prevent crushing, equation
(23)— -or (-24)— must bo satisfied for the point J (Figs. <ii), 70, etc.)
when the reservoir is full, and for // when the reservoir is empty.
Although it is possible to satisfy these conditions exactly, the
theoretical profile can ho obtained only by successive approxima-
tions. Thin is done by dividing the profile into elementary hori-
zontal layers., beginning at the top, and determining the dimension
of the huso of each layer separately. The theoretical width at the
top being xcro and the actual width being considerable., a portion of
the section at the top of the dam will bo rectangular. A lay or being
given, and the profile of the portion above it being known, certain
dimensions are assumed for the lower base of the layer ; and the
stabilitv against overturning is then determined by applying equa-
tion (P.*), or by the method of KIg. 70 (page JJ20). The maximum
pressure at A is then found by applying equation (17) or (",';*), after
which the maximum pressure at II when the reservoir is empty
must be determined by applying equation (2U). If the first dimen-
sions do not give results in accordance with the limiting conditions,
others must bo assumed and the computations repeated. A third
approximation will probably rarely bo needed.
It is not necessary to attempt to satisfy those equations precisely,
wince there area number of unknown and unknowable factors, as the
weight of tin* stone1, the quality of the mortar, the character
-of the foundation, the quality of the masonry, the hydrostatic
pressure, under the mass, the amount of clastic, yielding, the
force of the \vavo« and of the ice, etc.., which have more to do
with the ultimate1 stability of a dam than the mathematically exact
profile. It is therefore sufficient to assume a trial profile, luring
guided in this by the matters re f erred to in >$ Ml and ^ 512, and
test it at a few points by applying the preceding equations ; a few
modifications to more nearly satisfy tins mathematical conditions or
to simplify the profile is as far an it in wise to carry the theoretical
determination of the profile.
328
MASOXBY DAMS,
[CHAP." xiir.
511. Krantz's Study of Eeservoir Walls, translated from the
French by Capt. F. A. Mahan, TJ. S. A., gives the theoretical pro-
files for darns from 16.40 ft. (5 metres) to 164 ft. (50 metres) high.
The faces are arcs of circles. The mathematical work of determin-
ing the profiles is not given ; but it is evident that the polygonal
profile was deduced as above described,, and that an arc of a circle-
was then drawn to average the irregularities. The largest of these
profiles is shown in Fig. 72 by the broken line. The others are
simply the upper portion of the largest, with the thickness and the
height of the portion above the water decreased somewhat and the
radius of the faces modified correspondingly.
The larger profile of Fig. 72 is that recommended by the engi-
neers of the Aqueduct Commission for the proposed Quaker Bridge
dam. The profiles of most of the high masonry dams of the world
ART. 2.] OUTLINES OF THE DESIGN. 329
are exceedingly extravagant, and hence it is not worth while to give
examples.
512. Prof. Win. Cain has shown* that the equations of condi-
tion are nearly satisfied by a cross section composed of two tra-
pezoids, the lower and larger of which is the lower part of a triangle
having its base on the foundation of the dani and its apex at the
surface of the water,, and the upper trapezoid having for its top the
predetermined width of the dam on top (§ 509), and for its sides
nearly vertical lines which intersect the sides of the lower trapezoid.
The width of the dam at the bottom is obtained by applying the
equations of condition as above. The relative batter of the up-
stream and down-stream faces depends upon the relative factors
of safety for crushing and overturning. This section gives a
factor of safety which increases from bottom to top, — an important
feature.
513. THE PLAN. If the wall is to bo one side of a rectangular
reservoir, all the vertical sections will be alike ; and therefore the
heel, the toe, and the crest will all be straight. If the wall is to be
a dam across a narrow valley, the height of the masonry, and conse-
quently its thickness at the bottom, will be greater at the center
than at the sides. In this case the several vertical cross sections
may be placed so that (1) the crest will be straight, or (2) so that
the heel will be straight in plan, or (3) so that the toe will be
straight in plan. Since the up-stream face of the theoretical pro-
file is nearly vertical (see Pig. 72), there will be very little difference
in the form of the dam whether the several cross sections are
placed in the first or the second position as above. If the crest is
straight, the heel, in plan, will be nearly so ; if the crest is straight,
the toe, in plan, will be the arc of a circle such that the middle
ordinate to a chord equal to the span (length of the crest) will be
equal to the maximum thickness of the dam ; and if the toe is
made straight, the crest will become a circle of the same radius.
This shows that strictly speaking it is impossible to have a straight
gravity dam across a valley, since either the crest or toe must be
curved. The question then arises as to the relative merits of these
two forms.
514. Straight Crest vs. Straight Toe. The amount of masonry
* Engineering News, vol. xix. pp. 512-13.
330 MASONBY DAMS. [CHAP. XIII.
in the two forms is the same, since the vertical sections at all points
are alike in both.*
The stability of the two forms, considered only as gravity dams,
is the same, since the cross sections at like distances from the center
are the same.
The form with a curved crest and straight toe will have a slight
advantage due to its possible action as an arch. However, it is not
necessary to discuss further the relative advantages of these two
types, since it will presently be shown that both the toe and the crest
of a gravity dam should be curved.
515. Gravity vs. Arch Dams. A dam of the pure gravity type
is one in which the sole reliance for stability is tli3 weight of the
masonry. A dam of the pure arch type is one relying solely upon
the arched form for stability. With the arched dam, the pressure
of the water is transmitted laterally through the horizontal sections
to the abutments (side hills). The thickness of the masonry is so
small that the resultant of the horizontal pressure of the water and
the weight of the masonry passes outside of the toe ; and hence,
considered only as a gravity dam, is in a state of unstable equilib-
rium. If such a dani fails, it will probably be by the crushing
of the masonry at the ends of the horizontal arches. In the
present state of our knowledge concerning the elastic yielding of
masonry, we can not determine, with any considerable degree of
accuracy, the distribution of the pressure over the cross section of
the arch (see Art. 1, Chap. XVIII).
If it were not for the incompleteness -of our knowledge of the
laws governing the stability of masonry arches, the arch dam would
doubtless be the best type form, since it requires less masonry for
any particular case than the pure gravity form. The best infor-
mation we have in regard to the stability of masonry arches is de-
rived from experience. The largest vertical masonry arch in the
world has a span of only 220 feet. There are but two dams of the
pure arch type in the world, viz. : the Zola f in France and the
* If the valley across which the dam is built has any considerable longitudinal slope,
as it usually will have, there will be a slight difference according to the relative posi-
tion of the two forms. If two ends remain at the same place, the straight toe throws
the dam farther up the valley, makes the base higher, and consequently slightly de-
creases the amount of masonry.
t Tor description, see Report on Quaker Bridge Dam, Engineering News, vol. xix.
p. 6 ct seq.
ART. 2.] OUTLINES OP THE DESIGN. 331
Eear Valley* in Southern California. The length of the former is
'205 feet on top, height 122 feet, and radius 158 feet; the length
of the latter is 230 feet on top, height 64 feet, radius of top
335 feet and of the "bottom 226 feet. The experience with large
arches is so limited (see Table 63, page 502), as to render it un-
wise to make the stability of a dam depend wholly upon its action
as an arch, except under the most favorable conditions as to rigid
side-hills and also under the most unfavorable conditions as to cost
of masonry. Notice that with a dam of the pure arch type, the
failure of one part is liable to cause the failure of the whole ; while
with a gravity section, there is 'much less danger of this. Further,
since the average pressure on the end arch stones increases with the
span, the arch form is most suitable for short dams.
516. Curved Gravity Dams. Although it is not generally wise
to make the stability of a dam depend entirely upon its action as
an arch, a gravity dam should be built in the form of an arch, i. e.y
with both crest and toe curved, and thus secure some of the advan-
tages of the arch type. The vertical cross section should be so pro-
portioned as to resist the water pressure by the weight of the
masonry alone, and then any arch-like action will give an addi-
tional margin for safety. If the section is proportioned to resist
by its weight alone, arch action can take place only by the elastic
yielding of the masonry under the water pressure ; but it is known
that masonry will yield somewhat, and that therefore there will be
some arch action in a curved gravity dam. Since but little is known
about the elasticity of stone, brick, and mortar (see § 16), and noth-
ing at all about the elasticity of actual masonry, it is impossible
to determine the amount of arch action, i. e., the amount of pres-
sure that is transmitted laterally to the abutments (side-hills).
That it is possible for a dam to act as an arch and a gravity dam
at the same time is shown as follows : <( Conceive a dam of the
pure arch type, of thin rectangular cross section so as to have no
appreciable gravity stability. Conceive the dam to be made up of
successive horizontal arches with key-stones vertically over each
other. The thrust in each arch will increase with the depth, but
the spans will, under the ordinary practical conditions, decrease
with the depth, so that the tendency to e settle at the crown ' (move
horizontally) will be approximately equal in each. If now we adopt
* For description, see Engineering News, vol. xx. pp. 513-15.
332 MASONRY DAMS. [CHAP. XIII.
a triangular in place of a rectangular cross section, we increase the
areas and decrease the unit pressures from arch-thrust as we go-
down, and hence decrease compression and consequent horizontal
' settlement ' of the arches ; in other words, we introduce a tendency
in the water face of the dam to rotate about its lower edge. But
this is precisely the tendency which results from the elastic action
of the mass in respect to gravity stability, which latter we have at
the same time introduced by adopting the gravity section. Hence
the two act in perfect harmony, and there will be a certain size of
triangular section (theoretically, — practically it could not be exact)
at which precisely half the stability will be due to arch action and
half to gravity action, each acting without any appreciable conflict
or interference with the other. "*
517. In addition to the increased stability of a curved gravity
dam due to arch action, the curved form has another advantage.
The pressure of the water on the back of the arch is everywhere
perpendicular to the up-stream face, and can be decomposed into
two components — one perpendicular to the chord (the span) of the
arch, and the other parallel to the chord of the arc. The first
component is resisted by the gravity and arch stability of the dam,
and the second throws the entire up-stream face into compression.
The aggregate of this lateral pressure is equal to the water pressure
on the projection of the up-stream face on a vertical plane perpen-
dicular to the span of the dam. This pressure has a tendency to
close all vertical cracks and to consolidate the masonry transversely,
— which effect is very desirable, as the vertical joints are always less
perfectly filled than the horizontal ones. This pressure also pre-
pares the dam to act as an arch earlier than it would otherwise do,
and hence makes available a larger amount of stability duo to arch
action.
The compression due to these lateral components is entirely in-
dependent of the arch action of the dam, since the arch action
would take place if the pressure on the dam were everywhere per-
pendicular to the chord of the arch. Further, it in no way weakens
the dam, since considered as a gravity dam the effect of the thrust
of the water is to relieve the pressure on the back face, and con-
sidered as an arch the maximum pressure occurs at the sides of the
down-stream face.
Editorial in J&ngitwering News, vol. xix. p. 272.
AET. 2.] OUTLINES OF THE DESIGN. 333
The curved dam is a little longer than a straight one, and hence
would cost a little more. The difference in length between, a chord
and its arc is given, to a close degree of approximation, by the formula
in which a = the length of the arc, c = the length of the chord,
and r = the radius. This shows that the increase in length due to
the arched form is comparatively slight. For example, if the chord
is equal to the radius, the arch is only -£%, or 4 per cent., longer than
the chord. Furthermore, the additional cost is less, proportionally,
than the additional quantity of masonry ; for example, 10 per cent,
additional masonry will add less than 10 per cent, to the cost.
518. Of the twenty-five most important masonry darns in the
world, two are of the pure arch type, sixteen are of the curved
gravity type, and eight are of the straight gravity type. The eight
highest dams are of the curved gravity type.*
519. auALlTY OF THE MASONRY. It is a well settled principle
that any masonry structure which sustains a vertical load should
have no continuous vertical joints. Dams support both a horizontal
and a vertical pressure, and hence neither the vertical nor the hori-
zontal joints should be continuous. This requires that the masonry
shall be broken ashlar (Fig. 39, page 136) or random squared-stone
masonry (Fig. 44, page 137), or un coursed rubble (Fig. 45, page 13 7).
The last is generally employed, particularly for large dams. The
joints on the faces should be as thin as possible, to diminish the
effect of the weather on the mortar and also the cost of repointing.
In ordinary walls much mor£ care is given to filling completely
the horizontal than the vertical ones ; but in dams and reservoir
walls it is important that the vertical joints also shall be completely
filled.
To prevent leakage, it is very important that all spaces between
the stones should be filled completely with good mortar, or better,
with mortar impervioiis to water (see § 141). f If the stone itself is
not impervious, the wall may be made water tight by the lip-
plication of Sylvester's washes (§ 263) to the inside face of the
dam.
* For source of information concerning these dam,?, see § 520 — Bibliography of
Masonry Daos.
334 MASOXKY DAMS. [CHAP. XIII.
520. BIBLIOGKAPHY OF MASONRY BAMS. Design and Constrvc-
tionof Masonry Dams, Ranking (Miscellaneous Scientific Papers,
pp. 550-61.) Study of Reservoir Walls, Krantz, (translated from
the French by Capt. F. A. Mahan, U. S. A.) Profiles of High
Masonry Dams, McMaster, (published in Van Nostrand's Engineer-
ing Magazine and also as No. 6 of Van Nostrand's Science Series. )
Strains in- High Masonry Dams, E. Sherman Gould, (Van
Nostrand's Engineering Magazine, vol. 30., p. 265 et seq.). Histori-
cal and Descriptive Review of Earth and Masonry Dams, with
Plans, David Gravel, (Scientific American Supplement, No. 595
(May 28, 1887), pp. 9496-9500.) Wegmann's Design and Con-
struction of Masonry Dams gives an account of methods em-
ployed in determining the profile of the proposed Quaker Bridge
dam, and also contains illustrations of the high masonry dams
of the world. For a general discussion of high masonry dams,
including a consideration of the best form for the horizontal
cross section, a full description of the proposed Quaker Bridge
dam and a comparison of it with other great dams, and many
valuable points concerning practical details, see numerous re-
ports, correspondence, and editorials in Engineering News, Jan-
uary to June, 1888 (vol. 19). The above articles contain many
references to the literature, mostly French, of high masonry dams.
ART. 3. EOCK FILL DAMS.
521. There are three well-known types of dams, which have
been in use from time immemorial : earth bank, timber crib-work,
and masonry. Recent engineering practice on the Pacific coast has
introduced another type, viz.: the Rook Fill Dam, which is of too
much importance to pass by without a mention here, although
strictly it can not be classed as masonry construction.
A rock fill dam consists of an embankment of irregular stones
thrown in loosely, except that sometimes the faces are laid by hand.
If the overflow is to discharge over the crest, the largest stones
should be placed on the down-stream slope. The dam may be made
practically water tight (1) by filling the voids with smaller stones,
gravel, sand, and earth, or (2) by placing any desired thickness of
earth and puddle on the up-stream face, or (3) by covering the
water slope with one or more thicknesses of planking, which is calked
and sometimes also pointed. Either the first or second method
ART. 2.] OUTLINES OE THE DESIGN". 335
would make a dam practically water tight from the beginning., and
it would grow tighter with age ; the third method, if carefully exe-
cuted, would make the dam absolutely water tight at the beginning,
but would decay, since the upper part of the sheeting would ordi-
narily be alternately wet and dry.
A great number of rock fill dams have been built on the Pacific
slope in the past few years, for mining and irrigating purposes. A
dam of this character has recently been completed on the Hassa-
yampa River in Arizona, of the following dimensions : " Height,
110 ft.; base, 135 ft.; top width, 10ft.; length on top, 400 ft.;
water slope, 20 ft. horizontal to 47 ft. vertical Q- to 1); back slopes,
70 ft. horizontal to 180 ft. vertical (f to 1); contents, 46,000 cu. yds.;
cost, by contract, $2.40 per cu. yd." * It is proposed to build a dam
of this character in California 250 feet high, which is about 80 feet
higher than any existing masonry dam, and practically is nearly the
same amount higher than the proposed Quaker Bridge dam
(Fig. 72, page 328).
522. ' '" Earth dams are good and useful when only still water not
running over the crest is to be dealt with. Counting reservoir walls
as dams, which they are, earth dams are vastly more used than any
other. They must be made with the greatest care, and, if of any
considerable height, an inner wall of puddle is necessary to their
integrity. They must be carried down to firm and impervious sub-
soil of some kind, or they are worthless. Any considerable leak is
at once fatal to them ; and they are also subject to serious injury
from muskrats, crabs, etc. Nevertheless, many earth dams of
great age and great height exist, and bid fair to exist for ages,
showing that it is entirely possible to make them secure."
Stone-filled timber cribs have been very much used for dams ;
but such structures are sure to rot in time, since the timber can not
always be kept wet. It seems probable that in most instances where
cribs have been used a rock-fill dam would have been better,
cheaper, and more durable.
Masonry dams of all sizes, proportions, and ages exist in great
abundance, and the entire suitability of masonry for the construction
of dams is well established. This class of dams is to be preferred
where large quantities of stone are not near at hand, or where leak-
age is undesirable because of loss of water or of injury to land be*
* Engineering News, vol. xx. p. 232.
336 MASONRY DAMS. [CHAP. XIIL
low,, or where space is valuable,, or where the surroundings require
a darn of good appearance.
523. ci These three types afford an adequate choice for nearly all
requirements, but it is obvious that they are open to certain com-
mon objections from which the fourth type — a rock-fill dam — is
free. They are all comparatively costly ; they require a good deal
of labor, and much of it skilled and faithful labor, for their con-
struction ; they can only with great inconvenience be constructed
with water around them, which for the most part must be kept away
by costly coffer-dams or diversions of channels ; above all, a leak is
.always a source of danger, and is apt to be destructive. They are
.all of them, as it were, during all their existence, in unstable
equilibrium — all right so long as the balance of forces remains un-
disturbed, and seriously endangered by a variety of causes which
may disturb it. On the other hand a rock-fill dam is by the very
process of its construction, if conducted with reasonable judgment,
a structure which tends to improve with time, and which can not
be injured but may be benefited by causes which threaten the
other and more artificial types ; in other -words, it is a structure
which may not be very tight, but which is in stable equilibrium as
respects all disturbing causes, being improved and never injured by
them.
" A rock-fill dam is appropriate where the bed on which it rests
is either rock, hard-pan, stiff clay, or some other impervious and
almost unwashable material. The bed may be more or less over-
laid with gravel or loose material without harm, if it be possible
to remove the loose material in advance, and if there be current
enough to remove it from under the foot of the dam, as the work
of construction progresses, it will not even involve extra expense or
delay, and the dam may be begun on top of the stratum without
apparent regard to it ; but whenever there is any considerable
stratum of loose material, a rock-fill dam can only be built by back-
ing it with earth or puddle as a timber dam would be, and the
necessity of providing a proper apron to receive the overflow may
make a timber or crib dam the more economical. It is obvious
that the place of all places for the proper use of such a rock-fill
dam is where leakage is of no importance, either from the loss of
water or from in jury- to land below; where skilled labor is scarce
and costly, and simplicity of work rather than aggregate quantities
ART. 2.] OUTLINES OF THE DESIGN. 337
the important consideration ; where good materials for masonry are
.scarce or absent ; and where the surroundings do not demand at-
tention to the question of appearance/' *
The greatest economy in this form of dam occurs when the fill
is made in water ; and it is particularly advantageous in the canali-
zation of rivers, i. e., in forming pools in rivers for the benefit of
.navigation. It has been proposed to use rock-fill dams exclusively
in the construction of the Nicaragua canal.
524. In California the cost of this class of dams varies from $2
to $3 per cubic yard, including all accessories,, which is said to be
about 50 per cent, cheaper than for earth dams of equal area of
transverse cross section.
* Editorial in ^ngineenng News, vol. xx. p. 70.
CHAPTEE XIV.
RETAINING WALLS.
525. DEFINITIONS. Retaining wall is a wall of masonry for
sustaining the pressure of earth deposited behind it after it is built.
Face wall, or slope wall, is a species of retaining wall built
against the face of earth in its undisturbed and natural position.
Obviously it is much less important and involves less difficulties-
than a true retaining wall.
Buttresses are projections in the front of the wall to strengthen
it. They are not often used., on account of their unsightliness, ex-
cept as a remedy when a wall is seen to be failing.
Counterforts are projections at the rear of the wall to increase
its strength. They are of doubtful economy, and were much more
frequently used formerly than now.
Land-ties are long iron rods which connect the face of the wall
with a mass of masonry, a large iron plate, or a large wooden post
bedded in the earth behind the wall, to give additional resistance to-
overturning.
Surcharge. If the material to be supported slopes up and back,
from the top of the wall, the earth above the top is called the sur-
charge.
Among military men, a retaining wall is called a revetment.
When the earth is level with the top, a scarp revetment; when above-
it," a counterscarp revetment, or a clem i-revetment ; when the face-
of the wall is battered, a sloping revetment ; when the back is bat-
tered, a counter ^loping revetment. The batter is called the tains.
Retaining walls are frequently employed in railroad work, on
canals, about harbors, etc. ; and the principles involved in their
construction have more or less direct application in arches, in tun-
neling and mining, in timbering of shafts, and in the excavation of
deep trenches for sewers, etc., and in military engineering.
526. METHOD OF FAILTTKE. A retaining wall may fail (1) by
revolving about the front of any horizontal joint, or (2) by sliding
on the plane of any horizontal joint, or (3) by the bulging of the
body of the masonry. The first is much the most frequent mode of
DIFFICULTIES. 339
failure, and the second is the least frequent. The wall can not fail
by the center's bulging out, unless some force acts to keep the top
from moving forward,— as in a cellar wall, the abutments of arches,
etc,
527. DIFFICULTIES. In the discussion of the stability of dams,
it was shown that in order to completely determine the effect of the
thrust of the water against the wall, it is necessary to know (1)
the amount of the pressure,, (.^) its point of application, and (3)
the direction of its lino of action. Similarly, to determine the
eiTect of the. thrust of a bank of earth against a wall, it is necessary
to know (1) the amount of t lie pressure, (2) its point of application,
and (,'J) its lino of action. The determination of these three quan-
tities requires three equations. The resistance of the wall both to
sliding and to overturning can be found with sufficient accuracy,, as
has already been explained in Chapter XIII— Dams;— but the
other (dements of the problem are,, in the present state of our
knowledge, indeterminate.
The origin of the difliciillies may be explained briefly as follows.
A // represents a retaining wall ; A I) is the sur-
face of the ground. The earth has a tendency to
break a\\*av and conic down some line as ('!.!). The
force tending to bring the earth down is its weight;
tin* forces tending to keep it from coining down are
the friction and cohesion along the line (> I). The
pressure against the wall depends upon the form of B C
the line r />. If the- constants of weight, friction, Fia. 78.
and cohesion of any particular ground were known, the form of (JD
and U!HO the amount of the thrust on the wall, could bo determined.
Notwithstanding the fact that, since the earliest ages constructors
have known by practical experience that a mass of earthwork
will exert a severe lateral pressure, upon a wall or other retaining
structure, there in probably no other subject connected with the
constructor's art. in which there exists the same lack of exact ex-
perimental data. This lack is doubtless due, in part at least, to a
reliance upon theoretical investigations. Of course, mathematical
investigations unsupported by experiments or experience are a very
uncertain guide.
This subject, will bo discussed further under the heads (1)
Theoretical 'Formulas, and (2) Empirical Eules.
340 RETAINING- WALLS. [CHAP. XIY.
ART. 1. THEORETICAL FORMULAS.
528 A great variety of theories have been presented, but all rest
upon an uncertain foundation of assumption, and all are more or
less defective and self-contradictory. The theories of the stability
of retaining walls in most frequent use will now be stated, and the
underlying assumptions and the defects of each will be pointed out.
529. FIRST ASSUMPTION. All theories assume that the surface
of rupture, C D, Fig. 73, is a plane. This is equivalent to assum-
ing that the soil is devoid of cohesion, and is inelastic and homo-
geneous, and also that if a mass of such material be sustained by a
wall, there is a certain plane, called the plane of rupture, along
which the particles are in equilibrium, i. e., are just on the point of
moving. This assumption would be nearly correct in the case of
clean, sharp sand, but would be considerably in error with a tough,
tenacious soil.
This assumption gives the data by which the amount of the
thrust of the earth can be computed; that is to say, this assumption
furnishes the conditions from which one of the equations may be
established.
530. SECOND ASSUMPTION. A second assumption which is always
made is that the point of application of the lateral pressure of the
earth is one third of the height of the wall from the bottom. The
total pressure on the wall varies as some function of the height ;
and it is assumed to vary as the square of the height, and that
therefore the center of pressure is at a point two thirds of the
depth below the top. This is equivalent to assuming that the varia-
tion of the pressure in a mass of earth is the same as in a liquid,
t. e., that the material is devoid .of internal friction.
This assumption furnishes the second of the equations required
to determine the effect of the thrust of earth against a retaining
wall.
531. THIRD ASSUMPTION. The third equation is obtained by
assuming the direction of the pressure. There are different theories
based on different assumptions as to this direction. The theories
also differ because of the difference in the methods of deducing an
equation from the second assumption. The principal theories will
now be considered briefly.
ART. 1.]
THEORETICAL FORMULAS.
341
532. COULOMB'S THEORY. The theory advanced by Coulomb In
1784 \viis the first to even approximate the actual conditions, and
his method is the basis of nearly all formulas used by engineers at
the present time. It has been taken up and followed out to its
consequences by Prony (IHOri), Mayniel (1808), l<Yan<;aiso (1820),
.Navier (1820), Audoy and Poncelet (1840), 1 1 agon (I8f>;>), Hehetllcr
(isr>7), and Moseley, as well as a host of others, in recent times.
Coulomb (ixxitnied (1) that the line I) (!, Fig. 71* (page MO), is
a straight line, down which the prism A (J I) tends to slide; (M) that
the resultant pressure is applied at a point two thirds of the depth
below the top; and (ll) that the pressure exerted by this mass on the
wall is normal to its back face, which is equivalent to neglecting the
friction of the earth against the back of the wall, lie decomposed the
weight, II', of the prism A (J I), Kig.74,and the
reaction, A\ of the wall into t\vo components
respectively, parallel and perpendicular to the
surface of rupture, I) ('. The difference of
these parallel components, /\ — /'^ , he placed
equal to the prism's resistance to sliding; and
assumed the latter to he equal to// A",, in which
// is the : co-cnicient of friction. There is some prism, A (? D9 tho
pressure of which against the wall in just- sufficient to cause x/H/inff.
The amount of this pressure will depend upon the weight, /r, of a
unit of volume of the backing; upon the height,//, of tho wall;
upon the* co-eilicicnt of friction, //, of earth on earth; and upon tho
distance A A which call ;r.
Under the conditions assumed, it in possible* to state a value of
H in terms of //, //», //, and ,r. Coulomb assumed A* to vary an #_,
and differentiated the value of !\ to find the position of the surface
of rupture, I) (\ fora maximum pressure on the wall. This leads
to the1 simple conclusion that the lateral pressure exerted by a hank
of earth with u/tnriwu/tt/ tup is simply that due to the wedge-shaped
mass included between the vertical back of the wall and a Hue bi-
secting the angle between the vertical and the. slope* of repose of the
material;* that is, tin* pressure of the earth against tho wall A />,
FKJ. 74.
* For an al&cchniic tlrtnnnHtratloii, wi* Most'Iry^ Mwhanh'H of Kn^intMThi^ (Jid
Am<*r. Kd.). PI*- '^:* Hi; foru^rupiiicnl doinoriHtrntitm, HIM" Van NnHtrutui'H Knginuor-
in$ Mapi/,in<% vol. ix. j». *JO*J, and v«»I. xxii. jn y<J7.
342 RETAINING WALLS. [CHAP. XIV.
Kg. 74, is equal to the pressure of the prism A C E sliding along a
perfectly smooth plane C E, which bisects the angle of repose, A CD.
JSTo satisfactory proof has been given of the correctness of this
procedure by either Coulomb or any one else; and no defense has
ever been made against a number of serious objections to
it which have been raised. Experiments show that the
lateral pressure of the prism A B Cs Fig. 75. between two
boards A B and A C, against A B, "is quite as much when
the board A 0 is at the slope of repose, 14- to 1, as when it
js a£ kgji £]ie angie. an(| there was hardly any difference
whether the board was horizontal, or at a slope of J to 1, or at
any intermediate slope. "*
533. By this theory the pressure of the wedge A CD (Fig.
74) is
P = £ w 1? tan2 \A CD, ..... (1)
in which w is the weight of a unit of the material to be supported,
and h is the height of the wall. This thrust is assumed to act two
thirds of A C, Fig. 74, below A. Or, in other words, the thrust of
the prism is equivalent to the pressure of a liquid whose weight per
unit of volume is w tan2 -J A CD.
Equating the moment of the overturning force and the moments
of resistance in terms of the unknown thickness, and solving the
equation, gives the thickness which the wall must have to be on the
point of overturning. For example, assume that it is desired to
determine the thickness, t, of a vertical rectangular wall. Repre-
sent the weight of a cubic foot of the masonry by W. Then placing
the moment of the wall equal to the amount of the thrust of the
earth, gives
.$t = P.$7i ....... (2)
Solving equations (1) and (2) gives
* Benj. Baker, an eminent English engineer, in a very interesting and instructive
article on " The Actual Lateral Pressure of Earthwork," reprinted in Van Nostrand's
Engineering Magazine, vol. xxv. pp. 333-42, 353-71, and 492-505, from Proc. of the
Inst. of C. E.
ART. l.j THEORETICAL FORMULAS. 343
Numerous bibles have been computed which give, to a great
number of decimal places, the thickness of a rectangular wall in
terms of its height, the arguments being the ratio of the weights of
a unit of volume of the wall and backing,, and the angle of repose.
•Such tables are of but little- practical value, as will appear presently.
534. Surcharged Walls. The rule that the plane of rupture
bisects the angle between the natural slope of the earth and the back
•of the wall, holds good only when the top surface of the bank is
horizontal and the back of the wall vertical. The formula for a
surcharged wall, or for the case in which the back is not vertical,
or for both combined, may bo deduced * in the same general way as
above; but the results for each case are too complicated for ordinary
uso, and each is subject to the same errors as the formula for a ver-
tical wall and level top surface. There arc* a number of exceedingly
ingenious graphical solutions of the resulting equations, f
535. Reliability of Coulomb's Theory. It is generally conceded
that, the results obtained by this method have but little practical
value. kk Experiments and practical experience show that walls,
which according (o this theory are on the point of overturning,
possess on the average a factor of safety of about bwo." J One of
the author's students experimented with line shot, which appear to
fulfill the fundamental assumptions of this theory, and found that
tlii' observed resistance was 1.07 times that computed by Coulomb's
formula.^ The uncertainties of the fundamental assumptions and
the quest ionableneHs of some of the mathematical processes are
HuOicient explanation of the difference between tho theory and
practice,
536. WEYBAITCH'S THEOKY. This is the latest one, having being
proposed in 1878. It. was first brought to the attention of American
•engineers by Professor .1. A. Du Bois's translations of Winkler's
** Neue Thcorie dcs Mrddruckes/"11 and Weyrauelfs paper on retain-
ing walls published in ^ Zeitsebrift fiir Baukinule," 1878., Band i.
I left ^, which translation was published in the Journal of the Frank-
* Hee Mo.seley's Meehanien of KiiKimMirintf, pp. 424-130.
f See Van NoKtruniPs KnKineerinK Magazine, vol. ix. p. 204 ; and do., vol. xxv.
p. :*55. For references to elaborate, graphical treatises on retaining walls, soo Du
Bnis'H (Jraphieal Statien, pp. lv- Ivi of Introduction.
* Benj. Bilker In uThe Actual Lateral Pimsuro of Earthwork." iSco foot-note on
pi i«e JM2.
t" See M. KartfUSHoifH Baehelor'H Thesis, University of Illinois.
344
ItETAINING WALLS.
[CHAP. XIY.
lin Institute, vol. cviii. pp. 361-87. The following presentation of
this theory is drawn mainly from that article.
This theory assumes (1) that the surface of rupture is a plane,.
(2) that the point of application of the resultant of the lateral
pressure of the earth is at a point one third of the height of the
wall from the bottom, and (3) that there is no friction between the
earth and the back of the wall. It is claimed that these three are
the only assumptions involved in this theory, and that the direction
of the resultant pressure is deduced from the fundamental rela-
tions necessary for equilibrium under the conditions assumed.
The analysis to establish the equations for the amount and direc-
tion of the thrust of the earth is too long and too complicated to be
attempted here ; consequently, only the final equations will be
given.
Let E = the thrust of earth against
the wall.
w = the weight of a unit of the
earth.
h = the height of the wall.
a = the angle the back of wall
makes with the vertical.
# = the angle which E makes
with the normal to the
back of the wall.
e = the angle of the upper surface with the horizontal.
ft = the angle of the plane of rupture with the vertical.
cf> — the angle of repose with the horizontal.
537. General formulas. For a plane earth-surface, horizontal
or sloping up at any angle, and the back of the wall vertical or
leaning forward at any angle, the general relations are *
r __ |~ cos (0 — a) ~~|2 h* w
[_(n + 1) cos a_\ "2 cos (a + '
in which
n =
cos (A' -|- d) cos (a — e)'
(5)
* See Howe's Retaining Walls for Earth, pp. 46, 47; and also Van NostrancTs-
Engineering Magazine, vol. xxii. pp. 265-77.
T- 1-] THEORETICAL FORMULAS. 345
The value of d required in (5) can be deduced from
tan tf =
A" — cos (2 or — e) + £ cos x> (a — e)' ' '
in which
J^__ JCOS 6 — V COS2 6 — COS" 0
I_ - . ..... ...
538. Horizontal Earth-surface. If the upper surface of the
earth is horizontal, then e = 0, and
w
~ sin (a +~S) ' ~~
and d can be found from
sin 0 sin 2 a
, »
tan o =
- ™ --
1 — sin 0 cos 2 a
If the back of the wall is vertical,, a = 0 ; and equation (9)
gives tf = 0. Therefore
539. Surcharge at the Natural Slope. If the upper surface of
earth has the natural slope, e = <p ; and therefore
- r°os(0-*)T
L cos or J
2 cos
and (J is determined from
, . sin 0 cos (0 — 2 a) x_x
tan d = - - . , . t> - o^-r ....... (12)
1 — sm 0 sin (0 — 2 ar) v 7
If the back of the wall is vertical, a = 0, and d = 0, which
shows that .2? acts parallel to the top surface of the earth. In this
case
E = i cos 0 7^ w ........... (13)
* Compare with equation (1), page 342.
346 RETAI]STIKG WALLS. [CHAP. XXV.
540. The general equations for Weyrauch/s theory, viz., equa-
tions (4), (5), (6), and (7), have not been solved for any special
case, except for e = 0, and e = 0. The reduction is very long and
tedious.
541. The formulas for each of the ahove cases may be solved
graphically,* but the explanations are too long to be given here.
542. Reliability of Weyrauch's Theory. On behalf of this
theory it is claimed f that the only errors in it are those due to the
neglect of the cohesion of the backing, and to assuming that the
surface of rupture is a plane ; and also that " it is free from all the
objections which may be urged against all others, and can be used
with confidence/'' These claims are not supported by the facts.
Weyrauch's theory is unquestionably subject to any errors which
may be involved in the assumptions that the surface of rupture is a
plane (see § 529), and that the point of application of the resultant
pressure of the earth is at two thirds of the height of the wall from
the top (see § 530). Second, the analysis purports to be perfectly
general • J but it is evidently inapplicable to a wall inclined toward
the earth to be supported, since the formulas make the thrust of
the earth increase with the backward inclination of the wall. In
fact the theory makes no difference between a wall leaning forward
and one leaning backward. For a wall inclining at the angle of
repose, it gives a very great lateral pressure — see eqs. (8) and (9).
Third, the mathematical process of determining the position of the
surface of rupture is at least questionable. Fourth, the theory errs
on the safe side, because it neglects a vertical component of the
earth pressure which is independent of friction. §
Weyrauch's theory differs from Coulomb's only in the form of
the results and in the manner of deducing them. ; || and hence is of
no practical value.
543. "Weyrauch's method of deducing the direction of the earth
* See Jour. Frank. Inst, vol. cviii. pp. 380-85 ; Van Nostrand's Engineering
Magazine, vol. xxii. pp. 266-73 ; Howe's Retaining Walls for Earth, pp. 7-12.
t By its author, Prof. Weyrauch, and also by the translator, Prof. Du Bois, — see
Jour. Frank. Inst., vol. cviii. pp. 486-87.
I See Jour. Frank. Inst., vol. cviii. p. 377 ; and also Howe's Retaining Walls for
Earth, p. 2.
§ In proof that such a component exists, see experiments by Siegler in Annales des
Ibnts et Chausses, reprinted in Scientific American Supplement, vol. xxiv, pp. 9724-25.
| Van Nostrand's Engineering Magazine, vol. xxii. pp. 265-77.
1.] THEORETICAL FORMULAS.
pressure assumes that there is no friction "between the earth and the
"back of the wall, or, in other words, that the angle, £, which the
thrust of the earth makes with the back of the wall, does not de-
pend upon the structure of the wall for its value. The formula in
this form fails to agree with ordinary experience ; and hence it
has boon proposed* to modify the general formula by considering
that the angle between the resultant pressure of the earth and the
back of the wall is never less than the angle of friction between the
•Oiirth and the wall The method of doing this is as follows :
If <// represents the co-efficient of friction between the earth
jmd the wall, then the direction of .Z/7must make an angle with the
normal to the back face of the wall equal at least to <//. To intro-
<luee <// into Professor Weyrauch's theory, it is necessary to find the
value of $ as given by his formula, and see if it is greater or less than
456'. If it is less, use the value of 0' to determine the direction of
1$ \ if greater, use the value of <S" and omit c// altogether. The
value of <// can not he determined accurately ; but unless the back
of the wall in exceedingly smooth, <// will be greater than <p. If
the back of the wall iw rough rubble (§ 213) or is stepped, <// will be
considerably larger than 0. If the friction between the earth and
the wall l)o neglected, i. e., if it is* assumed that <// = 0, then when
rough nibble retaining walls are proportioned according to Wey-
ninch's theory, they will have a factor of safety considerably larger
than appears from the computations.
This modification Ls inconsistent with the general theory, since
the fundamental equations wore established for that value of $ which
would produces equilibrium, and the corresponding value of the
thrust was (led need jiooonlingly. It is certainly incorrect to use one
direction in determining the value of the thrust and another in
applying it. 'Further, it is not reasonable to believe that the thrust
<»ver makes an angle with, the normal to the back of the wall
greater than the angle oE friction, since one of the fundamental
Conditions of statics is that if the resultant pressure makes an angle
with the normal greater than, the angle of repose, motion takes
pluc.c. This modification of 'Weyniuch's theory purports to give the
relations fora state of equilibrium, and yet violates the fundamental
condition necessary for equilibrium. Neither the original theory
nor the above modification of it is of any practical value.
# By Prof. Cain in Van N"o8tmn<PH Engineering Magazine, vol. xxv. p. 92.
348 RETAINING WALLS. [CHAP. XIV.
544. KANKINE'S THEORY. There is another class of theories,
which, in addition to the assumptions of § 530 and § 531, assume
that the thrust of the earth makes an angle with the back of the
wall equal to the angle of repose of the earth. Different writers
arrive at their results in different ways, but most of them, proceed
from a consideration of the conditions of equilibrium of the earth
particles, and arrive at their results by integration. Of the formulas-
deduced in the latter way, Bankine's * are the best known. All the
theories of this class have essentially the same limitations and de-
fects as Coulomb's and Weyrauch's.
545. APPLICABILITY or THEORETICAL FORMULAS. It is generally
conceded that the ordinary theories — Coulomb's, Weyrauch's, and
Kankine's, — types of the only ones for which there is any consider-
able show of reasonableness, — are safe ; but f ' to assume upon theo-
retical grounds a lateral thrust which practice shows to be excessive,
and then compensate for it by giving no factor of safety to the wall,
although the common way, is not a scientific mode of procedure."'
This is only another reason for the statement, already made, that
theoretical investigations are of but little value in designing re-
taining walls. The problem of the retaining wall is not one that
admits of an exact mathematical solution; the conditions can not be
expressed in algebraic formulas. Something must be assumed in
any event, and it is far more simple and direct to assume the thick-
ness of the wall at once than to derive the latter from equations
based upon a number of uncertain assumptions.
Bear in. mind that none of the above formulas apply if the back
of the wall inclines towards the earth to be supported, or if the
wall has a curved profile, or if the upper surface is irregular. It
seems to be conceded that in these cases the surface of rupture is
not a plane, and hence no theory yet proposed will apply.
In this connection it seems necessary to warn the student that
not all theories for retaining walls are as nearly correct as those
referred to above. Some of them, although having all the prestige
of antiquity and offering the advantages of extended tables for their
application, are totally valueless, being based upon unwarranted
assumptions, and violating the fundamental principles of mechanics.
546. Theoretical investigations of many engineering problems
which in every-day practice need not be solved with extreme accu-
* Civil Engineering, pp. 401-07.
AET. 2.] EMPIRICAL BULES. 349
racy, are useful in determining the relations of the various elements
involved, and thus serve as a skeleton about which to group the
results of experience ; but the preceding discussion shows that the
present theories of the stability of retaining walls are not sufficiently
exact to serve even as a guide for future investigations. Further-
more, the stability of a retaining wall is not a purely mathematical
problem. Often the wall is designed and built before the nature of
the backing is known; and the variation of the backing, due to rain,
frost, shock, extraneous loads, etc., can not be included in any
formula.
ART. 2. EMPIRICAL EXILES.
547. ENGLISH RULES. The eminent English engineer Benjamin
Baker, who has had large experience in this line in the construc-
tion of the underground railroads of London, says, "Experience
has shown that a wall [to sustain earth having a level top surface],
whose thickness is one fourth of its height, and which batters 1 or
2 inches per foot on the face, possesses sufficient stability when the
backing and foundation are both favorable. This allows a factor of
safety of about two to cover contingencies. It has also been proved
by experience that under no ordinary conditions of surcharge or
heavy backing is it necessary to make a retaining wall on a solid
foundation more than double the above, or one half of the height in
thickness. Within these limits the engineer must vary the strength
according to the conditions affecting the particular case. Outside
of these limits, the structure ceases to be a retaining wall in the
ordinary acceptation of the term. As a result of his own experi-
ence, the author [Benj. Baker] makes the thickness of retaining
walls in ground of an average character equal to one third of the
height from the top of the footings.
"'Hundreds of revetments have been built by royal engineer
officers in accordance with Gen. Fanshawe's rule of some fifty years
ago, which was to make the thickness of a rectangular brick wall,
retaining ordinary material, 24 per cent, of the height for a batter
of |, 25 per cent, for -^ 26 per cent, for A, 27 per cent, for -^ 28 per
cent, for ^ 30 per cent, for -fa, and 32 per cent, for a vertical wall/ " *
548. TKATJTWINE'S RULE. Trautwinef recommends that " the
* Van Nostrand's Engineering Magazine, vol. xxv. p. 370, from Proc. Inst. of
C.E.
t Engineer's Pocket-Book (Ed. 1885), p. 683.
350 EETAIKING WALLS. [CHAP. XIV-
thickness of the top of the footing course of a vertical or nearly
vertical wall which is to sustain a backing of sand, gravel, or e-irth,
level top surface, when the backing is deposited loosely (as when
dumped from cars, carts, etc.). for railroad practice, should not be
less than the following :
Wall of cut-stone, or of first-class large-ranged rubble in mortar, 35 per cent.
" " good common scabbled mortar-rubble, or brick 40 per cent.
'* " well scabbled dry rubble 50 per cent.
When the backing is somewhat consolidated in horizontal layers,,
each of these thicknesses may be reduced; but no rule can be given.
for this. Since sand or gravel has no cohesion, the full dimensions
as above should be used, even though the backing be deposited in
layers. A mixture of sand, or earth with pebbles, paving stones,,
bowlders, etc., will exert a greater pressure against the wall than
the materials ordinarily used for backing; and hence when sucli
backing has to be used, the above thicknesses should be increased^
say, about 4 to -J- part."
549. DETAILS OF CoffSTEUCTioisr. The arrangement of the foun-
dation of a retaining wall is an important matter, but has already
been sufficiently discussed (see Part III, and also §§ 491 and 551).
It is universally admitted that a large majority — by some put at '
nine out of ten, and by others at ninety-nine out of a hundred — of
failures of retaining walls are due to defects in the foundation.
Ketaining walls are constructed of ashlar or brick, or of either
ashlar or brick backed with rubble, or of rubble either with mortar
or dry. As the pressure at each bed-joint is concentrated towards
the face of the wall, the larger and most regular stones should be
placed on the front. Occasional stones or even courses should
project beyond the back of the wall, so that the backing can rest
upon them, thus increasing the resistance of the wall to overturn-
ing. This object is also promoted by building the back in steps.
The coping should consist of large flat stones extending clear across
the wall.
As a rule, the greatest thrust comes against retaining walls when
the mortar is green and least able to resist it, which is a reason for
preferring cement to lime mortar. If the backing is to be filled in
before the mortar hardens, it should be deposited in thin, horizon-
tal layers, or the wall should be supported temporarily by shores.
550. Drainage. Next to a faulty foundation, water behind the
AKT. 2.] EMPIRICAL KULES. 351
wall is the most frequent cause of the failure of retaining walls.
"The water not only adds to the weight of the backing material, "but
also softens the material and changes the angle of repose so as to
greatly increase its lateral thrust. With clayey soil, or any material
resting upon a stratum of clay, this action becomes of the greatest
importance. To guard against the possibility of the backing's be-
coming saturated with water, holes, called weepers, are left through
the wall. One wcep-hole, three or four inches wide and the depth
of a course of masonry, is generally sufficient for every three or
four square yards of front of the wall. When the backing is clean
sand, the weep-holes will allow all the water to escape ; but if the
backing is retentive of water, a vertical layer of stones or coarse
gravel should be placed next to the wall to act as a drain. An
ordinary drain at the back of the wall is often useful.
When the backing is liable to be reduced to quicksand or mud
by saturation with water, and when this liability can not bo removed
by efficient drainage, one way of making provision to resist the
additional pressure which may arise from such saturation is to cal-
culate the requisite thickness of wall as if the earth were a fluid.
A puddle-wall is sometimes built against the back of dock-walls to
keep out the water.
The resistance of the wall to sliding is materially increased by
laying the lower courses of masonry with an inclination inward.
An objection to inclining the joints, particularly in dry masonry,
IB that the water will enter them and be carried to the backing.
This objection is sometimes met by building the face with horizon-
tal courses, and inclining the courses in the back of the wall. The
back of the wail for '3 or 3 feet from the top should have a batter
of at least 1 inch in 1 foot, in order that the frost may lift the
earth and not break the joints of the masonry.
Walls arc* sometimes built with both faces inclined toward the
material to be supported, and sometimes with a curved profile ; but
it is generally considered, unwise to do either, owing to the extra
expense and trouble in construction.
551. Land Ties. Retaining walls may have their stability in-
creased by being tied, or anchored by iron rods to vertical plates of
iron or blocks of stones imbedded in a firm stratum of earth at a
distance behind the wall. " The holding power, per foot of breadth,
of a rectangular vertical anchoring plate, the depth of whose upper
352 RETAINING WALLS. [CHAP. XIY.
and lower edges below the surface are respectively xl and #a , may
be approximately calculated from the following formula :
cos 2 0
in which If is the holding-power of the plate in pounds per foot of
breadth, w is the weight in pounds of a cubic foot of the earth,,
and <p its angle of repose. The center of pressure of the plate is
about two thirds of its height below its upper edge, — at which point
the tie-rod should be attached.
"If the retaining wall depends on the tie-rods alone for its
security against sliding forward, they should be fastened to plates
on the face of the wall in the line of the resultant pressure of the
earth behind the wall, that is, at one third [see § 530] of the height
of the wall above its base. But if the resistance to sliding forward
is to be distributed between the foundation and the tie-rods, the
latter should be placed at a higher level. For example, if half the
horizontal thrust is to be borne by the foundation and half by the
tie-rods, the latter should be fixed to the wall at two thirds of its
height above the base." *
552. Believing1 Arches. In extreme cases, the pressure of the
•earth may be sustained by relieving-arches. These consist of a row
of arches having their axes and the faces of their
piers at right angles to the face of a bank of earth.
There may be either a single row of them or several
tiers; and their front ends may be closed by a ver-
tical wall, — which then presents the appearance of
a retaining wall, although the length of the arch-
ways is such as to prevent the earth from abutting
FIG. 77. against it. Fig. 77 represents a vertical transverse
.section of such a wall, with two tiers of relieving arches be-
hind it.
To determine the conditions of stability of such a structure as a
whole, the horizontal pressure against the vertical plane OD may be
•determined, and compounded with the weight of the combined
mass of masonry and earth OAED, to find the resultant pressure
on the foundation.
*Rankine's Civil Engineering, p. 411.
CHAPTER XV.
IM1DGK ABUTMENTS.
There are four forms of almtments in
I. A plain wall parallel to the current,
553. GENERAL FORMS,
more or loss general use.
.shown in (Novation at, Fig. 7S, with or without the wings .-I I) /'rand
11 J'J (/. The slopes maybe finished with an inclined roping, an
A D, or offset at each course, as // A—usually the latter. This form
may appropriately be called the strait/lit dbuhneiif. *->. The wings
may be swung around into the bunk at. any angle, as shown (in plan)
in Fig. 79. The angle </> is usually about M()°. This form is known
D F.
Jl
n
Fit*. 81.
.us the iruttf abutment. IL When c/> of Fig. 79 becomes J)0", we havo
Kig. SO, which is called the U abut-menl. 4. If the wings of I^ig.
,S() are moved to the center of the head-wall, we get Kig. SI, which
is known as the T abutment.
The abutment of an ordinary bridge has two oflie.es to perform,
vi'/., (1) to support one end of the bridge*, and («) to keep the earth
•embankment from sliding into the water. In Fig. 7S, the portion
./) E (/ F nerves both them: purposes, while the wings A I) /'" and
,// AT (i act only as retaining walls. In Figs. 79 and SO, the portion
/> AT perfonuHboth oiVte.en, whili^ the wings A I> and // Ar are merely
retaining wal IK. In Fig. SI the ** head " /> K supports th<* bridge,
and the ** tail," or *'*Htem," A />* (!urri<is tht* train; henc<» tlu* whole
Hfcructuro acts as a retaining wall and also supports the load. The
abutment proper may fail (I) by sliding forward, (lr) by bulging, <>r
(3) by crushing; however, it is improbable that it will fail by .sliding
forward. Its dimensions are to bo determined an for a retaining
wall (Chap. XIV); but the mathematical theory of the* laterul
354 BRIDGE ABUTMENTS. [CHAP. XV.
pressure of earth is a much less perfect guide for designing bridge
abutments than it is for simple retaining walls. The weight of the
bridge helps the abutment to resist the thrust of the earth; but, on
the other hand,, the weight of the train on the embankment in-
creases the lateral pressure against the abutment.
554. The form of the abutment to be adopted for any particular
case will depend upon the locality, — whether the banks are low and
flat, or steep and rocky; whether the current is swift or slow; and
also upon the relative cost of earthwork and masonry. If the shore
is flat, and not liable to be cut away by the current, an abutment
like Fig. 78 will be sufficient and most economical. However, this
form is seldom used, owing to the danger of the water's flowing
along immediately behind the wall.
The form of Fig. 79 may be adopted when there is a contraction
of the waterway at the bridge site, since deflecting the wing walls,.
above and below, slightly increases the amount of water that can
pass. This advantage can be obtained, to some degree, with the
straight abutment (Fig. 78) by thinning the wings on the front and
leaving the back of the wings and abutments in one straight line.
There is not only no hydraulic advantage, but there is a positive
disadvantage, in increasing the deflection of the wings beyond, say,
10° or 15°. The more the wing departs from the face line as it
swings round into the embankment, the greater its length and also-
the greater is the thrust upon it. The wings are not usually ex-
tended to the toe, B, of the embankment slope, but stop at a height,
depending upon the angle of deflection and the slope, such that the-
earth flowing around the end of the wall will not get into the chan-
nel of the stream. It can be shown mathematically that, if the toe
of the earth which flows around the end of the wing is to be kept-
three or four feet back from the straight line through the face of
the abutment, an angle of 25° to 35° is best for economy of the
material in the wing walls. This angle varies slightly with the pro-
portions adopted for the wing wall and with the details of the
masonry. This form of construction is objectionable, since the
foot of the slope in front of the wing is liable to be washed away ;,
but this could be remedied somewhat by riprapping the slope, or^
better, by making the wings longer.
Fig. 78 is one extreme of Fig. 79, and Fig. 80 is the other. As
the wing swings back into the embankment the thrust upon it in-
WING ABUTMENT. 355
creases, reaching its maximum at an angle of about 45°; when the
wing is thrown farther back the outward thrust decreases, owing to
the filling up of the slope in front of the wing. Bringing the wings
perpendicular to the face of the abutment, as in Fig. SO, also de-
creases the lateral pressure of the earth, owing to the intersection of
the surfaces of rupture for the two sides, which is equivalent to re-
moving part of the "prism of maximum thrust." If the banks of
the stream are steep, the base of the wing walls of Fig. 80 may be
stepped to fit the ground, thereby saving masonry. Under these
conditions, also the wing abutment, Fig. 79, can be treated in the
same way; but the saving is considerably less. When the masonry
is Stepped off in this way, the angle thus formed becomes the weak-
est part of the masonry; but, as the masonry has a large excess of
strength, there is not much probability of danger from this cause,
provided the work is executed with reasonable care.
555. Fig. 81 is the most common form of abutment. For equal
amounts of masonry, wing abutments give better protection to the
embankments than T abutments. The latter are more stable, be-
cause the center of gravity of the masonry is farther back from the
line of the face of the abutment, about which line the abutment
must turn or along which it will first crush. The amount of ma-
sonry in tall T abutments can be decreased by building the tail wall
hollow, or by introducing arches under it. The more massive the
masonry, the cheaper it can be constructed; and, for this reason, it
is probable that the simple T abutment is cheaper than the U abut-
ment, although the latter may have less masonry in it. On the other
hand, the opportunities for inspecting the masonry during construc-
tion are better with the U than with the T abutment, and hence the
former is usually better built than the latter. This is an important
item, since it is somewhat common for railroad masonry to fail by
being shaken to pieces by the passage of trains.
556. WING ABUTMENT. Fig. 82 shows a common form of the
wing abutment. This one is finished with stone pedestal blocks —
marked B in plan, A in elevation, and C in section, — which is not
always done. The thickness of pedestal blocks and the thickness
of the coping under the pedestal blocks vary slightly with the span
(see § 558). The height of the parapet wall, or dirt wall (the wall
which keeps back the top of the embankment, marked P Win
section), will vary with the style of the bridge, but should not have
356
BRIDGE ABUTMENTS.
[CHAP. XV.
a thickness less than four tenths of its height (see §§ 547 and 548).
The bridge often rests directly upon the coping. The top dimen-
sions of the abutment will depend somewhat upon the size and
form of bridge : but for railroad bridges it will usually not be less
than 5 ft. wide by 20 ft. long, nor more than 6 ft. by 22 ft.
u
2
D
PQ
§
• y
o
The usual batter is 1 in 12; sometimes 1 in 24. For heights
under about 20 ft., the top dimensions and the batter determine the
thickness at the bottom. For greater heights, the quite uniform
WING ABUTMENT.
357
TABLE 87.
QUANTITY OF MASONRY IN WING ABUTMKNTH OF THE GBNBBAL FORM
SHOWN IN PIG. 82. SEE § 557.
i
1 $
h >/'4 :
DIMENSIONS OF THJC
ROTTOM OF ABUTMENT.
AREA OF LOWEST
COURSE.
MASONRY IN ONE ABUTMENT,
EXCLUSIVE OF FOOTING,
COPINGK, AND PEDESTAL**.*
Sl^
fc O :
2
»
!i ii 5
gP ; -S
S
£
&
1
!
h "* lit;
<p
«£* be
o a
m
.5
1
a
C 'J
"3
«*§
Sjjs
£
P=
ft
^
i
•tijhrt
.Whiii
Jg «M
o»
o
3
0)
p
2
*2
C
o
S3
o
H-(
pc
H
J
O
H
E-t
0
H
^
H
feet.
/<•»•*.
/<"*''.
ft'i't.
L ft.
*/../*.
Mf. ft.
r».//.
en, ft.
