UNIVERSITY OF TORONTO LIBRARY Acme Library Card I Under 1'at. "Kef. Index Kile." Made by LIBRARY BUREAU OCT 113. STANDARDIZATION RULES OF THE AMERICAN INSTITUTE OF ELECTRICAL ENGINEERS As approved by the Board of Directors. June 27. 191 1 mi- 99 *• I- e- *• PRICE. (Paper). 10 CENTS (Dl»co«ni en Ownttttea) PRICE. (Cloth). 25 CENTS (N.t) Published by THE AMERICAN INSTITUTE OF ELECTRICAL ENGINEERS 33 West Thirty-ninth Street. New York Third Edition. December. 1912 STANDARDIZATION RULES or THE AMERICAN INSTITUTE OF ELECTRICAL ENGINEERS HISTORY OF 1 VNDAKDIZATION R< *lep tak ' the %tandar al apparatus and method* was a topical discussion on " The Stand- •cnerators. Motors and Transformers." which took place .mcously ork and Chit Ago on thr evening of January 26. 1808. The ditctmion appears in t! rested were generally favorable to the »• standardisation . • .1 apparatus, although some members feared that difficulties might ante. As a result of this dis- cussion, a Committee on Standardization was appointed by the Council of tl .lowing meml>- Kit vs. is II ( K.H KI w ( kittrma*. !h t« IIINSOX CHABLBS P. SinswBTi LEWIS ! KI.L JOHN \V LIEU. JR. -it- THOU il consideration of the matter and consultation with the members of the Institute and interested parties generally, a " Report of the Committee on Standardization." was presented and accepted by me 26. 1899. Those original rules appeared in the In- stitute TKVN XVI, pages 255 and 268. As a result of changes and developments in the i was subsequently found necessary to revise the original report, this work being car 'he following Committ< lardisation: MM is B. CtOCKBI. Ckatrma*. A Kill i K t \RI.E4 P. ST*|N*> •M \V. I.IEH. JE. LBWIX h SUM. WELL C. o. N: HOMSOM This revised report was adopted at the 19th Annual Convention at Great Harrington, Mats., on June 20, 19O2. and appears in t • TmAMBAcnoHs. Vd M-^ ; ••^- i""'> to 1092. . further change and development in electrical apparatus and methods, it was de nbrr. 1905 that a second is needed, and the following C remittee was appointed to do this v FRANCIS B. CROCKEE. Ca«<>««». K» NXEU.Y. Stereo HENRY S. CARHART CHARLES P. SCOTT ix \V. LlBB. JR report at tin Annual Convention, held at Mihvar. v 28-30. 1°XX> siderable discussion the report was accepted .mi Committee for amend irrangemenl in form. It was then to be submitted to the Board of Directors for final adoption. In Si-p1 ber, 1906, the foil- on Committee was apj \N. is H. <-K! HMTIONS AND TECHNICAL DATA Paragraph A. DEFINITION*— CURRENTS AM* i: MP.'S.. 2 to 6 B. DiriNiTiOKt— ROTATING V 7 to 2la C. DEFINITIONS— STATIONARY INDUCTION APPA* ..' to 29b D. GENERAL CLASSIFICATION OF APPA»V 30 to M B. MOTORS— SPEED CLASSIFICATION 45 to 49 49., to 49g ION AND OF TERMS %0 to 63 rid Factor 50 tO Sib Load >v.» to ftia : » Power- Factor and Reactive Factor 54 to 56 Saturation- Factor 57 to 58 (V) Variation and Pulsati • 59 to 63 II PKRPORMANCE SPECIPICA . TESTS 65 to 78* B. WAVE SHAPK 79 to 80 C. EFFICIENT 84 to IM Definitions *4 to 88 of Efficiency .80 to 100 • Losses inl : fTcrent Types of Apparatus UK to 186 (A) Direct current Commutating Machines . .118 to I'M B) Alternating-Current Commutating Machines. 127 to 135 C) Synchronous Commutating Machines 1 t<> • D) Synchronous Machines . I4H to 155 itionary Induction Apparatus !'•• t .on Apparatus 162 to 167 (C) Unipolar or Acyclic Machine 16S to ng Apparatus 176 t« Transmission LiMi KM Phase- Displacing Apparatus 1 ^ i to 186 D. RE*. to 200 ls7 to 203 MS for and Tests of Regulation 204 to 200 E. INSILATI* .MO to 250 (I) Insulation Resistance .MO to 213 'cnKth .M4 to 250 .M4 to 226 (B) Methods of Testing 227 t hods for Measuring the Test Voltage .'4.' • Apparatus for Supplying Test Volugr 250 to 259 STANDARDIZATION Kl: :: \ //•:/•:. p. COM-! cnvm ... -2M RISE OF TEMPERATURE. . . .261 to 292 (I) Measurement of Temperature .261 to'JTl (A) Methods .261 to 266 (B) Normal Conditions for Tests.. .267 to 271 (II) Limiting Temperature Rise... ..272 to 292 (A) Machines in General ..274 to 278 (B) Rotary Induction Apparatus.. ..279 to 282 (O Stationary Induction Apparatus ..283 to 286 (D) Rheostats... .287 to 288 (E) Limits Recommended in Special Cases 289 to 292 H. OVERLOAD CAPACITIES. ... .293 to 304 III. VOLTAGES AND FREQUENCIES A. VOLTAGES... .".or, to 310 B. FREQUENCIES M to 312 IV. GENERAL RECOMMENDATIONS -il.i u V. APPENDICES AND TABULAR DATA APPENDIX A. — NOTATION ... 324 APPENDIX B. — RAILWAY MOTORS (I) Ratine. 325 to 327 (II) Selection of Motor for Specified Service 328 to 340 APPENDIX C. — PHOTOMETRY AND LAMPS... .11 to 357a APPENDIX D. — SPARKING DISTANCES 358 to 359 APIM-MHX K. IKMIM-KAM KK COEFFICIENT- 360 APIMMMX !-.— HORSE POWER.. 361 PAGE APPENDIX G. — Ivn K\ \ i I<>N \i. A<.KKKMKNTSOF THE I. E.G. 261 1 (Adopted at the Turin Congress in 1911.) APPENDIX H. — RATING OF ELECTRICAL MACHINJ I . 2572 t« (Comparative Rules of Different Countries.) APPENDIX I. — HEATING AND GUARANTEES 2584 to 2585 (Additional Comparative Rules.) STANDARDIZATION RULES OF THE A. I. E E. Ai'i'Mtixi-n 1 1 M '.'7, I'M 1 I DEFINITIONS AND TECHNICAL DATA 1 Af* rftmtions and dassificaUons are intended to be prac- cientifically rigid. A. DKF1M S A DIRECT • ; «s a unidirectional cur: I A r is a steady, or non-imitating, direct current. ; nt to the superpov alternating current upon a continuous current. • An ALTERNATING Ct RRENT OR E.M.F. it a currerr when plotted .IK' m rectangular coordinates, consists of half- waves of equal area in successively opposit- us from the tero •a CYCLE. Two imn. ucceeding half-waves constitute a cycle. 6b Pi KI- ired forth n of a cycle is called a penod REQUENI • cycles per second is called the frequency M WAVK-FOEM. Theshajv fe.mf. or current plotted against time in rectangular coordinates, is ordinarily referred to as the wave-form or wave-shape. Two alternating quantities are said to nave the same wave- shape if their corresponding phase ordinates bear a constant ratio. The wa\ .is ordinarily understood, is thus independent of the scales to which th Se SIMTLB A i Unless otherwise specified an alternating current or e.m.f. is assumed to be sinusoidal, ana the wave a sinusoid, sine-wave or curve of sines. On this account a complete c 860 degrees, and any j>< ay be expressed in degrees •, such as the ascending tero-p* is a non- sinusoidal wave complex -\f> wave is capable of being resolved into a single f fundamental f: with superposed odd-frequency waves, or ripples. Of I . (2 • + !) times the fundatiK v. each harmonic having constant amplitude a definite st on to the fundamental sine-wu custom.. inolvzing a complex wave, to neglect harmonics higher tha ecial cases, h itill higher may have to be considered. In cert : cases cvep harm 6g Rooi K VALUE (sometimes called the Virtual or Efl Val ss otherwise specified, the rating of an alternating-current or e.m.f.. in amf>eres or volts, is assumed to be the square root of the mean square value taken throughout one or more complete cycles. T sometimes abbreviated to r.m.s. The term root-mean-square it to be •rrt-d to the terms virtual or effective. The root -mean -square value is indicated \ ;>erlv calibrated Alternating-current voltmeters and am: c of a sine-wave, the ratio of the maximum to the r.m.s. value is \X2. 5 STANDARDIZATION RULES OF Till: 17 •h FORM-FACTOR OF AN ALTERNATING WAVE. The ratio of the root square to the arithmetical mean ordinate of a wave, taken without regard to sign, is called its form-factor. The form-factor for a purely rectangular wave is the minimum, 1.0; for a sine wave it is 1.11, and for a more peaked than a sine wave it is greater than 111 6i THE EQUIVALENT SINE WAVE is a sine wave having the same frequency and the same r.m.s value as the actual wave. .e DEVIATION of wave-form from the sinusoidal is determined py super- posing upon the actual wave, (as determined by oscillograph), the equiva- lent sine wave of equal length, in such a manner as to give the least \ *!/>:.% "A / //> I / 7UL 11 - tipplie* both direct and alternating c same armature -winding . 1U As i ..; alternator in which both itld and armature winding* am station .> lib aathinc structurally identical with an .iction motor, but .\c synchronous speed a* an alternating- nt gcnci 12 A MOTOR transforms electrical power into r*tffltftknt power. lia A DIRECI i MOTOR transforms d ;«ower into me- 12b >ntforms alternating -current lie A mach urally (dent* synchronous alternator, but operated a* a motor. lid A • * s. HRONOUS- PHASE MooiMEE. »omeiim«t called a SyocfefOflmft Con- rooous motor, running cither idle or underload. wbotefteJd • >cd to a» . the power-factor of t i or ihroufh -• influence the voltage of the or He rent motor, either i polrphaae, independent orimary and jtcondiry one of which, usually the »r» • The secondary winding has n<> .-.!:•:.•• . .,nn.-, non with the np|> Iff A Ki \IOTOI is an induct . 11 y wnfle phaae. in which axis of the secondary, (a doted coil winding mounted on the r). is maintained at a > •! angle with respect to the sUtiooary primary coil by mean* of a multi«rgmcntal commutator aad ih< ing brushes. 12g to a series direct-current t: i»ually |>r n ad- i series compensating * -ed around the out- t! in slots in the pole face*, for the poipos* of leakage react a: 13 A BoosTKE is a mat him- m>erted in MTK-N :n a .:• .11*. to change it* '.IKC. It mav !.<• M w M. K is a transforming device consisting of a motor '•cted to one or more generators. 16 A I1 msforming d< innmg both motor and general* •• magnet -her with two armatures, or with one armature having two separate winding- and independent commutator*. 16 ng mechanical rotation in elr i into another. A converter may to either of several types, as follows: 17 a. A DiKKt i ('t MKBST CONVERTER converts from a direct current to a direct current. . 'age. 18 s VERIER (commonly called a rotary converter* converts from an alternating to a other than the impressed turc of th nt at frc' t is a synchronous converter concatenated with an in- SO **. A FIBQVEM t t'utM.i * • « rts the power of an alternating-current system from one frequency to another, with or without a change in the number of phases or in the voltage. 21 t. A ROTARY PHASE CONVERTER cor MI an alternating-current system of one or more phases to an alternating-current system of a dif- ferent number of phases, but of the tame frequency. aia KOI U.I/IM. CONN*:* u. -sx are low resistance connections between equipotential points of multiple-wound closed-coil armatures to equalise the induced voltage between brushes. STANDARDlZArio.\ Ri'l.i HI: A.I / C, DEFINITIONS. STATIONARY INDUCTION APPARATUS. 22 STATIONAKN IM>I« IION APPARATUS changes electric energy to electric energy through the medium of magnetic energy. It comprises several forms, h Hi (>n motors, induction generators. frequency lary phase cor 18 i •> m which the rs maintains the same direction i respect to those conductors. 39 K J • i n , i -.. ' i . i > <»RNRRATORf 40 I i i • i MI IMA i n .\i-\- \»> as condensers, etc. 41 i 42 I LRC IKOTMKMMAL APPAR 42. i 1- 0 APPARA 43 I K APPAMV i« 2i> fair* breakers, Iifhtniof 44 iay, for convenience, be classified with reference to their speed characteristics as follows: 46 « Ahich the S;HT,I is either constant or does not uch as is motors, induction motors ton. 47 ' OTORS (two-speed. thr< .in be x- speeds being ; windings, or number of poles. 48 i - can be varied grad- ually over a considerable range; but when once remains prac- .lly unaffected by the load, such as shunt motors devigned for a con- siderable r ion. 49 d VAKMN<. -i i i o or motors in which the speed varies with the load, decreasing when the load increases: such as series motors. : \STRfMENTS. 49a As AMMI -is . nt-nu-asur licating in amperes. 49b .tge- measuring instrum< *in^ in volts. >wer. and •in in w.i 49d KKCUKDING AMMETERS, VOLTMETIK METKRS. etc.. are instru- •s which record graphically upon a time-chart the values of the qnaa* tit: 49e A V K METER is an instrum. ng total watt- hours. This term is to be preferred to the term -ing wattmet< 49f MKTBR COMPENSATOR is a device in connection with a meter, which causes the latter to indicate the voltage at some otb«-r point of the circuit. 49g IKOSCOPE is a synch: <• which, in . Mition to K- synchronism, shows whether the machine to be §yn« hronr fast or slow. G. DEFINITION A OP TKP (I) LOAD FACTOR. 60 The LOAD FACTOR of a machine, plant or system is the rat • '. the average power to the maximum p< ng a crrtain period of :>me. The average power is • n period of time, such as a dajr or a year, and the maximum is taken over .1 iterval of the maxi- mum load within that 61 In •-.-. h case the interval of maximum load should be definitely speci- fied. The pn>j»ei tally dependent upon local and upon the purpose for which the load factor is to be determined. 10 STANDARDIZATION RUI.KS ()/• Till- A.I.I- 17-.K.S7/ ) FACTOR. 61* DIVERSITY FACTOR is the ratio of the sum of the maximum p demands of the subdivisions of any system or part of a system, to the mut I of the whole system or of the part of the mder con- sideration, measured at the point of supply. (Ill) DEMAND FACTOR. 61b l)i MVM> F M IMK if the ratio of the maximum power demand of !«• the total connected load of th i or of •;. under considcraticii. (ID .VO.V-/A7H LOAD AND INDUCTIVE LOAD. 62 A non-inductive load is a load in which the current is in phase with the voltage across the load. 63 An inductive load is a load in which tin- current lags behind the voltage across the load. A load in which the current leads the voltage across the load is sometimes called a condensive or anti-inductive load. 63a When voltage and curr I arc sinusoidal but not in \>\ the voltage may be resolved into two components one in phase with the current, and the other in quadrature therewith. The former is called the effective component (sometimes the energy component), and the latter the reactive component of the voltage. The current may be similarly subdivided with respect to the voltage, and the two components similarly- named. (V) POWER- FACTOR AND REACTIVE FACTOR. 