CM. ft.
cu. ydtt.
6
2% 2
6.8
18.0
151
105
31(5
700
(510
280
57.7
(5
aa 1 a
7.0
20 . (5
I 155
184
880
803
821
230
70 8
7
22.8
r> o
22 3
1(51
203
3(54
1.021
1.020
280
84.1
8
22,3
7.3
24 lo
1 (53
228
3K«
1,188
1 ,2.38
280
08.1
7.' ft
1 (58
248
411
1.3 J8
1 .475
280
118 0
10
aa! 4
a: '.4
172
204
430
I 1,518
1.732
230
128.8
11
22.5
7* 8
20.1
17(5
285
401
I. CM
2,011
280
145.0
12
H!O
30.8
180
300
48(5
1 .WiO
2,810
280
1(52. (5
18
221 5
8.2
82 . 5
| 185
328
518
; 2 (i.VJ
2, (532
280
182.0
14
22.0
8.8
84 . 2
i 188
351
530
2.238
2.075
280
201.0
15
22.0
8.5
35 lo
192
87'4
50(5
2.420
3.811
280
222.2
in
22,7
8.7
37.0
1.97
398
505
2.C.23
8.781
280
243.8
17
8.8
30,4
200
422
022
2.K22
4.144
280
2(5(5.5
18
22 1 7
0.0
41.0
204
447
051
3.024
4,580
280
200.1
1«
22 . 8
42.8
207
472
070
8.232
5,041
280
814.0
20
22,8
Ol3
44.5
| 4) JO
407
700
! 3,4-12
5,52(5
230
340.0
21
22 . 0
0.5
! 217
528
740
8,057
(5,038
230
8(57.5
22 . 0
0.7
47.0
1 222
550
772
8.H70
(5.577
280
305,0
21
23 0
0.8
40. (5
i 22ft
577
802
4. KM)
7,148
280
424.0
24
23,0
10.0
51.3
! *>$()
(504
834
4,327
7.7*35
280
455.8
2ft
23.0
10.2
58,0
235
(533
8(58
4.550
H,8ft4
230
48(5.7
215
23.1
10.8
54.7
; 238
(5(51
8110
4,700
0.0(12
280
510.5
27
28.1
10.5
50.4
243
(500
$133
5,030
0.078
280
553.4
28
23 a
10,7
58.1
248
720
JI08
5.281
10.381
230
588.7
10.8
59.8
251
750
1,001
5,530
11.120
230
025.1
So
£j 3
11.0
01.5
25(5
780
1,030
5.7K4
11.880
J80
002.0
31
23.8
11.2
03.2
2(51
811
1,072
(5.041
i 12,082
*J80
701.0
23.8
11.8
04.0
2(58
818
1,10(5
(5,803
: 13.500
J80
7-12.0
83
11.5
(50, (J
2(5$)
875
1,144
(5,5(50
i 14,800
J80
784. 0
84
23 1 4
11.7
OK. 4
278
007
1,180
0,841
i 15,250
230
827.0
85
11.8
70.1
277
040
1,217
7,110
; 1(5,182
280
871.4
3(5
**3*5
12.0
71,8
282
073
1,255
7,305
; 1 7.130
280
017.2
37
28 (5
i*«j a
73 5
288
1 ,007
1,295
7,(!7'0
18,127
280
0(5.1.2
38
S!o
12.3
75.2
200
1,042
1,332
7,907
10,150
J80
1,012.8
* Dimwmion H|.OII« in two pwlwUl 1>
•• ** ** rnnilU1" of OI1U
„'
04 cu. f«««»t.
234 u '*
abutment
«.
rule IK to make the ihiektieHH four tenths of the height. The amount
of masonry in the abutment in computed in aeeordane.o with thin
rule, although the actual quantity in usually more than that required
by it. Siuee there i« no objection to tin* wall's being rough, no
358 BRIDGE ABUTMENTS. [CHAP. XT.
stones are cut out to secure the specified thickness, and hence the
actual quantity of masonry usually exceeds the amount required.
The spread of the footing courses and foundation will depend, of
course, upon the location.
The wings should be proportioned according to the rules for
retaining walls (see §§ 547 and 548). The wings are not always pro-
longed u*ntil their outer ends intersect the foot of the embankment
slope; but are frequently stopped with an end height of 3 to 5 feet
above the footing. The thickness of the wing wall decreases from
the body of the abutment toward the tail in proportion to the height.
For appearance, the top of the wing is usually made uniform from
head to tail, being usually from 2| to 3-|- feet, according to the size
of the structure. The steps should be capped with stones, not less
than 1 foot thick, covering the entire step and extending under the
step above not less than 1 foot.
557. Contents of Wing Abutments. The table on page 357
gives the quantities of masonry in wing abutments of the form
shown in Fig. 82. Since the outlines of such structures are not
simple geometrical figures, it is necessary to make more or less ap-
proximations in computing the cubical contents. For example, in
Fig. 82 the wings are stepped off to fit the slope of the embankment
as shown; and hence the corner of each course projects beyond the
earthwork. The amount of masonry in these projecting corners
varies as the thickness of the courses, and for any particular abut-
ment it could be found accurately; but, in computing a table of
general results, it is necessary to assume some thickness for the
courses. In this case the courses were assumed to be 1 foot thick.
The back of the ec head " was assumed to conform strictly to the batter
line, although in construction it would be stepped. The dimensions
of the parapet wall will vary with the thickness of the pedestal
blocks used, and also with the style of the bridge. The contents
of the parapet as given in the table are for the dimensions shown in
Fig. 82.
Footing courses were not included in the table, since they vary
with the nature of the foundation. The area of the lowest course
of masonry is given, from which the areas of the footing courses and
of the foundation pit may be determined. The thickness at tho
top and the batter, as in Fig. 82, give, for any height found in the
table, a thickness of wall at the bottom, of at least four tenths of its
U ABUTMENT. 359
height (see §548); for heights greater than in the table, the back
of the wall must be stepped to keep the thickness four tenths of the
height.*
558. U ABUTMENT. Fig. 83 shows the standard plans of the
Atchison, Topeka and Santa I1 e E. K.f for U abutments. This is
the only form of bridge abutment used on this road, except in
special cases. The T abutment was once the standard, but was
abandoned about fifteen years ago. J
The specifications under which these abutments are built, require
.as follows : " 1. Bed-plate pedestal blocks to be 2 feet thick, and
placed symmetrically with regard to the plates. 2. Coping under
pedestal blocks to be 18 inches thick for all spans exceeding 100
feet, 16 inches for 90 feet, and 14 inches for spans under 90
feet, — said coping to be through stones, and spaced alike from both
.sides of abutment. 3. Distances from front of dirt wall to front
of bridge seat, and from grade line to top of bridge seat, and
thickness of dirt wall, to vary for different styles and lengths of
bridges. 4. Front walls to be 22 feet wide under bridge seat for
all spans of 100 to 160 feet inclusive. 5. Total width of bridge
seat to be 5^ feet, for all spans. 6. Steps on back of walls to
be used only when necessary to keep thickness -fa- of the height.
7. In case piling is not used, footing courses may be added to give
secure foundation. 8. Length of wing walls to be determined by a
slope of 14- to 1 at the back end of the walls — as shown by dotted
line in front elevation, — thence by a slope of 1 to 1 down the outside
— as shown on side elevation — to the intersection of the ground line
with face of abutment. This rule may be modified in special cases.
9. Dimensions not given on the drawing are determined by the
style and length of bridge, and are to be found on special sheet."
559. Although this road is noted for the excellency of its
masonry, this design could be improved by leaving a weep hole in
the side walls, 2 or 3 inches wide and the depth of a course of
* In computing the contents of masonry structures, it is necessary to remember
that the volume of any mass which is made up of prisms, wedges, and pyramids-— or
cones— must "be determined by the prismoidal formula ; but if the mass is composed
wholly of prisms and wedges, the contents can be correctly found by using the aver-
age of the end areas.
t Published by permission of A. A. Robinson, Chief Engineer.
% Compare with § 555.
360
BEIDGE ABUTMENTS.
[CHAP. XT,
FIG. 83.— U ABUTMENT.— A. T. & S. F. B.
IT ABUTMENT.
361
TABLE 88.
QUANTITY OF MASONRY IN U ABUTMENTS OF TIIK GENERAL FORM
SHOWN IN FIG. 88. !Sec $ 560.
9*
DlMKNHIONH OF THE
BOTTOM OF THE
8
QUANTITY OF
MAHONUY, EX-
CLUHIVIC OF
l§
ABUTMENT.
£
COPING.*
t*o
to .
W S
0 o
h %
«5
EXAMPLES OF THE METHOD OF
0»
fa H
O O
•^i
USING THE TABLE.
I fc
$
i w
c
jd
o
gB
j*-1 o
2 o
•3
.<y
^
0 H
"S
o §
ffi
£
2
H
5
«,
W
H
o
/«•<*.
/«•*.
feet.
fcrt.
fft't.
cu.fi.
cu. ft.
s
1
22.2
5.1
118
8.1
Ill
6.0
5- <M. - * ~ - ...-.--
"*
2
22.8
5.2
115
8.2
225
12.8
^ g::^:::^ 3 : : a ;: » :
,1
22.5
5 2
1 1 9
8.2
842
l«»
4
22'.7
5.8
120
8! 8
462
25 .'2
§ ggggi^ fe2§§2s§
i
5
22.8
5.4
124
8.4
584
82.0
•g c*" oo"
Gi-
6
28.0
5.5
JT l\
120
8.5
*> /;
709
89.0
s II II II II II II II II II II II II II
ll
8
28! 8
O . "'
5.7
182
O.I)
8.7
968
46 . 0
58.8
JJ .
« : : : : ;
9
28 5
5.8
185
8.8
1,101
60.8
*/p > • \ ^ *r
10
28 7
5.8
188
4.0
1 288
68.4
§ : Xx«j»^
n
28 8
5.9
141
4.4
1,877
76,8
^ 1 30 ^ ^ * •
12
24 . 0
0 0
144
4.8
1 , 520
86 0
•K* ^ »J *~"S C t
18
24.2
0.1
147
5*.2
1^665
96 J)
"a ^",0 H I'll II
ffi
•O
14
24.8
0.2
150
5.6
1,814
100.8
"** xv <c>: " ^ *°'n
15
24.5
0.2 158
6.0
1,966
118.4
.s 60 ^^wff r*i
U
10
24.7
O.tt'i 156
0.4
2,120
180.8
S Q CJ^ II II II jj^^^
17
24.8
0.8 KJ9
6.8
2,288
144.0
§ 1; "t 1" 5 II*' xx
^
18
25.0
7.2
180
7.2
2,478
158.0
c <? x 22 *^ : : ^ v * p-
§.
19
25.2
7.6
191
7.6
2;688
172.8
S^" \*ra. T, r» •s--'~ifo!f5
if
20
25.8
8.0 208
8.0
2,920 188.4
• •» X o o o S *^ I-
b
13
21
25.5
8.4
214
8.4
8,174
204.8
f*< TP O C» TP "3« W) X f* •
22
25.7
8.8 226
8.H
8,449
222.0
•5 ^® "\-\' S .s^??
£
28
25,8
9.2 2M8
9.2
8,746
240.0
"a " "ttjilj; * ^fv
21
20.0
9.6 250
9.0
4,0(56
258.8
1 r CIW**^^' ^ ft. C^p;
©
25
20.2
10.0 202
10.0
4,408
278.4
"S > n S^j " " b«^ : *^I'£
H
20
20.8
10.4- 274
10.4
4,772
298 .8 Is ** J2 &?? ^ 'C *f «« *r> r/j a!
•27
20.5 '10.8 280 10.8
5,160
820. '()
*, ; o ^r it a • ^= r« ci we «
.g >re ^o .g £ p j ^ . .. 5f .2 S
28
20.7 11.2 299 ill. 2
5,570
842.0
"k" It'-'f'SlwJ jd o> !§ c M
29
20.8 11. Oj 811 U. 0
6,008
864.8
80
27.0 12.0' 824
2.0
6,400
888.4
"s ^ •? W*^' ^ : * P W S :
81
27.2 U2.4 887
2.4
6,941
412.8
•Si *-'S'g(tgi« ^ 5,*"
82
27.8 12.8 850
2.8
7,445
488.0
I | j ^c* s^Ss'i* sSs
88
27.5 i;18.2 808
8.2
7,978
464.0
: ^S*r:ss2ss s:r
84
27.7 18.6; 870
8.6
8.520
490.8
• SI a
85
27.8 14.0 890
14.0
9,108 518.4
"5 «0 q
___ ' „ _. , , _
1 "B^s""'*""*"*
* For rilmonHiotmof roplnjj and pctleHtul UloclcH,
: fll °
««•« Hcrottd paragraph of S fifiH.
.0
362
BRIDGE ABUTMENTS.
[CHAP. xv.
masonry., for each 4 or 5 square yards of wing wall. Cinders, or
sand and gravel are sometimes used to fill in between the wing walls
to give a better drainage, and also to decrease the lateral thrust of
the earth.
560. Contents of U Abutments. The table on page 361 gives
the contents of U abutments of the form shown in Fig. 83. The
u U
Pi n
U 'J
u u u
^^Innpnnp
Uuil1^ V'j','
r«c 84.
T ABUTMENT
quantities were computed on the basis that the thickness of the
walls was four tenths the height, except that no wall was taken of a
less thickness than that given by the thickness at the top and the
batter as in the drawing.
561. T ABUTMENT. Fig. 84 shows the ordinary form of T abut-
T ABUTMENT.
363
TABLE 39.
QUANTITY OF MASONRY IN T ABUTMENTS OF THE GENERAL FORM
SHOWN IN FIG. 84. SEE § 562.
>§
DIMENSIONS OF THE
QUANTITY OF MASONRY,
i S
X
BOTTOM OF THE HEAD.
EXCLUSIVE OF COPING.
2
(M
o
EXAMPLE OF THE METHOD OF
-§|
1
XT&INQ THE TABLE.
fr §
CO
01
•3
a
^
So
&"&
t3
3
1
!
a3
OJ
w
1
lr
/ee*.
feet.
feet.
feet.
CU. ft.
cu.ft.
CU. ft.
l^8g3f3|g|8fSS|
§
5
22.8
5.8
133
607
12.5
60
§ 0 co" 0*1-:
of
II
6
23.0
6.0
6c\
138
"1 A O
743
QQ-3
18.0
72
t'"* M='«wiH«w : i ::•::::
7
8
23.2
23 3
.2
6.8
14o j
148
ooo
1,029
32*.0
96 '
1
.2
9
23.5
6.5
153
1,179
40.5
108
ij; "" vvv •0606'*
2
10
23.7
6.7
158
1,334
50.0
120
« §*>§§ :oXX
3
O
11
23.8
6.8
163
1,495
60.5
132
CO
12
24.0
7.0
168
1,660
72.0
144
i +ixxx • ii 11 U
ii
13
24.2
7.2
173
1,831
84.5
156
^ • <oCJS°" w ^""^
II
14
24.3
7.3
178
2,006
98.0
168
^.•«to^T""~< *•* j ** £ *s
b
15
24.5
7.5
184
2,188
112.5
180
°°'Q «2 " X aojioo
p
16
24.7
7*. 7
189
2,374
128.0
192
^ |g 3 i**^
s
OS
17
24.8
7.8
195
2,566
144.5
204
^'S, 1*S,S 3 ^.J ".^
a
18
25.0
8.0
200
2,763
162.0
216
"2 « "So0 X'g^^^s 2 ££
1
19
25.2
8.2
206
2,966
180.5
228
S-o g-g o^^^S ««
20
25.3
8.3
211
3,174
200.0
240
g-2 ^ s ,-, gSe* r^rj^l^
21
25.5
8.5
217
3,388
220.5
252
"Sj ^ §0= - ^03^ "^JJwo
22
35.7
8.7
222
3,608
242.0
264
^'g *£"§ as J-S. , SS2
23
25.8
8.8
228
3,833
264.5
276
S"0 8/2 'I c?^" i XX
24
26.0
9.0
234
4,064
288.0
288
^^ ^2= = "lH p- ^- - "^^
25
26.2
9 2
240
4,301
312.5
300
-§ i 'S1^ ^43'w" ".E"* " ^^
26
26.3
9'.3
246
4,544
338.0
312
e"e ,~ ^ - ^ ^3- 2 'd^.
27
26.5
9.5
252
4,793
364.5
324
:§Ht *M-2 <oi^ ^2 s $2
28
26.7
9.7
258
5,047
392.0
336
«^§ S)®^ ^ rO^^S «M- - S-
29
26.8
9.8
264
5,308
420.5
348
®r5| *|S" " S*^"2 o. " *^;
30
27.0
10.0
270
5,575
450.0
360
"sS P^! ^o®3 •^:: * §*
31
27.2
10.2
276
5,848
480.5
372
"§•«- S"*3 s B^^"13^— p°
3'3
27.3
10.3
282
6,127
512.0
384
i^^i S'i'S'olS '•§-
33
27.5
10.5
289
6,413
544.5
396
v~ g^- s l8ll^'§2«2
**<!
97 7
107
OQ^k
6 705
578.0
408
o*t
35
& i . t
27.8
1 U . t
10.8
301
7^003
612^5
420
l| |
Area of coping on 2 wings, per ft. of length = 5 sq. ft.
Area of coping on bridge-seat = 138 " *'
If 6
364 BRIDGE ABUTMENTS. [CHAP. XV.
ment. For railroad bridges the head is usually not less than 5 ft.
X 20 ft., nor more than 6 ft. X 22 ft., under the coping, according
to the size of the bridge. The tail wall is usually 10 or 12 ft. wide,
and of such length that the foot of the slope of the embankment
will just reach to the back of the head wall. The batter on the
head wall is 1 to 12 or 1 to 24 all around. The tail wall is generally
built vertical on the sides and the end. Notice the batter at the
top of the free end of the tail wall. This is known as the " frost
batter," and is to prevent the frost from dislocating the corner of
the masonry. The drainage of the ballast pocket should be pro-
vided for by leaving a space between the ends of two stones.
Formerly the tail wall was sometimes only 7 or 8 feet wide, in which
case the ties were laid directly upon the masonry without the inter-
vention of ballast ; but this practice has been abandoned, as being
very destructive of both rolling stock and masonry.
According to the common theories for retaining walls, T abut-
ments with dimensions as above have very large factors of stability
against sliding, and overturning, and crushing.
562. Contents of T Abutments. The table on page 363 gives the
contents of the abutments of the form shown in Fig. 84. The
height of the tail above the under side of the bridge-seat coping will
vary with the thickness of the pedestal blocks, and with the style of
the bridge ; and hence the table gives the quantities in the abutment
below the bridge-seat coping and above the footing. The quantity
of masonry above this line will vary also with the amount of ballast
used. The term. ff wedge " in the table is used to designate that
part of the tail included between the head and a vertical plane
through the lower edge of the back face of the head.
563. FOUNDATION. Usually but little difficulty is encountered
in securing a foundation for bridge abutments: Frequently the
foundation is shallow, and can be put down without a coffer-dam,
or at most with only a light curb (see §§ 316-^0). Where the ground
is soft or liable to scour, a pile foundation and grillage is generally
employed. For the method of doing this, see Art. 3, Chapter XI ;.
and for examples of this kind of foundation, see Fig. 84 (page 362), .
Fig. 86 (page 380), and Fig. 90 (page 386).
"Where there is no danger of underwashing, and where the foun-
dation will at all times be under water, the masonry may be started
upon a timber platform consisting of timbers from, say, 8 to 12
QUALITY OF MASONRY. 365
inches thick, laid side by side upon sills, and covered by one or
more layers of timbers or thick planks, according to the depth of
the foundation and the magnitude of the structure. For an exam-
ple of a foundation of this class, see Plate II. For a discussion of
the method of failure by sliding on the foundation, see § 491.
564. QUALITY OF MASOBTBY.— -Bridge abutments are built of
first-class masonry (§ 207) or of second-class (§§ 209 and 212), ac-
cording to the importance of the structure. See also the specifica-
tions for bridge pier masonry (§§ 591-600). The coping should be
composed of as large stones as practicable — not less than 12 inches
thick, and 15 or 18 inches thick is better and more frequently used.
Sometimes, the bed plates of the bridge rest directly upon the
coping, but usually upon a stone pedestal block (see Figs. 82 and
S3), in which case small pedestals, upon which the rail stringers
rest (see Fig. 90, page 386), are also generally used.
565. COST. For data on the cost of masonry, see §§ 232-38.
CHAPTER XVL
BRIDGE PIERS.
566. The selection of the site of the bridge and the arrangement
of the spans, although important in themselves, do not properly be-
long to the part of the problem here considered ; therefore they
will be discussed only briefly. The location of the bridge is usually
a compromise between the interests of the railroad or highway, and
of the river. On navigable streams, the location of a bridge its
height, position of piers, etc., are subject to the approval of engi-
neers appointed for the purpose by the United States Government.
The law requires that the bridge shall cross the main channel nearly
at right angles, and that the abutments shall not contract nor the
piers obstruct the water way. For the regulations governing the
various streams, and also reports made on special cases, see the
various annual reports of the Chief of Engineers, II. S. A., particu-
larly Appendix X3, of the Report for 1878.
The arrangement of the spans is determined mainly by the rela-
tive expense for foundations, and the increased expense per linear
foot of long spans. Where the piers are low and foundations easily
secured, with a correspondingly light cost, short spans and an in-
creased number of piers are generally economical, provided the piers
do not dangerously obstruct the current or the stream is not navi-
gable. On the other hand, where the cost of securing proper foun-
dations is great and much difficulty is likely to be encountered, long
spans and the minimum number of piers is best. Sound judgment
and large experience are required in comparing and deciding upon
the plan best adapted to the varying local conditions.
Within a few years it has become necessary to build bridge piers
of very great height, and for economical considerations iron has
been substituted for stone. The determination of the stability of
such piers is wholly a question of finding the stress in frame struc-
tures,— the consideration of which is foreign to our subject.
366
AKT. 1.] THEORY OF STABILITY. 3 67
ART. 1. THEORY OF STABILITY.
567. METHOD OF FAILURE. A bridge pier may fail in any one
of three ways : (1) by sliding on tiny section on account, of the ac-
tion of the wind against the train, bridge, and exposed part of the
•pier, and of the current of the stream against, the immersed part of
the pier; or (;i) by overturning at any section when the moment, of
the horizontal forces above the section exceeds the moment; of the
weight on the section ; or (!>) by washing at any section under the
combined weight of the pier, the bridge, and the train. The-
dimensions of piers are seldom determined by the preceding condi-
tions ; the dimensions required at. the top (§f>S4) for the bridge
Beat, together with a slight batter for appearance, generally give
Huflioient stability against sliding, overturning, and crushing. How-
ever, the method of determining the stability will bo briefly out-
lined and illustrated by an example.
568. STABILITY AGAINST SLIDING. Effect of the Wind. The
pressure of the wind against the truss alone is usually taken at 50
Ibs. per sq. ft. against twice the vortical projection of one truss,
which for well-proportioned iron trusses will average about 10 sq. ft.
per linear foot of span. The. pressure of the wind against the truss
and train together is usually taken sit »H) Ibs, per sq. .ft., of truss and
train. The train ox poses about 10 sq. ft. of surface per linear foot.
The pressure of the wind against anv other than a flat surface in
not known with any certainty ; for a cylinder, it is usually assumed
that the pressure is two thirds of that against its vertical projection.
569. Effect of Current. For the pressure of the current of
water against an obstruction, Woisbach's Mechanics of Engineering
(page 1,(KH) of OOXO'H edition) gives the formula,
(1)
in which P ia the pressure in pounds, a the exposed surface in
sq. ft.j k a co-efficient depending upon the ratio of width to length
of the pier, w the weight of a cubic, foot of water, v the velocity in
ft. per noes., and // the acceleration of gravity. For piers with
rectangular OWHH section, /• varies between 1.47 and 1.33? the first
being for square piers and the* latter for those l\ times an long as
BRIDGE PIERS. ' [CHAP. XVI.
The law of the variation of
wide; to
the Telocity with depth is not certainly known ; but it is probable
that the velocity varies as the ordinates of an ellipse, the greatest
velocity being a little below the surface. Of course, the water has
its maximum effect when at its highest stage.
570. Effect of Ice, The pier is also liable to a horizontal press-
ure due to floating ice. The formulas for impact are not applica-
ble to this case. The assumption is sometimes made that the field
of ice which may rest against the pier, will simply increase the sur-
face exposed to the pressure of the current. The greatest pressure
possible will occur when a field of ice, so large that it is not stopped
by the impact, strikes the pier and plows past, crushing a channel
through it equal to the greatest width of the pier. The resulting
horizontal pressure is equal to the area crushed multiplied by the
crushing strength of the ice. The latter varies with the tempera-
ture; but since ice will move down stream in fields only when
melting, we desire its minimum strength. The crushing strength
of floating ice is sometimes put at 20 tons per sq. ft. (300 Ibs. per
sq. inch); but in computing the stability of the piers of the St.
Louis steel-arch bridge, it was taken at 600 Ibs. per sq. inch (43
tons per sq. ft.). According to some German experiments, the
crushing strength of ice, at 32° F., varies between 61 and 20-4 Ibs.
per sq. in.*
Occasionally a gorge of ice may form between the piers, and
dam the water back. The resulting horizontal pressure on a pier
will then be equal to the hydrostatic pressure on the width of the
pier and half the span on either side, due to the difference between
the level of the water immediately above and below the bridge
opening. A pier is also liable to blows from rafts, boats, etc. ; but
as these can not occur simultaneously with a field of ice, and will
probably be smaller than that, it will not generally be necessary to
consider them.
A lateral pressure on the pier is possible, due to the earth's be-
ing washed away from one side and not from the opposite. It will
be on the safe side, and near enough for this purpose, to assume
that this effect is equal to the pressure of a liquid whose density is
the difference between that of the water and the saturated soil dis-
placed. Under these conditions, the actual tendency to slide is
* Engineering News, vol. xiv. p. 407.
AUT. 1.] THEORY OF STABILITY. 3G9
•equal to the square root of the sum of the down stream forces and
the lateral thrust. However, this refinement is unnecessary, par-
ticularly since a pier "which is reasonably safe against overturning
and crushing will be amply safe against sliding.
571. Resisting Forces. The resisting force is the friction due to
the combined weight of the train, bridge, and the part of the pier
.above the section considered. For the greatest refinement, it would
be necessary to compute the forces tending to slide the pier for two
conditions : viz., (1) with a. wind, of f>0 Ibs. per sq. ft. on truss and
pier, in which ease the weight of the train should he omitted from
the resisting forces ; and (^) with a wind of IK) Ibs. per sq. ft. on
truss, train, and pier, in which case the weight of a train of r-nipft/
box cars should be included in the resisting forces. For a table of
weights of masonry, see page "200. If the water can find its way
under the foundation in thin sheets, the weight; of the part of the
pier that is immersed in the water will be diminished by <>*U Ibs.
per en. Ft. by buoyancy ; but if it finds its \va.y under any section
by absorption only, then no allowance* need be made for buoyancy.
The resisting force is equal to the product of the total weight
and the eo-efliciont of friction. For values of the- eo-cttk*.ient of
friction, see the table on page JUT). The tenacity of the mortar is
usually neglected, although it is a very considerable element of
strength (see £ 1JJ7).
572. STABILITY AGAIKST OVEBTTJRNING. The. forces which tend
to produce sliding also tend to produce overturning, and the forces
which resist sliding also resist overturning ; hence, there remains to
•determine only their points of application. The stability can be
determined either by moments or by resolution,, as was explained for
dams ; but in this ease, it is easier by moments, since there are sev-
eral horizontal forces, and it requires considerable work to find their
resultant as demanded by the method by resolution of forces.
573. A. By Moments. By this method, it is necessary to find
the arm of tho forces, i.e., the perpendicular distance from the lino
•of action of the forces to a point about which tho pier tends to turn.
This is the name method as that used in g§ 4.9'.M)8, which nee.
The center of pressure of the wind on the truss is practically at
the middle of its height ; that of tho wind on the train in 7 to 1)
feet above the top of the rail ; and that of the wind on the pier is
ait the middle of the exposed part. The arm for the pressure, of the
370
BRIDGE PIERS. [CHAP. X
ice should be measured from high water. The center of pressure
of the current is not easily determined, since the law of the varia-
tion of the velocity with the depth is not known ; but it will proba-
bly be safe to take it at one third the depth. Finally, the downward
forces will usually act vertically through the center of the pier.
From these data the overturning and resisting moments can
easilvbe computed. For equilibrium, the summation of the former
must be less than the latter. The above principles will bo further
elucidated in §§ 579-80 by an example.
574. B. By Eesolution of Porces. This is the method explained
in § 499 (page 320). In that case the problem was very sim-
ple, since there were but two forces ; but in the present case there
are several horizontal forces and also several vertical ones. The first
step is to find a single force which is equivalent in every respect to
the combined effect of all the horizontal forces ; the second is to
find an equivalent for all of the vertical forces ; and the third is to
find the resultant of these two forces.
The horizontal distance, x, of the point of application of the re-
sultant of all the vertical forces, back from the toe of the pier, is
found by the equation,
__ sum of the moments of the vertical forces m
sum of the vertical forces ' " * '
The weight of the train and bridge act vertically through the center
of the pier; and if the pier is symmetrical, as it usually is, the
weight of the pier will also act through its center. Therefore,, ic in
equation (2) will usually be half the length of the pier.
The vertical distance, y, of the point of application of the re-
sultant of all the horizontal forces above any horizontal joint is
found by the equation,
y __ sum of Me moments of the horizontal forces
sum of the horizontal forces * * ^'
Having found x and y, as above, draw a vertical line at a distance
x back from the down stream end of the pier; on this line lay off a
distance y above the horizontal joint under consideration. The
point thus determined corresponds to a of Fig. 70 (page 320) Con-
struct the parallelogram of forces by laying of, to any convenient
AET. 1.] THEORY OF STABILITY. 371
scale, (1) a horizontal line equal to the sum of all the horizontal
forces acting on the pier, and (2) a vertical line equal to the sum of
all the vertical forces ; and complete the diagram by drawing the
resultant. The stability of the pier is determined by the ratio of
A 0 to JV C, Fig. 70.
575. STABILITY AGAINST CRUSHING. Represent the maximum
pressure by P, the total weight on the section by W, the area of the
section by 8, the moment of inertia of the section by /, the length
of the section by Z, and the overturning moment by M ; then from
equation (1), page 205, we have
For the particular case in which the pier has a rectangular horizon-
tal cross section, the above formula becomes the same as equation
(18), (page 322,) as deduced for an element of a masonry dam.
The method of applying the above equation will be explained in
§ 581 by an example.
576. EXAMPLE OF METHOD OF COMPUTING STABILITY. Fig. 85
shows the dimensions of the channel pier of the Illinois Central R.
R. bridge over the Ohio River at Cairo, 111. This pier stands be-
tween two 523-foot spans. Its stability will now be tested by the
preceding principles.
577. Stability against Sliding. We will examine the stabil-
ity against sliding on the top footing course. The wind surface of
the truss = 10 sq. ft. X 523 = 5,230 sq. ft. The wind pressure
against the truss at 30 Ibs. per sq. ft. = 30 Ibs. X 5,230 =156,900
Ibs. •= 78 tons ; and the wind pressure on the truss at 50 Ibs. =
50 Ibs. X 5,230 = 261,500 Ibs. = 131 tons.
The wind pressure on train at 30 Ibs. per sq. ft. = 30 Ibs. X
523 x 10 = 156,900 Ibs = 78 tons.
The pressure of the wind against a section of the pier 52 ft.
long, is 20 Ibs. X 52 X 14 = 14,560 Ibs. = 7 tons.
The pressure due to the ice is found as follows: Assume the
thickness to be 1 foot , and also assume the crushing strength of
ice to be 200 Ibs. per sq. in. =, say, 15 tons per sq. ft. The pier is
16 ft. wide at the high- water line. Hence the resistance required in
the pier to crush its way through a field of ice is 15 tons X 16 X 1
= 240 tons.
372
BRIDGE PIERS.
[CHAP. xvi.
FIG. 85.— CHANNEL PIER, CAIRO BRIDGE.
ART. 1.] THEOBY OF STABILITY. 373
The pressure due to the current is found as follows: Prom
v a
§ 569, P = swk — . s represents the exposed surface = 70 ft. X
*9
19 ft. = 1,330 sq. ft., which value is equivalent to assuming that
the river may scour to the top of the footing courses, k represents
a co-efficient, which, if the pier were rectangular, would be about
1.4, and if the pier were cylindrical would equal about 0.73. "We
will assume it to be 1.1, — a trifle more than the mean of .these two
values, w = 62.5 Ibs, per cu. ft. The surface velocity at the
bridge site was measured* " when the Mississippi and the Ohio
were at about the same stage/' and found to be 4 miles per hour
(=6 ft. per second); but as high water may occur in the Ohio at
the time of moderately low water in the Mississippi, the possible
maximum velocity is greater than the above, and hence we will as-
sume that it is 10 ft. per second. The velocity of the water at
various depths below the surface of a stream, varies as the ordinate
of an ellipse; but the effect of the mean velocity is approximated
with sufficient accuracy for this purpose by assuming that the mean
pressure is half of that due to the surface velocity. Substituting
these numbers, the above equation becomes P = 1,330 X 1.1 X
62.5 X Vtf = ?0-5 tons = ?0 tons with sufficient accuracy. Divid-
ing this by 2 to get the pressure corresponding to the mean velocity,
we have the pressure of the current equal to 35 tons.
Collecting the preceding results, we have:
Wind on truss, 78 tons.
" " train, 78 "
" pier, 7 "
Pressure of ice, . . . : 240 "
" water, 35 "
Total force tending to slide the pier on the foot-
ing = 438 tons.
578. The weight of the bridge will be assumed at 2 tons per
lineal foot; and hence the total weight is 2 tons X 523 = 1,046
tons.
The weight of a train of empty cars is about 0. 5 ton per lineal
* Third Annual Report of the Illinois Society of Engineers, p. 78.
374: BKIDGE PIERS. [CHAP. XVI.
foot; and hence the total weight of the train is 0.5 tons X 523 =
261 tons.
The amount of masonry below the high- water line = 67,946 cu.
ft.; the amount above the high water line = 24,534 cu. ft.; and
hence the total masonry = 92,480 cu. ft. "We will assume the
weight of the masonry to be 150 Ibs. per cubic foot. Then the
weight of the masonry is 150 Ibs. X 92,480 = 6,936 tons.
Collecting these results, we have:
Weight of the bridge, 1,046 tons.
" " " train of empty cars, 261 "
" " " masonry, 6,936 "
Total weight to resist sliding " = 8,243 tons.
Sliding cannot take place, if the co-efficient of friction is equal
to or greater than 438 -~- 8,243 = 0.053. For values of the co-ef-
ficients of friction, see the table on page 315. In the above ex-
ample, the factor of safety against sliding is at least 12 to 15.
579. Stability against Overturning. "We will consider the
stability against overturning about the top of the upper footing
course. The wind on , the truss = 78 tons; the arm of this force =
height of the pier (123 ft.) +»Jialf the depth of the truss (30 ft.) =
153 ft.; and therefore the moment of this force = 78 tons X 153
ft. =11, 9 34 foot-tons.
The pressure of the wind on the train = 78 tons; and the arm
of this pressure = distance from footing to top of pier (123 ft.) +
distance from top of pier to top of rail (8 ft.) -f- distance from top
of rail to center of train (8 ft.) = 139 ft. Therefore the moment
of this pressure is 78 tons X 139 ft. = 10,842 foot-tons.
The pressure of the wind against the pier is 7 tons (§ 577); the
arm of this force = £ (202 + 150) — 79 = 97 ft. ; and the moment of
this force = 679 foot-tons.
The pressure of the ice is 240 tons, the arm is 70 ft., and the
moment is 16,800 foot-tons.
The pressure of the water is 35 tons. The center of pressure
lies somewhere between one third and one half of the depth from
the top; and as the increased area at the base of the pier compen-
sates in part for the decrease of velocity with the depth, we will as-
sume that it is at half the depth. The arm then is 36 ft., and the
moment is 35 tons X 36 ft. = 1,260 foot-tons.
ART. l.J THEORY OP STABILITY. 375
Collecting these results, we have:
Moment of the wind on the truss, . . . 11,934 foot-tons.
" " " " " tniin, . . . 10,842
" " " " 4* " pier, .... 079
tf " pressure of the ice, . . . 16,800
" " " " 'l " current . . 1,200 "
Total overturning moment ..... =41,515 foot- tons.
580. The total weight above the joint considered is (§ 578)
8,243 tons. This force acts vertically down through the center of
the pier; hence the arm is 31.5 ft., and the total moment resisting
overturning is 8,243 X 31.5 = 259,654 foot-tons. The factor of
safety against overturning about the top of the upper footing
course in 259,054 -*- 4l,,51f> = 0.3.
Assuming the train to be of! the bridge, and that the wind
pressure on the truss is 50 ll>s. per sq. ft., and following the method
pursued above, it is found that the factor of safety against sliding
under these conditions is (5.4.
581. Stability against Crushing. The maximum pressure on
the section will occur when the loaded train is on the bridge and
all the horizontal forces arc acting with their full intensity. The
loud when an cniplij train is on the bridge is (§ 57H) 8,243 tons.
Assuming that a loaded train will weigh, 1 J tons per lineal foot, we
must add (0.75 tons X 523 =) 392 tons to the above for the
difference between a loaded and an unloaded train. Then the total
direct pressure is 8,243 •{- 392 = 8,035 tons. The area of the sec-
tion at the top of the footing course is 1,100 sq. ft. Hence, the
maximum direct pressure is 8,035 ~- 1,100 — 7.4 tons per sq. ft.
The moment to overturn, J/, =41,515 foot-tons. The greatest
length of the section = (53 ft. The moment of inertia of the sec-
tion about an axis through its (tenter and perpendicular to its
length = 287,917 (ft.). From & 575, the maximum pressure
Substituting the above quantities in this equation gives
./> = 7.4 + 'llxM*u j!I = 7-4 + 4.5 = 11.9 tons per sq. ft.
Since it is highly improbable that all the forces will act at the
flame time with the intensity assumed in the preceding computa-
376 BKIDGE PIERS. [CHAP. XVI.
tions, we may conclude that the pressure will never exceed 11,9
tons per sq. ft. A comparison of this with the values of the com-
pressive strength of masonry as given in § 222 (page 149) shows
that this pressure is entirely safe.
Since this is an unusually high pier under an unusually long
span, and since the overturning and resisting moments and also the
top dimensions of the pier vary with the span, we may draw the-
conclusion that any pier which has sufficient room on top for the
bridge seat (§ 584) and which has a batter 0/1 in 12,, or 1 in 24,, is
safe against am/ mode of failure.
582. Pressure on the Bed of the Foundation. The caisson-
is 70 feet long, 30 feet wide, and 50 feet high. The load.
on the base is equal to the weight on the top of the footing plus
the weight of the footings plus the weight of the caisson.
The weight above the footing =• 8,635 tons (§ 581). The weight
of the footings = 1,300 sq. ft. X 4 ft. X 150 Ibs. = 390 tons. The
weight of the caisson = 70 ft. x 30 ft. x 50 ft. x 100 Ibs. = 5,250
tons. The total weight on the bed = 8,635 + 390 + 5,250 = 14,-
275 tons. The area = 70 ft. X 30 ft. = 2,100, sq. ft. The direct
pressure per unit of area = 14,275 -f- 2,100 = 6.8 tons per sq. ft.
The overturning moment, M, is equal to the moment about the
top of the footing (§ 581) plus the product of the sum of the hori-
zontal forces and the distance from the footing to the base of the
caisson; or, the moment about the base = 41,515 foot-tons + 438
tons X 54 ft. = 65,167 foot-tons. The moment of inertia, /, =
^ 30 (70)3 = 857,500 (ft.). I = 70 ft. The concentrated pressure
caused by the tendency to overturn is
Ml 65,167 X 70 .
The caisson was sunk all the way through, and rests, on sand ;
consequently the water will find its way freely under the entire
foundation, thus causing buoyancy to act with its full force. This
upward force of the water will be equal to the volume of the im-
mersed masonry multiplied by the weight of a cubic foot of water;
or the buoyancy = (67,946 + 5,200 + 105,000) X 62.4 = 5,558 tons,
The lifting effect of buoyancy is (5,558 -=- 2,100 =) 2.62 tons per
sq. ft.
Therefore, the total pressure is not greater than 6.8 + 2.7 — 2. G
= 6.9 tons per sq. ft.
ART. 2.] DETAILS OF CONSTRUCTION. 37?
The pressure would never be so much, for the following reasons :
1. There is no probability that both spans will be covered by a train
of maximum weight at the same time that the maximum effects of
the wind., of the current, and of the ice occur. 2. The friction on
the sides of the caisson will sustain part of the load. A friction of
600 Ibs. per sq. ft., which was about the amount experienced in
sinking these piers (see § 455), would decrease this pressure about
1|- tons per sq. ft.
Therefore, we conclude that the pressure on the sand will be at
least as much as 6.8 — 1.5 — 2.6 = 2.7 tons per sq. ft.; and that it
may possibly, but not probably, amount to 6.8 -j- 2.7 — 2.6 — 1.5 =
5.4 tons per sq. ft. The larger value was taken at the greatest pos-
sible one for the sake of establishing the conclusion stated in the
last paragraph of § 581.
583. Other 12xaMjpks. At the St. Louis steel-arch bridge
the greatest pressure possible on the deepest foundation (bed-
rock) is 19 tons per sq, ft. The pressure at the base of the
New York tower of the East "River suspension bridge is about
7-J tons per sq. ft. upon a stratum of sand 2 feet thick overlying
bed-rock ; and at the base of the nwonry the pressure is about Up-
tons per sq. ft.* The corresponding quantities for the Brooklyn
tower were a little over a ton less in each case. At the Plattsmouth
bridge f the maximum pressure caused by the weight of train, bridge,
and pier is 3 tons per sq. ft. At the Bismarck bridge f the pressure
due to the direct weight is 3 tons per sq. ft. on clay.
ART. 2. DETAILS OF CONSTRUCTION*.
584. TOP DIMENSIONS. The dimensions on the top will depend
somewhat upon the form of the cross section of the pier, and also
upon the style and span of the bridge; but, in a general way, it may
be stated that, for trussed spans of 100 ft. or over, the dimensions
.under the coping will not be less than 5 ft. X 20 ft.; for 250-ft.
spans, 8 ft. X 30 ft.; and for 500-ft. spans, 10 ft. X 40 ft. Appar-
ently 6 ft. X 22 ft. under the coping is the favorite size for spans of
100 to 200 ft.
*F. Collingwood, assistant engineer, in Van Nostrand's Engin'g Mag., vol. xvi.
p. 431.
t Report of Geo. S. Morison, chief engineer.
378 BRIDGE PIEES. [CHAP. XVI.
585. BOTTOM DIMENSIONS. Theoretically the dimensions at the
"bottom are determined by the area necessary for stability; but the
top dimensions required for the bridge seat, together with a slight
batter for the sake of appearance, gives sufficient stability (§ 581).
Only high piers for short spans — a combination not likely to occur
in practice — are liable to fail by overturning or crushing.
586. BATTER. The usual batter is 1 inch to a foot, although 4-
an inch to a foot is very common. In high piers it is customary to
use a batter of 1 to 24, and offset the masonry and introduce a water-
table at the high- water line, so as to give an average batter of about '
1 to 12. This construction very much improves the appearance,
and does not add materially to the cost.
A corbel course, or ''belt course/' is sometimes introduced im-
mediately under the coping for appearance's sake. For an exam-
ple, see Fig. 85 (page 372), Fig. 87 (page 383), and Fig. 88 (page
384).
587. CROSS SECTION. The up-stream end of a pier, and to a
considerable extent the' down-stream end also, should be rounded
or pointed to serve as a cut-water to turn the current aside and to
prevent the formation of whirls which act upon the bed of the
stream around the foundation, and also to prevent shock from ice,
logs, boats, etc. In some respects the semi-ellipse is the best form
for the ends ; but as it is more expensive to form, the ends are
usually finished to intersecting arcs of circles (see Figs. 85, 87, and
89 — pages 372, 383, and 385, respectively), or with semi-circulai
ends. Above the high-water line a rectangular cross section is as
good as a curved outline, except possibly for appearance.
A cheaper, but not quite as efficient, construction is to form the
two ends, called starlings, of two inclined planes. As seen in
plan, the sides of the starlings usually make an angle of about 45°
with the sides of the pier (see Fig. 90, page 386). A still cheaper
construction, and the one most common for the smaller piers, is to
finish the up-stream end, below the high-water line, with two in-
clined planes which intersect each other in a line having a batter of
from 3 to 9 inches per foot, and build the other three sides and the
part of the up-stream face above the high-water line with a batter
of 1 in 12 or 1 in 24. Of course the simplest construction is to
make the pier rectangular in horizontal cross sections and give it the
same batter on all faces.
ART. 2.] DETAILS OP CONSTRUCTION. 379
Occasionally, for economy, piers, particularly pivot piers, are
built hollow — sometimes with and sometimes without interior cross
walls (see Fig. 86, page 380). The piers of the bridge across the
Missouri Kiver at Glasgow, Mo., are solid up to the high-water line,
und above that each pier consists of two stone columns. The piers
of the bridge over the Missouri at St. Charles, Mo., have a somewhat
•similar construction, except that the secondary piers are connected
by a comparatively thin wall.
With piers subjected to a severe pressure from ice, it is customary
to protect the edge of the nose with an angle-iron or a railroad rail.
588, PIVOT PIERS. These differ from the ordinary piers only
in that they are circular, are larger on top, and have plumb sides.
Pivot piers are about 25 to 30 feet in diameter, under the coping,
for spans of 250 to 350 feet, respectively.
Fig. 86 shows the pivot pier for the Northern Pacific E. E.
bridge over the Eed Eiver at Grand Forks, Dakota. The specifica-
tions for the grillage were as follows: "Fasten the first course of
timbers together with |-inch X 20-inch drift bolts, 18 inches apart;
fasten second course to first course with drift bolts of same size at
every other intersection. Timbers to be laid with broken joints.
Put on top course of 4-inch x 12-inch plank, nailed every 2 feet
with -iV-inch X 8-inch boat spikes. The last course is to be thor-
oughly calked with oakum."
Pivot piers are protected from the pressure of ice and from
shock by boats, etc., by an ice breaker which is entirely distinct
from the pier. The ice breaker is usually constructed by driving a
group of 60 or 70 piles in'the form of a V (the sharp end up stream),
iit a short distance above the pier. On and above these piles a
strong timber crib-work is framed so as to form an inclined ridge
up which the cakes of ice slide and break in two of their own weight.
Between the ice breaker and the pier two rows of piles are driven,
on which a comparatively light crib is constructed for the greater
security of the pier and also for the protection of the river craft.
589. QJJALITY OF MASONRY. Bridge piers are usually quarry-
faced ashlar, i. e., first-class masonry (see § 207) backed with rubble.
Good concrete, if made with reasonable care, is equally as good as
ordinary rubble masonry, and is sometimes cheaper, — since it affords
an opportunity to use up the refuse from the quarry.
380
BRIDGE PIERS.
[CHAP.
AKT. 2.] DETAILS OF CONSTRUCTION. 381
For an illustrated description of the method of building concrete
"bridge piers, see Engineering News, vol. xix. pp. 443-44.
590. SPECIFICATIONS. The following specifications for the ma-
sonry of the railroad bridge over the Missouri River near Sibley, Mo.,
(Octave Chanute, engineer) may be taken as an example of the best
practice.*
591. General Requirements. " The stone to be used in these piers must be
of what is known as the best quality of Cottonwood limestone, or other stone
which, in the opinion of the engineer, is of equally good quality and in every
way suitable for the purpose for which it is to be used. It must be sound and
durable, free from all drys, shakes, or flaws of any kind whatever, and must
be of such a character as will, in the opinion of the engineer, withstand the
action of the weather. No stone of an inferior quality will be accepted or
even permitted to be delivered upon the ground. The masonry in the bridge
piers must be of the best and largest stones that the quarry will afford, and
must be quarried in time to season against frost before being used.
" The face stones composing the starling, and the ends and sides of the river
piers from the neat line about low water up for a distance of twelve (12; feet,
and also the pedestal blocks of the main piers will be of Minnesota granite,
or a granite of equal quality approved by the engineer.
<( All masonry of the main piers shall be regular coursed ashlar of the best
description, and must be laid in mortar of the proportions of sand and cement
hereinafter specified.
" All stones must be so shaped that the bearing beds shall be parallel to the
natural beds, and be prepared by dressing and hammering before they are
brought on the walls, as tooling and hammering will not be allowed after the
stones are in place. They are to be laid to a firm bearing on their natural beds
in a full bed of mortar,, without the use of chips, pinners, or level ers. No
shelving projections will be allowed to extend beyond the under bed on either
side. The stone and work are to be kept free from all dirt that will interfere
with the adhesion of mortar. Stones must be sprinkled with water before
being placed in position on the wall. In laying stone in mortar, their beds are
to be so prepared that when settled down they may rest close and full on the
mortar. In handling the stones care must be used not to injure the joints of
those already laid; and in case a stone is moved after being set and the joint
broken, it must be taken out, the mortar thoroughly cleaned from the beds,
and then reset.
" Wherever the engineer shall so require, stones shall have one or two 1£-
iuch iron dowels passing through them and into the stones below. The holes
for the dowels shall be drilled through such stones before they are put in
position on the walls. After the stones are in place the holes shall be con-
tinued down into the under stones at least six (6) inches ; the dowel pins will
then be set in and the holes rilled with neat cement grout. Clamps binding
* For specifications for first-class masonry, see § 207 ; see also Appendix I.
S82 BRIDGE PIERS. [CHAP. XVI,
the several stones of a course together may be inserted when required by the
engineer ; in such case they will be counter-sunk into the stones which they
fasten together.
592. Face Stones. " The face stones must be accurately squared, jointed,
and dressed on their beds and builds ; and the joints must be dressed back at
least twelve inches (12) from the face. Face stones are to be brought to a joint,
when laid, of not more than three quarters (f) of an inch nor less than one
half (i) inch. The courses shall not be less than eighteen (18) inches in thick-
ness, decreasing from bottom to top of the wall. Courses to be well bonded.
The face stones shall break joints at least twelve (12) inches. The face stones
may be left rough, except the stones forming the starling, which must be care-
fully dressed to a uniform surface. The edges of face stones shall be pitched
true and full to line, and on corners of all piers a chisel draft one and a half
(!•£) inches must be carried up from base to the under side of the coping. No
projection of more than three (3) inches from the edge of face stones will be
allowed. JN"o stone with a hollow face will be allowed in the work.
593. Stretchers. "Each stretcher shall have at least twenty (20) inches
width of bed for all courses of from eighteen (18) to twenty (20) inches rise,
and for all thicker courses at least as much bed as rise ; and shall have an
average length of at least three and one half (3-0 feet, and no stretcher shall be
less than three (3) feet in length.
594. Headers. "Each header shall have a width of not less than eighteen,
inches (18) and shall hold, back into the heart of the wall, the size that it shows
on the face. The headers shall occupy at least one fifth ($} of the whole face
of the wall, and be, as nearly as practicable, evenly distributed over it, and be
so placed that the headers in each course shall divide equally, or nearly so, the
spaces between the headers in the course directly below. In walls over six
feet X6) in thickness, the headers shall in no case be less than three and one half
feet (3£) long; and in walls over nine (9) feet thick, the headers shall be equal
in length to one third the thickness of the wall, except when this length of
header exceeds six (6) feet, — no header over six (6) feet long being required.
595. Backing. " The headers must alternate front and back, and their
binding effect be carried through the wall by intermediate stones — not less in
length and thickness than the headers of the same course — laid crosswise in
the interior of the wall. The stretchers and all stones in the heart of the wall
shall be of the same general dimensions and proportions as the face stones,
,-uid shall have equally good bed and bond, but may have less nice vertical
joints,— although no space greater than rive (5) inches in width shall be left be-
tween stones. All stones in the backing must be well fitted to their places,
and carry the course evenly quite through the wall.
596. Coping. " Tlie tops of the bridge piers, cap stones of the pedestals,
and such other parts of the masonry as the engineer shall direct, shall be cov-
ered with coping of such dimensions as prescribed. All coping stones shall
be neatly bush-hammer dressed on the face, bed, top, and joints; and shall be
well and carefully set on the walls, brought to one quarter (i) inch joints, and,
ABT. 2.]
DETAILS OF CONSTRUCTION.
383
FIG. 87. — CHANNEL PIER, BLAIR BRIDGE.
384
BEIDGE PIERS.
[CHAP. XVI.
if required, be doweled, the dowels being well secured iu and to the coping
ivith grout. No coping stone shall be less than nine (9) square feet on top.
597. Pointing. " All masonry is to be pointed so as to fill the joints solid.
The surface of the wall is to be scraped clean and the joints freed of all loose
mortar and refilled solid by using proper ramming tools. Joints must be well
wet before being pointed. Mortar used in pointing is to be composed of one
part Portland cement and one part sand.
598. Cement. " The cement used in the work shall be equal in quality to
the best brands of Milwaukee or Louisville cement, and shall be ground so
that at least 90 per cent, in weight will pass a standard sieve of 2,500 meshes
to the square inch, and shall have a tensile strength — after being exposed one
liour, or until set, in air, and the balance of the twenty-four hours in water not
i i
i r
i i
-4-3' 0"-
n
•*-4v3**| fc--/0' 4~ J
FIG. 88.— Top OF PIER, HENDERSON BRIDGE.
"below 60° F. — of at least 40 pounds per square inch; and, after being exposed
one day in air and six days iu water, from 60 to 100 pounds per square inch.
"All cements shall be furnished by the contractor subject to approval by
the engineer. The contractor shall provide a suitable building for storing the
cement, in which the same must be placed before being tested. The engineer
shall be notified of the receipt of cement at least three days before it is required
for use, and the inspector may take a sample from each package for testing.
599. Mortar. " The mortar shall be composed of the above cement and
clean, dry, sharp sand in the proportion of one part cement to two parts of
sand by weight.* The sand and cement shall be thoroughly mixed dry, and,
after adding sufficient water to render the mass plastic, shall be mixed and
worked until of uniform consistency throughout.
"Mortar remaining unused so long as to have taken an initial set shall not
l>e used in the work.
* This is an unusual, but exact, method of specifying proportions ; they are
usually stated in volumes.
ART.
DETAILS OF CONSTRUCTION.
600. Pedestal Masonry. " The pedestals shall be founded upon a bed of
•concrete or upon piles, as may be directed by the engineer. The masonry in
the pedestals shall be of the best de-
scription of coursed ashlar composed of
the limestone and the mortar described
above, the stones to be not less than
twelve (1:3) inches thick, and to have
horizontal beds and vertical joints on
the fa.ee. When the walls do not ex-
eeed three and one half («H) feet in
thickness, the headers shall run entirely
through, or a single stone ••—square and
•of the proper thickness— may be. used.
In walls over three and one half (!U)
feet, in thickness, and not over seven
(7) feet- in thickness, headers and
stretchers shall alternate, and there
.shall be as many headers as stretchers.
The space in the interior of the walls
shall be filled with a single atone, cut
to tit such space, and said stone shall
he of the same height as the headers
and stretchers of the course. In all the
masonry of these, pedestals the slope
must be curried up by steps and in ac-
oordnncc with the plans of theen^ineer.
All the quoins must have hammer-
dressed beds, builds, and joints, and
draft corners."
801. EXAMPLES OF BRIDGE
PlEES. Fig. H:> (page 372) .shows
the channel pier of the lllinoin
Central R. H. bridge over the
Ohio at Cairo, III.
Fig. H(J (page 380) nhoWH the
pivot pier of the Northern Pacific
It K. bridge over the Red River
at (traiid Forks, Dakota*
Fig. H7 (page 383) shows one
of the two channel piers of the
bridge*, over the Minsouri River,
near Blair, Neb.* Thin pier stands between two 33()~ft. spans.
* From the. Keport of (»«o. S. Morion, ehiof engineer of the
386
BRIDGE PIERS.
[CHAP. XYI.
JBcuse
_ -i |ay i 4--
V*V»v»N
niir T TT MM TITI iTirn MI MI
nn
in
I I I M I i I I I I I I I I I I I 1 I I 1 M 1 I I I I
FIG. 90.— PJEB OF ST. CEOIX RIVER BRJDOB.
ART. 2.] DETAILS OF CONSTBTJCTION. 387
cc The vertical joints are shown as they actually are in the struct-
ure." The masonry is 145 ft. from top to bottom.
Fig. 88 (page 384) shows the top of the pier between two 525-ft.
channel spans of the Louisville and Nashville K. K. bridge across
the Ohio River at Henderson, Ky.
Fig. 89 (page 385) shows the actual arrangement of the stones in
one of the courses of one of the channel piers (Fig. 85) of the Illinois
Central R. E. bridge over the Ohio River, at Cairo, 111.
602. Fig. 90 (page 386) shows the river pier of the Chicago, Bur-
lington and Northern R. R. bridge across the St. Croix River. This
pier stands between a draw of 370 feet and a fixed span of 153 feet.
The thickness of the courses is as follows, in order from the bottom
up : Two courses, including the footing, 28 inches ; two 26 inches ;
one each 24, 22, 21, 19, and 17 inches ; two 15 inches ; four 14
inches ; one 13 inches ; one 12 inches ; and the coping 18 inches.
The following table gives the quantity of masonry in the pier and
illustrates the manner of computing the contents of such structures.
Notice that the order in the table is the same as that in the pier ;
•L e.f the top line of the table relates to the uppermost masonry, etc.
TABLE 40.
CONTENTS OF THE PIER SHOWN IN FIG. 90 (page 386).
DESCRIPTION.
DIMENSIONS.
CUBIC
FEET.
Stringer Rests. .
2 X 2.75' X 3.0' X 3.13'
51.6
Bridge Seats
CopiUff
2 X 2.75' X 3. 0' X 1.46'
75'X240'X15'
24.1
270.0
"NTpof "Wnrlr
1(2 V 6 5' 4- 8 6") 23' -I- (2 V 8 6' 4-6 5'} 25 i'l ^
4 579 7
tt it
1ft 1 7'
(2 X 8 6' + 71')38' x
279.6
Ice Breaker. . . .
6
(8. 6' X 3.6')/— 4- 1.0'\
17.3
tt tt
Footing Course.
i (3.6' X 3.6' + 4.3' X 4.3') 18.17'
9 6' X29.4' X 2.33'
285.8
658.5
4.8' X 4. 8' X 2.33'
53.8
Total = 230.39 cubic yards =
6,220.4
603. Iron Tubular Piers. For a description of an iron tubular
pier, see § 415 ; and for a description of a pier founded upon screw
piles, see Engineering News, vol. xiii. pp. 210-12.
388 BRIDGE PIERS. [CHAP. XVI.
604. Timber Barrel Piers. The Chicago, Burlington and Qurncy
E. E. has constructed a few "barrel piers" as an experiment, the
object being to reduce the cost of foundations, and also to find some
cheap substitute for masonry. The barrels are cylindrical, 8 feet in
diameter, and 20 to 30 feet in length. The staves are 10 inches
thick, 8 inches wide on the outside, and are dressed to fit together
to form a cylinder. The staves are bolted at the top and bottom
to two inside rings made of I-beams, and are further held in place
by strong outside hoops of iron. These caissons or barrels are sunk
by excavating the soil from the inside. The bottom and top por-
tions of the caisson are filled with concrete, and the intermediate
portion with sand. On top of the wooden barrel, an iron frame is
placed, upon which the truss rests. Two barrels constitute a pier.
The advantages claimed for the wooden caissons are that they can
be put in without interfering with traffic, or without loss of time in
sinking by the passage of trains. The objection to them is that they
are not durable.
605. CONTENTS OF BRIDGE PIERS. The table on page 389 gives
the quantity of masonry in bridge piers having rectangular cross
sections and such dimensions on top and batters as occur most
frequently (see §§ 584-87). The quantities in the first four columns
cover most of the cases for highway and single track railway bridges;
and the quantities in the last two columns are applicable to double
track railway bridges. Since that portion of the pier below the
water should have more or less pointed ends, and since there is
likely to be an offset in the profile — particularly of high piers, —
the quantities in the table (being for a rectangular cross section) are
mainly useful in making preliminary estimates.
The contents of piers of other dimensions than those in the table
may be computed by the following formula : *
contents = t hi + 1} (I + t) h* -f 14 b*ks,
in which I = the length on top under the coping,
t = il thickness on top under the coping,
7i.= " height to the under side of the coping,
J = " batter—/, c., I = ^ or fa.
The length on the bottom = l + 2~bh; and the thickness on the
bottom '=:l + 26 h. To illustrate the method of applying this for-
* See foot-note, page 358.
AKT. 2.]
DETAILS OF CONSTRUCTION.
389
TABLE 41.
CONTENTS OF BRIDGE PIERS HAVING RECTANGULAR CROSS SECTION AND
THE SAME BATTER ON ALL PACES.
HEIGHT—-
TOP OF
FOOTING
TO BOTTOM
OF
COPING.
DIMENSION OF THE PIER ON TOP UNDTCR THE COPING.
5 ft. x 20 ft.
6 ft. x 22 ft.
Cft. x
34ft.
Batter 1 : 24
Batter 1 : 12
Batter 1 : 24
Batter 1 : 12
Batter 1 : 24
Batter 1 : 12
feet.
cu. yds.
cu. yds,
en. yds.
cu. yds.
cu. yds.
cu. yds.
5
20.49
19.49
26.64
25.53
40.90
3Q.33
0
25.07
23.63
32.51
30.90
49.84
47.57
7
29.83
27.85
38.57
36.36
59.05
55.93
8
34.74
32.13
44.81
41.90
68.52
64.43
9
39.84
36.52
51.24
47.55
78.28
73.04
10
45.09
40.97
57.86
53.28
88.23
81.80
11
50.53
45.51
64.67
59.09
98.50
90.68
12
56.14
50.14
71.69
65.02
109.02
99.68
13
61.93
54.85
78.89
71 . 02
119.83
108.88
14
67.91
59.64
86.31
77.13
130.90
118.09
15
74.07
64.52
93.92
83.33
142.25
127.49
It)
80.40
69.48
101.72
89.61
153.88
137.03
' 17
86.93
74.53
109.75
96.00
165.79
146.69
18
93.65
79.66
117.98
102.49
377.99
156.49
19
100.56
84.87
126.43
109.06
190.45
166.40
20
107.66
90.18
135.07
115.72
203.22
176.47
21
114.96
95.57
143.94
122.49
216.28
186.67
2*3
122.46
101.06
153.01
129.36
229.60
196.98
23
130.15
!()(). 02
162.33
136.34
243.24
207.45
24
138.04
1.12.27
171.84
143.39
257.17
218.05
25
146.14
118.03
181.56
150.53
2n.39
228.79
20
154.45
123.86
191.53
157.79
285.91
239.65
27
162.96
329.79
201.74
165.17
300.74
250.67
28
171.69
135.81
212.18
172.63
315.87
261.82
29
180.62
141.93
222.79
180.18
331.27
273.09
80
189.77
14.8.12
233.68
187.8")
347.01
284.51
82
208.72
160.81
256.15
203.47
379,42
307.78
34
228.54
173.86
"279.58
219.52
4.13.06
881.51)
36
249.26
187,30
303.98
235.98
447.99
355.99
38
270.91
201.12
329.36
252.84
484.17
480.92
40
293.47
215.32
355.74
270.13
521.66
406.43
42
316.98
229.92
383.17
287.88
560.51
432.57
44
341 .46
244.91
411.59
306.02
600.64
459.23
46
366.90
2(50.29
441.05
324.60
642.15
486.47
48
393.36
276.00
471.66
343.66
684.99
514.33
50
420.82
292.29
503.32
363.13
729.24
542.78
52
449.33
308.90
536.07
383.08
774.88
571.80
54
478.86
325.93
569.96
403.45
821.98
601.47
5«
509.45
343.38
604.96
424.29
870.45
631.71
58
541.13
361.24
641.11
445.57
920.41
602.57
60
573.85
379.52
678.48
467.42
| 971.78
694.02
390 BRIDGE PIERS. [CHAP. XVI.
mula, assume that it is required to find the contents of a pier 4 feet
thick, 20 feet long on top, and 30 feet high, having a batter on
all four faces of 1 inch per foot. Then I = 20, t = 4, b = TV, and
the preceding formula becomes
contents = 4 X 20 X 30 + T\ (20 + 4) (30)2 + f X Tf ¥ X (30)3
=4,450 cubic feet.
606. COST. For a general discussion of the cost of masonry, see
§§ 226-38 (pp. 153-60) ; and for data on the cost of bridge pier
masonry, see § 235 (p. 157).
CHAPTER XVIL
CULVERTS.
ART. 1. WATER WAY REQUIRED.
607. The determination of the amount of water way required in
any given case is a problem that does not admit of an exact mathe-
matical solution. Although the proportioning of culverts is in a
measure indeterminate,, it demands an intelligent treatment. If
the culvert is too small, it is liable to cause a washout, entailing
possibly loss of life, interruptions of traffic, and cost of repairs.
On the other hand, if the culvert is made unnecessarily large, the
cost of construction is needlessly increased. Any one can make a
culvert large enough ; but it is the province of the engineer to
design one of sufficient but not extravagant size.
608. THE FACTOKS. The area of water way required depends
upon (1) the rate of rain-fall, (2) the kind and condition of the
soil, (3) the character and inclination of the surface, (4) the condi-
tion and inclination of the bed of the stream, (5) the shape of the
area to be drained and the position of the branches of the stream,
(6) the form of the mouth and the inclination of the bed of the
culvert, and (7) whether it is permissible to back the water up above
the eulvert, thereby causing it to discharge under a head.
1. It is the maximum rate of rain-fall during the severest storms
which is required in this connection. This certainly varies greatly
in different sections ; but there are almost no data to show what it is
for any particular locality, since records generally give the amount
per day, and rarely per hour, while the duration of the storm
is seldom recorded. Further, probably the longer the series of
•observations, the larger will be the maximum rate recorded, since
the heavier the storm the less frequent its occurrence ; and hence a
record for a short period, however complete, is of but little value
in this connection. Further, the severest rain-falls are of compara-
tively limited extent, and hence the smaller the area, the larger the
391
392 CULVERTS. [CHAP. XVII,
possible maximum precipitation. Finally, the effect of the rain-fall
in melting snow would have to be considered in determining the
maximum amount of water for a given area.
2. The amount of water to be drained off will depend upon the
permeability of the surface of the ground, which will vary greatly
with the kind of soil, the degree of saturation, the condition of
cultivation, the amount of vegetation, etc.
3. The rapidity with which the water will reach the water
courses depends upon whether the surface is rougher smooth, steep
or flat, barren or covered with vegetation, etc.
4. The rapidity with which the water will reach the culvert
depends upon whether there is a well-defined and unobstructed
channel, or whether the water finds its way in a broad thin sheet.
If the water course is unobstructed and has a considerable inclina-
tion, the water may arrive at the culvert nearly as rapidly as it
falls ; but if the channel is obstructed, the water may be much
longer in passing the culvert than in falling.
5. Of course, the water way depends upon the amount of area
to be drained ; but in many cases the shape of this area and t he-
position of the branches of the stream are of more importance than
the amount of the territory. For example, if the area is long and
narrow, the water from the lower portion may pass through the
culvert before that from the upper end arrives ; or, on the other
hand, if the upper end of the area is steeper than the lower, the
water from the former may arrive simultaneously with that from
the latter. Again, if the lower part of the area is better supplied
with branches than the upper portion, the water from the former
will be carried past the culvert before the arrival of that from the
latter ; or, on the 'other hand, if the upper portion is better supplied
with branch water courses than the lower, the water from tho
whole area may arrive at the culvert at nearly the same time. Li
large areas the shape of the area and the position of the water
courses are very important considerations.
6. The efficiency of a culvert may be materially increased by so-
arranging the upper end that the water may enter it without being"
retarded (see § 639). The discharging capacity of a culvert can
also be increased by increasing the inclination of its bed, provided
the channel below will allow the water to flow away freely after
ART. 1. J AYATER WAY REQUIRED. 393
having passed the culvert. The last, although very important, is
frequently overlooked.
7. The discharging capacity of a culvert can be greatly increased
by allowing the water to dam up above it. A culvert will discharge
twice as much under a head of 4 feet as under a head of 1 foot.
This can only safely be done with a well-constructed culvert.
609. FORMULAS. The determination of the values of the differ-
ent factors entering into the problem is almost wholly a matter of
judgment. An estimate for any one of the above factors is liable
to be in error from ,100 to 200 per cent.,, or even more, and of
course any result deduced from such data must be very uncertain.
Fortunately, mathematical exactness is not required by the problem
nor warranted by the data. The question is not one of 10 or 20
per cent, of increase ; for if a 2-foot pipe is insufficient, a 3-foot
pipe will probably be the next size — an increase of 225 per cent., —
and if a 6-foot arch culvert is too small, an 8-foot will be used —
an increase of 180 per cent. The real question is whether a 2-foot
pipe or an 8-foot arch culvert is needed.
Numerous empirical formulas have been proposed for this and
similar problems ; * but at best they are all only approximate, since
no formula can give accurate results with inaccurate data. The
several formulas, when applied to the same problem, give very
discordant results, owing (.1) to the sources of error already re-
ferred to and (2) to the formulas" having been deduced for localities
differing widely in the essential characteristics upon which the
results depend. For example, a formula deduced for a dry climate,
as India, is wholly inapplicable to a humid and swampy region, as
Florida ; and a formula deduced from an agricultural region is
inapplicable in a city.
However, an approximate formula, if simple and easily applied,
may be valuable as a nucleus about which to group the results of
personal experience. Such a formula is to be employed more as a
guide to the judgment than as a working rule ; and its form, and
also the value of the constants in it, should be changed as subse-
quent experience seems to indicate. With this use in view, a few
formulas will be referred to briefly.
There are two classes of these formulas, one of which purports
* For a general note on empirical formulas, see § 364.
394 CULYEKTS. [CHAP. xvn.
to give the quantity of water to be discharged per unit of drainage
area and the other the area of the water way in terms of the area of
the territory to be drained. The former gives the amount of water
supposed to reach the culvert; and the area, slope, form, etc., of
the culvert must be adjusted to allow this amount of water to pass.
There are no reliable data by which to determine the discharging
capacity of a culvert of any given form, and hence the use of the
formulas of the first class adds complication without securing any
compensating reliability. Most of the formulas in common use for
proportioning water ways belong to this class. Such formulas will
not be considered here.
The two following formulas belong to the second class.
610 Myer's Formula. Of the formulas giving a relation be-
tween the area of water way and the area to be drained, Myer's is
the one most frequently used. It is
Area of water way, in square feet = G ^ 'Drainage area, in acres,
in which 0 is a variable co-efficient to be assigned. For slightly
rolling prairie, C is usually taken at 1; for hilly ground at 1.5; and
for mountainous and rocky ground at 4. For most localities, at
least, this formula gives too large results for small drainage areas.
For example, according to the formula, a culvert having a water
way of one square foot will carry the water from a single acre only.
Further, if the preponderance of the testimony of the formulas for
the quantity of water reaching the culvert from a given area can
be relied upon, the area of water way increases more rapidly than
the square root of the drainage area as required by this formula.
Hence, ifc appears that neither the constants nor the form of this
formula were correctly chosen; and, consequently, for small drainage
areas it gives the area of waterway too great, and for large drain-
age areas too small.
611. Talbot' s Formula. Prof. A. NT. Talbot proposed the fol-
lowing formula, "more as a guide to the judgment than as a work-
ing rule •/' *
Area of water way, in square feet = C y '(Drainage area, in acres)*,
in which C is a variable co-efficient. Data from various States gave
values for 0 as follows: "For steep and rocky ground, C varies
* Selected Papers of the Civil Engineers' Club of the University of Illinois, No. 2,
pp. 14-17.
AET. 1.] WATER WAY REQUIRED. 395
from f to 1. For rolling agricultural country subject to floods at
times of melting of snow, and with the length of yalley three or
four times its width,, (7 is about J; and if the stream is longer in
proportion to the area, decrease C. In districts not affected by
accumulated snow, and where the length of the valley is several
times the width, % or £, or even less, may be used. C should be
increased for steep side slopes, especially if the upper part of the
valley has a much greater fall than the channel at the culvert/"
The author has tested the above formula by numerous culverts
and small bridges in a small city and also by culverts under high-
ways in the* country (all slightly rolling prairie), and finds that
it agrees fairly well with the experience 6f fifteen to twenty years.
In these tests, it was found that water ways proportioned by this
formula will probably be slightly flooded, and consequently be com-
pelled to discharge under a small head, once every four or five
years.
612. In both of the preceding formulas it will be noticed that
the large range of the " constant " 0 affords ample opportunity for
the exercise of good judgment, and makes the results obtained by
the formulas almost wholly a matter of opinion.
613. Practical Method. Valuable data on the proper size of
any particular culvert may be obtained (1) by observing the existing
openings on the same stream, (2) by measuring — preferably at time
of high water — a cross section of the stream at some narrow place,
and (3) by determining the height of high water as indicated by
drift and the evidence of the inhabitants of the neighborhood.
With these data and a careful consideration of the various matters
referred to in § 608, it is possible to determine the proper area of
water way with a reasonable degree of accuracy.
Ordinarily it is wise to take into account a probable increase of
flow as the country becomes better improved. However, in con-
structing any structure, it is not wise to make it absolutely safe
against every possible contingency that may arise, for the expen-
diture necessitated by such a course would be a ruinous and un-
justifiable extravagance. Washouts can not be prevented altogether,
nor their liability reduced to a minimum, without an unreasonable
expenditure. It has been said — and within reasonable limits it is
true — that if some of a number of culverts are not carried away
396 -CULVERTS. [CHAP, xvn,
each year, they are not well designed; that is to say, it is only a
question of time when a properly proportioned culvert will perish
in some excessive flood. It is easy to make a culvert large enough
to be safe under all circumstances, but the difference in cost be-
tween such a structure and one that would be reasonably safe would
probably much more than overbalance the losses from the washing
out of an occasional culvert. It is seldom justifiable to provide for
all that may possibly happen in the course of fifty or one hundred
years. One dollar at 5 per cent, compound interest will amount to
$11.47 in 50 years and "to $131.50 in 100 years. Of course, the
question is not purely one of finance, but also one of safety to human
life; but even then it logically follows that, unless the engineer is
prepared to spend $131.50 to avoid a given danger now, he is not
justified in spending $1 to avoid a similar danger 100 years hence.
This phase of the problem is very important, but is foreign to the
subject of this volume.
614. In the construction of a new railroad, considerations of
first cost, time, and a lack of knowledge of the amount of future
traffic as well as ignorance of the physical features of the country,
usually require that temporary structures be first put in, to be re-
placed by permanent ones later. In the mean time an incidental
but very important duty of the engineer is to make a careful study
of the requirement of the permanent structures which will ulti-
mately replace the temporary ones. The high- water mark of streams
and the effect of floods, even in water courses ordinarily dry, should
be recorded. With these data the proper proportioning of the
water way of the permanent structures becomes a comparatively easy
task. Upon the judgment and ability displayed in this depends,
most of the economical value of the improvements; for, as the road
will have fixed or standard plans for culverts, abutments, piers,
etc., the supervision of the construction will not be difficult.
ART. 2. Box AND PIPE CULVERTS.
615. STONE Box CULVERT. This culvert consists of vertical side
walls of masonry with flag stones on top from one wall to the other.
Masonry box culverts were constructed much more frequently for-
merly than at the present time. The ]ack of suitable stone in many
parts of the West led to the adoption of vitrified pipes (§ G27) and
iron pipes (§ 631) instead of masonry box culverts. However, in
ART. 2.]
STOXE BOX CULVERTS.
397
many localities they are built frequently enough to warrant a brief
discussion here. *
616. Eoundation. A common foundation for masonry box cul-
verts is a stone pavement (§ 219) under the entire culvert, upon
which the side walls rest (see Fig. 91a). This is not good practice ;
for, since the paving is liable to be washed out, it endangers the
FIG. 91a.
FIG. 916.
wall. The tendency of the pavement to undermine may be dimin-
ished (1) by driving sheet piling or by setting deep curb-stones at
both ends, or (2) by extending the paving to a considerable distance
beyond both ends. The first is the better method ; but usually
these devices only postpone, and do not prevent, final failure. The
water is nearly certain to carry the soil away from under the pave-
ment, even if the curb-stones or sheet piles remain intact.
Sometimes culvert foundations are paved by laying large stones
flatwise. This practice is no better than ordinary stone paving, un-
less the flags are large enough to extend under both walls ; but
stones large enough for this can seldom be obtained.
A much better method is to give each side wall an independent
foundation and to pave between the walls only (see Fig. 91&). An
important advantage of this method is that each wall can be placed
separately, which facilitates the keeping, of the water away from the
foundation pit. Indeed, if the foundations are deep, or if there is
not much current, the paving may be entirely omitted. If the cur-
rent is only moderate, it is sufficient to build in, at each end of the
culvert, between the ends of the side walls with solid masonry up
to the bed of the stream ; but if the culvert is long, it is wise to
build one or more intermediate cross walls also. If the current is
strong, the cross walls at the ends should be carried down deep,
and the space between the side walls should be paved with large
stones closely set and deeply bedded. The best job possible is se-
cured by setting the paving in cement mortar. In this connection,
see Figs. 94> 95, and 96 (pages 403, 404, .and 406). . :
398
CULVERTS.
[CHAP,
The side walls and the cross walls (particularly at the end of the
culver tf should have their foundations below the effect of frost.
617. End Walls. The ends of box culverts are usually finished
either with a plane wall perpendicular to the axis of the culvert as
shown in Fig. 95 (page 404), or by stepping the ends off as shown
in Fig. 92. Either form is liable to become clogged and to have
its effectiveness greatly decreased, and probably its own existence
endangered, by drift collected at its upper end. This danger is-
Plan
FIG. 92.
FIG. 93.
considerably decreased by extending the side walls at the upper end
as shown in Fig. 93 and in Fig. 94 (page 403). If the mouth of
the culvert should become stopped with drift, the open top is a well
into which the water may fall. In this way the full discharging"
capacity of the culvert can be maintained. The lower end may be
stepped as shown in Fig. 92.
The wing walls may be made thinner at the outer end, thus pro-
ducing to a small degree the same effect as is obtained in splaying
the wings of arch culverts (see §§ 638-39).
In this connection, see also Fig. 96 (page 406).
61S. Cover Stones. To deduce a relationship between the thick-
ness of the cover stones and the load to be supported, let
T = the thicknessr in inches ;
S = the span, in feet ;
H = the height of bank, in feet, above the top of the culvert ;
R = the modulus of rupture, in pounds per square inch ;
G = the co-efficient of transverse strength (§ 15) ;
W= the total weight of the earth over the cover stone, in pounds.
ART. 2.] STOKE BOX CULVERTS. 399
For simplicity, consider a section of the culvert only a foot long.
The cover stones are in the condition of a beam supported at the
ends and loaded uniformly. By the principles of the resistance of
materials, one eighth of the uniform load multiplied ~by the span is
equal to one sixth of the continued product of the modulus of rup-
ture,, the breadth, and the square of the thickness. Expressing
this in symbols as above, and reducing, gives
8
Ordinarily, earth weighs from 80 to 100 Ibs. per cu. ft., but for
convenience we will assume it at 100 Ibs. per cu. ft., which is on
the safe side ; then W = 100 H S. The maximum moving load for
railroad bridges may be taken at, say, 2 tons per foot of track.
This is distributed over at least 8 square feet ; and hence the live
load is equal to one quarter of a ton, or 500 pounds, per square foot,
i. e. the live load is equal to an embankment 5 feet high. Therefore,
the maximum live load — a locomotive — is provided for by adding 5
feet to the actual height of the embankment. The table on page
12 shows that for limestone R = 1,500. Substituting these values
in equation (1), above, gives for limestone
By substituting the corresponding value of R from the table on
page 12, we have for sandstone
For highways, it is sufficiently exact to drop the 5 under the
radical, L e.3 to neglect the live load ; and equation (1) then becomes
for limestone
, (4)
and for sandstone
T=0.2ZSVH. ........ (5)
The preceding formulas give the thickness which a stone of
average quality must have to be on the point of breaking; and hence
400 CULVERTS. [CHAP. xvii.
in applying them it will be necessary to allow a margin for safety,
•either by selecting the stone or by increasing the computed thick-
ness. If reasonable care is used in selecting the stones,, it is probably
safe to double the thickness found as above. To allow for any given
factor of safety, multiply the thickness found by applying the above
formulas by the square root of the factor of safety. Thus, to allow
for a factor of 4, multiply the thickness found as above by 2 ; for a
factor of 6, multiply by 2 J ; and for a factor of 9, multiply by 3.
619, The thickness of the cover stones does not, however, de-
pend alone upon the depth of the earth, the live load, and the span.
In the first place, the pressure on the cover stone does not vary
•directly as the depth of the earth above it. (a) The earth itself
acts more or less as a beam to support part, at least, of the weight
over the opening. That earth may act thus is proven by the fact
that an excavation can be carried horizontally into an embankment
or side hill without supporting the roof. The beam strength of the
earth increases with the compactness and the tenacity of the soil
and with the square of the height of the embankment above the
roof. This effect would be zero with clean sand ; but, owing to the
nature of that material, it would seldom be employed, for filling over
a culvert. Hence, under ordinary conditions, part of the load is
supported by the beam strength of the earth itself. Therefore, a
low embankment may produce a greater strain in the cover than a
much higher one. (#) The prism of earth directly over the culvert
will be partially supported by the adjacent soil ; that is to say, the
particles of earth directly above the culvert will act more or less as
arches resting upon the earth at the sides of the culvert, thus par-
tially relieving the cover stones. This effect would be greater with
sharp sand than with clay, but would be entirely destroyed by shock,
as of passing trains, (c) The stones at the center of the culvert
would be relieved of part of their load by an action similar to that
mentioned above, whereby the weight over the center of the culvert
is transferred towards its ends. However, the relief caused by this
.action is but slight.
In the second place, the pressure due to the live load "is trans-
mitted downward in diverging lines, thus distributing the weight
over a considerably larger area than that assumed in deducing equa-
tions (2) and (3) above.
In the third place, the cover must be thick enough to resist the
ART. 2.] STOKE BOX CULVERTS. 401
effect of frost, as well as to support the earth, and live load above it.
The freezing, and consequent expansion, of the earth is a force
tending directly to break the cover stones. That this is an impor-
tant consideration is proved by the fact that these stones break
near the ends of culverts as frequently as near the middle, although
the weight to be supported is greater at the latter place.
620. It is impossible to compute, even approximately, the effect
•of the preceding factors ; but experience shows that the thickness
is independent of the height of the embankment, provided there is
sufficient earth over the cover stones to prevent serious shock, — say
.3 feet for railroads and/1 to 2 feet for highways.
The thickness employed on the railroads in States along the
fortieth parallel of latitude is generally about as follows, irrespec-
tive of the height of the bank or of whether the cover is limestone
•or sandstone :
SPAN OF CULVERT. THICKNESS OF COVER.
2 feet, 10 inches.
3 feet, 12 inches.
4 feet, 15 inches.
On the Canadian Pacific E. B., the minimum thickness of cover
stones for spans of 3 feet is 1C inches, and under 3 feet, 14 inches.
621. Quality of Masonry. Box culverts are usually built of
rubble masonry (§ 213) laid in cement mortar. Formerly they were
•often built of dry rubble, except for 3 or 4 feet at each end, which
was laid in mortar. It is now generally held that box culverts
.should be so built that they may discharge under a head without
damage. It is usually ^specified that the cover stones must have a
.solid, well-leveled bearing on the side walls of not less than 15
inches. The most careful constructors close the joints between the
cover stones by bedding spalls in mortar over them.
622. Specifications.* All stone box culverts shall have a water way at least
24- X 3 feet. The side walls shall not he less than two feet (2') thick, and
.shall be built of sound, durable stones not less than six inches (6") thick, laid
in cement mortar [usually 1 part Rosenclale cement to 2 parts sand]. The
walls must be laid in true horizontal courses, but in case the thickness of the
course is greater than 12 inches (12"), occasionally two stones may be used to
make up the thickness. The walls must be laid so as to be thoroughly bonded,
.and at least one fourth of the area of each course must be headers going en-
* Pennsylvania Railroad.
402 CULVERTS. [CHAP. xvn.
tirely through, the wall. The top course must have one half its area of through
stones, and the remainder of this course must consist of stone going at least
one half of the way across the wall from the inside face. The face stones of
each course must be dressed to a straight- edge, and pitched off to a true line.
All of the coping stones of head walls must be throughs, and must have the
upper surface hammer-dressed to a straight edge, and the face pitched off
to a line with margin draft. Cover stones shall have a thickness of at least
twelve inches (12") for opening of three feet (3'), and at least 14 inches (14") for
opening of four feet (4') ; and must be carefully selected, and must be of such,
length as to have a hearing of at least one foot (!') on either wall.
The beds and vertical joints of the face stones for a distance of six
inches (6") from the face of the wall shall be so dressed as to require a mortar-
joint not thicker than three fourths of an inch (£"). Joints between the cov-
ering stones must be not wider than three fourths of an inch (£"), and the
bearing surface of cover stones upon side walls must be so dressed as to-
require not more than a one-inch (1") mortar joint.
The paving shall consist of flat stones, set on edge, at right angles with the
line of the culvert, not less than twelve inches (12") deep, and shall be laid in,
cement mortar and grouted.
623. Examples. The box culvert shown in Fig. 94 (page 403),,
is presented as being on the whole the best (see § 617). The table
accompanying the diagram gives the various dimensions of, and also*
quantities of masonry in, box culverts for different openings. The
former data and the diagrams are ample for the construction of any
box culvert ; while the latter data will be useful in making esti-
mates of cost (§ 626). In the headings of the colums under "Size
of the Openings," the first number is the span of the culvert, and
the second is the clear height of water way. The quantities of
masonry in the table were computed for a cross wall at each end of
the culverts, of the section shown in Fig. 94 ; but in many cases,
this should be 3 feet deep instead of 2, as shown. In using the
table this correction is easily applied.
624. The box culvert shown in Fig. 95 is the one employed in
the construction of the "West Shore R. K."— New York City to-
Buffalo. The data in the table accompanying the diagram give the'
dimensions and quantities of masonry of various sizes. In the head-
ings under "Size of the Openings," the first number is the span of
the opening and the second is its height.
Box culverts of the general form shown in Fig. 95 are sometimes-
built double; i.e., two culverts are built side by side in such a-
manner as to have one side wall in common. The following table
ART. 2.]
STONE BOX CULVERTS.
403
£
•<
#
%
s
SIZE OF THE OPENING.
X
8,a,S>5>!,3, S i
00
T
( d
f/.
s
"^
M
d
.9
1
S.
o
«~4
O
5
a
T-4OJCGCOCO c$ "*"
<H
X
4J
<*-!
X
CO
CO
X
03
00
X
C)
X
c*
osobwooib 5S *"
OOSOCOOO* CO *-
So c~ w w *b £J *""
b b b b b b o or
co t~ c< m *#
b o o o b b w t*
sOOC^Ci^
i
a • c
:::::. ^ .••*.
:;:.:. a • o
\i\\l\ S .£
i I i I : : 5 .1
:::":: 5 ; a>
":::*: 2 ; g
:::: = : !>!§:
:::::: § :«:
S
*$
c
T3
O
1
i
M
5 «
cuP
JS a}
..*- th
2 a
is
a 3
1°
£
DiMEXsiONs:
Extreme width— end view
height •• •*
Thickness of top of side wall
** " bottom of side wall.
I>ng:th of cover stones,...
Thickness of cover stones and cop
CONTESTS:
Masonry in two end walis— from 1
cubic yards ,.
Masonry in the trunk, per foot of
piihip vnrrf*!
404
CULVERTS.
[CHAP. XYII.
*a
0
X
"*
^ 5 ^ 5 C
oooeoo— «
V ^ -s. V if3
CO OS CO CO "
Ci
^S?^
i-cd-^
1-1 THO
TJI
43
^>22P
Tl<
Qj X
g CO
55
O OO O O — «
^ ^ x ^ o>
i- y^ cc co ^
SSfe
sr°'
a *
o ^
H co*
W v
b x
, MM
5 c<
o
^ i x ^ cs
o ?* <o co — •
Ibooww1"1
JO QO CO
0 O 0
a
SI 43
5 S
X
Oi
^ i: ^ 5 S3
o oo o o •- 1
^ ^ ^ ^ o
»ra t^ oi CM "
TJ 00
g|§^
<?j o d
<M
i-llCI
Oi
X
ot
So ot b b •«
^ ^ x 0
OJ l~ W <M «
os do
V
^
§!
c -~
"~" «r
11
•s?
(!_, (W
o o
03 «
«g
« =.s
IOG
kao) ^
oTJjS
§
B
"5.3.2
"'dC
.sis
I-S
•a||
c S ®
O— t""1
"ioo
3 -• *J
DIMENSIONS:
End wall, length of
11 '* height of . ..
" " thicknessof.
Side wall,
Cover stones, " " .
CONTENTS:
Masonry in two end wal
Masonry in trunk, per f
Paving in trunk, per foe
AET. 2.]
STOKE BOX CULYEKTS.
405
gives the dimensions and quantities for such box culverts. The
dimensions not given in the following table are the same as in the
table accompanying Fig. 95.
TABLE 44.
DIMENSIONS AND CONTENTS OF DOUBLE Box CULVEBTS.
ITEMS.
2X 2£
feet.
2iX 3
feet.
2* X 8J
feet.
3X4
feet.
4X5
feet.
DIMENSIONS:
End wall, length of . .
16' 6"
OQ/ Q'f
20' 0"
°3' 0"
30' 0"
Center wall, thickness of
2' 0"
2' 0"
2' 0"
*V g//
g/ 0"
CONTENTS:
Masonry in two end walls, in cu. yds. .
13 16
16 18
21 50
32 18
53 25
Masonry in trunk, per foot of length from in-
side to inside of end walls, in cu. yds
Paving in trunk, per foot of length from inside
to inside of end walls, in cu. yds
0.864
0 407
0.982
0 444
1.222
0 481
1.778
0 592
2.565
0 703
SIZE OF THE OPENING.
The standard double box culvert employed in the construction
of the Canadian Pacific B. R. differed from the form described
above in having (1) shorter end walls, and wings at an angle of 30°
with the axis of the culvert, and (2) a triangular cut-water at the
upper end of the division wall.
625. The culvert shown in Fig. 96 is the standard on the Inter-
colonial Railway of Canada, and is very substantially constructed.
626. Cost. "With the data accompanying Figs. 94 and 95 (pages
403 and 404), and the table of cost of masonry on page 160, it is
an easy matter to make an estimate of the cost of a box culvert.
For example, assume that it is proposed to build a culvert 30 feet
long — out to out of culvert proper — having a water way 3 feet wide
and 4 feet high, and that estimates of the cost of the general forms
shown in Fig. 94 and also of that of Fig. 95 are desired.
Estimates for a%x4:ft. Box Culvert of tlie General Foi*m shown in Fig. 94.
Masonry in 3 end walls— 16.88 cu. yds <& $3.50 per cu. yd. = $59.08
" " 25 feet of trunk (1 444x25=) 36.10 cu. yds. @, $8.50 " " = 126.35
Paving " 25 " " " (0.111x25=) 2.78 •* " ® $2.00 ** " = 5.55
Total cost $190.98
Estimates for a 3 X 4* ft. Sox Culvert of Hie General 'Form shown in Fig. 95.
Masonry in 2 end walls— 24.20 cu. yds ®. $3 50 per cu. yd. = $84.70
tk 24 feet of trunk (24 x 1.148=) 27.55 cu. yds. ® $3 50 " " = 96.43
Paving " 24 " " " (24 x 0.370=) 8.88 " " ® $2.00 " " = 17.76
Total cost $198.89
406
CULVERTS.
[CHAP. xvn.
ART. 2.] VITRIFIED PIPE CULVERTS. 407
If the price for the masonry does not include the expense for
the necessary excavation, the above estimates should be increased
by the cost of excavation, which will vary with the situation of the
culvert.
To make a comparison of the relative cost of the two types
of culverts just mentioned, we may proceed as follows : The cost
per foot of the trunk of a 3 X 4 culvert of the form shown in
Pig. 94 is (1.444 cu. yds. of masonry @ $3.50 plus 0.111 cu. yds.
of paving @ $2.00) $5.28; and the corresponding cost for Fig.
95 is (1.148 cu. yds. of masonry @ $3.50 plus 0.370 cu. yds.
of paving @ $2.00) $4.76. The difference in cost per foot
is ($5.28 — $4.76) $0.52 in favor of Fig. 95. The cost of the
end walls for Fig. 94 is (16.88 cu. yds. @ $3.50) $59.08; and the
corresponding cost for Fig. 95 is (24.20 cu. yds. @ $3.50) $84.70.
The difference is $25.62 in favor of Fig. 94. Since in the former
the cross wall extends but 2 feet below the floor of the culvert,
while in the latter the end walls extend 3 feet, the difference in cost
should be decreased by the cost of the difference of the foundations.
If the cross walls of Fig. 94 be carried down another foot, the
amount of masonry will be increased 2 cu. yds. and the cost $7.00;
and the difference iii cost of the end walls will "be ($25.62 — $7.00)
$18.62 in favor of Fig. 94: Under these conditions, for a culvert
40 feet long, the two types will cost the same; for lengths less than
40 feet Fig. 94 is the cheaper, and for lengths greater than 40 feet
Fig. 95 is the cheaper. If the end walls of Fig. 95 are carried
down only 2 feet, the amount of masonry will be decreased by 3.4
cu. yds. and the cost by $11.90; and then the difference of cost will
be ($25.62 — $11.90) $13.72. Under this condition, for a culvert
30 feet long, the two types will cost the same; for lengths less than
30 feet Fig. 94 is the cheaper, and for lengths greater than 30 feet
Fig. 95 is the cheaper. We may conclude, therefore, that for
lengths under 35 or 40 feet the type shown in Fig. 94 is a little
cheaper, while for greater lengths than 35 or 40 feet that in Fig.
95 is slightly cheaper. For the smallest size the length of equal
cost is about 10 feet.
There is no material difference in the first cost of the two types;
but the culvert shown in Fig, 94 is the more efficient.
627. VITRIFIED PIPE CULVERTS. During the past lew years
vitrified sewer pipes have been extensively employed for small cul-
408
CULVERTS. [CHAP. XVII,
verts under both highways and railroads. The pipe generally
employed for this purpose is that known to the trade as culvert
pipe or "extra heavy" or "double strength" sewer pipe, which is
20 to 40 per cent, (varying with the maker and the size) heavier than
the quality ordinarily employed for sewers.
Apparently the heavier pipe is used on the supposition that the
lighter is not strong enough for culverts. In most cases, at least,
this is an erroneous assumption. 1. "With the same depth of earth
over the pipe, there is but little more pressure on the pipe when
used as a culvert than when employed in a sewer. At most, the
difference of pressure is that due to the live load, which can not
exceed the weight of an additional 5 feet of earth (see § 618), and
will generally be much less (see the second paragraph of §.619).
2. Experience demonstrates that the lighter pipes are not deficient
in strength when used in sewers, however deep they are laid.
According to experiments made by bedding the lower half of the
pipe in sand and applying a pressure along a comparatively narrow
area, the average crushing strength of ordinary sewer pipe was
2,400 Ibs. per sq. ft. of horizontal section, and for culvert pipe
12,000 Ibs. per sq. ft. If the pressure had been applied more
nearly as in actual practice, the pipes would have borne consider-
ably more. The first of the above results is equal to the weight of
24 feet of earth, and the second to that of 120 feet, although actual
embankments of these heights would not give anything like the
above pressures (see § 619).
There is a little difference between culverts and sewers in the
exposure to frost; but no danger need be apprehended from this-
cause, provided the culverts are so constructed that the water is
carried away from the lower end, since ordinary soft drain tile are
not in the least injured by the expansion of the frost in the earth,
around them.
628. Construction. In laying the pipe, the bottom of the trench
should be rounded out to fit the lower half of the body of the pipe,
with proper depressions for the sockets. If the ground is soft or
sandy, the earth should be rammed carefully, but solidly, :a and
around the lower part of the pipe. On railways, three feet of earth
between the top of the pipe and the bottom of the tie has been
found sufficient. On highways pipes have stood from 10 to 15
years under heavy loads with only 8 to 12 inches of earth over
ART. 2.]
VITRIFIED PIPE CULVERTS.
409
them;°but as a rule it is not wise to lay them with, less than 12 to
18 inches of earth covering.
In many cases — perhaps in most — the joints are not calked. If
this is not done, there is liability of the water's being forced out at
the joints and washing away the soil from around the pipe. Even
if the danger is not very imminent, the joints of the larger pipes,
at least, should be calked with hydraulic cement, since the cost is
very small compared with the insurance of safety thereby secured.
Sometimes the joints are calked with clay. Every- culvert should
be built so that it can discharge water under a head without damage
to itself.
The end sections should be protected with a timber or masonry
bulkhead, although it is often omitted. Of course a parapet wall
of rubble masonry or brick-work laid in cement is best (see Fig. 97).
FIG. 97.
FIG. 98.
The foundation of the bulkhead should be deep enough not to be
disturbed by frost. In constructing the end wall, it is well to in-
crease the fall near the outlet to allow for a possible settlement of
the interior sections. When stone and brick abutments are too
expensive, a fair substitute can be made by setting posts in the
ground and spiking plank on as shown in Fig. 98. When planks
are used, it is best to set them with considerable inclination towards
the road bed to prevent their being crowded outward by the pressure
of the embankment. The upper end of the culvert should be so
protected that the water will not readily find its way along the out-
side of the pipes, in case the month of the culvert should become
submerged.
The freezing of water in the pipe, particularly if more than
half full, is liable to burst it; consequently the pipe should have a
sufficient fall to drain itself, and the outlet should be so low that
410
CULVERTS.
[CHAP. xvii.
there is no danger of back-water's reaching the pipe. If properly
drained, there is no danger from frost.
When the capacity of one pipe is not sufficient, two or more
may be laid side by side. Although two small pipes do not have
as much discharging capacity as a single large one of equal cross
section, yet there is an advantage in laying two small ones side by
side, since then the water need not rise so high to utilize the full
capacity of the two pipes as would be necessary to discharge itself
through a single one of larger size.
629. Examples. Kg. 99 (page 411) shows the standard vitri-
fied pipe culverts employed on the Kansas City and Omaha E. E.
This construction gives a strong, durable culvert which passes water
freely. The dimensions of the masonry end walls and of the con-
crete bed for the intermediate sizes are nearly proportional to those
shown in Fig. 99. Table 46 (page 411) shows the quantities of
masonry required for the principal sizes.
630. Cost. Prices of vitrified pipe vary greatly with the con-
ditions of trade, and with competition and freight. Current (1888),
non-competitive prices for ordinary sewer pipe, in car-load lots
/. o. T). at the factory, are about as in the table below.
TABLE 45.
COST AND WEIGHT OF VITRIFIED SEWER PIPE.
INSIDE DIAMETER.
PRICE PER FOOT.
AREA.
WEIGHT PER
FOOT.
AMOUNT IN A
CAR LOAD.
12 inches.
15 cents.
.78 sq. ft.
45 Ibs.
500 feet.
14
23
1.07
55
400
16
30
1.40
65
350
18
38
1.76
75
300
20
53
2.18
90
260
22
57
2.64
110
230
24
87
3.14
140
200
1
Culvert pipe costs about 20 to 25 per cent, more than as above,
and second quality sewer pipe about 20 to 25 per cent. less. The
latter differs from first quality in being less perfectly glazed, less
perfectly burned, or not perfectly round, or in having fire cracks in
the glazing, blisters on either surface, excrescences or pimples on
the inside, or a piece broken out of the end. Frequently such
pipe is as good for culverts as first quality sewer pipe.
ART. 2.]
VITRIFIED PIPE CULVERTS.
411
Fia. 99.— STANDARD VITRIFIED PIPE CULVERT.— K. C. & O. R. R.
TABLE 46.
MASONRY REQUIRED FOR VITRIFIED PIPE CULVERTS OF THE GENERAL
FORM SHOWN ABOVE.
DIAMETER OF PIPE.
ITEMS.
14 inches.
16 inches.
20 inches.
24 inches.
Coping" two ends
cu. yds.
0 54
cu. yds.
0 71
cu. yds.
0 97
cu. yds.
1 07
Parapets, two ends
2 93
4 45
6.98
8.47
Total Masonry
3.47
5.16
7.95
9.54
Concrete, per lineal foot..
0.070
0.102
0.136
•
0.180
412
CULVERTS.
[CHAP. xvii.
631. IRON PIPE CULVERTS. In recent years, iron pipes have
been much used for culverts. In many localities good stone is not
available, and hence stone box culverts (§§ 615-26) can not be used.
In such localities vitrified stoneware pipes are used ; but as they
are not made larger than 2 feet in diameter, iron or stone is the only
material available for permanent culverts requiring a greater water
way than that obtained by using one or two of the largest vitrified
pipes. Apparently, stone culverts if well built should last forever;
but, as constructed in the past, they have been found to last rela-
tively only a short time. Hence, with the increasing cheapness of
iron, there has been an increasing tendency to use iron pipe for even
large culverts. Cast-iron pipes from 12 to 48 inches in diameter
and 12 feet long are in common use by all of the prominent roads
of the Mississippi Valley. Some of the roads cast their own, while
others buy ordinary water pipe. The lightest water pipes made, or
even such as have been rejected, are sufficiently strong for use in
culverts. The dimensions used on the Chicago, Milwaukee and St.
Paul E. R are about as follows :
TABLE 47.
DIMENSIONS OF CAST-IRON CULVERT PIPE.
INSIDE DIAMETER.
WEIGHT PER FOOT.
THICKNESS.
WEIGHT PER LINEAL FOOT
PER SQ. FT. OF AREA.
12 inches.
60 Ibs.
T\ inch.
77 Ibs.
16
88
I
63
20
118
59
24
175
i
56
30
240
f
49
36
320
£
46
42
400
£
42
48
510
1
41
632. Construction. In constructing a culvert with cast iron,
the points requiring particular attention are (1) tamping the soil
tightly around the pipe to prevent the water from forming a chan-
nel along the outside, and (2) protecting the ends by suitable head
walls and, when necessary, laying riprap at the lower end. The
amount of masonry required for the end walls depends upon the
relative width of the embankment and the number of sections of
pipe used. For example, if the embankment is, say, 40 feet wide
at the base, the culvert may consist of three 12-foot lengths of
AET. 2.] mm PIPE CULVERTS. 413
pipe and a light end wall near the toe of the bank ; but if the
embankment is, say, 32 feet wide, the culvert may consist of two
12-foot lengths of pipe and a comparatively heavy end wall well
back from the toe of the bank. The smaller sizes of pipe usually
come in 12-foot lengths, but sometimes a few 6-foot lengths are
included for use in adjusting the length of culvert to the width of
bank. The larger sizes are generally 6 feet long.
Fig. 100 (page 414) shows the method employed on the Atclii-
son, Topeka and Santa Fe E. E. in putting in cast-iron pipe
culverts. Table 48 (page 414) gives the dimensions for the end
walls for the various sizes. The length of pipe is determined by
taking the multiple of 6 feet next larger than the length given by
the position slope as in Fig. 100. To allow for settling, the pipe is
laid to a vertical curve having a crown at the center of 1 inch for
each 5 feet in vertical height from bottom of pipe to profile grade.
Where the soil is treacherous, it would be wise to lay the pipes
•on a bed of broken stone to prevent undue settling. In this con-
nection, see Figs. 96 and 99 (pages 406 and 411).
633. Fig. 101 (page 415) shows the method employed on the
•Chicago, Burlington and Quincy E. E. of putting in cast-iron pipe
•culverts. This construction has given entire satisfaction.
The same road has recently commenced the use of iron for cul-
verts up to 12 feet in diameter. For diameters greater than 4 feet,
the pipes are cast in quadrants 2, 4, 6, and 8 feet long, which are
.afterwards bolted together, through outside flanges, to form a
•cylinder of any desired length. The different segments are so com-
bined as to break joints around and also along the pipe. The body
•of the pipe was formerly If inches thick ; but is now 1|-, stiffened on
the outside by ribs. The sections are put together without any chip-
ping, drilling, or other skilled labor. Between the different sec-
tions is a recess in which a tarred rope smeared with neat cement
mortar is placed before bolting the segments together, which makes
the joints tight.*
634. Cost. The cost of cast-iron pipe varies greatly with com-
petition and the conditions of trade. The price ranges from $26 to
$36 per ton for first quality water pipes,/, o. Z>. at the foundry; or
approximately, say, 1£ cents per pound.
* Eor illustration of details, see Railroad Gazette, vol. xix. pp. 122-24.
HUNT LIBRARY
414
CULVERTS.
[CHAP. xvn.
I
8
M I
O ti)
9 S
£, d
i "i
-a
-
OOCOOQCO
CO O TH •»-( T-t
CCCDOi-iT-l
C- 2 3 2
OCOCOCOO
Ci CO t- T-( rH
"Si
if III
wS OHM
5
ART. 2.
IRON" PIPE CULVERTS.
415
Fio. 101.— CAST-IRON PIPIC CULVB»T.-~CM B. & Q. E. E.
416 CULVERTS. [CHAP. xvn.
Table 47 (page' 412) shows that the average weight of the pipe
per foot per square foot of water way is about 60 pounds ; and
hence the cost of the trunk of a cast-iron pipe, exclusive of trans-
portation and labor, is about (60 X H) 90 cents per lineal foot per
sq. ft. of area. The cost of sewer pipes is, from Table 46 (page
411), about 22 cents per foot per square foot of water way • and for
culvert pipe about 30 cents.
Assuming the cost of rubble masonry to be $3.50 per cubic yard
iind of paving to be $2.00 per cubic yard, the average cost of the
masonry in the trunk of the box culvert shown in Fig. 95 (page
404) is 40 cents per lineal foot for each square foot of water way ;
and the corresponding cost for the culvert of Fig. 94 (page 403) is
46 cents. The end walls required for these different forms of cul-
verts are essentially the same ; and hence the above comparison
shows approximately t .0 relative cost of the different forms of cul-
verts. According to this showing, cast-iron pipe is the most ex-
pensive ; but this difference is partly neutralized by the greater
ease with which the iron pipe can be put into place cither in new
work or in replacing a wooden box-culvert.
635. The following figures give the cost of a 7-foot cast-iron
culvert of the form referred to in § 633, which see.
42 ft. body @, $26.55 per foot (1.55 cents per pound) $1,114.83
8 ft. specials @ $29.42 " " " " " tl 235.32
Bolts and washers 29.91
Unloading -. 17.52
Putting in place 148.95
Stone for end walls, 70 cu. yds., @ $1.50 105.00
Stone for riprap foundation, 60 cu. yds., @ $1.00 60.00
Removing temporary bridge 285.62
Total $1,947.15
Excluding the cost of removing the temporary bridge — which
is not a part of the culvert proper,— and of the riprap foundation—
which the unusual conditions required, — the cost of the culvert was
$33.03 per foot, or 83 cents per lineal foot for each square foot of
water way.
636. TIMBER Box CTTLVEKTS. Timber box culverts should be
used only where more substantial material is not attainable at a
reasonable cost. Many culverts are constructed of timber
ART. 2.] BOX AHD PIPE CULVERTS.
periodically renewed with the same material, and many are con-
structed of wood and replaced with stone, or sewer or iron pipe.
The latter is an example of what may be called the standard
practice in American railroad building; i. e., constructing the road
as quickly and cheaply as possible, using temporary structures., and
completing with permanent ones later as the finances of the company
will allow and as the requirements of the situation become better
understood. After the line is open, the permanent structures can
be built in a more leisurely manner, at appropriate seasons, and
thus insure the maximum durability at a minimum cost.
There is a great variety of timber box culverts in common use,
but probably there are none more durable and efficient than those
used on the Chicago, Milwaukee and St. Paul R. R., — shown in
.Fig. 10:3 (page 418).* On this road, it is the custom to replace the
wooden boxes with iron pipes before the timber has seriously de-
cayed. If experience has shown the size of the wooden box to be
about right, the timbers are cut out a little and an iron pipe is
placed inside of the box without disturbing the earth.
For timber box culverts of sizes larger than can be made of
plank, the Atchison, Topeka and Santa Fe R. R. employs bridge-
tie box culverts. These are made by laying 6x8 inch sawed
bridge ties flatwise, in contact, to form a floor. These ties are
gained at the ends so as to leave a shoulder 1 inch deep against
which the inside of the side walls bears. Upon this floor, vertical
side walls are constructed by laying ties flatwise, one on top of the
•other ; the lowest timber in each side wall is fastened to each tie in
the floor by a drift-bolt 12 inches long, and each timber in the side
wall is fastened to the one below it by a 12-inch drift-bolt every 3
feet. The lengths of the ties employed in the side Avails are so ad-
justed as to make the exposed ends conform closely to the slope of
the embankment. The roof consists of 6- X S-inchties set edgewise,
in close contact, with a shoulder 1 inch deep on the inside, both
•ends of each piece being also drift-bolted to the side wall. .
637. TIMBER BARHEL CULVERTS. For a number of years past
the Chicago, Burlington and Quincy R. R. has found it desirable,
in view of the absence or poor quality of the stone along its lines, to
use a timber "barrel-culvert" when the opening is too large for a
* From Railroad Gazette.
418
CULVERTS.
[CHAE. XVII-
i
AKT. 3.]
ARCH CULVERTS.
419
timber box-culvert. The staves are 10 or 12 inches thick, accord-
ing to the size of the culvert, and 8 inches wide on the outside,
dressed to form a circle 4|- or 6 feet in diameter. Iron rings — made
of old rails — spaced about 10 feet apart, are used as a form upon
which to construct the culvert and also to give it strength. The
staves break joints and are drift-bolted (§ 381) together. As soon,
as the timber is thoroughly seasoned, the culverts are lined with a
single ring of brick, and concrete or stone parapet walls are built.
If, at any time, the timber fails, it is the intention to put iron pipe
through the present opening.
The timber costs about $12 per thousand feet, board measure,
at the Mississippi Eiver ; and the cost of dressing at the company's
shops is about $1.50 per thousand.
ART. 3. ARCH CULVERTS.
638. In this article will be discussed what may be called the
theory of the arch culvert in contradistinction to the theory of the
arch. The latter will be considered in the next chapter.
By the theory of the arch culvert is meant an exposition of the
method of disposing a given quantity of masonry so as to secure (1)
maximum discharging capacity, (2) minimum liability of being
choked by drift, and (3) maximum strength. Attention to a few
points, which are often neglected in the design of culverts, will se-
cure these ends without additional cost.
639. GENERAL FORM OF CULVERT. Splay of Wings. There
are three common ways of disposing the wing walls for finishing
the ends of arch culverts. 1. The culvert is finished with a straight
wall at right angles to the axis of the culvert (see Kg. 103). 2. The
FIG. 103.
FIG. 104.
FIG. 105.
wings are placed at an angle of 30° with the axis of the culvert
(see Eig. 104). 3. The wing walls are built parallel to the
axis of the culvert, the back of the wing and the abutment
being in a straight line and the only splay being derived from thin-
420
CULVERTS.
[CHAP. xvii.
ning the wings at their outer ends (see Fig. 105). The first method
is shown on a larger scale in Plate II, the third in Plate III, and
the second in Plate IV.
The quantity of masonry required for these three forms of wings
does not differ materially, Fig. 105 requiring the least and Fig. 103
the most. The most economical angle for the wings of Fig. 104 is
about 30° with the axis.
The position of the wings shown in Fig. 104 is much the most
common and is better than either of the others. Fig. 103 is ob-
jectionable for hydraulic considerations which will be considered
in the next section, and also because it is more liable to become
choked than either of the others. Fig. 105 does not have splay
enough to admit the natural width of the stream at high water,
and does not give sufficient protection to the toe of the embankment.
640. Junction of Wings and Body. With a culvert of the
general form outlined in Fig. 104,
there are two methods of joining
the wings to the body of the cul-
vert. The more common method
I is shown in Figs. 10 G and 108; and
the better, but less common, one is
shown in Figs. 107 and 109.
The form shown in Figs. 106
and 108 is very objectionable because (1) the corners reduce the
capacity of the culvert, and (2) add to its cost*
FIG. 106.
FIG. 107.
FIG. 108.
FIG. 109.