64 The POWER-FACTOR in alternating-current circuits or apparatus is the ratio of the effective (i.e. the cyclic average) power in watts to the appar- ent power in «'olt-ampcres. It may be expressed as follows: effective po watts effective current apparent power "total volt -amperes* total cur: 66 The REACTIVE-FACTOR is the ratio of the reactive volt-amp- the product of the reactive component of current by voltage, or re. component of voltage by current) to the total volt-amperes. It may be expressed as follows: : tivejxmtf _ reactive current _ i oltage apparent power* total yol s* total current 66 POWER-FACTOR and K FACTOR are related as foll« If p = power-factor and q = reactive-factor, then with sine waves of voltage and current. />'+R. 67 The SAT i K \im\- F.\< i<>k • f a machine is the ratio of a small p increase in field excitation to the corresponding percentage i: voltage thereby produced. The saturation factor is, therefore, a err of the degree of saturation attained in the magnetic circuit at any ex- •ion selected. Unless otherwise specified, however, the factor of a machine refers to the excitation existing at normal rated speed and voltage. It is determined from measurements of saturation made on open circuit at rated speed. 68 The PERCENTAGE OF SATI RATION of a machine at any excitation may be found from its saturation curve of generated voltage as ordinates, against excitation as abscissas, by drawing a tangent to the curve at the ordinate corresponding to the assigned excitation, and extending the tangent to intercept the axis of ordinates drawn through the origin. The rat o ot the intercept on this axis to the ordinate at the assigned excitation, when expressed in percentage, is the percentage of saturation and is indepen- \NDAIU>!ZATrO!9 Kt i.t in i / / 11 and voltage. Th; <*qual deducted .ind p the percentage of •at- IK/I/: 69 Th. VVHIMIMS is I'KIVU M..\, an an* ft; engines* is c.l in degree*. from the \>< \ould occupy with uniform rota- •i as 300 degn • 60 -K MOVKKS is the ratio of the difference between the maximum and minimum velocities in an en* -o the average 61 t in* s A tots or alternating in general it the n lifference in phase of the generated voltage wave from a wave of absolutely constant frequency of the same average value. expressed in electrical decrees (one cycle equals 300 degrees) and may be due to the variation of the prime n, 62 i :.' •! MOBS or alternating-current n gen- eral, is the ratio of the difference between maximum and minimum fre- luring an cn^ he average frequency. S3 I- "i VAKIAIIDS in prime mover and alternator. If p-num- >f pairs of poles, the variation of an alternator is p times the var : direct-connected, and p n times the variation of the prime mover if rigidly connected thereto in the velocity ratio •; so that the speed of the alternator is * times that of the prime mo . II. PERFORMANCE SPECIFICATIONS AND TESTS. TING. 66 k A us,, m < M MM i. All electrical apparatus should be rated by output and not by input. Generators, transformers, etc.. should be rated by electrical oir ors by mechanical output, and preferably in kilo- watts. 66a The following four classes of rating are recognised and recommended: they do not cover the ratine of railway motors which is treat- Appendix B. and there are other large though less definitely definable rliasei of i which each case must be treated by itself. Some of these may be later reduced to fairly simple terms and introduced into these Rules. 66b i vhich under load there is the attainn approximately stationary temperature, and no other limit of capac exce- 66c '2. INTKRMIM > which one minute periods of load and rest alternate until the attainment of approximately stationary temperature and no other limit of capacity is exceeded. 66d N the temperature depends upon the losses and the capacity he appar. it them, a constant load may be sub load in determining the temperature, provided the losses are m which under load for one minute, no mechanical. thermal, magnetic, or electrical limit of capacity is exceeded and no perma- nent wrought in the apparatus. 66f I \ VKIMMI SKKVICB R\TI i desirable here to recognise this class of rating which is intended the rating of motors for machine- tool and similar service, in which the thermal absorptive capacity plays a pan. The specif: >r this rating have not been fully determined at the time that this edition of the Rales goes to press. I _' STA XDA RDIZA TION R VLES OF Til / ,17 •6 K \IIN-. i^ KII.OWAIIV KUvtncal power should be expressed in kilo- watts, except when otherwise specif; 67 :. ii "\ « i i AMPERES. Apparent power in altrrnaiing- currcnt • uld be expressed in kilovoft-amperes as distinguished from effective power in kilowatts. When the power factor is 100 per cent, the apparent power in kilo volt -amperes is equal to the kilowa? 68 The RATED (PULL- LOAD huh. with the rated terminal voltage, gives the r.itr imum current which it is designed to carry continuously. 77m NOTE. In addition thereto, the maximum current and voltage at which a fuse or a circuit-breaker will open the circuit should be specified. It is to be noted that the behavior of fuses and of circuit-breakers is much influenced by the amount of electric power available on the circuit. 78 I sim AUNG METERS should be rated according to their full-scale reading of volts, amperes, or watts. In wattmeters the rated volts and rated amperes should also be included; i.e., the volts and amperes which can be safely and continuously carried by the voltage and current coils respectively. 78* WATT-HOUR METERS should be rated in volts and amperes. B. WAVE SHAPE. 79 The SINE WAVE should be considered as standard, except where a de- viation therefrom is inherent in the operation of the apparatus 80 A MAXIMUM DEVIATION of the wave from sinusoidal shape not exceeding 10 per cent is permissible, except when otherwise specified. See Section 5j. 81,82,83. See Sections 5e to 51. STANDAR/>IZAT/o.\ jfr/.A.s oh iin A I E.E. 13 BFPIC1 (I) DEFINITIONS. »4 an appat output to iu input The output and input may ».r m term* of watt-boor*, wmtu. volt-ampere*. ampere*, or any •>• of interest, thus respectively defining energy-enVim. -.. 5.. A,-: r!»i. •,!•.-.. .4;. ;.,--•• ,-•! , : ......... AIM specified, however, the term it ordinarily i :•.,:• • • • • : - " • -. -.••••. . • • • - 66 An In Apparatus in which a . inh< -i. apparent enVirnt-y should be the ratio of net i»« ,\\. 87 .. .oton. synchronous phase modifiers, >ous converters controlling the voltage of an alte: d regulator*, open magnetic circuit Iran 86 • parent efficiency of apparatus delivering electric pou the load, the apparent emciency. unless otherwise specified, should be referred to a load power-f actor of unity MEASUREMENT Oh Eh'hK 89 :nay be determined by cither of two methods, vts.: by measurement of input and outp -nent of losses. 90 I The input and output may both be meas •!>•. The ratio of the latter to th- the emciency. 91 .' SES. The losses may be measured either colic 1 losses may be added to the output to derive nput. or subtracted from the input to derive the output. 92 COMPARISON « The output and input method is preferable . small machines. When, howevi r. as in the case of large machines, measure the output and input; or when the per- 'age of power loss is small and the emciency is nearly unity, the method of determining rtVu u-ncy bv measuring the losses should be followed. 93 i hould be measured at the terminals of the appar- atus. In te .phase m.. he measurement of power should not IK* • a single circuit but should be extended to all the cir- cuits in ord< : 1 errors of unbalanced loading. N POWER in machines should be measured at the pulley, gearing, cout thus excluding the loss of power in said pulley, gearing or coupling. t> ng the bearing friction and windage. The magnitude of bearing friction and windage may be considered, with con- stant speed, as independent of the load. The loss of power in the belt and the increase of !•• -n should be excluded. is mounted upon the shaft of a prime n iot be separated therefrom, the fractional losses in bearings and in windage, which ought, by <: to be included y. should be excluded, owing to the practical impossibility of separating them from those of the prime mover. 96 In A APPARATUS, such as an exciter, the power lost in the auxiliary apparatus should not be charged to the principal machine, but to the plan* ng of principal machine and auxiliary app.t taken together. The plant emciency in such cases should be distinguished from the machine efficiency. 96 .• tests should be made under normal conditions herein set forth, which are to be assumed as standard. These conditions include voltage, current, power-factor, frequency, wave shape, speed, temperature and barometric pressure, or such of th< may apply in each particular case. Performance tests should be made under these standard conditions unless otherwise specified. See Sees. 75. 97 a. TEMPERATURE. The efficiency of all apparatus, except such as may be intended for intermittent service should be either measured at. or re- 14 \\n.\RrHZATION RULES OF Till A.l.E.E. duced to, the temperature which the apparatus assumes under continuous operation at rated load, referred to a room temperature of 25 deg. cent. See Sees. 267-202. 98 With apparatus intended for intermittent service, the efficiency should be determined at the temperature assumed under specified conditions. 99 b. POWER FACTOR. In determining the efficiency of alternating-current apparatus, the electric power should be measured when the currnr phase with the voltage, unless otherwise specified, except when a definite phase difference is inherent in the apparatus, as in induction motors, induction generators, frequency converters, etc. 100 c. WAVE SHAPE. In determining the efficiency of alternating-current apparatus, the sine wave should be considered as standard, except where a difference in the wave form from the sinusoidal is inherent in the operation of the apparatus. See Sec. 80. (Ill) MEASUREMENT OF LOSSES. 101 LOSSES. The usual sources of losses in electrical apparatus and the methods of determining these losses are as follows: 102 (A) BEARING FRICTION AND WINDAGE. The magnitude of bearing friction and windage (which may be consid- ered as independent of the load) is conveniently measured by driving the machine from an independent motor, the output of which may be suitably determined. See Sec. 94. (B) COMMUTATOR BRUSH FRICTION. 103 The magnitude of the commutator brush friction (which may be con- sidered as independent of the load) is determined by measuring the dif- ference in power required for driving the machine with brushes on and with brushes off (the field being unexcited). (O COLLECTOR-RING BRUSH FRICTION. 104 Collector-ring brush friction may be determined in the same manner as commutator brush friction. It is usually negligible. (D) MOLECULAR MAGNETIC FRICTION AND EDDY CURKI 105 These losses include those due to molecular magnetic friction and eddy currents in iron and copper and other metallic parts, also the losses due to currents in the cross-connections of cross-connected armatures. 106 In MACHINES these losses should be determined on open circuit and at a voltage equal to the rated voltage +/ r in a generator, and — / r in a motor, where / denotes the current strength and r denotes the int resistance of the machine. They should be measured at the correct speed and voltage, since they do not usually vary in any definite pro- portion to the speed or to the voltage. 107 NOTE. The TOTAL LOSSES in bearing friction and windage, brush fric- tion, magnetic friction and eddy currents can, in general, be determined by a single measurement by driving the machine with the field excited, either as a motor, or by means of an independent motor. 108 RETARDATION METHOD. The no-load iron, friction, and windage losses may be segregated by the Retardation Method. The generator should be brought up to full speed (or, if possible, to about 10 per cent above full speed) as a motor, and, after cutting off the driving power and excitation, frequent readings should be taken of speed and time, as the machine slows down, from which a speed-time curve can be plotted. A second curve should be taken in the same manner, but with full field ex- citation; from the second curve the iron losses may be found by subtracting the losses found in the first curve. 109 The speed-time curves can be plotted automatically by belting a small separately excited generator (say 1/10 kw.) to the generator shaft and connecting it to a recording voltmeter. (£) ARMATURE-RESISTANCE Loss. 110 This loss mav be expressed by p 7l r\ where r -resistance of one arma- ture circuit or branch, 7 = the current in such armature circuit or branch, and p-the number of armature circuits or branches. \SUARI>17.A1H>X *r/.A.s <» Hit-. .!./ 15 (F) COMULlAlulc. HklMi ASK 1'Kl %H COSTAO I RESISTANCE t.Qjg 111 It if desirable to point out that with carbon brushes these loesee may be considerable in low-voltage machines. (G) COLLBCt Mm MI - -Off. 112 .ii is usually negl , m machines of extremely low voltage or in unipolar machines. oss, 113 With separately excited field, the los« of power in the resistance of the . . alone -. --r shunt- or tenev field windings, however, the lots of power in the accompanying rheostat should also be included, the said rheostat being considered as an ossntisl pan of the machine, un< the method of Sec. 116 •• c the load losses cannot well be be considerable and. therefore, their 1 by oh - This can be done by operating me on short-circuit and at full-load current, that is. I called the " short -circuit core loss" With the low and great lag of current existing in this cav . : : . .• .-..:.. •' •...•-.• ; 117 core loss may. as an approximation, and in the absence of more accurate information, be assumed as the load loes. OF I>If s' OF APfAh (A) Pi HI . i <'t K.- 118 In DIRKI i i'i Kkt M ('OMMI i MIS.. M v le losses are: 119 : HKAKIM. IK M> WIM>A«.I Icasurement of Losses (<* 120 •• See Measurement of Losses (/> & 105. 121 « .\KM\II KI. i K LOSSE^ Measurement of Losses (£). 122 d. COMMUTATOR BKLSH FRICTION. See Measurement of Losses (B). 123 r COMMUTATOR, BlUSfl - IKKMMAMR. See Meas- urement of Losses (F). S< . Ill 124 /. FIELD Hxcn • v See Measurement of Losses (H). Sec. 113. 126 t. LOAD LOSSES -n of Losses (/). Sec. 1 126 NOTE. 6 and care losses in the armature or " armature losses"; 4 and t " commutator losses "; / " field losses/' (B) * RENT COM M INKS. 127 InAi.itKNv s. the losses a: 128 : Hi \KI-... !'. • Measurement of Losses (A). Sec. 129 6. Ro: »ss, measured with the machine at open circuit, the brushes on the commutator, and the field excited by alternating cur- rent when driving the machine by a motor. 130 This loss includes molecular magnetic fnction and eddy currents, caused by rotation through the magnetic field. /» r losses in cross-con- 16 STANDARDIZATION Kt'/.l // A.I.E.E. nections of cross-connected armatures, TV and other losses in armature- coils and armature-leads which are short-circuited by the brushes as these losses are due to rotation. 131 i. Ai IIKNMIM; or TRANSFORMER Loss. These losses are measured by wattmeter in the field circuit, under the conditions of test b. include molecular magnetic friction and eddy-currents due to the alter- nation of the magnetic field, TV losses in cross-connections of cross-con- nected armatures, Pr and other losses in armature coil and commutator leads which are short-circuited by the brushes, as far as these losses are due to the alternation of the magnetic flux. 132 The losses in armature-coils and commutator leads short-circuited by the brushes, can be separated in ft, and c, from the other losses, by run- ning the machine with and without brushes on the commutator. 133 d. 71/? Loss, other load losses in armature and compensating wind- ing and TV loss of brushes, may be measured by a wattmeter connected across the armature and compensating winding. 134 f. FIELD Ex< n AIK.N Loss. See Measurement of Losses (//), Sec. 113. 136 /. COMMUTATOR BRUSH-FRICTION. See Measurement of Losses (B), Sec. 103. (C) SYNCHRONOUS COMMUTATING MACHINES. 136 1. In DOUBLE-CURRENT GENERATORS, the efficiency of the machine should be determined as a direct-current generator, and also as an alter- nating-current generator. The two values of efficiency may be different, and should be clearly distinguished. 137 2. In CONVERTERS the losses should be determined when driving the machine by a motor. These losses are: 138 a. BEAR'ING FRICTION AND WINDAGE. See Measurement of Losses (A), Sec. 102. 139 b. MOLECULAR MAGNETIC FRICTION AND EDDY CURRENTS. See Meas- urement of losses (D) Sec. 105. 140 c. ARMATURE-RESISTANCE Loss. This loss in the armature is q 72r, where / = direct current in armature, r = armature resistance and q. a factor which is equal to 1.47 in single-circuit single-phase, 1.15 in double- circuit single-phase, 0.59 in three-phase, 0.39 in two-phase, and 0.27 in six-phase converters. 141 d. COMMUTATOR-BRUSH FRICTION. See Measurement of Losses (B), 103. 142 e. COLLECTOR-RING BRUSH FRICTION. See Measurement of Losses (C), Sec. 104. 143 /. COMMUTATOR, BRUSH AND BRUSH-CONTACT RESISTANCE Loss. See urement of Losses (F) Sec. 111. 144 g. COLLECTOR-RING BRUSH-CONTACT RESISTANCE Loss. See Measure- ment of Losses (C), Sec. 112. 145 h. FIELD-EXCITATION Loss. See Measurement of Losses (//), Sec. 109. 148 i. LOAD LOSSES. These can generally be neglected, owing to the ab- sence of field distortion. 147 3. i ICIENCY OF Two SIMILAR CONVERTERS may be determined by operating one machine as a converter from direct to alternating, and the other as a converter from alternating to direct, connecting the alter- nating sides together, and measuring the difference between the direct- current input and the direct-current output. This process may be modi- fied by returning the output of the second machine through two boosters into the first machine and measuring the losses. Another modification is to supply the losses by an alternator between the two machines, using potential regulators. (D) SYNCHRONOUS MACHINES. 148 In SYNCHRONOUS MACHINES the losses are: 149 a. BEARING FRICTION AND WINDAGE. See Measurement of Losses (A). Sec. inj 160 b. MOLECULAR MAGNETIC FRICTION AND HDDY CURRENTS. See Mea- surement of Losses (/>), Sec. 105. ,. Qt. STANDARi S Of THh. A I i i: 161 . A KM M t RE-RESISTANCE Lota. See Measurement of Lossn (£). Sec. 162 d COLLECTOR K ts<> BRUSSJ l 163 M TO*. RING BRI- 164 . Lots. Sec Measurement of Lossss (10. Sec. m 166 t L04 r« Measurement of Losses (/). Sec. Ill (fi) ?t nfcTioN APPARATUS. 166 I- >s APPARATUS the losses are: 167 • measured at open second.* l, rated frequency, and at rated voltage — / r. where ' - resistance of primar 168 •• LOSSES, the sum of the /' r losses in the primary and in the M-vondary windings of a transformer, or in the two sections of the isator or auto-transformer, where /-rated current in the coil or section of coil, and r » resistance. 169 i» LOSSES, i.r, eddy currents in the iron and especially in the ;-er conductors, caused by the current at rated load. For practical purposes they may be determined by uting the secondary of the transformer a; ssing upon the primary a voltage sufficient to send rated load current through the transformer. The loss in the trans- • these conditions, measured by wattmeter, gives the load losses + 7*r losses in .ary and secondary coils. 160 In CLOSED ' in TRANSFORMERS, either of the two circuits may be used as primary when determining the efficiency. 161 >• should be taken at the max- imum voltage for which the apparatus is designed, and with non-ind load, unless otherwise specified. ROTAR\ >s APPARATUS, or INDUCTION ' ' \- MINES 162 In ROTARY IMKTIION .\IT\K MIS. the losses are: 163 a. BEARING FRI .K. See Measurement of Losses (A). Sec. 164 b. Mi.- FKICIIOV n iron, copper and other metallic parts; also I- r losses which may exist in multiple- ngs. a and 6 together are determined by running the motor without load at rated voltage, and measuring the power input. 166 t. PRIMARY 7* R Loss, which may be determined by measurement of the current and the resist. i 166 d. SECOM»AK\ /•* K Loss, which may be determined as in the primary, when feasible; otherwise, as in squirrel-cage secondaries, this loss is meas- ured as part of t. 167 f LOAD LOSSES; i.r. molecular magnetic friction, and eddy currents ron, copper, etc.. caused by the stray field of primary and secondary currents, and secondary /» R loss when undeterminable under (4). These • losses may for practical purposes be determined by measuring the total power, with the rotor she: 1 at standstill and a current in the primary circuit equal to the primary energy current at full load. The loss in the motor under these conditions may be assumed 'to be equal to the load losses + P r losses in both primary and secondary coils. (G) \R OR A« NES. 168 In UNIPOLAR MAC MINES, the losses are: 169 (a) BEARING FRICTION AM> WIM.\..K See Measurement of Losaci (A). S< 170 MAGNETIC PRKU -s ^ CURRENTS. See Measurement of Losese (/ <>d. 171 u i ARMATURE-RESISTANCE LOSSES. See Measurement of Losese (£). Sec. 172 (d) COLLECTOR -BRUSH FRICTION. See Measurement of Losssi (Q. Sec. nn STANDARDIZATION RULES OF Till .\.I.E.E. 173 («) COLLECTOR BRUSH-CONTACT RESISTANCE. See Measurement of Losses (£), Sec. 1 174 ffl FIELD-EXCITATION. See Measurement of Lossr 176 (t) LOAD LOSSES. See Measurement of Losses (/), Sec. Ill (//) RECTIFYING APPARATUS, PULSATING-CURRENT GENERATORS. 176 This division includes: open-coil arc machines and mechanical and other rectifiers. 177 In RECTIFIERS the most satisfactory method of determining the efficiency is to measure both electric input ana electric output by wattmeter. The input is usually inductive, owing to phase displacement and to wave dis- tortion. For this reason the power factor and the apparent should also be considered, since the latter may be much lower than the true efficiency. The power consumed by auxiliary devices, such a synchronous motor or cooling devices, should be included in t input. 178 In Cos RRENT RECTIFIERS, transforming from constant poten- tial alternating to constant direct current, by means of constant-current transforming devices and rectifying devices, the losses in the transforming devices are to be included in determining the efficiency and have to be measured when operating the rectifier, since in this case the losses may be greater than when feeding an alternating secondary circuit. In constant- current transforming devices, the load losses may be considerable, and therefore, should not be neglected. 179 In OPEN-COIL ARC Y . the losses are essentially the same direct-current (closed coil) commutating machines. In this case, how- ever, the load losses are usually greater, and the efficiency should prefer- ably be measured by input- and output-test, using wattmeters for m ing'the output. 179a In alternating-current rectifiers, the output should, in general, be measured by wattmeter and not by voltmeter and ammeter, since owing to pulsation of current and voltage, a considerable discre; may exist between watts and volt-amperes. If, howev t-current and an alternating-current meter in the rectified circuit (either a volt- meter or an ammeter) give the same reading, the output ma ;sured by direct-current voltmeter and ammeter. The type of alternatin rent instrument here referred to should indicate the effective or root-of- mean-square value and the type of direct-current instrument the arith- metical mean value, which would be zero on an alternating-current circuit. (/) TRANSMISSION LINES. 180 The EFFICIENCY of transmission lines should be measured with non- inductive load at the receiving end, with the rated receiving voltage and frequency, also with sinusoidal impressed wave form, except where ex- pressly specified otherwise, and with the exclusion of transformers or other apparatus at the ends of the line. (/) PHASE-DISPLACING APPARATUS. 183 In SYNCHRONOUS PHASE-MODIFIERS and exciters of induction generators, the determination of losses is the same as in other synchronous machines. 184 In REACTORS the losses are molecular magnetic friction, eddy losses and 7* r loss. They should be measured by wattmeter. The losses of reactors should be determined with a sine wave of impressed voltage except where expressly specified otherwise. 185 In CONDENSERS, the losses are due to dielectric hysteresis and leak- age, and should be determined by wattmeter with a sine wave of voltage or by an alternating-current bridge method. 186 In POLARIZATION CELLS, the losses are those due to electric resistivity and a loss in the electrolyte of the nature of chemical hysteresis. These losses may be considerable. They depend upon the frequency, voltage and temperature, and should he de .-rminv 1 with • pt \vher- i ntheru S Of THR A./.R.R. 1) kl-:« ILLATION. (I) DEFINITIONS. 187 The .- .fa machine or apparatus in refard to some cha: v (such as terminal voltage, current or speed) of thai quantity from its normal value at rated load to that normal value. The term " regulation." therefore, has the same meaning as th< r emulation." occasionally used. 188 • - SM charactenstic quantity is intended to re- mum constant («.f.. constant voltage, constant speed, etc.) between rated load and no load, the regi the ratio of the maximum variation . the rated-load \ he no-load value. 189 tic quantity it intended to vary in .. t*tween rated load and no load, the regulai: thr the maximum variation from the specified condition to the rated-load va! 190 the variation (in voltage, current, speed, etc.) 1 load and no load is not sp< hould be assumed to be a simple linear relation; i.r.. one undergoing uniform variation between rated load and no load. 191 IK. The regulation of an apparatus may. therefore differ ac- cording to its qu. for use. Thus, the regulation of a compound- wound generator specified as a constant-potential generator, will be dif- it jM>ssesses when specified as an over -compounded generator. 192 i KM i AL ! s. the regulation is the ratio of the maximum difference of terminal voltage from the rated-load value (occur- ring within the range from rated load to open circuit) to the rated load 193 Ii. MINES, the regulation is the ratio of the maximum difference of current from the rated-load value (occurring he range from rated-load to short-circuit, or minimum limit of op< -ad current. 194 It >WBK APPARATUS, the regulation is the ratio of maxi- mum difference of power from the rated load value (occurring within the range of operation specified) to the rated power. 196 I: i ti> DIKK i CURRENT MOTORS and INDUCTION MOTORS the of the maximum variation of speed from its rated load value (occurring within the range from rated load to no-load) to the rated load speed. 198 The regulation of an induction motor re. not identical with which is the ratio of the drop in speed from syn- ch r« ronous speed. 197 I: SSFORMERS. the regulation is the ratio of the rise of secon<: voltage from rated non-inductive load to no-load (at constant primary impressed terminal voltage) to the secondary ten; .ige at rated load. 198 In OvER-Court' USES, the regulation is the ratio of the maximum difference in voltage from a straight line connecting the no-load and rated-load values of terminal voltage as function of the Toad current, to the rated-load terminal voltage. 199 . i-kv !>, N \\IOTORS. MOTOR-GENERATORS AND FREQO CONVERTERS, the regulation is the ratio of the maximum difference « minal voltage at the output side from the rated-load voltage, to the rated- load voltage on the output side. 200 In TRANSMISSION LINES. FEEDERS. ETC.. the regulation is the ratio of the maximum voltage difference at the receiving end. between rated non- inductive load and no load to the rated-load voltage at the receiving end (with constant voltage impressed upon the sending end). 201 In STEAM ENGINES, the regulation is the ratio of the maximum varia- tion of speed in passing slowly from rated-load to no-load (with constant steam pressure at the throttle) to the rated-load speed. For variation and pulsation see Sees. 59-64. 