1. The sharp angles of Fig. 106 materially decrease the amount
of water which can enter under a given head and also the amount
ART. 3.] ARCH CULVERTS.
which can be discharged. It is a well-established fact in hydraulics
that the discharging capacity of a pipe can be increased 200, or
even 300, per cent, simply by giving the inlet and outlet forms some-
what similar to Fig. 107. Although nothing lijxe this increase can
be obtained with a culvert, one finished at both the upper and the
lower end like Fig. 107 will discharge considerably more water than
one like Fig. 106. The capacity of Fig. 107 decreases as the angle
between the wing and the axis increases ; hence, the less splay the
better, provided the outer ends of the wings are far enough apart
to accommodate the natural width of the stream at high water.
Also the less the splay, the less the probability of the culvert's being
choked with drift. Fig. 106 is very bad for both the admission and
the discharge of water, and also on account of the great liability
that drift and rolling stones will catch in the angles between the
wings and the end walls. In this latter respect Fig.- 108 is slightly
better than Fig. 106.
2. Every angle adds materially to the cost of the masonry. In
a culvert like Fig. 106, there are four unnecessary corners. This
form probably owes its prevalence to the desire to have a uniform
batter on the face of the wing, and to have the face of the wing
wall intersect the end wall back of the arch stones. Satisfying both
of these conditions gives a culvert in ground plan like Fig. 106 ;
and satisfying the second one only, gives Fig. 108. Practically
there is but little difference between these two forms — both are
objectionable, as already explained. If the wing of Fig. 108 is
moved inward, and the corner of the wing, which would other-
wise project into the water way, is rounded off to a gentle curve,
Fig. 109 is obtained. This form is simple, efficient, and, on the
whole, the best.
Plate III shows another method of joining the wing to the
end wall without having an unnecessary angle, In this case, the
face of the wing up to the springing line of the arch is a warped
surface, which is in some respects undesirable, although it saves
a little masonry. However, the face of the wing wall could be
built vertical up to the springing line and then battered; or
the wing could be moved forward and the corner be rounded off
as in Fig. 109.
641. Semi-circular vs. Segmental Arches. There are two
classes of arches employed for culverts, viz., the semi-circular and
422 CULVERTS. [CHAP. xvii.
the segmental. The first is by far the more common; but neverthe-
less the latter is, on the whole, much the better.
1. For the same span, the segmental arch requires a shorter in-
trados (the inside curve of a section of the arch perpendicular to
its axis). For example, the culverts shown in Plates IV and V
have the same span, but the intrados of the semi-circular arch is
15.71 ft., while that of the segmental arch is 10.72 ft.; that is, the
intrados of the segmental is only 68 per cent, of the intrados of the
semi-circular arch. This difference depends upon the degree of
flatness of the segmental arch. The above example is an extreme
case, since the segmental arch is unusually flat, the central angle
being only 73° 44'. (The rise is one sixth of the span.) With a
central angle of 120°, the intrados of the segment is 77 per cent, of
the semi-circle.
Or, to state the above comparison in another and better form, for
the same length of intrados the segmental arch gives the greater
span. For example, a segmental arch on the same general plan as
that of Plate V, but having an intrados equal to that of Plate IV,
would have a span of 14.64 ft., which is 46 per cent, greater than
the span of the semi-circular arch shown in Plate IV. A segmental
arch with a central angle of 320° has a span 33 per cent, greater
than a semi-circular arch having the same length of intrados. This
difference constitutes an important advantage in favor of the seg-
mental arch culvert, since the wider the span the less the danger of
the culvert's being choked by obstructions, and because it will pass
considerably more water for the same depth.
2. For the same length of intrados, the segmental arch gives the
greater water way. The water way of the culvert shown in Plate
IV is 87.6 square feet; but the same length of intrados in a seg-
mental arch culvert having 73° 44' central angle (the same as Plate
V) would have a water way of 98.3 square feet; and with a central
angle of 120° would have a water way of 99.5 square feet. In both
examples the increase is one eighth.
3. On the other hand, the segmental culvert will require a
thicker arch. It will be shown in the next chapter that arches
can not be proportioned strictly in accordance with mathematical
formulas ; and hence the exact difference in thickness of arch which
should exist between a semi-circular and a segmental arch can not
be computed. According to established rules of practice, -small
AET. 3.] AECH CULVERTS. 423
segmental arches are from 10 to 25 per cent, thicker than semi-
circular ones. This difference is not very great, and its effect upon
the cost of the culvert is, proportionally, still less, since the cost
per yard of arch masonry is less for the thicker arches. Then, we
may conclude that, since for the same span the intrados of seg-
mental arches is from 20 to 40 per cent, shorter than the semi-
circle, the segmental arch requires a less volume of arch masonry
than the semi-'bircular, and also costs less per cubic yard. The arch
masonry per foot of length of the segmental arch culvert shown in
Plate V is only 71 per cent, of that in the semi-circular one shown
in Plate IV. The dimensions and contents of arch culverts of the
general forms shown in Plates IV and V are given in Tables 51
and 52 (pp. 430 and 431 respectively), from which it appears that
the segmental arch contains only from 60 to 76 per cent, as much
masonry as the semi-circular, the average for the six spans being
almost exactly 70 per cent. The cost of these two classes is shown
in Tables 56 and 5? (pages 437 and 438), from which it appears that
the average cost of segmental culverts 20 feet long and of different
spans is only. 59 per cent, of the cost of semi-circular ones of the
same length and span; and the average cost of an additional foot
in length for the segmental is only 86 per cent, of that for a circular
one. The water ways of the semi-circular culverts are a little the
greater, and hence the difference in cost per square foot of water
way is not as great as above; but, on the other hand, the form of
water way of the segmental culvert is the more efficient, and hence
the above comparison is about correct.
4. Will the segmental, i. e., the flatter, arch require heavier abut-
ments (side walls)? Unquestionably the flatter the arch the
greater the thrust upon the abutment; but the abutment not only
resists the thrust of the arch which tends to turn it over outwards,
but also the thrust of the embankment, which tends to push it in-
wards. It is impossible to compute, with any degree of accuracy,
either the thrust of the arch or of the embankment; and hence it is
impossible to determine either the relative value of these forces or the
thickness which the two abutments should have. Experience seems
to indicate that the thrust of the earth is greater than that of the
arch, as is shown by the fact that nearly all semi-circular culverts
have abutments of much greater thickness than are required to re-
sist the thrust of the arch; and hence we may conclude that expe-
424 CULVERTS. [CHAP. XVII,
rience has shown that the thrust of the earth necessitates a heavier
abutment than does the thrust of the arch. If this be true, then
the abutment for segmental arches may be thinner than those for
semi-circular ones; for,, since the thrust of the former is greater
than the latter, it exerts a greater force outward, which counter-
balances a larger part of the inward thrust of the embankment, and
thus leaves a less proportion of the latter to be resisted by the mass-
of the abutment. Segmental arch culverts are not often built; and
designers appear to have overlooked the thrust of the earth, since
the side walls of segmental arches are generally thicker than for
semi-circular ones (compare Plates IV and V).
The conclusions may, therefore, be drawn that segmental arch
culverts are both cheaper and more efficient than semi-circular ones.
642. As built, many semi-circular arches are practically seg-
mental; that is, the side walls are built so high, or the backing is
made so heavy, that practically the abutments are less than 120°
apart, and hence the two lower ends of the arch are really only a,
part of the side wall, and should be built square.
Further, it is shown in §§ 681-82 that a true arch of more than
about 90 to 120 degrees is impossible.
643. EXAMPLES, Under this head will be given a brief descrip-
tion of four series of arch culverts which are believed to be repre-
sentative of the best practice.
644. Illinois Central Arch Culverts. Plate II shows the gen-
eral plan of the standard arch culvert employed in the construction
(185^-53) of the Chicago branch of the Illinois Central Kailroad.*
While the timber in the foundation is apparently still in good con-
dition, the use of timber for such shallow foundations can not be
considered as the best construction. However, many of the con-
ditions, particularly drainage, have greatly changed since this road
was built, and it is by no means certain that this use of timber
was not good practice at that time (see § 636).
Table 49 (page 425) gives the dimensions and contents for the
several spans of this form of culvert. The contents of the end
walls were computed on the assumption that the off-set at the back
was 6 inches for each foot, counting from the top, until the full
thickness at the bottom was 'obtained (see Section E-F, Plate II).
* Published by permission of J. M. Healey, Division Engineer.
ART. 3.]
ARCH CULVERTS.
425
CO «H
'oococooooooii >
"-1
^ : pq r
CM
o - -
^ d ^r<
- o ^ - ^ ,
OS *O
"- o
cc
T
•(
JO iC
^OCQ-^rHCOCOrHCDC-rH
C^i C5i
CO rH CO (74 O5 rH
O C?
°2 >*H
CO
H
^
«M
^ : « r
3 £
£
O - - - £
g1 -- - -
g bb
_s
CO CO
o> *>•
OCSJ
"^O
•^i • lO C3S j>. cO
"^ 1O CO £5 CO
0 .2
z
CO CO rH CO T-
O O
W cu
§ 1
to
-
-
„
s
<l _d
.a ---------- ^ ^4J-_-
ooscoooococooo"*o . ^•<1M. W
•< c§
£
O " v
" O g - 4-3
Bi
00
xH O **H
1 1
COiZ>Ci^rHOlGStrHQOl>CO
(M C^t rH CM
cc^
2s § 1s
° £
CO " rH.
s a *
O id
;
-
V
^ J
K ^ O
oosocococoooooo
•>
«*-
^ •< -
•
rH p
o^
tH H5 0
in
C
H ^ a
-rH O <+H -
••cH . -HH ?-— A-» (V^
° H °°
C5 CO O5 CO rH C5 O5 rH -rH CO rfl • • - • 1C
C5 C<i rH O OO O
. L « rrt
CO CO 01
rH ^
£2 S
bO "S
C3 g
fl
cu
•:-
1 -
.2^3 : :-S
§ ° 03
« 2 : i o
o • • . • • • 0
o
172 o • • *""
o*l
0 • . d
1 : S>
0
5
«t-
^
^
-1
*2o i i|§
-< h 5
5 .2
o
c
5 c
*O rW eJ ^*T "5
TABLE 49. — DIMENSIONS
Dimensions not given in
1
i 1
,Q o
2 b^ .2
? to ^ 'S
w gn «I-M o — i y
'-g bp fl c § 'S - rt
o-g'S ^^ 5i" ^ f? c
^ R"o ^^cw - d 2 s'
^S^ b0°c,o^ g -|
fl 53 0 .a §-2^; £ *g E
o 'd a a be*-- 33-5, o> b
^SB^.S^^-^-a o =
,Q j/i r-4 £Li tf) rO |3 O
||W5 OCQ^csieM-
1 « 4J-24jOti- O
^d *f fl rt-^jd^0 "Y
f!«l: 1 ||?% i
o
1
bO
p
O
fl
T3
03
c
c
-t-
4.
c
\
c
;
c
t
c
«f
5
f
2 *M fe
jN
J ^ 03
s^|^
^0°—^
^ ^
to be covered with, under wings
to be covered with, under trim
tion— per foot of leugt
der end walls and in sheet pilii
der trunk, per foot of length-
side of wings of founcL
§53 |. -^S'l i
^ S ^ c
; n §§
02 ^ .S? r2 r
J=3 g_0 C
> =3 S bO
O ^ *2 E^ S CH fl
K * j * S E °
"*1
1
* b
/3 r-
?| I
2 r?H -S 0 t2 HO
c
H d " ^ ^ ^ P=
J^
1
S F
H .3 r^
^ tx} -^ GQ Pn j£j H
<1 EH O e-i ^
ft o
426 CULVERTS. [CHAP. xvii.
645. Example of the Use of Table 49. To illustrate the method
of using the above table, assume that an estimate of the amount of
material in an 8-ft. arch culvert of the preceding form is required.
Assume that the top of the coping is 3 feet below sub-grade, i. e.,
that there is 4. 25 feet of earth above the crown of the arch. Assume
also that the road bed is 1G feet, and that the slope of the embank-
ment is H to 1. Then the length of the culvert from inside to in-
side of the end walls will be 16 + 2 (f X 3) = 16 + 9 = 25 feet; and
from out to out of end walls, the length will be 25 + 2 X 2.5 = 30
feet.
Assuming that the timbers under the planking are 8x10 inches,
the 205£ sq. ft., as per the table, will require 1,639 ft. B. M. of tim-
ber, or 9 pieces 24 ft. long. Notice, however, that in practice 10
pieces would be used — 5 at each end of the culvert. The length of
the trunk of the foundation is 30 — 2 (4+ £ + 1) = 19 ft. Hence
the area under the trunk of the foundation to be covered with tim-
ber is 19 x 8 (see table) = 152 sq. ft. ; and if 8 X 10-inch timbers
are used, this will require 1,216 ft. B. M., or 12 pieces 14 feet long.
The plank under the wings and in the sheet piling is 1,493 feet (see
table), and that in the trunk is 32 (see table) X 19 = 608 ft. B. M. ;
hence the total plank is 1,493 + 608 = 2,101 ft. B. M.
The masonry in the end wall is 32.97 cu. yds., as in table. The
masonry in 1 foot of arch is (see table) 0.673 + 0.284 = 0.957; and
in 30 ft. it is 0.957x30 = 28.71 cu. yds. The masonry in the side
walls (abutments of the arch) is 0.444 (see table) X30 = 13.32 cu.
yds. The coping is 65 cu. ft. (see table) = 2.41 cu. yds.
Collecting and tabulating the preceding results,5 we have the
following :
Timber:— 10 pieces, 8 X 10 inches, 24 ft. long 1,866 ft. B. M.
12 " " " 14 " " 1,280 "
2-inchplank 2,101 "
Total timber in culvert 25 ft. long... . 5,247 "
Masonry: — 2 end walls 33 . 0 cu. yds.
coping 2.4" '*
side walls (abutments) 13. 3 "
arch masonry 28.7" "
Total masonry in culvert 25 ft. long.. 77.4" "
AET. 3.] ARCH CULVERTS. 427
646. Chicago, Kansas and Nebraska Arch Culverts. — The culvert
shown in Plate III is the standard form employed on the Chicago,
Kansas and Nebraska Kailroad.* Notice that the slope line inter-
sects the inside face of the end wall at a considerable distance above
the back of the crown of the arch (see Side View, Plate III). This
is sometimes urged as an objection to this form of construction, on
account of the supposed liability of the top of the end wall being
pushed outward; but there is no danger of this method of failure,
isince the height of the end wall above the crown of the arch is, ex-
clusive of the coping, only equal to its thickness, and in addition it
is buttressed on the outside by the wings. The advantage of this
construction is that it requires less masonry and also less labor.
Concerning the manner of joining the wings to the body, see the
last paragraph of § 640 (page 421).
Table 50 (page 428) gives the dimensions and contents for
various spans. The contents of the wings above the springing line
-of the arch were computed for courses 1 foot thick and for an earth
slope of 1J to 1 (see §557).
647. Example of the Use of Table 50. Assume the same depth
of earth over the crown of the arch as in the example in §644,
i. e., 4.25 ft.; and assume also that the slope line strikes the upper
corner of the coping instead of the lower as shown in Plate III.
The top of the coping will be 0.75 ft. below sub-grade; and, for a
16 -ft. road-bed, the length of the arch — inside to inside of end
walls— is 16 + 2(f X 0.75) = 18.25 ft. With the above data and
Table 50, we have the following:
Four wing walls, including one footing course, . . 40.5 cu. yds.
Two head " " " " . . 36.8 "
Coping, 1.8 "
Two side walls, 18* ft. @ 1.382 cu. yds. per foot, . . 25.2 "
Arch masonry, " " "1.184" " " " . . 21.6'*
Paving, 23.58 ft. @ 0.272 cu. yd. per ft., .... 6.4 '<
Total masonry in culvert 18* ft. long, . . 132.3 " "
In attempting to make comparisons between the above total and
that of §645, notice that the culverts are of very different style (see
§§ 638 and 639) and that the water ways are of different areas.
* Published by permission of H. A. Parker, Chief Engineer.
428
CULYERTS.
[CHAP. xvii.
TABLE 50.
DIMENSIONS AND CONTENTS OF CHICAGO, KANSAS AND NEBRASKA ARCH CULVERTS.
FOR DIAGRAM SEE PLATE in.
Dimensions not given in the table are the same, for all sizes, as in the diagram.
i
d
o
CO
- «
O O 00 O OO CO O ^ 00 O O OCi SO O O
£js-----2-s----- «,., «i r
-m
3
:>
00
.S-
OC
-**".
ri
- -w
3OO OQOCOOOOOOOOCOOOO "^
§s = =
2* 3
- 3
O
a?
H li 2 -
CO
e-
03
a
oooooooooo-irooooocooooo ^
o "* " ** " o
s;s
||«ooS«^««cooo^««^
H iS - =
io^
>
5
.
en
i
OOQOOGOCOOOCOcDOOOOOO
gs = ^ g
jSs----s--r2r2r23 i- CM. oo ^^o
C»0<WCOOS.-COt-<N«OOOr-,MCOr-t c^o^ o' OOO*
** '"' »-« r-i CO
so
DO
'
>
OTt<GOOOOOOOOWOOOOOOOC
>
P- S c i 5 C
o c
1 t-0 0 001s-
c,o3oS^«^WN^c,«=,«Nr.
3s!
«c
<jp:
' SEfflSS
: : ¥ J 2
S
CONTEXTS:
Four wing walls, including one footing course
Two end walls, " *' " "
Two side walls, including one footing course— p
foot of length from inside to inside of end walls
Arch masonry, per foot of length from inside
inside of head walls , .
Paving, per ft. of length from out to out of end wal
CoDiner. on two end walls
5
.<
DIMENSIONS:
End wall, height above the footing
length
thickness
Coping on end wall, width
" " " " length
Wing, height at inner end
" "outer "
length for slope of 1J^ to 1
thickness on top
" at bottom of outer end
distance between outer ends of wings.
Arch, height of springing above footing
thickness at crown
Side walls, thickness at springing
" top of footing
Pa vine1. deDth • . . .
ART. 3.] ABCH CULVEBTS. 429
648. Atchison, Topeka and Santa F6 Arch Culverts. Plates
IV and V show the standard semi-circular and segmental arch cul-
verts used by the Atchison, Topeka and Santa Fe Railroad.*
Tables 51 and 52 give the dimensions and contents for the
several spans. Notice that the heights of the end walls do not vary
uniformly, that for the 12-foot span being proportionately too great;
.and consequently the contents of the end walls and of the wings do
not vary uniformly. The contents of the facing of the wings were
•computed for courses 18 inches thick (see § 557)., and the backing
was computed 011 the assumption that the back surface was a plane
such that the dimension at the outer end and also where a plane
parallel to the section E-E passes through the corner of the end
wall is as in the diagram.
In computing the masonry in a given culvert, these tables are to
be employed as already explained i'or Tables 49 and 50 — see §§ 645
and 647.
649. Standard Arch Culvert. The culvert shown in Plate VI
has been designed in accordance with the principles laid down
in the preceding discussion (§§ 638-41). The wings are joined to
the body in such a manner as to offer the least possible resistance
to the passage. of water and drift. If the current is slow and not
liable to scour, the paving may be omitted, since the end walls, being
continuous under the ends of the water way, will prevent under-
mining of the side walls; or, in long culverts, one or more inter-
mediate cross walls may be constructed. But ordinarily the money
paid for paving is a good investment. If the current is very rapid,
it is wise to grout the paving, — and also to inspect the structure
f requen bly.
The arch ring is amply strong to support any bank of earth (see
Table 63, page 502, particularly Nos. 9, 12, 18, 53, 54, and 61).
The strains in a masonry arch can not be computed exactly; but the
best method of analysis (§ 688) shows that if the earth is 10 feet
thick over the crown, the maximum pressure is not more than 55
pounds per square inch (compare with §222 and also t§§ 246-48).
A greater thickness of earth at the crown would doubtless increase
the maximum pressure in the arch; but proportionally the pressure
would increase much less rapidly than the height of the bank (see
* Published by permission of A. A. Robinson, Chief Engineer.
430
CULVERTS.
[CHAP. xvii.
£ •: 232 2 ^
d
co
"£i * - - - -3
O - - - " y
*^- CO i-<
"f O QO •** CO O5 O
no
H
04 ?2 Oi T~' "* T-1 ^ « =° £> *>
10 Ctt Old CO OCO
CO C5 !.>• O
w-J
CC - „ ..
P
O
w
s
it* r-i L- Qt O ^ MO CO O T-< CO
°*
g a sss Srf
fl
co co" ^^ -HTr^t-" co
22 oJ ^sSo §0
-3
JH
% ~c$ 3
O (M (M (NW OQO
CO t— iCi O
fj
^
M s — - -
g
o
J
CM
1~ OOti'i-l 0 t_ T^O O 0 t- CO
3 - - - - -3
o o
»ra t- oo
M
-S
t/3
3
53 i-< & c*t
TH C5 t- 1^. t- JO O
06 i-3 r-i o ^r o o
0* «0 CO OJ
cc
§?
02
to ,, ^ ^
rVj
SI
"w
E* C££*OCD °Scooooo
^ ^
O
o - * - "5
EH
aM
10 -^ co co ot TP m
*
S S§* °° '" -frcD^o
oq i-i I-H «o QO o o*
G* 1O O4 CO
co
fl
s §
5 s s s s - ^
H
a ^
«
CO
i.- So t- TMO^''— OCOOOICO
CJ S
o ' - - - - o
O* CO CD
w
H
OPBK
3 £
§ *
-
s SSoM -«.»a.
CS O O*OO COO
CJ r-I ^'cOOT Orh
H
s 1
*•" ^
i
H
g 1
CD
O *-J O O O o^O O CO gj Q3
3 rrr. ° n
S- o) ® 3 a
- z a o o
»ra t- 2 ° o
1
.2
O)
oS <M
• o
g d d d§
o
OQ
bO
O
:S : : i : : : : i : : :
:S : : : :^ : : : g1 .J,
la fl • • ••§ •
tr
0?
a
i~i
DIMENSIONS AND Coi
DimeDsi(
e
:
i
4
DIMENSIONS:
End wall, length
height— top of footing t
coping
Coping, length
Arch, thickness at crown
41 at springing
number of voussoirs (arch si
width of voussoirs at intradc
Side wall, thickness at springing.
" l* top of fool
height of. above top of {
Wing, length for slope of H to 1 .
thickness at bottom of sect
CONTENTS:
Two end walls, above footing. . . .
Arch, per foot of length— inside
end walls
Two side walls, per foot of leug
inside of end walls
Four wings, facing— slope 1 J to 1 .
backing " " " ".
Paving, per foot of length— out t
walls
Coping, on two end walls
ART. 3.]
ARCH CULVERTS.
431
RTi
p
o
3 "
§ B
^ 5
p H
1
^ a
M 3
!?.
-jj CD
K d
3 «
s •§
II
a
»5
1
o
O
§
co
I
<M
to
£- QO t>- xji O OO CO C4 O 1O £TcO CO CO 1-1 O
| S !SS r .
*"• <M
^L i:: •;§'
«O OJ OO t— O OS
c5 05c5SSw'~<o:"n *-< *o co TT t> ^
O C5 O OO COO
w - ^j^o»" oo
Oi
<M
T
l^" Tt« I? CO O* «^ o O t- „ £?rs T-I O ^ O
t^ «w
S3 - - - - - fl
y - - - - - ^
MI Cft irj TH CO O>. *H W Tf T-l O CO lO I- Tf*
C* Ol T-l 1-1 T~|
ot ci «o os o o
J.~ co O t- iQ CO O
0 ^ WOOD' 0|
w - .. ^
•a - - - • - -
^
C*
I- «Dj.«.on<oxht-cc o cs ca o QO co
O)
>> «w
S - - - - -3
o - - - - - 0
JO •"* OO
fc
-<)
c> as eg o r-j ot r-< CN^ i-trMniot-^
,_, -— , ^, js_ Tfl iP.
O CJ Ci t- 00 O O
SJ ~ "S2 °'S
1
00 . . «
ra - - r s - ^
43
o
T-l
"~ ^ m»
1- M I- T»* Z> 00 03 ^ O CM CO CO O T-l O
OS
f*» tw
g = * = s = g
CO CO iPOt-. CO
CM CM T-I
O T-( •»-. lO CO O CO
TH 04 00
w , ^
T3 - - - - - ^
4J
«H
00
H* HooHs.^ 0 ^, ^ „ QQ ^0^ w 0 o 50
T-1 t>
&•» 53
S - - - - -S3
o - - - - - o
I> O CO
00 OOOS5OI-T-HHCMK> T-c^O^iOOB
O CO CO -1<T-< CO O
co* o' Tx'cio" ooo'
50 tO
T3 - - -Oj.
£5
CO
.4, IHHI^I -*• WI<H flp 33
CS »"1?*OOOOJ.-CO -r-COOSOj-r-
»-rt oo
•« >»,.......*.. . . - c a
k> k.G
S - - g§ dS
« - oo ° °
os 1-- c C Q
^_, -------. - - . « ^
00 <OOSXO?OT-<T-(T-ICO OOOCOCO
T-( t-1
o
S S U ioo
odd o'co
io S :::•§: :
a ::::::::.::::::
3 :::::::::: : : ji "«fe
;I;;;;i;;.;;j;^
: CD «::**::
•*w -g . . . o • •
: = a : : : 4* . :
! Q iT i : : § : :
s : : : :~ : : : :| : go : s
bp : ' : a>* i ':ghioojf
•1 : : : " :« :^5«2aow
o ! • : S :-?^ rrS^S^
:2 3 : ! :o : i
• CD bo ...*-..
••a a »-<.: 4J • •
:TS £ o: s : :
w.s ,M i ? : ;
s
1
5 : : : ^jHcSxag-a
"S i igg^^llaS'So^o
fillliill§i3£:4i
TSf :^figS:= ^§i 5^«
siujf"!" °£^^1^
Uibco^o* °« «-*S a .Sf«M a>
„ is°g| Jisss|5s a||
8 = ~T II |li If
0 g g,u *.- B^g -«
«i p £ rf "^ to
g -0 5, o «2 .=
H a o «- 2S
S W C-«1 02 1^
Q
CONTENTS:
Two end walls, above footii
Arch, per foot of length-
end walls
Two side walls, per foot c
inside of end walls
Four wings, facing— slope :
backing " '
Paving, per foot of length
walls
Coping, on two end walls. .
432 CULVERTS. [CHAP. xvn.
§ 619). The arch is also stable under any position of the moving
load, with either a heavy or a light embankment. The joints of
the abutment are radial, to prevent any possibility of failure by
the sliding of one course on another (see § 674).
Table 53 (page 433) gives the dimensions and contents of various
sizes. In each case the rise is one fifth of the span,, the central
angle is 87° 12', and the height of the opening is equal to half the
.span. The paving and coping were each assumed to be 1 foot thick;
but for any other thickness it is only necessary to increase or de-
crease the tabular numbers proportionally. The contents of the
wings were computed on the assumption that all the courses were 1
foot thick (see § 557).
650. QUALITY OF MASONRY. The masonry of arch culverts is
usually divided into two classes; the first consists of the masonry in
the wings and end walls (parapet), and the second of the arch
.stones. The former is classified as first-class or second-class nia-
:Sonry (see §225). Only the masonry in the arch stones is called
arch masonry. The arch stones which show at the end of the arch
are called ring stones, and the remainder of the arch stones the
.arch sheeting. The arch masonry proper is usually classified as
first-class or second-class arch masonry. The distinction between
these two classes is usually about as in the specifications below.
651. Specifications.* Foundations. "When the bottom of the pit is
common earth, gravel, etc., the foundations of arch culverts will generally
•consist of a pavement formed of stone, not less than twelve inches (12") in
depth, set edgewise, and secured at the ends by deep curbstones which nuist
be protected from undermining by broken stone placed in such quantity and
position as the engineer may direct. When the bottom upon which a culvert
is to be built is soft and compressible, and where it will at all times be
covered with water, timber well hewn, and from eight (8) to twelve inches
{12") in thickness, according to the span of the culvert, shall be laid side by
side crosswise upon longitudinal sills; and when the position of the culvert is
such that a strong current will be forced through during floods, three courses
of sheet piling shall be placed across the foundation — one course at each end,
and one in the middle, — which shall be sunk from three (3) to six feet (6')
below the top of the timber, according as the earth is more or less compact, "f
652. First-Class Arch Masonry. ''First-class arch masonry shall be built
in accordance with the specifications for first-class masonry [§ 225], with the
exception of the arch sheeting and the ring stones. The ring stones shall be
* See also Specifications for Railroad Masonry, Appendix 1.
t Pennsylvania Railroad.
AJttT. 3.]
AECH CULVEETS.
433
. o
CO
«
32 33
O
os in
CO CO JO t»-
5 SgSsg^-S — —8-
CO «O
OS 7-H
OO O5
w
<M
C">T""t CO y~(
3* =
0
JO ^
33 33*
W
St» coco
1
S ^go^^^o -^co,^
CO T-<
^s °s
1
I
CD
CM
^ CO 0 rtW
3 -
o
S 8
- 3*
- - - t)
O *-
Q
d
*
CM "
CO 7-1
S3 S|
z/f
fi
en
s
p
.
CD
"3
CM
O
. 0^00^ = 0*00,0
^H Ci
33 33
O GO COt-
M
•<
fi
H
H
*H
s «s^a— a — »»$;«
7-i 0
^"S ^co"
ft
3
CO
1C
3
W
£
§
PH
03
4
a
1
CM
00
CO CM 03
•^ a'j xh cs co c- T- os i-T» o o co o
P»> "
3 -
o -
&t o
— = g
,3
S
ft
«<
P2
£
co j>^ir;o5^oco o««^^«
05 o
005 Ol^
s
t-l
O
«1
^•j
as
S
p
ft
PS
0
ft
I
CM
«0
CM Tf| "* Mte
CM OCM^CMoiot-' r-jOOOj-jtD
o •*
i— i •rf
\o co
33 "3
0
S O5 OOt-
ft
CO
'o
.^
a
T-> CO CM Tf t- »-i O CO OCMCOCO'HC*
• o •
CO 0
OC» OCO
r-l 13^
0
a
02
•:g : : : : : : : 1 : : :- : : :
• S • : * : c • •
•O"*'". 4j J-q
; m
;1
'55 • • ° • •
•S : :"§ :
r-l ' ' e *
•fi
1
.5 : : ig* : : :^^'-g^ 'a
i«
5 : :2 :
be : :^ :
§ • :§ :
o
''•f3 : " o ' ' ;« S-«g 0*0 g
^s
•2 : :? :
s
3
t
i
E
H
1
H
1
jfs |s|sa|||J'|3
QQ & C «• ^ bfl
| | If ||
CONTENTS:
Two end walls, above footin
Arch, per foot of length— i
end walls
Two side walls, per foot o
inside of end walls
Four wings— slope H to 1 ...
Paving, per foot of length
walls
Coping, on two end walls. .,
CULVERTS. [CHAP, xvn,
dressed to such. shape as the engineer shaft direct. The ring stones and the
arch sheeting shall be of stone" not less than ten inches (10") thick on the
imrados, shall be dressed with three eighths of an inch (f ") joints, and shall
be of the full depth specified for the thickness of the arch; and the joints
shall be at right angles to the surface of the intrados. The face of sheeting
stones shall be dressed to make a close centering joint. The ring stones and
the sheeting shall break joints not less than one foot (!')•
" The wings shall be neatly stepped with selected stones of the full width
of the wing arid of not less than ten inches (10") in thickness, which shall
overlap by not less than eighteen inches (18"); or shall be finished with a-
neatly- capped newel at the free end, and a coping course on the wing. The
parapets shall be finished with a coping course not less than ten inches (10")
thick and of the full width of the parapet, which shall project six inches (6").
653. Second- Clans Arch Masonry. "Second-class arch masonry is the
same as second-class masonry [§225], with the exception of the arch sheeting.
The stones of the arch sheeting shall have a good bearing throughout, and
shall be well bonded and of the full depth of the thickness of the arch. No
stone shall be less than four inches (4") in thickness on the intrados. Ring
stones of all arches over eight feet (8') span shall be dressed according to
specifications for first-class arch masonry [§ 651]." *
654. Pamng. For specifications for Paving, see § 219 (page 148), and
also Specifications for Railroad Masonry, Appendix I.
655. COST. §§ 226-38 contain data on the cost of masonry, of
whicli the last is a summary. Table 17 (page 159) contains a de-
tailed statement of the actual cost of the masonry in an arch
culvert; and below are the items of the total cost of that culvert.
613 cxi. yds. of masonry @ $6.59, ........ 14,036.85
Excavations — foundations and drainage, ...... 263.36
Sheet piling .................. 19.69
Concrete, ................. 43.75
Extra allowance on sheeting stones,' ........ 20.00
Total cost of culvert, $4,383.65
The total cost of the culvert per yard of masonry is $7.16, — which
is unusually low.
Below is the total actual cost of the 8-ft. culvert (length out to
out of end walls = 30 ft.) for which the quantities were estimated
in § 645 (page 424).
* Atchison, Topeka and Santa F<5 R. R.
ART. 3.]
ARCH CULVERTS.
435
Wall masonry— 48.7 cu. yds. @ $7.00, $340.90
Arch masonry— 28.7 " " " 8.50, . 243.95
Timber— 5,247ft., B M., @ $40. 00, 209.88
Excavating foundations and straightening stream 158 cu.
yds. @50c., 79.00
Total cost of culvert $873.73
The total cost of this culvert per cubic yard of masonry is $11.29.
The average total cost of a number of representative culverts of
this style was $11.46 per cubic yard of masonry, being practically
constant for all spans.
656. Illinois Central Culverts. Table 54 gives the cost of cul-
verts 25 feet long — out to out of end walls — of various spans of the
general plan shown in Plate II, and will be very nseful in estimat-
ing the cost of such culverts. The quantities of masonry necessary
to compute Table 54 were taken from Table 49 (page 425). The
prices are believed to be fair averages (see page 160) for the first-
class masonry described in § 651. The prices are the same as
actually paid by the Illinois Central Railroad, except for arch
masonry and excavation, for which $8.50 and 50c. respectively were
paid. The prices used in deducing the table are given therein, and
hence the results can be modified for prices differing from those
there employed by simply taking proportional parts of the tabulated
TABLE 54.
COST OF ILLINOIS CENTRAL ARCH CULVERTS 25 FT. LONG FROM OUT TO
OUT OF END WALLS, AND ALSO OF EACH ADDITIONAL FOOT.
FOR DESCRIPTION SEE PAGE 424.
ITEMS.
SPAN.
6ft.
8ft.
10ft.
12ft.
Plain masonry (5i $7 00 per cu yd - •
$237.35
151.29
150.88
12.48
$325.29
191.29
188.12
15.85
$424.97
255.29
232.84
19.22
$455.98
362.82
268.92
21.38
Timber and plank at $40 per M. ft., B. M
Total cost of culvert 25 ft long
$552.00
$3.11
6.05
3.36
.32
$720.55
$3.11
7.65
3.84
.40
$932.32
$3 11
10.21
5.04
.48
$1,109.10
$3 63
14.51
5.88
.56
COST OF AN ADPTTIONAL FOOT OF LENGTH:
Timber and rilank (d), $40 per M f t B M ......
$12.84
$15.00
$18.84
$24.48
436
CULVERTS.
[CHAP. xvn.
quantities. The amount of excavation used in computing the table
is the mean of the actual quantities for a number of representative
culverts as constructed on the above road.
657. Chicago, Kansas and Nebraska Culverts. Table 55 is given
to facilitate estimating the cost of culverts of the general form
shown in Plate IJL The prices are about the average for the
respective kinds of work; but. in case it is desired to determine the
cost for other prices, it is only necessary to increase or decrease the
tabular numbers proportionally. The quantities of excavation are,
approximately, averages of the actual amounts for a number of
similar culverts, and are equivalent to a pit 2 feet 2 inches deep and
of an area equal to the area of the foundation. The table includes
only one footing course, but in so doing it is not intended to imply
that one is always, or even generally, enough. Notice that the cul-
vert in Table 55 is 25| feet long from, outside to outside of end
walls, and hence is one third of a foot longer than that presented in
Table 54.
658. A., T. and S. F. Semi-circular Culverts. Table 56 is similar
to the two preceding ones, and shows the cost of the Atchisou,
TABLE 55.
COST OF d K. AND N. ARCH CULVERTS 20 FT. LONG FROM INSIDE TO
INSIDE OF COPING, AND ALSO OF EACH ADDITIONAL FOOT OF LENGTH.
FOR DESCRIPTION SEE PAGE 427.
This table includes one footing course.
SPAN.
ITEMS.
3ft.
4ft.
6ft.
8ft.
10ft.
Plain masonry @ $7.00 per on. yd
Arch masonry <Ta 8 00 " •• ' •-
Paving © 2.00 u " "
Excavation @ .2r> " " "
$-217.08
4-1. f>4
4.4-2
7.44
$397.04
79.03
0.32
9.33
$657 23
130.78
10.16
12.42
$703.43
239.92
13.96
13.95
$853.16
34fi.OO
17.76
14.99
Total cost of culvert 20 ft. long . .
$•274.48
$491.72
$810.59
$971.26
$1,232.87
COST OF AN ADDTTIONAL FOOT OP i
LKNOTH: 1
Plain masonry @, $7.00 per cu. yd
Arch masonry @, 8.00 '• "• "
Paving @. 100 " "
Excavation @ .25 " "• "
$1 14
•2.30
17
23
$6.17
4.06
25
.27
$9.33
6.72
.40
.35
$9.67
10.06
.54
.39
$10.97
14.55
.69
.45
Total cost of 1 additional foot
$6.84
$10.75
$16.80
$20.66
$26.60
ART. 3.]
AECH CULVERTS.
437
Topeka and Santa Fe's standard semi-circular arch culvert as given
in Plate IV and Table 51 (page 430). The excavation is only ap-
proximate, and is computed on the assumption of a pit 2 feet 2
inches deep for the entire foundation including the paved area; •?'. e.,
the excavation is computed on the same basis as the two preceding.
Notice that this culvert is 23 feet between the outer faces of the
end walls., and hence is 1 foot shorter than that of Table 54 and 2J-
feet shorter than that of Table 55.
TABLE 56.
COST OF A. T. AND S. F. SEMI-CIRCULAR ARCH CULVERTS 20 FT.
FROM INSIDE TO INSIDE OF THE COPING, AND ALSO OF EACH ADDI-
TIONAL FOOT OF LENGTH.
FOB DESCRIPTION SEE PAGE 429.
This table does not include the masonry in the footings.
SPAN.
6ft.
8ft.
10ft.
12ft.
14ft.
16ft.
Plain masonry (& $7.00 per cu. yd.
Arch masonry " 8.00 " " u
Paving " 2.00 " " "
Excavation " .25 " " '"
Total cost of culvert 20 ft. long.
$325.15
140.72
9.88
6.93
$766.42
197.28
13.15
13.51
$997.14
270.32
36.42
16.01
$1,071.42
356.04
19.68
18.21
$1,328.12
418.40
22.99
21.10
$1,785.91
516.48
26.26
24.44
$482.68
$990.36
$1,299.89
$1,465.35
$1,790.61
$2,353.09
COST OF AN ADDITIONAL FOOT
OF LENGTH:
Plain masonry ©, $7.00 per cu. yd.
Arch masonry " 8.00 " ** "
Pavinjj " 2.00 " " "
Excavation " .25 l< " "
Total cost of 1 additional foot
$5.44
6.12
.52
.28
$8.49
8.58
.69
.32
$11.66
11.75
.86
.40
$12.44
15.48
1.04
.44
$14.98
18.19
1.21
.48
$19.48
22.46
1.38
.54
$12.36
$18.08
$24.68
$29.50
$34.86
$43.86
659. A., T. and S. F. Segmental Culverts. Table 57 is similar to
the three preceding., and is given to facilitate estimating the cost of
segmental arch culvert's of the standard form employed by the
Atchison, Topeka and Santa Fe Bailroad, as shown in Plate V and
Table 52 (page 431). The excavation is only approximate,, and is
computed on the assumption of a pit 2 feet 2 inches deep over the
entire foundation, including the paved area. Notice that this
culvert is 23 feet between the outer faces of the end walls, and is
therefore the same length as that of Table 56.
438
CULVERTS.
[CHAP. xvn.
TABLE 57.
COST OF A. T. AND S. F. SEGMENTAL ARCH CULYEKTS 20 FT. LONG
FROM INSIDE TO INSIDE OF THE COPING, AND ALSO OF EACH ADDI-
TIONAL FOOT OF LENGTH,
FOR DESCRIPTION SEE PAGE 429.
TMs table does not include the masonry in the footings.
ITEMS.
SPAN.
6ft.
8ft.
10 ft.
12ft.
14ft.
16ft.
Plain masonry ® $7.00 per cu. yd
Arch masonry " 8.00 " " u
Paving " 2.00 " " "
Excavation " .25 " " li
Total cost of culvert 20 feet long. . . .
COST OF AN ADDITIONAL FOOT OF
LENGTH:
Plain masonry ® $7.00 per cu. yd
Arch masonry " 8.00 " " lk
Paving " 2.00 " " "
Excavation k< .25 " " "
Total cost of 1 additional foot
$183.45
99.18
9.88
7.33
$470.34
150.33
13.15
11.75
$607.99
190.99
16.42
14.11
$657.83
229.12
19.68
15.17
$641.41
298.64
22.99
16.45
$669.13
353 84
26.26
17,82
$299.84
$5.44
4.31
'.'31
$645.57
$9.73
6.54
.69
.39
$829.51
$12.96
8.30
.86
.46
$921.80
$13.61
9.96
1.04
.50
$979.49
$14.47
12.98
1.21
.56
$1,067.05
$14.56
15.88
1.38
.62
$10.58
$17.35
$22.58
$25.11
$29.22
$31.94
660, Standard Arch Culvert, Table 58 is given to facilitate the
estimation of the cost of culverts of the general form shown in Plate
VI. The prices are about the average for the respective kinds of
work; but in case it is desired to determine the cost for other prices,
TABLE 58.
COST OF STANDARD ARCH CULVERTS 20 FT. LONG FROM INSIDE TO INSIDE
OF THE COPING, AND OF EACH ADDITIONAL FOOT OF LENGTH.
FOR DESCRIPTION SEE PAGE 429.
The masonry in the footings is not included in this table.
SPAN.
6ft.
8ft.
10ft.
12ft.
14ft.
16ft.
Plain masonry @ $7.00 per cu. yd ....
Arch masonry " 8.00 " " "
Paving " 2.00 " " "
Excavation u .25 " " "
Total cost of culvert 20 feet long . . .
COST OP AN ADDITIONAL FOOT OF
LENGTH:
Plain masonry @ $7.00 per cu. yd ...
Arch masonry " 8.00 " %l "...
Paving " 2.00 " " "...
Excavation " .25 " " " ...
Total cost of 1 additional foot
$233.11
65.87
6.83
8.24
$330.88
92.72
9.84
9.53
$496.79
127.33
12.65
12.42
$683.55
184.00
15.47
15.42
$912 45
238.64
18.28
18.33
$1,193.35
305.62
20.09
20.61
$314.05
$3.88
2.86
.37
.21
$442.97
$6.56
4.03
.52
.26
$649.19
$9.85
5.54
.07
.31
$898.44
$14.00
8.00
.81
.36
$1,187.70
$18.75
10. 3K
.J>6
.41
$1,539.67
$24.28
13.29
1.11
.46
$7.32
$11.37
$16.37
$23.17
$30.50
$39.14
ART. 3.] ARCH CULVERTS. 439
it is only necessary to increase or decrease the tabular numbers
proportionally. The quantities of excavation are, approximately,
averages of the actual amounts for a number of similar culverts,
and are equivalent to a pit 2 feet 2 inches deep and of an area equal
to the area of the foundation. Notice that the culvert in Table 58
]s 23 feet between the outer faces of the end walls; and is therefore
the same length as that in Tables 56 and 57, and is 1 foot shorter
than that of Table 54 and &J- feet shorter than that of Table 55.
Notice also that in Table 58 the height of the opening is in each
•case half of the span (see Table 53, page 433), while in Tables 56
and 57 the height of the opening is nearly the same for all spans
(see Tables 51 and 52, pages 430, 431).
CHAPTER XVIII.
ARCHES.
661. DEFINITIONS. Parts of an Arch.. Voussoirs. The wedge-
shaped stones of which the arch is composed ; also called the arch-
stones.
Keystone. The center or highest voussoir or arch-stone.
Soffit. The inner or concave surface of the arch.
lutrados. The concave line of intersection of the soffit, with a
vertical plane perpendicular to the axis or length of the arch. See
Kg. 110.
Extrados. The convex curve, in the same plane as the intrados,.
which bounds the outer extremities of the joints between the
voussoirs.
Crown. The highest part
of the arch.
Skewback. The inclined
surface or joint upon which
the end of the arch rests.
Abutment. A skewback
and the masonry which sup-
ports it.
Springing Line. The in-
ner edge of the skewback.
(Springer. The lowest voussoir or arch-stone
Haunch. The part of the arch between the crown and the-
skewback.
Spandrel. The space between the extrados and the roadway.
The material deposited in this space is called the spandrel filling,
and may be either masonry or earth, or a combination of them. In
large arches it often consists of several walls running parallel with
the roadway, connected at the top by small arches or covered with
nat stones, which support the material of the roadway.
440
FIG. 110.
KINDS OF ARCHES. 441
Span. The perpendicular distance between the springing
lines.
Rise. The vertical distance between the highest part of the
intrados and the plane of the springing lines.
Ring Stones. The voussoirs or arch-stones which show at the
ends of the arch.
Arcli Sheeting. The voussoirs which do not show at the end
of the arch.
Backing. Masonry, usually with joints horizontal or nearly
so, carried above the skewbacks and outside of the extrados.
String Course. A course of voussoirs extending from one end
of the arch to the other.
Coursing Joint. The joint between two adjoining string
courses. It is continuous from one end of the arch to the
other.
Heading Joint. A joint in a plane at right angles to the axis
of the arch. It is not continuous.
Ring Course. The stones between two consecutive series of
heading joints.
662. Kinds of Arches. Circular Arch. One in which the
intrados is a part of a circle.
Semi-circular Arch. One whose intrados is a semi-circle; also
called a full-centered arch.
Segmcntal Arch. One whose intrados is less than a semi-
circle.
Elliptical Arcli. One in which the intrados is a part of an
ellipse.
Basket-Handle Arcli. One in which the intrados resembles a
semi-ellipse, but is composed of arcs of circles tangent to each
other.
Pointed Arch. One in which the intrados consists of two arcs
of equal circles intersecting over the middle of the span. For ex-
ample, see Pigs. 115 and 117, page 447.
Hydrostatic Arch. An arch in equilibrium under the vertical
pressure of water.
Geostatic Arch. An arch in equilibrium under the vertical
pressure of an earth embankment.
Catenarian Arch. One whose intrados is a catenary.
663. Right Arch. A cylindrical arch, either circular or el-
442
ARCHES.
[CHAP. xvin.
liptical, terminated by two planes, termed heads of the arch, at
right angles to the axis of the arch. See Fig. 111.
*Jss^
FIG. 111.— RIGHT ARCH.
FIG. 112.— SKEW ARCH,
* SJceiv Arch. One whose heads are oblique to the axis. See
Kg. 112. Skew arches are quite common in Europe, but are
rarely employed in the "United States ; and in the latter when
an oblique arch is required, it is usually made, not after the
European method with spiral joints as shown in Fig. 112, but
by building a number of short right arches or ribs in contact
with each other, each successive rib being placed a little to one
side of its neighbor.
Groined and Cloistered Arches. Those formed by the in-
tersection of two or more cylindrical arches. The spans of
the intersecting arches may be different, but the rise must be
the same in each; and their axes must lie in the same plane,
but may intersect at any angle. The groined arch is formed
by removing those portions of each cylinder which lie under
the other and between their common curves of intersection,
thus forming a projecting or salient angle on the soffit along
these curves. The cloistered arch is formed by removing those
portions of each cylinder which are above the other and exterior
to their common intersection, thus forming re-entrant angles,
along the same lines.
DOME AND VAULT. If an arch revolves around a vertical
through the keystone, a dome is produced; and if it moves in
a straight line on the springer, a vault is produced. Hence
there are essentially the same kinds of domes and vaults as
arches.
Only right arches will be considered in this chapter.
LI2sTE OF RESISTANCE.
443
664. Line of Eesistance. If the action and reaction between
each pair of adjacent arch-stones be replaced by single forces so
situated as to be in every way the equivalent of the distributed
pressures, the line connecting the points of application of these
several forces is the line of resistance of the arch. For example,
assume that the half arch shown in Fig. 113 is held in equilibrium
by the horizontal thrust T — the reaction of the right-hand half of the
arch — applied at the middle of the joint C F. Assume also that the
\
FIG. 113.
several arch-stones fit mathematically, and that there is no adhesion
of the mortar. The forces Fl , F^ , Fs , and F^ represent the result-
ants of all the forces (including the weight of the stone itself) acting
upon the several voussoirs. The arch-stone CIHF is in equilib-
rium under the action of the three forces, T, Fl , and the reaction
of the voussoir IHEG. Hence these three forces must intersect
in a point, and the direction of jRj — the resultant pressure be-
tween the voussoirs CIHF and IHEG — can be found graphically
as shown in Fig. 113. The point of application of R^ is at b —
the point where R^ intersects the joint HL The voussoir GfEHl
444 ARCHES. [CHAP. xvnr..
is in equilibrium under the action of Rl , F^ , and J?2 — the resultant-
reaction between OEHI and GEDH, — and hence the direction,
the amount, and the point of application (6*) of J?2 can be deter-
mined as shown in the figure. J23and J?4 are determined in the same
manner as Rt and J2a .
The points a, b, cy d, and e} called centers of pressure, are the
points of application of the resultants of the pressure on the several
joints ; or they may be regarded as the centers of resistance for the
several joints. In the latter case the line abcde would be called
the line of resistance, and in the former the line of pressure.
Strictly speaking,, the line of resistance is a continuous curve cir-
cumscribing the polygon abcde. The greater the number of
joints the nearer the polygon abcde approaches this curve. Occa-
sionally the polygon mnop is called the line of resistance. The
greater the number of joints the nearer this line approaches the
line of resistance as defined above. For an infinite number of joints-
the polygons abcde and mnop coincide with the curved line of re-
sistance, a, b, cy dy and e being common to all three.
Notice that if the four geometrical lines ab, "be, cd, and de were
placed in the relative position shown in Fig. 113, and were acted
upon by the forces T, F1 , F^ , F3 , F4 , and R, as shown, they would
be in equilibrium ; and hence the line abcde, or rather a curve
passing through the points a, b, c, d, and e, is sometimes called a-
linear arch.
AKT. 1. THEOEY OF THE ARCH.
665. The theory of the masonry arch is one of great com-
plexity. Numerous volumes have been written on this subject, and
it still occupies the attention of mathematicians. No attempt will
be made here to give an exhaustive treatise on the arch ; but the
fundamental principles will be stated as clearly as possible, and the
principal solutions of the problem which have been proposed from
time to time will be explained and their underlying assumptions,
pointed out.
666. THE EXTERNAL FORCES. It is clear that before we can
find the strains in a proposed arch and determine its dimensions,
we must know the load to be supported by it. In other words,
the strength and stability of a masonry arch depend upon the
ART. 1.] THEORY OF THE ARCH. 445
position of the line of resistance ; and before this can be deter-
mined, it is necessary that the external forces acting upon the arch
shall be fully known, i. e., that (1) the point of application, (2) the
direction, and (3) the intensity of the forces acting upon each
voussoir shall be known. Unfortunately, the accurats determina-
tion of the outer forces is, in general, an impossibility.
1. If the arch supports a fluid, the pressure upon the several
voussoirs is perpendicular to the extrados, and can easily be found ;
and combining this with the weight of each voussoir gives the
several external forces. This case seldom occurs in practice.
2. If the arch is surmounted by a masonry wall, as is frequently
the case, it is impossible to determine, with any degree of accuracy,
the effect of the spandrel walls upon the stability of the arch. It
is usually assumed that the entire weight of the masonry above the
soffit presses vertically upon the arch; but it is known certainly
that this is not the case, for with even dry masonry a part of the
wall will be self-supporting. The load supported by the arch can
be computed roughly by the principle of § 250 (p. 168); but, as this
gives no idea of the manner in which this pressure is distributed, it
is of but little help. The error in the assumption that the entire
weight of the masonry above the arch presses upon it is certainly on
the safe side; but if the data are so rudely approximate, it is use-
less to attempt to compute the strains by mathematical processes.
The inability to determine this pressure constitutes one of the limi-
tations of the theory of the arch.
Usually it is virtually assumed that the extradosal end of each
voussoir terminates in a horizontal and vertical surface (the latter
may be zero); and therefore, since the masonry is assumed to press
only vertically,- there are no horizontal forces to be considered. But
as the extrados is sometimes a regular curve, there would be active
horizontal components of the vertical pressure on this surface; and
this would be true even though the spandrel masonry were divided
by vertical joints extending from the extrados to the upper limit of
the masonry. Further, even though no active horizontal forces are
developed, the passive resistance of the spandrel masonry — either
spandrel walls or spandrel backing — materially affects the stability
of an arch. Experience shows that most arches sink at the crown
and rise at the haunches when the centers are removed (see Fig.
116, p. 447), and hence the resistance of the spandrel masonry will
446 ARCHES. [CHAP. xvni.
materially assist in preventing the most common form of failure.
The efficiency of this resistance will depend upon the execution of
the spandrel masonry., and will increase as the deformation of the
arch ring increases. It is impossible to compute, even roughly,' the
horizontal forces due to the spandrel masonry.
Further,, in computing the strains in the arch, it is usually
assumed that the arch ring alone supports the masonry above it j
while, as a matter of fact, the entire masonry from the intrados to
the top of the wall acts somewhat as an arch in supporting its own
weight.
3. If the arch supports a mass of earth, we can know neither the
amount nor the direction of the earth pressure with any degree of
accuracy (see Chap. XIV — Retaining Walls, — particularly § 527,
page 339). We do know, however, that the arch does not support
the entire mass above it (see §§ 618-20). No one ever thinks of
trying to make a tunnel arch strong enough to sustain the weight of
the entire mass above it.
In the theory of the masonry arch, the pressure of the earth is
usually assumed to be wholly vertical. That the pressure of earth
gives, in general, active horizontal forces appears to be unquestion-
able. An examination of Fig. 113 (page 443) will show how the
horizontal forces add stability to an arch ring whose rise is equal to
or less than half the span. It is clear that for a certain position
and intensity of thrust Ty the line of resistance will approach the
extrados nearer when the external forces are vertical than when
they are inclined. "We know certainly that the passive resistance of
the earth adds materially to the stability of masonry arches ; for the
arch rings of many sewers which stand without any evidence of
weakness are in a state of unstable equilibrium, if the vertical press-
ure of the earth immediately above it be considered as the only
external force acting upon it.
667. METHOD OF FAILURE OF AECHES. A masonry arch may
yield in any one of three ways, viz. : (1) by the crushing of the
stone, or (2) by the sliding of one voussoir on another, or (3) by
rotation about an edge of some joint. 1. An arch will fail if the
pressure on any part is greater than the crushing strength of the
material composing it. 2. Figs. 114 and 115 represent the second
method of failure ; in the former the haunches of the arch slide
AKT. 1.]
THEORY OF THE ARCH.
447
out and the crown slips down, and in the latter the reverse is
shown. If the rise is less than the span and the arch fails by the
sliding of one voussoir on the other> the crown will usually sink;
but if the rise is more than the span, the haunches will generally
FIG. 114.
FIG. 115.
be pressed inward and the crown will rise. 3. Figs. 116 and 117
show the two methods by which an arch may give way by rotation
FIG. 116.
FIG. 117.
about the joints. As a rule the first case is most frequent for flat
arches and the second for pointed ones.
However, more arches fail on account of unequal settlement of
the foundation than because of a faulty design of the arch proper.