20 STANDARDIZATION RULE.^ Of 1'IIE A.I.E.E. 202 In a HVDKAI in ! t RHINE or OTHER WATER-MOTOR, the regulation is the ratio of the maximum variation of speed in passing slowly from rated- load to no-load (at constant head of water; i.e.. at constant difference of level between tail race and head race), to the rated-load speed, variation and pulsation see Sees. 59-64. 203 In a GENERATOR-UNIT, consisting of a generator united with a prime- mover, the regulation should be determined at constant conditions of the prime-mover; i.e pressure, head, etc. It includes the inherent speed variations of the prime-mover. For this reason the regu- lation of a generator-unit is to be distinguished from the regulation of either the prime-mover, or of the generator contained in it, when taken separately. (II) CONDITIONS FOR AND TESTS OP REGULATION. 204 SPEED. The REGULATION OF GENERATORS is to be determined at con- .t speed, and of alternating apparatus at constant impressed frequency. 205 N ON INDUCTIVE LOAD. In apparatus generating, transforming or t: mitting alternating currents, regulation should be understood to refer to non-inductive load, that is, to a load in which the current is in phase with the e.m.f. at the output side of the apparatus, except where expressly specified otherwise. 206 WAVK FORM. In alternating apparatus receiving electric power, regu- lation should refer to a sine wave of e.m.f., except where expressly speci- fied otherwise. 207 EXCITATION. In commutating machines, rectifying machines, and syn- chronous machines, such as direct-current generators and motors, alter- nating-current and polyphase generators, the regulation is to be. deter- mined under the following conditions: (1) At constant excitation in separately excited fields. (2) With constant resistance in shunt-field circuits, and (3) With constant resistance shunting series-field circuits; i.e., the field adjustment should remain constant, and should be so chosen give the required rated-load voltage at rated-load current. 208 IMPEDANCE RATIO. In alternating-current apparatus, in addition to the non-inductive regulation, the impedance ratio of the apparatus should be specified; i.e., the ratio of the voltage consumed by the total internal im- pedance of the apparatus at rated-load current, to its rated-load voltage. As far as possible, a sinusoidal current should be used. 209 COMPUTATION OF REGULATION. In synchronous machines the open- circuit exciting ampere-turns corresponding to terminal voltage plus arma- ture-resistance-drop, and the exciting ampere-turns at short-circuit for rated-load current should be combined vectorially to obtain the r ant ampere-turns, and the corresponding internal e.m.f. should be taken from the saturation curve. 1C. INSULATION. (I) INSULATION RESISTANCE. 210 INSULATION RESISTANCE is the ohmic resistance offered by an insulating coating, cover, material or support to an impressed voltage, tending to produce a leakage of current through the same. 211 OHMIC RESISTANT K AND DIKLECTRIC STRENGTH. The ohmic resistance of the insulation is of secondary importance only, as compared with the dielectric strength, or resistance to rupture by high voltage. Since the ohmic resistance of the insulation can be very greatly increased by baking, but the dielectric strength is liable to be weakened thereby, it is preferable to specify a high dielectric strength rather than a high insulation resist- ance. The high-voltage test for dielectric strength should always be ap- plied. 212 RECOMMENDED VALUE OF RESISTANCE. The insulation resistance of completed apparatus should be such that the rated terminal voltage of the apparatus will not send more than j QOO 000 °* the ratcd*loai»r. : he dielectric strength of an mtulating «*ll. cwating cover or path it mea»>: • -»e voltage which must be applied to ..r.ir: tc •-!!• et a !. .;u;. •!•..• •'. ham ••.,.•• .. - 216 UN :• i ... . TRST V The test voltage which should be a} insulation for commer- normal operating v c of the service in wh used, and the scve: i« mechanical and elect r h it may be subjected. 1 .;c> and other con which arc re. <-d have been determined as reasonable and proper t:reat ma cases and are proposed for general adoption. ;LTAGES. The following voltages are recommended for testing all apparatus, lines and cables, by a continued application for one minute. The test should be with alternating voltage having a (or root mean square referred to a sine wave of voltage) given in the table, and preferably for tests of alternating apparatus at the normal frequency of the apparatus. lUud Terminal Volu«e o( lUt«d Output. T«*un* Votu«* 220 Not exceeding 400 •. icr 10 kw 1.000 volts kw. and ..-.<- 1.500 400 and over, but less than 800 volts. . Under 10 kw and over 2.000 MX) - • 1.200 ' 3.500 •0 • - 2,500 ~ »H) 2.500 ' * Any Double the normal rated • 221 ICxcBPTios.— TtANSFORMiBS. Transformers having primary pressures of from 560 to 5,000 volts, the secondaries of which at- nected to consumption circuits, should have a testing voltage of 10.000 volts, to be applied bctw. ry and secondary windings, and also between the primary winding and the core. 222 KXCEFTION.— FIELD ---sts for field windings should be based on the rated voltage of the exciter and the rated output of the machine of which the coils are a part. Field windings of synchronous motors and converters, which are to be started by applying alter: current to the armature when the field is not excited and when a high voltage is induced in the field windings, should be tested at 5.000 volts. STANDARDIZATION RULES Ol- Till: ,!././ 223 RATED TERMINAL VOLTAGE. — DEFINITION. The rated terminal voltage of circuit in the above table, means the voltage between the conductors of the circuit to which the apparatus to be tested is to be connected, — for instance, in three-phase circuits the delta voltage should be taken. In the following specific cases, the rated terminal voltage of the circuit is to be determined as specified in ascertaining the testing voltage: 224 (a) TRANSFORMERS. The test of the insulation between the primary and secondary windings of transformers, is to be the same as that between the high-voltage windings and core, and both tests should be made simul- taneously by connecting the low-voltage winding and core together during the test. If a voltage equal to the specified testing voltage be induced in the high-voltage winding of a transformer it may DC used f«>r insulation I instead of an independently induced voltage. These tests should IK- made first with one ena and then with the other end of the high-tension \\mdine connected to the low-tension winding and to the core. 226 (6) CONSTANT-CURRENT APPARATUS. The testing voltage is to be based upon a rated terminal voltage equal to the maximum voltage which may exist at open or closed circuit. 226 (c) APPARAH - IN SERIES. For tests of machines or apparatus to be operated in series, so as to employ the sum of their separate voltages the testing voltage is to be based upon a rated terminal voltage equal to the sum of the separate voltages except where the frames of the machines are sepa: ulated, both from the ground and from each other, in which case the test for insulation between machines should be based upon the voltage of one machine, and the test between each machine and ground to be based upon the total voltage of the series. (B) METHODS OF TESTING. 227 CLASSES OF TESTS. Tests for dielectric strength cover such a wide range in voltage that the apparatus, methods and precautions which are essential in certain cases do not apply to others. For convenience, the tests will be separated into two classes: 228 CLASS 1. This class includes all apparatus for which the test voltage does not exceed 10 kilo volts, unless the apparatus is of very large static capacity, e.g., a large cable system. This class also includes all apparatus of small static capacity, such as line insulators, switches and the like, for all test voltages. 229 METHOD OF TEST FOR CLASS 1. The test voltage is to be continuously applied for the prescribed interval, — (one minute unless otherwise speci- fied). The test voltage may be taken from a constant-potential source and applied directly to the apparatus to be tested, or it may be raised gradually as specified for tests under Class 2. 230 CLASS 2. This class includes all apparatus not included in Class 1. 231 METHOD OF TEST FOR CLASS 2. The test voltage is to be raised to the required value smoothly and without sudden large increments and is then to be continuously applied for the prescribed interval, — (one minute, unless otherwise specified), and then gradually decreased. 232 CONDITIONS AND PRECAUTIONS FOR CLASS 1 and CLASS 2. The follow- ing apply to all tests: 233 The WAVE SHAPE should be approximately sinusoidal and the apparatus in the testing circuits should not materially distort this wave. 234 The SUPPLY CIRCUIT should have ample current-supply capacity so that the charging current which may be taken by the apparatus under test will not materially alter the wave form nor materially affect the test volt- age. The circuit should be free from accidental interruptions. 236 RESISTANCE OR INDUCTANCE in series with the primary of a raising transformer for the purpose of controlling its voltage is liable seriously to affect the wave form, thereby causing the maximum value of the volt- age to bear a different and unknown ratio to the root mean square value. This method of voltage adjustment is, therefore, in general, undesirable. It may be noted that if a resistance or inductance is employed to limit the current when burning out a fault, such resistance or inductance should be short circuited during the regular voltage test. STANDARDIZATION HI /./-.N • •/• //// i / 23 236 The Kit I.AIIUN under test should be in normal condition as to dry- ness and the temperature should when possible be that reached ia normal Njrvt <- 237 \ i-i'i i IONAL CONDITIONS AND PRECAUTIONS FOR CLASS 2. The following :u and precaution*, in addition to the foregoing, apply to tests of apparatus included in Class 2. 238 SUDDEN INCREMENT or '1 > OLTAGE on the apparatus under teat should be avoided, particularly at high voltages and with apparatus having considerable capacity, as a momentarily excessive rise In testing voltage will result. 239 Si OLTAGE of the circuit supplying the •>* the test should be avoided as they are likely to set up 240 <>.\* in •. :ig the test voltage are es- sential in or urtou* high frems ir banco* from 1 by a small water rheostat. :ig may occur, causing high-frr< turhancet which should be ully av«*: 241 TKANHFORMBR < c transformers, the low- voltage .ibly be connected to the core and to the ground when the high-voltage test i> bring made, in he stress from low-voltage D h would otherwise result through condenser action. The various terminals of each winding of the high-tension trans- former • should be c -get her during the test in order to prevent undue stress on the insulation between turns or sections of the winding in case the high-voltage test causes a break-down. (O METHODS FOR MBA«I-KIM. int. n \GB. 242 FOR MK\M KIM. no ii \«iB, two instruments ar« in common use. (1) the spark gap and .It meter. 243 1 '. so that it will break down with a certain pred< and is connected in parallel with the in- sulal ige applied to the insu. n the break-down voltage of the spark gap. A given setting of the spark gap is a measure of one definite voltage, and. as its operatic- upon t: vim value of the voltage wave. rm and is a limit on the maximum stress to which the The spark gap is not conveniently adapted low voltages. 244 >;ap may be set for th v apparatus adjusted to give a voltage at The spark gap should then be adj 'age. and the auxiliary apparatus >gc of the former breakdown, which be the assumed voltage for the test. This voltage is to be maintained for the required interval. 246 T new sewing needles, supported axially at the ends of 'or* which are each at least twice the f the ga; should be no extraneous body near the gap . radius <•: 'able of approximate striking dis- This table should be used in connection with tests n. c spark-gap methods. 246 A N • • \ I M K of about one-half ohm per volt should be inserted in series with each terminal of the gap so as to keep the discharge current between the limits of one-quarter ampere and 2 amperes. The pur- pose of the resistance is to limit the current in order to prevent the surges which might otherwise occur at the time of break-down. 247 J. The VOLTMETER gives a direct reading, and the different values of the voltage can be read during the application and duration of the test, suitable for all voltages, and does not introduce disturbances into the test -.lit. 248 In VOLTMETER MEASUREMENTS, the voltmeter should, in general, derive its voltage from the high-tension testing circuit either directly or through 24 STANDARDIZATION RULES Ol I III: ,!././ an auxiliary ratio transformer. It is permissible, however, to measure the voltage at other places, — for example, on the primary of the transf< provided the ratio of transformation does not materially vary during the test; or that proper account is taken thereof. 249 SPARK GAP tND VOLTMETER. The spark gap may be employed as a check upon the voltmeter used in high-tension tests in order to determine the transformation ratio of the transformer, the variation from th wave form and the like. It is also useful in conjunction with voltmeter measurements to limit the stress applied to the insulating n (D) APPARATUS FOR SUPPLYING TEST VOLTAGE. 260 The GENERATOR OR CIRCUIT supplying voltage for the test should have ample current carrying capa* hat the current which be taken for charging the apparatus to be tested will not mau-ri.-ilh the wave form nor otherwise materially change the voltage. The TESTING TRANSFORMER should be such that its ratio of trans- formation does not vary more than 10 per cent when delivering the charg- ing current required by the apparatus under test. (This may be deter- mined by short-circuiting the secondary or high voltage winding of the test- ing transformer and supplying 1/10 of the primary voltage to the pr under this condition. The primary current that flows under this condition is the maximum which should be permitted in regular dielectric test.) 261 The VOLTAGE CONTROL may be secured in either of several inch in order of preference, are as follows: 262 1. By generator field circuit. 263 2. By magnetic commutation. 264 3. By change in transformer ratio. 266 4. By resistance or choke coils. 266 In GENERATOR VOLTAGE CONTROL, the voltage of the generator si preferably be about its approximate normal rated load value when the lull testing voltage is attained, which requires that the ratio of the r transformer be such that the full testing voltage is reached when the gen- erator voltage is normal. This avoids the instability in the generator which may occur if a considerable leading current is taken from it when it has low voltage and low field current. 267 In MAGNETIC COMMUTATION, the control is effected by shunting the mag- metic flux through a secondary coil so as to vary the induction through the coil and the voltage induced in it. The shunting should be effected smoothly, thus avoiding sudden changes in the induced voltage. 268 In TRANSFORMER VOLTAGE CONTROL, by change of ratio, it is neces- that the transition from one step to another be made without inter- ruption of the test voltage, and by steps sufficiently small to prevent surges in the testing circuit. The necessity of this precaution is greater as the inductance or the static capacity of the apparatus in the t circuit under test is greater. 269 When RESISTANCE COILS OR REACTORS are used for voltage control, it is desirable that the testing voltage should be secured when the controlling resistance or reactance is very nearly or entirely out of circuit in order that the disturbing effect upon the wave form which results may be negli- gible at the highest voltage. F. CONDUCTIVITY 260 COPPER. The conductivity of copper in annealed wires and in electric cables should not be less than 98 per cent of the Annealed Copper Stand- ard, and the conductivity of hard-drawn copper wires should not be less than 95 per cent of the Annealed Copper Standard. The Annealed Copper Standard represents a mass-resistivitv of 0.153022 ohm per meter- gram at 20 deg. cent, or 873.75 ohms per mile-pound at 20 deg. cent.; or using a density of 8.89, a volume-resistivity of 1.72128 microhm-cm., or microhms in a cm. cube, at 20 deg. cent, or 0.67767microhm-inch at 20 dee. cent. STANDARDISATION RULES (Jf- Ulh. A I /UL RISB OF TEMPERATURE. (I) MEASUREMENT OP TEUPERATl (A) METHODS. 361 There are two methods in common use for determining the hse tn tern- per.* by thermometer, and (2) by increase in resistance of an r! 262 .Mowing precautions should be obecnred in the u*c of thermometer*: -• •< rmometers indicating the room temper- •hou tn thermal r . heated bodies, or >porary fluctuations of temper- be used. In using the thermometer by applying it i<> a heated part, care should be taken so to prote as t • radiation (rum it. and. at the tame lime, not to interfere mal radia the part to which it is applied. 264 icrmometer : . applied to the free surface of a ma- .at the bulb of the thermometer should be covered A convenient pad may be formed of cotton waste in a shullo box about one and a half inches in diameter. ugh a .slot in the • !-• tn which the thermometer bulb is inserted the thermometer tend;> .in the n .1 heat from the surface to which the thermometer is applied. 266 The resistance may be measured louble bridge, method. If a ist be as »pper may be takei "i. 00394 per deg. cei at 20 deg. cent., or 0.00438 :i and at • holds for average com- :t the 1-05. coefficient should be taken, ai explanation and discussion of the temperature The • rise may be «i 1) by dividing the per cent increase e coefficient for the -. it ure expressed in per cer. resistance :iperature legrees cent., and then dividing ihe pmdt: d absolute zero temperature of resistance " and is given in the last :rnn of the table in Appen -»r average commercial a**t*lt4 copper S). 266 .•;.' COMPARISON or METHODS. In electrical conductors, the rise of tem- perature should be determined by t: ise of resistance where prac- ticable. Temperature elevations measured in this way are usually in ex- cess of temp* :evations measured by thermometers. In very low resistance circuits, thermometer measurements are frequently more relt- abl< isurements by the resistance method. Where a thermometer applied to a coil or winding, indicates a h»»jher temperature ele-. t> that shown by resistance measurement, the thermon .ilion should be accepted. (B) NORMAL CONDITIONS FOR TESTS. 267 1. DURATION OP TESTS. The temperature should be measured after a run of sufficient duration for the apparatus to reach a practically constant temperature. This is usually from 6 to 18 hours, according to the wie and construction of the apparatus It is permissible, however, to shorten the time of the lest by running a lesser time on an overload in current and voltage, then reducing the load to normal, and maintaining it thus until the temperature has become constant. 268 2. ROOM TEMPERATURE. The rise of temperature should be referred to the standard condition of a room temperature of 25 deg. cent. 269 TEMPERATURE CORRECTION. If the room temperature during the teat STANDARDIZATION RULES OF THE A.I.E.E. differs from 25 dcg. cent., correction on account of difference in resistant should be made by changing the observed rise of temperature by one-half per cent for each degree centigrade. Thus with a room temperature of 35 deg. cent., the observed rise of temperature has to be decreased by 5 per cent, and with a room temperature of 15 deg. cent., the observed rise of temperature has to be increased by 5 per cent. In certain casrs. such as shunt-field circuits without rheostat, the current strength will he changed by a change of room temperature. The heat-productioi dissipation may be thereby affected. Correction for this should be made by changing the observed rise in temperature in proportion as the loss in the resistance of the apparatus is altered owing to the difference in room temperature. 270 3. BAROMETRIC PRESSURE. VENTILATION. A barometric pressure of 760 mm. and normal conditions of ventilation should be considered as standard, and the apparatus under test should neither be exposed to draught nor enclosed, except where expressly specified. The barometric pr« needs to be considered only when differing greatly from 760 mm. 271 BAROMETRIC PRESSURE CORRECTION. When the barometric pressure differs greatly from the standard pressure of 760 mm. of mercury. high altitudes, a correction should be applied. In the absence of more i accurate data, a correction of one per cent of the observed rise in tempera- ture for each 10 mm. deviation from the 760-mm. standard is recommended. For example at a barometric pressure of 680 mm. the observed rise of tem- perature is to be reduced by •• 8per O (II) LIMITING TEMPERATURE RISE. 272 GENERAL. The temperature of electrical machinery under regular vice conditions, should never be allowed to remain at a point at which permanent deterioration of its insulating material takes place. 273 LIMITS RECOMMENDED. It is recommended that the following maximum values of temperature elevation, referred to a standard room temperature of 25 degrees centigrade, at rated load under normal conditions of ven- tilation or cooling, should not be exceeded. (A} MACHINES IN GENERAL. 274 In commutating* machines, rectifying machines, pulsating-current erators, synchronous machines, synchronous commutating machines and unipolar machines, the temperature rise in the parts specified should not exceed the following: 276 Field and armature, 50 deg. cent. 276 Commutator and brushes, by thermometer, 55 deg. • 277 Collector rings, 65 deg. cent. 278 Bearings and other parts of machine, by thermometer, 40 deg. cent. 279 (B) ROTARY INDUCTION. APPARATUS. The temperature rise should not exceed the following: 280 Electric circuits, 50 dcg. cent., by resistance. 281 Bearings and other parts of the machine 40 deg. cent., by thermometer. 282 In squirrel-cage or short-circuited armatures, 55 deg. cent., by thermo- meter, may be allowed. (O STATIONARY INDUCTION APPARATUS. 283 a. TRANSFORMERS FOR CONTINUOUS SERVICE. The temperature rise should not exceed 50 deg. cent, in electric circuits, by resistance; ami in other parts, by thermometer. 284 b. TRANSFORMERS FOR INTERMITTENT SERVICE. In the case of trans- formers intended for intermittent service, or not operating continuously at rated load, but continuously in circuit, as in the ordinary case of lighting transformers, the temperature elevation above the surrounding air-tem- perature should not exceed 50 deg. cent., by resistance in electric circuits and by thermometer in other parts, after the period corresponding to the term of rated load. In this instance, the test load should not be applied \NDARDIZAT10N RULES OF THh A / E £. 27 until the transformer baa beta • for a sufficient time to attain the • ire elevation due to core lota. With transformers for com- mercial lighting, the .!-. -he rated-load test may be taken as three hours, unless otherwise specified. KEACTOH ^REGULATORS. EJectnccir by resistance and other parts by thermometer. 60 deg. cent. d. l.MM.H Art-Ai. urge generators, motor*, transfonnert. or other apparatus in which reliability and reserve overload capacity are important, are frequently specified not to rise in temperature more than 40 da*. i load and 56 deg. cent, at rated overload !•.:». how- it narily undesirable to specify lower temperature elevations than at rated load, measured aa ar> (£>) RBEOSI 287 HBATIBS and othr: hermal apparatus, no corn- bus' nflammable part or material, or portion liable to come in •nth such material, should rise more than 50 deg. cent, above the surrounding air under the service conditions for which it is designed. 188 j 1' \KTHOF RHEOSTATS. Parts of rheostats and similar apparatus nung in temperature, under the specified service conditions, more than 60 deg. ontain any combustible material, and should be arranged hat neither they, nor the hot air issuing from them, can come in contact with combustible material. l.i MI is RECOMMENDED IN SPECIAL CASKS. 269 «; HKAT KEM-I. vi apparatus in which the insu- lating materials have special heat-resisting qualities, a higher temperature elevation is permtssi 290 .V iUi.ti AIR TEMPER AT t: RK. In apparatus intended for service in places of abnormally high temperature, a lower temperature elevation should be specif i 291 c. APPARATUS SUBJECT TO OVERLOAD. In apparatus which by the service may be exposed to overload, or is to be used in very high voltage a small- temperature is desirable than in apparatus not liable to overloads or in low -voltage apparatus. In ap- itus built for conditions of limited space, as railway motors, a higher f temperature must be allowed. 292 d. APPARATUS FOR IMI-KMIIII M SKKVKK In the case of apparatus r. except railway motors, the temperature elevation which is attained at the end of the period corresponding to the he values specified for machines in general. In such apparatus, including railway motors, the temperature a lion should be measured after operation, under as nearly as pos- sible th' ns of service for which the apparatus is intended, and ! be specified. H *t 'VKKI.OAD CAP.V 293 I'nuokM\st H \\IIH OVERLOAD. AH apparatus should be able to carry the overload hereinafter specified without sen ng. spark* ss. etc.. and with an additional temperature rise not •leg. cent., above those specified for rated loads, the overload being applied after the apparatus has acquired the temperature corre- sponding to rated load continuous operation. Rheostats to which no temperature nse limits are attached are naturally exempt from this addi- tional temperature rise of 15 deg. cent, under overload specified in these rules. 294 N . - K M v .id guarantees should refer to normal con- ns of operation regarding speed, frequency, voltage, etc.. and to non- inductive ci.t n alternating apparatu where a phase dis- placement is inherent in the apparatus. STANDARDIZATION Rl'Ll- 295 OVERLOAD CAPAI in; - KKCOMMENDED. The following overload capaci- are recommended: 296 a. GENERATORS. Direct-current generators and alternating-current generators, 25 per cent for two hou 297 />. MOTORS. Direct-current motors, induction motors and synchronous motors, not including railway and other motors intended for intermittent ce, 25 per cent for two hours, and 50 per cent for one minute. 298 c. CONVERTERS. Synchronous converters, 25 per cent for two hours, 50 per cent for one-half hour. 299 RMERS AND RECTii it K-. Constant-potential transformers and rectifiers, 25 per cent for two hours; except in transformers connected to apparatus for which a different overload is guaranteed in which case the same guarantees shall apply for the transformers as for the apparatus connected thereto. 300 e. EXCITERS. Exciters of alternators and other synchronous machines, 10 per cent more overload than is required for the excitation of the syn- chronous machine at its guaranteed overload, and for the same period of time. All exciters of alternating-current, single-phase or polyphase gen- erators, should be able to give at their rated speed, sufficient voltage and current to excite their alternators, at the rated speed, to the full-load ter- minal voltage, at the rated output in kilovolt-amperes and with 50 per cent power factor. 301 /. A CONTINUOUS-SERVICE RHEOSTAT, such as an armature- or field- regulating rheostat, should be capable of carrying without injury for two hours, a current 25 per cent greater than that at which it is rated. It should also be capable of carrying for one minute a current 50 per cent greater than its rated load current, without injury. This excess of ca- pacity is intended for testing purposes only, and this margin qf capacity should not be relied upon in the selection of the rheostat. 