668. CRITERIA or SAFETY. There are three criteria, corre-
sponding to the three modes of failure, by which the stability of an
arch may be judged. (1) To prevent overturning, it is necessary
that the line of resistance shall everywhere lie between the intrados
and the extrados. (2) To prevent crushing, the line of resistance
should intersect each joint far enough from the edge so that the
maximum pressure will be less than the crushing strength of the
masonry. (3) To prevent sliding, the angle between the line of
resistance and the normal to any joint should be less than the angle
of repose ("angle of friction") for those surfaces ; that is to say,
the tangent of the angle between the line of resistance and the
normal to any joint should be less than the co-efficient of friction
(§
448 ARCHES. [CHAP. xvm.
669. Stability against Rotation. An arch composed of incom-
pressible vonssoirs can not fail by rotation as shown in Fig. 116,
unless the line of resistance touches the intrados at two points and
the extrados at one higher- intermediate point (see Fig. 120, page
454); and an arch can not fail by rotation as shown in Fig. 117,
unless the line of resistance touches the extrados at two points
.and the intrados at one higher intermediate point (see Fig. 120).
The factor of safety against rotation about any point is equal
to half the length of the joint divided by the distance between
the center of pressure and the center of the joint ; that is to
the factor of safety = —-r- •, (1)
in which I is the length of the joint and d the distance between
the center of pressure and the center of the joint. For example, if
the center of pressure is at one extremity of the middle third of the
joint, d = -J- 1 ; and, by equation (1), the factor of safety is three.
If the center of pressure is £ I from the middle of the joint, the
factor of safety is two.
It is customary to require that the line of resistance shall lie
within the middle third of the arch ring, which is equivalent to
• specifying that the minimum factor of safety for rotation shall not
be less than three.
670. Stability against Crushing. The method of determining
the pressure on any part of a joint has already been discussed in the
chapter on masonry dams (see pp. 320-26). When the total press-
ure and its center are known, the maximum pressure at any part
of the joint is given by formula (23), page 323. It is
I
in which P is the maximum pressure en the joint per unit of area ;
W is the total normal pressure on the joint per unit of length of the
arch ; I is the depth of the joint, i. e., the distance from intrados to
extrados ; and d is the distance from the center of pressure to
the middle of the joint. This formula is general, provided the
ART. l.J THEORY OF THE ARCH. 449
masonry is capable of resisting tension ; and if the masonry is
assumed to be incapable of resisting tension, it is still general, pro-
vided d does not exceed -J- 1
For the case in which the masonry is incapable of resisting ten-
sion and d exceeds ^ I, the maximum pressure is given by formula
(24), page 324. It is
If the line of resistance for any arch can be drawn, the maximum
pressure can be found by (1) resolving the resultant reaction per-
pendicular to the given joint, and (2) measuring the distance d from.
•a diagram of the arch similar to Fig. 113 (page 443), and (3) sub-
stituting these data in the proper one of the above formulas (the
•one to be employed depends upon the value of d), and computing
P.* This pressure should not exceed the compressive strength of
the masonry.
It is customary to prescribe that the line of resistance shall lie
within the middle third of each joint, and also that the result
obtained by dividing the total pressure by the area of the joint shall
not be more than one twentieth of the ultimate crushing strength
of the stone. Under these conditions the maximum pressure is
twice the mean, and hence using the above limits is equivalent to
.saying that the maximum pressure shall not be more than one tenth
of the ultimate crushing strength of the stone. The mean pressure
in arches is usually not more than one fortieth or one fiftieth, and
.sometimes only one hundredth, of the ultimate compressive strength
of the stone or brick of which it is constructed.
671. Unit Pressure. In the present state of our knowledge it
is not possible to determine the value of a safe and not extravagant
unit working-pressure. The customary unit appears less extrava-
gant, when it is remembered (1) that the crushing strength of
masonry is considerably less than that of the stone or brick of which
it is composed (see §§ 221-22 and §§ 246-47 respectively), and that
we have no definite knowledge concerning either the ultimate or
the safe crushing strength of stone masonry (§ 223) and but little
* For a numerical example of the method of doing this, see 2, § 690.
450 ARCH-EC. [CHAP, xviii,
concerning that of brickwork (§ 248) ; and (2) that all the data we
have on crushing strength are for a load perpendicular to the
pressed surface, while we have no experimental knowledge of the
effect of the component of the pressure parallel to the surface of the
joint, although ic is prohable that this component would have some-
what the same effect upon the strength of the voussoirs as a sheet
of lead has when placed next to a block of stone subjected to com-
pression (§ 9).
On the other hand, there are some considerations which still
further increase the degree of safety of the usual working-pressure.
(1) When the ultimate crushing strength of stone is referred to, the
crushing strength of cubes is intended, although the blocks of stone
employed in actual masonry have less thickness than width, and
hence are much stronger than cubes (see § 14, paragraph 2 § 60, and
§ 273). To prevent the arch stones from flaking off at the edges,
the mortar is sometimes dug out of the outer edge of the joint.
This procedure diminishes the area under pressure, and hence
increases the unit pressure ; but, on the other hand, the edge of
the stone which is not under pressure gives lateral support to the
interior portions, and hence increases the resistance of that portion
(see § 273). It is impossible to compute the relative effect of these
elements, and hence we can not theoretically determine the efficiency
of thus relieving the extreme edges of the joint. (2) The preceding
formulas (2 and 3) for the maximum pressure neglect the effect of
the elasticity of the stone ; and hence the actual pressure must be
less, by some unknown amount, than that given by either of the
formulas.
672. Notice that the distance which the center of pressure may
vary from the center of the joint without the masonry's being
crushed depends upon the ratio between the ultimate crushing
strength and the mean pressure on the joint. In other words, if
the mean pressure is very nearly equal to the ultimate crushing
strength, then a slight departure of the center of pressure from the
center of the joint may crush the voussoir ; but, on the other hand,
if the mean pressure is small, the center of pressure may de-
part considerably from the center of the joint without the stone's
being crushed. This can be shown by equation (2), page 448,
W
If both P and -=- are large, d must be small ; but if P is large and
ART. 1.] THEORY OF THE ARCH. 451
W
-y small., then d may be large. Essentially the same result can be
/
deduced from equation (3), page 449.
Even though the line of resistance approaches so near the edge
of the joint that the stone is crushed, the stability of the arch is not
necessarily endangered. For example, conceive a block of stone
resting upon an incompressible plane,
AB, Fig. 118, and assume that the
center of pressure is at JV". Then the
pressure is applied over an area pro-
jected in A V9 such that AN= $A V.
The pressure at A is represented by K
AI\, and the area of the triangle *""»- 118-
AKV represents the total pressure on the joint. Assume that
AKiB the ultimate crushing strength of the stone, and that the
center of pressure is moved to N*. As before, the pressure is borne
on an area projected in A V'9 such that A N' = -J A V. The press-
ure in the vicinity of A is uniform and equal to the crushing
strength AK\ hence the total pressure on the joint is represented
by the area of the figure AKGV, which has its center of gravity
in the vertical through N'. Eventually, when the center of press-
ure approaches so near A that the area in which the stone is
crushed becomes too great, the whole block will give way and the
arch will fall.*
673. Open Joints. It is frequently prescribed, that the lino of
resistance shall pass through the middle third of each joint, "so
that the joint may not open on the side most remote from the lino
of resistance/' If the line of resistance departs from the middle
third, the remote edge of the joint will bo in tension ; but since
cement mortar is now quite generally employed, if the masonry is
laid with ordinary care, the jnint will be able to bear considerable
tension (see Table 13, page 04); and hence it does not necessa-
rily follow that the joint will open.
* Rankine says : "It is true that arches have stood, and Htlll stand, In which the
centers of resistance of joints fall beyond tho middle third of the depth of the arch
ring ; but the stability of such arches is either now preonrimiH, or muni; have boon
precarious while the mortar was fresh." The above is on« nuwon why the stability
of the arch is not necessarily precarious, and other reasons are found In $ (MWl and
also in the subsequent discussion. A reasonable theory of the arch will not make a
structure appear instable which shows every evidence of security.
452 ARCHES. [CHAP. xvin.
If the line of pressure departs from the middle third and tlio>
mortar is incapable of resisting tension, the joint will open on the
side farthest from the line of resistance. For example, if the
center of pressure is at N, Fig. 118, then a portion of the joint
A V (= 3 AN) is in compression, while the portion VB has no force
acting upon it ; and hence the yielding of the portion A Fwill cause
the joint to open a little at B. This opening will increase as the
center of pressure approaches A, and when the material at that
point begins to crush the increase will become comparatively rapid.
Notice that the opening of a joint does not indicate that the
stability of the arch is in danger. In most cases, an open joint is
no serious matter, particularly if it is in the soffit. If in the
extrudes, it is a little more serious, since water might get into it
and freeze. To guard against this danger, it is customary to cover
the extrados with a layer of puddle or some coating impervious to
water (§ 264). Notice also that if there are no open joints in an
arch, it is probable that the actual line of resistance lies within the
middle third of the arch ring.
674. Stability against Sliding. If the effect of the mortar is
neglected, an arch is stable against sliding when the line of resist-
ance makes with the normal an angle less than the angle of friction.
According to Table 36 (page 315) the co-efficient of friction of
masonry under conditions the most unfavorable for stability — /. <?.,
while the mortar is wet — is about 0.50, which corresponds to an angle
of friction of about 25°. Hence if the line of pressure makes an
angle with the normal of more than 25°, there is a possibility of
one voiissoir's sliding on the other. This possibility can be elimi-
nated by changing the joints to a direction more nearly at right
angles' to the line of pressure.
However, there is no probability that an arch will receive its full
load before the mortar has begun to set ; and hence the angle of
friction is virtually much greater than 25°. It is customary to
arrange the joints of the arch at least nearly perpendicular to the
line of resistance, in which case little or no reliance is placed on the
resistance of friction or the adhesion of the mortar.
675. Conclusion. From the preceding discussion, it will be
noticed that the factors of stability for rotation and for crushing
are dependent upon each other ; while the factor for sliding is
independent 'of the other conditions of failure, and is dependent
ART. 1.] THEORY OF THE ARCH.
only upon the direction given to the joints. A theoretically perfect
design for an arch would be one m which the three factors of safety
were equal to each other and uniform throughout the arch. As
arches are ordinarily built, the factor for rotation is about three, or
a little more ; the nominal factor for crushing is ten to forty ; and
the nominal factor for sliding is one and a half to two.
It is evident that before any conclusions can be drawn concern-
ing the strength or stability of a masonry arch, the position of the
line of resistance must be known ; or, at least, limits must be found
within which the true line of resistance must be proved to lie.
676. LOCATION OF THE TEUE LIME OF BESISTA¥CE. The de-
termination of fche line of resistance of a semi-arch requires that the
external forces shall be folly known, and also that (1) the amount,
(2) the point of application, and (3) the direction of the thrust at
the crown shall be known. The determination of the external
forces is a problem independent of the theory of the arch ; and for
the present it will be assumed that they are fully known, although
as a matter of fact they can not be known with any considerable
degree of accuracy (see § 666).
Each value for the intensity of the thrust at the crown gives a
different line of resistance. For example, in Fig. 113 (page 443),
if the thrust T be increased,, the point b — where Rl intersects the
plane of the joint HI — will approach /; and consequently c, tL
and e will approach G, H9 and A respectively. If T be increased
sufficiently, the line of pressure will pass through A or H (usually
the former, this depending, however, upon the dimensions of the
arch and the values and directions of Fl , jPa, and F9)9 and the arch
will be on the point of rotating about the outer edge of one of these
joints. This value of T is then the maximum thrust at a consistent
with stability of rotation about the outer edge of a joint, and the
corresponding line of resistance is the line of resistance for maxi-
mum thrust at a. Similarly, if the thrust Tbe gradually decreased,
the line of resistance will approach and finally intersect the in trades,
in which case the thrust is the least possible consistent with stabil-
ity of rotation about some point in the intraclos. The lines of
resistance for maximum and minimum thrust at a are shown in
Fig. 119 (page 454).
If the point of application of the force T be gradually lowered
and at the same time its intensity be increased, a line of resistance
454
AECHES.
[CHAP. xvm.
FIG. 119.
may "be obtained which, will have one point in common with the
intrados. This is the line of resistance for
maximum thrust at the crown joint. Simi-
larly, if the point of application of T be
gradually raised, and at the same time its
intensity be decreased, a line of resistance
may be obtained which will have one point
in common with the extrados. This is the
line of resistance for minimum thrust at
the crown joint. The lines of resistance
for maximum and minimum thrust at the crown are shown in
Fig. 120.
Similarly each direction of the
thrust T will give a new line of re-
sistance. In short, every different
value of each of the several factors,
and also every combination of these
values, will give a different position
for the line of resistance. Hence, the
problem is to determine which of the
infinite number of possible lines of
resistance is the actual one. This
problem is indeterminate, since there are more unknown quantities
than conditions (equations) by which to determine them. To
meet these difficulties and make a solution of the problem possible,
various hypotheses have been made ; but there is no unanimity of
opinion among authorities regarding the position of the true line
of resistance. Some of these hypotheses will now be considered
briefly.
677. Hypothesis of Least Pressure. Some writers have assumed
the true line of resistance to be that which gives the smallest abso-
lute pressure on any joint. This principle is a meta-physical one,
and leads to results unquestionably incorrect. Of the four hypo-
theses here discussed this is the least satisfactory, and the least
frequently employed. It will not be considered further.
For an explanation of Claye's method of drawing the line of
pressure according to this theory, see Van Nostrand's Engineering
Magazine, vol. xv, pp. 33-36. For a general discussion of the
theory of the arch founded on this hypothesis, see an article by Pro-
FIG. 120.
AET. L]
THEOHY OF THE ARCH.
455
fessor Du Bois in Van Nostrand's Engineering Magazine, vol. xiii,
pp. 341-46, and also Du Bois's "Graphical Statics/3 Chapter XV.
678. Hypothesis of Least Thrust at the Crown. According to
this hypothesis the true line of resistance is that for which the
thrust at the crown is the least possible consistent with equilibrium.
This assumes that the thrust at the crown is a passive force called
into action by the external forces ; and that, since there is, no need
for a further increase after it has caused stability, it will be the least
possible consistent with equilibrium.
This principle alone does not limit the position of the line of
resistance; but, if the external forces are known and the direction
of the thrust is assumed, this hypothesis furnishes a condition by
which the line of resistance corresponding to a minimum thrust can
he found by a tentative process. The principle* of least crown
•thrust was first proposed by Moseley,* was amplified by Scheffler,t
.and has been adopted more generally
by writers and engineers than any
other.
679. The half arch shown in Fig.
121 is held in equilibrium by (1) the
vertical forces, wl9 w» etc., (2) by the
horizontal forces hl9 hz9 etc., (3) by
the reaction R at any joint, and (4)
by the thrust T at the crown. The
•direction of R is immaterial in this
discussion. Let a and 1) represent the points of application of T
and R, respectively, although the location of these points is yet un-
determined. Let
T— the thrust at the crown;
xl = the horizontal distance from 1) to the line of action of w^
x^ = the same for w2, etc. ;
-X- i
>/£— x, * A
FIG. 121.
* Philosophical Magazine, Oct., 1833 — see Moseley's Mechanical Principles of En-
gineering, 2d American ed., p. 430.
t " Theorie der G-ewolbe, Futtermauern, und eisernen Briicken," Braunschweig,
1857. A French translation of this work is entitled " Traite* de la Stability des con-
structions ; Ire partie, The"orie des Voutes et des Murs de Soutenement," Paris, 1864.
Cain's " A Practical Theory of Voussoir Arches " — No. 12 of Van Nostrand's Science
Series— New York, 1*874, is an exposition of a theory of the arch based upon this
hypothesis.
456 ARCHES. [CHAP. xvm.
y = the perpendicular distance from 1} to the line of action of T;
fcj = the perpendicular distance from I to the line of action of
7^; 7c2 = the same for li^\ etc.
Then,, by taking moments about b, we have
Tij = Wj xl + wfl aa + etc. + \ kl + 7^a £2 + etc. ; . (4)
hence
2Ai ............ (
y y
1. The value of T7 depends upon 2 li k — the sum of the
moments of the horizontal component of the external forces; — but
we know neither the nature of the material over the arch nor the
value of 2 li Jc for any particular material (see §§ 527-31). In
discussing and applying this principle, the term IE li Jc is usually
neglected. Ordinarily this gives an increased degree of stability;.
but this is not necessarily the case. The omission of the effect of
the horizontal component makes the computed value of T less than
it really is, and causes the line of resistance found on this assump-
tion to approach the in* r ados at the haunches nearer than it does in
fact; and hence the conditions may be such that the actual line of
resistance will be unduly near the extrados at the haunches, and
consequently endanger the arch in a new direction.
2. For simplicity of discussion, and because the error involved in
the discussion immediately to follow is immaterial, we will tempo-
rarily omit the effect of the horizontal components of the external
forces. If the horizontal forces are disregarded, equation (5)
becomes
y
Prom equation (6) we see that, other things remaining the same*
the larger y the smaller T \ and hence, for a minimum value of T,
a should be as near c as is possible without crushing the stone (see
§§ 670-72). Usually it is assumed that ac is equal to one third of
the thickness of the arch at the crown ; and hence the average
pressure per unit of area is to be equal to one half of the assumed
unit working pressure ; or, in other words, twice the thrust T
divided by the thickness of the crown is to be equal to the unit-
working pressure.
ART. 1.] THEORY OF THE ARCH. 457
3. To determine y, it is necessary that the direction of T should
be known. It is usually assumed that T is horizontal. If the arch
is symmetrical and is loaded uniformly over the entire span, this
assumption is reasonable ; but if the arch is subject to heavy moving-
loads, as most are, the thrust at the crown is certainly not hori-
zontal, and can not be determined.
4. If the joint A B is horizontal, then I is to be taken as near
A as is consistent with the crushing strength of the stone, or at,
say, one third of the length of the joints B from A. Notice that
if the springing line is inclined, as in general it will be (see last
two paragraphs of § 682, p. 463), moving J toward A decreases x,
and will at the same time increase y. Hence the position of b cor-
responding to a minimum value of T can be found only by trial.
It is usual, however, to assume that Alt is one third oi»AB, what-
ever the inclination of the joint.
680. Joint of Rupture. The joint of rupture is that joint for
which the tendency to open at the extrados is the greatest. The
joint of rupture of an arch is analogous to the dangerous section of
a beam. Practically, the joint of rupture is the springing line of
the arch, the arch masonry below that joint being virtually only a
part of the abutment.
That no joint may open at the extrados, the thrust at the crown
must be at least equal to the maximum value of T as determined
by equation (5), page 456. If the thrust is less than this, the joint
of rupture will open at the extrados ; and a greater value is incon-
sistent with the hypothesis of minimum crown thrust. Since the
moment of the horizontal components of the external forces is
indeterminable, the position of the true joint of rupture can be
found only by trial for assumed values and positions of the hori-
zontal forces.
681. As an example, assume that it is required to determine the
joint of rupture of the 16-foot arch shown in Fig. 123, which is
the standard form employed on the Chicago, Kansas & Nebraska
K. E. (see page 427 and Plate III). Assume that the arch supports
an embankment of earth extending 10 feet above the crown, and
that the earth weighs 100 pounds per cubic foot and the masonry
160. For simplicity, consider a section of the arch only a foot
thick perpendicular to the plane of the paper. The half -arch ring
and the earth embankment above it are divided into eight sections.
458
AKCHES.
[CHAP. xvin.
-which for a more accurate determination of the joint of rupture
are made smaller near the supposed position of that joint. The
weight of the first section rests upon the first joint, that of the first
two upon the second joint, etc. The values and the positions of
FIG. 122.
the lines of action of the weights of the several sections are given in
the second and third columns of Table 59.*
* The center of gravity of the arch stone is found by the method explained in
§ 494 (page 318); and the center of gravity of the prism of earth resting upon each arch
stone may, without sensible error, be taken as acting through its medial vertical line.
The center of gravity of the combined weight of the arch stone and the earth resting
upon it may be found by either of the two following methods, of which the first is
the shorter and more accurate :
1. The center of gravity of the two masses may be found by the following well-
known principle of analytical mechanics :
W1
(7)
in which x is the horizontal distance from any point, say the crown, to the vertical
through the center of gravity of the combined masses, wl and w$ are the weights of
the two masses, and a^ and xa the horizontal distances from any point, say the crown,
to the verticals through the centers of gravity of the separate masses respectively.
The same method can be employed for finding the center of gravity of any number
of masses, by simply adding the corresponding term or terms in the numerator and
the denominator of equation (7).
2. Since the principles employed in the second method of finding the center of
gravity of each arch stone and its load are frequently employed, in one form, or
ART. 1.]
THEORY OF THE ARCH.
459
TABLE 59.
To FIND THE JOINT OF RUPTURE OF THE ARCH ElNG SHOWN IN FlGL 122.
POSITION OF THE
.fl
DATA FOR VER-
TICAL FORCES.
DATA FOR HORI-
ZONTAL FORCES.
CENTER OF
PRESSURE FOR
THRUST AT THE CROWN.
s 3
EACH JOINT.
2-fl
1
,5!-
CD
ssl§
i CD
^B-l-W
0 CO
o S
.| £ & •-
<H
o3 ccj - fl
.2.2
n~t •** .
etf P-'O
~r-»O
*ll
.gis
0
'53 aj
S 2
»-<
||i|
0
t-H
Vertical dist
of point of
cation fron
top of the (
joint.
Horizontal (
tance from
crown joint
Vertical dist
1 from the to
the crown j
2 w x
y
Total
thrust.
y
Lbs.
Feet.
Lbs.
Feet.
Feet.
Feet.
Lbs.
Lbs.
Lbs.
1
2.938
1.20
66
0.10
2.20
1.18
3,866
94
3,960
2
3.045
3.57
243
0.55
4.57
1.86
7,744
308
8,052
3
1,644
5.33
192
1.17
5.27
2.42
8,518
424
8,942
4
1,716
6.45
259
1.78
6.17
3.11
8.748
662
9,400
5
1,825
7.50
315
2.53
6.98
3.90
8,577
700
9,277
6
1,888
8.47
415
3.40
7.71
4.81
8,407
941
9.348
7
3,939
9.77
1,030
5.02
8.85
6.84
7,506
1,407
8,911
8
4,098
11.05
1,624
7.70
9.50
9.25 I
5,990
1,983
7,973
another, in discussions of the stability of the masonry arch, this method will be ex-
plained a little more fully than is required for the problem in hand.
The first step is to reduce the actual load upon an arch (including the weight of
the arch ring itself) to an equivalent homogeneous load of the same density as the
arch ring. The upper limit of this imaginary loading is called the reduced-load contour.
For example, suppose it is required to find the reduced-load contour for the arch
loaded as in Fig. 123. Assume that the weight of the arch ring is 160 pounds per
FIG. 123.
FIG. 124.
cubic foot ; that of the rubble backing, 140 ; and that of the earth, 100. Then the
ordinate at a to the load contour of an equivalent load of the density of the arch ring
is equal to a & + 6 c ^JL 4. c d -^ = > say, gf. The value of gf is laid off in Fig. 124.
luU luU
Computing the ordinates for other points in the load contour gives the line JE F, Fig.
124, which is the reduced-load contour for the load shown in Fig. 123. The area
between the intrados and the reduced-load contour is proportional to the load on the
arch. In a similar manner, a live load (as, for example, a train) can be reduced to
an equivalent load of masonry, — in which case the reduced-load contour would con-
sist of a line Q H above and parallel to E I for that part of the span covered by the
460 ARCHES. [CHAP. xvm.
The value and position of the horizontal components of the-
external forces are somewhat indeterminate (see §§ 528-31). Ac-
cording to Kankine's theory of earth pressure,* the horizontal
pressure of earth at any point can not be greater than . — ^
times the vertical pressure at the same point, nor less than
"1 —*'• ^in eh
. — r times the vertical pressure, — 0 being the angle of
J. -J— sin (f)
repose, f If <p = 30° , the above expression is equivalent to saying-
that the horizontal pressure can not be greater than three times-
the vertical pressure nor less than one third of it. Evidently
the horizontal component will be greater the harder the earth
spandrel-filling is rammed into place. The condition in which the
earth will be deposited behind the arch can not be foretold,, but it
is probable that at least the minimum value, as above, will always
be realized. Hence we will assume that the horizontal component
is at least one third of the vertical pressure ; that is to say,
h — -J- 10 d I, in which w is the weight of a cubic unit of earth — which
was assumed above at 100 pounds,— tf the depth of the center of
pressed surface below the top of the earth filling, and I the vertical
dimension, of the surface. The values and the positions of the
horizontal forces acting on the respective sections of the arch ring
are given in the second double column of Table 59.
To find the least thrust at the crown consistent with, stability of
rotation, assume that the center of pressure on any joint is at a
distance from the intrados equal to one third of the length of the
joint (see paragraph 4, page 457). The co-ordinates to the several
centers of pressures are given in the third double column of Table
59. The length of the crown joint is 1.25 feet. The thrust at the
crown is supposed to be applied at the upper limit of the middle
third of the crown joint. Notice that the several values of x, k, and
y are simply the differences between two quantities given in Table
train ; while for the remainder of the span, the line IF is the reduced-load contour.
The second step is to draw the arch ring and its reduced-load contour on thick
paper, to a large scale, and then, with a sharp knife, carefully cut out the area repre-
senting the load on each arch stone. The center of gravity of each piece, as ijkl m nr
Fig. 124, can be found by balancing it on a knife-edge ; and then the position of the
center of gravity is to be transferred to the drawing of the arch.
* See §544, page 348.
t Rankine's Civil Engineering, p. 320.
ART. 1.] THEORY OF THE ARCH. 461
59. The last three columns of the table contain the partial values
.and also the total values of the crown thrust as computed by equa-
tion (5), page 456.
An inspection of the results in the last column of Table 59
shows that the thrust is a maximum for joint 4. A repetition of
the computations, using smaller divisions of the arch ring, might
show that the absolute maximum occurs a little to one side or the
other of this joint; but the uncertainty in the data for both the
vertical and the horizontal forces is too great (see § 619 and §§ 527-31
respectively) to justify an attempt at absolute accuracy, and hence
we will assume that joint 4 is the true joint of rupture. The
.angular distance of this joint from the crown is 45% which quantity
is termed the angle of rupture.
Any increase in the assumed intensity of the horizontal com-
ponents increases the computed value of the angle of rupture.
For example, if the quantities in the next to the last column of
Table 59 be doubled, the thrust for joint 7 will be the maximum.
Probably this condition could be realized by tightly tamping the
•earth spandrel-filling.
Notice that the preceding discussion of the position of the
joint of rupture is for a uniform stationary load. The angle of
rupture for a concentrated moving load will differ from the results
found above; but the mathematical investigation of the latter case
is too complicated and too uncertain to justify attempting it.
682. In discussions of the position of the joint of rupture, the
horizontal components are usually neglected.* This phase of the
subject will be considered only briefly. The following is the
method always employed f in investigating the position of the joint
of rupture, and is based on the assumption that the crown thrust is
correctly given by equation (6), page 456.
Let IF = the total weight resting on any joint; £ = the hori-
zontal distance of the center of gravity of this weight from the
crown joint ; and y = the arm of the crown thrust. Then equation
(6) becomes __
W?
T=— (8)
y
* So far as observed, Rankine's investigation is the only exception; and it is, in
fact, only an apparent exception (see paragraph 2, page 490).
fFor example, see Sonnet's Dictionnaire des Mathe'matique Applique'es, pp.
1084-85.
462 ARCHES. [CHAP. XYIIL,
To determine the condition for a maximum, it is assumed that W9
x, and y are independent variables. Differentiating equation (8),
dT_ld(Wx) Wxf
dy ~~ y dy f
but d( Wx) ~ Wdx +c2W.$dx= Wdx, and then
dT _ W_ dx _ Wx , ,
dy" y dy f ........
Hence the condition for a maximum crown thrust is
^ = * ........... (10)
dy y ^ f
The usual interpretation of equation (10) is: "The joint of rup-
ture is that joint at which the tangent to the intrados passes
through the intersection of T and the resultant of all the vertical
forces above the joint in question."
The position of the joint of rupture can be found by the above
principle only by trial. This method possesses no advantage over
the one explained in the preceding section, and is less convenient to
apply. The preceding investigation is approximate for the following
reasons: 1. The effect of the horizontal forces is omitted. 2. W,
x, and y are dependent variables, and not independent as assumed.
3. In the interpretation of equation (10), instead of " the tangent
to the intrados," should be employed the tangent to the line of
resistance.
In applying this method, a table, computed by M. Petit, which
gives the angle of rapture in terms of the ratio of the radii of the
iutraclos and the extrados, is generally employed. The table in-
volves the assumption that a, Fig. 121 (p. 455), is in the extrados
and 1) in the intrados; and also that the intrados and extrados are
parallel. According to this table, "a semi-circular arch of which
the thickness is uniform throughout and equal to the span divided
by seventeen and a half is the thinnest or lightest arch that can
stand. A thinner arch would be impossible." If the line of re-
sistance is restricted to the middle third, then, according to this
theory, the thinnest semi-circular arch which c,an stand is one
whose span is five and a half times the uniform thickness. Many
ART. 1.] THEORY OE THE ARCH. 468
arches in which the thickness Is much less than one seventeenth
of the span stand and carry heavy loads without showing any evi-
dence of weakness. Tor example, in arch No. 26 of Table 63 (pp.
502-3), which is frequently cited as being a model, the average thick-
ness is 3.25 ft., or about one twenty -fifth of the span; and since no
joints open, the line of resistance must lie in the middle third,
even though the thickness is only one fifth of that required by the
table. Owing to the approximations involved, and also to the limi-
tations to arches having intrados and extrados parallel, the ordi-
nary tables for the position of the joint of rupture have little, if
any, practical value. The only satisfactory way to find the angle
of rupture is> by trial by equation (5), as explained in § 681.
According to M. Petit's table, if the thickness is one fortieth of
the diameter, the angle of rupture is 46° 12'; if the thickness is one
twentieth, the angle is 53° 15'; and if one tenth, 59° 41'.
In conclusion, notice that the investigations of both this and the
preceding section show that an arch of more than about 90° to 120°
central angle is impossible.
683. Winkler's Hypothesis. Prof. Winkler, of Berlin,— a well-
known authority — published in 1879 in the " Zeitschrift des Archi-
telcten und Ingenieur Vereins zu Hannover," page 199, the follow-
ing theorem concerning the position of the line of resistance: " For
an arch ring of constant cross section that line of resistance is
approximately the true one which lies nearest to the axis of the
arch ring, as determined by the method of least squares." *
The only proof of this theorem is that by it certain conclusions
can be drawn from the voussoir arch which harmonize with the
accepted theory of solid elastic arches. The demonstration de-
pends upon certain assumptions and approximations, as follows:
1. It is assumed that the external forces acting on the arch are
vertical; whereas in many cases, and perhaps in most, they are
inclined. 2. The loads are assumed to be uniform over the entire
span ; whereas in many cases the arch is subject to moving con-
centrated loads, and sometimes the permanent load on one side of
the arch is heavier than that on the other. 3. It is assumed that
the load included between the lines PGD and NHC, Fig. 122
(page 458), is equal in all respects to that included between PGr2
* This theorem was first brought to the attention of American readers in 1880, by
Professor Swain in an article in Van NostraniTs Engin'g Mag., vol. xxiii, pp. 2G5-7&
464 A.BCHES. [CHAP. xvm.
.and NH\. The error thus involved is inappreciable at the crown,
but at the springing of semicircular arches is considerable. 4. The
•conclusions drawn from the voussoir (masonry) arch only approxi-
mately agree with the theory of elastic (solid iron or wood) arches.
5. Masonry arches do not ordinarily have a constant cross section
as required by the above theorem; but it usually, and properly,
increases toward the springing. 6. The phrase " as determined by
the method of least squares " means that the true line of resist-
ance is that for which the sum of the squares of the vertical
deviations is a minimum. Since the joints must be nearly perpen-
dicular to the line of resistance, the deviations should be measured
normal to that line. For a uniform load over the entire arch, the
lines of resistance are comparatively smooth curves; and hence, if
-the sum of the squares of the vertical deviations is a minimum,
•that of the normal also would probably be a minimum. But for
•eccentric or concentrated loads it is by no means certain that such a
relation would exist. 7. The degree of approximation in this theorem
is less the flatter the arch.
684. To apply Winkler's theorem, it is necessary to (1) con-
struct a line of resistance, (2) measure its deviations from the axis,
and (3) compute the sum of the squares of the deviations; and it is
then necessary to do the same for all possible lines of resistances,
the one for which the sum of the squares of the deviations is least
being the " true" one.
Instead of applying Winkler's theorem as above, many writers
-employ the following principle, which it is asserted follows directly
from that theorem: "If any line of resistance can be constructed
within the middle third of the arch ring, the true line of resistance
lies within the same limits, and hence the arch is stable." This
assertion is disputed by Winkler himself, who says it is not, in gen-
eral, correct.* It does not necessarily follow that because one line
of resistance lies within the middle third of the arch ring, the
"true" line of resistance also does; for the "true" line may coin-
cide very closely with the axis in one part of the arch ring and
depart considerably from it in another part, and still the sum of the
squares of the deviations be a minimum. This method of applying
"Wmkler's theorem is practically nothing more or less than an appli-
* Prof. Swain's review of Winkler's Theorem— Van Nostrand's Engineering Maga-
zine, vol. xxiii. p. 275.
ART. 1.] THEOKY OF THE ARCH. 465
cation of tlie conclusions derived from the hypothesis of least
resistance (§ 677).
685. ISTavier's Principle. It is well known, from the principles
,of fluid pressure, that the tangential thrust at any point of a circle
pressed by normal forces is equal to the pressure per unit of area
multiplied by the radius. " The condition of an arch of any form
,at any point where the pressure is normal is similar to that of a cir-
cular rib of the same curvature under a normal pressure of the same
intensity; and lieiice the following principle: the thrust at any
normally pressed point of a linear arch is the product of the radius
of curvature by the intensity of the pressure at that point. Or,
denoting the radius of curvature by p, the normal pressure per
unit of length of intrudes by p, and the thrust by T, we have
(11)
The above relation., due originally to Navier, has in itself nothing
to do with the position of the line of resistance; but is employed by
writers who assume that an arch is stable if a line of resistance can
l)o drawn anywhere within the middle third of the arch ring, to
detcM'mino the crown thrust. Notice, however., that under these
•cjoiulitioiis the radius of curvature is known only within limits. An
•oxupiplo of its application will be referred to later (§ 704; and 8,
§ 705; — pp. 482 and 486 respectively).
686. THEOEIES or THE AECH. Various theories haye been
proposed from time to time, which differ greatly in the fundamental
principles involved. Unfortunately, the underlying assumptions
lire not usually stated ; and, as a rule, the theory is presented in such
.a way as to lead the reader to believe that each particular method
" is free from any indeterminateness, and gives results easily and
accurately/7 Every theory of tho masonry arch is approximate,
owing to the uncertainty concerning the amount and distribution
of the external forces (§ 666), to the indeterminateness of the posi-
tion of the true line of resistance (§§ 676-85), to the neglect of the
influence of the adhesion of the rnortar and of the elasticity of the
material, and to the lack of knowledge concerning the strength of
masonry; and, further, the strains in a masonry arch are indeter-
minate owinff to the effect of variations in the material of which the
466 AECHES. [CHAP. XVIIL,
arch is composed, to tlie effect of imperfect workmanship in dress-
ing and bedding the stones, to the action of the center— its rigidity,
the method and rapidity of striking it, — to the spreading of the
abutments, and to the settling of the foundations. These elements.
are indeterminate, and can never be stated accurately or adequately
in a mathematical formula ; and hence any theory can be at best
only an approximation. The influence of a variation in any one of
these factors can be approximated only by a clear comprehension of
the relation which they severally bear to each other ; and hence a
thorough knowledge of theoretical methods is necessary for the
intelligent design and construction of arches.
A few of the most important theories will now be stated, and
the fundamental principles involved in each explained.
687. To save repetition, it may be mentioned here, once for all,
that every theory of the arch is but a method of verification. The
first step is to assume the dimensions of the arch outright, or to
make them agree with some existing arch or conform to some em-
pirical formula. The second step is to test the assumed arch by the
theory, and then if the line of resistance, as determined by the
theory, does not lie within the prescribed limits — usually the middle
third, — the depths of the voussoirs must be altered, and fche design
must be tested again.
688. EATIONAL THEORY. The following method of determining
the line of resistance is based upon the hypothesis of least crown
thrust (§ 678), and recognizes the existence of the horizontal com-
ponents of the external forces. Unfortunately, the results found
by this method, as well as those by all others, are rendered some-
what uncertain by the indeterminateness of the external forces
(§ 666).
689. Symmetrical Load. General Solution. As an example
of the application of this theory, let us investigate the stability of
the semi-arch shown in Fig. 125 (page 467). The first step is to
determine the line of resistance. The maximum crown thrust was
computed in Table 59 (page 459), as already explained (§ 681).
To construct the force diagram, a line BO is drawn to scale to
represent the maximum thrust as found in the fourth line of the
last column of Table 59. From 0, w, is laid off vertically upwards ;
and from its extremity, 7^ is laid off horizontally to the left. Then
the line from 0 to the left-hand extremity of Ji: (not shown in this-
ART. 1.]
RATIONAL THEORY OF THE ARCH.
46?
particular case) represents the direction and amount of the external
force Fl acting upon the first division of the arch stone ; and the
line jRj from B to the upper extremity of F^ represents the resultant
pressure of the first arch stone upon the one next below it. Simi-
larly, lay off w^ vertically upwards from the left-hand extremity of.
7^, and lay off li^ horizontally to the left; then a line F^ from the
upper end of w, to the left-hand end of hz represents the resultant
of the external forces acting on the second divisions of the arch,
and a line 72a from the upper extremity of F9 represents the resultant
pressure of the second arch stone on the third. The force diagram
is completed by drawing lines to represent the other values of
wl 7^ Fl and the corresponding reactions.
FIG. 125.
Iii the diagram of the arch, the points in which the horizontal
and vertical forces acting upon the several arch stones intersect, are
marked gl , #2 , etc., respectively ; and the oblique line through each
of these points shows the direction of the resultant external force
acting on each arch stone.
To construct the line of resistance, draw through U— the upper
468 ARCHES. [CHAP. xvnr.
limit of the middle third of the crown joint — a horizontal line to an
intersection with the oblique force through gl • and from this point
draw a line parallel to j£: , and prolong it to an intersection with the
oblique force through //2 . In a similar manner continue to the
springing line. Then the intersection of the line parallel to 7?1
with the first joint gives the center of pressure on that joint ; and
the intersection of Rz with the second joint gives the center of
pressure for that joint. — and so on for the other joints. Each
center of pressure is marked by a circular dot. A line connecting
these centers of pressure would be the line of resistance; but the
line is not shown in Pig. 125.
690. The next step is to determine the degree of stability.
1. Since the line of resistance lies within the middle third of the
arch ring, and touches the inner limit of that third at two points
.and its outer limit at an intermediate and higher point,, the factor
against rotation is 3 (see § 669).
2. The unit working pressure is found by applying equation (2),
2 W
page 448. At the crown, d = -j- 1, and hence P = — - — ; or, since
I/
IT= 9,400 pounds and I = 1.25 feet, P = 14,040 pounds per square
foot = 98 pounds per square inch. At the springing,, W = 21,700
pounds, I = 4.5 feet, and d = 0.10 feet ; and therefore
+ 1**^°^ = 4,820 + C43 = 5,463.
That r, /* = 5,463 pounds per square foot, or 38 pounds per square
inch. Except for a particular kind of stone and a definite quality
of masonry, it is impossible even to discuss the probable factor of
safety ; but it is certain that in this case the nominal factor is
excessive (see § 223), while the real factor is still more so (see
§§ G71-72).
If the maximum pressure at the most compressed joint had been
more than the safe bearing power of the masonry, it would have
been necessary to increase the depth of the arch, stones and repeat
the entire process. Notice that the total pressure on the joints
increases from the crown toward springing, and that hence the
depth of the arch stones also should increase in the same direc-
tion.
30 To determine the degree of stability against sliding, notice
AKT. 1.] RATIONAL THEORY. 469
that the angle between the resultant pressure on any joint and
the joint is least at the springing joint ; and hence the stability
of this joint against sliding is less than that for any other. The
nominal factor of safety is equal to the co-efficient of friction
divided by tan (90° — 72°) = tan 18° = 0.33. An examination of
Table 36 (page 315) shows that when the mortar is still wet the
co-efficient is at least 0.50 ; and hence the nominal factor for the
joint in question is at least 1|, and probably more, while the real
factor is still greater. The nominal factor for joint 7 is at least 34,
and that for joint 3 is about 5. There is little or no probability that
an arch will be found to be stable for rotation and crushing, and
unstable for sliding. If such a condition should occur, the direc-
tion of the assumed joint could be changed to give stability.* The
actual joints should be as nearly perpendicular to the line of resist-
ance as is consistent with simplicity of workmanship and with
stability. For circular arches, it is ordinarily sufficient to make all
the joints radial. In Fig. 125, the joints are radial to the intrados ;
but if they had been made radial to the extraclos or to an intermedi-
ate curve, the stability against sliding, particularly at the springing
joint, would have been a little greater.
691. Special Solution. The following entirely graphical solution
is useful when it is desired to find a line of resistance which will
pass through two predetermined points.
For example, assume that it is desired to pass a line of resistance
through 27 and a, Fig. 126 (page 470), the former being the upper
extremity of the middle third of the crown joint and the latter the
inner extremity of the middle third of joint 4.
The value and positions of the external forces, which are the
same as those employed in Fig. 125, are given in Table 59 (page
459). Construct a load line, as shown in the force diagram, by
laying off w1 and lil , and wz and Z>.Q , etc., in succession, and drawing
jpj , jF^ , etc. Since the load is symmetrical, we may assume that the
thrust at the crown is horizontal; and hence we may choose a pole
at any point, say P', horizontally opposite 0. Draw lines from, Pr
to the extremities of Fl9 ^2 , etc. Construct a trial equilibrium
polygon by drawing through U a line parallel to the line Pr 0, of
the force diagram, and prolong it to 1) where it intersects f\ . From
* Strictly any change in the direction of the joints will necessitate a recomputation
of the entire problem ; but, except in extreme cases, such revision is unnecessary.
470
ARCHES.
[CHAP. XVIIL
5 draw a line 5 c parallel to R\ of the force diagram ; from c, the
point where I c intersects the line of F» draw a line c d parallel to
R'n ; from d, the point where c d intersects Fz , draw a line d e
parallel to R\ ; and from e, the point where d e intersects JF , draw
a line ef parallel to R\ . Prolong the line fe to g, the point in
which it intersects the prolongation of Ub ; and then, by the prin-
ciples of graphical statics, g is a point on the resultant of the forces
The section of the arch from the crown joint to joint 4 is at
rest under the action of the crown thrust T, the resultant of the
external forces, and the reaction of joint 4. Since the first two
intersect at g, and since it has been assumed that the center of
pressure for joint 4 is at a — the inner extremity of the middle third,
— a line ag must represent the direction of the resultant reaction of
joint 4; and hence the line R^ in the force diagram drawn from
the upper extremity of F^ , parallel to a g, to an intersection with
P'O, represents, to the scale of the load line, the amount of the
reaction of joint 4. Then PO, to the same scale, represents the
crown thrust corresponding to the line of resistance passing through
U and a i and a line — not shown in Fig. 126 — from the upper
ART. 1.] RATIONAL THEORY. 471
extremity of F4 to the lower extremity of Fl9 would represent, in
both direction and amount, the resultant of Fl , F^, F^ , and F^.
Having found the thrust at the crown, complete the force dia-
gram by drawing the lines Hl3 R^, Ra, etc. ; and then construct a
new equilibrium polygon exactly as was described above for the
trial equilibrium polygon. The construction may be continued to
the springing line. The equilibrium polygon shown in Fig. 126 by
a solid line was obtained in this way.
The amount of the pressure on any joint is given by the length
of the corresponding ray in the force diagram. The points in which
the sides of the equilibrium polygon cut the joints are the centers
of pressure on the respective joints. The stability of the arch may
be discussed as in § 690.
692. One of the most useful applications of the method described
in the preceding section is in determining the line of resistance for
a segmental arch having a central angle so small as to make it
obvious that 'the joint of rupture (§§ 680-81) is at the springing.
For example, assume that it is required to draw the line of
resistance for the circular arch shown in Fig. 127 (p. 472). The span
is 50 feet, the rise 10 feet, the depth of voussoirs 2.5 feet, and the
height of the earth above the summit of the arch ring is- 10 feet.
The angular distance of the springing from the crown is 43° 45' ;
and since the angle of rupture is nearly always more than 45°, it is
safe to assume that the joint of rupture is at the springing.
The method of determining the line of resistance is the same
as that explained in § 691, and is sufficiently apparent from an
inspection of Fig. 127.
693. TJnsymmetrical Load. The design for an arch ring
should not be considered perfect until it is found that the criteria
of safety (§§ 668-75) are satisfied for the dead load and also for
every possible position of the live load. A direct determination of
the line of resistance for an arch under an unsymmetrical load is
impossible. To find the line of resistance for an arch under a
symmetrical load, it was necessary to make some assumption con-
cerning (1) the amount of the thrust, (2) its point of application,
and (3) its direction ; but when the load is unsymmetrical, wre
neither know any of these items nor can make any reasonable
hypothesis by which they can be determined. For an unsymmetri-
cal load we know nothing concerning the position of the joint of
472 AECHES. [CHAP, xvm,
rupture, and know that the thrust at the crown is neither horizontal
nor applied at one third of the depth of that joint from the
FIG. 127.
crown ; and hence the preceding methods can not be employed.
When the load is not symmetrical., the following method may be*
employed to find a line of resistance ; but it gives no indication as-
to which of the many possible lines of resistance is the true one.
Let it be required to test the stability of a symmetrical arch hav-
ing a uniform live load covering half the span. Divide the arch and
its load into sections, as shown in Fig. 128. The live load is a ver-
tical force, and the earth pressure would give a horizontal compo-
nent. The approximate reduced-load contour for the vortical forces.
is shown in Fig. 128, and the horizontal and vertical components-
are laid off in the force diagram. An equilibrium polygon can. be-
made to pass through any three points ; and therefore we may as-
sume three points for a trial equilibrium polygon, — as, for example,
(1) the lower limit of the middle third of the joint at the abutment
Ay (2) the middle., C, of the crown joint, and (3) the upper limit
of the middle third of the joint at B.
ABT. 1.]
EATIOKAL THEORY.
473
Construct a force diagram by laying off the external forces suc-
cessively from 0 in the usual way (§ 689), selecting a pole, P'} at any
point, and drawing lines connecting P' with the points of division
of the load line. Thou, commencing at A, construct an equilib-
rium polygon through A, 0', and 13'' 9 by the method explained in
§§ 691-92.
It is then necessary to move the pole of the force diagram in
such a way that the equilibrium polygon will pass through 13 instead
of Bf. To do this, draw a line through the pole P'9 parallel to A Br
— the closing line of the trial equilibrium polygon, — and then
through H- — the intersection of the preceding line with the load
line— draw IIP parallel to AB. The new pole, P, is at a point
FIG. 128.
on this lino such that IIP is TO the horizontal distance from Pf to
tho load lino AS (I'D' is TO (!/.). From P draw lines to the points
of division of the load line, and then construct an equilibrium,
polygon through Ay 0, and IL If tho resulting line of resistance
does not lie within the middle third, try some other position of the*
three points A9 O, and I> instead of as above. If a line of resistance
scan not be drawn (see § G94) within tho prescribed limits, then tho
section of tho arch ring must bo changed HO an to include tho lino
of resistance within tho limits.
694. Criterion. If tho lino of resistance, when constructed by
any of tho preceding methods, does not lie within the middle third
of the arch ring, the following process may bo employed to deter-
mine whether it is possible, or not, to draw a line of resistance in
the middle third.
Assume, for example, that the line of resistance of Fig. 129 lies
474 AECHES. [CHAP. xvin.
outside of the middle third at a and b. Next draw a line of resist-
ance through c and d, the points where
normals from a and I intersect the outer
iind inner boundary of the middle third
respectively. To pass a line of resistance
through c and d, it is necessary to deter-
mine the value and point of application of
the corresponding crown thrust. The
condition which makes the line of resist-
ance pass through c is: the thrust MULTI-
FIG. 129. PLIED BY the vertical distance of its point
of application above c is EQUAL TO the load on the joint at c MULTI-
PLIED BY its horizontal distance from c. The condition that makes
the line of resistance pass through d is: the thrust MULTIPLIED
BY the sum of the distance its point of application is above c and
of the vertical distance between c and d is EQUAL TO the load on
the joint at d MULTIPLIED BY its horizontal distance from d. These
conditions give two equations which contain two unknown quanti-
ties— the thrust and the distance its point of application is above c.
After solving these equations, the line of resistance can be drawn
by any of the methods already explained.
If this new line of resistance lies entirely within the prescribed
limits, it is plain that it is possible to draw a line of resistance
therein ; but if the second line does not lie within the prescribed
limits, it is not at all probable that a line of resistance can be drawn
therein. The possibility of finding, by a third or subsequent trial,
a line of resistance within the limits can not, in general, be answered
definitely, since such a possibility depends upon the form of the
section of the arch ring.
If the line of resistance drawn through £7" and Fgoes outside of
the arch ring beyond the extrados only, as at a, the second line of
resistance should be drawn through c and V\ and if, on the other
hand, it goes outside below the intrados only, as at #, the second
line should be drawn through U and d.
695. SCHEITLER'S THEORY.* This theory is the one most fre-
quently employed. It is based upon the hypothesis of least crown
thrust (§§ 678-82), and assumes that the external forces are vertical.
* See the second foot-note page 455.
ART. 1.]
SCHEFFLER'S THEORY.
475
This theory is frequently referred to as assuming that the arch
stones are incompressible; but, fairly considered, such is not the
case. Dr. Sch.ef9.er develops the theory of the position of the line
of pressures for incompressible voussoirs; but subsequently states
that the compressibility of the arch stones causes the line of resist-
ance to retreat within the arch ring at points where it would other-
wise reach the edge. He also says that, if a line of resistance can
be drawn within the arch ring, that nowhere approaches nearer the
£dges of the joint than one fourth of its depth, the stability of the
arch is assured.
This theory will be illustrated by two examples.
696. First Example. Assume that it is required to determine,
in accordance with this theory, the line of resistance for the circular
segmental arch shown in Eig. 130. The span is 50 feet, and the
FIG. 130.
rise is 10 feet. The voussoirs are 2 feet 6 inches deep, and the
spandrel wall rises 2 feet 10 inches above the summit of the arch
ring. In this example we will follow the explanation used by
Scheffler.*
The first step is to find the amount and the point of application
of the resultant of the external forces acting on the portion of the
arch above the successive joints. Divide the semi-arch and the
spandrel wall into any convenient number of parts by vertical lines
* Cain's "Practical Theory of the Arch," pp. 38-44.
476
AECHES.
[CHAP. xvin.
through Fy G, H, 1, J, and If, as shown. The positions of the act-
ual joints are assumed to be not yet fixed; but, for temporary pur-
poses, assume radial joints to be drawn through F, G, H, I, Jr
and K. Then the load on any part of the arch is assumed to be
proportional to the area above it, — for example, the load on CHGR
is assumed to be proportional to the area CNPR*
Haying determined the area representing the loads, it is then
necessary to determine (1) the numerical values of the several loads
and the distances of their centers of gravity from a vertical through
the crown, and (2) the amount and the position of the center of
gravity of the loads above any joint. The steps necessary for this
are given in Table 60.
The quantities in column 2 of Table 60 are the lengths of the
medial lines of the several trapezoids. Column 6 contains the
* Notice that really the load on the joint SH, for example, is SHNP&R, and not
CNPR as above. The error is least near the crown of flat segmental arches, and
greatest near the springing of semi-circular ones. The error could be eliminated (1)
by finding the weights of GPNH and J&GHS separately and combining them into
a single resultant for the weight on the joint SH, as was done in §681; or (2) by
drawing the arch to a large scale on thick paper and cutting out the several six-sided
figures which represent the loads, when the amounts of the several loads can be
determined readily from the weights of corresponding sections of the paper, and the
center of gravity of each section can be found by balancing it on a knife edge.
Schefiler gives the following empirical and approximate method of altering the
position of the joints to correct this 'error. Let DOG, Fig. 131, be the side of the-
trapezoid, and OJEf the uncorrected joint. From 6, the middle point of GH, draw
FIG. 131.
FIG. 132.
6Z> ; and draw Qc parallel to t>£, and ch parallel to CH. Then will ch be the corrected
joint. Conversely, having given the joint CH, Fig. 132, to find the side of the trape-
zoid which limits the portion of the load upon it, through C draw .DG vertical, and
draw Ckj parallel to JDb (b being the middle point of QH) ; then, from fft draw dy ver-
tical, and we have the desired side of the trapezoid.
ART. 1.]
SCHEFIXER'S THEOBY.
477
TABLE 60.
APPLICATION OF SCHEFFLER'S THEORY TO THE ARCH RING SHOWN IN
PIG. 130, PAGE 475.
1
2
3
4
5
6
7
8
9
s
THE AMOUNT, AND POSITION OF THE
To FIND THE AMOUNT, AND THE CENTER
IK. 5
CENTER OF GRAVITY, OF THE
OF GRAVITY, OF THE LOADS ABOVE
S
2; o
SEVERAL LOADS.
THE SEVERAL JOINTS.
OO .
y>&
i
| _tS
a) q flJ
W ~5
-1 G5 *
%'>
w
CO
fl o ^ eo
fci 0
Dimensions of the sections.
|U
A
^§
|||
|llll
|I
Pf«
ll
e tf
s«a
73J= C
to?£
"^ to
os£
^5.2
c <u!s,
^Ifs
ibifii
|il
Height.
Width.
Area.
go'o.S
o>
II
' f=>
OJ 0 *>
£^.fe
-5 a M
a- t> ^*
il-S
gdca
§ a o5 g
'§2"S^§
K«M^^C«
1
5.4
5
27 0
2.5
67.50
27.0
67.50
2.5
2
6.1
5
30.5
75
228.75
57.5
296 25
5.1
3
7. 6
5
38.0
12.5
! 475 00
95.5
771.25
8.1
4
9.S
5
49.0
17.5
1 857.50
144.5
1,628.75
11.3
5
13.2
5
66 0
22.5
1,485.00
210.5
3,113.75
14.7
6
14.5
1.75
25.4
25.9
657.86
235.9
3,771.61
16.0
products of the numbers in columns 4 and 5. Column 7 contains
the continued sums of the quantities in column 4. Column 8 con-
tains the continued sums of the quantities in column 6. Column 0
is found by the principle of analytical mechanics : the distance
of the center of parallel 'forces from any point is equal to the sum
of the moments of the several forces about that point divided ly
the sum of the several forces ; and hence the numbers in column
9 are found by dividing the quantities in column 8 by the corre-
sponding quantity in column 7,
697. The second step is to find the minimum thrust which
applied at U ( UF = -| FE) is sufficient to prevent the semi-arch
from rotating. The origin of moments is considered as being in
the successive joints at one third of the depth of each from the
intrados. •
If T= the thrust and y = its arms, and W= the load above
any joint and x = its arm,, then for equilibrium about any joint
Wx
y
(12)
It is required to find the maximum value of T.
478
ARCHES.
[CHAP. xvni.
The W — in terras of the weight of a cubic foot of the masonry —
for each joint is the corresponding number in colnmn 7 of Table
60, and is for convenience repeated in column 2 of the table be-
low. The x for each joint is the horizontal distance between the
resultant of the load above each joint and the center of that joint;
and is equal to the horizontal distance from U to the points 1, 2,
etc., minus the respective quantities in column 9 of Table 60.
The first of these quantities is given in column 3 of Table 61, the
second in column 4, and their difference in column 5. The y for
each joint is given in column 6 of Table 61. The value of the
thrust, obtained by substituting the above data successively in equa-
tion (12) and solving, is given ia column 7 of Table 61.
TABLE 61.
APPLICATION OF SCHEFFLER'S THEORY TO THE ARCH RING SHOWN IN
FIG. 130, PAGE 475.
1
2 1
a
4
5
6
7
No. OF THE JOINT,
COUNTING FROM
THE ONK NEXT TO
THE CROWN.
Area of the load
above each joint
(=TF).
Horizontal dis-
tance from U to
1,2, 3, etc., re-
spectively.
Horizontal dis-
tance from U to
the center of
gravity of the
loads above the
successive joints.
Arm of the load
about the center
of resistance of
the successive
joints ( = x).
Arm of the thrust
about the center
of resistance of
each joint ( — y)
Horizontal thrust
required to pre-
vent rotation
about the suc-
cessive joints
( = r,
1
27.0
4.8
2.5
2.3
1.15
54.0
2
57.5
9.6
5.1
4.5
2.09
123.6
3 •
95.5
14,4
8.1
6.3
3.72
110.9
4
144.5
19.2
11.8
7.9
6.16
185.3
5
210.5
24.0
14.7
9.3
9.60
204.0
6
235.9
25.6
16.0
9.6
11.00
205.9
The horizontal thrust for joint 6 is the greatest, and hence that
joint is the joint of rupture. This result might have been antici-
pated, since the angle of rupture ordinarily varies between 45°
and 60° (see last paragraph of § 682, page 463), while the angular
distance of joint 6 from the crown is only 43° 35'.
69,8. The .second istep i£ to construct the line .of resistance.
To find the center of pressure on joint 1, Fig. 130, page 475, draw
a horizontal line through U, and lay off, to any convenient scale, a
distance Ua to the left equal to the first quantity in column 4 of
Table 61. a is a point through which the weight of DEQP*
* Assumed to be equal to REQPG (see foot-note, page 476).
ART. 1.] SCHEFFLEB'S THEORY. 479
acts. Lay off, vertically, a distance ab equal to the first quantity
in column 2 of Table 61; this line represents the weight of the first
voussoir and the load resting upon it. From 1) lay off, horizontally
to the right, a distance be equal to the last quantity in column 7 of
Table 61. This line represents the horizontal pressure at the crown.
Then, by the principle of the triangle of forces, a line ca repre-
sents the resultant pressure on the joint RG\ and this line pro-
longed intersects the joint RGr at d, which is, therefore, the center
of pressure on that joint.
To find the center of pressure on the second joint, lay off from
U, horizontally to the left, a distance equal to the second quantity
in column 4 of Table 61; erect a vertical equal to the second quan-
tity in column 2; and from the point thus found lay off, horizon-
tally to the right, a quantity equal to the last quantity in column 7.
Then draw the third side of the triangle of forces, and prolong it
until it intersects the joint at e.
By a similar construction, the centers of pressure for the several
joints are determined to be U, d, e,f, g, h, and 6, as shown in Fig.
130. A line joining these points is the line of resistance (not shown
in the figure).
699. The preceding method of drawing the line of resistance
has two advantages : (1) The center of pressure on any joint may
be found at once; and (2) any small error in draughting is confined
to the joint where it first occurs. Notice, however, that the method
is applicable only when the horizontal component of the pressure on
the several joints is constant; that is, this method is applicable only
when the external forces are assumed to be vertical.
Having determined the line of resistance by the above method,
the stability of the arch can be discussed as described in § 690.
700. Second Example. Let us construct, according to this
theory, the line of resistance for the semi-arch shown in Fig. 133,
page 480, which is the same one discussed in § 681, where it was
shown that joint 4 is the joint of rupture, and that, if the horizon-
tal forces be disregarded, the maximum crown thrust is 8,748
pounds (see Table 59, page 459).
The crown thrust is laid off, to any convenient scale, from S
to 0 ; and the loads as given in Table 59 are laid off, to the same
scale, successively from 0 downwards. The remainder of the
480
AECHES.
[CHAP, xvm.
construction — shown by dash lines — is exactly similar to that
•described in § 689 in connection with Fig. 125,, page 467.
FIG. 333.
701. Erroneous Application. Frequently the principle of the
joint of rupture is entirely and improperly neglected in applying
this theory; that is to say, the crown thrust employed in determin-
ART. 1.] SCHEFFLEK/S THEORY. 481
ing the line of resistance is that which would produce equilibrium
of rotation about the springing line, instead of that which would
produce equilibrium about the joint of rupture. For example,
instead of employing the maximum value in the ~ — — column of
*./
Table 59, page 459, the last quantity in that column is used.
The line of resistance obtained by this method is shown in Fig.
133 (page 480) by the dotted line., the crown thrust (5, 990, as com-
puted in Table 59, page 459) being laid oil from 0 to 0, to the scale
-employed in. laying oft' the load line.
702. The error of this method is shown, incidentally, in §§ 678-
.82 and §§ 688-701, and needs no further explanation.
The amount of the error is illustrated in Fig. 133. According
to this analysis, the line of resistance is tangent to the iutrados,
which seems to show that the arch can not stand for a moment.
However, many such arches do stand, and carry a heavy railroad
traffic without any signs of weakness ; and further, any reasonable
method of analysis shows that the arch is not only safe, but even
extravagantly so (§ 690).
This method of analysis certainly accounts for some, and per-
haps many, of the excessively heavy arches built in the past. For
example, compare 8 and 9, 17 and 18, 33 and 34, 52 and 54, etc.,
of Table 63 (page 502).
703. Beliability of Scheffler^s Theory. For the sake of com-
parisons, the line of resistance according to the Rational Theory
(§§ 688-94), as determined in Fig. 125 (page 467), is shown in Fig.
133 by the solid lines. (Notice that Fig. 133 gives the lines of re-
sistance, and not the equilibrium polygons as in Fig. 125.) In this
particular case, the difference between the two lines above the joint
of rupture is not material ; but the difference below that joint has
a very important effect upon the thickness of the arch at the spring-
ing, and also upon the thickness of the abutment (§ 712).
If the maximum ratio of the horizontal to the vertical compo-
nent of the external forces (see first paragraph on page 400) had
been employed in determining the crown thrust arid the line of
resistance, there would have been a material difference in the posi-
tion of both the joint of rupture and the line of resistance above
that joint. Although the horizontal components of the external
forces can not be accurately determined, any theory that disregards
482 ARCHES. [CHAP, xvm,
the existence of these forces can not be considered more than a.
loose approximation.
704. EANKINE'S THEORY. Although this theory has long been
before the public and is in some respects much superior to the one
in common "use., it is comparatively but little employed in practice.
This is probably due, i,n part at least, to the fact that Eankine's-
discussion of the theory of the masonry arch is not very simple nor
very clearly stated, besides being distributed throughout various-
parts of his works. *
Eankine determines the thrust at the crown by Navier's princi-
ple (§ 685) ; but he makes no special assumption as to the point of
application of this thrust, further than to assume that if a line of
resistance can be drawn anywhere within the middle third of the
arch ring, the arch is stable.
In that part of his books which precedes the discussion of arches,,
Eankine investigates the various curves which a cord will assume-
under different distributions of the load ; and subsequently adopts
these curves as the form which the line of resistance of an arch
similarly loaded should have. The discussion of these curves con-
stitutes the most valuable part of his investigations concerning the
stability of the masonry arch.
705. Curvature of the Linear Arch. The curves assumed by
a cord under the various conditions of loading, can be applied to-
linear arches (the line of resistance of actual arches) by imagining
that the curve of the cord is reversed, and that the cord itself is
replaced vby a thin metal strip, which, like the cord, shall be prac-
tically without transverse strength, but which, unlike the cord,
shall be able at every point to resist a compressive force in the di-
rection of its length. The amount and distribution of the external
forces are the same in both cases ; but with the cord they act out-
ward, while with the linear arch they act inward. The formulas
and diagrams are essentially the same in both cases. The curves
assumed by a suspended cord under various distributions of the
load will now be briefly considered. In each case it will be assumed
that the ends of the suspended cord and also of the corresponding
linear arch are in the same horizontal line.
I. If the cord is acted upon by vertical loads distributed uni-
* "Civil Engineering, " and "Applied Mechanics.'7
ART. 1.] RANKINE'S THEORY. 483
formly along the horizontal,, it will assume the form of a parabola,
This case does not occur with masonry arches.
2. If the load is vertical and distributed uniformly along the
curve,, the resulting curve is the common catenary, of which the
equation is
m / x x\
y = ~{£!™+JS~™), (13)
in which y is the ordinate to any point, m the ordinate to the apex,
E the base of the Naperian logarithms, and x the abscissa corre-
sponding to y. Approximately., this case may occur with masonry
arches, since the above law of loading is nearly that of an arch
whose intrados is the common catenary and which supports a span-
drel wall of masonry having a horizontal upper surface (see 2, page
445).
3. Three points fix the common catenary ; and hence, if the posi-
tion of the springing lines and the crown are assumed., the depth of
the load at the crown is fixed by the equation of the curve. This
limitation would often interfere with the use- of the common cate-
nary in building arches. To meet this difficulty, Ilankiue trans-
forms the common catenary by the principle of what ho calls paral-
lel projections, i. e.y by increasing or decreasing one set of the
rectangular co-ordinates to the curve without changing the other,
and obtains the transformed catenary. The equation of the
curve is
in which ?/0 is the ordinate to the apex, and m is the modulus of the
curve and is found by the formula
. . (15)
_„
hyp. log. [•#- + \/-y-\ -
Ji a -r r
The determiiiation of values of y by equation (14) is not easy except
with either a table of Naperian logarithms or a table of results
deduced therefrom, and even then it is tedious.
With this curve we may assume the springing lines, the crown,
and the depth of load at the crown, and then compute tho curve of
equilibrium. The transformed catenary differs from a circular arc
between the same points only in being slightly (and frequently only
484 ARCHES. [CHAP. xvm.
very slightly) sharper in the haunches ; and hence it is not neces-
sary to discuss it further.*
4. If the load is uniform and normal at every point, the curve
of equilibrium is plainly a circle. An example of this case would be
an empty masonry shaft standing in water.
5. The ellipse is the form assumed by a cord under a load com-
posed of horizontal and vertical components which are constant
along the horizontal and vertical lines, but which differ from each
other in intensity. There is no case in ordinary practice where the
pressures upon an arch are strictly identical with those which give
an elliptical curve of equilibrium. The curve of equilibrium of a
tunnel arch through earth, when the depth belpw the surface is
great compared with the rise of the arch itself, approximates to an
•ellipse. The load is nearly uniform along the horizontal, while the
horizontal force at any point is some fractional part of the vertical
one at the same point ; and therefore the horizontal forces are
nearly uniform. It is readily shown that the intensity (the pressure
per unit of area perpendicular to the force) of the vertical com-
ponent is to that of the horizontal component as the square root
of the horizontal diameter of the ellipse is to the square of its ver-
tical diameter ; f that is to say,
the horizontal axis __ , / intensity of vertical component
the vertical axis ~~ intensity of horizontal component' ^ '
6. If the forces acting on the linear arch are normal and
increase in intensity in proportion to the distance of the points of
application from, a horizontal line, the curve is a, li-ydroxtatic arch.
A tunnel under water is an example of this method of loading.
The form of the curve is shown in Fig. 134, of which only the portion
— £ BA 0 is available in the construction of
arches. The equation of the curve is
p p = -wp() PO = a constant, . (17)
in which p is the normal pressure on a
184- unit area at any point, p the radius of
* For two numerical examples of the method of employing the transformed cate-
nary in the design of an areh, see an article by W. II. Booth in Van Nostrand's
Engin'g Mag. , vol. xxxi, pp. 1-10 ; and for another, see an editorial in Engineering
JVews, vol. xviii, p. 872.
t Rankine's Civil Engineering, p. 205.
ART. 1.] BANKINE'S THEORY. 485
curvature at the same point, y the distance from the line 0 (the
surface) to any point, p0 and t/0 the values of p and y for the point
A, and w the weight of a unit of volume of the loading.
" The true semi-ellipse of a given span and rise differs from the
hydrostatic arch by being of somewhat sharper curvature at the
crown and springing and of somewhat flatter curvature at the
haunches, and by enclosing a somewhat less area. The application
of the hydrostatic arch to practice is founded on the fact that every
arch, after having been built, subsides at the crown, and spreads,
or tends to spread, at the haunches^ which therefore press horizon-
tally against the filling of the spandrels ; from which it is inferred
as probable that, if an arch be built of a figure suited to equilibrium
under fluid pressure — /. e., pressure of equal intensity in all direc-
tions,— it will spread horizontally, and compress the masonry of the
spandrels until the horizontal pressure at each point becomes of
equal intensity to the vertical pressure, and is therefore sufficient to
keep the arch in equilibrio." *
7. If the vertical and the horizontal components of the normal
force differ from each other but both vary as the distance of the
point of application from a horizontal line, the curve of equilbrium
is the (/ecstatic arch. An arch in clean dry sand is the best example
of this form of loading. The geostatic arch bears the same relation
to. the hydrostatic arch that the ellipse does to the circle. The
geostatic curve can be produced from that of the hydrostatic curve
by increasing or decreasing one set of ordinates without altering the
other. If px be the horizontal intensity of the forces acting on the
hydrostatic arch and p'x be that for the geostatic arch, then
px = cp'x ; and if x is the horizontal diameter at any point of
the hydrostatic curve and a/ the same for the geostatic, then
xf = c x. \
S. Eankine next discusses the following more general problem :
" Given the curve of a linear arch and the vertical components of a
symmetrical load, to find the intensity and distribution of the
horizontal components necessary to produce equilibrium.
* Rankine's Civil Engineering, pp. 419-20.
t For a numerical example of the method of employing the geostatic curve for the
intrados of tunnel arches, see an article—" The Employment of Mathematical Curves
as the Intrados of Arches "—by W. H. Booth in Van NostranePs Engin'g Mag., vol.
xxx, pp. 355-60.
486 ARCHES. [CHAP. xvm.
C( Let V = the vertical load on any arc DC, — represented in
Fig. 135 by the line EG;
Vi = the vertical load on the serai-arch A C\
E = the horizontal load on any arc DC, — represented by
the line GF, Fig. 135 {
HI = the horizontal load on the semi-arch A C;
HQ = the compression at the crown C, — represented by the
line EC, Fig. 135;
0 = the compression on the rib at any point D, — repre-
sented by ED, Fig. 135 ;
px = the intensity of the horizontal force, i. e., the force
per unit of area perpendicular to its line of action;
py = the intensity of the vertical force;
j}Q = the value ofpy at the crown Q\
pQ = the radius of curvature at the crown (7;
1 = the angle that the tangent of the linear arch at any
point makes with the horizontal, — that is, i = the
angle EDG, Fig. 135.
FIG. 135.
rThen V= /%ycte; (18)
t/o -r* > v /^
(7= Fcoseci; (19)
H- Fcoti; (20)
d
_ ^g . d(Vcoti) v ,«,?y/_ .
Px~~~dy"~~ dy "" ^^"" " * ^ }
<c The integration constant for (21) is J70 ; and is found by equa-
tion (11), page 465, which, in the above nomenclature, becomes
jy —. p^ p^» ft>2)
AKT. 1.] RAKKIHTE'S THEORY. 487
However, before concluding this phase of the discussion of
arches, it is well to state that the only arches in common use are
the circular — either semi-circular or segmental — and the elliptic.
706. Stability of any Proposed Arch. To apply the preceding
principles in designing an arch, it is necessary to know both. the
vertical and the horizontal forces acting on the arch. Kankine
assumes* (1) that the vertical force acting on any part is the weight
of the masonry, earth, or other load vertically above the same ; and
(2) that the horizontal pressure of earth is given by the formula
,
sin 0
(S3)
^ 7
in which H is the horizontal pressure at any point, w the weight of
a unit of the earth, d the depth of earth over the point, and 0 tho
angle of repose. In the above nomenclature, the vertical compo-
nent is
V=wd. ........ (24)
By an application of these two principles are to be determined the
amount and distribution of the vertical and the horizontal forces
acting on the arch ; and then the equilibrium curve corresponding
to this form of loading (see § 705) is to be adopted for the intrados
of the proposed arch.
For an example, take the case of an arch under a high bank of
•earth whose angle of repose is 30°. Strictly, the curve of equi-
librium is the geostatic arch (see paragraph 7, § 705) ; but it will
be more simple and sufficiently exact, if we assume it to be an
ellipse, which is equivalent to assuming that the rise of the arch is
inconsiderable in comparison with the depth of earth over it. The
intrados is then to be an ellipse in which
= 4 A - sin & = 4/T (05}
1 + sin 0 ^ '
the Jiorizontal axis _
the vertical axis ~~ r H ~~ r 1 + sin 0
"If the earth is firm, and little liable to be disturbed, the propor-
tion of the half -span — or horizontal semi-axis — to the rise — or ver-
* Civil Engineering, p. 434.
t Bankine states (Civil Engineering, p. 320) that the horizontal pressure can not
be greater than w h ?!^~, nor less than w h- • ' . -~. Notice that the value employed
above is the minimum.
488 AKCHES. [CHAP, xvirr,
tical semi-axis—may be made greater than is given by the preced-
ing equation, and the earth will still resist the additional horizontal
thrust ; but that proportion should never be made less than the
value given by the equation, or the sides of the archway will be in
danger of being forced inwards." *
" There are numerous cases in which the form of the linear rib
suited to sustain a given load may at once be adopted for the in-
trados of a real arch for sustaining the same load, with sufficient
- exactness for practical purposes. The follow-
ing is the test whether this method is appli-
cable in any given case. Let A OB in Fig,
136 be one half of the ideal rib which it is-
proposed to adopt as the intrados of a real
arch. Draw A a normal to the rib at the
crown, so as to represent a length not ex-
. 136. ceeding two thirds of the intended depth of
the keystone. Draw a normal Bb at the springing of a length
such that
Bl _ thrust along rib at A „ , , ,
~Aa ~~ thrust along rib at B ' " " * ' ^ '
The thrust at A is found by equation (11), page 465 ; and the thrust
at any other point is given by equation (19), page 486. Construct
a line acb such that its perpendicular distance from the intrados at
any point, cC, is inversely as the thrust along the rib at that point.
Then if acb lies within the middle third of the proposed arch ring,.
the ideal rib ACB is of a suitable form for the intrados.
707. Eankine's general method of determining the stability of
a proposed arch is as follows: \
"The first step towards determining whether a proposed arch
will be stable, is to assume a linear arch parallel to the intrados or
soffit of the proposed arch, and loaded vertically with the same
weight, distributed in the same manner. Then by equation (21),
page 486, determine either a general expression, or a series of val-
ues, of the intensity px of the conjugate pressure, horizontal or
oblique as the case may be, required to keep the arch in equilibria
* Rankine's Civil Engineering, p. 434.
\ Ibid., p. 417.
I Ibid., pp. 421-22.
ART. 1 J
RANKINE'S THEORY.
489
under the given vertical load. If that pressure is nowhere nega-
tive, a curve, similar to the assumed arch5 drawn through the middle
of the arch ring will be, either exactly or very nearly, the line of
pressure of the proposed arch; px will represent, either exactly or
very nearly, the intensity of the lateral pressure which the real
arch, tending to spread outwards under its load, will exert at eacli
point against its spandrel and abutments; and the thrust along the
linear arch at each point will be the thrust of the real arch at the
corresponding joint.
" On the other hand, if px has some negative values for the
assumed linear arch, there must be a pair of points in that arch
where that quantity changes from positive to negative, and is equal
to nothing. The angle of inclination i at that point, called the
angle of rupture, is to be determined by placing the second member
of equation (21), page 486, equal to zero and solving for cot /. The
corresponding joints in the real arch are called the joints of rup-
ture ; and it is below those joints that conjugate pressure* from
without is required to sustain the arch and that consequently the
backing must be built with squared side- joints.
"In Fig. 137, let BCA represent one half of a symmetrical
arch, KLDE an abutment, and G
the joint of rupture — found by the
method already described. The point
of rupture, which is the center of re-
sistance of the joint of rupture, is ~
somewhere within the middle third
ot the depth of that joint; and from
that point down to the springing joint
B, the line of pressure is a curve sim-
ilar to the assumed linear arch, and
parallel to the intrados, being kept in FlG- 137-
cquilibrio by the lateral pressure between the arch, and its spandrel
and abutment.
" From the joint of rupture C to the crown A, the figure of the
true line of pressure is determined by the condition that it shall be
* A minus value of px will correspond to an outward putt, and consequently the
backing below the joint of rupture should be capable of resisting tension.
490 ABCHES. [CHAP. xvm.
a linear arch balanced under vertical forces only ; * that is to say,
the horizontal component of the thrust along it at each point is a
constant quantity, and equal to the horizontal component of the
thrust along the arch at the joint of rupture.
" The only point in the line of pressure above the joint of
rupture which it is important to determine is that of the crown of
the arch, A\ and.it is found in the following manner : Find the
center of gravity of the load between the joint of rupture C and the
crown A ; and draw through that center of gravity a vertical line.
Then if it be possible, from any point, such as M, in that vertical
line, to draw a pair of lines, one parallel to a tangent to the soffit at
the joint of rupture -and the other parallel to a tangent to the soffit
at the crown, so that the former of those lines shall cut the joint of
rupture and the latter the keystone, in a pair of points which are
both within the middle third of the depth of the arch ring, the
stability of the arch will be secure ; and% if the first point be the
point of rupture, the second will be the center of resistance at
the crown of the arch and the crown of the true line of pressures.
"When the pair of points, related to each other as above, do not
fall at opposite limits of the middle third of the arch ring, their
exact positions are to a small extent uncertain ; but that uncertainty
is of no consequence in practice. Their most probable positions are
equidistant from the middle line of the arch ring.
"Should the pair of points fall beyond the middle third of the
arch ring, the depth of the arch stones must be increased."
708. Reliability of Rankine's Theory. 1. This theory is ap-
proximate since it makes no attempt to determine the true line yf
resistance, but finds only a line of resistance which lies within the
middle third of the arch ring.
2. The value of the radius of curvature to be used in finding
the crown thrust is indeterminate. It is frequently, but erroneously,
taken as the radius of the intrados at the crown.
3. The method of finding the center of pressure at the crown
and also at the joint of rupture assumes that the portion CM A,
Fig. 137, is acted upon by only three forces ; viz., the vertical load,
the thrust at the crown, and the pressure on the joint of rupture.
* From this it appears that Eankine himself disregards, for that part of the arch
above the joint of rupture, the principal characteristic of his theory, viz. : the recog-
nition of the horizontal components of the external forces ; and hence this theory
is, in fact, the same as Scheffler's (§§ 695-703).
ART. 1.] IllXKTXi;- THE'Jl.Y. 4r<!
This Is erroneous fr ) . » c\ii*s * ;t wgw t> tL * 1 or:*: * ,t.;" i rrii' r » -* *«*
of the externul forces ar, 1 h i .-»* tl t i.f ^iul c »**.>r »f }rc^ir? ..t
the joint of nipt .11^ i-» uea.-ei the :nt..itioi? t! *xi tL*' ,' -it.<- i < f '
:is found in Ficr. i:)T : ami |^j lom^e It 1LJ- u. m-v vaV.e :' : M"
thrust at the crown whi<*h, in jrine.ul, wiL ui4**^ fr* n* tLi<. « i ' 1 >'-»- *
in finding the position of the joint of rupture.
4. Rankine himself say.s the nsethod of § 707 is inapplicable
to a circular arch greater than 90% and gives a complicated formula
for that case.
Rankine's theory is complicated and less
•either Sclieffler's (§ 695) or the theory (§ 688).
709. OTHEE THEOBIES OF THE AMS. There are several
In more or less common use, of determining tlie stability of the vons-
soir iircli, many of which are but different combinations of the pre-
ceding principles, wMk* some have a much less satisfactory basis.
It is not necessary to discuss any of these at length ; but there is
one which, owing to the frequency with which it is employed,
requires a few words. It is, the same as Scheffier's (g§ 695-703), ex-
cept iu assuming that the line of resistance passes through the
middle of the crown Joint and also through the Middle of the spring-
ing joint. The line of resistance is then determined in any one of
a ii n m her of ways ; and the arch is said to be stable, If the line of
resistance lies in the Middle third of the section of the arch ring.
This theory is much less satisfactory than Scheffler's and possesses
p.o advantage over it.
710. THEOEY OF THE ELASTIC AMH. It has long been recognized
that all theories for the voussoir arch are very unsatisfactory ; and
hence it has been proposed to- consider the masonry arch as an
elastic curved benm fixed at Its ends, and examine its stability by
the principles employed in computing the strains in arches of iron
or wood. There is no essential difference, as far as the theory is
Concerned, between the iron and the stone arch ; but there is great
difficulty in applying the mathematical theory of elasticity to the
masonry arch. The theory of elasticity when applied to the
masonry arch has the following sources of error, in addition to those
of the ordinary theory of the elastic arch : 1. There is great un-
certainty as to the external forces (§ fi»56). 2. We have no definite
knowledge concerning either the modulus of elasticity (£§ 16 and
140) or the ultimate strength of masonry (§§ "221-23, and §§ 24G-
492
AECHES.
[CHAP. XYIII,
49). 3. The stone arch is not homogeneous ; i. e., the modulus of
elasticity is not constant, but varies between that of the stone and
the mortar. 4. Slight imperfections in the workmanship — as, for
example, a projection on the bearing surface of an arch stone or a
pebble in the mortar — would break the continuity of the arch, and
render the theory inapplicable. 5. The stability of the arch would
be greatly influenced by the action of the center, — its rigidity, the
method of loading it to prevent deformation, and the method and
rapidity of striking it.
The application of the theory of elasticity to stone arches has
been considerably discussed in late years ; but it is generally con-
ceded that the results are, for the most part, illusory, since the
much simpler methods give results equally reliable. The explana-
tion of the theory of the elastic masonry arch as given by Prof essor
Greene in Part III — Arches — of his " Trusses and Arches " is all
that can be desired ; and hence this theory will not be discussed
here.
71 L STABILITY OF ABUTMENTS AND PIEES. The stability of the
abutment is in a measure indeterminate, since it depends upon the
position of the line of resistance of the arch. The stability of
the abutment may be determined most easily by treating it as a
part of the arch, i. e.3 by extending the
load line so as to include the forces acting
upon it and drawing the reactions in the
usual way ; or its stability may be deter-
mined as follows : Assume that it is re-
quired to test the stability of the abutment
shown in Fig. 138. Let qc represent the
direction of the resultant pressure on the
joint AB. g is the center of gravity of the
section ABC of the abutment, and g% that
for the section ABED* At a — the point
FIG. 135. where a vertical through g intersects qc-i
prolonged — lay off, to scale, a line ad equal to the weight of ABO,
and also a line ab equal to the pressure qc^ ; then c>2 — the point
where the diagonal ea pierces A C — is the center of pressure on A 61
* For a method of finding the center of gravity when the section is a trapezoid,
see the third paragraph of § 494 (page 318).
ART. L] STABILITY OF THE ABUTMENT. 493
In a similar manner, c3 is found to be the center of pressure on
DK
The amount of the pressure on A 0 is given by the length of the
line ae ; and the stability of the joint against crushing can be de-
termined as described in §§ 670-72 arid paragraph 2 of § 690.
The stability against rotation may be determined as described in
§ 669 and paragraph 1 of § 690. A line — not shown — connecting
CD c*> c-s> is the line of resistance of the abutment, to which the
joints should be nearly perpendicular (see § 674 and division 3 of
§ 690).
712. In Fig. 133 (page 480) is shown the line of resistance for
the abutment according to the rational theory of the arch (§§ 688-
94), and also that according to Scheffler's theory (§§ 695-703),—
the former by the solid line and the latter by the broken one.
Since to overestimate the horizontal components of the external
forces would be to err on the side of danger, in applying the former
theory in Pig. 133, the horizontal component acting against the
abutment was disregarded on the assumption that the abutment
might be set in a pit without greatly disturbing the surrounding
earth. If the horizontal component had been considered, the dif-
ference between the lines of resistance according to the two theories
would have been still greater. ISTotice that the analysis which
recognizes the existence of the horizontal forces,, i. e., the rational
theory, permits a lighter abutment than the theory which assumes
the external forces to be entirely vertical.
The omission of the horizontal components assumes that the
only object of the abutment is to resist the thrust of the arch ; and
that consequently the flatter the arch the greater the thrust and the
heavier the abutment. Ordinarily the abutment must resist the
thrust of the arch tending to overthrow it and to slide it outward,
and must act also as a retaining wall to resist the lateral pressure of
the earth tending to overthrow it and to slide it inward. For
large arches the former is the more important ; but for small
arches, particularly under high embankments, the latter is the more
important. Hence, for large arches or for an arch having a light
surcharge, the abutment should be proportioned to resist the thrust
of the arch; but for small arches under a heavy surcharge of
earth, the abutment should be proportioned as a retaining wall
(Chap. XIV).
494 • ARCHES. [CHAP, xvm.
Although the horizontal pressure of the earth can not be com-
puted accurately, there are many conditions under which the
horizontal components should not be omitted. For example, if the
abutment is high, or if the earth is deposited artificially behind it,
ordinarily it would be safe to count upon the pressure of the earth
to assist in preventing the abutment from being overturned out-
wards. Finally, although it may not always be wise to consider the
earth pressure as an active force, there is always a passive resistance
which will add greatly to the stability of the abutment, and whose
intensity will increase rapidly with any outward movement of the
abutment (see last paragraph of § 666).
For empirical rules for the dimensions of abutments, see §§
722-23.
ART. 2. EULES DERIVED FROM PRACTICE.
713. In the preceding article it was shown that every theory of
the arch requires certain fundamental assumptions, and that hence
the best theory is only an approximation. Further, since it is prac-
tically impossible, by any theory (§ 693), to include the effect of
passing loads, theoretical results are inapplicable when the moving
load is heavy compared with the stationary load. It was shown
also that the stability of a masonry arch does not admit of exact
mathematical solution, but is to some extent an indeterminate
problem. At best the strains in a masonry arch can never be com-
puted anything like as accurately as those in metallic structures.
However, this is no serious matter, since the material employed in
the former is comparatively cheap.
Considered practically, the designing of a masonry arch is
greatly simplified by the many examples furnished by existing
structures which afford incontrovertible evidence of their stability
by safely fulfilling their intended duties, to say nothing of the
history of those structures which have failed and thus supplied
negative evidence of great value. In designing arches, theory
should be interpreted by experience ; but experience should be
studied by the light of the best theory available.
This article will be devoted to the presentation of current prac-
tice as shown by approved empirical formulas and practical rules,
and by examples.
ART. 2.] RULES DERIVED FROM PRACTICE. 495
714. EMPIRICAL FORMULAS. Numerous formulas derived from
existing structures have been proposed for use in designing masonry
arches. Such formulas are useful as guides in assuming propor-
tions to be tested by theory,, and also as indicating what actual
practice is and thus affording data by which to check the results
obtained by theory.
As proof of the reliability of such formulas, they are frequently
accompanied by tables showing their agreement with actual struct-
ures. Concerning this method of proof , it is necessary to notice
that (1) if the structures were selected because their dimensions
agreed with the formula,, nothing is proven; and (2) if the struct-
ures were designed according to the formula to be tested, nothing
is proven except that the formula represents practice which is
probably safe.
At best, a formula derived from existing structures can only
indicate safe construction, but gives no information as to the degree
of safety. These formulas usually state the relation between the
principal dimensions ; but the stability of an arch can not be de-
termined from the dimensions alone, for it depends upon various
attendant circumstances,, — as the condition of the loading (if earth,,
upon whether loose or compact ; and if masonry, upon the bonding,
the mortar, etc.), the quality of the materials and of the workman-
ship, the manner of constructing and striking the centers, the
spreading of the abutments, the settlement of the foundations, etc.
The failure of an arch is a very instructive object lesson, and should
be most carefully studied, since it indicates the least degree of
stability consistent with safety. Many masonry arches are excessively
strong ; and hence there are empirical formulas which agree with
existing structures, but which differ from each other 300 or 400 per
cent. All factors of the problem must be steadily borne in mind in
comparing empirical formulas either with each other or with theo-
retical results.
A number of the more important empirical formulas will now be
given, but without any attempt at comparisons, owing to the lack
of space and of the necessary data.
715. Thickness of the Arch at the Crown. In designing an arch,
the first step is to determine the thickness at the crown, L e.? the
depth of the keystone.
496 ARCHES. [CHAP. xvm.
Let d = the depth at the crown, in feet ;
p = the radius of curvature of the intrados, in feet ;
r = the rise, in feet ;
s = the span, in feet.
716. American Practice. Traut wine's formula for the depth
of the keystone for a first-class cut-stone arch, whether circular or
elliptical, is
(27)
second-class work, this depth may be increased about one
eighth part; and for trick work or fair riMle, about one third."
717. English Practice. Kankine's formula for the depth of
keystone for a single arch is
d= 4/O.lS/o; (28)
for an arch of a series,
d=V^YTp; (29)
.and for tunnel arches, where the ground is of the firmest and safest,
and for soft and slipping materials,
487 (8i)
The segmental arches of the Kennies and the Stephensons, which
tire generally regarded as models, "have a thickness at the crown
of from -^ to ^g- of the span, or of from -fa to -^V °^ ^ne radius of
the intrados.1"
718. French Practice.* Perronnet, a celebrated French engi-
neer, is frequently credited with the formula,
*Frorn "Proportions of Arches from French Practice," by E. Sherman Gould
in Van Nostrand's Engin'g Mag., vol. xxix, p. 450.
ART. 2.] RULES DERIVED FROM PRACTICE. 497
•as being applicable to arches of all forms — semi-circular,, segmental,
•elliptical, or basket-handled, — and to railroad bridges or arches
sustaining heavy surcharges of earth. " Perronnet does not seem,
however,, to have paid much attention to the rule ; but has made
his bridges much lighter than the rule would require/' Other
formulas of the above form, but having different constants, are also
frequently credited to the same authority. Evidently Perronnet
varied the proportions of his arches according to the strength and
-weight of the material, the closeness of the joints, the quality of
mortar, etc. ; and hence different examples of his work give differ-
ent formulas.
Dejardin's formulas, which are frequently employed by French
.engineers, are as follows :
For circular arches,
if - = 1, d=l + 0.1/>; ..... (33)
5
if 1 = $, d = l+0.05p; .... (34)
s
if - = £, d = l + 0.035 p; .... (35)
5
if J = ,V, d = l + O.Q2p; .... (36)
o
For elliptical and basket-handled arches,
if £= i, d=l + 0.01p ...... (37)
Croizette-Desnoyers, a French authority, recommends the fol-
lowing formulas :
if -> |, d = 0.50 + 0.28 V~2~p] . . . (38)
s
if ~= £, ^ = 0.50 + 0.26 VTp~; . . . (39)
if = ^, ^ = 0.50 + 0.20 VYp; . . . (40)
498
ARCHES.
[CHAP, xviii.
719. Notice that in none of the above formulas does the char-
acter of the material enter as a factor. Notice also that none of
them has a factor depending upon the amount of the load.
Table 62 is given to facilitate the comparisons of the preceding
formulas with each other and with actual structures. Values not
given in the table can be interpolated with sufficient accuracy. It is
remarkable that according to all formulas credited to Perron net the
thickness at the crown is independent of the rise, and varies only
with the span. Notice that by Dejardin's formulas the thickness-
decreases as the rise increases, — as it should.
TABLE 62.
COMPARISON OF EMPIKICAL FORMULAS FOR DEPTH OF KEYSTONE.
PROPORTION OP RISE TO SPAN.
FORMULA.
Semi-circle.
Rise
Spun "" *
Rise
Span ~ T*
SPAN.
SPAN.
SPAN.
10
50
100
10
50
100
10
50
100
Traufc wine's, for first-class work
u second " u
" third l4 "
Rankiue's
.99
1.11
1.32
.77
1.51
1.50
1.38
1.93
2.23
2.64
1.73
3.26
3.50
2.48
2.70
3 04
3.60
2.45
5.43
6.00
3.30
1.11
1.25
1.48
1.00
1.51
1.42
1.56
2.23
2.51
2.97
2.25
3.26
3.07
2.86
3.09
3.43
4.12
3.1(5
5.43
5.17
3.85
1.26
1.44
1.68
1.25
1.51
1.26
1.62
2.57
2.89
3.42
2.70
3.26
2.30
3.01
3.55
4.00
4.73
3,95
5.43
2.00'
4.05
Perronnefc's •
Dejardin's
Croizettf-Desnoyers^s
720. Thickness of the Arch, at the Springing. Generally the
thickness of the arch at the springing is found by an application of
theory ; and hence but few empirical formulas are given for this
purpose.
Trautwine gives a formula for the thickness of the abutment,
which determines also the thickness of the arch at the springing;
(see § 722).
" The augmentation of thickness at the springing line is made,
by the Stephensons, from 20 to 30 per cent. ; and by the Bennies,
about 100 per cent."
721. If the loads are vertical, the horizontal component of the
compression on the arch ring is constant ; and hence, to have the
mean pressure on the joints uniform, the vertical projection of the
AET. 2.] RULES DERIVED FftOM PRACTICE. 499
joints should be constant. This principle leads to the following
formula, which is frequently employed : The length, measured radi-
ally, of each joint between the joint of rupture and the crown
sliould be such that its vertical projection is equal to the depth of
the keystone. In algebraic language, this rule is
Z = d sec a, ....... (41)
in which I is the length of the joint, d the depth at the crown, and
a. the angle the joint makes with the vertical.
The length of the joint of rupture,* i. e.y the thicknesss of the
arch at the practical springing line, can be computed by the above
formula. The following are the values for circular and segmental
arches :
, If j> I, l = 2.00d; ..... (42)
..... (43)
o
«-= I, Z=1.24d; ..... (44)
o
« ^ = ^r, I = l.l5d; ..... (45)
o
«*—£:, l~l.Wd ...... (46)
s
722. Thickness of the Abutment, f Trautwine's formula is
...... (47)
in which t is the thickness of the abutment at the springing, p the
radius, and r the rise, — all in feet, " The above formula applies
equally to the smallest culvert or the largest bridge — whether cir-
cular or elliptical, and whatever the proportions of rise and span —
and to any height of abutment. It applies also to all the usual
methods of filling above the arch, whether with solid masonry to
the level of the top of the crown, or entirely with earth. It gives
a thickness of abutment which is safe in itself without any back-
ing of earth behind it, and also safe against the pressure -of the
* Concerning the method of determining the joint of rupture, -see §§ 680-82.
t For a theoretical discussion of this subject, see §§ 711-12.
500
ARCHES.
[CHAP. xvin.
earth when the bridge is unloaded. It gives abutments which
alone are safe when the bridge is loaded ; but for small arches, the
formula supposes that earth will be deposited behind the abut-
ments to the height of the roadway. In small bridges and large
culverts on first-class railroads, subject to the jarring of heavy
trains at high speeds, the comparative cheapness with which an
-excess of strength can be thus given to important structures has led,
in many cases, to the use of abutments from one fourth to one half
thicker than those given by the preceding rule. If the abutment is
of rough rubble, add 6 inches to the thickness by the above formula,
to insure full thickness in every part."*
To find the thickness of the abutment at the bottom, lay off, in
Fig. 139, on = t as computed by the above equation ; vertically above
FIG. 139.
n lay off an = half the rise ; and horizontally from a lay off cib = one
twenty-fourth of the span. Then the line bn prolonged gives the
back of the abutment, provided the width at the bottom, sp, is not
less than two thirds of the height, ns. "In practice, os will rarely
exceed this limit, and only in arches of considerable rise. In very
high abutments,, the abutment as above will be too slight to sustain
the earth pressure safely." *
To find the thickness of the arch, compute the thickness ce by
equation (47), page 499, draw a curve through G parallel to the
intrados, and from b draw a tangent to the extrados; and then will
bfe be the top of the masonry filling above the arch. Or, instead of
drawing the extrados as above, find, by trial, a circle which will
pass through I, e, and b', the latter being a point on the left abut-
ment corresponding to J on the right.
* Trautwine's Engineer's Pocket-book.
ART. 2.] ttULES DERIVED PROM PRACTICE. 501
Trautwme's rule, or a similar one, for proportioning the abut-
ment and the backing is frequently employed. For examples, see
Plates IV and V.
723. Rankine s&ys that in some of the best examples of bridges
the thickness of the abutment ranges from one third to one fifth of
the radius of curvature of the arch at its crown.
The following formula is said to represent German and Russian
practice)
t = 1 + 0.04, (5 s + 4/0, ..... (48)
in which li is the distance between the springing line and the top of
the foundation.
724. DIMENSIONS OF ACTUAL ARCHES. Table 63 (pages 502-3)
gives the dimensions of a number of actual structures, which, from
their wide distribution and the frequency with which most of them
are cited as examples, may be taken to represent average practice.
Unfortunately the details concerning most of them are very
meager, the following and those in the table being all that can be
obtained.
No. 1 is the longest span ever built.
No. 2 is the longest span in existence.* The arch is a circular
arc of 110°. It carries a conduit (clear diameter 9 feet) and a car-
riage-way (width 20 feet). The top of the roadway is 101 feet above
the bottom of the ravine. The voussoirs are Quincy (Mass.) granite,
and are 2 feet thick, 4 feet deep at the crown, and 6 feet at the
springing. The spandrel filling is composed of Seneca sandstone,
which, for a distance above the arch of 4 feet at the crown and 15
feet at the springing, is laid in regular courses with joints radial to
the intrados ; and hence the effective thickness of the arch is about
8 feet at the crown and about 21 feet at the springing (see Fig. 159,
page 525). The abutments are prevented from spreading by the
bed-rock in the side-hills.
No. 9 is a remarkable bridge. It was built by an " uneducated"
mason in 1750: and although a very rude construction, is still in
perfect condition. A former bridge of the same general design at
the same place fell, on striking the centers, by the weight of the
haunches forcing up the crown ; and hence in building the present
structure the load on the haunches of the arch was lightened by
* Concerning arched clams, see foot of page 330 and top of 331.
502
ARCHES.
[CHAP. xvin.
TABLE
DATA CONCERNING
Kef.
No.
LOCATION AND DESCRIPTION.
1 TrezzoT Italy; built in 1380, destroyed in 1427; granite
2 Cabin John, Washington (D. C.); aqueduct; granite (see § 724, p. 501)
3 Grosvenor bridge, Chester, England
4 Ballochmyle, over the Ayr, Scotland
5 London bridge, England; street; granite
6 Gloucester, England
7 Turin, Italy
8 Alma bridge, Paris; small rough rubble in cement ; railroad
9 Pont-y-Prydd, Wales; rough nibble in lime mortar (see § 724, p. 501)
10 Maidenhead, England; brick in cement; railroad
11 Neuilly, France; five spans usee page 504)
12 Bourbonnais Railway bridge ; France ; cut granite (see page 504)
13 Waterloo bridge, London, England; granite .
14 Tongueland. England ; turnpike
15 Napoleon bridge, Paris; small rough rubble in cement; railroad
16 Mantes, over Seine, France
17 Etherow river, England ; railroad ; four spans
18 Bishop Auckland, England ; turnpike ; built in 1388
19 Wellington bridge, Leeds, England
20 Louis XIX
21 Dean bridge, near Edinburgh, Scotland ; turnpike
22 Licking Aqueduct, Chesapeake & Ohio canal
28 Dorlaston
24 Over the Oise, France. ; railroad
25 Trilport, France : railroad
26 Conemaugh viaduct, Pennsylvania R. R. ; sandstone in lime (no sand)
27 Royal Border viaduct, England ; brick in cement
28 Posen viaduct, Germany: brick in cement
29 Orleans, France; railroad
30 Hutcheson bridge, Glasgow, Scotland
31 Falls bridge, Philadelphia & Reading R. R
3-2 St. Maxence, over the Oise, France
33 Westminster bridge, London
34 Allentown, England; turnpike
35 Staines, England : turnpike
36 Black Rock Tunnel bridge, Philadelphia & Reading R. R
37 Edinburgh
38 Swatara, Philadelphia & Reading R. R. ; brick
39 Brent R, R. viaduct, England ; brick in cement
40 Wellesley b ridge at Limerick .".!!!.!!
41 Bow bridge, Kngland; turnpike
42 Houghton river, England ; railroad
48 Bewdly, England; turnpike
44 Chestnut Street bridge, Philadelphia; brick in cement
45 Carrollton viaduct, near Baltimore; railroad ; granite
46 Llanwast, in Denbighshire, Wales; built in 1036; turnpike
47 Monocacy viaduct, Chesapeake & Ohio canal
48 Over the Forth, at Stirling [
49 Nemours, France
50 Abattoir Street, Paris ; railroad
51 Ddle, over the Doubs, France
52 Chateau Thierry, France ! . . ]
53 Avon viaduct, England; brick in cement
54 Filbert St., Extension Pennsylvania R. R., Philadelphia; brick in lime mortar..
55 James River aqueduct. Virginia
56 Des Basses-Granges, Orleans & Tours, France
57 Over the Salat. France .'
58 Pesmes. over the Ougnon, France
59 Philadelphia & Reading R. R !.!!.'!.' ! '.'.'.'.'.'.'.'.'. '. ]'.'.'.'.'.'.".'.'.
60 Couturette, Arbois, France
61 Tonoloway culvert, under Chesapeake & Ohio canal; rubble in* cement.! ! ! ! . ! . !
* C = semi-circle ; E = elliptical ; B = basket-handled.
ART. 2.]
RULES DERIVED FROM PRACTICE.
503
63.
ACTUAL, AKCHES.
Ref.
No.
Engineer.
Curve
of
Intrados.
1
2 Meigs C
3 Hartley C
4 Miller C
5 Rennie E
6 Telford E
7 Mosca C
8 Darcel E
9 Edwards C
10 Brunei E
11 Perronnet B
12 Vaudray C
13 Rennie E
14 Telford C
15 Couche C
16 E
IT Haskoll C
18 C
19 Rennie....' C
•20 Perronnet C
21 Telford C
22 Fisk C
23 ' C
24 C
25 E
26 C
27 C
28 C
29 E
30 Stephenson C
31 C
32 Perronnet C
33 Labelye C
34 Stephenson C
35 Rennie C
36 Robinson C
37 Mylne C
38 Osborne C
39 Brunei E
40 E
41 Walker E
42 Haskoll C
43 Telford C
44 Kneass... C
45 C
46 Jones C
47 Fisk E
48 C
49 Perronnet C
50 C
51 E
52 Perronnet, E
53 Vignoles E
54 C
55 Ellet C
56 C
57 C
58 Bertrand C
59 Steele C
60 C
61 Fisk C
Span.
feet
251
220
200
181
152
150
148
141
140
128
128
124
120
118
116
115
100
100
100
94
90
90
87
83
81
80
79
79
78
77
76
75
74
72
72
70
70
70
66
65
60
60
58
58
54
53
53
53
52
51
50
50
50
49
46
45
44
43
40
Rise.
feet.
88
57
42
90.5
29.5
35
18
28
35
24
32
6.92
32
38
14.8
34
25
22
15
9.75
30
15
1&5
11.75
28
40
40
16
26.3
13
25
6.40
38
11.50
9.25
16.5
36
25
17.6
17.5
13.75
32.5
20
18
29
17
9
10.25
3.75
5.11
17.50
17.0
15
7
7
24.5
6.27
3.83
8
6,13
15
Radius
at
Crown.
feet.
133
134
140
90
162
98
160
103
88
369
159
281
112
65
120
49
75
76
40
40
58
43
119
47
44
47
33
34
29
33
45
28.3
47
24
34
21
THICKNESS.
Crown.
feet.
4.00
4 t
4.60
4.50
4.75
4.50
4.92
4.92
1.50
5.25
5.13
2.67
4.50
3.50
4.00
6.40
4.00
1.83
3.00
3.67
3.00
2.83
3 50
4.60
4.45
3.00
2.66
4 66
3.95
3.50
3.00
4.80
7.60
2.50
3.00
2.75
2.75
3.50
3.00
2.00
2.50
2.75
2.20
2.50
2.50
1.50
2.50
2.75
3.16
2.97
3.75
3.75
2.00
2.00
2.66
3.95
3.63
3.83
2.50
2.97
2.00
Spring-
ing.
feet.
7.00
6.00
9.00
2.50
7.16
3.60
8.00
4.00
i.RS
7.00
3.50
4.50
14.00
3.00
6.00
2.75
3.50
t See § 720, and also Fig. 159, page 525.
504 ARCHES. [CHAP. XVIIL
leaving horizontal cylindrical openings (see third paragraph of
§ 730) through the spandrel filling. The outer, or showing, arch
stones are only 2.5 feet deep, and that depth is made up of two-
stones ; and the inner arch stones are only 1.5 feet deep, and but
from 6 to 9 inches thick. The stone quarried with tolerably fail-
natural beds, and received little or no dressing. It is a wagon-road
bridge, and has almost no spandrel filling, the roadway being dan-
gerously steep. A strain sheet of the arch shows that the line of
resistance remains very near the center of the arch ring (see § 730).
The mean pressure at the crown is about 244 pounds per square-
inch. On the whole it is an example of creditable engineering.
No. 11, as designed, had a radius at the crown of 1GO feet ; but
the arch settled 2 feet on removing the center, and increased the
radius to about 250 feet.
No. 12 is noted for its boldness. This design was tested by
building an experimental arch — at Soupes, France — of the propor-
tions given in the table, and 12 feet wide. The center of the ex-
perimental arch was struck after four months, when the total set-
tlement was 1.25 inches, due mostly to the mortar joints, which
were about one quarter inch ; and it was not injured by a dis-
tributed load of 500 pounds per square foot, nor by a weight of 5-
tons falling 1.5 feet on the key.
No. 46 is said to have " approached a horizontal line in conse-
quence of the substitution of vehicles for pack-horses."
725. Table 63 affords some striking comparisons. For exam-
ple, Nos. 8 and 9 have practically the same span ; and as the rise
of the former is four fifths that of the latter, the thickness at the
crown of the former should be only about one and a .quarter times
that of the latter, while in fact it is 3.3 times as thick. How-
ever, the former carries a railroad, and the latter a turnpike ; but,
on the other hand, the former io laid in cement, and the latter in
lime.
Nos. 11 and 12 have nearly the same span, but the rise of the
former is 4.7 times the latter ; and if the thickness at the crown
were in like proportion — as it should be, — that of the former
woiild bo only 0.6 feet. Also compare No. 32 with No. 3;) ; and
No. 33 with Nos. 9 and 18.
726. Dimensions of Abutments. For examples of the abutments
of railway culverts, see Tables 49-52 (pages 425-31). Table 64,'
ART. 2.]
RULES DERIVED FROM PRACTICE.
505
below, gives the dimensions of a number of abutments represen-
tative of French, railroad practice.
TABLE 64.
DIMENSIONS OF ABUTMENTS FROM FRENCH RAILKOAD PRACTICE.*
6
fc
1
DESIGNATION OP BRIDGE.
CO
1
rt
<e
<H§
2l
£§?
81*
«
Height of
Abutment.
Mean thick-
ness of
Abutment.
1
2
8
CIKCULAR ARCHES.
De crochet, chemin de f er de Paris & Chartres
De Long-Sauts, chemin de fer de Paris 3, Chartres.
D'Enghien, chemin de f er du Nord
feet.
13.2
16.5
24 4
feet.
feet.
1.65
1.81
1 95
feet.
13.20
9.90
6 60
feet.
4.95
5.90
6.93
4
De Pantin canal St Martin . ....
07 o
2 47
11 85
10 *)5
5
De la Bastille, canal St. Martin
36 3
3 95
20 75
9 90
6
De Basses-Granges, Orleans a Tours
SKGMENTAL "ARCHES.
Des Frui tiers chemin du fer du Nord
49.4
13 2
2 31
3.95
1 81
6.60
13 20
12.50
5 94
8
De Paisia . .
16 5
2 64
1 7°
6 60
5 61
<)
De M6ry cb.em.in ds fer du Nord .
25 2
o 97
2 14
14 20
11 71
10
De Couturette at Arbois
42 9
6 13
2 97
6 60
17 16
11
Over the Salat « • •
46 1
6 °7
3 63
24 49
19 14
12
De la rue des Abattoirs, at Paris, chemin de fer de
Strasbourg . . . . .....
5° 9
5 11
o 97
12 96
33 00
13
Over the Forth at Stirling
53 5
10 °5
o 75
°0 75
16 00
14
15
St. Maxence, over the Oise
Over the Oisc chGinin de fer du Nord
77.2
go 7
6.40
11 75
4.80
4 60
27.85
17 90
38.94
31 65
Ifi
De Dorlaston . . ,
87 0
13 50
3 50
16 55
32 20
17
ELLIPTICAL OR FALSE-ELLIPTICAL ARCHES.
De Charolles
19 8
7 55
1 95
1.30
5.25
18
Du Canal St Denis . . .
30 5
14 85
2 95
10 20
12 35
19
°0
De Chateau-Thierry
De Dole over the £>oubs
51.3
52 4
17.10
17 50
3! 75
3 75
13.65
1 35
15.00
11.85
\V6lltlsl<?'V' gfa Limerick
70 0
17 50
2 00
12 00
16 50
22
23
D1 Orleans', chemin de fer de Vierzon
79.5
80 7
26.30
3.95
4 45
2.85
6 40
18.40
19 30
°d
115 2
34 40
6 40
3 20
28.90
25
De Neuillv. over the Seine
128.0
32.00
5.35
7.55
35.50
727. ILLUSTRATIONS or ACTUAL ABCHES.— For illustrations of
stone arches for railroad culverts, see Plates II-V. Fig. 143 (page 509)
shows a 50-foot stone arch on the Pennsylvania Railroad. For
brick arches for sewers, see Figs. 148 and 149 (pages 513 and 514).
For an example of a brick tunnel-arch,, see Fig. 147 (page 512).
Cabin John arch., the longest span in the world (see No. 2 of Table
63, page 502), is shown incidentally in Fig. 159 (page 525).
728. MINOE DETAILS. Backing, The backing is masonry of
inferior quality laid outside and above the arch stones proper, to
give additional security. The backing is ordinarily coursed or ran-
dom rubble, but sometimes concrete. Sometimes the upper ends
* E. Sherman Gould, in Van Nostrand's Engin'g Mag., vol. xxix, p. 450.
506
ARCHES.
[CHAP. XVIII.
of the arch stones are cut with horizontal surfaces, in which case
the backing is built in courses of the same depths as these steps
and bonded with them. The backing is occasionally built in ra-
diating courses, whose beds are prolongations of the bed- joints of
the arch stones ; but it usually consists of rubble, laid in horizontal
courses abutting against the arch ring, with occasional arch stones
extending into the former to bond both together. The radial
joints, possess some advantages in stability and strength, particu-
larly above the joint of rupture ; but below that j6int the horizon-
tal and vertical joints are best, since this form of construction the
better resists the overturning of the arch outward about the
springing line. Ordinarily, the backing has a zero thickness at or
near the crown, and gradually increases to the springing line ; but
sometimes it has a considerable thickness at the crown, and is pro-
portionally thicker at the springing.
It is impossible to compute the degree of stability obtained by
the use of backing ; but it is certain that the amount ordinarily
employed adds very greatly to the stability of the arch ring. In
fact, many arches are little more than abutting cantilevers ; and it
is probable that often the backing alone would support the struct-
ure, if the arch ring were entirely removed.
729. Spandrel Filling1. Since the roadway must not deviate
greatly from a horizontal line, a considerable quantity of material is
required above the backing to bring the
roadway level. Ordinarily this space is
filled with earth, gravel, broken stone,
cinders, etc. Sometimes, to save filling,
small arches are built over the haunches
of the main arch, as shown in Fig. 140.
The interior longitudinal walls may be
strengthened by transverse walls between
them. To distribute the pressure uni-
formly, the feet of these walls should
be expanded by footings where they rest
upon the back of the arch.
730. When the load is entirely sta-
tionary— as in an aqueduct or canal
FIG. 140. bridge — or nearly so — as in a long span
arch under a high railroad embankment, — the materials of the
ART. 2.]
RULES DERIVED PROM PRACTICE.
50?
spandrel filling and the size and position of the empty spaces may
be such as to cause the line of resistance to coincide,, at least very
nearly, with the center of the arch ring.
For example, ABCD, Pig. 141, represents a semi-arch for which
it is required to find a disposition of the load that will cause the
line of resistance to coincide with the center line of the arch ring.
Divide the arch and the load into any convenient number of divi-
sions, by vertical lines as shown. From P draw radiating lines par-
allel to the tangents of the center line of the arch ring at a, b, c,
etc., — the middle points of the successive divisions ; — and then at
such a distance from P that 01 shall represent, to any convenient
scale, the load on the first section of the arch ring (including its
own weight), draw a vertical line through 0. The intercepts 0-1,
1_2, 2-3, etc., represent, to scale, the loads which the several di-
visions must have to cause the line of resistance to coincide with
the center of the arch ring. Lay oil the distances 0-1, 1-2, etc.,
nt the centres of the respective sections vertically upwards from the
center line of the arch ring, and trace a curve through their upper
ends. The line thus formed — J3F, Fig. 141 — shows the required
amount of homogeneous load ; ?'. e.} JEJF is the contour of the
homogeneous load that will cause the line of resistance to pass
through the center of each joint.