302 g. An INTERMITTENT SERVICE OR MOTOR-STARTING RHEOSTAT is used for starting a motor from rest and accelerating it to rated speed. Under ordinary conditions of service, and unless expressly stated otherwise, a motor is assumed to start in fifteen seconds and with 150 per cent of rated current strength. A motor-starter should be capable of starting the motor under these conditions once every four minutes for one hour. 303 (a) This TEST may be carried out either by starting the motor at four-minute intervals, or by placing the starter at normal tem- perature across the maximum voltage for which it is marked, and moving the lever uniformly and gradually from the first to the last position during a period of fifteen seconds, the current being maintained substantially constant at said 50 per cent excess, by introducing resistance in series or by other suitable means. 304 (6) OTHER RHEOSTATS FOR INTERMITTENT-SERVICE are employed under such special and varied conditions, that no general rules are applicable to them. %. III. VOLTAGES AND FREQUENCIES. A. VOLTAGES. 306 DIRECT-CURRENT GENERATORS. In direct-current, low-voltage gener- ators, the following average terminal voltages are in general use and are recommended: 125 volts. 250 volts. 600 volts. 306 LOW-VOLTAGE CIRCUITS. In direct-current low-voltage circuits, the following terminal voltages are in general use and are recommended: 115 volts. 230 volts. 550 volts. In alternating-current low-voltage circuits, the following terminal volt- ages are in general use and are recommended. 110 volts. 220 volts. 440 volts. 550 volts. STANDAKDIZATJO19 RULES OP Tilt. A I KB. 307 I'kiuAKv I»IM» In Alternating-current. I, Bfiflsfjry*diitnbui u. an average voltage of 2.200 volts. with step-down transformer ratios I/ 10 and 1/30. is in general use. and U ftOOOUBMdtd* 308 TRANSMISSION alternating -current constant -potential :i emission 4get are recommended. «,60«' (100 33.000 44.000 ttA.OOOHM.000 110.000 109 i ORMRR K • commended that the standard transformer •§ should be such as to transform between the standard voltage* above named. usually be an exact multiple of 6 or 310 KAM.I \'.i In alter nat systems, a range of terminal voltage should be provided from rated voltage at no load to 10 per <• »p in transmission. If a greater range than ten per cent is specified, the generator should be considered as special. H FRKQUENCi 311 In ALTERNATING-CURRKS ITS. the* following frequencies are. standar 25 cycles 60 cycles 312 These frequencies are already in extensive use and it U deemed ad- visable to adhere to them as closely as possible. IV. GENERAL RECOMMENDATIONS. 313 NAME PLATES.* All electrical apparatus should be provide*! with a name plate giving the manufacturers' name, the voltage and the current in amperes for which it is designed. Where practical) watt capacity, character of current, speed, frequency, type, designation and serial num- ber should be added. 314 DIAGRAMS OP Coxst All electrical apparatus when leaving the factory should be accompanied by a diagram showing the electrical con- nections and the relation of the different parts in sufficient detail to give the necessary information for proper installation. 316 RHEOS rheostat should be clearly and permam marked with the voltage and amperes, or range of amperes, for which 15 design- 316 COLORED I .in-. When using colored indicating lights on switch-boards, red should denote danger such as " switch closed." or "; green should denote safety, such as " switch open." circuit ii 317 When white lights are used a lig^ht turned on should denote danger, such as " switch closed " or " circuit alive "; while the light out should denote safety, such as " switch open." or Low-effi- ciency lamps should be used on account of their lesser liability to acci- dental burn 318 The use of colored lights is recommended, as safer than white lights. 319 GROUNUING METAL WORK. It is desirable that all metal work near high potcnti.. be grounded. 320 .DEVICES. The following definitions are recommended. 321 KEAEER is an apparatus lor breaking a circuit at the highest current which n may be called upon to carry. 322 h. AIM-.. s an apparatus designed to open a circuit only when carrying little or no cur: 323 c. An AUTOMATIC CIRCUIT- BREAKER is an apparatus for breaking .. • automatically under an excessive strength of current. It should be capable of breaking the circuit repeatedly at rated voltage and at the maximum current which it may be called upon to carry. STANDARDIZATION RULES Ol 1 III: A.I.E.E. V. APPENDICES AND TABULAR DATA. APPENDIX A. NOTATION. The following notation is recommended: Name of Quantity Symbol Unit 324 Voltage, e.m.f., potential difference E, e, volt Current / ». ampere Resistance R. r. ohm Reactance A", x. Impedance /. *, Admittance Y, y, mho Conductance G, t, Susceptance H. o, Power P, p, watt Capacity ( '. < . farad Inductance L, henry Magnetic flux maxwell Magnetic density gauss Magnetic force //. gilbert per cm. Length L, I, cm. or inch Mass M, m, gm. or Ib. Time T, t, second or hour Em, Im and Bm should preferably be used for maximum cyclic values, e, i and p for instantaneous values, E and / for r.m.s. values (see Sec. 5g.) and P for the average value or effective power. These distinc- tions are not necessary in dealing with continuous-current circuits. Vector quantities are preferably represented by bold face capitals. APPENDIX B.— RAILWAY MOTOR (I) RATING. 325 INTRODUCTORY NOTE ON RATING. Railway motors usually operate in a service in which both the speed and the torque developed by the motor are varying almost continually. The average requirements, however, during successive hours in a given class of service are fairly uniform. On account of the wide variation of the instantaneous loads, it is impracticable to assign any simple and definite rating to a motor which will indicate accurately the absolute capacity of a given motor or the relative capacity of different motors under service conditions. It is also impracticable to select a motor for a particular service without much fuller data with regard both to the motor and to the service than is required, for example, in the case of stationary motors which run at constant speeds. 326 SCOPE OF NOMINAL RATING. It is common usage to give railway motors a nominal rating in horse power on the basis of a one-hour test. As above explained, a simple rating of this kind is not a proper measure of service capacity. This nominal rating, however, indicates approximately the maximum output which the motor should ordinarily be called upon to develop during acceleration. Methods of determining the continuous capacity of a railway motor for service requirements are given under a subsequent heading. 327 The NOMINAL RATING of a railway motor is the horse-power output at the car-axle, that is, including gear and other transmission losses, which gives A rise of temperature above the surrounding air (referred to a room temperature of 25 deg. cent.) not exceeding 90 deg. cent, at the commutator and 75 deg. cent, at any other part after one hour's con- tinuous run at its rated voltage (and frequency, in the case of. an alter- nating-current motor) on a stand, with the motor-covers removed, and with natural ventilation. The rise in temperature is to be determined by thermometer, but the resistance of no electrical circuit in the motor shall increase more than 40 per cent during the test. \M>.\Rl>l/..\llt>S RULES OF TV/A A I E.E. (II) SELECTION Of MOTOR FOR SPECIFIED SERVICE. 328 GENERAL REQUIREMEMTS. The futubthiy of • railway motor for a specified service depends upon ibe following considerations: 329 ; Mechanical ability to develop the requisite torque and its speed- torque c : 330 fc. / te successfully the current A»mftMH 331 t Ahihty to ojK-rMr in service without occasioning a l endangr 332 | operating conditions which are importan ,f a motor include the weight of load, the schedule speed, the -I. stance between stops. tl. n of stops, the of acceleration and of braking retardation, the grades and the curve*. with these data at hand, t) re required of the motor may be determined, provided the srr mis are within th- •petd-toraue curve of the motor. These outputs may be nip rusted Of curves givin* the instantaneous values of current and of nt be applied to the motor -» may b< line, hut they are usually - 1 only for ft O average or typical run. which it fairly representative of the conditions of service. To determine whether the motor has sufficient capacity to per- form the service safely, further tests or investigations must be made. 333 IK is M The capacity of a railway -he necessary output may be determined by measurement of its temperature after it has reached a maximum in ser- • a running test cannot be made under the actual conditions of service, an t lest may be made in a typical run back and forth, under such conditions of schedule speed, length of run. rate of acceleration. • the test cycle of motor losses and conditions of ventilation are essentially the same as would be o1 a the specified serv 334 MKIH-' v« \\\ ui in SERVICE REQUIRE- • is not convenient to test motors under actual service •is or in an equivalent typical run. recourse may be had to one of the two following methods of determining temperature rise now in general use: 336 1 in !.os,. \PAcm ri-RVB*. The heat de- railway motor is carried partly by conduction through the several parts rough the air to the motor-frame whence it is distributed to the outside air. As the temperature of the several parts is thus dependent not only upon their own internal losses but also upon the temperature of neighboring parts, it becomes necessary to determine accurately the actual value and distribution of losses in a railway motor for a given service and reproduce them in an equivalent run. The results of a series of typical runs expressed in the form of thermal capu • the relation between degrees rise per watt loss in the armature and in the field for all ratios of losses between them met with in the commercial application of a given motor. 336 1 his method consists, therefore, in calculating the several internal motor losses in a specified scr\ nperature rise with these losses from thermal capacit -:g the degrees rise per watt loss as obtained in experimental track tests made under the same conditions of ventilation. 337 The following motor losses cause its heating and should be carefully determined for a given s* on the basis of their mean horizontal can hut tn c • lamps in which the . lumii inter, lie comp.i: tie based on • .'. flui ligl lumens, or on their mean spherical candle-power. 362a LIFE TESTS. Similar filaments may be assumed to operate at the when their lumens per watt consumed are the i tests are compar.t similar conditions as to filam« :.i lures. 363 The SPHERICAL REDLCTION-PACTOR of a lamp mean spherical candle- pox- me 364 x of light in lumens < y a lamp • 4 V X mean M! candle-power X spherical redu 366 The- Si K should only be used when properly determined : 1 characteristics of cacn lamp. The spherical reduction-factor permits of substantially accurate com- parisons being made between the total lumens, or mean spherical candle- powers of different types of incandescent lamps, and may be used in the absence of proper facilities for direct measurement of the total lu- •is, or mean spherical candle-po. 366 " RBAI K." Where standard photometric measurements are impracticable, approximate measurements of illmmnants such as street lamps may be made by comparing their " reading distances. by determining alternately the distances at which an ordinary size of reading print can just be read, by the same person or persons, when all other light is screened. The angle below the horizontal at which the meas- u-nt is made should be specified when it exceeds 15 degrees. Reading- distance methods usually involve the comparison of very faint illuminations and hence the results may be seriously affected by th< • effect. 367 In COMPARING DIFFERES SOURCES not only should their candle-power be compared, but al lalive form, brightness, dis- tribution of illumination and character of light. 367s The following symbols are recommended in connection with photometry: Pholonwlnc magnitude Symbol Intensity of light. / International candle. Luminous flux. Lumen Illumina* £ Lumen/cm.1, foot-candle. /? Foot-candle. Brightness. * :n.« Qi: 0 Candle. Lighting. L Lumen-second, lumen-boor. AI < 1). SPARKING DISTANCES. 368 Table of Sparking Distances in Air between Opposed Sharp Needle* Points, for Various Root-Mean-Sauare Sinusoidal Voltages, in indie* nnd in centimeters. The table applies to the conditions specified in Sees. STANDARDIZATION RULES OF THE A.I.E.E. 369 UH I:;, he. ;ance. Cm. KilovolU M.S. (I •J'J.'i 0.67 1 10 0.47 1.19 150 0.725 1.84 Kill 1.0 •2 54 170 l :< 3.3 180 1.625 4.1 190 2.0 5.1 •joo 2.45 6.2 210.. .. 2.95 7.5 220 3.55 9.0 230 4.65 11.8 240 5.85 14.9 250 7.1 18.0 260 8.35 21.2 270 9.6 24.4 2 so 27.3 '-Mm . 11.85 30.1 300.. 12.90 32.8 Distance. KilovolU R M S. 5... 10... 20... 25... 30... 35... 40... 45... 50... 60... 70... 80... 90... 100... 110... 120. . . 130. APPENDIX E. TEMPERATURE COEFFICIENT OF COPPER 360 The fundamental relation between the rise of temperature and the increase of resistance of copper may be expressed thus: Inchet Cm. .13.95 35.4 .15.0 38.1 .16.05 40.7 .17.10 43.4 .18.15 46.1 .19.20 48.8 51.4 54.1 •2-2 :<:> 56.8 59.4 .24.45 62.1 .25.50 64.7 ,26.80 67.3 .27.50 69.8 28.50 72.4 .29.50 74.9 30.50 77 4 where Rt is the resistance at any temperature / deg. cent.; #/, is the re- sistance at any " initial temperature " (or " temperature of reference ") ti deg. cent.; and Ott is the temperature coefficient from and at the initial temperature t\ deg. cent. Obviously the temperature coefficient is dif- ferent for different initial temperatures, and this variation is shown in the horizontal rows of the table below. Furthermore, it has b that the temperature coefficient is different for different conduct! and that the temperature coefficient is substantially proportional to the conductivity. The results of this simple law are shown by t: columns of the table below. TEMPERATURE COEFFICIENTS OP COPPER FOR DIFFERENT INITIAL TEMPERATURES AND DIFFERENT CONDUCTIVITIES Ohms per meter- paa deg. cent Per cent con- due tivity «„ «,. «JO - T " Inferred /v r* ni ab #J& <*» zero ' 0.16108 M 0.00405 0.00381 0.00374 0.00367 0.00361 0.00336 0.15940 M 0.00409 0 00386 0 00378 0.00371 0.00364 0.00340 0.15776 97 0.00414 0.00390 0.00382 0.00375 0.00368 0.00343 0.15727 •97.3 0.00415 0.00391 0.00383 0.00376 000369 000344 -2409 0.15614 M 0.00418 0.00394 0.00386 0.00379 000372 000346 0.15457 99 0 00423 0.00398 0.00390 0.00383 0 00375 0 00349 -236 4 0.153022 100 101 0.00428 0.00432 0 00402 0.00406 0.00394 0.00386 0.00379 0.00352 000390 0.00383 0.00333 -fl 0.15151 0.00398 STANDARDIZATION RULES OF TV/A .4 / R.E. 35 .uuntuy - y >:•-..