Hence, by choosing the material of the spandrel filling and
508 ARCHES. [CHAP. xvm.
arranging the empty spaces so that the actual load shall be equiv-
alent in intensity and distribution to the reduced load obtained as-
above, the voussoirs can be made of moderate depth. The vacant
spaces may be obtained by the method shown in Fig. 140 (page
506) ; or by that shown in Fig. 142, in which A is a small empty
cylindrical arch extending from the face of one end wall to that of
the other. (See the description of arch No. 9, § 724, p. 501.)
Notice that the lines radiating successively from P, Fig. 141
(page 507), will intercept increasing lengths on the load-line ; and
that, therefore, the load which will keep a circular arch in equilib-
rium must increase in intensity per horizontal foot, from the crown
towards the springing, and must become infinite at the springing of
a semi-circular arch. Hence
it follows that it is not practi-
cable to load a circular arch,
beyond a certain distance from
the crown, so that the line of
resistance shall coincide with
the center line of the arch
ring.
731. Drainage. The drain-
age of arch bridges of more
than one span is generally ef-
fected by giving the top sur-
face of the backing a slight
inclination from each side toward the center of the width of the
bridge and also from the center toward the end of the span. The
water is thus collected over the piers, from whence it is discharged
through pipes laid in the masonry.
To prevent leakage through the backing and through the arch
sheeting, the top of the former should be covered with, a layer of
puddle, or plastered with a coat of best cement mortar (see § 141),
or painted with coal tar or asphaltum (see § 264).
732. For an illustration of the method of draining a series of
arches, and also of several minor details not mentioned above, see
Fig. 143, which represents " Little Juniata bridge No. 1J3 " on the
Pennsylvania KailroacL*
Published by permission of Wm, H. Brown, chief engineer.
RULES DERIVED FROM PRACTICE.
509
510 AKCHES. [CHAP. XYIIL
733. BBICK ARCHES. The only matter requiring special mention
in connection with, brick arches is the bond to be employed. "When
the thickness of the arch exceeds a brick and a half, the bond from
the soffit outward is a very important matter. There are three
principal methods employed in bonding brick arches. (1) The arch
may be built in concentric rings ; i. c., all the brick may be laid as
stretchers,, with only the tenacity of the mortar to unite the several
rings (see Fig. 144). This form of construction is frequently called
rowlock bond. (2) Part of the brick may be laid as stretchers and
part as headers, as in ordinary walls, by thickening the outer ends
of the joints — either by using more mortar or by driving in thin
pieces of slate, — so that there shall be the same number of bricks in
FIG-. 144. FIG. 145. FIG. 146.
each ring (see Fig. 145). This form of construction is known as header
and stretcher bond, or is described as being laid with continuous
radial joints. (3) Block in course loud is formed by dividing the
arch into sections similar in shape to the voussoirs of stone arches,
and laying the brick in each section with any desired bond, but
making the radial joints between the sections continuous from
intnulos to extrados. With this form of construction, it is custom-
ary to Liy one section in rowlock bond and the other with radial
joints continuous from intrados to extrados, the latter section being
much narrower than the former (see Fig. 146).
1. The objection to laying the arch in concentric rings is that,
since the rings act nearly or quite independent of each other, the
proportion of the load carried by each can not be determined. A
ring may be called upon to support considerably more than its proper
share of the load. This is by far the most common form of bonding
in brick arches, and that this difficulty does not more often mani-
ART. 2.] BULES DEKIVEJD FEOM PRACTICE. 511
fest itself is doubtless due to the very low unit working pressure
employed. The mean pressure on brick masonry arches ordinarily
varies from 20 to 40 pounds per square inch, under which condition
a single ring might carry the entire pressure (see Tables 19 and 20,
pages 164 and 166). The objection to this form of bond can be
partially removed by using the very best cement mortar between
the rings.
The advantages of the ring bond, particularly for tunnel
and sewer arches, are as follows : It gives 4-inch toothings for con-
necting with the succeeding section, while the others give only
2-inch toothings along much of the outline. It requires less
cement, is more rapidly laid, and is less liable to be poorly executed.
It possesses certain advantages in facilities for drainage, when laid
in the presence of water.
2. The objection to laying the arch with continuous radial joints
is that the outer ends of the joints, being thicker than the inner,
will yield more than the latter as the centers are removed, and
hence concentrate the pressure on the intrados. This objection
is not serious when this bond is employed in a narrow section
between two larger sections laid in rowlock courses (see Fig. 14(i).
3. When the brickwork is to be subject to a heavy pressure,
some form of the block in course bond should be employed. For
economy of labor, the ei blocks " of headers should be placed at such
a distance apart that between each pair of them there shall be one
more course of stretchers in the outer than in the inner ring ; but a
moment's consideration will show that this would make each section
about half as long as the radius of the arch, — which, of course,
is too long to be of any material benefit. Hence, this method
necessitates the use of thin bricks at the ends of the rings.
734. Examples of Brick Arches. The method of bonding shown
in Fig. 146 (page 510) is frequently employed — as, for example, in
the 70-foot brick arch of the Swatara bridge (Philadelphia and
Reading R. R.). The bonding employed in arching the Vosburg
tunnel (Lehigh Valley R. R.) is shown in Fig. 147 (page 512).*
735. Fig. 148 (page 513) shows the standard forms of large
brick sewers employed in the city of Philadelphia, f ** They are
*From Rosenberg's u The Voaburg Tunnel," by permission.
tR. Herinff, in Trans. Am. Soc. of C. E., vol. vii, pp. 252-57. The Illustrations
are reproduced from those in the original, the force diagrams being omitted here.
ARCHES.
[CHAP. XVIIL
designed for a maximum pressure on the brick-work of 80 pounds
per square inch/' which, considering the usual specifications for
such work (see § 260, p. 176), seems unnecessarily small (see Tables
19 and 20, pages 164 and 166).
Pig. 149 (page 514) shows the standard forms of sewers in
Washington, D. 0.* " The invert as shown is the theoretical form,
although the concrete is rammed into the trench and nearly always
extends beyond the limits shown." The largest sewers have a trap-
rock bottom ; the intermediate sizes have a semi-circular vitrified
FIG. 147.— -Bond and Center of Vosburg Tunnel.
pipe in the bottom ; and the smallest sizes consist of sewer pipes
bedded in concrete.
736, Owing to their great number of joints, brick arches are
liable to settle much more than stone ones, when the centers are re-
moved ; and hence are less suitable than the former for large or flat
arches. Nevertheless a number of brick arches of large span have
been built (see Table 63, page 502). Trautwine gives the following
description of some bold examples. " On the Filbert Street exten-
sion of the Pennsylvania R. E., in Philadelphia, are four brick arches
of 50 feet span, and with the very low rise of 7 feet. The arch rings
are 2£ feet thick, except on their showing faces, where they are but 2
feet. The joints are in common lime mortar, and are about £ inch
* Report of the Commissioners of tho District of Columbia, for the year ending
June 30, 1884, p. 175. For details of quantities of material required, and for esti-
mates of cost, see report for preceding year, pp. 277-79.
ART. 2.J
RULES DERIVED FROM PRACTICE.
513
514
ARCHES.
[CHAP. X
FIG. 149. —Standard Forms of Brick Sewers.— Washington, D, C.
ART. 3.] CENTERS. 515
thick. These four arches, about 200 yards apart, with a large num-
ber of others of 26 feet span,, form a viaduct. The piers between
the short spans are 4Jfeet thick, and those at the ends of the 50-foot
spans are 18 J feet. The road-bed is about 100 feet wide, giving room
for 9 or 10 tracks. The springing lines of all the arches are about
6 to 8 feet above the ground. One of the 50-foot arches settled 3
inches upon permanently striking the center • but no further settle-
ment has been observed, although the viaduct has, since built (1880),
had a very heavy freight and passenger traffic at from 10 to 20 miles
per hour/*
737. SPECIFICATIONS FOR STONE ARCHES. The specifications for
arch masonry employed on the Atchison, Topeka and Santa Fe
Railroad are as follows : *
738. First-Class Arch. Masonry shall be built in accordance with the speci-
fications for first-class masonry [see § 207], with the exception of the arch sheet-
ing and ring stones. The ring stones shall be dressed to such shape as the
engineer shall determine. The ring stones and the arch sheeting shall be not
less than ten inches (10") thick on the intrados, and shall have a depth equal
to the specified thickness of the arch. The joints shall be at right angles to
the intrados, and their thickness shall not exceed three eighths of an inch ($").
The face of the sheeting stones shall be dressed so as to make a close center-
ing joint. The ring stones and sheeting shall break joints not less than one
foot (!').
The wings shall be neatly stepped with selected stones of the full width of
the wing, and of not less than ten inches (10") in thickness, overlapping by
not less than one and one half feet (14-'); or they shall be finished with a neatly
capped newel at the end of each wing, and a coping course on the wing. The
parapets shall be finished with a coping course of not less than ten inches
(10'') in thickness, having a projection of six inches (6").
739. Second-Class Arch Masonry shall be the same as first-class masonry (see
§ 207). The stones of the arch sheeting shall be at least four inches (4") in thick-
ness on the intrados ; shall have a depth equal to the thickness of the arch ;
shall have good bearings throughout ; and shall be well bonded to each other
and to the ring stones.
74=0. SPECIFICATIONS FOR BRICK ARCHES. See §§ 260-61 (pages
176-77).
ART. 3. ARCH CENTERS.
741. A center is a temporary structure for supporting an arch
while in process of construction. It usually consists of a number of
frames (commonly called -ribs) placed a few feet apart in planes
* For general specifications for railroad masonry, see Appendix I.
516 , ARCHES. [CHAP. XYIII.
perpendicular to the axis of the arch, and covered with narrow
planks (called laggings) running parallel to the axis of the arch,
upon which the arch stones rest. The center is usually wood —
either a solid rib or a truss, — but is sometimes a curved rolled-iron
beam. In a trussed center, the pieces upon which the laggings rest
are called lack-pieces. The ends of the ribs may be supported
by timber struts which abut against large timbers laid upon the
ground, or they may rest upon a shoulder on the abutment.
The framing, setting up, and striking of the centers (§§ 752-55)
is a very important part of the construction of any arch, particularly
one of long span. A change in the shape of the center, due to
insufficient strength or improper bracing, will be followed by a
change in the curve of the intrados and consequently of the line of
resistance, which may endanger the safety of the arch itself.
742. LOAD TO BE SUPPOBTED. If there were no friction, the load
to be supported by the center could be computed exactly ; but fric-
tion between the several arch stones and between these and the
center renders all formulas for that purpose very uncertain.
Fortunately, the exact load upon the center is not required ; for the
center is only a temporary structure, and the material employed in
its construction is not entirely lost. Hence it is wise to assume
the loads to be greater than they really will be. Some allowance
must also be made for the accumulation of the material on the
center and for the effect of jarring during erection. The following
analysis of the problem will show roughly what the forces are and
why great accuracy is not possible.
To determine the pressure on the center, consider the voussoir
DEFG, Fig. 150, and let
a = the angle which the joint DE makes
with the horizontal ;
ja = the co-efficient of friction (see Table 36,
page 315), i. e., /* is the tangent of
the angle of repose ;
8 = the angular distance of any point from
the crown ;
W=z the weight of the voussoir DEFG ;
N = the radial pressure on the center due to
FIG' 150' the weight of DEFG.
If there were no friction, the stone DEFG would be supported
ART. 3.] CENTERS. 517
by the normal resistance of the surface DE and sthe radial reac-
tion of the center. The pressure on the surface DE would then
be W cos a, and the pressure in the direction of the radius W sin a.
Friction causes a slight indetermination, since part of the weight
of the voussoirs may pass to the abutment either through the arch
ring or through the back-pieces (perimeter) of the center. Owing
to friction, both of these surfaces will offer, in addition to the
above, a resistance equal to the product of the perpendicular pres-
sure and the co-efficient of friction (foot-note, page 276). If the
normal pressure on the joint DE is W cos <r, then the frictional
resistance is /* Hrcos a\ Any frictional resistance in the joint DE
will decrease the pressure on the center by that amount ; and conse-
quently, with friction on the joint DE, the radial pressure on the
center is
N = W (sin a — JJL cos a) ...... (49)
On the other hand, if there is friction between the arch stone and
the center, the frictional resistance between these surfaces will
decrease the pressure upon the joints DE, as computed above ; and
consequently the value of N will not be as in equation (49).
Notice that in passing from the springing toward the crown the
pressure of one arch stone on the other decreases. Near the crown
this decrease is rapid, and consequently the friction between the
voussoirs may be neglected. "Under this condition, the radial pres-
sure on the center is
(50)
As a rough approximation, equation (50) may be applied for
the first 30° from the crown, although it gives results slightly
greater than the real pressures ; and for the second 30°, equation
(49) may be employed, although it gives results less than the actual
pressure ; and for the third 30°, the arch stones may be considered
self-supporting.
743. The value of the co-efficient to be employed in equation
(49) is somewhat uncertain. Disregarding the adhesion of the
jnortar, the co-efficient varies from about 0.4 to 0.8 (see Table 36,
518 ARCHES. [CHAP. xvm.
page 315) ; and, including the adhesion of good cement mortar, it
may be nearly, or even more than, 1. (It is 1 if an arch stone
remains at rest, without other support, when placed upon another
one in such a position that the joint between them makes an angle
of 45° with the horizontal.) If the arch is small, and consequently
laid up before the mortar has time to harden, probably the smaller
value of the co-efficient should be used ; but if the arch is laid up
s@ slowly that the mortar has time to harden, a larger value could,
with equal safety, be employed. As a general average, we will
assume that the co-efficient is .58, L e., that the angle of repose
is 30°.
Notice that by equation (49) N = 0, if tan a = p ; that is to
say, N = 0, if OL = 30°. This shows that as the arch stones are
placed upon one another they would not begin to press upon the
center rib until the plane of the lower face of the top one reaches
an angle of 30° with the horizon.
Table 65 gives the value of the radial pressure of the several por-
tions of the arch upon the center ; and also shows the difference
between applying equation (49) and equation (50). Undoubtedly
the former should be applied when the angle of the lower face of
any arch stone with the horizontal does not differ greatly from 30°;
and when this angle is nearly 90°, then equation (50) should be ap-
plied. It is impossible to determine the point at which one equation
becomes inapplicable arid the other applicable ; but it is probably
safe to apply equation (49) up to 60° from the horizontal.
744. Example. To illustrate the method of using Table 65,
assume that it is required to find the pressure on a back-piece of a
20-foot semi-circular arch which extends from 30° to 60° from the
horizontal, the ribs being 5 feet apart, and the arch stones being 2
feet deep and weighing 150 pounds per cubic foot. Take the sum
of the decimals in the middle column of Table G5, which is 3.19.
This must be multiplied by the weight of the arch resting on 2° of the
center. (In this connection it is convenient to remember that an
arc of 1° is equal to 0.0175 times the radius.) The radius to the
middle of the voussoir is 11 feet, and the length of 2° of arc is 0.38
feet. The volume of 2° is 0.38x5x2 = 3.8 cubic feet; and the
weight of 2° is 3.8x150 = 570 pounds. Therefore the pressure
on the back-piece is 570x3.19 = 1,818 pounds.
ART. 3.]
CEOTEKS.
519
TABLE 65.
THE RADIAL PRESSURE OF THE ARCH STONES
OF A SEMI- ARCH, ON THE CENTER.
ANGLE OF THE LOWER
FACE WITH THE
HORIZONTAL.
RADIAL PRESSURE IN TERMS OF THE
WEIGHT OF THE ARCH STONE.
By Equation (49).
By Equation (50).
30°
0.00
32°
0.04
84°
0.08
36°
0.13
38°
0.16
40°
0.20
42°
0.24
0.67
44°
0.28
0.69
46°
0.32
0.72
48°
036
0.74
50°
0.40
0.76
55°
0.45
0.82
60°
0.54
0.86
65°
0.91
70°
. . «
0.94
80°
....
0.98
90°
1.00
745. OUTLINE EORMS or CENTEKS. Solid Wooden Bib. For
flat arches of 10-foot span or under, the rib may consist of a plank,
a, a, Pig. 151, 10 or 12 inches wide and !•£• or 2 inches thick, set
FIG. 151.
odgewise, and another, J, of the same thickness, trimmed to the
curve of the intrudes and placed above the first. The two should
be fastened together by nailing on two cleats of narrow boards as
.shown. These centers may be placed 3 or 3 feet apart.
520 ARCHES. [CHAR xvm.
746. Built Wooden Eib. For flat arches of 10 to 30 feet span,
the rib may consist of two or
three thicknesses of short
boards, fitted arid nailed (or
bolted) together as shown in
Fig. 152. An iron plate is.
often bolted on over the joints-
(see Fig. 147, page 512), which
adds materially to the rigidity
FIG-152' of the rib. Centers of this
form have an astonishing strength. Trau twine gives the two fol-
lowing examples which strikingly illustrate this.
In the first of these examples, this form of center was employed
for a semi-circular arch o.f 35 feet span, having arch stones 2 feet
deep. " Each rib consisted of two thicknesses of 2-inch plank, in
lengths of about 6.5 feet, treenailed together so as to break joint.
Each piece of plank was 12 inches deep at the middle, and 8 inches-
at each end, the top edge being cut to suit the curve of the arch. The
treenails were 1.25 inches in diameter, and 12 of them were used to
each length. These ribs were placed 17 inches apart from center to
center, and were steadied together by a bridging piece of 1-inch
board, 13 inches long, at each joint of the planks, or about 3.25 feet
apart. Headway for traffic • being necessary under the arch, there
were no chords to unite the opposite feet of the ribs. The ribs were
covered with close board-lagging, which also assisted in steadying
them together transversely. As the arch approached about two-
thirds of its height on each side, the ribs began to sink at the
haunches and rise at the crown. This was rectified by loading the
crown with stone to be used in completing the arch, which was then
finished without further trouble."
The other example was an elliptic arch of 60 feet span and 15-
feet rise, the arch stones being 3 feet deep at the crown and 4 feet
at the springing. "Each frame of the centre was a simple rib G
inches thick, composed of three thicknesses of 2-inch oak plank,.
in lengths (about 7 to 15 feet) to suit the curve and at the same-
time to preserve a width of about 16 inches at the middle of each
length and 12 inches at each of its ends. The segments broke-
joints, and were well treenailed together with from ten to sixteen
ART. 3.] CENTERS. 521
treenails to each length. There were no chords. These ribs were
placed 18 inches from center to center, and were steadied against
one another by a board bridging-piece, 1 foot long, at every 5 feet.
When the arch stones had approached to within about 12 feet of
each other, near the middle of the span, the sinking at the crown
and the rising at the haunches had become so alarming that pieces
of 12- X 12-inch oak were hastily inserted at intervals and well
wedged against the arch stones at their ends. The arch was then
finished in sections between these timbers, which were removed one
by one as the arch was completed."
Although the above examples can not be commended as good
construction — the flexibility of the ribs being so great as to endanger
the stability of the arch during erection and to break the adhesion
of the mortar, thus decreasing the strength of the finished arch, —
they are very instructive as showing the strength attainable by this
method.
747. The above form of center is frequently employed, partic-
ularly in tunnels, for spans of 20 to 30 feet, precautions being taken
to have the pieces break joints, to secure good bearings at the
pints, and to nail or bolt the several segments firmly together.
The centers for the 25-foot arch of the Musconetcong (N. J.) tun-
nel (Lehigti Valley R. R.) consisted of segments of 3-inch plank,
5 feet 8 inches long, 14 inches wide at the center, and 8 inches at
the ends, bolted together with four -J-inch and four 3-inch bolts
each, and 14- X 8-inch pieces of plate-iron over the joints. Where
the center was required to support the earth also, a three-ply rib
was employed; but in other positions two-ply ribs, spaced 4 to 5
feet apart, wore used. Centers of this form have successfully stood
very bad ground in the Musconetcong and other tunnels;* and
hence we may infer that they are at least sufficiently strong for any
ordinary arch of 30 feet span.
Although not necessary for stability, it is wise to connect the
feet of the rib by nailing a narrow board on each side, to prevent
the end of the rib from spreading outwards and pressing against the
masonry — thus interfering with the striking of the center, — and also
to prevent deformation in handling it.
* Drinker's Tunneling, p. 548.
522
ABCHES.
[CHAP. xvin.
748. Braced Wooden Rib. For semi-circular arches of 15 to 30
feet span, a construction similar to that shown in Fig. 147 (page 512)
may be employed. The segments should consist of two thicknesses
of 1- or 2-inch plank, according to span, from 8 to 12 inches wide
at the middle, according to the length of the segments. The hori-
zontal chord and the vertical tie may each he made of two thick-
nesses of the plank from which the segments are made.
For greater rigidity, the rib may be further braced by any of
the methods shown in outline in Figs. 153, 154, 155, or by obvious
FIG. 153.
FIG. 154.
FIG. 155.
modifications of them. The form to be adopted often depends upon
the passage-way required under the arch. Fig. 153 is supported by
a post under each end; in extreme cases, Fig. 154 may be supported
at the middle point also; and Fig. 155 may be supported at both
middle points as well as at the ends.
Since the arch masonry near the springing does not press upon
the center, it may be laid with a template before the center is set
up; and hence frequently the center of a semi-circular arch does
not extend down to the springing line. For examples, see Figs.
147 and 158 (page 512 and 524).
Center frames are put together on a temporary platform or the
floor of a large room, on which a full-size drawing of the rib is first
drawn.
749. Trussed Center. When the span is too great to employ
any of the centers described above, it becomes necessary to construct
trussed centers. It is not necessary here to discuss the principles
FIG, 156.
of trussing, or of finding the strains in the several pieces, or of
determining the sections, or of joining the several pieces, — all of
ART. 3.] CENTERS. 523
which, are fully described in treatises on roof and bridge construc-
tion. There is a very great variety of methods of constructing such
centers. Pigs. 156 and 157 show two common, simple, and efficient
general forms.
750. CAMBEE. Strictly, the center should be constructed with
a camber just equal to the amount it will yield when loaded with
the arch; but, since the load is indeterminate, it is impossible to
compute what this will be. Of course, the camber depends upon
the unit strain in the material of the center. The rule is frequently
given that the camber should be one four-hundredth of the radius;
but tins is too great for the excessively heavy centers ordinarily
used. It is probably better to build the centers true, and guard
against undue settling by giving the frames great stiffness; and
then if unexpected settling does take place, tighten the striking
wedges slightly.
The two sides of the arch should be carried up equally fast, to
prevent distortion of the center.
751. EXAMPLES OF ACTUAL CENTEKS. For an example of a
center employed in a tunnel, see Fig. 147 (page 512).
Pig. 158 (page 524) shows the center designed for the 60-foot
granite arches of the recently completed Washington bridge over
the Harlem Kiver, New York City.* The bridge is 80 feet wide,
and fifteen ribs were employed. Notice that the center does not
extend to the springing line of the arch ; the first fifteen feet of
the arch were laid by a template.
Fig. 159 f (page 525) shows the center employed in constructing
the Cabin John arch, which carries the "Washington (D. C.) aque-
duct over a creek, and which is the largest masonry arch in the
world (see No. 2, Tablo 63, page 502). The arch is 20 feet wide,
and five ribs were employed.
752. STKIKING THE CENTER, The Method. The ends of the ribs
or center-frames usually rest upon a timber lying parallel to, and
near, the springing line of the arch. This timber is supported by
wedges, preferably of hard wood, resting upon a second stick, which
is in turn supported by wooden posts — usually one under each end of
each rib. The wedges between the two timbers, as above, are used
* 'Published by perminaion of Win. R. Ilutton, chief engineer.
t Compiled from photographs taken during the progress of the work (1856-60), by
courtesy of Gen. M. U. MeigH, chief engineer.
524
AECHES.
[CHAP. xvin.
AET. 3
CENTERS.
525
ARCHES. [CHAP, xvin,
in removing the center after the arch is completed,, and are known
as striking wedges. They consist of a pair of folding wedges — 1 to
2 feet long, 6 inches wide, and having a slope of from 1 to 5 to 1 to
10 — placed under each end of each rib. It is necessary to remove
the centers slowly,, particularly for large arches ; and hence the
striking wedges should have a very slight taper,, — the larger the span
the smaller the taper.
The center is lowered by driving back the wedges. To lower
the center uniformly, the wedges must be driven back equally.
This is most easily accomplished by making a mark on the side of
each pair of wedges before commencing to drive, and then moving
each the same amount.
753. Instead of separate pairs of folding wedges, as above, a
compound wedge, Fig. 160, is sometimes employed. The pieces.
A ^___ ^ ^ L
/f
/f
c
-£--~^- - ^
FIG. 100.
A and B are termed striking plates. The ribs rest upon the former,
and the latter is supported by the wooden posts before referred to.
The wedge C is held in place during the construction of the arch
by the keys, K, K, etc., each of which is a pair of folding wedges.
To lower the center, the keys are knocked out and the wedge C is
driven back.
The piece C is usually as long as the arch, and supports one end
of all the ribs ; but with large arches, say SO to 100 feet span, it is
customary to support each rib on a compound wedge running
parallel to the chord of the center (perpendicular to the axis of the
arch). Instead of cutting the striking plates A and B as shown in
Fig. 160, the compound wedge may play between tapered blocks
gained into A and B. The piece C is usually made of an oak
stick 10 or 12 inches square. The individual wedges are from 4 to
6 feet long.
For the larger arches, the compound wedge is driven back
with a heavy log battering-ram suspended by ropes and swung
back and forth by hand. The inclined surfaces of the wedges
AKT. 3.] CESTTEBS. 527
should be lubricated when the center is set up, so as to facilitate
the striking.
754. An ingenious device,, first employed at the Pont d'Alma
arch — 141 feet span and 28 feet rise, — consisted in supporting the
center-frames by wooden pistons or plungers, the feet of which
rested on sand confined in plate-iron cylinders 1 foot in diameter
and about 1 foot high. Near the bottom of each cylinder there was
a plug which could be withdrawn and replaced at pleasure, by means
of which the outflow of the sand was regulated, and consequently
also the descent of the center. This method is particularly use-
ful for large arches, owing to the greater facility with which the
center can be lowered. See Fig. 158, page 524.
755. The Time. There is a great difference of opinion as to the
proper time for striking centers. Some hold that the center should
be struck as soon as the arch is completed and the spandrel filling
is in place ; while others contend that the mortar should be
given time to harden. It is probably best to slacken the centers as
soon as the .keystone is in place, so as to bring all the joints under
pressure. The length of time which should elapse before the centers
are finally removed should vary with the kind of mortar employed
(see Fig. 5, page 89) and also with its amount. In brick and rubble
arches a large proportion of the arch ring consists of mortar ; and
if the center is removed too soon, the compression of this mortar
might cause a serious or even dangerous deformation of the arch.
Hence the centers of such arches should remain until the mortar
has not only set, but has attained a considerable part of its ultimate
strength (see Fig. 5, page 89), — this depending somewhat upon the
maximum compression in the arch. It is probable that a knowledge
of the elasticity and of the "set" of mortar would give some light
as to the best time to strike centers ; but unfortunately our infor-
mation on those topics is very limited (see § 146).
Frequently the centers of bridge arches are not removed for
three or four months after the arch is completed ; but usually the
centers for the arches of tunnels, sewers, and culverts are removed
as soon as the arch is turned and, say, half of the spandrel filling is
in place.
APPENDIX I.
SPECIFICATIONS FOR MASONEY.*
CONTENTS.
General Railroad Masonry page 529
Masonry for Railroad Buildings l^ 534
Architectural Masonry " 539
Laying Masonry in Freezing Weather " 543
BAILROAD MASONRY, f
General Provisions. All stone used for the different classes of masonry
must be furnished from the best quarries in the vicinity, subject to the ap-
proval of the engineer. Brick masonry shall at all times be substituted for
stone, when so desired by the engineer.
Inspection. All materials will be subject to rigid inspection, and any that
have been condemned must be immediately removed from the site of the work.
The work will be done under the supervision of an inspector, whose duties
will be to see that the requirements of these specifications are carried out; but
his presence is in no way to be presumed to release in any degree the responsi-
bility or obligation of the contractor.
Laying Masonry. All classes of masonry laid in cement must be neatly
pointed with cement mortar, finely tempered. No masonry of any kind must
be covered until it has been inspected and accepted by the engineer. No ma-
sonry will be allowed to be laid in freezing weather. [Many specifications
omit this condition. See " Specifications for Laying Masonry in Freezing
Weather," page 543.]
Measurement of Masonry. All masonry and brick-work will be built ac-
cording to the plans and instructions furnished by the engineer, and will be
estimated and paid for by the cubic yard, computing only the actual solidity
thereof. No constructive or conventional measurement will be allowed, any
rule or custom in the section of the country through which the road passes to
the contrary notwithstanding. The price per cubic yard paid for masonry
and brick-work will include the furnishing of all material, scaffolding, cen-
tering, and all other expenses necessary to the construction and completion of
the masonry or brick-work. All "dressed" or "cut-stone" work—such as
copings, bridge-seats, cornices, belt-courses, water-tables, brackets, corbels,
etc. —furnished under the plans of the engineer will be paid for by the cubic
yard, under the classification of the masonry in which they occur, with an
additional price per square foot of the entire superficial surface of the stones
" dressed," or " cut," or " bush-hammered."
Allowance for Extras. No allowance will be made for timber, or work on
same, used in scaffolding, shoring, or centering for arches, — excepting only
timber, sheet-piling, or foundation plank, necessarily, and by order of the en-
gineer, left in the ground. No allowance will be made to the contractor for
* See also the specifications in the body of the bO"k. See " Specifications ' in Index.
t These specifications are the same, except in form, as those employed in the construction
of the " West Shore" Railroad, but do not differ materially from those used in other roads,
jiud have frequently heen accepted as the standard.
529
530 SPECIFICATIONS FOK MASONRY. [APP. I.
any damage lie may sustain by reason of floods or other causes; but suck
draining, bailing, or pumping from foundations as the engineer may decide to-
be necessary will be paid for at a price to be fixed by the engineer.
First-Class Masonry will consist of quarry-faced ashlar [see §§200-07]
laid in horizontal courses having parallel beds and vertical joints, of not less-
than ten inches (10"; nor more than thirty inches (30") in thickness, — decreas-
ing in thickness regularly from the bottom to the top of the wall, — laid flush
in cement mortar of the quality hereinafter specified. Each course must be
thoroughly grouted before the succeeding one is laid.
Size of Stones. StretcJwra must be not less than two and one half feet(2£')
nor more than six feet (6') in length, and not less than one and one half feet
(1-J-') in width, nor less in width than one and one half (1|) times their depth.
Headers must not be less than three and one half feet (3-t') nor more than four
and one half feet (4V) in length — where the thickness of the wall will admit
of the same,— and not less than one and one half feet (!$') in width, nor less-
in width than they are in depth of course.
Cutting. Every stone must be laid on its natural bed. All stones must
have their beds well dressed, parallel and true to the proper line, and made al-
ways as large as the stone will admit of. The beds and sides of the stone must
be cut, before being placed on the work, so as to form joints not exceeding one
half inch (£") in width. No hammering on a stone will be allowed after it is
set; but if any inequalities occur, they must be pointed oif. The vertical
joints of the face must be not less than eight inches (8") in from the face, and
as much more as the stone will admit of. All corners and batter lines must be
run with a neat chisel draft one and one half inches (!•£") on- each face. The
projections of the quarry face beyond the draft lines must not exceed four inches-
(4"); and in the side- walls of tunnels this projection must not exceed two
inches (2").
Bond. The masonry shall consist of headers and stretchers alternating. At
least one fourth of it shall consist of headers extending entirely through the
wall, and every header shall be immediately over a stretcher of the underlying
course. The stones of each course shall be so arranged as to form a proper
bond — in no case less than one foot (!') — with the stones of the underlying course.
Backing. The backing shall be of good-sized, well-shaped stones, laid so
as to break joints and thoroughly bond the work in all directions, and leave no-
spaces between them over six inches (6") in width, which spaces shall be filled
with small stones and spalls well grouted.
Coping. All bridge-seats and tops of walls will be finished with a coping
course of such dimensions and projections as may be ordered by the engineer,
dressed and cut to a true surface on top and front edges, in conformity with
diagrams for same which will be furnished by the engineer.
Foundation Courses. All foundation courses must be laid with selected
large flat stones, not less than twelve inches (12") thick, nor of less superficial
surface than fifteen (1 5) square feet.
Second-class Masonry [§§ 208-12] will consist of broken range rubble
of superior quality, laid with horizontal beds and vertical joints on the face,
with no stone less than eight inches (8") in thickness — unless otherwise directed
by the engineer, — well bonded, and leveled as well as can be without hammer-
dressing. No mortar joint shall exceed three quarters of an inch (£") in thick-
ness. All corners and quoins shall have hammer-dressed beds and joints; and
all corners and batter Hues shall be run with an inch-and-one-half (!£") chisel
draft. At least one fourth (i) of the stones in the face must be headers evenly
.distributed through the wall.
Bridge-seats arid tops of walls shall be coped in the same manner as specified
for first-class masonry. Stories in foundation courses shall be not less tban
twelve inches (12") thick, and shall contain not less than twelve (12) square-
feet of surface.
RAILROAD MASONRY. 531
Third-class Masonry will consist of good substantial rubble [§§ 213-17]
laid in cement mortar. All stones shall be perfectly sound, and sufficiently
large to make good, well-bonded, strong work; and shall be laid on their
natural beds, in the most substantial inanner, and with as much neatness as
this description of work admits of. The stones in the foundations must be not
less than ten inches (10") thick, and shall contain not less than teu (10) square
feet of surface; and each shall be firmly, solidly, and carefully laid.
First-class Arch-culvert Masonry shall be built in accordance
with the specifications for first-class masonry, with the exception of the arch
sheeting and the ring-stones. The rings shall be dressed to such size and
shape as the engineer shall direct. The ring-stones and sheeting-stones shall
not be of less thickness than ten inches (10") on the intraclos, and shall be
dressed with three eighths inch (£") joints, and shall he of the full depth speci-
fied (by drawings or otherwise) for the thickness of the arch. The joints must
be made on truly radial lines, and the face of the sheeting-stones must be
dressed to make close joints with the center. The ring-stone and sheeting-
stones shall break joints by not less than one foot (!').
The wing walls shall be neatly stepped, in accordance with the drawings
furnished, with selected stones of the full width of the wing and of not less
than ten inches (10") in thickness, no stone being covered less than eighteen
inches (18") by the one next above it; or the wing shall be finished with a
neatly capped newel at the end, and a coping course, — as may be selected by
the engineer. The parapet shall be finished with a coping course of full width
of parapet, with such projection as may be directed by the engineer, the stone
to be not less than ten inches (10") thick.
Second-class Arcli-culvert Masonry shall be of the same general
character and description as second-class masonry, with the exception of the
ring-stones and the arch sheeting. The former shall be dressed as specified
for first-class arch-culvert masonry. The latter shall consist of selected stones
of the full depth of the arch, and, shall have a good bearing throughout the
thickness of the arch, and shall be well bonded. No stone shall be less than
six inches (6") in thickness on the in trades.
Kox-cxilvert Masonry will be good rubble [see §§ 218-17], neatly laid
up with square-shaped stones of a size and quality satisfactory to the engineer.
The end parapet walls and also the side wnlls for three feet (3') from the ends
shall be laid in good cement mortar. When box culverts are ordered to be
laid up entirely in cement mortar [see § 214], they will be classified as third-
class masonry, and must conform to the specifications for the same.
The covering-stone for all box culverts shall be not less than ten inches
(10") in thickness, and must have a good, solid, well-leveled bearing on the
side walls of not less than fifteen inches (15").
Vitrified Pipe. In localities where but a small quantity of water passes,
vitrified pipe will be substituted for culverts when so ordered by the engineer.
Sizes of twelve (12"), fifteen (15"), or eighteen (18") inches in diameter may be
used, and must be of the best quality double strength, vitrified culvert pipe,
subject to the approval of the engineer. Vitrified pipes must be well and care-
fully bedded and laid [see Figs. 97-99, pages 409-10], in accordance with the
instructions of the engineer.
Retaining' Walls will be classified as second- or third-class masonry,
laid dry, as may be ordered in each particular case.
Slope Walls will be of such thickness and slope as directed by the en-
gineer. The stones must reach entirely through the wall, and be not less than
four inches (4") thick and twelve inches (12") long, kid with close joints, and
as free as possible from spalls. The foundations must be prepared and laid as
directed by the engineer.
Stone Paving shall be made by setting on edge stone from eight (8") to
532 SPECIFICATIONS FOR JIAS03TRY. [APP. I.
fifteen inches (15") in depth, laid either dry or grouted with strong cement
mortar, as may be directed by the engineer.
Riprap. When required by the engineer, the face of embankments and
the foot of slopes shall be protected from the action of water by a facing of
riprap stone, or of brush and stones, or by a retaining wall, as may be directed.
The riprap, when used, shall be laid by hand by competent workmen, and
shall be of such thickness and slope and of such undressed stone as the en-
gineer may direct
Brick Masonry. The brick must be of the best quality [see § 57],
well tempered, hard burned, and 8£ X 4 X 2£ inches.* ]STo bats, cracked,
crooked, or salmon bricks will under any circumstances be allowed in the
work. The brick shall be well soaked in water before being laid, and shall
be laid in hydraulic cement mortar of the quality hereafter specified, with
such thickness of joint and style of bond [§242 and §733] as shall be prescribed
by the engineer. Grout will be substituted for mortar when ordered by the
engineer.
Brick arching must be covered on the back with a coat of strong cement
mortar one inch (1") thick. In tunnel arching wherever a seam of water is
met, the arch must be covered with roofing felt; or with a course of asphaltum
(applied hot) of such thickness as may be directed by the engineer, and this
covered with a plastering of cement mortar so as to make the arch impervious
to water. A properly formed drainage channel shall be left in the backing of
the arch and side walls, with suitable openings for the escape of the water, at
such points and of such size as may be directed by the engineer. The keying
of all arches shall be most carefully done, and in such manner as may from
time to time be directed by the engineer. The packing between the arch and
tunnel roof shall never be put in until at least forty-eight (48) hours after the
section has been keyed.
Cement. The cement must be of the best quality of freshly ground hy-
draulic cement [of the Rosendale type — see § 72], and be equal in quality to the
best brands of ... ... cement. It will be subject to test by the engineer or his
appointed inspector, and must stand a tensile stress of fifty (oU) pounds per
square inch of sectional area on specimens allowed a set of thirty (30) minutes
in air and twenty-four (24) hours under water [see § 90, and art. 5 of Chapter
mi.
Mortar. The mortar shall in all cases be composed of one (1) part in bulk
of the above specified hydraulic cement to two (2) parts in bulk of clean,
sharp sand, well and thoroughly mixed together in a clean box of boards, be-
fore the addition of the water. It must be used immediately after being
mixed; and no mortar left over night, will, under any pretext, be allowed to
be used. The sand and cement used will at all times be subject to inspection,
test, and acceptance or rejection by the engineer.
Concrete. The concrete shall be composed of two (2) parts in bulk of
hard, sound, and acceptable stone — broken to a size that will pass in any direc-
tion through a two-inch (2") ring, thoroughly clean and free from mud, dust,
dirt, or any earthy admixture whatever, — and one (1) part of freshly-made
cement mortar of the quality above described. The concrete shall be qxiickly
laid in sections, in layers not exceeding nine (9) inches in thickness, and shall
be thoroughly rammed until the water flushes to the surface. It shall be al-
lowed at least twelve (12) hours to set before any work is laid on it.
Foundations. Excavations. Foundations for masonry shall be excavated
to such depths as may be necessary 10 secure a solid bearing for the masonry,
— of which the engineer shall be the judge. The materials excavated will be
* Instead of the dimensions as above, the specifications of which these are a revision and
also many others contain the term "standard size," but until recently that term could have
had no special significance (see § 62, page 46).
EAILBOAI) MASOXltY. 533
classified and paid for, as provided for in the Specifications for Grading. All
materials taken from the excavations for foundations, if of proper quality,
shall be deposited in the contiguous eimoankineut; and any material unfit for
such purpose shall be deposited outside the roadway, or ia such place as the
engineer shall direct, and so that it shall not interfere with any drain or water
course. In case of foundations in rock, the rock must be excavated to such
depth and in such form as may be required by the engineer, and must be
dressed level to receive the foundation course.
Artificial Foundations. When a safe and solid foundation for the masonry
can not be found at a reasonable depth (of which the engineer is to be the
judge), the contractor shall prepare such artificial foundations as the engineer
may direct.
Paving. Box culverts and small bridge abutments may have a paved foun-
dation, if so directed by the engineer, by setting stones on edge, breaking
joints, and extending across the entire width of the foundation.
Timber. Timber foundations shall be such as the engineer may by drawings
or otherwise prescribe, and will be paid for by the thousand feet, board meas-
ure,— the price to include the cost of material, framing, and putting in place.
All timber must be sound, straight-grained, and free from sap, loose or rotten
knots, wind shakes, or any other defect that would impair its strength, or
durability. It must be sawed (or hewed) perfectly straight and to exact
dimensions, with full corners and square edges. All framing must be done
in a thorough, workmanlike manner. Both material and workmanship will
be subject to the inspection and acceptance of the engineer.
Piling. All piles shall be of young, sound, and thrifty white oak, yellow
pine or other timber equally good for the purpose, acceptable to the engineer.
They must be at least eight inches (8") in diameter at the small end and twelve
inches (12") in diameter at the butt when sawn off; and must be perfectly
straight and be trimmed close, and have the bark stripped off before they are
driven. The piles must be driven into hard bottom until they do not move
more than one hulf inch (•£") under the blow of a hammer weighing two thou-
sand (3,000) pounds, falling twenty-five feet (25') at the last blow. They must
be driven vertically and at the distances apart, transversely and longitudinally,
required by the plans or directions of the engineer. They must be cut off
square at the butt and be well sharpened to a point; and when necessary, in
the opinion of ihe engineer, shall be shod with iron and the heads bound with
iron hoops of such dimensions as he may direct, — which will be paid for the
same as other iron-work used in foundations.
The necessary length of piles shall be ascertained by driving test piles in
different pnrts of the localities in which they are to be used. In case a single
pile shall not prove long enough to reach hard bottom, two shall be spliced
together as follows: The head shall be sawed off square, and a hole two inches
(2' ) in diameter and twelve inches (12") deep shall be bored into it; and into
this hole a circular white oak treenail twenty-three inches (23") IB length shall
be well driven. Then another pile similarly squared and bored, and of as
large a diameter at the small end as can be procured, shall be placed upon the
lower pile, brought to its proper position, and driven as before directed. All.
piles, when driven to the required depth, are to be cut off truly square and
horizontal at the height given by the engineer; and only the actual number of
lineal feet of the piles left for use in the foundations after being sawed off,
will be paid for.
Iron. All wrought and cast-iron work ordered by the engineer will be
paid for by the pound, — the price to include the cost of material, manufac-
ture., and placing in the work.
Coffer-dams. Where coffer-dams are, in the opinion of the engineer, re-
quired for foundations, the prices provided in the contract for timber, piles,
and iron in foundations, will be allowed for the material and work on same,
534 SPECIFICATIONS FOE MASOXBY. [APP. I.
which is understood as covering all risks from high water or otherwise, drain-
ing, bailing, pumping, and all materials connected with the coffer-darus.
Sheet-piling will be classed as plank in foundations; and if left in the ground
will be paid for by the thousand feet (1,000'), board measure.
KAILROAD BUILDINGS.*
Tools. All tools necessary for the execution of the contract, including
mortar boxes, will be furnished by the contractor at his own expense.
Staging'. All staging required for the execution of the work done under
contract shall be furnished by the contractor at his own expense. The rail-
way company will, however, upon the completion of any structure, purchase
of the contractor such staging material as it can advantageously use, and pay
the contractor for such material an amount which, in the opinion of the rail-
way company's engineer, shall seem reasonable and just.
JExcaviitious. Dry excavations, or excavations above water, will be
made by the contractor when so ordered by the railway company. Wet exca-
vations, or excavations below water, will be made by the railway company,
excepting when a special arrangement is made with the contractor. All exca-
vations will be classified as either earth, loose rock, or solid rock.
When the excavation for any structure is made entirely by the contractor,
it shall be measured in cubic yards, and paid for at the price per cubic yard
specified in the contract. When an excavation is made in part by the railway
company's force and is finished by the contractor's force, or when contractor's
force assists railway company's force in making any excavation, contractor will
be paid for the actual time that his force is employed, at laborer's current rate
per day plus ten per cent. In case contractor furnishes a foreman for such
work, time charged for foreman must not exceed one day for foreman for
each ten days of labor, and contractor will be paid for the services of such
foreman at a rate per day not to exceed the current wages paid foremen of
. laborers plus ten per cent. In case contractor uses masons, foremen of masons,
or other skilled labor for the execution of the above " extra" or ''time" work,
the wages and time allowed will be the same as it would be if the work had
been performed and supervised by laborers and foremen of laborers. When
"extra" or "time" work is performed by contractor's force, and is supervised
by contractor's foreman, who at the same time and place has charge of and
is supervising " contract " work, no pay will be allowed contractor for such
supervision, except when, in the opinion of the railway company's engineer,
it may seem reasonable and just.
All excavations shall be made strictly in accordance with the plans fur-
nished by the railway company and the stakes set by the railway company's
engineer, and shall be executed in a neat and workmanlike manner. Where
excavations are made under the supervision of the contractor, his agent or
foreman, any erroneous or unnecessary excavation, and any masonry conse-
quent to such erroneous or unnecessary excavation, shall be entirely at the
contractor's expense, unless the contractor can show that such unnecessary
work was caused by errors in the plans furnished by the railway company, or
by errors in the railway company's engineer's stakes or instructions.
When excavation is made for concrete, great care must be taken to make
the pits or trenches, as the case may be, of the exact width and depth required
for the concrete, and any unnecessary excavation made or concrete used on
account of lack of such care on the part of the contractor will be at his ex-
pense. Excavations for stone footing courses will be made, when not oiher-
* Atchison, Topeka and Santa F6 Railroad.
RAILROAD BUILDINGS. 535
wise ordered, eight inches (8") (four inches (4") on each side) wider than the
footing course. Excavations for walls not having footing courses will be
made, when not otherwise ordered, twelve inches (12") (six inches (6") on
«ach side) wider than the wall is thick.
Before masonry is built, excavations must be cleared of all loose earth
mud, or other objectionable material.
Stone. Stone will be furnished by the contractor at his own expense, and
toe of a quality suitable for the different classes of masonry hereinafter speci-
fied, and be subject to the inspection and acceptance of the railway company's
engineer. Stone will be loaded on cars and unloaded by the contractor at his
own expense. Stone will be delivered by the railway company on the nearest
available side track to the work, and no charges whatsoever will be allowed
•contractor for hauling- stone from cars to the work, except in extreme cases,
-where, in the opinion of the railway company's engineer, such charges may
appear reasonable and just.
Sand. All sand for mortar or concrete will be furnished by the contractor
at his own expense. When, in the opinion of the railway company's engineer,
sand can not be secured by contractor within reasonable distance by wagon
haul and at a reasonable price, transportation by rail will be furnished by the
railway company, it being optional with the railway company at what point
sand shall be procured. When railway company furnishes transportation for
;sand, cars shall be loaded and unloaded by contractor at his own expense.
All sand furnished by contractor shall be clean and sharp, and subject to
the inspection of, and rejection by, the railway company's engineer. When,
in the opinion of the railway company's engineer, sand requires screening, it
shall be screened by the contractor at his own expense.
Cement and Lime. All cement and lime will be furnished by the
railwa}r company at its own expense; and will be delivered on cars on the
nearest available side track to the work. It shall be unloaded by the con-
tractor at his own expense, and shall be piled up in such manner by him as the
railway company's engineer may direct. Cement and lime shall be covered
and protected from the weather by the contractor at his own expense, in such
manner as seems suitable to the railway company's engineer; and the con-
tractor will be held responsible for the value of any cement damaged on ac-
count of unsuitable protection.
Water. Water required for all work done under contract shall be fur-
nished by the contractor at his own expense. No charges made by contractor
for hauling water will be allowed. When, in the opinion of the railway com-
pany's engineer, water can not be procured by the contractor within reason-
able wagon haul, or at a reasonable expense, it will be furnished by the rail-
way company.
Mortar. Except when otherwise ordered, all mortar shall be thoroughly
mixed in a box, in the following proportions: One (1) part cement, two (2)
parts sand, with sufficient water to render the mixture of the proper consist-
ency. Care must be taken to thoroughly mix the sand and cement dry, in the
proportions specified, before the introduction of water into the mixture. Mor-
tar shall not be mixed except as it is used, and no mortar must be allowed to
stand over night in mortar boxes or elsewhere.
Concrete. All concrete shall consist of one (1) part cement, two (2) parts
sand, and six (6) parts broken stone, together with sufficient water to mix the
sand and cement to the consistency of good mortar for masonry. The pro-
portion of sand, cement, broken stone, and the quantity of water used in the
mixture, may be varied at the option of the railway compapy's engineer.
Stone shall be of a quality acceptable to the railway company's engineer,
and be broken so that seventy-five (75) per cent, will pass through a two-inch
{2") ring and so that all will pass through a two and one half inch (2J")
ring. Broken stone shall be free from mud, dirt, and other objectionable
536 SPECIFICATIONS FOR MASONRY. [APP. I,
material, and shall be subject to the inspection of, and rejection by, the rail-
way company's engineer.
The sand and cement must be thoroughly mixed dry, in a clean, tight
mortar box, before the introduction of water; and after water is applied to the
mixture, the whole must be worked over with hoes until a good mortar of
proper consistency is secured. After the mortar is made, the broken stone
must be thoroughly drenched with clean water, and then shall be added to
the mixture in the proportion stated above — or in any other proportion which
the railway company's engineer may specify. The concrete must then be
worked over and mixed until each stone is completely covered with mortar
and all spaces between the stones entirely filled with same.
The concrete shall be deposited in horizontal layers not exceeding twelve
inches (12 ') in depth, and shall be thoroughly tamped when so required by the
railway company's engineer.
Bubble Masonry. Rubble masonry will be classified as either heavy
rubble, foundation, rubble, pier rubble, or uncoursed hammer-squared rubble.
The latter will be called for convenience squared rubble [see g§ 2U8-12].
Heavy Rabble. When not otherwise speciiied or shown on the plans, foot-
ing courses will be built of rubble masonry. When footing courses exceed
thfrty inches (80'') in width, the masonry will be classified as heavy rubble;
and when thirty inches (30") or less in width, the masonry will be classified as-
foundation rubble..
Heavy rubble footing courses shall be built of well-selected stone, which
shall have a thickness not less than the height of the footing course. Each
stone shall have a bottom bed of good surface over its entire area, which shall
be horizontal when the stone is in position. As much of the upper surface of
each stone as will be directly under the masonry to be put above the fooling
course shall be uniform and parallel to the bottom bed. At least one third (J-)
of the length of the footing course shall be built of through-stone, and 'a
larger proportion shall be furnished by the contractor when, in the opinion
of the railway company's engineer, more through-stone are required to secure
stability. No stone shall be used which will not bond or extend under the
masonry to be built above the footing course a distance equal to at least, one
third (J-) the thickness or width of the masonry; and not more than two stones-
shall be used at any section to make up the total width of the footing course,
and the exposed face of each stone shall be at least twelve inches (12") in length.
All stones must be roughly jointed with a hammer for a distance back
from their faces equal to the projection or offset of the footing course. No
spaces to exceed forty (40) square inches in area shall be filled with spalls or
chips, and the total area of all spaces must not exceed five (5) per cent, of the
area of the footing cou use-
All stone when placed in position must be thoroughly rammed until firmly
embedded in a bed of mortar, which shall first be placed in bottom of excava-
tion or trench, and after stone are placed in position, all joints must bo well
grouted with mortar. When so required by the railway company's engineer,
footing courses shall be built exactly to the dimensions shown on drawings or
specifications, or with their edges built, to a line.
Foundation Rubble. In general, and when not otherwise specified, all masonry
below the bottom of water table or below the top of rail for stone, buildings,
and all masonry below the sill of wooden buildings, will be classified as foun-
dation rubble, except, footing courses more than thirty inches (SO") in width,
which will be classified as heavy rubble. Foundation rubble may be required,
however, for any portion or for all the masonry in any structure, in which
case no additional price shall be allowed, except when, in the opinion of the
railway company's engineer, it shall seem reasonable and just.
In this class of masonry no stone having an exposed face shall be less
than one twenty-fourth (^.f) of a foot in cubical contents nor less than two-
inches (2") thick. Any stone smaller than this will be considered a spall j,
RAILROAD BUILDINGS. 537
and spalls are not to be used to exceed seven (7) per cent, of the entire mass.
The contractor will not be required to furnish stone (except for through-
stone) larger than one and one half feet (!£') in cubical contents, but the stone
used shall not average less than one half (|) of a cubical foot in contents. No-
stone shall be used which does not bond, or extend into the wall, at least six
inches (6"). One through-stone, whose face area shall not be less than one
half (J) of a superficial foot, will he required for each sixteen (16) superficial
feet of face measurement of wall, and more than this may be required by the
railway company when, in the opinion of its engineer, a larger proportion of
through-stone is required to secure stability; provided, however, that the con-
tractor shall in no case he required to furnish through-stone to exceed ten (10)
per cent, of the entire mass. At least twenty (20) per cent, of the entire ma-
sonry shall consist of headers, or bond stones. Jn walls twenty-four inches-
(24'') thick or less, these headers shall be at least two thirds (f) the thickness of
the wall in length; and iu walls more than twenty-four inches (24") thick, they
shall be of sufficient length and be so placed as, in the opinion of the railway
company's engineer, seems necessary to secure well-bonded and stable work.
Each stone shall be laid in its quarry bed, and any stone set on edge, or
with the planes of its stratification vertical, will be rejected and ordered re-
moved at the expense of the contractor. Stones shall be firmly bedded in
mortar, and all spaces and joints thoroughly grouted with same.
Pier Rubble. Piers or pedestals whose horizontal sectional area is nine (9)
square feet or less will be classified as pier rubble. When this area exceeds
nine (9) square feet, the masonry will be classed as foundation rubble. Foot-
ing courses for such piers, when not exceeding sixteen (16) square feet in area,
will be classed as pier rubble; and when exceeding this area, they will be
classified as heavy rubble.
Footing courses must be built, so far as practicable, in accordance with the
preceding specifications for heavy rubble masonry. Masonry in piers above
footing courses must be carefully built of well-selected stone, having horizon-
tal beds and vertical joints, and be thoroughly bonded; corners and faces
must be built true and plumb. The specifications for foundation rubble, so
far as practicable, shall apply to this class of masonry.
Each pier or pedestal shall be furnished with a hammer-dressed cap-stone
not less than six inches (6") thick, of same area as pier, which must be accu-
rately set at the required level. The price of this cap-stone must be included
in the contract price per cubic yard for this class of masonry.
Squared Rubble. When not otherwise specified, the walls of all stone build-
ings above the bottom of the water-table will be built of uncoursed squared
rubble.
In general the specifications for foundation rubble will apply to this class
of masonry, the difference between the two classes being in the construction
and finish of the outside face. The outside face of the wall will be built of
well-selected stones, as nearly uniform in color as possible, which shall be
neatly squared to rectangular faces, and which in all cases shall be laid on
their natural or quarry beds. The beds of the stones shall be horizontal and
the side joints verticaCand no joints to exceed three fourths (£) of an inch will
be allowed. No stone having a face area of less than eighteen (18) square
inches or a thickness less than three inches (3") shall be used; and the average
face of all the stones shall not be less than seventy-two (72) square inches.
The inside face shall be built and finished in accordance with the specifica-
tions for foundation rubble.
Corners of all buildings shall be built up with quoin stones, uniform in size
and arrangement, for which no extra pay will be allowed contractor. Drafts
will be cut on the corners when so specified or shown on plans. All joints
shall be cleaned or raked out for a distance of three quarters of an inch (f "),
and neatly pointed with a raised joint. The mortar used for pointing shall be
composed of such material as the railway company's engineer may select.
538 SPECIFICATIONS FOB MASONRY. [APP. I.
Openings for windows, doors, or for other purposes, will be made in walls
when specified or shown on plans. The jambs of such openings shall be
neatly cut to a true and smooth surface, and be drove tooled, craudalled, or
tooth-axed [see pages 125-34, particularly 126 and 133], as may be required
by the railway company's engineer. Bed-joints of jamb-stones must be care-
fully cut, so that no joint to exceed one half an inch (•£") will appear on the
exposed face of the jambs. Jamb-stones shall be uniform in height, and one
half shall be through-stones. In general the arrangement of jamb-stones will
be shown on drawings.
The contract price for any opening shall include the cost of cut-stone sills,
lintels, arches, jarnb-stoues, or any other cut-stone work required for that
opening. In case no contract pjice is made for any opening, the contractor
will be paid such price as, in the opinion of the railway company's engineer,
seems reasonable and just.
Cut stone shall be furnished and put in place by the contractor when so re-
quired by the railway company. The stone furnished shall be of the quality
required for the work, and acceptable to the railway company's engineer; and
must be cut strictly in accordance with the plans and specifications in each
case, and must be so cut as to lie, when in position, on natural or quarry beds.
Cut stone will be paid for at the price specified in contract, and in case cut
stone is furnished by the contractor for which there is no contract price, a
price will be paid which, in the opinion of the railway company's engineer,
seems reasonable and just.
Cut stone, or dimension stone for cut-stone work, may be furnished by the
railway company at its own expense, and the contractor required to set the cut
stone in position, or to cut, and set the rough dimension stone, in which case the
contractor will be paid for the work either as "extra" or "time" work, or at
a price which, in the opinion of the railway company's engineer, may seem
reasonable and just.
Wall Masonry. All walls shall be built to a line both inside and out-
side, and both faces shall be finished with a smooth and uniform surface,
which shall be flat-pointed with a trowel, in a neat and workmanlike manner.
The upper courses of all walls, when leveled or finished for the reception of
superstructure, shall be provided with a through-stone at each end, and also
one through-stone for at least each five (5) lineal feet of wall. These through-
stone shall be dressed on their top beds and accurately set to a lovel one half
inch (£") below the level of the bottom of the superstructure. Between these
through-stone the walls must be carefully laid, with the upper beds of the
stones brought up flush with the top of the above-described through-stones so
as to secure a perfectly level surface for the top of the wall. In no case shall
spalls or chips be used, except in vertical joints.
The contractor will make such openings in walls as are required for
windows, doors, or other purposes. No additional pay will be allowed for
such openings, except where juinbs are to be cut, and cut-stone sills or lintels
are required, in which case such price per opening will be allowed as, in the
opinion of the railway company's engineer, may seern reasonable and just. Cut
or dressed dimension-stone will be furnished and set in position when so re-
quired by plans or specifications, and will be paid for by the railway company
at such price as may, in the opinion of its engineer, seem reasonable and just.
Wood, iron, or other material which may be required to be built into the ma-
sonry shall be properly put into position by the contractor, and no extra pay
shall be allowed for such work. The cubical contents of such material, how-
ever, will not be deducted from the measurement of the masonry.
When so required, the contractor shall plaster the outside surface of base-
ment or other walls with hydraulic mortar, composed of such materials as the
railway company may select, and tor such work the railway company will pay
the contractor a price per square yard in addition to the contract price ol the
masonry.
ARCHITECTURAL MASONRY. 539
Foundations for Trestles. Foundations for trestle bents, such as are
built for coal chutes, will be classified as foundation rubble, and must be built
with great care. The lower footing course, when exceeding thirty inches (30")
in width, will be classed as heavy rubble. The upper course shall have one
hammer-dressed, through-stone at each end of wall, and at least three such
through-stones between the end through-stones; otherwise the top course will
be finished in accordance with the second paragraph \mder "wall masonry"
above. This does not apply to bent foundations inside of coal-chute build-
ing, which will be built iu the same manner as foundation walls in general.
Well- wall Masonry. Well-walls will be classified as foundation rubble.
Well masonry will be built under the supervision of the well foreman who has
charge of the well excavation, and contractor's foreman shall execute the work
strictly in accordance with instructions given by him. When well- walls are
sunk, or settled, as the excavation is made great care must be taken to make
the outside surface perfectly smooth and uniform; and as many headers, not
to exceed the maximum heretofore specified, may be required as, in the opin-
ion of the railway company's engineer or well foreman, are necessary to
secure stability.
Measurement of Masonry. In measuring masonry paid for by the
cubic yard, all openings will be deducted, and the number of cubic yards
will be the actual cubical contents of the masonry built. The cubical contents
of cut stone, iron work, timber or other material, built into the masonry by the
contractor, will not be deducted from the cubical contents of the whole mass.
ARCHITECTURAL MASOKRY.* .
Permit. The contractor for the masonry shall take out a building per-
mit, including water for himself and plasterer and all other contractors that
may require water about the building during the progress of the work. This
contractor shall also take out street, and obstruction permit, and permit for
building curb and retaining walls. The cost of the above permits is to be in-
cluded in the estimate.
Grade. The inside grade at the building shall be such as the superintend-
ent shall direct. At the time of starting any pier, this contractor shall ascer-
tain from the superintendent the height the inside grade shall be set above the
established outside grade, taking into consideration the settlement that may
occur during the progress of the work.
Kxcavation. It is the intention that this contractor shall call at the
building and examine for himself the exact situation of the building site. He
shall remove from the premises all earth or debris, except that which the super-
intendent may consider good for use in the grading required about the build-
ing. This contractor shall complete such grading about the building as may
be found necessary. All sidewalk stone that may be found in connection with
the excavation shall be removed by the mason, the said stone becoming his
property. The same shall apply to any foundation stone or other material
that may be found in excavating, although none of said material shall be used
in connection with the new work about the building.
This contractor shall excavate, according to drawings, for all walls, piers,
areas, etc., the intention being that the general level shall be excavated simply
to the level of the finished basement floor. All trenches shall be excavated to
the neat size as near as practicable; and each shall be leveled to a line on the bot-
tom, ready to receive the foundation. At such time as the superintendent shall
* Except in form, these specifications are those employed by Burnham & Boot, archi-
tects, Chicago, for the Society of Savings Building, Cleveland, Ohio, and conform closely to
the general form employed by these architects.
540 SPECIFICATIONS FOB MASONRY. [APP. I,
direct, this contractor shall level off the basement surfaces and floors of areas
to a line finishing three inches (3") below the top of the level of the finished
basement floors, and leave the surface ready to receive the work of other con-
tractors. When considered necessary in the judgment of the superintendent,
all earth shall be tamped solidly and then be wet.
If any pockets of quicksand are found, this contractor shall excavate the
same, and till in solidly with concrete composed of clean broken stone of a size
that will pass through a two-inch (2") ring and English Portland cement, pro-
portioned 1 to 3, rammed solidly into place in the pockets, in layers, as the.
superintendent may direct. None of the sand that may be found while ex-
cavating shall be used in connection with any of the work about the building.
After all foundations or retaining walls are in and fixed, this contractor
shall tamp the earth solidly around them, leaving it level to a line within
eighteen inches (18") of the finished grade, and ready to receive the work of
other coutractc rs.
Bailing'. This contractor shall do all bailing and draining of trenches or
"basement surfaces that may be found necessary during the progress of the work.
Shoring1. This contractor shall protect all walls of the adjoining buildings,
underpin all walls that may be considered necessary — in the judgment of the
superintendent — to place the new work or to prevent injury of the old work,
make good all repairs, provide such cutting as may be found necessary to-
place the work, and leave the adjoining buildings as good as at the start. The
cost of this work is to be included in his estimate. This contractor shall
furnish and put in place any sheet piling that may be required to retain the
earth while the footings are being put in, and include all costs of the same ia
his estimates.
Protection. This contractor shall use proper care and diligence in brac-
ing and securing all parts of the work against storm, wind, and the action of
frost. Every night during freezing weather, each pier or wall shall be covered
on top with sail-cloth, and the covering shall extend down over the face of all
green work.
Concrete Footings. This contractor shall provide a frame of the area
of the pier, composed of two-inch (2") plank, so arranged that the parts can be
withdrawn and the pier left isolated after the concrete is set [see § 300]. All
footings not otherwise indicated shall be constructed of concrete furnished by
this contractor. The cement shall be first-quality, fresh Utica, or any other
equally good quality approved by the architects. The contractor at the time
of submitting his proposal shall state the kind of cement he intends using.
The sand shall be clean and sharp. The stone shall be clean limestone, crushed
to a size that will pass through a two-inch (2") ring, and screened. The con-
crete shall be composed of these ingredients in the following proportions: one
(1) part of hydraulic cement, one (1) part of sand, and two (2) parts of crushed
limestone. The cement and sand shall be mixed dry, and the mixture wet
with a quantity of water sufficient to reduce it to the consistency of mortar.
The stone and mortar shall be thoroughly mixed and laid in trenches as soon
as possible, in layers of not more than six inches (6") in thickness, and be
rammed until the water rises freely to the top.
All concrete, footings shall be carefully leveled or pitched with concrete,
and be left ready to receive the piers, walls, or columns, in each case as par-
ticularly- indicated on the drawings.
Railroad-Kail Footings. All railroad rails that may be required in
connection with the foundations shall be of Bessemer steel, weighing not less
than sixty- live (65) pounds per yard, straight and sound, cut to the neat lengths
indicated on the drawings. AH railroad rails shall be furnished by this con-
tractor, and by him set in place to centers and levels as indicated on the dia-
grams. None of these railroad rails are to be painted.
The concrete used in connection with steel-rail footings shall be composed
AKCHITECTUKAL MASONRY. 541
of one (1) part of first-quality English Portland cement—or any other equally
good quality approved by the architects, —one (1) part of clean sharp sand, and
two (2) parts of clean limestone crushed to chestnut size. This concrete shall
be mixed as for concrete footings, and shall be rammed in solidly between the
rails; and each tier shall be neatly squared at the outer edge.
Rubble Masonry- All piers colored blue on the drawings shall be
•classed as cut stone, and shall be furnished and set in place by another con
tractor; but all walls colored blue on the drawings — referring particularly to
foundation walls for boiler-house, foundation wall for staircase way in alley,
area walls, curb walls, and curtain walls between piers —shall be classed as rub-
ble masonry, and shall be furnished and set in place by the mason.
All stone used in connection with rabble masonry shall be of selected, large
size, first- quality stone, laid to the lines on both sides, well fitted together and
thoroughly pointed, frequent headers that extend through the wall being pro-
Tided. All stone shall be not less than two feet six inches (2' 6") long, one foot
.six inches (!' 6") wide, and eight inches (8") thick, except such as may be found
necessary to level up a course to the required height. The intention is that all
walls shall be laid in courses about one foot six inches (!' 6") in height,
leveled off at each course. Each stone shall have hammer-dressed beds and
joints, and shall be firmly bedded and be well cushioned into place. All
joints shall be filled with mortar. The facing of all walls shall be laid ran-
dom range, and the face of the stone shall be coarse bush-hamrne-red.
At the time of completing the retaining walls, this contractor shall excavate
at least one foot (!') on the outside of the wall, and point up all joints on the
outside; and then provide and apply a coat of first-quality English Portland
•cement, not less than a half inch (£") thick, to the outside of the wall from top
to bottom. No cement covering will be required on the curb walls. All joints
showing inside the building shall be raked out and neatly pointed up with
•cement; and, in addition, the face of walls coming in connection with the area
shall be squared up. the joints finishing not to exceed one half inch (£") thick.
All curb walls that may be required to receive the side-walks shall be
brought to such levels as the superintendent shall direct, and shall be cemented
on top and left ready to receive the side-walks — which shall be furnished and
set by another contractor. None of the screen walls shall be set in place until
such time as the superintendent shall direct. The foundation for the staircase
bay in the alley shall be set in place, after the building is partly completed, at
such time as the superintendent may direct. This contractor, at the time of
starting this work, shall furnish such anchors as may be considered neces-
sary, in the judgment of the superintendent, to attach his work to that
already in place, and shall do all cutting and fitting that maybe found neces-
sary to properly place his work.
Mortar for Rubble Masonry. All rubble masonry above referred to shall
be laid in mortar composed of perfectly fresh Utica cement—or other equally
as good approved by the architects, — mixed in the proportion of one (1) part
of cement to two (2) parts of clean sharp coarse sand. The sand and cement
shall be mixed in a box dry; then wet, tempered, and immediately used.
Common Brick- work. All walls or sections colored red on the draw-
ings or otherwise indicated to be of brick, shall be of selected, first-quality,
hard-burned Chicago sewer brick — or other equally good quality approved' by
the architects. The above quality of brick shall be used throughout the entire
work, except that hollow fire-clay brick shall be used in connection with all
•curtains between windows on elevations above the first story, and for the back-
ing of all stone-work above the top of the eighth-story floor-beams. No bats
shall be used. No pressed or face brick will be required in connection with
this work.
All brick shall be well wet, except in freezing weather, before being laid.
Each brick shall be laid with a shove joint, in a full bed of mortar, all inter-
542 SPECIFICATIONS FOR MASONRY. [APP. I.
stices being thoroughly filled; and where the brick comes in connection with
anchors, each one shall be "brought home" to do all the work possible. Up
to and including the fifth story, every fourth course shall consist of a heading
course of whole brick extending through the entire thickness of the walls-
above the fifth story, every sixth course shall be a heading course. All mor-
tar joints shall be neatly struck, as is customary for " first-class trowel work."
All courses of brick- work shall be kept level, and the bonds shall be accurately-
preserved. "When necessary to bring any course to the required height, clip-
ped courses shall be formed, as in no case shall any mortar joints finish more
than one half inch (£") thick. All brick- work shall be laid to the lines, and
each tier kept plumb, the intention being that none of the window-frames shall
be set in place until the roof is on.
All lintels over openings indicated in connection with brick partition walls
in basement shall be of steel railroad rails, and shall be furnished and set in
place by the mason. These rails shall be painted one coat of mineral paint be-
fore being brought to the building.
All cut stone shall be backed as fast as the superintendent may consider
proper, and the mason shall build in all anchors that may be furnished by the
contractor for the cut stone. When openings or slots are indicated in connec-
tion with walls, the size and position of the same shall be such as the superin-
tendent shall direct, unless otherwise shown. This contractor shall leave
openings to receive all registers that may be required in connection with the
heating or ventilating system, and shall also leave openings in connection with
the corner vaults at such places in the floor and ceiling as the superintendent
shall direct.
All masonry that may be required at the time of setting the boilers shall be
furnished and set in place by the contractor for steam-heating apparatus.
Mortar for Brick-work. All mortar used in connection with sewer brick,
together with the mortar in the brick parapet walls and the chimney above
the roof line, shall be composed of two (2) parts of lime mortar-- made up very
poor, — and one (1) part of first-quality Utica cement — or other equally good
approved by the architects. Said mortar shall be used immediately after being
mixed, and in no case shall any be used that has stood over night.
The remaining brick-work, including the fire-brick hereinafter referred to,
shall be laid in mortar composed of best slaked lime and coarse sharp clean
sand of approved quality.
Brick Arches. Where arches are indicated in connection with the first-
story banking1 vault or in connection with roadway in the court on the north
front of building, said arches shall be formed with common brick laid in row-
lock courses, regularly bonded [see § 733]. The mortar for this work shall con-
sist of one (1) part Portland cement and three (3) parts clean sharp sand. Each
brick shall be laid with a shove joint; and each rowlock course shall be
cemented on top at the time of laying the next course. The last course shall
be cemented on top, and be left ready to receive the concrete floor or roadway
— which shall be provided by another contractor.
All centers that may be required in connection with this work shall be
furnished and set in place by the carpenter; and none of said centers shall be
removed until such lime as the superintendent shall direct. After the same
have been removed, this contractor shall thoroughly clean down all face-work.
All iron indicated in connection with this work shall be furnished and set
in place by the contractor for constructional iron work, —except the bearing
plates, which shall be bedded by the mason.
Smoke KritcMiigf. The smoke britching indicated in connection with
the main boiler-stack will be furnished and set in place by the contractor for
constructional iron, although the mason shall back up the same at such time
as the superintendent shall direct.
JFire-brick. The lining shown to stand alone in connection with the
ARCHITECTURAL MASONRY. 543
boiler cnimney in the lower stories shall be kid with first-quality fire-clay
brick, laid in stretcher courses, regularly bonded, with headers of whole brick
sixtee'n inches (16") apart in every sixth course to stay the linings, care being
taken to preserve the air-space indicated.
All fire-clay brick shall be laid in first-class fire-clay mortar, each brick
bein°- laid with a solid joint neatly struck on each side with a trowel.
llollow Fire-clay JBrick. All brick used in connection with the
spandrels above the first story on all elevations, together with all backing re-
quired in connection with the stone work above the top of the eighth-story floor-
beams, shall consist of first-quality, bard-burned, tire-clay, hollow brick, equal
in quality to sample to be seen at the ofiiceof the architects. Each brick shall
be laid with a shove joint. This contractor shall point up this work, and
leave the surfaces of the walls smooth and ready to receive plastering.
Cutting and Fitting:. This contractor shall do, promptly and at the
time the superintendent so directs, all cutting and fitting that may be required
in connection with the mason- work by other contractors to make their work
come right, and shall make good after them.
Setting' Iron-work. It is the intention that all constructional iron-
work shall be furnished and set in place by an other contractor, and that all iron
shall be hoisted from the outside of the building by means of a derrick. In
setting the beams and columns in place, the mason shall keep pace with the
contractor for constructional iron work, and at no time shall the mason be left
one story behind the constructional iron-work. Each beam, girder, or column
shown to rest on the masonry shall be provided with iron plates by the con-
tractor for constructional iron, said plates being furnished to the mason at the
sidewalk; and the mason shall set the same in place, firmly bedded in mortar,
at such position or height as the superintendent shall direct.
All iron wall-plates that may be required to receive the fire-clay arches
will be furnished at the sidewalk by the constructional-iron contractor; and
this contractor shall set each in such position and at such height as the super-
intendent shall direct.
Cut Stone. All parts colored blue on the drawings, or otherwise indi-
cated to be of stone, or usually classed as cut stone, shairbe furnished and set
in place by the contractor for cut stone. The same shall apply for the terra-
cotta roof-copings indicated. All mortar, staging, or hoisting apparatus that
may be required in connection with this work shall be furnished by the con-
tractor for cut stone. All cut stone will be set from the outside; but the
mason shall back up all cut-stone work in a manner approved by the
superintendent.
SPECIFICATIONS FOE LAYING MASONRY IN FREEZING WEATHER.
Only in case of absolute necessity will any masonry be laid in freezing
weather [see § 144]. Any masonry laid in freezing weather must not be
pointed until warm weather in the spring.
If necessary, masonry may be laid in freezing weather, provided the stone
or brick are warmed sufficiently [§ 144] to remove ice from the surface, and
the mortar is mixed with brine made as follows: "Dissolve one pound (1)
of salt in eighteen gallons of water when the temperature is 32° F., and add
one ounce of salt for every degree the temperature is below 80° F.— or enough,
salt, whatever the temperature, to prevent the mortar's freezing."
INDEX.
ABTJ— AKC
Abutments of arches, dimensions of exist-
ing, 505
stability, empirical formulas for, 499
theory of, 492
Abutments of bridges, contents, 357, 361, 363
detailed plans, 350, 300, 302
foundation, 304
general form, 353
quality of masonry, 305, 385
T -abutment, 302
contents, 303
detailed plan, 302
U -abutment, 359
contents, 301
detailed plan, 360
wing abutment, 355
contents, 357
detailed plan, 356
Air-chamber, filling, 297
Air-lock, for pneumatic pile, 281
for pneumatic caisson, 284, 291, 299
position, 290
Arch, abutment of, stability, 492, 499
backing, 505
brick, 510
center, camber, 523
definitions, 515
examples. Cabin John arch, 525
stone bridges,
tunnel arch, 512
Washington bridge, 524
load supported, 51(5
outline forms. 519, 520, 523
striking, method, 523
time, 527
•culvert, 419
cost, 434
examples, 424
Atcbison, T. & S. F., segmental, 429
cost, 43H
semi-circular, 429
cost, 437
Chicago, K. & N., semi-circular, 427
cost, 430
Illinois Central, semi-circular, 424
cost, 435
standard segmental, 429
cost, 438
junction of wings to body, 420
masonry, cost of, 157, 159, 100
quality of, 432
specifications, foundations, 432, 533
masonry, 482, 531
paving, 148
segmental vs. semi-circular, 421
splay of wings, 419
definition, of kinds of arches, 441
of parts of an arch, 440
AEG
Arches, dimensions of abutments, 505
Of arches, 502
rules derived from practice, 494
thickness of abutment, 499
thickness at crown, American prac-
tice, 495
English practice, 496
French practice, 496
thickness at springing, 498
drainage 508
elastic, theory of, 491
engravings, 505
inverted, for foundations, 212
joint of rupture, 457
line of resistance, definition, 443
location. 453
hypothesis of least preesure. 554
hypothesis of least crown thrust, 455
30int of rupture, 457
Navier's principle, 405
Winkler's hypothesis, 4G3
masonry, 432
backing, 505
cost, 157, 159, 100
specifications, brick, 176, 177
stone, 482, 515, 531
relieving arches for retaining walls, 352
in spandrel filling, 506
spandrel, filling, q, v., 506
stability, criteria of safety, 447
conclusion, 452
crushing, 448
open joints, 451
maximum pressure, 4-51
unit pressure, 449
rotation, 448
sliding, 452
theories, 4C5
elastic arch, 491
external forces, 444
method of employing, 468
method of failure. 446
rational theory, 466
criterion, 473
symmetrical load, 466
general solution, 466
special solution, 469
unsymmetrical load, 471
Schemer's theory, 474
algebraic solution, 475
erroneous solution, 480
graphical solution, 479
reliability, 481
Rankine's theory, 482
curvature of linear arch, 482
method of applying, 487
reliability, 490
various theories referred to, 491
545
546
INDEX.
ART— BRI
Artificial stone. 112
B6tojti-Coignet, 113
Frear, 114
McMurtrie, 113
Portland, 113
R.aii some, 114
Sorel, 115
Ashlar, 138
backing-, 140
bond, 139
definitions, 136
dressing, 138
mortar required per yard, 141
pointing 141
specifications, 142
where employed, 142
Atchafalaya bridge, foundations, 273
Atehison, Topeka & Santa Fe, bridge abut-
ment, 359
culvert, iron pipe, 414
segmental arch, 429, 431.438
semi-circular arch, 429, 430, 437
Ax, and Tooth-ax, 126
Batter, definition, 135
Bearing piles, 219
Bearing power, piles, q. v., 233
soils, q. v., 188
Be* ton, see Concrete.
Beton-Coi^rnet, 113
Bismarck bridge, pressure on foundation,
877
Blair bridg-e, pier, 383
pneumatic foundation, caisson, 284
cost, 303
f rictional resistance, 297
rate of sinking:, 295
Blasting' in compressed air, 295
Brick, absorptive power, 20, 39, 45
arches, bond, 510
examples, 511, 513, 514
burning, 34
classification, 35
cost, 47
fire-brick, how made, 35
elasticity, co-efficient of , 13
masonry. 161
bond, 163
cost, 157, 160
data for estimates, brick required, 173
labor required. 174
mortar required, 174
impervious to water, 178
joints, finishing, 162
thickness, 10 1
strength, 164
compressive, 164
pressure allowed, 167
transverse, 167
specifications, arches, 177 532, 542
buildings. 175, 541
sewers, 176
vs. stone masonry, 177
moulding, 34
requisites for good, 37
size, 46
strength, crushing, 41
condition of surface, 42
data, 43-46
form of specimen, 42
size of specimen, 41
transverse. 40
data, 1*2, 45
weight, 46
Bridge; aAnument. see Abutment.
BRI— GEM
Bridge masonry, cost, 157, 160
Bridge piers, see Piers.
Bond, brick arches, 510
brick masonry* 163
stone masonry, 139
Box-culvert masonry, cost, 157, 100
Brooklyn-bridge foundations, cost, 303
description, 298
pressure, 377
Bush-hammer, 126
Building-stones, classification, 23
requisites for good, 3
tests, 5 ; see also Stone.
Buildings, data for computing weight of,
200
specifications for brick-work for, 541
Cain's profile for masonry dams, 329
Cairo bridge, f rictional resistance of caisson,
297
pier, outline of, 372
pressure on foundation, 377
stability of, 371
stones in a course of, 385
Caisson, definitions, 266
disease, 300
pneumatic, 284, 286
Blair bridge. 284
first use of, 280
guiding, 295
Havre de Grace bridge, 286
Canadian box culvert, 406
Cavil, 126
Cement, 52
amount required per yard of mortar. 86
classification, 52
cost, 67
data for estimates, 85, 86
lime-cement mortar, 84
strength, 92
mortar, see Mortar,
natural, 52
Portland, constancy of volume, 67
cost, 67
description. 53
specifications, 67. 71, 73. 74
strength, 62, 66, 69, 72, 73, 74
tests, see tests below.
weight per barrel, 67
Rosendale, cost, 67
definition, 52
description, 54
location of factories, 55
specifications, 73, 74
te-ts, sre tests below.
weight tier barrel, 67
selenitic, 100
specifications. American, 74
Austrian, 73
English, 74
French, 71
German, 67
tests. 56, 74
activity, 57, 68, 73
chemical analysis, 71
color, 56
constancy of volume, 67, 74
fineness, "60, 68, 73, 74, 76
sampling, 75
soundness, 59. 75
strength, 62, 69. 77
age wlien tested, 65
data, 65, 71, 72, 73, 176
form of specimen, 62
holding specimen, 62
1KDEX.
547
GEM— CTJL
Cement tests, strength, home-made testing-
machine, 63
mixing the mortar, 64, 69, 71
rapidity of applying stress, 63
time required to set, 68, 73
weight, 56
weight per barrel, 67
Centrifugal pump, 264
Center of foundation, proper position of,
20-2
Center of gravity of trapezoid, to find, 318
Center of pressure on foundation, 202
Channeling and wedging, quarrying by, 123
Chisel, pitching, 127
splitting, 128
tooth, 128
Chicago, K. & N. arch culvert, 427, 436
Co-efficient of friction, foundations, 276
masonry, 315
Coffer-dam, definition, 258
construction, 258, 289
double, 261
Havre de Grace bridge, 289
iron, 261
leakage, 262
movable, 261
process, for foundations, 214, 258
Compressed air, physiological effect, 209
Compressed-air process for foundations,
see Foundations, pneumatic.
Concrete, 102
cost, 110, 157, 160, 265
depositing under water, 106
foundations, 103, 215
for bridge piers, cost, 265
ingredients, 103
laying, 106
mixing, 105
proportions, 103
strength, 107
cornpressive, 109
transverse, 108
Concrete and piles for foundations, 254
Connecticut brown-stone, 30
Coping, 130
Cost, see the article in question.
Coulomb's theory of retaining wall, 341
Cover stones for box culverts, 398
theory for thickness, 398
formulas, 399
practical data, 401
Cramps, 136
Crandall, 127
Crib for coffer-dam, 260
Culvert, arch, see Arch,
iron pipe, 412
construction, 412
cost, 416
dimensions of the pipe, 412
end walls, contents of, 414
examples, 414, 415
large, 41G
weight of the pipe, 412
stone box, 396
Canadian, 406
contents, 403, 404, 405
cost, 405
cover stones, q. v., 398
dimensions, 403, 404, 405
double, 405
end walls, 398
examples, 403. 404, 406
foundation, 397
masonry, quality of, 401
specifications, 401, 531
CUI— EFF
iulvert, stone box, Standard form, 402, 403
West Shore E. E., 402, 404
timber box, 417
timber barrel, 418
vitrified pipe, 407
construction, 408
cost of the pipe, 410
end walls, 409
examples, 411
material required, 411
strength of the pipe, 408
water-way required, 391
formulas, 393
for quantity of flow, 304
Meyer's for the area, 394
Talbot's for the area, 394
practical method of finding, 395
Gushing pile foundation, 255
Cylindrical surface, method of forming in
stone, 129
Dam, arched vs. gravity, 330
bibliography, 334
curved gravity, 331
earth, 335
gravity, 311
masonry, 311
arched, 811
Cain's profile, 329
classification, 311
gravity, ccmditiou for stability of, 312
crushing, 320
maximum pressure, 322
tension in masonry, 32-1
limiting pressure, *325
nomenclature, 312
overturning, 817
by moments, 317
by resolution, of forces, 320
plan, 329
arched vs. gravity, 330
curved gravity, 33 1
straight crest vs. straight toe, 329
pressure allowable, 325
profile, 326
Cain's, 329
Krautz's, 328
method of finding, 827
Quaker Bridge, 328
Sliding, 313
qualify of masonry, 383
when employed, 335
width on top. 326
rock-fill, 384
cost, 337
when employed, 386
stone-filled timber crib, 835
Dimension stones, 136
Disk piles, described, 218
bearing power, 249
Dorchester sandstone, 30
Dowel, 130
Dredges, 271
Milroy, 272
Morris & Cumming's, 272
mud pump, 292
Dredging thro1 tubes, 271
Drift bolts, described, 258
holding power, 253
Drills used in quarrying, 118
Dynamite, 121
driving piles with, 227
Eads* mud-pump, 292
Efflorescence on brick-work, 181
548
IKDEX.
ELA— FOTI
Elastic arch, theory of, 491
Engravings, for list of, see Table of Con-
tents.
Estimates, data for, brick, 46, 47, 173, 174
cement, 67, 85, 86
lime, 50, 85, 86
mortar, 85, 86, 87
sand, 80, 86
Excavator, compressed-air, 272 ; see also
Dredges and Pumps.
Explosives, 119
dynamite, 121
gunpowder, 119
nitro-glycerine, 120, 124
quarrying by, 117
Extrados denned, 440
Face-hammer, 125
Facing, defined, 135
Feathers and Plug, described, 128
Figures, for list of, see Table of Contents.
Footings, off -set for masonry, 208
steel-rail, 212, 540
timber, 211
Forth bridge, pneumatic caisson, 298
Foundation, Atohafalaya bridge, 273
bearing power of clay, 190
bearing power of rock, 188
bearing power of sand, 192
bearing power of semi-liquid soil, 193
summary, 194
bed of, denned, 183
bridge piers, 255, 257; see also below.
buildings, 186
area required. 201
bearing power of soils, q. v. above, 188
consolidating the soil, 197
depth required, 195
drainage, 195
effect of wind. 204
examination of site, 186
footings, see Footings,
grillage, q. v., 215, 254
load to be supported, 199
piles, see Piles,
piles and grillage, 253
piles and concrete, 254
preparing the bed, 213
sand piles, 197
sand in layers, 198
springs, 196
coffer-dam process, 214. 258
construction of the dam, 258
thickness, 259
puddle wall, 260
leakage, 262
pumps, q. v., 263
preparing the bed, 264
cost, 264
compressed-air process, see pneumatic
process, below,
concrete, 103, 215, 265
cost of various processes compared, 310
« crib and erect caisson process, 266
construction of the caisson, 267
construction of the crib, 269
excavating the site, 270
principle of the method, 267
definitions, 183
drainage, 195
dredging through wells, 271
dredges, q. v., 271
cost, 277
iron tubes. 278
timber cribs, 278
FOTJ
Foundation, examination of site, 186
examples, 272
Atchafalaya bridge, 273
brick cylinders, 275
Hawkesbury bridge. 275
Pouglikeepsie bridge, 272
frictional resistance in sinking, 275
iron, cast, 276
wrought, 277
masonry, 277
freezing process, 307
advantages, 309
cost. 308
details, 307
history, 307
principle, 307
footings, see Footings above,
frictional resistance, 275
iron cylinders, 276
masonry cylinders, 277
pneuniatic'caissons, 297
wood piles, 247, 248
grillage, 215
Hawkesbury bridge, 275
independent, 204, 540
inverted arch, 212
lateral yielding, 235
pile, see Piles,
piles and grillage, 253
piles and concrete, 254
preparing the bed, 213, 264
Point Pleasant bridge, cost, 265
Poughkeepsie bridge, described, 272
pneumatic piles, 281
bearing power, 275, 283, 297
cost, 304, 305
pneumatic process, 278
advantages, 306
air-chamber, 284, 297, 208
air-lock construction, 281, 284, 290, 299
position, 290
caisson, 284
Blair bridge, 284
Havre de Grace bridge, q. v., 286
compressed-air process, 279
cost, Blair, 303
Brooklyn, 303
European examples, 304, 310
Havre de Grace, 302
Plattsmouth, 304
Philadelphia, 302, 304
definitions. 278
examples. Brooklyn, 298
Forth, 298
Havre de Grace, 286
St. Louis, 297
excavators, 291
blasting, 295
mud -pump, 292
sand-lift, 291
water-column, 294
filling the air-chamber, 297
frictional resistance, q. v., 275, 283, 297
guiding the caisson, 295
history, 279
physiological effect of compressed-air,
299
plenum process, 279
rate of sinking, 295
vacuum process, 278
sand in layers, 198
sand-piles, 197
steel-rail footings, 212
timber in, 269
timber footings, 211, 215
IKDEX.
549
— LIM
Foundation, under water, 257
vacuum process, 278
wind, effect of, 204
Freezing of mortar, 100
Freezing weather, specification for laying
masonry in, 543
Freezing process for foundations, q. v., 307
Friction-clutch pile-driver, 223
Friction, co-efficient of, for foundations,
276
for masonry, 315
Frictional resistance in sinking foundations,
q. v., 247, 248, 275, 297
Frost batter, 364
Grand Forks pivot pier, 380
Grillage, 215
Grout, 84
Gunpowder, 119
cost, 120
efficiency in blasting, 120
Gunpowder pile-driver, 226
Hammer, bush, 126
face, 125
hand, 127
patent, 127
Haunch of an arch, defined, 440
Havre de Grace bridge, pneumatic founda-
tions of, 286
air-lock, 291
caisson, 286
coffer-dam, 289
cost, 302
dimensions, 290
frictional resistance, 297
guiding the caisson, 295
machinery, 290
materials, quantity of, 290
mud-pump, 292
rate ol! sinking, 295
Henderson bridge, top of pier, 384
Hydraulic cement, .see Cement.
Hydraulic lime, 50, 82
Ice, effect on stability of pier, 368
Illinois Central arch culverts, 424, 435
Impervious brick-work, 178
Impervious mortar, 96
Independent piers for foundations, 204
Intrados, defined, 440
Inverted arch for foundation, 212
Iron coffer-dam, 261
Iron cylinders for foundations, bearing pow-
er of, 283
cost, 302. 304
frictional resistance in sinking, 276
method of sinking, 274, 281
Iron piles, 210
Jet vs. hammer pile-driver, 229
Joint of rupture, defined, 457
method of finding, 457
Fetit's theory, 462
Krantz's profile for masonry dams, 328
Laitance, 107
Lake Superior sandstone, 30
Lateral yielding of foundations, 255
Leakage of coffer-dams, 262
Lirne, cost, 50
data for estimates, 85
described, 48
hydraulic, 50
LIM— MOB
Lime, preserving, 49
testing, 49
weight per .barrel, 50
Lime mortar, 81
strength, 89
Lime-cement mortar, 84
strength, 92, 94
Machines, pile-driving, 221
Masonry, ashlar, see Ashlar. t
brick, see Brick,
co-efficient of friction, 315
cost, actual, arch culvert, 157, 160
bridge pier, 157, 160
railroad masonry. 157, 160
stone, 155
cutting, 156
summary, 160
tunnel masonry, 157
U. S. public buildings,
cutting the stone, 156
masonry complete, 156
cost, estimated, 153
ashlar, 154
dressing, 153
quarrying, 153
rubble, 155
dressing, 153
quarrying, 153
definitions of kinds, 136
footings, off-sets for, 208
general rules for, 138
measurement, brick, 172, 529
stone, 151, 529, 539
mortar required pert. yard, 87
off-sets for footings, 208
pedestal, specifications for, 385
specifications, see 'Specifications,
squared-stone, see Squared-stone.
stone, see Stone,
strength of, 148
brick, compresFuve, 164
transverse, 167
stone, allowed pressure, 149
safe pressure, 150
rubble, see Rubble,
weight of, 2UO
Measurement of masonry, brick, 172, 529
stone, 151, 529, 539
Medina sandstone, 30
Mortar, absorptive power, 20
amount required per yard of masonry, 87
cement, change of volume iu setting, 67,
cement-lime, 84, 8!) [74,, 101
co-efficient of elasticity of, 13
compression of, 101
cost, 95
estimates, data for, 85
elasticity, 1H, 101
freezing, effect of, 100
freezing weather, specifications for laying:
m, 543
grout, 84
hydraulic cement, 82
hydraulic lime, 82
impervious to water, 96
. lime, 81
lime-cement, 84
Portland va. RostMidale, 88, 91
Rosen dale VH. Portland, 83, 91
strength, 88
adhesive, 93
compressive, 92
increases with age, 89
tensile, (10
550
INDEX.
MOR— PIL
Mortar, strength, transverse, 12
sugar in, 97
Mud-pump, 292
Nipper pile-driver, 223
Nitroglycerine, 120, 124
Open joints in an arch, 451
Patent hammer, 127
Paving, 148, 532
cost, 157, 160
for foundations, 397, 432, 533
Philadelphia, pneumatic piles, cost at, 302
standard brick sewers, 513
Physiological effect of compressed air, 299
Pick, 126
Piers, contents, 387, 388
cross section. 378
examples, 372, 383, 384, 383
Gushing's pile, 255
dimensions, bottom, 378
examples. 372, 380, 383-SG
top, 377, 384
foundations, 257; see also Foundations,
iron tubular, 274, 387
location, 3(56
masonry, cost of, 157, 160
qiialtiy of, 379
specifications, 381, 537
pivot, 379
stability of, 367
crushing, theory of, 371
numerical example, 375
current, effect of, 3G7
foundation, pressure on, 376
ice, effect of, 3G8
overturning, theory of, 309, 370
numerical example, 374
resisting forces, 3(39
sliding1, theory of, 367
numerical example, 371
wind, effect of, 307
timber-barrel, 388
Piles, bearing power of, disk, 249
screw, 249
wood, actual, 247
experiments on, 246
factor of safety, 2-19
formulas, empirical, 241
author's, 245
Beaufoy's, 243
HaswelVs, 242
Mason's, 243
Mc&lpine's, 244
Nystro m's, 243
Sander's, 244
Traut wine's, 234
rational, 234
author's, 239
Kankine's, 241
Weisbach's, 241
friction al resistance of, 247, 248
load, safe, 248
ultimate, 247
butt vs. top down, 251
caps. 220
capping, 250
concrete and piles, in foundations, 254
- cost, 230
definitions of kinds, 216
disk, described, 218
bearing power, 249
PIL-PUM
Pile foundations, 250
concrete, 254
cost, 310
grillage. 253
position of piles, 250
sawing off the piles, 252
iron, 21(5
cylinders, 274, 281
cost, 304
sinking, fractional resistance, 276
method of, 274, 281
disk, q. v., 818
screw, q. v., 217
pneumatic, 281 ; see also Foundations,
pneumatic,
sand, 197
sawing off, 252
screw, 217
bearing power, 249
sheet, 219
shoes, 220
specifications, 220, 533
splicing, 221
top -us. butt down, 251
used to consolidate soil, 197
wood, 219
bearing power,see bearing power, above
specifications, 220, 533
Pile-driver, #21
drop hammer, 222
friction clutch, 223
Dipper, 223
steam vs. drop hammer, 225
dynamite, 227
friction clutch. 223
gunpowder, 22(3
hammer i*s. jet, 229
jet of water, 227
nipper, 223
steam, 224
drop hammer vs. steam, 225
water-jet, 227
hammer vs. jet, 229
Pile-driving, cost of, Si30
bridge construction, 231
foundations, 232
harbor work, 233
railroad construction, 230
railroad repairs, 231
river protection, 233
Pitching chisel, 127
Pivot pier, 379
Plane surfaces, method of forming in stone,
129
Plates, for list of, see Table of Contents.
Plattsmouth bridge, cost of concrete founda-
tions at, 2G5
cost of pneumatic foundations, 304
pressure on foundations, 377
rate of sinking by pneumatic process, 295
Plug and feathers,' 128
Pneumatic foundations, see Foundations,
pneumatic.
Point, 127
Pointing, 141 [265
Point Pleasant bridge, cost of foundation,
Poughkeepsie bridge, foundation described,
272
Pozznolana. 55
Pressure allowed on masonry, brick, 16G, 107
stone, 149, 151
Puddle, 260
Pulsometer, 264
Pumps, 263
hand, 263
I^DEX.
551
PUM—SEW
PumpB-, centrifugal, 2t>4
for waier-jet pile-driver, 228
mud-pump, 2U2
pulsometer, 264
steam siphon, 263
•Quarrying, 116
by channeling and wedging, 133
by explosives, 117
by hand tools, 116
•-Quoin, defined, 13G
Railroad masonry, classification, jo2
cost, 157, 160
specifications, 529, 534
Rankiue's theory of the arch, 482
Relieving arches for retaining' walls, 352
Resistance, fractional, in sinking founda-
tions, 247, 248, 275, 207
Retaining walls, Coulomb's theory, 341
definitions, 338
details in construction, 350
difficulties in theories, 339
dimensions, empirical rules for,
Benj. Baker's, 349
English, 349
Traut wine's, 349
drainage, 350
failure, method of, 338
land-ties, 351
Rankine's theory, 348
relieving arches', 352
stability, theory of. 339, 340
applicability of, 3-18
assumptions necessary, 340
Coulomb's theory, 341
surcharged wall, 343
reliability. 343
Rankine's 'theory, 348
Wey ranch's theory, 343
general formula, 344
horizontal earth-surface, 345
surcharge, 345
reliability, 316
Weyrauch's theory, q. v., 343
Riprap, 148, 532
cost, 157, 1GO
Rubble masonry, 145
cost, 157, 1(50
coursed, 137
mortar required per yard, 87, 146
specifications, 147 , 531, 53(5, 541
uncoursed, 137
Sand, amount required per yard of mor-
tar. 86
cost, 80
data for estimates, 86
foundations, used for, 197, 198
requisites for good, 79
voids in, 80
weight of, 80
Sand-lift, 291
Sand-pump, 292
Sandstones, those most frequently used, 30
Seheffler's theory of arch, 474
•Schuy Ikill bridge,cost of pn eumatic piles, 302
,Screw-piles, 217
bearing power, 249
'Seasoning of stones, 17
.Sewers, brick arches for .
Philadelphia standard, 513
Washington standard, 514
Sewer-pipe, cost, 410
SEW— STE
Sewer-pipe, strength, 408
weight, 410
Sibley bridge, guiding the caisson, 296
piers, specifications for, 381
Skew arch, defined, 442
Slope- wall masonry, 147
cost, 157, 100
specifications, 147, 531
Soap and alum wash for brick-work 178
Soffit, defined. 440
Soil, bearing power of. 188
clay, 190
rock, 188
sand, 192
semi-liquid soil, 193
summary, 194
testing, method of, 187
examining, method of, ]86
improving, method of, 195
Spandrel, defined, 440
filling, arches in, 508
drainage of, 508
Specifications,
arch culvert masonry, 432, 531
architectural masonry, 534, 539
ashlar, 142, 531)
box culverts, 401, 531
brick-work, arches, 177, 532
buildings, 175, 541
sewers, 176
bridge piers, 381
cement, 67, 71. 73, 74
concrete, 532, 535, 540
foundations, 432, 533
masonry,
arch culvert, "432
ashlar, 142
brick-work, 175, 177
buildings, architectural, 539
railroad, 584
laying in freezing weather, 543
paving, 148
pedestal, 385
pier, 3dl,
rubble, 147, 581, 536, 541
slope-wall, 147
squared-stoiie, 144
paving. 148
piers, 381, 539
piles, 220, 533
rubble masonry, 147, 531, 586, 541
slope-wall masonry, 147, 531
sqiiared-stone masonry, 144, 530, 588
Splicing piles, 221
Squa red-stone masonry, 148
definitions, 137
pitched-face, 137
quarry- face, 137
range, work, 137
mortar required per yard, 144
specifications, 144, 530, 538
Standard arch culvert, 249
contents, 438
cost, 438
dimensions. 483
Standard stone-box culvert, 402
contents, 40t3
cost, 405
dimensions, 408
St. Geiievteye sandstone, SO
St. Louis bridge foundations, 297
maximum pressure on, 877
Steam pile-driver, 224
drop-hammer us, steam, 2'Jo
Steam siphon, 2(33
552
IN mix.
STE— STO
Steel-rail footings, M12, MO
Stone, absorbing power, 20
Stone, argillaceous, 25
artificial, 11 a
calcareous, 25
cost, 155
crushing strength, 6
cushions, 6
data, 10
fracture, form of, C
specimen, dressing, 9
form, 8
size, 8
slabs, 10
cut-stone, 132
axed, 138
bush-hammered, 184
cranclalletl, 188
diamond panel, 184
fine-pointed, 133
tooth-ax«d, 183
rough-pointed, 182
rub beef, 184
description, artificial. 112
granite, 26
limestone, 27
marble, 27
sandstone, 28
trap, 26
durability, 4, 14
destructive agents, 15
preserving, methods of, 22
resisting agents! 16
seasoning, effect of, 17
testing, method of, 19
artificial, 19
absorptive power, 20
acid, effect of, 22
atmosphere, effect of 2&
Brard 'a method, 22 '
crushing strength, 6
frost, effect of, 20
microscopical examination, 22
elasticity, 13
granite, 26
hardness, 14
limestone, 27
local names, 31
marble, 27
market price, 155
masonry, q. v., definitions, 185
measurement of, 151 ,529 539
requisites for good 3 '
' deseriPtion <
specific gravity, 32
squared, drafted, 132
f"
STO YAZ
vti, j»»irlt f,-irnl, 1
ttt«v»l. KJ*
trnt»NVf».s«\ I !
ti-sts. hilittoKniji
«| v,,
t»f, M
Stnm» suvvs, I'JS
Sutfnr in mortar, '<*«'
Siirrmvs, ui«*tboil of f«»nni»^, !
Tnblrs. for lint of, ,*•»• Tnblp of i
Timber, bunvl rulvrrt, -IIU
box iMllVlMf, H,
fottuUutlnits, VWI
Trt»ini«», Idi'
Wall, d«»fluitioUK «»f jmrf'-i nf fit i:r»
Wnnit-d Nui'l'iiri*, uirdtoil **f fonutint, I'll
WuMhin^ton hrh'k M«wi«f"«, M4
Waft-r j«»t j»il«« «tnv«»r, y.'i
t1*. tmtumor |*tl<'-<Irivri\ '.f'JU
Watt»r-wiiy forctilvt'i'is :u>i
factors, "hill
fonnulns, .'HK1
Tafl«»t'K, .TJJ
Wavtn'ly siuubitotu*, "10
W««stShoiv*»unj»«.tiox *'«lv»Tt. -Hi1.1, -li'i
WcvmiuMi'M theory ««f rpinintitK unU-, ::j
\Miitt* wiinhM on lirh'U \vnrU, is|
WlntJ, I'H'iH-t ttri fotiiMtniinii, vol
proHHtuv, amount of, 7^1
Wood ln«nrin« pl!««H, wr 1'IU-M.
Welffht. brick, 'III
cuwt-iroit pip«s 4J'I
cubic foot, 0(i
linio, fj()
wand, H() *
Yazoo Rivt»r
PLATE I.
CAISSON, CRIB AND COFFER-DAM,
HAVRE DE GRACE BRIDGE.
FOB TEXT, SEE PAGE 286.
PLATE VL
12-FOOT STANDARD ARCH CULVERT.
FOR TEXT, SEE PAGE 429,
I
ADVEBTISEMEHTS.
(1)
GUSTAV LINDENTHAL,
Civil Engineer,
PITTSBURGH, PA.
SPECIALTIES: Difficult Foundations, Long-Span Bridges,, and all
Iron and Steel Constructions.
CHE AS. SOOYSMITH, President.
WM. SOOYSMITH, Consulting Engineer.
E. 3L. ABBOTT, Assistant Engineer*
(mCOKPORATED,)
Contracting Engineers,
Design and Build in any Part of the Country
BRIDGE PIERS, PNEUMATIC CAISSON FOUNDATIONS,
TUNNELS, MARINE PIERS, DOCKS,
LIGHTHOUSES,
AND ALL KINDS OF ENGINEERING CONSTRUCTIONS.
TI-IE
METHOD
Now in use by us, and for which we control the American Patents, makes
the construction of subaqueous tunnels, deep foundations, shafts, etc., prac-
ticable in soft or water-bearing ground, and to depths hitherto unattainable.
Main Office : No. 2 NASSAU STREET, NEW YORK
(2) ADVERTISEMENTS.
Drilling and
Compiling
FOR
TUNNELS, QUARRIES, MINES,
RAILROADS,
"wlierever Ore and IRocls: sure to Tbe
Drilled and Blasted.
SEND JPOJK NEW
RAND DRILL Co.,
33 Park Place, New York, TJ. S. A.
ADVUHTISEMEXTS. (3)
.JAMES BLACK, Prest., I — rm,^ Mn CHAS. BRAINERD, Supt.,
.JOHN S. ROPER, Sec'y, \st' Louis> Mo' Grafton, III.
Grafton Quaff y Co.,
DEALERS IN ALL KINDS OF
GRAFTON STONE.
OFFICE, 41 5 LOCUST STREET,
JKoom £04. ST. IX)UIS.
QUARRIES:
GRAFTON, JERSEY COUNTY, ILLINOIS.
froiti the Report of Capt. <Tas. IS. 2£ads, Chief Engineer Illinois
atitl St. Jjonis Jtridye Co., October 3.S7O, in. reyard to a test made of a,
specimen of Stotie from the Grafton Quarries. He says:
"It is remarkably strong. Many tests of its compressive strength have
been made in the company's testing machine, where its resistance has, in
several instances, exceeded 17,000 pounds per square inch, which is equal to
that of granite.
"A curious fact has "been developed by these tests, which is, that the
modulus of elasticity of this stone is about the same as that of wrought iron
That is, a given weight placed upon a wrought-iron column and on a column
•of the Grafton stone of the same size, will produce an equal shortening in
both ; while the elastic limit (or breaking point) of the stone is not far below
the limit at which the wrought iron would be permanently shortened. A
•column of the stone two inches in diameter and eight inches long was short-
ened under compression in the testing machine nearly one quarter of an inch
without fracturing it. When the strain was removed the piece recovered its
•original length."
JTroin the Geological Survey of the State of Illinois. Mr. Pcatten's Analysis
of a, specimen of Grafton Stone :
INSOLUBLE MATTER, .... 5.60
CARBONATE OF LIME, .... 47.79
IRON AND ALUMINA, .... 1.40
, fYT? M A fiNir.Rl A 4V, ««
(4) ADVERTISEMENTS.
PEERLESS COLORS
FOR MORTAR,
RED, BLACK, BROWN, AND BUFF.
ALL COLORS PERMANENT,
AND SUPERIOR TO ANY ARTICLE IN USE.
PREPAKED ONLY BY
Samuel fL French & Co.,
PAINT MANUFACTURERS,
IMPORTERS, DEALERS, AND MANUFACTURERS OF
PAINTERS' AND BUILDERS' SUPPLIES,
York Are., Fourth and CallowMll Sts.,
Send for Circulars and Catalogue. PHI LA DELPHI A5 P A«.
ADVERTISEMENTS. (<r>)
MILWAUKEE »•
CEMENT.
"gEST NATURAL flEMESI 1 THE ^ORLD."
Capacity, 4,000 Barrels per Bay. Annual Sales, 400,000 Barrels.'
CORRESPONDENCE SOLICITED.
For Uniformity of Grind and Ultimate Strength
It Stands Unrivaled.
MILWAUKEE CEMENT Co.,
West Water Street,,
Milwaukee, Wis.
Send for Handbook on Hydraulic Cement, free.
PROMPT SHIPMENT G-UARAWTEED.
Works of Prof. Robt H. TMrston.
MATERIALS OP ENGINEERING.
A work designed for Engineers, Students, and Artisans in wood, metal, and stone.
Also as a TEXT-BOOK in Scientific Schools, showing the properties of the subjects
treated. By Prof. K. H. Thurston. Well illustrated. In three parts.
Part I. THE NON-METALLIC MATERIALS OF ENGINEERING
AND METALLURGY,
With Measures in British and Metric Units, and Metric and Keduction Tables.
Svo, cloth, $3 00-
Part II. IRON AND STEEL.
The Ores of Iron ; Methods of Reduction ; Manufacturing Processes ; Chemical and
Physical Properties of Iron and Steel ; Strength, Ductility, Elasticity and Resistance:
Effects of Time, Temperature, and repeated Strain ; Methods of Test ; Specifications.
8vo, cloth, 4 00
PartHI. THE ALLOYS AND THEIR CpNSTITUENTS.
Copper, Tin, Zinc, Lead, Antimony, Bismuth, Nickel, Aluminum, etc.; The Brasses,
Bronzes ; Copper-Tin-Zinc Alloys ; Other V_aluable Alloys ; Their Qualities, Peculiar
Characteristics; Uses and Special Adaptations ; Thurston's " Maximum Alloys";
Strength of the Alloys as Commonly Made, and as Affected by Special Conditions ;
The Mechanical Treatment of Metals Svo, cloth, 3 OO
"As intimated above, this work, which is soon to be completed, will form one of the most
complete as well as modern treatises upon the Materials used in all sorts of Building Construc-
tions. AS a whole it forma a very comprehensive and practical book for Engineers, both Civil
and Mechanical."— American Machinist.
" We regard this as a most useful book for reference in Its departments ; it should be in every
Engineer's library-" — Mechanical Engineer.
MATERIALS OF CONSTRUCTION.
A Text-book for Technical Schools, condensed from Thurston' s " Materials of Engi-
neering.'7 Treating of Iron and Steel, their ores, manufacture, properties and uses;
the useful metals and their alloys, especially brasses and bronzes, and their "kal-
chords " ; strength, ductility, resistance, and elasticity, effects of prolonged and oft-
repeated loading, crystallization and granulation ; peculiar metals ; Thurston's "maxi-
mum alloys " ; stone ; timber; preservative processes, etc., etc. By Prof. Robt. H.
Thurston, of Cornell University. Many illustrations Thick 8vo, cloth, 5 OO
" Prof. Thurston has rendered a great service to the profession by the publication of this
throrough, yet comprehensive, text-book. . . . The book meets a long-felt want, and the
well-known reputation, of its author is a sufficient guarantee for its accuracy and thorough-
ness. "— Building.
TREATISE ON FRICTION AND LOST WORK IN MACHINERY
AND MILL WORK.
Containing an explanation of the Theory of Friction, and an account of the various
Lubricants in general use, with a record of various experimentg^to deduce the laws
of Friction and Lubricated Surfaces, etc. By Prof. Robt. H. Thurston. Copiously
illustrated Svo, cloth, 3 OO
" It is not too high praise to say that the present treatise is exhaustive and a complete review
of the whole subject. — American Engineer.
STATIONARY STEAM-ENGINES.
Especially adapted to Electric Lighting Purposes. Treating of the Development of
Steam-engines— the principles of Construction and Economy, with description of
Moderate Speed and High Speed Engines. By Prof. R. H. Thurston. 12mo, cloth, 1 50
"This work must prove to be of great interest to both manufacturers and users of steam-
engines. "—Builder and Wood-worker.
DEVELOPMENT OF THE PHILOSOPHY OP THE STEAM ENGINE.
An Historical Sketch. By Robert H. Thurston 12mo, cloth, 75
CONVERSION TABLES
Of the Metric and British or United States WEIGHTS AND MEASURES. With
an Introduction by Robt. H. Thurston, LL.D., Dr. Eng Svo, cloth, 1 00
A MANUAL OF STEAM BOILERS, THEIR DESIGN, CONSTRUC-
TION, AND OPERATION.
For Technical Schools and Engineers. By Prof. R.. H. Thurston. Numerous
illustrations. 686 pages Svo, cloth, 6 00
STEAM-BOILER EXPLOSIONS IN THEORY AND IN PRACTICE.
Containing Causes of — Preventives — Emergencies — Low Water — Consequences —
Management — Safety — Incrustation — Experimental Investigations, etc., etc., etc.
By R. H. Thurstou, LL.D., Dr. Eng., Director of Sibley College, Cornell Univer-
sity. With many illustrations 12mo, cloth, 1 50
"Prof. Thurston has had exceptional facilities for investigating the Causes of Boiler Explosions, and
throughout this work there will be found matter of peculiar IntereBt to Practical men."
—American Machinist.
HAND-BOOK OF ENGINE AND BOILER TRIALS.
A Practical Work. By Robert H. Thurston Svo, cloth, 5 00
*#* Will be Mailed and Prepaid on the receipt of the price.