-:. :n the last column of the above table calt .iture on the centigrade scale at which copper of the par- concerned would have aero electrical resist a nr« -tweenOdeg. cent and 100 deg. cent, applied .-.ly down to the absolute sero. The usefulneas c: erred absolut- :»peruture of resistance" in calculating tem- perature rise is evident from the following formula: */-*/ - ., ' latitude (London), and 550.5 at Washington. The Standards Comm however, recommends that the kilowatt instead of the horsepower be used generally as the unit of power. ADDENDA TO THE A. I. E. E. STANDARDIZATION RULES G. Official Actions of the Turin Congress AND H. Rating of Electrical Machinery in Different Countries Printed by order of the Board ol Director* in Accordance with the Following Resolution Adopted October I 3. 19 1 I . Resolved, that the Secretary be authorized to publnh with the Standard- ization Rules ol the Institute the decisions ol the International EJectrotednical Commission at Turin in regard to standard symbology and the direction for indicating advancement of phase in graphic diagrams of alternating current quantities, and a resume of the principal features of the rating ol electrical machinery of the leading foreign '///(/.! The following appendix, G, coven Che principal official actions of the Turin Congress in 1911 APPi: folio win,- he official action* of the Intern*- 'mission at Tunn in Ittll <«) / '. 1 I nsUntaneous values of : quantum* which vary with the time art* to be represented by small If conitant values <»! « to be represented quantities to be represented by » he subscript " m " be represented • T* of cither . -faced, or of any .HIM values of magn< • be repr* letters of cither svmit. gothic, heavy-faced, or of any special type, followed by the subschi 6. The following quantities to be repress he following I« rce Magnetic force Magnetic flu s'th Mass : K ««•:•-• to represent, respec- force, and the resistance, in the : Ohm's law. 8. I; .ts. the expression " Rca . ; adopted to designate VI sin f . (6) IU.\(,R.\MS H)R A he graphical representation of alternating electric and ma. n phase shall be represented in the counter >cl< E. The impedance of a reactive coil, of resistance R. and induct * /? + \/ ; :-.J that of a condenser of cap;. 1 * /- qual to 2 JT X frequen phase tnple alt- containing an improsseower available at the terminals. he output of electnc motors is defined as the mechanical power tble at the si nc and mechanical powers to be expressed in inter — __- <• --induct; tA» exampW* o- 40 RATING OF ELECTRICAL MACHINERY Appendices H and I give compaiisons of methods of rating electrical machinery, and particularly of D-C. machinery, in different countries, as compiled by the Secretary of the International Electrotechnical Com- mission. See Publication No. 9, " Rating of Electrical Machinery," of the I. E. C. August, 1911. APPENDIX H.— RATING OF ELECTRICAL MACHIM-KY The following are the comparative rules on the rating 01 irrcnt generators and motors as compiled by the General Secretary of the International Electrotechnical Commission from the National Rules of six countries as in force in 1911. These comparative rules have been appended to the Standardization Rules by order of the Board of Directors ol the American Institute of Electrical Engineers, in order to present the extent of agreement or diversity existing on these nil- l''ll, among the leading electrical engineering societies of the world. List of documents from which extracts have been made: BELGIUM. " Prescriptions normales " for the reception of electrical machines and transformers issued by the " Chambre syndicate des Electriciens Beiges " in 1908. FRANCE. General instructions for the delivery and reception of elec- trical machines and transforrm : by the " Union des Syndicats de I'Electricite* " in 1910. Regulations for tenders, supply and testing of electrical machines and transformers issued by the " Association Alsacicnne des Proprie*taires d'Appareils * Vapeur," 1906. GERMANY. Standard rules for the utilization and testing of electrical machines and transformers issued by the " Verband Deutscher Elektro- techniker " in 1910. GREAT BRITAIN. Report of the British Engineering Standards Committee on " Electrical Machinery " issued in 1907. SWEDEN. Rules for the testing and reception of electrical machines and transformers issued by the " Association of Swedish Engineers " in 1909. UNITED STATES. Standardization Rules of the American Institute of Electrical Engineers as contained in its PROCEEDINGS, August, 1911. ANALYSIS OF THE RULES POWER Method of Expressing the Power of Electrical Machines BELGIUM. Generators. Kw. at the machine terminals. Motors. ;anical horse power at the shaft (75 kg-m. per sec.) FRANCE. Generators. Kw. at the machine terminals. Motors. Kw. or horse power at the shaft (75 kg-m. per sec.). GERMANY. Generators. Kw. Motors. Horse power (75 kg-m. per sec. —736 \Y GREAT BRITAIN. Generators. Kw. Motors. B.h.p. (1 Brake horse power -746 W.). SWEDEN. Generators. Kw. Motors. Horse power (75 kg-m. per sec.). TED STATES. Generators. Kw. at the machine terminals. Motors. B.h.p. (746 W.) Preferably in kilowatts. NOTES. — BELGIUM. Motor* usually have their power indicated as " H.P.." with consequent confusion as to which is intended; the English b.h.p. being 746 watts, the " cheval-vapeur " being equivalent to 736 watts. PRANCE. Toe Association Alsacienne still allow* the Poncelet of 100 kg-m. per sec. RATING Of ELECTRICAL MACHINERY 41 RA TING BBLC.I i /niermiitr- In which the periods of work and re«t alter- nale in minutes. In *hi Aork of sufidently short nary trm|x-r.r reached are folio* periods of rest long enough f- ill to »pj h i he prno*U of work are roffi. id to the esu perat FIANCE. : tuoMJ temte. 1 nlfr mtl'.rn! jfrvii >• (1) • 'life. In which the periods of work and rest altet- . tramways, and similar ap- paratus.) VAor/ period service. In which the periods of work are not sunV .: for the final (rated) temperature to be reached, whi - of rest are long enough for the temperature to fall to approxt- mat« f the surrounding air. In which the periods of work are suffi< r the final temperature (rated) to DC attained. GBEAT B*n MS nttous working. The -rs and motors for king shall be the output at wi. can work con- tinuously for six hours and conform to the prescribed tests, and th- 1 as the Rated Load. Iniermtitent working. The output of motors for intermittent output at which they can work for one hour and prescribed tests, and this output shall be defined as the Rated Intern; id. SWEDEN. In which ti. iture reaches stationary In which the working periods do not exceed one hour or alternate with intervals of rest of a similar length. KS. 1 < > ttnuous ru/iMf. In wrmh. under load, there is the attainment nary tern per at Intermittent rating. In which one minute periods of load and rest ite until the attainment of approximately stationary conditions (3) Minute rating. In which, under load for one minute, no limit of capacity is exceeded, and no permanent change is wrought in the apparatus Variable service, rating. Not yet defined. Noras.— PBAMCB. The A* BRITAIN. The reajon for thr " vi hour* " in the workmt " i« due to the fact that the CoJnmtttec >cv, 2 i •«•' •** il a»tbai ipactei ftandardiutton b*inf to aaaUt the manularturr' d >r* pot include nMrhiaa* ninmnc from •Mfc.ead u H M mf : • - - itpot radar cxmtia^oaa atrrice is deftaed aa that o«t do *o abor*» I on brim to MriM the maoof* • voold •rartetr par to .000 kw. SAT1 rated ovtpat ined continoootlr for aa hour without the tavavmttnv u RATING OF ELECTRICAL MACHINERY NA ME-PLA TES Information to be Stated on the Name-plates BELGIUM. Service recognized (intermittent, momentary, for hours, or continuous). The rated values of the power, the pressure, the current and the angular speed. FRANCE. The power for which the machine has been sold. It is expressed thus: For generators, in kilowatts at the for motors, in kilowatts, or horse power of 75 kg-m. per second, available at the shaft. Additional information to be stated: For continuous working, the rated values of the speed in revolutions per minute, the pressure, and the current; for variable working, the limits of pressure and current; for intermittent working (traveller, crane, lift, etc.) the power for a period of one hour, mentioning " intermittent working." GERMANY. The power for generators to be stated in kilo\\. Mechanical power to be stated in kilowatts or in horse power In addition, the name-plate on which the power is stamped, or a special name-plate, must indicate the rated value of the number of revolutions, the pressure and the current. The name-plate must also indicate the rating: " Intermittent," or " For hours," or " Continuous." GREAT BRITAIN. Unless otherwise stated, the output is to 1>- sidered to apply to continuous working. In the case of intermit tint rating the word " Intermittent " is to be added. The name-plate shall also indicate: For generators: K\v., amperes, rev. per min. For motors: B.h.p., volts, amperes, rev. per min.; B.h.p (Intermittent), volts, amperes, rev. per min. SWEDEN. Unless otherwise stated, the output shall be considered as applying to continuous working. The values stated on the name-plate shall be in conformity with the rules, except it bear the indication " For special purposes." The following information to be stated: For generators: the kilowatts, volts, amperes, and revs. per minute. For motors: the mechanical power, the volts, amperes, and revs, per minute. N. B. — The speed shall be the speed with the machine hot. and a tolerance of ± 7% shall be allowed. The service, adding the words: " For continuous service." " For Intermittent service." For variable service, the respective limits shall be given. UNITED STATES. Name of the maker, volts, amperes. When practicable, the kilowatts, the revs, per minute, the type, the character of current, designation and serial number. COMMUTATION BELGIUM. Under all conditions not exceeding the rated load, the commutator of a machine shall not require to be cleaned or given other attention more than once a day, with the brushes remaining in the most favorable position. FRANCE. Union dfs Syndicate de L'ElectriciU. Under all loads included in running free up to the rated load, the brushes being ground and fixed in the most favorable position by means £>f a previous run, machines with a commutator must be capable of working for the period of the test (specified under Heating: Duration of Test,) without it being necessary to glass-paper the commutator or resort to any other method of cleaning. Association Alsacienne. Unless otherwise specified, when once the brushes have been adjusted in the most favorable position, machines with commutators shall be capable of working, without appreciable sparking or adjustment of brushes, at all loads from no load to rated load, even with sudden changes of current. RATING OF ELECTRICAL A/.U 7//.\ h.RY Und« lous workinf. »nJ at any load within the prescribed hail be such as to require at ten* r lubric.r r vaU of twelve hour*. Thit cleaning 'y at i •» also applies to collector rings. Oik "nder all conditions of load from one quarter up to the load, and wit ng produced must be so negl -ing attention. The brushes to be gr»ung. the position of the brashes may be altered. The working j>« rushes is to be indicated. ist carry the specified overload us sparking or mechanical weakness. OVERLOAD percentages given below imply an overload in excess of the rated load marked on the name-plate. BEL- -r continuous service. 20 per cent of the rated load for <>d equal to one-fifth of the duration of the heating test, with a max i nun: .ur. unttent service. 20 per cent of the rated load for one-fifth of an hour. For momentary service. 20 per cent of the rated load for a period equal to or marked on the name-plate. 40 per cent of ted load for 3 inn. • t to be applied at the close of the rated load test. All mat '• • be capable of withstanding, without deterioration or au{ .f the rated load for one-tenth of M of the test for continuous working; 30 per cent of the rated load for 5 minutes. •tent service: 25 per cent of the rated load : minutes; 30 per cent of the rated load for 5 minutes. GERMANY. For generators and motors: 25 per cent of the rated load for half an hour. >n (constant potential) : 40 per cent of the rated loa : minutes. M HKI i MS , , 11 f Mint <^ Conclusion of OttrtoaJ 1 SWEDEN. 25 per cent in excess of the rated current without injurious sparking. Adjustment of brushes permitted. i ED STATES. For generators: 25 per cent of the rated load '. u motors (continuous working): 25 per cent of the rated load for 2 hours; 50 per cent of the rated Toad for 1 minute. Norss.— Bsumrn. Tbt machine matt b* capable of •MUbrintf tk una« UN MtiUd pori I --.•..,-, • • • . --.,••. • . . •-.• cloM of UM rmted load te.t . In which c**» UM rtor te temperature mat act eareed the limits pmcnbed for UM rated IOM! by nor* than 10 d««. e««U For motors intended to work for prolonged period*. M owrload ir»t of 40 pv <«rt for three mtouu». All motor* mart be ctptbte of withMaMJat M iocrr**. of 90 ptr for .period of fiv» mioatM. The owrkMd twt b to be •pplted without rvferm n*e. And it r^iifl be commenced with ttM nit^fne At toch a tejnponk " — mil ••Trill innil. gwamln mi In niiiMi uf • with an overlo»d oTlS percent n RATING OF ELECTRICAL MACHINERY VARIATION OF PRESSURE AND SPEED BELGIUM. Generators. The pressure variation of a generator is 1 by the greatest difference observed, at constant speed, between any two values of the pressure corresponding with loads, the current of which does not exceed that defined by the rated load, the ; la-ing regu- at this current, to the rated load value. The brushes to remain adjusted in the working position. i . — The excitation of a generator, intended to work at constant pr« mu*t be capable of maintaining the rated value of the pressure under normal en: of angular speed, at all loads from no load up to and including l.l.'i times the rated load Motors. The speed variation is defined as the difference in angular speed at rated load and at no load at normal working pressure, and with- out a "f field rheostats adjusted for the rated load. FK\XCE. ne rotors. The pressure variation shall be measured in passing from the rated load to no 1« nt speed, in the case of self- S machines, whilst maintaining constant the resistance in the field circuit; in the case of separately excited machines, whilst maintaining constant the exciting current. During this test, and unless oil. specified, the brushes shall remain fixed in the rated load sparkless position. Motors. The speed variation shall be measured in passing trom the rated load to no load, with constant pressure at the terminals. GERMANY. At constant rated load speed and excitation, the pressure to be observed at, at least, four points practically equidistant on the load curve. The greatest difference between the observed press^: a measure of the variation. In regard to the adjustment of brushes, the conditions are to be governed acco-ding to the rating. GREAT BRITAIN. DEN. At constant rated load speed ang temperatures above 125 def . cent. Machines in which such materials are employed are dealt with separate A much higher tcmjx-ruiure rise than that specified on PA, may be permitted in machines in w is secured by meant of special materials designed to resist high temperatures, but the amount of permit Must depend on the properties of the insulating materials and the method of construction and most be settled specially for each clas* SWEDEN : out as nearly as possible under ordinary working conditions. •.<•rnp.-r.i-ur. allowed must not be such as to be detrimental to the insulation under ordinary working conditions. An overload may be a; horten the duration of the test. BELGIUM. By increase in resistance, if this method is practicable. Otherwise by means of thermometers. PRANCE. Temperatures ascertained by means of thermometers, placed in the hottest pan accessible; nevertheless, in the case of • •» and all stationary windings, the temperature may be by increase in resistance. GBK ng coils and stationary windings by increase in resistance, other parts by thermomf GREAT BRITAIN. Stationary windings by increase in resistance. Moving coils by increase in resistance, if possible, otherwise by ther- mometer or thermo-couple. Commutators, brushes, bearings by ther- mometer. SWEDEN. Windings by increase in resistance, if possible, otherwise by thermometer. Other parts by thermometer. i ED STATES. By thermometer. Conductors by rise in resistance, when possible. Duration of Test Continuous service. A period of sufficient duration to attain a prac- tically constant temperature: ordinarily 5 hours up to 20 kilowatts. 8 hours above 20 kilowatts. Intermittent servic*. One hour. Momentary tervice. The number of hours indicated on the name-plate. PRANCE. Continuous working. \ period sufficiently long to attain a prac1 constant temperature. ',S« Intermittent servtte. One ! Tb* periods art tivm. to * t*ocr*l m*ao«r. by Uw foOowtaf labto: K m Volti X Ampcr*. K ' Rrr.prr : 10... 2 hour. 10-30.. • m TUO-l.OOO . 100-200.. i.ooo-i.aoo . 10 Abor. l.io • mica, asbestos . O rtpUtt • • mmtator* . . . '•" Bearing • I KH. •nature windings. Commutators an«l brushes .'»."• Bearings and other parts . 40 ~Porlar*«maohhM».a Umpwatar* limit of 404*. cart, wrtw rated Ioa4 condition* and 55 d»«. «*m. muter ovwtoad u (r*qo»ntly K~ct< nature or method of using the ma. ceeding this figure, in which case the excess must be 100 per • PRANCE. Generators must be capable of withstanding a morm ••a«e in speed to | ase. according not or* n. standing, during five minutes, a speed of 20 per cent in excess of the r .,,-, i • •tors must be capable of withstanding, a speed of 3<> in excess of the rated apted. Gut" .led to work ,. ally con- must be cap * during five minute*, a Speed < in excess of the rated speed, first * . \r Hkii N SWEDEN. Machines must be capable of withstanding a speed of 20 per cent in excess of • speed. Generators driven by hydraulic turbines, unless otherwise specified, must be capable of withstanding a •peed of 00 per \cess of the rated speed. t MTBD STATES. El cT *dtttO*S BELGIUM. The n determination is to be specified. Unless « to be ascertained at rated load and under the corresponding conditions as to temperature. liower absorbed in the i. • .its of a machine is to be included as part of the power • the machine. In the case of a of the machine and that « • exciter, shall be separately stated. PRANCE. The eft. us should be made at. or reduced to. the temperature attu: >se of the working test. The efficiency shall be state rated load, three-quarters and half load, and is to include the !•••—• line •• •' :y apparatus such as ex -tla- tion. :ig pumps, forming an integral portion of the plant. GBRV ,-tit as to U. y applies to the rated load and the s of serv rs ts to be mentioned. The power absorb- a and in ihe rheostats must be consid* as losses for • •• of the unless otherwise stated the power absorbed in cooling the machine must also be considered as a loss, Por which are specially excited, the efficiency of the two machines must be stated separat. GREAT BRII •• SWEDES. The losses in excitation and in the rheostats are to be in* Friction losses are only to be included in the case of machines with automatic lul Losses due to an el are to be excluded. The cfliv ts are to be made <* mperaturv attained by the machine at the close of the rated load test and referred to a surrounding air temperature of 20 deg. cent. t'siuj) Si MRS. The test is to be carried out under ordinary work- ing conditions and with the surrounding air at standard temperati: In the case of belt-driven machines, the loss of power in belts and the increase of bearing friction, due to the increase of belt tension, is to be excluded. RATING OF ELECTRICAL MACHINERY In the case of a generator inseparable from its prime mover, bearing friction is to be excluded. The losses in exciters or in auxiliary apparatus are to be considered separately, and charged t<> the plant consisting of the machine toge' ;>pnratus. The plant efficiency is to be distinguished from the efficiency of the machine alone. The of a machine is to be me > reduced to, the temperature which the machine assumes under i load conditions, referred to a surrounding air temperature of 25 deg. cent. Method ALL Cot SIKH.-. D i< tly by input output, where possible. Indirectly by losses, if the direct method is not possil Enumeration of Losses BELGIUM. FRANCE. ^inical. (a) Bearing friction and ventilation. (6) Friction of brushes on commutators and collecting rings. Electrical. (c) Hysteresis and Foucault currer (d) Joule effects in the circuits. GERMANY. The losses are not enumerated in tabular form. GREAT BRITAIN. SWEDEN. (a) Bearing, brush and air friction. (6) Hysteresis and Foucault currents. (c) Ohmic losses in armature. (d) Ohmic losses in brushes. (e) Ohmic losses in exciting coils. UNITED STATES. (a) Bearing friction and windage losses. (b) Molecular magnetic friction and Foucault current losses. (c) Armature resistance losses. (d) Commutator-brush friction loss. (e) Brush and brush-contact resistance losses. (/) Field excitation loss. (g) Load losses. NOTES. — FRANCE. Association Alsatienne includes under electrical losses brush con- tact resistance. UNITED STATES. (/) Losses may be considerable with carbon brushes in low voltage machine*. <<> Difference between total lostes under load and sum of losses as here specified. DIELECTRIC TESTS General Conditions of Test • iiUM. Dielectric tests take the place of insulation tests unless the machine is intended for localities in which special conditions are imposed. The test is to be carried out before the machine is put into actual service. The repetition of the test is to be avoided. The test is to be carried out hot. The windings of machines and transformers must be capable of with- standing, for a period of half an hour, a working pressure of 30 per cent in excess of the highest pressure of the service. FRANCE. The test of the insulation is to be carried out hot, when possible, and shall only be made in the works of the manufacturer. The test pressure is to be applied gradually. The circuits of ma- chines and transformers shall be capable of withstanding, without undue strain, for a period of three minutes, a pressure 30 per cent in excess of the ordinary working pressure, provided no mechanical or electrical considerations are against it. RM1XG OF ELECTRICAL MACHINERY 51 GERMANY. The tests, when possible, are to be carried out at the works of the manufacturer. They are not to tw repeated e*cept in very e». nal cases. For large machine* the test is to be repeated, tm >i/». •h. ma. ; actual servtce. tie carried out h«.r M capable of withstanding, dunng fivr minutes, a pressure JO per c excess of the rated pre» M llMIMIN. — — SWRI>RK. The test to be earn. •! ..tii IN In gnu : • Ihr .ul ami » Msembl< !ry and free from «! /j of Application of Iht Vrt>\*rt N IKIES. The various rules spc teat pro* cd between windings and the frame and between all electric •,r» of tkf 1 But VMCB. (U •• WKIIKS. The values of the tact pres- m«ltcated are appl cases in ••• is sin t* mtrn.i :>t work ! ;>rc*sure shall be u specified. riding* it .nng current work »*e itinuous current, the test pressure shall be 1.4 times that spa Uk •'. .tor employed for the test shall be as m-.irlv .is pCM toll I lM 99199 GREAT BRITAIN. is. The test is to be carried out with alternating t * at the normal frrqm-ncy «-f the aupar.i The values herein given are the root mean square values of the test pressure r< a sine wave form. The wave shape of the test pressure should be as nearly as possible sinusoidal, and should not be materially distorted by the testing . BELGIUM. king Pressure. Test Pressure. I..- th.i:. 300 v. 4 times the working pressure + 300 300- 600 v. - + GOO v. 600- 1.200v. 2,400 v. - 5,000 Twice the working pressure. 5,000-10,00" The working pressure + 6.000 At 10.000 v. l.A times the working pressure. FRANCE. Rated Pressu Tot Up to 5,000 v. Prom 5,000-10.000 v. Aln KK)v. Up to 5.000 v. From 5.000-10.000 v. Above 10,000 v. (Twice the rated pressure minimum of IK' «ure + 5.000 1.5 times rated presst: (Three times the rated pressure with minimum of 500 Rated pressure + 10.000 v. Twice the rated 52 RATING OF ELECTRICAL MACHINERY GERMANY. Rated Pressure. Pressure. Above 10 \. At least 110 v. Prom 5,000- 7,500 v. The workim: DO T, Above 7,500 v. Twice the working GREAT BRITAIN. SWEDEN. Working Pressure Up to 3,300 v. .'t times tin- working with a mini- mum nf 7<) v. 400 v. and above, but less than MM) v. Under 10 kw. 1 :.<)0 v. 10 kw. and over. »0 v. 800 v. and above, but less than I.Jnov Any po ") v. 1,200 v. and above, but less than 2,500 v. 5,000 v. 2,500 v. and over. Double the normal rated voltage. Length of Test BELGIUM. 30 minutes. FRANCE. 30 minutes (hot) ^ j (Associtllillt, Ahaficttnrt ;, minutes). GERMANY. 1 minute. GREAT BRITAIN. SWEDEN. At least 1 minute. UNITED STATES. 1 minute. APPENDIX I. HE A TING (see p. 43). STIPULATION OF THE MILAN CONGRESS (September, 190G). The heating of a motor is to be considered as excessive when, starting from a surrounding air temperature equivalent to 25 deg. cent., the motor, after 10 hours' working at its permanent power or after one hour working at its normal power, attains a final temperature exceeding that of the surrounding air by the following values: (a) For windings insulated with cotton 70 deg For windings insulated with paper 80 " For windings insulated with mica, asbestos or m substances presenting the same qualities of in- sulation and incombustibility H»> " (6) For commutators . . 80 " (c) For metallic portions in which the windings are cm- bedded, the value corresponding to that indicated for the windings, according to the insulation em- ployed for the latter. When the windings are in - ith a combination of insulating materials, the lower limit will be taken. ... By permai r and normal power of a motor is to be understood that power which, the current being furnished at the normal pressure of supply, can be developed by the said motor during 10 consecutive hours, in the first case, and during an uninterrupted period of one hour, in the second case, without the heating being excessive in the sense indicated under the paragraph as to " Heating." RATING OF ELECTRICAL MACHINERY i REGARDS GUARANTEES Us: it OK !/Ki.Ki me The following table fixes: i ' Tolerance allowed for error* A in, h i he question a* to re, - ASSOCIATION ALSACIBNKI As acceptance of the various guarantees given, it i» usual to fix *.«•< limits, the first representing the permissible tolerance to allow for inex- : ies and errors of measurement, the second giving to the buyer the right to reject the material. Between these two limits it is usually a question of penalties in proportion to the deviation from the The penalties for the different guarantees are cumula The following values are to be recommended: M to :.-,.-.-. ^ . 4 dcf . emu above limit* nf. ftied (for rMJitinrn 10 only). ' . - 16% of UM Auto- tuanuiuod by DM ;-w teH 40%ofUM * rr ; '• ' 4»' 16% of UM MUB of tkt 40% of UM Bfldncy. IOOM*. total or »bl«. »i thr CAM m*> b* PLEASE DO NOT REMOVE CARDS OR SLIPS FROM THIS POCKET UNIVERSITY OF TORONTO UBRARY IM A 134